SRcb
–
Ripple-control checkback receiver for DIN-rail mounting
The SRcb is a state-of-the-art, Swistra-compatible audio-frequency ripple-control receiver
designed for DIN-rail mounting.
Thanks to the SRcb, incoming data from ripple-control telegrams and audio frequency levels
can be
recorded at any given location in the grid. All relevant data will reliably be stored locally and can be
downloaded to laptop or PC via RS232-interface. Thus, the data can be used for analysis purposes and
even be edited via MS Office. Due to its modularity, the SRcb can be used everywhere and can easily be
extended.
Features
•
T3-phase measurement input
•
ripple-control
frequency,
adjustable
from 116 to 2,000 Hz
•
3 freely parameterizable, potential-free
outputs with optical indication (LED)
•
signaling contact for message „evaluation of the received telegram“ (parameterizable)
•
voltage
output
in
analogy
to
the
measured frequency levels (0 - 10V
correspond to 0 - 10% signal level) optional
•
Input and output terminals are designed
as screw-type terminals
•
Serial interface RS232 for connection
with laptop or PC
•
Wall and DIN-rail mounting
•
Swistra-functionalities (option)
Technology
All Swistec ripple-control receivers use state-of-the-art, recently developed filter algorithms capable of
reliably processing ripple-control signals with operating voltages <0.3% Un – a result of state-of-the-art
processor technology combining high CPU power with little power consumption.
Technical Data
Power supply:
•
•
Mains voltage
Frequency of mains voltage
100 - 230 VAC -15% ...+15%
47 Hz ... 63 Hz
•
•
5W
12mVA / 5mW
•
Power consumption (supply)
Power consumption
(measurement input)
Surge voltage resistance
Filter data:
•
•
•
•
•
•
•
Operating frequency
Operating voltage
Non-operating voltage
Maximum control voltage
Measuring input voltage
Sampling rate
Swistra functions
110 – 2000 Hz (programmable)
Uf ≥ 0.3% Un and Uf > Unf
Unf ≥ 0.1% Un
8 to 15 times Uf (depending on frequency)
85 - 264 VAC
0.2 ms
available, option
Output data:
•
•
•
•
•
Number of relays
Nominal switching voltage Uc
Nominal switching current Ic
Optical indication
Voltage output
3 (potential-free, change-over contact)
230 V, 50 Hz (max. 247 VAC / 350 VDC)
120 mA (350 mA / 10 ms)
LED
0 - 10 V (corresponding to
0 - 10 % signal level)
mains terminal and relay 1 x 0.2 - 2.5 mm²
or 2 x max. 1.0 mm²
Real-time clock:
•
•
Accuracy
Power reserve (option)
+/- 20 x 10-6
> 48 hours
Resistance to
climatic conditions:
•
•
Operating temperature
Storage temperature
-20 ... +60°C
-30 ... +60°C
4kV 1.2/50 μs in accordance with IEC 60060-1
Type of protection:
IP20
Types of
installation:
DIN-rail or wall
Unit dimensions:
•
height x width x depth
76 x 100 x 60 mm
Swistec GmbH
Graue-Burg-Str. 24 - 26
53332 Bornheim
Germany
Phone: +49 - 2227 / 9171-0
Fax:
+49 - 2227 / 9171-41
info@swistec.de
www.swistec.de
November 2014