Specifications
and Performance
NOTICE
An ISO 9001-2000 Certified Company
The VPRC/VPRH is backed by EMI and ECR International and is tested and rated in
accordance with ARI Standard 390, UL-484 and UL-1995. Due to ongoing product
development, product designs and specifications may change without notice. Please
contact the factory for more information.
P/N 240007449, Rev. N [08/02/2012]
VPRC/VPRH Vertical Packaged Air Conditioner/Heat Pump
• Specifications and Performance •
General Product Information
Product description
• Condensate removal
–– VPRC/VPRH 09, 12, 19 & 24 — The outdoor blower incorporates a condensate slinger ring. Base pans are designed to
accommodate a field-installed drain stub kit if necessary. See
field installed accessories.
–– VPRC/VPRH 18, 30 & 36 require an internal drain system.
Models VPRC/VPRH 18 are supplied standard with an
overflow drain stub kit for field installation.
–– VPRC/VPRH 30-36 outdoor coil side drain stub is integral
to the base pan, and allows easy connection of the drain line.
• Microprocessor control board
–– Universal control board is used in straight cool electric resistance heat, hydronic heat (models 09–24 only), or cooling/
heat pump applications
–– Random start timer prevents multiple units from simultaneous start-ups
–– Fan purge — fan remains on for 60 seconds after heat/cool
call is satisfied
–– Anti-short-cycle compressor protection prevents the compressor from rapid cycling
–– Freeze protection — prevents evaporator coil freeze up,
improving compressor reliability
–– Low ambient lockout prevents compressor operation in outdoor temperatures less than 40°F (4.4°C)
–– Test operation — all timers are temporarily suppressed to
allow ease of testing or troubleshooting
–– Control board LED provides self-diagnostic troubleshooting
codes (see Sequence of Operation, page 9)
The VPRC/VPRH 09–36 single package vertical air conditioner
(SPVAC) and heat pump (SPVHP) creates new options in layout and
space utilization. The VPRC/VPRH 09–36 offers low cost operation
and quiet, comfortable air distribution, especially when used in multiroom suites, apartments, health care facilities, and homes.
Each system utilizes environmentally-friendly R-410A refrigerant,
and is supplied with a custom wall sleeve and outdoor louver. The
cabinet is constructed with 20 gauge galvanized steel with a G-90U
corrosion-resistant rating. The insulated top-discharge indoor compartment provides quiet, ducted, conditioned air delivery to other
room location(s).
Framed into a concealed closet enclosure for low operating sound
levels, the VPRC/VPRH vertical discharge allows ducting to the top
of the room(s) for superior air circulation and distribution.
All VPRC/VPRH models can be applied in non-ducted return air
applications. The VPRC/VPRH 30-36 can also be applied in ducted
return air applications.
The VPRC/VPRH offers an economic benefit when used in a multiroom suite by supplying conditioned air to more than one room without the need to install additional units. This is also a design advantage
since other rooms will not need an exterior wall to accommodate
additional units.
VPRH models are limited-range heat pumps — heat pump operation will cease at approximately 40°F (4.4°C) outdoor temperature.
Utilizing the electric resistant heat option or the hydronic heat option
is recommended if the heating load of the application will require the
unit to operate in outdoor ambient temperatures below 40°F (4.4°C).
Factory-installed options:
• Supplemental electric heat — see heat options in Figure 1
• 265/277V (contact factory for availability)
• Corrosion-resistant coil options (sea coast and harsh environment usage):
–– Coated aluminum fin/copper tube condenser coil
• Models 09–18 only — 10-inch diameter (254 mm) factoryinstalled duct collar
• Models 09–12 only — Carrier Model 50QT/ET replacement
configuration
• Models 09–24 only — Right or left control box mounting
• Models 09–24 only — Hydronic heat option
• Models 09–24 only — Power disconnect switch — ONLY to a
maximum of 5kW electric heat, or hydronic heat
Standard controls and components:
• Cooling or heat pump chassis with high efficiency rotary, scroll or
reciprocating type compressors
• Custom wall sleeve
• Anodized aluminum outdoor louver for indoor field installation
(optional colors available)
• R-410A refrigerant
• Ability to utilize single or 2-stage thermostat for VPRH emergency heat
• Front-mounted control box standard for 09–36 (right or left-side
mounting available for 09–24 only)
• Manual fresh air damper for models 09–24 — motorized fresh air
damper for models 30–36
• Filter — disposable return air filter for models 09–24 only, and a
washable, reusable return air filter for models 30–36 only
• Thermostatic drain pan valve for heat pump operation condensate
removal (VPRH 09, 12, 19–24 only)
• Air systems
–– Motors are thermally protected PSC type. Air stream surfaces
are insulated with 1/4 inch (6.3 mm) fiberglass or 1/8 inch
(3.2 mm) VolaraTM.
–– The indoor fan is a forward-curved type directly mounted to
the motor shaft.
–– Models VPRC/VPRH 09, 12, 19 & 24 blow air across the
outdoor coil, while models VPRC/VPRH 18, 30 & 36 draw
air through the outdoor coil.
The Right Fit for Comfort
Field-installed accessories:
•
•
•
•
Hydronic heat plenum (coil included on models 09–24 only)
Remote wall thermostat (digital 1-stage or 2-stage available)
Painted condenser louver — (baked enamel/Kynar)
Return air access panel (standard white, consult factory for custom
colors — w/disposable return air filters) — optional solid panel
available for application with separate air intake
• Models 09, 12, 19–24 only — Overflow drain stub kit — can be
installed on front, right side or left side.
• Wall sleeve transition kit Model 30 only - Needed when replacing
a VPAC/VPHP 30 with a VPRC/VPRH 30 (See Pgs 3 & 30)
2
P/N 240007449, Rev. N [08/02/2012]
VPRC/VPRH Vertical Packaged Air Conditioner/Heat Pump
• Specifications and Performance •
General Product Information (continued)
Models 09–24
Models 30–36
1
1
Supply
Supply
Outside louver
Return
Outside louver
Return
12
8
11
8
8
3
4
3
10
Wall sleeve,
custom for application
10
Front — 09, 12, 18, 19, 24
1
2
3
4
5
6
7
8
9
10
11
12
Indoor coil (behind filter)
Outdoor coil
Control/power box
Alternate control box location
(right or left side)
Thermostatic drain valve
(09, 12, 19 and 24 only)
24-volt connection strip
Power cord strain relief
(for units with power cords)
Line voltage power entrances
(for hard-wired units)
Optional disconnect switch
Drain stub location options
(front, right or left side) — ½”
Fresh air shutter
Return air filter (see Table 2,
page 7 for dimensions)
Wall sleeve,
custom for application
6
Front — 30, 36
3
3
1
2
3
4
5
Indoor coil (behind filter)
Outdoor coil
Control/power box
24-volt connection strip
Line voltage power
entrances
6 Drain stub location — ¾”
7 Motorized fresh air damper
switch
8 Return air filter (see Table 2,
page 7 for dimensions)
7
6
9
Control panel, typical
09–24
4
5
7
Control panel, typical
30, 36
4
Rear — 18
2
2
5
10
Rear — 09, 12, 19, 24
Rear — 30, 36
P/N 240007449, Rev. N [08/02/2011]
3
Transition Kit #55002100
(Req’d if replacing VPAC/HP30)
Made in USA
VPRC/VPRH Vertical Packaged Air Conditioner/Heat Pump
• Specifications and Performance •
General Product Information (continued)
Figure 1
Model nomenclature
Position:
1, 2, 3, 4
5, 6
7
8
9
10
11
12
13
14
15
Example:
V P R C
1 2
D
5
1
B
A
B
T
0
A
Product Series:
VPRC - Straight Cool Unit
VPRH - Heat Pump Unit
Design Revision:
A - Revision Level
Compressor Code:
0 - Standard
A - Z Special Option
Cooling Capacity (Btuh):
09 - 9,000
24 - 24,000
12 - 12,000
30 - 30,000
18 - 17,000
36 - 36,000
19 - 18,000
Compressor Code:
T - Rotary (09-12 Btuh Only)
C - Recip (18, 24, 30, 36 Btuh Only)
S - Scroll (19 Btuh Only)
Voltage Option:
D - 208/230 - 1 - 60
E - 265/277 - 1 - 60
Condenser Coil Option and Filter:
B - Factory Installed Filter
C - Coated Coil and Factory Installed Filter
Heat Options (230 Volts):
0 - No Heat (09-36)
3 - 3kW Elect Heat (09-24 Btuh)
4 - 4kW Elect Heat (09-24 Btuh)
5 - 5kW Elect Heat (09-36 Btuh)
7 - 7kW Elect Heat (19-36 Btuh)
1 - 10kW Elect Heat (19-36 Btuh)
A - 15kW Elect Heat (36 Btuh)
8 - Hydronic Coil (09-24 Btuh)
Controls Options:
1 - Remote, Front Control Access
2 - Remote, Right Control Access
3 - Remote, Left Control Access
4 - Remote, Front Control, Disconnect Switch (2-5kW 09-24 Btuh Only)
5 - Remote, Right Control, Disconnect Switch (2-5kW 09-24 Btuh Only)
6 - Remote, Left Control, Disconnect Switch (2-5kW 09-24 Btuh Only)
The Right Fit for Comfort
4
Options:
A - NON - Hydronic models
B - Right Hand Piping with Sweat Connections
C - Left Hand Piping with Sweat Connections
D - Front Hand Piping with Sweat Connections
E - Right Hand Piping with Ball Valves and P/T Ports
F - Left Hand Piping with Ball Valves and P/T Ports
G - Front Hand Piping with Ball Valves and P/T Ports
H - Right Hand Piping with Auto Valves
J - Left Hand Piping HYD with Auto Valves
K - Front Hand Piping HYD with Auto Valves
Options:
A - 10” Round Duct Collar
B - Standard
C - 50QT Option
P/N 240007449, Rev. N [08/02/2012]
VPRC/VPRH Vertical Packaged Air Conditioner/Heat Pump
• Specifications and Performance •
Operational Performance Data
IMPORTANT
Tested/Rated
in Accordance with
ARI Standard 390
Performance data is subject to change without notice. For the most current unit/
system performance data, please refer to the Enviromaster International listing
of certified products in the ARI certified directory, at www.ahridirectory.org.
Due to ongoing product development, designs, specifications, and performance
are subject to change without notice. Please consult the factory for further
information.
Table 1
Model
VPRC/VPRH 09–36 performance data
Cooling
Btuh (kW)
Sensible
Heat
Ratio
EER
Heat Pump
Btuh (kW)
COP
Air Flow vs External Static Pressure
Static Pressure
0.10 in. w.c. 0.20 in. w.c. 0.30 in. w.c.
(2.5 mm
(5.1 mm (7.6 mm w.c.)
w.c.)
w.c.)
CFM (L/s)
CFM (L/s)
CFM (L/s)
VPRC09
9,000 (2.64)
0.75
9.0
N/A
N/A
330 (156)
300 (142)
250 (118)
VPRH09
9,000 (2.64)
0.75
9.0
9,000 (2.64)
3.0
330 (156)
300 (142)
250 (118)
VPRC12
12,000 (3.51)
0.70
9.0
N/A
N/A
440 (208)
385 (182)
350 (165)
VPRH12
12,000 (3.51)
0.70
9.0
11,400 (3.34)
3.0
440 (208)
385 (182)
350 (165)
VPRC18
17,200 (5.04)
0.71
9.0
N/A
N/A
600 (283)
550 (260)
500 (236)
VPRH18
17,200 (5.04)
0.71
9.0
16,200 (4.75)
3.0
600 (283)
550 (260)
500 (236)
VPRC19
18,400 (5.39)
0.73
9.0
N/A
N/A
710 (335)
650 (307)
600 (283)
VPRH19
18,400 (5.39)
0.73
9.0
16,400 (4.81)
3.0
710 (335)
650 (307)
600 (283)
VPRC24
23,200 (6.80)
0.73
9.0
N/A
N/A
710 (335)
650 (307)
600 (283)
VPRH24
23,200 (6.80)
0.73
9.0
21,600 (6.33)
3.0
710 (335)
650 (307)
600 (283)
VPRC30
31,600 (9.26)
0.69
9.0
N/A
N/A
1,190 (562)
1,170 (552)
1,130 (533)
VPRH30
31,600 (9.26)
0.69
9.0
32,000 (9.38)
3.0
1,190 (562)
1,170 (552)
1,130 (533)
VPRC36
35,600
(10.43)
0.73
9.0
N/A
N/A
1,350 (637)
1,290 (609)
1,210 (571)
VPRH36
35,600
(10.43)
0.73
9.0
P/N 240007449, Rev. N [08/02/2011]
36,000 (10.55)
3.0
5
1,350 (637)
1,290 (609)
Fresh
Air
Inlet
Flow
Outdoor
Sound
Level
CFM
(L/s)
dBa
30
65
35
75
40
71
50
69
60
70
95
69
95
69
1,210 (571)
Made in USA
VPRC/VPRH Vertical Packaged Air Conditioner/Heat Pump
• Specifications and Performance •
Dimensional Data
IMPORTANT
Due to ongoing product development, designs, specifications, and performance are subject to change without notice. Please consult
the factory for further information.
Figure 2
VPRC/ VPRH dimensions — inches (mm)
M
K
K
L
J
A
K
M
A
L
J
H
L
M
A
B
G
H
G
F
J
D
B
G
B
E
E
REAR
O
TYP
E
REAR
F
REAR
C
D
O
TYP
D
VPRC/VPRH
09, 12, 19 & 24
16"H X 25"W
RETURN
AIR FILTER
FRONT
N
C
VPRC/VPRH
18
VPRC/VPRH
30-36
20"H X 26"W
RETURN
AIR FILTER
16"H X 25"W
RETURN
AIR FILTER
FRONT
FRONT
N
N
The Right Fit for Comfort
6
P/N 240007449, Rev. N [08/02/2012]
VPRC/VPRH Vertical Packaged Air Conditioner/Heat Pump
• Specifications and Performance •
Dimensional/Physical Data (continued)
IMPORTANT
Due to ongoing product development, designs, specifications, and performance are subject to change without notice. Please consult
the factory for further information.
Table 2
Dimensions, shipping weights and return air filter sizes
Model
Dimension
09–12
in. (mm)
18
in. (mm)
19-24
in. (mm)
30
in. (mm)
36
in. (mm)
A
7 5/8 (194)
7 3/4 (197)
6 1/2 (165)
8 3/4 (222)
8 3/4 (222)
B
40 (1016)
40 (1016)
50 (1270)
56 (1422)
56 (1422)
C
21 7/16 (545)
21 7/16 (545)
26 7/16 (672)
D
25 (635)
25 (635)
25 (635)
28 (711)
28 (711)
E
14 5/8 (372)
14 13/16 (376)
20 5/8 (524)
21 3/4 (553)
21 3/4 (553)
F
25 (635)
24 5/8 (625)
32 (813)
G
10 5/16 (261)
9 13/16 (249)
11 3/8 (289)
6 1/4 (159)
6 1/4 (159)
H
3 1/2 (89)
3 1/2 (89)
3 1/2 (89)
J
16 1/2 (419)
16 1/2 (419)
21 9/16 (548)
28 (711)
28 (711)
K
6 1/8 (156)
6 1/8 (156)
8 3/16 (208)
11 1/4 (286)
11 1/4 (286)
L
9 5/8 (245)
9 1/2 (241)
12 (305)
10 1/4 (260)
10 1/4 (260)
M
4 1/4 (108)
4 1/4 (108)
10 3/8 (264)
16 (406)
16 (406)
N
12 1/2 (317)
12 1/2 (317)
12 1/2 (317)
1 5/8 (41)
1 5/8 (41)
O
8 3/4 (222)
8 3/4 (222)
13 3/4 (348)
Model
Shipping weight — pounds (kg)
Return air filter dimensions — inches (mm)
All models must have an air filter installed prior to operation.
(shipping weight = unit weight + 60 lbs (27 kg)
Chassis mounted
Return air access panel mounted
09
190 (86)
16 x 25 (406 x 635)
20 x 20 (508 x 508)
12
190 (86)
16 x 25 (406 x 635)
20 x 20 (508 x 508)
18
260 (118)
16 x 25 (406 x 635)
20 x 20 (508 x 508)
19
300 (136)
16 x 25 (406 x 635)
20 x 30 (508 x 762)
24
300 (136)
16 x 25 (406 x 635)
20 x 30 (508 x 762)
30
430 (195)
20 x 26 (508 x 660)
20 x 30 (508 x 762)
36
430 (195)
20 x 26 (508 x 660)
20 x 30 (508 x 762)
P/N 240007449, Rev. N [08/02/2011]
7
Made in USA
VPRC/VPRH Vertical Packaged Air Conditioner/Heat Pump
• Specifications and Performance •
Features
Hydronic heat operation (optional)
Emergency heat (optional)
NOTE
An optional factory-supplied, field-installed hydronic heat package
is available. With the thermostat system switch set to heat and the
setpoint temperature above room temperature, the hydronic valve
will open allowing water to flow through the coil. The indoor fan
will also switch on and warm air will flow from the unit. Heating will
continue as long as the setpoint remains above room temperature.
Place the setpoint temperature below room temperature. The hydronic
valve will close and indoor fan will switch off after the sixty-second
purge time has elapsed. The hydronic valve is a 24vac normally open
valve. Should power be lost to the unit, the valve will default to the
open position.
VPRH units
ECR International recommends using a factory-supplied,
field-installed two-stage thermostat with heat pump
units (VPRH) equipped with electric resistance heat option. In the event of heat pump system failure, the two-stage
thermostat will automatically switch the unit’s control from
heat pump mode to electric heat mode.
If a single-stage thermostat is used and the heat
pump system fails, it is possible to manually force the
control board into electric heat mode.
VPRC units
Use a single-stage heat/cool thermostat, available as a
factory option.
The hydronic package is equipped with a thermostat (freeze-stat) that
is designed to prevent the hydronic coil from freezing. At 35°F (1.7°C)
the thermostat will switch open the hot water valve to prevent the coil
from freezing. At 50°F (10°C) the thermostat will reset. If the room
thermostat is not calling for heat, the valve will close. The freeze stat
is factory preset.
Anti-short-cycle timer (standard)
This feature prevents compressor short cycling. It also prevents
multiple units from starting simultaneously after a power outage.
This delay-on-break feature ensures that the compressor remains off
between cycles until the three-minute time delay period has elapsed,
allowing system pressures to equalize before restarting.
Coil freeze protection (standard)
This feature prevents the coil from freeze up in the cooling mode. Coil
freeze up can occur due to a dirty air filter, low refrigerant charge or
low room or outdoor temperatures. This in turn can cause compressor
damage. Should a freeze condition be detected, the compressor and
condenser fan will be switched off for a minimum of three minutes
and until the freeze condition is satisfied. During this time the indoor
fan will continue to run to aid in the defrost process.
Random start timer (standard)
Thermostatic drain valve
Carrier 50QT/ET replacement (optional)
The random start feature, initiated after a power failure, will add a
random time delay (from 5 to 120 seconds) to the three-minute anti
short cycle time following a power outage. This will stagger the starting of multiple units in a single facility allowing a building to slowly
go back on line when power is restored.
(standard — VPRH 09, 12, 19 & 24 only)
The VPRC/VPRH 09–18 can be used to replace the Carrier 50QT/
ET series PTAC and older vertical PTAC’s from other manufacturers . Refer to Figure 1 on page 4 “Options” when ordering a Carrier
50QT/ET replacement. Model 18 can be field-modified with a simple
extension of the outdoor air baffle. Consult your ECR International
sales representative for more information.
Heat pump units are equipped with a thermostatic drain valve that
will open when outdoor temperatures fall below 50°F (10°C). This
keeps the base pan free of condensate water where it may otherwise
freeze during colder outdoor temperatures.
The Right Fit for Comfort
8
P/N 240007449, Rev. N [08/02/2012]
VPRC/VPRH Vertical Packaged Air Conditioner/Heat Pump
• Specifications and Performance •
Sequence of Operation
Initial power-up or power restoration
Cooling operation
When power is applied to the unit, either for the first time or after a
power failure, the board will initialize itself. During the initialization,
LED1 will be lit continuously for approximately 5 seconds.
If the room temperature is above the thermostat setting, the reversing
valve (VPRH only) will be energized. The compressor and outdoor
fan will start provided the Anti-Short Cycle Timer has timed out from
the initial power-up, power restoration or a previous compressor on
cycle. Operation will continue until the room temperature satisfies
the thermostat. Once the room temperature falls below the set point
by 3 ºF (2 ºC), the compressor, outdoor fan motor and reversing valve
(VPRH only) will de-energize.
Following initialization, a random-start timer is initiated. This timer
adds a randomly selected 5-120 seconds to the start-up sequence,
reducing the possibility of multiple units starting at the same time.
Once the random start timer has expired, a 180-second anti-shortcycle timer is initiated. LED1 blinks a two-flash code. (The antishort-cycle timer prevents the compressor from rapid cycling.) After
the anti-short-cycle timer expires, LED1 blinks a one-blink code,
indicating normal operation.
Figure 3
As soon as the compressor is de-energized, the anti-short-cycle timer
will be initialized and will prevent the compressor from starting again
for another 180 seconds. While the anti-short-cycle timer is active,
the LED1 is set to blink a two-flash code. After the anti-short-cycle
timer expires, the LED1 is set to blink a one-blink code, indicating
normal operation.
Indicator LED1
Mechanical heating (VPRH only)
If the outdoor coil temperature remains above 25 ºF (-4 ºC), the
compressor and outdoor fan will start provided the anti-short-cycle
timer has timed out from the initial power-up, power restoration or a
previous compressor on cycle. Operation will continue until the room
temperature satisfies the thermostat.
LED1
Once the room temperature rises above the set point by 3 ºF (2 ºC),
the compressor and outdoor fan motor will de-energize.
As soon as the compressor is de-energized, the anti-short-cycle timer
will be initialized and will prevent the compressor from starting again
for another 180 seconds. While the anti-short-cycle timer is active,
LED1 blinks a two-flash code. After the anti-short-cycle timer expires,
LED1 flashes a one-blink code, indicating normal operation.
Auxiliary heating
If the outdoor coil temperature falls to 25 ºF (-4 ºC) or below for
180 seconds at anytime during a heating call, the compressor and
outdoor fan motor will be de-energized and auxiliary heat will be
energized. The anti-short-cycle timer will be initiated, prohibiting
compressor operation for 180 seconds. LED1 will flash a three-blink
code, indicating auxiliary heat operation. Heating operation with
auxiliary heat will continue until the outdoor coil sensor reaches
50 ºF (10 ºC).
Fan operation
Some thermostats are equipped with an auto/on fan switch.
• When this switch is placed in the on position the indoor fan will
run continuous.
• When the switch is in the auto position the indoor fan will cycle
with the call for heating or cooling.
Hydronic heating
• Fan purge (auto mode only) — after the room thermostat has
been satisfied, the purge feature allows the indoor fan to remain on
for an additional 60 seconds. This increases efficiency by pulling
the remaining energy from the unit.
With a call for heat, a signal from the processor board will activate
the water or steam valve and the indoor fan. The signal to the water
or steam valve will continue until the room temperature rises above
the set point by 3 ºF (2 ºC).
P/N 240007449, Rev. N [08/02/2011]
9
Made in USA
VPRC/VPRH Vertical Packaged Air Conditioner/Heat Pump
• Specifications and Performance •
Electrical Connections
Electrical connections
Choosing a thermostat
All field wiring must be done in accordance with the National Electrical Code, ANSI/NFPA 70–latest edition, and local codes (in Canada
— CSA C22.1 Canadian Electrical Code Part 1 and local codes).
ECR International offers your choice of a single-stage or two-stage
mercury-free thermostat that is compatible with all models of the
VPRC/VPRH. (Use a two-stage thermostat for VPRH units equipped
with the electric heat option.)
Check the VPRC/VPRH ratings. The installer is responsible for ensuring that VPRC/VPRH units are installed in accordance with all
applicable national and local codes. Check the rating plate for circuit
ampacity. Size the breaker(s) or fuse size(s) accordingly.
• RetroAire™ thermostats have digital readout with a temperature
control range from 45°F (7°C) to 90°F (32°C).
• Use only HACR type breakers or time delay fuses.
• When using a thermostat other than one offered by ECR International, use ONLY a 24v heat/cool thermostat.
• Select the proper wire for the breaker or fuse size used.
Cooling-only with electric or hydronic heat
(VPRC only)
• Some units require more than one power supply.
• Select a thermostat that is compatible with a cooling/electric
heat system.
• If a plug and receptacle are used, check for proper fit.
• Check the nameplate and wiring diagram for further instructions
and wire connections.
• The thermostat should have “R”, “Y”, “W” and “G” terminals.
• Each unit is equipped for a 24v wall thermostat connection.
(VPRH only)
Heat pump with electric heat
Single-stage thermostat
NOTICE
VPRC/VPRH units are wired for 230v primary voltage
from the factory. The transformer must be rewired by the
installer if the jobsite voltage is 208v.
Power cord with integral safety protection
All VPRC/VPRH units that are cord connected to the power supply
are equipped with a power cord with an integral sensor that:
Select a thermostat that is compatible with a cooling/single stage
heat/heat pump system.
• The thermostat should have “R”, “Y”, “O” and “G” terminals.
RetroAire™ units are single stage heating only.
• The electric heat and heat pump will not operate simultaneously.
Two-stage thermostat
• Provides personal shock protection.
A two-stage heat pump thermostat can be used with VPRH units.
• Provides arcing and fire prevention.
• See the wiring diagram for connections.
• Senses any damage in the line cord and disconnects power before
a fire can occur.
Tested in accordance with Underwriters Laboratories, the cord set
also offers a unique “passive” operation, meaning the unit does not
require resetting if main power is interrupted.
• VPRH units are designed to operate as single stage heat pumps —
they will alternate between heat pump and electric heat to meet
the heat demand.
Disconnect switch (optional)
The disconnect switch ensures that all power to the control box is
disconnected for servicing.
The Right Fit for Comfort
10
P/N 240007449, Rev. N [08/02/2012]
VPRC/VPRH Vertical Packaged Air Conditioner/Heat Pump
• Specifications and Performance •
Electrical Specifications
NOTICE
All field wiring must be done in accordance with the National Electrical Code, ANSI/NFPA 70–latest edition, and local codes (in Canada
— CSA C22.1 Canadian Electrical Code Part 1 and local codes).
Table 4
Legend for electrical specifications
FLA
Min
Full Load Amps
Minimum
Maximum Overcurrent Protection Device Amps
(HACR-type breakers or time-delay fuses)
H-WIRE
Hard Wired
MOCP
HA
Heater Amps
OFM
Outdoor Fan Motor
Hp
Horse Power
RLA
Rated Load Amps
Htr #
Heater Option Number (see Figure 1)
TCA
Total Cooling Amps
IFM
Indoor Fan Motor
THA
Total Heating Amps
LRA
Locked Rotor Amps
Volt
Voltage
Max
Maximum
MCA
Maximum Circuit Ampacity
Table 3
W
Watts
NEMA Specifications Non-Locking/Receptacles
IMPORTANT
Due to ongoing product development, designs, specifications, and performance are subject to change without notice. Please consult
the factory for further information.
P/N 240007449, Rev. N [08/02/2011]
11
Made in USA
VPRC/VPRH Vertical Packaged Air Conditioner/Heat Pump
• Specifications and Performance •
Electrical Specifications (continued)
Table 5
VPRC/VPRH 9,000 BTU electrical specifications
Power Supply
Volt — 1–60
Volt
Min
Compressor
RLA
LRA
Indoor Fan
Motor
FLA
Hp
Outdoor Fan
Motor
FLA
Hp
Electric Heat
Htr #
0 or 8
208/
230V
3
197
20
0.80
0.07
0.72
0.125
4
5
3.9
0 or 8
2
265V
240
18.8
0.56
0.07
1.2
0.125
3
4
Volt
208
230
208
230
280
230
208
230
265
277
265
277
265
277
265
277
W
N/A
N/A
2454
3000
3271
4000
4089
5000
N/A
N/A
2655
2901
3752
4100
4576
5000
Unit Electrical Ratings
HA
N/A
N/A
11.8
13.0
15.7
17.4
19.7
21.7
N/A
N/A
10.0
10.5
14.2
14.8
17.3
18.1
TCA
5.42
5.08
THA
MCA
MOCP
Plug
15
6–15P
20
6–20P
25
6–30P
30
6–30P
0.8*
6.4
12.6
13.8
16.5
18.2
20.5
22.5
15.7
17.3
20.7
22.7
25.6
28.2
0.56
6.0
15
10.58
11.03
14.72
15.36
17.83
18.61
13.2
13.8
18.4
19.2
22.3
23.3
15
15
20
20
25
25
H- WIRE
* THA value applies to hydronic heat only, Htr #8.
Table 6
VPRC/VPRH 12,000 BTU electrical specifications
Power Supply
Volt — 1–60
Volt
Min
Compressor
RLA
LRA
Indoor Fan
Motor
FLA
Hp
Outdoor Fan
Motor
FLA
Hp
Electric Heat
Htr #
0 or 8
208/
230V
3
197
5.2
27
0.80
0.07
0.7
0.09
4
5
0 or 8
2
265V
240
4.6
20
0.56
0.07
1.2
0.125
3
4
Volt
208
230
208
230
280
230
208
230
265
277
265
277
265
277
265
277
W
N/A
N/A
2454
3000
3271
4000
4089
5000
N/A
N/A
2655
2901
3752
4100
4576
5000
Unit Electrical Ratings
HA
N/A
N/A
11.8
13.0
15.7
17.4
19.7
21.7
N/A
N/A
10.0
10.5
14.2
14.8
17.3
18.1
TCA
6.7
6.36
THA
MCA
MOCP
Plug
15
6–15P
20
6–20P
25
6–30P
30
6–30P
0.8*
8.1
12.6
13.8
16.5
18.2
20.5
22.5
15.7
17.3
20.7
22.7
25.6
28.2
0.56
7.6
15
10.58
11.03
14.72
15.36
17.83
18.61
13.2
13.8
18.4
19.2
22.3
23.3
15
15
20
20
25
25
H- WIRE
* THA value applies to hydronic heat only, Htr #8.
Table 7
VPRC/VPRH 18,000 BTU electrical specifications
Power Supply
Volt — 1–60
Volt
Min
Compressor
Indoor Fan
Motor
Outdoor Fan
Motor
RLA
FLA
FLA
LRA
Hp
Hp
Electric Heat
Htr #
0 or 8
3
208/
230V
197
6.5
43
1.0
0.15
0.8
0.125
4
5
0 or 8
265V
240
5.8
46
0.56
0.07
0.5
0.17
3
4
* THA value applies to hydronic heat only, Htr #8.
The Right Fit for Comfort
12
Unit Electrical Ratings
Volt
W
HA
208
N/A
N/A
230
N/A
N/A
208
2454
11.8
230
3000
13.0
208
3271
15.7
230
4000
17.4
208
4089
230
5000
265
TCA
THA
MCA
MOCP
Plug
1.0*
10.0
15
6–15P
12.8
16.0
14.0
17.6
20
6–20P
16.7
20.9
18.4
23.0
25
6–30P
19.7
20.7
25.8
21.7
22.7
28.4
30
6–30P
N/A
N/A
6.86
8.4
15
265
3752
14.2
14.7
18.4
20
277
4100
14.8
15.4
19.2
20
265
4576
17.3
17.8
22.3
25
277
5000
18.1
18.6
23.3
25
8.3
6.86
H-Wire
P/N 240007449, Rev. N [08/02/2012]
The Right Fit for Comfort
VPRC / VPRH
Single Package Vertical Air Conditioner/Heat Pump
Engineering Submittal
& Wall Sleeve Specification Worksheet
REMOVE THIS SECTION FROM THE BOOKLET,ENTER INFORMATION IN THE
SPACES PROVIDED, AND SUBMIT WITH YOUR ORDER.
Job Name:
Location:
Customer:
Project Engineer:
Project Architect:
General Contractor:
Submitted by:
For: Reference [ ] Approval [ ]
Date:
ECR International LLC
5780 Success Drive
Rome, NY 13440
e-mail: info@RetroAire™.com
An ISO 9001-2000 Certified Company
P/N 240007449, Rev. D [08/09]
VPRC/VPRH Vertical Packaged Air Conditioner/Heat Pump
• Specifications and Performance •
H
7
1
1
9
B
B
A
B
B
A
A
A
A
0
A
A
Please enter the decoding for the hydronic coil option that is suitable for your application in the boxes below.
Refer to the example for information placement.
H
1
Revision:
A - Revision Level
1
Series:
Special -Standard:
0 - Standard
A - Z Special Option
7
Piping:
R - Right Side
L - Left Side
F - Front
Shipping:
A - Single (STD)
F
Capacity:
0 - 09 - 18
1 - 19 - 24
OEM:
A - RetroAire (STD)
H
Chassis Configuration:
1 - Remote
X - Special
Motorized Valve
B - 24V, 3 Way N / C Valve (STD)
H
Aux Heat:
8 - 1 Row (09 - 18)
9 - 2 Row (19 - 24)
X - Special
Example:
Pipe Connection:
B - Standard
Shut Off Valves:
A - Sweat Connections (STD)
B - Ball Valves & P/T Ports
C - Automatic Balancing Valves
X - Special
P/N 240007449, Rev. N [08/02/2012]
14
The Right Fit for Comfort
VPRC/VPRH Vertical Packaged Air Conditioner/Heat Pump
• Specifications and Performance •
(Availability of 09-12 TBD)
Field-installed options
Return air access panel with frame and filter
Painted condenser louver (specify color)
Internal drain connection kit (09–24 Btu only)
X Field-installed options
Remote thermostat — Digital — 1-stage
Remote thermostat — Digital — 2-stage
X
Made in USA
15
P/N 240007449, Rev. N [08/02/2011]
VPRC/VPRH Vertical Packaged Air Conditioner/Heat Pump
• Specifications and Performance •
VPRC/VPRH order specifications for engineering purposes
This information is important to ensure that equipment supplied is properly designed for the application for which
it is intended.
1. TYPE OF CONSTRUCTION: New Construction
Replacement
If replacement, what is the current model being replaced? _____________________________
Manufacturer :_____________________________
Model # :_____________________________
2. ELECTRIC HEAT: Output or kW: _____ Current Circuit Breaker Used: _____ Amps
3. IS THERE AN INTERNAL DRAIN SYSTEM FOR CONDENSATE REMOVAL?
Yes
4. WHAT ARE THE DIMENSIONS OF THE UNIT ENCLOSURE?
No
L _____
W _____
H _____
(NOTE: Unit enclosure must meet minimum clearance specifications.)
5. IS A RETURN AIR ACCESS PANEL NEEDED?
Yes
No
(NOTE: Standard R/A access panel is supplied with a disposable filter.) What is return air opening size?
If not, what will be used? _____________________________
L _____ W _____ What is free area of existing return air opening? ____________________
6. WHAT IS DESIGNED EXTERNAL STATIC PRESSURE (E.S.P.)? _________________________
If not known, describe the supply air configuration. Duct Length : _________________
Rectangular Duct
L _____ W _____
Circular Duct
Diameter ____
How many supply air diffusers? ___________________
• How many rooms are being conditioned by one unit?________________________________
7. WHAT IS THE OVERALL WALL THICKNESS? (REFER TO DIAGRAM BELOW) ____________________________
8. WHILE FACING THE UNIT WHERE WILL THE CONTROLS BE LOCATED?
Front________ left_________right__________
Attach sketch or
photo if possible.
Specify overall wall thickness when
ordering the wall sleeve — it will be
supplied to meet the required depth.
Overall wall
thickness
Foam gasket
1/2 X 1/2 inch
(13 X 13 mm)
Exterior
wall
Outdoor louver
Interior
wall
Wall
sleeve
Drip edge will extend
outside exterior wall
when installed to
guide condensate
away from building
Company Name
Authorized signature
Date
Lag Holes
(4 on each
side)
VPRC/VPRH WALL
SLEEVE ASSEMBLY
EMI signature
CROSS SECTION
OF TYPICAL WALL
Date
The Right Fit for Comfort
16
P/N 240007449, Rev. N [08/02/2012]
VPRC/VPRH Vertical Packaged Air Conditioner/Heat Pump
• Specifications and Performance •
Electrical Specifications (continued)
IMPORTANT
Due to ongoing product development, designs, specifications, and performance are subject to change without notice. Please consult
the factory for further information.
Table 8
VPRC/VPRH 19 electrical specifications
Power Supply
Volt — 1–60
Volt
Min
Compressor
Indoor Fan
Motor
Outdoor Fan
Motor
RLA
FLA
FLA
LRA
Hp
Hp
Electric Heat
Htr #
0 or 8
3
4
208/
230V
197
7.3
48
1.5
0.25
1.30
0.25
5
7
1
0 or 8
3
265V
240
7.1
43
1.3
0.25
1.3
0.25
4
7
1
Unit Electrical Ratings
Volt
W
HA
208
N/A
N/A
230
N/A
N/A
208
2454
230
TCA
THA
MCA
MOCP
Plug
1.5*
14.6
15
6–15P
11.8
13.3
16.6
3000
13.0
14.5
18.2
20
6–20P
280
3271
15.7
17.2
21.5
230
4000
17.4
18.9
23.6
25
6–30P
208
4089
19.7
21.2
26.4
230
5000
21.7
23.2
29.0
30
6–30P
208
5725
27.5
29.0
36.3
230
7000
30.4
31.9
39.9
208
8178
39.3
40.8
51.0
230
10,000
43.5
45.0
56.2
10.1
40
60
265
N/A
N/A
9.7
11.5
15
265
3752
14.2
15.5
19.3
20
277
4100
14.8
15.5
20.1
25
265
4576
17.3
16.1
22.3
25
277
5000
18.1
18.6
24.2
25
265
6635
25.0
19.4
32.9
35
277
7250
26.2
26.3
34.3
35
265
9152
34.5
35.8
44.8
50
277
10,000
36.1
37.4
46.8
50
9.7
H-WIRE
* THA value applies to hydronic heat only, Htr #8.
P/N 240007449, Rev. N [08/02/2011]
17
Made in USA
VPRC/VPRH Vertical Packaged Air Conditioner/Heat Pump
• Specifications and Performance •
Electrical Specifications (continued)
Table 9
VPRC/VPRH 24 electrical specifications
Power Supply
Volt — 1–60
Volt
Min
Compressor
Indoor Fan
Motor
Outdoor Fan
Motor
RLA
FLA
FLA
LRA
Hp
Hp
Electric Heat
Htr #
0 or 8
3
4
208/
230V
197
9.4
54.0
1.5
0.25
1.30
0.25
5
7
1
0 or 8
3
265V
240
8.0
46
1.3
0.25
1.3
0.25
4
7
1
Unit Electrical Ratings
Volt
W
HA
208
N/A
N/A
230
N/A
N/A
208
2454
230
TCA
THA
MCA
MOCP
Plug
1.5*
14.6
20
6–20P
11.8
13.3
16.6
3000
13.0
14.5
18.2
20
6–20P
280
3271
15.7
17.2
21.5
230
4000
17.4
18.9
23.6
25
6–30P
208
4089
19.7
21.2
26.4
230
5000
21.7
23.2
29.0
30
6–30P
208
5725
27.5
29.0
36.3
230
7000
30.4
31.9
39.9
208
8178
39.3
40.8
51.0
230
10,000
43.5
45.0
56.2
12.2
40
60
265
N/A
N/A
9.7
11.4
15
265
3752
14.2
15.5
19.3
20
277
4100
14.8
16.1
20.1
25
265
4576
17.3
18.6
23.2
25
277
5000
18.1
19.4
24.2
25
265
6635
25.0
26.3
34.3
35
277
7250
26.2
27.5
34.0
35
265
9152
34.5
35.8
44.8
50
277
10,000
36.1
37.4
46.8
50
6.86
H-WIRE
* THA value applies to hydronic heat only, Htr #8.
The Right Fit for Comfort
18
P/N 240007449, Rev. N [08/02/2012]
VPRC/VPRH Vertical Packaged Air Conditioner/Heat Pump
• Specifications and Performance •
Electrical Specifications (continued)
IMPORTANT
Due to ongoing product development, designs, specifications, and performance are subject to change without notice. Please consult
the factory for further information.
Table 10
VPRC/VPRH 30 electrical specifications
Power Supply
Volt — 1–60
Volt
Min
Compressor
Indoor Fan
Motor
Outdoor Fan
Motor
RLA
FLA
FLA
LRA
Hp
Hp
Electric Heat
Htr #
0
5
208/
230V
197
13.0
74
3.0
1.3
7
0.5
0.25
1
0
4
265V
240
10.5
67
2.3
1.4
7
1
P/N 240007449, Rev. N [08/02/2011]
Unit Electrical Ratings
Volt
W
HA
208
N/A
N/A
230
N/A
N/A
208
4089
230
5000
280
6134
29.5
230
7500
32.6
208
8178
230
265
THA
MCA
MOCP
N/A
20.6
30
19.7
22.7
28.4
30
21.7
24.7
31.0
35
32.5
40.7
35.6
44.5
39.3
42.3
52.9
60
10,000
43.5
46.5
58.1
60
N/A
N/A
14.2
16.8
25
265
4576
17.3
19.6
24.5
25
277
5000
18.1
20.4
25.5
30
265
6864
25.9
28.2
35.3
40
277
7500
27.1
29.4
36.8
40
265
9152
34.5
36.8
46.1
50
277
10,000
36.1
38.4
48.1
50
19
TCA
17.3
6.86
Plug
45
H-WIRE
Made in USA
VPRC/VPRH Vertical Packaged Air Conditioner/Heat Pump
• Specifications and Performance •
Electrical Specifications (continued)
Table 11
Power Supply
Voltage —
1/60
Volt
Min
VPRC/VPRH 36 electrical specifications
Indoor Fan Outdoor Fan
Motor
Motor
Compressor
RLA
LRA
FLA
Hp
FLA
Hp
Electric Heat
Htr #
0
5
208/
230V
197
13.6
88
3.0
1.3
7
1
0.5
0.25
A
0
4
265V
240
12
67
2.3
1.4
7
1
A
Unit Electrical Ratings
Volt
W
HA*
208
N/A
N/A
TCA
N/A
230
N/A
N/A
N/A
208
4089
19.7
230
5000
21.7
280
6134
29.5
230
7500
32.6
208
8178
39.3
230
10,000
43.5
208
12,268
19.7 / 39.3
22.7 / 39.3 28.4 / 49.2
30 / 50
230
15,000
21.7 / 43.5
24.7 / 43.5 31.0 / 54.4
35 / 60
17.9
THA*
MCA*
MOCP*
21.3
30
22.7
28.4
30
24.7
31.0
35
32.5
40.7
35.6
44.5
42.3
52.9
46.5
58.1
45
60
60
265
N/A
N/A
14.2
16.8
25
265
4576
17.3
19.6
24.5
30
277
5000
18.1
20.4
25.5
30
265
6864
25.9
28.2
35.3
40
277
7500
27.1
29.4
36.8
40
265
9152
34.5
36.8
46.1
50
277
10,000
36.1
38.4
48.1
50
265
13,729
17.3/34.5
19.6/34.5
24.5/43.2
30/45
277
15,000
18.1/36.1
20.4/36.1
25.5/45.2
30/50
15.7
Plug
H-WIRE
* — Where two values are shown, data is displayed as Circuit 1 / Circuit 2
NOTICE
All field wiring must be done in accordance with the National
Electrical Code, ANSI/NFPA 70–latest edition, and local codes
(in Canada — CSA C22.1 Canadian Electrical Code Part 1 and
local codes).
The Right Fit for Comfort
20
P/N 240007449, Rev. N [08/02/2012]
VPRC/VPRH Vertical Packaged Air Conditioner/Heat Pump
• Specifications and Performance •
Optional return air access panel
Optional return air access panel (with filter)
Make sure the installation will provide adequate clearance and access
to the control panel.
NOTE
It is necessary to work closely with the other trades to locate the opening for the return air access panel. The return air access panel must be
installed with enough room available to remove the unit if necessary.
The frame is installed with screws through the lag holes into the frame
studs and should be level and plumb (Figure 4). The return air access
panel is set onto the frame and held in place with 6 screws.
All models must have an air filter installed prior to operation.
Return air access panels vary by model. When ordering, be sure to
match access panels to units.
Figure 4
Return air access panel (available with solid doors if ducted return air is used; available in standard white or consult factory for custom colors)
Return air access panel part numbers
(includes items 2, 5 and 6 below)
09–18
19–24
30–36
Table 12
Model
09–18 Std.
19–24 Std.
30–36 Std.
Part # 240003010C
Part # 240003013C
Part # 240004439C
Return Air Access Panel Dimensions — Inches (mm)
A
B
C
D
E
F
G
H
J
K
29 3/4
28
(756) (711)
49 3/4
30
17 3/4 20 1/4
20
20
50
477/8
(1264) (762) (451) (514) (508) (508) (1270) (1220)
29 3/4
28
(756) (711)
61 3/4
30
28
20 1/4
30
20
62
597/8
(1569) (762) (711) (514) (762) (508) (1518) (1518)
35 7/8 341/8
(911) (864)
33
62
36 7/8 17 5/8 9
30
20
/16
(1575) (918) (448)
(762) (508)
(852)
P/N 240007449, Rev. N [08/02/2011]
62
60
3/16 (1524)
21
Item
Description
1
Solid door panel (for ducted return air installations)
2
Door assembly, front view
3
Door assembly, rear view
4
Filter bracket (on back)
5
Frame assembly (5a are lag holes, 3 per side)
6
Filter
Made in USA
VPRC/VPRH Vertical Packaged Air Conditioner/Heat Pump
• Specifications and Performance •
Hydronic Coil Option — Performance Data
Figure 5
Hydronic coil option nomenclature (order as described below to obtain required coil and accessories)
Position:
1,
2,
3,
4,
5,
6,
7
8
9
10
11
12
13
14
15
Example:
H
H
F
7
1
1
1
9
B
A
B
A
A
0
A
Series:
Revision:
A - Revision Level
Piping:
R - Right Side
L - Left Side
F - Front
Special -Standard:
0 - Standard
A - Z Special Option
Capacity:
0 - 09 - 18
1 - 19 - 24
Shipping:
A - Single (STD)
Chassis Configuration:
1 - Remote
X - Special
OEM:
A - RetroAire (STD)
Aux Heat:
8 - 1 Row (09 - 18)
9 - 2 Row (19 - 24)
X - Special
Motorized Valve
B - 24V, 3 Way N / C Valve (STD)
Pipe Connection:
B - Standard
Shut Off Valves:
A - Sweat Connections (STD)
B - Ball Valves & P/T Ports
C - Automatic Balancing Valves
X - Special
HH Series Hydronic Coil Option
IMPORTANT
(Available for VPRC / VPRH models 09-24 only)
System duct work is connected to the discharge opening on
the duct collar or plenum. A flex collar is advised.
Description
The HH series hydronic coil option is designed for use with VPRC/
VPRH models 09-24 only, and offers an alternative means of space
heating.
Encased in a 20-ga. galvanized G90U sheet metal enclosure, the HH
option is field mounted to the top of the VPRC/VPRH chassis. It is
suspended by 5/16” threaded rods, allowing removal of the VPRC/
VPRH chassis, if necessary, without disconnecting piping connections.
The supply air duct connection is made via a 10” diameter duct collar.
A two- or three-way motorized 24-volt water valve is available
Order the hydronic coil package as either left, right or front aligned
— match the control panel alignment of the unit on which it is to be
installed.
The Right Fit for Comfort
•
22
Standard Features
• 20 Ga. Galvanized G90U sheet metal enclosure.
• Front, Left or Right side piping connections.
• ½” sweat connections
• 24V, 3 way, normally closed motorized valve.
• 10” diameter supply air duct connection.
Optional Features
• Ball valves & P/T ports
• Automatic balancing valves with P/T ports and shut-off
• Refer to Figure 5, page 20 for HH series nomenclature to order
the hydronic coil that meets your needs.
P/N 240007449, Rev. N [08/02/2012]
VPRC/VPRH Vertical Packaged Air Conditioner/Heat Pump
• Specifications and Performance •
Hydronic Coil Option — Performance Data (continued)
IMPORTANT
Due to ongoing product development, designs, specifications, and performance are subject to change without notice. Please consult
the factory for further information.
Table 13
VPRC/VPRH hydrocoil specifications (Entering Air Temperature on 70°F, dry bulb/58°F, wet bulb)
Unit Size
09
12
18
19
24
Note 1
CFM (L/s)
300 (142)
400 (189)
500 (236)
700 (330)
700 (330)
GPM (L/s)
1
2
3
1
2
3
1
2
3
1
2
3
1
2
3
1
2
3
2
4
6
2
4
6
2
4
6
2
4
6
2
4
6
2
4
6
2
4
6
2
4
6
2
4
6
(0.163)
(0.126)
(0.189)
(0.163)
(0.126)
(0.189)
(0.163)
(0.126)
(0.189)
(0.163)
(0.126)
(0.189)
(0.163)
(0.126)
(0.189)
(0.163)
(0.126)
(0.189)
(0.126)
(0.252)
(0.379)
(0.126)
(0.252)
(0.379)
(0.126)
(0.252)
(0.379)
(0.126)
(0.252)
(0.379)
(0.126)
(0.252)
(0.379)
(0.126)
(0.252)
(0.379)
(0.126)
(0.252)
(0.379)
(0.126)
(0.252)
(0.379)
(0.126)
(0.252)
(0.379)
Entering H2O Temp
FC
140 (60)
160 (71.1)
180 (82.2)
140 (60)
160 (71.1)
180 (82.2)
140 (60)
160 (71.1)
180 (82.2)
140 (60)
160 (71.1)
180 (82.2)
140 (60)
160 (71.1)
180 (82.2)
Btu/h
(kW)
Head Loss, Ft/H2O
7300
8400
8900
9500
10900
11500
11800
13500
14200
8300
9800
10400
10800
12700
13500
13400
15700
16600
10900
12200
12700
14200
15800
16400
17500
19400
20100
23800
28400
30300
30900
36700
39200
38000
45100
48100
23800
28400
30300
30900
36700
39200
38000
45100
48100
2.14
2.46
2.61
2.78
3.19
3.37
3.46
3.95
4.16
2.43
2.87
3.05
3.16
3.72
3.95
3.92
4.60
4.86
3.19
3.57
3.72
4.16
4.63
4.80
5.12
5.68
5.89
6.97
8.32
8.87
9.05
10.75
11.48
11.13
13.21
14.08
6.97
8.32
8.87
9.05
10.75
11.48
11.13
13.21
14.08
1.1
4.0
8.7
1.1
3.9
8.6
1.0
3.9
8.4
1.1
4.0
8.7
1.1
3.9
8.6
1.0
3.9
8.4
4.0
15.2
33.2
3.9
14.9
32.6
3.9
14.7
32.0
2.2
8.4
18.5
2.2
8.3
18.2
2.2
8.2
17.9
2.2
8.4
18.5
2.2
8.3
18.2
2.2
8.2
17.9
(see note 1)
Head loss data above is for hydronic coil only. The optional motorized 3-way valve has a Cv of 4.0; the optional AutoFlow valves
have a Cv of 7.0 at full open.
P/N 240007449, Rev. N [08/02/2011]
23
Made in USA
VPRC/VPRH Vertical Packaged Air Conditioner/Heat Pump
• Specifications and Performance •
Hydronic Coil Option — Assembly and dimensions
Figure
Figure76 Hydronic
Hydroniccoil
coiloption
option(front/right
(front/right application
application shown)
shown)
— see
-- see
Figure 5,
Figure 5,
page 16
Page 20
forfor
ordering
ordering
information
information
1
2
3
4
5
6
7
8
9
10
10-inch round (254 mm) duct collar
Chassis top panel
Z brackets (factory-supplied)
Z-bracket mounting screws (included)
Freezestat
Freezestat setpoint adjustment screw
½ x ½ inch foam gasket
Mounting rods (field-supplied & installed), 5/16-18 all-thread
5/16-inch nuts (field-supplied & installed)
Optional ball valves and P/T ports — includes (2) ball valves and
(2) P/T ports
11 Optional Autoatic balancing valves (with dual P/T ports)
12 ½-inch copper piping (factory-assembled when valve option is
specified)
The Right Fit for Comfort
24
13 Bleed valve
14 Return line Autoatic balancing valve, with drain cock in wye
15 Supply line Autoatic balancing valve
16 Flanges and nuts — flange is factory-installed with this option;
automatic balancing valves are shipped with the HH, and are field
installed
17 P/T ports
18 Optional 3-way motorized diverting valve (normally closed),
factory piped as shown when ordered
19 Plug with wires to motorized valve (factory-wired to valve when
valve is ordered)
20 Plug with wires to freezestat (factory-wired to freezestat)
21 Optional ball valves
P/N 240007449, Rev. N [08/02/2012]
VPRC/VPRH Vertical Packaged Air Conditioner/Heat Pump
• Specifications and Performance •
Hydronic Coil Option — Assembly and dimensions (continued)
Figure 8
Hydronic coil dimensions
Dimensions — Inches (mm)
Models
A
B
C
C1
D
E
F
G
H
J
K
9–18
13
(330)
8
(203)
19
(483)
17
(432)
10
(254)
Diameter
18
(457)
9
(229)
½
(13)
10
(254)
5
(127)
1½
(38)
19–24
17
(432)
12
(305)
23
(533)
21
(533)
10
(254)
Diameter
22
(559)
11
(279)
½
(13)
13
(330)
6½
(165)
1½
(38)
P/N 240007449, Rev. N [08/02/2011]
25
Made in USA
VPRC/VPRH Vertical Packaged Air Conditioner/Heat Pump
• Specifications and Performance •
Chassis and wall sleeve
Provide proper clearances
Rough openings
NOTE: ECR International recommends installing the unit before any
carpentry work is started for the enclosure.
It is very important for proper air flow and sound levels that a minimum clearance of 4 inches, 102 mm (models 09–18) or 6 inches,
152 mm (models 24–36) between the enclosure and the chassis be
maintained (see Figure 8).
For designed performance, sound levels, and service, maintain a minimum of 6 inches (152 mm) on both sides and front for non-ducted
return air applications only.
Ducted return air applications only require minimal spacing for service
requirements.
Consult ECR International’s Sales Department if these minimums can
not be met. Depending on the application and return air introduction,
some re-configuration can probably be accommodated.
Minimum and maximum operation conditions must be observed
to ensure maximum system performance with minimum service
required.
Access opening — The access opening must allow for the unit to be
inserted for installation. Provide at least the minimum opening dimensions below. (See Table 12, page 19, for dimensions of the opening
when using the option return access panel assembly.)
Figure 9
Wall sleeve rough opening — It is very important that the rough
opening in the wall for the wall sleeve and louver be the correct dimension and in the exact position necessary for installation.
Minimum clearances around unit
Minimum clearances [inches (mm)]
Model
A
B
C
09, 12, 18
4 (102)
4 (102)
4 (102)
19, 24, 30, 36
6 (152)
6 (152)
6 (152)
Table 14
Width [inches (mm)]
Model
Height [inches (mm)]
Without
With
hydronic option hydronic option
Front access
Side access
09–12
26 1/8 (664)
26 1/8 (664)
45 3/4 (1162)
55 3/4 (1416)
18
26 1/8 (664)
26 5/8 (676)
45 3/4 (1162)
55 3/4 (664)
19–24
26 1/8 (664)
33 5/8 (854)
57 3/4 (1467)
69 3/4 (664)
30
28 9/16 (726)
36 1/4 (921)
58 3/4 (1492)
N/A
36
28 9/16 (726)
36 1/4 (921)
58 3/4 (1492)
N/A
(front control panel) (side control panel)
Table 15
A = distance from left side of unit to interior wall
B = distance from right side of unit to interior wall
C = distance from front of unit to interior wall
Minimum access opening dimensions (item 1,
Figure 9)
VPRC/VPRH rough wall sleeve opening
Model
Width [inches (mm)]
Height [inches (mm)]
09–12
26 1/8 (664)
26 1/8 (664)
18
26 1/8 (664)
26 5/8 (676)
19–24
26 1/8 (664)
33 5/8 (854)
30
28 9/16 (726)
36 1/4 (921)
36
28 9/16 (726)
36 1/4 (921)
Platform
See Figure 10, Page 25 and Figure 13, Page 27 for details of the platform
and wall sleeve installation. The platform height must make the bottom
of the VPRC or VPRH chassis flush with the bottom inside edge of
the wall sleeve. This means that the platform surface must be ½ inch
(13 mm) ABOVE the bottom of the wall sleeve rough opening.
The platform dimensions above will allow the chassis base pan to align
with the bottom of the wall sleeve.
Air filter
All models must have an air filter installed prior to operation. Use
the chassis-mounted air filter supplied with the unit unless using the
optional return air access panel. For these applications, remove and
discard the filter from the unit and install the access panel with the
supplied filter in place.
The Right Fit for Comfort
26
P/N 240007449, Rev. N [08/02/2012]
VPRC/VPRH Vertical Packaged Air Conditioner/Heat Pump
• Specifications and Performance •
Chassis and wall sleeve (continued)
Figure 10 Exploded view of typical installation (chassis shown is typical of models 09–24)
6
10
1
2
9
30/36 chassis
(models 09–24
shown at right)
5
4
7
3
6
9
1
Access opening (for unit insertion/removal)
— See unit dimensions in Figure 2, Page 6. See
Table 14, page 24 for minimum recommended
opening dimensions. Make sure to account for
the extra height of the hydronic coil module,
if used.
8
5
Outside louver‑ — The outside louver attaches
to the wall sleeve with nuts placed on the
louver studs.
6
VPRC/VPRH chassis.
7
Control panel (front standard; available on
left side or right side for models 09–24 only).
Access opening must be on the same side of
the unit as the control panel. Thermostat
connection terminal block located here.
NOTE: The access opening will be in the left
or right side of the enclosure for left or rightside-mounted control panel units (available
option on models 09–24 only).
See Table 14, Page 24 for minimum clearances
around unit to determine minimum enclosure
dimensions.
8
Optional return access panel assembly. See
page 19 for details and dimensions.
2
Wall sleeve opening to outside — See required
dimensions in Table 15, Page 24.
9
3
Platform — See Page 24 for the required
platform height. The platform MUST be level.
4
Wall sleeve (see page 26) — The wall sleeve
must be ordered to accommodate the total wall
thickness (from inside surface of wall sleeve
opening to the surface of the outside wall).
Return air opening — EVERY VPRC/VPRH
requires an air filter on the return air. The filter
is located on the chassis opening unless the
optional return air access panel is used (for
these applications, the air filter is removed
from the chassis — a filter is installed on the
access panel).
P/N 240007449, Rev. N [08/02/2011]
1
10 Hydronic coil option — See page 20 to
page 23.
27
Made in USA
VPRC/VPRH Vertical Packaged Air Conditioner/Heat Pump
• Specifications and Performance •
Chassis and wall sleeve (continued)
Determine wall sleeve depth
Wall sleeve assembly
The wall sleeve depth must be suitable for the overall wall thickness.
It is critical that wall thickness be determined before ordering the
wall sleeve (Figure 10).
• Models 09–24 are supplied with a tabbed-assembly wall sleeve,
and must be field assembled.
• Wall sleeves for models 30–36 are factory assembled.
Consult factory for available wall sleeves.
• The minimum wall sleeve depth is for a 6½ inch (165 mm) overall
wall thickness, and available in ½-inch (13-mm) increments for
thicker walls.
• For wall thicknesses less than 6½ inches, the wall sleeve will penetrate into the room, and will require interior framing adaptations
for proper fit.
Determine openings and enclosure
Determine the access opening size, wall sleeve opening size and enclosure size per page 24.
Figure 12 Typical tabbed-assembly wall sleeve (09–24)
Figure 11 Determining wall sleeve depth
Specify overall wall thickness when
ordering the wall sleeve — it will be
supplied to meet the required depth.
Inside
Overall wall
thickness
Foam gasket
1/2 X 1/2 inch
(13 X 13 mm)
Exterior
wall
Outdoor louver
Interior
wall
Wall
sleeve
Drip edge will extend
outside exterior wall
when installed to
guide condensate
away from building
Lag holes
(4 on each side)
Chassis
studs
Lag Holes
(4 on each
side)
VPRC/VPRH WALL
SLEEVE ASSEMBLY
The Right Fit for Comfort
CROSS SECTION
OF TYPICAL WALL
Outside
28
P/N 240007449, Rev. N [08/02/2012]
VPRC/VPRH Vertical Packaged Air Conditioner/Heat Pump
• Specifications and Performance •
Chassis
Return
and
Airwall
Access
sleeve
Panels
(continued)
Figure 13 Typical VPRC/VPRH installation, with platform
Platform surface must be ½ inch (13 mm) ABOVE
the bottom of the wall sleeve rough opening.
* Platform surface must be raised an additional 3/8 in (10 mm)
if installing a wall sleeve transition kit. (See Pgs. 2 & 28)
P/N 240007449, Rev. N [08/02/2011]
29
Made in USA
VPRC/VPRH Vertical Packaged Air Conditioner/Heat Pump
• Specifications and Performance •
Replacing Older RetroAire VPAC/VPHP30 Units
The VPRC/VPRH30 is larger than the VPAC/VPHP30. Ductwork changes are required. If replacing a VPAC/VPHP30
with a VPRC/VPRH30, RetroAire offers a transition wall sleeve and adapter (550002100) for the existing VPAC/
VPHP30 wall sleeve. This adapter adds 3.5” (89mm) to the depth of the unit and allows the use of the existing wall
sleeve and louver. If using this transition piece, be sure to maintain the minimum clearances required. The transition
adapter also requires the platform height to be increased by 3/8” (10mm).
Replacing
VPAC/VPHP30
Outside louver
VPAC/VPHP30
Wall sleeve
Wall sleeve transition kit
Model 30 ONLY
VPRC/VPRH30 Unit
3/8" (10mm)
Outside
Louver
VPAC/VPHP30
Wall Sleeve
The Right Fit for Comfort
30
P/N 240007449, Rev. N [08/02/2012]
VPRC/VPRH Vertical Packaged Air Conditioner/Heat Pump
• Specifications and Performance •
Notes
P/N 240007449, Rev. N [08/02/2011]
31
Made in USA
ECR International LLC
2201 Dwyer Avenue
Utica, NY 13501
e-mail: info@RetroAire.com
An ISO 9001-2000 Certified Company
The Right Fit for Comfort32
P/N 240007449, Rev. N [08/02/2012]