T606MSx-4 and T606MSx-4+PIR Series Multi

T606MSx-4 and T606MSx-4+PIR Series Multi-Stage
Temperature and Humidity Controllers
Code No. LIT-12011654
Product Bulletin
Issued December 1, 2010
T606MSN-4, T606MSN-4+PIR,
T606MSP-4, T606MSP-4+PIR
Refer to the QuickLIT Web site for the most up-to-date version of this document.
The T606MSN-4 and T606MSN-4+PIR Series
Non-programmable and T606MSP-4 and
T606MSP-4+PIR Series Programmable Temperature
and Humidity Controllers are specifically designed for
control of multi-stage heating and cooling equipment,
such as rooftop or self-contained units with a humidifier
and/or dehumidifier.
The T606MSx-4+PIR Series Controllers have
occupancy sensing capability built into the device.
These are stand-alone devices that maximize up to
30% energy savings in high-energy usage light
commercial buildings, such as schools and hotels,
during occupied times by using additional setpoint
strategies.
The T606MSx-4 and T606MSx-4+PIR Series
Controllers provide exceptional temperature control in
an easy-to-use and flexible package. All models have
over 20 configurable parameters, enabling the
controllers to adapt to a variety of applications.
Figure 1: T606MSx-4 and T606MSx-4+PIR Series
Temperature and Humidity Controllers
The T606MSx-4 and T606MSx-4+PIR Series
Controller models employ an embedded complete
humidity solution with a unique, Proportional-Integral
(PI) time-proportioning algorithm that virtually
eliminates temperature offset associated with
traditional, differential-based controllers.
Table 1: Features and Benefits
Features
Benefits
Embedded Humidification Sequence (0 to 10
VDC Output) and Dehumidification Sequence
(Dry Contact)
Simplifies installation and reduces installation costs.
Onboard Occupancy Sensor (Passive Infrared
[PIR] Models)
Provides energy savings without additional installation time/cost.
Password Protection Option
Protects against undesired thermostat controller tampering.
Backlit Liquid Crystal Display (LCD)
Offers real-time control status of the environment in easy-to-read,
English plain text messages with constant backlight that brightens
during user interaction.
Simplified Setpoint Adjustment
Enables the user to change the setpoint by simply pressing the
UP/DOWN arrow keys.
Five Easy-to-Use Interface Keys
Allow for easy commissioning and adjustment of the thermostat
controller and eliminate the need for DIP switches.
Three Light-Emitting Diodes (LEDs)
Provide fan, heating, and cooling status at a glance.
One Configurable Digital Input
Provides additional input for advanced functions such as remote night
setback, occupancy override, and service or filter alarms.
Over 20 Configurable Parameters
Enable the thermostat controller to adapt to any application, allowing
installer parameter access without opening the cover.
Configurable Auxiliary Output
Provides 24 VAC control for exhaust fans, lighting, and other auxiliary
functions.
T606MSx-4 and T606MSx-4+PIR Series Multi-Stage Temperature and Humidity Controllers
Product Bulletin
1
Product Overview
The T606MSx-4 and T606MSx-4+PIR Series
Controllers are specifically designed for control of the
most common commercial heating and cooling
equipment with humidifiers and/or dehumidifiers. A
number of configurable parameters enable the
thermostat controller to effectively and efficiently
control various types of equipment in nearly any
application. Configuration, setup, and operation of the
thermostat controller is extremely intuitive and
accomplished through the user interface.
The T606MSP-4 and T606MSP-4+PIR Series
Programmable Controllers feature a fully
programmable 7-day, 2- or 4-event schedule, along
with one programmable digital input and one
configurable output, enabling effective and efficient
control of equipment in nearly any application.
IMPORTANT: The T606MSx-4 and
T606MSx-4+PIR Controllers are intended to provide
an input to equipment under normal operating
conditions. Where failure or malfunction of the
controller could lead to personal injury or property
damage to the controlled equipment or other
property, additional precautions must be designed
into the control system. Incorporate and maintain
other devices, such as supervisory or alarm systems
or safety or limit controls, intended to warn of or
protect against failure or malfunction of the
controller.
•
Frost Protection Enable/Disable
Turns the heat on when the zone temperature
drops below 42°F (6°C) regardless of the mode of
the thermostat controller.
•
Adjustable Maximum Heating/Minimum Cooling
Setpoints
Establish the maximum heating setpoint and
minimum cooling setpoint that can be entered
through the user interface.
•
Adjustable Proportional Band
Adjusts the proportional band used by the
thermostat controller PI control loop from
2.0F°/1.1C° to 8.0F°/4.4C°.
•
Adjustable Anti-Short Cycling Timer
Adjusts the minimum on and off times for the
equipment from 0 to 5 minutes.
•
Adjustable Heating/Cooling Cycles per Hour
Balance temperature control and equipment
cycling through configurable maximum number of
heating and cooling cycles (3 to 8 heating cycles
maximum and 3 or 4 cooling cycles maximum) in a
1-hour period.
•
Adjustable Heating/Cooling Deadband
Adjusts the minimum heating/cooling deadband
from 2.0F°/1.1C° to 4.0F°/2.0C°.
•
Fan Control
Provides the option for equipment fan control.
•
Fan Delay Control
Enables the user to select how the fan operates on
a call for heating and the delay at the end of the
heating or cooling cycle.
•
Adjustable Temporary Occupancy Time
Adjusts the temporary occupancy time from
0 to 12 hours.
•
Sensor Offset Adjustments
Set the desired room or outside air temperature
calibration (offset).
•
System Mode Lockout
Allows the heating and cooling modes to be locked
out based on the outside air temperature when an
outside air temperature sensor is connected.
•
Unoccupied Timer (T606MSx-4+PIR Series)
Sets the time delay between the occupied and
unoccupied modes after motion is detected.
•
Progressive Recovery
Ensures the correct temperature is reached at the
programmed occupied time.
Additional Features
The T606MSx-4 and T606MSx-4+PIR Series
Controllers offer many other features, including:
•
Local Relative Humidity (RH) Display
Enables display of humidity below the room
temperature on the thermostat controller display.
•
Stationary or Scrolling Display
Provides the option of having the display
continuously scroll the parameters.
•
Three Levels of Keypad Lockout
Provide three levels of keypad lockout that can be
set up through the Installer Configuration Menu.
•
Adjustable Power Delay on Startup
Enables a delay before any operation is authorized
upon powerup of the thermostat controller. Can be
used for equipment protection or to sequence
startup of multiple units in one location.
2
T606MSx-4 and T606MSx-4+PIR Series Multi-Stage Temperature and Humidity Controllers Product Bulletin
•
Smart Fan
Enables the fan to operate continuously during the
occupied times and cycle with the equipment
during the unoccupied times.
•
Minimum/Maximum Outdoor Air Temperature
for RH Setpoint Reset
Sets the outdoor air temperature setpoints for
when the humidity setpoint is reset (an outdoor air
sensor must be connected).
•
Dehumidification Outdoor Air Temperature
Lockout
Sets the outside air temperature setpoint under
which dehumidification operation is disabled (an
outdoor air sensor must be connected).
•
Dehumidification Lockout Functions
Enable or disable the lockout functions for
dehumidification control output.
•
Dehumidification Hysteresis
Sets the dehumidification control hysteresis used
during dehumidification operation.
•
Reset Humidity Setpoint
Serves as setpoint value when the minimum
outdoor air temperature for RH Setpoint reset is
reached.
•
Room Humidity Calibration
Functions as offset that is added to or subtracted
from the actual displayed humidity by ±15% RH.
•
High Limit Sensor Value Display
Serves as diagnostic to help troubleshoot sensor/
humidifier operation.
•
Nonvolatile Electrically Erasable
Programmable Read-Only Memory (EEPROM)
Prevents loss of adjusted parameters during power
failure.
Table 2: Multi-Stage Thermostat Controller Models
Code Number
Onboard
Occupancy
Sensor
Application
T606MSN-4
No
Multi-Stage Packaged Heating/Cooling Equipment with Humidifier and/or Dehumidifier
T606MSN-4+PIR
Yes
Non-programmable
Programmable
T606MSP-4
No
T606MSP-4+PIR
Yes
Multi-Stage Packaged Heating/Cooling Equipment with Humidifier and/or Dehumidifier
Table 3: Accessories (Order Separately)
Code Number
Hx-67
Series1
Description
Duct- or Wall-Mount Humidity Sensor
SEN-600-1
Remote Inside Air Temperature Sensor
SEN-600-4
Remote Inside Air Temperature Sensor with Occupancy Override and LED
TE-6361M-12
Duct-Mount Air Temperature Sensor
TE-6363P-12
Outside Air Temperature Sensor
TEC-3-PIR3
Cover with Occupancy Sensor
1.
2.
3.
The humidity sensor must have a 0 to 10 VDC output. Remote wall-mounted version can be used for remote return or room
air humidity sensing with the sensor mounted on the wall. Remote duct-mounted humidity sensor can be used for remote
return air humidity sensing with the sensor mounted on the return air duct or as a supply air humidity sensor used as a high
limit protection.
Additional TE-63xx-x Series 10k ohm Johnson Controls® Type II Thermistor Sensors are available; refer to the
TE-6300 Series Temperature Sensors Product Bulletin (LIT-216320) for more details. When a TE-63xx-x Series Sensor is
installed according to remote sensing wiring, the thermostat controller controls based off the temperature sensed by the
TE-63xx-x Series Sensor.
The TEC-3-PIR Accessory Cover can be used to replace the existing cover on a non-PIR T606MSx-4 Series Thermostat
Controller to provide occupancy sensing capability.
T606MSx-4 and T606MSx-4+PIR Series Multi-Stage Temperature and Humidity Controllers Product Bulletin
3
PIR motion detector
saves energy.
70.0 °F
27.0 %RH
LEDs indicate
system activity.
FIG:frnt_vw
Backlit, plain text
LCD is easy to read
in any condition.
Five keys on the thermostat controller
make operation easy and intuitive.
Figure 2: Front Cover of Thermostat Controller (T606MSx-4+PIR Model Shown)
Thermostat Controller User Interface Keys
Backlit LCD
The T606MSx-4 and T606MSx-4+PIR Series
Thermostat Controller user interface consists of five
keys on the front cover (Figure 2). The function of each
key is as follows:
The T606MSx-4 and T606MSx-4+PIR Series
Controllers include a 2-line, 8-character backlit display.
Low-level backlighting is present during normal
operation, and the display brightens when any user
interface key is pressed. The backlight returns to low
level when the thermostat controller is left unattended
for 45 seconds.
•
Use the YES key to:
-
confirm menu selections and to advance to the
next menu item.
-
stop the Status Display Menu from scrolling
and to manually scroll to the next parameter on
the menu.
Note: Scrolling resumes when the thermostat
controller is left unattended for 45 seconds.
•
Use the NO key to decline a parameter change and
to advance to the next menu item.
•
Use the MENU key to:
•
4
-
access the Main User Menu or exit the menu.
-
access the Installer Configuration Menu or to
exit the menu.
Use the UP/DOWN arrow keys to change the
configuration parameters and to activate a setpoint
adjustment.
LEDs
Three LEDs are included to indicate the fan status, call
for heat, or call for cooling:
•
The fan LED
is on when the fan is on.
•
The heat LED
is on when heating is on.
•
The cool LED
is on when cooling is on.
Integrated PIR Sensor –
T606MSx-4+PIR Series Controllers
The integrated PIR sensor allows for automatic
switching between fully adjustable Occupied and
Unoccupied temperature setpoints without user
interaction. This feature generates incremental energy
savings during scheduled occupied periods while the
space is unoccupied.
T606MSx-4 and T606MSx-4+PIR Series Multi-Stage Temperature and Humidity Controllers Product Bulletin
4-15/16
(125)
4-15/16
(125)
70.0 °F
27.0 %RH
70.0 °F
27.0 %RH
1-1/8
(29)
1-3/8
(36)
FIG:dmnsns
3-3/8
(86)
3-3/8
(86)
Figure 3: T606MSx-4 Series (Left) and T606MSx-4+PIR Series (Right) Thermostat Controller
Dimensions, in. (mm)
Menu Overview
Three menus are available to view and configure the
T606MSx-4 and T606MSx-4-+PIR Series Controllers:
•
Status Display Menu
•
Main User Menu
•
Installer Configuration Menu
The following sections outline the functions and
contents of each menu.
Status Display Menu
The Status Display Menu is displayed during normal
thermostat controller operation, and continuously
scrolls through the following parameters:
•
Room Temperature
•
Day and Time (T606MSP-4 and T606MSP-4+PIR
Series)
•
System Mode
•
Schedule Status (Occupied/Unoccupied/
Override [PIR Models])
•
Outside Temperature – An outside air temperature
sensor must be installed and connected.
•
Applicable Alarms – The backlight lights up as an
alarm condition is displayed.
Note: An option is available within the Installer
Configuration Menu to lock out the scrolling display and
show only the Room Temperature parameter.
Main User Menu
Use the Main User Menu to access and change the
basic operating parameters of the thermostat controller.
Access the menu by pressing the MENU key during
normal thermostat controller operation.
Installer Configuration Menu
Use the Installer Configuration Menu to set up the
thermostat controller for application-specific operation.
To access the menu, press and hold the MENU key for
approximately 8 seconds.
The Installer Configuration Menu includes the following
parameters that are accessed by pressing the same
MENU key:
•
Password
•
%RH Display
•
Digital Input (DI) Configuration
•
Menu Scroll
•
Three Keypad Lockout Levels
•
Power Delay on Power-Up
•
Frost Protection
Note: Press the YES key to temporarily stop this
menu from scrolling.
T606MSx-4 and T606MSx-4+PIR Series Multi-Stage Temperature and Humidity Controllers Product Bulletin
5
•
Maximum Heating Setpoint/Minimum Cooling
Setpoint
•
Two or Four Events per Day Configuration
(T606MSP-4 and T606MSP-4+PIR Series)
•
Proportional Band
•
Auxiliary Output Configuration
•
Anti-Short Cycle Timer
•
Enable/Disable Progressive Recovery
•
Heating Stages Cycles per Hour
•
•
Cooling Stages Cycles per Hour
Minimum/Maximum Outdoor Air Temperature for
RH Setpoint Reset
•
Minimum Deadband
•
High RH Limit Setpoint
•
Fan Control
•
Dehumidification Outdoor Air Temperature Lockout
•
End of Cycle Fan Delay
•
Dehumidification Lockout Functions
•
Temporary Occupancy Time
•
Dehumidification Hysteresis
•
Room Air Temperature Sensor Calibration
•
Reset Humidity Setpoint
•
Outside Air Temperature Sensor Calibration
•
Room Humidity Calibration
•
Heating Operation Lockout Based on Outside Air
Temperature
•
Display High Limit Sensor Value
•
Cooling Operation Lockout Based on Outside Air
Temperature
•
Unoccupied Timer Value (T606MSx-4+PIR Series)
Repair Information
If either the T606MSx-4 or T606MSx-4+PIR Series
Thermostat Controller fails to operate within its
specifications, replace the unit. For a replacement
thermostat controller, contact the nearest
Johnson Controls representative.
Technical Specifications
T606MSx-4 and T606MSx-4+PIR Series Controllers (Part 1 of 2)
Power Requirements
19 to 30 VAC, 50/60 Hz, 2 VA (Terminals RC and C) at 24 VAC Nominal, Class 2 or
Safety Extra-Low Voltage (SELV)
Relay Contact Rating (Y2, Y1, G, W1,
W2, and AUX)
19 to 30 VAC, 1.0 A Maximum, 15 mA Minimum 3.0 A Inrush, Class 2 or SELV
Digital Input
Voltage-Free Contacts across Terminal C to Terminal DI
Humidification Analog Output
Rating
0 to 10 VDC into 2k ohm Resistance Minimum
Wire Size
18 AWG (1.0 mm Diameter) Maximum, 22 AWG (0.6 mm Diameter) Recommended
Temperature Sensor Type
Local 10k ohm Johnson Controls Type II Negative Temperature Coefficient (NTC)
Thermistor Sensor
Temperature Range
Backlit
Display
-40.0°F/-40.0°C to 122.0°F/ 50.0°C in 0.5° Increments
Heating
Control
40.0°F/4.5°C to 90.0°F/32.0°C
Cooling
Control
54.0°F/12.0°C to 100.0°F/38.0°C
Temperature
±0.9F°/±0.5C° at 70.0°F/21.0°C Typical Calibrated
Humidity
±5% RH from 30 to 70% RH at 50 to 90°F (10 to 32°C)
Accuracy
Minimum Deadband
Ambient Conditions
6
2F°/1C° between Heating and Cooling
Operating
32 to 122°F (0 to 50°C); 95% RH Maximum, Noncondensing
Storage
-22 to 122°F (-30 to 50°C); 95% RH Maximum, Noncondensing
T606MSx-4 and T606MSx-4+PIR Series Multi-Stage Temperature and Humidity Controllers Product Bulletin
T606MSx-4 and T606MSx-4+PIR Series Controllers (Part 2 of 2)
Compliance
United States
UL Listed, File E27734, CCN XAPX,
Under UL 873, Temperature Indicating and Regulating Equipment
FCC Compliant to CFR 47, Part 15, Subpart B, Class A
Canada
UL Listed, File E27734, CCN XAPX7,
Under CAN/CSA C22.2 No. 24, Temperature Indicating and Regulating Equipment
Industry Canada, ICES-003
Europe
CE Mark – Johnson Controls, Inc., declares that this product is in compliance with
the essential requirements and other relevant provisions of the
EMC Directive 2004/108/EC.
Australia and
New Zealand
C-Tick Mark, Australia/NZ Emissions Compliant
Shipping Weight
T606MSx-4 Models: 0.75 lb (0.34 kg)
T606MSx-4+PIR Models: 0.77 lb (0.35 kg)
The performance specifications are nominal and conform to acceptable industry standards. For application at conditions beyond these
specifications, consult the local Johnson Controls office. Johnson Controls, Inc. shall not be liable for damages resulting from misapplication or
misuse of its products.
United States Emissions Compliance
This equipment has been tested and found to comply with the limits for a Class A digital device pursuant to Part 15 of the FCC Rules. These
limits are designed to provide reasonable protection against harmful interference when this equipment is operated in a commercial
environment. This equipment generates, uses, and can radiate radio frequency energy and, if not installed and used in accordance with the
instruction manual, may cause harmful interference to radio communications. Operation of this equipment in a residential area is likely to cause
harmful interference, in which case the user will be required to correct the interference at his/her own expense.
Canadian Emissions Compliance
This Class (A) digital apparatus meets all the requirements of the Canadian Interference-Causing Equipment Regulations.
Cet appareil numérique de la Classe (A) respecte toutes les exigences du Règlement sur le matériel brouilleur du Canada.
Building Efficiency
507 E. Michigan Street, Milwaukee, WI 53202
Metasys® and Johnson Controls® are registered trademarks of Johnson Controls, Inc.
All other marks herein are the marks of their respective owners. © 2010 Johnson Controls, Inc.
T606MSx-4 and T606MSx-4+PIR Series Multi-Stage Temperature and Humidity Controllers Product Bulletin
Published in U.S.A.
7
www.johnsoncontrols.com
T60xDFH-3 and T60xDFH-3+PIR Series Thermostat
Controllers with Dehumidification and Occupancy Sensing
Code No. LIT-12011275
Capability
Issued November 26, 2008
Supersedes February 21, 2007
Product Bulletin
The T60xDFH-3 and T60xDFH-3+PIR Series
Thermostat Controllers provide control of two- or
four-pipe fan coils, cabinet unit heaters, or other
equipment. These thermostat controllers provide
on/off, floating, or proportional 0 to 10 VDC control
outputs; three speeds of fan control; and
dehumidification capability. The T60xDFH-3+PIR
Series Thermostat Controllers have occupancy
sensing capability built into the device. They are
stand-alone devices that maximize up to 30% energy
savings in high-energy usage light commercial
buildings, such as schools and hotels, during occupied
times by using additional standby setpoints.
The non-programmable T60x Series Thermostat
Controllers provide the user access to parameters such
as system mode, fan mode, and temperature setpoints.
Additionally, the T60x Series has over 20 configurable
parameters enabling the thermostat controllers to
adapt to a variety of applications.
Figure 1: T60xDFH-3 and T60xDFH-3+PIR Series
Thermostat Controllers with Dehumidification
and Occupancy Sensing Capability
All T60x Series Thermostat Controllers use an intuitive,
plain text, menu-driven backlit display that makes
setup and operation quick and easy. The T60x Series
also employ a unique, Proportional-Integral (PI)
time-proportioning algorithm that virtually eliminates
temperature offset associated with traditional,
differential-based thermostat controllers.
Table 1: Features and Benefits (Part 1 of 2)
Feature
Benefit
Onboard Occupancy Sensor (Passive
Infrared [PIR] Models)
Provides energy savings without additional installation time/cost.
Diagnostic Light-Emitting Diode (LED) in PIR
Models
Provides visual confirmation of motion detection during installation for a
period of up to 30 minutes.
Dehumidification Capability
(Dehumidification Models)
Increases occupancy comfort by providing dehumidification.
Backlit Liquid Crystal Display (LCD)
Offers real-time control status of the environment in easy-to-read,
English plain text messages with constant backlight that brightens during
user interaction.
On/Off, Floating, or Proportional 0 to 10 VDC
Control
Offers additional application flexibility by providing more advanced control
signals.
Three Speeds of Fan Control
Provide easy FAN speed selection, via the interface key, to meet the
application requirements.
Temperature Scale Selector Key
Offers guests the ability to select a Fahrenheit (°F) or Celsius (°C)
temperature scale display.
T60xDFH-3 and T60xDFH-3+PIR Series Thermostat Controllers with Dehumidification and
Occupancy Sensing Capability Product Bulletin
1
Table 1: Features and Benefits (Part 2 of 2)
Feature
Benefit
Simplified Setpoint Adjustment
Enables the user to change the setpoint by simply pressing the
UP/DOWN arrow keys.
Two Configurable Binary Inputs
Provide additional inputs for advanced functions such as remote night
setback, service or filter alarms, motion detector, and window status.
Over 20 Configurable Parameters
Enable the thermostat controller to adapt to any application, allowing
installer parameter access without opening the cover.
Product Overview
The T60xDFH-3 and T60xDFH-3+PIR Series
Thermostat Controllers provide control of two- or
four-pipe fan coils, cabinet unit heaters, or other
equipment using on/off, floating, or proportional 0 to
10 VDC control input. The T60xDFH-3+PIR Series
Thermostat Controllers have occupancy sensing ability
built into the device. These stand-alone devices
maximize up to 30% energy savings in high-energy
usage light commercial buildings, such as schools and
hotels, during occupied times by using additional
stand-by setpoints.
The T60xDFH-3 and T60xDFH-3+PIR Series
Thermostat Controllers also employ a unique, PI
time-proportioning algorithm that virtually eliminates
temperature offset associated with traditional,
differential based thermostat controllers.
IMPORTANT: The T60xDFH-3 and
T60xDFH-3+PIR Series Thermostat Controllers are
intended to provide an input to equipment under
normal operating conditions. Where failure or
malfunction of the thermostat controller could lead to
personal injury or property damage to the controlled
equipment or other property, additional precautions
must be designed into the control system.
Incorporate and maintain other devices, such as
supervisory or alarm systems or safety or limit
controls, intended to warn of or protect against
failure or malfunction of the thermostat controller.
Additional Features
The T60xDFH-3 and T60xDFH-3+PIR Series
Thermostat Controllers offer many other features,
including:
•
2
Adjustable Heating and Cooling Stand-By
Setpoints (PIR Models)
Provides an adjustable range of setpoints that can
be used to conserve energy.
•
Adjustable Time Delay for Activating
Unoccupied Setpoints (PIR Models)
Allows the user to adjust time delay before
unoccupied setpoints are enabled to maintain
comfort temperatures while conserving energy.
•
Occupancy Sensing in Conjunction with Door
Switch Toggle (PIR Models)
Adds more efficiency by associating the door
switch into the sequence of operation.
•
Adjustable Heating/Cooling Deadband
Adjusts the minimum heating/cooling deadband
from 2.0F°/1.0C° to 5.0F°/2.5C°.
•
Remote Indoor Sensing
Accommodates remote indoor sensors. Up to
three indoor sensors can be averaged.
•
Five Easy-to-Use Interface Keys
Allow for easy commissioning of the thermostat
controller, and eliminate the need for DIP switches.
•
Six Levels of Keypad Lockout
Provide six levels of keypad lockout that can be
set up through the Installer Configuration Menu.
•
Accessible Configuration Parameters
Allow local access to all configurable parameters
while limiting unwanted parameter tampering once
the thermostat controller is set up.
•
Three LEDs
Provide fan, heating, and cooling status at a
glance.
•
Adjustable Temporary Occupancy Time
Adjusts the temporary occupancy time from
0 to 24 hours.
•
Auxiliary Contact
Provides 24 VAC control for reheat, lighting, and
other auxiliary functions.
T60xDFH-3 and T60xDFH-3+PIR Series Thermostat Controllers with Dehumidification and Occupancy
Sensing Capability Product Bulletin
•
Adjustable Heating/Cooling Cycles per Hour
(On/Off Control)
Configurable for the maximum number of heating
and cooling cycles (3 to 8 cycles maximum) in a
1-hour period, balancing temperature control and
equipment cycling.
•
Nonvolatile Electrically Erasable
Programmable Read-Only Memory (EPROM)
Prevents loss of adjusted parameters during a
power failure.
•
Remote Access
Allows the user to read/write and access the
parameters of the thermostat controller via a
supervisory controller.
Table 2: Thermostat Controller Models
Code Number
Control Outputs
Fan Control
Dehumidification
Capability
Onboard
Occupancy Sensor
T601DFH-3
Two On/Off
Up to Three Speeds
No
No
T601DFH-3+PIR
Two On/Off
Up to Three Speeds
No
Yes
T602DFH-3
Two On/Off or Floating
Up to Three Speeds
No
No
T602DFH-3+PIR
Two On/Off or Floating
Up to Three Speeds
No
Yes
T603DFH-3
Two On/Off or Floating
Up to Three Speeds
Yes
No
T603DFH-3+PIR
Two On/Off or Floating
Up to Three Speeds
Yes
Yes
T604DFH-3
Two Proportional 0 to 10 VDC
Up to Three Speeds
No
No
T604DFH-3+PIR
Two Proportional 0 to 10 VDC
Up to Three Speeds
No
Yes
T605DFH-3
Two Proportional 0 to 10 VDC
Up to Three Speeds
Yes
No
T605DFH-3+PIR
Two Proportional 0 to 10 VDC
Up to Three Speeds
Yes
Yes
Table 3: Accessories (Order Separately)
Code Number
Description
SEN-600-1
Remote Indoor Air Temperature Sensor
TE-6361M-11
Duct Mount Air Temperature Sensor
TE-636S-1
Strap-Mount Temperature Sensor
1.
Additional TE-63xx-x Series 10k ohm Johnson Controls® Type II Thermistor Sensors are available; refer to the
TE-6300 Series Temperature Sensors Product Bulletin (LIT-216320) for more details. When a TE-63xx-x Series Sensor is
installed according to remote sensing wiring, the thermostat controller controls based off the temperature sensed by the
TE-63xx-x Series Sensor.
Thermostat Controller User Interface Keys
•
The T60xDFH-3 and T60xDFH-3+PIR Series
Thermostat Controllers user interface consists of five
keys on the front cover (as illustrated in Figure 2). The
function of each key is as follows:
°C/°F key changes the temperature scale to either
Celsius or Fahrenheit and allows access to the
Installer Configuration Menu. (See the Installer
Configuration Menu section.)
•
UP/DOWN arrow keys change the configuration
parameters and activate a setpoint adjustment.
•
•
MODE key toggles among the system modes
available, as defined by selecting the appropriate
operation sequence in the Installer Configuration
Menu (for example, Off, Heat, Cool, Auto).
FAN key toggles among the fan modes available,
as defined by selecting the appropriate fan menu
options defined in the Installer Configuration Menu
(for example, Low, Med, High, Auto).
Backlit LCD
The T60xDFH-3 and T60xDFH-3+PIR Series
Thermostat Controllers include a 2-line, 8-character
backlit display. Low-level backlighting is present during
normal operation, and it brightens when any user
interface key is pressed. The backlight returns to low
level when the thermostat controller is left unattended
for 45 seconds.
T60xDFH-3 and T60xDFH-3+PIR Series Thermostat Controllers with Dehumidification and Occupancy
Sensing Capability Product Bulletin
3
PIR motion detector
saves energy using
stand-by setpoints.
Room Temp
70.0ºF
MODE
FAN
LEDs indicate
system activity.
°C
°F
FIG:frnt_vw
Backlit, plain text
LCD is easy to read
in any condition.
Five keys on the thermostat controller
make operation easy and intuitive.
Figure 2: Front Cover of Thermostat Controller (T60xDFH-3+PIR Model Shown)
4-15/16
(125)
4-15/16
(125)
Room Temp
70.0ºF
Room Temp
70.0ºF
FAN
MODE
°C
°F
FAN
°C
°F
3-3/8
(86)
3-3/8
(86)
1-1/8
(29)
1-3/8
(36)
FIG:dmnsns
MODE
Figure 3: T60xDFH-3 Series Thermostat Controller (Left) and
T60xDFH-3+PIR Series Thermostat Controller (Right)
Dimensions, in. (mm)
LEDs
Integrated PIR Sensor
Three LEDs are included to indicate the fan status, call
for heat, or call for cooling:
The integrated PIR sensor allows for automatic
switching between fully adjustable occupied and
standby temperature setpoints without user interaction.
This generates incremental energy savings during
scheduled occupied periods while the space is vacant.
•
The FAN LED is on when the fan is on.
•
The HEAT LED is on when heating or reheat is on.
•
The COOL LED is on when cooling is on.
4
T60xDFH-3 and T60xDFH-3+PIR Series Thermostat Controllers with Dehumidification and Occupancy
Sensing Capability Product Bulletin
Menu Overview
•
Control Type (On/Off or Floating Models)
Two menus are available to view and configure the
T60xDFH-3 and T60xDFH-3+PIR Series Thermostat
Controllers:
•
Sequence of Operation
•
Fan Menu
•
Dehumidification Lockout (Dehumidification
Models)
•
Dehumidification Setpoint (Dehumidification
Models)
•
Dehumidification Hysteresis (Dehumidification
Models)
•
Maximum Dehumidification Cooling Output
(Dehumidification Models)
•
Stand-By Setpoint Timer Value (PIR Models)
•
Unoccupied Timer Value (PIR Models)
•
Status Display Menu
•
Installer Configuration Menu
The following sections outline the functions and
contents of each menu.
Status Display Menu
The Status Display Menu is displayed during normal
thermostat controller operation. This menu
continuously scrolls through the following parameters:
•
Room Temperature (All Models) and Humidity
(T603 and T605 Series Models)
•
System Mode
•
•
Occupancy Status
(Occupied/Stand-By [PIR Models]
Unoccupied/Override)
Stand-By Heating Setpoint/Stand-By Cooling
Setpoint (PIR Models)
•
Unoccupied Heating Setpoint/Unoccupied Cooling
Setpoint
•
Maximum Heating Setpoint/Minimum Cooling
Setpoint
•
Setpoint Type
•
Temporary Occupancy Time
•
Door Open Time
•
Heating/Cooling Deadband
•
Room Air Temperature Calibration
•
Room Humidity Calibration (Dehumidification
Models)
•
Auxiliary Configuration
•
Floating Time (Floating Models)
•
Applicable Alarms (The backlight lights up as an
alarm condition is displayed.)
Note: An option is available within the Installer
Configuration Menu to lock out the scrolling display and
show only the Room Temperature parameter.
Installer Configuration Menu
The Installer Configuration Menu is used to set up the
thermostat controller for an application-specific
operation. To access the menu, press and hold the
center key for approximately 8 seconds.
The Installer Configuration Menu includes the following
parameters that are accessed by pressing the same
center key:
•
BI1 and BI2 Input Configuration
•
Cycles per Hour (On/Off Models)
•
UI3 Input Configuration to Locally Monitor Supply
Air Temperature or Hot/Cold Water Changeover
Switching
•
Direct/Reverse Acting (Proportional Models)
•
Reheat Time
•
Display UI3 Value
•
Menu Scroll
•
Auto Mode
•
% RH Display (Dehumidification Models)
•
Six Keypad Lockout Levels
•
Pipe No.
Repair Information
If either the T60xDFH-3 or T60xDFH-3+PIR Series
Thermostat Controller fails to operate within its
specifications, replace the unit. For a replacement
thermostat controller, contact the nearest
Johnson Controls representative.
T60xDFH-3 and T60xDFH-3+PIR Series Thermostat Controllers with Dehumidification and Occupancy
Sensing Capability Product Bulletin
5
Technical Specifications
T60xDFH-3 and T60xDFH-3+PIR Series Thermostat Controllers with Dehumidification and
Occupancy Sensing Capability (Part 1 of 2)
Power Requirements
19 to 30 VAC, 50/60 Hz, 2 VA (Terminals 4 and 5) at 24 VAC Nominal, Class 2 or
Safety Extra-Low Voltage (SELV)
Relay/Triac
Contact
Rating
On/Off and
Floating
Control
30 VAC, 1.0 A Maximum, 15 mA Minimum, 3.0 A In-Rush, Class 2 or SELV
Analog
Output Rating
Proportional
Control
0 to 10 VDC into 2k ohm Resistance (Minimum)
Fan Relay Output Rating
19 to 30 VAC, 1.0 A Maximum, 3.0 A In-Rush
Auxiliary
Output Rating
19 to 30 VAC, 1.0 A Maximum, 3.0 A In-Rush
Triac Output
Digital Inputs
Voltage-Free Contacts across Terminal Scom to Terminals BI1, BI2, or UI3
Analog Inputs
Resistive Inputs (RS and UI3) for 10k ohm Johnson Controls Type II Negative
Temperature Coefficient (NTC) Thermistor Sensors
Temperature Sensor Type
Local 10k ohm NTC Thermistor
Wire Size
18 AWG (1.0 mm Diameter) Maximum, 22 AWG (0.6 mm Diameter) Recommended
Temperature
Range
Accuracy
Backlit Display
-40.0°F/-40.0°C to 122.0°F/50.0°C in 0.5° Increments
Heating Control
40.0°F/4.5°C to 90.0°F/32.0°C
Cooling Control
54.0°F/12.0°C to 100.0°F/38.0°C
Temperature
±0.9F°/±0.5C° at 70.0°F/21.0°C Typical Calibrated
Humidity
±5% RH from 20 to 80% RH at 50 to 90°F (10 to 32°C)
Minimum Deadband
2F°/1C° between Heating and Cooling
Ambient
Conditions
Operating
32 to 122°F (0 to 50°C); 95% RH Maximum, Noncondensing
Storage
-22 to 122°F (-30 to 50°C); 95% RH Maximum, Noncondensing
Compliance
United States
UL Listed, File E27734, CCN XAPX,
Under UL 873, Temperature Indicating and Regulating Equipment
FCC Compliant to CFR 47, Part 15, Subpart B, Class A
Canada
UL Listed, File E27734, CCN XAPX7,
Under CAN/CSA C22.2 No. 24, Temperature Indicating and Regulating Equipment
Industry Canada, ICES-003
6
Europe
CE Mark, EMC Directive 89/336/EEC
Australia and
New Zealand
C-Tick Mark, Australia/NZ Emissions Compliant
T60xDFH-3 and T60xDFH-3+PIR Series Thermostat Controllers with Dehumidification and Occupancy
Sensing Capability Product Bulletin
T60xDFH-3 and T60xDFH-3+PIR Series Thermostat Controllers with Dehumidification and
Occupancy Sensing Capability (Part 2 of 2)
Shipping
Weight
T60xDFH-3
Models
0.75 lb (0.34 kg)
T60xDFH-3+PIR
Models
0.77 lb (0.35 kg)
The performance specifications are nominal and conform to acceptable industry standards. For application at conditions beyond these
specifications, consult the local Johnson Controls office. Johnson Controls, Inc. shall not be liable for damages resulting from misapplication or
misuse of its products.
United States Emissions Compliance
This equipment has been tested and found to comply with the limits for a Class A digital device pursuant to Part 15 of the FCC Rules. These
limits are designed to provide reasonable protection against harmful interference when this equipment is operated in a commercial
environment. This equipment generates, uses, and can radiate radio frequency energy and, if not installed and used in accordance with the
instruction manual, may cause harmful interference to radio communications. Operation of this equipment in a residential area is likely to cause
harmful interference, in which case the user will be required to correct the interference at his/her own expense.
Canadian Emissions Compliance
This Class (A) digital apparatus meets all the requirements of the Canadian Interference-Causing Equipment Regulations.
Cet appareil numérique de la Classe (A) respecte toutes les exigences du Règlement sur le matériel brouilleur du Canada.
Building Efficiency
507 E. Michigan Street, Milwaukee, WI 53202
Metasys® and Johnson Controls® are registered trademarks of Johnson Controls, Inc.
All other marks herein are the marks of their respective owners. © 2008 Johnson Controls, Inc.
T60xDFH-3 and T60xDFH-3+PIR Series Thermostat Controllers with Dehumidification and Occupancy
Sensing Capability Product Bulletin
Published in U.S.A.
7
www.johnsoncontrols.com
T600xxx-4 and T600xxx-4+PIR Series Thermostat
Controllers
Code No. LIT-12011583
Product Bulletin
Issued November 13, 2009
T600HCx-4, T600HPx-4, T600MSx-4, T600MEP-4,
T600HCx-4+PIR, T600HPx-4+PIR, T600MSx-4+PIR, T600MEP-4+PIR
The T600xxN-4 and T600xxN-4+PIR Series
Non-programmable and T600xxP-4 and
T600xxP-4+PIR Series Programmable Thermostat
Controllers are specifically designed for control of
single-stage, multi-stage, and heat pump commercial
heating and cooling equipment. The T600xxP-4 and
T600xxP-4+PIR Series Thermostat Controllers are
also specifically designed for control of rooftop units
(with and without economizers).
The T600xxx-4+PIR Series Thermostat Controllers
have occupancy sensing capability built into the device.
These are stand-alone devices that maximize up to
30% energy savings in high-energy usage light
commercial buildings, such as schools and hotels,
during occupied times by using additional setpoint
strategies.
The T600xxx-4 and T600xxx-4+PIR Series Thermostat
Controllers provide exceptional temperature control in
an easy-to-use and flexible package. All models have
over 20 configurable parameters, enabling the
thermostat controllers to adapt to a variety of
applications.
Figure 1: T600xxx-4 and T600xxx-4+PIR Series
Thermostat Controllers
The T600xxx-4 and T600xxx-4+PIR Series Thermostat
Controllers include several models: single-stage
(T600HCx-4 and T600HCx-4+PIR Series), heat pump
(T600HPx-4 and T600HPx-4+PIR Series), multi-stage
(T600MSx-4 and T600MSx-4+PIR Series), and
economizer (T600MEP-4 and T600MEP-4+PIR). All
models employ a unique, Proportional-Integral (PI)
time-proportioning algorithm that virtually eliminates
temperature offset associated with traditional,
differential-based thermostat controllers.
Table 1: Features and Benefits (Part 1 of 2)
Feature
Benefit
Onboard Occupancy Sensor (Passive Infrared
[PIR] Models)
Provides energy savings without additional installation time/cost.
Password Protection Option
Protects against undesired thermostat controller tampering.
Backlit Liquid Crystal Display (LCD)
Offers real-time control status of the environment in easy-to-read,
English plain text messages with constant backlight that brightens
during user interaction.
Simplified Setpoint Adjustment
Enables the user to change the setpoint by simply pressing the
UP/DOWN arrow keys.
Five Easy-to-Use Interface Keys
Allow for easy commissioning and adjustment of the thermostat
controller and eliminates the need for DIP switches.
Three Light-Emitting Diodes (LEDs)
Provide fan, heating, and cooling status at a glance.
Two Configurable Digital Inputs
Provide additional inputs for advanced functions such as remote night
setback, occupancy override, and service or filter alarms.
T600xxx-4 and T600xxx-4+PIR Series Thermostat Controllers Product Bulletin
1
Table 1: Features and Benefits (Part 2 of 2)
Feature
Benefit
Over 20 Configurable Parameters
Enable the thermostat controller to adapt to any application, allowing
installer parameter access without opening the cover.
Configurable Auxiliary Output
Provides 24 VAC control for exhaust fans, lighting, and other auxiliary
functions.
Economizer Output (T600MEP-4 and
T600MEP-4+PIR Models)
Controls economizer operation for single- and multi-stage unitary
rooftop equipment.
Product Overview
•
The T600xxx-4 and T600xxx-4+PIR Series Thermostat
Controllers are specifically designed for control of the
most common commercial heating and cooling
equipment. A number of configurable parameters
enable the thermostat controller to effectively and
efficiently control various types of equipment in nearly
any application. Configuration, setup, and operation of
the thermostat controller is extremely intuitive and is
accomplished through user interface.
Adjustable Power Delay on Startup
Enables a delay before any operation is authorized
upon powerup of the thermostat controller. Can be
used for equipment protection or to sequence
startup of multiple units in one location.
•
Frost Protection Enable/Disable
Turns the heat on when the zone temperature
drops below 42°F (6°C) regardless of the mode the
thermostat controller.
•
Adjustable Maximum Heating/Minimum Cooling
Setpoints
Establish the maximum heating setpoint and
minimum cooling setpoint that can be entered
through the user interface.
•
Adjustable Anti-Short Cycling Timer
Adjusts the minimum on and off times for the
equipment from 0 to 5 minutes.
•
Adjustable Heating/Cooling Cycles per Hour
Configurable for the maximum number of heating
and cooling cycles (3 to 8 heating cycles maximum
and 3 or 4 cooling cycles maximum) in a 1-hour
period, balancing temperature control and
equipment cycling.
•
Adjustable Heating/Cooling Deadband
Adjusts the minimum heating/cooling deadband
from 2.0F°/1.0C° to 4.0F°/2.0C°.
•
Fan Control
Provides the option for equipment fan control.
•
Fan Delay Control
Enables the user to select how the fan operates on
a call for heating and the delay at the end of the
heating or cooling cycle.
•
Adjustable Temporary Occupancy Time
Adjusts the temporary occupancy time from
0 to 12 hours.
•
Sensor Offset Adjustments
Sets the desired room or outside air temperature
calibration (offset).
The T600xxP-4 and T600xxP-4+PIR Series
Programmable Thermostat Controllers feature a fully
programmable 7-day, 2- or 4-event schedule, along
with two programmable digital inputs and one
configurable output, enabling effective and efficient
control of equipment in nearly any application.
IMPORTANT: The T600xxx-4 and T600xxx-4+PIR
Thermostat Controllers are intended to provide an
input to equipment under normal operating
conditions. Where failure or malfunction of the
thermostat controller could lead to personal injury or
property damage to the controlled equipment or
other property, additional precautions must be
designed into the control system. Incorporate and
maintain other devices, such as supervisory or
alarm systems or safety or limit controls, intended to
warn of or protect against failure or malfunction of
the thermostat controller.
Additional Features
The T600xxx-4 and T600xxx-4+PIR Series Thermostat
Controllers offer many other features, including:
•
•
2
Stationary or Scrolling Display
Provides the option of having the display
continuously scroll the parameters.
Three Levels of Keypad Lockout
Provide three levels of keypad lockout that can be
set up through the Installer Configuration Menu.
T600xxx-4 and T600xxx-4+PIR Series Thermostat Controllers Product Bulletin
•
System Mode Lockout
Allows the heating and cooling modes to be locked
out based on the outside air temperature when an
outside air temperature sensor is connected.
•
Unoccupied Timer (T600xxx-4+PIR Series)
Sets the time delay between the occupied and
unoccupied modes after motion is detected.
•
Progressive Recovery
Ensures the correct temperature is reached at the
programmed occupied time.
•
Smart Fan
Enables the fan to operate continuously during the
occupied times and cycle with the equipment
during the unoccupied times.
•
Remote Inside and Outside Air Temperature
Sensing
Accommodates remote inside and outside air
temperature sensors. Up to three inside air
temperature sensors can be averaged.
•
Nonvolatile Electrically Erasable
Programmable Read-Only Memory (EEPROM)
Prevents loss of adjusted parameters during power
failure.
•
Heating and Cooling Stage Enable/Disable
(T600MEP-4, T600MEP-4+PIR, and T600MSx-4
and T600MSx-4+PIR Series)
Allows operation of the second-stage heating and
cooling to be disabled, reverting the thermostat
controller to single-stage operation on multi-stage
thermostat controllers.
•
Power Loss Backup for Clock (T600xxP-4 and
T600xxP-4+PIR Series)
Retains clock setting for up to 6 hours in the event
of a power loss.
•
High and Low Balance Point Adjustments
Enable more precise control of heat pump
operation based on the outside air temperature
(T600HPx-4 and T600HPx-4+PIR Series).
•
Heat Pump Compressor Stage Enable/Disable
(T600HPx-4 and T600HPx-4+PIR Series)
Allows operation of the second-stage compressor
to be disabled, reverting the thermostat controller
to single-stage compressor operation on heat
pump thermostat controllers.
Table 2: Thermostat Controller Models (Part 1 of 2)
Code Number
Description
Onboard
Occupancy
Sensor
Applications
T600HCN-4
Single-Stage
No
Fan Coil Units, Unit Heaters, and Single-Stage Packaged
Heating/Cooling Equipment
T600HCN-4+PIR
Single-Stage
Yes
Fan Coil Units, Unit Heaters, and Single-Stage Packaged
Heating/Cooling Equipment
T600HPN-4
Heat Pump
No
Heat Pump with Up to Three Heating Stages and Two
Cooling Stages
T600HPN-4+PIR
Heat Pump
Yes
Heat Pump with Up to Three Heating Stages and Two
Cooling Stages
T600MSN-4
Multi-Stage
No
Multi-Stage Packaged Heating/Cooling Equipment
T600MSN-4+PIR
Multi-Stage
Yes
Multi-Stage Packaged Heating/Cooling Equipment
Non-programmable
T600xxx-4 and T600xxx-4+PIR Series Thermostat Controllers Product Bulletin
3
Table 2: Thermostat Controller Models (Part 2 of 2)
Code Number
Description
Onboard
Occupancy
Sensor
Applications
T600HCP-4
Single-Stage
No
Fan Coil Units, Unit Heaters, and Single-Stage Packaged
Heating/Cooling Equipment
T600HCP-4+PIR
Single-Stage
Yes
Fan Coil Units, Unit Heaters, and Single-Stage Packaged
Heating/Cooling Equipment
T600HPP-4
Heat Pump
No
Heat Pump with Up to Three Heating Stages and Two
Cooling Stages
T600HPP-4+PIR
Heat Pump
Yes
Heat Pump with Up to Three Heating Stages and Two
Cooling Stages
T600MEP-4
Economizer
No
Packaged Rooftop Units with Economizers
T600MEP-4+PIR
Economizer
Yes
Packaged Rooftop Units with Economizers
T600MSP-4
Multi-Stage
No
Multi-Stage Packaged Heating/Cooling Equipment
T600MSP-4+PIR
Multi-Stage
Yes
Multi-Stage Packaged Heating/Cooling Equipment
Programmable
Table 3: Accessories (Order Separately)
Code Number
Description
SEN-600-1
Remote Inside Air Temperature Sensor
SEN-600-4
Remote Inside Air Temperature Sensor with Occupancy Override and LED
TE-6361M-11
Duct Mount Air Temperature Sensor
TE-6363P-11
Outside Air Temperature Sensor
TEC-3-PIR2
Cover with Occupancy Sensor
1.
2.
Additional TE-63xx-x Series 10k ohm Johnson Controls® Type II Thermistor Sensors are available; refer to the
TE-6300 Series Temperature Sensors Product Bulletin (LIT-216320) for more details. When a TE-63xx-x Series Sensor is
installed according to remote sensing wiring, the thermostat controller controls based off the temperature sensed by the
TE-63xx-x Series Sensor.
The TEC-3-PIR Accessory Cover can be used to replace the existing cover on a non-PIR T600xxx-4 Series Thermostat
Controller to provide occupancy sensing capability.
Thermostat Controller User Interface Keys
The T600xxx-4 and T600xxx-4+PIR Series Thermostat
Controller user interface consists of five keys on the
front cover (as illustrated in Figure 2). The function of
each key is as follows:
•
4
Use the YES key to:
-
confirm menu selections and to advance to the
next menu item.
-
stop the Status Display Menu from scrolling
and to manually scroll to the next parameter on
the menu.
Note: When the thermostat controller is left
unattended for 45 seconds, the thermostat controller
display resumes scrolling.
•
Use the NO key to decline a parameter change and
to advance to the next menu item.
•
Use the MENU key to:
•
-
access the Main User Menu or exit the menu.
-
access the Installer Configuration Menu or to
exit the menu.
Use the UP/DOWN arrow keys to change the
configuration parameters and to activate a setpoint
adjustment.
T600xxx-4 and T600xxx-4+PIR Series Thermostat Controllers Product Bulletin
Backlit LCD
The T600xxx-4 and T600xxx-4+PIR Series Thermostat
Controllers include a 2-line, 8-character backlit display.
Low-level backlighting is present during normal
operation, and it brightens when any user interface key
is pressed. The backlight returns to low level when the
thermostat controller is left unattended for 45 seconds.
PIR motion detector
saves energy.
Room Temp
70.0ºF
Backlit, plain text
LCD is easy to read
in any condition.
FIG:frnt_vw
LEDs indicate
system activity.
Five keys on the thermostat controller
make operation easy and intuitive.
Figure 2: Front Cover of Thermostat Controller (T600xxx-4+PIR Model Shown)
4-15/16
(125)
4-15/16
(125)
Room Temp
70.0ºF
Room Temp
70.0ºF
1-1/8
(29)
1-3/8
(36)
FIG:dmnsns
3-3/8
(86)
3-3/8
(86)
Figure 3: T600xxx-4 Series Thermostat Controller (Left) and
T600xxx-4+PIR Series Thermostat Controller (Right)
Dimensions, in. (mm)
T600xxx-4 and T600xxx-4+PIR Series Thermostat Controllers Product Bulletin
5
LEDs
Three LEDs are included to indicate the fan status, call
for heat, or call for cooling:
Note: An option is available within the Installer
Configuration Menu to lock out the scrolling display and
show only the Room Temperature parameter.
Main User Menu
•
The fan LED
is on when the fan is on.
•
The heat LED
is on when heating is on.
•
The cool LED
is on when cooling is on.
Integrated PIR Sensor –
T600xxx-4+PIR Series Thermostat
Controllers
The integrated PIR sensor allows for automatic
switching between fully adjustable Occupied and
Unoccupied temperature setpoints without user
interaction. This feature generates incremental energy
savings during scheduled occupied periods while the
space is unoccupied.
Menu Overview
Three menus are available to view and configure the
T600xxx-4 and T600xxx-4-+PIR Series Thermostat
Controllers:
•
Status Display Menu
•
Main User Menu
•
Installer Configuration Menu
The following sections outline the functions and
contents of each menu.
Status Display Menu
The Status Display Menu is displayed during normal
thermostat controller operation, and continuously
scrolls through the following parameters:
Use the Main User Menu to access and change the
basic operating parameters of the thermostat controller.
Access the menu by pressing the MENU key during
normal thermostat controller operation.
Installer Configuration Menu
Use the Installer Configuration Menu to set up the
thermostat controller for application-specific operation.
To access the menu, press and hold the MENU key for
approximately 8 seconds.
The Installer Configuration Menu includes the following
parameters that are accessed by pressing the same
MENU key:
•
Password
•
DI1 and DI2 Input Configuration
•
Menu Scroll
•
Three Keypad Lockout Levels
•
Power Delay on Power-Up
•
Frost Protection
•
Maximum Heating Setpoint/Minimum Cooling
Setpoint
•
Proportional Band
•
Anti-Short Cycle Timer
•
Heating Stages Cycles per Hour
•
Cooling Stages Cycles per Hour
•
Minimum Deadband
•
Room Temperature
•
Fan Control
•
Day and Time (T600xxP-4 and T600xxP-4+PIR
Series)
•
End of Cycle Fan Delay
•
System Mode
•
Temporary Occupancy Time
•
Schedule Status –
(Occupied/Unoccupied/Override [PIR Models])
•
Room Air Temperature Sensor Calibration
•
Outside Air Temperature Sensor Calibration
•
Outside Temperature – An outside air temperature
sensor must be installed and connected.
•
•
Applicable Alarms – The backlight lights up as an
alarm condition is displayed.
Number of Heating Stages (T600MEP-4,
T600MEP-4+PIR, and T600MSx-4 and
T600MSx-4+PIR Series)
•
Number of Cooling Stages (T600MEP-4,
T600MEP-4+PIR, and T600MSx-4 and
T600MSx-4+PIR Series)
•
Number of Heat Pump Stages (T600HPx-4 and
T600HPx-4+PIR Series)
Note: Press the YES key to temporarily stop this
menu from scrolling.
6
T600xxx-4 and T600xxx-4+PIR Series Thermostat Controllers Product Bulletin
•
Reversing Valve Operation
•
Compressor/Auxiliary Interlock
•
Heating Operation Lockout Based on Outside Air
Temperature
•
Cooling Operation Lockout Based on Outside Air
Temperature
•
Unoccupied Timer Value (T600xxx-4+PIR Series)
•
Economizer Changeover Setpoint
•
Two or Four Events per Day Configuration
(T600xxP-4 and T600xxP-4+PIR Series)
•
Outside Air Dampers Minimum Position
•
Auxiliary Output Configuration
•
Mechanical Cooling Operation with Economizer
•
Enable/Disable Progressive Recovery
•
Mixed Air Temperature Setpoint
•
Displaying the Mixed Air Temperature
The following parameters are for the T600HPx-4 and
T600HPx-4+PIR Series Thermostat Controllers:
The following parameters are for the T600MEP-4 and
T600MEP-4+PIR Thermostat Controllers:
Repair Information
•
High Balance Point
•
Low Balance Point
•
Comfort/Economy Heat Pump Operation
If either the T600xxx-4 or T600xxx-4+PIR Series
Thermostat Controller fails to operate within its
specifications, replace the unit. For a replacement
thermostat controller, contact the nearest
Johnson Controls representative.
Technical Specifications
T600xxx-4 and T600xxx-4+PIR Series Thermostat Controllers (Part 1 of 2)
Power Requirements
19 to 30 VAC, 50/60 Hz, 2 VA (Terminals RC and C) at 24 VAC Nominal, Class 2
or Safety Extra-Low Voltage (SELV)
Relay Contact Rating
19 to 30 VAC, 1.0 A Maximum, 15 mA Minimum, 3.0 A Inrush, Class 2 or SELV
Digital Inputs
Voltage-Free Contacts across Terminal C to Terminals DI1 or DI2
Economizer Output (T600MEP-4 and
T600MEP-4+PIR Models)
0 to 10 VDC into 2k ohm Resistance Minimum
Wire Size
18 AWG (1.0 mm Diameter) Maximum, 22 AWG (0.6 mm Diameter)
Recommended
Temperature Sensor Type
Local 10k ohm Johnson Controls Type II Negative Temperature Coefficient (NTC)
Thermistor Sensor
Temperature Range
Backlit
Display
-40.0°F/-40.0°C to 122.0°F/ 50.0°C in 0.5° Increments
Heating
Control
40.0°F/4.5°C to 90.0°F/32.0°C
Cooling
Control
54.0°F/12.0°C to 100.0°F/38.0°C
Temperature
±0.9F°/±0.5C° at 70.0°F/21.0°C Typical Calibrated
Accuracy
Minimum Deadband
Ambient Conditions
2F°/1C° between Heating and Cooling
Operating
32 to 122°F (0 to 50°C); 95% RH Maximum, Noncondensing
Storage
-22 to 122°F (-30 to 50°C); 95% RH Maximum, Noncondensing
T600xxx-4 and T600xxx-4+PIR Series Thermostat Controllers Product Bulletin
7
T600xxx-4 and T600xxx-4+PIR Series Thermostat Controllers (Part 2 of 2)
Compliance
United States
UL Listed, File E27734, CCN XAPX,
Under UL 873, Temperature Indicating and Regulating Equipment
FCC Compliant to CFR 47, Part 15, Subpart B, Class A
Canada
UL Listed, File E27734, CCN XAPX7,
Under CAN/CSA C22.2 No. 24, Temperature Indicating and Regulating
Equipment
Industry Canada, ICES-003
Shipping Weight
Europe
CE Mark, EMC Directive 2004/108/EC
Australia and
New Zealand
C-Tick Mark, Australia/NZ Emissions Compliant
T600xxx-4
Models
0.75 lb (0.34 kg)
T600xxx-4+PIR
Models
0.77 lb (0.35 kg)
The performance specifications are nominal and conform to acceptable industry standards. For application at conditions beyond these
specifications, consult the local Johnson Controls office. Johnson Controls, Inc. shall not be liable for damages resulting from misapplication or
misuse of its products.
United States Emissions Compliance
This equipment has been tested and found to comply with the limits for a Class A digital device pursuant to Part 15 of the FCC Rules. These
limits are designed to provide reasonable protection against harmful interference when this equipment is operated in a commercial
environment. This equipment generates, uses, and can radiate radio frequency energy and, if not installed and used in accordance with the
instruction manual, may cause harmful interference to radio communications. Operation of this equipment in a residential area is likely to cause
harmful interference, in which case the user will be required to correct the interference at his/her own expense.
Canadian Emissions Compliance
This Class (A) digital apparatus meets all the requirements of the Canadian Interference-Causing Equipment Regulations.
Cet appareil numérique de la Classe (A) respecte toutes les exigences du Règlement sur le matériel brouilleur du Canada.
Building Efficiency
507 E. Michigan Street, Milwaukee, WI 53202
Metasys® and Johnson Controls® are registered trademarks of Johnson Controls, Inc.
All other marks herein are the marks of their respective owners. © 2009 Johnson Controls, Inc.
8
T600xxx-4 and T600xxx-4+PIR Series Thermostat Controllers Product Bulletin
Published in U.S.A.
www.johnsoncontrols.com
T600xxx-3 Series Thermostats
Product Bulletin
Code No. LIT-12011193
Issued September 6, 2006
The T600xxN-3 Series non-programmable and
T600xxP-3 Series programmable thermostats are
specifically designed for control of single-stage, multistage, and heat pump commercial heating and cooling
equipment. The T600xxP-3 Series thermostats are
also specifically designed for control of rooftop units
(with and without economizers).
The T600xxx-3 Series thermostats provide exceptional
temperature control in an easy-to-use, yet flexible,
package. The T600xxx-3 Series thermostats have over
20 configurable parameters, enabling the thermostats
to adapt to a variety of applications.
The T600xxx-3 Series thermostats include several
models: Single-stage (T600HCx-3), Heat Pump
(T600HPx-3), Multi-stage (T600MSx-3), and
Economizer (T600MEP-3). All thermostats use a
unique Proportional-Integral (PI) proportional control
algorithm that virtually eliminates temperature offset
associated with traditional differential based
thermostats.
Figure 1: T600xxx-3 Series Thermostat
Table 1: Features and Benefits
Features
Benefits
Backlit Liquid Crystal Display (LCD)
Offers real-time control status of the environment in easy-to-read,
English plain text messages with constant backlight that brightens
during user interaction.
Simplified Setpoint Adjustment
Enables user to change the setpoint by simply pressing the UP/DOWN
arrow keys.
Five Easy-to-Use Interface Keys
Allow for easy commissioning and adjustment of the thermostat and
eliminates the need for Dual Inline Package (DIP) switches.
Three Light-Emitting Diodes (LEDs)
Provide fan, heating, and cooling status at a glance
Two Configurable Digital Inputs
Provide additional inputs for advanced functions such as remote night
setback, occupancy override, and service or filter alarms.
Over 20 Configurable Parameters
Enable the thermostat to adapt to any application, allowing installer
parameter access without opening the thermostat cover.
Configurable Auxiliary Output
Provides 24 VAC control for exhaust fans, lighting, and other auxiliary
functions.
Economizer Output (T600MEP-3)
Controls economizer operation for single- and multi-stage unitary
rooftop equipment.
T600xxx-3 Series Thermostats Product Bulletin
1
Product Overview
•
The T600xxx-3 Series thermostats are specifically
designed for control of the most common commercial
heating and cooling equipment. A number of
configurable parameters enable the
T600xxx-3 Series thermostat to effectively and
efficiently control various types of equipment in nearly
any application. Configuration, setup, and operation of
the T600xxx-3 Series thermostat are extremely intuitive
and are accomplished through the user interface.
Adjustable Power Delay on Start-up
Enables a delay before any operation is authorized
upon power up of the thermostat. Can be used for
equipment protection or to sequence start-up of
multiple units in one location.
•
Remote Indoor and Outdoor Sensing
Accommodates remote indoor and outdoor
sensors. Up to three indoor sensors can be
averaged.
•
Three Levels of Keypad Lockout
Provide three different levels of keypad lockout that
can be set up through the menu and interface
keys.
•
Adjustable Anti-Short Cycling Timer
Adjusts the minimum on and off times for the
equipment from 0 to 5 minutes.
•
Frost Protection Enable/Disable
Turns the heat on when the zone temperature
drops below 42°F (5.5°C) regardless of the
thermostat’s mode.
•
Adjustable Temporary Occupancy Time
Adjusts the occupancy override time from
0 to 12 hours.
•
High and Low Balance Point Adjustments
Enable more precise control of heat pump
operation based on outdoor air temperature
(T600HPx-3).
•
System Mode Lockout
Allows the heating and cooling modes to be locked
out based on outdoor air temperature when an
outdoor air sensor is connected.
•
Non-volatile EEPROM Memory
Prevents loss of adjusted parameters during power
failure.
•
Power Loss Backup for Clock (T600xxP-3)
Retains clock setting for up to 6 hours in case of
power loss.
•
Heating and Cooling Stage Enable/Disable
(T600MEP-3, T600MSx-3)
Allows operation of the second-stage heating and
cooling to be disabled, reverting the thermostat to
single-stage operation on multi-stage thermostats.
•
Heat Pump Compressor Stage Enable/Disable
(T600HPx-3)
Allows operation of the second-stage compressor
to be disabled, reverting the thermostat to singlestage compressor operation on heat pump
thermostats.
The T600xxP-3 Series programmable thermostats
feature a fully programmable 7-day, 2- or 4-event
schedule, along with two programmable digital inputs
and one configurable output, enabling effective and
efficient control of equipment in nearly any application.
IMPORTANT: Use the T600xxx-3 thermostat only
as an operating control. Where failure or malfunction
of these thermostats could lead to personal injury or
property damage to the controlled equipment or
other property, additional precautions must be
designed into the system. Incorporate and maintain
other devices such as supervisory or alarm systems
or safety or limit controls intended to warn of, or
protect against, failure or malfunction of the
thermostats.
Additional Features
The T600xxx-3 Series thermostats also offer many
other features:
•
Adjustable Heating/Cooling Deadband
Adjusts the minimum heating/cooling deadband
from 2 to 4F° (1 to 2C°).
•
Adjustable Maximum Heating/Minimum Cooling
Setpoints
Establish the maximum heating setpoint and
minimum cooling setpoint that can be entered
through the user interface.
•
•
•
2
Progressive Recovery
Ensures the correct temperature is reached at the
programmed occupied time.
Adjustable Heating/Cooling Cycles per Hour
Configurable for a maximum of 3 to 8 heating
cycles and 3 or 4 cooling cycles in a 1-hour period,
balancing temperature control and equipment
cycling.
Smart Fan
Enables the fan to operate continuously during the
occupied times and cycle with the equipment
during the unoccupied times.
T600xxx-3 Series Thermostats Product Bulletin
•
Fan Operation Control
Enables the user to select how the fan operates on
a call for heating and the delay at the end of the
heating or cooling cycle.
•
access the Installer Configuration Menu or to
exit the menu
Use the UP/DOWN arrow keys to change the
configuration parameters and to activate a setpoint
adjustment.
Backlit Liquid Crystal Display (LCD)
Backlit
plain English text
LCD is
easy to read
in any condition.
4-15/16
(125)
Light-Emitting Diodes (LEDs)
Room Temp
70.0ºF
Three LEDs are included to indicate the fan status, call
for heat, or call for cooling on the T600HCx-3,
T600MSx-3, and T600MEP-3 thermostats:
LEDs indicate
system activity.
Five keys
make operation
easy and intuitive.
3-3/8
(86)
FIG:T600_frnt
1-1/8
(29)
Figure 2: T600 Thermostat
Thermostat User Interface Keys
The T600xxx-3 Series thermostat user interface
consists of five keys on the front cover (as illustrated in
Figure 2). The function of each key is as follows:
•
The T600xxx-3 Series thermostat includes a 2-line,
8-character backlit display. Low-level backlighting is
present during normal operation, and it brightens when
any user interface key is pressed. The backlight returns
to low level when the thermostat is left unattended for
45 seconds.
Use the YES/SCROLL key to:
-
confirm menu selections and to advance to the
next menu item
-
stop the Status Display Menu from scrolling
and to manually scroll to the next parameter on
the menu
•
The FAN LED is on when the fan is on.
•
The HEAT LED is on when heating is on.
•
The COOL LED is on when cooling is on.
On the T600HPx-3 thermostats, the three LEDs
indicate heat pump operation.
•
The FAN LED is on when the fan is on.
•
The AUX HEAT LED is on when auxiliary heat is
on
•
The HEAT-PUMP LED is on when the heat-pump
compressor is on.
Programming Overview
There are three menus used to view, program, and
configure the T600xxx-3 Series thermostat:
The Status Display Menu is displayed during normal
thermostat operation. This menu continuously scrolls
through the following parameters:
•
Room Temperature
•
Day and Time (T600xxP-3)
Note: When the thermostat is left unattended for
45 seconds, the thermostat display resumes
scrolling.
•
System Mode
•
Occupancy Status – Occupied/Unoccupied/
Override
•
Use the NO key to decline a parameter change and
to advance to the next menu item.
•
Outdoor Temperature – An outdoor air temperature
sensor must be connected.
•
Use the MENU key to:
•
Applicable Alarms – The backlight lights up as an
alarm condition is displayed.
-
access the Main User Menu or exit the menu
Note: Press the YES/SCROLL key to temporarily stop
this menu from scrolling.
T600xxx-3 Series Thermostats Product Bulletin
3
The Main User Menu is used to access and change
the basic operating parameters of the thermostat.
Access this menu by pressing the MENU key during
normal thermostat operation.
The Installer Configuration Menu is used to set up
the thermostat for application-specific operation. To
access this menu, press and hold the MENU key for
approximately 8 seconds.
The Installer Configuration Menu includes the following
parameters that are accessed by pressing the same
MENU key:
•
Number of Heat Pump Stages (T600HPx-3)
•
Heating Operation Lockout Based on Outdoor Air
Temperature
•
Cooling Operation Lockout Based on Outdoor Air
Temperature
•
Two or Four Events per Day Configuration
(T600xxP-3)
•
Auxiliary Output Configuration
•
Enable/Disable Progressive Recovery
•
DI1 and DI2 Input Configuration
The following parameters are for the T600HPx-3
thermostats:
•
Three Keypad Lockout Levels
•
Low Balance Point
•
Power Delay on Power up
•
High Balance Point
•
Frost Protection
•
Comfort/Economy Heat Pump Operation
•
Maximum Heating Setpoint/Minimum Cooling
Setpoint
•
Reversing Valve Operation
•
Anti-Short Cycle Timer
•
Compressor/Auxiliary Interlock
•
Heating Stages Cycles per Hour
•
Cooling Stages Cycles per Hour
•
Minimum Deadband
•
Fan Control
•
End of Cycle Fan Delay
•
Temporary Occupancy Time
•
Room Air Sensor Calibration
•
Outdoor Air Sensor Calibration
•
Number of Heating Stages (T600MSx-3 and
T600MEP-3)
•
Number of Cooling Stages (T600MSx-3 and
T600MEP-3)
The following parameters are for the T600MEP-3
thermostat:
•
Economizer Changeover Setpoint
•
Outdoor Air Minimum Position
•
Mechanical Cooling Operation w/ Economizer
•
Mixed Air Temperature Setpoint
•
Displaying the Mixed Air Temperature
Repair Information
If the T600xxx-3 Series thermostat fails to operate
within its specifications, replace the unit. For a
replacement T600xxx-3 Series thermostat, contact the
nearest Johnson Controls® representative.
Ordering Information
Table 2: T600xxx-3 Series Thermostats (Part 1 of 2)
Code Number
Description
Applications
T600HCN-3
Single-stage
Fan Coil Units, Unit Heaters, and Single-stage Packaged Heating/Cooling Equipment
T600HPN-3
Heat Pump
Heat Pump with up to 3 Heating/2 Cooling Stages
T600MSN-3
Multi-stage
Multi-stage Packaged Heating/Cooling Equipment
Non-Programmable
4
T600xxx-3 Series Thermostats Product Bulletin
Table 2: T600xxx-3 Series Thermostats (Part 2 of 2)
Programmable
T600HCP-3
Single-stage
Fan Coil Units, Unit Heaters, and Single-stage Packaged Heating/Cooling Equipment
T600HPP-3
Heat Pump
Heat Pump with up to 3 Heating/2 Cooling Stages
T600MEP-3
Economizer
Packaged Rooftop Units with Economizers
T600MSP-3
Multi-stage
Multi-stage Packaged Heating/Cooling Equipment
Table 3: Accessories (Order Separately)
Code Number
Description
SEN-600-1
Remote Indoor Air Temperature Sensor
SEN-600-4
Remote Indoor Air Temperature Sensor with Occupancy Override and LED
TE-6361P-1
8 in. (203 mm)1 Duct Mount Air Temperature Sensor
TE-6363P-1
Outdoor Air Temperature Sensor
1.
Other probe lengths available.
T600xxx-3 Series Thermostats Product Bulletin
5
Technical Specifications
T600xxx-3 Series Thermostats
Power Requirements
19 to 30 VAC, 50/60 Hz, 2 VA (Terminals 4 and 5) at 24 VAC Nominal, Class 2 or
Safety Extra-Low Voltage (SELV)
Relay Contact Rating Maximum
Inductive
30 VAC, 1.0 A Maximum, 3.0 A In-Rush
Digital Inputs
Voltage-Free Contacts across Terminal C to Terminals DI1 or DI2
Economizer Output
0 to 10 VDC into 2k ohm resistance minimum (T600MEP-3 only)
Recommended Wire Size
18 AWG (1.0 mm Diameter) Maximum, 22 AWG (0.6 mm Diameter) Recommended
Sensor Type
Local 10k ohm NTC thermistor
Temperature Range
Accuracy
Backlit
Display
-40.0°F/-40.0°C to 122.0°F/ 50.0°C in 0.5° Increments
Heating
Control
40.0°F/4.5°C to 90.0°F/32.0°C
Cooling
Control
54.0°F/12.0°C to 100.0°F/38.0°C
Temperature
±0.9F°/±0.5C° at 70.0°F/21.0°C Typical Calibrated
Minimum Deadband
Ambient Conditions
2F°/1C° between Heating and Cooling
Operating
32 to 122°F (0 to 50°C); 95% RH Maximum, Noncondensing
Storage
-22 to 122°F (-30 to 50°C); 95% RH Maximum, Noncondensing
Dimensions (H x W x D)
4.94 x 3.38 x 1.13 in. (125 x 86 x 29 mm)
Compliance
UL Listed, File E27734, CCN XAPX,
Under UL 873, Temperature Indicating and Regulating Equipment
United States
FCC Compliant to CFR 47, Part 15, Subpart B, Class A
Canada
UL Listed, File E27734, CCN XAPX7,
Under CAN/CSA C22.2 No. 24, Temperature Indicating and Regulating Equipment
Industry Canada, ICES-003
Europe
CE Mark, EMC Directive 89/336/EEC
Australia and
New Zealand
C-Tick Mark, Australia/NZ Emissions Compliant
Shipping Weight
0.75 lb (0.34 kg)
The performance specifications are nominal and conform to acceptable industry standards. For application at conditions beyond these
specifications, consult the local Johnson Controls office. Johnson Controls, Inc. shall not be liable for damages resulting from misapplication or
misuse of its products.
United States Emissions Compliance:
This equipment has been tested and found to comply with the limits for a Class A digital device pursuant to Part 15 of the FCC Rules. These
limits are designed to provide reasonable protection against harmful interference when this equipment is operated in a commercial
environment. This equipment generates, uses, and can radiate radio frequency energy and, if not installed and used in accordance with the
instruction manual, may cause harmful interference to radio communications. Operation of this equipment in a residential area is likely to cause
harmful interference, in which case the user will be required to correct the interference at his/her own expense.
Canadian Emissions Compliance:
This Class (A) digital apparatus meets all requirements of the Canadian Interference-Causing Equipment Regulations.
Cet appareil numérique de la Classe (A) respecte toutes les exigences du Règlement sur le matériel brouiller du Canada.
Controls Group
507 E. Michigan Street
Milwaukee, WI 53202
6
.
All other marks herein are the marks of their respective owners.
© 2006 Johnson Controls, Inc.
T600xxx-3 Series Thermostats Product Bulletin
Published in U.S.A.
www.johnsoncontrols.com