- Industrial & lab equipment
- Electrical equipment & supplies
- Power conditioning
- Power adapters & inverters
- User manual
advertisement
Instruction Manual For KFG Power Supply
KFG-2420
DIN rail mounting
• Universal AC single phase input full range
• Can also be used as bi-phase 400VAC
• Installation on DIN rail 7.5 or 15mm
• PFC as standard
• High efficiency up to 90%
• Power ready output
• Parallel connection feature
• Compact dimensions
• CE, TÜV, CCC approved and cULus listed
• Class I Div 2 Groups A, B, C, D approved
Product Description
The Switching power supplys KFG series are specially designed to be used in all automation application where de installation is on a DIN rail and compact dimensions and performance are a must.
Approvals
Ba uart geprüft
T
Rheinland
Product Safety y p e a p p r o v e d
Output Performances
MODEL NO.
KFG-2420
INPUT
VOLTAGE
90~264 VAC
OUTPUT
WATTAGE
480 WATTS
OUTPUT
VOLTAGE
Single Output Models
+ 24 VDC
OUTPUT
CURRENT
20 A
1) When S/P switch is set to parallel, it is not possible to trim output voltage.
Output Data
Line regulation
Load regulation
Non parallel model
Parallel model
± 0.5%
±1%
±5%
Minimum load 0A
Turn on time (full resistive load)
VI nom, Io nom 1000ms
VI nom, Io nom with 7000 μF CAP 1500ms
Transient recovery time 2ms
Ripple and noise
Output voltage accuracy
100mVpp
±1%
±0.03%/°C
EFF.
(min.)
86%
EFF.
(typ.)
89%
Hold up time
Vi= 115VAC
Vi=230VAC
Voltage fall time
(I
0 nom Vi nom)
Rated continuous loading
24V Model
Reverse voltage
24V Model
25ms
30ms
150ms max
20A @ 24VDC/16.8A @ 28.5VDC
VDC 35
Capacitor load
Voltage rise time
Vi nom Io nom
7000μF
150ms
Vi nom, Io nom with 7000μF CAP 500ms
1
Instruction Manual For KFG Power Supply
KFG-2420
DIN rail mounting
Input Data
Rated input voltage
Voltage range
AC
115 - 230VAC
90 - 264VAC
DC
Rated input current
(Vi:90VAC, Io nom)
Inrush current
Typ.
Max.
120 - 375VDC
4.9/2.5A
7/3.5A
Vi= 115VAC 25A
Vi= 230VAC 50A
Controls and Protections
Overload
Input fuse
Output short circuit
Power ready output threshold at start up
Electrical isolation
Contact rating at 60VDC
110 - 140%
T10A/250VAC internal
Fold forward
≥17.6-19.4VDC
500VDC
0.3A
Power dissipation
(Vi : 400VAC, Io nom)
24V Model 63W
Frequency range
Leakage current
Input-Output
Input-FG
47-63Hz
0.25mA
3.5mA
P.F.C Vi=115/230VAC, Ionom 0.99/0.97
Over voltage protection 125/140%
Internal surge voltage protection Varistor
(IEC 61000-4-5)
General Data (@ nominal line, full load, 25°C)
Ambient temperature
Derating (>61°C to +71°C)
Ambient humidity
Storage
Protection degree
Cooling
Pollution degree
MTB
(Bellcore issue 6 @ 40°C, GB)
24V Model
48V Model
-40°C to +71°C
2.5%/C
20 ~ 95%RH
-40°C to +85°C
IP20
Free air convection
2
403000 Hours
416000 Hours
Case material Metal
Dimensions LxWxD mm (inch)
Screw terminal type
Detachable connector type
124.5 x 175.5 x 123.6 mm
(4.9 x 6.91 x 4.87 inches)
143.5 x 175.5 x 123.6 mm
Weight
(5.65 x 6.91 x 4.87 inches)
430 g
Norms and Standards
Vibration resistance
Shock resistance
UL/cUL
TUV
ISA meet IEC 60068-2-6
(Mounting by rail: 10-500Hz,
2G, along X, Y, Z each Axis,
60 min for each Axis) meet IEC 60068-2-27
(15G,11ms, 3 Axis, 6 faces,
3 times for each face)
UL508 listed, UL60950-1
Recognized
EN 60950-1, CB scheme
EN 61558-1, EN 61558-2-
17 (meet EN 60204)
12.12.01 Class I Div 2
Groups A, B, C, D
CE EN 61000-6-3, EN 55022
Class B, EN 61000-3-2,
EN 61000-3-3,
EN 61000-6-2,
EN 55024,
EN 61000-4-2 Level 4,
EN 61000-4-3 Level 3,
EN 61000-4-4 Level 4,
EN 61000-4-5 L-Level 3,
L/N-FG Level 4,
EN 61000-4-6 Level 3,
EN 61000-4-8 Level 4,
EN 61000-4-11,
ENV 50204 Level 2,
EN 61204-3
2
Instruction Manual For KFG Power Supply
KFG-2420
DIN rail mounting
Block Diagram
L 1
L 2
L 3
X
X
X
Rectificador de puente
Y
Circuito
P.F.C.*
Semiconductores de conmutación
Control
PWM**
Rectificador
Opto-
Isolation
Detección intensidad
Reference &
Error Amp.
Over Voltage
Detection
Vo +
Vo -
Selección funcionamiento
Select
Continuos /
Discontinuos
DC ON
DC LOW
Vout ADJ
S/P
* P. F. C. = Corrección de factor de potencia
** PWM = Modulación anchura de pulso
Pin Assignement and Front Controls
7
8
9
5
6
Pin No.
1, 2
3, 4
L
N
Designation
V-
V+
RDY
Description
Negative output teminal
Positive output terminal
A normal open relay contact for DC ON level control
(Never connect except 24V model)
Input terminals (phase conductor, no polarity at DC input)
Input terminal (neutral conductor, no polarity at DC input)
Ground this terminal to minimize high-frequency emissions
Operation indicator LED
DC LOW voltage indicator LED
Trimmer-potentiometer for Vout adjustment
Single / Paralle select switch
Typ. Efficiency Curve Derating Diagram
100
75
0
-40 61 71
80
75
70
65
90
85
10
230 VAC
115 VAC
25 50
Power Out (%)
75 100
3
Instruction Manual For KFG Power Supply
KFG-2420
DIN rail mounting
Typ. Current Limited Curve
Mechanical Drawings
mm (inches)
175.50 [6.91]
175.50 [6.91]
116.60 [4.59] 7 [0.28]
Installation
Ventilation and cooling
Connector
Input Connector
Normal convection
All sides 25mm free space for cooling is recommended.
Size range AWG 24-10 cable.
can withstand torque at maximum 9 pound-inches
Output Connector
Max. torque for screws terminals
Input terminals
Output terminals
4 can withstand torque at maximum 5.5 poundinches.
8 mm strip ping at cable end recom mends, use copper conductors only, 60/75°C.
0.784Nm (7.0lb-in)
0.784Nm (7.0lb-in)
advertisement