Basic Rack PDU for
Blade Servers (AP7526)
Overview
The American Power Conversion (APC™) Basic
Rack Power Distribution Unit (PDU) for Blade
Servers distributes power to devices in the rack.
Outlets. The PDU has six (6) IEC-320-C19
outlets.
Power cord. The 8-ft (2.43-m) power cord
terminates with an IEC-309 32 A connector.
pdu0350a
AP7526
Specifications
Electrical
Input connector
IEC-309, 32A connector
Output connectors
(6) IEC-320-C19
Overload protection
(6) 16-A single-pole breakers
Max output current (outlet)
16 A
Max output current (phase)
32 A
Cord length
8 ft (2.43 m)
Nominal input voltage
400 VAC, 3-phase
Acceptable input voltage
±10% of nominal voltage
Input frequency
50/60 Hz
Physical
Dimensions (H × W × D)
1.72 × 17.20 × 10.00 in
(4.36 × 43.68 × 25.40 cm)
Shipping dimensions
(H × W × D)
9.50 × 22.00 × 19.75 in
(24.13 × 55.88 × 50.16 cm)
Weight
10.65 lb (4.83 kg)
Shipping weight
15.35 lb (6.96 kg)
Environmental
Elevation (above MSL)
Operating
Storage
10, 000 ft (3000 m)
50,000 ft (15 000 m)
Temperature
Operating
Storage
23 to 113°F (–5 to 45°C)
–13 to 149°F (–25 to 65°C)
Humidity
Operating
Storage
5–95%, non-condensing
5–95%, non-condensing
Approvals
Safety Certification
VDE, CE Mark,
GOST IEC-60950,
Queensland Australia