technical guide technical guide

5167825-BTG-F-0217
TECHNICAL
GUIDE
Description
ASHRAE 90.1 COMPLIANT
XA units are convertible single packages with a common
footprint cabinet and common roof curb for all 6.5 through 12.5
ton models. All units have two compressors with independent
refrigeration circuits to provide 2 stages of cooling. The units
were designed for light commercial applications and can be
easily installed on a roof curb, slab, or frame.
R-410A
XA SERIES
6.5 THRU 12.5 TON
60 Hertz
All XA units are self-contained and assembled on rigid full
perimeter base rails allowing for 3-way forklift access and
overhead rigging. Every unit is completely charged, wired,
piped, and tested at the factory to provide a quick and easy field
installation.
XA units in all tonnage sizes are convertible between side
airflow and down airflow, with corresponding economizer if
economizer option is desired.
XA units are available in the following configurations: heat
pump and heat pump with electric heat. Electric heaters are
available as factory-installed options or field-installed
accessories.
Tested in accordance with:
6.5 THROUGH 10 TON
12.5 TON
FOR DISTRIBUTION USE ONLY - NOT TO BE USED AT POINT OF RETAIL SALE
5167825-BTG-F-0217
Table of Contents
Description . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1
Table of Contents . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2
Component Location . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2
Nomenclature . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3
Prior Nomenclature . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4
Features and Benefits . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5
Guide Specifications . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 10
Physical Data . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 13
Capacity Performance . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 15
Airflow Performance . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 28
Sound Performance . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 35
Electrical Data . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 37
Typical Wiring Diagrams . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 45
Weights and Dimensions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 53
Economizer Options . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 60
Component Location
Heat Pump
Smart Equipment™ Control
board w/screw connectors for T-stat wiring and
network connection
Terminal block
for hi-voltage
connection
Disconnect location
(optional disconnect switch)
Filter access
(2” or 4” filter options)
Filter drier (solid core)
Condenser
section
Second Model
Nameplate Inside
Control Door
Slide-out motor and
blower assembly for
easy adjustment and
service.
Dual stage cooling for maximum
comfort (7.5 12.5 Only)
Compressor #2
Access (High-Eff
Compressor)
Base Rails w/ Forklift Slots (3 Sides)
& Lifting Holes
Belt-drive
blower
motor
Roof curbs in eight- and
fourteen-inch heights. Roof
curbs for transitioning from
the large footprint to the
XA series footprint are also
available (field installed
accessory)
Toolless
Door Latch
2
Side entry power
and control wiring
knockouts
Compressor #1 Access
(High-Eff Compressor)
Slide-out drain pain
with steel 3/4” NPT,
Female Connection
Johnson Controls Unitary Products
5167825-BTG-F-0217
Nomenclature
6.5-12.5 Ton Model Number Nomenclature
X A -10 C 00 A 2 A 1 A A A 1 A 1
Product Generation
Product Category
1 = First Generation
X = HP, Single Pkg., R-410A
Cabinet Options
A = Std Cabinet
E = SSD (SST Drain Pan)
Product Identifier
A = Pkg HP R410A Std Eff
Additional Options
Nominal Cooling Capacity
1
2
3
4
5
6
-06 = 6.5 Ton
-07 = 7.5 Ton
-08 = 8.5 Ton
-10 = 10.0 Ton
-12 = 12.5 Ton
=
=
=
=
=
=
STD Throwaway Filter
2" Pleated Filters (Merv 8)
4" Pleated Filters (Merv 13)
Coil Guard (CG), STD Filter
2" Pleated Filter,CG
4" Pleated Filter,CG
Refrigeration
Heat Type
A = Standard Refrigeration
B = ECC (E-Coat Cond Coil)
C = EEC (E-Coat Evap Coil)
F = ECC,EEC
C = Cooling Only
E = Electric Heat
Heat Capacity
Controls Option
00 = Cooling Only
Electric Heat (Unit Size Allowed)
09
18
24
36
54
=
=
=
=
=
A = Stand Alone Smart Equipment™
C = BACnet MSTP,Mdbs,N2 COM Card
D = CPC Control, DFS, APS
F = Fault Detection Diagnostics
G = Novar UCM Ctrl, DFS, APS
H = Hnywll Excel 10 CTRL,DFS,APS
M = Verasys Single Zone
N = Verasys Change Over Bypass
P = Verasys VAV
Q = Verasys Single Zone W/FDD
R = Verasys COBP W/FDD
T = Verasys VAV W/FDD
9 KW (-06, -07, -08)
18 KW (-06, -07, -08, -10, -12)
24 KW (-06, -07, -08, -10, -12)
36 KW (-06, -07, -08, -10, -12)
54 KW (-10, -12)
Blower Option
B = Standard Static
D = High Static
P = VFD IntelliSpeed Std Static
R = VFD IntelliSpeed High Static
S = VFD w/Byp IntelliSp Std Static
U = VFD w/Byp IntelliSp Hi Static
V = VFD Cust IntelliSp Std Static
X = VFD Cust IntelliSp Hi Static
Sensors
A = No Sensors
B = PHM (Phase Monitor)
C = DFS (Dirty Filter Switch)
D = SSD (Supply Air Smoke DET)
E = RSD (Return Air Smoke DET)
F = PHM,DFS
G = PHM,SSD
H = PHM,RSD
J = DFS,SSD
K = DFS,RSD
L = SSD,RSD
M = PHM,DFS,SSD
N = PHM,DFS,RSD
P = PHM,SSD,RSD
Q = DFS,SSD,RSD
R = PHM,DFS,SSD,RSD
Voltage
2 = 208/230-3-60
4 = 460-3-60
5 = 575-3-60
Outdoor Air Option
A = No Economizer
B = Economizer w/Barometric RLF
D = Economizer w/Power EXH
H = Motorized Damper
Service Options
1
2
3
4
5
6
Johnson Controls Unitary Products
=
=
=
=
=
=
No Service Options
DSC (Disconnect Switch)
NCO (Non-PWR Conv. Outlet)
PCO (Powered Conv. Outlet)
DSC,NCO
DSC,PCO
3
5167825-BTG-F-0217
Prior Nomenclature
6.5-12.5 Ton Single Package Model Number Nomenclature
For Units Produced Before 2-01-2016
X A -10 N18 A T A AA 7 0 1 2 4 A
Product Category
Product Style
X = HP, Single Pkg., R-410A
A = Style A
B = Style B
Configuration Options (not required for all units)
These four digits will not be assigned until a quote is requested, or an order placed.
Product Identifier
SS Drain Pan
A = 11.0+ EER HP
CPC Controller, DFS, APS
Honeywell Controller, DFS, APS
Novar Controller, DFS, APS
Simplicity®Smart Equipment w/Comm Card (BACnet, N2, Mod-Bus)
Nominal Cooling Capacity
Fault Detection and Diagnostics (FDD)
IntelliSpeed with VFD
-06 = 6.5 Ton
-07 = 7.5 Ton
-08 = 8.5 Ton
-10 = 10.0 Ton
-12 = 12.5 Ton
IntelliSpeed, VFD and Manual Bypass
IntelliSpeed, VFD Ready (for customer-provided, field-installed drive)
2" Pleated Filters, MERV 7
4" Pleated Filters, MERV 13
BAS Ready Economizer (2-10 V.D.C. Actuator without a Controller)
Shipping Bag
Heat Type and Nominal Heat Capacity
Any Combination of Additional Options that Don’t Have an Option Code Pre-assigned
C00 = Cooling Only. No heat installed
Product Generation
Electric Heat Options
7 = Seventh Generation
E09 = 9 KW
E18 = 18 KW
E24 = 24 KW
E36 = 36 KW
E54 = 54 KW
Additional Options
AA = None
AB = Phase Monitor
AC = Coil Guard
AD = Dirty Filter Switch
AE = Phase Monitor & Coil Guard
AF = Phase Monitor & Dirty Filter Switch
AG = Coil Guard & Dirty Filter Switch
AH = Phase Monitor, Coil Guard & Dirty Filter Switch
Airflow
A = Std. Motor
D = Std. Motor/Motorized Damper (Downflow Only)
H = Std Motor/Low Leak Econ/Barometric Relief (Downflow
& Horizontal End Return Only)
J = Std Motor/Low Leak Econ/Power Exhaust (Downflow
& Horizontal End Return Only)
N = Hi Static
R = Hi Static/Motorized Damper (Downflow Only)
V = Hi Static Mtr/Low Leak Econ/Barometric Relief
(Downflow & Horizontal End Return Only)
W = Hi Static Mtr/Low Leak Econ/Power Exhaust
(Downflow & Horizontal End Return Only)
Voltage
T = 208/230-3-60
W = 460-3-60
X = 575-3-60
TA = Technicoat Condenser Coil
TJ = Technicoat Evaporator Coil
TS = Technicoat Evaporator & Condenser Coils
EA = E-Coat Condenser Coil
EJ = E-Coat Evaporator Coil
ES = E-Coat Cond & Evap Coils
ZZ = If desired option combination is not listed above, ZZ will be assigned and configuration options will be
located in digits 15-18.
Installation Options
A = No Options Installed
B = Option 1
C = Option 2
D = Options 1 & 2
E = Option 3
F = Option 4
G = Options 1 & 3
H = Options 1 & 4
J = Options 1, 2 & 3
K = Options 1, 2, & 4
L = Options 1,3 & 4
M = Options 1, 2, 3, & 4
N = Options 2 & 3
P = Options 2 & 4
Q = Options 2, 3, & 4
R = Options 3 & 4
S = Option 5
T = Options 1 & 5
U = Options 1, 3, & 5
V = Options 1, 4, & 5
W = Options 1, 3, 4, & 5
X = Options 3 & 5
Y = Options 4 & 5
Z = Options 3, 4 & 5
Options
1 = Disconnect
2 = Non-Pwr'd Conv. Outlet
3 = Smoke Detector S.A.
4 = Smoke Detector R.A.
5 = Pwr'd Conv. Outlet
4
Johnson Controls Unitary Products
5167825-BTG-F-0217
Features and Benefits
Standard Features
• Service Friendly - The XA unit incorporates a number of
key features for ease of serviceability.
Service time is reduced through the use of hinged,
toolless panels. Such panels provide access to frequently
inspected components and areas, including the control
box, compressors, filters, indoor motor & blower, and the
heating section. The panels are screwed in place at the
factory to prevent access by children or other
unauthorized persons. It is recommended that the panels
be secured with screws once service is complete.
Service windows have been placed in both condenser
section walls. Rotation of the cover allows easy access to
the condenser coils for cleaning or inspection.
The Smart Equipment™ control board provides alarm
messages to help quickly identify any faults.
All units use the same standard filter size. This
standardization removes any confusion on which filter
sizes are needed for replacement.
The non-corrosive drain pan slides out of the unit to permit
easy cleaning. The drain pan is accessed by removing the
drain pan cover plate on the rear of the unit. Once the plate is
removed, the drain pan slides out through the rear of the unit.
All XA units have a second model nameplate located
inside the control access door. This is to prevent
deterioration of the nameplate through weathering.
• Environmentally Aware - For improved Indoor Air
Quality, a combination of aluminum foil faced and
elastometric rubber insulations are used exclusively
throughout the units.
• Convertible Airflow Design – The side duct openings
are covered when they leave the factory. If a side supply/
return is desired, the installer simply removes the two side
duct covers from the outside of the unit and installs them
over the down shot openings. No panel cutting is required.
Convertible airflow design allows maximum field flexibility
and minimum inventory.
• System Protection - Suction line freezestats are supplied
on all units to protect against loss of charge and coil frosting
when the economizer operates at low outdoor air
temperatures while the compressors are running. Every unit
has solid-core liquid line filter-driers and high and lowpressure switches. Internal compressor protection is
standard on all compressors. Phase Monitors are standard
on units with scroll compressors. This accessory monitors
the incoming power to the unit and protects the unit from
phase loss and reversed phase rotation.
• Advanced Controls - Smart Equipment™ control boards
have standardized a number of features previously
available only as options or by utilizing additional controls.
The Smart Equipment™ control board used in this
product will effectively operate the cooling system
down to 0°F when this product is applied in a comfort
cooling application for people. An economizer is
typically included in this type of application. When
applying this product for process cooling applications
(computer rooms, switchgear, etc.), please
reference applications bulletin AE-011-07 or call the
applications department for Unitary Products @ 1877-UPG-SERV for guidance. Additional
accessories may be needed for stable operation at
temperatures below 30°F.
• Units will come with the new state of the art Smart
Equipment™ control system. The new unit control
incorporates the best of the already proven Simplicity™
unitary controls and creates a more robust, intelligent
control. The goal of this control is to utilize cutting edge
technology making the equipment easier to install,
operate, and service. All units are Factory commissioned,
configured, and run tested.
• Versatile - The Smart Equipment™ control can be
configured to use with a standard thermostat (easy to
connect screw terminals), A zone sensor, or can be setup
to communicate with multiple BAS communication
protocols to integrate with building automation systems.
• Reduce field installed complexity - Each unit will comes
equipped with factory installed supply air, return air, and
outdoor air temperature sensors providing key
temperature readings thus reduce field installed
complexity.
• On-board USB Port - The new control comes with a long
list of features including data logging, current and
previous system faults and software update capabilities
using the on board USB port and common flash drive.
Energy use monitoring capabilities allow custom tailoring
to allow a system to work more efficiently at all times and
occupancy levels. Self test and start-up reports also
Johnson Controls Unitary Products
available from the board VIA the USB port.
5
5167825-BTG-F-0217
• Embedded LCD Display - The board has a easy to read,
built-in LCD display and easy to use navigation joystick
and buttons allowing the user to quickly navigate the
menus displaying unit status, options, current function,
supply, return and outdoor temperatures, fault codes and
other information.
• Safety Monitoring - The control monitors the outdoor,
supply, and return air temperatures and the high and low
pressure switch status on the independent refrigerant
circuits. On units with heating the gas valve and high
temperature limit switches are monitored on gas and
electric heating units. The control also monitors the
voltage supplied to the unit and will protect the unit if low
voltage due to a brown out, or other electrical issue
occurs.
• Low Ambient - An integrated low-ambient control allows
units to operate in the cooling mode down to 0°F outdoor
ambient without additional components or intervention.
Optionally, the control board can be programmed to
lockout the compressors when the outdoor air
temperature is low or when free cooling is available.
• Anti-Short Cycle Protection - To aid compressor life, an
anti- short cycle delay is incorporated into the standard
control. Compressor reliability is further ensured by
programmable minimum run times. For testing, the antishort cycle delay can be temporarily overridden with the
push of a button.
• Fan Delays - Fan on and fan off delays are fully
programmable. Furthermore, the heating and cooling fan
delay times are independent of one another. All units are
programmed with default values based upon their
configuration of cooling and/or heating capacity.
• Nuisance Trip Protection and Three Strikes - To
prevent nuisance calls, the control board uses a three
times, you're out philosophy. The high, low-pressure
switch, anti-freeze protection, low voltage or heating high
limit must trip three times within two hours before the unit
control board will lock out the associated compressor.An
alarm message will be displayed on the LCD screen.
• Lead-Lag - An integrated Lead-Lag option allows equal
run time hours on all compressors, thereby extending the
life of all compressors. This option is selectable on the unit
control board.
• Low Limit Control (LLC) - To prevent the supply air from
dropping below a specified set point, when there is a
demand for cooling during cold outside conditions.
(Programmable Set point)
• Reliable - From the beginning - All units undergo
computer automated testing before they leave the factory.
Units are tested for refrigerant charge and pressure, unit
amperage, and 100% functionality. For the long term - All
units are painted with a long lasting, powder paint that
stands up over the life of the unit. The paint used has
been proven by a 1000 hour salt spray test.
• Full Perimeter Base Rails - The permanently attached
base rails provide a solid foundation for the entire unit and
protect the unit during shipment. The rails offer rigging
holes so that an overhead crane can be used to place the
units on a roof.
6
• Easy Installation - Gas and electric utility knockouts are
supplied in the unit underside as well as the side of the
unit. Utility connections can be made quickly and with a
minimum amount of field labor. All units are shipped with
2" throw-away filters installed.
• Wide Range of Indoor Airflows - All supply air blowers
are equipped with a belt drive that can be adjusted to
meet the exact requirements of the job. A high static drive
option is available for applications with a higher CFM and/
or static pressure requirement.
• Warranty - All models include a 1-year limited warranty
on the complete unit. Compressors and electric heater
elements each carry a 5-year warranty. Aluminized steel
(10 yr.) and stainless steel tubular heat exchangers carry
a 15- year warranty.
Factory Installed Options
UP offers several equipment options factory installed, for the
XAline.
• Optional Factory Installed Economizers - XA units offer
a variety of optional factory installed economizers with low
leak dampers. The outdoor air dry bulb sensor enables
economizer operation if the outdoor air temperature is less
than the set point of the economizer logic module. See
economizer options section to determine the correct
economizer for your application.
• Down flow / End Return Economizers (with barometric
relief and fresh air hood) - All units offer a variety of
optional factory installed down flow economizers that are
shipped, installed and wired with low leak dampers
designed to meet ASHRAE 90.1-2010, AMCA 511 Class
1A damper, and the International Energy Conservation
Code (IECC) certification requirements by achieving
leakage rates of 3 cfm/sq. ft. at 1" of static pressure. Each
economizer goes through a rigorous 60,000 cycle test. Dry
bulb, single enthalpy, and dual enthalpy (with field installed
kit) can be selected. The economizer has spring return,
fully modulating damper actuators and is capable of
introducing up to 100% outdoor air. As the outdoor air
intake dampers open, the return air dampers close. The
changeover from mechanical refrigeration to economizer
operation is regulated by the outdoor air dry bulb
temperature or the outdoor air enthalpy input. The optional
(field installed) single or dual enthalpy kits provide
additional inputs to monitor outdoor air/ or return air
humidity and temperature for true enthalpy control. The
installer needs only to assemble the outdoor air hood,
attach the enthalpy control the hood and mount the hood
to the unit (Hood and control are provided).
• Power Exhaust - This factory option allows down flow or
horizontal end return economizer operation. The power
exhaust must be removed from the unit and mounted
in the horizontal end return duct work when applying
the product in the horizontal, end return
configuration.
• Motorized Outdoor Air Damper - The motorized outdoor
air damper includes a slide-in/plug-in damper assembly
with an outdoor air hood and filters. The outdoor air
dampers open to the preset position when the indoor fan
motor is energized. The damper has a range of 0% to
100% outdoor air entry.
Johnson Controls Unitary Products
5167825-BTG-F-0217
• Alternate Indoor Blower Motor - For applications with
high static restrictions, units are offered with optional
indoor motors that provide higher static output and/or
higher airflow, depending upon the installer’s needs.
• Stainless Steel Drain Pan - An optional rust-proof
stainless steel drain pan is available to provide years of
trouble-free operation in corrosive environments.
• Electric Heaters - The electric heaters range from 9kW to
54kW and are available in all the voltage options of the
base units. All heaters are dual staged. All heaters are
intended for single point power supply.
• IntelliSpeed™ Supply Fan Control Option (ASHRAE
90.1 compliant, section 6.4.3.10) - Units configured with
the IntelliSpeed™ Supply Fan Option will contain a VFD
for multi-speed supply fan operation. This option allows
the supply fan RPM to vary based on the number of
compressors or heating stages energized. The
economizer's minimum position will also be configurable
to vary based on the supply fan VFD frequency output.
• Disconnect Switch - For heat pump units with electric
heat, a HACR breaker sized to the unit is provided. For
heat pump units, a switch sized to the largest electric heat
available for the particular unit is provided. Factory
installed option only.
• Convenience Outlet - (Non-Powered/Powered) - This
option locates a 120V single-phase GFCI outlet with cover,
on the corner of the unit housing adjacent to the
compressors. The “Non-powered” option requires the
installer to provide the 120V single-phase power source and
wiring. The “Powered” option is powered by a stepdown
transformer in the unit. Factory installed option only.
• Smoke Detectors - The smoke detectors stop operation
of the unit and provide a fault message to the control
board. Smoke detectors are available for both the supply
and/or return air configurations.
Factory installed smoke detectors in the return air, may be
subjected to freezing temperatures during "off" times due
to out side air infiltration. These smoke detectors have an
operational limit of 32 °F to 131°F. Smoke detectors
installed in areas that could be out side those limitations
will have to be moved to prevent having false alarms.
• Filters – 2” Pleated MERV 8 or 4” Pleated MERV 13 are
available to meet LEED requirements. A 2” Throwaway is
shipped as standard.
• Phase Monitors - Designed to prevent unit damage. The
phase monitor will shut the unit down in an out-of phase
condition. (Standard on units with Scroll Compressors.)
• Coil Guard - Customers can purchase a coil guard kit to
protect the condenser coil from damage. Additionally, this
kit stops animals and foreign objects from entering the
space between the inner condenser coil and the main
cabinet. This is not a hail guard kit.
• Dirty Filter Switch - This kit includes a differential
pressure switch that energizes the fault light on the unit
thermostat, indicating that there is an abnormally high
Johnson Controls Unitary Products
pressure drop across the filters. Factory installed option or
field installed accessory.
• E-Coat Condenser Coils - The condenser coils are
coated with an epoxy polymer coating to protect against
corrosion.
• E-Coat Evaporator Coils - The evaporator coils are
coated with an epoxy polymer coating to protect against
corrosion.
Control Options
• Smart Equipment™ with Communication Option
Control - The Unitary Products Smart Equipment™ with
Communication Option Control is factory installed. It
includes all the features of the Smart Equipment™ control
with an additional gateway to BACnet MS/TP
(programmable to Modbus or N2 protocols).
• FDD (Fault Detection and Diagnostics) - Refrigerant
side A factory installed control system option on the
commercial equipment that constantly monitors
refrigerant circuit pressures, refrigerant circuit
temperatures, as well as the environmental temperatures
and humidity via multiple sensor inputs.
• Provides a building owner, technician or contractor with
the operational characteristics of the RTUs entire
refrigerant circuit to ensure the unit is functioning at its
specified performance level.
• Provides alarms if the unit is not functioning optimally.
• Remotely accessible via the Mobile Access Portal (MAP)
gateway as well as scrolled on the UCB LCD screen.
• Novar® BAS Control - The Novar® building automation
system controller is factory installed. Includes supply air
sensor, return air sensor, dirty filter indicator switch, and
air proving switch.
• CPC BAS Control - The Computer Process Controls
Model 810-3060 ARTC Advanced Rooftop building
automation system controller is factory installed. Includes
supply air sensor, return air sensor, with optional dirty
filter indicator switch and air proving switch.
• Honeywell BAS Control - The Honeywell W7750C
building automation system controller is factory installed.
Includes air supply sensor, return air sensor, with optional
dirty filter indicator switch, and air proving switch.
• Verasys - Verasys provides a simple user experience
with configurable self-recognizing controllers without the
need for any additional tools. Verasys creates enhanced
integration of HVACR equipment, zoning, and controls.
Contractors are able to offer a complete bundled solution
of equipment and controls to serve the light commercial
market.
Field Installed Accessories
UP offers several equipment accessories for field installation,
for the XA line.
• Down flow and End Return Economizers (with fresh air
hood and barometric relief) - All units offer a variety of
optional factory installed down flow economizers that are
shipped, installed and wired with low leak dampers designed
to meet ASHRAE 90.1-2010, AMCA 511 Class 1A damper,
7
5167825-BTG-F-0217
•
•
•
•
•
•
8
and the International Energy Conservation Code (IECC)
certification requirements by achieving leakage rates of 3
cfm/sq. ft. at 1" of static pressure. Each economizer goes
through a rigorous 60,000 cycle test. Dry bulb, single
enthalpy, and dual enthalpy (with field installed kit) can be
selected. The economizer has spring return, fully modulating
damper actuators and is capable of introducing up to 100%
outdoor air. As the outdoor air intake dampers open, the
return air dampers close. The changeover from mechanical
refrigeration to economizer operation is regulated by the
outdoor air dry bulb temperature or the outdoor air enthalpy
input. The dual enthalpy kit provides a second input used to
monitor the return air (field installed). The installer needs only
to assemble the outdoor air hood, attach the enthalpy control
the hood and mount the hood to the unit (Hood and control
are provided).
Single or Dual Enthalpy Control, Accessories - These
kits contain the required components to convert a dry bulb
economizer to a single enthalpy and/or dual enthalpy
economizer.
Barometric Relief Damper - Zero to 100% capacity
barometric relief dampers for use with horizontal flow, or
field installed economizers.
Power Exhaust - This accessory installs in the unit with a
down flow or horizontal end return economizer. Power
exhaust plugs into the connector in the unit bulkhead.
User must purchase the 1EH0408 barometric relief
and hood kit when applying the product in a
horizontal flow application. The power exhaust must
be mounted in the horizontal end return ductwork.
Manual Outdoor Air Damper - Like the motorized outdoor
air damper, each manual outdoor air damper includes a
slide-in damper assembly with an outdoor air hood and
filters. Customers have a choice of dampers with ranges of
0% to 100% or 0% to 35% outdoor air entry.
Motorized Outdoor Air Damper - The motorized outdoor
air damper includes a slide-in/plug-in damper assembly with
an outdoor air hood and filters. The outdoor air dampers
open to the preset position when the indoor fan motor is
energized. The damper has a range of 0% to 100% outdoor
air entry. Factory installed option or field installed accessory.
Smoke Detectors - The smoke detectors stop operation
of the unit by interrupting power to the control board if
smoke is detected within the air compartment.
• CO2 Sensor - Senses CO2 levels and automatically
overrides the economizer when levels rise above the
preset limits.
• Dirty Filter Switch - This kit includes a differential
pressure switch that energizes the fault light on the unit
thermostat, indicating that there is an abnormally high
pressure drop across the filters.
• Coil Guard - Field installed decorative wire coil guard.
• Hail Guard - This kit includes a sloped hood which installs
over the outside condenser coil and prevents damage to
the coil fins from hail strikes. Field installed accessory only.
• Electric Heaters - The electric heaters range from 9 kW
to 54kW and are available in all the voltage options of the
base units. All heaters are dual staged. All units include
an adapter panel for easy installation of the electric
heaters. Necessary hardware and connectors are
included with the heaters. All heaters are intended for
single point power supply.
• Low Limit / Compressor Lockout Kit
• Compressor Lockout (CLO): To prevent mechanical
(compressorized) operation of the unit during cold
outdoor conditions where there is a risk of returning
liquid refrigerant back to the compressors.
• Low Limit Control (LLC): To prevent the supply air
from dropping below a specified setpoint by utilizing the
units first stage heating means when there is a demand
for cooling during cold outside conditions.
• Metal Frame Filter Kit - Metal frame with polyester filter
medium.
• Permanent Filters - Permanent filters are available.
• Roof Curbs - The roof curbs have insulated decks and are
shipped disassembled The roof curbs are available in 8” and
14” heights. For applications with security concerns, burglar
bars are available for the duct openings of the roof curbs.
• Roof Curb Transition - Single Piece Adapter (10” High) Roof curbs for transitioning from DHB/DUC/DHC/DUS
units to XA units. Fits 7.5 to 12.5 Ton roof curbs only.
• Burglar Bars - Mount in the supply and return openings
to prevent entry into the duct work.
• Thermostat - The units are designed to operate with 24volt electronic and electro-mechanical thermostats. All
units (with or without an economizer) operate with twostage heat/two-stage cool or two-stage cooling only
thermostats, depending upon unit configuration.
Johnson Controls Unitary Products
5167825-BTG-F-0217
Accessories
Part Number
1RC0470
1RC0471
1RC0472
1BD0408
2TP04520925
2TP04531825
2TP04532425
2TP04533625
2TP04525425
2TP04520946
2TP04531846
2TP04532446
2TP04533646
2TP04525446
2TP04520958
2TP04521858
2TP04522458
2TP04523658
2TP04525458
2TP04540925
2TP04541825
2TP04542425
2TP04543625
2TP04540946
2TP04541846
2TP04542446
2TP04543646
2TP04540958
2TP04541858
2TP04542458
2TP04543658
2MD04703824
2MD04703924
2EE04707624
2EE04707424
Description
Roof Curb, 8" Height
Roof Curb, 14" Height
Roof Curb, Transition (7.5 T through 12.5 T)
Burglar Bars, Downflow
Electric Heat 9kW 230V
Electric Heat 18kW 230V
Electric Heat 24kW 230V
Electric Heat 36kW 230V
Electric Heat 54kW 230V
Electric Heat 9kW 460V
Electric Heat 18kW 460V
Electric Heat 24kW 460V
Electric Heat 36kW 460V
Electric Heat 54kW 460V
Electric Heat 9kW 575V
Electric Heat 18kW 575V
Electric Heat 24kW 575V
Electric Heat 36kW 575V
Electric Heat 54kW 575V
Electric Heat 9kW 230V, 42" Tall Cabinet
Electric Heat 18kW 230V, 42" Tall Cabinet
Electric Heat 24kW 230V, 42" Tall Cabinet
Electric Heat 36kW 230V, 42" Tall Cabinet
Electric Heat 9kW 460V, 42" Tall Cabinet
Electric Heat 18kW 460V, 42" Tall Cabinet
Electric Heat 24kW 460V, 42" Tall Cabinet
Electric Heat 36kW 460V, 42" Tall Cabinet
Electric Heat 9kW 575V, 42" Tall Cabinet
Electric Heat 18kW 575V, 42" Tall Cabinet
Electric Heat 24kW 575V, 42" Tall Cabinet
Electric Heat 36kW 575V, 42" Tall Cabinet
Motorized Damper, Downflow without Barometric Relief
Motorized Damper, Horizontal
2EE04706924
Economizer for Downflow, End Return Horizontal, or ERV Applications. Includes FA Hood, Exhaust Hood w/Baro Relief
Economizer for Downflow, End Return Horizontal, or ERV Applications. Includes FA Hood, Exhaust Hood w/Baro Relief
Horizontal Economizer without Barometric Relief
2PE04704706*
2PE04704746*
2PE04704758*
2EC04700924
2EC0401
2EC0402
Power Exhaust 230V Downflow or Horizontal
Power Exhaust 460V Downflow or Horizontal
Power Exhaust 575V Downflow or Horizontal
Dual Enthalpy Control (Use with Single Enthalpy Economizer)
Single Enthalpy Control
Dual Enthalpy Control (Includes 2 Sensors)
1EH0408
Barometric Relief Kit for Power Exhaust, Horizontal Application
1FA0413
1FA0414
2AQ04700424
2AQ04700324
2SD04700824
2SD04700924
2SD04701024
2MK04700624
1CG0419
1CG0424
1CG0427
1HG0411
1HG0415
1FL0402
1FL0423
2DF0401
1FF0414
1FF0415
S1-YK-MAP1810-0P
Manual Outside Air Damper 0-35%, Downflow
Manual Outside Air Damper 0-100%, Downflow
CO2 Detector Unit Mount
CO2 Detector Space Mount
Smoke Detector for Supply (All Gen 5 and greater units with 2" & 4" Filters)
Smoke Detector for Return (All Gen 5 and greater units with 2" & 4" Filters)
Smoke Detector for Supply and Return (All Gen 5 and greater units with 2" & 4" Filters)
Low Limit / Compressor Lockout Kit
Coil Guard (Electric / Electric & HP models), 8-1/2 and 10 Ton
Coil Guard (Electric / Electric and HP models), 12-1/2 Ton
Coil Guard (Electric / Electric & HP Models), 6-1/2 and 7-1/2 Ton
Hail Guard Kit
Hail Guard Kit, 42" Tall Cabinet
Permanent Filter Kit
Permanent Filter Kit, 42" Tall Cabinet
Dirty Filter Switch
2” only Metal Filter Frame Kit, 50” Tall Cabinet
2” only Metal Filter Frame Kit, 42" Tall Cabinet
MAP (Mobile Access Portal) Gateway- For use with Smart Equipment™ Control.
MAP (Mobile Access Portal) Gateway Kit- Replacement MAP gateway protective case, lanyard and communication cable. Use only
to replace worn or damaged components.
S1-MP-PRTKIT-0P
Johnson Controls Unitary Products
9
5167825-BTG-F-0217
Guide Specifications
GENERAL
Units shall be manufactured by Unitary Products in an ISO
9001 certified facility. XA units are convertible single packages
with a common footprint cabinet and common roof curb for all
6.5 through 12.5 ton models. All units have two compressors
with independent R-410a refrigeration circuits to provide 2
stages of cooling. The units were designed for light commercial
applications and can be easily installed on a roof curb, slab, or
frame. All XA units are self-contained and assembled on rigid
full perimeter base rails allowing for 3-way forklift access and
overhead rigging. Every unit is completely charged with R410a, wired, piped, and tested at the factory to provide a quick
and easy field installation. All units are convertible between
side and down airflow. Independent economizer designs are
used on side and down discharge applications, as well as all
tonnage sizes. XA units are available in the following
configurations: heat pump and heat pump with electric heat.
Electric heaters are available as factory-installed options or
field-installed accessories.
DESCRIPTION
Units shall be factory assembled, single package (Heat Pump),
designed for outdoor installation. They shall have built in field
convertible duct connections for down discharge supply/return or
horizontal discharge supply/return and be available with factory
installed options or field installed accessories. The units shall be
factory wired, piped and charged with R-410a refrigerant and
factory tested prior to shipment. All unit wiring shall be both
numbered and color coded. The cooling performance shall be
rated in accordance with DOE and AHRI test procedures. Units
shall be CSA certified to ANSI Z21.47 and UL 1995/CAN/CSA No.
236-M90 standards.
UNIT CABINET
Unit cabinet shall be constructed of galvanized steel with
exterior surfaces coated with a non-chalking, powder paint
finish, certified at 1000 hour salt spray test per ASTM-B117
standards. Indoor blower sections shall be insulated with up to
1” thick insulation coated on the airside. Either aluminum foil
faced or elastometric rubber insulation shall be used in the
unit’s compartments and be fastened to prevent insulation from
entering the air stream. Cabinet doors shall be hinged with
toolless access for easy servicing and maintenance. Full
perimeter base rails shall be provided to assure reliable transit
of equipment, overhead rigging, fork truck access and proper
sealing on roof curb applications. Disposable 2” filters shall be
furnished and be accessible through hinged access door. Fan
performance measuring ports shall be provided on the outside
of the cabinet to allow accurate air measurements of evaporator
fan performance without removing panels or creating bypass of
the coils. Condensate pan shall be slide out design, constructed
of a non corrosive material, internally sloped and conforming to
ASHRAE 62-B9 standards. Condensate connection shall be a
minimum of ¾” I.D. female and be rigid mount connection.
10
INDOOR (EVAPORATOR) FAN ASSEMBLY
Fan shall be a belt drive assembly and include an adjustable
pitch motor pulley. Job site selected brake horsepower shall not
exceed the motors nameplate horsepower rating plus the service factor. Units shall be designed to operate within the service
factor. Fan wheel shall be double inlet type with forward curve
blades, dynamically balanced to operate smoothly throughout
the entire range of operation. Airflow design shall be constant
volume. Bearings shall be sealed and permanently lubricated
for longer life and no maintenance. Entire blower assembly and
motor shall be slide out design.
OUTDOOR (CONDENSER) FAN ASSEMBLY
The outdoor fans shall be of the direct drive type, discharge air
vertically, have aluminum blades riveted to corrosion resistant
steel spider brackets and shall be dynamically balanced for
smooth operation. The outdoor fan motors shall have permanently
lubricated bearings internally protected against overload
conditions and staged independently. A cleaning window shall be
provided on two sides of the units for coil cleaning.
REFRIGERANT COMPONENTS
Compressors:
a. Shall be fully hermetic type, direct drive, internally
protected with internal high-pressure relief and over
temperature protection. The hermetic motor shall be
suction gas cooled and have a voltage range of + or –
10% of the unit nameplate voltage.
b. Shall have internal spring isolation and sound muffling to
minimize vibration and noise, and be externally isolated
on a dedicated, independent mounting.
Coils:
a. Evaporator and condenser coils shall have aluminum
plate fins mechanically bonded to seamless internally
enhanced copper tubes with all joints brazed. Special
Phenolic coating shall be available as a factory option.
b. Evaporator and condenser coils shall be of the direct
expansion, draw-thru design.
Refrigerant Circuit and Refrigerant Safety Components shall
include:
a. Independent fixed-orifice
expansion devices.
or
thermally
operated
b. Solid core filter drier/strainer to eliminate any moisture or
foreign matter.
c. Accessible service gage connections on both suction
and discharge lines to charge, evacuate, and measure
refrigerant pressure during any necessary servicing or
troubleshooting, without losing charge.
d. The unit shall have two independent refrigerant circuits,
equally split in 50% capacity increments.
Johnson Controls Unitary Products
5167825-BTG-F-0217
Unit Controls:
a. Unit shall be complete with self-contained low-voltage
control circuit protected by a resettable circuit breaker on
the 24-volt transformer side.
b. Unit shall incorporate a lockout circuit which provides
reset capability at the space thermostat or base unit,
should any of the following standard safety devices trip
and shut off compressor.
1. Loss-of-charge/Low-pressure switch.
2. High-pressure switch.
a fully-modulating, spring-return damper actuator. The
maximum leakage rate for the outdoor air intake dampers
shall be designed to meet ASHRAE 90.1-2010, AMCA
511 Class 1A damper, and the International Energy
Conservation Code (IECC) certification requirements by
achieving leakage rates of 3 cfm/sq. ft. at 1" of static
pressure. Changeover from compressor to economizer
operation shall be provided by an integral electronic
enthalpy control that feeds input into the basic module.
The outdoor intake opening shall be covered with a rain
hood that matches the exterior of the unit. Water
eliminator/filters shall be provided.
3. Freeze condition sensor on evaporator coil. If any of
these safety devices trip, the LCD screen will display
the alarm message.
Simultaneous economizer/compressor operation is also
possible. Dampers shall fully close on power loss.
Available with barometric relief and power exhaust.
c. Unit shall incorporate "AUTO RESET" compressor over
temperature, over current protection.
• MOTORIZED OUTDOOR AIR DAMPERS - Outdoor and
return air dampers that are interlocked and positioned by
a 2- position, spring-return damper actuator. A unitmounted potentiometer shall be provided to adjust the
outdoor and return air damper assembly to take in the
design CFM of outdoor air to meet the ventilation
requirements of the conditioned space during normal
operation. Whenever the indoor fan motor is energized,
the dampers open up to one of two pre-selected positions
- regardless of the outdoor air enthalpy. Dampers return to
the fully closed position when the indoor fan motor is deenergized. Dampers shall fully close on power loss.
d. Unit shall operate with conventional thermostat designs
and have a low voltage terminal strip for easy hook-up.
e. Unit control board shall have on-board diagnostics and
fault message display.
f. Standard controls shall include anti-short cycle and low
voltage protection, and permit cooling operation down to
a selectable value as low as 0 °F.
g. Control board shall monitor each refrigerant safety switch
independently.
ELECTRIC HEATING SECTION (IF EQUIPPED)
An electric heating section, with nickel chromium elements,
shall be provided in a range of 9 thru 54 KW, offering two states
of capacity all sizes. The heating section shall have a primary
limit control(s) (automatic reset) to prevent the heating element
system from operating at an excessive temperature. The Heating Section assembly shall slide out of the unit for easy maintenance and service. Units with Electric Heating Sections shall be
wired for a single point power supply with branch circuit fusing
(where required).
UNIT OPERATING CHARACTERISTICS
Unit shall be capable of starting and running at 125 ºF outdoor
temperature, exceeding maximum load criteria of AHRI Standard 340/360. The compressor, with standard controls, shall be
capable of operation down to 0 ºF outdoor temperature.
ELECTRICAL REQUIREMENTS - All unit power wiring shall
enter unit cabinet at a single factory provided location and be
capable of side or bottom entry to minimize roof penetrations
and avoid unit field modifications. Separate side and bottom
openings shall be provided for the control wiring.
ADDITIONAL FACTORY INSTALLED OPTIONS
• ALTERNATE INDOOR BLOWER MOTOR – For
applications with high restrictions, units are available with
optional indoor blower motors that provide higher static
output and/or higher airflow.
• CONVENIENCE OUTLET (POWERED/NON-POWERED)–
Unit can be provided with an optional 120VAC GFCI outlet
with cover on the corner of the unit housing the compressors.
• ELECTRIC HEAT - Electric Heaters range from 9 kW to
54 kW and are available in all the voltage options of the
base unit.
• PHASE MONITOR - Designed to prevent damage in outof-phase condition.
• COIL GUARD - Designed to prevent condenser coil
damage.
• BAS CONTROLS HARDWARE - Include supply air
sensor, return air sensor, dirty filter indicator and air
proving switch.
• DIRTY FILTER SWITCH – This kit includes a differential
pressure switch that energizes the fault light on the unit
thermostat, indicating that there is an abnormally highpressure drop across the filters.
STANDARD LIMITED WARRANTIES - Compressor – 5 Years,
Elect. Heat Elem. – 5 Years, Parts – 1 Year
• BREAKER – An HACR breaker can be factory installed
on heat pumps or heat pumps with electric heat.
FACTORY INSTALLED OPTIONAL OUTDOOR AIR (Shall be
made available by either/or):
• DISCONNECT SWITCH - A disconnect can be factory
installed on a cooling only units sized for the largest
electric heat available.
• DRY BULB AUTOMATIC ECONOMIZER - Outdoor and
return air dampers that are interlocked and positioned by
Johnson Controls Unitary Products
11
5167825-BTG-F-0217
• SMOKE DETECTOR – A smoke detector can be factory
mounted and wired in the supply and/or return air
compartments.
OTHER PRE-ENGINEERED ACCESSORIES AVAILABLE
• ROOF CURB - 14” and 8” high, full perimeter knockdown
curb, with hinged design for quick assembly.
• BAROMETRIC RELIEF DAMPER – (Unit mounted –
Downflow, Duct Mounted – Horizontal) – Contains a rain
12
hood, air inlet screen, exhaust damper and mounting
hardware. Used to relieve internal air pressure through
the unit during economizer operation.
• ECONOMIZER (Downflow and Horizontal flow)
• POWER EXHAUST – (Unit mount – Downflow, Duct
mount – Horizontal flow)
• DUAL ENTHALPY KIT - Provides a second input to
economizer to monitor return air.
Johnson Controls Unitary Products
5167825-BTG-F-0217
Physical Data
XA-06 thru -12 Physical Data
Component
Models
XA-06
XA-07
XA-08
XA-10
XA-12
6.5
7.5
8.5
10
12.5
Gross Capacity @ AHRI A point (Mbh)
80000
92550
105600
122000
158300
AHRI net capacity (Mbh)
78000
90000
100000
115000
148000
EER
12.0
11.4
11.2
11.0
11.0
IEER with Constant Volume
12.2
12.2
12.4
11.6
10.8
IEER with Intellispeed
13.2
12.6
13.5
12.2
11.3
Nominal Tonnage
AHRI COOLING PERFORMANCE
IPLV
12.4
12.4
12.4
12.4
11.9
Nominal CFM
2600
3000
3750
3750
4900
System power (KW)
Refrigerant type
6.78
8.18
9.27
10.45
13.64
R-410A
R-410A
R-410A
R-410A
R-410A
Refrigerant charge (lb-oz)
System 1
14-2
13-0
13-12
12-14
17-6
System 2
12-10
13-2
13-13
12-12
17-8
AHRI HEATING PERFORMANCE
47°F capacity rating (Mbh)
75.0
88.0
94.0
106.0
135.0
System power (KW) / COP
6.2 / 3.40
7.7 / 3.40
7.9 / 3.40
8.6 / 3.40
13.2 / 3.2
17°F capacity rating (Mbh)
43.0
51.0
53.0
59.0
90.0
System power (KW) / COP
5.7 / 2.25
6.4 / 2.25
6.9 / 2.25
7.8 / 2.25
13.5 / 2.20
Length
89
89
89
89
119-7/16
Width
59
59
59
59
59
Height
50-3/4
50-3/4
50-3/4
50-3/4
50-3/4
1080
1090
1137
1135
1403
Scroll
Scroll
Scroll
Scroll
Scroll
2
2
2
2
2
50 / 100
50 / 100
50 / 100
50 / 100
50/100
29.0
29.0
29.0
29.0
47.5
2
2
2
2
2
DIMENSIONS (inches)
OPERATING WT. (lbs.)
COMPRESSORS
Type
Quantity
Unit Capacity Steps (%)
CONDENSER COIL DATA
Face area (Sq. Ft.)
Rows
Fins per inch
16
16
16
16
15
Tube diameter (in.)
3/8
3/8
3/8
3/8
3/8
Split-face
Split-face
Split-face
Split-face
Split-face
TXV
TXV
TXV
TXV
TXV
13.2
Circuitry Type
Refrigerant control
EVAPORATOR COIL DATA
Face area (Sq. Ft.)
13.2
13.2
13.2
13.2
Rows
4
4
4
4
4
Fins per inch
15
15
15
15
15
Tube diameter
3/8
3/8
3/8
3/8
3/8
Circuitry Type
Split-face
Split-face
Split-face
Split-face
Split-face
TXV
TXV
TXV
TXV
TXV
Refrigerant control
Johnson Controls Unitary Products
13
5167825-BTG-F-0217
XA-06 thru -12 Physical Data (Continued)
Models
Component
XA-06
XA-07
XA-08
XA-10
XA-12
6.5
7.5
8.5
10
12.5
2
2
2
2
4
Nominal Tonnage
CONDENSER FAN DATA
Quantity of Fans
Fan diameter (Inch)
24
24
24
24
24
Type
Prop
Prop
Prop
Prop
Prop
Drive Type
Direct
Direct
Direct
Direct
Direct
2
2
2
2
4
1/3
1/3
1/3
1/3
1/3
Quantity of motors
Motor HP each
No. speeds
1
1
1
1
1
RPM
850
850
850
850
850
Nominal total CFM
6800
6800
6800
6800
14000
BELT DRIVE EVAP FAN DATA
Quantity
Fan Size (Inch)
Type
1
1
1
1
1
15 x 15
15 x 15
15 x 15
15 x 15
15 x 15
Centrifugal
Centrifugal
Centrifugal
Centrifugal
Centrifugal
Motor Sheave
VL40
VL44
1VL40
1VM50
1VP50
1VP50
1VM50
1VM50
1VM50
1VP56
Blower Sheave
AK84
AK71
AK69
AK69
AK89
AK74
AK84
AK74
AK74
BK77
Belt
A54
A52
A52
A54
A56
A54
A56
A54
A54
BX56
Motor HP each
1-1/2
2
1-1/2
3
2
3
2
3
3
5
RPM
1725
1725
1725
1725
1725
1725
1725
1725
1725
1725
56
56
56
56
56
56
56
56
56
184T
Frame size
FILTERS
4 - (24 x 20 x 2)1,2 4 - (24 x 20 x 2)1,2 4 - (24 x 20 x 2)1,2 4 - (24 x 20 x 2)1,2 4 - (24 x 20 x 2)1,2
Quantity - Size
4 - (24 x 20 x 2)3
4 - (24 x 20 x 4)3
4 - (24 x 20 x 4)3
4 - (24 x 20 x 2)3
4 - (24 x 20 x 4)3
1. 2 In. Throwaway, Standard, MERV (Minimum Efficiency Reporting Value) 3.
2. 2 In. Pleated, Optional, MERV 8.
3. 4 In. Pleated, Optional, MERV 13.
XA-06 thru -12 Unit Limitations
Unit Limitations
Size
(Tons)
-06
(6.5)
-07
(7.5)
-08
(8.5)
-10
(10)
-12
(12.5)
14
Model
XA
XA
XA
XA
XA
Unit Voltage
Applied Voltage
Outdoor DB Temp
Min
Max
Max (°F)
208/230-3-60
187
252
125
460-3-60
432
504
125
575-3-60
540
630
125
208/230-3-60
187
252
125
460-3-60
432
504
125
575-3-60
540
630
125
208/230-3-60
187
252
125
460-3-60
432
504
125
575-3-60
540
630
125
208/230-3-60
187
252
125
460-3-60
432
504
125
575-3-60
540
630
125
208/230-3-60
187
252
125
460-3-60
432
504
125
575-3-60
540
630
125
Johnson Controls Unitary Products
5167825-BTG-F-0217
Capacity Performance
XA-06 thru -12 Cooling Capacities
XA-06 (6.5 Ton)
Air on
Evaporator Coil
CFM
1625
1950
2275
2600
2925
3250
1625
1950
2275
2600
2925
WB
(°F)
Total
Capacity1
(MBh)
Total
Input
(kW)2
77
72
67
62
77
72
67
62
57
77
72
67
62
57
77
72
67
62
57
72
67
62
57
72
67
62
57
107.3
99.2
91.1
81.6
112.8
104.3
95.7
85.8
83.3
118.3
109.4
100.4
90.0
87.4
123.8
114.4
105.1
94.2
91.5
117.9
108.2
97.1
94.2
121.3
111.3
99.9
97.0
4.8
4.7
4.7
4.6
4.8
4.8
4.7
4.7
4.6
4.9
4.8
4.8
4.7
4.7
4.9
4.9
4.8
4.8
4.7
4.9
4.8
4.8
4.7
4.9
4.9
4.8
4.8
77
72
67
62
77
72
67
62
57
77
72
67
62
57
77
72
67
62
57
72
67
62
57
99.2
90.3
81.5
75.1
102.7
93.5
84.4
77.8
76.7
106.2
96.8
87.3
80.4
79.3
109.8
100.0
90.2
83.1
82.0
100.9
91.1
83.9
82.7
6.2
6.1
6.1
6.1
6.2
6.2
6.1
6.1
6.1
6.2
6.2
6.1
6.1
6.1
6.2
6.2
6.1
6.1
6.1
6.1
6.1
6.1
6.1
Johnson Controls Unitary Products
Temperature of Air on Condenser Coil
Sensible Capacity (MBh)
Total
Total
Return Dry Bulb (°F)
Capacity1
Input
(MBh)
(kW)2
90
85
80
75
70
65
75°F
47.0
38.9
30.7
103.2
5.5
57.9
49.8
41.7
33.5
94.7
5.4
68.8
60.7
52.6
44.5
36.4
86.3
5.4
81.6
70.5
61.8
53.7
45.5
37.4
78.4
5.3
53.0
43.7
34.4
107.7
5.5
65.2
55.9
46.6
37.3
98.9
5.5
77.4
68.1
58.8
49.5
40.2
90.1
5.4
85.8
78.4
69.1
59.8
50.5
41.2
81.8
5.4
83.3
81.9
72.6
63.3
54.0
44.7
80.0
5.4
58.9
48.5
38.0
112.3
5.5
72.5
62.0
51.5
41.1
103.1
5.5
86.0
75.5
65.1
54.6
44.1
93.9
5.5
90.0
86.3
76.5
66.0
55.6
45.1
85.2
5.4
87.4
86.7
80.3
69.8
59.4
48.9
83.4
5.4
64.9
53.3
41.6
116.8
5.6
79.7
68.1
56.5
44.8
107.2
5.5
94.5
82.9
71.3
59.7
48.0
97.6
5.5
94.2
94.2
83.8
72.2
60.6
48.9
88.7
5.4
91.5
91.5
88.0
76.4
64.7
53.1
86.7
5.4
85.1
72.4
59.7
47.0
109.4
5.5
102.9 88.1
75.4
62.6
49.9
99.6
5.5
97.1
97.1
90.5
77.8
65.1
52.4
90.5
5.4
94.2
94.2
92.5
79.8
67.1
54.3
88.5
5.4
90.6
76.7
62.9
49.1
111.6
5.5
111.3 93.3
79.5
65.6
51.8
101.6
5.5
99.9
99.9
97.3
83.5
69.6
55.8
92.3
5.4
97.0
97.0
97.0
83.2
69.4
55.6
90.2
5.4
95°F
44.1
36.5
28.8
92.8
7.0
54.5
46.8
39.1
31.4
84.1
7.0
64.8
57.1
49.4
41.7
34.0
75.4
7.0
75.1
71.1
60.4
52.7
45.0
37.3
69.4
6.9
49.6
40.5
31.4
95.7
7.0
60.8
51.7
42.7
33.6
86.8
7.0
72.1
63.0
53.9
44.9
35.8
77.8
7.0
77.8
75.1
66.0
57.0
47.9
38.8
71.6
6.9
76.7
76.1
67.0
57.9
48.9
39.8
71.9
6.9
55.0
44.5
34.1
98.7
7.0
67.2
56.7
46.3
35.8
89.4
7.0
79.4
68.9
58.5
48.1
37.6
80.2
7.0
80.4
79.1
71.6
61.2
50.7
40.3
73.8
6.9
79.3
79.0
72.7
62.2
51.8
41.3
74.1
6.9
60.4
48.6
36.7
101.6
7.0
73.5
61.7
49.9
38.1
92.1
7.0
86.7
74.9
63.1
51.2
39.4
82.6
7.0
83.1
83.1
77.2
65.4
53.6
41.8
76.0
6.9
82.0
82.0
78.4
66.5
54.7
42.9
76.3
6.9
79.6
66.6
53.6
40.6
92.9
7.0
89.3
80.7
67.7
54.7
41.7
83.3
6.9
83.9
83.9
80.9
67.9
54.9
41.9
76.6
6.9
82.7
82.7
80.9
67.9
54.9
41.9
77.0
6.9
90
45.6
56.2
66.8
78.4
51.3
63.0
74.7
81.8
80.0
56.9
69.8
82.7
85.2
83.4
62.6
76.6
90.6
88.7
86.7
82.4
96.1
90.5
88.5
88.1
101.6
92.3
90.2
39.9
51.2
62.6
69.4
46.0
57.3
68.7
71.6
71.9
52.1
63.4
74.8
73.8
74.1
58.2
69.5
80.8
76.0
76.3
75.7
82.4
76.6
77.0
Sensible Capacity (MBh)
Return Dry Bulb (°F)
85
80
75
70
85°F
37.7
29.7
48.3
40.4
32.5
58.9
51.0
43.1
35.2
70.8
61.1
53.2
45.3
42.1
32.9
53.8
44.6
35.5
65.6
56.4
47.2
38.0
76.8
67.6
58.4
49.2
79.0
69.8
60.6
51.4
46.5
36.0
59.4
48.9
38.5
72.2
61.8
51.3
40.9
82.7
74.0
63.6
53.1
82.9
76.5
66.0
55.6
50.9
39.2
64.9
53.2
41.5
78.9
67.2
55.5
43.7
88.7
80.5
68.8
57.1
86.7
83.2
71.4
59.7
69.5
56.6
43.8
84.4
71.5
58.7
45.8
90.5
85.7
72.9
60.0
88.5
86.7
73.8
61.0
74.1
60.1
46.1
89.9
75.9
61.9
47.9
92.3
91.0
77.0
62.9
90.2
90.2
76.2
62.2
105°F
33.2
25.5
43.5
35.8
28.1
53.9
46.2
38.5
30.8
67.0
55.6
47.9
40.2
37.0
28.0
48.3
39.3
30.3
59.7
50.7
41.7
32.7
70.0
61.0
52.0
43.0
70.8
61.8
52.8
43.8
40.8
30.5
53.1
42.8
32.5
65.5
55.2
44.9
34.6
73.0
66.4
56.1
45.8
73.5
67.3
57.0
46.7
44.6
33.0
57.9
46.3
34.7
71.3
59.7
48.1
36.5
76.0
71.8
60.2
48.6
76.3
72.8
61.2
49.6
62.8
49.8
36.9
76.3
64.2
51.3
38.3
76.6
74.6
61.6
48.7
77.0
75.2
62.3
49.3
65
37.4
40.0
42.3
42.7
45.1
45.3
48.0
47.1
48.1
48.9
48.2
32.5
34.0
34.8
35.5
36.4
37.0
38.0
35.7
36.3
15
5167825-BTG-F-0217
XA-06 (6.5 Ton) (Continued)
Air on
Evaporator Coil
CFM
WB
(°F)
Total
Capacity1
(MBh)
Total
Input
(kW)2
3250
72
67
62
57
101.9
91.9
84.7
83.5
6.1
6.1
6.0
6.0
16
90
85.7
91.9
84.7
83.5
Temperature of Air on Condenser Coil
Sensible Capacity (MBh)
Total
Total
Return Dry Bulb (°F)
Input
Capacity1
(MBh)
(kW)2
85
80
75
70
65
71.4
57.2
43.0
93.7
6.9
86.5
72.3
58.1
43.9
84.0
6.9
84.7
84.7
70.5
56.2
42.0
77.3
6.9
83.5
83.5
69.3
55.1
40.8
77.7
6.9
90
81.9
84.0
77.3
77.7
Sensible Capacity (MBh)
Return Dry Bulb (°F)
85
80
75
70
67.6
53.3
39.0
81.4
68.7
54.4
40.1
77.3
77.3
63.0
48.7
77.7
77.7
63.3
49.0
65
34.4
34.7
Johnson Controls Unitary Products
5167825-BTG-F-0217
XA-06 (6.5 Ton) (Continued)
Air on
Evaporator Coil
CFM
1625
1950
2275
2600
2925
3250
WB
(°F)
Total
Capacity1
(MBh)
Total
Input
(kW)2
90
77
72
67
62
77
72
67
62
57
77
72
67
62
57
77
72
67
62
57
72
67
62
57
72
67
62
57
86.5
77.9
69.4
63.7
88.8
80.0
71.2
65.4
67.1
91.1
82.1
73.1
67.1
68.9
93.4
84.2
74.9
68.8
70.6
84.9
75.6
69.4
71.2
85.6
76.2
69.9
71.8
7.8
7.8
7.8
7.8
7.8
7.8
7.8
7.8
7.7
7.8
7.8
7.8
7.8
7.7
7.8
7.8
7.8
7.8
7.7
7.8
7.8
7.8
7.7
7.8
7.8
7.8
7.7
35.6
48.0
60.5
63.7
42.4
53.8
65.3
65.4
67.1
49.3
59.7
70.1
67.1
68.9
56.1
65.5
74.9
68.8
70.6
71.9
75.6
69.4
71.2
78.2
76.2
69.9
71.8
Temperature of Air on Condenser Coil
Sensible Capacity (MBh)
Total
Total
Return Dry Bulb (°F)
Input
Capacity1
(MBh)
(kW)2
85
80
75
70
65
115°F
29.9
22.2
80.1
8.7
40.3
32.6
24.9
71.7
8.6
50.7
43.0
35.3
27.6
63.3
8.6
62.9
50.7
43.0
35.3
27.6
58.0
8.6
33.5
24.6
81.8
8.7
44.9
36.0
27.1
73.2
8.6
56.4
47.4
38.5
29.6
64.6
8.6
64.9
55.9
47.0
38.1
29.2
59.2
8.6
65.5
56.5
47.6
38.7
29.8
62.4
8.5
37.0
26.9
83.5
8.6
49.5
39.4
29.2
74.7
8.6
62.0
51.9
41.7
31.6
65.9
8.6
66.8
61.2
51.0
40.9
30.7
60.4
8.6
68.1
61.9
51.7
41.5
31.4
63.7
8.5
40.5
29.2
85.2
8.6
54.1
42.8
31.4
76.2
8.6
67.7
56.3
45.0
33.6
67.3
8.6
68.8
66.5
55.1
43.7
32.3
61.6
8.6
70.6
67.2
55.8
44.4
33.0
65.0
8.5
59.0
46.1
33.2
76.8
8.6
72.0
60.7
47.8
35.0
67.8
8.6
69.4
68.2
55.3
42.4
29.5
62.1
8.6
71.2
69.5
56.6
43.7
30.8
65.5
8.5
63.8
49.4
35.0
77.4
8.6
76.2
65.1
50.7
36.3
68.3
8.6
69.9
69.9
55.5
41.1
26.7
62.6
8.6
71.8
71.8
57.4
43.0
28.6
66.0
8.5
90
30.4
44.8
58.3
58.0
38.8
50.4
61.9
59.2
62.4
47.3
55.9
65.5
60.4
63.7
55.7
61.5
67.3
61.6
65.0
68.0
67.8
62.1
65.5
74.5
68.3
62.6
66.0
Sensible Capacity (MBh)
Return Dry Bulb (°F)
85
80
75
70
125°F
26.7
19.0
37.1
29.4
21.7
47.5
39.8
32.1
24.4
58.0
45.8
38.1
30.4
30.0
21.1
41.5
32.6
23.8
53.0
44.2
35.3
26.5
59.2
50.9
42.0
33.2
60.2
51.3
42.5
33.6
33.3
23.2
45.9
35.9
25.9
58.6
48.6
38.6
28.6
60.4
56.0
46.0
36.0
62.6
56.5
46.4
36.4
36.5
25.4
50.3
39.2
28.0
64.1
53.0
41.8
30.7
61.6
61.1
49.9
38.8
65.0
61.6
50.4
39.3
55.2
42.4
29.5
67.6
57.3
44.4
31.6
62.1
61.8
49.0
36.2
65.5
63.8
51.0
38.1
60.0
45.5
31.0
68.3
61.5
47.0
32.5
62.6
62.6
48.1
33.6
66.0
66.0
51.5
37.0
65
22.7
24.3
24.7
26.0
26.4
27.6
28.1
23.3
25.3
19.1
22.5
1. These capacities are gross ratings. For net capacity, deduct air blower motor, MBh = 3.415 x kW. Refer to the appropriate Blower
Performance Table for the kW of the supply air blower motor.
2. These ratings include the condenser fan motors (total 1 kW) and the compressor motors but not the supply air blower motor.
Johnson Controls Unitary Products
17
5167825-BTG-F-0217
XA-07 (7.5 Ton)
Air on
Evaporator Coil
CFM
1875
2250
2625
3000
3375
3750
1875
2250
2625
3000
3375
3750
18
WB
(°F)
Total
Capacity1
(MBh)
Total
Input
(kW)2
90
77
72
67
62
77
72
67
62
57
77
72
67
62
57
77
72
67
62
57
72
67
62
57
72
67
62
57
116.6
107.8
99.0
93.7
120.7
111.7
102.6
97.0
93.4
124.9
115.5
106.1
100.3
96.6
129.1
119.4
109.6
103.7
99.8
120.8
111.0
104.9
101.1
122.3
112.3
106.2
102.3
5.8
5.7
5.6
5.5
5.8
5.7
5.6
5.6
5.6
5.8
5.7
5.6
5.6
5.6
5.8
5.7
5.6
5.6
5.6
5.7
5.7
5.6
5.6
5.7
5.7
5.6
5.6
48.6
62.9
77.2
93.7
53.8
69.3
84.8
97.0
93.4
59.0
75.7
92.4
100.3
96.6
64.1
82.1
100.0
103.7
99.8
87.0
106.1
104.9
101.1
91.9
112.3
106.2
102.3
77
72
67
62
77
72
67
62
57
77
72
67
62
57
77
72
67
62
57
72
67
62
57
72
67
62
57
103.4
95.0
86.6
79.0
106.3
97.7
89.0
81.3
81.1
109.3
100.4
91.5
83.6
83.4
112.2
103.1
94.0
85.8
85.6
103.5
94.4
86.2
86.0
104.0
94.8
86.5
86.3
7.3
7.2
7.2
7.1
7.3
7.3
7.2
7.1
7.1
7.4
7.3
7.2
7.1
7.1
7.4
7.3
7.2
7.2
7.2
7.3
7.3
7.2
7.2
7.3
7.3
7.2
7.2
43.0
56.8
70.5
79.0
47.7
62.6
77.6
81.3
81.1
52.3
68.4
84.6
83.6
83.4
56.9
74.3
91.6
85.8
85.6
79.7
93.2
86.2
86.0
85.2
94.8
86.5
86.3
Temperature of Air on Condenser Coil
Sensible Capacity (MBh)
Total
Total
Return Dry Bulb (°F)
Capacity1
Input
(MBh)
(kW)2
85
80
75
70
65
75°F
40.0
31.5
110.0
6.5
54.3
45.7
37.2
101.4
6.5
68.6
60.0
51.5
42.9
92.8
6.4
85.2
74.6
66.1
57.5
48.9
86.4
6.3
44.0
34.1
113.5
6.5
59.5
49.6
39.8
104.7
6.5
75.0
65.1
55.3
45.5
95.8
6.4
91.3
81.0
71.2
61.4
51.5
89.2
6.3
93.4
85.1
75.3
65.4
55.6
87.2
6.3
47.9
36.8
117.1
6.6
64.6
53.5
42.5
108.0
6.5
81.3
70.2
59.2
48.1
98.8
6.4
97.5
87.3
76.3
65.2
54.1
92.0
6.4
96.6
91.8
80.7
69.6
58.6
90.0
6.4
51.8
39.5
120.7
6.6
69.7
57.4
45.1
111.2
6.5
87.7
75.4
63.0
50.7
101.8
6.4
103.7 93.7
81.4
69.1
56.7
94.8
6.4
99.8
98.4
86.1
73.8
61.5
92.7
6.4
73.9
60.7
47.6
112.2
6.5
92.8
79.6
66.5
53.3
102.7
6.5
104.9 99.9
86.8
73.6
60.5
95.6
6.4
101.1 100.4 87.2
74.1
60.9
93.5
6.4
78.0
64.0
50.0
113.1
6.5
97.9
83.9
69.9
55.9
103.5
6.5
106.2 106.2 92.2
78.2
64.2
96.4
6.4
102.3 102.3 88.3
74.3
60.3
94.3
6.4
95°F
34.8
26.5
95.4
8.2
48.5
40.3
32.0
87.7
8.1
62.3
54.0
45.8
37.5
79.9
8.1
79.0
66.6
58.4
50.1
41.9
74.0
8.0
38.2
28.8
97.6
8.2
53.2
43.8
34.4
89.7
8.2
68.1
58.7
49.3
39.9
81.8
8.1
81.3
72.4
63.0
53.6
44.2
75.7
8.0
81.1
74.8
65.4
56.0
46.6
75.4
8.0
41.7
31.1
99.9
8.3
57.9
47.3
36.7
91.8
8.2
74.0
63.4
52.8
42.2
83.7
8.1
83.6
78.2
67.6
57.0
46.5
77.5
8.1
83.4
80.8
70.2
59.6
49.0
77.1
8.1
45.2
33.4
102.1
8.3
62.5
50.8
39.0
93.8
8.2
79.9
68.1
56.3
44.6
85.6
8.1
85.8
84.0
72.2
60.5
48.7
79.2
8.1
85.6
86.8
75.0
63.3
51.5
78.8
8.1
67.0
54.2
41.4
93.9
8.2
85.5
72.7
59.9
47.2
85.6
8.2
86.2
85.3
72.5
59.7
47.0
79.3
8.1
86.0
86.5
73.8
61.0
48.2
78.9
8.1
71.4
57.6
43.8
94.0
8.3
91.1
77.3
63.5
49.7
85.7
8.2
86.5
86.5
72.8
59.0
45.2
79.4
8.1
86.3
86.3
72.5
58.7
45.0
79.0
8.1
90
45.8
59.8
73.8
86.4
50.7
65.9
81.2
89.2
87.2
55.6
72.1
88.5
92.0
90.0
60.5
78.2
95.8
94.8
92.7
83.4
99.7
95.6
93.5
88.6
103.5
96.4
94.3
37.5
53.1
68.7
74.0
43.7
58.8
73.9
75.7
75.4
49.8
64.5
79.2
77.5
77.1
56.0
70.2
84.4
79.2
78.8
75.2
85.1
79.3
78.9
80.1
85.7
79.4
79.0
Sensible Capacity (MBh)
Return Dry Bulb (°F)
85
80
75
70
85°F
37.4
29.0
51.4
43.0
34.6
65.4
57.0
48.6
40.2
82.1
70.6
62.2
53.8
41.1
31.5
56.3
46.7
37.1
71.5
61.9
52.3
42.7
86.3
76.7
67.1
57.5
87.2
80.0
70.3
60.7
44.8
34.0
61.2
50.4
39.6
77.7
66.8
56.0
45.2
90.5
82.8
72.0
61.1
90.0
86.3
75.5
64.6
48.5
36.5
66.1
54.1
42.1
83.8
71.7
59.7
47.7
94.8
88.8
76.8
64.8
92.7
92.6
80.6
68.5
70.4
57.4
44.5
89.1
76.2
63.2
50.2
95.6
92.6
79.6
66.7
93.5
93.4
80.5
67.5
74.7
60.8
46.9
94.5
80.6
66.7
52.8
96.4
96.4
82.5
68.6
94.3
94.3
80.4
66.5
105°F
31.2
23.2
45.1
37.0
29.0
58.9
50.9
42.9
34.8
74.0
62.0
54.0
45.9
34.5
25.3
49.6
40.4
31.2
64.7
55.5
46.3
37.1
75.7
67.6
58.4
49.2
75.4
69.1
59.9
50.7
37.7
27.4
54.1
43.8
33.4
70.5
60.2
49.8
39.4
77.5
73.3
62.9
52.5
77.1
74.8
64.5
54.1
41.0
29.5
58.7
47.1
35.6
76.3
64.8
53.3
41.7
79.2
78.9
67.4
55.8
78.8
80.6
69.1
57.5
62.7
50.2
37.7
80.1
69.0
56.5
44.1
79.3
79.1
66.7
54.2
78.9
79.8
67.3
54.8
66.7
53.3
39.8
83.9
73.2
59.8
46.4
79.4
79.4
65.9
52.5
79.0
79.0
65.6
52.1
65
45.4
47.9
51.1
50.3
53.8
52.7
56.5
53.7
54.6
54.7
52.6
37.9
40.0
41.5
42.2
43.7
44.3
46.0
41.7
42.3
39.1
38.7
Johnson Controls Unitary Products
5167825-BTG-F-0217
XA-07 (7.5 Ton) (Continued)
Air on
Evaporator Coil
CFM
1875
2250
2625
3000
3375
3750
WB
(°F)
Total
Capacity1
(MBh)
Total
Input
(kW)2
90
77
72
67
62
77
72
67
62
57
77
72
67
62
57
77
72
67
62
57
72
67
62
57
72
67
62
57
87.4
80.3
73.3
68.9
89.0
81.7
74.5
70.1
69.6
90.5
83.2
75.8
71.3
70.8
92.0
84.6
77.1
72.5
72.0
84.3
76.9
72.4
71.8
84.1
76.7
72.2
71.7
9.1
9.1
9.0
8.9
9.2
9.1
9.0
9.0
9.0
9.2
9.1
9.0
9.0
9.0
9.2
9.1
9.1
9.0
9.0
9.2
9.1
9.0
9.0
9.2
9.1
9.1
9.0
32.0
49.4
66.9
68.9
39.7
55.0
70.3
70.1
69.6
47.4
60.6
73.7
71.3
70.8
55.1
66.1
77.1
72.5
72.0
70.6
76.9
72.4
71.8
75.1
76.7
72.2
71.7
Temperature of Air on Condenser Coil
Sensible Capacity (MBh)
Total
Total
Return Dry Bulb (°F)
Input
Capacity1
(MBh)
(kW)2
85
80
75
70
65
115°F
27.6
19.8
79.5
10.1
41.6
33.8
26.0
73.0
10.0
55.6
47.8
40.0
32.2
66.6
9.9
68.9
57.4
49.6
41.7
33.9
63.9
9.9
30.7
21.7
80.3
10.1
46.0
37.0
28.1
73.8
10.0
61.3
52.4
43.4
34.4
67.3
9.9
70.1
62.9
53.9
44.9
35.9
64.5
9.9
69.6
63.3
54.4
45.4
36.4
63.9
9.9
33.7
23.6
81.1
10.1
50.4
40.3
30.1
74.5
10.0
67.1
56.9
46.8
36.6
68.0
9.9
71.3
68.3
58.2
48.1
37.9
65.2
9.9
70.8
68.9
58.7
48.6
38.4
64.6
9.9
36.8
25.5
81.9
10.1
54.8
43.5
32.2
75.3
10.1
72.8
61.5
50.2
38.9
68.7
10.0
72.5
73.8
62.5
51.2
39.9
65.9
9.9
72.0
74.4
63.1
51.8
40.5
65.2
9.9
58.4
46.2
34.0
74.8
10.1
74.8
65.3
53.1
41.0
68.2
10.0
72.4
73.0
60.8
48.6
36.4
65.4
10.0
71.8
73.0
60.8
48.7
36.5
64.8
10.0
62.0
48.9
35.9
74.2
10.1
76.7
69.2
56.1
43.0
67.7
10.0
72.2
72.2
59.1
46.0
33.0
65.0
10.0
71.7
71.7
58.6
45.5
32.5
64.3
10.0
90
25.8
45.8
65.4
63.9
35.7
51.2
66.7
64.5
63.9
45.5
56.6
68.0
65.2
64.6
55.4
62.0
68.7
65.9
65.2
66.0
68.2
65.4
64.8
70.0
67.7
65.0
64.3
Sensible Capacity (MBh)
Return Dry Bulb (°F)
85
80
75
70
125°F
23.8
16.5
38.2
30.6
23.0
52.3
44.7
37.1
29.5
63.9
52.7
45.1
37.5
26.9
18.1
42.4
33.7
24.9
57.9
49.2
40.4
31.7
64.5
58.1
49.3
40.6
63.9
57.6
48.8
40.1
30.1
19.8
46.7
36.8
26.8
63.6
53.7
43.8
33.8
65.2
63.4
53.5
43.6
64.6
62.9
53.0
43.0
33.2
21.5
50.9
39.9
28.8
68.7
58.2
47.1
36.0
65.9
65.9
57.6
46.6
65.2
65.2
57.1
46.0
54.1
42.2
30.3
68.2
61.6
49.8
37.9
65.4
65.4
55.0
43.1
64.8
64.8
54.4
42.5
57.3
44.6
31.9
67.7
65.1
52.4
39.7
65.0
65.0
52.3
39.6
64.3
64.3
51.6
38.9
65
29.9
31.8
31.3
33.6
33.1
35.5
34.9
31.2
30.6
26.9
26.2
1. These capacities are gross ratings. For net capacity, deduct air blower motor, MBh = 3.415 x kW. Refer to the appropriate Blower
Performance Table for the kW of the supply air blower motor.
2. These ratings include the condenser fan motors (total 1 kW) and the compressor motors but not the supply air blower motor.
Johnson Controls Unitary Products
19
5167825-BTG-F-0217
XA-08 (8.5 Ton)
Air on
Evaporator Coil
CFM
2125
2550
2975
3400
3825
4250
2125
2550
2975
3400
3825
4250
20
WB
(°F)
Total
Capacity1
(MBh)
Total
Input
(kW)2
90
77
72
67
62
77
72
67
62
57
77
72
67
62
57
77
72
67
62
57
72
67
62
57
72
67
62
57
120.9
113.7
106.4
96.7
126.2
118.6
110.9
100.9
100.3
131.4
123.5
115.5
105.1
104.4
136.7
128.4
120.1
109.3
108.6
132.2
123.6
112.5
111.8
136.0
127.2
115.7
115.0
6.2
6.1
6.0
5.9
6.2
6.1
6.0
6.0
5.9
6.2
6.1
6.0
6.0
6.0
6.2
6.1
6.0
6.0
6.0
6.2
6.1
6.0
6.0
6.3
6.2
6.1
6.1
58.3
69.9
81.4
96.7
62.1
78.1
94.1
100.9
100.3
65.9
86.3
106.8
105.1
104.4
69.7
94.6
119.5
109.3
108.6
101.6
123.3
112.5
111.8
108.6
127.2
115.7
115.0
77
72
67
62
77
72
67
62
57
77
72
67
62
57
77
72
67
62
57
72
67
62
57
72
67
62
57
116.2
105.1
94.0
87.9
120.4
108.9
97.4
91.1
91.1
124.5
112.6
100.7
94.2
94.2
128.7
116.4
104.1
97.4
97.4
118.8
106.3
99.4
99.4
121.3
108.4
101.4
101.4
7.8
7.8
7.8
7.7
7.8
7.8
7.8
7.7
7.7
7.9
7.9
7.8
7.7
7.7
7.9
7.9
7.9
7.8
7.8
7.9
7.9
7.8
7.8
7.9
7.9
7.8
7.8
46.9
64.7
82.5
87.9
56.5
73.1
89.7
91.1
91.1
66.1
81.5
96.9
94.2
94.2
75.7
89.9
104.1
97.4
97.4
96.9
106.3
99.4
99.4
103.9
108.4
101.4
101.4
Temperature of Air on Condenser Coil
Sensible Capacity (MBh)
Total
Total
Return Dry Bulb (°F)
Capacity1
Input
(MBh)
(kW)2
85
80
75
70
65
75°F
45.7
36.0
118.6
7.0
60.2
50.5
40.8
109.4
6.9
74.6
65.0
55.3
45.6
100.2
6.9
94.3
79.3
69.6
59.9
50.2
92.3
6.8
51.0
39.8
123.3
7.0
67.0
55.8
44.7
113.7
7.0
83.0
71.8
60.7
49.5
104.2
6.9
99.3
87.7
76.5
65.4
54.3
96.0
6.8
100.5 89.7
78.6
67.5
56.3
95.7
6.8
56.2
43.6
128.0
7.0
73.7
61.2
48.6
118.1
7.0
91.3
78.7
66.1
53.5
108.1
6.9
104.3 96.1
83.5
70.9
58.3
99.6
6.9
104.6 98.3
85.8
73.2
60.6
99.3
6.9
61.5
47.5
132.7
7.1
80.5
66.5
52.5
122.4
7.0
99.6
85.6
71.5
57.5
112.1
7.0
109.3 104.5 90.4
76.4
62.4
103.3
6.9
108.6 106.9 92.9
78.9
64.9
103.0
6.9
86.1
70.7
55.3
125.5
7.1
106.7 91.0
75.5
60.1
115.0
7.0
112.5 110.1 94.7
79.2
63.8
105.9
6.9
111.8 111.0 95.5
80.1
64.7
105.6
6.9
91.8
74.9
58.1
128.6
7.1
113.8 96.4
79.5
62.7
117.8
7.0
115.7 115.7 98.9
82.1
65.2
108.6
7.0
115.0 115.0 98.2
81.4
64.5
108.2
7.0
95°F
39.8
29.8
107.5
8.9
54.7
44.7
34.7
97.2
8.8
69.6
59.6
49.5
39.5
86.8
8.8
87.9
71.6
61.6
51.5
41.5
80.7
8.7
44.9
33.3
111.4
8.9
61.5
49.9
38.3
100.6
8.9
78.1
66.5
54.9
43.3
89.9
8.8
91.1
79.9
68.3
56.7
45.1
83.5
8.7
90.8
79.2
67.6
56.0
44.4
85.1
8.8
50.0
36.8
115.2
9.0
68.3
55.1
41.9
104.0
8.9
86.6
73.4
60.2
47.0
92.9
8.9
94.2
88.2
75.0
61.8
48.6
86.4
8.8
94.1
87.5
74.3
61.0
47.8
88.0
8.8
55.0
40.2
119.0
9.0
75.1
60.3
45.5
107.5
9.0
95.2
80.4
65.6
50.8
96.0
8.9
97.4
96.6
81.8
67.0
52.2
89.2
8.8
97.4
95.7
80.9
66.1
51.3
90.9
8.8
80.7
64.4
48.2
109.5
9.0
101.8 85.9
69.7
53.4
97.8
8.9
99.4
99.0
82.8
66.5
50.3
90.9
8.8
99.4
98.6
82.3
66.1
49.9
92.6
8.8
86.2
68.6
50.9
111.6
9.0
108.4 91.4
73.8
56.1
99.7
8.9
101.4 101.4 83.8
66.1
48.4
92.6
8.9
101.4 101.4 83.8
66.1
48.5
94.4
8.9
90
52.6
67.3
82.0
92.3
59.3
75.6
91.9
96.0
95.7
66.0
83.9
101.8
99.6
99.3
72.7
92.2
111.8
103.3
103.0
99.2
114.8
105.9
105.6
106.2
117.8
108.6
108.2
44.1
62.6
81.1
80.7
56.2
71.1
86.0
83.5
85.1
68.4
79.7
91.0
86.4
88.0
80.5
88.3
96.0
89.2
90.9
95.4
97.8
90.9
92.6
102.5
99.7
92.6
94.4
Sensible Capacity (MBh)
Return Dry Bulb (°F)
85
80
75
70
85°F
42.8
32.9
57.4
47.6
37.7
72.1
62.3
52.4
42.5
91.1
75.4
65.6
55.7
47.9
36.6
64.2
52.9
41.5
80.5
69.2
57.8
46.4
95.2
83.8
72.4
61.0
95.7
84.5
73.1
61.7
53.1
40.2
71.0
58.1
45.2
89.0
76.1
63.2
50.3
99.2
92.2
79.3
66.4
99.3
92.9
80.0
67.1
58.3
43.8
77.8
63.4
49.0
97.4
83.0
68.5
54.1
103.3 100.5 86.1
71.7
103.0 101.3 86.9
72.5
83.4
67.6
51.8
104.3 88.4
72.6
56.8
105.9 104.5 88.7
72.9
105.6 104.8 88.9
73.1
89.0
71.8
54.5
111.1 93.9
76.7
59.4
108.6 108.6 91.3
74.1
108.2 108.2 91.0
73.7
105°F
37.9
28.3
52.5
42.4
32.3
67.1
56.5
46.4
36.3
80.7
68.6
58.5
48.4
43.5
31.8
59.4
47.6
35.9
75.2
63.5
51.7
40.0
83.5
77.0
65.3
53.5
85.0
73.3
61.6
49.8
49.2
35.3
66.3
52.9
39.4
83.4
70.4
57.0
43.6
86.4
85.5
72.1
58.7
87.9
81.4
67.9
54.5
54.8
38.8
73.2
58.1
43.0
91.5
77.4
62.3
47.2
89.2
93.9
78.9
63.8
90.9
89.4
74.3
59.2
78.8
62.2
45.6
95.6
82.9
66.3
49.7
90.9
93.3
76.7
60.1
92.6
91.9
75.3
58.7
84.4
66.3
48.2
99.7
88.4
70.3
52.2
92.6
92.6
74.6
56.5
94.4
94.4
76.3
58.2
65
45.9
49.7
50.3
53.5
54.2
57.3
58.1
57.1
57.3
56.8
56.5
38.3
41.8
38.1
45.2
41.1
48.7
44.1
43.5
42.1
38.4
40.1
Johnson Controls Unitary Products
5167825-BTG-F-0217
XA-08 (8.5 Ton) (Continued)
Air on
Evaporator Coil
CFM
2125
2550
2975
3400
3825
4250
WB
(°F)
Total
Capacity1
(MBh)
Total
Input
(kW)2
90
77
72
67
62
77
72
67
62
57
77
72
67
62
57
77
72
67
62
57
72
67
62
57
72
67
62
57
98.9
89.2
79.6
73.4
102.3
92.4
82.4
76.0
79.1
105.8
95.5
85.1
78.5
81.8
109.2
98.6
87.9
81.1
84.4
100.3
89.4
82.5
85.9
101.9
90.9
83.9
87.3
10.0
9.9
9.8
9.7
10.0
9.9
9.8
9.8
9.8
10.1
10.0
9.9
9.8
9.8
10.1
10.0
9.9
9.8
9.9
10.0
9.9
9.9
9.9
10.1
10.0
9.9
9.9
41.2
60.4
79.6
73.4
55.9
69.1
82.4
76.0
79.1
70.7
77.9
85.1
78.5
81.8
85.4
86.6
87.9
81.1
84.4
93.9
89.4
82.5
85.9
101.1
90.9
83.9
87.3
Temperature of Air on Condenser Coil
Sensible Capacity (MBh)
Total
Total
Return Dry Bulb (°F)
Input
Capacity1
(MBh)
(kW)2
85
80
75
70
65
115°F
36.0
26.8
90.2
11.1
50.3
40.1
30.0
81.3
11.0
64.5
53.4
43.3
33.2
72.4
10.9
73.4
65.6
55.4
45.3
35.2
66.2
10.8
42.2
30.3
93.3
11.1
57.3
45.4
33.5
84.1
11.0
72.3
60.5
48.6
36.7
74.9
10.9
76.0
74.1
62.3
50.4
38.5
68.5
10.8
79.1
67.5
55.6
43.7
31.8
73.1
10.8
48.4
33.8
96.4
11.2
64.3
50.6
37.0
86.9
11.0
80.1
67.5
53.8
40.2
77.3
10.9
78.5
82.7
69.1
55.5
41.8
70.7
10.8
81.8
75.3
61.6
48.0
34.4
75.6
10.9
54.6
37.3
99.5
11.2
71.3
55.9
40.5
89.7
11.1
87.9
74.5
59.1
43.7
79.8
10.9
81.1
91.3
75.9
60.6
45.2
73.0
10.9
84.4
83.1
67.7
52.3
37.0
78.0
10.9
76.9
60.0
43.0
91.0
11.1
89.4
79.9
63.0
46.0
81.0
11.0
82.5
87.6
70.7
53.7
36.8
74.0
10.9
85.9
85.2
68.3
51.3
34.4
79.1
10.9
82.6
64.1
45.6
92.3
11.1
90.9
85.4
66.8
48.3
82.1
11.0
83.9
83.9
65.4
46.8
28.3
75.1
10.9
87.3
87.3
68.8
50.3
31.8
80.3
11.0
90
44.1
58.2
72.4
66.2
59.4
67.2
74.9
68.5
73.1
74.8
76.1
77.3
70.7
75.6
90.2
85.0
79.8
73.0
78.0
91.0
81.0
74.0
79.1
92.3
82.1
75.1
80.3
Sensible Capacity (MBh)
Return Dry Bulb (°F)
85
80
75
70
125°F
31.8
25.3
48.0
37.8
27.6
62.0
50.4
40.2
30.0
66.2
66.2
52.3
42.2
40.8
28.8
55.1
43.1
31.1
69.4
57.4
45.4
33.4
68.5
68.5
59.2
47.2
73.1
61.6
49.6
37.6
49.9
32.3
62.2
48.4
34.6
76.9
64.5
50.6
36.8
70.7
70.7
66.1
52.3
75.6
69.2
55.3
41.5
58.9
35.9
69.4
53.7
38.0
79.8
71.5
55.8
40.2
73.0
73.0
73.0
57.4
78.0
76.8
61.1
45.5
75.1
57.8
40.5
81.0
76.9
59.6
42.3
74.0
74.0
64.6
47.3
79.1
78.5
61.2
43.9
80.8
61.8
42.9
82.1
82.1
63.4
44.4
75.1
75.1
56.2
37.2
80.3
80.3
61.3
42.4
65
32.0
35.2
25.5
38.5
27.7
41.7
29.8
30.0
26.6
18.3
23.4
1. These capacities are gross ratings. For net capacity, deduct air blower motor, MBh = 3.415 x kW. Refer to the appropriate Blower
Performance Table for the kW of the supply air blower motor.
2. These ratings include the condenser fan motors (total 1 kW) and the compressor motors but not the supply air blower motor.
Johnson Controls Unitary Products
21
5167825-BTG-F-0217
XA-10 (10 Ton)
Air on
Evaporator Coil
CFM
2500
3000
3500
4000
4500
5000
2500
3000
3500
4000
4500
5000
22
WB
(°F)
Total
Capacity1
(MBh)
Total
Input
(kW)2
90
77
72
67
62
77
72
67
62
57
77
72
67
62
57
77
72
67
62
57
72
67
62
57
72
67
62
57
143.9
137.2
130.5
121.6
147.9
141.0
134.1
124.9
127.2
151.8
144.7
137.7
128.2
130.6
155.8
148.5
141.3
131.6
134.0
144.4
137.4
128.0
130.4
140.3
133.5
124.4
126.7
7.2
7.0
6.9
6.9
7.2
7.0
6.9
6.9
6.8
7.2
7.0
6.9
6.9
6.8
7.2
7.1
6.9
6.9
6.8
7.1
7.0
7.0
6.9
7.2
7.1
7.0
7.0
59.2
79.6
100.1
121.6
65.7
88.3
110.9
124.9
127.2
72.3
97.0
121.7
128.2
130.6
78.9
105.7
132.5
131.6
134.0
107.3
133.0
128.0
130.4
109.0
133.5
124.4
126.7
77
72
67
62
77
72
67
62
57
77
72
67
62
57
77
72
67
62
57
72
67
62
57
72
67
62
57
130.2
121.9
113.6
106.1
133.6
125.1
116.5
108.8
112.8
137.0
128.2
119.4
111.6
115.7
140.4
131.4
122.4
114.3
118.5
128.7
119.9
112.0
116.1
126.1
117.4
109.7
113.7
9.3
9.1
8.9
8.9
9.4
9.2
9.0
8.9
8.9
9.4
9.2
9.0
8.9
8.9
9.4
9.2
9.0
9.0
8.9
9.3
9.0
9.0
8.9
9.3
9.1
9.0
9.0
62.5
78.8
95.1
106.1
68.9
86.2
103.6
108.8
112.8
75.2
93.6
112.0
111.6
115.7
81.6
101.0
120.5
114.3
118.5
108.2
118.9
112.0
116.1
115.3
117.4
109.7
113.7
Temperature of Air on Condenser Coil
Sensible Capacity (MBh)
Total
Total
Return Dry Bulb (°F)
Capacity1
Input
(MBh)
(kW)2
85
80
75
70
65
75°F
48.0
36.8
137.1
8.3
68.4
57.3
46.1
129.6
8.1
88.9
77.7
66.6
55.4
122.0
7.9
112.1 92.0
80.8
69.7
58.5
113.8
7.9
53.3
40.8
140.7
8.3
75.9
63.4
51.0
133.0
8.1
98.4
86.0
73.5
61.1
125.3
7.9
118.6 101.9 89.5
77.0
64.6
116.9
7.9
117.6 105.2 92.7
80.3
67.8
120.0
7.8
58.6
44.9
144.4
8.3
83.3
69.6
55.8
136.5
8.1
108.0 94.2
80.5
66.8
128.6
7.9
125.1 111.8 98.1
84.4
70.6
119.9
7.9
125.8 115.3 101.6 87.8
74.1
123.2
7.8
63.9
48.9
148.1
8.3
90.7
75.7
60.7
139.9
8.1
117.5 102.5 87.5
72.5
131.8
8.0
131.6 121.7 106.7 91.7
76.7
123.0
7.9
134.0 125.4 110.4 95.4
80.4
126.3
7.9
92.1
76.8
61.5
136.6
8.2
120.4 104.1 88.8
73.5
128.7
8.0
128.0 123.0 107.8 92.5
77.2
120.0
8.0
130.4 126.0 110.7 95.5
80.2
123.3
7.9
93.4
77.8
62.3
133.2
8.3
123.4 105.7 90.1
74.5
125.5
8.1
124.4 124.4 108.8 93.2
77.6
117.0
8.0
126.7 126.7 111.1 95.5
79.9
120.2
8.0
95°F
51.8
41.1
119.6
10.6
68.1
57.4
46.7
112.1
10.4
84.4
73.7
63.0
52.2
104.5
10.2
106.1 94.4
83.7
73.0
62.3
97.9
10.1
56.3
43.7
122.6
10.6
73.6
61.1
48.5
114.9
10.4
91.0
78.4
65.8
53.3
107.1
10.2
108.8 100.5 87.9
75.3
62.8
100.3
10.1
110.9 98.4
85.8
73.2
60.6
105.1
10.2
60.8
46.4
125.6
10.6
79.2
64.8
50.3
117.7
10.4
97.6
83.1
68.7
54.3
109.7
10.2
111.6 106.6 92.1
77.7
63.3
102.8
10.1
114.7 104.3 89.9
75.4
61.0
107.7
10.2
65.3
49.0
128.6
10.6
84.7
68.4
52.2
120.5
10.4
104.2 87.9
71.6
55.3
112.4
10.2
114.3 112.6 96.3
80.0
63.8
105.2
10.2
118.5 110.3 94.0
77.7
61.4
110.2
10.2
90.9
73.7
56.5
117.9
10.5
110.8 94.6
77.4
60.1
110.0
10.3
112.0 111.2 93.9
76.7
59.5
103.0
10.2
116.1 112.0 94.8
77.5
60.3
107.9
10.2
97.1
78.9
60.8
115.3
10.5
117.4 101.3 83.2
65.0
107.5
10.3
109.7 109.7 91.5
73.3
55.2
100.7
10.2
113.7 113.7 95.6
77.4
59.2
105.5
10.2
90
60.8
79.2
97.6
113.8
67.3
87.3
107.2
116.9
120.0
73.8
95.3
116.9
119.9
123.2
80.3
103.4
126.5
123.0
126.3
107.8
126.0
120.0
123.3
112.1
125.5
117.0
120.2
53.1
73.0
92.9
97.9
63.1
81.1
99.0
100.3
105.1
73.2
89.2
105.2
102.8
107.7
83.3
97.3
111.4
105.2
110.2
103.1
109.5
103.0
107.9
108.8
107.5
100.7
105.5
Sensible Capacity (MBh)
Return Dry Bulb (°F)
85
80
75
70
85°F
49.9
38.9
68.3
57.3
46.4
86.7
75.7
64.8
53.8
109.1 93.2
82.3
71.3
54.8
42.3
74.8
62.2
49.7
94.7
82.2
69.7
57.2
113.7 101.2 88.7
76.2
114.3 101.8 89.2
76.7
59.7
45.6
81.2
67.2
53.1
102.8 88.7
74.6
60.5
118.3 109.2 95.1
81.0
120.3 109.8 95.7
81.6
64.6
49.0
87.7
72.1
56.4
110.8 95.2
79.5
63.9
123.0 117.2 101.5 85.9
126.3 117.8 102.2 86.5
91.5
75.2
59.0
115.6 99.3
83.1
66.8
120.0 117.1 100.8 84.6
123.3 119.0 102.8 86.5
95.3
78.4
61.5
120.4 103.5 86.6
69.8
117.0 117.0 100.2 83.3
120.2 120.2 103.3 86.4
105°F
45.8
35.3
62.4
51.9
41.3
79.0
68.5
57.9
47.4
97.9
84.3
73.7
63.2
50.6
38.0
68.5
56.0
43.5
86.5
73.9
61.4
48.9
100.3 91.0
78.4
65.9
101.5 88.9
76.4
63.8
55.4
40.8
74.7
60.1
45.6
94.0
79.4
64.9
50.4
102.8 97.7
83.1
68.6
105.9 95.5
80.9
66.4
60.1
43.6
80.8
64.3
47.7
101.5 84.9
68.4
51.8
105.2 104.3 87.8
71.3
110.2 102.0 85.5
68.9
85.7
68.4
51.0
104.5 90.3
73.0
55.7
103.0 102.5 85.2
67.8
107.9 103.8 86.4
69.1
90.6
72.5
54.4
107.5 95.7
77.6
59.5
100.7 100.7 82.6
64.4
105.5 105.5 87.4
69.2
65
60.4
63.7
64.2
66.9
67.6
70.2
70.9
68.3
70.2
66.4
69.6
52.6
53.3
51.3
54.0
51.9
54.7
52.4
50.5
51.8
46.3
51.1
Johnson Controls Unitary Products
5167825-BTG-F-0217
XA-10 (10 Ton) (Continued)
Air on
Evaporator Coil
CFM
2500
3000
3500
4000
4500
5000
WB
(°F)
Total
Capacity1
(MBh)
Total
Input
(kW)2
90
77
72
67
62
77
72
67
62
57
77
72
67
62
57
77
72
67
62
57
72
67
62
57
72
67
62
57
109.0
102.2
95.4
89.6
111.7
104.7
97.7
91.8
97.4
114.3
107.1
100.0
93.9
99.6
116.9
109.6
102.3
96.1
101.9
107.1
100.0
93.9
99.6
104.6
97.7
91.7
97.3
11.8
11.6
11.5
11.3
11.8
11.6
11.5
11.3
11.4
11.8
11.6
11.4
11.3
11.4
11.8
11.6
11.4
11.3
11.4
11.7
11.5
11.4
11.5
11.7
11.5
11.4
11.5
43.6
67.1
90.6
89.6
57.4
76.0
94.5
91.8
97.4
71.2
84.8
98.4
93.9
99.6
85.0
93.6
102.3
96.1
101.9
97.9
100.0
93.9
99.6
102.3
97.7
91.7
97.3
Temperature of Air on Condenser Coil
Sensible Capacity (MBh)
Total
Total
Return Dry Bulb (°F)
Input
Capacity1
(MBh)
(kW)2
85
80
75
70
65
115°F
39.8
29.5
98.4
13.1
56.7
46.4
36.0
92.4
12.9
73.6
63.3
52.9
42.5
86.4
12.7
89.6
74.2
63.8
53.4
43.0
81.4
12.6
44.9
32.4
100.7
13.1
63.4
50.9
38.4
94.5
12.9
82.0
69.5
57.0
44.5
88.4
12.7
91.8
81.5
68.9
56.4
43.9
83.2
12.6
92.0
79.5
67.0
54.5
42.0
89.6
12.7
49.9
35.3
102.9
13.0
70.1
55.5
40.8
96.6
12.9
90.4
75.7
61.1
46.4
90.3
12.7
93.9
88.8
74.1
59.5
44.8
85.1
12.5
97.0
86.6
72.0
57.3
42.7
91.6
12.7
55.0
38.2
105.2
13.0
76.8
60.1
43.3
98.7
12.8
98.7
82.0
65.2
48.4
92.3
12.7
96.1
96.1
79.3
62.5
45.7
86.9
12.5
101.9 93.8
77.0
60.2
43.4
93.6
12.7
80.5
63.1
45.6
96.3
12.9
98.2
86.0
68.6
51.2
90.0
12.7
93.9
93.9
76.4
59.0
41.6
84.8
12.6
99.6
95.5
78.1
60.6
43.2
91.3
12.8
84.2
66.1
48.0
93.9
13.0
97.7
90.1
72.0
53.9
87.8
12.8
91.7
91.7
73.6
55.5
37.4
82.7
12.6
97.3
97.3
79.2
61.1
43.0
89.1
12.8
90
36.1
61.3
86.4
81.4
53.3
70.8
88.4
83.2
89.6
70.5
80.4
90.3
85.1
91.6
87.6
89.9
92.3
86.9
93.6
92.8
90.0
84.8
91.3
93.9
87.8
82.7
89.1
Sensible Capacity (MBh)
Return Dry Bulb (°F)
85
80
75
70
125°F
32.0
23.6
51.1
40.8
30.6
68.3
58.0
47.8
37.6
81.4
64.0
53.8
43.6
39.2
26.7
58.3
45.9
33.4
77.5
65.0
52.5
40.1
83.2
71.9
59.5
47.0
82.6
70.1
57.6
45.1
46.3
29.7
65.6
50.9
36.1
86.8
72.0
57.3
42.5
85.1
79.9
65.1
50.4
88.1
77.8
63.1
48.3
53.5
32.7
72.9
55.9
38.8
92.3
79.0
62.0
44.9
86.9
86.9
70.8
53.7
93.6
85.5
68.5
51.5
75.3
57.7
40.2
90.0
81.8
64.2
46.7
84.8
84.8
67.7
50.2
91.3
87.3
69.8
52.2
77.7
59.6
41.6
87.8
84.5
66.5
48.4
82.7
82.7
64.6
46.6
89.1
89.1
71.0
52.9
65
33.4
34.5
32.6
35.6
33.5
36.7
34.4
32.6
34.7
28.5
34.9
1. These capacities are gross ratings. For net capacity, deduct air blower motor, MBh = 3.415 x kW. Refer to the appropriate Blower
Performance Table for the kW of the supply air blower motor.
2. These ratings include the condenser fan motors (total 1 kW) and the compressor motors but not the supply air blower motor.
Johnson Controls Unitary Products
23
5167825-BTG-F-0217
XA-12 (12.5 Ton)
Air on
Evaporator Coil
CFM
3125
3750
4375
5000
5625
6250
3125
3750
4375
5000
5625
6250
24
WB
(°F)
Total
Capacity1
(MBh)
Total
Input
(kW)2
90
77
72
67
62
77
72
67
62
57
77
72
67
62
57
77
72
67
62
57
72
67
62
57
72
67
62
57
177.3
169.6
161.9
142.0
185.6
177.6
169.5
148.6
155.3
194.0
185.6
177.2
155.3
162.3
202.3
193.6
184.8
162.0
169.3
196.8
187.9
164.7
172.1
200.0
190.9
167.4
174.9
9.4
9.2
8.9
8.8
9.5
9.2
9.0
8.9
8.9
9.6
9.3
9.1
9.0
9.0
9.7
9.4
9.1
9.1
9.1
9.5
9.2
9.1
9.2
9.6
9.3
9.2
9.3
80.2
105.2
130.1
142.0
85.3
112.7
140.0
148.6
155.3
90.4
120.2
149.9
155.3
162.3
95.5
127.7
159.9
162.0
169.3
141.2
175.4
164.7
172.1
154.7
190.9
167.4
174.9
77
72
67
62
77
72
67
62
57
77
72
67
62
57
77
72
67
62
57
72
67
62
57
72
67
62
57
158.2
150.8
143.3
131.3
166.6
158.8
150.9
138.2
136.2
175.0
166.7
158.5
145.2
143.0
183.3
174.7
166.0
152.1
149.8
176.0
167.3
153.2
150.9
177.3
168.5
154.4
152.1
11.4
11.3
11.1
10.9
11.5
11.3
11.2
11.0
10.9
11.6
11.4
11.2
11.0
11.0
11.6
11.5
11.3
11.1
11.1
11.5
11.3
11.1
11.1
11.5
11.3
11.1
11.1
74.7
97.1
119.5
131.3
83.0
107.6
132.2
138.2
136.2
91.3
118.1
144.8
145.2
143.0
99.6
128.6
157.5
152.1
149.8
139.3
163.0
153.2
150.9
150.0
168.5
154.4
152.1
Temperature of Air on Condenser Coil
Sensible Capacity (MBh)
Total
Total
Return Dry Bulb (°F)
Capacity1
Input
(MBh)
(kW)2
85
80
75
70
65
75°F
64.9
49.6
167.8
10.4
89.8
74.5
59.2
160.2
10.2
114.8 99.4
84.1
68.8
152.6
10.0
139.6 120.0 104.6 89.3
74.0
136.6
9.9
69.8
54.4
176.1
10.5
97.2
81.7
66.2
168.2
10.3
124.5 109.1 93.6
78.1
160.2
10.1
147.1 131.6 116.1 100.6 85.1
143.4
9.9
155.3 136.8 121.3 105.8 90.4
145.7
9.9
74.8
59.2
184.5
10.6
104.6 88.9
73.3
176.1
10.4
134.3 118.7 103.1 87.4
167.8
10.2
154.5 143.2 127.6 112.0 96.3
150.2
10.0
162.3 148.9 133.3 117.6 102.0
152.7
10.0
79.7
64.0
192.8
10.6
111.9 96.2
80.4
184.1
10.4
144.1 128.3 112.6 96.8
175.4
10.2
162.0 154.8 139.1 123.3 107.5
157.0
10.1
169.3 161.0 145.2 129.4 113.7
159.6
10.1
122.2 103.2 84.1
186.4
10.5
156.7 137.7 118.6 99.6
177.6
10.3
164.7 161.1 142.1 123.1 104.0
159.0
10.1
172.1 167.9 148.9 129.9 110.8
161.5
10.1
132.4 110.2 87.9
188.6
10.5
169.3 147.0 124.7 102.4
179.7
10.3
167.4 167.4 145.1 122.8 100.5
160.9
10.2
174.9 174.9 152.6 130.3 108.0
163.5
10.2
95°F
61.1
47.4
154.6
12.7
83.5
69.8
56.2
145.2
12.6
105.8 92.2
78.5
64.9
135.7
12.4
131.2 111.8 98.1
84.5
70.8
128.8
12.2
67.5
52.1
161.3
12.8
92.1
76.6
61.1
151.5
12.6
116.7 101.2 85.7
70.2
141.6
12.5
138.2 122.7 107.2 91.7
76.2
134.3
12.3
136.2 123.7 108.2 92.8
77.3
131.7
12.3
74.0
56.7
168.0
12.9
100.8 83.4
66.1
157.8
12.7
127.5 110.2 92.9
75.6
147.5
12.6
145.1 133.6 116.3 99.0
81.7
139.8
12.3
143.0 134.7 117.4 100.1 82.8
137.2
12.3
80.5
61.3
174.6
12.9
109.4 90.3
71.1
164.0
12.8
138.4 119.2 100.1 80.9
153.4
12.6
152.1 144.5 125.4 106.3 87.1
145.4
12.4
149.8 145.8 126.6 107.5 88.3
142.6
12.4
118.3 97.3
76.4
165.7
12.8
149.5 128.5 107.6 86.6
155.0
12.6
153.2 149.5 128.5 107.5 86.5
146.9
12.4
150.9 148.9 127.9 106.9 86.0
144.1
12.4
127.2 104.4 81.6
167.4
12.8
160.7 137.9 115.1 92.3
156.6
12.7
154.4 154.4 131.6 108.7 85.9
148.4
12.4
152.1 152.1 129.2 106.4 83.6
145.5
12.4
90
77.5
101.1
124.8
136.6
84.2
110.1
136.1
143.4
145.7
90.9
119.1
147.4
150.2
152.7
97.6
128.1
158.7
157.0
159.6
140.3
169.2
159.0
161.5
152.4
179.7
160.9
163.5
68.2
92.3
116.4
128.8
78.0
102.7
127.3
134.3
131.7
87.9
113.1
138.2
139.8
137.2
97.8
123.5
149.2
145.4
142.6
133.3
152.9
146.9
144.1
143.2
156.6
148.4
145.5
Sensible Capacity (MBh)
Return Dry Bulb (°F)
85
80
75
70
85°F
63.0
48.5
86.6
72.2
57.7
110.3 95.8
81.3
66.8
135.4 115.9 101.4 86.9
68.7
53.2
94.7
79.2
63.7
120.6 105.1 89.6
74.2
142.6 127.1 111.7 96.2
145.7 130.3 114.8 99.3
74.4
57.9
102.7 86.2
69.7
130.9 114.4 98.0
81.5
149.8 138.4 121.9 105.5
152.7 141.8 125.3 108.9
80.1
62.7
110.7 93.2
75.8
141.2 123.8 106.3 88.9
157.0 149.7 132.2 114.8
159.6 153.4 135.9 118.4
120.3 100.2 80.2
153.1 133.1 113.1 93.1
159.0 155.3 135.3 115.3
161.5 158.4 138.4 118.4
129.8 107.3 84.7
165.0 142.5 119.9 97.3
160.9 160.9 138.3 115.8
163.5 163.5 140.9 118.4
105°F
56.5
43.1
78.9
65.5
52.1
101.2 87.8
74.4
61.0
122.6 104.4 91.0
77.6
62.7
47.5
87.4
72.1
56.8
112.0 96.7
81.4
66.1
130.2 114.9 99.6
84.3
128.9 115.2 99.9
84.6
69.0
51.8
95.9
78.7
61.5
122.8 105.6 88.4
71.2
137.8 125.5 108.3 91.1
135.8 125.7 108.6 91.4
75.2
56.2
104.4 85.3
66.2
133.6 114.5 95.4
76.3
145.4 136.0 116.9 97.9
142.6 136.3 117.2 98.2
112.6 91.8
71.0
143.1 123.1 102.3 81.5
146.9 142.2 121.4 100.6
144.1 140.9 120.1 99.3
120.7 98.2
75.7
152.7 131.8 109.3 86.7
148.4 148.4 125.9 103.4
145.5 145.5 123.0 100.5
65
72.4
80.7
83.8
89.0
92.4
97.3
101.0
95.3
98.4
93.2
95.8
64.2
69.0
69.3
73.9
74.2
78.8
79.1
79.8
78.5
80.9
78.0
Johnson Controls Unitary Products
5167825-BTG-F-0217
XA-12 (12.5 Ton) (Continued)
Air on
Evaporator Coil
CFM
3125
3750
4375
5000
5625
6250
WB
(°F)
Total
Capacity1
(MBh)
Total
Input
(kW)2
90
77
72
67
62
77
72
67
62
57
77
72
67
62
57
77
72
67
62
57
72
67
62
57
72
67
62
57
151.0
139.6
128.2
126.2
156.0
144.2
132.4
130.4
127.3
161.0
148.8
136.6
134.5
131.3
166.0
153.4
140.8
138.7
135.4
155.5
142.7
140.5
137.2
157.5
144.6
142.4
139.0
14.0
13.9
13.7
13.5
14.1
13.9
13.8
13.5
13.6
14.2
14.0
13.9
13.6
13.7
14.2
14.1
13.9
13.7
13.7
14.1
14.0
13.7
13.7
14.1
14.0
13.7
13.7
61.6
87.4
113.3
126.2
73.1
97.8
122.5
130.4
127.3
84.5
108.1
131.6
134.5
131.3
95.9
118.4
140.8
138.7
135.4
127.4
142.7
140.5
137.2
136.4
144.6
142.4
139.0
Temperature of Air on Condenser Coil
Sensible Capacity (MBh)
Total
Total
Return Dry Bulb (°F)
Input
Capacity1
(MBh)
(kW)2
85
80
75
70
65
115°F
51.9
38.8
147.4
15.3
74.3
61.1
48.0
134.0
15.2
96.7
83.5
70.3
57.2
120.6
15.0
114.1 97.0
83.8
70.7
57.5
123.6
14.7
57.9
42.8
150.7
15.4
82.6
67.5
52.4
136.9
15.2
107.4 92.2
77.1
62.0
123.1
15.1
122.3 107.2 92.1
77.0
61.9
126.4
14.8
121.7 106.6 91.5
76.4
61.3
122.8
14.9
64.0
46.9
154.0
15.4
91.0
74.0
56.9
139.8
15.3
118.1 101.0 83.9
66.9
125.7
15.2
130.5 117.3 100.3 83.2
66.2
129.2
14.9
128.6 116.7 99.7
82.6
65.6
125.5
15.0
70.0
51.0
157.3
15.5
99.4
80.4
61.4
142.8
15.4
128.8 109.8 90.7
71.7
128.2
15.3
138.7 127.5 108.5 89.5
70.5
132.0
15.0
135.4 126.8 107.8 88.8
69.8
128.2
15.1
106.8 86.2
65.6
145.2
15.4
136.7 117.7 97.1
76.5
130.4
15.3
140.5 135.0 114.3 93.7
73.1
134.2
15.0
137.2 132.9 112.3 91.7
71.1
130.3
15.1
114.2 92.0
69.8
147.6
15.4
144.6 125.6 103.4 81.2
132.7
15.3
142.4 142.4 120.2 98.0
75.8
136.4
15.0
139.0 139.0 116.8 94.6
72.4
132.5
15.1
90
52.9
82.6
110.2
123.6
68.1
92.8
117.6
126.4
122.8
83.2
103.1
125.1
129.2
125.5
98.3
113.3
128.2
132.0
128.2
121.4
130.4
134.2
130.3
129.6
132.7
136.4
132.5
Sensible Capacity (MBh)
Return Dry Bulb (°F)
85
80
75
70
125°F
47.4
34.5
69.7
56.8
43.9
92.1
79.2
66.2
53.3
105.5 89.6
76.7
63.8
53.1
38.2
77.9
63.0
48.1
102.7 87.8
72.9
57.9
114.3 99.4
84.5
69.6
114.5 98.1
83.1
68.2
58.9
42.0
86.1
69.2
52.3
113.3 96.4
79.5
62.5
123.1 109.2 92.3
75.3
121.3 107.7 90.8
73.9
64.7
45.8
94.3
75.4
56.5
124.0 105.0 86.1
67.1
132.0 119.0 100.1 81.1
128.2 117.4 98.5
79.5
101.0 80.6
60.2
130.3 112.3 91.9
71.4
134.2 127.7 107.3 86.9
130.3 124.9 104.5 84.1
107.7 85.8
63.9
132.7 119.5 97.6
75.7
136.4 136.4 114.5 92.6
132.5 132.5 110.6 88.7
65
50.9
54.7
53.3
58.4
56.9
62.2
60.6
66.5
63.7
70.7
66.8
1. These capacities are gross ratings. For net capacity, deduct air blower motor, MBh = 3.415 x kW. Refer to the appropriate Blower
Performance Table for the kW of the supply air blower motor.
2. These ratings include the condenser fan motors (total 1 kW) and the compressor motors but not the supply air blower motor.
Johnson Controls Unitary Products
25
5167825-BTG-F-0217
XA-06 thru -12 Heating Capacities
XA-06 thru -12
Size
(Tons)
Model
Air Over Evaporator
Coil
CFM
DB (°F)
55
1950
70
80
55
-06
(6.5)
XA
2600
70
80
55
3250
70
80
55
2250
70
80
55
-07
(7.5)
XA
3000
70
80
55
3750
70
80
55
2550
70
80
55
-08
(8.5)
XA
3400
70
80
55
4250
70
80
26
Capacity1 &
kW
MBH
kW
MBH
kW
MBH
kW
MBH
kW
MBH
kW
MBH
kW
MBH
kW
MBH
kW
MBH
kW
MBH
KW
MBH
KW
MBH
KW
MBH
KW
MBH
KW
MBH
KW
MBH
KW
MBH
KW
MBH
KW
MBH
KW
MBH
KW
MBH
KW
MBH
KW
MBH
KW
MBH
KW
MBH
KW
MBH
KW
MBH
KW
Outdoor Temperature (°F @ 72% RH)
-10
0
10
20
30
40
50
60
10.1
4.10
4.8
4.95
0.9
5.54
13.4
3.63
8.0
4.45
4.3
5.07
13.8
3.25
8.5
4.11
4.6
4.69
17.4
5.0
15.4
6.1
13.0
6.9
20.1
4.4
18.0
5.5
15.9
6.4
21.2
4.0
19.1
5.1
16.7
5.9
9.4
4.9
12.2
6.1
11.1
6.9
14.9
4.3
17.7
5.6
16.6
6.4
17.2
4.0
20.0
5.2
18.9
6.1
21.7
4.30
16.4
5.15
12.5
5.74
25.0
3.83
19.6
4.65
15.8
5.27
25.3
3.45
20.0
4.30
16.2
4.89
29.3
5.2
27.3
6.3
24.9
7.1
32.0
4.6
29.9
5.7
27.7
6.6
33.0
4.2
31.0
5.3
28.6
6.1
22.3
5.1
25.1
6.3
24.0
7.1
27.8
4.5
30.6
5.8
29.4
6.6
30.1
4.2
32.9
5.4
31.8
6.3
33.3
4.50
28.0
5.35
24.1
5.94
36.6
4.03
31.2
4.85
27.4
5.47
36.9
3.65
31.6
4.50
27.7
5.09
41.1
5.4
39.1
6.5
36.7
7.3
43.8
4.9
41.8
5.9
39.6
6.8
44.9
4.4
42.9
5.5
40.5
6.3
35.1
5.3
37.9
6.5
36.8
7.3
40.6
4.7
43.4
6.0
42.3
6.8
42.9
4.4
45.7
5.6
44.6
6.5
44.8
4.70
39.5
5.55
35.7
6.14
48.1
4.22
42.7
5.05
39.0
5.67
48.5
3.85
43.2
4.70
39.3
5.29
53.0
5.6
51.0
6.7
48.6
7.5
55.7
5.1
53.6
6.1
51.5
7.0
56.7
4.6
54.7
5.7
52.3
6.5
48.0
5.5
50.8
6.7
49.7
7.5
53.5
4.9
56.3
6.2
55.1
7.0
55.8
4.6
58.6
5.9
57.5
6.7
56.4
4.89
51.1
5.75
47.2
6.33
59.7
4.42
54.3
5.24
50.5
5.86
60.0
4.05
54.7
4.90
50.9
5.48
64.9
5.9
62.8
6.9
60.4
7.7
67.6
5.3
65.5
6.3
63.3
7.2
68.6
4.8
66.6
5.9
64.2
6.7
60.8
5.7
63.7
6.9
62.5
7.7
66.3
5.2
69.1
6.4
68.0
7.2
68.6
4.8
71.4
6.1
70.3
6.9
68.0
5.09
62.7
5.94
58.8
6.53
71.3
4.62
65.9
5.44
62.1
6.06
71.6
4.24
66.3
5.10
62.4
5.68
76.7
6.1
74.7
7.1
72.3
7.9
79.4
5.5
77.3
6.6
75.2
7.4
80.5
5.1
78.5
6.1
76.1
6.9
73.7
5.9
76.5
7.1
75.4
7.9
79.2
5.4
82.0
6.6
80.8
7.4
81.5
5.0
84.3
6.3
83.2
7.1
79.5
5.29
74.2
6.14
70.4
6.73
82.8
4.82
77.4
5.64
73.7
6.26
83.2
4.44
77.9
5.29
74.0
5.88
88.6
6.3
86.6
7.4
84.2
8.1
91.3
5.7
89.2
6.8
87.1
7.6
92.3
5.3
90.3
6.3
87.9
7.1
86.5
6.1
89.4
7.3
88.2
8.2
92.0
5.6
94.8
6.8
93.7
7.6
94.3
5.2
97.1
6.5
96.0
7.3
91.1
5.49
85.8
6.34
81.9
6.93
94.4
5.02
89.0
5.84
85.2
6.46
94.7
4.64
89.5
5.49
85.6
6.08
100.5
6.5
98.4
7.6
96.0
8.4
103.2
5.9
101.1
7.0
98.9
7.8
104.2
5.5
102.2
6.6
99.8
7.3
99.4
6.3
102.2
7.5
101.1
8.4
104.9
5.8
107.7
7.0
106.6
7.8
107.2
5.4
110.0
6.7
108.9
7.5
Johnson Controls Unitary Products
5167825-BTG-F-0217
XA-06 thru -12 (Continued)
Size
(Tons)
Model
Air Over Evaporator
Coil
CFM
DB (°F)
55
3000
70
80
55
-10
(10)
XA
4000
70
80
55
5000
70
80
55
3750
70
80
55
-12
(12.5)
XA
5000
70
80
55
6250
70
80
Capacity1 &
kW
MBH
kW
MBH
kW
MBH
kW
MBH
kW
MBH
kW
MBH
kW
MBH
kW
MBH
kW
MBH
kW
MBH
kW
MBH
kW
MBH
kW
MBH
kW
MBH
kW
MBH
kW
MBH
kW
MBH
kW
MBH
kW
Outdoor Temperature (°F @ 72% RH)
-10
0
10
20
30
40
50
60
51.3
5.35
40.6
6.49
37.7
7.24
52.4
4.68
41.8
5.83
39.0
6.59
52.1
3.49
41.5
4.63
38.6
5.38
26.6
8.44
22.5
10.24
20.5
11.93
34.6
7.16
30.6
8.99
28.6
10.69
36.0
6.57
31.9
8.38
29.9
10.07
63.5
5.59
52.8
6.73
50.0
7.48
64.6
4.92
54.0
6.07
51.2
6.83
64.4
3.73
53.7
4.87
50.8
5.62
46.1
8.82
42.0
10.63
40.0
12.32
54.2
7.55
50.2
9.38
48.2
11.08
55.5
6.96
51.4
8.77
49.4
10.46
75.7
5.83
65.0
6.97
62.2
7.72
76.8
5.16
66.2
6.31
63.4
7.07
76.6
3.97
65.9
5.11
63.0
5.86
65.7
9.21
61.6
11.02
59.6
12.71
73.7
7.94
69.7
9.77
67.7
11.46
75.1
7.35
71.0
9.16
69.0
10.85
87.9
6.07
77.2
7.21
74.4
7.96
89.1
5.40
78.4
6.55
75.6
7.31
88.8
4.21
78.1
5.35
75.2
6.11
85.2
9.60
81.2
11.41
79.1
13.10
93.3
8.32
89.3
10.16
87.3
11.85
94.6
7.74
90.6
9.55
88.5
11.23
100.1
6.31
89.4
7.45
86.6
8.20
101.3
5.65
90.6
6.79
87.8
7.55
101.0
4.45
90.3
5.59
87.4
6.35
104.8
9.99
100.7
11.80
98.7
13.48
112.9
8.71
108.9
10.55
106.9
12.24
114.2
8.13
110.1
9.93
108.1
11.62
112.3
6.55
101.6
7.69
98.8
8.44
113.5
5.89
102.8
7.03
100.0
7.79
113.2
4.70
102.5
5.84
99.6
6.59
124.4
10.38
120.3
12.18
118.2
13.87
132.4
9.10
128.4
10.93
126.4
12.63
133.8
8.51
129.7
10.32
127.7
12.01
124.5
6.79
113.8
7.93
111.0
8.68
125.7
6.13
115.0
7.27
112.2
8.03
125.4
4.94
114.7
6.08
111.8
6.83
143.9
10.76
139.8
12.57
137.8
14.26
152.0
9.49
148.0
11.32
146.0
13.02
153.3
8.90
149.2
10.71
147.2
12.40
136.7
7.03
126.1
8.17
123.2
8.92
137.9
6.37
127.2
7.51
124.4
8.28
137.6
5.18
126.9
6.32
124.0
7.07
163.5
11.15
159.4
12.96
157.4
14.65
171.5
9.88
167.5
11.71
165.5
13.40
172.9
9.29
168.8
11.10
166.8
12.79
1. These capacities do not include the supply air blower motor heat. For net capacity, add motor heat, MBh = 3.415 x kW.
Johnson Controls Unitary Products
27
5167825-BTG-F-0217
Airflow Performance
XA-06 thru -12 Side Duct Application
XA-06 (6.5 Ton) Side Duct
Air Flow
(CFM)
1800
2000
2200
2400
2600
2800
3000
3200
3400
1.
2.
3.
4.
Available External Static Pressure - IWG1
0.2
0.4
0.6
0.8
1.0
1.2
1.4
1.6
1.8
2.0
RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP
441
470
500
529
558
587
616
645
674
FS4
0.44
552
0.48
571
0.54
591
0.60
612
0.68
635
0.78
658
0.88
683
1.00
710
1.14
737
0.54
0.59
0.66
0.73
0.82
0.92
1.02
1.14
1.27
639
654
669
686
705
725
746
768
792
Standard 1.5 HP & Drive
0.63
719
0.72
785
0.69
730
0.79
795
0.76
743
0.87
806
0.85
756
0.96
819
0.94
771
1.05
832
1.04
788
1.16
847
1.15
806
1.28
863
1.27
825
1.41
879
1.40
846
1.55
897
0.81
0.89
0.97
1.07
1.17
1.29
1.41
1.55
1.70
859
870
882
894
906
918
931
943
956
0.99
1.09
1.18
1.29
1.40
1.51
1.63
1.76
1.89
Hi Static 2 HP & Drive
920
1.16
966
1.25
932
1.25
978
1.35
944
1.35
990
1.44
956
1.45 1002 1.55
968
1.56 1014 1.66
980
1.68 1026 1.77
992
1.80 1038 1.89
1005 1.92 1051 2.02
1018 2.06 1064 2.15
1018 1.35
1030 1.44
1042 1.54
1054 1.64
1066 1.75
1078 1.87
1090 1.99
1103 2.12
1116 2.25
FS4
1066
1078
1090
1102
1114
1126
1138
1151
-
1.43
1.53
1.62
1.73
1.84
1.95
2.07
2.20
-
Blower performance includes gas heat exchangers and 2" filters. See STATIC RESISTANCE table for additional applications.
See RPM SELECTION table to determine desired motor sheave setting and to determine the maximum continuous BHP.
kW = BHP x .932.
Field Supplied Drive.
XA-07 (7.5 Ton) Side Duct
Air Flow
(CFM)
2000
2200
2400
2600
2800
3000
3200
3400
3600
3800
1.
2.
3.
4.
Available External Static Pressure - IWG1
0.2
0.4
0.6
0.8
1.0
1.2
1.4
1.6
1.8
2.0
RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP
619
631
642
652
663
675
688
703
718
FS4
656
0.07
670
0.16
682
0.27
692
0.39
703
0.53
714
0.68
726
0.84
739
1.03
753
1.23
769
0.24
0.32
0.41
0.52
0.64
0.77
0.92
1.09
1.28
1.47
711
724
736
747
757
768
780
793
807
823
0.48
0.57
0.66
0.76
0.88
1.02
1.17
1.34
1.52
1.72
768
781
793
804
814
825
837
850
864
880
Standard 1.5 HP & Drive
0.73
826
0.96
886
0.81
840
1.04
899
0.90
852
1.14
911
1.01
862
1.24
922
1.13
873
1.36
932
1.26
884
1.50
943
1.41
896
1.65
955
1.58
909
1.82
968
1.76
923
2.00
983
1.96
939
2.20
998
1.19
1.27
1.36
1.47
1.59
1.73
1.88
2.04
2.23
2.43
945
959
970
981
992
1003
1014
1027
1042
1058
1.41
1.49
1.58
1.69
1.81
1.94
2.09
2.26
2.44
2.64
1003
1016
1028
1039
1049
1060
1072
1085
1100
1115
Hi Static 3 HP & Drive
1.61 1058 1.79 1110
1.69 1072 1.87 1124
1.78 1084 1.97 1136
1.89 1094 2.07 1146
2.01 1105 2.19 1157
2.14 1116 2.33 1168
2.29 1128 2.48 1180
2.46 1141 2.65 1193
2.64 1155 2.83
2.84 1171 3.03
-
1.95
2.04
2.13
2.24
2.36
2.49
2.64
2.81
-
Blower performance includes gas heat exchangers and 2” filters. See STATIC RESISTANCE table for additional applications.
See RPM SELECTION table to determine desired motor sheave setting and to determine the maximum continuous BHP.
kW = BHP x 0.932.
Field Supplied Drive.
XA-08 (8.5 Ton) Side Duct
Air Flow
(CFM)
2200
2400
2600
2800
3000
3200
3400
3600
3800
4000
4200
Available External Static Pressure - IWG1
0.2
0.4
0.6
0.8
1.0
1.2
1.4
1.6
1.8
2.0
RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP
2 HP & Field Supplied Drive
632
0.23
684
0.44
639
0.32
691
0.53
646
0.41
698
0.62
654
0.50
706
0.71
663
0.60
714
0.81
673
0.71
724
0.93
684
0.84
735
1.05
696
0.98
747
1.19
709
1.14
761
1.35
724
1.31
776
1.52
740
1.50
792
1.71
734
741
748
756
765
774
785
798
811
826
842
0.65
0.74
0.82
0.92
1.02
1.13
1.25
1.39
1.55
1.72
1.92
783
790
797
805
813
823
834
846
860
874
890
Standard 2 HP & Drive
0.84
830
1.03
876
0.93
837
1.12
883
1.02
844
1.21
890
1.11
852
1.30
898
1.21
861
1.40
907
1.32
871
1.51
917
1.45
882
1.63
928
1.59
894
1.78
940
1.75
907
1.93
953
1.92
922
2.11
968
2.11
938
2.30
984
1.21
1.30
1.39
1.48
1.58
1.69
1.82
1.96
2.12
2.29
2.48
921
928
936
943
952
962
973
985
999
1013
1029
1.39
1.48
1.57
1.66
1.76
1.87
2.00
2.14
2.29
2.47
2.66
966
972
980
987
996
1006
1017
1029
1043
1057
1073
Hi Static 3 HP & Drive
1.56 1009 1.74 1051 1.91
1.65 1015 1.83 1058 2.00
1.74 1023 1.92 1065 2.09
1.83 1031 2.01 1073 2.18
1.93 1039 2.11 1082 2.28
2.05 1049 2.22 1091 2.39
2.17 1060 2.34 1102 2.52
2.31 1072 2.48 1115 2.66
2.47 1086 2.64 1128 2.81
2.64 1100 2.82 1143 2.99
2.83 1116 3.01 1159 3.18
3 HP & Field Supplied Drive
1. Blower performance includes 2” filters. See STATIC RESISTANCE table for additional applications.
2. See RPM SELECTION table to determine desired motor sheave setting and to determine the maximum continuous BHP.
3. kW = BHP x 0.932.
28
Johnson Controls Unitary Products
5167825-BTG-F-0217
XA-10 (10 Ton) Side Duct
Air Flow
(CFM)
2600
2800
3000
3200
3400
3600
3800
4000
4200
4400
4600
4800
5000
Available External Static Pressure - IWG1
0.2
0.4
0.6
0.8
1.0
1.2
1.4
1.6
1.8
2.0
RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP
646
654
663
673
684
696
709
724
740
757
776
795
816
2 HP & Field Supplied Drive
0.41
698
0.62
748
0.50
706
0.71
756
0.60
714
0.81
765
0.71
724
0.93
774
0.84
735
1.05
785
0.98
747
1.19
798
1.14
761
1.35
811
1.31
776
1.52
826
1.50
792
1.71
842
1.71
809
1.92
859
1.94
827
2.15
877
2.19
847
2.40
897
2.45
868
2.66
918
0.82
0.92
1.02
1.13
1.25
1.39
1.55
1.72
1.92
2.13
2.35
2.60
2.86
797
805
813
823
834
846
860
874
890
908
926
946
967
1.02
1.11
1.21
1.32
1.45
1.59
1.75
1.92
2.11
2.32
2.55
2.79
3.06
844
852
861
871
882
894
907
922
938
955
974
993
1014
Standard 2 HP & Drive
1.21
890
1.39
936
1.30
898
1.48
943
1.40
907
1.58
952
1.51
917
1.69
962
1.63
928
1.82
973
1.78
940
1.96
985
1.93
953
2.12
999
2.11
968
2.29 1013
2.30
984
2.48 1029
2.51 1001 2.69 1046
2.74 1020 2.92 1065
2.98 1040 3.16 1085
3.25 1061 3.43
-
1.57
1.66
1.76
1.87
2.00
2.14
2.29
2.47
2.66
2.87
3.10
3.34
-
980
987
996
1006
1017
1029
1043
1057
1073
1091
1109
-
1.74
1.83
1.93
2.05
2.17
2.31
2.47
2.64
2.83
3.04
3.27
-
Hi Static 3 HP & Drive
1023 1.92 1065 2.09
1031 2.01 1073 2.18
1039 2.11 1082 2.28
1049 2.22 1091 2.39
1060 2.34 1102 2.52
1072 2.48 1115 2.66
1086 2.64 1128 2.81
1100 2.82 1143 2.99
1116 3.01 1159 3.18
1134 3.22 1176 3.39
1152 3.45
3 HP & Field Supplied Drive
1. Blower performance includes 2” filters. See STATIC RESISTANCE table for additional applications.
2. See RPM SELECTION table to determine desired motor sheave setting and to determine the maximum continuous BHP.
3. kW = BHP x 0.932.
XA-12 (12.5 Ton) Side Duct
Air Flow
(CFM)
3200
3400
3600
3800
4000
4200
4400
4600
4800
5000
5200
5400
5600
5800
6000
6200
Available External Static Pressure - IWG1
0.2
0.4
0.6
0.8
1.0
1.2
1.4
1.6
1.8
2.0
RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP
673
684
696
709
724
740
757
776
795
816
839
862
886
912
939
967
0.71
0.84
0.98
1.14
1.31
1.50
1.71
1.94
2.19
2.45
2.73
3.03
3.34
3.67
4.02
4.39
724
735
747
761
776
792
809
827
847
868
890
914
938
964
990
1018
3 HP & Field Supplied Drive
0.93
774
1.13
823
1.32
871
1.05
785
1.25
834
1.45
882
1.19
798
1.39
846
1.59
894
1.35
811
1.55
860
1.75
907
1.52
826
1.72
874
1.92
922
1.71
842
1.92
890
2.11
938
1.92
859
2.13
908
2.32
955
2.15
877
2.35
926
2.55
974
2.40
897
2.60
946
2.79
993
2.66
918
2.86
967
3.06 1014
2.94
940
3.14
989
3.34 1037
3.24
964
3.44 1012 3.64 1060
3.55
988
3.76 1037 3.95 1084
3.89 1014 4.09 1063 4.28 1110
4.23 1041 4.44 1089 4.63 1137
4.60 1068 4.80 1117 4.99 1165
Hi Static 5 HP & Drive
1.51
1.63
1.78
1.93
2.11
2.30
2.51
2.74
2.98
3.25
3.53
3.82
4.14
4.47
4.82
5.18
917
928
940
953
968
984
1001
1020
1040
1061
1083
1106
1131
1156
1183
1211
1.69
1.82
1.96
2.12
2.29
2.48
2.69
2.92
3.16
3.43
3.71
4.01
4.32
4.65
5.00
5.36
962
973
985
999
1013
1029
1046
1065
1085
1106
1128
1151
1176
1201
1228
1256
Standard 3 HP & Drive
1.87 1006 2.05 1049 2.22 1091
2.00 1017 2.17 1060 2.34 1102
2.14 1029 2.31 1072 2.48 1115
2.29 1043 2.47 1086 2.64 1128
2.47 1057 2.64 1100 2.82 1143
2.66 1073 2.83 1116 3.01 1159
2.87 1091 3.04 1134 3.22 1176
3.10 1109 3.27 1152 3.45 1194
3.34 1129 3.52 1172 3.69 1214
3.61 1150 3.78 1193 3.95 1235
3.89 1172 4.06 1215 4.23 1257
4.18 1195 4.36 1238 4.53 1281
4.50 1220 4.67 1263 4.85 1305
4.83 1246 5.01 1289 5.18 1331
5.18 1272 5.35 1315 5.53 1358
5.54 1300 5.72
5 HP & Field Supplied Drive
2.39
2.52
2.66
2.81
2.99
3.18
3.39
3.62
3.86
4.13
4.41
4.70
5.02
5.35
5.70
-
1. Blower performance includes 2” filters. See STATIC RESISTANCE table for additional applications.
2. See RPM SELECTION table to determine desired motor sheave setting and to determine the maximum continuous BHP.
3. kW = BHP x 0.932.
Johnson Controls Unitary Products
29
5167825-BTG-F-0217
XA-06 thru -12 Bottom Duct Application
XA-06 (6.5 Ton) Bottom Duct
Air Flow
(CFM)
1800
2000
2200
2400
2600
2800
3000
3200
3400
1.
2.
3.
4.
Available External Static Pressure - IWG1
0.2
0.4
0.6
0.8
1.0
1.2
1.4
1.6
1.8
2.0
RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP
445
486
530
567
605
645
686
729
772
FS4
0.63
559
0.71
589
0.84
624
0.91
653
1.02
685
1.16
719
1.31
757
1.49
797
1.70
839
0.66
0.76
0.90
0.98
1.10
1.24
1.39
1.57
1.77
Standard 1.5 HP & Drive
648
0.69
730
0.72
674
0.79
753
0.83
705
0.94
781
0.99
729
1.04
801
1.09
758
1.16
826
1.21
788
1.29
854
1.36
822
1.46
885
1.53
858
1.64
917
1.73
897
1.84
953
1.93
799
820
846
867
889
915
943
972
1005
0.75
0.87
1.03
1.14
1.27
1.43
1.60
1.81
2.03
875
898
924
944
965
988
1013
1038
1066
Hi Static 2 HP & Drive
0.89
937
0.99
984
1.05
1.02
960
1.13 1007 1.18
1.19
988
1.31 1034 1.35
1.31 1007 1.41 1055 1.47
1.45 1028 1.55 1075 1.60
1.60 1051 1.71 1099 1.75
1.77 1076 1.88 1123 1.93
1.96 1102 2.07 1149 2.11
2.16 1130 2.27 1177 2.31
FS4
1038
1061
1088
1108
1128
1151
1176
1203
1230
1.08
1.21
1.39
1.50
1.63
1.80
1.97
2.16
2.36
1086
1109
1137
1156
1178
1201
1225
1252
1.11
1.25
1.42
1.54
1.67
1.83
2.00
2.19
Blower performance includes gas heat exchangers and 2" filters. See STATIC RESISTANCE table for additional applications.
See RPM SELECTION table to determine desired motor sheave setting and to determine the maximum continuous BHP.
kW = BHP x .932.
Field Supplied Drive.
XA-07 (7.5 Ton) Bottom Duct
Air Flow
(CFM)
2000
2200
2400
2600
2800
3000
3200
3400
3600
3800
1.
2.
3.
4.
Available External Static Pressure - IWG1
0.2
0.4
0.6
0.8
1.0
1.2
1.4
1.6
1.8
2.0
RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP
FS4
644
0.11
666
0.26
689
0.42
712
0.60
736
0.80
761
1.00
787
1.22
813
1.46
841
1.70
869
1.96
698
720
743
766
790
815
840
867
894
923
0.38
0.53
0.69
0.87
1.06
1.27
1.49
1.73
1.97
2.22
755
777
800
823
847
872
898
924
952
980
Standard 1.5 HP & Drive
0.62
814
0.85
874
0.77
836
1.00
896
0.93
859
1.16
919
1.11
882
1.34
942
1.31
906
1.53
967
1.52
931
1.74
991
1.74
957
1.96 1017
1.97
984
2.19 1044
2.21 1011 2.44 1071
2.47 1039 2.69 1099
1.06
1.21
1.37
1.55
1.74
1.95
2.17
2.40
2.65
2.90
933
956
978
1002
1026
1051
1076
1103
1130
1158
1.26
1.41
1.57
1.75
1.94
2.15
2.37
2.61
2.85
3.10
990
1012
1035
1058
1082
1107
1133
1160
1187
1215
1.46
1.61
1.77
1.95
2.14
2.35
2.57
2.80
3.05
3.30
Hi Static 3 HP & Drive
1043 1.66 1090 1.87 1131
1065 1.81 1113 2.02 1153
1088 1.97 1135 2.18 1176
1111 2.15 1159 2.36 1199
1135 2.34 1183 2.55 1223
1160 2.55 1208 2.76 1248
1186 2.77 1233 2.98 1274
1212 3.01 1260 3.21
3 HP & Field Supplied Drive
2.09
2.24
2.40
2.58
2.78
2.98
3.20
-
Blower performance includes gas heat exchangers and 2” filters. See STATIC RESISTANCE table for additional applications.
See RPM SELECTION table to determine desired motor sheave setting and to determine the maximum continuous BHP.
kW = BHP x 0.932.
Field Supplied Drive.
XA-08 (8.5 Ton) Bottom Duct
Air Flow
(CFM)
2200
2400
2600
2800
3000
3200
3400
3600
3800
4000
4200
Available External Static Pressure - IWG1
0.2
0.4
0.6
0.8
1.0
1.2
1.4
1.6
1.8
2.0
RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP
2 HP & Field Supplied Drive
662
0.53
717
0.68
677
0.63
732
0.78
693
0.75
748
0.90
712
0.88
767
1.03
733
1.03
788
1.18
757
1.20
811
1.36
782
1.40
837
1.55
810
1.61
865
1.76
841
1.85
896
2.00
874
2.11
928
2.26
909
2.38
963
2.53
770
784
801
819
841
864
890
918
948
981
1016
0.83
0.93
1.04
1.17
1.33
1.50
1.69
1.91
2.14
2.40
2.68
Standard 2 HP & Drive
821
0.96
870
1.09
835
1.06
885
1.19
852
1.18
901
1.31
871
1.31
920
1.44
892
1.46
941
1.59
915
1.64
964
1.77
941
1.83
990
1.96
969
2.04 1018 2.18
999
2.28 1049 2.41
1032 2.54 1082 2.67
1067 2.81 1117 2.95
918
933
949
968
989
1012
1038
1066
1097
1130
1164
1.22
1.32
1.44
1.57
1.72
1.89
2.09
2.30
2.54
2.80
3.07
Hi Static 3 HP & Drive
965
1.35 1010 1.47 1055 1.59
979
1.44 1025 1.57 1069 1.69
996
1.56 1041 1.68 1085 1.80
1014 1.69 1060 1.81 1104 1.94
1036 1.84 1081 1.97 1125 2.09
1059 2.02 1104 2.14 1149 2.26
1085 2.21 1130 2.33 1174 2.45
1113 2.43 1158 2.55 1203 2.67
1143 2.66 1189 2.78 1233 2.91
1176 2.92 1222 3.04 1266 3.16
1211 3.20 1256 3.32 1301 3.44
3 HP & Field Supplied Drive
1098
1112
1129
1148
1169
1192
1218
1246
1276
1309
-
1.71
1.81
1.92
2.06
2.21
2.38
2.58
2.79
3.03
3.28
-
1. Blower performance includes 2” filters. See STATIC RESISTANCE table for additional applications.
2. See RPM SELECTION table to determine desired motor sheave setting and to determine the maximum continuous BHP.
3. kW = BHP x 0.932.
30
Johnson Controls Unitary Products
5167825-BTG-F-0217
XA-10 (10 Ton) Bottom Duct
Air Flow
(CFM)
2600
2800
3000
3200
3400
3600
3800
4000
4200
4400
4600
4800
Available External Static Pressure - IWG1
0.2
0.4
0.6
0.8
1.0
1.2
1.4
1.6
1.8
2.0
RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP
2 HP & Field Supplied Drive
693
0.75
748
0.90
712
0.88
767
1.03
733
1.03
788
1.18
757
1.20
811
1.36
782
1.40
837
1.55
810
1.61
865
1.76
841
1.85
896
2.00
874
2.11
928
2.26
909
2.38
963
2.53
946
2.68 1000 2.83
985
3.00 1040 3.15
1026 3.33
-
801
819
841
864
890
918
948
981
1016
1053
1092
-
1.04
1.17
1.33
1.50
1.69
1.91
2.14
2.40
2.68
2.98
3.29
-
Standard 2 HP & Drive
852
1.18
901
1.31
949
1.44
996
871
1.31
920
1.44
968
1.57 1014
892
1.46
941
1.59
989
1.72 1036
915
1.64
964
1.77 1012 1.89 1059
941
1.83
990
1.96 1038 2.09 1085
969
2.04 1018 2.18 1066 2.30 1113
999
2.28 1049 2.41 1097 2.54 1143
1032 2.54 1082 2.67 1130 2.80 1176
1067 2.81 1117 2.95 1164 3.07 1211
1104 3.11 1154 3.24 1202 3.37
1143 3.43
3 HP & Field Supplied Drive
Hi Static 3 HP & Drive
1.56 1041 1.68 1085
1.69 1060 1.81 1104
1.84 1081 1.97 1125
2.02 1104 2.14 1149
2.21 1130 2.33 1174
2.43 1158 2.55 1203
2.66 1189 2.78 1233
2.92 1222 3.04 1266
3.20 1256 3.32 1301
-
1.80
1.94
2.09
2.26
2.45
2.67
2.91
3.16
3.44
-
1129
1148
1169
1192
1218
1246
1276
1309
-
1.92
2.06
2.21
2.38
2.58
2.79
3.03
3.28
-
1. Blower performance includes 2” filters. See STATIC RESISTANCE table for additional applications.
2. See RPM SELECTION table to determine desired motor sheave setting and to determine the maximum continuous BHP.
3. kW = BHP x 0.932.
XA-12 (12.5 Ton) Bottom Duct
Air Flow
(CFM)
3200
3400
3600
3800
4000
4200
4400
4600
4800
5000
5200
5400
5600
5800
Available External Static Pressure - IWG1
0.2
0.4
0.6
0.8
1.0
1.2
1.4
1.6
1.8
2.0
RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP
757
782
810
841
874
909
946
985
1026
1069
1114
1161
1210
1260
3 HP & Field Supplied Drive
1.20
811
1.36
864
1.40
837
1.55
890
1.61
865
1.76
918
1.85
896
2.00
948
2.11
928
2.26
981
2.38
963
2.53 1016
2.68 1000 2.83 1053
3.00 1040 3.15 1092
3.33 1081 3.48 1133
3.69 1124 3.84 1177
4.06 1169 4.21 1222
4.45 1216 4.60 1268
4.86 1264 5.01 1317
5.28 1315 5.43 1367
1.50
1.69
1.91
2.14
2.40
2.68
2.98
3.29
3.63
3.98
4.35
4.74
5.15
5.57
915
941
969
999
1032
1067
1104
1143
1184
1228
1273
1319
1368
1418
1.64
1.83
2.04
2.28
2.54
2.81
3.11
3.43
3.76
4.12
4.49
4.88
5.29
5.71
964
990
1018
1049
1082
1117
1154
1193
1234
1277
1322
1369
1418
-
Standard 3 HP & Drive
1.77 1012 1.89 1059
1.96 1038 2.09 1085
2.18 1066 2.30 1113
2.41 1097 2.54 1143
2.67 1130 2.80 1176
2.95 1164 3.07 1211
3.24 1202 3.37 1248
3.56 1241 3.69 1287
3.90 1282 4.02 1328
4.25 1325 4.38 1372
4.62 1370 4.75 1417
5.01 1417 5.14 1463
5.42 1465 5.55 1512
5 HP & Field Supplied Drive
2.02
2.21
2.43
2.66
2.92
3.20
3.49
3.81
4.15
4.50
4.87
5.26
5.67
-
1104
1130
1158
1189
1222
1256
1294
1333
1374
1417
1462
1509
-
2.14
2.33
2.55
2.78
3.04
3.32
3.62
3.93
4.27
4.62
5.00
5.38
-
Hi Static 5 HP & Drive
1149 2.26 1192 2.38
1174 2.45 1218 2.58
1203 2.67 1246 2.79
1233 2.91 1276 3.03
1266 3.16 1309 3.28
1301 3.44 1344 3.56
1338 3.74 1381 3.86
1377 4.05 1420 4.18
1418 4.39 1461 4.51
1461 4.74 1505 4.87
1506 5.12 1550 5.24
1553 5.51 1596 5.63
-
1. Blower performance includes 2” filters. See STATIC RESISTANCE table for additional applications.
2. See RPM SELECTION table to determine desired motor sheave setting and to determine the maximum continuous BHP.
3. kW = BHP x 0.932.
RPM Selection
Size
(Tons)
Model
-06
(6.5)
XA
-07
(7.5)
XA
-08
(8.5)
XA
-10
(10)
XA
-12
(12.5)
XA
1.5
Max
BHP
1.73
Motor
Sheave
VL40
Blower
Sheave
AK84
6 Turns
Open
NA
5 Turns
Open
576
4 Turns
Open
618
3 Turns
Open
661
2 Turns
Open
702
1 Turn
Open
748
Fully
Closed
792
2.0
1.5
3
2
3
2
3
3
5
2.30
1.73
3.45
2.30
3.45
2.30
3.45
3.45
5.75
VL44
1VL40
1VM50
1VP50
1VP50
1VM50
1VM50
1VM50
1VP56
AK71
AK69
AK69
AK89
AK74
AK84
AK74
AK74
BK77
NA
N/A
N/A
N/A
N/A
N/A
N/A
N/A
1052
790
690
955
735
880
785
880
880
1095
843
743
1008
775
928
821
928
928
1136
887
796
1062
815
972
858
972
972
1175
936
849
1115
851
1016
901
1016
1016
1216
989
902
1168
889
1067
940
1067
1067
1272
1041
955
1221
930
1110
980
1110
1110
N/A
HP
Johnson Controls Unitary Products
31
5167825-BTG-F-0217
Additional Static Resistance
Size
(Tons)
-06 (6.5)
-07 (7.5)
-08 (8.5)
-10 (10)
-12 (12.5)
Model
CFM
Economizer1 2
4” Filter1
XA
1900
2100
2300
2500
2700
2900
3100
3300
3500
3700
3900
4100
4300
4500
4700
4900
5100
5300
5500
5700
5900
6100
6300
0.02
0.02
0.04
0.11
0.18
0.25
0.31
0.37
0.43
0.49
0.54
0.58
0.65
0.69
0.74
0.78
0.82
0.86
0.89
0.93
0.96
0.98
1.01
0.12
0.13
0.14
0.16
0.17
0.19
0.20
0.22
0.26
0.27
0.29
0.32
0.35
0.38
0.41
0.44
0.47
0.51
0.55
0.58
0.62
0.67
0.71
9
0.05
0.06
0.07
0.08
0.09
0.10
0.12
0.13
0.15
0.17
0.19
0.21
0.23
0.25
0.28
0.30
0.33
0.35
0.38
0.41
0.44
0.47
0.50
Electric Heat kW1
18
24
36
0.06
0.07
0.08
0.07
0.08
0.09
0.08
0.09
0.10
0.09
0.10
0.11
0.10
0.12
0.13
0.11
0.13
0.14
0.13
0.15
0.16
0.14
0.17
0.18
0.16
0.19
0.20
0.18
0.21
0.22
0.20
0.23
0.24
0.22
0.25
0.26
0.24
0.28
0.29
0.26
0.30
0.31
0.29
0.33
0.34
0.31
0.35
0.37
0.34
0.38
0.40
0.37
0.41
0.43
0.40
0.44
0.46
0.43
0.47
0.49
0.46
0.50
0.53
0.49
0.53
0.56
0.53
0.56
0.59
54
0.10
0.11
0.13
0.14
0.16
0.18
0.20
0.22
0.24
0.26
0.28
0.31
0.34
0.37
0.40
0.43
0.46
0.49
0.53
0.56
0.59
0.62
0.65
1. Deduct these values from the available external static pressure shown in the respective Blower Performance
Tables.
2. The pressure drop through the economizer is greater for 100% outdoor air than for 100% return air. If the
resistance of the return air duct is less than 0.25 IWG, the unit will deliver less CFM during full economizer
operation.
32
Johnson Controls Unitary Products
5167825-BTG-F-0217
Drive Selection
1.
Determine side or bottom supply duct Application.
2.
Determine desired airflow.
3.
Calculate or measure the amount of external static pressure.
4.
Using the operating point determined from steps 1, 2 & 3, locate this point on the appropriate supply air blower performance
table. (Linear interpolation may be necessary.)
5.
Noting the RPM and BHP from step 4, locate the appropriate motor and, or drive on the RPM selection table.
6.
Review the BHP compared to the motor options available. Select the appropriate motor and, or drive.
7.
Review the RPM range for the motor options available. Select the appropriate drive if multiple drives are available for the
chosen motor.
8.
Determine turns open to obtain the desired operation point.
Example
1.
2600 CFM
2.
1.6 iwg
3.
Using the supply air blower performance table below, the following data point was located: 1268 RPM & 1.95 BHP.
4.
Using the RPM selection table below, Size X and Model Y is found.
5.
1.95 BHP exceeds the maximum continuous BHP rating of the 1.5 HP motor. The 2 HP motor is required.
6.
1268 RPM is within the range of the 2 HP drives.
7.
Using the 2 HP motor and drive, .5 turns open will achieve 1268 RPM.
Airflow Performance
Example Supply Air Blower Performance
Air Flow
(CFM)
2200
2400
2600
2800
Available External Static Pressure - IWG
0.2
0.4
0.6
0.8
1.0
1.2
1.4
1.6
1.8
2.0
RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP
804
835
869
906
0.50
0.66
0.84
1.03
1.5 HP & Field Supplied Drive
866
0.71
925
0.90
982
897
0.87
956
1.06 1013
931
1.05
990
1.24 1047
968
1.25 1027 1.43 1084
1.06
1.22
1.40
1.60
1038
1069
1103
1139
Standard 1.5 HP & Drive
1.21 1092 1.35 1147
1.37 1124 1.51 1178
1.55 1158 1.69 1212
1.75 1194 1.89 1249
1.48
1.64
1.82
2.02
1203
1234
1268
1304
Alternate 2 HP & Drive
1.61 1259 1.73 1317
1.77 1290 1.90 1348
1.95 1324 2.07 1382
2.14 1361 2.27
-
1.87
2.03
2.21
-
Table X: RPM Selection
Size
(Tons)
Model
HP
X
Y
1.5
2
Max
BHP
1.73
2.30
Johnson Controls Unitary Products
Motor
Sheave
1VM50
1VM50
Blower
Sheave
AK74
AK64
6 Turns
Open
N/A
N/A
5 Turns
Open
897
1039
4 Turns
Open
945
1094
3 Turns
Open
991
1150
2 Turns
Open
1035
1207
1 Turn
Open
1079
1256
Fully
Closed
1126
1308
33
5167825-BTG-F-0217
Altitude/Temperature Correction Factors
Air
Temp.
40
50
60
70
80
90
100
0
1.060
1.039
1.019
1.000
0.982
0.964
0.946
1000
1.022
1.002
0.982
0.964
0.947
0.929
0.912
2000
0.986
0.966
0.948
0.930
0.913
0.897
0.880
3000
0.950
0.931
0.913
0.896
0.880
0.864
0.848
4000
0.916
0.898
0.880
0.864
0.848
0.833
0.817
Altitude (Ft.)
5000
0.882
0.864
0.848
0.832
0.817
0.802
0.787
6000
0.849
0.832
0.816
0.801
0.787
0.772
0.758
7000
0.818
0.802
0.787
0.772
0.758
0.744
0.730
8000
0.788
0.772
0.757
0.743
0.730
0.716
0.703
9000
0.758
0.743
0.729
0.715
0.702
0.689
0.676
10000
0.729
0.715
0.701
0.688
0.676
0.663
0.651
1.100
1.050
Correction Factor
1.000
Sea Level
0.950
1000 ft
0.900
2000 ft
0.850
3000 ft
0.800
5000 ft
0.750
6000 ft
7000 ft
4000 ft
8000 ft
0.700
9000 ft
10000 ft
0.650
0.600
40
50
60
70
80
90
100
Air Temperature (ºF)
Electric Heat Minimum Supply Air
Size
(Tons)
34
Model
-06
(6.5)
XA
-07
(7.5)
XA
-08
(8.5)
XA
-10
(10)
XA
-12
(12.5)
XA
Voltage
208/230-3-60
460-3-60
600-3-60
208/230-3-60
460-3-60
600-3-60
208/230-3-60
460-3-60
600-3-60
208/230-3-60
460-3-60
600-3-60
208/230-3-60
460-3-60
600-3-60
9
1950
1950
1950
2250
2250
2250
2550
2550
2550
-
Minimum Supply Air (CFM)
Heater kW
18
24
36
1950
1950
1950
1950
1950
1950
1950
1950
1950
2250
2250
2250
2250
2250
2250
2250
2250
2250
2550
2550
2550
2550
2550
2550
2550
2550
2550
3000
3000
3000
3000
3000
3000
3000
3000
3000
3750
3750
3750
3750
3750
3750
3750
3750
3750
54
3500
3000
3500
4000
3750
3750
Johnson Controls Unitary Products
5167825-BTG-F-0217
Indoor Blower Specifications
Motor
Size
(Tons)
Model
-06
(6.5)
-07
(7.5)
-08
(8.5)
-10
(10)
-12
(12.5)
XA
XA
XA
XA
XA
HP
RPM
Eff.
SF
Frame
1-1/2
2
1-1/2
3
2
3
2
3
3
5
1725
1725
1725
1725
1725
1725
1725
1725
1725
1725
0.8
0.8
0.8
0.8
0.8
0.8
0.8
0.8
0.8
0.87
1.15
1.15
1.15
1.15
1.15
1.15
1.15
1.15
1.15
1.15
56
56
56
56
56
56
56
56
56
184T
Motor Sheave
Datum Dia.
Bore (in.)
(in.)
2.4 - 3.4
7/8
2.8 - 3.8
7/8
2.6 - 3.6
7/8
3.6 - 4.6
7/8
3.4 - 4.4
7/8
3.4 - 4.4
7/8
3.4 - 4.4
7/8
3.4 - 4.4
7/8
3.4 - 4.4
7/8
4.3 - 5.3
1-1/8
Blower Sheave
Datum Dia.
Bore (in.)
(in.)
8.1
1
6.7
1
6.5
1
6.5
1
8.5
1
7.0
1
8.0
1
7.0
1
7.0
1
6.7
1
Model
VL40
VL44
1VL40
1VM50
1VP50
1VP50
1VM50
1VM50
1VM50
1VP56
Model
AK84
AK71
AK69
AK69
AK89
AK74
AK84
AK74
AK74
BK77
Belt
A54
A52
A52
A54
A56
A54
A56
A54
A54
BX56
Power Exhaust Specifications
Model
Voltage
2PE04703225
2PE04703246
2PE04703258
208/230-1-60
460-1-60
575-1-60
HP
3/4
3/4
3/4
Motor
RPM1
1075
1075
1050
QTY
1
1
1
Motor
FLA
5
2.2
1.5
LRA
7.8
3.4
2.9
CFM @
0.1 ESP
3800
3800
3800
Fuse Size
MCA
6.3
2.8
1.9
10
5
4
1. Motors are multi-tapped and factory wired for high speed.
Electric Heat Multipliers
Voltage
Nominal
kW Capacity Multipliers1
Applied
208
230
460
575
240
480
600
0.75
0.92
0.92
0.92
1. Electric heaters are rated at nominal voltage. Use this table to determine the electric heat
capacity for heaters applied at lower voltages.
Sound Performance
Indoor Sound Power Levels
Size
(Tons)
-06
(6.5)
-07
(7.5)
-08
(8.5)
-10
(10)
-12
(12.5)
Model
CFM
ESP
(IWG)
Blower
RPM
BHP
Sound Rating
dB (A)
1
63
Sound Power, dB (10-12) Watts
Octave Band Centerline Frequency (Hz)
125
250
500
1000
2000
4000
8000
XA
2600
0.6
812
1.14
74
71
73
73
71
69
65
65
60
XA
3000
0.6
854
1.47
77
74
76
76
74
72
68
68
63
XA
3400
0.6
872
1.65
80
77
79
79
77
75
71
71
66
XA
4000
0.6
959
2.29
83
80
82
82
80
78
74
74
69
XA
5000
0.6
1132
3.74
87
84
86
86
84
82
78
78
73
1. These values have been accessed using a model of sound propagation from a point source into the hemispheric/free field. The dBA values
provided are to be used for reference only. Calculation of dBA values cover matters of system design and the fan manufacture has no way
of knowing the details of each system. This constitutes an exception to any specification or guarantee requiring a dBA value of sound data
in any other form than sound power level ratings.
Johnson Controls Unitary Products
35
5167825-BTG-F-0217
Outdoor Sound Power Levels
Size
(Tons)
-06
(6.5)
-07
(7.5)
-08
(8.5)
-10
(10)
-12
(12.5)
Model
Sound Rating1
dB (A)
125
Octave Band Centerline Frequency (Hz)
250
500
1000
2000
4000
8000
XA
83
88.0
82.5
81.5
78.0
73.0
69.0
62.0
XA
83
89.5
83.5
82.0
78.0
72.5
68.0
60.5
XA
83
89.0
84.5
81.5
78.0
72.5
68.5
70.5
XA
83
89.5
83.5
81.0
78.0
72.0
68.5
70.5
XA
84
90.0
84.5
81.5
77.5
72.0
68.5
61.5
1. Rated in accordance with AHRI 270 standard.
36
Johnson Controls Unitary Products
5167825-BTG-F-0217
Electrical Data
XA-06 thru -12 Standard Motor - Without Powered Convenience Outlet
Size
(Tons)
Volt
Compressors
(each)
RLA LRA
MCC
OD Fan
Motors
(each)
Supply
Blower
Motor
Pwr
Exh
Motor
Pwr
Conv
Outlet
FLA
FLA
FLA
FLA
208
13.5
88.0
21.1
2.1
5.2
5.5
0.0
230
13.5
88.0
21.1
2.1
5.2
5.5
0.0
460
6.0
44.0
9.3
1.3
2.6
2.2
0.0
575
4.9
34.0
7.7
0.7
2.0
1.8
0.0
208
13.7
83.1
21.4
2.1
5.2
5.5
0.0
230
13.7
83.1
21.4
2.1
5.2
5.5
0.0
460
6.2
41.0
9.7
1.3
2.6
2.2
0.0
575
4.8
33.0
7.5
0.7
2.0
1.8
0.0
208
14.5
98.0
22.6
2.1
6.8
5.5
0.0
230
14.5
98.0
22.6
2.1
6.8
5.5
0.0
460
6.3
55.0
9.9
1.3
3.4
2.2
0.0
575
6.0
41.0
9.4
0.7
2.4
1.8
0.0
-06
(6.5)
-07
(7.5)
-08
(8.5)
Johnson Controls Unitary Products
Electric Heat Option
Model
kW
Stages
Amps
None
E09
E18
E24
E36
None
E09
E18
E24
E36
None
E09
E18
E24
E36
None
E09
E18
E24
E36
None
E09
E18
E24
E36
None
E09
E18
E24
E36
None
E09
E18
E24
E36
None
E09
E18
E24
E36
None
E09
E18
E24
E36
None
E09
E18
E24
E36
None
E09
E18
E24
E36
None
E09
E18
E24
E36
6.8
13.5
18.0
25.5
9.0
18.0
24.0
34.0
9.0
18.0
24.0
34.0
9.0
18.0
24.0
34.0
6.8
13.5
18.0
25.5
9.0
18.0
24.0
34.0
9.0
18.0
24.0
34.0
9.0
18.0
24.0
34.0
6.8
13.5
18.0
25.5
9.0
18.0
24.0
34.0
9.0
18.0
24.0
34.0
9.0
18.0
24.0
34.0
1
2
2
2
1
2
2
2
1
2
2
2
1
2
2
2
1
2
2
2
1
2
2
2
1
2
2
2
1
2
2
2
1
2
2
2
1
2
2
2
1
2
2
2
1
2
2
2
18.9
37.5
50.0
70.8
21.7
43.3
57.7
81.8
10.8
21.7
28.9
40.9
8.7
17.3
23.1
32.7
18.9
37.5
50.0
70.8
21.7
43.3
57.7
81.8
10.8
21.7
28.9
40.9
8.7
17.3
23.1
32.7
18.9
37.5
50.0
70.8
21.7
43.3
57.7
81.8
10.8
21.7
28.9
40.9
8.7
17.3
23.1
32.7
MCA1
(Amps)
MCA1
w/Pwr
Exh
(Amps)
39.8
63.4
86.6
102.2
128.3
39.8
66.8
93.9
111.9
142.0
18.6
32.2
45.7
54.7
69.7
14.3
25.2
36.0
43.2
55.2
40.2
63.8
87.1
102.7
128.7
40.2
67.3
94.4
112.4
142.5
19.1
32.6
46.1
55.2
70.2
14.1
24.9
35.8
43.0
55.0
43.6
67.2
90.5
106.1
132.1
43.6
70.7
97.8
115.8
145.9
20.1
33.6
47.2
56.2
71.2
17.2
28.0
38.9
46.1
58.1
45.3
68.9
92.1
107.7
133.8
45.3
72.3
99.4
117.4
147.5
20.8
34.4
47.9
56.9
71.9
16.1
27.0
37.8
45.0
57.0
45.7
69.3
92.6
108.2
134.2
45.7
72.8
99.9
117.9
148.0
21.3
34.8
48.3
57.4
72.4
15.9
26.7
37.6
44.8
56.8
49.1
72.7
96.0
111.6
137.6
49.1
76.2
103.3
121.3
151.4
22.3
35.8
49.4
58.4
73.4
19.0
29.8
40.7
47.9
59.9
1
Max Fuse2/ Max Fuse3 /
Breaker3 Breaker
Size w/
Size
Pwr Exh
(Amps)
(Amps)
50
50
70
70
90
100
110
110
150
150
50
50
70
80
100
100
125
125
150
150
20
25
35
35
50
50
60
60
70
80
15
20
30
30
40
40
45
45
60
60
50
50
70
70
90
100
110
110
150
150
50
50
70
80
100
100
125
125
150
150
25
25
35
35
50
50
60
60
80
80
15
20
25
30
40
40
45
45
60
60
50
60
70
80
100
100
110
125
150
150
50
60
80
80
100
110
125
125
150
175
25
25
35
40
50
50
60
60
80
80
20
25
30
30
40
45
50
50
60
60
37
5167825-BTG-F-0217
XA-06 thru -12 Standard Motor - Without Powered Convenience Outlet (Continued)
Size
(Tons)
Volt
Compressors
(each)
RLA LRA
MCC
OD Fan
Motors
(each)
Supply
Blower
Motor
Pwr
Exh
Motor
Pwr
Conv
Outlet
FLA
FLA
FLA
FLA
208
16.0 110.0 24.9
2.1
6.8
5.5
0.0
230
16.0 110.0 24.9
2.1
6.8
5.5
0.0
460
7.8
52.0
12.1
1.3
3.4
2.2
0.0
575
5.7
38.9
8.9
0.7
2.4
1.8
0.0
208
22.4 149.0 35.0
2.1
9.6
5.5
0.0
230
22.4 149.0 35.0
2.1
9.6
5.5
0.0
460
10.6
75.0
16.5
1.3
4.7
2.2
0.0
575
7.7
54.0
12.0
0.7
3.6
1.8
0.0
-10
(10)
-12
(12.5)
Electric Heat Option
MCA
(Amps)
MCA1
w/Pwr
Exh
(Amps)
47.0
93.8
109.5
135.5
149.4
47.0
101.1
119.2
149.2
149.2
23.5
50.5
59.6
74.6
74.6
16.5
38.2
45.4
57.4
57.4
68.4
115.2
130.9
156.9
156.9
68.4
122.5
140.6
170.6
170.6
33.6
60.7
69.7
84.7
84.7
23.6
45.2
52.4
64.5
64.5
52.5
99.3
115.0
141.0
156.2
52.5
106.6
124.7
154.7
154.7
25.7
52.7
61.8
76.8
76.8
18.3
40.0
47.2
59.2
59.2
73.9
120.7
136.4
162.4
162.4
73.9
128.0
146.1
176.1
176.1
35.8
62.9
71.9
86.9
86.9
25.4
47.0
54.2
66.3
66.3
1
Model
kW
Stages
Amps
None
E18
E24
E36
E54
None
E18
E24
E36
E54
None
E18
E24
E36
E54
None
E18
E24
E36
E54
None
E18
E24
E36
E54
None
E18
E24
E36
E54
None
E18
E24
E36
E54
None
E18
E24
E36
E54
13.5
18.0
25.5
40.6
18.0
24.0
34.0
54.0
18.0
24.0
34.0
54.0
18.0
24.0
34.0
54.0
13.5
18.0
25.5
40.6
18.0
24.0
34.0
54.0
18.0
24.0
34.0
54.0
18.0
24.0
34.0
54.0
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
37.5
50.0
70.8
112.7
43.3
57.7
81.8
129.9
21.7
28.9
40.9
65.0
17.3
23.1
32.7
52.0
37.5
50.0
70.8
112.7
43.3
57.7
81.8
129.9
21.7
28.9
40.9
65.0
17.3
23.1
32.7
52.0
1
Max Fuse2/ Max Fuse3 /
Breaker3 Breaker
Size w/
Size
Pwr Exh
(Amps)
(Amps)
60
60
100
100
110
125
150
150
150
175
60
60
110
110
125
125
150
175
150
175
30
30
60
60
60
70
80
80
80
80
20
20
40
40
50
50
60
60
60
60
90
90
125
125
150
150
175
175
175
175
90
90
125
150
150
150
175
200
175
200
40
45
70
70
70
80
90
90
90
90
30
30
50
50
60
60
70
70
70
70
1. Minimum Circuit Ampacity.
2. Dual Element, Time Delay Type.
3. HACR type per NEC.
38
Johnson Controls Unitary Products
5167825-BTG-F-0217
XA-06 thru -12 Hi Static Motor - Without Powered Convenience Outlet
Size
(Tons)
Volt
Compressors
(each)
RLA LRA
MCC
OD Fan
Motors
(each)
Supply
Blower
Motor
Pwr
Exh
Motor
Pwr
Conv
Outlet
FLA
FLA
FLA
FLA
208
13.5
88.0
21.1
2.1
6.8
5.5
0.0
230
13.5
88.0
21.1
2.1
6.8
5.5
0.0
460
6.0
44.0
9.3
1.3
3.4
2.2
0.0
575
4.9
34.0
7.7
0.7
2.4
1.8
0.0
208
13.7
83.1
21.4
2.1
9.6
5.5
0.0
230
13.7
83.1
21.4
2.1
9.6
5.5
0.0
460
6.2
41.0
9.7
1.3
4.7
2.2
0.0
575
4.8
33.0
7.5
0.7
3.6
1.8
0.0
208
14.5
98.0
22.6
2.1
9.6
5.5
0.0
230
14.5
98.0
22.6
2.1
9.6
5.5
0.0
460
6.3
55.0
9.9
1.3
4.7
2.2
0.0
575
6.0
41.0
9.4
0.7
3.6
1.8
0.0
-06
(6.5)
-07
(7.5)
-08
(8.5)
Johnson Controls Unitary Products
Electric Heat Option
Model
kW
None
E09
E18
E24
E36
None
E09
E18
E24
E36
None
E09
E18
E24
E36
None
E09
E18
E24
E36
None
E09
E18
E24
E36
None
E09
E18
E24
E36
None
E09
E18
E24
E36
None
E09
E18
E24
E36
None
E09
E18
E24
E36
None
E09
E18
E24
E36
None
E09
E18
E24
E36
None
E09
E18
E24
E36
6.8
13.5
18.0
25.5
9.0
18.0
24.0
34.0
9.0
18.0
24.0
34.0
9.0
18.0
24.0
34.0
6.8
13.5
18.0
25.5
9.0
18.0
24.0
34.0
9.0
18.0
24.0
34.0
9.0
18.0
24.0
34.0
6.8
13.5
18.0
25.5
9.0
18.0
24.0
34.0
9.0
18.0
24.0
34.0
9.0
18.0
24.0
34.0
MCA1
(Amps)
MCA1
w/Pwr
Exh
(Amps)
41.4
65.0
88.2
103.8
129.9
41.4
68.4
95.5
113.5
143.6
19.4
33.0
46.5
55.5
70.5
14.7
25.6
36.4
43.6
55.6
44.6
68.2
91.5
107.1
133.1
44.6
71.7
98.8
116.8
146.9
21.2
34.7
48.2
57.3
72.3
15.7
26.5
37.4
44.6
56.6
46.4
70.0
93.3
108.9
134.9
46.4
73.5
100.6
118.6
148.7
21.4
34.9
48.5
57.5
72.5
18.4
29.2
40.1
47.3
59.3
46.9
70.5
93.7
109.3
135.4
46.9
73.9
101.0
119.0
149.1
21.6
35.2
48.7
57.7
72.7
16.5
27.4
38.2
45.4
57.4
50.1
73.7
97.0
112.6
138.6
50.1
77.2
104.3
122.3
152.4
23.4
36.9
50.4
59.5
74.5
17.5
28.3
39.2
46.4
58.4
51.9
75.5
98.8
114.4
140.4
51.9
79.0
106.1
124.1
154.2
23.6
37.1
50.7
59.7
74.7
20.2
31.0
41.9
49.1
61.1
Stages Amps
1
2
2
2
1
2
2
2
1
2
2
2
1
2
2
2
1
2
2
2
1
2
2
2
1
2
2
2
1
2
2
2
1
2
2
2
1
2
2
2
1
2
2
2
1
2
2
2
18.9
37.5
50.0
70.8
21.7
43.3
57.7
81.8
10.8
21.7
28.9
40.9
8.7
17.3
23.1
32.7
18.9
37.5
50.0
70.8
21.7
43.3
57.7
81.8
10.8
21.7
28.9
40.9
8.7
17.3
23.1
32.7
18.9
37.5
50.0
70.8
21.7
43.3
57.7
81.8
10.8
21.7
28.9
40.9
8.7
17.3
23.1
32.7
2
Max Fuse2/ Max Fuse3 /
Breaker
Breaker3
Size w/ Pwr
Size
Exh
(Amps)
(Amps)
50
60
70
80
90
100
110
110
150
150
50
60
70
80
100
110
125
125
150
150
25
25
35
40
50
50
60
60
80
80
15
20
30
30
40
40
45
50
60
60
50
60
70
80
100
100
110
125
150
150
50
60
80
80
100
110
125
125
150
175
25
25
35
40
50
60
60
60
80
80
20
20
30
30
40
40
45
50
60
60
60
60
70
80
100
100
110
125
150
150
60
60
80
80
110
110
125
125
150
175
25
25
35
40
50
60
60
60
80
80
20
25
30
35
45
45
50
50
60
70
39
5167825-BTG-F-0217
XA-06 thru -12 Hi Static Motor - Without Powered Convenience Outlet (Continued)
Size
(Tons)
Volt
Compressors
(each)
RLA LRA
MCC
OD Fan
Motors
(each)
Supply
Blower
Motor
Pwr
Exh
Motor
Pwr
Conv
Outlet
FLA
FLA
FLA
FLA
208
16.0 110.0 24.9
2.1
9.6
5.5
0.0
230
16.0 110.0 24.9
2.1
9.6
5.5
0.0
460
7.8
52.0
12.1
1.3
4.7
2.2
0.0
575
5.7
38.9
8.9
0.7
3.6
1.8
0.0
208
22.4 149.0 35.0
2.1
14.0
5.5
0.0
230
22.4 149.0 35.0
2.1
14.0
5.5
0.0
460
10.6
75.0
16.5
1.3
6.6
2.2
0.0
575
7.7
54.0
12.0
0.7
5.2
1.8
0.0
-10
(10)
-12
(12.5)
Electric Heat Option
Model
kW
None
E18
E24
E36
E54
None
E18
E24
E36
E54
None
E18
E24
E36
E54
None
E18
E24
E36
E54
None
E18
E24
E36
E54
None
E18
E24
E36
E54
None
E18
E24
E36
E54
None
E18
E24
E36
E54
13.5
18.0
25.5
40.6
18.0
24.0
34.0
54.0
18.0
24.0
34.0
54.0
18.0
24.0
34.0
54.0
13.5
18.0
25.5
40.6
18.0
24.0
34.0
54.0
18.0
24.0
34.0
54.0
18.0
24.0
34.0
54.0
MCA
(Amps)
MCA1
w/Pwr
Exh
(Amps)
49.8
96.6
112.3
138.3
152.9
49.8
103.9
122.0
152.0
152.0
24.8
51.8
60.9
75.9
75.9
17.7
39.4
46.6
58.6
58.6
72.8
119.6
135.3
161.3
161.3
72.8
126.9
145.0
175.0
175.0
35.5
62.6
71.6
86.6
86.6
25.2
46.8
54.0
66.1
66.1
55.3
102.1
117.8
143.8
159.7
55.3
109.4
127.5
157.5
157.5
27.0
54.0
63.1
78.1
78.1
19.5
41.2
48.4
60.4
60.4
78.3
125.1
140.8
166.8
166.8
78.3
132.4
150.5
180.5
180.5
37.7
64.8
73.8
88.8
88.8
27.0
48.6
55.8
67.9
67.9
1
Stages Amps
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
37.5
50.0
70.8
112.7
43.3
57.7
81.8
129.9
21.7
28.9
40.9
65.0
17.3
23.1
32.7
52.0
37.5
50.0
70.8
112.7
43.3
57.7
81.8
129.9
21.7
28.9
40.9
65.0
17.3
23.1
32.7
52.0
2
Max Fuse2/ Max Fuse3 /
Breaker
3
Breaker
Size w/ Pwr
Size
Exh
(Amps)
(Amps)
60
70
100
110
125
125
150
150
175
175
60
70
110
110
125
150
175
175
175
175
30
30
60
60
70
70
80
80
80
80
20
25
40
45
50
50
60
70
60
70
90
100
125
150
150
150
175
175
175
175
90
100
150
150
150
175
175
200
175
200
45
45
70
70
80
80
90
90
90
90
30
30
50
50
60
60
70
70
70
70
1. Minimum Circuit Ampacity.
2. Dual Element, Time Delay Type.
3. HACR type per NEC.
40
Johnson Controls Unitary Products
5167825-BTG-F-0217
XA-06 thru -12 Standard Motor - With Powered Convenience Outlet
Size
(Tons)
Volt
Compressors
(each)
RLA LRA
MCC
OD Fan
Motors
(each)
Supply
Blower
Motor
Pwr
Exh
Motor
Pwr
Conv
Outlet
FLA
FLA
FLA
FLA
208
13.5
88.0
21.1
2.1
5.2
5.5
10.0
230
13.5
88.0
21.1
2.1
5.2
5.5
10.0
460
6.0
44.0
9.3
1.3
2.6
2.2
5.0
575
4.9
34.0
7.7
0.7
2.0
1.8
4.0
208
13.7
83.1
21.4
2.1
5.2
5.5
10.0
230
13.7
83.1
21.4
2.1
5.2
5.5
10.0
460
6.2
41.0
9.7
1.3
2.6
2.2
5.0
575
4.8
33.0
7.5
0.7
2.0
1.8
4.0
208
14.5
98.0
22.6
2.1
6.8
5.5
10.0
230
14.5
98.0
22.6
2.1
6.8
5.5
10.0
460
6.3
55.0
9.9
1.3
3.4
2.2
5.0
575
6.0
41.0
9.4
0.7
2.4
1.8
4.0
-06
(6.5)
-07
(7.5)
-08
(8.5)
Johnson Controls Unitary Products
Electric Heat Option
Model
kW
None
E09
E18
E24
E36
None
E09
E18
E24
E36
None
E09
E18
E24
E36
None
E09
E18
E24
E36
None
E09
E18
E24
E36
None
E09
E18
E24
E36
None
E09
E18
E24
E36
None
E09
E18
E24
E36
None
E09
E18
E24
E36
None
E09
E18
E24
E36
None
E09
E18
E24
E36
None
E09
E18
E24
E36
6.8
13.5
18.0
25.5
9.0
18.0
24.0
34.0
9.0
18.0
24.0
34.0
9.0
18.0
24.0
34.0
6.8
13.5
18.0
25.5
9.0
18.0
24.0
34.0
9.0
18.0
24.0
34.0
9.0
18.0
24.0
34.0
6.8
13.5
18.0
25.5
9.0
18.0
24.0
34.0
9.0
18.0
24.0
34.0
9.0
18.0
24.0
34.0
MCA1
(Amps)
MCA1
w/Pwr
Exh
(Amps)
49.8
73.4
96.6
112.2
138.3
49.8
76.8
103.9
121.9
152.0
23.6
37.2
50.7
59.7
74.7
18.3
29.2
40.0
47.2
59.2
50.2
73.8
97.1
112.7
138.7
50.2
77.3
104.4
122.4
152.5
24.1
37.6
51.1
60.2
75.2
18.1
28.9
39.8
47.0
59.0
53.6
77.2
100.5
116.1
142.1
53.6
80.7
107.8
125.8
155.9
25.1
38.6
52.2
61.2
76.2
21.2
32.0
42.9
50.1
62.1
55.3
78.9
102.1
117.7
143.8
55.3
82.3
109.4
127.4
157.5
25.8
39.4
52.9
61.9
76.9
20.1
31.0
41.8
49.0
61.0
55.7
79.3
102.6
118.2
144.2
55.7
82.8
109.9
127.9
158.0
26.3
39.8
53.3
62.4
77.4
19.9
30.7
41.6
48.8
60.8
59.1
82.7
106.0
121.6
147.6
59.1
86.2
113.3
131.3
161.4
27.3
40.8
54.4
63.4
78.4
23.0
33.8
44.7
51.9
63.9
Stages Amps
1
2
2
2
1
2
2
2
1
2
2
2
1
2
2
2
1
2
2
2
1
2
2
2
1
2
2
2
1
2
2
2
1
2
2
2
1
2
2
2
1
2
2
2
1
2
2
2
18.9
37.5
50.0
70.8
21.7
43.3
57.7
81.8
10.8
21.7
28.9
40.9
8.7
17.3
23.1
32.7
18.9
37.5
50.0
70.8
21.7
43.3
57.7
81.8
10.8
21.7
28.9
40.9
8.7
17.3
23.1
32.7
18.9
37.5
50.0
70.8
21.7
43.3
57.7
81.8
10.8
21.7
28.9
40.9
8.7
17.3
23.1
32.7
2
Max Fuse2/ Max Fuse3 /
Breaker
Breaker3
Size w/ Pwr
Size
Exh
(Amps)
(Amps)
60
60
80
80
100
110
125
125
150
150
60
60
80
90
110
110
125
150
175
175
25
30
40
40
60
60
60
70
80
80
20
25
30
35
40
45
50
50
60
70
60
60
80
80
100
110
125
125
150
150
60
60
80
90
110
110
125
150
175
175
30
30
40
40
60
60
70
70
80
80
20
20
30
35
40
45
50
50
60
70
60
70
80
90
110
110
125
125
150
150
60
70
90
90
110
125
150
150
175
175
30
30
40
45
60
60
70
70
80
80
25
25
35
35
45
45
60
60
70
70
41
5167825-BTG-F-0217
XA-06 thru -12 Standard Motor - With Powered Convenience Outlet (Continued)
Size
(Tons)
Volt
Compressors
(each)
RLA LRA
MCC
OD Fan
Motors
(each)
Supply
Blower
Motor
Pwr
Exh
Motor
Pwr
Conv
Outlet
FLA
FLA
FLA
FLA
208
16.0 110.0 24.9
2.1
6.8
5.5
10.0
230
16.0 110.0 24.9
2.1
6.8
5.5
10.0
460
7.8
52.0
12.1
1.3
3.4
2.2
5.0
575
5.7
38.9
8.9
0.7
2.4
1.8
4.0
208
22.4 149.0 35.0
2.1
9.6
5.5
10.0
230
22.4 149.0 35.0
2.1
9.6
5.5
10.0
460
10.6
75.0
16.5
1.3
4.7
2.2
5.0
575
7.7
54.0
12.0
0.7
3.6
1.8
4.0
-10
(10)
-12
(12.5)
Electric Heat Option
Model
kW
None
E18
E24
E36
E54
None
E18
E24
E36
E54
None
E18
E24
E36
E54
None
E18
E24
E36
E54
None
E18
E24
E36
E54
None
E18
E24
E36
E54
None
E18
E24
E36
E54
None
E18
E24
E36
E54
13.5
18.0
25.5
40.6
18.0
24.0
34.0
54.0
18.0
24.0
34.0
54.0
18.0
24.0
34.0
54.0
13.5
18.0
25.5
40.6
18.0
24.0
34.0
54.0
18.0
24.0
34.0
54.0
18.0
24.0
34.0
54.0
MCA
(Amps)
MCA1
w/Pwr
Exh
(Amps)
57.0
103.8
119.5
145.5
161.9
57.0
111.1
129.2
159.2
159.2
28.5
55.5
64.6
79.6
79.6
20.5
42.2
49.4
61.4
61.4
78.4
125.2
140.9
166.9
166.9
78.4
132.5
150.6
180.6
180.6
38.6
65.7
74.7
89.7
89.7
27.6
49.2
56.4
68.5
68.5
62.5
109.3
125.0
151.0
168.7
62.5
116.6
134.7
164.7
164.7
30.7
57.7
66.8
81.8
81.8
22.3
44.0
51.2
63.2
63.2
83.9
130.7
146.4
172.4
172.4
83.9
138.0
156.1
186.1
186.1
40.8
67.9
76.9
91.9
91.9
29.4
51.0
58.2
70.3
70.3
1
Stages Amps
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
37.5
50.0
70.8
112.7
43.3
57.7
81.8
129.9
21.7
28.9
40.9
65.0
17.3
23.1
32.7
52.0
37.5
50.0
70.8
112.7
43.3
57.7
81.8
129.9
21.7
28.9
40.9
65.0
17.3
23.1
32.7
52.0
2
Max Fuse2/ Max Fuse3 /
Breaker
3
Breaker
Size w/ Pwr
Size
Exh
(Amps)
(Amps)
70
70
110
110
125
125
150
175
175
175
70
70
125
125
150
150
175
175
175
175
35
35
60
60
70
70
80
90
80
90
25
25
45
45
50
60
70
70
70
70
100
100
150
150
150
150
175
175
175
175
100
100
150
150
175
175
200
200
200
200
45
50
70
70
80
80
90
100
90
100
35
35
50
60
60
60
70
80
70
80
1. Minimum Circuit Ampacity.
2. Dual Element, Time Delay Type.
3. HACR type per NEC.
42
Johnson Controls Unitary Products
5167825-BTG-F-0217
XA-06 thru -12 Hi Static Motor - With Powered Convenience Outlet
Size
(Tons)
Volt
Compressors
(each)
RLA LRA
MCC
OD Fan
Motors
(each)
Supply
Blower
Motor
Pwr
Exh
Motor
Pwr
Conv
Outlet
FLA
FLA
FLA
FLA
208
13.5
88.0
21.1
2.1
6.8
5.5
10.0
230
13.5
88.0
21.1
2.1
6.8
5.5
10.0
460
6.0
44.0
9.3
1.3
3.4
2.2
5.0
575
4.9
34.0
7.7
0.7
2.4
1.8
4.0
208
13.7
83.1
21.4
2.1
9.6
5.5
10.0
230
13.7
83.1
21.4
2.1
9.6
5.5
10.0
460
6.2
41.0
9.7
1.3
4.7
2.2
5.0
575
4.8
33.0
7.5
0.7
3.6
1.8
4.0
208
14.5
98.0
22.6
2.1
9.6
5.5
10.0
230
14.5
98.0
22.6
2.1
9.6
5.5
10.0
460
6.3
55.0
9.9
1.3
4.7
2.2
5.0
575
6.0
41.0
9.4
0.7
3.6
1.8
4.0
-06
(6.5)
-07
(7.5)
-08
(8.5)
Johnson Controls Unitary Products
Electric Heat Option
Model
kW
None
E09
E18
E24
E36
None
E09
E18
E24
E36
None
E09
E18
E24
E36
None
E09
E18
E24
E36
None
E09
E18
E24
E36
None
E09
E18
E24
E36
None
E09
E18
E24
E36
None
E09
E18
E24
E36
None
E09
E18
E24
E36
None
E09
E18
E24
E36
None
E09
E18
E24
E36
None
E09
E18
E24
E36
6.8
13.5
18.0
25.5
9.0
18.0
24.0
34.0
9.0
18.0
24.0
34.0
9.0
18.0
24.0
34.0
6.8
13.5
18.0
25.5
9.0
18.0
24.0
34.0
9.0
18.0
24.0
34.0
9.0
18.0
24.0
34.0
6.8
13.5
18.0
25.5
9.0
18.0
24.0
34.0
9.0
18.0
24.0
34.0
9.0
18.0
24.0
34.0
MCA1
(Amps)
MCA1
w/Pwr
Exh
(Amps)
51.4
75.0
98.2
113.8
139.9
51.4
78.4
105.5
123.5
153.6
24.4
38.0
51.5
60.5
75.5
18.7
29.6
40.4
47.6
59.6
54.6
78.2
101.5
117.1
143.1
54.6
81.7
108.8
126.8
156.9
26.2
39.7
53.2
62.3
77.3
19.7
30.5
41.4
48.6
60.6
56.4
80.0
103.3
118.9
144.9
56.4
83.5
110.6
128.6
158.7
26.4
39.9
53.5
62.5
77.5
22.4
33.2
44.1
51.3
63.3
56.9
80.5
103.7
119.3
145.4
56.9
83.9
111.0
129.0
159.1
26.6
40.2
53.7
62.7
77.7
20.5
31.4
42.2
49.4
61.4
60.1
83.7
107.0
122.6
148.6
60.1
87.2
114.3
132.3
162.4
28.4
41.9
55.4
64.5
79.5
21.5
32.3
43.2
50.4
62.4
61.9
85.5
108.8
124.4
150.4
61.9
89.0
116.1
134.1
164.2
28.6
42.1
55.7
64.7
79.7
24.2
35.0
45.9
53.1
65.1
Stages Amps
1
2
2
2
1
2
2
2
1
2
2
2
1
2
2
2
1
2
2
2
1
2
2
2
1
2
2
2
1
2
2
2
1
2
2
2
1
2
2
2
1
2
2
2
1
2
2
2
18.9
37.5
50.0
70.8
21.7
43.3
57.7
81.8
10.8
21.7
28.9
40.9
8.7
17.3
23.1
32.7
18.9
37.5
50.0
70.8
21.7
43.3
57.7
81.8
10.8
21.7
28.9
40.9
8.7
17.3
23.1
32.7
18.9
37.5
50.0
70.8
21.7
43.3
57.7
81.8
10.8
21.7
28.9
40.9
8.7
17.3
23.1
32.7
2
Max Fuse2/ Max Fuse3 /
Breaker
Breaker3
Size w/ Pwr
Size
Exh
(Amps)
(Amps)
60
70
80
90
100
110
125
125
150
150
60
70
80
90
110
125
125
150
175
175
30
30
40
45
60
60
70
70
80
80
20
25
30
35
45
45
50
50
60
70
60
70
80
90
110
110
125
125
150
150
60
70
90
90
110
125
150
150
175
175
30
30
40
45
60
60
70
70
80
80
20
25
35
35
45
45
50
60
70
70
70
70
80
90
110
110
125
125
150
175
70
70
90
90
125
125
150
150
175
175
30
30
40
45
60
60
70
70
80
80
25
30
35
35
45
50
60
60
70
70
43
5167825-BTG-F-0217
XA-06 thru -12 Hi Static Motor - With Powered Convenience Outlet (Continued)
Size
(Tons)
Volt
Compressors
(each)
RLA LRA
MCC
OD Fan
Motors
(each)
Supply
Blower
Motor
Pwr
Exh
Motor
Pwr
Conv
Outlet
FLA
FLA
FLA
FLA
208
16.0 110.0 24.9
2.1
9.6
5.5
10.0
230
16.0 110.0 24.9
2.1
9.6
5.5
10.0
460
7.8
52.0
12.1
1.3
4.7
2.2
5.0
575
5.7
38.9
8.9
0.7
3.6
1.8
4.0
208
22.4 149.0 35.0
2.1
14.0
5.5
10.0
230
22.4 149.0 35.0
2.1
14.0
5.5
10.0
460
10.6
75.0
16.5
1.3
6.6
2.2
5.0
575
7.7
54.0
12.0
0.7
5.2
1.8
4.0
-10
(10)
-12
(12.5)
Electric Heat Option
Model
kW
None
E18
E24
E36
E54
None
E18
E24
E36
E54
None
E18
E24
E36
E54
None
E18
E24
E36
E54
None
E18
E24
E36
E54
None
E18
E24
E36
E54
None
E18
E24
E36
E54
None
E18
E24
E36
E54
13.5
18.0
25.5
40.6
18.0
24.0
34.0
54.0
18.0
24.0
34.0
54.0
18.0
24.0
34.0
54.0
13.5
18.0
25.5
40.6
18.0
24.0
34.0
54.0
18.0
24.0
34.0
54.0
18.0
24.0
34.0
54.0
MCA
(Amps)
MCA1
w/Pwr
Exh
(Amps)
59.8
106.6
122.3
148.3
165.4
59.8
113.9
132.0
162.0
162.0
29.8
56.8
65.9
80.9
80.9
21.7
43.4
50.6
62.6
62.6
82.8
129.6
145.3
171.3
171.3
82.8
136.9
155.0
185.0
185.0
40.5
67.6
76.6
91.6
91.6
29.2
50.8
58.0
70.1
70.1
65.3
112.1
127.8
153.8
172.2
65.3
119.4
137.5
167.5
167.5
32.0
59.0
68.1
83.1
83.1
23.5
45.2
52.4
64.4
64.4
88.3
135.1
150.8
176.8
177.7
88.3
142.4
160.5
190.5
190.5
42.7
69.8
78.8
93.8
93.8
31.0
52.6
59.8
71.9
71.9
1
Stages Amps
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
37.5
50.0
70.8
112.7
43.3
57.7
81.8
129.9
21.7
28.9
40.9
65.0
17.3
23.1
32.7
52.0
37.5
50.0
70.8
112.7
43.3
57.7
81.8
129.9
21.7
28.9
40.9
65.0
17.3
23.1
32.7
52.0
2
Max Fuse2/ Max Fuse3 /
Breaker
3
Breaker
Size w/ Pwr
Size
Exh
(Amps)
(Amps)
70
80
110
125
125
150
150
175
175
175
70
80
125
125
150
150
175
175
175
175
35
35
60
60
70
70
90
90
90
90
25
25
45
50
60
60
70
70
70
70
100
110
150
150
150
175
175
200
175
200
100
110
150
150
175
175
200
200
200
200
50
50
70
70
80
80
100
100
100
100
35
35
60
60
60
60
80
80
80
80
1. Minimum Circuit Ampacity.
2. Dual Element, Time Delay Type.
3. HACR type per NEC.
44
Johnson Controls Unitary Products
5167825-BTG-F-0217
Typical Wiring Diagrams
XA-06 thru -12 Typical Wiring Diagrams
Typical XA-06 thru-10 Heat Pump with/without Electric Heat Wiring Diagram
Johnson Controls Unitary Products
45
5167825-BTG-F-0217
Typical XA-06 thru-10 Heat Pump with/without Electric Heat Unit (Options)
46
Johnson Controls Unitary Products
5167825-BTG-F-0217
Typical XA-12 Heat Pump with/without Electric Heat Wiring Diagram
Johnson Controls Unitary Products
47
5167825-BTG-F-0217
Typical XA-12 Heat Pump with/without Electric Heat Unit (Options)
48
Johnson Controls Unitary Products
5167825-BTG-F-0217
BAS Controls Typical Wiring Diagrams
Typical SURVEYOR BAS Control Wiring Diagram
Johnson Controls Unitary Products
49
5167825-BTG-F-0217
Typical CPC BAS Control Wiring Diagram
50
Johnson Controls Unitary Products
5167825-BTG-F-0217
Typical HONEYWELL BAS Control Wiring Diagram
Johnson Controls Unitary Products
51
5167825-BTG-F-0217
Typical NOVAR BAS Control Wiring Diagram
52
Johnson Controls Unitary Products
5167825-BTG-F-0217
Weights and Dimensions
XA-06 thru -12 Unit Weights
Unit 4 Point Load Weight
Unit 6 Point Load Weight
FRONT
FRONT
LEFT
LEFT
B
C
B
A
A
D
C
E
F
D
Y
X
FRONT
LEFT
Weight (lbs.)
Center of Gravity
Size
Model
Shipping Operating
X
Y
(Tons)
-06
XA
1085
1080
38
25
(6.5)
-07
XA
1095
1090
38
23
(7.5)
-08
XA
1142
1137
38
25.5
(8.5)
-10
XA
1140
1135
38
25.5
(10)
-12
XA
1408
1403
51
25.5
(12.5)
4 Point Load Location (lbs.)
A
B
C
D
A
6 Point Load Location (lbs.)
B
C
D
E
F
262
195
266
357
184
150
124
169
204
250
243
181
284
381
171
139
115
181
217
267
282
210
276
370
197
161
133
175
211
259
281
209
275
369
197
160
133
175
211
259
259
347
456
340
165
198
244
320
260
216
XA-06 thru -12 Unit Accessory Weights
Unit Accessory
Economizer
Power Exhaust
Electric Heat1
Weight (lbs.)
Shipping
Operating
90
85
40
35
49
49
1. Weight given is for the maximum heater size available
(54KW).
Johnson Controls Unitary Products
53
5167825-BTG-F-0217
XA-06 thru -12 Unit Dimensions
XP078-120
See detail A for drain location
XA-12
See detail A for drain location
54
Johnson Controls Unitary Products
5167825-BTG-F-0217
XA-06 thru -12 Unit Physical Dimensions
Unit Model Number
078
090
102
120
150
A
50 3/4
50 3/4
50 3/4
50 3/4
50 3/4
B
89
89
89
89
119 1/2
Dimension (in.)
C
D
30 3/16
24 3/16
30 3/16
24 3/16
30 3/16
24 3/16
30 3/16
24 3/16
30 3/16
24 3/16
E
17 3/16
17 3/16
17 3/16
17 3/16
17 3/16
F
6 3/16
6 3/16
6 3/16
6 3/16
6 3/16
Detail A
5-3/8
3/4” FPT
XA-06 thru -12 Unit Clearances
Direction
Top1
Front
Rear
Distance (in.)
72
36
36
Direction
Right
Left
Bottom2
Distance (in.)
12
36
0
1. Units must be installed outdoors. Over hanging structure or shrubs should not obscure condenser air discharge outlet.
2. Units may be installed on combustible floors made from wood or class A, B or C roof covering materials.
XA-06 thru -12 Unit Bottom Duct Openings
Johnson Controls Unitary Products
55
5167825-BTG-F-0217
XA-06 thru -12 Unit Electrical Entry
Disconnect Swith Cover
Power Entry Ø 2-1/2
Control Entry Ø 7/8
Power Entry Ø 2-1/2
Convenience Outlet Cover
Convenience Outlet
Power Entry Ø 7/8
FRONT
XA-06 thru -12 Unit Side Duct Openings
18-1/4
Dot Plugs
A
Return
Air
Supply
Air
D
B
2-31/32
5-5/32
C
31-11/16
56
Johnson Controls Unitary Products
5167825-BTG-F-0217
XA-12 Unit Side Duct Openings
Dot Plugs
18-1/4
A
D
B
5-5/32
2-7/8
C
31-5/8
Side Duct Dimensions
Unit Model Number
-06
-07
-08
-10
-12
A
28 1/4
28 1/4
28 1/4
28 1/4
28 1/4
Dimension (in.)
B
C
18 1/16
28 1/4
18 1/16
28 1/4
18 1/16
28 1/4
18 1/16
28 1/4
18 1/16
28 1/4
D
18 1/4
18 1/4
18 1/4
18 1/4
18 1/4
XA-06 thru -12 Unit Left Duct Opening
30-3/8
4-5/16
Johnson Controls Unitary Products
57
5167825-BTG-F-0217
XA-06 thru -12 Unit Accessory Dimensions
XA-06 thru -12 Roof Curb
RIGHT
80-5/8
INSULATED DECK UNDER
CONDENSER SECTION
20
SUPPLY
20
6
RETURN
2 TYP.
30
INSULATED DECK UNDER
COMPRESSOR SECTION
50-1/2
FRONT
8 or 14
XA-06 thru -12 Transition Roof Curb
2 TYP
50-1/2
30-1/2
23 4
80-5/8
26
RETURN
SUPPLY
10
76-5/8
94
FRONT
58
59-1/4
64-1/4
RIGHT
Johnson Controls Unitary Products
5167825-BTG-F-0217
XA-06 thru -12 Roof Curb Cut Away
3/4” X 1-1/4” WIDE GASKETING FOR CURB
FRAME AND ALL DUCT SUPPORT SURFACES
2“
UNIT BASE
3.75”
WOOD NAILER
3.56”
UNIT BASE RAILS
14”
8“ MIN. ABOVE FINISHED ROOF
CURB FRAME
COUNTERFLASHING
CAN’T STRIP
INSULATION AND ROOFING MATERIAL
INSULATION
ROOF DECK AND SUPPORT STRUCTURE
Johnson Controls Unitary Products
59
5167825-BTG-F-0217
Economizer Options
Economizer Usage
Application
Cabinet Height
Description
Model
Side Return
All
Horizontal economizer without barometric relief
2EE047069241
Downflow, End Return
Horizontal or ERV
42"
Economizer, 42” tall cabinet
2EE047074242
50"
Economizer, 50” tall cabinet
2EE047076242
1. Barometric relief must be ordered separately and installed in duct work.
2. Includes fresh air hood, exhaust hood and barometric relief.
Economizer Downflow W/Power Exhaust
Fresh Air Hood
Low Leak Economizer
Power Exhaust
Barometric
Relief Damper
60
Barometric Relief
Hood
Johnson Controls Unitary Products
Economizer End Return W/Power Exhaust
Fresh Air Hood
Field Installed
Duct Work
Low Leak
Economizer
Power Exhaust
Barometric Relief Damper
Barometric Relief Hood
Field Installed Horizontal Economizer W/Power Exhaust
Return Air Damper
Field Installed
Duct Work
Fresh Air Damper
Power Exhaust
Barometric
Relief Damper
Barometric
Relief Hood
Subject to change without notice. Printed in U.S.A.
Copyright © 2017 by Johnson Controls, Inc. All rights reserved.
York International Corporation
5005 York Drive
Norman, OK 73069
Fresh Air Hood
5167825-BTG-F-0217
Supersedes: 5167825-BTG-E-0516