B5/B5 IR-Probe GAS TRANSMITTER/SENSOR

B5/B5 IR-Probe
GAS TRANSMITTER/SENSOR
B5
IR-Probe
INSTALLATION
OPERATION AND MAINTENANCE
MANUAL
QUATROSENSE ENVIRONMENTAL LTD.
5935 OTTAWA STREET, PO BOX 749 (RICHMOND) OTTAWA, ONTARIO CANADA K0A 2Z0
PHONE: (613) 838-4005 FAX: (613) 838-4018
www.QELsafety.com
B5 Operation And Maintenance Manual
READ BEFORE OPERATING ................................................................................................................... 2
1.
SPECIFICATIONS .............................................................................................................................. 2
1.1
1.2
ELECTRICAL/MECHANICAL SPECIFICATIONS ........................................................................................... 2
SENSOR SPECIFICATIONS......................................................................................................................... 4
2.
INSTALLATION ................................................................................................................................. 6
2.1 ENCLOSURES PHYSICAL DIMENSIONS ..................................................................................................... 6
2.2 TERMINALS ............................................................................................................................................. 6
2.2.1
Wire and Cable ............................................................................................................................. 7
2.2.2
RS-485 Terminator ....................................................................................................................... 7
2.2.3
RS-485 Driver Replacement ......................................................................................................... 7
2.2.4
Relays Output ............................................................................................................................... 7
2.2.5
Note for B5: .................................................................................................................................. 8
2.2.6
Certification: ................................................................................................................................ 8
3.
FUNCTION AND CONFIGURATION ............................................................................................. 9
3.1 INDICATORS ............................................................................................................................................ 9
3.1.1 RS485-TX/RX: ............................................................................................................................ 9
3.1.2 Relay 1-3 LED: ........................................................................................................................... 9
3.2 TOOL FUNCTION ................................................................................................................................... 10
3.2.1
Enter Main Menu........................................................................................................................ 10
3.2.2
Hush Buzzer and Relay............................................................................................................... 10
3.2.3
Reset Latched/Hushed ................................................................................................................ 10
3.2.4
Reset MENU Password .............................................................................................................. 10
3.2.5
Exit Tool Mode ........................................................................................................................... 10
3.3 MAIN MENU TREE ................................................................................................................................ 11
3.4 MENU “1_SYSTEM SETUP” .............................................................................................................. 12
3.4.1
System Settings ........................................................................................................................... 12
3.5 MENU “2_ZERO CAL” ........................................................................................................................ 15
3.5.1
Equipment Required ................................................................................................................... 15
3.5.2
Zeroing Calibration Procedure .................................................................................................. 15
3.6 MENU “3_SPAN CAL” ........................................................................................................................ 16
3.7 MENU “4_OUT TEST” ........................................................................................................................ 17
3.8 MENU “5_VIEW SETTING” ............................................................................................................... 18
3.9 MENU “6_ALARM SETUP” ................................................................................................................ 19
3.10
MENU “7_RELAY STYLE” ............................................................................................................ 20
3.11
MENU “8_BUZZER STYLE” .......................................................................................................... 21
3.12
MENU “A_ALL DISABLE” ............................................................................................................ 21
3.13
MENU “B_SIMULATION” ............................................................................................................. 21
3.14
MENU “C_SITE SERVICE” AND “D_FACTROY SET” ................................................................. 21
4.
BACNET PIC STATEMENT SUPPORTED BY B5 ...................................................................... 21
4.1 SMART SENSOR ASSEMBLY REPLACEMENT .......................................................................................... 22
4.1.1
Disassembling ............................................................................................................................ 22
4.1.2
Replacement Procedure ............................................................................................................. 22
4.1.3
Replacement Parts ...................................................................................................................... 23
4.1.4
Accessories ................................................................................................................................. 25
5.
TROUBLESHOOTING .................................................................................................................... 26
85950-101-000 RB
1
August 7, 2015
B5 Operation And Maintenance Manual
READ BEFORE OPERATING
All individuals who have or will have the responsibility of using, maintaining, or
servicing this product must carefully read this manual. The product will perform as
designed only if it is used, maintained, and serviced in accordance with the
manufacturer’s instructions.
The B5 is a state-of-the-art transmitter that can operate as an independent, stand-alone
system or as part of an integrated system. Setup procedures are simplified with user
friendly push buttons and LCD menus.
The B5 and the B5 IR-Probe are the Q5 and Q5 IR-Probe with BACnet® MS/TP master
protocol. Therefore, the B5 and the B5 IR-Probe do not support the 4-20mA and VDC
analog output.
BACnet MS/TP protocol is a peer-to-peer, multiple master protocol based on token
passing. Only master nodes are allowed to send and receive tokens on the MSTP network.
Passive slave nodes on the other hand may only transmit data frames on the network in
response to a request from a master node. Passing the token represents overhead in the
sense that the messages used for managing the token do not carry data that is useful to
automation or monitoring.
The B5 and the B5 IR-Probe can be set to be a Master Node or a Slave Node in the field.
Factory default is slave node.
1. Specifications
1.1 Electrical/Mechanical Specifications
Input Power:
24VDC nominal, range 18 to 30VDC, 0.3A DC Total Max.
24VAC nominal, range 15 to 24VAC, 0.3A AC Total Max.
Fuse:
F2 on Main Board: Polyswitch 750mA
Polyswitch device resets after the fault is cleared and power to
the circuit is removed.
Sensor:
Combustible gases: Catalytic or NDIR
Toxic gases and Oxygen: Electrochemical
Carbon Dioxide: Non-Dispersive Infra-Red (NDIR)
Sampling:
Diffusion or Pump-through
85950-101-000 RB
2
August 7, 2015
B5 Operation And Maintenance Manual
Panel Indicators:
5 Status LED’s
• RS-485 TX Status (Green)
• RS-485 RX Status (Green)
• Relay1 Status (Red)
• Relay2 Status (Red)
• Relay2 Status (Red)
Display:
LCD graphic display c/w backlight
Keypad:
3 capacitive touch sensing Keys: F1, F2, F3
Relays:
3 Relays SPDT, Dry contacts
• 1.0A maximum at 30 VDC (resistive load)
• 0.3A maximum at 125VAC (resistive load)
Buzzer:
80 db at 10 cm, 2700 Hz
Buzzer 1, 2, 3: Programmable tone
Tone: chirp once / chirp twice / 50% duty cycle / constant ON
Output Signal:
BACnet® MS/TP master /slave protocol
Enclosure Rating:
IP 66 & NEMA 4, 4X, 12 & 13
Operating Temperature:
-40°C to 70°C, depends on sensor specification
Ambient Humidity:
5% to 95% RH (non-condensing)
Storage Temperature:
0°C to 40°C, depends on sensor specification
Size:
150mm X 90mm X 65mm
Weight:
Less than 0.5lbs
85950-101-000 RB
3
August 7, 2015
B5 Operation And Maintenance Manual
1.2 Sensor Specifications
Code
Gas
Symbol
16
Methane
CH4
17
Propane
C3H8
18
Hydrogen
H2
*19
Combustible
LEL
*20
Ethylene
C2H4
*21
Iso-Butane
C4H10
*22
Iso-Pentane
C5H12
*23
Methanol
CH3OH
*24
Benzene
C6H6
*25
Acetone
CH3CO
*26
Butanol, n-Butane BUTAN
Code
Gas
Symbol
0
Oxygen
O2
Code
Gas
Symbol
1
Carbon Monoxide
CO
1
Carbon Monoxide
CO
2
Hydrogen Sulfide
H2S
2
Hydrogen Sulfide
H2S
3
Sulphur Dioxide
SO2
5
Nitrogen Dioxide
NO2
6
Hydrogen
H2
6
Hydrogen
H2
7
Hydrogen Cyanide
HCN
9
Ammonia
NH3
9
Ammonia
NH3
11
Ozone
O3
13
Chlorine
Cl2
14
Chlorine Dioxide
ClO2
96
Arsine
AsH3
85950-101-000 RB
Gas
Density
Lighter
Heavier
Lighter
Slightly
Lighter
Heavier
Lighter
Lighter
Lighter
Lighter
Heavier
Gas
Density
0 - 100%LEL
Operating
Temperature
-10°C to +50°C
0 - 100%LEL
-10°C to +50°C
0 - 100%LEL
-10°C to +50°C
0 - 100%LEL
-10°C to +50°C
0 - 100%LEL
-10°C to +50°C
0 - 100%LEL
-10°C to +50°C
0 - 100%LEL
-10°C to +50°C
0 - 100%LEL
-10°C to +50°C
0 - 100%LEL
-10°C to +50°C
0 - 100%LEL
-10°C to +50°C
0 - 100%LEL
-10°C to +50°C
Span
Span
0 - 25%VOL
Gas
Density
Slightly
Lighter
Slightly
Lighter
Heavier
Heavier
Heavier
Heavier
Lighter
Lighter
Lighter
Lighter
Lighter
Heavier
Heavier
Heavier
Heavier
4
Operating
Temperature
-30°C to +55°C
Span
Operating
Temperature
0 – 250ppm
-20°C to +50°C
0 – 1000ppm
-20°C to +50°C
0 – 25ppm
-20°C to +50°C
0 – 100ppm
-20°C to +50°C
0 – 6ppm
-20°C to +50°C
0 – 10ppm
-20°C to +50°C
0 – 1000ppm
-20°C to +50°C
0 – 2000ppm
-20°C to +50°C
0 – 50ppm
-20°C to +50°C
0 – 100ppm
-30°C to +50°C
0 – 1000ppm
-30°C to +50°C
0 – 1ppm
-20°C to +40°C
0 – 5ppm
-20°C to +50°C
0 – 2ppm
-20°C to +40°C
0 – 1ppm
-20°C to +40°C
August 7, 2015
B5 Operation And Maintenance Manual
97
Phosphine
PH3
97
Phosphine
PH3
98
Silane
SiH4
99
Germane
GeH4
100 Diborane
B2H6
4
Nitric Oxide
NO
8
Hydrogen Chloride
HCl
Ethylene Oxide
ETO
12
101 Hydrogen Bromide
HBr
Heavier
Heavier
Heavier
Heavier
Slightly
Lighter
Slighter
Heavier
Heavier
Heavier
Heavier
-20°C to +40°C
0 – 1ppm
-20°C to +40°C
0 – 50ppm
-20°C to +40°C
0 – 2ppm
-20°C to +40°C
0 – 2ppm
-20°C to +40°C
0 –100ppm
-20°C to +50°C
0 – 30ppm
-20°C to +40°C
0 – 20ppm
-20°C to +50°C
0 – 30ppm
-20°C to +40°C
0 – 5000ppm
IR-CO2
Heavier
Heavier
Operating
Temperature
-20°C to +50°C
0 – 5%VOL
-20°C to +50°C
Carbon Dioxide
IR-CO2
Heavier
0 – 20%VOL
-20°C to +50°C
15
Carbon Dioxide
IR-CO2
0 – 100%VOL
-20°C to +50°C
16
Methane
IR-CH4
Heavier
Lighter
Lighter
Code
Gas
Symbol
15
Carbon Dioxide
IR-CO2
15
Carbon Dioxide
15
16
Methane
*NOTE: Mounting Heights
85950-101-000 RB
IR-CH4
Gas
Density
0 – 5ppm
Span
0 – 100%LEL
-20°C to +50°C
0 – 100%VOL
-20°C to +50°C
- Low = 9-18 inches (0.25-0.5 meters) from floor
- Mid = 4-6 feet (1.25-1.75 meters) from floor
- High = 9-18 inches (0.25-0.5 meters) from ceiling
5
August 7, 2015
B5 Operation And Maintenance Manual
2. Installation
2.1 Enclosures Physical Dimensions
The enclosure is a NEMA 4 rated enclosure and can be wall mounted with 4 screws. To
maintain the NEMA rating, it is important that the conduit opening is sealed upon
installation.
2.2 Terminals
B5 Terminals
85950-101-000 RB
6
August 7, 2015
B5 Operation And Maintenance Manual
2.2.1 Wire and Cable
Terminal blocks TB1 to TB7 accept 12 AWG to 24 AWG wire. Use 16 AWG or 18
AWG wire for the power supply in long wiring runs, which can be up to 1km (1,000
meters) long.
We recommend using BELDEN 9841 for communications. This wire has 120 ohm input
impendence, which will eliminate RS-485 communication problems.
2.2.2 RS-485 Terminator
The terminator on each end of the RS485 run is designed to match the electrical
impedance characteristic of the twisted pair wire, and will prevent signal echoes from
corrupting the data on the line. The terminator should be enabled on BOTH ends of the
RS485 run. Short and medium length ModBus/485 runs can operate without the
terminating resistor. Longer runs may require the terminating resistors. But adding
terminator dramatically increases power consumption.
Factory default setting is disabled terminator.
The B5 supplies this resistor on the main board, and it is chosen using a jumper at J4.
• J4 1-2: Terminator Disabled / OFF (default)
• J4 2-3: Terminator Enabled / ON
2.2.3 RS-485 Driver Replacement
RS-485 lines in heavy industrial environments are sometimes subjected to magnetic
disturbances causing sufficient inducted power surges to damage the driver integrated
circuit (IC). This IC (U6) has a socket on the circuit card for ease of replacement in the
field.
2.2.4 Relays Output
The B5 has three onboard programmable Single-Pole Double-Throw (SPDT) relays.
These relays can be used to control other equipment, such as fans, lights, horns, etc.
eliminating the need for a separate controller.
Three terminal blocks (TB1, TB2 and TB3) are located on the main board. Each relay can
be programmed individually.
Switching capability of each relay is:
•
1.0 A maximum resistive load at 30 VDC
•
0.3A maximum resistive load at 125VAC
85950-101-000 RB
7
August 7, 2015
B5 Operation And Maintenance Manual
2.2.5 Note for B5:
The B5 supports BACnet MS/TP protocol and can be networked to form a BACnet
MS/TP network.
The B5 default baud rate is 38400bps.
Each B5 on the MS/TP network must have a unique BACnet MAC address and unique
Device Instance Number (Object ID).
•
B5 valid MAC addresses are 0-127 for master node, 0-254 for slave node.
•
B5 default MAC address is 126.
•
Default Device Instance Number (Object ID) is 4005.
The B5 power supply and RS-485 connection are similar to the Q5. The B5 doesn't have
terminal blocks TB4 and TB6.
Avoid running communication wires or sensor input wires next to AC power wires or the
relay output wires. These can be sources of noise that can affect signal quality.
When the B5 input power is AC, the 24VAC can be either grounded or non-grounded.
Polarization is very important when the B5 is connected to a network. Make sure the
Neutral is connected to the GND of TB5.
2.2.6 Certification:
The Q5/B5 series have been certified to the following Standard:
Safety requirement for Electrical Equipment for Measurement, Control, and Laboratory UsePart 1: General Requirements CAN/CSA-22.2 No. 61010-1 Third Edition, Dated May 11, 2012;
And
Safety Requirements for Electrical Equipment for measurement, Control, and Laboratory UsePart 1: General Requirements UL 61010-1 Third Edition, Dated May 11, 2012.
Installation must be in accordance with ANSI/NFPA 70, National Electrical Code (NEC);
the
Canadian Electrical Code (CEC), Part I, CSA C22.1, and CSA C22.2 No. 0; and the
Manufacturers’ installation instructions
The Q5/B5 series have not been tested for Life Safety Applications and are not to be used in
Life Safety Applications in jurisdictions that require this certification.
85950-101-000 RB
8
August 7, 2015
B5 Operation And Maintenance Manual
3. Function and Configuration
3.1 Indicators
The indicators consist of five LED’s – two to indicate RS-485 digital communication,
three to indicate the status of relays 1-3.
3.1.1 RS485-TX/RX:
When the B5 is connected to a controller system via RS-485, the traffic of the
communication can be monitored visually through the two RS-485 indicators. One is RX
LED, which indicates the data stream received in from the controller. The other is TX
LED, which indicates the data stream out of the B5.
Note: If the TX LED or the RX LED is always ON, is indicative of a communication
problem. See Troubleshooting for RS-485.
3.1.2 Relay 1-3 LED:
Indicate the status of each relay. When the relay is actuated/closed, the relay LED is ON.
When the relay is de-actuated/open, the relay LED is OFF.
Note: If you set the relay to be Normally Energized (Fail Safe), the relay LED will
turn ON at non-alarm state and turn OFF at alarm state, because the LED reflects
the relay coil status.
85950-101-000 RB
9
August 7, 2015
B5 Operation And Maintenance Manual
3.2 Tool Function
Press key [F3] to enter tool functions that might be used frequently in the field.
TOOL FUNCTION
F1
1. ENTER
MAIN MENU
PRE
NEXT
ENTER
F2
F1
2. HUSH
BUZZER/RELAY
PRE
NEXT
ENTER
F2
F1
3. RESET
LATCHED/HUSHED
PRE
NEXT
ENTER
F2
F1
4. RESET
MENU PSW
PRE
NEXT
ENTER
RESET
LATCHED / HUSHED
F2
F1
5. TOOL MODE
PRE
EXIT?
PRE
NEXT
NEXT
TOOL
ENTER
F1 KEY
F2
F2 KEY
F3 KEY
3.2.1 Enter Main Menu
Press key [F1] to browse previous item of the current menu.
Press key [F2] to browse next item of the current menu.
Press key [F3] to enter the main menu for more configuration and settings.
3.2.2 Hush Buzzer and Relay
Press key [F3] to silence the buzzer and buzzer-style relays.
3.2.3 Reset Latched/Hushed
To acknowledge a latched condition or a hushed condition, press key [F3] to reset latched
relays and hushed buzzer for which the alarm condition has been removed. If the alarm
condition (e.g. high gas concentration) is still present the relay(s) will not reset.
3.2.4 Reset MENU Password
If you forgot the main menu password, you can reset the menu password to default
password “4321” by entering a correct active code. For the active code, contact QEL.
3.2.5 Exit Tool Mode
Press key [F3] to return to monitoring mode.
85950-101-000 RB
10
August 7, 2015
B5 Operation And Maintenance Manual
3.3 Main Menu Tree
The main menu is password protected. Once the password is accepted, you are allowed
into the main menu tree.
Factory default password is 4321.
Note: While in the menu tree, all normal monitoring operations stop. The alarm
status does not change.
F2
F1
MENU:
1_ SYSTEM SETUP
PRE
NEXT
F3
ENTER
F2
F1
MENU:
F3
2_ ZERO CAL
PRE
NEXT
ENTER
F2
F1
MENU:
F3
3_ SPAN CAL
PRE
NEXT
ENTER
F2
F1
MENU:
F3
4_ OUTPUT TEST
PRE
NEXT
F2
ENTER
F1
MENU:
F3
5_ VIEW SETTING
PRE
NEXT
F2
ENTER
F1
MENU:
F3
6_ ALARM SETUP
PRE
NEXT
ENTER
F2
F1
F3
F1/2
MENU:
F2
F1
B_ SIMULATION
MENU:
F3
7_ RELAY STYLE
PRE
NEXT
ENTER
PRE
NEXT
F2
F1
F1
MENU:
F3
8_ BUZZER STYLE
PRE
NEXT
ENTER
MENU:
ENTER
F2
F1
F3
C_ SITE SERVICE
PRE
NEXT
ENTER
F2
F1
F2
F1
MENU:
MENU:
F3
9_ A-OUT SETUP
PRE
NEXT
ENTER
F3
D_ FACTORY SET
PRE
NEXT
F2
F2
ENTER
F1
F1
F3
MENU:
A_ ALL DISABLE
PRE
NEXT
ENTER
MENU:
F3
E_ EXIT MENU
F1/2
PRE
NEXT
ENTER
F2
F2
F1
85950-101-000 RB
11
August 7, 2015
B5 Operation And Maintenance Manual
3.4 Menu “1_SYSTEM SETUP”
The system setup subdivision contains general settings for monitor operations,
communications and 4-20mA calibrations.
3.4.1 System Settings
Password:
Default password is 4321.
MAC
The B5 RS-485 address can be defined from 0 to 255. B5 default address is
126.
Address:
Object ID:
BACnet Device Instance Number. Default is 4005.
Baud rate:
Define baud rate for RS-485 communication with BACnet protocol.
B5 default baud rate is 38400 bps.
Scroll Rate:
In normal operation, the sensor and relay status information scrolls
automatically. Set the number of seconds for each item to be displayed.
Default value is 3 seconds.
Backlight:
The LCD backlight can be set to Always Off, Always On and Auto Power
Saving mode. In Auto Power Saving mode, the backlight will turn on for 10
seconds after any key has been pressed. Default setting is Always ON.
UTC Offset
The B5 supports the execution of the TimeSynchronization service and
UTCTimeSynchronization service. It indicates the number of minutes (
780 to +780) offset between local standard time and Universal Time
Coordinated. Default is +300 (US & Canada Eastern Time).
Daylight
Saving
It indicates whether daylight saving time is in effect (Enabled) or not
(Disabled) at the B5 location in UTCTimeSynchronization service.
Default is Enabled.
New
Password:
The new password can be any combination of up to four digits. Default
password is 4321.
Warning:
Be sure that you record the new password in a safe and
secure location!
Protocol:
The B5 supports BACnet MS/TP master or slave protocol. Default is
MS/TP master.
85950-101-000 RB
12
August 7, 2015
B5 Operation And Maintenance Manual
Display
Mode:
•
Display Instant: displays instantaneous gas concentration
•
Display Average:
o Displays STEL (15min average reading)
o Displays TWA (8 hour average reading)
o Displays daily peak
•
Display Alarm: displays alarm 1-8 status
•
Display Relay: displays relay 1-3 status
•
Display Buzzer: displays buzzer 1-3 status
•
Display A-Out mA: displays current 4-20mA output
•
Display A-Out VDC: displays current VDC output
•
Display Clock: displays real time clock
If there is nothing to display, the unit will display “Running…”
Auto Zero:
When AutoZero is set to ON, the unit will gather the lowest reading in 7-day
period and set the unit into Zeroing Calibration mode so that the lowest
reading goes to zero. When AutoZero is set to OFF, the unit will not adjust
its own zero and work off the last manual or factory calibration. Default
value is OFF.
NOTE: AutoZero works best in situations where the building will
purge at night (or over a weekend) to a zero concentration of target gas.
Key
Beeper:
ON: Beeping when keypad is touched
Restore
Default:
Note: Don’t do this if you don’t have calibration gas and precision
reference instrumentation to calibrate the unit.
OFF: No beeping when keypad is touched
To load defaults to factory settings, to restore the unit to correct operation.
The settings below will be restored to default values:
-Password, -Baud rate, -Scroll rate, -Backlight, -Display mode, -Key beeper,
-LCD contrast, -Gas type on the Sensor Board, -Alarm settings, Relay/Buzzer settings, and 4-20mA/1-5VDC settings.
The unit needs to change the gas type if the sensor on the sensor board is not
the default gas type: CO, CH4 or O2. Contact QEL for instructions.
Zero and span calibrations are needed.
85950-101-000 RB
13
August 7, 2015
B5 Operation And Maintenance Manual
ADJ Clock:
Adjust real time clock.
The B5 supports the execution of the TimeSynchronization service and
UTCTimeSynchronization service. The clock can be adjusted remotely.
ADJ
Contrast:
Adjust the LCD contrast. Valid values are between 10 (light) and 50 (dark).
Default is 21.
Check
Battery
The sensor board is equipped with a coin battery. This setting will enable or
disable the B5 to check the battery voltage and beep for a low battery level.
Default is ON.
Output
Alarm output (BV) present_value and relay output (BO) present_value
support command prioritization. The B5 has priority #12 as default.
Priority:
The lower the priority umber the more critical the nature of the output.
Priority #1 is considered the highest priority. Priority #16 is the lowest
priority.
85950-101-000 RB
14
August 7, 2015
B5 Operation And Maintenance Manual
3.5 Menu “2_ZERO CAL”
The B5 is calibrated using a two-point calibration process. First, use a “Zero Gas”, then
use a “CAL Gas” containing a known concentration of a standard reference gas, to set the
second point of reference.
3.5.1 Equipment Required
• A cylinder of Zero Gas, (clean air or nitrogen).
• A cylinder of Cal Gas
• Flow Limiting Regulator(s) 0.2 to 1.0 lpm
• Tubing
3.5.2 Zeroing Calibration Procedure
• “2_ ZERO CAL:”
2_ ZERO CAL
•
Press key [F3] and the device will show the calibration notice and then ask if you
want to continue. The middle line will display the current concentration.
CONTINUE?
XXPPM
•
Apply the Zero Gas.
•
Wait for about 3 minutes or until the reading is stable.
•
Press key [F3] to confirm Zeroing Cal.
•
When the device is in Zeroing CAL, it will take 3 seconds to 20 seconds to
complete.
•
When the zeroing CAL operation is over, the device will display “Accepted” and
return to “2_ZERO CAL”.
•
Make sure there is no Cal Error displayed. If Cal Error is reported, repeat the
procedures above. If the Cal Error is still showed up, the sensor may be expired.
•
Remove the gas.
•
Exit the menu to Monitoring Mode.
85950-101-000 RB
15
August 7, 2015
B5 Operation And Maintenance Manual
3.6 Menu “3_SPAN CAL”
• “3_ SPAN CAL”
3_ SPAN CAL
•
Press key [F3] and the device will ask for the CAL GAS, input the concentration
of the calibration gas.
CAL GAS:
>
•
XXX
Press key [F3] and the device will show the calibration notice and then show the
flow rate for the span calibration. Press any key to continue, and then the device
will ask you if you want to continue. The middle line will display the current
concentration.
CONTINUE?
XXPPM
•
Apply the calibration gas.
•
Wait for about 3 minutes or until the reading is stable.
•
Press key [F3] to confirm SPAN CAL.
•
When the device is in span cal, it will take 10 seconds to 1 minute to complete.
•
When the span cal operation is over, the device will display “Accepted” and
return to “3_SPAN CAL”.
•
Make sure there is no Cal Error displayed. If Cal Error is reported, repeat the
procedures above. If the Cal Error is still showed up, the sensor maybe expired.
•
Remove the gas.
•
Exit menu to Monitoring Mode.
85950-101-000 RB
16
August 7, 2015
B5 Operation And Maintenance Manual
3.7 Menu “4_OUT TEST”
During system installation and testing, it may be necessary to force relays and buzzers on
and off.
The Relay Testing feature allows the user to force the actuation of each relay. This
function forces an Actuate vs. De-actuate action, not an energized vs. non-energized
action. Therefore the user must be aware of these relays, which have been defined as
normally energized or not normally energized.
The 4mA (1VDC/2VDC) and 20mA (5VDC/10VDC) outputs can be tested too.
F1
F3
MENU: TESTING:
1. TEST RELAY1
Up
PRE
NEXT
F3
ENTER
F1
1. TEST RELAY1
OFF
ON
OFF
EXIT
F2
1. TEST RELAY1
ON
ON
OFF
EXIT
F2
F1
F3
MENU: TESTING:
2. TEST RELAY2
Up
PRE
NEXT
F3
ENTER
F1
2. TEST RELAY2
OFF
ON
OFF
EXIT
F2
2. TEST RELAY2
ON
ON
OFF
EXIT
F2
F1
F3
MENU: TESTING:
3. TEST RELAY3
Up
PRE
NEXT
F3
ENTER
F1
3. TEST RELAY3
OFF
ON
OFF
EXIT
F2
3. TEST RELAY3
ON
ON
OFF
EXIT
F2
F1
F3
MENU: TESTING:
4. TEST BUZZER
Up
PRE
NEXT
F3
ENTER
F1
4.TEST BUZZER
OFF
ON
OFF
EXIT
F2
4.TEST BUZZER
ON
ON
OFF
EXIT
F2
F1
F3
MENU: TESTING:
5. TEST 4MA
Up
PRE
NEXT
F3
ENTER
F1
5. TEST 4MA
OFF
ON
OFF
EXIT
F2
5. TEST 4MA
ON
ON
OFF
EXIT
F2
F1
F3
MENU: TESTING:
6. TEST 20MA
Up
PRE
NEXT
ENTER
F1
6.TEST 20MA
F3
OFF
ON
OFF
EXIT
F2
6.TEST 20MA
ON
ON
OFF
EXIT
F2
F1
VDC OUTPUT CAN BE TESTED AT THE SAME TIME AS
TESTING 4/20MA:
WHEN OUTPUT 4MA, THE VDC OUTPUTS 1V OR 2V
WHEN OUTPUT 20MA THE VDC OUTPUTS 5V OR 10V
4mA and 20mA TEST ONLY IN Q5
MENU: TESTING:
RETURN
TO MAIN MENU
EXIT TESTING
PRE
NEXT
ENTER
F2
85950-101-000 RB
17
August 7, 2015
B5 Operation And Maintenance Manual
3.8 Menu “5_VIEW SETTING”
This function is to verify the settings for the alarms, relays, buzzers and analog outputs.
F1
F3
1. VIEW
ALARM SETUP
PRE
NEXT
EXIT
F3
RELAY STYLE
NEXT
F1
ENTER
F3
BUZZER STYLE
NEXT
F1
ENTER
F3
A-OUT SETUP
NEXT
RELAY 1
EXIT
NEXT
F3
ENTER
F3
4. ON-DELAY: 010 SEC
5. OFF-DELAY: 010 SEC
END OF DETAIL
1. ON-DELAY: 010 SEC
2. OFF-DELAY: 010 SEC
3. CHIRP TWICE
END OF DETAIL
VIEW
BUZZER 3
EXIT
NEXT
F3
ENTER
ENTER
INPUT: 15 MIN AVG
4MA : 0 PPM
20MA : 100 PPM
VDC OUTPUT: 1-5V
F2
F1
F3
5. VIEW
EVENT RECORDS
NEXT
F3
ENTER
EVENT 1:
2009-12-08 20:05:32
RELAY 1 ON
PRE
NEXT
EXIT
F2
F1
EVENT 2:
2009-12-08 20:06:30
HUSHED BUZZER/RELAY
PRE
NEXT
EXIT
F2
F1
6. VIEW SETTING
F3
EXIT?
PRE
1. DE-ENERGIZE
2. NON-LATCHING
3. NORMAL STYLE
KEY TO CONTINUE ...
VIEW
F2
F1
4. VIEW
PRE
ENTER
F2
F1
3. VIEW
PRE
NEXT
INPUT: INSTANT
ON : 25PPM
OFF : 23PPM
TRIGGER: R1, 2, B1
F3
F2
2. VIEW
PRE
ALARM 2
F1
ENTER
F1
PRE
VIEW
NEXT
RETURN TO
MAIN MENU
ENTER
F2
85950-101-000 RB
18
August 7, 2015
B5 Operation And Maintenance Manual
3.9 Menu “6_ALARM SETUP”
The B5 supports alarm 1 to alarm 8.
Alarm is a programmable condition that can receive a selectable input and trigger relays
and buzzers.
Disabled or
Each alarm may be individually set to be enabled or disabled. If the alarm
is disabled, the alarm will not be used to calculate or trigger anything.
Enabled:
Default: Alarm 1 to Alarm 4 is enabled. Alarm 5 to Alarm 8 is
disabled.
Input:
One of five inputs is selected to calculate the alarm condition status to
trigger the selected outputs:
•
INSTANT: instantaneous gas reading.
•
15 MIN AVG (STEL): Short Term Exposure Limit, average
reading over 15 minutes.
•
8 HOURS AVG (TWA): 8-hour Time Weighted Average, average
reading over 8 hours.
•
DAILY PEAK: daily peak reading.
•
FAULT: If the unit reports any faults, no matter the gas
concentration, it will trigger the selected outputs.
Alarm On
If Alarm On is greater than or equal to Alarm Off:
and
Alarm On: Sets the concentration at or above which the relay will actuate.
Alarm Off
Alarm Off: Sets the concentration at or below which the relay will deactuate.
Reading:
If Action On is less than Action Off:
Action On: Sets the concentration below that the relay will actuate.
Action Off: Sets the concentration above that the relay will de-actuate.
Trigger:
Trigger Outputs: Relay 1, Relay 2, Relay 3, Buzzer 1, Buzzer 2, Buzzer 3
85950-101-000 RB
19
August 7, 2015
B5 Operation And Maintenance Manual
3.10 Menu “7_RELAY STYLE”
Enabled:
Each relay may be individually set to be enabled or disabled. If it’s
disabled, the relay will always de-actuate no matter what the current gas
concentration.
Default is Enabled.
Normally
Deenergized:
Latching:
Each relay may be individually set to be normally energized or normally
de-energized.
Default is normally de-energized.
Each relay may be set to latch in actuate status until acknowledged by a
front-panel action.
Default is Non-Latching.
ON Delay:
“Delay on Actuation” or “Delay on Make”. For each relay a separate time
delay may be set from 0 to 990 seconds before an alarm condition will
cause the relay to actuate.
Default is 5 seconds.
OFF Delay:
“Delay on De-Actuation” or “Delay on Break”. For each relay a separate
time delay may be set from 0 to 990 seconds before a return to a nonalarming signal condition will cause the relay to de-actuate.
Default is 5 seconds.
Style:
Normal Relay Style: Work as normal relay.
Buzzer Style Relay: When the relay is used to control a buzzer or horn.
Working as a buzzer style will make the relay have the same function as
the buzzer. It will be switched off when performing the Hush
Buzzer/Relay function in the Tool Menu.
Default is OFF.
85950-101-000 RB
20
August 7, 2015
B5 Operation And Maintenance Manual
3.11 Menu “8_BUZZER STYLE”
The buzzer style is almost identical to that of the relays, except the style that represents
the buzzer tone options:
•
Tone 1: Chirp once.
•
Tone 2: Chirp twice.
•
Tone 3: Intermittent 50% duty cycle.
•
Tone 4: Continuous.
The menus are identical to those for the Relay Style.
3.12 Menu “A_ALL DISABLE”
This function is for calibration, system testing etc. When All Disable is ON, the status of
the relay, buzzer and analog output, etc., will freeze in their current state.
Default is OFF.
3.13 Menu “B_SIMULATION”
Simulation mode is used to assist in testing the installation before commissioning. When
simulation is enabled, the unit will not detect gas concentrations; it will display the
simulated value and use it to calculate the status of relays and buzzers. This feature is
available for evaluating the user settings and testing the installation (e.g.: the activation of
the valve, fan speed, relay set points, etc. can be verified.)
Any concentration between 0ppm and 9999ppm can be simulated.
3.14 Menu “C_SITE SERVICE” and “D_FACTROY SET”
Factory service staff access only. The customer has no need to operate it.
4. BACnet PIC Statement Supported By B5
See document: 85950-103-000 (B5 PIC Statement).
85950-101-000 RB
21
August 7, 2015
B5 Operation And Maintenance Manual
4.1 Smart Sensor Assembly Replacement
4.1.1 Disassembling
Observe all safety and electrical codes and regulations before removing enclosure lid.
Important: Calibrate the transmitter whenever a component is replaced. But if you replace
a smart sensor assembly with a sensor onboard from QEL, you don’t need to recalibrate
the transmitter, as all the calibration information has been stored in the smart sensor
board in the factory process.
4.1.2 Replacement Procedure
To replace the entire smart sensor assembly, complete the following steps:
1. Power down the transmitter.
2. Remove the four screws securing the enclosure lid assembly to the base enclosure
and remove the enclosure lid assembly.
3. Remove the two screws securing the smart sensor board and remove the smart
sensor board from the lid assembly
4. Feed the O-ring over the sensor on the new smart sensor assembly
5. Plug the new smart sensor assembly and secure with two screws. Ensure that the
connectors are correctly matched. Incorrect installation may damage the sensor
assembly and/or the display board.
85950-101-000 RB
22
August 7, 2015
B5 Operation And Maintenance Manual
4.1.3 Replacement Parts
Code
Gas
Symbol
Span
Smart Sensor Assembly
0
Oxygen
O2
0 - 25%VOL
85930-016-000
Code
Gas
Symbol
Span
Smart Sensor Assembly
16
17
18
*19
*20
*21
*22
*23
*24
*25
*26
Methane
Propane
Hydrogen
Combustible
Ethylene
Iso-Butane
Iso-Pentane
Methanol
Benzene
Acetone
Butanol, n-Butane
CH4
C3H8
H2
LEL
C2H4
C4H10
C5H12
CH3OH
C6H6
CH3CO
BUTAN
Code
Gas
Symbol
Span
Smart Sensor Assembly
1
1
2
2
3
5
6
6
7
9
9
11
13
14
96
97
97
98
99
100
Carbon Monoxide
Carbon Monoxide
Hydrogen Sulfide
Hydrogen Sulfide
Sulphur Dioxide
Nitrogen Dioxide
Hydrogen
Hydrogen
Hydrogen Cyanide
Ammonia
Ammonia
Ozone
Chlorine
Chlorine Dioxide
Arsine
Phosphine
Phosphine
Silane
Germane
Diborane
CO
CO
H2S
H2S
SO2
NO2
H2
H2
HCN
NH3
NH3
O3
Cl2
ClO2
AsH3
PH3
PH3
SiH4
GeH4
B2H6
0 – 250ppm
0 – 1000ppm
0 – 25ppm
0 – 100ppm
0 – 6ppm
0 – 10ppm
0 – 1000ppm
0 – 2000ppm
0 – 50ppm
0 – 100ppm
0 – 1000ppm
0 – 1ppm
0 – 5ppm
0 – 2ppm
0 – 1ppm
0 – 5ppm
0 – 1ppm
0 – 50ppm
0 – 2ppm
0 – 2ppm
85930-018-001
85930-018-201
85930-018-002
85930-018-202
85930-018-003
85930-018-005
85930-018-006
85930-018-206
85930-018-007
85930-018-009
85930-018-209
85930-018-011
85930-018-013
85930-018-014
85930-018-096
85930-018-097
85930-018-297
85930-018-098
85930-018-099
85930-018-100
85950-101-000 RB
0
0
0
0
0
0
0
0
0
0
0
-
100%LEL
100%LEL
100%LEL
100%LEL
100%LEL
100%LEL
100%LEL
100%LEL
100%LEL
100%LEL
100%LEL
23
85930-017-016
85930-017-017
85930-017-018
85930-017-019
85930-017-020
85930-017-021
85930-017-022
85930-017-023
85930-017-024
85930-017-025
85930-017-026
August 7, 2015
B5 Operation And Maintenance Manual
Code
Gas
Symbol
Span
Smart Sensor Assembly
4
8
12
101
Nitric Oxide
Hydrogen Chloride
Ethylene Oxide
Hydrogen Bromide
NO
HCl
ETO
HBr
0 –100ppm
0 – 30ppm
0 – 20ppm
0 – 30ppm
85930-018-004
85930-018-008
85930-018-012
85930-018-101
Code
Gas
Symbol
Span
Smart Sensor Assembly
IR-CO2
IR-CO2
IR-CO2
IR-CO2
IR-CH4
IR-CH4
0 –5000ppm
0 – 5%VOL
0 – 20%VOL
0 – 100%VOL
0 – 100%LEL
0 – 100%VOL
85930-019-015
85930-019-215
85930-019-315
85930-019-415
85930-019-016
85930-019-216
15
15
15
15
16
16
Carbon Dioxide
Carbon Dioxide
Carbon Dioxide
Carbon Dioxide
Methane
Methane
85950-101-000 RB
24
August 7, 2015
B5 Operation And Maintenance Manual
4.1.4 Accessories
Pump-thru &
Calibration Cap Kit
SKU#: 85930-006-000
Splash Guard Kit
SKU#: 85930-007-000
Duct Mount Adapter Kit
Free stand or Duct mount IR-Probe
SKU#: 85930-040-000
Note: For Duct Mount Installation, B5 needs both the Pump-thru Kit and Duct Mount Kit.
85950-101-000 RB
25
August 7, 2015
B5 Operation And Maintenance Manual
5. Troubleshooting
This troubleshooting guide is intended as an aid in identifying the cause of unexpected
behavior and determining whether the behavior is due to normal operation or an internal
or external problem.
SYMPTOMS
RS-485
PROBABLE CAUSE
•
RX LED or
TX LED constantly ON
RS-485 bus connection has a
SUGGESTED SOLUTION
•
problem
the problem
•
RS-485 driver U6 is damaged
•
Replace U6 IC on main board
•
Controller side RS-485 driver
•
Replace the RS-485 driver on
has problem
No response to gas
Disconnect the cable to isolate
the controller
•
Sensor screen is dirty
•
Clean sensor opening
•
Sensor has expired
•
Replace smart sensor assembly,
see Replacement Parts
Apparent false alarm
•
Puff of gas
•
Monitor is functioning
•
Not properly calibrated
•
Recalibrate
•
Solvent fumes or interference
•
Remove source of interfering gas
•
Check that grounding and
from high levels of interfering
gas
•
Radio frequency interference
shielding is correct
85950-101-000 RB
26
August 7, 2015
B5 Operation And Maintenance Manual
WARRANTY STATEMENT
The information contained in this manual is based upon data considered accurate; however, no
warranty is expressed or implied regarding the accuracy of this data. All QEL equipment is
warranted against defects in material and workmanship for a period of two years from date of
shipment with the following exceptions:
Electrochemical Sensors (Toxic)
Catalytic Sensors (Combustible)
Six Months
One Year
During the warranty period we will repair or replace, at our discretion, any components or
complete units that prove, in our opinion, to be defective. We are not liable for consequential or
incidental damage to auxiliary interfaced equipment.
A returned material authorization number should be obtained from the factory prior to returning
any goods. All return shipments must be shipped freight prepaid and a copy of the maintenance
records should accompany the unit concerned.
Warranty should be considered F.O.B. the factory. Labour and travel time are chargeable for any
field site visits required for warranty work.
LIMITED LIABILITY
All QEL systems shall be installed by a qualified technician/electrician and maintained in strict
accordance with data provided for individual systems in the form of installation/maintenance
manuals. QEL assumes no responsibility for improper installation, maintenance, etc., and
stresses the importance of reading all manuals. QEL shall not be responsible for any liability
arising from auxiliary interfaced equipment nor any damage resulting from the installation or
operation of this equipment.
QEL’s total liability is contained as above with no other liability expressed or implied, as the
purchaser is entirely responsible for installation and maintenance of systems.
This warranty is in lieu of all other warranties, expressed or implied, and no representative or
person is authorized to represent or assume for QEL any liability in connection with the sales of
our products other than that set forth herein.
NOTE:
Due to on-going product development, QEL reserves the right to change
specifications without notice and will assume no responsibility for any costs as a
result of modifications.