Red Lion Meter CUB5RT Specification

Bulletin No. CUB5RT-F
Drawing No. LP0644
Released 02/10
Tel +1 (717) 767-6511
Fax +1 (717) 764-0839
www.redlion.net
MODEL CUB5RT - MINIATURE ELECTRONIC 5-DIGIT RTD METER
 MINIMUM AND MAXIMUM DISPLAY CAPTURE
 LCD, REFLECTIVE OR GREEN/RED LED BACKLIGHTING
 0.48" (12.2 mm) HIGH DIGITS
 OPTIONAL SETPOINT OUTPUT CARD
 OPTIONAL SERIAL COMMUNICATION CARD (RS232 or RS485)
 OPTIONAL USB PROGRAMMING CARD
 OPERATES FROM 9 TO 28 VDC POWER SOURCE
 FRONT PANEL OR CRIMSON PROGRAMMABLE
 DISPLAY COLOR CHANGE CAPABILITY AT SETPOINT OUTPUT
 NEMA 4X/IP65 SEALED FRONT BEZEL
 RTD INPUTS
RTD types Pt385, Pt392, Ni672, Cu427
 PROGRAMMABLE TEMPERATURE OFFSET
 SELECTABLE °F or °C WITH 1 or 0.1 DEGREE RESOLUTION
C
 °F OR °C DISPLAY ANNUNCIATORS
UL
R
US LISTED
IND. CONT. EQ.
51EB
GENERAL DESCRIPTION
SAFETY SUMMARY
The CUB5 provides the user the ultimate in flexibility, from its complete user
programming to the optional setpoint control and communication capability.
The CUB5RT accepts an RTD input and provides a temperature display in
Celcius or Farenheit. The meter also features minimum and maximum display
capture, display offset, °F or °C indicator, and programmable user input. The
display can be toggled either manually or automatically between the selected
displays.
The CUB5 display has 0.48" (12.2 mm) high digits. The LCD is available in
two versions, reflective and red/green backlight. The backlight version is user
selectable for the desired color and also has variable display intensity.
The capability of the CUB5 can be easily expanded with the addition of
option cards. Setpoint capability is field installable with the addition of the
setpoint output cards. Serial communications capability for RS232 or RS485 is
added with a serial option card.
The CUB5 can be powered from an optional Red Lion Micro-Line/Sensor
Power Supply (MLPS), which attaches directly to the back of a CUB5. The
MLPS is powered from 85 to 250 VAC and provides up to 400 mA to drive the
unit and sensors.
All safety related regulations, local codes and instructions that appear in this
literature or on equipment must be observed to ensure personal safety and to
prevent damage to either the instrument or equipment connected to it. If
equipment is used in a manner not specified by the manufacturer, the protection
provided by the equipment may be impaired.
Do not use this meter to directly command motors, valves, or other actuators
not equipped with safeguards. To do so can be potentially harmful to persons or
equipment in the event of a fault to the meter.
CAUTION: Risk of Danger.
Read complete instructions prior to
installationand operation of the unit.
CAUTION: Risk of electric shock.
DIMENSIONS In inches (mm)
Note: Recommended minimum clearance (behind the panel) for mounting clip installation is 2.15" (54.6) H x 3.00" (76.2) W.
.13 (3.3)
SEL
1.30 +.024
-.000
1.29 (32.8)
1.54 (39.1)
(33 +6
-0 )
RST
2.95 (74.9)
.15 (3.8)
1.71
(43.4)
2.68
(68
+.025
-.000
+8
-0 )
Distributed by Relevant Solutions | 1.888.858.3647 | relevantsolutions.com
1
ORDERING INFORMATION
TYPE
MODEL NO.
CUB5
DESCRIPTION
CUB5RT
Optional Plug-in
Cards
CUB5RTB0
Single Relay Output Card
CUB5RLY0
CUB5SNK
Dual Sinking Output Card
CUB5SNK0
RS485 Serial Communications Card
CUB5COM1
RS232 Serial Communications Card
CUB5COM2
USB Programming Card
CUB5USB0
+12 VDC Micro-Line Power Supply, 85 to 250 VAC source, 400 mA max out
MLPS1000
CUB5USB
MLPS
1 Crimson
CUB5RTR0
RTD Meter with Backlight Display
CUB5RLY
CUB5COM
Accessories
PART NUMBER
RTD Meter with Reflective Display
CBLPROG
+24 VDC Micro-Line Power Supply, 85 to 250 VAC source, 200 mA max out
MLPS2000
RS232 Programming Cable (DB9-RJ11)
CBLPROG0
CBPRO
Crimson PC Configuration Software for Windows 98, ME, 2000, XP 1
SFCRD200
CBLUSB
USB Programming Cable
CBLUSB00
software is a free download from http://www.redlion.net/
GENERAL METER SPECIFICATIONS
5. RESPONSE TIME:
Display: 500 msec min.
Output: 1.25 sec max (with input filter setting of 0)
6. USER INPUT (USR): Programmable input. Connect terminal to common
(USR COMM) to activate function. Internal 10K pull-up resistor to +9 to
28 VDC.
Threshold Levels: VIL = 1.0 V max; VIH = 2.4 V min; VMAX = 28 VDC
Response Time: 5 msec typ.; 50 msec debounce (activation and release)
7. CERTIFICATIONS AND COMPLIANCES:
SAFETY
UL Recognized Component, File #E179259, UL61010-1, CSA 22.2 No. 61010-1
Recognized to U.S. and Canadian requirements under the Component
Recognition Program of Underwriters Laboratories, Inc.
UL Listed, File # E137808, UL508, CSA C22.2 No. 14-M95
LISTED by Und. Lab. Inc. to U.S. and Canadian safety standards
Type 4X Outdoor Enclosure rating (Face only), UL50
IECEE CB Scheme Test Report #E179259-V01-S02
Issued by Underwriters Laboratories, Inc.
IEC 61010-1, EN 61010-1: Safety requirements for electrical equipment
for measurement, control, and laboratory use, Part 1.
IP65 Enclosure rating (Face only), IEC 529
ELECTROMAGNETIC COMPATIBILITY
Emissions and Immunity to EN 61326: Electrical Equipment for Measurement,
Control and Laboratory use.
1. DISPLAY: 5 digit LCD 0.48" (12.2 mm) high digits
CUB5RTR0: Reflective LCD with full viewing angle
CUB5RTB0: Transmissive LCD with selectable red or green LED backlight,
viewing angle optimized. Display color change capability with output state
when using an output module.
2. POWER: Input voltage range is +9 to +28 VDC with short circuit and input
polarity protection. Must use an RLC model MLPS or a NEC Class 2 or
Limited Power Source (LPS) rated power supply.
INPUT CURRENT INPUT CURRENT
@ 9 VDC WITHOUT @ 9 VDC WITH
CUB5RLY0
CUB5RLY0
MODEL
NO.
DISPLAY COLOR
CUB5RTR0
CUB5RTB0
CUB5RTB0
--Red (max intensity)
Green (max intensity)
10 mA
85 mA
95 mA
40 mA
115 mA
125 mA
3. READOUT:
Resolution: 1 or 0.1 degrees
Scale: °F or °C
Offset Range: -19999 to 19999 display units
4. RTD INPUTS:
Isolation: Input and EXC terminals are not electrically isolated from the
power supply or optional comms cards.
Failed Sensor Display:  or 
Overrange/Underrange Input: /
Overrange/Underrange Display : “.....”/“-.....”
Maximum Input Voltage: 30 VDC
Type: 2, 3 or 4 wire
Excitation current: 100 ohm range: 165 μA
10 ohm range: 2.5 mA
Lead resistance: 100 ohm range: 10 ohm/lead max.
10 ohm range: 3 ohms/lead max.
Balanced Lead Resistance: Automatically compensated up to max per lead.
Unbalanced Lead Resistance: Uncompensated.
INPUT TYPE
100 ohm Pt
alpha = .00385
100 ohm Pt
alpha = .00392
120 ohm Nickel
alpha = .00672
10 ohm Copper
alpha = .00427
RANGE
ACCURACY*
(18 to 28°C)
ACCURACY*
(0 to 50°C)
STANDARD
-200 to 850°C
0.4°C
1.6°C
IEC 751
-200 to 850°C
0.4°C
1.6°C
-80 to 260°C
0.2°C
0.5°C
-100 to 260°C
0.4°C
0.9°C
Immunity to Industrial Locations:
Electrostatic discharge
EN 61000-4-2 Criterion A
4 kV contact discharge
8 kV air discharge
Electromagnetic RF fields
EN 61000-4-3 Criterion A
10 V/m
Fast transients (burst)
EN 61000-4-4 Criterion A
2 kV power
1 kV signal
Surge
EN 61000-4-5 Criterion A
1 kV L-L,
2 kV L&N-E power
RF conducted interference
EN 61000-4-6 Criterion A
3 V/rms
Power frequency magnetic fields EN 61000-4-8 Criterion A
30 A/m
Emissions:
Emissions
EN 55011
Class A
no official
standard
no official
standard
no official
standard
*After 20 min. warm-up. Accuracy is specified in two ways: Accuracy at
23°C and 15 to 75% RH environment; and Accuracy over a -35 to 75°C and
0 to 85% RH (non condensing) environment. Accuracy specified over the -35
to 75°C operating range includes meter tempco effects. The specification
includes the A/D conversion errors and linearization conformity. Total system
accuracy is the sum of meter and probe errors. Accuracy may be improved by
field calibrating the meter readout at the temperature of interest.
Note:
1. Criterion A: Normal operation within specified limits.
Refer to EMC Installation Guidelines for additional information.
8. MEMORY: Nonvolatile E2PROM memory retains all programming
parameters and max/min values when power is removed.
Distributed by Relevant Solutions | 1.888.858.3647 | relevantsolutions.com
2
Storage Temperature: -35 to 85 °C
Operating and Storage Humidity: 0 to 85% max. relative humidity (noncondensing)
Vibration According to IEC 68-2-6: Operational 5 to 500 Hz, in X, Y, Z
direction for 1.5 hours, 5 g’s.
Shock According to IEC 68-2-27: Operational 30 g's, 11 msec in 3
directions.
Altitude: Up to 2000 meters
11. CONSTRUCTION: This unit is rated for NEMA 4X/IP65 requirements for
outdoor use. Installation Category I, Pollution Degree 2. High impact plastic
case with clear viewing window. Panel gasket and mounting clip included.
12. WEIGHT: 3.2 oz (100 g)
9. CONNECTIONS: Wire clamping screw terminals
Wire Strip Length: 0.3" (7.5 mm)
Wire Gage: 30-14 AWG copper wire
Torque: 5 inch-lbs (0.565 N-m) max.
10. ENVIRONMENTAL CONDITIONS:
Operating Temperature Range for CUB5TCR0: -35 to 75 °C
Operating Temperature Range for CUB5TCB0 depends on display color
and intensity level as per below:
INTENSITY LEVEL
Red Display
Green Display
1&2
3
4
5
1&2
3
4
5
TEMPERATURE
-35
-35
-35
-35
-35
-35
-35
-35
to
to
to
to
to
to
to
to
75°C
70°C
60°C
50°C
75°C
65°C
50°C
35°C
OPTIONAL PLUG-IN CARDS
ADDING OPTION CARDS
The CUB5 meters can be fitted with optional output cards and/or serial
communications cards. The details for the plug-in cards can be reviewed in the
specification section below. The plug-in cards, that are sold separately, can be
installed initially or at a later date.
RS485 SERIAL COMMUNICATIONS CARD
Type: RS485 multi-point balanced interface (non-isolated)
Note: Non-grounded (isolated) RTD probes must be used when multiple units
are connected in an RS485 network, or measurement errors will occur.
Baud Rate: 300 to 38.4k
Data Format: 7/8 bits; odd, even, or no parity
Bus Address: 0 to 99; max 32 meters per line
Transmit Delay: Selectable (refer to CUB5COM bulletin)
WARNING: Disconnect all power to the unit before
installing Plug-in card.
SINGLE RELAY CARD
Type: Single FORM-C relay
Isolation To Sensor & User Input Commons: 1400 Vrms for 1 min.
Working Voltage: 150 Vrms
Contact Rating: 1 amp @ 30 VDC resistive; 0.3 amp @ 125 VAC resistive
Life Expectancy: 100,000 minimum operations
RS232 SERIAL COMMUNICATIONS CARD
Type: RS232 half duplex (non-isolated)
Baud Rate: 300 to 38.4k
Data Format: 7/8 bits; odd, even, or no parity
USB PROGRAMMING CARD
Type: USB virtual comms port
Connection: Type B
Baud Rate: 300 to 38.4k
Unit Address: 0 to 99
DUAL SINKING OUTPUT CARD
Type: Non-isolated switched DC, N Channel open drain MOSFET
Current Rating: 100 mA max.
VDS ON: 0.7 V @ 100 mA
VDS MAX: 30 VDC
Offstate Leakage Current: 0.5 mA max.
1.0 INSTALLING
THE
METER
forward slot possible. To achieve a proper seal, tighten the latch screws evenly
until the unit is snug in the panel (Torque to approx. 28 to 36 in-oz [0.202 to 0.26
N-m]). Do not over-tighten the screws.
INSTALLATION
The meter meets NEMA 4X/IP65 requirements when properly installed. The
unit is intended to be mounted into an enclosed panel. Prepare the panel cutout
to the dimensions shown. Remove the panel latch from the unit. Slide the panel
gasket over the rear of the unit to the back of the bezel.
The unit should be installed fully assembled. Insert
the unit into the panel cutout.
While holding the unit in place, push the panel
latch over the rear of the unit so that the tabs of
the panel latch engage in the slots on the case.
The panel latch should be engaged in the farthest
INSTALLATION ENVIRONMENT
The unit should be installed in a location that does not exceed the operating
temperature and provides good air circulation. Placing the unit near devices that
generate excessive heat should be avoided.
The bezel should only be cleaned with a soft cloth and neutral soap product.
Do NOT use solvents. Continuous exposure to direct sunlight may accelerate the
aging process of the bezel.
Do not use tools of any kind (screwdrivers, pens, pencils, etc.) to operate the
keypad of the unit.
NUT FASTENER
BEZEL
PANEL
MOUNTING SCREW
+.025
-.000
(68 +.8 )
-.0
2.68
MOUNTING CLIP
PANEL
GASKET
Distributed by Relevant Solutions | 1.888.858.3647 | relevantsolutions.com
3
+.024
-.000
(33 +.6)
-.0
1.30
2.0 SETTING
THE
JUMPERS
100 ohm
This jumper is used to select the proper input range. The input range selected
in programming must match the jumper setting. Select a range that is high
enough to accommodate the maximum input signal to avoid overloads. To
access the jumper, remove the rear cover of the meter.
Warning: Exposed line voltage exists on the circuit boards. Remove
all power to the meter and load circuits before accessing inside of
the meter.
10 ohm
INPUT RANGE JUMPER
INPUT RANGE JUMPER
MAIN CIRCUIT
BOARD
REMOVING THE REAR COVER
To remove the rear cover, locate the cover locking tab below the 2nd and 3rd
input terminals. To release the tab, insert a small, flat blade screwdriver between
the tab and the plastic wall below the terminals. Inserting the screwdriver will
provide enough pressure to release the tab locks. To replace the cover, align the
cover with the input terminals and press down until the cover snaps into place.
INPUT RANGE
JUMPER LOCATION
3.0 INSTALLING PLUG-IN CARDS
provide enough pressure to release the tab locks. To replace the cover, align the
cover with the input terminals and press down until the cover snaps into place.
The Plug-in cards are separately purchased option cards that perform specific
functions. The cards plug in to the main circuit board of the meter.
WARNING: Exposed line voltage exists on the circuit boards.
Remove all power to the meter and load circuits before
accessing inside of the meter.
CAUTION: The Plug-in cards and main circuit board contain static
sensitive components. Before handling the cards, discharge
static charges from your body by touching a grounded bare
metal object. Ideally, handle the cards at a static controlled
clean workstation. Also, only handle the cards by the edges.
Dirt, oil or other contaminants that may contact the cards can
adversely affect circuit operation.
Range Jumpers
Setpoint Card
Comms or
Programming
Card
REMOVING THE REAR COVER
To remove the rear cover, locate the cover locking tab below the 2nd and 3rd
input terminals. To release the tab, insert a small, flat blade screwdriver between
the tab and the plastic wall below the terminals. Inserting the screwdriver will
Locking Tab
4.0 WIRING
THE
METER
b. Connect the shield to earth ground at both ends of the cable, usually when
the noise source frequency is above 1 MHz.
c. Connect the shield to common of the meter and leave the other end of the
shield unconnected and insulated from earth ground.
3. Never run Signal or Control cables in the same conduit or raceway with AC
power lines, conductors feeding motors, solenoids, SCR controls, and
heaters, etc. The cables should be ran in metal conduit that is properly
grounded. This is especially useful in applications where cable runs are long
and portable two-way radios are used in close proximity or if the installation
is near a commercial radio transmitter.
4. Signal or Control cables within an enclosure should be routed as far as possible
from contactors, control relays, transformers, and other noisy components.
5. In extremely high EMI environments, the use of external EMI suppression
devices, such as ferrite suppression cores, is effective. Install them on Signal
and Control cables as close to the unit as possible. Loop the cable through the
core several times or use multiple cores on each cable for additional protection.
Install line filters on the power input cable to the unit to suppress power line
interference. Install them near the power entry point of the enclosure. The
following EMI suppression devices (or equivalent) are recommended:
Ferrite Suppression Cores for signal and control cables:
Fair-Rite # 0443167251 (RLC# FCOR0000)
TDK # ZCAT3035-1330A
Steward # 28B2029-0A0
Line Filters for input power cables:
Schaffner # FN610-1/07 (RLC# LFIL0000)
Schaffner # FN670-1.8/07
Corcom # 1 VR3
Note: Reference manufacturer’s instructions when installing a line filter.
6. Long cable runs are more susceptible to EMI pickup than short cable runs.
Therefore, keep cable runs as short as possible.
7. Switching of inductive loads produces high EMI. Use of snubbers across
inductive loads suppresses EMI.
Snubber: RLC# SNUB0000.
WIRING OVERVIEW
Electrical connections are made via screw-clamp terminals located on the
back of the meter. All conductors should conform to the meter’s voltage and
current ratings. All cabling should conform to appropriate standards of good
installation, local codes and regulations. It is recommended that the power
supplied to the meter (DC or AC) be protected by a fuse or circuit breaker.
Strip the wire, leaving approximately 0.3" (7.5 mm) bare lead exposed
(stranded wires should be tinned with solder.) Insert the lead under the correct
screw-clamp terminal and tighten until the wire is secure. (Pull wire to verify
tightness.) Each terminal can accept up to one #14 AWG (2.55 mm) wire, two
#18 AWG (1.02 mm), or four #20 AWG (0.61 mm).
EMC INSTALLATION GUIDELINES
Although this meter is designed with a high degree of immunity to ElectroMagnetic Interference (EMI), proper installation and wiring methods must be
followed to ensure compatibility in each application. The type of the electrical
noise, source or coupling method into the meter may be different for various
installations. The meter becomes more immune to EMI with fewer I/O
connections. Cable length, routing, and shield termination are very important
and can mean the difference between a successful or troublesome installation.
Listed below are some EMC guidelines for successful installation in an
industrial environment.
1. The meter should be mounted in a metal enclosure, which is properly
connected to protective earth.
2. Use shielded (screened) cables for all Signal and Control inputs. The shield
(screen) pigtail connection should be made as short as possible. The
connection point for the shield depends somewhat upon the application.
Listed below are the recommended methods of connecting the shield, in order
of their effectiveness.
a. Connect the shield only at the panel where the unit is mounted to earth
ground (protective earth).
Distributed by Relevant Solutions | 1.888.858.3647 | relevantsolutions.com
4
Sinking Logic
+9 to +28 VDC: +VDC
Power Common: -VDC
USR COMM
USR
}
-
INP+
EXC
The user input of the meter is
internally pulled up to +9 to +28 V
with 10 K resistance. The input is
active when it is pulled low (<0 .7 V).
USR
Connect external switching device between the
User Input terminal and User Input Common.
COMM
USR
INP+
DC Power
EXC
4.2 USER INPUT WIRING
COMM
4.1 POWER WIRING
+
PWR COMMON
+9-28 VDC
PWR COMMON
+9-28 VDC
4.3 INPUT WIRING
CAUTION: Power input common and sensor input common are NOT isolated
from user input common. In order to preserve the safety of the meter
application, the power input common and the sensor input common must
be suitably isolated from hazardous live earth referenced voltages; or
input common must be at protective earth ground potential. If not, hazardous
live voltage may be present at the User Inputs and User Input Common
terminals. Appropriate considerations must then be given to the potential of
the user input common with respect to earth common; and the common of
the isolated plug-in cards with respect to input common.
INP+
EXC
COMM
2-WIRE RTD
INP+
EXC
COMM
3-WIRE RTD
JUMPER
4.4 SETPOINT (OUTPUT) WIRING
SINGLE SETPOINT RELAY PLUG-IN CARD
ELECTRICAL CONNECTIONS
COM
N.O.
N.C.
COM
DUAL SETPOINT N-FET OPEN DRAIN PLUG-IN CARD
N.O.
N.C.
ELECTRICAL CONNECTIONS
COM
OSNK 1(2)
(30 V MAX.)
OSNK1
OSNK2
COM
Output Common is not isolated from DC Power Common. Load
must be wired between OSNK terminal and V+ of the load supply.
4.6 USB PROGRAMMING
4.5 SERIAL COMMUNICATION WIRING
1
RS485
N/C
2
RX
N/C
3
COMM
N/C
4
COMM
COMM
5
N/C
A+
6
USB PROGRAMING PLUG-IN CARD
TX
N/C
B-
SERIAL COMMUNICATIONS PLUG-IN CARD
6
5
4
3
2
1
RS232
RJ11 CONNECTOR PIN OUTS
Distributed by Relevant Solutions | 1.888.858.3647 | relevantsolutions.com
5
5.0 REVIEWING
THE
FRONT BUTTONS
SEL
BUTTON
AND
DISPLAY
RST
DISPLAY MODE OPERATION
ENTERING PROGRAM MODE
PROGRAMMING MODE OPERATION
SEL
Index display through enabled values
Press and hold for 2 seconds to activate
Store selected parameter and index to next parameter
RST
Resets values (MIN / MAX) or outputs
Advances through the program menu
Increments selected parameter value or selection
OPERATING MODE DISPLAY DESIGNATORS
MAX - Maximum display capture value
MIN - Minimum display capture value
“1” - To the right of the display indicates setpoint 1 output activated.
“2” - To the right of the display indicates setpoint 2 output activated.
Pressing the SEL button toggles the meter through the selected displays. If display scroll is enabled, the display will toggle automatically every four seconds between
the enabled display values.
6.0 PROGRAMMING
THE
METER
OVERVIEW
DISPLAY
MODE
PROGRAMMING MENU
SEL
NO
Pro
Signal Input
Parameters
Secondary
Function
Parameters
Display and Front
Panel Key
Parameters
Setpoint
Output
Parameters
Serial
Setup
Parameters
RST
SEL
1-INP
SEL
SEL
2-SEC
3-dSP
SEL
SEL
4-SPt
5-SEr
PROGRAMMING MODE ENTRY (SEL BUTTON)
PROGRAMMING MODE EXIT (SEL BUTTON)
It is recommended that all programming changes be made off line, or before
installation. The meter normally operates in the Display Mode. No parameters
can be programmed in this mode. The Programming Mode is entered by
pressing and holding the SEL button. If it is not accessible then it is locked by
either a security code, or a hardware lock.
The Programming Mode is exited by pressing the SEL button with Pro NO
displayed. This will commit any stored parameter changes to memory and
return the meter to the Display Mode. (If power loss occurs before returning to
the Display Mode, verify recent parameter changes.)
PROGRAMMING TIPS
MODULE ENTRY (SEL & RST BUTTONS)
It is recommended to start with Module 1 and proceed through each module
in sequence. When programming is complete, it is recommended to record the
parameter programming and lock out parameter programming with the user
input or programming security code.
The Programming Menu is organized into separate modules. These modules
group together parameters that are related in function. The display will alternate
between Pro and the present module. The RST button is used to select the desired
module. The displayed module is entered by pressing the SEL button.
FACTORY SETTINGS
MODULE MENU (SEL BUTTON)
Factory Settings may be completely restored in Module 2. This is useful
when encountering programming problems.
Pressing both the SEL and the RST button on power-up will also load the
factory settings and display rESEt. This allows operation in the event of a
memory failure or corrupted data.
Each module has a separate module menu (which is shown at the start of each
module discussion). The SEL button is pressed to advance to a particular
parameter to be changed, without changing the programming of preceding
parameters. After completing a module, the display will return to Pro NO.
Programming may continue by accessing additional modules.
ALTERNATING SELECTION DISPLAY
SELECTION / VALUE ENTRY
In the explanation of the modules, the following dual display with arrows will
appear. This is used to illustrate the display alternating between the parameter
on top and the parameter’s Factory Setting on the bottom. In most cases,
selections and values for the parameter will be listed on the right.
For each parameter, the display alternates between the present parameter and
the selections/value for that parameter. The RST button is used to move through
the selections/values for that parameter. Pressing the SEL button, stores and
activates the displayed selection/value. This also advances the meter to the next
parameter.
For numeric values, press the RST button to access the value. The right hand
most digit will begin to flash. Pressing the RST button again increments the
digit by one or the user can hold the RST button and the digit will automatically
scroll. The SEL button will advance to the next digit. Pressing and holding the
SEL button will enter the value and move to the next parameter.
Indicates Program Mode Alternating Display
Parameter
USrIN


N0
Selection/Value
Factory Settings are shown.
Distributed by Relevant Solutions | 1.888.858.3647 | relevantsolutions.com
6
6.1 MODULE 1 - SIGNAL INPUT PARAMETERS (1-INP)
PARAMETER MENU
1-INP
Pro
SEL
tYPE
dECPt
SCALE
RTD Type
Temperature
Scale
Display
Decimal Point
OFSEt
FILtr
bANd
Display Offset
Value
Filter Setting
Filter Band
RTD TYPE

tYPE

Pt385
SELECTION
TYPE
RANGE JUMPERS
Pt385
Pt392
Ni672
Cu427
RTD Platinum 385
100 ohm
RTD Platinum 392
100 ohm
RTD Nickel 672
100 ohm
RTD Copper 10 
10 ohm


°F
°F
°C

0
0


0
DISPLAY OFFSET VALUE
-19999
to
19999
The temperature display can be corrected with an offset value. This can be
used to compensate for probe errors, errors due to variances in probe placement
or adjusting the readout to a reference thermometer.
FILtr


1
FILTER BAND
00
to
199

display units

NO
USER INPUT FUNCTION
MODE
DESCRIPTION
NO
P-Loc
No Function
rESEt
Reset (Edge triggered)
d-HLd
Display Hold
d-SEL
d-LEV
COLOr
Display Select
(Edge Triggered)
Display Intensity Level
(Edge Triggered)
Backlight Color
(Edge Triggered)
Print
Print Request
Serial transmit of the active parameters
selected in the Print Options menu
(Module 5).
P-r5t
rSt-1
rSt-2
rSt12
Print and Reset
Same as Print Request followed by a
momentary reset of the assigned value(s).
Setpoint 1 Reset
Resets setpoint 1 output.
Setpoint 2 Reset
Resets setpoint 2 output.
Setpoint 1 and 2 Reset
Reset both setpoint 1 and 2 outputs.
User Input disabled.
Program Mode Lock-out
0.0
Select the decimal point location for the desired display resolution. This
selection applies for the Input, MAX and MIN displays.
OFSEt
USrIN
DISPLAY
DISPLAY DECIMAL POINT

10
User Input
Assignment
TEMPERATURE SCALE
Select the temperature scale. This selection applies for the Input, MAX and
MIN displays.
dECPt

U-ASN
User Input
Function
The filter will adapt to variations in the input signal. When the variation
exceeds the input filter band value, the filter disengages. When the variation
becomes less than the band value, the filter engages again. This allows for a
stable readout, but permits the display to settle rapidly after a large process
change. The value of the band is in display units, independent of the Display
Decimal Point position. A band setting of ‘0’ keeps the filter permanently
engaged at the filter level selected in the previous parameter.
Select the RTD type used for the application. The appropriate curve will be
automatically loaded for the selected type. The position of the Input Range
Jumper must match the RTD type selected.
SCALE
bANd

USrIN
FILTER SETTING
See Programming Mode Access chart
(Module 3).
Resets the assigned value(s) to the
current input value.
Holds the assigned display, but all other
meter functions continue as long as
activated (maintained action).
Advance once for each activation.
Increase intensity one level for each
activation (backlight version only).
Change backlight color with each
activation (backlight version only).
USER INPUT ASSIGNMENT
U-ASN
0,1 2 3

If the displayed temperature is difficult to read due to small process
variations or noise, increased levels of filtering will help to stabilize the display.
Software filtering effectively combines a fraction of the current input reading
with a fraction of the previous displayed reading to generate the new display.
Filter values represent no filtering (0), up to heavy filtering (3). A value of 1
for the filter uses 1/4 of the new input and 3/4 of the previous display to
generate the new display. A filter value of 2 uses 1/8 new and 7/8 previous. A
filter value of 3 uses 1/16 new and 15/16 previous.

dSP
HI
LO
HI-LO
dSP
Select the value(s) to which the User Input Function is assigned. The User
Input Assignment only applies if a selection of reset, display hold, or print and
reset is selected in the User Input Function menu.
Distributed by Relevant Solutions | 1.888.858.3647 | relevantsolutions.com
7
6.2 MODULE 2 - SECONDARY FUNCTION PARAMETERS (2-SEC)
2-SEC
Pro
PARAMETER MENU
SEL
HI-En
HI-t
LO-En
LO-t
Max Display
Enable
Max Capture
Delay Time
Min Display
Enable
Min Capture
Delay TIme
FCS
Factory
Service
Operations


NO
NO
YES
MAX CAPTURE DELAY TIME


2.0
0.0
to
CodE


48
The CUB5RT uses stored resistance calibration values
to provide accurate temperature measurements. Over
time, the electrical characteristics of the components
inside the meter could slowly change. The result is that
the stored calibration values may no longer accurately
define the input circuit. For most applications, recalibration every 1 to 2 years
should be sufficient.
Calibration of the CUB5RT involves a resistance calibration. Allow 30
minute warm up before performing any calibration related procedure. The
following procedures should be performed at an ambient temperature of 15 to
35 °C (59 to 95 °F).
Calibration should only be performed by individuals experienced in
calibrating electronic equipment.
CAUTION: The accuracy of the calibration equipment will directly affect the
accuracy of the CUB5RT.
Enables the Maximum Display Capture capability.
HI-t
Access Code
For Service
Operations
CALIBRATION
MAX DISPLAY ENABLE
HI-En
CodE
999.9 seconds
When the Input Display is above the present MAX value for the entered
delay time, the meter will capture that display value as the new MAX reading.
A delay time helps to avoid false captures of sudden short spikes.
10 OHM RTD Range Calibration
1. Set the Input Range Jumper to 10 ohm.
2. With the display at CodE 48, press and hold the SEL button for 2 seconds. Unit
will display CAL NO.
3. Press the RST button. Display reads CAL r10.
4. Press the SEL button. Display reads 00r.
5. Apply a direct short to terminals INP+, EXC, and COMM using a three wire
link. Press SEL. Display reads CALC for about 15 seconds.
6. When the display reads 15.0r, apply a precision resistance of 15 ohms (with an
accuracy of 0.01% or better) to terminals INP+, EXC, and COMM using a
three wire link. Press SEL. Display reads CALC for about 15 seconds.
7. When display reads CAL NO, press the SEL button to exit calibration, or
proceed to the 100 ohm RTD Range Claibration.
MIN DISPLAY ENABLE
LO-En


NO
NO
YES
Enables the Minimum Display Capture capability.
MIN CAPTURE DELAY TIME
LO-t


2.0
0.0
to
999.9 seconds
100 OHM RTD Range Calibration
1. Set the Input Range Jumper to 100 ohm.
2. With the display at CodE 48, press and hold the SEL button for 2 seconds. Unit
will display CAL NO.
3. Press the RST button until the display reads CAL r100.
4. Press the SEL button. Display reads 0.0r.
5. Apply a direct short to terminals INP+, EXC, and COMM using a three wire
link. Press SEL. Display reads CALC for about 15 seconds.
6. When the display reads 300.0r, apply a precision resistance of 300 ohms (with
an accuracy of 0.01% or better) to terminals INP+, EXC, and COMM using
a three wire link. Press SEL. Display reads CALC for about 15 seconds.
7. When display reads CAL NO, press the SEL button to exit calibration.
When the Input Display is below the present MIN value for the entered delay
time, the meter will capture that display value as the new MIN reading. A delay
time helps to avoid false captures of sudden short spikes.
FACTORY SERVICE OPERATIONS
FCS


NO
NO
yES
Select YES to perform any of the Factory Service Operations shown below.
RESISTANCE DISPLAY MODE
CodE


66
CodE


85
Entering Code 85 will place the CUB5RT in a resistance
display mode. This mode is useful for diagnostic purposes
before and after calibration, or to display the measured
resistance of a connected RTD probe. If the RTD type is set
for Cu427 with the jumper set to the 10 ohm position, the display will read
resistance in 0.000 ohms resolution. For all other RTD types, with the jumper in
the 100 ohm position, the display will read in 0.00 ohms resolution.
Re-entering code 85 toggles the display back to the temperature display mode
without having to remove power from the meter. If power is removed, the
display always returns to the temperature display mode when power is reapplied.
RESTORE FACTORY DEFAULT SETTINGS
Entering Code 66 will overwrite all user settings with
the factory settings. The meter will display rESEt and then
return to CodE 00. Press SEL button to exit the module.
Pressing both the SEL and the RST button on power-up
will also load the factory settings and display rESEt. This allows operation in
the event of a memory failure or corruted data.
Distributed by Relevant Solutions | 1.888.858.3647 | relevantsolutions.com
8
6.3 MODULE 3 - DISPLAY
AND
FRONT PANEL BUTTON
PARAMETERS (3-dSP)
PARAMETER MENU
3-dSP
SEL
dSP-t
SEL
rSt
Front Panel
Display
Select Enable
Display
Update Time
ScroL
Front Panel
Reset Enable
COLOr
Display
Scroll
Enable
0.5
1
2
d-LEV
seconds


CodE
NO


dSP
NO
HI
LO
HI-LO
dSP
This selection allows the RST button to reset the selected value(s).


NO
yES
to
5

000
000
to
999
USER INPUT USER INPUT SECURITY MODE WHEN “SEL”
FUNCTION
STATE
CODE
BUTTON IS PRESSED
DISPLAY SCROLL ENABLE
ScroL
1
The Security Code determines the programming mode and the accessibility
of programming parameters. This code can be used along with the Program
Mode Lock-out (P-Loc) in the User Input Function parameter (Module 1).
Two programming modes are available. Full Programming mode allows all
parameters to be viewed and modified. Quick Programming mode permits only
the Setpoint values to be modified, but allows direct access to these values
without having to enter Full Programming mode.
Programming a Security Code other than 0, requires this code to be entered
at the CodE prompt in order to access Full Programming mode. Depending on the
code value, Quick Programming may be accessible before the CodE prompt
appears (see chart).
FRONT PANEL RESET ENABLE (RST)


PROGRAMMING SECURITY CODE
The yES selection allows the SEL button to toggle through the enabled
displays.
rSt
Programming
Security Code
Enter the desired Display Intensity Level (1-5). The display will actively dim
or brighten as levels are changed. This parameter is active for backlight units only.

yES
Display
Intensity
Level
5
FRONT PANEL DISPLAY SELECT ENABLE (SEL)
yES
CodE
DISPLAY INTENSITY LEVEL (BACKLIGHT UNIT ONLY)
This parameter sets the display update time in seconds.
SEL
d-LEV
Display
Color
DISPLAY UPDATE TIME
dSP-t 

1
Pro
Backlight Unit Only
0
Full Programming
Immediate Access
1-99
Quick Programming
After Quick
Programming with
correct code entry at
CodE prompt *
100-999
CodE prompt
With correct code entry
at CodE prompt *
0
Programming Lock
No Access
1-99
Quick Programming
No Access
100-999
CodE prompt
With correct code entry
at CodE prompt *
0-999
Full Programming
Immediate Access
NO
not
The yES selection allows the display to automatically scroll through the
enabled displays. The scroll rate is every 4 seconds.
P-Loc
______
FULL PROGRAMMING
MODE ACCESS
DISPLAY COLOR (BACKLIGHT UNIT ONLY)
COLOr


rEd
P-Loc
rEd
Active
6rn
Enter the desired display color, red or green. This parameter is active for
backlight units only.
Not Active
* Entering Code 222 allows access regardless of security code.
Distributed by Relevant Solutions | 1.888.858.3647 | relevantsolutions.com
9
6.4 MODULE 4 - SETPOINT OUTPUT PARAMETERS (4-SPt)
PARAMETER MENU
4-SPt
Backlight
Unit Only
SEL
SPSEL
Act-n
Setpoint
Select
SPt-n
Setpoint
Action
HYS-n
Setpoint
Value
tON-n
tOF-n
On Time
Delay
Hysteresis
Value
rSt-n
Off Time
Delay
Output Reset
Action
The Setpoint Output Parameters are only active when an optional output
module is installed in the meter.

SETPOINT SELECT
SPSEL


NO
SP-1

NO
YES
Probe
Burn-out
ChC-n
Change Display
Color with
Output State

100
-9999
to
99999
HYSTERESIS VALUE
HYS-n


1
to
59999
2
Enter desired hysteresis value. See Setpoint Output Figures for visual
explanation of how setpoint output actions (balanced and unbalanced) are
affected by the hysteresis. When the setpoint is a control output, usually
balanced hysteresis is used. For alarm applications, usually unbalanced
hysteresis is used. For unbalanced hysteresis modes, the hysteresis functions on
the low side for high acting setpoints and functions on the high side for low
acting setpoints.
SETPOINT 2 ENABLE

brn-n
Standby
Operation
Enter the desired setpoint value. The decimal point position for the setpoint
and hysteresis values follow the selection set in Module 1.
SP-2
Enter the setpoint (output) to be programmed. The n in the following
parameters will reflect the chosen setpoint number. After the chosen setpoint
is completely programmed, the display will return to SPSEL. Repeat steps for
each setpoint to be programmed. Select NO to exit the module. The number of
setpoints available is setpoint output card dependent.
Enb-2
Stb-n
SETPOINT VALUE
SPt-n
NO
rEn-n
Output Reset
With Display
Reset Enable
Pro
NO
Note: Hysteresis eliminates output chatter at the switch point, while time delay
can be used to prevent false triggering during process transient events.
Select YES to enable Setpoint 2 and access the setup parameters. If NO is
selected, the unit returns to SPSEL and setpoint 2 is disabled.
ON TIME DELAY
SETPOINT ACTION
Act-n 
 HI-Ub
LO-bL
HI-bL
HI-Ub
LO-Ub
High Acting, with balanced hysteresis
=
Low Acting, with balanced hysteresis
=
High Acting, with unbalanced hysteresis
=
Low Acting, with unbalanced hysteresis
Hys
SP - ½Hys
0.0
0.0
to
599.9 Sec
tOF-n


0.0
0.0
to
599.9 Sec
Enter the time value in seconds that the output is delayed from turning off
after the trigger point is reached. A value of 0.0 allows the meter to update the
output status per the response time listed in the Specifications.
SP + ½Hys
SP

OFF TIME DELAY
=
SP + ½Hys

Enter the time value in seconds that the output is delayed from turning on
after the trigger point is reached. A value of 0.0 allows the meter to update the
output status per the response time listed in the Specifications.
Enter the action for the selected setpoint (output). See Setpoint Output
Figures for a visual detail of each action.
HI-bL
LO-bL
HI-Ub
LO-Ub
tON-n
SP
Hys
SP - ½Hys
OUTPUT RESET ACTION
OUTPUT
STATE
OFF
ON
OFF
OUTPUT
STATE
OFF
OFF
rSt-n
TRIGGER POINTS
TRIGGER POINTS
High Acting (Balanced Hys) =
ON
HI-bL
Low Acting (Balanced Hys) =

LO-bL

Auto
Auto
LAtCH
L-dLY
Enter the reset action of the output. See figure for details.
Auto = Automatic action; This action allows the output to automatically reset off
Hys
SP - Hys
OUTPUT
STATE
at the trigger points per the Setpoint Action shown in Setpoint Output
Figures. The “on” output may be manually reset (off) immediately by the
front panel RST button or user input.The output remains off until the trigger
point is crossed again.
SP + Hys
SP
Hys
SP
OFF
ON
OFF
TRIGGER POINTS
OUTPUT
STATE
OFF
ON
LAtCH = Latch with immediate reset action; This action latches the output on at
OFF
the trigger point per the Setpoint Action shown in Setpoint Output Figures.
Latch means that the output can only be turned off by the front panel RST
button or user input manual reset, serial reset command or meter power cycle.
TRIGGER POINTS
High Acting (Unbalanced Hys) =
HI-Ub
Low Acting (Unbalanced Hys) =
LO-Ub
Distributed by Relevant Solutions | 1.888.858.3647 | relevantsolutions.com
10
When the user input or RST button is activated (momentary action), the
corresponding “on” output is reset immediately and remains off until the
trigger point is crossed again. (Previously latched alarms will be off if power
up Display Value is lower than setpoint value.)
STANDBY OPERATION
L-dLY = Latch with delay reset action; This action latches the output on at the
Stb-n


NO
NO
YES
When YES, the output is disabled (after a power up) until the trigger point is
crossed. Once the output is on, the output operates normally per the Setpoint
Action and OutputReset Action.
trigger point per the Setpoint Action shown in Setpoint Output Figures. Latch
means that the output can only be turned off by the front panel RST button
or user input manual reset, serial reset command or meter power cycle. When
the user input or RST button is activated (momentary action), the meter
delays the event until the corresponding “on” output crosses the trigger off
point. (Previously latched outputs are off if power up Display Value is lower
than setpoint value. During a power cycle, the meter erases a previous L-dLY
reset if it is not activated at power up.)
PROBE BURN-OUT ACTION
MANUAL
RESET

Hys
SP - Hys
{
OFF
OUTPUT
STATE
OFF
ON
ON
OFF
ON
OFF
OFF
ON
OFF
ON
ON
OFF

ON
OFF
OFF
( Auto )
( LAtCH )
CHANGE DISPLAY COLOR w/OUTPUT STATE
( L-dLY )
NO
ChC-n


NO
NO
YES
This parameter enables the backlight CUB5 to switch the backlight color when
the output state changes. This parameter is only active for the backlight version.
OUTPUT RESET WITH DISPLAY RESET

OFF
OFF
Enter the probe burn-out action. In the event of a temperature probe failure
(open or short), the output can be programmed to be on or off.
Setpoint Output Reset Actions
rEn-n

brn-n
SP
YES
YES
This parameter enables the RST button or user input to reset the output when
the display is reset.
Note: For this parameter to operate, the RST button or User Input being used
must be set to dSP and the Input value must be displayed. If these conditions are
not met, the output will not reset.
6.5 MODULE 5 - SERIAL SETUP PARAMETERS (5-SEr)
PARAMETER MENU
5-SEr
Pro
SEL
bAUd
Baud Rate
dAtA
Data Bit
PAr
Addr
Parity Bit
Meter
Address
Abbr
Abbreviated
Printing
OPt
Print
Options
The Serial Setup Parameters are only active when one of the optional serial communications/programming cards is installed in the meter.
Refer to the CUB5COM bulletin for details and setup for the CUB5 RS232 or RS485 serial communications.
Refer to the CUB5USB bulletin for details on the CUB5 USB programming and programming requirements.
LIMITED WARRANTY
The Company warrants the products it manufactures against defects in materials and workmanship for a period limited to two years
from the date of shipment, provided the products have been stored, handled, installed, and used under proper conditions. The
Company’s liability under this limited warranty shall extend only to the repair or replacement of a defective product, at The
Company’s option. The Company disclaims all liability for any affirmation, promise or representation with respect to the products.
The customer agrees to hold Red Lion Controls harmless from, defend, and indemnify RLC against damages, claims, and expenses
arising out of subsequent sales of RLC products or products containing components manufactured by RLC and based upon personal
injuries, deaths, property damage, lost profits, and other matters which Buyer, its employees, or sub-contractors are or may be to
any extent liable, including without limitation penalties imposed by the Consumer Product Safety Act (P.L. 92-573) and liability
imposed upon any person pursuant to the Magnuson-Moss Warranty Act (P.L. 93-637), as now in effect or as amended hereafter.
No warranties expressed or implied are created with respect to The Company’s products except those expressly contained herein.
The Customer acknowledges the disclaimers and limitations contained herein and relies on no other warranties or affirmations.
Distributed by Relevant Solutions | 1.888.858.3647 | relevantsolutions.com
11
bAUd
Baud Rate
Setpoint
Select
SPSEL
Display
Update Time
dSP-t
5-SEr
SEL
SEL
SEL
Max Display
Enable
HI-En
RST
RST
4-SPt
RST
3-dSP
RST
2-SEC
RTD Type
SEL
tYPE
Exit
Programming
End
RST
SEL
SEL
1-INP
RST
NO
Pro
Data Bit
dAtA
Setpoint
Action
Act-n
Front Panel
Display
Select Enable
SEL
Max Capture
Delay Time
HI-t
Temperature
Scale
SCALE
Press and hold SEL button
to enter Programming Mode.
Parity Bit
PAr
Setpoint
Value
SPt-n
Front Panel
Reset Enable
rSt
Min Display
Enable
LO-En
Display
Decimal Point
dECPt
OFSEt
Meter
Address
Addr
Hysteresis
Value
HYS-n
Display
Scroll
Enable
ScroL
Min Capture
Delay TIme
LO-t
Display Offset
Value
FILtr
Abbreviated
Printing
Abbr
On Time
Delay
tON-n
Display
Color
COLOr
USrIN
Print
Options
OPt
Off Time
Delay
tOF-n
Display
Intensity
Level
d-LEV
rSt-n
Output Reset
Action
rEn-n
Output Reset
With Display
Reset
User Input
Assignment
U-ASN
Programming
Security Code
CodE
User Input
Function
Access Code
For Service
Operations
CodE
Filter Band
bANd
Backlight Unit Only
Factory
Service
Operations
FCS
Filter Setting
Standby
Operation
Stb-n
Probe
Burn-out
Action
brn-n
Change Display
Color with
Output State
ChC-n
Backlight
Unit Only
CUB5RT PROGRAMMING QUICK OVERVIEW
Distributed by Relevant Solutions | 1.888.858.3647 | relevantsolutions.com
Download PDF
Similar pages