Mounting Connection Application examples Operation 48005931 *48005931* ® Troubleshooting DeltaSol BS Plus RESOL DeltaSol® BS Plus (Version 2) en Thank you for buying this RESOL product. Read this manual carefully to get the best perfomance from this unit. Please keep this manual carefully. Manual www.resol.com DeltaSol® BS Plus Contents 1. Installation............................................................ 4 1.1Mounting.................................................................................4 1.2Electrical connection............................................................4 1.3Data communication/ Bus..................................................5 1.4Terminal allocation in the different system layouts.....6 System layout 1......................................................................6 System layout 2......................................................................8 System-specific functions................................................. 10 System layout 3....................................................................12 System-specific functions..................................................14 System layout 4....................................................................16 System layout 5....................................................................18 System layout 6................................................................... 20 System layout 7................................................................... 22 System layout 8....................................................................24 System-specific functions................................................. 26 System layout 9................................................................... 28 System layout 10................................................................ 30 2. Operation and function.................................... 32 2.1Push buttons....................................................................... 32 2.2System monitoring display............................................... 32 2.3Flashing codes......................................................................33 3. Commissioning.................................................. 34 4. Channel overview.............................................. 37 4.1Display channels..................................................................37 4.2Adjustment channels......................................................... 39 5. Troubleshooting................................................ 47 5.1Various.................................................................................. 48 6. Accessories......................................................... 50 Impressum............................................................... 52 Safety advice Target group Please pay attention to: These instructions are exclusively addressed to authorised skilled personnel. - safety advice in order to avoid danger and damage to people and property. Only qualified electricians should carry out electrical works. - the valid local standards, regulations and directives! Initial installation must be effected by qualified personnel named by the manufacturer. Description of symbols Information about the product WARNING! Warnings are indicated with a warning triangle! They contain information on how to avoid the danger described. Signal words describe the danger that may occur, when it is not avoided. WARNING means that injury, possibly life-threatening injury, can occur. ATTENTION means that damage to the appliance can occur. Proper usage The solar controller is designed for use in solar thermal and heating systems in compliance with the technical data specified in these instructions. Improper use excludes all liability claims. CE-Declaration of conformity The product complies with the relevant directives and is therefore labelled with the CE mark. The Declaration of Conformity is available upon request, please contact RESOL. Note Notes are indicated with an information symbol. Note Strong electromagnetic fields can impair the function of the controller. ÎÎ Arrows indicate instruction steps that should be carried out. ÎÎ Make sure the controller as well as the system are not exposed to strong electromagnetic fields. Disposal Dispose of the packaging in an environmentally sound manner. Dispose of old appliances in an environmentally sound manner. Upon request we will take back your old appliances bought from us and guarantee an environmentally sound disposal of the devices. |2 Subject to technical change. Errors excepted. © RESOL 11157_deltasol_bs_plus.monen.indd General...................................................................... 2 Overview.................................................................... 3 DeltaSol® BS Plus Overview • System-monitoring-display • Up to 4 Pt1000 temperature sensors • 2 semiconductor relays for pump speed control • 10 basic system layouts to choose from • Heat quantity measurement • VBus® • Function control • Thermostat function (time-controlled) • Control of the system by ServiceCenter software possible ! • User-friendly operation • Housing with outstanding design • Extra-low power consumption • HE pump control via adapter 1 × accessory bag 1 × spare fuse T4A 2 × screws and wall plugs 4 × strain relief and screws 6.8" 172 mm 1 × DeltaSol® BS Plus 2.6" 66 mm 6.1" 155 mm 1.1" 28 mm Included with the BS Plus: 1 × manual © RESOL 11157_deltasol_bs_plus.monen.indd Additionally enclosed in the full kit: 2 × sensor FKP6 2 × sensor FRP6 Technical data Housing: plastic, PC-ABS and PMMA Protection type: IP 20 / EN 60529 Ambient temp.: 0 ... 40 °C [32 ... 104 °F] Size: 172 × 110 × 46 mm 6.8" × 4.3" × 1.9" Mounting: wall mounting, mounting into patch-panels is possible Display: System screen for system visualisation, 16-segment display, 7-segment display, 8 symbols for system status and operating control lamp 0.4" / 11 mm 4.3" 110 mm Operation: by 3 push buttons at the front of the housing Functions: Differential temperature controller with optional add-on system functions. Function control, operating hours counter for solar pump, tube collector function, pump speed control, thermostat function, drainback and booster option, and heat quantity measurement. Inputs: for 4 Pt1000 temperature sensors Outputs: 2 semiconductor relays 0.5" / 13 mm 1.9" / 47 mm Bus: VBus® Power supply: 100 ... 240 V ~ Standby power consumption: < 1W Switching capacities: R1: 1 (1) A 100 ... 240 V ~ (semiconductor relay) R2: 1 (1) A 100 ... 240 V ~ (semiconductor relay) 3| DeltaSol® BS Plus 1. Installation 1.1Mounting WARNING! Electric shock! Opening the housing will expose live parts! ÎÎ Switch off power supply and disconnect the device from power supply before opening the housing! display push button cover cable conduits with strain relief fuse 4A 130 mm 5.1“ upper fastening 104 mm 4.1“ lower fastening 1.2Electrical connection T4A 100 ... 240 V~ 50-60 Hz CU 72091163 01 Temp. Sensor Pt1000 2 3 S2 4 S3 5 6 S4 7 8 VBus 9 10 R1 1 (1) A (100 ... 240) V~ R2 1 (1) A (100 ... 240) V~ 12 13 14 N R2 N R1 N L 15 16 17 18 19 20 Note: VBus® sensor terminal ground terminal load terminals power supply terminals |4 ATTENTION! ESD damage! Electrostatic discharge can lead to damage to electronic components! ÎÎ Take care to discharge properly before touching the inside of the device. To do so, touch a grounded surface such as a radiator or tap! The minimum pump speed must be set to 100 % when auxiliary relays or valves are connected. © RESOL 11157_deltasol_bs_plus.monen.indd IP 20 1 The controller must additionally be supplied from a doublepole switch with contact gap of at least 3 mm [0.12“]. Route sensor cables and power supply cables separately. ÎÎ Unscrew the cross-head screw from the cover and remove it along with the cover from the housing ÎÎ Mark the upper fastening point on the wall and drill ÎÎ Fasten the enclosed wall plug and screw leaving the head protruding ÎÎ Hang the housing from the upper fastening point and mark the lower fastening point through the hole in the terminal box (centers 130 mm [5.1“]) ÎÎ Drill and insert the lower wall plug ÎÎ Fasten the housing to the wall with lower fastening screw and tighten ÎÎ Complete wiring connections in accordance with terminal allocations, see chap. 1.2 “Electrical connection” ÎÎ Place the cover back onto the housing ÎÎ Fasten the cover by means of the cross-head screw fuse DE-45527 Hattingen DeltaSol BS Plus V2 Made in Germany S1 The unit must only be installed •• in a dry interior location •• in a non-hazardous location •• away from electromagnetic fields DeltaSol® BS Plus T4A 100 ... 240 V~ 50-60 Hz CU 72091163 01 IP 20 R1 1 (1) A (100 ... 240) V~ R2 1 (1) A (100 ... 240) V~ 000 S4 7 8 VBus 9 10 N R2 N R1 N L 12 13 14 15 16 17 18 19 20 Grounding and load terminals DE-45527 Hattingen DeltaSol BS Plus V2 Made in Germany Temp. Sensor Pt1000 S1 1 2 3 S2 4 S3 5 6 S4 7 8 Sensor terminals S1 ... S4 © RESOL 11157_deltasol_bs_plus.monen.indd 1.3Data communication/ Bus VBus® connection terminals VBus 9 10 Connecting the device to the mains supply must always be the last step of the installation! The power supply to the controller must be carried out via an external power switch (last step!). The supply voltage must be 100 ... 240 V~ (50 ... 60 Hz). Flexible cables must be attached to the housing with the enclosed strain relief and the corresponding screws. The controller is equipped with two semiconductor relays, to which loads such as pumps, valves etc. can be connected: •• Relay 1 18 = conductor R1 17 = neutral conductor N 13 = ground conductor •• Relay 2 16 = conductor R2 15 = neutral conductor N 14 = ground conductor The mains supply is to be carried out at the terminals: 19 = neutral conductor N 20 = conductor L 12 = ground terminal The temperature sensors (S1 up to S4) are to be connected to the following terminals with either polarity: 1 / 2 = SensorT4A 1 (e.g. Sensor collector 1) 3 / 4 = Sensor100 2 (e.g. store 1) ... 240Sensor V~ Hz 5 / 6 = Sensor 3 50-60 (e.g. Sensor store top) CU 72091163 01 7 / 8 = Sensor 4 (e.g. Sensor return) All Pt1000 temperature are equipped with a R1 1 (1) A (100 ... 240)sensors V~ IP 20 platinum element 1 (1) A (100 ... 240) V~ in their tip. The electrical R2 measuring resistance of the measuring element changes in relation N R2 N R1 N L to the temperature (see table in chap. 5). 12 13 14 15 16 17 18 19 20 The difference between FKP and FRP type sensors only lies in the cable insulation material. The insulation material of FKP type sensor cables resists a higher temperature, so that FKP type sensors should be used as collector sensors. FRP type sensors are best used as reference sensors in stores or pipes. The controller is equipped with a RESOL VBus® for data transfer with and energy supply to external modules. The connection is carried out at the terminals marked “VBus” (either polarity). One or more RESOL VBus® modules can be connected via this data bus, such as •• GA3 large display, SD3 smart display •• DL2 datalogger •• VBus® /USB or VBus® /LAN interface adapter •• VBus® /PWM interface adapter •• AM1 alarm module •• WMZ calorimeter module By means of a DL2 datalogger or an interface adapter, the controller can be connected to a PC or a computer network. With the RESOL ServiceCenter Software (RSC) the controller measurements can be read out, processed and visualised. The software allows easy function control of the system. For the remote parametrisation of the controller, a special software tool will be available for download, soon. 5| DeltaSol® BS Plus 1.4Terminal allocation in the different system layouts System layout 1 The controller calculates the temperature difference between collector sensor S1 and store sensor S2. If the difference is larger than or identical to the adjusted switchon temperature difference (DT O), the solar pump will be operated by relay 1, and the store will be loaded until the switch-off temperature difference (DT F) or the maximum store temperature (S MX) is reached. Sensors S3 and S4 can optionally be connected for measurement purposes. S3 can optionally be used as reference sensor for the store emergency shutdown option (OSEM). If heat quantity measurement (OHQM) is activated, sensor S4 has to be connected as return sensor. If the drainback option (ODB) is activated, relay 2 can be used to operate a booster pump by activating the booster function (OBST). VBus 9 10 Arr 1 S1 S3 S1 exemplary Drainback system layout (with booster pump) R1 S4 / TR S2 R1 R2 S4/TR S3 Display Channels Channel Description x* INIT ODB initialisation active x* FLL ODB filling time active x* STAB ODB stabilisation in progress COL x Temperature collector TST x Temperature store S3 x Temperature sensor 3 TSTT x* Temperatur store at the top S4 x Temperature sensor 4 TR x* Temperature return sensor n% x Pump speed R1 hP x Operating hours R1 hP1 x* Operating hours R1 (if OBST is activated) hP2 x* Operating hours R2 (if OBST is activated) kWh x* Heat quantity kWh MWh x* Heat quantity MWh TIME x Time |6 Terminal S1 S2 S3 S3 S4 S4 R1 R1 R1 R2 - Page 37 37 37 37 37 37 37 37 37 38 38 38 38 38 38 34 © RESOL 11157_deltasol_bs_plus.monen.indd S2 DeltaSol® BS Plus Adjustment Channels Channel Description Arr x System DT O x Switch-on temperature difference DT F x Switch-off temperature difference DT S x Nominal temperature difference RIS x Rise control R1 nMN x Minimum pump speed S MX x Maximum store temperature OSEM x Option store emergency shutdown Emergency temperature collector EM x Emergency temperature collector if ODB is activated: OCC x Option collector cooling CMX x* Maximum collector temperature OSYC x Option system cooling DTCO x* Cooling switch-on temperature difference DTCF x* Cooling switch-off temperature difference OSTC x Option store cooling OHOL x* Option holiday cooling THOL x* Holiday cooling temperature OCN x Option minimum limitation CMN x* Minimum collector temperature OCF x Option antifreeze CFR x* Antifreeze temperature O TC x Option tube collector TCST x* OTC starting time TCEN x* OTC ending time TCRU x* OTC runtime TCIN x* OTC standstill interval OHQM x Option heat quantity measurement FMAX x* Maximum flow MEDT x* Antifreeze type MED% x* Antifreeze concentration (only if MEDT = propylene or ethylene) ODB x Drainback option tDTO x* ODB switch-on condition - time period tFLL x* ODB filling time tSTB x* ODB stabilisation time OBST s* Option booster function MAN1 x Manual operation R1 MAN2 x Manual operation R2 ADA1 x HE pump control LANG x Language UNIT x Temperature unit RESE x Reset - back to factory settings W005#### Version number Factory setting 1 6.0 K [12.0 °Ra] 4.0 K [8.0 °Ra] 10.0 K [20.0 °Ra] 2 K [4 °Ra] 30 % 60 °C [140 °F] OFF 130 °C [270 °F] 95 °C [200 °F] OFF 110 °C [230 °F] OFF 20.0 K [40.0 °Ra] 15.0 K [30.0 °Ra] OFF OFF 40 °C [110 °F] OFF 10 °C [50 °F] OFF 4.0 °C [40.0 °F] OFF 07:00 19:00 30 s 30 min OFF 6.0 l 1 45 % OFF 60 s 5.0 min 2.0 min OFF Auto Auto OFF En °C Page 39 39 39 39 39 39 40 40 40 40 41 41 41 41 41 42 42 42 42 42 42 42 44 44 44 44 44 44 44 44 44 45 45 45 45 45 46 46 46 46 46 46 © RESOL 11157_deltasol_bs_plus.monen.indd Legend: Symbol Specification x Channel is available x* Channel is available if the corresponding option is activated. s* System-specific channel, only available if the corresponding option is activated 7| DeltaSol® BS Plus System layout 2 The controller calculates the temperature difference between collector sensor S1 and store sensor S2. If the difference is larger than or identical to the adjusted switchon temperature difference (DT O), the solar pump will be operated by relay 1, and the store will be loaded until the switch-off temperature difference (DT F) or the maximum store temperature (S MX) is reached. Heat exchange from store 1 to store 2 will be operated by relay 2, if the temperature difference between sensors S3 and S4 is larger than or identical to the adjusted switch-on temperature difference (DT3O), until the adjusted minimum (MN3O) and maximum (MX3O) temperature thresholds of the respective stores are reached. S3 can optionally be used as reference sensor for the store emergency shutdown option (OSEM). Arr 2 VBus 9 10 S1 Store 2 Store 1 R1 S3 S4 S2 Display Channels Channel Description x* INIT ODB initialisation active x* FLL ODB filling time active x* STAB ODB stabilisation in progress COL x Temperature collector TST1 x Temperature store 1 base TSTT x Temperature store 1 at the top TST2 x Temperature store 2 base n1 % x Pump speed R1 n2 % x Pump speed R2 h P1 x Operating hours R1 h P2 x Operating hours R2 TIME x Time |8 Terminal S1 S2 S3 S4 R1 R2 R1 R2 - Page 37 37 37 37 37 37 37 38 38 38 38 34 © RESOL 11157_deltasol_bs_plus.monen.indd R2 DeltaSol® BS Plus © RESOL 11157_deltasol_bs_plus.monen.indd Adjustment Channels Channel Description Arr x System DT O x Switch-on temperature difference DT F x Switch-off temperature difference DT S x Nominal temperature difference RIS x Rise control R1 n1MN x Minimum pump speed R1 S MX x Maximum store temperature OSEM x Option store emergency shutdown n2MN s Minimum pump speed R2 Emergency temperature collector EM x Emergency temperature collector if ODB is activated: OCC x Option collector cooling CMX x* Maximum collector temperature OSYC x Option system cooling DTCO x* Cooling switch-on temperature difference DTCF x* Cooling switch-off temperature difference OSTC x Option store cooling OHOL x* Option holiday cooling THOL x* Holiday cooling temperature OCN x Option minimum limitation CMN x* Minimum collector temperature OCF x Option antifreeze CFR x* Antifreeze temperature O TC x Option tube collector TCST x* OTC starting time TCEN x* OTC ending time TCRU x* OTC runtime TCIN x* OTC standstill interval DT3O s Switch-on temperature difference 3 DT3F s Switch-off temperature difference 3 DT3S s Nominal temperature difference 3 RIS3 s Rise control R2 MX3O s Switch-on treshold for maximum temperature MX3F s Switch-off treshold for maximum temperature MN3O s Switch-on treshold for minimum temperature MN3F s Switch-off treshold for minimum temperature ODB x Drainback option tDTO x* ODB switch-on condition - time period tFLL x* ODB filling time tSTB x* ODB stabilisation time MAN1 x Manual operation R1 MAN2 x Manual operation R2 ADA1 x HE pump control ADA2 x HE pump control LANG x Language UNIT x Temperature unit RESE x Reset - back to factory settings W005#### Version number Factory setting 2 6.0 K [12.0 °Ra] 4.0 K [8.0 °Ra] 10.0 K [20.0 °Ra] 2 K [4 °Ra] 30 % 60 °C [140 °F] OFF 30 % 130 °C [270 °F] 95 °C [200 °F] OFF 110 °C [230 °F] OFF 20.0 K [40.0 °Ra] 15.0 K [30.0 °Ra] OFF OFF 40 °C [110 °F] OFF 10 °C [50 °F] OFF 4.0 °C [40.0 °F] OFF 07:00 19:00 30 s 30 min 6.0 K [12.0 °Ra] 4.0 K [8.0 °Ra] 10.0 K [20.0 °Ra] 2 K [4 °Ra] 60.0 °C [140.0 °F] 58.0 °C [136.0 °F] 5.0 °C [40.0 °F] 10.0 °C [50.0 °F] OFF 60 s 5.0 min 2.0 min Auto Auto OFF OFF En °C Page 39 39 39 39 39 39 40 40 10 40 40 41 41 41 41 41 42 42 42 42 42 42 42 44 44 44 44 44 10 10 10 10 11 11 11 11 45 45 45 45 46 46 46 46 46 46 46 Legend: Symbol Specification x Channel is available x* Channel is available if the corresponding option is activated. s Channel is specifically available in this system layout 9| DeltaSol® BS Plus System-specific functions The following adjustments are used for the specific function in system layout 2. ∆T control for the heat exchange between 2 stores DT3O: Switch-on temperature diff. Adjustment range: 1.0 ... 20.0 K [2.0 ... 40.0°Ra] in steps of 0.5 K [1 °Ra] Factory setting: 6.0 K [12.0°Ra] DT3F: Switch-off temperature diff. Adjustment range: 0.5 ... 19.5 K [1.0 ... 39.0°Ra] in steps of 0.5 K [1 °Ra] Factory setting: 4.0 K [8.0°Ra] Pump speed control DT3S: Nominal temperature difference Adjustment range: 1.5 ... 30.0 K [3.0 ... 60.0 °Ra] in steps of 0.5 K [1 °Ra] Factory setting: 10.0 K [20.0 °Ra] RIS3: Rise Adjustment range: 1 ... 20 K[2 ... 40 °Ra] in steps of 1 K [2 °Ra] Factory setting: 2 K [4 °Ra] Reference sensors for this function are S3 and S4. In system layout 2 the controller is equipped with an additional differential control for heat exchange between two stores. The basic differential function is adjusted using the switch-on (DT3O) and switch-off (DT3F) temperature differences. When the temperature difference exceeds the switch-on temperature difference, relay 2 switches on. If the temperature difference then falls below the adjusted switch-off temperature difference, relay 2 switches off. Note: The switch-on temperature difference must be at least 0.5 K [1 °Ra] higher than the switch-off temperature difference. Note: For pump speed control of the heat exchange pump, the operation mode of relay 2 (MAN2) must be set to Auto. When the switch-on temperature difference is reached, the pump is activated at full speed for 10 seconds.Then, the speed is reduced to the minimum pump speed value (n2MN). If the temperature difference reaches the adjusted nominal temperature difference (DT3S), the pump speed increases by one step (10 %). If the difference increases by the adjustable rise value, the pump speed increases by 10 % respectively until the maximum pump speed of 100 % is reached.The response of the controller can be adapted via the parameter RIS3. Note: The nominal temperature difference must be at least 0.5 K [1 °Ra] higher than the switch-on temperature difference. Minimum pump speed | 10 A relative minimum pump speed can be allocated to the output R2 via the adjustment channel n2MN. Note: When loads which are not speed-controlled (e.g. valves) are used, the value must be set to 100 % in order to deactivate pump speed control. © RESOL 11157_deltasol_bs_plus.monen.indd n2MN: Pump speed control Adjustment range: 30 ... 100 in steps of 5 % Factory setting: 30 DeltaSol® BS Plus Maximum temperature limitation MX3O / MX3F: Maximum temperature limitation Adjustment range: 0.0 ... 95.0 °C [30.0 ... 200.0 °F] in steps of 0.5 °C [1.0 °F] Factory setting: MX3O: 60.0 °C [140.0 °F] MX3F: 58.0 °C [136.0 °F] Minimum temperature limitation MN3O / MN3F: Minimum temperature limitation Adjustment range: 0.0 ... 90.0 °C [30.0 ...190.0 °F] in steps of 0.5 °C [1.0 °F] Factory setting (Arr = 2 only): MN3O: 5.0 °C [40.0 °F] MN3F: 10.0 °C [50.0 °F] Minimum and maximum temperature limits can be set for the heat exchange function. The maximum temperature limitation uses sensor 4 as reference sensor. The maximum temperature limitation function provides a maximum temperature setting, usually to reduce scald risk in a storage store. If MX3O is exceeded, relay 2 is switched off until the temperature at sensor 4 falls below MX3F. The minimum temperature limitation uses sensor 3 as reference sensor. The minimum temperature limitation function provides a minimum temperature setting for the heat source in system layout 2. If the temperature at sensor 3 falls below MN3O, relay 2 is switched off until the temperature at sensor 3 exceeds MN3F. © RESOL 11157_deltasol_bs_plus.monen.indd Both switch-on and switch-off temperature differences DT3O and DT3F are valid for the maximum and minimum temperature limitation. 11 | DeltaSol® BS Plus System layout 3 The controller calculates the temperature difference between collector sensor S1 and store sensor S2. If the difference is larger than or identical to the adjusted switchon temperature difference (DT O), the solar pump will be operated by relay 1, and the store will be loaded until the switch-off temperature difference (DT F) or the maximum store temperature (S MX) is reached. Sensor S3 is used for a thermostatic function, which operates relay 2 for afterheating or heat dump purposes, when the adjusted thermostat switch-on temperature (AH O) is reached. This function can optionally be combined with up to three adjustable time frames. Sensor S3 can also be optionally used as a reference sensor for the thermal disinfection function OTD or the store emergency shutdown option (OSEM). Sensor S4 can optionally be connected for measurement purposes. If heat quantity measurement (OHQM) is activated, sensor S4 has to be connected as return sensor. VBus 9 10 Arr 3 S1 R1 S3 R2 S4 / TR Display Channels Channel Description x* INIT ODB initialisation active x* FLL ODB filling time active x* STAB ODB stabilisation in progress COL x Temperature collector TSTB x Temperature store 1 base TSTT x Temperature store 1 at the top s* TDIS Thermal disinfection temperature S4 x Temperature sensor 4 TR x* Temperature return sensor n1 % x Pump speed R1 h P1 x Operating hours R1 h P2 x Operating hours R2 x* kWh Heat quantity kWh x* MWh Heat quantity MWh s* CDIS Countdown of monitoring period s* SDIS Starting time display s* DDIS Heating period display TIME x Time | 12 Terminal S1 S2 S3 S3 S4 S4 R1 R1 R2 - Page 37 37 37 37 37 37 37 37 37 38 38 38 38 38 38 38 38 34 © RESOL 11157_deltasol_bs_plus.monen.indd S2 © RESOL 11157_deltasol_bs_plus.monen.indd DeltaSol® BS Plus Adjustment Channels Channel Description Arr x System DT O x Switch-on temperature difference DT F x Switch-off temperature difference DT S x Nominal temperature difference RIS x Rise control R1 n1MN x Minimum pump speed R1 S MX x Maximum store temperature OSEM x Option store emergency shutdown Emergency temperature collector EM x Emergency temperature collector if ODB is activated: OCC x Option collector cooling CMX x* Maximum collector temperature OSYC x Option system cooling DTCO x* Cooling switch-on temperature difference DTCF x* Cooling switch-off temperature difference OSTC x Option store cooling OHOL x* Option holiday cooling THOL x* Holiday cooling temperature OCN x Option minimum limitation CMN x* Minimum collector temperature OCF x Option antifreeze CFR x* Antifreeze temperature O TC x Option tube collector TCST x* OTC starting time TCEN x* OTC ending time TCRU x* OTC runtime TCIN x* OTC standstill interval OHQM x Option heat quantity measurement FMAX x* Maximum flow MEDT x* Antifreeze type MED% x* Antifreeze concentration AH O s Switch-on temp. for thermostat 1 AH F s Switch-off temp. for thermostat 1 t1 O s Switch-on time 1 thermostat t1 F s Switch-off time 1 thermostat t2 O s Switch-on time 2 thermostat t2 F s Switch-off time 2 thermostat t3 O s Switch-on time 3 thermostat t3 F s Switch-off time 3 thermostat ODB x Drainback option tDTO x* ODB switch-on condition - time period tFLL x* ODB filling time tSTB x* ODB stabilisation time OTD s Option thermal disinfection PDIS s* Monitoring period DDIS s* Heating period TDIS s* Disinfection temperature SDIS s* Starting time MAN1 x Manual operation R1 MAN2 x Manual operation R2 ADA1 x HE pump control LANG x Language UNIT x Temperature unit RESE x Reset - back to factory settings W005#### Version number Factory setting 3 6.0 K [12.0 °Ra] 4.0 K [8.0 °Ra] 10.0 K [20.0 °Ra] 2 K [4 °Ra] 30 % 60 °C [140 °F] OFF 130 °C [270 °F] 95 °C [200 °F] OFF 110 °C [230 °F] OFF 20.0 K [40.0 °Ra] 15.0 K [30.0 °Ra] OFF OFF 40 °C [110 °F] OFF 10 °C [50 °F] OFF 4.0 °C [40.0 °F] OFF 07:00 19:00 30 s 30 min OFF 6.0 l 1 45 % 40 °C [110 °F] 45 °C [120 °F] 00:00 00:00 00:00 00:00 00:00 00:00 OFF 60 s 5.0 min 2.0 min OFF 01:00 01:00 60 °C [140 °F] 00:00 Auto Auto OFF En °C Page 39 39 39 39 39 39 40 40 40 40 41 41 41 41 41 42 42 42 42 42 42 42 44 44 44 44 44 44 44 44 44 14 14 14 14 14 14 14 14 45 45 45 45 15 15 15 15 15 46 46 46 46 46 46 Legend: Symbol x x* s s* Specification Channel is available Channel is available if the corresponding option is activated. Channel is specifically available in this system layout System-specific channel, only available if the corresponding option is activated 13 | DeltaSol® BS Plus System-specific functions The following functions are exclusively available in system layout 3.The corresponding channels will not be available in any other system layout. Thermostat function Afterheating The thermostat function works independently from the solar operation and can be used for using surplus energy or for afterheating. • AH O< AH F thermostat function for afterheating • AH O> AH F thermostat function for using surplus energy Use of surplus energy The symbol will be shown on the display if the second relay output is activated. Reference sensor for the thermostat function is S3! AH O: Thermostat switch-on temp. Adjustment range: 0.0 ... 95.0 °C [30.0 ... 200.0 °F] in steps of 0.5 °C [1.0 °F] Factory setting: 40.0 °C [110.0°F] AH F: Thermostat switch-off temp. Adjustment range: 0.0 ... 95.0 °C [30.0 ... 200.0 °F] in steps of 0.5 °C [1.0 °F] Factory setting: 45.0 °C [120.0 °F] t1 F, t2 F, t3 F: Thermostat switch-off time Adjustment range: 00:00 ... 23:45 Factory setting: 00:00 | 14 In order to block the thermostat function for a certain period, there are three time frames t1 ... t3. If the function should be active between 6:00 and 9:00, set t1 O to 6:00 and t1 F to 9:00. If all time frames are set to 00:00 o’clock, the thermostat function is continuously activated (factory setting). © RESOL 11157_deltasol_bs_plus.monen.indd t1 O, t2 O, t3 O: Thermostat switch-on time Adjustment range: 00:00 ... 23:45 Factory setting: 00:00 DeltaSol® BS Plus Option:Thermal disinfection of the upper DHW zone (OTD) OTD Thermal disinfection function Adjustment range: ON / OFF Factory setting: OFF PDIS Monitoring period Adjustment range: 0 ... 30:0 ... 24 h (dd:hh) Factory setting: 01:00 DDIS Heating period Adjustment range: 00:00 ... 23:59 (hh:mm) Factory setting: 01:00 TDIS Disinfection temperature Adjustment range: 0 ... 95 °C [30 ... 200 °F] in steps of 2 °C [2 °F] Factory setting: 60 °C [140 °F] This function is used for protecting the upper store zone against Legionella by activating the afterheating. Reference sensor for the thermal disinfection is S3! ÎÎ To activate the function, select “On” in the OTD channel. For thermal disinfection, the temperature in the upper DHW store zone has to be monitored. This protection is ensured when, during the monitoring period (PDIS), the disinfection temperature (TDIS) is continuously exceeded for the entire heating period (DDIS). S3 is used as the reference sensor and displayed as TSTT. If OTD is activated, PDIS will start as soon as the temperature at S3 falls below TDIS. The display channel CDIS appears, counting backwards the remaining time of PDIS. If, during the monitoring period, the temperature at S3 exceeds TDIS continuously for the duration of DDIS, thermal disinfection is considered complete and a new monitoring period begins. If CDIS counts down to 00:00, relay 2 will be operated in order to use the afterheating for thermal disinfection. CDIS will then be replaced with a display channel DDIS showing the adjusted heating period. DDIS will start counting down the heating period as soon as TDIS is exceeded at S3. As long as DDIS is active, the temperature at S3 will be displayed as TDIS instead of TSTT. If, during DDIS, the temperature at S3 exceeds TDIS by more than 5 K [10 °Ra], relay 2 is switched off until the temperature falls below TDIS + 2 K [4 °Ra]. If, during DDIS, the temperature at S3 falls below TDIS, the heating period will restart. DDIS can only be completed when TDIS is exceeded without interruption. Due to the flexible control logic, the exact time of thermal disinfection is not predictable. In order to set a fixed time for the disinfection to be run, the starting delay SDIS must be employed: © RESOL 11157_deltasol_bs_plus.monen.indd Thermal disinfection with starting delay SDIS Starting time Adjustment range: 00:00 ... 24:00 (o´clock) in steps of: 00:01 Factory setting: 00:00 When a starting time for thermal disinfection with starting delay is adjusted in SDIS, the thermal disinfection will be delayed until that time, even after the CDIS has counted down to 00:00. If CDIS ends, for example, at 12:00 o‘clock, and SDIS has been set to 18:30, relay 2 will be operated with a delay of 6.5 hours at 18:30 instead of 12:00. During the waiting time, SDIS is displayed with the adjusted starting time (flashing). If, during the waiting time, the temperature at S3 exceeds TDIS for the adjusted heating period DDIS, thermal disinfection is considered complete and a new monitoring period begins. If the starting time is adjusted to 00:00 (factory setting), the delay function is inactive. Upon delivery, OTD is deactivated. The adjustment values PDIS, TDIS, DDIS and SDIS are displayed after the option has been activated. After the thermal disinfection function has been completed, the values will be “hidden” and the monitoring period will be displayed. 15 | DeltaSol® BS Plus System layout 4 The controller calculates the temperature differences between collector sensor S1 and store sensors S2 and S3. If the differences are larger than or identical to the adjusted switch-on temperature differences (DT1O / DT2O), the solar pump will be operated by relay 1, and the respective store zone will be loaded until the switch-off temperature differences (DT1F / DT2F) or the maximum store tempera- tures (S1MX / S2MX) are reached.The priority logic causes priority loading of the upper zone of the store, if possible. The 3-way-valve will be operated by relay 2 then. Sensor S4 can optionally be connected for measurement purposes. If heat quantity measurement (OHQM) is activated, sensor S4 has to be connected as return sensor. VBus 9 10 Arr 4 S1 R1 S4 / TR Display Channels Channel Description COL x Temperature collector TSTB x Temperature store 1 base TSTT x Temperature store 1 at the top S4 x Temperature sensor 4 TR x* Temperature return sensor n% x Pump speed relay hP1 x Operating hours R1 hP2 x Operating hours R2 x* kWh Heat quantity kWh x* MWh Heat quantity MWh TIME x Time | 16 S3 S2 Terminal S1 S2 S3 S4 S4 R1 R1 R2 - Page 37 37 37 37 37 38 38 38 38 38 34 © RESOL 11157_deltasol_bs_plus.monen.indd R2 DeltaSol® BS Plus Adjustment Channels Channel Description Arr x System nMN x Minimum pump speed DT1O x Switch-on temperature difference 1 DT1F x Switch-off temperature difference 1 DT1S x Nominal temperature difference 1 RIS1 x Rise control R1 S1 MX x Maximum temperature store 1 DT2O x Switch-on temperature difference 2 DT2F x Switch-off temperature difference 2 DT2S x Nominal temperature difference 2 RIS2 x Rise control R2 S2MX x Maximum temperature store 2 EM x Emergency temperature collector OCC x Option collector cooling CMX x* Maximum collector temperature OSYC x Option system cooling DTCO x* Cooling switch-on temperature difference DTCF x* Cooling switch-off temperature difference OSTC x Option store cooling OHOL x* Option holiday cooling THOL x* Holiday cooling temperature OCN x Option minimum limitation CMN x* Minimum collector temperature OCF x Option antifreeze CFR x* Antifreeze temperature PRIO x Priority tLB x Break time tRUN x Circulation runtime O TC x Option tube collector TCST x* OTC starting time TCEN x* OTC ending time TCRU x* OTC runtime TCIN x* OTC standstill interval OHQM x Option heat quantity measurement FMAX x* Maximum flow MEDT x* Antifreeze type MED% x* Antifreeze concentration (only if MEDT = propylene or ethylene) MAN1 x Manual operation R1 MAN2 x Manual operation R2 ADA1 x HE pump control LANG x Language UNIT x Temperature unit RESE x Reset - back to factory settings W005#### Version number Factory setting 4 30 % 6.0 K [12.0 °Ra] 4.0 K [8.0 °Ra] 10.0 K [20.0 °Ra] 2 K [4 °Ra] 60 °C [140 °F] 6.0 K [12.0 °Ra] 4.0 K [8.0 °Ra] 10.0 K [20.0 °Ra] 2 K [4 °Ra] 60 °C [140 °F] 130 °C [270 °F] OFF 110 °C [230 °F] OFF 20.0 K [40.0 °Ra] 15.0 K [30.0 °Ra] OFF OFF 40 °C [110 °F] OFF 10 °C [50 °F] OFF 4.0 °C [40.0 °F] 2 2 min 15 min OFF 07:00 19:00 30 s 30 min OFF 6.0 l 1 45 % Auto Auto OFF En °C Page 39 39 39 39 39 39 40 39 39 39 39 40 40 41 41 41 41 41 42 42 42 42 42 42 42 43 43 43 44 44 44 44 44 44 44 44 44 46 46 46 46 46 46 © RESOL 11157_deltasol_bs_plus.monen.indd Legend: Symbol Specification x Channel is available x* Channel is available if the corresponding option is activated. 17 | DeltaSol® BS Plus System layout 5 The controller calculates the temperature differences between collector sensor S1 and store sensors S2 and S3. If the differences are larger than or identical to the adjusted switch-on temperature differences (DT1O / DT2O), the solar pump will be operated by relay 1, and the respective store will be loaded until the switch-off temperature differences (DT1F / DT2F) or the maximum store temperatures (S1MX / S2MX) are reached. The priority logic causes priority loading of store 1, if possible. For loading store 2 the 3-way-valve will be operated by relay 2. Sensor S4 can optionally be connected for measurement purposes. If heat quantity measurement (OHQM) is activated, sensor S4 has to be connected as return sensor. VBus 9 10 Arr 5 S1 R2 Store 1 Store 2 R1 S4 / TR Display Channels Channel Description COL x Temperature collector TST1 x Temperature store 1 base TST2 x Temperature store 2 base S4 x Temperature sensor 4 TR x* Temperature return sensor n% x Pump speed relay hP1 x Operating hours R1 hP2 x Operating hours R2 x* kWh Heat quantity kWh x* MWh Heat quantity MWh x TIME Time | 18 S3 Terminal S1 S2 S3 S4 S4 R1 R1 R2 - Page 37 37 37 37 37 38 38 38 38 38 34 © RESOL 11157_deltasol_bs_plus.monen.indd S2 DeltaSol® BS Plus Adjustment Channels Channel Description Arr x System nMN x Minimum pump speed DT1O x Switch-on temperature difference 1 DT1F x Switch-off temperature difference 1 DT1S x Nominal temperature difference 1 RIS1 x Rise control R1 S1 MX x Maximum temperature store 1 DT2O x Switch-on temperature difference 2 DT2F x Switch-off temperature difference 2 DT2S x Nominal temperature difference 2 RIS2 x Rise control R2 S2MX x Maximum temperature store 2 EM x Emergency temperature collector OCC x Option collector cooling CMX x* Maximum collector temperature OSYC x Option system cooling DTCO x* Cooling switch-on temperature difference DTCF x* Cooling switch-off temperature difference OSTC x Option store cooling OHOL x* Option holiday cooling THOL x* Holiday cooling temperature OCN x Option minimum limitation CMN x* Minimum collector temperature OCF x Option antifreeze CFR x* Antifreeze temperature PRIO x Priority tLB x Break time tRUN x Circulation runtime O TC x Option tube collector TCST x* OTC starting time TCEN x* OTC ending time TCRU x* OTC runtime TCIN x* OTC standstill interval OHQM x Option heat quantity measurement FMAX x* Maximum flow MEDT x* Antifreeze type MED% x* Antifreeze concentration (only if MEDT = propylene or ethylene) MAN1 x Manual operation R1 MAN2 x Manual operation R2 ADA1 x HE pump control LANG x Language UNIT x Temperature unit RESE x Reset - back to factory settings W005#### Version number Factory setting 5 30 % 6.0 K [12.0 °Ra] 4.0 K [8.0 °Ra] 10.0 K [20.0 °Ra] 2 K [4 °Ra] 60 °C [140 °F] 6.0 K [12.0 °Ra] 4.0 K [8.0 °Ra] 10.0 K [20.0 °Ra] 2 K [4 °Ra] 60 °C [140 °F] 130 °C [270 °F] OFF 110 °C [230 °F] OFF 20.0 K [40.0 °Ra] 15.0 K [30.0 °Ra] OFF OFF 40 °C [110 °F] OFF 10 °C [50 °F] OFF 4.0 °C [40.0 °F] 1 2 min 15 min OFF 07:00 19:00 30 s 30 min OFF 6.0 l 1 45 % Auto Auto OFF En °C Page 39 39 39 39 39 39 40 39 39 39 39 40 40 41 41 41 41 41 42 42 42 42 42 42 42 43 43 43 44 44 44 44 44 44 44 44 44 46 46 46 46 46 46 © RESOL 11157_deltasol_bs_plus.monen.indd Legend: Symbol Specification x Channel is available x* Channel is available if the corresponding option is activated. 19 | DeltaSol® BS Plus System layout 6 The controller calculates the temperature differences between collector sensor S1 and store sensors S2 and S3. If the differences are larger than or identical to the adjusted switch-on temperature differences (DT1O / DT2O), the solar pumps will be operated by relay 1 and / or relay 2, and the respective store will be loaded until the switch-off temperature differences (DT1F / DT2F) or the maximum store temperatures (S1MX / S2MX) are reached.The priority logic causes priority loading of the selected store (PRIO), if possible. Loading both stores simultaneously is possible as well (PRIO = 0). Sensor S4 can optionally be connected for measurement purposes or used as reference sensor for the store emergency shutdown option (OSEM). VBus 9 10 Arr 6 S1 S4 R2 Store 1 Store 2 S2 Display Channels Channel Description COL x Temperature collector TST1 x Temperature store 1 base TST2 x Temperature store 2 base S4 x Temperature sensor 4 TSTT x* Temperature store at the top n1 % x Pump speed R1 n2 % x Pump speed R2 h P1 x Operating hours R1 h P2 x Operating hours R2 TIME x Time | 20 S3 Terminal S1 S2 S3 S4 S4 R1 R2 R1 R2 - Page 37 37 37 37 37 38 38 38 38 34 © RESOL 11157_deltasol_bs_plus.monen.indd R1 DeltaSol® BS Plus Adjustment Channels Channel Description Arr x System DT1O x Switch-on temperature difference 1 DT1F x Switch-off temperature difference 1 DT1S x Nominal temperature difference 1 RIS1 x Rise control R1 n1MN x Minimum pump speed R1 S1 MX x Maximum temperature store 1 OSEM x Option store emergency shutdown DT2O x Switch-on temperature difference 2 DT2F x Switch-off temperature difference 2 DT2S x Nominal temperature difference 2 RIS2 x Rise control R2 n2MN x Minimum pump speed R2 S2MX x Maximum temperature store 2 EM x Emergency temperature collector OCC x Option collector cooling CMX x* Maximum collector temperature OSYC x Option system cooling DTCO x* Cooling switch-on temperature difference DTCF x* Cooling switch-off temperature difference OSTC x Option store cooling OHOL x* Option holiday cooling THOL x* Holiday cooling temperature OCN x Option minimum limitation CMN x* Minimum collector temperature OCF x Option antifreeze CFR x* Antifreeze temperature PRIO x Priority tLB x Break time tRUN x Circulation runtime DTSE x* Spread temperature difference O TC x Option tube collector TCST x* OTC starting time TCEN x* OTC ending time TCRU x* OTC runtime TCIN x* OTC standstill interval MAN1 x Manual operation R1 MAN2 x Manual operation R2 ADA1 x HE pump control ADA2 x HE pump control LANG x Language UNIT x Temperature unit RESE x Reset - back to factory settings W005#### Version number Factory setting 6 6.0 K [12.0 °Ra] 4.0 K [8.0 °Ra] 10.0 K [20.0 °Ra] 2 K [4 °Ra] 30 % 60 °C [140 °F] OFF 6.0 K [12.0 °Ra] 4.0 K [8.0 °Ra] 10.0 K [20.0 °Ra] 2 K [4 °Ra] 30 % 60 °C [140 °F] 130 °C [270 °F] OFF 110 °C [230 °F] OFF 20.0 K [40.0 °Ra] 15.0 K [30.0 °Ra] OFF OFF 40 °C [110 °F] OFF 10 °C [50 °F] OFF 4.0 °C [40.0 °F] 1 2 min 15 min 40 K [70 °Ra] OFF 07:00 19:00 30 s 30 min Auto Auto OFF OFF En °C Page 39 39 39 39 39 39 40 40 39 39 39 39 39 40 40 41 41 41 41 41 42 42 42 42 42 42 42 43 43 43 43 44 44 44 44 44 46 46 46 46 46 46 46 © RESOL 11157_deltasol_bs_plus.monen.indd Legend: Symbol Specification x Channel is available x* Channel is available if the corresponding option is activated. 21 | DeltaSol® BS Plus System layout 7 The controller calculates the temperature differences between the collector sensors S1 and S3 and the store sensor S2. If the differences are larger than or identical to the adjusted switch-on temperature difference (DT O), the respective solar pump will be operated by relay 1 and / or relay 2, and the store will be loaded until the switch-off temperature difference (DT F) or the maximum store temperature (S MX) is reached. Sensor S4 can optionally be connected for measurement purposes or used as reference sensor for the store emergency shutdown option (OSEM). Arr 7 VBus 9 10 S1 R1 S3 R2 Display Channels Channel Description COL1 x Temperature collector 1 TST x Temperature store COL2 x Temperature collector 2 S4 x Temperature sensor 4 TSTT x* Temperature store at the top n1 % x Pump speed R1 n2 % x Pump speed R2 h P1 x Operating hours R1 h P2 x Operating hours R2 TIME x Time | 22 Terminal S1 S2 S3 S4 S4 R1 R2 R1 R2 - Page 37 37 37 37 37 38 38 38 38 34 © RESOL 11157_deltasol_bs_plus.monen.indd S2 DeltaSol® BS Plus Adjustment Channels Channel Description Arr x System DT O x Switch-on temperature difference DT F x Switch-off temperature difference DT S x Nominal temperature difference RIS x Rise control R1 / R2 n1MN x Minimum pump speed R1 S MX x Maximum store temperature OSEM x Option store emergency shutdown n2MN x Minimum pump speed R2 EM1 x Emergency temperature collector EM2 x Emergency temperature collector OCC1 x Option collector cooling collector 1 CMX1 x* Maximum temperature collector 1 OCC2 x Option collector cooling collector 2 CMX2 x* Maximum temperature collector 2 OSYC x Option system cooling DTCO x* Cooling switch-on temperature difference DTCF x* Cooling switch-off temperature difference OSTC x Option store cooling OHOL x* Option holiday cooling THOL x* Holiday cooling temperature OCN1 x Option minimum limitation collector 1 CMN1 x* Minimum temperature collector 1 OCN2 x Option minimum limitation collector 2 CMN2 x* Minium temperature collector 2 OCF1 x Option antifreeze collector 1 CFR1 x* Antifreeze temperature collector 1 OCF2 x Option antifreeze collector 2 CFR2 x* Antifreeze temperature collector 2 O TC x Option tube collector TCST x* OTC starting time TCEN x* OTC ending time TCRU x* OTC runtime TCIN x* OTC standstill interval MAN1 x Manual operation R1 MAN2 x Manual operation R2 ADA1 x HE pump control ADA2 x HE pump control LANG x Language UNIT x Temperature unit RESE x Reset - back to factory settings W005#### Version number Factory setting 7 6.0 K [12.0 °Ra] 4.0 K [8.0 °Ra] 10.0 K [20.0 °Ra] 2 K [4 °Ra] 30 % 60 °C [140 °F] OFF 30 % 130 °C [270 °F] 130 °C [270 °F] OFF 110 °C [230 °F] OFF 110 °C [230 °F] OFF 20.0 K [40.0 °Ra] 15.0 K [30.0 °Ra] OFF OFF 40 °C [110 °F] OFF 10 °C [50 °F] OFF 10 °C [50 °F] OFF 4.0 °C [40.0 °F] OFF 4.0 °C [40.0 °F] OFF 07:00 19:00 30 s 30 min Auto Auto OFF OFF En °C Page 39 39 39 39 39 39 40 40 39 40 40 41 41 41 41 41 41 41 42 42 42 42 42 42 42 42 42 42 42 44 44 44 44 44 46 46 46 46 46 46 46 © RESOL 11157_deltasol_bs_plus.monen.indd Legend: Symbol Specification x Channel is available x* Channel is available if the corresponding option is activated. 23 | DeltaSol® BS Plus System layout 8 The controller calculates the temperature difference between collector sensor S1 and store sensor S2. If the difference is larger than or identical to the adjusted switchon temperature difference (DT O), the solar pump will be operated by relay 1, and the store will be loaded until the switch-off temperature difference (DT F) or the maximum store temperature (S MX) is reached. A solid fuel boiler will be operated by relay 2, if the temperature difference between sensors S4 and S3 is larger than or identical to the adjusted switch-on temperature difference (DT3O), until the adjusted minimum (MN3O) and maximum (MX3O) temperature thresholds of the fuel boiler and the store are reached. S3 can optionally be used as reference sensor for the store emergency shutdown option (OSEM). VBus 9 10 Arr 8 S1 R1 S4 S3 Display Channels Channel Description x* INIT ODB initialisation active x* FLL ODB filling time active x* STAB ODB stabilisation in progress COL x Temperature collector TSTB x Temperature store 1 base TSTT x Temperature store 1 at the top TSFB x Temperature solid fuel boiler n1 % x Pump speed R1 n2 % x Pump speed R2 h P1 x Operating hours R1 h P2 x Operating hours R2 TIME x Time | 24 R2 Terminal S1 S2 S3 S4 R1 R2 R1 R2 - Page 37 37 37 37 37 37 37 38 38 38 38 34 © RESOL 11157_deltasol_bs_plus.monen.indd S2 DeltaSol® BS Plus © RESOL 11157_deltasol_bs_plus.monen.indd Adjustment Channels Channel Description Arr x System DT O x Switch-on temperature difference DT F x Switch-off temperature difference DT S x Nominal temperature difference RIS x Rise control R1 n1MN x Minimum pump speed R1 S MX x Maximum store temperature OSEM x Option store emergency shutdown n2MN s Minimum pump speed R2 Emergency temperature collector EM x Emergency temperature collector if ODB is activated: OCC x Option collector cooling CMX x* Maximum collector temperature OSYC x Option system cooling DTCO x* Cooling switch-on temperature difference DTCF x* Cooling switch-off temperature difference OSTC x Option store cooling OHOL x* Option holiday cooling THOL x* Holiday cooling temperature OCN x Option minimum limitation CMN x* Minimum collector temperature OCF x Option antifreeze CFR x* Antifreeze temperature O TC x Option tube collector TCST x* OTC starting time TCEN x* OTC ending time TCRU x* OTC runtime TCIN x* OTC standstill interval DT3O s Switch-on temperature difference 3 DT3F s Switch-off temperature difference 3 DT3S s Nominal temperature difference 3 RIS3 s Rise control R2 MX3O s Switch-on treshold for maximum temperature MX3F s Switch-off treshold for maximum temperature MN3O s Switch-on treshold for minimum temperature MN3F s Switch-off treshold for minimum temperature ODB x Drainback option tDTO x* ODB switch-on condition - time period tFLL x* ODB filling time tSTB x* ODB stabilisation time MAN1 x Manual operation R1 MAN2 x Manual operation R2 ADA1 x HE pump control ADA2 x HE pump control LANG x Language UNIT x Temperature unit RESE x Reset - back to factory settings W005#### Version number Factory setting 8 6.0 K [12.0 °Ra] 4.0 K [8.0 °Ra] 10.0 K [20.0 °Ra] 2 K [4 °Ra] 30 % 60 °C [140 °F] OFF 30 % 130 °C [270 °F] 95 °C [200 °F] OFF 110 °C [230 °F] OFF 20.0 K [40.0 °Ra] 15.0 K [30.0 °Ra] OFF OFF 40 °C [110 °F] OFF 10 °C [50 °F] OFF 4.0 °C [40.0 °F] OFF 07:00 19:00 30 s 30 min 6.0 K [12.0 °Ra] 4.0 K [8.0 °Ra] 10.0 K [20.0 °Ra] 2 K [4 °Ra] 60.0 °C [140.0 °F] 58.0 °C [136.0 °F] 60.0 °C [140.0 °F] 65.0 °C [150.0 °F] OFF 60 s 5.0 min 2.0 min Auto Auto OFF OFF En °C Page 39 39 39 39 39 39 40 40 26 40 40 41 41 41 41 41 42 42 42 42 42 42 42 44 44 44 44 44 26 26 26 26 27 27 27 27 45 45 45 45 46 46 46 46 46 46 46 Legend: Symbol Specification x Channel is available x* Channel is available if the corresponding option is activated. s Channel is specifically available in this system layout 25 | DeltaSol® BS Plus System-specific functions The following adjustments are used for the specific functions in system layout 8. ∆T control for afterheating by solid fuel boiler Reference sensors for this function are S4 and S3. In system layout 8, the controller is equipped with an additional differential control for heat exchange from a solid fuel boiler (e.g. woodstove). The basic differential function is adjusted using the switch-on (DT3O) and switch-off (DT3F) temperature differences. When the switch-on difference is reached, relay 2 switches on. When the temperature difference falls below the adjusted switch-off temperature difference, relay 2 switches off. DT3F: Switch-off temperature diff. Adjustment range: 0.5 ... 19.5 K [1.0 ... 39.0°Ra] in steps of 0.5 K [1 °Ra] Factory setting: 4.0 K [8.0°Ra] Pump speed control DT3S: Nominal temperature difference Adjustment range: 1.5 ... 30.0 K [3.0 ... 60.0 °Ra] in steps of 0.5 K [1 °Ra] Factory setting: 10.0 K [20.0 °Ra] RIS3: Rise Adjustment range: 1 ... 20 K [2 ... 40 °Ra] in steps of 1 K [2 °Ra] Factory setting: 2 K [4 °Ra] Minimum pump speed n2MN: Pump speed control Adjustment range: 30 ... 100 in steps of 5 % Factory setting: 30 | 26 Note: The switch-on temperature difference must be at least 0.5 K [1 °Ra] higher than the switch-off temperature difference. Note: For pump speed control of the solid fuel boiler pump, the operation mode of relay 2 (MAN2) must be set to Auto. When the switch-on temperature difference is reached, the pump is activated at full speed for 10 seconds.Then, the speed is reduced to the minimum pump speed value (n2MN). If the temperature difference reaches the adjusted nominal temperature difference (DT3S), the pump speed increases by one step (10 %). If the difference increases by the adjustable rise value, the pump speed increases by 10 % respectively until the maximum pump speed of 100 % is reached.The response of the controller can be adapted via the parameter RIS3. Note: The nominal temperature difference must be at least 0.5 K [1 °Ra] higher than the switch-on temperature difference. A relative minimum pump speed can be allocated to the output R2 via the adjustment channel n2MN. Note: When loads which are not speed-controlled (e.g. valves) are used, the value must be set to 100 % in order to deactivate pump speed control. © RESOL 11157_deltasol_bs_plus.monen.indd DT3O: Switch-on temperature diff. Adjustment range: 1.0 ... 20.0 K [2.0 ... 40.0°Ra] in steps of 0.5 K [1 °Ra] Factory setting: 6.0 K [12.0°Ra] DeltaSol® BS Plus Maximum temperature limitation MX3O / MX3F: Maximum temperature limitation Adjustment range: 0.0 ... 95.0 °C [30.0 ... 200.0 °F] in steps of 0.5 °C [1 °F] Factory setting: MX3O: 60.0 °C [140.0 °F] MX3F: 58.0 °C [136.0 °F] Minimum temperature limitation MN3O / MN3F: Minimum temperature limitation Adjustment range: 0.0 ... 90.0 °C [30.0 ...190.0 °F] in steps of 0.5 °C [1 °F] Factory setting (Arr = 8 only): MN3O: 60.0 °C [140.0 °F] MN3F: 65.0 °C [150.0 °F] Minimum and maximum temperature limits can be set for the solid fuel boiler. The maximum temperature limitation function provides a maximum temperature setting, usually to reduce scald risk in a storage store. If MX3O is exceeded, relay 2 is switched off until the sensor falls below MX3F. TIn Arr 8, this function uses sensor 3 as reference sensor. The minimum temperature limitation uses sensor 4 as reference sensor. The minimum temperature limitation function provides a minimum temperature setting for the solid fuel boiler in system layout 8. If the temperature at sensor 4 falls below MN3O, relay 2 is switched off until the temperature exceeds MN3F again. © RESOL 11157_deltasol_bs_plus.monen.indd Both switch-on and switch-off temperature differences DT3O and DT3F are valid for the maximum and minimum temperature limitation. 27 | DeltaSol® BS Plus System layout 9 The controller calculates the temperature difference between collector sensor S1 and store sensor S2. If the difference is larger than or identical to the adjusted switchon temperature difference (DT O), the solar pump will be operated by relay 1, and the store will be loaded until the switch-off temperature difference (DT F) or the maximum store temperature (S MX) is reached. A heating circuit return preheating will be operated by relay 2, if the temperature difference between sensors S3 and S4 is larger than or identical to the adjusted switch-on temperature difference (DT3O). For this purpose, relay 2 will operate the 3-way-valve. S3 can optionally be used as reference sensor for the store emergency shutdown option (OSEM). Arr 9 VBus 9 10 S1 S4 R1 S3 Display Channels Channel Description x* INIT ODB initialisation active x* FLL ODB filling time active x* STAB ODB stabilisation in progress COL x Temperature collector TSTB x Temperature store 1 base TSTT x Temperature store 1 at the top TRET x Temperature heating circuit n% x Pump speed relay hP1 x Operating hours R1 hP2 x Operating hours R2 TIME x Time | 28 R2 Terminal S1 S2 S3 S4 R1 R1 R2 - Page 37 37 37 37 37 37 38 38 38 38 34 © RESOL 11157_deltasol_bs_plus.monen.indd S2 DeltaSol® BS Plus Adjustment Channels Channel Description Arr x System DT O x Switch-on temperature difference DT F x Switch-off temperature difference DT S x Nominal temperature difference RIS x Rise control R1 nMN x Minimum pump speed S MX x Maximum store temperature OSEM x Option store emergency shutdown Emergency temperature collector EM x Emergency temperature collector if ODB is activated: OCC x Option collector cooling CMX x* Maximum collector temperature OSYC x Option system cooling DTCO x* Cooling switch-on temperature difference DTCF x* Cooling switch-off temperature difference OSTC x Option store cooling OHOL x* Option holiday cooling THOL x* Holiday cooling temperature OCN x Option minimum limitation CMN x* Minimum collector temperature OCF x Option antifreeze CFR x* Antifreeze temperature O TC x Option tube collector TCST x* OTC starting time TCEN x* OTC ending time TCRU x* OTC runtime TCIN x* OTC standstill interval DT3O s Switch-on temperature difference 3 DT3F s Switch-off temperature difference 3 ODB x Drainback option tDTO x* ODB switch-on condition - time period tFLL x* ODB filling time tSTB x* ODB stabilisation time MAN1 x Manual operation R1 MAN2 x Manual operation R2 ADA1 x HE pump control LANG x Language UNIT x Temperature unit RESE x Reset - back to factory settings W005#### Version number Factory setting 9 6.0 K [12.0 °Ra] 4.0 K [8.0 °Ra] 10.0 K [20.0 °Ra] 2 K [4 °Ra] 30 % 60 °C [140 °F] OFF 130 °C [270 °F] 95 °C [200 °F] OFF 110 °C [230 °F] OFF 20.0 K [40.0 °Ra] 15.0 K [30.0 °Ra] OFF OFF 40 °C [110 °F] OFF 10 °C [50 °F] OFF 4.0 °C [40.0 °F] OFF 07:00 19:00 30 s 30 min 6.0 K [12.0 °Ra] 4.0 K [8.0 °Ra] OFF 60 s 5.0 min 2.0 min Auto Auto OFF En °C Page 39 39 39 39 39 39 40 40 40 40 41 41 41 41 41 42 42 42 42 42 42 42 44 44 44 44 44 39 39 45 45 45 45 46 46 46 46 46 46 Legend: © RESOL 11157_deltasol_bs_plus.monen.indd Symbol Specification x Channel is available x* Channel is available if the corresponding option is activated. s Channel is specifically available in this system layout 29 | DeltaSol® BS Plus System layout 10 The controller calculates the temperature difference between collector sensor S1 and store sensor S2. If the difference is larger than or identical to the adjusted switchon temperature difference (DT O), the solar pump will be operated by relay 1, and the store will be loaded until the switch-off temperature difference (DT F) or the maximum store temperature (S MX) is reached. If the maximum collector temperature (CMX) is reached, the solar pump will be operated by relay 1 and the 3-way-valve will be operated by relay 2 in order to direct the surplus energy to a heat dump. For security purpose this will be carried out only if the store temperature is below the nonadjustable emergency shutdown of 95 °C [200 °F]. Sensors S3 and S4 can optionally be connected for measurement purposes. S3 can optionally be used as reference sensor for the store emergency shutdown option (OSEM). If heat quantity measurement (OHQM) is activated, sensor S4 has to be connected as return sensor. VBus 9 10 Arr 10 S1 R2 S4 / TR Display Channels Channel Description COL x Temperature collector TST x Temperature store S3 x Temperature sensor 3 TSTT x Temperature store at the top S4 x Temperature sensor 4 x* TR Temperature return sensor n% x Pump speed relay h P1 x Operating hours R1 h P2 x Operating hours R2 kWh x* Heat quantity kWh MWh x* Heat quantity MWh TIME x Time | 30 S3 S2 Terminal S1 S2 S3 S3 S4 S4 R1 R1 R2 - Page 37 37 37 37 37 37 30 38 38 38 38 34 © RESOL 11157_deltasol_bs_plus.monen.indd R1 DeltaSol® BS Plus Adjustment Channels Channel Description Arr x System DT O x Switch-on temperature difference DT F x Switch-off temperature difference DT S x Nominal temperature difference RIS x Rise control R1 nMN x Minimum pump speed S MX x Maximum store temperature OSEM x Option store emergency shutdown EM x Emergency temperature collector CMX s Maximum collector temperature OCN x Option minimum limitation CMN x* Minimum collector temperature OCF x Option antifreeze CFR x* Antifreeze temperature O TC x Option tube collector TCST x* OTC starting time TCEN x* OTC ending time TCRU x* OTC runtime TCIN x* OTC standstill interval OHQM x Option heat quantity measurement FMAX x* Maximum flow MEDT x* Antifreeze type MED% x* Antifreeze concentration (only if MEDT = propylene or ethylene) MAN1 x Manual operation R1 MAN2 x Manual operation R2 ADA1 x HE pump control LANG x Language UNIT x Temperature unit RESE x Reset - back to factory settings W005#### Version number Factory setting 10 6.0 K [12.0 °Ra] 4.0 K [8.0 °Ra] 10.0 K [20.0 °Ra] 2 K [4 °Ra] 30 % 60 °C [140 °F] OFF 130 °C [270 °F] 110 °C [230 °F] OFF 10 °C [50 °F] OFF 4.0 °C [40.0 °F] OFF 07:00 19:00 30 s 30 min OFF 6.0 l 1 45 % Auto Auto OFF En °C Page 39 39 39 39 39 39 40 40 40 41 42 42 42 42 44 44 44 44 44 44 44 44 44 46 46 46 46 46 46 Legend: © RESOL 11157_deltasol_bs_plus.monen.indd Symbol Specification x Channel is available x* Channel is available if the corresponding option is activated. s Channel is specifically available in this system layout 31 | DeltaSol® BS Plus 2. Operation and function 2.1Push buttons operating control lamp forward (+) backward (-) 2 3 1 OK (selection / adjustment mode) 2.2System-Monitoring-Display ! system monitoring display channel display The controller is operated via three push buttons below the display. Button 1 is used for scrolling forward through the indication menu or to increase the adjustment values. Button 2 is used for scrolling backward and reducing values. Button 3 is used for selecting channels and confirming adjustments. During normal operation, only the display channels are shown. ÎÎ Scroll through the display channels by pressing buttons 1 and 2 Accessing the adjustment channels: ÎÎ Scroll down in the display menu and press button 1 for approx. two seconds after you have reached the last display item. When an adjustment value is shown on the display, is indicated to the right of the channel name. ÎÎ Press button 3 in order to access the adjustment mode starts flashing. ÎÎ Adjust the value using buttons 1 and 2 ÎÎ Briefly press button 3, permanently appears,the adjusted value will be saved. The system monitoring display consists of three blocks: channel display, tool bar and system screen (active system layout). The channel display consists of two lines. The upper line is an alpha-numeric 16-segment display (text display) for displaying channel names and menu items. In the lower 7-segment display, the channel values and the adjustment parameters are displayed. Temperatures are either indicated in °C or °F, whereas temperature differences are indicated in K or °Ra respectively. The additional symbols of the tool bar indicate the current system status. Status standard flashing relay 1 active relay 2 active maximum store temperature exceeded + store emergency shutdown active collector emergency shutdown active tool bar collector cooling active system cooling active store cooling active + holiday cooling function active + collector minimum limitation active antifreeze function activated antifreeze function active manual operation relay 1 ON manual operation relay 2 ON manual operation relay 1 / 2 OFF sensor defective | 32 / + + © RESOL 11157_deltasol_bs_plus.monen.indd holiday cooling function activated DeltaSol® BS Plus System screen The system screen (active system layout) shows the system selected on the controller. It consists of several system component symbols, which are – depending on the current status of the system – either flashing, permanently shown or hidden. system screen sensors collector 2 store sensor at the top heating circuit collector 1 valve heating circuit return sensor valve pumps sensor additional symbol for operation of the burner store heat exchanger store store 2 or afterheating (with an additional symbol) afterheating with burner symbol store sensor base Temperature sensor Collectors with collector sensor Heating circuit Stores 1 and 2 with heat exchanger Pump 3-way valve the flow direction or the actual switching position is shown Afterheating with burner symbol © RESOL 11157_deltasol_bs_plus.monen.indd 2.3Flashing codes System screen flashing codes • Pumps are flashing when the corresponding relay is switched on • Sensor symbols are flashing if the corresponding sensor display channel is selected • Sensors are flashing quickly in the case of a sensor fault • Burner symbol is flashing if the afterheating is active LED flashing codes green: red/green flashing: red flashing: everything OK initialisation phase manual operation sensor fault (sensor symbol is flashing quickly) 33 | DeltaSol® BS Plus 3. Commissioning 2 3 1 (OK) The three push buttons of the BS Plus controller ÎÎ Establish the power supply During a short initialisation phase, the operating control lamp flashes red and green. When the controller is commissioned for the first time or after a reset, it will run a commissioning menu. The commissioning menu leads the user through the most important adjustment channels needed for operating the system. Operating the commissioning menu: ÎÎ Enter the channel by pressing button 3 The symbol flashes. ÎÎ Adjust the value by pressing buttons 1 and 2 ÎÎ Save the adjustment by pressing button 3 again The symbol stops flashing. ÎÎ Press button 1 or 2 to switch to the next or previous channel The commissioning menu consists of the following 6 channels: 1. Language ÎÎ Adjust the desired menu language in this channel • dE : German • En : English • Fr : French UNIT: Temperature unit selection Selection: °C, °F Factory setting: °C 2. Unit ÎÎ Adjust the unit in which temperatures and temperature differences shall be displayed TIME: Real time adjustment 3. Time ÎÎ Adjust the current time for the real time clock The hours and minutes have to be adjusted separately, first the hours, then the minutes. © RESOL 11157_deltasol_bs_plus.monen.indd LANG: Language selection Selection: dE, En, Fr Factory setting: En | 34 DeltaSol® BS Plus Arr: System layout selection Adjustment range:1 ... 10 Factory setting: 1 4. System layout ÎÎ Adjust the desired system layout of your solar thermal system For a detailed description of the different system layouts selectable, see chapter 1.4. Overview of system layouts: Arr 1 Arr 2 Arr 1 : standard solar system layout Arr 2 : solar system layout with heat exchange Arr 3 Arr 4 Arr 3 : solar system layout with afterheating Arr 4 : solar system layout with vertical store charging Arr 5 Arr 6 Arr 5 : 2-store solar system layout with valve logic Arr 6 : 2-store solar system layout with pump logic Arr 7 Arr 8 Arr 7 : solar system layout with 2 collectors and 1 store Arr 8 : solar system layout with afterheating by solid fuel boiler Arr 9 Arr 10 Arr 9 : solar system layout with heating circuit return preheating Arr 10: standard solar system layout with heat dump If the system layout selection is changed later on, any previous adjustments which have been made in the other channels will be lost. Therefore, changing the system layout is always followed by a security enquiry. Only confirm the security enquiry if you are sure that you wish to change the system layout selection! ÎÎ To confirm the security enquiry, press button 3 © RESOL 11157_deltasol_bs_plus.monen.indd Security enquiry: 35 | DeltaSol® BS Plus S MX / S1MX / S2MX: Maximum store temp. Adjustment range: 4 ... 95 °C [40 ... 200 °F] Arr 10: 4 ... 90 °C [40 ... 190 °F] in steps of 1 °C [2 °F] Factory setting: 60 °C [140 °F] 5. Maximum store temperature ÎÎ Adjust the desired maximum store temperature nMN, n1MN, n2MN: Pump speed control Adjustment range: 30 ... 100 in steps of 5 % Factory setting: 30 6. Minimum pump speed ÎÎ Adjust a minimum speed for the pump Confirmation enquiry Completing the commissioning menu After the last channel of the commissioning menu has been adjusted and confirmed, the controller asks for confirmation of the adjustments. ÎÎ To confirm the adjustments made in the commissioning menu, press button 3 Note: The controller is also equipped with a nonadjustable emergency shutdown function, which will shut the system down if the store reaches 95 °C [200 °F]. Note: If loads which are not speed-controlled (e.g. valves) are used, the value must be set to 100 % for the respective relay. © RESOL 11157_deltasol_bs_plus.monen.indd Now the controller is ready for operation with typical settings to suit the selected system layout. The settings made in the commissioning menu can be changed later on in the corresponding adjustment channels. Additional functions and options can of course be individually adjusted as well (see chap. 4.2). | 36 DeltaSol® BS Plus 4. Channel overview 4.1Display channels Note: The displayed values and adjustment channels depend on which system layout, which options and functions have been selected. Only values and adjustment channels available for the individual settings selected will appear in the menu. Indication of drainback time periods Initialisation INIT: ODB initialisation active Indicates the time adjusted in tDTO, running backwards. Filling time FLL: ODB filling time active Indicates the time adjusted in tFLL, running backwards. Stabilisation STAB: Stabilisation Indicates the time adjusted in tSTB, running backwards. Indication of collector temperatures COL, COL1, COL2: Collector temperature Display range: -40 ... +260 °C [-40 ... +500 °F] Indicates the current collector temperature. Indication of store temperatures TST,TSTB,TSTT, TST1,TST2,TDIS: Store temperatures Display range: -40 ... +260 °C [-40 ... +500 °F] Indicates the current store temperature. Indication of sensors 3 and 4 © RESOL 11157_deltasol_bs_plus.monen.indd S3, S4: Sensor temperatures Display range: -40 ... +260 °C [-40 ... +500 °F] Indication of other temperatures TSFB,TRET,TR: Other measured temperatures Display range: -40 ... +260 °C [-40 ... +500 °F] • COL : collector temperature (1-collector system) • COL1: collector temperature 1 • COL2: collector temperature 2 •• •• •• •• •• •• TST :store temperature (1-store system) TSTB:store temperature base TSTT:store temperature top TST1:temperature store 1 (2-store-systems) TST2:temperature store 2 (2-store-systems) TDIS:thermal disinfection temperature (Arr = 3 only; replaces TSTT if, during thermal disinfection, the heating period DDIS is active) Indicates the current temperature of the corresponding additional sensor (without control function). • St: temperature sensor 4 Note: S3 and S4 will only be indicated if the temperature sensors are connected. Indicates the current temperature of the corresponding sensor. • TSFB : temperature solid fuel boiler • TRET: temperature heating return preheating • TR : temperature return 37 | DeltaSol® BS Plus n %, n1 %, n2 %: Current pump speed Display range: 30 ... 100 % kWh/MWh: Heat quantity in kWh / MWh Display channel CDIS Countdown of monitoring period Display range: 0 ... 30:0 ... 24 (dd:hh) SDIS Starting time display Display range: 00:00 ... 24:00 (hh:mm) DDIS Heating period display Display range: 00:00 ... 24:00 (hh:mm) TIME Operating hours counter h P / h P1 / h P2: Operating hours counter Display channel | 38 Indicates the current pump speed of the corresponding pump. • n % : current pump speed (1-pump system) • n1 % : current pump speed pump 1 • n2 % : current pump speed pump 2 Indicates the energy gained in heat quantity – only available if heat quantity measurement (OHQM) is activated. The flow rate as well as the reference sensors S1 (flow) and S4 (return) are used for calculating the heat quantity supplied. It is shown in kWh in the channel kWh and in MWh in the channel MWh. The overall heat quantity results from the sum of both values. The accumulated heat quantity can be set back to 0. As soon as one of the display channels of the heat quantity is selected, the symbol is permanently shown on the display. ÎÎ Press button 3 for about two seconds in order to access the RESET mode of the counter. The display symbol will flash and the heat quantity value will be set to 0. ÎÎ Confirm the reset with button 3 in order to finish the reset. In order to interrupt the RESET-process, do not press a button for about five seconds. The display returns to the display mode. If the thermal disinfection option (OTD) is activated and the monitoring period is in progress, the remaining monitoring time will be displayed as CDIS (in days and hours) and counted backwards. If the thermal disinfection option (OTD) is activated and a starting delay time has been adjusted, the adjusted delay time is displayed (flashing) in this channel. If the thermal disinfection option (OTD) is activated and the heating period is in progress, the remaining time of the heating period is displayed (in hours and minutes) in this channel, counting backwards. Indicates the current time. ÎÎ Press button 3 for two seconds to adjust the hours ÎÎ Set the hours by pressing buttons 1 and 2 ÎÎ Press button 3 again to adjust the minutes ÎÎ Set the minutes by pressing buttons 1 and 2 ÎÎ Press button 3 in order to save the adjustments The operating hours counter accumulates the solar operating hours of the respective relay (h P / h P1 / h P2). Full hours are displayed. The accumulated operating hours can be set back to zero. As soon as one operating hours channel is selected, the is displayed. symbol ÎÎ In order to access the RESET-mode of the counter, press button 3 for approx. two seconds. will flash and the operating hours The display symbol will be set to 0. ÎÎ Confirm the reset with button 3 in order to finish the reset. In order to interrupt the RESET-process, do not press a button for about five seconds. The display returns to the display mode. © RESOL 11157_deltasol_bs_plus.monen.indd Indication of current pump speed DeltaSol® BS Plus 4.2Adjustment channels System layout selection Arr: System layout selection. Adjustment range:1 ... 10 Factory setting: 1 Security enquiry: In this channel, a pre-defined system layout can be selected. Each system layout has a set of pre-programmed settings that can be individually changed. If the system layout selection is changed later on, all adjustments made in the other channels will be lost. Therefore, changing the system layout is always followed by a security enquiry. Only confirm the security enquiry if you are sure that you wish to change the system layout selection! ÎÎ To confirm the security enquiry, press button 3 ∆T-regulation DT O / DT1O / DT2O / DT3O: Switch-on temperature diff. Adjustment range: 1.0 ... 20.0 K [2.0 ... 40.0 °Ra] in steps of 0.5 K [1 °Ra] Factory setting: 6.0 K [12.0 °Ra] Note: The switch-on temperature difference must be at least 0.5 K [1 °Ra] higher than the switchoff temperature difference. DT F / DT1F / DT2F / DT3F: Switch-off temperature d iff. Adjustment range: 0.5 ... 19.5 K [1.0 ... 39.0°Ra] in steps of 0.5 K [1 °Ra] Factory setting: 4.0 K [8.0°Ra] Note: When the drainback option ODB is activated, the temperature differences DT O, DT F and DT S are set to a fixed adjustment: DT O= 10 K [20 °Ra] DT F = 4 K [8 °Ra] DT S = 15 K[30 °Ra] Previous adjustments made in these channels will be overridden and may have to be entered again if ODB is deactivated later on. Pump speed control DT S / DT1S / DT2S / DT3S: Nominal temperature difference Adjustment range: 1.5 ... 30.0 K [3.0 ... 60.0 °Ra] in steps of 0.5 K [1 °Ra] Factory setting: 10.0 K [20.0 °Ra] Note: For pump speed control, the operation mode of the corresponding relay must be set to Auto (adjustment channel MAN1 / MAN2) RIS / RIS1 / RIS2 / RIS3: Rise Adjustment range: 1 ... 20 K [2 ... 40 °Ra] in steps of 1 K [2 °Ra] Factory setting: 2 K [4 °Ra] © RESOL 11157_deltasol_bs_plus.monen.indd The controller works as a standard differential controller. If the switch-on difference is reached, the pump is activated. When the temperature difference falls below the adjusted switch-off temperature difference, the respective relay switches off. When the switch-on temperature difference is reached, the pump is activated at full speed for 10 seconds.Then, the speed is reduced to the minimum pump speed value (factory setting = 30 %). If the temperature difference reaches the adjusted nominal temperature difference, the pump speed increases by one step (10 %). If the difference increases by the adjustable rise value, the pump speed increases by 10 % respectively until the maximum pump speed of 100 % is reached.The response of the controller can be adapted via the parameter “Rise”. Note: The nominal temperature difference must be at least 0.5 K [1 °Ra] higher than the switch-on temperature difference. Minimum pump speed nMN, n1MN, n2MN: Pump speed control Adjustment range: 30 ... 100 % in steps of 5 % Factory setting: 30 % nMN, n1MN, if ODB is activated: 50 % A relative minimum pump speed can be allocated to the outputs R1 and R2 via the adjustment channels nMN, n1MN and n2MN. Note: When loads which are not speed-controlled (e.g. valves) are used, the value must be set to 100 % in order to deactivate pump speed control. 39 | DeltaSol® BS Plus Maximum store temperature S MX / S1MX / S2MX: Maximum store temp. Adjustment range: 4 ... 95 °C [40 ... 200 °F] Arr 10: 4 ... 90 °C [40 ... 190 °F] in steps of 1 °C [2 °F] Factory setting: 60 °C [140 °F] Once the adjusted maximum temperature is exceeded, the solar pump is switched off and further loading of the store is prevented to reduce scald risk or system damage. A fixed hysteresis of 2 K [4 °Ra] is set for the maximum store temperature. When the temperature at the corresponding sensor exceeds the adjusted maximum store temperature, the symbol is shown on the display. Store emergency shutdown option OSEM Store emergency shutdown option Adjustment range: OFF / ON Factory setting: OFF This option is used for activating the integrated store emergency shutdown for an upper store sensor. If the temperature at the reference sensor exceeds 95 °C, store 1 will be blocked and loading will be stopped until the temperature falls below 90 °C. Collector temperature limitation Emergency shutdown of the collector If the adjusted collector emergency shutdown temperature (EM / EM1 / EM2) is exceeded, the controller switches off the solar pump (R1 / R2) in order to protect the system against overheating (collector emergency shutdown). A hysteresis of 10 K [20 °Ra] is set for the collector temperature limitation.While the collector is in emergency (flashing) is shown on the display. shutdown, Note: Sensor S3 ist used as the reference sensor in the system layouts 1, 2, 3, 8, 9 and 10. In the system layouts 6 and 7, sensor S4 is used as the reference sensor. This option is not available in system layouts 4 and 5. Note: If the drainback option ODB is activated, the adjustment range of EM is changed to 80 ... 120 °C [170 ... 250 °F].The factory setting in that case is 95 °C [200 °F]. WARNING! | 40 Danger of injury and system damage through pressure surges! If water is used as a heat transfer medium in a pressure-less system, the water will start boiling at 100 °C [212 °F]. ÎÎ If a pressure-less drainback system is used with water as a heat transfer medium, do not adjust the collector temperature limitation EM to more than 95 °C [200 °F]! © RESOL 11157_deltasol_bs_plus.monen.indd EM / EM1 / EM2: Collector temperature limitation Adjustment range: 80 ... 200 °C [170 ... 390 °F] in steps of 1 °C [2 °F] Factory setting: 130 °C [270 °F] Note: If the collector cooling or the system cooling function is activated, the adjusted store temperature may be overridden. In order to prevent system damage, the controller is also equipped with an integrated store emergency shutdown if the store reaches 95 °C [200 °F]. DeltaSol® BS Plus Cooling functions In the following the three cooling functions – collector cooling, system cooling and store cooling – are described in detail. The following notes are valid for all three cooling functions: Note: The cooling functions will not become active as long as solar loading is possible. Note: In 2-store-systems, the cooling functions will only affect store 1, respectively the base area of the store (such as in Arr = 4). Collector cooling function OCC / OCC1 / OCC2: Option collector cooling Adjustment range: OFF / ON Factory setting: OFF CMX / CMX1 / CMX2: Maximum collector temp. Adjustment range: 70 ... 160 °C [150 ...320 °F] in steps of 1 °C [1 °F] Factory setting: 110 °C [230 °F] When the collector cooling function is activated, the controller aims to keep the collector at an operational temperature. When the adjusted maximum store temperature is reached, solar loading stops. If the collector temperature increases to the adjusted maximum collector temperature, the solar pump is activated until the collector temperature falls at least 5 K [10 °Ra] below the maximum collector temperature.The store temperature may increase (subordinate active maximum store temperature), but only up to 95 °C [200°F] (emergency shutdown of the store). If the collector cooling function is active, and (flashing) is shown on the display. Note: This function will only be available if the system cooling function (OSYC) is deactivated. Note: In system layout 10, the parameter CMX is available without the OCC function. In system layout 10, CMX is used to set the activation temperature for the heat dump function. No other switch-on condition is needed in that case. System cooling function OSYC: Option system cooling Adjustment range: OFF / ON Factory setting: OFF © RESOL 11157_deltasol_bs_plus.monen.indd DTCO: Switch-on temperature diff. Adjustment range: 1.0 ... 30.0 K [2.0 ... 60.0 °Ra] in steps of 0.5 K [1 °Ra] Factory setting: 20.0 K [40.0°Ra] DTCF: Switch-off temperature d iff. Adjustment range: 0.5 ... 29.5 K [1.0 ... 59.0 °Ra] in steps of 0.5 K [1 °Ra] Factory setting: 15.0 K [30.0 °Ra] When the system cooling function is activated, the controller aims to keep the solar system operational for a longer time. The function overrides the maximum store temperature to provide thermal relief of the collector field and the heat transfer fluid on hot days. If the store temperature is higher than the maximum store temperature (S MX / S1MX) and the switch-on temperature difference DTCO is reached, the solar system remains activated. Solar loading is continued until either the store temperature reaches 95 °C [200 °F] (emergency shutdown of the store), the temperature difference falls below the adjusted value DTCF or the collector emergency shutdown temperature EM is reached. If the system cooling function is active, and (flashing) is shown on the display. Note: This function will only be available if the collector cooling function (OCC) is deactivated. 41 | DeltaSol® BS Plus OHOL: Holiday cooling option Adjustment range: OFF / ON Factory setting: OFF THOL: Holiday cooling temperature Adjustment range: 20 ... 80 °C [70 ... 175 °F] in steps of 1 °C [1 °F] Factory setting: 40 °C [110 °F] Collector minimum limitation option OCN / OCN1 / OCN2: Collector minimum limitation Adjustment range: OFF / ON Factory setting: OFF CMN / CMN1 / CMN2: Collector minimum temp. Adjustment range: 10.0 ... 90.0 °C [50.0 ... 190.0 °F] in steps of 0.5 °C [1.0 °F] Factory setting: 10.0 °C [50.0 °F] Antifreeze option OCF / OCF1 / OCF2: Antifreeze function Adjustment range: OFF / ON Factory setting: OFF CFR / CFR1 / CFR2: Antifreeze temperature Adjustment range: -40.0 ... +10.0 °C [-40.0 ... +50.0 °F] in steps of 0.5 °C [1 °F] Factory setting: 4.0 °C [40.0 °F] | 42 When the store cooling function is activated, the controller aims to cool down the store during the night in order to prepare it for solar loading on the following day. If the adjusted maximum store temperature (S MX / S1MX) is exceeded and the collector temperature falls below the store temperature, the system will be reactivated in order to cool down the store. Cooling will continue until the store temperature has fallen below the adjusted maximum store temperature (S MX / S1MX) again.A fixed hysteresis of 2 K [4 °Ra] is set for this function. Reference threshold temperature differences for the store cooling function are DT O and DT F. If no DHW consumption is expected for a longer period of time, the additional holiday cooling option OHOL can be activated in order to extend the store cooling function. The adjustable temperature THOL then replaces the maximum store temperature (S MX / S1MX) as a switch-off temperature for the store cooling function. When the holiday cooling function is activated, and (flashing) are shown on the display. While the holiday cooling function is active, , and (flashing) are shown on the display. If the collector minimum limitation option is activated, the pump (R1 / R2) is only switched on if the adjustable collector minimum temperature is exceeded.The minimum temperature prevents the pump from being switched on too often at low collector temperatures. A fixed hysteresis of 5 °K [10 °Ra] is set for this function If the collector minimum limitation is active, (flashing) is shown on the display. Note: If OSTC or OCF is active, the collector minimum function will be overridden. In that case, the collector temperature may fall below CMN. The antifreeze function activates the loading circuit between the collector and the store when the temperature falls below the adjusted antifreeze temperature. This will protect the fluid against freezing or coagulating. If the adjusted antifreeze temperature is exceeded by 1 K [2 °Ra], the loading circuit will be deactivated. is shown on When the antifreeze function is activated, the display. If the antifreeze function is active, and (flashing) are shown on the display. Note: Since this function uses the limited heat quantity of the store, the antifreeze function should be used in regions with few days of temperatures around the freezing point. The antifreeze function will be suppressed if the store temperature falls below 5 °C [40 °F] in order to protect the store from frost damage. © RESOL 11157_deltasol_bs_plus.monen.indd Store cooling function OSTC: Store cooling option Adjustment range: OFF / ON Factory setting: OFF DeltaSol® BS Plus The DeltaSol® BS Plus priority logic Note: Priority logic can be used in multi-store system layouts only (Arr = 4, 5, 6). PRIO: Loading priority Adjustment range: SE 1, SE 2, Su 1, Su 2, 0, 1, 2 Factory setting: Arr 4: 2 Arr 5, 6:1 Note: If the priority is set to Su 1 or Su 2, solar loading of the subordinate store will be aborted at once if the temperature in the priority store (store 1 for Su 1, store 2 for Su 2) falls below the adjusted maximum temperature. If, in that case, the temperature difference between the priority store and the collector is not sufficiently high, solar loading will be stopped completely. Spreaded loading temperature difference (only available if PRIO is set to SE 1 or SE 2) DTSE: Spread temperature difference Adjustment range: 20 ... 90 K [40 ... 160 °Ra] in steps of 1 K [1 °Ra] Factory setting: 40 K [70 °Ra] Store sequence control (only available if priority is set to SE 1, SE 2, 1 or 2) tLB: Loading break time Adjustment range: 1 ... 30 min Factory setting: 2 min © RESOL 11157_deltasol_bs_plus.monen.indd tRUN: Loading runtime Adjustment range: 1 ... 30 min Factory setting: 15 min If a multi-store system layout has been chosen, the priority logic determines how the heat is divided between the stores. Different types of priority logic are adjustable: •• spreaded loading (SE 1 and SE 2) •• successive loading (Su 1 and Su 2) •• parallel loading (0) •• store sequence control (1 and 2) If priority SE 1 or SE 2 (only available in Arr 6) is adjusted, the subordinate store will be loaded in parallel if the temperature difference between the collector and the priority store (store 1 for SE 1, store 2 for SE 2) exceeds the adjusted value DTSE and the subordinate store has not reached its maximum temperature. Parallel loading will stop as soon as the temperature difference between the collector and the priority store falls 2 K [4 °Ra] below DTSE or the subordinate store reaches its maximum temperature. If priority Su 1 or Su 2 is adjusted, the stores are loaded successively.The subordinate store will only be loaded if the priority store (store 1 for Su 1, store 2 for Su 2) has reached its adjusted maximum temperature (S1MX or S2MX). If priority 0 is adjusted and the switch-on conditions are fulfilled for both stores, the stores are loaded in parallel (Arr 6), resp. in an oscillating loading (Arr 4, 5) beginning with the store with the lowest temperature. In an oscillating loading, solar loading will switch from one store to the other in steps of 5 K [10 °Ra] temperature difference between the stores. If priority 1 / 2 is adjusted, store sequence control will be activated (see below) with the corresponding store as priority store. Store sequence control will be activated when PRIO is set to SE 1, SE 2, 1 or 2. If the priority store cannot be loaded, the subordinate store is checked. If useful heat can be added, it will be loaded for the “loading runtime time” (tRUN - factory setting 15 min.) After this, the loading process stops and the controller monitors the increase in collector temperature during the loading break time tLB. If it increases by 2 K [4° Ra], the break time timer starts again to allow the collector to gain more heat. If the collector temperature does not increase sufficiently, the subordinate store will be loaded again for the tRUN time as before. As soon as the switch-on condition of the priority store is fulfilled, it will be loaded. If the switch-on condition of the priority store is not fulfilled, loading of the second store will be continued. If the priority store reaches its maximum temperature, sequence controlled loading will not be carried out. If store sequence control is active and the system switches to load the priority store, the parameter tLB also acts as a stabilisation timer, during which the switch-off condition DT F is ignored while the system operation stabilises. 43 | DeltaSol® BS Plus Tube collector function TCST: Tube collector function starting time Adjustment range: 00:00 ... 23:45 in steps of 00:15 Factory setting: 07:00 TCEN: Tube collector function ending time Adjustment range: 00:00 ... 23:45 in steps of 00:15 Factory setting: 19:00 TCRU: Tube collector function runtime Adjustment range: 5 ... 500 s in steps of 5 s Factory setting: 30 s TCIN: Tube collector function standstill interval Adjustment range: 1 ... 60 min in steps of 1 min Factory setting: 30 min Heat quantity measurement This function helps overcome the disadvantages caused by the non-ideal sensor position with some tube collectors. This function operates within an adjusted time frame (beginning at TCST and ending at TCEN). It activates the collector circuit pump for an adjustable runtime (TCRU) between adjustable standstill intervals (TCIN) in order to compensate for the delayed temperature measurement. If the runtime TCRU is set to more than ten seconds, the pump will be run at 100 % for the first ten seconds of the runtime. For the remaining runtime, the pump will be run at the adjusted minimum speed nMN. If the collector sensor is defective or the collector is blocked, this function is suppressed or switched off. In system layout 7 (Arr = 7) both collectors are operated independently from each other by means of this function. If the store is being loaded by one collector, the other one is nevertheless operated after the adjusted standstill time. Note: If the drainback option ODB is activated, TCRU will not be available. In that case, the runtime is determined by the parameters tFLL and tSTB. WARNING! Danger of injury and system damage through pressure surges! If a drainback system is filled due to the tube collector function and the heat transfer medium enters very hot collectors, pressure surges can occur. ÎÎ If a pressure-less drainback s ystem is used, TCST and TCEN must be adjusted such that the system will not be filled during times of potentially strong irradiation! OHQM: Heat quantity measurement Adjustment range: OFF / ON Factory setting: OFF If OHQM is activated, the heat quantity gained can be calculated and displayed. Heat quantity measurement is possible on Arr. 1, 3, 4, 5 and 10 if a flowmeter is used.To enable heat quantity measurement, proceed as follows: FMAX: Flow rate in l/min Adjustment range: 0.5 ... 100.0 in steps of 0.5 Factory setting: 6.0 ÎÎ Read the flow rate (l/min) from the flowmeter at maximum pump speed and adjust it in the FMAX channel ÎÎ Adjust the heat transfer fluid and the concentration of the antifreeze in the channels MEDT and MED%. MEDT: Heat transfer fluid Adjustment range: 0 ... 3 Factory setting: 1 Heat transfer fluid: 0 : Water 1 : Propylene glycol 2 : Ethylene glycol 3 : Tyfocor® LS / G-LS MED%: Antifreeze ratio in Vol-% (MED% is hidden when MEDT 0 or 3 is used.) Adjustment range: 20 ... 70 % in steps of 1 % Factory setting: 45 % | 44 Note: If the system layout 10 has been selected and OHQM is activated, heat quantity measurement will be interrupted when the 3-way-valve switches to the heat dump. © RESOL 11157_deltasol_bs_plus.monen.indd O TC: Tube collector function Adjustment range: OFF / ON Factory setting: OFF DeltaSol® BS Plus Drainback option Note: A drainback system layout requires additional components such as a holding tank. The drainback option should only be activated if all components required are properly installed. Note: The drainback option is only available in system layouts with one store and one collector (Arr 1, 2, 3, 8 and 9). ODB: Drainback option Adjustment range: OFF / ON Factory setting: OFF Note: When the drainback option ODB is activated, the cooling functions OCC, OSYC and OSTC as well as the antifreeze function OCF are not available. If OCC, OSYC, OSTC or OCF have already been activated before, they will be deactivated again as soon as ODB is activated. They will remain deactivated, even if ODB is deactivated later on. Time period - switch-on conditions tDTO: Time period switch-on conditions Adjustment range: 1 ... 100 s in steps of 1 s Factory setting: 60 s © RESOL 11157_deltasol_bs_plus.monen.indd Filling time tFLL: Filling time Adjustment range: 1.0 ... 30.0 min in steps of 0.5 min Factory setting: 5.0 min Stabilisation tSTB: Stabilisation Adjustment range: 1.0 ... 15.0 min in steps of 0.5 min Factory setting: 2.0 min Booster function option OBST: Booster function Adjustment range: ON / OFF Factory setting: OFF A drainback system permits the heat transfer fluid to drain back into the holding tank when solar energy is not collected. The drainback option will initiate the filling of the system when solar loading begins. If the drainback option ODB is activated, the pump will operate at 100 % speed for the adjusted filling time tFLL in order to fill the system with fluid from the holding tank. After tFLL, pump speed will go down to the adjusted minimum pump speed nMn. The switch-off conditions will then be ignored for the stabilisation time tSTB in order to avoid the system from shutting down prematurely. If the function is activated, the menu items described in the following (tDTO, tFLL and tSTB) have to be adjusted: Note: When the drainback option ODB is activated, the temperature differences DT O, DT F and DT S as well as the minimum speed values nMN / n1MN are set to a fixed adjustment. Additionally, the adjustment range and the factory setting of the collector emergency shutdown temperature EM changes (see the corresponding channel descriptions for further information). Previous adjustments made in these channels will be overridden and have to be entered again if ODB is deactivated later on. The parameter tDTO is used for adjusting the time period during which the switch-on condition DT O must be permanentely fulfilled. The filling time can be adjusted using the parameter tFLL. During this period, the pump runs at 100 % speed. The parameter tSTB is used for adjusting the time period during which the switch-off condition DT F will be ignored after the filling time has ended. This function is used for switching on a second pump when filling the solar system. When solar loading starts, R2 is energised in parallel to R1. After the filling time (tFLL) has ended, R2 is switched off. Note: The booster function is available in system layout 1 (Arr = 1) only. The booster function will only be available if the drainback option has been activated. 45 | DeltaSol® BS Plus Operating mode MAN1 / MAN2: Operating mode Adjustment range: OFF, Auto, ON Factory setting: Auto For control and service work, the operating mode of the controller can be manually adjusted. For this purpose, select the adjustment value MAN1, MAN2 in which the following adjustments can be made: • MAN1 / MAN2 Operating mode OFF : relay off (flashing) + Auto: relay in automatic operation ON : relay on (flashing) + + / Note: Always adjust the operating mode back to “Auto” when the control and service work is completed. Normal operation is not possible in manual mode. HE pump control ADA1 / ADA2: HE pump control Adjustment range: ON / OFF Factory setting: OFF This option is used for controlling high-efficiency pumps via a VBus® / PWM adapter. The power supply of the pump(s) takes place via the semiconductor relay(s). For pump speed control with activated ADA1 / ADA2 option, the relay is switched on or off (no pulse packets). Temperature dependent speed information is transmitted via the VBus®.The relay will remain deactivated for 1 hour after its switch-off conditions have been fulfilled (pump protection). Language LANG: Language selection Selection: dE, En, Fr Factory setting: En The menu language can be adjusted in this channel. • dE : German • En : English • Fr : French Unit UNIT: Temperature unit selection Selection: °C, °F Factory setting: °C In this adjustment channel, the display unit for temperatures and temperature differences can be chosen.The unit can be switched between °C / K and °F / °Ra during operation. Temperatures and temperature differences in °F and °Ra are displayed without units. If the indication is set to °C, the units are displayed with the values. Reset RESE Reset function By using the reset function, all adjustments will be set back to the factory settings. ÎÎ To initiate a reset, press button 3 Any previous adjustments will be lost. Therefore, initiating the reset function is always followed by a security enquiry. Only confirm the security enquiry if you are sure that you wish to reset all adjustments to the factory settings! Security enquiry: ÎÎ To confirm the security enquiry, press button 3 Note: Whenever a reset has been completed, the controller runs the commissioning menu again (see chap. 3). | 46 © RESOL 11157_deltasol_bs_plus.monen.indd Note: The parameter ADA1 refers to relay 1 and is available in all system layouts. The parameter ADA2 refers to relay 2 and is available in the system layouts 2, 6, 7, 8. DeltaSol® BS Plus 5. Troubleshooting fuse In the case of an error, a message is shown on the display of the controller: T4A 100 ... 240 V~ 50-60 Hz DE-45527 Hattingen DeltaSol BS Plus V2 Made in Germany CU 72091163 01 IP 20 Temp. Sensor Pt1000 S1 1 2 3 S2 4 S3 5 S4 6 7 VBus 8 9 10 Warning symbols R1 1 (1) A (100 ... 240) V~ R2 1 (1) A (100 ... 240) V~ 12 13 14 N R2 N R1 N L 15 16 17 18 19 20 Operating control lamp VBus® terminals sensor terminals ground terminals load terminals power supply terminals Operating control lamp flashes red. On the display the symbols and appear. Sensor defect. An error code instead of a temperature is displayed in the sensor display channel. 888.8 - 88.8 Short circuit. Check cable. Cable broken. Check cable. © RESOL 11157_deltasol_bs_plus.monen.indd Disconnected Pt1000 temperature sensors can be checked with an ohmmeter. In the following table, the resistance values with the corresponding temperatures are shown. °C °F Ω °C °F Ω -10 -5 0 5 10 15 20 25 30 35 40 45 50 14 23 32 41 50 59 68 77 86 95 104 113 122 961 980 1000 1019 1039 1058 1078 1097 1117 1136 1155 1175 1194 55 60 65 70 75 80 85 90 95 100 105 110 115 131 140 149 158 167 176 185 194 203 212 221 230 239 1213 1232 1252 1271 1290 1309 1328 1347 1366 1385 1404 1423 1442 Operating control lamp off. Check the power supply. Is it disconnected? no yes The fuse of the controller could be blown. It can be replaced after the front cover has been removed (spare fuse is enclosed in the accessory bag). Check the supply line and reconnect it. Resistance values of the Pt1000-sensors 47 | DeltaSol® BS Plus 5.1Various Pump is overheated, but no heat transfer from the collector to the store, flow and return have the same temperature; perhaps also air / gas bubbles in the lines. Pump starts for a short moment, switches off, switches on again, etc. Air in the system? Temperature difference at the controller too small? no yes Is the collector circuit blocked at the dirt trap? Air in the system; increase the system pressure to at least static primary pres sure plus 7. 25 psi (0.5 bar); if necessary continue to increase pressure; switch the pump off and on for a short time. no Change ∆Ton and ∆Toff correspondingly. Problem solved? no Wrong position of collector sensors? no yes yes yes Clean the dirt trap Plausibility control of the option tube collector special function yes o.k. Mount the collector sensor at solar flow (warmest collector output); use sensor well of the respective collector. Pump starts up very late The temperature difference between store and collector increases enormously during operation; the collector circuit cannot dissipate the heat. Switch-on temperature difference ∆Ton to large? Collector circuit pump defective? no yes Change ∆Ton and ∆Toff correspondingly. yes Check / replace it Heat exchanger calcified? Non-ideal position of the collector sensor (e.g. flatscrew sensor instead of sensor in sensor wells)? yes no no yes Decalcify it Activate tube collector function if necessary. Heat exchanger blocked? o.k. yes Clean it Heat exchanger too small? yes | 48 Replace with correctly sized one. © RESOL 11157_deltasol_bs_plus.monen.indd no DeltaSol® BS Plus a Stores cool down at night b Control the non-return valve in warm water circulation - o.k. Collector circuit pump runs during the night? no yes Collector temperature is at night higher than the outdoor temperature no yes Sufficient store insulation? yes no Check controller: Manual operation active? Tube collector function active? Store cooling or antifreeze function active? Check the check valve in the flow and the return pipe with regard to the functional efficiency. Increase insulation. no Replace insulation or increase it. Are the store connections insulated? yes no Warm water outflow upwards? no yes Insulate the connections. Change connection and let the water flow hori zontally or through a siphon (downwards); less store losses now ? no yes o.k. Does the warm water circulation run for a very long time? © RESOL 11157_deltasol_bs_plus.monen.indd no yes Circulation pump and blocking valve should be switched off for one night; less store losses? yes no Use the circulation pump with timer and switch-off thermostat (energy efficient circulation). Check whether the pumps of the afterheating circuit run at night; check whether the non-return valve is defective; problem solved ? The thermosiphoning in the circulation line is too strong; insert a stronger valve in the non-return valve or an electrical 2-port valve behind the circulation pump; the 2-port valve is open when the pump is activated, otherwise it is closed; connect pump and 2-port valve electrically in parallel; activate the circulation again b Is the control lamp (LED) illuminated? yes Clean or replace it no The adjusted temperature difference for starting the pump is to high; choose a value which makes more sense. Is the pump stuck? yes yes Turn the pump shaft using a screwdriver; now passable? no Are the controller fuses o.k. ? no Replace fuses. o.k. yes Is the pump current enabled by the controller? no There is no current; check fuses / replace them and check power supply. no Does the pump start up in manual operation? yes no a no The solar circuit pump does not work, although the collector is considerably warmer than the store. Insulation close enough to the store? yes yes Further pumps which are connected to the solar store must also be checked. Pump is defective - replace it yes Controller might be defective - replace it or contact the distributor. 49 | DeltaSol® BS Plus 6. Accessories Sensors Our product range includes high-precision platinum temperature sensors, flatscrew sensors, outdoor temperature sensors, indoor temperature sensors, cylindrical clip-on sensors, also as complete sensors with immersion sleeve. For more information, see our catalogue and price list. Overvoltage protection device In order to avoid overvoltage damage at collector sensors (e.g. caused by local lightning storms), we recommend the overvoltage protection RESOL SP10. RESOL SP10 Article no.: 180 110 70 Smart Display SD3 The RESOL Smart Display is designed for simple connection to RESOL controllers with RESOL VBus®. It is used for visualizing data issued by the controller: collector temperature, storage temperature and energy yield of the solar thermal system.The use of high-efficient LEDs and filter glass assures a high optical brilliance and good readability even in poor visibility conditions and from a larger distance. An additional power supply is not required. RESOL SD3 (unit °C) RESOL SD3 (unit °F) Article no.: 180 004 90 Article no.: 180 007 77 Large Display GA3 The RESOL Large Display GA3 is designed for simple connection to RESOL controllers via the RESOL VBus®. It is used for visualizing the data issued by the controller: collector and store temperature as well as heat quantity produced in the solar system. The use of high-efficient LEDs and antireflective filter glass assures a high optical brilliance and good readability - even in poor lighting conditions and at a larger distance. Article no.: 180 006 50 Article no.: 180 007 87 © RESOL 11157_deltasol_bs_plus.monen.indd RESOL GA3 (unit °C) RESOL GA3 (unit °F) | 50 DeltaSol® BS Plus DL2 Datalogger This additional module enables the acquisition and storage of large amounts of data (such as measuring and balance values of the solar system) over a long period of time. The DL2 can be configured and read-out with a standard internet browser via its integrated web interface. For transmission of the data stored in the internal memory of the DL2 to a PC, an SD card can be used. The DL2 is appropriate for all controllers with RESOL VBus®. It can be connected directly to a PC or router for remote access and thus enables comfortable system monitoring for yield monitoring or for diagnostics of faults. RESOL DL2 Article no.: 180 007 10 VBus® / USB interface adapter The new VBus® / USB interface adapter is the interface between the controller and a personal computer.With its standard mini-USB port it enables a fast transmission of system data via the VBus® for processing, visualizing and archiving. A full version of the RESOL ServiceCenter software is included. RESOL VBus® / USB interface adapter Article no.: 180 008 50 VBus® / LAN interface adapter The VBus® / LAN interface adapter is designed for the direct connection of the controller to a PC network or router. It enables easy access to the controller via the local network of the owner.Thus, controller access and data charting can be effected from every workstation of the network. A full version of the RESOL ServiceCenter software is included. RESOL VBus® / LAN interface adapter Article no.: 180 008 80 VBus® / PWM interface adapter The VBus® / PWM interface adapter is used for the speed control of a pump via a PWM or 0-10 V signal.Via the VBus®, the adapter receives information from the controller about the necessary pump speed.The speed is converted into a PWM or direct voltage signal and put out to the corresponding terminals. © RESOL 11157_deltasol_bs_plus.monen.indd RESOL VBus® / PWM interface adapter Article no.: 180 008 60 AM1 Alarm module The AM1 alarm module is designed to signal system failures. It is to be connected to the VBus® of the controller and issues an optical signal via a red LED if a failure has occurred. The AM1 also has a potential-free relay output, which can e. g. be connected to a building management system (BMS). Thus, a collective error message can be issued in the case of a system failure. RESOL AM1 Alarm module Article no.: 180 008 70 51 | DeltaSol® BS Plus Important notice: The texts and drawings in this manual are correct to the best of our knowledge. As faults can never be excluded, please note: Your own calculations and plans, under consider ation of the current standards should only be basis for your projects.We do not offer a guarantee for the completeness of the drawings and texts of this manual - they only represent some examples. They can only be used at your own risk. No liability is assumed for incorrect, incomplete or false information and / or any resulting damages. RESOL - Elektronische Regelungen GmbH Heiskampstraße 10 45527 Hattingen / Germany Tel.: +49 (0) 23 24 / 96 48 - 0 Fax: +49 (0) 23 24 / 96 48 - 755 www.resol.com info@resol.com Reprinting / copying This mounting- and operation manual including all parts is copyrighted. Another use outside the copyright requires the approval of RESOL - Elektronische Regelungen GmbH. This especially applies for copies, translations, microfilms and the storage into electronic systems. Editor: RESOL - Elektronische Regelungen GmbH Please note: The design and the specifications can be changed without prior notice. The illustrations may differ from the original product. | 52 © RESOL 11157_deltasol_bs_plus.monen.indd Distributed by: