SITOP PSU100C 12 V/6.5 A STABILIZED POWER SUPPLY INPUT:
AC 120-230 V (DC 110-300 V) OUTPUT: DC 12 V/6.5 A
Technical specifications
Product
SITOP PSU100C
Power supply, type
12 V/6.5 A
Input
Input
1-phase AC or DC
Rated voltage value Vin rated
100 ... 230 V
Voltage range AC
85 ... 264 V
Input voltage for DC
110 ... 300 V
Wide-range input
Yes
Overvoltage resistance
2.3 × Vin rated, 1.3 ms
Mains buffering at Iout rated, min.
20 ms; at Vin = 230 V
Rated line frequency
50 ... 60 Hz
Rated line range
47 ... 63 Hz
Input current at rated input voltage 100 V Rated
value
1.6 A
Input current at rated input voltage 230 V Rated
value
0.8 A
Switch-on current limiting (+25 °C), max.
31 A
I²t, max.
3 A²·s
Built-in incoming fuse
internal
6EP1322-5BA10
Page 1/3
07.01.2015
Changes preserved
© Copyright Siemens AG
Protection in the mains power input (IEC 898)
Recommended miniature circuit breaker: from 16 A characteristic
B or from 10 A characteristic C
Output
Output
Controlled, isolated DC voltage
Rated voltage Vout DC
12 V
Total tolerance, static ±
3 %
Residual ripple peak-peak, max.
200 mV
Residual ripple peak-peak, typ.
80 mV
Spikes peak-peak, max. (bandwidth: 20 MHz)
300 mV
Spikes peak-peak, typ. (bandwidth: 20 MHz)
80 mV
Adjustment range
10.5 ... 12.9 V
Product function Output voltage adjustable
Yes
Output voltage setting
via potentiometer
Status display
Green LED for output voltage OK
On/off behavior
Overshoot of Vout approx. 1 %
Startup delay, max.
1 s
Voltage rise, typ.
500 ms
Rated current value Iout rated
6.5 A
Current range
0 ... 6.5 A
● Note
+50 ... +70 °C: Derating 3.5%/K
Active power supplied typical
78 W
Parallel switching for enhanced performance
Yes; Start-up with single nominal load only
Numbers of parallel switchable units for enhanced
performance
2
Efficiency
Efficiency at Vout rated, Iout rated, approx.
86 %
Power loss at Vout rated, Iout rated, approx.
12.5 W
Active power loss during no-load operation maximum
0.75 W
Closed-loop control
Dynamic mains compensation (Vin rated ±15 %),
max.
0.1 %
Dynamic load smoothing (Iout: 10/90/10 %), Uout ±
typ.
3 %
Load step setting time 10 to 90%, typ.
3 ms
Load step setting time 90 to 10%, typ.
3 ms
Protection and monitoring
Output overvoltage protection
Yes, according to EN 60950-1
Current limitation, typ.
7.2 A
Property of the output Short-circuit proof
Yes
Short-circuit protection
Electronic shutdown, automatic restart
Overload/short-circuit indicator
-
Safety
Primary/secondary isolation
6EP1322-5BA10
Page 2/3
Yes
07.01.2015
Changes preserved
© Copyright Siemens AG
Galvanic isolation
Safety extra-low output voltage Uout acc. to EN 60950-1 and EN
50178
Protection class
Class I
Leakage current maximum
3.5 mA
Leakage current typical
0.4 mA
CE mark
Yes
UL/CSA approval
Yes
UL/cUL (CSA) approval
cULus-Listed (UL 508, CSA C22.2 No. 107.1), File E197259;
cCSAus (CSA C22.2 No. 60950-1, UL 60950-1)
Explosion protection
ATEX (EX) II 3G Ex nA IIC T4; cCSAus (CSA C22.2 No. 213M1987, ANSI/ISA-12.12.01-2007) Class I, Div. 2, Group ABCD,
T4
Certificate of suitability IECEx
No
Certificate of suitability NEC Class 2
No
FM approval
-
CB approval
Yes
Marine approval
GL, ABS
Degree of protection (EN 60529)
IP20
EMC
Emitted interference
EN 55022 Class B
Supply harmonics limitation
EN 61000-3-2
Noise immunity
EN 61000-6-2
Operating data
Ambient temperature during operation
● Note
-20 ... +70 °C
with natural convection
Ambient temperature during transport
-40 ... +85 °C
Ambient temperature during storage
-40 ... +85 °C
Humidity class according to EN 60721
Climate class 3K3, no condensation
Mechanics
Connection technology
screw-type terminals
Connections Supply input
L, N, PE: Removable screw terminal, each for 1 x 0.5 ... 2.5 mm²
Connections Output
+: 1 screw terminal for 0.5 ... 2.5 mm²; -: 2 screw terminals for 0.5
... 2.5 mm²
Connections Auxiliary
-
Width of the enclosure
52.5 mm
Height of the enclosure
80 mm
Depth of the enclosure
100 mm
Weight, approx.
0.32 kg
Product property of the enclosure housing for sideby-side mounting
Yes
Installation
Snaps onto DIN rail EN 60715 35x7.5/15
Electrical accessories
Removable spring-type terminal 6EP1971-5BA00
Other information
Specifications at rated input voltage and ambient temperature +25
°C (unless otherwise specified)
6EP1322-5BA10
Page 3/3
07.01.2015
Changes preserved
© Copyright Siemens AG