Daikin Hybrid Cassette 20-3-2014 PCSAU0739C

PCSAU0739C
Air Conditioning Systems
FCQN-KVEA + RQ-LV1A
HEAT PUMP [50Hz ]
!!
w
o
l
f
air
360 °
CEILING MOUNTED CASSETTE TYPE
Round Flow
Uniform 360 airflow cassette air conditioner
is setting tomorrow's standards.
Option
Accessory required for indoor unit
Wired Remote Controller
"Nav Ease"
BRC1E61
Note: Remote controller cable not
included. Cables must be
procured locally.
Wireless LCD remote controller
A signal receiver must be added to the indoor unit.
Heat pump
BRC7F632F
Signal receiver unit
(Installed type)
Wireless remote controller and signal
receiver unit are sold as a set.
PRODUCT RANGE
Series
71
100
125
140
FCQN71KVEA
FCQN100KVEA
FCQN125KVEA
FCQN140KVEA
INDOOR UNIT
CEILING MOUNTED
CASSETTE TYPE
Round Flow
NEW
NEW
OUTDOOR UNIT
RQ71LV1A
1
RQ100LV1A
RQ125LV1A
RQ140LV1A
Avoids uneven temperature and discomfort caused by drafts.
Comfort enhanced by Round Flow!
Air movement is gentle
360 ° airflow
with Round Flow
With uniform temperature
distribution
Enhanced Comfort
Airflow
distribution
creates uniform
comfort throughout
the space
360° airflow can
maintain comfort
even if air
discharge speed is
lower.
If you raise the set
temperature by 1 to
1.5 in cooling (and
lower in heating),
and velocity is decreased
by 25%, you still obtain
the same feeling
temperature and comfort.
Greater comfort
Adapts easily to the installation space.
As air flows out from corner outlets, comfort spreads more evenly.
Typical flow patterns
There are a total of 23 flow patterns.
All-round flow
3-way flow
(E.g., installed in
middle of ceiling)
(E.g., installed
near a wall)
L-shaped
2-way flow
(E.g., installed in
a corner)
Opposite
2-way flow
(E.g., installed in
a long room)
4-way flow also possible.
Note: Whatever the discharge direction, the same type of panel is used. If installing for other than all-round flow, an air discharge outlet sealing member (option) must be used to
close each unused outlet.
Operation sound increases when using 2-way or 3-way flow.
Grime prevention and bactericidal coating: Makes cleaning easier.
External panels are treated with a coating that helps to
Treated
Untreated
repel dirt.
surface
surface
To prevent dirt sticking to the
external panels, they have
been coated with a surface
treatment.
Resists
soiling
Grimy
surface
• Condition after exposure
to the smoke of 600
cigarettes in 1 m3
enclosed space.
Bactericidal treatment for
drain pan
Non-flocking horizontal louvres
Filter has anti-mould and
bactericidal treatment
Anti bacterial treatment, that includes
silver ions is used which may assist in
preventing the growth of microorganisms
that cause smells and clogging.
Dew does not easily form on the nonflocking louvres and may prevent dirt
from clinging to them. It is easy to
clean.
Helps prevents mould and
microorganisms growing out of the dust
and moisture
that adheres to the filters.
2
CEILING MOUNTED CASSETTE TYPE
Unified square panels
Round Flow
Compact body and quiet operation
dB(A)
Panel size is the same for all models, FCQN71-140K.
It is easy to maintain a neat appearance when multiple
units are installed in the same room.
950
mm
Indoor unit
High
Low
71K
35
43
44
44
28
32
34
36
100K
95
0m
125K
Same for
all models
m
140K
Optimal comfort and convenience
assured by air discharge modes
Note: Air direction is set to the standard position when the unit is shipped from the factory.
The position can be changed from the remote controller.
Air direction
Desired
situation
Auto-swing
Standard setting
Setting to prevent soiling of ceiling*
Standard setting to
prevent draft.
Recommended for shops with
light coloured ceilings that
must be kept spotless.
Note : Anechoic chamber
conversion value, measured
according to JIS parameters
and criteria. During
operation these values are
somewhat higher owing to
ambient conditions.
Quick and easy to install
Just 256 mm high. Installable in tight
ceiling spaces (71K)
256 mm *1
265 mm *2
*1 298 mm high with 100K–140K
*2 303 mm high with 100K–140K
Auto-swing between
15° and 60°
Auto-swing between
25° and 60°
Easy height adjustment
5-levels
air direction
setting
Settable to 5 different
levels between 15° and 60°
Settable to 5 different
levels between 25° and 60°
Draft prevention
(In heating mode)
At heating startup and thermo OFF, air discharge
is automatically set to a near horizontal 25˚ or 30˚
to prevent direct exposure to cool air drafts.
Auto air
direction control
The air direction is set automatically to the
memorised position of the previous air direction.
*Closing of the corner discharge outlets is recommended.
Note: If the wireless remote control option is installed, a light receptor
unit is housed in one of the adjuster pockets.
All models can be installed without
using lifter because of the light weight.
Can be installed in
any direction
Suitable for high ceilings
Even in spaces with high ceilings, a comfortable airflow is carried down to
the floor level.
Criteria for ceiling height and number of air discharge outlets
Number of air discharge outlets used
Standard
Ceiling
High ceiling
height
High ceiling
Each corner of the unit has an Adjuster Pocket that
lets you easily adjust the unit's suspended height.
71K
100K–140K
All round 4-way 3-way 2-way
flow
flow
flow
flow
All round 4-way 3-way 2-way
flow
flow
flow
flow
2.7 m 3.1 m 3.0 m 3.5 m
3.0 m 3.4 m 3.3 m 3.8 m
3.5 m 4.0 m 3.5 m -
3.2 m 3.4 m 3.6 m 4.2 m
3.6 m 3.9 m 4.0 m 4.2 m
4.2 m 4.5 m 4.2 m -
Note: Factory settings are for standard ceiling height and all-round flow.
High ceiling settings (1) and (2) are set with the remote controller.
Two selectable temperature-sensors
Both indoor unit and wired remote controller (option (BRC1E61) ) contain
temperature- sensors. Temperature sensing can be set at the unit or, to
further improve comfort level, closer to the target area at the wired remote
control. This feature requires initial setting by the installer.
*Temperature-sensor on indoor unit must be used when the air conditioner is controlled from another room.
**Wireless remote controller does not have a temperature-sensor.
Since the orientation of
the intake grill can be
adjusted after installing,
the direction of the intake
grill lines can be unified
when multiple units
are installed.
Drain pump is equipped as standard
accessory with 850 mm lift.
850 mm
175 mm
Transparent drain
socket
Hot start (after defrost)
Switchable fan speed: High/Low
Timer selector
3
Easier connection with the centralised
control system
Low gas pressure detection
Easier to maintain
The condition of the drain pan and
drain water can be checked by
removing the drain plug and
intake grille.
e
en th !
p
o
t
e
Jus ke grill
inta
Drain plug
Options required for specific operating environments
High-efficiency filter
Panel spacer
Available in two types: 65% and 90% colorimetry.
Use when only minimal space is available between drop
ceilings and ceiling slabs.
Fresh air intake kit
Using this kit, a
duct can be fitted
to increase the
intake of outdoor
air.
Outside
40mm
Panel spacer
Note: *Connecting ducts, insect nets, fire dampers, air filters, and other
parts should, as required, be procured locally.
**Outside Air fan interlocked with air conditioning unit is necessary.
Optional PCB(KRP1C63)is required for interlocking.
***It is recommended that the volume of outdoor air introduced
through the kit is limited to 10% of the maximum airflow rate of the
indoor unit. Introducing higher quantities will increase the
operating sound and may also influence temperature sending.
Note: Some ceiling constructions may hinder installation.
Contact your Daikin Dealer before installing your unit.
Sealing member of air discharge outlet
Sealing members block air discharge openings not used in 2way or 3-way blow.
Branch duct (direct-connection round duct)
A round duct can be attached without the need for a chamber.
A flanged port for direct connection of a round duct is
provided. An existing branch duct chamber can also be fitted
(square slit hole).
The units can be installed in the following different ways.
Chamber type
(without T-joint pipe and fan)
Chamber type
(with T-joint pipe and without fan)
KDDP55B160
KDDP55B160K
Flexible duct
(procured locally)
Flexible duct
T-joint pipe
(procured locally)
T-joint pipe
Suction
chamber
Intake duct
Connection (procured locally)
chamber
(duct length: 4 m max.)
Suction
chamber
Intake duct
Connection (procured locally)
chamber
(duct length: 4 m max.)
Direct installation type
KDDP55X160
Duct flange
(with insulation
material)
Intake duct
(procured locally)
Note: Use of options will increase operating sound.
4
OUTDOOR UNIT
Compact Outdoor
Unit for Round Flow
Cassette
NEW
RQ71LV1A
NEW
NEW
NEW
RQ100LV1A
RQ125LV1A
RQ140LV1A
Easy installation and maintenance
Durability
Pre charged for up to 30 metres
As the bottom frame is subject to corrosion,
a corrosion-proof galvarium steel plate is
adopted to enhance the durability.
If refrigerant piping length does not exceed
30 m, there is no need for on-site gas
charging.
50 m piping length
Allowed refrigerant pipe length and
level difference
Pre charged
*1
Max. length
30 m
Equivalent length
4-direction piping offers greater
layout freedom
The outer panel for the piping connection
part of the front, right side and backside
can be removed
and is easier for
post-installation
piping work.
Separation
available
Max. level
difference
Heat exchange fins are provided with anticorrosion treatment
Construction
Non-treated fin
Aluminium
Anti corrosion
treated heat
exchangers
Hydrophilic film
Aluminium
Corrosion resistant
acrylic resin
50 m
50 m
RQ100L
30 m
Equivalent length
30 m
70 m
50 m
RQ125L
30 m
Equivalent length
Facilitates pump down
(Refrigerant recovery function)
A pump-down switch is provided to make
it easier to collect refrigerant if the unit is to
be moved or layout modified.
30 m
A coating of 40 m or more protects the
outside unit from exposure to rain
and snow.
*Pump-down function is available for pre-charged
refrigerant amount.
70 m
50 m
RQ140L
30 m
Equivalent length
30 m
70 m
Note: 1Additional refrigerant charging is required if the
refrigerant pipe is longer than the length.
Low gas level detection function
Effective gas monitoring reduces the labor
required for operation, maintenance, and
repairs.
Coating
30 m
70 m
Casing net plate
RQ71L
Average
40 m
or more
Outside air
Compact and light weight
Height(mm)
Width(mm)
Depth(mm)
Weight(kg)
71L
770
100/125/140L
1,170
900
320
68
98
Operation range
Suited for year-round cooling
applications
Cooling is efficient even in winter when
indoor temperatures are higher than those
outside, such as in underground public
spaces or offices with many computers.
The maximum capacity is maintained
within a set level of power
consumption, which makes it possible
to keep a comfortable and effective
demand control.
Wide operation range
50
40
46˚CDB
Limitation
30
20
Cooling
10
0
-5˚CDB
-10
15.5˚CWB
CWB
Heating
-10˚CWB
CWB
8:00
-20
Outdoor temp(˚CDB)
5
Demand Control
Function
Power
consumption
Easy centralised installation
with the module oriented design
Outdoor temp(˚CWB)
12:00
* Required for KRP58M51 (Option)
16:00
20:00 Time
Night time quiet operation function
The Automatic night quiet mode will initiate 8
hours after the peak temperature is reached in the
daytime, and normal operation will resume 10
hours after that.
Peak in outdoor temperature
1
Reducing noise will reduce capacity slightly.
Night Quiet Mode
RQ71L
49
45
RQ100L
51
46
RQ125L
51
46
RQ140L
52
47
100
8 hours
50
Load (%)
Operation
Sound (dB(A))
Rated
2
Capacity (%)
Sound level (dB(A))
Note : 1Anechoic chamber conversion value, measured according
to JIS parameters and criteria. During operation these
values are somewhat higher owing to ambient conditions.
2
Value when cooling. Value will differ when heating.
0
58
Rated
50
Quiet mode
Quiet mode
8:00
12:00
Technology
for efficient
and quiet operation.
1
10 hours
16:00
20:00
0:00
4:00
8:00
3
2
Scroll compressor
(RQ100/125/140LV1A)
Smooth running, minimal
vibration, low operating
noise
1
4
RQ71LV1A
Swing bushing
Refrigerant gas
>> Swing compressor
3
DC fan motor
Efficiency improved in all areas compared to
conventional AC motors, especially at low speeds.
Energy savings is realised,
eliminating the friction and
the leakage of refrigerant
gas.
DC fan motor
structure
Piston by incorporated
blade and roller.
RQ100LV1A/125LV1A/140LV1A
Suction
>> The structural scroll
DC motor efficiency
2
(comparison with a conventional AC motor)
100
Scroll section
Efficiency (%)
Sucked gas is compressed in the
scrolling part before the heated
motor, so that the machine
compress the non-expanded gas, Discharge
resulting high efficiency compression.
Motor section
Smooth Air Inlet Bell Mouth and
Aero Spiral Fan
These two features work to reduce noise. Guides are
added to the bell mouth intake to reduce turbulence in
the airflow generated by fan suction. The Aero Spiral
Fan features fan blades with the bent blade edges,
further reducing turbulence.
With the bent
blade edge
80
DC motor
60
Approx.
20%
increase
40 Approx.
AC motor
40%
20 increase
0
200 300
400 500
600
700 800
Note:
Data are based on
studies conducted
under controlled
conditions at a Daikin
laboratory.
900 1000
Motor speed (rpm)
4
Super Aero Grille
The grill is shaped to match the direction the fan blows
in order to tame the wind turbulence.
Without the bent
blade edge
Escaping eddies are sucked in by
the bent blade edges, reducing
overall turbulence.
6
LCD REMOTE CONTROLLER
Optional accessory
Easy-to-read LCD remote controller allows vario
can control multiple indoor units.
Remote controller options are shown on the page introducing each indoor unit model.
Wired Remote Controller
"Nav Ease"
Clear display,
Simple operation.
This advanced, yet simple and modern remote
controller, makes operation easier by simply
following the indications on the new remote
controller.
BRC1E61
Clear Display
Dot matrix display
Simple operation
Large buttons and arrow keys
A combination of fine dots enables various icons
and texts to be displayed smoothly. Large text
display improves readability.
Large buttons and arrows keys
for easy operation. Basic
settings such as fan speed and
temperature can be intuitively
operated. for other settings
just select the function from the
menu list.
Backlight display
Equipped backlight helps
operating in dark rooms.
Guide on display
The display gives an
explanation of each setting
for easy operation.
Available in 10 languages
Multilingual display
Display is available in 10
languages.
7
us system control configurations and
Weekly schedule timer
Other Features
The weekly schedule timer can
be easily programmed.
Up to 5 ON/OFF settings can
be set per day for each day of
the week.
Off reminder timer
The off timer becomes effective automatically every
time the operation button is pushed.
Can preset the operation period from 30 to 180
minutes in 10 minute units.
Any daily programs set can be
replicated to occur on any other
day by simply using the copy
function.
Error code / model name display
If an error occurs, the error code, model name and
contact address are displaied.
*Contact address need to be registered at the installation.
*Model name or model code will be displayed depends on the model.
The temperature can be set for the ON setting, this
makes it possible to change the set temperature
automatically at a specific time during operation.
Example of setting for an office (in summer)
28
Set temp.
27
(˚C)
26
Time
Operation
12:00
13:00
16:00
17:30
28
OFF
26
28
OFF
25
24
AM
PM
23
8:30
12:00 13:00
16:00
17:30
LCD wireless remote controller
The wireless remote controller is supplied in a set with a signal receiver.
Signal receiver unit is contained inside decoration panel or indoor unit.
Shape of signal receiver unit differs according to the indoor unit.
Note: The signal receiver unit shown in the photograph is for mounting inside the decoration panel of the ceiling
mounted cassette type.
Signal receiver unit
(For ceiling mounted
cassette type)
BRC7F632F
Wireless remote
controller
SkyAir shares common control with the Heat Reclaim Ventilator
and other Daikin air-conditioning units, thus simplifying
interlocking operations.
SkyAir
Indoor unit
Interlocking
LCD remote controller
for SkyAir indoor unit
Heat Reclaim
Ventilator
8
Simple system provides a diverse assortment of control modes.
Control pattern
Control by 1
remote controller
LCD REMOTE CONTROLLER
Wired remote controller
Wireless remote controller
(Basic system)
Non-polar, double-core
(max. wiring length 500 m)
Control by 2
remote controllers
Group control
For control from 2
locations such as in
room and control room,
exits, etc.
For simultaneous
control of up to 16
indoor units.
Signal receiver unit installed
on indoor unit
Connects 2 wired
remote controllers
Not possible
Automatic address setting function
Automatic address setting function
Signal receiver unit installed
on 1 indoor unit
Control by
external command
Operation and
surveillance is carried out
using the contact signal
from the operation control
box in the building
surveillance (security)
room.
Optional wiring adaptor for
electrical appendices is necessary
Optional wiring adaptor for
electrical appendices is necessary
Central remote controller (option)
Centralised remote
control
Central remote controller (option)
Centralised control of
up to 64 indoor groups
from remote location
up to 1 kilometer away.
Optional SkyAir series interface
adaptor required.
Optional SkyAir series interface
adaptor required.
Heat Reclaim
Ventilator
Link by remote
controller group control.
Interlock control
with Heat Reclaim
Ventilator
Heat Reclaim
Ventilator
Can be operated simultaneously
or independently by remote controller
(set by ventilation mode)
Can be operated simultaneously
by remote controller
(set by ventilation mode)
Central remote controller (option)
Zone link control by
centralised control.
Central remote controller (option)
Heat Reclaim
Ventilator
Heat Reclaim
Ventilator
Heat Reclaim Ventilator for indoor units within a zone are operated by
interlocking. Can also be operated independently by remote controller.
Heat Reclaim Ventilator for indoor units within
a zone are operated by interlocking
Note: When a wireless remote controller is used, remote control by two remote controllers is not possible.
Easily adaptable to large-scale, high-function, centralised remote control system.
Central remote controller
DCS302CA61 (Option)
Unified on/off controller
Schedule timer
DCS301BA61 (Option)
DST301BA61 (Option)
Centralised control, with a setting as
simple as it is with a standard
remote controller, of up to 64 groups
(1,024 indoor units) is possible.
Centralised control of on/off by
group or all at once for up to 256
indoor units.
Interface adaptor for SkyAir series
Enables centralised control via connection
to a high-speed, DIII-NET communication
system, adopted for the Daikin VRV system.
DTA112BA51 (Option)
Unified control of weekly schedule
for up to 1,024 indoor units.
Schedule timer sets on/off time in 1 minute units
to be executed twice a day for a week at a time.
Necessary for interface adaptor for SkyAir series with the
central remote control units shown at above.
9
DCS601C51 (Option)
With its high functionality, the full
colour “all-in-one” graphic controller
facilitates management of SkyAir
System in a variety of ways.
The interface adaptor for the SkyAir series is
optional except for the ceiling mounted cassette
type.
Abundance of features that provide comfortable
air-conditioning in stores and offices.
Comfort
Auto-swing
Delivers comfortable airconditioning to all areas,
near to and far from the airconditioner.
High-ceiling application
The air flow direction can be fixed
at your desited angle by the
remote controller.
Delivers air-conditioning comfort all the way down to the floor
in air-conditioning zones with high ceilings.
Swing pattern selection
(standard, ceiling soiling prevention)
You can freely set 2 air discharge settings by remote controller.
(1) Air direction in
standard setting
(2) Air direction in ceiling
soiling prevention
setting
Draft prevention function (heating)
To prevent cold air drafts, automatically adjusts airflow to near
horizontal position when heating initially starts or when the
thermostat turns off.
Switchable fan speed
High setting provides maximum reach while low setting
minimises drafts.
Note:When units are installed on high ceilings, depending on the model,
various restrictions concerning maximum height, air discharge direction,
and choice of options may apply.
Two selectable temperature-sensors
Temperature-sensors are included in the indoor unit and
optional wired remote controller. Temperature sensing closer
to the target area is possible to
further increase the comfort
level.
Use the temperature-sensor in the
indoor unit when controlling air
conditioning from another room.
Note: Wireless remote controllers have no
temperature-sensor.
Hot start (after defrost)
Cold air flow is avoided when heating operation starts or
when switching to heat after defrosting.
Year-round cooling applicable
Programme "Dry" with a humidity sensor
Dehumidification is a microprocessor controlled to prevent
abrupt and uncomfortable changes in air temperature. Useful
for reducing uncomfortable humidity without uncomfortable
cooling of the room.
Efficient cooling even in winter when the indoor temperatures
are higher than those outside, such as in underground public
spaces or offices with many computers.
Night quiet operation
The Automatic night quiet mode will initiate 8 hours after the
peak temperature is reached in the daytime, and normal
operation will resume 10 hours after that.
Timer selector
Operation starts when the preset time of the ON timer elapses
and stops when the preset time of the OFF timer elapses.
Weekly schedule timer
Up to five operation ON/OFF settings can be programmed per
day for each day of the week. Not only can the time be set for
the operation ON setting, but also the temperature.
Cleanliness
Anti-bacterial air filter
The Air filter has a anti-bacterial treatment to help prevent
the growth of bacteria and mould on it.
Silver ion anti-bacterial drain pan
Drain pan has silver ion anti-bacterial treatment to help
prevent the growth of bacteria and mould.
10
Work and Servicing
Drain pump mechanism
Steeper gradient realises more
efficient condensate drainage.
High-lift is especially useful for
long lengths of drain piping.
Pre charged for up to 30 metres
If the refrigerant piping length does not exceed 30 m, there is
no need for on-site gas charging.
Ceiling soiling prevention function
Daikin's innovative air discharge mechanism keeps airflow
away from the ceiling. Ceiling cleaning is less frequently
required.
Filter sign
The filter sign warns you when it is time to clean the filter.
Low gas pressure detection
Insufficient gas charging is normally hard to detect. During
post-installation trials and regular inspection procedures, the
refrigerant level is monitored by a microprocessor to maintain
proper gas pressure. Reliability is assured and maintenance
and inspection can be carried out more quickly.
Emergency operation
If there is a malfunction elsewhere in the system, the fan or
compressor can still be operated.
Self diagnosis function
The operating parameters of indoor and outdoor units, and
sensor data at critical locations throughout the system, are
constantly monitored using a microcomputer. To facilitate a
quick response in the event of a malfunction, a message
appears on the LCD of the remote controller and an LED on
the unit illuminates.
*When using a wired remote controller the sign is displayed in the LCD. When using a
wireless remote controller the filter sign lamp illuminates on the signal receiver unit.
Control features
Auto-restart
If there is a power outage while the equipment is operating,
operations will restart in the same mode as before the power
cut when electricity is restored.
External command control
Operation and surveillance is carried out using the contact
signal from the operation control box in the building
surveillance (security) room.
*Required for KRP58M51 (Option)
Auto cool/heat change-over (Heat pump only)
Detects difference in preset temperature and actual room
temperature and automatically switches to cooling or heating
accordingly.
Control by 2 remote controllers
Using 2 remote controllers you can operate the equipment
locally or from a remote location.
Note: When a wireless remote controller is used, remote control by two remote controllers is
not possible.
Central remote control
An optional central remote controller enables centralised
control of up to 1024 indoor units (64 groups) from up to 1
kilometer away.
Interlock control
Enables interlocking control with external equipment such as
Heat Reclaim Ventilator.
Group control by 1 remote controller
You can turn up to 16 indoor units on/off with a single remote
controller. (When using connected indoor units, the settings
must all be the same and on/off will be simultaneous.)
Options
High-efficiency filter unit
Two types are available: 65% and 90% colorimetry.
Fresh-air intake kit
You can provide air-conditioning with fresh air from outside.
Convenient for places where a ventilation fan cannot be
installed.
Note: *Connecting ducts, insect nets, fire dampers, air filters, and other parts
should, as required, be procured locally.
**Outside Air fan interlocked with air conditioning unit is necessary. Optional
PCB(KRP1C63)is required for interlocking.
***It is recommended that the volume of outdoor air introduced through the kit
is limited to 10% of the maximum airflow rate of the indoor unit. Introducing
higher quantities will increase the operating noise and may also influence
temperature sending.
Others
Anti corrosion treated heat exchangers
To achieve increased durability by improved resistance to salt corrosion and atmospheric pollution, coated Anti corrosion treated heat
exchangers (with special acryl pretreatment) are used for the heat exchanger of the outdoor unit.
In high corrosive areas, regular maintenance needs to be carried out.
11
SPECIFICATIONS
CEILING MOUNTED CASSETTE TYPE
71
FCQN71KVEA
RQ71LV1A
Indoor unit
Outdoor unit
Model
Name
Power supply
Cooling capacity
rated (Min. - Max.)1
Heating capacity
rated (Min. - Max.)2
Cooling1
Heating2
Cooling1
Heating2
Colour
Unit
Decoration panel
Airflow rate (H/L)
AEER
ACOP
Indoor
unit
Sound level (H/L)3
Sound power (H/L)4
Dimensions
(HXWXD)
Machine
weight
Outdoor
unit
Unit
Decoration panel
Unit
Decoration panel
Certified Indoor Cooling
Operation Range Heating
Colour
Compressor Type
Cooling/Heating3
Night quiet mode
Sound power4
Dimensions (HXWXD)
Machine weight
Certified Outdoor Cooling
Operation Range Heating
Piping
Liquid (Flare)
connections Gas (Flare)
Drain
Indoor unit
Outdoor unit
Max. interunit piping length
Max. installation level difference
Heat insulation
13.6
(6.8–13.6)
7.1
(3.6–7.1)
kW
8.0
(4.0–8.0)
11.2
(5.6–11.2)
14.0
(7.0–14.0)
16.0
(8.0–16.0)
2.09
2.21
3.24
3.43
3.09
3.20
3.16
3.40
4.16
4.02
2.96
3.40
4.54
5.00
2.95
3.14
550/375
33/22.5
44/34
61/52
298X840X840
50X950X950
24
5.5
550/375
33/22.5
44/36
61/53
298X840X840
50X950X950
24
5.5
---------Fresh white
/s
m3/min
dB(A)
dB(A)
mm
mm
kg
kg
O
CWB
O
CDB
350/225
21/13.5
35/28
53/46
256X840X840
50X950X950
21
5.5
533/333
32/20
43/32
60/50
298X840X840
50X950X950
24
5.5
14 to 25
15 to 27
Ivory white
Hermetically sealed
swing type
Motor output
Refrigerant charge (R-410A)
Sound level
140
FCQN140KVEA
RQ140LV1A
kW
kW
kW
Power consumption
100
125
FCQN100KVEA
FCQN125KVEA
RQ100LV1A
RQ125LV1A
1 Phase, 220-240 V, 50 Hz
10.0
12.5
(5.0–10.0)
(6.3–12.5)
kW
kg
dB(A)
dB(A)
dB(A)
mm
kg
CDB
O
CWB
mm
mm
mm
mm
m
m
Hermetically sealed scroll type
1.7
2.75
(Charged for 30 m)
1.9
3.7
(Charged for 30 m)
2.4
3.7
(Charged for 30 m)
3.1
3.7
(Charged for 30 m)
49/51
45
67
770X900X320
68
51/55
46
67
1,170X900X320
98
51/53
46
–
1,170X900X320
98
52/54
47
–
1,170X900X320
98
o/ 9.5
o/ 9.5
o/ 15.9
o/ 15.9
I.D o/ 25XO.D o/ 32
I.Do/ 25XO.Do/ 32
o/ 26.0 (Hole)
o/ 26.0 (Hole)
50 (Equivalent length 70)
30
Both liquid and gas piping
o/ 9.5
o/ 15.9
I.D o/ 25XO.D o/ 32
o/ 26.0 (Hole)
O
-5 to 46
-10 to 15.5
o/ 9.5
o/ 15.9
I.Do/ 25XO.D o/ 32
o/ 26.0 (Hole)
Note :
1
Cooling capacities are based on the following conditions:
Indoor temp., 27OCDB, 19.0OCWB; outdoor temp. 35OCDB Equiv. refrigeration piping, 7.5 m (horizontal).
2
Heating capacities are based on the following conditions:
Indoor temp., 20OCDB, outdoor temp., 7OCDB, 6OCWB. Equiv. refrigeration piping, 7.5 m (horizontal)
3
Anechoic chamber conversion value, measured according to JIS parameters and criteria. During operation these values are somewhat higher owing to ambient conditions.
4
Numerical values are according to ISO 3741:1999.
OPTIONS
Indoor unit
CEILING MOUNTED CASSETTE TYPE
Name of option
Remark
FCQN71KVEA
Decoration panel
Sealing member of air discharge outlet
Panel spacer
Fresh air
Chamber
type
intake kit1
Without the T-joint pipe and fan
With the T-joint pipe, without fan
Direct installation type
2
Chamber connection kit
Insulation kit for high humidity
(Colorimetric method 65%)
High-efficiency filter
(Colorimetric method 90%)
Replacement
(Colorimetric method 65%)
high-efficiency filter
(Colorimetric method 90%)
Filter chamber
Branch duct chamber
Wireless type
Remote controller
Wired type3 "Nav Ease"
Central remote controller4
Unified ON/OFF controller4
Schedule timer4
Touch Controller4
Adaptor for wiring5
Group control adaptor5
Installation box for adaptor PCB
Remote sensor (for indoor temperature)
KDTP55K80
KAFP556B80
KAFP557B80
KAFP552B80
KAFP553B80
KDJP55B80
Kit name
FCQN100KVEA
FCQN125KVEA
BYCP125K-W1
KDBH55K160F
KDBP55H160FA
KDDP55B160
KDDP55B160K
KDDP55X160
KKSJ55KA160
KDTP55K160
KAFP556B160
KAFP557B160
KAFP552B160
KAFP553B160
KDDFP55B160
KDJP55B160
BRC7F632F
BRC1E61
DCS302CA61
DCS301BA61
DST301BA61
DCS601C51
KRP1C63
KRP4AA53
KRP1H98
KRCS01-4B
FCQN140KVEA
Note: 1Refer to page 4 for the details.
2
Required for installing high-efficiency filter or ultra long-life filter.
3
Wiring for wired remote controller to be procured locally.
4
This type of indoor units is equipped with the interface adopter for SkyAir series. DTA112BA51 is unnecessary.
5
Installation box for adaptor PCB (KRP1H98) is necessary.
12
OPTIONS
Round flow type: List of optional parts required to achieve different flow patterns
For each flow pattern – all round, 4-way, 3-way, 2-way, branch duct connection – the compatibility of each independently installed option
(shown in the column on the left) to accessory options (listed across the top of each table) is shown in the cells where the relevant row and column intersect.
A circle (o) indicates compatibility, and a cross (x) indicates incompatibility. Any options not shown below are not suitable for independent or accessory installation.
All-round flow 4-way flow
Optional accessory parts
Independently installable optional parts
Panel/grille related
Panel spacer1
Operation control related
Wireless remote controller
Auxillary function related
Fresh air intake kit (Chamber type)1,2
Fresh air intake kit (direct mount)
High-humidity operation kit
Filter related
High-efficiency filter2
Panel spacer1
o
o
o
x
o
Wireless
Fresh air intake kit Fresh air intake kit
remote controller (Chamber type)1,2
(direct mount)
o
o
o
o
o
o
o
x
x
o
o
o
x
o
o
High-humidity
operation kit
x
o
x
o
x
High-efficiency
filter2
o
o
o
o
x
3-way flow 2-way flow
Optional accessory parts
Independently installable optional parts
Panel/grille related
Panel spacer1
Operation control related
Wireless remote controller
Auxillary function related
Fresh air intake kit (Chamber type)1,2
Fresh air intake kit (direct mount)
High-humidity operation kit
Panel spacer1
o3
o3
o3
x
Wireless
Fresh air intake kit Fresh air intake kit
remote controller (Chamber type)1,2
(direct mount)
o3
o
o
o
o3
o
x
x
o3
o
x
o
High-humidity
operation kit
High-efficiency
filter2
x
o
x
o
x
x
x
x
x
High-humidity
operation kit
High-efficiency
filter2
x
x
x
x
x
x
Branch duct connection
Optional accessory parts
Independently installable optional parts
1
Branch duct
1-way branch / unit 3-way flow
(Chamber type)
2-way branch / unit 2-way flow
(Round duct type)
1-way branch / unit 2-way flow
Panel spacer1
o
x
x
Wireless
Fresh air intake kit Fresh air intake kit
remote controller (Chamber type)1,2
(direct mount)
o
o
o
o
o
o
o
o4
o4
4
1
In some cases, depending on how the unit is embedded in the ceiling, use of branch ducts and fresh air intake kits may not be possible. Before starting installation work make sure to check
whether or not joint installation is possible. In particular, ensure that the lower fixing position caused by the addition of panel spacers is acceptable.
Use a chamber connection kit if two different types of optional chamber are used together. In this case, the fresh air intake kit must be installed in the upper position.
3
It is not possible to use panel spacers in a 2-way flow installation.
4
It is not possible to install a branch duct on the same side to which a fresh air intake kit (direct mount) is installed.
2
Outdoor unit
Name of option
Central drain plug
Wire fixture for preventing overturning
Fixture for preventing overturning
Demand adaptor
13
RQ71LV1A
Kit name
RQ100LV1A
RQ125LV1A
KKPJ5F180
K-KYZP15C
KPT-60B160
KRP58M51
RQ140LV1A
DIMENSIONS
(Unit: mm)
CEILING MOUNTED CASSETTE TYPE
[FCQN71-140KVEA]
[FCQN71-140KVEA]
[FCQN71KVEA]
[FCQN100-140KVEA]
B
167
160
67
29
95
93
157
350
Connection position
of branch duct
(square-shaped type)
B arrow view
167
93
160
67
95
29
157
350
2 100=200 80
213
25
160
157
350
80
C/L
Connection position
of branch duct
(round shape type)
Connection position
of fresh air intake kit
(direct installation type)
90
2x100=200 80
25
124
80
90
160
213
95
110
124
35 or less
(Note 4)
Connection position
of branch duct
(square-shaped type)
C/L
[FCQN100-140KVEA]
Connection position
of branch duct
(square-shaped type)
20-M4
Prepared hole
ø1
Connection position
(kn 00
of branch duct
ock
hole
(round shape type)
)
90
Connection position
183
of fresh air intake kit
C
arrow
view
(direct installation type)
4
1
2
35 or less
(Note 4)
Connection position
of branch duct
(round shape type)
55
85
27-M4 Prepared hole
5
256
157
350
A
67
160
64
50
840
2 100=200
160
60
105
81
35 or less
(Note 4)
Connection position
of branch duct
(square-shaped type)
1500 or more
(required space)
From the floor side 2500 or more
For height installation
157
280
330
A
42
125
165
20 C/L
350
157
350
3 55
150
160
298
95
167
850
Adjustable(0~675)
Suspension bolt
4-M8~M10
Connection position
of branch duct
(round shape type)
16-M4 Hole
ø1
(kn 00
ock
hole
)
90
196
C arrow view
[FCQN100-140KVEA]
16-M4 Prepared hole
55 Connection position
of branch duct
(square-shaped type)
175
29
50
40
160
288
10
840
340
80 2 100=200 80
160
256
1500 or more
(required space)
From the floor side 2500 or more
For height installation
35 or less
(Note 4)
Connection position
of branch duct
(round shape type)
[FCQN100-140KVEA]
55
20-M4 Prepared hole
55
5
130
60
840
81 2x100=200 85
64
124
50
42
105
2
55
160
124
109
95
Connection position
of branch duct
(square-shaped type)
20-M4
Prepared hole
95
167
93
29
280
330
1
3
150
124
256
850
Adjustable(0~675)
95
110
125
165
157
4
Connection position
85 of branch duct
(round shape type)
2 100=200
160
C/L
[FCQN71KVEA]
[FCQN71KVEA]
350
Connection position
of branch duct
(square-shaped type)
7
16-M4 Prepared hole
55 Connection position
of branch duct
(square-shaped type)
175
29
160
246
10
50
40
20 C/L
Suspension bolt
4-M8~M10
Connection position
of branch duct
(round shape type)
157
350
B arrow view
6
81
Drain Connection
Side
[FCQN71KVEA]
80
85 Connection position
of branch duct
(round shape type)
16-M4 Hole
95
110
160
124
950
C
A arrow view
840
340
80 2 100=200
124
2x100=200
124
C/L
Note 2
8
Pipe Connection
Side
420
55
81
950
780(Suspension position)
860~910(Ceiling opening space) (Note 4)
9
860~910(Ceiling opening space) (Note 4)
710(Suspension position)
420
130
300
or less
Notes:
1
Sticking location for manufacture's label
manufacture's label for indoor unit:
Suction grille inner side's electric components box's lid surface
manufacture's label for decoration panel :
Decoration panel's corner decoration cover inner surface
2
In case of using wireless remote controller, this position will be a signal receiver. Refer to the drawing of wireless remote controller
in detail.
3
When the temperature and humidity in the ceiling exceed 30˚C and RH 80% or the fresh air is inducted into the ceiling or the unit
continues 24 hour operation, an additional insulation (thickness 10mm or more of glasswool or polyethylene form) is required.
4
Though the installation is acceptable up to maximum of 910mm square ceiling opening, keep the clearance of 35mm or less
between the indoor unit and the ceiling opening so that
the panel overlap allowance can be ensured.
5
Please do not place the thing been damp and troubled under an indoor unit.
When the case where humidity is 80% or more, and the drain outlet are choked up and the air filter are dirty, dew may fall.
Required space
200mm or more
1500mm or more
1500mm
or more
1500mm
or more
200mm
or more
1500mm or more
When the blow-off grille is closing.
The required space is 500mm or more.
When uniting and closing a corner part
(both right and left of the blow-off grille to close),
it is 200mm or more.
1 Liquid pipe connection
2 Gas pipe connection
3 Drain pipe connection
4 Power-source wiring and a unit wiring connection
5 Connection wiring / remote control wiring connection
6 Air-outlet
7 Suction grille
8 Corner decoration cover
9 Drain hose (accessory)
14
DIMENSIONS
(Unit: mm)
OUTDOOR UNIT // RQ71LV1A
1
2
3
4
5
6
7
8
Gas pipe connection
Liquid pipe connection
Service port
Grounding terminal M5 (in switch box)
Refrigerant piping intake
Power supply wiring intake
Control wiring intake
Drain outlet
OUTDOOR UNIT // RQ100LV1A, 125LV1A, 140LV1A
3 Service port
4 Grounding terminal
1 Gas pipe connection
2 Liquid pipe connection
15
5 Refrigerant piping intake
6 Power supply wiring intake
7 Control wiring intake
8 Drain outlet
REMOTE CONTROLLER
Wireless type
Remote controller dimensions
CEILING MOUNTED CASSETTE TYPE
Receiver installation procedure
Transmitting part
Receiver
157
Refrigerant
piping side
62
Drain piping
side
17.5
Remote controller holder
installation procedure
<installation to wall surface>
Decoration panel
Receiver detail
Liquid crystal
remote controller
(wireless)
Remote controller
holder
Wired type
Remote controller dimensions
Installation method
Upper case
A Exposed cord
Lower case
Condit
C Embedded code
(use switch box)
19
84
84
19
40
19
5X7 oblong hole
28
Cord outlet hole
28
23
46
40
120
Operation
lamp
(Green)
120
B Embedded cord
Staple
Upper center
outlet
42
Upper outlet
48.5
5X15 oblong hole
84
BRC1E61
48.5
Left outlet
19
Lower case portion
Note)2
Through hole Switch box for one switch
ex.) KJB111A
( 8- 10)
(optional accessory)
Specifications of cord
Type
Size
Total length
Vinyl cord with sheath or cable (insulated thickness: 1mm or more)
0.75~1.25 mm2
500 m
46
0~5
Switch box for two switch
(Between remote
ex.) KJB211A
controller and
(optional accessory)
control box) Switch box
case portion
[field supplied part]
Lower
Note)
1. Remote controller cord and staple are not attached.
They are field supplied parts.
2.If the hole size is too large or the location is not proper,
the hole may come out from the remote controller.
16
Example of installation service space for outdoor unit
For RQ71-140LV1A
The values represent the case for the RQ100-140LV1A.
The dimensions in ( ) are for the RQ71LV1A (The unit values is mm. )
1 When there is an obstruction on the inlet side
2 When there is an obstruction on the outlet side
1) When the overhead space is open
1) When the overhead space is open
1. For single unit installation
1. For single unit installation
When there is an
obstruction only
on the inlet side
ore
rm
0o
50
re
mo
or
)
(50
0
10
2. For multiple units installation
(more than two units)
100 or more
100 or more
When there are obstructions
on both sides
re
or m
ore
100
r
0o
or m
10
ore
ss
r le
0o
50
1. For single unit installation
100 or more
100 or more
10
00
or
An obstruction
in the overhead space
mo
ore
re
20
0o
r
)o
00
rm
0(2
ore
50
2. For multiple units installation
(more than two units)
30
ss
1000 or more
r le
0o
50
re
00
10
An obstruction
in the overhead
space
ss
r le
0o
50
150
mo
3 When there are obstructions on both
the inlet and outlet sides
(When the obstruction on the outlet side is higher than the
unit itself)
1000 or more
When there are obstructions
on the inlet side and
both sides
or
e
or
rm
0o
10
An obstruction
in the overhead
space
100
or more
An obstruction
in the overhead space
1. For single unit installation
When there is an
obstruction on the
inlet side
ss
r le
0o
50
100 or more
2) When there is an obstruction
in the overhead space
rm
0o
re
mo
1000 or more
When there are
obstructions on
both sides
10
2) When there is an obstruction
in the overhead space
2. For multiple units installation
(more than two units)
mo
or
00
re
mo
1000 or more
100
1) When the overhead space is open
(There is no limit to the height of the obstruction on the
outlet side.)
or m
ore
150
e
or
rm
0o
or m
ore
15
1. For single unit installation
2. For multiple units installation (more than two units)
00
or
ss
r le
0o
50
10
0
50 ore
m
or
An obstruction
in the overhead
space
1000 or more
When there are obstructions
on the inlet side and
both sides
100 or more
2. For multiple units installation
(more than two units)
100 or more
100 or more
100
or more
mo
re
20
0o
rm
ore
)
00
0(2 re
30 r mo
o
Note : As for other patterns of installation, please refer to Installation manual or Engineering Data Book.
17
0)
0(5 e
10 mor
or
00
10 ore
m
or
)
00
0(2 re
30 r mo
o
MEMO
18
Warning
Daikin products are manufactured for export to numerous countries throughout the world. Prior to
purchase, please confirm with your local authorised importer, distributor and/or retailer whether this
product conforms to the applicable standards, and is suitable for use, in the region where the product
will be used. This statement does not purport to exclude, restrict or modify the application of any local
legislation.
Ask a qualified installer or contractor to install this product. Do not try to install the product yourself.
Improper installation can result in water or refrigerant leakage, electrical shock, fire or explosion and
may have resultant impacts on warranty.
Use only those parts and accessories supplied or specified by Daikin. Ask a qualified installer or
contractor to install those parts and accessories. Use of unauthorised parts and accessories or
improper installation of parts and accessories can result in water or refrigerant leakage, electrical
shock, fire or explosion.
Read the User's Manual carefully before using this product. The User's Manual provides important
safety instructions and warnings. Be sure to follow these instructions and warnings.
If you have any enquiries, please contact your local importer, distributor and/or retailer.
Cautions on product corrosion
1. Air conditioners should not be installed in areas where corrosive gases, such as acid gas or alkaline gas, are produced.
2. If the outdoor unit is to be installed close to the sea, direct exposure to sea breeze should be avoided. If you need to install
the outdoor unit close to the sea, contact your local distributor.
Organization:
DAIKIN INDUSTRIES, LTD.
AIR CONDITIONING MANUFACTURING
DIVISION
JMI-0107
Scope of Registration:
THE DESIGN/DEVELOPMENT AND
MANUFACTURE OF COMMERCIAL AIR
CONDITIONING, HEATING, COOLING,
REFRIGERATING EQUIPMENT, HEATING
EQUIPMENT, RESIDENTIAL AIR
CONDITIONING EQUIPMENT, HEAT
RECLAIM VENTILATION, AIR CLEANING
EQUIPMENT, COMPRESSORS AND VALVES.
Organization:
DAIKIN INDUSTRIES
(THAILAND) LTD.
JQA-1452
Scope of Registration:
THE DESIGN/DEVELOPMENT
AND MANUFACTURE OF AIR
CONDITIONERS AND THE
COMPONENTS INCLUDING
COMPRESSORS USED FOR
THEM
Daikin Australia
Pty Limited (ISO9001)
QEC23256 May 31, 2006
Sydney, Brisbane, Adelaide,
Melbourne, Newcastle,
Townsville, Perth, Auckland
Dealer
All of the Daikin
Group’s business
facilities and
subsidiaries in Japan
are certified under the
ISO 14001
international standard
for environment
management.
Daikin Australia
Pty Limited (ISO14001)
CEM20437 October 27, 2006
Sydney, Brisbane, Melbourne,
Adelaide
Head Office:
Umeda Center Bldg., 2-4-12, Nakazaki-Nishi,
Kita-ku, Osaka, 530-8323 Japan
Tokyo Office:
JR Shinagawa East Bldg., 2-18-1, Konan,
Minato-ku, Tokyo, 108-0075 Japan