Technical
Bulletin
BT10D004GB-07
VERSATEMP EQV-X
DIRECT EXPANSION HIGH EFFICIENCY
PACKAGED AIR CONDITIONER
EQV-X 5-21 RANGE
WATER-AIR HEAT PUMP
Nominal cooling capacity from 2,1 to 4,1 kW
Nominal heating capacity from 2,5 to 5,1 kW
VERSATEMP EQV-X is the highly efficient and autonomous air-conditioner which automatically heats and cools the ambient over
the entire year, using water as its source.
Thanks to its rotary compressor, electronic expansion valve, plate exchanger and multi-speed centrifuge fan, VERSATEMP EQV-X
stands out for its high efficiency in all working conditions and for its high level of reliability. Even its start-up is simplified by
specific plumbing assemblies which are available for different application solutions, supplied already installed and tested on
board.
The VERSATEMP EQV-X design can be elegantly added to different settings both in its uncased and in its cased configuration,
available for its maximum integration within furnishings. The operating silence is ensured by the particular sound-proofing of the
compressor compartment, the accurate balancing of the fans and the anti-vibration devices provided for all moving parts.
The data contained in this document are binding and may be changed by the manufacturer without obligation of prior notice.
Reproduction, even is part, is FORBIDDEN © Copyright - CLIVET S.p.A. - Feltre (BL) - Italia
Index of contents
Total comfort is required all year round, even in the most difficult application situations ......................................................................4
Highly efficient and reliable reversible electric heat pump technology .........................................................................................................4
Heat pump systems which use water as a heat source are even more efficient than traditional systems .........................................4
VERSATEMP EQV-X is the compact and silent solution for the high efficiency year round air-conditioning ....................................5
Advantages............................................................................................................................................................................................................................5
High versatility in positioning and use ........................................................................................................................................................................6
High energy efficiency all year round ..........................................................................................................................................................................7
The silent comfort ...............................................................................................................................................................................................................7
Reliability and safety ..........................................................................................................................................................................................................7
Easy to use in the small and large plants ....................................................................................................................................................................8
Perfect for the retrofit of the existing versatemp systems ...................................................................................................................................9
Ready to be connected to the water mains............................................................................................................................................................ 10
Standard unit specifications ......................................................................................................................................................................................... 11
Configuration Code ......................................................................................................................................................................................................... 13
General technical data.................................................................................................................................................................................................... 14
Electrical data .................................................................................................................................................................................................................... 15
Performances in cooling ................................................................................................................................................................................................ 16
Performance in Heating ................................................................................................................................................................................................. 17
Operating range (Cooling) ............................................................................................................................................................................................ 18
Operating range (Heating)............................................................................................................................................................................................ 18
Standard unit water circuit pressure drops............................................................................................................................................................. 19
Electric fans performance ............................................................................................................................................................................................. 19
Performance corrective coefficients in relation to the speed of the treatment fans ............................................................................... 19
Sound levels ....................................................................................................................................................................................................................... 20
Common accessories for uncased and cased unit configurations ................................................................................................................. 21
Uncased unit accessories............................................................................................................................................................................................... 29
Cased unit accessories .................................................................................................................................................................................................... 31
Option compatibility ....................................................................................................................................................................................................... 33
Dimensional drawings.................................................................................................................................................................................................... 34
BT10D004GB-07
VERSATEMP
3
Total comfort is required all year round, even in the most difficult
application situations
In applications like offices, shops, hotels and public buildings it is necessary to maintain comfort all year round, regardless of the external
conditions and the different uses of the served ambient. Each area requires its own temperature, humidity and air purification level, in the
fastest and simplest way for users.
The maintenance cost of this comfort depends on the chosen air-conditioning system, both when purchasing and above all during use
and maintenance over its working lifetime. The rationale of the chosen system and its energy efficiency are therefore fundamental factors
of choice.
Finally, an air-conditioning system must be perfectly integrated into a building, in harmony with the structure and the furniture. In some
cases, this is a very complex challenge, where, for instance, external units cannot be installed and air vents cannot be fitted, as in certain
buildings or historical structures due to regulatory or aesthetic reasons.
Highly efficient and reliable reversible electric heat pump technology
Electric heat pumps represent an efficient and advantageous choice for ambient air-conditioning. These devices enable energy to be
exchanged between the external ambient, known as the source, and the served setting, using the particular refrigeration circuit which
they are equipped with.
This transfer only requires the use of electrical energy and is highly efficient, therefore at low consumption. Furthermore, reversible electric
heat pumps simplify the system, since only one plant can operate heating and cooling requirements over the entire annual cycle.
Thanks to their energy efficiency, electric heat pumps guarantee the desired level of comfort with reduced management costs and a low
impact on the environment. For this reason there are numerous initiatives to aid their production with economic and fiscal incentives.
Heat pump systems which use water as a heat source are even more
efficient than traditional systems
In the face of apparently limited costs, direct expansion systems, for instance, split,
multisplit and VRF/VRV systems have numerous limitations in their applications. The
piping which contains the refrigerant passes through served settings and is therefore
subject to restrictions and usage limitations. It must be limited in length and insulated.
Furthermore, external units may be totally incompatible with the architectural and
constructions characteristics of the building.
Hydronic systems are without doubt more complete and versatile. Often the system costs
for medium and small sized systems are higher in that they are more highly articulated
and subject to labour costs for installation, set up and calibration. The complexity
increases even more in large-scale centralised systems with four-pipe distribution.
On the other hand, when each area is equipped with its own heat pump which uses water
as a heat source, there are only two supply pipes, which save space and installation costs
and pump usage costs. Furthermore, there are no length limitations, since they contain
water and not refrigerant. The water temperature is generally neutral in comparison
with the served ambient and therefore the pipes do not need to be insulated. By using
water as a heat source, the energy efficiency of the heat pump further increases, even
as much as by 30%.
4
VERSATEMP
BT10D004GB-07
VERSATEMP EQV-X is the compact and silent solution for the high
efficiency year round air-conditioning
EQV-X brings together the Clivet reversible heat pump technology and the VERSATEMP system reliability in a design product, which is
versatile as a fan coil.
A high efficient rotating compressor with ecological refrigerant R410A, electronic expansion valve, plate exchanger source side and multispeed fan: are only some of the solutions available in this completely automatic air-conditioner.
Thanks to the numerous models available either for uncased or cased installation, VERSATEMP EQV-X integrates perfectly into the
furnishings. Furthermore, it contains only a minimum quantity of ecological refrigerant (less than 3 kg), and is therefore not subject to
restrictions on use. The two water supply ducts do not have length limitations, even, in many cases, they do not need to be insulated and
result easy to install and maintain.
It purifies and conditions the air
in all settings
Use water as heat source
It contains the best reversible heat pump
technology in its interior
Advantages
VERSATEMP EQV-X simplifies the system
Thanks to its one-piece construction, the system components and installations are already within the unit itself. The
heat or cooling energy which is generated by the unit is directly transferred into the served ambient. The supply
water may come from an energy transfer WLHP loop circuit, from a natural source such as a well or ground water, or
even from water works in certain cases where architectural constraints make any other system solution impossible.
VERSATEMP EQV-X is silent and reduces management costs
Thanks to the numerous construction solutions which have been adopted and to its special automatic control,
vibrations and sound emissions are undoubtedly reduced. The reversible heat pump technology at high energy
efficiency maintains the required comfort only where and when it is needed, reducing the consumption and therefore
the management costs over the entire annual cycle. In all the applications which allow it, the devices which limit
water consumption reduce these expenses even further.
VERSATEMP EQV-X is the perfect solution for the system retrofit
The uncased and cased versions are compatible with VERSATEMP products of the EQV, VM, VV series as far as regards
capacities, sizes and water connections. VERSATEMP EQV-X is therefore the ideal solution for the retrofit of the existing
systems and their possible completion or enlargement.
BT10D004GB-07
VERSATEMP
5
High versatility in positioning and use
VERSATEMP EQV-X offers the maximum flexibility in positioning and integration into
various architectural contexts.
Indeed, it is available in two configurations:
•
•
an uncased configuration, which disappears within the furnishings
a cased configuration, complete with aesthetic fairing.
Complete integration into the furnishings
The uncased configuration (standard) can be requested with frontal or bottom return. The numerous accessories which are available,
further simplify its installation within the furnishings, offering the most appropriate combination at all times.
WALL UNIT WITH FRONTAL RETURN
WALL UNIT WITH BOTTOM RETURN
FLOOR MOUNTED WITH BOTTOM RETURN
WALL UNIT WITH FLEXIBLE CONNECTION AND
GRILLE
This image represents only a few of the numerous positioning possibilities.
Free positioning within the room
Versatile and pleasing to look as a fan coil, the unit in the cased configuration can be installed directly in the served room thanks to the
cover fairing, to its silence during operating, to its various positioning solutions and to the model with a rear aesthetic panel suitable for
installation near glass walls.
WALL UNIT WITH FRONTAL RETURN
WALL UNIT WITH BOTTOM RETURN
FLOOR MOUNTED WITH BOTTOM RETURN
FLOOR MOUNTED WITH REAR AESTHETIC PANEL
This image represents only a few of the numerous positioning possibilities.
6
VERSATEMP
BT10D004GB-07
High energy efficiency all year round
VERSATEMP EQV-X raises the overall efficiency of the system thanks to its technological solutions,
all chosen for an efficient and long-lasting operation and guaranteed by strict quality checks during
the assembly phase and rigorous operating tests on the final product.
High efficiency rotary compressor
With silent and reliable operation, it uses the ecological refrigerant R410A and it is contained within
a special compartment which has been further sound-proofed.
Electronic expansion valve
The electronic expansion valve (EEV) rapidly and precisely adapts to the effective load required. Furthermore, in the heat pump operation
it ensures stability also with high water temperatures.
Source side plate exchanger
Universally recognised for its highly efficient heat exchange, it is complete with a regulation probe
and safety device and is offered with a matching mechanical steel knit strainer which can ensure
excellent performance over time.
Multi-speed fan
The EXTRAQUIET, QUIET and POWERFUL speeds allow to achieve always the best operating
conditions in the different applications. In the AUTO mode, the unit automatically sets the most
appropriate speed to quickly reach the comfort conditions, thanks to the automatic compensation
depending on the distance between the effective temperature in the served room and the set-point.
The silent comfort
The compressor is housed in a dedicated compartment, made of thick stainless steel and covered
with sound-proofing material. It is equipped with a double anti-vibration support system, a vibration
sound absorber in the refrigerant circuit, and also with a metal closure hood and finishing in the
cased configuration.
At the end of the steady state phase, the AUTO fan mode activation maintains furthermore the
minimum speed necessary to maintain the comfort, further increasing the acoustic comfort in the
room.
Reliability and safety
Among the numerous adopted solutions, are:
•
The combination of outlet water anti-freeze sensor, treated air anti-freeze sensor, inlet water
temperature sensor and water flow-rate monitoring device protects the unit from the ice
formation and any malfunctioning which may derive from it.
•
The thermostatic valve with MOP (Maximum Operating Pressure) function automatically
controls the evaporating pressure to an optimal value for the efficient compressor operating,
even upon changes of the heat exchange conditions with the water source.
•
The electronic control of the thermostatic valve also uses dynamic algorithms, managing the
regularity of the refrigerant flow in the circuit and ensuring a compressor stable operating and,
therefore, an increase of its efficiency and operating life.
BT10D004GB-07
VERSATEMP
7
Easy to use in the small and large plants
VERSATEMP EQV-X is extremely versatile and reliable even in solutions controlled by the User.
Standard automatic functions
The standard VERSATEMP EQV-X version is equipped with a standard automatic control, complete
with a micro processor card and control and safety sensors built-in. Given that it is without a user
display, this version represents an efficient solution in all applications open to the public where the
operating parameters could otherwise be inappropriately changed:
•
•
•
it detects the room conditions and compares them with the user set point
•
it can manage without further accessories a mini local network of 15 units, one of which is a
master and the others slaves which replicate its operating.
it can decide the operating mode automatically (heating or cooling)
it decides the activation of resources and can automatically select the fan speed depending on
the distance from the scheduled set point
Voltage-free contact user interface
The standard version has a series of voltage-free contacts, or rather contacts without tension, for managing the following
functions remotely: Switching on and switching off, Changing function mode (heating or cooling), setting the Set point
(standard or economic).
User interface with built-in or wall display
Both the uncased and the cased unit configuration can be equipped with an electronic room control with
a display. The control can be built-in supplied or pre-set for wall installation. It has a modern aspect and
is very simple to use even for non-specialised users. Furthermore, it has different access levels, password
protected, available for managing the different unit functions.
Among the main functions, it detects the temperature using the temperature sensor in its interior,
schedules the operating time bands, displays and manages the operating alarms and parameters, enables
the manual management of the fan speed and operating mode (heating or cooling).
BUILT-IN INSTALLATION
on uncased unit
REMOTE INSTALLATION
on cased unit
on the wall
in a uncased box
User interface by serial connection
Thanks to the different communication protocols available, the unit is able to exchange
information with the main supervisory systems using serial connections.
8
VERSATEMP
BT10D004GB-07
Perfect for the retrofit of the existing versatemp systems
VERSATEMP EQV-X can be easily installed in the existing systems to substitute or
integrate VERSATEMP units of the EQV, VM, and VV series thanks to:
•
•
•
delivered capacity and water connection compatibility
same or smaller sizes
different protocols available for the supervision Systems
The units have been set for two different types of intervention work:
•
•
total substitution (all the units in the system)
partial substitution (only some of the units in the system)
In case of total substitution
The total substitution of VERSATEMP EQV, VM and VV units can be carried out without
any changes of the water components of the system (such as pumps, ducts, by-passes)
and without balancing interventions.
Indeed, the new VERSATEMP EQV-X units are able to correctly operate even when they
are powered with water flow-rates of the substituted units, which are typically lower
than the nominal flow. Furthermore, they have lower pressure drops on the exchanger
water side. A new hydraulic equilibrium is established in the system.
If the intention is to make the units operate with the same water flow-rate of the
substituted units, even though it is not necessary, it is sufficient only to provide a flow
controller on each unit and on the main system ducting.
In case of partial substitution
If only some units are substituted on the existing VERSATEMP system, it is necessary to
provide a flow controller which balances the branch where the new units are installed.
Indeed, due to the lower pressure drops of the EQV-X, the system can be unbalanced as
follows:
•
excessive reduction of the water flow-rate on branches that maintain the existing
units
•
increase of the water flow-rate on branches equipped with new units.
It is therefore necessary to provide for a flow controller on each unit (available as an
accessory), or on the whole branch involved with the substitution.
BT10D004GB-07
VERSATEMP
9
Ready to be connected to the water mains
The system components for the VERSATEMP EQV-X connection to the water supply circuit are available built-in. Thanks to their easily
accessible position, installation and routine maintenance are notably simplified. Furthermore, reliability is increased since the seal and
functionality of the parts are tested at the end of the production process. Thanks to the specific pipe work options are available, the unit
integrates perfectly within different types of water systems whether loop systems or using aqueduct or disposable water. Each component
has been accurately designed to guarantee the maximum operating efficiency and protect the high efficiency exchanger water side from
fouling.
The functions of the standard version
The unit without optional hydraulic pipework arrangement is complete with plate exchanger and control and safety devices, both in the
uncased and in the cased version.
The other system components needed for the connection to the water supply are available as accessories,
for installation by the Client:
•
•
•
•
•
steel mesh strainer
manual shut-off valves
manual by-pass valve for the system cleaning
manual balancing valve
flexible pipes for water supply and condensate drain
Standard unit (without hydraulic pipework arrangements)
The reliability and versatility of the hydraulic pipework
The unit can be supplied complete with pipe work arrangements built-in, with what is necessary for the correct start-up and use of the
system in the different types of systems: constant flow loop, variable flow loop. Indeed, the pipe work arrangements enable the unit to be
intercepted from the system, the system cleaning (fluxing), the water mechanical filtration during the ordinary operating to protect the
exchanger from fouling.
The 2-way modulating valve, available as accessory, allows to:
•
further extend the application range to systems fed with well water, groundwater or aqueduct. It is so possible to reduce the water
consumption
•
•
extend the standard unit operating field in cooling mode with source at low water temperature
maximize the efficiency in heating mode also with source at high water temperature.
In the presence of the 2-way modulating valve, the water feeding must be at variable flow. This allows an interesting energy saving on the
installation and then a further reduction of the management costs.
A - Manual shut-off valve
B - Stell mesh filter
C - Cleaning by-pass
D - ON-OFF motorised 2-way valve
E - Modulating motorised 2-way valve
APPLICATION: CONSTANT FLOW RATE LOOP
APPLICATION: VARIABLE FLOW RATE LOOP
APPLICATION: WASTE WATER SYSTEM
* To instal outside the unit
The version compatibility for the system retrofit
The unit can be set for the rapid replacement (retrofit) of VERSATEMP EQV, VM and VV units. For loop systems with constant water flow-rate.
This execution includes:
•
•
water inlet and outlet lines in the same position and of the same type of the units to substitute;
steel mesh filter, water side.
Retrofit EQV, VM, VV units at constant flow
10
VERSATEMP
BT10D004GB-07
Standard unit specifications
Compressor
Hermetic rotary compressor with gas compression in the crankcase, direct suction, no oil heater. It is mounted on antivibration rubber pads. Includes oil
feed.
Structure
Structure made entirely from “aluzink” plate that guarantees excellent mechanical characteristics and high corrosion strength over time. The compressor
area is made from thick metal plate and is completely insulated with soundproofing material to minimise noise output. The ventilating section is completely
lined with anti-condensate and soundproofing material.
Internal exchanger
Direct expansion finned exchanger, made of copper pipes in staggered rows and mechanically expanded to the fin collars. The fins are made of aluminium
with a corrugated surface and adequately distanced to ensure the maximum heat exchange efficiency.
External exchanger source side (water)
Direct expansion heat exchanger with braze welded stainless steel INOX AISI 316 plates and complete with external thermal/anti-condensation insulation.
The exchanger is complete with:
differential pressure switch, water side
inlet water temperature sensor
outlet water temperature sensor, with antifreeze protection
•
•
•
•
vent valve
Fan
Dual intake centrifugal fan with forward blades for maximum efficiency and low noise. Statically- and dynamically-balanced according to the ISO 1940
standards, section 6.3. The scroll, the rotor and the frame are made from galvanized steel plate (semdzimir). Directly coupled to the three speed electric
motor.
Refrigeration circuit
Flat filter, made up of a galvanized plate frame with galvanized and electric-welded protective mesh and 100% regenerable polyester filtering media
with PVC resin. G2 efficiency according to CEN-EN 779 standard (Eurovent class EU4/5 - average efficiency 79% ASHRAE 52-76 Atm). Self-extinguishing
(resistance to fire class 1 - DIN 53438).
Drain pan
Condensate collecting tray plate “Aluzink” welded, fitted with a discharge coupling and covered externally with anti-condensate insulation.
Electrical panel
The electrical panel, consisting of a microprocessor control, is located inside the unit and can be accessed via a panel which can be easily removed.
The capacity section includes:
power input terminals
main fuse
•
•
The control section includes:
microprocessor control
self-test system
switch on and off daily and weekly programmer and set point
cumulative alarms, potential-free contacts for remote ON-OFF, summer/winter mode, ECO set-point setting, water flow-rate
antifreeze protection on the air side
antifreeze protection water side
no water flow-rate protection
return air temperature probe with thermoregulation function
manual or automatic fan speed selection
connector for connection of the optional electronic room control
•
•
•
•
•
•
•
•
•
•
Casing (only cased configuration)
Removable fairing, made from 10/10 thick steel, power painted (RAL9003 colour, smooth texture). The top-side fittings allow easy access to the internal
components.
BT10D004GB-07
VERSATEMP
11
Accessories
Unit in uncased and cased configuration
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
Front return (FR)
Water balancing valve (Accessory separately supplied)
Steel mesh filter (Accessory separately supplied)
Condensate drain pump, built-in
Condensate drain pump (Accessory separately supplied)
200 mm flexible pipes for the connection to the water circuit + drop conduit (Accessory separately supplied)
500 mm flexible pipes for the connection to the water circuit + drop conduit (Accessory separately supplied)
Couple of manual shut-off valves (accessory provided separately)
Hydraulic pipework arrangement for loop with constant flow rate with manual valves
Hydraulic pipework arrangement for loop with variable flow rate with 2 way ON-OFF valve
2-way modulating valve for disposable water system (Accessory separately supplied)
Constant flow retrofit water connections for EQV,VV,VM units
Electronic room control with display, for wall installation in built-in box (Accessory separately supplied)
Serial port RS485 with MODBUS protocol, built-in
RS485 Serial port with Modbus protocol (Accessory separately supplied)
BACnet serial communication module (Accessory separately supplied)
LonWorks serial communication module (Accessory separately supplied)
Unit in uncased configuration
•
•
•
•
•
Electronic room control with display, for installation on the uncased unit (Accessory separately supplied)
Air supply duct with flexible connection (Accessory separately supplied)
Air supply grille with flexible connection (Accessory separately supplied)
Increased zinc-coated plinths for floor fixing on uncased unit (Accessory separately supplied)
Increased zinc-coated plinths for floor fixing on uncased unit (Accessory separately supplied)
Unit in cased configuration
•
•
•
•
•
•
Electronic room control with display, installed in a visible position on the unit with fairing
Painted plinths for floor fixing (Accessory separately supplied)
Painted plinths for floor fixing with front grille and rear closing panel (Accessory separately supplied)
Painted rear panel for cased version
Rear closing panel for painted plinths
2-waysmodulating valve fixing kit for disposable water system Accessory separately supplied
NOTE: The compatibility of the different options is shown in the table at the end of the “Accessory” section.
12
VERSATEMP
BT10D004GB-07
Configuration Code
(1) Configuration
UC - Uncased version (without casing)
CAB - Configuration with fairing for uncased applications
(5) Condensate drain pump
Condensate drain pump: (-) not required (standard)
CDPA - Condensate drain pump, built-in
(2) Room thermostat
Electronic room control (-) not required (standard)
CONT - Electronic room control with display, installed in a visible position on the unit with fairing
(6) Remote communication serial port
Remote communication serial port: (-) not required (standard)
MOBA - RS485 serial port with Modbus protocol, built-in
(3) Return
R3 - Intake from below (standard)
RF - Front air intake
(7) Unit installation
Painted rear panel for uncased version: (-) not requested (standard)
BACKV - Painted rear panel for uncased version
(4) Hydraulic module
Hydraulic pipework arrangement: (-) not required (standard)
MIPC - Hydraulic pipework arrangement for loop with constant flow rate with manual valves
MIPV - Hydraulic pipework arrangement for loop with variable flow with 2-way ON-OFF valve
REQV - Constant flow retrofit water connections for EQV,VV,VM units
BT10D004GB-07
VERSATEMP
13
General technical data
Size
5
7
9
15
17
21
Cooling
Cooling capacity
1
kW
2.08
2.39
2.88
3.38
3.75
4.11
Sensible capacity
1
kW
1.47
1.69
2.12
2.55
2.64
3.05
Compressor power input
1
kW
0.43
0.56
0.61
0.71
0.77
0.84
Total power input
2
kW
0.49
0.62
0.67
0.81
0.87
0.96
EER (EN14511:2011)
2
4.19
3.78
4.20
4.09
4.22
4.20
Heating
Heating capacity
3
kW
2.54
3.05
3.55
4.29
4.78
5.10
Compressor power input
3
kW
0.47
0.63
0.70
0.77
0.92
1.04
Total power input
4
kW
0.53
0.69
0.76
0.87
1.02
1.16
COP (EN 14511:2011)
4
4.91
4.49
4.71
5.05
4.72
4.49
Heating
Heating capacity
5
kW
2.33
2.73
3.10
3.82
4.17
4.68
Compressor power input
5
kW
0.46
0.60
0.65
0.75
0.89
1.01
Total power input
6
kW
0.52
0.66
0.71
0.85
0.99
1.13
COP (EN 14511:2011)
6
4.60
4.21
4.41
4.62
4.30
4.24
7
ROT
ROT
ROT
ROT
ROT
ROT
Compressor
Type of compressors
No. of compressors
No
1
1
1
1
1
1
Refrigerant charge (C1)
kg
0.57
0.62
0.70
0.74
0.71
0.80
CFG
CFG
CFG
CFG
CFG
CFG
Air Handling Section Fans (Supply)
Type of fans
8
Airflow
l/s
106
128
126
208
208
231
Airflow
m3/h
380
460
455
750
750
830
PHE
PHE
PHE
PHE
PHE
PHE
Water side exchanger
Type of exchanger
9
Water flow-rate
10
l/s
0.12
0.14
0.17
0.19
0.21
0.24
Pressure drop
11
kPa
33
26
29
19
23
28
Connections
Water fittings
12
1/2”
1/2”
1/2”
1/2”
1/2”
1/2”
Condensate drain
13
15
15
15
15
15
15
V
230/1/50
230/1/50
230/1/50
230/1/50
230/1/50
230/1/50
dB(A)
41
41
41
45
45
47
Power supply
Standard power supply
Noise Levels
Sound pressure level (1 m)
The Product is compliant with the Erp (Energy Related Products) European Directive. It includes the Commission
delegated Regulation (EU) No 2016/2281, also known as Ecodesign Lot21.
Performances referred to the standard speed fan (Quiet)
A 27/19 W 30 = Unit inlet air temperature 27°C D.B. / 19°C W.B. Unit inlet water temper
A 20 W 20 = Unit inlet air temperature 20°C Unit inlet water temperature 20°C
A 20 W 15 = Inlet air temperature 20°C Inlet water temperature 15°C
DB = dry bulb WB = wet bulb
1. Ambient air 27°C D.B./19°C W.B. Exchanger water temperature 30°C / 35°C. Performance not including fan motor
capacity
2. Ambient air 27°C D.B./19°C W.B. Exchanger water temperature 30°C / 35°C. Values read in compliance with
EN14511:2011 and including the required system fan motor and water pump capacity for overcoming pressure drops
inside the unit.
3. Ambient temperature 20°C D.B. Exchanger inlet water 20°C. Exchanger outlet water temperature is set in relation
to the water flow in cooling. Performance not including fan motor capacity
4. Ambient temperature 20°C D.B. Exchanger inlet water 20°C. Exchanger outlet water temperature is set in relation
to the water flow in cooling. Values read in compliance with EN14511:2011 and including the required system fan
motor and water pump capacity for overcoming pressure drops inside the unit.
14
5. Ambient air 20°C D.B. Exchanger inlet water temperature 15°C. The water temperature at the exchanger output is
read in relation to the flow of water being chilled. Performance not including fan motor capacity
6. Ambient air 20°C D.B. Exchanger inlet water temperature 15°C
The water temperature at the exchanger output is read in relation to the flow of water being chilled.
Values read in compliance with EN14511:2011 and including the required system fan motor and water pump
capacity for overcoming pressure drops inside the unit.
7. ROT = rotary compressor
8. CFG = centrifugal fan
9. PHE = plate exchanger
10. Water flow calculated in relation to the performances in cooling
11. Total pressure drop of the standard unit (without optional hydraulic pipe works). To obtain the total drops with
any additional hydraulic components see accessory section.
12. Inlet / outlet
13. Pipe outside diameter
Max. working pressure water side 10 bar.
VERSATEMP
BT10D004GB-07
Electrical data
Size
5
7
9
15
17
21
F.L.A. - Full load current at max admissible conditions
F.L.A. - Compressor 1
A
2.82
3.50
3.90
4.55
5.13
5.86
F.L.A. - Single supply fan
A
0.35
0.66
0.66
0.74
0.74
0.74
A
3.17
4.16
4.56
5.29
5.87
6.60
F.L.A. - Total
1
F.L.I. - Full load power input at max admissible conditions
F.L.I. - Compressor 1
kW
0.65
0.75
0.85
1.02
1.12
1.25
F.L.I. - Single External Fan
kW
0.080
0.15
0.15
0.17
0.17
0.17
kW
0.73
0.90
1.00
1.19
1.29
1.42
A
18.4
19.7
20.7
22.2
26.0
26.2
F.L.I. - Total
2
M.I.C. Maximum inrush current
M.I.C. - Value
Data refer to standard units.
Power supply: 230/1/50 Hz. Voltage variation: max. +/-10%
1. Values not including the accessories. To obtain the value of F.L.A. including accessories, add to the total F.L.A. value that of any accessories (see electrical data of accessories)
2. Values not including the accessories. To obtain the F.L.I. value including the accessories add to the F.L.I. value the value of any accessories (see the electrical data of the accessories)
BT10D004GB-07
VERSATEMP
15
Performances in cooling
Size
Ta °C
DB/
WB
22 / 16
24 / 17
26 / 18
5
27 / 19
28 / 20
30 / 22
22 / 16
24 / 17
26 / 18
7
27 / 19
28 / 20
30 / 22
22 / 16
24 / 17
26 / 18
9
27 / 19
28 / 20
30 / 22
22 / 16
24 / 17
26 / 18
15
27 / 19
28 / 20
30 / 22
22 / 16
24 / 17
26 / 18
17
27 / 19
28 / 20
30 / 22
22 / 16
24 / 17
26 / 18
21
27 / 19
28 / 20
30 / 22
20 / 25
25 / 30
30 / 35
35 / 40
40 / 45
45 / 50
kWf
kWs
kWe
EER
kWf
kWs
kWe
EER
kWf
kWs
kWe
EER
kWf
kWs
kWe
EER
kWf
kWs
kWe
EER
kWf
kWs
kWe
EER
1,93
2,01
2,09
2,17
2,26
2,44
2,19
2,3
2,4
2,51
2,63
2,87
2,62
2,72
2,83
2,95
3,07
3,32
3,2
3,32
3,44
3,56
3,69
3,95
3,74
3,87
4,01
4,14
4,28
4,56
4,09
4,22
4,35
4,48
4,62
4,91
1,31
1,39
1,48
1,5
1,53
1,65
1,51
1,59
1,69
1,74
1,83
2,15
1,87
1,99
2,11
2,13
2,18
2,36
2,31
2,49
2,65
2,61
2,54
2,27
2,52
2,67
2,82
2,81
2,81
2,81
2,88
3,08
3,26
3,22
3,17
2,98
0,36
0,35
0,35
0,35
0,34
0,33
0,4
0,39
0,38
0,38
0,37
0,35
0,54
0,53
0,52
0,5
0,49
0,46
0,58
0,58
0,58
0,58
0,58
0,58
0,73
0,73
0,72
0,72
0,72
0,72
0,67
0,67
0,67
0,68
0,69
0,71
5,4
5,66
5,95
6,26
6,58
7,31
5,52
5,89
6,27
6,69
7,13
8,1
4,83
5,15
5,49
5,88
6,3
7,29
5,49
5,72
5,95
6,18
6,4
6,83
5,11
5,32
5,53
5,74
5,95
6,36
6,14
6,3
6,45
6,59
6,71
6,94
1,92
1,99
2,07
2,14
2,22
2,39
2,18
2,27
2,37
2,46
2,57
2,78
2,62
2,72
2,83
2,94
3,05
3,3
3,15
3,26
3,37
3,49
3,61
3,87
3,57
3,69
3,82
3,95
4,09
4,37
3,91
4,03
4,16
4,29
4,42
4,7
1,31
1,39
1,47
1,48
1,51
1,63
1,49
1,57
1,67
1,72
1,8
2,12
1,87
1,98
2,11
2,13
2,17
2,36
2,28
2,46
2,62
2,58
2,51
2,24
2,44
2,59
2,73
2,72
2,72
2,74
2,8
3
3,17
3,14
3,08
2,87
0,39
0,39
0,39
0,38
0,38
0,37
0,48
0,48
0,47
0,47
0,46
0,45
0,57
0,56
0,55
0,54
0,53
0,52
0,64
0,64
0,63
0,63
0,63
0,63
0,74
0,74
0,74
0,73
0,73
0,73
0,76
0,76
0,76
0,76
0,77
0,78
4,92
5,14
5,36
5,61
5,87
6,44
4,53
4,77
5,02
5,29
5,58
6,22
4,62
4,86
5,13
5,41
5,72
6,41
4,93
5,12
5,32
5,52
5,73
6,15
4,83
5,01
5,19
5,38
5,57
5,97
5,18
5,33
5,47
5,62
5,77
6,06
1,88
1,94
2,01
2,08
2,15
2,3
2,14
2,22
2,3
2,39
2,48
2,67
2,57
2,67
2,77
2,88
2,99
3,23
3,06
3,16
3,27
3,38
3,5
3,74
3,39
3,51
3,63
3,75
3,89
4,16
3,75
3,87
3,99
4,11
4,24
4,52
1,3
1,38
1,46
1,47
1,5
1,6
1,48
1,55
1,65
1,69
1,77
2,09
1,87
1,98
2,1
2,12
2,17
2,35
2,25
2,43
2,59
2,55
2,48
2,22
2,36
2,5
2,64
2,64
2,64
2,66
2,72
2,92
3,09
3,05
2,99
2,77
0,44
0,44
0,43
0,43
0,43
0,42
0,57
0,56
0,56
0,56
0,55
0,54
0,62
0,61
0,61
0,61
0,6
0,59
0,71
0,71
0,71
0,71
0,7
0,7
0,77
0,77
0,77
0,77
0,77
0,77
0,84
0,84
0,84
0,84
0,84
0,84
4,29
4,46
4,63
4,84
5,02
5,45
3,77
3,94
4,12
4,27
4,5
4,94
4,17
4,35
4,54
4,72
4,96
5,43
4,3
4,46
4,62
4,76
4,97
5,36
4,38
4,54
4,69
4,87
5,03
5,4
4,48
4,61
4,75
4,89
5,04
5,35
1,79
1,85
1,91
1,98
2,04
2,18
2,06
2,13
2,21
2,29
2,37
2,54
2,48
2,57
2,67
2,77
2,88
3,1
2,93
3,03
3,13
3,24
3,35
3,57
3,2
3,31
3,43
3,55
3,67
3,94
3,6
3,72
3,84
3,96
4,08
4,34
1,3
1,37
1,45
1,46
1,48
1,57
1,46
1,53
1,62
1,66
1,74
2,06
1,87
1,98
2,1
2,12
2,16
2,34
2,22
2,4
2,56
2,52
2,45
2,19
2,27
2,42
2,56
2,55
2,55
2,58
2,65
2,84
3,01
2,97
2,9
2,66
0,5
0,5
0,5
0,49
0,49
0,49
0,65
0,65
0,65
0,64
0,64
0,64
0,69
0,69
0,69
0,69
0,69
0,69
0,8
0,8
0,8
0,8
0,79
0,79
0,83
0,83
0,84
0,84
0,84
0,84
0,91
0,91
0,91
0,91
0,91
0,91
3,6
3,73
3,86
4
4,15
4,48
3,17
3,29
3,42
3,55
3,69
4,01
3,58
3,71
3,85
4
4,15
4,48
3,67
3,8
3,93
4,07
4,21
4,53
3,84
3,97
4,1
4,24
4,39
4,71
3,95
4,07
4,2
4,33
4,47
4,77
1,67
1,72
1,78
1,84
1,9
2,03
1,96
2,02
2,09
2,16
2,24
2,39
2,35
2,43
2,52
2,62
2,72
2,92
2,76
2,86
2,95
3,05
3,15
3,36
3
3,11
3,21
3,33
3,44
3,69
3,47
3,58
3,7
3,82
3,94
4,19
1,3
1,37
1,44
1,44
1,46
1,55
1,44
1,51
1,6
1,64
1,71
2,03
1,86
1,97
2,09
2,11
2,16
2,34
2,19
2,37
2,52
2,49
2,42
2,16
2,19
2,33
2,47
2,47
2,47
2,5
2,57
2,76
2,93
2,88
2,81
2,56
0,57
0,57
0,57
0,57
0,57
0,57
0,74
0,74
0,73
0,73
0,73
0,73
0,79
0,8
0,8
0,8
0,8
0,81
0,9
0,9
0,9
0,9
0,9
0,9
0,92
0,92
0,92
0,92
0,92
0,92
0,98
0,98
0,98
0,98
0,98
0,98
2,92
3,01
3,11
3,22
3,33
3,58
2,66
2,75
2,85
2,95
3,05
3,28
2,95
3,05
3,16
3,26
3,38
3,61
3,06
3,16
3,27
3,38
3,5
3,74
3,26
3,37
3,48
3,6
3,73
3,99
3,55
3,66
3,77
3,89
4,02
4,29
1,5
1,56
1,61
1,66
1,72
1,84
1,82
1,88
1,95
2,01
2,08
2,22
2,16
2,24
2,33
2,42
2,5
2,69
2,55
2,64
2,73
2,83
2,92
3,1
2,79
2,89
2,99
3,1
3,2
3,42
3,36
3,47
3,58
3,69
3,81
4,05
1,29
1,36
1,43
1,43
1,44
1,52
1,43
1,49
1,58
1,61
1,68
1,99
1,86
1,97
2,09
2,11
2,15
2,33
2,16
2,33
2,49
2,46
2,39
2,14
2,1
2,25
2,39
2,38
2,39
2,42
2,49
2,68
2,85
2,8
2,72
2,45
0,66
0,66
0,66
0,66
0,66
0,66
0,82
0,82
0,82
0,82
0,82
0,82
0,92
0,93
0,93
0,93
0,94
0,94
1,02
1,02
1,02
1,03
1,03
1,03
1,03
1,04
1,04
1,04
1,04
1,04
1,04
1,04
1,04
1,04
1,04
1,04
2,29
2,36
2,44
2,52
2,6
2,79
2,21
2,29
2,37
2,45
2,53
2,69
2,35
2,43
2,51
2,59
2,67
2,85
2,5
2,58
2,67
2,75
2,84
3,02
2,7
2,79
2,89
2,99
3,09
3,3
3,23
3,33
3,43
3,54
3,65
3,89
Performances referred to the standard speed fan (Quiet)
EER referred only to compressors
Ta = Entering air temperature to the air handling coil (°C)
DB = dry bulb WB = wet bulb
kWf = Cooling capacity in kW
kWe = Electrical power absorbed by compressors (kW)
kWs = Sensible cooling capacity (kW)
Not all cooling yields take into account the heat dissipated by the fan motors
16
VERSATEMP
BT10D004GB-07
Performance in Heating
Size
5
7
9
15
17
21
Ta (°C)
DB
10
15
18
20
22
25
30
10
15
18
20
22
25
30
10
15
18
20
22
25
30
10
15
18
20
22
25
30
10
15
18
20
22
25
30
10
15
18
20
22
25
30
kWt
2,08
2,09
2,09
2,08
2,07
2,04
1,98
2,47
2,48
2,47
2,46
2,44
2,4
2,32
2,8
2,79
2,77
2,75
2,73
2,7
2,63
3,44
3,41
3,39
3,37
3,34
3,31
3,24
4,07
3,89
3,8
3,74
3,69
3,62
3,53
4,47
4,35
4,28
4,23
4,18
4,11
3,99
12 / 7
kWe
0,37
0,41
0,43
0,44
0,46
0,48
0,53
0,45
0,52
0,55
0,58
0,6
0,63
0,68
0,54
0,57
0,6
0,62
0,64
0,67
0,75
0,62
0,67
0,7
0,73
0,75
0,79
0,87
0,82
0,83
0,85
0,87
0,9
0,94
1,03
0,8
0,88
0,93
0,97
1,01
1,06
1,16
COP
5,59
5,15
4,88
4,69
4,5
4,21
3,74
5,5
4,8
4,46
4,25
4,06
3,79
3,4
5,14
4,86
4,64
4,47
4,29
4
3,52
5,53
5,09
4,82
4,63
4,44
4,17
3,72
4,99
4,67
4,44
4,28
4,11
3,85
3,43
5,62
4,94
4,58
4,36
4,16
3,87
3,45
kWt
2,31
2,3
2,29
2,27
2,25
2,22
2,14
2,75
2,72
2,69
2,66
2,64
2,59
2,5
3,08
3,06
3,03
3,01
2,99
2,94
2,85
3,8
3,76
3,74
3,71
3,68
3,63
3,54
4,39
4,22
4,12
4,06
4
3,93
3,81
4,81
4,7
4,62
4,58
4,53
4,45
4,32
15 / 10
kWe
0,38
0,41
0,44
0,46
0,47
0,5
0,55
0,47
0,54
0,57
0,6
0,62
0,66
0,71
0,54
0,58
0,62
0,64
0,67
0,71
0,79
0,62
0,68
0,72
0,74
0,77
0,82
0,9
0,81
0,84
0,86
0,89
0,92
0,96
1,07
0,82
0,91
0,96
1
1,04
1,1
1,2
COP
6,14
5,56
5,21
4,99
4,76
4,43
3,9
5,85
5,06
4,67
4,45
4,24
3,95
3,53
5,71
5,23
4,91
4,7
4,48
4,16
3,63
6,17
5,57
5,22
4,99
4,76
4,44
3,92
5,43
5,05
4,77
4,58
4,37
4,07
3,57
5,85
5,16
4,8
4,57
4,36
4,05
3,61
kWt
2,46
2,43
2,4
2,38
2,36
2,32
2,24
2,92
2,87
2,83
2,8
2,76
2,71
2,61
3,28
3,24
3,21
3,19
3,16
3,11
3,01
4,03
3,99
3,95
3,92
3,89
3,84
3,73
4,62
4,44
4,35
4,29
4,23
4,14
4,01
5,04
4,91
4,83
4,78
4,73
4,65
4,52
17 / 12
kWe
0,38
0,42
0,44
0,46
0,48
0,51
0,56
0,48
0,55
0,59
0,61
0,64
0,67
0,72
0,54
0,6
0,63
0,66
0,69
0,73
0,81
0,62
0,68
0,72
0,75
0,78
0,83
0,92
0,81
0,84
0,87
0,9
0,93
0,98
1,09
0,84
0,93
0,98
1,02
1,06
1,12
1,22
COP
6,48
5,8
5,41
5,17
4,92
4,56
4,01
6,06
5,21
4,81
4,59
4,35
4,05
3,62
6,05
5,43
5,07
4,83
4,6
4,25
3,72
6,53
5,85
5,46
5,23
4,96
4,6
4,05
5,71
5,29
4,99
4,77
4,56
4,22
3,68
5,99
5,3
4,93
4,69
4,47
4,16
3,7
kWt
2,66
2,59
2,54
2,51
2,48
2,44
2,37
3,17
3,08
3,03
2,99
2,95
2,89
2,8
3,59
3,53
3,49
3,46
3,42
3,37
3,28
4,38
4,3
4,25
4,21
4,18
4,11
4
4,96
4,8
4,71
4,65
4,58
4,49
4,33
5,39
5,2
5,1
5,04
4,98
4,9
4,79
20 / 15
kWe
0,38
0,42
0,45
0,47
0,48
0,51
0,57
0,5
0,57
0,6
0,63
0,65
0,69
0,74
0,55
0,62
0,66
0,69
0,72
0,77
0,85
0,63
0,69
0,74
0,77
0,8
0,85
0,95
0,82
0,85
0,89
0,92
0,95
1
1,12
0,87
0,95
1
1,04
1,08
1,14
1,25
COP
6,95
6,14
5,69
5,34
5,13
4,74
4,16
6,34
5,43
5
4,75
4,52
4,21
3,77
6,48
5,68
5,25
5,01
4,74
4,39
3,86
6,95
6,2
5,76
5,47
5,22
4,83
4,23
6,07
5,63
5,31
5,05
4,84
4,47
3,87
6,17
5,48
5,1
4,85
4,63
4,31
3,84
kWt
2,98
2,8
2,71
2,66
2,62
2,58
2,54
3,55
3,41
3,33
3,29
3,24
3,18
3,07
4,14
4,02
3,96
3,92
3,89
3,84
3,78
4,94
4,77
4,69
4,63
4,58
4,51
4,42
5,56
5,45
5,36
5,3
5,23
5,11
4,88
6
5,63
5,46
5,36
5,29
5,2
5,15
25 / 20
kWe
0,39
0,42
0,45
0,46
0,48
0,51
0,57
0,53
0,59
0,63
0,65
0,68
0,71
0,77
0,59
0,68
0,73
0,76
0,79
0,84
0,91
0,67
0,72
0,76
0,79
0,82
0,88
0,98
0,85
0,89
0,92
0,95
0,98
1,04
1,15
0,94
0,98
1,02
1,05
1,09
1,15
1,27
COP
7,65
6,63
6,09
5,75
5,44
5,02
4,43
6,73
5,77
5,3
5,04
4,79
4,47
4
6,97
5,92
5,43
5,15
4,9
4,58
4,13
7,33
6,6
6,16
5,86
5,58
5,16
4,52
6,53
6,12
5,8
5,57
5,32
4,93
4,26
6,41
5,72
5,33
5,09
4,85
4,53
4,06
kWt
3,05
2,87
2,78
2,73
2,69
2,65
2,61
3,59
3,45
3,38
3,33
3,29
3,23
3,12
4,19
4,07
4,01
3,97
3,93
3,89
3,82
4,99
4,82
4,74
4,68
4,63
4,56
4,47
5,59
5,48
5,39
5,33
5,26
5,14
4,9
6,04
5,67
5,5
5,41
5,33
5,25
5,19
35 / 30
kWe
0,41
0,45
0,47
0,49
0,51
0,54
0,6
0,59
0,65
0,69
0,71
0,73
0,77
0,83
0,64
0,73
0,78
0,81
0,84
0,89
0,96
0,72
0,77
0,81
0,84
0,87
0,93
1,03
0,88
0,92
0,95
0,98
1,01
1,07
1,17
1
1,05
1,09
1,12
1,16
1,22
1,34
COP
7,36
6,42
5,92
5,6
5,31
4,92
4,37
6,14
5,32
4,92
4,69
4,47
4,19
3,78
6,53
5,6
5,16
4,91
4,68
4,39
3,98
6,89
6,24
5,84
5,58
5,31
4,94
4,35
6,35
5,96
5,66
5,43
5,19
4,82
4,18
6,03
5,4
5,05
4,82
4,61
4,31
3,89
Performances referred to the standard speed fan (Quiet)
COP referred only to compressors
Ta = Entering air temperature to the air handling coil (°C)
DB = dry bulb
kWt = Provided heating capacity (kW)
kWe = Electrical power absorbed by compressors (kW)
Not all cooling yields take into account the heat dissipated by the fan motors
BT10D004GB-07
VERSATEMP
17
Operating range (Cooling)
The limits are meant as an indication and they have been calculated by considering:
•
general and non specific sizes
•
standard airflow (Fan speed: Medium speed (M))
•
non-critical positioning and correct use of the unit
•
operation at full load
•
difference between inlet / outlet water temperature = 5°C
Ta = handling air coil entering air temperaturE (°C)
WARNING! WET BULB TEMPERATURE
(W.B. = WET BULB)
TH2O = Water temperature at plate exchanger input (°C)
WET BULB TEMPERATURE - EXAMPLE
1. Standard operating range
2. Operating field for unit equipped with ‘V2MODX - 2-way modulating valve
for installation with disposable water’ option, i.e. well water, aqueduct,
groundwater or anyway a source at low water temperature. by this option the
water feeding system must be at variable flow.
Operating range (Heating)
The limits are meant as an indication and they have been calculated by
considering:
•
general and non specific sizes
•
standard airflow (Fan speed: Medium speed (M))
•
non-critical positioning and correct use of the unit
•
operation at full load
•
difference between inlet / outlet water temperature = 5°C
Ta = handling air coil entering air temperature (°C)
CAUTION! dry bulb measured temperature (D.B.=DRY BULB)
(W.B. = WET BULB)
TH2O = Water temperature at plate exchanger input (°C)
1. Standard operating range
2. Operating field for water glycol system (to prevent frost)
3. Standard unit operating field. in this field the cop efficiency can be increased
equipping the unit with the ‘V2MODX - 2-way modulating valve for installation
with disposable water’ option, that controls the heat exchange with the source.
in this way the unit performances are similar to the unit ones with feeding water
temperature (T H2O) equal to 25°C. with this option the water feeding system
must be at variable flow.
18
VERSATEMP
BT10D004GB-07
Standard unit water circuit pressure drops
Q = water flow rate (l/s)
DP = water side pressure drops (kPa)
The standard unit includes the following components: 1 - plate heat exchanger complete with differential water side pressure switch (to check for the presence of water
flow) and water temperature control probe (for avoiding ice formation and to deactivate the compressor when the water temperature falls below a limit value) 2 - bleed
bibcock (to let air out of the system). It does not provide for other shut off or control devices
Electric fans performance
SIZES
5
7
9
15
17
21
93
114
113
172
172
208
Minimum speed - EXTRAQUIET
Airflow
l/s
Airflow
m3/h
335
410
405
620
620
750
kW
0.029
0.042
0.042
0.063
0.063
0.083
Airflow
l/s
106
128
126
208
208
230
Airflow
m3/h
380
460
455
750
750
830
kW
0.043
0.048
0.048
0.083
0.083
0.094
Airflow
l/s
114
183
182
230
230
258
Airflow
m3/h
410
660
655
830
830
930
kW
0.052
0.072
0.072
0.094
0.094
0,115
Total input
Standard speed - QUIET
Total input
Maximum speed - POWERFUL
Total input
Performance corrective coefficients in relation to the speed of the
treatment fans
Minimum speed - EXTRAQUIET
Kf
Ks
Kt
Kef
Standard speed - QUIET
Ket
Kf
Ks
Kt
Kef
Maximum speed - POWERFUL
Ket
Kf
Ks
Kt
Kef
Ket
5
0,88
0,81
0,95
1,02
1,03
1
1
1
1
1
1,02
1,04
1,01
1
0,97
7
0,94
0,94
0,99
1,01
1,02
1
1
1
1
1
1,06
1,18
1,03
1,01
0,94
9
0,96
0,94
0,98
1,02
1,03
1
1
1
1
1
1,06
1,21
1,04
1
0,92
15
0,93
0,83
0,94
1,01
1,14
1
1
1
1
1
1,01
1,06
1,01
1
0,97
17
0,97
0,78
0,93
1,01
1,11
1
1
1
1
1
1,02
1,06
1,02
1
0,96
21
0,98
0,95
0,99
1
1,06
1
1
1
1
1
1,02
1,06
1,02
1
0,96
The performances at the handling fan speeds are obtained by multiplying the standard flow unit (Quiet) by the correction factors in the table.
Extra-quiet = Fan maximum speed
Quiet (standard) = Fan medium speed
Powerful = Fan maximum speed
Kf = Output multiplying coefficient in cooling mode
Ks= Sensible output multiplication coefficient
Kt = Heating performance multiplication coefficient
Kef = Multiplying coefficient of the power absorbed by the compressors in cooling mode
Ket = Multiplying coefficient of the power absorbed by the compressors in heating mode
BT10D004GB-07
VERSATEMP
19
Sound levels
Extra-quiet = Fan maximum speed
Sound power level (dB)
Size
Octave band (Hz)
63
125
250
500
1000
2000
4000
8000
Sound
power
level
Sound
pressure
level
dB(A)
dB(A)
5
54
62
51
46
46
41
37
35
51
40
7
55
59
47
48
44
39
34
35
50
38
9
55
59
51
49
44
40
35
34
50
38
15
59
59
54
51
46
41
40
37
52
41
17
59
60
53
51
45
41
41
37
52
41
21
61
57
57
55
51
46
42
38
56
45
Sound
power
level
Sound
pressure
level
dB(A)
dB(A)
Quiet (standard) = Fan medium speed
Sound power level (dB)
Size
Octave band (Hz)
63
125
250
500
1000
2000
4000
8000
5
56
62
54
49
45
44
37
36
52
41
7
63
58
52
51
47
43
37
35
52
41
9
63
59
52
51
47
43
39
36
52
41
15
59
58
56
56
50
45
39
37
56
45
17
60
59
58
56
51
46
40
36
56
45
21
62
59
59
57
53
49
41
35
58
47
Sound
power
level
Sound
pressure
level
dB(A)
dB(A)
Powerful = Fan maximum speed
Sound power level (dB)
Size
Octave band (Hz)
63
125
250
500
1000
2000
4000
8000
5
56
54
54
50
46
45
36
34
52
41
7
57
58
55
52
50
48
40
38
55
43
9
60
61
56
51
50
47
39
36
54
43
15
63
62
58
58
52
48
40
38
58
47
17
65
61
59
58
53
49
40
38
58
47
21
66
60
60
58
55
52
44
37
60
49
The sound levels are referred to units operating at a full load in nominal conditions. The sound pressure level is referred at a distance of 1m. from the external unit surface, with fairing, fitted to a wall. Please note that when the unit is
installed in conditions other than nominal test conditions /for example near walls or obstacles in general) the sound levels may undergo substantial variation.
Measurements are made in accordance to the UNI EN ISO 9614-2, with units installed over two sound reflective surfaces.
Measurements are made in accordance to the UNI EN ISO 9614-2, with units installed over two sound reflective surfaces.
20
VERSATEMP
BT10D004GB-07
Common accessories for uncased and cased unit configurations
MIPC - Hydraulic pipework arrangement for loop with constant flow rate with manual valves
Option supplied built-in. It simplifies the design and the installation in closed loop applications at constant water flow. Complete with water steel-mash
filter, two 2-way shut-off valves with manual operation at the inlet and outlet to the water side exchanger, a 2-way valve with manual activation which works
as a by-pass during hydraulic circuit cleaning, two bleed bibcocks.
Pressure drop of the unit complete with MIPC option
MIPC option scheme
Q = water flow-rate[l/s]
DP = water side pressure drops (kPa)
1.
2.
3.
4.
5.
Internal exchanger with temperature probes, differential pressure switch, vent valve
Steel mesh strainer
Vent valve
Manual switch off valve
Manual by-pass valve
MIPV - Hydraulic pipework arrangement for loop with variable flow rate with 2 way ON-OFF
valve
Option supplied built-in. It simplifies the design and the installation in closed loop applications at variant water flow. Includes a 2-way motorised ON/OFF
valve at the outlet of the water side exchanger, powered and controlled by the unit. Its function is coupled to that of the refrigerant circuit: with the stopped
compressor, the valve stays closed, reducing water consumption. Furthermore, complete with steel-mesh filter, two 2-way shut off valves with manual
activation at the inlet of the water side exchanger, a 2-way valve with manual activation which works as a by-pass during the hydraulic circuit cleaning, two
bleed bibcocks.
Pressure drop of the unit complete with MIPV option
MIPV option scheme
Q = water flow-rate[l/s]
DP = water side pressure drops (kPa)
1.
2.
3.
4.
5.
6.
Internal exchanger with temperature probes, differential pressure switch, vent valve
Steel mesh strainer
Vent valve
Manual switch off valve
Manual by-pass valve
Motorised two-way ON /OFF valve
The supplied valve ensures proper opening and closure for water differential pressures that do not exceed
CDPA - Condensate drain pump, built-in
Device which enables condensation water to be discharged into the collection tray in case it cannot drain away due to gravity. It
is necessary in installations where the external outlet is placed at a higher height than the condensate tray. The integrated sensor
activates the pump only when necessary. If the water level in the tray should be greater than the pre-set limit, the unit stops the
compressor to avoid the tray overflowing, signalling the fault with an alarm.
The device is installed and wired built-in the unit.
Technical specifications of the condensate drain pump
Size
5-7-9-15-17-21
Water flow-rate
6 l/h
Available pressure
60 kPa
BT10D004GB-07
VERSATEMP
21
REQV - Water connections for retrofit of EQV, VM AND VV units with constant flow-rate
Option supplied built-in. This simplifies hydraulic connection of the VERSATEMP EQV, VM, VV series unit replacement, uncased and cased,
since it keeps the same size fittings in the same places. Complete with steel-mash filter and safety valve.
The device is built-in the unit.
Pressure drop of the unit complete with REQV option
REQV option scheme
Q = water flow-rate[l/s]
DP = water side pressure drops (kPa)
1.
2.
3.
Internal exchanger with temperature probes, differential pressure switch, vent valve
Steel mesh strainer
Vent valve
The graph shows only the EQV-x sizes suitable replacement (retrofit) with the VERSATEMP unit, series EQV, VM, VV.
The system side connections are female
EQV-X performance table with retrofit system
EQV-X SIZES
5
7
9
15
17
Water flow-rate
1
l/s
0.064
0.064
0.075
0.114
0,114
Airflow
2
l/s
106
128
126
208
208
Airflow
2
m3/h
380
460
455
750
750
COOLING
A 27/19 W 30
Cooling capacity
kW
1.99
2.25
2.71
3.26
3.59
Compressor power input
kW
0.48
0.64
0.70
0.77
0.85
HEATING
A 20 W 20
Heating capacity
kW
2.33
2.68
3.12
3.98
4.34
Compressor power input
kW
0.46
0.61
0.68
0.76
0.90
°C
20
20
20
20
20
OPERATION RANGE
Min inlet water temperature in cooling mode
Max inlet water temperature in cooling mode
°C
40
39
39
41
40
Min inlet water temperature in heating mode
°C
13
14
14
12
13
Max inlet water temperature in heating mode
°C
45
45
45
45
45
1. EQV-X water flow-rate = EQV, VM, VV water flow-rate
A 27/19 W 30 = Unit inlet air temperature 27°C D.B. / 19°C W.B. Unit inlet water temper
2. EQV-X airflow, at the fan standard speed (Quiet)
A 20 W 20 = Unit inlet air temperature 20°C Unit inlet water temperature 20°C
DB = dry bulb WB = wet bulb
Note: The difference between the inlet and the outlet water temperature can be calculated in relation to the water flow rate and the unit’s power output.
Q = water flow-rate (l/s)
DT = DIFFERENCE BETWEEN INLET AND OUTLET WATER TEMPERATURE (°C)
kWt = BASED ON THE OPERATING MODE
- kWt = Pf + Pe compressor (COOLING)
- kWt = Pt - Pe compressor (HEATING)
22
VERSATEMP
BT10D004GB-07
MOBA - RS485 serial port with Modbus protocol, built-in
It allows the serial connection to supervision systems, using BACnet as the communication protocol. It allows the
access to the complete list of operating variables, controls and alarms.
On the serial line can be connected up to 32 units for a typical distance of 1000 m. The connection is made using
a suitable cable to RS485 network or formed by a twisted pair and shielded wires.
The device is installed and wired built-in the unit.
Accessories separately supplied
CIWMX - Electronic room control with display for wall installation with uncased box
Option which allows the remote control of the unit which can be easily installed in the main built-in units which are available on the market with squared
or rounded 65 mm diameter / 31 mm deep profiles.
The electronic control with display is simple to use even for non-specialised users. Thanks to the icon menu
which is complete with back-lighting, it allows different unit functions to be controlled, including:
•
•
•
•
•
•
switching the unit on and off
•
•
•
management of the operating parameters.
reading the temperature using the probe in its interior
display the alarm code and the unit stata
password protection to access the unit’s parameters
changing the manual operating mode (hot or cold) and/or set point
programming the daily and weekly time schedule for switching on and off and for setting the standard
or economic set point.
language management for the navigation menu
manually, or automatically, managing the fan speed, depending on the distance from the set- point.
Electrical connection for distances lower than 10m
Electrical connection for distances exceeding 10m
The device is prepared for connection to a unit electrical panel (installation by the Client) with the following modes: - For a max distance of 10m only use the power
supply cable and serial communication included in the pack. In this way electric power is supplied by the unit. - For a max distance of 200m use a shielded twisted pair
cable with a min 0.5 / max 1.5 mm2 section. In this case the 230/1/50 electricity supply is by the Client (transformer integrated in the display).
BT10D004GB-07
VERSATEMP
23
CWMX - Electronic control with display for wall installation
An option which enables the unit to be remotely controlled. It can be attached to a wall with the support in a horizontal or vertical position.
The electronic control with display is simple to use even for non-specialised users.
It allows different unit functions to be controlled, including:
•
•
•
•
reading the temperature directly on the thermostat using the probe in its interior
•
•
•
•
•
•
changing the manual operating mode (hot or cold) and/or set point
switching the unit on and off
machine parameter protection with password
programming the daily and weekly time schedule for switching on and off and for setting the
standard or economic set point.
alarm and unit status display;
management of the operating parameters.
language management for the navigation menu
back-lit icon menu
manual or automatic fan speed management in relation to how far away the setpoint is.
Electrical connection for distances lower than 10m
Electrical connection for distances exceeding 10m
The device is prepared for connection to a unit electrical panel (installation by the Client) with the following modes: - For a max distance of 10m only use the power
supply cable and serial communication included in the pack. In this way electric power is supplied by the unit. - For a max distance of 200m use a shielded twisted pair
cable with a min 0.5 / max 1.5 mm2 section. In this case the 230/1/50 electricity supply is by the Client (transformer integrated in the display).
V2MODX - 2-way modulating valve for installation with disposable water
Option indicated in the applications with disposable water at a temperature relatively low (well, groundwater, aqueduct) or
with loop at a variable flow where the unit must operate in heating with high water temperatures or in cooling with low water
temperatures. The 2-way motorized valve, modulating type, is placed in the exchanger output water side and is fed by the
unit. Its operating is combined with that of the refrigerant circuit: the modulation by 0-10V signal according to the refrigerant
pressure in the exchanger source side, reduces the water consumption and maintains the unit in the provided operating field
both in cooling and in heating mode.
The supplied valve ensures proper opening and closure for water differential pressures that do not exceed 800 kPa, i.e. 8 bar.
Pressure drops of v2modx option
Q = water flow-rate[l/s]
DP = water side pressure drops (kPa)
Water connection diagram
1.
2.
3.
Internal exchanger with temperature probes, differential pressure switch, vent valve
Manual switch off valve (provided by the Customer)
Manual by-pass valve (provided by the Customer)
4.
Drain cock (provided by the Customer)
V2MODX - Two-way modulating valve for systems with disposable water
IFWX - Steel mesh strainer water side
Option to be installed outside the unit on the water outlet pipe of the exchanger. Provide for spaces to assemble/disassemble the valve.
With this option the unit is provided full of rapid electric connections for the valve feeding and automatic control.
To simplify the fixing and ensure the correct valve positioning is recommended the matching to the ‘KFVMX - 2-way modulating valve fixing kit for installation with
disposable water’ accessory.
24
VERSATEMP
BT10D004GB-07
KFVMX - 2-way modulating valve fixing kit for installation with disposable water
Option that simplifies the mechanical and electrical installation of the ‘V2MODX - 2-way modulating valve for installation with disposable water’ device
both in the configuration with fairing and in the uncased one. In the configuration with fairing it allows to be hidden from view thanks to the mandatory
coupling with the ‘FXVFHX - Painted plinths for floor fixing with front grille and rear closing’ accessory. It is made up of pipes, fittings and a fixing bracket. It
also includes the drain cock otherwise provided by the Customer.
This accessory has to be combined to the ‘V2MODX - 2-way modulating valve for installation with disposable water’ option
For the units in configuration with fairing this accessory has to be combined to the ‘FXVFHX - Painted plinths for floor fixing with front grille and rear closing’ option
For the units in uncased configuration that have to be placed on the floor, this accessory has to be combined to the ‘FXPMX– Raised zinc-coated plinth for floor standing
arrangement for uncased unit’ option.
IFWX - Steel mesh strainer on water side
The device protects the plate exchanger of any impurities in the hydraulic circuit. The mechanical stainless steel-mesh filter is easily disassembled for routine
maintenance and cleaning.
IFWX OPTION PRESSURE DROPS
Q = water flow-rate[l/s]
DP = water side pressure drops (kPa)
IFWX option technical specifications
Size
5-7-9
15-17-21
Filter diameter
1/2”
3/4”
Water fitting diameter
1/2”
1/2”
FEMALE
FEMALE
System side water fittings
Unit side water fittings
Degree of filtration
MALE
MALE
400 µm
400 µm
Pressure drop referred to a clean filter
To carry out routine maintenance there should be appropriate shut-offs on the hydraulic line.
BT10D004GB-07
VERSATEMP
25
FCVBX - Manual balancing valve
The device enables the water flow through the unit to be calibrated without measuring tables or devices. In this way it is possible to balance the water flow
in the circuit. The special viewer enables instantaneous reading of the water flow (in litres / minute). The calibration can be easily carried out even by nonspecialised operators, operating on the special control screws. It includes adaptors for varying the diameter between the balancing valve and the water
fittings.
Features of the manual balancing valve
Size
5-7-9
15-17-21
Balancing valve diameter
3/4”
1”
Water fitting diameter
1/2”
1/2”
System side water fittings
MALE
MALE
Unit side water fittings
MALE
MALE
Max. operating pressure
10 bar
10 bar
0.05 ÷ 0.2 l/s
0.13 ÷ 0.5 l/s
1.85
5.00
Field flow control
Flow-rate coefficient (Kvs)
The water side pressure drop can be determined with the following formula:
Q = water flow-rate[l/s]
Dp = water side pressure drops (bar)
Kvs = flow-rate coefficient [m3/h]
CDPAX - Condensate drain pump
Technical characteristics as for the CPDA accessory, but with the exception of installation and wiring which have to be fitted by Client.
The device is prepared for installation inside the unit (to be fitted by Client). The pack includes a condensate drain flexible pipe (1m in length) and the the electricity
power cable and the control.
CSVX - Couple of manual shut-off valves
Shut-off device which enables the unit to be hydraulically closed for maintenance works and to prepare the system before
connecting the unit. The two manual operated valves are located on the water lines at the inlet and outlet.
Technical specifications of the manual shut-off valves
Size
Filter diameter
System side water fittings
Unit side water fittings
26
5-7-9-15-17-21
1/2”
FEMALE
MALE
VERSATEMP
BT10D004GB-07
PFHCX - 200 mm flexible pipes for water connection and condensate drain
PFHC1X - 500 mm flexible pipes for water connection and condensate drain
An option which simplifies the water connection and reduces any vibrations between the unit and the system. It
includes two flexible pipes with stainless steel net covering and a reinforced plastic pipe for the connection of the tray
to the external drain.
Technical specifications of the flexible pipes for water connections
Size
5-7-9-15-17-21
Diameter of the fittings
System side water fittings
1/2”
FEMALE
Unit side water fittings
MALE
Max. operating pressure
12 bar
Min. bending radius
45 mm
Pressure drops of the single 200 mm flexible pipe
Q = water flow-rate[l/s]
DP = water side pressure drops (kPa)
Pressure drops of the single 500 mm flexible pipe
Q = water flow-rate[l/s]
DP = water side pressure drops (kPa)
Technical specifications of the flexible pipe for condensate drain
Size
5-7-9-15-17-21
Pipe diameter
Pipe length
15 mm
1m
The flexible pipe of the condensate drain can be completed with a suitable trap to prevent the odour return in the room and connected to a suitable drain (installed
by Customer).
BT10D004GB-07
VERSATEMP
27
MOBX - RS485 serial port with Modbus protocol
This accessory has the same technical specifications of MOBA accessory, with the exception of the installation and wiring to be complet by customer.
The device is ready for connecting to the electrical panel (installed by the customer).
CMSLWX - LonWorks communication serial module
This enables the serial connection of the supervision system which uses the LonWorks communication protocol.
It enables access to a list of operating variables, commands and alarms which comply with the Echelon® standard.
With this accessory, each unit can communicate with the main supervisor systems such as Trend, Johnson
Controls, PlantVisor.
The device needs to be combined with the RS485 serial port option with Modbus protocol.
The package includes the transformer, which is powered by 230/1/50, and the Gateway of communication between the supervisor and the Modbus serial line. The
configuration and management of the LonWorks network are the responsability of the Customer.
The device is prearranged to mounting in DIN rail, for external installation (7 DIN modules, installed by the customer)
BACX - BACnet communication serial module
Allows to perform the serial connection to supervision systems by using BACnet as a communication protocol. It
allows the access to the entire list of operating variables, controls and alarms
With this accessory, each unit can communicate with the main supervisor systems such as Trend, Johnson
Controls, PlantVisor.
The device requires the coupling with the “RS485 serial port with Modbus protocol” option
The package includes the transformer, which is powered by 230/1/50, and the Gateway of communication between the supervisor and the Modbus serial line. The
configuration and management of the BACnet network are the responsability of the customer.
The device is prearranged to mounting in DIN rail, for external installation (7 DIN modules, installed by the customer)
Main variables of supervision by serial (Modbus / LonWorks / BACnet).
•
•
•
•
•
•
•
•
•
•
•
28
Current room temperature
Ideal temperature Set-Point
Maximum correction of the set-point temperature set by the user via electronic room control
Fan speed (Extraquiet, Quiet, Powerful, AUTO)
Operating mode (Heating, Cooling, AUTO)
Alarm reset
ECONOMIC operating mode (using a pre-set ECO set point)
Remote ON-OFF
Heating temperature hysteresis
Cooling temperature hysteresis
Deadband
VERSATEMP
BT10D004GB-07
Uncased unit accessories
Accessories separately supplied
FXPFX - Zinc-coated plinths for floor fixing on uncased unit
Option that simplifies the designa and realization of the containment furniture. The plinths are made of zinc-coated
stainless steel and are supplied with adjustable rubber feet.
Option available only with uncased configuration unit
FXPFX - Zinc-coated plinths for floor fixing on uncased unit
Option that simplifies the designa and realization of the containment furniture. The plinths are made of zinc-coated
stainless steel and are supplied with adjustable rubber feet.
The rise obtained keeps the unit raised from the ground and allows any installation components to be put under the unit
(performed by the Customer). The plinths are drilled in the middle to allow the passage of any electrical cables and pipes.
Option available only with uncased configuration unit
CONTX - Electronic room control with display, for installation on the uncased unit
An option which enables the electronic control to be assembled built-in, in a horizontal, visible position.
The electronic control with display is simple to use even for non-specialised users.
It allows different unit functions to be controlled, including:
•
•
•
switching the unit on and off
•
•
•
•
•
•
changing the manual operating mode (hot or cold) and/or set point
machine parameter protection with password
programming the daily and weekly time schedule for switching on and off and for setting the standard or
economic set point.
alarm and unit status display;
management of the operating parameters.
language management for the navigation menu
back-lit icon menu
manual or automatic fan speed management in relation to how far away the setpoint is.
Package includes mounting screws and the power cable and serial communication (installed by customer)
BT10D004GB-07
VERSATEMP
29
GOJX - Air supply grille with flexible joint and grille
Option that simplifies the designa and realization of the containment furniture. The kit consists of:
•
an aluminium grille for air diffusion. With a pleasing design, it is equipped with one single line of blades and
integrated attachment flange for building into the furnishings. A portion of the grille opened for access to
the “Electronic control with display” option (when present);
•
a flexible PVC duct for connection with the unit air discharge. It enables a good level of freedom in
positioning the air diffusion grille in relation to the unit.
Size
5
7-9
15-17-21
A
880
1030
1180
B
125 ÷ 205
125 ÷ 205
125 ÷ 205
170 ÷ 250
C
170 ÷ 250
170 ÷ 250
D
182
182
182
E
145
145
145
Option available only with uncased configuration unit
DAOJX - Air supply duct with flexible joint
Option that simplifies the design and realization of the containment furniture. The kit consists of a flexible PVC
duct for connection with the unit air supply. It enables a good level of freedom in positioning the air diffusion
grille in relation to the unit.
Size
5
7-9
15-17-21
A
605
750
860
B
150 ÷ 230
150 ÷ 230
150 ÷ 230
C
145
145
145
Option available only with uncased configuration unit
30
VERSATEMP
BT10D004GB-07
Cased unit accessories
CAB - Configuration with fairing for cased applications
With this aesthetic finishing option the unit can be installed directly in the room. The external fairing is made of
zinc-coated stainless steel and powder-coated (colour RAL 9003), with finishing and grilles in robust RAL 7047
colour ABS plastic. “Aluzinc” assembly to the internal structure at 4 points which are hidden by the air supply
grille. The air supply grilles and, if present, the frontal air grille are supplied with one single line of fixed fins. They
can be easily extracted and rotated by 180° to obtain a different direction in the air flow.
The joint between the fairing and the sides is made using ABS profiles (RAL 7047)
CONT - Electronic room control with display, installed in a visible position on the unit with
fairing
The electronic control with display is electrically connected built-in, in an easily visible position
and is simple to use even for non-specialised users.
It allows different unit functions to be controlled, including:
•
•
•
switching the unit on and off
•
•
•
•
•
•
changing the manual operating mode (hot or cold) and/or set point
machine parameter protection with password
programming the daily and weekly time schedule for switching on and off and for setting the
standard or economic set point.
alarm and unit status display;
management of the operating parameters.
language management for the navigation menu
back-lit icon menu
manual or automatic fan speed management in relation to how far away the setpoint is.
Icons and status visible from the display:
1.
Operating mode
2.
Unit Status
3.
Fan: manual / automatic speed
4.
Status variables, parameter, alarms
5.
Set-point, times, days of the week
BACKV - Rear painted panel for cased unit
Option which enables the installation of a unit with a rear visible wall (for instance, in front of a glass wall). It
includes a rear aesthetic panel in galvanized steel and powder-coated with the same colour of the hood (RAL
9003).
Option available only with cased configuration unit
BT10D004GB-07
VERSATEMP
31
Accessories separately supplied
FXVFX - Painted plinths for floor fixing
Enables safe positioning even when the unit cannot be attached to a rear wall, as in the case of plasterboard
walls or near to a glass wall. The plinths are made of galvanized steel and powder-coated with the same colour
as the grilles (RAL 7047) and are supplied with rubber adjustable feet.
Option available only with cased configuration unit
FXVFHX - Painted plinths for floor fixing with front grille and rear closing
Enables safe positioning even when the unit cannot be attached to a rear wall, as in the case of plasterboard
walls or near to a glass wall. Furthermore, enables any pipe work components to be hidden. It includes:
•
•
two plinths made of zinc-coated stainless steel and supplied with rubber adjustable feet
•
a rear closing panel with the same colour as the grilles (RAL 7047) that allows the unit installation with
exposed rear wall (for example close to a glass wall).
a covering panel made of galvanized steel and powder-coated with the same colour as the grilles (RAL
7047), complete with frontal air grille which is the same as the air delivery grille.
Option available only with cased configuration unit
The painted plinths of the FXVFHX and FXVFX options are of different heights
32
VERSATEMP
BT10D004GB-07
Option compatibility
OPTIONS OF EQV-X RANGE
REF.
DESCRIPTION
WITH FAIRING
UNCASED
Versions
CAB
Configuration with fairing for cased applications
√
-
UC
Uncased version (without casing)
-
√
Aeraulic circuit
GOJX
Air supply grille with flexible connection
-
◊
DAOJX
Air supply duct with flexible connection
-
◊
√
√
RF
Front air inlet
Hydraulic circuit
CDPX
condensate drain pump
◊
◊
CDPA
condensate drain pump, built-in
√
√
IFWX
Steel mesh strainer on the water side
◊
◊
FCVBX
Water balancing valve
◊
◊
CSVX
Couple of manual shut-off valves
◊
◊
PFHCX
200 mm flexible pipes for the connection to the
water circuit + drop conduit
◊
◊
PFHC1X
500 mm flexible pipes for the connection to the
water circuit + drop conduit
◊
◊
MIPC
Hydraulic pipework arrangement for loop with
constant flow rate with manual valves
√
√
MIPV
Hydraulic pipework arrangement for loop with
variable flow with 2-way ON-OFF valve
√
√
V2MODX
2-way modulating valve for disposable water
system
◊
◊
KFVMX
2-way modulating valve fixing kit for disposable
water system
◊¹
◊¹
REQV
Water connections for EQV, VV unit retrofit at
constant flow
√
√
MOBA
Serial port RS485 with MODBUS protocol, built-in
√
√
MOBX
RS485 serial port kit with Modbus protocol
◊
◊
Electric circuit
CMSLWX
LonWorks serial communication module
◊*
◊*
BACX
BACnet serial communication module
◊*
◊*
CWMX
Electronic room control with display, for wall
installation
◊
◊
CIWMX
Electronic room control with display, for wall
installation in built-in box
◊
◊
CONT
Electronic room control with display, installed in a
visible position on the unit with fairing
√
-
CONTX
Electronic room control with display, for installation on the uncased unit
-
◊
Application
BACKV
Painted rear panel for cased version
√
-
FXVFX
Painted plinths for floor fixing
◊
-
FXVFHX
Painted plinths for floor fixing with front grille and
rear closing
◊
-
FXPF1X
Zinc-coated plinths for floor fixing on uncased unit
◊
-
FXPFX
Zinc-coated plinths for floor fixing on uncased unit
-
◊
√
O
◊*
◊¹
Standard component
Optional component
Accessories separately supplied (optional) and available only with: RS485 Serial port with Modbus protocol (Clivet Ref. MOBA o MOBX)
Accessory separately supplied (optional) and available only with: Modulating 2-way valve with disposable water ( Clivet Ref. V2MODX)
◊ Accessory separately supplied (optional)
BT10D004GB-07
VERSATEMP
33
Dimensional drawings
Uncased unit
Size 5-21
1.
Power input
2.
Unit wall-mounting bracket
3.
Optional hydraulic module
4.
Water inlet - unit with optional hydraulic module (female)
5.
Water outlet - unit with optional hydraulic module (female)
6.
Standard unit water outlet (female)
7.
Standard unit water inlet (female)
8.
Condensate drain (15 mm)
9.
Conduit drop output from condensate drain pump (option)
34
Size
5
7
9
15
17
21
A (Lenght)
945
1095
1095
1245
1245
1245
B (Height)
490
490
490
490
490
490
C (Depth)
225
225
225
225
225
225
D
160
160
160
160
160
160
E
605
755
755
875
875
875
F
348
348
348
348
348
348
G
32
32
32
32
32
32
H
60
60
60
60
60
60
I
40
40
40
40
40
40
J
188
188
188
188
188
188
K
26
26
26
26
26
26
L
90
90
90
90
90
90
M
605
750
750
870
870
870
N
190
190
190
190
190
190
Operating weight
55
61
61
64
64
68
Standard unit water fittings
1/2”
1/2”
1/2”
1/2”
1/2”
1/2”
VERSATEMP
BT10D004GB-07
Unit in uncased version with hydraulic pipework arrangement or retrofit options
HYDRAULIC PIPEWORK ARRANGEMENT
- FOR CONSTANT FLOW LOOP
- FOR VARIABLE FLOW LOOP
HYDRAULIC PIPEWORK ARRANGEMENT
- WITH SYSTEM RETROFIT
Size
5
7
9
15
17
21
U
135
135
135
135
135
135
V
65
65
65
65
65
65
W
90
90
90
90
90
90
X
320
320
320
320
320
320
Y
75
75
75
75
75
75
Z
55
55
55
55
55
55
Unit water fittings with optional
hydraulic pipework arrangement
1/2”
1/2”
1/2”
1/2”
1/2”
1/2”
Unit water fittings with water connections for system retrofit
1/2”
1/2”
1/2”
1/2”
1/2”
1/2”
Functional clearances
Size
5
7
9
15
17
21
P (min)
100
100
100
100
100
100
Q
200
200
200
200
200
200
R
500
500
500
500
500
500
S
100
100
100
100
100
100
T (min)
0
0
0
0
0
0
BT10D004GB-07
VERSATEMP
35
Cased unit
1.
Electronic room control with display (optional)
2.
Power input
3.
Unit wall-mounting bracket
4.
Optional hydraulic module
5.
Water inlet - unit with optional hydraulic module (female)
6.
Water outlet - unit with optional hydraulic module (female)
7.
Standard unit water outlet (female)
8.
standard unit water inlet (female)
9.
Condensate drain (15 mm)
10. Conduit drop output from condensate drain pump (option)
36
Size
5
7
9
15
17
21
A (Lenght)
1050
1200
1200
1350
1350
1350
B (Height)
520
520
520
520
520
520
C (Depth)
240
240
240
240
240
240
D
125
125
125
125
125
125
E
765
920
920
1075
1075
1075
F
348
348
348
348
348
348
G
32
32
32
32
32
32
H
60
60
60
60
60
60
I
40
40
40
40
40
40
J
188
188
188
188
188
188
K
26
26
26
26
26
26
L
90
90
90
90
90
90
M
765
920
920
1070
1070
1070
N
210
210
210
210
210
210
Operating weight
63
70
70
73
73
77
Standard unit water fittings
1/2”
1/2”
1/2”
1/2”
1/2”
1/2”
VERSATEMP
BT10D004GB-07
Unit in cased version with hydraulic pipework arrangement or retrofit options
HYDRAULIC PIPEWORK ARRANGEMENT
- FOR CONSTANT FLOW LOOP
- FOR VARIABLE FLOW LOOP
HYDRAULIC PIPEWORK ARRANGEMENT
- WITH SYSTEM RETROFIT
Size
5
7
9
15
17
21
U
135
135
135
135
135
135
V
65
65
65
65
65
65
W
90
90
90
90
90
90
X
320
320
320
320
320
320
Y
75
75
75
75
75
75
Z
55
55
55
55
55
55
Unit water fittings with optional hydraulic pipework
arrangement
1/2”
1/2”
1/2”
1/2”
1/2”
1/2”
Unit water fittings with water connections for system
retrofit
1/2”
1/2”
1/2”
1/2”
1/2”
1/2”
Functional clearances
Size
5
7
9
15
17
21
P (MIN)
100
100
100
100
100
100
Q
200
200
200
200
200
200
R
500
500
500
500
500
500
S
100
100
100
100
100
100
T (MIN)
0
0
0
0
0
0
BT10D004GB-07
VERSATEMP
37
Page intentionally left blank
38
VERSATEMP
BT10D004GB-07
Page intentionally left blank
BT10D004GB-07
VERSATEMP
39
CLIVET SPA
Via Camp Lonc 25, Z.I. Villapaiera - 32032 Feltre (BL) - Italy
Tel. + 39 0439 3131 - Fax + 39 0439 313300 - info@clivet.it
CLIVET GROUP UK LIMITED
4 Kingdom Close, Segensworth East - Fareham, Hampshire - PO15 5TJ - United Kingdom
Tel. + 44 (0) 1489 572238 - Fax + 44 (0) 1489 573033 - enquiries@clivetgroup.co.uk
CLIVET GROUP UK Limited (Service Department)
Units F5&F6 Railway Triangle Ind Est, Walton Road - Portsmouth, Hampshire - PO6 1TG - United Kingdom
Tel. +44 (0) 2392 381235 - Fax. +44 (0) 2392 381243 - service@clivetgroup.co.uk
CLIVET ESPAÑA S.A.U.
C/ Bac de Roda, 36 - 08019 Barcelona - España
Tel: +34 93 8606248 - Fax +34 93 8855392 - info@clivet.es
Av.Manoteras Nº 38, Oficina C303 - 28050 Madrid - España
Tel. +34 91 6658280 - Fax +34 91 6657806 - info@clivet.es
CLIVET GmbH (Hydronic and Applied Division)
Hummelsbütteler Steindamm 84, 22851 Norderstedt - Germany
Tel. + 49 (0) 40 32 59 57-0 - Fax + 49 (0) 40 32 59 57-194 - info.de@clivet.com
CLIVET GmbH (VRF, Residential and Lightcom Division)
Eisenstrasse 9c, 65428 Rüsselsheim/Frankfurt - Germany
Tel. + 49 (0) 6142 83594-0 - Fax + 49 (0) 6142 83594-20 - vrf.de@clivet.com
CLIVET RUSSIA
Elektrozavodskaya st. 24, office 509 - 107023, Moscow, Russia
Tel. + 74956462009 - Fax + 74956462009 - info.ru@clivet.com
CLIVET MIDEAST FZCO
Dubai Silicon Oasis (DSO), High Bay Complex, Office N. 20, PO BOX 342009, Dubai, UAE
Tel. + 9714 3208499 - Fax + 9714 3208216 - info@clivet.ae
CLIVET AIRCONDITIONING SYSTEMS PRIVATE LIMITED
4BA, Gundecha Onclave, Kherani Road - Sakinaka, Andheri (East) - Mumbai 400 072 - India
Tel. +91 22 6193 7000 - Fax +91 22 6193 7001 - info.in@clivet.com
w w w. c l i ve t . co m
w w w.clivetlive.com
A Group Company of
Download PDF
Similar pages