TM172PDG42R
Product datasheet
Characteristics
Disclaimer: This documentation is not intended as a substitute for and is not to be used for determining suitability or reliability of these products for specific user applications
Modicon M172 Performance Display 42 I/Os,
Ethernet, Modbus
Main
Range of product
Modicon M171/M172
Product or component type
Programmable controllers
Product specific application
HVAC and pumping solution
Variant
Programmable
Number of inputs/outputs
42
Discrete input number
12
Discrete output number
2 for relay outputs SPST with same common
2 for relay outputs SPST with independent common
2 for relay outputs SPDT with same common
3 for relay outputs SPST with independent common
Discrete output current
1 A for relay SPDT
3 A for relay SPST
Analogue input number
12 configurable by pair
Analogue output number
4 voltage, range: 0...10 V
2 voltage/current, range: 4...20 mA or 0...10 V or PWM (2 kHz)
Complementary
Number of port
1 CAN port - screw terminal block
1 USB type A - USB type A female
1 USB type mini B - USB device port Mini-B
2 RS485 - screw terminal block (Modbus serial link or BACnet MS/TP)
1 Ethernet - RJ45 (Modbus TCP and BACnet IP with webserver)
Input/Output number
12 analog input(s)
6 analog output(s)
12 digital input(s)
12 digital output(s)
Discrete input logic
Sink or source (positive/negative)
Discrete input voltage
24 V AC/DC
Discrete input current
2.5 mA
Input impedance
20 kOhm
Analogue input type
Direct input
Apr 01, 2018
1
Impedance 0...1500 hOhm
Impedance 0...300 daOhm
Voltage 0...5 V (absolute or ratiometric)
PTC temperature probe - 55...150 °C - res.: 0.1 °C
NTC temperature probe - 50...110 °C - res.: 0.1 °C (extended)
NTC temperature probe - 40...150 °C - res.: 0.1 °C
Pt 1000 temperature probe - 200...850 °C - res.: 0.1 °C
Voltage 0...10 V
Current 0...20 mA/4...20 mA
Sensor power supply
5 V DC at 50 mA (supplied by the controller)
24 V DC at 150 mA (supplied by the controller)
[Us] rated supply voltage
20...38 V DC
24 V +/- 10 % AC
Power consumption in W
15 W at 24 V AC/DC
Realtime clock
Built-in realtime clock at -20...60 °C
Display type
Backlit LCD - 128 x 64 pixels
Overvoltage category
II
Local signalling
1 LED red programmable
1 LED yellow programmable
1 LED green programmable
1 LED green power
Mounting support
DIN rail
Panel mounting with accessory
Width
144 mm
Height
110 mm
Depth
60.5 mm
Product weight
0.385 kg
Environment
Directives
2011/65/EU - RoHS directive
86/188/EEC - physical agents (noise) directive
2006/95/EC - low voltage directive
1907/2006/EC - REACH directive
Standards
EN/IEC 60730
Product certifications
EAC (pending)
cURus (pending)
CE
CSA (pending)
Ambient air temperature for operation
-20...60 °C conforming to UL 60730-1
-20...65 °C with derating conforming to UL 60730-1
Ambient air temperature for storage
-30...70 °C
Relative humidity
5...95 % non-condensing
IP degree of protection
IP20
Pollution degree
2
Offer Sustainability
Sustainable offer status
Green Premium product
RoHS (date code: YYWW)
Compliant - since 1529 - Schneider Electric declaration of conformity
Schneider Electric declaration of conformity
REACh
Reference not containing SVHC above the threshold
Reference not containing SVHC above the threshold
Product environmental profile
Available
Product environmental
Product end of life instructions
Available
End of life manual
2
Product datasheet
Dimensions Drawings
TM172PDG42R
Dimensions
3
Product datasheet
Mounting and Clearance
Mounting and Clearance
DIN Rail Mounting
Clips for Panel Mounting
Panel Mounting
4
TM172PDG42R
Clearance
Incorrect Mounting Position
Assembling a Module
Wiring Sections and Torque
A, C, D, E, F, G, H
B
5
Product datasheet
Connections and Schema
Connections and Schema
Logic Controller Connectors
Power Supply
(1)
Type T fuse 2 A
Digital Inputs
The COM_DI terminals are not connected internally.
Fast Digital Inputs
Pulse / Frequency counter up to 2 kHz.
6
TM172PDG42R
Digital Outputs
The Cx terminals are not connected internally.
Analog Inputs
(1)
(2)
(CN5 + CN13) Max. current: 50 mA.
(CN5 + CN13) Max. current: 150 mA.
Analog Outputs
AO3, AO4 can be used also as PWM generator, up to 2 kHz.
RS 485 - Modbus SL or BACnet MS/TP
Apply 120 Ω terminal resistance.
7
CAN Expansion Bus
8