1 4 25 Power Cable of Copper 4 X25 Sq.MM, Power Cable o

Sr. No.
Store
Code
1
No. of Size Sq. Type
Cores mm
Power & Control Cable
4
25
Power Cable of
Copper
2
4
35
Festoon
3
4
2.5
Festoon
4
3
150
3
150
19
2.5
5
6
7
EL00002095
Aluminium
XLPE
Description
Qty
(meter)
4 X25 Sq.MM, Power Cable of copper, 3.3 KV(UE), heavy duty,
800
flexible type, annealed tinned stranded copper conductor PCP inner
sheathed, PCP outer sheathed, confirming to standards- IS:9968-II/
88, cable size considered is 4C x25 Sq.mm. current rating of cable is
123 Amps at 40 deg. C.
Cable 4 X 35 Sq.MM, Festoon cable ,EPR insulated, 1 KV grade, annealed 300
tinned stranded copper conductor, confirming to standards- IS:9968,
part-1
Cable 4 X 2.5 Sq.MM, Festoon cable ,EPR insulated, 1 KV grade, annealed 250
tinned stranded copper conductor, confirming to standards- IS:9968,
part-1
3 X 150 Sq. MM, 1.1 KV grade stranded aluminium conductor, XLPE
500
insulated, extruded PVC inner sheathed, galvanised steel strip/wire
armoured and extruded PVC inner sheath, galvanised steel strip/wire
armoured and extruded PVC overall jacketed and conforming to IS-1554,
Part-I
3X150Sq.MM, 3.3KVstranded compacted aluminium conductor, semi 1500
conducting conductor screen, XLPE insulated, semi-conducting
insulation screen, copper tapped, earth fault current rating shall be
0.3KA for 1 sec (all 3cores combined) PVC type ST2 inner sheathed,
Galvanised steel formed wire armoured, PVC type-ST2(FRLS) outer
sheathed cable conforming to IS:7098(Part-II)
19C X 2.5 Sq. MM, Copper Cable(armoured) ,1.1 KV grade, Stranded Copper 500
Conductor, PVC insulated, Extruded PVC inner sheathed, Galvanised Steel
strip/wire armoured and extruded PVC over aluminium jacketed conforming
to IS-1554, Part-I
Instrumentation Cables
Individual & Overall Sheilded Instrumentation 16Px0.5 Cable
4 KM
Applicable Standard : Gen. to IS-8130/84, BS-5308, IS-3975/88, IS-1554,IS5831/84 etc.with latest upto date amendments
Voltage Grade : 660/1100V
Suitable for both neutral earthed/unearthed system
Permissible for +/-10% voltage and frequency variation for stisfactory
operation
CONDUCTOR:
Material : Annealed Tinned High Conductivity Stranded Copper as per Class
2
Shape of Conductor : Stranded - Circular
Approx. No. of Wire : 7
Nom. Diameter of wire : 0.307mm
Nom. Area of Cross Section : 0.5mm2
Diameter/Size of conductor (Nom.) : 0.9mm
Confirming Standard of Conductor Material : IS 8130/84
Grade :E.C Grade, Class : 2
INSULATION :
Material : HR PVC Type C
Thickness of insulation (Nom.) :
(i) Between Cores : 1.2mm(Nom.)
(ii) Between cores & Inner sh. (Nom.) : 0.60mm (Nom.)
Nom. Diameter of Core over Insulation : 2.19mm
Specific insulation resistance at 85 deg.C and Min. Volume Resistivity at
27deg.C : 1x10(10)W-cm at 85°C and 1x10(13)W-cm at 27°C
Type/Applicable Standard : IS 5831/84
Sheilding :
(i) Material : Aluminium Mylar Tape along with ATC Drain Wire (0.5Sq.mm)
(ii)Tape/Applicable Standard : Tape (Individual & Overall)
(iii) Thickness in mm individual pair sheil/overall sheild : 0.06mm(Min.)
Approx. dial of Cable over sheilding : 21.30mm
Continuous current carrying capacity:
For standard conditions as per IS:
(i) In Air at 40 deg.C : 3A
(ii) In Ground at 30 deg.C : 3A
(iii) In Duct at 30 deg.C : 3A
(iv) In Trench at 30 deg.C : 3A
For site conditions
(i) In Air at 50 deg.C : 2A
(ii) In Ground at 40 deg.C : 3A
(iii) In Duct at 40 deg.C : 2A
(iv) In Trench at 40 deg.C : 2A
Derating factor for fire resistance treatment : 0.99
Maximum Conductor Temperature
(i) Continuous : 85 Deg.C
(II) Short time : 160 Deg.C
INNER SHEATH :
Material : Extruded FRLS PVC Type ST2
Type : Extruded
Thickness : 0.3mm (Min.)
Nom.Diameter of Cable over inner sheath : 22.30mm
Type/Applicable Standard : IS 5831/84
Colour : Black
Filler Material : HR PVC Fillers
ARMOURING :
Material : Galvanised Steel
Type of armuring : Flat Strip
Diameter of wire/Size of strip : 0.90mm
Wheather Galvanised : Yes
Nom. Diameter of cable over armouring : 16
Type/Applicable Standard : Gen. to IS 3975/88
Approx. No. of wire used for Armouring : 16
D.C.Resistance 20Deg.C : 3.20 Ohm/km
Short Circuit Current (K amp) Carrying Capacity : 2.545 K amp
OUTER SHEATH :
Material : Extruded FRLS PVC Type ST2
Thickness of sheath : 1.4mm
Overall diameter of cable (approx.)+/-2mm tolerance : 27mm
Type/Applicable Standard : IS 5831/84
Colour : Black
Scheme for identification of Pairs/Units : As per IS 9983
ELECTRICAL PARAMETERS :
Max. Condt. Resistance at 20 deg.C : 39.2 Ohm/km
Mutual capacitance at 0.8KHz : 120 nf/km
Cross talk at 0.8KHz : 70 Db
Insulation Resistance at 20 deg.C for completed cable : 100 Mohm/km
Max. Characteristic Impedance at 1 KHz : 370 Ohams
Attenuation at 1 KHz : 0.8KHz = 0.11db/100m & 10.0KHz = 0.29 db/100m
High Voltage test between Conducts to Conductor and conductor & shield :
2KV (rms) for 1 minute
Short circuit withstand capacity for conductor :
Short circuit current : 0.16kA
Duration of short circuit : 1sec
Cable constants:
Max. DC/AC Resistance per core at 20 deg.C : 12.60 ohm/km
Reactance per core : 0.14 ohm/km
Mutual capacitance per core at 0.8KHz : <100 nf/km
Insulaton :
Loss tangent : 0.1
Dielectric Constant : 6-7
FRLS PROPERTIES FOR INNER & OUTER SHEATH :
Min. Oxygen index as per ASTM D 2863 : 29%
Min. Temp. Index as per ASTM D 2863 : 250 OC
Max. HCL Emission as per IEC-754-I : 20% by weight
Smoke density rating as per ASTM D 2843 : 60%
Flammability test on completed cable as per IEC-332 part-1 / IEEE 383-1974
OTHER PROPERTIES :
Outer sheath must be Rodent and Termite replusion proof.
Min. Insulation Resistance at 20 deg.C of complete cable : 100 Mohm/km
8
Water immersion test as per VDE 0815
Image attenuation at 0.8khz(db/100mtr) : 1.20 dB/km
Image attenuation at 10khz(db/100mtr) : 0.29 dB/km
Min. cross talk attenuation at 0.8khz(db/lm) : 60dB/km
Coupling Capacitance at 0.8khz : 100nf/km
high Voltage test between Conducts to Conductor and conductor & shield :
2KV (rms), 50Hz for 1 minute
Min. electrostatic noise rejection ratio(db) : 75 Db
Characteristic Impedance at 0.8khz : 370 ohm
0.5Sq.mm(7/0.3mm)Ind. & O/A Screened Armoured FRLS Sheathed 12P
Cable
Cable Type & No. of pairs : Ind. & O/A Screened Armoured Cable & 12P
Applicable Standard : IS-5831, IS-8130, IS-3975, IS-1554-I,IS-10810, ASTM D
2843, 2863, IEC-332-III-C, IEC-754-I, SS 424 1475 F(3) & Tech. Particulars
CONDUCTOR:
Material : Annealed Tinned Copper as per IS-8130
Grade : Electrolytic
No. of strands/dia of each strand : 7/0.3(Nom.)
Area of Cross Section : 0.5mm2
Shape of Conductor : Stranded - Circular
Voltage Grade : 600/1100V
Temp. Rating : 85deg.C
INSULATION :
Material : HR PVC Type C of IS-5831
Thickness of insulation (Nom.) : 0.4mm
Method of Application : Extrusion
Dia of insulation : 1.70mm
4 KM
Twisting lay for pairs : 50mm
SCREEN/OVERALL SCREEN:
Material : Al.Mylar Tape
Type : Helical
Thickness of Tape : 0.060mm
Coverage/Overlap : 100%/25%
DRAIN WIRE :
Material : Annealed Tinned Copper
Area of Cross Section : 0.5mm2
No. of strands/Size : 1/0.8mm
INNER SHEATH :
Material : PVC Type ST2 of IS-5831 with FRLS Properties
Type : Extruded
Thickness : 0.3mm
Colour : Black
ARMOURING :
Material : Galvanised Flat Strip as per IS-3975
Type : Single Layer - Helical
Size of strip : 4x0.8 F/S
OUTER SHEATH :
Material : PVC Type ST2 of IS-5831 with FRLS Properties
Type : Extruded
Thickness : 1.4mm
Dia over outer sheath : 22.3mm
Colour : Black
FILLER : Flame retardant and moisture resistance
ELECTRICAL PARAMETERS :
Max. Condt. Resistance at 20 deg.C : 39.2 Ohm/km
Mutual capacitance at 0.8KHz : 120 nf/km
Cross talk at 0.8KHz : 70 Db
Insulation Resistance at 20 deg.C for completed cable : 100 Mohm/km
Max. Characteristic Impedance at 1 KHz : 370 Ohams
Attenuation at 1 KHz : 0.8KHz = 0.11db/100m & 10.0KHz = 0.29 db/100m
High Voltage test between Conducts to Conductor and conductor & shield :
2KV (rms) for 1 minute
FRLS PROPERTIES FOR INNER & OUTER SHEATH :
Min. Oxygen index at room temp. when tested as per ASTM D 2863 : 29%
Min. Temp. Index at O.I 21 when tested as per ASTM D 2863 : 250 OC
9
Max. HCL Emission when tested as per IEC-754-I : 20% by weight
Smoke density rating when tested as per ASTM D 2843 : Not be more than
60%
Flammability test IEC-332-III-C,IEEE-383 SS 424 1475 CI.F3 : shall pass the
test
Individual & Overall Sheilded Instrumentation 8Px0.5 Cable
Applicable Standard : Gen. to IS-8130/84, BS-5308, IS-3975/88, IS-1554,IS5831/84 etc.with latest upto date amendments
Voltage Grade : 660/1100V
Suitable for both neutral earthed/unearthed system
Permissible for +/-10% voltage and frequency variation for stisfactory
operation
CONDUCTOR:
Material : Annealed Tinned High Conductivity Stranded Copper as per Class
2
Shape of Conductor : Stranded - Circular
Approx. No. of Wire : 7
Nom. Diameter of wire : 0.307mm
Nom. Area of Cross Section : 0.5mm2
Diameter/Size of conductor (Nom.) : 0.9mm
Confirming Standard of Conductor Material : IS 8130/84
Grade :E.C Grade, Class : 2
INSULATION :
Material : HR PVC Type C
Thickness of insulation (Nom.) :
(i) Between Cores : 1.2mm(Nom.)
(ii) Between cores & Inner sh. (Nom.) : 0.60mm (Nom.)
Nom. Diameter of Core over Insulation : 2.19mm
Specific insulation resistance at 85 deg.C and Min. Volume Resistivity at
27deg.C : 1x10(10)W-cm at 85°C and 1x10(13)W-cm at 27°C
Type/Applicable Standard : IS 5831/84
Sheilding :
(i) Material : Aluminium Mylar Tape along with ATC Drain Wire (0.5Sq.mm)
(ii)Tape/Applicable Standard : Tape (Individual & Overall)
(iii) Thickness in mm individual pair sheild/overall sheild : 0.06mm(Min.)
Approx. dial of Cable over sheilding : 16.40mm
Continuous current carrying capacity:
For standard conditions as per IS:
4 KM
(i) In Air at 40 deg.C : 4A
(ii) In Ground at 30 deg.C : 4A
(iii) In Duct at 30 deg.C : 3A
(iv) In Trench at 30 deg.C : 3A
For site conditions
(i) In Air at 50 deg.C : 3A
(ii) In Ground at 40 deg.C : 3A
(iii) In Duct at 40 deg.C : 3A
(iv) In Trench at 40 deg.C : 3A
Derating factor for fire resistance treatment : 0.99
Maximum Conductor Temperature
(i) Continuous : 85 Deg.C
(II) Short time : 160 Deg.C
INNER SHEATH :
Material : Extruded FRLS PVC Type ST2
Type : Extruded
Thickness : 0.3mm (Min.)
Nom.Diameter of Cable over inner sheath : 17.40mm
Type/Applicable Standard : IS 5831/84
Colour : Black
Filler Material : HR PVC Fillers
ARMOURING :
Material : Galvanised Steel
Type of armuring : Flat Strip
Diameter of wire/Size of strip : 4x0.8mm
Wheather Galvanised : Yes
Nom. Diameter of cable over armouring : 19
Type/Applicable Standard : Gen. to IS 3975/88
Approx. No. of wire used for Armouring : 12
D.C.Resistance 20Deg.C : 4.26 Ohm/km
Short Circuit Current (K amp) Carrying Capacity : 1.908 K amp
OUTER SHEATH :
Material : Extruded FRLS PVC Type ST2
Thickness of sheath : 1.4mm
Overall diameter of cable (approx.)+/-2mm tolerance : 22.50mm
Type/Applicable Standard : IS 5831/84
Colour : Black
Scheme for identification of Pairs/Units : As per IS 9983
ELECTRICAL PARAMETERS :
Mutual capacitance at 0.8KHz : <100 nf/km
Cross talk at 0.8KHz : 70 Db
Insulation Resistance at 20 deg.C for completed cable : 100 Mohm/km
Max. Characteristic Impedance at 1 KHz : 370 Ohams
Attenuation at 1 KHz : 0.8KHz = 0.11db/100m & 10.0KHz = 0.29 db/100m
High Voltage test between Conducts to Conductor and conductor & shield :
2KV (rms) for 1 minute
Short circuit withstand capacity for conductor :
Short circuit current : 0.16kA
Duration of short circuit : 1sec
Cable constants:
Max. DC/AC Resistance per core at 20 deg.C : 12.60 ohm/km
Reactance per core : 0.14 ohm/km
Mutual capacitance per core at 0.8KHz : <100 nf/km
Insulaton :
Loss tangent : 0.1
Dielectric Constant : 6-7
FRLS PROPERTIES FOR INNER & OUTER SHEATH :
Min. Oxygen index as per ASTM D 2863 : 29%
Min. Temp. Index as per ASTM D 2863 : 250 OC
Max. HCL Emission as per IEC-754-I : 20% by weight
Smoke density rating as per ASTM D 2843 : 60%
Flammability test on completed cable as per IEC-332 part-1 / IEEE 383-1974
OTHER PROPERTIES :
Outer sheath must be Rodent and Termite replusion proof.
Min. Insulation Resistance at 20 deg.C of complete cable : 100 Mohm/km
Water immersion test as per VDE 0815
Image attenuation at 0.8khz(db/100mtr) : 1.20 dB/km
Image attenuation at 10khz(db/100mtr) : 0.29 dB/km
Min. cross talk attenuation at 0.8khz(db/lm) : 60dB/km
Coupling Capacitance at 0.8khz : 100nf/km
high Voltage test between Conducts to Conductor and conductor & shield :
2KV (rms), 50Hz for 1 minute
Min. electrostatic noise rejection ratio(db) : 75 Db
Characteristic Impedance at 0.8khz : 370 ohm
10
0.5Sq.mm(7/0.3mm)Ind. & O/A Screened Armoured FRLS Sheathed 4P
Cable
Cable Type & No. of pairs : Ind. & O/A Screened Armoured Cable & 4P
Applicable Standard : IS-5831, IS-8130, IS-3975, IS-1554-I,IS-10810, ASTM D
2843, 2863, IEC-332-III-C, IEC-754-I, SS 424 1475 F(3) & Tech. Particulars
CONDUCTOR:
Material : Annealed Tinned Copper as per IS-8130
Grade : Electrolytic
No. of strands/dia of each strand : 7/0.3(Nom.)
Area of Cross Section : 0.5mm2
Shape of Conductor : Stranded - Circular
Voltage Grade : 600/1100V
Temp. Rating : 85deg.C
INSULATION :
Material : HR PVC Type C of IS-5831
Thickness of insulation (Nom.) : 0.4mm
Method of Application : Extrusion
Dia of insulation : 1.70mm
Colour scheme for identification : Blue+Red, Grey+Yellow, Green+Brown,
White+Black
Twisting lay for pairs : 50mm
SCREEN/OVERALL SCREEN:
Material : Al.Mylar Tape
Type : Helical
Thickness of Tape : 0.060mm
Coverage/Overlap : 100%/25%
DRAIN WIRE :
Material : Annealed Tinned Copper
Area of Cross Section : 0.5mm2
No. of strands/Size : 1/0.8mm
INNER SHEATH :
Material : PVC Type ST2 of IS-5831 with FRLS Properties
Type : Extruded
Thickness : 0.3mm
Colour : Black
ARMOURING :
Material : Galvanised Steel Wire as per IS-3975
Type : Single Layer - Helical
Size of strip : 0.9R/W
OUTER SHEATH :
Material : PVC Type ST2 of IS-5831 with FRLS Properties
Type : Extruded
Thickness : 1.24mm
Dia over outer sheath : 14.8mm
Colour : Black
FILLER : Flame retardant and moisture resistance
ELECTRICAL PARAMETERS :
Max. Condt. Resistance at 20 deg.C : 39.2 Ohm/km
Mutual capacitance at 0.8KHz : 120 nf/km
Cross talk at 0.8KHz : 70 Db
Insulation Resistance at 20 deg.C for completed cable : 100 Mohm/km
Max. Characteristic Impedance at 1 KHz : 370 Ohams
Attenuation at 1 KHz : 0.8KHz = 0.11db/100m & 10.0KHz = 0.29 db/100m
High Voltage test between Conducts to Conductor and conductor & shield :
2KV (rms) for 1 minute
4 KM
FRLS PROPERTIES FOR INNER & OUTER SHEATH :
Min. Oxygen index at room temp. when tested as per ASTM D 2863 : 29%
Min. Temp. Index at O.I 21 when tested as per ASTM D 2863 : 250 OC
11
Max. HCL Emission when tested as per IEC-754-I : 20% by weight
Smoke density rating when tested as per ASTM D 2843 : Not be more than
60%
Flammability test IEC-332-III-C,IEEE-383 SS 424 1475 CI.F3 : shall pass the
test
0.5Sq.mm(7/0.3mm)Ind. & O/A Screened Armoured FRLS Sheathed 2P
Cable
4 KM
Cable Type & No. of pairs : Ind. & O/A Screened Armoured Cable & 1P
Applicable Standard : IS-5831, IS-8130, IS-3975, IS-1554-I,IS-10810, ASTM D
2843, 2863, IEC-332-III-C, IEC-754-I, SS 424 1475 F(3) & Tech. Particulars
CONDUCTOR:
Material : Annealed Tinned Copper as per IS-8130
Grade : Electrolytic
No. of strands/dia of each strand : 7/0.3(Nom.)
Area of Cross Section : 0.5mm2
Shape of Conductor : Stranded - Circular
Voltage Grade : 600/1100V
Temp. Rating : 85deg.C
INSULATION :
Material : HR PVC Type C of IS-5831
Thickness of insulation (Nom.) : 0.4mm
Method of Application : Extrusion
Dia of insulation : 1.70mm
Colour scheme for identification : Blue+Red
Twisting lay for pairs : 50mm
SCREEN/OVERALL SCREEN:
Material : Al.Mylar Tape
Type : Helical
Thickness of Tape : 0.060mm
Coverage/Overlap : 100%/25%
DRAIN WIRE :
Material : Annealed Tinned Copper
Area of Cross Section : 0.5mm2
No. of strands/Size : 1/0.8mm
INNER SHEATH :
Material : PVC Type ST2 of IS-5831 with FRLS Properties
Type : Extruded
Thickness : 0.3mm
Colour : Black
ARMOURING :
Material : Galvanised Steel Wire as per IS-3975
Type : Single Layer - Helical
Size of strip : 0.9R/W
OUTER SHEATH :
Material : PVC Type ST2 of IS-5831 with FRLS Properties
Type : Extruded
Thickness : 1.24mm
Dia over outer sheath : 14.8mm
Colour : Black
ELECTRICAL PARAMETERS :
Max. Condt. Resistance at 20 deg.C : 39.2 Ohm/km
Mutual capacitance at 0.8KHz : 120 nf/km
Insulation Resistance at 20 deg.C for completed cable : 100 Mohm/km
Max. Characteristic Impedance at 1 KHz : 370 Ohams
Attenuation at 1 KHz : 0.8KHz = 0.11db/100m & 10.0KHz = 0.29 db/100m
High Voltage test between Conducts to Conductor and conductor & shield :
2KV (rms) for 1 minute
FRLS PROPERTIES FOR INNER & OUTER SHEATH :
Min. Oxygen index at room temp. when tested as per ASTM D 2863 : 29%
Min. Temp. Index at O.I 21 when tested as per ASTM D 2863 : 250 OC
12
13
14
15
Max. HCL Emission when tested as per IEC-754-I : 20% by weight
Smoke density rating when tested as per ASTM D 2843 : Not be more than
60%
Flammability test IEC-332-III-C,IEEE-383 SS 424 1475 CI.F3 : shall pass the
test
4 core x 1.0 sq. mm Armoured Control Cable
6 core x 1.0 sq. mm Armoured Control Cable
2 pair x 1.5 sq.mm Armoured Control Cable
4 pair x 1.5 sq. mm Armoured Control Cable
1 Km
1 Km
1.5 Km
1 Km
16
17
18
19
20
21
2 core x 2.5 sq. mm Armoured Control Cable
3 core x 2.5 sq. mm Armoured Control Cable
4 core x 2.5 sq. mm Armoured Control Cable
5 core x 2.5 sq. mm Armoured Control Cable
7 core x 2.5 sq. mm Armoured Control Cable
14 core x 2.5 sq. mm Armoured Control Cable
Data Sheet for 1.0 sq mm and 1.5 sq mm
Strd Annealed Tinned Cu Cond HR PVC Type "C" Insulated to form a core,
Cores twisted to form a Pair, Individual & overall screened Alu-Mylar Tape
with Drain wire, FRLS PVC Type "ST-2" inner sheathed GS Wire Armoured,
FRLS PVC Type "ST-2" Outer sheathed cable with rip cord
CONDUCTOR
Type - Strd Annealed Tinned Cu
No. of wires / wire size : 7/0.53 mm2
Resistance at 20 deg C : Max 12.60 Ohm/Km
DRAIN WIRE
Type - Strd Annealed Tinned Cu
Diameter of Wire : 0.80 mm2
No. of wires : 1
Resistance at 20 deg C : Max 30 Ohm/Km
Persulphate test of tinned Cu : Max 5 gm2
SCREENING (INDIVIDUAL & OVERALL)
Alu. Mylar Tape thickness : Ind 0.06/ Overall 0.06
Overlap percentage : 25%
Coverage : 100%
INSULATION
Thickness Minimum / Nominal : 0.44/0.60 mm
without ageing - Tensile strength : Min 12.5 N/mm2
without ageing - Elongation at breake : Min 12.5 %
Volume Resistivity - At 27 deg C : Min 1x1013 Ohm-cm
Volume Resistivity - At 85 deg C : Min 1x1013 Ohm-cm
Insulation Resistance : Min 100 Mega Ohm
Mutual Capacitance At 0.8 Khz : Max 100 nF/Km
Inner sheath Type / Min thickness: FRLS PVC Type "ST-2"/0.30mm
ARMOUR WIRE (G.I.)
Diamensions : 0.90 + 0.030 mm
Uniformity of Zinc coating : One Dip 1/2 Minute
Mass of zinc coating : Min 95 G/M2 .
Tnesile strength : 250 to 580 N/sq.mm
Elongation at break : Min 6%
Trotion test : Min 33 Turns
Resistivity of Armour at 20 deg : Max 14.5 x10-6
OUTER SHEATH
Type : FRLS PVC TYPE "ST-2"
Color : Black
Thickness Minimum : Min 1.24 mm
WITHOUT AGEING
Tensile Strength : Min 12.5 N/sq mm
Elongation at break : Min 150%
High Voltage Test : 2 KV for 1 minute - core to core & 2.0 KV for 1 minute core to shield
Flammability Test - As per IEC-332 Part 3 Cat. B Total volume of cumbustible
material 3.5 Litre : Charred or affected portion should not reach exceeding
2.5 mtrs
Flammability Test - As per IEEE-383 Total WT of cumbustible material per
meter 10 kg : Charred or affected portion should not reach exceeding 2.5
mtrs
Data Sheet for 2.5 sq mm
1100 Volts Grade Strd Cu Conductor, XLPE insulated, core laidup, PVC " ST2" FRLS PVC outer sheathed cable
CONDUCTOR
Resistance at 20 deg C : Max 7.410 Ohm/Km
Annealing Test for Cu : Min 22.50%
INSULATION
Thickness - Minimum / Average : Min 0.53mm/Min 0.70mm
Hot set test : Max 175%
Permanent set (200 + 3 deg C for 15 minute): Max 15%
WITHOUT AGEING : -Tensile Strength : Min 12.5 N/sq mm
Elongation at break : Min 200%
AFTER AGEING IN AIR OVEN (135 + 3 deg C for 168 Hrs):Variation in TS : Max + 12.5 N/sq mm
Variation in Elong : Max +12.5 N/sq mm
SHRINKAGE TEST (130 + 3 deg C for 1 Hrs): Max 4%
WATER ABSORPTION TEST (gravimetric)(85 + 2 deg C for 14 Days): Max 1
Mg/Cm2
Volume Resistivity- At 27 deg C : Min 1x1014 Ohm-cm
Volume Resistivity- At 90 deg C : Min 1x1012 Ohm-cm
500 mtr
500 mtr
500 mtr
500 mtr
500 mtr
500 mtr
INNER SHEATH (ST2) Thickness : Min 0.30 mm
ARMOUR WIRE
Dimensions : .40 + 0.040 mm
Uniformity of Zinc Coating : One Dip for 1/2 Minutes
Mass of Zinc Coating : Min 90 G/M2
Tensile Test : 300 to 500 N/sq. mm
Elongation : Min 10%
Tortion test : Min 43 Turn
Resistivity of Armour at 20 deg C : Max 14.5x10-6 Ohm-cm
OUTER SHEATH (ST2)
Thickness - Minimum : Min 1.24mm
WITHOUT AGEING : -Tensile Strength : Min 12.5 N/sq mm
Elongation at break : Min 150%
AFTER AGEING IN AIR OVEN (135 + 3 deg C for 168 Hrs):Tensile Strength : Min 12.5 N/sq mm
Elongation at break : Min 150%
Variation in TS : Max + 25%
Variation in Elong : Max +25%
Loss of mass of test (100 + 2 deg C for 168 Hrs): Max 2 Mg/Cm2
SHRINKAGE TEST (150 + 2 deg C for 15 Minute): Max 4%
Heat Shock Test (150 + 2 deg C for 1 Hrs): No cracks
Hot Deformation test (Depth of indentation) (80 + 2 deg C for 6 Hrs): Max
50%
Thermal stability test : 200 + 0.5 deg C : 80 Minute
High Voltage Test : 3.0 KV AC for 5 Minutes
Flammability Test :Period of burning after removal of flame : Max 60 minute
Uneffected length Min 50 mm
ADDITIONAL TEST FRLS PVC
Oxygen Index Test ASTDM 2863-77: Min 29%
Temp Index Test ASTMD 2863: Min 250 deg C
Smoke Density Test ASTMD 2843: Max 60%
HCL Gas Emmission IEC-754-I: Max 20%
Swedish Chimmeny SS 424 1475 F3
Anti Rodent & Termite Repulsion test : Presence of lead
Flammability Test As per IEC-332 Part 3: Charred or affected portion should
not reach exceeding 2.5 mtrs
Flammability Test As per IEEE-383 Part 3: Flame should not propogate upto
top end of the cable
22
23
Extension Cable for K Type Thermocouple 1PR*16 AWG (Data sheet
attached in separate worksheet)
Extension Cable for K Type Thermocouple for Metal Bearing Temp. of
Turbine, 2 Pair, Black& Red color for +ve & -ve insulation of core, Black
Outer insulation (Data sheet attached in separate Worksheet)
8000
Meter
8000
Meter
Download PDF