PACKAGED HEAT PUMP KH ROOFTOP UNITS 60 HZ ENGINEERING DATA Bulletin No. KHA−024−030−036−048−060−072 (11/09) ASHRAE 90.1 COMPLIANT 2 to 6 Tons Net Cooling Capacity − 22,800 to 69,000 Btuh Net Heating Capacity − 24,000 to 70,000 Btuh Optional Electric Heat − 7.5 to 30 kW MODEL NUMBER IDENTIFICATION K h A 060 S 4 B N 1 Y Voltage P = 208/230V−1 phase−60hz Y = 208/230V-3 phase-60hz G = 460V-3 phase-60hz J = 575V-3 phase-60hz Brand/Family K = Product Line Unit Type H = Packaged Heat Pump Major Design Sequence A = 1st Generation B = 2nd Generation Nominal Cooling Capacity − Tons 024 = 2 Tons 030 = 2.5 Tons 036 = 3 Tons 048 = 4 Tons 060 = 5 Tons 072 = 6 Tons Cooling Efficiency S = Standard Efficiency Minor Design Sequence 1 = 1st Revision 2 = 2nd Revision 3 = 3rd Revision Factory Installed Electric Heat N = No Heat Blower Type D = Direct Drive B = Belt Drive Refrigerant Type 4 = R−410A CONTENTS Accessory Air Resistance . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Page 22 Blower Performance . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Pages 15−22 Cooling/Heating Ratings . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Pages 12−13 Dimensions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Pages 30−37 Electrical/Electric Heat Data . . . . . . . . . . . . . . . . . . . . . . . . . . . Pages 23−26 Electric Heat Capacities . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Page 28 Features and Benefits . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Pages 2−4 Model Number Identification . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Page 1 Options / Accessories . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Pages 6−8 Specifications . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Pages 9−10 Sound Data . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Page 23 Unit Clearances . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Page 28 Weights . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Page 29 FEATURES AND BENEFITS APPROVALS ETL and CSA listed. Efficiency rating verified by CSA. Components bonded for grounding to meet safety standards for servicing required by UL, ULC and National and Canadian Electrical Codes. 2 thru 5 ton models are certified in accordance with the USE certification program, which is based on AHRI Standard 210/240-2006. 6 ton models are certified in accordance with the ULE certification program, which is based on AHRI Standard 340/360−2007. All models are ASHRAE 90.1 compliant ISO 9001 Registered Manufacturing Quality System. WARRANTY Limited five years on compressors. Limited one year all other covered components. CABINET B Construction C D E Packaged Heat Pump 2 to 6 tons / Page 2 Heavy−gauge steel panels and full perimeter heavy−gauge galvanized steel base rail provides structural integrity for transportation, handling, and installation. Base rails have rigging holes. Three sides of the base rail have fork slots. Raised edges around duct and power entry openings in the bottom of the unit provide additional protection against water entering the building. Air−Flow Choice Units are shipped in down−flow (vertical) configuration, can be field converted to horizontal air flow configuration without the need of a kit. Power Entry Electrical lines can be brought through the unit base or through horizontal access knock−outs. Exterior Panels Constructed of heavy−gauge, galvanized steel with a two−layer enamel paint finish. Insulation All panels adjacent to conditioned air are fully insulated with non−hygroscopic fiberglass insulation. Unit base is fully insulated. The insulation also serves as an air seal to the roof curb, eliminating the need to add a seal during installation. Access Panels Access panels are provided for the economizer/filter section, heating/blower section, and the compressor/controls section. OPTIONS/ACCESSORIES Factory Installed Corrosion Protection A completely flexible immersed coating with an electrodeposited dry film process. (AST ElectroFin E−Coat) Meets Mil Spec MIL−P−53084, ASTM B117 Standard Method Salt Spray Testing, ASTM 1153 Standard Specification for Methyl Isobutyl Ketone. F Hinged Access Panels Large access panels are hinged and have quarter−turn latches for quick and easy access to maintenance areas (economizer / filter, compressor / controls, heating / blower). Field Installed Coil Guards Painted, galvanized steel wire guards to protect outdoor coil. Not used with Hail Guards. Hail Guards Constructed of heavy gauge steel, painted to match cabinet, helps protect outdoor coils from hail damage. Not used with Coil Guards. FEATURES AND BENEFITS B E D K L J H N M I G F C KHA060S (Heat Pump) Shown With Optional Economizer, Power Exhaust and Hinged Access Panels COOLING / HEATING SYSTEM Designed to maximize sensible and latent cooling performance at design conditions. System can operate from 30°F to 125°F without any additional controls. Refrigerant Non−chlorine, ozone friendly R−410A. Unit pre−charged with refrigerant. See Specification table. G Compressor Resiliently mounted on rubber grommets for quiet operation. Scroll compressors for high performance, reliability and quiet operation. J Compressor Crankcase Heater Protects against refrigerant migration that can occur during low ambient operation. High Pressure Switch Protects the compressor from overload conditions such as dirty condenser coils, blocked refrigerant flow, or loss of outdoor fan operation. H Check/Thermal Expansion Valves Assures optimal performance throughout the application range. Removable element head. I Reversing Valves 4-way interchange reversing valve effects a rapid change in direction of refrigerant flow resulting in quick changeover from cooling to heating and vice versa. K Defrost Control Provides a defrost cycle, if needed, every 30 or 60 or 90 minutes (adjustable) of compressor on" time at outdoor coil temperature below 35°F. Temperature switch mounted on outdoor coil liquid line terminates defrost cycle. Filter/Drier High capacity filter/drier protects the system from dirt and moisture. Freezestat Protects the evaporator coil from damaging ice build−up due to conditions such as low/no air flow, or low refrigerant charge. Coil Construction Copper tube construction, enhanced rippled−edge aluminum fins, flared shoulder tubing connections, silver soldered construction for improved heat transfer. Factory leak tested. Indoor Coil Cross row circuiting with rifled copper tubing optimizes both sensible and latent cooling capacity. Outdoor Coil Two independent formed coils allow separation for cleaning. Condensate Drain Pan Plastic pan, sloped to meet drainage requirements of ASHRAE 62.1. Side or bottom drain connections. Reversible to allow connection at back of unit. Outdoor Coil Fan Motor Thermal overload protected, totally enclosed, permanently lubricated sleeve (024, 030, 036 and 048 models) or ball bearings (060 and 072 models), shaft up, wire basket mount. Outdoor Coil Fan PVC coated fan guard furnished. REQUIRED SELECTIONS Cooling Capacity Specify nominal cooling capacity of the unit. OPTIONS/ACCESSORIES Field Installed Condensate Drain Trap Field installed only. Available in copper or PVC. Low Ambient Kit Cycles the outdoor fan while allowing compressor operation in the cooling cycle. This intermittent fan operation allows the system to operate without icing the evaporator coil and losing capacity. Designed for use in ambient temperatures no lower than 0°F. Packaged Heat Pump 2 to 6 tons / Page 3 FEATURES AND BENEFITS CONTROLS Unit Control All control voltage is provided via a 24V (secondary) transformer with built−in circuit breaker protection. Heat/Cool Staging − Capable of up to 2 heat / 2 cool staging with a third party DDC control system or thermostat. Low Voltage Terminal Block − Provides screw terminal connections for thermostat or controller wiring. Night Setback Mode − Saves energy by closing outdoor air dampers and operating supply fan on thermostat demand only. OPTIONS / ACCESSORIES Field Installed Dirty Filter Switch Senses static pressure increase indicating dirty filter condition. Smoke Detector Photoelectric type, installed in supply or return air section. L BLOWER A wide selection of supply air blower options are available to meet a variety of air flow requirements. Motor Overload protected, equipped with ball bearings (belt drive) or sleeve bearings (direct drive). Direct drive motors are offered on 024, 030, 036 and 048 models. Belt drive motors are offered on 036, 048, 060 and 072 models and are available in several different sizes to maximize air performance. Supply Air Blower Forward curved blades, blower wheel is statically and dynamically balanced. All belt drive motors have adjustable pulley for speed change. Ordering Information Specify direct drive or belt drive motor For belt drive, specify motor horsepower and drive kit number when base unit is ordered. Packaged Heat Pump 2 to 6 tons / Page 4 REQUIRED SELECTIONS Supply Air Blower Order one, belt drive or direct drive (See Blower Data Table for specifications). Order one drive kit, belt drive only, see Drive Kit Specifications Table. INDOOR AIR QUALITY Air Filters Disposable 2 inch filters furnished as standard. OPTIONS/ACCESSORIES Field Installed Healthy Climate® UVC Germicidal Lamps Helps eliminate mold and bacterial growth on the evaporator and drain pans. Improves indoor air quality and maintains efficiency of system by reducing fouling of evaporator coil. Indoor Air Quality (CO2) Sensor levels adjusts Monitors CO2 economizer dampers as needed for Demand Control Ventilation. ELECTRICAL REQUIRED SELECTIONS Voltage Choice Specify when ordering base unit. OPTIONS/ACCESSORIES Factory or Field Installed GFI Service Outlets (2) 115v ground fault circuit interrupter (GFCI) type. Field Installed Disconnect Switch up to 150 Amp Accessible from outside of unit, spring loaded weatherproof cover furnished. Main power to the unit is field connected to the disconnect which allows all power to be shut off for service. See Electrical/Electric Heat tables for ordering information, Pages 23−26. Electric Heat Helix wound nichrome elements, individual element limit controls, wiring harness. Unit fuse block furnished as standard. SERVICEABILITY Designed to streamline general maintenance and decrease troubleshooting time. Marked & Color−Coded Wiring All electrical wiring is color−coded and marked to identify which components it is connecting. Electrical Plugs Positive connection electrical plugs are used to connect common accessories or maintenance parts for easy removal or installation. Blower Access Supply air blower parts are located near the access door for easy servicing and adjustment. Thermal Expansion Valves Thermal expansion valves are located near the perimeter of the unit for easier access. Removable element head allows change out of element and bulb without removing the TXV. Coil Cleaning Independently formed condenser coils allow separation for easier cleaning. Compressor Compartment Compressor is located near the perimeter of the unit for easier access. Compressor is isolated from the condenser air flow allowing system operation checks to be done without changing the air flow across the outdoor coils. OPTIONS / ACCESSORIES ECONOMIZER/OUTDOOR AIR/EXHAUST OPTIONS M Factory or Field Installed Economizer, Down−Flow Parallel gear−driven action return air and outdoor air dampers, plug-in connections to unit, nylon bearings, neoprene seals, 24−volt, fully−modulating, spring return motor, adjustable minimum damper position. Economizer includes barometric relief dampers. Barometric Relief Dampers allow relief of excess air, aluminum blade dampers prevent blow back and outdoor air infiltration during off cycle, bird screen furnished. Hood furnished. Outdoor Air Hoods are included when economizer is factory installed and are furnished with economizer when ordered for field installation. Choice of single (factory installed) or differential (optional) enthalpy or temperature economizer control is available. Horizontal conversion kit available for field installation. Single Enthalpy Control Outdoor air enthalpy sensor enables economizer if the outdoor enthalpy is less than the setpoint of the board. Furnished with Economizer. Field Installed Outdoor Air Damper − Manual Two sliding dampers provide 0 to 35% outdoor air, installs internal to unit. Includes Outdoor Air Hood. Outdoor Air Damper Motorized Kit Used to convert Manual Outdoor Air Dampers to motorized dampers. Kit includes linked mechanical dampers and spring return damper motor with plug−in connection. Differential Enthalpy Control An optional, return air, solid-state enthalpy sensor can be ordered extra for field installation. Allows the economizer control board to select between outdoor air or return air, whichever has lower enthalpy. Field installed. Economizer Temperature Control − Single An optional, solid-state temperature sensor can be ordered extra for field installation. Enables the economizer when the outdoor air temperature is below the configured setpoint. N Economizer Temperature Control − Differential Order two single, temperature control kits. One is field installed in the return air section, the other in the outdoor air section. Allows the economizer control board to select between outdoor air or return air, whichever has lower temperature. Horizontal Conversion Kit Insulated panel covers the bottom return air opening on the unit base to convert down−flow economizer to horizontal air flow. Power Exhaust Fan Installs internal to unit for down-flow applications only with economizer option. Provides exhaust air pressure relief. Interlocked to run when supply air blower is operating, fan runs when outdoor air dampers are 50% open (adjustable), motor is overload protected. Requires Economizer with Outdoor Air Hood. Fan is 16 in. diameter with 4 fan blades (T1PWRE10A) or 20 in. diameter with 5 blades (T1PWRE10N). Both include a 3/4 hp motor. NOTE − Not available for 024 and 030 models. CEILING DIFFUSERS Ceiling Diffusers (Flush and Step−Down) Aluminum grilles, large center grille, insulated diffuser box with flanges, hanging rings furnished, interior transition (even air flow), internally sealed (prevents recirculation), adapts to T-bar ceiling grids or plaster ceilings. Transitions (Supply and Return) Used with diffusers, installs in roof curb, galvanized steel construction, flanges furnished for duct connection to diffusers, fully insulated. ROOF CURB Roof Curb, Down−Flow Nailer strip furnished, mates to unit, US National Roofing Contractors Approved, shipped knocked down. Available in 8, 14, 18, and 24 inch heights. Cliplock curbs use interlocking tabs to fasten together. No tools required. Hinged curb corners fasten together with furnished hinge pins. Standard roof curb corners fasten together with furnished hardware. NOTE − 072 models can be used on smaller 79−3/4 in. roof curbs (not full perimeter) with 15−3/4 in. overhang at condenser end of unit. See dimension drawing on page 36. Packaged Heat Pump 2 to 6 tons / Page 5 OPTIONs / ACCESSORIES Catalog No. 024 030 036 048 060 072 PVC − LTACDKP03/07 37K69 x x x x x x Copper − LTACDKC03/07 45K67 x x x x x x K1SNSR33AN1 41W33 x x x x x x Standard R−410A Direct Drive − 0.25 hp Direct Drive − 0.5 hp Belt Drive − 1.5 hp Standard Efficiency 1 Belt Drive − 2 hp Standard Efficiency Drive Kits See Blower Data Tables for selection Kit A01 − T1DRKT001−1 − 673−1010 rpm Drive Kits See Blower Data Tables for selection Kit A03 − T1DRKT003−1 − 833−1250 rpm Item COOLING SYSTEM Condensate Drain Trap Low Ambient Kit Efficiency Refrigerant Type Blower − SUPPLY AIR Motors Kit A02 − T1DRKT002−1 − 745−1117 rpm Kit A04 − T1DRKT004−1 − 968−1340 rpm Kit A05 − T1DRKT005−1 − 897−1346 rpm Kit A06 − T1DRKT006−1 − 1071−1429 rpm Kit A07 − T1DRKT007−1 − 1212−1548 rpm Kit A08 − T1DRKT008−1 − 1193−1591 rpm CABINET Coil Guards T1GARD20A−1 17W87 T1GARD20N−1 17W88 K1GARD20AP1 53W21 Corrosion Protection Hail Guards T1GARD10A−1 17W89 T1GARD10N−1 17W90 K1GARD10AP1 53W22 Hinged Access Panels x x x x x x x x x x x x CONTROLS Dirty Filter Switch COSWCH00AE−1 30K48 x x x x x x T1SNSR41AN1 39W16 x x x x x x Sensor − white case CO2 display C0SNSR50AS1L 77N39 x x x x x x Sensor − duct−mount, black case, no display C0SNSR53AE1L 87N54 x x x x x x C0MISC19AE1− 85L43 x x x x x x E1UVCL10AN1 50W90 x x x x x x Smoke Detector − Supply/Return Indoor Air Quality Indoor Air Quality (Co2) Sensors CO2 Sensor Duct Mounting Kit UVC Germicidal Lamps 2 Healthy Climate® UVC Light Kit (208/230v−1ph) NOTE − The catalog and model numbers that appear here are for ordering field installed accessories only. ⊗ − Field Installed or Configure to Order (factory installed) − Configure to Order (Factory Installed) X − Field Installed 1 2 hp blower motor is not available for 208/230V−1ph applications. 2 Lamps operate on 110−230V single−phase power supply. Step−down transformer may be ordered separately for 460V and 575V units. Alternately, 110V power supply may be used to directly power the UVC ballast(s). Packaged Heat Pump 2 to 6 tons / Page 6 OPTIONs / ACCESSORIES Item Catalog No. 024 030 036 048 f f f f 060 072 f f ECONOMIZER Economizer Economizer, Single Enthalpy Control Includes Outdoor Air Hood and Barometric Relief Dampers with Hood T1ECON30A−1 36W96 T1ECON30N−1 36W97 Horizontal Economizer Conversion Kit T1HECK00AN1 17W45 x x x x x x Differential Enthalpy Sensor T1SNSR60AN1 17W71 x x x x x x Single Temperature Control TASEK10/15 76M37 x x x x x x Order 2 − TASEK10/15 76M37 x x x x x x See Electrical/Electric Heat Tables for selection x x x x x x 208/230V − 1 phase 208/230V − 3 phase 460V − 3 phase 575V − 3 phase x Economizer Controls Differential Temperature Control ELECTRICAL Disconnect Voltage 60 hz GFI Service Outlets LTAGFIK10/15 74M70 x x x x x 208/230V−1ph − T1EH0075AN1P 14W32 x x x x x 208/230V−3ph − T1EH0075AN1Y 14W35 x x x x 460V−3ph − T1EH0075AN1G 14W39 x x x x 575V−3ph − T1EH0075AN1J 14W43 x x x x 10 kW 208/230V−1ph − T1EH0100A1P 30W26 15 kW 208/230V−1ph − T1EH0150AN1P 14W33 x x x 208/230V−3ph − T1EH0150AN1Y 14W36 x x x x 460V−3ph − T1EH0150AN1G 14W40 x x x x 575V−3ph − T1EH0150AN1J 14W44 x x x x 208/230V−1ph − T1EH0225AN1P 14W34 x 208/230V−3ph − T1EH0225AN1Y 14W37 x x 460V−3ph − T1EH0225AN1G 14W41 x x 575V−3ph − T1EH0225AN1J 14W45 x x 208/230V−3ph − T1EH0300N−1Y 14W38 x 460V−3ph − T1EH0300N−1G 14W42 x 575V−3ph − T1EH0300N−1J 14W46 x ELECTRIC HEAT 7.5 kW 22.5 kW 30 kW x x NOTE − The catalog and model numbers that appear here are for ordering field installed accessories only. ⊗ − Field Installed or Configure to Order (factory installed) − Configure to Order (Factory Installed) X − Field Installed. Packaged Heat Pump 2 to 6 tons / Page 7 OPTIONs / ACCESSORIES Catalog No. 024 030 036 048 T1DAMP11A−1 16W88 x x x x T1DAMP11N−1 16W91 T1DAMP21AN1 16W92 208/230V−1 or 3 ph − T1PWRE10A−1P Item 060 072 x x x x OUTDOOR AIR Outdoor Air Dampers Damper Section − Manual, Includes Outdoor Air Hood Damper Motorized Kit Order Manual Outdoor Air Damper Separately x x x x 17W39 x x 460V−3ph − T1PWRE10A−1G 17W40 x x 575V−3ph − T1PWRE10A−1J 17W41 x x 208/230V−1 or 3 ph − T1PWRE10N−1P 17W42 x x 460V−3ph − T1PWRE10N−1G 17W43 x x 575V−3ph − T1PWRE10N−1J 17W44 x x RTD9−65−R 27G87 RTD11−95 29G04 x (Canada Only) RTD11−95S 13K61 x FD9−65−R 27G86 FD11−95 29G08 x (Canada Only) FD11−95S 13K56 x POWER EXHAUST FAN Standard Static CEILING DIFFUSERS Step−Down − Order one Flush − Order one Transitions (Supply and Return) − Order one T1TRAN10AN1 17W53 T1TRAN20N−1 17W54 T1CURB23AN1 16W93 K1CURB23AP1 52W20 x x x x x x x x x x x x x x x x ROOF CURBS − downFlow Cliplock 8 in. height 14 in. height 18 in. height 24 in. height T1CURB20AN1 16W94 K1CURB20AP1 52W21 T1CURB21AN1 16W95 K1CURB21AP1 52W22 T1CURB22AN1 16W96 K1CURB22AP1 52W23 T1CURB30AN1 17W46 K1CURB30AP1 52W17 x x x x x 1 x 1 x 1 x x x x x x x x x x x x x x x x x x x 1 x x Hinged 8 in. height 18 in. height 24 in. height T1CURB32AN1 17W47 K1CURB32AP1 52W18 T1CURB33AN1 17W48 K1CURB33AP1 52W19 T1CURB10AN1 13W27 K1CURB10AP1 52W24 x x x x x 1 x 1 x 1 x x x x x x x x x x x x x x Standard 14 in. height NOTE − The catalog and model numbers that appear here are for ordering field installed accessories only. X − Field Installed. 1 072 models will fit smaller roof curbs with overhang. See dimension drawing. Packaged Heat Pump 2 to 6 tons / Page 8 x x x x x 1 x x SPECIFICATIONS − DIRECT DRIVE BLOWER Nominal Tonnage General Data Model No. Efficiency Type Cooling Performance Gross Cooling Capacity − Btuh 1 Net 2 Cooling Capacity − Btuh 2.5 Ton 3 Ton 4 Ton KHA024S4D KHA030S4D KHA036S4D KHA048S4D Standard Standard Standard Standard 23,600 30,000 37,100 49,000 22,800 29,000 35,600 47,000 AHRI Rated Air Flow − cfm 800 1000 1160 1600 Sound Rating Number (dB) 75 75 75 75 Total Unit Power − kW 1 SEER (Btuh/Watt) 1 EER (Btuh/Watt) Type Refrigerant Charge Furnished Heating Performance 2 − 4 TON 2 Ton Total High Heating Capacity − Btuh Total Unit Power − kW 1 COP 1 HSPF 2.0 2.6 3.3 4.4 13.0 13.0 13.0 13.0 11.2 11.3 10.9 10.7 R−410A R−410A R−410A R−410A 13 lbs. 0 oz. 13 lbs. 0 oz. 12 lbs. 8 oz. 13 lbs. 2 oz. 24,000 29,200 36,400 48,000 2.1 2.5 3.0 4.0 3.4 3.5 3.6 3.5 7.7 (6.7) 7.7 (6.7) 7.7 (6.7) 7.7 (6.7) 14,400 17,600 22,000 29,500 Total Unit Power − kW 1.8 2.3 2.8 3.6 COP 2.3 2.3 2.3 2.4 − Region IV (Region V) Total Low Heating Capacity − Btuh Electric Heating Options See Electrical/Electric Heat Tables Pages 23−26 Compressor Type (no.) Outdoor Coil Scroll (1) Scroll (1) Scroll (1) Scroll (1) Net face area − sq. ft. 15.6 15.6 15.6 15.6 Tube diameter − in. 3/8 3/8 3/8 3/8 Number of rows 2.0 2.0 2.0 2.0 Fins / inch 20 20 20 20 Motor HP 1/4 1/4 1/4 1/4 Motor rpm 825 825 825 825 Total motor watts 250 250 250 250 Diameter − in. / No. of blades 24 − 3 24 − 3 24 − 3 24 − 3 Total air volume − cfm 3300 3300 3300 3300 Net face area − sq. ft. 7.78 7.78 7.78 7.78 Tube diameter − in. Outdoor Coil Fan Indoor Coil 3/8 3/8 3/8 3/8 Number of rows 3 3 3 3 Fins / inch 14 14 14 14 (1) 3/4 NPT (1) 3/4 NPT (1) 3/4 NPT (1) 3/4 NPT Drain Connection (no. and size) − in. Expansion device type Indoor Blower Nominal Motor HP Wheel nom. diameter x width − in. Type Filters Number and size − in. Electrical Characteristics − 60 hz Balanced Port Thermostatic Expansion Valve, removeable power head .25 .25 .5 .5 10 x 10 10 x 10 10 x 10 10 x 10 Disposable Disposable (4) 16 x 20 x 2 (4) 16 x 20 x 2 208/230V − 1 phase 208/230V 1 phase 208/230V 1 phase 208/230V, 460V & 575V 3 phase 208/230V, 460V & 575V 3 phase NOTE − Net capacity includes evaporator blower motor heat deduction. Gross capacity does not include evaporator blower motor heat deduction. 1 Certified in accordance with the USE certification program, which is based on AHRI Standard 210/240. Cooling Ratings − 95°F outdoor air temperature and 80°F db/67°F wb entering indoor coil air. High Temperature Heating Ratings − 47°F db/43°F wb outdoor air temperature and 70°F entering indoor coil air. Low Temperature Heating Ratings − 17°F db/15°F wb outdoor air temperature and 70°F entering indoor coil air. 2 Sound Rating Number rated in accordance with test conditions included in AHRI Standard 270. Packaged Heat Pump 2 to 6 tons / Page 9 SPECIFICATIONS − BELT DRIVE BLOWER Nominal Tonnage Model No. Efficiency Type Gross Cooling Capacity − Btuh Cooling 1 Net Cooling Capacity − Btuh Performance AHRI Rated Air Flow − cfm 4 Sound Rating Number (dB) Total Unit Power − kW 1 SEER (Btuh/Watt) 3 IEER (Btuh/Watt) EER (Btuh/Watt) Type Refrigerant Charge Furnished Total High Heating Capacity − Btuh Heating Performance Total Unit Power − kW 1 COP HSPF − Region IV (Region V) Total Low Heating Capacity − Btuh Total Unit Power − kW 1 COP Electric Heating Options Compressor Type (no.) Net face area − sq. ft. Outdoor Coil Tube diameter − in. Number of rows Fins / inch Motor HP Outdoor Coil Fan Motor rpm Total motor watts Diameter − in. / No. of blades Total air volume − cfm Net face area − sq. ft. Indoor Coil Tube diameter − in. Number of rows Fins / inch Drain Connection (no. and size) − in. Expansion device type 5 Indoor Nominal Motor HP Blower & Maximum Usable Motor HP Drive Selection Available Drive Kits General Data Wheel nom. diameter x width − in. Type Number and size − in. Electrical Characteristics − 60 hz Filters 3 − 6 TON 3 Ton 4 Ton 5 Ton 6 Ton KHA036S4B KHA048S4B KHA060S4B KHA072S4B Standard Standard Standard Standard 37,100 49,000 61,500 71,300 1 35,600 1 47,000 1 59,000 2 69,000 1160 1600 1985 2060 75 75 82 83 3.3 4.4 5.4 6.3 13.0 13.0 13.0 −−− −−− −−− −−− 11.2 1 10.9 1 10.7 1 10.9 2 11.0 R−410A R−410A R−410A R−410A 12 lbs. 8 oz. 13 lbs. 2 oz. 16 lbs. 0 oz. 20 lbs. 8 oz. 36,400 48,000 60,500 70,000 3.0 4.0 4.9 6.2 3.6 3.5 3.6 3.3 7.7 (6.7) 7.7 (6.7) 7.7 (6.7) −−− 22,000 29,500 36,000 40,000 2.8 3.6 4.5 5.7 2.3 2.4 2.4 2.25 See Electrical/Electric Heat Tables Pages 23−26 Scroll (1) Scroll (1) Scroll (1) Scroll (1) 15.6 15.6 19.27 28.00 3/8 3/8 3/8 3/8 2 2 2 2 20 20 20 20 1/4 1/4 1/3 1/2 825 825 1075 1075 250 250 405 680 24 − 3 24 − 3 24 − 3 24 − 4 3300 3300 4800 5735 7.78 7.78 9.7 9.7 3/8 3/8 3/8 3/8 3 3 4 4 14 14 14 14 (1) 3/4 NPT (1) 3/4 NPT (1) 3/4 NPT (1) 3/4 NPT Balanced Port Thermostatic Expansion Valve, removeable power head 1.5 hp, 6 2 hp 1.5 hp, 6 2 hp 1.5 hp, 2 hp 1.72 hp, 1.72 hp, 1.72 hp, 2.3 hp 2.3 hp 2.3 hp A01 A02 A03 A04 673 − 1010 rpm 745 − 1117 rpm 833 − 1250 rpm 968 − 1340 rpm A05 A06 A07 A08 897 − 1346 rpm 1071 − 1429 rpm 1212 − 1548 rpm 1193 − 1591 rpm 10 x 10 10 x 10 10 x 10 10 x 10 Disposable Disposable (4) 16 x 20 x 2 (4) 20 x 20 x 2 208/230V 208/230V 208/230V 208/230V, 1 phase 1 phase 1 phase 460V & 575V 3 phase 208/230V, 208/230V, 208/230V, 460V & 575V 460V & 575V 460V & 575V 3 phase 3 phase 3 phase NOTE − Net capacity includes evaporator blower motor heat deduction. Gross capacity does not include evaporator blower motor heat deduction. 1 Certified in accordance with the USE certification program, which is based on AHRI Standard 210/240 or 2 340/360. Cooling Ratings − 95°F outdoor air temperature and 80°F db/67°F wb entering indoor coil air. High Temperature Heating Ratings − 47°F db/43°F wb outdoor air temperature and 70°F entering indoor coil air. Low Temperature Heating Ratings − 17°F db/15°F wb outdoor air temperature and 70°F entering indoor coil air. 3 Integrated Energy Efficiency Ratio certified and tested according to AHRI Standard 210/240. 4 Sound Rating Number rated in accordance with test conditions included in AHRI Standard 270. 5 Using total air volume and system static pressure requirements determine from blower performance tables rpm and motor hp required. Maximum usable hp of motors furnished are shown. In Canada, nominal motor hp is also maximum usable motor hp. If motors of comparable hp are used, be sure to keep within the service factor limitations outlined on the motor nameplate. 6 2 hp blower motor is not available for 208/230V−1phase applications. Packaged Heat Pump 2 to 6 tons / Page 10 COOLING / HEATING RATINGS NOTE − For Temperatures and Capacities not shown in tables, see bulletin − Cooling Unit Rating Table Correction Factor Data in Miscellaneous Engineering Data section. 2 TON STANDARD EFFICIENCY − COOLING CAPACITY KHA024S4 Outdoor Air Temperature Entering Outdoor Coil Entering Wet Bulb Temperature 63F (17C) 67F (19C) 71F (22C) 85F (29C) Total Air Volume Total Cooling Capacity cfm L/s kBtuh kW 640 800 960 640 800 960 640 800 960 300 380 455 300 380 455 300 380 455 22.4 23.3 24.2 24.0 24.9 25.5 25.7 26.6 27.2 6.6 6.8 7.1 7.0 7.3 7.5 7.5 7.8 8.0 95F (35C) Sensible To Total Ratio (S/T) Dry Bulb Comp Motor kW Input 75F 24C 1.36 .74 1.35 .79 1.36 .85 1.36 .57 1.36 .61 1.36 .64 1.36 .43 1.36 .44 1.36 .46 80F 27C .87 .96 1.00 .70 .76 .83 .56 .59 .63 Total Cooling Capacity 105F (41C) Sensible To Total Ratio (S/T) Dry Bulb Comp Motor kW 85F 75F kBtuh kW Input 29C 24C 1.00 21.2 6.2 1.56 .75 1.00 22.1 6.5 1.56 .81 1.00 23.1 6.8 1.56 .87 .84 22.7 6.7 1.56 .58 .92 23.6 6.9 1.56 .62 .99 24.2 7.1 1.57 .66 .68 24.4 7.2 1.57 .43 .74 25.2 7.4 1.57 .45 .80 25.7 7.5 1.57 .46 80F 27C .90 .98 1.00 .72 .79 .85 .56 .60 .65 Total Cooling Capacity 85F kBtuh kW 29C 1.00 20.0 5.9 1.00 20.9 6.1 1.00 21.9 6.4 .86 21.4 6.3 .94 22.2 6.5 1.00 22.7 6.7 .69 23.0 6.7 .76 23.7 6.9 .83 24.2 7.1 115F (46C) Sensible To Total Ratio (S/T) Dry Bulb Comp Motor kW Input 75F 24C 1.79 .76 1.79 .84 1.79 .90 1.79 .60 1.79 .64 1.79 .68 1.80 .44 1.80 .45 1.80 .47 80F 27C .92 1.00 1.00 .74 .81 .88 .58 .62 .67 Total Cooling Capacity 85F kBtuh kW 29C 1.00 18.7 5.5 1.00 19.7 5.8 1.00 20.7 6.1 .89 20.0 5.9 .98 20.7 6.1 1.00 21.1 6.2 .71 21.5 6.3 .79 22.1 6.5 .86 22.5 6.6 Sensible To Total Comp Ratio (S/T) Motor Dry Bulb kW Input 75F 80F 85F 24C 27C 29C 2.04 .79 .96 1.00 2.04 .87 1.00 1.00 2.04 .94 1.00 1.00 2.04 .61 .76 .92 2.05 .65 .84 1.00 2.05 .70 .92 1.00 2.05 .44 .59 .74 2.06 .46 .64 .82 2.06 .48 .69 .90 2.5 TON STANDARD EFFICIENCY − COOLING CAPACITY KHA030S4 Outdoor Air Temperature Entering Outdoor Coil Entering Wet Bulb Temperature cfm 63F (17C) 67F (19C) 71F (22C) 85F (29C) Total Air Volume 800 1000 1200 800 1000 1200 800 1000 1200 Total Cooling Capacity 95F (35C) Sensible To Total Ratio (S/T) Dry Bulb Comp Motor kW 75F L/s kBtuh kW Input 24C 380 28.4 8.3 1.76 .72 470 29.6 8.7 1.77 .78 565 30.7 9.0 1.77 .84 380 30.4 8.9 1.77 .56 470 31.5 9.2 1.78 .60 565 32.3 9.5 1.78 .63 380 32.6 9.6 1.78 .42 470 33.7 9.9 1.79 .43 565 34.4 10.1 1.79 .45 80F 27C .86 .94 1.00 .69 .75 .81 .54 .58 .62 Total Cooling Capacity 105F (41C) Sensible To Total Ratio (S/T) Dry Bulb Comp Motor kW 85F 75F kBtuh kW Input 29C 24C .99 27.1 7.9 2.01 .73 1.00 28.2 8.3 2.01 .79 1.00 29.4 8.6 2.02 .86 .82 29.0 8.5 2.01 .57 .91 30.0 8.8 2.02 .61 .98 30.7 9.0 2.02 .64 .67 31.0 9.1 2.02 .42 .73 32.0 9.4 2.03 .44 .79 32.7 9.6 2.04 .45 80F 27C .88 .97 1.00 .70 .77 .84 .55 .59 .63 Total Cooling Capacity 85F kBtuh kW 29C 1.00 25.6 7.5 1.00 26.8 7.9 1.00 28.0 8.2 .84 27.4 8.0 .93 28.3 8.3 1.00 28.9 8.5 .68 29.3 8.6 .74 30.2 8.9 .81 30.8 9.0 115F (46C) Sensible To Total Ratio (S/T) Dry Bulb Comp Motor kW Input 75F 24C 2.29 .75 2.29 .82 2.29 .89 2.29 .58 2.29 .62 2.30 .66 2.30 .43 2.30 .44 2.31 .46 80F 27C .91 .99 1.00 .72 .79 .87 .56 .61 .65 Total Cooling Capacity 85F kBtuh kW 29C 1.00 24.0 7.0 1.00 25.2 7.4 1.00 26.5 7.8 .87 25.6 7.5 .97 26.5 7.8 1.00 27.1 7.9 .70 27.5 8.1 .77 28.3 8.3 .84 28.8 8.4 Sensible To Total Comp Ratio (S/T) Motor Dry Bulb kW Input 75F 80F 85F 24C 27C 29C 2.61 .77 .94 1.00 2.61 .85 1.00 1.00 2.61 .92 1.00 1.00 2.61 .59 .75 .91 2.61 .64 .82 1.00 2.62 .68 .90 1.00 2.61 .43 .58 .72 2.62 .45 .62 .80 2.62 .47 .67 .87 2 TON STANDARD EFFICIENCY − HEATING CAPACITY KHA024S4 Air Temperature Entering Outdoor Coil Indoor Coil Air Volume 70F db (21C db) 65F (18C) cfm L/s kBtuh kW 640 800 960 300 380 455 29.2 29.8 30.2 8.6 8.7 8.9 45F (7C) Comp. Motor kW Input 1.85 1.72 1.64 Total Heating Capacity Total Heating Capacity kBtuh kW 22.3 22.9 23.3 6.5 6.7 6.8 25F (−4C) Comp. Motor kW Input 1.67 1.54 1.46 Total Heating Capacity kBtuh kW 15.1 15.7 16.1 4.4 4.6 4.7 5F (−15C) Comp. Motor kW Input 1.49 1.36 1.28 kBtuh kW 10.3 10.9 11.3 3.0 3.2 3.3 −15F (−26C) Comp. Motor kW Input 1.33 1.20 1.12 Total Heating Capacity Total Heating Capacity kBtuh kW 5.0 5.6 6.0 1.5 1.6 1.8 2.5 TON STANDARD EFFICIENCY − HEATING CAPACITY KHA030S4 Air Temperature Entering Outdoor Coil Indoor Coil Air Volume 70F db (21C db) 65F (18C) Total Heating Capacity cfm L/s kBtuh kW 800 1000 1200 380 470 565 35.6 36.2 36.6 10.4 10.6 10.7 45F (7C) Comp. Motor kW Input 2.15 2.00 1.91 Total Heating Capacity kBtuh kW 27.3 27.9 28.3 8.0 8.2 8.3 25F (−4C) Comp. Motor kW Input 2.00 1.86 1.77 2 TON STANDARD EFFICIENCY − KHA024S4 − HEATING PERFORMANCE at 800 cfm Indoor Coil Air Volume *Outdoor Temperature F 65 60 55 50 47 45 40 35 30 25 20 17 15 10 5 0 −5 −10 −15 −20 Comp. Motor kW Input 1.01 .88 .80 C 18 16 13 10 8 7 4 2 −1 −4 −7 −8 −9 −12 −15 −18 −21 −23 −26 −29 Compressor Motor kW Input 1.72 1.68 1.64 1.60 1.57 1.54 1.47 1.39 1.38 1.36 1.34 1.33 1.32 1.28 1.20 1.12 1.04 .96 .88 .80 Total Output kBtuh 29.8 28.2 26.6 25.0 24.0 22.9 20.2 17.4 16.6 15.7 14.9 14.4 13.8 12.2 10.9 9.5 8.2 6.9 5.6 4.3 kW 8.7 8.3 7.8 7.3 7.0 6.7 5.9 5.1 4.9 4.6 4.4 4.2 4.0 3.6 3.2 2.8 2.4 2.0 1.6 1.3 Total Heating Capacity kBtuh kW 18.6 19.2 19.6 5.4 5.6 5.7 5F (−15C) Comp. Motor kW Input 1.85 1.70 1.61 kBtuh kW 12.7 13.3 13.7 3.7 3.9 4.0 −15F (−26C) Comp. Motor kW Input 1.68 1.53 1.44 Total Heating Capacity Total Heating Capacity kBtuh kW 6.3 6.9 7.3 1.8 2.0 2.1 Comp. Motor kW Input 1.26 1.11 1.02 2.5 TON STANDARD EFFICIENCY − KHA030S4 − HEATING PERFORMANCE at 1000 cfm Indoor Coil Air Volume *Outdoor Temperature F 65 60 55 50 47 45 40 35 30 25 20 17 15 10 5 0 −5 −10 −15 −20 C 18 16 13 10 8 7 4 2 −1 −4 −7 −8 −9 −12 −15 −18 −21 −23 −26 −29 Compressor Motor kW Input 2.00 1.97 1.94 1.90 1.88 1.86 1.80 1.73 1.72 1.70 1.69 1.68 1.67 1.64 1.53 1.43 1.32 1.22 1.11 1.01 Total Output kBtuh 36.2 34.2 32.3 30.4 29.2 27.9 24.5 21.2 20.2 19.2 18.2 17.6 16.8 14.9 13.3 11.7 10.1 8.5 6.9 5.3 Packaged Heat Pump 2 to 6 tons / Page 11 kW 10.6 10.0 9.5 8.9 8.6 8.2 7.2 6.2 5.9 5.6 5.3 5.2 4.9 4.4 3.9 3.4 3.0 2.5 2.0 1.6 COOLING / HEATING RATINGS NOTE − For Temperatures and Capacities not shown in tables, see bulletin − Cooling Unit Rating Table Correction Factor Data in Miscellaneous Engineering Data section. 3 TON STANDARD EFFICIENCY − COOLING CAPACITY KHA036S4 Outdoor Air Temperature Entering Outdoor Coil Entering Wet Bulb Temperature 63F (17C) 67F (19C) 71F (22C) 85F (29C) Total Air Volume Total Cooling Capacity cfm L/s kBtuh kW 960 1200 1440 960 1200 1440 960 1200 1440 455 565 680 455 565 680 455 565 680 35.2 36.7 37.9 37.6 39.0 39.9 40.2 41.5 42.4 10.3 10.8 11.1 11.0 11.4 11.7 11.8 12.2 12.4 95F (35C) Sensible To Total Ratio (S/T) Dry Bulb Comp Motor kW Input 75F 24C 2.26 .72 2.27 .78 2.28 .83 2.28 .57 2.28 .60 2.29 .63 2.30 .43 2.31 .44 2.31 .45 80F 27C .86 .93 .99 .70 .75 .81 .55 .58 .62 Total Cooling Capacity 105F (41C) Sensible To Total Ratio (S/T) Dry Bulb Comp Motor kW 85F 75F kBtuh kW Input 29C 24C .98 33.6 9.8 2.57 .74 1.00 34.9 10.2 2.58 .80 1.00 36.3 10.6 2.59 .86 .82 35.8 10.5 2.58 .57 .90 37.1 10.9 2.59 .61 .97 37.9 11.1 2.60 .65 .67 38.3 11.2 2.61 .43 .73 39.5 11.6 2.62 .44 .79 40.3 11.8 2.62 .46 80F 27C .88 .96 1.00 .71 .77 .83 .56 .59 .64 Total Cooling Capacity 85F kBtuh kW 29C 1.00 31.7 9.3 1.00 33.1 9.7 1.00 34.6 10.1 .84 33.9 9.9 .92 35.0 10.3 .99 35.8 10.5 .68 36.3 10.6 .75 37.4 11.0 .81 38.1 11.2 115F (46C) Sensible To Total Ratio (S/T) Dry Bulb Comp Motor kW Input 75F 24C 2.92 .75 2.93 .82 2.94 .88 2.93 .58 2.94 .62 2.95 .66 2.96 .43 2.97 .45 2.98 .46 80F 27C .91 .98 1.00 .73 .79 .86 .57 .61 .65 Total Cooling Capacity Sensible To Total Comp Ratio (S/T) Motor Dry Bulb kW 85F 75F 80F 85F Input kBtuh kW 29C 24C 27C 29C 1.00 29.8 8.7 3.33 .78 .93 1.00 1.00 31.2 9.1 3.34 .85 1.00 1.00 1.00 32.7 9.6 3.34 .91 1.00 1.00 .87 31.8 9.3 3.34 .60 .75 .90 .95 32.8 9.6 3.35 .64 .82 .98 1.00 33.5 9.8 3.36 .68 .89 1.00 .70 34.0 10.0 3.36 .44 .58 .73 .77 35.0 10.3 3.37 .45 .63 .80 .84 35.6 10.4 3.38 .47 .67 .87 4 TON STANDARD EFFICIENCY − COOLING CAPACITY KHA048S4 Outdoor Air Temperature Entering Outdoor Coil Entering Wet Bulb Temperature 63F (17C) 67F (19C) 71F (22C) 85F (29C) Total Air Volume Total Cooling Capacity cfm L/s kBtuh kW 1280 1600 1920 1280 1600 1920 1280 1600 1920 605 755 905 605 755 905 605 755 905 47.0 48.8 50.5 50.1 51.7 52.9 53.4 55.0 56.1 13.8 14.3 14.8 14.7 15.2 15.5 15.6 16.1 16.4 95F (35C) Sensible To Total Ratio (S/T) Dry Bulb Comp Motor kW Input 75F 24C 3.08 .70 3.09 .75 3.09 .82 3.09 .55 3.10 .58 3.11 .61 3.11 .41 3.11 .42 3.12 .43 80F 27C .84 .93 .99 .67 .73 .79 .53 .57 .60 Total Cooling Capacity 105F (41C) Sensible To Total Ratio (S/T) Dry Bulb Comp Motor kW 85F 75F kBtuh kW Input 29C 24C .99 44.7 13.1 3.51 .71 1.00 46.4 13.6 3.53 .78 1.00 48.3 14.2 3.53 .84 .81 47.5 13.9 3.54 .56 .89 49.0 14.4 3.55 .59 .97 50.1 14.7 3.56 .63 .65 50.7 14.9 3.56 .41 .71 52.2 15.3 3.57 .42 .77 53.1 15.6 3.58 .44 80F 27C .87 .96 1.00 .69 .75 .82 .54 .58 .62 Total Cooling Capacity 85F kBtuh kW 29C 1.00 42.3 12.4 1.00 44.0 12.9 1.00 45.9 13.5 .83 45.0 13.2 .92 46.3 13.6 .99 47.3 13.9 .67 47.9 14.0 .73 49.2 14.4 .79 50.1 14.7 115F (46C) Sensible To Total Ratio (S/T) Dry Bulb Comp Motor kW Input 75F 24C 3.98 .73 4.00 .80 4.02 .87 4.01 .57 4.03 .60 4.04 .64 4.05 .42 4.07 .43 4.08 .45 80F 27C .90 .98 1.00 .71 .78 .85 .55 .59 .63 Total Cooling Capacity 85F kBtuh kW 29C 1.00 39.7 11.6 1.00 41.5 12.2 1.00 43.3 12.7 .86 42.1 12.3 .95 43.4 12.7 1.00 44.3 13.0 .69 45.0 13.2 .75 46.1 13.5 .83 46.8 13.7 Sensible To Total Comp Ratio (S/T) Motor Dry Bulb kW Input 75F 80F 85F 24C 27C 29C 4.53 .75 .93 1.00 4.54 .83 1.00 1.00 4.57 .91 1.00 1.00 4.55 .58 .73 .90 4.57 .62 .81 .99 4.59 .66 .88 1.00 4.59 .42 .56 .71 4.61 .44 .61 .78 4.62 .46 .66 .86 3 TON STANDARD EFFICIENCY − HEATING CAPACITY KHA036S4 Air Temperature Entering Outdoor Coil Indoor Coil Air Volume 70F db (21C db) 65F (18C) cfm L/s kBtuh kW 960 1200 1440 455 565 680 44.3 45.3 46.1 13.0 13.3 13.5 45F (7C) Comp. Motor kW Input 2.62 2.45 2.34 Total Heating Capacity Total Heating Capacity kBtuh kW 33.6 34.6 35.4 9.8 10.1 10.4 25F (−4C) Comp. Motor kW Input 2.44 2.27 2.17 Total Heating Capacity kBtuh kW 22.2 23.2 24.0 6.5 6.8 7.0 5F (−15C) Comp. Motor kW Input 2.26 2.09 1.98 kBtuh kW 15.7 16.7 17.5 4.6 4.9 5.1 −15F (−26C) Comp. Motor kW Input 2.05 1.88 1.77 Total Heating Capacity Total Heating Capacity kBtuh kW 7.7 8.7 9.5 2.3 2.5 2.8 4 TON STANDARD EFFICIENCY − HEATING CAPACITY KHA048S4 Air Temperature Entering Outdoor Coil Indoor Coil Air Volume 70F db (21C db) 65F (18C) Total Heating Capacity cfm L/s kBtuh kW 1280 1600 1920 605 755 905 58.0 59.1 60.1 17.0 17.3 17.6 45F (7C) Comp. Motor kW Input 3.58 3.36 3.23 Total Heating Capacity kBtuh kW 44.2 45.3 46.3 13.0 13.3 13.6 25F (−4C) Comp. Motor kW Input 3.30 3.08 2.95 3 TON STANDARD EFFICIENCY − KHA036S4 − HEATING PERFORMANCE at 1200 cfm Indoor Coil Air Volume *Outdoor Temperature F 65 60 55 50 47 45 40 35 30 25 20 17 15 10 5 0 −5 −10 −15 −20 Comp. Motor kW Input 1.54 1.37 1.26 C 18 16 13 10 8 7 4 2 −1 −4 −7 −8 −9 −12 −15 −18 −21 −23 −26 −29 Compressor Motor kW Input 2.45 2.41 2.37 2.33 2.30 2.27 2.20 2.12 2.11 2.09 2.07 2.06 2.05 2.01 1.88 1.75 1.62 1.49 1.37 1.24 Packaged Heat Pump 2 to 6 tons / Page 12 Total Output kBtuh 45.3 42.9 40.4 38.0 36.6 34.6 29.6 24.6 23.9 23.2 22.5 22.1 21.2 18.8 16.7 14.7 12.7 10.7 8.7 6.6 kW 13.3 12.6 11.8 11.1 10.7 10.1 8.7 7.2 7.0 6.8 6.6 6.5 6.2 5.5 4.9 4.3 3.7 3.1 2.5 1.9 Total Heating Capacity kBtuh kW 29.3 30.4 31.4 8.6 8.9 9.2 5F (−15C) Comp. Motor kW Input 3.00 2.78 2.65 kBtuh kW 21.4 22.5 23.5 6.3 6.6 6.9 −15F (−26C) Comp. Motor kW Input 2.69 2.47 2.34 Total Heating Capacity Total Heating Capacity kBtuh kW 10.5 11.6 12.6 3.1 3.4 3.7 Comp. Motor kW Input 2.02 1.80 1.67 4 TON STANDARD EFFICIENCY − KHA048S4 − HEATING PERFORMANCE at 1600 cfm Indoor Coil Air Volume *Outdoor Temperature F 65 60 55 50 47 45 40 35 30 25 20 17 15 10 5 0 −5 −10 −15 −20 C 18 16 13 10 8 7 4 2 −1 −4 −7 −8 −9 −12 −15 −18 −21 −23 −26 −29 Compressor Motor kW Input 3.36 3.29 3.23 3.16 3.12 3.08 2.97 2.85 2.82 2.78 2.75 2.73 2.70 2.64 2.47 2.30 2.14 1.97 1.80 1.64 Total Output kBtuh 59.1 56.0 52.9 49.9 48.0 45.3 38.4 31.5 30.9 30.4 29.8 29.5 28.3 25.2 22.5 19.7 17.0 14.3 11.6 8.9 kW 17.3 16.4 15.5 14.6 14.1 13.3 11.3 9.2 9.1 8.9 8.7 8.6 8.3 7.4 6.6 5.8 5.0 4.2 3.4 2.6 COOLING / HEATING RATINGS NOTE − For Temperatures and Capacities not shown in tables, see bulletin − Cooling Unit Rating Table Correction Factor Data in Miscellaneous Engineering Data section. 5 TON STANDARD EFFICIENCY − COOLING CAPACITY KHA060S4 Outdoor Air Temperature Entering Outdoor Coil Entering Wet Bulb Temperature cfm 63F (17C) 67F (19C) 71F (22C) 85F (29C) Total Air Volume Total Cooling Capacity L/s kBtuh kW 1600 755 2000 945 2400 1135 1600 755 2000 945 2400 1135 1600 755 2000 945 2400 1135 58.8 61.2 63.4 62.7 65.0 66.6 67.1 69.2 70.7 17.2 17.9 18.6 18.4 19.0 19.5 19.7 20.3 20.7 95F (35C) Sensible To Total Ratio (S/T) Dry Bulb Comp Motor kW Input 75F 24C 3.72 .70 3.75 .76 3.77 .82 3.77 .55 3.79 .58 3.81 .62 3.82 .41 3.84 .43 3.86 .44 80F 27C .84 .93 1.00 .68 .73 .80 .53 .57 .61 Total Cooling Capacity 105F (41C) Sensible To Total Ratio (S/T) Dry Bulb Comp Motor kW 85F 75F kBtuh kW Input 29C 24C .98 55.8 16.4 4.22 .72 1.00 58.1 17.0 4.24 .78 1.00 60.5 17.7 4.27 .85 .81 59.5 17.4 4.26 .56 .89 61.5 18.0 4.28 .60 .97 62.9 18.4 4.30 .63 .65 63.6 18.6 4.31 .42 .71 65.5 19.2 4.34 .43 .77 66.8 19.6 4.36 .45 80F 27C .87 .96 1.00 .69 .76 .82 .54 .58 .62 Total Cooling Capacity 85F kBtuh kW 29C 1.00 52.6 15.4 1.00 54.8 16.1 1.00 57.4 16.8 .83 56.0 16.4 .92 57.8 16.9 .99 59.1 17.3 .67 59.9 17.6 .73 61.6 18.1 .80 62.7 18.4 115F (46C) Sensible To Total Ratio (S/T) Dry Bulb Comp Motor kW Input 75F 24C 4.78 .74 4.81 .81 4.83 .88 4.82 .57 4.85 .61 4.87 .65 4.88 .42 4.90 .44 4.92 .45 80F 27C .90 .99 1.00 .71 .78 .85 .55 .60 .64 Total Cooling Capacity 85F kBtuh kW 29C 1.00 49.1 14.4 1.00 51.5 15.1 1.00 53.9 15.8 .86 52.2 15.3 .96 53.9 15.8 1.00 55.0 16.1 .69 55.8 16.4 .76 57.3 16.8 .83 58.3 17.1 Sensible To Total Comp Ratio (S/T) Motor Dry Bulb kW Input 75F 80F 85F 24C 27C 29C 5.44 .76 .93 1.00 5.47 .84 1.00 1.00 5.49 .91 1.00 1.00 5.48 .58 .74 .90 5.50 .63 .81 .99 5.52 .67 .89 1.00 5.53 .43 .57 .71 5.55 .44 .62 .79 5.57 .46 .67 .87 6 TON STANDARD EFFICIENCY − COOLING CAPACITY KHA072S4 Outdoor Air Temperature Entering Outdoor Coil Entering Wet Bulb Temperature cfm 63F (17C) 67F (19C) 71F (22C) 85F (29C) Total Air Volume 1920 2400 2880 1920 2400 2880 1920 2400 2880 Total Cooling Capacity L/s kBtuh kW 905 1135 1360 905 1135 1360 905 1135 1360 69.4 73.0 75.9 73.7 77.2 79.7 78.1 81.6 84.2 20.3 21.4 22.2 21.6 22.6 23.4 22.9 23.9 24.7 95F (35C) Sensible To Total Ratio (S/T) Dry Bulb Comp Motor kW Input 75F 24C 4.53 .71 4.53 .76 4.54 .82 4.54 .56 4.54 .59 4.55 .62 4.54 .42 4.55 .43 4.55 .45 80F 27C .86 .95 1.00 .69 .73 .80 .54 .58 .61 Total Cooling Capacity 105F (41C) Sensible To Total Ratio (S/T) Dry Bulb Comp Motor kW 85F 75F kBtuh kW Input 29C 24C 1.00 66.2 19.4 5.03 .72 1.00 69.5 20.4 5.04 .78 1.00 72.8 21.3 5.04 .85 .82 70.2 20.6 5.03 .57 .90 73.5 21.5 5.04 .60 .98 75.8 22.2 5.05 .63 .66 74.6 21.9 5.04 .42 .71 77.8 22.8 5.05 .44 .77 80.4 23.6 5.05 .46 80F 27C .88 .97 1.00 .70 .76 .82 .55 .59 .62 Total Cooling Capacity 85F kBtuh kW 29C 1.00 62.6 18.3 1.00 65.8 19.3 1.00 69.3 20.3 .85 66.5 19.5 .94 69.5 20.4 1.00 71.6 21.0 .68 70.4 20.6 .73 73.6 21.6 .79 75.8 22.2 115F (46C) Sensible To Total Ratio (S/T) Dry Bulb Comp Motor kW Input 75F 24C 5.60 .74 5.60 .81 5.60 .88 5.60 .58 5.60 .62 5.61 .65 5.60 .43 5.61 .45 5.61 .46 80F 27C .91 1.00 1.00 .72 .78 .85 .56 .60 .64 Total Cooling Capacity 85F kBtuh kW 29C 1.00 58.7 17.2 1.00 62.2 18.2 1.00 65.4 19.2 .87 62.3 18.3 .97 64.9 19.0 1.00 66.9 19.6 .69 66.0 19.3 .75 68.9 20.2 .82 70.9 20.8 Sensible To Total Comp Ratio (S/T) Motor Dry Bulb kW Input 75F 80F 85F 24C 27C 29C 6.23 .77 .96 1.00 6.24 .84 1.00 1.00 6.24 .92 1.00 1.00 6.24 .59 .74 .91 6.24 .63 .82 1.00 6.24 .67 .89 1.00 6.24 .44 .57 .72 6.25 .45 .62 .79 6.24 .47 .66 .86 5 TON STANDARD EFFICIENCY − HEATING CAPACITY KHA060S4 Air Temperature Entering Outdoor Coil Indoor Coil Air Volume 70F db (21C db) 65F (18C) cfm L/s kBtuh kW 1600 2000 2400 755 945 1135 74.6 76.0 77.5 21.9 22.3 22.7 45F (7C) Comp. Motor kW Input 4.19 3.92 3.75 Total Heating Capacity Total Heating Capacity kBtuh kW 56.5 57.9 59.4 16.6 17.0 17.4 25F (−4C) Comp. Motor kW Input 3.92 3.65 3.48 Total Heating Capacity kBtuh kW 37.4 38.8 40.3 11.0 11.4 11.8 5F (−15C) Comp. Motor kW Input 3.65 3.38 3.21 kBtuh kW 25.7 27.1 28.6 7.5 7.9 8.4 −15F (−26C) Comp. Motor kW Input 3.24 2.97 2.80 Total Heating Capacity Total Heating Capacity kBtuh kW 12.7 14.1 15.6 3.7 4.1 4.6 6 TON STANDARD EFFICIENCY − HEATING CAPACITY KHA072S4 Air Temperature Entering Outdoor Coil Indoor Coil Air Volume 70F db (21C db) 65F (18C) Total Heating Capacity cfm L/s kBtuh kW 1920 2400 2880 905 1135 1360 87.4 89.7 91.3 25.6 26.3 26.8 45F (7C) Comp. Motor kW Input 5.55 5.25 5.07 Total Heating Capacity kBtuh kW 66.5 68.9 70.5 19.5 20.2 20.7 25F (−4C) Comp. Motor kW Input 4.89 4.59 4.41 5 TON STANDARD EFFICIENCY − KHA060S4 − HEATING PERFORMANCE at 2000 cfm Indoor Coil Air Volume *Outdoor Temperature F 65 60 55 50 47 45 40 35 30 25 20 17 15 10 5 0 −5 −10 −15 −20 Comp. Motor kW Input 2.43 2.16 1.99 C 18 16 13 10 8 7 4 2 −1 −4 −7 −8 −9 −12 −15 −18 −21 −23 −26 −29 Compressor Motor kW Input 3.92 3.85 3.78 3.71 3.67 3.65 3.58 3.51 3.44 3.38 3.31 3.27 3.24 3.17 2.97 2.77 2.57 2.37 2.16 1.96 Total Output kBtuh 76.0 71.9 67.7 63.5 61.1 57.9 50.1 42.2 40.5 38.8 37.1 36.1 34.5 30.3 27.1 23.8 20.6 17.3 14.1 10.8 kW 22.3 21.1 19.8 18.6 17.9 17.0 14.7 12.4 11.9 11.4 10.9 10.6 10.1 8.9 7.9 7.0 6.0 5.1 4.1 3.2 Total Heating Capacity kBtuh kW 45.3 47.7 49.3 13.3 14.0 14.4 5F (−15C) Comp. Motor kW Input 4.18 3.88 3.70 kBtuh kW 27.8 30.1 31.7 8.1 8.8 9.3 −15F (−26C) Comp. Motor kW Input 3.70 3.40 3.21 Total Heating Capacity Total Heating Capacity kBtuh kW 13.5 15.8 17.4 4.0 4.6 5.1 Comp. Motor kW Input 2.82 2.52 2.33 6 TON STANDARD EFFICIENCY − KHA072S4 − HEATING PERFORMANCE at 2400 cfm Indoor Coil Air Volume *Outdoor Temperature F 65 60 55 50 47 45 40 35 30 25 20 17 15 10 5 0 −5 −10 −15 −20 C 18 16 13 10 8 7 4 2 −1 −4 −7 −8 −9 −12 −15 −18 −21 −23 −26 −29 Compressor Motor kW Input 5.25 5.11 4.96 4.81 4.72 4.59 4.27 3.96 3.92 3.88 3.85 3.83 3.77 3.62 3.40 3.18 2.96 2.74 2.52 2.30 Total Output kBtuh 89.7 84.6 79.5 74.5 71.4 68.9 62.5 56.2 51.9 47.7 43.4 40.8 38.8 33.7 30.1 26.5 23.0 19.4 15.8 12.2 Packaged Heat Pump 2 to 6 tons / Page 13 kW 26.3 24.8 23.3 21.8 20.9 20.2 18.3 16.5 15.2 14.0 12.7 12.0 11.4 9.9 8.8 7.8 6.7 5.7 4.6 3.6 BLOWER DATA − DIRECT DRIVE 2 − 2.5 TON Blower tables include resistance for base unit with wet indoor coil & 2 in. disposable air filters in place. FOR ALL UNITS ADD: 1 − Any factory installed options air resistance (economizer, etc.) See page 22. 2 − Any field installed accessories air resistance (electric heat, duct resistance, diffuser, etc.) See page 22. External Static Pressure (in. w.g.) 208 VOLTS High Medium 2 and 2.5 Ton Standard Efficiency (Downflow) Air Volume (cfm) at Various Blower Speeds 230 VOLTS Low High Medium Low KHA024S and KHA030S 0.0 1230 975 845 1425 1125 910 0.1 1220 940 815 1395 1110 875 0.2 1205 910 775 1375 1085 845 0.3 1185 880 730 1350 1055 815 0.4 1155 845 680 1320 1010 780 0.5 1115 800 −−− 1280 955 740 0.6 1060 750 −−− 1225 895 690 0.7 985 685 −−− 1150 830 −−− 0.8 890 −−− −−− 1050 755 −−− 0.9 770 −−− −−− 920 680 −−− 1.0 −−− −−− −−− 760 −−− −−− 2 and 2.5 Ton Standard Efficiency (Horizontal) KHA024S and KHA030S 0.0 1165 925 800 1350 1065 865 0.1 1155 895 770 1325 1055 830 0.2 1140 865 735 1300 1030 800 0.3 1125 835 695 1280 1000 770 0.4 1095 800 645 1250 955 740 0.5 1055 760 −−− 1215 905 700 0.6 1005 710 −−− 1160 850 655 0.7 935 650 −−− 1090 785 −−− 0.8 845 −−− −−− 995 720 −−− 0.9 730 −−− −−− 875 645 −−− 1.0 −−− −−− −−− 720 −−− −−− Packaged Heat Pump 2 to 6 tons / Page 14 BLOWER DATA − DIRECT DRIVE 3 − 4 TON Blower tables include resistance for base unit with wet indoor coil & 2 in. disposable air filters in place. FOR ALL UNITS ADD: 1 − Any factory installed options air resistance (economizer, etc.) See page 22. 2 − Any field installed accessories air resistance (electric heat, duct resistance, diffuser, etc.) See page 22. External Static Pressure (in. w.g.) 208 VOLTS High Medium Low 3 and 4 Ton Standard Efficiency (Downflow) Air Volume (cfm) at Various Blower Speeds 230 VOLTS 460/575 VOLTS High Medium Low High Medium Low KHA036S and KHA048S 0.0 1990 1625 1145 2175 1825 1330 2100 1735 1220 0.1 1935 1595 1145 2100 1790 1320 2050 1705 1215 0.2 1885 1565 1130 2040 1755 1300 2000 1665 1205 0.3 1830 1530 1095 1980 1710 1265 1945 1625 1180 0.4 1775 1485 1050 1915 1660 1215 1885 1575 1145 0.5 1710 1425 980 1850 1595 1150 1815 1520 1095 0.6 1630 1350 900 1765 1510 1070 1735 1450 1025 0.7 1540 1255 800 1660 1405 975 1640 1375 940 0.8 1425 1140 −−− 1535 1280 −−− 1530 1285 −−− 0.9 1285 1000 −−− 1375 1120 −−− 1405 1185 −−− 1.0 1125 −−− −−− 1180 −−− −−− 1260 −−− −−− 3 and 4 Ton Standard Efficiency (Horizontal) KHA036S and KHA048S 0.0 1890 1545 1090 2060 1740 1265 2085 1745 1260 0.1 1830 1515 1090 1990 1700 1255 2020 1700 1240 0.2 1780 1480 1070 1930 1660 1230 1960 1660 1225 0.3 1730 1445 1040 1870 1615 1200 1900 1620 1205 0.4 1675 1400 995 1810 1565 1150 1835 1575 1170 0.5 1610 1340 930 1740 1500 1090 1760 1515 1115 0.6 1530 1260 845 1650 1410 1010 1680 1440 1035 0.7 1420 1160 745 1535 1295 905 1580 1340 915 0.8 1290 1025 −−− 1385 1150 −−− 1460 1210 −−− 0.9 1120 865 −−− 1195 965 −−− 1320 1045 −−− 1.0 910 −−− −−− 960 −−− −−− 1155 −−− −−− Packaged Heat Pump 2 to 6 tons / Page 15 BLOWER DATA − BELT DRIVE 3 TON Blower tables include resistance for base unit with wet indoor coil & 2 in. disposable air filters in place. FOR ALL UNITS ADD: 1 − Any factory installed options air resistance (economizer, etc.) See page 22 2 − Any field installed accessories air resistance (electric heat, duct resistance, diffuser, etc.) See page 22 Then determine from table the blower motor output and drive required. 0.10 to 1.00 in. w.g. Air Volume 0.10 0.20 (cfm) RPM BHP RPM BHP Field Furnished 900 485 0.10 595 0.15 1000 520 0.10 615 0.20 1100 550 0.15 640 0.20 3 Ton Standard Efficiency (Downflow) External Static (in.w.g.) 0.30 0.40 0.50 0.60 RPM BHP RPM BHP RPM BHP RPM BHP Low Static − Drive Kit A01 690 0.20 780 0.30 860 0.40 930 0.50 705 0.25 790 0.35 870 0.45 945 0.55 725 0.30 805 0.35 885 0.45 955 0.55 KHA036S 0.70 RPM BHP 1000 1010 0.60 0.65 0.80 RPM BHP Kit A05 1065 0.75 1075 0.75 1200 585 0.20 665 0.25 745 0.30 825 0.40 900 0.50 965 0.60 1020 1030 0.70 0.70 1085 1095 0.80 0.85 1300 1400 620 660 0.20 0.25 695 730 0.30 0.35 770 795 0.35 0.40 845 865 0.45 0.50 915 935 0.55 0.60 980 995 0.65 0.70 1045 1060 0.75 0.80 1105 1120 0.90 0.95 1500 695 0.30 760 0.40 825 0.45 890 0.55 955 0.65 1015 0.75 1075 0.85 1135 1.00 0.90 to 1.60 in. w.g. Air Volume 0.90 (cfm) RPM BHP High Static 900 1125 0.85 1000 1130 0.90 1100 1140 0.90 3 Ton Standard Efficiency (Downflow) External Static (in.w.g.) 1.0 1.10 1.20 1.30 RPM BHP RPM BHP RPM BHP RPM BHP − Drive Kit A05 1180 1.00 1230 1.10 1285 1.25 1330 1.35 1190 1.00 1240 1.15 1295 1.30 1340 1.40 1200 1.05 1250 1.20 1300 1.35 1350 1.50 1200 1150 0.95 1210 1.10 1300 1165 1.00 1220 1.15 1400 1175 1.05 1230 1.20 1500 1190 1.15 1240 1.25 0.10 to 0.80 in. w.g. Air Volume 0.10 0.20 (cfm) RPM BHP RPM BHP Field Furnished 900 480 0.10 570 0.15 1000 520 0.15 595 0.15 KHA036S 1.40 1.50 RPM BHP RPM BHP Field Furnished 1380 1.50 1425 1.65 1390 1.60 1435 1.75 1400 1.65 1260 1.25 1310 1.40 1360 1.55 1410 1.70 1270 1.30 1320 1.45 1370 1.60 1415 1.75 1280 1.35 1330 1.50 1380 1.65 1425 1.80 1295 1.40 1345 1.55 1390 1.70 1435 1.90 3 Ton Standard Efficiency (Horizontal) External Static (in.w.g.) 0.30 0.40 0.50 0.60 RPM BHP RPM BHP RPM BHP RPM BHP Low Static − Drive Kit A01 655 0.20 735 0.30 810 0.35 875 0.45 1445 1455 1465 1470 1480 1.60 RPM BHP 1465 1475 1.80 1.85 1.80 1.85 1.90 1.95 2.05 1485 1.95 1495 2.00 1505 2.05 1515 2.15 1525 2.20 KHA036S 0.70 RPM BHP 0.80 RPM BHP 940 0.55 1000 0.65 675 0.25 750 0.30 820 0.40 890 0.50 950 0.60 1010 0.70 960 975 0.60 0.65 1020 1030 0.75 0.75 1100 1200 1300 555 595 635 0.15 0.20 0.25 625 660 0.20 0.25 695 725 0.25 0.30 765 790 0.35 0.40 835 850 0.45 0.45 900 915 0.50 0.55 690 0.30 750 0.35 810 0.40 870 0.50 930 0.60 990 0.70 1045 0.80 1400 675 0.30 730 0.35 785 0.40 840 0.50 895 0.55 950 0.65 1005 0.75 1060 0.85 1500 720 0.35 765 0.40 815 0.45 870 0.55 920 0.60 970 0.70 1025 0.80 1075 0.95 0.90 to 1.60 in. w.g. Air Volume 0.90 (cfm) RPM BHP High Static 900 1055 0.75 1000 1065 0.80 1100 1075 0.85 3 Ton Standard Efficiency (Horizontal) External Static (in.w.g.) 1.0 1.10 1.20 1.30 RPM BHP RPM BHP RPM BHP RPM BHP − Drive Kit A05 1105 0.90 1155 1.00 1200 1.10 1245 1.25 1115 0.90 1165 1.05 1210 1.15 1255 1.30 1125 0.95 1175 1.10 1220 1.20 1265 1.35 KHA036S 1.40 RPM BHP 1.50 RPM BHP 1285 1300 1310 1.35 1.40 1.50 1325 1340 1.50 1.55 1.60 RPM BHP Field 1365 1.60 1380 1.70 1.60 1.70 1.75 1.80 1395 1405 1415 1425 1.75 1.85 1.90 1.95 1.85 1435 2.05 1200 1300 1400 1085 1095 1110 0.90 0.95 1.00 1135 1145 1160 1.00 1.05 1.10 1185 1195 1210 1.15 1.20 1.25 1235 1245 1255 1.25 1.30 1.40 1280 1290 1300 1.40 1.45 1.50 1320 1330 1340 1.55 1.60 1.65 1350 1365 1375 1385 1500 1125 1.05 1175 1.15 1220 1.30 1265 1.45 1310 1.60 1355 1.75 1395 Packaged Heat Pump 2 to 6 tons / Page 16 BLOWER DATA − BELT DRIVE 4 TON Blower tables include resistance for base unit with wet indoor coil & 2 in. disposable air filters in place. FOR ALL UNITS ADD: 1 − Any factory installed options air resistance (economizer, etc.) See page 22 2 − Any field installed accessories air resistance (electric heat, duct resistance, diffuser, etc.) See page 22 Then determine from table the blower motor output and drive required. 0.10 to 0.80 in. w.g. 4 Ton Standard Efficiency (Downflow) External Static (in.w.g.) Air Volume 0.10 0.20 0.30 0.40 0.50 0.60 (cfm) RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP Field Furnished Low Static − Drive Kit A02 1200 580 0.15 665 0.20 740 0.30 820 0.35 890 0.45 955 0.53 1300 620 0.20 690 0.25 765 0.30 835 0.40 905 0.48 970 0.58 1400 655 0.25 725 0.30 795 0.35 860 0.45 925 0.53 990 0.63 1500 690 0.28 755 0.35 820 0.40 884 0.50 945 0.58 1005 0.68 1600 730 0.33 790 0.40 850 0.48 910 0.55 970 0.65 1025 0.73 1700 765 0.40 825 0.48 880 0.53 935 0.60 995 0.70 1050 0.80 1800 805 0.48 860 0.53 910 0.60 970 0.70 1020 0.80 1075 0.88 1900 845 0.53 895 0.63 945 0.68 995 0.78 1050 0.85 1100 0.95 2000 885 0.63 930 0.68 980 0.78 1030 0.88 1080 0.95 1125 1.05 0.90 to 1.60 in. w.g. 4 Ton Standard Efficiency (Downflow) Air External Static (in.w.g.) Volume 0.90 1.00 1.10 1.20 1.30 1.40 (cfm) RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP High Static − Drive Kit A06 1200 1135 0.83 1190 0.95 1240 1.05 1290 1.20 1335 1.30 1380 1.43 1300 1145 0.88 1200 1.00 1250 1.10 1300 1.25 1350 1.38 1395 1.50 1400 1160 0.93 1215 1.05 1265 1.18 1310 1.30 1360 1.43 1405 1.57 1500 1175 0.98 1225 1.10 1275 1.25 1325 1.35 1370 1.50 1415 1.63 1600 1190 1.08 1240 1.18 1290 1.30 1340 1.45 1385 1.55 1430 1.70 1700 1205 1.13 1260 1.25 1305 1.38 1355 1.50 1400 1.65 1440 1.78 1800 1225 1.23 1275 1.33 1320 1.45 1370 1.60 1415 1.75 1455 1.85 1900 1245 1.28 1290 1.43 1340 1.55 1385 1.70 1425 1.80 1470 1.95 2000 1270 1.38 1315 1.53 1355 1.65 1400 1.78 1445 1.93 1485 2.05 0.10 to 0.80 in. w.g. 4 Ton Standard Efficiency (Horizontal) External Static (in.w.g.) Air Volume 0.10 0.20 0.30 0.40 0.50 0.60 (cfm) RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP Field Furnished Low Static − Drive Kit A02 1200 590 0.18 655 0.20 720 0.25 780 0.35 845 0.40 905 0.50 1300 630 0.20 685 0.25 745 0.30 805 0.38 865 0.45 925 0.52 1400 675 0.25 725 0.30 780 0.35 835 0.43 890 0.50 945 0.53 1500 715 0.33 760 0.35 810 0.40 860 0.50 914 0.55 965 0.63 1600 755 0.38 800 0.43 845 0.48 895 0.55 940 0.60 990 0.70 1700 795 0.45 835 0.50 880 0.55 925 0.63 970 0.70 1015 0.78 1800 840 0.53 875 0.58 915 0.63 960 0.70 1000 0.78 1045 0.85 1900 880 0.63 920 0.68 955 0.73 995 0.80 1035 0.88 1075 0.95 2000 925 0.73 960 0.78 995 0.83 1030 0.90 1070 0.98 1105 1.05 0.90 to 1.60 in. w.g. Air Volume 0.90 (cfm) RPM BHP Kit A02 1200 1070 0.75 1300 1085 0.80 1400 1100 0.85 1500 1115 0.90 1600 1130 0.98 1700 1150 1.05 1800 1170 1.13 1900 1195 1.23 2000 1220 1.33 1.0 RPM BHP High Static 1120 0.85 1135 0.90 1145 0.98 1160 1.03 1175 1.08 1195 1.15 1215 1.23 1235 1.33 1260 1.43 4 Ton Standard Efficiency (Horizontal) External Static (in.w.g.) 1.10 1.20 1.30 RPM BHP RPM BHP RPM BHP − Drive Kit A06 1170 0.98 1215 1.08 1255 1.18 1180 1.00 1225 1.13 1270 1.23 1195 1.08 1240 1.18 1280 1.28 1205 1.13 1250 1.23 1295 1.35 1220 1.18 1265 1.33 1305 1.43 1240 1.28 1280 1.38 1320 1.50 1255 1.35 1300 1.48 1340 1.58 1275 1.43 1315 1.55 1355 1.68 1300 1.53 1340 1.68 1375 1.78 KHA048S 0.70 RPM BHP 0.80 RPM BHP 1020 1035 1050 1065 1085 1105 1125 1150 1175 1080 1090 1105 1120 1140 1155 1175 1200 1220 0.63 0.68 0.73 0.78 0.83 0.90 0.98 1.08 1.15 0.73 0.78 0.83 0.88 0.93 1.03 1.08 1.18 1.28 KHA048S 1.50 RPM BHP 1425 1440 1450 1460 1470 1485 1500 1510 1525 1.58 1.63 1.68 1.78 1.83 1.93 2.03 2.10 2.20 1.60 RPM BHP Field 1470 1.70 1480 1.78 1490 1.83 1500 1.93 1515 2.00 1525 2.08 1540 2.18 1555 2.28 1565 2.38 KHA048S 0.70 RPM BHP 0.80 RPM BHP 965 980 995 1015 1040 1060 1085 1115 1145 1020 1034 1050 1065 1085 1105 1130 1155 1180 0.58 0.60 0.65 0.73 0.80 0.85 0.93 1.03 1.13 0.68 0.70 0.75 0.80 0.88 0.95 1.03 1.13 1.23 KHA048S 1.40 RPM BHP 1.50 RPM BHP 1.60 RPM BHP 1300 1310 1324 1335 1350 1365 1380 1395 1415 1340 1350 1365 1375 1390 1400 1415 1435 1450 1380 1390 1405 1415 1425 1440 1455 1470 1485 1.30 1.35 1.43 1.48 1.55 1.63 1.73 1.78 1.93 1.40 1.48 1.53 1.63 1.68 1.75 1.83 1.93 2.03 Packaged Heat Pump 2 to 6 tons / Page 17 1.55 1.60 1.68 1.73 1.80 1.88 1.98 2.08 2.18 BLOWER DATA − BELT DRIVE 5 TON Blower tables include resistance for base unit with wet indoor coil, & 2 in. disposable air filters in place. FOR ALL UNITS ADD: 1 − Any factory installed options air resistance (larger gas heat section, economizer, etc.) See page 22 2 − Any field installed accessories air resistance (duct resistance, diffuser, etc.) See page 22 Then determine from table the blower motor output and drive required. 0.10 to 0.80 in. w.g. 5 Ton Standard Efficiency (Downflow) Air Volume (cfm) KHA060S External Static (in.w.g.) 0.10 RPM BHP 0.20 RPM BHP 0.30 RPM BHP Field Furnished 0.40 RPM BHP 0.50 RPM BHP 0.60 RPM 0.70 0.80 BHP RPM BHP RPM BHP Low Static − Drive Kit A03 1600 675 0.30 730 0.35 785 0.40 835 0.45 885 0.50 935 0.60 985 0.65 1030 0.70 1700 710 0.35 760 0.40 815 0.45 860 0.50 910 0.60 960 0.65 1005 0.70 1050 0.80 1800 745 0.45 795 0.50 845 0.55 890 0.60 935 0.65 980 0.70 1025 0.80 1070 0.85 1900 780 0.50 830 0.55 875 0.60 920 0.65 965 0.75 1010 0.80 1050 0.85 1090 0.95 2000 820 0.60 865 0.65 905 0.70 950 0.75 990 0.80 1035 0.90 1075 0.95 1115 1.05 2100 855 0.65 900 0.70 940 0.80 980 0.85 1020 0.90 1060 1.00 1100 1.05 1140 1.15 2200 890 0.75 935 0.80 970 0.85 1010 0.95 1050 1.00 1090 1.10 1130 1.15 1165 1.25 2300 930 0.85 970 0.90 1005 1.00 1045 1.05 1080 1.10 1120 1.20 1155 1.25 1190 1.35 2400 965 0.95 1005 1.05 1040 1.10 1075 1.15 1115 1.25 1150 1.30 1185 1.40 1220 1.50 0.90 to 1.60 in. w.g. Air Volume (cfm) 5 Ton Standard Efficiency (Downflow) KHA060S External Static (in.w.g.) 0.90 RPM BHP 1.00 RPM BHP 1.10 RPM BHP 1.20 RPM BHP 1.30 RPM BHP Low Static − Drive Kit A03 1.40 RPM BHP 1.50 RPM BHP 1.60 RPM BHP High Static − Drive Kit A07 1600 1075 0.80 1120 0.85 1160 0.95 1200 1.05 1240 1.10 1280 1.20 1320 1.30 1355 1.35 1700 1090 0.85 1135 0.95 1175 1.00 1215 1.10 1255 1.20 1295 1.30 1330 1.35 1365 1.45 1800 1110 0.95 1155 1.00 1195 1.10 1230 1.20 1270 1.25 1310 1.35 1345 1.45 1380 1.55 1900 1135 1.05 1170 1.10 1210 1.20 1250 1.25 1285 1.35 1325 1.45 1360 1.55 1395 1.65 2000 1155 1.10 1195 1.20 1230 1.30 1270 1.35 1305 1.45 1340 1.55 1375 1.65 1410 1.75 2100 1180 1.20 1215 1.30 1250 1.40 1290 1.45 1325 1.55 1360 1.65 1395 1.75 1425 1.85 2200 1200 1.30 1240 1.40 1275 1.50 1310 1.60 1345 1.70 1380 1.80 1410 1.85 1445 1.95 2300 1225 1.45 1260 1.50 1295 1.60 1330 1.70 1365 1.80 1400 1.90 1430 2.00 1465 2.10 2400 1255 1.55 1285 1.65 1320 1.75 1355 1.85 1385 1.90 1420 2.05 1450 2.10 1480 2.20 Packaged Heat Pump 2 to 6 tons / Page 18 BLOWER DATA − BELT DRIVE 5 TON Blower tables include resistance for base unit with wet indoor coil, & 2 in. disposable air filters in place. FOR ALL UNITS ADD: 1 − Any factory installed options air resistance (larger gas heat section, economizer, etc.) See page 22 2 − Any field installed accessories air resistance (duct resistance, diffuser, etc.) See page 22 Then determine from table the blower motor output and drive required. 0.10 to 0.80 in. w.g. 5 Ton Standard Efficiency (Horizontal) Air Volume (cfm) KHA060S External Static (in.w.g.) 0.10 RPM BHP Field 0.20 RPM BHP 0.30 RPM BHP 0.40 RPM 0.50 0.60 0.70 0.80 BHP RPM BHP RPM BHP RPM BHP RPM BHP Low Static − Drive Kit A03 1600 785 0.40 845 0.45 900 0.50 955 0.55 1010 0.65 1060 0.70 1110 0.80 1160 0.90 1700 825 0.45 880 0.50 935 0.60 990 0.65 1040 0.70 1090 0.80 1135 0.85 1185 0.95 1800 865 0.50 920 0.60 975 0.65 1020 0.75 1070 0.80 1120 0.90 1165 0.95 1210 1.05 1900 910 0.60 960 0.70 1010 0.75 1060 0.85 1105 0.90 1150 1.00 1195 1.05 1240 1.15 2000 950 0.70 1000 0.80 1050 0.85 1095 0.95 1140 1.00 1185 1.10 1225 1.15 1265 1.25 2100 995 0.80 1040 0.90 1085 0.95 1130 1.05 1175 1.15 1215 1.20 1260 1.30 1300 1.40 2200 1040 0.95 1085 1.00 1125 1.10 1170 1.15 1210 1.25 1250 1.35 1290 1.40 1330 1.50 2300 1080 1.05 1125 1.15 1165 1.20 1205 1.30 1245 1.40 1285 1.45 1325 1.55 1360 1.65 2400 1125 1.20 1165 1.25 1205 1.35 1245 1.45 1285 1.55 1320 1.60 1360 1.70 1395 1.80 0.90 to 1.60 in. w.g. Air Volume (cfm) 5 Ton Standard Efficiency (Horizontal) KHA060S External Static (in.w.g.) 0.90 RPM BHP 1.00 RPM BHP 1.10 RPM BHP 1.20 RPM 1.30 1.40 1.50 1.60 BHP RPM BHP RPM BHP RPM BHP RPM BHP Drive Kit A03 High Static − Drive Kit A07 1600 1210 0.95 1255 1.05 1305 1.15 1350 1.30 1395 1.40 1440 1.55 1485 1.65 1530 1.80 1700 1230 1.05 1275 1.15 1320 1.25 1365 1.35 1410 1.45 1455 1.60 1495 1.70 1540 1.85 1800 1255 1.15 1300 1.25 1340 1.35 1385 1.45 1425 1.55 1470 1.70 1510 1.80 1550 1.95 1900 1280 1.25 1325 1.35 1365 1.45 1405 1.55 1445 1.65 1485 1.75 1525 1.90 1565 2.00 2000 1310 1.35 1350 1.45 1390 1.55 1430 1.65 1470 1.75 1505 1.85 1545 2.00 1585 2.15 2100 1340 1.50 1375 1.55 1415 1.65 1455 1.80 1490 1.90 1530 2.00 1565 2.10 1605 2.25 2200 1370 1.60 1405 1.70 1445 1.80 1480 1.90 1515 2.00 1555 2.15 1590 2.25 1625 2.40 2300 1400 1.75 1435 1.85 1470 1.95 1510 2.05 1545 2.20 1580 2.30 1615 2.40 1650 2.55 2400 1430 1.90 1465 2.00 1505 2.15 1535 2.20 1570 2.35 1605 2.45 1640 2.60 1675 2.70 Packaged Heat Pump 2 to 6 tons / Page 19 BLOWER DATA − BELT DRIVE 6 TON Blower tables include resistance for base unit with wet indoor coil & 2 in. disposable air filters in place. FOR ALL UNITS ADD: 1 − Any factory installed options air resistance (economizer, etc.) See page 22. 2 − Any field installed accessories air resistance (electric heat, duct resistance, diffuser, etc.) See page 22. Then determine from table the blower motor output and drive required. 0.10 to 0.80 in. w.g. Air Volume (cfm) 6 Ton Standard Efficiency (Downflow) KHA072S External Static (in.w.g.) 0.10 RPM BHP 0.20 RPM BHP 0.30 RPM BHP 0.40 RPM BHP 0.50 RPM BHP Field Furnished 0.60 RPM BHP 0.70 RPM 0.80 BHP RPM BHP Low Static − Drive Kit A04 1900 752 0.48 803 0.53 855 0.58 903 0.62 957 0.72 1008 0.78 1066 0.88 1118 0.92 2000 793 0.52 845 0.62 892 0.68 940 0.73 990 0.77 1041 0.88 1093 0.93 1144 1.03 2100 838 0.64 881 0.68 929 0.73 978 0.83 1023 0.88 1073 0.93 1124 1.03 1169 1.14 2200 880 0.73 923 0.78 966 0.84 1015 0.93 1061 0.99 1104 1.03 1149 1.13 1198 1.24 2300 921 0.83 966 0.89 1009 0.93 1053 0.99 1097 1.09 1139 1.15 1183 1.25 1220 1.35 2400 964 0.94 1007 0.99 1046 1.05 1089 1.14 1127 1.19 1168 1.29 1211 1.35 1247 1.45 2500 1006 1.05 1044 1.09 1087 1.14 1124 1.25 1160 1.30 1201 1.40 1238 1.51 1274 1.56 2600 1047 1.15 1085 1.20 1121 1.30 1157 1.36 1197 1.46 1234 1.56 1269 1.62 1304 1.72 2700 1094 1.31 1124 1.37 1159 1.41 1195 1.52 1229 1.62 1265 1.67 1295 1.77 1330 1.88 2800 1133 1.42 1162 1.52 1196 1.57 1226 1.67 1260 1.73 1295 1.83 1325 1.94 1360 2.04 2900 1170 1.58 1204 1.68 1232 1.73 1261 1.84 1290 1.89 1326 2.00 1356 2.09 1386 2.19 0.90 to 1.60 in. w.g. Air Volume (cfm) 6 Ton Standard Efficiency (Downflow) KHA072S External Static (in.w.g.) 0.90 RPM BHP 1.00 RPM BHP 1.10 1.20 1.30 1.40 1.50 1.60 RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP High Static − Kit A08 1900 1170 1.03 1216 1.12 1261 1.23 1299 1.28 1338 1.39 1381 1.49 1423 1.59 1462 1.69 2000 1190 1.13 1238 1.18 1279 1.28 1317 1.39 1356 1.49 1397 1.59 1434 1.69 1476 1.80 2100 1213 1.19 1261 1.29 1300 1.39 1339 1.49 1373 1.60 1414 1.70 1449 1.79 1490 1.90 2200 1241 1.30 1282 1.39 1316 1.50 1355 1.60 1394 1.70 1429 1.79 1463 1.90 1498 1.99 2300 1263 1.39 1303 1.50 1337 1.60 1376 1.70 1409 1.80 1444 1.90 1483 2.04 1517 2.14 2400 1289 1.55 1323 1.61 1362 1.76 1397 1.86 1430 1.96 1464 2.05 1498 2.15 1532 2.25 2500 1314 1.66 1349 1.76 1383 1.87 1416 1.96 1451 2.06 1484 2.15 1517 2.24 1545 2.34 2600 1340 1.82 1374 1.92 1408 2.02 1438 2.12 1471 2.21 1505 2.30 1532 2.39 1565 2.49 2700 1365 1.98 1399 2.08 1429 2.12 1463 2.27 1497 2.36 1525 2.45 1558 2.55 1585 2.63 2800 1390 2.08 1425 2.24 1454 2.27 1488 2.42 1517 2.51 1545 2.60 1578 2.69 1605 2.84 2900 1421 2.28 1451 2.39 1480 2.47 1514 2.57 1543 2.65 1570 2.75 1597 2.89 1625 2.99 Note − BOLD − to operate in this range, 3 hp blower motor is required. Packaged Heat Pump 2 to 6 tons / Page 20 BLOWER DATA − BELT DRIVE 6 TON Blower tables include resistance for base unit with wet indoor coil, & 2 in. disposable air filters in place. FOR ALL UNITS ADD: 1 − Any factory installed options air resistance (economizer, etc.) See page 22. 2 − Any field installed accessories air resistance (electric heat, duct resistance, diffuser, etc.) See page 22. Then determine from table the blower motor output and drive required. 0.10 to 0.80 in. w.g. Air Volume (cfm) 6 Ton Standard Efficiency (Horizontal) KHA072S External Static (in.w.g.) 0.10 RPM 0.20 BHP Field RPM BHP 0.30 RPM 0.40 BHP 0.50 RPM BHP 0.60 RPM BHP RPM BHP 0.70 0.80 RPM BHP RPM BHP Low Static − Drive Kit A04 1900 919 0.60 969 0.65 1020 0.74 1065 0.79 1111 0.83 1154 0.93 1194 0.99 1232 1.04 2000 962 0.70 1013 0.75 1058 0.84 1103 0.90 1148 0.94 1186 1.04 1226 1.09 1264 1.15 2100 1010 0.80 1056 0.85 1101 0.95 1146 0.99 1185 1.05 1223 1.15 1262 1.20 1296 1.30 2200 1054 0.91 1099 0.95 1143 1.06 1183 1.10 1222 1.21 1261 1.25 1295 1.36 1333 1.41 2300 1102 1.01 1142 1.11 1182 1.16 1220 1.26 1258 1.31 1297 1.42 1330 1.46 1364 1.57 2400 1146 1.16 1184 1.21 1224 1.32 1262 1.37 1300 1.47 1333 1.58 1367 1.63 1401 1.72 2500 1188 1.27 1227 1.38 1265 1.48 1303 1.53 1336 1.63 1370 1.73 1404 1.79 1438 1.88 2600 1235 1.44 1273 1.55 1306 1.65 1339 1.70 1378 1.79 1407 1.89 1441 1.99 1475 2.03 2700 1276 1.61 1314 1.71 1347 1.81 1380 1.91 1414 2.00 1449 2.05 1478 2.14 1512 2.23 2800 1321 1.82 1354 1.92 1388 1.97 1421 2.07 1456 2.16 1485 2.25 1519 2.34 1549 2.44 2900 1367 2.03 1400 2.08 1429 2.17 1463 2.27 1497 2.36 1526 2.45 1556 2.54 1586 2.63 0.90 to 1.60 in. w.g. Air Volume (cfm) 6 Ton Standard Efficiency (Horizontal) KHA072S External Static (in.w.g.) 0.90 RPM 1.00 BHP RPM BHP Drive Kit A04 1.10 RPM 1.20 BHP RPM 1.30 BHP 1.40 1.50 1.60 RPM BHP RPM BHP RPM BHP RPM BHP High Static − Kit A08 1900 1271 1.13 1310 1.18 1345 1.24 1380 1.34 1421 1.39 1458 1.50 1493 1.60 1524 1.65 2000 1303 1.24 1337 1.29 1371 1.40 1412 1.45 1448 1.55 1485 1.61 1516 1.70 1551 1.75 2100 1335 1.36 1370 1.45 1404 1.50 1439 1.60 1476 1.65 1512 1.76 1544 1.81 1579 1.90 2200 1367 1.51 1401 1.56 1436 1.66 1472 1.71 1503 1.81 1540 1.91 1570 1.96 1606 2.06 2300 1398 1.62 1433 1.71 1468 1.81 1503 1.86 1535 1.97 1567 2.02 1603 2.11 1633 2.21 2400 1436 1.78 1470 1.87 1501 1.96 1535 2.01 1567 2.12 1600 2.22 1630 2.27 1660 2.36 2500 1473 1.98 1503 2.03 1533 2.12 1568 2.21 1599 2.27 1631 2.37 1662 2.47 1693 2.57 2600 1505 2.13 1539 2.23 1570 2.32 1600 2.37 1632 2.47 1664 2.57 1694 2.67 1725 2.77 2700 1542 2.33 1572 2.37 1607 2.47 1638 2.57 1664 2.67 1696 2.77 1726 2.87 1757 2.97 2800 1579 2.53 1609 2.58 1640 2.68 1670 2.77 1701 2.87 1732 2.96 1758 3.07 1789 3.16 2900 1616 2.73 1646 2.83 1676 2.92 1708 3.02 1733 3.06 1764 3.17 1794 3.31 1821 3.37 Note − BOLD − to operate in this range, 3 hp blower motor is required. BLOWER DATA BELT DRIVE KIT SPECIFICATIONS − 036−072 Motor hp Nominal Maximum Drive A01 Drive A02 1.5 1.72 2 2.3 673 − 1010 745 − 1117 Drive A03 RPM Range Drive A04 Drive A05 833 − 1250 968 − 1340 897 − 1346 Drive A06 Drive A07 Drive A08 1071 − 1429 1212 − 1548 1193 − 1591 *Using total air volume and system static pressure requirements determine from blower performance tables rpm and motor hp required. Maximum usable hp of motors furnished are shown. In Canada, nominal motor hp is also maximum usable motor hp. If motors of comparable hp are used, be sure to keep within the service factor limitations outlined on the motor nameplate. Packaged Heat Pump 2 to 6 tons / Page 21 BLOWER DATA POWER EXHAUST FANS PERFORMANCE Return Air System Air Volume Exhausted − cfm Static Pressure T1PWRE10A in. w.g. 208V 230V, 460V and 575V 208V Low Medium High Low Medium High Low Medium 1290 1300 1320 1300 1305 1295 3545 3915 0 0.1 1045 1055 1055 1040 1050 1055 2880 3215 0.2 805 805 815 805 810 810 2290 2665 0.3 580 580 600 595 590 585 1735 2175 0.4 390 405 400 405 400 410 1165 1660 0.5 245 315 215 240 255 300 530 1045 0.6 155 340 35 90 165 290 −−− 250 0.7 145 515 −−− −−− 140 400 −−− −−− OPTIONS / ACCESSORIES AIR RESISTANCE − in. w.g. Air Volume cfm 800 1000 1200 1400 1600 1800 2000 2200 2400 2600 2800 3000 CEILING DIFFUSERS AIR RESISTANCE (in. w.g.) RTD9−65 Step-Down Diffuser Air Volume 2 Ends 1 Side & All Ends & cfm Open 2 Ends Open Sides Open 800 0.15 0.13 0.11 1000 0.19 0.16 0.14 1200 0.25 0.20 0.17 1400 0.33 0.26 0.20 1600 0.43 0.32 0.20 1800 0.56 0.40 0.30 2000 0.73 0.50 0.36 2200 0.95 0.63 0.44 2400 −−− −−−− −−− 2600 −−− −−−− −−− 2800 −−− −−−− −−− 3000 −−− −−−− −−− CEILING DIFFUSER AIR THROW DATA 1 Effective Throw − ft. Air Volume − cfm Model No. RTD9−65 FD9−65 800 10 − 17 14 − 18 1000 10 − 17 15 − 20 1200 11 − 18 16 − 22 1400 12 − 19 17 − 24 1600 12 − 20 18 − 25 1800 13 − 21 20 − 28 2000 14 − 23 21 − 29 2200 16 − 25 22 − 30 Model No. RTD11−95 FD11−95 2600 24 − 29 19 − 24 2800 25 − 30 20 − 28 3000 27 − 33 21 − 29 1 Effective throw based on terminal velocities of 75 ft. per minute. Packaged Heat Pump 2 to 6 tons / Page 22 T1PWRE10N 230V, 460V and 575V High Low Medium High 4230 3880 4135 4340 3580 3255 3550 3755 3055 2710 3010 3240 2605 2200 2500 2770 2175 1685 2010 2325 1710 1120 1510 1885 1160 470 990 1420 470 −−− 430 915 Economizer Electric Heat 0.04 0.04 0.04 0.04 0.04 0.05 0.05 0.05 0.05 0.06 0.06 0.06 0.01 0.03 0.06 0.09 0.12 0.15 0.18 0.20 0.22 0.24 0.26 0.28 FD9−65 Flush Diffuser 0.11 0.14 0.17 0.20 0.24 0.30 0.36 0.44 −−− −−− −−− −−− RTD11−95 Step-Down Diffuser 2 Ends 1 Side & All Ends & Open 2 Ends Open Sides Open −−− −−− −−− −−− −−− −−− −−− −−− −−− −−− −−− −−− −−− −−− −−− 0.13 0.11 0.09 0.15 0.13 0.11 0.18 0.15 0.12 0.21 0.18 0.15 0.24 0.21 0.18 0.27 0.24 0.21 0.32 0.29 0.25 FD11−95 Flush Diffuser −−− −−− −−− −−− −−− 0.09 0.10 0.12 0.14 0.17 0.20 0.25 OUTDOOR SOUND DATA 1 Unit Model No. 125 250 500 1000 2000 4000 8000 Sound Rating Number (dB) Cooling 63 66 70 71 68 62 53 75 Heating 63 66 71 70 68 62 54 75 Operating Mode 024, 030, 036 and 048 060 072 Octave Band Sound Power Levels dBA, re 10−12 Watts Center Frequency − HZ Cooling 67 72 77 76 73 68 61 82 Heating 70 72 77 76 73 69 60 82 Cooling 67 75 78 78 75 68 59 83 Heating 69 77 79 80 76 69 61 84 NOTE − The octave sound power data shown does not include tonal correction. 1 Tested according to AHRI Standard 270-95 test conditions and ANSI Standard S1.32-1981. ELECTRICAL DATA 2 − 2.5 TON DIRECT DRIVE BLOWER KHA024S 1 Voltage − 60hz Compressor 1 Outdoor Fan Motors (1) Rated Load Amps Locked Rotor Amps Full Load Amps (total) Service Outlet 115V GFI Indoor Blower Motor 2 Horsepower Full Load Amps Unit Only 3 Unit Only Maximum Overcurrent Protection Minimum Circuit Ampacity KHA030S 208/230V − 1 Ph 13.5 58.3 1.7 208/230V − 1 Ph 14.1 73 1.7 15 Amps .25 1.8 30 15 Amps .25 1.8 35 21 22 ELECTRIC HEAT DATA 2 Maximum Overcurrent Protection 3 Minimum Circuit Ampacity Electric Heat Voltage Unit + 7.5 kW Electric Heat 10 kW 208 60 240 60 208 60 240 70 70 80 70 80 Unit + 7.5 kW Electric Heat 10 kW 55 60 55 61 66 73 67 74 20W15 20W21 20W15 20W21 20W15 20W21 20W15 20W21 ELECTRICAL ACCESSORIES Disconnect Kit 1 2 3 Standard Access − 0−10 kW Hinged Access − 0−10 kW Extremesofoperatingrangeareplusandminus10%oflinevoltage. HACR type breaker or fuse. RefertoNational or CanadianElectricalCodemanualtodeterminewire,fuseanddisconnectsizerequirements. Packaged Heat Pump 2 to 6 tons / Page 23 ELECTRICAL DATA 3 TON KHA036S 1 Voltage − 60hz Compressor 1 208/230V − 1 Ph 208/230V − 3 Ph 460V − 3 Ph Rated Load Amps 575V − 3 Ph 16.7 10.4 5.8 3.8 Locked Rotor Amps 79 73 38 36.5 Outdoor Fan Motors (1) Full Load Amps (total) 1.7 1.7 1.1 0.7 Power Exhaust (1) 0.75 HP Full Load Amps (total) 5 5 2.2 1.5 Service Outlet 115V GFI Indoor Blower Motor 15 Amps 15 Amps 1.5 .5 1.5 2 .5 1.5 2 .5 1.5 2 Full Load Amps 3.9 11 3.9 6.6 7.5 2 3 3.4 2 2.4 2.7 Unit Only 40 50 25 30 30 15 15 15 15 15 15 with (1) 0.75 HP Power Exhaust 45 50 30 35 35 15 15 15 15 15 15 Unit Only 27 34 19 22 23 11 12 12 8 8 9 with (1) 0.75 HP Power Exhaust 32 39 24 27 28 13 14 14 9 10 10 3 Minimum Circuit Ampacity 15 Amps .5 2 Maximum Overcurrent Protection 15 Amps Horsepower ELECTRIC HEAT DATA Electric Heat Voltage 208 240 208 240 208 240 208 240 208 240 480 480 480 600 600 600 2 Maximum Overcurrent Protection Unit + 7.5 kW 70 70 70 80 Electric Heat 15 kW 100 110 110 125 40 45 45 45 45 50 25 25 25 20 20 20 60 70 70 70 70 70 35 35 35 30 30 30 3 Unit + 7.5 kW 61 Electric Heat 15 kW 95 73 39 42 41 44 42 45 22 23 24 17 17 18 105 102 112 58 64 61 67 62 68 33 34 35 26 26 27 Maximum Overcurrent Protection Unit + 7.5 kW 70 80 80 80 Electric Heat and (1) 0.75 HP 15 kW 100 110 110 125 Power Exhaust 45 50 50 50 50 50 25 25 30 20 20 20 70 70 70 80 70 80 40 40 40 30 30 30 3 Unit + 7.5 kW 66 71 73 78 Electric Heat and (1) 0.75 HP 15 kW 100 110 107 117 Power Exhaust 44 47 46 49 47 50 24 25 26 18 19 19 63 69 66 72 67 73 36 37 37 27 28 28 Minimum Circuit Ampacity 2 Minimum Circuit Ampacity 66 68 ELECTRICAL ACCESSORIES Disconnect Kit 1 2 3 Standard Access − 0−7.5 kW 20W15 20W15 20W15 20W15 20W15 20W15 20W15 15 kW 20W16 20W16 20W15 20W15 20W15 20W15 20W15 Hinged Access − 0−7.5 kW 20W21 20W21 20W21 20W21 20W21 20W21 20W21 15 kW 20W22 20W22 20W21 20W21 20W21 20W21 20W21 Extremesofoperatingrangeareplusandminus10%oflinevoltage. HACR type breaker or fuse. RefertoNational or CanadianElectricalCodemanualtodeterminewire,fuseanddisconnectsizerequirements. Packaged Heat Pump 2 to 6 tons / Page 24 ELECTRICAL DATA 4 TON KHA048S 1 Voltage − 60hz Compressor 1 208/230V − 1 Ph 208/230V − 3 Ph 460V − 3 Ph 575V − 3 Ph Rated Load Amps 21.8 13.7 6.2 4.8 Locked Rotor Amps 117 83.1 41 33 Outdoor Fan Motors (1) Full Load Amps (total) 1.7 1.7 1.1 0.7 Power Exhaust (1) 0.75 HP Full Load Amps (total) 5 5 2.2 1.5 15 Amps 15 Amps 15 Amps 15 Amps Service Outlet 115V GFI Indoor Blower Motor Horsepower .5 1.5 .5 1.5 2 .5 1.5 2 .5 1.5 2 Full Load Amps 3.9 11 3.9 6.6 7.5 2 3 3.4 2 2.4 2.7 Unit Only 50 60 35 35 40 15 15 15 15 15 15 with (1) 0.75 HP Power Exhaust 50 60 40 40 45 15 20 20 15 15 15 Unit Only 33 40 23 26 27 11 12 13 9 10 10 with (1) 0.75 HP Power Exhaust 38 45 28 31 32 14 15 15 11 11 11 480 480 480 600 600 600 2 Maximum Overcurrent Protection 3 Minimum Circuit Ampacity ELECTRIC HEAT DATA Electric Heat Voltage 208 240 208 240 208 240 208 240 208 240 2 Maximum Overcurrent Protection Unit + 7.5 kW 80 80 80 90 Electric Heat 15 kW 110 125 110 125 50 50 50 50 50 50 25 25 25 20 20 20 70 70 70 80 70 80 35 35 35 30 30 30 3 Unit + 7.5 kW 67 72 74 80 Electric Heat 15 kW 101 111 108 119 43 46 45 48 46 49 23 24 24 18 19 19 62 68 65 71 66 72 34 35 35 27 28 28 Maximum Overcurrent Protection Unit + 7.5 kW 80 90 90 90 Electric Heat and (1) 0.75 HP 15 kW 110 125 125 125 Power Exhaust 50 60 50 60 60 60 25 30 30 20 20 20 70 80 70 80 80 80 40 40 40 30 30 30 3 Unit + 7.5 kW 72 77 79 85 Electric Heat and (1) 0.75 HP 15 kW 106 116 113 124 Power Exhaust 48 51 50 53 51 54 25 26 26 20 20 20 67 73 70 76 71 77 36 37 38 29 29 29 Minimum Circuit Ampacity 2 Minimum Circuit Ampacity ELECTRICAL ACCESSORIES Disconnect Kit 1 2 3 Standard Access − 0−7.5 kW 20W15 20W16 20W15 20W15 20W15 20W15 20W15 15 kW 20W16 20W16 20W15 20W15 20W15 20W15 20W15 Hinged Access − 0−7.5 kW 20W21 20W22 20W21 20W21 20W21 20W21 20W21 15 kW 20W22 20W22 20W21 20W21 20W21 20W21 20W21 Extremesofoperatingrangeareplusandminus10%oflinevoltage. HACR type breaker or fuse. RefertoNational or CanadianElectricalCodemanualtodeterminewire,fuseanddisconnectsizerequirements. Packaged Heat Pump 2 to 6 tons / Page 25 ELECTRICAL/ELECTRIC HEAT DATA 5 TON KHA060S 1 Voltage − 60hz Compressor 1 Outdoor Fan Motors (1) Power Exhaust (1) 0.75 HP Rated Load Amps Locked Rotor Amps Full Load Amps (total) 208/230V − 1 Ph 26.3 134 2.4 208/230V − 3 Ph 15.6 110 2.4 460V − 3 Ph 7.8 52 1.3 575V − 3 Ph 5.8 38.9 1 Full Load Amps (total) 5 5 2.2 1.5 15 Amps 1.5 11 70 70 15 Amps 1.5 6.6 40 45 2 7.5 45 45 15 Amps 1.5 2 3 3.4 20 20 20 20 15 Amps 1.5 2 2.4 2.7 15 15 15 15 47 52 29 34 30 35 15 17 15 17 11 13 11 13 480 30 40 50 26 37 48 30 40 60 28 39 51 480 30 40 50 26 38 49 30 40 60 28 40 51 600 20 30 40 20 29 38 25 35 40 22 31 40 600 20 30 40 20 29 39 25 35 40 22 31 40 Service Outlet 115V GFI Indoor Blower Motor 2 Maximum Overcurrent Protection 3 Minimum Circuit Ampacity Horsepower Full Load Amps Unit Only with (1) 0.75 HP Power Exhaust Unit Only with (1) 0.75 HP Power Exhaust ELECTRIC HEAT DATA 2 Maximum Overcurrent Protection 3 Minimum Circuit Ampacity 2 Maximum Overcurrent Protection 3 Minimum Circuit Ampacity Electric Heat Voltage Unit + 7.5 kW Electric Heat 15 kW 22.5 kW Unit + 7.5 kW Electric Heat 15 kW 22.5 kW Unit + 7.5 kW Electric Heat 15 kW and (1) 0.75 HP Power Exhaust 22.5 kW Unit + 7.5 kW Electric Heat 15 kW and (1) 0.75 HP Power Exhaust 22.5 kW 208 90 125 150 81 114 148 100 125 175 86 119 153 240 100 125 175 86 125 164 100 150 175 91 130 169 208 50 70 90 51 68 88 60 80 100 54 73 93 240 60 80 100 51 74 97 60 80 110 57 79 102 208 60 70 90 52 69 89 60 80 100 54 74 94 240 60 80 100 52 75 98 60 80 110 57 80 103 ELECTRICAL ACCESSORIES Disconnect Kit 1 2 3 Standard Access − 0−15 kW 22.5 kW Hinged Access − 0−15 kW 22.5 kW 20W19 −−− 20W25 −−− 20W18 20W19 20W24 20W25 20W18 20W19 20W24 20W25 Extremesofoperatingrangeareplusandminus10%oflinevoltage. HACR type breaker or fuse. RefertoNational or CanadianElectricalCodemanualtodeterminewire,fuseanddisconnectsizerequirements. Packaged Heat Pump 2 to 6 tons / Page 26 20W18 20W18 20W24 20W24 20W18 20W18 20W24 20W24 ELECTRICAL/ELECTRIC HEAT DATA 6 TON KHA072S 1 Voltage − 60hz Compressor 208/230V − 3 Ph 460V − 3 Ph 575V − 3 Ph Rated Load Amps 19 9.7 7.4 Locked Rotor Amps 123 62 50 Outdoor Fan Motor Full Load Amps 3 1.5 1.2 Power Exhaust (1) 0.75 HP Full Load Amps 5 2.2 1.5 15 Amps 15 Amps 15 Amps Service Outlet 115V GFI Indoor Blower Motor Horsepower 1.5 2 1.5 2 1.5 2 Full Load Amps 6.6 7.5 3 3.4 2.4 2.7 Unit Only 50 50 25 25 20 20 With (1) 0.75 HP 50 50 25 25 20 20 Unit Only 34 35 17 18 13 14 With (1) 0.75 HP Power Exhaust 39 40 19 20 15 15 2 Maximum Overcurrent Protection Power Exhaust 3 Minimum Circuit Ampacity ELECTRIC HEAT DATA Electric Heat Voltage 2 Maximum Overcurrent Protection 3 Minimum Circuit Ampacity 2 Maximum Overcurrent Protection 3 Minimum Circuit Ampacity Unit+ Electric Heat Unit+ Electric Heat Unit+ Electric Heat and (1) 0.75 HP Power Exhaust Unit+ Electric Heat and (1) 0.75 HP Power Exhaust 208 240 208 240 480 480 600 600 7.5 kW 60 70 60 70 35 35 25 25 15 kW 80 80 80 80 40 40 35 35 22.5 kW 100 110 100 110 60 60 40 45 30 kW 125 125 125 125 70 70 50 50 7.5 kW 53 56 54 57 28 29 22 23 15 kW 73 79 74 80 40 40 31 32 22.5 kW 92 102 93 102 51 51 40 41 30 kW 112 124 113 125 62 63 49 50 7.5 kW 70 70 70 70 35 35 25 25 15 kW 80 90 80 90 45 45 35 35 22.5 kW 100 110 100 110 60 60 45 45 30 kW 125 150 125 150 70 70 60 60 7.5 kW 58 61 59 62 31 31 24 24 15 kW 78 84 79 85 42 42 33 33 22.5 kW 97 107 98 107 53 54 42 42 30 kW 117 129 118 130 64 65 51 51 ELECTRICAL ACCESSORIES Disconnect Kit 1 2 3 Standard Access − 0−22.5 kW 20W18 20W18 20W18 20W18 30 kW 20W19 20W19 20W18 20W18 Hinged Access − 0−22.5 kW 20W24 20W24 20W24 20W24 30 kW 20W25 20W25 20W24 20W24 Extremesofoperatingrangeareplusandminus10%oflinevoltage. HACR type breaker or fuse. RefertoNational or CanadianElectricalCodemanualtodeterminewire,fuseanddisconnectsizerequirements. Packaged Heat Pump 2 to 6 tons / Page 27 ELECTRIC HEAT CAPACITIES 10 kW 15 kW 22.5 kW 30 kW 7.5 kW Input Btuh No of kW Btuh No of kW Btuh No of kW Btuh No of kW Btuh Voltage No of kW Stages input Output Stages input Output Stages input Output Stages input Output Stages input Output 208 1 5.6 19,200 1 7.5 25,600 1 11.2 38,200 2 16.9 57,700 1 22.5 76,800 220 1 6.3 21,500 1 8.4 28,700 1 12.6 43,000 2 18.9 64,500 1 25.2 86,000 230 1 6.9 23,500 1 9.2 31,400 1 13.8 47,000 2 20.7 70,700 1 27.5 93,900 240 1 7.5 25,600 1 10.0 34,200 1 15.0 51,200 2 22.5 76,800 1 30.0 102,400 440 1 6.3 21,500 −−− −−− −−− 1 12.6 43,000 2 18.9 64,500 1 25.2 86,000 460 1 6.9 23,500 −−− −−− −−− 1 13.8 47,000 2 20.7 70,700 1 27.5 93,900 480 1 7.5 25,600 −−− −−− −−− 1 15.0 51,200 2 22.5 76,800 1 30.0 102,400 550 1 6.3 21,500 −−− −−− −−− 1 12.6 43,000 2 18.9 64,500 1 25.2 86,000 575 1 6.9 23,500 −−− −−− −−− 1 13.8 47,000 2 20.7 70,700 1 27.5 93,900 600 1 7.5 25,600 −−− −−− −−− 1 15.0 51,200 2 22.5 76,800 1 30.0 102,400 UNIT CLEARANCES − INCHES (MM) C B OUTDOOR AIR HOOD D A 1 A Unit Clearance B C D in. mm in. mm in. mm in. mm Service Clearance 36 914 36 914 36 934 36 914 Minimum Operation Clearance 36 914 36 914 36 914 36 914 Top Clearance Unobstructed NOTE − Entire perimeter of unit base requires support when elevated above the mounting surface. 1 Service Clearance − Required for removal of serviceable parts. Minimum Operation Clearance − Required clearance for proper unit operation. Packaged Heat Pump 2 to 6 tons / Page 28 WEIGHT DATA Shipping Net Base Model Number 024S 030S 036S 048S 060S 072S lbs. 531 533 535 557 667 750 Max. kg 241 242 243 253 303 340 lbs. 643 645 647 669 770 862 Base kg 292 293 293 303 349 391 lbs. 591 593 595 617 727 810 Max. kg 268 269 270 280 330 367 lbs. 712 714 716 738 842 931 kg 323 324 325 335 382 422 Base Unit − The unit with NO OPTIONS. Max. Unit − The unit with ALL OPTIONS Installed (Economizer, etc.) OPTIONs / ACCESSORIES Shipping Weights ECONOMIZER / OUTDOOR AIR Economizer Economizer, Includes Outdoor Air Hood and Barometric Relief Dampers with Hood OUTDOOR AIR Outdoor Air Dampers Outdoor Air Damper Motorized Kit Damper Section Manual Power Exhaust Standard Static ELECTRIC HEAT Electric Heat ROOF CURBS − DOWNFLOW Cliplock 8 in. height 14 in. height 18 in. height 24 in. height Hinged 8 in. height 18 in. height 24 in. height Standard 14 in. height CEILING DIFFUSERS Step−Down Flush Transitions (Supply and Return) lbs. kg T1ECON30A−1 T1ECON30N−1 123 142 56 65 T1DAMP11A−1 T1DAMP11N−1 T1DAMP21AN1 25 29 18 12 14 9 T1PWRE10A−1 T1PWRE10N−1 35 39 17 19 7.5 kW − T1EH0075AN1 10 kW − T1EH0100AN1 15 kW − T1EH0150AN1 22.5 kW − T1EH0225AN1 30 kW − T1EH0300N−1 31 31 31 35 35 14 14 14 16 16 T1CURB23AN1 K1CURB23AP1 T1CURB20AN1 K1CURB20AP1 T1CURB21AN1 K1CURB21AP1 T1CURB22AN1 K1CURB22AP1 78 83 96 101 108 113 126 131 35 38 44 46 49 51 57 59 T1CURB30AN1 K1CURB30AP1 T1CURB32AN1 K1CURB32AP1 T1CURB33AN1 K1CURB33AP1 78 83 108 113 126 131 35 38 49 51 57 59 T1CURB10AN1 K1CURB10AP1 96 101 44 46 67 88 37 75 22 21 30 40 17 34 10 10 RTD9−65 RTD11−95 FD9−65 FD11−95 T1TRAN10AN1 T1TRAN20N−1 Packaged Heat Pump 2 to 6 tons / Page 29 DIMENSIONS − INCHES (MM) Model No. 024 030 036 048 060 072 CORNER WEIGHTS AA BB Base Max. Base Max. lbs. kg lbs. kg lbs. kg lbs. kg 92 42 116 53 112 51 131 59 92 42 116 53 112 51 131 60 93 42 116 53 112 51 132 60 96 44 120 55 117 53 136 62 115 52 138 63 140 64 157 71 160 73 185 84 180 82 208 94 CC Base Max. lbs. kg lbs. kg 180 82 211 96 180 82 211 96 181 82 212 96 188 86 219 100 226 103 252 115 233 106 269 122 CENTER OF GRAVITY EE FF Base Max. Base Max. in. mm in. mm in. mm in. mm 38−1/2 978 40 1016 18 457 18 457 38−1/2 978 40 1016 18 457 18 457 38−1/2 978 40 1016 18 457 18 457 38−1/2 978 40 1016 18 457 18 457 38−1/2 978 40 1016 18 457 18 457 46−1/4 1174 46−1/4 1174 20−1/2 521 20−1/2 521 DD Base Max. lbs. kg lbs. kg 148 67 186 85 149 68 187 85 149 68 187 85 155 71 194 88 166 84 223 101 207 94 239 108 Base Unit − The unit with standard heat exchanger NO OPTIONS. Max. Unit − The unit with ALL OPTIONS Installed. (Economizer, etc.) 5−5/8 (143) AA 16−1/4 (413) 11 (279) 18 (457) BB 5 (102) 7 (178) BOTTOM RETURN AIR OPENING 29 (737) BOTTOM SUPPLY AIR OPENING 47 (1192) BASE 20 (508) CENTER OF GRAVITY 25−3/4 (654) 024 thru 060 38−3/4 (984) 072 FF 6−5/8 (168) 9−1/2 (241) DD CC 26−1/2 (673) BOTTOM CONDENSATE OUTLET EE BOTTOM POWER ENTRY 3 X 8 (76 X 203) TOP VIEW (Base) 83−1/4 (2115) 024 thru 060 96−1/4 (2445) 072 35−3/8 (899) 024 thru 048 43−3/8 (1102) 060 / 072 38−7/8 (987) 024 thru 048 46−7/8 (1191) 060 / 072 45 (1143) ELECTRICAL INLET CONDENSATE OUTLET (EITHER SIDE) 5−1/2 (140) 1 (25) 1 (25) 3−1/2 (89) 47 (1192) BASE END VIEW 26−1/2 (673) LIFTING HOLES (For rigging) 85−1/4 (2165) 024 thru 060 BASE 98−1/4 (2496) 072 BASE SIDE VIEW 19−1/2 (495) 20 (508) FORKLIFT SLOTS (Front, Back and Blower End) 11 (279) 2 (51) 29 (737) 5−1/2 HORIZONTAL HORIZONTAL 5−1/2 RETURN AIR (140) (140) SUPPLY AIR OPENING OPENING (Without Economizer) BACK VIEW Packaged Heat Pump 2 to 6 tons / Page 30 18−3/8 (467) ACCESSORY DIMENSIONS − INCHES (MM) OUTDOOR AIR HOOD DETAIL FOR OPTIONAL ECONOMIZER AND BAROMETRIC RELIEF DAMPERS (Downflow Applications) 11−3/4 (298) 024 thru 048 15−3/4 (400) 060 and 072 OPTIONAL OUTDOOR AIR HOOD (Furnished with Economizer) 12 (305) OPTIONAL BAROMETRIC RELIEF HOOD (Furnished with Economizer) SIDE VIEW BAROMETRIC RELIEF HOOD FOR ECONOMIZER (Furnished) OUTDOOR AIR HOOD FOR ECONOMIZER (Furnished) 1−1/4 (32) 2−1/2 (64) 12 (305) C 33 (838) 30−1/2 (775) 1−1/4 (32) 2−1/2 (64) 1−1/2 (38) 3/4 (19) B A 1 (25) 3/8 (10) Model No. A B C in. mm in. mm in. mm 024, 030, 036, 048 19−1/4 489 13 330 11−3/4 298 060, 072 23−1/4 591 17 432 15−3/4 400 OUTDOOR AIR DAMPER HOOD DETAIL FOR OPTIONAL MANUAL OR MOTORIZED OUTDOOR AIR DAMPERS (Downflow or Horizontal Applications) 10−1/2 (267) 35 (889) OPTIONAL OUTDOOR AIR DAMPERS AND PANEL 13−1/2 (343) OUTDOOR AIR DAMPER HOOD OUTDOOR AIR DAMPER HOOD (Furnished) 35 (889) 024 thru 048 43 (1092) 060 and 072 SIDE VIEW 16−1/2 (419) 10−1/2 (267) Packaged Heat Pump 2 to 6 tons / Page 31 ACCESSORY DIMENSIONS − INCHES (MM) OUTDOOR AIR HOOD DETAIL WITH OPTIONAL ECONOMIZER AND BAROMETRIC RELIEF DAMPERS (Horizontal Applications) Barometric Relief Hood and Dampers ECONOMIZER DAMPERS RETURN AIR DUCT (Field Fabricated − Must be sized to accommodate Barometric Relief Hood and Return Air Requirements) RETURN AIR DUCT TRANSITION (Field fabricated and installed on unit) SUPPLY AIR DUCT (Field Provided) SUPPLY AIR OUTLET BAROMETRIC RELIEF HOOD DIMENSIONS Width − 35−1/2 in. (902 mm) Height − 21 in. (533 mm) (024, 030, 036, 048) 25 in. (635 mm) (060, 072) See previous page for details. RETURN AIR INLET TOP VIEW OUTDOOR AIR HOOD (Furnished with Economizer) 29−1/4 (743) 19−1/2 (495) HORIZONTAL SUPPLY AIR OPENING 20 (508) B BAROMETRIC RELIEF HOOD (Furnished with Economizer and Field Installed on Field fabricated Return Air Duct) 7/8 (22) OUTDOOR AIR This opening not used in Horizontal Applications with Economizer 2−1/4 (57) HORIZONTAL RETURN AIR OPENING A 30−7/16 (773) 2−1/4 (57) EXHAUST AIR 5 (127) RETURN AIR DUCT TRANSITION (Field fabricated and installed on unit) BACK VIEW RETURN AIR DUCT INLET (Field Fabricated − Must be sized to accommodate Barometric Relief Hood and Return Air Requirements) NOTE − Return Air Duct and Transition must be supported. Model No. A B in. mm in. mm 024, 030, 036, 048 18−3/4 476 11−3/4 298 060, 072 22−1/2 572 15−3/4 400 Packaged Heat Pump 2 to 6 tons / Page 32 7/8 (22) UNIT RETURN AIR DUCT OPENING WITH ECONOMIZER INSTALLED END VIEW ACCESSORY DIMENSIONS − INCHES (MM) CLIPLOCK 1000 ROOF CURBS − DOUBLE DUCT OPENING 1−13/16 (46) 21−1/8 (537) C A 41−1/2 (1054) 37−7/8 (962) B 19−1/8 (486) 15−1/8 (384) 8 (203) 14 (356) 18 (457) 24 (610) SUPPLY OPENING 12−5/8 (321) 1−13/16 (46) RETURN OPENING 32 (813) NOTE − Roof deck may be omitted within confines of curb. DETAIL ROOF CURB TYPICAL FLASHING DETAIL FOR ROOF CURB BASE BOTTOM 1−13/16 (46) PACKAGED UNIT 1/2 (13) FIBERGLASS INSULATION (Furnished) COUNTER FLASHING (Field Supplied) FACTORY INSTALLED PERIMETER WOOD NAILER STRIP NAILER STRIP (Furnished) CANT STRIP (Field Supplied) ROOF CURB (Extends around entire perimeter of unit) 8 (203) 14 (356) 18 (457) 24 (610) ROOFING MATERIAL RIGID INSULATION (Field Supplied) 1−13/16 (46) Model No. A B C in. mm in. mm in. mm 024, 030, 036, 048, 060, 1 072 29−1/4 743 79−3/4 2026 76−1/8 1934 072 42−1/4 1073 92−3/4 2356 89−1/8 2264 1 072 models can be used on smaller 79−3/4 in. (2026 mm) roof curbs (not full perimeter) with 15−3/4 in. (400 mm) overhang at condenser end of unit. See dimension drawing on page 36. Packaged Heat Pump 2 to 6 tons / Page 33 ACCESSORY DIMENSIONS − INCHES (MM) HINGED ROOF CURBS − DOUBLE DUCT OPENING 1−13/16 (46) 41−1/2 (1054) 21−1/8 (537) C A 37−7/8 (962) B 19−1/8 (486) 15−1/8 (384) 8 (203) 18 (457) 24 (610) SUPPLY OPENING 12−5/8 (321) 1−13/16 (46) RETURN OPENING 32 (813) NOTE − Roof deck may be omitted within confines of curb. TYPICAL FLASHING DETAIL FOR ROOF CURB BASE BOTTOM DETAIL ROOF CURB 1−13/16 (46) PACKAGED UNIT 1/2 (13) FIBERGLASS INSULATION (Furnished) COUNTER FLASHING (Field Supplied) FACTORY INSTALLED PERIMETER WOOD NAILER STRIP NAILER STRIP (Furnished) CANT STRIP (Field Supplied) ROOF CURB (Extends around entire perimeter of unit) 8 (203) 18 (457) 24 (610) ROOFING MATERIAL RIGID INSULATION (Field Supplied) 1−13/16 (46) Model No. A B C in. mm in. mm in. mm 024, 030, 036, 048, 060, 072 29−1/4 743 79−3/4 2026 76−1/8 1934 072 42−1/4 1073 92−3/4 2356 89−1/8 2264 1 1 072 models can be used on smaller 79−3/4 in. (2026 mm) roof curbs (not full perimeter) with 15−3/4 in. (400 mm) overhang at condenser end of unit. See dimension drawing on page 36. Packaged Heat Pump 2 to 6 tons / Page 34 ACCESSORY DIMENSIONS − INCHES (MM) STANDARD ROOF CURBS − DOUBLE DUCT OPENING 1−13/16 (46) 41−1/2 (1054) 21−1/8 (537) C A 37−7/8 (962) B 19−1/8 (486) 15−1/8 (384) 14 (356) SUPPLY OPENING 12−5/8 (321) 1−13/16 (46) RETURN OPENING 32 (813) NOTE − Roof deck may be omitted within confines of curb. DETAIL ROOF CURB TYPICAL FLASHING DETAIL FOR ROOF CURB BASE BOTTOM 1−13/16 (46) PACKAGED UNIT 1 (25) FIBERGLASS INSULATION (Furnished) COUNTER FLASHING (Field Supplied) FACTORY INSTALLED PERIMETER WOOD NAILER STRIP NAILER STRIP (Furnished) CANT STRIP (Field Supplied) ROOF CURB (Extends around entire perimeter of unit) 14 (356) ROOFING MATERIAL RIGID INSULATION (Field Supplied) 2 (51) Model No. A B C in. mm in. mm in. mm 024, 030, 036, 048, 060, 1 072 29−1/4 743 79−3/4 2026 76−1/8 1934 072 42−1/4 1073 92−3/4 2356 89−1/8 2264 1 072 models can be used on smaller 79−3/4 in. (2026 mm) roof curbs (not full perimeter) with 15−3/4 in. (400 mm) overhang at condenser end of unit. See dimension drawing on page 36. Packaged Heat Pump 2 to 6 tons / Page 35 ACCESSORY DIMENSIONS − INCHES (MM) 072 MODELS − SHOWING OVERHANG ON SMALLER 79−3/4 INCH LENGTH ROOF CURBS (Not Full Perimeter) ROOF CURB 79−3/4 (2026) 2−3/4 (686) 15−3/4 (400) SIDE VIEW TRANSITIONS T1TRAN10AN−1 − FOR 18 INCH (457 MM) DUCT T1TRAN20N−1 − FOR 20 INCH (508 MM) DUCT 12 (305) 31−1/2 (800) 8 (203) 1−1/2 inch (38 mm) T1TRAN10AN−1 2 inch (51mm) T1TRAN20N−1 32 (813) 12−5/8 (321) 19−1/8 (486) RETURN OPENING RETURN TRANSITION SUPPLY OPENING 21−1/8 (521) T1TRAN10AN−1 − FOR 18 INCH (457 MM) DUCT T1TRAN20N−1 − FOR 20 INCH (508 MM) DUCT 18−1/2 (470) 20−1/2 (521) 8 (203) 1−1/2 inch (38 mm) T1TRAN10AN−1 2 inch (51mm) T1TRAN20N−1 SUPPLY TRANSITION Packaged Heat Pump 2 to 6 tons / Page 36 ACCESSORY DIMENSIONS − INCHES (MM) COMBINATION CEILING SUPPLY AND RETURN DIFFUSERS STEP-DOWN CEILING DIFFUSER FLUSH CEILING DIFFUSER H G E D F G H F C G C 2 (51) 2 (51) A L D H G E H A B B J K Model Number A B C D E F G H J K L Duct Size in. mm in. mm in. mm in. mm in. mm in. mm in. mm in. mm in. mm in. mm in. mm in. mm RTD9−65 47−5/8 1159 23−5/8 600 11−3/8 289 21−1/2 546 45−1/2 1156 22−1/2 572 11−1/2 292 10−3/4 273 45−1/2 1156 21−1/2 546 7−1/8 181 18 round 457 round RTD11−95 47−5/8 1159 29−5/8 752 14−3/8 365 27−1/2 699 45−1/2 1158 22−1/2 572 11−1/2 292 13−3/4 349 45−1/2 1156 27−1/2 699 8−1/8 206 20 round 508 round Model Number A B C D E F G H Duct Size in. mm in. mm in. mm in. mm in. mm in. mm in. mm in. mm in. mm FD9−65 47−5/8 1159 23−5/8 600 13−1/2 343 21 533 45 1143 22−1/2 572 11−1/4 286 10−1/2 267 18 round 457 round Packaged Heat Pump 2 to 6 tons / Page 37 FD11−95 47−5/8 1159 29−5/8 752 16−5/8 422 27 686 45 1143 22−1/2 572 11−1/4 286 13−1/2 343 20 round 508 round REVISIONS Sections Description of Change Options/Accessories Drive Kits changed to Factory Installed. Expanded ratings Updated table for 072. NOTE − Due to our ongoing commitment to quality, Specifications, Ratings and Dimensions subject to change without notice and without incurring liability. Improper installation, adjustment, alteration, service or maintenance can cause property damage or personal injury. ©2009 Allied Air Enterprises Installation and service must be performed by a qualified installer and servicing agency.