CONVENTIONAL FIRE ALARM PANEL
FP9000L-2/4/6/8
TECHNICAL CHARACTERISTICS
LINES














 Lines:
2, 4, 6 or 8
Number of lines
32
Maximum number of fire detectors in a line
biconductional
Type of the joining line
Plume maximum resistance
100 
 Current thresholds in the lines:
from 1 to 4 mA
Interruption
from 4 to 16 mA
Duty mode
from 17 to 70 mA
Fire
from 40 to 70 mA
Fire direct /without delay outputs/
> 70 mA
Short circuit
 Lines functional characteristics:
Verification quantity before entering Fire
2
mode:
Verification and regestrating fault in a earth
yes
conductor
OUTPUTS
 Independent relay output in case of fire alarm:
1
Quantity
switching
Type
3А/125V AC,
Electrical characteristics
3A/30V DC
Optional
selectively
NC / NO
“DMTeh” Ltd. Pleven, Bulgaria, 34 Gen. Lieutenant Atahas Stefanov Str., office 7, Tel. 0889992660,
web: http://dm-teh.com, e-mail: office@dm-teh.com
DMTeh Ltd.
Fire alarm panel FP9000L-2/4/6/8
 Controllable output in case of fire alarm:
2
 Quantity
potentional relay
 Type
(19-28)VDC/ 0,5A
 Electrical characteristics
 Additional relay outputs (modul M9000R 2/4/6/8) in case of fire alarm:
2/4/6/8
 Quantity
potentional-free
NO
 Type
3А/125V AC,
 Electrical characteristics
3A/30V DC
 Independent relay output in case of failure:
1
 Quantity
potentional-free,
NC / NO
 Type
switching
3А/125V AC,
 Electrical characteristics
3A/30V DC
 Delay outputs:
0 ÷ 7 minutes
 Time delay of switching outputs
POWER SUPPLY
 Mains power
(187-252)V AC
 Voltage
50/60 Hz
 Frequency
38W / AC
 Maximum power to mains power
 Battery power
2
 Battery quantity
Lead, gel
 Type of the battery
12V DC
 Battery rated voltage
1.3Ah, 4.5Ah, 5 Ah
 Reted power C20
temperature
27,6 VDC
 Charger voltage
compensated
Consumption of battery power in standby mode
< 40 mA to 24 VDC
 Configuration with 2 lines
< 50 mA to 24 VDC
 Configuration with 4 lines
< 60 mA to 24 VDC
 Configuration with 6 lines
< 70 mA to 24 VDC
 Configuration with 8 lines
Time needed in security mode when mains power supply is down with battery 12V/ 5Ah
120h
 Configuration with 2 lines
90h
 Configuration with 4 lines
80h
 Configuration with 6 lines
72h
 Configuration with 8 lines
Time needed in security mode when mains power supply is down with battery
12V/1.3Ah
32h
 Configuration with 2 lines
Executive devicess powering
(19-28)V DC
 Voltage
 Maximal current (including the controllable
1А
outputs current)
Fuses
4,0 A fusible
 Mains power 230V AC
4,0 А fusible
 Battery power
Technical characteristics
Redaction 1/16
Page 2 of 3
DMTeh Ltd.
Fire alarm panel FP9000L-2/4/6/8
 Powering external devices
 Controllable outputs









1,85 А automatic
1,1 А automatic
Functional characteristics
Control of the lines and controllable outputs for fault conditions (short circuit and
interruption) and automatic reset;
Ability to delay controllable and general outputs for fire for a period of 0 to 7 minutes
after the registration of state Fire with DIP switch;
Built-in sounder in case of fire – monotonal, continuous with the possibility of exclusion;
Test mode of each (fire alarm) lines;
Ability to Disable each of the fire alarm lines;
Ability to Disable controllable outputs for fire;
Interface for communication with external devices RS485 and networking / optional /;
Possibility for GPRS communication and remote control and monitoring / optional /;
Possibility Ability to add module relay M9000R-2/4/6/8. The module expands the outputs
of the Panel.
 Over all size
310х240х80 mm
 Weight without batteries
1,25 kg
 Safety degree
IP30/ EN 60529
The panel meets standarts:










EN 54-2:1997
EN 54-2:1997/A1:2006
EN 54-2:1997/AC:1999
EN 54-4:1997
EN 54-4:1997/A1:2002
EN 54-4:1997/A2:2006
EN 54-4:1997AC:1999
EN 50130-4:2011
EN 55022:2006/А1:2007
EN 60950-1:2006/А11:2009
DELIVEERY COMPOSITION AND COMPLEXITY/SET
 Fire Station FP 9000L
 EOL - resistor 4,7k/0,5W:
- for configuration with 2 lines /FP9000-2/
- for configuration with 4 lines /FP9000-4/
- for configuration with 6 lines /FP9000-6/
- for configuration with 8 lines /FP9000-8/
 (EOL) End for controllable output - resistor 4,7k/0,5W;
 Fuse 4,0А;
 Connective bridge for batteries;
 Packaging.
Technical characteristics
Redaction 1/16
1 qty.
2 qty.
4 qty.
6 qty.
8 qty.
2 qty.
2 qty.
1 qty.
1 qty.
Page 3 of 3