Z-Series™ Rooftop Units 3 to 5 Tons Net Cooling Capacity

PA C KA G E D H E AT P U M P S
ZH
Z-Series™ Rooftop Units
60 HZ
P R O D U C T S P E C I F I C AT I O N S
Bulletin No. ZHA/ZHB-036-060 (5/2015)
ASHRAE 90.1
COMPLIANT
3 to 5 Tons
Net Cooling Capacity − 36,200 to 58,000 Btuh
Net Heating Capacity − 34,200 to 58,500 Btuh
Optional Electric Heat - 5 to 22.5 kW
MODEL NUMBER IDENTIFICATION
Z H B 060 S 4 B N 1 Y
Brand/Family
Z = Z-Series
Voltage
P = 208/230V−1 phase-60hz
Y = 208/230V-3 phase-60hz
G = 460V-3 phase-60hz
J = 575V-3 phase-60hz
Unit Type
H = Packaged Heat Pump
Major Design Sequence
A = 1st Generation
B = 2nd Generation
Nominal Cooling Capacity - Tons
036 = 3 Tons
048 = 4 Tons
060 = 5 Tons
Cooling Efficiency
S = Standard Efficiency
Refrigerant Type
4 = R-410A
Minor Design Sequence
1 = 1st Revision
2 = 2nd Revision
3 = 3rd Revision
Factory Installed Electric Heat
N = No Heat
Blower Type
B = Belt Drive
FEATURES AND BENEFITS
E
I
D
G
B
C
H
F
Z-Series™ rooftop units from Allied are the new standard for cost efficient, reliable rooftop
units built for long-lasting performance that can significantly improve indoor environments.
Z-Series™ rooftop units feature:
•
•
•
•
•
•
•
•
•
Quick and Easy Retrofit - Fast installation for replacement of many existing rooftop
units - fits high volume competitor’s roof curbs
R-410A Refrigerant - Environmentally friendly
Scroll Compressors - Single speed scroll compressor is furnished on all models.
High Pressure Switch - Protects compressor.
Belt Drive Blower Motor - To maximize air performance.
Downflow or Horizontal Airflow - Easy field conversion.
Two Fork Lift Slots on Three Sides - Easy to pick up and transport units from almost
any angle.
Corrosion-Resistant Drain Pan - Provides application flexibility, durability, improved
serviceability and meets ASHRAE 62.1 requirements for drain pan slope.
Thermostatic Expansion Valve - Provides peak heating performance across the entire
application range.
Z-Series™ Packaged Heat Pump 3 to 5 Tons / Page 2
FEATURES AND BENEFITS
CONTENTS
Accessory Dimensions . . . . . . . . . . . . . . . . . . . . . . . . . . . 25
Blower Data . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 13
Cooling / Heating Ratings . . . . . . . . . . . . . . . . . . . . . . . . . 11
Dimensions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 24
Electrical Data . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 17
Electric Heat Capacities . . . . . . . . . . . . . . . . . . . . . . . . . . 20
Features And Benefits . . . . . . . . . . . . . . . . . . . . . . . . . . . .2
Model Number Identification . . . . . . . . . . . . . . . . . . . . . . . . .1
Options / Accessories . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8
Outdoor Sound Data . . . . . . . . . . . . . . . . . . . . . . . . . . . . 22
Specifications . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .10
Unit Clearances . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 21
Weight Data . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 23
APPROVALS
AHRI Certified to AHRI Standard
210/240-2008.
CSA listed.
Units are Certified by CSA.
Components bonded for grounding
to meet safety standards for
servicing required by UL, ULC and
National and Canadian Electrical
Codes.
All models are ASHRAE 90.1
compliant.
ISO 9001 Registered
Manufacturing Quality System.
WARRANTY
Limited five years on compressors.
Limited five years optional High
Performance Economizers.
Limited one year all other covered
components.
High Pressure Switch
Protects the compressor from
overload conditions such as
dirty condenser coils, blocked
refrigerant flow, or loss of outdoor
fan operation
Automatic reset.
Reversing Valve
4-way interchange reversing valve
effects a rapid change in direction
of refrigerant flow resulting in quick
changeover from cooling to heating
and vice versa.
Defrost Control
Provides a defrost cycle, if needed,
every 30 or 60 or 90 minutes
(adjustable) of compressor “on”
time at outdoor coil temperature
below 35°F. Temperature switch
mounted on outdoor coil liquid line
terminates defrost cycle.
COOLING / HEATING
SYSTEM
Designed to maximize sensible
and latent cooling performance at
design conditions.
System can operate from 35°F
to 125°F without any additional
controls.
Filter/Drier
High capacity filter/drier protects
the system from dirt and moisture.
C
R-410A Refrigerant
Non-chlorine, ozone friendly,
R-410A.
Unit is factory pre-charged with
refrigerant. See Specifications
Table.
B Compressor
Scroll compressors for high
performance, reliability and quiet
operation.
Resiliently mounted on rubber
grommets for quiet operation.
Compressor Crankcase Heater
Protects against refrigerant
migration that can occur during low
ambient operation.
Refrigerant Metering Orifice
Accurately meters refrigerant in
system.
Refrigerant control is accomplished
by exact sizing of refrigerant
metering orifice.
Coil Construction
Copper tube construction,
enhanced rippled-edge aluminum
fins, flared shoulder tubing
connections, silver soldered
construction for improved heat
transfer. Factory leak tested.
Indoor Coil
Cross row circuiting with rifled
tubing optimizes both sensible and
latent cooling capacity.
Condensate Drain Pan
Plastic pan, sloped to meet
drainage requirements of ASHRAE
62.1.
End drain connection.
D Outdoor Coil Fan Motor
Thermal overload protected, totally
enclosed, permanently lubricated
bearings, shaft down, fan guard
mount.
Outdoor Coil Fan Guard
PVC coated fan guard furnished.
Z-Series™ Packaged Heat Pump 3 to 5 Tons/ Page 3
FEATURES AND BENEFITS
COOLING / HEATING
SYSTEM (continued)
Required Selections
Cooling Capacity
Specify nominal cooling capacity of
the unit.
Options/Accessories
Field Installed
Condensate Drain Trap
Field installed only.
Available in copper or PVC.
Drain Pan Overflow Switch
Monitors condensate level in
drain pan, shuts down unit if drain
becomes clogged.
Low Ambient Kit
Cycles the outdoor fan while
allowing compressor operation in
the cooling cycle. This intermittent
fan operation allows the system
to operate without icing the
evaporator coil and losing capacity.
Designed for use in ambient
temperatures no lower than 0°F.
CABINET
E Construction
Heavy-gauge steel panels and full
perimeter heavy-gauge galvanized
steel base rail provides structural
integrity for transportation,
handling, and installation.
Base rails have rigging holes.
Three sides of the base rail have
fork slots.
Raised edges around duct and
power entry openings in the bottom
of the unit provide additional
protection against water entering
the building.
Airflow Choice
Units are shipped in downflow
(vertical) configuration, can be
field converted to horizontal airflow
configuration without the need of
a kit.
F Power Entry
Electrical lines can be brought
through the unit base or through
horizontal access knock-outs.
Optional Bottom Power Entry Kit is
available.
G Exterior Panels
Constructed of heavy-gauge,
galvanized steel with a two-layer
enamel paint finish.
H Insulation
All panels adjacent to conditioned
air are fully insulated with nonhygroscopic fiberglass insulation.
Access Panels
Access panels are provided for
the compressor, heating, controls,
blower and air filter/economizer
section.
Z-Series™ Packaged Heat Pump 3 to 5 Tons / Page 4
Options/Accessories
Factory Installed
Corrosion Protection
A completely flexible immersed
coating with an electrodeposited dry film process. (AST
ElectroFin E-Coat) Meets Mil
Spec MIL-P-53084, ASTM B117
Standard Method Salt Spray
Testing.
Indoor Corrosion Protection:
- Coated coil
Outdoor Corrosion Protection:
- Coated coil
Field Installed
Coil/Hail Guards
Constructed of heavy gauge steel,
painted to match cabinet, helps
protect outdoor coil from damage
on all three sides of cabinet.
FEATURES AND BENEFITS
CONTROLS
I BLOWER
INDOOR AIR QUALITY
Unit Control
All control voltage is provided via a
24V (secondary) transformer with
inline fuse protection.
A wide selection of supply air
blower options are available
to meet a variety of air flow
requirements.
Air Filters
Disposable 2 inch filters furnished
as standard.
Heat/Cool Staging - Capable of
up to 2 heat / 2 cool staging with a
thermostat.
Motor
Overload protected, equipped with
ball bearings. Belt drive motors
are offered on all models and are
available in several different sizes
to maximize air performance.
Indoor Air Quality (CO2) Sensor
Monitors CO2 levels adjusts
economizer dampers as needed
for Demand Control Ventilation.
Night Setback Mode - Saves
energy by closing outdoor air
dampers and operating supply fan
on thermostat demand only.
Smoke Detectors
NOTE - Smoke detectors are
not available and must be field
provided by installer.
Supply Air Blower
Forward curved blades, blower
wheel is statically and dynamically
balanced.
Equipped with ball bearings and
adjustable pulley (allows speed
change).
Required Selections
Supply Air Blower
Order blower motor horsepower
and drive kit number required
when base unit is ordered, see
Drive Kit Specifications Table.
Field Installed
ELECTRICAL
Marked & Color-Coded Wiring
All electrical wiring is color-coded
and marked to identify which
components it is connecting.
Electrical Plugs
Positive connection electrical plugs
are used to connect common
accessories or maintenance parts
for easy removal or installation.
Required Selections
Voltage Choice
Specify when ordering base unit.
Field Installed
Electric Heat
Helix wound nichrome elements,
individual element limit controls,
wiring harness. See Options /
Accessories tables for ordering
information.
NOTE - Unit Fuse Block is required
and must be ordered separately.
See Electrical/Electric Heat tables
for ordering information.
Z-Series™ Packaged Heat Pump 3 to 5 Tons/ Page 5
OPTIONS / ACCESSORIES
ECONOMIZER OPTIONS
Factory or Field Installed
Economizer (Downflow or
Horizontal)
(Standard and High Performance
Common Features)
Outdoor Air Hood is furnished.
Economizer includes Barometric
Relief Dampers with Exhaust
Hood.
Barometric Relief Dampers allow
relief of excess air, aluminum blade
dampers prevent blow back and
outdoor air infiltration during off
cycle, bird screen furnished. Hood
is furnished.
Single Sensible Temperature
Control is furnished with the
economizer
Outdoor air sensor enables
Economizer if the outdoor
temperature is less than the
setpoint of the control.
Demand Control Ventilation (DCV)
ready using optional CO2 sensors.
NOTE - Horizontal Economizer is
field installed only.
Standard Economizer Features
(Not for Title 24)
Gear-driven action, return air
and outdoor air dampers, plugin connections to unit, neoprene
seals, 24-volt, fully-modulating
spring return motor.
Standard Economizer
Control Module
The Standard
Economizer
Control Module
can be adjusted
to operate based
on outdoor air
temperatures.
Economizer Controls:
• D
amper Minimum Position
- Can be set lower than
traditional minimum air
requirements resulting in cost
savings.
• IAQ Sensor - Signals
dampers to modulate and
maintain 55°F when CO2 is
higher than the CO2 setpoint.
• Demand Control Ventilation
(DCV) LED - A steady green
Demand Control Ventilation
LED indicates the IAQ reading
is higher than setpoint and
requires more fresh air.
• Free Cool LED - A steady
green LED indicates outdoor
air is suitable for free cooling.
Free Cooling runs when outdoor
air temperature is lower than
the set temperature on the
economizer control.
NOTE: The Free Cooling
default setting for outdoor air
temperature sensor is 55°F.
High Performance
Economizer Features
Approved for California Title 24
building standards.
ASHRAE 90.1-2010 compliant.
Gear-driven action, high torque
24-volt fully-modulating spring
return damper motor, return air
and outdoor air dampers, plug-in
connections to unit, nylon bearings,
enhanced neoprene blade edge
seals and flexible stainless steel
jamb seals to minimize air leakage.
NOTE - High Performance
Economizers are not approved for
use with enthalpy controls in Title
24 applications.
High Performance
Economizer Control Module
Module
provides inputs
and outputs
to control
economizer
based on
parameter settings.
Z-Series™ Packaged Heat Pump 3 to 5 Tons / Page 6
Module automatically detects
sensors by polling to determine
which sensors are installed in
system.
Module displays any alarm
messages (fault detection
and diagnostics) as an aid in
troubleshooting.
Non-volatile memory retains
parameter settings in case of
power failure.
Keypad with four navigation
buttons and LCD screen is
furnished for setting economizer
parameters.
• Menu Up/Exit
button
returns to the main menu.
• A
rrow Up button moves
to the previous or next
parameter within the selected
menu.
• Arrow Down button moves
to the next parameter within
the selected menu.
• Select (enter) button
confirms parameter selection.
Main Menu Structure:
• S
TATUS (economizer and
system operation status)
• SETPOINTS (settings for
various setpoint parameters)
• SYSTEM SETUP (settings/
information about the system)
• ADVANCED SETUP (freeze
protection, CO2 settings,
stage 3 delay and additional
calibration settings)
• CHECKOUT (damper
positions)
• ALARMS (output signal that
can be configured for remote
alarm monitoring)
NOTE - The Free Cooling
setpoint for Title 24 applications
must be set based on the
Climate Zone where the system
is installed. See Section 140.4
“Prescriptive Requirements for
Space Conditioning Systems”
of the California Energy
Commission’s 2013 Building
Energy Efficiency Standards.
Refer to Installation Instructions
for complete setup information
and menu parameters available.
OPTIONS / ACCESSORIES
ECONOMIZER OPTIONS
(continued)
Field Installed
Single Enthalpy Temperature
Control
(Not for Title 24)
Outdoor air enthalpy sensor
enables Economizer if the outdoor
enthalpy is less than the setpoint of
the control.
EXHAUST OPTIONS
Field Installed
Power Exhaust Fan - Downflow
or Horizontal
Installs external to unit for
applications with Economizer
option. Provides exhaust air
pressure relief. Interlocked to
run when supply air blower is
operating, fan runs when outdoor
air dampers are 50% open
(adjustable), motor is overload
protected.
Fan is 12 in. diameter with 5 fan
blades. 1/2 hp motor.
OUTDOOR AIR OPTIONS
ROOF CURBS
Field Installed
Outdoor Air Dampers Downflow
Linked mechanical dampers, 0 to
35% (fixed) outdoor air adjustable,
installs in unit.
Automatic model features fully
modulating spring return damper
motor with plug-in connection.
Manual model features a slide
damper. Maximum mixed air
temperature in cooling mode:
100°F.
Hybrid Roof Curbs, Downflow
Nailer strip furnished, mates
to unit, US National Roofing
Contractors Approved, shipped
knocked down.
Roof curb can be assembled using
interlocking tabs to fasten corners
together. No tools required.
Curb can also be fastened together
with furnished hardware.
Available in 8, 14, 18, and 24 inch
heights.
Adaptor Curbs (not shown)
Curbs are regionally sourced.
Dimensions will vary based
upon the source. Contact your
local sales representative for a
detailed cut sheet with applicable
dimensions.
CEILING DIFFUSERS
Ceiling Diffusers
(Flush and Step-Down)
Aluminum grilles, large center
grille, insulated diffuser box with
flanges, hanging rings furnished,
interior transition (even air flow),
internally sealed (prevents
recirculation), adapts to T-bar
ceiling grids or plaster ceilings.
Transitions (Supply and Return)
NOTE - Ceiling Diffuser Transitions
are not furnished and must be field
fabricated.
Z-Series™ Packaged Heat Pump 3 to 5 Tons/ Page 7
OPTIONS / ACCESSORIES
Item
Catalog
No.
ZHA
ZHB
036
ZHA
ZHB
048
ZHA
ZHB
060
PVC - C1TRAP20AD2
Copper - C1TRAP10AD2
Z1SNSR90A1
Z1SNSR34A-1
76W26
76W27
99W59
99W68
X
X
X
X
X
X
X
X
X
X
X
X
1
Belt Drive - 1 hp Standard Efficiency
Belt Drive - 1.5 hp Standard Efficiency
Kit #ZA01 - 678-1035 rpm
Kit #ZA02 - 803-1226 rpm
Kit #ZA03 - 906-1383 rpm
Kit #ZA04 - 964-1471 rpm
2
Kit #ZA05 -1098-1490 rpm
2
Kit #ZA06 -1262-1634 rpm
Kit #ZAA01 - 522-784 rpm
Kit #ZAA02 - 632-875 rpm
Kit #ZAA03 - 798-1105 rpm
Factory
Factory
Factory
Factory
Factory
Factory
Factory
Factory
Factory
Factory
Factory
O
O
O
O
O
O
O
ZHA models only - Z1GARD10A-1
ZHA060 and ZHB models only - Z1GARD10AT-1
97W53
99W58
Factory
X
X
O
208/230V - 1 phase
208/230V - 3 phase
460V - 3 phase
575V - 3 phase
Z1PEKT01A-1
Factory
Factory
Factory
Factory
98W08
3
O
O
O
O
X
3
O
O
O
O
X
3
208/230V-1ph - Z1EH0050AN1P
208/230V-3ph - Z1EH0050AN1Y
460V-3ph - Z1EH0050AN1G
575V-3ph - Z1EH0050AN1J
208/230V-1ph - Z1EH0075AN1P
208/230V-3ph - Z1EH0075AN1Y
460V-3ph - Z1EH0075AN1G
575V-3ph - Z1EH0075AN1J
208/230V-1ph - Z1EH0100AN1P
208/230V-3ph - Z1EH0100AN1Y
460V-3ph - Z1EH0100AN1G
575V-3ph - Z1EH0100AN1J
208/230V-1ph - Z1EH0150AN1P
208/230V-3ph - Z1EH0150AN1Y
460V-3ph - Z1EH0150AN1G
575V-3ph - Z1EH0150AN1J
208/230V-1ph - Z1EH0225AN1P
208/230V-3ph - Z1EH0225AN1Y
460V-3ph - Z1EH0225AN1G
575V-3ph - Z1EH0225AN1J
98W96
99W01
99W06
99W11
98W97
99W02
99W07
99W12
98W98
99W03
99W08
99W13
98W99
99W04
99W09
99W14
99W00
99W05
99W10
99W15
1
X
X
X
X
1
X
X
X
X
1
X
X
X
X
1
X
X
X
X
1
X
X
X
X
1
X
X
X
X
1
X
X
X
X
1
X
X
X
X
1
X
X
X
X
1
COOLING SYSTEM
Condensate Drain Trap
Drain Pan Overflow Switch
Low Ambient Kit
Blower - SUPPLY AIR
Motors
Drive Kits
See Blower Data Tables for selection
CABINET
Coil/Hail Guards
Corrosion Protection
ELECTRICAL
Voltage
60 hz
Bottom Power Entry Kit
ELECTRIC HEAT
5 kW
7.5 kW
10 kW
15 kW
22.5 kW
ELECTRIC HEAT ACCESSORIES
Unit Fuse Block (required) - See Electrical/Electric Heat Tables for Selection
1 hp blower motor is not available for 208/230V-1ph applications.
2
1.5 hp motor is required with ZA05 and ZA06 drive kits.
3
ZHB models only.
4
ZHA models only.
1
NOTE - The catalog and model numbers that appear here are for ordering field installed accessories only.
OX - Field Installed or Configure to Order (Factory Installed)
O - Configure to Order (Factory Installed)
X - Field Installed.
Z-Series™ Packaged Heat Pump 3 to 5 Tons / Page 8
O
O
4
O
O
O
O
3
O
3
O
4
3
X
X
X
O
X
X
O
O
O
O
O
X
X
X
X
X
1
X
X
X
X
1
X
X
X
X
1
X
X
X
X
1
X
X
X
X
X
OPTIONS / ACCESSORIES
Item
Catalog
No.
ZHA
ZHB
036
ZHA
ZHB
048
ZHA
ZHB
060
ECONOMIZER
Standard Economizer With Outdoor Air Hood (Not for Title 24)
Standard Economizer (Downflow)
Includes Barometric Relief Dampers and Exhaust Hood
Z1ECON30A-1
98W09
OX
OX
OX
Standard Economizer (Horizontal)
Includes Barometric Relief Dampers and Exhaust Hood
Z1ECON16A-1
98W68
X
X
X
C1SNSR64FF1
53W64
X
X
X
Standard Economizer Controls (Not for Title 24)
Single Enthalpy Control
High Performance Economizer With Outdoor Air Hood (Approved for California Title 24 Building Standards)
High Performance Economizer (Downflow)
Includes Barometric Relief Dampers and Exhaust Hood
Z1ECON32A-1
10U51
OX
OX
OX
High Performance Economizer (Horizontal)
Includes Barometric Relief Dampers and Exhaust Hood
Z1ECON33A-1
10U52
X
X
X
C1SNSR61FF1
11G21
X
X
X
Motorized
Z1DAMP21A-1
95W74
X
X
X
Manual
Z1DAMP11A-1
95W73
X
X
X
208/230V-1 or 3ph - Z1PWRE10A-1P
21E01
X
X
X
460V-3ph - Z1PWRE10A-1G
23E01
X
X
X
208/230V-1 or 3ph - Z1PWRE15A-1P
24E01
X
X
X
460V-3ph - Z1PWRE15A-1G
28E01
X
X
X
575V-3ph - Z1TRFM20A-1J
59E02
X
X
X
High Performance Economizer Controls (Not for Title 24)
Single Enthalpy Control
OUTDOOR AIR
Outdoor Air Dampers - Includes Outdoor Air Hood
Power EXhaust FAN
Standard Static (Downflow)
Standard Static (Horizontal)
575V Transformer Kit
NOTE - Order 575V Transformer Kit with 208/230V Power Exhaust Fan for 575V applications.
Indoor Air Quality
Indoor Air Quality (Co2) Sensors
Sensor - Wall-mount, off-white plastic cover with LCD display
C0SNSR50AE1L
77N39
X
X
X
Sensor - Wall-mount, black plastic case, no display, rated for plenum
mounting
C0SNSR53AE1L
87N54
X
X
X
CO2 Sensor Duct Mounting Kit - for downflow applications
C0MISC19AE1
85L43
X
X
X
Aspiration Box - for duct mounting non-plenum rated CO2 sensor (77N39)
C0MISC16AE1
90N43
X
X
X
8 in. height
Z1CURB70A-1
11F76
X
X
X
14 in. height
Z1CURB71A-1
11F77
X
X
X
18 in. height
Z1CURB72A-1
11F78
X
X
X
24 in. height
Z1CURB73A-1
11F79
X
X
X
RTD9-65-R
27G87
X
X
X
FD9-65-R
27G86
X
X
X
ROOF CURBS
Hybrid Roof Curbs, Downflow
CEILING DIFFUSERS
Step-Down - Order one
Flush - Order one
NOTE - Ceiling Diffuser Transitions are not furnished and must be field fabricated.
NOTE - The catalog and model numbers that appear here are for ordering field installed accessories only.
OX - Field Installed or Configure to Order (Factory Installed)
O - Configure to Order (Factory Installed)
X - Field Installed.
Z-Series™ Packaged Heat Pump 3 to 5 Tons/ Page 9
SPECIFICATIONS - ZHA
General Data
Nominal Tonnage
Model No.
Efficiency Type
Cooling
Gross Cooling Capacity - Btuh
1
Performance
Net Cooling Capacity - Btuh
AHRI Rated Air Flow - cfm
2
Sound Rating Number (SRN) (dBA) Cooling
Heating
Total Unit Power - kW
1
SEER (Btuh/Watt)
1
EER (Btuh/Watt)
Refrigerant
Type
Charge Furnished
Heating
Total High Heating Capacity - Btuh
Performance
Total Unit Power - kW
1
COP
HSPF - Region IV (Region V)
Total Low Heating Capacity - Btuh
Total Unit Power - kW
COP
Electric Heat Available - See page 8
Compressor Type (one per unit)
Outdoor Coil
Net face area - sq. ft.
Tube diameter - in.
Number of rows
Fins / inch
Expansion device type
Outdoor
Motor HP
Coil Fan
Motor rpm
Total motor watts
Diameter - in.
Number of blades
Total air volume - cfm
Indoor Coil
Net face area - sq. ft.
Tube diameter - in.
Number of rows
Fins per inch
Drain Connection (no.and size) - in.
Expansion device type
3
Indoor
Nominal Motor HP
Blower & Drive
Maximum Usable Motor HP
Selection
Available Drive Kits
Wheel nominal diameter x width - in.
Filters
Electrical Characteristics - 60 Hz
Type
Number and size - in.
3 Ton
4 Ton
5 Ton
ZHA036S4B
ZHA048S4B
ZHA060S4B
Standard
Standard
Standard
37,600
48,500
60,700
36,200
46,500
58,000
1310
1610
1940
79
79
83
80
80
83
3.1
4.3
5.3
13.00
13.00
13.00
11.3
10.8
10.9
R-410A
R-410A
R-410A
11 lbs. 12 oz.
12 lbs. 8 oz.
15 lbs. 3 oz.
34,200
45,000
58,500
2.9
3.9
4.9
3.42
3.40
3.50
7.70 (6.70)
7.70 (6.70)
7.70 (6.70)
20,400
27,400
33,400
2.8
3.6
4.5
2.18
2.24
2.20
5, 7.5, 10, 15 kW
5, 7.5, 10, 15, 22.5 kW
Scroll
Scroll
Scroll
16.1
16.1
19.9
3/8
3/8
3/8
2
2
2
20
20
20
Balanced port TXV, removable head
(1) 1/4 (PSC)
(1) 1/4 (PSC)
(1) 1/3 (PSC)
825
825
1075
300
300
340
(1) 22
(1) 22
(1) 22
4
4
3
3200
3200
3600
8.4
8.4
9.6
3/8
3/8
3/8
3
3
3
14
14
14
(1) 1 NPT
(1) 1 NPT
(1) 1 NPT
Fixed Orifice
Fixed Orifice
Fixed Orifice
1 hp, 1.5 hp
1 hp, 1.5 hp
1 hp, 1.5 hp
1.15 hp, 1.7 hp
1.15 hp, 1.7 hp
1.15 hp, 1.7 hp
Kit #ZA01
Kit #ZA02
Kit #ZA03
678-1035 rpm
803-1226 rpm
906-1383 rpm
Kit #ZA04
964-1471 rpm
10 x 10
(4) 14 x 20 x 2
208/230V,
460V & 575V
3 phase
Kit #ZA05
1098-1490 rpm
10 x 10
Disposable
(4) 14 x 20 x 2
208/230V
460V & 575V
3 phase
5
Kit #ZA06
1262-1634 rpm
10 x 10
5
(4) 16 x 20 x 2
208/230V
460V & 575V
3 phase
NOTE - Net capacity includes evaporator blower motor heat deduction. Gross capacity does not include evaporator blower motor heat deduction.
1
AHRI Certified to AHRI Standard 210/240:
Cooling Ratings - 95°F outdoor air temperature and 80°F db/67°F wb entering indoor coil air.
High Temperature Heating Ratings - 47°F db/43°F wb outdoor air temperature and 70°F entering indoor coil air.
Low Temperature Heating Ratings - 17°F db/15°F wb outdoor air temperature and 70°F entering indoor coil air.
2
Sound Rating Number (SRN) rated in accordance with test conditions included in ANSI/AHRI Standard 270-2008.
3
Using total air volume and system static pressure requirements determine from blower performance tables rpm and motor hp required. Maximum usable hp of motors
furnished are shown. In Canada, nominal motor hp is also maximum usable motor hp output. If motors of comparable hp are used, be sure to keep within the service
factor limitations outlined on the motor nameplate.
5
1.5 hp motor is required with ZA05 and ZA06 drive kits.
Z-Series™ Packaged Heat Pump 3 to 5 Tons / Page 10
SPECIFICATIONS - ZHB
General Data
Nominal Tonnage
Model No.
Efficiency Type
Cooling
Gross Cooling Capacity - Btuh
1
Net Cooling Capacity - Btuh
Performance
AHRI Rated Air Flow - cfm
2
Sound Rating Number (SRN) (dBA) Cooling
Heating
Total Unit Power - kW
1
SEER (Btuh/Watt)
1
EER (Btuh/Watt)
Refrigerant
Type
Charge Furnished
Heating
Total High Heating Capacity - Btuh
Total Unit Power - kW
Performance
1
COP
HSPF - Region IV (Region V)
Total Low Heating Capacity - Btuh
Total Unit Power - kW
COP
Electric Heat Available - See page 8
Compressor Type (one per unit)
Outdoor Coil
Net face area - sq. ft.
Tube diameter - in.
Number of rows
Fins / inch
Expansion device type
Outdoor
Motor HP
Motor rpm
Coil Fan
Total motor watts
Diameter - in.
Number of blades
Total air volume - cfm
Indoor Coil
Net face area - sq. ft.
Tube diameter - in.
Number of rows
Fins per inch
Drain Connection (no.and size) - in.
Expansion device type
3
Indoor
Nominal Motor HP
Maximum Usable Motor HP
Blower & Drive
Available Drive Kits
Selection
3 Ton
4 Ton
5 Ton
ZHB036S4B
ZHB048S4B
ZHB060S4B
Standard
Standard
Standard
36,300
47,900
59,700
35,000
46,500
58,000
1260
1520
2015
79
77
82
80
78
82
3.1
4.2
5.2
14.00
14.00
14.00
11.40
11.20
11.20
R-410A
R-410A
R-410A
14 lbs. 8 oz.
16 lbs. 5 oz.
14 lbs. 4 oz.
34,200
45,000
55,000
2.9
3.8
4.5
3.50
3.50
3.60
8.00 (6.70)
8.00 (6.70)
8.00 (6.70)
20,000
26,100
32,500
2.7
3.5
4.2
2.20
2.20
2.25
5, 7.5, 10, 15 kW
5, 7.5, 10, 15, 22.5 kW
Scroll
Scroll
Scroll
19.9
19.9
19.9
3/8
3/8
3/8
2
2
2
20
20
20
Balanced port TXV, removable head
(1) 1/4
(1) 1/4
(1) 1/3
825
825
1075
300
300
350
(1) 22
(1) 22
(1) 22
4
4
3
3335
3335
3600
9.6
10.8
10.8
3/8
3/8
3/8
3
3
3
12
12
12
(1) 1 NPT
(1) 1 NPT
(1) 1 NPT
Fixed Orifice
Fixed Orifice
Fixed Orifice
4
4
4
1 hp, 1.5 hp
1 hp, 1.5 hp
1 hp, 1.5 hp
1.15 hp, 1.7 hp
1.15 hp, 1.7 hp
1.15 hp, 1.7 hp
Kit #ZA01
Kit #ZA02
Kit #ZAA01
678-1035 rpm
803-1226 rpm
522-784 rpm
Kit #ZA04
964-1471 rpm
Kit #ZA05
1098-1490 rpm
5
Kit #ZAA02
632-875 rpm
Kit #ZAA03
798-1105 rpm
15 x 9
5
Wheel nominal diameter x width - in.
Filters
Electrical Characteristics - 60 Hz
Type
Number and size - in.
10 x 10
(4) 16 x 20 x 2
10 x 10
Disposable
(4) 16 x 20 x 2
208/230V
1 phase
208/230V,
1 phase
(2) 16 X 20 X 2
(2) 20 X 20 X 2
208/230V,
1 phase
208/230V,
460V & 575V
3 phase
208/230V
460V & 575V
3 phase
208/230V
460V & 575V
3 phase
NOTE - Net capacity includes evaporator blower motor heat deduction. Gross capacity does not include evaporator blower motor heat deduction.
1
AHRI Certified to AHRI Standard 210/240:
Cooling Ratings - 95°F outdoor air temperature and 80°F db/67°F wb entering indoor coil air.
High Temperature Heating Ratings - 47°F db/43°F wb outdoor air temperature and 70°F entering indoor coil air.
Low Temperature Heating Ratings - 17°F db/15°F wb outdoor air temperature and 70°F entering indoor coil air.
2
Sound Rating Number (SRN) rated in accordance with test conditions included in ANSI/AHRI Standard 270-2008.
3
Using total air volume and system static pressure requirements determine from blower performance tables rpm and motor hp required. Maximum usable hp of motors
furnished are shown. In Canada, nominal motor hp is also maximum usable motor hp output. If motors of comparable hp are used, be sure to keep within the service
factor limitations outlined on the motor nameplate.
4
1 hp blower motor is not available for 208/230V-1ph applications.
5
1.5 hp motor is required with ZA05 and ZAA03 drive kits.
Z-Series™ Packaged Heat Pump 3 to 5 Tons/ Page 11
COOLING / HEATING RATINGS - ZHA
NOTE − For Temperatures and Capacities not shown in tables, see bulletin − Cooling Unit Rating Table Correction Factor Data in Miscellaneous Engineering Data section.
3 TON COOLING STANDARD EFFICIENCY ZHA036S4
Outdoor Air Temperature Entering Outdoor Coil
Entering
85°F
95°F
105°F
115°F
Total
Wet
Air
Total Comp. Sensible To Total Total Comp. Sensible To Total Total Comp. Sensible To Total Total Comp. Sensible To Total
Bulb
Volume Cool Motor
Ratio (S/T)
Ratio (S/T)
Ratio (S/T)
Ratio (S/T)
Cool Motor
Cool Motor
Cool Motor
TemperCap. Input
Cap. Input
Cap. Input
Cap. Input
Dry Bulb
Dry Bulb
Dry Bulb
Dry Bulb
ature
cfm
kBtuh
kW
75°F 80°F 85°F kBtuh
kW
75°F 80°F 85°F kBtuh
kW
75°F 80°F 85°F kBtuh
kW
75°F 80°F 85°F
960
34.6
2.05 0.74 0.88
1
33.2
2.35
0.75 0.89
1
31.4
2.68 0.76 0.92
1
28.6
3.01
0.79 0.96
1
63°F
1200
36.5
2.06 0.79 0.95
1
35.1
2.36
0.81 0.97
1
33
2.68 0.83
1
1
30.3
3.03
0.86
1
1
1440
38
2.06 0.85
1
1
36.6
2.36
0.86
1
1
34.7
2.7
0.89
1
1
31.8
3.04
0.94
1
1
960
36.8
2.06 0.58 0.71 0.84 35.4
2.36
0.59 0.72 0.86 33.4
2.69 0.59 0.74 0.88 30.3
3.02
0.61 0.77 0.93
67°F
1200
38.7
2.07 0.61 0.77 0.92 37.1
2.37
0.62 0.78 0.94 34.9
2.7
0.63 0.81 0.97 31.6
3.03
0.66 0.85
1
1440
40
2.07 0.65 0.82 0.99 38.2
2.37
0.66 0.84
1
35.9
2.7
0.67 0.87
1
32.4
3.04
0.7
0.92
1
960
38.9
2.07 0.44 0.56 0.69 37.3
2.37
0.44 0.57
0.7
35.2
2.7
0.44 0.58 0.72 31.9
3.04
0.45
0.6
0.75
71°F
1200
40.9
2.08 0.45 0.6 0.74 39.1
2.38
0.45 0.61 0.76 36.7
2.71 0.46 0.62 0.78 33.2
3.05
0.47 0.65 0.83
1440
42.4
2.08 0.47 0.64 0.8
40.4
2.39
0.47 0.65 0.82 37.8
2.72 0.47 0.67 0.85 34.1
3.05
0.49
0.7
0.9
3 TON HEATING STANDARD EFFICIENCY ZHA036S4
Indoor Coil
Air Volume
70°F Dry
Bulb
cfm
960
1200
1440
Total
Heating
Capacity
kBtuh
42.2
42.4
42.6
65°F
Comp.
Motor Input
Input
kW
2.55
2.37
2.27
Total
Heating
Capacity
kBtuh
32.7
32.9
33.2
Air Temperature Entering Outdoor Coil
25°F
5°F
Comp.
Total
Comp.
Total
Comp.
Motor Input
Heating
Motor Input
Heating
Motor Input
Input
Capacity
Input
Capacity
Input
kW
kBtuh
kW
kBtuh
kW
2.39
23.1
2.23
15.1
2.01
2.21
23.3
2.04
15.3
1.82
2.11
23.6
1.95
15.5
1.72
45°F
Total
Heating
Capacity
kBtuh
7.8
7.9
8.2
-15°F
Comp.
Motor Input
Input
kW
1.51
1.32
1.23
4 TON COOLING STANDARD EFFICIENCY ZHA048S4
Outdoor Air Temperature Entering Outdoor Coil
Entering
85°F
95°F
105°F
115°F
Total
Wet
Air
Total Comp. Sensible To Total Total Comp. Sensible To Total Total Comp. Sensible To Total Total Comp. Sensible To Total
Bulb
Volume Cool Motor
Ratio (S/T)
Ratio (S/T)
Ratio (S/T)
Ratio (S/T)
Cool Motor
Cool Motor
Cool Motor
TemperCap. Input
Cap. Input
Cap. Input
Cap. Input
Dry Bulb
Dry Bulb
Dry Bulb
Dry Bulb
ature
cfm
kBtuh
kW
75°F 80°F 85°F kBtuh
kW
75°F 80°F 85°F kBtuh
kW
75°F 80°F 85°F kBtuh
kW
75°F 80°F 85°F
1280
46.3
2.99 0.73 0.88
1
41.9
3.39
0.73
0.9
1
37.3
3.85 0.74 0.93
1
32.5
4.39
0.76 0.97
1
63°F
1600
49.4
3.01 0.79 0.96
1
44.8
3.41
0.81 0.98
1
40.2
3.87 0.83
1
1
35.6
4.41
0.86
1
1
1920
52
3.03 0.85
1
1
47.7
3.42
0.87
1
1
43.2
3.89
0.9
1
1
38.4
4.44
0.94
1
1
1280
50.1
3.01 0.56 0.71 0.85 45.6
3.41
0.55 0.71 0.87 40.9
3.87 0.54 0.72 0.89 35.7
4.41
0.53 0.74 0.93
67°F
1600
53.2
3.03
0.6 0.77 0.93 48.4
3.43
0.6
0.79 0.95 43.4
3.9
0.6 0.81 0.98
38
4.43
0.6
0.84
1
1920
55.3
3.05 0.64 0.84 0.99 50.4
3.45
0.64 0.86
1
45.1
3.91 0.65 0.88
1
39.5
4.45
0.66 0.92
1
1280
53.8
3.03
0.4 0.55 0.69 49.3
3.43
0.39 0.54 0.69 44.3
3.9
0.36 0.54 0.71 39.1
4.44
0.33 0.53 0.72
71°F
1600
57
3.06 0.43 0.59 0.75 52.1
3.46
0.41 0.59 0.77
47
3.93 0.39 0.6 0.79 41.5
4.47
0.37
0.6
0.82
1920
59.5
3.08 0.45 0.64 0.82 54.3
3.48
0.43 0.64 0.84 48.8
3.95 0.42 0.65 0.86
43
4.49
0.4
0.67
0.9
4 TON HEATING STANDARD EFFICIENCY ZHA048S4
Indoor Coil
Air Volume
70°F Dry
Bulb
cfm
1280
1600
1920
Total
Heating
Capacity
kBtuh
54.5
55.2
55.9
65°F
Comp.
Motor Input
Input
kW
3.33
3.12
3
Total
Heating
Capacity
kBtuh
42.3
43.1
43.8
Air Temperature Entering Outdoor Coil
25°F
5°F
Comp.
Total
Comp.
Total
Comp.
Motor Input
Heating
Motor Input
Heating
Motor Input
Input
Capacity
Input
Capacity
Input
kW
kBtuh
kW
kBtuh
kW
3.12
29.7
2.91
20
2.64
2.91
30.5
2.7
20.8
2.43
2.79
31.2
2.58
21.5
2.31
45°F
Z-Series™ Packaged Heat Pump 3 to 5 Tons / Page 12
Total
Heating
Capacity
kBtuh
9.9
10.7
11.4
-15°F
Comp.
Motor Input
Input
kW
1.98
1.77
1.64
COOLING / HEATING RATINGS - ZHA
NOTE − For Temperatures and Capacities not shown in tables, see bulletin − Cooling Unit Rating Table Correction Factor Data in Miscellaneous Engineering Data section.
5 TON COOLING STANDARD EFFICIENCY ZHA060S4
Outdoor Air Temperature Entering Outdoor Coil
Entering
85°F
95°F
105°F
115°F
Total
Wet
Air
Total Comp. Sensible To Total Total Comp. Sensible To Total Total Comp. Sensible To Total Total Comp. Sensible To Total
Bulb
Volume Cool Motor
Ratio (S/T)
Ratio (S/T)
Ratio (S/T)
Ratio (S/T)
Cool Motor
Cool Motor
Cool Motor
TemperCap. Input
Cap. Input
Cap. Input
Cap. Input
Dry Bulb
Dry Bulb
Dry Bulb
Dry Bulb
ature
cfm
kBtuh
kW
75°F 80°F 85°F kBtuh
kW
75°F 80°F 85°F kBtuh
kW
75°F 80°F 85°F kBtuh
kW
75°F 80°F 85°F
1600
58.4
3.7
0.73 0.88
1
53.3
4.17
0.74
0.9
1
47.8
4.72 0.75 0.93
1
42.1
5.37
0.77 0.96
1
63°F
2000
62
3.72 0.79 0.95
1
56.8
4.2
0.81 0.98
1
51.1
4.75 0.83
1
1
45.7
5.42
0.86
1
1
2400
65.2
3.74 0.85
1
1
60.2
4.22
0.87
1
1
54.7
4.79
0.9
1
1
49
5.46
0.94
1
1
1600
62.9
3.72 0.56 0.71 0.84 57.7
4.21
0.55 0.71 0.86 51.9
4.76 0.55 0.73 0.89 45.9
5.42
0.54 0.75 0.93
67°F
2000
66.7
3.75
0.6 0.77 0.92 61.2
4.23
0.6
0.79 0.95 55.1
4.79
0.6 0.81 0.98 48.7
5.46
0.6
0.84
1
2400
69.5
3.77 0.64 0.83 0.98 63.5
4.25
0.64 0.85
1
57.3
4.81 0.65 0.88
1
50.7
5.48
0.66 0.91
1
1600
67.4
3.75 0.41 0.55 0.68 62.1
4.24
0.39 0.55 0.69 56.1
4.8
0.38 0.54 0.71
50
5.47
0.35 0.54 0.73
71°F
2000
71.3
3.78 0.43 0.59 0.75 65.7
4.27
0.42 0.59 0.77 59.5
4.84
0.4
0.6 0.79 52.8
5.5
0.39
0.6
0.82
2400
74.4
3.8
0.45 0.63 0.81 68.3
4.29
0.44 0.64 0.83 61.7
4.86 0.43 0.65 0.86 54.9
5.54
0.42 0.67 0.89
5 TON HEATING STANDARD EFFICIENCY ZHA060S4
Indoor Coil
Air Volume
70°F Dry
Bulb
cfm
1600
2000
2400
Total
Heating
Capacity
kBtuh
72.9
73.7
74.4
65°F
Comp.
Motor Input
Input
kW
4.28
4.04
3.9
Total
Heating
Capacity
kBtuh
55.2
56
56.7
Air Temperature Entering Outdoor Coil
25°F
5°F
Comp.
Total
Comp.
Total
Comp.
Motor Input
Heating
Motor Input
Heating
Motor Input
Input
Capacity
Input
Capacity
Input
kW
kBtuh
kW
kBtuh
kW
3.98
36.8
3.68
23.8
3.28
3.74
37.6
3.44
24.6
3.04
3.6
38.3
3.29
25.3
2.9
45°F
Total
Heating
Capacity
kBtuh
12.1
13
13.6
-15°F
Comp.
Motor Input
Input
kW
2.45
2.21
2.07
Z-Series™ Packaged Heat Pump 3 to 5 Tons/ Page 13
COOLING / HEATING RATINGS - ZHB
NOTE − For Temperatures and Capacities not shown in tables, see bulletin − Cooling Unit Rating Table Correction Factor Data in Miscellaneous Engineering Data section.
3 TON COOLING STANDARD EFFICIENCY ZHB036S4
Outdoor Air Temperature Entering Outdoor Coil
Entering
85°F
95°F
105°F
115°F
Total
Wet
Air
Total Comp. Sensible To Total Total Comp. Sensible To Total Total Comp. Sensible To Total Total Comp. Sensible To Total
Bulb
Volume Cool Motor
Ratio (S/T)
Ratio (S/T)
Ratio (S/T)
Ratio (S/T)
Cool Motor
Cool Motor
Cool Motor
TemperCap. Input
Cap. Input
Cap. Input
Cap. Input
Dry Bulb
Dry Bulb
Dry Bulb
Dry Bulb
ature
cfm
kBtuh
kW
75°F 80°F 85°F kBtuh
kW
75°F 80°F 85°F kBtuh
kW
75°F 80°F 85°F kBtuh
kW
75°F 80°F 85°F
960
34.7
2.11
0.7 0.85
1
31.7
2.38
0.7
0.88
1
28.6
2.7
0.72 0.92
1
25.4
3.08
0.74 0.96
1
63°F
1200
36.9
2.12 0.76 0.95
1
33.8
2.39
0.78 0.98
1
30.7
2.71
0.8
1
1
27.7
3.09
0.84
1
1
1440
38.9
2.13 0.83
1
1
36
2.4
0.85
1
1
33
2.73 0.89
1
1
29.7
3.09
0.93
1
1
960
37.3
2.12 0.54 0.68 0.82 34.3
2.4
0.53 0.68 0.84 31.1
2.71 0.53 0.7 0.87 27.7
3.08
0.53 0.72 0.92
67°F
1200
39.6
2.13 0.58 0.74 0.91 36.3
2.4
0.58 0.76 0.94 32.9
2.73 0.58 0.78 0.98 29.4
3.09
0.59 0.81
1
1440
41.2
2.14 0.61 0.8 0.99 37.8
2.41
0.62 0.83
1
34.3
2.73 0.63 0.86
1
30.5
3.09
0.64 0.91
1
960
40
2.13 0.39 0.53 0.66 36.8
2.41
0.38 0.52 0.66 33.6
2.72 0.37 0.52 0.68
30
3.09
0.35 0.52
0.7
71°F
1200
42.4
2.15 0.41 0.57 0.72
39
2.42
0.4
0.57 0.73 35.5
2.73 0.39 0.58 0.75 31.8
3.1
0.38 0.58 0.79
1440
44
2.16 0.43 0.61 0.78 40.5
2.43
0.42 0.62 0.81 36.9
2.74 0.42 0.62 0.84
33
3.11
0.41 0.64 0.88
3 TON HEATING STANDARD EFFICIENCY ZHB036S4
Indoor Coil
Air Volume
70°F Dry
Bulb
cfm
960
1200
1440
Total
Heating
Capacity
kBtuh
41.2
41.9
42.5
65°F
Comp.
Motor Input
Input
kW
2.49
2.32
2.23
Total
Heating
Capacity
kBtuh
32
32.7
33.3
Air Temperature Entering Outdoor Coil
25°F
5°F
Comp.
Total
Comp.
Total
Comp.
Motor Input
Heating
Motor Input
Heating
Motor Input
Input
Capacity
Input
Capacity
Input
kW
kBtuh
kW
kBtuh
kW
2.38
22.6
2.27
15.1
2.07
2.22
23.3
2.11
15.9
1.91
2.13
23.8
2.02
16.4
1.82
45°F
Total
Heating
Capacity
kBtuh
7.5
8.2
8.7
-15°F
Comp.
Motor Input
Input
kW
1.54
1.38
1.29
4 TON COOLING STANDARD EFFICIENCY ZHB048S4
Outdoor Air Temperature Entering Outdoor Coil
Entering
85°F
95°F
105°F
115°F
Total
Wet
Air
Total Comp. Sensible To Total Total Comp. Sensible To Total Total Comp. Sensible To Total Total Comp. Sensible To Total
Bulb
Volume Cool Motor
Ratio (S/T)
Ratio (S/T)
Ratio (S/T)
Ratio (S/T)
Cool Motor
Cool Motor
Cool Motor
TemperCap. Input
Cap. Input
Cap. Input
Cap. Input
Dry Bulb
Dry Bulb
Dry Bulb
Dry Bulb
ature
cfm
kBtuh
kW
75°F 80°F 85°F kBtuh
kW
75°F 80°F 85°F kBtuh
kW
75°F 80°F 85°F kBtuh
kW
75°F 80°F 85°F
1280
45.5
2.92 0.69 0.85
1
41.9
3.32
0.7
0.87
1
38.2
3.78 0.71 0.9
1
34.1
4.32
0.73 0.95
1
63°F
1600
48.4
2.93 0.75 0.94
1
44.7
3.32
0.77 0.97
1
40.9
3.78 0.79
1
1
37
4.32
0.82
1
1
1920
50.9
2.93 0.81
1
1
47.4
3.35
0.84
1
1
43.7
3.81 0.87
1
1
39.7
4.32
0.91
1
1
1280
49
2.93 0.53 0.67 0.81 45.3
3.33
0.53 0.68 0.83 41.3
3.78 0.52 0.69 0.86 37.1
4.33
0.53 0.71
0.9
67°F
1600
51.7
2.93 0.57 0.73 0.9
47.8
3.35
0.57 0.74 0.93 43.7
3.79 0.57 0.76 0.97 39.2
4.33
0.58 0.79
1
1920
53.8
2.94
0.6 0.79 0.98 49.7
3.35
0.61 0.81
1
45.4
3.8
0.62 0.84
1
40.8
4.33
0.63 0.88
1
1280
52.3
2.93 0.39 0.52 0.65 48.5
3.35
0.38 0.52 0.66 44.5
3.8
0.37 0.52 0.67 40.1
4.35
0.35 0.52 0.69
71°F
1600
55.3
2.94 0.41 0.56 0.71 51.3
3.35
0.4
0.56 0.72
47
3.82 0.39 0.57 0.74 42.3
4.35
0.38 0.58 0.77
1920
57.4
2.95 0.43 0.6 0.77 53.1
3.37
0.42
0.6
0.79 48.8
3.84 0.41 0.62 0.82 43.8
4.35
0.41 0.63 0.86
4 TON HEATING STANDARD EFFICIENCY ZHB048S4
Indoor Coil
Air Volume
70°F Dry
Bulb
cfm
1280
1600
1920
Total
Heating
Capacity
kBtuh
50.8
51.8
52.5
65°F
Comp.
Motor Input
Input
kW
3.58
3.35
3.21
Total
Heating
Capacity
kBtuh
43.4
44.3
45
Air Temperature Entering Outdoor Coil
25°F
5°F
Comp.
Total
Comp.
Total
Comp.
Motor Input
Heating
Motor Input
Heating
Motor Input
Input
Capacity
Input
Capacity
Input
kW
kBtuh
kW
kBtuh
kW
3.18
36.2
2.77
25.6
2.42
2.95
37.1
2.55
26.5
2.19
2.82
37.9
2.41
27.3
2.06
45°F
Z-Series™ Packaged Heat Pump 3 to 5 Tons / Page 14
Total
Heating
Capacity
kBtuh
12.2
13.1
13.9
-15°F
Comp.
Motor Input
Input
kW
1.85
1.62
1.48
COOLING / HEATING RATINGS - ZHB
NOTE − For Temperatures and Capacities not shown in tables, see bulletin − Cooling Unit Rating Table Correction Factor Data in Miscellaneous Engineering Data section.
5 TON COOLING STANDARD EFFICIENCY ZHB060S4
Outdoor Air Temperature Entering Outdoor Coil
Entering
85°F
95°F
105°F
115°F
Total
Wet
Air
Total Comp. Sensible To Total Total Comp. Sensible To Total Total Comp. Sensible To Total Total Comp. Sensible To Total
Bulb
Volume Cool Motor
Ratio (S/T)
Ratio (S/T)
Ratio (S/T)
Ratio (S/T)
Cool Motor
Cool Motor
Cool Motor
TemperCap. Input
Cap. Input
Cap. Input
Cap. Input
Dry Bulb
Dry Bulb
Dry Bulb
Dry Bulb
ature
cfm
kBtuh
kW
75°F 80°F 85°F kBtuh
kW
75°F 80°F 85°F kBtuh
kW
75°F 80°F 85°F kBtuh
kW
75°F 80°F 85°F
1600
56.7
3.61 0.68 0.86
1
50.2
4.08
0.68 0.87
1
43.5
4.65 0.68 0.9
1
36.6
5.32
0.68 0.94
1
63°F
2000
61.2
3.63 0.75 0.95
1
54.6
4.11
0.76 0.98
1
47.7
4.68 0.78
1
1
41.2
5.36
0.8
1
1
2400
65.3
3.66 0.82
1
1
58.9
4.14
0.84
1
1
52.4
4.7
0.86
1
1
45.4
5.38
0.9
1
1
1600
62.3
3.64 0.51 0.67 0.82 55.6
4.12
0.49 0.66 0.84 48.7
4.69 0.46 0.66 0.86 41.3
5.34
0.43 0.67
0.9
67°F
2000
66.8
3.66 0.56 0.74 0.91 59.7
4.14
0.54 0.74 0.94 52.4
4.71 0.53 0.76 0.97 44.7
5.38
0.51 0.78
1
2400
69.9
3.68
0.6
0.8 0.99 62.7
4.16
0.59 0.82
1
55.1
4.72 0.59 0.84
1
47.1
5.39
0.58 0.88
1
1600
67.9
3.66 0.36 0.51 0.65 61.2
4.15
0.33 0.49 0.65 53.9
4.71 0.28 0.47 0.65 46.5
5.4
0.24 0.45 0.65
71°F
2000
72.6
3.69 0.39 0.56 0.72 65.4
4.18
0.36 0.55 0.73 57.8
4.74 0.33 0.54 0.74 49.8
5.41
0.28 0.52 0.76
2400
75.9
3.71 0.41 0.6 0.78 68.4
4.19
0.39
0.6
0.8
60.5
4.76 0.36 0.59 0.82 52.2
5.44
0.32
0.6
0.86
5 TON HEATING STANDARD EFFICIENCY ZHB060S4
Indoor Coil
Air Volume
70°F Dry
Bulb
cfm
1600
2000
2400
Total
Heating
Capacity
kBtuh
61.7
62.7
63.7
65°F
Comp.
Motor Input
Input
kW
3.84
3.59
3.45
Total
Heating
Capacity
kBtuh
52.8
53.9
54.8
Air Temperature Entering Outdoor Coil
25°F
5°F
Comp.
Total
Comp.
Total
Comp.
Motor Input
Heating
Motor Input
Heating
Motor Input
Input
Capacity
Input
Capacity
Input
kW
kBtuh
kW
kBtuh
kW
3.65
44.4
3.46
31.7
3.14
3.4
45.5
3.21
32.8
2.9
3.26
46.4
3.07
33.7
2.75
45°F
Total
Heating
Capacity
kBtuh
15.1
16.2
17.1
-15°F
Comp.
Motor Input
Input
kW
2.34
2.1
1.95
Z-Series™ Packaged Heat Pump 3 to 5 Tons/ Page 15
BLOWER DATA - BELT DRIVE - ZHA036
BLOWER TABLE INCLUDES RESISTANCE FOR BASE UNIT ONLY WITH DRY INDOOR COIL AND AIR FILTERS IN PLACE.
FOR ALL UNITS ADD:
1 - Any factory installed options air resistance (heat section, economizer, wet coil, etc.).
2 - Any field installed accessories air resistance (duct resistance, diffuser, etc.).
See page 22 for blower motors and drives and wet coil and options/accessory air resistance data.
DOWNFLOW
External Static - in. w.g.
Air
Volume
cfm
RPM
900
562
0.16
629
1000
586
0.18
1100
612
0.2
1200
641
1300
673
1400
1500
0.10
0.20
BHP
RPM
0.30
BHP
RPM
0.40
BHP
RPM
0.50
BHP
RPM
0.60
BHP
Field Furnished
RPM
0.70
0.80
BHP
RPM
BHP
RPM
BHP
962
0.26
1015
0.29
Kit ZA01
0.18
699
0.19
771
0.2
840
0.22
904
0.24
654
0.2
725
0.21
796
0.23
864
0.25
927
0.27
983
0.3
1034
0.33
681
0.22
752
0.24
823
0.26
890
0.28
950
0.31
1004
0.34
1054
0.37
0.23
711
0.25
783
0.27
852
0.29
917
0.32
975
0.35
1027
0.39
1074
0.42
0.25
744
0.28
815
0.3
882
0.33
944
0.36
1000
0.4
1050
0.44
1096
0.48
709
0.29
779
0.32
849
0.34
914
0.37
973
0.41
1026
0.45
1074
0.49
1118
0.53
747
0.33
816
0.36
883
0.39
945
0.42
1001
0.46
1052
0.51
1098
0.55
1141
0.59
External Static - in. w.g.
Air
Volume
cfm
RPM
900
1065
0.32
1112
0.35
1158
0.38
1202
0.41
1000
1082
0.36
1128
0.39
1173
0.42
1216
1100
1100
0.4
1145
0.44
1189
0.47
1231
1200
1119
0.45
1163
0.49
1206
0.52
1300
1139
0.51
1182
0.55
1224
0.58
1400
1160
0.57
1202
0.61
1243
1500
1182
0.64
1223
0.68
1263
0.90
1.00
BHP
RPM
1.10
BHP
RPM
1.20
BHP
RPM
1.30
BHP
RPM
1.40
1.50
1.60
BHP
RPM
BHP
RPM
BHP
RPM
BHP
1243
0.44
1284
0.48
1323
0.52
1364
0.55
0.45
1257
0.49
1297
0.53
1336
0.57
1375
0.6
0.51
1272
0.54
1311
0.58
1349
0.62
1388
0.66
1247
0.56
1287
0.6
1326
0.64
1364
0.68
1402
0.72
1265
0.62
1304
0.66
1342
0.71
1379
0.75
1416
0.79
0.65
1283
0.69
1322
0.73
1359
0.78
1396
0.82
1432
0.87
0.72
1303
0.76
1341
0.81
1378
0.85
1414
0.9
1449
0.94
Kit ZA04
HORIZONTAL
External Static - in. w.g.
Air
Volume
cfm
RPM
0.10
0.20
BHP
RPM
0.30
BHP
RPM
0.40
BHP
RPM
0.50
BHP
Field Furnished
RPM
0.60
BHP
RPM
0.70
BHP
RPM
0.80
BHP
Kit ZA01
RPM
BHP
Kit ZA04
900
580
0.14
649
0.17
721
0.19
794
0.22
868
0.24
938
0.27
998
0.3
1045
0.33
1000
612
0.17
681
0.19
752
0.22
825
0.25
897
0.27
963
0.3
1017
0.33
1061
0.37
1100
647
0.2
717
0.23
788
0.26
858
0.28
926
0.31
986
0.34
1036
0.38
1077
0.41
1200
687
0.23
757
0.26
826
0.29
893
0.32
955
0.35
1008
0.39
1054
0.42
1095
0.46
1300
730
0.27
798
0.3
864
0.33
926
0.37
982
0.4
1030
0.44
1073
0.47
1116
0.51
1400
775
0.31
840
0.34
902
0.38
959
0.42
1009
0.46
1054
0.5
1096
0.53
1140
0.56
1500
820
0.36
881
0.4
939
0.44
993
0.49
1039
0.53
1082
0.56
1124
0.59
1168
0.62
External Static - in. w.g.
Air
Volume
cfm
RPM
0.90
1.00
BHP
RPM
1.10
BHP
RPM
1.20
BHP
RPM
1.30
BHP
RPM
1.40
1.50
1.60
BHP
RPM
BHP
RPM
BHP
RPM
BHP
Kit ZA04
900
1091
0.36
1140
0.38
1188
0.4
1232
0.43
1272
0.46
1309
0.49
1346
0.53
1383
0.57
1000
1105
0.4
1154
0.42
1201
0.45
1245
0.47
1284
0.5
1321
0.54
1357
0.58
1394
0.62
1100
1121
0.44
1169
0.47
1216
0.49
1259
0.52
1298
0.56
1335
0.6
1370
0.64
1406
0.69
1200
1139
0.49
1187
0.52
1234
0.54
1276
0.58
1314
0.62
1350
0.66
1385
0.71
1421
0.75
1300
1161
0.54
1208
0.57
1254
0.6
1295
0.64
1332
0.69
1366
0.73
1401
0.78
1436
0.83
1400
1185
0.59
1232
0.63
1276
0.67
1315
0.71
1351
0.76
1384
0.81
1419
0.86
1454
0.9
1500
1212
0.66
1257
0.7
1299
0.74
1337
0.79
1371
0.84
1404
0.89
1438
0.94
1473
0.99
Z-Series™ Packaged Heat Pump 3 to 5 Tons / Page 16
BLOWER DATA - BELT DRIVE - ZHA048
BLOWER TABLE INCLUDES RESISTANCE FOR BASE UNIT ONLY WITH DRY INDOOR COIL AND AIR FILTERS IN PLACE.
FOR ALL UNITS ADD:
1 - Any factory installed options air resistance (heat section, economizer, wet coil, etc.).
2 - Any field installed accessories air resistance (duct resistance, diffuser, etc.).
See page 22 for blower motors and drives and wet coil and options/accessory air resistance data.
DOWNFLOW
Air
Volume
cfm
1200
1300
1400
1500
1600
1700
1800
1900
2000
Air
Volume
cfm
0.10
RPM BHP
641
673
709
747
787
827
868
907
946
0.90
RPM BHP
1200
1119
1300
1139
1400
1160
1500
1182
1600
1205
1700
1228
1800
1253
1900
1279
2000
1305
HORIZONTAL
Air
Volume
cfm
1200
1300
1400
1500
1600
1700
1800
1900
2000
Air
Volume
cfm
1200
1300
1400
1500
1600
1700
1800
1900
2000
0.23
0.25
0.29
0.33
0.38
0.43
0.48
0.54
0.60
0.45
0.51
0.57
0.64
0.70
0.78
0.85
0.94
1.04
0.20
0.30
RPM BHP RPM BHP
Field Furnished
711
0.25
783
0.27
744
0.28
815
0.30
779
0.32
849
0.34
816
0.36
883
0.39
854
0.41
918
0.44
892
0.46
952
0.49
929
0.52
986
0.55
966
0.58 1019 0.62
1001 0.65 1053 0.69
1.00
RPM BHP
Kit ZA02
1163 0.49
1182 0.55
1202 0.61
1223 0.68
1245 0.75
1268 0.82
1292 0.91
1317 1.00
1343 1.10
0.10
0.20
RPM BHP RPM BHP
Field Furnished
687
0.23
757
0.26
730
0.27
798
0.30
775
0.31
840
0.34
820
0.36
881
0.40
864
0.42
921
0.46
907
0.48
961
0.53
948
0.56
999
0.61
987
0.64 1037 0.69
1028 0.73 1076 0.78
0.90
1.00
RPM BHP RPM BHP
Kit ZA02
1139 0.49 1187 0.52
1161 0.54 1208 0.57
1185 0.59 1232 0.63
1212 0.66 1257 0.70
1242 0.73 1284 0.77
1272 0.81 1312 0.86
1302 0.90 1341 0.96
1334 1.01 1371 1.07
1365 1.12 1401 1.19
External Static - in. w.g.
0.40
0.50
RPM BHP RPM BHP
1.10
RPM BHP
852
0.29
917
0.32
882
0.33
944
0.36
914
0.37
973
0.41
945
0.42 1001 0.46
976
0.48 1030 0.52
1007 0.53 1058 0.58
1038 0.59 1087 0.64
1069 0.66 1116 0.71
1101 0.74 1146 0.79
External Static - in. w.g.
1.20
1.30
RPM BHP RPM BHP
1206
1224
1243
1263
1284
1307
1331
1355
1380
1247
1265
1283
1303
1323
1345
1368
1392
1416
0.52
0.58
0.65
0.72
0.79
0.87
0.96
1.05
1.15
0.30
RPM BHP
826
864
902
939
976
1013
1049
1086
1123
0.29
0.33
0.38
0.44
0.51
0.58
0.66
0.74
0.83
1.10
RPM BHP
1234
1254
1276
1299
1324
1350
1377
1406
1435
0.54
0.60
0.67
0.74
0.82
0.92
1.02
1.13
1.25
0.56
0.62
0.69
0.76
0.84
0.92
1.01
1.10
1.21
1287
1304
1322
1341
1361
1382
1404
1427
1450
0.60
0.66
0.73
0.81
0.88
0.97
1.06
1.16
1.26
0.60
RPM BHP
Kit ZA02
975
0.35
1000 0.40
1026 0.45
1052 0.51
1078 0.56
1105 0.63
1132 0.69
1160 0.77
1188 0.85
1.40
RPM BHP
Kit ZA05
1326 0.64
1342 0.71
1359 0.78
1378 0.85
1397 0.93
1417 1.02
1439 1.11
1461 1.21
1484 1.32
External Static - in. w.g.
0.40
0.50
0.60
RPM BHP RPM BHP RPM BHP
Kit ZA02
893
0.32
955
0.35 1008 0.39
926
0.37
982
0.40 1030 0.44
959
0.42 1009 0.46 1054 0.50
993
0.49 1039 0.53 1082 0.56
1027 0.56 1072 0.60 1113 0.63
1061 0.63 1105 0.67 1146 0.70
1096 0.71 1139 0.75 1180 0.78
1132 0.79 1174 0.83 1214 0.86
1168 0.87 1210 0.91 1250 0.96
External Static - in. w.g.
1.20
1.30
1.40
RPM BHP RPM BHP RPM BHP
Kit ZA05
1276 0.58 1314 0.62 1350 0.66
1295 0.64 1332 0.69 1366 0.73
1315 0.71 1351 0.76 1384 0.81
1337 0.79 1371 0.84 1404 0.89
1360 0.88 1394 0.93 1426 0.99
1385 0.98 1418 1.04 1451 1.09
1411 1.08 1444 1.15 1477 1.20
1439 1.20 1471 1.26 1504 1.32
1468 1.32 1500 1.38 1532 1.44
0.70
RPM BHP
0.80
RPM BHP
1027
1050
1074
1098
1123
1148
1174
1200
1228
1074
1096
1118
1141
1164
1189
1214
1240
1267
0.39
0.44
0.49
0.55
0.61
0.68
0.75
0.82
0.91
0.42
0.48
0.53
0.59
0.66
0.73
0.80
0.88
0.98
1.50
RPM BHP
1.60
RPM BHP
1364
1379
1396
1414
1432
1452
1473
1494
1516
1402
1416
1432
1449
1467
1486
1506
1527
1549
0.68
0.75
0.82
0.90
0.98
1.07
1.16
1.26
1.37
0.72
0.79
0.87
0.94
1.03
1.11
1.21
1.31
1.42
0.70
RPM BHP
0.80
RPM BHP
1054
1073
1096
1124
1155
1187
1221
1255
1289
1095
1116
1140
1168
1198
1230
1262
1295
1328
0.42
0.47
0.53
0.59
0.66
0.73
0.82
0.90
1.00
0.46
0.51
0.56
0.62
0.69
0.77
0.86
0.95
1.06
1.50
RPM BHP
1.60
RPM BHP
1385
1401
1419
1438
1460
1485
1510
1537
1565
1421
1436
1454
1473
1495
1519
1544
1571
1598
0.71
0.78
0.86
0.94
1.04
1.14
1.25
1.37
1.49
0.75
0.83
0.90
0.99
1.08
1.19
1.30
1.41
1.53
Z-Series™ Packaged Heat Pump 3 to 5 Tons/ Page 17
BLOWER DATA - BELT DRIVE - ZHA060
BLOWER TABLE INCLUDES RESISTANCE FOR BASE UNIT ONLY WITH DRY INDOOR COIL AND AIR FILTERS IN PLACE.
FOR ALL UNITS ADD:
1 - Any factory installed options air resistance (heat section, economizer, wet coil, etc.).
2 - Any field installed accessories air resistance (duct resistance, diffuser, etc.).
See page 22 for blower motors and drives and wet coil and options/accessory air resistance data.
DOWNFLOW
Air
Volume
cfm
1600
1700
1800
1900
2000
2100
2200
2300
2400
Air
Volume
cfm
0.10
RPM BHP
764
801
838
876
914
953
993
1033
1074
0.90
RPM BHP
1600
1180
1700
1204
1800
1229
1900
1256
2000
1284
2100
1312
2200
1341
2300
1371
2400
1402
HORIZONTAL
Air
Volume
cfm
1600
1700
1800
1900
2000
2100
2200
2300
2400
Air
Volume
cfm
1600
1700
1800
1900
2000
2100
2200
2300
2400
0.35
0.40
0.46
0.52
0.59
0.66
0.74
0.83
0.93
0.68
0.75
0.83
0.91
1.00
1.10
1.22
1.34
1.48
0.10
RPM BHP
783
825
866
907
948
987
1026
1064
1102
0.38
0.44
0.50
0.56
0.63
0.70
0.78
0.88
0.98
0.20
0.30
RPM BHP RPM BHP
Field Furnished
822
0.39
880
0.42
857
0.44
913
0.48
893
0.50
947
0.54
929
0.56
982
0.61
966
0.63 1017 0.68
1004 0.71 1054 0.76
1042 0.79 1090 0.85
1081 0.89 1128 0.94
1120 0.99 1166 1.05
1.00
RPM BHP
1222
1245
1270
1296
1322
1350
1378
1407
1436
0.72
0.79
0.87
0.96
1.06
1.16
1.28
1.41
1.55
1.00
RPM BHP
1183
1205
1230
1255
1281
1308
1337
1366
1396
1223
1245
1268
1292
1318
1345
1372
1401
1431
0.68
0.75
0.83
0.91
1.00
1.11
1.23
1.35
1.49
936
0.46
991
0.51
968
0.52 1020 0.57
1000 0.58 1051 0.63
1033 0.65 1082 0.70
1067 0.72 1115 0.77
1102 0.81 1148 0.86
1137 0.90 1181 0.96
1173 1.01 1216 1.07
1209 1.12 1251 1.19
External Static - in. w.g.
1.10
1.20
1.30
RPM BHP RPM BHP RPM BHP
Kit ZA03
1263 0.76 1303 0.80 1341 0.85
1285 0.84 1325 0.88 1362 0.93
1309 0.92 1347 0.97 1384 1.02
1334 1.01 1371 1.07 1407 1.12
1360 1.11 1396 1.17 1431 1.23
1386 1.22 1422 1.28 1456 1.34
1414 1.34 1448 1.41 1481 1.46
1442 1.47 1475 1.54 1507 1.59
1470 1.61 1503 1.67 1535 1.73
0.20
0.30
RPM BHP RPM BHP
Field Furnished
844
0.41
902
0.44
882
0.47
938
0.50
921
0.53
973
0.56
959
0.59 1008 0.63
996
0.66 1042 0.70
1033 0.74 1077 0.78
1070 0.82 1112 0.87
1106 0.92 1147 0.97
1143 1.03 1182 1.08
0.90
RPM BHP
0.72
0.79
0.87
0.96
1.06
1.17
1.29
1.42
1.56
External Static - in. w.g.
0.40
0.50
RPM BHP RPM BHP
External Static - in. w.g.
0.40
0.50
RPM BHP RPM BHP
957
0.48 1008 0.52
989
0.54 1038 0.57
1021 0.60 1067 0.64
1054 0.66 1098 0.71
1086 0.74 1128 0.78
1119 0.82 1159 0.87
1152 0.92 1191 0.98
1186 1.03 1223 1.09
1220 1.15 1256 1.21
External Static - in. w.g.
1.10
1.20
1.30
RPM BHP RPM BHP RPM BHP
Kit ZA03
1263 0.76 1302 0.81 1340 0.86
1284 0.84 1322 0.89 1360 0.94
1306 0.92 1344 0.98 1380 1.03
1330 1.02 1367 1.07 1402 1.13
1355 1.12 1391 1.18 1425 1.23
1381 1.23 1416 1.29 1450 1.35
1408 1.35 1442 1.42 1475 1.47
1435 1.49 1469 1.55 1501 1.61
1464 1.63 1496 1.69 1528 1.75
Z-Series™ Packaged Heat Pump 3 to 5 Tons / Page 18
0.60
RPM BHP
Kit ZA03
1042 0.55
1070 0.61
1099 0.68
1129 0.75
1160 0.83
1192 0.92
1224 1.02
1257 1.14
1291 1.26
1.40
RPM BHP
1378
1398
1420
1442
1465
1489
1513
1539
1566
0.90
0.98
1.07
1.17
1.28
1.40
1.52
1.65
1.79
0.60
RPM BHP
Kit ZA03
1056 0.56
1083 0.62
1111 0.68
1139 0.75
1168 0.83
1198 0.93
1228 1.03
1260 1.15
1292 1.28
1.40
RPM BHP
1377
1396
1416
1437
1459
1482
1507
1532
1559
0.91
0.99
1.08
1.18
1.29
1.41
1.53
1.67
1.81
0.70
RPM BHP
0.80
RPM BHP
1091
1117
1145
1173
1203
1233
1264
1296
1329
1136
1162
1188
1215
1244
1273
1303
1334
1366
0.60
0.66
0.73
0.80
0.88
0.98
1.09
1.20
1.33
0.64
0.71
0.78
0.85
0.94
1.04
1.15
1.27
1.41
1.50
1.60
RPM BHP RPM BHP
Kit ZA06
1414 0.94 1449 0.99
1434 1.03 1468 1.08
1454 1.12 1488 1.17
1476 1.23 1509 1.28
1498 1.33 1531 1.38
1521 1.45 1554 1.50
1546 1.57 1578 1.62
1571 1.70 1602 1.75
1597 1.84 1628 1.89
0.70
RPM BHP
0.80
RPM BHP
1100
1126
1152
1179
1207
1235
1265
1295
1327
1142
1166
1191
1217
1244
1272
1301
1331
1362
0.60
0.66
0.73
0.80
0.89
0.99
1.10
1.22
1.35
0.64
0.71
0.78
0.86
0.94
1.05
1.16
1.28
1.42
1.50
1.60
RPM BHP RPM BHP
Kit ZA06
1413 0.95 1448 1.00
1431 1.04 1465 1.09
1450 1.13 1483 1.19
1470 1.24 1503 1.29
1492 1.35 1524 1.40
1514 1.46 1546 1.52
1538 1.59 1569 1.64
1563 1.72 1594 1.77
1589 1.86 1619 1.91
BLOWER DATA - BELT DRIVE - ZHB036
BLOWER TABLE INCLUDES RESISTANCE FOR BASE UNIT ONLY WITH DRY INDOOR COIL AND AIR FILTERS IN PLACE.
FOR ALL UNITS ADD:
1 - Any factory installed options air resistance (heat section, economizer, wet coil, etc.).
2 - Any field installed accessories air resistance (duct resistance, diffuser, etc.).
See page 22 for blower motors and drives and wet coil and options/accessory air resistance data.
DOWNFLOW
External Static - in. w.g.
Air
Volume
cfm
RPM
900
562
0.11
621
0.13
685
0.16
752
0.18
818
0.21
1000
584
0.13
644
0.16
707
0.18
773
0.21
838
1100
609
0.16
669
0.18
732
0.21
796
0.24
860
1200
635
0.19
696
0.21
758
0.24
821
0.27
1300
664
0.22
725
0.25
786
0.28
848
0.31
1400
696
0.26
756
0.29
816
0.32
876
1500
729
0.30
788
0.33
848
0.37
906
0.10
0.20
BHP
RPM
BHP
0.30
RPM
BHP
0.40
RPM
0.50
BHP
RPM
0.60
BHP
0.70
0.80
BHP
RPM
BHP
RPM
BHP
883
0.24
944
0.27
1001
0.30
0.24
901
0.27
960
0.3
1015
0.33
0.27
921
0.30
978
0.34
1031
0.37
883
0.31
942
0.34
997
0.38
1049
0.42
908
0.35
965
0.39
1018
0.43
1068
0.47
0.36
935
0.40
989
0.44
1041
0.48
1089
0.52
0.41
962
0.45
1015
0.50
1065
0.54
1112
0.58
Field Furnished
RPM
Kit ZA01
External Static - in. w.g.
Air
Volume
cfm
RPM
900
1053
0.32
1000
1066
1100
1081
1200
1300
0.90
1.00
BHP
RPM
BHP
1.10
RPM
BHP
1.20
RPM
1.30
BHP
RPM
1.40
1.50
1.60
BHP
RPM
BHP
RPM
BHP
RPM
BHP
Kit ZA04
1103
0.35
1149
0.38
1193
0.41
1234
0.43
1274
0.47
1312
0.50
1351
0.53
0.36
1114
0.39
1160
0.42
1204
0.45
1245
0.48
1284
0.51
1322
0.54
1361
0.58
0.40
1128
0.43
1173
0.46
1216
0.49
1257
0.53
1296
0.56
1334
0.60
1372
0.63
1097
0.45
1144
0.48
1188
0.51
1231
0.54
1271
0.58
1310
0.62
1347
0.66
1385
0.69
1115
0.50
1161
0.53
1204
0.56
1246
0.60
1286
0.64
1325
0.68
1362
0.72
1399
0.76
1400
1135
0.56
1179
0.59
1222
0.62
1264
0.66
1303
0.70
1341
0.75
1378
0.79
1415
0.83
1500
1157
0.62
1200
0.65
1242
0.69
1282
0.73
1321
0.77
1359
0.82
1396
0.86
1431
0.91
HORIZONTAL
External Static - in. w.g.
Air
Volume
cfm
RPM
0.10
0.20
BHP
RPM
BHP
0.30
RPM
BHP
0.40
RPM
0.50
BHP
RPM
0.60
BHP
Field Furnished
RPM
0.70
0.80
BHP
RPM
BHP
RPM
BHP
Kit ZA01
900
560
0.16
624
0.18
692
0.20
761
0.21
830
0.23
896
0.25
956
0.27
1012
0.29
1000
583
0.18
647
0.20
715
0.22
783
0.24
850
0.25
914
0.27
972
0.30
1025
0.33
1100
609
0.20
673
0.22
740
0.24
808
0.26
873
0.28
934
0.31
990
0.34
1041
0.37
1200
637
0.23
702
0.25
769
0.27
835
0.29
898
0.32
956
0.35
1009
0.38
1058
0.41
1300
669
0.26
734
0.28
800
0.30
863
0.33
924
0.36
979
0.39
1030
0.43
1077
0.46
1400
704
0.29
768
0.32
832
0.35
894
0.37
951
0.41
1004
0.44
1052
0.48
1097
0.52
1500
742
0.33
805
0.36
867
0.39
925
0.42
980
0.46
1030
0.50
1076
0.54
1119
0.58
External Static - in. w.g.
Air
Volume
cfm
RPM
0.90
1.00
BHP
RPM
BHP
1.10
RPM
BHP
1.20
RPM
1.30
BHP
RPM
1.40
1.50
1.60
BHP
RPM
BHP
RPM
BHP
RPM
BHP
Kit ZA04
900
1064
0.32
1114
0.35
1162
0.38
1208
0.41
1251
0.45
1293
0.49
1333
0.52
1373
0.56
1000
1076
0.36
1124
0.39
1170
0.42
1216
0.46
1259
0.49
1300
0.53
1340
0.57
1379
0.61
1100
1089
0.40
1136
0.43
1181
0.46
1225
0.50
1268
0.54
1308
0.58
1347
0.62
1386
0.66
1200
1104
0.45
1150
0.48
1194
0.51
1237
0.55
1279
0.59
1319
0.63
1357
0.67
1394
0.71
1300
1121
0.5
1165
0.53
1209
0.57
1251
0.61
1292
0.65
1331
0.69
1368
0.73
1405
0.78
1400
1140
0.56
1183
0.59
1225
0.63
1266
0.67
1306
0.71
1345
0.76
1382
0.8
1417
0.85
1500
1161
0.62
1202
0.65
1243
0.69
1284
0.73
1323
0.78
1360
0.83
1396
0.87
1432
0.92
Z-Series™ Packaged Heat Pump 3 to 5 Tons/ Page 19
BLOWER DATA - BELT DRIVE - ZHB048
BLOWER TABLE INCLUDES RESISTANCE FOR BASE UNIT ONLY WITH DRY INDOOR COIL AND AIR FILTERS IN PLACE.
FOR ALL UNITS ADD:
1 - Any factory installed options air resistance (heat section, economizer, wet coil, etc.).
2 - Any field installed accessories air resistance (duct resistance, diffuser, etc.).
See page 22 for blower motors and drives and wet coil and options/accessory air resistance data.
DOWNFLOW
Air
Volume
cfm
1200
1300
1400
1500
1600
1700
1800
1900
2000
Air
Volume
cfm
0.10
RPM BHP
620
652
687
724
764
806
849
892
935
0.90
RPM BHP
1200
1111
1300
1127
1400
1145
1500
1164
1600
1185
1700
1208
1800
1233
1900
1261
2000
1289
HORIZONTAL
Air
Volume
cfm
1200
1300
1400
1500
1600
1700
1800
1900
2000
Air
Volume
cfm
1200
1300
1400
1500
1600
1700
1800
1900
2000
0.23
0.28
0.33
0.40
0.46
0.53
0.60
0.68
0.76
0.58
0.62
0.68
0.73
0.79
0.84
0.91
0.98
1.07
0.10
RPM BHP
614
644
677
714
752
792
832
873
914
0.21
0.24
0.29
0.34
0.40
0.46
0.53
0.60
0.67
0.90
RPM BHP
1105
1123
1142
1163
1185
1209
1234
1260
1287
0.51
0.55
0.60
0.66
0.72
0.78
0.86
0.95
1.04
0.20
0.30
RPM BHP RPM BHP
Field Furnished
681
0.29
744
0.34
713
0.34
775
0.39
747
0.39
809
0.44
784
0.45
844
0.50
823
0.51
882
0.56
863
0.58
919
0.62
903
0.65
957
0.69
944
0.72
995
0.77
984
0.81 1033 0.86
1.00
RPM BHP
Kit ZA02
1156 0.60
1172 0.65
1189 0.70
1208 0.75
1229 0.81
1252 0.87
1276 0.94
1303 1.02
1330 1.11
1.10
RPM BHP
809
0.39
875
0.43
839
0.44
903
0.48
871
0.49
934
0.53
905
0.54
965
0.59
940
0.60
997
0.65
975
0.67 1028 0.71
1010 0.74 1058 0.78
1045 0.82 1089 0.86
1079 0.91 1122 0.95
External Static - in. w.g.
1.20
1.30
RPM BHP RPM BHP
1199
1214
1231
1251
1271
1294
1318
1343
1370
1241
1256
1274
1293
1313
1335
1358
1382
1407
0.62
0.66
0.72
0.78
0.84
0.90
0.98
1.06
1.16
0.20
0.30
RPM BHP RPM BHP
Field Furnished
681
0.25
752
0.30
712
0.29
782
0.34
746
0.34
814
0.39
781
0.40
848
0.45
818
0.45
882
0.50
855
0.52
917
0.56
894
0.58
952
0.63
932
0.65
988
0.69
970
0.72 1023 0.76
1.00
RPM BHP
Kit ZA02
1152 0.53
1169 0.57
1187 0.63
1207 0.69
1228 0.75
1251 0.82
1275 0.91
1300 1.00
1326 1.10
External Static - in. w.g.
0.40
0.50
RPM BHP RPM BHP
0.63
0.68
0.74
0.80
0.86
0.94
1.02
1.11
1.21
1284
1299
1316
1334
1354
1375
1397
1420
1444
0.65
0.70
0.76
0.83
0.90
0.98
1.06
1.16
1.27
External Static - in. w.g.
0.40
0.50
RPM BHP RPM BHP
1.10
RPM BHP
821
0.34
888
0.39
850
0.39
915
0.43
880
0.44
942
0.48
911
0.49
970
0.53
943
0.55
999
0.59
975
0.61 1028 0.64
1007 0.67 1058 0.70
1040 0.73 1088 0.77
1073 0.80 1120 0.85
External Static - in. w.g.
1.20
1.30
RPM BHP RPM BHP
1197
1213
1230
1249
1270
1292
1315
1340
1365
1240
1255
1272
1290
1310
1331
1354
1377
1402
0.55
0.60
0.66
0.72
0.79
0.87
0.96
1.05
1.16
Z-Series™ Packaged Heat Pump 3 to 5 Tons / Page 20
0.58
0.63
0.69
0.76
0.83
0.92
1.01
1.11
1.21
1280
1295
1312
1330
1349
1370
1391
1414
1437
0.61
0.67
0.73
0.80
0.88
0.97
1.06
1.16
1.27
0.60
RPM BHP
Kit ZA02
941
0.47
967
0.51
994
0.57
1021 0.62
1048 0.69
1075 0.75
1102 0.82
1131 0.89
1163 0.97
1.40
RPM BHP
Kit ZA05
1326 0.67
1341 0.73
1357 0.79
1374 0.86
1393 0.94
1413 1.02
1434 1.11
1455 1.21
1478 1.32
0.60
RPM BHP
Kit ZA02
950
0.43
974
0.47
998
0.52
1023 0.57
1050 0.62
1077 0.68
1105 0.74
1134 0.81
1163 0.89
1.40
RPM BHP
Kit ZA05
1320 0.64
1334 0.70
1350 0.77
1368 0.85
1387 0.93
1407 1.02
1428 1.11
1450 1.22
1472 1.33
0.70
RPM BHP
0.80
RPM BHP
1004
1025
1048
1071
1094
1119
1145
1174
1204
1060
1078
1098
1118
1140
1164
1189
1217
1247
0.51
0.55
0.61
0.66
0.72
0.78
0.85
0.92
1.00
0.54
0.59
0.64
0.70
0.75
0.81
0.88
0.95
1.03
1.50
RPM BHP
1.60
RPM BHP
1367
1381
1397
1413
1431
1449
1469
1490
1513
1408
1421
1436
1451
1468
1485
1504
1525
1547
0.71
0.77
0.83
0.91
0.98
1.07
1.16
1.26
1.37
0.74
0.81
0.88
0.95
1.03
1.12
1.21
1.31
1.42
0.70
RPM BHP
0.80
RPM BHP
1006
1027
1049
1072
1097
1123
1149
1177
1205
1057
1076
1097
1119
1142
1166
1192
1219
1246
0.46
0.51
0.55
0.60
0.66
0.72
0.78
0.85
0.94
0.49
0.53
0.58
0.63
0.69
0.75
0.82
0.90
0.99
1.50
RPM BHP
1.60
RPM BHP
1358
1372
1388
1405
1423
1443
1463
1485
1507
1395
1409
1424
1441
1459
1478
1498
1519
1541
0.68
0.74
0.82
0.90
0.98
1.07
1.17
1.27
1.38
0.72
0.79
0.86
0.94
1.03
1.12
1.22
1.32
1.43
BLOWER DATA - BELT DRIVE - ZHB060
BLOWER TABLE INCLUDES RESISTANCE FOR BASE UNIT ONLY WITH DRY INDOOR COIL AND AIR FILTERS IN PLACE.
FOR ALL UNITS ADD:
1 - Any factory installed options air resistance (heat section, economizer, wet coil, etc.).
2 - Any field installed accessories air resistance (duct resistance, diffuser, etc.).
See page 22 for blower motors and drives and wet coil and options/accessory air resistance data.
DOWNFLOW
Air
Volume
cfm
1600
1700
1800
1900
2000
2100
2200
2300
2400
Air
Volume
cfm
0.10
RPM BHP
522
539
558
578
600
623
647
671
696
1600
1700
1800
1900
2000
2100
2200
2300
2400
Air
Volume
cfm
1600
1700
1800
1900
2000
2100
2200
2300
2400
External Static - in. w.g.
0.40
0.50
RPM BHP RPM BHP
1.00
RPM BHP
Kit ZAA02
844
0.74
857
0.80
870
0.87
885
0.94
899
1.01
915
1.10
931
1.19
948
1.29
965
1.39
1.10
RPM BHP
619
0.43
656
0.48
638
0.48
674
0.53
658
0.54
694
0.59
678
0.60
714
0.65
699
0.66
734
0.71
721
0.73
755
0.79
743
0.81
776
0.86
766
0.89
798
0.95
788
0.98
819
1.04
External Static - in. w.g.
1.20
1.30
RPM BHP RPM BHP
877
889
901
915
929
944
959
975
992
908
919
931
944
957
971
986
1001
1017
0.20
RPM BHP
Kit ZAA01
561
0.34
578
0.39
597
0.44
618
0.49
639
0.55
661
0.62
685
0.69
709
0.77
734
0.85
0.30
RPM BHP
0.90
1.00
RPM BHP RPM BHP
Kit ZAA02
819
0.66
851
0.72
833
0.72
865
0.78
848
0.79
880
0.85
864
0.87
895
0.93
881
0.95
911
1.01
898
1.03
927
1.10
916
1.12
944
1.19
934
1.22
961
1.29
952
1.32
979
1.40
1.10
RPM BHP
0.90
RPM BHP
1600
809
1700
823
1800
838
1900
853
2000
869
2100
885
2200
902
2300
920
2400
938
HORIZONTAL
Air
Volume
cfm
0.27
0.32
0.38
0.44
0.50
0.57
0.65
0.73
0.81
0.20
0.30
RPM BHP RPM BHP
Kit ZAA01
552
0.32
585
0.37
570
0.37
603
0.43
589
0.43
623
0.48
610
0.49
643
0.54
632
0.56
665
0.61
655
0.62
688
0.68
678
0.70
711
0.75
702
0.78
734
0.83
726
0.87
757
0.92
0.69
0.75
0.81
0.88
0.96
1.04
1.13
1.23
1.33
0.10
RPM BHP
525
543
561
581
602
625
648
673
699
0.30
0.34
0.39
0.44
0.50
0.57
0.64
0.71
0.79
597
615
635
655
676
698
721
745
769
883
896
910
924
940
955
971
988
1005
0.80
0.86
0.92
0.99
1.07
1.15
1.24
1.35
1.45
0.39
0.43
0.49
0.54
0.61
0.67
0.75
0.83
0.91
0.77
0.84
0.92
0.99
1.08
1.17
1.26
1.36
1.47
0.85
0.92
0.98
1.05
1.13
1.22
1.31
1.41
1.52
936
947
958
971
984
997
1012
1027
1042
0.91
0.97
1.04
1.11
1.19
1.28
1.37
1.47
1.58
External Static - in. w.g.
0.40
0.50
RPM BHP RPM BHP
0.60
0.70
RPM BHP RPM BHP
Kit ZAA02
693
0.53
732
0.59
711
0.59
749
0.64
730
0.64
767
0.70
749
0.70
785
0.76
769
0.77
803
0.83
789
0.84
822
0.91
809
0.93
841
1.00
829
1.02
860
1.09
850
1.11
880
1.19
0.80
RPM BHP
1.40
RPM BHP
Kit ZAA03
963
0.97
973
1.03
984
1.10
996
1.17
1009 1.25
1022 1.34
1036 1.43
1051 1.53
1066 1.64
1.50
RPM BHP
1.60
RPM BHP
989
999
1009
1021
1033
1046
1060
1075
1090
1014
1024
1034
1045
1058
1070
1084
1098
1113
0.60
RPM BHP
Kit ZAA02
711
0.51
728
0.57
746
0.63
765
0.69
784
0.76
804
0.84
824
0.92
845
1.01
866
1.11
635
0.43
673
0.47
653
0.48
691
0.52
672
0.53
710
0.58
692
0.59
729
0.64
713
0.66
749
0.71
735
0.73
770
0.78
757
0.80
791
0.86
780
0.88
813
0.94
803
0.97
835
1.04
External Static - in. w.g.
1.20
1.30
1.40
RPM BHP RPM BHP RPM BHP
Kit ZAA03
913
0.83
943
0.89
971
0.95
926
0.90
954
0.96
982
1.02
939
0.98
967
1.04
994
1.10
953
1.06
980
1.12 1007 1.18
967
1.14
994
1.21 1020 1.27
982
1.23 1008 1.30 1033 1.37
998
1.33 1023 1.40 1047 1.47
1014 1.43 1038 1.50 1062 1.58
1030 1.54 1054 1.62 1077 1.69
1.02
1.09
1.16
1.23
1.31
1.40
1.50
1.60
1.70
771
787
803
819
837
854
872
890
909
0.64
0.69
0.75
0.82
0.90
0.98
1.06
1.16
1.26
1.08
1.14
1.22
1.29
1.38
1.46
1.56
1.66
1.77
0.70
RPM BHP
0.80
RPM BHP
748
765
782
800
818
837
856
876
896
784
800
816
833
850
868
886
905
924
0.56
0.62
0.68
0.75
0.82
0.90
0.98
1.08
1.18
0.61
0.67
0.73
0.80
0.88
0.96
1.05
1.15
1.25
1.50
RPM BHP
1.60
RPM BHP
998
1009
1020
1032
1044
1057
1071
1085
1099
1024
1034
1045
1056
1068
1080
1093
1107
1121
1.01
1.08
1.16
1.25
1.34
1.43
1.54
1.65
1.76
1.07
1.14
1.23
1.31
1.40
1.50
1.60
1.71
1.83
Z-Series™ Packaged Heat Pump 3 to 5 Tons/ Page 21
BLOWER DATA
DRIVE KIT SPECIFICATIONS
Model No.
Blower Motor Choice (HP)
Maximum
Nominal
Nominal
Maximum
ZHA/ZHB036
1
1
1
1.15
1.5
1.7
ZHA/ZHB048
1
1
1
1.15
1.5
1.7
ZHA060
1
1
1
1.15
1.5
1.7
ZHB060
1
1
1
1.15
1.5
1.7
Drive Kit No.
RPM Range
ZA01
ZA04
ZA02
2
ZA05
ZA03
2
ZA06
ZAA01
ZAA02
2
ZAA03
678 - 1035
964 - 1471
803 - 1226
1098 - 1490
906-1383
1262-1634
522 - 784
632 - 875
798 - 1105
NOTE - Using total air volume and system static pressure requirements determine from blower performance tables rpm and motor hp required. Maximum usable hp of
motors furnished are shown. In Canada, nominal motor hp is also maximum usable motor hp. If motors of comparable hp are used, be sure to keep within the service
factor limitations outlined on the motor nameplate.
1
1 hp blower motor is not available for 208/230V-1ph applications.
2
1.5 hp motor is required with ZA05, ZA06 and ZAA03 drive kits.
POWER EXHAUST FAN PERFORMANCE
Air Volume Exhausted
cfm
1865
1785
1710
1630
1545
1450
1350
1240
Return Air System Static Pressure - in. w.g.
0.00
0.05
0.10
0.15
0.20
0.25
0.30
0.35
OPTIONS / ACCESSORIES AIR RESISTANCE - in. w.g.
Wet Indoor Coil
Air Volume
cfm
ZHA036, ZHA048
ZHA060, ZHB036
ZHB048, ZHB060
900
0.01
0.01
--1000
0.02
0.01
--1100
0.02
0.02
--1200
0.02
0.02
0.01
1300
0.03
0.02
0.02
1400
0.03
0.03
0.02
1500
0.04
0.03
0.02
1600
0.04
0.03
0.03
1700
0.05
0.04
0.03
1800
0.05
0.04
0.03
1900
0.06
0.05
0.04
2000
0.06
0.05
0.04
2100
--0.06
0.05
2200
--0.06
0.05
2300
--0.07
0.05
2400
--0.07
0.06
CEILING DIFFUSERS AIR RESISTANCE (in. w.g.)
RTD9-65 Step-Down Diffuser
Air Volume
2 Ends
1 Side &
All Ends &
cfm
Open
2 Ends Open
Sides Open
800
0.15
0.13
0.11
1000
0.19
0.16
0.14
1200
0.25
0.20
0.17
1400
0.33
0.26
0.20
1600
0.43
0.32
0.20
1800
0.56
0.40
0.30
2000
0.73
0.50
0.36
2200
0.95
0.63
0.44
Z-Series™ Packaged Heat Pump 3 to 5 Tons / Page 22
FD9-65
Flush
Diffuser
0.11
0.14
0.17
0.20
0.24
0.30
0.36
0.44
Electric
Heat
0.05
0.06
0.08
0.09
0.12
0.17
0.22
0.26
0.30
0.33
0.33
0.31
0.27
0.29
0.31
0.32
Economizer
Downflow
Horizontal
0.03
0.04
0.03
0.05
0.04
0.05
0.05
0.06
0.05
0.07
0.06
0.08
0.07
0.08
0.08
0.09
0.09
0.10
0.10
0.11
0.11
0.12
0.12
0.13
0.13
0.14
0.14
0.15
0.15
0.16
0.16
0.18
CEILING DIFFUSER AIR THROW DATA
1
Air Volume - cfm
Effective Throw - ft.
Model No.
RTD9-65
FD9-65
800
10 - 17
14 - 18
1000
10 - 17
15 - 20
1200
11 - 18
16 - 22
1400
12 - 19
17 - 24
1600
12 - 20
18 - 25
1800
13 - 21
20 - 28
2000
14 - 23
21 - 29
2200
16 - 25
22 - 30
1
Effective throw based on terminal velocities of 75 ft. per minute.
ELECTRICAL/ELECTRIC HEAT DATA - ZHA
3 TON
ZHA036S4
208/230V - 3 Ph
460V - 3 Ph
575V - 3 Ph
Rated Load Amps
8.7
4
3.6
Locked Rotor Amps
70
31
27
Outdoor Fan
Motor
Full Load Amps
1.7
0.9
0.7
Power Exhaust
(1) 0.5 HP
Full Load Amps
1.5
0.6
0.6
1
Voltage - 60hz
Compressor
Indoor Blower
Motor
2
3
Horsepower
Maximum
Overcurrent
Protection
Minimum
Circuit
Ampacity
1
1.5
1
1.5
1
1.5
Full Load Amps
4.6
6.6
2.1
3
1.7
2.4
Unit Only
25
25
15
15
15
15
With (1) 0.5 HP
Power Exhaust
25
25
15
15
15
15
Unit Only
18
20
8
9
7
8
With (1) 0.5 HP
Power Exhaust
19
21
9
10
8
9
ELECTRIC HEAT DATA
Electric Heat Voltage
2
3
2
3
Maximum
Overcurrent
Protection
Minimum
Circuit
Ampacity
Maximum
Overcurrent
Protection
Minimum
Circuit
Ampacity
208V
240V
208V
240V
480V
480V
600V
600V
5 kW
35
35
35
35
20
20
15
15
7.5 kW
40
40
40
45
20
25
20
20
10 kW
45
50
50
50
25
25
20
20
15 kW
60
70
60
70
35
35
25
30
5 kW
31
33
33
35
16
17
13
14
7.5 kW
37
40
39
42
20
21
16
17
10 kW
44
48
46
50
24
24
19
20
15 kW
57
63
59
65
31
32
25
26
Unit+
5 kW
Electric Heat
7.5 kW
and
(1) 0.5 HP 10 kW
Power Exhaust
15 kW
35
35
35
40
20
20
15
15
40
45
45
45
20
25
20
20
45
50
50
60
25
25
20
25
60
70
60
70
35
35
30
30
Unit+
5 kW
Electric Heat
7.5 kW
and
(1) 0.5 HP 10 kW
Power Exhaust
15 kW
32
34
34
36
17
18
14
15
39
42
41
44
20
21
17
18
45
49
47
51
24
25
20
21
58
64
60
66
32
33
26
27
Unit+
Electric Heat
Unit+
Electric Heat
ELECTRIC HEAT ACCESSORIES
Unit Fuse Block
Unit Only
10A27
10A27
10A29
10A29
10A29
10A29
Unit + Power Exhaust
10A27
10A27
10A29
10A29
10A29
10A29
NOTE - All units have a minimum Short Circuit Current Rating (SCCR) of 5000 amps.
1
Extremes of operating range are plus and minus 10% of line voltage.
2
HACR type breaker or fuse.
3
Refer to National or Canadian Electrical Code manual to determine wire, fuse and disconnect size requirements.
Z-Series™ Packaged Heat Pump 3 to 5 Tons/ Page 23
ELECTRICAL/ELECTRIC HEAT DATA - ZHA
4 TON
ZHA048S4
208/230V - 3 Ph
460V - 3 Ph
575V - 3 Ph
Rated Load Amps
11
5.5
4.7
Locked Rotor Amps
86
37
34
Outdoor Fan
Motor
Full Load Amps
1.7
0.9
0.7
Power Exhaust
(1) 0.5 HP
Full Load Amps
1.5
0.6
0.6
1
Voltage - 60hz
Compressor
Indoor Blower
Motor
2
3
Horsepower
Maximum
Overcurrent
Protection
Minimum
Circuit
Ampacity
1
1.5
1
1.5
1
1.5
Full Load Amps
4.6
6.6
2.1
3
1.7
2.4
Unit Only
30
30
15
15
15
15
With (1) 0.5 HP
Power Exhaust
30
30
15
15
15
15
Unit Only
21
23
10
11
9
9
With (1) 0.5 HP
Power Exhaust
22
24
11
12
9
10
ELECTRIC HEAT DATA
Electric Heat Voltage
2
3
2
3
Maximum
Overcurrent
Protection
Minimum
Circuit
Ampacity
Maximum
Overcurrent
Protection
Minimum
Circuit
Ampacity
Unit+
Electric Heat
Unit+
Electric Heat
Unit+
Electric Heat
and
(1) 0.5 HP
Power Exhaust
Unit+
Electric Heat
and
(1) 0.5 HP
Power Exhaust
208V
240V
208V
240V
480V
480V
600V
600V
5 kW
40
40
40
45
20
20
15
15
7.5 kW
45
45
45
50
25
25
20
20
10 kW
50
60
50
60
25
30
25
25
15 kW
60
70
70
70
35
35
30
30
22.5 kW
80
90
90
90
45
45
40
40
5 kW
34
36
36
38
18
19
15
15
7.5 kW
40
43
42
45
22
23
18
18
10 kW
47
51
49
53
25
26
21
22
15 kW
60
66
62
68
33
34
27
28
22.5 kW
79
88
81
90
44
45
36
37
5 kW
40
40
40
45
20
20
15
20
7.5 kW
45
50
50
50
25
25
20
20
10 kW
50
60
50
60
30
30
25
25
15 kW
70
70
70
70
35
35
30
30
90
90
90
100
45
50
40
40
5 kW
35
37
37
39
18
19
15
16
7.5 kW
42
45
44
47
22
23
18
19
10 kW
48
52
50
54
26
27
21
22
15 kW
61
67
63
69
34
34
27
28
22.5 kW
81
90
83
92
45
46
36
37
ELECTRIC HEAT ACCESSORIES
Unit Fuse Block
Unit Only
10A27
10A27
10A29
10A29
10A29
10A29
Unit + Power Exhaust
10A27
10A27
10A29
10A29
10A29
10A29
NOTE - All units have a minimum Short Circuit Current Rating (SCCR) of 5000 amps.
1
Extremes of operating range are plus and minus 10% of line voltage.
2
HACR type breaker or fuse.
3
Refer to National or Canadian Electrical Code manual to determine wire, fuse and disconnect size requirements.
Z-Series™ Packaged Heat Pump 3 to 5 Tons / Page 24
ELECTRICAL/ELECTRIC HEAT DATA - ZHA
5 TON
ZHA060S4
208/230V - 3 Ph
460V - 3 Ph
575V - 3 Ph
Rated Load Amps
13.5
8
5
Locked Rotor Amps
109
59
40
Outdoor Fan
Motor
Full Load Amps
1.7
1
0.9
Power Exhaust
(1) 0.5 HP
Full Load Amps
1.5
0.6
0.6
1
Voltage - 60hz
Compressor
Indoor Blower
Motor
2
3
Horsepower
Maximum
Overcurrent
Protection
Minimum
Circuit
Ampacity
1
1.5
1
1.5
1
1.5
Full Load Amps
4.6
6.6
2.1
3
1.7
2.4
Unit Only
35
35
20
20
15
15
With (1) 0.5 HP
Power Exhaust
35
40
20
20
15
15
Unit Only
24
26
14
14
9
10
With (1) 0.5 HP
Power Exhaust
25
27
14
15
10
11
ELECTRIC HEAT DATA
Electric Heat Voltage
2
3
2
3
Maximum
Overcurrent
Protection
Minimum
Circuit
Ampacity
Maximum
Overcurrent
Protection
Minimum
Circuit
Ampacity
Unit+
Electric Heat
Unit+
Electric Heat
Unit+
Electric Heat
and
(1) 0.5 HP
Power Exhaust
Unit+
Electric Heat
and
(1) 0.5 HP
Power Exhaust
208V
240V
208V
240V
480V
480V
600V
600V
5 kW
45
45
45
50
25
25
15
20
7.5 kW
50
50
50
50
30
30
20
20
10 kW
50
60
60
60
30
30
25
25
15 kW
70
70
70
80
40
40
30
30
22.5 kW
90
100
90
100
50
50
40
40
5 kW
37
39
39
41
21
22
15
16
7.5 kW
43
46
45
48
25
26
18
19
10 kW
50
54
52
56
29
30
21
22
15 kW
63
69
65
71
36
37
27
28
22.5 kW
82
91
84
93
47
48
36
37
5 kW
45
50
50
50
25
25
20
20
7.5 kW
50
50
50
50
30
30
20
20
10 kW
60
60
60
60
30
30
25
25
15 kW
70
70
70
80
40
40
30
30
90
100
90
100
50
50
40
40
5 kW
38
40
40
42
22
23
16
17
7.5 kW
45
48
47
50
25
26
19
20
10 kW
51
55
53
57
29
30
22
23
15 kW
64
70
66
72
37
38
28
29
22.5 kW
84
93
86
95
48
49
37
38
ELECTRIC HEAT ACCESSORIES
Unit Fuse Block
Unit Only
10A28
10A28
10A29
10A29
10A29
10A29
Unit + Power Exhaust
10A28
10A28
10A29
10A29
10A29
10A29
NOTE - All units have a minimum Short Circuit Current Rating (SCCR) of 5000 amps.
1
Extremes of operating range are plus and minus 10% of line voltage.
2
HACR type breaker or fuse.
3
Refer to National or Canadian Electrical Code manual to determine wire, fuse and disconnect size requirements.
Z-Series™ Packaged Heat Pump 3 to 5 Tons/ Page 25
ELECTRICAL/ELECTRIC HEAT DATA - ZHB
3 TON
ZHB036S4
208/230V - 1 Ph
208/230V - 3 Ph
460V - 3 Ph
575V - 3 Ph
15.3
8.7
4
3.6
Locked Rotor Amps
70
70
31
27
Outdoor Fan
Motor
Full Load Amps
1
1
0.6
0.45
Power Exhaust
(1) 0.5 HP
Full Load Amps
1.5
1.5
0.6
0.6
Horsepower
1.5
1
1.5
1
1.5
1
1.5
Full Load Amps
11
4.6
6.6
2.1
3
1.7
2.4
Unit Only
45
25
25
15
15
15
15
With (1) 0.5 HP
Power Exhaust
45
25
25
15
15
15
15
Unit Only
32
17
19
8
9
7
8
With (1) 0.5 HP
Power Exhaust
33
18
20
9
10
8
8
1
Voltage - 60hz
Compressor
Rated Load Amps
Indoor Blower
Motor
2
3
Maximum
Overcurrent
Protection
Minimum
Circuit
Ampacity
ELECTRIC HEAT DATA
Electric Heat Voltage
2
3
2
3
Maximum
Overcurrent
Protection
Minimum
Circuit
Ampacity
Maximum
Overcurrent
Protection
Minimum
Circuit
Ampacity
208V
240V
208V
240V
208V
240V
480V
480V
600V
600V
5 kW
60
60
35
35
35
35
20
20
15
15
7.5 kW
70
80
40
40
40
45
20
20
20
20
10 kW
80
90
45
50
45
50
25
25
20
20
15 kW
100
110
60
70
60
70
35
35
25
30
5 kW
54
58
30
32
32
34
16
17
13
14
7.5 kW
65
71
37
40
39
42
19
20
16
17
10 kW
77
84
43
47
45
49
23
24
19
20
15 kW
99
110
56
62
58
64
31
32
25
26
Unit+
5 kW
Electric Heat
7.5 kW
and
(1) 0.5 HP 10 kW
Power Exhaust
15 kW
60
60
35
35
35
40
20
20
15
15
70
80
40
45
40
45
20
25
20
20
80
90
45
50
50
60
25
25
20
20
110
125
60
70
60
70
35
35
30
30
56
59
32
34
34
36
16
17
14
14
67
72
38
41
40
43
20
21
17
17
78
85
45
49
47
51
24
25
20
20
101
111
58
64
60
66
31
32
26
26
Unit+
Electric Heat
Unit+
Electric Heat
Unit+
5 kW
Electric Heat
7.5 kW
and
(1) 0.5 HP 10 kW
Power Exhaust
15 kW
ELECTRIC HEAT ACCESSORIES
Unit Fuse Block
Unit Only
10A26
10A27
10A27
10A29
10A29
10A29
10A29
Unit + Power Exhaust
10A26
10A27
10A27
10A29
10A29
10A29
10A29
NOTE - All units have a minimum Short Circuit Current Rating (SCCR) of 5000 amps.
1
Extremes of operating range are plus and minus 10% of line voltage.
2
HACR type breaker or fuse.
3
Refer to National or Canadian Electrical Code manual to determine wire, fuse and disconnect size requirements.
Z-Series™ Packaged Heat Pump 3 to 5 Tons / Page 26
ELECTRICAL/ELECTRIC HEAT DATA - ZHB
4 TON
ZHB048S4
208/230V - 1 Ph
208/230V - 3 Ph
460V - 3 Ph
575V - 3 Ph
Rated Load Amps
20
11
5.5
4.7
Locked Rotor Amps
99
86
37
34
Outdoor Fan
Motor
Full Load Amps
1.7
1.7
0.9
0.7
Power Exhaust
(1) 0.5 HP
Full Load Amps
1.5
1.5
0.6
0.6
Horsepower
1.5
1
1.5
1
1.5
1
1.5
Full Load Amps
11
4.6
6.6
2.1
3
1.7
2.4
Unit Only
50
30
30
15
15
15
15
With (1) 0.5 HP
Power Exhaust
50
30
30
15
15
15
15
Unit Only
38
21
23
10
11
9
9
With (1) 0.5 HP
Power Exhaust
40
22
24
11
12
9
10
1
Voltage - 60hz
Compressor
Indoor Blower
Motor
2
3
Maximum
Overcurrent
Protection
Minimum
Circuit
Ampacity
ELECTRIC HEAT DATA
Electric Heat Voltage
2
3
2
3
Maximum
Overcurrent
Protection
Minimum
Circuit
Ampacity
Maximum
Overcurrent
Protection
Minimum
Circuit
Ampacity
Unit+
Electric Heat
Unit+
Electric Heat
Unit+
Electric Heat
and
(1) 0.5 HP
Power Exhaust
Unit+
Electric Heat
and
(1) 0.5 HP
Power Exhaust
208V
240V
208V
240V
208V
240V
480V
480V
600V
600V
5 kW
70
70
40
40
40
45
20
20
15
15
7.5 kW
80
80
45
45
45
50
25
25
20
20
10 kW
90
90
50
60
50
60
25
30
25
25
15 kW
110
125
60
70
70
70
35
35
30
30
22.5 kW
150
175
80
90
90
90
45
45
40
40
5 kW
61
64
34
36
36
38
18
19
15
15
7.5 kW
72
77
40
43
42
45
22
23
18
18
10 kW
83
90
47
51
49
53
25
26
21
22
15 kW
106
116
60
66
62
68
33
34
27
28
22.5 kW
140
155
79
88
81
90
44
45
36
37
5 kW
70
80
40
40
40
45
20
20
15
20
7.5 kW
80
90
45
50
50
50
25
25
20
20
10 kW
90
100
50
60
50
60
30
30
25
25
15 kW
110
125
70
70
70
70
35
35
30
30
150
175
90
90
90
100
45
50
40
40
5 kW
62
66
35
37
37
39
18
19
15
16
7.5 kW
74
79
42
45
44
47
22
23
18
19
10 kW
85
92
48
52
50
54
26
27
21
22
15 kW
107
118
61
67
63
69
34
34
27
28
22.5 kW
141
157
81
90
83
92
45
46
36
37
ELECTRIC HEAT ACCESSORIES
Unit Fuse Block
Unit Only
10A26
10A27
10A27
10A29
10A29
10A29
10A29
Unit + Power Exhaust
10A26
10A27
10A27
10A29
10A29
10A29
10A29
NOTE - All units have a minimum Short Circuit Current Rating (SCCR) of 5000 amps.
1
Extremes of operating range are plus and minus 10% of line voltage.
2
HACR type breaker or fuse.
3
Refer to National or Canadian Electrical Code manual to determine wire, fuse and disconnect size requirements.
Z-Series™ Packaged Heat Pump 3 to 5 Tons/ Page 27
ELECTRICAL/ELECTRIC HEAT DATA - ZHB
5 TON
ZHB060S4
208/230V - 1 Ph
208/230V - 3 Ph
460V - 3 Ph
575V - 3 Ph
Rated Load Amps
22.1
13.5
8
5
Locked Rotor Amps
125
109
59
40
Outdoor Fan
Motor
Full Load Amps
1.7
1.7
1
0.9
Power Exhaust
(1) 0.5 HP
Full Load Amps
1.5
1.5
0.6
0.6
Horsepower
1.5
1
1.5
1
1.5
1
1.5
Full Load Amps
11
4.6
6.6
2.1
3
1.7
2.4
Unit Only
60
35
35
20
20
15
15
With (1) 0.5 HP
Power Exhaust
60
35
40
20
20
15
15
Unit Only
41
24
26
14
14
9
10
With (1) 0.5 HP
Power Exhaust
42
25
27
14
15
10
11
1
Voltage - 60hz
Compressor
Indoor Blower
Motor
2
3
Maximum
Overcurrent
Protection
Minimum
Circuit
Ampacity
ELECTRIC HEAT DATA
Electric Heat Voltage
2
3
2
3
Maximum
Overcurrent
Protection
Minimum
Circuit
Ampacity
Maximum
Overcurrent
Protection
Minimum
Circuit
Ampacity
Unit+
Electric Heat
Unit+
Electric Heat
Unit+
Electric Heat
and
(1) 0.5 HP
Power Exhaust
Unit+
Electric Heat
and
(1) 0.5 HP
Power Exhaust
208V
240V
208V
240V
208V
240V
480V
480V
600V
600V
5 kW
80
80
45
45
45
50
25
25
15
20
7.5 kW
80
90
50
50
50
50
30
30
20
20
10 kW
90
100
50
60
60
60
30
30
25
25
15 kW
110
125
70
70
70
80
40
40
30
30
22.5 kW
150
175
90
100
90
100
50
50
40
40
5 kW
63
67
37
39
39
41
21
22
15
16
7.5 kW
75
80
43
46
45
48
25
26
18
19
10 kW
86
93
50
54
52
56
29
30
21
22
15 kW
109
119
63
69
65
71
36
37
27
28
22.5 kW
142
158
82
91
84
93
47
48
36
37
5 kW
80
80
45
50
50
50
25
25
20
20
7.5 kW
90
90
50
50
50
50
30
30
20
20
10 kW
100
100
60
60
60
60
30
30
25
25
15 kW
110
125
70
70
70
80
40
40
30
30
150
175
90
100
90
100
50
50
40
40
5 kW
65
68
38
40
40
42
22
23
16
17
7.5 kW
76
81
45
48
47
50
25
26
19
20
10 kW
87
94
51
55
53
57
29
30
22
23
15 kW
110
120
64
70
66
72
37
38
28
29
22.5 kW
144
160
84
93
86
95
48
49
37
38
ELECTRIC HEAT ACCESSORIES
Unit Fuse Block
Unit Only
10A26
10A28
10A28
10A29 10A29 10A29 10A29
Unit + Power Exhaust
10A26
10A28
10A28
10A29 10A29 10A29 10A29
NOTE - All units have a minimum Short Circuit Current Rating (SCCR) of 5000 amps.
1
Extremes of operating range are plus and minus 10% of line voltage.
2
HACR type breaker or fuse.
3
Refer to National or Canadian Electrical Code manual to determine wire, fuse and disconnect size requirements.
Z-Series™ Packaged Heat Pump 3 to 5 Tons / Page 28
ELECTRIC HEAT CAPACITIES
5 kW
7.5 kW
10 kW
15 kW
22.5 kW
Input
Btuh No of kW
Btuh No of kW
Btuh No of kW
Btuh No of kW
Btuh
Voltage No of kW
Stages input Output Stages input Output Stages input Output Stages input Output Stages input Output
208
1
3.8
12,800
1
5.6
19,200
1
7.5
25,600
1
11.2
38,400
1
16.9
57,700
220
1
4.2
14,300
1
6.3
21,500
1
8.4
28,700
1
12.6
43,000
1
18.9
64,500
230
1
4.6
15,700
1
6.9
23,500
1
9.2
31,400
1
13.8
47,000
1
20.7
70,700
240
1
5.0
17,100
1
7.5
25,600
1
10.0
34,200
1
15.0
51,200
1
22.5
76,800
440
1
4.2
14,300
1
6.3
21,500
1
8.4
28,700
1
12.6
43,000
1
18.9
64,500
460
1
4.6
15,700
1
6.9
23,500
1
9.2
31,400
1
13.8
47,000
1
20.7
70,700
480
1
5.0
17,100
1
7.5
25,600
1
10.0
34,200
1
15.0
51,200
1
22.5
76,800
550
1
4.2
14,300
1
6.3
21,500
1
8.4
28,700
1
12.6
43,000
1
18.9
64,500
575
1
4.6
15,700
1
6.9
23,500
1
9.2
31,400
1
13.8
47,000
1
20.7
70,700
600
1
5.0
17,100
1
7.5
25,600
1
10.0
34,200
1
15.0
51,200
1
22.5
76,800
Z-Series™ Packaged Heat Pump 3 to 5 Tons/ Page 29
UNIT CLEARANCES - INCHES (MM)
UNIT WITH DOWNFLOW ECONOMIZER
OUTDOOR AIR
HOOD
C
D
B
A
UNIT WITH HORIZONTAL ECONOMIZER
HORIZONTAL
OUTDOOR AIR
HOOD
C
D
B
A
1
A
Unit Clearance
B
C
Downflow
C
Horizontal
D
in.
mm
in.
mm
in.
mm
in.
mm
in.
mm
Service Clearance
36
914
36
914
36
914
60
1524
36
914
Minimum Operation Clearance
36
914
36
914
36
914
60
1524
36
914
NOTE - Entire perimeter of unit base requires support when elevated above the mounting surface.
1
S
ervice Clearance - Required for removal of serviceable parts.
Minimum Operation Clearance - Required clearance for proper unit operation.
Z-Series™ Packaged Heat Pump 3 to 5 Tons / Page 30
Top
Clearance
Unobstructed
OUTDOOR SOUND DATA
Unit
Model No.
ZHA036
ZHA048
ZHA060
ZHB036
ZHB048
ZHB060
1
Octave Band Linear Sound Power Levels dB, re 10-12 Watts - Center Frequency - Hz
Sound Rating
Number (SRN)
(dBA)
1
125
250
500
1000
2000
4000
8000
Cooling
82
79
78
74
70
66
61
79
Heating
82
79
79
74
71
67
63
80
Cooling
82
79
78
74
70
66
61
79
Heating
82
79
79
74
71
67
63
80
Cooling
86
83
82
77
73
70
67
83
Heating
85
83
82
78
73
70
66
83
Cooling
82
79
78
74
70
66
61
79
Heating
82
79
79
74
71
67
63
80
Cooling
82
79
78
74
70
66
61
77
Heating
82
79
79
74
71
67
63
78
Cooling
86
83
82
77
73
70
67
82
Heating
85
83
82
78
73
70
66
82
Sound Rating Number according to ANSI/AHRI Standard 270-2008. “SRN” is the overall A-Weighted Sound Power Level, (LWA), dB (100 Hz to 10,000 Hz).
Z-Series™ Packaged Heat Pump 3 to 5 Tons/ Page 31
WEIGHT DATA
Model Number
Net
Shipping
Base
Max.
Base
Max.
lbs.
kg
lbs.
kg
lbs.
kg
lbs.
kg
ZHA036S
530
240
581
264
535
243
586
266
ZHB036S
580
263
634
288
585
265
639
290
ZHA048S
539
244
590
268
544
247
595
270
ZHB048S
585
265
639
290
590
268
644
292
ZHA060S
585
265
639
290
590
268
644
292
ZHB060S
610
277
664
301
615
279
669
303
Base Unit - The unit with NO OPTIONS.
Max. Unit - The unit with ALL OPTIONS Installed. (Economizer, etc.)
OPTIONS / ACCESSORIES
Shipping Weights
lbs.
kg
Downflow
62
28
Horizontal
92
42
Motorized
30
14
Manual
23
10
Downflow
54
24
Horizontal
41
19
5 kW - Z1EH0050AN1
25
11
7.5 kW - Z1EH0075AN1
26
12
10 kW - Z1EH0100AN1
27
12
15 kW - Z1EH0150AN1
27
12
22.5 kW - Z1EH0225AN1
29
13
8 in. height
Z1CURB70A-1
63
29
14 in. height
Z1CURB71A-1
83
38
18 in. height
Z1CURB72A-1
93
42
24 in. height
Z1CURB73A-1
113
51
RTD9-65-R
67
30
FD9-65-R
37
17
ECONOMIZER
Economizer
Economizer, Includes Outdoor Air Hood and
Barometric Relief Dampers with Hood
OUTDOOR AIR
Outdoor Air Dampers
POWER EXHAUST
Standard Static
ELECTRIC HEAT
ROOF CURBS
Hybrid Roof Curbs, Downflow
CEILING DIFFUSERS
Step-Down
Flush
Z-Series™ Packaged Heat Pump 3 to 5 Tons / Page 32
DIMENSIONS - INCHES (MM) - ZHA
Model
No.
CORNER WEIGHTS
AA
Base
BB
Max.
Base
CENTER OF GRAVITY
CC
Max.
Base
DD
Max.
Base
EE
Max.
Base
lbs. kg lbs. kg lbs. kg lbs. kg lbs. kg lbs. kg lbs. kg lbs. kg
in.
FF
Max.
in.
in.
mm
036
136 62 152 69 126 57 157 71 129 58 138 62 139 63 134 61 39.5 1003 37.5 953 23.25 591
25
635
048
139 63 155 70 128 58 159 72 131 59 140 63 142 64 136 62 39.5 1003 37.5 953 23.25 591
25
635
060
172 78 190 86 139 63 171 77 123 56 132 60 151 69 147 67
1067
40
mm
1016
in.
Max.
mm
42
mm
Base
25
635 26.5 673
Base Unit - The unit with NO OPTIONS.
Max. Unit - The unit with ALL OPTIONS Installed. (Economizer, largest blower motor, etc.).
BOTTOM POWER ENTRY
Holes required for Optional Bottom Power Entry Kit
Threaded
Hole Diameter
Wire
Conduit Fittings
Required in
Use
(Provided in Kit)
Unit Base (Max.)
A
1/2
ACC
7/8 (23)
B
1/2
24V
7/8 (23)
C
3/4
POWER
1-1/8 (29)
25-5/8
(651)
AA
CENTER
OF
GRAVITY
47-1/4
(1200)
BASE
16-1/8
(410) 13-5/8
(346)
A
B
C
11-1/8
(283)
DD
BB
BOTTOM
RETURN
AIR OPENING
FF
BOTTOM
SUPPLY
AIR
OPENING
5-1/8
(130)
10-7/8
(276)
29
(737)
17-3/4
(451)
5-3/4
(146)
24-9/16
(624)
BOTTOM
POWER
ENTRY
(See Table)
CC
12-1/8
(308)
EE
75-7/8
(1927)
5-1/8
(130)
TOP VIEW (Base)
73-3/4
(1873)
36-7/8 (937) 036 / 048
44-7/8 (1140) 060
POWER
ENTRY
5-9/16
(141)
11-7/8
(302)
1
(25)
Either side
5-3/4
(146)
3-1/2 (89)
1
(25)
47-1/4 BASE
(1200)
END VIEW
1
(25)
LIFTING HOLES
(For rigging)
3-1/2 (89)
TYP.
FRONT VIEW
6-1/2
(165)
CONDENSATE
OUTLET
HORIZONTAL
SUPPLY
6-1/4
(159)
17-3/8
(441)
27
(686)
31
(787)
HORIZONTAL
RETURN
45-1/4
(1149)
25-3/4
(654)
8-3/8
(213)
5-3/4
(146)
10-7/8
(276)
END VIEW
Z-Series™ Packaged Heat Pump 3 to 5 Tons/ Page 33
DIMENSIONS - INCHES (MM) - ZHB
Model
No.
CORNER WEIGHTS
AA
Base
BB
Max.
Base
CENTER OF GRAVITY
CC
Max.
Base
DD
Max.
Base
EE
Max.
lbs. kg lbs. kg lbs. kg lbs. kg lbs. kg lbs. kg lbs. kg lbs. kg
Base
in.
FF
Max.
mm
in.
Base
mm
in.
Max.
mm
in.
mm
036
158 72 173 78 133 60 145 66 124 56 135 61 147 67 160 73 41.25 1048 39.25 997 24.5 622 25.75 654
048
168 76 183 83 136 62 148 67 120 54 130 59 148 67 161 73
060
163 74 177 80 142 64 155 70 142 64 155 70 163 74 177 80 40.5 1029 38.5 978 23.5 597
42
1067
40
1016
25
635 26.5 673
25
635
Base Unit - The unit with NO OPTIONS.
Max. Unit - The unit with ALL OPTIONS Installed. (Economizer, largest blower motor, etc.).
BOTTOM POWER ENTRY
Holes required for Optional Bottom Power Entry Kit
Threaded
Hole Diameter
Wire
Conduit Fittings
Required in
Use
(Provided in Kit)
Unit Base (Max.)
A
1/2
ACC
7/8 (23)
B
1/2
24V
7/8 (23)
C
3/4
POWER
1-1/8 (29)
25-5/8
(651)
AA
CENTER
OF
GRAVITY
47-1/4
(1200)
BASE
16-1/8
(410) 13-5/8
(346)
A
B
C
11-1/8
(283)
DD
BB
BOTTOM
RETURN
AIR OPENING
FF
BOTTOM
SUPPLY
AIR
OPENING
5-1/8
(130)
10-7/8
(276)
29
(737)
17-3/4
(451)
5-3/4
(146)
24-9/16
(624)
BOTTOM
POWER
ENTRY
(See Table)
CC
12-1/8
(308)
EE
75-7/8
(1927)
5-1/8
(130)
TOP VIEW (Base)
73-3/4
(1873)
44-7/8 (1140)
POWER
ENTRY
5-9/16
(141)
11-7/8
(302)
1
(25)
Either side
5-3/4
(146)
3-1/2 (89)
1
(25)
47-1/4 BASE
(1200)
1
(25)
LIFTING HOLES
(For rigging)
END VIEW
Z-Series™ Packaged Heat Pump 3 to 5 Tons / Page 34
3-1/2 (89)
TYP.
FRONT VIEW
6-1/2
(165)
CONDENSATE
OUTLET
HORIZONTAL
SUPPLY
6-1/4
(159)
17-3/8
(441)
27
(686)
31
(787)
END VIEW
HORIZONTAL
RETURN
45-1/4
(1149)
25-3/4
(654)
8-3/8
(213)
10-7/8
(276)
5-3/4
(146)
ACCESSORY DIMENSIONS - INCHES (MM)
OUTDOOR AIR HOOD DETAIL FOR OPTIONAL ECONOMIZER
(Downflow Applications)
18-1/4
(464)
18-1/4
(464)
31
(787)
3/4
(19)
18-1/4
(464)
OPTIONAL OUTDOOR
AIR HOOD
(Furnished with Economizer)
SIDE VIEW
OUTDOOR AIR DAMPER HOOD DETAIL FOR OPTIONAL MANUAL OR MOTORIZED OUTDOOR AIR DAMPERS
(Downflow or Horizontal Applications)
OPTIONAL
OUTDOOR
AIR DAMPERS
AND PANEL
10-5/8
(270)
42-1/2
(1080)
OUTDOOR AIR
DAMPER HOOD
14
(356)
16-1/2
(419)
OUTDOOR AIR
DAMPER HOOD
(Furnished)
22
(559)
10-5/8
(270)
SIDE VIEW
Z-Series™ Packaged Heat Pump 3 to 5 Tons/ Page 35
ACCESSORY DIMENSIONS - INCHES (MM)
OUTDOOR AIR HOOD DETAIL WITH OPTIONAL ECONOMIZER AND BAROMETRIC RELIEF DAMPERS
(Horizontal Applications)
RETURN AIR DUCT INLET
(Field Fabricated - Must be sized to
accommodate Barometric Relief Hood
and Return Air Requirements)
OUTDOOR AIR/
BAROMETRIC
RELIEF HOOD
(Furnished with
Economizer)
31
(787)
This opening not used in
Horizontal Applications
with Economizer
73-3/4
(1873)
38-1/4
(971)
11-7/8
(302)
HORIZONTAL
SUPPLY AIR
OPENING
5-3/4
(146)
6-1/2
(165)
17-3/8
(441)
END VIEW
TOP VIEW
HORIZONTAL
RETURN AIR
OPENING
16
(406)
18-1/4
(463)
16
(406)
FRESH AIR
OPENING
HORIZONTAL
ECONOMIZER
LOCATION
EXHAUST
OPENING
Note - Return Air Duct and Transition must be supported.
Z-Series™ Packaged Heat Pump 3 to 5 Tons / Page 36
BACK VIEW
ACCESSORY DIMENSIONS - INCHES (MM)
HYBRID ROOF CURBS - DOUBLE DUCT OPENING
15
(381)
32-1/16
(814)
71
(1803)
RETURN
OPENING
42-5/16
(1075)
14
(356)
20-1/4
(514)
SUPPLY
OPENING
8 (203)
14 (356)
18 (457)
24 (610)
3-5/8
(92)
17-3/16
(437)
DECK PANS (3)
NOTE - Roof deck may be omitted within confines of curb.
TYPICAL FLASHING DETAIL FOR ROOF CURB
BASE BOTTOM
DETAIL ROOF CURB
PACKAGED
UNIT
1-3/4
(44)
1/2 (13)
FIBERGLASS
INSULATION
(Furnished)
COUNTER FLASHING
(Field Supplied)
NAILER STRIP
(Furnished)
ROOF CURB
(Extends around entire
perimeter of unit)
CANT STRIP
(Field Supplied)
ROOFING
MATERIAL
8 (203)
14 (356)
18 (457)
24 (610)
FACTORY INSTALLED
PERIMETER WOOD
NAILER STRIP
RIGID INSULATION
(Field Supplied)
1-3/4
(44)
Z-Series™ Packaged Heat Pump 3 to 5 Tons/ Page 37
ACCESSORY DIMENSIONS - INCHES (MM)
COMBINATION CEILING SUPPLY AND RETURN DIFFUSERS
STEP-DOWN CEILING DIFFUSER
E
FLUSH CEILING DIFFUSER
H
G
F
G
D
E
H
G
C
C
2 (51)
A
B
H
F
2 (51)
L
D
H
G
A
B
J
K
Model Number
A
RTD9-65
in.
mm
B
in.
mm
C
in.
mm
D
in.
mm
E
in.
mm
F
in.
mm
G
in.
mm
H
in.
mm
J
in.
mm
K
in.
mm
L
in.
mm
Duct Size
47-5/8
Model Number
A
1159
23-5/8
B
D
546
45-1/2
E
1156
22-1/2
F
H
45-1/2
1156
21-1/2
546
7-1/8
181
in.
18 round
mm
457 round
Z-Series™ Packaged Heat Pump 3 to 5 Tons / Page 38
23-5/8
600
13-1/2
343
21
mm
533
in.
in.
in.
in.
mm
Duct Size
1159
in.
mm
273
47-5/8
mm
mm
G
292
10-3/4
in.
mm
572
11-1/2
in.
mm
C
289
21-1/2
in.
mm
600
11-3/8
FD9-65
45
1143
22-1/2
572
11-1/4
286
10-1/2
267
in.
18 round
mm
457 round
REVISIONS
Sections
Description of Change
Document
New Product - ZHB High efficiency models specifications, ratings, dimensions and
options added.
Visit us at www.allied-commercial.com
For the latest technical information, visit us at www.allied-commercial.com
Contact us at 1-800-448-5872
NOTE - Due to Allied Commercial ongoing commitment to quality, Specifications, Ratings and Dimensions subject to change without notice and without incurring liability.
Improper installation, adjustment, alteration, service or maintenance can cause property damage or personal injury.
Installation and service must be performed by a qualified installer and servicing agency.
©2015 Allied Air Enterprises LLC, a Lennox International Inc. Company
Download PDF
Similar pages