CI/SfB
56.83
X
Product guide
Direct gas-fired
heating systems
Introduction
Niche is a specialist manufacturer and supplier of direct gas-fired heating and make up air solutions suitable for industrial,
commercial and civic buildings. Niche offers unparalleled engineering expertise in its field to offer the optimum solution to
meet the exact heating, ventilation or make up air requirements for the application. Niche direct gas-fired technology
has also been applied to a variety of process applications within the industrial, agricultural and food preparation market.
Niche offers a supply based service to meet the needs of end users, specifiers and contractors including system design
and on site technical support.
The Niche service team provides on site technical training and support, is ACS accredited and has expansive knowledge
of Trend® control systems.
Concept of direct gas fired heating
Direct gas-firing is an effective, cost efficient method of space heating for open areas. It provides a
positive ventilation rate, gently pressurizing the building and ensuring a fresh and warm atmosphere
with minimal stratification. Niche’s fully modulating burner system provides the optimum heat required
at maximum efficiency – so reducing running costs.
Where air is extracted from a building either for process or environmental reasons, a supply of heated
‘make up’ air is introduced ensuring an even comfortable environment without draughts or cold spots.
System benefits
•
•
•
Reduced running costs.
•
Rapid warm up –
even in the largest buildings.
•
•
•
•
Improved air quality.
Low installation costs.
Even heat distribution
without stratification.
Ventilation at no extra cost.
No ductwork necessary.
Low maintenance costs.
The Niche range
Niche offers the most comprehensive
range of direct fired heating units
in the market place. There are four
distinct ranges of product providing
heating capacities between 29kW and
879kW as standard with airflows from
0.56m3/s to 16m3/s. The ranges have
been developed to cater for differing
needs and applications yet all units
are capable of being tailor-made
to specific customer requirements.
All Niche products are CE approved
to the Gas Appliance Directive.
Applications overview
•
•
•
•
•
•
•
Industrial premises
Restaurants and public houses
Night clubs and casinos
Swimming pools
Churches
Retail outlets
Distribution depots
•
•
•
•
•
•
•
Sports centres
Greenhouses
Woodworking shops
Theatres and cinemas
Hostile or contaminated environments
Agricultural drying
Industrial process heating
TTW range
The TTW is a cost effective product solution for smaller industrial, workshop environments and
specific commercial applications; particularly those with flammable dust or vapor in the atmosphere.
Available as a standard ‘on/off’ heater, in sizes from 29kW to 150kW. Fan ratings from 0.56-2.78m3/s.
TTW standard features
•
•
•
•
•
100% thermal efficient based on net c.v.
•
•
Standard integral controls and time clock.
On/off unit.
29 to 150kW input.
Single phase.
Construction from aluminum extruded section
with panels made from galvanized steel.
30 and 60kW models standard with direct drive fans.
TTW optional features
•
•
•
•
Range of airflows and external pressures.
•
•
•
Three phase.
Insulated cases.
Double skin steel panels.
Plastic coated steel case or painted to
match surroundings.
60kW unit has optional pulley driven fan.
Unit available in ‘flat-pack’ for on site assembly.
TTW benefits
•
Suitable for smaller industrial and
workshop environments.
•
•
‘Free cooling’ available in summer.
Can be installed internally or externally.
MUA/LSD range
The MUA/LSD is an extremely flexible engineered product, particularly suited to where there is
a requirement for precise heating and ventilation control, low noise operation and aesthetic
integration with the building. The MUA/LSD is an ideal solution for the more prestigious environment,
including churches, libraries and indoor domestic swimming pools. Available as a fully modulating
heater, in sizes from 29kW to 103kW. Fan ratings from 0.56-1.95m3/s.
MUA/LSD standard features
•
•
•
•
•
•
•
100% thermal efficient based on net c.v.
•
•
Insulated panels.
29 to 103kW input.
Fully modulating gas burner with 25:1 turndown.
Mixed-flow fan for higher efficiency and lower noise.
Maximum static pressure of 425 Pa.
Single phase.
Construction from 30mm aluminum extruded section
with panels made from galvanized steel.
Trend® controls fitted as standard.
MUA/LSD optional features
•
•
•
•
•
•
MUA/LSD benefits
•
•
•
•
Very quiet operation.
Compact, slimline construction.
Aesthetically pleasing.
Can be used in conjunction with heat recovery.
Modular heat recovery.
Extract module.
Plastic coated steel case or painted to match surroundings.
Variable air volume system incorporating box burner and speed inverters.
Three phase.
Unit available in ‘flat-pack’ for on site assembly.
MUA benefits
MUA range
The MUA is the core of the Niche direct fired range, offering a diversity of solutions
for a whole range of industrial and commercial applications from large factories to
pubs, casinos and warehouses. The units are specifically built to meet the needs of
each client and can be enhanced with variable air volume, cooling, specialist filtration
and a customized control system. MUA is available as a fully modulating heater in
sizes from 29kW to 879kW as standard with extra duties being available on request.
Fan ratings from 0.56-16.01m3/s.
The allowances include the cost
of the heater plus directly related
installation costs.
Very flexible in its design
and operation.
•
Suited to many types of industrial
and commercial applications.
•
Can be customized to include
heat recovery.
MUA optional features
MUA standard features
This symbol verifies that the product
was independently assessed and qualifies
for the ECA scheme, an upfront tax
relief enabling businesses that invest
in energy-saving equipment to claim
100% first-year capital allowances
against their taxable profits.
•
•
Variable air volume system
incorporating box burner and
speed inverters.
Fully modulating gas burner with
25:1 turndown.
•
•
Backward curve fans for high
external static pressures.
Combination of motor and fan rating to
achieve required external static pressures.
•
•
Plastic coated steel case or painted
to match surroundings.
Anti-vibration mountings on fan and
motor assembly.
Double skin steel panels.
•
•
Single phase or three phase.
•
•
•
•
Single skin steel panels.
•
•
•
•
•
•
•
•
100% thermal efficient based on net c.v.
29 to 879kW input.
Construction from aluminum
extruded section with panels made
from galvanized steel.
Trend® controls fitted as standard.
Forward curved fan.
Orientations: horizontal, vertical
with various discharges.
The Niche box burner
The box burner is a concept that is unique to the Niche range. It is a pressurized burner
assembly with integral combustion fans that maintains the optimum conditions for
combustion and provides the basis for the variable air volume system. The box burner
is fitted as standard to the MUA/LSD range, and can be added to the MUA range to
increase its flexibility and operation. The box burner can also be used as a pressurized
burner in its own right for in-duct heater battery replacement, inclusion within air
handling units and agricultural/process drying applications.
Insulated single and double skin panels.
Modular heat recovery.
Extract module.
Unit available in ‘flat-pack’ for on
site assembly.
Discharge options
Trend® controls
Each product in the Niche range is controlled by a powerful and flexible Trend®
microprocessor system. It has been programmed to give the most efficient operation
of the heater and incorporates many operator selectable options. Niche’s engineering
and after sales service team are fully trained in the design, use and application of
Trend® systems on all its product range.
Trend® features and options
•
7 day programmable time clock with 3 on/off
switching operations per day.
•
Heater discharge controlled between set bands –
maximum and minimum discharge temperature.
•
•
•
•
•
•
•
•
Standard and special week settings.
•
•
•
•
•
•
•
•
Remote display of faults – with audible alarm.
Optimum start and optimum stop.
Modulating control of room temperature – to 0.5°C.
PIN secured adjustments on key pad.
High accuracy room sensor.
Temperatures displayed at remote terminal screen.
Night setback or frost protection.
Control on a combination of temperature, humidity
and static pressure.
Removable fascia panel for remote control (hard wired).
Hour run meter on fan and burner.
Programmable in house.
Network/BMS compatible.
Remote monitoring via modem access.
Remote start relay.
Range of customized features.
Specification and technical data
TTW
Model
Airflow (m3/s)
Input (kW)
0.56
0.56
1.13
1.13
1.96
2.82
29
29
59
59
103
146
TTW
30
30PD
60
60PD
100
150
Output (kW) Gas rate (m3/h) Gas connection
Motor size
(BSP) kW @ ESP 75Pa
1/2”
27
2.83
0.37
1/2”
27
2.83
0.55
1/2”
54
5.66
0.92
1/2”
54
5.66
0.75
3/4”
95
9.91
1.1
3/4”
136
14.16
2.2
Full load Electrical supply
current (amps)
(volts)
2.2
230V
3.5/1.45
230V/400V
8.5
230V
4.5/1.9
230V/400V
6.7/2.59
230V/400V
12/4.8
230V/400V
Note
The table above details typical units based upon space heating applications on a temperature rise of 45ºC.
Alternative airflows, heat outputs and static pressures may be specified to match precise application requirements up to a maximum temperature rise of 55ºC.
External pressure available up to 525 pascals with increased motor sizes.
Gas rates and gas connections listed are for natural gas. LPG options are available on request.
For higher pressures consult Niche.
MUA/LSD
Model
Airflow (m3/s)
Input (kW)
0.56
0.86
1.11
1.11
1.95
1.95
29
44
59
59
103
103
MUA/LSD
100
150
200
200 3PH
350
350 3PH
Output (kW) Gas rate (m3/h) Gas connection
Motor size
(BSP) kW @ ESP 75Pa
1/2”
27
2.83
0.31
1/2”
41
4.25
0.96
1/2”
54
5.66
1.45
1/2”
54
5.66
1.35
3/4”
95
9.91
1.45
3/4”
95
9.91
2.4
Full load Electrical supply
current (amps)
(volts)
1.35
230V
4.3
230V
6.1
230V
2.3
400V
6.1
230V
4.3
400V
Note
The table above details typical units based upon space heating applications on a temperature rise of 45ºC.
Alternative airflows, heat outputs and static pressures may be specified to match precise application requirements.
Gas rates and gas connections listed are for natural gas. LPG options are available on request.
External pressure available up to 375 pascals with increased motor sizes.
MUA
Model
MUA
10DD
10PD
20DD
20PD
25
35
50
75
100
125
150
175
200
225
250
275
300
Airflow (m3/s)
Input (kW)
0.56
0.56
1.13
1.13
1.41
1.96
2.82
4.00
5.18
6.59
8.00
9.42
10.36
11.77
13.18
14.60
16.01
29
29
59
59
73
103
146
220
293
366
439
513
586
659
732
806
879
Output (kW) Gas rate (m3/h) Gas connection
Motor size
(BSP) kW @ ESP 75Pa
1/2”
27
2.83
0.37
1/2”
27
2.83
0.55
1/2”
54
5.66
0.92
1/2”
54
5.66
0.75
1/2”
68
7.08
1.1
3/4”
95
9.91
1.1
3/4”
136
14.16
2.2
204
21.24
1
3
272
28.32
1 1/4”
3
341
35.40
1 1/4”
5.5
409
42.48
1 1/2”
5.5
477
49.55
1 1/2”
7.5
545
56.63
2
7.5
613
63.71
2
11
681
70.79
2
11
749
77.87
2
7.5
817
84.95
2
11
Full load Electrical supply
current (amps)
(volts)
2.2
230V
3.5/1.45
230V/400V
8.5
230V
4.5/1.9
230V/400V
6.7/2.59
230V/400V
6.7/2.59
230V/400V
12/4.8
230V/400V
6.48
400V
6.48
400V
11.1
400V
11.1
400V
14.8
400V
14.8
400V
21.5
400V
21.5
400V
15.4
400V
23
400V
Note
The table above details typical units based upon space heating applications on a temperature rise of 45ºC.
Alternative airflows, heat outputs and static pressures may be specified to match precise application requirements up to a maximum temperature rise of 55ºC.
External pressure available up to 525 pascals with increased motor sizes.
Gas rates and gas connections listed are for natural gas. LPG options are available on request.
For higher pressures consult Niche.
TTW
Model
TTW
30
30PD
60
60PD
100
150
Length (mm)
1350
1800
1800
1800
2000
2000
Case dimension
Width (mm)
Height (mm) Base height (mm)
545
585
n/a
860
700
50
860
700
50
860
700
50
1100
900
50
1100
900
50
Duct connections
Width (mm)
Height (mm)
485
525
800
640
800
640
800
640
1040
840
1040
840
Weight approx
(kg)
140
300
300
300
350
350
Duct connections
Width (mm)
Height (mm)
various
various
various
various
various
various
various
various
various
various
various
various
Weight approx
(kg)
350
350
400
400
400
400
Duct connections
Width (mm)
Height (mm)
800
640
800
640
800
640
800
640
800
640
1040
840
1040
840
1250
1050
1705
1250
1705
1250
1800
1645
1800
1645
2000
1850
2000
1850
2300
1850
2540
2110
2540
2110
Weight approx
(kg)
300
300
300
300
300
350
350
450
550
550
700
700
900
900
1200
1420
1420
Note
The table above details units in horizontal configuration, with horizontal inlet and discharge.
Duct connections will vary with discharge orientation options.
The base height must be added to case height to obtain overall height for the horizontal configuration.
Weights are approximate and can vary depending on fan and motor assembly selected.
Insulation will add weight to units.
Designed and produced by Kate Marston Email kate@koadesign.co.uk
Dimensions and weights
MUA/LSD
Model
MUA/LSD
100
150
200
200 3PH
350
350 3PH
Length (mm)
900
900
1050
1050
1050
1050
Case dimension
Width (mm)
Height (mm) Base height (mm)
700
1700
500
700
1700
500
800
1700
500
800
1700
500
800
1700
500
800
1700
500
Note
The table above details units in vertical configuration, with bottom inlet and top discharge.
Duct connections will vary with discharge orientation options.
The base height must be added to case height to obtain overall height for the vertical configuration.
Consult Niche for orientation, discharge options and X plate heat exchanger options.
Weights are approximate and can vary depending on fan and motor assembly selected.
Model
MUA
10DD
10PD
20DD
20PD
25
35
50
75
100
125
150
175
200
225
250
275
300
Length (mm)
1800
1800
1800
1800
1800
2000
2000
2200
2400
2400
2550
2550
2550
2550
2750
3200
3200
Case dimension
Width (mm)
Height (mm) Base height (mm)
860
700
50
860
700
50
860
700
50
860
700
50
860
700
50
1100
900
50
1100
900
50
1350
1150
75
1805
1350
75
1805
1350
75
1900
1745
100
1900
1745
100
2100
1950
100
2100
1950
100
2400
1950
100
2640
2210
100
2640
2210
100
Note
The table above details units in horizontal configuration, with horizontal inlet and discharge.
Duct connections will vary with discharge orientation options.
The base height must be added to case height to obtain overall height for the horizontal configuration.
MUA 150 and above consists of burner module and fan assembly module.
Weights are approximate and can vary depending on fan and motor assembly selected.
Insulation will add weight to units.
Niche
Unit 28 Rifle Hill Works
Braintree Essex
CM7 1EN United Kingdom
Telephone 01376 332200
Facsimile 01376 332201
Email sales@niche.ltd.uk
Website www.niche.ltd.uk
NICHE is the registered
trademark of Ambi-Rad Limited.
Due to continuous product
innovation, Niche reserves the right
to change product specification
without due notice.
Document reference number GB/NIC/001/0805 (1K 2005)