FlexPower FPO250-E1
250W, 20A/12V or 10A/24V
Power Management System
E1 locking enclosure 12" x 14" 4.5"
DESCRIPTION
The FlexPower FPO250-E1 is an offline switchmode power supply-battery
charger specifically designed for the lifesafety industry. Capable of providing two power outputs, user selectable for 12 or 24 VDC, the unit is
configured in a painted, steel, locking enclosure with tamper switch and
integral battery space.
One output provides continuous output power for system use, the second is programmable for either fail-safe or fail-secure operation, activated
when the fire alarm disconnect is initiated.
Complete fault detection and reporting, with programmable fault delays,
is provided along with datalogging capability of fault occurrence, battery
usage time and current power supply status.
BENEFITS
¾¾Agency Listed for Access Control, Fire, Security, CCTV, and Mass Notification
¾¾FlexPower ® Feature Set
ŠŠ SureCharge Microprocessor controlled battery charging
ŠŠ PowerCom Power supply programming / monitoring software
ŠŠ VSelect
Installer selectable output voltage
ŠŠ TruWatt
Delivers twice the current at 12V than at 24V
ŠŠ PwrHealth
Intelligent battery charging and battery state monitoring
ŠŠ FlexConnect Dual voltage bus / pre-wired accesory board interconnects
ŠŠ Reliability+ Full fault protection / high efficiency / fiberglass pcb
ŠŠ GreenSmart RoHS compliant, lead free, energy efficient design
ŠŠ DataLink Network communication interface option
¾¾System Features
ŠŠ Fully modular power management system
ŠŠ Multiple outputs for system power, direct lock control and accessory power distribution modules
ŠŠ Fire alarm interface for egress lock control (FAI)
ŠŠ Configurable fail-safe / fail-secure modes of operation
ŠŠ Comprehensive fault detection and reporting including optional
earth ground and battery presence
ŠŠ AC and System fault output relays can be delayed via PowerCom
ŠŠ Microprocessor dual rate charging restores battery sets from 4 to
80 amphours
ELECTRICAL RATINGS
Parameter
FPO250
Unit
Input Voltage
120 / 230
VAC
282
Watts
Output Voltage
12 or 24
VDC
Output Current
20 or 10
Amps
Battery Charge Capacity
80
Ah
Efficiency
88
%
Output Ripple
120
mVp-p
Line Regulation
0.1
±%
Load Regulation
2
±%
109
BTU/Hr
Input Power (max)
BTU Rating
Continuous Power Outputs
1
Switched Power Outputs
1
Fire Alarm Interface
March 2012
¾¾Power Management & Reporting (patent pending)
ŠŠ PowerCom s/w monitors, programs, and reports on power supply
core functions through a computer USB or network connection
ŠŠ Service personnel can perform onsite power supply programming and
system diagnostics using the DL1 USB cable and a computer laptop
ŠŠ NL1 DataLink module connects power supply to a LAN/WAN
network for remote power supply programming and diagnostics.
Monitors and reports system status, battery state, generates email
or SNMP notification of system trouble or time to service alert
¾¾Ten Year Warranty
AGENCY LISTINGS
USA
UL 294 UL 1481
UL 603 UL 2044
UL 864 UL 2572
UL 1076
FCC Part 15, Subpart B
CSFM Approved
Yes
1/2
CANADA
ULC S318
ULC S319
ULC S527
CSA C22.2 #107.1
CSA 22.2 #60950
www.lifesafetypower.com
FlexPower FPO250-E1
FAULT DETECTION AND REPORTING
SureCharge The microprocessor controlled charging process used by the
FlexPower power supply guarantees both proper charging current for the
battery and fastest charge time. The constant current charger provides a
linear, predictable charge time for any lead acid, gel battery set from 4 to 80
amphours (based on charger rating) without stress or damage to the battery.
The comprehensive fault detection and reporting mechanism of the FPO
series provides for both local and remote fault reporting.
PowerCom/PowerCom-USB LifeSafety Power’s proprietary software
interface for communication with FlexPower equipment through a
DATALINK or USB connection. PowerCom is used for power supply
monitoring, programming, and reporting.
Detected Fault Conditions:
¾¾AC Power
ŠŠ AC loss, AC low
On-board visual indicators are provided to give immediate installer feedback.
Independent form C relay contacts are provided to report AC and system fault
conditions to remote or auxiliary equipment.
¾¾DC Power and System
ŠŠ Abnormal or loss of power supply operation
ŠŠ Over current, over temperature condition
ŠŠ DC output high, low
ŠŠ Battery Presence, Earth Ground (user optional)
ŠŠ Reversed battery condition, blown fuse or loss of output voltage on
selected accessory boards (detected on the power supply)
The NL1 DATALINK network module enhances PowerCom's capability with
remote diagnostics, battery management, trouble / service email alerts via
LAN/WAN, and remote on/off reset control.
The DL1 USB cable and a computer laptop USB connection, enables
PowerCom-USB to be used by service personnel for onsite power supply
programming and system diagnostic evaluation.
FIRE ALARM INTERFACE (FAI)
VSelect One single switch for configuring the output between 12 and 24VDC
eliminates field errors and allows for the reduction and simplification of service
inventory by eliminating the necessity of stocking units in each voltage.
¾¾Activation Methods
ŠŠ DC voltage: 9 to 33VDC, 3 to 15mA
ŠŠ Dry contact NO/NC
TruWatt Output power capability of the power supply remains constant
regardless of the output voltage setting. For example, a FlexPower 250 watt
supply will provide 10 amps at 24VDC and 20 amps at 12VDC, allowing the
same number of locking devices to be used at either the 12 or 24V setting.
¾¾Latch Enable: NC contact set or switch (typically for Canadian use)
FPO PERFORMANCE GRAPHS
Field upgrading or expansion is as simple as using common mounting
footprints, predrilled mounting holes, snap-in standoffs, and pluggable
wires to add additional system capability or capacity when needed, all
without restrictive agency listing issues.
+10
+10
Line Regulation
Output Regulation
% Deviation
Output Regulation
% Deviation @ Full Load
FlexConnect The FlexPower series provides a prewired interconnection
system between the power supply and accessory boards of the power system that introduces the concept of a dual voltage bus structure throughout
all system modules and eliminates intermodule wiring by the field installer.
+5
0
–5
Transfer to
Battery
–10
0
20
0
–5
–10
80
100
110
40
60
Line Voltage (% of Maximum)
120
0
+10
20
80
100
110
40
60
Output Power (% of Maximum)
120
SureCharge
+5
% Recharged
Output Regulation
% Deviation
Reliability+ All power supplies within the FlexPower system are fully fault
protected and feature fiberglass printed circuit boards rather than paperbased to protect the electronics from water and other corrosive elements
found in industrial settings. High efficiency power supply design promotes
low heat generation leading to a longer service life.
Load Regulation
+5
0
–5
Output vs Temperature
Conventional Charge
Battery Recharge vs Time
–10
–10
GreenSmart All members of the FlexPower family are RoHs compliant,
lead-free, and meet the latest state, federal and European requirements for
energy efficiency.
0
10
30
40
20
Temperature (°C)
50
60
Charging Hours
© 2012 LifeSafety Power Inc. P01-261A 03/12
DataLink - Smart Power Management Communication Interface
Monitor, program, control, and report key power supply functions by computer
or local/wide area network using a browser interface or LifeSafety Power's
PowerCom® remote management software.
Power supply network connection requires the optional NL1 network module.
Power supply computer connection requires the optional DL1 USB cable.
Model No.
FPO250-E1
Power Supply / E1 Cabinet
Mechanical Info
Size: 12" x 14" x 4.5"
Weight: 10.5 lb.
FlexPower Numbering System
FPO100 – C82D8 – E2
FlexPower series
Power rating (W)
Enclosure
Accessory module
Accessory quantity (more than 1)
Important: All information, including illustrations, is believed to be reliable. Users, however, should
independently evaluate the suitability of each product for their particular application. LifeSafety Power
makes no warranties as to the accuracy or completeness of the information, and disclaims any liability
regarding its use. LifeSafety Power’s only obligations are those in the LifeSafety Power Standard Terms
and Conditions of Sale for this product, and in no case will LifeSafety Power or its distributors be liable
for any incidental, indirect, or consequential damages arising from the sale, resale, use, or misuse of
the product. Specifications are subject to change without notice. In addition, LifeSafety Power reserves
the right to make changes—without notification to Buyer—to processing or materials that do not affect
compliance with any applicable specification.
Worldwide Headquarters
LifeSafety Power, Inc.
49 Range Road
Windham, NH 03087 USA
Tel 888-LSP-BUY8
info@lifesafetypower.com
March 2012
LifeSafety Power, FlexPower, DataLink, GreenSmart, FlexConnect, PowerCom, Reliability+, SureCharge, TruWatt, and VSelect are registered trademarks of LifeSafety Power Inc. or its affiliates.
FLEXPOWER ® STANDARD FEATURES
2/2
www.lifesafetypower.com
Download PDF
Similar pages