Mitsubishi heavy industries Commercial and industrial

High Performance
Air-Conditioning
2016
50/60Hz
16P01E
Inverter Packaged Air-Conditioners
Our new advanced technology has realized high efficiency, strong heating
and long piping.
This contributes to the environmental protection through energy saving
and permits installation of the units (4~6HP) considering a heating
operation under temperature conditions down to -20˚C and design
flexibility has been improved by extension of piping length to 100m.
Blue
Fin
Line up
1.5
HP
2
2.5
3
3.5
4
5
6
-
Hyper Inverter
8
10
-
-
SRC40ZMX-S (1.5HP)
SRC50ZMX-S (2.0HP)
SRC60ZMX-S (2.5HP)
Blue
Fin
FDC71VNX (3.0HP)
FDC100VNX/VSX (4.0HP)
FDC125VNX/VSX (5.0HP)
FDC140VNX/VSX (6.0HP)
High efficiency (comparison of FDT series)
Hyper inverter outdoor units
high COP levels are achieved
by our latest technologies,
such as high efficient twin
rotary compressors.
EER in cooling
3.81
4.00
3.62
3.09
Micro
Hyper
2.81
Micro
4HP
-20˚C : Heating operation down to -20˚C
-15˚C : Nominal heating capacity maintained at -15˚C
+43˚C
-15˚C
-30
+20˚C
Heating
-20
Cooling
-10
0
10
20
30
40
Hyper
5HP
Strong heating (Hyper Inverter 3~6HP)
-20˚C
COP in heating
Micro
3.34
Hyper
4.34
4.09
Micro
6HP
Hyper
4HP
4.08
3.71
Micro
Thanks to changing fin
configuration from flat
sheet to M shape fin. This
high dimensional structure
provides optimum balance
of heat transfer and airflow.
12.5
18.0
16.0
FDC140VSX(6HP, 3Phase 380V)
20.0
16.5
Hyper
6HP
High
Low
Hyper Inverter Micro Inverter
16.0
Micro
Heat Transfer Coef. W/m2K
50
FDC125VSX(5HP, 3Phase 380V)
3.81
High efficiency (All outdoor units)
Max.heating capacity (kW)
FDC100VSX(4HP, 3Phase 380V)
Hyper
5HP
3.50
2
M fin
Leading powerful heating capacity in the industry
Temperature of supply air can reach 40˚C
in 4 minutes after start up under low
temperature operation conditions (at both
indoor and outdoor temperature of 2˚C)
and can reach 50˚C in 8 minutes after that.
Thanks to optimization of refrigeration control with use of electric
expansion valve and development of twin rotary compressors, max
heating capacity has been increased.
Hyper Inverter series can reach the set temperature very quickly,
keeping nominal heating capacity when outdoor temperature is -15˚C.
It is effective to be used even in cold area.
(kW)
18.0
14.5
14.0
Heating capacity
Heating capacity (in case of 5HP, 3Phase 380V)
Keeping nominal heating
capacity at -15˚C
50˚C
Hyper Inverter
Hyper Inverter
nominal
heating
capacity
14.0kW
40˚C
Micro Inverter
8.8
0
-15˚C
2˚C
30˚C
7˚C
20˚C
model name
(kW at outdoor temperature of 7˚C)
nominal heating capacity
heating capacity
at outdoor temperature of -15˚C
FDC100VSX(4HP, 3Phase 380V)
11.2kW
11.2kW
FDC125VSX(5HP, 3Phase 380V)
14.0kW
14.0kW
FDC140VSX(6HP, 3Phase 380V)
16.0kW
16.0kW
Micro Inverter
10˚C
0˚C
4minutes
Please refer to our technical manual for installation conditions, operation range and heating/cooling capacities. (including 1Phase 220V)
8minutes
Installation workability
Enhanced installation workability thanks to the extended pipe length – longest level
in the industry and precharged refrigerant.
1 Piping length – 100m (Hyper Inverter 4~6HP)
Point
Micro Inverter
Piping
length
Height
difference
(Outdoor higher
than Indoor)
Piping length Height difference
HP
1.5~2.5
30m
HP
Standard Inverter
Piping length Height difference
20m
4~6
50m
30m
8.10
70m
30m
3
50m
30m
4~6
100m
30m
HP
3~4
Piping length Height difference
30m
20m
2 Refrigerant precharged piping length extending to 30m
Point
Refrigerant precharged piping length extends up to 30m. This eliminates the need to add refrigerant on site, which sets it free from trouble of
excessive or insufficient charging of refrigerant, and allows carrying out the installation smoothly.
That of Hyper inverter 1.5~2.5HP & Standard inverter is up to 15m.
3 Blue Fin (3~10HP)
Point
Due to application of blue coated fins (KS101)
for the heat exchanger of new outdoor unit,
corrosion resistance has been improved
compared to current models.
Blue
Fin
4 Monitoring Function (All series)
Point
Equipped with RS232C
for connection directly
to your PC monitoring
and service tasks
made simple with our
service software
(“Mente PC”).
5 Base heater kit (option)
Point
This kit is recommended to be used in an area
where the lowest temperature drops below 0˚C.
CW-H-E1
applied for
FDC71VNX
FDC100~140VNX,VSX
FDC100~140VN,VS
FDC200/250VSA
FDC100VNP
3
Micro Inverter
Line up
1.5
HP
Micro Inverter
-
2
-
2.5
-
3
-
3.5
4
5
6
8
10
Blue
Fin
Blue
Fin
-
Blue
Fin
FDC100VN/VS (4.0HP)
FDC125VN/VS (5.0HP)
FDC140VN/VS (6.0HP)
FDC200VSA (8.0HP)
FDC250VSA (10.0HP)
Tropical Usage Mode
Size reduction and high efficiency
performance on the DC twin
rotary compressors (Micro Inverter 4-6HP)
Wide range of operation
Our new advanced technology has expanded the heating and cooling
operation range.
This permits installation of the units under a low outdoor temperature
conditions down to -15˚C/-20˚C In heating operation and -15˚C in
cooling operation.
Employment of DC twin rotary compressor has enabled to utilize a highspeed range of up to 120 rps at the maximum to secure the required
capacity.
Optimum compressor control has been realized by employing the vector
control* and the starting current has been improved significantly
compared with former models. Moreover, vibration has been reduced.
Heating
-20ºC
FDC100/125/140
+20ºC
FDC200/250
+20ºC
-15ºC
Cooling
-15ºC
-15ºC
Outside diameter of shell
ø185mm
ø133mm
Former
compressor
New model
DC twin rotary compressor
+50ºC*
FDC200/250
-20
* Vector control means
a. technique to realize
an optimum control by
converting the current
wave to a smooth
sinusoidal waveform
Height at 342mm
Height at 440 mm
Reduction in height by 22.3%
Reduction in volume by 44.1%
+43ºC
FDC100/125/140
-10
0
10
20
30
40
50
* FDC200/250 : extended to 50˚CDB in the cooling mode.
2 Layer Construction (Micro Inverter 10HP)
Thanks to control box structure with 2 layer
construction using hinge connection,
service and maintenance has been made
much easier for inverter components.
Serviceability (Micro Inverter 10HP)
Improved freedom of piping layout
4
Front
2
1
Right
Four handles
Rear
4
2
3
Down
A transparent rain cover
1
3
Hole size becomes
120% bigger.
Wire insertion holes for fall prevention
Attached as a standard for
easy maintenance.
Fixing screws to service panel
Decreasing number of screws from 5 to 2,
installation & service speed is improved.
Located at the same level for
easy transport and transfer.
4
M fin
Standard Inverter
Line up
HP
1.5
Standard Inverter -
2
2.5
-
-
3
3.5
4
5
6
8
10
-
-
-
-
FDC71VNP (3.0HP)
Blue
Fin
NEW
Blue
Fin
FDC90VNP (3.5HP)
FDC100VNP (4.0HP)
Compact Design of outdoor units
Volume
33%
less
All outdoor units (Hyper, Micro,Standard)
Weight
25%
Fits into elevators
less
FDC71VNX
FDC71VNP
High SEER & SCOP (in case of indoor unit: FDT71VF1)
Though the nominal efficiency is lower than that of FDC71VNX (Hyper inverter),
higher SEER & SCOP are achieved by optimizing control.
7
6
Easy
installation
6.14
5.72
5
4.27
4.09
4
3
FDC71VNX
FDC71VNP
FDC71VNX
SEER
FDC71VNP
SCOP
CONTENTS
OUTDOOR UNITS
INDOOR UNITS
BENEFITS SUMMARY
CONTROL SYSTEMS
OUTDOOR UNIT DIMENSIONS
ENERGY LABEL (FOR EU / EEA AREA ONLY)
2~5
10~44
45
46~49
50~53
54 • 55
5
SINGLE
Type
4way
P.10
CEILING CASSETTE
FDT
HP
1.5
2.0
2.5
3.0
4.0
kW
4.0
5.0
6.0
7.1
10.0
Btu/h
13,600
17,100
20,500
24,200
34,100
kcal/h
3,440
4,300
5,160
6,100
8,600
FDT40ZMXVF
FDT50ZMXVF
FDT60ZMXVF
FDT71VNXVF1
FDT100VNXVF2
1Phase
Set
Indoor unit
Outdoor
unit
4way compact
(600 x 600mm)
P.16
Set
Outdoor
unit
High Static
pressure
P.20
FDT60VF
FDT71VF1
FDT100VF2
SRC40ZMX-S
SRC50ZMX-S
SRC60ZMX-S
FDC71VNX
FDC100VNX
FDC100VSX
3Phase
1Phase
1Phase
FDTC40ZMXVF
FDTC50ZMXVF
FDTC60ZMXVF
FDTC40VF
FDTC50VF
FDTC60VF
SRC40ZMX-S
SRC50ZMX-S
SRC60ZMX-S
FDU71VNXVF1
1Phase
DUCT CONNECTED
P.25
FDUM
1Phase
FDC71VNX
FDC100VNX
FDC100VSX
1Phase
FDUM40ZMXVF FDUM50ZMXVF FDUM60ZMXVF FDUM71VNXVF1 FDUM100VNXVF2
3Phase
FDUM100VSXVF2
1Phase
FDUM40VF
FDUM50VF
FDUM60VF
FDUM71VF1
FDUM100VF2
SRC40ZMX-S
SRC50ZMX-S
SRC60ZMX-S
FDC71VNX
FDC100VNX
FDC100VSX
3Phase
1Phase
FDE40ZMXVG
FDE50ZMXVG
FDE60ZMXVG
FDE71VNXVG
CEILING
SUSPENDED
FDE100VSXVG
3Phase
Outdoor
unit
WALL
MOUNTED FLOOR STANDING
P.38
FDE100VNXVG
Set
Indoor unit
NEW
FDU100VF2
Set
Outdoor
unit
NEW
FDU71VF1
3Phase
Indoor unit
P.32
FDU100VNXVF2
FDU100VSXVF2
Indoor unit
Low/Middle
Static pressure
Set
1Phase
FDE40VG
FDE50VG
FDE60VG
FDE71VG
FDE100VG
SRC40ZMX-S
SRC50ZMX-S
SRC60ZMX-S
FDC71VNX
FDC100VNX
FDC100VSX
3Phase
1Phase
Indoor unit
Outdoor
unit
FDF
FDT50VF
Set
Outdoor
unit
SRK
FDT40VF
3Phase
FDU
6
1Phase
Indoor unit
FDTC
FDE
FDT100VSXVF2
3Phase
P.41
1Phase
1Phase
FDF71VNXVD1
FDF100VNXVD2
Set
FDF100VSXVD2
3Phase
Indoor unit
Outdoor
unit
1Phase
3Phase
FDF71VD1
FDF100VD2
FDC71VNX
FDC100VNX
FDC100VSX
Capacity Range (Rated Cooling Capacity)
Micro Inverter
Standard Inverter
5.0
6.0
4.0
5.0
6.0
8.0
10.0
3.0
3.5
4.0
12.5
14.0
10.0
12.5
14.0
20.0
24.0
7.1
9.0
10.0
42,700
47,800
34,100
42,700
47,800
68,200
81,300
24,200
30,700
34,100
10,750
12,040
8,600
10,750
12,040
17,200
20,640
6,100
7,740
8,600
FDT125VNXVF
FDT140VNXVF
FDT100VNVF2
FDT125VNVF
FDT140VNVF
FDT125VSXVF
FDT140VSXVF
FDT100VSVF2
FDT125VSVF
FDT140VSVF
FDT125VF
FDT140VF
FDT100VF2
FDT125VF
FDT140VF
FDT71VF1
FDT100VF2
FDT100VF2
FDC125VNX
FDC140VNX
FDC100VN
FDC125VN
FDC140VN
FDC71VNP
FDC90VNP
FDC100VNP
FDC125VSX
FDC140VSX
FDC100VS
FDC125VS
FDC140VS
FDU125VNXVF
FDU140VNXVF
FDU100VNVF2
FDU125VNVF
FDU140VNVF
FDU125VSXVF
FDU140VSXVF
FDU100VSVF2
FDU125VSVF
FDU140VSVF
FDU200VSAVG
FDU250VSAVG
FDU125VF
FDU140VF
FDU100VF2
FDU125VF
FDU140VF
FDU200VG
FDU250VG
FDC125VNX
FDC140VNX
FDC100VN
FDC125VN
FDC140VN
FDC125VSX
FDC140VSX
FDC100VS
FDC125VS
FDC140VS
FDUM125VNXVF
FDUM140VNXVF FDUM100VNVF2 FDUM125VNVF
FDUM140VNVF
FDUM125VSXVF
FDUM140VSXVF FDUM100VSVF2 FDUM125VSVF
FDUM140VSVF
FDT71VNPVF1
FDU71VNPVF1
FDC200VSA
FDT90VNPVF2 FDT100VNP1VF2
FDU90VNPVF2 FDU100VNP1VF2
FDU71VF1
FDU100VF2
FDU100VF2
FDC71VNP
FDC90VNP
FDC100VNP
FDC250VSA
FDUM71VNPVF1 FDUM90VNPVF2 FDUM100VNP1VF2
FDUM125VF
FDUM140VF
FDUM100VF2
FDUM125VF
FDUM140VF
FDUM71VF1
FDUM100VF2
FDUM100VF2
FDC125VNX
FDC140VNX
FDC100VN
FDC125VN
FDC140VN
FDC71VNP
FDC90VNP
FDC100VNP
FDC125VSX
FDC140VSX
FDC100VS
FDC125VS
FDC140VS
FDE125VNXVG
FDE140VNXVG
FDE100VNVG
FDE125VNVG
FDE140VNVG
FDE71VNPVG
FDE90VNPVG
FDE100VNP1VG
FDE125VSXVG
FDE140VSXVG
FDE100VSVG
FDE125VSVG
FDE140VSVG
FDE125VG
FDE140VG
FDE100VG
FDE125VG
FDE140VG
FDE71VG
FDE100VG
FDE100VG
FDC125VNX
FDC140VNX
FDC100VN
FDC125VN
FDC140VN
FDC71VNP
FDC90VNP
FDC100VNP
FDC125VSX
FDC140VSX
FDC100VS
FDC125VS
FDC140VS
SRK71VNPZM
SRK100VNP1ZR
SRK71ZM-S
SRK100ZR-S
FDC71VNP
FDC100VNP
FDF125VNXVD
FDF140VNXVD
FDF100VNVD2
FDF125VNVD
FDF140VNVD
FDF71VNPVD1
FDF90VNPVD2 FDF100VNP1VD2
FDF125VSXVD
FDF140VSXVD
FDF100VSVD2
FDF125VSVD
FDF140VSVD
FDF125VD
FDF140VD
FDF100VD2
FDF125VD
FDF140VD
FDF71VD1
FDF100VD2
FDF100VD2
FDC125VNX
FDC140VNX
FDC100VN
FDC125VN
FDC140VN
FDC71VNP
FDC90VNP
FDC100VNP
FDC125VSX
FDC140VSX
FDC100VS
FDC125VS
FDC140VS
Tropical Usage Mode
7
MULTI SYSTEM
Up to Four indoor units can be connected
to a single outdoor unit and simultaneously
operated with a single remote control.
Twin / Triple / Double Twin Multi System
By referring to the following table for applicable indoor units,
select the same models and capacities.
Applicable indoor units
Capacity
Model
40
50
60
71
100
125
4way
FDT
4way compact (600 x 600mm)
FDTC
Low/Middle Static pressure
FDUM
Ceiling Suspended
FDE
Wall Mounted
SRK
Floor Standing
FDF
Combination of indoor units
Micro Inverter
Outdoor
Unit
FDC125VNX FDC140VNX FDC100VN FDC125VN FDC140VN
FDC71VNX FDC100VNX
FDC100VSX FDC125VSX FDC140VSX FDC100VS FDC125VS FDC140VS FDC200VSA FDC250VSA
40 + 40
50 + 50
60 + 60
71 + 71
50 + 50
60 + 60
71 + 71
100 + 100
125 + 125
Twin
Triple
50 + 50 + 50
50 + 50 + 50 71 + 71 + 71
Double
50+50+50+50 60+60+60+60
Twin
Decision of piping specification
Twin type
(Example)
Item
Models FDC71VNX, FDC100~140VN/VS
[Branch pipe set : DIS-WA1]
Model
FDC71
FDC100
FDC125
FDC140
Indoor unit
Gas line
4
3
2
1
4
Liquid line
3
Symbol
Liquid pipe
24
Reducer
8
ID15.88
2
Symbol
210
ø6.35
flared nut
ID9.52
50
8
ID9.52
Reducer
Symbol
ID12.7
10
OD15.88
3
Floor
Mount
sections
level with the floor.
Floor
Mount
sections
perpendicular to the floor.
3-Way Branch
4
80
105
Notes (1) Symbol 1 to 4 in the drawing shows the symbols of branch piping parts in the chart respectively.
(2) Branch piping should always be arranged to have level or perpendicular position.
8
2-Way Branch
ø15.88Xt1.0
Symbol
180
1
The branch piping (both gas and liquid lines)
should always be arranged to have a level
or perpendicular position.
ø12.7Xt 0.8
ø9.52X t 0.8 ø9.52X t 0.8 ø15.88Xt1.0
ID9.52
48
ID15.88
11
Gas pipe
Main pipe Branch pipe
ID9.52
ID15.88
11
Chart of shapes of
branch piping parts
(DIS-WA1)
Liquid pipe
Main pipe Branch pipe
Notes (1) When 40-60 models of indoor units are applied to this combination, the
reducer 3 supplied with the branch piping set should be used in order to
reduce the liquid piping size from ø9.52mm to ø6.35mm at indoor unit side
(flare connection). Accordingly be sure to select the liquid piping size
ø9.52mm from branch to indoor unit.
(2) The reducer 4 is for FDC71 and 100 models only.
L
Gas pipe
Indoor unit
combinations
40+40
50+50
60+60
71+71
8
Outdoor unit
Diagrams below show the application as samples. For further information, refer to TECHNICAL MANUAL.
2 piece
2 piece
Floor
Floor
Ideal for the installation in large area and L-shaped rooms, the V
Multi System has an extensive degree of flexibility in the selection
of indoor units. Specifically, the selection of indoor units with
different capacities in different types can be made.
V Multi System
Different models and capacities
can be selected.
Applicable indoor units
Capacity
Model
40
50
60
71
100
125
4way
FDT
Ceiling Suspended
FDE
Combination of indoor units
Micro Inverter
Outdoor
Unit
FDC125VNX FDC140VNX FDC100VN FDC125VN FDC140VN
FDC71VNX FDC100VNX
FDC100VSX FDC125VSX FDC140VSX FDC100VS FDC125VS FDC140VS FDC200VSA FDC250VSA
60 + 60
60 + 60
100 + 100
50 + 50
71 + 71
50 + 50
71 + 71
125 + 125
Twin
40 + 40
50 + 71
71 + 125
50 + 71
50 + 50 + 50
Triple
50 + 50 + 50 71 + 71 + 71 60+60+125
71+71+100
Double
Twin
50+50+50+50 60+60+60+60
Triple type
The indoor_outdoor piping length differences among indoor units are less than 3m.
Model FDC140VN/VS
[Branch pipe set : DIS-TA1]
(Example)
Indoor unit
Item
Model
3
Outdoor unit
50+50+50
ø9.52X t 0.8
ø9.52Xt 0.8
ø15.88Xt 1.0
ø12.7X t0.8
Notes (1) The reducer 3 supplied with the branch piping set should be used in order to reduce the liquid piping size
from ø9.52mm to ø6.35mm at indoor unit side (flare connection). Accordingly be sure to select the liquid piping
size ø9.52mm from branch to indoor unit.
Gas line
Floor
FDC140
Gas pipe
Main pipe
Branch pipe
Liquid pipe
Main pipe
Branch pipe
Indoor unit
combinations
1
L
ID15.88
Liquid pipe
0
Symbol
ID9.52
1
8
10
300
Reducer
Symbol
ID9.52x3
14˚
10
30
Symbol
ID12.7x3
30
80 80
100
100
Chart of shapes of
branch piping parts
(DIS-TA1)
3
Floor
Gas pipe
3
10
2
Liquid line
8
2
ID9.52
50
8
ø6.35
flared
nut
3
105
237
Notes (1) Symbol 1 to 3 in the drawing shows the symbols of branch piping parts in the chart respectively.
(2) Branch piping should always be arranged to have level or perpendicular position.
9
CEILING CASSETTE -4way-
FDT
R410A
FDT 40/50/60/71/100/125/140
Remote control (Option)
Wireless
Wired
RC-EX1A
1 Individual flap control system
Point
According to room temperature conditions, four directions of air flow
can be controlled individually by following Flap control system.
Individual flap control is available even after installation.
RC-E5
RCH-E3
RCN-T-36W-E
2 Flap control
Point
The flap can swing within the range
of upper and lower flap position
selected with wired remote control.
Selected
upper position
Max swing
range
Selected
lower position
For person who is far
from the indoor unit
3 Wireless remote control
Point
A wireless remote control is available
for your convenience.
Wireless receiver kit
Receiver
5 Easy checking of drain pan
Point
Easy checking of drain pan
condition is available by
removing corner lid only.
Due to new design
changing fan motor is
available without removing
a panel.
10
For both persons who are
feeling hot or cold
Can cool both the kitchen
and the guests
4 Arrangement of installation
Point
balance of indoor unit
Checking from access ports with
detachable covers at each corner,
arrangement of installation balance
of indoor unit can be available
without removing a panel.
Workability is improved and time of
installation is reduced.
6 700mm Drain Pump
Point
Drain can be discharged
upwards by 700mm from the
ceiling surface. It allows a piping
layout with a high degree of
freedom. Depending on the
installation location and 260mm
flexible hose as a standard
equipment supports easy
workability.
Flexible hose
less than
700mm
OUTDOOR UNIT
Micro Inverter
SRC • FDC
40~60ZMX
71VNX
100~140VN(S)X
100~140VN(S)
Chargeless
15m
30m
Height x Width x Depth (mm) 640 x 800(+71) x 290 750 x 880(+88) x 340 1,300 x 970 x 370
845 x 970 x 370
200VSA
250VSA
model
30m
1,300 x 970 x 370 1,505 x 970 x 370
Standard Inverter
FDC
71VNP
90VNP
100VNP
model
Chargeless
15m
Height x Width x Depth (mm) 640 x 800(+71) x 290 750 x 880(+88) x 340
845 x 970 x 370
DIMENSIONS (Unit:mm)
Models FDT40VF,50VF,60VF,71VF1
Models FDT100VF1,100VF2,125VF,140VF
11
SPECIFICATIONS
Set model name
Indoor unit
Outdoor unit
Power source
Nominal cooling capacity (Min~Max)
Nominal heating capacity (Min~Max)
Power consumption Cooling/Heating
EER/COP
Cooling/Heating
Inrush current
Max. current
Sound power Indoor Cooling/Heating
level*1
Outdoor Cooling/Heating
Cooling (Hi/Me/Lo)
Sound
Indoor
pressure
Heating (Hi/Me/Lo)
level*1 1
Outdoor Cooling/Heating
Cooling (Hi/Me/Lo)
Indoor
Air flow 1
Heating (Hi/Me/Lo)
Outdoor Cooling/Heating
Indoor
Exterior
HeightxWidthxDepth
dimensions Outdoor
Indoor
Net weight
Outdoor
Ref.piping size Liquid/Gas
Refrigerant line (one way) length
Vertical height differences Outdoor is higher/lower
Cooling
Outdoor operating
temperature range
Heating
Panel
Air filter, Q'ty
Remote control (option)
Set model name
Indoor unit
Outdoor unit
Power source
Nominal cooling capacity (Min~Max)
Nominal heating capacity (Min~Max)
Power consumption Cooling/Heating
EER/COP
Cooling/Heating
Inrush current
Max. current
Sound power Indoor Cooling/Heating
level*1
Outdoor Cooling/Heating
Cooling (Hi/Me/Lo)
Sound
Indoor
Heating (Hi/Me/Lo)
pressure
level*1 1
Outdoor Cooling/Heating
Cooling (Hi/Me/Lo)
Indoor
Air flow 1
Heating (Hi/Me/Lo)
Outdoor Cooling/Heating
Indoor
Exterior
HeightxWidthxDepth
dimensions Outdoor
Indoor
Net weight
Outdoor
Ref.piping size Liquid/Gas
Refrigerant line (one way) length
Vertical height differences Outdoor is higher/lower
Cooling
Outdoor operating
temperature range
Heating
Panel
Air filter, Q'ty
Remote control (option)
FDT40ZMXVF
FDT40VF
SRC40ZMX-S
kW
kW
kW
A
dB(A)
m3/min
mm
kg
ømm
m
m
°C
kW
kW
kW
A
dB(A)
m3/min
mm
kg
ømm
m
m
°C
FDT50ZMXVF
FDT60ZMXVF
FDT71VNXVF1
FDT50VF
FDT60VF
FDT71VF1
SRC50ZMX-S
SRC60ZMX-S
FDC71VNX
1 Phase 220-240V, 50Hz / 220V, 60Hz
4.0 ( 1.1 ~ 4.7 )
5.0 ( 1.1 ~ 5.6 )
5.6 ( 1.1 ~ 6.3 )
7.1 ( 3.2 ~ 8.0 )
4.5 ( 0.6 ~ 5.4 )
5.4 ( 0.6 ~ 6.3 )
6.7 ( 0.6 ~ 7.1 )
8.0 ( 3.6 ~ 9.0 )
0.93 / 1.06
1.29 / 1.29
1.52 / 1.70
2.04 / 1.94
4.30 / 4.25
3.88 / 4.19
3.68 / 3.94
3.48 / 4.12
5
5
5
5
12
15
15
17
55 / 55
55 / 55
60 / 60
64 / 64
63 / 63
63 / 63
64 / 64
66 / 66
33 / 31 / 30
33 / 31 / 30
33 / 31 / 30
35 / 33 / 31
33 / 31 / 30
33 / 31 / 30
33 / 31 / 30
35 / 33 / 31
50 / 50
54 / 50
54 / 54
51 / 48
18 / 16 / 14
18 / 16 / 14
18 / 16 / 14
21 / 19 / 17
18 / 16 / 14
18 / 16 / 14
18 / 16 / 14
21 / 19 / 17
36 / 33
40 / 33
41.5 / 39
60 / 50
Unit: 246 x 840 x 840 Panel: 35 x 950 x 950
640 x 800(+71) x 290
750 x 880(+88) x 340
27.5(Unit:22 Panel:5.5)
29.5(Unit:24 Panel:5.5)
45
60
6.35(1/4") / 12.7(1/2")
9.52(3/8") / 15.88(5/8")
Max.30
Max. 50
Max.20 / Max.20
Max.30 / Max.15
-15~43*3
-15~20
-20~20
T-PSA-3BW-E
Pocket plastic net x 1(Washable)
wired:RC-EX1A, RC-E5, RCH-E3 wireless:RCN-T-36W-E
FDT100VNXVF2
FDT125VNXVF
FDT140VNXVF
FDT100VSXVF2
FDT125VSXVF
FDT140VSXVF
FDT100VF2
FDT125VF
FDT140VF
FDT100VF2
FDT125VF
FDT140VF
FDC100VNX
FDC125VNX
FDC140VNX
FDC100VSX
FDC125VSX
FDC140VSX
1 Phase 220-240V, 50Hz / 220V, 60Hz
3 Phase 380-415V, 50Hz / 380V, 60Hz
10.0 ( 4.0 ~ 11.2 )
12.5 ( 5.0 ~ 14.0 )
14.0 ( 5.0 ~ 16.0 )
10.0 ( 4.0 ~ 11.2 )
12.5 ( 5.0 ~ 14.0 )
14.0 ( 5.0 ~ 16.0 )
11.2 ( 4.0 ~ 12.5 )
14.0 ( 4.0 ~ 17.0 )
16.0 ( 4.0 ~ 18.0 )
11.2 ( 4.0 ~ 16.0 )
14.0 ( 4.0 ~ 18.0 )
16.0 ( 4.0 ~ 20.0 )
2.50 / 2.58
3.28 / 3.43
4.19 / 4.20
2.50 / 2.58
3.28 / 3.43
4.19 / 4.20
4.00 / 4.34
3.81 / 4.08
3.34 / 3.81
4.00 / 4.34
3.81 / 4.08
3.34 / 3.81
5
5
5
5
5
5
24
26
26
15
15
15
65 / 65
68 / 68
68 / 68
65 / 65
68 / 68
68 / 68
70 / 70
70 / 70
72 / 72
70 / 70
70 / 70
72 / 72
40 / 37 / 35
42 / 40 / 37
43 / 41 / 38
40 / 37 / 35
42 / 40 / 37
43 / 41 / 38
40 / 37 / 35
42 / 40 / 37
43 / 41 / 38
40 / 37 / 35
42 / 40 / 37
43 / 41 / 38
48 / 50
48 / 50
49 / 52
48 / 50
48 / 50
49 / 52
27 / 24 / 20
30 / 27 / 23
30 / 27 / 23
27 / 24 / 20
30 / 27 / 23
30 / 27 / 23
27 / 24 / 20
30 / 27 / 23
30 / 27 / 23
27 / 24 / 20
30 / 27 / 23
30 / 27 / 23
100 / 100
100 / 100
100 / 100
100 / 100
100 / 100
100 / 100
Unit: 298 x 840 x 840 Panel: 35 x 950 x 950
1,300 x 970 x 370
32.5(Unit:27 Panel:5.5)
105
9.52(3/8") / 15.88(5/8")
Max.100
Max.30 / Max.15
-15~43*3
-20~20
T-PSA-3BW-E
Pocket plastic net x 1(Washable)
wired:RC-EX1A, RC-E5, RCH-E3 wireless:RCN-T-36W-E
1 Powerful-Hi can be selected.
Sound pressure level: 40/50ZMXVF 39dB(A), 60ZMXVF 46dB(A), 71VNXVF1 46dB(A), 100VN(S)XVF2 51dB(A), 125/140VN(S)XVF 51dB(A)
M
m3 min
N
m3 min
N( )
m3 min
N( )
m3 min
Air ow:
M
m3 min
NOTES:
he data are measured under the following conditions( O- ).
Cooling: ndoor temp. of
C
C
and outdoor temp. of
C . eating: ndoor temp. of
C
and outdoor temp. of C
C
.
* : ndicates the value in an anechoic cham er. uring operation these values are somewhat higher due to am ient conditions.
*2 : The values are for one indoor unit operation.
* : f a cooling operation is conducted when the outdoor air temperature is C or lower the outdoor unit should e installed at a place where it is not in uenced y
natural wind. f wind lows the low pressure will drop and compressor fre uency will increase this will cause the capacity to drop and may cause the unit to reak
down.
12
SPECIFICATIONS
he values are for simultaneous Multi operation.
FDT71VNXPVF
Set model name
Indoor unit
Outdoor unit
Power source
Nominal cooling capacity (Min~Max)
Nominal heating capacity (Min~Max)
Power consumption Cooling/Heating
EER/COP
Cooling/Heating
Inrush current
Max. current
2
Sound power Indoor* Cooling/Heating
level*1
Outdoor Cooling/Heating
Cooling (Hi/Me/Lo)
Sound
Indoor*2
pressure
Heating (Hi/Me/Lo)
1
level* 2
Outdoor Cooling/Heating
Cooling (Hi/Me/Lo)
Indoor*2
Air flow 2
Heating (Hi/Me/Lo)
Outdoor Cooling/Heating
Indoor
Exterior
HeightxWidthxDepth
dimensions Outdoor
Indoor
Net weight
Outdoor
Ref.piping size Liquid/Gas
Refrigerant line (one way) length
Vertical height differences Outdoor is higher/lower
Cooling
Outdoor operating
temperature range
Heating
Panel
Air filter, Q'ty
Remote control (option)
FDT100VNXPVF
FDT125VNXPVF
FDT140VNXPVF1
Twin
FDT40VF
FDC71VNX
kW
kW
kW
A
dB(A)
m3/min
mm
kg
ømm
m
m
°C
FDT50VF
FDC100VNX
FDT60VF
FDT71VF1
FDC125VNX
FDC140VNX
1 Phase 220-240V, 50Hz / 220V, 60Hz
7.1 ( 3.2 ~ 8.0 )
10.0 ( 4.0 ~ 11.2 )
12.5 ( 5.0 ~ 14.0 )
14.0 ( 5.0 ~ 16.0 )
8.0 ( 3.6 ~ 9.0 )
11.2 ( 4.0 ~ 12.5 )
14.0 ( 4.0 ~ 17.0 )
16.0 ( 4.0 ~ 18.0 )
1.85 / 1.99
2.56 / 2.66
3.06 / 3.22
3.88 / 3.70
3.84 / 4.02
3.91 / 4.21
4.08 / 4.35
3.61 / 4.32
5
5
5
5
17
24
26
26
55 / 55
55 / 55
60 / 60
64 / 64
66 / 66
70 / 70
70 / 70
72 / 72
33 / 31 / 30
33 / 31 / 30
33 / 31 / 30
35 / 33 / 31
33 / 31 / 30
33 / 31 / 30
33 / 31 / 30
35 / 33 / 31
51 / 48
48 / 50
48 / 50
49 / 52
18 / 16 / 14
18 / 16 / 14
18 / 16 / 14
21 / 19 / 17
18 / 16 / 14
18 / 16 / 14
18 / 16 / 14
21 / 19 / 17
60 / 50
100 / 100
100 / 100
100 / 100
Unit: 246 x 840 x 840 Panel: 35 x 950 x 950
750 x 880(+88) x 340
1,300 x 970 x 370
27.5(Unit:22 Panel:5.5)
29.5(Unit:24 Panel:5.5)
60
105
9.52(3/8") / 15.88(5/8")
Max. 50
Max. 100
Max.30 / Max.15
-15~43*3
-20~20
T-PSA-3BW-E
Pocket plastic net x 1(Washable)
wired:RC-EX1A, RC-E5, RCH-E3 wireless:RCN-T-36W-E
FDT140VNXTVF
Triple
FDT50VF
FDC140VNX
14.0 ( 5.0 ~ 16.0 )
16.0 ( 4.0 ~ 18.0 )
3.88 / 3.76
3.61 / 4.26
5
26
55 / 55
72 / 72
33 / 31 / 30
33 / 31 / 30
49 / 52
18 / 16 / 14
18 / 16 / 14
100 / 100
27.5(Unit:22 Panel:5.5)
he values are for simultaneous Multi operation.
FDT100VSXPVF
Set model name
Indoor unit
Outdoor unit
Power source
Nominal cooling capacity (Min~Max)
Nominal heating capacity (Min~Max)
Power consumption Cooling/Heating
EER/COP
Cooling/Heating
Inrush current
Max. current
2
Sound power Indoor* Cooling/Heating
level*1
Outdoor Cooling/Heating
Cooling (Hi/Me/Lo)
Sound
Indoor*2
pressure
Heating (Hi/Me/Lo)
1
level* 2
Outdoor Cooling/Heating
Cooling (Hi/Me/Lo)
Indoor*2
Air flow 2
Heating (Hi/Me/Lo)
Outdoor Cooling/Heating
Indoor
Exterior
HeightxWidthxDepth
dimensions Outdoor
Indoor
Net weight
Outdoor
Ref.piping size Liquid/Gas
Refrigerant line (one way) length
Vertical height differences Outdoor is higher/lower
Cooling
Outdoor operating
temperature range
Heating
Panel
Air filter, Q'ty
Remote control (option)
FDT50VF
FDC100VSX
kW
kW
kW
A
dB(A)
m3/min
10.0 ( 4.0 ~ 11.2 )
11.2 ( 4.0 ~ 16.0 )
2.56 / 2.66
3.91 / 4.21
5
15
55 / 55
70 / 70
33 / 31 / 30
33 / 31 / 30
48 / 50
18 / 16 / 14
18 / 16 / 14
100 / 100
mm
kg
ømm
m
m
°C
27.5(Unit:22 Panel:5.5)
FDT125VSXPVF
FDT140VSXPVF1
Twin
FDT60VF
FDT71VF1
FDC125VSX
FDC140VSX
3 Phase 380-415V, 50Hz / 380V, 60Hz
12.5 ( 5.0 ~ 14.0 )
14.0 ( 5.0 ~ 16.0 )
14.0 ( 4.0 ~ 18.0 )
16.0 ( 4.0 ~ 20.0 )
3.06 / 3.22
3.88 / 3.70
4.08 / 4.35
3.61 / 4.32
5
5
15
15
60 / 60
64 / 64
70 / 70
72 / 72
33 / 31 / 30
35 / 33 / 31
33 / 31 / 30
35 / 33 / 31
48 / 50
49 / 52
18 / 16 / 14
21 / 19 / 17
18 / 16 / 14
21 / 19 / 17
100 / 100
100 / 100
Unit: 246 x 840 x 840 Panel: 35 x 950 x 950
1,300 x 970 x 370
29.5(Unit:24 Panel:5.5)
105
9.52(3/8") / 15.88(5/8")
Max.100
Max.30 / Max.15
-15~43*3
-20~20
T-PSA-3BW-E
Pocket plastic net x 1(Washable)
wired:RC-EX1A, RC-E5, RCH-E3 wireless:RCN-T-36W-E
FDT140VSXTVF
Triple
FDT50VF
FDC140VSX
14.0 ( 5.0 ~ 16.0 )
16.0 ( 4.0 ~ 20.0 )
3.88 / 3.76
3.61 / 4.26
5
15
55 / 55
72 / 72
33 / 31 / 30
33 / 31 / 30
49 / 52
18 / 16 / 14
18 / 16 / 14
100 / 100
27.5(Unit:22 Panel:5.5)
2 Powerful-Hi can be selected.
Sound pressure level: 71VNXPVF 39dB(A), 100VN(S)XPVF 39dB(A), 125VN(S)XPVF 46dB(A), 140VN(S)XPVF1 46dB(A), 140VN(S)XTVF 39dB(A)
Air ow:
N P
m3 min
N( ) P
m3 min
N( ) P
m3 min
N( ) P
m3 min
N( )
m3 min
13
SPECIFICATIONS
Set model name
Indoor unit
Outdoor unit
Power source
Nominal cooling capacity (Min~Max)
Nominal heating capacity (Min~Max)
Power consumption Cooling/Heating
EER/COP
Cooling/Heating
Inrush current
Max. current
Sound power Indoor Cooling/Heating
level*1
Outdoor Cooling/Heating
Cooling (Hi/Me/Lo)
Sound
Indoor
pressure
Heating (Hi/Me/Lo)
level*1 1
Outdoor Cooling/Heating
Cooling (Hi/Me/Lo)
Indoor
Air flow 1
Heating (Hi/Me/Lo)
Outdoor Cooling/Heating
Indoor
Exterior
HeightxWidthxDepth
dimensions Outdoor
Indoor
Net weight
Outdoor
Ref.piping size Liquid/Gas
Refrigerant line (one way) length
Vertical height differences Outdoor is higher/lower
Cooling
Outdoor operating
temperature range
Heating
Panel
Air filter, Q'ty
Remote control (option)
kW
kW
kW
A
dB(A)
m3/min
mm
kg
ømm
m
m
°C
FDT100VNVF2
FDT125VNVF
FDT140VNVF
FDT100VSVF2
FDT125VSVF
FDT140VSVF
FDT100VF2
FDT125VF
FDT140VF
FDT100VF2
FDT125VF
FDT140VF
FDC100VN
FDC125VN
FDC140VN
FDC100VS
FDC125VS
FDC140VS
1 Phase 220-240V, 50Hz / 220V, 60Hz
3 Phase 380-415V, 50Hz / 380V, 60Hz
10.0 ( 4.0 ~ 11.2 )
12.5 ( 5.0 ~ 14.0 )
14.0 ( 5.0 ~ 14.5 )
10.0 ( 4.0 ~ 11.2 )
12.5 ( 5.0 ~ 14.0 )
14.0 ( 5.0 ~ 14.5 )
11.2 ( 4.0 ~ 12.5 )
14.0 ( 4.0 ~ 16.0 )
16.0 ( 4.0 ~ 16.5 )
11.2 ( 4.0 ~ 12.5 )
14.0 ( 4.0 ~ 16.0 )
16.0 ( 4.0 ~ 16.5 )
2.76 / 2.74
4.05 / 3.77
4.98 / 4.57
2.76 / 2.74
4.05 / 3.77
4.98 / 4.57
3.62 / 4.09
3.09 / 3.71
2.81 / 3.50
3.62 / 4.09
3.09 / 3.71
2.81 / 3.50
5
5
5
5
5
5
24
24
24
15
15
15
65 / 65
68 / 68
68 / 68
65 / 65
68 / 68
68 / 68
70 / 70
72 / 72
73 / 73
70 / 70
72 / 72
73 / 73
40 / 37 / 35
42 / 40 / 37
43 / 41 / 38
40 / 37 / 35
42 / 40 / 37
43 / 41 / 38
40 / 37 / 35
42 / 40 / 37
43 / 41 / 38
40 / 37 / 35
42 / 40 / 37
43 / 41 / 38
49 / 49
50 / 51
51 / 51
49 / 49
50 / 51
51 / 51
27 / 24 / 20
30 / 27 / 23
30 / 27 / 23
27 / 24 / 20
30 / 27 / 23
30 / 27 / 23
27 / 24 / 20
30 / 27 / 23
30 / 27 / 23
27 / 24 / 20
30 / 27 / 23
30 / 27 / 23
75 / 73
75 / 73
75 / 73
75 / 73
75 / 73
75 / 73
Unit: 298 x 840 x 840 Panel: 35 x 950 x 950
845 x 970 x 370
32.5(Unit:27 Panel:5.5)
81
83
9.52(3/8") / 15.88(5/8")
Max.50
Max.30 / Max.15
-15~43*3
-20~20
T-PSA-3BW-E
Pocket plastic net x 1(Washable)
wired:RC-EX1A, RC-E5, RCH-E3 wireless:RCN-T-36W-E
he values are for simultaneous Multi operation.
FDT100VNPVF
Set model name
Indoor unit
Outdoor unit
Power source
Nominal cooling capacity (Min~Max)
Nominal heating capacity (Min~Max)
Power consumption Cooling/Heating
EER/COP
Cooling/Heating
Inrush current
Max. current
2
Sound power Indoor* Cooling/Heating
level*1
Outdoor Cooling/Heating
Cooling (Hi/Me/Lo)
Sound
Indoor*2
pressure
Heating (Hi/Me/Lo)
level*1 1
Outdoor Cooling/Heating
Cooling (Hi/Me/Lo)
Indoor*2
Air flow 1
Heating (Hi/Me/Lo)
Outdoor Cooling/Heating
Indoor
Exterior
HeightxWidthxDepth
dimensions Outdoor
Indoor
Net weight
Outdoor
Ref.piping size Liquid/Gas
Refrigerant line (one way) length
Vertical height differences Outdoor is higher/lower
Cooling
Outdoor operating
temperature range
Heating
Panel
Air filter, Q'ty
Remote control (option)
kW
kW
kW
A
dB(A)
m3/min
mm
kg
ømm
m
m
°C
FDT125VNPVF
FDT140VNPVF1
FDT140VNTVF
FDT100VSPVF
FDT125VSPVF
FDT140VSPVF1
Twin
Triple
Twin
FDT50VF
FDT60VF
FDT71VF1
FDT50VF
FDT50VF
FDT60VF
FDT71VF1
FDC100VN
FDC125VN
FDC140VN
FDC140VN
FDC100VS
FDC125VS
FDC140VS
1 Phase 220-240V, 50Hz / 220V, 60Hz
3 Phase 380-415V, 50Hz / 380V, 60Hz
10.0 ( 4.0 ~ 11.2 ) 12.5 ( 5.0 ~ 14.0 ) 14.0 ( 5.0 ~ 14.5 ) 14.0 ( 5.0 ~ 14.5 ) 10.0 ( 4.0 ~ 11.2 ) 12.5 ( 5.0 ~ 14.0 ) 14.0 ( 5.0 ~ 14.5 )
11.2 ( 4.0 ~ 12.5 ) 14.0 ( 4.0 ~ 16.0 ) 16.0 ( 4.0 ~ 16.5 ) 16.0 ( 4.0 ~ 16.5 ) 11.2 ( 4.0 ~ 12.5 ) 14.0 ( 4.0 ~ 16.0 ) 16.0 ( 4.0 ~ 16.5 )
2.94 / 3.09
3.95 / 3.70
4.51 / 4.58
4.65 / 4.63
2.94 / 3.09
3.95 / 3.70
4.51 / 4.58
3.40 / 3.62
3.16 / 3.78
3.10 / 3.49
3.01 / 3.46
3.40 / 3.62
3.16 / 3.78
3.10 / 3.49
5
5
5
5
5
5
5
24
24
24
24
15
15
15
55 / 55
60 / 60
64 / 64
55 / 55
55 / 55
60 / 60
64 / 64
70 / 70
72 / 72
73 / 73
73 / 73
70 / 70
72 / 72
73 / 73
33 / 31 / 30
33 / 31 / 30
35 / 33 / 31
33 / 31 / 30
33 / 31 / 30
33 / 31 / 30
35 / 33 / 31
33 / 31 / 30
33 / 31 / 30
35 / 33 / 31
33 / 31 / 30
33 / 31 / 30
33 / 31 / 30
35 / 33 / 31
49 / 49
50 / 51
51 / 51
51 / 51
49 / 49
50 / 51
51 / 51
18 / 16 / 14
18 / 16 / 14
21 / 19 / 17
18 / 16 / 14
18 / 16 / 14
18 / 16 / 14
21 / 19 / 17
18 / 16 / 14
18 / 16 / 14
21 / 19 / 17
18 / 16 / 14
18 / 16 / 14
18 / 16 / 14
21 / 19 / 17
75 / 73
75 / 73
75 / 73
75 / 73
75 / 73
75 / 73
75 / 73
Unit: 246 x 840 x 840 Panel: 35 x 950 x 950
845 x 970 x 370
27.5(Unit:22 Panel:5.5)
29.5(Unit:24 Panel:5.5)
27.5(Unit:22 Panel:5.5)
29.5(Unit:24 Panel:5.5)
81
83
9.52(3/8") / 15.88(5/8")
Max.50
Max.30 / Max.15
-15~43*3
-20~20
T-PSA-3BW-E
Pocket plastic net x 1(Washable)
wired:RC-EX1A, RC-E5, RCH-E3 wireless:RCN-T-36W-E
1 Powerful-Hi can be selected.
Sound pressure level: 100VN(S)VF2 51dB(A), 125/140VN(S)VF 51dB(A), 100VN(S)PVF 39dB(A), 125VN(S)PVF 46dB(A), 140VN(S)PVF1 46dB(A), 140VNTVF 39dB(A)
N( )
m3 min
N( )P
m3 min
N( )P
m3 min
N( )P
m3 min
N
m3 min
Air ow:
N( )
m3 min
NOTES:
he data are measured under the following conditions( O- ).
Cooling: ndoor temp. of
C
C
and outdoor temp. of
C .
eating: ndoor temp. of
C
and outdoor temp. of C
C
.
ndicates the value in an anechoic cham er. uring operation these values are somewhat higher due to am ient conditions.
*2 :: The
values are for one indoor unit operation.
* : f a cooling
is conducted when the outdoor air temperature is
C or lower the outdoor unit should e installed at a place where it is not in uenced y
* natural wind.operation
f wind lows the low pressure will drop and compressor fre uency will increase this will cause the capacity to drop and may cause the unit to reak
down.
14
SPECIFICATIONS
he values are for simultaneous Multi operation.
FDT200VSAPVF2
Set model name
Indoor unit
Outdoor unit
Power source
Nominal cooling capacity (Min~Max)
Nominal heating capacity (Min~Max)
Power consumption Cooling/Heating
EER/COP
Cooling/Heating
Inrush current
Max. current
2
Sound power Indoor* Cooling/Heating
level*1
Outdoor Cooling/Heating
Cooling (Hi/Me/Lo)
Sound
Indoor*2
pressure
Heating (Hi/Me/Lo)
level*1 2
Outdoor Cooling/Heating
Cooling (Hi/Me/Lo)
Indoor*2
Air flow 2
Heating (Hi/Me/Lo)
Outdoor Cooling/Heating
Indoor
Exterior
HeightxWidthxDepth
dimensions Outdoor
Indoor
Net weight
Outdoor
Ref.piping size Liquid/Gas
Refrigerant line (one way) length
Vertical height differences Outdoor is higher/lower
Cooling
Outdoor operating
temperature range
Heating
Panel
Air filter, Q'ty
Remote control (option)
Set model name
Indoor unit
Outdoor unit
Power source
Nominal cooling capacity (Min~Max)
Nominal heating capacity (Min~Max)
Power consumption Cooling/Heating
EER/COP
Cooling/Heating
Inrush current
Max. current
Sound power Indoor Cooling/Heating
level*1
Outdoor Cooling/Heating
Cooling (Hi/Me/Lo)
Sound
Indoor
pressure
Heating (Hi/Me/Lo)
level*1 2
Outdoor Cooling/Heating
Cooling (Hi/Me/Lo)
Indoor
Air flow 2
Heating (Hi/Me/Lo)
Outdoor Cooling/Heating
Indoor
Exterior
HeightxWidthxDepth
dimensions Outdoor
Indoor
Net weight
Outdoor
Ref.piping size Liquid/Gas
Refrigerant line (one way) length
Vertical height differences Outdoor is higher/lower
Cooling
Outdoor operating
temperature range
Heating
Panel
Air filter, Q'ty
Remote control (option)
FDT250VSAPVF
FDT140VSTVF
Twin
FDT100VF2
FDC200VSA
kW
kW
kW
A
dB(A)
m3/min
mm
kg
ømm
m
m
°C
FDT200VSATVF1
FDT200VSADVF
FDT250VSADVF
Double Twin
FDT50VF
FDT60VF
FDC200VSA
FDC250VSA
Triple
FDT125VF
FDC250VSA
FDT50VF
FDT71VF1
FDC140VS
FDC200VSA
3 Phase 380-415V, 50Hz / 380V, 60Hz
19.0 ( 5.2 ~ 22.4 )
24.0 ( 6.9 ~ 28.0 )
14.0 ( 5.0 ~ 14.5 )
19.0 ( 5.2 ~ 22.4 )
19.0 ( 5.2 ~ 22.4 )
24.0 ( 6.9 ~ 28.0 )
22.4 ( 3.3 ~ 25.0 )
27.0 ( 5.5 ~ 31.5 )
16.0 ( 4.0 ~ 16.5 )
22.4 ( 3.3 ~ 25.0 )
22.4 ( 3.3 ~ 25.0 )
27.0 ( 5.5 ~ 31.5 )
6.25 / 6.02
8.36 / 7.15
4.65 / 4.63
6.01 / 5.76
6.26 / 6.15
7.42 / 6.83
3.04 / 3.72
2.87 / 3.78
3.01 / 3.46
3.16 / 3.89
3.04 / 3.64
3.23 / 3.95
5
5
5
5
5
5
20
21
15
20
20
21
65 / 65
68 / 68
55 / 55
64 / 64
55 / 55
60 / 60
72 / 74
73 / 75
73 / 73
72 / 74
72 / 74
73 / 75
40 / 37 / 35
42 / 40 / 37
33 / 31 / 30
35 / 33 / 31
33 / 31 / 30
33 / 31 / 30
40 / 37 / 35
42 / 40 / 37
33 / 31 / 30
35 / 33 / 31
33 / 31 / 30
33 / 31 / 30
58 / 59
59 / 62
51 / 51
58 / 59
58 / 59
59 / 62
27 / 24 / 20
30 / 27 / 23
18 / 16 / 14
21 / 19 / 17
18 / 16 / 14
18 / 16 / 14
27 / 24 / 20
30 / 27 / 23
18 / 16 / 14
21 / 19 / 17
18 / 16 / 14
18 / 16 / 14
135 / 135
143 / 151
75 / 73
135 / 135
135 / 135
143 / 151
Unit: 298 x 840 x 840 Panel: 35 x 950 x 950
Unit: 246 x 840 x 840 Panel: 35 x 950 x 950
1,300 x 970 x 370
1,505 x 970 x 370
845 x 970 x 370
1,300 x 970 x 370
1,505 x 970 x 370
32.5(Unit:27 Panel:5.5)
27.5(Unit:22 Panel:5.5) 29.5(Unit:24 Panel:5.5) 27.5(Unit:22 Panel:5.5) 29.5(Unit:24 Panel:5.5)
115
143
83
115
143
9.52(3/8") / 22.22(7/8") 12.7(1/2") / 22.22(7/8") 9.52(3/8") / 15.88(5/8")
9.52(3/8") / 22.22(7/8")
12.7(1/2") / 22.22(7/8")
Max.70
Max.50
Max.70
Max.30 / Max.15
-15~43*3
-15~50*3
-15~50*3
-15~20
-20~20
-15~20
T-PSA-3BW-E
Pocket plastic net x 1(Washable)
wired:RC-EX1A, RC-E5, RCH-E3 wireless:RCN-T-36W-E
Standard Inverter
FDT90VNPVF2
FDT100VNP1VF2
FDT100VF2
FDT100VF2
FDC90VNP
FDC100VNP
1 Phase 220-240V, 50Hz / 220V, 60Hz
7.1 ( 1.4 ~ 7.1 )
9.0 ( 1.9 ~ 9.0 )
10.0 ( 2.8 ~ 11.2 )
7.1 ( 1.0 ~ 7.1 )
9.0 ( 1.5 ~ 9.0 )
11.2 ( 2.5 ~ 12.5 )
2.50 / 1.90
2.67 / 2.19
2.76 / 2.84
2.84 / 3.74
3.37 / 4.11
3.62 / 4.52
5
5
5
14.5
18.0
21.0
64 / 64
65 / 65
65 / 65
67 / 67
69 / 69
70 / 70
35 / 33 / 31
40 / 37 / 35
40 / 37 / 35
35 / 33 / 31
40 / 37 / 35
40 / 37 / 35
54 / 54
57 / 55
57 / 61
21 / 19 / 17
27 / 24 / 20
27 / 24 / 20
21 / 19 / 17
27 / 24 / 20
27 / 24 / 20
36 / 36
63 / 49.5
75 / 79
Unit: 246 x 840 x 840 Panel: 35 x 950 x 950
Unit: 298 x 840 x 840 Panel: 35 x 950 x 950
640 x 800(+71) x 290
750 x 880(+88) x 340
845 x 970 x 370
29.5 ( Unit: 24 Panel: 5.5 )
32.5 ( Unit: 27 Panel: 5.5 )
45
57
70
6.35(1/4") / 12.7(1/2")
6.35(1/4") / 15.88(5/8")
9.52(3/8") / 15.88(5/8")
Max.30
Max.20 / Max.20
-15~46*3
-15~20
T-PSA-3BW-E
Pocket Plastic net x1(Washable)
wired:RC-EX1A, RC-E5, RCH-E3 wireless:RCN-T-36W-E
FDT71VNPVF1
FDT71VF1
FDC71VNP
kW
kW
kW
A
dB(A)
m3/min
mm
kg
ømm
m
m
°C
2 Powerful-Hi can be selected.
ound pressure level :
AP
d (A)
AP
d (A)
71VNPVF1 46dB(A), 90VNPVF2 51dB(A), 100VNP1VF2 51dB(A)
3
3
AP
m min
m3 min
Air ow :
AP
m min
NP
m3 min
NP
m3 min
NP
m3 min
d (A)
A
A
3
m min
d (A)
A
A
3
m min
d (A)
A
A
d (A)
3
m min
15
CEILING CASSETTE -4way Compact (600 X 600mm)-
FDTC
R410A
Fits into standard
600 x 600 ceiling
FDTC 40/50/60
Remote control (Option)
Wireless
Wired
RC-EX1A
1 Individual flap control system
Point
According to room temperature conditions, four directions of air flow
can be controlled individually by following Flap control system.
Individual flap control is available even after installation.
RC-E5
RCH-E3
RCN-TC-24W-ER
2 Flap control
Point
The flap can swing within the range of upper and lower
flap position selected with wired remote control.
Selected
upper position
Max swing
range
Selected
lower position
3 “CLEARER”Air Flow
Point
5 Quiet operation
Point
(Sound Pressure level in the Lo mode)
dB(A)
36
35
3dB(A)
Down
35dB(A)
34
New shape & angled louver redirects the air
current away from the ceiling, to reduce
ceiling stains
33
32dB(A)
32
31
30dB(A)
30
29
28
27
4 Installation Workability
Point
For wireless control simply insert the
infrared receiver kit on a corner of the
panel
wireless
remote control
RCN-TC-24W-ER
16
5dB(A)
Down
26
25
Previous
(Cooling/Heating)
Current
(Cooling)
Current
(Heating)
6 Taking OA (Outside Air) into inside
Point
OA Spacer TC-OAS-E (option)
Joint Duct TC-OAD-E (option)
Drain can be discharged upward by 600 mm from the ceiling
surface close to the indoor unit.
It allows a piping layout with a high degree of freedom
depending on the installation location.
Utilizing OA spacer which comes as optional equipment, outside air
can be taken inside.
Using 1 joint duct:
OA up to 1.3m3/min.
Using 2 joint ducts:
OA from 1.3 to 2.6m3/min.
7 600mm Drain Pump
Point
Indoor Unit FDTC
Flexible hose
600mm
248mm
300mm
OA Spacer
Ceiling OA
surface
OA
Panel
Joint Duct
8 Arrangement of installation balance of indoor unit
Point
Checking from access ports with detachable covers at each corner, arrangement of installation
balance of indoor unit can be available without removing a panel. Workability is improved and time
of installation is reduced.
OUTDOOR UNIT
Micro Inverter
SRC • FDC
40~60ZMX
71VNX
100~140VN(S)X
100~140VN(S)
Chargeless
15m
30m
Height x Width x Depth (mm) 640 x 800(+71) x 290 750 x 880(+88) x 340 1,300 x 970 x 370
845 x 970 x 370
200VSA
250VSA
model
30m
1,300 x 970 x 370 1,505 x 970 x 370
DIMENSIONS (Unit:mm)
17
SPECIFICATIONS
Set model name
Indoor unit
Outdoor unit
Power source
Nominal cooling capacity (Min~Max)
Nominal heating capacity (Min~Max)
Power consumption Cooling/Heating
EER/COP
Cooling/Heating
Inrush current
Max. current
Sound power Indoor Cooling/Heating
level*1
Outdoor Cooling/Heating
Cooling (Hi/Me/Lo)
Sound
Indoor
pressure
Heating (Hi/Me/Lo)
level*1 1
Outdoor Cooling/Heating
Cooling (Hi/Me/Lo)
Indoor
Air flow 1
Heating (Hi/Me/Lo)
Outdoor Cooling/Heating
Indoor
Exterior
HeightxWidthxDepth
dimensions Outdoor
Indoor
Net weight
Outdoor
Ref.piping size Liquid/Gas
Refrigerant line (one way) length
Vertical height differences Outdoor is higher/lower
Cooling
Outdoor operating
temperature range
Heating
Panel
Air filter, Q'ty
Remote control (option)
FDTC40ZMXVF
FDTC40VF
SRC40ZMX-S
kW
kW
kW
A
dB(A)
m3/min
mm
kg
ømm
m
m
°C
4.0 ( 1.1 ~ 4.7 )
4.5 ( 0.6 ~ 5.4 )
1.04 / 1.10
3.85 / 4.09
5
12
60 / 60
63 / 63
42 / 36 / 30
42 / 36 / 32
50 / 50
11.5 / 9 / 7
11.5 / 9 / 8
36 / 33
FDTC50ZMXVF
FDTC50VF
SRC50ZMX-S
1 Phase 220-240V, 50Hz / 220V, 60Hz
5.0 ( 1.1 ~ 5.6 )
5.4 ( 0.6 ~ 6.3 )
1.56 / 1.45
3.21 / 3.72
5
15
60 / 60
63 / 63
42 / 36 / 30
42 / 36 / 32
54 / 50
11.5 / 9 / 7
11.5 / 9 / 8
40 / 33
Unit: 248 x 570 x 570 Panel: 35 x 700 x 700
640 x 800(+71) x 290
18.5(Unit:15 Panel:3.5)
45
6.35(1/4") / 12.7(1/2")
Max.30
Max.20 / Max.20
-15~43*3
-15~20
TC-PSA-25W-E
Pocket plastic net x 1(Washable)
wired:RC-EX1A, RC-E5, RCH-E3 wireless:RCN-TC-24W-ER
FDTC60ZMXVF
FDTC60VF
SRC60ZMX-S
5.6 ( 1.1 ~ 6.3 )
6.7 ( 0.6 ~ 6.7 )
1.99 / 2.07
2.81 / 3.24
5
15
60 / 60
64 / 64
46 / 39 / 30
46 / 39 / 32
54 / 54
13.5 / 10 / 7
13.5 / 10 / 8
41.5 / 39
he values are for simultaneous Multi operation.
Set model name
Indoor unit
Outdoor unit
Power source
Nominal cooling capacity (Min~Max)
Nominal heating capacity (Min~Max)
Power consumption Cooling/Heating
EER/COP
Cooling/Heating
Inrush current
Max. current
2
Sound power Indoor* Cooling/Heating
level*1
Outdoor Cooling/Heating
Cooling (Hi/Me/Lo)
Sound
Indoor*2
pressure
Heating (Hi/Me/Lo)
level*1 1
Outdoor Cooling/Heating
Cooling (Hi/Me/Lo)
Indoor*2
Air flow 1
Heating (Hi/Me/Lo)
Outdoor Cooling/Heating
Indoor
Exterior
HeightxWidthxDepth
dimensions Outdoor
Indoor
Net weight
Outdoor
Ref.piping size Liquid/Gas
Refrigerant line (one way) length
Vertical height differences Outdoor is higher/lower
Cooling
Outdoor operating
temperature range
Heating
Panel
Air filter, Q'ty
Remote control (option)
kW
kW
kW
A
dB(A)
m3/min
mm
kg
ømm
m
m
°C
FDTC71VNXPVF FDTC100VNXPVF FDTC125VNXPVF FDTC140VNXTVF FDTC100VSXPVF FDTC125VSXPVF FDTC140VSXTVF
Twin
Triple
Twin
Triple
FDTC40VF
FDTC50VF
FDTC60VF
FDTC50VF
FDTC50VF
FDTC60VF
FDTC50VF
FDC71VNX
FDC100VNX
FDC125VNX
FDC140VNX
FDC100VSX
FDC125VSX
FDC140VSX
1 Phase 220-240V, 50Hz / 220V, 60Hz
3 Phase 380-415V, 50Hz / 380V, 60Hz
7.1 ( 3.2 ~ 8.0 ) 10.0 ( 4.0 ~ 11.2 ) 12.5 ( 5.0 ~ 14.0 ) 14.0 ( 5.0 ~ 16.0 ) 10.0 ( 4.0 ~ 11.2 ) 12.5 ( 5.0 ~ 14.0 ) 14.0 ( 5.0 ~ 16.0 )
8.0 ( 3.6 ~ 9.0 ) 11.2 ( 4.0 ~ 12.5 ) 14.0 ( 4.0 ~ 17.0 ) 16.0 ( 4.0 ~ 18.0 ) 11.2 ( 4.0 ~ 16.0 ) 14.0 ( 4.0 ~ 18.0 ) 16.0 ( 4.0 ~ 20.0 )
2.04 / 2.21
3.18 / 3.20
4.10 / 4.10
4.34 / 4.34
3.18 / 3.20
4.10 / 4.10
4.34 / 4.34
3.48 / 3.62
3.14 / 3.50
3.05 / 3.41
3.23 / 3.69
3.14 / 3.50
3.05 / 3.41
3.23 / 3.69
5
5
5
5
5
5
5
17
24
26
26
15
15
15
60 / 60
60 / 60
60 / 60
60 / 60
60 / 60
60 / 60
60 / 60
66 / 66
70 / 70
70 / 70
72 / 72
70 / 70
70 / 70
72 / 72
42 / 36 / 30
42 / 36 / 30
46 / 39 / 30
42 / 36 / 30
42 / 36 / 30
46 / 39 / 30
42 / 36 / 30
42 / 36 / 32
42 / 36 / 32
46 / 39 / 32
42 / 36 / 32
42 / 36 / 32
46 / 39 / 32
42 / 36 / 32
51 / 48
48 / 50
48 / 50
49 / 52
48 / 50
48 / 50
49 / 52
11.5 / 9 / 7
11.5 / 9 / 7
13.5 / 10 / 7
11.5 / 9 / 7
11.5 / 9 / 7
13.5 / 10 / 7
11.5 / 9 / 7
11.5 / 9 / 8
11.5 / 9 / 8
13.5 / 10 / 8
11.5 / 9 / 8
11.5 / 9 / 8
13.5 / 10 / 8
11.5 / 9 / 8
60 / 50
100 / 100
100 / 100
100 / 100
100 / 100
100 / 100
100 / 100
Unit: 248 x 570 x 570 Panel: 35 x 700 x 700
750 x 880(+88) x 340
1,300 x 970 x 370
18.5(Unit:15 Panel:3.5)
60
105
9.52(3/8") / 15.88(5/8")
Max.50
Max.100
Max.30 / Max.15
-15~43*3
-20~20
TC-PSA-25W-E
Pocket plastic net x 1(Washable)
wired:RC-EX1A, RC-E5, RCH-E3 wireless:RCN-TC-24W-ER
1 Powerful-Hi can be selected.
Sound pressure level: 40/50/60ZMXVF 47dB(A), 71VNXPVF 47dB(A), 100/125VN(S)XPVF 47dB(A), 140VN(S)XTVF 47dB(A)
N P
. m3 min
N( ) P
. m3 min
N( )
. m3 min
Air ow:
M
. m3 min
NOTES:
he data are measured under the following conditions( O- ).
Cooling: ndoor temp. of
C
C
and outdoor temp. of
C .
eating: ndoor temp. of
C
and outdoor temp. of C
C
.
ndicates the value in an anechoic cham er. uring operation these values are somewhat higher due to am ient conditions.
*2 :: The
values are for one indoor unit operation.
* : f a cooling
is conducted when the outdoor air temperature is
C or lower the outdoor unit should e installed at a place where it is not in uenced y
* natural wind.operation
f wind lows the low pressure will drop and compressor fre uency will increase this will cause the capacity to drop and may cause the unit to reak
down.
18
SPECIFICATIONS
he values are for simultaneous Multi operation.
FDTC100VNPVF
Set model name
Indoor unit
Outdoor unit
Power source
Nominal cooling capacity (Min~Max)
Nominal heating capacity (Min~Max)
Power consumption Cooling/Heating
EER/COP
Cooling/Heating
Inrush current
Max. current
2
Sound power Indoor* Cooling/Heating
level*1
Outdoor Cooling/Heating
Cooling (Hi/Me/Lo)
Sound
Indoor*2
pressure
Heating (Hi/Me/Lo)
level*1 2
Outdoor Cooling/Heating
Cooling (Hi/Me/Lo)
Indoor*2
Air flow 2
Heating (Hi/Me/Lo)
Outdoor Cooling/Heating
Indoor
Exterior
HeightxWidthxDepth
dimensions Outdoor
Indoor
Net weight
Outdoor
Ref.piping size Liquid/Gas
Refrigerant line (one way) length
Vertical height differences Outdoor is higher/lower
Cooling
Outdoor operating
temperature range
Heating
Panel
Air filter, Q'ty
Remote control (option)
FDTC125VNPVF
Twin
FDTC50VF
FDC100VN
kW
kW
kW
10.0 ( 4.0 ~ 11.2 )
11.2 ( 4.0 ~ 12.5 )
3.25 / 3.26
3.08 / 3.44
5
24
60 / 60
70 / 70
42 / 36 / 30
42 / 36 / 32
49 / 49
11.5 / 9 / 7
11.5 / 9 / 8
75 / 73
A
dB(A)
m3/min
mm
kg
ømm
m
m
°C
FDTC60VF
FDC125VN
1 Phase 220-240V, 50Hz / 220V, 60Hz
12.5 ( 5.0 ~ 14.0 )
14.0 ( 4.0 ~ 16.0 )
5.35 / 4.62
2.34 / 3.03
5
24
60 / 60
72 / 72
46 / 39 / 30
46 / 39 / 32
50 / 51
13.5 / 10 / 7
13.5 / 10 / 8
75 / 73
Unit: 248 x 570 x 570 Panel: 35 x 700 x 700
845 x 970 x 370
18.5(Unit:15 Panel:3.5)
81
9.52(3/8") / 15.88(5/8")
Max.50
Max.30 / Max.15
-15~43*3
-20~20
TC-PSA-25W-E
Pocket plastic net x 1(Washable)
wired:RC-EX1A, RC-E5, RCH-E3 wireless:RCN-TC-24W-ER
FDTC140VNTVF
Triple
FDTC50VF
FDC140VN
14.0 ( 5.0 ~ 14.5 )
16.0 ( 4.0 ~ 16.5 )
4.64 / 4.52
3.02 / 3.54
5
24
60 / 60
73 / 73
42 / 36 / 30
42 / 36 / 32
51 / 51
11.5 / 9 / 7
11.5 / 9 / 8
75 / 73
he values are for simultaneous Multi operation.
FDTC100VSPVF
Set model name
Indoor unit
Outdoor unit
Power source
Nominal cooling capacity (Min~Max)
Nominal heating capacity (Min~Max)
Power consumption Cooling/Heating
EER/COP
Cooling/Heating
Inrush current
Max. current
2
Sound power Indoor* Cooling/Heating
level*1
Outdoor Cooling/Heating
Cooling (Hi/Me/Lo)
Sound
Indoor*2
pressure
Heating (Hi/Me/Lo)
level*1 2
Outdoor Cooling/Heating
Cooling (Hi/Me/Lo)
Indoor*2
Air flow 2
Heating (Hi/Me/Lo)
Outdoor Cooling/Heating
Indoor
Exterior
HeightxWidthxDepth
dimensions Outdoor
Indoor
Net weight
Outdoor
Ref.piping size Liquid/Gas
Refrigerant line (one way) length
Vertical height differences Outdoor is higher/lower
Cooling
Outdoor operating
temperature range
Heating
Panel
Air filter, Q'ty
Remote control (option)
FDTC125VSPVF
FDTC140VSTVF
FDTC200VSADVF
FDTC250VSADVF
Triple
Double Twin
FDTC60VF
FDTC50VF
FDTC50VF
FDTC60VF
FDC125VS
FDC140VS
FDC200VSA
FDC250VSA
3 Phase 380-415V, 50Hz / 380V, 60Hz
12.5 ( 5.0 ~ 14.0 )
14.0 ( 5.0 ~ 14.5 )
19.0 ( 5.2 ~ 22.4 )
24.0 ( 6.9 ~ 28.0 )
14.0 ( 4.0 ~ 16.0 )
16.0 ( 4.0 ~ 16.5 )
22.4 ( 3.3 ~ 25.0 )
27.0 ( 5.5 ~ 31.5 )
5.35 / 4.62
4.64 / 4.52
6.95 / 6.98
11.10 / 9.66
2.34 / 3.03
3.02 / 3.54
2.73 / 3.21
2.16 / 2.80
5
5
5
5
15
15
20
21
60 / 60
60 / 60
60 / 60
60 / 60
72 / 72
73 / 73
72 / 74
75 / 75
46 / 39 / 30
42 / 36 / 30
42 / 36 / 30
46 / 39 / 30
46 / 39 / 32
42 / 36 / 32
42 / 36 / 32
46 / 39 / 32
50 / 51
51 / 51
58 / 59
61 / 62
13.5 / 10 / 7
11.5 / 9 / 7
11.5 / 9 / 7
13.5 / 10 / 7
13.5 / 10 / 8
11.5 / 9 / 8
11.5 / 9 / 8
13.5 / 10 / 8
75 / 73
75 / 73
135 / 135
143 / 151
Unit: 248 x 570 x 570 Panel: 35 x 700 x 700
845 x 970 x 370
1,300 x 970 x 370
1,505 x 970 x 370
18.5(Unit:15 Panel:3.5)
83
115
143
9.52(3/8") / 15.88(5/8")
9.52(3/8") / 22.22(7/8") 12.7(1/2") / 22.22(7/8")
Max.50
Max.70
Max.30 / Max.15
-15~43*3
-15~50*3
-20~20
-15~20
TC-PSA-25W-E
Pocket plastic net x 1(Washable)
wired:RC-EX1A, RC-E5, RCH-E3 wireless:RCN-TC-24W-ER
Twin
FDTC50VF
FDC100VS
kW
kW
kW
A
dB(A)
m3/min
10.0 ( 4.0 ~ 11.2 )
11.2 ( 4.0 ~ 12.5 )
3.25 / 3.26
3.08 / 3.44
5
15
60 / 60
70 / 70
42 / 36 / 30
42 / 36 / 32
49 / 49
11.5 / 9 / 7
11.5 / 9 / 8
75 / 73
mm
kg
ømm
m
m
°C
2 Powerful-Hi can be selected.
ound pressure level:
N( )P
Air ow:
N( )P
. m3 min
d (A)
N( )
N( )
d (A)
. m3 min
A
A
d (A)
. m3 min
19
DUCT CONNECTED -High Static pressure-
FDU
R410A
FDU 71/100/125/140
FDU 200/250
Tropical Usage Mode
Remote control (Option)
Wired
RC-EX1A
RC-E5
Wireless
RCH-E3
RCN-KIT3-E
Point
1 Automatic external static pressure (E.S.P.) control
Indoor unit
Duct
Duct
Longer Duct
Ceiling
Keep the same
air flow volume
case1
Setting No.
No.8
No.9 No.10 No.11 No.12 No.13 No.14 No.15
E.S.P.
80Pa
90Pa 100Pa 110Pa 120Pa 130Pa 140Pa 150Pa
case2
You can set External Static Pressure (E.S.P.) by method of
manual setting on remote control. Indoor unit will control
fan-speed to keep rated air flow volume at each fan speed setting.
You can set required E.S.P. by wired remote control that
calculated with the set air flow rate and pressure loss of the duct
connected.
E.S.P. button
External Static Pressure
(E.S.P.) can be set by
E.S.P. button.
*Range of 80~150 Pa is set at ex-factory default.
Range of 10~200 Pa is available by setting SW8-4 switch on at site.
RC-E5
<Expansion of external static pressure range>
Previous
Current
10~130Pa
10~200Pa
2 Reduction of sound pressure level
Point
Thanks to use of DC fan motor, fan steps increase from two to
four and quiet operation is achieved.(FDU200/250)
Previous
20
Current
Lo mode
3 High efficiency
Point
Energy efficiency is improved by use of DC fan motor & high
efficient heat exchanger.
8HP
(in case of 50Hz)
4
3.03
3.09
3.01
10HP
4
FDU71
37
25
12dB(A) less!!
3
2
2
FDU100
38
30
8dB(A) less!!
1
1
FDU200
51
45
6dB(A) less!!
2.52
Previous
COP
Current
Previous
Current
EER
(in case of 50Hz)
3.68
3.72
Previous
Current
3
COP
3.75
3.29
Previous
Current
EER
4 Transparent inspection window
5 Improvement of the serviceability
Point
Point
Dirt condition of the bottom of a drain pan can be checked through
this transparent inspection window without removing drain pan.
A cross is visible
Fan unit (impeller and motor) can be
pulled out from the right side of the
unit. Maintenance can be available
from the right side or the bottom side.
Pipe
Fan unit
invisible
Cleaning
Cleaning
not required
required
An outer
circle is visible
6 Enhanced installation workability
Point
600mm Drain Pump is mounted in
FDU71/100/125/140.
The indoor unit is completely hidden
in the ceiling, so this is suitable for
spaces with classy interior decoration.
invisible
600mm
Round duct adapter
In case of requirements of round duct adapter, please access
the followings for details.
Company : AIRZONE
e-mail : jmoral@altracorporacion.es
tel : +34-902-400-445
OUTDOOR UNIT
Micro Inverter
100~140VN(S)X
100~140VN(S)
Chargeless
15m
30m
Height x Width x Depth (mm) 640 x 800(+71) x 290 750 x 880(+88) x 340 1,300 x 970 x 370
845 x 970 x 370
SRC•FDC
40~60ZMX
71VNX
200VSA
250VSA
model
30m
1,300 x 970 x 370 1,505 x 970 x 370
Standard Inverter
FDC
71VNP
90VNP
100VNP
model
Chargeless
15m
Height x Width x Depth (mm) 640 x 800(+71) x 290 750 x 880(+88) x 340
845 x 970 x 370
21
DIMENSIONS (Unit:mm)
Model FDU71VF1
N
View N
Models FDU100VF2,125VF,140VF
N
View N
Models FDU200VG, 250VG
N
View N
22
SPECIFICATIONS
Set model name
Indoor unit
Outdoor unit
Power source
Nominal cooling capacity (Min~Max)
Nominal heating capacity (Min~Max)
Power consumption Cooling/Heating
EER/COP
Cooling/Heating
Inrush current
Max. current
Sound power Indoor Cooling/Heating
level*1
Outdoor Cooling/Heating
Cooling (Hi/Me/Lo)
Sound
Indoor
pressure
Heating (Hi/Me/Lo)
level*1 1
Outdoor Cooling/Heating
Cooling (Hi/Me/Lo)
Indoor
Air flow 1
Heating (Hi/Me/Lo)
Outdoor Cooling/Heating
External static pressure*2
Indoor
Exterior
HeightxWidthxDepth
dimensions Outdoor
Indoor
Net weight
Outdoor
Ref.piping size Liquid/Gas
Refrigerant line (one way) length
Vertical height differences Outdoor is higher/lower
Cooling
Outdoor operating
temperature range
Heating
Air filter
Remote control (option)
Set model name
Indoor unit
Outdoor unit
Power source
Nominal cooling capacity (Min~Max)
Nominal heating capacity (Min~Max)
Power consumption Cooling/Heating
EER/COP
Cooling/Heating
Inrush current
Max. current
Sound power Indoor Cooling/Heating
level*1
Outdoor Cooling/Heating
Cooling (Hi/Me/Lo)
Sound
Indoor
pressure
Heating (Hi/Me/Lo)
1
level* 1
Outdoor Cooling/Heating
Cooling (Hi/Me/Lo)
Indoor
Air flow 1
Heating (Hi/Me/Lo)
Outdoor Cooling/Heating
External static pressure*2
Indoor
Exterior
HeightxWidthxDepth
dimensions Outdoor
Indoor
Net weight
Outdoor
Ref.piping size Liquid/Gas
Refrigerant line (one way) length
Vertical height differences Outdoor is higher/lower
Cooling
Outdoor operating
temperature range
Heating
Air filter
Remote control (option)
1 Powerful-Hi can be selected.
ound pressure level:
N
Air ow:
N
m3 min
FDU71VNXVF1
FDU71VF1
FDC71VNX
kW
kW
kW
A
dB(A)
m3/min
Pa
mm
kg
ømm
m
m
7.1 ( 3.2 ~ 8.0 )
8.0 ( 3.6 ~ 9.0 )
2.05 / 2.01
3.46 / 3.98
5
17
65 / 65
66 / 66
33 / 29 / 25
33 / 29 / 25
51 / 48
19 / 15 / 10
19 / 15 / 10
60 / 50
Standard:35 Max:200
280 x 950 x 635
750 x 880(+88) x 340
34
60
Max.50
°C
FDU100VSXVF2
FDU100VF2
FDC100VSX
kW
kW
kW
A
dB(A)
m3/min
10.0 ( 4.0 ~ 11.2 )
11.2 ( 4.0 ~ 16.0 )
2.68 / 3.02
3.73 / 3.71
5
16
65 / 65
70 / 70
38 / 36 / 30
38 / 36 / 30
48 / 50
28 / 25 / 19
28 / 25 / 19
100 / 100
Pa
mm
kg
ømm
m
m
°C
d (A)
N( )
N( )
m3 min
d (A)
N( )
FDU100VNXVF2
FDU125VNXVF
FDU100VF2
FDU125VF
FDC100VNX
FDC125VNX
1 Phase 220-240V, 50Hz / 220V, 60Hz
10.0 ( 4.0 ~ 11.2 )
12.5 ( 5.0 ~ 14.0 )
11.2 ( 4.0 ~ 12.5 )
14.0 ( 4.0 ~ 17.0 )
2.68 / 3.02
3.49 / 3.77
3.73 / 3.71
3.58 / 3.71
5
5
25
29
65 / 65
67 / 67
70 / 70
70 / 70
38 / 36 / 30
40 / 34 / 29
38 / 36 / 30
40 / 34 / 29
48 / 50
48 / 50
28 / 25 / 19
32 / 26 / 20
28 / 25 / 19
32 / 26 / 20
100 / 100
100 / 100
Standard:60 Max:200
280 x 1,370 x 740
1,300 x 970 x 370
54
105
9.52(3/8") / 15.88(5/8")
Max.100
Max.30 / Max.15
-15~43*3
-20~20
Procure locally
wired:RC-EX1A, RC-E5, RCH-E3 wireless:RCN-KIT3-E
FDU125VSXVF
FDU125VF
FDC125VSX
3 Phase 380-415V, 50Hz / 380V, 60Hz
12.5 ( 5.0 ~ 14.0 )
14.0 ( 4.0 ~ 18.0 )
3.49 / 3.77
3.58 / 3.71
5
18
67 / 67
70 / 70
40 / 34 / 29
40 / 34 / 29
48 / 50
32 / 26 / 20
32 / 26 / 20
100 / 100
Standard:60 Max:200
280 x 1,370 x 740
1,300 x 970 x 370
54
105
9.52(3/8") / 15.88(5/8")
Max.100
Max.30 / Max.15
-15~43*3
-20~20
Procure locally
wired:RC-EX1A, RC-E5, RCH-E3 wireless:RCN-KIT3-E
N( )
m3 min
d (A)
N( )
N( )
m3 min
FDU140VNXVF
FDU140VF
FDC140VNX
14.0 ( 5.0 ~ 16.0 )
16.0 ( 4.0 ~ 18.0 )
4.28 / 4.42
3.27 / 3.62
5
30
70 / 70
72 / 72
40 / 35 / 30
40 / 35 / 30
49 / 52
35 / 28 / 22
35 / 28 / 22
100 / 100
FDU140VSXVF
FDU140VF
FDC140VSX
14.0 ( 5.0 ~ 16.0 )
16.0 ( 4.0 ~ 20.0 )
4.28 / 4.42
3.27 / 3.62
5
19
70 / 70
72 / 72
40 / 35 / 30
40 / 35 / 30
49 / 52
35 / 28 / 22
35 / 28 / 22
100 / 100
d (A)
NOTES:
he data are measured under the following conditions( O- ).
Cooling: ndoor temp. of
C
C
and outdoor temp. of
C .
eating: ndoor temp. of
C
and outdoor temp. of C
C
.
the value in an anechoic cham er. uring operation these values are somewhat higher due to am ient conditions.
* :: Endicates
ternal static pressure is changea le to e set y the remote control. MA e ternal static pressure is igh static pressure setting. he values of sound pressure
* level
ecome d (A) higher at e ternal static pressure of
Pa.
f a cooling operation is conducted when the outdoor air temperature is
C or lower the outdoor unit should e installed at a place where it is not in uenced y
* : natural
wind. f wind lows the low pressure will drop and compressor fre uency will increase this will cause the capacity to drop and may cause the unit to reak
down.
23
SPECIFICATIONS
Set model name
Indoor unit
Outdoor unit
Power source
Nominal cooling capacity (Min~Max)
Nominal heating capacity (Min~Max)
Power consumption Cooling/Heating
EER/COP
Cooling/Heating
Inrush current
Max. current
Sound power Indoor Cooling/Heating
level*1
Outdoor Cooling/Heating
Cooling (Hi/Me/Lo)
Sound
Indoor
pressure
Heating (Hi/Me/Lo)
level*1 1
Outdoor Cooling/Heating
Cooling (Hi/Me/Lo)
Indoor
Air flow 1
Heating (Hi/Me/Lo)
Outdoor Cooling/Heating
External static pressure*2
Indoor
Exterior
HeightxWidthxDepth
dimensions Outdoor
Indoor
Net weight
Outdoor
Ref.piping size Liquid/Gas
Refrigerant line (one way) length
Vertical height differences Outdoor is higher/lower
Cooling
Outdoor operating
temperature range
Heating
Air filter
Remote control (option)
Set model name
Indoor unit
Outdoor unit
Power source
Nominal cooling capacity (Min~Max)
Nominal heating capacity (Min~Max)
Power consumption Cooling/Heating
EER/COP
Cooling/Heating
Inrush current
Max. current
Sound power Indoor Cooling/Heating
level*1
Outdoor Cooling/Heating
Cooling (Hi/Me/Lo)
Sound
Indoor
pressure
Heating (Hi/Me/Lo)
level*1 1
Outdoor Cooling/Heating
Cooling (Hi/Me/Lo)
Indoor
Air flow 1
Heating (Hi/Me/Lo)
Outdoor Cooling/Heating
External static pressure*2
Indoor
Exterior
HeightxWidthxDepth
dimensions Outdoor
Indoor
Net weight
Outdoor
Ref.piping size Liquid/Gas
Refrigerant line (one way) length
Vertical height differences Outdoor is higher/lower
Cooling
Outdoor operating
temperature range
Heating
Air filter
Remote control (option)
1 Powerful-Hi can be selected.
ound pressure level:
N( )
100VNP1VF2 44dB(A)
Air ow:
N( )
m3 min
NP
m3 min
kW
kW
kW
A
dB(A)
m3/min
Pa
mm
kg
ømm
m
m
°C
FDU100VNVF2
FDU125VNVF
FDU140VNVF
FDU100VSVF2
FDU125VSVF
FDU140VSVF
FDU100VF2
FDU125VF
FDU140VF
FDU100VF2
FDU125VF
FDU140VF
FDC100VN
FDC125VN
FDC140VN
FDC100VS
FDC125VS
FDC140VS
1 Phase 220-240V, 50Hz / 220V, 60Hz
3 Phase 380-415V, 50Hz / 380V, 60Hz
10.0 ( 4.0 ~ 11.2 )
12.5 ( 5.0 ~ 14.0 )
14.0 ( 5.0 ~ 14.5 )
10.0 ( 4.0 ~ 11.2 )
12.5 ( 5.0 ~ 14.0)
14.0 ( 5.0 ~ 14.5)
11.2 ( 4.0 ~ 12.5 )
14.0 ( 4.0 ~ 16.0 )
16.0 ( 4.0 ~ 16.5 )
11.2 ( 4.0 ~ 12.5 )
14.0 ( 4.0 ~ 16.0 )
16.0 ( 4.0 ~ 16.5 )
2.80 / 3.02
3.90 / 3.88
4.95 / 4.69
2.80 / 3.02
3.90 / 3.88
4.95 / 4.69
3.57 / 3.71
3.21 / 3.61
2.83 / 3.41
3.57 / 3.71
3.21 / 3.61
2.83 / 3.41
5
5
5
5
5
5
25
27
28
16
18
19
65 / 65
67 / 67
70 / 70
65 / 65
67 / 67
70 / 70
70 / 70
72 / 72
73 / 73
70 / 70
72 / 72
73 / 73
38 / 36 / 30
40 / 34 / 29
40 / 35 / 30
38 / 36 / 30
40 / 34 / 29
40 / 35 / 30
38 / 36 / 30
40 / 34 / 29
40 / 35 / 30
38 / 36 / 30
40 / 34 / 29
40 / 35 / 30
49 / 49
50 / 51
51 / 51
49 / 49
50 / 51
51 / 51
28 / 25 / 19
32 / 26 / 20
35 / 28 / 22
28 / 25 / 19
32 / 26 / 20
35 / 28 / 22
28 / 25 / 19
32 / 26 / 20
35 / 28 / 22
28 / 25 / 19
32 / 26 / 20
35 / 28 / 22
75 / 73
75 / 73
75 / 73
75 / 73
75 / 73
75 / 73
Standard:60 Max:200
280 x 1,370 x 740
845 x 970 x 370
54
81
83
9.52(3/8") / 15.88(5/8")
Max.50
Max.30 / Max.15
-15~43*3
-20~20
Procure locally
wired:RC-EX1A, RC-E5, RCH-E3 wireless:RCN-KIT3-E
FDU200VSAVG
FDU250VSAVG
FDU200VG
FDU250VG
FDC200VSA
FDC250VSA
3 Phase 380-415V, 50Hz / 380V, 60Hz
kW
19.0 ( 5.2 ~ 22.4 )
24.0 ( 6.9 ~ 28.0)
kW
22.4 ( 3.3 ~ 25.0 )
27.0 ( 5.5 ~ 31.5 )
kW
6.15 / 6.03
7.98 / 7.20
3.09 / 3.71
3.01 / 3.75
5
5
A
25
27
75 / 75
75 / 75
72 / 74
73 / 75
dB(A)
50 / 47 / 45
50 / 47 / 45
50 / 47 / 45
50 / 47 / 45
57 / 59
59 / 62
72 / 64 / 56
72 / 64 / 56
m3/min
72 / 64 / 56
72 / 64 / 56
135 / 135
143 / 151
Pa
Standard:72 Max:200
379 x 1,600 x 893
mm
1,300 x 970 x 370
1,505 x 970 x 370
89
kg
115
143
ømm 9.52(3/8") / 22.22(7/8")
12.7(1/2") / 25.4(1")
m
Max.70
m
Max.30 / Max.15
-15~50*3
°C
-15~20
Procure locally
wired:RC-EX1A, RC-E5, RCH-E3 wireless:RCN-KIT3-E
d (A)
N( )
N( )
3
m min
d (A)
N( )
N( )
3
m min
Standard Inverter
FDU90VNPVF2
FDU100VNP1VF2
FDU100VF2
FDU100VF2
FDC90VNP
FDC100VNP
1 Phase 220-240V, 50Hz / 220V, 60Hz
7.1 ( 1.4 ~ 7.1 )
9.0 ( 1.9 ~ 9.0 )
10.0 ( 2.8 ~ 11.2 )
7.1 ( 1.0 ~ 7.1 )
9.0 ( 1.5 ~ 9.0 )
11.2 ( 2.5 ~ 12.5 )
2.63 / 1.96
2.65 / 2.25
3.00 / 2.93
2.70 / 3.62
3.40 / 4.00
3.33 / 3.82
5
5
5
14.5
18.0
22.0
65 / 65
65 / 65
65 / 65
67 / 67
69 / 69
70 / 70
33 / 29 / 25
38 / 36 / 30
38 / 36 / 30
33 / 29 / 25
38 / 36 / 30
38 / 36 / 30
54 / 54
57 / 55
57 / 61
19 / 15 / 10
28 / 25 / 19
28 / 25 / 19
19 / 15 / 10
28 / 25 / 19
28 / 25 / 19
36 / 36
63 / 49.5
75 / 79
Standard:35 Max:200
Standard:60 Max:200
280 x 950 x 635
280 x 1,370 x 740
640 x 800(+71) x 290
750 x 880(+88) x 340
845 x 970 x 370
34
54
45
57
70
6.35(1/4") / 12.7(1/2")
6.35(1/4") / 15.88(5/8") 9.52(3/8") / 15.88(5/8")
Max.30
Max.20 / Max.20
-15~46*3
-15~20
Procure locally
wired:RC-EX1A, RC-E5, RCH-E3 wireless:RCN-KIT3-E
FDU71VNPVF1
FDU71VF1
FDC71VNP
d (A)
A G:
A G:
3
m min
d (A)
NP
NP
d (A)
3
m min
NP
NP
d (A)
3
m min
NOTES:
24
he data are measured under the following conditions( O- ).
Cooling: ndoor temp. of
C
C
and outdoor temp. of
C .
eating: ndoor temp. of
C
and outdoor temp. of C
C
.
the value in an anechoic cham er. uring operation these values are somewhat higher due to am ient conditions.
* :: Endicates
ternal static pressure is changea le to e set y the remote control. MA e ternal static pressure is igh static pressure setting. he values of sound pressure
* level
ecome d (A) higher at e ternal static pressure of
Pa.
f a cooling operation is conducted when the outdoor air temperature is
C or lower the outdoor unit should e installed at a place where it is not in uenced y
* : natural
wind. f wind lows the low pressure will drop and compressor fre uency will increase this will cause the capacity to drop and may cause the unit to reak
down.
DUCT CONNECTED -Low/Middle Static pressure-
FDUM
R410A
FDUM 40/50/60/71/100/125/140
Remote control (Option)
Wireless
Wired
RC-EX1A
RC-E5
RCH-E3
RCN-KIT3-E
Point
1 Thin design
Filter kit (option)
UM-FL1EF : for 40, 50
UM-FL2EF : for 60, 71
UM-FL3EF : for 100, 125, 140
The height of all FDUM models is only 280mm.
70mm less
19mm less
external static pressure loss:5Pa
H 350
H 299
H 280
H 280
FDUM100/125/140VF
FDUM40/50/60/71VF
Point
2 Automatic external static pressure (E.S.P.) control
You can set External Static Pressure (E.S.P.) by method of
manual setting on remote control. Indoor unit will control
fan-speed to keep rated air flow volume at each fan speed
setting. You can set required E.S.P. by wired remote control that
calculated with the set air flow rate and pressure loss of the duct
connected.
Point
3 Improvement of the serviceability
Fan unit (impeller and motor) can be pulled out from the right
side of the unit. Maintenance can be available from the right
side or the bottom side.
Pipe
E.S.P. button
Unit
External Static Pressure
(E.S.P.) can be set by
E.S.P. button.
RC-E5
Duct
Indoor unit
Duct
Fan unit
Maintenance
hole
Service
space
Longer Duct
Ceiling
Keep the same
air flow volume
case1
Setting No.
No.8
No.9 No.10 No.11 No.12 No.13 No.14 No.15
E.S.P.
80Pa
90Pa 100Pa 110Pa 120Pa 130Pa 140Pa 150Pa
case2
*Range of 80~150 Pa is set at ex-factory default.
Range of 10~200 Pa is available by setting SW8-4 switch on at site.
<Expansion of external static pressure range>
Previous
10~130Pa
Current
10~200Pa
25
Point
4 Transparent inspection window
Dirt condition of the bottom of a drain pan can be checked
through this transparent inspection window without
removing drain pan.
A cross is visible
invisible
Cleaning
Cleaning
not required
required
An outer
circle is visible
5 Enhanced installation workability
Point
600mm Drain Pump is mounted in
all models.
The indoor unit is completely hidden
in the ceiling, so this is suitable for
spaces with classy interior
decoration.
600mm
Round duct adapter
In case of requirements of round duct adapter, please access
the followings for details.
invisible
Company : AIRZONE
e-mail : jmoral@altracorporacion.es
tel : +34-902-400-445
OUTDOOR UNIT
Micro Inverter
SRC • FDC
40~60ZMX
71VNX
100~140VN(S)X
100~140VN(S)
Chargeless
15m
30m
Height x Width x Depth (mm) 640 x 800(+71) x 290 750 x 880(+88) x 340 1,300 x 970 x 370
845 x 970 x 370
200VSA
250VSA
model
Standard Inverter
FDC
71VNP
90VNP
100VNP
model
Chargeless
15m
Height x Width x Depth (mm) 640 x 800(+71) x 290 750 x 880(+88) x 340
845 x 970 x 370
DIMENSIONS (Unit:mm)
Models FDUM40VF, FDUM50VF
N
View N
26
30m
1,300 x 970 x 370 1,505 x 970 x 370
DIMENSIONS (Unit:mm)
Models FDUM60VF,71VF1
N
View N
Models FDUM100VF2,125VF,140VF
N
View N
27
SPECIFICATIONS
Set model name
Indoor unit
Outdoor unit
Power source
Nominal cooling capacity (Min~Max)
Nominal heating capacity (Min~Max)
Power consumption Cooling/Heating
EER/COP
Cooling/Heating
Inrush current
Max. current
Sound power Indoor Cooling/Heating
level*1
Outdoor Cooling/Heating
Cooling (Hi/Me/Lo)
Sound
Indoor
pressure
Heating (Hi/Me/Lo)
level*1 1
Outdoor Cooling/Heating
Cooling (Hi/Me/Lo)
Indoor
Air flow 1
Heating (Hi/Me/Lo)
Outdoor Cooling/Heating
External static pressure*3
Indoor
Exterior
HeightxWidthxDepth
dimensions Outdoor
Indoor
Net weight
Outdoor
Ref.piping size Liquid/Gas
Refrigerant line (one way) length
Vertical height differences Outdoor is higher/lower
Cooling
Outdoor operating
temperature range
Heating
Air filter
Remote control (option)
Set model name
Indoor unit
Outdoor unit
Power source
Nominal cooling capacity (Min~Max)
Nominal heating capacity (Min~Max)
Power consumption Cooling/Heating
EER/COP
Cooling/Heating
Inrush current
Max. current
Sound power Indoor Cooling/Heating
level*1
Outdoor Cooling/Heating
Cooling (Hi/Me/Lo)
Sound
Indoor
Heating (Hi/Me/Lo)
pressure
level*1 1
Outdoor Cooling/Heating
Cooling (Hi/Me/Lo)
Indoor
Air flow 1
Heating (Hi/Me/Lo)
Outdoor Cooling/Heating
External static pressure*3
Indoor
Exterior
HeightxWidthxDepth
dimensions Outdoor
Indoor
Net weight
Outdoor
Ref.piping size Liquid/Gas
Refrigerant line (one way) length
Vertical height differences Outdoor is higher/lower
Cooling
Outdoor operating
temperature range
Heating
Air filter
Remote control (option)
1 Powerful-Hi can be selected.
ound pressure level:
M
Air ow:
M
M
FDUM40ZMXVF
FDUM40VF
SRC40ZMX-S
kW
kW
kW
A
dB(A)
m3/min
Pa
mm
kg
ømm
m
m
°C
kW
kW
kW
A
dB(A)
m3/min
FDUM50ZMXVF
FDUM50VF
SRC50ZMX-S
FDUM60ZMXVF
FDUM71VNXVF1
FDUM100VNXVF2
FDUM60VF
FDUM71VF1
FDUM100VF2
SRC60ZMX-S
FDC71VNX
FDC100VNX
1 Phase 220-240V, 50Hz / 220V, 60Hz
4.0 ( 1.1 ~ 4.7 )
5.0 ( 1.1 ~ 5.6 )
5.6 ( 1.1 ~ 6.3 )
7.1 ( 3.2 ~ 8.0 )
10.0 ( 4.0 ~ 11.2 )
4.5 ( 0.6 ~ 5.4 )
5.4 ( 0.6 ~ 6.3 )
6.7 ( 0.6 ~ 7.1 )
8.0 ( 3.6 ~ 9.0 )
11.2 ( 4.0 ~ 12.5 )
0.952 / 1.07
1.38 / 1.45
1.54 / 1.75
2.03 / 1.99
2.68 / 3.02
4.20 / 4.21
3.62 / 3.72
3.64 / 3.83
3.50 / 4.02
3.73 / 3.71
5
5
5
5
5
12
15
15
17
24
60 / 60
60 / 60
60 / 60
65 / 65
65 / 65
63 / 63
63 / 63
64 / 64
66 / 66
70 / 70
32 / 29 / 26
32 / 29 / 26
31 / 28 / 25
33 / 29 / 25
38 / 36 / 30
32 / 29 / 26
32 / 29 / 26
31 / 28 / 25
33 / 29 / 25
38 / 36 / 30
50 / 50
54 / 50
54 / 54
51 / 48
48 / 50
10 / 9 / 8
10 / 9 / 8
15 / 13 / 10
19 / 15 / 10
28 / 25 / 19
10 / 9 / 8
10 / 9 / 8
15 / 13 / 10
19 / 15 / 10
28 / 25 / 19
36 / 33
40 / 33
41.5 / 39
60 / 50
100 / 100
Standard:35 Max:100
Standard:60 Max:100
280 x 750 x 635
280 x 950 x 635
280 x 1,370 x 740
640 x 800(+71) x 290
750 x 880(+88) x 340
1,300 x 970 x 370
29
34
54
45
60
105
6.35(1/4") / 12.7(1/2")
9.52(3/8") / 15.88(5/8")
Max.30
Max.50
Max.100
Max.20 / Max.20
Max.30 / Max.15
-15~43*4
-15~20
-20~20
Filter kit : UM-FL1EF / UM-FL2EF / UM-FL3EF (option)
wired:RC-EX1A, RC-E5, RCH-E3 wireless:RCN-KIT3-E
FDUM125VNXVF
FDUM140VNXVF
FDUM125VF
FDUM140VF
FDC125VNX
FDC140VNX
1 Phase 220-240V, 50Hz / 220V, 60Hz
12.5 ( 5.0 ~ 14.0 )
14.0 ( 5.0 ~ 16.0 )
14.0 ( 4.0 ~ 17.0 )
16.0 ( 4.0 ~ 18.0 )
3.49 / 3.77
4.28 / 4.42
3.58 / 3.71
3.27 / 3.62
5
5
26
26
67 / 67
70 / 70
70 / 70
72 / 72
40 / 34 / 29
40 / 35 / 30
40 / 34 / 29
40 / 35 / 30
48 / 50
49 / 52
32 / 26 / 20
35 / 28 / 22
32 / 26 / 20
35 / 28 / 22
100 / 100
100 / 100
FDUM100VSXVF2
FDUM125VSXVF
FDUM140VSXVF
FDUM100VF2
FDUM125VF
FDUM140VF
FDC100VSX
FDC125VSX
FDC140VSX
3 Phase 380-415V, 50Hz / 380V, 60Hz
10.0 ( 4.0 ~ 11.2 )
12.5 ( 5.0 ~ 14.0 )
14.0 ( 5.0 ~ 16.0 )
11.2 ( 4.0 ~ 16.0 )
14.0 ( 4.0 ~ 18.0 )
16.0 ( 4.0 ~ 20.0 )
2.68 / 3.02
3.49 / 3.77
4.28 / 4.42
3.73 / 3.71
3.58 / 3.71
3.27 / 3.62
5
5
5
15
15
15
65 / 65
67 / 67
70 / 70
70 / 70
70 / 70
72 / 72
38 / 36 / 30
40 / 34 / 29
40 / 35 / 30
38 / 36 / 30
40 / 34 / 29
40 / 35 / 30
48 / 50
48 / 50
49 / 52
28 / 25 / 19
32 / 26 / 20
35 / 28 / 22
28 / 25 / 19
32 / 26 / 20
35 / 28 / 22
100 / 100
100 / 100
100 / 100
Standard:60 Max:100
280 x 1,370 x 740
1,300 x 970 x 370
54
105
9.52(3/8") / 15.88(5/8")
Max.100
Max.30 / Max.15
-15~43*4
-20~20
Filter kit : UM-FL3EF (option)
wired:RC-EX1A, RC-E5, RCH-E3 wireless:RCN-KIT3-E
Pa
mm
kg
ømm
m
m
°C
M
m3 min
d (A)
M
M
m3 min
d (A)
N
N
d (A)
N( )
d (A)
N( )
m3 min
N( )
m3 min
N( )
d (A)
m3 min
N( )
N( )
d (A)
m3 min
NOTES:
he data are measured under the following conditions( O- ).
Cooling: ndoor temp. of
C
C
and outdoor temp. of
C .
eating: ndoor temp. of
C
and outdoor temp. of C
C
.
ndicates the value in an anechoic cham er. uring operation these values are somewhat higher due to am ient conditions.
*2 :: The
values are for one indoor unit operation.
* : E ternal
static pressure is changea le to e set y the remote control. MA e ternal static pressure is igh static pressure setting. he values of sound pressure
* level ecome
d (A) higher at e ternal static pressure of
Pa.
f a cooling operation is conducted when the outdoor air temperature is
C or lower the outdoor unit should e installed at a place where it is not in uenced y
* : natural
wind. f wind lows the low pressure will drop and compressor fre uency will increase this will cause the capacity to drop and may cause the unit to reak
down.
28
SPECIFICATIONS
he values are for simultaneous Multi operation.
FDUM71VNXPVF
Set model name
Indoor unit
Outdoor unit
Power source
Nominal cooling capacity (Min~Max)
Nominal heating capacity (Min~Max)
Power consumption Cooling/Heating
EER/COP
Cooling/Heating
Inrush current
Max. current
2
Sound power Indoor* Cooling/Heating
level*1
Outdoor Cooling/Heating
Cooling (Hi/Me/Lo)
Sound
Indoor*2
pressure
Heating (Hi/Me/Lo)
1
level* 2
Outdoor Cooling/Heating
Cooling (Hi/Me/Lo)
Indoor*2
Air flow 2
Heating (Hi/Me/Lo)
Outdoor Cooling/Heating
External static pressure*3
Indoor
Exterior
HeightxWidthxDepth
dimensions Outdoor
Indoor
Net weight
Outdoor
Ref.piping size Liquid/Gas
Refrigerant line (one way) length
Vertical height differences Outdoor is higher/lower
Cooling
Outdoor operating
temperature range
Heating
Air filter
Remote control (option)
FDUM100VNXPVF
FDUM125VNXPVF
FDUM140VNXPVF1
Twin
FDUM40VF
FDC71VNX
kW
kW
kW
A
dB(A)
m3/min
Pa
mm
kg
ømm
m
m
°C
FDUM50VF
FDC100VNX
FDUM60VF
FDUM71VF1
FDC125VNX
FDC140VNX
1 Phase 220-240V, 50Hz / 220V, 60Hz
7.1 ( 3.2 ~ 8.0 )
10.0 ( 4.0 ~ 11.2 )
12.5 ( 5.0 ~ 14.0 )
14.0 ( 5.0 ~ 16.0 )
8.0 ( 3.6 ~ 9.0 )
11.2 ( 4.0 ~ 12.5 )
14.0 ( 4.0 ~ 17.0 )
16.0 ( 4.0 ~ 18.0 )
2.01 / 1.91
2.66 / 3.02
3.26 / 3.66
4.36 / 4.35
3.53 / 4.19
3.76 / 3.71
3.83 / 3.83
3.21 / 3.68
5
5
5
5
17
24
26
26
60 / 60
60 / 60
60 / 60
65 / 65
66 / 66
70 / 70
70 / 70
72 / 72
39 / 29 / 26
32 / 29 / 26
31 / 28 / 25
33 / 29 / 25
39 / 29 / 26
32 / 29 / 26
31 / 28 / 25
33 / 29 / 25
51 / 48
48 / 50
48 / 50
49 / 52
10 / 9 / 8
10 / 9 / 8
15 / 13 / 10
19 / 15 / 10
10 / 9 / 8
10 / 9 / 8
15 / 13 / 10
19 / 15 / 10
60 / 50
100 / 100
100 / 100
100 / 100
Standard:35 Max:100
280 x 750 x 635
280 x 950 x 635
750 x 880(+88) x 340
1,300 x 970 x 370
29
34
60
105
9.52(3/8") / 15.88(5/8")
Max.50
Max.100
Max.30 / Max.15
-15~43*4
-20~20
Filter kit : UM-FL1EF / UM-FL2EF (option)
wired:RC-EX1A, RC-E5, RCH-E3 wireless:RCN-KIT3-E
FDUM140VNXTVF
Triple
FDUM50VF
FDC140VNX
14.0 ( 5.0 ~ 16.0 )
16.0 ( 4.0 ~ 18.0 )
4.21 / 4.69
3.33 / 3.41
5
26
60 / 60
72 / 72
32 / 29 / 26
32 / 29 / 26
49 / 52
10 / 9 / 8
10 / 9 / 8
100 / 100
280 x 750 x 635
29
he values are for simultaneous Multi operation.
FDUM100VSXPVF
Set model name
Indoor unit
Outdoor unit
Power source
Nominal cooling capacity (Min~Max)
Nominal heating capacity (Min~Max)
Power consumption Cooling/Heating
EER/COP
Cooling/Heating
Inrush current
Max. current
2
Sound power Indoor* Cooling/Heating
level*1
Outdoor Cooling/Heating
Cooling (Hi/Me/Lo)
Sound
Indoor*2
pressure
Heating (Hi/Me/Lo)
level*1 2
Outdoor Cooling/Heating
Cooling (Hi/Me/Lo)
Indoor*2
Air flow 2
Heating (Hi/Me/Lo)
Outdoor Cooling/Heating
External static pressure*3
Indoor
Exterior
HeightxWidthxDepth
dimensions Outdoor
Indoor
Net weight
Outdoor
Ref.piping size Liquid/Gas
Refrigerant line (one way) length
Vertical height differences Outdoor is higher/lower
Cooling
Outdoor operating
temperature range
Heating
Air filter
Remote control (option)
2 Powerful-Hi can be selected.
ound pressure level:
N P
Air ow:
N P
N( ) P
FDUM125VSXPVF
FDUM140VSXPVF1
Twin
FDUM60VF
FDUM71VF1
FDC125VSX
FDC140VSX
3 Phase 380-415V, 50Hz / 380V, 60Hz
12.5 ( 5.0 ~ 14.0 )
14.0 ( 5.0 ~ 16.0 )
14.0 ( 4.0 ~ 18.0 )
16.0 ( 4.0 ~ 20.0 )
3.26 / 3.66
4.36 / 4.35
3.83 / 3.83
3.21 / 3.68
5
5
15
15
60 / 60
65 / 65
70 / 70
72 / 72
31 / 28 / 25
33 / 29 / 25
31 / 28 / 25
33 / 29 / 25
48 / 50
49 / 52
15 / 13 / 10
19 / 15 / 10
15 / 13 / 10
19 / 15 / 10
100 / 100
100 / 100
Standard:35 Max:100
280 x 950 x 635
1,300 x 970 x 370
34
105
9.52(3/8") / 15.88(5/8")
Max.100
Max.30 / Max.15
-15~43*4
-20~20
Filter kit : UM-FL1EF / UM-FL2EF (option)
wired:RC-EX1A, RC-E5, RCH-E3 wireless:RCN-KIT3-E
FDUM50VF
FDC100VSX
kW
kW
kW
A
dB(A)
m3/min
10.0 ( 4.0 ~ 11.2 )
11.2 ( 4.0 ~ 16.0 )
2.66 / 3.02
3.76 / 3.71
5
15
60 / 60
70 / 70
32 / 29 / 26
32 / 29 / 26
48 / 50
10 / 9 / 8
10 / 9 / 8
100 / 100
Pa
mm
280 x 750 x 635
29
kg
ømm
m
m
°C
N( ) P
m3 min
d (A)
N( ) P
N( ) P
m3 min
d (A)
N( ) P
N( ) P
m3 min
d (A)
N( )
N( )
m3 min
FDUM140VSXTVF
Triple
FDUM50VF
FDC140VSX
14.0 ( 5.0 ~ 16.0 )
16.0 ( 4.0 ~ 20.0 )
4.21 / 4.69
3.33 / 3.41
5
15
60 / 60
72 / 72
32 / 29 / 26
32 / 29 / 26
49 / 52
10 / 9 / 8
10 / 9 / 8
100 / 100
280 x 750 x 635
29
d (A)
29
SPECIFICATIONS
Set model name
Indoor unit
Outdoor unit
Power source
Nominal cooling capacity (Min~Max)
Nominal heating capacity (Min~Max)
Power consumption Cooling/Heating
EER/COP
Cooling/Heating
Inrush current
Max. current
Sound power Indoor Cooling/Heating
level*1
Outdoor Cooling/Heating
Cooling (Hi/Me/Lo)
Sound
Indoor
pressure
Heating (Hi/Me/Lo)
level*1 1
Outdoor Cooling/Heating
Cooling (Hi/Me/Lo)
Indoor
Air flow 1
Heating (Hi/Me/Lo)
Outdoor Cooling/Heating
External static pressure*3
Indoor
Exterior
HeightxWidthxDepth
dimensions Outdoor
Indoor
Net weight
Outdoor
Ref.piping size Liquid/Gas
Refrigerant line (one way) length
Vertical height differences Outdoor is higher/lower
Cooling
Outdoor operating
temperature range
Heating
Air filter
Remote control (option)
kW
kW
kW
A
dB(A)
m3/min
Pa
mm
kg
ømm
m
m
°C
FDUM100VNVF2
FDUM125VNVF
FDUM140VNVF
FDUM100VSVF2
FDUM125VSVF
FDUM140VSVF
FDUM100VF2
FDUM125VF
FDUM140VF
FDUM100VF2
FDUM125VF
FDUM140VF
FDC100VN
FDC125VN
FDC140VN
FDC100VS
FDC125VS
FDC140VS
1 Phase 220-240V, 50Hz / 220V, 60Hz
3 Phase 380-415V, 50Hz / 380V, 60Hz
10.0 ( 4.0 ~ 11.2 )
12.5 ( 5.0 ~ 14.0 )
14.0 ( 5.0 ~ 14.5 )
10.0 ( 4.0 ~ 11.2 )
12.5 ( 5.0 ~ 14.0 )
14.0 ( 5.0 ~ 14.5 )
11.2 ( 4.0 ~ 12.5 )
14.0 ( 4.0 ~ 16.0 )
16.0 ( 4.0 ~ 16.5 )
11.2 ( 4.0 ~ 12.5 )
14.0 ( 4.0 ~ 16.0 )
16.0 ( 4.0 ~ 16.5 )
2.80 / 3.02
3.90 / 3.88
4.95 / 4.69
2.80 / 3.02
3.90 / 3.88
4.95 / 4.69
3.57 / 3.71
3.21 / 3.61
2.83 / 3.41
3.57 / 3.71
3.21 / 3.61
2.83 / 3.41
5
5
5
5
5
5
24
24
24
15
15
15
65 / 65
67 / 67
70 / 70
65 / 65
67 / 67
70 / 70
70 / 70
72 / 72
73 / 73
70 / 70
72 / 72
73 / 73
38 / 36 / 30
40 / 34 / 29
40 / 35 / 30
38 / 36 / 30
40 / 34 / 29
40 / 35 / 30
38 / 36 / 30
40 / 34 / 29
40 / 35 / 30
38 / 36 / 30
40 / 34 / 29
40 / 35 / 30
49 / 49
50 / 51
51 / 51
49 / 49
50 / 51
51 / 51
28 / 25 / 19
32 / 26 / 20
35 / 28 / 22
28 / 25 / 19
32 / 26 / 20
35 / 28 / 22
28 / 25 / 19
32 / 26 / 20
35 / 28 / 22
28 / 25 / 19
32 / 26 / 20
35 / 28 / 22
75 / 73
75 / 73
75 / 73
75 / 73
75 / 73
75 / 73
Standard:60 Max:100
280 x 1,370 x 740
845 x 970 x 370
54
81
83
9.52(3/8") / 15.88(5/8")
Max.50
Max.30 / Max.15
-15~43*4
-20~20
Filter kit : UM-FL3EF (option)
wired:RC-EX1A, RC-E5, RCH-E3 wireless:RCN-KIT3-E
he values are for simultaneous Multi operation.
FDUM100VNPVF
Set model name
Indoor unit
Outdoor unit
Power source
Nominal cooling capacity (Min~Max)
Nominal heating capacity (Min~Max)
Power consumption Cooling/Heating
EER/COP
Cooling/Heating
Inrush current
Max. current
2
Sound power Indoor* Cooling/Heating
level*1
Outdoor Cooling/Heating
Cooling (Hi/Me/Lo)
Sound
Indoor*2
pressure
Heating (Hi/Me/Lo)
level*1 1
Outdoor Cooling/Heating
Cooling (Hi/Me/Lo)
Indoor*2
Air flow 1
Heating (Hi/Me/Lo)
Outdoor Cooling/Heating
External static pressure*3
Indoor
Exterior
HeightxWidthxDepth
dimensions Outdoor
Indoor
Net weight
Outdoor
Ref.piping size Liquid/Gas
Refrigerant line (one way) length
Vertical height differences Outdoor is higher/lower
Cooling
Outdoor operating
temperature range
Heating
Air filter
Remote control (option)
1 Powerful-Hi can be selected.
ound pressure level:
N( )
140VNTVF 37dB(A)
3
Air ow:
N( )
m min
m3 min
FDUM125VNPVF
FDUM140VNPVF1
FDUM140VNTVF
FDUM100VSPVF
Twin
Triple
Twin
FDUM60VF
FDUM71VF1
FDUM50VF
FDUM50VF
FDC125VN
FDC140VN
FDC140VN
FDC100VS
3 Phase 380-415V, 50Hz / 380V, 60Hz
1 Phase 220-240V, 50Hz / 220V, 60Hz
12.5 ( 5.0 ~ 14.0 )
14.0 ( 5.0 ~ 14.5 )
14.0 ( 5.0 ~ 14.5 )
10.0 ( 4.0 ~ 11.2 )
14.0 ( 4.0 ~ 16.0 )
16.0 ( 4.0 ~ 16.5 )
16.0 ( 4.0 ~ 16.5 )
11.2 ( 4.0 ~ 12.5 )
3.87 / 4.07
4.78 / 4.60
4.65 / 5.15
2.84 / 3.35
3.23 / 3.44
2.93 / 3.48
3.01 / 3.11
3.52 / 3.34
5
5
5
5
24
24
15
15
60 / 60
65 / 65
60 / 60
60 / 60
72 / 72
73 / 73
73 / 73
70 / 70
31 / 28 / 25
33 / 29 / 25
32 / 29 / 26
32 / 29 / 26
31 / 28 / 25
33 / 29 / 25
32 / 29 / 26
32 / 29 / 26
50 / 51
51 / 51
51 / 51
49 / 49
15 / 13 / 10
19 / 15 / 10
10 / 9 / 8
10 / 9 / 8
15 / 13 / 10
19 / 15 / 10
10 / 9 / 8
10 / 9 / 8
75 / 73
75 / 73
75 / 73
75 / 73
Standard:35 Max:100
280 x 950 x 635
280 x 750 x 635
845 x 970 x 370
34
29
81
83
9.52(3/8") / 15.88(5/8")
Max.50
Max.30 / Max.15
-15~43*4
-20~20
Filter kit : UM-FL1EF / UM-FL2EF (option)
wired:RC-EX1A, RC-E5, RCH-E3 wireless:RCN-KIT3-E
FDUM50VF
FDC100VN
kW
kW
kW
A
dB(A)
m3/min
10.0 ( 4.0 ~ 11.2 )
11.2 ( 4.0 ~ 12.5 )
2.84 / 3.35
3.52 / 3.34
5
24
60 / 60
70 / 70
32 / 29 / 26
32 / 29 / 26
49 / 49
10 / 9 / 8
10 / 9 / 8
75 / 73
Pa
280 x 750 x 635
mm
29
kg
ømm
m
m
°C
d (A)
N( )
N( )
3
m min
d (A)
N( )
N( )
3
m min
d (A)
N( )P
N( )P
3
m min
d (A)
NP
NP
3
m min
d (A)
NP
NP
3
m min
d (A)
N
NOTES:
30
he data are measured under the following conditions( O- ).
Cooling: ndoor temp. of
C
C
and outdoor temp. of
C .
eating: ndoor temp. of
C
and outdoor temp. of C
C
.
ndicates the value in an anechoic cham er. uring operation these values are somewhat higher due to am ient conditions.
*2 :: The
values are for one indoor unit operation.
* : E ternal
static pressure is changea le to e set y the remote control. MA e ternal static pressure is igh static pressure setting. he values of sound pressure
* level ecome
d (A) higher at e ternal static pressure of
Pa.
f a cooling operation is conducted when the outdoor air temperature is
C or lower the outdoor unit should e installed at a place where it is not in uenced y natural
* : wind.
f wind lows the low pressure will drop and compressor fre uency will increase this will cause the capacity to drop and may cause the unit to reak down.
SPECIFICATIONS
he values are for simultaneous Multi operation.
FDUM125VSPVF
Set model name
Indoor unit
Outdoor unit
Power source
Nominal cooling capacity (Min~Max)
Nominal heating capacity (Min~Max)
Power consumption Cooling/Heating
EER/COP
Cooling/Heating
Inrush current
Max. current
2
Sound power Indoor* Cooling/Heating
level*1
Outdoor Cooling/Heating
Cooling (Hi/Me/Lo)
Sound
Indoor*2
pressure
Heating (Hi/Me/Lo)
level*1 2
Outdoor Cooling/Heating
Cooling (Hi/Me/Lo)
Indoor*2
Air flow 2
Heating (Hi/Me/Lo)
Outdoor Cooling/Heating
External static pressure*3
Indoor
Exterior
HeightxWidthxDepth
dimensions Outdoor
Indoor
Net weight
Outdoor
Ref.piping size Liquid/Gas
Refrigerant line (one way) length
Vertical height differences Outdoor is higher/lower
Cooling
Outdoor operating
temperature range
Heating
Air filter
Remote control (option)
Set model name
Indoor unit
Outdoor unit
Power source
Nominal cooling capacity (Min~Max)
Nominal heating capacity (Min~Max)
Power consumption Cooling/Heating
EER/COP
Cooling/Heating
Inrush current
Max. current
Sound power Indoor Cooling/Heating
level*1
Outdoor Cooling/Heating
Cooling (Hi/Me/Lo)
Sound
Indoor
pressure
Heating (Hi/Me/Lo)
level*1 2
Outdoor Cooling/Heating
Cooling (Hi/Me/Lo)
Indoor
Air flow 2
Heating (Hi/Me/Lo)
Outdoor Cooling/Heating
External static pressure*3
Indoor
Exterior
HeightxWidthxDepth
dimensions Outdoor
Indoor
Net weight
Outdoor
Ref.piping size Liquid/Gas
Refrigerant line (one way) length
Vertical height differences Outdoor is higher/lower
Cooling
Outdoor operating
temperature range
Heating
Air filter
Remote control (option)
2 Powerful-Hi can be selected.
ound pressure level:
P
NP
d (A)
NP
3
Air ow:
P
m min
NP
m3 min
m3 min
kW
kW
kW
A
dB(A)
m3/min
Pa
mm
kg
ømm
m
m
°C
FDUM140VSPVF1
FDUM200VSAPVF2
FDUM250VSAPVF
FDUM140VSTVF
FDUM200VSATVF1
Twin
Triple
FDUM60VF
FDUM71VF1
FDUM100VF2
FDUM125VF
FDUM50VF
FDUM71VF1
FDC125VS
FDC140VS
FDC200VSA
FDC250VSA
FDC140VS
FDC200VSA
3 Phase 380-415V, 50Hz / 380V, 60Hz
12.5 ( 5.0 ~ 14.0 )
14.0 ( 5.0 ~ 14.5 )
19.0 ( 5.2 ~ 22.4 )
24.0 ( 6.9 ~ 28.0 )
14.0 ( 5.0 ~ 14.5 )
19.0 ( 5.2 ~ 22.4 )
14.0 ( 4.0 ~ 16.0 )
16.0 ( 4.0 ~ 16.5 )
22.4 ( 3.3 ~ 25.0 )
27.0 ( 5.5 ~ 31.5 )
16.0 ( 4.0 ~ 16.5 )
22.4 ( 3.3 ~ 25.0 )
3.87 / 4.07
4.78 / 4.60
6.51 / 6.04
8.33 / 7.52
4.65 / 5.15
6.46 / 6.15
3.23 / 3.44
2.93 / 3.48
2.92 / 3.71
2.88 / 3.59
3.01 / 3.11
2.94 / 3.64
5
5
5
5
5
5
15
15
22
24
15
22
60 / 60
65 / 65
65 / 65
67 / 67
60 / 60
65 / 65
72 / 72
73 / 73
72 / 74
73 / 75
73 / 73
72 / 74
31 / 28 / 25
33 / 29 / 25
38 / 36 / 30
40 / 34 / 29
32 / 29 / 26
33 / 29 / 25
31 / 28 / 25
33 / 29 / 25
38 / 36 / 30
40 / 34 / 29
32 / 29 / 26
33 / 29 / 25
50 / 51
51 / 51
58 / 59
59 / 62
51 / 51
58 / 59
15 / 13 / 10
19 / 15 / 10
28 / 25 / 19
32 / 26 / 20
10 / 9 / 8
19 / 15 / 10
15 / 13 / 10
19 / 15 / 10
28 / 25 / 19
32 / 26 / 20
10 / 9 / 8
19 / 15 / 10
75 / 73
75 / 73
135 / 135
143 / 151
75 / 73
135 / 135
Standard:35 Max:100
Standard:60 Max:100
Standard:35 Max:100 Standard:35 Max:100
280 x 950 x 635
280 x 1,370 x 740
280 x 750 x 635
280 x 950 x 635
845 x 970 x 370
1,300 x 970 x 370
1,505 x 970 x 370
845 x 970 x 370
1,300 x 970 x 370
34
54
29
34
83
115
143
83
115
9.52(3/8") / 15.88(5/8")
9.52(3/8") / 22.22(7/8") 12.7(1/2") / 22.22(7/8") 9.52(3/8") / 15.88(5/8") 9.52(3/8") / 22.22(7/8")
Max.50
Max.70
Max.50
Max.70
Max.30 / Max.15
-15~43*4
-15~50*4
-15~43*4
-15~50*4
-20~20
-15~20
-20~20
-15~20
Filter kit : UM-FL1EF / UM-FL2EF / UM-FL3EF (option)
wired:RC-EX1A, RC-E5, RCH-E3 wireless:RCN-KIT3-E
Standard Inverter
FDUM90VNPVF2
FDUM100VNP1VF2
FDUM100VF2
FDUM100VF2
FDC90VNP
FDC100VNP
1 Phase 220-240V, 50Hz / 220V, 60Hz
9.0 ( 1.9 ~ 9.0 )
10.0 ( 2.8 ~ 11.2 )
9.0 ( 1.5 ~ 9.0 )
11.2 ( 2.5 ~ 12.5 )
2.65 / 2.25
3.00 / 2.93
3.40 / 4.00
3.33 / 3.82
5
5
18.0
22.0
65 / 65
65 / 65
69 / 69
70 / 70
38 / 36 / 30
38 / 36 / 30
38 / 36 / 30
38 / 36 / 30
57 / 55
57 / 61
28 / 25 / 19
28 / 25 / 19
28 / 25 / 19
28 / 25 / 19
63 / 49.5
75 / 79
Standard:60 Max:100
280 x 1,370 x 740
750 x 880(+88) x 340
845 x 970 x 370
54
57
70
6.35(1/4") / 15.88(5/8")
9.52(3/8") / 15.88(5/8")
Max.30
Max.20 / Max.20
-15~46*4
-15~20
Filter kit : UM-FL2EF / UM-FL3EF (option)
wired:RC-EX1A, RC-E5, RCH-E3 wireless:RCN-KIT3-E
FDUM71VNPVF1
FDUM71VF1
FDC71VNP
kW
kW
kW
7.1 ( 1.4 ~ 7.1 )
7.1 ( 1.0 ~ 7.1 )
2.63 / 1.96
2.70 / 3.62
5
14.5
65 / 65
67 / 67
33 / 29 / 25
33 / 29 / 25
54 / 54
19 / 15 / 10
19 / 15 / 10
36 / 36
Standard:35 Max:200
280 x 950 x 635
640 x 800(+71) x 290
34
45
6.35(1/4") / 12.7(1/2")
A
dB(A)
m3/min
Pa
mm
kg
ømm
m
m
°C
d (A)
d (A)
P
NP
P
NP
m min
m3 min
3
d (A)
d (A)
AP
AP
3
m min
d (A)
AP
AP
3
m min
d (A)
d (A)
3
m min
A
A
d (A)
3
m min
NP
31
CEILING SUSPENDED
FDE
R410A
NEW
FDE 40/50/60/71/100/125/140
Remote control (Option)
Wired
RC-EX1A
RC-E5
Wireless
RCH-E3
RCN-E-E
2 Reduction of weight
1 High efficiency
Point
Point
Energy efficiency was improved by use of DC fan motor & high efficient
heat exchanger.
Thanks to decreasing the numbers of fan motor from two to one,
reduction of weight was achieved.
EER 5
3.92
4
3.57
3.57
3
3.24
3.18
Current
2.81
2
1
100VG 100VF
125VG 125VF
New
60·71VG
37
100·125·140VG 49
33 4kg less!!
43 6kg less!!
140VG 140VF
•In case of Hyper INV
3 Reduction of sound pressure level (Lo mode)
Point
dB(A)
50
40
38dB(A)
7dB(A)
less!!
6dB(A)
less!!
31dB(A)
31dB(A)
30
38dB(A)
38dB(A)
37dB(A)
6dB(A)
less!!
6dB(A)
less!!
5dB(A)
less!!
8dB(A)
less!!
43dB(A)
7dB(A)
less!!
39dB(A)
34dB(A)
32dB(A)
32dB(A)
43dB(A)
35dB(A)
36dB(A)
20
40VG
50VG
60VG
4 Flap control
Point
The flap can swing within the range of upper and lower
flap position selected with wired remote control.
Selected
upper position
Max swing
range
Selected
lower position
32
71VG
100VG
125VG
140VG
5 Improved installation workability
Point
Increased freedom of a piping layout
The refrigerant pipe from the
unit can be arranged in three
directions, rear, right and up.
The drain pipe can be
arranged in two directions,
left and right. This will allow
a free layout of piping for
various installation
conditions. The unit can only
be serviced from the bottom.
Up
Right
Rear
OUTDOOR UNIT
Micro Inverter
SRC • FDC
40~60ZMX
71VNX
100~140VN(S)X
100~140VN(S)
Chargeless
15m
30m
Height x Width x Depth (mm) 640 x 800(+71) x 290 750 x 880(+88) x 340 1,300 x 970 x 370
845 x 970 x 370
200VSA
250VSA
model
30m
1,300 x 970 x 370 1,505 x 970 x 370
Standard Inverter
FDC
71VNP
90VNP
100VNP
model
Chargeless
15m
Height x Width x Depth (mm) 640 x 800(+71) x 290 750 x 880(+88) x 340
845 x 970 x 370
DIMENSIONS (Unit:mm)
[e]
[d]
[a]
[b]
[c]
40·50·60VG
12.7(1/2”)(Flare)
6.35(1/4”)(Flare)
71·100·125·140VG
15.88(5/8”)(Flare)
9.52(3/8”)(Flare)
VP20
(M10 or M8)
PE cover
Plate cover
(Knock out)
[f]
DIMENSIONS TABLE
model
[a]
[b]
[c]
[d]
[e]
[f]
FDE40,50
1022
990
1070
215
210
4000
FDE60,71
1272
1240
1320
215
210
4500
FDE100~140
1572
1540
1620
255
250
5000
33
SPECIFICATIONS
Set model name
Indoor unit
Outdoor unit
Power source
Nominal cooling capacity (Min~Max)
Nominal heating capacity (Min~Max)
Power consumption Cooling/Heating
EER/COP
Cooling/Heating
Inrush current
Max. current
Sound power Indoor Cooling/Heating
level*1
Outdoor Cooling/Heating
Cooling (Hi/Me/Lo)
Sound
Indoor
pressure
Heating (Hi/Me/Lo)
level*1 1
Outdoor Cooling/Heating
Cooling (Hi/Me/Lo)
Indoor
Air flow 1
Heating (Hi/Me/Lo)
Outdoor Cooling/Heating
Indoor
Exterior
HeightxWidthxDepth
dimensions Outdoor
Indoor
Net weight
Outdoor
Ref.piping size Liquid/Gas
Refrigerant line (one way) length
Vertical height differences Outdoor is higher/lower
Cooling
Outdoor operating
temperature range
Heating
Air filter, Q'ty
Remote control (option)
Set model name
Indoor unit
Outdoor unit
Power source
Nominal cooling capacity (Min~Max)
Nominal heating capacity (Min~Max)
Power consumption Cooling/Heating
EER/COP
Cooling/Heating
Inrush current
Max. current
Sound power Indoor Cooling/Heating
level*1
Outdoor Cooling/Heating
Cooling (Hi/Me/Lo)
Sound
Indoor
pressure
Heating (Hi/Me/Lo)
1
level* 1
Outdoor Cooling/Heating
Cooling (Hi/Me/Lo)
Indoor
Air flow 1
Heating (Hi/Me/Lo)
Outdoor Cooling/Heating
Indoor
Exterior
HeightxWidthxDepth
dimensions Outdoor
Indoor
Net weight
Outdoor
Ref.piping size Liquid/Gas
Refrigerant line (one way) length
Vertical height differences Outdoor is higher/lower
Cooling
Outdoor operating
temperature range
Heating
Air filter, Q'ty
Remote control (option)
FDE40ZMXVG
FDE40VG
SRC40ZMX-S
kW
kW
kW
A
dB(A)
m3/min
mm
kg
ømm
m
m
°C
kW
kW
kW
A
dB(A)
m3/min
FDE50ZMXVG
FDE50VG
SRC50ZMX-S
FDE60ZMXVG
FDE71VNXVG
FDE100VNXVG
FDE60VG
FDE71VG
FDE100VG
SRC60ZMX-S
FDC71VNX
FDC100VNX
1 Phase 220-240V, 50Hz / 220V, 60Hz
4.0 ( 1.1 ~ 4.7 )
5.0 ( 1.1 ~ 5.6 )
5.6 ( 1.1 ~ 6.3 )
7.1 ( 3.2 ~ 8.0 )
10.0 ( 4.0 ~ 11.2 )
4.5 ( 0.6 ~ 5.4 )
5.4 ( 0.6 ~ 6.3 )
6.7 ( 0.6 ~ 7.1 )
8.0 ( 3.6 ~ 9.0 )
11.2 ( 4.0 ~ 12.5 )
1.02 / 1.10
1.52 / 1.46
1.75 / 1.86
2.11 / 2.11
2.55 / 2.68
3.92 / 4.09
3.29 / 3.70
3.20 / 3.60
3.36 / 3.79
3.92 / 4.18
5
5
5
5
5
12
15
15
17
24
60 / 60
60 / 60
60 / 60
60 / 60
64 / 64
63 / 63
63 / 63
64 / 64
66 / 66
70 / 70
38 / 36 / 31
38 / 36 / 31
41 / 37 / 32
41 / 37 / 32
43 / 38 / 34
38 / 36 / 31
38 / 36 / 31
41 / 37 / 32
41 / 37 / 32
43 / 38 / 34
50 / 50
54 / 50
54 / 54
51 / 48
48 / 50
10 / 9 / 7
10 / 9 / 7
16 / 13 / 10
16 / 13 / 10
26 / 21 / 16.5
10 / 9 / 7
10 / 9 / 7
16 / 13 / 10
16 / 13 / 10
26 / 21 / 16.5
36 / 33
40 / 33
41.5 / 39
60 / 50
100 / 100
210 x 1,070 x 690
210 x 1,320 x 690
250 x 1,620 x 690
640 x 800(+71) x 290
750 x 880(+88) x 340
1,300 x 970 x 370
28
33
43
45
60
105
6.35(1/4") / 12.7(1/2")
9.52(3/8") / 15.88(5/8")
Max.30
Max.50
Max.100
Max.20 / Max.20
Max.30 / Max.15
-15~43*3
-15~20
-20~20
Pocket Plastic net x2(Washable)
wired:RC-EX1A, RC-E5, RCH-E3 wireless:RCN-E-E
FDE125VNXVG
FDE140VNXVG
FDE125VG
FDE140VG
FDC125VNX
FDC140VNX
1 Phase 220-240V, 50Hz / 220V, 60Hz
12.5 ( 5.0 ~ 14.0 )
14.0 ( 5.0 ~ 16.0 )
14.0 ( 4.0 ~ 17.0 )
16.0 ( 4.0 ~ 18.0 )
3.50 / 3.77
4.40 / 4.69
3.57 / 3.71
3.18 / 3.41
5
5
26
26
64 / 64
65 / 65
70 / 70
72 / 72
45 / 40 / 35
45 / 40 / 36
45 / 40 / 35
45 / 40 / 36
48 / 50
49 / 52
29 / 23 / 17
29 / 23 / 18
29 / 23 / 17
29 / 23 / 18
100 / 100
100 / 100
FDE125VSXVG
FDE140VSXVG
FDE125VG
FDE140VG
FDC125VSX
FDC140VSX
3 Phase 380-415V, 50Hz / 380V, 60Hz
10.0 ( 4.0 ~ 11.2 )
12.5 ( 5.0 ~ 14.0 )
14.0 ( 5.0 ~ 16.0 )
11.2 ( 4.0 ~ 16.0 )
14.0 ( 4.0 ~ 18.0 )
16.0 ( 4.0 ~ 20.0 )
2.55 / 2.68
3.50 / 3.77
4.40 / 4.69
3.92 / 4.18
3.57 / 3.71
3.18 / 3.41
5
5
5
15
15
15
64 / 64
64 / 64
65 / 65
70 / 70
70 / 70
72 / 72
43 / 38 / 34
45 / 40 / 35
45 / 40 / 36
43 / 38 / 34
45 / 40 / 35
45 / 40 / 36
48 / 50
48 / 50
49 / 52
26 / 21 / 16.5
29 / 23 / 17
29 / 23 / 18
26 / 21 / 16.5
29 / 23 / 17
29 / 23 / 18
100 / 100
100 / 100
100 / 100
250 x 1,620 x 690
1,300 x 970 x 370
43
105
9.52(3/8") / 15.88(5/8")
Max.100
Max.30 / Max.15
-15~43*3
-20~20
Pocket Plastic net x2(Washable)
wired:RC-EX1A, RC-E5, RCH-E3 wireless:RCN-E-E
mm
kg
ømm
m
m
°C
1 Powerful-Hi can be selected.
ound pressure level:
M G d (A)
M G
M G m3 min
Air ow:
M G m3 min
d (A)
N G
N G
m3 min
d (A)
FDE100VSXVG
FDE100VG
FDC100VSX
N( )
G
N( ) G
m3 min
d (A)
N( )
G
N( ) G
m3 min
d (A)
NOTES:
he data are measured under the following conditions( O- ).
Cooling: ndoor temp. of
C
C
and outdoor temp. of
C .
eating: ndoor temp. of
C
and outdoor temp. of C
C
.
ndicates the value in an anechoic cham er. uring operation these values are somewhat higher due to am ient conditions.
*2 :: The
values are for one indoor unit operation.
* : f a cooling
is conducted when the outdoor air temperature is
C or lower the outdoor unit should e installed at a place where it is not in uenced y
* natural wind.operation
f wind lows the low pressure will drop and compressor fre uency will increase this will cause the capacity to drop and may cause the unit to reak
down.
34
SPECIFICATIONS
he values are for simultaneous Multi operation.
FDE71VNXPVG
Set model name
Indoor unit
Outdoor unit
Power source
Nominal cooling capacity (Min~Max)
Nominal heating capacity (Min~Max)
Power consumption Cooling/Heating
EER/COP
Cooling/Heating
Inrush current
Max. current
2
Sound power Indoor* Cooling/Heating
level*1
Outdoor Cooling/Heating
Cooling (Hi/Me/Lo)
Sound
Indoor*2
pressure
Heating (Hi/Me/Lo)
1
level* 2
Outdoor Cooling/Heating
Cooling (Hi/Me/Lo)
Indoor*2
Air flow 2
Heating (Hi/Me/Lo)
Outdoor Cooling/Heating
Indoor
Exterior
HeightxWidthxDepth
dimensions Outdoor
Indoor
Net weight
Outdoor
Ref.piping size Liquid/Gas
Refrigerant line (one way) length
Vertical height differences Outdoor is higher/lower
Cooling
Outdoor operating
temperature range
Heating
Air filter, Q'ty
Remote control (option)
FDE100VNXPVG
FDE125VNXPVG
FDE140VNXPVG
Twin
FDE40VG
FDC71VNX
kW
kW
kW
A
dB(A)
m3/min
mm
kg
ømm
m
m
°C
FDE50VG
FDC100VNX
FDE60VG
FDE71VG
FDC125VNX
FDC140VNX
1 Phase 220-240V, 50Hz / 220V, 60Hz
7.1 ( 3.2 ~ 8.0 )
10.0 ( 4.0 ~ 11.2 )
12.5 ( 5.0 ~ 14.0 )
14.0 ( 5.0 ~ 16.0 )
8.0 ( 3.6 ~ 9.0 )
11.2 ( 4.0 ~ 12.5 )
14.0 ( 4.0 ~ 17.0 )
16.0 ( 4.0 ~ 18.0 )
2.05 / 2.35
3.00 / 3.39
3.97 / 3.70
4.67 / 4.58
3.46 / 3.40
3.33 / 3.30
3.15 / 3.78
3.00 / 3.49
5
5
5
5
17
24
26
26
60 / 60
60 / 60
60 / 60
60 / 60
66 / 66
70 / 70
70 / 70
72 / 72
38 / 36 / 31
38 / 36 / 31
41 / 37 / 32
41 / 37 / 32
38 / 36 / 31
38 / 36 / 31
41 / 37 / 32
41 / 37 / 32
51 / 48
48 / 50
48 / 50
49 / 52
10 / 9 / 7
10 / 9 / 7
16 / 13 / 10
16 / 13 / 10
10 / 9 / 7
10 / 9 / 7
16 / 13 / 10
16 / 13 / 10
60 / 50
100 / 100
100 / 100
100 / 100
210 x 1,070 x 690
210 x 1,320 x 690
750 x 880(+88) x 340
1,300 x 970 x 370
28
33
60
105
9.52(3/8") / 15.88(5/8")
Max. 50
Max. 100
Max.30 / Max.15
-15~43*3
-20~20
Pocket plastic net x 2(Washable)
wired:RC-EX1A, RC-E5, RCH-E3 wireless:RCN-E-E
FDE140VNXTVG
Triple
FDE50VG
FDC140VNX
14.0 ( 5.0 ~ 16.0 )
16.0 ( 4.0 ~ 18.0 )
4.66 / 4.53
3.00 / 3.53
5
26
60 / 60
72 / 72
38 / 36 / 31
38 / 36 / 31
49 / 52
10 / 9 / 7
10 / 9 / 7
100 / 100
210 x 1,070 x 690
28
he values are for simultaneous Multi operation.
FDE100VSXPVG
Set model name
Indoor unit
Outdoor unit
Power source
Nominal cooling capacity (Min~Max)
Nominal heating capacity (Min~Max)
Power consumption Cooling/Heating
EER/COP
Cooling/Heating
Inrush current
Max. current
2
Sound power Indoor* Cooling/Heating
level*1
Outdoor Cooling/Heating
Cooling (Hi/Me/Lo)
Sound
Indoor*2
pressure
Heating (Hi/Me/Lo)
1
level* 2
Outdoor Cooling/Heating
Cooling (Hi/Me/Lo)
Indoor*2
Air flow 2
Heating (Hi/Me/Lo)
Outdoor Cooling/Heating
Indoor
Exterior
HeightxWidthxDepth
dimensions Outdoor
Indoor
Net weight
Outdoor
Ref.piping size Liquid/Gas
Refrigerant line (one way) length
Vertical height differences Outdoor is higher/lower
Cooling
Outdoor operating
temperature range
Heating
Air filter, Q'ty
Remote control (option)
FDE50VG
FDC100VSX
kW
kW
kW
A
dB(A)
m3/min
mm
kg
ømm
m
m
°C
10.0 ( 4.0 ~ 11.2 )
11.2 ( 4.0 ~ 16.0 )
3.00 / 3.39
3.33 / 3.30
5
15
60 / 60
70 / 70
38 / 36 / 31
38 / 36 / 31
48 / 50
10 / 9 / 7
10 / 9 / 7
100 / 100
210 x 1,070 x 690
28
FDE125VSXPVG
FDE140VSXPVG
Twin
FDE60VG
FDE71VG
FDC125VSX
FDC140VSX
3 Phase 380-415V, 50Hz / 380V, 60Hz
12.5 ( 5.0 ~ 14.0 )
14.0 ( 5.0 ~ 16.0 )
14.0 ( 4.0 ~ 18.0 )
16.0 ( 4.0 ~ 20.0 )
3.97 / 3.70
4.67 / 4.58
3.15 / 3.78
3.00 / 3.49
5
5
15
15
60 / 60
60 / 60
70 / 70
72 / 72
41 / 37 / 32
41 / 37 / 32
41 / 37 / 32
41 / 37 / 32
48 / 50
49 / 52
16 / 13 / 10
16 / 13 / 10
16 / 13 / 10
16 / 13 / 10
100 / 100
100 / 100
210 x 1,320 x 690
1,300 x 970 x 370
33
105
9.52(3/8") / 15.88(5/8")
Max.100
Max.30 / Max.15
-15~43*3
-20~20
Pocket plastic net x 2(Washable)
wired:RC-EX1A, RC-E5, RCH-E3 wireless:RCN-E-E
FDE140VSXTVG
Triple
FDE50VG
FDC140VSX
14.0 ( 5.0 ~ 16.0 )
16.0 ( 4.0 ~ 20.0 )
4.66 / 4.53
3.00 / 3.53
5
15
60 / 60
72 / 72
38 / 36 / 31
38 / 36 / 31
49 / 52
10 / 9 / 7
10 / 9 / 7
100 / 100
210 x 1,070 x 690
28
2 Powerful-Hi can be selected.
Sound pressure level: 71/100VN(S)XPVG 46dB(A), 125/140VN(S)XPVG 47dB(A), 140VNXTVG 46dB(A)
N( ) P G m3 min
N
G m3 min
Air ow:
N( ) P G m3 min
35
SPECIFICATIONS
Set model name
Indoor unit
Outdoor unit
Power source
Nominal cooling capacity (Min~Max)
Nominal heating capacity (Min~Max)
Power consumption Cooling/Heating
EER/COP
Cooling/Heating
Inrush current
Max. current
Sound power Indoor Cooling/Heating
level*1
Outdoor Cooling/Heating
Cooling (Hi/Me/Lo)
Sound
Indoor
pressure
Heating (Hi/Me/Lo)
level*1 1
Outdoor Cooling/Heating
Cooling (Hi/Me/Lo)
Indoor
Air flow 1
Heating (Hi/Me/Lo)
Outdoor Cooling/Heating
Indoor
Exterior
HeightxWidthxDepth
dimensions Outdoor
Indoor
Net weight
Outdoor
Ref.piping size Liquid/Gas
Refrigerant line (one way) length
Vertical height differences Outdoor is higher/lower
Cooling
Outdoor operating
temperature range
Heating
Air filter, Q'ty
Remote control (option)
kW
kW
kW
A
dB(A)
m3/min
mm
kg
ømm
m
m
°C
FDE100VNVG
FDE125VNVG
FDE140VNVG
FDE100VSVG
FDE125VSVG
FDE140VSVG
FDE100VG
FDE125VG
FDE140VG
FDE100VG
FDE125VG
FDE140VG
FDC100VN
FDC125VN
FDC140VN
FDC100VS
FDC125VS
FDC140VS
1 Phase 220-240V, 50Hz / 220V, 60Hz
3 Phase 380-415V, 50Hz / 380V, 60Hz
10.0 ( 4.0 ~ 11.2 )
12.5 ( 5.0 ~ 14.0 )
14.0 ( 5.0 ~ 14.5 )
10.0 ( 4.0 ~ 11.2 )
12.5 ( 5.0 ~ 14.0 )
14.0 ( 5.0 ~ 14.5 )
11.2 ( 4.0 ~ 12.5 )
14.0 ( 4.0 ~ 16.0 )
16.0 ( 4.0 ~ 16.5 )
11.2 ( 4.0 ~ 12.5 )
14.0 ( 4.0 ~ 16.0 )
16.0 ( 4.0 ~ 16.5 )
2.85 / 2.90
4.45 / 4.08
5.80 / 4.92
2.85 / 2.90
4.45 / 4.08
5.80 / 4.92
3.51 / 3.86
2.81 / 3.43
2.41 / 3.25
3.51 / 3.86
2.81 / 3.43
2.41 / 3.25
5
5
5
5
5
5
24
24
24
15
15
15
64 / 64
64 / 64
65 / 65
64 / 64
64 / 64
65 / 65
70 / 70
72 / 72
73 / 73
70 / 70
72 / 72
73 / 73
43 / 38 / 34
45 / 40 / 35
45 / 40 / 36
43 / 38 / 34
45 / 40 / 35
45 / 40 / 36
43 / 38 / 34
45 / 40 / 35
45 / 40 / 36
43 / 38 / 34
45 / 40 / 35
45 / 40 / 36
49 / 49
50 / 51
51 / 51
49 / 49
50 / 51
51 / 51
26 / 21 / 16.5
29 / 23 / 17
29 / 23 / 18
26 / 21 / 16.5
29 / 23 / 17
29 / 23 / 18
26 / 21 / 16.5
29 / 23 / 17
29 / 23 / 18
26 / 21 / 16.5
29 / 23 / 17
29 / 23 / 18
75 / 73
75 / 73
75 / 73
75 / 73
75 / 73
75 / 73
250 x 1,620 x 690
845 x 970 x 370
43
81
83
9.52(3/8") / 15.88(5/8")
Max.50
Max.30 / Max.15
-15~43*3
-20~20
Pocket Plastic net x2(Washable)
wired:RC-EX1A, RC-E5, RCH-E3 wireless:RCN-E-E
he values are for simultaneous Multi operation.
FDE100VNPVG
Set model name
Indoor unit
Outdoor unit
Power source
Nominal cooling capacity (Min~Max)
Nominal heating capacity (Min~Max)
Power consumption Cooling/Heating
EER/COP
Cooling/Heating
Inrush current
Max. current
2
Sound power Indoor* Cooling/Heating
level*1
Outdoor Cooling/Heating
Cooling (Hi/Me/Lo)
Sound
Indoor*2
pressure
Heating (Hi/Me/Lo)
level*1 1
Outdoor Cooling/Heating
Cooling (Hi/Me/Lo)
Indoor*2
Air flow 1
Heating (Hi/Me/Lo)
Outdoor Cooling/Heating
Indoor
Exterior
HeightxWidthxDepth
dimensions Outdoor
Indoor
Net weight
Outdoor
Ref.piping size Liquid/Gas
Refrigerant line (one way) length
Vertical height differences Outdoor is higher/lower
Cooling
Outdoor operating
temperature range
Heating
Air filter, Q'ty
Remote control (option)
FDE50VG
FDC100VN
kW
kW
kW
A
dB(A)
m3/min
mm
kg
10.0 ( 4.0 ~ 11.2 )
11.2 ( 4.0 ~ 12.5 )
3.12 / 3.49
3.21 / 3.21
5
24
60 / 60
70 / 70
38 / 36 / 31
38 / 36 / 31
49 / 49
10 / 9 / 7
10 / 9 / 7
75 / 73
210 x 1,070 x 690
28
ømm
m
m
°C
1 Powerful-Hi can be selected.
ound pressure level:
N( ) G
Air ow:
N( ) G m3 min
d (A)
N( ) G
N( ) G
m3 min
FDE125VNPVG
FDE140VNPVG
FDE140VNTVG
FDE100VSPVG
FDE125VSPVG
Twin
Triple
Twin
FDE60VG
FDE71VG
FDE50VG
FDE50VG
FDE60VG
FDC125VN
FDC140VN
FDC140VN
FDC100VS
FDC125VS
1 Phase 220-240V, 50Hz / 220V, 60Hz
3 Phase 380-415V, 50Hz / 380V, 60Hz
12.5 ( 5.0 ~ 14.0 )
14.0 ( 5.0 ~ 14.5 )
14.0 ( 5.0 ~ 14.5 )
10.0 ( 4.0 ~ 11.2 )
12.5 ( 5.0 ~ 14.0 )
14.0 ( 4.0 ~ 16.0 )
16.0 ( 4.0 ~ 16.5 )
16.0 ( 4.0 ~ 16.5 )
11.2 ( 4.0 ~ 12.5 )
14.0 ( 4.0 ~ 16.0 )
4.16 / 3.80
4.87 / 4.59
4.88 / 4.57
3.12 / 3.49
4.16 / 3.80
3.00 / 3.68
2.87 / 3.49
2.87 / 3.50
3.21 / 3.21
3.00 / 3.68
5
5
5
5
5
24
24
24
15
15
60 / 60
60 / 60
60 / 60
60 / 60
60 / 60
72 / 72
73 / 73
73 / 73
70 / 70
72 / 72
41 / 37 / 32
41 / 37 / 32
38 / 36 / 31
38 / 36 / 31
41 / 37 / 32
41 / 37 / 32
41 / 37 / 32
38 / 36 / 31
38 / 36 / 31
41 / 37 / 32
50 / 51
51 / 51
51 / 51
49 / 49
50 / 51
16 / 13 / 10
16 / 13 / 10
10 / 9 / 7
10 / 9 / 7
16 / 13 / 10
16 / 13 / 10
16 / 13 / 10
10 / 9 / 7
10 / 9 / 7
16 / 13 / 10
75 / 73
75 / 73
75 / 73
75 / 73
75 / 73
210 x 1,320 x 690
210 x 1,070 x 690
210 x 1,320 x 690
845 x 970 x 370
33
28
33
81
83
9.52(3/8") / 15.88(5/8")
Max. 50
Max.30 / Max.15
-15~43*3
-20~20
Pocket plastic net x 2(Washable)
wired:RC-EX1A, RC-E5, RCH-E3 wireless:RCN-E-E
d (A)
N( )P G d (A)
N( )P G d (A)
NP G d (A)
N( )P G m3 min
N( )P G m3 min
NP G m3 min
N
N G d (A)
G m3 min
NOTES:
he data are measured under the following conditions( O- ).
Cooling: ndoor temp. of
C
C
and outdoor temp. of
C .
eating: ndoor temp. of
C
and outdoor temp. of C
C
.
ndicates the value in an anechoic cham er. uring operation these values are somewhat higher due to am ient conditions.
*2 :: The
values are for one indoor unit operation.
* : f a cooling
is conducted when the outdoor air temperature is
C or lower the outdoor unit should e installed at a place where it is not in uenced y
* natural wind.operation
f wind lows the low pressure will drop and compressor fre uency will increase this will cause the capacity to drop and may cause the unit to reak
down.
36
SPECIFICATIONS
he values are for simultaneous Multi operation.
FDE140VSPVG
Set model name
Indoor unit
Outdoor unit
Power source
Nominal cooling capacity (Min~Max)
Nominal heating capacity (Min~Max)
Power consumption Cooling/Heating
EER/COP
Cooling/Heating
Inrush current
Max. current
2
Sound power Indoor* Cooling/Heating
level*1
Outdoor Cooling/Heating
Cooling (Hi/Me/Lo)
Sound
Indoor*2
pressure
Heating (Hi/Me/Lo)
level*1 2
Outdoor Cooling/Heating
Cooling (Hi/Me/Lo)
Indoor*2
Air flow 2
Heating (Hi/Me/Lo)
Outdoor Cooling/Heating
Indoor
Exterior
HeightxWidthxDepth
dimensions Outdoor
Indoor
Net weight
Outdoor
Ref.piping size Liquid/Gas
Refrigerant line (one way) length
Vertical height differences Outdoor is higher/lower
Cooling
Outdoor operating
temperature range
Heating
Air filter, Q'ty
Remote control (option)
FDE71VG
FDC140VS
kW
kW
kW
14.0 ( 5.0 ~ 14.5 )
16.0 ( 4.0 ~ 16.5 )
4.87 / 4.59
2.87 / 3.49
5
A
15
60 / 60
73 / 73
dB(A)
41 / 37 / 32
41 / 37 / 32
51 / 51
16 / 13 / 10
m3/min
16 / 13 / 10
75 / 73
210 x 1,320 x 690
mm
845 x 970 x 370
33
kg
83
ømm 9.52(3/8") / 15.88(5/8")
m
Max.50
m
-15~43*3
°C
-20~20
FDE200VSAPVG
FDE250VSAPVG
FDE140VSTVG
FDE200VSATVG
Twin
Triple
FDE100VG
FDE125VG
FDE50VG
FDE71VG
FDC200VSA
FDC250VSA
FDC140VS
FDC200VSA
3 Phase 380-415V, 50Hz / 380V, 60Hz
19.0 ( 5.2 ~ 22.4)
24.0 ( 6.9 ~ 28.0 )
14.0 ( 5.0 ~ 14.5 )
19.0 ( 5.2 ~ 22.4 )
22.4 ( 3.3 ~ 25.0 )
27.0 ( 5.5 ~ 31.5 )
16.0 ( 4.0 ~ 16.5 )
22.4 ( 3.3 ~ 25.0 )
6.34 / 6.10
8.52 / 7.54
4.88 / 4.57
6.33 / 5.94
3.00 / 3.67
2.82 / 3.58
2.87 / 3.50
3.00 / 3.77
5
5
5
5
20
21
15
20
64 / 64
64 / 64
60 / 60
60 / 60
72 / 74
73 / 75
73 / 73
72 / 74
43 / 38 / 44
45 / 40 / 35
38 / 36 / 31
41 / 37 / 32
43 / 38 / 44
45 / 40 / 35
38 / 36 / 31
41 / 37 / 32
58 / 59
59 / 62
51 / 51
58 / 59
26 / 21 / 16.5
29 / 23 / 17
10 / 9 / 7
16 / 13 / 10
26 / 21 / 16.5
29 / 23 / 17
10 / 9 / 7
16 / 13 / 10
135 / 135
143 / 151
75 / 73
135 / 135
250 x 1,620 x 690
210 x 1,070 x 690
210 x 1,320 x 690
1,300 x 970 x 370
1,505 x 970 x 370
845 x 970 x 370
1,300 x 970 x 370
43
28
33
115
143
83
115
9.52(3/8") / 22.22(7/8") 12.7(1/2") / 22.22(7/8") 9.52(3/8") / 15.88(5/8") 9.52(3/8") / 22.22(7/8")
Max.70
Max.50
Max.70
Max.30 / Max.15
-15~50*3
-15~43*3
-15~50*3
-15~20
-20~20
-15~20
Pocket plastic net x 2(Washable)
wired:RC-EX1A, RC-E5, RCH-E3 wireless:RCN-E-E
he values are for simultaneous Multi operation.(e cept tandard nverter)
Standard Inverter
FDE200VSADVG
FDE250VSADVG
Set model name
Double Twin
Indoor unit
FDE50VG
FDE60VG
Outdoor unit
FDC200VSA
FDC250VSA
Power source
3 Phase 380-415V, 50Hz / 380V, 60Hz
Nominal cooling capacity (Min~Max)
kW
19.0 ( 5.2 ~ 22.4 )
24.0 ( 6.9 ~ 28.0 )
Nominal heating capacity (Min~Max)
kW
22.4 ( 3.3 ~ 25.0 )
27.0 ( 5.5 ~ 31.5 )
Power consumption Cooling/Heating
kW
6.90 / 7.10
8.00 / 7.02
EER/COP
Cooling/Heating
2.75 / 3.15
3.00 / 3.85
Inrush current
5
5
A
Max. current
20
21
2
60 / 60
60 / 60
Sound power Indoor* Cooling/Heating
1
level*
Outdoor Cooling/Heating
72 / 74
73 / 75
Cooling (Hi/Me/Lo) dB(A)
38 / 36 / 31
41 / 37 / 32
Sound
Indoor*2
pressure
Heating (Hi/Me/Lo)
38 / 36 / 31
41 / 37 / 32
level*1 2
Outdoor Cooling/Heating
58 / 59
59 / 62
10 / 9 / 7
16 / 13 / 10
2 Cooling (Hi/Me/Lo)
Indoor*
Air flow 2
Heating (Hi/Me/Lo) m3/min
10 / 9 / 7
16 / 13 / 10
Outdoor Cooling/Heating
135 / 135
143 / 151
Indoor
210 x 1,070 x 690
210 x 1,320 x 690
Exterior
HeightxWidthxDepth mm
dimensions Outdoor
1,300 x 970 x 370
1,505 x 970 x 370
Indoor
28
33
Net weight
kg
Outdoor
115
143
Ref.piping size Liquid/Gas
ømm 9.52(3/8") / 22.22(7/8") 12.7(1/2") / 22.22(7/8")
Refrigerant line (one way) length
m
Max.70
Vertical height differences Outdoor is higher/lower m
Max.30 / Max.15
Cooling
-15~50*3
Outdoor operating
°C
temperature range
Heating
-15~20
Air filter, Q'ty
Pocket plastic net x 2(Washable)
Remote control (option)
wired:RC-EX1A, RC-E5, RCH-E3 wireless:RCN-E-E
2 Powerful-Hi can be selected.
ound pressure level:
P G d (A)
AP G d (A)
NP G d (A)
NP G d (A)
NP G d (A)
3
3
AP G m min
G
Air ow:
P G m min
NP G m3 min
NP G m3 min
NP G m3 min
G
3
m min
FDE71VNPVG
FDE90VNPVG
FDE100VNP1VG
FDE71VG
FDC71VNP
FDE100VG
FDE100VG
FDC90VNP
FDC100VNP
1 Phase 220-240V, 50Hz / 220V, 60Hz
7.1 ( 1.4 ~ 7.1 )
9.0 ( 1.9 ~ 9.0 )
10.0 ( 2.8 ~ 11.2 )
7.1 ( 1.0 ~ 7.1 )
9.0 ( 1.5 ~ 9.0 )
11.2 ( 2.5 ~ 12.5 )
2.50 / 1.96
2.75 / 2.22
2.66 / 2.94
2.84 / 3.62
3.27 / 4.05
3.76 / 3.81
5
5
5
14.5
18.0
21.0
60 / 60
64 / 64
64 / 64
67 / 67
69 / 69
70 / 70
41 / 37 / 32
43 / 38 / 34
43 / 38 / 34
41 / 37 / 32
43 / 38 / 34
43 / 38 / 34
54 / 54
57 / 55
57 / 61
16 / 13 / 10
26 / 21 / 16.5
26 / 21 / 16.5
16 / 13 / 10
26 / 21 / 16.5
26 / 21 / 16.5
36 / 36
63 / 49.5
75 / 79
210 x 1,320 x 690
250 x 1,620 x 690
640 x 800(+71) x 290
750 x 880(+88) x 340
845 x 970 x 370
33
43
45
57
70
6.35(1/4") / 12.7(1/2")
6.35(1/4") / 15.88(5/8") 9.52(3/8") / 15.88(5/8")
Max.30
Max.20 / Max.20
-15~46*3
-15~20
Pocket Plastic net x2(Washable)
wired:RC-EX1A, RC-E5, RCH-E3 wireless:RCN-E-E
d (A)
A
A
G
3
G
m min
d (A)
A
A
G
3
G
m min
d (A)
A
A
G
G
d (A)
3
m min
37
WALL MOUNTED
SRK
R410A
Only used with Single case.
SRK 71
NEW
Common to the both case of Single / Multi
SRK 100
1 Jet Air Scroll
Point
We used the same aerodynamic
analysis technology as used in
developing jet engines.
CFD (computational fluid dynamics),
used in blade shape design of jet
engines, has been applied to the design
of air channels in air conditioners to
develop the ideal air channel system (air
circulation). The airflow of the jets
created in this system enable a large
volume of air to be blown with minimum
power consumption, yet the air flow is
uniform, quiet and reaches points a long
distance from the blower.
Only used with Multi System.
SRK 50•60
(C)Mitsubishi Aircraft Corporation
Wired remote control (Option)
RC-EX1A
RC-E5
RCH-E3
Fast
Slow
Colors in the figure show the air speed.
2 Long Reach Air Flow
Point
Max three indoor units are connectable.
Powerful airflow is realized by Jet technology.
Good for large living rooms and shops. Increase your comfort.
SC-BIKN-E
SRK50/60ZMX
(in cooling operation)
RC-EX1A
RC-E5
15m
38
38
17m
SRK100ZR
(in cooling operation)
SC-BIKN-E
OUTDOOR UNIT
Standard Inverter
Micro Inverter
FDC
100~125VN(S)X
100~140VN(S)
Chargeless
30m
Height x Width x Depth (mm) 1,300 x 970 x 370
30m
845 x 970 x 370
71VNP
100VNP
model
15m
640 x 800(+71) x 290 845 x 970 x 370
DIMENSIONS (Unit:mm)
SRK50ZMX-S, 60ZMX-S
SRK71ZM-S
881.9
61.5
21
46.5
61.5
60
60
46.5
26
Outlet for wiring
220
3
309
(right, left)61.5
890
Outlet for piping
122.1
9
3.1
Terminal block
Piping hole
right
SRK100ZR-S
Outlet for piping
Outlet for piping
Outlet for piping
Outlet for wiring
SPECIFICATIONS
he values are for simultaneous Multi operation.
SRK100VNXPZMX
SRK125VNXPZMX
SRK140VNXTZMX
SRK100VSXPZMX
SRK125VSXPZMX
SRK140VSXTZMX
Twin
Triple
Twin
Triple
Indoor unit
SRK50ZMX-S
SRK60ZMX-S
SRK50ZMX-S
SRK50ZMX-S
SRK60ZMX-S
SRK50ZMX-S
Outdoor unit
FDC100VNX
FDC125VNX
FDC140VNX
FDC100VSX
FDC125VSX
FDC140VSX
Power source
1 Phase 220-240V, 50Hz / 220V, 60Hz
3 Phase 380-415V, 50Hz / 380V, 60Hz
Nominal cooling capacity (Min~Max)
kW
10.0 ( 4.0 ~ 11.2 )
12.5 ( 5.0 ~ 14.0 )
14.0 ( 5.0 ~ 16.0 )
10.0 ( 4.0 ~ 11.2 )
12.5 ( 5.0 ~ 14.0 )
14.0 ( 5.0 ~ 16.0)
Nominal heating capacity (Min~Max)
kW
11.2 ( 4.0 ~ 12.5 )
14.0 ( 4.0 ~ 17.0 )
16.0 ( 4.0 ~ 18.0 )
11.2 ( 4.0 ~ 16.0 )
14.0 ( 4.0 ~ 18.0 )
16.0 ( 4.0 ~ 20.0 )
Power consumption Cooling/Heating
kW
2.66 / 2.60
3.60 / 3.48
3.98 / 3.68
2.66 / 2.60
3.60 / 3.48
3.98 / 3.68
EER/COP
Cooling/Heating
3.76 / 4.31
3.47 / 4.02
3.52 / 4.35
3.76 / 4.31
3.47 / 4.02
3.52 / 4.35
Inrush current
5
5
5
5
5
5
A
Max. current
24
26
26
15
15
15
2
60 / 64
64 / 64
60 / 64
60 / 64
64 / 64
60 / 64
Sound power Indoor* Cooling/Heating
level*1
Outdoor Cooling/Heating
70 / 70
70 / 70
72 / 72
70 / 70
70 / 70
72 / 72
47 / 40 / 27 / 25
51 / 41 / 29 / 25
47 / 40 / 27 / 25
47 / 40 / 27 / 25
51 / 41 / 29 / 25
47 / 40 / 27 / 25
Sound
2 Cooling (Hi/Me/Lo/Ulo) dB(A)
Indoor*
pressure
Heating (Hi/Me/Lo/Ulo)
48 / 40 / 33 / 26
48 / 41 / 34 / 27
48 / 40 / 33 / 26
48 / 40 / 33 / 26
48 / 41 / 34 / 27
48 / 40 / 33 / 26
level*1
Outdoor Cooling/Heating
48 / 50
48 / 50
49 / 52
48 / 50
48 / 50
49 / 52
13.5 / 11 / 8 / 7
14.5 / 12.5 / 8.5 / 7
13.5 / 11 / 8 / 7
13.5 / 11 / 8 / 7
14.5 / 12.5 / 8.5 / 7
13.5 / 11 / 8 / 7
2 Cooling (Hi/Me/Lo/Ulo)
Indoor*
Air flow
Heating (Hi/Me/Lo/Ulo) m3/min 17 / 14.5 / 10.5 / 8 17.5 / 15 / 11 / 8.5 17 / 14.5 / 10.5 / 8 17 / 14.5 / 10.5 / 8 17.5 / 15 / 11 / 8.5 17 / 14.5 / 10.5 / 8
Outdoor Cooling/Heating
100 / 100
100 / 100
100 / 100
100 / 100
100 / 100
100 / 100
Indoor
309 x 890 x 220
Exterior
HeightxWidthxDepth mm
dimensions Outdoor
1,300 x 970 x 370
Indoor
15
Net weight
kg
Outdoor
105
Ref.piping size Liquid/Gas
ømm
9.52(3/8") / 15.88(5/8")
Refrigerant line (one way) length
m
Max.100
Vertical height differences Outdoor is higher/lower m
Max.30 / Max.15
Cooling
-15~43*3
Outdoor operating
°C
temperature range
Heating
-20~20
Air filter, Q'ty
Polypropylene net x 2(washable)
Remote control (option)
wired:RC-EX1A, RC-E5, RCH-E3 & Interface kit:SC-BIKN-E
Set model name
NOTES:
he data are measured under the following conditions( O- ).
Cooling: ndoor temp. of
C
C
and outdoor temp. of
C .
eating: ndoor temp. of
C
and outdoor temp. of C
C
.
ndicates the value in an anechoic cham er. uring operation these values are somewhat higher due to am ient conditions.
*2 :: The
values are for one indoor unit operation.
* : f a cooling
is conducted when the outdoor air temperature is
C or lower the outdoor unit should e installed at a place where it is not in uenced y natural
* wind. f windoperation
lows the low pressure will drop and compressor fre uency will increase this will cause the capacity to drop and may cause the unit to reak down.
39
39
SPECIFICATIONS
he values are for simultaneous Multi operation.
SRK100VNPZMX
SRK140VNTZMX
SRK100VSPZMX
SRK125VSPZMX
SRK140VSTZMX
Triple
Twin
Triple
Indoor unit
SRK50ZMX-S
SRK60ZMX-S
SRK50ZMX-S
SRK50ZMX-S
SRK60ZMX-S
SRK50ZMX-S
Outdoor unit
FDC100VN
FDC125VN
FDC140VN
FDC100VS
FDC125VS
FDC140VS
Power source
1 Phase 220-240V, 50Hz / 220V, 60Hz
3 Phase 380-415V, 50Hz / 380V, 60Hz
Nominal cooling capacity (Min~Max)
kW
10.0 ( 4.0 ~ 11.2 )
12.5 ( 5.0 ~ 14.0 )
14.0 ( 5.0 ~ 14.5 )
10.0 ( 4.0 ~ 11.2 )
12.5 ( 5.0 ~ 14.0 )
14.0 ( 5.0 ~ 14.5)
Nominal heating capacity (Min~Max)
kW
11.2 ( 4.0 ~ 12.5 )
14.0 ( 4.0 ~ 16.0 )
16.0 ( 4.0 ~ 16.5 )
11.2 ( 4.0 ~ 12.5 )
14.0 ( 4.0 ~ 16.0 )
16.0 ( 4.0 ~ 16.5 )
Power consumption Cooling/Heating
kW
2.72 / 2.86
4.25 / 4.29
4.53 / 4.05
2.72 / 2.86
4.25 / 4.29
4.53 / 4.05
EER/COP
Cooling/Heating
3.68 / 3.92
2.94 / 3.26
3.09 / 3.95
3.68 / 3.92
2.94 / 3.26
3.09 / 3.95
Inrush current
5
5
5
5
5
5
A
Max. current
24
24
24
15
15
15
2
60 / 64
64 / 64
60 / 64
60 / 64
64 / 64
60 / 64
Sound power Indoor* Cooling/Heating
level*1
Outdoor Cooling/Heating
70 / 70
72 / 72
73 / 73
70 / 70
72 / 72
73 / 73
47 / 40 / 27 / 25
51 / 41 / 29 / 25
47 / 40 / 27 / 25
47 / 40 / 27 / 25
51 / 41 / 29 / 25
47 / 40 / 27 / 25
Sound
2 Cooling (Hi/Me/Lo/Ulo) dB(A)
Indoor*
pressure
Heating (Hi/Me/Lo/Ulo)
48 / 40 / 33 / 26
48 / 41 / 34 / 27
48 / 40 / 33 / 26
48 / 40 / 33 / 26
48 / 41 / 34 / 27
48 / 40 / 33 / 26
level*1
Outdoor Cooling/Heating
49 / 49
50 / 51
51 / 51
49 / 49
50 / 51
51 / 51
13.5 / 11 / 8 / 7
14.5 / 12.5 / 8.5 / 7
13.5 / 11 / 8 / 7
13.5 / 11 / 8 / 7
14.5 / 12.5 / 8.5 / 7
13.5 / 11 / 8 / 7
2 Cooling (Hi/Me/Lo/Ulo)
Indoor*
Air flow
Heating (Hi/Me/Lo/Ulo) m3/min 17 / 14.5 / 10.5 / 8 17.5 / 15 / 11 / 8.5 17 / 14.5 / 10.5 / 8 17 / 14.5 / 10.5 / 8 17.5 / 15 / 11 / 8.5 17 / 14.5 / 10.5 / 8
Outdoor Cooling/Heating
75 / 73
75 / 73
75 / 73
75 / 73
75 / 73
75 / 73
Indoor
309 x 890 x 220
Exterior
HeightxWidthxDepth mm
dimensions Outdoor
845 x 970 x 370
Indoor
15
Net weight
kg
Outdoor
81
83
Ref.piping size Liquid/Gas
ømm
9.52(3/8") / 15.88(5/8")
Refrigerant line (one way) length
m
Max. 50
Vertical height differences Outdoor is higher/lower m
Max.30 / Max.15
Cooling
-15~43*3
Outdoor operating
°C
temperature range
Heating
-20~20
Air filter, Q'ty
Polypropylene net x 2(washable)
Remote control (option)
wired:RC-EX1A, RC-E5, RCH-E3 & Interface kit:SC-BIKN-E
Set model name
SRK125VNPZMX
Twin
he values are for simultaneous Multi operation.(e cept ingle case)
Standard Inverter
Set model name
Indoor unit
Outdoor unit
Power source
Nominal cooling capacity (Min~Max)
Nominal heating capacity (Min~Max)
Power consumption Cooling/Heating
EER/COP
Cooling/Heating
Inrush current
Max. current
2
Sound power Indoor* Cooling/Heating
level*1
Outdoor Cooling/Heating
Cooling (Hi/Me/Lo/Ulo)
Sound
Indoor*2
pressure
Heating (Hi/Me/Lo/Ulo)
level*1
Outdoor Cooling/Heating
Cooling (Hi/Me/Lo/Ulo)
Indoor*2
Air flow
Heating (Hi/Me/Lo/Ulo)
Outdoor Cooling/Heating
Indoor
Exterior
HeightxWidthxDepth
dimensions Outdoor
Indoor
Net weight
Outdoor
Ref.piping size Liquid/Gas
Refrigerant line (one way) length
Vertical height differences Outdoor is higher/lower
Cooling
Outdoor operating
temperature range
Heating
Air filter, Q'ty
Remote control (option)
SRK200VSAPZR
Twin
SRK71ZM-S
SRK100ZR-S
SRK100ZR-S
FDC71VNP
FDC100VNP
FDC200VSA
1 Phase 220-240V, 50Hz / 220V, 60Hz
3 Phase 380-415V, 50Hz / 380V, 60Hz
7.1 ( 1.4 ~ 7.1 )
10.0 ( 2.4 ~ 10.5 )
19.0 ( 5.2 ~ 22.4 )
7.1 ( 1.0 ~ 7.1 )
11.2 ( 3.2 ~ 11.5 )
22.4 ( 3.3 ~ 25.0 )
2.36 / 1.88
3.09 / 3.28
7.52 / 7.41
3.01 / 3.78
3.24 / 3.41
2.53 / 3.02
5
14.4
5
14.5
21
20
60 / 61
63 / 63
63 / 63
67 / 67
70 / 74
72 / 74
49 / 45 / 39 / 26
48 / 45 / 40 / 27
48 / 45 / 40 / 27
46 / 43 / 38 / 35
48 / 43 / 38 / 30
48 / 43 / 38 / 30
54 / 54
57 / 61
58 / 59
17.5 / 14 / 8
24.5 / 21.3 / 17.6
24.5 / 21.3 / 17.6 / 10.4
19.5 / 15.5 / 14
27.5 / 23.2 / 19.1
27.5 / 23.2 / 19.1 / 13.6
36 / 36
75 / 80
135 / 135
318 x 1,098 x 248
339 x 1,197 x 262
640 x 800(+71) x 290
845 x 970 x 370
1,300 x 970 x 370
16
16.5
45
70
115
6.35(1/4") / 12.7(1/2")
9.52(3/8") / 15.88(5/8")
9.52(3/8") / 22.22(7/8")
Max.30
Max.70
Max.20 / Max.20
Max.30 / Max.15
-15~50*3
-15~46*3
-15~20
Polypropylene net x2 (Washable)
wired:RC-EX1A, RC-E5, RCH-E3 & Interface kit:SC-BIKN-E
SRK71VNPZM
kW
kW
kW
A
dB(A)
m3/min
mm
kg
ømm
m
m
°C
SRK100VNP1ZR
NOTES:
he data are measured under the following conditions ( O- ).
Cooling: ndoor temp. of
C
C
and outdoor temp. of
C . eating: ndoor temp. of
C
and outdoor temp. of C
C
.
the value in an anechoic cham er. uring operation these values are somewhat higher due to am ient conditions.
* :: ndicates
values are for one indoor unit operation. (Multi system only)
* : f he
a cooling operation is conducted when the outdoor air temperature is
C or lower the outdoor unit should e installed at a place where it is not in uenced y
* natural
wind. f wind lows the low pressure will drop and compressor fre uency will increase this will cause the capacity to drop and may cause the unit to reak
down.
40
FLOOR STANDING
FDF
R410A
Wireless remote control (Option)
RCN-KIT3-E
FDF 71/100/125/140
1 Wide and powerful air flow
Point
Wide and powerful air flow increase your comfort, realizing high
efficiency in combination with our highly advanced outdoor units.
2 Easy Transportation and Installation workability
Point
Piping and drain hose connection can be selected out of 4-directions
and the selection makes installation workability more effective.
Due to slim design (Depth: 320mm), easy transportation and
installation are realized.
Easy Maintenance
The surface of heat exchanger can be appeared only removing the
front panel. Easy cleaning of heat exchanger is possible.
OUTDOOR UNIT
Micro Inverter
100~140VN(S)X
100~140VN(S)
Chargeless
15m
30m
Height x Width x Depth (mm) 750 x 880(+71) x 340 1,300 x 970 x 370
845 x 970 x 370
FDC
71VNX
200VSA
250VSA
model
30m
1,300 x 970 x 370 1,505 x 970 x 370
Standard Inverter
FDC
71VNP
90VNP
100VNP
model
Chargeless
8m
Height x Width x Depth (mm) 640 x 800(+71) x 290 750 x 880(+88) x 340
15m
845 x 970 x 370
41
DIMENSIONS(Unit:mm)
View A
SPECIFICATIONS
Set model name
Indoor unit
Outdoor unit
Power source
Nominal cooling capacity (Min~Max)
Nominal heating capacity (Min~Max)
Power consumption Cooling/Heating
EER/COP
Cooling/Heating
Inrush current
Max. current
Sound power Indoor Cooling/Heating
level*1
Outdoor Cooling/Heating
Cooling (Hi/Me/Lo)
Sound
Indoor
pressure
Heating (Hi/Me/Lo)
level*1 1
Outdoor Cooling/Heating
Cooling (Hi/Me/Lo)
Indoor
Air flow 1
Heating (Hi/Me/Lo)
Outdoor Cooling/Heating
Indoor
Exterior
HeightxWidthxDepth
dimensions Outdoor
Indoor
Net weight
Outdoor
Ref.piping size Liquid/Gas
Refrigerant line (one way) length
Vertical height differences Outdoor is higher/lower
Cooling
Outdoor operating
temperature range
Heating
Air filter, Q'ty
Remote control
1 Powerful-Hi can be selected.
ound pressure level:
N
Air ow:
N
m3 min
FDF71VNXVD1
FDF71VD1
FDC71VNX
kW
kW
kW
A
dB(A)
m3/min
mm
kg
ømm
m
m
°C
FDF100VNXVD2
FDF125VNXVD
FDF140VNXVD
FDF100VSXVD2
FDF125VSXVD
FDF140VSXVD
FDF100VD2
FDF125VD
FDF140VD
FDF100VD2
FDF125VD
FDF140VD
FDC100VNX
FDC125VNX
FDC140VNX
FDC100VSX
FDC125VSX
FDC140VSX
1 Phase 220-240V, 50Hz / 220V, 60Hz
3 Phase 380-415V, 50Hz / 380V, 60Hz
7.1 ( 3.2 ~ 8.0 ) 10.0 ( 4.0 ~ 11.2 ) 12.5 ( 5.0 ~ 14.0 ) 14.0 ( 5.0 ~ 16.0 ) 10.0 ( 4.0 ~ 11.2 ) 12.5 ( 5.0 ~ 14.0 ) 14.0 ( 5.0 ~ 16.0 )
8.0 ( 3.6 ~ 9.0 ) 11.2 ( 4.0 ~ 12.5 ) 14.0 ( 4.0 ~ 17.0 ) 16.0 ( 4.0 ~ 18.0 ) 11.2 ( 4.0 ~ 16.0 ) 14.0 ( 4.0 ~ 18.0 ) 16.0 ( 4.0 ~ 20.0 )
2.21 / 2.21
2.83 / 3.04
3.89 / 3.88
4.65 / 4.69
2.83 / 3.04
3.89 / 3.88
4.65 / 4.69
3.21 / 3.62
3.53 / 3.68
3.21 / 3.61
3.01 / 3.41
3.53 / 3.68
3.21 / 3.61
3.01 / 3.41
5
5
5
5
5
5
5
17
24
26
26
15
15
15
61 / 61
65 / 65
73 / 73
73 / 73
65 / 65
73 / 73
73 / 73
66 / 66
70 / 70
70 / 70
72 / 72
70 / 70
70 / 70
72 / 72
39 / 35 / 33
50 / 48 / 44
50 / 48 / 44
50 / 48 / 44
50 / 48 / 44
50 / 48 / 44
50 / 48 / 44
39 / 35 / 33
50 / 48 / 44
50 / 48 / 44
50 / 48 / 44
50 / 48 / 44
50 / 48 / 44
50 / 48 / 44
51 / 48
48 / 50
48 / 50
49 / 52
48 / 50
48 / 50
49 / 52
18 / 16 / 14
26 / 23 / 19
26 / 23 / 19
26 / 23 / 19
26 / 23 / 19
26 / 23 / 19
26 / 23 / 19
18 / 16 / 14
26 / 23 / 19
26 / 23 / 19
26 / 23 / 19
26 / 23 / 19
26 / 23 / 19
26 / 23 / 19
60 / 50
100 / 100
100 / 100
100 / 100
100 / 100
100 / 100
100 / 100
1,850 x 600 x 320
750 x 880(+88) x 340
1,300 x 970 x 370
49
52
60
105
9.52(3/8") / 15.88(5/8")
Max.50
Max.100
Max.30 / Max.15
-15~43*3
-20~20
Plastic net x 1(washable)
wired:RC-E5 (installed) wireless:RCN-KIT3-E (option)
d (A)
N( )
N( )
m3 min
d (A)
N( )
N( )
m3 min
d (A)
NOTES:
he data are measured under the following conditions( O- ).
Cooling: ndoor temp. of
C
C
and outdoor temp. of
C . eating: ndoor temp. of
C
and outdoor temp. of C
C
.
ndicates the value in an anechoic cham er. uring operation these values are somewhat higher due to am ient conditions.
*2 :: The
values are for one indoor unit operation.
* : f a cooling
is conducted when the outdoor air temperature is
C or lower the outdoor unit should e installed at a place where it is not in uenced y
* natural wind.operation
f wind lows the low pressure will drop and compressor fre uency will increase this will cause the capacity to drop and may cause the unit to reak
down.
42
SPECIFICATIONS
he values are for simultaneous Multi operation.
FDF140VNXPVD1
Set model name
Indoor unit
Outdoor unit
Power source
Nominal cooling capacity (Min~Max)
Nominal heating capacity (Min~Max)
Power consumption Cooling/Heating
EER/COP
Cooling/Heating
Inrush current
Max. current
2
Sound power Indoor* Cooling/Heating
level*1
Outdoor Cooling/Heating
Cooling (Hi/Me/Lo)
Sound
Indoor*2
pressure
Heating (Hi/Me/Lo)
1
level* 2
Outdoor Cooling/Heating
Cooling (Hi/Me/Lo)
Indoor*2
Air flow 2
Heating (Hi/Me/Lo)
Outdoor Cooling/Heating
Indoor
Exterior
HeightxWidthxDepth
dimensions Outdoor
Indoor
Net weight
Outdoor
Ref.piping size Liquid/Gas
Refrigerant line (one way) length
Vertical height differences Outdoor is higher/lower
Cooling
Outdoor operating
temperature range
Heating
Air filter, Q'ty
Remote control
Set model name
Indoor unit
Outdoor unit
Power source
Nominal cooling capacity (Min~Max)
Nominal heating capacity (Min~Max)
Power consumption Cooling/Heating
EER/COP
Cooling/Heating
Inrush current
Max. current
Sound power Indoor Cooling/Heating
level*1
Outdoor Cooling/Heating
Cooling (Hi/Me/Lo)
Sound
Indoor
pressure
Heating (Hi/Me/Lo)
1
level* 2
Outdoor Cooling/Heating
Cooling (Hi/Me/Lo)
Indoor
Air flow 2
Heating (Hi/Me/Lo)
Outdoor Cooling/Heating
Indoor
Exterior
HeightxWidthxDepth
dimensions Outdoor
Indoor
Net weight
Outdoor
Ref.piping size Liquid/Gas
Refrigerant line (one way) length
Vertical height differences Outdoor is higher/lower
Cooling
Outdoor operating
temperature range
Heating
Air filter, Q'ty
Remote control
FDF140VSXPVD1
Twin
FDF71VD1
FDC140VNX
1 Phase 220-240V, 50Hz / 220V, 60Hz
14.0 ( 5.0 ~ 16.0 )
16.0 ( 4.0 ~ 18.0 )
4.83 / 4.97
2.90 / 3.22
5
26
61 / 61
72 / 72
39 / 35 / 33
39 / 35 / 33
49 / 52
16 / 14 / 12
16 / 14 / 12
100 / 100
kW
kW
kW
A
dB(A)
m3/min
1,850 x 600 x 320
1,300 x 970 x 370
49
105
9.52(3/8") / 15.88(5/8")
Max.100
Max.30 / Max.15
-15~43*3
-20~20
Plastic net x 1(washable)
wired:RC-E5 (installed) wireless:RCN-KIT3-E (option)
mm
kg
ømm
m
m
°C
kW
kW
kW
A
dB(A)
m3/min
mm
kg
ømm
m
m
2 Powerful-Hi can be selected.
ound pressure level:
N( ) P
Air ow:
N( ) P
m3 min
°C
FDF71VD1
FDC140VSX
3 Phase 380-415V, 50Hz / 380V 60Hz
14.0 ( 5.0 ~ 16.0 )
16.0 ( 4.0 ~ 20.0 )
4.83/ 4.97
2.90 / 3.22
5
15
61 / 61
72 / 72
39 / 35 / 33
39 / 35 / 33
49 / 52
16 / 14 / 12
16 / 14 / 12
100 / 100
FDF100VNVD2
FDF125VNVD
FDF140VNVD
FDF100VSVD2
FDF125VSVD
FDF140VSVD
FDF100VD2
FDF125VD
FDF140VD
FDF100VD2
FDF125VD
FDF140VD
FDC100VN
FDC125VN
FDC140VN
FDC100VS
FDC125VS
FDC140VS
1 Phase 220-240V, 50Hz / 220V, 60Hz
3 Phase 380-415V, 50Hz / 380V, 60Hz
10.0 ( 4.0 ~ 11.2 )
12.5 ( 5.0 ~ 14.0 )
14.0 ( 5.0 ~ 14.5 )
10.0 ( 4.0 ~ 11.2 )
12.5 ( 5.0 ~ 14.0 )
14.0 ( 5.0 ~ 14.5 )
11.2 ( 4.0 ~ 12.5 )
14.0 ( 4.0 ~ 16.0 )
16.0 ( 4.0 ~ 16.5 )
11.2 ( 4.0 ~ 12.5 )
14.0 ( 4.0 ~ 16.0 )
16.0 ( 4.0 ~ 16.5 )
3.12 / 3.10
4.40 / 4.36
5.15 / 5.31
3.12 / 3.10
4.40 / 4.36
5.15 / 5.31
3.21 / 3.61
2.84 / 3.21
2.72 / 3.01
3.21 / 3.61
2.84 / 3.21
2.72 / 3.01
5
5
5
5
5
5
24
24
24
15
15
15
65 / 65
73 / 73
73 / 73
65 / 65
73 / 73
73 / 73
70 / 70
72 / 72
73 / 73
70 / 70
72 / 72
73 / 73
50 / 48 / 44
50 / 48 / 44
50 / 48 / 44
50 / 48 / 44
50 / 48 / 44
50 / 48 / 44
50 / 48 / 44
50 / 48 / 44
50 / 48 / 44
50 / 48 / 44
50 / 48 / 44
50 / 48 / 44
49 / 49
50 / 51
51 / 51
49 / 49
50 / 51
51 / 51
26 / 23 / 19
26 / 23 / 19
26 / 23 / 19
26 / 23 / 19
26 / 23 / 19
26 / 23 / 19
26 / 23 / 19
26 / 23 / 19
26 / 23 / 19
26 / 23 / 19
26 / 23 / 19
26 / 23 / 19
75 / 73
75 / 73
75 / 73
75 / 73
75 / 73
75 / 73
1,850 x 600 x 320
845 x 970 x 370
52
81
83
9.52(3/8") / 15.88(5/8")
Max.50
Max.30 / Max.15
-15~43*3
-20~20
Plastic net x 1(Washable)
wired:RC-E5 (installed) wireless:RCN-KIT3-E (option)
d (A)
N( )
N( )
m3 min
d (A)
N( )
N( )
m3 min
d (A)
43
SPECIFICATIONS
he values are for simultaneous Multi operation.
FDF140VNPVD1
Set model name
Indoor unit
Outdoor unit
Power source
Nominal cooling capacity (Min~Max)
Nominal heating capacity (Min~Max)
Power consumption Cooling/Heating
EER/COP
Cooling/Heating
Inrush current
Max. current
2
Sound power Indoor* Cooling/Heating
level*1
Outdoor Cooling/Heating
Cooling (Hi/Me/Lo)
Sound
Indoor*2
pressure
Heating (Hi/Me/Lo)
level*1 1
Outdoor Cooling/Heating
Cooling (Hi/Me/Lo)
Indoor*2
Air flow 1
Heating (Hi/Me/Lo)
Outdoor Cooling/Heating
Indoor
Exterior
HeightxWidthxDepth
dimensions Outdoor
Indoor
Net weight
Outdoor
Ref.piping size Liquid/Gas
Refrigerant line (one way) length
Vertical height differences Outdoor is higher/lower
Cooling
Outdoor operating
temperature range
Heating
Air filter, Q'ty
Remote control
Set model name
Indoor unit
Outdoor unit
Power source
Nominal cooling capacity (Min~Max)
Nominal heating capacity (Min~Max)
Power consumption Cooling/Heating
EER/COP
Cooling/Heating
Inrush current
Max. current
Sound power Indoor Cooling/Heating
level*1
Outdoor Cooling/Heating
Cooling (Hi/Me/Lo)
Sound
Indoor
Heating (Hi/Me/Lo)
pressure
level*1 1
Outdoor Cooling/Heating
Cooling (Hi/Me/Lo)
Indoor
Heating (Hi/Me/Lo)
Air flow 1
Outdoor Cooling/Heating
Indoor
Exterior
HeightxWidthxDepth
dimensions Outdoor
Indoor
Net weight
Outdoor
Ref.piping size Liquid/Gas
Refrigerant line (one way) length
Vertical height differences Outdoor is higher/lower
Cooling
Outdoor operating
temperature range
Heating
Air filter, Q'ty
Remote control
1 Powerful-Hi can be selected.
ound pressure level: d (A)
54dB(A)
Air ow:
N( )P
m3 min
FDF140VSPVD1
FDF200VSAPVD2
FDF250VSAPVD
Twin
FDF71VD1
FDC140VN
1 Phase 220-240V, 50Hz / 220V, 60Hz
kW
14.0 ( 5.0 ~ 14.5 )
kW
16.0 ( 4.0 ~ 16.5 )
kW
5.16 / 5.01
2.71 / 3.19
5
A
24
61 / 61
73 / 73
dB(A)
39 / 35 / 33
39 / 35 / 33
51 / 51
16 / 14 / 12
m3/min
16 / 14 / 12
75 / 73
mm
kg
81
ømm
m
m
°C
FDF71VD1
FDC140VS
FDF100VD2
FDF125VD
FDC200VSA
FDC250VSA
3 Phase 380-415V, 50Hz / 380V, 60Hz
14.0 ( 5.0 ~ 14.5 )
19.0 ( 5.2 ~ 22.4 )
24.0 ( 6.9 ~ 28.0 )
16.0 ( 4.0 ~ 16.5 )
22.4 ( 3.3 ~ 25.0 )
27.0 ( 5.5 ~ 31.5 )
5.16 / 5.01
6.74 / 6.42
9.15 / 8.49
2.71 / 3.19
2.82 / 3.49
2.62 / 3.18
5
5
5
15
20
21
61 / 61
65 / 65
73 / 73
73 / 73
72 / 74
73 / 75
39 / 35 / 33
50 / 48 / 44
50 / 48 / 44
39 / 35 / 33
50 / 48 / 44
50 / 48 / 44
51 / 51
58 / 59
59 / 62
16 / 14 / 12
26 / 23 / 19
26 / 23 / 19
16 / 14 / 12
26 / 23 / 19
26 / 23 / 19
75 / 73
135 / 135
143 / 151
1,850 x 600 x 320
845 x 970 x 370
1,300 x 970 x 370
1,505 x 970 x 370
49
52
83
115
143
9.52(3/8") / 15.88(5/8")
9.52(3/8") / 22.22(7/8")
12.7(1/2") / 22.22(7/8")
Max.50
Max.70
Max.30 / Max.15
-15~50*3
-15~43*3
-20~20
-15~20
Plastic net x 1(washable)
wired:RC-E5 (installed) wireless:RCN-KIT3-E (option)
Standard Inverter
FDF90VNPVD2
FDF100VD2
FDC90VNP
1 Phase 220-240V, 50Hz / 220V, 60Hz
9.0 ( 1.9 ~ 9.0 )
9.0 ( 1.5 ~ 9.0 )
2.79 / 2.25
3.23 / 4.00
5
18.0
65 / 65
69 / 69
50 / 48 / 44
50 / 48 / 44
57 / 55
26 / 23 / 19
26 / 23 / 19
63 / 49.5
1,850 x 600 x 320
750 x 880(+88) x 340
FDF71VNPVD1
FDF71VD1
FDC71VNP
kW
kW
kW
7.1 ( 1.4 ~ 7.1 )
7.1 ( 1.0 ~ 7.1 )
2.63 / 2.08
2.70 / 3.41
5
14.5
61 / 61
67 / 67
39 / 35 / 33
39 / 35 / 33
54 / 54
18 / 16 / 14
18 / 16 / 14
36 / 36
A
dB(A)
m3/min
mm
640 x 800(+71) x 290
49
45
6.35(1/4") / 12.7(1/2")
kg
ømm
m
m
FDF100VNP1VD2
FDF100VD2
FDC100VNP
10.0 ( 2.8 ~ 11.2 )
11.2 ( 2.5 ~ 12.5 )
3.19 / 3.09
3.13 / 3.62
5
21.0
65 / 65
70 / 70
50 / 48 / 44
50 / 48 / 44
57 / 61
26 / 23 / 19
26 / 23 / 19
75 / 79
845 x 970 x 370
52
57
6.35(1/4") / 15.88(5/8")
70
9.52(3/8") / 15.88(5/8")
Max.30
Max.23
Max.20 / Max.20
-15~46*3
-15~20
Plastic net x1(Washable)
wired:RC-E5 (installed) wireless:RCN-KIT3-E (option)
°C
N( )P
AP
d (A)
3
m min
AP
d (A)
AP
3
m min
AP
NP
d (A)
3
m min
NP
d (A)
NP
NP
3
m min
d (A)
NP
NP
3
m min
NOTES:
he data are measured under the following conditions( O- ).
Cooling: ndoor temp. of
C
C
and outdoor temp. of
C .
eating: ndoor temp. of
C
and outdoor temp. of C
C
.
ndicates the value in an anechoic cham er. uring operation these values are somewhat higher due to am ient conditions.
*2 :: The
values are for one indoor unit operation.
* : f a cooling
is conducted when the outdoor air temperature is
C or lower the outdoor unit should e installed at a place where it is not in uenced y
* natural wind.operation
f wind lows the low pressure will drop and compressor fre uency will increase this will cause the capacity to drop and may cause the unit to reak
down.
44
BENEFITS SUMMARY
FDT FDTC FDU FDUM FDE
SRK
FDF
Option
Option
Option
Comfort
Economy
When using RC-EX1A (Remote control), functions with symbol are available.
However, for RC-E5 (Remote control), functions with are not available.
Inverter technology
Inverter control technology functions at high efficiency with
smooth operation from high speed to low speed.
A smooth sine voltage wave is attained.
Energy-saving
Since the capacity is controlled automatically based on the outdoor
temperature, energy can be saved without losing comfort.
Home leave operation
When the unit is not used for a long period of time, the room
temperature is maintained at a moderate level, avoiding extremely
hot or cool temperatures.
Set temperature auto return
The temperature automatically returns to the previously set
temperature.
Automatic operation
The air conditioner automatically selects from among heating,
cooling operations.
Silent mode
The unit can be set to prioritise the period of time it operates at a
lower noise level.
Draught prevention
Others
Convenient
Timer
Air flow
Hi power mode
When starting to warm up or when the thermostat is off, the air
discharge direction is set horizontally and the fan to low speed, to
prevent draught. After warming up, air discharge and fan speed
are set as desired.
The high power operation adjusts the room temperature quickly to a
pleasant level by increasing the operation capacity. The high power
operation continues for 15 minutes at maximum and returns to the
normal operation automatically.
Individual flap control
Motion range (upper and lower limit positions) of the flap at each
air outlet can be set at a desired range individually.
Vertical auto swing
Flap moves up and down continuously. The Up/Down flap swing
can be fixed at the preferred operation angle.
Ceiling stain prevention
The shape & angled louver redirects the air current away from the
ceiling reducing ceiling stains.
Automatic fan speed
The micro-computer automatically adjusts the airflow effectively
to follow the changes of return air temperature.
Sleep timer
Set the time period from start to stop of operation. The selectable
range of setting time is from 30 to 240 minutes (at 10-minute
intervals).
Peak-cut timer
Capacity control can be set by using peak cut function on RC-EX1A
for better energy saving. Five-step capacity control is available.
Weekly timer
On or Off timer can be set on a weekly basis.
Static pressure adjustment
This is operable when connecting duct type indoor units equipped
with the external static pressure adjustment function. It will adjust
the airflow accordingly based on the connected duct static pressure.
Remote control
You can select wired remote controls, wireless remote controls or
central remote controls.
Select the language
Set the language to be displayed on the remote control.
Air filter
Removes airborne dust particles through the air filter to ensure a
steady supply of clean air.
Filter sign
Announces the due time for cleaning of the air filter.
Outside air intake
Outside fresh air can be taken inside.
Self-diagnosis
In the case that the air conditioner malfunctions, an internal
microcomputer automatically runs a self-diagnosis. (Inspection
and repair should be performed by authorized dealers.)
Drain up
It allows for a flexible piping layout for condensate allowing a high
degree of freedom depending on the installation location
Option
Option
Procare
locally
Option
Option
Option
Option
*1
*
: E cept
45
CONTROL SYSTEMS
Simple setting REMOTE CONTROL
Advanced touch screen panel with full dot Liquid Crystal display
User friendly
•LCD panel with light tap operation
introduced as the industry's first
•Simple interface with only three buttons
High level of visibility
•Big LCD with 3.8 inch full dot display
•Back light function
•Multi language display (9 languages)
RC-EX1A (option)
Operation mode
Setting temperature screen
Operation mode setting screen
Cooling
Fan
Dry
Heating
Auto
The desired operation mode can
be selected by simply tapping
this button.
You can select the temperature as
desired by tapping
button.
Simple setting by tapping button only
Run / Stop
High power operation
Energy-saving operation
The highest capacity operation (Max 15 minutes)
•Increasing compressor� speed
•Increasing air flow volume
•Changes set temperature.
At 28ºC in cooling mode and 22ºC in heating mode, 25ºC in auto mode.
•Operation correction by outdoor temperature
Main functions
Saving energy
Comfort
Sleep timer
Peak cut timer
Automatic temperature set back
Weekly timer
Set ON/OFF timer by hour
Set ON/OFF timer by clock
Individual flap control
High power operation
External ventilation ON/OFF
Warming up operation
Automatic fan speed
Temperature increment setting
by 0.5ºC
Convenience
Service
LCD contrast setting
Error code display
Back light setting
Operation data display
Filter sign
Next service date display
Control sound
Contact company display
Outdoor silent mode
USB connection (mini-B)
Summer time setting
Home leave mode
Indoor & outdoor temperature display
Heating standby display
Defrosting operation display
Auto cooling/heating display
ºC/ºF display
Administrator settings
Room name setting
46
Remote control RC-EX1A Series
Utility Software
By connecting this system to the Remote Control,
the Remote Control can be operated from PC.
Outdoor unit
Indoor unit
Remote Control
USB
Remote Control
RC-EX1A Utility Software
Remote Control line up
indoor unit
wired
remote control
RC-EX1A
RC-E5
RCH-E3
all models
wireless
indoor unit
FDT
FDTC
FDUM, FDU, FDF
FDE
remote control
RCN-T-36W-E
RCN-TC-24W-ER
RCN-KIT3-E
RCN-E-E
Wired remote control (option)
RC-E5
Run hour meters to facilitate maintenance checking
RC-E5 stores operation data when an anomaly occurs and indicates the error
on the LCD. It also displays cumulative operation hours of the air conditioner
and compressor since commissioning.
The RC-E5 control enables
extensive access to service
and maintenance technical
data combined with easy to
use functions and a clear
LCD display.
Weekly timer function as standard
RC-E5 provides (as a standard feature) a weekly timer, which allows oneweek operation schedules to be registered. A user can specify up to four
times a day to start/stop the air conditioner. (Temperature setting is also
possible with the timer).
Timer operation
Room temperature controlled
by the remote control sensor
The temperature sensor is housed in the top
section of the remote control unit. This
arrangement has improved the sensitivity of the
remote control unit’s sensor, which permits more
finely controlled air conditioning.
Changeable set temperature ranges
RC-E5 allows the upper and lower limits of a set temperature range to be
specified separately.
By adjusting a set temperature range, you can ensure energy saving air
conditioning by avoiding excessive cooling or heating.
Changeable range
Upper limit
20~30˚C(effective for heating operation)
Lower limit
18~26˚C(effective for non-heating operation)
Simple remote control (option)
RCH-E3 (wired)
Considering specialized usage in hotel
rooms, control buttons are limited only to
minimum required functions such as ON/OFF,
mode, temperature setting and fan speed. It
is really simple and easy to use.
Up to 16 units
It can control up to 16 units individually, with pressing the AIR CON No. button.
AUTO restart
RCH-E3 is not applicable to the Individual flap control
system and the Flap control system.
When RCH-E3 is used, the fan has 3 speed settings
(Hi-Me-Lo) only.
This function allows starting the air conditioner automatically when power
supply is restored after power failure or by turning on the power switch.
Wireless remote control (option)
Thermistor (option)
For wireless control simply insert the infrared
receiver kit on a corner of the panel.
RCN-T-36W-E,
RCN-TC-24W-ER
SC-THB-E3
RCN-KIT3-E
RCN-E-E
In case sensor in the indoor units or the remote
control sensor can not sense the room temperature
correctly, or individual remote control in each room is
not required but only censor is required (as when
center control system is in place), install SC-THB-E3
at proper place in the rooms.
Wireless remote control is not applicable to the Individual flap control system and the Flap control system.
When wireless remote control and RCH-E3 are used, the fan has 3 speed settings (Hi-Me-Lo) only.
47
Control System
SUPERLINK-
KXZ series
SC-SL1N-E
RAC series
(SRK/SRF-ZMX-S)
SC-BIKN-E
SC-ADNA-E
SC-SL2NA-E
SC-ADNA-E
SC-ADNA-E
Central Control
SC-SL1N-E
Start/stop control of up to 16 indoor units is
possible either individually or collectively. With
simple operations, you can effect centralized
control.
Centralized control of up to 64 indoor units. It
can allow connection with a weekly timer
without using any interface.
PC windows central control
BMS interface unit
SC-WGWNB256-A/B*
SC-WGWNB-A/B
SC-BGWNA256-A/B*
SC-BGWNA-A/B
(SC-WGWNB256-B/SC-WGWNB-B are with electric power calculation function)
Production by order
In case of SC-WGWNB256-A/B, up to 256
cells (some cells can have two or more
indoor units and total number of indoor units
can be up to 256 units) are controlled from
the Internet Explorer.
48
SC-SL2NA-E
SC-SL4-AE/BE
Easy operation realized with a large color LCD
and touch panel. Up to 128 indoor units can be
controlled, when SUPERLINK-II systems are
connected.
SC-LGWNA-A*
(LonWorks gateway)
(BACnet gateway)
(SC-BGWNA256-B/BGWNA-B are with electric power calculation function)
Production by order
In case of SC-BGWNA256-A/B, up to 256 cells
(some cells can have two or more indoor units
and total number of indoor units can be up to
256 units) are controlled centrally from a BMS.
Production by order
Up to 96 indoor units (48 indoor unit x 2) are
linked as an open network. Centrally controlled
through LonWorks.
In case of SC-BGWNA-B/BGWNA256-B, communication test by
qualified person regarding electric cost calculation function is
required before commissioning.
*Additional engineering service cost etc. is required. Please consult your dealer when using these system.
SUPERLINK E BOARD (SC-ADNA-E)
This board is used when conducting control of the single package (wired remote control unit) 1-type series using a network
option (SC-SL1N-E, SC-SL2NA-E, etc).
(1) Functions
(a) Transmits the settings from the network option to the indoor units.
(b) Returns the priority indoor unit data in response to a data request from the network option.
(c) Inspects the error status of connected indoor units and transmits the inspection codes to the network option.
(d) A maximum of 16 units can be controlled (if in the same operation mode).
(2) Wiring connection diagram
(3) Metal box dimension (unit:mm)
Connected to the terminals for
Superlink signal lines
MVVS 0.75 - 1.25mm2
SW2
Network address setting switches
[000]-(127)
Basic Connections
70
Y
Connected to the remote control terminals (no
polarity) (the length should be 600 m or shorter)
200 m or shorter
0.5 mm2 x 2 cores
0.75 mm2 x 2 cores
300 m or shorter
1.25 mm2 x 2 cores
400 m or shorter
2.0 mm2 x 2 cores
600 m or shorter
ON
Master/Sub
address
X
White
90
LED3
LED2
Black
Y
SW1
5
B
X
OFF SW3
A
Blue
B
35
30
22.5
100
Run
Abnormal
Blue
A
SL E board
85
40
2-ø6
Plural Controls by Multiple Remote Controls. Mixture of Multiple Units
Outdoor unit
Outdoor unit
Internal/external Crossing
Internal/external Crossing
Indoor unit
X Y
SL E Board
X Y
A B
Inside Inside Inside Inside
Remote control
X Y
SL E
Board
R
R
Network
options
Network A B
options
• Transmit the information of plural “Master” units to the network.
• Transmit the abnormalities of the “Slave” units to the network.
Setting the plural “Master/Slave” units with the dip SW of the printed circuit board.
Setting the “Master/Slave” remote controls with the dip SW of the remote control board.
Plural Controls by Multiple Remote Controls. Mixture of Multiple Units
Outdoor unit
Outdoor unit
Internal/external Crossing
Inside Inside Inside Inside
SL E
Board
Network
options
R
R
Outdoor unit
Internal/external Crossing
Inside Inside Inside
R
Wireless Kit
Outdoor unit
Internal/external Crossing
SL E
Board
Without Remote Control
Internal/external Crossing
Inside Inside
SL E
Board
R
Set up “000” to “127” using address switch on the SL E board.
Network
options
Inside Inside
Set the SL E board dip SW
to “Master” SW3-1 ON.
The network option SL1N-E
is not allowed (This will
disturb switching of the
operation mode)
SL E
Board
Network
options
Wireless Kit
Wireless
remote control
External switch connection CnT
HOTEL
HOTEL
All indoor units are equipped with an additional
connection point-CnT-to connect indoor units to an
external ON/OFF switch; e.g. time clock, fire alarm,
etc.
Remote surveillance system
Card key on-off
49
OUTDOOR UNIT DIMENSIONS (unit:mm)
SRC40ZMX-S, 50ZMX-S, 60ZMX-S
Terminal block
148.4
33.5
640
L2
Check joint
B
Service
space
outlet
42.5
93
12.4
Dimensions
24.3
L1
L2
L3
L4
Mark
A
B
D
E
201
14.8
17.9
E
800
Mark
A
B
C
D
E
223
Item
Refrigerant gas side pipe connection tap
Refrigerant liquid side pipe connection tap
Drain discharge port
Anchor bolt hole
Item
Service valve connection
(gas side)
Service valve connection
(liquid side)
Pipe/cable draw-out hole
Drain discharge hole
Anchor bolt hole
ø20x3places
M10x4places
L3
47.5
.5
R7
2-
15
Intake
L4
418
380
340
L2
Service
space
150
580
880
150
L1
27
D
19
61
Intake
61
outlet
32
88
Terminal block
Minimum installation space
750
C
B
30
48.5
30
24
Examples of
installation
103.5
Dimensions
A
165.5
50
3
ø12.7(flare)
ø6.35(flare)
ø20.5x5places
M10x4places
Notes:
(1) It must not be surrounded by walls on the four sides.
(2) The unit must be fixed with anchor bolts. An anchor bolt must
not protrude more the 15mm.
(3) Where the unit is subject to strong winds, lay it in such a
direction that the blower outlet faces perpendicularly to the
dominant wind direction.
(4) Leave 1m or more space above the unit.
(5) A wall in front of the blower outlet must not exceed the units
height.
(6) The model name label is attached on the lower right corner of
the front.
ø15.88(5/8")
(Flare)
ø9.52(3/8")
(Flare)
E
60
310
2
Notes:
(1) It must not be surrounded by walls on the four sides.
(2) The unit must be fixed with anchor bolts.An anchor bolt must not protrude more than
15mm.
(3) Where the unit is subject to strong winds, lay it in such a direction that the blower outlet
faces perpendicularly to the dominant wind direction.
(4) Leave a 1m or larger space above the unit.
(5) A wall in front of the blower outlet must not exceed the units height.
(6) The unit name plate is attached on the lower right corner of the front panel.
71.2
FDC71VNX
1
Open 280 280
100
75 Open
100
80
80
250 Open 250
351.6
290
312.5
43.5
A
83.5
327.3
510
L1
40
12
89
L4
Examples of
installation
50.6
327.3
L3
Intake
40
D
Intake
25
L1
L2
L3
L4
1
2
3
Open
300
100
250
Open
250
150
250
500
Open
100
250
FDC100VNX, 100VSX, 125VNX, 125VSX,
140VNX, 140VSX
Mark
A
B
C
D
E
B
F
51
46
A
46
Notes:
(1) It must not be surrounded by walls on the four
sides.
(2) The unit must be fixed with anchor bolts. An
anchor bolt must not protrude more than 15mm.
(3) Where the unit is subject to strong winds, lay it in
such a direction that the blower outlet faces
perpendicularly to the dominant wind direction.
(4) Leave 1m or more space above the unit.
(5) A wall in front of the blower outlet must not
exceed the units height.
(6) The model name label is attached on the lower
right corner of the front panel.
(7) Connect the Service valve with local pipe by
using the pipe of the attachment. (Gas side only)
Item
Service valve connection of the
attached connecting pipe(gas
ø15.88(5/8")(Flare)
side)
Service valve connection(liquid side) ø9.52(3/8")(Flare)
Pipe/cable draw-out hole
ø20x3places
Drain discharge hole
M10x4places
Anchor bolt hole
ø30(front)
ø45(side)
Cable draw-out hole
ø50(back)
113
Terminal block
B
1300
A
F
C
15
970
E
580
325
15
150
195
L3
L2
15
38
103
55
410
370
40
20
262
60
50
40
F
15
200
C
60
C
50
27
60
40
20
190
50
55
C
50
10
195
70
110
624
110
612
F
Examples of
installation
Intake
Dimensions
L4
Intake
L1
Service
space
Outlet
L1
L2
L3
L4
1
2
3
Open Open 500
300
5 Open
150 300 150
5
5
5
Minimum installation space
D
FDC100VN, 125VN, 140VN
FDC100VS, 125VS, 140VS
51
OUTDOOR UNIT DIMENSIONS (unit:mm)
FDC200VSA
FDC250VSA
52
FDC71VNP
FDC90VNP
FDC100VNP
53
ENERGY LABEL [FOR EU/EEA AREA ONLY]
Several radical design changes and engineering developments have brought about
a vast improvement in energy efficiency and environmental protection.
ENERGY LABEL
Employment of lead-free solder
SEER and SCOP is defined in European
regulations listed below.
Adapted to RoHS directive
RoHS:Restriction of Hazardous substances
No.626/2011 of 4 May 2011: energy
labeling of air-conditioners (below
cooling capacity 12kW).
No.206/2012 of 6 March 2012:
requirement for air-conditioners and
comfort fans.
Seasonal efficiency is the new way of
rating the true efficiency of heating and
cooling products over an entire year.
Set by the EU's new regulation
implementing Eco-Design Directive for
Energy Related Product (ErP) which
specifies the minimum efficiency of airconditioners manufacturers must
integrate into their products.
The new Seasonal Efficiency rating
system that must be used for heating
and cooling by all manufacturers are;
SEER - Seasonal Efficiency Ratio
(value in cooling)
SCOP - Seasonal Coefficient of
Performance (value in heating)
The new rating system will indicate the
true efficiency of the energy using
product at specified condition.
In order to avoid the release of hazardous
substances into the environments, all
models have utilized lead-free solder
application. It has been considered to be
difficult to use lead-free solder for practical
applications because it requires higher
solder temperatures at assembly, which can
jeopardize reliability. However our PbF
soldering method can produce a higher
quality lead-free printed circuit board.
Employment of
All models use refrigerant R410A
characterized by the ozone depletion
coefficient being 0.
Excellent Energy Saving
High performance and excellent energy
savings are achieved at the same time by
heat exchanger's increased capacity and
employment of high efficiency DC motor.
Indoor unit
FDT40VF
FDT50VF
FDT60VF
FDT71VF1
FDT100VF2
FDT100VF2
FDT40VFx2
FDT50VFx2
FDT50VFx2
Outdoor unit
SRC40ZMX-S
SRC50ZMX-S
SRC60ZMX-S
FDC71VNX
FDC100VNX
FDC100VSX
FDC71VNX
FDC100VNX
FDC100VSX
Energy class (cooling/heating)
A++/A+
A++/A+
A++/A
A+/A+
A+/A
A+/A
A+/A+
A+/A
A+/A
SEER
7.57
6.91
7.69
5.72
5.84
5.79
5.68
5.92
5.88
SCOP (Average climate)
4.16
4.09
3.86
4.09
3.96
3.95
4.10
3.85
3.84
Pdesignc
kW
4.0
5.0
5.6
7.1
10.0
10.0
7.1
10.0
10.0
Pdesignh (@-10°C)
kW
4.8
5.1
5.9
6.5
13.5
13.5
7.3
13.1
13.1
185/1617
254/1748
255/2139
435/2226
600/4778
605/4782
438/2494
592/4768
596/4772
Annual electricity consumption (cooling/heating) kWh/a
Refrigerant (GWP)
R410A (1975)
Designated heating season
Average
Indoor unit
FDT100VF2
FDT100VF2
FDT50VFx2
FDT50VFx2
FDT71VF1
FDT100VF2
FDT100VF2
FDTC40VF
FDTC50VF
Outdoor unit
FDC100VN
FDC100VS
FDC100VN
FDC100VS
FDC71VNP
FDC90VNP
FDC100VNP
SRC40ZMX-S
SRC50ZMX-S
A+/A
Energy class (cooling/heating)
A+/A
A/A
A+/A
A+/A
A++/A+
A++/A+
A++/A+
A++/A
SEER
5.61
5.57
5.89
5.85
6.14
6.73
6.78
6.53
6.01
SCOP (Average climate)
3.92
3.91
3.81
3.81
4.27
4.11
4.52
3.96
3.85
Pdesignc
kW
10.0
10.0
10.0
10.0
7.1
9.0
10.0
4.0
5.0
Pdesignh (@-10°C)
kW
9.7
9.7
9.5
9.5
5.7
8.1
8.1
4.0
4.8
625/3466
629/3470
595/3488
599/3492
405/1871
468/2756
516/2507
215/1416
291/1745
Annual electricity consumption (cooling/heating) kWh/a
Refrigerant (GWP)
R410A (1975)
Designated heating season
Average
Indoor unit
FDTC60VF
FDTC40VFx2
FDTC50VFx2
FDTC50VFx2
FDTC50VFx2
FDTC50VFx2
FDU71VF1
FDU100VF2
FDU100VF2
Outdoor unit
SRC60ZMX-S
FDC71VNX
FDC100VNX
FDC100VSX
FDC100VN
FDC100VS
FDC71VNX
FDC100VNX
FDC100VSX
A/A+
Energy class (cooling/heating)
A+/A
A/A
A/A
A/A
A/A
A/A
A/A
A/A+
SEER
5.76
5.31
5.23
5.19
5.17
5.13
5.24
5.22
5.19
SCOP (Average climate)
3.80
3.88
3.87
3.86
3.84
3.84
3.90
4.10
4.10
Pdesignc
kW
5.6
7.1
10.0
10.0
10.0
10.0
7.1
10.0
10.0
Pdesignh (@-10°C)
kW
5.9
6.8
10.2
10.2
9.4
9.4
7.0
13.0
13.0
341/2172
468/2455
670/3692
674/3695
678/3424
682/3428
475/2513
670/4437
675/4441
Annual electricity consumption (cooling/heating) kWh/a
Refrigerant (GWP)
R410A (1975)
Designated heating season
Average
R410A refrigerant contained in the products is a fluorinated greenhouse gas listed in Regulation (EU) No 517/2014.
54
Indoor unit
FDU100VF2
FDU100VF2
FDU71VF1
FDU100VF2
FDU100VF2
FDUM40VF
FDUM50VF
FDUM60VF
FDUM71VF1
Outdoor unit
FDC100VN
FDC100VS
FDC71VNP
FDC90VNP
FDC100VNP
SRC40ZMX-S
SRC50ZMX-S
SRC60ZMX-S
FDC71VNX
Energy class (cooling/heating)
B/A
B/A
A+/A+
A++/A+
A++/A+
A+/A+
A+/A+
A++/A+
A/A
SEER
5.06
5.03
5.71
6.86
6.36
6.01
5.68
6.42
5.24
3.90
SCOP (Average climate)
3.94
3.94
4.00
4.20
4.13
4.15
4.36
4.37
Pdesignc
kW
10.0
10.0
7.1
9.0
10.0
4.0
5.0
5.6
7.1
Pdesignh (@-10°C)
kW
9.3
9.3
5.7
8.1
8.1
3.5
4.3
5.4
7.0
692/3303
696/3307
436/1996
459/2703
551/2746
233/1182
309/1382
306/1731
475/2513
Annual electricity consumption (cooling/heating) kWh/a
Refrigerant (GWP)
R410A (1975)
Designated heating season
Average
Indoor unit
FDUM100VF2
FDUM100VF2
FDUM40VFx2
FDUM50VFx2
FDUM50VFx2
FDUM100VF2
FDUM100VF2
FDUM50VFx2
FDUM50VFx2
Outdoor unit
FDC100VNX
FDC100VSX
FDC71VNX
FDC100VNX
FDC100VSX
FDC100VN
FDC100VS
FDC100VN
FDC100VS
Energy class (cooling/heating)
A/A+
A/A+
A+/A+
A/A
A/A
B/A
B/A
B/A
B/A
SEER
5.22
5.19
5.61
5.14
5.11
5.06
5.03
4.81
4.78
4.10
4.10
4.05
3.88
3.87
3.94
3.94
3.82
3.81
10.0
10.0
7.1
10.0
10.0
10.0
10.0
10.0
10.0
SCOP (Average climate)
Pdesignc
kW
Pdesignh (@-10°C)
kW
Annual electricity consumption (cooling/heating) kWh/a
13.0
13.0
7.0
10.0
10.0
9.3
9.3
9.3
9.3
670/4437
675/4441
444/2422
681/3611
685/3614
692/3303
696/3307
728/3413
732/3416
Refrigerant (GWP)
R410A (1975)
Designated heating season
Average
Indoor unit
FDUM71VF1
FDUM100VF2
FDUM100VF2
FDE40VG
FDE50VG
FDE60VG
FDE71VG
FDE100VG
FDE100VG
Outdoor unit
FDC71VNP
FDC90VNP
FDC100VNP
SRC40ZMX-S
SRC50ZMX-S
SRC60ZMX-S
FDC71VNX
FDC100VNX
FDC100VSX
Energy class (cooling/heating)
A+/A+
A++/A+
A++/A+
A++/A
A++/A
A++/A+
B/A+
A+/A+
A+/A+
SEER
5.71
6.86
6.36
6.46
6.10
6.72
4.87
5.89
5.84
SCOP (Average climate)
4.00
4.20
4.13
3.93
3.92
4.08
4.00
4.18
4.17
Pdesignc
kW
7.1
9.0
10.0
4.0
5.0
5.6
7.1
10.0
10.0
Pdesignh (@-10°C)
kW
5.7
8.1
8.1
3.0
3.8
4.3
6.0
11.2
11.2
436/1996
459/2703
551/2746
217/1069
288/1358
292/1475
511/2102
595/3754
599/3758
Annual electricity consumption (cooling/heating) kWh/a
Refrigerant (GWP)
R410A (1975)
Designated heating season
Average
Indoor unit
FDE40VGx2
FDE50VGx2
FDE50VGx2
FDE100VG
FDE100VG
FDE50VGx2
FDE50VGx2
FDE71VG
FDE100VG
Outdoor unit
FDC71VNX
FDC100VNX
FDC100VSX
FDC100VN
FDC100VS
FDC100VN
FDC100VS
FDC71VNP
FDC90VNP
A++/A+
Energy class (cooling/heating)
A/A+
A/A
A/A
A/A
A/A
A/A
A/A
A++/A+
SEER
5.26
5.53
5.49
5.43
5.39
5.16
5.13
6.35
6.63
SCOP (Average climate)
4.09
3.94
3.94
3.91
3.90
3.81
3.80
4.22
4.25
Pdesignc
kW
7.1
10.0
10.0
10.0
10.0
10.0
10.0
7.1
9.0
Pdesignh (@-10°C)
kW
6.0
10.8
10.8
7.9
7.9
7.8
7.8
5.8
8.2
473/2054
634/3836
638/3840
645/2830
649/2833
679/2868
683/2872
392/1925
475/2704
Annual electricity consumption (cooling/heating) kWh/a
Refrigerant (GWP)
R410A (1975)
Designated heating season
Average
Indoor unit
FDE100VG
SRK71ZM-S
SRK100ZR-S
Outdoor unit
FDC100VNP
FDC71VNP
FDC100VNP
FDC100VNX
FDC100VSX
FDC100VN
FDC100VS
Energy class (cooling/heating)
A++/A+
A++/A+
A++/A+
A/A+
A/A+
A/A+
A/A+
B/A
A/A
SEER
6.73
6.60
6.60
5.51
5.47
5.46
5.47
4.80
5.20
4.44
4.47
4.40
4.00
4.00
4.00
4.00
3.81
3.80
10.0
7.1
10.0
10.0
10.0
10.0
10.0
7.1
10.0
SCOP (Average climate)
Pdesignc
kW
Pdesignh (@-10°C)
kW
Annual electricity consumption (cooling/heating) kWh/a
SRK50ZMX-Sx2 SRK50ZMX-Sx2 SRK50ZMX-Sx2 SRK50ZMX-Sx2
8.1
5.7
7.2
11.6
11.6
8.2
8.2
6.7
13.0
377/1786
531/2289
636/4060
640/4063
642/2869
646/2872
518/2464
673/4792
Refrigerant (GWP)
R410A (1975)
Average
Indoor unit
FDF100VD2
FDF100VD2
FDF100VD2
FDF71VD1
FDF100VD2
FDF100VD2
Outdoor unit
FDC100VSX
FDC100VN
FDC100VS
FDC71VNP
FDC90VNP
FDC100VNP
Energy class (cooling/heating)
A/A
B/A
B/A
A/A
A+/A+
A/A
SEER
5.17
5.02
4.99
5.24
5.69
5.41
Pdesignc
kW
Pdesignh (@-10°C)
kW
Annual electricity consumption (cooling/heating) kWh/a
FDF100VD2
FDC100VNX
521/2556
Designated heating season
SCOP (Average climate)
FDF71VD1
FDC71VNX
3.80
3.80
3.80
3.91
4.01
3.94
10.0
10.0
10.0
7.1
9.0
10.0
13.0
9.3
9.3
5.5
8.1
8.1
678/4795
697/3423
701/3427
475/1972
555/2826
647/2875
Refrigerant (GWP)
R410A (1975)
Designated heating season
Average
55
Before starting use
Heating performance
Refrigerant leakage
The heating performance values (kW) described in catalogue are the values obtained by operating at an outdoor temperature of 7 C and indoor temperature of 20 C as set forth in the ISO Standards. As the heating performance decreases as the outdoor temperature drops, if the outdoor temperature is too low and the heating performance is insufficient, use other heating appliances as well. The refrigerant (R410A) used for Air conditioner is non-toxic and inflammable in its original state. However, in consideration of a state where the refrigerant leaks into the room, measures against refrigerant leaks must be taken in small rooms where the tolerable level could be exceeded. Take measures by installing ventilation devices, etc.
Indication of sound values
Use in snowy areas
The sound values are the values (A scale) measured in a chamber such as an anechoic chamber following the ISO Standards. In the actual installation state, the value is normally larger than the values given in the catalog due to the effect of surrounding noise and echo. Take this into consideration when installing.
Take the following measures when installing the outdoor unit in snowy areas.
·Snow prevention
Install a snow-prevention hood so that the snow does not obstruct the air intake port or enter and freeze in the outdoor unit.
Use in oil atmosphere
·Snow piling
Avoid installing this unit in as atmosphere where oil scatters or builds up, such as in a kitchen or machine factory. If the oil adheres to the heat exchanger, the heat exchanging performance will drop, mist may be generated, and the synthetic resin parts may deform and break.
In areas with heavy snow fall, the piled snow could block the air intake port. In this case, a frame that is 50cm or higher than the estimated snow fall must be installed underneath the outdoor unit.
Use in acidic or alkaline atmosphere
If this unit is used in acidic atmosphere such as hot spring areas having high level of sulfuric gases or in alkaline atmosphere including ammonia or calcium chloride, places where the exhaust of the heat exchanger is sucked in, or at coastal areas where the unit is subject to salt breezes, the outer plate or heat exchanger, etc., will corrode. Please ask a dealer or specialist when you use an air conditioner in places differing from a general atmosphere.
Use in places with high ceilings
If the ceiling is high, install a circulator to improve the heat and air flow distribution when heating.
Automatic defrosting device
If the temperature is low, and the humidity is high, frost will stick to the heat exchanger of the outdoor unit. If use is continued, the heating performance will drop. The "Automatic defrosting device" will function to remove this frost. After heating for approx, three to ten minutes, it will stop, and the frost will be removed. After defrosting, hot air will be blown again.
Servicing the air-conditioner
After the air-conditioner is used for several seasons, dirt will build up in the air-conditioner causing the performance to drop. In addition to regular servicing, we recommend the maintenance contract (charged for) by a specialist.
Safety Precautions
Air-conditioner usage target
Installation
The air-conditioner described in this catalog is a dedicated cooling/heating device for human use. Do not use it for special applications such as the storage of foodstuffs, animals or plants, precision devices or valuable art, etc. This could cause the quality of the items to drop, etc. Do not use this for cooling vehicles or ships. Water leakage or current leaks could occur.
Always commission the installation to a dealer or specialist. Improper installation will lead to water leakage, electric shocks and fires. Make sure that the outdoor unit is stable in installation. Fix the unit to stable base. Before use
Always read the "User,s Manual" thoroughly before starting use.
Usage place
Do not install in places where combustible gas could leak or where there are sparks. Installation in a place where combustible gas could be generated, flow or accumulate, or places containing carbon fibers could lead to fires.
Mitsubishi Heavy Industries, Ltd.
Air-Conditioning & Refrigeration Division
Machinery Equipment & Infrastructure
16-5, Konan 2-chome, Minato-ku, Tokyo, 108-8215 Japan
http://www.mhi.co.jp
Our factories are ISO9001 and ISO14001 certified.
Certified ISO 9001
Certified ISO 14001
ISO 14001
Certificate 04104 1998 0813 E5
BIWAJIMA PLANT
Mitsubishi Heavy Industries, Ltd.
Air-conditioning & Refrigeration Systems Headquarters
Certified ISO 9001
Certificate Number : JQA-0709
16P01E
MITSUBISHI HEAVY INDUSTRIESMAHAJAK AIR CONDITIONERS CO., LTD.
Certified ISO 9001
Certificate Number : 04100 1998 0813
January 2016 F
Mitsubishi Heavy
Industries-Haier (Quingdao)
Air-conditioners Co.,Ltd.
Certificate Number : 5170-1996-AQ-RCG-RvA
BIWAJIMA PLANT
Mitsubishi Heavy Industries, Ltd.
Air-conditioning & Refrigeration Systems Headquarters
Certificate Number : YKA4003622
MITSUBISHI HEAVY INDUSTRIESMAHAJAK AIR CONDITIONERS CO.,LTD.
Certificate Number : 04104 1998 0813 E5
Mitsubishi Heavy
Industries-Haier (Quingdao)
Air-conditioners Co.,Ltd.
Certificate number : 01-1998-083