PSF132UM.qxd
08/04/2004
09:00
Page 1
MINERVA® Marine
601F-M & 601FEx-M Conventional InfraRed Flame Detectors
Features:
Unlike UV and UV/IR detection, not blinded
by oil mist in machinery spaces
Reduces cabling, no interface required
No additional power source required
Easy installation, uses a common plug in
base for smoke and heat detectors
Can be used on all vessels as fully marine
approved
Standard or Intrinsically Safe
ATEX approved
The 601F-M and 601FEx-M point type flame
detectors form part of the 600 series of conventional
detectors. The range includes heat, optical, ionisation
and carbon monoxide detection technologies and
with the addition of the 601F-M and 601FEx-M now
encompasses infrared flame detection.
Both the 601F-M and the 601FEx-M are full featured
solar blind flame detectors for enclosed use and boast
a high degree of false alarm immunity. The standard
unit is the 601F-M and it is designed for connection
to a conventional zone of point type fire detectors that
may include any mix of detection technologies. The
601FEx-M is an intrinsically safe version intended for
use in hazardous atmospheres and must be
connected via a suitable isolator or shunt diode safety
barrier in a certified Intrinsically Safe system.
Ordering Information:
Stockcode
Description
516.600.007
601F-M Conventional Flame
Detector
601FEx-M Conventional
Flame Detector Intrinsically
Safe
5B 5" Universal Base
MUBEx Base For
600/800Ex
MTL5061 2 Channel
Galvanic Isolator
DX170 MTL5/7000
Enclosure
T110 IR Test Source
T110 Test Source Adapter
516.600.067
517.050.017
517.050.610
517.001.244
517.001.247
592.001.012
592.001.018
Fire Detection
PSF132UM.qxd
08/04/2004
09:00
Page 2
Mechanical
Detector Material:
Dimensions:
Weight: - 601F-M
- 601FEx-M
Environmental
FR110 ‘BAYBLEND’
108mm x 21.2mm
74g
108g
Operating temperature:
Operation below 0oC is not recommended unless steps are taken to
eliminate condensation and hence ice formation on the detector.
Electrical
Supply Voltage:
Quiescent current:
Alarm current:
Storage Temperature:
Relative Humidity:
601F-M 18 – 32Vdc
601FEx-M 18 – 28 Vdc
Typical 300 micro Amp
8-30 mA
Range:
28V
93mA
650mW
0
0
Field of View:
0.1m2 n-heptane at 20m
0.4m2 n-heptane at 50m
100o
Mounting Base
Hazardous Area
ATEX code:
-40oC to +80oC
90% RH continuous (noncondensing) and up to 99% RH
intermittent (non-condensing)
Performance
Intrinsic Safety Rating
Maximum Voltage for Safety (Ui):
Maximum Current for Safety (Ii):
Maximum Power Input (Pi):
Equivalent Inductance (Li):
Equivalent Capacitance (Ci):
-20oC to +70oC
II 1 G EEx ia IIC T4
50o 50o
L -VE IN/OUT
L1 +VE IN
L2 +VE OUT
R Remote LED Drive -VE
12m
Note 2: Diagram not to scale
19m
0.2m2
Connections:
8m
9.5m
0.1m2
5” Universal Base
Note 1: When the risk is a hot
vibrating body the detector should be
mounted securely using a suitably
fabricated bracket at an angle or on a
vertical surface to view the risk.
4m
0.05m2
5B:
28.5m
16m
0.4m2
Approx Flame Area
38m
The right is reserved to modify or withdraw any product
or service without notice
Technical Information Sheet PSF132UM Issue 1
www.tycosafetyproducts-europe.com
©Tyco Safety Products 2003
DISTRIBUTOR FOR NORWAY
Holta & Håland Safety AS
Download PDF
Similar pages