COMMERCIAL & INDUSTRIAL
UNITARY HEATING PRODUCTS
GAS
STEAM/HOT WATER
OIL
ELECTRIC
75-136.49 • MAY, 2017
MODINE COMMERCIAL & INDUSTRIAL UNIT HEATERS
Modine has always been the industry standard for comfort heating
applications. With the Modine product line, you can fulfill your unit
heater application needs with a variety of energy sources.
Natural or Propane Gas • Steam/Hot Water • Oil • Electric
Modine sales representatives are experienced specialists in the
engineering, selection and application of Modine commercial and
industrial heating and ventilating equipment. Located near you, these
representatives can help you satisfy your comfort needs and indoor-air
quality requirements. Contact your Modine product source for assistance
in providing top-quality, high-efficiency Indoor Air Solutions.
➀
➀
➀
➀
➀
➀
➀
➀ Products as noted can be found in the latest revision of 75-137, Commercial & Industrial Applied Products
2
75-136.49
UNITARY HEATING PRODUCTS - TABLE OF CONTENTS
CONTENTSPAGE
Gas-Fired Unit Heaters, Indoor Duct Furnaces, Infrared Heaters
Power-Exhausted.................................................................................. 4
Separated Combustion............................................................................ 5
Separated Combustion, High-Efficiency Condensing........................... 6-7
Blower Models....................................................................................... 8
Indoor Duct Furnaces........................................................................... 9
High-Intensity Infrared Heaters........................................................... 10
High Intensity Patio Heaters............................................................... 11
Low-Intensity Pressurized Infrared Heaters........................................ 12
Steam/Hot Water Unit Heaters
Hot Dawg H2O® - Low Profile Hot Water Unit Heater ........................ 13
Horizontal Delivery.............................................................................. 14
Vertical Delivery.................................................................................. 15
Oil-Fired Unit Heaters
Horizontal Delivery.............................................................................. 16
Electric Unit Heaters
Horizontal and Vertical Delivery.......................................................... 17
Horizontal Delivery for Hazardous Locations...................................... 18
Modine Breeze® AccuSpec Sizing and Selection Program................. 19
75-136.49
3
TAPE OUT
GAS-FIRED, POWER-EXHAUSTED
• 82% Thermal Efficiency • Horizontal or Vertical Venting • Field Convertible to Propane • 100% Shut-Off with
Continuous Retry • Commercial or Residential Applications
MODEL HD
For applications requiring a low profile unit, Modine offers the Hot Dawg® unit heater. The Hot Dawg®
may be installed in residential or commercial applications just one inch below the ceiling. The
superior quality matched with the following features makes the Hot Dawg® unit heater an easy
choice for a variety of applications:
• 82% thermal efficiency for fuel savings.
• Uses natural or propane gas (field convertible from natural to propane gas).
• Certified for residential, commercial and industrial use.
• Lightweight, easily installs 1" from ceiling with only two angle brackets (standard on 30-75,
accessory for 100-125).
• Install quickly and easily with knockouts for quick access to gas and electricity.
• The standard power exhauster allows the unit to be vented vertically or horizontally and is
designed to use the smallest diameter vent pipe possible.
• Permanently-lubricated motor for trouble-free dependability.
• Full 10-year warranty on heat exchanger.
• Available in both propeller fan and centrifugal blower configurations.
The PDP (propeller) power vented gas-fired unit heater is a product that is inexpensive to install,
easy to use, and offers excellent in-service economy. The PDP model series expands on the size
range of the HD model series providing product that is certified for commercial and industrial
applications in sizes from 150 through 400MBH.
For blower model data, see page 8.
Table 4.1 - Propeller Unit Model HD and PDP General Performance Data
Model HD Sizes
MODEL PDP
Model PDP Sizes
30
45
60
75
100
125
150
175
200
Btu/Hr Input ➀
30,000
45,000
60,000
75,000 100,000 125,000 150,000 175,000 200,000 250,000 300,000 350,000 400,000
250
300
350
400
Btu/Hr Ouput ➀
24,600
36,900
49,200
61,500
Entering Airflow (CFM)
@ 70°F
82,000 102,500 123,000 143,500 164,000 205,000 246,000 287,000 328,000
505
720
990
1160
1490
1980
2180
2550
2870
3700
4460
4870
5440
Air Temp. Rise (°F)
44
46
45
48
50
47
51
51
52
50
50
53
54
Max. Mounting
Height (Ft.) ➁
10
10
12
14
12
16
16
17
15
19
21
20
19
Heat Throw (Ft.) @
Max Mtg Ht ➁
25
27
36
38
42
56
55
59
51
67
74
70
69
The PTP features a stainless steel tubular heat exchanger as STANDARD on all units with a
10-year heat exchanger warranty, providing customers with a peace of mind. Users of the PTP will
also benefit from a design that allows quick and easy installations.
Table 4.2 - Propeller Unit Model PTP General Performance Data
Model PTP Sizes
MODEL PTP
150
175
200
250
300
350
400
Btu/Hr Input ➀
150,000
175,000
200,000
250,000
300,000
350,000
400,000
Btu/Hr Ouput ➀
123,000
143,500
164,000
205,000
246,000
287,000
328,000
Entering Airflow (CFM) @ 70°F
2140
2725
2870
3995
4545
5280
5995
Air Temp. Rise (°F)
53
48
52
47
50
50
51
Max. Mounting
Height (Ft.) ➁
15
14
15
18
19
18
21
Heat Throw (Ft.) (@
Max Mtg Ht)
51
50
53
62
69
65
74
R
atings shown are for elevations up to 2,000 Ft. For elevations above 2,000 feet, ratings should be reduced at the rate of 4%
for each 1,000 feet above sea level. (In Canada see rating plate.) Reduction of ratings requires use of a high altitude kit.
ata taken at 55°F air temperature rise. At 65°F ambient and unit fired at full-rated input. Mounting height as measured from
‚D
bottom of unit, and without deflector hoods. For units equipped with deflector hoods.
DO NOT LOCATE ANY GAS-FIRED UNIT IN AREAS WITH CHLORINATED,
HALOGENATED, OR ACIDIC VAPORS IN ATMOSPHERE.
Request Catalog 6-189 For Complete Technical Information and Specifications.
4
75-136.49
GAS-FIRED, SEPARATED COMBUSTION
• 100% Outside Air for Combustion • Sealed Compartment Protects Combination Gas Control, Ignition Control,
Manifold and Burner • Horizontal or Vertical Concentric Venting • 82% Thermal Efficiency • Direct Spark Ignition
• 100% Shut-Off with Continuous Retry • Certified for Commercial or Residential Applications
The separated combustion models HDS/HDC and PTS/BTS draw 100% of their combustion air from
outside to ensure that the unit will always have plenty of fresh, clean air to breathe. This fresh-air
supply reduces common concerns about maintenance, performance, and durability in dusty, dirty, or
humid applications. In addition, by drawing the combustion air from the outside, the overall heating
efficiency is increased. In short, the separated combustion units give you the added advantages of:
MODEL HDS
• 82% thermal efficiency for fuel savings.
• A sealed compartment protects the combination gas valve, ignition control, manifold, and burner
from the environment.
• External gas connections.
• Uses natural or propane gas (field convertible from natural to propane gas).
• Certified for residential (30-125MBH), commercial and industrial use (30-400MBH).
• Lightweight, easily installs 1" from ceiling with only two angle brackets (standard on 30-75,
accessory for 100-125).
• Install quickly and easily with knockouts for quick access to gas and electricity.
• Standard power exhaust simplifies side-wall or roof venting with small-diameter vent pipe.
• Horizontal or vertical two-pipe or concentric venting options.
• Permanently-lubricated motor for trouble-free dependability.
• Full 10-year warranty on heat exchanger.
• Available in both propeller fan and centrifugal blower configurations.
For blower model data, see page 8.
MODEL HDC
MODEL PTS
Table 5.1 - Propeller Unit Model HDS and PTS General Performance Data
Model HDS Sizes
75
Model PTS Sizes
30
45
60
100
125
150
175
200
Btu/Hr Input ➀
30,000
45,000
60,000
75,000 100,000 125,000 150,000 175,000 200,000 250,000 300,000 350,000 400,000
250
300
350
400
Btu/Hr Ouput ➀
24,600
26,900
49,200
61,500
Entering Airflow (CFM)
@ 70°F
82,000 102,500 123,000 143,500 164,000 205,000 246,000 287,000 328,000
505
720
990
1160
1490
1980
2140
2725
2870
3995
4545
5280
5995
Air Temp. Rise (°F)
44
46
45
48
50
47
53
48
52
47
50
50
51
Max. Mounting
Height (Ft.) ➁
10
10
12
14
12
16
15
14
15
18
19
18
21
Heat Throw (Ft.) @
Max Mtg Ht ➁
25
27
36
38
42
56
51
50
53
62
69
65
74
➀R
atings shown are for elevations up to 2,000 Ft. For elevations above 2,000 feet, ratings should be reduced at the rate of 4% for each 1,000 feet
above sea level. (In Canada see rating plate.) Reduction of ratings requires use of a high altitude kit.
➁D
ata taken at 55°F air temperature rise. At 65°F ambient and unit fired at full-rated input. Mounting height as measured from bottom of unit, and
without deflector hoods.
DO NOT LOCATE ANY GAS-FIRED UNIT IN AREAS WITH CHLORINATED,
HALOGENATED, OR ACIDIC VAPORS IN ATMOSPHERE.
Request Catalog 6-175 For Complete Technical Information and Specifications.
75-136.49
5
GAS-FIRED, SEPARATED COMBUSTION, HIGH-EFFICIENCY CONDENSING
• 100% Outside Air for Combustion • Sealed Compartment Protects Combination Gas Control, Ignition Control,
Manifold and Burner • Conservicore® Secondary Heat Exchanger • Horizontal or Vertical Concentric Venting
• 93% Thermal Efficiency • Direct Spark Ignition • 100% Shut-Off with Continuous Retry
MODEL PTC
MODINE
CONSERVICORE®
HEAT EXCHANGER
At 93% thermal efficiency for all model sizes, Modine’s Effinity93® condensing unit heater
features the highest efficiency available in North America for commercial and industrial,
as well as residentially certified (sizes 110 and smaller) gas-fired unit heaters. This industry
leading efficiency is a result of the coupling of our Conservicore® secondary heat
exchanger technology with our robust tubular primary heat exchanger design. The
Conservicore® technology features a secondary recuperative heat exchanger fabricated
from AL29-4C® stainless steel. This material is superior to other lower grades of stainless
steel and aluminum, resulting in outstanding ability to withstand the corrosive environment
of condensing gas fired equipment.
Available in ten model sizes with input ranges from 55,000 to 310,000 Btu/Hr, Modine offers
application flexibility unmatched in the industry. The separated combustion units draw
combustion air from outside to ensure that the unit will always have plenty of fresh, clean
air for combustion while increasing the overall heating efficiency. Venting material to be
used is PVC, an extremely cost effective vent system.
• 93% thermal efficiency for fuel savings.
• Conservicore® secondary heat exchanger made of AL29-4C® stainless steel.
•A
sealed compartment protects the combination gas valve, ignition control, manifold,
and burner from the environment.
• External gas connections.
• Uses natural or propane gas (field convertible from natural to propane gas).
• Certified for residential (55-110MBH), commercial, and industrial use.
•S
tandard Contractor Convenience Package with diagnostic LEDs, disconnect switch,
and condensate pump outlet.
• Standard power exhaust simplifies side-wall or roof venting with small-diameter pipe.
• Horizontal or vertical two-pipe or concentric venting options.
• Permanently lubricated motor for trouble-free dependability.
• Full 10-year warranty on both heat exchangers.
For blower model data, see page 8.
Table 6.1 - Propeller Unit Heater Model PTC General Performance Data
PTC Model Sizes
55 ➂
65 ➂
85 ➂
110 ➂
135
156
180
215
260
310
Btu/Hr Input ➀
55,000 65,000 85,000 110,000 135,000 155,000 180,000 215,000 260,000 310,000
Btu/Hr Output ➀
51,150 60,450 79,050 102,300 125,550 144,150 167,400 199,950 241,800 288,300
Condensate Production (Gal/Hr)
0.3
0.4
0.5
0.7
1.0
1.1
1.3
1.6
1.9
2.3
Entering Airflow (CFM) @ 70°F ➁
1097
1141
1650
1750
2160
2600
3020
3865
4585
5400
Air Temp Rise (°F)
43
49
44
54
54
51
51
48
49
49
Max. Mounting Height (Ft.) ➁
12
12
13
13
14
18
15
17
20
19
Heat Throw (Ft.) @ Max. Mtg. Ht.
43
43
48
46
51
62
53
60
70
67
➀R
atings shown are for elevations up to 2,000 Ft. For elevations above 2,000 feet, ratings should be reduced at the rate of 4% for
each 1,000 feet above sea level. (In Canada see rating plate.) Reduction of ratings requires use of a high altitude kit.
➁D
ata taken at 65°F ambient and unit fired at full-rated input. Mounting height as measured from bottom of unit, and without
deflector hoods.
➂ Also certified for residential installations.
®A
L29-4C is a Registered Trademark of Allegheny Ludlum Corporation.
®E
ffinity93®, Conservicore®, and any combination of these names either together or with other words is trademarked by
Modine Manufacturing Co.
Heaters are designed for use in heating applications with ambient temperatures between 40°F and 80°F. Heaters should not be
used in applications where the heated space temperature is below 40°F. The combination of low space and combustion air
temperatures may result in condensate freezing in the secondary heat exchanger and/or condensate drain.
DO NOT LOCATE ANY GAS-FIRED UNIT IN AREAS WITH CHLORINATED,
HALOGENATED, OR ACIDIC VAPORS IN ATMOSPHERE.
Request Catalog 5-157
6-170 For Complete Technical Information and Specifications.
6
75-136.49
GAS-FIRED, SEPARATED COMBUSTION, HIGH-EFFICIENCY CONDENSING
Figure 7.1 - U.S. Average Heat Load Hours Map
Use 3500 for Alaska and Canada.
Table 7.1 - Estimated Annual Fuel Cost Savings Using
the Effinity93 Condensing Unit Heater
Estimated Annual Savings
Against Other Equipment ➀ ➁
Gravity Vented
Design Heat Load (Btu/Hr):
Annual Heat
Load Hours
(refer to Figure 7.1)
500
1000
1500
2000
2500
3000
3500
Power Vented
120,000
280,000
120,000
280,000
$306
$611
$917
$1,223
$1,529
$1,834
$2,140
$713
$1,427
$2,140
$2,853
$3,567
$4,280
$4,993
$136
$273
$409
$546
$682
$819
$955
$318
$637
$955
$1,274
$1,592
$1,911
$2,229
➀ Based on a natural gas rate of $1.10/Therm. Actual realized savings can vary significantly
based on a number of changing factors including, but not limited to, fuel prices, climate,
building use or construction, etc.
➁ Compares 93% efficient against 65% seasonal efficient gravity vented and 78% seasonal
efficient power vented.
Table 7.2 - Effinity93 PTC260 (260,000 BTU/hr) vs.
Comparable Power-Vented Unit Heater ➀
Uses Less Natural Gas for Fewer CO2 Emissions
City
Annual
Gas Savings
Equivalent
Urban Trees Planted
Pounds of
CO2 Saved
Chicago, IL
Las Vegas, NV
Minneapolis, MN
Nashville, TN
Oklahoma City, OK
Philadelphia, PA
Portland, OR
$914
$325
$903
$555
$656
$916
$671
154 trees
58 trees
187 trees
88 trees
96 trees
118 trees
109 trees
13,261
4,945
16,099
7,350
8,278
10,131
9,328
➀S
avings are realized by comparing the Effinity93® BTU/hr output to a 78% seasonally efficient
power-vented heater. Savings were determined by applying appropriate degree days at 65
degrees indoor design temperature under full year, 24/7 operation to each state's 2012
average price/therm of gas.
DO NOT LOCATE ANY GAS-FIRED UNIT IN AREAS WITH CHLORINATED,
HALOGENATED, OR ACIDIC VAPORS IN ATMOSPHERE.
6-170 For Complete Technical Information and Specifications.
Request Catalog 5-157
75-136.49
7
GAS-FIRED, BLOWER MODELS
Blower unit heaters are designed for both heating and ventilating. All Modine gas-fired unit
heater types can be equipped with blowers, including our Hot Dawg® low-profile residential
garage heaters and the Effinity93®. In fact, the Effinity93® is the only high efficiency gas-fired
unit heater in North America with this option available.
These units can be used in a variety of ways:
• Ducting air in from adjacent spaces for ventilation.
•P
rotecting units from corrosive spaces by mounting them remotely and ducting in warm air.
•W
here quietness is important, blower fans are lower-noise and can be ducted, unlike
propeller units.
• Deflector hoods can be used in areas with higher mounting heights.
MODEL HDB
Table 8.1 - Power-Exhausted Blower Unit Model HDB and BDP General Performance Data
Model HDB Sizes
60
MODEL BDP
75
100
Model BDP Sizes
125
150
175
200
300
350
400
Btu/Hr Input ➀
60,000
75,000 100,000 125,000 150,000 175,000 200,000 250,000 300,000 350,000
400,000
Btu/Hr Ouput ➀
49,200
61,500
82,000
328,000
Entering Airflow
Range (CFM)
6351111
7941389
11402116
12352058
15872778
18523241
21163704
26464630
31755556
37046481
42336584
Outlet Velocity
(FPM)
437-726
546908
443781
488773
869
892
773
966
1026
1037
1008
Air Temp. Rise (°F)
40-70
40-70
35-65
45-75
40-70
40-70
40-70
40-70
40-70
40-70
40-70
Max. Mounting
Height (Ft.) ➁
7-13
7-16
8-19
8-17
14
15
13
16
18
19
19
Heat Throw (Ft.) @
Max Mtg Ht ➁
20-45
24-57
27-68
27-59
49
52
47
58
64
67
68
102,500 123,000 143,500 164,000 205,000 246,000 287,000
Table 8.2 - Separated Combustion Blower Unit Model HDC and BTS General Performance Data
Model HDC Sizes
MODEL BTS
250
Model BTS Sizes
60
75
100
125
150
175
200
250
300
350
400
Btu/Hr Input ➀
60,000
75,000
100,000
125,000
150,000
175,000
200,000
250,000
300,000
350,000
400,000
Btu/Hr Ouput ➀
49,200
61,500
82,000
102,500
123,000
143,500
164,000
205,000
246,000
287,000
328,000
Entering Airflow
Range (CFM)
6351111
7941389
11402116
12352058
15872778
18523241
21163704
26464630
31755556
37046481
42337407
Air Temp. Rise (°F)
40-70
40-70
35-65
45-75
40-70
40-70
40-70
40-70
40-70
40-70
40-70
Max. Mounting
Height (Ft.) ➁
7-13
7-16
8-19
8-17
9-21
8-18
9-21
10-22
11-26
11-26
13-29
Heat Throw (Ft.) @
Max Mtg Ht ➁
20-45
24-57
27-68
27-59
33-75
28-65
32-74
34-78
40-94
39-90
44-102
Table 8.3 - Separated Combusion, High-Efficiency Condensing
Blower Unit Heater Model BTC General Performance Data Model BTC Sizes
MODEL BTC
215
260
310
Btu/Hr Input ➀
215,000
260,000
310,000
288,300
Btu/Hr Output ➀
199,950
241,800
Condensate Production (Gal./Hr.)
1.6
1.9
2.3
Entering Airflow Range (CFM)
2645-4628
3198-5597
3813-6674
Air Temp. Rise (°F)
40-70
40-70
40-70
Max. Mounting Height (Ft.) ➂
9-22
11-26
11-26
Heat Throw (Ft.) @ Max. Mtg Ht
33-77
40-94
39-91
➀R
atings shown are for elevations up to 2,000 Ft. For elevations above 2,000 feet, ratings should be reduced at the rate of 4% for each 1,000 feet
above sea level. (In Canada see rating plate.) Reduction of ratings requires use of a high altitude kit.
➁D
ata taken at 55°F air temperature rise. At 65°F ambient and unit fired at full-rated input. Mounting height as measured from bottom of unit, and
without deflector hoods.
➂D
ata taken at 65°F ambient and unit fired at full-rated input. Mounting height as measured from bottom of unit, and without deflector hoods.
DO NOT LOCATE ANY GAS-FIRED UNIT IN AREAS WITH CHLORINATED,
HALOGENATED, OR ACIDIC VAPORS IN ATMOSPHERE.
Request Catalog 6-189 (HDB, BDP), 6-175 (BTS) and 6-170 (BTC)
For Complete Technical Information and Specifications.
8
75-136.49
GAS-FIRED, GRAVITY AND POWER-VENTED DUCT FURNACES
• Low Initial Cost • Applications Cover Heating and/or Make-Up Air • 75,000 to 400,000 Btu/Hr Input Capacity
• 82% Minimum Thermal Efficiency • Low Maintenance • Easy to Service
The Modine indoor duct furnace was designed for use with a building’s heating, heating/
cooling and make-up air systems. Available in 11 model sizes, in both gravity and power
vented configurations, the unit covers a wide variety of applications. They have input
ranges from 75,000 to 400,000 Btu/Hr and can operate on either natural or propane
gas. The airflow direction can be specified when ordering the unit. The duct furnace is
certified for location either upstream or downstream from cooling coils and has a drain
pan that allows connection to a condensate drain line.
Standard features include:
• C.S.A. certification.
• ETL certification.
• All units a minimum of 82% thermally efficient.
• 20 gauge aluminized steel cabinet.
• Certified to 3.0" W.C. external static pressure for high static applications.
MODEL DFG
GRAVITY VENTED
Optional features include:
• 409 stainless steel heat exchanger and burner.
• 409 stainless steel drip pan.
• Two-stage and electronic modulation controls for either natural or propane gas.
• Building management compatible gas conrols for modulation control using 0 - 10 Vdc
or 4 - 20 mA input.
• High and/or low gas pressure switches.
Table 9.1 - DFG/DFP Duct Furnace Performance Data ➀ ➁ ➂
Btu/Hr
DFG/DFP
Model Size
InputOutput
MODEL DFP
POWER VENTED
Without Air Baffle
Temperature Rise
CFM Range
Range (°F)
With Air Baffle
Temperature Rise
CFM Range
Range (°F)
75
75,000
61,500
20 - 60
926 - 2,778
20 - 100
556 - 2,778
100
100,000
82,000
20 - 60
1,235 - 3,704
20 - 100
741 - 3,704
125
125,000
102,500
20 - 60
1,543 - 4,630
20 - 100
926 - 4,630
150
150,000
123,000
20 - 60
1,852 - 5,556
20 - 100
1,111 - 5,556
175
175,000
143,500
20 - 60
2,160 - 6,481
20 - 100
1,296 - 6,481
200
200,000
164,000
20 - 60
2,469 - 7,407
20 - 100
1,481 - 7,407
225
225,000
184,500
20 - 60
2,778 - 8,333
20 - 100
1,667 - 8,333
250
250,000
205,000
20 - 60
3,086 - 9,259
20 - 100
1,852 - 9,259
300
300,000
246,000
20 - 60
3,704 - 11,111
20 - 100
2,222 - 11,111
350
350,000
287,000
20 - 60
4,321 - 12,963
23 - 100
2,593 - 11,111
400
400,000
328,000
20 - 60
4,938 - 14,815
27 - 100
2,963 - 11,111
➀ Ratings are shown for elevations up to 2,000 feet.
➁ Model DFP units approved for use in California by CEC.
➂ When high rates of CFM are used, the air distribution baffle may be removed to reduce the pressure drop through the duct furnace.
DFG is design certified by CSA for the gas heating furnace section, and ETL for the electrical controls.
DFP is design certified by ETL for both the gas heating furnace section and the electrical controls.
DO NOT LOCATE ANY GAS-FIRED UNIT IN AREAS WITH CHLORINATED,
HALOGENATED, OR ACIDIC VAPORS IN ATMOSPHERE.
Request Catalog 5-174 For Complete Technical Information and Specifications.
75-136.49
9
GAS-FIRED, HIGH-INTENSITY INFRARED UNITS
• 30,000 to 200,000 Btu/Hr Input • Simple Chain Mounting • High Heat Transfer Ceramic Tiles • Unvented
Operation • Low Installation Cost • Ideal for Spot Heating • Available in Natural or Propane Gas
Modine’s high-intensity ceramic infrared heater is approved for indoor unvented
installation. It does not utilize a fan, thus eliminating noise and draft distractions.
Gas and power connections are simple and maintenance is inexpensive, since there
are no moving parts to maintain. Available controls include Direct Spark Ignition,
Self-Generating Millivolt, and Intermittent Pilot (non-100% shut-off).
MODEL IHR
Modine’s IHR series heaters include the following features:
• Rugged aluminized steel frame.
• Exclusive ceramic burner provides maximum infrared radiation.
• Stainless steel rods increase heat temperature and efficiency.
• Highly polished aluminum reflector design.
• Direct spark or pilot ignition.
• Potted circuitry for protection in high moisture environments (DSI only).
• 5-year limited ceramic burner warranty.
• CSA Design Certified, UL-Listed, CE Certified.
Table 10.1 - IHR High-Intensity Infrared Heater Performance Data
Recommended Mounting Height (Ft.)
Radiating
Surface
(sq. in.)
Model
Size
Gas Controls ③④
Input Rating
(Btu/hr)
Standard Reflector
Parabolic Reflector
30°
30°
IRH 30
Single Stage or Millivolt
30,000
12 - 14
12 - 15
85
IRH 60
Single Stage or Millivolt
60,000
14 - 16
18 - 21
170
IHR 90
Single Stage or Millivolt
90,000
16 - 18
21 - 25
255
IHR 130
Single Stage or Millivolt
130,000
21 - 24
26 - 32
340
IHR 160
Single Stage or Millivolt
160,000
24 - 28
29 - 35
425
DO NOT LOCATE ANY GAS-FIRED UNIT IN AREAS WITH CHLORINATED,
HALOGENATED, OR ACIDIC VAPORS IN ATMOSPHERE.
Request Catalog 9-122 For Complete Technical Information and Specifications.
10
75-136.49
GAS-FIRED, HIGH-INTENSITY INFRARED UNITS
• 31,000 to 34,000 Btu/Hr Input • Simple Bracket Mounting • High Heat Transfer Ceramic Tiles • Unvented
Operation • Low Installation Cost • Available in Natural or Propane Gas
Modine’s high-intensity ceramic Patio infrared heater is approved for indoor and
outdoor residential or commercial applications. It does not utilize a fan, thus eliminating
noise and draft distractions. Gas and power connections are simple and maintenance
is inexpensive, since there are no moving parts to maintain. Potted (Water Resistant)
24 V circuitry.
MODEL OHP
Modine’s OHP series heaters include the following features:
• Rugged aluminized steel frame.
• ETL Design Certified to the latest edition of the ANSI Z83.26 Standard.
• Decorative stainless steel windscreen eggcrate grille.
• Wind and rain protected design.
• Reliable direct spark ignition.
• Potted (water resistant) 24V circuitry.
• Black coated aluminized steel or brushed stainless steel housing.
Table 11.1 - OHP High-Intensity Infrared Heater Performance Data
Model
Size
Housing
BTU/Hr Input
Ship Weight
Recommended
Mounting Heights ①
Approx. Area
Control
Voltage
OHP 31
430 SS
31,000
59 lbs
8.0’ to 12.0’
8’ x 8’
24 vac
OHP 34
430 SS
34,000
59 lbs
8.5’ to 13.0’
9’ x 9’
24 vac
Request Catalog 5-157 For Complete Technical Information and Specifications.
75-136.49
11
GAS-FIRED, LOW-INTENSITY INFRARED UNITS
• Pressurized Type, Low-Intensity Heater • 50,000 to 200,000 Btu/Hr Input • 20 to 70 Foot System Lengths
• Straight and U-Shaped Configurations • Simple Chain Mounting • Designed for Indoor or Outdoor, Vented or
Unvented, Commercial and Industrial Installation • Available in Natural or Propane Gas
Modine’s single-burner positive pressure infrared heater is approved for vented or
unvented commercial and industrial applications. A water-resistant control compartment
provides weatherproof protection and allows either indoor or outdoor installation.
MODEL IPT
Modine’s low-intensity IPT series heaters include the following features:
•H
eat-treated 16 gauge aluminized steel heat exchanger provides enhanced corrosion
resistance and radiant heat transfer.
• Durable 16 gauge aluminized steel combustion chamber.
• Blocked intake/exhaust shut-off switch.
•C
ontrols located in enclosed, water-resistant compartment for indoor or outdoor
installation.
• 180° rotatable gas valve, accessible from either side of burner box.
• Durable polyester powder paint maintains life-long appearance.
• Side access panels for servicing either side of the burner box.
• Improved serviceability with sight window for flame viewing, indicator lights for
combustion blower operation and a removable cover.
• Thermal efficiencies of up to 80% maximize fuel savings
Table 12.1 - IPT Low-Intensity Infrared Heater Performance Data
Model Size
Btu/Hr Input
System Lengths
(Ft.)
Recommended Mounting
Height (Ft.)
IPT 50
50,000
20, 30
10 - 12
IPT 60
60,000
20, 30, 40
10 - 12
IPT 75
75,000
20, 30, 40
12 - 14
IPT 100
100,000
30, 40, 50 ➀
12 - 14
IPT 125
125,000
40, 50, 60
15 - 22
IPT 150
150,000
50, 60
15 - 25
IPT 175
175,000
50, 60, 70
18 - 28
IPT 200
200,000
50, 60, 70
20 - 30
➀ Consult factory for propane operation at 50 Ft. system length.
DO NOT LOCATE ANY GAS-FIRED UNIT IN AREAS WITH CHLORINATED,
HALOGENATED, OR ACIDIC VAPORS IN ATMOSPHERE.
Request Catalog 9-117
5-157 For Complete Technical Information and Specifications.
12
75-136.49
HOT DAWG H2O® - LOW PROFILE HOT WATER UNIT HEATER
• Low Profile Design • Available in Two Model Sizes • Side Access Piping and Electrical Connections • Flexible
Mounting Orientations • Attractive Hammertone Beige Powdercoat Paint Finish • High Capacity Two-Row Hot
Water Coil • Twin Blower Wheels
MODEL HHD
For applications requiring a low profile unit, Modine offers the Hot Dawg H2O® hot
water unit heater. The Hot Dawg H2O® may be installed in residential or commercial
applications just one inch below the ceiling. The superior quality matched with the
following features makes the Hot Dawg H2O® unit heater an easy choice for a variety
of applications:
• Low profile design is ideally suited for residential garages, basements, vestibules,
commercial, industrial, institutional installations. Non-potable water applications only.
•L
ow profile, 18 gauge steel cabinet results in a clean appearance that maximizes
head room.
•C
abinet pre-treated for prevention of rust and corrosion and finished with a durable
electrostatically applied baked-on polyester powdercoat paint. Attractive Hammertone
Beige paint color.
•H
orizontal adjustable air-deflector blades.
•F
ingerproof inlet air openings.
•S
ide access piping and electrical.
•E
lectrical connections are standard on the left with piping on the right. Access sides
can be easily reversed in the field by simply flipping the unit over.
•T
wo L-shaped mounting brackets.
•B
rackets designed to match up to standard 16" on-center joist spacing.
•M
ounting orientation flexibility includes:
- Horizontal air delivery, mounted parallel to joists.
- Horizontal air delivery, mounted perpendicular to joists.
- Vertical air delivery, mounted between joists.
•H
igh capacity, 2-row hot water coil.
•C
opper tubes mechanically expanded into aluminum fins for maximum heat transfer.
•1
/2" NPT piping connections.
•C
oils suitable for water pressures up to 150PSI and temperatures up to 200°F.
•T
win centrifugal blower wheels for quieter operation.
•D
ual shaft blower motor (115V/60Hz/1ph).
•S
olid state speed controller standard on Model size HHD 45.
•F
actory supplied neoprene vibration isolators.
Table 13.1 - Performance Data ➀ ➁
Model Airflow
WPD
GPM
Size
(CFM)
(Ft. Water)
30
405
710
(High
Speed)
2
45
425
(Low
Speed)
Entering Water Temperature (60°F Entering Air Temperature)
120°F
140°F
160°F
180°F
200°F
Btu/Hr
WTD
Btu/Hr
WTD
Btu/Hr
WTD
Btu/Hr
WTD
Btu/Hr
WTD
1
0.6
11,900
25
15,800
33
19,800
41
23,700
49
27,700
58
2
2.2
15,500
16
20,600
22
25,800
27
30,900
32
36,100
38
3
4.7
17,200
12
22,900
16
28,600
20
34,400
24
40,100
28
4
7.9
18,200
10
24,200
13
30,300
16
36,300
19
42,400
22
5
12
19,600
8
26,100
11
32,600
14
39,200
16
45,700
19
1
0.6
17,200
36
22,900
48
28,600
60
34,400
72
40,100
84
2
2.2
22,400
23
29,900
31
37,300
39
44,800
47
52,300
55
3
4.7
24,900
17
33,200
23
41,500
29
49,800
35
58,100
40
4
7.9
26,400
14
35,100
18
43,900
23
52,700
27
61,500
32
5
12
28,400
12
37,800
16
47,300
20
56,800
24
66,300
28
1
0.6
11,900
25
15,900
33
19,900
41
23,900
50
27,900
58
2
2.2
15,600
16
20,700
22
25,900
27
31,100
33
36,300
38
3
4.7
17,300
12
23,000
16
28,800
20
34,600
24
40,300
28
4
7.9
18,300
10
24,400
13
30,500
16
36,600
19
42,700
22
5
12
19,700
8
26,300
11
32,800
14
39,400
16
46,000
19
➀ For conditions other than shown above, please refer to the Modine Breeze AccuSpec program for detailed performance data.
➁ Allowable water temperature range is 100°F to 200°F. Allowable indoor air temperature range is 40°F to 100°F.
If temperatures below freezing are expected, provisions should be made to either drain the unit heater coil or utilize a
continually circulating glycol solution.
®
Request Catalog 1-115
5-157 For Complete Technical Information and Specifications.
75-136.49
13
STEAM/HOT WATER, HORIZONTAL DELIVERY UNIT HEATERS
• Totally-Enclosed Motor • Thermal Overload Protection • Adjustable Horizontal Blades • Top/Bottom
(Model HSB) or Side (Model HC) Inlet/Outlet Piping • Fan Safety Guard • High Air Velocity Models PT/PTN
An industry leader since Arthur B. Modine invented and patented the first lightweight,
suspended hydronic unit heater in 1923, the Modine hydronic unit heater has proven one of
the most popular of all unit-heater types in commercial and industrial applications. Designed
for long heat-throw and uniform heat delivery, two types are offered:
•H
orizontal Delivery Units (Model HSB/HC) – Recommended for use in buildings where
ceilings are low and with few obstructions. Units are normally placed around the perimeter
of the building so that the air stream from each heater “wipes” the wall to produce a blanket
of warm air along walls where heat loss is greatest.
•P
ower-Throw™ High Velocity Horizontal Delivery Units (Model PT/PTN) –
Recommended where there is a requirement for heat throw greater than can be provided
by standard horizontal delivery models. For hard-to-heat areas, such as frequently opened
loading dock doors or large warehouses, Power-ThrowTM units are an ideal choice. A single
Power-ThrowTM unit can often replace as many as three smaller horizontal delivery units,
reducing equipment, installation, and maintenance costs.
MODEL HSB
MODEL HC
Standard features include:
•T
op/bottom (Model HSB) or side (Model HC) inlet/outlet piping.
•U
nits install quickly, easily, and at low cost because they are lightweight, yet are ruggedly
constructed to resist rigorous handling and on-the-job abuse.
•C
arefully-selected motors and fans with a scientifically designed venturi fan-shroud reduce
noise levels to a satisfactory minimum.
•T
otally enclosed motor with thermal-overload protection.
•F
ans are statically and dynamically balanced.
•F
an and motor assemblies are exposed and can be removed without lowering the unit heater.
•T
he unit casing is treated for protection against corrosion prior to the application of the
attractive gray-green, baked-on polyester powder coat paint finish.
•H
orizontal air deflector blades are standard (vertical deflector blades available).
•L
ow outlet temperature models are recommended for steam pressure above 30 PSI, but can
also be used in dirty environments to minimize buildup of air contaminants on the coil.
•M
odine PTN models feature coils made from cupro-nickel tubes that have the extra
strength to withstand higher steam pressures (250 PSI) or water temperatures (400°F).
Table 13.1 - Horizontal Steam/Hot Water Unit Heater Performance Data
Standard Models
Motor Data ➀
Model No.
MODEL PT/PTN
Steam
(2# Steam, 60°F Ent. Air)
Final
Condensate Air
(Lbs/Hr) Temp.
(°F)
Hot Water
(200°F in 180°F out, 60°F Ent. Air)
Press.
Water Final Air Drop
Flow Temp. (Ft of
(GPM) (°F) Water)
CFM
Max.
Mounting
Height
(Ft.)
Throw
@ Max.
Mounting
Height
(Ft.)
HP
Approx
RPM
Btu/Hr
HSB/HC 18 1/60 1550
18,000 18 107 12,600 1.3 94 0.5 340
8
17
HSB/HC 24 1/25 1550 24,000 25 119 16,300 1.7 100 0.8 370 9
18
HSB/HC 33 1/25 1550 33,000 35 108 21,700 2.3 91 0.2 630 10 21
HSB/HC 47 1/12 1550 47,000 49
119 30,900 3.2 98 0.4 730 12 28
HSB/HC 63 1/12 1550 63,000 66 111 45,600 4.7 97 0.6 1120 14 29
HSB/HC 86 1/8 1625 86,000
89 118 60,200 6.3 101 1.0 1340 15 31
HSB/HC 108 1/8 1625 108,000 111 109 83,700 8.7 98 2.8 2010 17 31
HSB/HC 121 1/5 1075 121,000 126 122 93,000 9.7 108 3.3 1775 16 25
HSB/HC 165 1/3 1075 165,000 170 106 130,900 13.6 97 8.6 3240 19 40
HSB/HC 193 1/3 1075 193,000 200 121 143,000 14.9 105 1.4 2900 18 38
HSB/HC 258 1/2 1075 258,000 267 111 202,000 21.0 100 5.7 4560 19 44
HSB/HC 290 1/2 1075 290,000 300 117 228,600 23.8 105 7.1 4590 20 46
HSB/HC 340 1/2 1075 340,000 352 120 271,100 28.2 108 11.3 5130 20 Btu/Hr
46
PT/PTN 279 1/2 1075 279,000 288
111 192,40020.0 94
0.2 5460 16
100
PT/PTN 333 3/4 1140 333,000 345
116 238,50024.8 99
0.4 5980 17
110
PT/PTN 385 1
110 276,10028.8 95
0.6 7680 17
115
130
1140 385,000 398
PT/PTN 500 1-1/2 1140 500,000
518
108 358,00037.3 93
0.510,390 18
PT/PTN 610 1-1/2 1140 610,000
631
112 450,40046.9 97
1.011,750 20
140
PT 952
986
139 721,60075.2 120 1.112,170 21
145
2
1140 952,000
➀ Applies to most popular motor.
Request Catalog 1-150 For Complete Technical Information and Specifications.
14
75-136.49
STEAM/HOT WATER, VERTICAL DELIVERY UNIT HEATERS
• 15 Standard Models • Lightweight, Easy to Install • Totally-Enclosed Motors • 33,000 to 952,000 Btu/Hr Input
• Built-In Fan Safety Guard
Modine model V/VN vertical steam/hot water unit heaters are designed for long
heat-throw, uniform comfort heat delivery, and reduced maintenance. The units are
recommended for areas where ceilings are high or where obstructions do not permit
good horizontal movement of air.
MODEL V/VN
Standard features include:
•U
nits install quickly, easily, and at low cost because they are lightweight, yet are
ruggedly constructed to resist rigorous handling and on-the-job abuse.
•C
arefully-selected motors and fans with a scientifically designed venturi fan-shroud
reduce noise levels to a satisfactory minimum.
• Totally enclosed motor with thermal-overload protection.
• A motor heat shield protects the motor from heated air passing through the heater.
• Fans are statically and dynamically balanced.
•F
an and motor assemblies are exposed and can be removed without lowering the
unit heater.
•T
he unit casing is treated for protection against corrosion prior to the application of
the attractive gray-green, baked-on polyester powder coat paint finish.
•A
variety of deflector-blade options provides an increased degree of control over
air-discharge direction.
•L
ow outlet temperature models are recommended for steam pressure above 30 PSI,
but can also be used in dirty environments to minimize buildup of air contaminants on
the coil.
•M
odine VN models feature coils made from cupro-nickel tubes that have the extra strength
to withstand higher steam pressures (250 PSI) or water temperatures (400°F).
Table 14.1 - Vertical Steam/Hot Water Unit Heater Performance Data
Standard Models
Motor Data ➀
Model Size
HP
Approx
RPM
Steam
(2# Steam, 60°F Ent. Air)
Btu/Hr
Hot Water
(200°F in 180°F out, 60°F Ent. Air)
Final Air
Condensate
Temp. Btu/Hr
(Lbs/Hr)
(°F)
Press.
Water Final Air
Drop
Temp.
Flow
(Ft of
(°F)
(GPM)
Water)
Max.
Heat
Mounting
CFM
Spread
Height
(Ft.)➁
(Ft.)
V/VN 42
1/301050 42,000
43
103 30,100 3.1
90 0.6
V/VN 59
1/30
61
111
96
V/VN 78
1/151050 78,000
81
109 57,000 5.9
V/VN 95
1/151050 95,000
99
118 69,300 7.2 101 0.5 1665 20
15
V/VN 139
1/5 1075 139,000
144
112 106,60011.1
99
2.6 2660 24
18
V/VN 161
1/3 1075 161,000
167
115 123,20012.8 101
2.2 2940 27
20
V/VN 193
1/3 1075 193,000
200
116 147,20015.3 101
2.2 3500 30
22
V/VN 212
1/3 1075 212,000
219
120 161,70016.8 104
1.5 3610 30
22
V/VN 247
1/2 1075 247,000
256
111 188,70019.7
98
2.1 4820 34
26
V/VN 279
1/2 1075 279,000
288
111 212,70022.2
98
2.1 5460 37
30
V/VN 333
3/4 1140 333,000
345
116 260,10027.1 103
3.8 5980 37
30
V/VN 385
1 1140 385,000
398
110 302,10031.5
98
5.0 7680 36
30
V/VN 500 1-1/21140 500,000
518
108 391,700 40.8
97
4.810,390 44
37
V/VN 610 1-1/21140 610,000
631
112 450,400 46.9
97
1.011,750 43
36
2 1140 952,000
986
139 721,600 75.2 120
1.112,170 45
56
V 952
1050
59,000 42,600
4.4
0.5
950 15
1155
19
95 0.5 1590 20
11
14
15
➀ For most popular motor used on each model.
➁ At 2 psi steam, 60°F entering air – unit heaters equipped with cone-jet deflectors.
Request Catalog 1-150
5-157 For Complete Technical Information and Specifications.
75-136.49
15
OIL-FIRED, HORIZONTAL DELIVERY UNIT HEATERS
• Three Sizes • Pressure-Atomizing, Gun-Type Oil Burner • Cad-Cell Safety Shut-Off • Electric-Spark Ignition
• Fan and Limit Control
Modine model POR oil-fired unit heaters are built with time-tested and field-proven
components to provide optimum comfort and heating efficiency as high as 84%.
MODEL POR
Standard features include:
•A
long-life heat exchanger is made of corrosion-resistant, aluminized steel and rollformed to eliminate thermal stress. It contains a preformed, ceramic fiber fire-pot that
is lightweight, resilient, and resists both mechanical and thermal shocks.
•F
or ease of service, the heat exchanger is equipped with an inspection port,
two clean-out ports, and an amply-sized service door for removing fire pot when
replacement becomes necessary.
•A
reliable, pressure-atomizing gun-type burner equipped with a stainless steel,
die-stamped flame-retention head that can increase combustion efficiency by as much
as 20 to 30 percent over non-flame retention-type burners.
•B
eckett microprocessor-based ignition controller providing superior combustion and
safety monitoring.
•O
nboard diagnostics with LED output for simplifying the lives of service personnel.
• Interrupted-duty ignition that disables the spark once ignition is proven. Older
technology uses a continuous spark that is noisy, prone to shorter lifespan, and not
energy efficient.
•E
lectronic oil igniter module with superior spark voltage (20kV) replaces traditional
bulky ignition transformers.
•B
eckett CleanCut burner pump that uses a solenoid valve to instantly cut oil flow on
shutdown, eliminating soot formation from coasting stops.
•T
wo stage pump with PSC motor provides maximum fuel pressure delivery, even in
high lift applications.
•F
inger-proof fan guard.
•T
he unit casing is treated for protection against corrosion prior to the application of
the attractive gray-green, baked-on polyester powder coat paint finish.
•A
ccessory Outside Combustion Air Kit converts the burner to accept outside
combustion air piping for tight building applications.
Table 15.1 - Oil Fired Unit Heater Performance Data
Model Size
Input
Btu/Hr
Input
GPH
Output
Btu/Hr
CFM
@ 70°F
Delivery
FPM
Temp.
Rise (°F)
Max
Height ➀
Heat
Throw
POR100119,000 0.85
100,000 1890 460
49
12'
39'
POR145175,000 1.25
145,000 2400 580
56
13.5'
50'
POR185231,000 1.65
185,000 3200 740
54
12'
51'
➀ Deflector blades pitched 45° toward the floor. Mounting height is measured from floor to bottom of unit.
Request Catalog 4-112 For Complete Technical Information and Specifications.
16
75-136.49
ELECTRIC, HORIZONTAL VERTICAL DELIVERY UNIT HEATERS
• Low Installation Cost and Maintenance • Model VE Available in 21 Models, 9 Sizes from 5k W through 50 kW
• Model HER Available in 8 Sizes from kW through 25kW • High-Capacity Unit with Horizontal Air Delivery • Model
PTE Available in 3 Sizes from 15kW through 50 kW • Model PTE and VE Offered in Single and Two-Stage Controls
Modine electric unit heaters provide a wide variety of options in solving comfort-heating
problems. Each is designed for long heat-throw, uniform heat-delivery, and reduced
maintenance. The types offered are:
•H
orizontal Delivery Units (Model HER) – Recommended for use in buildings where
ceilings are low and with few obstructions. Units are normally placed around the perimeter of
the building so that the air stream from each heater “wipes” the wall to produce a blanket of
warm air along walls where heat loss is greatest.
• Power-Throw™ High Velocity Horizontal Delivery Units (Model PTE) –
Recommended where there is a requirement for heat throw greater than can be provided
by standard horizontal delivery models. For hard-to-heat areas, such as frequently opened
loading dock doors or large warehouses, Power-Throw™ units are an ideal choice. A single
Power-Throw™ unit can often replace as many as three smaller horizontal delivery units,
reducing equipment, installation, and maintenance costs.
•V
ertical Delivery Units (Model VE) – Recommended for areas where ceilings are high or
where obstructions do not permit good horizontal movement of air.
MODEL HER
Standard features include:
•C
ompletely factory assembled and wired for specific power supply ordered.
•F
inned-tube sheathed nichrome wire heating elements.
•T
otally enclosed motor with thermal-overload protection.
•F
ans are statically and dynamically balanced.
•A
motor heat shield protects the motor from heated air passing through the heater (VE models).
•F
an and motor assemblies are exposed and can be removed without lowering the unit heater.
•T
he unit casing is treated for protection against corrosion prior to the application of the
attractive gray-green, baked-on polyester powder coat paint finish.
•A
variety of deflector-blade options provides an increased degree of control over
air-discharge direction (VE models).
•H
orizontal air deflector blades are standard (vertical deflector blades available) (HER and
PTE models).
•T
erminal and junction boxes provide easy access to heating-element terminals, an overheat
control switch, and the power supply and control connections.
•A
n automatic reset overheat control.
Table 16.1 - Electric Unit Heater Performance Data
MODEL PTE
Model
Size
MODEL VE
Air Delivery Data
Heating Capacity
kW
Btu/Hr
CFM
Outlet Velocity
(FPM)
Temp.
Rise
(°F) ➀
Max. Mounting
Height (Ft.) ➁
Heat Throw
(Ft.) ➁
Electrical
Rating (Volts/
Hz/Ph)
HER30 3.010,200 380
433
25
8
208/60/1
12
HER50 5.017,100 380
447
42
8
12
HER75 7.525,600 530
472
45
8
14
HER100 10.034,100
830
730
38
9
20
HER125 12.542,700
830
743
38
10
20
HER150 15.051,200
830
754
57
10
20
HER200 20.068,300 1300
825
49
11
25
HER250 25.085,400 1300
842
61
11
25
PTE300 30.0102,000 2575
1240
40
17
75
PTE400 40.0137,000 2575
1240
54
15
60
PTE500 50.0171,000 2575
1240
70
14
45
VE50 5.017,100 800
700
21
13
20
VE75 7.525,600 800
700
31
11
17
VE100 10.034,100
940
820
36
12
18
VE150 15.051,200 1340
1170
38
17
26
➂
VE200 19.064,900 1600
1400
41
20
30
➃
VE250 25.085,400 1600
1400
55
17
26
VE300 30.0102,000 2575
1240
40
20
31
VE400 40.0137,000 2575
1240
54
18
27
240/60/1
208/60/3
240/60/3
480/60/3
208/60/3
240/60/3
480/60/3
480/60/3
240/60/1
208/60/3
240/60/3
480/60/3
480/60/3
➀ With 70°F ambient air.
➁ With air deflector blades pitched 45° toward the floor on horizontal models HER and PTE, otherwise no deflector on
model VE. Mounting height is measured from floor to bottom of unit.
➂ VE150 available in 208V/60Hz/3Ph, 240V/60Hz/3Ph and 480V/60Hz/3Ph
➃ VE200 available in 240V/60Hz/3Ph and 480V/60Hz/3Ph
Request Catalog 2-116
5-157 For Complete Technical Information and Specifications.
75-136.49
17
ELECTRIC, HAZARDOUS LOCATIONS UNIT HEATERS
• Rated for 100,000 Cycles of Service • UL Listed • Sealed Heat-Exchanger Core • Ethylene Glycol for Heat
Transfer Fluid • Protected, Explosion-Proof Electric Motor • Two-Piece Fan-Guard
Modine’s HEX electric unit heaters are designed for hazardous industrial locations
where potential for explosion exists due to the presence of flammable gases, vapors,
powdered-metals or dusts. HEX electric unit heaters are UL-listed for Class I, Divisions
1 & 2, Groups C & D; Class II, Division 1, Groups E, F and G and Class II, Division 2,
Groups F and G. UL temperature code shall be T3B 329°F (165°C) for Class I and II,
indicating maximum operating-surface temperatures.
MODEL HEX
Standard features include:
• Liquid to air, finned tube heat exchanger core.
• Ethylene glycol water mixture used as heat-transfer fluid in the heater core, providing
-49°F (-45°C) freeze damage protection.
• Thermally protected, automatic reset, explosion-proof, motor driven fan moves
air across finned tubes for even heat distribution.
• Automatically reset, bimetal high-limit provides over temperature protection and is rated for 100,000 cycles of service.
• Pressure relief valve provides over-pressure protection.
• Epoxy coated, 14 gauge steel cabinet contains heater core, motor, and fan assembly.
• Narrow-gap, two-piece fan-guard shields all moving parts.
• Adjustable extruded aluminum louvers allow directional control of air.
• Copper conductor wires enclosed in steel conduits carry all electrical power.
Table 17.1 - Explosion Proof Electric Unit Heater Performance Data
kW
3
5
Model Size
Supply
Voltage
Heater
Amps
HEX5-208160-030
208/60/1
14.4
HEX5-208360-030
208/60/3
8.3
HEX5-240160-030
240/60/1
12.5
HEX5-240360-030
240/60/3
7.2
3.6
HEX5-480360-030
480/60/3
HEX5-208160-050
208/60/1
24
HEX5-208360-050
208/60/3
13.9
HEX5-240160-050
240/60/1
20.8
HEX5-240360-050
240/60/3
12
Btu/hr
Air Temp
Rise (°F)
Max. Mounting
Height (Ft.)
Heat Throw (Ft.)
10,250
11.2
10
30
17,050
18.6
10
30
25,600
27.9
10
30
34,100
37.2
10
30
51,200
27.1
10
40
HEX5-480360-050
480/60/3
6
HEX5-208160-075
208/60/1
36.1
HEX5-208360-075
208/60/3
20.8
HEX5-240160-075
240/60/1
31.3
HEX5-240360-075
240/60/3
18
HEX5-480360-075
480/60/3
9
HEX5-208360-100
208/60/3
27.8
HEX5-240160-100
240/60/1
41.7
HEX5-240360-100
240/60/3
24.1
HEX5-480360-100
480/60/3
12
HEX5-240360-150
240/60/3
36.1
HEX5-480360-150
480/60/3
18
20
HEX5-480360-200
480/60/3
24.1
68,250
36.1
10
40
25
HEX5-480360-250
480/60/3
30.1
85,300
45.2
20
70
30
HEX5-480360-300
480/60/3
36.1
102,350
26.4
20
70
35
HEX5-480360-350
480/60/3
42.1
119,450
30.7
20
70
7.5
10
15
Request Catalog 2-116 For Complete Technical Information and Specifications.
18
75-136.49
MODINE BREEZE® ACCUSPEC SIZING AND SELECTION PROGRAM
• With the Modine AccuSpec Program, Equipment Selection is a Breeze®
The Modine Breeze® AccuSpec is the fastest way to generate performance data based
on actual job conditions. The Breeze AccuSpec program is a Web-based sizing and
selection program. The program provides a series on step-by-step questions that allow
for the easy configuration of Modine products. After a model has been configured, the
program can generate Submittal Schedules, Performance Data, Dimensional Drawings,
and Specifications.
Calculates Equipment
Capacities and Capabilities
Pictures for Easy Visual
Selection of Equipment
Submittal Schedules
Dimensional Drawings
Specifications
Request Catalog 5-157 For Complete Technical Information and Specifications.
75-136.49
19
HISTORY
A.B. Modine founded Modine Manufacturing Company in 1916 as a one-room office
adjacent to a small workshop in Racine, WI. Today, Modine is an integral
part of the world marketplace with sales approaching $1.5 billion. It specializes
in products used in industrial heating, ventilation and air conditioning equipment,
light, medium and heavy-duty vehicles, off-highway and industrial equipment and
refrigeration systems.
From the beginning, Modine has applied innovative thermal technology to meet
its customers’ needs, with breakthroughs yielding state-of-the-art customized
heating and cooling solutions.
1916 - 1929
1930 - 1949
1950 - 1969
1970 - 1989
1990 - present
Modine is founded by
A.B. Modine in 1916
Modine moves
to current
site in Racine, WI
Company introduces
“Airditioner” a/c
unit for residential
and non-residential
applications
Weatherproof duct
furnaces are
introduced
Modine acquires
Langerer & Reich and
forms Modine Europe
Modine introduces
the PF™ (parallel
flow) condenser
New multi-million
dollar Tech Center
opens in Racine, WI
Vehicular wind
tunnel built
in 1941
A.B. Modine invents
the unit heater by
combining an
automotive radiator, a
fan and steam pipes
The Spirex radiator
is patented and
Modine’s influence
in the transportation
industry grows
Ford makes the
Turbotube radiator
standard on all
Model Ts. Modine
becomes a publicly held company
20
Began producing
all-aluminum,
brazed a/c coils for
cars and trucks
Heating division
introduces a
line of electric
unit heaters
Modine begins
manufacturing
aftercoolers for the P-51 Mustang
fighter plane
Modine begins
manufacturing
rooftop a/c and
unit ventilators
Buena Vista, VA,
home of the
Atherion,
manufacturing
plant opens
Modine acquires
Airedale, an
international leader
in a/c products
West Kingston, RI,
plant acquired and
production begins
on unitary products
The Effinity93™ launches,
the most efficient
gas-fired unit heater
in North America
Modine introduces the
Atherion® and Geofinity
ORIGINAL
Request Catalog 5-157 For Complete Technical Information and Specifications.
®
75-136.49
THIS PAGE INTENTIONALLY LEFT BLANK
Request Catalog 5-157 For Complete Technical Information and Specifications.
75-136.49
21
THIS PAGE INTENTIONALLY LEFT BLANK
Request Catalog 5-157 For Complete Technical Information and Specifications.
22
75-136.49
THIS PAGE INTENTIONALLY LEFT BLANK
Request Catalog 5-157 For Complete Technical Information and Specifications.
75-136.49
23
Products from Modine are designed to provide indoor air-comfort and ventilation
solutions for residential, commercial, institutional and industrial applications.
Whatever your heating, ventilating and air conditioning requirements, Modine
has the product to satisfy your needs, including:
HVAC
•Unit Heaters:
–Gas
–Hydronic
–Electric
–Oil
•Ceiling Cassettes
•Duct Furnaces
•Hydronic Cabinet Unit Heaters, Fin Tube, Convectors
•Infrared Heaters
• Make-up Air Systems
• Unit Ventilators
Ventilation
• Packaged Rooftop Ventilation
School Products
•Vertical Packaged Classroom HVAC:
– DX Cooling/Heat Pump
– Water/Ground Source Heat Pump
– Horizontal/Vertical Unit Ventilators
Geothermal
•Water-to-Water
•Water-to-Air
•Combination
Specific catalogs are available for each product. Catalogs 75-136 and 75-137
provide details on all Modine HVAC equipment.
Modine Manufacturing Company
1500 DeKoven Avenue
Racine, Wisconsin 53403-2552
Phone: 1.800.828.4328 (HEAT)
www.modinehvac.com
© Modine Manufacturing Company 2017
COMMERCIAL & INDUSTRIAL
APPLIED PRODUCTS
HEATING
VENTILATING
COOLING
MAKE-UP AIR
75-137.11 • AUGUST, 2015
MODINE COMMERCIAL & INDUSTRIAL APPLIED PRODUCT LINE
With Modine, we can solve your commercial and industrial heating,
ventilating, and air conditioning application needs with duct furnaces
and direct- or indirect-fired heating & make-up air systems, with heating
capacities up to 7,425,000 Btu/hr and air-handling capacities as high
as 60,000 CFM. Modine also offers a comprehensive line of steam/hot
water cabinet unit heaters, fin tube radiation, and convectors that feature
attractive styling to satisfy your architectural needs.
Modine sales representatives are experienced specialists in the
engineering, selection and application of Modine commercial and
industrial heating and ventilating equipment. Located near you, these
representatives can help you satisfy your comfort needs and indoor-air
quality requirements. Contact your Modine product source for assistance
in providing top-quality, high-efficiency Indoor Air Solutions.
➀
➀
➀
➀
➀
➀
➀
➀ Products as noted can be found in the latest revision of 75-136, Commercial & Industrial Unitary Heating Products
2
75-137.11
MODINE INDUSTRIAL & COMMERCIAL HEATING & VENTILATING EQUIPMENT
CONTENTS
PAGE
Indoor Gas-Fired Gravity Vented, Power Vented, and
Separated Combustion Duct Furnaces ..................................................4
Indoor Gas-Fired Gravity, Power, and Separated Combustion
Vented Heating, Cooling, Ventilating, and Make-Up Air System Units......5
WeatherHawk® Weatherproof Gas-Fired Duct Furnace .........................6
WeatherHawk® Weatherproof Gas-Fired System Units
Heating, Cooling, Ventilating, and Make-Up Air Units ............................7
Direct-Gas-Fired Indoor and Outdoor Heating and
Make-Up Air Units ..................................................................................8
Ductless Ceiling Cassettes.....................................................................9
Cabinet Unit Heaters ............................................................................10
Commercial Fin Tube Radiation ...........................................................11
Convectors ...........................................................................................12
Valedictorian® Unit Ventilator ................................................................13
Modine Breeze® AccuSpec Sizing and Selection Program ..................14
75-137.11
3
GAS-FIRED, GRAVITY AND POWER-VENTED DUCT FURNACES
• Low Initial Cost • Applications Cover Heating and/or Make-Up Air • 75,000 to 400,000 Btu/Hr Input Capacity
• 80% Minimum Thermal Efficiency • Low Maintenance • Easy to Service
Modine offers three types of indoor indirect gas fired duct furnaces to cover a wide range
of heating applications in building heating and make-up air systems.
Gravity Vented
Model DFG duct furnaces are an economical choice for superior quality and dependability in most
applications. These units feature the following:
• Available in 11 model sizes from 75,000 to 400,000 Btu/hr, all 80% thermally efficient for fuel savings.
• Aluminized steel heat exchanger (409 stainless steel optional).
• Uses natural or propane gas (field convertible from natural to propane gas).
• Certified for location either upstream or downstream from cooling coils and has a drain pan that
allows connection to a condensate drain line.
• Certified to 3.0" W.C. external static pressure for high static applications.
• A wide range of controls, options, and accessories for unit customization.
• Because the unit relies on a natural draft to vent properly, power vented units should be
considered if the vent system is horizontal or if the space in which the unit is located is generally
under a negative pressure.
MODEL DFG
GRAVITY VENTED
Power Vented
Model DFP includes the items featured for Model DFG, but adds an integral power exhauster for:
• Vertical or horizontal venting with the smallest diameter vent pipe possible.
• The ability to overcome reasonable negative pressures seen in buildings with inadequate make up air.
• Improved building efficiency through the reduction of off-cycle vent losses.
Separated Combustion
Model DFS builds upon the advantages of the Power Vented Model DFP, but is specifically designed
for buildings with hostile environments, such as dirty or high humidity applications. This model
features:
• Separate electrical and gas control access with fully gasketed doors to seal components from the
environment.
• Combustion air that is drawn from outside to ensure the unit has plenty of fresh, clean air.
• Since combustion air is introduced from outside, off-cycle vent losses are essentially eliminated,
further improving building efficiency.
• Horizontal or vertical two-pipe or concentric venting options.
Performance Data
MODEL DFP
POWER VENTED
Model
Size
75
100
125
150
Without Air Baffle (DFG/DFP) ➁
With Air Baffle (DFG/DFP) ➁
or
or
Low Air Temperature Rise (DFS) High Air Temperature Rise (DFS)
Btu/Hr
Input
Output
75,000
60,000
80,000
100,000
120,000
Temperature Rise
Range (°F)
20 - 60
20 - 60
20 - 60
20 - 60
160,000
20 - 60
100,000
125,000
150,000
175
175,000
140,000
225
225,000
180,000
200
250
MODEL DFS
SEPARATED
COMBUSTION
➀➁➂
300
350
400
200,000
250,000
300,000
350,000
400,000
200,000
240,000
280,000
320,000
Temperature Rise
Range (°F)
926 - 2,778
20 - 100
1,235 - 3,704
20 - 100
1,543 - 4,630
20 - 100
1,852 - 5,556
20 - 100
CFM Range
CFM Range
556 - 2,778
741 - 3,704
926 - 4,630
1,111 - 5,556
20 - 60
2,160 - 6,481
20 - 100
1,296 - 6,481
20 - 60
2,778 - 8,333
20 - 100
1,667 - 8,333
20 - 60
20 - 60
20 - 60
20 - 60
2,469 - 7,407
3,086 - 9,259
3,704 - 11,111
4,321 - 12,963
4,938 - 14,815
20 - 100
20 - 100
20 - 100
23 - 100
27 - 100
1,481 - 7,407
1,852 - 9,259
2,222 - 11,111
2,593 - 11,111
2,963 - 11,111
➀ Ratings are shown for elevations up to 2,000 feet.
➁ For DFG or DFP models in high CFM applications, the air distribution baffle may be removed to reduce the pressure drop through
the duct furnace. DFS units are ordered specifically designed for either low air temperature rise or high air temperature rise.
➂ DFP and DFS are approved for use in California by CEC.
DO NOT LOCATE ANY GAS-FIRED UNIT IN AREAS WITH CHLORINATED,
HALOGENATED OR ACIDIC VAPORS IN ATMOSPHERE.
Request Catalog 5-174 For Complete Technical Information and Specifications.
4
75-137.11
INDOOR GAS-FIRED HEATING, COOLING, VENTILATING, AND MAKE-UP AIR UNITS
• 75,000 to 1,200,000 Btu/Hr Input Capacity • Gravity, Power, or Separated Combustion Venting
• Large Selection of Blower Fan/Drive and Motor Combination Available
• Easy to Service • Variable Frequency Drive for Variable Air Volume Applications
The Modine indoor duct furnace with blower and/or cooling sections was designed for use
with a building’s heating, heating/ventilating/cooling and make-up air systems. Available in
17 model sizes, these units cover a wide variety of applications. They have input ranges
from 75,000 to 1,200,000 Btu/Hr and can operate on either natural or propane gas. The
airflow ranges from 556 to 14,500 CFM and right or left hand control access can be
specified when ordering the unit. They can be provided with a cooling coil section with either
a factory installed DX or chilled water cooling coil or the coil can be provided by others.
MODEL DBG
MODEL DBP
Standard Features:
• 18 gauge insulated aluminized steel blower cabinet with a baked-on polyester powder
paint finish on exterior casing parts
• Blower performance up to 3.0" W.C. external static pressure
• Blower and motor vibration isolation
• Gravity and power vented units are specifically designed for low cost installations
• Separated combustion units are specifically designed for buildings with hostile
atmospheric conditions, such as high humidity or negative pressures.
Optional Features:
• DX or chilled water section with factory installed cooling coil
• Double wall construction for blower and/or cooling cabinet
• Dead-front disconnect switches
• Two position, modulating, building pressure sensing, three position, building
management (0 - 10 Vdc or 4 - 20 mA input) damper actuators
• Variable frequency drive for variable air volume applications
Performance Data
MODEL DBS
Model
Size
Btu/Hr
Input
Btu/Hr
Output
75
100
125
150
175
200
225
250
300
350
400
500
600
700
800
840
900
75,000
100,000
125,000
150,000
175,000
200,000
225,000
250,000
300,000
350,000
400,000
500,000
600,000
700,000
800,000
1,050,000
1,200,000
60,000
80,000
100,000
120,000
140,000
160,000
180,000
200,000
240,000
280,000
320,000
400,000
480,000
560,000
640,000
840,000
960,000
DBG/DBP/DBS DBG/DBP/DBS, DCG/DCP/DCS
MODEL DCP
➀➁
Temperature
Rise Range (°F)
20
20
20
20
23
23
26
20
20
22
25
40
40
40
41
60
63
-
100
100
100
100
100
100
100
100
100
100
100
120
120
120
120
120
120
CFM
Range
556 - 2,778
741 - 3,704
926 - 4,630
1,111 - 5,556
1,296 - 5,556
1,481 - 6,500
1,667 - 6,500
1,852 - 9,259
2,222 - 11,111
2,593 - 12,000
2,963 - 12,000
3,086 - 9,259
3,704 - 11,111
4,321 - 12,963
4,938 - 14,500
6,481 - 12,963
7,407 - 14,500
Total Static
Pressure Range
(Inches w.c.)
0 - 3.0
0 - 3.0
0 - 3.0
0 - 3.0
0 - 3.0
0 - 3.0
0 - 3.0
0 - 3.0
0 - 3.0
0 - 3.0
0 - 3.0
0 - 3.0
0 - 3.0
0 - 3.0
0 - 3.0
0 - 3.0
0 - 3.0
➀ Ratings are shown for elevations up to 2000 feet.
➁ Power vented and separated combustion units approved for use in California by CEC.
Cooling Coil Performance Data
Model
Size
MODEL DCS
75
100/125
150/175
200/225
250/300
350/400
Cooling Coil
Maximum Cooling Tons ➁
Maximum CFM
Water
DX Coil ➂ Chilled
Coil ➂
1,891
2,206
2,521
3,352
3,724
5,214
9.38
11.43
13.42
18.12
20.24
27.26
10.56
12.62
14.77
19.28
21.33
29.25
➁ 1 Ton = 12,000 Btu/Hr
➂ Based on 95°F entering dry bulb, 75°F entering wet bulb
Request Catalog 5-173 For Complete Technical Information and Specifications.
75-137.11
5
WEATHERHAWK® WEATHERPROOF GAS-FIRED DUCT-FURNACE
• Low Initial Cost • Applications Cover Heating and/or Make-Up Air • 75,000 to 400,000 Btu/Hr Input Capacity
• Low Maintenance • Easy to Service
The Modine WeatherHawk® weatherproof duct furnace was
designed for use with a building’s heating, heating/cooling
and make-up air systems. Available in 11 power vented
model sizes, the unit covers a wide variety of applications.
They have input ranges from 75,000 to 400,000 Btu/Hr
and can operate on either natural or propane gas. Right
or left hand control access can be specified when ordering
the unit. The duct furnace is certified for location either
upstream or downstream from cooling coils and has holes to
drain any condensate that may form onto the roof.
MODEL HFP
Standard Features:
• All units a minimum of 80% thermal efficient
• 18 gauge aluminized steel cabinet with a baked-on polyester powder paint finish on
exterior casing parts
• Certified to 3.0” W.C. external static pressure
Optional Features:
• 409 stainless steel heat exchanger and burner
• 409 stainless steel drip pan
• Two-stage and electronic modulation controls for either natural or propane gas
• Building management compatible modulating gas controls for 0 - 10 Vdc or 4 - 20 mA input
• High and/or low gas pressure switches
Performance Data
➀➁
Btu/Hr
Model
No.
Input
Output
HFP75
HFP100
HFP125
HFP150
HFP175
HFP200
HFP225
HFP250
HFP300
HFP350
HFP400
75,000
100,000
125,000
150,000
175,000
200,000
225,000
250,000
300,000
350,000
400,000
60,000
80,000
100,000
120,000
140,000
160,000
180,000
200,000
240,000
280,000
320,000
Low Temperature
High Temperature
Temperature Rise
Temperature Rise
CFM Range
CFM Range
Range (°F)
Range (°F)
20 - 60
926 - 2,778
20 - 100
556 - 2,778
20 - 60
1,235 - 3,704
20 - 100
741 - 3,704
20 - 60
1,543 - 4,630
20 - 100
926 - 4,630
20 - 60
1,852 - 5,556
20 - 100
1,111 - 5,556
20 - 60
2,160 - 6,481
20 - 100
1,296 - 6,481
20 - 60
2,469 - 7,407
20 - 100
1,481 - 7,407
20 - 60
2,778 - 8,333
20 - 100
1,667 - 8,333
20 - 60
3,086 - 9,259
20 - 100
1,852 - 9,259
20 - 60
3,704 - 11,111
20 - 100
2,222 - 11,111
20 - 60
4,321 - 12,963
23 - 100
2,593 - 11,111
20 - 60
4,938 - 14,815
27 - 100
2,963 - 11,111
➀ Ratings are shown for elevations up to 2,000 feet.
➁ Units approved for use in California by CEC.
Request Catalog 5-173 For Complete Technical Information and Specifications.
6
75-137.11
OUTDOOR GAS-FIRED HEATING, COOLING, VENTILATING, AND MAKE-UP AIR UNITS
The Modine weatherproof duct furnace with blower, cooling,
and/or downturn plenum sections was designed for use with
a building’s heating, heating/ventilating/cooling and make-up
air systems. Available in 17 power vented model sizes, the
unit covers a wide variety of applications. They have input
ranges from 75,000 to 1,200,000 Btu/Hr and can operate on
either natural or propane gas. The airflow ranges from 556
to 14,500 CFM and right or left hand control access can be
specified when ordering the unit. The unit can be provided with a cooling coil section with either
a factory installed DX or chilled water cooling coil or the coil can be provided by others.
Optional Features:
• DX or chilled water section with factory installed cooling coil
• Double wall construction for blower, cooling cabinet, and/or downturn plenum sections
• Dead-front disconnect switches
• Two position, modulating, building pressure sensing, three position, building management
(0 - 10 Vdc or 4 - 20 mA input) damper actuators
• Variable frequency drive for variable air volume applications
Performance Data
Model
HBP/HCP/HDP/HPP
MODEL HDP
Standard Features:
• 18 gauge insulated aluminized steel cabinet with a baked-on polyester powder paint
finish on exterior casing parts
• Blower performance up to 3.0" W.C. external static pressure
• Blower and motor vibration isolation
• Side or bottom (through a roof curb) gas and electrical connection access
HBP/HDP
MODEL HBP
➀➁
Model
Size
Btu/Hr Input
Btu/Hr
Output
Temperature Rise
Range (°F)
CFM Range
75
100
125
150
175
200
225
250
300
350
400
500
600
700
800
840
960
75,000
100,000
125,000
150,000
175,000
200,000
225,000
250,000
300,000
350,000
400,000
500,000
600,000
700,000
800,000
1,050,000
1,200,000
60,000
80,000
100,000
120,000
140,000
160,000
180,000
200,000
240,000
280,000
320,000
400,000
480,000
560,000
640,000
840,000
960,000
20 - 100
20 - 100
20 - 100
20 - 100
23 - 100
23 - 100
26 - 100
20 - 100
20 - 100
22 - 100
25 - 100
40 - 120
40 - 120
40 - 120
41 - 120
60 - 120
63 - 120
556 - 2,778
741 - 3,704
926 - 4,630
1,111 - 4,630
1,296 - 5,556
1,481 - 6,500
1,667 - 6,500
1,852 - 9,259
2,222 - 11,111
2,593 - 12,000
2,963 - 12,000
3,086 - 9,259
3,704 - 11,111
4,321 - 12,963
4,938 - 14,500
6,481 - 12,963
7,401 - 14,500
➀ Ratings are shown for elevations up to 2,000 feet.
➁ Units approved for use in California by CEC.
Total Static
Pressure Range
(Inches w.c.)
0 - 3.0
Cooling Coil and Evaporative Cooling Performance Data
Cooling Coil
Max. Cooling Tons ➂
Model Size Maximum CFM
Chilled Water
DX Coil➃
Coil➃
75
1,891
9.38
10.56
100/125
2,206
11.43
12.62
150/175
2,521
13.42
14.77
200/225
3,352
18.12
19.28
250/300
3,724
20.24
21.33
350/400
5,214
27.26
29.25
➂ 1 Ton = 12,000 Btu/Hr
➃ Based on 95°F entering dry bulb, 75°F entering wet bulb
Evaporative Cooling
Btu/Hr
Maximum CFM
Min.
Max.
2,750
4,000
5,200
6,000
10,400
11,050
9,968
13,125
19,198
24,952
37,916
44,247
52,272
54,432
70,762
81,648
141,523
150,368
Request Catalog 5-173 For Complete Technical Information and Specifications.
75-137.11
7
DIRECT GAS-FIRED INDOOR AND OUTDOOR HEATING
AND MAKE-UP AIR UNITS
• ETL Certified • Btu/Hr Outputs from 42,000 to 7,425,000 • CFM Ranges from 1,600 to 60,000
• 100% Make-Up Air and Recirculating Configurations • 100% Thermal Efficiency
• Designed for Indoor or Outdoor Mounting • Factory-Assembled Natural or Propane Gas Manifolds
Modine direct-fired, make-up-air units - the MDB (Single Speed and Variable Frequency
Drive Two Speed/Multi Speed Make-Up Air) and MRB (Fresh and Return Air), are designed
to provide an economical and efficient means of supplying tempered make-up air to a
space or building. Available in eight airflow configurations, the units cover a wide variety of
applications.
Standard Features:
• 100% thermal efficiency (92% sensible) results in lower fuel bills
• Units are designed for indoor or outdoor mounting, providing flexibility in applications
• Natural or propane gas manifolds are factory-assembled to provide flexible fuel options
and to reduce field-installation, start-up costs and problems
• Factory-wired electrical panel with numbered terminals significantly reduces start-up delays
• 100% factory flame-testing eliminates field start-up problems caused by defective controls
• Weatherproof roof with drip ledge provides protection from water being drawn into the unit
• 18-gauge galvanized steel casing provides high corrosion protection for long life
• Adjustable motor sheaves through 10 HP simplify air balancing
• Four access doors provide maximum access for easy adjustments and service
• High firing rate turndown for optimum temperature control
MODEL MDB/MRB
Optional Features:
• V-bank filter section
• Inlet hood
• Inlet damper
• Discharge damper
• Evaporative cooling
• IRI and FM manifold arrangements
• Discharge air temperature control, space temperature control, or building management
(0-10 Vdc or 4-20 mA input) control
• High and low gas pressure switches
• Internal blower and motor vibration isolation
• Painted casing
Performance Data
Model
No.
CFM Range
SCFM ➀
Maximum
Output
(Btu/Hr) ➀
Natural Gas
Maximum
Temperature
Rise (F) ➀
Total Static
Pressure
Range (" W.C.)
Horsepower
Range
MDB/MRB110
1,600-3,300
432,400
115
0-2.8"
3/4-3
MDB/MRB112
2,000-4,700
615,800
115
0-3.0"
3/4-5
MDB/MRB115
3,000-6,500
851,700
115
0-2.6"
1-5
MDB/MRB118
3,500-10,000
1,310,300
115
0-3.0"
1 1/2-10
MDB/MRB120
6,000-13,500
1,769,000
115
0-3.0"
2-15
MDB/MRB122
8,000-16,500
2,162,100
115
0-3.0"
3-20
MDB124 ➁
10,000-21,500
2,200,000
115
0-3.0"
3-20
MDB/MRB125
10,000-21,500
2,817,300
115
0-3.0"
3-20
MDB/MRB130
14,000-30,000
3,931,100
115
0-2.7"
5-25
MDB/MRB220
18,000-27,000
3,538,000
115
0-3.0"
7 1/2-25
MDB/MRB222
25,000-33,000
4,324,200
115
0-3.0"
15-30
MDB/MRB225
30,000-46,000
6,027,700
115
0-3.0"
15-40
MDB/MRB230
44,000-60,000
7,425,000
115
0-2.7"
20-50
➀ CFM, Btu/Hr capacities & Temperature Rise vary depending on unit configuration and certification.
The Maximum Temperature Rise for propane gas is 100°F.
➀ Model Size 124 is available only as Model MDB for 100% outside air applications.
Request Catalog 7-150 For Complete Technical Information and Specifications.
Model MDB units are ETL Certified for use in the U.S. and Canada.
Model MRB units are ETL Certified for use in the U.S. only.
8
75-137.11
MODINE INDUSTRIAL & COMMERCIAL HEATING & VENTILATING EQUIPMENT
The Modine Cassette units effectively make each area served an independent controlled
temperature zone. Through thermostatic control of operations, conditions can be varied
to suit diverse requirements or activities. Optional fresh air intakes are available to
provide for ventilation and recirculation of room air.
Modine Cassettes are available in a choice of three models – DX cooling or heat
pumps in five model sizes and chilled water cooling with six model sizes – to properly
match units to job requirements. Optional heating can be provided by factory installed
electric heat or hot water modules, depending on model. This versatility eliminates
compromising architecture or design. Important cost savings are often realized during
building modernizations, as existing piping and/or wiring can frequently be reused.
Design techniques are incorporated in every Modine Cassette to reduce noise levels
to an absolute minimum. These techniques include low blower speeds, rigid panel and
cabinet construction, and sound-absorbent cabinet insulation.
For individual comfort, Modine Cassettes are available with electro-mechanical or microprocessor based controls. The micro-processor controller includes infrared transmitter
which enables room conditions to be maintained at a user defined set point. Modine
Cassettes are also available with Carel microprocessor controls and network cards to
allow units to be connected to a Building Management System.
Direct Expansion (DX) Air Conditioning and Heat Pump Models
Model No.
SSD/SSH 18
SSD/SSH 24
SSD/SSH 30
SSD/SSH 36
SSD/SSH 42
Total
Heat
Hot Water Electric
Cooling
Pump SEER HSPF
Heat
Heat
(BTU/h) ➀ (BTUh) ➁
(BTU/h) ➂ (kW)
Dimensions - H x W x D (inches)
Chassis
Fascia
Weight
(lbs)
2 5/8 x 37 x 37
84
21,500
16,400
13
7.7
38,746
3.0
11 5/8 x 32 5/16 x 32 3/8
34,800
27,400
13
7.7
56,609
5.0
11 1/2 x 44 7/16 x 32 3/8 2 5/8 x 49 3/16 x 37
118
11 1/2 x 44 7/16 x 32 3/8 2 5/8 x 49 3/16 x 37
118
25,400
41,800
45,500
21,400
13
32,400
13
37,000
13
7.7
7.7
7.7
41,993
59,600
64,268
3.0
5.0
5.0
11 5/8 x 32 5/16 x 32 3/8
2 5/8 x 37 x 37
84
11 1/2 x 44 7/16 x 32 3/8 2 5/8 x 49 3/16 x 37
118
➀ Cooling capacities based on 80/67°F DB/WB Indoor and 82/65°F DB/WB Outdoor Ambient.
➁ Heating capacities based on 70/60°F DB/WB Indoor and 47/43°F DB/WB Outdoor Ambient.
➂ Nominal hot water heating capacity based on air 70°F & 180°F inlet / 160°F outlet water temperatures.
Chilled Water Cooling Models
Model No.
Total
Cooling
(BTU/h) ➀
SCW 08
7,026
Hot
Electric
Water Heat
Heat
(BTU/h) ➁
(kW)
Dimensions - H x W x D (inches)
Chassis
Fascia
13,799
1.5
10 11/16 x 22 1/2 x 22 1/2
2 5/8 x 25 3/16 x 25 3/16
Weight
(lbs)
45
SCW 12
11,236
N/A
1.5
10 11/16 x 22 1/2 x 22 1/2
2 5/8 x 25 3/16 x 25 3/16
45
SCW 18
18,432
29,258
3.0
9 1/2 x 32 5/16 x 32 3/8
2 5/8 x 37 x 37
82
SCW 20
19,971
30,946
3.0
9 1/2 x 32 5/16 x 32 3/8
2 5/8 x 37 x 37
82
SCW 33
30,595
46,555
5.0
11 1/2 x 44 7/16 x 32 3/8
2 5/8 x 49 3/16 x 37
118
SCW 36
35,934
51,600
5.0
11 1/2 x 44 7/16 x 32 3/8
2 5/8 x 49 3/16 x 37
118
➀ Nominal chilled water cooling capacity based on air 80/67°F Dry/Wet Bulb & 45°F inlet / 55°F outlet water temperature.
➁ Nominal hot water heating capacity based on air 70°F & 180°F inlet / 160°F outlet water temperatures.
Request Catalog 8-105 For Complete Technical Information and Specifications.
75-137.11
9
STEAM/HOT WATER CABINET UNIT HEATERS
• One- or Two-Row, Copper Tube - Aluminum Fin Coil • Motor with Built-In Thermal Overload Protection, 115v/60/1φ
• Forward-Curved Aluminum Blower Wheels • Unit-Mounted, Solid-State Speed Control • Permanent, Cleanable Air Filter
• Sound-Dampening Insulation on Front Panels • Stamped Louvers
Modine cabinet unit heaters effectively make each area served an independent heating
zone. Through thermostatic control of heater operations, conditions can be varied to suit
diverse requirements or activities. Optional controls and outside and return-air dampers
are available to provide for ventilation and recirculation of room air.
Modine cabinet unit heaters are available in a choice of two models and eight sizes
to properly match units to job requirements. This versatility eliminates compromising
architecture or design. Important cost savings are often realized during building
modernizations, as existing piping and/or wiring can frequently be reused.
MODEL C
Exposed
Floor Mounted
Unit
Design techniques are incorporated in every cabinet unit heater to reduce noise
levels to an absolute minimum. These techniques include low blower speeds, rigid
panel and cabinet construction, and sound-absorbent cabinet insulation.
Clean, uncluttered designs and compact dimensions allow Modine cabinet unit heaters
to blend into any environment and minimize installation space. The standard cabinet
finish is a light-tan baked polyester powder coat paint, and optional factory-applied
decorative colors are also available.
Performance Data
Hot Water
(200°F in 180°F out, 60°F Ent. Air)
Standard Coil
Unit
Size
Standard Coil
High Capacity Coil
Btu/Hr
GPM
CFM
Final Air
Temp.
(°F)
2
12,400
1.28
250
106
23,200
2.4
250
146
19,800
250
21
133
4
28,100
2.87
450
117
45,800
4.7
440
156
42,500
450
44
147
MODEL CW
Exposed Wall or
Ceiling Mounted
Unit
Steam
(2lb. Steam, 60°F Ent. Air)
3
6
8
21,100
44,300
48,800
10
55,700
14
79,200
12
72,300
2.23
4.43
330
121
Btu/Hr
GPM
CFM
Final Air
Temp.
(°F)
Btu/Hr
GPM
CFM
Final Air
Temp.
(°F)
33,400
3.6
325
155
28,300
330
29
620
126
59,700
6.0
615
150
52,100
620
54
5.70
1050
108
84,600
8.7
1040
135
76,000
1050
79
8.10
1430
111
12.1
1410
137
102,600
1430
5.00
7.40
840
1240
113
113
71,900
105,600
118,300
7.4
10.8
835
1220
139
140
67,700
95,400
840
1240
70
99
106
133
137
134
126
130
126
MODEL CW
Recessed
(Full or Partial)
Wall or Ceiling
Mounted Unit
Shown with Optional
Perma-Lap® Frame
Request Catalog 11-160 For Complete Technical Information and Specifications.
10
75-137.11
STEAM/HOT WATER COMMERCIAL FIN TUBE RADIATION
• Enclosures Fasten Together with a Slip Joint • Knob or Tamperproof Dampers Available
• Easy Installation with Hanger Strip and Enclosure Support
Fin tube radiation heaters from Modine are designed with a variety of enclosure styles to
meet most any application or architectural style. Heating elements are copper tubes with
aluminum fins. The aluminum fins are mechanically bonded to the copper tube to provide
maximum heat transfer. A choice of fin spacings permits the selection of elements to meet
your design requirements.
Modine’s fin tube radiation heaters can be supplied in two- to eight-foot lengths and
in a variety of colors to match most decors. A full compliment of accessories to match
enclosure styles provides flexibility in design and installation.
Model SP
Trimfin®
Model TA
Top Outlet
with Aluminum Grille
Model S
Slope Top
Model F
Front Outlet
Model R
Front and Top Outlet
Model RF
Front and Top Outlet
Floor Mounted
Model SF
Slope Top
Floor Mounted
Model T
Top Outlet
Model PS
Slope Top Security
Model FT
Flat Top
Protective Metal Cover
Model P
Pedestal Mounted
Model EM
Expanded Metal
Model PA
Pedestal Mounted
Aluminum Grille
Copper Tube with Aluminum
Fin Heating Element
Request Catalog 12-135 For Complete Technical Information and Specifications.
75-137.11
11
STEAM/HOT WATER CONVECTORS
• Easy Installation • Louvered Air Outlet and/or Inlet Grilles • Copper-Tube Aluminum Fin Heating Element for
Use with Steam or Hot Water • Opposite-End Heating Element Piping Connections
Modine convectors provide maximum installation flexibility for a variety of heating
applications. They come in a variety of models, allowing convectors to be partially
recessed, wall hung, and free standing. The heating elements can be used for hot
water or steam. The standard header is copper with top and bottom tappings.
Tubes are mechanically expanded into aluminum fins to form a durable bond for
maximum heat transfer.
Modine offers convectors in 24 - 64 inch lengths and 4 different heights, ranging from
18 - 32 inches depending on model. A variety of optional colors are offered. A complete
line of options and accessories provides flexibility in design and installation.
Model SL
Slope-Top Wall Mounted
Model FL
Flat-Top Floor Mounted
Model SF
Slope-Top Floor Mounted
Model PL
Fully-Recessed Wall Mounted
Request Catalog 13-111 For Complete Technical Information and Specifications.
12
75-137.11
VALEDICTORIAN® UNIT VENTILATOR
• Heavy-Duty Construction • Flexible Modular Design • Copper Tube-Aluminum Highmix® Fin Water Coils
• Modulating Valve or Face & Bypass Temperature Control • Floor and Ceiling Mounted Configurations
The Valedictorian vertical unit ventilator is the perfect solution for both new construction
and replacement of existing units in schools that want to improve the indoor air quality
of their classrooms. Designed to be tough, dependable, aesthetically pleasing, quiet
and easy to install, the Valedictorian keeps an established product up-to-date with an
impressive list of features and options.
®
MODELS VFV & VFF
The Valedictorian has heavy-duty construction with 14 gauge exterior panels, tamperproof cabinet locks, and pencil-proof aluminum supply air bar grills. Electrostatically
applied, baked-on polyester powder coat paint ensures a long-lasting, durable finish.
A variety of available sub-bases, utility compartments, filler sections, side end-panels,
and adapter backs allow for existing systems to easily be upgraded. Available as floor
or ceiling mounted, the Valedictorian can be utilized in any new or existing construction
condition.
®
MODEL VFC
Available in four sizes, the unit incorporates a draw-through design with 2, 3, or 4-row
coils for chilled water only, chilled water/hot water 2-pipe or 4-pipe installation, DX cooling
coil, and steam heating coil. Optional 1 or 2-row hot water coils are available for 4-pipe
systems and can be positioned for either preheat or reheat applications. A variety of
ventilation configurations are available that utilize fully modulating outside air and return
air dampers allowing for any mixture of outside air and return air to be drawn through
the unit.
Discharge air temperature is controlled using either a face-and-bypass damper or a
modulating control valve. An optional factory installed microcontroller is available or
the units may be configured as DDC ready or set-up for field installed controls. Piping
components can be ordered individually or configured as a pre-assembled piping
package for easy on-site installation.
Chilled Water Cooling Performance (Btu/Hr)
➀➁➂
Rows of Coil
Unit Size
2
3
4
Total
Sensible
Total
Sensible
Total
Sensible
VFF/VFV/VFC 750
18,500
49,800
59,650
70,100
70,100
70,100
VFF/VFV/VFC 1000
24,250
62,400
77,550
92,600
92,600
92,600
VFF/VFV/VFC 1250
26,250
72,400
88,400
103,600
103,600
103,600
VFF/VFV/VFC 1500
61,150
81,100
99,200
108,950
108,950
108,950
➀ Rated in accordance with ARI Standard 840.
➁ Water temperature rise is 10°F, with entering water temperature of 45°F.
➂ Entering air temperature is 80°F dry bulb, 67°F wet bulb.
Hot Water Heating Performance (Btu/Hr)
Unit Size
➀➁
Rows of Coil
1
2
3
4
70,100
VFF/VFV/VFC 750
38,400
49,800
59,650
VFF/VFV/VFC 1000
50,100
62,400
77,550
92,600
VFF/VFV/VFC 1250
57,200
72,400
88,400
103,600
VFF/VFV/VFC 1500
61,150
81,100
99,200
108,950
➀ Water temperature is 160°F, with water flow rate of 6 gpm.
➁ Entering air temperature is 60°F.
Request Catalog 14-100 For Complete Technical Information and Specifications.
75-137.11
13
MODINE BREEZE® ACCUSPEC SIZING AND SELECTION PROGRAM
• With the Modine AccuSpec Program, Equipment Selection is a Breeze®
The Modine Breeze AccuSpec is the fastest way to generate performance data based
on actual job conditions. The Breeze AccuSpec program is a Web-based sizing and
selection program. The program provides a series on step-by-step questions that allow
for the easy configuration of Modine products. After a model has been configured, the
program can generate Submittal Schedules, Performance Data, Dimensional Drawings,
and Specifications.
Calculates Equipment
Capacities and Capabilities
Pictures for Easy Visual
Selection of Equipment
Submittal Schedules
14
Dimensional Drawings
75-137.11
Specifications
HISTORY
A.B. Modine founded Modine Manufacturing Company in 1916 as a one-room
office adjacent to a small workshop in Racine, WI. Today, Modine is an integral
part of the world marketplace with sales approaching $1.5 billion. It specializes
in products used in industrial heating, ventilation and air conditioning equipment,
light, medium and heavy-duty vehicles, off-highway and industrial equipment
and refrigeration systems.
From the beginning, Modine has applied innovative thermal technology to meet
its customers’ needs, with breakthroughs yielding state-of-the-art customized
heating and cooling solutions.
1916 - 1929
1930 - 1949
1950 - 1969
1970 - 1989
1990 - present
Modine is founded by
A.B. Modine in 1916
Modine moves
to current
site in Racine, WI
Company introduces
“Airditioner” a/c
unit for residential
and non-residential
applications
Weatherproof duct
furnaces are
introduced
Modine acquires
Langerer & Reich and
forms Modine Europe
Modine introduces
the PF™ (parallel
flow) condenser
New multi-million
dollar Tech Center
opens in Racine, WI
Vehicular wind
tunnel built
in 1941
A.B. Modine invents
the unit heater by
combining an
automotive radiator, a
fan and steam pipes
The Spirex radiator
is patented and
Modine’s influence
in the transportation
industry grows
Began producing
all-aluminum,
brazed a/c coils for
cars and trucks
Heating division
introduces a
line of electric
unit heaters
Modine begins
manufacturing
aftercoolers for
the P-51 Mustang
fighter plane
Modine begins
manufacturing
rooftop a/c and
unit ventilators
Buena Vista, VA,
home of the
Atherion,
manufacturing
plant opens
Ford makes the
Turbotube radiator
standard on all
Model Ts. Modine
becomes a publicly
held company
Modine acquires
Airedale, an
international leader
in a/c products
West Kingston, RI,
plant acquired and
production begins
on unitary products
The Effinity93™ launches,
the most efficient
gas-fired unit heater
in North America
Modine introduces the
Atherion® and Geofinity
ORIGINAL
®
75-137.11
15
The Modine brand has been the
industry standard since Arthur B.
Modine invented and patented
the first lightweight, suspended
hydronic unit heater in 1923.
No other manufacturer can
provide the combined application
Products from Modine are designed to provide indoor air-comfort and ventilation
solutions for residential, commercial, institutional and industrial applications.
Whatever your heating, ventilating and air conditioning requirements, Modine
has the product to satisfy your needs, including:
HVAC
• Unit Heaters:
– Gas
– Hydronic
– Electric
– Oil
• Ceiling Cassettes
• Duct Furnaces
flexibility, technical expertise and
• Hydronic Cabinet Unit Heaters, Fin Tube, Convectors
fast delivery found at Modine.
• Infrared Heaters
Consult your local Modine
distributor for help in solving your
indoor air problems.
• Make-up Air Systems
• Unit Ventilators
Ventilation
• Packaged Rooftop Ventilation
School Products
• Vertical Packaged Classroom HVAC:
– DX Cooling/Heat Pump
– Water/Ground Source Heat Pump
– Horizontal/Vertical Unit Ventilators
Geothermal
• Water-to-Water
• Water-to-Air
• Combination
Specific catalogs are available for each product. Catalogs 75-136 and 75-137
provide details on all Modine HVAC equipment.
Modine Manufacturing Company
1500 DeKoven Avenue
Racine, Wisconsin 53403-2552
Phone: 1.800.828.4328 (HEAT)
www.modinehvac.com
© Modine Manufacturing Company 2015
The Modine Controls
System Advantage
Controls are one of the most important – and overlooked – components of
specialized HVAC equipment. It doesn’t matter how advanced or efficient your
HVAC products are, if they aren’t equipped with customized controls you may
not be getting the most out of your investment.
For more than 10 years, Modine Controls Systems have given end users
peace of mind in knowing their systems are equipped with a reliable, proven
OEM controls system.
The beauty of the Modine Controls System is that it is designed around the
equipment, not the other way around. Instead of building around an out-of-the-box
control system, Modine Controls Systems are designed and engineered around
the final product, ensuring maximized performance.
“We found the Modine Controls System
intuitive and straight forward. It’s comforting
to power-up ‘state of the art’ equipment and
have it perform as it was intended.”
Tom Hattaway
Controls Engineer, CMH Solutions
West Palm Beach, FL
Through a partnership with
Carel, Modine’s experienced
team of engineers program
the Modine Controls System
package at the factory, ensuring
the product is set up to deliver
optimum performance the
moment it is turned on.
Why should you select equipment
with a Modine Controls System inside?
Maximize Efficiency and Operation
• Controls that are matched to the unit versus a unit that is matched to the
limitations of a non-OEM control system
• Energy consumption reductions thanks to more efficient sequencing
and programming
Reliability
• Includes relay outputs vs. triac outputs allowing the unit to handle
electrical surges or brownouts
• Control is specifically designed for robust conditions such as those found
in classrooms or on a rooftop
• No special programs or products need to be added at the time of purchase
• The Modine Controls System gives end users everything they want in one
box from one company
Serviceability
• Modine programs the control, which means changes or updates can be
made quicker
• The “Smart Key” – a plug-in memory key that remembers your customized
program – is used for faster set-up times
• Hand-held user interface makes troubleshooting a breeze – reduces staff
time setting up the unit, reduces diagnostic time, and easier to comprehend
than flashing-light controllers
• Compatible with all major Building Management Systems such as BacNET
and LonWorks
“We installed several hundred Airedale
units with the Modine Controls System
and it’s been great. They have allowed our
staff to start-up, service, maintain and
troubleshoot any issues much quicker
than before.”
Ted Rescorla
Director of Operations
Grand Haven Area Public Schools
Grand Haven, MI
Modine Controls Systems can currently be found in products featuring the
following labels:
TM
Whether your need is an Airedale classroom HVAC unit, or an Atherion
packaged rooftop ventilation system, you have the assurance of maximized
performance thanks to the Modine Controls System.
To learn more visit www.ModineHVAC.com
or call 1-800-828-HEAT.
School service technicians need to only open the
doors of their Airedale classroom HVAC units to
have easy access to the controls.
RAISE YOUR COMFORT LEVEL
©2012 Modine Manufacturing Co.
80-162
Bringing continuous comfort to the classroom
with Modine School Systems.
Our Complete Line
of HVAC Solutions
THE TRUSTED NAME FOR COMFORTABLE
LEARNING ENVIRONMENTS.
A.B. Modine originally founded Modine Manufacturing Company on
revolutionary developments in radiator designs and technology. By 1922,
Modine moved the company into the HVAC industry with one of his
most significant inventions – the hydronic unit heater. Today
that same innovative, entrepreneurial spirit continues
through Modine’s Airedale product line.
Since 1974, Airedale has been an industry leader in
the research, design and production of heating,
ventilation and air conditioning systems for school
applications. The Airedale product line now
incorporates Modine’s near century of HVAC
experience. This new combination brings
a complete line of proven products and
unsurpassed experience to the
classroom environment.
“Modine’s Airedale product line
provides a high quality HVAC system
meeting the stringent requirements of
today’s modern education environments.”
Joe Di Cara
Di Cara | Rubino Architects
Wayne, NJ
Our single packaged vertical
units blend seamlessly into the
classroom, delivering plenty of
fresh air at low noise levels.
“Quality, factory support and a
commitment to continually
improve to meet the evolving
needs of the market set
Airedale products apart from
all other manufacturers.”
Robert Roop
CPD, LEED® AP
Peter Basso Associates, Inc.
Troy | Ann Arbor | Las Vegas | Phoenix
Denny International Middle School (Seattle, WA) was a runner-up
for the 2013 Engineering Design Award from HPAC magazine.
The school featured Airedale Sentinel vertical unit ventilators.
E.H. Wadewitz School (Racine, WI) replaced
outdated HVAC equipment in its existing structure
to optimize their high efficiency boiler and updated
building management system.
During construction of the new Rivercrest Elementary School
(Hudson, WI), Modine worked with the school district to
meet HVAC specifications.
“Modine has been a great company to
work with. They have stood by us long
after our warranty was over.”
Mark Ceo
Manager of Maintenance and Engineering
Birmingham Public Schools
Birmingham, MI
IMPROVING THE ENVIRONMENT
IN CLASSROOMS OF ALL KINDS.
As an industry leader in classroom HVAC solutions,
Modine is dedicated to actively solving air quality
problems in schools by offering systems designed
to provide a healthier and quieter learning
environment. Our school systems maintain an
effective balance between energy efficiency and
the proper amount of outside ventilation air.
Low Intensity
Infrared
Spot- or areaheating for objects
(not air) in larger
environments,
such as high
ceilings, near
open doors and
loading docks
Indirect Fired
Rooftop
(WeatherHawk)
For buildings that
require significant
space heating
and/or make-up
air; wide
performance
capabilities
We are best known for our single packaged vertical
Airedale HVAC classroom solutions. These products
are available as chilled water cooling/hot water
heating, steam heating, gas heating, DX cooling
and heat pump, and ground source (geothermal)/
water source heat pump units.
Plus, we offer a number of complementary
products, creating a one-stop-shop when it
comes to specifying an HVAC solutions provider.
This includes products such as ceiling cassettes,
under-the-window unit ventilators, hydronic
and cabinet unit heaters, fin tube radiation and
packaged rooftop units, and many more. With
sizes available to handle a diverse range of airflow
demands, Modine School Systems are the solution
for all of your HVAC needs.
“It is Airedale products
that are second to
none in exceeding
our MEP engineering
expectations. We have
a long list of satisfied
clients to show for it.”
John Urban, PE
Johnson & Urban Consulting Engineers
Holmdel, NJ
Direct Fired
Rooftop
For buildings
that require
significant
make-up air;
wide performance
capabilities;
100% efficient
Duct Furnace
Supplies heat
to an air stream
provided by other
equipment; ideal
for make-up air
Steam/Hot Water
Unit Heater
Cabinet Unit
Heater
Ideal for
commercial and
industrial apps;
horizontal and
vertical throw
available; low
cost and easy
installation
Perfect solution
for independent
heating zones,
with flexible
control and
configuration
options;
steam/hot
water heating
source
Convector
Fin Tube
Cassette
Greater
flexibility - can
be installed
recessed, wall
hung or free
standing;
steam/hot
water heating
source
Variety of styles
and enclosures
to meet any
architectural
style; steam/hot
water heating
source
Offers ductless
cooling, zone
control for better
efficiency, low
equipment/
installation
costs and
space-saving
Sentinel®
Vertical Unit
Ventilator
Operates with a
school’s central
chiller/boiler,
and available in
chilled water,
hot water/steam
or both, and
high-humidity
or draw-through
face and bypass
ClassMate® HE
Vertical DX
Cooling & Heat
Pump
ClassMate®
Features the
®
ClassMate
patentedHECF®
– Vertical
DX Cooling
coil, modulating
Pump
EC fan
motors
Highly efficient & Heat
with a
and advanced
single packaged Available
two-speed
blower R410a
and
vertical air
Highly
compressor
conditioning and compressor.
single
technologies
heat pump unit, efficient
vertical
air
for even
greater
and available withpackaged
conditioning
andand
heat
efficiencies
a two-speed
pump
unit savings
energy
R-410A
compressor
SchoolMate®
Vertical Water/
Ground Source
Heat Pump
Combines the
patented CF coil
and a ground
source heat
pump using the
natural heat sink
of the earth for
maximum
energy efficiency
Varsity™ Floor and
Ceiling Mounted
Unit Ventilators
Time-tested
solution to
bring fresh air
into classrooms,
and a design
blending in with
surroundings,
inside and out
MODINE SCHOOL SYSTEMS
MAKE THE MOST SENSE.
Our school systems are
manufactured to meet the
needs of today’s facilities.
Serviceability – Convenient modular designs save
Modine Controls Systems are engineered around the
unit, versus equipment designed around the controls,
to maximize efficiency and operation.
significant time and money thanks to the accessibility
of critical components and controls. Even annual filter
replacement and general cleaning are a snap.
Efficiency – Our units utilize the latest technology
exclusive to Modine, including our patented two-row
CF® microchannel technology and Modine Controls
System for maximum efficiency and operation. High
efficiency levels reduce energy costs, which can in turn
be administered to other critical school resources.
Noise reduction – Less background noise and fewer
distractions mean more successful classrooms.
Additional sound attenuating options are available for
all of our packaged units.
Size options – We offer multiple configurations, capacity
Patented two-row CF technology available only
through Modine provides higher efficiencies
and better performance, which means
greater comfort and energy savings.
options and product footprints to handle a wide variety
of specifications and CFM demands.
Environmentally conscious – With the R-410A refrigerant
and our expanded line of water/ground source heat
pump units, our systems help schools stay in front of
the environmental curve.
Airedale understands schools have limited space.
We have products to fit any unique situation, whether
it’s under a window, tucked into a ceiling or located in
the corner of a classroom.
Optional rear extensions are available, giving schools
the flexibility of installing new equipment without
having to create new holes in outside walls. This
illustration also features a three-way discharge
plenum atop the unit.
MAXIMIZING AIR MOVEMENT.
We offer vertical classroom solutions
that allow a variety of supply air options,
all of which assure superior classroom
air circulation to meet or exceed local
requirements.
•Ducted high wall supply – Conditioned air supplied through field-installed ductwork provides excellent supply air with low sound levels for retrofit projects
and restricted ceiling space.
•Ducted ceiling supply – Conditioned air supplied through a ducted ceiling system provides reduced sound levels and superior air distribution.
•Standard discharge plenum – Acoustically lined and painted to match the unit, these plenums distribute conditioned air at high levels for up to three directions. Ideal for tight budgets or projects with restricted ceiling space.
•Acoustic discharge plenum – Fitted with acoustic shelf and lined with acoustic foam.
•Accessory gas plenum – Available on the
ClassMate HE, this plenum provides additional heating capacity. Compatible with ducted supply.
Supply air is ventilated throughout the classroom via a
ducted ceiling system in this example.
ARCHITECTURAL AESTHETIC FREEDOM.
Outside air louvers are available in multiple
styles and colors that blend into the exterior,
allowing architectural freedom in the design
of roofs and façades.
• Single or twin louvers
• Baked enamel or clear anodized aluminum
• Over/under sill
• Through window
Our variety of louvers make it easy to
integrate products into new or
existing structures.
CLASSMATE® HE
Air Conditioning and Heat Pump School Units
Model Sizes of 24, 36, 48 and 60 Nominal MBH
Standard features
• 2" filters, MERV 8 rated
• Hot water or steam heating coil
• Two-speed scroll compressor provides
staged capacity control, enabling part
load efficiencies to be increased
• Modine Controls System
• Hot gas reheat for
dehumidification control
• ECM fan technology offers the perfect
balance between performance
and noise
• Designed and optimized for
R-410A refrigerant
Options
• Ultra-quiet door with side intake air
louvers and 2" insulation
• Hot water valve and piping packages
• Sound-reducing compressor
acoustic wrap
• Wall sleeve and rear extension
for customized solutions
• Factory supplied BACnet or
LonWorks compatible controls
• Humidity sensor
• Modulating economizer damper
providing 100% free-cooling and
minimum fresh air requirements
• Energy recovery wheel
• Aluminized steel casing with a durable
polyester powder coat paint finish
• Gas plenum
• Electric heating
• Powered exhaust
Accessories
• Discharge plenums
• Duct shrouds
• Outdoor louvers
• Side trims
• Vibration mat
CLASSMATE®
Air Conditioning and Heat Pump School Units
Model Sizes of 24, 36, 48 and 60 Nominal MBH
Standard features
• 2" filters, MERV 8 rated
• Featuring the patented CF coil for
greater cooling and heating efficiency
• Modine Controls System provides head
pressure control for hot gas reheat
• Hot water valve and piping packages
• Hermetic two-speed scroll compressor
enables part load efficiencies to be
increased
Options
Accessories
• ECM fan technology balances
performance and noise
• Sound-reducing compressor
acoustic wrap
• Wall sleeve and rear extension
for customized solutions
• Factory supplied BACnet or
LonWorks compatible controls
• Discharge plenums (acoustic
option available)
• Energy recovery wheel with up to
100% economizer capability
• Humidity sensor
• Electric heating
• Outdoor louvers
• Designed and optimized for
R-410A refrigerant
• Modulating economizer damper
providing 100% free-cooling and
minimum fresh air requirements
• Aluminized steel casing with a durable
polyester powder coat paint finish
• Available MERV 16 filtration
• Powered exhaust
• Hot water or steam heating coil
• Hot gas reheat for
dehumidification control
• Duct shrouds
• Side trims
• Vibration mat
SCHOOLMATE®
Ground Source Heat Pump and Water Source School Unit
Model Sizes of 24, 30, 36, 42, 48 and 60 Nominal MBH
Standard features
• Featuring the patented CF coil for
greater cooling and heating efficiency
• Energy efficiency rating over 24*
* Based on select integrated part load value
• Hot water valve and piping packages
Options
Accessories
• Sound-reducing compressor
acoustic wrap
• Wall sleeve and rear extension
for customized solutions
• Factory supplied BACnet or
LonWorks compatible controls
• Discharge plenums (acoustic
option available)
• ECM fan technology balances
performance and noise
• Newly designed energy recovery
ventilator allows for up to 500 CFM
of outside air
• Humidity sensor
• Aluminized steel casing with a durable
polyester powder coat paint finish
• Hot water or steam heating coil
• Hermetic two-speed scroll compressor
enables part load efficiencies to be
increased
• Designed and optimized for
R-410A refrigerant
• 2" filters, MERV 8 rated
• Modine Controls System provides head pressure control for hot gas reheat
• Electric heating
• Hot gas reheat for
dehumidification control
• Duct shrouds
• Outdoor louvers
• Side trims
• Vibration mat
SENTINEL®
School Unit Ventilator
Model Sizes of 30, 40, 50 and 60 Nominal MBH
Standard features
Options
Accessories
• Five models: Chilled water, hot
water, steam or a combination of
both chilled and hot water (twopipe and four-pipe configurations)
• Factory supplied BACnet or
LonWorks compatible controls
• Wall sleeve and rear extension
for customized solutions
• Energy recovery wheel
• Discharge plenums
• Face and Bypass
• Humidity sensor
• Three-speed switch
• Duct shrouds
• Powered exhaust
• Outdoor louvers
• Hot water and chilled water valve
and piping packages
• Side trims
• Modulating economizer damper
providing 100% free-cooling and
minimum fresh air requirements
• Aluminized steel casing with a
durable polyester powder coat
paint finish
• 2" filters, MERV 8 rated
• High Humidity (HH) unit with
outside air pre-treatment coil
• Modine Controls System
VARSITY ™
Floor and Ceiling Mounted Unit Ventilators
Model Sizes of 750, 1,000, 1,250 and 1,500 CFM
Standard features
Options
• Slopetop design
• Chilled water cooling coil
• Hot water heating coil
• Ceiling mounted design
• Modulating economizer damper
providing 100% free cooling and
minimum fresh air requirements
• Face and Bypass
Accessories
• Subbases
• 14 gauge cabinet panels
• Factory supplied BACnet or LonWorks compatible controls
• Hot water and chilled water valve
and piping packages
• Wall sleeves
• Textured, fingerprint free
hammertone finish
• DX cooling or steam
• Multiple rear extension/adapter
inlet air arrangements
• Utility compartments
• Outdoor louvers
• Modine Controls System
SLIMLINE CEILING CASSETTES
Air Conditioning, Heat Pump and Chilled Water Models
Ratings from 8,000 to 42,000 BTU/hr
Standard features
• Energy efficient, space
saving design
• Low noise level operation
• Fresh air knock-outs for ducted
connections to outside air
Accessories
• Control transformer 230V/1Ph
to 24V
• Duct collars
• R-410A air conditioning or
heat pump from 18,000 to
42,000 BTU/hr
Options
• Chilled water cooling from 8,000
to 36,000 BTU/hr
• Electric heat
• Easy installation and maintenance
• Built-in condensation pump
• Branch knock-outs for duct to
remote outlets
• Hot water heating
• Hot water coil freeze protection
• Modine Controls System
• Mechanical and digital thermostats
• Valve packages for chilled water
and hot water models
• Spare filters
• Condensing units
INDIRECT FIRED DUCT FURNACES AND MAKE-UP AIR UNITS
Indirect Gas-Fired, Indoor and Outdoor, Duct Furnace and Make-Up Air Units
Ratings from 75,000 to 1,200,000 BTU/hr, Natural or Propane Gas Airflow Ranges from 556 to 14,500 CFM
Standard features
Options/Accessories
• Available in 17 gravity, separated
combustion, or power vented
model sizes
• Downturn plenum section (outdoor)
• 80% thermally efficient
• Evaporative cooling section (outdoor)
• Aluminized steel heat exchanger,
burner, drip pan (stainless optional)
• Blower performance certified to 3.0"
W.C. external static pressure
• Single stage, two stage, or electronic
modulating gas valves
• Separate line voltage and low voltage
terminal strips options
• DX or chilled water cooling
coil section
• 1" or 2" permanent, 2" disposable,
or 2” FARR® 30/30 filters
• Building management system
compatible or master/slave gas
controls
• Two position, modulating,
or floating inlet dampers,
economizer control packages
• Totally enclosed, high efficiency,
two-speed motor options with
variable frequency drives
• Blower and motor vibration isolation
• Insulation for blower, cooling cabinet,
and/or downturn plenum, and
double wall construction
GAS-FIRED LOW INTENSITY INFRARED HEATERS
Gas-Fired, Indoor and Outdoor, Low Intensity Heating
Ratings from 50,000 to 200,000 BTU/hr
Standard features
• Natural or propane gas
• Heat-treated darkened 16 gauge
corrosion-resistant aluminized steel
heat exchanger tubes for long life
and maximum radiant heat output
• Water-resistant controls
compartment for indoor/outdoor
installation
• Rotatable gas valve for right or left
hand accessibility
• Durable, long-life, gray-green
polyester powder coat paint finish
• Enclosed burner compartment
allows burner box to be open
while manifold pressure
is adjusted
• Permanently-lubricated combustion
air blower mounted inside burner
box for quiet operation
• Side access panels for servicing
both sides of burner box
• Polished aluminum reflectors
efficiently direct radiant heat
DIRECT FIRED MAKE-UP AIR UNITS
Direct Gas-Fired, Indoor and Outdoor, Heating and Make-Up Air Units Input
Ratings Up to 7,862,000 BTU/hr, Natural or Propane Gas, Airflow Ranges from 1,600 to 60,000 CFM
Return Air Model Capable of 75% Maximum Return Air
Standard features
Options/Accessories
• 100% thermal efficiency
(92% sensible)
• Inlet hood, inlet dampers, v-bank filter
section, discharge dampers,
discharge louvers
• Fully insulated 8 gauge unpainted
G90 galvanized steel casing
(paint optional)
• Evaporative cooler, fill and drain kits
• Four full access service doors
• Two-speed motors or variable
frequency drive motor control
• Separate manifold and controls
compartments
• Compatible building management
system controls
• Terminal strip, color coded wiring
and job specific wiring
• Blower and motor spring
vibration isolation
• Motor ratings to 50HP
• Maxitrol 14, 44, or SC11 modulating
temperature controls
STEAM/HOT WATER UNIT HEATERS
Steam/Hot Water Unit Heaters
Ratings from 12,600 to 952,000 BTU/hr
Standard features
• Horizontal, vertical, or horizontal high
velocity air delivery
• Copper coil tubes with optional fin
spacing for low outlet temperatures
• Rugged construction to handle
rigorous conditions
Accessories
• Totally enclosed motors with thermal
overload protection
• Solid state speed controllers
• An electrical junction box for easy
electrical connections
• Cupronickel coil tubes on select
models for high steam pressure/
water temperatures
• Optional air deflectors
• Pipe hanger kits
• Optional finger proof fan guard
CONVECTORS
Steam/Hot Water Convectors
Ratings from 1,000 to 27,000 BTU/hr
Standard features
Options/Accessories
• Tamperproof hardware
• 20 gauge liner, 18 gauge front
• Louvered, security perforated or
aluminum bar grille inlet/outlet
front covers
• Right and/or left hand end pocket
• Heating elements available in
three nominal depths: 4" (2-tube),
6" (3-tube), or 8" (4-tube)
• 18, 16 or 14 gauge liner and/or
cover options
• Mechanically bonded aluminum fins
with integral collars for uniform
spacing and maximum heat transfer
• Optional colors per AIR13-416
• Outlet damper assembly, knob or
tamperproof operator
• Access door
FIN TUBE
Steam/Hot Water Fin Tube Radiation - Element and Enclosures
Ratings from 840 to 3,860 BTU/hr
Standard features
• Full range of enclosure styles and
sizes for the most demanding
architectural requirements
• Air discharge louvers with “pencil
proof” design
• Interlocking slip-joints for smooth
hairline joints - no fasteners required
• 3/4", 1", or 1-1/4" OD seamless
copper tube elements with fin options
Options/Accessories
• Dampers, knob or
tamperproof operator
• Aluminum bar discharge grilles
• End caps and end enclosures
• Enclosure extensions, with or
without door
• Valve compartments
• Corners, inside or outside,
90° or 135°
• Optional colors per AIR75-403
CABINET UNIT HEATERS
Steam/Hot Water Cabinet Unit Heaters
Ratings from 7,800 to 121,800 BTU/hr
Standard features
• Attractive one-piece cabinet top
and sides for rigorous conditions
• Solid state speed control with
off position
• Dampers - manual or motorized
• High capacity two-row coil
• Optional colors per AIR75-403
• Unit mounted return air thermostat
• Cabinet end pockets and sound
dampening insulation
• Disconnect switch
• Quick change permanent filters
• Access doors on WCC models
• Perma-Lap® frame for
recessed applications
• Tamperproof hardware
and/or keylocks
• Valves - two and three position
electric and modulating non-electric
• Copper tube, aluminum fin coils,
single row coil
• Blower and motor removable as a
single platform
• Aluminum bar grilles
• Duct collars
WORLD RENOWNED RESEARCH
AND DEVELOPMENT CAPABILITIES
Modine is dedicated to HVAC research and development. All of our products are
tested and proven at our state-of-the-art technical center, located in Racine, WI.
These facilities give us the capability of putting our school system technologies to
the test in simulated classroom environments. Our labs are third-party certified
and ensure our HVAC solutions deliver comfort to schools.
Split Room Climate Chambers – Dedicated air-to-air split rooms for testing DX
classroom products like the ClassMate. Meets AHRI 210/240 and 390 standards.
Geothermal Climate Chamber – Dedicated geothermal lab for our classroom geo
solutions like the SchoolMate. Meets ANSI/AHRI/ASHRAE ISO Standard 13256-1
and 13256-2.
Semi-Anechoic Sound Room – Sound is a major issue for schools. We now have
the capability to provide reliable data from our new, world-class laboratory.
Ventilation Test Cell – Capable of temperatures from -40°F to 140°F and
relative humidity of 10-90%, this cell is used for testing packaged rooftop
equipment. Meets AHRI 340/360 and CSA C747-06 standards.
Refrigeration Lab – Modine makes its own coils, including the CF coil.
These groundbreaking technologies are invented and proven here.
Heating Lab – Unitary heating products are validated here. Meets ANSI
Z83.8/CSA 2.6, ANSI Z21.47/CSA2.3 and ANSI Z83.20/CSA 2.34 standards.
Wind Tunnel – Capable of duplicating almost any location on Earth: up to 520
tons of cooling capacity; replicates 96% of the sun’s UV rays; and generates
temperatures of -20°F to 131°F. Meets AHRI 340/360 and CSA C746-06 standards.
Visit us at
ModineHVAC.com/schoolsystems
to learn more, or call 1-866-823-1631.
Follow us on Twitter @ModineHVAC
Modine Manufacturing Company
1500 DeKoven Avenue • Racine, Wisconsin 53403-2552 • P: 1-866-823-1631
©2013 Modine Manufacturing Co.
AIR75-120.4
THE MOST EFFICIENT METHOD OF
HEATING & COOLING TODAY
GEOTHERMAL SYSTEMS
WHAT IS GEOTHERMAL?
Ground source heat pumps are the most commonly applied geothermal systems today. By taking the natural heating and
cooling properties of the ground, the system creates “free energy” for a given space. Using a loop, geothermal systems
harness the renewable thermal energy stored in the ground (ground loop) or from water just below the ground’s surface
(ground water). The system then heats and cools residential and commercial spaces by using forced-air.
GEO-FIELD LOOPING OPTIONS:
Vertical Loop System
Horizontal Loop System
Pond/Lake Loop System
Open-Loop System
MODINE STANDARD PRODUCT FEATURES
Variable-Speed EC Motor – Adjusts fan speed to deliver
constant airflow, resulting in consistent, gentle air circulation.
(Applies to all water-to-air and air handling units.)
Modine Control System – Optimize performance and maintain
maximum energy efficiencies.
Dual Speed Scroll Compressor – Saves energy and provides
years of efficient, quiet and reliable performance. (Single-stage
on water-to-air 018 sized units and on all water-to-water units.)
Steel Cabinet Construction – A fully-insulated, polyester
powder-coated and corrosion-resistant cabinet.
Oversized Heat Exchangers – Designed with oversized air
coils and coaxial heat exchangers for producing increased
efficiencies and greater cost savings.
10-Year Limited Warranty on Parts*
5-Year Limited Warranty on Labor*
*Residential Products, see owner’s manual for details
MODINE CONTROL SYSTEM ADVANTAGE
Modine Controls Systems are designed and engineered for Modine Geothermal Systems, not only to ensure that each
unit will operate safely and reliably, but also to optimize performance and to maintain maximum energy efficiency.
WATER-TO-AIR RESIDENTIAL & LIGHT COMMERCIAL
High-efficiency, eco-friendly forced-air heating and cooling solutions
for the ultimate in comfort.
Available in 1.5 to 6 ton horizontal units and 2 to 6 ton vertical units
to fit virtually any residential or commercial space, such as a basement,
attic or crawlspace.
WATER-TO-WATER RESIDENTIAL & LIGHT COMMERCIAL
Reversible and/or non-reversible geothermal system options that provide
superior hot and/or chilled water performance at a fraction of the cost
of conventional systems.
Available in 3 to 12 ton sizes and engineered exclusively with the green,
performance enhancing refrigerant.
SPLIT SYSTEM/AIR-HANDLING RESIDENTIAL & LIGHT COMMERCIAL
The geothermal HVAC solution ideal for new or retrofitting a location. Both the
air coil or air handler and split mechanical sections can be easily installed when
paired together.
Choose between 2 to 6 ton models with air handler. Available in 2 to 5 ton sizes
when matched with stand-alone air coil.
GeoSync™ P-Series Water-to-Air ISO 13256-1 Performance Data
Ground Water
Cooling
Capacity
EER
Heating
Capacity
COP
Full
28,500
26.0
25,200
5.0
27,600
Part
21,700
32.0
18,800
5.3
Model
024
036
048
060
072
Ground Loop
Cooling
Capacity
EER
Heating
Capacity
COP
Cooling
Capacity
EER
19.4
20,000
4.3
26,400
16.9
31,200
5.9
21,000
26.3
15,900
4.6
19,200
18.3
23,200
6.5
Full
37,200
26.1
35,000
5.6
35,500
20.0
27,400
4.5
35,500
18.5
41,500
6.2
29,000
33.5
26,000
5.7
27,400
27.7
21,500
4.9
26,000
20.2
32,200
7.0
Full
53,500
27.2
46,200
5.4
50,700
21.6
37,300
4.4
48,500
18.0
57,500
6.2
Part
39,500
36.0
33,500
5.8
38,000
30.2
29,500
5.1
35,000
20.5
41,000
7.1
Full
67,000
24.0
61,000
4.8
61,400
18.8
48,500
4.0
61,000
16.6
74,400
5.5
Part
49,000
30.5
43,000
5.0
46,000
25.5
38,000
4.4
44,200
18.2
53,000
5.9
Full
76,000
23.5
73,000
4.4
71,500
18.1
58,000
3.7
70,500
16.2
90,000
5.0
Part
59,400
28.5
54,000
4.5
55,400
23.5
46,000
4.0
53,000
17.5
67,500
5.2
Ground Water
018
024
036
048
060
Heating
Capacity
COP
Part
F-Series Water-to-Air ISO 13251 Performance Data
Model
Water Loop
Split System ISO 13256-1 Performance Data
Ground Loop
59° F
50° F
77° F
Capacity EER Capacity COP Capacity EER
Ground Water
32° F
Capacity COP
Full 20,200
26.4 17,300
4.6
18,100
18.8
13,200
3.6
Full 25,000
20.2 23,600
4.2
24,500
16.4
19,000
3.7
Part 18,800
26.3 16,600
4.5
17,900
22.0
15,200
4.1
Full 39,500
20.0 35,100
4.2
36,800
16.6
27,800
3.7
Part 29,200
26.3 24,300
4.5
26,600
21.3
21,800
4.0
Full 49,900
21.3 47,000
4.5
47,200
16.7
36,800
3.8
Part 38,100
28.1 33,500
4.8
37,200
24.0
29,600
4.3
Full 62,300
21.5 59,700
4.5
59,500
16.9
43,700
3.6
Part 46,800
28.1 40,200
4.4
43,100
22.9
33,800
3.9
Model
024
036
048
060
072
Ground Loop
59° F
50° F
77° F
Capacity EER Capacity COP Capacity EER
32° F
Capacity COP
Full 27,700
25.8 25,500
4.7
25,800
19.7
20,000
4.0
Part 20,900
31.8 18,800
4.8
20,100
26.5
16,600
4.3
Full 41,100
23.0 37,600
4.6
38,200
17.7
29,400
3.9
Part 30,300
30.2 26,200
4.8
28,900
25.0
22,800
4.3
Full 54,000
23.7 50,200
4.6
49,800
17.9
39,200
3.9
Part 41,000
31.3 35,500
4.7
38,600
25.6
31,000
4.2
Full 66,600
22.5 64,200
4.5
61,200
17.3
50,500
3.8
Part 49,500
29.4 44,400
4.6
47,400
24.7
38,500
4.1
Full 73,600
20.9 73,700
4.1
68,900
16.2
58,300
3.5
Part 57,600
26.6 53,000
4.1
55,800
22.3
46,400
3.7
Reversible Water-to-Water ISO 13256-2 Performance Data*
Ground Water
Model
Ground Loop
59° F
50° F
77° F
32° F
Capacity EER Capacity COP Capacity EER Capacity COP
036 Full 38,500
20.1 38,600
3.6
35,100
15.1 31,200
3.0
048 Full 54,200
20.1 55,300
3.6
49,300
14.4 46,700
3.0
060 Full 62,200
21.0 62,000
3.8
58,100
16.1 49,700
3.1
066 Full 72,700
18.0 75,100
3.5
68,400
14.2 61,800
3.0
To learn more, visit
www.modinehvac.com
or call 1-877-679-4GEO (4436)
096 Full 108,400 20.1 110,600 3.6
98,600
14.4 93,400
3.0
120 Full 124,400 21.0 124,000 3.8
116,200
16.1 99,400
3.1
Follow us @ModineHVAC
See us at YouTube.com/ModineHVAC
132 Full 145,400 18.0 150,200 3.5
136,800
14.2 123,600 3.0
Modine Manufacturing Company
1500 DeKoven Avenue
Racine, Wisconsin 53403-2552
©2017 Modine Manufacturing Co.
GEO 80-104.6