Precision Plumbing Products

Oregon #1 Trap Primer Valve
TRAP PRIMER VALVES
Precision Plumbing Products
“Specify with Confidence - Install with Pride”®
“OREGON #1”
TRAP PRIMER VALVE
www.pppinc.net
NO Adjustment Required!
“... Automatically maintains
a constant water seal in floor
drain traps.”
PART NO: PO-500
The OREGON #1 Trap Primer Valve is a
diaphragm operated primer which delivers a fresh
water prime to seldom used floor drains. This primer
requires no adjustment but must be installed on a
cold fresh water line of 1 1/2” (38mm) diameter or
less. The primer valve is automatically activated when
it senses a pressure drop of 5 to 10 PSIG (35 to 70
kpa). The valve’s operating range is 35 to 75 PSIG
(245 to 525 kpa).
Inlet 1/2”
NPT (M)
(12mm BSP)
6” (153 mm)
BEST FOR USE WITH LOW FLOW FIXTURES
WHEN POTENTIAL PRESSURE DROP IS REDUCED.
AUTOMATICALLY ADJUSTS TO LINE PRESSURE WITH
PROPER DELIVERY AMOUNT.
ONE MODEL – FOR 1 TO 4 FLOOR DRAIN TRAPS.
Outlet 1/2”
NPT (F)
(12mm BSP)
2 3/4”(70mm)
“OREGON #1”
Floor Drain Trap Primer Valve Components
SPECIFICATIONS
Body, Check Valve Retainer Plate,
Float (Polypropylene), cover
Material Specification
Geon PVC M-1000 Type 1, Grade 1 molding
compound. NSF listed material #270
Check Valve Ball
#316 - Stainless Steel
Check Valve Ball Retainer
Monel Metal
Cover Screws (6)
5/8” x 10/24” Stainless Steel
Slip Joint Nut - 1/2” NPT
Chrome Plated Brass
Slip Joint Nut Washer - Neoprene Strainer
40 Mesh - Stainless Steel Wire Cloth
PROJECT SUBMITTAL
Project:
Contractor:
Engineer:
Date Submitted:
Prepared By:
COVERED BY
U.S.A. & FOREIGN
PATENT NO’s.
U.S. PATENT
4,204,556
CANADIAN PATENT
340,740
TRAP PRIMER VALVES
Oregon #1 Trap Primer Valve
TRAP PRIMER DISTRIBUTION UNITS
DISTRIBUTION UNIT DU-4 & DU-U:
A metered amount of water from the floor drain trap primer
is distributed to as many as four (4) floor drain traps by
means of the patented distribution unit. The priming valve
must have a minimum elevation of 12” inches (305mm)
above the finished floor.
Inlet
1/2” NPT (M)
(12mm)
Service
Valve
Trap Primer
Valve
DISTRIBUTION UNIT INSTALLATION:
Must be installed level.
Must be installed with clear plastic cover.
Must be installed with access for periodic inspection.
Do not subject trap primer valve to rough-in pressure test.
For further detail see information sheet specific for the
distribution units.
USE DEBRIS LOOP TO PREVENT FOREIGN
MATERIAL FROM ENTERING DIRECTLY INTO
PRIMER.
Outlet
1/2” FNPT
(12mm)
Installation
Dimension
13-1/2 ”
(350 mm)
Distribution
Unit DU-U
TRAP PRIMER VALVE
CHECK VALVE SEAL
VACUUM BREAKER
Minimum
1/2” copper
floor drain
trap
make-up
water
line. Not
supplied.
NOTE: Consult plumbing inspector
prior to installing distribution units.
THE PRIMING VALVE MUST HAVE A MINIMUM ELEVATION
OF 12” INCHES (305MM) ABOVE THE FINISHED FLOOR.
Precision Plumbing Products
Division of JL Industries, Inc.
Airport Business Center
6807 NE 79th Court, Suite E
Portland, Oregon 97218
T (503) 256-4010
F (503) 253-8165
www.pppinc.net
Rev 02/08
Download PDF