Our technology. Your peace-of-mind
Product list
JULY 2017
Detnov Security started its activity in 2007 in Barcelona. We are a company specialized in the development and
manufacture of fire alarm systems for any kind of installation as offices, hospitals, hotels, shopping malls, university
campuses, residential buildings, etc.
We have a team of highly qualified professionals with more than 20 years experience in the field of fire protection.
Our R & D team designs each of our products from advanced production technoligies to meet the market needs.
We have our own laboratories for electromagnetic compatibility (EMC / EMI) and calibration, which allow us to
guarantee the quality of all our products with the highest standards exigency.
índex
ADDRESSABLE SYSTEM
Addressable control panels .............................................................
Addressable repeaters .....................................................................
Voice evacuation system .................................................................
Addressable control panel accessories .........................................
Addressable detectors .....................................................................
Addressable detectors with built-in isolator ................................
Addressable detectors (black) ........................................................
Addressable detector accessories .................................................
Addressable manual call points ....................................................
Addressable sounders and beacons .............................................
Addressable modules ......................................................................
Addressable modules with built-in isolator ..................................
Addressable module accessories ..................................................
06
07
07
08
10
10
11
12
13
14
15
17
18
CONVENTIONAL SYSTEM
Conventional control panels ...........................................................
Conventional control panel accessories .......................................
Conventional detectors ...................................................................
Conventional detectors (black) ......................................................
Conventional detector accessories ...............................................
Conventional manual call points ...................................................
Conventional sounders ....................................................................
Conventional beacons ....................................................................
19
20
22
22
23
24
25
26
EXTINGUISHING SYSTEM
21
SPECIALS DETECTORS
Beam detector .................................................................................
Optical beam detectors ..................................................................
High sensitivity detectors ...............................................................
High sensitivity accesories .............................................................
Wireless certified system ...............................................................
Duct detector ....................................................................................
Gas detectors ..................................................................................
Residential alarm system ...............................................................
Flame detectors ...............................................................................
27
28
29
29
31
33
33
34
35
ACCESORIES
Door holders ......................................................................................
Electromagnetic locks .....................................................................
Wires ..................................................................................................
Power supply units ...........................................................................
Batteries ............................................................................................
Detector testers ................................................................................
37
38
39
40
40
41
CO DETECTION
CO Control panels ............................................................................. 42
CO Control panel accessories ......................................................... 42
CO Detectors ...................................................................................... 43
Addressable
Addressable control panels
CAD-150-1-Mini
Addressable fire alarm control panel with 1 loop. Up to of 100 addresses (detectors, modules, sounders or manual call
points) with the loop. Self-search and self-diagnosis functions. 250 programmable zones, 20 alarm and fault led display
zones, 6.000 event history logs, free configuration and maintenance software, configuration via USB port, 2 supervised
sounder outputs and 2 configurable relay outputs. Graphic LCD display. Auxiliary output of 24V. ABS plastic casing for
wall mounting and even prepared to be embedded into it. Multilingual keyboard. Able to be networked up to 32 fire
control panel o repeaters via RS485 or fiber optics. Modbus output for integrations and Contact ID for connection to CMS
(optional). Full remote access of the panel if a TED-151WS card is added. CPR certificate EN54-2, EN54-4 and EN54-13.
Requires 2 BTD-1207 batteries not included. Dimensions: 430 x 268 x 109 mm
CAD-150-1
Addressable fire alarm control panel with1 loop. Up to of 250 addresses (detectors, modules, sounders or manual call
points) with the loop. Self-search and self-diagnosis functions. 250 programmable zones, 20 alarm and fault led display
zones, 6.000 event history logs, free configuration and maintenance software, configuration via USB port, 2 supervised
sounder outputs and 2 configurable relay outputs. Graphic LCD display. Auxiliary output of 24V. ABS plastic casing for
wall mounting and even prepared to be embedded into it. Multilingual keyboard. Able to be networked up to 32 fire
control panel o repeaters via RS485 or fiber optics. Modbus output for integrations and Contact ID for connection to CMS
(optional). Full remote access of the panel if a TED-151WS card is added. CPR certificate EN54-2, EN54-4 and EN54-13.
Requires 2 BTD-1207 batteries not included. Dimensions: 430 x 268 x 109 mm
CAD-150-2
Addressable fire alarm control panel with 2 loops. Up to of 500 addresses (250 addresses per loop: detectors, modules,
sounders or manual call points) with the loop. Self-search and self-diagnosis functions. 250 programmable zones, 20
alarm and fault led display zones, 6.000 event history logs, free configuration and maintenance software, configuration
via USB port, 2 supervised siren outputs and 2 configurable relay outputs. Graphic LCD display. Auxiliary output of
24V. ABS plastic casing for wall mounting and even prepared to be embedded into it. Multilingual keyboard. Able to be
networked up to 32 fire control panel o repeaters via RS485 or fiber optics. Modbus output for integrations and Contact ID
for connection to CMS (optional). Full remote access of the panel if a TED-151WS card is added. CPR certificate EN54-2,
EN54-4 and EN54-13. Requires 2 BTD-1207 batteries not included. Dimensions: 430 x 268 x 109 mm
CAD-150-4
Addressable fire alarm control panel with 4 loops. Up to of 1.000 addresses (250 addresses per loop: detectors,
modules, sounders or manual call points). Self-search and self-diagnosis functions. 250 programmable zones, 6.000
event history logs, free configuration and maintenance software, configuration via USB port, 2 supervised siren outputs
and 2 configurable relay outputs. Graphic LCD display. Auxiliary output of 24V. Metal box. Multilingual keyboard. Able to be
networked up to 32 fire control panel o repeaters via RS485 or fiber optics. Modbus output for integrations and Contact ID
for connection to CMS (optional). Full remote access of the panel if a TED-151WS card is added. CPR certificate EN54-2,
EN54-4 and EN54-13. Requires 2 BTD-1207 batteries not included. Dimensions: 430 x 360 x 120 mm
CAD-150-8
Addressable fire alarm control panel with 4 loops expandable up to 8 loops, by means of 2 additional loops cards
(TBUD-150). Up to of 2,000 addresses (250 free addresses per loop: detectors, modules, sounders or call points). Autosearch function, 250 programmable zones, 40 alarm and fault display zones via leds, 6.000 event history logs, free
configuration and maintenance software, USB port configuration, 2 supervised siren outputs and 2 free relay outputs.
Voltage configurable on board. Graphic LCD display. Auxiliary output of 24V. Able to be networked up to 32 fire control
panel o repeaters via RS485 or fiber optics. Modbus connection and to alarm central station (optional). Full remote
access of the panel if a TED-151WS card is added. Metal box, multilingual keyboard. CPR certificate EN54-2, EN54-4 and
EN54-13. Requires 2 BT1218 batteries not included. Dimensions: 525 x 450 x 120 mm
CAD-150-8PLUS
Addressable fire alarm control panel with 4 loops expandable up to 8 loops, by means of 2 additional loops card
(TBUD-150). Up to of 2,000 addresses (250 free addresses per loop: detectors, modules, sounders or call points). Autosearch function, 250 programmable zones, 40 alarm and fault display zones via leds, 6.000 event history logs, free
configuration and maintenance software, USB port configuration, 2 supervised siren outputs and 2 free relay outputs.
Voltage configurable on board. Graphic LCD display. Auxiliary output of 24V. Able to be networked up to 32 fire control
panel o repeaters via RS485 or fiber optics. Modbus connection and to alarm central station (optional). Full remote
access of the panel if a TED-151WS card is added. Metal box, multilingual keyboard. CPR certificate EN54-2, EN54-4 and
EN54-13. Requires 2 BT1224 batteries not included. Dimensions: 525 x 450 x 200 mm
6
Addressable fire alarm control panel with 4 loops in rack format. Up to of 1.000 addresses (250 addresses per loop:
detectors, modules, sounders or call points). Self-search and self-diagnosis function. 250 programmable zones, 6,000
event history log, free configuration and maintenance software, configuration via USB port, 2 supervised siren outputs
and 2 configurable relay outputs. Graphic LCD display. Auxiliary output of 24V. Metal box. Multilingual keyboard. Able to be
networked up to 32 fire control panel o repeaters via RS485 or fiber optics. Modbus output for integrations and Contact ID
for connection to CMS (optional). Full remote access of the panel if a TED-151WS card is added. CPR certificate EN54-2,
EN54-4 and EN54-13. Requires 2 BTD-1207 batteries not included. Dimensions: 430 x 360 x 120 mm.
Addressable
CAD-150-4RACK
Addressable repeaters
RAD-150
Bidirectional repeater for Detnov addressable systems. Allows the remote supervision control of a fire control panel
networked (up to 32 nodes) or standalone. It shows the same incidences reflected in the control panel. It can be added
in ring or bus networks configurations. LCD display and 4 control keys (reset, mute buzzer, mute sounders and activate
sounders). Includes RS485 communication card (TRED-150). ABS plastic casing for wall mounting and even prepared
to be embedded into it. Requires 230Vac and 2 batteries BTD-1207 (not included). Dimensions: 443 x 268 x 109 mm.
RTD-150E
Graphical repeater for addressable Detnov system. Allows the visualization and graphical management of the detection
installation through a (HDMI) monitor. Accepts all picture formats (jpeg, bmp, gif, etc.). Easy and intuitive use. It is
recommended to use a touch screen interface. HDMI output and Ethernet connection for the connection of a repeaters
network, using the existing Ethernet and Wi-Fi infrastructure. One of the repeaters must be connected to the fire system
by means of a TMB-151 card. Power supply included.
RTD-150T
Graphical 10” tablet repeater for addressable Detnov system. It allows the visualization and graphic management
of the fire detection facility through maps and pictures. Easy and intuitive use. Accepts all picture formats (jpeg, bmp,
gif, etc.). Wi-Fi output available for networking several graphical repeaters RTD-150E. One of the repeaters must be
connected to the fire system by means of a TMB-151 card. Dimensions: 296 x 195 x 32 mm. Power supply included.
RTD-150W
Wireless graphical 7” tablet repeater for addressable Detnov system. It allows the visualization and graphic
management of the fire detection facility through maps and pictures. Easy and intuitive use. Accepts all picture formats
(jpeg, bmp, gif, etc.). Wi-Fi connection is required and at least one RTD-150E or RTD-150 acting as a master device.
Dimensions: 188 x 113 x 10 mm. Power supply included.
Voice evacuation system
CAD-150-EVAC
Integrated voice evacuation system including of addressable fire control panel CAD-150-4 and NEO voice evacuation
control unit EN54-2, EN54-4, EN 54-16 and EN 60849.
7
Addressable
Addressable control panel accessories
TBUD-150
2 loops microprocessor expansion card (500 addresses). 250 addresses per loop (detectors, modules, sounders and
manual call points). To be used in CAD-150-8 and CAD-150-8PLUS.
TRED-150
Network connection RS485 communication card for addressable CAD-150 panels. Allows ring or bus installation
networking. Up to 32 nodes. Includes electric isolation circuit between nodes. Printer output via serial connection. 1.000
meters maximum distance between nodes.
TMB-151
RS485 communication with Modbus output card, for networking addressable CAD-150 panels or repeaters. Includes
Modbus protocol output for integrations with third parties. Network system installation in ring or bus. Includes electric
isolation circuit between nodes. 1.000 meters maximum distance between nodes.
TMBFI-151
Fiber optic communication with Modbus output card, for networking addressable CAD-150 panels or repeaters.
Includes Modbus protocol output for integrations with third parties. Network system installation in ring or bus. It
incorporates electric isolation circuit between nodes. Allows mixed RS485 and fiber optic connection.
TETD-150
Ethernet communication card for CAD-150 addressable control panels range. Connection gateway required for our
SGD-150 graphic software.
TED-151-WS
Embedded Webserver TCP / IP communication card for our conventional CCD-100 or addressable CAD-150 control
panel ranges. Remote monitoring and control of the fire alarm control panel in which it is built in. Automatic sending of
emails.
TCD-106-A
CMS (Central Monitoring Station) communication card via IP / GPRS, Contact ID protocol to transmit alarms and
faults. Compatible with our addressable CAD-150 fire panel range. RS485 connection between the fire panel and this
card. 24 V power supply not included.
CAJ007
Mounting Box for TCD-106 transmitter
8
Hand-held programmer for 200A addressable detectors range and 400 series devices (modules, call points and
sounders). Allows the display of the device address, analogue value of the detectors and consecutive address programming
if cuished. Includes 3 9V batteries.
SCD-150
Addressable
PGD-200
CAD-150 series addressable control panels range configuration, commissioning and maintenance software. PC
connection via USB cable.
SGD-150
CAD-150 series addressable control panels and CMD-500 monoxide control panels graphical software. Control,
supervision and management of the fire alarm system and carbon monoxide systems installation in graphical environment.
CUSB-150
CAD-150 range standard USB configuration cable for PC connection.
9
Addressable
Addressable detectors
DOD-220A
Addressable optical smoke detector, with dirt compensation and algorithm verification. Led status indicator anti-theft
system and output for remote pilot indicator PAD-10 or buzzer BUD-200. White color. Non polarity installation. Requires
connection base Z-200 or Z-200-H. CPR certificate EN54-7. Dimensions: 100 x 40 mm.
DOTD-230A
Addressable optical & heat detector, with dirt compensation and algorithm verification. Led status indicator anti-theft
system and output for remote pilot indicator PAD-10 or buzzer BUD-200. White color. Non polarity installation. Requires
connection base Z-200 or Z-200-H. CPR certificates EN54-5 and EN54-7. Dimensions: 100 x 40 mm.
DTD-210A
Addressable heat (58°C fixed temperature and thermal rate of rise) detector, with algorithm verification. Led status
indicator and output for remote pilot or buzzer, anti-theft system. White color. Allows installation without polarity. Requires
base Z-200 or Z-200-H. CPR certificate EN54-5. Dimensions: 100 x 40 mm.
DTD-215A
Addressable high temperature detector (fixed at 78ºC), with algorithm verification. Led status indicator and output for
remote pilot or buzzer, anti-theft system. White color. Allows installation without polarity. Requires connection base Z-200
or Z-200-H. CPR certificate EN54-5. Dimensions: 100 x 40 mm.
Addressable detectors with built-in isolator
DOD-220A-I
Addressable optical smoke detector with built-in isolator, with dirt compensation and algorithm verification. Led
status indicator anti-theft system and output for remote pilot indicator PAD-10 or buzzer BUD-200. White color. Requires
connection base Z-200 or Z-200-H. CPR certificate EN54-7 and EN54-17. Dimensions: 100 x 40 mm.
DOTD-230A-I
Addressable optical & heat detector with built-in isolator, with dirt compensation and algorithm verification. Led
status indicator anti-theft system and output for remote pilot indicator PAD-10 or buzzer BUD-200. White color. Requires
connection base Z-200 or Z-200-H. CPR certificates EN54-5, EN54-7 and EN54-17. Dimensions: 100 x 40 mm.
DTD-210A-I
Addressable heat (58°C fixed temperature and thermal rate of rise) detector with built-in isolator, with algorithm
verification. Led status indicator and output for remote pilot or buzzer, anti-theft system. White color. Requires base Z-200
or Z-200-H. CPR certificate EN54-5 and EN54-17. Dimensions: 100 x 40 mm.
DTD-215A-I
Addressable high temperature detector (fixed at 78ºC) with built-in isolator, with algorithm verification. Led status
indicator and output for remote pilot or buzzer, anti-theft system. White color. Requires connection base Z-200 or Z-200-H.
CPR certificate EN54-5 and EN54-17. Dimensions: 100 x 40 mm
10
DOD-220A-B
Addressable optical smoke detector, with dirt compensation and algorithm verification. Led status indicator anti-theft
system and output for remote pilot indicator PAD-10 or buzzer BUD-200. Black color. Non polarity installation. Requires
connection base Z-200 or Z-200-H. CPR certificate EN54-7. Dimensions: 100 x 40 mm.
Addressable
Addressable detectors (black)
DOTD-230A-B
Addressable optical & heat detector, with dirt compensation and algorithm verification. Led status indicator anti-theft
system and output for remote pilot indicator PAD-10 or buzzer BUD-200. Black color. Non polarity installation. Requires
connection base Z-200 or Z-200-H. CPR certificates EN54-5 and EN54-7. Dimensions: 100 x 40 mm.
DTD-210A-B
Addressable heat (58°C fixed temperature and thermal rate of rise) detector, with algorithm verification. Led status
indicator and output for remote pilot or buzzer, anti-theft system. Black color. Allows installation without polarity. Requires
base Z-200 or Z-200-H. CPR certificate EN54-5. Dimensions: 100 x 40 mm.
DTD-215A-B
Addressable high temperature detector (fixed at 78ºC), with algorithm verification. Led status indicator and output for
remote pilot or buzzer, anti-theft system. Black color. Allows installation without polarity. Requires connection base Z-200
or Z-200-H. CPR certificate EN54-5. Dimensions: 100 x 40 mm.
11
Addressable
Addressable detector accessories
Z-200
Connection base for 200 and 200A series detectors. It has an anti-theft detector system. Stainless steel contacts. White
color. Dimensions: 5 x 100 mm.
Z-200-H
Deep connection base for 200 and 200A series detectors. It has an anti-theft detector system. Stainless steel contacts.
Ceiling mounted with conduit entris for standars 20mm conduit. White color. Dimensions: 43 x 100 mm.
STD-200
Euro-mounting base for Z-200 connection base. It allows the connection base to be ceiling mounted with conduit entris
for standars 20mm conduit. White color.
MAD-492
Isolator base for 200A series addressable detectors. It has detector anti-theft system, stainless metal contacts. White
color. Dimensions: 5x100 mm.
Z-200-B
Connection base for 200-B and 200A-B series detectors. It has an anti-theft detector system. Stainless steel contacts.
Black color. Dimensions: 5 x 100 mm.
Z-200-B-H
Deep connection base for 200-B and 200A-B series detectors. It has an anti-theft detector system. Stainless steel
contacts. Ceiling mounted with conduit entris for standars 20mm conduit. Black color. Dimensions: 43 x 100 mm.
STD-200-B
Euro-mounting base for Z-200-B connection base. It allows the connection base to be ceiling mounted with conduit
entris for standars 20mm conduit. Black color.
PAD-10
Remote indicator for direct connection to 200 and 200A series detectors, installed in enclosed or concealed
enclosures. 5mA very low consumption. Dimensions: 80x80x27mm.
BUD-200
Buzzer for direct connection to addressable detectors series 200A. Very low power consumption alarm and high
acoustic power.
12
MAD-450
Addressable manual call point. LED status indicator and test key. Allows installation without polarity. Red color. CPR
certificate EN54-11. Dimensions: 98 x 98 x 48 mm.
Addressable
Addressable manual call points
MAD-450-I
Addressable manual call point with built-in isolator. LED status indicator and test key. Red color. CPR certificates EN5411 and EN54-17. Dimensions: 98 x 98 x 48 mm
TBD-450
Protective plastic cover, for indoors as PCD-100, MAD-450 or MAD-450-I manual callpoints.
SMD-450
Call point recessing bezel for indoor use, PCD-100, MAD-450 or MAD-450-I. Red color.
MAD-450-IW
Addressable manual call point IP67 with built-in isolator. Suitable for outdoor applications. LED status indicator and
test key. Red color. Dimensions: 119 x 128 x 62 mm.
TBD-450-IW
Protective plastic cover for RP-GS1, PCD-100WP and MAD-450-IW outdoor manual call points.
13
Addressable
Addressable sounders and beacons
MAD-461-I
Addressable loop sounder with isolator. Low power consumption, acoustic power 87.5 dB. It takes just one address in
the loop. Color red. For indoor use. IP21. CPR certificate EN54-3 and EN54-17. Dimensions: 65x90 mm.
MAD-463-I
Addressable loop sounder with beacon and isolator. Low power consumption, acoustic power 87.5 dB. It takes just one
address in the loop. Color red. For indoor use. IP21. CPR certificate EN54-3 and EN54-17. Dimensions: 65x90 mm.
MAD-464-I
Addressable loop sounder with built-in isolator. Low power consumption. 32 tones and 3 configurable volumes (Low,
Medium, High). Acoustic power from 78.3 dBA to 104.6 dBA depending on the selected tone. It takes just one address in
the loop. Red color. IP65. Deep base. CPR certificate EN54-3 and EN54-17. Dimensions: 100 x 75 mm
MAD-465-I
Addressable loop sounder with beacon and built-in isolator. Low power consumption. 32 tones and 3 configurable
volumes (Low, Medium, High). Acoustic power 76 dBA to 117 dBA depending on the selected tone. It takes just one
address in the loop. Red color. From IP65. Deep base. CPR certificate EN54-3 and EN54-17. Dimensions: 100 x 75 mm
MAD-472
Addressable loop connection base with sounder. 200A detector compatible. CPR Certified EN54-3. Acoustic power:
80dB. Indoor use. IP30. Dimensions: 150 x 100 mm.
MAD-473
Addressable loop connection base with sounder and beacon. 200A detector compatible. CPR Certified EN54-3. Acoustic
power: 80dB. Indoor use. IP30. Dimensions: 150 x 100 mm.
MAD-467-IC
Addressable loop sounder with white beacon for ceiling installation, and built-in isolator. Beacon cover C-2.4-7. Low
power consumption. 32 tones and 3 configurable volumes (Low, Medium, High). Acoustic power 76 dBA to 117 dBA
depending on the selected tone. It takes justs one address in the loop. Red color. Indoor use. IP21C. Deep base. CPR
Certificate EN54-3, EN54-17 and EN54-23. Dimensions: 100 x 75 mm
MAD-467-IW Addressable loop sounder with white beacon for wall installation, and built-in isolator. Beacon cover W-2.4-8. Low
power consumption. 32 tones and 3 configurable volumes (Low, Medium, High). Acoustic power 76 dBA to 117 dBA
depending on the selected tone. It takes just one address in the loop. Red color. Indoor use. IP21C. Deep base. CPR
Certificate EN54-3, EN54-17 and EN54-23. Dimensions: 100 x 75 mm
MAD-469-IC
Addressable beacon of white color with red base for ceiling installation, with built-in isolator. Beacon cover C-2.4-7.
IP33C. For direct connection to the loop. Low power consumption. Indoor use. CPR Certificate EN54-23 and EN54-17.
MAD-469-IW Addressable beacon of white color with red base for wall installation, with built-in isolator. Beacon cover W-2,4-8.
IP33C. For direct connection to the loop. Low power consumption. Indoor use. CPR Certificate EN54-23 and EN54-17.
14
MAD-401
Addressable monitor module with 1 supervised technical input for device status indication providing NC or NO
contact. It takes one address in the loop. Fed directly from the loop. LED status indicator. Connection through removable
strips up to 2.5mm2 section. Possibility of being installed in DIN rail or flat to wall mounting in box BOX-400. Non polarity
installation. Consumption less than 300μA at rest. Red color. Dimensions: 100 x 82 x 23 mm. CPR certificate EN54-18.
Addressable
Addressable modules
MAD-402
Addressable monitor module with 2 supervised technical inputs for devices status signaling providing NC or NO
contact. It takes two addresses in the loop. Fed directly from the loop. LED status indicator. Connection through removable
strips up to 2.5mm2 section. Possibility of being installed in DIN rail or flat to wall mounting in box BOX-400. Consumption
less than 300μA at rest. Non polarity installation. Red color. Dimensions: 100 x 82 x 23 mm. CPR certificate EN54-18.
MAD-411
Addressable control module for 1 voltage-free relay output providing non-resettable contact C, NO, NC. It takes one
address in the loop. Fed directly from the loop. LED status indicator. Connection through removable strips up to 2.5mm2
section. Possibility of being installed in DIN rail or flat to wall mounting in box BOX-400. Consumption less than 300μA at
rest. Non polarity installation. Red color. Dimensions: 100 x 82 x 23 mm. CPR certificate EN54-18.
MAD-412
Addressable control module of 2 relay outputs free of tension that provides two contacts C, NA, NC non-resettable.
It takes two addresses in the loop. Fed directly from the loop. LED status indicator. Connection through removable strips
up to 2.5mm2 section. Possibility of being installed in DIN rail or flat to wall mounting in box BOX-400. Consumption
less than 300μA at rest. Non polarity installation. Red color. Dimensions: 100 x 82 x 23 mm. CPR certificate EN54-18.
MAD-421
Addressable monitor and control module with 1 supervised technical input for status indication of devices that
provides NC or NO contact and 1 voltage-free relay output providing non-resettable C, NO, NC contact. It takes two
addresses in the loop. Fed directly from the loop. LED status indicator. Connection through removable strips up to 2.5mm2
section. Possibility of being installed in DIN rail or flat to wall mounting in box BOX-400. Consumption less than 300μA at
rest. Non polarity installation. Red color. Dimensions: 100 x 82 x 23 mm. CPR certificate EN54-18.
MAD-422
Addressable monitor and control module with of 2 supervised technical inputs, for the devices status signaling that
provide NC or NO contact and 2 voltage-free relay outputs that provide two non-resettable C, NO, NC contacts. It
takes four addresses in the loop. Fed directly from the loop. LED status indicator. Connection through removable strips up
to 2.5mm2 section. Possibility of being installed in DIN rail or flat to wall mounting in box BOX-400. Consumption less than
300μA at rest. Non polarity installation. Red color. Dimensions: 100 x 82 x 23 mm. CPR certificate EN54-18.
15
Addressable
MAD-431
Addressable control module of 1 monitored 24V output, for the activation of optical-acoustic signaling devices or
maneuvers that require power, discriminating the fault of cut or short circuit in said line. It takes one loop address.
Requires 24 Vdc auxiliary power. LED status indicator. Connection through removable strips up to 2.5mm2 section.
Possibility of being installed in DIN rail or flat to wall mounting in box BOX-400. Consumption less than 300μA at rest.
Allows installation without polarity. Red color. Dimensions: 100 x 82 x 23 mm. CPR certificate EN54-18.
MAD-432
Addressable control module of 2 supervised 24V outputs, for the activation of optical-acoustic signaling devices or
maneuvers that require power, discriminating the fault of cut or short circuit in said line. It takes two loop addresses.
Requires 24 Vdc auxiliary power. LED status indicator. Connection through removable strips up to 2.5mm2 section.
Possibility of being installed in DIN rail or flat to wall mounting in box BOX-400. Consumption less than 300μA at rest.
Allows installation without polarity. Red color. Dimensions: 100 x 82 x 23 mm. CPR certificate EN54-18.
MAD-441
Addressable monitor module of 1 conventional zone, allows connection of up to 20 conventional detectors and / or
32 conventional manual call points. Can identify between detector alarm and push button, between the fault by cutting
or by short circuit in the zone. It takes one loop address. Requires 24 Vdc auxiliary power. LED status indicator. Connection
through removable strips up to 2.5mm2 section. Possibility of being installed in DIN rail or flat to wall mounting in box
BOX-400. Consumption less than 300μA at rest. Allows installation without polarity. Red color. Dimensions: 100 x 82 x
23 mm. CPR certificate EN54-18.
MAD-442
Addressable monitor module of 2 conventional zones, allows the connection of up to 20 conventional detectors and
/ or 32 conventional manual call points per zone. Can identify between detector alarm and push button, between the
fault by cutting or by short circuit in the zone. It takes two loop addresses. Requires 24 Vdc auxiliary power. LED status
indicator. Connection through removable strips up to 2.5mm2 section. Possibility of being installed in DIN rail or flat to
wall mounting in box BOX-400. Consumption less than 300μA at rest. Allows installation without polarity. Red color.
Dimensions: 100 x 82 x 23 mm. CPR certificate EN54-18.
MAD-481
Addressable control module of 1 relay output voltage free of 240 Vac and 5A which provides a non-resettable
contact C, NO, NC. It takes one loop address. Requires 24 Vdc auxiliary power. LED status indicator. Connection through
removable strips up to 2.5mm2 section. Possibility of being installed in DIN rail or flat to wall mounting in box BOX-400.
Consumption less than 300μA at rest. Allows installation without polarity. Red color. Dimensions: 100 x 82 x 23 mm. CPR
certificate EN54-18.
MAD-490
Addressable short-circuit protection isolating module, with status LED, which isolates the loop section between two
isolators in the event of a short-circuit in the loop. Takes no address in the loop. Direct feed from the loop. Connection
through removable strips up to 2.5mm2 section. Possibility of being installed in DIN rail or flat to wall mounting in box
BOX-400. Consumption less than 300μA at rest. Red color. Dimensions: 100 x 82 x 23 mm. CPR certificate EN54-17.
KIT-5MAD-402B
Kit of 10 technical inputs, consisting of 5 MAD-402 (2-input addressable module) and BOX-400 waterproof housing
16
MAD-401-I
Addressable monitor module with built-in isolator of 1 supervised technical input for status indication of equipment
providing NC or NO contact. It takes one loop address. Direct feed from the loop. LED status indicator. Connection
through removable strips up to 2.5mm2 section. Possibility of being installed in DIN rail or flat to wall mounting in box
BOX-400. Consumption less than 300μA at rest. Red color. Dimensions: 100 x 82 x 23 mm. CPR certificate EN54-18 and
EN54-17.
Addressable
Addressable modules with built-in isolator
MAD-402-I
Addressable monitor module with built-in isolator of 2 supervised technical inputs for status indication of equipment
providing NC or NO contact. It takes two loop addresses. Direct feed from the loop. LED status indicator. Connection
through removable strips up to 2.5mm2 section. Possibility of being installed in DIN rail or flat to wall mounting in box
BOX-400. Consumption less than 300μA at rest. Red color. Dimensions: 100 x 82 x 23 mm. CPR certificate EN54-18 and
EN54-17.
MAD-411-I
Addressable control module with built-in isolator of 1 voltage-free relay output providing non-resettable C, NO, NC
contact. It takes one loop address. Direct feed from the loop. LED status indicator. Connection through removable strips
up to 2.5mm2 section. Possibility of being installed in DIN rail or flat to wall mounting in box BOX-400. Consumption less
than 300μA at rest. Red color. Dimensions: 100 x 82 x 23 mm. CPR certificate EN54-18 and EN54-17.
MAD-412-I
Addressable control module with built-in isolator of 2 relay outputs free of voltage that provides two contacts C,
NO, NC non-resettable. It takes two loop addresses. Direct feed from the loop. LED status indicator. Connection through
removable strips up to 2.5mm2 section. Possibility of being installed in DIN rail or flat to wall mounting in box BOX-400.
Consumption less than 300μA at rest. Red color. Dimensions: 100 x 82 x 23 mm. CPR certificate EN54-18 and EN54-17.
MAD-421-I
Addressable monitor and control module with built-in isolator of 1 supervised technical input for the status signaling
of equipment that provides NC or NO contact and 1 voltage-free relay output providing non-resettable C, NO, NC
contact. It takes two loop addresses. Direct feed from the loop. LED status indicators. Connection through removable
strips up to 2.5mm2 section. Possibility of being installed in DIN rail or flat to wall mounting in box BOX-400. Consumption
less than 300μA at rest. Red color. Dimensions: 100 x 82 x 23 mm. CPR certificate EN54-18 and EN54-17.
MAD-422-I
Addressable monitor module and control with built-in isolator of 2 supervised technical inputs for the status signaling
of equipment that provide NC or NO contact and 2 voltage-free relay outputs providing two non-resettable C, NO, NC
contacts. It occupies four directions in the loop. Direct feed from the loop. LED status indicators. Connection through
removable strips up to 2.5mm2 section. Possibility of being installed in DIN rail or flat to wall mounting in box BOX-400.
Consumption less than 300μA at rest. Red color. Dimensions: 100 x 82 x 23 mm. CPR certificate EN54-18 and EN54-17.
17
Addressable
MAD-431-I
Addressable control module with built-in isolator of 1 monitored 24V output, for the activation of optical-acoustic
signaling devices or maneuvers that require power, discriminating the breakdown or short-circuit fault in said line. It
takes one loop address. Requires 24 Vdc auxiliary power. LED status indicator. Connection through removable strips up to
2.5mm2 section. Possibility of being installed in DIN rail or flat to wall mounting in box BOX-400. Consumption less than
300μA at rest. Red color. Dimensions: 100 x 82 x 23 mm. CPR certificate EN54-18 and EN54-17.
MAD-432-I
Addressable control module with built-in isolator of 2 supervised 24V outputs, for the activation of optical-acoustic
signaling devices or maneuvers requiring power, discriminating the breakdown or short-circuit fault in said line. It
takes two loop addresses. Requires 24 Vdc auxiliary power. LED status indicator. Connection through removable strips up
to 2.5mm2 section. Possibility of being installed in DIN rail or flat to wall mounting in box BOX-400. Consumption less than
300μA at rest. Red color. Dimensions: 100 x 82 x 23 mm. CPR certificate EN54-18 and EN54-17.
MAD-441-I
Addressable monitor module with built-in isolator of 1 conventional zone, allows the connection of up to 20
conventional detectors and / or 32 conventional manual call points. Can identify between detector alarm and push
button, between the fault by cutting or by short circuit in the zone. It takes one loop address. Requires 24 Vdc auxiliary
power. LED status indicator. Connection through removable strips up to 2.5mm2 section. Possibility of being installed in
DIN rail or flat to wall mounting in box BOX-400. Consumption less than 300μA at rest. Red color. Dimensions: 100 x 82
x 23 mm. CPR certificate EN54-18 and EN54-17.
MAD-442-I
Addressable monitor module with built-in isolator of 2 conventional zones, allows the connection of up to 20
conventional detectors and / or 32 conventional manual call points per zone. Can identify between detector alarm
and push button, between the fault by cutting or by short circuit in the zone. It takes two loop addresses. Requires 24 Vdc
auxiliary power. LED status indicators. Connection through removable strips up to 2.5mm2 section. Possibility of being
installed in DIN rail or flat to wall mounting in box BOX-400. Consumption less than 300μA at rest. Red color. Dimensions:
100 x 82 x 23 mm. CPR certificate EN54-18 and EN54-17.
Addressable module accessories
BOX-400
Transparent waterproof box for installation of addressable modules of the MAD-400 series. Maximum capacity of 6
modules.
18
CCD-102
Conventional fire alarm panel for 2 zones mounted on ABS plastic housing. Flush mount option. Discriminates between
detector alarm and manual call points alarm. Up to 32 detectors per zone. Possibility to connect to PC via USB for complex
programming. Integrable to addressable systems directly to the loop. It has 2 configurable supervised sounder outputs
(1A maximum consumption between the two), alarm and fault relay outputs free of voltage, auxiliary 24V output (500 mA
maximum consumption), 24V resettable output (500 mA maximum consumption) and 1 external input programmable.
TSD100: 4 supervised siren outputs, TMD-100: Modbus output for integrations, TCD: Contact ID protocol for connection
to CMS, TPLD-100: integration to addressable loop). Tele maintenance and remote control through the TED-151WS card.
Optical-acoustic indications by zones. Multilingual keyboard. CPR certificate EN54-2 ,EN54-4 and EN54-13. Dimensions:
443 x 268 x 109 mm. Requires 2 BTD-1207 batteries not included.
Conventional
Conventional control panels
CCD-104
Conventional fire alarm panel for 4 zones mounted on ABS plastic housing. Flush mount option. Discriminates between
detector alarm and manual call points alarm. Up to 32 detectors per zone. Possibility to connect to PC via USB for complex
programming. Integrable to addressable systems directly to the loop. It has two configurable supervised siren outputs
(1A maximum consumption between the two), alarm and fault relay outputs free of voltage, auxiliary 24V output (500 mA
maximum consumption), 24V resettable output (500 mA maximum consumption) and 1 external input programmable.
TSD100: 4 supervised siren outputs, TMD-100: Modbus output for integrations, TCD: Contact ID protocol for connection
to CRA, TPLD-100: integration to addressable loop). Tele maintenance and remote control through the TED-151WS card.
Optical-acoustic indications by zones. Multilingual keyboard. CPR certificate EN54-2 ,EN54-4 and EN54-13. Dimensions:
443 x 268 x 109 mm. Requires 2 BTD-1207 batteries not included.
CCD-108
Conventional fire alarm panel for 8 zones mounted on ABS plastic housing. Flush mount option. Discriminates between
detector alarm and manual call points alarm. Up to 32 detectors per zone. Possibility to connect to PC via USB for complex
programming. Integrable to addressable systems directly to the loop. It has two configurable supervised siren outputs
(1A maximum consumption between the two), alarm and fault relay outputs free of voltage, auxiliary 24V output (500 mA
maximum consumption), 24V resettable output (500 mA maximum consumption) and 1 external input programmable.
TSD100: 4 supervised siren outputs, TMD-100: Modbus output for integrations, TCD: Contact ID protocol for connection
to CRA, TPLD-100: integration to addressable loop). Tele maintenance and remote control through the TED-151WS card.
Optical-acoustic indications by zones. Multilingual keyboard. CPR certificate EN54-2 ,EN54-4 and EN54-13. Dimensions:
443 x 268 x 109 mm. Requires 2 BTD-1207 batteries not included.
CCD-112
Conventional fire alarm panel for 12 zones mounted on ABS plastic housing. Flush mount option. Discriminates between
detector alarm and manual call points alarm. Up to 32 detectors per zone. Possibility to connect to PC via USB for complex
programming. Integrable to addressable systems directly to the loop. It has two configurable supervised siren outputs
(1A maximum consumption between the two), alarm and fault relay outputs free of voltage, auxiliary 24V output (500 mA
maximum consumption), 24V resettable output (500 mA maximum consumption) and 1 external input programmable.
TSD100: 4 supervised siren outputs, TMD-100: Modbus output for integrations, TCD: Contact ID protocol for connection
to CRA, TPLD-100: integration to addressable loop). Tele maintenance and remote control through the TED-151WS card.
Optical-acoustic indications by zones. Multilingual keyboard. CPR certificate EN54-2 ,EN54-4 and EN54-13. Dimensions:
443 x 268 x 109 mm. Requires 2 BTD-1207 batteries not included.
19
Conventional
Conventional control panel accessories
TRD-100
Expansion card of 4 free voltage relay outputs for conventional CCD-100 control panels. Maximum load: 10A at 30Vdc.
Maximum 3 cards per panel. Programmable via SWD-100 software.
TSD-100
4 supervised sounder outputs card, for conventional CCD-100 control panels, allowing four independent sounder
outputs. Maximum load: 500 mA per output. Maximum 3 cards per panel. Programmable via SWD-100 software.
TMD-100
RS485 communication card for integration to a network using the Modbus protocol, for conventional CCD-100
panels. Allows remote control of the main functions of the fire panel and integrate it with third parties.
TPLD-100
Addressable loop gateway card for conventional CCD-100 and CCD-103 panels range. Allows alarms and faults
communication from the conventional control panel to the addressable loop to a CAD-150 control panel range.
TED-151-WS
Embedded Webserver TCP / IP communication card for our conventional CCD-100 or addressable CAD-150 control
panel ranges. Remote monitoring and control of the fire alarm control panel in which it is built in. Automatic sending of
emails.
TCD-106-C
CMS (Central Monitoring Station) IP / GPRS communication card, Contact ID protocol to transmit the alarm and
faults. Compatible with the conventional CCD-100 fire panel range. RS485 connection between the fire panel and this
card. 24 V supply required but not included.
CAJ007
Mounting Box for TCD-106 transmitter
CCC-100
USB configuration cable for the conventional CCD-100 range and CCD-103 extinguishing panel connection to a PC.
SWD-100
Conventional control panel CCD-100 range configuration software. PC Connection via CCC-100 cable.
20
CCD-103
Extinguishing control panel for 1 risk (3 detection zones). 1 output for the activation of the bottle and 1 output for
activating the sign, 2 inputs for monitoring the bottle, manual call point inputs: release, abort and pause, 2 sounder
outputs for the two possible states extinguishing process, configurable extinction fire delay, 3 modes of operation of
the extinguishing block: Manual, automatic and canceled, 2 inputs for monitoring the enclosure: door and ventilation.
Historical event log. Possibility to connect to PC via USB for complex programming and event download. Integrable to
addressable systems directly from the addressable loop. CPR certificates EN12094/1 and EN54-2 and EN54-4.
Dimensions: 443 x 268 x 109 mm. Requires 2 BTD-1207 batteries not included.
Extinguishing
Extinguishing system
SWD-103
Configuration software for the CCD-103 extinguishing panel. Connection to PC via CCC-100 cable.
PDD-100
Release manual call point. Yellow color. With test key, surface mount. Protective plastic cover included. Use for indoor
applications. Includes resistance of 100 Ohm -2W. Dimensions: 98 x 98 x 48 mm.
PDD-100W
Release manual call point IP67. Yellow color. With test key, surface mount. Protective plastic cover included. Use for
outdoor applications. Includes resistance of 100 Ohm -2W. Dimensions: 98 x 98 x 48 mm.
PPD-100
Abort manual call point. Color blue. With test key, surface mount. Protective plastic cover included. Indoor use. Includes
resistance of 100 Ohm -2W. Dimensions: 98 x 98 x 48 mm.
PPD-100W
Abort manual call point. Color blue. With test key, surface mount. Protective plastic cover included. Use outdoors.
Includes resistance of 100 Ohm -2W. Dimensions: 98 x 98 x 48 mm.
REXD-103
Indicator light with buzzer. 24Vdc power supply required. High brightness LED lighting. Polycarbonate case with
transparent front. White color. Included “EXTINGUISHING SYSTEM ACTIVATED” label. CPR certificate EN54-3.
21
Conventional
Conventional detectors
DOD-220
Conventional optical smoke detector with status LED indicator output for remote pilot, anti-theft system. White color.
Requires connection base Z-200 or Z-200-H. CPR certificate EN54-7. Dimensions: 100 x 40 mm
DOTD-230
Conventional optical and heat detector with status LED indicator output for remote pilot, anti-theft system. White color.
Requires connection base Z-200 or Z-200-H. CPR certificate EN54-5 and EN54-7. Dimensions: 100 x 40 mm
DTD-210
Conventional heat detector (58°C fixed temperature and 8ºC/min thermal rate of rise) with status indicator LED
remote pilot output, anti-theft system. White color. Requires connection base Z-200 or Z-200-H. CPR certificate EN54-5.
Dimensions: 100 x 40 mm
DTD-215
Conventional heat detector (fixed temperature 78ºC) with status indicator LED remote pilot output, anti-theft system.
White color. Requires connection base Z-200 or Z-200-H. CPR certificate EN54-5. Dimensions: 100 x 40 mm
Conventional detectors (black)
DOD-220-B
Conventional optical smoke detector with status LED indicator output for remote pilot, anti-theft system. Black color.
Requires connection base Z-200-B or Z-200-B-H. CPR certificate EN54-7. Dimensions: 100 x 40 mm
DOTD-230-B
Conventional optical and thermal for smoke and temperature detection with status LED indicator output for remote
pilot, anti-theft system. Black color. Requires connection base Z-200-B or Z-200-B-H. CPR certificate EN54-5 and EN54-7.
Dimensions: 100 x 40 mm
DTD-210-B
Conventional heat detector (58°C fixed temperature and 8ºC/min thermal rate of rise) with status indicator LED and
remote pilot output, anti-theft system. Black color. Requires connection base Z-200-B or Z-200-B-H. CPR certificate EN545. Dimensions: 100 x 40 mm.
DTD-215-B
Conventional heat detector (fixed temperature 78ºC) with status indicator LED remote pilot output, anti-theft system.
Black color. Requires connection base Z-200-B or Z-200-B-H. CPR certificate EN54-5. Dimensions: 100 x 40 mm
22
Z-200
Connection base for 200 and 200A series detectors. It has an anti-theft detector system. Stainless steel contacts. White
color. Dimensions: 5 x 100 mm.
Z-200-H
Conventional
Conventional detector accessories
Deep connection base for 200 and 200A series detectors. It has an anti-theft detector system. Stainless steel contacts.
Ceiling mounted with conduit entris for standars 20mm conduit. White color. Dimensions: 43 x 100 mm.
STD-200
Euro-mounting base for Z-200 connection base. It allows the connection base to be ceiling mounted with conduit entris
for standars 20mm conduit. White color.
Z-200-R
Connection base with relay output for 200 series detectors. Detector anti-theft system available. Stainless steel
contacts. White color. Dimensions: 5 x 100 mm.
Z-200-B
Connection base for 200-B and 200A-B series detectors. It has an anti-theft detector system. Stainless steel contacts.
Black color. Dimensions: 5 x 100 mm.
Z-200-B-H
Deep connection base for 200-B and 200A-B series detectors. It has an anti-theft detector system. Stainless steel
contacts. Ceiling mounted with conduit entris for standars 20mm conduit. Black color. Dimensions: 43 x 100 mm.
STD-200-B
Euro-mounting base for Z-200-B connection base. It allows the connection base to be ceiling mounted with conduit
entris for standars 20mm conduit. Black color.
PAD-10
Remote indicator for direct connection to 200 and 200A series detectors, installed in enclosed or concealed
enclosures. 5mA very low consumption. Dimensions: 80 x 80 x 27 mm.
STI-9604
Galvanized steel cage coated with white polyester for the protection of fire detectors Series 200. It protects against
accidental or malicious blows that could damage the correct functioning of the device.
STI-9505
Galvanized steel cage coated with white polyester for the protection of fire detectors 200 series with tube inlet
viewed. Protects against accidental or malicious punctures that could damage the correct operation of the device.
23
Conventional
Conventional manual call points
PCD-100
Conventional manual call point, with test key, for surface installation. Suitable for indoor. Red color. Includes resistance
of 100 Ohm.-2W. Dimensions: 98 x 98 x 48 mm. CPR certificate EN54-11.
TBD-450
Protective plastic cover, for indoors PCD-100, MAD-450 or MAD-450-I manual call points.
SMD-450
Call point recessing bezel for indoor use, PCD-100, MAD-450 or MAD-450-I. Red color.
PCD-100WP
Conventional manual call point IP67, with test key, for surface installation. Suitable for outdoor. Red color. No
resistance of 100 Ohm included.-2W. Dimensions: 119 x 128 x 62 mm. CPR certificate EN54-11.
RP-GS1
Conventional manual call point for evacuation and emergencies. Green color, surface installation. Suitable for Indoors.
Dimensions: 98 x 98 x 48 mm.
TBD-450-IW
Plastic protective cover for RP-GS1, PCD-100WP and MAD-450-IW outdoor manual call points.
STI-13110ESP
Outdoor protector for PAD-100 or MAD-450 manual call points. Made of hard and transparent polycarbonate.
Recommended to avoid vandalism, misuse, situations of involuntary activation of the call point, dust, water and weather
indemencies. Includes a seal that seals the unit preventing the entry of dust, dirt and water. IP54. Dimensions: 101 x 126
x18 mm
24
SCD-100
Indoor alarm sounder. 32 selectable tones. Power at 24Vdc/12.5mA. IP44. Red color. Acoustic power between 87,5dB.
CPR certificate EN54-3. Dimensions: 65 x 90 mm.
Conventional
Conventional sounders
SCD-200
Indoor alarm sounder. 32 selectable tones. Power at 24Vdc / 7mA at 32mA according to tone. IP43. Red color. Acoustic
power between 95 and 100 dB according to tone. CPR certificate EN54-3. Dimensions: 85x75 mm.
SCD-210
Outdoor alarm sounder. 32 selectable tones. Power at 24Vdc / 7mA at 32mA according to tone. IP65. Red color. Acoustic
power between 95 and 100 dB according to tone. CPR certificate EN54-3. Dimensions: 100 x 75 mm.
SFD-220
Indoor alarm sounder with beacon. 32 selectable tones. Power at 24Vdc / 8mA at 36mA according to tone. IP43. Red
color. Acoustic power between 78 and 116 dB according to tone. CPR certificate EN54-3. Dimensions: 85 x 75 mm.
SFD-230
Outdoor alarm sounder with beacon. 32 selectable tones. Power at 24Vdc / 8mA at 36mA according to tone. IP65. Red
color. Acoustic power between 78 and 116 dB according to tone. CPR certificate EN54-3. Dimensions: 100 x 75 mm.
SFD-221C
Indoor alarm sounder with white beacon for ceiling installation. Flash cover C-2.4-7. IP21C, power to 24Vdc, consumption
of 25 to 40mA depending on the tone, 32 tones. Acoustic power between 78 and 98 dB. Certificate EN54-3 and EN54-23.
SFD-231C
Indoor alarm sounder with white beacon for ceiling installation with deep base. Flash cover C-2.4-7. IP33C, power to
24Vdc, consumption of 25 to 40mA depending on the tone, 32 tones. Acoustic power between 78 and 98 dB. Certificate
EN54-3 and EN54-23.
SFD-221W
Indoor alarm sounder with white beacon for wall installation. Flash cover W-2.4-8. IP21C, power to 24Vdc, consumption
of 25 to 40mA depending on the tone, 32 tones. Acoustic power between 78 and 98 dB. Certificate EN54-3 and EN54-23.
SFD-231W
Indoor alarm sounder with white beacon for wall installation with deep base. Flash cover W-2.4-8. IP33C, power to
24Vdc, consumption of 25 to 40mA depending on the tone, 32 tones. Acoustic power between 78 and 98 dB. Certificate
EN54-3 and EN54-23.
SCD-120
Alarm sounder with beacon. Power supply at 24Vdc / 200mA. Red color labeled “FIRE.” Polycarbonate housing
Dimensions: 297 x 210 x 75 mm.
25
Conventional
CAMD-100
6“ alarm bell. Low-power at 24 Vdc / 11 mA. Red color. Indoor use. Maximum acoustic power 94 dB. CPR Certificate
EN54-3.
RLI-80
Light indicator with buzzer. 24Vdc power supply. High brightness LED lighting. Polycarbonate case with transparent front.
White color. “FIRE ALARM” label included. CPR certificate EN54-3.
Conventional beacons
PED-50
Beacon of polycarbonate, red color glass and black base. 24Vdc / 35mA. Indoor or outdoor use.
PED-60
Beacon of polycarbonate, blue color glass and black base. 24Vdc / 35mA. Indoor or outdoor use.
PED-70
Beacon of polycarbonate, amber color glass and black base. 24Vdc / 35mA. Indoor or outdoor use.
PED-221C
Beacon with white color glass and red base for ceiling installation. Beacon cover C-3-8. IP21C, power to 24Vdc,
consumption of 25 to 40mA depending on the tone, 32 tones. Indoor use. Certificate EN54-23
PED-231C
Beacon with white color glass and red base for installation in ceiling with deep base. Beacon cover C-3-8. IP33C,
power to 24Vdc, consumption of 25 to 40mA depending on the tone, 32 tones. Indoor use. Certificate EN54-23
PED-221W
Beacon with white flash and red base for wall installation. Beacon cover W-2,4-8. IP21C, power to 24Vdc, consumption
of 25 to 40mA depending on the tone, 32 tones. Indoor use. Certificate EN54-23
PED-231W
Beacon with white flash and red base for wall installation with deep base. Beacon cover W-2,4-8. IP33C, power to
24Vdc, consumption of 25 to 40mA depending on the tone, 32 tones. Indoor use. Certificate EN54-23
26
DBD-DL40
Beam detector for distances over 5 metres and up to 40 meters, expandable up to 80 or 100 meters with extension
kits. Separated head detector and controller for easy access to programming. IP65 for use outdoors or indoor with extreme
environmental conditions. 24Vdc power supply. CPR certificate EN54-12. Dimensions: detector 180x155x137mm,
controller 185x120x62mm.
KBD-DL80
Special detectors
Beam detector
Mid range distance kit for beam detector DBD-DL40. Use this for distances over 40 meters and up to 80 meters.
KBD-DL100
Long range distance kit for beam detector DBD-DL40. Use this for distances over 80 meters and up to a maximum of
100 meters.
KIT-DL
Anti fog kit for beam detector DBD-DL40. Specially developed to overcome the problems of condensation, this special
kit contains a reflector and lens cover that have been treated with a special Nano technology finish that will not mist over.
REF-DL
Anti fog reflector. A single reflector with a nano technology finish, sold singularly.
SOP-DL
Adjustable wall fixing for beam detector DBD-DL40. A very high quality aluminium fully adjustable bracket that can be
accommodate both the beam head and the reflector.
STI-9861
Galvanized steel cage coated with white polyester for the protection for beam detector from accidental or malicious
blows that could misalign and / or affect the correct operation of the device. The grille is made of 9 gauge steel with
polyester coating resistant to the corrosion. Dimensions: 160 x 186 x 143 mm
STI-9862
Galvanized steel cage coated with white polyester for the protection of the control keyboard for beam detector.
27
Special detectors
Optical beam detectors
OSI-10
Linear detector (receiver) of smoke 10 degrees of vision. Detection based on the use of light at two different wavelengths.
Maximum range 150 meters with 1 standard emitter. Field of view (7 degrees horizontal and 4 degrees vertical). Maximum
of 1 emitter. Power supply at 24Vdc / 27mA. Status LEDs (alarm, fault and power). 3 levels of sensitivity (low, medium and
high). Dimensions: 198 x 130 x 96 mm.
OSI-45
Linear detector (receiver) of smoke 45 degrees of vision. Detection based on the use of light at two different wavelengths.
Maximum range 120 meters with high power emitter / 60 meters with standard emitter. Field of vision (38 degrees
horizontally and 19 degrees vertically). Maximum of 7 emitters. Power supply at 24Vdc / 27mA. Status LEDs (alarm, fault
and power). 3 levels of sensitivity (low, medium and high). Dimensions: 198 x 130 x 96 mm.
OSI-90
Linear detector (receiver) optical smoke 90 degrees of vision. Detection based on the use of light at two different
wavelengths. Maximum range 68 meters with high power emitter / 34 meters with standard emitter. Field of vision (80
degrees horizontally and 48 degrees vertical). Maximum of 7 emitters. Power supply at 24Vdc / 27mA. Status LEDs
(alarm, fault and power). 3 levels of sensitivity (low, medium and high). Dimensions: 198 x 130 x 96 mm.
OSE-SP
Linear detector (emitter). Detection based on the use of light at two different wavelengths. Maximum range according
to receiver model. Battery powered. Status LEDs (alarm, fault and power). 3 levels of sensitivity (low, medium and high).
Dimensions: 198 x 130 x 96 mm.
OSE-SPW
Linear detector (emitter). Detection based on the use of light at two different wavelengths. Maximum range according to
receiver model. Power supply at 24Vdc / 31mA. Status LEDs (alarm, fault and power). 3 levels of sensitivity (low, medium
and high). Dimensions: 198 x 130 x 96 mm.
OSE-HPW
Linear high-power detector (emitter). Detection based on the use of light at two different wavelengths. Maximum range
according to receiver model. Power supply at 24Vdc / 31mA. Status LEDs (alarm, fault and power). 3 levels of sensitivity
(low, medium and high). Dimensions: 198 x 130 x 96 mm.
OSID-INST
Kit Installation for the OSI series equipment. Includes laser, cable, manual, lens cleaner and test equipment.
STI-9845
Galvanized steel cage coated with white polyester for the protection of linear OSI smoke detectors from accidental or
malicious blows that could misalign and / or affect the proper functioning of the device. The grille is made of 9 gauge
steel with a resistant polyester coating to corrosion Dimensions: 234 x 167 x 104 mm
28
ILS1
High sensitivity smoke detector with analysis chamber with 1 detector for early detection. Pipe up to 100 meters in
length. Supervised airflow. IP50 housing. Dimensions: 254x180x165mm. 24 Vdc/460mA. Interchangeable filter. CPR
certificate EN54-20.
Special detectors
High sensitivity detectors
ILS2
High sensitivity smoke detector with analysis chamber with 2 detectors for early detection. Pipe up to 100 meters in
length. Supervised airflow. IP50 housing. Dimensions: 254x180x165mm. 24 Vdc / 460mA. Interchangeable filter. CPR
certificate EN54-20.
IFT-PT
High sensitivity laser detector. Dynamic range from 0.005% to 20% darkening per meter. Two inputs for two pipes
(25 mm outside) of 100 meters in length, for a detection zone. Four programmable alarm levels (alert, action and 2 of
fire) with their corresponding relays free of tension to carry out the necessary maneuvers. 24Vdc/1A. It has Ethernet
connection for the configuration by web. CPR certificate EN54-20.
High sensitivity accesories
VSP-850
Filter holder + filter for laser suction systems. Installed in pipe line for easy maintenance in dirty areas.
02-FL53
Filter for IFT-PT series, pack 10 units.
SAD-T25
25 mm pipe. 3 meters length. Red color.
SAD-U25
Straight connection for 25 mm pipes. Red color.
SAD-UR25
25 mm direct connection with thread. Red color.
SAD-C90
90 degree elbow for 25mm pipe. Red color.
SAD-C45
45 degree elbow for 25mm pipe. Red color.
29
Special detectors
SAD-UT25
T-joint for 25 mm pipes. Red color.
SAD-TF25
End cap of 25 mm pipe. Red color.
SAD-A25
25mm clamp. Red color.
SAD-BC25
Capillary bifurcation for 8 mm. For 25 mm pipe. Red color.
SAD-TC25
Capillary tube of 8 mm, 100 meters in length.
SAD-PMP25
Flat sampling point.
SAD-PMC25
Conical sampling point.
30
SGCWE
Wireless transmitter / receiver module for conventional systems. It allows to integrate and monitor up to 32
conventional radio entry elements in a conventional zone. It allows, in the same way, the control of conventional sirens
via addition, through the use of a supervised control input from the conventional control panel. Certified EN54-25.
Configurable by PC. Range up to 200 meters, allowing a range of up to 3 kilometers with the use of radio frequency
amplifiers. Power to 24 V, external to the conventional zone. Consumption: 60 mA. IP51. Dimensions: 120 x 160 x 51 mm.
Working frequency 868MHz.
Special detectors
Wireless certified system
SGWE
Wireless receiver amplifier module for conventional systems. It allows the integration and monitoring of up to 32
conventional radio input elements, acting as an expander of the SGCWE transmitter module. It also allows the control of
conventional sirens via radio, by using a supervised control input from the conventional control panel. Certified EN5425. Working frequency 868MHz. Configurable by PC. Range up to 200 meters, allowing a range of up to 3 kilometers
with the use of radio frequency amplifiers. Power to 24 V, external to the conventional zone. Consumption: 60 mA. IP51.
Dimensions: 120 x 160 x 51 mm.
SG100
Wireless conventional optical detector. Certified EN54-7 and EN54-25. Optical detection camera composed by light
reflection. Equipped with a double lithium battery that guarantees the operation of the detector for approximately 5 years,
which is fully supervised. Double led alarm indicator. Sensitivity selectable from SGCWE software (Level 1 - Sensitivity 2%
osc / m). Mounted on ABS plastic housing measures Ø110 x 65 mm. Working frequency 868MHz.
SGD200
Wireless conventional optical / thermal detector. Certified EN54-5, EN54-7 and EN54-25. Composite camera for optical
detection by light reflection and high definition thermistor circuit. Thermal chamber of class A1R (thermovelocimetric at
58 ° C). Equipped with a double lithium battery that guarantees the operation of the detector for approximately 5 years,
being this, totally supervised. Double led alarm indicator. Sensitivity selectable from the software of the SGCWE module
(Level 1 - Sensitivity of 2% osc / m). Mounted on ABS plastic housing measures Ø110 x 65 mm. Working frequency
868MHz.
SG350
Wireless conventional rate of rise thermal detector. Class A1R. Certified EN54-5 and EN54-25. Composite high definition
thermistor circuit. Equipped with a double lithium battery that guarantees the operation of the detector for approximately
5 years, being this, totally supervised. Double led alarm indicator. Sensitivity selectable from the software of the SGCWE
module. Mounted on ABS plastic housing measures Ø110 x 65 mm. Working frequency 868MHz.
SGCP100
Wireless manual call point for indoor applications. Certified EN54-11 and EN54-25. Equipped with double lithium
battery that guarantees the operation of the pushbutton for approximately 5 years, being this, totally supervised. Equipped
with alarm LED. Supplied with integrated surface base, plastic element and reset or test key. Degree of protection IP54.
Red color. Dimensions: 87 x 87 x 58 mm. Working frequency 868MHz.
SGMI200
Wireless input module for indoor applications. Certified EN54-25. Equipped with a double lithium battery that guarantees
the operation of the module for approximately 5 years, which is fully supervised. Equipped with alarm LED. Designed for
the supervision of external equipment that has an NA contact, integrating them into the system via conventional radio.
IP42. Dimensions: 87 x 87 x 39 mm. Working frequency 868MHz.
31
Special detectors
SGMC200
Wireless output module for indoor applications. Certified EN54-25. Designed to control external equipment that needs
to be activated, such as fire doors, gates, etc. It can be linked to any point in the system. Relay contact NA / NC. IP42.
Power supply: 10 V - 27 V. Consumption: 50 mA. Dimensions: 109 x 37 x 29 mm. Working frequency 868MHz.
SGMCB200
Wireless output module for outdoor applications. Certified EN54-25. Equipped with a double lithium battery that
guarantees the operation of the module for approximately 5 years, which is fully supervised. Designed to control external
equipment that needs to be activated, such as fire doors, gates, etc. It can be linked to any point in the system. Relay
contact NA / NC. The module includes an unsupervised 12 V / 24 V output with a maximum current of 40 mA / 20 mA.
IP65. Dimensions: 135 x 95 x 57 mm. Working frequency 868MHz.
SGRBS100
Wireless sounder base for conventional radio detectors SG100 series. Certified EN54-3 and EN54-25. Equipped with
double lithium battery that guarantees the operation of the siren during 5 years being this, totally supervised. It has
acoustic output up to 91 dB and 5 selectable tones. Adjustable volume. IP21. White color. Dimensions: Ø116 x 51 mm.
Working frequency 868MHz. Detector not included.
SGRBS100-AV
Wireless sounder base with optical indicator for conventional radio detectors SG100 series. Certified EN54-3 and
EN54-25. Equipped with double lithium battery that guarantees the operation of the siren during 5 years being this, totally
supervised. It has acoustic output up to 92 dB and 5 selectable tones. Adjustable volume. IP21. White color. Dimensions:
Ø142 x 66 mm. Working frequency 868MHz. Detector not included.
KIT SCW100
Wireless sounder. Certified EN54-3 and EN54-25. Equipped with a double lithium battery that guarantees the operation
of the siren for 5 years being fully supervised. It has acoustic output up to 100dB and 3 selectable tones. Adjustable
volume. Degree of protection IP21. Red color. Dimensions: 108 x 108 x 95 mm. Working frequency 868MHz.
KIT SCW100-AV
Wireless sounder with flash. Certified EN54-3 and EN54-25. Equipped with a double lithium battery that guarantees
the operation of the siren for 5 years being fully supervised. It has acoustic output up to 100dB and 3 selectable tones.
Adjustable volume. Degree of protection IP21. Red color. Dimensions: 108 x 108 x 95 mm. Working frequency 868MHz.
SGFI200-S
Pilot indicating conventional action via radio. Certified EN54-25. Equipped with double lithium battery that guarantees
the operation of the indicator for 5 years being this, totally supervised. The indicator can be programmed for activation
from one or more detectors from the SGCWE module software. IP42. Dimensions: 87 x 87 x 68 mm. Working frequency
868MHz.
SGSK200
Portable radio kit for field measurements in sturdy PVC case. It allows to carry out measurements prior to the installation
of systems via radio SGCWE in order to validate the correct operation for all the equipment and to ensure, therefore, the
overall operation of the whole set, prior to its assembly.
32
DCON-DC700
Ventilation duct detectors installation camera. Compatible with all conventional and addressable Detnov detectors.
IP54. Detector and base not included. Sampling pipe length: 600mm. Dimensions: 180 x 253 x 183 mm.
DCON-TC700
Special detectors
Duct detector
Pipe for the duct detector DCON-DC700. 1,5 meters length for big size ducts.
DCON-BM700
Mounting arm for uneven ducts for DCON-DC700 detection camera.
Gas detectors
DGD-600
Natural Gas / City Gas (methane) detector for residential use. 24 Vdc supply required. Maximum consumption: 65 mA.
IP32D. Includes alarm buzzer (85db). Standalone or able to be connected to the Detnov addressable loop. Includes alarm
relay and fault relay. Conforms to EN 50194-1. Dimensions: 89.6 x 146.5 x 39 mm. Test button. 3 status LEDs: Service,
fault and alarm. Wall mounting or DIN rail.
DGD-600-AC
Natural Gas / City Gas (methane) detector for residential use. 230 Vac supply required. Maximum consumption: 65 mA.
IP32D. Includes alarm buzzer (85db). Standalone or able to be connected to the Detnov addressable loop. Includes alarm
relay and fault relay. Conforms to EN 50194-1. Dimensions: 89.6 x 146.5 x 39 mm. Test button. 3 status LEDs: Service,
fault and alarm. Wall mounting or DIN rail.
DGD-620
Liquefied petroleum gases (butane and propane) detector for residential use. 24 Vdc supply required. Maximum
consumption: 65 mA. IP32D. Includes alarm buzzer (85db). Standalone or able to be connected to the Detnov addressable
loop. Includes alarm relay and fault relay. Conforms to EN 50194-1. Dimensions: 89.6 x 146.5 x 39 mm. Test button. 3
status LEDs: Service, fault and alarm. Wall mounting or DIN rail.
DGD-620-AC
Liquefied petroleum gases (butane and propane) detector for residential use. 230 Vac supply required. Maximum
consumption: 65 mA. IP32D. Includes alarm buzzer (85db). Standalone or able to be connected to the Detnov addressable
loop. Includes alarm relay and fault relay. Conforms to EN 50194-1. Dimensions: 89.6 x 146.5 x 39 mm. Test button. 3
status LEDs: Service, fault and alarm. Wall mounting or DIN rail.
33
Special detectors
Residential alarm system
CALYPSO-II
Smoke detector for residential use. Includes battery of high autonomy (10 years). Acoustic alarm indicator of 85dB
at 3 meters and visual indicator (red pilot). Button for test of operation. Alarm neutralization function. Automatic reset.
Acoustic low battery warning. Mounting to wall or ceiling. Mounting hardware included. Dimensions: Ø105 x 50 mm.
Certificate CPR and EN114604: 2005 + AC: 2008.
CALYPSO-II-R
Wireless smoke detector for residential use. High autonomy battery includes (10 years). Acoustic alarm indicator of
85dB at 3 meters and visual indicator (red pilot). Button for test of operation. Alarm neutralization function. Automatic
reset. Acoustic low battery warning. Mounting to wall or ceiling. Mounting hardware included. Dimensions: Ø105 x 50 mm.
Certificate CPR and EN114604: 2005 + AC: 2008. Wireless detector networks can be made up to 10 units.
ACCTA043
Wireless transmitter and receiver for Calypso-II-R detectors. Relay output for interconnection with other devices (alarm
centers, home automation, remote control unit, telephone transmitter, etc.). Dimensions: 83 x 83 x 46 mm. Red color,
indoor use. Power from 9 to 28Vdc, not included.
NEMO RADIO
Wireless manual call point. Connectable to other wireless residential devices. Power supply: 1 battery 6LR 9 V. Autonomy
5 years. Dimensions: 240 x 125 x 65 mm
IROISE T4P+R
Wireless alarm device via radio, emits acoustic and visual alarm signals when the button is pressed. Connectable to
other devices IROISE T4P + R, maximum 10. Power supply: 1 6LR 9V battery. Autonomy 5 years. Dimensions: 240 x 125
x 65 mm.
ACC0010
Wireless sounder with flash for residential use. Compatible with Calypso-II-R detectors. Acoustic power 90dB. IP 40. Low
battery acoustic warning. Power: 2 LR6 9V batteries (included). Autonomy 300 warnings or 10 years at rest. Certifications
EN50130-4: 2011 and EN61000-6-3: 2007 + A1: 2011. Dimensions: 140 x 120 x 80 mm
ACC0014
Wireless vibratory alert device, in case of emergency. Designed for the hearing impaired, it is placed under the pillow
and with vibration awakens the person when there is an alarm. Compatible with Calypso-II-R detectors. Autonomy: 300
cycles of vibration or 10 years at rest. Power: 2 AA 1.5V batteries, Dimensions: Ø 95 mm x H 35 mm.
ASL0015
Wireless activation test device of Calypso-II-R, ACC0014, sounder ACC0015. Power: 1 lithium battery 3V, Autonomy:
10 years. Battery fault warning. Dimensions: 48 x 153 x 82 mm
34
DLL-IR2
IR² flame detector (double infrared) Certified EN54-10. 90 degree detection cone and detection distance up to 45
meters Includes selectable outputs: Dry contact relay output or 4- 20 mA Programmable sensitivity Includes filters and
microprocessor analysis to eliminate false alarms Infrared spectral response: 0.75 to 2.7 µm Power supply 14 - 30 V.
Consumption: 28 mA Housing with IP65 degree of protection Zinc Alloy Dimensions: 142 x 108 x 82 mm.
Special detectors
Flame detectors
DLL-IR2IS
IR² flame detector (double infrared) for intrinsic safety applications. Certified EN54-10. Rated ATEX Ex II 1 G, Cenelec
/ IEC Ga Ex d IIC T4, for zones 0, 1 or 2. 90 degree detection cone and detection distance up to 45 meters. Incorporates
selectable outputs: Relay output via dry contact or 4-20 mA output. Programmable sensitivity. Incorporates filters and
microprocessor analysis to eliminate false alarms. Spectral response in the infrared: 0.75 to 2.7 µm. Power supply 14 - 30
V. Consumption: 28 mA. Housing with IP65 degree of Zinc alloy. Dimensions: 142 x 108 x 82 mm.
DLL-IR2EX
IR² flame detector (double infrared) for intrinsically safe applications with flameproof IP66 cover. Certified EN54-10.
Rated ATEX II 2 G D, Cenelec / IEC Ex d IIC T4 Gb and Ex IIIC T135ºC Db IP66 A21, for zones 1, 2, 21 or 22. Cone 90 degree
detection and detection distance up to 45 meters. Incorporates selectable outputs: Relay output via dry contact or 4-20
mA output. Programmable sensitivity. Incorporates filters and microprocessor analysis to eliminate false alarms. Spectral
response in the infrared: 0.75 to 2.7 µm. Power supply 14 - 30 V. Consumption: 28 mA. Housing with IP66 degree of fireresistant aluminum. Dimensions: 150 x 146 x 110 mm.
DLL-IR3
IR³ flame detector (triple infrared) Designed, manufactured and certified according to EN54-10 90 degree detection cone
and sensing distance up to 45 meters Includes selectable outputs: Dry contact relay output or 4- 20 mA Programmable
sensitivity Includes filters and microprocessor analysis to eliminate false alarms Infrared spectral response: 0.75 to 2.7
µm Power supply 14 - 30 V. Consumption: 28 mA Housing with IP65 Zinc Alloy Dimensions: 142 x 108 x 82 mm.
DLL-IR3IS
IR³ (triple infrared) flame detector for intrinsic safety applications. Certified EN54-10. Rated ATEX Ex II 1 G, Cenelec /
IEC Ga Ex d IIC T4, for zones 0, 1 or 2. 90 degree detection cone and detection distance up to 45 meters. Incorporates
selectable outputs: Relay output via dry contact or 4-20 mA output. Programmable sensitivity. Incorporates filters and
microprocessor analysis to eliminate false alarms. Spectral response in the infrared: 0.75 to 2.7 µm. Power supply 14 - 30
V. Consumption: 28 mA. Housing IP65 of Zinc alloy. Dimensions: 142 x 108 x 82 mm.
DLL-IR3EX
IR³ (triple infrared) flame detector for intrinsically safe applications with flameproof IP66 cover. Designed,
manufactured and certified according to EN54-10. Rated ATEX II 2 G D, Cenelec / IEC Ex d IIC T4 Gb and Ex IIIC T135ºC
Db IP66 A21, for zones 1, 2, 21 or 22. Cone 90 degree detection and detection distance up to 45 meters. Incorporates
selectable outputs: Relay output via dry contact or 4-20 mA output. Programmable sensitivity. Incorporates filters and
microprocessor analysis to eliminate false alarms. Spectral response in the infrared: 0.75 to 2.7 µm. Power supply 14 - 30
V. Consumption: 28 mA. Housing IP66 of fire-resistant aluminum. Dimensions: 150 x 146 x 110 mm.
35
Special detectors
DLL-UVIR
UV / IR² flame detector (combined: ultraviolet and double infrared) Certified EN54-10. 90 degree detection cone and
sensing distance up to 45 meters Consists of selectable outputs: Dry contact or 4-20 mA output Programmable sensitivity
Built-in filters and microprocessor analysis for false alarm suppression Infrared spectral response from 1 to 2.7 µm and
ultraviolet from 185 to 260 nm Power supply 14 - 30 V. Consumption: 28 mA Housing with IP65 degree of zinc alloy
Dimensions: 142 x 108 x 82 mm.
DLL-UVIREX
UV / IR² flame detector (combined: ultraviolet and double infrared) for intrinsically safe applications with flameproof
IP66 housing. Certified EN54-10. Rated ATEX II 2 G D, Cenelec / IEC Ex d IIC T6, for zones 1, 2, 21 or 22. Cone 90
degree detection and detection distance up to 45 meters. Incorporates selectable outputs: Relay output via dry contact
or 4-20 mA output. Programmable sensitivity. Incorporates filters and microprocessor analysis to eliminate false alarms.
Spectral response in the infrared from 1 to 2.7 µm and in the ultraviolet from 185 to 260 nm. Power supply 14 - 30 V.
Consumption: 28 mA. Housing with IP66 degree of fire-resistant aluminum. Dimensions: 150 x 146 x 110 mm.
DLL-TESTER
Test unit for checking the range of Talentum flame detectors (UV, UV / IR, IR / IR², IR³, IR², IR). This test unit is
designed to generate a wide range of optical output signals. Portable equipment with rechargeable NiCd battery Selection
of the desired optical output type (constant illumination, flashing, flame-like flicker) The time between tests is 30 seconds
Range of 3 meters Allows testing in Intrinsically safe areas (see the manual for this application).
36
RED-100
Door holders for surface mounting with manual release button. Retention force: 400N. Power supply: 24Vdc / 67mA.
Magnet IP54, retainer IP42. Supplied with retaining plate with ball joint. Reverse polarity protection. Dimensions:
110x85x38 mm.
Accessories
Door Holders
RED-110
Door holders for surface mounting. Retention force: 400N. Power supply: 24Vdc / 67mA. Magnet IP54, retainer IP42.
Supplied with retaining plate with ball joint. Reverse polarity protection. Dimensions: 55x55x33 mm.
RED-120
Door holders for flush mount. Retention force: 400N. Power supply: 24Vdc / 67mA. Magnet IP54, door holders IP42.
Supplied with retaining plate with ball joint. Reverse polarity protection. Dimensions: 85x85x35 mm.
RED-130
Door holders for wall mounting with integrated manual release button. Retention force: 400N. Power supply: 24Vdc
/ 67mA. Magnet IP54, door holders IP42. Supplied with retaining plate with ball joint. Reverse polarity protection.
Dimensions: 70x70x65 mm.
RED-140
Door holders for floor mount with integrated manual release button. Retention force: 400N. Power supply: 24Vdc
/ 67mA. Magnet IP54, door holders IP42. Supplied with retaining plate with ball joint. Reverse polarity protection.
Dimensions: 128x95x91 mm.
RED-150
Door holders for floor / wall mount with integrated manual release button. Support adjustable and folding 175mm
with 180º and 150mm with 90º. Retention force: 400N. Power supply: 24Vdc / 67mA. Magnet IP54, door holders IP42.
Supplied with retaining plate with ball joint. Reverse polarity protection. Dimensions: 90x80x150 mm. With 90º or
90x80x175 mm. With 180º.
SED-150
Wall or floor mount for RED-100 door holders. Length 150 mm.
SED-300
Wall or floor mount for RED-100 door holders. Length 300 mm.
37
Accessories
Electromagnetic locks
MEX-100
Electromagnetic lock of 1800N of retention force, non-monitored, for surface mounting. 12Vdc / 250mA power
supply. Dimensions: 166 x 40 x 22 mm.
MEX-400
Electromagnetic lock of 3000N of retention force, not monitored, for surface mount. Power supply 12Vdc / 270mA or
24Vdc / 180mA. Dimensions: 241 x 52 x 27 mm.
MEX-430
Electromagnetic lock of 3000N of retention force, monitored and timed (5 to 30 sec). Incorporates state led, for
surface mounting. Power supply 12Vdc / 270mA or 24Vdc / 180mA. Dimensions: 241 x 52 x 27 mm.
MEX-700
Electromagnetic lock of 6500N of retention force, non-monitored, for surface mounting. Power supply 12Vdc / 270mA
or 24Vdc / 180mA. Dimensions: 265 x 70 x 38 mm.
MEX-730
Electromagnetic lock of 6000N of force of retention, monitored and timed (5 to 30 sec). Incorporates state led, for
surface mounting. Power supply 12Vdc / 270mA or 24Vdc / 180mA. Dimensions: 265 x 70 x 38 mm.
MBAX-180
Z Mounting Bracket for MEX-100
MBAX-300
Z Mounting Bracket for MEX-400 and MEX-430
MBAX-600
Z Mounting Bracket for MEX-700 and MEX-730
MBEX-180
L-mount bracket for MEX-100
MBEX-300
L-mount bracket for MEX-400 and MEX-430
MBEX-600
L-mount bracket for MEX-700 and MEX-730
38
Glass Mounting Bracket for Series MEX-100
MHAX-300
Glass mounting bracket for MEX-400 and MEX-430 series.
Accessories
MHAX-180
Wires
CBD-K2
Fire alarm wire of 2 x 1,5 mm². Twisted halogen free. Supplied in 100 meters rolls. CPR Certificate.
CBD-K2A
Fire alarm wire with protection 2 x 1.5 mm². Twisted and shielded, very low capacity, halogen free. Supplied in rolls of
100 meters. CPR Certificate.
CBD-K4A
Fire alarm wire with protection 2 x (2 x 1,5) mm². Twisted and shielded, very low capacity, halogen free. Supplied in rolls
of 100 meters. CPR Certificate.
CBD-KRF
Fire alarm wire (fire resistant) 2 x 1,5 mm². Twisted and shielded. Fire resistant RF90. Supplied in 100 meters rolls.
CPR Certificate.
39
Accessories
Power supply Units
FAD-902
Power supply 24Vdc 2A, with battery charger, and 24V output protected by fuse. Mounted in metal box. Fault relay
energized at rest and signaling by battery condition led, mains input, fuses, and grounding. Requires 2 BT1207 batteries
not included. Dimensions: 315 x 325 x 91 mm.
FAD-905
Power supply 24Vdc 5A, with battery charger, and 24V output protected by fuse. Mounted in metal box. Fault relay
energized at rest and signaling by battery condition led, mains input, fuses and grounding. Requires 2 BT1207 batteries
not included. Dimensions: 315 x 325 x 91 mm.
TUL373
Supervised power supply 24V 3A, with battery charger. Built-in ammeter with 10 levels, indication of overload. 2
independent relay outputs (1 programmable mains absent and 1 battery failure). Opening tamper. Certified EN 54-4.
Requires 2 batteries not included. Dimensions: 373 x 310 x 175 mm.
TUL375
Supervised power supply 24V 5A, with battery charger. Built-in ammeter with 10 levels, indication of overload. 2
independent relay outputs (1 programmable mains absent and 1 battery failure). Opening tamper. Certified EN 54-4.
Requires 2 batteries not included. Dimensions: 373 x 310 x 175 mm
Batteries
BTD-1202
Sealed lead battery 12 Vdc 2.3 A.
BTD-1207
Sealed lead battery 12 Vdc 7,2 A.
BTD-1218
Sealed lead battery 12 Vdc 18 A.
BTD-1224
Sealed lead battery 12 Vdc 24 A.
40
HRD-TS800
Smoke detector tester aerosol.
Accessories
Detector testers
HRD-TS805
Carbon monoxide detector tester.
HRD-TS815
Universal extraction tool.
HRD-TS820
Wireless tester for heat detectors.
HRD-TS825
Smoke detector tester.
HRD-TS830
Telescopic fiberglass pole 4.5 meters long
HRD-TS835
Extension telescopic pole of fiberglass of 1.2 meters in length.
HRD-CB001
Transport bag testing equipment
41
Monoxide
CO Control panels
CMD-501
Carbon monoxide control panel of 1 zone expandable to 3 by module MMD509. Up to 32 detectors per module. 2-wire
installation without polarity, maximum distance of 2 km. 3 programmable level relays (extraction 1, extraction 2 and
alarm). The relays can be configured for activation with a fault. Two shooting modes, standard (by value of each detector)
or by the real average of the whole area. Test mode for the maintenance of the installation. Optional: TRMD-500 or TRMD501 card allows the control of a speed regulator connected to an engine achieving energy efficiency and reduction of
noise and vibrations. Housing made of ABS plastic, with possibility of being recessed. Dimensions: 439 x 268 x 112 mm.
Power supply at 230 Vac. Certificate UNE 23300: 1984.
CMD-502
Carbon monoxide control panel of 2 zones expandable to 3 using MMD509 module. Up to 32 detectors per module.
2-wire installation without polarity, maximum distance of 2 km. 3 programmable level relays (extraction 1, extraction
2 and alarm). The relays can be configured for activation with a fault. Two shooting modes, standard (by value of each
detector) or by the real average of the whole area. Test mode for the maintenance of the installation. Optional: TRMD500 or TRMD-501 card allows the control of a speed controller connected to an engine achieving energy efficiency and
reducing noise and vibrations. Housing made of ABS plastic, with possibility of being recessed. Dimensions: 439 x 268 x
112 mm. Power supply at 230 Vac. Certificate UNE 23300: 1984. Certified according to UNE 23300: 1984.
CMD-503
Carbon monoxide control panel of 3 zones. Up to 32 detectors per module. 2-wire installation without polarity, maximum
distance of 2 km. 3 programmable level relays (extraction 1, extraction 2 and alarm). The relays can be configured for
activation with a fault. Two shooting modes, standard (by value of each detector) or by the real average of the whole area.
Test mode for the maintenance of the installation. Optional: TRMD-500 or TRMD-501 card allows the control of a speed
regulator connected to an engine achieving energy efficiency and reduction of noise and vibrations. Housing made of ABS
plastic, with possibility of being recessed. Dimensions: 439 x 268 x 112 mm. Power supply at 230 Vac. Certificate UNE
23300: 1984.
CO Control panel accessories
MMD-509
Expansion module for CMD-500 carbon monoxide control panels. Up to 32 detectors per module. Installation with 2
wires without polarity.
TRMD-500
Expansion card for CMD-500 carbon monoxide control panels. It allows the connection of up to 3 speed regulators for
the control of the ventilation / extraction motors, obtaining optimum motor performance in addition to energy efficiency
of the installation.
TRMD-501
Expansion card for CMD-500 carbon monoxide control panels. It allows the connection of up to 3 speed regulators for
the control of the ventilation / extraction motors, obtaining optimum motor performance in addition to energy efficiency of
the installation. Includes Ethernet card for programming, remote management or remote maintenance of the installation.
42
DMD-500
Standard carbon monoxide detector with electrochemical cell with deep base included. Connection to 2 wires without
polarity. Diagnostic LED. Resolution: 1 ppm. Certificate UNE 23300: 1984. Dimensions: 77x100 mm. Ten years life time.
Monoxide
CO Detectors
DMDP-500
Compact carbon monoxide detector with electrochemical cell. Antivandal protection (wall fastening, shock resistance,
protection against water). Connection to 2 wires without polarity. Diagnostic LED. Resolution: 1 ppm. Certificate UNE
23300: 1984. Dimensions: 93 x 93 x 55 mm. Ten years life time.
RCOD-500
Light indicator with buzzer. 24Vdc power supply. High brightness LED lighting. Polycarbonate case with transparent front.
White color. Label “DO NOT ENTER EXCESS OF CO” included. CPR certificate EN54-3.
43
Notes:
44
Carrer de l’Alguer, 8, Pol. Ind. Les Salines
08830 Sant Boi de Llobregat - Barcelona (Spain)
+34 93 371 60 25
info@detnov.com
C/ La Granja, 30
28108 Alcobendas - Madrid (Spain)
+34 91 919 79 69
madrid@detnov.com
www.detnov.com