air handling - WESPER, Heating,Ventilation and Air Conditioning

Wesper
Experts in air conditioning
Experts in air handling
A global service
Since 1948
- Integrated department of engineers and specialists for a personalised
service of technical and project advice
- Integrated R&D department
- Own production facilities
- Customer service
- Aftersales service
Founded in 1948, Wesper is a French manufacturer setting
the standards in the design, development and production of air
conditioning and air handling systems for residential, commercial,
industrial and service sector applications.
The company has the largest capacity production site in all of
Europe, covering 55.000 m2 and located in Pons, France, where the
company manufactures water chillers, terminal units, air handling
units and rooftop units.
CUSTOMER SERVICE
+33 (0)1 82 88 94 47
July 2014
france@wesper.com
Wesper enters a new stage after its acquisition by the Hitecsa
Group, a European leader in the design, manufacture and
instruction of air conditioning equipment. The Hitecsa Group's
offices and 10.000 m2 production site are located in Vilanova i la
Geltrù, Barcelona (Spain) for the manufacture of air conditioning
units. It also has another production site at Arenys de Mar,
Barcelona, where it manufactures high-efficiency boilers.
AFTERSALES
+33 (0)5 46 92 33 52
sav@wesper.com
NORD-PASDE-CALAIS
HAUTENORMANDIE
PICARDIE
BASSENORMANDIE
ILE-DE-FRANCE
BRETAGNE
CHAMPAGNEARDENNE
LORRAINE
PAYS-DELOIRE
CENTRE
BOURGOGNE
Production site
at Pons (France)
FRANCHECOMTE
POITOUCHARENTE
LIMOUSIN
Pons
RHÔNESALPES
AUVERGNE
AQUITAINE
MIDIPYRENEES
ASTURIAS
CANTABRIA
LANGUEDOCROUSSILLON
PAÍS VASCO
GALICIA
PROVENCE-ALPESCÔTE-D'AZUR
Production site
at Arenys de Mar (Spain)
NAVARRA
LA RIOJA
CASTILLA Y LEÓN
CATALUÑA
ARAGÓN
Arenys de Mar
Vilanova i la Geltrú
MADRID
BALEARES
CASTILLA-LA MANCHA
VALENCIA
EXTREMADURA
Production site
at Vilanova i la Geltrú (Spain)
MURCIA
ANDALUCÍA
1
Values
Effective services
for lasting quality
Innovation and Quality
In order to respond to the questions that our clients might ask us,
from how to install our equipment to commissioning and aftersales
servicing, Wesper has set up quality services.
User satisfaction and being able to meet all of their expectations
with regard to our products is our top priority. With this in mind,
Wesper is committed to continuously improving our service to
professional customers, an approach which is structured around
three fundamental priorities: training, spare parts and technical
support.
Expertise
More than 60 years of experience in the design, development and
production of residential, commercial and industrial applications
make Wesper a major European player in this market. There are
numerous job references from both French and international
customers from all sectors, including several hospitals (operating
theatres, cleanrooms), industrial sites, high energy performance
office buildings, hotels and also onboard naval applications. Our
sales department will gladly present our job references according to
your specific needs.
OFFICES
SERVICES
HOTELS
HOSPITALS
INDUSTRY
Versatility
Speed
Support
Flexibility
Quality
Industrial capacity
NAVAL
Innovation and Quality are the most important elements of the Wesper
philosophy. The Group dedicates all of its energy to the continuous
development of innovative products intended for our customers, to
guarantee our position in the market.
Every day more than 130 people devote themselves to researching
products, concentrating in particular on improving energy efficiency
and reducing noise levels.
Certifications
The Group's factories are ISO 9001 certified, awarded by well known
certification bodies. Furthermore, Wesper participates in the Eurovent
certification programme, which uses independent laboratories to
ensure verification of technical specifications in accordance with
international standards.
View the certified products and models on the Eurovent website.
Technology and environment
Innovation only makes sense when it respects the environment. The
women and men of Wesper make a point of designing, industrialising
and selling products that are ever closer to users' aspirations all while
respecting our environment. We research the balance between
technology and ecology for each of our products while complying
with the maximum demands in terms of quality and environmental
friendliness. In accordance with this principle and European directives,
Wesper uses environmentally friendly HFC (hydrofluorocarbon) type
refrigerants that do not harm the ozone layer in all of its equipment.
Moreover, Wesper designs and sells energy efficient equipment,
thereby limiting CO2 emissions into the atmosphere.
2
GENERAL
SUMMARY
3
GENERAL SUMMARY
LIQUID CHILLERS
7
AIR-COOLED TYPE
MICRO ADVANCE
10
MINI KRONO 2
12
KRONO XA / KRONO XBA
14
KRONO CZ / KRONO CBZ
16
EQPLU
18
EQPL
20
EQPH
24
EQPLA
28
EQSL
34
EQSLA
38
EQSH
42
EQUL
46
EQUL PF
50
EQUH
54
EQUH PF
60
AIR-COOLED TYPE WITH FREE COOLING
EQMF
64
EQMF PF
70
EQEF
74
EQSFA
78
WATER-COOLED TYPE
EWNL
83
EWNH
86
EWNL RC
88
EWNH RC
89
EWML
90
EWMH
96
EWML RC
101
EWMH RC
102
EWSL K
103
EWSL A
105
EWSL A+
107
CHILLED WATER TERMINAL UNITS
109
FAN COIL
110
FCW / FCCW
4-WAY CASSETTE
114
FKW / FKWS
WALL MOUNTED
FPW
116
DUCTABLE
BHW
117
BSW
118
EHW
121
CLW
123
AIR HANDLING
125
AIR HANDLING UNITS
WESPAK 1.39 to 3.99
128
SLIM@IR 0303 to 0318
130
EFF@IR CFI EC
132
EFF@IR HP
136
EFF@IR WRI EC
138
PREMI@IR DOUBLE DECK COMPACT
140
PREMI@IR 20 à 360
142
@IRTWIN 20 to 360
144
@IRTWIN 400 to 1000
146
WINCLIM II and III
148
RCAH
149
4
AIR-COOLED CONDENSERS
151
ACCL - ACCH
152
ACCL PF - ACCH PF
156
DRY COOLERS
160
DC
161
DC PF
163
UNIT HEATERS
165
WESTHERM
166
WATER SOURCE HEAT PUMPS
169
Mini WCBZ
170
WPHZ - WPHBZ
172
WCHZ - WCHBZ
174
WPVZ - WPVBZ
176
WCVZ - WCVBZ
178
DIRECT EXPANSION SYSTEMS
180
AIR / AIR INVERTER
ACHIBA
ECHIBA/CCHIBA
181
ACVIBA
ECVIBA/CCVIBA
184
AIR / AIR ON-OFF
ACHA ECHA/CCHA
ACHBA ECHBA/CCHBA
CCHA/FTA
CCHBA/FTBA
ACVA ECVA/CCVA
ACVBA ECVBA/CCVBA
UXCA/ECVA
UXCBA/ECVBA
186
189
192
196
DUCTABLE VERTICAL INDOOR UNITS
CLVA
CLVBA
198
SPLIT A/C, CONDENSER WITH AXIAL FANS
DXCZ FTZ
DXCBZ FTBZ
AXCZ "Dual" FTZ
AXCBZ "Dual" FTBZ
200
203
ROOFTOP
205
STANDARD COMPACT. AXIAL FANS
RXCZ - RXCBZ
206
STANDARD. AXIAL FANS
RXCA - RXCBA
208
WITH THERMODYNAMIC HEAT RECOVERY, AXIAL FANS
RXCA RCF - RXCBA RCF
210
STANDARD. CENTRIFUGAL FANS
RCCA - RCCBA
212
WITH THERMODYNAMIC HEAT RECOVERY, CENTRIFUGAL FANS
RCCA RCF - RCCBA RCF
214
CONTROLS
216
CONTROLLERS AND THERMOSTATS
217
HYDROFAN SYSTEM
220
PL@NT VISOR MONITORING SYSTEM (BMS)
222
CENTRALISED MANAGEMENT SYSTEM AND BMS
224
OTHER CONTROLS
226
GENERAL TERMS AND CONDITIONS OF SALE FOR PRODUCTS AND SERVICES
229
5
MODERN AND HIGH PERFORMANCE
PERFORMANCE TECHNOLOGY
SCROLL
VIS / SCREW
CONTROLS
ELECTRONIC
EXPANSION DEVICES
PLUG FAN AND
EC MOTOR
HIGH EFFICIENCY
EXCHANGERS
EUROVENT
View the certified products and models on the Eurovent
website.
TESTING
MICROCHANNEL
CONDENSERS
ENGAGEMENT - EFFICIENCY - ENERGY
Our company is committed to a
voluntary approach to seeking
energy efficiencies in and around
our products. This logo represents
the translation of this route in
terms of:
DESCRIPTION OF SYMBOLS
All of our units systematically undergo full-scale testing at
the end of the production line.
Our refrigerants are environmentally friendly.
INVERTER
INVERTER TECHNOLOGY: energy efficiency and maximum
comfort.
Cooling only
Reversible
Free cooling
Plug fan
Win
Clim
Hydrofan system
6
WinClim
LIQUID
CHILLERS
LIQUID CHILLERS
The liquid chillers range - large - complete - flexible
AIR-COOLED CHILLERS
Cap. kW
5
KRONO X
Mini Krono 2
REVERSIBLE
COOLING ONLY
KRONO C
FREE
COOLING
20
125
R410A
Krono X
200
300
400
500
600
R410A
Centrifuge Scroll
EQPLU / EQPL
2, 3 and 4 circuits - Scroll compressors - Axial
EQPLA
R410A
2, 3 and 4 circuits - Scroll compressors - Axial - Class A
EQSL
R410A
Bi-circuits - Screw compressor - Axial
EQSLA
Bi-circuits - Screw compressor - Axial - Class A
EQUL
1 and 2 circuits - Scroll compressors - Axial
EQUL PF
1 and 2 circuits - Scroll compressors - Axial and Plug Fan - Ductable
MICRO ADV
1 circuit- Scroll compressors - Axial
KRONO X
Mini Krono 2
R410A
Krono X
R410A
R410A
R410A
R410A
Centrifuge Scroll
KRONO C
EQPH
2, 3 and 4 circuits- Scroll compressors - Axial
EQSH
R410A
Bi-circuits - Screw compressor - Axial
EQUH
1 and 2 circuits - Scroll compressors - Axial
EQUH PF
1 and 2 circuits - Scroll compressors - Axial and Plug Fan - Ductable
EQMF
1 and 2 circuits - Scroll compressors - Axial - Free Cooling
EQMF PF
1 and 2 circuits - Scroll compressors - Plug Fan - Free Cooling - Ductable
R410A
R410A
R410A
R410A
1 and 2 circuits - Scroll compressors - Axial - Free Cooling
EQEF
R410A
EQSFA
Bi-circuits - Screw compressor - Axial - Class A
WATER-COOLED CHILLERS
COOLING ONLY
Cap. kW
5
20
125
EWNL
1 circuit - Scroll compressors
EWNL RC
2 circuits - Scroll compressors - Remote condenser
200
300
500
600
R410A
R410A
EWML
1 and 2 circuits - Scroll compressors
EWML RC
1 and 2 circuits - Scroll compressors - Remote condenser
R410A
R410A
EWSL K
Mono-circuit - Screw compressor
EWSL A
Bi-circuit - Screw compressor - Class
EWSL A+
REVERSIBLE
400
Bi-circuit - Scre
EWNH
1 circuit - Scroll compressors
EWNH RC
1 circuit - Scroll compressors - Remote condenser
R410A
R410A
EWMH
1 and 2 circuits - Scroll compressors - Reversible refrigerant side
EWMH RC
1 and 2 circuits - Scroll compressors - Reversible refrigerant side - Remote condenser
8
R410A
R410A
700
800
900
1000
1100
1200 1300 1400
1500 1600
Page 14
Page 16
Page 18 / 20
Page 28
Page 34
Page 38
Page 46
Page 50
Page 10
Page 14
Page 16
Page 24
Page 42
Page 54
Page 60
Page 64
Page 70
Page 74
Page 78
700
800
900
1000
1100
1200 1300 1400
1500 1600
Page 82
Page 88
Page 90
Page 101
Page 103
se A
Page 105
ew compressor - Classe A+
Page 107
Page 86
Page 89
Page 96
Page 102
9
LIQUID CHILLERS | AIR-COOLED
MICRO
ADVANCE
Small unit
Cooling only
and reversible
SCROLL
MAIN FEATURES
Capacities from 4.5 to 20 kW
13 models available
EER up to 2.75
ESEER up to 3.40
Scroll compressor
One air circuit
Brazed-plate evaporator
AC axial fan
For outdoor installation
Options
Operating limits in Cooling mode
- Water leaving temperature: -8 to +18ºC
- Outdoor air temperature: -10 to +46ºC
Water filter
Additional water pump (see models)
Water tank (30 or 60 litres depending on model)
Water valves
Low temperature kit
Rubber anti-vibration kit
Remote control kit
Operating limits in Heating mode
- Water leaving temperature: +25 to +50ºC
- Outdoor air temperature: -7 to +20ºC
EWMA Cooling only
EWMBA Reversible
MODEL
Summer mode - nominal cooling capacity (1) kW
Cooling absorbed power kW
Water flow m3/h
Besides these options, please speak to our Sales Department for any other
configuration or function that is not listed as being available.
TECHNICAL SPECIFICATIONS
M5
M6
T6
M7
T7
M9
T9
4.5
5.5
5.7
6.8
6.7
8.4
8.7
2.3
2.1
2.1
2.6
2.6
3.3
3.3
0.8
0.9
1.0
1.2
1.1
1.4
1.5
Water pressure drop kPa
25
26
26
38
38
35
35
Winter mode - nominal heating capacity (2) kW
5.9
7.0
6.9
8.5
8.4
10.7
10.5
Heating absorbed power kW
2.4
2.1
2.1
2.6
2.6
3.4
3.2
Compressors
scroll
Quantity n.
1
1
1
1
1
1
1
Number of circuits n.
1
1
1
1
1
1
1
AC axial fans n.
1
1
1
1
1
1
1
2400
3500
3500
3500
3500
4200
4200
Air circuits n.
1
1
1
1
1
1
1
Gas circuits n.
1
1
1
1
1
1
230/1/50
230/1/50
400/3/50+N 230/1/50
400/3/50+N 230/1/50
400/3/50+N
EER (1) kW/kW
1.97
2.56
2.63
2.62
2.57
2.56
2.65
COP (2) kW/kW
2.79
3.06
3.01
3.14
3.13
3.31
3.23
2.43
3.25
3.33
3.32
3.25
3.17
3.27
Sound power level [Lw] (3) dB(A)
64.0
68.9
68.9
69.5
69.5
69.5
69.5
Average sound pressure level [Lpm] (4) dB(A)
50.1
55.1
55.1
55.1
55.1
55.1
55.1
90
95
95
110
110
115
115
3/4"
3/4"
1 1/4"
3/4"
1 1/4"
3/4"
1 1/4"
Air flow m3/h
Other
Power supply V/Ph/Hz
ESEER
Net weight kg
1
Hydraulic connections
Evaporator IN/OUT – ISO 228/1 – G Ø
➜
10
EWMA Cooling only
EWMBA Reversible
MODEL
Summer mode - nominal cooling capacity (1) kW
Cooling absorbed power kW
Water flow m3/h
Water pressure drop kPa
Winter mode - nominal heating capacity (2) kW
Heating absorbed power kW
TECHNICAL SPECIFICATIONS
M11
T11
T13
T15
T19
T22
10.9
11.1
12.9
14.9
18.7
20.1
4.6
4.4
4.8
5.7
7.1
8.4
1.9
1.9
2.2
2.6
3.2
3.5
32
31
35
34
40
40
13.3
13.8
15.6
18.1
23.0
24.8
4.6
4.3
4.7
5.6
7.1
8.3
Compressors
scroll
Quantity n.
1
1
1
1
1
1
Number of circuits n.
1
1
1
1
1
1
AC axial fans n.
2
2
2
2
2
2
6800
6800
6800
6400
7000
7000
Air circuits n.
1
1
1
1
1
1
Gas circuits n.
1
1
1
1
1
1
230/1/50
400/3/50+N 400/3/50+N 400/3/50+N 400/3/50+N 400/3/50+N
EER (1) kW/kW
2.36
2.51
2.70
2.61
2.62
2.38
COP (2) kW/kW
3.04
3.56
3.26
3.35
3.47
3.32
2.88
3.18
3.31
3.24
3.22
2.98
Sound power level [Lw] (3) dB(A)
72.8
72.8
72.8
73.3
78.5
78.6
Average sound pressure level [Lpm] (4) dB(A)
58.0
58.0
58.0
58.2
63.0
63.1
140
140
160
170
265
270
1 1/4"
1 1/4"
1 1/4"
1 1/4"
1 1/4"
1 1/4"
Air flow m3/h
Other
Power supply V/Ph/Hz
ESEER
Net weight kg
Hydraulic connections
Evaporator IN/OUT – ISO 228/1 – G Ø
(1) Values calculated according to chilled water temperature 12/7ºC; outdoor air temperature 35ºC (in accordance with Eurovent certification).
(2) Values calculated according to hot water temperature 40/45ºC; outdoor air temperature 7ºC (in accordance with Eurovent certification).
(3) Sound power level [Lw] according to ISO EN 9614-2.
(4) Average sound pressure level [Lpm] 1m to ISO EN 3744.
DIMENSIONS
a mm
M5
M6
T6
M7
T7
M9
T9
M11
T11
T13
T15
T19
T22
900
900
900
900
900
900
900
900
900
900
900
1450
1450
b mm
370
370
370
370
370
370
370
370
370
370
420
550
550
c mm
640
640
640
940
940
940
940
1240
1240
1240
1390
1200
1200
c
c
a
b
a
11
b
LIQUID CHILLERS | AIR-COOLED
MINI
KRONO 2
Small unit
Cooling only
and reversible
MAIN FEATURES
Cooling capacity between 25 and 40 kW.
Refrigerant circuit with 1 scroll compressor
and 1 fan.
Condensation in cooling mode controlled by
2-speed fan.
High energy efficiency.
LCX control included.
Remote start/stop.
Remote winter/summer.
Second setpoint.
Alarm signal.
Options
ENERGY EFFICIENCY
Compressor soft start.
Condensation controlled by variable voltage controller.
EC fan.
SOUND LEVEL
Acoustic insulation on compressor.
Advantages
INSTALLATION
Magneto-thermal circuit breakers in
the electrical board.
Stand-alone electrical board.
Operation option for power supply without neutral.
Power supply 60 Hz at 230 V and 208 V.
Aluminium-zinc treated coil.
Protection grille on outdoor heat exchanger.
Modbus connection.
Remote control.
Solid design and energy efficiency for
chilled water installations.
HYDRONIC KIT
Water pump.
Water pump, expansion vessel
and buffer tank.
Extra electric heater.
Besides these options, please speak to our Sales Department for any other
configuration or function that is not listed as being available.
EWXA Cooling only
EWXBA Reversible
MODEL
Cooling capacity kW
Cooling absorbed power kW
Heating capacity kW
Heating absorbed power kW
TECHNICAL SPECIFICATIONS
801.1
1001.1
1201.1
1501.1
25.9
30.2
33.5
39.8
8.3
9.7
10.8
13.7
27.7
31.1
35.0
41.2
8.6
9.7
10.9
13.8
Electrical power supply Volts
400/3/50
Water connections
Water flow m3/h
Water-side pressure drop kPa
1 1/2
4.5
5.2
5.8
6.8
31
42
34
44
312
340
Dimensions (length x width x height) mm
Net weight kg
1200 x 1050 x 1470
12
348
354
HYDRAULIC DIAGRAM
COMPONENTS
1. Plate heat exchanger
2. Water pump
3. Air vent
4. Water tank
5. Expansion vessel
6. Safety valve
7. Drain valve
8. Water filter / flow switch (optional)
REFRIGERANT FLOW DIAGRAM
COMPONENTS
1. Compressor
2. 4-way cycle reversal valve
3. Condenser coil
4. Expansion valve
5. Non-return valve
6. Filter dryer
7. Liquid receiver
8. Suction accumulator
9. Plate heat exchanger
TC Condensing pressure transducer
TE Evaporating pressure transducer
PA High pressure switch
13
LIQUID CHILLERS | AIR-COOLED
KRONO XA
Cooling only
KRONO XBA
Reversible
MAIN FEATURES
Cooling capacities between 45.3 and 136.0 kW
One refrigerant circuit with tandem scroll
compressors
High energy efficiency
LCX control included
Step control on condensation in cooling mode and
on evaporation in heating mode
Water differential pressure switch
Remote start/stop
Remote winter/summer
Timer programming capability
Advantages
Integrated units for air conditioning solutions. Flexibility and
reliability all in one. The EWXA/EWXBA chillers are compact units
designed for outdoor installation, whether on flat roofs, patios or on
the ground.
Options
ENERGY EFFICIENCY
Compressor soft start
Partial heat recovery exchanger (DHW)
EC fans
Condensation controlled by frequency inverter
or variable voltage controller
SOUND LEVEL
Acoustic insulation on compressor
Silent
Super silent
UNIT INSTALLATION
Magneto-thermal circuit breakers in the electrical
board
60Hz power supply and voltages of 230, 208 etc.
Upgraded fans
Upgraded pumps
Integrated hydronic kit (with tank, etc.)
Integrated hydronic kit (without tank)
Integrated pump
Double or twin pump
Operation option for antifreeze electric heater in
condensate tray
Anti-corrosion pre-treated coils
Suitable for disassembly
Option for shell and tube evaporator (only without hydronic kit)
Protection grilles on outdoor heat exchangers
Victaulic outside couplings
MAINTENANCE
Service valves
External pressure tapping points
Refrigerant manometers
Water manometers
Water filter
CONTROLS
Second setpoint
Alarm signals
Stand-alone electrical board
Option for master/slave operation
Operation option for power supply without neutral
Modbus connection, etc.
See Thermostats chapter
Besides these options, please speak to our Sales Department for any other
configuration or function that is not listed as being available.
14
EWXA Cooling only
EWXBA Reversible
TECHNICAL SPECIFICATIONS
1601.2
2001.2
2401.2
2501.2
3001.2
Nominal cooling capacity kW
45.3
52.6
61.5
67.8
77.3
Nominal cooling capacity T.R.
12.9
14.9
17.5
19.3
22.0
Nominal heating capacity kW
53.1
62.0
73.8
79.3
84.9
EER kW/kW
2.8
2.8
2.8
2.8
3.0
COP kW/kW
3.3
3.3
3.4
3.2
3.1
MODEL
Power supply (50 Hz ~) (1) V
Water connections Ø (")
Water flow m3/h
Water pressure drop kPa
Dimensions (length x width x height) mm
Net weight kg
MODEL
400.3+N
400.3+N
400.3+N
400.3+N
400.3+N
2
2
2
2
2
7.8
9.0
10.6
11.7
13.3
22
24
26
26
32
2450x1220x1640
2450x1220x1640
2450x1220x1640
2860x1220x1630
2860x1220x1630
730
740
770
870
880
3201.2
3501.2
4001.2
4501.2
5001.2
Nominal cooling capacity kW
81.3
94.9
112.5
125.1
136.0
Nominal cooling capacity T.R.
23.1
27.0
32.0
35.6
38.7
Nominal heating capacity kW
EER kW/kW
COP kW/kW
Power supply (50 Hz ~)** V
Water connections Ø (")
Water flow m3/h
Water pressure drop kPa
Dimensions (length x width x height) mm
Net weight kg
88.6
103.4
123.0
136.0
146.3
2.8
2.8
2.8
2.9
3.0
2.9
3.0
3.2
3.2
3.3
400.3+N
400.3+N
400.3+N
400.3+N
400.3+N
2
2
2
2
2
14.0
16.3
19.4
21.5
23.4
30
35
41
43
46
2860x1220x1630
3400x1220x1640
3400x1220x1640
3400x1220x1640
3400x1220x1640
900
1040
1120
1200
1250
Information about the operating conditions in accordance with EUROVENT
(1) Availability of other voltages and frequencies in the electric power supply
EWXA/EWXBA HYDRAULIC DIAGRAMS
Standard diagram
1-pump hydronic kit (without tank)
2-pump hydronic kit (without tank)
COMPONENTS
COMPONENTS
COMPONENTS
1. Plate heat exchanger
2. Air vent
3. Water filter (optional)
1. Plate heat exchanger
2. Air vent
3. Water pump
4. Service valve
5. Expansion vessel
6. Water filter (optional)
2-pump hydronic kit (with tank)
COMPONENTS
1. Plate heat exchanger
2. Non-return valve
3. Water pump
4. Service valve
5. Air vent
6. Water tank
7. Expansion vessel
1. Plate heat exchanger
2. Air vent
3. Non-return valve
4. Water pump
5. Service valve
6. Expansion vessel
7. Water filter (optional)
1-pump hydronic kit (with tank)
COMPONENTS
8. Safety valve
9. Manometer
10. Drain valve
11. Water filter (optional)
1. Plate heat exchanger
2. Water pump
3. Service valve
15
4. Air vent
5. Water tank
6. Expansion vessel
7. Safety valve
8. Manometer
9. Drain valve
10. Water filter (optional)
LIQUID CHILLERS | AIR-COOLED
KRONO CZ
Cooling only
KRONO CBZ
Reversible
CENTRIFUGAL FANS
MAIN FEATURES
Cooling capacities between 15.9 and 78.5 kW
Independent refrigerant circuits
Scroll compressors
Thermostats and controllers included for units with
electromechanical controls Microchiller2 (all models)
Advantages
Liquid chillers with centrifugal fan: solutions for small spaces.
The EWCZ/EWCBZ chillers are compact air/water units, primarily
intended for indoor installation.
Suitable for medical centres, hotels, offices, industrial facilities,
hospitals...
Options
ENERGY EFFICIENCY
Compressor soft start (depending on model)
Fan soft start (depending on model)
Condensation control by frequency inverter for low ambient
temperature operation
SOUND LEVEL
Double thermal-acoustic insulation
Acoustic insulation on compressor
UNIT INSTALLATION
Magneto-thermal circuit breakers in the electrical board
60Hz power supply and voltages of 230, 208 etc.
Kit for bad weather installation
Upgraded motors
Operation option for antifreeze electric heater
in condensate tray
Flame-proof filter class M0
Thermal-acoustic insulation class M0
Base frame
Anti-corrosion pre-treated coils
Suitable for disassembly
Pressure reading external manometers
Option on request for shell and tube evaporator
External hydronic module MWI
Air inlet/outlet configuration options
701, 3002
standard
Leaving water temperature less than 7ºC
Water differential pressure switch
Vertical condenser air outlet
MAINTENANCE
Service valves
External pressure tapping points
Filter on condenser
CONTROLS
Suitable for Hydrofan
Alarm signals
Smoke detection
Remote start/stop
Stand-alone electrical board
Option for master/slave operation
Operation option for redundant machine
Operation option for centralized integrated management
Operation option for power supply without neutral
Timer programming function and Modbus connection etc. please
refer to the Thermostats section
Besides these options, please speak to our Sales Department for any other
configuration or function that is not listed as being available.
optional
3502
16
EWCZ Cooling only
TECHNICAL SPECIFICATIONS
MODEL
Nominal cooling capacity
Nominal cooling capacity
Cooling absorbed power
Power supply (50 Hz ~)
Water connections
Water flow
Water pressure drop
Air flow
External static pressure
Dimensions (length x width x height)
Net weight
kW
T.R.
kW
V
Ø (")
l/s
kPa
m3/h
Pa
mm
kg
Nominal cooling capacity
Nominal cooling capacity
Cooling absorbed power
Power supply (50 Hz ~)
Water connections
Water flow
Water pressure drop
Air flow
External static pressure
Dimensions (length x width x height)
Net weight
kW
T.R.
kW
V
Ø (")
l/s
kPa
m3/h
Pa
mm
kg
MODEL
701
801
1001
1201
1602
16.2
4.6
5.4
400.3+N
1 1/2
0.8
40
7000
70
1130x800x1250
277
19.8
5.6
6.3
230.3 or 400.3+N
1 1/2
0.9
45
7800
95
1130x800x1250
282
24.5
7.0
8.2
230.3 or 400.3+N
1 1/2
1.2
40
11000
50
1700x870x1250
376
30.3
8.6
9.5
230.3 or 400.3+N
1 1/2
1.4
35
12500
50
1700x870x1250
416
39.6
11.3
13.0
230.3 or 400.3+N
2
1.9
45
16000
90
2000x939x1250
567
2002
2402
3002
3502
49.0
13.9
16.7
230.3 or 400.3+N
2
2.3
40
18000
60
2150x980x1362
651
60.6
17.2
19.4
230.3 or 400.3+N
2
2.9
35
18500
78
2150x980x1362
687
71.2
20.2
22.3
230.3 or 400.3+N
2
3.4
30
27000
140
2800x1050x1722
1038
80.4
22.9
25.8
400.3+N
2
3.8
30
32000
160
2800x1050x1722
1120
Wesper recommends applying antifreeze electric heater in the drain pipe of condensate tray where ambient temperature
conditions are less than 5ºC.
EWCBZ Reversible
TECHNICAL SPECIFICATIONS
MODEL
Nominal cooling capacity
Nominal cooling capacity
Nominal heating capacity
Cooling absorbed power
Heating absorbed power
Power supply (50 Hz ~)
Water connections
Water flow
Water pressure drop
Air flow
External static pressure
Dimensions (length x width x height)
Net weight
kW
T.R.
kW
kW
kW
V
Ø (")
l/s
kPa
m3/h
Pa
mm
kg
Nominal cooling capacity
Nominal cooling capacity
Nominal heating capacity
Cooling absorbed power
Heating absorbed power
Power supply (50 Hz ~)
Water connections
Water flow
Water pressure drop
Air flow
External static pressure
Dimensions (length x width x height)
Net weight
kW
T.R.
kW
kW
kW
V
Ø (")
l/s
kPa
m3/h
Pa
mm
kg
MODEL
701
801
1001
1201
1602
15.9
4.5
17.4
5.5
5.0
400.3+N
1 1/2
0.8
40.0
7000
70
1130x800x1250
277
19.4
5.5
21.3
7.4
5.8
230.3 or 400.3+N
1 1/2
0.9
45.0
7800
95
1130x800x1250
282
24.0
6.8
26.4
9.8
7.5
230.3 or 400.3+N
1 1/2
1.1
40.0
11000
50
1700x870x1250
376
29.7
8.4
32.6
12.3
8.8
230.3 or 400.3+N
1 1/2
1.4
35.0
12500
50
1700x870x1250
416
38.9
11.1
42.5
14.7
11.7
230.3 or 400.3+N
2
1.9
45.0
16000
90
2000x939x1250
567
2002
2402
3002
3502
48.0
13.6
52.8
19.6
14.8
230.3 or 400.3+N
2
2.3
40
22000
120
2600x980x1422
807
59.4
16.9
65.2
24.4
17.7
230.3 or 400.3+N
2
2.8
35
23000
135
2600x980x1422
863
69.8
19.8
76.0
26.1
20.2
230.3 or 400.3+N
2
3.3
30
27000
140
2800x1050x1722
1038
78.5
22.3
85.2
30.3
22.0
400.3+N
2
3.8
30
32000
160
2800x1050x1722
1120
Wesper recommends applying antifreeze electric heater in the drain pipe of condensate tray where
ambient temperature conditions are less than 5ºC.
Please contact the Sales Department for hydronic modules for these units.
17
LIQUID CHILLERS | AIR-COOLED
EQPLU
128.1 /
204.2
Cooling only
SCROLL COMPRESSOR(S)
Cooling capacities from 128 to 200 kW
10 sizes
Refrigerant: R410A
EER up to 2.98
ESEER up to 3.99
MAIN FEATURES
AVAILABLE VERSIONS
Partial heat recovery version
Total heat recovery version
ELN extra low sound level version
EC motor for external static pressure version
Brine low and very low temperature version
All-year-round operation as standard feature (-12°C)
Advantages
2 Scroll compressors per circuit for greater efficiency
Single or twin circuit units
Increased ESEER
Refrigerant load reduced thanks to microchannel
technology
Different acoustic levels available
Partial or total heat recovery
EC fans for external static pressure
Remote demand limit via additional electronic board
Analog setpoint compensation
Easy maintenance
Besides these options, please speak to our Sales Department for any other
configuration or function that is not listed as being available.
Cooling operating limits
Indicative values. The operating T° are influenced by
a series of settings such as: operating conditions,
thermal load, adjustments, etc... Data to be confirmed
upon selection.
Main accessories and options
Code
79 Electrical panel heating resistance
83 Compressor operation indicator
101 EC fan motors
118 Kit A leaving chilled water low temperature operation
119 Kit B leaving chilled water low temperature operation
150 Kit LNO low sound level
170 Antivibration mounts - spring - supplied loose
171 Antivibration mounts - rubber - supplied loose
250 Coil protection kit
350 Coil coating for agressive environment
449 Partial heat recovery dry contact for activation of
circulation pump
450 Desuperheater
451 Total heat recovery
454 Total heat recovery dry contact for activation of circulation pump
720 Medium pressure single pump kit
721 Medium pressure double pump kit
722 Low pressure single pump kit
723 Low pressure double pump kit
725 Water tank + 1 medium pressure pump
726 Water tank + 2 medium pressure pumps
727 Water tank + 1 low pressure pump
728 Water tank + 2 low pressure pumps
923 COM MBUS/JBUS serial card
926 LON serial card
931 BACnet Ethernet - SNMP - TCP/IP serial card
932 BACnet MS/TP serial card
934 MP.COM extension card
943 Data logger
(°C)
20
Water outlet temperature
from the evaporator
Available with single or double refrigeration circuit(s)
2 SCROLL compressors mounted on
antivibration mounts
All aluminium microchannel condenser
15
10
5
0
Glycol solution
+ low temperature kit
-5
-10
-13
-10
-5
0
5
10
15
20
25
Outdoor air temperature
18
30
35
40
45
(°C)
EQPLU 128.1 / 204.2 Cooling only
SIZE
TECHNICAL SPECIFICATIONS
128.1
128.2
146.1
146.2
164.1
164.2
186.1
186.2
204.1
204.2
COOLING ONLY (1)
Cooling capacity kW
123
125
138
138
163
163
181
182
199
200
Compressor absorbed power kW
40.6
40.8
48
48
50
50
59.1
59.1
68.5
68.5
Nominal operating current Compressors A
Evaporator water flow m³/h
Evaporator pressure loss kPa
70.7
70.8
82.4
82.4
86.8
86.8
101
101
116
116
21.2
21.5
23.7
23.8
28
28
31.2
31.2
34.3
34.3
49
46
50
56
51
55
52
51
50
48
COOLING ONLY + HEAT RECOVERY 100% (2)
Cooling capacity kW
113
113
128
128
143
144
162
163
181
182
Heating capacity kW
159
160
182
182
204
205
232
232
259
259
Compressors absorbed power kW
Nominal operating current Compressors A
Heat recovery exchanger water flow m³/h
Heat recovery pressure loss kPa
46.7
46.7
53.9
53.9
61.1
61
69.4
69.3
78
77.9
78.3
78.4
90.4
90.4
103
102
116
116
130
130
27.7
27.7
31.6
31.6
35.5
35.6
40.3
40.3
45
45.1
9
9
12
13
13
14
15
15
16
15
PARTIAL HEAT RECOVERY (3)
Heating capacity kW
Heat recovery exchanger water flow m³/h
Heat recovery pressure loss kPa
COMPRESSORS
Quantity n.
Maximum operating current A
Starting current A
Number of capacity steps n.
EVAPORATOR
n.
Type (6)
Water volume l
Maximum water flow m³/h
TOTAL HEAT RECOVERY EXCHANGER
n.
Water volume l
Maximum water flow m³/h
PARTIAL HEAT RECOVERY EXCHANGER
n.
Water volume l
Maximum water flow m³/h
AXIAL FANS (AC)
n.
Total air flow m³/h
Absorbed power kW
45.3
--
50.6
--
59.8
--
66.5
--
73.1
--
7.8
--
8.7
--
10.3
--
11.5
--
12.6
--
25
--
31.3
--
31
--
32.2
--
35.6
--
scroll
scroll
scroll
scroll
scroll
scroll
scroll
scroll
scroll
scroll
2
2
2
2
2
2
2
2
2
2
97
97
113.9
113.9
131
131
148
148
165.2
165.2
321
321
359
359
321
321
473
473
491
491
2
2
2
2
2
2
2
2
2
2
1
1
1
1
1
1
1
1
1
1
PHE
PHE
PHE
PHE
PHE
PHE
PHE
PHE
PHE
PHE
8
8.8
9
8.8
11
8.6
12
9.8
14
11.7
40.6
40.7
45.4
45.5
53.7
53.8
59.8
59.9
65.7
65.8
1
1
1
1
1
1
1
1
1
1
8
8.8
9
8.8
11
8.6
12
9.8
14
11.7
29.9
30
33.5
33.5
39.7
39.7
44.1
44.2
48.5
48.5
1
--
1
--
1
--
1
--
1
--
1.7
--
1.7
--
2.3
--
2.8
--
3.1
--
11
--
12.3
--
14.6
--
16.2
--
17.8
--
2
2
2
2
3
3
3
3
3
3
42360
42360
42360
42360
63540
63540
63540
63540
63540
63540
3.2
3.2
3.2
3.2
4.7
4.7
4.7
4.7
4.7
4.7
7.8
7.8
7.8
7.8
11.7
11.7
11.7
11.7
11.7
11.7
Maximum external static pressure Pa
0
0
0
0
0
0
0
0
0
0
n.
2
2
2
2
3
3
3
3
3
3
42360
42360
42360
42360
63540
63540
63540
63540
63540
63540
Nominal operating current Compressors A
AXIAL FANS (EC)
Total air flow m³/h
Absorbed power kW
Nominal operating current Compressors A
Maximum external static pressure Pa
REFRIGERANT
Total refrigerant load (excluding options) kg
Number of refrigerant circuits n.
V/Ph/
Hz
SUPPLY VOLTAGE
2.6
2.6
2.6
2.6
3.8
3.8
3.8
3.8
3.8
3.8
7.8
7.8
7.8
7.8
11.7
11.7
11.7
11.7
11.7
11.7
0
0
0
0
0
0
0
0
0
0
R410A
R410A
R410A
R410A
R410A
R410A
R410A
R410A
R410A
R410A
12.3
12.3
12.3
12.5
12
13.7
20.9
23.5
21.4
24.3
1
2
1
2
1
2
1
2
1
2
400/3/
50+N
400/3/
50+N
400/3/
50+N
400/3/
50+N
400/3/
50+N
400/3/
50+N
400/3/
50+N
400/3/
50+N
400/3/
50+N
400/3/
50+N
ENERGY EFFICIENCY RATIOS (1)
EER kW/kW
ESEER = Eurovent standard
2.81
2.84
2.7
2.7
2.98
2.98
2.84
2.85
2.72
2.73
3.77
3.26
3.61
3.11
3.99
3.45
3.81
3.29
3.64
3.14
SOUND LEVELS
Average sound pressure level [Lpm] (4) dB(A)
62.1
62.1
62.1
62.1
62.5
62.5
64.1
64.1
65.2
65.2
Sound power level (Lw) dB(A)
80.3
80.3
80.3
80.3
81.3
81.3
82.8
82.8
84
84
HYDRAULIC KIT
Medium pressure single pump
Low pressure single pump
Medium pressure double pump
Low pressure double pump
Water tank volume l
HYG 360/1
HYG 360/1
HYG 360/1
HYG 360/1
GPUM2/1
GPUM2/1
GPUM2/1
GPUM2/1
GPUM2/1
GPUM2/1
-
-
-
-
GPUB2/1
GPUB2/1
GPUB2/1
GPUB2/1
GPUB2/1
GPUB2/1
HYG 360/2
HYG 360/2
HYG 360/2
HYG 360/2
GPUM2/2
GPUM2/2
GPUM2/2
GPUM2/2
GPUM2/2
GPUM2/2
-
-
-
-
GPUB2/2
GPUB2/2
GPUB2/2
GPUB2/2
GPUB2/2
GPUB2/2
360
360
360
360
200
200
200
200
200
200
DIMENSIONS
Length mm
2960
2960
2960
2960
4000
4000
4000
4000
4000
4000
Width mm
1200
1200
1200
1200
1200
1200
1200
1200
1200
1200
Height mm
1950
1950
1950
1950
1970
1970
1970
1970
1970
1970
kg
910
910
930
930
990
1020
1030
1040
1060
1070
NET WEIGHT
HYDRAULIC CONNECTIONS
EVAPORATOR
Inlet outlet diameter Ø
PARTIAL HEAT RECOVERY EXCHANGER
Ø mm
-
-
-
-
-
-
-
-
-
-
73.1
73.1
73.1
73.1
73.1
73.1
73.1
73.1
73.1
73.1
1+1/2"
-
1+1/2"
-
1+1/2"
-
1+1/2"
-
1+1/2"
-
73.1
73.1
73.1
73.1
73.1
73.1
73.1
73.1
73.1
73.1
Inlet outlet diameter – ISO 7/1 – R
Inlet outlet diameter – ISO 228/1-GM Ø
TOTAL HEAT RECOVERY EXCHANGER
Inlet outlet diameter Ø mm
(1) Gross value - chilled water temperature 12/7°C; external air temperature 35°C.
(2) Gross value - chilled water temperature 12/7°C and hot water temperature 40/45°C.
(3) Gross value - chilled water temperature 12/7°C; external air temperature 35°C and hot
water temperature 40/45°C.
19
(4) Sound pressure level [Lpm] at 1m far according to ISO EN 3744
(5) Sound power level [Lw] according to ISO EN 9614-2.
(6) PHE = Brazed-plate heat exchanger; S&T = Shell and tube heat exchanger
LIQUID CHILLERS | AIR-COOLED
EQPL
215 / 830
Cooling only
SCROLL COMPRESSORS
Cooling capacities from 210 to 808 kW
20 sizes
Refrigerant: R410A
EER up to 3.11
ESEER up to 4.18
Available with 2, 3 or 4 refrigeration circuits
2 SCROLL compressors per circuit, fitted on
antivibration mounts
All aluminium microchannel condenser
Modern and modular design
Shell and tube evaporator from size 430
AVAILABLE VERSIONS
Partial heat recovery version
Total heat recovery version
ELN extra low sound level version
EC motor for external static pressure version
Brine low and very low temperature versions
All-year-round operation as standard feature (-12°C)
Advantages
Wide power range covered by scroll technology with
maximum reliability (multiple circuits)
2 Scroll compressors per circuit for greater efficiency and
reliability
Electronic expansion valve as standard
Increased ESEER
Dialogue interface with screen and graphical icons for easier
reading
Refrigerant load reduced thanks to microchannel technology
Large choice of acoustic levels
Partial or total heat recovery
EC fans for available pressure
Remote demand limit via additional electronic board
Analog setpoint compensation
Easy maintenance
Cooling operating limits
Indicative values. The operating T° are influenced by
a series of settings such as: operating conditions,
thermal load, adjustments, etc... Data to be confirmed
upon selection.
Main accessories and options
Code
79 Electrical panel heating resistance
83 Compressor operation indicator
101 EC fan motors
118 Kit A leaving chilled water low temperature operation
119 Kit B leaving chilled water low temperature operation
150 Kit LNO low sound level
170 Antivibration mounts - spring - supplied loose
171 Antivibration mounts - rubber - supplied loose
180 Power factor capacitor for compressor motor
183 Full Victaulic connection
251 Coil protection kit
350 Coil coating for agressive environment
449 Partial heat recovery dry contact for activation
of circulation pump
450 Desuperheater
451 Total heat recovery
454 Total heat recovery dry contact for activation of circulation pump
459 Shell and tube evaporator
720 Medium pressure single pump kit
721 Medium pressure double pump kit
722 Low pressure single pump kit
723 Low pressure double pump kit
725 Water tank + 1 medium pressure pump
726 Water tank + 2 medium pressure pumps
727 Water tank + 1 low pressure pump
728 Water tank + 2 low pressure pumps
923 COM MBUS/JBUS serial card
926 LON serial card
931 BACnet Ethernet - SNMP - TCP/IP serial card
934 MP.COM extension card
943 Data logger
Besides these options, please speak to our Sales Department for any other
configuration or function that is not listed as being available.
(°C)
Water outlet temperature
from the evaporator
MAIN FEATURES
20
15
10
5
0
Glycol solution
+ low temperature kit A
-5
Glycol solution
+ low temperature kit B
-10
-13
-10
-5
0
5
10
15
20
25
30
Outdoor air temperature
20
35
40
45
(°C)
EQPL 215 / 830 Cooling only
SIZE
TECHNICAL SPECIFICATIONS
215.2
235.2
255.2
285.2
305.2
kW
kW
A
m³/h
kPa
210
62.8
115
36
54
229
71.1
125
39.3
54
250
81.5
142
43
54
282
96.6
166
48.4
53
302
87.5
153
51.9
52
kW
kW
kW
A
m³/h
kPa
203
269
66.4
120
46.8
89
224
298
73.7
128
51.7
97
251
332
80.9
141
57.7
73
290
383
92.3
160
66.5
78
294
385
91.9
159
67
71
Heating capacity kW
Heat recovery exchanger water flow m³/h
Heat recovery pressure loss kPa
77
13.3
18.1
84
14.5
21.5
91.8
15.8
25.7
103
17.8
26.5
111
19.1
26.7
COOLING ONLY (1)
Cooling capacity
Compressors absorbed power
Nominal operating current Compressors
Evaporator water flow
Evaporator pressure loss
COOLING ONLY + HEAT RECOVERY 100% (2)
Cooling capacity
Heating capacity
Compressors absorbed power
Nominal operating current Compressors
Heat recovery exchanger water flow
Heat recovery pressure loss
PARTIAL HEAT RECOVERY (3)
COMPRESSORS
Quantity
Maximum operating current
Starting current
Number of capacity steps
EVAPORATOR
n.
A
A
n.
n.
Type (6)
Water volume l
Maximum water flow m³/h
TOTAL HEAT RECOVERY EXCHANGER
n.
Water volume l
Maximum water flow m³/h
PARTIAL HEAT RECOVERY EXCHANGER
n.
Water volume l
Maximum water flow m³/h
AXIAL FANS (AC)
Total air flow
Absorbed power
Nominal operating current Compressors
Maximum external static pressure
AXIAL FANS (EC)
Total air flow
Absorbed power
Nominal operating current Compressors
Maximum external static pressure
scroll
scroll
scroll
scroll
scroll
4
165
389
4
4
177
401
4
4
194
418
4
4
228
472
4
4
228
472
4
1
1
1
1
1
PHE
11.7
68.2
PHE
13.3
74.4
PHE
15.1
81.5
PHE
18.6
91.9
PHE
22.8
98.4
1
1
1
1
1
11.7
65.5
13.3
72.4
15.1
80.8
18.6
93.1
22.8
93.8
2
2
2
2
2
3.5
18.5
3.5
20.2
3.5
22.1
4.1
24.9
4.6
26.7
n.
4
4
4
4
6
m³/h
kW
A
Pa
84720
6.3
15.6
0
84720
6.3
15.6
0
84720
6.3
15.6
0
84720
6.3
15.6
0
127080
9.5
23.4
0
n.
4
4
4
4
6
m³/h
kW
A
Pa
84720
5.1
15.6
80
84720
5.1
15.6
80
84720
5.1
15.6
80
84720
5.1
15.6
80
127080
7.7
23.4
80
REFRIGERANT
R410A
R410A
R410A
R410A
R410A
19.3
2
19.6
2
19.9
2
19.9
2
27.6
2
400/3/50
400/3/50
400/3/50
400/3/50
400/3/50
3.04
4.07
2.96
3.96
2.85
3.82
2.74
3.67
3.11
4.18
68.9
87.7
70
88.8
71.2
90
71.2
90
71.2
90.6
GPVM1/1
GPVB1/1
GPVM1/2
GPVB1/2
130
GPVM1/1
GPVB1/1
GPVM1/2
GPVB1/2
130
GPVM1/1
GPVB1/1
GPVM1/2
GPVB1/2
130
GPVM1/1
GPVB1/1
GPVM1/2
GPVB1/2
130
GPVM1/1
GPVB1/1
GPVM1/2
GPVB1/2
190
Length mm
Width mm
Height mm
2410
2260
2304
2410
2260
2304
2410
2260
2304
2410
2260
2304
3530
2260
2304
kg
1730
1920
1970
2010
2280
Ø mm
88.9
88.9
88.9
88.9
88.9
Ø
Ø
-2 x 1"
-2 x 1"
-2 x 1"
-2 x 1"
-2 x 1"
Ø mm
88.9
88.9
88.9
88.9
88.9
Total refrigerant load (excluding options) kg
Number of refrigerant circuits n.
SUPPLY VOLTAGE
ENERGY EFFICIENCY RATIOS (1)
V/Ph/Hz
EER kW/kW
ESEER = Eurovent standard
SOUND LEVELS
Average sound pressure level [Lpm] (4) dB(A)
Sound power level (Lw) dB(A)
HYDRAULIC KIT
Medium pressure single pump
Low pressure single pump
Medium pressure double pump
Low pressure double pump
Water tank volume l
DIMENSIONS
NET WEIGHT
HYDRAULIC CONNECTIONS
EVAPORATOR
Inlet outlet diameter
PARTIAL HEAT RECOVERY EXCHANGER 100%
Inlet outlet diameter – ISO 7/1 – R
Inlet outlet diameter – ISO 228/1-GM
TOTAL HEAT RECOVERY EXCHANGER
Inlet outlet diameter
(1) Gross value - chilled water temperature 12/7°C; outdoor temperature 35°C.
(2) Gross value - chilled water temperature 12/7°C and hot water temperature 40/45°C.
(3) Gross value - chilled water temperature 12/7°C; outdoor temperature 35°C and hot
water temperature 40/45°C.
(4) Sound pressure level [Lpm] at 1m far according to ISO EN 3744
(5) Sound power level [Lw] according to ISO EN 9614-2.
(6) PHE = Brazed-plate heat EXCHANGER; S&T = Shell and tube heat EXCHANGER
21
➜
LIQUID CHILLERS | AIR-COOLED
EQPL 215 / 830 Cooling only
TECHNICAL SPECIFICATIONS
SIZE
340.2
380.2
410.2
430.3
470.3
kW
kW
A
m³/h
kPa
333
101
174
57.2
53
370
119
203
63.6
51
405
138
233
69.5
52
423
145
248
72.7
31
456
141
245
78.4
36
kW
kW
kW
A
m³/h
kPa
329
431
103
178
75
73
371
489
118
202
85
77
413
547
134
227
95
88
-------
-------
Heating capacity kW
Heat recovery exchanger water flow m³/h
Heat recovery pressure loss kPa
122
21.1
32.4
136
23.4
33.5
148
25.6
36.7
155
26.7
26.5
167
28.8
27
COOLING ONLY (1)
Cooling capacity
Compressors absorbed power
Nominal operating current Compressors
Evaporator water flow
Evaporator pressure loss
COOLING ONLY + HEAT RECOVERY 100% (2)
Cooling capacity
Heating capacity
Compressors absorbed power
Nominal operating current Compressors
Heat recovery exchanger water flow
Heat recovery pressure loss
PARTIAL HEAT RECOVERY (3)
COMPRESSORS
Quantity
Maximum operating current
Starting current
Number of capacity steps
EVAPORATOR
n.
A
A
n.
n.
Type (6)
Water volume l
Maximum water flow m³/h
TOTAL HEAT RECOVERY EXCHANGER
n.
Water volume l
Maximum water flow m³/h
PARTIAL HEAT RECOVERY EXCHANGER
n.
Water volume l
Maximum water flow m³/h
AXIAL FANS (AC)
Total air flow
Absorbed power
Nominal operating current Compressors
Maximum external static pressure
AXIAL FANS (EC)
Total air flow
Absorbed power
Nominal operating current Compressors
Maximum external static pressure
scroll
scroll
scroll
scroll
scroll
4
262
506
4
4
296
621
4
4
330
656
4
6
342
586
6
6
359
603
6
1
1
1
1
1
PHE
22.8
108.7
PHE
26
120.8
PHE
29.2
132.3
S&T
133.4
138
S&T
133.4
148.4
1
1
1
--
--
22.8
105
26
119
29.2
133
---
---
2
2
2
3
3
4.6
29.4
5.6
32.7
6.4
35.8
6.2
37.4
7
40.3
n.
6
6
6
6
8
m³/h
kW
A
Pa
127080
9.5
23.4
0
127080
9.5
23.4
0
127080
9.5
23.4
0
127080
9.5
23.4
0
169440
12.6
31.2
0
n.
6
6
6
6
8
m³/h
kW
A
Pa
127080
7.7
23.4
80
127080
7.7
23.4
80
127080
7.7
23.4
80
127080
7.7
23.4
80
169440
10.2
31.2
80
REFRIGERANT
R410A
R410A
R410A
R410A
R410A
28.1
2
28.3
2
28.3
2
29.9
3
38.6
3
400/3/50
400/3/50
400/3/50
400/3/50
400/3/50
3.01
4.06
2.88
3.87
2.75
3.69
2.74
3.67
2.97
3.98
71.2
90.7
73.6
93
75.1
94.6
72.9
92.4
72.9
93
GPVM1/1
GPVB1/1
GPVM1/2
GPVB1/2
190
GPVM2/1
GPVB2/1
GPVM2/2
GPVB2/2
190
GPVM2/1
GPVB2/1
GPVM2/2
GPVB2/2
190
GPVM2/1
GPVB2/1
GPVM2/2
GPVB2/2
-
GPVM2/1
GPVB2/1
GPVM2/2
GPVB2/2
-
Length mm
Width mm
Height mm
3530
2260
2304
3530
2260
2304
3530
2260
2304
3530
2260
2304
4650
2260
2304
kg
2310
2360
2410
2980
3270
Ø mm
88.9
88.9
88.9
168.3
168.3
Ø
Ø
-2 x 1"
-2 x 1"
-2 x 1"
-3 x 1"
-3 x 1"
Ø mm
88.9
88.9
88.9
--
--
Total refrigerant load (excluding options) kg
Number of refrigerant circuits n.
SUPPLY VOLTAGE
ENERGY EFFICIENCY RATIOS (1)
V/Ph/Hz
EER kW/kW
ESEER = Eurovent standard
SOUND LEVELS
Mean sound pressure level [Lpm] (4) dB(A)
Sound power level (Lw) dB(A)
HYDRAULIC KIT
Medium pressure single pump
Low pressure single pump
Medium pressure double pump
Low pressure double pump
Water tank volume l
DIMENSIONS
NET WEIGHT
HYDRAULIC CONNECTIONS
EVAPORATOR
Inlet outlet diameter
PARTIAL HEAT RECOVERY EXCHANGER
Inlet outlet diameter – ISO 7/1 – R
Inlet outlet diameter – ISO 228/1-GM
TOTAL HEAT RECOVERY EXCHANGER
Inlet outlet diameter
(1) Gross value - chilled water temperature 12/7°C; outdoor temperature 35°C.
(2) Gross value - chilled water temperature 12/7°C and hot water temperature 40/45°C.
(3) Gross value - chilled water temperature 12/7°C; outdoor temperature 35°C and hot water
temperature 40/45°C.
22
500.3
540.3
560.3
610.3
630.3
680.4
720.4
750.4
800.4
830.4
497
160
274
85.4
43
526
178
303
90.5
48
547
177
303
94.1
51
602
207
350
104
58
615
202
342
106
60
666
201
349
114
67
701
220
378
120
74
729
238
406
125
81
775
256
435
133
87
808
276
467
139
55
-------
-------
-------
-------
-------
-------
-------
-------
-------
-------
182
31.4
32
193
33.3
30.2
201
34.6
32.6
221
38.1
36.2
226
38.9
37.7
244
42.1
32.4
257
44.3
30.1
267
46.1
32.5
284
49
33.7
296
51
36.6
scroll
scroll
scroll
scroll
scroll
scroll
scroll
scroll
scroll
scroll
6
393
718
6
6
427
753
6
6
444
769
6
6
496
821
6
6
496
821
6
8
523
866
8
8
558
883
8
8
592
917
8
8
626
952
8
8
661
986
8
1
1
1
1
1
1
1
1
1
1
S&T
124.7
161
S&T
124.7
170.2
S&T
124.7
177.1
S&T
221.7
195.5
S&T
221.7
200.1
S&T
221.7
215.1
S&T
206.5
226.6
S&T
206.5
235.8
S&T
206.5
250.7
S&T
184.4
262.2
--
--
--
--
--
--
--
--
--
--
---
---
---
---
---
---
---
---
---
---
3
3
3
3
3
4
4
4
4
4
7
43.4
8.4
46.3
9.6
48.4
9.6
53.1
9.6
54.3
9.3
58.5
11.2
61.6
11.2
64.6
12.7
68.8
12.7
71.4
8
8
9
9
10
12
12
12
12
12
169440
12.6
31.2
0
169440
12.6
31.2
0
190620
14.2
35.1
0
190620
14.2
35.1
0
211800
15.8
39
0
254160
19
46.8
0
254160
19
46.8
0
254160
19
46.8
0
254160
19
46.8
0
254160
19
46.8
0
8
8
9
9
10
12
12
12
12
12
169440
10.2
31.2
80
169440
10.2
31.2
80
190620
11.5
35.1
80
190620
11.5
35.1
80
211800
12.8
39
80
254160
15.4
46.8
80
254160
15.4
46.8
80
254160
15.4
46.8
80
254160
15.4
46.8
80
254160
15.4
46.8
80
R410A
R410A
R410A
R410A
R410A
R410A
R410A
R410A
R410A
R410A
38.6
3
38.6
3
42.4
3
42.6
3
46.4
3
56.3
4
56.6
4
56.6
4
56.6
4
56.7
4
400/3/50
400/3/50
400/3/50
400/3/50
400/3/50
400/3/50
400/3/50
400/3/50
400/3/50
400/3/50
2.88
3.83
2.76
3.69
2.86
3.83
2.72
3.66
2.82
3.8
3.03
4.11
2.93
4.01
2.84
3.9
2.82
3.86
2.74
3.75
74.3
94.3
75.9
95.9
75.3
95.8
76.9
97.4
76.9
97.4
74.2
95.1
75.5
96.5
76.6
97.5
77.4
98.3
78.1
99
GPVM2/1
GPVB2/1
GPVM2/2
GPVB2/2
-
GPVM2/1
GPVB2/1
GPVM2/2
GPVB2/2
-
GPVM2/1
GPVB2/1
GPVM2/2
GPVB2/2
-
GPVM2/1
GPVB2/1
GPVM2/2
GPVB2/2
-
GPVM2/1
GPVB2/1
GPVM2/2
GPVB2/2
-
GPVM2/1
GPVB2/1
GPVM2/2
GPVB2/2
-
GPVM3/1
GPVB3/1
GPVM3/2
GPVB3/2
-
GPVM3/1
GPVB3/1
GPVM3/2
GPVB3/2
-
GPVM3/1
GPVB3/1
GPVM3/2
GPVB3/2
-
GPVM3/1
GPVB3/1
GPVM3/2
GPVB3/2
-
4650
2260
2304
4650
2260
2304
5770
2260
2304
5770
2260
2304
5770
2260
2304
6890
2260
2304
6890
2260
2304
6890
2260
2304
6890
2260
2304
6890
2260
2304
3330
3360
3700
3940
3940
4530
4600
4630
4670
4750
168.3
168.3
168.3
219.1
219.1
219.1
219.1
219.1
219.1
219.1
-3 x 1"
-3 x 1"
-3 x 1"
-3 x 1"
-3 x 1"
-4 x 1"
-4 x 1"
-4 x 1"
-4 x 1"
-4 x 1"
--
--
--
--
--
--
--
--
--
--
(4) Sound pressure level [Lpm] at 1m far according to ISO EN 3744
(5) Sound power level [Lw] according to ISO EN 9614-2.
(6) PHE = Brazed-plate heat EXCHANGER; S&T = Shell and tube heat EXCHANGER
23
LIQUID CHILLERS | AIR-COOLED
EQPH
128 / 830
Reversible
SCROLL COMPRESSORS
Cooling capacities from 117 to 772 kW
Heating capacities from 132 to 932 kW
26 sizes
Refrigerant: R410A
EER up to 2.74
ESEER up to 3.65
COP up to 3.18
MAIN FEATURES
Available with 1, 2, 3 or 4 refrigeration circuits
2 SCROLL compressors per circuit, fitted on
antivibration mounts
Modern and modular design
Shell and tube evaporator from size 430
AVAILABLE VERSIONS
Partial heat recovery version
ELN extra low sound level version
EC motor for external static pressure version
Brine low and very low temperature versions
All-year-round operation as a standard feature (-10°C)
Advantages
Wide power range covered by scroll technology with
maximum reliability (multiple circuits)
2 Scroll compressors per circuit for greater efficiency and
reliability
Electronic expansion valve as standard
High COP
Dialogue interface with screen and graphical icons for easier
reading
Large choice of sound levels
EC fan motors for available pressure
Remote demand limit via additional electronic board
Analog setpoint compensation
Easy maintenance
Operating limits (standard model)
Main accessories and options
Code
79 Electrical panel heating resistance
83 Compressor operation indicator
101 EC fan motors
118 Kit A leaving chilled water low temperature operation
119 Kit B leaving chilled water low temperature operation
150 Kit LNO low sound level
170 Antivibration mounts - spring - supplied loose
171 Antivibration mounts - rubber - supplied loose
180 Power factor capacitor for compressor motor
183 Full Victaulic connection
251 Coil protection kit
350 Coil protection against agressive environment
449 Partial heat recovery dry contact for activation
of circulation pump
450 Desuperheater
459 Shell and tube evaporator
720 Medium pressure single pump kit
721 Medium pressure double pump kit
722 Low pressure single pump kit
723 Low pressure double pump kit
725 Water tank + 1 medium pressure pump
726 Water tank + 2 medium pressure pumps
727 Water tank + 1 low pressure pump
728 Water tank + 2 low pressure pumps
923 COM MBUS/JBUS serial card
926 LON serial card
931 BACnet Ethernet - SNMP - TCP/IP serial card
934 MP.COM extension card
943 Data logger
Besides these options, please speak to our Sales Department for any other
configuration or function that is not listed as being available.
COOLING OPERATION
Water leaving temperature (no glycol) 5 / 20ºC
Water leaving temperature (with glycol max 40%) -12 / 5°C
Max outdoor air temperature 45°C
Min outdoor air temperature -10°C
HEATING OPERATION
Max water leaving temperature 55°C
Max outdoor air temperature 20°C
Min outdoor air temperature -10°C
24
EQPH 128 / 830 Reversible
TECHNICAL SPECIFICATIONS
SIZE
128.1
128.2
146.1
146.2
164.1
164.2
186.1
Cooling capacity kW
117
117
138
138
155
155
175
Compressors absorbed power kW
42.6
42.6
46.3
46.3
52.3
52.3
60.1
72.6
72.6
79.6
79.6
89.5
89.6
102
Entering water temperature °C
12
12
12
12
12
12
12
Leaving water temperature °C
7
7
7
7
7
7
7
20.1
20.1
23.7
23.7
26.7
26.7
30.1
Evaporator pressure loss kPa
45
41
50
55
47
51
49
Outdoor air temperature °C
35
35
35
35
35
35
35
Heating capacity kW
132
132
153
153
173
177
197
Compressors absorbed power kW
41.1
41
47.8
47.7
53.6
53.2
61.2
70.8
70.8
81.7
81.7
91.6
90.8
104
Entering water temperature °C
39.3
39.3
39.4
39.4
39.4
39.2
39.3
Leaving water temperature °C
45
45
45
45
45
45
45
Outdoor air temperature °C
7
7
7
7
7
7
7
scroll
scroll
scroll
scroll
scroll
scroll
scroll
Quantity n.
2
2
2
2
2
2
2
97
97
114
113.9
97
131
148
321
320.5
359
358.5
321
320.5
473
2
2
2
2
2
2
2
1
1
1
1
1
1
1
8
8.8
9
8.8
11
8.6
12
28.1
28.1
33.1
33.1
37.3
37.4
42.1
0
0
0
0
0
0
0
SUMMER operation (1)
Nominal operating current Compressors A
Evaporator water flow m³/h
WINTER operation (2)
Nominal operating current Compressors A
COMPRESSORS
Maximum operating current A
Starting current A
Number of capacity steps n.
EVAPORATOR (brazed-plate)
n.
Water volume l
Maximum water flow m³/h
Antifreeze %
Fouling factor m²°K/kW 0.043
0.043
0.043
0.043
0.043
0.043
0.043
2
2
3
3
3
3
3
36900
36900
56700
56700
56700
56700
55350
2.8
2.8
4.3
4.3
4.3
4.3
4.3
7.8
7.8
11.7
11.7
11.7
11.7
11.7
R410A
R410A
R410A
R410A
R410A
R410A
R410A
44.6
47.7
52.1
55.7
53
56.7
65.6
1
2
1
2
1
2
1
400/3/50
400/3/50
400/3/50
400/3/50
400/3/50
400/3/50
400/3/50
EER EUROVENT kW/kW
2.53
2.53
2.67
2.67
2.69
2.69
2.67
COP EUROVENT kW/kW
2.98
2.99
2.91
2.91
2.96
3.05
2.98
3.41
3.42
3.61
3.62
3.64
3.65
3.61
Sound pressure level at 1 m in free field conditions
dB(A)
(Lpm) (ISO3744)
63.9
63.8
64.1
64.1
64.1
64.1
66.1
Sound power level (Lw) (ISO EN 9614-2) dB(A)
81.9
81.9
83
83
83
83
85
Length mm
2960
2960
4000
4000
4000
4000
4000
Width mm
1200
1200
1200
1200
1200
1200
1200
Height mm
1950
1950
1970
1970
1970
1970
1970
kg
1065
1097
1160
1194
1182
1217
1277
AXIAL FANS (AC)
n.
Total air flow m³/h
Absorbed power kW
Fans maximum operating current A
REFRIGERANT
Total refrigerant load kg
Number of refrigerant circuits n.
SUPPLY VOLTAGE
V/ph/Hz
ENERGY EFFICIENCY RATIOS (1)
ESEER = Eurovent Standard
SOUND LEVELS
DIMENSIONS
NET WEIGHT
➜
(1) Gross value - chilled water temperature 12/7°C; outdoor temperature 35°C.
(2) Gross value - hot water outlet temperature 45°C and outdoor temperature 7°C.
25
LIQUID CHILLERS | AIR-COOLED
EQPH 128 / 830 Reversible
TECHNICAL SPECIFICATIONS
SIZE
186.2
204.1
204.2
215.2
235.2
255.2
305.2
Cooling capacity kW
175
194
195
194
210
242
274
Compressors absorbed power kW
60.2
68.6
68.6
66.9
76.9
81.1
96.7
102
115
116
120
132
140
165
12
12
12
12
12
12
12
SUMMER operation (1)
Nominal operating current Compressors A
Entering water temperature °C
Leaving water temperature °C
7
7
7
7
7
7
7
30.1
33.4
33.5
33.4
36.2
41.5
47
Evaporator pressure loss kPa
48
47
46
47
46
51
43
Outdoor air temperature °C
35
35
35
35
35
35
35
Heating capacity kW
201
218
222
220
240
281
315
Compressors absorbed power kW
60.8
68.7
68.2
67
74.5
83.4
94.9
103
116
115
120
129
143
162
Entering water temperature °C
39.2
39.3
39.2
39.3
39.2
39.1
39.2
Leaving water temperature °C
Evaporator water flow m³/h
WINTER operation (2)
Nominal operating current Compressors A
45
45
45
45
45
45
45
Outdoor air temperature °C
7
7
7
7
7
7
7
scroll
scroll
scroll
scroll
scroll
scroll
scroll
Quantity n.
2
2
2
4
4
4
4
148
165
165.2
165
177
194
228
473.4
491
490.6
389
401
418
472
COMPRESSORS
Maximum operating current A
Starting current A
Number of capacity steps n.
EVAPORATOR (brazed-plate)
n.
Water volume l
Maximum water flow m³/h
Antifreeze %
2
2
2
4
4
4
4
1
1
1
1
1
1
1
9.8
14
11.7
11.7
13.3
15.1
22.8
42.1
46.7
46.8
46.7
50.5
58.1
65.7
0
0
0
0
0
0
0
Fouling factor m²°K/kW 0.043
0.043
0.043
0.043
0.043
0.043
0.043
3
3
3
4
4
6
6
55350
55350
55350
68400
68400
106920
106920
4.3
4.3
4.3
5.7
5.7
8.5
8.5
11.7
11.7
11.7
15.6
15.6
23.4
23.4
R410A
R410A
R410A
R410A
R410A
R410A
R410A
70.2
66
70.6
67.2
69.2
76.2
77.4
2
1
2
2
2
2
2
400/3/50
400/3/50
400/3/50
400/3/50
400/3/50
400/3/50
400/3/50
EER EUROVENT kW/kW
2.67
2.62
2.63
2.63
2.5
2.66
2.57
COP EUROVENT kW/kW
3.06
2.96
3.04
3
2.97
3.04
3.03
3.61
3.54
3.55
3.59
3.42
3.62
3.49
66.1
67.5
67.5
68.9
70
71.2
71.2
85
86.4
86.4
87.7
88.8
90.7
90.7
AXIAL FANS (AC)
n.
Total air flow m³/h
Absorbed power kW
Fans maximum operating current A
REFRIGERANT
Total refrigerant load kg
Number of refrigerant circuits n.
SUPPLY VOLTAGE
V/ph/Hz
ENERGY EFFICIENCY RATIOS (1)
ESEER = Eurovent Standard
SOUND LEVELS
Sound pressure level at 1 m in free field conditions
dB(A)
(Lpm) (ISO3744)
Sound power level (Lw) (ISO EN 9614-2) dB(A)
DIMENSIONS
NET WEIGHT
Length mm
4000
4000
4000
2410
2410
3530
3530
Width mm
1200
1200
1200
2260
2260
2260
2260
Height mm
1970
1970
1970
2304
2304
2304
2304
kg
1316
1296
1335
1957
2114
2458
2507
(1) Gross value - chilled water temperature 12/7°C; outdoor temperature 35°C.
(2) Gross value - hot water outlet temperature 45°C and outdoor temperature 7°C.
26
340.2
380.2
410.2
430.3
470.3
500.3
560.3
610.3
680.4
750.4
800.4
830.4
306
340
380
408
430
469
506
542
615
666
729
772
108
127
142
145
147
165
190
221
217
254
265
274
184
213
238
247
251
279
320
369
368
427
445
461
12
12
12
12
12
12
12
12
12
12
12
12
7
7
7
7
7
7
7
7
7
7
7
7
52.7
58.5
65.4
70.3
74
80.8
87.1
92.9
106
114
126
133
45
43
46
31
34
40
44
50
59
70
80
57
35
35
35
35
35
35
35
35
35
35
35
35
359
402
456
482
512
558
617
678
728
823
873
932
104
122
137
142
148
163
179
201
213
238
258
274
178
206
230
243
253
278
304
339
364
404
436
461
39.1
39
38.9
39
39
39
38.8
38.7
39
38.7
39
38.9
45
45
45
45
45
45
45
45
45
45
45
45
7
7
7
7
7
7
7
7
7
7
7
7
scroll
scroll
scroll
scroll
scroll
scroll
scroll
scroll
scroll
scroll
scroll
scroll
4
4
4
6
6
6
6
6
8
8
8
8
262
296
330
342
359
393
444
496
523
592
626.4
660.8
506
621
656
586
603
718
769
821
866
917
951.8
986.2
4
4
4
6
6
6
6
6
8
8
8
8
1
1
1
1
1
1
1
1
1
1
1
1
22.8
26
29.2
133.4
124.7
124.7
221.7
221.7
221.7
206.5
184.4
184.4
73.6
81.7
91.4
107
110
110
135
135
135
160
190
190
0
0
0
0
0
0
0
0
0
0
0
0
0.043
0.043
0.043
0.043
0.043
0.043
0.043
0.043
0.043
0.043
0.043
0.043
6
6
8
9
9
9
9
9
12
12
14
16
102600
102600
142560
160380
153900
153900
153900
153900
205200
205200
239400
273600
8.5
8.5
11.4
12.8
12.8
12.8
12.8
12.8
17.1
17.1
19.9
22.8
23.4
23.4
31.2
35.1
35.1
35.1
35.1
35.1
46.8
46.8
54.6
62.4
R410A
R410A
R410A
R410A
R410A
R410A
R410A
R410A
R410A
R410A
R410A
R410A
100.9
101.9
102.9
141.9
162.5
164
182.5
182.5
233.3
237.8
269.4
294.8
2
2
2
3
3
3
3
3
4
4
4
4
400/3/50
400/3/50
400/3/50
400/3/50
400/3/50
400/3/50
400/3/50
400/3/50
400/3/50
400/3/50
400/3/50
400/3/50
2.59
2.48
2.45
2.56
2.66
2.61
2.47
2.29
2.59
2.42
2.51
2.56
3.17
3.06
3.05
3.1
3.17
3.16
3.2
3.15
3.14
3.2
3.11
3.12
3.52
3.37
3.33
3.48
3.62
3.55
3.36
3.11
3.53
3.3
3.44
3.5
71.2
73.6
75.1
72.9
72.9
74.3
75.3
76.8
74.2
76.6
77.4
78.1
90.7
93
95.1
93.4
93.4
94.8
95.8
97.3
95.1
97.5
98.8
99.8
3530
3530
4650
5770
5770
5770
5770
5770
6890
6890
8010
9130
2260
2260
2260
2260
2260
2260
2260
2260
2260
2260
2260
2260
2304
2304
2304
2304
2304
2304
2304
2304
2304
2304
2304
2304
2681
2739
3015
3876
4029
4087
4422
4461
5213
5358
5600
5789
27
LIQUID CHILLERS | AIR-COOLED
EQPLA
106 / 860
Class A
Cooling only
SCROLL COMPRESSORS
CLASS A
Cooling capacities from 210 to 808 kW
31 sizes
Refrigerant: R410A
EER up to 3.25
ESEER up to 4.35
Class A
MAIN FEATURES
Available with 2, 3 or 4 refrigeration circuits
2 SCROLL compressors per circuit, fitted on
antivibration mounts
All aluminium microchannel condenser
Modern and modular design
Shell and tube evaporator from size 430
Cooling operating limits
Indicative values. The operating T° are influenced by a
series of settings such as: operating conditions, thermal
load, adjustments, etc... Data to be confirmed upon
selection.
AVAILABLE VERSIONS
20
Water outlet temperature
from the evaporator
Partial heat recovery version
Full heat recovery version
ELN extra low sound level version
EC motor for external static pressure version
Brine low and very low temperature versions
All-year-round operation as a standard feature (-12°C)
(°C)
15
10
5
0
Glycol solution
+ low temperature kit A
-5
Glycol solution
+ low temperature kit B
-10
-13
Main accessories and options
Code
79 Electrical panel heating resistance
101 EC fan motors
118 Kit A leaving chilled water low temperature operation
119 Kit B leaving chilled water low temperature operation
150 Kit LNO low sound level
170 Antivibration mounts - spring - supplied loose
171 Antivibration mounts - rubber - supplied loose
183 Full Victaulic connection
350 Coil protection against agressive environment
449 Partial heat recovery dry contact for activation
of circulation pump
450 Desuperheater
451 Total heat recovery
454 Total heat recovery dry contact for activation
of circulation pump
720 Medium pressure single pump kit
721 Medium pressure double pump kit
722 Low pressure single pump kit
723 Low pressure double pump kit
725 Water tank + 1 medium pressure pump
726 Water tank + 2 medium pressure pumps
727 Water tank + 1 low pressure pump
728 Water tank + 2 low pressure pumps
923 COM MBUS/JBUS serial card
926 LON serial card
931 BACnet Ethernet - SNMP - TCP/IP serial card
934 MP.COM extension card
943 Data logger
-10
-5
0
5
10
15
20
25
30
35
40
45
(°C)
Outdoor air temperature
Advantages
Class A
Wide power range covered by scroll technology with
maximum reliability (multiple circuits)
2 Scroll compressors per circuit for greater efficiency
and reliability
Electronic expansion valve as standard
High ESEER
Dialogue interface with screen and graphical icons
for easier reading
Refrigerant load reduced thanks to microchannel technology
Large choice of sound levels
Partial or total heat recovery
EC fans for available pressure
Remote demand limit via additional electronic board
Analog setpoint compensation
Easy maintenance
Besides these options, please speak to our Sales Department for any other
configuration or function that is not listed as being available.
28
EQPLA 106 / 860 Cooling only
SIZE
TECHNICAL SPECIFICATIONS
106.1
128.2
132.1
140.2
153.2
kW
kW
A
m³/h
kPa
108
31.8
58.2
18.6
33
124
35.2
64
21.4
46
134
38.9
68.5
23
34
139
40.4
74.6
23.9
39
152
43.6
83.4
26.1
46
kW
kW
kW
A
m³/h
kPa
105
138
33.1
59.9
24.1
38
119
157
37.9
68
27.3
58
129
170
41
71.1
29.6
36
136
178
41.9
76.7
30.9
55
147
193
46.2
87.1
33.5
64
Heating capacity kW
Heat recovery exchanger water flow m³/h
Heat recovery pressure loss kPa
39.7
6.8
27.2
45.7
7.9
18.7
49.1
8.5
29.4
51.1
8.8
23.4
55.7
9.6
19
COOLING ONLY (1)
Cooling capacity
Compressors absorbed power
Nominal operating current Compressors
Evaporator water flow
Evaporator pressure loss
COOLING ONLY + HEAT RECOVERY 100% (2)
Cooling capacity
Heating capacity
Compressors absorbed power
Nominal operating current Compressors
Heat recovery exchanger water flow
Heat recovery pressure loss
PARTIAL HEAT RECOVERY (3)
COMPRESSORS
Quantity
Maximum operating current
Starting current
Number of capacity steps
EVAPORATOR
n.
A
A
n.
n.
Type (6)
Water volume l
Maximum water flow m³/h
TOTAL HEAT RECOVERY EXCHANGER
n.
Water volume l
Maximum water flow m³/h
PARTIAL HEAT RECOVERY EXCHANGER
n.
Water volume l
Maximum water flow m³/h
AXIAL FANS (AC)
Total air flow
Absorbed power
Nominal operating current Compressors
Maximum external static pressure
AXIAL FANS (EC)
Total air flow
Absorbed power
Nominal operating current Compressors
Maximum external static pressure
scroll
scroll
scroll
scroll
scroll
2
83
306
2
4
100
193
4
2
97
321
2
4
124
233
4
4
130
270
4
1
1
1
1
1
PHE
11
35.1
PHE
8.6
40.5
PHE
11
43.5
PHE
9.8
45.3
PHE
9.8
49.5
1
1
1
1
1
11
33.7
8.6
38.2
11
41.4
9.8
43.3
9.8
46.9
1
2
1
2
2
1.4
9.5
1.7
11
1.7
11.8
1.7
12.3
2.2
13.4
n.
4
6
6
6
6
m³/h
kW
A
Pa
38940
2.2
7.9
0
53340
3.2
7.9
0
53340
3.2
7.9
0
53340
3.2
7.9
0
59300
3.2
7.9
0
n.
4
6
6
6
6
m³/h
kW
A
Pa
38940
1.6
6.4
0
53340
2.3
9.6
0
53340
2.3
9.6
0
53340
2.3
9.6
0
59300
2.3
9.6
0
REFRIGERANT
R410A
R410A
R410A
R410A
R410A
12
1
12
2
12.4
1
12.1
2
23.3
2
400/3/50+N
400/3/50+N
400/3/50+N
400/3/50+N
400/3/50+N
3.18
4.2
3.23
4.34
3.18
4.22
3.19
4.27
3.25
4.35
57.3
75.5
55.5
73.7
59.4
77.5
55.9
74.1
56.1
74.7
GPWM1/1
GPWB1/1
GPWM1/2
GPWB1/2
200
GPWM1/1
GPWB1/1
GPWM1/2
GPWB1/2
200
GPWM1/1
GPWB1/1
GPWM1/2
GPWB1/2
200
GPWM1/1
GPWB1/1
GPWM1/2
GPWB1/2
200
GPWM1/1
GPWB1/1
GPWM1/2
GPWB1/2
200
Length mm
Width mm
Height mm
2455
1750
2110
2455
1750
2110
2455
1750
2110
2455
1750
2110
2455
1750
2410
kg
1250
1310
1390
1330
1300
Ø mm
73.1
73.1
73.1
73.1
73.1
Ø
nxØ
1"
--
1"
--
1"
--
1"
--
1"
--
Ø mm
73.1
73.1
73.1
73.1
73.1
Total refrigerant load (excluding options) kg
Number of refrigerant circuits n.
SUPPLY VOLTAGE
ENERGY EFFICIENCY RATIOS (1)
V/Ph/Hz
EER kW/kW
ESEER = Eurovent standard
SOUND LEVELS
Average sound pressure level [Lpm] (4) dB(A)
Sound power level (Lw) dB(A)
HYDRAULIC KIT
Medium pressure single pump
Low pressure single pump
Medium pressure double pump
Low pressure double pump
Water tank volume l
DIMENSIONS
NET WEIGHT
HYDRAULIC CONNECTIONS
EVAPORATOR
Inlet outlet diameter
PARTIAL HEAT RECOVERY EXCHANGER
Inlet outlet diameter – ISO 7/1 – R
Inlet outlet diameter – ISO 228/1-GM
TOTAL HEAT RECOVERY EXCHANGER
Inlet outlet diameter
(1) Gross value - chilled water temperature 12/7°C; outdoor temperature 35°C.
(2) Gross value - chilled water temperature 12/7°C and hot water temperature 40/45°C.
(3) Gross value - chilled water temperature 12/7°C; outdoor temperature 35°C and hot
water temperature 40/45°C.
(4) Sound pressure level [Lpm] at 1m far according to ISO EN 3744
(5) Sound power level [Lw] according to ISO EN 9614-2.
(6) PHE = Brazed-plate heat EXCHANGER; S&T = Shell and tube heat EXCHANGER
29
➜
LIQUID CHILLERS | AIR-COOLED
EQPLA 106 / 860 Cooling only
TECHNICAL SPECIFICATIONS
SIZE
164.2
168.1
168.2
184.2
190.2
kW
kW
A
m³/h
kPa
164
48.4
94.5
28.2
42
170
50.6
87.6
29.2
25
171
50.6
87.7
29.4
34
185
55.2
101
31.8
35
189
53.3
99.7
32.4
43
kW
kW
kW
A
m³/h
kPa
161
211
50.2
97
36.6
64
166
218
52.4
90.2
38
20
164
218
54
92.4
37.9
52
186
241
54.8
101
41.9
65
181
238
57.1
105
41.4
69
Heating capacity kW
Heat recovery exchanger water flow m³/h
Heat recovery pressure loss kPa
60.4
10.4
22.3
62.3
10.7
33.7
62.7
10.8
24.1
68
11.7
20
69.2
11.9
14.6
COOLING ONLY (1)
Cooling capacity
Compressors absorbed power
Nominal operating current Compressors
Evaporator water flow
Evaporator pressure loss
COOLING ONLY + HEAT RECOVERY 100% (2)
Cooling capacity
Heating capacity
Compressors absorbed power
Nominal operating current Compressors
Heat recovery exchanger water flow
Heat recovery pressure loss
PARTIAL HEAT RECOVERY (3)
COMPRESSORS
Quantity
Maximum operating current
Starting current
Number of capacity steps
EVAPORATOR
n.
A
A
n.
n.
Type (6)
Water volume l
Maximum water flow m³/h
TOTAL HEAT RECOVERY EXCHANGER
n.
Water volume l
Maximum water flow m³/h
PARTIAL HEAT RECOVERY EXCHANGER
n.
Water volume l
Maximum water flow m³/h
AXIAL FANS (AC)
Total air flow
Absorbed power
Nominal operating current Compressors
Maximum external static pressure
AXIAL FANS (EC)
Total air flow
Absorbed power
Nominal operating current Compressors
Maximum external static pressure
scroll
scroll
scroll
scroll
scroll
4
136
276
4
2
131
375
2
2
131
375
2
4
148
259
4
4
148
333
4
1
1
1
1
1
PHE
11.7
53.5
PHE
14
55.2
PHE
11.7
55.5
PHE
13.3
60.3
PHE
13.3
61.3
1
1
1
1
1
11.7
51.2
14
53.2
11.7
53.1
13.3
58.7
13.3
58
2
1
2
2
2
2.2
14.5
2.3
15
2.2
15.1
2.7
16.4
3.5
16.7
n.
6
6
6
6
4
m³/h
kW
A
Pa
59300
3.2
7.9
0
59300
3.2
7.9
0
59300
3.2
7.9
0
59300
3.2
7.9
0
84720
6.3
15.6
0
n.
6
6
6
6
4
m³/h
kW
A
Pa
59300
2.3
9.6
0
59300
2.3
9.6
0
59300
2.3
9.6
0
59300
2.3
9.6
0
84720
5.1
15.6
80
REFRIGERANT
R410A
R410A
R410A
R410A
R410A
24.1
2
21.3
1
24.3
2
25
2
19
2
400/3/50+N
400/3/50+N
400/3/50+N
400/3/50+N
400/3/50
3.18
4.27
3.16
4.19
3.18
3.63
3.17
4.25
3.17
4.24
56.3
74.9
59.4
77.9
59.4
77.9
58.1
76.7
66.7
85.5
GPWM1/1
GPWB1/1
GPWM1/2
GPWB1/2
200
GPWM1/1
GPWB1/1
GPWM1/2
GPWB1/2
200
GPWM1/1
GPWB1/1
GPWM1/2
GPWB1/2
200
GPWM1/1
GPWB1/1
GPWM1/2
GPWB1/2
200
GPVM1/1
GPVB1/1
GPVM1/2
GPVM1/2
130
Length mm
Width mm
Height mm
2455
1750
2410
2455
1750
2410
2455
1750
2410
2455
1750
2410
2410
2260
2304
kg
1440
1540
1530
1390
1700
Ø mm
73.1
73.1
73.1
73.1
88.9
Ø
nxØ
1"
--
1"
--
1"
--
1"
--
-2 x 1"
Ø mm
73.1
73.1
73.1
73.1
88.9
Total refrigerant load (excluding options) kg
Number of refrigerant circuits n.
SUPPLY VOLTAGE
ENERGY EFFICIENCY RATIOS (1)
V/Ph/Hz
EER kW/kW
ESEER = Eurovent standard
SOUND LEVELS
Average sound pressure level [Lpm] (4) dB(A)
Sound power level (Lw) dB(A)
HYDRAULIC KIT
Medium pressure single pump
Low pressure single pump
Medium pressure double pump
Low pressure double pump
Water tank volume l
DIMENSIONS
NET WEIGHT
HYDRAULIC CONNECTIONS
EVAPORATOR
Inlet outlet diameter
PARTIAL HEAT RECOVERY EXCHANGER
Inlet outlet diameter – ISO 7/1 – R
Inlet outlet diameter – ISO 228/1-GM
TOTAL HEAT RECOVERY EXCHANGER
Inlet outlet diameter
(1) Gross value - chilled water temperature 12/7°C; outdoor temperature 35°C.
(2) Gross value - chilled water temperature 12/7°C and hot water temperature 40/45°C.
(3) Gross value - chilled water temperature 12/7°C; outdoor temperature 35°C and hot water
temperature 40/45°C.
30
214.2
236.2
270.2
304.2
340.2
374.2
390.2
410.2
430.2
455.3
218
62.5
115
37.5
38
235
68.8
121
40.3
38
271
75.1
134
46.6
33
308
87.7
154
52.9
43
344
99.2
172
59
35
372
104
180
63.9
41
394
112
194
67.6
35
413
118
203
70.9
39
438
126
215
75.2
38
471
130
228
80.9
38
214
278
64.5
117
48.4
73
234
303
69.1
121
52.7
69
260
341
80.6
141
59.2
46
299
391
92.2
160
67.9
60
340
441
101
174
76.6
52
357
468
111
190
81.2
58
382
499
118
202
86.8
33
402
525
123
210
91.3
61
430
559
129
219
97.2
62
-------
80
13.8
19.5
86.1
14.8
22.6
99.6
17.2
24.6
113
19.5
27.7
126
21.7
34.5
137
23.5
33.9
145
24.9
38
152
26.1
38.3
161
27.7
43
173
29.8
22.2
scroll
scroll
scroll
scroll
scroll
scroll
scroll
scroll
scroll
scroll
4
165
389
4
4
177
401
4
4
194
418
4
4
228
472
4
4
262
506
4
4
279
604
4
4
296
621
4
4
313
639
4
4
330
656
4
6
342
586
6
1
1
1
1
1
1
1
1
1
1
PHE
15.1
71
PHE
15.1
76.4
PHE
18.6
88.3
PHE
26
100.3
PHE
30
111.9
PHE
31.6
120.8
PHE
133.4
127.7
PHE
133.4
134.6
PHE
124.7
142.6
S&T
113.5
153
1
1
1
1
1
1
1
1
1
--
15.1
67.8
15.1
73.8
18.6
82.9
26
95.1
30
107.2
31.6
113.7
133.4
121.5
133.4
127.8
124.7
136.1
---
2
2
2
2
2
2
2
2
2
3
3.5
27
3.5
20.7
4.1
24
4.6
27.2
4.6
30.4
5.6
32.9
6.4
34.8
6.4
36.5
6.4
38.7
7
41.2
4
4
6
6
6
8
8
8
8
10
84720
6.3
15.6
0
84720
6.3
15.6
0
127080
9.5
23.4
0
127080
9.5
23.4
0
127080
9.5
23.4
0
169440
12.6
31.2
0
169440
12.6
31.2
0
169440
12.6
31.2
0
169440
12.6
31.2
0
211800
15.8
39
0
4
4
6
6
6
8
8
8
8
10
84720
5.1
15.6
80
84720
5.1
15.6
80
127080
7.7
23.4
80
127080
7.7
23.4
80
127080
7.7
23.4
80
169440
10.2
31.2
80
169440
10.2
31.2
80
169440
10.2
31.2
80
169440
10.2
31.2
80
211800
12.8
39
80
R410A
R410A
R410A
R410A
R410A
R410A
R410A
R410A
R410A
R410A
19.4
2
20.2
2
27.8
2
27.8
2
28.3
2
36.2
2
36.2
2
36.3
2
36.3
2
41.7
3
400/3/50
400/3/50
400/3/50
400/3/50
400/3/50
400/3/50
400/3/50
400/3/50
400/3/50
400/3/50
3.17
4.25
3.13
4.23
3.2
4.31
3.17
4.25
3.16
4.25
3.19
4.29
3.16
4.23
3.16
4.23
3.16
4.24
3.23
4.23
68.9
87.7
70
88.8
71.2
90.7
71.2
90.7
71.2
90.7
72.6
92.6
73.6
93.6
74.4
94.4
75.1
95.1
73
93.5
GPVM1/1
GPVB1/1
GPVM1/2
GPVM1/2
130
GPVM1/1
GPVB1/1
GPVM1/2
GPVM1/2
130
GPVM1/1
GPVB1/1
GPVM1/2
GPVM1/2
190
GPVM1/1
GPVB1/1
GPVM1/2
GPVM1/2
190
GPVM1/1
GPVB1/1
GPVM1/2
GPVM1/2
190
GPVM2/1
GPVB2/1
GPVM2/2
GPVM2/2
330
GPVM2/1
GPVB2/1
GPVM2/2
GPVM2/2
330
GPVM2/1
GPVB2/1
GPVM2/2
GPVM2/2
330
GPVM2/1
GPVB2/1
GPVM2/2
GPVM2/2
330
GPVM2/1
GPVB2/1
GPVM2/2
GPVM2/2
--
2410
2260
2304
2410
2260
2304
3530
2260
2304
3530
2260
2304
3530
2260
2304
4650
2260
2304
4650
2260
2304
4650
2260
2304
4650
2260
2304
5770
2260
2304
1740
1930
2250
2300
2340
2640
2690
2710
2730
3620
88.9
88.9
88.9
88.9
88.9
114.3
114.3
114.3
114.3
168.3
-2 x 1"
-2 x 1"
-2 x 1"
-2 x 1"
-2 x 1"
-2 x 1"
-2 x 1"
-2 x 1"
-2 x 1"
-3 x 1"
88.9
88.9
88.9
88.9
88.9
114.3
114.3
114.3
114.3
--
(4) Sound pressure level [Lpm] at 1m far according to ISO EN 3744
(5) Sound power level [Lw] according to ISO EN 9614-2.
(6) PHE = Brazed-plate heat EXCHANGER; S&T = Shell and tube heat EXCHANGER
31
➜
LIQUID CHILLERS | AIR-COOLED
EQPLA 106 / 860 Cooling only
TECHNICAL SPECIFICATIONS
SIZE
504.3
530.3
550.3
584.3
604.3
kW
kW
A
m³/h
kPa
523
145
253
89.8
36
539
156
269
92.6
38
563
163
280
96.7
41
593
169
291
102
44
614
175
301
105
47
kW
kW
kW
A
m³/h
kPa
-------
-------
-------
-------
-------
192
33
35.4
198
34.1
37.8
207
35.6
34.5
218
37.5
38.2
225
38.8
37.6
COOLING ONLY (1)
Cooling capacity
Compressors absorbed power
Nominal operating current Compressors
Evaporator water flow
Evaporator pressure loss
COOLING ONLY + HEAT RECOVERY 100% (2)
Cooling capacity
Heating capacity
Compressors absorbed power
Nominal operating current Compressors
Heat recovery exchanger water flow
Heat recovery pressure loss
PARTIAL HEAT RECOVERY (3)
Heating capacity kW
Heat recovery exchanger water flow m³/h
Heat recovery pressure loss kPa
COMPRESSORS
Quantity
Maximum operating current
Starting current
Number of capacity steps
EVAPORATOR
n.
A
A
n.
n.
Type (6)
Water volume l
Maximum water flow m³/h
TOTAL HEAT RECOVERY EXCHANGER
n.
Water volume l
Maximum water flow m³/h
PARTIAL HEAT RECOVERY EXCHANGER
n.
Water volume l
Maximum water flow m³/h
AXIAL FANS (AC)
Total air flow
Absorbed power
Nominal operating current Compressors
Maximum external static pressure
AXIAL FANS (EC)
Total air flow
Absorbed power
Nominal operating current Compressors
Maximum external static pressure
scroll
scroll
scroll
scroll
scroll
6
392
637
6
6
410
735
6
6
427
752
6
6
444
769
6
6
461
787
6
1
1
1
1
1
S&T
221.7
170.2
S&T
221.7
176
S&T
221.7
182.9
S&T
206.5
193.2
S&T
206.5
200.1
--
--
--
--
--
---
---
---
---
---
3
3
3
3
3
7
45.7
9.6
47.7
9.6
49.8
9.6
52.4
9.6
54.3
n.
10
10
10
12
12
m³/h
kW
A
Pa
211800
15.8
39
0
211800
15.8
39
0
211800
15.8
39
0
254160
19
46.8
0
254160
19
46.8
0
n.
10
10
10
12
12
m³/h
kW
A
Pa
211800
12.8
39
80
211800
12.8
39
80
211800
12.8
39
80
254160
15.4
46.8
80
254160
15.4
46.8
80
REFRIGERANT
R410A
R410A
R410A
R410A
R410A
42.4
3
46.6
3
46.6
3
54.4
3
54.4
3
400/3/50
400/3/50
400/3/50
400/3/50
400/3/50
3.25
4.22
3.14
4.22
3.15
4.23
3.15
4.23
3.16
4.23
73
93.5
73.9
94.4
74.7
95.2
75.3
96.3
75.9
96.9
GPVM2/1
GPVB2/1
GPVM2/2
GPVM2/2
--
GPVM2/1
GPVB2/1
GPVM2/2
GPVM2/2
--
GPVM2/1
GPVB2/1
GPVM2/2
GPVM2/2
--
GPVM2/1
GPVB2/1
GPVM2/2
GPVM2/2
--
GPVM2/1
GPVB2/1
GPVM2/2
GPVM2/2
--
Length mm
Width mm
Height mm
5770
2260
2304
5770
2260
2304
5770
2260
2304
6890
2260
2304
6890
2260
2304
kg
3820
3840
3860
4180
4,200
Ø mm
219.1
219.1
219.1
219.1
219.1
Ø
nxØ
-3 x 1"
-3 x 1"
-3 x 1"
-3 x 1"
-3 x 1"
Ø mm
--
--
--
--
--
Total refrigerant load (excluding options) kg
Number of refrigerant circuits n.
SUPPLY VOLTAGE
ENERGY EFFICIENCY RATIOS (1)
V/Ph/Hz
EER kW/kW
ESEER = Eurovent standard
SOUND LEVELS
Average sound pressure level [Lpm] (4) dB(A)
Sound power level (Lw) dB(A)
HYDRAULIC KIT
Medium pressure single pump
Low pressure single pump
Medium pressure double pump
Low pressure double pump
Water tank volume l
DIMENSIONS
NET WEIGHT
HYDRAULIC CONNECTIONS
EVAPORATOR
Inlet outlet diameter
PARTIAL HEAT RECOVERY EXCHANGER
Inlet outlet diameter – ISO 7/1 – R
Inlet outlet diameter – ISO 228/1-GM
TOTAL HEAT RECOVERY EXCHANGER
Inlet outlet diameter
(1) Gross value - chilled water temperature 12/7°C; outdoor temperature 35°C.
(2) Gross value - chilled water temperature 12/7°C and hot water temperature 40/45°C.
(3) Gross value - chilled water temperature 12/7°C; outdoor temperature 35°C and hot water
temperature 40/45°C.
32
646.3
670.3
726.4
780.4
820.4
860.4
655
188
320
112
52
691
200
346
119
32
743
213
368
128
40
769
224
385
132
42
832
237
407
143
37
876
252
429
150
39
-------
-------
-------
-------
-------
-------
240
41.4
42.8
253
43.7
47.6
273
47
40.3
282
48.6
36.2
305
52.6
42.3
321
55.4
43
scroll
scroll
scroll
scroll
scroll
scroll
6
496
821
6
8
523
768
8
8
558
883
8
8
592
917
8
8
626
952
8
8
661
986
8
1
1
1
1
1
1
S&T
206.5
212.8
S&T
184.4
224.3
S&T
184.4
241.5
S&T
184.4
250.7
S&T
225
270.3
S&T
225
285.2
--
--
--
--
--
--
---
---
---
---
---
---
3
3
4
4
4
4
9.6
57.9
9.3
61
11.2
65.7
12.7
68
12.7
73.5
12.7
77.4
12
12
14
14
16
16
254160
19
46.8
0
254160
19
46.8
0
296520
22.1
54.6
0
296520
22.1
54.6
0
338880
25.3
62.4
0
338880
25.3
62.4
0
12
12
14
14
16
16
254160
15.4
46.8
80
254160
15.4
46.8
80
296520
17.9
54.6
80
296520
17.9
54.6
80
338880
20.5
62.4
80
338880
20.5
62.4
80
R410A
R410A
R410A
R410A
R410A
R410A
54.4
3
56.6
4
64.6
4
64.7
4
72.5
4
72.6
4
400/3/50
400/3/50
400/3/50
400/3/50
400/3/50
400/3/50
3.16
4.25
3.16
4.31
3.16
4.31
3.12
4.26
3.17
4.32
3.16
4.32
76.9
97.8
74.2
95.5
77.4
98.8
76.6
97.9
77.4
99.1
78.1
99.8
GPVM2/1
GPVB2/1
GPVM2/2
GPVM2/2
--
GPVM2/1
GPVB2/1
GPVM2/2
GPVM2/2
--
GPVM3/1
GPVB3/1
GPVM3/2
GPVM3/2
--
GPVM3/1
GPVB3/1
GPVM3/2
GPVM3/2
--
GPVM3/1
GPVB3/1
GPVM3/2
GPVM3/2
--
GPVM3/1
GPVB3/1
GPVM3/2
GPVM3/2
--
6890
2260
2304
6890
2260
2304
8010
2260
2304
8010
2260
2304
9130
2260
2304
9130
2260
2304
4240
4860
4900
4940
5300
5340
219.1
219.1
219.1
219.1
219.1
219.1
-3 x 1"
-3 x 1"
-4 x 1"
-4 x 1"
-4 x 1"
-4 x 1"
--
--
--
--
--
--
(4) Sound pressure level [Lpm] at 1m far according to ISO EN 3744
(5) Sound power level [Lw] according to ISO EN 9614-2.
(6) PHE = Brazed-plate heat EXCHANGER; S&T = Shell and tube heat EXCHANGER
33
LIQUID CHILLERS | AIR-COOLED
EQSL
300 / 1310
Cooling only
SCREW COMPRESSORS
Cooling capacities from 299 to 808 kW
20 sizes
Refrigerant: R-134a
EER up to 2.79
ESEER up to 3.34
MAIN FEATURES
Available with 2 refrigeration circuits
2 SCREW compressors mounted on rubber
antivibration mounts
Modern and modular design
Shell and tube evaporator
AVAILABLE VERSIONS
Partial heat recovery version
Total heat recovery version
ELN extra low sound level version
EC motor for external static pressure version
Brine low and very low temperature versions
All-year-round operation as a standard feature (-10°C)
Advantages
Wide power range covered by SCREW technology
Screw compressors per circuit for greater efficiency
and reliability
Electronic expansion valve as standard
Linear step capacity control
Dialogue interface with screen and graphical icons
for easier reading
Large choice of sound levels
Partial or total heat recovery
Remote demand limit via additional electronic board
Analog setpoint compensation
Easy maintenance
Main accessories and options
Code
101
118
119
143
150
151
170
172
175
351
450
451
550
605
650
731
739
740
769
770
919
923
926
931
932
934
942
943
Besides these options, please speak to our Sales Department for any other
configuration or function that is not listed as being available.
(°C)
Cooling operating limits
15
Water outlet temperature
from the evaporator
Indicative values. The operating T° are influenced
by a series of settings such as: operating
conditions, thermal load, adjustments, etc... Data
to be confirmed upon selection.
EC fan motors
Kit A leaving chilled water low temperature operation
Kit B leaving chilled water low temperature operation
Without glycol
Kit LNO low sound level
Kit ELN extra low sound level
Antivibration mounts - spring - supplied loose
Antivibration mounts - rubber - supplied loose
Victaulic connections
Coils with pre-painted fins
Desuperheater
Total heat recovery
Stop valve on compressor suction line
Power factor capacitor for cos phi 0.9 on compressor motor
Compressor thermal relays
Water flow switch
1 pump hydraulic kit
2 pump hydraulic kit
1 pump + 1 standby pump hydraulic kit
2 pump + 1 standby pump hydraulic kit
Clock card
COM MBUS/JBUS serial card
LON serial card
BACnet Ethernet - SNMP - TCP/IP serial card
BACnet MS/TP serial card
MP.COM extension card
Serial card for GSM modem
Data logger
10
5
0
Glycol solution
+ low temperature kit A
-5
Glycol solution
+ low temperature kit B
-10
-13
-20
-15
-10
-5
0
5
10
15
20
Outdoor air temperature
34
25
30
35
40
45(°C)
EQSL 300 / 1310 Cooling only
SIZE
TECHNICAL SPECIFICATIONS
300
320
360
390
430
480
kW
kW
A
m³/h
kPa
299
96
162
51.3
47
315
102
163
54.1
52
335
116
200
57.5
48
391
125
208
67.1
59
430
140
237
73.9
54
476
157
261
81.8
38
kW
kW
kW
A
m³/h
kPa
294
394
100
168
68.5
62
311
417
105
167
72.4
50
333
451
118
202
78.4
61
386
515
129
213
89.5
63
429
570
140
238
99
92
476
633
157
262
108
94
Heating capacity kW
Heat recovery exchanger water flow m³/h
Heat recovery pressure loss kPa
59.5
10.2
6.6
62.7
10.8
7.3
66.7
11.5
8.2
77.8
13.4
8.9
85.6
14.7
4.4
94.7
16.3
4.1
twinscrew
twinscrew
twinscrew
twinscrew
twinscrew
twinscrew
2
201.8
403.9
25…100%
2
205
382.5
25…100%
2
235.6
468.8
25…100%
2
269.6
629.8
25…100%
2
288.2
639.1
25…100%
2
309.3
790.1
25…100%
1
1
1
1
1
1
113
63
113
63
113
63
160
90
160
90
150
95
2
2
2
2
2
2
28
78
32
90
32
90
38
108
38
108
38
108
2
2
2
2
2
2
5
20
5
20
5
20
5
20
6.8
30
6.8
30
COOLING ONLY (1)
Cooling capacity
Compressors absorbed power
Nominal operating current Compressors
Evaporator water flow
Evaporator pressure loss
COOLING ONLY + HEAT RECOVERY 100% (2)
Cooling capacity
Heating capacity
Compressors absorbed power
Nominal operating current Compressors
Heat recovery exchanger water flow
Heat recovery pressure loss
PARTIAL HEAT RECOVERY (3)
COMPRESSORS
Quantity n.
Maximum operating current A
Starting current A
Number of capacity steps
EVAPORATOR (SHELL AND TUBE)
n.
Water volume l
Maximum water flow m³/h
TOTAL HEAT RECOVERY EXCHANGER
n.
Water volume l
Maximum water flow m³/h
PARTIAL HEAT RECOVERY EXCHANGER
n.
Water volume l
Maximum water flow m³/h
AXIAL FANS (AC)
n.
6
6
6
8
8
8
135498
11.6
23.4
135498
11.7
23.4
135498
11.7
23.4
180664
15.4
31.2
180664
15.4
31.2
180664
15.4
31.2
R134a
R134a
R134a
R134a
R134a
R134a
110
2
146
2
146
2
145
2
145
2
145
2
400/3/50
400/3/50
400/3/50
400/3/50
400/3/50
400/3/50
2.78
3.06
2.77
3.03
2.62
3.2
2.78
3.18
2.77
3.1
2.76
3.13
73.1
92.9
71.7
91.4
72
91.8
71.6
91.9
76
96.2
76.2
96.4
GE80/1
-GE80/2
--
GE80/1
-GE80/2
--
GE80/1
-GE80/2
--
GE80/1
-GE80/2
--
GE80/1
-GE80/2
--
GE80/1
-GE80/2
--
Length mm
Width mm
Height mm
3520
2260
2550
3520
2260
2550
3520
2260
2550
4490
2260
2550
4490
2260
2550
4490
2260
2550
kg
3992
4258
4411
4544
4753
4890
Ø mm
141.3
141.3
141.3
168.3
168.3
168.3
Ø
2 x 2"
2 x 2"
2 x 2"
2 x 2"
2 x 2"
2 x 2"
Ø
Ø mm
2 x 2"
--
2 x 2"
--
2 x 2"
--
2 x 2 1/2"
--
2 x 2 1/2"
--
2 x 2 1/2"
--
Total air flow m³/h
Absorbed power kW
Nominal operating current Compressors A
REFRIGERANT
Total refrigerant load (excluding options) kg
Number of refrigerant circuits n.
SUPPLY VOLTAGE
ENERGY EFFICIENCY RATIOS (1)
V/Ph/Hz
EER kW/kW
ESEER = Eurovent standard
SOUND LEVELS
Average sound pressure level [Lpm] (4) dB(A)
Sound power level (Lw) (5) dB(A)
HYDRAULIC KIT
1 pump
2 pumps
1 operational pump + 1 reserve pump
2 operational pumps + 1 reserve pump
GE
GE
GE
GE
DIMENSIONS
NET WEIGHT
HYDRAULIC CONNECTIONS
EVAPORATOR
Inlet outlet diameter
PARTIAL HEAT RECOVERY EXCHANGER
Inlet outlet diameter – ISO 228/1-GM
TOTAL HEAT RECOVERY EXCHANGER
Inlet outlet diameter – ISO 228/1-GM
Inlet outlet diameter
➜
(1) Gross value - chilled water temperature 12/7°C; outdoor temperature 35°C.
(2) Gross value - chilled water temperature 12/7°C and hot water temperature 40/45°C.
(3) Gross value - chilled water temperature 12/7°C; outdoor temperature 35°C and hot
water temperature 40/45°C.
(4) Sound pressure level [Lpm] at 1m far according to ISO EN 3744
(5) Sound power level [Lw] according to ISO EN 9614-2.
(6) PHE = Brazed-plate heat EXCHANGER; S&T = Shell and tube heat EXCHANGER
35
LIQUID CHILLERS | AIR-COOLED
EQSL 300 / 1310 Cooling only
TECHNICAL SPECIFICATIONS
SIZE
530
540
560
610
650
kW
kW
A
m³/h
kPa
523
174
286
89.8
38
543
180
297
93.3
41
563
186
309
96.7
45
611
204
332
105
51
645
217
354
111
56
kW
kW
kW
A
m³/h
kPa
527
699
171
281
118
81
551
726
175
290
126
63
568
750
183
305
130
69
620
818
198
323
132
71
668
870
203
333
151
69
Heating capacity kW
Heat recovery exchanger water flow m³/h
Heat recovery pressure loss kPa
104
17.9
3.8
108
18.6
3.5
112
19.2
2.6
121
20.9
3.1
128
22.1
2.8
COOLING ONLY (1)
Cooling capacity
Compressors absorbed power
Nominal operating current Compressors
Evaporator water flow
Evaporator pressure loss
COOLING ONLY + HEAT RECOVERY 100% (2)
Cooling capacity
Heating capacity
Compressors absorbed power
Nominal operating current Compressors
Heat recovery exchanger water flow
Heat recovery pressure loss
PARTIAL HEAT RECOVERY (3)
COMPRESSORS
twin-screw twin-screw twin-screw twin-screw twin-screw
Quantity n.
Maximum operating current A
Starting current A
Number of capacity steps
EVAPORATOR (multi-tube)
n.
Water volume l
Maximum water flow m³/h
TOTAL HEAT RECOVERY EXCHANGER
n.
Water volume l
Maximum water flow m³/h
PARTIAL HEAT RECOVERY EXCHANGER
n.
Water volume l
Maximum water flow m³/h
AXIAL FANS (AC)
n.
2
330.4
811.2
25…100%
2
348.6
526.2
25…100%
2
366.8
544.4
25…100%
2
390.4
544.4
25…100%
2
414
568
25…100%
1
1
1
1
1
150
95
143
100
143
100
256
127
256
127
2
2
2
2
2
42
118
46
132
46
132
46
132
58
156
2
2
2
2
2
6.8
30
6.8
30
6.8
30
8.6
35
10.4
40
8
8
8
8
8
Total air flow m³/h
Absorbed power kW
Nominal operating current Compressors A
180664
15.4
31.2
177924
15.5
31.2
175184
15.6
31.2
175184
15.6
31.2
175184
15.6
31.2
R134a
R134a
R134a
R134a
R134a
Total refrigerant load (excluding options) kg
Number of refrigerant circuits n.
145
2
170
2
194
2
194
2
194
2
400/3/50
400/3/50
400/3/50
400/3/50
400/3/50
2.76
3.17
2.78
3.23
2.79
3.21
2.78
3.17
2.77
3.24
Average sound pressure level [Lpm] (4) dB(A)
Sound power level (Lw) (5) dB(A)
76.4
96.7
76.4
96.7
76.4
96.7
78
98.2
79.2
99.4
1 pump
2 pumps
1 operational pump + 1 reserve pump
2 operational pumps + 1 reserve pump
GE80/1
-GE80/2
--
GE80/1
-GE80/2
--
GE80/1
-GE80/2
--
GE80/1
-GE80/2
--
GE80/1
-GE80/2
--
Length mm
Width mm
Height mm
4490
2260
2550
4490
2260
2550
4490
2260
2550
4490
2260
2550
4490
2260
2550
kg
5012
5117
5221
5321
5241
Ø mm
168.3
168.3
168.3
168.3
168.3
Ø
2 x 2"
2 x 2"
2 x 2"
2 x 2"
2 x 2"
Ø
Ø mm
2 x 2 1/2"
--
2 x 2 1/2"
--
2 x 2 1/2"
--
2 x 2 1/2"
--
2 x 3"
--
REFRIGERANT
SUPPLY VOLTAGE
ENERGY EFFICIENCY RATIOS (1)
V/Ph/Hz
EER kW/kW
ESEER = Eurovent standard
SOUND LEVELS
HYDRAULIC KIT
GE
GE
GE
GE
DIMENSIONS
NET WEIGHT
HYDRAULIC CONNECTIONS
EVAPORATOR
Inlet outlet diameter
PARTIAL HEAT RECOVERY EXCHANGER
Inlet outlet diameter – ISO 228/1-GM
TOTAL HEAT RECOVERY EXCHANGER
Inlet outlet diameter – ISO 228/1-GM
Inlet outlet diameter
(1) Gross value - chilled water temperature 12/7°C; outdoor temperature 35°C.
(2) Gross value - chilled water temperature 12/7°C and hot water temperature 40/45°C.
(3) Gross value - chilled water temperature 12/7°C; outdoor temperature 35°C and hot water
temperature 40/45°C.
36
710
770
850
910
950
1060
1120
1180
1310
707
237
377
121
63
768
258
400
132
73
853
289
456
147
55
905
303
479
156
63
949
320
515
163
71
1063
355
597
183
41
1121
375
634
193
45
1181
396
680
203
49
1310
443
742
225
59
718
948
230
366
156
78
783
1031
248
385
179
81
878
1151
273
432
200
86
924
1214
290
459
211
86
979
1277
298
482
222
82
1081
1425
344
579
248
105
1159
1511
353
599
263
74
1227
1595
368
638
277
81
1357
1770
414
697
308
86
141
24.2
2.7
153
26.3
3.2
170
29.2
2.6
180
31
2.5
189
32.5
3.3
212
36.4
4.1
223
38.4
4.6
235
40.5
5.1
261
44.9
6.2
twin-screw twin-screw twin-screw twin-screw twin-screw twin-screw twin-screw twin-screw twin-screw
2
444.1
581
25…100%
2
474.2
611.1
25…100%
2
535.8
720.9
25…100%
2
567.4
826.7
25…100%
2
615.4
902.7
25…100%
2
709.6
1057.8
25…100%
2
753.6
1137.8
25…100%
2
797.6
1181.8
25…100%
2
896
1324
25…100%
1
1
1
1
1
1
1
1
1
256
127
247
143
238
154
223
172
223
172
382
208
382
208
370
220
359
241
2
2
2
2
2
2
2
2
2
58
156
64
180
72
204
80
228
88
252
88
252
100
284
100
284
114
326
2
2
2
2
2
2
2
2
2
10.4
40
10.4
40
15.8
50
15.8
50
19.4
50
23
50
25.7
60
28.4
60
35.6
60
9
10
10
12
12
16
16
16
16
197082
17.6
35.1
218980
19.5
39
212690
20.1
39
262776
23.4
46.8
262776
23.4
46.8
361328
30.9
62.4
361328
30.9
62.4
361328
30.9
62.4
350368
31.2
62.4
R134a
R134a
R134a
R134a
R134a
R134a
R134a
R134a
R134a
241
2
241
2
302
2
289
2
289
2
290
2
290
2
290
2
389
2
400/3/50
400/3/50
400/3/50
400/3/50
400/3/50
400/3/50
400/3/50
400/3/50
400/3/50
2.78
3.18
2.77
3.18
2.76
3.19
2.77
3.26
2.76
3.32
2.75
3.29
2.76
3.34
2.77
3.32
2.76
3.3
79.4
100.1
80
100.7
79.7
100.4
78.8
99.8
78.8
99.8
81.1
102.9
81.1
102.9
81.1
102.9
81.4
103.2
-GE80/11
-GE80/21
-GE80/11
-GE80/21
-GE80/11
-GE80/21
-GE80/11
-GE80/21
-GE80/11
-GE80/21
-GE80/11
-GE80/21
-GE80/11
-GE80/21
-GE80/11
-GE80/21
-GE80/11
-GE80/21
5460
2260
2550
5460
2260
2550
5460
2260
2550
6430
2260
2550
6430
2260
2550
8720
2260
2550
8720
2260
2550
8720
2260
2550
8720
2260
2550
6232
6517
7032
7354
7414
9491
9975
9995
10075
168.3
219.1
219.1
219.1
219.1
219.1
219.1
219.1
273
2 x 2"
2 x 2"
2 x 2"
2 x 2"
2 x 2"
2 x 2"
2 x 2"
2 x 2"
2 x 2"
2 x 3"
--
2 x 3"
--
2 x 3"
--
2 x 3"
--
2 x 3"
--
2 x 3"
--
2 x 3"
--
2 x 3"
--
-2 x 114.3
(4) Sound pressure level [Lpm] at 1m far according to ISO EN 3744
(5) Sound power level [Lw] according to ISO EN 9614-2.
(6) PHE = Brazed-plate heat EXCHANGER; S&T = Shell and tube heat EXCHANGER
37
LIQUID CHILLERS | AIR-COOLED
EQSLA
290 / 1510
Class A
Cooling only
SCREW COMPRESSORS
CLASS A
Cooling capacities from 283 to 1510 kW
26 sizes
Refrigerant: R134a
EER up to 3.38
ESEER up to 3.95
Class A
MAIN FEATURES
Main accessories and options
Available with 2 refrigeration circuits
2 SCREW compressors mounted on
rubber anitvibration mounts
Modern and modular design
Shell and tube evaporator
Code
101
118
119
143
150
151
170
171
351
450
451
550
605
650
731
739
740
769
770
919
923
926
931
932
934
942
943
AVAILABLE VERSIONS
Partial heat recovery version
Total heat recovery version
ELN extra low sound level version
EC motor for external static pressure version
Brine low and very low temperature versions
All-year-round operation as a standard feature (-10°C)
Main characteristics
Energy efficiency Class A
Wide power range covered by SCREW technology
Screw compressors per circuit for greater efficiency and
reliability
Electronic expansion valve as standard
Linear step capacity control
Dialogue interface with screen and graphical icons for
easier reading
Large choice of sound levels
Partial or total heat recovery
Remote demand limit via additional electronic board
Analog setpoint compensation
Easy maintenance
EC fan motors
Kit A leaving chilled water low temperature operation
Kit B leaving chilled water low temperature operation
Without glycol
Kit LNO low sound level
Kit ELN extra low sound level
Antivibration mounts - spring - supplied loose
Antivibration mounts - rubber - supplied loose
Coils with pre-painted fins
Desuperheater
Total heat recovery
Stop valve on compressor suction line
Power factor capacitor for cos phi 0.9 on compressor motor
Compressor thermal relays
Water flow switch
1 pump hydraulic kit
2 pump hydraulic kit
1 pump + 1 standby pump hydraulic kit
2 pump + 1 standby pump hydraulic kit
Clock card
COM MBUS/JBUS serial card
LON serial card
BACnet Ethernet - SNMP - TCP/IP serial card
BACnet MS/TP serial card
MP.COM extension card
Serial card for GSM modem
Data logger
Besides these options, please speak to our Sales Department for any other
configuration or function that is not listed as being available.
(°C)
Indicative values. The operating T° are influenced by
a series of settings such as: operating conditions,
thermal load, adjustments, etc... Data to be confirmed
upon selection.
15
Water outlet temperature
from the evaporator
Cooling operating limits
10
5
0
Glycol solution
+ low temperature kit A
-5
Glycol solution
+ low temperature kit B
-10
-13
-20
-15
-10
-5
0
5
10
15
20
25
Outdoor air temperature
38
30
35
40
45(°C)
EQSLA 290 / 1510 Cooling only
SIZE
TECHNICAL SPECIFICATIONS
290
300
320
340
360
400
450
kW
kW
A
m³/h
kPa
283
76.8
133
48.7
12
300
83
140
51.5
17
319
87.1
148
54.8
19
340
92
157
58.4
21
358
97
157
61.4
17
399
110
192
68.5
13
446
122
212
76.6
17
kW
kW
kW
A
m³/h
kPa
264
348
83.8
142
60.4
48
289
380
91.1
151
66
58
310
404
94.2
158
70.3
39
326
428
102
170
74.4
42
345
453
107
168
78.7
55
388
507
119
204
88.1
57
433
565
132
227
98.2
42
Heating capacity kW
Heat recovery exchanger water flow m³/h
Heat recovery pressure loss kPa
56.4
9.7
5.9
59.7
10.3
6.6
63.6
10.9
7.5
67.7
11.7
6.7
71.2
12.3
3
79.4
13.7
2.9
88.8
15.3
2.8
twinscrew
twinscrew
twinscrew
twinscrew
twinscrew
twinscrew
twinscrew
2
163
350
25…100%
2
179
356
25…100%
2
190
392
25…100%
2
201
403
25…100%
2
205
382
25…100%
2
235
468
25…100%
2
269
629
25…100%
COOLING ONLY (1)
Cooling capacity
Compressors absorbed power
Nominal operating current Compressors
Evaporator water flow
Evaporator pressure loss
COOLING ONLY + HEAT RECOVERY 100% (2)
Cooling capacity
Heating capacity
Compressors absorbed power
Nominal operating current Compressors
Heat recovery exchanger water flow
Heat recovery pressure loss
PARTIAL HEAT RECOVERY (3)
COMPRESSORS
Quantity n.
Maximum operating current A
Starting current A
Number of capacity steps
EVAPORATOR (SHELL AND TUBE)
n.
Water volume l
Maximum water flow m³/h
TOTAL HEAT RECOVERY EXCHANGER
n.
Water volume l
Maximum water flow m³/h
PARTIAL HEAT RECOVERY EXCHANGER
n.
Water volume l
Maximum water flow m³/h
AXIAL FANS (AC)
n.
1
1
1
1
1
1
1
113
63
107
72
107
72
107
72
160
90
157
90
150
95
2
2
2
2
2
2
2
24
66
28
78
32
90
32
90
32
90
38
108
46
132
2
2
2
2
2
2
2
3.2
20
3.2
20
4.1
20
5
20
5
20
5
20
5
20
6
6
7
8
8
8
10
131388
11.7
23.4
127614
12.1
23.4
153286
13.7
27.3
175184
15.6
31.2
170152
16.1
31.2
170152
16.1
31.2
212690
20.1
39
74
2
74
2
96
2
96
2
96
2
145
2
120
2
400/3/50
400/3/50
400/3/50
400/3/50
400/3/50
400/3/50
400/3/50
3.2
3.55
3.16
3.52
3.17
3.53
3.16
3.53
3.17
3.51
3.16
3.52
3.14
3.51
72.3
92
72.8
92.5
72.5
92.7
72.7
92.9
71.3
91.5
71.7
91.9
71.4
92.1
GE80/1
-GE80/2
--
GE80/1
-GE80/2
--
GE80/1
-GE80/2
--
GE80/1
-GE80/2
--
GE80/1
-GE80/2
--
GE80/1
-GE80/2
--
GE80/1
-GE80/2
--
Length mm
Width mm
Height mm
3520
2260
2550
3520
2260
2550
4490
2260
2550
4490
2260
2550
4490
2260
2550
4490
2260
2550
5460
2260
2550
kg
3738
4109
4515
4520
4697
4902
5428
Ø mm
141.3
141.3
141.3
141.3
168.3
168.3
168.3
Ø
2 x 2"
2 x 2"
2 x 2"
2 x 2"
2 x 2"
2 x 2"
2 x 2"
Ø
Ø mm
2 x 2"
--
2 x 2"
--
2 x 2"
--
2 x 2"
--
2 x 2"
--
2 x 2 1/2"
--
2 x 2 1/2"
--
Total air flow m³/h
Absorbed power kW
Nominal operating current Compressors A
REFRIGERANT
Total refrigerant load (excluding options) kg
Number of refrigerant circuits n.
SUPPLY VOLTAGE
ENERGY EFFICIENCY RATIOS (1)
V/Ph/Hz
EER kW/kW
ESEER = Eurovent standard
SOUND LEVELS
Average sound pressure level [Lpm] (4) dB(A)
Sound power level (Lw) (5) dB(A)
HYDRAULIC KIT
1 pump
2 pumps
1 operational pump + 1 reserve pump
2 operational pumps + 1 reserve pump
GE
GE
GE
GE
DIMENSIONS
NET WEIGHT
HYDRAULIC CONNECTIONS
EVAPORATOR
Inlet outlet diameter
PARTIAL HEAT RECOVERY EXCHANGER
Inlet outlet diameter – ISO 228/1-GM
TOTAL HEAT RECOVERY EXCHANGER
Inlet outlet diameter – ISO 228/1-GM
Inlet outlet diameter
➜
(1) Gross value - chilled water temperature 12/7°C; outdoor temperature 35°C.
(2) G
ross value - chilled water temperature 12/7°C and hot water inlet temperature 40°C.
(3) Gross value - chilled water temperature 12/7°C; outdoor temperature 35°C and hot
water temperature 40/45°C.
39
(4) Sound pressure level [Lpm] at 1m far according to ISO EN 3744
(5) Sound power level [Lw] according to ISO EN 9614-2.
LIQUID CHILLERS | AIR-COOLED
EQSLA 290 / 1510 Cooling only
TECHNICAL SPECIFICATIONS
SIZE
480
520
570
620
660
700
760
kW
kW
A
m³/h
kPa
472
129
222
81
17
518
144
243
88.9
17
565
159
264
97
24
614
172
289
105
49
654
184
306
112
33
695
196
323
119
38
761
215
328
131
44
kW
kW
kW
A
m³/h
kPa
458
598
140
238
104
42
503
659
156
260
115
42
554
720
166
274
125
50
604
782
178
298
136
56
647
836
189
313
145
61
684
887
203
334
154
60
749
971
222
339
169
63
Heating capacity kW
Heat recovery exchanger water flow m³/h
Heat recovery pressure loss kPa
93.9
16.2
2.6
103
17.8
2.2
112
19.4
2.6
122
21
2.5
130
22.4
2.3
138
23.8
2.6
151
26.1
2.1
twinscrew
twinscrew
twinscrew
twinscrew
twinscrew
twinscrew
twinscrew
2
288
639
25…100%
2
309
790
25…100%
2
330
811
25…100%
2
366
544
25…100%
2
390
568
25…100%
2
414
568
25…100%
2
444
598
25…100%
COOLING ONLY (1)
Cooling capacity
Compressors absorbed power
Nominal operating current Compressors
Evaporator water flow
Evaporator pressure loss
COOLING ONLY + HEAT RECOVERY 100% (2)
Cooling capacity
Heating capacity
Compressors absorbed power
Nominal operating current Compressors
Heat recovery exchanger water flow
Heat recovery pressure loss
PARTIAL HEAT RECOVERY (3)
COMPRESSORS
Quantity n.
Maximum operating current A
Starting current A
Number of capacity steps
EVAPORATOR (SHELL AND TUBE)
n.
Water volume l
Maximum water flow m³/h
TOTAL HEAT RECOVERY EXCHANGER
n.
Water volume l
Maximum water flow m³/h
PARTIAL HEAT RECOVERY EXCHANGER
n.
Water volume l
Maximum water flow m³/h
AXIAL FANS (AC)
n.
1
1
1
1
1
1
1
143
100
256
127
256
127
256
127
247
143
247
143
223
172
2
2
2
2
2
2
2
46
132
46
132
58
156
58
156
64
180
64
180
72
204
2
2
2
2
2
2
2
6.8
30
6.8
30
6.8
30
6.8
30
8.6
35
10.4
40
10.4
40
10
10
10
10
11
12
13
212690
20.1
39
212690
20.1
39
212690
20.1
39
212690
20.1
39
244303
21.3
42.9
262776
23.4
46.8
284674
25.4
50.7
181
2
181
2
181
2
181
2
217
2
217
2
252
2
400/3/50
400/3/50
400/3/50
400/3/50
400/3/50
400/3/50
400/3/50
3.17
3.51
3.16
3.55
3.15
3.52
3.2
3.62
3.18
3.55
3.17
3.56
3.17
3.52
75.5
96.2
75.8
96.4
76
96.7
76
96.7
78.2
99.3
79.4
100.4
79.7
101.1
GE80/1
-GE80/2
--
GE80/1
-GE80/2
--
GE80/1
-GE80/2
--
GE80/1
-GE80/2
--
GE80/1
-GE80/2
--
GE80/1
-GE80/2
--
-GE80/11
-GE80/21
Length mm
Width mm
Height mm
5460
2260
2550
5460
2260
2550
5460
2260
2550
5460
2260
2550
6430
2260
2550
6430
2260
2550
7400
2260
2550
kg
5662
5999
6121
6112
6733
6743
7404
Ø mm
168.3
168.3
168.3
168.3
219.1
219.1
219.1
Ø
2 x 2"
2 x 2"
2 x 2"
2 x 2"
2 x 2"
2 x 2"
2 x 2"
Ø
Ø mm
2 x 2 1/2"
--
2 x 2 1/2"
--
2 x 3"
--
2 x 3"
--
2 x 3"
--
2 x 3"
--
2 x 3"
--
Total air flow m³/h
Absorbed power kW
Nominal operating current Compressors A
REFRIGERANT
Total refrigerant load (excluding options) kg
Number of refrigerant circuits n.
SUPPLY VOLTAGE
ENERGY EFFICIENCY RATIOS (1)
V/Ph/Hz
EER kW/kW
ESEER = Eurovent standard
SOUND LEVELS
Average sound pressure level [Lpm] (4) dB(A)
Sound power level (Lw) (5) dB(A)
HYDRAULIC KIT
1 pump
2 pumps
1 operational pump + 1 reserve pump
2 operational pumps + 1 reserve pump
GE
GE
GE
GE
DIMENSIONS
NET WEIGHT
HYDRAULIC CONNECTIONS
EVAPORATOR
Inlet outlet diameter
PARTIAL HEAT RECOVERY EXCHANGER
Inlet outlet diameter – ISO 228/1-GM
TOTAL HEAT RECOVERY EXCHANGER
Inlet outlet diameter – ISO 228/1-GM
Inlet outlet diameter
(1) Gross value - chilled water temperature 12/7°C; outdoor temperature 35°C.
(2) Gross value - chilled water temperature 12/7°C and hot water temperature 40/45°C.
(3) Gross value - chilled water temperature 12/7°C; outdoor temperature 35°C and hot water
temperature 40/45°C.
40
830
870
920
980
1020
1090
1150
1280
1350
1430
1470
1510
826
233
333
142
51
871
248
375
150
56
916
262
418
157
61
974
274
435
167
68
1020
287
464
175
76
1084
305
504
186
71
1148
322
544
197
79
1276
359
611
219
54
1352
385
652
232
41
1430
411
693
246
44
1474
406
685
253
35
1510
398
672
259
35
811
1053
242
346
183
72
860
1115
255
385
194
71
910
1176
266
423
204
69
962
1244
281
446
216
76
1018
1306
288
466
227
53
1078
1386
308
508
241
60
1138
1466
327
552
255
66
1265
1630
365
620
283
72
1348
1735
388
656
302
77
1435
1843
408
688
320
55
1458
1869
411
692
325
57
1483
1896
413
696
329
57
164
28.3
2
173
29.8
2.8
182
31.4
3
194
33.4
3.4
203
35
3.8
216
37.1
4.3
228
39.3
4.6
254
43.7
5.7
269
46.4
6.3
285
49
7
293
50.5
7.5
301
51.8
7.7
twinscrew
twinscrew
twinscrew
twinscrew
twinscrew
twinscrew
twinscrew
twinscrew
twinscrew
twinscrew
twinscrew
twinscrew
2
474
611
25…100%
2
505
690
25…100%
2
535
720
25…100%
2
567
826
25…100%
2
615
902
25…100%
2
662
1010
25…100%
2
709
1057
25…100%
2
797
1181
25…100%
2
846
1274
25…100%
2
896
1324
25…100%
2
896
1324
25…100%
2
896
1324
25…100%
1
1
1
1
1
1
1
1
1
1
1
1
382
208
382
208
382
208
382
208
348
265
348
265
348
265
348
265
620
407
620
407
620
407
620
407
2
2
2
2
2
2
2
2
2
2
2
2
72
204
80
228
88
252
88
252
100
284
100
284
100
284
114
326
126
362
132
386
132
386
132
386
2
2
2
2
2
2
2
2
2
2
2
2
10.4
40
13.1
45
15.8
50
15.8
50
19.4
50
21.2
50
23
50
28.4
60
32
60
35.6
60
35.6
60
35.6
60
14
14
14
16
16
18
20
20
20
20
22
24
306572
27.3
54.6
302169
27.7
54.6
297766
28.1
54.6
350368
31.2
62.4
350368
31.2
62.4
401014
34.9
70.2
451660
38.6
78
437960
39
78
431670
39.6
78
425380
40.2
78
467918
44.2
85.8
510456
48.2
93.6
252
2
295
2
337
2
290
2
290
2
326
2
362
2
362
2
412
2
462
2
530
2
578
2
400/3/50
400/3/50
400/3/50
400/3/50
400/3/50
400/3/50
400/3/50
400/3/50
400/3/50
400/3/50
400/3/50
400/3/50
3.17
3.5
3.16
3.49
3.16
3.51
3.19
3.55
3.21
3.68
3.19
3.69
3.18
3.68
3.21
3.69
3.18
3.68
3.17
3.72
3.27
3.83
3.38
3.95
80.3
101.7
80.1
101.6
80
101.4
78.1
99.9
78.1
99.9
79.5
101.7
81.5
103.9
81.5
103.9
81.7
104.1
81.8
104.2
81.6
104.2
81.3
104.2
-GE80/11
-GE80/21
-GE80/11
-GE80/21
-GE80/11
-GE80/21
-GE80/11
-GE80/21
-GE80/11
-GE80/21
-GE80/11
-GE80/21
-GE80/11
-GE80/21
-GE80/11
-GE80/21
-GE80/11
-GE80/21
-GE100/11
-GE100/21
-GE100/11
-GE100/21
-GE100/11
-GE100/21
7400
2260
2550
7400
2260
2550
7400
2260
2550
8720
2260
2550
8720
2260
2550
9690
2260
2550
10660
2260
2550
10660
2260
2550
10660
2260
2550
10660
2260
2550
11630
2260
2550
12600
2260
2550
8139
8341.5
8544
9195
9318
10274
11180
11362
11972
12292
12931
13090
219.1
219.1
219.1
219.1
273
273
273
273
323.9
323.9
323.9
323.9
2 x 2"
2 x 2"
2 x 2"
2 x 2"
2 x 2"
2 x 2"
2 x 2"
2 x 2"
2 x 2"
2 x 2"
2 x 2"
2 x 2"
2 x 3"
--
2 x 3"
--
2 x 3"
--
2 x 3"
--
2 x 3"
--
2 x 3"
--
2 x 3"
--
-2 x 114.3
-2 x 114.3
-2 x 114.3
-2 x 114.3
-2 x 114.3
(4) Sound pressure level [Lpm] at 1m far according to ISO EN 3744
(5) Sound power level [Lw] according to ISO EN 9614-2.
(6) PHE = Brazed-plate heat EXCHANGER; S&T = Shell and tube heat EXCHANGER
41
LIQUID CHILLERS | AIR-COOLED
EQSH
200 / 1090
Reversible
SCREW COMPRESSORS
Cooling capacities from 201 to 1098 kW
Heating capacities from 233 to 1307 kW
15 sizes
Refrigerant: R134a
EER up to 3.02
ESEER up to 3.46
COP up to 3.75
MAIN FEATURES
Available with 2 refrigeration circuits
2 SCREW compressors mounted on a rubber
antivibration mounts
Hot water leaving temperature up to 60°C
Shell and tube evaporator
AVAILABLE VERSIONS
Partial heat recovery version
ELN extra low sound level version
Main charasteristics
Wide power range covered by SCREW technology
Screw compressors per circuit for greater efficiency and
reliability
Electronic expansion valve as standard
Linear step capacity control
Dialogue interface with screen and graphical icons for
easier reading
Large choice of sound levels
Partial or total heat recovery
Remote demand limit via additional electronic board
Analog setpoint compensation
Easy maintenance
Main accessories and options
Code
150
151
170
172
175
351
450
452
550
605
650
731
739
740
756
757
919
923
926
931
932
934
942
943
Kit LNO low sound level
Kit ELN extra low sound level
Antivibration mounts - spring - supplied loose
Antivibration mounts - rubber -supplied loose
Victaulic connections
Coils with pre-painted fins
Desuperheater
Sanitary hot water production (up to 20% of nominal capacity)
Stop valve on compressor suction line
Power factor capacitor for cos phi 0.9 on compressor motor
Compressor thermal relays
Water flow switch
1 pump hydraulic kit
2 pump hydraulic kit
1 LN pump hydraulic kit
2 LN pump hydraulic kit
Clock card
COM MBUS/JBUS serial card
LON serial card
BACnet Ethernet - SNMP - TCP/IP serial card
BACnet MS/TP serial card
MP.COM extension card
Serial card for GSM modem
Data logger
Besides these options, please speak to our Sales Department for any other
configuration or function that is not listed as being available.
(°C)
Heating operating limits
65
Hot water outlet temperature
60
Indicative values. The operating T° are influenced by
a series of settings such as: operating conditions,
thermal load, adjustments, etc... Data to be
confirmed upon selection.
55
50
45
40
35
30
25
20
-10
-5
0
5
10
Outdoor air temperature
42
15
20 (°C)
EQSH 200 / 1090 Reversible
TECHNICAL SPECIFICATIONS
SIZE
200
250
280
340
370
Cooling capacity kW
201
244
281
340
373
Compressors absorbed power kW
59.5
70.3
83.1
99
109
97.3
113
142
142
191
34.5
41.9
48.2
58.4
63.9
10
8
11
9
18
Heating capacity kW
233
277
321
379
417
Compressors absorbed power kW
65.4
78
92.3
96.4
109
106
124
154
110
167
40
48.5
55.9
67.7
74.1
6.9
8.4
9.6
11.7
12.8
twin-screw
twin-screw
twin-screw
twin-screw
twin-screw
2
2
2
2
2
Maximum operating current A
145
165
203
205
236
Starting current A
350
386
474
383
469
4
4
4
25…100%
25…100%
1
1
1
1
1
20
20
32
225
225
55
70
70
165
165
2
2
2
2
2
18
18
18
18
28
12
12
12
18
18
4
6
6
8
8
89644
144498
139686
193536
187992
7.7
10.9
11.2
14.6
15
15.6
23.4
23.4
31.2
31.2
R134a
R134a
R134a
R134a
R134a
116
103
138
143
191
2
2
2
2
2
400/3/50
400/3/50
400/3/50
400/3/50
400/3/50
EER kW/kW
2.99
3
2.98
2.99
3.01
COP kW/kW
3.19
3.12
3.1
3.41
3.36
3.46
3.42
3.29
3.37
3.38
Average sound pressure level [Lpm] (4) dB(A)
72.3
72.2
72.3
71.7
72.1
Sound power level (Lw) (5) dB(A)
91.6
92.2
92.3
92.5
92.9
SUMMER MODE (1)
Nominal operating current Compressors A
Evaporator water flow m³/h
Evaporator pressure loss kPa
WINTER MODE (2)
Nominal operating current Compressors A
PARTIAL HEAT RECOVERY (3)
Heating capacity kW
Heat recovery exchanger water flow m³/h
COMPRESSORS
Quantity n.
Number of capacity steps
EVAPORATOR (brazed-plate)
n.
Water volume l
Maximum water flow m³/h
PARTIAL HEAT RECOVERY EXCHANGER
n.
Water volume l
Maximum water flow m³/h
AXIAL FANS (AC)
n.
Total air flow m³/h
Absorbed power kW
Nominal operating current Fans A
REFRIGERANT
Total refrigerant load (excluding options) kg
Number of refrigerant circuits n.
SUPPLY VOLTAGE
V/Ph/Hz
ENERGY EFFICIENCY RATIOS (1)
ESEER = Eurovent standard
SOUND LEVELS
HYDRAULIC KIT
1 pump 2 poles GP
R10/1
R20/1
R20/1
R30/1
R30/1
2 pumps 2 poles GP
R10/2
R20/2
R20/2
R30/2
R30/2
1 pump 4 poles GP
R10/1 LN
R20/1 LN
R20/1 LN
R30/1 LN
R30/1 LN
2 pumps 4 poles GP
R10/2 LN
R20/2 LN
R20/2 LN
R30/2 LN
R30/2 LN
Length mm
3815
5215
5215
6045
6045
Width mm
2206
2206
2206
2206
2206
Height mm
2015
2015
2015
2525
2525
kg
3181
3773
3783
5714
5730
88.9
88.9
88.9
219.1
219.1
2 x 2"
2 x 2"
2 x 2"
2 x 2"
2 x 2"
DIMENSIONS
NET WEIGHT
HYDRAULIC CONNECTIONS
EVAPORATOR
Inlet outlet diameter – ISO 7/1 – R Ø mm
HEATING PARTIAL HEAT RECOVERY EXCHANGER
Inlet outlet diameter – ISO 7/1 – R Ø
(1) Gross value - chilled water temperature 12/7°C; outdoor temperature 35°C.
(2) Gross value - hot water outlet temperature 45°C and outdoor temperature 7°C.
(3) Gross value - chilled water temperature 12/7°C; outdoor temperature 35°C and hot
water temperature 40/45°C.
(4) Sound pressure level [Lpm] at 1m far according to ISO EN 3744
(5) Sound power level [Lw] according to ISO EN 9614-2.
43
➜
LIQUID CHILLERS | AIR-COOLED
EQSH 200 / 1090 Reversible
TECHNICAL SPECIFICATIONS
SIZE
410
440
520
570
Cooling capacity kW
412
448
520
575
Compressors absorbed power kW
123
130
153
169
211
224
253
284
70.7
76.9
89.3
98.9
30
14
32
27
Heating capacity kW
468
496
599
657
Compressors absorbed power kW
124
125
157
166
186
186
259
280
81.9
89.1
104
114
14.1
15.4
17.8
19.7
twin-screw
twin-screw
twin-screw
twin-screw
2
2
2
2
SUMMER MODE (1)
Nominal operating current Compressors A
Evaporator water flow m³/h
Evaporator pressure loss kPa
WINTER MODE (2)
Nominal operating current Compressors A
PARTIAL HEAT RECOVERY (3)
Heating capacity kW
Heat recovery exchanger water flow m³/h
COMPRESSORS
Quantity n.
Maximum operating current A
270
288
330
367
Starting current A
630
639
811
544
25…100%
Number of capacity steps
EVAPORATOR (brazed-plate)
n.
Water volume l
Maximum water flow m³/h
PARTIAL HEAT RECOVERY EXCHANGER
n.
Water volume l
Maximum water flow m³/h
AXIAL FANS (AC)
n.
Total air flow m³/h
Absorbed power kW
Nominal operating current Fans A
REFRIGERANT
Total refrigerant load (excluding options) kg
Number of refrigerant circuits n.
25…100%
25…100%
25…100%
1
1
1
1
207
310
185
225
165
120
190
148
2
2
2
2
28
36
36
48
38
18
26
26
8
10
10
10
181216
241920
234990
234990
15.6
18.3
18.8
18.8
31.2
39
39
39
R134a
R134a
R134a
R134a
239
179
238
238
2
2
2
2
400/3/50
400/3/50
400/3/50
400/3/50
EER kW/kW
2.97
3.02
3.03
3.06
COP kW/kW
3.35
3.46
3.41
3.56
3.31
3.37
3.34
3.45
SUPPLY VOLTAGE
V/Ph/Hz
ENERGY EFFICIENCY RATIOS (1)
ESEER = Eurovent standard
SOUND LEVELS
Average sound pressure level [Lpm] (4) dB(A)
76.4
76
76.5
76.5
Sound power level (Lw) (5) dB(A)
97.2
97.2
97.7
97.7
1 pump 2 poles GP
R40/1
R50/1
R50/1
R50/1
2 pumps 2 poles GP
R40/2
R50/2
R50/2
R50/2
1 pump 4 poles GP
R40/1 LN
R50/1 LN
R50/1 LN
R50/1 LN
2 pumps 4 poles GP
R40/2 LN
R50/2 LN
R50/2 LN
R50/2 LN
Length mm
6045
7175
7175
7175
Width mm
2206
2206
2206
2206
Height mm
2525
2525
2525
2525
kg
5782
6475
6642
6739
219.1
219.1
219.1
219.1
2 x 2"
2 x 2"
2 x 2"
2 x 2"
HYDRAULIC KIT
DIMENSIONS
NET WEIGHT
HYDRAULIC CONNECTIONS
EVAPORATOR
Inlet outlet diameter – ISO 7/1 – R Ø mm
PARTIAL HEAT RECOVERY EXCHANGER
Inlet outlet diameter – ISO 7/1 – R Ø
(1) Gross value - chilled water temperature 12/7°C; outdoor temperature 35°C.
(2) Gross value - hot water outlet temperature 45°C and outdoor temperature 7°C.
(3) Gross value - chilled water temperature 12/7°C; outdoor temperature 35°C and hot water
temperature 40/45°C.
44
670
790
880
930
980
1090
668
796
884
937
980
1098
201
242
272
284
298
336
327
372
427
447
479
563
115
137
152
161
168
189
47
41
39
41
44
52
782
945
1030
1092
1160
1307
208
245
261
273
286
321
336
375
412
431
461
540
133
158
176
186
195
219
22.9
27.3
30.3
32.1
33.6
37.6
twin-screw
twin-screw
twin-screw
twin-screw
twin-screw
twin-screw
2
2
2
2
2
2
414
474
536
567
615
710
568
611
721
827
903
1058
25…100%
25…100%
25…100%
25…100%
25…100%
25…100%
1
1
1
1
1
1
185
225
303
378
378
348
148
165
205
218
218
236
2
2
2
2
2
2
48
58
58
68
76
86
38
52
52
76
96
118
12
12
12
14
14
14
290304
281988
271824
328986
328986
317128
22
22.6
23.4
26.3
26.3
27.3
46.8
46.8
46.8
54.6
54.6
54.6
R134a
R134a
R134a
R134a
R134a
R134a
214
284
355
331
331
414
2
2
2
2
2
2
400/3/50
400/3/50
400/3/50
400/3/50
400/3/50
400/3/50
3
3.01
2.99
3.02
3.02
3.02
3.4
3.53
3.62
3.65
3.71
3.75
3.38
3.38
3.37
3.41
3.49
3.49
78.8
80.1
79.8
77.7
77.7
80.9
100.4
101.7
101.4
99.9
99.9
102.9
R60/1
R60/1
R70/1
R80/1
R80/1
R80/1
R60/2
R60/2
R70/2
R80/2
R80/2
R80/2
R60/1 LN
R60/1 LN
R60/1 LN
R70/1 LN
R70/1 LN
R70/1 LN
R60/2 LN
R60/2 LN
R60/2 LN
R70/2 LN
R70/2 LN
R70/2 LN
8305
8305
8305
9435
9435
9435
2206
2206
2206
2206
2206
2206
2525
2525
2525
2525
2525
2525
7118
7695
8170
8507
8567
9563
219.1
219.1
219.1
219.1
219.1
219.1
2 x 2"
2 x 2"
2 x 2"
2 x 2"
2 x 2"
2 x 2"
(4) Sound pressure level [Lpm] at 1m far according to ISO EN 3744
(5) Sound power level [Lw] according to ISO EN 9614-2.
45
LIQUID CHILLERS | AIR-COOLED
EQUL
21 / 260
Cooling only
SCROLL COMPRESSORS
Cooling capacities from 20 to 260 kW
29 sizes
Refrigerant: R410A
EER up to 3.26
ESEER up to 4.67
ESPECIALLY FOR
SETUP IN DIFFICULT
LOCATIONS
MAIN FEATURES
Available with single or double refrigeration circuit(s)
1 or 2 SCROLL compressors mounted on
antivibration mounts
Condenser on one face only
Possible installation in difficult locations
AVAILABLE VERSIONS
Partial heat recovery version
Full heat recovery version
ELN extra low sound level version
Brine low and very low temperature versions
All-year-round operation as a standard feature
(-12°C)
For external static pressure see PF version
Main Characteristics
Possible installation in a corner, or against walls
Mono or twin circuit units
High ESEER
Water tank under the unit for improved mass gravity and
reduced footprint (optional)
Easy access to components
Large choice of sound levels
Partial or total heat recovery
EC fan motor as standard
Remote demand limit via additional electronic board
Analog setpoint compensation
Easy maintenance
Service valves on liquid and discharge lines
Main accessories and options
Code
118
150
151
170
172
175
251
351
450
451
605
731
739
740
756
757
768
919
923
926
931
932
934
942
943
Kit A leaving chilled water low temperature operation
Kit LNO low sound level
Kit ELN extra low sound level
Antivibration mounts - spring - supplied loose
Antivibration mounts - rubber -supplied loose
Victaulic connections
Coil protection kit
Coils with pre-painted fins
Desuperheater
Total heat recovery
Power factor capacitor for cos phi 0.9 on compressor motor
Water flow switch
1 pump hydraulic kit
2 pump hydraulic kit
1 LN pump hydraulic kit
2 LN pump hydraulic kit
Water tank
Clock card
COM MBUS/JBUS serial card
LON serial card
BACnet Ethernet - SNMP - TCP/IP serial card
BACnet MS/TP serial card
MP.COM extension card
Serial card for GSM modem
Data logger
Besides these options, please speak to our Sales Department for any other
configuration or function that is not listed as being available.
(°C)
Cooling operating limits
20
15
Evaporator water
outlet temperature
Indicative values. The operating T° are influenced by
a series of settings such as: operating conditions,
thermal load, adjustments, etc... Data to be confirmed
upon selection.
10
5
0
Glycol solution
+ low temperature kit A
-5
-10
-13
-10
-5
0
5
10
15
20
25
30
Outdoor air temperature
46
35
40
45
(°C)
EQUL 21 / 260 Cooling only
TECHNICAL SPECIFICATIONS
SIZE
21.1
24.1
28.1
30.1
34.1
40.1
50.1
kW
kW
A
m³/h
kPa
19.8
6.1
11.1
3.4
28
22.4
7.1
13.3
3.9
36
26.5
8.2
15.3
4.6
38
29.2
9.7
17.2
5
29
34
10.2
18.6
5.8
38
39
12.4
23.9
6.7
39
49.6
15.9
28
8.5
35
kW
kW
kW
A
m³/h
kPa
21.1
27.1
6
11
4.7
44
24.6
31.4
6.9
12.9
5.5
57
28.9
36.8
7.9
14.9
6.4
55
30.9
39.9
9
16.2
6.9
45
39.5
51.6
12.2
18.6
9
75
40
52
12
23.3
9
56
50.5
66.3
15.8
27.7
11.5
47
Heating capacity kW
Heat recovery exchanger water flow m³/h
Heat recovery pressure loss kPa
7.3
1.3
18.7
8.2
1.4
23.9
9.7
1.7
33.3
10.7
1.9
13.7
12.5
2.2
18.5
14.3
2.5
24.3
18.2
3.1
39.3
COOLING ONLY (1)
Cooling capacity
Compressors absorbed power
Nominal operating current Compressors
Evaporator water flow
Evaporator pressure loss
COOLING ONLY + HEAT RECOVERY 100% (2)
Cooling capacity
Heating capacity
Compressors absorbed power
Nominal operating current Compressors
Heat recovery exchanger water flow
Heat recovery pressure loss
PARTIAL HEAT RECOVERY (3)
COMPRESSORS
Quantity
Maximum operating current
Starting current
Number of capacity steps
EVAPORATOR (brazed-plate)
scroll
scroll
scroll
scroll
scroll
scroll
scroll
n.
A
A
n.
1
16
95
1
1
21
111
1
1
22
118
1
1
25
118
1
1
31
140
1
1
34
174
1
1
40
225
1
n.
1
1
1
1
1
1
1
1.9
5.1
1.9
5.8
2.1
6.8
2.8
7.1
2.9
8.2
3.3
9.5
4.2
12.1
1
1
1
1
1
1
1
1.9
6
1.9
7.7
1.9
9
2.5
9.7
2.5
10.9
2.5
12.7
3.1
16.1
1
1
1
1
1
1
1
0.4
1.4
0.4
1.4
0.4
1.4
0.6
1.4
0.6
1.4
0.6
1.4
0.6
1.4
Water volume l
Maximum water flow m³/h
TOTAL HEAT RECOVERY EXCHANGER
n.
Water volume l
Maximum water flow m³/h
PARTIAL HEAT RECOVERY EXCHANGER
n.
Water volume l
Maximum water flow m³/h
AXIAL FANS (AC)
1
1
1
1
2
2
2
Total air flow m³/h
Absorbed power kW
Nominal operating current Compressors A
n.
8,500
0.5
1.6
8,500
0.5
1.6
11000
0.8
1.6
11000
0.8
1.6
13000
0.5
3.2
15000
0.8
3.2
20500
1.6
3.3
R410A
R410A
R410A
R410A
R410A
R410A
R410A
Total refrigerant load (excluding options) kg
Number of refrigerant circuits n.
5.3
1
5.3
1
5.3
1
5.5
1
7.7
1
7.7
1
9
1
REFRIGERANT
SUPPLY VOLTAGE 400V/3PH/50HZ
ENERGY EFFICIENCY RATIOS (1)
V/Ph/Hz
EER kW/kW
ESEER = Eurovent standard
IPLV - ARI Standard 550/590
400/3/50 400/3/50 400/3/50 400/3/50 400/3/50 400/3/50 400/3/50
3.03
4.67
5.18
2.95
4.74
5.25
2.96
4.57
5.07
2.8
4.21
4.67
3.18
4.85
5.38
2.96
4.46
4.94
2.83
4.02
4.46
64.6
81.1
64.9
81.5
65.6
82.2
64.8
81.4
64.9
82.2
67.7
84.9
71.8
89
1/1
-1/1 LN
-130
1/1
-1/1 LN
-130
1/1
-1/1 LN
-130
1/1
-1/1 LN
-130
2/1
-2/1 LN
-210
2/1
-2/1 LN
-210
2/1
-2/1 LN
-210
1250
890
2010
1250
890
2010
1250
890
2010
1250
890
2010
1800
1040
2060
1800
1040
2060
1800
1040
2060
kg
350
350
360
360
520
520
610
Ø
Ø mm
1 1/2"
--
1 1/2"
--
1 1/2"
--
1 1/2"
--
2"
--
2"
--
2"
--
Ø
1"
1"
1"
1"
1 1/4"
1 1/4"
1 1/4"
Ø
Ø mm
1 1/2"
--
1 1/2"
--
1 1/2"
--
1 1/2"
--
2"
--
2"
--
2"
--
SOUND LEVELS
Average sound pressure level [Lpm] (4) dB(A)
Sound power level (Lw) (5) dB(A)
HYDRAULIC KIT
1 pump 2 poles
2 pumps 2 poles
1 pump 4 poles
2 pumps 4 poles
Water tank volume
PPF UNI
PPF UNI
PPF UNI
PPF UNI
l
DIMENSIONS
Length mm
Width mm
Height mm
NET WEIGHT
HYDRAULIC CONNECTIONS
EVAPORATOR
Inlet outlet diameter – ISO 7/1 – R
Inlet outlet diameter
PARTIAL HEAT RECOVERY EXCHANGER
Inlet outlet diameter – ISO 7/1 – R
TOTAL HEAT RECOVERY EXCHANGER
Inlet outlet diameter – ISO 7/1 – R
Inlet outlet diameter
(1) Gross value - chilled water temperature 12/7°C; outdoor temperature 35°C.
(2) Gross value - chilled water temperature 12/7°C and hot water temperature 40/45°C.
(3) Gross value - chilled water temperature 12/7°C; outdoor temperature 35°C and hot
water temperature 40/45°C.
(4) Sound pressure level [Lpm] at 1m far according to ISO EN 3744
(5) Sound power level [Lw] according to ISO EN 9614-2.
47
➜
LIQUID CHILLERS | AIR-COOLED
EQUL 21 / 260 Cooling only
TECHNICAL SPECIFICATIONS
SIZE
52.1
52.2
58.1
58.2
62.1
65.1
65.2
76.1
kW
kW
A
m³/h
kPa
50.5
16.7
31.1
8.7
36
50.5
16.4
30.5
8.7
21
57.7
18.6
33.5
9.9
36
60.8
17.5
31.4
10.5
19
61.2
20
34.6
10.5
30
64.8
20.9
38.3
11.1
35
64.7
21
38.2
11.1
21
75.4
24.9
48
13
37
kW
kW
kW
A
m³/h
kPa
51.6
68.1
16.4
30.6
11.8
50
52.5
68.5
16.1
30.1
11.9
33
58.4
77
18.6
33.3
13.4
48
59.8
77.9
18.1
32.6
13.5
29
62.6
82.4
19.8
34.4
14.3
40
75.7
101
24.8
37.7
17.5
70
76.7
101
24.4
37.3
17.6
43
77.5
102
24.4
47.1
17.7
54
Heating capacity kW
Heat recovery exchanger water flow m³/h
Heat recovery pressure loss kPa
18.5
3.2
26.6
18.5
3.2
30.3
21.2
3.7
34.6
22.3
3.8
14.8
22.4
3.9
38.9
23.8
4.1
43.7
23.7
4.1
16.7
27.7
4.8
34.6
COOLING ONLY (1)
Cooling capacity
Compressors absorbed power
Nominal operating current Compressors
Evaporator water flow
Evaporator pressure loss
COOLING ONLY + HEAT RECOVERY 100% (2)
Cooling capacity
Heating capacity
Compressors absorbed power
Nominal operating current Compressors
Heat recovery exchanger water flow
Heat recovery pressure loss
PARTIAL HEAT RECOVERY (3)
COMPRESSORS
scroll scroll scroll scroll scroll scroll scroll scroll
Quantity
Maximum operating current
Starting current
Number of capacity steps
EVAPORATOR (brazed-plate)
n.
A
A
n.
n.
Water volume l
Maximum water flow m³/h
TOTAL HEAT RECOVERY EXCHANGER
n.
Water volume l
Maximum water flow m³/h
PARTIAL HEAT RECOVERY EXCHANGER
n.
Water volume l
Maximum water flow m³/h
AXIAL FANS (AC)
n.
Total air flow m³/h
Absorbed power kW
Nominal operating current Compressors A
REFRIGERANT
Total refrigerant load (excluding options) kg
Number of refrigerant circuits n.
SUPPLY VOLTAGE
ENERGY EFFICIENCY RATIOS (1)
V/Ph/Hz
EER kW/kW
ESEER = Eurovent standard
IPLV - ARI Standard 550/590
2
44
140
2
2
44
140
2
2
50
143
2
2
50
143
2
1
48.5
272
1
2
62
171
2
2
62
171
2
2
68
208
2
1
1
1
1
1
1
1
1
4.2
12.3
4.3
12.3
4.8
14
5.3
14.1
5.7
14.9
5.5
15.8
5.6
15.8
6.3
18.4
1
1
1
1
1
1
1
1
3.9
16.7
3.6
18.8
3.9
19
3.6
20.1
3.9
16.6
4.7
21.3
4.2
21.4
5.8
24.8
1
2
1
2
1
1
2
1
0.8
1.4
2 x 0.4
2.8
0.8
2.8
2 x 0.6
2.8
0.8
2.8
0.8
2.8
2 x 0.6
2.8
1
2.8
2
2
3
3
3
3
3
3
20500
1.6
3.3
20500
1.6
3.3
22000
1.1
4.7
22000
1.1
4.7
23000
1.3
4.7
24000
1.5
4.7
24000
1.5
4.7
30000
2.4
4.9
R410A
R410A
R410A
R410A
R410A
R410A
R410A
R410A
12.9
1
9.3
2
9
1
12.7
2
12.4
1
13.1
1
12.7
2
13.6
1
400/3/50 400/3/50 400/3/50 400/3/50 400/3/50 400/3/50 400/3/50 400/3/50
2.76
4.21
4.67
2.8
3.82
4.24
2.92
4.76
5.28
3.26
4.21
4.67
2.87
4.28
4.74
2.9
4.51
5.01
2.88
4.01
4.45
2.76
4.13
4.58
68.9
86.1
68.9
86.1
68
85.9
68
85.9
73.8
91.6
67.8
85.7
67.8
85.7
68.2
86.1
2/1
-2/1 LN
-210
2/1
-2/1 LN
-210
3/1
3/2
3/1 LN
3/2 LN
360
3/1
3/2
3/1 LN
3/2 LN
360
3/1
3/2
3/1 LN
3/2 LN
360
3/1
3/2
3/1 LN
3/2 LN
360
3/1
3/2
3/1 LN
3/2 LN
360
3/1
3/2
3/1 LN
3/2 LN
360
1800
1040
2060
1800
1040
2060
2600
1200
2060
2600
1200
2060
2600
1200
2060
2600
1200
2060
2600
1200
2060
2600
1200
2060
kg
590
590
810
810
850
820
820
840
Ø
Ø mm
2"
--
2"
--
-73
-73
-73
-73
-73
-73
Ø
1 1/4"
1 1/4"
1 1/2"
1 1/2"
1 1/2"
1 1/2"
1 1/2"
1 1/2"
Ø
Ø mm
2"
--
2"
--
-73
-73
-73
-73
-73
-73
SOUND LEVELS
Average sound pressure level [Lpm] (4) dB(A)
Sound power level (Lw) (5) dB(A)
HYDRAULIC KIT
1 pump 2 poles
2 pumps 2 poles
1 pump 4 poles
2 pumps 4 poles
Water tank volume
PPF UNI
PPF UNI
PPF UNI
PPF UNI
l
DIMENSIONS
Length mm
Width mm
Height mm
NET WEIGHT
HYDRAULIC CONNECTIONS
EVAPORATOR
Inlet outlet diameter – ISO 7/1 – R
Inlet outlet diameter
HEATING PARTIAL HEAT RECOVERY EXCHANGER
Inlet outlet diameter – ISO 7/1 – R
FULL HEAT RECOVERY EXCHANGER
Inlet outlet diameter – ISO 7/1 – R
Inlet outlet diameter
(1) Gross value - chilled water temperature 12/7°C; outdoor temperature 35°C.
(2) Gross value - chilled water temperature 12/7°C and hot water temperature
40/45°C.
(3) Gross value - chilled water temperature 12/7°C; outdoor temperature 35°C
and hot water temperature 40/45°C.
48
76.2
98.1
98.2
124.1
124.2
158.1
158.2
180.1
180.2
197.1
197.2
230.1
240.2
260.2
75
24.9
47.9
12.9
23
97.3
31.5
55.5
16.7
36
96.1
31.4
55.3
16.5
27
123
40
69.5
21.1
38
120
39.8
69.3
20.5
31
155
53
90.8
26.6
32
157
53.2
90.9
27
28
177
59.2
102
30.3
34
178
59.2
102
30.6
36
194
66.8
115
33.4
41
197
67.1
115
33.9
35
227
80.8
138
39
41
234
85.3
146
40.3
40
260
102
172
44.7
36
77.8
102
24.1
46.7
17.7
35
98.5
130
31.5
55.3
22.6
45
98.1
129
31.1
54.8
22.5
38
125
165
39.8
69.1
28.6
46
122
162
39.4
68.5
28.1
44
163
213
50
86.3
37.1
52
167
217
49.6
85.7
37.7
47
185
241
24.2
98.1
41.9
54
186
243
24.2
97.8
42.2
59
204
268
63.6
110
46.5
67
210
273
62.9
109
47.4
57
241
316
75.5
130
54.9
67
252
331
78.3
136
57.4
67
290
379
89
154
65.9
63
27.5
4.7
22.5
35.7
6.2
33.7
35.3
6.1
36.9
45
7.8
37.3
43.9
7.6
37.1
56.9
9.8
45.7
57.7
9.9
37.2
64.8
11.2
34.9
65.3
11.2
28.1
71.2
12.3
42.1
72.3
12.5
34.5
83.2
14.3
40.9
85.9
14.8
33.7
95.3
16.4
41.4
scroll
scroll
scroll
scroll
scroll
scroll
scroll
scroll
scroll
scroll
scroll
scroll
scroll
scroll
2
68
208
2
2
80
265
2
2
80
265
2
2
97
320.5
2
2
97
320.5
2
2
130.8
375.4
2
2
130.8
375.4
2
2
147.4
439.4
2
2
147.4
439.4
2
2
164
456
2
2
164
456
2
3
196.2
440.8
3
4
194
417.5
4
4
294.8
586.8
4
1
1
1
1
1
1
1
1
1
1
1
1
1
1
5.9
18.3
8.4
23.7
7.5
23.5
10.5
29.9
8.8
29.2
10.5
37.9
11
38.4
13
43.1
17.2
43.4
16
47.4
19.6
48.1
18.8
55.3
22
57.1
23.6
63.3
1
1
1
1
1
1
1
1
1
1
1
1
1
1
5.1
24.8
5.8
31.7
6.7
31.4
7.2
40.1
6.7
39.3
8.7
52
8.3
52.8
11.1
58.7
9.5
59.1
17.6
64.9
15.8
66.1
17.6
76.9
20.3
80.4
20.3
92.3
2
1
2
1
2
1
2
1
2
1
2
1
2
2
2 x 0.6
2.8
1.7
2.8
2 x 0.6
2.8
2.1
2.8
2 x 0.8
2.8
4
2.8
2 x 1.0
2.8
5.3
2.8
2 x 2.1
2.8
5.3
2.8
2 x 2.1
2.8
6.3
4.2
2 x 2.1
5.6
2 x 2.1
5.6
3
4
4
4
4
4
4
5
5
5
5
5
5
5
30000
2.4
4.9
40000
2.5
6.5
40000
2.5
6.5
46000
3.6
11.4
46000
3.6
11.4
55800
6.4
11.4
55800
6.4
11.4
60000
4.6
14.3
60000
4.6
14.3
66000
6.1
14.3
66000
6.1
14.3
69000
7
14.3
69000
8.1
14.3
69000
8.1
14.3
R410A
R410A
R410A
R410A
R410A
R410A
R410A
R410A
R410A
R410A
R410A
R410A
R410A
R410A
13.5
2
18.9
1
19.3
2
23.5
1
24.1
2
24.6
1
24.9
2
47.4
1
47.8
2
49.3
1
49.6
2
49.9
1
60.8
2
60.6
2
400/3/50 400/3/50 400/3/50 400/3/50 400/3/50 400/3/50 400/3/50 400/3/50 400/3/50 400/3/50 400/3/50 400/3/50 400/3/50 400/3/50
2.75
3.71
4.11
2.86
4.39
4.87
2.84
3.92
4.35
2.82
4.21
4.67
2.77
3.74
4.15
2.61
3.75
4.16
2.63
3.46
3.84
2.78
4.26
4.72
2.79
3.81
4.23
2.66
4.02
4.46
2.69
3.64
4.04
2.59
4.27
4.73
2.51
3.45
3.83
2.36
3.37
3.74
68.2
86.1
65.6
84.2
65.6
84.2
69.5
88.1
69.5
88.1
72
90.6
72
90.6
69.3
88.6
69.3
88.6
71.1
90.4
71.1
90.4
71.9
91.2
73.6
92.9
73.8
93
3/1
3/2
3/1 LN
3/2 LN
360
4/1
4/2
4/1 LN
4/2 LN
520
4/1
4/2
4/1 LN
4/2 LN
520
4/1
4/2
4/1 LN
4/2 LN
520
4/1
4/2
4/1 LN
4/2 LN
520
4/1
4/2
4/1 LN
4/2 LN
520
4/1
4/2
4/1 LN
4/2 LN
520
5/1
5/2
5/1 LN
5/2 LN
720
5/1
5/2
5/1 LN
5/2 LN
720
5/1
5/2
5/1 LN
5/2 LN
720
5/1
5/2
5/1 LN
5/2 LN
720
5/1
5/2
5/1 LN
5/2 LN
720
5/1
5/2
5/1 LN
5/2 LN
720
5/1
5/2
5/1 LN
5/2 LN
720
2600
1200
2060
3700
1260
2050
3700
1260
2050
3700
1260
2050
3700
1260
2050
3700
1260
2050
3700
1260
2050
4950
1260
2090
4950
1260
2090
4950
1260
2090
4950
1260
2090
4950
1260
2090
4950
1260
2090
4950
1260
2090
840
1310
1310
1380
1380
1410
1410
1860
1860
1870
1870
2020
2130
2170
-73
-88.9
-88.9
-88.9
-88.9
-88.9
-88.9
-88.9
-88.9
-88.9
-88.9
-88.9
-88.9
-88.9
1 1/2"
2"
2"
2"
2"
2"
2"
2"
2"
2"
2"
2"
2"
2"
-73
-88.9
-88.9
-88.9
-88.9
-88.9
-88.9
-88.9
-88.9
-88.9
-88.9
-88.9
-88.9
-88.9
(4) Sound pressure level [Lpm] at 1m far according to ISO EN 3744
(5) Sound power level [Lw] according to ISO EN 9614-2.
49
LIQUID CHILLERS | AIR-COOLED
EQUL PF
21 / 290
Cooling only
SCROLL COMPRESSORS
DUCTABLE FAN
Cooling capacities from 20 to 260 kW
29 sizes
Refrigerant: R410A
EER up to 3.26
ESEER up to 4.67
ESPECIALLY FOR
SETUP IN DIFFICULT
LOCATIONS
MAIN FEATURES
Available with single or double refrigeration circuit(s)
1 or 2 SCROLL compressors mounted on
mounted on antivibration mounts
Condenser on one face only
Possible installation in difficult locations
External static pressure from 50 to 700 Pa depending
on model
Plug fan as standard
AVAILABLE VERSIONS
Partial heat recovery version
Total heat recovery version
ELN extra low sound level version
Brine low and very low temperature versions
All-year-round operation as a standard feature (-12°C)
Main characteristics
Ductable unit
Choice of vertical or horizontal air discharge
Installation inside buildings
Mono or twin circuit units
High performance
Easy access to components
Numerous acoustic sound levels possible
Water tank under the unit for better mass gravity and
reduced footprint (cf. option)
Partial or total heat recovery
EC fan motor as standard:
Remote demand limit via additional electronic board
Analog setpoint compensation
Easy maintenance
Service valves on liquid and discharge lines
Main accessories and options
Code
118
119
150
151
160
170
172
175
251
351
450
451
460
605
731
739
740
756
757
768
822
919
923
926
931
932
934
942
943
Kit A leaving chilled water low temperature operation
Kit B leaving chilled water low temperature operation
Kit LNO low sound level
Kit ELN extra low sound level
Discharge air plenum with sound attenuator
Antivibration mounts - spring - supplied loose
Antivibration mounts - rubber -supplied loose
Victaulic connections
Coil protection kit
Coils with pre-painted fins
Desuperheater
Total heat recovery
Outdoor installation kit
Power factor capacitor for cos phi 0.9 on compressor motor
Water flow switch
1 pump hydraulic kit
2 pump hydraulic kit
1 LN pump hydraulic kit
2 LN pump hydraulic kit
Water tank
Supply air plenum mounting kit
Clock card
COM MBUS/JBUS serial card
LON serial card
BACnet Ethernet - SNMP - TCP/IP serial card
BACnet MS/TP serial card
MP.COM extension card
Serial card for GSM modem
Data logger
Besides these options, please speak to our Sales Department for any other
configuration or function that is not listed as being available.
(°C)
Cooling operating limits
Evaporator water
outlet temperature
20
Indicative values. The operating T° are influenced by
a series of settings such as: operating conditions,
thermal load, adjustments, etc... Data to be confirmed
upon selection.
15
10
5
0
Glycol solution
+ low temperature kit A
-5
-10
-13
-10
-5
0
5
10
15
20
25
30
Outdoor air temperature
50
35
40
45
(°C)
EQUL PF 21 / 290 Cooling only
TECHNICAL SPECIFICATIONS
SIZE
22.1
24.1
28.1
32.1
36.1
42.1
53.1
kW
kW
A
m³/h
kPa
19.6
6.5
11.6
3.4
27
22.3
7.5
13.8
3.8
35
26
8.8
16.1
4.5
37
29.4
10
17.6
5.1
29
32.5
11.1
20.1
5.6
36
37.3
13.5
25.4
6.4
36
48.1
16.8
29.1
8.3
33
kW
kW
kW
A
m³/h
kPa
20.6
26.6
6
11
4.6
45
23.6
30.5
6.9
12.9
5.3
60
27.9
35.8
7.9
14.9
6.2
57
31.6
40.6
9
16.2
7.1
47
35.4
45.6
10.2
18.7
7.9
59
41.5
53.3
11.9
22.8
9.3
59
50.5
66.3
15.8
27.7
11.5
47
Heating capacity kW
Heat recovery exchanger water flow m³/h
Heat recovery pressure loss kPa
7.2
1.2
18.2
8.2
1.4
23.5
9.5
1.6
32.1
10.8
1.9
13.8
11.9
2.1
16.9
13.7
2.4
22.3
17.6
3
36.9
COOLING ONLY (1)
Cooling capacity
Compressors absorbed power
Nominal operating current Compressors
Evaporator water flow
Evaporator pressure loss
COOLING ONLY + HEAT RECOVERY 100% (2)
Cooling capacity
Heating capacity
Compressors absorbed power
Nominal operating current Compressors
Heat recovery exchanger water flow
Heat recovery pressure loss
PARTIAL HEAT RECOVERY (3)
COMPRESSORS
Quantity
Maximum operating current
Starting current
Number of capacity steps
EVAPORATOR (brazed-plate)
scroll
scroll
scroll
scroll
scroll
scroll
scroll
n.
A
A
n.
1
16
95
1
1
21
111
1
1
22
118
1
1
25
118
1
1
31
140
1
1
34
174
1
1
40
225
1
n.
1
1
1
1
1
1
1
1.9
5.2
1.9
5.9
1.9
6.8
2.5
7.8
2.5
8.8
2.5
10.1
3.1
12.8
1
1
1
1
1
1
1
1.9
6.4
1.9
7.4
1.9
8.6
2.5
9.8
2.5
11.1
2.5
13
3.1
16.1
1
1
1
1
1
1
1
0.4
1.9
0.4
2.2
0.4
2.5
0.6
2.9
0.6
3.2
0.6
3.7
0.6
4.7
n.
1
1
1
1
1
1
2
m³/h
Pa
Pa
kW
A
6,500
50
737
0.6
4.3
7000
50
704
0.7
4.3
8,500
50
509
1.1
4.3
10000
50
480
1.2
4.9
11000
50
312
1.6
4.9
12000
50
112
2.1
4.9
16000
50
568
2
8.6
R410A
R410A
R410A
R410A
R410A
R410A
R410A
5.3
1
5.3
1
5.3
1
5.5
1
5.6
1
5.6
1
9
1
Water volume l
Maximum water flow m³/h
TOTAL HEAT RECOVERY EXCHANGER
n.
Water volume l
Maximum water flow m³/h
PARTIAL HEAT RECOVERY EXCHANGER
n.
Water volume l
Maximum water flow m³/h
PLUG FANS
Total air flow
External static pressure
MAX External static pressure
Absorbed power
Nominal operating current Compressors
REFRIGERANT
Total refrigerant load (excluding options) kg
Number of refrigerant circuits n.
SUPPLY VOLTAGE
ENERGY EFFICIENCY RATIOS (1)
V/Ph/Hz
EER kW/kW
ESEER = Eurovent standard
IPLV - ARI Standard 550/590
400/3/50 400/3/50 400/3/50 400/3/50 400/3/50 400/3/50 400/3/50
2.79
4.49
4.98
2.73
4.4
4.88
2.63
4.05
4.5
2.63
4.1
4.55
2.56
3.88
4.3
2.4
3.57
3.96
2.56
3.93
4.36
70.6
87.1
72.1
88.7
76.3
92.9
75.6
92.1
77.6
94.2
79.4
96
77.6
94.8
1/1
-1/1 LN
-130
1/1
-1/1 LN
-130
1/1
-1/1 LN
-130
1/1
-1/1 LN
-130
1/1
-1/1 LN
-130
1/1
-1/1 LN
-130
2/1
-2/1 LN
-210
1250
890
1950
1250
890
1950
1250
890
1950
1250
890
1950
1250
890
1950
1250
890
1950
1800
1040
2000
kg
370
370
380
390
390
400
630
Ø
Ø mm
1 1/2"
--
1 1/2"
--
1 1/2"
--
1 1/2"
--
1 1/2"
--
1 1/2"
--
2"
--
Ø
1"
1"
1"
1"
1"
1"
1 1/4"
Ø
Ø mm
1 1/2"
--
1 1/2"
--
1 1/2"
--
1 1/2"
--
1 1/2"
--
1 1/2"
--
2"
--
SOUND LEVELS
Average sound pressure level [Lpm] (4) dB(A)
Sound power level (Lw) (5) dB(A)
HYDRAULIC KIT
1 pump 2 poles
2 pumps 2 poles
1 pump 4 poles
2 pumps 4 poles
Water tank volume
PPF UNI
PPF UNI
PPF UNI
PPF UNI
l
DIMENSIONS
Length mm
Width mm
Height mm
NET WEIGHT
HYDRAULIC CONNECTIONS
EVAPORATOR
Inlet outlet diameter – ISO 7/1 – R
Inlet outlet diameter
PARTIAL HEAT RECOVERY EXCHANGER
Inlet outlet diameter – ISO 7/1 – R
TOTAL HEAT RECOVERY EXCHANGER
Inlet outlet diameter – ISO 7/1 – R
Inlet outlet diameter
(1) Gross value - chilled water temperature 12/7°C; outdoor temperature 35°C.
(2) Gross value - chilled water temperature 12/7°C and hot water temperature 40/45°C.
(3) Gross value - chilled water temperature 12/7°C; outdoor temperature 35°C and hot
water temperature 40/45°C.
(4) Sound pressure level [Lpm] at 1m far according to ISO EN 3744
(5) Sound power level [Lw] according to ISO EN 9614-2.
51
➜
LIQUID CHILLERS | AIR-COOLED
EQUL PF 21 / 290 Cooling only
SIZE
TECHNICAL SPECIFICATIONS
67.1
55.1
55.2
62.1
62.2
71.1
71.2
85.1
kW
kW
A
m³/h
kPa
60.3
22.2
37.9
10.4
29
50.7
17.3
31.8
8.7
36
50.8
17.3
31.8
8.7
21
57
19.7
34.9
9.8
35
56.9
19.7
35
9.8
18
59.1
21.5
38.9
10.2
35
63.4
22
39.8
10.9
20
75.6
25.7
49.1
13
37
kW
kW
kW
A
m³/h
kPa
64.1
84
19.8
34.4
14.6
42
52.9
69.3
16.5
30.6
12.1
52
53.7
69.8
16.1
30.1
12.1
34
59.8
78.4
18.6
33.3
13.6
50
61.3
79.4
18.1
32.6
13.8
30
68.3
89
20.7
37.9
15.5
55
68.9
89.4
20.5
37.5
15.5
33
80.3
104
24.1
46.3
18.1
57
Heating capacity kW
Heat recovery exchanger water flow m³/h
Heat recovery pressure loss kPa
22.1
3.8
37.8
18.6
3.2
26.7
18.6
3.2
30.6
20.9
3.6
33.8
20.9
3.6
13
21.7
3.7
36.3
23.3
4
16.1
27.7
4.8
34.8
scroll
scroll
scroll
scroll
scroll
scroll
scroll
scroll
1
48.5
272
1
2
44
140
2
2
44
140
2
2
50
143
2
2
50
143
2
2
62
171
2
2
62
171
2
2
68
208
2
COOLING ONLY (1)
Cooling capacity
Compressors absorbed power
Nominal operating current Compressors
Evaporator water flow
Evaporator pressure loss
COOLING ONLY + HEAT RECOVERY 100% (2)
Cooling capacity
Heating capacity
Compressors absorbed power
Nominal operating current Compressors
Heat recovery exchanger water flow
Heat recovery pressure loss
PARTIAL HEAT RECOVERY (3)
COMPRESSORS
Quantity
Maximum operating current
Starting current
Number of capacity steps
EVAPORATOR (brazed-plate)
n.
A
A
n.
n.
Water volume l
Maximum water flow m³/h
TOTAL HEAT RECOVERY EXCHANGER
n.
Water volume l
Maximum water flow m³/h
PARTIAL HEAT RECOVERY EXCHANGER
n.
Water volume l
Maximum water flow m³/h
PLUG FANS
Total air flow
External static pressure
MAX External static pressure
Absorbed power
Nominal operating current Compressors
1
1
1
1
1
1
1
3.9
13.3
3.6
13.3
3.9
15
3.6
15.1
4.7
17.2
4.2
17.1
5.8
20.4
1
1
1
1
1
1
1
1
3.9
20.4
3.9
16.6
3.6
16.7
3.9
19
3.6
19.2
4.7
21.6
4.2
21.8
5.8
25.4
1
1
2
1
2
1
2
1
0.8
5.9
0.8
4.9
2 x 0.4
4.9
0.8
5.5
2 x 0.6
5.5
0.8
6.3
2 x 0.6
6.3
1
7.5
n.
2
2
2
2
2
2
2
3
m³/h
Pa
Pa
kW
A
21000
50
363
2.3
8.4
18000
50
589
2
9.8
18000
50
589
2
9.8
20500
50
421
2.2
8.4
20500
50
421
2.2
8.4
23000
50
308
2.9
8.4
23000
50
308
2.9
8.4
25500
50
643
2.7
14.7
R410A
R410A
R410A
R410A
R410A
R410A
R410A
R410A
9.5
1
9.3
1
9
2
9.3
1
9
2
9.7
1
9.3
2
13.7
1
REFRIGERANT
Total refrigerant load (excluding options) kg
Number of refrigerant circuits n.
SUPPLY VOLTAGE
ENERGY EFFICIENCY RATIOS (1)
1
3.9
16.2
V/Ph/Hz 400/3/50 400/3/50 400/3/50 400/3/50 400/3/50 400/3/50 400/3/50 400/3/50
EER kW/kW
ESEER = Eurovent standard
IPLV - ARI Standard 550/590
2.46
3.56
4.02
2.62
3.92
4.35
2.63
4.31
4.78
2.61
3.93
4.36
2.6
3.73
4.14
2.42
4.04
4.48
2.55
3.71
4.11
2.67
4.41
4.89
79.5
96.7
75.9
93.1
75.9
93.1
69.6
86.8
69.6
86.8
72
89.2
72
89.2
76
93.9
2/1
-2/1 LN
-210
2/1
-2/1 LN
-210
2/1
-2/1 LN
-210
2/1
-2/1 LN
-210
2/1
-2/1 LN
-210
2/1
-2/1 LN
-210
3/1
3/2
3/1 LN
3/2 LN
360
1800
1040
2000
1800
1040
2000
1800
1040
2000
1800
1040
2000
1800
1040
2000
1800
1040
2000
1800
1040
2000
2600
1200
2000
kg
670
630
630
690
700
700
710
890
Ø
Ø mm
2"
--
2"
--
2"
--
2"
--
2"
--
2"
--
2"
--
-76.1
Ø
1 1/4"
1 1/4"
1 1/4"
1 1/4"
1 1/4"
1 1/4"
1 1/4"
1 1/2"
Ø
Ø mm
2"
--
2"
--
2"
--
2"
--
2"
--
2"
--
2"
--
-76.1
SOUND LEVELS
Average sound pressure level [Lpm] (4) dB(A)
Sound power level (Lw) (5) dB(A)
HYDRAULIC KIT
1 pump 2 poles
2 pumps 2 poles
1 pump 4 poles
2 pumps 4 poles
Water tank volume
PPF UNI 2/1
PPF UNI -PPF UNI 2/1 LN
PPF UNI -l
210
DIMENSIONS
Length mm
Width mm
Height mm
NET WEIGHT
HYDRAULIC CONNECTIONS
EVAPORATOR
Inlet outlet diameter – ISO 7/1 – R
Inlet outlet diameter
PARTIAL HEAT RECOVERY EXCHANGER
Inlet outlet diameter – ISO 7/1 – R
TOTAL HEAT RECOVERY EXCHANGER
Inlet outlet diameter – ISO 7/1 – R
Inlet outlet diameter
(1) Gross value - chilled water temperature 12/7°C; outdoor temperature 35°C.
(2) Gross value - chilled water temperature 12/7°C and hot water temperature 40/45°C.
(3) Gross value - chilled water temperature 12/7°C; outdoor temperature 35°C and hot water
temperature 40/45°C.
52
85.2
107.1
107.2
135.1
135.2
170.1
170.2
195.1
195.2
220.1
220.2
250.1
265.2
290.2
75.2
25.8
49.3
12.9
23
96.8
33
57.5
16.7
36
95.7
32.8
57.2
16.4
26
120
42.3
72.4
20.6
37
118
42.3
72.4
20.3
30
156
53.5
91.3
26.8
36
154
53.2
91
26.4
33
176
62.4
106
30.3
42
173
62.9
107
29.8
36
202
67.3
115
34.8
43
199
67.6
116
34.2
37
227
83.7
142
39
41
239
86.2
147
41.1
41
264
102
173
45.4
45
80.6
104
23.9
45.9
18.2
37
101
132
31.5
55.4
23
47
100
132
31.1
54.8
22.9
40
126
166
39.9
69.1
28.9
47
125
165
39.4
68.6
28.6
45
164
214
50.7
87.3
37.2
40
161
212
50.4
86.8
36.8
45
186
243
57.2
98.7
42.2
72
191
247
56.6
97.9
43
61
208
272
63.8
110
47.2
69
214
277
63.1
110
48.1
59
246
322
75.5
130
55.9
70
258
337
78.3
137
58.5
69
294
383
89.5
155
66.6
78
27.6
4.8
22.6
35.5
6.1
33.4
35.1
6.1
36.6
43.9
7.6
35.4
43.2
7.5
36.1
57.2
9.9
46.1
56.3
9.7
35.5
64.5
11.1
34.6
63.6
11
26.7
74.2
12.8
45.7
73.1
12.6
35.3
83.2
14.3
40.9
87.7
15.1
35.1
96.7
16.7
42.7
scroll
scroll
scroll
scroll
scroll
scroll
scroll
scroll
scroll
scroll
scroll
scroll
scroll
scroll
2
68
208
2
2
80
265
2
2
80
265
2
2
97
320.5
2
2
97
320.5
2
2
130.8
375.4
2
2
130.8
375.4
2
2
147.4
439.4
2
2
147.4
439.4
2
2
164
456
2
2
164
456
2
3
196.2
440.8
3
4
194
417.5
4
4
294.8
586.8
4
1
1
1
1
1
1
1
1
1
1
1
1
1
1
5.1
20.4
5.8
25.8
6.7
25.5
7.2
32.1
6.7
31.6
8.7
41.5
8.3
40.9
11.1
46.1
9.5
46.8
17.6
53.7
15.8
52.8
17.6
60.2
20.3
63.9
20.3
70
1
1
1
1
1
1
1
1
1
1
1
1
1
1
5.1
25.4
5.8
32.2
6.7
31.9
7.2
40.4
6.7
39.9
8.7
52.1
8.3
51.4
11.1
59
9.5
60.1
17.6
66.1
15.8
67.4
17.6
78.1
20.3
81.7
20.3
93
2
1
2
1
2
1
2
1
2
1
2
1
2
2
2 x 0.6
7.5
1.7
9.5
2 x 0.6
9.4
2.1
11.8
2 x 0.8
11.6
4
15.2
2 x 1.0
15
5.3
16.9
2 x 1.7
17.2
5.3
19.4
2 x 2.1
19.7
6.3
22
2 x 2.1
23.4
2 x 2.1
25.7
3
3
3
4
4
4
4
4
4
5
5
5
5
5
25500
50
643
2.7
14.7
32000
50
324
5
14.7
32000
50
324
5
14.7
40000
50
467
3.6
16.8
40000
50
467
3.6
16.8
52000
50
175
7.6
16.8
52000
50
175
7.6
16.8
54000
50
120
8.5
16.8
54000
50
120
8.5
16.8
62500
50
243
8.2
21
62500
50
243
8.2
21
64000
50
212
8.8
21
66000
50
147
10.1
21
66000
50
147
10.1
21
R410A
R410A
R410A
R410A
R410A
R410A
R410A
R410A
R410A
R410A
R410A
R410A
R410A
R410A
13.5
2
16.9
1
17.3
2
20.1
1
20.6
2
24.6
1
24.6
2
25.7
1
26
2
49.3
1
49.6
2
49.9
1
60.8
2
60.7
2
400/3/50 400/3/50 400/3/50 400/3/50 400/3/50 400/3/50 400/3/50 400/3/50 400/3/50 400/3/50 400/3/50 400/3/50 400/3/50 400/3/50
2.64
3.95
4.38
2.55
3.89
4.31
2.54
3.56
3.95
2.61
4.45
4.93
2.57
3.94
4.37
2.55
3.91
4.33
2.53
3.58
3.97
2.48
3.79
4.2
2.42
3.49
3.87
2.68
4.13
4.58
2.62
3.81
4.23
2.46
4.31
4.78
2.48
3.68
4.08
2.35
3.55
3.94
76
93.9
80.8
98.7
80.8
98.7
74
92.6
74
92.6
77.3
95.9
77.3
95.9
78
96.6
78
96.6
77.3
96.6
77.3
96.6
77.7
96.9
78.1
97.4
78.1
97.4
3/1
3/2
3/1 LN
3/2 LN
360
3/1
3/2
3/1 LN
3/2 LN
360
3/1
3/2
3/1 LN
3/2 LN
360
4/1
4/2
4/1 LN
4/2 LN
520
4/1
4/2
4/1 LN
4/2 LN
520
4/1
4/2
4/1 LN
4/2 LN
520
4/1
4/2
4/1 LN
4/2 LN
520
4/1
4/2
4/1 LN
4/2 LN
520
4/1
4/2
4/1 LN
4/2 LN
520
5/1
5/2
5/1 LN
5/2 LN
720
5/1
5/2
5/1 LN
5/2 LN
720
5/1
5/2
5/1 LN
5/2 LN
720
5/1
5/2
5/1 LN
5/2 LN
720
5/1
5/2
5/1 LN
5/2 LN
720
2600
1200
2000
2600
1200
2000
2600
1200
2000
3700
1260
2000
3700
1260
2000
3700
1260
2000
3700
1260
2000
3700
1260
2000
3700
1260
2000
4950
1260
2040
4950
1260
2040
4950
1260
2040
4950
1260
2040
4950
1260
2040
890
1080
1080
1460
1460
1550
1550
1600
1600
1970
1970
2140
2290
2340
-76.1
-76.1
-76.1
-88.9
-88.9
-88.9
-88.9
-88.9
-88.9
-88.9
-88.9
-88.9
-88.9
-88.9
1 1/2"
1 1/2"
1 1/2"
2"
2"
2"
2"
2"
2"
2"
2"
2"
2"
2"
-76.1
-76.1
-76.1
-88.9
-88.9
-88.9
-88.9
-88.9
-88.9
-88.9
-88.9
-88.9
-88.9
-88.9
(4) Sound pressure level [Lpm] at 1m far according to ISO EN 3744
(5) Sound power level [Lw] according to ISO EN 9614-2.
53
LIQUID CHILLERS | AIR-COOLED
EQUH
21 / 260
Reversible
SCROLL COMPRESSORS
ESPECIALLY FOR
SETUP IN DIFFICULT
LOCATIONS
Cooling capacities from 20 to 260 kW
Heating capacities from 23 to 333 kW
29 sizes
Refrigerant: R410A
EER up to 3.08
ESEER up to 4.67
COP up to 3.66
MAIN FEATURES
Reversible operation
Available with single or double refrigeration circuit(s)
1 or 2 SCROLL compressors mounted on
antivibration mounts
Condenser on one face only
Possible installation in difficult locations
AVAILABLE VERSIONS
Partial heat recovery version
ELN extra low sound level version
For external static pressure see PF version
Main characteristics
Possible installation on corners, against walls
Mono or twin circuit units
Water tank under the unit for better distribution of mass
and reduced footprint (cf. option)
High performance
Easy access for maintenance
Large choice of sound levels
Partial or total heat recovery
Remote demand limit via additional electronic board
Analog setpoint compensation
Easy maintenance
Service valves on liquid and discharge lines
Main accessories and options
Code
150
151
170
172
175
251
351
450
605
731
739
740
756
757
768
919
923
926
931
932
934
942
943
Kit LNO low sound level
Kit ELN extra low sound level
Antivibration mounts - spring - supplied loose
Antivibration mounts - rubber - supplied loose
Victaulic connections
Coil protection kit
Coils with pre-painted fins
Desuperheater
Power factor capacitor for cos phi 0.9 on compressor motor
Water flow switch
1 pump hydraulic kit
2 pump hydraulic kit
1 LN pump hydraulic kit
2 LN pump hydraulic kit
Water tank
Clock card
COM MBUS/JBUS serial card
LON serial card
BACnet Ethernet - SNMP - TCP/IP serial card
BACnet MS/TP serial card
MP.COM extension card
Serial card for GSM modem
Data logger
Besides these options, please speak to our Sales Department for any other
configuration or function that is not listed as being available.
Hot water outlet temperature
(°C) 60
Heating operating limits
Indicative values. The operating T° are influenced by
a series of settings such as: operating conditions,
thermal load, adjustments, etc... Data to be confirmed
upon selection.
55
50
45
40
35
30
-10
-5
0
5
10
15
Outdoor air temperature
54
20
25
30 (°C)
EQUH 21 / 260 Reversible
TECHNICAL SPECIFICATIONS
SIZE
21.1
24.1
28.1
30.1
34.1
19.2
6.1
11.1
3.3
26
21.6
7.1
13.2
3.7
33
25.5
8.2
15.2
4.4
36
27.7
10.2
18.2
4.8
27
32.7
10.1
18.5
5.6
35
23.9
6.2
11.2
27.2
7.1
13.3
31.8
8.2
15.2
32.1
9.4
16.7
41
10.3
19
7
1.2
17.5
7.9
1.4
22.2
9.4
1.6
30.9
10.2
1.8
12.3
12
2.1
17.1
SUMMER MODE (1)
Cooling capacity
Compressors absorbed power
Nominal operating current Compressors
Evaporator water flow
Evaporator pressure loss
kW
kW
A
m³/h
kPa
WINTER MODE (2)
Heating capacity kW
Compressors absorbed power kW
Nominal operating current Compressors A
PARTIAL HEAT RECOVERY (3)
Heating capacity kW
Heat recovery exchanger water flow m³/h
Heat recovery pressure loss kPa
COMPRESSORS
Quantity
Maximum operating current
Starting current
Number of capacity steps
EVAPORATOR (brazed-plate)
n.
A
A
n.
n.
Water volume l
Maximum water flow m³/h
PARTIAL HEAT RECOVERY EXCHANGER
n.
Water volume l
Maximum water flow m³/h
AXIAL FANS (AC)
n.
Total air flow m³/h
Absorbed power kW
Nominal operating current Fans A
REFRIGERANT
Total refrigerant load (excluding options) kg
Number of refrigerant circuits n.
SUPPLY VOLTAGE
ENERGY EFFICIENCY RATIOS (1)
V/Ph/Hz
EER kW/kW
COP kW/kW
ESEER = Eurovent standard
IPLV - ARI Standard 550/590
scroll
scroll
scroll
scroll
scroll
1
16
95
1
1
21
111
1
1
22
118
1
1
25
118
1
1
31
140
1
1
1
1
1
1
1.9
4.9
1.9
5.6
1.9
6.6
2.5
7.1
2.5
7.8
1
1
1
1
1
0.4
1.8
0.4
2.1
0.4
2.4
0.6
2.6
0.6
2.9
1
1
1
1
2
8,500
0.5
1.6
8,500
0.5
1.6
11000
0.8
1.6
11000
0.8
1.6
13000
0.5
3.2
R410A
R410A
R410A
R410A
R410A
10.5
1
10.6
1
10.6
1
10.8
1
12.9
1
400/3/50
400/3/50
400/3/50
400/3/50
400/3/50
2.95
3.6
4.59
5.09
2.87
3.59
4.66
5.17
2.86
3.57
4.48
4.97
2.53
3.17
4.29
4.76
3.08
3.8
4.67
5.18
64.6
81.1
64.9
81.5
65.6
82.2
64.8
81.4
64.9
82.2
1/1
-1/1 LN
-130
1/1
-1/1 LN
-130
1/1
-1/1 LN
-130
1/1
-1/1 LN
-130
2/1
-2/1 LN
-210
1250
890
2010
1250
890
2010
1250
890
2010
1250
890
2010
1800
1040
2060
390
390
400
410
410
1 1/2"
--
1 1/2"
--
1 1/2"
--
1 1/2"
--
2"
--
1"
1"
1"
1"
1 1/4"
SOUND LEVELS
Average sound pressure level [Lpm] (4) dB(A)
Sound power level (Lw) (5) dB(A)
HYDRAULIC KIT
1 pump 2 poles
2 pumps 2 poles
1 pump 4 poles
2 pumps 4 poles
Water tank volume
PPF REV
PPF REV
PPF REV
PPF REV
l
DIMENSIONS
Length mm
Width mm
Height mm
NET WEIGHT
HYDRAULIC CONNECTIONS
kg
EVAPORATOR
Inlet outlet diameter – ISO 7/1 – R Ø
Inlet outlet diameter Ø mm
PARTIAL HEAT RECOVERY EXCHANGER
Inlet outlet diameter – ISO 7/1 – R Ø
(1) Gross value - chilled water temperature 12/7°C; outdoor temperature 35°C.
(2) Gross value - leaving hot water temperature 45°C and outdoor temperature 7°C.
(3) Gross value - chilled water temperature 12/7°C; outdoor temperature 35°C and hot
water temperature 40/45°C.
(4) Sound pressure level [Lpm] at 1m far according to ISO EN 3744
(5) Sound power level [Lw] according to ISO EN 9614-2.
55
➜
LIQUID CHILLERS | AIR-COOLED
EQUH 21 / 260 Reversible
TECHNICAL SPECIFICATIONS
SIZE
40.1
50.1
52.1
52.2
37.6
12.2
23.6
6.5
36
46.8
15.7
27.6
8.1
31
47.7
16.8
31.3
8.2
32
47.7
16.8
31.3
8.2
32
47.2
12.2
23.6
60
15.9
25.6
61.7
17
31.8
61.5
16.6
30.8
13.8
2.4
22.6
17.2
3
35
17.5
3
23.7
17.5
3
27.1
SUMMER MODE (1)
Cooling capacity
Compressors absorbed power
Nominal operating current Compressors
Evaporator water flow
Evaporator pressure loss
kW
kW
A
m³/h
kPa
WINTER MODE (2)
Heating capacity kW
Compressors absorbed power kW
Nominal operating current Compressors A
PARTIAL HEAT RECOVERY (3)
Heating capacity kW
Heat recovery exchanger water flow m³/h
Heat recovery pressure loss kPa
COMPRESSORS
Quantity
Maximum operating current
Starting current
Number of capacity steps
EVAPORATOR (brazed-plate)
n.
A
A
n.
n.
Water volume l
Maximum water flow m³/h
PARTIAL HEAT RECOVERY EXCHANGER
n.
Water volume l
Maximum water flow m³/h
AXIAL FANS (AC)
n.
Total air flow m³/h
Absorbed power kW
Nominal operating current Fans A
REFRIGERANT
Total refrigerant load (excluding options) kg
Number of refrigerant circuits n.
SUPPLY VOLTAGE
V/Ph/Hz
scroll
scroll
scroll
scroll
1
34
174
1
1
40
225
1
1
44
140
1
2
44
140
2
1
1
1
1
2.5
9
3.1
11.2
3.9
11.4
3.6
11.3
1
1
1
1
0.6
3.3
0.6
4.1
0.8
4.2
0.7
4.8
2
2
2
2
15000
0.8
3.2
20500
1.6
3.3
20500
1.6
3.3
20500
1.6
3.3
R410A
R410A
R410A
R410A
12.9
1
14.3
1
18.1
1
14.6
2
400/3/50
400/3/50
400/3/50
400/3/50
2.9
3.64
4.29
4.76
2.7
3.42
3.83
4.25
2.59
3.31
4.2
4.66
2.59
3.38
3.6
3.99
67.7
84.9
71.8
89
68.9
86.1
68.9
86.1
2/1
-2/1 LN
-210
2/1
-2/1 LN
-210
2/1
-2/1 LN
-210
2/1
-2/1 LN
-210
1800
1040
2060
1800
1040
2060
1800
1040
2060
1800
1040
2060
420
650
650
650
2"
--
2"
--
2"
--
2"
--
1 1/4"
1 1/4"
1 1/4"
1 1/4"
ENERGY EFFICIENCY RATIOS (1)
EER kW/kW
COP kW/kW
ESEER = Eurovent standard
IPLV - ARI Standard 550/590
SOUND LEVELS
Average sound pressure level [Lpm] (4) dB(A)
Sound power level (Lw) (5) dB(A)
HYDRAULIC KIT
1 pump 2 poles
2 pumps 2 poles
1 pump 4 poles
2 pumps 4 poles
Water tank volume
PPF REV
PPF REV
PPF REV
PPF REV
l
DIMENSIONS
Length mm
Width mm
Height mm
NET WEIGHT
kg
HYDRAULIC CONNECTIONS
EVAPORATOR
Inlet outlet diameter – ISO 7/1 – R Ø
Inlet outlet diameter Ø mm
PARTIAL HEAT RECOVERY EXCHANGER
Inlet outlet diameter – ISO 7/1 – R Ø
(1) Gross value - chilled water temperature 12/7°C; outdoor temperature 35°C.
(2) Gross value - leaving hot water temperature 45°C and outdoor temperature 7°C.
(3) Gross value - chilled water temperature 12/7°C; outdoor temperature 35°C and hot
water temperature 40/45°C.
(4) Sound pressure level [Lpm] at 1m far according to ISO EN 3744
(5) Sound power level [Lw] according to ISO EN 9614-2.
56
58.1
58.2
62.1
65.1
65.2
76.1
76.2
98.1
54.3
17.9
32.1
9.3
32
54.6
18.9
33.9
9.4
17
58
19.9
34.6
10
27
60.6
20.5
37.6
10.4
32
61.3
20.7
37.9
10.5
18
70.3
24.4
47.3
12.1
33
71.4
24.4
47.3
12.3
20
89.6
30.8
54.4
15.4
32
70.7
18.2
32.6
70.9
18.5
35
74.8
20
35.1
79.1
20.5
37.8
79.2
20.9
38.3
91.6
24.3
47.4
90.8
24.6
47.6
118
31.8
56.2
19.9
3.4
30.7
20
3.5
11.9
21.3
3.7
35
22.2
3.8
38.2
22.5
3.9
15
25.8
4.4
30.1
26.2
4.5
20.3
32.9
5.7
28.5
scroll
scroll
scroll
scroll
scroll
scroll
scroll
scroll
2
50
143
2
2
50
143
2
2
48.5
272
2
2
62
171
2
2
62
171
2
2
68
208
2
2
68
208
2
2
80
265
2
1
1
1
1
1
1
1
1
3.9
13
3.6
13
3.9
13.9
4.7
14.6
4.2
14.5
5.8
17.4
5.1
16.9
5.8
22
2
1
2
1
2
1
2
1
0.8
4.8
1.1
5.1
0.8
4.2
0.8
5.4
1.2
5.3
1
6.4
1.2
6.2
1.7
8.1
3
3
3
3
3
3
3
4
22000
1.1
4.7
22000
1.1
4.7
23000
1.3
4.7
24000
1.5
4.7
24000
1.5
4.7
30000
2.4
4.9
30000
2.4
4.9
40000
2.5
6.5
R410A
R410A
R410A
R410A
R410A
R410A
R410A
R410A
19.6
1
17.9
2
22.9
1
18.3
1
23.3
2
21.6
1
24
2
32.3
1
400/3/50
400/3/50
400/3/50
400/3/50
400/3/50
400/3/50
400/3/50
400/3/50
2.85
3.66
4.11
4.56
2.73
3.61
4.02
4.46
2.74
3.51
4.32
4.79
2.76
3.6
3.84
4.26
2.76
3.54
4.3
4.77
2.63
3.43
4.01
4.45
2.67
3.37
3.52
3.9
2.69
3.44
4.18
4.63
68
85.9
68
85.9
73.8
91.6
67.8
85.7
67.8
85.7
68.2
86.1
68.2
86.1
65.6
84.2
3/1
3/2
3/1 LN
3/2 LN
360
3/1
3/2
3/1 LN
3/2 LN
360
3/1
3/2
3/1 LN
3/2 LN
360
3/1
3/2
3/1 LN
3/2 LN
360
3/1
3/2
3/1 LN
3/2 LN
360
3/1
3/2
3/1 LN
3/2 LN
360
3/1
3/2
3/1 LN
3/2 LN
360
4/1
4/2
4/1 LN
4/2 LN
520
2600
1200
2060
2600
1200
2060
2600
1200
2060
2600
1200
2060
2600
1200
2060
2600
1200
2060
2600
1200
2060
3700
1260
2050
720
730
700
730
730
920
930
1120
-76.1
-76.1
-76.1
-76.1
-76.1
-76.1
-76.1
-88.9
1 1/2"
1 1/2"
1 1/2"
1 1/2"
1 1/2"
1 1/2"
1 1/2"
2"
➜
57
LIQUID CHILLERS | AIR-COOLED
EQUH 21 / 260 Reversible
TECHNICAL SPECIFICATIONS
SIZE
98.2
124.1
124.2
158.1
91.8
31
55
15.8
23
111
39
68.1
19.2
34
116
39.5
69
19.9
27
150
52.5
89.8
25.8
32
118
31.9
56.2
149
40.6
70.2
150
40.3
69.9
182
61.3
86.2
33.7
5.8
33.7
40.9
7
30.8
42.5
7.3
34.9
55.1
9.5
42.9
SUMMER MODE (1)
Cooling capacity
Compressors absorbed power
Nominal operating current Compressors
Evaporator water flow
Evaporator pressure loss
kW
kW
A
m³/h
kPa
WINTER MODE (2)
Heating capacity kW
Compressors absorbed power kW
Nominal operating current Compressors A
PARTIAL HEAT RECOVERY (3)
Heating capacity kW
Heat recovery exchanger water flow m³/h
Heat recovery pressure loss kPa
COMPRESSORS
Quantity
Maximum operating current
Starting current
Number of capacity steps
EVAPORATOR (brazed-plate)
n.
A
A
n.
n.
Water volume l
Maximum water flow m³/h
PARTIAL HEAT RECOVERY EXCHANGER
n.
Water volume l
Maximum water flow m³/h
AXIAL FANS (AC)
n.
scroll
scroll
scroll
scroll
2
80
265
2
2
97
320.5
2
2
97
320.5
2
2
130.8
375.4
2
1
1
1
1
6.7
21.5
7.2
27.7
6.7
26.7
8.7
37.9
2
1
2
1
1.2
7.9
2.1
10.2
1.5
9.8
4
13.9
4
4
4
4
40000
2.5
6.5
46000
3.6
11.4
46000
3.6
11.4
55800
6.4
11.4
R410A
R410A
R410A
R410A
35.4
2
36.7
1
39.8
2
37.7
1
400/3/50
400/3/50
400/3/50
400/3/50
2.74
3.43
3.71
4.11
2.61
3.37
4.01
4.45
2.69
3.42
3.55
3.94
2.55
2.69
3.75
4.16
65.6
84.2
69.5
88.1
69.5
88.1
72
90.6
4/1
4/2
4/1 LN
4/2 LN
520
4/1
4/2
4/1 LN
4/2 LN
520
4/1
4/2
4/1 LN
4/2 LN
520
4/1
4/2
4/1 LN
4/2 LN
520
Length mm
Width mm
Height mm
3700
1260
2050
3700
1260
2050
3700
1260
2050
3700
1260
2050
kg
1120
1510
1500
1600
-88.9
-88.9
-88.9
-88.9
2"
2"
2"
2"
Total air flow m³/h
Absorbed power kW
Nominal operating current Fans A
REFRIGERANT
Total refrigerant load (excluding options) kg
Number of refrigerant circuits n.
SUPPLY VOLTAGE
V/Ph/Hz
ENERGY EFFICIENCY RATIOS (1)
EER kW/kW
COP kW/kW
ESEER = Eurovent standard
IPLV - ARI Standard 550/590
SOUND LEVELS
Average sound pressure level [Lpm] (4) dB(A)
Sound power level (Lw) (5) dB(A)
HYDRAULIC KIT
1 pump 2 poles
2 pumps 2 poles
1 pump 4 poles
2 pumps 4 poles
Water tank volume
PPF REV
PPF REV
PPF REV
PPF REV
l
DIMENSIONS
NET WEIGHT
HYDRAULIC CONNECTIONS
EVAPORATOR
Inlet outlet diameter – ISO 7/1 – R Ø
Inlet outlet diameter Ø mm
PARTIAL HEAT RECOVERY EXCHANGER
Inlet outlet diameter – ISO 7/1 – R Ø
(1) Gross value - chilled water temperature 12/7°C; outdoor temperature 35°C.
(2) Gross value - leaving hot water temperature 45°C and outdoor temperature 7°C.
(3) Gross value - chilled water temperature 12/7°C; outdoor temperature 35°C and hot
water temperature 40/45°C.
(4) Sound pressure level [Lpm] at 1m far according to ISO EN 3744
(5) Sound power level [Lw] according to ISO EN 9614-2.
58
158.2
180.1
180.2
197.1
197.2
230.1
240.2
260.2
155
53.1
91
26.6
26
170
58.4
100
29.1
34
176
59.3
102
30.3
33
188
66.1
114
32.4
41
194
66.8
115
33.4
32
227
79.7
136
39
41
223
85.2
146
38.4
36
261
100
170
45
33
195
41.3
71.4
215
57.3
98.9
215
57.4
99.4
238
64
110
238
64.5
112
280
75.4
130
288
80.8
141
333
90.1
156
56.9
9.8
36.1
62.2
10.7
32.1
64.8
11.2
27.7
69.1
11.9
39.6
71.2
12.3
33.5
83.2
14.3
40.9
81.9
14.1
30.6
95.8
16.5
41.9
scroll
scroll
scroll
scroll
scroll
scroll
scroll
scroll
2
130.8
375.4
2
2
147.4
439.4
2
2
147.4
439.4
2
2
164
456
2
2
164
456
2
3
196.2
440.8
3
4
194
417.5
4
4
294.8
586.8
4
1
1
1
1
1
1
1
1
8.3
37.7
11.1
42.2
9.5
40.6
17.6
48.3
15.8
46.9
17.6
55.3
20.3
54.5
20.3
60.6
2
1
2
1
2
1
2
2
2
13.8
5.3
15.5
3.4
14.9
5.3
17.7
3.4
17.2
6.3
20.3
4.2
20
4.2
22.2
4
5
5
5
5
5
5
5
55800
6.4
11.4
60000
4.6
14.3
60000
4.6
14.3
66000
6.1
14.3
66000
6.1
14.3
69000
7
14.3
69000
8.1
14.3
69000
8.1
14.3
R410A
R410A
R410A
R410A
R410A
R410A
R410A
R410A
40.4
2
60.6
1
63.7
2
78.8
1
95.6
2
79.5
1
106.8
2
106.7
2
400/3/50
400/3/50
400/3/50
400/3/50
400/3/50
400/3/50
400/3/50
400/3/50
2.6
4.09
3.45
3.83
2.7
3.48
4.17
4.62
2.76
3.47
3.65
4.05
2.6
3.4
4.1
4.55
2.66
3.37
3.63
4.03
2.62
3.4
4.27
4.73
2.39
3.24
3.35
3.72
2.42
3.39
3.3
3.66
72
90.6
69.3
88.6
69.3
88.6
71.1
90.4
71.1
90.4
71.9
91.2
73.6
92.9
73.8
93
4/1
4/2
4/1 LN
4/2 LN
520
5/1
5/2
5/1 LN
5/2 LN
720
5/1
5/2
5/1 LN
5/2 LN
720
5/1
5/2
5/1 LN
5/2 LN
720
5/1
5/2
5/1 LN
5/2 LN
720
5/1
5/2
5/1 LN
5/2 LN
720
5/1
5/2
5/1 LN
5/2 LN
720
5/1
5/2
5/1 LN
5/2 LN
720
3700
1260
2050
4950
1260
2090
4950
1260
2090
4950
1260
2090
4950
1260
2090
4950
1260
2090
4950
1260
2090
4950
1260
2090
1590
1650
1640
2050
2040
2220
2380
2430
-88.9
-88.9
-88.9
-88.9
-88.9
-88.9
-88.9
-88.9
2"
2"
2"
2"
2"
2"
2"
2"
59
LIQUID CHILLERS | AIR-COOLED
EQUH PF
22 / 290
Reversible
SCROLL COMPRESSORS
DUCTABLE FAN
ESPECIALLY FOR
SETUP IN DIFFICULT
LOCATIONS
Cooling capacities from 20 to 260 kW
Heating capacities from 23 to 333 kW
29 sizes
Refrigerant: R410A
EER up to 3.08
ESEER up to 4.67
COP up to 3.66
MAIN FEATURES
Reversible operation
Available with single or double refrigeration circuit(s)
1 or 2 SCROLL compressors mounted on
antivibration mounts
Condenser on one face only
Possible installation in ‘difficult’ locations
Ductable unit with external static pressure
from 50 to 700 Pa depending on model
AVAILABLE VERSIONS
Partial heat recovery version
ELN extra low sound level version
Main characteristics
Plug fan as standard
Possible installation in corners, against walls
Mono or twin circuit units
Water tank under the unit for better mass distribution and
reduced footprint (cf. option)
High performance
Easy access to components
Large choice of sound levels
Partial or total heat recovery
EC fan motor as standard
Remote demand limit via additional electronic board
Analog setpoint compensation
Easy maintenance
Service valves on liquid and discharge lines
Main accessories and options
Code
150
160
170
172
175
251
351
450
460
605
731
739
740
756
757
768
919
923
926
931
932
934
942
943
Kit LNO low sound level
Discharge air plenum with sound attenuator
Antivibration mounts - spring - supplied loose
Antivibration mounts - rubber - supplied loose
Victaulic connections
Coil protection kit
Coils with pre-painted fins
Desuperheater
Outdoor installation kit
Power factor capacitor for cos phi 0.9 on compressor motor
Water flow switch
1 pump hydraulic kit
2 pump hydraulic kit
1 LN pump hydraulic kit
2 LN pump hydraulic kit
Water tank
Clock card
COM MBUS/JBUS serial card
LON serial card
BACnet Ethernet - SNMP - TCP/IP serial card
BACnet MS/TP serial card
MP.COM extension card
Serial card for GSM modem
Data logger
Besides these options, please speak to our Sales Department for any other
configuration or function that is not listed as being available.
Hot water outlet temperature
(°C) 60
Heating operating limits
Indicative values. The operating T° are influenced by
a series of settings such as: operating conditions,
thermal load, adjustments, etc... Data to be confirmed
upon selection.
55
50
45
40
35
30
-10
-5
0
5
10
15
Outdoor air temperature
60
20
25
30 (°C)
EQUH PF 22 / 290 Reversible
SIZE
TECHNICAL SPECIFICATIONS
22.1
24.1
28.1
32.1
36.1
42.1
53.1
19.1
6.4
11.5
3.3
27
20.7
7.4
13.7
3.6
35
24.2
8.7
16
4.2
37
28.8
9.9
17.4
5
29
32
11
19.9
5.5
35
36.5
13.4
25.3
6.3
36
46.2
16.6
28.7
7.9
32
23.7
6.2
11.3
25.1
7
13.3
29.3
8.1
15.2
35.5
9.3
16.5
39.8
10.3
18.8
45.6
12.1
23.4
58.2
16.1
28.2
7
1.2
17.3
7.6
1.3
20.3
8.9
1.5
27.9
10.6
1.8
13.2
11.8
2
16.4
13.4
2.3
21.3
17
2.9
34.1
COOLING ONLY (1)
Cooling capacity
Compressors absorbed power
Nominal operating current Compressors
Evaporator water flow
Evaporator pressure loss
kW
kW
A
m³/h
kPa
WINTER HEATING MODE (2)
Heating capacity kW
Compressors absorbed power kW
Nominal operating current A
PARTIAL HEAT RECOVERY (3)
Heating capacity kW
Heat recovery exchanger water flow m³/h
Heat recovery pressure loss kPa
COMPRESSORS
Quantity
Maximum operating current
Starting current
Number of capacity steps
EVAPORATOR (brazed-plate)
n.
A
A
n.
n.
Water volume l
Maximum water flow m³/h
PARTIAL HEAT RECOVERY EXCHANGER
n.
scroll
scroll
scroll
scroll
scroll
scroll
scroll
1
16
95
1
1
21
111
1
1
22
118
1
1
25
118
1
1
31
140
1
1
34
174
1
1
40
225
1
1
1
1
1
1
1
1
1.9
6.9
1.9
7.8
2.1
9
2.8
10.3
2.9
11.6
3.3
13.4
4.2
16.9
1
1
1
1
1
1
1
0.4
1.9
0.4
2.1
0.4
2.4
0.6
2.8
0.6
3.1
0.6
3.6
0.6
4.6
n.
1
1
1
1
1
1
2
m³/h
Pa
Pa
kW
A
6,500
50
737
0.6
4.3
7000
50
704
0.7
4.3
8,500
50
509
1.1
4.3
10000
50
480
1.2
4.9
11000
50
312
1.6
4.9
12000
50
112
2.1
4.9
16000
50
568
2
8.6
R410A
R410A
R410A
R410A
R410A
R410A
R410A
10.5
1
10.6
1
10.6
1
10.8
1
10.8
1
10.8
1
14.3
1
400/3/50
400/3/50
400/3/50
400/3/50
400/3/50
400/3/50
400/3/50
2.74
3.51
4.49
4.98
2.56
3.26
4.4
4.88
2.46
3.16
4.05
4.5
2.6
3.38
4.1
4.55
2.54
3.34
3.88
4.3
2.36
3.22
3.57
3.96
2.48
3.21
3.93
4.36
Average sound pressure level [Lpm] (4) dB(A)
70.6
72.1
76.3
75.6
77.6
79.4
77.6
Sound power level (Lw) (5) dB(A)
87.1
88.7
92.9
92.1
94.2
96
94.8
1/1
-1/1 LN
-130
1/1
-1/1 LN
-130
1/1
-1/1 LN
-130
1/1
-1/1 LN
-130
1/1
-1/1 LN
-130
2/1
-2/1 LN
-210
1250
890
1950
1250
890
1950
1250
890
1950
1250
890
1950
1250
890
1950
1250
890
1950
1800
1040
2000
kg
390
390
400
410
410
420
650
Ø
Ø mm
1 1/2"
--
1 1/2"
--
1 1/2"
--
1 1/2"
--
1 1/2"
--
1 1/2"
--
2"
--
Ø
Ø
1"
3/4"
1"
3/4"
1"
3/4"
1"
3/4"
1"
3/4"
1"
3/4"
1 1/4"
3/4"
Water volume l
Maximum water flow m³/h
PLUG FANS
Total air flow
External static pressure
MAX External static pressure
Absorbed power
Nominal operating current Compressors
REFRIGERANT
Total refrigerant load (excluding options) kg
Number of refrigerant circuits n.
SUPPLY VOLTAGE
ENERGY EFFICIENCY RATIOS (1)
V/Ph/Hz
EER kW/kW
COP kW/kW
ESEER = Eurovent standard
IPLV - ARI Standard 550/590
SOUND LEVELS
HYDRAULIC KIT
1 pump 2 poles
2 pumps 2 poles
1 pump 4 poles
2 pumps 4 poles
Water tank volume
PPF REV 1/1
PPF REV -PPF REV 1/1 LN
PPF REV -l
130
DIMENSIONS
Length mm
Width mm
Height mm
NET WEIGHT
HYDRAULIC CONNECTIONS
EVAPORATOR
Inlet outlet diameter – ISO 7/1 – R
Inlet outlet diameter
PARTIAL HEAT RECOVERY EXCHANGER
Inlet outlet diameter – ISO 7/1 – R
Condensate evacuation
(1) Gross value - chilled water temperature 12/7°C; outdoor temperature 35°C.
(2) Gross value - leaving hot water temperature 45°C; outdoor temperature 7°C.
(3) Gross value - chilled water temperature 12/7°C; outdoor temperature 35°C and hot
water temperature 40/45°C.
(4) Sound pressure level [Lpm] at 1m far according to ISO EN 3744
(5) Sound power level [Lw] according to ISO EN 9614-2.
61
➜
LIQUID CHILLERS | AIR-COOLED
EQUH PF 22 / 290 Reversible
TECHNICAL SPECIFICATIONS
SIZE
67.1
55.1
55.2
62.1
62.2
71.1
71.2
85.1
58.4
21.1
36.1
10
29
48.7
17.1
31.6
8.4
36
48.4
17.1
31.4
8.3
21
54.8
19.6
34.7
9.4
35
54.8
19.6
34.7
9.4
18
62
21.8
39.5
10.7
34
61.5
21.8
39.3
10.5
20
72.8
25.4
48.4
12.5
37
73.1
20
34.7
61.5
16.9
31.2
62
16.7
30.9
69.5
19.1
34
69.3
18.7
33.5
77.7
20.8
38.1
77.4
20.6
37.7
85.7
24.4
47.2
21.4
3.7
35.5
17.9
3.1
24.7
17.7
3.1
27.8
20.1
3.5
31.2
20.1
3.5
12
22.8
3.9
40
22.6
3.9
15.1
26.7
4.6
32.3
COOLING ONLY (1)
Cooling capacity
Compressors absorbed power
Nominal operating current Compressors
Evaporator water flow
Evaporator pressure loss
kW
kW
A
m³/h
kPa
WINTER HEATING MODE (2)
Heating capacity kW
Compressors absorbed power kW
Nominal operating current A
PARTIAL HEAT RECOVERY (3)
Heating capacity kW
Heat recovery exchanger water flow m³/h
Heat recovery pressure loss kPa
COMPRESSORS
Quantity
Maximum operating current
Starting current
Number of capacity steps
EVAPORATOR (brazed-plate)
n.
A
A
n.
n.
Water volume l
Maximum water flow m³/h
PARTIAL HEAT RECOVERY EXCHANGER
n.
Water volume l
Maximum water flow m³/h
PLUG FANS
Total air flow
External static pressure
MAX External static pressure
Absorbed power
Nominal operating current Compressors
scroll
scroll
scroll
scroll
scroll
scroll
scroll
2
44
140
2
2
44
140
2
2
50
143
2
2
50
143
2
2
62
171
2
2
62
171
2
2
68
208
2
1
1
1
1
1
1
1
1
5.7
21.4
4.2
17.6
4.3
17.6
4.8
19.9
5.3
20
5.5
22.7
5.6
22.7
6.3
27
1
1
2
1
2
1
2
1
0.8
5.8
0.8
4.8
0.7
4.8
0.8
5.4
1.1
5.4
0.8
6.2
1.2
6.2
1
7.3
n.
2
2
2
2
2
2
2
3
m³/h
Pa
Pa
kW
A
21000
50
363
2.3
8.4
18000
50
589
2
9.8
18000
50
589
2
9.8
20500
50
421
2.2
8.4
20500
50
421
2.2
8.4
23000
50
308
2.9
8.4
23000
50
308
2.9
8.4
25500
50
643
2.7
14.7
REFRIGERANT
Total refrigerant load (excluding options) kg
Number of refrigerant circuits n.
SUPPLY VOLTAGE
scroll
1
48.5
272
1
V/Ph/Hz
R410A
R410A
R410A
R410A
R410A
R410A
R410A
R410A
14.8
1
14.6
1
19.6
2
14.5
1
19.6
2
15
1
19.9
2
21.6
1
400/3/50 400/3/50 400/3/50 400/3/50 400/3/50 400/3/50 400/3/50 400/3/50
ENERGY EFFICIENCY RATIOS (1)
EER kW/kW
COP kW/kW
ESEER = Eurovent standard
IPLV - ARI Standard 550/590
2.5
3.28
3.56
4.02
2.55
3.25
3.92
4.35
2.53
3.31
4.31
4.78
2.52
3.27
3.93
4.36
2.52
3.32
3.73
4.14
2.51
3.28
4.04
4.48
2.49
3.29
3.71
4.11
2.59
3.17
4.41
4.89
79.5
96.7
75.9
93.1
75.9
93.1
69.6
86.8
69.6
86.8
72
89.2
72
89.2
76
93.9
2/1
-2/1 LN
-210
2/1
-2/1 LN
-210
2/1
-2/1 LN
-210
2/1
-2/1 LN
-210
2/1
-2/1 LN
-210
2/1
-2/1 LN
-210
3/1
3/2
3/1 LN
3/2 LN
360
1800
1040
2000
1800
1040
2000
1800
1040
2000
1800
1040
2000
1800
1040
2000
1800
1040
2000
1800
1040
2000
2600
1200
2000
kg
700
650
650
720
730
730
740
920
Ø
Ø mm
2"
--
2"
--
2"
--
2"
--
2"
--
2"
--
2"
--
-76.1
Ø
Ø
1 1/4"
3/4"
1 1/4"
3/4"
1 1/4"
3/4"
1 1/4"
3/4"
1 1/4"
3/4"
1 1/4"
3/4"
1 1/4"
3/4"
1 1/2"
2 x 3/4"
SOUND LEVELS
Average sound pressure level [Lpm] (4) dB(A)
Sound power level (Lw) (5) dB(A)
HYDRAULIC KIT
1 pump 2 poles
2 pumps 2 poles
1 pump 4 poles
2 pumps 4 poles
Water tank volume
PPF REV 2/1
PPF REV -PPF REV 2/1 LN
PPF REV -l
210
DIMENSIONS
Length mm
Width mm
Height mm
NET WEIGHT
HYDRAULIC CONNECTIONS
EVAPORATOR
Inlet outlet diameter – ISO 7/1 – R
Inlet outlet diameter
PARTIAL HEAT RECOVERY EXCHANGER
Inlet outlet diameter – ISO 7/1 – R
Condensate evacuation
(1) Gross value - chilled water temperature 12/7°C; outdoor temperature 35°C.
(2) Gross value - leaving hot water temperature 45°C; outdoor temperature 7°C.
(3) Gross value - chilled water temperature 12/7°C; outdoor temperature 35°C and hot water
temperature 40/45°C.
62
85.2
107.1
107.2
135.1
135.2
170.1
170.2
195.1
195.2
220.1
220.2
250.1
265.2
290.2
71.9
25.3
48.4
12.4
23
93.1
32.6
56.8
16
35
91
32.3
56.2
15.7
26
115
41.9
71.6
19.8
36
112
41.7
71.3
19.3
30
150
52.9
90.3
25.8
35
146
52.6
89.9
25.1
33
175
63.1
107
30.2
41
170
62.3
106
29.3
35
201
68
116
34.6
42
195
67.4
115
33.6
36
230
84.7
143
39.6
40
231
85.4
145
39.8
41
255
102
173
44
44
92.4
24.4
47.1
117
32
56.2
117
31.6
55.7
147
40.4
69.9
147
40.1
69.6
189
51.4
88.5
189
51.4
88.3
211
57.6
99.8
198
56.7
98.1
241
64.2
111
241
63.7
110
273
75.9
131
291
79.4
138
324
90.7
157
26.4
4.6
20.7
34.2
5.9
30.8
33.4
5.8
33.1
42.3
7.3
32.8
41.1
7.1
32.7
55
9.5
42.6
53.5
9.2
31.9
64.4
11.1
34.4
62.5
10.8
25.8
73.9
12.7
45.3
71.7
12.4
34
84.5
14.6
42.2
84.9
14.6
32.9
93.6
16.1
40
scroll
scroll
scroll
scroll
scroll
scroll
scroll
scroll
scroll
scroll
scroll
scroll
scroll
scroll
2
68
208
2
2
80
265
2
2
80
265
2
2
97
320.5
2
2
97
320.5
2
2
130.8
375.4
2
2
130.8
375.4
2
2
147.4
439.4
2
2
147.4
439.4
2
2
164
456
2
2
164
456
2
3
196.2
440.8
3
4
194
417.5
4
4
294.8
586.8
4
1
1
1
1
1
1
1
1
1
1
1
1
1
1
5.9
27
8.4
34.1
7.5
33.8
10.5
42.4
8.8
41.9
14.7
55
11.4
54.2
14
60.9
17.2
61.9
16
70
19.6
71.1
18.8
79.6
22
84.6
23.6
92.6
2
1
2
1
2
1
2
1
2
1
2
1
2
2
1.2
7.3
1.7
9.3
1.2
9.2
2.1
11.5
1.5
11.4
4
14.9
2
14.7
5.3
16.5
3.4
16.8
5.3
19
3.4
19.3
6.3
21.6
4.2
23
4.2
25.1
3
3
3
4
4
4
4
4
4
5
5
5
5
5
25500
50
643
2.7
14.7
32000
50
324
5
14.7
32000
50
324
5
14.7
40000
50
467
3.6
16.8
40000
50
467
3.6
16.8
52000
50
175
7.6
16.8
52000
50
175
7.6
16.8
54000
50
120
8.5
16.8
54000
50
120
8.5
16.8
62500
50
243
8.2
21
62500
50
243
8.2
21
64000
50
212
8.8
21
66000
50
147
10.1
21
66000
50
147
10.1
21
R410A
R410A
R410A
R410A
R410A
R410A
R410A
R410A
R410A
R410A
R410A
R410A
R410A
R410A
24
2
30.1
1
33.1
2
33.2
1
36.4
2
37.7
1
40.4
2
38.8
1
41.8
2
78.8
1
95.6
2
79.5
1
106.8
2
106.7
2
400/3/50 400/3/50 400/3/50 400/3/50 400/3/50 400/3/50 400/3/50 400/3/50 400/3/50 400/3/50 400/3/50 400/3/50 400/3/50 400/3/50
2.57
3.41
3.95
4.38
2.48
3.17
3.89
4.31
2.44
3.2
3.56
3.95
2.53
3.34
4.45
4.93
2.47
3.36
3.94
4.37
2.48
3.2
3.91
4.33
2.42
3.2
3.58
3.97
2.45
3.19
3.79
4.2
2.4
3.04
3.49
3.87
2.64
3.33
4.13
4.58
2.58
3.35
3.81
4.23
2.46
3.22
4.31
4.78
2.42
3.25
3.68
4.08
2.27
3.21
3.55
3.94
76
93.9
80.8
98.7
80.8
98.7
74
92.6
74
92.6
77.3
95.9
77.3
95.9
78
96.6
78
96.6
77.3
96.6
77.3
96.6
77.7
96.9
78.1
97.4
78.1
97.4
3/1
3/2
3/1 LN
3/2 LN
360
3/1
3/2
3/1 LN
3/2 LN
360
3/1
3/2
3/1 LN
3/2 LN
360
4/1
4/2
4/1 LN
4/2 LN
520
4/1
4/2
4/1 LN
4/2 LN
520
4/1
4/2
4/1 LN
4/2 LN
520
4/1
4/2
4/1 LN
4/2 LN
520
4/1
4/2
4/1 LN
4/2 LN
520
4/1
4/2
4/1 LN
4/2 LN
520
5/1
5/2
5/1 LN
5/2 LN
720
5/1
5/2
5/1 LN
5/2 LN
720
5/1
5/2
5/1 LN
5/2 LN
720
5/1
5/2
5/1 LN
5/2 LN
720
5/1
5/2
5/1 LN
5/2 LN
720
2600
1200
2000
2600
1200
2000
2600
1200
2000
3700
1260
2000
3700
1260
2000
3700
1260
2000
3700
1260
2000
3700
1260
2000
3700
1260
2000
4950
1260
2040
4950
1260
2040
4950
1260
2040
4950
1260
2040
4950
1260
2040
930
1120
1120
1510
1500
1600
1590
1650
1640
2050
2040
2220
2380
2430
-76.1
-76.1
-76.1
-88.9
-88.9
-88.9
-88.9
-88.9
-88.9
-88.9
-88.9
-88.9
-88.9
-88.9
1 1/2"
2 x 3/4"
1 1/2"
2 x 3/4"
1 1/2"
2 x 3/4"
2"
2 x 3/4"
2"
2 x 3/4"
2"
2 x 3/4"
2"
2 x 3/4"
2"
2 x 3/4"
2"
2 x 3/4"
2"
2 x 3/4"
2"
2 x 3/4"
2"
2 x 3/4"
2"
2 x 3/4"
2"
2 x 3/4"
(4) Sound pressure level [Lpm] at 1m far according to ISO EN 3744
(5) Sound power level [Lw] according to ISO EN 9614-2.
63
LIQUID CHILLERS | AIR-COOLED. FREE COOLING
EQMF
21 / 260
Cooling only
Free cooling
SCROLL COMPRESSORS
Cooling capacities from 20 to 260 kW
29 sizes
Refrigerant: R410A
EER up to 3.02
ESEER up to 4.67
ESPECIALLY FOR
SETUP IN DIFFICULT
LOCATIONS
MAIN FEATURES
AVAILABLE VERSIONS
Partial heat recovery version
ELN extra low sound level version
Brine low and very low temperature versions
All-year-round operation as a standard feature
(-10°C)
For external static pressure see PF version
Main Characteristics
Free cooling = 'free' energy recovery
Possible installation in corners, against walls
Mono or twin circuit units
High ESEER
Easy access to components
Large choice of sound levels
Electronic expansion valve from size 98
Remote demand limit via additional electronic board
Analog setpoint compensation
Easy maintenance
Service valves on liquid and discharge lines
Water tank (optional) under the unit, optimised footprint
and better mass distribution
Free cooling coil with 3-way valve and ambient air control.
Management by integrated unit control
Main accessories and options
Code
118
119
150
151
170
172
175
251
351
450
605
650
731
739
740
768
919
923
926
931
932
934
942
943
Kit A leaving chilled water low temperature operation
Kit B leaving chilled water low temperature operation
Kit LNO low sound level
Kit ELN extra low sound level
Antivibration mounts - spring - supplied loose
Antivibration mounts - rubber - supplied loose
Victaulic connections
Coil protection kit
Coils with pre-painted fins
Desuperheater
Power factor capacitor for cos phi 0.9 on compressor motor
Compressor thermal relays
Water flow switch
1 pump hydraulic kit
2 pump hydraulic kit
Water tank
Clock card
COM MBUS/JBUS serial card
LON serial card
BACnet Ethernet - SNMP - TCP/IP serial card
BACnet MS/TP serial card
MP.COM extension card
Serial card for GSM modem
Data logger
Besides these options, please speak to our Sales Department for any other
configuration or function that is not listed as being available.
(°C) 35
30
25
Water outlet temperature
from the chiller
FREE COOLING
Available with single or double refrigeration circuit(s)
1 or 2 SCROLL compressors mounted on
antivibration mounts
Condenser on one face only
Possible installation in difficult locations
Free-cooling operating limits
Indicative values. The operating T° are influenced by
a series of settings such as: operating conditions,
thermal load, adjustments, etc... Data to be confirmed
upon selection.
20
15
10
5
0
-5
-10
-15
-20
-15
-10
-5
0
5
10
15
Outdoor air temperature
64
20
25
30 (°C)
EQMF 21 / 260 Cooling only
TECHNICAL SPECIFICATIONS
SIZE
21.1
24.1
28.1
30.1
34.1
18.9
21.3
25.2
27.7
33.3
6.2
7.3
8.4
9.9
10.4
11.3
13.5
15.6
17.6
19
3.5
3.9
4.6
5.1
6.1
62
77
92
89
87
Cooling capacity kW
18.4
19.4
23.5
24.4
31.6
Heating capacity kW
7
7.8
9.2
10.2
12.2
1.2
1.4
1.6
1.8
2.1
17
21.6
30.1
12.3
17.7
scroll
scroll
scroll
scroll
scroll
1
1
1
1
1
Maximum operating current A
16
21
22
25
31
Starting current A
95
111
118
118
140
1
1
1
1
1
1
1
1
1
1
18
18
18
18.7
27.1
4.7
5.3
6.3
6.9
8.3
1
1
1
1
1
0.4
0.4
0.4
0.6
0.6
1.7
2
2.3
2.6
3.1
1
1
1
1
2
7500
7500
9650
9650
12000
0.5
0.5
0.8
0.8
0.6
1.5
1.5
1.6
1.6
3
R410A
R410A
R410A
R410A
R410A
11.3
11.3
11.3
11.5
13.7
1
1
1
1
1
400/3/50
400/3/50
400/3/50
400/3/50
400/3/50
COOLING ONLY (1)
Cooling capacity kW
Compressors absorbed power kW
Nominal operating current Compressors A
Evaporator water flow m³/h
Evaporator pressure loss kPa
FREE COOLING (2)
PARTIAL HEAT RECOVERY (3)
Heat recovery exchanger water flow m³/h
Press loss partial heat recovery exchanger kPa
COMPRESSORS
Quantity n.
Number of capacity steps n.
EVAPORATOR (brazed-plate)
n.
Water volume l
Maximum water flow m³/h
PARTIAL HEAT RECOVERY EXCHANGER
n.
Water volume l
Maximum water flow m³/h
AXIAL FANS (AC)
n.
Total air flow m³/h
Absorbed power kW
Nominal operating current Fans A
REFRIGERANT
Total refrigerant load (excluding options) kg
Number of refrigerant circuits n.
SUPPLY VOLTAGE
V/Ph/Hz
ENERGY EFFICIENCY RATIOS (1)
2.84
2.75
2.73
2.58
3.02
IPLV - ARI Standard 550/590
EER kW/kW
4.79
4.76
4.53
4.38
5.18
ESEER = Eurovent standard
4.32
4.29
4.09
3.95
4.67
Average sound pressure level [Lpm] (4) dB(A)
64.2
64.6
66
65.2
66.4
Sound power level (Lw) (5) dB(A)
80.8
81.2
82.6
81.8
83.6
SOUND LEVELS
HYDRAULIC KIT
1 pump 2 poles PPF MAX
1/1
1/1
1/1
1/1
2/1
-
-
-
-
-
130
130
130
130
210
Length mm
1250
1250
1250
1250
1800
Width mm
1010
1010
1010
1010
1180
Height mm
2010
2010
2010
2010
2060
430
440
440
440
600
1 1/2"
1 1/2"
1 1/2"
1 1/2"
2"
-
-
-
-
-
1"
1"
1"
1"
1 1/4"
2 pumps 2 poles PPF MAX
Water tank volume l
DIMENSIONS
NET WEIGHT
kg
HYDRAULIC CONNECTIONS
EVAPORATOR
Inlet outlet diameter – ISO 7/1 – R Ø
Inlet outlet – Flexible joint - OD Ø mm
PARTIAL HEAT RECOVERY EXCHANGER
Inlet outlet diameter – ISO 7/1 – R Ø
➜
(1) Gross value - chilled water temperature 12/7°C; outdoor temperature 35°C;
20% ethylene glycol solution.
(2) G
ross value - water inlet temperature 15°C; 20% ethylene glycol solution;
outdoor temperature 3°C.
(3) Gross value - chilled water temperature 12/7°C; outdoor temperature 35°C
and hot water temperature 40/45°C.
(4) Sound pressure level [Lpm] at 1m far according to ISO EN 3744
(5) Sound power level [Lw] according to ISO EN 9614-2.
65
LIQUID CHILLERS | AIR-COOLED. FREE COOLING
EQMF 21 / 260 Cooling only
TECHNICAL SPECIFICATIONS
SIZE
40.1
50.1
52.1
52.2
Cooling capacity kW
37.5
46
47.8
47.7
Compressors absorbed power kW
12.4
16.3
17.2
17.3
23.9
28.5
31.9
31.9
6.9
8.5
8.8
8.8
96
94
100
80
Cooling capacity kW
35.7
42.6
43.1
43.1
Heating capacity kW
13.8
16.9
17.5
17.5
2.4
2.9
3
3
22.5
33.9
23.8
23.6
scroll
scroll
scroll
scroll
1
1
2
2
34
40
44
44
174
225
140
140
1
1
2
2
1
1
1
1
27.1
27.8
28.8
28.4
9.4
11.4
11.9
11.9
1
1
1
2
0.6
0.6
0.8
0.8
3.4
4.2
4.4
4.4
2
2
2
2
14000
17300
17300
17300
1
1.7
1.7
1.7
3
3.2
3.2
3.2
R410A
R410A
R410A
R410A
13.7
15
15.3
16
1
1
1
2
400/3/50
400/3/50
400/3/50
400/3/50
COOLING ONLY (1)
Nominal operating current Compressors A
Evaporator water flow m³/h
Evaporator pressure loss kPa
FREE COOLING (2)
PARTIAL HEAT RECOVERY (3)
Heat recovery exchanger water flow m³/h
Press loss partial heat recovery exchanger kPa
COMPRESSORS
Quantity n.
Maximum operating current A
Starting current A
Number of capacity steps n.
EVAPORATOR (brazed-plate)
n.
Water volume l
Maximum water flow m³/h
PARTIAL HEAT RECOVERY EXCHANGER
n.
Water volume l
Maximum water flow m³/h
AXIAL FANS (AC)
n.
Total air flow m³/h
Absorbed power kW
Nominal operating current Fans A
REFRIGERANT
Total refrigerant load (excluding options) kg
Number of refrigerant circuits n.
SUPPLY VOLTAGE
V/Ph/Hz
ENERGY EFFICIENCY RATIOS (1)
2.8
2.56
2.54
2.52
IPLV - ARI Standard 550/590
EER kW/kW
4.63
4.16
4.41
3.97
ESEER = Eurovent standard
4.18
3.75
3.98
3.58
SOUND LEVELS
Average sound pressure level [Lpm] (4) dB(A)
69.4
72.5
70
70
Sound power level (Lw) (5) dB(A)
86.6
89.8
87.2
87.2
HYDRAULIC KIT
1 pump 2 poles PPF MAX
2 pumps 2 poles PPF MAX
Water tank volume l
2/1
2/1
2/1
2/1
-
-
-
-
210
210
210
210
DIMENSIONS
NET WEIGHT
Length mm
1800
1800
1800
1800
Width mm
1180
1180
1180
1180
Height mm
2060
2060
2060
2060
600
740
700
700
2"
2"
2"
2"
-
-
-
-
1 1/4"
1 1/4"
1 1/4"
1 1/4"
kg
HYDRAULIC CONNECTIONS
EVAPORATOR
Inlet outlet diameter – ISO 7/1 – R Ø
Inlet outlet – Flexible joint - OD Ø mm
PARTIAL HEAT RECOVERY EXCHANGER
Inlet outlet diameter – ISO 7/1 – R Ø
(1) Gross value - chilled water temperature 12/7°C; outdoor temperature 35°C; 20%
ethylene glycol solution.
(2) Gross value - water inlet temperature 15°C; 20% ethylene glycol solution; outdoor
temperature 3°C.
(3) Gross value - chilled water temperature 12/7°C; outdoor temperature 35°C and hot water
temperature 40/45°C.
(4) Sound pressure level [Lpm] at 1m far according to ISO EN 3744
(5) Sound power level [Lw] according to ISO EN 9614-2.
66
58.1
58.2
62.1
65.1
65.2
76.1
76.2
98.1
55.6
55.8
59.1
62.6
62.4
71.7
71.3
92.7
18.7
18.7
20.2
21
20.9
25.4
25.4
32.1
33.6
33.4
35.1
38.2
38.1
48.7
48.6
56.3
10.2
10.3
10.9
11.5
11.5
13.2
13.1
17
91
68
89
101
81
99
79
79
53.9
53.9
56.3
58.8
58.7
65.1
65
82.8
20.4
20.5
21.7
23
22.9
26.3
26.2
34
3.5
3.5
3.7
4
3.9
4.5
4.5
5.9
36.8
32.3
14
40.7
15.5
31.3
20.3
30.6
scroll
scroll
scroll
scroll
scroll
scroll
scroll
scroll
2
2
1
2
2
2
2
2
50
50
48.5
62
62
68
68
80
143
143
272
171
171
208
208
265
2
2
1
2
2
2
2
2
1
1
1
1
1
1
1
1
42.2
41.9
42
43.2
42.6
44.5
43.7
62
13.9
14
14.8
15.6
15.6
17.9
17.9
23.2
1
2
1
1
2
1
2
1
0.8
1.2
0.8
0.8
1.2
1
1.2
1.7
5.1
5.1
5.4
5.8
5.8
6.6
6.6
8.6
3
3
3
3
3
3
3
4
21000
21000
22000
23000
23000
25750
25750
35000
1.5
1.5
1.7
2
2
2.5
2.5
2.7
4.5
4.5
4.5
4.5
4.5
4.8
4.8
6.4
R410A
R410A
R410A
R410A
R410A
R410A
R410A
R410A
21.7
19.3
18.9
22.1
19.6
28.6
25.5
33.9
1
2
1
1
2
1
2
1
400/3/50
400/3/50
400/3/50
400/3/50
400/3/50
400/3/50
400/3/50
400/3/50
2.75
2.76
2.7
2.73
2.73
2.57
2.56
2.66
4.91
4.41
4.45
4.62
4.18
4.35
3.88
4.6
4.42
3.98
4.01
4.17
3.77
3.92
3.5
4.14
70.3
70.3
75.1
70.2
70.2
69.4
69.4
68.4
88.2
88.2
93
88.1
88.1
87.3
87.3
87
3/1
3/1
3/1
3/1
3/1
3/1
3/1
4/1
3/2
3/2
3/2
3/2
3/2
3/2
3/2
4/2
360
360
360
360
360
360
360
520
2600
2600
2600
2600
2600
2600
2600
3700
1340
1340
1340
1340
1340
1340
1340
1490
2060
2060
2060
2060
2060
2060
2060
2050
930
920
970
940
930
1000
1000
1470
-
-
-
-
-
-
-
-
76.1
76.1
76.1
76.1
76.1
76.1
76.1
88.9
1 1/2"
1 1/2"
1 1/2"
1 1/2"
1 1/2"
1 1/2"
1 1/2"
2"
➜
67
LIQUID CHILLERS | AIR-COOLED. FREE COOLING
EQMF 21 / 260 Cooling only
TECHNICAL SPECIFICATIONS
SIZE
98.2
124.1
124.2
158.1
Cooling capacity kW
91.5
114
112
147
Compressors absorbed power kW
31.9
41.4
41.4
54.6
56
71.3
71.3
92.9
16.8
21
20.6
27
66
74
64
80
Cooling capacity kW
82.3
98.1
97.5
113
Heating capacity kW
33.6
41.9
41.2
53.9
5.8
7.2
7.1
9.3
33.5
32.2
32.7
41
scroll
scroll
scroll
scroll
2
2
2
2
80
97
97
130.8
265
320.5
320.5
375.4
2
2
2
2
1
1
1
1
63.1
63.7
63.1
65.5
23
28.6
28.2
36.7
2
1
2
1
1.2
2.1
1.6
4
8.5
10.5
10.4
13.5
4
4
4
4
35000
42000
42000
46800
2.7
4.7
4.7
7.1
6.4
11.4
11.4
11.4
R410A
R410A
R410A
R410A
31.3
38.6
42.1
50.9
2
1
2
1
400/3/50
400/3/50
400/3/50
400/3/50
COOLING ONLY (1)
Nominal operating current Compressors A
Evaporator water flow m³/h
Evaporator pressure loss kPa
FREE COOLING (2)
PARTIAL HEAT RECOVERY (3)
Heat recovery exchanger water flow m³/h
Press loss partial heat recovery exchanger kPa
COMPRESSORS
Quantity n.
Maximum operating current A
Starting current A
Number of capacity steps n.
EVAPORATOR (brazed-plate)
n.
Water volume l
Maximum water flow m³/h
PARTIAL HEAT RECOVERY EXCHANGER
n.
Water volume l
Maximum water flow m³/h
AXIAL FANS (AC)
n.
Total air flow m³/h
Absorbed power kW
Nominal operating current Fans A
REFRIGERANT
Total refrigerant load (excluding options) kg
Number of refrigerant circuits n.
SUPPLY VOLTAGE
V/Ph/Hz
ENERGY EFFICIENCY RATIOS (1)
2.64
2.47
2.43
2.38
IPLV - ARI Standard 550/590
EER kW/kW
4.11
4.07
3.66
3.84
ESEER = Eurovent standard
3.71
3.67
3.3
3.46
SOUND LEVELS
Average sound pressure level [Lpm] (4) dB(A)
Sound power level (Lw) (5) dB(A)
68.4
72.3
72.3
74.4
87
90.9
90.9
93
HYDRAULIC KIT
1 pump 2 poles PPF MAX
4/1
4/1
4/1
4/1
2 pumps 2 poles PPF MAX
4/2
4/2
4/2
4/2
520
520
520
520
Water tank volume l
DIMENSIONS
NET WEIGHT
Length mm
3700
3700
3700
3700
Width mm
1490
1490
1490
1490
Height mm
2050
2050
2050
2050
kg
1470
1610
1610
1660
-
-
-
-
88.9
88.9
88.9
88.9
2"
2"
2"
2"
HYDRAULIC CONNECTIONS
EVAPORATOR
Inlet outlet diameter – ISO 7/1 – R Ø
Inlet outlet – Flexible joint - OD Ø mm
PARTIAL HEAT RECOVERY EXCHANGER
Inlet outlet diameter – ISO 7/1 – R Ø
(1) Gross value - chilled water temperature 12/7°C; outdoor temperature 35°C; 20%
ethylene glycol solution.
(2) Gross value - water inlet temperature 15°C; 20% ethylene glycol solution; outdoor
temperature 3°C.
(3) Gross value - chilled water temperature 12/7°C; outdoor temperature 35°C and hot water
temperature 40/45°C.
(4) Sound pressure level [Lpm] at 1m far according to ISO EN 3744
(5) Sound power level [Lw] according to ISO EN 9614-2.
68
158.2
180.1
180.2
197.1
197.2
230.1
240.2
260.2
149
169
170
186
183
209
231
258
54.8
60.4
60.5
69.1
69.5
85.6
83.2
99
93.4
103
104
118
117
145
143
168
27.3
31
31.1
34.1
33.7
38.5
42.5
47.5
72
65
68
89
81
97
95
100
113
131
132
145
145
153
165
190
54.5
61.9
62.3
68.1
67.2
76.6
84.9
94.6
9.4
10.7
10.7
11.7
11.6
13.2
14.6
16.3
33.2
31.8
25.6
38.5
29.8
34.7
32.9
40.9
scroll
scroll
scroll
scroll
scroll
scroll
scroll
scroll
2
2
2
2
2
3
4
4
130.8
147.4
147.4
164
164
196.2
194
227.8
375.4
459.4
459.4
476
476
440.8
417.5
472.4
2
2
2
2
2
3
4
4
1
1
1
1
1
1
1
1
65
116.2
114.2
124
121.8
104.8
161.2
161.2
37.2
42.2
42.4
45.6
46.3
51.9
54.5
54.5
2
1
2
1
2
1
2
2
2
5.3
4.2
5.3
4.2
6.3
4.2
4.2
13.7
15.5
15.6
16.8
17
19.1
20
20
4
5
5
5
5
5
5
5
46800
53000
53000
54000
54000
56300
69000
69000
7.1
6.8
6.8
7.2
7.2
8.2
9.1
9.1
11.4
14.3
14.3
14.3
14.3
14.3
14.3
14.3
R410A
R410A
R410A
R410A
R410A
R410A
R410A
R410A
42.9
73.7
65.8
83.1
102.2
83.7
127
126.6
2
1
2
1
2
1
2
2
400/3/50
400/3/50
400/3/50
400/3/50
400/3/50
400/3/50
400/3/50
400/3/50
2.41
2.51
2.53
2.44
2.39
2.23
2.5
2.39
3.53
4.15
3.75
3.99
3.6
4.15
3.79
3.72
3.18
3.74
3.38
3.6
3.25
3.74
3.4
3.34
74.4
74.1
74.1
74.4
74.4
75.4
74.1
74.1
93
93.3
93.3
93.7
93.7
94.7
93.4
93.4
5/1
5/1
5/1
5/1
5/1
5/1
5/1
5/1
5/2
5/2
5/2
5/2
5/2
5/2
5/2
5/2
520
720
720
720
720
720
720
720
3700
4950
4950
4950
4950
4950
4950
4950
1490
1500
1500
1500
1500
1500
1500
1500
2050
2090
2090
2090
2090
2090
2090
2090
1640
2240
2210
2220
2230
2370
2510
2510
-
-
-
-
-
-
-
-
88.9
88.9
88.9
88.9
88.9
88.9
88.9
88.9
2"
2"
2"
2"
2"
2"
2"
2"
69
LIQUID CHILLERS | AIR-COOLED. FREE COOLING
EQMF PF
22 / 290
Cooling only
Free cooling
SCROLL COMPRESSORS
DUCTABLE FAN
Cooling capacities from 20 to 260 kW
29 sizes
Refrigerant: R410A
EER up to 3.26
ESEER up to 4.67
ESPECIALLY FOR
SETUP IN DIFFICULT
LOCATIONS
MAIN FEATURES
AVAILABLE VERSIONS
Partial heat recovery version
ELN extra low sound level version
Brine low and very low temperature versions
Main accessories and options
Code
118
119
150
160
170
172
175
251
351
450
460
605
731
739
740
756
757
768
822
919
923
926
931
932
934
942
943
Kit A leaving chilled water low temperature operation
Kit B leaving chilled water low temperature operation
Kit LNO low sound level
Discharge air plenum with sound attenuator
Antivibration mounts - spring - supplied loose
Antivibration mounts - rubber - supplied loose
Victaulic connections
Coil protection kit
Coils with pre-painted fins
Desuperheater
Outdoor installation kit
Power factor capacitor for cos phi 0.9 on compressor motor
Water flow switch
1 pump hydraulic kit
2 pump hydraulic kit
1 LN pump hydraulic kit
2 LN pump hydraulic kit
Water tank
Supply air plenum mounting kit
Clock card
COM MBUS/JBUS serial card
LON serial card
BACnet Ethernet - SNMP - TCP/IP serial card
BACnet MS/TP serial card
MP.COM extension card
Serial card for GSM modem
Data logger
Advantages
Free cooling = 'free' energy recovery
Ductable unit
Choice of vertical or horizontal air discharge
Installation inside buildings
Mono or twin circuit units
High performance
Easy access to components
Large choice of sound levels
Electronic expansion valve from size 98
EC fan motor as standard
Remote demand limit via additional electronic board
Analog setpoint compensation
Easy maintenance
Service valves on liquid and discharge lines
Water tank under the unit = reduced footprint and
distribution of mass (optional)
Free cooling coil with 3-way valve and ambient air control,
Management by integrated unit control
Free-cooling operating limits
Indicative values. The operating T° are influenced by
a series of settings such as: operating conditions,
thermal load, adjustments, etc... Data to be confirmed
upon selection.
(°C) 35
30
Water outlet temperature
from the chiller
FREE COOLING
Available with single or double refrigeration circuit(s)
1 or 2 SCROLL compressors mounted on
antivibration mounts
Condenser on one face only
Possible installation in difficult locations
External static pressure from 50 to 700 Pa
depending on model
Plug fan as standard
Photo with buffer tank under the unit
not included in standard version
25
20
15
10
5
0
-5
-10
-15
-20
-15
-10
-5
0
5
10
15
Outdoor air temperature
Besides these options, please speak to our Sales Department for any other
configuration or function that is not listed as being available.
70
20
25
30 (°C)
EQMF PF 22 / 290 Cooling only
TECHNICAL SPECIFICATIONS
SIZE
22.1
24.1
28.1
32.1
36.1
42.1
53.1
21.4
23.9
27.9
31.6
35.2
39.6
51.4
6.6
7.7
9
10.2
11.4
14
17.3
11.9
14.1
16.4
17.9
20.6
26.1
29.8
4
4.4
5.2
5.8
6.5
7.3
9.5
75
95
111
113
109
122
113
Cooling capacity kW
18.1
19.5
22.9
26
28.2
29.9
42.3
Heating capacity kW
7.4
8.2
9.6
10.9
12.1
13.6
17.7
1.3
1.4
1.7
1.9
2.1
2.4
3.1
19.1
23.8
32.5
14
17.4
22
37.1
COOLING ONLY (1)
Cooling capacity kW
Compressors absorbed power kW
Nominal operating current Compressors A
Evaporator water flow m³/h
Evaporator pressure loss kPa
Free cooling (2)
PARTIAL HEAT RECOVERY (3)
Heat recovery exchanger water flow m³/h
Heat recovery pressure loss kPa
COMPRESSORS
1
1
1
1
1
1
1
Maximum operating current A
Quantity n.
16
21
22
25
31
34
40
Starting current A
95
111
118
118
140
174
225
1
1
1
1
1
1
1
1
1
1
1
1
1
1
15
15
15.2
15.9
16
16.4
24.3
5.2
5.9
6.8
7.8
8.8
10.1
12.8
1
1
1
1
1
1
1
0.4
0.4
0.4
0.6
0.6
0.6
0.6
1.9
2.2
2.5
2.8
3.2
3.7
4.7
1
1
1
1
1
1
2
6,500
7000
8,500
10000
11000
11500
16000
50
50
50
50
50
50
50
MAX External static pressure Pa
710
673
464
418
237
134
511
Absorbed power kW
0.6
0.7
1.3
0.7
1.9
2.1
2.3
4.3
4.3
4.3
4.9
4.9
4.9
8.6
R410A
R410A
R410A
R410A
R410A
R410A
R410A
11.3
11.3
11.3
11.5
11.6
11.6
18
1
1
1
1
1
1
1
400/3/50
400/3/50
400/3/50
400/3/50
400/3/50
400/3/50
400/3/50
Number of capacity steps n.
EVAPORATOR (brazed-plate)
n.
Water volume
Evaporator + free cooling coil l
Maximum water flow m³/h
PARTIAL HEAT RECOVERY EXCHANGER
n.
Water volume l
Maximum water flow m³/h
PLUG FANS
n.
Total air flow m³/h
External static pressure Pa
Nominal operating current Compressors A
REFRIGERANT
Total refrigerant load (excluding options) kg
Number of refrigerant circuits n.
SUPPLY VOLTAGE
V/Ph/Hz
ENERGY EFFICIENCY RATIOS (1)
2.96
2.85
2.74
2.89
2.65
2.45
2.62
ESEER = Eurovent standard
EER kW/kW
4.39
4.31
3.94
4.63
3.68
3.45
3.77
IPLV - ARI Standard 550/590
4.87
4.78
4.37
5.13
4.09
3.83
4.19
Average sound pressure level [Lpm] (4) dB(A)
70.7
72.3
76.4
75.5
77.9
78.9
77.8
Sound power level (Lw) (5) dB(A)
87.3
88.9
93
92.1
94.5
95.5
95
1/1
1/1
1/1
1/1
1/1
2/1
-
-
-
-
-
-
130
130
130
130
130
130
210
Length mm
1250
1250
1250
1250
1250
1250
1800
Width mm
1010
1010
1010
1010
1010
1010
1180
Height mm
1950
1950
1950
1950
1950
1950
2000
450
460
460
470
470
480
750
1 1/2"
1 1/2"
1 1/2"
1 1/2"
1 1/2"
1 1/2"
2"
--
--
--
--
--
--
--
1"
1"
1"
1"
1"
1"
1 1/4"
SOUND LEVELS
HYDRAULIC KIT
1 pump 2 poles PPF UNI 1/1
2 pumps 2 poles PPF UNI Water tank volume l
DIMENSIONS
NET WEIGHT
kg
HYDRAULIC CONNECTIONS
EVAPORATOR
Inlet outlet diameter – ISO 7/1 – R Ø
Inlet outlet diameter Ø mm
PARTIAL HEAT RECOVERY EXCHANGER
Inlet outlet diameter – ISO 7/1 – R Ø
(1) Gross value - chilled water temperature 12/7°C; outdoor temperature 35°C; 20%
glycol.
(2) Gross value - air inlet to chiller temperature 15°C; 20% ethylene glycol, ambient
temperature 3°C.
(3) Gross value - chilled water temperature 12/7°C and hot water temperature 40/45°C.
(4) Sound pressure level [Lpm] at 1m far according to ISO EN 3744
(5) Sound power level [Lw] according to ISO EN 9614-2.
71
➜
LIQUID CHILLERS | AIR-COOLED. FREE COOLING
EQMF PF 22 / 290 Cooling only
TECHNICAL SPECIFICATIONS
SIZE
67.1
55.1
55.2
62.1
62.2
71.1
71.2
85.1
Cooling capacity kW
54.1
54.2
60.7
60.9
64.4
68.4
68.3
80.5
Compressors absorbed power kW
18.3
18.2
19.8
19.8
22
22.8
22.7
26.5
33.6
33.4
35.1
35.1
37.4
40.9
40.8
50.4
10
10
11.2
11.2
11.9
12.6
12.6
14.9
Evaporator pressure loss kPa
124
100
139
112
139
157
135
120
Cooling capacity kW
45.7
45.7
50.6
50.6
52.1
55.6
55.5
67.1
Heating capacity kW
18.6
18.6
20.9
21
22.2
23.5
23.5
27.7
3.2
3.2
3.6
3.6
3.8
4.1
4
4.8
26.7
30.6
33.7
13
37.9
42.8
16.4
34.7
2
2
2
2
1
2
2
2
44
44
50
50
48.5
62
62
68
140
140
143
143
272
171
171
208
COOLING ONLY (1)
Nominal operating current Compressors A
Evaporator water flow m³/h
Free cooling (2)
PARTIAL HEAT RECOVERY (3)
Heat recovery exchanger water flow m³/h
Heat recovery pressure loss kPa
COMPRESSORS
Quantity n.
Maximum operating current A
Starting current A
Number of capacity steps n.
EVAPORATOR (brazed-plate)
n.
2
2
2
2
1
2
2
2
1
1
1
1
1
1
1
1
24.3
24.4
24.9
25.4
25.8
25.6
25.7
37.6
13.3
13.3
15
15.1
16.2
17.2
17.1
20.4
1
2
1
2
1
1
2
1
0.8
0.7
0.8
1.1
0.8
0.8
1.2
1
Water volume
Evaporator + free cooling coil l
Maximum water flow m³/h
PARTIAL HEAT RECOVERY EXCHANGER
n.
Water volume l
Maximum water flow m³/h
4.9
4.9
5.5
5.5
5.9
6.3
6.3
7.5
2
2
2
2
2
2
2
3
18000
18000
20500
20500
21000
23000
23000
25500
50
50
50
50
50
50
50
50
MAX External static pressure Pa
516
516
324
324
263
188
188
580
Absorbed power kW
2.5
2.5
3
3
2.3
4.1
4.1
3.2
PLUG FANS
n.
Total air flow m³/h
External static pressure Pa
Nominal operating current Compressors A
REFRIGERANT
Total refrigerant load (excluding options) kg
Number of refrigerant circuits n.
SUPPLY VOLTAGE
9.8
9.8
8.4
8.4
8.4
8.4
8.4
14.7
R410A
R410A
R410A
R410A
R410A
R410A
R410A
R410A
18.3
16
18.3
16
18.5
18.7
16.2
28.7
1
2
1
2
1
1
2
1
V/Ph/Hz 400/3/50 400/3/50 400/3/50 400/3/50 400/3/50 400/3/50 400/3/50 400/3/50
ENERGY EFFICIENCY RATIOS (1)
2.6
2.62
2.67
2.67
2.65
2.55
2.55
ESEER = Eurovent standard
EER kW/kW
3.73
3.92
3.63
3.51
3.56
3.62
3.38
2.71
4.18
IPLV - ARI Standard 550/590
4.14
4.35
4.03
3.89
4.02
4.01
3.75
4.63
SOUND LEVELS
Average sound pressure level [Lpm] (4) dB(A)
76.4
76.4
70.3
70.3
80
72.6
72.6
76.5
Sound power level (Lw) (5) dB(A)
93.6
93.6
87.5
87.5
97.2
89.8
89.8
94.4
2/1
2/1
2/1
2/1
2/1
2/1
3/1
-
-
-
-
-
-
3/2
210
210
210
210
210
210
360
HYDRAULIC KIT
1 pump 2 poles PPF UNI 2/1
2 pumps 2 poles PPF UNI Water tank volume l
210
DIMENSIONS
Length mm
1800
1800
1800
1800
1800
1800
1800
2600
Width mm
1180
1180
1180
1180
1180
1180
1180
1340
Height mm
NET WEIGHT
kg
2000
2000
2000
2000
2000
2000
2000
2000
740
740
810
810
790
820
820
1050
2"
2"
2"
2"
2"
2"
2"
--
--
--
--
--
--
--
--
76.1
1 1/4"
1 1/4"
1 1/4"
1 1/4"
1 1/4"
1 1/4"
1 1/4"
1 1/2"
HYDRAULIC CONNECTIONS
EVAPORATOR
Inlet outlet diameter – ISO 7/1 – R Ø
Inlet outlet diameter Ø mm
PARTIAL HEAT RECOVERY EXCHANGER
Inlet outlet diameter – ISO 7/1 – R Ø
(1) Gross value - chilled water temperature 12/7°C; outdoor temperature 35°C; 20%
glycol.
(2) Gross value - air inlet to chiller temperature 15°C; 20% ethylene glycol, ambient
temperature 3°C.
72
85.2
107.1
107.2
135.1
135.2
170.1
170.2
195.1
195.2
220.1
220.2
250.1
265.2
290.2
80.1
103
102
128
126
166
164
182
185
210
214
240
253
277
26.5
34
33.9
43.6
43.6
55
55
55.4
65.9
69.8
70.1
87.2
90
108
50.1
58.9
58.5
74.4
73.7
94.6
93.3
111
111
119
119
147
152
180
14.8
19.1
18.9
23.5
23.2
30.6
30.2
33.6
34.2
38.8
39.4
44.4
46.7
51.3
98
155
139
88
77
107
101
123
117
112
106
124
131
148
67
81.1
80.9
99.5
99
124
123
127
127
163
163
171
173
176
27.6
35.6
35.2
43.9
43.2
57.2
56.3
62.6
63.7
72.3
73.5
82.7
87
95.4
4.8
6.1
6.1
7.6
7.4
9.9
9.7
10.8
11
12.5
12.7
14.2
15
16.4
22.5
33.5
36.7
35.4
36
46.1
35.4
32.6
26.8
43.4
35.7
40.4
34.5
41.6
2
2
2
2
2
2
2
2
2
2
2
3
4
4
68
80
80
97
97
130.8
130.8
147.4
147.4
164
164
196.2
194
294.8
208
265
265
320.5
320.5
375.4
375.4
439.4
439.4
456
456
440.8
417.5
586.8
2
2
2
2
2
2
2
2
2
2
2
3
4
4
1
1
1
1
1
1
1
1
1
1
1
1
1
1
37.2
39.7
38.8
56.4
54.7
60.6
57.3
59.9
63.1
81.6
85.2
84.4
87.6
89.2
20.4
25.8
25.5
32
31.6
41.5
40.9
46
46.8
53.6
52.8
60.2
63.9
70
2
1
2
1
2
1
2
1
2
1
2
1
2
2
1.2
1.7
1.2
2.1
1.5
4
2
5.3
3.4
5.3
4.2
6.3
4.2
4.2
7.5
9.5
9.4
11.8
11.6
15.2
15
16.8
17
19.4
19.7
22
23.3
25.5
3
3
3
4
4
4
4
4
4
5
5
5
5
5
25500
32000
32000
40000
40000
52000
52000
52000
52000
62500
62500
64000
64000
64000
50
50
50
50
50
50
50
50
50
50
50
50
50
50
580
224
224
396
396
55
55
55
55
108
108
71
50
50
3.2
6
6
4.8
4.8
10.2
10.2
11.3
11.3
11.7
11.7
12.5
13
13
14.7
14.7
14.7
16.8
16.8
16.8
16.8
16.8
16.8
21
21
21
21
21
R410A
R410A
R410A
R410A
R410A
R410A
R410A
R410A
R410A
R410A
R410A
R410A
R410A
R410A
25.5
32
29.3
35.1
38.6
50.9
42.6
51.9
44
83.1
102.2
83.7
113.3
113.2
2
1
2
1
2
1
2
1
2
1
2
1
2
2
400/3/50 400/3/50 400/3/50 400/3/50 400/3/50 400/3/50 400/3/50 400/3/50 400/3/50 400/3/50 400/3/50 400/3/50 400/3/50 400/3/50
2.7
2.57
2.55
2.64
2.6
2.55
2.51
2.73
2.4
2.58
2.62
2.41
2.46
2.29
3.79
3.62
3.36
4.14
3.73
3.54
3.29
3.39
3.18
3.7
3.47
3.85
3.36
3.26
4.2
4.01
3.73
4.6
4.14
3.92
3.65
3.76
3.53
4.1
3.85
4.27
3.73
3.62
76.5
81.3
81.3
74.1
74.1
77.6
77.6
77.6
77.6
77.6
77.6
77.9
78
78
94.4
99.2
99.2
92.7
92.7
96.2
96.2
96.2
96.2
96.8
96.8
97.2
97.3
97.3
3/1
3/1
3/1
4/1
4/1
4/1
4/1
4/1
4/1
5/1
5/1
5/1
5/1
5/1
3/2
3/2
3/2
4/2
4/2
4/2
4/2
4/2
4/2
5/2
5/2
5/2
5/2
5/2
360
360
360
520
520
520
520
520
520
720
720
720
720
720
2600
2600
2600
3700
3700
3700
3700
3700
3700
4950
4950
4950
4950
4950
1340
1340
1340
1490
1490
1490
1490
1490
1490
1500
1500
1500
1500
1500
2000
2000
2000
2000
2000
2000
2000
2000
2000
2040
2040
2040
2040
2040
1050
1240
1240
1690
1690
1800
1780
1850
1820
2320
2330
2490
2670
2720
--
--
--
--
--
--
--
--
--
--
--
--
--
--
76.1
76.1
76.1
88.9
88.9
88.9
88.9
88.9
88.9
88.9
88.9
88.9
88.9
88.9
1 1/2"
1 1/2"
1 1/2"
2"
2"
2"
2"
2"
2"
2"
2"
2"
2"
2"
(3) Gross value - chilled water temperature 12/7°C and hot water temperature 40/45°C.
(4) Sound pressure level [Lpm] at 1m far according to ISO EN 3744
(5) Sound power level [Lw] according to ISO EN 9614-2.
73
LIQUID CHILLERS | AIR-COOLED. FREE COOLING
EQEF
60 / 300
Cooling only
Free cooling
SCROLL COMPRESSORS
Cooling capacities from 64 to 313 kW
17 sizes
Refrigerant: R410A
EER up to 2.91
ESEER up to 4.76
MAIN FEATURES
FREE COOLING
Available with single or double refrigeration circuit(s)
2 SCROLL compressors mounted on
antivibration mounts
AVAILABLE VERSIONS
Partial heat recovery version
ELN extra low sound level version
Brine low and very low temperature version
Advantages
Free cooling = 'free' energy recovery
2 Scroll compressors per circuit for greater efficiency and
reliability
Electronic expansion valve as standard
Large choice of sound levels
Partial heat recovery
Service valves on liquid and discharge lines
Easy maintenance
Free cooling coil with 3-way valve and ambient air control,
Management by integrated unit control.
Main accessories and options
Code
118
119
150
151
170
172
251
450
605
731
739
740
919
923
926
931
932
942
943
Kit A leaving chilled water low temperature operation
Kit B leaving chilled water low temperature operation
Kit LNO low sound level
Kit ELN extra low sound level
Antivibration mounts - spring - supplied loose
Antivibration mounts - rubber - supplied loose
Coil protection kit
Desuperheater
Power factor capacitor for cos phi 0.9 on compressor motor
Water flow switch
1 pump hydraulic kit
2 pump hydraulic kit
Clock card
COM MBUS/JBUS serial card
LON serial card
BACnet Ethernet - SNMP - TCP/IP serial card
BACnet MS/TP serial card
Serial card for GSM modem
Data logger
Besides these options, please speak to our Sales Department for any other
configuration or function that is not listed as being available.
Operating limits
(to be confirmed following selection conditions)
COOLING MODE
Water leaving temperature (no glycol)
5 / 15ºC
Water leaving temperature (with glycol max 40%)
-10 / 5°C
Max outdoor air temperature
45°C
Min outdoor air temperature
-20°C
74
EQEF 60 / 300 Cooling only
TECHNICAL SPECIFICATIONS
SIZE
60.1
60.2
70.1
70.2
90.1
COOLING ONLY (1)
Cooling capacity kW
64
64
73.4
73.2
94.9
20.5
20.5
24.6
24.6
30.9
37.8
37.8
47.8
47.8
55
11.7
11.8
13.5
13.4
17.4
Evaporator pressure loss kPa
112
91
131
111
94
Cooling capacity kW
46.3
46.3
50.2
50.2
61.9
Heating capacity kW
23.5
--
26.9
--
34.8
4
--
4.6
--
6
--
--
--
--
--
scroll
scroll
scroll
scroll
scroll
2
2
2
2
2
62
62
68
68
80
171
171
207
207
265
2
2
2
2
2
1
1
1
1
1
22
22
22
22
33
17.4
17.5
20
20
25.9
1
--
1
--
1
0.8
--
1
--
1.7
5.6
--
6.4
--
8.4
6
6
6
6
2
30000
30000
33000
33000
44000
1.5
1.5
1.5
1.5
3.4
2.4
2.4
2.4
2.4
7.8
R410A
R410A
R410A
R410A
R410A
31.6
34.6
32
35.6
42
1
2
1
2
1
400/3/50
400/3/50
400/3/50
400/3/50
400/3/50
Compressors absorbed power kW
Nominal operating current Compressors A
Evaporator water flow m³/h
FREE COOLING (2)
PARTIAL HEAT RECOVERY (3)
Heat recovery exchanger water flow m³/h
Press loss partial heat recovery exchanger kPa
COMPRESSORS
Quantity n.
Maximum operating current A
Starting current A
Number of capacity steps n.
EVAPORATOR (brazed-plate)
n.
Water volume l
Maximum water flow m³/h
PARTIAL HEAT RECOVERY EXCHANGER
n.
Water volume l
Maximum water flow m³/h
AXIAL FANS (AC)
n.
Total air flow m³/h
Absorbed power kW
Nominal operating current Fans A
REFRIGERANT
Total refrigerant load (excluding options) kg
Number of refrigerant circuits n.
SUPPLY VOLTAGE
V/Ph/Hz
ENERGY EFFICIENCY RATIOS (1)
2.91
2.91
2.81
2.8
2.77
ESEER = Eurovent standard
EER kW/kW
4.76
4.57
4.61
4.27
4.61
IPLV = ARI Standard 550/590
5.26
5.13
5.12
4.89
5.07
Average sound pressure level [Lpm] (4) dB(A)
66.3
66.3
66.4
66.4
74.2
Sound power level (Lw) (5) dB(A)
83.3
83.3
83.8
83.8
92.3
SOUND LEVELS
HYDRAULIC KIT
1 pump 2 poles
1/1
1/1
2/1
2/1
2/1
2 pumps 2 poles
1/2
1/2
2/2
2/2
2/2
Length mm
Width mm
2580
1200
2580
1200
2580
1200
2580
1200
3020
1200
Height mm
1630
1630
1630
1630
1950
830
810
870
850
1170
2"
2"
2"
2"
--
--
--
--
--
76.1
1 1/2"
--
1 1/2"
--
1 1/2"
DIMENSIONS
NET WEIGHT
kg
HYDRAULIC CONNECTIONS
EVAPORATOR
Inlet outlet diameter – ISO 7/1 – R Ø
Inlet outlet – Flexible joint - OD Ø mm
PARTIAL HEAT RECOVERY EXCHANGER
Inlet outlet diameter – ISO 7/1 – R Ø
➜
(1) Gross value - chilled water temperature 12/7°C; outdoor temperature 35°C; 20%
ethylene glycol solution.
(2) G
ross value - water inlet temperature 15°C; 20% ethylene glycol solution; outdoor
temperature 3°C.
(3) Gross value - chilled water temperature 12/7°C; outdoor temperature 35°C and hot water
temperature 40/45°C.
(4) Sound pressure level [Lpm] at 1m far according to ISO EN 3744
(5) Sound power level [Lw] according to ISO EN 9614-2.
75
LIQUID CHILLERS | AIR-COOLED. FREE COOLING
EQEF 60 / 300 Cooling only
TECHNICAL SPECIFICATIONS
SIZE
90.2
120.1
120.2
135.1
150.1
Cooling capacity kW
93.8
116
114
130
154
Compressors absorbed power kW
30.8
40.7
40.5
47.6
50.9
54.9
70.7
70.5
81.8
88
17.2
21.3
21
23.9
28.3
78
114
103
133
111
Cooling capacity kW
61.6
69.3
68.9
71.9
106
Heating capacity kW
--
42.6
--
47.7
56.6
--
7.3
--
8.2
9.8
--
--
--
--
--
scroll
scroll
scroll
scroll
scroll
2
2
2
2
2
80
97
97
113.9
130.8
265
320.5
320.5
358.5
375.4
2
2
2
2
2
1
1
1
1
1
33
33
33
33
54
25.6
31.1
31.5
45
42.6
--
1
--
1
1
--
2.1
--
2.1
4
13.6
COOLING ONLY (1)
Nominal operating current Compressors A
Evaporator water flow m³/h
Evaporator pressure loss kPa
FREE COOLING (2)
PARTIAL HEAT RECOVERY (3)
Heat recovery exchanger water flow m³/h
Press loss partial heat recovery exchanger kPa
COMPRESSORS
Quantity n.
Maximum operating current A
Starting current A
Number of capacity steps n.
EVAPORATOR (brazed-plate)
n.
Water volume l
Maximum water flow m³/h
PARTIAL HEAT RECOVERY EXCHANGER
n.
Water volume l
Maximum water flow m³/h
AXIAL FANS (AC)
n.
Total air flow m³/h
Absorbed power kW
Nominal operating current Fans A
REFRIGERANT
Total refrigerant load (excluding options) kg
Number of refrigerant circuits n.
SUPPLY VOLTAGE
V/Ph/Hz
--
10.2
--
11.5
2
2
2
2
3
44000
48000
48000
50000
66000
3.4
3.4
3.4
3.4
5.1
7.8
7.8
7.8
7.8
11.7
R410A
R410A
R410A
R410A
R410A
40.8
42.9
41.4
43.6
62.6
2
1
2
1
1
400/3/50
400/3/50
400/3/50
400/3/50
400/3/50
2.75
ENERGY EFFICIENCY RATIOS (1)
2.74
2.63
2.6
2.55
ESEER = Eurovent standard
EER kW/kW
4.36
4.3
4.06
4.17
4.45
IPLV = ARI Standard 550/590
4.92
4.73
4.59
4.6
4.95
SOUND LEVELS
Average sound pressure level [Lpm] (4) dB(A)
74.2
74.4
74.4
75.4
76
Sound power level (Lw) (5) dB(A)
92.3
92.5
92.5
93.5
95.4
1 pump 2 poles
2/1
2/1
2/1
2/1
2/1
2 pumps 2 poles
2/2
2/2
2/2
2/2
2/2
Length mm
3020
3020
3020
3020
4400
Width mm
1200
1200
1200
1200
1800
Height mm
1950
1950
1950
1950
1990
kg
1150
1280
1270
1350
1560
HYDRAULIC KIT
DIMENSIONS
NET WEIGHT
HYDRAULIC CONNECTIONS
EVAPORATOR
Inlet outlet diameter – ISO 7/1 – R Ø
Inlet outlet – Flexible joint - OD Ø mm
--
--
--
--
--
76.1
76.1
76.1
76.1
88.9
--
1 1/2"
--
1 1/2"
2"
HEATING PARTIAL HEAT RECOVERY EXCHANGER
Inlet outlet diameter – ISO 7/1 – R Ø
(1) Gross value - chilled water temperature 12/7°C; outdoor temperature 35°C; 20%
ethylene glycol solution.
(2) Gross value - water inlet temperature 15°C; 20% ethylene glycol solution; outdoor
temperature 3°C.
(3) Gross value - chilled water temperature 12/7°C; outdoor temperature 35°C and hot water
temperature 40/45°C.
(4) Sound pressure level [Lpm] at 1m far according to ISO EN 3744
(5) Sound power level [Lw] according to ISO EN 9614-2.
76
150.2
190.2
200.1
200.2
240.2
270.2
300.2
157
186
187
192
227
269
313
51.1
66.1
68.3
68
85.2
93.3
106
88.3
116
116
115
146
161
182
28.8
34.1
34.3
35.2
41.8
49.4
57.5
101
89
116
113
120
140
172
106
115
116
117
129
172
192
57.4
68.1
68.6
70.4
83.5
98.6
115
9.9
11.7
11.8
12.1
14.4
17
19.8
--
--
--
--
--
--
--
scroll
scroll
scroll
scroll
scroll
scroll
scroll
2
4
2
2
4
4
4
130.8
160
164
164
194
227.8
261.6
375.4
345
466
466
417.5
472.4
506.2
2
4
2
2
4
4
4
1
1
1
1
1
1
1
54
68
54
54
68
84
84
42
50.9
51.6
50.7
61.7
72.8
81.3
2
2
1
2
2
2
2
2
3.4
5.3
3.4
4.2
4.2
16
13.7
16.2
16.4
16.8
20
23.7
27.4
3
3
3
4
4
6
6
66000
72000
72000
76000
88000
108000
126000
5.1
5.1
5.1
6.8
6.8
10.2
10.2
11.7
11.7
11.7
15.6
15.6
23.4
23.4
R410A
R410A
R410A
R410A
R410A
R410A
R410A
64.6
68.4
66.4
67
68
94.2
95.8
2
2
1
2
2
2
2
400/3/50
400/3/50
400/3/50
400/3/50
400/3/50
400/3/50
400/3/50
2.79
2.61
2.55
2.57
2.47
2.6
2.69
4.28
4.2
4
3.97
4.08
4.51
4.49
4.83
4.67
4.45
4.47
4.48
4.96
4.96
76
75.4
75.4
75.4
80.2
81.5
81.5
95.4
94.8
94.8
94.8
100
101.8
101.8
3/1
3/1
3/1
3/1
3/1
4/1
5/1
3/2
3/2
3/2
3/2
3/2
4/2
5/2
4400
3600
4400
4400
3600
4600
4600
1800
2290
1800
1800
2290
2290
2290
1990
2250
1990
1990
2250
2250
2250
1580
1840
1710
1730
1850
2260
2710
--
--
--
--
--
--
--
88.9
88.9
88.9
88.9
88.9
88.9
88.9
2" 2"
2"
2"
2"
2"
2"
77
LIQUID CHILLERS | AIR-COOLED. FREE COOLING
EQSFA
290 / 1450
Class A
Cooling only
Free cooling
SCREW COMPRESSORS
CLASS A
ooling capacities from 288 to 1445 kW
C
24 sizes
Refrigerant: R134a
EER up to 3.15
ESEER up to 3.77
Class A
MAIN FEATURES
REE COOLING
F
Available in 2 refrigeration circuits
2 SCREW compressors mounted on rubber
antivibration mounts
Modern design
Shell and tube evaporator
AVAILABLE VERSIONS
LS very low sound level version
X
EC motor version for avail. pressure
All-year-round free cooling operation down to - 20°C
Advantages
lass A = energy efficiency
C
Free cooling = 'free' energy recovery
Wide power range covered by SCREW technology
Electronic expansion valve as standard
Linear step capacity control
Dialogue interface with screen and graphical icons for
easier reading
Large choice of sound levels
Specific free cooling heat exchanger
Remote demand limit via additional electronic board
Analog setpoint compensation
Easy maintenance
Free cooling coil with 3-way valve and ambient air control,
Management by integrated unit control.
Main accessories and options
Code
101
143
170
171
175
351
605
650
731
739
740
769
770
919
923
926
931
932
934
942
943
EC fan motors
Without glycol
Antivibration mounts - spring - supplied loose
Antivibration mounts - rubber - supplied loose
Victaulic connections
Coils with pre-painted fins
Power factor capacitor for cos phi 0.9 on compressor motor
Compressor thermal relays
Water flow switch
1 pump hydraulic kit
2 pump hydraulic kit
1 pump + 1 standby pump hydraulic kit
2 pump + 1 standby pump hydraulic kit
Clock card
COM MBUS/JBUS serial card
LON serial card
BACnet Ethernet - SNMP - TCP/IP serial card
BACnet MS/TP serial card
MP.COM extension card
Serial card for GSM modem
Data logger
Besides these options, please speak to our Sales Department for any other
configuration or function that is not listed as being available.
(°C) 35
30
Water outlet temperature
from the chiller
25
Free-cooling operating limits
Indicative values. The operating T° are influenced by
a series of settings such as: operating conditions,
thermal load, adjustments, etc... Data to be confirmed
upon selection.
20
15
10
5
0
-5
-10
-15
-20
-20
-15
-10
-5
0
5
10
15
Outdoor air temperature
78
20
25
30 (°C)
EQSFA 290 / 1450 Cooling only
TECHNICAL SPECIFICATIONS
SIZE
290
310
330
360
380
288
305
329
352
373
79
85
90.2
96
102
135
143
152
160
161
51.6
54.6
58.9
63.1
66.8
28
24
26
29
25
312
16.9
244
316
18.9
244
386
27
324
422
30.5
332
426
30.2
332
57.3
60.7
65.4
70
74.2
9.9
10.5
11.3
12.1
12.8
5
5.2
5.4
5.2
5.6
twin-screw
twin-screw
twin-screw
twin-screw
twin-screw
COOLING ONLY (1)
Cooling capacity kW
Compressors absorbed power kW
Nominal operating current Compressors A
Evaporator water flow m³/h
Evaporator pressure loss kPa
FREE COOLING (2)
Cooling capacity kW
Pressure loss free-cooling coil kPa
Free cooling coil volume l
PARTIAL HEAT RECOVERY (3)
Heating capacity kW
Heat recovery exchanger water flow m³/h
Press loss partial heat recovery exchanger kPa
COMPRESSORS
2
2
2
2
2
Maximum operating current A
Quantity n.
163.4
179.2
190.5
201.8
205
Starting current A
350.7
356.6
392.6
403.9
382.5
25…100%
25…100%
25…100%
25…100%
25…100%
1
1
1
1
1
160
143
256
256
256
90
100
127
127
127
2
2
2
2
2
3.2
3.2
4.1
5
5
20
20
20
20
20
6
6
7
8
8
122376
119280
142772
163168
159040
12.4
12.5
14.4
16.5
16.7
23.4
23.4
27.3
31.2
31.2
R134a
R134a
R134a
R134a
R134a
110
146
145
145
194
2
2
2
2
2
400/3/50
400/3/50
400/3/50
400/3/50
400/3/50
3.15
3.13
3.14
3.13
3.14
3.59
3.53
3.57
3.56
3.55
Average sound pressure level [Lpm] (4) dB(A)
72.4
72.8
72.5
72.7
71.3
Sound power level (Lw) (5) dB(A)
92.1
92.5
92.7
92.9
91.5
GE65/1
GE65/1
GE65/1
GE65/1
GE65/1
--
--
--
--
--
1 operational pumps + 1 emergency pump GE
GE65/2
GE65/2
GE65/2
GE65/2
GE65/2
2 operational pumps + 1 emergency pump GE
--
--
--
--
--
3520
3520
4490
4490
4490
Number of capacity steps n.
EVAPORATOR (brazed-plate)
n.
Water volume
Maximum water flow m³/h
PARTIAL HEAT RECOVERY EXCHANGER
n.
Water volume l
Maximum water flow m³/h
AXIAL FANS (AC)
n.
Total air flow m³/h
Absorbed power kW
Nominal operating current Fans A
REFRIGERANT
Total refrigerant load (excluding options) kg
Number of refrigerant circuits n.
SUPPLY VOLTAGE
V/Ph/Hz
ENERGY EFFICIENCY RATIOS (1)
EER kW/kW
ESEER = Eurovent standard
SOUND LEVELS
HYDRAULIC KIT
1 pump 2 poles GE
2 pumps 2 poles GE
DIMENSIONS
Length mm
NET WEIGHT
Width mm
2260
2260
2260
2260
2260
Height mm
2550
2550
2550
2550
2550
kg
5330
5923
6633
6638
6857
168.3
168.3
168.3
168.3
168.3
2 x 2"
2 x 2"
2 x 2"
2 x 2"
2 x 2"
HYDRAULIC CONNECTIONS
EVAPORATOR
Inlet outlet diameter Ø mm
PARTIAL HEAT RECOVERY EXCHANGER
Inlet outlet diameter – ISO228/1-G M Ø
(1) G
ross value - chilled water temperature 12/7°C; outdoor temperature 35°C; 20%
ethylene glycol solution.
(2) G
ross value - water inlet temperature 15°C; 20% ethylene glycol solution; outdoor
temperature 3°C.
(3) Gross value - chilled water temperature 12/7°C; outdoor temperature 35°C
and hot water temperature 40/45°C.
(4) Sound pressure level [Lpm] at 1m far according to ISO EN 3744
(5) Sound power level [Lw] according to ISO EN 9614-2.
79
➜
LIQUID CHILLERS | AIR-COOLED. FREE COOLING
EQSFA 290 / 1450 Cooling only
TECHNICAL SPECIFICATIONS
SIZE
420
460
490
540
590
Cooling capacity kW
412
457
484
532
581
Compressors absorbed power kW
115
125
134
150
165
196
204
226
247
269
73.8
81.9
86.7
95.3
104
31
37
51
51
51
441
36.1
332
544
53.1
402
554
58.8
402
571
69.6
402
585
81.2
402
82
90.9
96.3
106
116
14.1
15.7
16.6
18.2
19.9
5.3
4.9
5.2
5.6
5.7
twin-screw
twin-screw
twin-screw
twin-screw
twin-screw
2
2
2
2
2
COOLING ONLY (1)
Nominal operating current Compressors A
Evaporator water flow m³/h
Evaporator pressure loss kPa
FREE COOLING (2)
Cooling capacity kW
Pressure loss free-cooling coil kPa
Free cooling coil volume l
PARTIAL HEAT RECOVERY (3)
Heating capacity kW
Heat recovery exchanger water flow m³/h
Press loss partial heat recovery exchanger kPa
COMPRESSORS
Quantity n.
Maximum operating current A
235.6
269.6
288.2
309.3
330.4
Starting current A
468.8
629.8
639.1
790.1
811.2
25…100%
25…100%
25…100%
25…100%
25…100%
1
1
1
1
1
247
247
247
223
223
143
143
143
172
172
2
2
2
2
2
5
5
6.8
6.8
6.8
20
20
30
30
30
8
10
10
10
10
159040
198800
198800
198800
198800
16.7
20.9
20.9
20.9
20.9
31.2
39
39
39
39
R134a
R134a
R134a
R134a
R134a
Number of capacity steps n.
EVAPORATOR (brazed-plate)
n.
Water volume
Maximum water flow m³/h
PARTIAL HEAT RECOVERY EXCHANGER
n.
Water volume l
Maximum water flow m³/h
AXIAL FANS (AC)
n.
Total air flow m³/h
Absorbed power kW
Nominal operating current Fans A
REFRIGERANT
Total refrigerant load (excluding options) kg
Number of refrigerant circuits n.
SUPPLY VOLTAGE
V/Ph/Hz
194
241
241
241
241
2
2
2
2
2
400/3/50
400/3/50
400/3/50
400/3/50
400/3/50
3.13
3.13
3.13
3.11
3.13
3.52
3.53
3.52
3.52
3.55
ENERGY EFFICIENCY RATIOS (1)
EER kW/kW
ESEER = Eurovent standard
SOUND LEVELS
Average sound pressure level [Lpm] (4) dB(A)
71.7
71.4
75.6
75.8
76
Sound power level (Lw) (5) dB(A)
91.9
92.1
96.2
96.5
96.7
GE65/1
GE65/1
GE65/1
GE65/1
GE65/1
--
--
--
--
--
1 operational pumps + 1 emergency pump GE
GE65/2
GE65/2
GE65/2
GE65/2
GE65/2
2 operational pumps + 1 emergency pump GE
--
--
--
--
--
HYDRAULIC KIT
1 pump 2 poles GE
2 pumps 2 poles GE
DIMENSIONS
NET WEIGHT
Length mm
4490
5484
5484
5484
5484
Width mm
2260
2260
2260
2260
2260
Height mm
2550
2550
2550
2550
2550
kg
6895
8018
8030
8182
8304
219.1
219.1
219.1
219.1
219.1
2 x 2"
2 x 2"
2 x 2"
2 x 2"
2 x 2"
HYDRAULIC CONNECTIONS
EVAPORATOR
Inlet outlet diameter Ø mm
PARTIAL HEAT RECOVERY EXCHANGER
Inlet outlet diameter – ISO228/1-G M Ø
(1) Gross value - chilled water temperature 12/7°C; outdoor temperature 35°C; 20%
ethylene glycol solution.
(2) Gross value - water inlet temperature 15°C; 20% ethylene glycol solution; outdoor
temperature 3°C.
(3) Gross value - chilled water temperature 12/7°C; outdoor temperature 35°C and hot water
temperature 40/45°C.
(4) Sound pressure level [Lpm] at 1m far according to ISO EN 3744
(5) Sound power level [Lw] according to ISO EN 9614-2.
80
630
680
720
790
860
910
960
1050
1110
629
670
715
786
859
905
951
1048
1108
176
189
200
221
242
257
272
303
318
291
309
324
332
339
383
426
483
500
113
120
128
141
154
162
170
188
199
62
66
70
54
61
66
70
46
51
637
19.3
482
715
24.6
562
754
26.6
562
846
33.2
648
895
38.8
648
909
42.5
648
923
46.4
648
947
55.1
648
1035
67.7
726
125
133
142
156
171
180
189
209
221
21.6
23
24.5
27
29.5
31
32.6
35.9
38
6
6.4
6.5
6.4
6.8
6.6
6.9
7
6.9
twin-screw
twin-screw
twin-screw
twin-screw
twin-screw
twin-screw
twin-screw
twin-screw
twin-screw
2
2
2
2
2
2
2
2
2
366.8
390.4
414
444.1
474.2
505
535.8
615.4
662.5
544.4
544.4
568
581
611.1
690.1
720.9
826.7
1010.7
25…100%
25…100%
25…100%
25…100%
25…100%
25…100%
25…100%
25…100%
25…100%
1
1
1
1
1
1
1
1
1
247
238
238
370
370
359
359
348
348
143
154
154
220
220
241
241
265
265
2
2
2
2
2
2
2
2
2
6.8
8.6
10.4
10.4
10.4
13.1
15.8
19.4
21.2
30
35
40
40
40
45
50
50
50
12
13
14
15
16
16
16
16
18
238560
261794
278320
302070
318080
318080
318080
318080
357840
25
27
29.2
31.1
33.4
33.4
33.4
33.4
37.6
46.8
50.7
54.6
58.5
62.4
62.4
62.4
62.4
70.2
R134a
R134a
R134a
R134a
R134a
R134a
R134a
R134a
R134a
289
295
337
340
389
389
389
389
436
2
2
2
2
2
2
2
2
2
400/3/50
400/3/50
400/3/50
400/3/50
400/3/50
400/3/50
400/3/50
400/3/50
400/3/50
3.13
3.1
3.12
3.12
3.12
3.12
3.11
3.12
3.12
3.68
3.58
3.59
3.55
3.57
3.52
3.56
3.76
3.72
76.7
77.9
79
79.3
79.9
79.8
79.6
78.1
79.5
97.7
99.3
100.4
101.1
101.7
101.6
101.4
99.9
101.7
GE65/1
GE65/1
GE65/1
--
--
--
--
--
--
--
--
--
GE65/11
GE65/11
GE65/11
GE65/11
GE65/11
GE65/11
GE65/2
GE65/2
GE65/2
--
--
--
--
--
--
--
--
--
GE65/21
GE65/21
GE65/21
GE65/21
GE65/21
GE65/21
6428
7398
7398
8767
8767
8767
8767
8767
9737
2260
2260
2260
2260
2260
2260
2260
2260
2260
2550
2550
2550
2550
2550
2550
2550
2550
2550
9086
9669
9872
11754
12233
12267
12277
12376
13934
219.1
219.1
219.1
219.1
219.1
273
273
273
273
2 x 2"
2 x 2"
2 x 2"
2 x 2"
2 x 2"
2 x 2"
2 x 2"
2 x 2"
2 x 2"
➜
81
LIQUID CHILLERS | AIR-COOLED. FREE COOLING
EQSFA 290 / 1450 Cooling only
TECHNICAL SPECIFICATIONS
SIZE
1170
1240
1310
1380
1450
1170
1239
1311
1377
1445
334
356
379
396
414
517
558
599
644
688
210
222
235
247
259
56
61
45
50
54
1174
91.8
804
1191
90.9
804
1208
100.1
804
1292
42
884
1339
23.8
964
233
247
261
274
288
40.1
42.5
44.9
47.2
49.5
6.8
6.5
7
6.9
7.1
twin-screw
twin-screw
twin-screw
twin-screw
twin-screw
2
2
2
2
2
709.6
753.6
797.6
846.8
896
1057.8
1137.8
1181.8
1274.8
1324
25…100%
25…100%
25…100%
25…100%
25…100%
1
1
1
1
1
348
620
620
620
620
265
385
385
385
385
2
2
2
2
2
23
25.7
28.4
32
35.6
50
60
60
60
60
20
20
20
22
24
397600
397600
397600
437360
477120
41.7
41.7
41.7
45.9
50.1
78
78
78
85.8
93.6
R134a
R134a
R134a
R134a
R134a
482
482
482
530
578
2
2
2
2
2
400/3/50
400/3/50
400/3/50
400/3/50
400/3/50
3.11
3.12
3.12
3.12
3.11
3.72
3.72
3.77
3.72
3.72
81.5
81.5
81.5
81.4
81.3
103.9
103.9
103.9
104.1
104.2
COOLING ONLY (1)
Cooling capacity kW
Compressors absorbed power kW
Nominal operating current Compressors A
Evaporator water flow m³/h
Evaporator pressure loss kPa
FREE COOLING (2)
Cooling capacity kW
Pressure loss free-cooling coil kPa
Free cooling coil volume l
PARTIAL HEAT RECOVERY (3)
Heating capacity kW
Heat recovery exchanger water flow m³/h
Press loss partial heat recovery exchanger kPa
COMPRESSORS
Quantity n.
Maximum operating current A
Starting current A
Number of capacity steps n.
EVAPORATOR (brazed-plate)
n.
Water volume
Maximum water flow m³/h
PARTIAL HEAT RECOVERY EXCHANGER
n.
Water volume l
Maximum water flow m³/h
AXIAL FANS (AC)
n.
Total air flow m³/h
Absorbed power kW
Nominal operating current Fans A
REFRIGERANT
Total refrigerant load (excluding options) kg
Number of refrigerant circuits n.
SUPPLY VOLTAGE
V/Ph/Hz
ENERGY EFFICIENCY RATIOS (1)
EER kW/kW
ESEER = Eurovent standard
SOUND LEVELS
Average sound pressure level [Lpm] (4) dB(A)
Sound power level (Lw) (5) dB(A)
HYDRAULIC KIT
1 pump 2 poles GE
2 pumps 2 poles GE
--
--
--
--
--
GE65/11
GE65/11
GE65/11
GE65/11
GE65/11
1 operational pumps + 1 emergency pump GE
--
--
--
--
--
2 operational pumps + 1 emergency pump GE
GE65/21
GE65/21
GE65/21
GE65/21
GE65/21
Length mm
10660
10660
10660
11630
12600
Width mm
2260
2260
2260
2260
2260
Height mm
2550
2550
2550
2550
2550
15142
15402
15422
16101
16780
273
323.9
323.9
323.9
323.9
2 x 2"
2 x 2"
2 x 2"
2 x 2"
2 x 2"
DIMENSIONS
NET WEIGHT
kg
HYDRAULIC CONNECTIONS
EVAPORATOR
Inlet outlet diameter Ø mm
PARTIAL HEAT RECOVERY EXCHANGER
Inlet outlet diameter – ISO228/1-G M Ø
(1) Gross value - chilled water temperature 12/7°C; outdoor temperature 35°C; 20%
ethylene glycol solution.
(2) Gross value - water inlet temperature 15°C; 20% ethylene glycol solution; outdoor
temperature 3°C.
(3) Gross value - chilled water temperature 12/7°C; outdoor temperature 35°C and hot water
temperature 40/45°C.
(4) Sound pressure level [Lpm] at 1m far according to ISO EN 3744
(5) Sound power level [Lw] according to ISO EN 9614-2.
82
LIQUID CHILLERS | WATER-COOLED
EWNL
06 / 30
Cooling only
SCROLL COMPRESSORS
Cooling capacities from 5 to 30 kW
10 sizes
Refrigerant: R410A
EER up to 4.84
ESEER up to 6.68
MAIN FEATURES
Solution for domestic and small office installations
Scroll compressor
Brazed-plate evaporator
Brazed-plate condenser
Main accessories and options
AVAILABLE VERSIONS
Code
450
610
920
923
1002
Mono-phase up to 13 kW
Tri-phase on the full range
Heat pump version (see EWNH range)
Remote condenser cooling only
(see EWNL RC range)
Remote condenser heat pump
(see EWNH RC range)
Desuperheater
Compressor sound-insulating jacket
Remote control kit
COM MBUS/JBUS serial card
Condensation control with 2-way valve
Besides these options, please speak to our Sales Department for any other
configuration or function that is not listed as being available.
Advantages
Simple and reliable
Plug and play
Electronic control system
3-speed circulation pump (evap) as standard
0-10V signal for controlling 2-way valve on condenser
Service valves on discharge and liquid line
Cooling operating limits
20
15
Evaporator water
outlet temperature
Indicative values. The operating T° are influenced
by a series of settings such as: operating
conditions, thermal load, adjustments, etc... Data
to be confirmed upon selection.
(°C)
10
5
0
Glycol solution
+ low temperature kit
-5
-10
-13
20
25
30
35
40
45
50
Water outlet temperature from the condenser
83
55
60(°C)
LIQUID CHILLERS | WATER-COOLED
EWNL 06 / 30 Cooling only
TECHNICAL SPECIFICATIONS
SIZE
06M
08M
10M
13M
06T
Cooling capacity (1) kW
5.7
7.4
11.1
14.1
5.7
Compressors absorbed power kW
1.4
1.8
2.4
3
1.4
6.5
8.2
11.9
14.9
2.8
1
1
Nominal operating current Compressors A
EVAPORATOR No.
Evaporator water flow m³/h
Evaporator pressure loss kPa
CONDENSER
Evaporator water flow m³/h
Evaporator pressure loss kPa
0.98
1.27
1.91
2.41
0.98
35
33
37
40
35
1
1
1
1
1
1.23
1.6
2.34
2.95
1.23
54
49
53
58
53
0.9
1.2
1.7
2.2
0.9
0.15
0.2
0.3
0.38
0.15
0.25
0.41
0.93
1.48
0.25
scroll
scroll
scroll
scroll
scroll
1
1
1
1
1
12.8
17.1
21
31
4.7
60
67
98
115.5
28
1
1
1
1
1
PARTIAL HEAT RECOVERY (2)
Heating capacity kW
Heat recovery exchanger water flow m³/h
Heat recovery pressure loss kPa
COMPRESSORS
Quantity n.
Maximum operating current A
Starting current A
Number of capacity steps n.
EVAPORATOR
n.
Water volume l
Maximum water flow m³/h
CONDENSER
1
1
1
1
1
0.5
0.7
0.9
1.1
0.5
1.5
2
2.7
3.5
1.4
0.5
0.7
0.9
1.1
0.5
1.8
2.4
3.2
4.1
1.7
1
1
1
1
1
0.1
0.1
0.1
0.1
0.1
0.4
0.5
0.6
0.8
0.3
n.
Water volume l
Maximum water flow m³/h
PARTIAL HEAT RECOVERY EXCHANGER
n.
Water volume l
Maximum water flow m³/h
REFRIGERANT
Total refrigerant load (excluding options) kg
Number of refrigerant circuits n.
SUPPLY VOLTAGE
V/Ph/Hz
R410A
R410A
R410A
R410A
R410A
0.7
0.9
1.1
1.4
0.7
1
1
1
1
1
230/1/50
230/1/50
230/1/50
230/1/50
400/3/50+N
4.12
4.09
4.63
4.7
4.11
ENERGY EFFICIENCY RATIOS (1)
EER kW/kW
ESEER – Eurovent Standard
6.01
6.23
6.28
6.54
6.26
IPLV – ARI Standard 550/590
6.39
6.62
6.68
6.95
6.65
42
42
44
44
42
56.2
56.2
58.2
58.2
56.2
Length mm
555
555
555
555
555
Width mm
650
650
650
650
650
Height mm
900
900
900
900
900
88.7
91.4
101.5
106.3
88.7
1 1/2"
1 1/2"
1 1/2"
1 1/2"
1 1/2"
1"
1"
1"
1"
1"
SOUND LEVELS
Average sound pressure level [Lpm] (4) dB(A)
Sound power level (Lw) dB(A)
DIMENSIONS
NET WEIGHT
kg
HYDRAULIC CONNECTIONS
EVAPORATOR / CONDENSER
Inlet outlet diameter – ISO228/1-G M Ø
PARTIAL HEAT RECOVERY EXCHANGER
Inlet outlet diameter – ISO228/1-G M Ø
(1) Gross value - chilled water temperature 12/7°C; 30/35°C on condenser.
(2) Gross value - chilled water temperature 12/7°C; 30/35°C on condenser and
heat recovery water temperature 40/45°C.
(3) Sound pressure level [Lpm] at 1m far according to ISO EN 3744
(4) Sound power level [Lw] according to ISO EN 9614-2.
84
08T
10T
13T
15T
17T
20T
25T
30T
7.3
10.4
13.3
15.1
17.4
20.1
24.8
30.5
1.8
2.3
2.9
3.4
4
4.5
5.6
6.3
3.6
4.1
5
6.4
7.4
9.2
11.2
12.7
1
1
1
1
1
1.25
1.78
2.29
2.58
2.99
3.45
4.26
5.24
32
36
40
37
43
40
40
44
1
1
1
1
1
1
1
1
1.57
2.2
2.81
3.2
3.7
4.26
5.26
6.38
48
53
57
53
61
55
53
49
1.1
1.6
2.1
2.4
2.7
3.1
3.9
4.8
0.2
0.28
0.36
0.4
0.47
0.54
0.67
0.82
0.4
0.81
1.33
0.45
0.61
0.81
1.23
1.87
scroll
scroll
scroll
scroll
scroll
scroll
scroll
scroll
1
1
1
1
1
1
1
1
6.5
8
10.3
11.8
15
15
21
22
38
43
51.5
64
75
101
111
118
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
0.7
0.9
1.1
1.2
1.3
1.6
2
2.4
1.9
2.5
3.3
3.8
4.4
5
6.3
7.4
0.7
0.9
1.1
1.2
1.3
1.6
2
2.4
2.2
3
3.9
4.5
5.2
5.9
7.4
8.7
1
1
1
1
1
1
1
1
0.1
0.1
0.1
0.2
0.2
0.2
0.2
0.2
0.4
0.6
0.8
0.9
1.1
1.2
1.5
1.7
R410A
R410A
R410A
R410A
R410A
R410A
R410A
R410A
0.9
1.1
1.4
1.5
1.8
1.8
2.5
3.1
1
1
1
1
1
1
1
1
400/3/50+N
400/3/50+N
400/3/50+N
400/3/50+N
400/3/50+N
400/3/50+N
400/3/50+N
400/3/50+N
4.15
4.48
4.55
4.43
4.37
4.48
4.44
4.84
6.41
6.62
6.49
6.38
6.53
6.4
6.47
6.68
6.81
7.04
6.9
6.78
6.94
6.8
6.88
7.1
42
44
44
47
51
48
50
50
56.2
58.2
58.2
61.2
65.2
62.2
64.2
64.2
555
555
555
555
555
555
555
555
650
650
650
650
650
650
650
650
900
900
900
900
900
900
900
900
91.4
101.5
106.3
114.5
116
118.5
141.7
147.4
1 1/2"
1 1/2"
1 1/2"
1 1/2"
1 1/2"
1 1/2"
1 1/2"
1 1/2"
1"
1"
1"
1"
1"
1"
1"
1"
85
LIQUID CHILLERS | WATER-COOLED
EWNH
06 / 30
Reversible
SCROLL COMPRESSORS
Cooling capacities from 5 to 30 kW
Heating capacities from 7 to 37 kW
13 sizes
Refrigerant: R410A
EER up to 4.81
ESEER up to 6.68
COP up to 4.44
MAIN FEATURES
Heat pump (reversible refrigerant circuit refrigeration
circuit)
Solution for domestic and small office installations
Scroll compressor
Brazed-plate evaporator
Brazed-plate condenser
AVAILABLE VERSIONS
Mono-phase up to 13 kW
Tri-phase on the full range
Cooling only (see EWNL range)
Remote condenser cooling only
(see EWNL RC range)
Remote condenser heat pump
(see EWNH RC range)
Main accessories and options
Code
450
610
920
923
1002
Desuperheater
Compressor sound-insulating jacket
Remote control kit
COM MBUS/JBUS serial card
Condensation control with 2-way valve
Besides these options, please speak to our Sales Department for any other
configuration or function that is not listed as being available.
Advantages
Simple and reliable
Plug and play
Electronic control system
3-speed circulation pump (evap) as standard
0-10V signal for controlling 2-way valve on condenser
Service valves on discharge and liquid line
Indicative values. The operating T° are influenced by
a series of settings such as: operating conditions,
thermal load, adjustments, etc... Data to be
confirmed upon selection.
(°C)
20
15
Evaporator water
outlet temperature
Cooling/heating operating limits
10
5
0
Glycol solution
+ low temperature kit
-5
-10
-13
20
25
30
35
40
45
50
Water outlet temperature from the condenser
86
55
60(°C)
EWNH 06 / 30 Reversible
TECHNICAL SPECIFICATIONS
SIZE
06M
08M
10M
13M
06T
08T
10T
13T
15T
17T
20T
25T
30T
SUMMER CONDITIONS (1)
Cooling capacity (1) kW
5.6
7.6
10.5
13
5.3
6.8
9.5
12.3
13.9
16.6
18.6
23.4
30
Compressors absorbed power kW
1.4
1.8
2.3
3
1.4
1.8
2.3
2.9
3.5
4
4.5
5.6
6.2
2.8
3.6
4.1
5.1
2.8
3.6
4.1
5.1
6.4
7.4
9.3
11.3
12.5
Nominal operating current Compressors A
PLANT SIDE HEAT EXCHANGER
Water flow m³/h
Pressure loss kPa
0.96
1.3
1.8
2.23
0.91
1.16
1.63
2.12
2.39
2.85
3.19
4.02
5.16
37
33
38
42
33
30
34
38
35
40
37
40
41
REJECTION SIDE HEAT EXCHANGER
Water flow m³/h
Pressure loss kPa
1.2
1.6
2.1
2.76
1.1
1.48
2
2.6
3
3.5
3.9
5
5.8
54
48
49
59
45
45
47
53
51
56
50
53
40
WINTER CONDITIONS (2)
Heating capacity (2) kW
7.6
9.5
13.1
17.2
7.2
9.2
12.7
16.5
18.5
21.8
24.7
30.8
37.4
Compressors absorbed power kW
1.9
2.3
3.1
3.9
1.9
2.4
3
3.8
4.3
5.2
5.8
7.1
8.6
3.4
4.3
5.2
6.4
3.4
4.3
5.1
6.4
7.8
8.9
10.8
13.1
16
Nominal operating current Compressors A
PLANT SIDE HEAT EXCHANGER
Water flow m³/h
Ppressure loss kPa
0.96
1.3
1.8
2.23
0.91
1.16
1.63
2.12
2.39
2.85
3.19
4.02
5.16
29
30
34
33
26
23
27
29
27
32
29
30
34
REJECTION SIDE HEAT EXCHANGER
Water flow m³/h
Pressure loss kPa
0.98
1.24
1.73
2.3
0.92
1.18
1.66
2.18
2.43
2.87
3.24
4.09
4.95
31
28
32
35
27
25
28
31
29
33
31
34
35
PARTIAL HEAT RECOVERY (3)
Heating capacity kW
Heat recovery exchanger water flow m³/h
Heat recovery pressure loss kPa
COMPRESSORS
Quantity n.
Maximum operating current A
Starting current A
Number of capacity steps n.
PLANT SIDE HEAT EXCHANGER
n.
Water volume l
Maximum water flow m³/h
REJECTION SIDE HEAT EXCHANGER
n.
Water volume l
Maximum water flow m³/h
PARTIAL HEAT RECOVERY EXCHANGER
n.
Water volume l
Maximum water flow m³/h
REFRIGERANT
Total refrigerant load (excluding options) kg
Number of refrigerant circuits n.
V/Ph/
Hz
SUPPLY VOLTAGE
0.9
1.1
1.6
2.1
0.9
1.1
1.5
2
2.2
2.6
3
3.7
4.7
0.2
0.2
0.3
0.4
0.2
0.2
0.3
0.3
0.4
0.5
0.5
0.6
0.8
0.3
0.4
0.8
1.3
0.2
0.4
0.7
1.2
0.4
0.6
0.7
1.1
1.8
scroll
scroll
scroll
scroll
scroll
scroll
scroll
scroll
scroll
scroll
scroll
scroll
scroll
1
1
1
1
1
1
1
1
1
1
1
1
1
12.8
17.1
21
31
4.7
6.5
8
10.3
11.8
15
15
21
22
60
67
98
115.5
28
38
43
51.5
64
75
101
111
118
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
0.5
0.7
0.9
1.1
0.5
0.7
0.9
1.1
1.2
1.3
1.6
2
2.4
1.6
2.2
2.9
3.7
1.6
2.1
2.7
3.6
4
4.7
5.3
6.7
7.8
1
1
1
1
1
1
1
1
1
1
1
1
1
0.5
0.7
0.9
1.1
0.5
0.7
0.9
1.1
1.2
1.3
1.6
2
2.4
1.2
1.6
2.1
2.8
1.1
1.6
2
2.6
3
3.5
3.9
5
5.8
1
1
1
1
1
1
1
1
1
1
1
1
1
0.1
0.1
0.1
0.1
0.1
0.1
0.1
0.1
0.2
0.2
0.2
0.2
0.2
0.3
0.5
0.6
0.8
0.3
0.4
0.6
0.8
0.9
1
1.2
1.5
1.7
R410A
R410A
R410A
R410A
R410A
R410A
R410A
R410A
R410A
R410A
R410A
R410A
R410A
0.7
0.9
1.1
1.4
0.7
0.9
1.1
1.4
1.5
1.8
1.8
2.5
3.1
1
1
1
1
1
1
1
1
1
1
1
1
1
230/1/
50
230/1/
50
230/1/
50
230/1/
50
400/3/
50+N
400/3/
50+N
400/3/
50+N
400/3/
50+N
400/3/
50+N
400/3/
50+N
400/3/
50+N
400/3/
50+N
400/3/
50+N
ENERGY EFFICIENCY RATIOS
EER Kw/Kw
3.95
4.23
4.53
4.41
3.76
3.78
4.08
4.18
4.02
4.15
4.12
4.18
4.81
COP Kw/Kw
4.09
4.11
4.3
4.44
3.9
3.92
4.19
4.3
4.26
4.23
4.24
4.34
4.37
ESEER – Eurovent Standard
4.78
6.23
5.19
5.46
4.6
4.86
6.62
6.49
5.28
5.38
5.28
6.47
6.68
IPLV – ARI Standard 550/590
6.39
6.62
6.68
6.95
6.65
6.81
7.04
6.9
6.78
6.94
6.8
6.88
7.1
SOUND LEVELS
Average sound pressure level [Lpm] (4) dB(A)
Sound power level (Lw) (5) dB(A)
42
42
44
44
42
42
44
44
47
51
48
50
50
56.2
56.2
58.2
58.2
56.2
56.2
58.2
58.2
61.2
65.2
62.2
64.2
64.2
DIMENSIONS
Length mm
555
555
555
555
555
555
555
555
555
555
555
555
555
Width mm
650
650
650
650
650
650
650
650
650
650
650
650
650
Height mm
900
900
900
900
900
900
900
900
900
900
900
900
900
90.8
93.5
103.6
108.4
90.8
93.5
103.6
108.4
116.6
118.1
120.6
143.8
149.5
1 1/2"
1 1/2"
1 1/2"
1 1/2"
1 1/2"
1 1/2"
1 1/2"
1 1/2"
1 1/2"
1 1/2"
1 1/2"
1 1/2"
1 1/2"
1"
1"
1"
1"
1"
1"
1"
1"
1"
1"
1"
1"
1"
NET WEIGHT
kg
HYDRAULIC CONNECTIONS
PLANT / REJECTION HEAT EXCHANGERS
Inlet outlet diameter – ISO228/1-G M Ø
PARTIAL HEAT RECOVERY EXCHANGER
Inlet outlet diameter – ISO228/1-G M Ø
(1) Gross value - chilled water temperature 12/7°C; 30/35°C on condenser.
(2) Gross value - chilled water temperature 12/7°; hot water outlet temperature 45°C.
(3) Gross value - chilled water temperature 12/7°C; 30/35°C on condenser and heat
recovery water temperature 40/45°C.
(4) Sound pressure level [Lpm] at 1m far according to ISO EN 3744
(5) Sound power level [Lw] according to ISO EN 9614-2.
87
LIQUID CHILLERS | WATER-COOLED
EWNL RC
06 / 30
Cooling only
SCROLL COMPRESSORS
REMOTE CONDENSER
Cooling capacities from 5 to 30 kW
13 sizes
Refrigerant: R410A
EER up to 4.84
ESEER up to 6.68
MAIN FEATURES
Remote condenser
Solution for domestic and small office installations
Scroll compressor
Brazed-plate evaporator
AVAILABLE VERSIONS
Mono-phase up to 13 kW
Tri-phase on the full range
Heat pump (see EWNH range)
Cooling only (see EWNL range)
Remote condenser heat pump (see EWNH RC)
Main accessories and options
Code
450
610
764
920
923
Desuperheater
Compressor sound-insulating jacket
Water tank
Remote control kit
COM MBUS/JBUS serial card
Besides these options, please speak to our Sales Department for any other
configuration or function that is not listed as being available.
Advantages
FOR THE TECHNICAL SPECIFICATIONS
SEE EWNL ON PAGE 84; FOR THE PERFORMANCES
SEE SELECTION SOFTWARE
Simple and reliable
Plug and play
Electronic control system
3-speed circulation pump (evap) as standard
Operating limits
(to be confirmed following selection conditions)
COOLING MODE
Water leaving temperature evaporator (without glycol)
5 / 20ºC
Water leaving temperature evaporator
(with glycol max 40%)
-12 / 5°C
88
LIQUID CHILLERS | WATER-COOLED
EWNH RC
06 / 30
Reversible
SCROLL COMPRESSORS
REMOTE CONDENSER
Cooling capacities from 5 to 30 kW
Heating capacities from 7 to 37 kW
13 sizes
Refrigerant: R410A
EER up to 4.84
ESEER up to 6.68
COP up to 4.44
MAIN FEATURES
Heat pump (reversible refrigeration circuit
refrigeration circuit)
Remote condenser
Solution for domestic and small office installations
Scroll compressor
Brazed-plate evaporator
Main accessories and options
Code
450
610
920
923
AVAILABLE VERSIONS
Mono-phase up to 13 kW
Tri-phase on the full range
Cooling only (see EWNL range)
Heat pump (see EWNH range)
Remote condenser cooling only (see EWNL RC range)
Desuperheater
Compressor sound-insulating jacket
Remote control kit
COM MBUS/JBUS serial card
Besides these options, please speak to our Sales Department for any other
configuration or function that is not listed as being available.
FOR THE TECHNICAL SPECIFICATIONS SEE EWNH
ON PAGE 87; FOR THE PERFORMANCES SEE
SELECTION SOFTWARE
Advantages
Simple and reliable
Plug and play
Electronic control system
3-speed circulation pump (evap) as standard
89
LIQUID CHILLERS | WATER-COOLED
EWML
27 / 570
Cooling only
SCROLL COMPRESSORS
Cooling capacities from 23 to 670 kW
33 sizes
Refrigerant: R410A
EER up to 4.40
ESEER up to 6.51
MAIN FEATURES
Scroll compressors
Brazed-plate evaporator
Brazed-plate condenser
Mono or twin circuit units
Partial heat recovery
Heat pump reversible on the refrigeration circuit
(see EWMH range)
Remote condenser cooling only
(see range EWML RC)
Remote condenser heat pump
(see range EWMH RC)
Leaving water low temperature version
Advantages
Plug and play
Condenser water outlet up to 60°C
Universal communication electronic control system, easy
to read and easy access to information
Electronic expansion valve as standard from size 175
0-10V signal for controlling 2-way valve on condenser
Service valves on discharge and liquid line
Cooling operating limits
Indicative values. The operating T° are influenced
by a series of settings such as: operating
conditions, thermal load, adjustments, etc... Data
to be confirmed upon selection.
Main accessories and options
Code
118
119
172
175
220
450
605
919
923
926
931
932
942
943
1002
Kit A leaving chilled water low temperature operation
Kit B leaving chilled water low temperature operation
Antivibration mounts - rubber - supplied loose
Victaulic connections
Electronic expansion valve
Desuperheater
Power factor capacitor for cos phi 0.9 on compressor motor
Clock card
COM MBUS/JBUS serial card
LON serial card
BACnet Ethernet - SNMP - TCP/IP serial card
BACnet MS/TP serial card
Serial card for GSM modem
Data logger
Condensation control with 2-way valve
Besides these options, please speak to our Sales Department for any other
configuration or function that is not listed as being available.
(°C)
20
15
Evaporator water
outlet temperature
AVAILABLE VERSIONS
10
5
0
Glycol solution
+ Low temp. operation kit
-5
-10
-13
20
25
30
35
40
45
50
Water outlet temperature from the condenser
90
55
60(°C)
EWML 27 / 570 Cooling only
TECHNICAL SPECIFICATIONS
SIZE
T 27 P1
Cooling capacity (1) kW
Compressors absorbed power kW
Nominal operating current Compressors A
T 30 P1
T 33 P1
T 40 P1
T 40 P2
T 40 P2
29.1
32.9
36.6
41.3
47.6
48.5
6.4
7.2
8.2
10.1
11.4
11.5
12.8
13.7
16
21
22.7
22.9
5
5.7
6.3
7.1
8.2
8.3
55
56
50
37
46
28
EVAPORATOR
Evaporator water flow m³/h
Evaporator pressure loss kPa
CONDENSER
Condenser water flow m³/h
Condenser pressure loss kPa
6.1
7
7.8
8.9
10.2
10.4
69
63
64
47
57
38
PARTIAL HEAT RECOVERY (2)
Heating capacity kW
Heat recovery exchanger water flow m³/h
Heat recovery pressure loss kPa
COMPRESSORS
Quantity n.
Maximum operating current A
4.5
5.1
5.7
6.4
7.4
--
0.8
0.9
1
1.1
1.3
--
7.3
9.3
11.5
4.9
6.5
--
scroll
scroll
scroll
scroll
scroll
scroll
1
1
1
1
2
2
22
25
31
34
42
42
118
118
140
173
132
132
Number of capacity steps n.
1
1
1
1
2
2
n.
1
1
1
1
1
1
2.8
2.8
2.8
3.1
3.1
3.6
7
7.9
8.8
9.9
11.4
11.6
1
1
1
1
1
1
2.8
2.8
2.8
3.1
3.1
3.6
8.6
9.7
10.9
12.5
14.3
14.6
1
1
1
1
1
--
Starting current A
EVAPORATOR
Water volume l
Maximum water flow m³/h
CONDENSER
n.
Water volume l
Maximum water flow m³/h
PARTIAL HEAT RECOVERY EXCHANGER
n.
Water volume l
Maximum water flow m³/h
REFRIGERANT
Total refrigerant load (excluding options) kg
Number of capacity steps n.
SUPPLY VOLTAGE
V/Ph/Hz
0.4
0.4
0.4
0.6
0.6
--
1.1
1.2
1.4
1.6
1.8
--
R410A
R410A
R410A
R410A
R410A
R410A
2.9
2.9
3
3.9
4.2
5
1
1
1
1
1
2
400/3/50
400/3/50
400/3/50
400/3/50
400/3/50
400/3/50
4.55
4.56
4.44
4.09
4.18
4.22
ENERGY EFFICIENCY RATIOS (1)
EER kW/kW
ESEER – Eurovent Standard
6.36
6.32
5.97
6.14
5.34
6.27
IPLV – ARI Standard 550/590
6.76
6.72
6.35
6.53
5.68
6.67
SOUND LEVELS
Average sound pressure level [Lpm] (4) dB(A)
Sound power level (Lw) dB(A)
50
51
52
53
53
53
65.4
66.4
67.4
68.8
68.9
68.9
DIMENSIONS
NET WEIGHT
Length mm
1000
1000
1000
1000
1200
1200
Width mm
650
650
650
650
750
750
Height mm
1400
1400
1400
1400
1700
1700
258
260
270
281
440
450
1 1/2"
1 1/2"
1 1/2"
2"
2"
2"
--
--
--
--
--
--
1"
1"
1"
1"
1"
--
kg
HYDRAULIC CONNECTIONS
EVAPORATOR / CONDENSER
Inlet outlet diameter – ISO228/1-G M Ø
Inlet outlet diameter Ø mm
PARTIAL HEAT RECOVERY EXCHANGER
Inlet outlet diameter – ISO228/1-G M Ø
(1) Gross value - chilled water temperature 12/7°C; 30/35°C on condenser.
(2) Gross value - chilled water temperature 12/7°C; 30/35°C on condenser and heat
recovery water temperature 40/45°C.
(3) Sound pressure level [Lpm] at 1m far according to ISO EN 3744
(4) Sound power level [Lw] according to ISO EN 9614-2.
91
➜
LIQUID CHILLERS | WATER-COOLED
EWML 27 / 570 Cooling only
TECHNICAL SPECIFICATIONS
SIZE
T 48 P2
T 48 P2
T 54 P2
T 54 P2
T 60 P2
Cooling capacity (1) kW
56.9
56.7
65.4
64.2
69.8
Compressors absorbed power kW
13.2
12.9
15.1
14.6
16.8
26.2
25.8
28.3
27.7
32.5
9.8
9.7
11.2
11
12
47
29
50
28
43
12.1
12.1
13.9
13.6
15
57
38
60
37
51
8.9
--
10.2
--
10.9
1.5
--
1.8
--
1.9
9.3
--
8
--
9.2
scroll
scroll
scroll
scroll
scroll
2
2
2
2
2
Nominal operating current Compressors A
EVAPORATOR
Evaporator water flow m³/h
Evaporator pressure loss kPa
CONDENSER
Condenser water flow m³/h
Condenser pressure loss kPa
PARTIAL HEAT RECOVERY (2)
Heating capacity kW
Heat recovery exchanger water flow m³/h
Heat recovery pressure loss kPa
COMPRESSORS
Quantity n.
Maximum operating current A
44
44
50
50
62
140
140
143
143
171
Number of capacity steps n.
2
2
2
2
2
n.
1
1
1
1
1
3.1
4.2
3.9
4.2
3.9
13.7
13.6
15.7
15.4
16.8
1
1
1
1
1
3.1
4.2
3.9
4.2
3.9
16.9
16.9
19.5
19
21
1
--
1
--
1
0.6
--
0.8
--
0.8
2.1
--
2.5
--
2.6
R410A
R410A
R410A
R410A
R410A
Starting current A
EVAPORATOR
Water volume l
Maximum water flow m³/h
CONDENSER
n.
Water volume l
Maximum water flow m³/h
PARTIAL HEAT RECOVERY EXCHANGER
n.
Water volume l
Maximum water flow m³/h
REFRIGERANT
Total refrigerant load (excluding options) kg
Number of capacity steps n.
SUPPLY VOLTAGE
V/Ph/Hz
4.3
5.7
5.7
5.7
5.8
1
2
1
2
1
400/3/50
400/3/50
400/3/50
400/3/50
400/3/50
4.31
4.4
4.33
4.4
4.15
ENERGY EFFICIENCY RATIOS (1)
EER kW/kW
ESEER – Eurovent Standard
5.59
6.47
5.54
6.52
5.21
IPLV – ARI Standard 550/590
5.94
6.88
5.88
6.93
5.54
SOUND LEVELS
Average sound pressure level [Lpm] (4) dB(A)
Sound power level (Lw) dB(A)
53
53
54
54
55
68.9
68.9
69.9
69.9
70.9
DIMENSIONS
NET WEIGHT
Length mm
1200
1200
1200
1200
1200
Width mm
750
750
750
750
750
Height mm
1700
1700
1700
1700
1700
444
455
455
468
460
2"
2"
2"
2"
2"
--
--
--
--
--
1"
--
1"
--
1"
kg
HYDRAULIC CONNECTIONS
EVAPORATOR / CONDENSER
Inlet outlet diameter – ISO228/1-G M Ø
Inlet outlet diameter Ø mm
PARTIAL HEAT RECOVERY EXCHANGER
Inlet outlet diameter – ISO228/1-G M Ø
(1) Gross value - chilled water temperature 12/7°C; 30/35°C on condenser.
(2) Gross value - chilled water temperature 12/7°C; 30/35°C on condenser and heat
recovery water temperature 40/45°C.
(3) Sound pressure level [Lpm] at 1m far according to ISO EN 3744
(4) Sound power level [Lw] according to ISO EN 9614-2.
92
T 60 P2
T 70 P2
T 70 P2
T 90 P2
T 90 P2
T 120 P2
T 120 P2
T 150 P2
T 150 P2
70.4
83.4
83.1
108
107
135
134
175
173
16.5
20.6
20
26.2
25.7
33.2
32.6
42.3
41.6
31.9
41.9
41.3
48.3
47.7
61
60.5
75.5
75.1
12.1
14.3
14.3
18.5
18.4
23.1
23
30
29.7
28
50
28
46
29
48
38
46
42
15
18
17.8
23.2
23
29.1
28.8
37.5
37.2
36
60
37
52
36
53
47
45
47
--
13
--
16.9
--
21
--
27.2
27
--
2.2
--
2.9
--
3.6
--
4.7
4.7
8.3
--
7.7
--
7.5
--
8.1
--
10.5
scroll
scroll
scroll
scroll
scroll
scroll
scroll
scroll
scroll
2
2
2
2
2
2
2
2
2
62
68
68
80
80
97
97
131
131
171
207
207
265
265
321
321
375
375
2
2
2
2
2
2
2
2
2
1
1
1
1
1
1
1
1
1
4.2
4.7
6.4
5.8
6.7
7.2
8.3
8.7
12.3
16.9
20
20
25.9
25.8
32.3
32.2
42
41.6
1
1
1
1
1
1
1
1
1
4.2
4.7
6.4
5.8
6.7
7.2
8.3
8.7
12.3
21
25.2
24.9
32.5
32.2
40.7
40.3
52.5
52.1
--
1
--
1
--
1
--
1
2
--
1
--
1.7
--
2.1
--
4
2 x 1.0
--
3.1
--
4.1
--
5.1
--
6.6
6.5
R410A
R410A
R410A
R410A
R410A
R410A
R410A
R410A
R410A
5.7
6.6
8.1
8.7
10.4
10.7
12.7
12.4
17
2
1
2
1
2
1
2
1
2
400/3/50
400/3/50
400/3/50
400/3/50
400/3/50
400/3/50
400/3/50
400/3/50
400/3/50
4.27
4.05
4.16
4.12
4.16
4.07
4.11
4.14
4.16
5.93
5.56
6.45
5.18
6.06
5.23
6.1
5.08
6.13
6.3
5.91
6.86
5.5
6.44
5.56
6.48
5.4
6.52
55
56
56
61
61
64
64
64
64
70.9
71.9
71.9
76.9
76.9
80.1
80.1
81
81
1200
1200
1200
1200
1200
1200
1200
1800
1800
750
750
750
750
750
750
750
1200
1200
1700
1700
1700
1700
1700
1700
1700
1740
1740
485
465
495
715
760
775
788
1022
1030
2"
2"
2"
--
--
--
--
--
--
--
--
--
73.1
73.1
73.1
73.1
73.1
73.1
--
1"
--
1 1/4"
--
1 1/4"
--
2"
2 x 1"
➜
93
LIQUID CHILLERS | WATER-COOLED
EWML 27 / 570 Cooling only
TECHNICAL SPECIFICATIONS
SIZE
T 170 P4
T 175 P3
T 190 P4
T 200 P2
T 200 P2
Cooling capacity (1) kW
200
199
214
229
227
Compressors absorbed power kW
45.8
49.8
54.3
53.4
53.3
88.9
91.5
95.8
95.2
95.5
34.3
34.2
36.8
39.2
38.9
42
54
34
46
53
42.6
43.1
46.6
48.8
48.5
70
51
42
62
71
31.2
31.1
33.5
35.6
35.3
5.4
5.4
5.8
6.1
6.1
11
8
7.4
10.6
8.2
Nominal operating current Compressors A
EVAPORATOR
Evaporator water flow m³/h
Evaporator pressure loss kPa
CONDENSER
Condenser water flow m³/h
Condenser pressure loss kPa
PARTIAL HEAT RECOVERY (2)
Heating capacity kW
Heat recovery exchanger water flow m³/h
Heat recovery pressure loss kPa
COMPRESSORS
Quantity n.
scroll
scroll
scroll
scroll
scroll
4
3
4
2
2
Maximum operating current A
148
146
160
164
164
Starting current A
333
369
345
466
466
4
3
4
2
2
Number of capacity steps n.
EVAPORATOR
n.
Water volume l
Maximum water flow m³/h
CONDENSER
n.
Water volume l
Maximum water flow m³/h
PARTIAL HEAT RECOVERY EXCHANGER
n.
Water volume l
Maximum water flow m³/h
REFRIGERANT
Total refrigerant load (excluding options) kg
Number of capacity steps n.
SUPPLY VOLTAGE
V/Ph/Hz
1
1
1
1
1
12.3
11.1
20.3
20.7
20.3
48
47.9
51.5
54.9
54.5
1
1
1
1
1
12.3
11.1
20.3
20.3
21.2
59.6
60.3
65.2
68.3
67.9
2
1
2
1
2
2 x 1.7
5.3
2 x 1.7
5.3
2 x 1.7
7.5
7.5
8.1
8.6
8.5
R410A
R410A
R410A
R410A
R410A
17.8
16
23.9
22.4
22.8
2
1
2
1
2
400/3/50
400/3/50
400/3/50
400/3/50
400/3/50
ENERGY EFFICIENCY RATIOS (1)
4.37
4
3.94
4.29
4.26
ESEER – Eurovent Standard
EER kW/kW
5.29
6.33
6.02
5.29
6.11
IPLV – ARI Standard 550/590
5.76
6.73
6.8
5.62
6.49
SOUND LEVELS
Average sound pressure level [Lpm] (4) dB(A)
64
65.8
64
64
64
Sound power level (Lw) dB(A)
81
82.8
81
81
81
DIMENSIONS
NET WEIGHT
Length mm
1800
1800
1800
1800
1800
Width mm
1200
1200
1200
1200
1200
Height mm
1740
1740
1740
1740
1740
kg
1130
1152
1315
1085
1115
--
--
--
--
--
73.1
73.1
88.9
88.9
88.9
2 x 1 1/4"
2"
2 x 1 1/4"
2"
2 x 1 1/4"
HYDRAULIC CONNECTIONS
EVAPORATOR / CONDENSER
Inlet outlet diameter – ISO228/1-G M Ø
Inlet outlet diameter Ø mm
PARTIAL HEAT RECOVERY EXCHANGER
Inlet outlet diameter – ISO228/1-G M Ø
(1) Gross value - chilled water temperature 12/7°C; 30/35°C on condenser.
(2) Gross value - chilled water temperature 12/7°C; 30/35°C on condenser and heat
recovery water temperature 40/45°C.
(3) Sound pressure level [Lpm] at 1m far according to ISO EN 3744
(4) Sound power level [Lw] according to ISO EN 9614-2.
94
T 220 P3
T 240 P4
T 290 P3
T 300 P4
T 340 P4
T 380 P4
T 460 P6
T 570 P6
270
276
331
347
403
446
534
670
62.4
65
79.3
83.2
95
107
124
161
113
121
142
150
170
190
224
287
46.4
47.3
56.8
59.5
69.1
76.6
91.6
115
52
61
49
70
70
64
63
85
57.6
59
71.1
74.5
86.2
95.7
114
144
68
81
60
89
86
74
64
83
42.1
43
51.7
54.1
62.8
69.6
83.2
104
7.3
7.4
8.9
9.3
10.8
12
14.3
18
10.5
8.4
10
10.3
13.9
10.1
10.3
10.1
scroll
scroll
scroll
scroll
scroll
scroll
scroll
scroll
3
4
3
4
4
4
6
6
197
246
194
262
295
328
393
492
441
584
418
507
597
630
637
794
3
4
3
4
4
4
6
6
1
1
1
1
1
1
1
1
20.7
27
20.3
27.5
33.8
44.6
44.6
57.2
65
66.2
79.5
83.3
96.7
107.2
128.2
161
1
1
1
1
1
1
1
1
22.5
23.9
30.6
29.3
33.8
41
51.8
56.3
80.6
82.6
99.5
104.3
120.7
134
159.6
201.6
1
2
1
2
2
2
2
2
6.3
2 x 2.1
8
2 x 4.0
2 x 4.0
2 x 5.3
2 x 6.3
2 x 8.0
10.2
10.4
12.5
13
15.1
16.8
20
25.2
R410A
R410A
R410A
R410A
R410A
R410A
R410A
R410A
23.1
24.7
30.3
31.6
31.1
48.1
49.5
62.4
1
2
1
2
2
2
2
2
400/3/50
400/3/50
400/3/50
400/3/50
400/3/50
400/3/50
400/3/50
400/3/50
4.33
4.25
4.17
4.17
4.24
4.17
4.31
4.16
6.51
5.64
6.35
5.76
5.88
5.77
6.14
6.05
6.92
6
6.75
6.13
6.25
6.14
6.53
6.43
65.8
67
65.8
67
67
67
68.8
68.8
82.8
84.1
82.8
84.1
84.5
84.5
86.3
86.3
1800
1800
1800
1800
1800
1800
1800
1800
1200
1200
1200
1200
1800
1800
1800
1800
1740
1740
1740
1740
1740
1740
1740
1740
1302
1545
1403
1590
1665
1775
2270
2300
--
--
--
--
--
--
--
--
88.9
88.9
88.9
88.9
88.9
88.9
88.9
88.9
2"
2 x 1 1/4"
2"
2 x 2"
2 x 2"
2 x 2"
2 x 2"
2 x 2"
95
LIQUID CHILLERS | WATER-COOLED
EWMH
27 / 570
Reversible
SCROLL COMPRESSORS
Cooling capacities from 23 to 670 kW
Heating capacities from 27 to 828 kW
33 sizes
Refrigerant: R410A
EER up to 4.29
ESEER up to 6.63
COP up to 4.35
MAIN FEATURES
AVAILABLE VERSIONS
Mono or twin circuit units
Partial heat recovery
Cooling only (see EWML range)
Remote condenser cooling only
(see EWML RC range)
Remote condenser heat pump
(see EWMH RC range)
Leaving water low temperature version
Advantages
Plug and play
Condenser water outlet up to 60°C
Universal communication electronic control system, easy
to read and easy access to information
Electronic expansion valve as standard
0-10V signal for controlling 2-way valve on condenser
Service valves on discharge and liquid line
Cooling/heating operating limits
Indicative values. The operating T° are influenced by
a series of settings such as: operating conditions,
thermal load, adjustments, etc... Data to be
confirmed upon selection.
Main accessories and options
Code
118
119
172
175
450
605
919
923
926
931
932
942
943
1002
Kit A leaving chilled water low temperature operation
Kit B leaving chilled water low temperature operation
Antivibration mounts - rubber - supplied loose
Victaulic connections
Desuperheater
Power factor capacitor for cos phi 0.9 on compressor motor
Clock card
COM MBUS/JBUS serial card
LON serial card
BACnet Ethernet - SNMP - TCP/IP serial card
BACnet MS/TP serial card
Serial card for GSM modem
Data logger
Condensation control with 2-way valve
Besides these options, please speak to our Sales Department for any other
configuration or function that is not listed as being available.
(°C)
20
15
Evaporator water
outlet temperature
Heat pump (reversible on the refrigeration circuit)
Scroll compressors
Brazed-plate evaporator
Brazed-plate condenser
10
5
0
Glycol solution
+ Low temp. operation kit
-5
-10
-13
20
25
30
35
40
45
50
Water outlet temperature from the condenser
96
55
60(°C)
EWMH 27 / 570 Reversible
TECHNICAL SPECIFICATIONS
SIZE
27.1
30.1
33.1
39.1
40.1
40.2
48.1
26.8
6.3
12.6
30.3
7.1
13.5
33.7
8.1
15.6
37.4
10
20.5
42.3
11.3
22.4
43.8
11.3
22.5
51.7
13.1
25.9
Water flow m³/h
Pressure loss kPa
4.6
55
5.2
56
5.8
50
6.4
37
7.3
46
7.5
28
8.9
47
Water flow m³/h
Pressure loss kPa
5.7
69
6.5
63
7.2
64
8.2
47
9.3
57
9.5
38
11.2
57
34.8
8.1
15
39.3
9
16.1
43.8
10.3
18.5
50.2
12.5
23.5
57.6
14.3
26.4
59.2
14.4
26.5
69.3
16.8
30.9
Water flow m³/h
Pressure loss kPa
4.6
42
5.2
42
5.8
37
6.4
25
7.3
30
7.5
20
8.9
31
Water flow m³/h
Pressure loss kPa
4.6
47
5.2
48
5.8
42
6.5
31
7.5
38
7.7
22
9
38
Heating capacity kW
Heat recovery exchanger water flow m³/h
Heat recovery pressure loss kPa
4.2
0.7
6.1
4.7
0.8
7.9
5.2
0.9
9.6
5.9
1
4.1
6.8
1.2
5.4
----
8.2
1.4
8
scroll
scroll
scroll
scroll
scroll
scroll
scroll
1
22
118
1
1
25
118
1
1
31
140
1
1
34
173
1
2
42
132
2
2
42
132
2
2
44
140
2
1
1
1
1
1
1
1
2.8
6.4
2.8
7.3
2.8
8.1
3.1
9
3.1
10.2
3.6
10.5
3.1
12.4
1
1
1
1
1
1
1
2.8
8
2.8
9.1
2.8
10.1
3.1
11.5
3.1
13
3.6
13.4
3.1
15.7
1
1
1
1
1
--
1
0.4
1
0.4
1.1
0.4
1.3
0.6
1.4
0.6
1.6
---
0.6
2
SUMMER CONDITIONS (1)
Cooling capacity (1) kW
Compressors absorbed power kW
Nominal operating current Compressors A
PLANT SIDE HEAT EXCHANGER
REJECTION SIDE HEAT EXCHANGER
WINTER CONDITIONS (2)
Heating capacity (2) kW
Compressors absorbed power kW
Nominal operating current Compressors A
PLANT SIDE HEAT EXCHANGER
REJECTION SIDE HEAT EXCHANGER
PARTIAL HEAT RECOVERY (3)
COMPRESSORS
Quantity
Maximum operating current
Starting current
Number of capacity steps
PLANT SIDE HEAT EXCHANGER
n.
A
A
n.
n.
Water volume l
Maximum water flow m³/h
REJECTION SIDE HEAT EXCHANGER
n.
Water volume l
Maximum water flow m³/h
PARTIAL HEAT RECOVERY EXCHANGER
n.
Water volume l
Maximum water flow m³/h
REFRIGERANT
Total refrigerant load (excluding options) kg
Number of refrigerant circuits n.
SUPPLY VOLTAGE
ENERGY EFFICIENCY RATIOS
V/Ph/Hz
EER kW/kW
COP kW/kW
ESEER – Eurovent Standard
IPLV – ARI Standard 550/590
R410A
R410A
R410A
R410A
R410A
R410A
R410A
2.9
1
2.9
1
3
1
3.9
1
4.2
1
5
2
4.3
1
400/3/50
400/3/50
400/3/50
400/3/50
400/3/50
400/3/50
400/3/50
4.24
4.31
5.87
6.24
4.27
4.35
5.84
6.21
4.17
4.25
5.86
6.23
3.76
4.02
6.02
6.4
3.74
4.03
5.2
5.52
3.88
4.11
6.14
6.53
3.95
4.13
5.46
5.8
50
65.4
51
66.4
52
67.4
53
68.8
53
68.9
53
68.9
53
68.9
1000
650
1400
1000
650
1400
1000
650
1400
1000
650
1400
1200
750
1700
1200
750
1700
1200
750
1700
263
266
275
288
445
455
455
1 1/2"
-1"
1 1/2"
-1"
1 1/2"
-1"
2"
-1"
2"
-1"
2"
---
2"
-1"
SOUND LEVELS
Average sound pressure level [Lpm] (4) dB(A)
Sound power level (Lw) (5) dB(A)
DIMENSIONS
Length mm
Width mm
Height mm
NET WEIGHT
HYDRAULIC CONNECTIONS
kg
PLANT / REJECTION HEAT EXCHANGER
Inlet outlet diameter – ISO228/1-G M Ø
PARTIAL HEAT RECOVERY EXCHANGER Ø mm
Inlet outlet diameter – ISO228/1-G M Ø
(1) Gross value - chilled water temperature 12/7°C; 30/35°C on condenser.
(2) Gross value - hot water outlet temperature 45°C; chilled water outlet temperature 15/10°C.
(3) Gross value - chilled water temperature 12/7°C; 30/35°C on condenser and heat recovery
water temperature 40/45°C.
97
(4) Sound pressure level [Lpm] at 1m far according to ISO EN 3744
(5) Sound power level [Lw] according to ISO EN 9614-2.
➜
LIQUID CHILLERS | WATER-COOLED
EWMH 27 / 570 Reversible
TECHNICAL SPECIFICATIONS
SIZE
48.2
54.1
54.2
60.1
60.2
70.1
70.2
50.5
12.7
25.5
56.9
14.9
27.8
57.3
14.5
27.2
62.5
16.5
31.8
63.7
16.2
31.2
84.7
20.1
41.1
74.8
19.6
40.6
Water flow m³/h
Pressure loss kPa
8.7
29
9.8
50
9.8
28
10.7
43
10.9
28
14.5
50
12.8
28
Water flow m³/h
Pressure loss kPa
11
38
12.4
60
12.4
37
13.7
51
13.8
36
18.2
60
16.4
37
68
16.4
30.4
76.4
19.1
33.7
76.6
18.6
32.9
84
21.1
37.9
84.6
20.6
37.3
101
25.1
47.1
101
24.8
46.7
Water flow m³/h
Pressure loss kPa
8.7
20
9.8
32
9.8
20
10.7
27
10.9
20
14.5
40
12.8
19
Water flow m³/h
Pressure loss kPa
8.9
23
9.9
40
10
22
10.8
35
11
22
13.1
41
13.1
23
----
8.9
1.5
6.2
----
9.8
1.7
7.4
----
11.9
2
6.4
----
scroll
scroll
scroll
scroll
scroll
scroll
scroll
2
44
140
2
2
50
143
2
2
50
143
2
2
62
171
2
2
62
171
2
2
68
207
2
2
68
207
2
1
1
1
1
1
1
1
4.2
12.1
3.9
13.7
4.2
13.8
3.9
15
4.2
15.3
4.7
20.3
6.4
17.9
1
1
1
1
1
1
1
4.2
15.4
3.9
17.4
4.2
17.4
3.9
19.2
4.2
19.3
4.7
25.5
6.4
23
SUMMER CONDITIONS (1)
Cooling capacity (1) kW
Compressors absorbed power kW
Nominal operating current Compressors A
PLANT SIDE HEAT EXCHANGER
REJECTION SIDE HEAT EXCHANGER
WINTER CONDITIONS (2)
Heating capacity (2) kW
Compressors absorbed power kW
Nominal operating current Compressors A
PLANT SIDE HEAT EXCHANGER
REJECTION SIDE HEAT EXCHANGER
PARTIAL HEAT RECOVERY (3)
Heating capacity kW
Heat recovery exchanger water flow m³/h
Heat recovery pressure loss kPa
COMPRESSORS
Quantity
Maximum operating current
Starting current
Number of capacity steps
PLANT SIDE HEAT EXCHANGER
n.
A
A
n.
n.
Water volume l
Maximum water flow m³/h
REJECTION SIDE HEAT EXCHANGER
n.
Water volume l
Maximum water flow m³/h
PARTIAL HEAT RECOVERY EXCHANGER
n.
Water volume l
Maximum water flow m³/h
REFRIGERANT
Total refrigerant load (excluding options) kg
Number of refrigerant circuits n.
SUPPLY VOLTAGE
ENERGY EFFICIENCY RATIOS
V/Ph/Hz
EER kW/kW
COP kW/kW
ESEER – Eurovent Standard
IPLV – ARI Standard 550/590
--
1
--
1
--
1
--
---
0.8
2.2
---
0.8
2.4
---
1
2.9
---
R410A
R410A
R410A
R410A
R410A
R410A
R410A
5.7
2
5.7
1
5.7
2
5.8
1
5.7
2
6.6
1
8.1
2
400/3/50
400/3/50
400/3/50
400/3/50
400/3/50
400/3/50
400/3/50
3.98
4.15
6.43
6.84
3.82
4
5.38
5.72
3.95
4.12
6.15
6.54
3.79
3.98
5.09
5.41
3.93
4.11
5.79
6.15
4.21
4.02
5.45
5.79
3.82
4.07
6.3
6.7
53
68.9
54
69.9
54
69.9
55
70.9
55
70.9
56
71.9
56
71.9
1200
750
1700
1200
750
1700
1200
750
1700
1200
750
1700
1200
750
1700
1200
750
1700
1200
750
1700
470
465
480
470
495
475
506
2"
---
2"
-1"
2"
---
2"
-1"
2"
---
2"
-1"
2"
---
SOUND LEVELS
Average sound pressure level [Lpm] (4) dB(A)
Sound power level (Lw) (5) dB(A)
DIMENSIONS
Length mm
Width mm
Height mm
NET WEIGHT
HYDRAULIC CONNECTIONS
kg
PLANT / REJECTION HEAT EXCHANGER
Inlet outlet diameter – ISO228/1-G M Ø
PARTIAL HEAT RECOVERY EXCHANGER Ø mm
Inlet outlet diameter – ISO228/1-G M Ø
(1) Gross value - chilled water temperature 12/7°C; 30/35°C on condenser.
(2) Gross value - hot water outlet temperature 45°C; chilled water outlet temperature
15/10°C.
(3) Gross value - chilled water temperature 12/7°C; 30/35°C on condenser and heat recovery
water temperature 40/45°C.
98
90.1
90.2
120.1
120.2
150.1
150.2
170.2
190.2
200.1
200.2
220.1
220.2
96.9
25.7
47.5
98.2
25.1
46.7
122
32.6
60
119
31.9
59.3
158
41.5
74.1
154
40.8
73.6
194
45.4
88
206
53.3
94
207
52.4
93.7
220
52.3
93.6
262
61.1
110
250
63.9
119
16.6
46
16.8
29
20.9
48
20.5
38
27
46
26.4
42
33.3
43
35.4
34
35.6
46
37.7
53
45
52
42.9
61
21.2
52
21.3
36
26.7
53
26.2
47
34.5
45
33.8
47
41.5
69
45
42
45
62
47.1
71
55.9
68
54.3
81
132
32.5
55.6
132
31.7
54.5
165
40.9
69.3
164
40.3
68.5
213
52
87.8
211
51.6
87.3
237
58.1
105
262
69.7
113
275
64.7
110
276
64.2
109
332
76.8
130
335
80.4
137
16.6
27
16.8
19
20.9
28
20.5
24
27
24
26.4
24
33.3
58
35.4
76
35.6
37
37.7
43
45
46
42.9
44
17.1
37
17.3
23
21.4
39
21.2
31
27.8
38
27.4
33
30.9
45
33.2
28
36.2
43
36.4
44
43.9
49
43.8
50
15.5
2.7
6.3
----
19.4
3.3
6.9
----
25.2
4.3
8.9
24.9
4.3
7
28
4.8
8.9
30.1
5.2
6
32.9
5.7
9
33
5.7
7.2
39.8
6.9
9.4
39.7
6.8
7.2
scroll
scroll
scroll
scroll
scroll
scroll
scroll
scroll
scroll
scroll
scroll
scroll
2
80
265
2
2
80
265
2
2
97
321
2
2
97
321
2
2
131
375
2
2
131
375
2
4
148
333
4
4
160
345
4
2
164
466
2
2
164
466
2
3
197
441
3
4
246
584
4
1
1
1
1
1
1
1
1
1
1
1
1
5.8
23.2
6.7
23.5
7.2
29.3
8.3
28.7
8.7
37.8
12.3
37
12.3
46.6
20.3
49.6
20.7
49.8
20.3
52.8
20.7
63
20.3
60.1
1
1
1
1
1
1
1
1
1
1
1
1
5.8
29.7
6.7
29.8
7.2
37.4
8.3
36.7
8.7
48.3
12.3
47.3
12.3
58.1
20.3
63
20.7
63
20.3
65.9
20.7
78.3
20.3
76
1
--
1
--
1
2
2
2
1
2
1
2
1.7
3.7
---
2.1
4.7
---
4
6.1
2
6
3.4
6.7
3.4
7.3
5.3
7.9
3.4
8
6.3
9.6
4.2
9.6
R410A
R410A
R410A
R410A
R410A
R410A
R410A
R410A
R410A
R410A
R410A
R410A
8.7
1
10.4
2
10.7
1
12.7
2
12.4
1
17
2
17.8
2
23.9
2
22.4
1
22.8
2
23.1
1
24.7
2
400/3/50
400/3/50
400/3/50
400/3/50
400/3/50
400/3/50
400/3/50
400/3/50
400/3/50
400/3/50
400/3/50
400/3/50
3.77
4.06
5.2
5.52
3.91
4.16
5.96
6.34
3.74
4.03
5.13
5.46
3.73
4.07
5.99
6.37
3.81
4.1
5.1
5.42
3.77
4.09
6
6.38
4.27
4.08
5.46
5.62
3.86
3.76
6.63
6.43
3.95
4.25
5.17
5.5
4.21
4.3
6.01
6.39
4.29
4.32
6.37
6.77
3.91
4.17
5.53
5.87
61
76.9
61
76.9
64
80.1
64
80.1
64
81
64
81
64
81
64
81
64
81
64
81
65.8
82.8
67
84.1
1200
750
1700
1200
750
1700
1200
750
1700
1200
750
1700
1800
1200
1740
1800
1200
1740
1800
1200
1740
1800
1200
1740
1800
1200
1740
1800
1200
1740
1800
1200
1740
1800
1200
1740
730
770
785
800
1035
1040
1140
1345
1100
1135
1310
1570
-73.1
1 1/4"
-73.1
--
-73.1
1 1/4"
-73.1
--
-73.1
2"
-73.1
2 x 1"
-73.1
2 x 1 1/4"
-88.9
2 x 1 1/4"
-88.9
2"
-88.9
2 x 1 1/4"
-88.9
2"
-88.9
2 x 1 1/4"
➜
(4) Sound pressure level [Lpm] at 1m far according to ISO EN 3744.
(5) Sound power level [Lw] according to ISO EN 9614-2.
99
LIQUID CHILLERS | WATER-COOLED
EWMH 27 / 570 Reversible
TECHNICAL SPECIFICATIONS
SIZE
290.1
300.2
340.2
380.2
460.2
570.2
328
78.3
140
313
81.8
147
364
93.4
168
405
104
187
482
121
219
606
158
282
Water flow m³/h
Pressure loss kPa
56.3
49
53.7
70
62.6
70
69.5
64
82.7
63
104
85
Water flow m³/h
Pressure loss kPa
70.3
60
68.4
89
79.3
86
88.2
74
105
64
132
83
413
96.4
164
420
103
175
488
116
197
539
129
220
646
130
260
817
196
333
Water flow m³/h
Pressure loss kPa
56.3
40
53.7
48
62.6
46
69.5
40
82.7
34
104
44
Water flow m³/h
Pressure loss kPa
54.5
46
54.6
57
63.9
57
70.5
53
88.9
52
107
69
Heating capacity kW
Heat recovery exchanger water flow m³/h
Heat recovery pressure loss kPa
49.4
8.5
9.1
49.5
8.5
8.6
57.9
10
11.8
63.9
11
8.5
80.6
13.9
9.6
96.9
16.7
8.7
SUMMER CONDITIONS (1)
Cooling capacity (1) kW
Compressors absorbed power kW
Nominal operating current Compressors A
PLANT SIDE HEAT EXCHANGER
REJECTION SIDE HEAT EXCHANGER
WINTER CONDITIONS (2)
Heating capacity (2) kW
Compressors absorbed power kW
Nominal operating current Compressors A
PLANT SIDE HEAT EXCHANGER
REJECTION SIDE HEAT EXCHANGER
PARTIAL HEAT RECOVERY (3)
COMPRESSORS
Quantity
Maximum operating current
Starting current
Number of capacity steps
PLANT SIDE HEAT EXCHANGER
n.
A
A
n.
n.
Water volume l
Maximum water flow m³/h
REJECTION SIDE HEAT EXCHANGER
n.
Water volume l
Maximum water flow m³/h
PARTIAL HEAT RECOVERY EXCHANGER
n.
Water volume l
Maximum water flow m³/h
REFRIGERANT
scroll
scroll
scroll
scroll
scroll
4
262
507
4
4
295
597
4
4
328
630
4
6
393
637
6
6
492
794
6
1
1
1
1
1
1
27
78.8
27.5
75.2
33.8
87.6
44.6
97.3
44.6
115.8
57.2
145.6
1
1
1
1
1
1
27
98.4
27.5
95.8
33.8
111
44.6
123.5
44.6
147
57.2
184.8
1
2
2
2
2
2
8
11.9
8
11.9
8
14
10.6
15.4
12.6
19.5
16
23.4
R410A
R410A
R410A
R410A
R410A
R410A
30.3
1
31.6
2
31.1
2
48.1
2
49.5
2
62.4
2
400/3/50
400/3/50
400/3/50
400/3/50
400/3/50
400/3/50
4.19
4.28
6.23
6.62
3.83
4.08
5.65
6.01
3.9
4.21
5.75
6.12
3.89
4.18
5.66
6.02
3.98
4.97
6
6.38
3.84
4.17
5.93
6.31
65.8
82.8
67
84.1
67
84.5
67
84.5
68.8
86.3
68.8
86.3
Length mm
Width mm
Height mm
1800
1200
1740
1800
1200
1740
1800
1800
1740
1800
1800
1740
1800
1800
1740
1800
1800
1740
kg
1390
1615
1710
1796
2270
2365
-88.9
2"
-88.9
2 x 2"
-88.9
2 x 2"
-88.9
2 x 2"
-88.9
2 x 2"
-88.9
2 x 2"
Total refrigerant load (excluding options) kg
Number of refrigerant circuits n.
SUPPLY VOLTAGE
ENERGY EFFICIENCY RATIOS
scroll
3
194
418
3
V/Ph/Hz
EER kW/kW
COP kW/kW
ESEER – Eurovent Standard
IPLV – ARI Standard 550/590
SOUND LEVELS
Average sound pressure level [Lpm] (4) dB(A)
Sound power level (Lw) (5) dB(A)
DIMENSIONS
NET WEIGHT
HYDRAULIC CONNECTIONS
PLANT / REJECTION HEAT EXCHANGER
Inlet outlet diameter – ISO228/1-G M Ø
PARTIAL HEAT RECOVERY EXCHANGER Ø mm
Inlet outlet diameter – ISO228/1-G M Ø
(1) Gross value - chilled water temperature 12/7°C; 30/35°C on condenser.
(2) Gross value - hot water outlet temperature 45°C; chilled water outlet temperature
15/10°C.
(3) Gross value - chilled water temperature 12/7°C; 30/35°C on condenser and heat recovery
water temperature 40/45°C.
(4) Sound pressure level [Lpm] at 1m far according to ISO EN 3744
(5) Sound power level [Lw] according to ISO EN 9614-2.
100
LIQUID CHILLERS | WATER-COOLED
EWML RC
27 / 570
Cooling only
SCROLL COMPRESSORS
REMOTE CONDENSER
Cooling capacities from 23 to 670 kW
33 sizes
Refrigerant: R410A
EER up to 4.40
ESEER up to 6.51
MAIN FEATURES
Remote condenser
Scroll compressors
Brazed-plate evaporator
Main accessories and options
AVAILABLE VERSIONS
Mono or twin circuit units
Partial heat recovery
Heat pump reversible on the refrigeration circuit
(see EWMH range)
Remote condenser heat pump
(see range EWMH RC)
Leaving water low temperature version
Total heat recovery
Advantages
Universal communication electronic control system, easy
to read and easy access to information
Electronic expansion valve as standard
Service valves on discharge and liquid line
Code
118
119
172
175
178
450
451
605
919
923
926
931
932
942
943
Kit A leaving chilled water low temperature operation
Kit B leaving chilled water low temperature operation
Antivibration mounts - rubber - supplied loose
Victaulic connections
HR 100% Victaulic connections
Desuperheater
Total heat recovery
Power factor capacitor for cos phi 0.9 on compressor motor
Clock card
COM MBUS/JBUS serial card
LON serial card
BACnet Ethernet - SNMP - TCP/IP serial card
BACnet MS/TP serial card
Serial card for GSM modem
Data logger
Besides these options, please speak to our Sales Department for any other
configuration or function that is not listed as being available.
FOR THE TECHNICAL SPECIFICATIONS SEE EWML
ON PAGE 91; FOR THE PERFORMANCES SEE
SELECTION SOFTWARE
101
LIQUID CHILLERS | WATER-COOLED
EWMH RC
27 / 380
Reversible
SCROLL COMPRESSORS
REMOTE CONDENSER
Cooling capacities from 23 to 670 kW
Heating capacities from 27 to 828 kW
28 sizes
Refrigerant: R410A
EER up to 4.29
ESEER up to 6.63
COP up to 4.35
MAIN FEATURES
Heat pump (reversible refrigerant circuit circuit)
Remote condenser
Scroll compressors
Brazed-plate evaporator
AVAILABLE VERSIONS
Mono or twin circuit units
Partial heat recovery
Cooling only (see EWML range)
Remote condenser cooling only
(see EWML RC range)
Heat pump (see EWMH range)
Leaving water low temperature version
Main accessories and options
Code
118
119
172
174
450
605
919
923
926
931
932
942
943
Kit A leaving chilled water low temperature operation
Kit B leaving chilled water low temperature operation
Antivibration mounts - rubber - supplied loose
EVP Victaulic connections
Desuperheater
Power factor capacitor for cos phi 0.9 on compressor motor
Clock card
COM MBUS/JBUS serial card
LON serial card
BACnet Ethernet - SNMP - TCP/IP serial card
BACnet MS/TP serial card
Serial card for GSM modem
Data logger
Main assets
Remote condenser
Universal communication electronic control system, easy
to read and easy access to information
Electronic expansion valve as standard
Service valves on discharge and liquid line
Besides these options, please speak to our Sales Department for any other
configuration or function that is not listed as being available.
FOR THE TECHNICAL SPECIFICATIONS SEE EWMH
ON PAGE 97; FOR THE PERFORMANCES SEE
SELECTION SOFTWARE
102
LIQUID CHILLERS | WATER-COOLED
EWSL K
190 / 660
Cooling only
SCREW COMPRESSORS
Cooling capacities from 186 to 655 kW
13 sizes
Refrigerant: R134a
EER up to 4.76
ESEER up to 5.25
MAIN FEATURES
Class B
MONO SCREW compressor
Brazed-plate evaporator
Brazed-plate condenser
Linear capacity modulation 25 …100%
Main accessories and options
Code
118
119
171
550
919
923
926
931
932
942
943
AVAILABLE VERSIONS
Leaving water low temperature version
Advantages
Plug and play, reliable and robust
Evaporator water outlet down to -12°C
Universal communication electronic control system, easy
to read and easy access to information
Electronic expansion valve as standard
Input port on additonal control module (optional) for
ambient air temperature
Service valves on discharge and liquid lines
Wide operating limits
Besides these options, please speak to our Sales Department for any other
configuration or function that is not listed as being available.
Cooling/heating operating limits
(°C)
20
15
Evaporator water
outlet temperature
Indicative values. The operating T° are influenced by
a series of settings such as: operating conditions,
thermal load, adjustments, etc... Data to be
confirmed upon selection.
Kit A leaving chilled water low temperature operation
Kit B leaving chilled water low temperature operation
Antivibration mounts - rubber - supplied loose
Stop valve on compressor suction line
Clock card
COM MBUS/JBUS serial card
LON serial card
BACnet Ethernet - SNMP - TCP/IP serial card
BACnet MS/TP serial card
Serial card for GSM modem
Data logger
10
5
0
Glycol solution
+ low temperature kit A
-5
Glycol solution
+ low temperature kit B
-10
-13
15
20
25
30
35
40
45
50
Water outlet temperature from the condenser
103
55
60
65 (°C)
LIQUID CHILLERS | WATER-COOLED
EWSL K 190 / 660 Cooling only
SIZE
Cooling capacity (1) kW
Compressors absorbed power kW
Nominal operating current Compressors A
TECHNICAL SPECIFICATIONS
190.1
210.1
240.1
250.1
270.1
310.1
360.1
410.1
470.1
500.1
530.1
580.1
660.1
186
207
231
249
263
306
353
410
463
491
525
579
655
39.1
43.5
48.7
52.3
55.7
65
74.7
86.8
98.7
106
111
123
138
66
69.8
80.3
90.4
90.6
109
128
139
159
167
180
201
225
EVAPORATOR
Evaporator water flow m³/h
Evaporator pressure loss kPa
31.9
35.5
39.6
42.7
45.1
52.5
60.6
70.3
79.4
84.2
90.1
99.3
112
18
22
20
18
27
31
32
33
35
32
31
28
19
CONDENSER
Condenser water flow m³/h
Condenser pressure loss kPa
39
43.4
48.4
52.2
55.2
63
74
84
95
103
110
122
137
6
5
5
5
7
7
8
8
10
11
11
9
9
Twin
Twin
Twin
Twin
Twin
Twin
Twin
Twin
Twin
Twin
Twin
Twin
Twin
screw screw screw screw screw screw screw screw screw screw screw screw screw
COMPRESSORS
Quantity n.
Maximum operating current A
Starting current A
Number of capacity steps %
EVAPORATOR
n.
Water volume l
Maximum water flow m³/h
CONDENSER
n.
Water volume l
Maximum water flow m³/h
REFRIGERANT
Total refrigerant load (excluding options) kg
Number of refrigerant circuits n.
V/Ph/
Hz
SUPPLY VOLTAGE
1
1
1
1
1
1
1
1
1
1
1
1
1
102.5
117.8
134.8
144.1
165.2
183.4
207
237.1
267.9
283.7
307.7
354.8
398.8
280
351
495
495
646
361
361
374
453
543
595
703
783
50…100
50…100
50…100
50…100
50…100
50…100
50…100
50…100
50…100
50…100
50…100
50…100
50…100
1
1
1
1
1
1
2
2
2
2
2
2
2
14
16
18
20
23
29
2x31
2x36
2x40
2x40
2x45
2x54
2x67
32
37
42
47
53
68
74
84
95
95
105
126
158
1
1
1
1
1
1
2
2
2
2
2
2
2
25
27
29
29
25
27
2x31
2x36
2x40
2x45
2x49
2x54
2x58
58
63
68
68
58
63
74
84
95
105
116
126
137
R134a
R134a
R134a
R134a
R134a
R134a
R134a
R134a
R134a
R134a
R134a
R134a
R134a
15
16
17
17
15
16
37
42
48
53
58
64
69
1
1
1
1
1
1
1
1
1
1
1
1
1
400/3/
50
400/3/
50
400/3/
50
400/3/
50
400/3/
50
400/3/
50
400/3/
50
400/3/
50
400/3/
50
400/3/
50
400/3/
50
400/3/
50
400/3/
50
4.75
ENERGY EFFICIENCY RATIOS (1)
4.76
4.76
4.74
4.76
4.72
4.71
4.73
4.72
4.69
4.63
4.73
4.71
ESEER - Eurovent Standard
5.09
5.25
5.2
5.07
4.99
5.1
5.09
5.07
5
5.04
5.18
5.17
5.19
IPLV - ARI Standard 550/590
5.23
5.4
5.35
5.21
5.28
5.39
5.38
5.36
5.35
5.44
5.56
5.56
5.57
EER kW/kW
SOUND LEVELS
Average sound pressure level [Lpm] (2) dB(A)
Sound power level (Lw) (3) dB(A)
71
72
76
76
76
79
80
80
79
81
81
82
82
88.1
89.1
93.1
93.1
93.1
96.1
97.4
97.4
96.4
98.4
98.4
99.6
99.6
DIMENSIONS
Length mm
2500
2500
2500
2500
2500
2500
2800
2800
2800
2800
2800
3100
3100
Width mm
600
600
600
600
600
600
700
700
700
700
700
700
700
Height mm
1790
1790
1790
1790
1790
1790
1790
1790
1790
1790
1790
1790
1790
1399
1423
1465
1476
1689
1733
1750
2117
2151
2177
2233
2616
2663
88.9
88.9
88.9
88.9
88.9
88.9
2x88.9
2x88.9
2x88.9
2x88.9
2x88.9
2x88.9
2x88.9
88.9
88.9
88.9
88.9
88.9
88.9
2x88.9
2x88.9
2x88.9
2x88.9
2x88.9
2x88.9
2x88.9
NET WEIGHT
kg
HYDRAULIC CONNECTIONS
EVAPORATOR
Inlet outlet diameter nxØ mm
CONDENSER
Inlet outlet diameter nxØ mm
(1) Gross value - chilled water temperature 12/7°C; 30/35°C on condenser
(2) Sound pressure level [Lpm] at 1m far according to ISO EN 3744
(3) Sound power level [Lw] according to ISO EN 9614-2.
104
LIQUID CHILLERS | WATER-COOLED
EWSL A
410 / 1610
Class A
Cooling only
SCREW COMPRESSORS
CLASS A
Cooling capacities from 406 to 1604 kW
14 sizes
Refrigerant: R134 A
EER up to 5.12
ESEER up to 5.72
MAIN FEATURES
Class A
SCREW compressers
High efficiency shell and tube evaporator
High efficiency shell and tube condenser
Linear capacity modulation 25 …100%
2 refrigeration circuits
Main accessories and options
Code
118
119
171
450
550
731
780
919
923
926
931
932
942
943
AVAILABLE VERSIONS
Leaving water low temperature version
Partial heat recovery
Advantages
Class A
2 refrigeration circuits
Plug and play, reliable and robust
Evaporator water outlet down to -11°C
Universal communication electronic control system, easy
to read and easy access to information
Electronic expansion valve as standard
Input port on additonal control module (optional) for
ambient air temperature
Service valves on discharge and liquid line
Wide operating limits
Indicative values. The operating T° are influenced
by a series of settings such as: operating
conditions, thermal load, adjustments, etc... Data
to be confirmed upon selection
Besides these options, please speak to our Sales Department for any other
configuration or function that is not listed as being available.
(°C)
20
15
Evaporator water
outlet temperature
Cooling operating limits
Kit A leaving chilled water low temperature operation
Kit B leaving chilled water low temperature operation
Antivibration mounts - rubber - supplied loose
Desuperheater
Stop valve on compressor suction line
Water flow switch
Sound-insulating casing
Clock card
COM MBUS/JBUS serial card
LON serial card
BACnet Ethernet - SNMP - TCP/IP serial card
BACnet MS/TP serial card
Serial card for GSM modem
Data logger
10
5
0
Glycol solution
+ low temperature kit A
-5
Glycol solution
+ low temperature kit B
-10
-13
15
20
25
30
35
40
45
Water outlet temperature from the condenser
105
50
55 (°C)
LIQUID CHILLERS | WATER-COOLED
EWSL A 410 / 1610 Cooling only
TECHNICAL SPECIFICATIONS
SIZE
510
410
460
540
610
700
790
940
1050
1110
1140
1310
1460
1610
COOLING ONLY
Cooling capacity (1) kW
408
458
507
540
607
701
790
932
1041
1105
1139
1304
1453
1604
Compressors absorbed power kW
80.6
90.2
99.9
106
120
137
156
184
206
217
224
256
286
317
134
142
162
181
194
230
264
290
326
340
359
415
455
504
Nominal operating current
Compressors
A
EVAPORATOR
Evaporator water flow m³/h
Evaporator pressure loss kPa
70
78.6
87
92.6
104
120
136
160
179
190
195
224
249
275
12
18
19
21
24
16
13
19
26
27
23
28
36
45
CONDENSER
Condenser water flow m³/h
Condenser pressure loss kPa
84.6
94.9
105
112
126
145
164
193
216
229
236
270
301
333
10
13
16
1
22
21
25
19
21
25
23
19
19
22
PARTIAL HEAT RECOVERY (2)
Heating capacity kW
Heat recovery exchanger water flow m³/h
Heat recovery pressure loss kPa
53
59.5
65.9
70.2
78.9
91.1
103
121
135
144
148
170
189
209
9.1
10.3
11.3
12.1
13.6
15.7
17.7
20.9
23.3
24.8
25.5
29.2
32.5
35.9
4.6
4.2
3.7
3.5
3.3
3.4
3.8
4.6
5.2
7.2
8.3
10.9
13.5
16.5
twintwintwintwintwintwintwintwintwintwintwintwintwintwinscrew screw screw screw screw screw screw screw screw screw screw screw screw screw
COMPRESSORS
Quantity n.
Maximum operating current A
Starting current A
Number of capacity steps
EVAPORATOR
n.
Water volume l
Maximum water flow m³/h
CONDENSER
n.
Water volume l
Maximum water flow m³/h
HEATING PARTIAL HEAT
RECOVERY EXCHANGER
n.
Water volume l
Maximum water flow m³/h
REFRIGERANT
Total refrigerant load
(excluding options)
kg
Number of refrigerant circuits n.
V/Ph/
Hz
SUPPLY VOLTAGE
2
2
2
2
2
2
2
2
2
2
2
2
2
2
185.8
194.4
219.6
238.4
271.8
310.8
347.8
391.4
441.8
466.2
497.2
569.6
640.6
713.6
354.9
377.2
460.8
614.2
359.9
435.4
453.9
549.7
594.9
686.1
791.6
835.8
1023.3
1147.8
25...100
25...100
25...100
25...100
25...100
25...100
25...100
25...100
25...100
25...100
25...100
25...100
25...100
25...100
1
1
1
1
1
1
1
1
1
1
1
1
1
1
149
142
255
255
255
255
237
229
276
276
370
368
357
431
95
100
127
127
127
127
154
172
172
172
220
245
267
312
2
2
2
2
2
2
2
2
2
2
2
2
2
2
78
78
99
99
99
99
109
109
135
135
155
171
182
210
98
98
116
116
116
116
170
186
216
216
240
260
284
320
2
2
2
2
2
2
2
2
2
2
2
2
2
2
14.4
14.4
19.2
19.2
19.2
27
37
32
34
34
39
39
54
54
37
37
37
37
37
37
37
67
67
67
67
67
67
67
R134a
R134a
R134a
R134a
R134a
R134a
R134a
R134a
R134a
R134a
R134a
R134a
R134a
R134a
65
65
155
155
155
155
142
136
130
130
121
180
176
172
2
2
2
2
2
2
2
2
2
2
2
2
2
2
400/3/
50
400/3/
50
400/3/
50
400/3/
50
400/3/
50
400/3/
50
400/3/
50
400/3/
50
400/3/
50
400/3/
50
400/3/
50
400/3/
50
400/3/
50
400/3/
50
ENERGY EFFICIENCY RATIOS
5.06
5.08
5.08
5.09
5.06
5.12
5.06
5.07
5.05
5.09
5.08
5.09
5.08
5.06
ESEER – Eurovent Standard
5.41
5.34
5.68
5.72
5.12
5.19
5.16
5.08
5.06
5.16
5.04
5.04
5.1
4.99
IPLV – ARI Standard 550/590
5.72
5.42
5.77
6.04
5.44
5.51
5.49
5.37
5.34
5.46
5.17
5.18
5.24
5.12
EER kW/kW
SOUND LEVELS
Average sound pressure level [Lpm] (3) dB(A)
Sound power level (Lw) (4) dB(A)
74
74
74
79
79
79
82
82
82
82
82
84
84
84
91.8
91.8
91.8
96.8
96.8
97.6
100.6
100.6
101.2
101.2
101.2
103.6
103.6
103.6
DIMENSIONS
Length mm
3359.5
3359.5
3349.5
3349.5
3435
3514
3894
3894
3894
3932.5
3874
4273
4273
4352
Width mm
975
975
1013
1013
1007
1060
1210
1210
1210
1218
1287
1284
1284
1284
Height mm
1498
1498
1618
1618
1740
1780
1888
1888
1888
1890
1975
2084
2084
2108
3237
3268
3498
3590
3720
3967
4071
4835
4949
5031
5549
6407
6537
6814
Inlet outlet diameter Ømm
168.3
168.3
168.3
168.3
168.3
168.3
219.1
219.1
219.1
219.1
219.1
219.1
273
273
Inlet outlet diameter – (ISO228/1) n x Ø
2 x 3"
2 x 3"
2 x 3"
2 x 3"
2 x 3"
2 x 3"
2 x 3"
2 x 3"
2 x 3"
2 x 3"
--
--
--
--
--
--
--
--
--
--
--
--
--
--
2 x 114.3
2 x 114.3
2 x 114.3
2 x 141.3
2 x 2"
2 x 2"
2 x 2"
2 x 2"
2 x 2"
2 x 2"
2 x 2"
2 x 2"
2 x 2"
2 x 2"
2 x 2"
2 x 2"
2 x 2"
2 x 2"
NET WEIGHT
kg
HYDRAULIC CONNECTIONS
EVAPORATOR
CONDENSER
Inlet outlet diameter
nx
Ømm
PARTIAL HEAT RECOVERY
EXCHANGER
Inlet outlet diameter – ISO228/
(ISO228/1)
nxØ
(1) Gross value - chilled water temperature 12/7°C; 30/35°C on condenser.
(2) Gross value - chilled water temperature 12/7°C; 30/35°C on condenser and heat
recovery water temperature 40/45°C.
(3) Sound pressure level [Lpm] at 1m far according to ISO EN 3744
(4) Sound power level [Lw] according to ISO EN 9614-2.
106
LIQUID CHILLERS | WATER-COOLED
EWSL A+
620 / 1180
Class A+
Cooling only
SCREW COMPRESSORS
CLASS A+
Cooling capacities from 620 to 1160 kW
7 sizes
Refrigerant: R134a
EER up to 5.61
ESEER up to 6.55
MAIN FEATURES
Class A+
SCREW compressers
High efficiency shell and tube evaporator
High efficiency shell and tube condenser
Linear capacity modulation 25 …100%
2 refrigeration circuits
Main accessories and options
Code
118
119
171
450
550
731
780
919
923
926
931
932
942
943
AVAILABLE VERSIONS
Leaving water low temperature version
Partial heat recovery
Advantages
Class A+
Very high level of energy efficiency
2 refrigeration circuits
Plug and play, reliable and robust
Evaporator water outlet down to -11°C
Universal communication electronic control system, easy
to read and easy access to information
Electronic expansion valve as standard
Input port on additonal control module (optional) for
ambient air temperature
Service valves on discharge and liquid line
Wide operating limits
Besides these options, please speak to our Sales Department for any other
configuration or function that is not listed as being available.
(°C)
Cooling operating limits
20
15
Evaporator water
outlet temperature
Indicative values. The operating T° are influenced by
a series of settings such as: operating conditions,
thermal load, adjustments, etc... Data to be
confirmed upon selection.
Kit A leaving chilled water low temperature operation
Kit B leaving chilled water low temperature operation
Antivibration mounts - rubber - supplied loose
Desuperheater
Stop valve on compressor suction line
Water flow switch
Sound-insulating casing
Clock card
COM MBUS/JBUS serial card
LON serial card
BACnet Ethernet - SNMP - TCP/IP serial card
BACnet MS/TP serial card
Serial card for GSM modem
Data logger
10
5
0
Glycol solution
+ low temperature kit A
-5
Glycol solution
+ low temperature kit B
-10
-13
15
20
25
30
35
40
45
Water outlet temperature from the condenser
107
50
55 (°C)
LIQUID CHILLERS | WATER-COOLED
EWSL A+ 620 / 1180 Cooling only
TECHNICAL SPECIFICATIONS
SIZE
620
720
820
970
1080
1150
1180
Cooling capacity kW
623
717
813
961
1064
1123
1160
Compressors absorbed power kW
111
131
147
175
197
208
214
179
218
251
277
317
328
347
107
123
140
165
183
193
199
11
16
25
15
20
22
25
127
147
166
197
218
230
238
22
4
40
55
8
5
4
81.1
93.2
106
125
138
146
151
14
16
18.2
21.5
23.8
25.1
26
3.4
3.5
4
4.9
5.4
7.4
8.6
twinscrew
twinscrew
twinscrew
twinscrew
twinscrew
twinscrew
twinscrew
COOLING ONLY (1)
Nominal operating current Compressors A
EVAPORATOR
Evaporator water flow m³/h
Evaporator pressure loss kPa
CONDENSER
Condenser water flow m³/h
Condenser pressure loss kPa
PARTIAL HEAT RECOVERY (2)
Heating capacity kW
Heat recovery exchanger water flow m³/h
Heat recovery pressure loss kPa
COMPRESSORS
2
2
2
2
2
2
2
Maximum operating current A
Quantity n.
272
311
348
391
442
466
497
Starting current A
360
435
454
550
595
686
792
25 ...100
25 ...100
25 ...100
25 ...100
25 ...100
25 ...100
25 ...100
1
1
1
1
1
1
1
382
359
348
425
625
724
724
Number of capacity steps %
EVAPORATOR
n.
Water volume l
Maximum water flow m³/h
CONDENSER
n.
Water volume l
Maximum water flow m³/h
PARTIAL HEAT RECOVERY EXCHANGER
n.
Water volume l
Maximum water flow m³/h
REFRIGERANT
Total refrigerant load (excluding options) kg
Number of refrigerant circuits n.
SUPPLY VOLTAGE
V/Ph/Hz
208
241
265
385
407
440
440
2
2
2
2
2
2
2
267
213
297
342
297
342
366
204
204
252
326
326
362
362
2
2
2
2
2
2
2
19.2
27
37
32
34
34
39
37
37
37
67
67
67
67
R134a
R134a
R134a
R134a
R134a
R134a
R134a
171
171
156
216
216
211
211
2
2
2
2
2
2
2
400/3/50
400/3/50
400/3/50
400/3/50
400/3/50
400/3/50
400/3/50
ENERGY EFFICIENCY RATIOS
5.61
5.47
5.53
5.49
5.4
5.4
5.42
ESEER - Eurovent Standard
EER kW/kW
6.14
6.18
6.16
6.1
6.13
6.18
5.98
IPLV - ARI Standard 550/590
6.55
6.53
6.54
6.46
6.45
6.52
6.2
79
79
82
82
82
82
82
96.8
96.8
97.6
97.6
97.6
98.2
98.2
Length mm
3514
3514
3982
3818
3818
3818
3818
Width mm
1060
1060
1057.5
1269
1269
1269
1269
Height mm
1770
1770
1770
1991
1991
1991
1991
kg
4009
4051
4325
5439
5459
5565
5649
168.3
219.1
219.1
219.1
219.1
219.1
273
3"
3"
3"
--
--
--
--
--
--
--
114.3
114.3
114.3
114.3
2 x 2"
2 x 2"
2 x 2"
2 x 2"
2 x 2"
2 x 2"
2 x 2"
SOUND LEVELS
Average sound pressure level [Lpm] (3) dB(A)
Sound power level (Lw) (4) dB(A)
DIMENSIONS
NET WEIGHT
HYDRAULIC CONNECTIONS
EVAPORATOR
Inlet outlet diameter Ømm
CONDENSER
Inlet outlet diameter – (ISO228/1) Ø
Inlet outlet diameter Ømm
PARTIAL HEAT RECOVERY EXCHANGER
Inlet outlet diameter – ISO228/ (ISO228/1) n x Ø
(1) Gross value - chilled water temperature 12/7°C; 30/35°C on condenser.
(2) Gross value - chilled water temperature 12/7°C; 30/35°C on condenser and heat
recovery water temperature 40/45°C.
(3) Sound pressure level [Lpm] at 1m far according to ISO EN 3744
(4) Sound power level [Lw] according to ISO EN 9614-2.
108
CHILLED WATER
TERMINAL UNITS
109
CHILLED WATER TERMINAL UNITS | FAN COIL
FCW
Concealed
FCCW
Cabinet fitted
MAIN FEATURES
Cooling capacities between 0.9 and 11 kW
Can be combined with the entire range of
KRONO and ADVANCE liquid chillers.
Horizontal or vertical configuration
Cabinet fitted or concealed version
4 installation options:
- FCW 3R: concealed with 2 pipes
- FCCW 3R: cabinet fitted with 2 pipes
- FCW 3R+1: concealed with 4 pipes
- FCCW 3R+1: cabinet fitted with 4 pipes
Different options for air intake or air discharge:
- FCCW: version V vertical
- FCCW: version H horizontal
- FCW: version V vertical
- FCW: version H horizontal
Advantages
Options
Water terminal units for the hotel and offices sector.
The FCW-FCCW is a terminal unit equipped with centrifugal fan.
It features a modern design and can be installed in any
environment.
ENERGY EFFICIENCY
Brushless DC motor
UNIT INSTALLATION
High pressure motors to 60 Pa
3-way valve for 2-pipe model
Shut-off valve and control valve for 2-pipe model
3-way valve for 4-pipe model
Shut-off valve and control valve for 4-pipe model
Secondary condensate tray
Support base
CONTROLS
Electronic thermostat
For the functions, see the
"Controls" section on page 216
Besides these options, please speak to our Sales Department for any other
configuration or function that is not listed as being available.
Air inlet/outlet configuration options
110
FCW 3R / FCCW 3R (2 pipes) TECHNICAL SPECIFICATIONS
10
15
20
25
30
40
kW
kW
T.R.
kW
kW
kW
W
V
m3/h
m3/h
l/h
Ø (")
dB(A)
dB(A)
kg
mm
0.9
0.9
0.2
1.3
1.6
2.2
30
230.1
227
277
148
3/4
37
50
15.6
480x660x225
1.3
1.7
0.4
1.9
2.3
3.2
30
230.1
289
410
220
3/4
36
56
18.9
480x860x225
2.2
2.5
0.6
2.6
3.0
4.4
40
230.1
404
533
373
3/4
35
50
23.7
480x1060x225
2.5
2.8
0.7
3.3
3.6
5.5
50
230.1
453
530
435
3/4
38
52
23.9
480x1060x225
3.1
3.9
0.9
3.7
4.4
6.2
60
230.1
575
811
535
3/4
38
56
27.7
480x1260x225
3.5
4.4
1.0
4.5
4.9
7.5
80
230.1
685
815
662
3/4
43
57
27.9
480x1260x225
50
60
70
80
100
110
kW
kW
T.R.
kW
kW
kW
W
V
m3/h
m3/h
l/h
Ø (")
dB(A)
dB(A)
kg
mm
4.1
5.4
1.2
5.1
5.8
8.6
70
230.1
708
864
745
3/4
43
58
32.7
585x1260x225
5.6
7.2
1.6
6.7
8.2
11.3
160
230.1
1058
1513
961
3/4
49
68
38.0
585x1460x225
6.9
7.5
2.0
8.1
8.7
13.7
180
230.1
1242
1416
1187
3/4
55
68
38.5
585x1460x225
8.0
8.7
2.3
10.1
10.9
16.9
213
230.1
1356
1505
1376
3/4
54
66
50.0
602x1660x257
10.0
2.8
13.1
22.0
277
230.1
2012
1727
3/4
58
58.5
602x1960x257
11.0
3.1
13.3
23.8
273
230.1
2003
1898
3/4
57
59.0
602x1960x257
MODEL
Water cooling capacity
Water cooling capacity (*)
Water cooling capacity
Water heating capacity 50ºC
Water heating capacity 50ºC (*)
Water heating capacity 70/60ºC
Absorbed power
Power supply (50 Hz ~)
Air flow (1)
Air flow (*)
Water flow
Water connections
Sound pressure (2)
Sound pressure (2) (*)
Weight
Dimensions (height x length x width) (2)
MODEL
Water cooling capacity
Water cooling capacity (*)
Water cooling capacity
Water heating capacity 50ºC
Water heating capacity 50ºC (*)
Water heating capacity 70/60ºC
Absorbed power
Power supply (50 Hz ~)
Air flow (1)
Air flow (*)
Water flow
Water connections
Sound pressure (2)
Sound pressure (2) (*)
Weight
Dimensions (height x length x width) (2)
FCW 3R+1/ FCCW 3R+1 (4 pipes) TECHNICAL SPECIFICATIONS
MODEL
Water cooling capacity
Water cooling capacity (*)
Water cooling capacity
Water heating capacity 70/60ºC
Water heating capacity 70/60ºC (*)
Absorbed power
Power supply (50 Hz ~)
Air flow (1)
Air flow (*)
Water flow
Water connections
Sound pressure (2)
Sound pressure (2) (*)
Weight
Dimensions (height x length x width) (2)
kW
kW
T.R.
kW
kW
W
V
m3/h
m3/h
l/h
Ø (")
dB(A)
dB(A)
kg
mm
Water cooling capacity
Water cooling capacity (*)
Water cooling capacity
Water heating capacity 70/60ºC
Water heating capacity 70/60ºC (*)
Absorbed power
Power supply (50 Hz ~)
Air flow (1)
Air flow (*)
Water flow
Water connections
Sound pressure (2)
Sound pressure (2) (*)
Weight
Dimensions (height x length x width) (2)
kW
kW
T.R.
kW
kW
W
V
m3/h
m3/h
l/h
Ø (")
dB(A)
dB(A)
kg
mm
MODEL
10
15
20
25
30
40
0.8
0.9
0.2
1.3
1.6
30
230.1
216
264
144
3/4
36
50
15.6
480x660x225
1.2
1.6
0.3
1.9
2.3
30
230.1
275
391
212
3/4
38
56
18.9
480x860x225
20.8
2.6
5.9
2.7
3.2
40
230.1
384
507
358
3/4
35
50
23.7
480x1060x225
2.4
2.7
0.7
2.9
3.2
56
230.1
430
503
409
3/4
38
52
23.9
480x1060x225
2.8
3.7
0.8
3.5
4.2
60
230.1
546
770
509
3/4
37
56
27.7
480x1260x225
3.7
4.2
1.0
4.1
4.5
80
230.1
651
775
635
3/4
44
57
27.9
480x1260x225
50
60
70
80
100
110
4.5
5.2
1.3
5.0
5.7
78
230.1
673
821
769
3/4
44
58
32.7
585x1260x225
2.4
6.8
0.7
6.2
7.6
160
230.1
1005
1437
920
3/4
50
68
38.0
585x1460x225
6.6
7.2
1.9
7.7
8.2
180
230.1
1180
1345
1130
3/4
56
68
38.5
585x1460x225
7.7
8.4
2.2
8.4
9.1
182
230.1
1291
1433
1330
3/4
54
66
50.0
602x1660x257
9.7
2.8
10.1
273
230.1
1916
1673
3/4
58
58.5
602x1960x257
10.7
3.0
11.4
273
230.1
1908
1837
3/4
58
59.0
602x1960x257
(1) 0 Pa static pressure available
(2) Considered 8.6 dB(A) less in relation to the sound power in an area of
90 m3 with a reverberation time of 0.5 sec.
Data calculated at full speed
(*) At speed 6: configurable on request
111
CHILLED WATER TERMINAL UNITS | FAN COIL
Options
Fancoil supports kit
Secondary trays for condensates
Electric heating coils. Safety
thermostat included (230-i)
Supply plenum for
units without cabinet
Adjustable air grilles
for units without cabinet
90º supply plenum for unit without
cabinet
Return air plenum for
units without cabinet
Extension for straight and 90º
plenum for units without cabinet
Supply plenum with spigots for unit
without cabinet
Return air plenum with spigots and
filter for units without cabinet
Painted lower panel without grille
for units without cabinet
Painted lower panel with filter and
grille for units with cabinet
Condensate pumps
Painted ceiling panel plus return air plenum
and 90° supply plenum for
units without cabinet
112
Options
COMPONENTS
A. Valve + actuator
B. Elbow connectors
C. Shut-off/control valve
FOR MODELS
DESCRIPTION
Ø"
FOR MODELS
IMPORTANT:
The elbow connectors are not
supplied with the valves.
To be ordered separately.
DESCRIPTION
Ø"
FCW 1-6 2-pipe, 3-way system
1/2
FCW 100-120 2-pipe, 3-way system
1
FCW 1-6 2-pipe, 3-way system floating at 3 points
1/2
FCW 100-120 2-pipe, 3-way system floating at 3 points
1
FCW 1-6 2-pipe, 3-way system modulating 0-10 V
1/2
FCW 100-120 2-pipe, 3-way system modulating 0-10 V
1 - 3/4
FCW 1-6 4-pipe, 3-way system
1/2 - 1/2
FCW 100-120 4-pipe, 3-way system
1 - 3/4
FCW 1-6 4-pipe, 3-way system floating at 3 points
1/2 - 1/2
FCW 100-120 4-pipe, 3-way system floating at 3 points
1 - 3/4
FCW 1-6 4-pipe, 3-way system modulating 0-10 V
1/2 - 1/2
FCW 100-120 4-pipe, 3-way system modulating 0-10 V
1
FCW 1-6 2-pipe, 2-way system
1/2
FCW 100-120 2-pipe, 2-way system
1
FCW 1-6 2-pipe, 3-way system floating at 3 points
1/2
FCW 100-120 2-pipe, 2-way system floating at 3 points
1
FCW 1-6 2-pipe, 3-way system modulating 0-10 V
1/2
FCW 100-120 2-pipe, 3-way system modulating 0-10 V
1 - 3/4
FCW 1-6 4-pipe, 2-way system
1/2 - 1/2
FCW 100-120 4-pipe, 2-way system
1 - 3/4
FCW 1-6 4-pipe, 3-way system floating at 3 points
1/2 - 1/2
FCW 100-120 4-pipe, 2-way system floating at 3 points
1 - 3/4
FCW 1-6 4-pipe, 3-way system modulating 0-10 V
1/2 - 1/2
FCW 100-120 4-pipe, 3-way system modulating 0-10 V
1
FCW 1-6 Shut-off/control valve. 2-pipe system
1/2
FCW 100-120 Shut-off/control valve. 2-pipe system
1 - 3/4
FCW 1-6 Shut-off/control valve. 4-pipe system
1/2 - 1/2
FCW 100-120 Shut-off/control valve. 4-pipe system
1
FCW 1-6 2 shut-off valves. 2-pipe system
1/2
FCW 100-120 2 shut-off valves. 2-pipe system
1 - 3/4
FCW 1-6 2 shut-off valves. 4-pipe system
1/2 - 1/2
FCW 100-120 2 shut-off valves. 4-pipe system
-
FCW 1-6 Elbow connectors. 2-pipe system
-
FCW 100-120 Elbow connectors. 2-pipe system
-
FCW 1-6 Elbow connectors. 4-pipe system
-
FCW 100-120 Elbow connectors. 4-pipe system
-
FCW 70-90 2-pipe, 3-way system
3/4
FCW 70-90 2-pipe, 3-way system floating at 3 points
3/4
FCW 70-90 2-pipe, 3-way system modulating 0-10 V
3/4
FCW 70-90 4-pipe, 3-way system
3/4 - 3/4
FCW 70-90 4-pipe, 3-way system floating at 3 points
3/4 - 3/4
FCW 70-90 4-pipe, 3-way system modulating 0-10 V
3/4 - 3/4
FCW 70-90 2-pipe, 2-way system
3/4
FCW 70-90 2-pipe, 2-way system floating at 3 points
3/4
FCW 70-90 2-pipe, 3-way system modulating 0-10 V
3/4
FCW 70-90 4-pipe, 2-way system
3/4 - 3/4
FCW 70-90 4-pipe, 2-way system floating at 3 points
3/4 - 3/4
FCW 70-90 4-pipe, 3-way system modulating 0-10 V
3/4 - 3/4
Fresh air damper kits
FCW 70-90 Shut-off/control valve. 2-pipe system
3/4
FCW 70-90 Shut-off/control valve. 4-pipe system
3/4 - 3/4
Rear closure panel for units with cabinet
FCW 70-90 2 shut-off valves. 2-pipe system
3/4
FCW 70-90 2 shut-off valves. 4-pipe system
3/4 - 3/4
FCW 70-90 Elbow connectors. 2-pipe system
-
FCW 70-90 Elbow connectors. 4-pipe system
-
113
Other accessories
Supply grilles for units with cabinet
Other accessories: please contact our
Sales Department
CHILLED WATER TERMINAL UNITS | 4-WAY CASSETTE
FKW
With infrared
remote control
FKWS
Without infrared
remote control
MAIN FEATURES
Cooling capacities between 2.4 and 7.6 kW
2 versions:
- FKW (with own infrared remote control)
- FKWS (without control and ready to be installed
with wall-mounted control)
2 dimensions: 580x580 and 835x835 mm
Removable filter. Easy maintenance
Valves not installed. Supplied separately
Integrated condensate drain pump
Connector tubes supplied separately
Advantages
Units can be built into false ceilings for office buildings sector.
The cassette fan coil is an ambient air handling terminal unit that
works just as well in winter as in summer. Specially designed with
standard dimensions for installation in false ceilings.
Options
ENERGY EFFICIENCY
3-way valve for 2-pipe model
Shut-off valve and control valve for 2-pipe model
Elbow connectors for 2-pipe installation
3-way valve for 4-pipe model
Shut-off valve and control valve for 4-pipe model
Elbow connectors for 4-pipe installation
CONTROLS
Wall-mounted electronic thermostat
For the functions, see the
"Controls" section on page 216
Besides these options, please speak to our Sales Department for any other
configuration or function that is not listed as being available.
FKW Model with control FKWS Model without control. 2-pipe installation. TECHNICAL SPECIFICATIONS
21
22
23
24
Water cooling capacity 7/12ºC kW
2.4
2.8
3.3
4.5
Water cooling capacity 7/12ºC T.R.
0.7
0.8
0.9
1.3
Water heating capacity 50ºC kW
3.4
3.8
4.5
5.3
230.1
230.1
230.1
230.1
3/4
3/4
3/4
3/4
50
50
53
55
23.5
24.5
24.5
24.5
580x580x280+23
580x580x280+23
580x580x280+23
580x580x280+23
MODEL
Power supply (50 Hz ~) V
Standard water coil connections Ø (")
Sound pressure (1) dB(A)
Weight kg
Dimensions (length x height x width) mm
31
32
33
34
Water cooling capacity 7/12ºC kW
5.6
6.4
7.1
7.6
Water cooling capacity 7/12ºC T.R.
1.6
1.8
2.0
2.2
Water heating capacity 50ºC kW
7.3
7.3
8.0
8.3
230.1
230.1
230.1
230.1
3/4
1
1
1
47
49
52
52
37
43
43
45
835x835x240+60
835x835x305+60
835x835x305+60
835x835x305+60
MODEL
Power supply (50 Hz ~) V
Standard water coil connections Ø (")
Sound pressure (1) dB(A)
Weight kg
Dimensions (length x height x width) mm
114
FKW Model with control FKWS Model without control. 4-pipe installation. TECHNICAL SPECIFICATIONS
41
42
43
44
Water cooling capacity 7/12ºC kW
1.9
2.8
3.5
4.4
Water cooling capacity 7/12ºC T.R.
0.5
0.8
1.0
1.3
Water heating capacity 60/70ºC kW
1.9
2.8
3.5
4.4
230.1
230.1
230.1
230.1
Standard water coil connections Ø (")
3/4
3/4
3/4
3/4
Secondary water coil connections Ø (")
1/2
1/2
1/2
1/2
50
50
53
55
23.5
24.5
24.5
24.5
580x580x280+23
580x580x280+23
580x580x280+23
580x580x280+23
MODEL
Power supply (50 Hz ~) V
Sound pressure (1) dB(A)
Weight kg
Dimensions (length x height x width) mm
51
52
53
54
Water cooling capacity 7/12ºC kW
4.3
5.0
5.5
6.1
Water cooling capacity 7/12ºC T.R.
1.2
1.4
1.5
1.7
Water heating capacity 70/60ºC kW
5.9
6.6
7.3
8.6
230.1
230.1
230.1
230.1
Standard water coil connections Ø (")
3/4
1
1
1
Secondary water coil connections Ø (")
1/2
3/4
3/4
3/4
47
49
52
52
37
43
43
45
835x835x240+60
835x835x305+60
835x835x305+60
835x835x305+60
MODEL
Power supply (50 Hz ~) V
Sound pressure (1) dB(A)
Weight kg
Dimensions (length x height x width) mm
(1) Considered 8.6 dB(A) less in relation to the sound power in an area of 90 m3 with a reverberation time of 0.5 sec.
Data calculated at full speed
115
CHILLED WATER TERMINAL UNITS | WALL MOUNTED
FPW
Wall mounted
fan coil unit
MAIN FEATURES
Cooling capacities between 2.0 and 4.0 kW
Easy maintenance
Valves built into the unit
4 versions:
- FPW (with own infrared remote control)
- FPWS (without control and ready to be
installed with wall-mounted control)
- FPW+V3 (with infrared remote control and
with 3-way valve)
- FPWS+V3 (without infrared remote control
and with 3-way valve)
Advantages
Solutions for low requirements with difficult installation location.
The wall mounted fan coil unit is an ambient air handling terminal
unit that works just as well in winter as in summer. It features an
attractive design and outstanding comfort, with minimal sound
levels.
FPW TECHNICAL SPECIFICATIONS
MODEL
Cooling capacity (1) kW
20
25
35
40
2.0
2.4
3.3
4.0
Cooling capacity (1) T.R.
0.6
0.7
0.9
1.1
Heating capacity (2) kW
2.6
3.0
4.4
4.9
Heating capacity (3) kW
4.4
5.0
7.5
8.3
29
29
48
51
Absorbed power W
Power supply (50 Hz ~) V
230.1
230.1
230.1
230.1
336
409
573
686
Water connections Ø (")
1/2
1/2
1/2
1/2
Sound pressure (4) db(A)
45
45
45
48
Water flow l/h
Dimensions (width x length x height) mm
Weight kg
880x298x205
990x305x210
1172x360x220
1172x360x220
11.5
12.4
19
20.5
(1) Water inlet 7ºC, water outlet 12ºC. Air temperature 27ºC dry bulb, 19ºC wet bulb.
(2) Water inlet 50ºC. Air temperature 20ºC
(3) Water inlet 60/70ºC. Air temperature 20ºC
(4) Considered 8.6 dB(A) less in relation to the sound power in an area of 90 m3 with a reverberation time of 0.5 sec.
Data calculated at full speed
0 Pa external static pressure
116
CHILLED WATER TERMINAL UNITS | DUCTABLE
BHW
Low silhouette
ductable fan coil
unit
Advantages
MAIN FEATURES
Flexible and versatile applications for water-based installations.
The low silhouette ductable fan coil units are fitted with
a heat exchanger constructed from copper tubes and aluminium
fins. Centrifugal fans operated by three-speed
motors.
Cooling capacities between 4.5 and 25 kW
Easy maintenance
Maximum adaptability to the needs of the facility
Options
Auxiliary electric heating coils
Pre-treated anti-corrosion coils
Filter with bottom outlet
Adaptable filter
Main switch
Suitable for vertical installation
AIR QUALITY
G4 gravimetric filter on return
SOUND LEVEL
Double thermal-acoustic insulation
UNIT INSTALLATION
60Hz power supply and voltages of 230, 208 etc.
Electrical board with fan contact, thermal and magnetothermal relay
Potentiated motors (depending on model)
Opposite side connectors
Supply plenum with grille
Supply plenum with spigots (depending on the model)
Thermal-acoustic insulation class M0
Flame-proof filter class M0
Hot water heating coils
Additional coil for 4-pipe operation
MAINTENANCE
Dirty filter detector
Ductable filter
CONTROLS
Compatible with Hydrofan
Alarm signals
Smoke detection
Remote start/stop
For the functions, see the
"Controls" section on page 216
Besides these options, please speak to our Sales Department for any other
configuration or function that is not listed as being available.
BHW TECHNICAL SPECIFICATIONS
205
358
410
Cooling capacity water temp. 7ºC Speed I-II-III (kW) 3.1 - 4.1 - 4.5
174
4.4 - 5.0 - 5.3
6.0 - 5.9 - 8.9
7.9 - 9.1 - 10.8
Heating capacity water temp. 50ºC Speed I-II-III (kW) 4.5 - 5.8 - 6.3
6.4 - 7.1 - 7.5
8.6 - 9.7 - 11.9
11.1 - 12.6 - 14.9
Heating capacity water temp. 70ºC Speed I-II-III (kW) 7.6 - 9.8 - 10.7
10.8 - 12.1 - 12.7
14.6 - 16.5 - 20.1
18.8 - 21.4 - 25.2
0.2
0.3
0.5
0.6
230.1
230.1
230.1
230.1
530 - 690 - 760
760 - 850 - 895
1030 - 1180 - 1440
1360 - 1560 - 1850
600 - 900 - 1050
950 - 1130 - 1220
1100 - 1340 - 1850
1400 - 1700 - 2200
2 - 2.5 - 3
2.5 - 3 - 4
6-7-8
6 - 7.5 - 8
3/4
3/4
3/4
3/4
829x791x219
829x791x258
915x791x285
915x791x315
30
34
44
45
515
720
724
MODEL
Total absorbed power kW
Voltage (50 Hz~) V
Water flow speed I-II-III l/h
Air flow speed I-II-III m3/h
External static pressure speed I-II-III mm WG
Water connection Ø (")
Dimensions (width x length x height) mm
Net weight kg
MODEL
Cooling capacity water temp. 7ºC Speed I-II-III (kW) 12.2 - 13.9 - 15.3
20.2
25.0
Heating capacity water temp. 50ºC Speed I-II-III (kW) 16.1 - 18.2 - 19.7
26.5
32.7
Heating capacity water temp. 70ºC Speed I-II-III (kW) 27.2 - 30.8 - 33.5
44.8
55.5
0.6
0.8
1.6
230.1
230.1
230.1
2090-2360-2565
3365
4190
2200-2600-2900
3850
5200
3 - 4 - 5.5
5
5
1
1 1/4
1 1/4
1200x826x352
1350x900x412
1350x900x412
62
80
80
Total absorbed power kW
Voltage (50 Hz~) V
Water flow speed I-II-III l/h
Air flow speed I-II-III m3/h
External static pressure speed I-II-III mm WG
Water connection Ø (")
Dimensions (width x length x height) mm
Net weight kg
117
CHILLED WATER TERMINAL UNITS | DUCTABLE
BSW
High static
pressure ductable
fan coil unit
MAIN FEATURES
Cooling capacities between 3.6 and 50.6 kW
High external static pressure: from 105 Pa
Standard model without filter. EU3 filter optional
2 versions: BSW H (horizontal installation)
and BSW V (vertical installation)
Easy maintenance
Advantages
Flexible and versatile applications for water-based installations.
The ductable fan coil units are designed to be installed in false
ceilings thanks to their low height.
Options
AIR QUALITY
Air filter
UNIT INSTALLATION
3-way valve for 2-pipe model
Shut-off valve and control valve for 2-pipe model
Elbow connectors for 2-pipe installation
3-way valve for 4-pipe model
Shut-off valve and control valve for 4-pipe model
Elbow connectors for 4-pipe installation
Hot water coil
Electric coil
Condensate tray
CONTROLS
Wall-mounted electronic thermostat
For the functions, see the
"Controls" section on page 216
Besides these options, please speak to our Sales Department for any other
configuration or function that is not listed as being available.
BSW H/BSW V (2 pipes) TECHNICAL SPECIFICATIONS
MODEL
Cooling capacity (1) kW
10
20
30
40
3.8
7.1
9.2
10.6
11.4
Cooling capacity (1) T.R.
2.8
5.7
8.5
Heating capacity (2) kW
5.0
8.6
11.3
12.9
155
195
325
355
230.1
230.1
230.1
230.1
895
1423
1951
2131
105
105
135
135
Maximum absorbed power W
Power supply (50 Hz ~) V
Air flow m3/h
External static pressure Pa
606.5
1092.2
1489.1
1684.3
Water connections Ø (")
Water flow l/h
1/2
1/2
3/4
3/4
Sound pressure (3) db(A)
59.4
57.4
61.4
60.4
650x300x533
1000x300x533
1100x325x533
1340x325x533
Dimensions (length x height x width) H mm
Dimensions (length x height x width) V mm
Weight kg
738x330x603
1088x330x603
1188x355x623
1428x355x623
28
36
41
46
➜
118
BSW H/BSW V (2 pipes) TECHNICAL SPECIFICATIONS
50
60
70
Cooling capacity (1) kW
13.1
27.8
50.6
Cooling capacity (1) T.R.
3.7
7.9
14.4
Heating capacity (2) kW
17.0
32.9
60.9
525
1300
2400
230.1
230.1
230.1
3002
4678
9250
205
260
260
1945.0
4234.6
7802.1
1 1/2
MODEL
Maximum absorbed power W
Power supply (50 Hz ~) V
Air flow m3/h
External static pressure Pa
Water flow l/h
Water connections Ø (")
1
1 1/4
Sound pressure (3) dB(A)
66.4
69.4
72.4
1340x375x533
1341x675x853
2028x675x853
Dimensions (length x height x width) H mm
Dimensions (length x height x width) V mm
Weight kg
1428x405x723
1481x703x1294
2168x703x1294
57
117
192
(1) Water inlet 7ºC, water outlet 12ºC. Air temperature 27ºC dry bulb,
19ºC wet bulb
(2) Water inlet 50ºC. Air temperature 20ºC
(3) Considered 8.6 dB(A) less in relation to the sound power in an area of
90 m3 with a reverberation time of 0.5 sec.
Data calculated at full speed
BSW H/BSW V (4 pipes) TECHNICAL SPECIFICATIONS
MODEL
Cooling capacity (1)
Cooling capacity (1)
Heating capacity (2)
Maximum absorbed power
Power supply (50 Hz ~)
Air flow
External static pressure
Water flow
Water connections
Sound pressure (3)
Dimensions (length x height x width) H
Dimensions (length x height x width) V
Weight
kW
T.R.
kW
W
V
m3/h
Pa
l/h
Ø (")
dB(A)
mm
mm
kg
MODEL
Cooling capacity (1) kW
10
20
30
40
3.6
1.0
4.2
155
230.1
795
95
606.5
1/2
60.4
650x300x533
738x330x603
28
7.0
2.0
7.0
195
230.1
1353
90
1092.2
1/2
57.4
1000x300x533
1088x330x603
36
9.0
2.6
9.2
325
230.1
1850
120
1489.1
3/4
61.4
1100x325x533
1188x355x623
41
9.6
2.7
10.6
355
230.1
2025
120
1684.3
3/4
61.4
1340x325x533
1428x355x623
46
50
60
70
13.6
24.9
45.5
Cooling capacity (1) T.R.
3.9
7.1
12.9
Heating capacity (2) kW
12.7
38.8
70.2
525
1300
2400
230.1
230.1
230.1
3036
4445
8788
180
220
220
1945.0
4234.6
7802.1
1
1 1/4
1 1/2
Maximum absorbed power W
Power supply (50 Hz ~) V
Air flow m3/h
External static pressure Pa
Water flow l/h
Water connections Ø (")
Sound pressure (3) dB(A)
Dimensions (length x height x width) H mm
Dimensions (length x height x width) V mm
Weight kg
64.4
69.4
72.4
1340x375x533
1341x675x853
2028x675x853
1428x405x723
1481x703x1294
2168x703x1294
57
117
192
(1) Water inlet 7ºC, water outlet 12ºC. Air temperature 27ºC dry bulb, 19ºC wet bulb
(2) Water inlet 60/70ºC. Air temperature 20ºC
119
CHILLED WATER TERMINAL UNITS | DUCTABLE
Options
COMPONENTS
A. Valve + actuator
B. Interconnection tube
C. Shut-off/control valve
IMPORTANT:
The elbow connectors are not
supplied with the valves.
To be ordered separately.
Valves, 2-pipe and 4-pipe installation
VALVE MODEL
BSW 20 Ø (")
BSW 30 A 50 Ø (")
BSW 60 Ø (")
BSW 70 Ø (")
2-pipe, 3-way system 1/2
BSW 10 Ø (")
3/4
1
1 1/2
2
2-pipe, 3-way system floating at 3 points 1/2
3/4
1
1 1/2
2
2-pipe, 3-way system modulating 0-10 V 1/2
3/4
1
1 1/2
2
4-pipe, 3-way system 1/2 - 1/2
3/4 - 1/2
1 - 3/4
1 1/2 - 1 1/2
2 - 1 1/2
4-pipe, 3-way system floating at 3 points 1/2 - 1/2
3/4 - 1/2
1 - 3/4
1 1/2 - 1 1/2
2 - 1 1/2
4-pipe, 3-way system modulating 0-10 V 1/2 - 1/2
3/4 - 1/2
1 - 3/4
1 1/2 - 1 1/2
2 - 1 1/2
2-pipe, 2-way system 1/2
3/4
1
1 1/2
2
2-pipe, 2-way system floating at 3 points 1/2
3/4
1
1 1/2
2
2-pipe, 2-way system modulating 0-10 V 1/2
3/4
1
1 1/2
2
4-pipe, 2-way system 1/2 - 1/2
3/4 - 1/2
1 - 3/4
1 1/2 - 1 1/2
2 - 1 1/2
4-pipe, 2-way system floating at 3 points 1/2 - 1/2
3/4 - 1/2
1 - 3/4
1 1/2 - 1 1/2
2 - 1 1/2
4-pipe, 2-way system modulating 0-10 V 1/2 - 1/2
3/4 - 1/2
1 - 3/4
1 1/2 - 1 1/2
2 - 1 1/2
Shut-off/control valve. 2-pipe system 1/2
3/4
1
1 1/2
2
Shut-off/control valve. 4-pipe system 1/2 - 1/2
3/4 - 1/2
1 - 3/4
1 1/2 - 1 1/2
2 - 1 1/2
2 shut-off valves. 2-pipe system 1/2
3/4
1
1 1/2
2
2 shut-off valves. 4-pipe system 1/2 - 1/2
3/4 - 1/2
1 - 3/4
1 1/2 - 1 1/2
2 - 1 1/2
Interconnection tube for 2-pipe system -
-
-
-
-
Interconnection tube for 4-pipe system -
-
-
-
-
Secondary trays for condensates
Air filter
Secondary hot water coils
1 row for 4-pipe systems
For models
kW
BSW 10
4.2
BSW 20
7
BSW 30
9.2
BSW 40
10.5
BSW 50
14
BSW 60
38.8
BSW 70
70.2
Condensate pumps
Electric heating coils
Electric heating coils
Other optional accessories
4-row coils
5-row coils
6-row coils
Fresh air intake damper section
Supply plenum
Return air plenum
120
For models
BSW 10
BSW 10
BSW 20
BSW 20
BSW 30
BSW 30
BSW 40
BSW 40
BSW 50
BSW 50
BSW 60
BSW 60
BSW 70
BSW 70
kW
3
4.5
6
6
9
9
9
9
12
12
12
18
18
24
CHILLED WATER TERMINAL UNITS | DUCTABLE
EHW
Horizontal ductable
fan coil unit
MAIN FEATURES
Cooling capacities between 18 and 110 kW
Air flows up to 18000 m3/h
Can be integrated with the Hydrofan system
Outside installation option
Advantages
Flexible and versatile applications for water-based installations.
The EHW series is composed of units designed to supplement
and optimise air conditioning with hydronic systems. They are
fitted with a heat exchanger constructed with copper tubes and
aluminium fins and centrifugal fans operated by belt-driven motors.
Options
ENERGY EFFICIENCY
Double mixing box with 3 dampers for free cooling
Radial EC fan
AIR QUALITY
G4 gravimetric filter on return
Opacimetric filter on return, class F6 to F9 (can be combined
with a G4 or Fx+Fy)
MAINTENANCE
Dirty filter detector
Ductable filter
SOUND LEVEL
Double thermal-acoustic insulation
UNIT INSTALLATION
Magneto-thermal circuit breakers in the electrical board
60Hz power supply and voltages of 230, 208 etc.
(depending on model)
Kit for bad weather installation
Upgraded motors
Flame-proof filter class M0
Thermal-acoustic insulation class M0
Opposite side connectors
Air inlet/outlet configuration options
Base frame
Horizontal air discharge
Hot water heating coils
Heating coils for use on 4-tube system
Auxiliary electric heating coils
Pre-treated anti-corrosion coils
Possibility of disassembling
CONTROLS
Compatible with Hydrofan
Alarm signals
Smoke detection
Remote start/stop
Stand-alone electrical board
For the functions, see the
"Controls" section on page 216
Besides these options, please speak to our Sales Department for any other
configuration or function that is not listed as being available.
standard
121
optional
CHILLED WATER TERMINAL UNITS | DUCTABLE
EHW TECHNICAL SPECIFICATIONS
518
725
830
1036
1042
1250
Cooling capacity water temp. 7ºC kW
18.0
25.0
30.0
36.0
42.0
50.0
Cooling capacity water temp. 50ºC kW
26.7
36.0
32.9
50.0
57.7
69.9
Cooling capacity water temp. 85ºC kW
59.3
79.2
94.2
110.0
127.0
145.0
Cooling capacity water temp. 7ºC T.R.
5.1
7.1
8.5
10.2
11.9
14.2
Cooling capacity water temp. 50ºC T.R.
7.6
10.2
9.4
14.2
16.4
19.9
Cooling capacity water temp. 85ºC T.R.
16.9
22.5
26.8
31.3
36.1
41.2
0.6
0.8
1.1
0.8
1.1
1.5
230.3 or
400.3+N
230.3 or
400.3+N
230.3 or
400.3+N
230.3 or
400.3+N
230.3 or
400.3+N
230.3
2978
4637
5381
6028
6841
7753
3500
4200
5200
5500
6500
8200
8.0
10.5
7.4
10.8
8.0
7.0
1 1/4
1 1/2
1 1/2
2
2
2
1085x750x580
1130x900x650
1130x900x650
1700x870x650
1700x870x650
1700x870x650
108
150
150
214
214
217
1657
2069
2476
3097
35110
MODEL
Total absorbed power kW
Power supply (50 Hz ~) V
Water flow l/s
Air flow m3/h
External static pressure mm WG
Water connections Ø (")
Dimensions (length x width x height) mm
Net weight kg
MODEL
Cooling capacity water temp. 7ºC kW
57.0
69.0
76.0
97.0
110.0
Cooling capacity water temp. 50ºC kW
82.8
100.0
110.0
132.0
155.0
Cooling capacity water temp. 85ºC kW
183.0
220.0
241.0
290.0
342.0
Cooling capacity water temp. 7ºC T.R.
16.2
19.6
21.6
27.6
31.3
Cooling capacity water temp. 50ºC T.R.
23.5
28.4
31.3
37.5
44.1
Cooling capacity water temp. 85ºC T.R.
52.0
62.6
68.5
82.5
97.2
2.2
3.0
3.0
4.0
4.0
230.3 or
400.3+N
230.3 or
400.3+N
230.3 or
400.3+N
230.3 or
400.3+N
230.3 or
400.3+N
Total absorbed power kW
Power supply (50 Hz ~) V
Water flow l/s
Air flow m3/h
External static pressure mm WG
Water connections Ø (")
Dimensions (length x width x height) mm
Net weight kg
9676
11776
12829
15534
17575
9500
11200
12500
14800
18000
11.3
14.5
15.0
18.0
20.5
2
2
2
2 1/2
2 1/2
2000x937x747
2600x980x752
2600x980x752
2800x1050x915 2800x1050x915
291
356
356
452
122
558
CHILLED WATER TERMINAL UNITS | DUCTABLE
CLW
Vertical ductable
fan coil unit
MAIN FEATURES
Cooling capacities between
7.6 and 47.6 kW
Air flows up to 8200 m3/h
Can be integrated with the Hydrofan system
Outside installation option
Advantages
Flexible and versatile applications for water-based installations.
The CLW series is composed of units designed to supplement and
optimise air conditioning with hydronic systems. They are fitted with
a heat exchanger constructed with copper tubes and aluminium fins
and centrifugal fans with external static pressure.
Options
ENERGY EFFICIENCY
Mixing box with actuators
Fan soft start
Radial EC fan
AIR QUALITY
G4 gravimetric filter on return
Opacimetric filter on return class F6 to F9 (can be combined
with a G4 or Fx+Fy)
SOUND LEVEL
Double thermal-acoustic insulation
UNIT INSTALLATION
Magneto-thermal circuit breakers in the electrical board
60Hz power supply and voltages of 230, 208 etc. (depending
on model)
Kit for bad weather installation
Upgraded motors
Flame-proof filter class M0
Thermal-acoustic insulation class M0
Opposite side connectors
Base frame
Air inlet/outlet configuration options
standard
123
Horizontal air discharge
Hot water heating coils
Heating coils for use on 4-pipe system
Auxiliary electric heating coils
Pre-treated anti-corrosion coils
Possibility of disassembling
Air intake grille
MAINTENANCE
Dirty filter detector
Ductable filter
CONTROLS
Compatible with Hydrofan
Alarm signals
Smoke detection
Remote start/stop
Stand-alone electrical board
For the functions, see the
"Controls" section on page 216
Besides these options, please speak to our Sales Department for any other
configuration or function that is not listed as being available.
optional
CHILLED WATER TERMINAL UNITS | DUCTABLE
CLW TECHNICAL SPECIFICATIONS
270
412
515
720
824
Cooling capacity water temp. 7ºC kW
7.6
14.0
15.6
18.6
22.4
Heating capacity water temp. 50ºC kW
11.7
20.7
23.5
27.9
29.2
Heating capacity water temp. 85ºC kW
25.8
45.6
51.8
61.4
64.0
Cooling capacity water temp. 7ºC T.R.
2.2
4.0
4.4
5.3
6.4
Heating capacity water temp. 50ºC T.R.
3.3
5.9
6.7
7.9
8.3
Heating capacity water temp. 85ºC T.R.
7.3
13.0
14.7
17.5
18.2
Total absorbed power kW
0.3
0.5
0.6
0.8
0.4
230.1
230.1 - 400.3+N
230.3 - 400.3+N
230.3 - 400.3+N
230.3 - 400.3+N
1,314
2,411
2,684
3,193
3,859
1,900
2,801
3,500
4,200
3,500
100
50
150
135
100
3/4
1
1
1 1/4
1 1/2
697x500x1000
697x500x1000
757x500x1100
1152x600x1200
1152x600x1200
45
71
94
115
151
MODEL
Power supply (50 Hz ~) V
Water flow L/h
Air flow m3/h
External static pressure Pa
Water connections Ø (")
Dimensions (length x width x height) mm
Net weight kg
830
1036
1042
1250
29.5
36.7
41.0
47.6
Heating capacity water temp. 50ºC kW
40.1
48.6
55.7
66.9
Heating capacity water temp. 85ºC kW
88.0
107.0
122.0
147.0
MODEL MODEL
Cooling capacity water temp. 7ºC kW
Cooling capacity water temp. 7ºC T.R.
8.4
10.4
11.7
13.5
Heating capacity water temp. 50ºC T.R.
11.4
13.8
15.8
19.0
Heating capacity water temp. 85ºC T.R.
2.1
3.7
4.2
5.0
Total absorbed power kW
1.1
0.8
1.1
1.5
230.3 - 400.3+N
230.3 - 400.3+N
230.3 - 400.3+N
230.3 - 400.3+N
5,079
6,313
7,052
8,191
5,200
5,500
6,500
8,200
100
85
75
85
1 1/2
2
2
2
1152x600x1200
1700x600x1300
1700x600x1300
1700x600x1300
151
171
171
182
Power supply (50 Hz ~) V
Water flow L/h
Air flow m3/h
External static pressure Pa
Water connections Ø (")
Dimensions (length x width x height) mm
Net weight kg
124
AIR
HANDLING
125
AIR HANDLING
WESPAK
page
128
Mini compact air handling
unit, single or double skin,
10 mm.
3-speed direct drive motor.
Horizontal or vertical installation.
Flow up to 3700 m3/h.
Made in France.
EFF@IR
page
SLIM@IR
page
130
High-performance compact
unit with 25 mm double skin,
satisfies RT 2102 and EN 1886.
Fans: freewheel with high-efficiency IE2 or EC motors.
Heat recovery devices with high yield of 70 to 80%.
Flow up to 6000 m3/h.
On-board Aqu@net control system communicating in
Modbus.
Accessibility: full from the side or below, vertical or
horizontal installation.
Configuration: in series, stacked or
side-by-side.
Finish: pre-painted, galvanised or
stainless steel.
Removable tray as standard to
facilitate cleaning.
Made in France.
132
Compact dual-flow unit with
integrated control system, with
40 mm double skin.
Flow up to 6000 m3/h.
EFF@IR CFI EC
EFF@IR HP
EFF@IR WRI EC
Counter-flow plate heat
exchanger, high yield from 85 to
93%, low consumption EC motor.
Model: stacked, horizontal or
vertical.
Crossed-flow plate heat exchanger
with yield from 50 to 70%.
Model: stacked or horizontal.
Rotary heat exchanger with
high yield from 75 to 86%.
Low consumption EC motor.
Model: stacked or vertical
with air recovery and air
delivery on top.
126
PREMI@IR
PREMI@IR DOUBLE
DECK COMPACT page 140
Designed for comfort, hygienic or industrial
applications.
Flow up to 30000 m3/h.
Eurovent certified.
Option: control system.
Made in France.
Rotary or plate heat exchanger greater than 85%.
Freewheel fan connected to high-efficiency IE2
or EC motors.
Flow up to 18000 m3/h.
Smooth interior to facilitate cleaning.
Made in France.
page
142
Self-supporting air handling unit
with 50 mm double skin.
Self-supporting, compact, dual-flow
air handling unit, 50 mm double skin
with integrated touch display control
system.
@IRTWIN
page
144
@IRTWIN
020 to 360
Air handling unit with 25 and 50 mm
double skin.
Designed for comfort, hygienic
or industrial applications.
Flow up to 100000 m3/h.
Eurovent certified.
Option: control system.
Made in France.
@IRTWIN
400 to 1000
127
AIR HANDLING | AIR HANDLING UNITS
WESPAK
1.39 to 3.99
Main features
MAIN FEATURES
Power on chilled water: 4 kW (4 rows at 500 m /h)
to 33 kW (6 rows at 4000 m3/h)
Power on hot water: 9 kW (at 500 m3/h) to 51 kW
(at 4000 m3/h)
Number of sizes: 3
Air flow range: 500 to 4400 m3/h (fan only)
Insulation: 10 mm thick foam
3
DESCRIPTION
WESPAK compact direct-transmission air handling
units are designed with a modular construction
to meet the varying needs of heating and air
conditioning for medium-sized facilities.
Single or double skin construction, made of 1.2 mm
thick galvanised sheet steel (paint on the external skin
available as an option) with 10 mm thick, open-cell
foam thermal insulation (fire protection class M1).
Available in horizontal or vertical configuration.
Advantages
Their 370 mm thickness permits to install it easily into false
ceilings.
Easy maintenance: access on the left or right hand side to the
internal components. Access to filters from four sides available
as an option. The components are fixed on sliding rails for
easy maintenance (except for the cooling coil in the vertical
configuration).
Numerous installation options.
Fans: centrifugal with 1 or 2 direct drive turbines powered by
a 3-speed motor, 230 V/1 phase/50 Hz, class F insulation with
protection against internal overheating with auto reset.
Two types of filter:
- Synthetic G2 or G4 filter. Fire protection class M1 in good
condition.
- Metallic G1 filter. Fire protection class M0 in good condition.
Coils: 2 rows (heating coils), 4 rows (chilled water coils or direct
expansion) or 6 rows (chilled water coils) consisting of copper tubes
and aluminium fins. The coils can be fitted with a droplet eliminator as
an option to protect against excessive humidities or sizeable air flows.
Main options
2-way mixing box with front and top dampers (MD1) or side and
underneath dampers (MD2).
3-way mixing box (MD3).
10 mm thick double skin panels (DP).
Painted external panel (PT).
Shut-off damper with parallel blades (AG).
10 mm thick metallic G1 filter (FM1) instead of the standard filter.
External filter function with:
- 10 mm thick metallic G1 filter (FA1)
- 10 mm thick synthetic G2 filter (FA2)
- 50 mm thick synthetic G4 filter (FA3)
Double reflection air plenum (PLE).
90° square air duct (R).
Air intake mounting frame (CA).
Flexible sleeve (M) for air duct connection.
Silencer (PAS).
Rain hood (AP) and roof (TO).
Main accessories
3-position speed switch (CMVM).
Remote controller with summer/winter + ambiance thermostat +
start/stop + 3-position switch. Control box with:
- Action on valve and ventilation (TRM-FA)
- Action on valves only (TRM-VP)
Droplet eliminator (metallic filter).
- Controller:
CMVM
- Controller:
TRM-FA
- Controller:
TRM-VP
For the functions, see the "Controls" section on page 216.
Besides these options, please contact our Sales Department for any other configuration or function that is not listed as being available.
128
WESPAK WP TECHNICAL SPECIFICATIONS
SIZE
1.39
Air flow
Air speed on cooling coil
Height (in-line)
Height (stacked)
Width (in-line or stacked)
m³/h 1010
m/s 1.5
mm
mm
mm
1340
2.0
370
740
762
2.69
1680
2.5
1650
1.5
2200
2.0
370
740
1150
3.99
2750
2.5
2220
1.5
2960
2.0
370
740
1500
3710
2.5
COILS
Number of rows
Fin spacing
Air flow
Total cooling capacity (4 rows)
Total sensible cooling capacity (4 rows)
Total cooling capacity (6 rows)
Total sensible cooling capacity (6 rows)
Cooling coil connection (4 rows)
Heating capacity (2 rows)
Heating coil connection (2 rows)
Min electric heating capacity
Max electric heating capacity
FAN MOTOR UNIT
Type available
Number of fans
Absorbed power
Motor nominal power
Max current
FILTER
Available filter
EXTERNAL STATIC PRESSURE
Air flow
G2 filter + fan (HM6)
G2 filter + heating coil 2R + fan (HP6)
G2 filter + cooling coil 4R + fan (HP7)
G2 filter + heating coil 2R + cooling coil 4R + fan
(HP4)
mm
m³/h
kW
kW
kW
kW
DN
kW
DN
kW
kW
2 rows for heating - 4 and 6 rows for water coils - 4 rows in direct expansion coil
2.1
1010
1340
1680
1650
2200
2750
2220
2960
3710
7.4
9.4
11.3
12.0
15.3
18.3
16.3
20.7
24.6
5.3
6.9
8.4
8.7
11.3
13.7
11.7
15.1
18.3
9.1
11.7
14.2
14.8
19.3
23.5
19.9
25.6
30.9
6.1
8.0
9.7
10.0
13.1
16.1
13.4
17.5
21.3
26/34
26/34
26/34
15.9
19.7
23.1
26.0
32.2
37.8
33.6
41.6
48.8
26/34
26/34
26/34
3.0
6.0
12.0
9.0
18.0
36.0
Direct contact centrifugal fan
2
960
368
4.22
1
700
250
3.30
W
W
A
2
900
540
5.01
Metallic G1, synthetic G2 filter (10 mm) or flat G4 (50 mm) compliant to EN779
m³/h
Pa
Pa
Pa
1010
254 (MV)
243 (MV)
216 (MV)
1340
256 (GV)
237 (GV)
193 (GV)
1680
192 (GV)
164 (GV)
96 (GV)
Pa
205 (MV) 174 (GV) 68 (GV)
1650
227 (MV)
216 (MV)
189 (MV)
2200
234 (GV)
215 (GV)
170 (GV)
2750
162 (GV)
134 (GV)
65 (GV)
179 (MV) 151 (GV) 37 (GV)
2220
250 (PV)
239 (PV)
213 (PV)
Configurations
HP6 INSTALLATION
HP7 INSTALLATION
129
3710
169 (GV)
141 (GV)
73 (GV)
202 (PV) 167 (GV) 44 (GV)
Cooling coil based on an air temperature of 27°C/50% and water temperature of 7/12°C.
Heating coil based on an air temperature of 15°C and water temperature of 90/70°C (coil next to discharge).
PV: Low speed – MV: Medium speed – GV: High speed
Other features and details: please refer to the technical instructions (EDM).
HM8 INSTALLATION
2960
249 (GV)
230 (GV)
186 (GV)
HP4 INSTALLATION
AIR HANDLING | AIR HANDLING UNITS
SLIM@IR
0303 to 0318
MAIN FEATURES
Cooling capacity from: 3 to 38 kW
Heating capacity from: 8 to 108 kW
Electric coil power: 1 to 54 kW
Number of sizes: 6
Air flow range: 500 (1.5 m/s) to 6000 m3/h
(3.1 m/s on the coil)
Insulation: glass wool or rock wool
DESCRIPTION
Free-standing design with double wall panels,
Slim@ir is a really compact and ultra-flexible air
handling unit, designed to cover all the needs of the
market with numerous mounting options: single inline flow installation, dual in-line flow installation, sideby-side, stacked, vertical and outdoor.
A concentration of innovation and technology
that follows the same rules and constraints as
those required for large air handling units, with a
classification to EN 1886: T3 – TB3 – L1 – F9 – D1
(tested by the independent laboratory TUV).
Advantages
With 6 models, from 500 to 6000 m3/h, fully adapted to
all applications thanks to a high-efficiency cabinet with full
accessibility to all internal components: side access with hinged
doors, access from below with hinged doors or access from below
with hatches on rollers; make
Slim@ir one of the most powerful air handling units for suspended
ceiling applications on the market.
The Slim@ir is also suitable for hygienic environments thanks to
its L1 (EN 1886) classification, an entirely smooth, easy to clean
interior tunnel and a removable condensate tray provided as
standard.
Innovative selection software with a user-friendly 3D graphical
interface allows all kinds of simulations by providing detailed
technical characteristics as well as dimensional drawings.
Operating limits/recommendations
Total pressure ± 1000 Pa.
-20°C min and +40°C max.
Depending on the indoor air temperature and the outdoor air
temperature, condensation may appear on the panels.
Main options
2 types of plate heat exchangers (efficiency - 50% & - 80%).
Glass wool or rock wool insulation.
Large choice of filters: flat G4 filter to F9 long pocket filter.
1, 2 or 3 row heating coils with a length of fins of 2.1 mm.
3, 4 or 6 row cooling coils with a length of fins of 2.5 mm.
Condensate tray made of inox AISI 304L or 316L for cooling coil.
Water coils with copper tubes and aluminium, epoxy or copper fins.
Electric battery with 5 power levels per size, from 1 kW (1 ph) to 54
kW (3 ph).
Frame of components, sheet metal capping and inox AISI 304L or
316L runners.
Choice of 3 types dampers: Standard, waterproof class 3 and
waterproof class 4 according to EN 1751.
1, 2 and 3 way mixing functionality.
Sound trap cabinets of 300, 600, 900 and 1200 mm length.
Freewheel fan (3 ph) with epoxy-coated wheel and epoxy fan
sheeting.
End panel with connecting flanges.
Double reflection air plenum.
90° square discharge duct.
Main accessories
Antifreeze thermostat.
Galvanised or inox 304L droplet eliminator (25 mm thick
metallic filter).
Standard connection frame (galvanised, 304L or 316L).
Standard connection with flanges (galvanised, 304L or 316L).
Pressure ports.
U-shaped and inclined manometers.
Differential pressure switch and Magnehelic needle manometer.
Flexible sleeves with flanges, standard and hygienic EVS-80 Se
class C.
Sand trap.
Umbrella awning.
IP 20 or IP 55 frequency inverter.
Factory-mounted IP 54 safety switch.
IP 54 servo-motors: 24 V or 230 V on-off and 0-10 V – 24 V AC/DC.
Aqu@Net controls (A, B, C, D & E systems) with RCL wired remote
controller and other accessories.
For the functions, see the "Controls" section on page 216.
Besides these options, please speak to our Sales Department for any other
configuration or function that is not listed as being available.
130
SLIM@IR SR TECHNICAL SPECIFICATIONS
SIZE
Air flow (at 2.7 m/s on the cooling coil)
Height (in-line – side access)
Height (in-line - access from the lower doors with hinges)
Height (in-line – access by hatch on body)
Height (stacked – side access)
Height (in-line or stakced – side access)
Width (side-by-side – side access)
COILS
Number of rows
Fin spacing for water-based coils
Total sensible cooling capacity (3 rows)
Total sensible cooling capacity (6 rows)
Total heating capacity (1 row)
Total heating capacity (3 rows)
Min electric heating capacity (1 stage/1~230 V)
Max electric heating capacity (3 stages/3~400 V)
FAN
0303
0306
0309
0312
0315
0318
m³/h
mm
mm
mm
mm
mm
mm
890
400
430
480
850
509
1314
1680
400
430
480
850
774
1844
2580
400
430
480
850
1079
2454
3490
400
430
480
850
1384
3064
4370
400
430
480
850
1689
3674
5270
400
430
480
850
1994
4284
mm
kW
kW
kW
kW
kW
kW
1, 2 and 3 rows for heating coils – 3, 4 and 6 rows for cooling coils
2.1 mm for heating coils – 2.5 mm for cooling coils
3.1/3.1
6.2/6.1
9.6/9.4
13/12.7
16/15.8
19.8/19.3
6.8/5.1
13/9.7
19.8/14.8
27/20.1
33.5/25
38.3/29.3
8.7
16.5
25.6
34.7
43.6
53.4
18.4
34.9
53.5
72.0
89.6
108.5
1.0
2.0
3.0
4.0
5.0
6.0
9.0
18.0
27.0
36.0
45.0
54.0
1
Plug fans with motors IP55 - F - 400 V/3Ph/50 HZ 3000 TR/M - IE2 (for motors over 0.75 kW)
1
1
2
2
2
1.1
1.5
2.2
3.0
4.4
1
1
2
3
3
0.70
3.0
0.70
3.0
1.40
6.0
2.10
9.0
2.10
9.0
Type
Number of fans
Maximum absorbed power
Motor nominal power
Max current
Type
Number of fans
Maximum absorbed power
Motor nominal power
Max current
kW
kW
A
kW
kW
A
3.0
EC plug fans
2
1.40
6.0
FILTER
Flat G4/F5/F7/F9 (50 mm) – Short bag F7/F9 (305 mm) – Long bag F7/F9 (500 mm)
– Compact F7/F9 (292 mm)*
Available filter
HEAT RECOVERY
Air flow
Plate heat exchanger standard efficiency (wet/dry) EN308
Available pressure fresh air/air intake
Length of the module
m³/h
%
Pa
mm
890
48.8/52.7
126/112
720
Plate heat exchanger high efficiency (wet/dry) EN308 m³/h 82.4/91.2
Available pressure fresh air/air intake %
Length of the module Pa
69/84
960
1680
46.1/50.9
169/150
1040
2580
46.2/50.9
177/158
1280
4370
49.1/53.7
112/106
720
5270
48.6/52.9
117/110
720
80.8/90
80.1/89.5
79.8/89.3
79.5/89.1
79.4/89.0
104/129
960
127/157
960
140/173
960
150/185
960
156/193
960
Cold coil performance for 32°C/40% and 7/12°C.
Hot coil performance for -7°C/90% and 90/70°C.
Outdoor configuration: side access only (height of cabinet without frame = 425 mm)
DN20 on all hot and cold coils.
Thermal efficiency of the plate heat exchangers based on fresh air temperature of -7°C/90% - 22°C/50%.
131
3490
47.4/52.6
216/192
1440
AIR HANDLING | AIR HANDLING UNITS
EFF@IR
CFI EC
400 to 4000
MAIN FEATURES
Air flow range: 250 to 5200 m3/h
Number of sizes: 6
Versions: stacked, horizontal, vertical
Insulation: 40 mm thick polyurethane foam
Efficiency from 85 to 93%
DESCRIPTION
High-efficiency plug-fan connected to EC motors
230-400V / 3 / 50-60Hz (to ErP-2015)
Dual-flow unit fitted with a high-efficiency, modular
counter-current flow plate heat exchanger made of
polypropylene in horizontal configuration, efficiency
from 85% to 93%, with an extruded aluminium
profiled structure and double skin prepainted steel
panels, insulated by injected polyurethane foam,
42 kg/m3 density, 40 mm thick.
Available in 4 configurations: standard, with electric
coil, with water-based reheating/recooling coil or with
R410A direct expansion coil (to be connected to a
remote heat pump not supplied).
Advantages
Ideal solution for low energy consumption buildings in residential,
commercial and industrial sectors.
G4 filtration (EN779) for extract air and F7 (EN779) with low
pressure loss for fresh air.
Plug-and-play solutions with an electrical panel and control by
pre-wired micro-processor.
100% bypass for automatic free-cooling.
Circular aeraulic connection at intake/exhaust.
Compliant with ErP-2015.
Main options
Control method:
VAV: variable air flow (available with CO2 or CO2/VOC air quality
control or humidity control). Controlled independently of air flows
(balance/imbalance). Please contact our Technical Department.
CAV: constant air flow.
COP: constant pressure.
Accessories for air filtration:
F9 filter with low pressure drop.
Pre-heating of input air.
Counter-current flow plate heat exchanger for applications
requiring non-combustible materials (for establishments open to
the public).
Main accessories
Controlled by microprocessor (see accessories manual):
EVO PH
EVO D PH
Sensors (for VAV control system only):
CO2 sensor EE80
CO2/VOC air quality sensor QPA 2002
Humidity sensor EE16
Safety accessories:
SKMF-R awning
Safety roofing T (for the horizontal configuration only)
Controls: besides these options, please speak to our Sales Department for any
other configuration or function that is not listed as being available.
Operating limits/recommendations
Indoor or outdoor installation, with temperatures between -15
and +50°C.
Avoid installing near sources of heat, vapour, inflammable and/or
explosive gas, dusty environments.
Depending on the indoor air temperature and the outdoor air
temperature, condensation may appear on the panels.
Units not adapted to specific environments (marine, etc.)
132
EFF@IR CFI EC AIR FLOW
STACKED
HORIZONTAL
VERTICAL
Size (air flow in m3/h - Efficiency in %) 0400 (650m3/h ‐ 79%)
0400 (580m3/h ‐ 78%)
0300 (250m3/h ‐ 90%)
Size (air flow in m3/h - Efficiency in %) 0800 (970m3/h ‐ 79%)
0700 (900m3/h ‐ 81%)
0500 (480m3/h ‐ 87%)
Size (air flow in m3/h - Efficiency in %) 1900 (2300m3/h ‐ 80%)
1700 (2100m3/h ‐ 81%)
Size (air flow in m3/h - Efficiency in %) 2500 (3150m3/h ‐ 80%)
2400 (3100m3/h ‐ 79%)
AIR FLOW AND SIZE for 200 Pa available
Size (air flow in m /h - Efficiency in %) 3000 (4400m /h ‐ 79%)
3
3
Size (air flow in m3/h - Efficiency in %) 4000 (5200m3/h ‐ 80%)
EFF@IR CFI EC STACKED TECHNICAL SPECIFICATIONS
WATER POST HEATING/RECOOLING COIL*
SIZES
Water 70/60°C
(T°ext. = -5°C ; T°int. = 20°C)
Water 45/35°C
(T°ext. = -5°C ; T°int. = 20°C)
Water flow Δp water
(l/h)
(kPa)
Water flow Δp water
(l/h)
(kPa)
Power
(kW)
Water 7/12°C
(T°ext. = -5°C ; T°int. = 20°C)
Power
(kW)
Water flow Δp water
(l/h)
(kPa)
Rows
(No.)
CFI-EC SUP 400 4
Ø
H2O
1/2"
Length of
tubes
60
Power
(kW)
7.0
611
7.7
3.1
272
1.8
4.2
722
12.4
CFI-EC SUP 800 4
3/4"
60
11.1
976
4.4
4.8
412
3.1
6.6
1127
5.4
CFI-EC SUP 1900 4
3/4"
60
22.3
1957
5.8
9.4
813
3.3
12.8
2202
7.2
CFI-EC SUP 2500 3
1"
60
29.6
2591
8.7
13.1
1137
4.6
18.0
3096
13.9
CFI-EC SUP 3000 3
1"
60
38.9
3412
16.7
17.7
1528
6.6
23.6
4059
28.5
CFI-EC SUP 4000 3
1" 1/4
60
50.9
4458
7.5
22.5
1951
6.1
31.2
5354
11.3
* For specific conditions, please contact our commercial department.
ELECTRIC COIL
SIZES
Power (kW)
Voltage
(V)
Phase
(No.)
Stage *
(No.)
Abs. current
(A)
T° fresh air
(°C)
T° air
Internal (°C)
T° output air
(°C)
CFI-EC SUP 400 2
230V-1-50Hz
1
1
8.70
-10
20
25.24
CFI-EC SUP 800 3
230V-1-50Hz 1
1
13.04
-10
20
24.85
CFI-EC SUP 1900 6
230V-1-50Hz 1
1
26.09
-10
20
24.75
CFI-EC SUP 2500 8
230V-1-50Hz 1
1
34.78
-10
20
23.99
CFI-EC SUP 2500 8
400V-3-50Hz 3
1
11.55
-10
20
23.99
CFI-EC SUP 3000 12
400V-3-50Hz 3
1
17.32
-10
20
25.09
CFI-EC SUP 4000 16
400V-3-50Hz 3
1
23.09
-10
20
25.60
* For electric coils linked to an EVO PH (local) or EVO PH D (Modbus), 0-10 V control voltage
ELECTRICS
SIZES
FANS*
Power (W)
CFI-EC SUP 400 170
CFI-EC SUP
Power supply
Max. current (230V)
Insulation class
Power supply - IP
Max. current
230V, 50/60 Hz 1F
1.20 A
IP 44 - B class
230V-50Hz-1F_IP20
2.50 A
CFI-EC SUP 800 170
230V, 50/60 Hz 1F
1.40 A
IP 54 - B class
230V-50Hz-1F_IP20
2.90 A
CFI-EC SUP 1900 448
230V, 50/60 Hz 1F
2.80 A
IP 54 - B class
230V-50Hz-1F_IP20
5.70 A
CFI-EC SUP 2500 715
230V, 50/60 Hz 1F
3.10 A
IP 54 - B class
230V-50Hz-1F_IP20
6.30 A
CFI-EC SUP 3000 1270
400V, 50/60 Hz 1F
5.60 A
IP 54 - B class
230V-50Hz-1F_IP20
11.30 A
CFI-EC SUP 4000 1400
400V, 50/60 Hz 1F
6.00 A
IP 54 - B class
230V-50Hz-1F_IP20
12.1 A
* Values for a single fan
Stacked configuration
Fresh air
Intake air
Extract air
Blown air
133
AIR HANDLING | AIR HANDLING UNITS
EFF@IR CFI EC HORIZONTAL TECHNICAL SPECIFICATIONS
WATER POST HEATING/RECOOLING COIL*
SIZES
Water 70/60°C
(T°ext. = -5°C ; T°int. = 20°C)
Water 45/35°C
(T°ext. = -5°C ; T°int. = 20°C)
Water flow Δp water
(l/h)
(kPa)
Water flow Δp water
(l/h)
(kPa)
Power
(kW)
Water 7/12°C
(T°ext. = -5°C ; T°int. = 20°C)
Power
(kW)
Water flow Δp water
(l/h)
(kPa)
Rows
(No.)
CFI-EC HOR 400 4
Ø
H2O
1/2"
Length of
tubes
60
Power
(kW)
5.5
486
4.3
2.4
210
1.0
3.7
632
8.3
CFI-EC HOR 700 4
3/4"
60
10.0
876
6.0
4.5
3931
3.7
7.0
1200
9.6
CFI-EC HOR 1700 4
3/4"
60
19.8
1739
5.8
8.3
714
3.5
10.1
1727
6.2
CFI-EC HOR 2400 2
3/4"
60
28.8
2523
8
12.5
1079
4.6
12.0
2058
9.0
* For specific conditions, please contact our commercial department.
ELECTRIC COIL
SIZES
Power (kW)
Voltage
(V)
Phase
(No.)
Stage *
(No.)
Abs. current
(A)
T° fresh air
(°C)
T° air
Internal (°C)
T° output air
(°C)
CFI-EC HOR 400 2
230V-1-50Hz
1
1
8.70
-10
20
25.07
CFI-EC HOR 700 3
230V-1-50Hz 1
1
13.04
-10
20
24.68
CFI-EC HOR 1700 6
230V-1-50Hz 1
1
26.09
-10
20
24.32
CFI-EC HOR 2400 8
230V-1-50Hz 1
1
34.78
-10
20
23.56
CFI-EC HOR 2400 8
400V-3-50Hz 3
1
11.55
-10
20
23.56
* For electric coils linked to an EVO PH (local) or EVO PH D (Modbus), 0-10 V control voltage
ELECTRICS
SIZES
FANS*
Power (W)
CFI-EC HOR 400 170x2
CFI-EC SUP
Power supply
Max. current (230V)
Insulation class
Power supply - IP
Max. current
230V, 50/60 Hz 1F
1.20 A
IP 44 - B class
230V-50Hz-1F_IP20
2.50 A
CFI-EC HOR 700 170x2
230V, 50/60 Hz 1F
1.40 A
IP 54 - B class
230V-50Hz-1F_IP20
2.90 A
CFI-EC HOR 1700 448x2
230V, 50/60 Hz 1F
2.80 A
IP 54 - B class
230V-50Hz-1F_IP20
5.70 A
CFI-EC HOR 2400 715
230V, 50/60 Hz 1F
3.10 A
IP 54 - B class
230V-50Hz-1F_IP20
6.30 A
* Values for a single fan
Horizontal configuration
Fresh air
Intake air
Extract air
Blown air
Service side
134
EFF@IR CFI EC VERTICAL TECHNICAL SPECIFICATIONS
[BA-AC] WATER POST HEATING COIL
SIZES
Water 80/70°C
(T°ext. = -5°C ; T°int. = 20°C)
Flow
(m3/h)
CFI-EC VER 300 400
Ø conn.
(mm)
150
CFI-EC VER 500 600
150
Ø
H2O
1/2"
Power
(kW)
T° air exhaust
(°C)
Δp air
(Pa)
Δp air
(kPa)
330x260x200
Rows
(No.)
1
0.88
23.60*
18
0.9
330x260x200
1
1/2"
1.07
21.95*
34
0.9
Coil dimensions
* 400 - Winter: Fresh air -5°C / 80% - Internal air 20°C / 50% - Air mand. 17.5°C / 16.8%
* 600 - Winter: Fresh air -5°C / 80% - Internal air 20°C / 50% - Air mand. 16.7°C / 17.8%
[REL-M] ELECTRIC POST HEATING COIL
SIZES
T° output air
(°C)
Ø conn.
(mm)
Flow
(m3/h)
CFI-EC VER 300 400
Power
(kW)
0.5
Voltage
(V)
230V-1-50Hz
Phase
(No.)
1
Stage *
(No.)
1
Abs. current
(A)
2.2
21*
150x300
CFI-EC VER 500 600
0.5
230V-1-50Hz
1
1
2.2
20*
150x300
* 400 - Winter: Fresh air -5°C / 80% - Internal air 20°C / 50% - Air mand. 17.5°C / 16.8%
* 600 - Winter: Fresh air -5°C / 80% - Internal air 20°C / 50% - Air mand. 16.7°C / 17.8%
[BA-AFC] WATER-BASED POST HEATING/RECOOLING COIL
TYPE
BA-AFC
350-150
T° water intake/discharge 70°/60°
BA-AFC
500-150
BA-AFC
500-180
45°/35°
7°/12°
70°/60°
45°/35°
7°/12°
70°/60°
45°/35°
7°/12°
Air flow (m3/h) 400
400
400
600
600
600
600
600
600
Ø Air connection (mm) 150
150
150
150
150
150
180
180
180
Ø Water connection (") 1/2"
1/2"
1/2"
1/2"
1/2"
1/2"
1/2"
1/2"
1/2"
19
19
19
19
19
19
19
19
Ø Condensate (mm) 19
Rows (No.) 4
4
4
5
5
5
5
5
5
1.35
1.89
6.8
3.1
4.3
6.8
3.1
4.3
Air pressure loss (Pa) 35
35
36
45
44
45
45
44
45
Water pressure loss (Pa) 1.3
0.9
1.8
8
2.1
15
8
2.1
15
Nominal power (kW) 3.3
Dimension [AxBxC] (mm)
T° of ventilation (°C) 41.8*
404x355x210
27.1*
464x355x270
20.9**
50.0*
31.9*
464x355x270
18.0**
50.0*
31.9*
18.0**
* 400 - Winter: Fresh air -5°C / 80% - Internal air 20°C hr 50% - Air mand. 17.5°C / 16.8% ** Summer: Fresh air 34°C / 50% - Internal air 27°C / 45% - Blown air 28.1°C / 70%
* 600 - Winter: Fresh air -5°C / 80% - Internal air 20°C hr 50% - Air mand. 16.7°C / 17.8 ** Summer: Fresh air 34°C / 50% - Internal air 27°C / 45% - Blown air 28.1°C / 70%
ELECTRICS
SIZES
FANS*
Power (W)
CFI-EC SUP
Power supply
Max. current (230V)
Insulation class
Power supply - IP
Max. current
CFI-EC VER 300 71x2
230V, 50/60 Hz 1F
0.50 A
IP 44 - B class
230V-50Hz-1F
1.20 A
CFI-EC VER 500 170x2
230V, 50/60 Hz 1F
1.10 A
IP 44 - B class
230V-50Hz-1F
2.50 A
* Values for a single fan
Vertical configuration
Intake air
Extract air
Blown air
Fresh air
135
AIR HANDLING | AIR HANDLING UNITS
EFF@IR HP
HP S/HP L 1 to 6
HP LS 400 to 3500
MAIN FEATURES
Hot water coil capacity: 2.2 to 34.5 kW
Electric coil power: 2 to 12 kW
Air flow range: 400 to 5600 m3/h
Number of sizes: 6 (HP S/HP L) - 5 (HP LS)
DESCRIPTION
A dual flow heat recovery unit (efficiency 50% to
70%) in horizontal or vertical configuration, available
in two versions:
HP S version (coils in duct) / HP L (coils in CTA)
Extruded aluminium profiled structure with
rounded corners.
Double-skin panels made of white plasticized steel,
insulated by 25 mm thick injected polyurethane
foam.
Access from side/below for maintenance and
servicing.
Pressure ports for measuring filter pressure losses.
Condensate diasposal system.
HP LS version (bypass integrated in the CTA)
Free-standing structure cabinet made of
galvanised steel.
Low height suitable for false ceilings.
Side access for maintenance and servicing.
Condensate disposal system.
Single skin panels:
- 10/10 mm thick steel wall.
- External cladding with adhesive 5 mm thick
thermal-acoustic polyethylene insulation.
Double skin panels:
- Free-standing galvanised steel structure with 25
mm thick rock wool insulation, 110 kg/m3 density.
Operating limits/recommendations
Indoor or outdoor installation, with temperatures between -15
and +50°C.
Avoid installing near sources of heat, vapour, inflammable and/or
explosive gas, dusty environments.
Depending on the indoor air temperature and the outdoor air
temperature, condensation may appear on the panels.
Units not adapted to specific environments (marine, etc.)
Advantages
Ideal solution for ventilation of buildings in the commercial sector,
available:
- Without controls.
- Plug-and-play solutions with a pre-wired electrical panel and
control by on-board micro-processor.
Main options
Defrosting and/or reheating for installation in ducts:
RCF-SC: electric coil.
RCFE-SCT: electric coil with electronic controls.
RCF-SCTTC: electric coil with thermostatic controls.
BA-AC: hot water coil (80/70°C) > for the HP S version only.
BA-AC: warm water coil (45/35°C) > for the HP S and HP LS
versions only.
Recooling for installation in ducts:
BA-AF: cold water coil with insulated plenum.
Air filtration:
F9 filter with low pressure drop.
Main accessories
Controls (for standard version only):
CV4: 4-speed switch for motors 230 V/1 ph/50 Hz.
CV3: 3-speed switch for motors 230 V/1 ph/50 Hz.
RVT 6A and RVT 9A: speed regulator for motors 400 V/3 ph/50 Hz.
Controlled by microprocessor (see accessories manual):
EVO PH
EVO D PH
Sensors:
EE80: CO2 sensor
QPA 2002: CO2/VOC air quality sensor
EE16: humidity sensor
Safety accessories:
SKMF-R: awning
T: safety roofing
Controls: besides these options, please speak to our Sales Department for any
other configuration or function that is not listed as being available.
136
EFF@IR HP S / HP L TECHNICAL SPECIFICATIONS
SIZE
Nominal air flow m³/h
Available static pressure* Pa
1
2
3
4
5
6
400
85
800
100
1900
140
3000
180
4500
100
5600
120
SOUND LEVELS ***
Lw speed 1 (transmitted noise) dB(A)
29
42
Lw speed 2 (transmitted noise) dB(A)
37
48
65
52
Lw speed 3 (transmitted noise) dB(A)
43
53
67
68
Lw speed 4 (transmitted noise) dB(A)
48
55
69
79
75
DIMENSION **** AND WEIGHT FOR HORIZONTAL UNITS FOR HP S (COILS IN DUCTS WITHOUT BYPASS ON THE PLATE)
Height (without bypass) mm
345
360
535
630
855
Height (with bypass) mm
450
465
640
735
855
Width mm
640
820
1040
1270
1200
Length mm
960
1230
1560
1905
1550
Weight kg
40
56
110
155
195
Circuit connections – input/outlet diameter mm
200
250
315
355
450
HEAT RECOVERY **
Yield %
50.7
53.9
51.6
52.5
54
EFF@IR HP LS TECHNICAL SPECIFICATIONS
SIZE
Nominal air flow m³/h
Available static pressure* Pa
SOUND LEVELS FOR SINGLE SKIN ***
Lw speed 1 (transmitted noise) dB(A)
Lw speed 2 (transmitted noise) dB(A)
Lw speed 3 (transmitted noise) dB(A)
Lw speed 4 (transmitted noise) dB(A)
DIMENSION **** AND WEIGHT FOR HORIZONTAL UNITS
Height (with or without internal bypass) mm
Width mm
Length mm
Weight kg
Circuit connections – input/outlet diameter mm
HEAT RECOVERY **
Yield %
77
855
855
1200
1550
200
450
52.5
400
800
1600
2500
3500
485
100
885
100
1600
100
2680
100
3500
100
33
41
47
52
45
52
57
59
57
59
61
59
61
63
57
65
71
360
620
960
55
200
360
730
56
250
500
870
1560
110
315
550
1040
1905
155
355
550
1300
1550
195
450
51.2
51.6
54.2
52.7
52.3
550x2
4
4x2
8
3
750x2
4
8.1x2
16.2
3
750x2
4
3.1x2
6.2
1
8
230/1 ou
400/3
12
12
400/3
400/3
COMMON DATA TECHNICAL SPECIFICATIONS
FAN
Installed fan power
Pole
Max absorbed current
Max absorbed current
Fan speed
Protection class/unit insulation
Electric power supply
W
Num.
A
A
150x2
2
0.66x2
1.32
4
355x2
2
1.55x2
3.1
4
V/Ph/Hz
373x2
4
2.75x2
5.5
3
IP20/F
230V-1-50Hz
1500x2
4
5.6x2
11.2
1
IP55/F
400V-3-50Hz
FILTER
Filtration class for exhaust air/fresh air EN779
ELECTRIC DFROST HEATING
Nominal power kW
Voltage/phase V/ph
G4/F7
2
4
6
230/1
230/1
230/1
8
230/1 ou
400/3
For other features, please refer to the technical instructions or our Technical Department.
*The values refer to the nominal air flow having overcome the pressure losses of the heat recovery device and the filters.
**The values refer to the following conditions: Tbs air ext. = -5°C, Tbs ambiance = 20°C, HR ambiance = 50%, nominal air flow.
***Sound levels compliant with UNI EN ISO 3747 (ΔLfA ≥ 7 dB for each measuring point, accuracy class 2).
****For the bypass add 105 mm to the height for sizes 1 to 4 and 0 mm to the height for sizes 5 and 6.
Configurations
Horizontal configuration HP S / HP L
Horizontal configuration HP LS
Vertical configuration HP LS
137
AIR HANDLING | AIR HANDLING UNITS
EFF@IR
WRI EC
MAIN FEATURES
Dual-flow unit fitted with a high efficiency aluminium
thermal wheel
Version: stacked
Ideal solution for low energy consumption buildings
in the residential, commercial and industrial sector.
Filtration and preheating at fresh air intake
Stacked configuration (installation on ground)
Unit supplied wired from factory (plug-&-play
solution). Available controls:
- EVO PH (with remote controller)
- EVO D PH (no remote controller – for control via
the GTC/GTB using the ModBus communication
protocol)
DESCRIPTION
Aluminium profiled cabinet structure
Double skin panel, 36 mm insulation with injected
polyurethane foam
Circular duct connection
Easy access for maintenance
Fully automatic bypass
Fans providing high pressure and low energy
consumption.
Other
FAN
High-efficiency plug-fan connected to EC motors 230-400V / 3 /
50-60Hz (to ErP-2015)
HEAT RECOVERY
High efficiency aluminium thermal wheel (η= min. 75% ;
max >90%)
FILTERS
G4 on air intake
F7 low pressure loss on fresh air
RANGE
5 sizes from 900 m3/h to 6,200 m3/h (@ 100 Pa)
AVAILABLE VERSIONS
Standard (no coil)
With electric post-coil
With water heating/recooling post-coil
With direct expansion R410a coil
AVAILABLE CONTROL SYSTEM (FACTORY INSTALLED ON REQUEST)
Thermal wheel with constant rotation speed and variable rotation
speed [RR]:
- VAV: Variable air flow
- CAV: Constant air flow
- COP: Variable air flow at constant pressure
ACCESSORIES AVAILABLE ON REQUEST
Optional sensors (for VAV control system only):
- EE80 CO2 sensor
- QPA 2002 CO2/VOC air quality sensor
- EE16 humidity sensor
Pre-heating:
- RCF-SC: electric pre-heating coil
Accessories for air filtration:
- F9 in low pressure loss version
Accessories:
- T safety roofing
- SKMF-R awning
- SIPH siphon
Controls: besides these options, please contact our Sales Department for
any other configuration or function not listed.
138
EFF@IR WRI EC TECHNICAL SPECIFICATIONS
[BA-AF/AC] WATER POST HEATING/RECOOLING COIL*
SIZES
Water 70/60°C
(T°ext. = -5°C ; T°int. = 20°C)
WRI-EC SUP 500
WRI-EC SUP 1500
WRI-EC SUP 2400
WRI-EC SUP 4000
WRI-EC SUP 5200
Ø
H2O
3/4"
3/4"
1"
1" 1/4
1" 1/4
Rows
(No.)
3
3
3
3
3
Length of
tubes
60
60
60
60
60
Water 45/35°C
(T°ext. = -5°C ; T°int. = 20°C)
Water 7/12°C
(T°ext. = -5°C ; T°int. = 20°C)
Power
(kW)
Water flow Δp water
(l/h)
(kPa)
Power
(kW)
Water flow Δp water
(l/h)
(kPa)
Power
(kW)
Water flow Δp water
(l/h)
(kPa)
7.3
16.4
24.8
33.9
48.3
644
1438
2178
2972
4231
3.2
7.7
11.5
15.9
23.5
276
663
997
1376
2033
4.0
9.2
14.0
18.5
26.2
686
1577
2401
3186
4510
4.0
12.2
11.8
9.1
21.9
3.0
5.0
4.9
4.4
7.3
4.5
17.3
17.2
17.2
30.4
* For specific conditions, please contact your technical contact person or use the selection software.
[REL-M/T] ELECTRIC COIL
SIZES
WRI-EC SUP 500
WRI-EC SUP 1500
WRI-EC SUP 2400
WRI-EC SUP 4000
WRI-EC SUP 5200
Power (kW)
Voltage
(V)
Phase
(No.)
Stage *
(No.)
Abs. current
(A)
T° fresh air
(°C)
T° air
Internal (°C)
T° output air
(°C)
4
6
8
12
16
230V-1-50Hz
230V-1-50Hz
400V-3-50Hz
400V-3-50Hz
400V-3-50Hz
1
1
3
3
3
1
1
1
1
1
17.4
26.1
11.6
17.4
23.2
-10
-10
-10
-10
-10
20
20
20
20
20
28.0
21.9
21.3
21.2
20.3
ELECTRICS
SIZES
FANS*
WRI-EC SUP 500
WRI-EC SUP 1500
WRI-EC SUP 2400
WRI-EC SUP 4000
WRI-EC SUP 5200
* Values for a single fan
Power (W)
Power supply
170
448
715
1400
1850
230V, 50/60 Hz 1F
230V, 50/60 Hz 1F
230V, 50/60 Hz 1F
230V, 50/60 Hz 1F
400V, 50/60 Hz 3F
1.40 A
2.80 A
3.10 A
6.00 A
2.90 A
WRI-EC SUP
Power (W)
Power supply
IP 54 - B class
IP 54 - B class
IP 54 - B class
IP 54 - B class
IP 54 - B class
230V-50Hz-1F_IP20
230V-50Hz-1F_IP20
230V-50Hz-1F_IP20
230V-50Hz-1F_IP20
400V-50Hz-3F_IP20
Stacked configuration
Fresh air
Blown air
Extract air
Intake air
139
3.00 A
6.00 A
7.00 A
13.4 A
7.20 A
AIR HANDLING | AIR HANDLING UNITS
PREMI@IR
DOUBLE
DECK
COMPACT
Win
Clim
MAIN FEATURES
Chilled water coil power: 6,4 to 185 kW
Hot water coil power: 2 to 185 kW
Number of sizes: 7
Air flow range: 800 to 18.000 m3/h
Insulation: glass wool, rock wool, polyurethane foam
DESCRIPTION
With 7 models, from 800 to 18.000 m3/h, this
range is suitable for comfort, hygiene and industrial
applications.
An innovative, robust and free-standing structure
with perfectly smooth tunnel, including at the junction
between modules, avoids any microbial development
due to accumulation of dust.
The double-walled panels are covered on 6 sides to
avoid any penetration of humidity. They are fitted with
fire-rated thermal insulation.
Main options
2 types of thermal wheels (standard efficiency and high efficiency)
2 types of plate heat exchangers (standard, medium and high
efficiency).
Removable condensate tray for an ideal hygienic aspect.
A choice of 3 types of damper: standard, class 3 waterproof and
class 4 waterproof to EN 1751.
Wide choice of material: galvanised, pre-painted, inox 304L or 316L
on the internal and/or external skin.
Direct drive fans, epoxy paint on fan, etc.
Main accessories
Advantages
Since Premi@ir air handling units are manufactured to order
according to the specific needs of each installation, they offer an
infinite choice of solutions.
Class T2 – TB2 – L2 – F9 – D1 certified by EUROVENT.
Configurations available: double deck.
Suitable for indoor or outdoor installation.
Access door without thermal bridge thanks to polyamide hinges
and external rotor that doesn't transverse the door.
Wide choice of filter classes and types: flat, pocket and rigid
from G4 to H14.
Wide choice of coils available as standard from 2 to 8 rows
with fin lengths from 2.1 - 2.5 - 3.2 mm. Fins made of aluminium,
aluminium epoxy or copper. As an option, the coils can be fully
protected by Blygold cladding for harsh environments.
Powerful selection software with user-friendly graphical interface
allows you to make all kinds of simulations. To optimise the
product ranges, the "execution" quality documents (plans in DXF
format) are provided from the prototype phase.
Flexible connection M0 class.
Internal lighting 24 V or 230 V with waterproof switch.
Viewing window in access door.
Rain hoods.
U-shaped and inclined manometers.
Operating limits/recommendations
1500 Pa maximum on the positive and negative pressure panels.
-20°C minimum for fresh air.
Depending on the indoor air temperature and the outdoor air
temperature, condensation may appear on the panels.
Controls: besides these options, please contact our Sales Department for
any other configuration or function not listed.
140
PREMI@IR PR TECHNICAL SPECIFICATIONS
SIZE
Nominal air flow for 82% efficiency (EN308) at
m3/h
the wheel
0306
0408
0409
0612
0715
0918
1121
1400
2300
3400
5600
8700
12600
17200
Air velocity in the tunnel m/s
1.57
1.62
1.68
1.76
1.81
1.86
1.90
Height with body mm
1058
1230
1395
1700
2005
2310
2615
825
1020
1200
1435
1740
2045
2350
Length main cabinet 'only' with wheel mm
Width (without roof) mm
1630
1690
2026
2296
2672
2744
2944
Length main cabinet 'only' with plates mm
2230
2440
3032
N/A
N/A
N/A
N/A
FILTER
Support frame
Class F9 in accordance with standard EN1886
Available filters
G4 & M5 flat - F7 & F9 pocket to EN 779
HEAT RECOVERY
Efficiency (EN 308) of the "very high efficiency" % /
wheel (range of 1.5 mm) PDC
Classification EN13053 of the "very high
Class
efficiency" wheel
Efficiency (EN 308) of the "high efficiency" wheel % /
(range of 2.0 mm) PDC
Classification EN13053 of the "high efficiency"
Class
wheel
Efficiency (EN 308) of the counter-flow plate
%/
PDC
Classification EN13053 of the counter-flow plate Class
82.2% 200Pa
82.1% 202Pa
82.2% 200Pa
82.1% 202Pa
82.1% 201Pa
82.0% 202Pa
82.0% 203Pa
H1
H1
H1
H1
H1
H1
H1
73.1% 117Pa
73.0% 118Pa
73.1 % 118Pa
73.0 % 118Pa
73.1 % 118Pa
73.0 % 118Pa
73.0 % 119Pa
H1
H1
H1
H1
H1
H1
H1
86.6% 166Pa
87.6% 172Pa
89.0% 177Pa
N/A
N/A
N/A
N/A
H1
H1
H1
N/A
N/A
N/A
N/A
56.7
98.2
COILS
Rows
Heating: 1 to 3 rows - Cooling: 3 to 6 rows
Fins spacing mm
Total cooling capacity (4 rows - 2.5 mm)** kW
2.1 - 2.5 - 3.2
6.4
10.8
14.8
24.7
39.0
Sensible cooling capacity (4 rows - 2.5 mm)** kW
4.8
8.0
11.4
18.8
29.2
42.2
72.4
Connection diameter of the 4-row cold coil DN
25
25
32
40
50
50
60
Heating capacity (1 row - 2.5 mm) kW
2.0
3.3
4.7
7.8
12.1
17.5
24.3
Connection diameter of the 1-row hot coil DN
20
20
20
25
32
32
40
ELECTRICAL COIL (option)
Min. electrical power (3 stages) kW
3.0
6.0
9.0
12.0
30.0
36.0
54.0
Max. electrical power (3 stages) kW
12.0
18.0
27.0
48.0
75.0
108.0
144.0
Wheel 82% - Main block alone Weight N/A
N/A
567
838
1213
1637
2014
N/A
N/A
1734
1636
1662
1658
1696
Wheel 82% - Main cabinet only Weight 315
440
561
797
1187
1502
1848
1859
1931
1594
1807
1617
1774
407
567
847
1085
1437
1768
2002
2164
1673
1749
1723
1944
DIMENSIONS AND WEIGHTS - (mm and kg)
W/
SFPv Global (intake + supply) with inverter loss
(m3.s)
W/
SFPv Global (intake + supply)
(m3.s)
1712
Wheel 82% - Main cabinet only Weight 329
W/
SFPv Global (intake + supply)
(m3.s)
1928
Hot water coil section (HM0) Length 450
1 row - without valves Weight 62
Impact on the SFPv (value to be added)
W/
(m3.s)
28
Chilled water coil section (HM1) Length 500
4 rows - without valves Weight 72
Impact on the SFPv (value to be added)
W/
(m3.s)
180
Electrical coil section (HM0-E) Length 800
Min. power - 3 stages Weight 89
Impact on the SFPv (value to be added)
W/
(m3.s)
104
450
450
450
450
450
450
72
76
88
105
122
158
28
23
22
20
21
20
500
500
500
500
500
500
84
89
112
141
171
184
151
97
95
81
81
80
800
800
800
800
800
800
103
114
138
174
204
225
90
64
60
55
56
55
Performances of heat recovery devices given for a balanced nominal air flow. -7°C/90% for fresh air and 22°C/50% for the intake in winter; 32°C/40% for fresh air
and 25°C/50% for the intake in summer - thermal wheel with the highest efficiency available. Pt = Ptotal = Dynamic pressure of the fan + Static pressure in the
ducts + Static pressure in the unit. PDC = pressure loss.
** Performance calculated taking into account the temperature at output of the very high efficiency wheel for a unit output of 21°C in winter (water 80°C/60°C)
and 16°C in summer (water: 7°C/12°C).
*** SFPv communicated for a Premi@ir version PR DFC without coils, with on the discharge and intake: F7 bag filters; 200 Pa static pressure, dampers.
Indicative values, please refer to the software for the accurate performance at the working point.
141
AIR HANDLING | AIR HANDLING UNITS
PREMI@IR
20 à 360
Win
Clim
MAIN FEATURES
Cooling capacity: from 10 to 175 kW
Heating capacity: from 20 to 356 kW
Sizes: 10
Air flow: from 1,000 to 30,000 m³/h
Insulation: glass wool, rock wool, polyurethane
foam
DESCRIPTION
With 10 models, from 1000 to 30000 m³/h, this
range is suitable for comfort, hygienic and industrial
applications.
Innovative, robust free-standing composition with a
perfectly smooth tunnel, including at module junctions, which prevents any microbial development due
to the accumulation of dust.
The double skin panels are covered on six sides to
prevent any penetration of humidity. They are fitted
with fireproof thermal insulation.
Main options
2 types of thermal wheels (standard and high efficiency).
3 types of plates (standard, medium and high efficiency).
Removable condensate tray or dry tray with 3 slopes for
hygienic applications.
A choice of 3 types of damper: standard, class 3 and
class 4 to EN 1751.
Wide choice of material: galvanised, pre-coated, stainless steel
304L (1.4307) or 316L (1.4404) on the internal and/or external skin.
Wide choice of fans: action, reaction or plug-fans.
Main accessories
Connection frame and flexible sleeve M0.
Internal lighting 24 V or 230 V with waterproof switch.
Viewing window in access doors.
Rain hood.
Roof.
Fresh air intake.
Bird screen.
Pressure taping points.
Inclined and U-shaped manometers.
Blank sections with different lengths.
Rigid connection frame.
3-point actuators, on-off or 0-10 V.
Advantages
Since Premi@ir units are manufactured to order, scrupulously
complying with the specific needs of each installation, they offer an
infinite choice of solutions.
Eurovent certification T2 - TB2 - L2 - F9 - D1.
Different combinations available: In-line, stacked or side-by-side.
Suitable for indoor or outdoor installation.(*)
Access door without thermal bridge thanks to polyamide hinge and
an external rotor that doesn't transverse the door.
Wide choice of filter: flat, bag or compact from G4 to H14.
Wide choice of coils supplied as standard from 2 rows to 8
rows with a fins spacing from 2.1, 2.5 or 3.2 mm with fins made
of aluminium, aluminium epoxy or copper and/or Blygold(R) if the
environmental conditions are harsh.
Powerful selection software with user-friendly interface enabling all
kinds of simulations. To optimise presentation of the product ranges,
the "execution" quality documents (plans in DXF format) are provided
from the prototype phase.
Operating limits/recommendations
1500 Pa maximum on the positive pressure and negative pressure
panel.
40°C maximum on the motor without under-dimensioning factor of
the motor power. 60°C with under-dimensioning factor of 0.82 on the
motor power.
-20°C minimum for the air intake.
(*) Condensation may form on the panels depending on the
temperature of the indoor and outdoor air.
Controls: besides these options, please speak to our Sales Department for any
other configuration or function that is not listed as being available.
142
PREMI@IR PR TECHNICAL SPECIFICATIONS
SIZE
20
40
60
90
120
160
200
240
300
360
Air flow (at 2.9 m/s on the cooling coil) m³/h
1650
3300
5500
7500
9100
12850
16600
20200
24400
2950
Height with body (STD or side-by-side)
Height with chassis (double deck)
Width (STD or double deck)
Width (side-by-side)
mm
mm
mm
mm
685
1220
715
1430
1045
1940
715
1430
1045
1940
1020
2040
1045
1940
1325
2650
1225
2300
1325
2650
1555
2960
1325
2650
1555
2960
1630
3260
1555
2960
1935
3870
1845
3540
1935
3870
2145
4140
1935
3870
Number of rows
Fin spacing
Total cooling capacity (for 4 rows – 2.5 mm)
Sensible cooling capacity (for 4 rows – 2.5 mm)
Cooling coil connection (4 rows)
Heating capacity (for 2 rows – 2.5 mm)
Heating coil connection (2 rows)
Min electric heating capacity
Max electric heating capacity
mm
kW
kW
DN
kW
DN
kW
kW
123.2
109.8
65
246.9
50
12.0
252.0
147.0
131.9
65
269.9
50
18.0
396.0
171.8
157.0
65
355.6
50
21.0
462.0
560
710
710
900
630
800
800
1000
COILS
1 to 8 in heating – 2 to 8 in cooling
2.1 - 2.5 - 3.2
54.7
77.3
49.2
69.4
32
50
110.6 155.4
32
32
10.5
12.0
147.0 168.0
10.0
9.0
25
19.9
25
3.75
22.5
19.0
17.5
25
40.3
25
9.0
54.0
33.4
29.8
32
66.9
25
9.0
90.0
45.1
40.5
32
92.0
32
9.0
126.0
104.3
91.4
50
201.7
32
12.0
216.0
160
200
200
250
200
250
315
400
Action - Reaction – Reinforced reaction – Plug fan
250
280
355
400
450
500
315
355
450
500
560
630
315
355
400
500
560
630
400
450
500
630
710
800
FANS
Type available
Min size of centrifugal fan
Max size of centrifugal fan
Min size of Plug fan
Max size of Plug fan
FILTER
Filter frame
Available filter
Class F9 (as per EN 1886)
G2 (metal) and flat G4 – bag F5, F7 and F8 – Rigid F7 and F9 - H10 to H14 HEPA
HEAT RECOVERY
Run around coil
Efficiency at standard yield of thermal wheel
Efficiency at increased yield of thermal wheel
Length of section at STD yield of plate heat exchanger
Efficiency at medium yield of plate heat exchanger
Efficiency at increased yield of plate heat exchanger
Dimensions and weight (in mm and kg)
%
%
%
%
%
48
60
72
68
83
20
Extraction (type A) Length 820
Single fan, reaction Weight 99
100% fresh air (type D) – Flat G4 filter + F7 bag filter + Length 2120
2R heating coil + 4R cooling coil + reaction fan Weight 261
2-way mixing box (type G) Length 2420
2-way mixing section + type D Weight 293
Dual flow in-line (type J) Length 3660
Type A + 3-way mixing in-line + type D Weight 427
Stacked (type I) – type G on fresh air Length 3440
Type A + flat G4 filter on the return Weight 538
From 2 to 8 rows
45
53
58
59
70
73
59
50
74
75
46
59
72
34
73
45
59
72
56
75
46
59
72
70
77
40
60
90
120
920
136
2220
342
2620
385
4060
563
3840
692
1120
189
2420
454
2940
524
4460
749
4060
944
1220
226
2520
525
3040
598
4660
848
4160
1057
1520
315
2620
610
3240
709
5060
1021
4560
1265
53
59
73
54
76
51
57
71
50
73
49
58
73
55
74
50
61
70
50
71
160
200
240
300
360
1520
371
2940
805
3540
902
5780
1334
4860
1568
1620
442
3040
949
3640
1059
5980
1560
5160
1971
1720
539
3240
1184
3840
1305
6280
1912
5480
2374
1820
723
3240
1321
3840
1464
6380
2247
5680
2782
2020
891
3340
1647
4140
1843
7080
2839
6280
3419
Performances of cooling coils for 32°C/40% - 7-12°C and performances of heating coils for -7°C/90% - 90/70°C.
Configurations
CONFIGURATION A
CONFIGURATION D
CONFIGURATION G
CONFIGURATION J
CONFIGURATION I
AN
AR
A
C
AE
AN
A
E
AS
AR
A
N
AS
AR
AC
AS
AE
AS
AN
143
AIR HANDLING | AIR HANDLING UNITS
@IRTWIN
20 to 360
Win
Clim
MAIN FEATURES
Cooling capacity: 10 to 175 kW
Heating capacity: 20 to 356 kW
Number of sizes: 10
Air flow range: 1000 to 30000 m3/h
Insulation: 25 mm thick glass wool or rock wool
DESCRIPTION
With 10 models, from 1000 to 30000 m3/h,
this range is suitable for comfort and industrial
applications.
A skeleton structure compatible with ERP (public
buildings) consisting of aluminium profiles and rigid
and light polycarbonate corners reinforced with glass
fibre.
The 25 mm thick double-skin panels are covered on
6 sides to avoid any penetration of humidity. They are
fitted with fire-rated thermal insulation.
Advantages
Since @irtwin air handling units are manufactured to order
according to the specific needs of each installation, they offer an
infinite choice of solutions.
Classification T4 – TB3 – L2 – F9 – D1 certified by EUROVENT.
Various configurations available: in-line, stacked or side-by-side.
Suitable for indoor or outdoor installation (precaution against risk
of condensation on the panels).
Wide choice of filter classes and types: flat, bag and rigid from
G4 to F9.
Wide choice of coils available as standard from 2 to 8 rows with
fins spacing from 2.1 - 2.5 or 3.2 mm. Fins made of aluminium,
aluminium epoxy or copper. As an option, the coils can be fully
protected by Blygold cladding against harsh environments.
Powerful selection software with user-friendly graphical interface
allows you to make all kinds of simulations. To optimise the
product ranges, the "execution" quality documents (plans in DXF
format) are provided from the prototype phase.
Main options and accessories
2 types of thermal wheels (standard efficiency and high efficiency)
3 types of plate heat exchangers (standard, medium and high
efficiency).
A choice of 3 types of damper: standard, class 3 and class 4 to EN
1751.
2 types of mineral wool available: glass wool and rock wool.
Wide choice of roofing: galvanised, pre-painted, inox 304L or 316L.
Wide choice of belt-drive fans (action or reaction type fan) or direct
drive fans (freewheel type fan), inspection hatch, drain hole and
epoxy paint on fan, variable pulley, twin speed motors, 60 Hz motors,
emergency motors, proximity switch etc.
Flexible connection frame and sleeve M0 class.
Internal lighting 24 V or 230 V with waterproof switch.
Viewing window in access door.
Rain hoods.
Roof.
Pressure taping points.
U-shaped and inclined manometers.
Blank functions with different lengths.
Operating limits/recommendations
1000 Pa maximum on panels in positive and negative pressure.
40°C maximum on motors, beyond this the power of the motor
is downgraded (coefficient of 0.82 on the power for a maximum
temperature of 60°C).
-20°C minimum on the air intake for internal components.
Depending on the indoor air temperature and the outdoor air
temperature, condensation may appear on the panels.
Controls: besides these options, please speak to our Sales Department for
any other configuration or function that is not listed as being available.
144
@IRTWIN - TR TECHNICAL SPECIFICATIONS
SIZE
Air flow (at 2.9 m/s on the cooling coil) m³/h
Height with chassis (STD or side-by-side)
Height with chassis (double deck)
Width (STD or double deck)
Width (side-by-side)
mm
mm
mm
mm
Number of rows
Fin spacing
Total cooling capacity (for 4 rows – 2.5 mm)
Sensible cooling capacity (for 4 rows – 2.5 mm)
Cooling coil connection (4 rows)
Heating capacity (for 2 rows – 2.5 mm)
Heating coil connection (2 rows)
Min electric heating capacity
Max electric heating capacity
mm
kW
kW
DN
kW
DN
kW
kW
20
40
60
90
120
160
200
240
300
360
1650
3300
5500
7500
9100
12850
16600
20200
24400
2950
685
1220
715
1430
1045
1940
715
1430
1045
1940
1020
2040
1045
1940
1325
2650
1225
2300
1325
2650
1555
2960
1325
2650
1555
2960
1630
3260
1555
2960
1935
3870
1845
3540
1935
3870
2145
4140
1935
3870
123.2
109.8
65
246.9
50
12
252
147
131.9
65
269.9
50
18
396
171.8
157
65
355.6
50
21
462
560
710
710
900
630
800
800
1000
COILS
1 to 8 in heating – 2 to 8 in cooling
2.1 - 2.5 - 3.2
54.7
77.3
49.2
69.4
32
50
110.6 155.4
32
32
10.5
12
147
168
10
9
25
19.9
25
3.75
22.5
19
17.5
25
40.3
25
9
54
33.4
29.8
32
66.9
25
9
90
45.1
40.5
32
92
32
9
126
104.3
91.4
50
201.7
32
12
216
160
200
200
250
200
250
315
400
Action - Reaction – Reinforced reaction – Plug fan
250
280
355
400
450
500
315
355
450
500
560
630
315
355
400
500
560
630
400
450
500
630
710
800
FANS
Type available
Min size of centrifugal fan
Max size of centrifugal fan
Min size of Plug fan
Max size of Plug fan
FILTER
Filter frame
Available filter
Class F9 (as per EN 1886)
G2 (metal) and flat G4 – pocket F5, F7 and F8 – Rigid F7 and F9 - H10 to H14 HEPA
HEAT RECOVERY
Run around coil
Efficiency at standard yield of thermal wheel
Efficiency at increased yield of thermal wheel
Length of section at STD yield of thermal plate
Efficiency at medium yield of thermal plate
Efficiency at increased yield of thermal plate
DIMENSIONS AND WEIGHTS (in mm and kg)
%
%
%
%
%
48
60
72
68
83
20
Extraction (type A) Length 784
Single fan, reaction Weight 99
100% fresh air (type D) – Flat G4 filter + F7 bag filter + Length 2084
2R heating coil + 4R cooling coil + reaction fan Weight 261
2-way air mixing box (type G) Length 2384
2-way mixing section + type D Weight 293
Dual flow in-line (type J) Length 3552
Type A + 3-way mixing box in-line + type D Weight 427
Stacked (type I) – type G on fresh air Length 3368
Type A + flat G4 filter on the intake Weight 538
From 2 to 8 rows
45
53
58
59
70
73
59
50
74
75
46
59
72
34
73
45
59
72
56
75
46
59
72
70
77
40
60
90
120
884
136
2184
342
2584
385
3952
563
3768
692
1084
189
2384
454
2868
524
4352
749
3952
944
1184
226
2484
525
2968
598
4552
848
4052
1057
1484
315
2584
610
3168
709
4952
1021
4452
1265
53
59
73
54
76
51
57
71
50
73
49
58
73
55
74
50
61
70
50
71
160
200
240
300
360
1484
371
2868
805
3468
902
5636
1334
4752
1568
1584
442
2968
949
3568
1059
5836
1560
5052
1971
1684
539
3168
1184
3768
1305
6163
1912
5336
2374
1784
723
3168
1321
3768
1464
6236
2247
5536
2782
1984
891
3268
1647
4068
1843
6936
2839
6136
3419
Performance of cooling coils based on: 32°C/40% - 7/12°C & performance of heating coil on: -7°C/90% – 90/70°C.
Performance of the heat recovery device based on: balanced air flow – fresh air -7°C/90% - air intake 22°C/50% - plate heat exchanger
without bypass – thermal wheel with the smallest possible fin spacing.
Configurations
CONFIGURATION A
CONFIGURATION D
CONFIGURATION G
CONFIGURATION J
CONFIGURATION I
AN
AR
A
C
AE
AN
A
E
AS
AR
A
N
AS
AR
AC
AS
AE
AS
AN
145
AIR HANDLING | AIR HANDLING UNITS
@IRTWIN
400 to 1000
Win
Clim
MAIN FEATURES
Chilled water coil power: 200 to 505 kW
Hot water coil power: 500 to 1375 kW
Number of sizes: 5
Air flow range: 30000 to 100000 m3/h
Insulation: 50 mm thick glass wool, rockwool or
polyurethan foam
DESCRIPTION
With 5 additional models, from 30000 to 100000
m3/h, the @irtwin range is suitable for comfort,
hygienic and industrial applications, in line with the
main features offered by the Premi@ir range.
A skeleton structure compatible with ERP (public
buildings) consisting of aluminium profiles and rigid
and soft polycarbonate corners protected with glass
fibre.
The 50 mm thick double-skin panels are covered on
6 sides to avoid any penetration of humidity.
Advantages
As for the Permi@air air handling units, the @irtwin units 400
to 1000 are manufactured to offer a product matching with the
specific needs of each installation by offering an infinite choice of
solutions.
Classification T4 – TB3 – L2 – F9 – D1 certified by EUROVENT.
Various configurations available: in-line, double deck or side-byside.
Suitable for indoor or outdoor installation.
Access door without thermal bridge thanks to polyamide hinges
and external rotor that doesn't transverse the door.
Wide choice of filter: flat, bag and rigid from G4 to H14.
Wide choice of coils from 2 to 8 rows with fin spacing from 2.0
or 3.0 mm. Fins made of aluminium, aluminium epoxy or copper.
As an option, the coils can be fully protected by Blygold cladding
against harsh environments.
Powerful selection software with user-friendly graphical interface
allows you to make all kinds of simulations. To optimise the
product ranges, the "execution" quality documents (plans in DXF
format) are provided from the design phase.
Main options and accessories
2 types of thermal wheels (standard efficiency and high efficiency)
3 types of plate heat exchangers (standard, medium and high
efficiency).
A choice of 3 types of damper: standard, class 3 waterproof and
class 4 waterproof to EN 1751.
2 types of mineral wool available: glass wool and rock wool.
Wide choice of roofing: galvanised, pre-painted, inox 304L or 316L.
Wide choice of belt-drive fans (action or reaction type fan) or direct
drive fans (freewheel type fan), inspection hatch, drain hole and
epoxy paint on fan, variable pulley, twin speed motors, 60 Hz motors,
emergency motors, proximity switch etc.
Flexible connection frame and sleeve M0 class.
Internal lighting 24 V or 230 V with waterproof switch.
Viewing window in access door.
Air intake and delivery rain hoods.
Roof.
Pressure taping points.
U-shaped and inclined manometers.
Blank sections with different lengths.
Operating limits/recommendations
1500 Pa maximum on panels, in positive pressure and negative
pressure.
40°C maximum on motors, beyond this the power of the motor
is downgraded (coefficient of 0.82 on the power for a maximum
temperature of 60°C).
-20°C minimum at the air intake.
Depending on the indoor air temperature and the outdoor air
temperature, condensation may appear on the panels.
Controls: besides these options, please speak to our Sales Department for
any other configuration or function that is not listed as being available.
146
@IRTWIN - TR TECHNICAL SPECIFICATIONS
SIZE
Air flow (at 2.8 m/s on the cooling coil) m³/h
Height with chassis (STD or side-by-side)
Height with chassis (double deck)
Width (STD or double deck)
Width (side-by-side)
mm
mm
mm
mm
Number of rows
Fin spacing
Total cooling capacity (for 4 rows – 3.0 mm)
Sensible cooling capacity (for 4 rows – 3.0 mm)
Cooling coil connection (4 rows)
Heating capacity (for 2 rows – 2.0 mm)
Heating coil connection (2 rows)
Min electric heating capacity
Max electric heating capacity
mm
kW
kW
DN
kW
DN
kW
kW
400
500
700
900
34290
42200
53200
70930
1000
87865
2230
4280
2220
4440
2230
4280
2670
5340
2230
4280
3300
6600
2850
N/A
3300
6600
2850
N/A
4000
8000
199.3
184.4
65
538.0
50
21.0
252.0
257.9
231.8
65
671.0
65
21.0
420.0
2.0 and 3.0
301.6
273.7
80
819.0
65
21.0
588.0
415.9
382.7
80
1092.0
65
24.0
624.0
505.3
470.4
80
1375.0
80
24.0
840.0
630
800
900
1120
Action - Reaction – Reinforced reaction – Plug fans
710
800
900
900
900
1000
900
900
1120
1120
1120
1400
COILS
2 to 8
FANS
Type available
Min size of centrifugal fan
Max size of centrifugal fan
Min size of Plug fans
Max size of Plug fans
1000
1120
1400
FILTER
Filter frame
Available filter
Class F9 (as per EN 1886)
G2 (metal) and flat G4 – bag F5, F7 and F8 – Rigid F7 and F9 - H10 to H14 HEPA
HEAT RECOVERY
Run around coils
Efficiency at standard yield of thermal wheel
Efficiency at increased yield of thermal wheel
Length of section at STD yield of thermal plate
Efficiency at medium yield of thermal plate
Efficiency at increased yield of thermal plate
%
%
%
%
%
50
55
62
54
70
From 2 to 8 rows
46
50
56
56
N/A
46
50
56
59
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
Performance of cooling coils based on: 32°C/40% - 7/12°C & performance of heating coil on: -7°C/90% – 90/70°C.
N/A: Not available
Performance of the heat recovery device based on: balanced air flow – fresh air -7°C/90% - return 22°C/50% - Plate heat exchangers without bypass – thermal
wheel with the smallest possible fin spacing.
Configurations
CONFIGURATION A
CONFIGURATION D
CONFIGURATION G
CONFIGURATION J
CONFIGURATION I
AN
AR
A
C
AE
AN
A
E
AS
AR
A
N
AS
AR
AC
AS
AE
AS
AN
147
AIR HANDLING | WINCLIM
Win
Clim
Eurovent certified software
Drawings and documents
exported in DXF,
RTF (DOC) and PDF
Simple and intuitive user
interface
WinClim II
Selection software for Premi@ir and @irtwin
EUROVENT certified, the Premi@ir and @irtwin air handling units can
be selected from software that is EUROVENT approved, with a userfriendly graphical interface running on Windows XP and Windows 7
operating systems.
The WinClim II selection software allows all kinds of simulations. To
optimise the product ranges, the "execution" quality documents (plans
in DXF format) are provided from the design phase. WinClim II also
ensures any quotations and
customisation requirements are saved.
WinClim II and Premi@ir/
@irtwin ensure you have
all the details about your
selections, where nothing
is left to chance, such as
fan curves with visualisation
of the operating point,
development of the air in the
psychrometric diagram, from
the design stage. What you
receive is a quality execution
document.
WinClim III
Selection software for Premi@ir Double Deck Compact air handling units
Eurovent certified, the Premi@ir DFC air handling units
can be selected from the winCLIM III software, also approved by
Eurovent.
With a user-friendly graphical interface, winCLIM III runs
on Windows operating systems (XP, 7).
Intuitive, user-friendly, quick and effective, winCLIM III allows
users to:
Select and visualise a unit.
Represent a unit as a scale 2D model.
Change and configure the components.
Automatically generate 2D drawings in DXF format compatible
with AutoCAD, selection files comprising the
full technical characteristics and the price as well as a
production order.
Contact our sales team and take a look
at our website to find out more.
148
AIR HANDLING | AIR HANDLING UNITS
RCAH
Heat recovery
device
MAIN FEATURES
Air flows from 500 to 6000 m3/h
Aluminium crossed-flow heat exchanger
Reduced energy consumption with a minimum heat
recovery efficiency of 50%
3 versions available:
- RCAH / Efficiency greater than 50%
- RCAH AE / Efficiency greater than 90%
- RCAH RCF / With integrated R410A cooling circuit
Unit available in horizontal or vertical configuration
Various air intake and air discharge options
Easy access and easy to maintain components
Double skin structure with insulation
G4 filters included
Advantages
Yield optimisation for air-conditioning installations.
The RCAH units are static heat recovery devices that can be
complemented with air-air or air-water conditioning systems while
achieving considerable energy savings.
Options
ENERGY EFFICIENCY
Brushless fans
Adiabatic refrigeration kit
Flexible joint
Antifreeze thermostat
Outdoor installation kit
AIR QUALITY
F6-F7-F8 filters
Air quality control
CONTROLS
On/off controller and 3-speed switch
Remote temperature sensor
Basic electronic controller
Advanced electronic controller
UNIT INSTALLATION
Bypass
Electric coil
Hot water coil (internal or external)
Chilled water cooling coil
3-way valve with actuator
Constant flow rate check
Dirty filter detector
Circular inlet
Besides these options, please speak to our Sales Department for any other
configuration or function that is not listed as being available.
149
AIR HANDLING | AIR HANDLING UNITS
RCAH TECHNICAL SPECIFICATIONS
5
10
20
30
40
m3/h
Pa
%
kW
V
A
dB(A)
mm
kg
500
155
58.7
2.4
230.1
1.4
51.0
750x750x295
41
1000
125
56.4
4.7
230.1
3.0
52.0
900x900x410
68
2000
130
50.0
8.3
230.1
7.8
58.0
1000x1000x470
99
3200
160
53.8
14.3
230.1
11.4
59.0
1300x1300x530
155
4300
180
54.6
19.5
400.3
6.6
62.0
1400x1400x705
235
50
60
m3/h
Pa
%
kW
V
A
dB(A)
mm
kg
5000
99
53.8
22.4
400.3
11.2
63.7
1700x1350x705
235
6000
188
53.1
26.5
400.3
10.8
64.5
1900x1450x755
273
MODEL
Maximum air flow
Available static pressure
Efficiency
Recovered power
Power supply (50 Hz ~)
Maximum absorbed current
Sound level at 1 m
Dimensions (length x width x height)
Weight
MODEL
Maximum air flow
Available static pressure
Efficiency
Recovered power
Power supply (50 Hz ~)
Maximum absorbed current
Sound level at 1 m
Dimensions (length x width x height)
Weight
Performance with an air inlet temperature of -5ºC (80% HR) and an outlet air temperature of 20ºC (50% HR)
Maximum ventilation speed
RCAH AE TECHNICAL SPECIFICATIONS
MODEL
Maximum air flow
Available static pressure
Efficiency
Recovered power
Power supply (50 Hz ~)
Maximum absorbed current
Sound level at 1 m
Dimensions (length x width x height)
Weight
m3/h
Pa
%
kW
V
A
dB(A)
mm
kg
5
10
15
20
500
85
90.0
4.1
230.1
3.0
52.0
1150x860x385
75
1000
130
90.1
8.2
230.1
6.2
55.0
1450x1230x410
120
1500
150
90.1
12.3
230.1
14.2
60.0
1700x1230x490
175
2000
215
90.0
16.3
230.1
11.4
59.0
1700x1230x630
220
Performance with an air inlet temperature of -7ºC (80% HR) and an outlet air temperature of 20ºC (55% HR)
Maximum ventilation speed
RCAH RCF TECHNICAL SPECIFICATIONS
10
15
20
25
Maximum air flow
Blow-out static pressure
Return static pressure
Efficiency (1)
Total refrigeration capacity (1)
EER (1)
Efficiency (2)
Total heating capacity (2)
COP (2)
Power supply (50 Hz ~)
Maximum absorbed current
Sound level at 1 m
Dimensions (length x width x height)
Weight
m3/h
Pa
Pa
%
kW
W/W
%
kW
W/W
V
A
dB(A)
mm
kg
900
225
184
46.7
5.4
2.8
54.0
8.8
6.1
230.1
14.6
55.0
1450x1230x470
212
1400
154
122
44.6
8.2
2.6
51.4
13.7
5.6
230.1
21.6
52.0
1450x1230x470
225
2000
187
130
49.2
12.2
2.6
56.9
21.0
5.7
230.1
36.3
59.0
1700x1560x530
258
2600
179
148
47.8
15.0
2.9
55.2
26.5
5.9
400.3
22.6
58.0
1700x1560x530
258
30
40
Maximum air flow
Blow-out static pressure
Return static pressure
Efficiency (1)
Total refrigeration capacity (1)
EER (1)
Efficiency (2)
Total heating capacity (2)
COP (2)
Power supply (50 Hz ~)
Maximum absorbed current
Sound level at 1 m
Dimensions (length x width x height)
Weight
m3/h
Pa
Pa
%
kW
W/W
%
kW
W/W
V
A
dB(A)
mm
kg
3300
211
153
48.8
20.6
2.9
56.4
35.1
6.0
400.3
26.9
58.0
1900x1700x705
305
4000
159
133
47.8
23.5
2.8
55.2
40.4
5.6
400.3
24.8
62.0
1900x1700x705
315
MODEL
MODEL
(1) Performance with an air inlet temperature of 32ºC (50% HR) and an outlet air temperature of 26ºC (50% HR)
(2) Performance with an air inlet temperature of -5ºC (80% HR) and an outlet air temperature of 20ºC (50% HR)
150
AIR-COOLED
CONDENSERS
AIR-COOLED CONDENSERS
ACCL 11 / 280
Cooling only
ACCH 11 / 280
Reversible
ACCL for Cooling only application
ACCH for Reversible application
Capacity from 12 to 300 kW
Sizes = 19
Refrigerants:
- R134a = ACCL only
- R410A, R407C = ACCL ACCH
MAIN FEATURES
Axial fans with blades generating low noise levels
Valves (supplied loose) on gas and liquid line
for connection to refrigerant piping system, the
condenser is delivered with a nitrogen charge
Thermostatic expansion valve (only on ACCH)
Liquid sight glass (only on ACCH)
Filter dryer (only on ACCH)
Solenoid valve (only on ACCH)
Check valve (only on ACCH)
0:10 V connection block for the condensation
control system (connected to the indoor unit)
Terminal block for alarm (connected to
the indoor unit)
Fan rotational speed control to regulate
condensation (only with axial fans)
Advantages
Simple and reliable
Choice of sound level
Integrated condensation control
Main accessories and options
Code
511 Feet for vertical air discharge (kit)
AVAILABLE VERSIONS
ACCL for Cooling only application
ACCH for Reversible application
Single phase power supply for sizes up to 140
STD standard version
LS low sound level version
XLS extra low sound level version
152
ACCL STD Cooling only
ACCH STD Reversible
TECHNICAL SPECIFICATIONS
11
14
17
20
25
30
35
45
50
60
With R410A refrigerant kW
12.1
14.7
18.4
20.7
24.2
32.7
37.4
47.6
56.1
62.6
With R407C refrigerant kW
12
14.7
18.2
20.4
24.2
32.3
37.1
47.1
55.5
62
11.7
14.4
17.9
20
23.7
31.7
36.6
46.5
54.8
61.2
1
1
1
1
1
1
1
2
2
2
4900
4,500
5200
6400
9600
9,500
9100
12000
17000
16000
0
0
0
0
0
0
0
0
0
0
Nominal absorbed capacity kW
0.25
0.25
0.25
0.39
0.53
0.53
0.53
0.78
1.08
1.08
Maximum operating current A
1.2
1.2
1.2
1.8
2.9
2.9
2.9
3.6
5.7
5.7
63
63
63
65
67
67
67
67.4
69.4
69.4
70
95
110
130
140
185
210
250
280
SIZE
CAPACITY (1)
**With R134a refrigerant kW
AXIAL FANS
N.
Air flow m³/h
Available static pressure Pa
AVERAGE SOUND LEVELS (2)
dB(A)
SIZE
CAPACITY (1)
With R410A refrigerant kW
74
99.4
111
133
151
201
232
276
307
With R407C refrigerant kW
73.3
98.3
110
132
150
198
231
273
304
**With R134a refrigerant kW
72.4
97
109
130
149
195
228
270
301
2
3
3
4
4
6
6
8
8
18000
28200
27200
37800
36000
56000
54000
74600
72000
0
0
0
0
0
0
0
0
0
Nominal absorbed capacity kW
1.08
1.59
1.59
2.12
2.12
3.18
3.18
4.24
4.24
Maximum operating current A
5.7
8.5
8.5
11.4
11.4
17.1
17.1
22.8
22.8
69.4
70.5
70.5
71.1
71.1
71.5
71.5
72.2
72.2
AXIAL FANS
N.
Air flow m³/h
Available static pressure Pa
AVERAGE SOUND LEVELS (2)
ACCL STD Cooling only
dB(A)
ACCH STD Reversible
ELECTRICAL POWER SUPPLY
COMMON FEATURES
11
14
17
20
25
30
35
45
50
60
230/1/50
230/1/50
230/1/50
230/1/50
230/1/50
230/1/50
230/1/50
230/1/50
230/1/50
230/1/50
0.8
1.2
1.7
1.7
2
3
4
4.7
4.1
5.5
Length mm
875
875
1200
1200
1400
1400
1400
1600
1850
1850
Width mm
540
540
540
540
665
665
665
665
665
665
Height mm
727
727
727
727
1027
1027
1027
1027
1027
1027
51
55
66
72
102
111
120
153
175
188
70
95
110
130
140
185
210
250
280
230/1/50
230/1/50
230/1/50
230/1/50
230/1/50
400/3/50
+N(*)
400/3/50
+N(*)
400/3/50
+N(*)
400/3/50
+N(*)
7.7
8.7
11.6
11.6
15.4
20.8
27.7
27.7
37
Length mm
2320
3490
3490
4540
4540
3490
3490
4540
4540
Width mm
665
665
665
665
665
665
665
665
665
Height mm
1140
1150
1150
1150
1150
2200
2200
2200
2200
214
240
270
320
350
470
520
630
690
SIZE
V/ph/
Hz
Refrigerant charge (3) kg
DIMENSIONS
NET WEIGHT
kg
SIZE
ELECTRICAL POWER SUPPLY
V/ph/
Hz
Refrigerant charge (3) kW
DIMENSIONS
NET WEIGHT
kg
(1) For a condensation temperature of 50°C and an outdoor temperature of 35°C.
(2) Sound pressure level Lpm 1 m far according to ISO EN 3744.
(3) The condenser is delivered without refrigerant (nitrogen). For the refrigerant charge, in addition to the values above, add the charge of the piping system and
the indoor units; for oil add 10% of the total quantity of refrigerant.
(*) also available in 230V / 1PH / 50 Hz, please refer to the electrical diagram for the unit.
**Not available in ACCH.
153
AIR-COOLED CONDENSERS
ACCL LS Cooling only
ACCH LS Reversible
SIZE
TECHNICAL SPECIFICATIONS
11
14
17
20
25
30
35
45
50
60
CAPACITY (1)
With R410A refrigerant kW
10.9
13.1
16.4
18.5
21.8
29.1
32.9
42
50.1
55.3
With R407C refrigerant kW
10.8
13.1
16.2
18.2
21.8
28.7
32.6
41.6
49.6
54.8
**With R134a refrigerant kW
10.6
12.9
15.9
17.9
21.3
28.3
32.3
41.1
48.9
54.2
1
1
1
1
1
1
1
2
2
2
4165
3825
4420
5440
8160
8075
7735
10200
14450
13600
0
0
0
0
0
0
0
0
0
0
Nominal absorbed capacity kW
0.21
0.21
0.21
0.33
0.45
0.45
0.45
0.66
0.92
0.92
Maximum operating current A
1.2
1.2
1.2
1.8
2.9
2.9
2.9
3.6
5.7
5.7
59.1
59.1
59.1
61.1
63.1
63.1
63.1
63.6
65.5
65.5
70
95
110
130
140
185
210
250
280
AXIAL FANS
N.
Air flow m³/h
Available static pressure Pa
AVERAGE SOUND LEVELS (2)
dB(A)
SIZE
CAPACITY (1)
With R410A refrigerant kW
65.1
88.3
97.7
118
133
179
205
245
270
With R407C refrigerant kW
64.6
87.4
97.3
117
132
176
203
243
268
**With R134a refrigerant kW
63.8
86.3
96.2
116
131
174
201
240
265
2
3
3
4
4
6
6
8
8
18000
28200
27200
37800
36000
56000
54000
74600
72000
0
0
0
0
0
0
0
0
0
Nominal absorbed capacity kW
0.92
1.35
1.35
1.8
1.8
2.7
2.7
3.6
3.6
Maximum operating current A
5.7
8.5
8.5
11.4
11.4
17.1
17.1
22.8
22.8
65.5
66.6
66.6
67.2
67.2
67.7
67.7
68.3
68.3
AXIAL FANS
N.
Air flow m³/h
Available static pressure Pa
AVERAGE SOUND LEVELS (2)
ACCL LS Cooling only
dB(A)
ACCH LS Reversible
ELECTRICAL POWER SUPPLY
COMMON FEATURES
11
14
17
20
25
30
35
45
50
60
230/1/50
230/1/50
230/1/50
230/1/50
230/1/50
230/1/50
230/1/50
230/1/50
230/1/50
230/1/50
0.8
1.2
1.7
1.7
2
3
4
4.7
4.1
5.5
Length mm
875
875
1200
1200
1400
1400
1400
1600
1850
1850
Width mm
540
540
540
540
665
665
665
665
665
665
Height mm
727
727
727
727
1027
1027
1027
1027
1027
1027
51
55
66
72
102
111
120
153
175
188
70
95
110
130
140
185
210
250
280
230/1/50
230/1/50
230/1/50
230/1/50
230/1/50
400/3/50
+N(*)
400/3/50
+N(*)
400/3/50
+N(*)
400/3/50
+N(*)
7.7
8.7
11.6
11.6
15.4
20.8
27.7
27.7
37
Length mm
2320
3490
3490
4540
4540
3490
3490
4540
4540
Width mm
665
665
665
665
665
665
665
665
665
Height mm
1140
1150
1150
1150
1150
2200
2200
2200
2200
214
240
270
320
350
470
520
630
690
SIZE
V/ph/
Hz
Refrigerant charge (3) kg
DIMENSIONS
NET WEIGHT
kg
SIZE
ELECTRICAL POWER SUPPLY
V/ph/
Hz
Refrigerant charge (3) kW
DIMENSIONS
NET WEIGHT
kg
(1) For a condensation temperature of 50°C and an outdoor temperature of 35°C.
(2) Sound pressure level Lpm 1 m far according to ISO EN 3744.
(3) The condenser is delivered without refrigerant (nitrogen). For the refrigerant charge, in addition to the values above, add the charge of the piping system and
the indoor units; for oil add 10% of the total quantity of refrigerant.
(*) also available in 230V / 1PH / 50 Hz, please refer to the electrical diagram for the unit.
**Not available in ACCH.
154
ACCL XLS Cooling only
ACCH XLS Reversible
SIZE
TECHNICAL SPECIFICATIONS
11
14
17
20
25
30
35
45
50
60
CAPACITY (1)
With R410A refrigerant kW
9.6
11.4
14.1
16.1
19.2
25.2
28.2
36.1
43.5
47.6
With R407C refrigerant kW
9.5
11.4
14
15.8
19.2
24.9
27.9
35.7
43.1
47.2
**With R134a refrigerant kW
9.3
11.2
13.8
15.6
18.8
24.5
27.6
35.3
42.6
46.7
1
1
1
1
1
1
1
2
2
2
3430
3150
3640
4480
6720
6650
6370
8400
11900
11200
0
0
0
0
0
0
0
0
0
0
Nominal absorbed capacity kW
0.18
0.18
0.18
0.27
0.37
0.37
0.37
0.55
0.76
0.76
Maximum operating current A
1.2
1.2
1.2
1.8
2.9
2.9
2.9
3.6
5.7
5.7
54.5
54.5
54.5
56.5
58.5
58.5
58.5
58.9
60.8
60.8
70
95
110
130
140
185
210
250
280
AXIAL FANS
N.
Air flow m³/h
Available static pressure Pa
AVERAGE SOUND LEVELS (2)
dB(A)
SIZE
CAPACITY (1)
With R410A refrigerant kW
55.8
76.4
83.7
102
114
155
175
212
231
With R407C refrigerant kW
55.3
75.7
83.3
101
113
153
173
210
229
**With R134a refrigerant kW
54.7
74.8
82.5
100
112
151
172
208
227
2
3
3
4
4
6
6
8
8
12600
19740
19040
26460
25200
39200
37800
52220
50400
0
0
0
0
0
0
0
0
0
Nominal absorbed capacity kW
0.76
1.11
1.11
1.48
1.48
1.48
2.23
2.23
2.97
Maximum operating current A
5.7
8.5
8.5
11.4
11.4
17.1
17.1
22.8
22.8
60.8
61.9
61.9
62.5
62.5
63
63
63.7
63.7
AXIAL FANS
N.
Air flow m³/h
Available static pressure Pa
AVERAGE SOUND LEVELS (2)
ACCL XLS Cooling only
dB(A)
ACCH XLS Reversible
ELECTRICAL POWER SUPPLY
COMMON FEATURES
11
14
17
20
25
30
35
45
50
60
230/1/50
230/1/50
230/1/50
230/1/50
230/1/50
230/1/50
230/1/50
230/1/50
230/1/50
230/1/50
0.8
1.2
1.7
1.7
2
3
4
4.7
4.1
5.5
Length mm
875
875
1200
1200
1400
1400
1400
1600
1850
1850
Width mm
540
540
540
540
665
665
665
665
665
665
Height mm
727
727
727
727
1027
1027
1027
1027
1027
1027
51
55
66
72
102
111
120
153
175
188
70
95
110
130
140
185
210
250
280
230/1/50
230/1/50
230/1/50
230/1/50
230/1/50
400/3/50
+N(*)
400/3/50
+N(*)
400/3/50
+N(*)
400/3/50
+N(*)
7.7
8.7
11.6
11.6
15.4
20.8
27.7
27.7
37
Length mm
2320
3490
3490
4540
4540
3490
3490
4540
4540
Width mm
665
665
665
665
665
665
665
665
665
Height mm
1140
1150
1150
1150
1150
2200
2200
2200
2200
214
240
270
320
350
470
520
630
690
SIZE
V/ph/
Hz
Refrigerant charge (3) kg
DIMENSIONS
NET WEIGHT
kg
SIZE
ELECTRICAL POWER SUPPLY
V/ph/
Hz
Refrigerant charge (3) kW
DIMENSIONS
NET WEIGHT
kg
(1) For a condensation temperature of 50°C and an outdoor temperature of 35°C.
(2) Sound pressure level Lpm 1 m far according to ISO EN 3744.
(3) The condenser is delivered without refrigerant (nitrogen). For the refrigerant charge, in addition to the values above, add the charge of the piping system and
the indoor units; for oil add 10% of the total quantity of refrigerant.
(*) also available in 230V / 1PH / 50 Hz, please refer to the electrical diagram for the unit.
**Not available in ACCH.
155
AIR-COOLED CONDENSERS | DUCTABLE
ACCL PF 11 / 144
Cooling only
ACCH PF 11 / 144
Reversible
ACCL for Cooling only application
ACCH for Reversible application
Capacity from 12 to 150 kW
Sizes = 14
Refrigerants
R134a = ACCL only
R410A, R407C = ACCL ACCH
Available static pressure from 50 to 500 Pa
depending on size
MAIN FEATURES
Plug fans with EC motor
Valves (supplied loose) on gas and liquid line
for connection to refrigerant piping system, the
condenser is delivered with a nitrogen charge
Thermostatic expansion valve (only on ACCH)
Liquid sight glass (only on ACCH)
Filter dryer (only on ACCH)
Solenoid valve (only on ACCH)
Check valve (only on ACCH)
0:10 V connection block for the condensation
control system (connected to the indoor unit)
Terminal block for alarm (connected to the
indoor unit)
Advantages
Available static pressure
Simple and reliable
Choice of sound level
Integrated condensation control
EC motor
Low power consumption
AVAILABLE VERSIONS
ACCL for Cooling only application
ACCH for Reversible application
STD standard version
LS low sound level version
XLS extra low sound level version
156
ACCL PF STD Cooling only
ACCH PF STD Reversible
TECHNICAL SPECIFICATIONS
11
14
17
20
25
33
38
With R410A refrigerant kW
12.1
15.6
18.2
21.6
25
35.1
39.8
With R407C refrigerant kW
12
15.6
18.2
21.6
25
35.1
39.8
11.7
15.3
17.9
21.3
24.7
34.7
39.3
1
1
1
1
1
1
1
4900
4900
4900
4900
6400
8000
10000
50
50
50
50
50
50
50
Maximum available static pressure Pa
375
350
332
290
748
474
298
Nominal absorbed capacity kW
0.38
0.42
0.45
0.52
0.64
1.3
1.14
Maximum operating current A
1.6
1.6
1.6
1.6
4.3
4.3
3.6
61.6
61.6
61.5
61.5
67.1
72
71.1
44
58
69
86
108
114
144
With R410A refrigerant kW
46.5
62
73.1
91
113
122
154
With R407C refrigerant kW
46.5
62
73.1
91
113
122
154
46
61.2
72.4
89.9
111
121
152
1
2
2
3
3
3
4
10000
16000
16000
24000
32000
28000
36000
50
50
50
50
50
50
50
Maximum available static pressure Pa
268
552
512
542
515
204
237
Nominal absorbed capacity kW
1.24
2.18
2.39
3.34
4.74
5.63
7.4
Maximum operating current A
3.6
8.6
8.6
12.9
17.2
12.9
17.2
71.3
77.3
77.4
80.3
81.8
83.7
84.5
SIZE
CAPACITY (1)
**With R134a refrigerant kW
PLUG FANS
N.
Air flow m³/h
Available static pressure Pa
AVERAGE SOUND LEVELS (2)
dB(A)
SIZE
CAPACITY (1)
**With R134a refrigerant kW
PLUG FANS
N.
Air flow m³/h
Available static pressure Pa
AVERAGE SOUND LEVELS (2)
dB(A)
ACCL PF STD Cooling only
ACCH PF STD Reversible
ELECTRICAL POWER SUPPLY
COMMON FEATURES
11
14
17
20
25
33
38
380-480/3/
50-60
380-480/3/
50-60
380-480/3/
50-60
380-480/3/
50-60
380-480/3/
50-60
380-480/3/
50-60
380-480/3/
50-60
0.8
1.2
1.7
2.6
2.5
3.8
4.3
Length mm
890
890
890
890
1190
1190
1390
Width mm
880
880
880
880
880
880
880
Height mm
900
900
900
900
900
900
1300
143
148
153
163
210
222
284
44
58
69
86
108
114
144
380-480/3/
50-60
380-480/3/
50-60
380-480/3/
50-60
380-480/3
/50-60
380-480/3/
50-60
380-480/3/
50-60
380-480/3/
50-60
6.4
5.9
8.8
10.2
9.4
10.3
14
Length mm
1390
1840
1840
2290
1840
2290
1840
Width mm
880
880
880
880
880
880
880
Height mm
1300
1300
1300
1300
1300
1300
1800
310
387
421
515
625
557
673
SIZE
V/ph/
Hz
Refrigerant charge (3) kg
DIMENSIONS
NET WEIGHT
kg
SIZE
ELECTRICAL POWER SUPPLY
V/ph/
Hz
Refrigerant charge (3) kW
DIMENSIONS
NET WEIGHT
kg
1. For a condensation temperature of 50°C and an outdoor temperature of 35°C.
2. Sound pressure level Lpm 1 m far according to ISO EN 3744.
3. The condenser is delivered without refrigerant (nitrogen). For the refrigerant charge, in addition to the values above, add the charge of the piping system and
the indoor units; for oil add 10% of the total quantity of refrigerant.
**Not available in ACCH
157
AIR-COOLED CONDENSERS | DUCTABLE
ACCL PF LS Cooling only
ACCH PF LS Reversible
SIZE
TECHNICAL SPECIFICATIONS
11
14
17
20
25
33
38
CAPACITY (1)
With R410A refrigerant kW
10.8
13.7
15.9
18.8
21.6
30.2
34.5
With R407C refrigerant kW
10.5
13.7
15.9
18.8
21.6
30.2
34.5
**With R134a refrigerant kW
10.2
13.3
15.5
18.4
21
29.4
33.7
1
1
1
1
1
1
1
4165
4165
4165
4165
5440
6800
8,500
50
50
50
50
50
50
50
Maximum available static pressure Pa
375
350
332
290
748
474
298
Nominal absorbed capacity kW
0.26
0.28
0.3
0.34
0.42
0.83
0.74
Maximum operating current A
1.6
1.6
1.6
1.6
4.3
4.3
3.6
57.7
57.7
57.6
57.6
63.2
68.1
67.2
44
58
69
86
108
114
144
PLUG FANS
N.
Air flow m³/h
Available static pressure Pa
AVERAGE SOUND LEVELS (2)
dB(A)
SIZE
CAPACITY (1)
With R410A refrigerant kW
40.1
53.4
62.7
78.6
98.9
105
131
With R407C refrigerant kW
40.1
53.4
62.7
78.6
98.9
105
131
**With R134a refrigerant kW
39.3
51.8
61.3
76.2
96.2
102
127
1
2
2
3
3
3
4
8,500
13600
13600
20400
27200
23800
30600
50
50
50
50
50
50
50
Maximum available static pressure Pa
268
552
512
542
515
204
237
Nominal absorbed capacity kW
0.8
1.4
1.51
2.15
3.04
3.57
4.69
Maximum operating current A
3.6
8.6
8.6
12.9
17.2
12.9
17.2
67.4
73.4
73.5
76.4
77.9
79.8
80.6
PLUG FANS
N.
Air flow m³/h
Available static pressure Pa
AVERAGE SOUND LEVELS (2)
dB(A)
ACCL PF LS Cooling only
ACCH PF LS Reversible
ELECTRICAL POWER SUPPLY
COMMON FEATURES
11
14
17
20
25
33
38
380-480/3/
50-60
380-480/3/
50-60
380-480/3/
50-60
380-480/3/
50-60
380-480/3/
50-60
380-480/3/
50-60
380-480/3/
50-60
0.8
1.2
1.7
2.6
2.5
3.8
4.3
Length mm
890
890
890
890
1190
1190
1390
Width mm
880
880
880
880
880
880
880
Height mm
900
900
900
900
900
900
1300
143
148
153
163
210
222
284
44
58
69
86
108
114
144
380-480/3/
50-60
380-480/3/
50-60
380-480/3/
50-60
380-480/3
/50-60
380-480/3/
50-60
380-480/3
/50-60
380-480/3/
50-60
6.4
5.9
8.8
10.2
9.4
10.3
14
Length mm
1390
1840
1840
2290
1840
2290
1840
Width mm
880
880
880
880
880
880
880
Height mm
1300
1300
1300
1300
1300
1300
1800
310
387
421
515
625
557
673
SIZE
V/ph/
Hz
Refrigerant charge (3) kg
DIMENSIONS
NET WEIGHT
kg
SIZE
ELECTRICAL POWER SUPPLY
V/ph/
Hz
Refrigerant charge (3) kW
DIMENSIONS
NET WEIGHT
kg
(1) For a condensation temperature of 50°C and an outdoor temperature of 35°C.
(2) Sound pressure level Lpm 1 m far according to ISO EN 3744.
(3) The condenser is delivered without refrigerant (nitrogen). For the refrigerant charge, in addition to the values above, add the charge of the piping system and
the indoor units; for oil add 10% of the total quantity of refrigerant.
**Not available in ACCH
158
ACCL PF XLS Cooling only
ACCH PF XLS Reversible
SIZE
TECHNICAL SPECIFICATIONS
11
14
17
20
25
33
38
CAPACITY (1)
With R410A refrigerant kW
9.5
11.9
13.7
16
18.7
25.8
29.7
With R407C refrigerant kW
9.3
11.9
13.7
16
18.7
25.8
29.7
**With R134a refrigerant kW
9.1
11.6
13.4
15.7
18.2
25.2
29.1
1
1
1
1
1
1
1
3430
3430
3430
3430
4480
5600
7000
50
50
50
50
50
50
50
Maximum available static pressure Pa
375
350
332
290
748
474
298
Nominal absorbed capacity kW
0.16
0.17
0.19
0.21
0.26
0.5
0.49
Maximum operating current A
1.6
1.6
1.6
1.6
4.3
4.3
3.6
53.1
53.1
53
53
58.6
63.5
62.6
44
58
69
86
108
114
144
With R410A refrigerant kW
34
46.2
53.4
68.1
85.9
89.8
113
With R407C refrigerant kW
34
46.2
53.4
68.1
85.9
89.8
113
33.5
45
52.4
66.4
83.8
87.9
110
1
2
2
3
3
3
4
7000
11200
11200
16800
22400
19600
25200
50
50
50
50
50
50
50
Maximum available static pressure Pa
268
552
512
542
515
204
237
Nominal absorbed capacity kW
0.48
0.84
0.92
1.29
1.82
2.1
2.76
Maximum operating current A
3.6
8.6
8.6
12.9
17.2
12.9
17.2
62.8
68.8
68.9
71.8
73.3
75.2
76
PLUG FANS
N.
Air flow m³/h
Available static pressure Pa
AVERAGE SOUND LEVELS (2)
dB(A)
SIZE
CAPACITY (1)
**With R134a refrigerant kW
PLUG FANS
N.
Air flow m³/h
Available static pressure Pa
AVERAGE SOUND LEVELS (2)
dB(A)
ACCL PF XLS Cooling only
ACCH PF XLS Reversible
ELECTRICAL POWER SUPPLY
COMMON FEATURES
11
14
17
20
25
33
38
380-480/3/
50-60
380-480/3/
50-60
380-480/3/
50-60
380-480/3/
50-60
380-480/3/
50-60
380-480/3/
50-60
380-480/3/
50-60
0.8
1.2
1.7
2.6
2.5
3.8
4.3
Length mm
890
890
890
890
1190
1190
1390
Width mm
880
880
880
880
880
880
880
Height mm
900
900
900
900
900
900
1300
143
148
153
163
210
222
284
44
58
69
86
108
114
144
380-480/3/
50-60
380-480/3/
50-60
380-480/3/
50-60
380-480/3
/50-60
380-480/3/
50-60
380-480/3
/50-60
380-480/3/
50-60
6.4
5.9
8.8
10.2
9.4
10.3
14
Length mm
1390
1840
1840
2290
1840
2290
1840
Width mm
880
880
880
880
880
880
880
Height mm
1300
1300
1300
1300
1300
1300
1800
310
387
421
515
625
557
673
SIZE
V/ph/
Hz
Refrigerant charge (3) kg
DIMENSIONS
NET WEIGHT
kg
SIZE
ELECTRICAL POWER SUPPLY
V/ph/
Hz
Refrigerant charge (3) kW
DIMENSIONS
NET WEIGHT
kg
(1) For a condensation temperature of 50°C and an outdoor temperature of 35°C.
(2) Sound pressure level Lpm 1 m far according to ISO EN 3744.
(3) The condenser is delivered without refrigerant (nitrogen). For the refrigerant charge, in addition to the values above, add the charge of the piping system and
the indoor units; for oil add 10% of the total quantity of refrigerant.
**Not available in ACCH
159
DRY COOLERS
DRY COOLERS
DC 14 / 280
Axial fans
Capacity from 8 to 172 kW
Sizes = 10
MAIN FEATURES
Axial fans with blades generating low noise levels
0:10 V connection block for the condensation
control system (connected to the indoor unit)
Terminal block for alarm (connected to the
indoor unit)
Fan rotational speed control to regulate
condensation (only with axial fans)
Copper tube heat exchanger with high efficiency
aluminium fins developed for greater thermal transfer
and low pressure drops
Advantages
Simple and reliable
Choice of sound level
Integrated condensation control
AVAILABLE VERSIONS
Single phase for sizes up to 140
STD standard version
LS low sound level version 85%
LS low sound level version 70 %
Main accessories and options
Code
511 Feet for vertical air discharge (kit)
DC TECHNICAL SPECIFICATIONS
14
20
35
45
60
70
110
140
210
280
8.3
11.7
22.6
26.4
31.8
40.2
62.2
86.1
124
172
1.5
2.1
4
4.7
5.7
7.2
11.1
15.4
22.1
30.8
Pressure drop kPa
24
21
26
16
8
12
17
40
17
40
Water volume l
4
5.7
15.7
15.2
17.9
25.1
37.7
72.8
75.3
100.4
1
1
1
2
2
2
3
4
6
8
4,500
6400
9100
12000
16000
18000
27200
36000
54000
72000
0
0
0
0
0
0
0
0
0
0
Nominal absorbed capacity kW
0.25
0.39
0.53
0.78
1.08
1.08
1.59
2.12
3.18
4.24
Maximum operating current A
0.7
1.8
2.9
3.6
5.7
5.7
8.5
11.4
17.1
22.8
63
65
67
67.4
69.4
69.4
70.5
71.1
71.5
72.2
14
20
35
45
60
70
110
140
210
280
SIZE
CAPACITY (1)
kW
Heat exchanger
Water flow m³/h
AXIAL FANS
N.
Air flow m³/h
Available static pressure Pa
AVERAGE SOUND LEVELS (2)
dB(A)
DC COMMON FEATURES
SIZE
V/ph/
Electrical power supply
Hz
400/3/50 400/3/50
230/1/50 230/1/50 230/1/50 230/1/50 230/1/50 230/1/50 230/1/50 230/1/50
+N(*)
+N(*)
Dimensions Length mm
875
1200
1400
1600
1850
2320
3490
4540
3490
4540
Dimensions Width mm
540
540
665
665
665
665
665
665
665
665
Dimensions Height mm
727
727
1027
1027
1027
1140
1150
1150
2200
2200
56
73
122
156
191
219
227
359
533
708
Net weight kg
161
DRY COOLERS
DC LN 85% TECHNICAL SPECIFICATIONS
SIZE
CAPACITY (1)
kW
14
20
35
45
60
70
110
140
210
280
7.3
10.4
19.8
23.3
28
35.3
54.8
75.9
109
152
Heat exchanger
1.3
1.9
3.5
4.2
5
6.3
9.8
13.6
19.5
27.1
Pressure drop kPa
Water flow m³/h
19
17
21
13
6
10
14
32
14
32
Water volume l
4
5.7
15.7
15.2
17.9
25.1
37.7
72.8
75.3
100.4
1
1
1
2
2
2
3
4
6
8
3825
5440
7735
10200
13600
15300
23120
30600
45900
61200
AXIAL FANS
N.
Air flow m³/h
0
0
0
0
0
0
0
0
0
0
Nominal absorbed capacity kW
Available static pressure Pa
0.21
0.33
0.45
0.66
0.92
0.92
1.35
1.8
2.7
3.6
Maximum operating current A
0.7
1.8
2.9
3.6
5.7
5.7
8.5
11.4
17.1
22.8
59.1
61.1
63.1
63.6
65.5
65.5
66.6
67.2
67.7
68.3
20
35
45
60
70
110
140
210
280
AVERAGE SOUND LEVELS (2)
dB(A)
DC LN 85% COMMON FEATURES
14
SIZE
V/ph/
Electrical power supply
Hz
400/3/50 400/3/50
230/1/50 230/1/50 230/1/50 230/1/50 230/1/50 230/1/50 230/1/50 230/1/50
+N(*)
+N(*)
Dimensions Length mm
875
1200
1400
1600
1850
2320
3490
4540
3490
4540
Dimensions Width mm
540
540
665
665
665
665
665
665
665
665
Dimensions Height mm
727
727
1027
1027
1027
1140
1150
1150
2200
2200
56
73
122
156
191
219
227
359
533
708
Net weight kg
DC LN 70% TECHNICAL SPECIFICATIONS
SIZE
CAPACITY (1)
kW
14
20
35
45
60
70
110
140
210
280
6.4
9
16.9
19.9
23.8
30.2
46.9
65
93.2
130
Heat exchanger
1.1
1.6
3
3.6
4.3
5.4
8.4
11.6
16.7
23.3
Pressure drop kPa
Water flow m³/h
15
13
16
10
5
7
11
25
10
25
Water volume l
4
5.7
15.7
15.2
17.9
25.1
37.7
72.8
75.3
100.4
1
1
1
2
2
2
3
4
6
8
3150
4480
6370
8400
11200
12600
19040
25200
37800
50400
0
0
0
0
0
0
0
0
0
0
Nominal absorbed capacity kW
0.18
0.27
0.37
0.55
0.76
0.76
1.11
1.48
2.23
2.97
Maximum operating current A
0.7
1.8
2.9
3.6
5.7
5.7
8.5
11.4
17.1
22.8
59.1
61.1
63.1
63.6
65.5
65.5
66.6
67.2
67.7
68.3
20
35
45
60
70
110
140
210
280
AXIAL FANS
N.
Air flow m³/h
Available static pressure Pa
AVERAGE SOUND LEVELS (2)
dB(A)
DC LN 70% COMMON FEATURES
14
SIZE
V/ph/
Electrical power supply
Hz
400/3/50 400/3/50
230/1/50 230/1/50 230/1/50 230/1/50 230/1/50 230/1/50 230/1/50 230/1/50
+N(*)
+N(*)
Dimensions Length mm
875
1200
1400
1600
1850
2320
3490
4540
3490
4540
Dimensions Width mm
540
540
665
665
665
665
665
665
665
665
Dimensions Height mm
727
727
1027
1027
1027
1140
1150
1150
2200
2200
56
73
122
156
191
219
227
359
533
708
Net weight kg
(1) Gross values - air inlet 35°C with water inlet temperature 45°C - 20% glycol
(2) Sound pressure level Lpm 1 m far according to ISO EN 3744.
(*) also available in 230V / 1PH / 50 Hz, please refer to the electrical diagram for the unit.
162
DRY COOLERS
DC PF
14 / 144
Plug fans
Capacity from 8 to 89 kW
Sizes = 13
Available static pressure from 50 to 500 Pa
depending on size
MAIN FEATURES
Plug fans and EC motor
0:10 V connection block for the condensation
control system (connected to the indoor unit)
Terminal block for alarm (connected to the
indoor unit)
Copper tube heat exchanger with high efficiency
aluminium fins developed for greater thermal transfer
and low pressure drops
Advantages
Available static pressure
Simple and reliable
Choice of sound level
Integrated condensation control
EC motor
Low power consumption
AVAILABLE VERSIONS
STD standard version
LS low sound level version 85%
LS low sound level version 70 %
DC PF TECHNICAL SPECIFICATIONS
SIZE
CAPACITY (1)
kW
14
17
21
24
33
38
44
58
69
86
108
114
144
8.8
10.5
12.6
13.7
20.6
24.3
28
31.8
41.9
50
60.3
68.8
89
Heat exchanger
1.6
1.9
2.3
2.4
3.7
4.3
5
5.7
7.5
9
10.8
12.3
15.9
Pressure drop kPa
Water flow m³/h
26
24
15
15
26
30
29
8
18
18
10
15
31
Water volume l
3.9
5.2
7.8
7.4
11.1
12.7
19.1
17.5
26.2
24.5
28
36.7
41.9
PLUG FANS
N.
Air flow m³/h
Available static pressure Pa
Max. available static pressure Pa
1
1
1
1
1
1
1
2
2
3
4
3
4
4900
4900
4900
6400
80000
10000
10000
16000
16000
24000
32000
28000
36000
50
50
50
50
50
50
50
50
50
50
50
50
50
350
332
290
748
474
298
268
552
512
542
515
204
237
Nominal absorbed capacity kW
0.42
0.45
0.52
0.64
1.3
1.14
1.24
2.18
2.39
3.34
4.74
5.63
7.4
Maximum operating current A
1.6
1.6
1.6
4.3
4.3
3.6
3.6
8.6
8.6
12.9
17.2
12.9
17.2
dB(A) 61.6
61.5
61.5
67.1
72
71.1
71.3
77.3
77.4
80.3
81.8
83.7
84.5
AVERAGE SOUND LEVELS (2)
DC PF COMMON FEATURES
14
17
21
24
33
38
44
58
69
86
108
114
144
380480/3/5060
380480/3/5060
380480/3/5060
380480/3/5060
380480/3/5060
380480/3/5060
380480/3/5060
380480/3/5060
380480/3/5060
380480/3/5060
380480/3/5060
380480/3/5060
380480/3/5060
Dimensions Length mm
890
890
890
1190
1190
1390
1390
1840
1840
2290
1840
2290
1840
Dimensions Width mm
880
880
880
880
880
880
880
880
880
880
880
880
880
Dimensions Height mm
900
900
900
900
900
1300
1300
1300
1300
1300
1800
1300
1800
149
154
165
209
224
287
314
391
427
520
631
565
682
SIZE
V/ph/
Electrical power supply
Hz
Net weight kg
163
DRY COOLERS
DC PF LS 85% TECHNICAL SPECIFICATIONS
SIZE
CAPACITY (1)
kW
14
17
21
24
33
38
44
58
69
86
108
114
144
7.8
9.2
11
12.1
18
21.4
24.5
28
36.7
44.3
53.3
60.4
78.3
Heat exchanger
Water flow m³/h
Pressure drop kPa
Water volume l
PLUG FANS
N.
Air flow m³/h
Available static pressure Pa
1.4
1.7
2
2.2
3.2
3.8
4.4
5
6.6
7.9
9.5
10.8
14
21
19
11
12
21
24
23
6
14
14
8
12
24
3.9
5.2
7.8
7.4
11.1
12.7
19.1
17.5
26.2
24.5
28
36.7
41.9
1
1
1
1
1
1
1
2
2
3
4
3
4
4165
4165
4165
5440
6800
8,500
8,500
13600
13600
20400
27200
23800
30600
50
50
50
50
50
50
50
50
50
50
50
50
50
Max. available static pressure Pa
350
332
290
748
474
298
268
552
512
542
515
204
237
Nominal absorbed capacity kW
0.28
0.3
0.34
0.42
0.83
0.74
0.8
1.4
1.51
2.15
3.04
3.57
4.69
Maximum operating current A
1.6
1.6
1.6
4.3
4.3
3.6
3.6
8.6
8.6
12.9
17.2
12.9
17.2
dB(A) 57.7
57.6
57.6
63.2
68.1
67.2
67.4
73.4
73.5
76.4
77.9
79.8
80.6
AVERAGE SOUND LEVELS (2)
DC PF LS 85% COMMON FEATURES
14
17
21
24
33
38
44
58
69
86
108
114
144
380480/3/5060
380480/3/5060
380480/3/5060
380480/3/5060
380480/3/5060
380480/3/5060
380480/3/5060
380480/3/5060
380480/3/5060
380480/3/5060
380480/3/5060
380480/3/5060
380480/3/5060
Dimensions Length mm
890
890
890
1190
1190
1390
1390
1840
1840
2290
1840
2290
1840
Dimensions Width mm
880
880
880
880
880
880
880
880
880
880
880
880
880
Dimensions Height mm
900
900
900
900
900
1300
1300
1300
1300
1300
1800
1300
1800
149
154
165
209
224
287
314
391
427
520
631
565
682
SIZE
V/ph/
Electrical power supply
Hz
Net weight kg
DC PF LS 70% TECHNICAL SPECIFICATIONS
SIZE
CAPACITY (1)
kW
14
17
21
24
33
38
44
58
69
86
108
114
144
6.8
8
9.3
10.3
15.4
18.3
20.6
23.8
31.1
38.1
45.8
51.4
67
Heat exchanger
Water flow m³/h
Pressure drop kPa
Water volume l
PLUG FANS
N.
Air flow m³/h
Available static pressure Pa
1.2
1.4
1.7
1.9
2.8
3.3
3.7
4.3
5.6
6.8
8.2
9.2
12
17
15
9
9
16
18
17
5
11
11
6
9
19
3.9
5.2
7.8
7.4
11.1
12.7
19.1
17.5
26.2
24.5
28
36.7
41.9
1
1
1
1
1
1
1
2
2
3
4
3
4
3430
3430
3430
4480
5600
7000
7000
11200
11200
16800
22400
19600
25200
50
50
50
50
50
50
50
50
50
50
50
50
50
Max. available static pressure Pa
350
332
290
748
474
298
268
552
512
542
515
204
237
Nominal absorbed capacity kW
0.17
0.19
0.21
0.26
0.5
0.49
0.48
0.84
0.92
1.29
1.82
2.1
2.76
Maximum operating current A
1.6
AVERAGE SOUND LEVELS (2)
dB(A) 53.1
1.6
1.6
4.3
4.3
3.6
3.6
8.6
8.6
12.9
17.2
12.9
17.2
53
53
58.6
63.5
62.6
62.8
68.8
68.9
71.8
73.3
75.2
76
DC PF LS 70% COMMON FEATURES
14
17
21
24
33
38
44
58
69
86
108
114
144
380480/3/5060
380480/3/5060
380480/3/5060
380480/3/5060
380480/3/5060
380480/3/5060
380480/3/5060
380480/3/5060
380480/3/5060
380480/3/5060
380480/3/5060
380480/3/5060
380480/3/5060
Dimensions Length mm
890
890
890
1190
1190
1390
1390
1840
1840
2290
1840
2290
1840
Dimensions Width mm
880
880
880
880
880
880
880
880
880
880
880
880
880
Dimensions Height mm
900
900
900
900
900
1300
1300
1300
1300
1300
1800
1300
1800
149
154
165
209
224
287
314
391
427
520
631
565
682
SIZE
V/ph/
Electrical power supply
Hz
Net weight kg
(1) Gross values - air inlet 35°C with water inlet temperature 45°C - 20% glycol
(2) Sound pressure level Lpm 1 m far according to ISO EN 3744.
164
UNIT HEATERS
165
UNIT HEATERS
WESTHERM
Unit heater
FEATURES
Chilled water coil capacity: 3 to 33 kW
Hot water coil capacity: 4 to 143 kW
Steam coil capacity: 15 to 302 kW
Number of sizes: 6
Air flow range: 284 to 13780 m3/h
DESCRIPTION
The WESTHERM propeller fan type unit heaters are
intended for air heating, cooling or blowing applications
in the office building, commercial and industrial sectors.
The WESTHERM range consists of 6 sizes.
It is available in 3 versions:
- Hot water/steam.
- Chilled water (PHM series only).
- Air blower.
And in 2 series depending on the type of motor used
and the size:
- PHM series equipped with 5-speed mono-phase
motor,
- PHT series equipped with tri-phase, 1 or 2-speed
motor (as an option).
Thanks to a wide choice of air diffusers, special
arrangements, options and accessories, the
WESTHERM range makes it possible to respond to any
application encountered.
Advantages
PHT series unit heaters:
Ventilation is ensured by an aluminium wide blade
propeller fan whose special profile ensures excellent air
flow/pressure characteristics and a low sound level.
The fan is balanced statically and dynamically.
A Venturi obtained by stamping the panel on the air intake
side helps to reduce pressure drops and the sound level.
PHM series unit heaters:
The units in this series are equipped with monophase propeller fans (asynchronous motor, internal
rotor, ball bearing design, aluminium motor housing). An
autotransformer is supplied as standard, making it possible
to ensure 5 speeds of ventilation.
The propellers (5 or 7 blades depending on sizes) are
made of 30% glass fibre reinforced composite material.
The PHM series unit heaters have a fan guard supplied as
standard, made of black polyester coated steel wire.
High acoustic performance, low energy consumption,
compact design and stability of the air flow despite the coil
clogging make up the main features of these new fans.
Operating limits/recommendations
Indicative values. The operating T° are influenced by a series
of settings such as: operating conditions, thermal load,
adjustments, etc... Data to be confirmed upon selection.
Main options
Air blowers:
Two-speed motor for PHT unit heaters only.
Maintenance and repair switch for PHM and PHT unit heaters
(single-speed and two-speed).
Aluminium propellers for PHM unit heaters.
Epoxy paint on casing.
Chilled water version:
Maintenance and repair switch.
Aluminium propellers for PHM series unit heaters.
Hot water/steam version:
Cupro-nickel coils for high temperature water or steam applications.
Room thermostat.
Two-speed motors (except size 35) for PHT unit heaters only.
Air filter inside or outside the cubic air intake casing.
Special installation kit (VAL, VAF, VAK, VAJF, VAGK, VAGJF, VAGZ,
VABGZ, VABF, HABGZ).
Maintenance and repair switch for PHM and PHT unit heaters
(single-speed and two-speed).
Aluminium propellers for PHM unit heaters.
Epoxy paint on casing.
Main accessories
Wall-mounted support kit.
Maintenance and repair switch.
Anti-radiation screen (for PHM unit heaters with composite
propellers).
Air blowers:
- Air diffusers: HN, HP (except for size 70) and HO (except for sizes
35 & 70).
- Fan guard for PHT unit heaters only (standard on PHM unit heaters).
Chilled water version:
- Double deflection N diffuser.
- Fan guard for PHT unit heaters only (standard on PHM unit
heaters).
Hot water/steam version:
- Double deflection N diffuser.
- HP, HO, VR diffusers.
- Fan guard for PHT unit heaters only (standard on PHM unit
heaters).
- Room thermostat.
- Special installation kit (VAL, VAF, VAK, VAJF, VAGK, VAGJF,
VAGZ, VABGZ, VABF, HABGZ).
166
WESTHERM TECHNICAL SPECIFICATIONS
SIZE
35
45
50
55
65
70
PHM 230V – 1PH – 50 HZ – 5 SPEEDS
Min air flow (1 speed with 3-row coil) m³/h 284
608
1063
1299
1653
Max air flow (5 speed with 1-row coil) m³/h 2048
3748
6010
7623
9985
Nominal speed rpm 1370
1280
1400
1390
1300
Power supply kW
0.16
0.37
0.7
0.96
1.36
Current A
0.8
1.9
3.2
4.6
6.6
Class/IP
Class F/IP 55
PHT 230/400V – 3PH – 50 HZ – 900 RPM
Min air flow (900 rpm with 3-row coil) m³/h 1030
2620
3820
4950
6980
Sound pressure at 5 m dB(A) 46
53
57
61
63
Power supply kW
0.037
0.25
0.25
0.25
0.37
Current A
0.46/0.27
1.44/0.83
1.44/0.83
1.44/0.83
2.08/1.19
Class/IP
F/54
F/55
PHT 230/400V – 3PH – 50 HZ – 1400 RPM
Max air flow (1400 rpm with 1-row coil) m³/h 1840
4820
6750
8940
11960
Sound pressure at 5 m dB(A) 46
53
57
61
63
Power supply kW
0.038
0.25
0.55
0.55
0.75
Current A
0.46/0.23
1.41/0.81
2.46/1.42
2.46/1.42
3.22/1.86
Class/IP
F/54
F/55
CHILLED WATER VERSION – PERFORMANCE WITH 3-ROW COOLING COIL – VERSION PHM (230V – 1PH – 50 HZ) ONLY
Air flow speed 1 m³/h N/A
608
N/A
1299
1653
Sound pressure at 5 m (to NF-S 31-021) for speed 1 dB(A) N/A
19
N/A
33
42
Cooling capacity speed 1 (Air: 25°C/50% - water 7/12°C) kW
N/A
2.88
N/A
5.65
7.22
Cooling capacity speed 1 (Air: 35°C/50% - water 7/12°C) kW
N/A
7.36
N/A
16.09
19.16
Air flow speed 2 m³/h N/A
1149
N/A
2452
3123
Sound pressure at 5 m (to NF-S 31-021) for speed 2 dB(A) N/A
33
N/A
42
50
Cooling capacity speed 2 (Air: 25°C/50% - water 7/12°C) kW
N/A
3.82
N/A
7.47
9.48
Cooling capacity speed 2 (Air: 35°C/50% - water 7/12°C) kW
N/A
10.53
N/A
23.49
27.7
Air flow speed 3 (max. permitted speed) m³/h N/A
1726
N/A
3684
4691
Sound pressure at 5 m (to NF-S 31-021) for speed 3 dB(A) N/A
42
N/A
45
53
Cooling capacity speed 3 (Air: 25°C/50% - water 7/12°C) kW
N/A
4.68
N/A
3.82
11.92
Cooling capacity speed 3 (Air: 35°C/50% - water 7/12°C) kW
N/A
12.71
N/A
28.01
32.88
HOT WATER VERSION – PHM OR PHT MODEL
Min air flow (speed 1 with 3-row coil) m³/h 1440
3090
5400
6600
8398
Heating capacity for air 12°C/90% - water: 90/70% kW
23.01
43.08
67.92
86.21
110.59
Heating capacity for air 12°C/90% - water: 80/60% kW
19.23
35.31
55.93
71.53
90.87
Heating capacity for air 12°C/90% - water: 60/40% kW
11.47
19.41
31.5
41.59
50.61
Max air flow (speed 5 with 1-row coil) m³/h 2048
3748
6010
7623
9985
Heating capacity for air 12°C/90% - water: 90/70% kW
14.18
29.83
44.05
N/A
74.8
Heating capacity for air 12°C/90% - water: 80/60% kW
10.99
24.1
35.9
N/A
60.7
Heating capacity for air 12°C/90% - water: 60/40% kW
4.82
15.54
19.4
26.45
32.21
2320
13538
860
1.14
5.3
13780
N/A
0.75
3.65/2.1
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
11780
143.7
116.65
61.56
13538
96.34
77.53
39.74
WATER VAPOUR VERSION – PHM OR PHT MODEL
Min air flow (speed 1 with 3-row coil)
Heating capacity for air 12°C/90% - steam: 2 bar
Heating capacity for air 12°C/90% - steam: 4 bar
Heating capacity for air 12°C/90% - steam: 6 bar
Max air flow (speed 5 with 1-row coil)
Heating capacity for air 12°C/90% - steam: 2 bar
Heating capacity for air 12°C/90% - steam: 4 bar
Heating capacity for air 12°C/90% - steam: 6 bar
m³/h
kW
kW
kW
m³/h
kW
kW
kW
1440
N/A
N/A
23.01
2048
16.58
20.47
14.18
3090
64.05
78.59
43.08
3748
29.84
36.86
29.83
5400
N/A
N/A
67.92
6010
N/A
N/A
44.05
6600
N/A
N/A
86.21
7623
N/A
N/A
N/A
8398
N/A
197.59
110.59
9985
N/A
N/A
74.8
11780
N/A
N/A
143.7
13538
N/A
118.05
96.34
The sound data are subject to variations due to the position of the unit, the type of coil, accessories, the environment
of the room and background noise.
Diffuser VN
Diffuser HO
Diffuser VM
Diffuser HN
Diffuser VR
Diffuser HP
Horizontal discharge
Horizontal discharge
Horizontal discharge
Vertical discharge
Air curtain discharge
Vertical discharge
167
WATER SOURCE
HEAT PUMPS
WATER SOURCE HEAT PUMPS
Mini WCBZ
Reversible on
water loop system
LOW CAPACITY
ULTRA-COMPACT
MAIN FEATURES
Cooling capacity: from 1.9 to 3.0 kW
Heating capacity: from 2.7 to 3.6 kW
Sizes: 3 models, 1 casing
Refrigerant: R407C
Versions: - Cooling and heating mode
- Cooling only
- Cooling and heating mode
or cooling and electric heating mode
- Cooling and electric heating mode
Configurations: Horizontal recessed type
Thermostats and controllers included for units with
electromechanical controls:
- Standard controller:
th TUNE
- Optional controller:
pGD
Main options
Two-stage electric heating coil
G2/M1 filter
Quick connector
General alarm dry contact
Circuit breaker
Front or side discharge plenum
Fresh air intake
Main accessories
For the functions, see the "Controls" section on page 216
Advantages
Room sensor
Water flow switch
Motorised water valve
pGD mini-supervision station
Robust coaxial water heat exchanger
Operating range from +9° to +48°
High energy efficiency with EC motor and high COP/EER
values
Coil at discharge side to avoid installation of oversized
siphon
Electronic controller with ModBus communication
Easy access to components by large removable panels
Flexibility of aeraulic and hydraulic configuration to easily
replace the R22 units installed on site
Acoustic insulation and compressor isolated and mounted
on spring type anti-vibration mounts to provide an optimum
acoustic comfort
Condensate tray with anti-corrosion treatment
Low height for recessed installation: 250 mm
Flexibility of configuration
Operating limits (standard model)
Cooling
Entering water temperature
Heating
Cooling
Coaxial heat exchanger
Horizontal compressor
Air intake temperature
Heating
Maximum operating water pressure
170
Min
18ºC
Max
45ºC
Min
9ºC
Max
32ºC
Min
21ºC BS / 15ºC BH
Max
32ºC BS / 23ºC BH
Min
15ºC
Max
25ºC
31 bar
Mini WCBZ Reversible
TECHNICAL SPECIFICATIONS
SIZE
2000
2500
3000
2057
1686
2706
2405
1983
2997
2983
2346
3558
4.12
3.88
4.17
4.13
4.3
3.85
452
1 / G2
225 x 365 x 10
503
1 / G2
225 x 365 x 10
605
1 / G2
225 x 365 x 10
l/s
%
kPa
kPa
inch
mm
0.116
43
11
27
0.173
29
23
44
16
0.127
39
13
30
Male type ISO 1/2’ INT
16
V/Ph/Hz
W
W
W
A
A
A
230 / 1 / 50
595
722
1200
0.85
2.8
16
230 / 1 / 50
648
785
1600
0.85
3.0
16
230 / 1 / 50
879
932
2000
1.4
4.0
18.9
dB(A)
dB(A)
dB(A)
dB(A)
55/57/59
53/55/56
34/36/38
30/32/34
56/58/60
54/56/58
35/37/39
31/34/36
56/58/62
58/61/65
37/40/44
34/37/42
900 x 530 x 250
900 x 530 x 250
900 x 530 x 250
51
51
51
CAPACITIES
Total cooling capacity (1) W
Sensible cooling capacity W
Heating capacity (1) W
PERFORMANCE
COP (1)
EER (1)
VENTILATION
Nominal air flow m³/h
Number of air filter / Efficiency
Air filter dimensions / thickness mm
HYDRAULIC CIRCUIT
Nominal water flow
Cutoff water flow vs Nominal water flow (2)
WPD at nominal water flow
WPD at nominal water flow with valve
Water connection
Condensate outlet - External Ø
16
ELECTRICAL DATA
Power supply
Asborbed power - Cooling mode (3)
Absorbed power - Heating mode (3)
Electric heating capacity (4)
Fan maximum current (ESP=0 Pa)
Compressor nominal current
Compressor start-up current
SOUND LEVELS
Sound power, Return+Radiated (5)
Sound power, Discharge (5)
Sound pressure (6)
NR (6)
DIMENSIONS
L x D x H mm
WEIGHT
Unit weight kg
(1) Performance is based on nominal conditions: Cooling: Tair=27 °C, Twater=30 °C & Heating: Tair=20 °C, Twater=20 °C
(2) Protection by flow switch (optional)
(3) Absorbed electric power at nominal conditions (compressor + fan at high speed)
(4) Heating by electric heating coil available
(5) Sound power with 50 Pa external static pressure at high speed, in line unit with filter
(6) Sound pressure considering a sound attenuation of 21 dB in the room
171
WATER SOURCE HEAT PUMPS | HORIZONTAL COMPACT PACKAGED TYPE
WPHZ
Cooling only
WPHBZ
Reversible
MAIN FEATURES
Cooling capacities between 2.7 and 40.5 kW
Plate type condenser
Air flow up to 8000 m3/h
Easy access to the inside of the unit for maintenance
Thermostats and controllers included for units with
electromechanical controls:
- Standard controller:
SUPER
SI 24V
- Optional controller:
DSX@
Advantages
Robust and adaptable solutions for ENERGY LOOPING
installations.
The WPHZ/WPHBZ series are horizontal packaged units fitted with
a water-cooled plate condenser, adapted to operation connected
to a network of air distribution conduits.
For the functions, see the "Controls" section on page 216
Options
ENERGY EFFICIENCY
Option for double mixing box with 3 dampers for free cooling
Thermal or enthalpic control system with PCO controller card
and pGD controller
Compressor soft start (depending on model)
Fan soft start (depending on model)
Internal EC radial fan (depending on model)
AIR QUALITY
G4 gravimetric filter on return
Opacimetric filter on return class F6 to F9
(can be combined with a G4 or Fx+Fy)
SOUND LEVEL
Double thermal-acoustic insulation
Acoustic insulation on compressor
UNIT INSTALLATION
Magneto-thermal circuit breakers in the electrical board
60Hz power supply and voltages of 230, 208 etc.
Option to manufacture symmetrical configuration units
Rear air discharge
Water differential pressure switch
Water shut-off solenoid valves
Kit for bad weather installation
Upgraded motors
Flame-proof filter class M0
Thermal-acoustic insulation class M0
Hot gas bypass
Water regulator pressure switch valve
Hot water heating coils
Auxiliary electric heating coils
Pre-treated anti-corrosion coils
Suitable for disassembly
Without water condenser
MAINTENANCE
Service valves
External pressure tapping points
Dirty filter detector
Separate filter
CONTROLS
ARIA thermostat
pGD thermostat
SUPER SI thermostat (man. 24 V)
HoneyWell T8376B thermostat (man. 24 V)
Eberle 7007 thermostat (man. 24 V)
DSX@ thermostat (man. 24 V)
Alarm signals
Smoke detection
Remote start/stop
Stand-alone electrical board
Option for master/slave operation
Detection pressure switch for resetting from thermostat
Unit without thermostat
Wall-mounted room temperature sensor
Return temperature sensor
Temperature sensor in conduit
Operation for redundant machine
Centralised integrated management operation
Operation without neutral
Timer programming function and Modbus connection etc.
please refer to the Thermostats section
Besides these options, please speak to our Sales Department for any other
configuration or function that is not listed as being available.
172
Air inlet/outlet configuration options
WPHZ Cooling only
WPHBZ Reversible
MODEL
Nominal cooling capacity kW
standard
optional
TECHNICAL SPECIFICATIONS
091
121
141
171
201
2.7
3.5
4.1
5.2
6.4
Nominal cooling capacity T.R.
0.8
1.0
1.2
1.5
1.8
Nominal heating capacity kW
3.2
4.1
4.8
6.1
7.6
Total absorbed power for cooling kW
1.0
1.2
1.3
1.6
1.8
Total absorbed power for heating kW
1.2
1.5
1.6
1.8
2.0
230.1
230.1
230.1
230.1
230.1
550 - 26
900 - 17
1200 - 110
1500 - 58
1/2
1/2
3/4
3/4
Power supply (50 Hz ~) V
Air flow - static pressure m3/h - Pa 500 - 13
Water connections Ø (")
Dimensions (length x width x height) mm
Net weight kg
MODEL
Nominal cooling capacity kW
1/2
1055x560x385
1055x560x385
1055x560x385
1055x560x470
1055x560x470
79
80
82
85
87
251
351
401
501
701
8.1
11.9
13.4
16.6
20.6
Nominal cooling capacity T.R.
2.3
3.4
3.8
4.7
5.9
Nominal heating capacity kW
9.6
14.0
15.8
19.6
24.8
Total absorbed power for cooling kW
2.4
3.7
4.3
4.8
6.4
Total absorbed power for heating kW
2.5
3.8
4.4
5.0
6.6
230.1
230.1-400.3+N
400.3+N
400.3+N
400.3+N
2300 - 86
2400 - 94
3500 - 70
4300 - 80
3/4
1
1 1/4
1 1/4
Power supply (50 Hz ~) V
Air flow - static pressure m3/h - Pa 2000 - 55
Water connections Ø (")
Dimensions (length x width x height) mm
Net weight kg
MODEL
3/4
1135x670x530
1135x670x530
1135x670x530
1385x940x620
1385x940x620
104
115
120
160
200
751
1001
1201
Nominal cooling capacity kW
25.1
35.4
40.5
Nominal cooling capacity T.R.
7.1
10.1
11.5
Nominal heating capacity kW
Total absorbed power for cooling kW
Total absorbed power for heating kW
Power supply (50 Hz ~) V
30.1
41.8
49.6
8.3
11.0
13.4
8.6
11.3
13.8
400.3+N
400.3+N
400.3+N
Air flow - static pressure m3/h - Pa 4800 - 100
Water connections Ø (")
Dimensions (length x width x height) mm
Net weight kg
1 1/2
5800 - 86
8000 - 85
1 1/2
1 1/2
1385x940x620
1600x1040x690
1600x1040x690
225
275
290
173
WATER SOURCE HEAT PUMPS | HORIZONTAL COMPACT PACKAGED TYPE
WCHZ
Cooling only
WCHBZ
Reversible
MAIN FEATURES
Cooling capacities between 6.4 and 25.1 kW
Coaxial condenser
Air flows up to 4600 m3/h
Easy access to the inside of the unit for maintenance
Reduced dimensions
Thermostats and controllers included for units with
electromechanical controls:
- Standard controller:
SUPER
SI 24V
- Optional controller:
DSX@
Advantages
Robust and adaptable solutions for ENERGY LOOPING
installations.
The WCHZ/WCHBZ series are compact horizontal packaged units
fitted with a water-cooled coaxial condenser, adapted to operation
connected to a system of distribution conduits.
Wesper recommends installing units with coaxial condensers for
the highest robustness to counter possible impurities in the circuit.
For the functions, see the "Controls" section on page 216
Options
ENERGY EFFICIENCY
Option for double mixing box with 3 dampers for free cooling
(depending on model)
Thermal or enthalpic control system with PCO controller card
and pGD controller
Compressor soft start (depending on model)
Fan soft start (depending on model)
Internal EC radial fan (depending on model)
AIR QUALITY
G4 gravimetric filter on return
Opacimetric filter on return class F6 to F9 (can be combined
with a G4 or Fx+Fy)
SOUND LEVEL
Double thermal-acoustic insulation
Acoustic insulation on compressor
UNIT INSTALLATION
Water differential pressure switch
Magneto-thermal circuit breakers in the electrical board
60Hz power supply and voltages of 230, 208 etc.
Kit for bad weather installation
Upgraded motors
Operation for antifreeze electric heater in condensate tray
Flame-proof filter class M0
Hot gas bypass
Pressure switch valve
Inverse air intake or air discharge
Base frame
Hot water heating coils
Auxiliary electric heating coils
Pre-treated anti-corrosion coils
Sea water condenser
Without water condenser
MAINTENANCE
Service valves
External pressure tapping points
Dirty filter detector
Separate filter
Manometers
CONTROLS
ETN thermostat
ARIA thermostat
pGD thermostat
Thermostat DSX@
Alarm signals
Smoke detection
Remote start/stop
Stand-alone electrical board
Option for master/slave operation
High-pressure switch for resetting from thermostat
Unit without thermostat
Wall-mounted room temperature sensor
Return temperature sensor
Temperature sensor in conduit
Operation for redundant machine
Centralised integrated management operation
Operation without neutral
Timer programming function and Modbus connection etc.
please refer to the Thermostats section
Besides these options, please speak to our Sales Department for any other
configuration or function that is not listed as being available.
174
Air inlet/outlet configuration options
WCHZ Cooling only
standard
optional
TECHNICAL SPECIFICATIONS
MODEL
Nominal cooling capacity kW
201
251
271
351
401
6.4
8.1
9.0
11.3
13.4
Nominal cooling capacity T.R.
1.8
2.3
2.6
3.2
3.8
Total absorbed power kW
2.1
2.7
2.7
3.3
4.4
230.1
230.1
230.1 or 400.3+N
230.1- 230.3 or
400.3+N
230.3 or 400.3+N
Power supply (50 Hz ~) V
Air flow - static pressure m3/h - Pa 1500 - 58
Water connections Ø (")
Dimensions (length x width x height) mm
Net weight kg
1/2
1600 - 55
2000 - 77
2300 - 86
2400 - 94
1/2
1/2
1/2
3/4
990x520x425
1080x657x484
1200x750x484
1200x750x484
1280x850x542
87
104
123
130
147
501
701
721
751
Nominal cooling capacity kW
16.6
20.6
22.2
25.1
Nominal cooling capacity T.R.
4.7
5.9
6.3
7.1
Total absorbed power kW
5.2
6.6
6.2
7.7
230.3 or 400.3+N
400.3+N
230.3 or
400.3+N
230.3 or
400.3+N
MODEL
Power supply (50 Hz ~) V
Air flow - static pressure m3/h - Pa 3500 - 70
Water connections Ø (")
Dimensions (length x width x height) mm
Net weight kg
WCHBZ Reversible
3/4
4300 - 80
4500 - 75
4600 - 120
1
1
1
1400x900x542
1600x1030x630
1600x1030x630
1600x1030x630
160
240
259
259
TECHNICAL SPECIFICATIONS
MODEL
Nominal cooling capacity kW
201
251
351
401
501
6.0
8.1
11.1
13.0
16.5
Nominal cooling capacity T.R.
1.7
2.3
3.2
3.7
4.7
Nominal heating capacity kW
6.9
9.1
12.6
16.0
19.6
Total absorbed power for cooling kW
1.9
2.6
3.4
4.3
5.1
Total absorbed power for heating kW
1.8
2.5
3.2
4.2
5.0
230.1
230.1 or 400.3+N
230.1-230.3 or
400.3+N
230.3 or 400.3+N
230.3 or 400.3+N
Power supply (50 Hz ~) V
Air flow - static pressure m3/h - Pa 1500 - 58
Water connections Ø (")
Dimensions (length x width x height) mm
Net weight kg
1/2
2000 - 55
2300 - 86
2400 - 94
3500 - 70
1/2
1/2
3/4
3/4
1080x675x484
1200x750x484
1200x750x484
1280x850x542
1400x900x542
104
130
130
160
185
175
WATER SOURCE HEAT PUMPS | VERTICAL COMPACT PACKAGED TYPE
WPVZ
Cooling only
WPVBZ
Reversible
MAIN FEATURES
Cooling capacities between 8.1 and 132 kW
Plate type condenser
Air flow up to 21500 m3/h
Easy access to the inside of the unit for maintenance
Thermostats and controllers included for units with
electromechanical controls:
- Standard controller:
SUPER
SI 24V
- Optional controller:
DSX@
Advantages
Robust and adaptable solutions for ENERGY LOOPING
installations.
The WPVZ/WPVBZ series are compact vertical packaged units
fitted with a water-cooled plate type condenser, adapted to
operation connected to a system of distribution conduits.
For the functions, see the "Controls" section on page 216
Options
ENERGY EFFICIENCY
Option for double mixing box with 3 dampers for free cooling
Thermal or enthalpic control system with PCO controller card
and pGD controller
Compressor soft start (depending on model)
Fan soft start (depending on model)
Radial EC fan (depending on model)
AIR QUALITY
G4 gravimetric filter on return
Opacimetric filter on return class F6 to F9
(can be combined with a G4 or Fx+Fy)
SOUND LEVEL
Double thermal-acoustic insulation
Acoustic insulation on compressor
UNIT INSTALLATION
Magneto-thermal circuit breakers in the electrical board
60Hz power supply and voltages of 230, 208 etc.
Option to manufacture symmetrical configuration units
Kit for bad weather installation
Upgraded motors
Flame-proof filter class M0
Thermal-acoustic insulation class M0
Adaptable return filter
Water differential pressure switch
Air intake grille
Without water condenser
Water regulator pressure switch valve
Rear air discharge (mod. 1001-4002)
Front air discharge (mod. 201-751)
Discharge plenum
Hot gas bypass
Hot water heating coils
Auxiliary electric heating coils
Pre-treated anti-corrosion coils
Suitable for disassembly
MAINTENANCE
Service valves
External pressure tapping points
Dirty filter detector
Separate filter
CONTROLS
ARIA thermostat
pGD thermostat
SUPER SI thermostat (man. 24 V)
HoneyWell T8376B thermostat (man. 24 V)
Eberle 7007 thermostat (man. 24 V)
DSX@ thermostat (man. 24 V)
Alarm signals
Smoke detection
Remote start/stop
Stand-alone electrical board
Option for master/slave operation
Detection pressure switch for resetting from thermostat
Unit without thermostat
Wall-mounted room temperature sensor
Return temperature sensor
Temperature sensor in conduit
Operation for redundant machine
Centralised integrated management operation
Operation without neutral
Timer programming function and Modbus connection etc.
please refer to the Thermostats section.
Besides these options, please speak to our Sales Department for any other
configuration or function that is not listed as being available.
176
Air inlet/outlet configuration options
WPVZ/BZ 251-751
standard
optional
WPVZ/BZ 1001-4002
WPVZ Cooling only
WPVBZ Reversible
TECHNICAL SPECIFICATIONS
251
351
401
501
701
Nominal cooling capacity
Nominal cooling capacity
Nominal heating capacity
Total absorbed power for cooling
Total absorbed power for heating
Power supply (50 Hz ~)
Air flow - static pressure
Water connections
Dimensions (length x width x height)
Net weight
kW
T.R.
kW
kW
kW
V
m3/h - Pa
Ø (")
mm
kg
8.1
2.3
9.6
2.4
2.5
230.1
2000 - 55
3/4
720x650x1230
139
11.9
3.4
14.0
3.7
3.8
230.1 or 400.3+N
2300 - 86
1
720x650x1230
146
13.4
3.8
15.8
4.2
4.4
400.3+N
2400 - 94
1
780x650x1380
166
16.6
4.7
19.6
4.8
4.9
400.3+N
3500 - 70
1 1/4
1140x700x1730
251
21.0
6.0
24.8
6.4
6.6
400.3+N
4300 - 80
1 1/4
1140x700x1730
258
751
1001
1201
1501
2002
Nominal cooling capacity
Nominal cooling capacity
Nominal heating capacity
Total absorbed power for cooling
Total absorbed power for heating
Power supply (50 Hz ~)
Air flow - static pressure
Water connections
Dimensions (length x width x height)
Net weight
kW
T.R.
kW
kW
kW
V
m3/h - Pa
Ø (")
mm
kg
25.5
7.3
30.1
8.3
8.6
400.3+N
4800 - 100
1 1/2
1140x700x1730
265
35.4
10.1
41.8
11.0
11.3
400.3+N
7400 - 70
1 1/2
1790x870x1630
450
42.0
11.9
49.6
13.4
13.8
400.3+N
8200 - 80
1 1/2
1790x870x1630
478
54.0
15.4
63.7
15.9
16.4
400.3+N
9000 - 110
1 1/2
1790x870x1630
515
70.8
20.1
83.5
22.6
23.3
400.3+N
11000 - 190
1 1/2
1790x980x1980
650
MODEL
MODEL
2402
3002
4002
Nominal cooling capacity kW
84.0
108.0
132.0
MODEL
Nominal cooling capacity T.R.
23.9
30.7
37.5
Nominal heating capacity kW
99.1
127.4
155.8
Total absorbed power for cooling kW
26.5
35.0
43.0
Total absorbed power for heating kW
27.3
36.0
44.3
400.3+N
400.3+N
400.3+N
18000 - 270
21500 - 190
1 1/2
2
2
1790x980x1980
2404x1157x2092
2404x1157x2092
711
973
1065
Power supply (50 Hz ~) V
Air flow - static pressure m3/h - Pa 12000 - 190
Water connections Ø (")
Dimensions (length x width x height) mm
Net weight kg
177
WATER SOURCE HEAT PUMPS | VERTICAL COMPACT PACKAGED TYPE
WCVZ
Cooling only
WCVBZ
Reversible
MAIN FEATURES
Cooling capacities between 6.0 and 120 kW
Coaxial condenser
Air flows up to 21500 m3/h
Easy access to the inside of the unit for maintenance
Reduced dimensions
Thermostats and controllers included for units with
electromechanical controls:
- Standard controller:
SUPER
SI 24V
- Optional controller:
DSX@
Advantages
Robust and adaptable solutions for energy looping installations.
The WCVZ/WCVBZ series are compact vertical packaged units
fitted with a water-cooled coaxial condenser, adapted to operation
connected to a system of distribution conduits.
Wesper recommends installing units with coaxial condensers for the
highest robustness to counter possible impurities in the circuit.
For the functions, see the "Controls" section on page 216
Options
ENERGY EFFICIENCY
Option for double mixing box with 3 dampers for free cooling
Thermal or enthalpic control system with PCO controller card
and pGD controller
Compressor soft start (depending on model)
Fan soft start (depending on model)
Internal EC radial fan (depending on model)
AIR QUALITY
G4 gravimetric filter on return
Opacimetric filter on return class F6 to F9
(can be combined with a G4 or Fx+Fy)
SOUND LEVEL
Double thermal-acoustic insulation
Acoustic insulation on compressor
UNIT INSTALLATION
Magneto-thermal circuit breakers in the electrical board
60Hz power supply and voltages of 230, 208 etc.
Kit for bad weather installation
Upgraded motors
Operation for antifreeze electric heater in condensate tray
Flame-proof filter class M0
Hot gas bypass
Pressure switch valve
More compact WCVSZ units
WCVCZ units for air conditioning in swimming pools
Hot water heating coils (only models WCVZ – cooling only)
Auxiliary electric heating coils
Pre-treated anti-corrosion coils
Front air discharge (mod. 201/751)
Rear air discharge (mod. 1001/3603)
Without water condenser
Sea water condenser
Without compressor
Discharge plenum
Air intake grille
Adaptable return filter
Base frame
Manometers
Water differential pressure switch
Suitable for disassembly
MAINTENANCE
Service valves
External pressure tapping points
Dirty filter detector
Separate filter
CONTROLS
ETN thermostat
ARIA thermostat
pGD thermostat
Thermostat DSX@
SUPER SI thermostat
Alarm signals
Smoke detection
Remote start/stop
Stand-alone electrical board
Option for master/slave operation
High-pressure switch for resetting from thermostat
Unit without thermostat
Wall-mounted room temperature sensor
Return temperature sensor
Temperature sensor in conduit
Operation for redundant machine
Centralised integrated management operation
Operation without neutral
Timer programming function and Modbus connection etc.
please refer to the Thermostats section
Besides these options, please speak to our Sales Department for any other
configuration or function that is not listed as being available.
178
Air inlet/outlet configuration options
WCVBZ 201-351
standard
optional
WCVZ 201-751
WCVBZ 401
WCVZ Cooling only
WCVZ 1001-3603
TECHNICAL SPECIFICATIONS
MODEL
Nominal cooling capacity kW
201
251
271
351
401
501
6.4
8.1
9.0
11.9
13.4
16.6
4.7
Nominal cooling capacity T.R.
1.8
2.3
2.6
3.4
3.8
Total absorbed power kW
1.7
2.1
2.3
3.3
3.5
4.5
230.1
230.1
230.1 or
400.3+N
230.1-230.3 o
400.3+N
230.3 or
400.3+N
230.3 or
400.3+N
3500 - 70
Power supply (50 Hz ~) V
Air flow - static pressure m3/h - Pa 1500 - 58
Water connections Ø (")
Dimensions (length x width x height) mm
Net weight kg
MODEL
Nominal cooling capacity kW
2000 - 55
2000 - 77
2300 - 86
2400 - 94
1/2
1/2
1/2
1/2
1/2
3/4
628x440x1060
720x550x1200
720x550x1200
720x550x1200
780x550x1350
1140x600x1700
105
134
134
141
160
245
701
721
751
1001
1201
1002
20.6
23.0
25.1
35.4
40.5
35.6
10.1
Nominal cooling capacity T.R.
5.9
6.5
7.1
10.1
11.5
Total absorbed power kW
5.4
5.9
6.3
9.8
11.2
9.7
400.3+N
230.3 or
400.3+N
230.3 or
400.3+N
230.3 or
400.3+N
230.3 or
400.3+N
230.3 or
400.3+N
7300 - 87
Power supply (50 Hz ~) V
Air flow - static pressure m3/h - Pa 4300 - 80
Water connections Ø (")
Dimensions (length x width x height) mm
Net weight
4500 - 75
4800 - 100
7400 - 70
8200 - 80
1
1
1
2
2
2
1140x600x1700
1140x600x1700
1140x600x1700
1700x870x1600
1700x870x1600
1700x870x1600
kg
252
252
258
445
472
470
1402
1502
2002
2402
3003
3603
Nominal cooling capacity kW
41.2
50.2
70.8
81.0
105.0
120.0
Nominal cooling capacity T.R.
11.7
14.3
20.1
23.0
29.9
34.1
Total absorbed power kW
11.3
13.7
19.7
22.4
28.9
33.3
230.3 or
400.3+N
230.3 or
400.3+N
230.3 or
400.3+N
230.3 or
400.3+N
230.3 or
400.3+N
230.3 or
400.3+N
8200 - 80
9000 - 110
11000 - 190
12000 - 190
18000 - 270
21500 - 190
2
2
2
2
2
2
MODEL
Power supply (50 Hz ~) V
Air flow - static pressure m3/h - Pa
Water connections Ø (")
Dimensions (length x width x height) mm
Net weight kg
WCBVZ Reversible
1700x870x1600 1700x870x1600 1700x980x1950 1700x980x1950 2307x1157x2062 2307x1157x2062
515
525
645
706
968
1060
TECHNICAL SPECIFICATIONS
201
251
351
401
Nominal cooling capacity kW
6.0
8.1
11.0
13.0
Nominal cooling capacity T.R.
1.7
2.3
3.1
3.7
Nominal heating capacity kW
6.9
9.1
12.6
16.0
Total absorbed power for cooling kW
1.8
2.5
3.3
3.8
Total absorbed power for heating kW
1.8
2.4
3.2
3.8
230.1
230.1 or 400.3+N
230.1-230.3 or 400.3+N
230.3 or 400.3+N
1500 - 58
2000 - 55
2300 - 86
2400 - 94
1/2
1/2
1/2
1/2
601x625x1000
601x625x1000
601x625x1000
780x550x1350
105
134
141
165
MODEL
Power supply (50 Hz ~) V
Air flow - static pressure m3/h - Pa
Water connections Ø (")
Dimensions (length x width x height) mm
Net weight kg
179
DIRECT EXPANSION
SYSTEMS
DIRECT EXPANSION SYSTEMS | AIR / AIR INVERTER
ACHIBA
ECHIBA/CCHIBA
Reversible
Reversible
PACKAGED configuration
SPLIT configuration
ECHIBA/CCHIBA
ACHIBA
Options
MAIN FEATURES
ENERGY EFFICIENCY
Option for mixing module for semi-enthalpic free cooling with
two dampers
Variable air flow for external fan
Three air speeds in the internal fan
Cooling capacities between 4 and 29 kW
EER/COP coefficient up to 3.2 under nominal
temperature conditions
Scroll compressors with soft start
R410A refrigerant
Can be combined with the RCAH range of high
energy efficiency heat recovery exchangers and
filtration group to class F
DC inverter technology: maximum savings and
comfort
Low sound level
High efficiency in heat pump mode for low external
temperatures down to -15˚C
Operating limit in cooling mode with an external
temperature of 48˚C
Fan soft start, internal and/or external
Oil separator (only for ductable units)
Remote start/stop
Remote cooling/heating
Timer programming and Modbus connection
TH Tune controls supplied as standard
AIR QUALITY
G4 gravimetric filter on return
Opacimetric filter on return class F6 to F9 (can be combined with
a G4 or Fx+Fy)
SOUND LEVEL
Double thermal-acoustic insulation
Acoustic insulation on compressor
UNIT INSTALLATION
Option to manufacture symmetrical configuration units
Kit for bad weather installation
Upgraded motors
Operation for antifreeze electric heater in condensate tray
Flame-proof filter class M0
Hot water heating coils
Electric heating coils for defrost aid
Pre-treated anti-corrosion coils
Ready for disassembly
Quick connection valves with refrigerant gas pre-charge (for
SPLIT configuration only)
MAINTENANCE
Service valves
External pressure tapping points (in series on model 901)
Dirty filter detector
Filter on condenser
Separate filter
Advantages
High energy efficiency inverter for energy efficiency conversions in
the commercial sector.
This range of packaged and split units uses a horizontal design. It
is suitable for operation connected to a network of air distribution
conduits, in both the internal and external section.
Designed to be installed inside the area to be air conditioned, they
are characterised by installation versatility.
CONTROLS
Alarm signals
Smoke detection
Stand-alone electrical board
Wall-mounted or room temperature sensor
Discharge temperature sensor
Centralised integrated management operation
Operation without neutral
Besides these options, please speak to our Sales Department for any other
configuration or function that is not listed as being available.
181
DIRECT EXPANSION SYSTEMS | AIR / AIR INVERTER
Air inlet/outlet configuration options
standard
ACHIBA
ECHIBA/CCHIBA
301
601, 741
ACHIBA Reversible
optional
ECHIBA
901
CCHIBA 301
CCHIBA 601, 741
CCHIBA 901
TECHNICAL SPECIFICATIONS
MODEL
Maximum cooling capacity (110 Hz) kW
301
601
741
901
8.1
17.3
22.4
28.9
Maximum cooling capacity (110 Hz) T.R.
2.3
4.9
6.4
8.2
Maximum heating capacity (110 Hz) kW
8.3
18.6
24.2
28.9
Nominal cooling capacity (80 Hz) kW
7.4
12.9
16.6
20.6
Nominal cooling capacity (80 Hz) T.R.
2.1
3.7
4.7
5.9
Nominal heating capacity (80 Hz) kW
Maximum EER coefficient kW/kW
Maximum COP coefficient kW/kW
SCOP coefficient (hot zone) kW/kW
Power supply (50 Hz ~) V
8.3
13.0
15.7
20.4
>8
3.16
2.95
2.90
-
3.21
3.03
2.93
4.1
-
-
-
220-240 / 1 / 50
400.3+N
400.3+N
400.3+N
Nominal internal air flow for cooling m3/h
1000/1400/1800
2300
3000
3700
Nominal internal air flow for heating m3/h
1100/1400/1600
2800
3600
4400
Max. int. air flow - static pressure m3/h - Pa
1800 - 50
3600 - 70
4600 - 80
5600 - 90
Max. ext. air flow - static pressure m3/h - Pa
3000 - 50
5600 - 50
6200 - 50
7,500 - 50
1445x1339x504
1755x1697x640
1755x 1697x 640
1998x 1755x672
220
375
420
495
Dimensions (length x width x height) mm
Net weight kg
CCHIBA Reversible
- OUTDOOR UNIT TECHNICAL SPECIFICATIONS
MODEL
Maximum cooling capacity (110 Hz) kW
301
601
741
901
8.1
17.3
22.4
26.5
Maximum cooling capacity (110 Hz) T.R.
2.3
4.9
6.4
7.5
Maximum cooling capacity (110 Hz) kW
8.3
18.6
24.2
28.9
Nominal cooling capacity (80 Hz) kW
7.4
12.9
16.6
20.6
Nominal cooling capacity (80 Hz) T.R.
2.1
3.7
4.7
5.9
Nominal cooling capacity (80 Hz) kW
Maximum EER coefficient kW/kW
Maximum COP coefficient kW/kW
SCOP coefficient (hot zone) kW/kW
Power supply (50 Hz ~) V
Refrigerant connection. Liquid line Ø (")
Refrigerant connection. Gas line Ø (")
Max. ext. air flow - static pressure m3/h - Pa
Dimensions (length x width x height) mm
Net weight kg
ECHIBA Reversible
8.3
13.0
15.7
20.4
-
3.16
2.95
2.90
-
3.21
3.03
2.93
4.1
-
-
-
220-240 / 1 / 50
400.3+N
400.3+N
400.3+N
1/2
1/2
5/8
5/8
3/4
7/8
1 1/8
1 1/8
3000 - 50
5600 - 50
6200 - 50
7500 - 50
1445x825x504
1755x1004x640
1755x1004x640
1750x1057x662
148
240
295
312
- INDOOR UNIT TECHNICAL SPECIFICATIONS
MODEL
Maximum cooling capacity (110 Hz) kW
301
601
741
901
8.1
17.3
22.4
28.9
Maximum cooling capacity (110 Hz) T.R.
2.3
4.9
6.4
8.2
Maximum cooling capacity (110 Hz) kW
8.3
18.6
24.2
28.9
Nominal cooling capacity (80 Hz) kW
7.4
12.9
16.6
20.6
Nominal cooling capacity (80 Hz) T.R.
2.1
170.9
210.7
256.2
Nominal cooling capacity (80 Hz) kW
Maximum EER coefficient kW/kW
Maximum COP coefficient kW/kW
SCOP coefficient (hot zone) kW/kW
Power supply (50 Hz ~) V
Refrigerant connection. Liquid line Ø (")
Refrigerant connection. Gas line Ø (")
8.3
13.0
15.7
20.4
-
3.16
2.95
2.90
-
3.21
3.03
2.93
4.1
-
-
-
220-240 / 1 / 50
400.3+N
400.3+N
400.3+N
1/2
1/2
5/8
5/8
3/4
7/8
1 1/8
1 1/8
Nominal internal air flow for cooling m3/h
1000/1400/1800
2300
3000
3700
Nominal internal air flow for heating m3/h
1100/1400/1600
2800
3600
4400
1800 - 50
3600 - 70
4600 - 80
5500 - 90
1445x600x504
1755x752x640
1755x752x640
1750x900x662
83
145
150
180
Max. int. air flow - static pressure m3/h - Pa
Dimensions (length x width x height) mm
Net weight kg
182
Amortisation study
Comparative study and calculation of the period of amortisation for replacing the existing unit with a fixed-speed unit
or an inverter unit in the banking sector. This is the equivalent of a standard branch in the climate region of Madrid.
Calculation estimated according to data supplied by the client.
WESPER's Technical Department is at your disposal
to calculate cost estimates for replacing units.
Cost of inverter vs on-off (€)
12,500
RECOMMENDED
PRODUCT
FOR
ENERGY
REHABILITATION
10,500
8,500
6,500
ON-OFF
INVERTER
4,500
0
3
6
9
12
15
18
19
21
24
27
30
33
36
Amortisation period - month
Standard controller
TH TUNE
Performance comparison
INVERTER
TECHNOLOGY.
MAXIMUM
YIELD
Temperatura (ºC)
Functions: Selection of 3
speeds. Automatic MODE, 1
stage electrical resistance (only
active in defrost). 3 access
levels: USER, MAINTENANCE,
MANUFACTURER. Option of
ModBus protocol with RS 485
card
Tiempo
SET 26ºC
SET 24ºC
SET 22ºC
Frequencia de compresor
Example of packaged installation
Example of installation for
inverter units
Air-air installation by ducts
ACHBA
183
DIRECT EXPANSION SYSTEMS | AIR / AIR INVERTER
ACVIBA
ECVIBA/CCVIBA
Reversible
Reversible
PACKAGED configuration
SPLIT configuration
ACVIBA
MAIN FEATURES
Cooling capacities up to 30 kW
EER/COP coefficient up to 2.9 under nominal
temperature conditions
Scroll compressors with soft start
R410A refrigerant
DC inverter technology: maximum savings and
comfort
Low sound level
High efficiency in heat pump mode for low external
temperatures up to -15˚C
Operating limit in cooling mode with an external
temperature of 48˚C
Fan soft start, internal and/or external
Oil separator (only for ductable units)
Remote start/stop
Remote cooling/heating
Timer programming and Modbus connection
TH Tune controls supplied as standard
Advantages
High energy efficiency inverter for energy efficiency conversions in
the commercial sector.
This range of packaged and split units uses a vertical design. It is
suitable for operation connected to a network of air distribution
conduits, in both the internal and external section. Designed
to be installed inside the area to be air conditioned, they are
characterised by installation versatility.
ECVIBA/CCVIBA
Options
ENERGY EFFICIENCY
Option for mixing module for free cooling with three dampers
AIR QUALITY
G4 gravimetric filter on return
Opacimetric filter on return class F6 to F9 (can be combined with
a G4 or Fx+Fy)
SOUND LEVEL
Double thermal-acoustic insulation
Acoustic insulation on compressor
UNIT INSTALLATION
Option to manufacture symmetrical configuration units
Kit for bad weather installation
Upgraded motors
Operation for antifreeze electric heater in condensate tray
Flame-proof filter class M0
Hot water heating coils
Electric heating coils for defrost aid
Pre-treated anti-corrosion coils
Suitable for disassembly
Only for SPLIT configuration:
- Quick connection valves with pre-load
of refrigerant gas
MAINTENANCE
Service valves
Dirty filter detector
Filter on condenser
Separate filter
CONTROLS
Alarm signals
Smoke detection
Stand-alone electrical board
Wall-mounted or room temperature sensor
Discharge temperature sensor
Centralised integrated management operation
Operation without neutral
Besides these options, please speak to our Sales Department for any other
configuration or function that is not listed as being available.
184
Air inlet/outlet configuration options
ACVIBA
standard
optional
ECVIBA/CCVIBA
ECVIBA 601.741.901
ACVIBA Reversible
TECHNICAL SPECIFICATIONS
MODEL
Maximum cooling capacity (120 Hz)
Maximum cooling capacity (120 Hz)
Maximum heating capacity (120 Hz)
Nominal cooling capacity (80 Hz)
Nominal cooling capacity (80 Hz)
Nominal heating capacity (80 Hz)
Maximum EER coefficient
Maximum COP coefficient
Power supply (50 Hz ~)
Internal air flow
Max. int. air flow - static pressure
Max. ext. air flow - static pressure
Dimensions (length x width x height)
Net weight
CCVIBA Reversible
kW
T.R.
kW
kW
T.R.
kW
kW/kW
kW/kW
V
m3/h
m3/h - Pa
m3/h - Pa
mm
kg
601
741
901
18.5
5.3
20.0
13.8
3.9
14.0
2.90
2.95
400.3+N
2700/3200/4000
4000 - 70
6800 - 50
1130x800x1900
400
23.9
6.8
26.1
17.7
5.0
18.0
2.86
2.94
400.3+N
3200/3800/4800
4800 - 75
7300 - 50
1130x800x1900
470
28.3
8.1
30.6
22.0
6.3
22.5
2.96
2.99
400.3+N
3900/4650/5900
5900 - 90
10,000 - 50
1700x870x1900
600
- OUTDOOR UNIT TECHNICAL SPECIFICATIONS
MODEL
Maximum cooling capacity (120 Hz)
Maximum cooling capacity (120 Hz)
Maximum heating capacity (120 Hz)
Nominal cooling capacity (80 Hz)
Nominal cooling capacity (80 Hz)
Nominal heating capacity (80 Hz)
Maximum EER coefficient
Maximum COP coefficient
Power supply (50 Hz ~)
Refrigerant connection. Liquid line
Refrigerant connection. Gas line
Max. ext. air flow - static pressure
Dimensions (length x width x height)
Net weight
ECVIBA Reversible
CCVIBA 601.741.901
kW
T.R.
kW
kW
T.R.
kW
kW/kW
kW/kW
V
Ø (")
Ø (")
m3/h - Pa
mm
kg
601
741
901
18.5
5.3
20.0
13.8
3.9
14.0
2.90
2.95
400.3+N
1/2
7/8
6800 - 50
1130x800x1250
260
23.9
6.8
26.1
17.7
5.0
18.0
2.86
2.94
400.3+N
5/8
1 1/8
7300 - 50
1130x800x1250
320
28.3
8.1
30.6
22.0
6.3
22.5
2.96
2.99
400.3+N
5/8
1 1/8
10,000 - 50
1700x870x1250
390
- INDOOR UNIT TECHNICAL SPECIFICATIONS
MODEL
Maximum cooling capacity (120 Hz)
Maximum cooling capacity (120 Hz)
Maximum heating capacity (120 Hz)
Nominal cooling capacity (80 Hz)
Nominal cooling capacity (80 Hz)
Nominal heating capacity (80 Hz)
Maximum EER coefficient
Maximum COP coefficient
Power supply (50 Hz ~)
Refrigerant connection. Liquid line
Refrigerant connection. Gas line
Internal air flow
Max. int. air flow - static pressure
Dimensions (length x width x height)
Net weight
kW
T.R.
kW
kW
T.R.
kW
kW/kW
kW/kW
V
Ø (")
Ø (")
m3/h
m3/h - Pa
mm
kg
601
741
901
18.5
5.3
20.0
13.8
3.9
14.0
2.90
2.95
400.3+N
1/2
7/8
2700/3200/4000
4000 - 70
1130x800x650
140
23.9
6.8
26.1
17.7
5.0
18.0
2.86
2.94
400.3+N
5/8
1 1/8
3200/3800/4800
4800 - 75
1130x800x650
150
28.3
8.1
30.6
22.0
6.3
22.5
2.96
2.99
400.3+N
5/8
1 1/8
3900/4650/5900
5900 - 90
1700x870x650
210
185
DIRECT EXPANSION SYSTEMS | AIR / AIR ON-OFF
ACHA
ECHA/CCHA
ACHBA
ECHBA/CCHBA
Reversible
Reversible
PACKAGED configuration
SPLIT configuration
Cooling only
Cooling only
ECHA/CCHA - ECHBA/CCHBA
ACHA/ACHBA
Advantages
MAIN FEATURES
Cooling capacities between 5.6 and 33.5 kW
Scroll compressors
R410A refrigerant
Can be combined with the RCAH range of high energy efficiency heat recovery exchangers and filtration
group to class F.
Thermostats and controllers included for units with
electromechanical controls:
- Standard controller:
SUPER
SI 24V
Maximum versatility for air conditioning via the conduits of
commercial buildings.
This range of packaged and split units uses a horizontal design. It
is suitable for operation connected to a network of air distribution
conduits, in both the internal and external section.
Designed to be installed inside the area to be air conditioned, they
are characterised by offering a wide installation versatility.
- Optional controller:
DSX@
For the functions, see the "Controls" section on page 216
Air inlet/outlet configuration options
standard
optional
ACHA/ACHBA
201, 501
701, 721, 751, 801
1001, 1201
ECHA/CCHA - ECHBA/CCHBA
ECHA/ECHBA 251, 1201
CCHA/CCHBA 201, 251, 351, 371, 501
CCHA/CCHBA 701, 721, 751, 801
186
CCHA/CCHBA 1001, 1201
Options
ENERGY EFFICIENCY
Option for mixing module for free cooling with two and three
dampers
Thermal or enthalpic control system with PCO controller card
and pGD controller
Condensation controlled by frequency inverter or variable
voltage controller
Compressor soft start (depending on model)
Fan soft start, internal and/or external (depending on model)
AIR QUALITY
G4 gravimetric filter on return
Opacimetric filter on return class F6 to F9 (can be combined
with a G4 or Fx+Fy)
SOUND LEVEL
Double thermal-acoustic insulation
Acoustic insulation on compressor
UNIT INSTALLATION
Magneto-thermal circuit breakers in the electrical board
60Hz power supply and voltages of 230, 208 etc.
Option to manufacture symmetrical configuration units
Kit for bad weather installation
Upgraded motors
Operation for antifreeze electric heater in condensate tray
Flame-proof filter class M0
Hot gas bypass
Hot water heating coils
Auxiliary electric heating coils
Pre-treated anti-corrosion coils
Availability of models with R407C refrigerant to be consulted
Suitable for disassembly
Only for SPLIT configuration:
- Oil separator
- Service valves
- Quick connection valves with pre-load
of refrigerant gas
ACHA Cooling only
ACHBA Reversible
MAINTENANCE
Service valves
External pressure tapping points
Dirty filter detector
Filter on condenser
Separate filter
CONTROLS
ETN thermostat
ARIA thermostat
SUPER SI thermostat (man. 24 V)
pGD thermostat
DSX@ thermostat (man. 24 V)
Alarm signals
Smoke detection
Remote start/stop
Stand-alone electrical board
Option for master/slave operation
Detection pressure switch for resetting from thermostat
Unit without thermostat
Wall-mounted room temperature sensor
Return temperature sensor
Temperature sensor in conduit
Operation for redundant machine
Centralised integrated management operation
Operation without neutral
Timer programming function and Modbus connection etc.
please refer to the Thermostats section
Besides these options, please speak to our Sales Department for any other
configuration or function that is not listed as being available.
TECHNICAL SPECIFICATIONS
201
251
351
371
401
501
Nominal cooling capacity kW
5.6
7.4
9.7
11.6
12.4
14.1
MODEL
Nominal cooling capacity T.R.
1.6
2.1
2.8
3.3
3.5
4.0
Nominal heating capacity kW
6.1
8.2
9.8
12
13.8
16.4
Total absorbed power for cooling kW
2.8
3.3
4.3
4.9
5.1
6.5
Total absorbed power for heating kW
2.6
3.1
3.8
4.4
4.6
5.9
230.1
230.1-400.3+N
230.1-400.3+N
400.3+N
400.3+N
400.3+N
Int. air flow static pressure m /h - Pa
1500 - 37
1600 - 47
2000 - 37
2700 - 32
2700 - 32
3200 - 48
Ext. air flow static pressure m3/h - Pa
2100 - 50
2450 - 50
3180 - 50
3800 - 50
3800 - 50
4150 - 50
1175x1109x452
1325x1259x504
1445x1339x504 1505x1389x562 1505x1389x562 1505x1389x562
159
197
219
253
Power supply (50 Hz ~) V
3
Dimensions (length x width x height) mm
Net weight kg
253
260
701
721
751
801
1001
1201
Nominal cooling capacity kW
17.2
18.5
20.8
21.9
28.4
33.5
Nominal cooling capacity T.R.
4.9
5.3
5.9
6.2
8.1
9.5
Nominal heating capacity kW
18.9
20.4
21.9
24.6
29.8
37.2
Total absorbed power for cooling kW
7.8
8.5
9.5
9.7
12.4
15.7
Total absorbed power for heating kW
6.9
7.9
8.1
8.8
11.8
15.1
MODEL
400.3+N
400.3+N
400.3+N
400.3+N
400.3+N
400.3+N
Int. air flow static pressure m3/h - Pa
Power supply (50 Hz ~) V
4300 - 50
4300 - 50
4300 - 50
4300 - 50
5900 - 50
7550 - 82
Ext. air flow static pressure m3/h - Pa
5600 - 50
5600 - 50
5700 - 50
6200 - 50
7600 - 50
9900 - 90
1755x1697x640
1755x1697x640
1755x1697x640 1755x1697x640 1998x1755x672 2400x2201x782
354
354
395
Dimensions (length x width x height) mm
Net weight kg
187
404
476
633
DIRECT EXPANSION SYSTEMS | AIR / AIR ON-OFF
CCHA Cooling only
CCHBA Reversible
- OUTDOOR UNIT TECHNICAL SPECIFICATIONS
201
251
351
371
401
501
Nominal cooling capacity kW
5.6
7.4
9.7
11.6
12.4
14.1
MODEL
Nominal cooling capacity T.R.
1.6
2.1
2.8
3.3
3.5
4.0
Nominal heating capacity kW
6.1
8.2
9.8
12
13.8
16.4
Total absorbed power for cooling kW
2.5
3.0
3.9
4.3
4.5
5.6
Total absorbed power for heating kW
2.3
2.9
3.4
3.8
4.0
4.9
230.1
230.1 - 400.3+N 230.1 - 400.3+N 400.3+N
400.3+N
400.3+N
Refrigerant connection. Liquid line Ø (")
3/8"
3/8"
3/8"
1/2"
1/2"
1/2"
Refrigerant connection. Gas line Ø (")
1/2"
5/8"
3/4"
7/8"
7/8"
7/8"
Power supply (50 Hz ~) V
Air flow - ext. static pressure m3/h - Pa
2100 - 50
2450 - 50
3180 - 50
3800 - 50
3800 - 50
4150 - 50
1175x619x452
1325x706x504
1405x825x504
1455x843x562
1455x843x562
1455x843x562
106
133
146
172
172
172
701
721
751
801
1001
1201
Nominal cooling capacity kW
17.2
18.5
20.8
21.9
28.4
33.5
Nominal cooling capacity T.R.
4.9
5.3
5.9
6.2
8.1
9.5
Nominal heating capacity kW
18.9
20.4
21.9
24.6
29.8
37.2
Total absorbed power for cooling kW
6.7
7.4
8.3
8.5
11.1
13.6
Total absorbed power for heating kW
5.7
6.7
7
7.4
10.2
12.2
400.3+N
400.3+N
400.3+N
400.3+N
400.3+N
400.3+N
Refrigerant connection. Liquid line Ø (")
1/2"
1/2"
5/8"
5/8"
5/8"
5/8"
Refrigerant connection. Gas line Ø (")
7/8"
7/8"
7/8"
7/8"
1 1/8"
1 1/8"
5600 - 50
5600 - 50
5700 - 50
6200 - 50
7600 - 50
9900 - 90
Dimensions (length x width x height) mm
Net weight kg
MODEL
Power supply (50 Hz ~) V
Air flow - ext. static pressure m3/h - Pa
Dimensions (length x width x height) mm
Net weight kg
ECHA Cooling only
1755x1004x640 1755x1004x640 1755x1004x640 1755x1004x640 1750x1057x662 2300x1382x782
223
ECHBA Reversible
223
263
272
292
410
- INDOOR UNIT TECHNICAL SPECIFICATIONS
201
251
351
371
401
501
Nominal cooling capacity kW
5.6
7.4
9.7
11.6
12.4
14.1
Nominal cooling capacity T.R.
1.6
2.1
2.8
3.3
3.5
4.0
Nominal heating capacity kW
6.1
8.2
9.8
12
13.8
16.4
Total absorbed power for cooling kW
0.15
0.23
0.3
0.4
0.4
0.7
Total absorbed power for heating kW
0.15
0.23
0.3
0.4
0.4
0.7
1500 - 37
1600 - 47
2000 - 37
2700 - 32
2700 - 32
3200 - 48
MODEL
Air flow - static pressure m3/h - Pa
230.1 - 400.3+N 230.1
230.1
230.1
230.1 - 400.3+N 400.3+N
Refrigerant connection. Liquid line Ø (")
Power supply (50 Hz ~) V
1/2"
3/8"
3/8"
1/2"
1/2"
1/2"
Refrigerant connection. Gas line Ø (")
3/8"
5/8"
3/4"
7/8"
7/8"
7/8"
Dimensions (length x width x height) mm
1175x562x452
1325x600x504
1405x600x504
1455x642x562
1455x642x562
1455x642x562
61
72
81
89
89
96
Net weight kg
701
721
751
801
1001
1201
Nominal cooling capacity kW
17.2
18.5
20.8
21.9
28.4
33.5
Nominal cooling capacity T.R.
4.9
5.3
5.9
6.2
8.1
9.5
Nominal heating capacity kW
18.9
20.4
21.9
24.6
29.8
37.2
Total absorbed power for cooling kW
0.9
0.9
0.9
1.3
1.6
2.7
Total absorbed power for heating kW
0.8
0.9
0.9
1.1
1.3
2.1
4300 - 50
4300 - 50
4300 - 50
4300 - 50
5900 - 50
7550 - 82
MODEL
Air flow - static pressure m3/h - Pa
400.3+N
400.3+N
400.3+N
400.3+N
400.3+N
400.3+N
Refrigerant connection. Liquid line Ø (")
Power supply (50 Hz ~) V
1/2"
1/2"
5/8"
5/8"
5/8"
5/8"
Refrigerant connection. Gas line Ø (")
7/8"
7/8"
7/8"
7/8"
1 1/8"
1 1/8"
Dimensions (length x width x height) mm
1775x752x640
1755x752x640
1755x752x640
1755x752x640
1750x900x662
2300x925x782
136
136
137
137
172
209
Net weight kg
For the dimensions of the refrigeration lines, depending on the route and total distance of the installation, please contact our Sales Department
188
DIRECT EXPANSION SYSTEMS | AIR / AIR ON-OFF
CCHA/FTA
Cooling only
CCHBA/FTBA
Reversible
SPLIT configuration, low profile
centrifugal condenser
FTA/FTBA
CCHA/CCHBA
Advantages
MAIN FEATURES
Maximum versatility for air conditioning via the conduits of
commercial buildings.
Units of the CCHA/FTA and CCHBA/FTBA series are sets
composed of a centrifugal condenser unit and a direct expansion
fancoil evaporator unit.
The reduced height of the internal unit allows quick installation in
false ceilings with the unit suspended or supported.
Cooling capacity between 5.2 and 19.3 kW
Outdoor units with coils pre-treated with blue fins
supplied as standard
Internal 3-speed fan
Maximum connection distance between internal and
external unit 50 metres
Thermostats and controllers provided for units with
electromechanical control system:
- Standard controller:
SUPER
SI 24V
- Optional controller:
DSX@
For the functions, see the "Controls" section on page 216
Air inlet/outlet configuration options
CCHA/CCHBA 201, 251, 351, 371, 501
standard
CCHA/CCHBA 701, 721
189
optional
DIRECT EXPANSION SYSTEMS | AIR / AIR ON-OFF
Options
ENERGY EFFICIENCY
Compressor soft start (depending on model)
Condensation controlled by frequency inverter or variable
voltage controller
AIR QUALITY
G4 gravimetric filter on return
SOUND LEVEL
Double thermal-acoustic insulation
Acoustic insulation on compressor
UNIT INSTALLATION
Magnto-thermal circuit breakers in the electrical board
60Hz power supply and voltages of 230, 208 etc.
Side air intake and air discharge (outdoor unit)
Option to manufacture symmetrical configuration units
(outdoor unit)
Rear connections. (outdoor unit)
Indoor unit and accessories painted with polyester powder
RAL 1013
Kit for bad weather installation
Upgraded motors
Operation for antifreeze electric heater in condensate tray
Flame-proof filter class M0
Hot gas bypass
Hot water heating coils
Auxiliary electric heating coils
Pre-treated anti-corrosion coils
Availability of models with R407C refrigerant to be consulted
Ready for disassembly Only for SPLIT configuration:
- Oil separator
- Service valves
- Quick connection valves with pre-load of refrigerant gas
Discharge and return air plenum
Discharge and return air plenum grille
Plenum with 3 and 5 spigots
Condensate drain pump
MAINTENANCE
Service valves
External pressure tapping points
Dirty filter detector
Filter on condenser
Separate filter
CONTROLS
Pressure switches
Electromechanical control system
Infrared remote controller
ARIA thermostat
pGD thermostat
ETN thermostat
DSX@ thermostat (man. 24 V)
SUPER SI thermostat (man. 24 V)
Alarm signals
Smoke detection
Remote start/stop
Stand-alone electrical board
Option for master/slave operation
Detection pressure switch for resetting from thermostat
Evaporator fan stop during defrost
Unit without thermostat
Wall-mounted room temperature sensor
Return temperature sensor
Temperature sensor in conduit
Operation for redundant machine
Centralised integrated management operation
Operation without neutral
Timer programming function and Modbus connection etc. please
refer to the Thermostats section
Besides these options, please speak to our Sales Department for any other
configuration or function that is not listed as being available.
190
CCHA/FTA Cooling only
CCHBA/FTBA Reversible
TECHNICAL SPECIFICATIONS
201
251
351
371
Nominal cooling capacity kW
5.2
7.4
9.6
10.4
Nominal cooling capacity T.R.
1.5
2.1
2.7
3.0
Nominal heating capacity kW
5.8
7.8
10.2
11.0
Total absorbed power for cooling kW
2.7
3.2
4.24
4.68
Total absorbed power for heating kW
2.5
3.1
3.74
4.18
230.1
230.1 or 400.3+N
230.1-230.3 or 400.3+N
230.1-230.3 or 400.3+N
Air flow - static pressure indoor unit m3/h - Pa
1100 - 44
1150 - 72
1500 - 80
2200 - 96
Air flow - static pressure outdoor unit m3/h - Pa
OUTDOOR MODEL / INDOOR MODEL
Power supply (50 Hz ~) V
2100 - 50
2450 - 50
3180 - 50
3800 - 50
Diameter liq. tube Ø (")
3/8
3/8
3/8
1/2
Diameter gas tube Ø (")
1/2
5/8
3/4
3/4 (int.)- 7/8 (ext.)
1175x619x452
1325x706x504
1405x825x504
1455x843x562
925x660x280
925x660x280
925x660x280
1250x750x315
Total dist. indoor/outdoor unit m
50
50
50
50
Vertical dist. indoor/outdoor unit m
25
25
25
25
106
133
146
172
37
39
44
59
Outdoor unit dimensions mm
(length x width x height)
Indoor unit dimensions mm
(length x width x height)
Net weight outdoor unit kg
Net weight indoor unit kg
401
501
701
721
Nominal cooling capacity kW
11.8
14.5
18.0
19.3
Nominal cooling capacity T.R.
3.4
4.1
5.1
5.5
Nominal heating capacity kW
12.5
15.3
19.8
20.6
Total absorbed power for cooling kW
4.94
6.13
7.9
8.6
Total absorbed power for heating kW
4.44
5.43
6.9
7.9
230.3 or 400.3+N
230.3 or 400.3+N
400.3+N
230.3 or 400.3+N
Air flow - static pressure indoor unit m3/h - Pa
2300 - 80
2500 - 76
3000 - 140
3000 - 140
Air flow - static pressure outdoor unit m3/h - Pa
OUTDOOR MODEL / INDOOR MODEL
Power supply (50 Hz ~) V
3800 - 50
4150 - 50
5600 - 50
5600 - 50
Diameter liq. tube Ø (")
1/2
1/2
1/2
1/2
Diameter gas tube Ø (")
3/4 (int.)- 7/8 (ext.)
7/8
7/8
7/8
Outdoor unit dimensions mm
(length x width x height)
1455x843x562
1455x843x562
1755x1004x640
1755x1004x640
Indoor unit dimensions mm
(length x width x height)
1250x750x315
1250x750x315
1250x805x369
1250x805x369
Total dist. indoor/outdoor unit m
50
50
50
50
Vertical dist. indoor/outdoor unit m
25
25
25
25
172
172
223
223
59
61
71
71
Net weight outdoor unit kg
Net weight indoor unit kg
Voltage indoor unit 230.1 50 Hz ~
For the sizing of the refrigeration lines, depending on the layout and total distance of the installation, please contact our Sales Department
191
DIRECT EXPANSION SYSTEMS | AIR / AIR ON-OFF
ACVA
ECVA/CCVA
ACVBA
ECVBA/CCVBA
Reversible
Reversible
PACKAGED configuration
SPLIT configuration
Cooling only
Cooling only
ECVA/CCVA - ECVBA/CCVBA
ACVA/ACVBA
Advantages
MAIN FEATURES
Cooling capacities between 9.8 and 114.3 kW
Scroll compressors
R410a refrigerant
2 independent refrigerant circuits (models from 1402
to 3502)
Option to operate as a multi split 2x1 group (models
from 1402 to 3002)
Two internal units connected to one external unit
(operation with one or two thermostats)
One internal unit connected to two external units
(operation with a single thermostat)
Refrigerant line distance between the internal and
external unit (split configuration) up to 50 m total
Can be combined with the RCAH range of high energy
efficiency heat recovery exchangers and filtration group
to class F.
Thermostats and controllers included for units with
electromechanical controls:
- Standard controller:
SUPER
SI 24V
Maximum versatility for air conditioning via the conduits of
commercial buildings.
This range of packaged and split units uses a vertical design. It is
suitable for operation connected to a network of air distribution
conduits, in both the internal and external section.
Designed to be installed inside the area to be air conditioned, they
are characterised by offering a wide installation versatility.
- Optional controller:
DSX@
For the functions, see the "Controls" section on page 216
192
Air inlet/outlet configuration options
ACVA/ACVBA
standard
optional
ECVA/CCVA - ECVBA/CCVBA
ECVA-ECVBA 351, 3502
CCVA-CCVBA 351, 3002
CCVA-CCVBA 3502
Options
ENERGY EFFICIENCY
Option for mixing module for free cooling
with three dampers
Thermal or enthalpic control system with PCO controller card
and pGD controller
Compressor soft start (depending on model)
Fan soft start, internal and/or external (depending on model)
Condensation controlled by frequency inverter or variable
voltage controller
Internal radial EC fan (depending on model)
AIR QUALITY
G4 gravimetric filter on return
Opacimetric filter on return class F6 to F9 (can be combined
with a G4 or Fx+Fy)
SOUND LEVEL
Double thermal-acoustic insulation
Acoustic insulation on compressor
UNIT INSTALLATION
Magneto-thermal circuit breakers in the electrical board
60Hz power supply and voltages of 230, 208 etc.
Option to manufacture symmetrical configuration units
Kit for bad weather installation
Upgraded motors
Operation for antifreeze electric heater in condensate tray
Flame-proof filter class M0
Hot gas bypass
Hot water heating coils
Auxiliary electric heating coils
Pre-treated anti-corrosion coils
Availability of models with R407C refrigerant to be consulted
Suitable for disassembly
Only for SPLIT configuration:
- Oil separator
- Service valves
- Quick connection valves
with pre-load of refrigerant gas
Multi split 2x1 operation (1402 to 2402)
193
MAINTENANCE
Service valves
External pressure tapping points
Dirty filter detector
Filter on condenser
Separate filter
CONTROLS
ETN thermostat (mod. 1 circuit)
ARIA thermostat
SUPER SI thermostat (man. 24 V)
pGD thermostat
DSX@ thermostat (man. 24 V)
Alarm signals
Smoke detection
Remote start/stop
Stand-alone electrical board
Option for master/slave operation
Detection pressure switch for resetting from thermostat
Unit without thermostat
Wall-mounted room temperature sensor
Return temperature sensor
Temperature sensor in conduit
Operation for redundant machine
Centralised integrated management operation
Operation without neutral
Timer programming function and Modbus connection etc.
please refer to the Thermostats section.
Besides these options, please speak to our Sales Department for any other
configuration or function that is not listed as being available.
DIRECT EXPANSION SYSTEMS | AIR / AIR ON-OFF
ACVA Cooling only
ACVBA Reversible
TECHNICAL SPECIFICATIONS
351
401
501
701
721
751
Nominal cooling capacity kW
9.8
12.5
14.4
18.9
19.6
22.7
Nominal cooling capacity T.R.
2.8
3.6
4.1
5.4
5.6
6.5
Nominal heating capacity kW
10.4
13.7
15.0
20.0
21.0
23.9
Total absorbed power for cooling kW
4.6
5.6
7.2
8.4
9.3
10.9
Total absorbed power for heating kW
4.2
5.1
6.5
7.9
8.2
10.3
400.3+N
400.3+N
400.3+N
400.3+N
400.3+N
400.3+N
Int. air flow static pressure m3/h - Pa 2315-43
2600-50
3540-60
4720-55
4720-55
5133-53
Ext. air flow static pressure m3/h - Pa 4300-50
3950-50
4900-50
6800-50
6800-50
7400-50
937x750x1604
1087x750x1604 1130x800x1900 1130x800x1900 1130x800x1900
MODEL
Power supply (50 Hz ~) V
Dimensions (length x width x height) mm
937x750x1604
Net weight kg
251
276
290
367
392
423
801
1001
1201
1402
1502
1602
Nominal cooling capacity kW
24.2
30.1
34.9
37.8
43.4
50.2
Nominal cooling capacity T.R.
6.9
8.6
9.9
10.7
12.3
14.3
Nominal heating capacity kW
25.3
31.7
38.2
39.5
44.2
51.9
Total absorbed power for cooling kW
10.9
13.4
14.4
16.2
17.6
20.1
Total absorbed power for heating kW
9.6
12.4
13.2
15.5
16.5
18.0
400.3+N
400.3+N
400.3+N
400.3+N
400.3+N
400.3+N
Int. air flow static pressure m3/h - Pa 5150-83
6200-73
8000-91
8000-130
10000-145
10000-145
Ext. air flow static pressure m3/h - Pa 7714-57
10000-50
12500-50
13600-88
15600-110
16000-110
MODEL
Power supply (50 Hz ~) V
Dimensions (length x width x height) mm
1130x800x1900 1700x870x1900 1700x870x1900 2000x939x1997 2000x939x1997 2000x939x1997
Net weight kg
440
MODEL
Nominal cooling capacity
kW
553
558
2002
2302
2402
63.1
73.6
78.5
Nominal cooling capacity
T.R.
17.9
20.9
22.3
Nominal heating capacity
kW
65.5
81.9
81.9
Total absorbed power for cooling
kW
26.0
28.7
34.3
Total absorbed power for heating
kW
22.8
27.5
29.0
400.3+N
400.3+N
400.3+N
Int. air flow static pressure m3/h - Pa 11000-175
12000-160
12000-160
Ext. air flow static pressure m3/h - Pa 22000-123
23000-142
23000-142
Power supply (50 Hz ~)
Dimensions (length x width x height)
V
mm
Net weight
CCVA Cooling only
kg
730
810
820
2600x980x2174 2600x980x2174 2600x980x2174
1080
CCVBA Reversible
1115
1135
- OUTDOOR UNIT TECHNICAL SPECIFICATIONS
351
401
501
701
721
751
Nominal cooling capacity kW
9.8
12.5
14.4
18.9
19.6
22.7
Nominal cooling capacity T.R.
2.8
3.6
4.1
5.4
5.6
6.5
Nominal heating capacity kW
10.4
13.7
15.0
20.0
21.0
23.9
Total absorbed power for cooling kW
4.0
5.1
6.4
7.3
8.0
9.4
Total absorbed power for heating kW
3.7
4.5
5.5
6.8
7.0
9.0
400.3+N
400.3+N
400.3+N
400.3+N
400.3+N
400.3+N
Refrigerant connection. Liquid line Ø (")
3/8
1/2
1/2
1/2
1/2
5/8
Refrigerant connection. Gas line Ø (")
3/4
3/4
7/8
7/8
7/8
7/8
4300-50
3950-50
4900-50
6800-50
6800-50
7400-50
937x750x1022
937x750x1022
1087x750x1022 1130x800x1250 1130x800x1250 1130x800x1250
172
189
200
253
272
297
801
1001
1201
1402
1502
1602
Nominal cooling capacity kW
24.2
30.1
34.9
37.8
43.4
50.2
Nominal cooling capacity T.R.
6.9
8.6
9.9
10.7
12.3
14.3
Nominal heating capacity kW
25.3
31.7
38.2
39.5
44.2
51.9
Total absorbed power for cooling kW
9.4
12.0
12.5
13.9
15.2
14.4
Total absorbed power for heating kW
8.3
11.0
11.5
14.9
14.6
16.5
400.3+N
400.3+N
400.3+N
400.3+N
400.3+N
400.3+N
Refrigerant connection. Liquid line Ø (")
5/8
5/8
5/8
1/2
5/8
5/8
Refrigerant connection. Gas line Ø (")
7/8
1 1/8
1 1/8
7/8
7/8
1 1/8
7714-57
10000-50
12500-50
13600-88
15600-110
16000-110
MODEL
Power supply (50 Hz ~) V
Air flow - static pressure m3/h - Pa
Dimensions (length x width x height) mm
Net weight kg
MODEL
Power supply (50 Hz ~) V
Air flow - static pressure m3/h - Pa
Dimensions (length x width x height) mm
Net weight kg
1130x800x1250
1700x870x1250 1700x870x1250 2000x939x1250 2000x939x1250
2000x939x1250
304
373
548
397
194
477
538
CCVA Cooling only
CCVBA Reversible
MODEL
Nominal cooling capacity kW
- OUTDOOR UNIT TECHNICAL SPECIFICATIONS
2002
2302
2402
3002
3502
63.1
73.6
78.5
86.6
114.3
Nominal cooling capacity T.R.
17.9
20.9
22.3
24.6
32.5
Nominal heating capacity kW
65.5
81.9
81.9
88.8
119.6
Total absorbed power for cooling kW
21.6
23.4
24.2
31.1
39.8
Total absorbed power for heating kW
21.7
25.7
25.5
27.4
32.3
400.3+N
400.3+N
400.3+N
400.3+N
400.3+N
5/8
5/8
5/8
5/8
7/8
1 1/8
1 1/8
1 1/8
1 3/8
1 5/8
Power supply (50 Hz ~) V
Refrigerant connection. Liquid line Ø (")
Refrigerant connection. Gas line Ø (")
Air flow - static pressure m3/h - Pa 22000-123
Dimensions (length x width x height) mm
Net weight kg
ECVA Cooling only
23000-142
23000-142
27000-140
32000-160
2600x980x1422
2600x980x1422
2600x980x1422
2800x1050x1722
2800x1050x1722
747
782
802
978
1058
ECVBA Reversible
- INDOOR UNIT TECHNICAL SPECIFICATIONS
351
401
501
701
721
751
Nominal cooling capacity kW
9.8
12.5
14.4
18.9
19.6
22.7
Nominal cooling capacity T.R.
2.8
3.6
4.1
5.4
5.6
6.5
Nominal heating capacity kW
10.4
13.7
15.0
20.0
21.0
23.9
Total absorbed power for cooling kW
0.3
0.4
0.9
1.0
0.9
1.1
Total absorbed power for heating kW
0.3
0.4
0.8
0.9
0.9
1.0
400.3+N
400.3+N
400.3+N
400.3+N
400.3+N
400.3+N
Refrigerant connection. Liquid line Ø (")
3/8
1/2
1/2
1/2
1/2
5/8
Refrigerant connection. Gas line Ø (")
3/4
3/4
7/8
7/8
7/8
7/8
2600-50
3540-60
4720-55
4720-55
5133-53
937x750x582
937x750x582
1087x750x582
1130x800x650
1130x800x650
1130x800x650
92
95
99
126
126
136
801
1001
1201
1402
1502
1602
Nominal cooling capacity kW
24.2
30.1
34.9
37.8
43.4
50.2
Nominal cooling capacity T.R.
6.9
8.6
9.9
10.7
12.3
14.3
Nominal heating capacity kW
25.3
31.7
38.2
39.5
44.2
51.9
Total absorbed power for cooling kW
1.0
1.0
1.3
2.2
2.2
2.3
Total absorbed power for heating kW
1.0
0.9
1.2
1.7
1.7
1.9
400.3+N
400.3+N
400.3+N
400.3+N
400.3+N
400.3+N
Refrigerant connection. Liquid line Ø (")
5/8
5/8
5/8
1/2
5/8
5/8
Refrigerant connection. Gas line Ø (")
7/8
1 1/8
1 1/8
7/8
7/8
1 1/8
6277-73
8000-91
8000-130
10000-145
10000-145
1130x800x650
1700x870x650
1700x870x650
2000x939x747
2000x939x747
2000x939x747
136
197
199
253
272
272
2002
2302
2402
3002
3502
Nominal cooling capacity kW
63.1
73.6
78.5
86.6
114.3
Nominal cooling capacity T.R.
17.9
20.9
22.3
24.6
32.5
Nominal heating capacity kW
65.5
81.9
81.9
88.8
119.6
Total absorbed power for cooling kW
3.1
3.3
3.6
3.9
3.9
Total absorbed power for heating kW
2.7
2.4
2.9
2.3
2.3
400.3+N
400.3+N
400.3+N
400.3+N
400.3+N
5/8
5/8
5/8
5/8
7/8
1 1/8
1 1/8
1 1/8
1 3/8
1 5/8
12000-160
12000-160
14000-200
18000-250
MODEL
Power supply (50 Hz ~) V
Air flow - static pressure m3/h - Pa 2315-43
Dimensions (length x width x height) mm
Net weight kg
MODEL
Power supply (50 Hz ~) V
Air flow - static pressure m3/h - Pa 5125-83
Dimensions (length x width x height) mm
Net weight kg
MODEL
Power supply (50 Hz ~) V
Refrigerant connection. Liquid line Ø (")
Refrigerant connection. Gas line Ø (")
Air flow - static pressure m3/h - Pa 11000-175
Dimensions (length x width x height) mm
Net weight kg
2600x980x752
2600x980x752
2600x980x752
2800x1050x915 2800x1050x915
333
333
333
418
524
For the sizing of the refrigeration lines, depending on the layout and total distance of the installation, please contact our Sales Department
195
DIRECT EXPANSION SYSTEMS | AIR / AIR ON-OFF
UXCA/ECVA
Cooling only
UXCBA/ECVBA
Reversible
ECVA/ECVBA
UXCA/UXCBA
Advantages
MAIN FEATURES
Cooling capacities between 23.6 and 139.7 kW
Scroll compressors
2 cooling circuits (models 1602 to 4502)
Can be combined with the RCAH range of high energy
efficiency heat recovery exchangers and filtration group
to class F.
Maximum versatility for air conditioning via the conduits of
commercial buildings.
The units that make up the UXCA/ECVA - UXCBA/ECVBA series are
ductable units, specially designed to be installed on roofs, terraces
or any other outdoor space.
Their design makes it possible to cover large distances in the
installation between the indoor and outdoor unit.
3 versions available:
- Standard (STD)
- Low sound level (SIL)
- High ambient temperatures (HTA)
Refrigerant distance between the internal and external
unit up to 50 m in total
Option to operate as a multi split 2x1 group (models
1602 to 3002)
Two internal units connected to one external unit
(operation with one or two thermostats)
One internal unit connected to two external units
(operation with a single thermostat)
Thermostats and controllers included for units with
electromechanical controls:
- Standard controller:
SUPER
SI 24V
- Optional controller:
DSX@
For the functions, see the "Controls" section on page 216.
Besides these options, please speak to our Sales Department for any
other configuration or function that is not listed as being available.
196
Air inlet/outlet configuration options
UXCA Cooling only
UXCBA Reversible
standard
- OUTDOOR UNIT TECHNICAL SPECIFICATIONS
801
MODEL
optional
1001
1201
1501
1602
Nominal cooling capacity kW
23.6
29.7
34.5
40.3
49.6
Nominal cooling capacity T.R.
6.7
8.4
9.8
11.5
14.1
Nominal heating capacity kW
24.9
30.6
39.6
41.6
52.4
Total absorbed power for cooling kW
10.1
12.0
14.0
15.5
19.5
Total absorbed power for heating kW
Power supply (50 Hz ~) V
Dimensions (length x width x height) mm
Net weight kg
MODEL
Nominal cooling capacity kW
9.9
11.1
14.2
14.7
18.3
400.3+N
400.3+N
400.3+N
400.3+N
400.3+N
1430x1008x325
1430x1008x1325
1400x1320x1500
1400x1320x1500
2035x1030x1325
251
316
382
392
495
2002
2402
3002
4002
4502
65.3
73.1
89.4
122.9
139.7
Nominal cooling capacity T.R.
18.6
20.8
25.4
34.9
39.7
Nominal heating capacity kW
67.6
78.3
86.0
124.8
144.2
Total absorbed power for cooling kW
23.0
24.4
29.6
40.7
46.3
Total absorbed power for heating kW
21.3
24.7
30.7
38.4
42.3
400.3+N
400.3+N
400.3+N
400.3+N
400.3+N
2035x1030x1325
2280x1320x1500
2720x1320x1500
2200x2250x1725
2200x2250x1725
545
567
894
950
992
Power supply (50 Hz ~) V
Dimensions (length x width x height) mm
Net weight kg
ECVA Cooling only
ECVBA Reversible
- INDOOR UNIT TECHNICAL SPECIFICATIONS
801
1001
1201
1501
1602
Nominal cooling capacity kW
23.6
29.7
34.5
40.3
49.6
Nominal cooling capacity T.R.
6.7
8.4
9.8
11.5
14.1
Nominal heating capacity kW
24.9
30.6
39.6
41.6
52.4
Total absorbed power for cooling kW
1.5
1.4
1.9
2.6
2.4
Total absorbed power for heating kW
1.5
1.3
1.7
2.4
2.3
400.3+N
400.3+N
400.3+N
400.3+N
400.3+N
Refrigerant connection. Liquid line Ø (")
5/8
5/8
5/8
5/8
5/8
Refrigerant connection. Gas line Ø (")
7/8
1 1/8
1 1/8
1 1/8
1 1/8
6200-73
8000-91
9000-130
10000-145
1130x800x650
1700x870x650
1700x870x650
2000x939x747
2000x939x747
136
197
199
272
272
MODEL
Power supply (50 Hz ~) V
Air flow - static pressure m3/h - Pa 5150-83
Dimensions (length x width x height) mm
Net weight kg
2002
2402
3002
4002
4502
Nominal cooling capacity kW
65.3
73.1
89.4
122.9
139.7
Nominal cooling capacity T.R.
18.6
20.8
25.4
34.9
39.7
Nominal heating capacity kW
67.6
78.3
86
124.8
144.2
Total absorbed power for cooling kW
2.6
2.6
3.3
5.6
6.2
Total absorbed power for heating kW
2.5
2.5
3.6
5.5
5.4
400.3+N
400.3+N
400.3+N
400.3+N
400.3+N
5/8
5/8
5/8
7/8
7/8
1 1/8
1 1/8
1 3/8
1 5/8
1 5/8
12000-160
14000-200
20500-210
22000-200
2600x980x752
2600x980x752
2800x1050x915
2900x1200x1115
2900x1200x1115
333
333
418
550
570
MODEL
Power supply (50 Hz ~) V
Refrigerant connection. Liquid line Ø (")
Refrigerant connection. Gas line Ø (")
Air flow - static pressure m3/h - Pa 11000-175
Dimensions (length x width x height) mm
Net weight kg
For the sizing of the refrigeration lines, depending on the layout and total distance of the installation, please contact our Sales Department
197
DIRECTION EXPANSION SYSTEMS | DUCTABLE VERTICAL INDOOR UNITS
CLVA
Cooling only
CLVBA
Reversible
MAIN FEATURES
Air flows up to 10,200 m3/h
Various installation options
Can be connected to any Wesper condensing unit
Thermostats and controllers included for units with
electromechanical controls:
- Standard controller:
SUPER
SI 24V
- Optional controller:
DSX@
For the functions, see the "Controls" section on page 216
Advantages
Maximum versatility for air conditioning via the conduits of
commercial buildings.
The units of the CLVA/CLVBA series are units with direct expansion
evaporators suitable to operate connected to a system of air
distribution conduits. The units are designed to work with any
outdoor Wesper units with equivalent cooling capacities.
Free discharge can be used on all models via an optional air
plenum that ends in an anodised aluminium grille for direct air
discharge.
Options
ENERGY EFFICIENCY
Option for mixing module for free cooling
with three dampers
Thermal or enthalpic control system with PCO controller card
and pGD controller
Internal EC radial fan (depending on model)
Fan soft start (depending on model)
AIR QUALITY
G4 gravimetric filter on return
Opacimetric filter on return class F6 to F9 (can be combined
with a G4 or Fx+Fy)
SOUND LEVEL
Double thermal-acoustic insulation
UNIT INSTALLATION
Front air discharge
60Hz power supply and voltages of 230, 208 etc.
Kit for bad weather installation
Upgraded motors
Flame-proof filter class M0
Hot gas bypass
Hot water heating coils (cooling only)
Auxiliary electric heating coils
Return with circular connection
Opposite side connectors
Discharge plenum
Air intake grille
Pre-treated anti-corrosion coils
Availability of models with R407C refrigerant to be consulted
Suitable for disassembly
Base frame
MAINTENANCE
Service valves
Dirty filter detector
Separate filter
Besides these options, please speak to our Sales Department for any other
configuration or function that is not listed as being available.
198
Air inlet/outlet configuration options
CLVA Cooling only
CLVBA Reversible
standard
optional
TECHNICAL SPECIFICATIONS
251
351
401
501
701
Nominal cooling capacity kW
7.4
9.8
12.0
14.4
18.2
Nominal cooling capacity T.R.
2.1
2.8
3.4
4.1
5.2
Nominal heating capacity kW
7.4
10.4
12.7
15.5
19.3
Total absorbed power kW
0.3
0.4
0.6
0.6
0.9
230.1
230.1
230 or 400.3+N
230 or 400.3+N
230 or 400.3+N
2500-68
3000-56
3400-100
4200-115
1/2
MODEL
Power supply (50 Hz ~) V
Air flow - static pressure m3/h - Pa 1900-38
Diameter liquid tube Ø (")
3/8
3/8
1/2
1/2
Diameter gas tube Ø (")
5/8
3/4
3/4
7/8
7/8
697x500x1000
697x500x1000
697x500x1000
757x500x1100
1152x600x1200
45
69
73
94
118
721
751
801
1001
1201
Nominal cooling capacity kW
22.1
22.1
23.2
29.7
35.0
Nominal cooling capacity T.R.
6.3
6.3
6.6
8.4
10.0
Nominal heating capacity kW
23.5
23.5
24.4
31.7
37.0
0.9
1.3
1.3
1.3
1.8
230 or 400.3+N
230 or 400.3+N
230 or 400.3+N
230 or 400.3+N
230 or 400.3+N
4800-120
5200-84
7200-78
8000-85
5/8
Dimensions (length x width x height) mm
Net weight kg
MODEL
Total absorbed power kW
Power supply (50 Hz ~) V
Air flow static pressure m3/h - Pa 4400-109
Diameter liquid tube Ø (")
1/2
5/8
5/8
5/8
Diameter gas tube Ø (")
7/8
1 1/8
1 1/8
1 1/8
1 1/8
1152x600x1200
1152x600x1200
1152x600x1200
1700x600x1300
1700x600x1300
175
175
Dimensions (length x width x height) mm
118
119
125
1402
1502
1602
Nominal cooling capacity kW
36.4
44.2
45.4
Nominal cooling capacity T.R.
10.3
12.6
12.9
Nominal heating capacity kW
38.6
46.6
48.8
1.8
2.6
2.6
230 or 400.3+N
230 or 400.3+N
230 or 400.3+N
9600-129
10200-123
2x5/8
Net weight kg
MODEL
Total absorbed power kW
Power supply (50 Hz ~) V
Air flow static pressure m3/h - Pa 8400-72
Diameter liquid tube Ø (")
2x1/2
2x5/8
Diameter gas tube Ø (")
2x7/8
2x7/8
2x1 1/8
1800x675x1400
1800x675x1400
1800x675x1400
187
187
197
Dimensions (length x width x height) mm
Net weight kg
For the sizing of the refrigeration lines, depending on the layout and total distance of the installation, please contact our Sales Department
199
DIRECT EXPANSION SYSTEMS SYSTEMS | SPLIT A/C, CONDENSER WITH AXIAL FANS
DXCZ
FTZ
DXCBZ
FTBZ
Reversible
Reversible
Cooling only
Cooling only
SPLIT configuration
FTZ/FTBZ
DXCZ/DXCBZ
Advantages
MAIN FEATURES
Cooling capacities between
4.7 and 19 kW
Rotary compressors (models 171-351) and Scroll
(371-721)
Outdoor units with coils pretreated with blue fins
supplied as standard
Maximum versatility for air conditioning via the conduits of
commercial buildings.
Units of the DXCZ/FTZ and DXCBZ/FTBZ series are sets
composed of an axial condenser unit and a direct expansion
fancoil evaporator unit. The reduced height of the internal unit
allows quick installation in false ceilings with the unit suspended or
supported.
Internal 3-speed fan
Maximum connection distance between internal and
external unit 50 metres
Quick connection valves with refrigerant gas precharge for 5 metres
Thermostats and controllers included for units with
electromechanical controls:
- Standard controller:
SUPER
SI 24V
- Optional controller:
DSX@
For the functions, see the "Controls" section on page 216
200
Options
MAINTENANCE
Service valves
External pressure tapping points
Dirty filter detector
Separate filter
ENERGY EFFICIENCY
Condensation controlled by frequency inverter or variable
voltage controller
AIR QUALITY
G4 gravimetric filter on return
CONTROLS
Pressure switches
Option for tri-phase evaporator
ARIA thermostat
pGD thermostat
Infrared remote controller
SUPER SI thermostat (man 24 V)
DSX@ thermostat (man 24 V)
Alarm signals
Smoke detection
Remote start/stop
Stand-alone electrical board
Option for master/slave operation
Detection pressure switch for resetting
from thermostat
Unit without thermostat
Wall-mounted room temperature sensor
Return temperature sensor
Temperature sensor in conduit
Operation for redundant machine
Centralised integrated management operation
Operation without neutral
Timer programming function and Modbus connection etc.
please refer to the Thermostats section
SOUND LEVEL
Double thermal-acoustic insulation
Acoustic insulation on compressor
UNIT INSTALLATION
Indoor unit and accessories painted with polyester powder
RAL 1013
Rear connections, outdoor unit
Magneto-thermal circuit breakers in the electrical board
60Hz power supply and voltages of 230, 208 etc.
(depending on model)
Option to manufacture symmetrical configuration units
Operation for antifreeze electric heater in condensate tray
Flame-proof filter class M0
Thermal-acoustic insulation class M0
Hot gas bypass
Discharge and return air plenum
Discharge and return air plenum grille
Plenum with 3 and 5 spigots
Condensate drain pump
Hot water heating coils
Auxiliary electric heating coils
Pre-treated anti-corrosion coils
Anticorrosion treatment on piping with galval coating
Suitable for disassembly
- Oil separator
- Without refrigerant or flare valves
DXCZ/FTZ Cooling only
Besides these options, please speak to our Sales Department for any other
configuration or function that is not listed as being available.
TECHNICAL SPECIFICATIONS
171
201
221
251
271
351
Nominal cooling capacity kW
4.7
5.3
6.3
7.0
7.7
9.8
Nominal cooling capacity T.R.
1.3
1.5
1.8
2.0
2.2
2.8
Total absorbed power kW
1.9
2.1
2.7
3.0
3.0
3.9
230.1
230.1
230.1
230.1
230.1 or 400.3 230.1 or 400.3
OUTDOOR MODEL / INDOOR MODEL
Power supply (50 Hz ~) V
Air flow - static pressure m3/h - Pa 700 - 32
1100 - 44
1100 - 44
1150 - 72
1400 - 96
1500 - 80
Diameter liq. tube Ø (")
3/8
3/8
3/8
3/8
3/8
3/8
Diameter gas tube Ø (")
1/2
1/2
1/2
5/8
3/4
3/4
Outdoor unit dimensions (length x width x height) mm
870x394x630
870x394x630
870x394x630
870x394x630
920x394x730
920x394x730
Indoor unit dimensions (length x width x height) mm
726x555x218
925x660x280
925x660x280
925x660x280
925x660x280
925x660x280
Total dist. indoor/outdoor unit m
50
50
50
50
50
50
Vertical dist. indoor/outdoor unit (1) m
25
25
25
25
25
25
Net weight outdoor unit Kg
50
53
53
54
58
63
Net weight indoor unit Kg
31
37
37
39
43
44
➜
1) For greater distances we recommend installing an oil separator
Voltage indoor unit 230.1 50 Hz ~
201
DIRECT EXPANSION SYSTEMS | SPLIT A/C, CONDENSER WITH AXIAL FANS
DXCZ/FTZ Cooling only
TECHNICAL SPECIFICATIONS
371
401
451
501
701
Nominal cooling capacity kW
11.0
11.8
13.5
14.8
17.2
19.0
Nominal cooling capacity T.R.
3.1
3.4
3.8
4.2
4.9
5.4
OUTDOOR MODEL / INDOOR MODEL
Total absorbed power kW
Power supply (50 Hz ~) V
721
4.3
4.6
5.4
5.7
7.3
7.8
400.3
400.3
400.3
400.3
400.3
400.3
Air flow - static pressure m3/h - Pa 2200 - 96
2300 - 80
2400 - 94
2500 - 76
3000 - 140
3000 - 140
Diameter liq. tube Ø (")
1/2
1/2
1/2
1/2
1/2
1/2
Diameter gas tube Ø (")
3/4
3/4
7/8
7/8
7/8
7/8
Outdoor unit dimensions (length x width x height) mm
950x374x1143
950x374x1143
950x374x1143
950x374x1143
950x374x1143
950x374x1143
Indoor unit dimensions (length x width x height) mm
1250x750x315
1250x750x315
1250x750x315
1250x750x315
1250x805x369
1250x805x369
Total dist. indoor/outdoor unit (1) m
50
50
50
50
50
50
Vertical dist. indoor/outdoor unit (1) m
25
25
25
25
25
25
Net weight outdoor unit Kg
82
82
101
101
115
120
Net weight indoor unit Kg
59
59
61
61
71
71
351
1) For greater distances we recommend installing an oil separator
Voltage indoor unit 230.1 50 Hz ~
DXCBZ/FTBZ Reversible
TECHNICAL SPECIFICATIONS
171
201
221
251
271
Nominal cooling capacity kW
4.7
5.3
6.3
7.0
7.7
9.8
Nominal cooling capacity T.R.
1.3
1.5
1.8
2.0
2.2
2.8
OUTDOOR MODEL / INDOOR MODEL
Nominal heating capacity kW
4.8
5.8
6.5
7.8
8.3
10.4
Total absorbed power for cooling kW
1.9
2.1
2.7
3.0
3.0
3.9
Total absorbed power for heating kW
1.9
2.0
2.3
2.6
2.6
3.7
230.1
230.1 or
400.3+N
230.1 or
400.3+N
Power supply (50 Hz ~) V
230.1
Air flow - static pressure m3/h - Pa 700 - 32
230.1
230.1
1100 - 44
1100 - 44
1150 - 72
1400 - 96
1500 - 80
Diameter liq. tube Ø (")
3/8
3/8
3/8
3/8
3/8
3/8
Diameter gas tube Ø (")
1/2
1/2
1/2
5/8
3/4
3/4
Outdoor unit dimensions (length x width x height) mm
870x394x630
870x394x630
870x394x630
870x394x630
920x394x730
920x394x730
Indoor unit dimensions (length x width x height) mm
726x555x218
925x660x280
925x660x280
925x660x280
925x660x280
925x660x280
Total dist. indoor/outdoor unit (1) m
50
50
50
50
50
50
Vertical dist. indoor/outdoor unit (1) m
25
25
25
25
25
25
Net weight outdoor unit Kg
53
56
56
58
62
68
Net weight indoor unit Kg
31
37
37
39
43
44
371
401
451
501
701
721
OUTDOOR MODEL / INDOOR MODEL
Nominal cooling capacity kW
11.0
11.8
13.5
14.8
16.8
18.6
Nominal cooling capacity T.R.
3.1
3.4
3.8
4.2
4.8
5.3
Nominal heating capacity kW
12.0
12.8
14.0
15.3
19.8
20.7
Total absorbed power for cooling kW
4.3
4.6
5.4
5.7
7.3
7.8
Total absorbed power for heating kW
3.7
4.1
4.9
5.0
6.7
7.5
400.3+N
400.3+N
400.3+N
400.3+N
400.3+N
400.3+N
Power supply (50 Hz ~) V
Air flow - static pressure m3/h - Pa 2200 - 96
2300 - 80
2400 - 94
2500 - 76
3000 - 140
3000 - 140
Diameter liq. tube Ø (")
1/2
1/2
1/2
1/2
1/2
1/2
Diameter gas tube Ø (")
3/4
3/4
7/8
7/8
7/8
7/8
Outdoor unit dimensions (length x width x height) mm
950x374x1143
950x374x1143
950x374x1143
950x374x1143
950x374x1143
1035x424x1335
Indoor unit dimensions (length x width x height) mm
1250x750x315
1250x750x315
1250x750x315
1250x750x315
1250x805x369
1250x805x369
Total dist. indoor/outdoor unit m
50
50
50
50
50
50
Vertical dist. indoor/outdoor unit (1) m
25
25
25
25
25
25
Net weight outdoor unit Kg
89
89
109
109
130
135
Net weight indoor unit Kg
59
59
61
61
71
71
(1) For distances greater than 25 m we recommend installing an oil separator
Voltage indoor unit 230.1 50 Hz ~
202
DIRECT EXPANSION SYSTEMS | SPLIT A/C, CONDENSER WITH AXIAL FANS
AXCZ "Dual"
FTZ
AXCBZ "Dual"
FTBZ
Reversible
Reversible
Cooling only
Cooling only
FTZ/FTBZ
AXCZ/AXCBZ "Dual"
Advantages
MAIN FEATURES
Maximum versatility for air conditioning via the conduits of
commercial buildings.
The units of the AXCZ/FTZ and AXCBZ/FTBZ DUAL series are groups
consisting of a dual circuit axial condenser, usually non-identical, and
two direct expansion fancoil evaporator units. The reduced height of
the internal unit allows quick installation in false ceilings with the unit
suspended or supported.
Cooling capacities between 10.8 and 15.8 kW
Outdoor units with coils pretreated with blue fins
supplied as standard
Internal 3-speed fan
Maximum connection distance between internal and
external unit 50 metres
Thermostats and controllers included for units with
electromechanical controls:
- Standard controller:
SUPER
SI 24V
- Optional controller:
DSX@
For the functions, see the "Controls" section on page 216
AXCZ "Dual"/FTZ Cooling only
TECHNICAL SPECIFICATIONS
OUTDOOR MODEL
AXCZ 402
AXCZ 442
AXCZ 452
AXCZ 472
AXCZ 502
AXCZ 542
INDOOR MODEL
FTZ 201+201
FTZ 221+221
FTZ 201+251
FTZ 221+251
FTZ 251+251
FTZ 271+271
Nominal cooling capacity kW
5.4 + 5.4
6.0 + 6.0
5.4 + 7.4
6.0 + 7.4
7.4 + 7.4
7.9 + 7.9
Nominal cooling capacity T.R.
1.5 + 1.5
1.7 + 1.7
1.5 + 2.1
1.7 + 2.1
2.1 + 2.1
2.2 + 2.2
4.2
4.4
4.7
4.8
5.14 - 5.06
5.38 - 5.46
230.1 or
400.3+N
Total absorbed power kW
Power supply (50 Hz ~) V
230.1
Air flow m3/h -m3/h 1100 - 1100
230.1
230.1
230.1
230.1 or
400.3+N
1100 - 1100
1100 - 1150
1100 - 1150
1150 - 1150
1400 - 1400
44
44
44 - 72
44 - 72
72 - 72
96 - 96
Diameter liq. tube Ø (")
3/8 - 3/8
3/8 - 3/8
3/8 - 3/8
3/8 - 3/8
3/8 - 3/8
3/8 - 3/8
Diameter gas tube Ø (")
Outdoor unit dimensions
mm
(length x width x height)
1/2 - 1/2
1/2 - 1/2
1/2 - 5/8
1/2 - 5/8
5/8 - 5/8
3/4 - 3/4
950x407x1349
950x407x1349
950x407x1349
950x407x1349
950x407x1349
950x407x1349
See models
FTBZ
50
See models
FTBZ
50
See models
FTBZ
50
See models
FTBZ
50
See models
FTBZ
50
See models
FTBZ
50
25
25
25
25
25
25
131
135
138
139
141
176
37 + 37
37 + 37
37 + 39
37 + 39
39 + 39
43 + 43
Static pressure Pa
Indoor unit dimensions mm
(length x width x height)
Total dist. indoor/outdoor unit m
Vertical dist. indoor/outdoor unit m
Net weight outdoor unit Kg
Net weight indoor unit Kg
203
DIRECT EXPANSION SYSTEMS | SPLIT A/C, CONDENSER WITH AXIAL FANS
AXCBZ "Dual"/FTBZ Reversible
TECHNICAL SPECIFICATIONS
AXCBZ 402
OUTDOOR MODEL
INDOOR MODEL
Nominal cooling capacity kW
AXCBZ 442
AXCBZ 452
AXCBZ 472
AXCBZ 502
AXCBZ 542
FTBZ 201+201
FTBZ 221+221
FTBZ 201+251
FTBZ 221+251
FTBZ 251+251
FTBZ 271+271
5.2 + 5.2
6.0 + 6.0
5.2 + 7.0
6.0 + 7.0
7.0 + 7.0
7.5 + 7.5
Nominal cooling capacity T.R.
1.5 + 1.5
1.7 + 1.7
1.5 + 2.0
1.7 + 2.0
2.0 + 2.0
2.1 + 2.1
Nominal heating capacity kW
6.2 + 6.2
6.6 + 6.6
6.2 + 8.1
6.6 + 8.1
8.1 + 8.1
8.3 + 8.3
Total absorbed power for cooling kW
4.2
4.4
4.7
4.8
5.14 - 5.06
5.38 - 5.46
Total absorbed power for heating kW
3.6
3.7
4.0
4.0
4.40 - 4.32
4.60 - 4.64
230.1
230.1
230.1
230.1
230.1 - 400.3+N 230.1 - 400.3+N
Power supply (50 Hz ~) V
Air flow m3/h-m3/h 1100 - 1100
Static pressure Pa
44
1100 - 1100
1100 - 1150
1100 - 1150
1150 - 1150
1400 - 1400
44
44 - 72
44 - 72
72 - 72
96 - 96
Diameter liq. tube Ø (")
3/8 - 3/8
3/8 - 3/8
3/8 - 3/8
3/8 - 3/8
3/8 - 3/8
3/8 - 3/8
Diameter gas tube Ø (")
Outdoor unit dimensions mm
(length x width x height)
1/2 - 1/2
1/2 - 1/2
1/2 - 5/8
1/2 - 5/8
5/8 - 5/8
3/4 - 3/4
950x407x1349
950x407x1349
950x407x1349
950x407x1349
950x407x1349
950x407x1349
See models
FTBZ
50
See models
FTBZ
50
See models
FTBZ
50
See models
FTBZ
50
See models
FTBZ
50
See models
FTBZ
50
Indoor unit dimensions mm
(length x width x height)
Total dist. indoor/outdoor unit m
Vertical dist. indoor/outdoor unit m
Net weight outdoor unit Kg
Net weight indoor unit Kg
25
25
25
25
25
25
137
141
143
145
148
182
37 + 37
37 + 37
37 + 39
37 + 39
39 + 39
43 + 43
Voltage indoor unit 230.1 50 Hz ~
Options
ENERGY EFFICIENCY
Compressor soft start (depending on model)
Condensation controlled by frequency inverter or variable
voltage controller
AIR QUALITY
G4 gravimetric filter on return
SOUND LEVEL
Double thermal-acoustic insulation
Acoustic insulation on compressor
UNIT INSTALLATION
Indoor unit and accessories painted with polyester powder
RAL 1013
Rear connections, outdoor unit
Magneto-thermal circuit breakers in the electrical board
60Hz power supply and voltages of 230, 208 etc. (depending
on model)
Operation for antifreeze electric heater in condensate tray
Flame-proof filter class M0
Thermal-acoustic insulation class M0
Hot gas bypass
Hot water heating coils
Auxiliary electric heating coils
Pre-treated anti-corrosion coils
Anticorrosion treatment on piping with galval coating
Without refrigerant or flare valves
Discharge and return air plenum
Discharge and return air plenum grille
Plenum with 3 and 5 spigots
Condensate drain pump
CONTROLS
Pressure switches
Automatic reset of the high pressure switch
Option for tri-phase evaporator
ETN thermostat
ARIA thermostat
pGD thermostat
Infrared remote controller
SUPER SI thermostat (man 24 V)
DSX@ thermostat (man 24 V)
Alarm signals
Smoke detection
Remote start/stop
Stand-alone electrical board
Option for master/slave operation
High-pressure switch for resetting from thermostat
Unit without thermostat
Wall-mounted room temperature sensor
Return temperature sensor
Temperature sensor in conduit
Operation for redundant machine
Centralised integrated management operation
Operation without neutral
Timer programming function and Modbus connection etc.
please refer to the Thermostats section
Besides these options, please speak to our Sales Department for any other
configuration or function that is not listed as being available.
MAINTENANCE
Service valves
External pressure tapping points
Dirty filter detector
Separate filter
204
ROOFTOP
205
ROOFTOP | STANDARD COMPACT. AXIAL FANS
RXCZ
Cooling only
RXCBZ
Reversible
MAIN FEATURES
Cooling capacity from 29 to 137 kW
Alternative hermetic compressors or Scroll
compressors depending on model
Maximum capacity reduction up to 2 stages
depending on model
Thermostats and controllers included for standard
units with electromechanical controls:
- Standard controller:
ARIA
Advantages
High flow solutions for rooftops, versatile and adaptable to every
project.
The units of the RXCZ-RXCBZ series are rooftop type compact
packaged units, especially designed for installation on terraces, roofs
or any other outdoor space, with air distribution via conduits.
For the functions, see the "Controls" section on page 216
Options
ENERGY EFFICIENCY
Option for mixing module for free cooling with two and three
dampers
Thermal or enthalpic control system with PCO controller card
and pGD controller
Condensation controlled by variable voltage controller
AIR QUALITY
G4 gravimetric filter on return
Fresh air inlet damper
SOUND LEVEL
Double thermal-acoustic insulation
Acoustic insulation on compressor
UNIT INSTALLATION
Magneto-thermal circuit breakers in the electrical board
60 Hz power supply and voltages of 230, 208 etc.
Upgraded motors
Operation for antifreeze electric heater in condensate tray
Lateral indoor air discharge
Upper indoor air discharge
Lateral indoor air return
Inverse lateral indoor air return
Flame-proof filter class M0
Hot gas bypass
Condensation controlled by double speed
Condensation control
Hot water heating coils
Auxiliary electric heating coils
Pre-treated anti-corrosion coils
Mounting base
Internal droplet separator
MAINTENANCE
Service valves
External manometers for reading pressure
External pressure tapping points
Dirty filter detector
CONTROLS
pGD thermostat
Alarm signals
Smoke detection
Option for master/slave operation
Unit without thermostat
Wall-mounted or room temperature sensor
Return temperature sensor (ARIA)
Wall-mounted air quality sensor
Operation without neutral
For the functions,
please refer to the
"Control" section
on page 216
Besides these options, please speak to our Sales Department for any other
configuration or function that is not listed as being available.
206
Air inlet/outlet configuration options
RXCZ Cooling only
standard
optional
TECHNICAL SPECIFICATIONS
MODEL
1001
1201
1501
Nominal cooling capacity
kW
29.0
35.0
43.0
Nominal cooling capacity
T.R.
8.3
9.9
12.2
Nominal heating capacity
kW
-
-
-
Power supply (50 Hz ~)
Air flow - static pressure
Dimensions (length x width x height)
Net weight
RXCBZ Reversible
V
400.3
400.3
400.3
m3/h - Pa
7000 - 140
8000 - 218
9000 - 205
mm
2686x1707x1460
2686x1707x1530
2686x1707x1530
Kg
730
780
820
TECHNICAL SPECIFICATIONS
MODEL
1001
1201
1501
Nominal cooling capacity
kW
28.0
35.0
42.0
Nominal cooling capacity
T.R.
8.0
9.9
11.9
Nominal heating capacity
kW
30.0
36.0
44.0
Power supply (50 Hz ~)
Air flow - static pressure
Dimensions (length x width x height)
Net weight
V
230.3 / 400.3
230.3 / 400.3
230.3 / 400.3
m3/h - Pa
7000 - 140
8000 - 218
9000 - 205
mm
2686x1707x1460
2686x1707x1580
2686x1707x1580
Kg
730
780
820
207
ROOFTOP | STANDARD. AXIAL FANS
RXCA
Cooling only
RXCBA
Reversible
MAIN FEATURES
Cooling capacities between 40.7 and 192.3 kW
Scroll compressors
Maximum capacity reduction up to 9 stages
depending on model
Maximum air quality and comfort. Option to install
high efficiency F type filters (F6 to F9)
3 versions available: standard (STD), with
gas burner module (GAZ) and high ambient
temperatures (HTA)
Thermostats and controllers included for standard
units with electromechanical controls:
ARIA
Models 1602 to 4502
Advantages
High flow solutions for rooftops, versatile and adaptable to every
project. The units of the RXCA-RXCBA series are rooftop type
compact packaged units, especially designed for installation on
terraces, roofs or any other outdoor space, with air distribution via
conduits.
pGD
Models 5002 to 6002
For the functions, see the "Controls" section on page 216
RXCA Cooling only
RXCBA Reversible
TECHNICAL SPECIFICATIONS
1402
1602
2002
2402
3002
Nominal cooling capacity kW
40.7
46.2
61.2
71.5
84.5
Nominal cooling capacity T.R.
11.6
13.1
17.4
20.3
24.0
Nominal heating capacity kW
42.2
48.6
63.4
74.6
87.5
400.3+N
400.3+N
400.3+N
400.3+N
400.3+N
EER kW/kW
2.7
2.7
2.7
2.8
3.0
COP kW/kW
3.0
3.0
3.0
3.1
3.3
Cooling energy rating (1) 0
C
C
C
C
B
Heating energy rating (1) 0
D
D
D
C
B
Air flow - static pressure m3/h - Pa
7800-100
9500 - 100
12318 - 135
14075 - 115
14980 - 115
2702x2300x1647
2702x2300x1647
2702x2300x1647
2702x2300x1832
2702x2300x2010
1200
1200
1236
1250
1300
MODEL
Power supply (50 Hz ~) V
Dimensions (length x width x height) mm
Net weight Kg
3502
4002
4502
5002
6002
Nominal cooling capacity kW
105.2
115.0
142.6
162.0
192.3
Nominal cooling capacity T.R.
29.9
32.7
40.5
46.1
54.7
Nominal heating capacity kW
109.8
120.0
148.7
167.8
199.4
400.3+N
400.3+N
400.3+N
400.3+N
400.3+N
EER kW/kW
2.9
3.1
2.9
3.0
2.9
COP kW/kW
3.6
3.5
3.2
3.3
3.3
Cooling energy rating (1) 0
B
A
B
B
B
Heating energy rating (1) 0
A
A
C
B
B
Air flow - static pressure m3/h - Pa
17901 - 125
20258-125
25083 - 125
28100 - 150
32800 - 175
4800x2100x1872
4800x2100x1872
4800x2100x1872
4800x2100x2222
4800x2100x2222
2200
2210
2240
2600
2710
MODEL
Power supply (50 Hz ~) V
Dimensions (length x width x height) mm
Net weight Kg
208
Air inlet/outlet configuration options
standard
optional
Options
ENERGY EFFICIENCY
Option for mixing module for free cooling with three
dampers
Thermal or enthalpic control system with PCO controller
card and pGD controller
Compressor soft start
Fan soft start, internal and/or external
Thermodynamic heat recovery (R-404A, etc.)
Hot water heating coils
Auxiliary electric heating coils
Pre-treated anti-corrosion coils
Suitable for disassembly
Mounting base
Condensation fan with available pressure
RCCBA with centrifugal condensation fan
Condensate tray on external section
Safety grille on outside heat exchanger section
Droplet separator
Internal EC plugfan
Axial EC fans
Condensation controlled by variable voltage controller
MAINTENANCE
Service valves
External manometers for reading pressure
External pressure tapping points
Dirty filter detector
AIR QUALITY
G4 gravimetric filter on return
Opacimetric filter on return class F6 to F9 (can be
combined with a G4 or Fx+Fy)
External module for F filters on rail
Fresh air inlet damper
CONTROLS
pGD thermostat
DSX@ thermostat (requires 24 V)
Alarm signals
Smoke detection
Remote start/stop
Stand-alone electrical board
Option for master/slave operation
High-pressure switch for resetting
from thermostat
Unit without thermostat
Wall-mounted room temperature sensor
Return temperature sensor (ARIA)
Temperature sensor in conduit
Air quality sensor
Operation for redundant machine
Centralised integrated management operation
Operation without neutral
Timer programming function and Modbus connection etc.
please refer to the Thermostats section
Option to personalise the software with specific functions for the
client
SOUND LEVEL
Double thermal-acoustic insulation
Acoustic insulation on compressor
Low noise outdoor fan
UNIT INSTALLATION
Magneto-thermal circuit breakers in the electrical board
60Hz power supply and voltages of 230, 208 etc.
Option to manufacture symmetrical configuration units
Upgraded motors
Internal flow control if filters clogged (with internal EC
plugfan)
Operation for antifreeze electric heater in condensate tray
Lower internal air discharge
Upper internal air discharge
Rear internal air discharge (with EC plugfan)
Lower internal air return
Upper internal air return
Flame-proof filter class M0
Thermal-acoustic insulation class M0
Gas burner
Hot gas bypass
Condensation controlled by double speed fan, models
1402/3502
Condensation controlled by On/Off fan, models 4002/4502
Besides these options, please speak to our Sales Department for any other
configuration or function that is not listed as being available.
209
ROOFTOP | WITH THERMODYNAMIC HEAT RECOVERY, AXIAL FANS
RXCA RCF
Cooling only
RXCBA RCF
Reversible
MAIN FEATURES
Cooling capacities
between 53.1 and 233.4 kW
Scroll compressors
Maximum capacity reduction up to 9 stages
depending on model
Maximum air quality and comfort. Option to install
high efficiency F type filters (F6 to F9)
3 versions available: with thermodynamic heat
recovery (RCF), with gas burner module (GAZ) and
high ambient temperatures (HTA)
Thermostat:
pGD
standard
RXCBA RCF Reversible
MODEL
Total cooling capacity
Cooling capacity main circuits
Cooling capacity recovery circuit
Total cooling capacity
Cooling capacity main circuits
Cooling capacity recovery circuit
Total heating capacity
Heating capacity main circuits
Heating capacity recovery circuit
Power supply (50 Hz ~)
EER
COP
Cooling energy rating (1)
Heating energy rating (1)
Air flow
Supply side available pressure
Return side available pressure
Dimensions (length x width x height)
Net weight
Rooftop solution with thermodynamic heat recovery. Maximum
efficiency in minimum space.
The units of the RXCA/RXCBA RCF series are rooftop type compact
packaged units, especially designed for installation on terraces, roofs
or any other outdoor space, with air distribution via conduits. The
thermodynamic heat recovery system uses an additional refrigerant
circuit as a heat exchanger. The purpose of this additional circuit is to
transfer the energy of the exhaust air to the fresh air of ventilation. This
system is an alternative to the conventional heat recovery system.
For the functions, see
the "Controls" section
on page 216
Air inlet/outlet configuration options
RXCA RCF Cooling only
Advantages
kW
kW
kW
T.R.
T.R.
T.R.
kW
kW
kW
V
0
0
0
0
m3/h
Pa
Pa
mm
Kg
optional
TECHNICAL SPECIFICATIONS
1402
1602
2002
2402
3002
53.1
40.2
12.9
15.1
11.4
3.7
55.7
43.8
11.9
400.3+N
2.9
3.4
B
B
7,800
100
75
2702x2300x2175
1420
60.6
46.6
14.0
17.2
13.2
4.0
60.1
47.2
12.9
400.3+N
2.9
3.4
B
B
9,500
100
85
2702x2300x2175
1425
75.4
58.9
16.5
21.4
16.7
4.7
76.9
61.7
15.2
400.3+N
2.8
3.2
C
C
12,318
135
85
2702x2300x2175
1475
92.3
71.1
21.2
26.2
20.2
6.0
93.1
72.5
20.6
400.3+N
2.9
3.2
B
C
14,075
115
85
2702x2300x2360
1540
101.9
80.2
21.7
29.0
22.8
6.2
105.5
85.1
20.4
400.3+N
3.0
3.3
B
B
14,980
115
85
2702x2300x2540
1604
➜
210
RXCA RCF Cooling only
RXCBA RCF Reversible
MODEL
Total cooling capacity
Cooling capacity main circuits
Cooling capacity recovery circuit
Total cooling capacity
Cooling capacity main circuits
Cooling capacity recovery circuit
Total heating capacity
Heating capacity main circuits
Heating capacity recovery circuit
Power supply (50 Hz ~)
EER
COP
Cooling energy rating (1)
Heating energy rating (1)
Air flow
Supply side available pressure
Return side available pressure
Dimensions (length x width x height)
Net weight
kW
kW
kW
T.R.
T.R.
T.R.
kW
kW
kW
V
kW
kW
kW
kW
m3/h
Pa
Pa
mm
Kg
TECHNICAL SPECIFICATIONS
3502
4002
4502
5002
6002
125.1
100.5
24.6
35.6
28.6
7.0
130.6
106.7
23.9
400.3+N
3.3
3.7
A
A
17,901
125
70
4800x2100x2410
2650
141.4
110.4
31.0
40.2
31.4
8.8
146.9
116.7
30.2
400.3+N
3.1
3.5
A
A
20,258
125
85
4800x2100x2410
2780
178.9
141.3
37.6
50.9
40.2
10.7
179.8
144.5
35.3
400.3+N
3.0
3.3
B
B
25,083
125
85
4800x2100x2410
2820
202.9
160.9
42.0
57.7
45.7
11.9
202.9
163.1
39.8
400.3+N
3.1
3.4
A
B
28,100
150
85
4800x2100x2760
3450
233.4
190.9
42.5
66.4
54.3
12.1
233.9
193.8
40.1
400.3+N
3.0
3.3
B
B
32,800
175
100
4800x2100x2760
3480
Options
ENERGY EFFICIENCY
Thermal or enthalpic control system for the integrated
free-cooling with PCO controller card and pGD controller
Compressor soft start
Soft start internal and/or external fan
Condensation control by variable voltage controller
Thermodynamic heat recovery (R-404A, etc.)
Mounting base
Condensation fan with available pressure
RCCBA with centrifugal condensation fan
Condensate tray on external section
Safety grille on outside heat exchanger section
Droplet separator
Internal EC plugfan
Axial EC fans
AIR QUALITY
G4 gravimetric filter on return
Opacimetric filter on return class F6 to F9 (can be combined
with a G4 or Fx+Fy)
External module for F filters on rail
SOUND LEVEL
Double thermal-acoustic insulation
Acoustic insulation on compressor
Low noise outdoor fan
UNIT INSTALLATION
Magneto-thermal circuit breakers in the electrical board
60Hz power supply and voltages of 230, 208 etc.
Option to manufacture symmetrical configuration units
Upgraded motors
Internal flow control if filters are clogged
Operation for antifreeze electric heater in condensate tray
Lower internal air discharge
Rear internal air discharge (with EC plugfan)
Upper internal air return
Flame-proof filter class M0
Thermal-acoustic insulation class M0
Gas burner
Hot gas bypass
Condensation controlled by double speed fan, models
1402/3502
Condensation controlled by On/Off fan, models 4002/4502
Hot water heating coils
Auxiliary electric heating coils
Pre-treated anti-corrosion coils
Suitable for disassembly
MAINTENANCE
Service valves
External manometers for reading pressure
External pressure tapping points
Dirty filter detector
CONTROLS
pGD thermostat
Thermostat DSX@
Alarm signals
Smoke detection
Remote start/stop
Stand-alone electrical board
Option for master/slave operation
High-pressure switch for resetting from thermostat
Unit without thermostat
Wall-mounted or room temperature sensor
Return temperature sensor
Temperature sensor in conduit
Air quality sensor
Operation for redundant machine
Centralised integrated management operation
Operation without neutral
Timer programming and Modbus connection etc. please refer to
the section on Thermostats
Besides these options, please speak to our Sales Department for any other
configuration or function that is not listed as being available.
211
ROOFTOP | STANDARD. CENTRIFUGAL FANS
RCCA
Cooling only
RCCBA
Reversible
MAIN FEATURES
ESPECIALLY FOR
SETUP IN DIFFICULT
LOCATIONS
Cooling capacities between 40.7 and 84.5 kW
Scroll compressors
Maximum capacity reduction up to 4 stages
depending on model
Maximum air quality and comfort. Option to install
high efficiency F type filters (F6 to F9)
3 versions available: standard (STD), with gas
burner module (GAZ) and high ambient temperatures
(HTA)
Thermostats and controllers included for standard
units with electromechanical controls:
Advantages
Shopping centres, multiplex cinemas, large supermarkets, etc.
The units of the RCCA/RCCBA series are rooftop type compact
packaged units with centrifugal fans on both sections enabling
installation indoors; air is distributed via conduits.
ARIA
Models 1402 to 3002
For the functions, see the "Controls" section on page 216
Air inlet/outlet configuration options
standard
OUTDOOR SECTION
RCCA Cooling only
optional
INDOOR SECTION
RCCBA Reversible
TECHNICAL SPECIFICATIONS
1402
1602
2002
2402
3002
Nominal cooling capacity kW
40.7
46.2
61.2
71.5
84.5
Nominal cooling capacity T.R.
11.6
13.1
17.4
20.3
24.0
Nominal heating capacity kW
42.2
48.6
63.4
74.6
87.5
400.3+N
400.3+N
400.3+N
400.3+N
400.3+N
EER kW/kW
2.7
2.6
2.6
2.7
2.8
COP kW/kW
2.9
2.8
2.9
3.0
3.2
Cooling energy rating 0
C
D
D
C
C
Heating energy rating 0
D
D
D
D
C
7800-100
9500 - 100
12318 - 135
14075 - 115
14980 - 115
2702x2300x2185
2702x2300x2185
2702x2300x2185
2702x2300x2390
2702x2300x2550
1500
1500
1536
1550
1600
MODEL
Power supply (50 Hz ~) V
Air flow - static pressure m3/h - Pa
Dimensions (length x width x height) mm
Net weight Kg
212
Options
ENERGY EFFICIENCY
Option for mixing module for free cooling with three dampers
Thermal or enthalpic control system with PCO controller card
and pGD controller
Compressor soft start
Fan soft start, internal and/or external
Thermodynamic heat recovery (R-404A, etc.)
Condensation controlled by frequency inverter
Internal EC plugfan
AIR QUALITY
G4 gravimetric filter on return
Opacimetric filter on return class F6 to F9 (can be combined
with a G4 or Fx+Fy)
External module for F filters on rail
Fresh air inlet damper
SOUND LEVEL
Double thermal-acoustic insulation
Acoustic insulation on compressor
UNIT INSTALLATION
Magneto-thermal circuit breakers in the electrical board
60Hz power supply and voltages of 230, 208 etc.
Option to manufacture symmetrical configuration units
Upgraded motors
Internal flow control if filters are clogged
Operation for antifreeze electric heater in condensate tray
Lower internal air discharge
Upper internal air discharge
Rear internal air discharge (with plugfan EC fans)
Lower internal air return
Upper internal air return
Flame-proof filter class M0
Gas burner (pGD thermostat is required)
Thermal-acoustic insulation class M0
Hot gas bypass
Hot water heating coils
Auxiliary electric heating coils
Pre-treated anti-corrosion coils
Suitable for disassembly
Mounting base
Condensation fan with greater available pressure
Safety grille on outside heat exchanger section
Droplet separator
MAINTENANCE
Service valves
External manometers for reading pressure
External pressure tapping points
Dirty filter detector
CONTROLS
pGD thermostat
Thermostat DSX@ (with man. 24 V)
SUPER SI thermostat (man. 24 V)
Alarm signals
Smoke detection
Remote start/stop
Stand-alone electrical board
Option for master/slave operation
High-pressure switch for resetting from thermostat
Unit without thermostat
Wall-mounted room temperature sensor
Return temperature sensor
Temperature sensor in conduit
Air quality sensor
Operation for redundant machine
Centralised integrated management operation
Operation without neutral
Timer programming function and Modbus connection etc.
please refer to the Thermostats section
Besides these options, please speak to our Sales Department for any other
configuration or function that is not listed as being available.
213
ROOFTOP | WITH THERMODYNAMIC HEAT RECOVERY, CENTRIFUGAL FANS
RCCA RCF
Cooling only
RCCBA RCF
Reversible
MAIN FEATURES
ESPECIALLY FOR
SETUP IN DIFFICULT
LOCATIONS
Cooling capacities between 53.1 and 101.9 kW
Scroll compressors
Maximum capacity reduction up to 4 stages
depending on model
Maximum air quality and comfort. Option to install
high efficiency F type filters (F6 to F9)
3 versions available: with thermodynamic heat
recovery (RCF), with gas burner module (GAZ) and
high ambient temperatures (HTA)
Thermostat – pGD (all models)
pGD
Advantages
Shopping centres, multiplex cinemas, large supermarkets, etc.
The units of the RCCA/RCCBA RCF series are rooftop type compact
packaged units with centrifugal fans on both sections enabling
installation indoors; air is distributed via conduits. The thermodynamic
recovery system uses an additional refrigerant circuit as a heat
exchanger. The purpose of this additional circuit is to transfer the
energy of the exhaust air to the fresh air of ventilation. This system is
an alternative to the conventional heat recovery system.
For the functions,
please refer to the "Control"
section on page 216
Air inlet/outlet configuration options
standard
Example of installation with packaged units
optional
OUTDOOR SECTION
INDOOR SECTION
RXCA/RXCBA
RCCA/RCCBA
RCCA RCF Cooling only
RCCBA RCF Reversible
TECHNICAL SPECIFICATIONS
1402
1602
2002
2402
3002
Total cooling capacity kW
53.1
60.6
75.4
92.3
101.9
Cooling capacity main circuits kW
40.2
46.6
58.9
71.1
80.2
Cooling capacity recovery circuit kW
12.9
14.0
16.5
21.2
21.7
Total cooling capacity T.R.
15.1
17.2
21.4
26.2
29.0
Cooling capacity main circuits T.R.
11.4
13.2
16.7
20.2
22.8
3.7
4.0
4.7
6.0
6.2
Total heating capacity kW
55.7
60.1
76.9
93.1
105.5
Heating capacity main circuits kW
43.8
47.2
61.7
72.5
85.1
Heating capacity recovery circuit kW
11.9
12.9
15.2
20.6
20.4
400.3+N
400.3+N
400.3+N
400.3+N
400.3+N
EER kW/kW
2.9
2.9
2.8
2.9
3.0
COP kW/kW
3.3
3.3
3.1
3.1
3.2
Cooling energy rating 0
B
B
C
B
B
Heating energy rating 0
B
B
C
C
C
7,800
9,500
12,318
14,075
14,980
Supply side available pressure Pa
100
100
135
115
115
Return side available pressure Pa
75
85
85
85
85
2702x2300x2185
2702x2300x2185
2702x2300x2185
2702x2300x2390
2702x2300x2550
1720
1725
1775
1840
1904
MODEL
Cooling capacity recovery circuit T.R.
Power supply (50 Hz ~) V
Air flow m3/h
Dimensions (length x width x height) mm
Net weight Kg
214
Options
ENERGY EFFICIENCY
Thermal or enthalpic control system for the integrated
free-cooling with PCO controller card and pGD controller
Compressor soft start
Internal fan soft start and/or external
Thermodynamic heat recovery (R-404A, etc.)
Condensation controlled by frequency inverter
Auxiliary electric heating coils
Pre-treated anti-corrosion coils
Suitable for disassembly
Mounting base
Condensation fan with available pressure
Safety grille on outside heat exchanger section
Droplet separator
Internal EC plugfan
MAINTENANCE
Service valves
External manometers for reading pressure
External pressure tapping points
Dirty filter detector
AIR QUALITY
G4 gravimetric filter on return
Opacimetric filter on return class F6 to F9 (can be
combined with a G4 or Fx+Fy)
External module for F filters on rail
CONTROLS
pGD thermostat
Thermostat DSX@ (with man. 24 V)
SUPER SI thermostat (man. 24 V)
Alarm signals
Smoke detection
Remote start/stop
Stand-alone electrical board
Option for master/slave operation
Wall-mounted or room temperature sensor
Temperature sensor in conduit
Air quality sensor
Operation for redundant machine
Centralised integrated management operation
Operation without neutral
Timer programming function and Modbus connection etc.
please refer to the Thermostats section
SOUND LEVEL
Double thermal-acoustic insulation
Acoustic insulation on compressor
UNIT INSTALLATION
Magneto-thermal circuit breakers in the electrical board
60Hz power supply and voltages of 230, 208 etc.
Option to manufacture symmetrical configuration units
Upgraded motors
Internal flow control if filters are clogged
Operation for antifreeze electric heater in condensate tray
Lower internal air discharge
Rear internal air discharge (with plugfan EC fans)
Upper internal air return
Flame-proof filter class M0
Thermal-acoustic insulation class M0
Gas burner (pGD thermostat is required)
Hot gas bypass
Hot water heating coils
Besides these options, please speak to our Sales Department for any other
configuration or function that is not listed as being available.
THE BENEFITS OF THERMODYNAMIC RECOVERY
1. The extra recovery circuit operates at very high efficiency and continuously and does not depend on changes
of external temperature like the main circuits > Very high efficiency with moderated temperatures (whereas
conventional static heat recuperators have very low efficiencies).
2. Very compact profile of the equipment > Easier and quicker installation.
3. By adding an extra circuit, we get greater capacity reduction and therefore higher efficiencies on partial load >
Significant reduction of energy consumed.
CONDENSER
EXHAUST
GREATER
ENERGY EFFICIENCY
RETURN
COIL
FRESH AIR
DISCHARGE
MAIN CIRCUITS
215
CONTROLS
CONTROLS | CONTROLLERS AND THERMOSTATS
FOR AIR-AIR AND AIR-WATER PACKAGED RANGE
SUPER-SI CONTROLLER
Digital thermostat with LCD screen
Operation at 24 V supply
Cool/Heat/automatic control
Fan speed selection
For 1 or 2 compressor machines
Cooling only or heat pump
1 or 2 electric capacity steps
Window contact / economy function
Internal/external sensor (remote)
STANDARD
ON-OFF RANGE
DSX@
Digital thermostat with LCD screen
Operation at 24 V supply
Cool/Heat/automatic selection
Fan speed selection
For 1 or 2 compressor machines
Cooling only or heat pump
1 or 2 electric capacity steps
Timer
Internal/external sensor (remote)
Integrated MODBUS protocol
OPTIONAL
ON-OFF RANGE
FOR INVERTER AND AIR-AIR PACKAGED RANGE
th TUNE
Thermostat consisting of a user interface
terminal installed in the room and an input/
output electronic board (uPC), located
in outdoor unit (electrical panel). For
INVERTER AIR-AIR R410A units
For inverter units with 1 compressor
Cooling only or heat pump
220 V power supply
3-speed or automatic speed selection
of indoor fan
1 step electric heater used during
defrosting only
Return air temperature sensor
3 access level thermostat for Users,
Maintenance and Manufacturer
Modbus option with RS-485
connection
STANDARD
INVERTER RANGE
FOR AIR-WATER PACKAGED AND ROOFTOP UNITS RANGE
ARIA
Thermostat consisting of a user
interface terminal installed in the room
and an input/output electronic board,
located in outdoor unit (electrical panel).
For AIR-AIR or AIR-WATER units
For units with 1 or 2 compressors
Cooling only or heat pump
2 step electric heater
Return air or room temperature sensor
selection
3 access level thermostat for Users,
Maintenance and Manufacturer
217
Timer programming system (only for
ARIA PROGRAMMABLE)
Option for ARIA pLAN model network
connection (see Centralised management
systems)
Output signal compatible with Modbus,
BacNet, Lonworks communication
protocols via super node gateway plus
protocol card used
CONTROLS | CONTROLLERS AND THERMOSTATS
FOR AIR-AIR PACKAGED AND ROOFTOP UNITS RANGE
pGD (with PCOC, PCOC3 control cards)
Thermostat consisting of a user interface
terminal installed in the room and an input/
output electronic board (PCOC, PCO3),
located in outdoor unit (electrical panel).
Only for AIR-AIR units
For units with 1 or 2 compressors
Cooling only or heat pump
Control of 2 or 3 step electric heater,
heating valve and gas burner module
Option to adapt and modify the internal
software to meet the specific needs of
the client
Option to interconnect units in
network (see Centralised management
systems)
Several options available: clock card
for timer programming, cards available
for Modbus, BacNet, Lonworks, TCPIP communication protocols...
FOR LIQUID CHILLERS
LCX06C
Configurable thermostat used mainly
for AIR to WATER or WATER to WATER
chillers with R410A refrigerant. Formed by
a single set that is composed of electronic
board and user interface.
For units with up to 2 compressors.
Cooling only or heat pump.
Management of water pump and
hydraulic module.
Timer programming system.
3 access level themostat for Users,
Maintenance and Manufacturer.
Communication screen for the user
via a LED display.
Option for Modbus protocol output
signal by a communication card.
Standard for: Krono XA / XBA 801.1
-1001.1 - 1201.1 - 1501.1
MCX08
Configurable thermostat used mainly
for AIR to WATER or WATER to WATER
chillers with R410A refrigerant. Consisting
of a single set that is composed of
electronic board and user interface.
For machines with up to 4 compressors.
Cooling only or heat pump.
Management of water pump and
hydraulic module.
Timer programming system
3 access level themostat for Users,
Maintenance and Manufacturer
218
Option to interconnect units in
network (see Centralised management
systems)
Option for Modbus protocol output
signal by a communication card.
Standard for: Krono XA / XBA 1601.2
to 5001.2
Optional for: Krono XA / XBA 801.1
-1001.1 - 1201.1 - 1501.1
FOR FCW/FCCW, FPWS, FKW, FKWS, BSW RANGE
FANCOIL UNITS
FW BASIC CONTROLLER
CT CONTROLLER +
THERMOSTAT
Features:
On/Off switching, Winter/Summer selection
3 speeds
Without thermostat
Built-in type
Only for vertical FCCW units with cabinet.
Features:
Electronic thermostat for 2 or 4 pipe units
Temperature control
On/Off switching, Winter/Summer
selection
3 speeds
External sensor
230 V
Built-in type
Accessories:
Room thermostat (mounted or
non-mounted)
Water low temperature thermostat (mounted
or non-mounted)
MI INFRARED CONTROLLER
RC-1 WALL-MOUNTED
BASIC CONTROLLER
Features:
For 2 or 4 pipe units
Remote controller with LCD screen and
temperature setting, manual or automatic
change of fan speed, manual heating/
cooling change, clock, start/stop timer.
Room temperature and minimum water
temperature sensor
Output signal for on-off valve and
condensate pump
230 V
Built-in type
Option supplied loose
Features:
On/Off switching, Winter/Summer
selection
3 speeds
Without thermostat
Wall mounted type
MP2 WALL-MOUNTED
ELECTRONIC THERMOSTAT
WALL-MOUNTED RC-2/X6
ELECTRONIC
THERMOSTAT
Features:
For 2 or 4 pipe units
Temperature control
On/Off switching, Winter/Summer selection
3 speeds
Input signal for room temperature and
minimum water temperature sensor
Output signal for on-off valve and
condensate pump
230 V
Wall mounted type
Option supplied loose
Features:
Programmable for 2 or 4 pipe units
LCD screen
Temperature control
Automatic, manual or centralised heating/
cooling change
Filter clogging control
Economy mode
Antifreeze mode
Input signals for window contact, low
temperature and air intake
Output signals for on-off valve 230 V or
24 V supply and electric heater
3 speeds
230 V or 24 V supply
Wall mounted type
Option supplied loose
Please contact us for models with
modulating valves
REMOTE CONTROL
WITH CABLE RCTZ/X7
Features:
Accessories for units with remote controller
For 2 or 4 pipe units
LCD screen with temperature control,
automatic or manual fan speed change
Manual heating/cooling change
Clock and start/stop timer
Air diffuser control
Economy function
Wall mounted type
Only for FKW cassette fan coil units
MODEL
FCW/FCCW
FW BASIC CONTROLLER
CT CONTROLLER + THERMOSTAT
MI INFRARED CONTROLLER
RC-1 WALL-MOUNTED BASIC CONTROLLER
MP2 WALL-MOUNTED ELECTRONIC THERMOSTAT
RC-2/X6 WALL-MOUNTED ELECTRONIC THERMOSTAT
RCTZ/X7 WIRED REMOTE CONTROL
219
Accessories:
Transformer 230/24V
NTC type sensor for air intake
(includes 1 m cable)
Minimum water level sensor
(includes 1 m cable)
FKW
FKWS
BSW
CONTROL SYSTEMS | HYDROFAN SYSTEM
HYDROFAN SYSTEM
System designed to control water-based installations in a centralised, simple and efficient manner.
Consisting of a set of components, including a touchscreen display, for controlling liquid chillers,
fancoils and AHU.
SYSTEM COMPONENTS
Cards
Fcc base card
4 relay card
2 x (0-10 V) + 2 relay card
RS-485 serial card
Thermostat
ACQUA ENVIRONMENT
pGD TOUCH touchscreen display
The touchscreen display functions
as a central control panel. Access is
controlled by username and password
and the panel is used to control the
components.
The touchscreen display can control installations
up to 30 fan coil units with 1 chiller.
For installations with more elements, please refer
to the possible configurations.
Screen showing all elements of the network (in
this installation, there are 14 FCU, 1 AHU and 1
chiller).
This screen allows access to every fancoil in order
to turn units on or off, to change the setpoint, to
select automatic speed or manual low, medium
or high speed and to view unit status, cooling or
heating mode.
From this screen, user can turn AHU on or off,
change the setpoint, view the opening of the
control valve and view unit status, cooling or
heating mode.
The chiller screen allows user to turn the unit on
or off, to select cooling or heating mode, to view
the leaving and the return temperatures and to
check if the chiller has an alarm.
From this screen, user can configure a timer
programme for startup and for all other elements.
220
Our Hydrofan control system makes it possible to optimise the control and operation of the system and to adapt the
capacity of the liquid chiller to the needs at the time of installation.
The individual control of the different types of fancoil is integrated into a collective control system that enables simple
and effective interaction for users and several options for remote control via our pGD touchscreen.
CENTRALISED CONTROL SYSTEM
TO MAXIMISE THE ENERGY
EFFICIENCY OF THE INSTALLATION
FANCOIL
FANCOIL
Thermostat
ACQUA
Thermostat
ACQUA
LIQUID
CHILLER
221
FANCOIL
Thermostat
ACQUA
Touchscreen
display
pGD TOUCH
CONTROL SYSTEM | PL@NT VISOR MONITORING SYSTEM (BMS)
PL@NT VISOR MONITORING SYSTEM (BMS)
Carel monitoring system designed for controlling installations.
All thermostats with a MODBUS output can be connected and integrated via RS-485.
The Pl@nt Visor technology allows integration and control of the system via ModBus by means of the RS485 card
installed in the units. This system allows control via the internet of the whole group and on-line monitoring to verify
correct operation remotely.
MAIN FEATURES
Monitoring features with visual and graphical elements
User management for access control and logging operations
Configurable report management
Alarm management
Local and remote connectivity
Timer programming system
Energy saving management
Option for customisation of screens by emulating installation (SCADA)
Activity planning and controls for tools or groups of tools
PL@NT VISOR: MAXIMUM LEVEL OF
CONTROL FOR CONSTANT MONITORING
OF THE INSTALLATION
Pl@ntVisor
(freeware)
(pGDXXXXX)
Unit 30
(PJ32XXXXX)
Unit 13
(IR32XXXXX)
Unit 15
(MCH2XXXXX)
Unit 14
Maximum number of connected units to be confirmed, according to the Pl@nt Visor model.
222
(PCO2000XX0)
Unit 12
(MTCDXXXXXX)
Unit 1
Installation screen layout (example):
a customised installation is possible.
Customised screen for rooftop, basic controller of the
unit: makes it possible to carry out basic operations: ON-OFF,
change cooling/heating mode, change temperature setpoints
and visualise the status of the main components.
Rooftop detail screen: makes it possible to visualise and
change all parameters via the
Pl@nt Visor.
Screen with full list of settings (access according to user
level): allows reading/modification of values as well as saving
them (backup copy).
Screen with full list of alarms (access according to user level):
enables visualisation of alarms and allows you to reset them.
Report management screen (access according to user
level): allows configuration and creation of reports, depending
on date intervals and the variables selected.
223
CONTROL SYSTEM | CENTRALISED MANAGEMENT SYSTEM AND BMS
CENTRALISED MANAGEMENT SYSTEM AND BMS
Centralised control for units with ARIA pLAN thermostat
Network up to 15 units
Centralised management for a network of ARIA pLAN units, via a pGD controller
"ARIA" CONTROLLER
"ARIA" CONTROLLER
"ARIA" CONTROLLER
Network from 15 to 40 units
Centralised management for a network of ARIA pLAN units, via a pGD controller
"ARIA" CONTROLLER
"ARIA" CONTROLLER
"ARIA" CONTROLLER
SUPER NODE
Connection to BMS with the following
integration languages: "Modbus" "Lonworks" "BacNet".
Please contact us for other integration languages.
Centralised control system for units with pGD thermostat and PCOC, PCO3 boards
Connection of several units via a pLAN network, suitable for the PCOC, PCO3 board. From s single pGD thermostat it is possible to
access to each of the machines connected to the network. Maximum 15 units connected.
224
Connection of several units using POOC, PCO3 cards via the RS-458 cards towards a monitoring system.
BMS connection with the following integration languages:
Modbus - Lonworks - BacNet. Please contact us for other integration languages.
Centralised control for units with MICROCHILLER 2 thermostat
Output to BMS monitoring system via FCSER cards.
1
2
3
BMS connection with the following integration languages: Modbus. Please contact us for other integration languages.
Maximum number of connected units to be confirmed according to the language.
Centralised control for units with DN33 thermostat
Output to BMS monitoring system via RS-485 cards for DN33.
Modbus. Please contact us for other integration
languages.
Maximum number of connected units to be confirmed
according to the language.
225
CONTROL SYSTEM | OTHER CONTROLS
OTHER CONTROLS
CMVM
Manual speed selector:
With 4 positions : Off – Low speed –
Medium speed – High speed
For installation on the unit
Suitable for units of type:
FCW
FCCW
WESPAK
TRM-FA
Wall type thermostat supplied in kit:
On/Off switch, Summer/Winter manual
changeover, manual speed selector :
- Low speed
- Medium speed
- High speed
Suitable for units of type:
FPW in 2-pipe system without valve,
with action on ventilation only
FCW, FCCW in 2-pipe or 4-pipe
system with action on ventilation and
valves
BSW, BHW ductable type
TRM-VP
Wall type thermostat supplied in kit:
On/Off switch, Summer/Winter manual
changeover, manual speed selector:
- Low speed
- Medium speed
- High speed
Suitable for units of type:
FCW, FCCW, BSW and BHW in
2-pipe or 4-pipe system with action
on valves only
TAE 20
Wall type thermostat supplied in kit:
Comprises adjustable dead zone with
Summer/Winter automatic changeover
With manual switch to set the operating
mode (heating or cooling) in standby
and to select fan speeds (LS – MS – HS),
normally open or normally closed window
contact, antifreeze mode, unoccupied
mode and adjustable differentials for
heating and cooling modes
Suitable for units of type:
FCW, FCCW, BSW and BHW in
2-pipe and 4-pipe system with action
on valves only or on valve and electric
heater
FPW in 2-pipe system with action on
valves only
TAE 20 + SEH
Wall type thermostat supplied in kit:
Comprises adjustable dead zone with
Summer/Winter automatic changeover
With manual switch to set the operating
mode (heating or cooling) in standby
and to select fan speeds (LS – MS – HS),
normally open or normally closed window
contact, antifreeze mode, unoccupied
mode and adjustable differentials for
heating and cooling modes
226
Supplied with piping sensor for
changeover on water
Installation of 4-way valve is
mandatory
Suitable for units of type:
FCW, FCCW, BSW and BHW in
reversible 2-pipe system with action
on valves only or on valve and electric
heater
FPW in reversible 2-pipe system with
action on valves only
AQU@NET
The Aqu@Net electronic control has
been specifically developed for the
console, ceiling or cassette type fan coil
units working with 100% recycled air,
suitable for cooling only 2-pipe, heating
only 2-pipe, 2-pipe/2-wire, reversible
2-pipe with or without extra electric
heating and 4-pipe applications.
It is composed of a FCC controller
mounted on the unit and a RCL control
that can be mounted as optional on the
console type fan coil unit range.
Aqu@Net is a new generation of
communicating control working under
proprietary bus thanks to an additional
PC board very easy to install and
a supervision station called µBMS
(please refer to the manual of this
latter).
This control allows also, for the small
installations, to realize easily a master/
slaves network by wire in order to
control up to 15 units with one RCL
control only.
Aqu@Net electronic system:
The Aqu@Net electronic control
has been designed to provide a good
compromise between cost (thermal
valve for integral proportional control),
ergonomy and performance.
It is compatible with the supervision
station µBMS and is communicating
under proprietary bus, but it can also
work without supervision station.
The Aqu@Net control ensures the
following models of air conditioning
system:
- Model A: For heating only 2-pipe or
cooling only 2-pipe fan coil units with
manual changeover.
- Model B: For reversible 2-pipe fan
coil units with automatic changeover
(piping sensor).
- Model C: For 2-pipe/2-wire fan coil
units.
- Model D: For reversible 2-pipe fan
coil units with automatic changeover
(piping sensor) and extra electric
heating.
- Model E: For 4-pipe fan coil units.
Description of RCL control:
The RCL control has been specifically
designed to be used with fan coil units
equipped with Aqu@Net system.
It operates independently on the units
having FCC controller whatever its
configuration (A, B, C, D, E).
Once electrical connections
adequately carried out, the digital
display shows set point temperature,
operating mode and fan speeds.
Remark : If a µBMS supervision
station or a BMS (Building
Management System) is used, the
settings displayed are not necessarily
the settings used at the instant by the
Aqu@Net controller.
The RCL control displays only the
settings changed on it and is not
capable of displaying the settings
changed on a µBMS supervision
station or a BMS.
NOTE: When the RCL control is installed on
a cabinet type unit, its blue connector is not
plugged into the FCC controller.
Control suitable for the units:
WESPAK and SLIM@IR
227
GENERAL TERMS AND
CONDITIONS OF SALE FOR
PRODUCTS AND SERVICES
GENERAL TERMS AND CONDITIONS OF SALE FOR PRODUCTS AND SERVICES
TERMS AND CONSIDERATIONS AND ENFORCEABILITY
1. These Terms and Conditions apply to all sales made by WESPER
FRANCE (hereinafter WESPER), whose registered office is at 42, Cours
Jean Jaurès, 17800 Pons, France.
2. These Terms and Conditions govern the sales and technical
assistance services for air conditioning units concluded in metropolitan
France by WESPER and are deemed known and accepted by the
buyer at the time of ordering, being fully applicable unless stipulated
otherwise in writing by WESPER.
3. The term CLIENT refers to the individual or legal entity with which
WESPER signs a sales contract for air conditioning units or for the
provision of technical assistance services. In addition, PRODUCTS
refers to the air-conditioning units being sold by WESPER to the Client.
4. These Terms and Conditions of Sale and Service replace those
previously published in various sales catalogues under the WESPER
brand.
5. Placing an order with WESPER causes the unconditional acceptance
by the Client of these Terms and Conditions of Sale. These Terms
and Conditions of Sale shall be communicated by WESPER to any
Client who requests them for the exercise of their professional activity.
These Terms and Conditions of Sale supersede any purchasing
conditions issued by the Client, whatever the medium (including
Terms and Conditions of Purchase, purchase orders, ...), which are
entirely unenforceable against WESPER. Unless specifically stipulated
otherwise in these Terms and Conditions of Sale, any modification of
the Terms is automatically enforceable on the Client within a period of
one (1) month following notification by any means (mail, email, fax, ...).
ORDERS AND QUOTATIONS
1. Commercial quotations are valid for two months from the date of
sending to the Client.
2. Orders must be in writing, be signed by the Client and marked with
the seal of the Company (if a legal entity) and refer to the WESPER
quotation. By sending the order proposal, these Terms and Conditions
of Sale are deemed as accepted, the acceptance of the order by
WESPER being necessary to carry out its execution.
AMENDMENTS, RETURNS AND CANCELLATIONS
1. Product exchanges or returns will not be accepted after shipment,
unless expressly authorised in writing by WESPER. If approved, the
shipping costs incurred will be charged to the Client, the products
being deemed in perfect condition and packaging. WESPER reserves
the right to charge fees in respect of depreciation of thirty (30)% of the
value of the equipment and costs for receiving, inspecting and repairing
the returned products.
2. Once orders are accepted by WESPER, order cancellations will not
be accepted unless expressly authorised by WESPER. If approved,
WESPER reserves the right to charge fees in respect of expenses
incurred.
3. Any amendments to the order must be made in writing and with the
acceptance of both parties in order to be valid.
DELVIERY TIMES
1. The delivery times shown on quotations are indicative. No damage,
penalties or compensation will be recognised to the Client in case of
delay on the part of WESPER, whatever the reason.
2. The delivery time refers to the date the products leave the factory.
3. Delays can in no way justify cancellation of the order.
4. If special arrangements stipulate penalties, these cannot in any case
exceed 5% of the ex-factory value of equipment not delivered within
the deadlines provided.
5. WESPER is exempted of any commitment relating to delivery in
cases of force majeure such as strikes, fire, war, requisition, epidemic
or delay in transportation.
6. In case of damage during transport, it is the responsibility of the
recipient of the product to confirm specific reservations to the carrier in
accordance with Article 133(3) of the French Commercial Code.
DELIVERY CONDITIONS
1. Delivery is free of ports, metropolitan France, with trucking excluding
tailgate, provided there are no unforeseen accessibility issues. Permits
and licenses required for this purpose are the responsibility of the
Client.
2. Deliveries will be made in business hours and on business days.
3. Products will be delivered in a standard package, the price being
included in the sale price.
4. The Client is responsible for the correct environmental waste
management of packaging supplied with the products.
229
PRICE
1. The prices indicated in the quotations may vary by notification to
the buyer. If the buyer does not accept the new price, they must send
notification in writing within 5 days, consecutive to the date of receipt of
such notification.
2. Prices are free of ports, metropolitan France, with truck tailgate not
included. For deliveries outside of this area, the ports will be charged to the
Client by default.
3. The prices indicated in the quotations are excluding VAT. All taxes that
may be applicable to the sale or service, at the date of their delivery, will be
charged to the Client.
PAYMENT TERMS
1. Billing will be done when the units leave WESPER facilities.
2. The quotation will show in detail the time and manner of payment, in
accordance with the French Law on the Modernisation of the Economy
(LME).
Payment for any account opening or for an amount less than five hundred
(500) euros, payment in full (100%) on request by endorsed bill, by bank
draft or by bank transfer.
Payment beyond the outstanding granted, payment of a deposit (30%) on
request and the balance fifteen (15) days before the date of shipment of
equipment, by endorsed bill, by bank draft or bank transfer.
Payments under the LME to the level of the outstanding granted, invoices
payable 45 days end of month of delivery or up to 60 days net maximum
by endorsed bill or bank transfer.
3. Any non-payment implies the immediate cancellation of the guarantee
on the products supplied and the provision of services.
4. The products remain the property of WESPER until the finalisation of
payment in full. Fir the purposes of retention of title, payment is deemed to
have been made when it is irrevocable. Without prejudice to the retention
of title, WESPER transfer to the Client the right to use the Product,
provided that they meet the General Terms and Conditions of Sale and are
up to date with payment for the Products in accordance with agreed terms.
5. The Client does not have the right to sell the Products to a third party
without having paid all invoices due to WESPER.
6. A discount of 2% is applicable to any early payment.
7. Our invoices are payable at our registered office.
LIABILITY
1. WESPER shall not be liable for damages caused, directly or indirectly,
because of improper installation of the units, provided that installation was
not carried out directly by WESPER or any other company subcontracted
by WESPER.
GUARANTEE
1. In this respect, WESPER publishes the General Terms and Conditions of
Service Guarantee, which constitute the only framework for this purpose.
The Client confirms being aware of these conditions by accepting the
quotation.
2. The equipment is guaranteed for a period of two (2) years from the date
of invoice.
3. Spare parts are guaranteed for a period of six (6) months from the date
of invoice, unless the current guarantee period of the equipment is lower.
4. No claim for compensation or damages may be asserted under the
guarantee.
JURISDICTION
1. For all issues arising from the interpretation and application of these
General Terms and Conditions of Sale, WESPER and the Client submit to
the jurisdiction and
competence of the Courts and Tribunals of Pons (France), expressly
waiving any other jurisdiction that may apply to them.
All information contained in this catalogue may be changed without notice.
LIMITATION
1. Any action or claim on the part of the Client arising from the purchase
relationship between WESPER and the Client in a given year will be
prescribed after a period of two (2) years from the last day of that year.
NOTES
230
NOTES
231
NOTES
232
Download PDF