RAS
Product Specifications
ELECTRIC COOLING, R−410A SINGLE PACKAGE ROOFTOP
3 − 15 TONS (1 & 3−Phase)
BUILT TO LAST, EASY TO INSTALL AND SERVICE
• One−piece, standard efficiency electric cooling with a low profile, prewired, tested, and charged at the factory
• Field Convertible from vertical to horizontal airflow on all models. No special kit required on
036−150 models. Field accessory supply duct kit required for 180 size model only.
• Full perimeter base rail with built-in rigging adapters and fork truck slots
• Pre−painted exterior panels and primer−coated interior panels tested to 500 hours salt spray protection
• Fully insulated cabinet
• Single-stage or two stage cooling capacity control
• Single or dual scroll compressor with internal line−break overload protection
• All units have high and low pressure switches
• Two inch disposable fiberglass type return air filters in dedicated rack with tool−less filter access door
RAS036−072
• Refrigerant circuits contain a liquid line filter drier to trap dirt and moisture
• Indoor and outdoor coils constructed of aluminum fins mechanically bonded to seamless copper tubes
• Newly−designed indoor refrigerant header for easier maintenance and replacement
• Exclusive non−corrosive composite condensate pan in accordance with ASHRAE 62 Standard,
sloping design; side or center drain
• Belt drive evaporator−fan motor and pulley combinations available to meet any application
• Access panels with easy grip handles provide quick and easy access to the blower and blower
motor, control box, and compressor.
• “No−strip” screw system has superior holding power and guides screws into position while
preventing the screw from stripping the unit’s metal.
RAS090−121
• Newly designed terminal board facilitates simple safety circuit troubleshooting and simplified control box arrangement
• Outdoor temperature cooling operation range up to 115°F (46°C) and
down to 40°F ( 4°C ) using winter start kit
• Fixed orifice metering devices on all models to precisely control refrigerant flow
• Large, laminated control wiring and power wiring drawings are affixed to unit to make troubleshooting easy
• Standard, medium and high static fan motor options available
• Capable of thru−the−base or thru−the−curb electrical routing
• Single point electrical connections
WARRANTY
• 5 Year limited warranty on compressor
• 5 Year limited warranty on electric heater parts
• 1 Year limited warranty on parts
UNIT PERFORMANCE DATA − Single Stage Cooling
Use of the AHRI Certified TM Mark indicates a manufacturer’s participation
in the program. For verification of certification for individual products, go to
www.ahridirectory.org .
COOLING
UNIT
RAS036*0AA0AAA
RAS048*0AA0AAA
RAS060*0AA0AAA
RAS072*0AA0AAA
RAS091*0AA0AAA
RAS101*0AA0AAA
RAS121*0AA0AAA
Nom.
Tons
3
4
5
6
7−1/2
8−1/2
10
Net Cap.
(Btuh)
34,600
45,000
59,000
70,000
88,000
97,000
117,000
SEER
13.0
13.0
13.0
N/A
N/A
N/A
N/A
EER
11.0
11.0
10.8
11.2
11.2
11.2
11.2
Total
Power
(kW)
3.1
4.0
5.5
6.4
8.0
8.8
10.6
Unit Dimensions
HxWxL
33−3/8” x 46−3/4” x 74−3/8” (847 x 1187 x 1888)
33−3/8” x 46−3/4” x 74−3/8” (847 x 1187 x 1888)
33−3/8” x 46−3/4” x 74−3/8” (847 x 1187 x 1888)
41−3/8” x 46−3/4“ x 74−3/8” (1051 x 1187 x 1888)
41−3/8” x 59−1/2“ x 88−1/8” (1051 x 1510 x 2238)
49−3/8” x 59−1/2“ x 88−1/8” (1253 x 1510 x 2238)
49−3/8” x 59−1/2“ x 88−1/8” (1253 x 1510 x 2238)
Unit
Weight
lb. [kg]
438 [199]
494 [224]
524 [238]
607 [275]
705 [320]
845 [384]
855 [388]
UNIT PERFORMANCE DATA − Dual Stage Cooling
COOLING
Total
Power
Nom.
Net Cap.
Unit Dimensions
(kW)
Tons
(Btuh)
SEER
EER
HxWxL
UNIT
RAS090*0AA0AAA
7−1/2
83,000
N/A
11.2
7.4
41−3/8” x 59−1/2“ x 88−1/8” (1051 x 1510 x 2238)
RAS102*0AA0AAA
8−1/2
97,000
N/A
11.2
9.0
49−3/8” x 59−1/2“ x 88−1/8” (1253 x 1510 x 2238)
RAS120*0AA0AAA
10
114,000
N/A
11.3
10.1
49−3/8” x 59−1/2“ x 88−1/8” (1253 x 1510 x 2238)
RAS150*0AA0AAA
12−1/2
140,000
N/A
11.0
12.7
49−3/8” x 59−1/2“ x 88−1/8” (1253 x 1510 x 2238)
RAS180*0AA0AAA
15
174,000
N/A
11.0
15.8
57−3/8” x 63−3/8“ x 115−7/8” (1456 x 1609 x 2942)
* Indicates Unit voltage: K = 208/230−1−60, H = 208/230−3−60, L = 460−3−60, S = 575−3−60
NOTE: BASE MODEL NUMBERS LISTED. SEE MODEL NOMENCLATURE LISTING FOR ADDITIONAL OPTIONS
Unit
Weight
lb. [kg]
760 [345]
855 [388]
865 [393]
1075 [489]
1305 [593]
513 31 3209 02
02/26/13
TABLE OF CONTENTS
PAGE
MODEL NUMBER NOMENCLATURE . . . . . . . . . . . . . . . 3
FAN PERFORMANCE . . . . . . . . . . . . . . . . . . . . . . . . . . . . 56
FACTORY OPTIONS AND/OR ACCESSORIES . . . . . . . 5
ELECTRICAL INFO FOR UNITS MADE ON OR AFTER
JULY 30, 2012 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 70
AHRI COOLING RATING TABLE . . . . . . . . . . . . . . . . . . . 13
MINIMUM/MAXIMUM AIRFLOW TABLE . . . . . . . . . . . . 14
ELECTRICAL HEATER INFO FOR UNITS MADE
ON OR AFTER JULY 30, 2012 . . . . . . . . . . . . . . . . . . . . 76
SOUND PERFORMANCE TABLE . . . . . . . . . . . . . . . . . . 14
UNIT WIRE/FUSE OR BKR SIZING DATA . . . . . . . . . 105
PHYSICAL DATA . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 15
ELECTRICAL INFO FOR UNITS MADE PRIOR TO
JULY 30, 2012 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 124
CURBS & WEIGHTS DIMENSIONS . . . . . . . . . . . . . . . . 18
OPTIONAL ACCESSORY WEIGHTS . . . . . . . . . . . . . . . 29
APPLICATION DATA . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 30
COOLING TABLES . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 32
STATIC PRESSURE ADDERS . . . . . . . . . . . . . . . . . . . . . 53
OUTDOOR AIR INTAKE & EXHAUST PERF . . . . . . . . 54
ELECTRICAL HEATER INFO FOR UNITS MADE
PRIOR TO JULY 30, 2012 . . . . . . . . . . . . . . . . . . . . . . . 130
UNIT WIRE/FUSE OR BKR SIZING DATA . . . . . . . . . 148
SEQUENCE OF OPERATION . . . . . . . . . . . . . . . . . . . . 166
HOT GAS REHEAT DIAGRAMS . . . . . . . . . . . . . . . . . . 168
GUIDE SPECIFICATIONS . . . . . . . . . . . . . . . . . . . . . . . . 169
3 to 15 TON ROOFTOP UNIT FIOP CODES (Use with Model Nomenclature on next page)
NOMENCLATURE
CODE
OPTION DESCRIPTION
OPTIONS
2
Non−Fused Disconnect Switch
0A
None
4
Easy Access Hinged Panels
4B
2
5
Unpowered Convenience Outlet
AT
5
9
Supply Air Smoke Detector
BR
9
7C
2, 5
7K
2,5,9
BA
5, 9
8A
2, 9
AA
4
6C
2, 4
6D
2, 4, 5
6L
2, 4, 5, 9
7B
2, 4, 9
AB
4, 5
AJ
4, 5, 9
CH
4, 9
2
Specifications subject to change without notice.
513 31 3209 02
MODEL NOMENCLATURE (With Single Speed IFM)
MODEL SERIES
R
A
S
0
9
1
H
0
A
A
0
A
A
A
Position Number
R = Rooftop
1
2
3
4
5
6
7
8
9
10
11
12
13
14
A = Air Conditioning (Cooling Only)
H = Heat Pump
G = Gas/Electric
Type
S = Standard ASHRAE 90.1−2010 Efficiency
Efficiency
036 = 3 Tons
048 = 4 Tons
060 = 5 Tons
072 = 6 Tons
091 = 7.5 Tons (Single Compressor)
090 = 7.5 Tons (Dual Compressor)
101 = 8.5 Tons (Single Compressor)
102= 8.5 Tons (Dual Compressor)
121 = 10 Tons (Single Compressor)
120 = 10 Tons (Dual Compressor)
150 = 12.5 Tons (Dual Compressor)
180 = 15 Tons (Dual Compressor)
Nominal Cooling Capacity
K = 208/230−1−60
H = 208/230−3−60
L = 460−3−60
S = 575−3−60
0 = No Heat
Voltage
Heating Capacity (See spec sheet for actual capacity)
A = Standard Motor (3 − 15 ton)
B = High Static Motor (6 − 12.5 ton, 3 phase models only)
E = High Static, High Efficiency Motor (15 ton only)
C = Medium Static Motor (Not available on 3, 4, & 8.5 ton)
G = High Static Motor / Drive with Hot Gas Re−heat (15 Ton only)
H = High Static Motor / Drive with Hot Gas Re−heat (3 − 12.5 ton, 3 phase models only)
Motor Option
A = None
B = Economizer w/Baro−relief, OA Temp sensor
E = Economizer w/Baro−relief + CO2 Sensor, OA Temp sensor
No more factory installed economizers for
single phase
H = Economizer w/Baro−relief, enthalpy sensor
L = Economizer w/Baro−relief + CO2 Sensor, enthalpy sensor
P = 2−Position damper
Outdoor Air Options / Control (See spec sheet for details)
0A = No Options
AT = Non−powered 115v C.O.
BR = Supply Air Smoke Detector
AA = Easy Access Hinged Panels
Factory Installed Options (3 Phase Only)
A = Aluminum / Copper Cond & Evap Coil
B = Precoat Alum/Copper Cond & Alum / Copper Evap (3 phase only)
C = E−Coated Alum/Copper Cond & Alum / Copper Evap (3 phase only)
D = E−Coated Alum / Copper Cond & Evap (3 phase only)
E = Copper/Copper Cond & Alum/Copper Evap (3 phase only)
F = Copper/Copper Cond & Evap (3 phase only)
Condenser / Evaporator Coil Configuration
A = Standard Single Speed Indoor Fan Motor
Motor Type Option
Note: On single phase (K voltage code) motors, the following are not available as factory installed options: Coated or copper fin coils and Economizers or 2 position dampers.
513 31 3209 02
Specifications subject to change without notice.
3
MODEL NOMENCLATURE (With Two Speed IFM)
MODEL SERIES
R
A
S
0
9
1
H
0
A
A
0
A
A
T
Position Number
R = Rooftop
1
2
3
4
5
6
7
8
9
10
11
12
13
14
A = Air Conditioning (Cooling Only)
H = Heat Pump
G = Gas/Electric
Type
S = Standard ASHRAE 90.1−2010 Efficiency
Efficiency
090 = 7.5 Tons (Dual Compressor)
102= 8.5 Tons (Dual Compressor)
120 = 10 Tons (Dual Compressor)
150 = 12.5 Tons (Dual Compressor)
180 = 15 Tons (Dual Compressor)
Nominal Cooling Capacity
H = 208/230−3−60
L = 460−3−60
S = 575−3−60
0 = No Heat
Voltage
Heating Capacity (See spec sheet for actual capacity)
A = Standard Motor
B = High Static Motor (7.5 − 15 ton)
C = Medium Static Motor (Not available on 8.5 ton)
H = High Static Motor / Drive with Hot Gas Re−heat
Motor Option
A = None
B = Economizer w/Baro−relief, OA Temp sensor
E = Economizer w/Baro−relief + CO2 Sensor, OA Temp sensor
H = Economizer w/Baro−relief, enthalpy sensor
L = Economizer w/Baro−relief + CO2 Sensor, enthalpy sensor
U = Temp Ultra Low Leak Economizer w/Baro−relief
W = Enthalpy Ultra Low Leak Economizer w/Baro−relief
Outdoor Air Options / Control (See spec sheet for details)
0A = No Options
AT = Non−powered 115v C.O.
BR = Sup. Air Smoke Detector
AA = Easy Access Hinged Panels
Factory Installed Options (3 Phase Only)
A = Aluminum / Copper Cond & Evap Coil
B = Precoat Alum/Copper Cond & Alum / Copper Evap (3 phase only)
C = E−Coated Alum/Copper Cond & Alum / Copper Evap (3 phase only)
D = E−Coated Alum / Copper Cond & Evap (3 phase only)
E = Copper/Copper Cond & Alum/Copper Evap (3 phase only)
F = Copper/Copper Cond & Evap (3 phase only)
Condenser / Evaporator Coil Configuration
T = 2 Speed Indoor Fan Motor VFD Controller (For 2-stage units only)
4
Specifications subject to change without notice.
Motor Type Option
513 31 3209 02
Table 1 – FACTORY INSTALLED OPTIONS AND FIELD INSTALLED ACCESSORIES
CATEGORY
Cabinet
Coil Options
Humidity Control
Condenser
Protection
Controls
Economizers
& Outdoor Air
Dampers
Economizer Sensors
& IAQ Devices
Indoor Motor & Drive
Electric Heat
Low Ambient
Control
Power
Options
Roof Curbs
ITEM
Thru−the−base electrical connections
Supply Duct Cover (15 ton only)
Hinged Access Panels
Copper/Copper indoor and/or outdoor coils
Pre−coated outdoor coils
Premium, E−coated outdoor coils
Hot Gas Reheat
FACTORY
INSTALLED
OPTION
X
X
X
X
X
Condenser coil hail guard (louvered design)
Smoke detector (supply air)
Time Guard II compressor delay control circuit
Phase Monitor
Economizer IV (for electro−mechanical controlled RTUs)
Motorized 2 position outdoor−air damper
Manual outdoor−air damper
Barometric relief1
Power exhaust
Ultra Low Leak Economizer X (for 2−Speed Indoor Fan Motor
System only 090 to 150 sizes with 2 stages of cooling), vertical
supply and return air only.
Single dry bulb temperature sensors2
Single enthalpy sensors2
Differential enthalpy sensors2
CO2 sensor (wall, duct, or unit mounted)2
Multiple motor and drive packages
2−Speed Indoor Fan Motor System w/VFD controller
Electric Resistance Heaters
Single Point Kit
Winter start kit3
Head pressure controller3
Convenience outlet (unpowered)
Non−fused disconnect4
Roof curb 14” (356mm)
Roof curb 24” (610mm)
FIELD
INSTALLED
ACCESSORY
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
NOTES:
1. Included with economizer.
2. Sensors used to optimize economizer performance.
3. See application data for assistance.
4. Available on units with MOCP’s of 80 amps or less
5. All FIOP’s are 3 phase only
513 31 3209 02
Specifications subject to change without notice.
5
FACTORY OPTIONS AND/OR ACCESSORIES
Economizer (dry−bulb or enthalpy)
Economizers save money. They bring in fresh, outside air for
ventilation; and provide cool, outside air to cool your building.
This is the preferred method of low ambient cooling. When
coupled to CO2 sensors, Economizers can provide even more
savings by coupling the ventilation air to only that amount
required.
Economizers are available, installed and tested by the factory,
with either enthalpy or dry−bulb temperature inputs. There are
also models for electromechanical as well as direct digital
controllers. Additional sensors are available as accessories to
optimize the economizers.
Economizers include gravity controlled, barometric relief which
equalizes building pressure and ambient air pressures. This can
be a cost effective solution to prevent building pressurization.
CO2 Sensor
Improves productivity and saves money by working with the
economizer to intake only the correct amount of outside air for
ventilation. As occupants fill your building, the CO2 sensor
detects their presence through increasing CO2 levels, and opens
the economizer appropriately.
When the occupants leave, the CO2 levels decrease, and the
sensor appropriately closes the economizer. This intelligent
control of the ventilation air, called Demand Control Ventilation
(DCV) reduces the overall load on the rooftop, saving money.
CO2 sensors are available with the economizer, installed and
tested by the factory.
Smoke Detectors
Smoke detectors immediately shut down the rooftop unit when
smoke is detected. Supply air smoke detectors are available,
installed by the factory.
Louvered Hail Guards
Sleek, accessory louvered panels protect the condenser coil
from hail damage, foreign objects, and incidental contact.
Convenience Outlet (un−powered)
Lower service bills by including a convenience outlet in your
specification. Provides a convenient, 15 amp, 115v GFCI
receptacle.
Non−fused Disconnect
This OSHA−compliant, factory−installed, safety switch allows a
service technician to locally secure power to the rooftop.
Barometric Relief
Gravity controlled, barometric relief equalizes building pressure
and ambient air pressures. This can be a cost effective solution
to prevent building pressurization.
Power Exhaust
Superior internal building pressure control. This field−installed
accessory may eliminate the need for costly, external pressure
control fans.
6
Time Guard II Control Circuit
This accessory protects your compressor by preventing
short−cycling in the event of some other failure, prevents the
compressor from restarting for 30 seconds after stopping. Not
required with authorized commercial thermostats.
Motorized 2−Position Damper
A 2−position, motorized outdoor air damper is available as a
field installed accessory and admits up to 100% outside air.
Using reliable, gear−driven technology, the 2−position damper
opens to allow ventilation air and closes when the rooftop stops,
stopping unwanted infiltration.
Manual OA Damper
Accessory manual outdoor air dampers are an economical way
to bring in ventilation air.
2−Speed Indoor Fan Speed Motor System
The 2−Speed Indoor Fan Motor System saves energy and
installation time by utilizing a Variable Frequency Drive (VFD) to
automatically adjust the indoor fan motor speed in sequence
with the units cooling operation. Per ASHRAE 90.1 2010
standard section 6.4.3.10.b, during the first stage of cooling
operation the VFD will adjust the fan motor to provide 2/3rd of
the total cfm established for the unit. When a call for the second
stage of cooling is required, the VFD will allow the total cfm for
the unit established (100%). During the heating mode the VFD
will allow total design cfm (100%) operation and during the
ventilation mode the VFD will allow operation to 2/3rd of total
cfm.
Compared to 1−speed indoor fan motor systems, the 2−Speed
Indoor Fan Motor System can save substantial energy, 25%+/−,
versus 1−speed indoor fan motor systems.
The VFD used in the 2−Speed Indoor Fan Motor System has
soft start capabilities to slowly ramp up the speeds, thus
eliminating any high inrush air volume during initial start−up. It
also has internal over−current protection for the fan motor and a
field installed display kit that allows adjustment and in depth
diagnostics of the VFD.
This 2−Speed Indoor Fan Motor System is available on models
with 2−stage cooling operation with electromechanical or RTU
Open, Multi Protocol controls. Both space sensor and
conventional thermostats/controls can be used to provide
accurate control in any application.
The 2−Speed Indoor Fan Motor System is very flexible for initial
fan performance set up and adjustment. The standard factory
shipped VFD is pre−programmed to automatically stage the fan
speed between the first and second stage of cooling. The unit
fan performance static pressure and cfm can be easily adjusted
using the traditional means of pulley adjustments. The other
means to adjust the unit static and cfm performance is to utilize
the field installed Display Kit and adjust the frequency and
voltage in the VFD to performance requirements. In either case,
once set up, the VFD will automatically adjust the speed
between the cooling stage operations.
Specifications subject to change without notice.
513 31 3209 02
Optional Hot Gas Reheat System
Hinged Access Panels
The Hot Gas Reheat System is an all−inclusive factory−installed
option that can be ordered with any 3 phase RAS unit.
Allows access to unit’s major components with specifically
designed hinged access panels. Panels are: filters, control box,
fan motor and compressor.
This system expands the envelope of operation of our rooftop
products to provide unprecedented flexibility to meet year−round
comfort conditions.
The Hot Gas Reheat System has the industry’s only dual
dehumidification mode setting. The Hot Gas Reheat System
includes two new modes of operation.
The RAS rooftop coupled with the Hot Gas Reheat system is
capable of operating in normal design cooling mode, subcooling
mode, and hot gas reheat mode. Normal design cooling mode is
when the unit will operate under its normal sequence of
operation by cycling compressors to maintain comfort
conditions.
Winter Start Kit
The accessory winter start kit extends the low ambient limit of
your rooftop to 25_F (−4_C). The kit bypasses the low pressure
switch, preventing nuisance tripping of the low pressure switch.
Other low ambient precautions may still be prudent.
Alternate Motors and Drives
Some applications need larger horsepower motors, some need
more airflow, and some need both. Regardless of the case, your
unit has a factory installed combination to meet your application.
A wide selection of motors and pulleys (drives) are available,
factory installed, to handle nearly any application.
Thru−the−Base Connections
Subcooling mode will operate to satisfy part load type conditions
when the space requires combined sensible and a higher
proportion of latent load control. Hot Gas Reheat mode will
operate when outdoor temperatures diminish and the need for
latent capacity is required for sole humidity control. Hot Gas
Reheat mode will provide neutral air for maximum
dehumidification operation.
Thru−the−base connections, available as an accessory, are
necessary to ensure proper connection and seal when routing
wire and piping through the rooftop’s basepan and curb. These
couplings eliminate roof penetration and should be considered
for main power lines, as well as control power.
Head Pressure Controller
RAS units offer a full−line of accessory heaters. The heaters are
very easy to use / install and are pre−engineered and certified.
The motor controller is a low ambient, head pressure controller
kit that is designed to maintain the unit’s condenser head
pressure during periods of low ambient cooling operation. This
device should be used as an alternative to economizer free
cooling not when economizer usage is either not appropriate or
desired. The controller will either cycle the outdoor−fan motors
or operate them at reduced speed to maintain the unit operation,
depending on the model.
513 31 3209 02
Electric Heaters
Supply Duct Cover
This supply duct cover is required when field converting the
factory standard vertical duct supply to horizontal duct supply
configuration. One required per unit. (180 size only)
Specifications subject to change without notice.
7
ACCESSORIES − RAS036−180
ECONOMIZERS
Model Number
Description
Vertical Economizer IV with solid−state controller, gear−driven,
3−position modulating damper, spring return actuator, up to 100%
DNECOMZR020A02
barometric relief, supply and outdoor air sensors, and CO2 sensor
compatible.
Vertical Economizer IV with solid−state controller, gear−driven,
3−position modulating damper, spring return actuator, up to 100%
DNECOMZR021A03
barometric relief, supply and outdoor air sensors, and CO2 sensor
compatible.
Vertical Economizer IV with solid−state controller, gear−driven,
3−position modulating damper, spring return actuator, up to 100%
DNECOMZR062A00
barometric relief, supply and outdoor air sensors, and CO2 sensor
compatible.
Ultra Low Leak Vertical3 Economizer X with solid−state W7220
controller, gear−driven, modulating damper, spring return actuator, up
CRECOMZR069A001,2
to 100% barometric relief, supply and outdoor air sensors, and CO2
sensor compatible, for use in electro mechanical controls only.
Ultra Low Leak Vertical3 Economizer X with solid−state W7220
controller, gear−driven, modulating damper, spring return actuator, up
CRECOMZR071A001,2
to 100% barometric relief, supply and outdoor air sensors, and CO2
sensor compatible, for use in electro mechanical controls only.
Horizontal Economizer IV with solid−state controller, gear−driven,
3−position modulating damper, spring return actuator, up to 100%
DNECOMZR024A02
barometric relief, supply and outdoor air sensors, and CO2 sensor
compatible.
Horizontal Economizer IV with solid−state controller, gear−driven,
3−position modulating damper, spring return actuator, up to 100%
DNECOMZR025A02
barometric relief, supply and outdoor air sensors, and CO2 sensor
compatible.
Horizontal Economizer IV with solid−state controller, gear−driven,
3−position modulating damper, spring return actuator, up to 100%
DNECOMZR064A00
barometric relief, supply and outdoor air sensors, and CO2 sensor
compatible.
1 Economizer X cannot be installed with Economizer IV, manual damper, or motorized damper.
2 Can only be used on electrical mechanical units with 2−stage cooling and 2−speed fan control.
3 Economizer X is currently only available on vertical air flow configuration models.
Use With Model Size
036 − 072
090 − 150
180
090 − 150
180
036 − 072
090 − 150
180
ECONOMIZER SENSORS
Model Number
Description
Use With Model Size
Outdoor or Return Dry Bulb Temperature Sensor used with
DNTEMPSN002A00
Economizer IV
Electro−Mechanical control.
CO2 Sensor for use in return airstream. Also includes Aspirator Box
DNCBDIOX005A00
Economizer IV
required for Duct Mounting.
Return Air Enthalpy Sensor used with Electro−Mechanical controls,
DNENTDIF004A00
Economizer IV
use with AXB078ENT for differential enthalpy control.
AXB078ENT
Accusensor II Economizer Differential Enthalpy Control Upgrade
Economizer IV
Outdoor or return dry bulb temperature sensor used with Honeywell
CRTEMPSN005A00
Economizer X
W7220 electro−mechanical control.
Enthalpy control for W7220 controller only. (One required for single
HH57AC081
Economizer X
enthalpy, two required for differential enthalpy)
NOTE: Supply air temperature sensor (SAT and low ambient lockout switch) provided with economizer IV or economizer X.
8
Specifications subject to change without notice.
513 31 3209 02
ACCESSORIES − RAS036−180 (cont.)
POWER EXHAUST
Model Number
DNPWREXH030A01
DNPWREXH021A01
DNPWREXH022A01
DNPWREXH023A01
DNPWREXH080A00
DNPWREXH081A00
DNPWREXH028A01
DNPWREXH029A01
DNPWREXH082A00
DNPWREXH083A00
Description
Vertical Power Exhaust 208/230 volt (1 or 3 Phase)
Vertical Power Exhaust 460 volt
Vertical Power Exhaust 208/230 volt (1 or 3 Phase)
Vertical Power Exhaust 460 volt
Vertical Power Exhaust 208/230 volt
Vertical Power Exhaust 460 volt
Horizontal Power Exhaust 208/230 & 575 volt (1 or 3 Phase)
Horizontal Power Exhaust 460 volt
Horizontal Power Exhaust 208/230 & 575 volt
Horizontal Power Exhaust 460 volt
Use With Model Size
036 − 072
036 − 072
090 − 150
090 − 150
180
180
036 − 150
036 − 150
180
180
Description
Transformer for conversion from 575v to 208/230v power exhaust
applications.
Use With Model Size
Description
Use With Model Size
036 − 072
090 − 150
180
036 − 072
090 − 150
180
575V TRANSFORMER
Model Number
1171494 2
ALL
FLAT ROOF CURBS
Model Number
CRRFCURB001A01
CRRFCURB003A01
CRRFCURB074A00
CRRFCURB002A01
CRRFCURB004A01
CRRFCURB075A00
14” High Roof Curb. Ductwork attaches to the roof curb. Includes
thru−the−bottom capability.
24” High Roof Curb. Ductwork attaches to the roof curb. Includes
thru−the−bottom capability.
HAIL GUARDS
Model Number
CRLVHLGD011A00
CRLVHLGD012A00
CRLVHLGD013A00
CRLVHLGD014A00
CRLVHLGD015A00
CRLVHLGD016A00
CRLVHLGD032A00
Description
Louvered Condenser Coil Hail Guard
Louvered Condenser Coil Hail Guard
Louvered Condenser Coil Hail Guard
Louvered Condenser Coil Hail Guard
Louvered Condenser Coil Hail Guard
Louvered Condenser Coil Hail Guard
Louvered Condenser Coil Hail Guard
Use With Model Size
036
048 − 060
072
090, 091
101
102, 120, 121, 150
180
ACCESSORY KITS FOR UNITS WITH HINGED ACCESS PANELS
Model Number
CRPECONV003A00
CRPECONV004A00
CRPECONV007A00
CRHNGPNL001A00
CRHNGPNL002A00
CRHNGPNL007A00
513 31 3209 02
Description
Vertical accessory kit used with installing a vertical economizer on a
unit that has hinged access panels. Includes angle and seal strip
Vertical accessory kit used with installing a vertical economizer on a
unit that has hinged access panels. Includes angle and seal strip
Vertical & Horizontal accessory kit used with installing a 2−position
damper or vertical & horizontal economizer on a unit that has hinged
access panels. Includes angle and seal strip
Horizontal accessory kit used with installing a vertical economizer on
a unit that has hinged access panels. Includes angle and seal strip
Horizontal accessory kit used with installing a vertical economizer on
a unit that has hinged access panels. Includes angle and seal strip
Vertical & Horizontal accessory kit used with installing a 2−position
damper or vertical & horizontal economizer on a unit that has hinged
access panels. Includes angle and seal strip
Specifications subject to change without notice.
Use With Model Size
036−072
090−150
180
036−072
090−150
180
9
ACCESSORIES − RAS036−180 (cont.)
MANUAL OUTDOOR AIR DAMPERS
Model Number
CRMANDPR001A03
CRMANDPR001A02
CRMANDPR002A03
CRMANDPR002A02
CRMANDPR011A00
Description
25% Open Manual Fresh Air Damper
50% Open Manual Fresh Air Damper
25% Open Manual Fresh Air Damper
50% Open Manual Fresh Air Damper
50% Open Manual Fresh Air Damper
Use With Model Size
036 − 072
036 − 072
090 − 150
090 − 150
180
MOTORIZED OUTDOOR AIR DAMPERS
Model Number
CRTWOPOS010A00
CRTWOPOS011A00
CRTWOPOS014A00
Description
Motorized 2 position outdoor air damper (25−100% Outdoor Air)
Motorized 2 position outdoor air damper (25−100% Outdoor Air)
Motorized 2 position outdoor air damper (25−100% Outdoor Air)
Use With Model Size
036 − 072
090 − 150
180
SPECIAL − 180 SIZE SPECIFIC ASSESSORIES
Model Number
CRDISBKT001A00
CRDUCTCV002A00
Description
Disconnect Switch Bracket − Provides a pre engineered and sized
mounting bracket for applications requiring a unit mounted fused
diconnect of greater than 100 amps. Bracket assures that no damage
will occur to coils when mounting with screws and other fasteners.
Supply Duct Cover − This supply duct cover is required when field
converting the factory standard vertical duct supply to horizontal duct
supply configuration. One required per unit.
Use With Model Size
180
180
THROUGH−THE−BOTTOM/CURB POWER CONNECTION
Model Number
Description
Use With Model Size
Thru−the−bottom electrical connections and thru−the−curb gas connections. Includes a 3/4−inch diameter liquid tight conduit fitting for
CRBTMPWR001A01
036 − 072
high voltage power wires
Thru−the−bottom electrical connections and thru−the−curb gas connections. Includes a 1−1/4−inch diameter liquid tight conduit fitting for
CRBTMPWR002A01
090 − 150
high voltage power wires
Thru−the−bottom power, control, and gas connections. Includes a
3/4−inch diameter liquid tight conduit fitting for high voltage power
CRBTMPWR003A01
036 − 072
wires
Thru−the−bottom power, control, and gas connections. Includes a
1−1/4−inch diameter liquid tight conduit fitting for high voltage power
CRBTMPWR004A01
090 − 150
wires
Thru−the−bottom power, control, and gas connections. Includes a
1−1/4 inch diameter liquid tight conduit fitting for high voltage power
CRBTMPWR005A00
wires
Thru−the−bottom power, control, and gas connections. Includes a
180
1−1/2 inch diameter liquid tight conduit fitting for high voltage power
CRBTMPWR006A00
wires
Thru−the−bottom power, control, and gas connections. Includes a 2
CRBTMPWR007A00
inch diameter liquid tight conduit fitting for high voltage power wires
NOTE: Economizer IV, Economizer X, Manual Damper and 2−Position damper are all mutually exclusive and cannot be installed
together.
1. Manual dampers include hood assembly, bird screen, adjustable damper blade (to allow up to the rated outdoor air %), and bottom
panel with opening.
2. Motorized dampers include bottom panel with opening (100% two−position damper includes 30% barometric relief capability), and
adjustable damper (to allow up to the rated outdoor air %)
3. Motorized dampers will close on loss of power to the rooftop unit.
Manual and motorized dampers are not compatible with a vertical power exhaust module.
10
Specifications subject to change without notice.
513 31 3209 02
ACCESSORIES − RAS036−180 (cont.)
LOW AMBIENT CONTROLS *
Model Number
32LT900301 1
32LT900611 1
CPLOWAMB001A00
Description
Motormaster I Solid−State Variable Speed Motor Controller enables
cooling down to −20° F by varying the speed on the condenser fan.
MotorMaster I Solid−State Variable Speed Motor Controller enables
cooling down to −20° F by varying the speed on the condenser fan.
MotormasterR II Low Ambient Control − Enables cooling system to
operate down to 0° F by cycling condenser fan on and off. The control
is activated by a temperature sensor. No motor change−out required.
1171974 2
Motormaster I Compatible Condenser Fan Motor
1171975 2
Motormaster I Compatible Condenser Fan Motor
CRLOWAMB030A00 3
CRLOWAMB031A00 3
CRLOWAMB032A00 3
CRLOWAMB039A00
CRLOWAMB040A00
CRTRXKIT001A00
Motormaster V Low Ambient Kit. Mechanical cooling operation down
to −20° F (− 29° C)
Motormaster V Low Ambient Kit. Mechanical cooling operation down
to −20° F (− 29° C)
Motormaster V Low Ambient Kit. Mechanical cooling operation down
to −20° F (− 29° C).
Motormaster I Low Ambient Kit. Mechanical cooling operation down to
−20° F (− 29° C). Kit includes 3 motors, MotorMaster controller, wiring
label, and required wire ties and connectors, DNWINSTR001A00 also
required (one per refrigerant circuit)
Motormaster I Low Ambient Kit. Mechanical cooling operation down to
−20° F (− 29° C). Kit includes 3 motors, MotorMaster controller, wiring
label, and required wire ties and connectors ) 575 Volt models also
require CRTRXKIT002A00 plus DNWINSTR001A00 also required
(one per refrigerant circuit)
Motormaster I Low Ambient Control − Transformer Kit. Must be used
in conjunction with Low Ambient Controller if used on 575−3−60 volt
models.
Use With Model Size
036 − 121
208/230−1−60, 208/203−3−60,
575−3−60
036 − 121
460−3−60
036 − 121
208/230−3−60, 460−3−60 4
036 − 121
208/230−1−60, 208/230−3−60,
575−3−60
036 − 121
460−3−60
150
208/230−3−60
150
460−3−60
150
575−3−60
180
208/230−3−60
180
460−3−60
180
575−3−60
CONTROL UPGRADE KITS
Model Number
Description
Use With Model Size
2−Speed VFD display kit provides the field capability to set up points
and troubleshooting codes on the VFD controller. Can be used for any
CRDISKIT001A00
All 2−Speed VFD Controllers
associated unit with VFD.
NRTIMEGD001A00
Time Guard II
036 − 180
CRSDTEST001A00
Remote keyed attenuator / test / reset station
036 − 180
Electronic phase monitor breaks “R” control signal if trouble is detecDNWINSTR001A00
036 − 180
ted. (Allows operation down to 25°F from standard 40°F.)
CRPHASE3001A02
Phase Monitor Control
036 − 180 (3 Phase only)
CRPHASE3002A00
Phase Monitor Control
036 − 180 (575v only)
CRSTATUS001A00
Fan/Filter Status Switch − Indicator light not included
036 − 180
*See usage tables in kit instructions.
1 Requires motor change out. Sizes 036−072 require one (1) Low Ambient Controller and one (1) compatible condenser fan motor for
change−out. Sizes 090−121 require one (1) Low Ambient Controller and two (2) compatible condenser fan motors for change−out.
See Motormaster I kit instructions for capacitor replacement information.
2 Available from FAST Parts.
3 No motor change is required on these specific models.
4 One DNWINSTR001A00 also required per refrigerant circuit.
513 31 3209 02
Specifications subject to change without notice.
11
ACCESSORIES − RAS036−180 (cont.)
ELECTRIC HEATERS
Model Number
CRHEATER101A00
CRHEATER102A00
CRHEATER103B00
CRHEATER104B00
CRHEATER105A00
CRHEATER106A00
CRHEATER107A00
CRHEATER108A00
CRHEATER109A00
CRHEATER110A00
CRHEATER111A00
CRHEATER112A00
CRHEATER113A00
CRHEATER114A00
CRHEATER115A00
CRHEATER116A00
CRHEATER117A00
CRHEATER118A00
CRHEATER119A00
CRHEATER288A00
CRHEATER289A00
CRHEATER290A00
CRHEATER291A00
CRHEATER292A00
CRHEATER293A00
CRHEATER294A00
CRHEATER295A00
CRHEATER296A00
Voltage
208/230
208/230
208/230
208/230
208/230
460
460
460
460
208/230
208/230
208/230
460
460
460
460
208/230
575
575
208/230
460
575
208/230
460
575
208/230
460
575
Nominal Power (kW)
4.4
6.5
8.7
10.5
16
6
8.8
11.5
14
16
24.8
32
16.5
27.8
33
13.9
10.4
17
34
10.0
10.0
10.0
16.5
16.5
16.5
33.5
33.5
33.5
Voltage
208/230/460−3−60
208/230−3−60
208/230−1−60
208/230/460/575−3−60
208/230−3−60
460/575−3−60
208/230−3−60
208/230/460/575−3−60
208/230−3−60
460/575−3−60
208/230−3−60
208/230−3−60
Used With Model Size
072
048, 60
036, 048, 60
090, 091
090, 091
090, 091
090, 091
101, 102, 120, 121, 150, 180
101, 102, 120, 121, 150, 180
101, 102, 120, 121, 150, 180
101, 102, 120, 121, 150, 180
180
Used With Model Size
036 − 072
036 − 072
036 − 060
036 − 072
036 − 072
036 − 072
036
036 − 072
036 − 072
090 − 150
090 − 121
090 − 150
090 − 150
090 − 150
090 − 150
090 − 150
090 − 150
090 − 150
090 − 150
180
180
180
180
180
180
180
180
180
SINGLE POINT WIRING KITS
Model Number
CRSINGLE037A00
CRSINGLE038A00
CRSINGLE040A00
CRSINGLE042A00
CRSINGLE043A00
CRSINGLE044A00
CRSINGLE045A00
CRSINGLE047A00
CRSINGLE049A00
CRSINGLE050A00
CRSINGLE051A00
CRSINGLE053A00
12
Specifications subject to change without notice.
513 31 3209 02
Table 2 – AHRI COOLING RATING TABLE − Single Stage Cooling
UNIT
RAS
036
048
060
072
091
101
121
COOLING
STAGES
1
1
1
1
1
1
1
NOM.
CAPACITY
(TONS)
3
4
5
6
7.5
8.5
10
NET
COOLING
CAPACITY
(MBH)
34.6
45.0
59.0
70.0
88.0
97.0
117.0
TOTAL
POWER (KW)
3.1
4.0
5.5
6.4
8.0
8.8
10.6
SEER
13.0
13.0
13.0
−
−
−
−
EER
11.0
11.0
10.8
11.2
11.2
11.2
11.2
IEER
−
−
−
11.4
11.4
11.4
11.4
Table 3 – AHRI COOLING RATING TABLE − Two Stage Cooling
UNIT
RAS
090
102
120
150
180
COOLING
STAGES
2
2
2
2
2
NOM.
CAPACITY
(TONS)
7.5
8.5
10
12.5
15
NET
COOLING
CAPACITY
(MBH)
83.0
99.0
114.0
140.0
174.0
TOTAL
POWER (kW)
7.4
9.0
10.1
12.7
15.8
LEGEND
AHRI
− Air−Conditioning, Heating & Refrigeration Institute
ASHRAE − American Society of Heating, Refrigerating
and Air Conditioning, Inc.
EER
− Energy Efficiency Ratio
IEER
− Integrated Energy Efficiency Ratio
SEER
− Seasonal Energy Efficiency Ratio
SEER
N/A
N/A
N/A
N/A
N/A
EER
11.2
11.2
11.3
11.0
11.0
IEER WITH
1-SPEED
INDOOR FAN
MOTOR
11.7
11.7
12.2
11.2
11.5
IEER WITH
2-SPEED
INDOOR FAN
MOTOR
13.0
13.0
13.0
12.0
12.6
NOTES:
1. Rated and certified under AHRI Standard 340/360−04, as
appropriate.
2. Ratings are based on:
Cooling Standard: 80_F (27_C) db, 67_F (19_C) wb indoor air
temp and 95_F (35_C) db outdoor air temp.
IEER Standard: A measure that expresses cooling part−load
EER efficiency for commercial unitary air conditioning and heat
pump equipment on the basis of weighted operation at various
load capacities.
3. All RAS units comply with ASHRAE 90.1 2001, 2004 Energy
Standard for minimum SEER and EER requirements.
4. Where appropriate, RAS units comply with US Energy Policy
Act (2005). Refer to state and local codes.
Use of the AHRI Certified TM Mark indicates a manufacturer’s participation
in the program. For verification of certification for individual products, go to
www.ahridirectory.org .
513 31 3209 02
Specifications subject to change without notice.
13
Table 4 – MINIMUM − MAXIMUM AIRFLOWS ELECTRIC HEAT
COOLING
UNIT
RAS
036
048
060
072
090/091
101/102
120/121
150
180
Minimum
900
1200
1500
1800
2250
2550
3000
3600
4500
Maximum
1500
2000
2500
3000
3750
4250
5000
6000
7500
* Minimum electric heat CFM exceptions :
UNIT
RAS
UNIT VOLTAGE
120
208/230
150
120
208/230
150
120
460
150
090/091
101/102
575
120/121
150
ELECTRIC HEATERS
Minimum
Maximum
900
1500
1200
2000
1500
2500
1800
3000
2250*
3750
2250*
4250
3000*
5000
3000*
6000
4500
7500
HEATER KW
UNIT CONFIGURATION
REQUIRED MINIMUM
CFM
42.4
Horizontal
3200
50.0
Horizontal
3200
50.0
Horizontal or Vertical
3200
17.0
2800
Horizontal or Vertical
34.0
2350
Table 5 – SOUND PERFORMANCE TABLE
UNIT
RAS
036
048
060
072
091
090
101
102
121
120
150
180
COOLING
STAGES
1
1
1
1
1
2
1
2
1
2
2
2
A−WEIGHTED
80
81
78
78
82
82
83
82
82
82
87
87
LEGEND
dB − Decibel
Use of the AHRI Certified TM Mark indicates a manufacturer’s participation
in the program. For verification of certification for individual products, go to
www.ahridirectory.org .
14
63
90.6
90.9
84.0
88.8
90.1
85.8
91.2
88.6
88.6
89.0
87.0
87.0
125
80.9
84.6
82.2
81.8
82.6
84.3
86.4
85.0
85.0
83.1
85.2
85.2
OUTDOOR SOUND (dB)
250
500
1000
80.2
76
74.6
79.5
77.9
76.5
76.3
74.8
72.5
76.9
74.4
73.3
81.0
79.4
77.0
80.5
78.7
76.4
81.9
81.0
78.3
81.6
79.5
77.4
81.6
79.5
77.4
80.5
78.5
75.5
84.6
84.9
82.2
84.6
84.9
82.2
2000
71.3
71.1
68.8
69.8
73.0
72.7
73.9
74.1
74.1
71.6
78.4
78.4
4000
68.5
66.9
65.6
66.3
70.4
68.3
71.4
71.0
71.0
69.6
75.3
75.3
8000
63.9
62.5
61.8
62.7
66.7
65.1
67.3
66.3
66.3
69.3
72.9
72.9
NOTES:
1. Outdoor sound data is measure in accordance with AHRI
standard 270−95.
2. Measurements are expressed in terms of sound power. Do
not compare these values to sound pressure values because
sound pressure depends on specific environmental factors
which normally do not match individual applications. Sound
power values are independent of the environment and therefore
more accurate.
3. A−weighted sound ratings filter out very high and very low
frequencies, to better approximate the response of “average”
human ear. A−weighted measurements are taken in accordance
with AHRI standard 270−95.
Specifications subject to change without notice.
513 31 3209 02
Table 6 – PHYSICAL DATA (COOLING) 3 − 6 TONS
RAS036
Refrigeration System
1 / 1 / Scroll
5−10
8−11
1 / 1 / Scroll
14−2
22−5
Cu / Al
3/8” RTPF
2 / 15
5.5
3/4”
Cu / Al
3/8” RTPF
2 / 15
5.5
3/4”
Cu / Al
3/8” RTPF
4 / 15
5.5
3/4”
Cu / Al
3/8” RTPF
4 / 15
7.3
3/4”
Standard Static
1 phase
Motor Qty / Drive Type
Max BHP
RPM Range
Motor Frame Size
Fan Qty / Type
Fan Diameter (in)
1 / Belt
1.2
560−854
48
1 / Centrifugal
10 x 10
1 / Belt
1.2
560−854
48
1 / Centrifugal
10 x 10
1 / Belt
1.2
770−1175
48
1 / Centrifugal
10 x 10
−
−
−
−
−
−
Medium Static
1 phase
630 / 505
54 / 117
Motor Qty / Drive Type
Max BHP
RPM Range
Motor Frame Size
Fan Qty / Type
Fan Diameter (in)
−
−
−
−
−
−
−
−
−
−
−
−
1 / Belt
1.5
1035−1466
56
1 / Centrifugal
10 x 10
−
−
−
−
−
−
Standard Static
3 phase
1 / 1 / Scroll
1 / 1 / Scroll
8−8
10−11
14−13
16−0
Fixed Metering Device
630 / 505
630 / 505
54 / 117
54 / 117
RAS072
Motor Qty / Drive Type
Max BHP
RPM Range
Motor Frame Size
Fan Qty / Type
Fan Diameter (in)
1 / Belt
1.2
560−854
48
1 / Centrifugal
10 x 10
1 / Belt
1.2
560−854
48
1 / Centrifugal
10 x 10
1 / Belt
1.5
770−1175
48
1 / Centrifugal
10 x 10
1 / Belt
2.4
1073−1457
56
1 / Centrifugal
10 x 10
Medium Static
3 phase
630 / 505
54 / 117
RAS060
Motor Qty / Drive Type
Max BHP
RPM Range
Motor Frame Size
Fan Qty / Type
Fan Diameter (in)
−
−
−
−
−
−
−
−
−
−
−
−
1 / Belt
2.4
1035−1466
56
1 / Centrifugal
10 x 10
1 / Belt
2.9*
1173−1518
56
1 / Centrifugal
10 x 10
High Static
3 phase
# Circuits / # Comp. / Type
Refrig. R−410A)charge (lbs−oz)
Hot Gas Reheat Refrig. R−410A charge (lbs−oz)
Metering Device
High−press. Trip / Reset (psig)
Low−press. Trip / Reset (psig)
Evap. Coil
Material
Coil type
Rows / FPI
Total Face Area (ft2)
Condensate Drain Conn. Size
Evap. Fan and Motor
RAS048
Motor Qty / Drive Type
Max BHP
RPM Range
Motor Frame Size
Fan Qty / Type
Fan Diameter (in)
1 / Belt
2.4
1035−1466
56
1 / Centrifugal
10 x 10
1 / Belt
2.4
1035−1466
56
1 / Centrifugal
10 x 10
1 / Belt
2.9
1303−1687
56
1 / Centrifugal
10 x 10
1 / Belt
3.7
1474−1788
56
1 / Centrifugal
10 x 10
Material
Coil type
Rows / FPI
Total Face Area (ft2)
Cu / Al
3/8” RTPF
1 / 17
14.6
Cu / Al
3/8” RTPF
2 / 17
16.5
Cu / Al
3/8” RTPF
2 / 17
16.5
Cu / Al
3/8” RTPF
2 / 17
21.3
Material
Rows / FPI
Total Face Area (ft2)
Cu / Al
1 / 17
3.9
Cu / Al
2 / 17
3.9
Cu / Al
2 / 17
3.9
Cu / Al
2 / 17
5.2
1/ Direct
1/4 / 1100
22
1/ Direct
1/4 / 1100
22
1/ Direct
1/4 / 1100
22
1/ Direct
1/4 / 1100
22
2 / 16 x 25 x 2
1 / 20 x 24 x 1
2 / 16 x 25 x 2
1 / 20 x 24 x 1
2 / 16 x 25 x 2
1 / 20 x 24 x 1
4 / 16 x 16 x 2
1 / 20 x 24 x 1
Cond. Coil
Hot Gas Reheat Coil
Cond. fan / motor
Qty / Motor Drive Type
Motor HP / RPM
Fan diameter (in)
Filters
RA Filter # / Size (in)
OA inlet screen # / Size (in)
* RTPF − Round Tube Plate Fin Coil Design
513 31 3209 02
Specifications subject to change without notice.
15
Table 6 − (Cont.) PHYSICAL DATA (COOLING) 7.5 − 8.5 TONS
RAS091
RAS090
RAS101
RAS102
1 / 1 / Scroll
13 − 12
2 / 2 / Scroll
8−5/8−2
1 / 1 / Scroll
15 − 4
2 / 2 / Scroll
10 − 5 / 10 − 12
−
13 − 3 / 13 − 3
−
16 − 13 / 16 − 13
Refrigeration System
630 / 505
54 / 117
Fixed Metering Device
630 / 505
630 / 505
54 / 117
54 / 117
630 / 505
54 / 117
Cu / Al
3/8” RTPF
3 / 15
8.9
3/4”
Cu / Al
3/8” RTPF
3 / 15
8.9
3/4”
Cu / Al
3/8” RTPF
3 / 15
11.1
3/4”
Cu / Al
3/8” RTPF
3 / 15
11.1
3/4”
−
−
−
−
Cu / Al
3/8” RTPF
2 / 17
6.3
−
−
−
−
Cu / Al
3/8” RTPF
2 / 17
8.4
Standard Static
3 phase
Motor Qty / Drive type
Max BHP
RPM range
motor frame size
Fan Qty / Type
Fan Diameter (in)
1 / Belt
1.7
489−747
56
1 / Centrifugal
15 x 15
1 / Belt
1.7
518−733
56
1 / Centrifugal
15 x 15
1 / Belt
1.7
518−733
56
1 / Centrifugal
15 x 15
Medium Static
3 phase
Motor Qty / Drive type
Max BHP
RPM range
motor frame size
Fan Qty / Type
Fan Diameter (in)
1 / Belt
2.9
733−949
56
1 / Centrifugal
15 x 15
1 / Belt
1.7
489−747
56
1 / Centrifugal
15 x 15
0
1 / Belt
2.9
733−949
56
1 / Centrifugal
15 x 15
−
−
−
−
−
−
−
−
−
−
−
−
High Static
3 phase
# Circuits / # Comp. / Type
RTPF models R−410a charge A/B (lbs − oz)
Hot Gas Reheat RTPF models R−410a charge A/B
(lbs − oz)
Metering device
High−press. Trip / Reset (psig)
Low−press. Trip / Reset (psig)
Evap. Coil
Material
Coil type
Rows / FPI
total face area (ft2)
Condensate drain conn. size
Hot Gas Reheat Coil
Material
Coil type
Rows / FPI
total face area (ft2)
Evap. fan and motor
Motor Qty / Drive type
Max BHP
RPM range
motor frame size
Fan Qty / Type
Fan Diameter (in)
1 / Belt
4.7
909−1102
145TY
1 / Centrifugal
15 x 15
1 / Belt
4.7
909−1102
145TY
1 / Centrifugal
15 x 15
1 / Belt
3.7
838−1084
56
1 / Centrifugal
15 x 15
1 / Belt
3.7
838−1084
56
1 / Centrifugal
15 x 15
Material
Coil type
Rows / FPI
Total Face Area (ft2)
Cu / Al
3/8” RTPF*
2 / 17
20.5
Cu / Al
3/8” RTPF*
2 / 17
20.5
Cu / Al
3/8” RTPF*
2 / 17
21.4
Cu / Al
3/8” RTPF*
2 / 17
25.1
Qty / Motor drive type
Motor HP / RPM
Fan diameter (in)
2 / direct
1/4 / 1100
22
2 / direct
1/4 / 1100
22
2 / direct
1/4 / 1100
22
2 / direct
1/4 / 1100
22
4 / 16 x 20 x 2
1 / 20 x 24 x 1
4 / 16 x 20 x 2
1 / 20 x 24 x 1
4 / 20 x 20 x 2
1 / 20 x 24 x 1
4 / 20 x 20 x 2
1 / 20 x 24 x 1
Cond. Coil
Cond. fan / motor
Filters
RA Filter # / size (in)
OA inlet screen # / size (in)
* RTPF − Round Tube Plate Fin Coil Design
16
Specifications subject to change without notice.
513 31 3209 02
Table 6 − (Cont.) PHYSICAL DATA (COOLING) 10 − 15 TONS
RAS121
RAS120
RAS150
RAS180
Refrigeration System
# Circuits / # Comp. / Type
RTPF models R−410a charge A/B (lbs − oz)
Hot Gas Reheat RTPF models R−410a charge A/B (lbs − oz)
Metering device
High−press. Trip / Reset (psig)
Low−press. Trip / Reset (psig)
1 / 1 / Scroll
20 − 0 / −
− /−
630 / 505
54 / 117
2 / 2 / Scroll
2 / 2 / Scroll
10 − 5 / 10 − 3
11 − 0 / 11 − 6
16 − 0 / 16 − 0
17 − 0 / 18 − 3
Fixed Metering Device
630 / 505
630 / 505
54 / 117
54 / 117
2 / 2 / Scroll
15−14/16−12
−/−
630 / 505
54 / 117
Evap. Coil
Material
Coil type
Rows / FPI
total face area (ft2)
Condensate drain conn. size
Cu / Al
3/8” RTPF
4 / 15
11.1
3/4”
Cu / Al
3/8” RTPF
4 / 15
11.1
3/4”
Cu / Al
3/8” RTPF
4 / 15
11.1
3/4”
Cu / Al
3/8” RTPF
3 / 15
17.5
3/4”
1 / Belt
1 / Belt
1 / Belt
1 / Belt
Evap. fan and motor
Motor Qty / Drive type
Standard Static
3 phase
Max BHP
RPM range
motor frame size
2.4
2.4
2.9
2.9
591−838
591−838
652−843
507−676
56
56
56
56
1 / Centrifugal
1 / Centrifugal
1 / Centrifugal
1 / Centrifugal
15 x 15
15 x 15
15 x 15
18 x 18
Motor Qty / Drive type
Max BHP
RPM range
motor frame size
Fan Qty / Type
Fan Diameter (in)
1 / Belt
3.7
838−1084
56
1 / Centrifugal
15 x 15
1 / Belt
3.7
838−1084
56
1 / Centrifugal
15 x 15
1 / Belt
3.7
838−1084
56
1 / Centrifugal
15 x 15
1 / Belt
3.7
627−851
56
1 / Centrifugal
18 x 18
Motor Qty / Drive type
Max BHP
RPM range
motor frame size
Fan Qty / Type
Fan Diameter (in)
1 / Belt
4.7
1022−1240
14
1 / Centrifugal
15 x 15
1 / Belt
4.7
1022−1240
14
1 / Centrifugal
15 x 15
1 / Belt
4.7
1022−1240
14
1 / Centrifugal
15 x 15
1 / Belt
6.1
776−955
S184T
1 / Centrifugal
18 x 18
Motor Qty / Drive type
-
-
-
1 / Belt
Max BHP
-
-
-
6.1
RPM range
-
-
-
776-955
motor frame size
-
-
-
S184T
Fan Qty / Type
-
-
-
1 / Centrifugal
Fan Diameter (in)
-
-
-
18 x 18
Material
Coil type
Rows / FPI
total face area (ft2)
Cu / Al
3/8" RTPF
2 / 17
25.1
Cu / Al
3/8" RTPF
2 / 17
25.1
Cu / Al
3/8" RTPF
3 / 17
25.1
Cu / Al
3/8" RTPF
2/17
2 @ 23.1
Qty / Motor drive type
Motor HP / RPM
Fan diameter (in)
2 / direct
1/4 / 1100
22
2 / direct
1/4 / 1100
22
1 / direct
1 / 1175
30
3 / direct
1/4 / 1100
22
RA Filter # / Size (in)
4 / 20 x 20 x 2
4 / 20 x 20 x 2
4 / 20 x 20 x 2
OA inlet screen # / Size (in)
1 / 20 x 24 x 1
1 / 20 x 24 x 1
1 / 20 x 24 x 1
6 / 18 x 24 x 2
V2 / 24 x 27 x 1
H1 / 30 x 39 x 1
Fan Qty / Type
High Static
High Efficiency
3 phase *
High Static
3 phase
Medium Static
3 phase
Fan Diameter (in)
Cond. Coil
Cond. fan / motor
Filters
* RTPF − Round Tube Plate Fin Coil Design
513 31 3209 02
Specifications subject to change without notice.
17
BASE UNIT DIMENSIONS − RAS036−072
036
048
060
072
18
Specifications subject to change without notice.
513 31 3209 02
WEIGHT & CLEARANCE DIMENSIONS − RAS036−072 (cont.)
UNIT
RAS036
RAS048
RAS060
RAS072
Corner
Weight
A
LBS
KG
108
49
122
55
130
59
150
68
BASE UNIT
WEIGHT
LBS
KG
438
199
494
224
524
238
607
275
Corner
Weight
B
LBS
KG
115
52
130
59
138
63
160
73
Corner A
Corner
Weight
C
LBS
KG
110
50
125
57
132
60
153
69
Corner
Weight
D
LBS
KG
104
47
117
53
124
56
144
65
Center of Gravity
In [mm]
X
Y
Z
38 [965] 22 [559] 17-1/4 [438]
38 [965] 22 [559] 17-1/2 [445]
38 [965] 22 [559] 17-3/4 [451]
38 [965] 22 [559] 20-3/4 [527]
Corner B
Y
Z
Corner D
X
Corner C
UNIT CLEARANCES
LOC
DIMENSION
48” (1219 mm)
18” (457 mm)
18” (457 mm)
12” (305 mm)
42” (1067 mm)
36” (914 mm)
Special
36” (914 mm)
18” (457 mm)
48” (1219 mm)
42” (1067 mm)
36” (914 mm)
Special
A
B
C
D
CONDITION
Unit disconnect is mounted on panel
No disconnect, convenience outlet option
Recommended service clearance
Minimum clearance
Surface behind servicer is grounded (e.g., metal, masonry wall)
Surface behind servicer is electrically non−conductive (e.g., wood, fiberglass)
Check for sources of flue products within 10−ft of unit fresh air intake hood
Side condensate drain is used
Minimum clearance
No flue discharge accessory installed, surface is combustible material
Surface behind servicer is grounded (e.g., metal, masonry wall, another unit)
Surface behind servicer is electrically non−conductive (e.g., wood, fiberglass)
Check for adjacent units or building fresh air intakes within 10−ft of this unit’s flue outlet
C
D
B
513 31 3209 02
A
Specifications subject to change without notice.
19
ROOF CURB DETAILS − RAS036−072
Roof Curb Accessory
CRRFCURB001A01
CRRFCURB002A01
Connector Pkg. Acc.
CRBTMPWR001A01
CRBTMPWR003A01
A
1' 2 “ [356]
2' 0” [610]
Unit Size
RAS036-072
Gas Connection Type
Thru the Curb
Thru the Bottom
NOTES:
1. Roofcurb accessory is shipped disassembled.
2. Insulated panels, 1” thick polyurethane foam, 1−3/4# density.
3. Dimensions in. [ ] in millimeters.
4. Roofcurb 16ga steel.
5. Attach ductwork to curb (Flanges of duct rest on curb)
6. Service clearance 4’ on each side.
7.
Direction of airflow.
8. Connector pkg. CRBTMPWR001A01 is for thru−the−curb gas connections.
Pkg. CRBTMPWR003A01 is for thru−the−bottom gas connections.
Gas
[19] NPT
1/2” [12.7] NPT
3/ ”
4
Power
3/ ”
4
[19] NPT
Control
1/ ”
2
[12.7] NPT
Accessory Power
1/ ”
2
[12.7] NPT
0’−0 1/4”
[6.3]
13-7/8”
20-1/4”
Supply Air
13-5/8”
32-1/16”
Return Air
A
5’−7 1/8”
[1705]
3’−0 15/16”
[938]
20
Specifications subject to change without notice.
513 31 3209 02
BASE UNIT DIMENSIONS − RAS090−121
Optional Economizer Hood
091
41−1/4
[1048]
33−3/4
[857]
15−7/8
[403]
101
49−3/8
[1253]
36−3/8
[925]
27−7/8
[708]
121
49−3/8
[1253]
36−3/8
[925]
15−7/8
[403]
090
41−1/4
[1048]
49−3/8
[1253]
33−3/4
[857]
36−3/8
[925]
15−7/8
[403]
15−7/8
[403]
49−3/8
[1253]
36−3/8
[925]
15−7/8
[403]
102
120
513 31 3209 02
Specifications subject to change without notice.
21
WEIGHT & CLEARANCE DIMENSIONS − RAS090−121 (cont.)
UNIT
RAS091
RAS101
RAS121
RAS090
RAS102
RAS120
BASE UNIT
WEIGHT
LBS
KG
705
320
845
384
855
388
760
345
855
388
865
393
Corner
Weight
A
LBS
KG
172
78
206
94
210
95
158
72
223
101
225
102
Corner
Weight
B
LBS
KG
142
65
167
76
180
82
155
70
171
77
173
79
Corner A
Corner
Weight
C
LBS
KG
177
80
212
96
215
98
222
101
200
91
203
92
Corner
Weight
D
LBS
KG
214
97
261
119
250
114
225
102
261
119
264
120
Center of Gravity
In [mm]
X
Y
Z
40 [1013] 33 [838]
21 [540]
40 [1003] 33 [845]
24 [610]
41 [1035] 32 [822]
25 [641]
44 [1111] 35 [889]
20 [508]
38 [975]
32 [816]
19 [486]
38 [975]
32 [816]
19 [486]
Corner B
Z
Y
Corner D
Corner C
X
UNIT CLEARANCES
LOC
A
B
C
D
DIMENSION
48” (1219 mm)
36” (914 mm)
18” (457 mm)
18” (457 mm)
12” (305 mm)
36” (914 mm)
12” (305 mm)
Special
36” (914 mm)
18” (457 mm)
42” (1067 mm)
36” (914 mm)
CONDITION
Unit disconnect is mounted on panel
If dimension−B is 12”
No disconnect, convenience outlet option
Recommended service clearance (use electric screwdriver)
Minimum clearance (use manual ratchet screwdriver)
Unit has economizer
If dimension−A is 36”
Check for sources of flue products within 10−ft of unit fresh air intake hood
Side condensate drain is used
Minimum clearance
Surface behind servicer is grounded (e.g., metal, masonry wall, another unit)
Surface behind servicer is electrically non−conductive (e.g., wood, fiberglass)
C
D
B
22
A
Specifications subject to change without notice.
513 31 3209 02
ROOF CURB DETAILS − RAS090 − 150
Roof Curb Accessory
CRRFCURB003A01
CRRFCURB004A01
Connector Pkg. Acc.
CRBTMPWR002A01
CRBTMPWR004A01
A
1' 2 “ [356]
2' 0” [610]
NOTES:
1. Roofcurb accessory is shipped disassembled.
2. Insulated panels, 1” thick polyurethane foam, 1−3/4# density.
3. Dimensions in. [ ] in millimeters.
4. Roofcurb 16ga steel.
5. Attach ductwork to curb (Flanges of duct rest on curb)
6. Service clearance 4’ on each side.
7.
Direction of airflow.
8. Connector pkg. CRBTMPWR002A01 is for thru−the−curb gas connections.
Pkg. CRBTMPWR004A01 is for thru−the−bottom gas connections.
Unit Size
RAS090-150
Gas Connection Type
Thru the Curb
Thru the Bottom
Gas
3/ ”
4
[19] NPT
Power
1l-1/4”
[31.7] NPT
Control
[12.7]
NPT
Accessory Power
1/ ”
2
1/ ”
2
[12.7] NPT
0’−3 516”
[84.0]
15-11/16”
[385]
31-3/8”
Supply Air
15-5/16”
40-1/16”
A
Return Air
6’−6”
[84.0]
4'-1 3/4”
[1264]
513 31 3209 02
Specifications subject to change without notice.
23
BASE UNIT DIMENSIONS − RAS150
49-3/8
[1253]
28-3/4
[731]
150
24
Specifications subject to change without notice.
15-7/8
[403]
513 31 3209 02
BASE UNIT DIMENSIONS − RAS150
RAS150
1075
489
340
155
155
70
181
82
399
181
27-1/2 [721]
32 [813]
20-1/2 [523]
C
D
B
A
Service Clearance
LOC
A
B
C
D
513 31 3209 02
DIMENSION
48” (1219 mm)
18” (457 mm)
18” (457 mm)
12” (305 mm)
42” (1067 mm)
36” (914 mm)
Special
36” (914 mm)
18” (457 mm)
42” (1067 mm)
36” (914 mm)
CONDITION
Unit disconnect is mounted on panel
No disconnect, convenience outlet option
Recommended service clearance
Minimum clearance
Surface behind servicer is grounded (e.g., metal, masonry wall)
Surface behind servicer is electrically non-conductive (e.g., wood, fiberglass)
Check for sources of flue products within 10-ft of unit fresh air intake hood
Side condensate drain is used
Minimum clearance
Surface behind servicer is grounded (e.g., metal, masonry wall, another unit)
Surface behind servicer is electrically non-conductive (e.g., wood, fiberglass)
Specifications subject to change without notice.
25
C101143
BASE UNIT DIMENSIONS − RAS180
26
Specifications subject to change without notice.
513 31 3209 02
BASE UNIT DIMENSIONS − RAS180
RAS180
C101116
513 31 3209 02
Specifications subject to change without notice.
27
ROOF CURB DETAILS − RAS180
28
Specifications subject to change without notice.
513 31 3209 02
OPTION / ACCESSORY WEIGHTS
OPTION / ACCESSORY
Hot Gas Reheat
Power Exhaust - vertical
Power Exhaust - horizontal
Economizer (IV or X)
Two Position damper
Manual Dampers
Hail Guard (louvered)
Cu/Cu Condenser Coil1
Cu/Cu Cond. & Evaporator Coils1
Roof Curb (14-in. curb)
Roof Curb (24-in. curb)
CO2 sensor
Electric Heater
Single Point Kit
Optional Indoor Motor / Drive
Motor Master Controller
Supply Smoke Detector
Non-Fused Disconnect
Non-Powered Convenience outlet
Enthalpy Sensor
Differential Enthalpy Sensor
2 Speed Indoor Fan Motor System
with VFD
OPTION / ACCESSORY WEIGHTS
Unit Size (ton)
3
4
5
6
7.5
8.5
10
12.5
lb kg lb kg lb kg lb kg lb kg lb kg lb kg lb kg
15
7
23 10 25 11 29 13 38 17 47 21 57 21 47 21
50 23 50 23 50 23 50 23 75 34 75 34 75 34 75 34
30 14 30 14 30 14 30 14 30 14 30 14 30 14 30 14
50 23 50 23 50 23 50 23 75 34 75 34 75 34 75 34
39 18 39 18 39 18 39 18 58 26 58 26 58 26 58 26
12
5
12
5
12
5
12
5
18
8
18
8
18
8
18
8
16
7
16
7
16
7
16
7
34 15 34 15 34 15 34 15
6
3
13
6
13
6
15
7
12
5
23 10 23 10 23 10
12
5
19
9
21 10 26 12 25 11 49 22 49 22 49 22
115 52 115 52 115 52 115 52 143 65 143 65 143 65 143 65
197 89 197 89 197 89 197 89 245 111 245 111 245 111 245 111
5
2
5
2
5
2
5
2
5
2
5
2
5
2
5
2
30 14 30 14 30 14 30 14 45 20 45 20 45 20 45 20
10
5
10
5
10
5
10
5
12
5
12
5
12
5
15
7
10
5
10
5
10
5
10
5
15
7
15
7
15
7
15
7
35 16 35 16 35 16 35 16 35 16 35 16 35 16 40 18
5
2
5
2
5
2
5
2
5
2
5
2
5
2
5
2
15
7
15
7
15
7
15
7
15
7
15
7
15
7
15
7
5
2
5
2
5
2
5
2
5
2
5
2
5
2
5
2
2
1
2
1
2
1
2
1
2
1
2
1
2
1
2
1
3
1
3
1
3
1
3
1
3
1
3
1
3
1
3
1
-
-
-
-
-
-
-
-
20
9
20
9
20
9
20
9
15
lb kg
57 26
85 39
75 34
115 52
65 29
25 11
45 20
190 86
280 127
180 82
255 116
5
2
25 11
25 11
45 20
35 16
5
2
15
7
5
2
2
1
3
1
20
9
NOTE: Where multiple variations are available, the heaviest combination is listed.
1
Where Available
513 31 3209 02
Specifications subject to change without notice.
29
APPLICATION DATA
Min operating ambient temp (cooling):
Low ambient applications
In mechanical cooling mode, your rooftop can safely operate
down to an outdoor ambient temperature of 25_F (−4_C), with
an accessory winter start kit; 40_F (4_C) standard min operating
temperature. It is possible to provide cooling at lower outdoor
ambient temperatures by using less outside air, economizers,
and/or accessory low ambient kits.
The optional economizer can adequately cool your space by
bringing in fresh, cool outside air. In fact, when so equipped,
accessory low−ambient kit may not be necessary. In low
ambient conditions, unless the outdoor air is excessively humid
or contaminated, economizer−based “free cooling” is the
preferred less costly and energy conscious method.
Max operating ambient temp (cooling):
In low ambient applications where outside air might not be
desired (such as contaminated or excessively humid outdoor
environments), your rooftop can operate to ambient
temperatures down to −20_F (−29_C) using the recommended
accessory Motormaster low ambient controller.
The maximum operating ambient temperature for cooling mode
is 115_F (46_C). While cooling operation above 115_F (46_C)
may be possible, it could cause either a reduction in
performance, reliability, or a protective action by the unit’s
internal safety devices.
Min and max airflow (heating and cooling):
To maintain safe and reliable operation of your rooftop, operate
within the cooling airflow limits. Operating above the max may
cause blow−off, undesired airflow noise, or airflow related
problems with the rooftop unit. Operating below the min may
cause problems with coil freeze−up.
Airflow:
All units are draw−though in cooling mode.
Outdoor air application strategies:
Economizers reduce operating expenses and compressor run
time by providing a free source of cooling and a means of
ventilation to match application changing needs. In fact, they
should be considered for most applications. Also, consider the
various economizer control methods and their benefits, as well
as sensors required to accomplish your application goals.
Please contact your local sales representative for assistance.
Motor limits, break horsepower (BHP):
Due to the internal unit design, air path, and specially designed
motors, the full horsepower (maximum continuous BHP) band,
as listed in Table 6, can be used with the utmost confidence.
There is no need for extra safety factors, the motors are
designed and rigorously tested to use the entire, listed BHP
range without either nuisance tripping or premature motor
failure.
Sizing a rooftop
Bigger isn’t necessarily better. While an air conditioner needs to
have enough capacity to meet the design loads, it doesn’t need
excess capacity. In fact, excess capacity typically results in very
poor partload performance and humidity control.
Using higher design temperatures than ASHRAE recommends
for your location, adding “safety factors” to the calculated load,
are all signs of oversizing air conditioners. Oversizing the air
conditioner leads to short cycling ( quick on−off cycles ) which
results in poor humidity control, reduced efficiency, higher utility
bills, larger indoor temperature swings, excessive noise, and
increased wear and tear on the air conditioner.
Rather than oversizing an air conditioner, engineers should
“right−size” or even slightly undersize air conditioners. Correctly
sizing an air conditioner controls humidity better; promotes
efficiency; reduces utility bills; extends equipment life, and
maintains even, comfortable temperatures. Please contact your
local representative for assistance.
30
Winter start
A winter start kit extends the low ambient limit of your rooftop to
25_F (−4_C). The kit bypasses the low pressure switch,
preventing nuisance tripping of the low pressure switch. Other
low ambient precautions may still be prudent.
2−speed indoor fan motor with Variable
Frequency Drive (VFD)
The 2−Speed Indoor Fan Motor System utilizes a Variable
Frequency Drive (VFD) to automatically adjust the indoor fan
motor speed in sequence with the units cooling operation. Per
ASHRAE 90.1 2010 standard section 6.4.3.10.b, during the first
stage of cooling operation the VFD will adjust the fan motor to
provide 2/3rd of the total cfm established for the unit. When a
call for the second stage of cooling is required, the VFD will
allow the total cfm for the unit established (100%). During the
heating mode, the VFD will allow total design cfm (100%)
operation and during the ventilation mode the VFD will allow
operation to 2/3rd of total cfm.
The VFD used in the 2−Speed Indoor Fan Motor System has
soft start capabilities to slowly ramp up the speeds, thus
eliminating any high inrush air volume during initial start−up. It
also has internal over current protection for the fan motor and a
field installed display kit that allows adjustment and in depth
diagnostics of the VFD.
This 2−Speed Indoor Fan Motor System is available on models
with 2−stage cooling operation with electrical mechanical or RTU
Open (multi Protocol) controls. Both space sensor and
conventional thermostats/controls can be used to provide
accurate control in any application.
The 2−Speed Indoor Fan Motor System is very flexible for initial
fan performance set up and adjustment. The standard factory
shipped VFD is pre programmed to automatically stage the fan
speed between the first and second stage of cooling. The unit
fan performance static pressure and cfm can be easily adjusted
using the traditional means of pulley adjustments. The other
means to adjust the unit static and cfm performance is to utilize
the field installed display module and adjust the frequency and
voltage in the VFD to required performance requirements. In
either case, once set up the VFD will automatically adjust the
speed between the cooling stage operation.
Specifications subject to change without notice.
513 31 3209 02
SELECTION PROCEDURE (WITH RAS072 EXAMPLE)1
I.
II.
III.
IV.
Determine cooling and heating loads.
Given:
Mixed air drybulb
80_F (27_C)
Mixed air wetbulb
67_F (19_C)
Ambient drybulb
95_F (35_C)
69.0 MBH
TCLoad
SHCLoad
51.0 MBH
Vertical supply air
2100 CFM
Heating load
85.0 MBH
External static pressure
0.66 in.wg
Electrical characteristics
230−3−60
Make an initial guess at cooling tons.
Refrig. tons = TCLoad / 12 MBH per ton
Refrig. tons = 69.0 / 12 = 5.75 tons
In this case, start by looking at the RAS072.
Look up the rooftop’s TC and SHC.
Table 7 shows that, at the application’s supply air
CFM, mixed air and ambient temperatures, the
RAS072 supplies:
TC = 73.7 MBH
SHC = 54.4 MBH.
Calculate the building latent heat load.
LHCLoad = TCLoad − SHCLoad
LHCLoad = 69.0 MBH − 51.0 MBH = 18.0 MBH
LEGEND
BHP
—
FLA
—
LC
—
LRA
—
MBH
—
MCA
—
MOCP —
RPM
—
RTU
—
SHC
—
TC
—
Break horsepower
Full load amps
Latent capacity
Lock rotor amp
(1,000) BTUH
Min. circuit ampacity
Max. over-current protection
Revolutions per minute
Rooftop unit
Sensible heat capacity
Total capacity
513 31 3209 02
V.
Calculate RTU latent heat capacity.
LHC = TC − SHC
LHC = 73.7 MBH − 54.3 MBH = 19.4 MBH
Compare RTU capacities to loads. 2,3
Compare the rooftop’s SHC and LHC to the
building’s sensible and latent heat loads.
VII. Select factory options (FIOP)
Local code requires an economizer for any unit with
TC less than 65.0 MBH.
VIII. Calculate the total static pressure.
External static pressure
0.66 in. wg
Sum of FIOP / Accessory static
+0.14 in. wg
VI.
Total Static Pressure
0.80 in. wg
IX.
Look up the indoor fan RPM & BHP.
Table 22 shows, at 2100 CFM & ESP= 0.8,
RPM = 1268 & BHP = 1.52
X.
Determine electrical requirements.
Table 43 shows the MCA and MOCP of a RAS072
(without convenience outlet) as:
MCA = 30.5 amps & MOCP = 45.0 amps
Min. disconnect size: FLA = 30 & LRA = 157.
NOTES:
1. Selection software saves time by performing many of the
steps above. Contact your sales representative for assistance.
2. Selecting a unit with a SHC slightly lower than the SHCLoad is
often better than oversizing. Slightly lower SHC’s will help
control indoor humidity, and prevent temperature swings.
3. If the rooftop's capacity meets the Sensible Heat Load, but
not the Latent Heat Load.
4. Indoor fan motor efficiency is available in the electrical tables.
Use the decimal form in the equation, eg. 80% = .8.
Specifications subject to change without notice.
31
Table 7 – COOLING CAPACITIES
EAT (wb)
900 Cfm
62
67
72
76
58
EAT (wb)
1050 Cfm
62
67
72
76
58
EAT (wb)
1200 Cfm
62
67
72
76
58
EAT (wb)
1350 Cfm
62
67
72
76
58
EAT (wb)
1500 Cfm
62
67
72
76
LEGEND:
Cfm
EAT(db)
EAT(wb)
SHC
TC
-
3 TONS
AMBIENT TEMPERATURE
95
105
EAT (db)
EAT (db)
80
85
75
80
26.3
29.8
24.5
24.5
26.3
29.8
21.3
24.5
27.8
29.8
25.1
25.1
25.7
29.8
20.2
24.3
33.1
33.1
30.5
30.5
22.7
26.9
17.4
21.6
37.1
37.1
35.1
35.1
18.8
23.0
13.7
17.9
39.6
39.6
37.6
15.4
20.2
14.6
TC
SHC
TC
SHC
TC
SHC
TC
SHC
TC
SHC
75
28.1
24.4
30.3
22.6
35.5
19.5
39.0
15.3
-
85
EAT (db)
80
28.1
28.1
30.3
26.8
35.5
23.7
39.0
19.5
41.4
16.0
TC
SHC
TC
SHC
TC
SHC
TC
SHC
TC
SHC
30.2
26.3
31.9
24.6
36.7
20.6
40.1
15.7
-
30.2
30.2
31.9
29.4
36.7
25.4
40.1
20.5
42.4
16.6
34.2
34.2
34.2
34.2
36.7
30.2
40.1
25.3
42.4
22.2
28.4
24.7
29.4
23.4
34.8
19.8
38.2
15.0
-
28.4
28.4
29.4
28.1
34.8
24.6
38.2
19.8
40.6
15.9
32.2
32.2
32.8
32.8
34.8
29.4
38.2
24.6
40.6
21.3
26.5
23.1
26.7
22.0
32.2
18.8
36.1
14.2
-
TC
SHC
TC
SHC
TC
SHC
TC
SHC
TC
SHC
32.2
28.0
33.3
26.4
37.7
21.7
40.9
16.1
-
32.2
32.2
33.3
31.7
37.7
27.0
40.9
21.5
43.1
17.1
36.4
36.4
37.0
37.0
37.7
32.4
40.9
26.8
43.1
23.1
30.4
26.4
30.8
25.1
35.6
20.9
39.0
15.4
-
30.4
30.4
30.8
30.3
35.6
26.3
39.0
20.8
41.3
16.4
34.3
34.3
35.5
35.5
35.6
31.6
39.0
26.1
41.3
22.3
TC
SHC
TC
SHC
TC
SHC
TC
SHC
TC
SHC
28.4
17.6
33.2
15.0
37.5
11.8
-
28.4
24.1
33.2
21.4
37.5
18.3
40.1
15.3
30.5
30.5
33.2
27.9
37.5
24.8
40.1
22.7
32.1
27.9
32.2
26.6
36.4
21.9
39.7
15.8
-
32.1
32.1
32.2
32.2
36.4
27.8
39.7
21.7
41.8
16.8
TC
SHC
TC
SHC
TC
SHC
TC
SHC
TC
SHC
28.1
21.9
30.3
19.8
35.5
16.7
39.0
12.4
-
28.1
28.1
30.3
26.8
35.5
23.7
39.0
19.5
41.4
16.0
34.2
34.2
33.8
33.8
35.5
30.7
39.0
26.6
41.4
24.3
33.7
29.3
33.7
27.8
36.9
22.8
40.2
16.1
-
33.7
33.7
33.7
33.7
36.9
29.2
40.2
22.5
42.2
17.2
RAS036
58
1−STAGE COOLING
85
31.7
31.7
31.0
31.0
35.5
27.9
39.0
23.7
41.4
21.0
75
26.3
22.9
27.8
21.5
33.1
18.5
37.1
14.5
-
85
27.7
27.7
28.4
28.4
30.5
25.8
35.1
22.2
37.6
19.3
75
22.6
19.6
22.6
18.7
27.5
16.2
32.7
12.9
-
115
EAT (db)
80
22.6
22.6
22.6
22.6
27.5
20.4
32.7
17.1
35.4
13.8
26.5
26.5
26.7
26.6
32.2
23.6
36.1
19.0
38.5
15.2
30.0
30.0
31.2
31.2
32.2
28.4
36.1
23.8
38.5
20.4
24.5
21.3
24.5
20.3
29.1
17.6
33.7
13.4
-
24.5
24.5
24.5
24.5
29.1
22.4
33.7
18.2
36.2
14.4
27.7
27.7
28.8
28.8
29.1
27.2
33.7
23.0
36.2
19.5
28.4
24.7
28.4
23.4
33.4
20.0
36.9
14.7
-
28.4
28.4
28.4
28.4
33.4
25.4
36.9
20.0
39.1
15.7
32.1
32.1
33.4
33.4
33.4
30.8
36.9
25.4
39.1
21.4
26.3
22.8
26.3
21.7
30.4
18.8
34.4
13.8
-
26.3
26.3
26.3
26.3
30.4
24.2
34.4
19.2
36.8
14.9
29.7
29.7
30.9
30.9
30.4
29.6
34.4
24.5
36.8
20.5
36.3
36.3
37.8
37.8
36.4
33.7
39.7
27.5
41.8
23.2
30.0
26.1
30.1
24.8
34.1
21.0
37.5
15.0
-
30.0
30.0
30.1
30.1
34.1
26.9
37.5
20.9
39.6
16.1
34.0
34.0
35.3
35.3
34.1
32.9
37.5
26.8
39.6
22.3
27.9
24.2
27.9
23.0
31.5
20.0
35.0
14.2
-
27.9
27.9
27.9
27.9
31.5
26.0
35.0
20.1
37.3
15.3
31.5
31.5
32.8
32.8
32.0
32.0
35.0
26.0
37.3
21.5
38.1
38.1
39.6
39.6
36.9
35.7
40.2
28.8
42.2
24.0
31.6
27.4
31.6
26.1
34.6
21.9
38.0
15.4
-
31.6
31.6
31.6
31.6
34.6
28.4
38.0
21.7
40.0
16.5
35.7
35.7
37.1
37.1
34.9
34.9
38.0
28.1
40.0
23.2
29.3
25.5
29.4
24.2
32.0
21.0
35.5
14.6
-
29.3
29.3
29.4
29.4
32.0
27.5
35.5
21.0
-
33.2
33.2
34.5
34.5
34.0
34.0
35.5
27.4
-
85
25.5
25.5
26.5
26.5
27.5
24.6
32.7
21.3
35.4
18.3
Do not operate
Cubic feet per minute (supply air)
Entering air temperature (dry bulb)
Entering air temperature (wet bulb)
Sensible heat capacity
Total capacity
513 31 3209 02
32
Table 7 − COOLING CAPACITIES (cont.)
Temp (F) Air Ent
Condenser (Edb)
75
85
95
105
115
TC
SHC
kW
TC
SHC
kW
TC
SHC
kW
TC
SHC
kW
TC
SHC
kW
Temp (F) Air Ent
Condenser (Edb)
80
75
70
60
50
40
LEGEND
Edb Ewb kW Idb Iwb SHC TC -
TC
SHC
kW
TC
SHC
kW
TC
SHC
kW
TC
SHC
kW
TC
SHC
kW
TC
SHC
kW
1−STAGE COOLING
RAS036 (3 TONS) - UNIT WITH HOT GAS REHEAT IN SUBCOOLING MODE
Air Entering Evaporator - CFM
80 dry bulb
80 dry bulb
72 wet bulb
67 wet bulb
900
1200
1500
900
1200
1500
900
40.6
43.2
45.3
37.0
39.4
41.3
33.4
21.6
23.9
25.6
25.6
27.7
29.3
29.6
2.0
2.0
2.0
2.0
2.0
2.0
2.0
37.0
39.6
41.7
33.6
36.0
37.9
30.2
17.7
20.2
22.2
22.7
25.0
26.9
27.7
2.3
2.3
2.3
2.3
2.3
2.3
2.3
33.5
36.0
38.1
30.2
32.5
34.4
26.9
13.7
16.6
18.8
19.7
22.4
24.4
25.7
2.6
2.6
2.6
2.5
2.5
2.5
2.5
29.9
32.4
34.5
26.8
29.1
31.0
23.6
9.8
12.9
15.3
16.8
19.7
22.0
23.8
2.9
2.9
2.9
2.8
2.8
2.8
2.8
26.3
28.8
30.9
23.3
25.7
27.5
20.4
5.8
9.2
11.9
13.8
17.0
19.5
21.9
3.2
3.2
3.2
3.1
3.1
3.1
3.1
3 TONS
80 dry bulb
62 wet bulb
1200
35.6
31.6
2.0
32.3
29.9
2.3
29.1
28.2
2.5
25.8
26.5
2.8
22.5
24.8
3.1
1500
37.4
33.1
2.0
34.1
31.6
2.3
30.8
30.1
2.5
27.5
28.6
2.8
24.2
27.1
3.1
RAS036 (3 TONS) - UNIT WITH HOT GAS REHEAT IN HOT GAS REHEAT MODE
Air Entering Evaporator - CFM
75 dry bulb
75 dry bulb
75 dry bulb
62.5 wet bulb (50% relative)
64 wet bulb (55% relative)
65.3 wet bulb (60% relative)
1050
1200
1350
1050
1200
1350
1050
1200
1350
14.7
15.5
16.2
15.9
16.7
17.4
16.9
17.7
18.4
6.7
7.6
8.5
4.8
5.7
6.6
3.2
4.1
5.0
2.0
2.0
2.0
2.0
2.0
2.0
2.0
2.0
2.0
15.1
15.8
16.4
16.2
17.0
17.6
17.2
18.0
18.6
7.5
8.4
9.2
5.8
6.7
7.5
4.4
5.2
6.0
1.9
1.9
1.9
2.0
2.0
2.0
2.0
2.0
2.0
15.5
16.1
16.7
16.6
17.3
17.9
17.5
18.2
18.8
8.4
9.3
10.0
6.9
7.7
8.5
5.5
6.4
7.1
1.9
1.9
1.9
1.9
1.9
1.9
1.9
1.9
1.9
16.2
16.8
17.3
17.2
17.8
18.3
18.1
18.7
19.2
10.2
10.9
11.6
8.9
9.7
10.4
7.8
8.6
9.3
1.8
1.8
1.8
1.8
1.8
1.8
1.9
1.9
1.9
17.0
17.5
17.9
17.9
18.4
18.8
18.7
19.2
19.6
11.9
12.6
13.2
11.0
11.6
12.2
10.1
10.8
11.4
1.7
1.7
1.7
1.8
1.8
1.8
1.8
1.8
1.8
17.7
18.1
18.5
18.6
19.0
19.3
19.3
19.7
20.1
13.7
14.3
14.8
13.0
13.6
14.1
12.4
13.0
13.5
1.7
1.7
1.7
1.7
1.7
1.7
1.7
1.7
1.7
Entering Dry-Bulb
Entering Wet-Bulb
Compressor Motor Power Input
Leaving Dry-Bulb
Leaving Wet-Bulb
Sensible Heat Capacity (1000 Btuh) Gross
Total Capacity (1000 Btuh) Gross
NOTES:
1. Direct interpolation is permissible. Do not extrapolate.
2. The following formulas may be used:
sensible capacity (Btuh)
1.10 x cfm
tlwb = Wet-bulb temperature corresponding to enthalpy of air
leaving evaporator coil (hlwb)
tldb = tedb –
total capacity (Btuh)
4.5 x cfm
Where: hewb = Enthalpy of air entering evaporator coil
hlwb = hewb –
33
513 31 3209 02
Table 7 − COOLING CAPACITIES (cont.)
EAT (wb)
1200 Cfm
62
67
72
76
58
EAT (wb)
1400 cfm
62
67
72
76
58
EAT (wb)
1600 Cfm
62
67
72
76
58
EAT (wb)
1800 Cfm
62
67
72
76
58
EAT (wb)
2000 Cfm
62
67
72
76
LEGEND:
Cfm
EAT(db)
EAT(wb)
SHC
TC
-
4 TONS
AMBIENT TEMPERATURE
95
105
EAT (db)
EAT (db)
80
85
75
80
36.1
36.1
31.5
36.1
40.8
40.8
38.4
38.4
35.3
40.6
28.9
34.1
45.2
45.2
42.9
42.9
30.2
35.5
23.9
29.2
49.1
49.1
46.8
46.8
24.7
30.1
18.4
23.7
51.5
51.5
49.2
20.2
26.8
19.3
TC
SHC
TC
SHC
TC
SHC
TC
SHC
TC
SHC
75
43.1
31.2
47.4
25.9
51.1
20.1
-
85
EAT (db)
80
43.1
36.4
47.4
31.2
51.1
25.5
53.3
20.8
TC
SHC
TC
SHC
TC
SHC
TC
SHC
TC
SHC
41.9
36.6
44.6
33.4
48.7
27.3
52.2
20.6
-
41.9
41.9
44.6
39.4
48.7
33.2
52.2
26.7
54.1
21.5
47.3
47.3
45.4
45.4
48.7
39.2
52.2
32.7
54.1
29.0
40.1
35.0
42.3
32.3
46.6
26.4
50.3
19.9
-
40.1
40.1
42.3
38.3
46.6
32.3
50.3
25.9
52.3
20.8
45.3
45.3
44.2
44.2
46.6
38.3
50.3
32.0
52.3
28.0
38.2
33.3
39.8
31.0
44.2
25.3
47.8
18.9
-
TC
SHC
TC
SHC
TC
SHC
TC
SHC
TC
SHC
44.0
38.3
45.7
35.3
49.8
28.4
53.0
21.0
-
44.0
44.0
45.7
42.0
49.8
35.0
53.0
27.6
54.6
22.0
49.6
49.6
48.6
48.6
49.8
41.6
53.0
34.3
54.6
29.9
42.1
36.7
43.5
34.2
47.6
27.6
51.1
20.3
-
42.1
42.1
43.5
40.8
47.6
34.2
51.1
27.0
52.8
21.3
47.4
47.4
47.5
47.5
47.6
40.9
51.1
33.6
52.8
29.0
TC
SHC
TC
SHC
TC
SHC
TC
SHC
TC
SHC
44.0
37.6
45.7
34.5
49.8
27.6
53.0
20.2
-
44.0
44.0
45.7
42.0
49.8
35.0
53.0
27.6
54.6
22.0
50.3
50.3
49.5
49.5
49.8
42.5
53.0
35.1
54.6
30.9
42.1
36.0
43.5
33.4
47.6
26.8
51.1
19.5
-
42.1
42.1
43.5
40.8
47.6
34.2
51.1
27.0
52.8
21.3
TC
SHC
TC
SHC
TC
SHC
TC
SHC
TC
SHC
46.9
40.9
47.5
38.5
51.2
30.5
54.0
21.7
-
46.9
46.9
47.5
46.3
51.2
38.3
54.0
29.2
55.2
22.7
52.9
52.9
54.0
54.0
51.2
46.0
54.0
36.8
55.2
31.4
45.0
39.3
45.3
37.3
49.1
29.8
52.1
21.1
-
45.0
45.0
45.3
44.9
49.1
37.6
52.1
28.7
53.5
22.0
RAS048
58
1−STAGE COOLING
85
43.1
41.7
47.4
36.4
51.1
30.9
53.3
27.4
75
40.8
30.1
45.2
25.0
49.1
19.4
-
85
40.7
40.7
39.4
39.4
42.9
34.4
46.8
29.0
49.2
25.7
75
34.3
29.9
35.9
27.8
40.3
22.9
43.9
17.4
-
115
EAT (db)
80
34.3
34.3
35.9
33.0
40.3
28.2
43.9
22.7
45.9
18.3
38.2
38.2
39.8
37.0
44.2
31.3
47.8
24.9
49.9
19.9
43.2
43.2
42.9
42.9
44.2
37.3
47.8
30.9
49.9
26.9
36.3
31.7
37.3
29.8
41.4
24.2
44.8
17.9
-
36.3
36.3
37.3
35.7
41.4
30.2
44.8
23.8
46.4
18.8
41.0
41.0
41.6
41.6
41.4
36.2
44.8
29.7
46.4
25.7
40.1
34.9
41.0
32.9
45.1
26.5
48.6
19.4
-
40.1
40.1
41.0
39.4
45.1
33.2
48.6
26.0
50.4
20.3
45.2
45.2
46.0
46.0
45.1
39.9
48.6
32.6
50.4
27.9
38.1
33.2
38.5
31.6
42.3
25.4
45.4
18.3
-
38.1
38.1
38.5
38.0
42.3
32.1
45.4
24.8
46.8
19.2
43.0
43.0
44.4
44.4
42.3
38.7
45.4
31.3
46.8
26.6
48.1
48.1
48.3
48.3
47.6
41.7
51.1
34.4
52.8
30.0
40.1
34.3
41.0
32.1
45.1
25.7
48.6
18.5
-
40.1
40.1
41.0
39.4
45.1
33.2
48.6
26.0
50.4
20.3
45.9
45.9
46.8
46.8
45.1
40.7
48.6
33.4
50.4
28.9
38.0
32.6
38.4
30.8
42.3
24.6
45.4
17.5
-
38.0
38.0
38.4
38.0
42.3
32.1
45.4
24.8
46.8
19.2
43.5
43.5
45.2
45.2
42.3
39.5
45.4
32.1
46.8
27.5
50.8
50.8
52.5
52.5
49.1
45.5
52.1
36.4
53.5
30.6
42.9
37.4
43.0
35.6
46.5
28.7
49.7
20.1
-
42.9
42.9
43.0
43.0
46.5
36.6
49.7
27.8
51.0
21.1
48.4
48.4
50.3
50.3
46.5
44.5
49.7
35.4
51.0
29.6
40.7
35.5
40.7
33.8
43.5
27.5
46.2
18.9
-
40.7
40.7
40.7
40.7
43.5
35.4
46.2
26.4
47.3
19.9
45.9
45.9
47.7
47.7
43.5
43.2
46.2
33.9
47.3
28.1
85
38.6
38.6
38.2
38.2
40.3
33.4
43.9
28.0
45.9
24.6
Do not operate
Cubic feet per minute (supply air)
Entering air temperature (dry bulb)
Entering air temperature (wet bulb)
Sensible heat capacity
Total capacity
513 31 3209 02
34
Table 7 − COOLING CAPACITIES (cont.)
Temp (F) Air Ent
Condenser (Edb)
75
85
95
105
115
TC
SHC
kW
TC
SHC
kW
TC
SHC
kW
TC
SHC
kW
TC
SHC
kW
Temp (F) Air Ent
Condenser (Edb)
80
75
70
60
50
40
LEGEND
Edb Ewb kW Idb Iwb SHC TC -
TC
SHC
kW
TC
SHC
kW
TC
SHC
kW
TC
SHC
kW
TC
SHC
kW
TC
SHC
kW
1−STAGE COOLING
RAS048 (4 TONS) - UNIT WITH HOT GAS REHEAT IN SUBCOOLING MODE
Air Entering Evaporator - CFM
80 dry bulb
80 dry bulb
72 wet bulb
67 wet bulb
1200
1600
2000
1200
1600
2000
1200
52.5
55.9
58.6
47.1
50.2
52.7
41.7
22.6
25.5
27.8
27.1
29.9
32.0
31.6
2.5
2.5
2.5
2.5
2.5
2.5
2.5
48.7
52.2
54.9
43.4
46.5
49.0
38.0
18.0
21.3
23.9
23.6
26.8
29.2
29.3
2.9
2.9
2.9
2.9
2.9
2.9
2.9
44.9
48.4
51.2
39.6
42.8
45.3
34.3
13.4
17.2
20.0
20.2
23.7
26.4
27.0
3.4
3.4
3.4
3.3
3.3
3.3
3.3
41.1
44.7
47.5
35.9
39.1
41.7
30.6
8.8
13.0
16.1
16.7
20.6
23.6
24.6
3.8
3.8
3.8
3.7
3.7
3.7
3.7
37.4
41.0
43.9
32.1
35.4
38.0
26.8
4.3
8.8
12.2
13.3
17.5
20.7
22.3
4.2
4.2
4.2
4.2
4.2
4.2
4.1
4 TONS
80 dry bulb
62 wet bulb
1600
44.5
34.2
2.5
40.8
32.2
2.9
37.1
30.2
3.3
33.5
28.2
3.7
29.8
26.2
4.1
2000
46.8
36.2
2.5
43.1
34.4
2.9
39.4
32.7
3.3
35.8
31.0
3.7
32.1
29.2
4.1
RAS048 (4 TONS) - UNIT WITH HOT GAS REHEAT IN HOT GAS REHEAT MODE
Air Entering Evaporator - CFM
75 dry bulb
75 dry bulb
75 dry bulb
62.5 wet bulb (50% relative)
64 wet bulb (55% relative)
65.3 wet bulb (60% relative)
1200
1600
2000
1200
1600
2000
1200
1600
2000
11.6
13.8
15.5
13.5
15.8
17.6
15.2
17.5
19.3
-1.0
1.2
3.0
-3.1
-0.8
0.9
-4.8
-2.6
-0.9
2.5
2.5
2.5
2.5
2.5
2.5
2.5
2.5
2.5
12.5
14.6
16.2
14.3
16.4
18.1
15.9
18.1
19.8
-0.7
1.4
3.0
-2.7
-0.6
1.1
-4.3
-2.2
-0.6
2.5
2.5
2.5
2.5
2.5
2.5
2.5
2.5
2.5
13.4
15.3
16.8
15.1
17.1
18.7
16.6
18.7
20.3
-0.5
1.5
3.0
-2.3
-0.3
1.2
-3.8
-1.9
-0.3
2.5
2.5
2.5
2.5
2.5
2.5
2.5
2.5
2.5
15.1
16.8
18.1
16.7
18.4
19.8
18.1
19.9
21.2
0.0
1.7
3.1
-1.5
0.2
1.5
-2.8
-1.1
0.2
2.6
2.6
2.6
2.6
2.6
2.6
2.6
2.6
2.6
16.9
18.3
19.4
18.3
19.8
20.9
19.6
21.0
22.2
0.6
2.0
3.1
-0.7
0.7
1.8
-1.8
-0.4
0.7
2.6
2.6
2.6
2.6
2.6
2.6
2.6
2.6
2.6
18.7
19.8
20.7
19.9
21.1
22.0
21.0
22.2
23.2
1.1
2.2
3.1
0.1
1.2
2.1
-0.8
0.4
1.3
2.6
2.6
2.6
2.7
2.7
2.7
2.7
2.7
2.7
Entering Dry-Bulb
Entering Wet-Bulb
Compressor Motor Power Input
Leaving Dry-Bulb
Leaving Wet-Bulb
Sensible Heat Capacity (1000 Btuh) Gross
Total Capacity (1000 Btuh) Gross
NOTES:
1. Direct interpolation is permissible. Do not extrapolate.
2. The following formulas may be used:
sensible capacity (Btuh)
1.10 x cfm
tlwb = Wet-bulb temperature corresponding to enthalpy of air
leaving evaporator coil (hlwb)
tldb = tedb –
total capacity (Btuh)
4.5 x cfm
Where: hewb = Enthalpy of air entering evaporator coil
hlwb = hewb –
35
513 31 3209 02
Table 7 − COOLING CAPACITIES (cont.)
EAT (wb)
1500 Cfm
62
67
72
76
58
EAT (wb)
1750 Cfm
62
67
72
76
58
EAT (wb)
2000 Cfm
62
67
72
76
58
EAT (wb)
2250 Cfm
62
67
72
76
58
EAT (wb)
2500 Cfm
62
67
72
76
LEGEND:
Cfm
EAT(db)
EAT(wb)
SHC
TC
-
5 TONS
AMBIENT TEMPERATURE
95
105
EAT (db)
EAT (db)
80
85
75
80
49.9
56.6
46.6
46.6
49.9
56.6
40.4
46.6
52.2
55.7
47.8
47.8
47.8
55.7
37.8
45.6
58.8
58.8
54.4
54.4
41.2
49.1
31.4
39.3
64.8
64.8
60.8
60.8
33.9
41.9
24.4
32.4
69.0
69.0
65.4
27.6
35.9
26.3
TC
SHC
TC
SHC
TC
SHC
TC
SHC
TC
SHC
75
52.9
45.8
56.2
41.8
62.4
34.8
68.2
27.2
-
85
EAT (db)
80
52.9
52.9
56.2
49.7
62.4
42.8
68.2
35.2
71.1
28.4
TC
SHC
TC
SHC
TC
SHC
TC
SHC
TC
SHC
56.5
48.9
58.5
45.2
64.3
36.9
69.5
27.8
-
56.5
56.5
58.5
54.3
64.3
46.1
69.5
36.9
72.2
29.3
64.0
64.0
63.4
63.4
64.3
55.2
69.5
45.9
72.2
38.9
53.3
46.1
54.4
43.2
60.5
35.3
66.5
26.7
-
53.3
53.3
54.4
52.2
60.5
44.5
66.5
35.9
70.1
28.6
60.4
60.4
61.3
61.3
60.5
53.7
66.5
45.1
70.1
38.2
49.8
43.1
49.9
41.0
56.2
33.6
62.4
25.2
-
TC
SHC
TC
SHC
TC
SHC
TC
SHC
TC
SHC
59.3
51.4
60.1
48.1
65.7
38.8
70.1
28.3
-
59.3
59.3
60.1
58.3
65.7
49.1
70.1
38.1
72.9
30.1
67.3
67.3
68.5
68.5
65.7
59.5
70.1
48.0
72.9
40.7
56.1
48.6
56.2
46.2
61.9
37.3
67.6
27.4
-
56.1
56.1
56.2
56.2
61.9
47.7
67.6
37.7
70.8
29.3
63.6
63.6
66.3
66.3
61.9
58.1
67.6
48.0
70.8
39.9
TC
SHC
TC
SHC
TC
SHC
TC
SHC
TC
SHC
61.5
53.2
61.6
50.6
66.8
40.5
70.8
28.7
-
61.5
61.5
61.6
61.6
66.8
52.0
70.8
39.5
73.4
30.7
69.8
69.8
72.6
72.6
66.8
63.4
70.8
50.2
73.4
42.1
58.4
50.5
58.4
47.9
63.0
39.1
68.5
28.0
-
58.4
58.4
58.4
58.4
63.0
50.7
68.5
39.3
71.2
30.0
TC
SHC
TC
SHC
TC
SHC
TC
SHC
TC
SHC
63.3
54.8
63.4
52.0
67.6
42.1
71.3
29.1
-
63.3
63.3
63.4
63.4
67.6
54.6
71.3
40.7
73.8
31.2
71.8
71.8
74.7
74.7
67.6
67.1
71.3
52.2
73.8
43.3
60.1
52.1
60.2
49.4
63.8
40.9
69.0
28.5
-
60.1
60.1
60.2
60.2
63.8
53.5
69.0
40.7
71.4
30.5
RAS060
58
1−STAGE COOLING
85
60.0
60.0
57.6
57.6
62.4
50.7
68.2
43.2
71.1
36.6
75
49.9
43.2
52.2
39.9
58.8
33.2
64.8
25.9
-
85
52.9
52.9
53.5
53.5
54.4
47.3
60.8
40.4
65.4
34.6
75
43.1
37.3
43.2
35.5
49.5
29.4
56.2
22.6
-
115
EAT (db)
80
43.1
43.1
43.2
43.2
49.5
37.3
56.2
30.6
60.9
24.8
49.8
49.8
49.9
49.9
56.2
42.8
62.4
34.5
66.6
27.4
56.5
56.5
58.9
58.9
56.2
51.9
62.4
43.7
66.6
36.8
46.1
39.9
46.1
37.9
51.3
31.6
57.7
23.5
-
46.1
46.1
46.1
46.1
51.3
40.8
57.7
32.8
-
52.3
52.3
54.4
54.4
51.3
49.9
57.7
42.0
-
52.5
45.4
52.5
43.1
57.5
35.6
63.6
26.0
-
52.5
52.5
52.5
52.5
57.5
46.0
63.6
36.4
67.4
28.2
59.5
59.5
62.0
62.0
57.5
56.4
63.6
46.7
67.4
38.7
48.6
42.1
48.7
39.9
52.6
33.6
58.9
24.3
-
48.6
48.6
48.7
48.7
52.6
44.0
58.9
34.7
-
55.1
55.1
57.4
57.4
54.4
54.4
58.9
45.2
-
66.2
66.2
68.9
68.9
63.0
62.3
68.5
50.5
71.2
41.4
54.8
47.4
54.8
45.0
58.5
37.4
64.5
26.7
-
54.8
54.8
54.8
54.8
58.5
49.0
64.5
38.1
67.9
28.9
62.1
62.1
64.6
64.6
60.6
60.6
64.5
49.6
67.9
40.4
50.8
43.9
50.8
41.7
53.6
35.5
59.8
25.0
-
50.8
50.8
50.8
50.8
53.6
47.0
59.8
36.6
-
57.6
57.6
59.9
59.9
58.6
58.6
59.8
48.1
-
68.2
68.2
71.0
71.0
66.2
66.2
69.0
52.9
71.4
42.6
56.5
49.0
56.6
46.5
59.3
39.2
65.1
27.3
-
56.5
56.5
56.6
56.6
59.3
51.9
65.1
39.7
68.3
29.6
64.1
64.1
66.7
66.7
64.6
64.6
65.1
52.2
68.3
41.9
52.6
45.5
52.6
43.2
54.4
37.2
60.4
25.7
-
52.6
52.6
52.6
52.6
54.4
49.8
60.4
38.3
-
59.6
59.6
62.1
62.1
62.5
62.5
60.4
50.9
-
85
48.9
48.9
51.0
51.0
49.5
45.3
56.2
38.6
60.9
33.0
Do not operate
Cubic feet per minute (supply air)
Entering air temperature (dry bulb)
Entering air temperature (wet bulb)
Sensible heat capacity
Total capacity
513 31 3209 02
36
Table 7 − COOLING CAPACITIES (cont.)
Temp (F) Air Ent
Condenser (Edb)
75
85
95
105
115
TC
SHC
kW
TC
SHC
kW
TC
SHC
kW
TC
SHC
kW
TC
SHC
kW
Temp (F) Air Ent
Condenser (Edb)
80
75
70
60
50
40
LEGEND
Edb Ewb kW Idb Iwb SHC TC -
TC
SHC
kW
TC
SHC
kW
TC
SHC
kW
TC
SHC
kW
TC
SHC
kW
TC
SHC
kW
1−STAGE COOLING
RAS060 (5 TONS) - UNIT WITH HOT GAS REHEAT IN SUBCOOLING MODE
Air Entering Evaporator - CFM
80 dry bulb
80 dry bulb
72 wet bulb
67 wet bulb
1750
2000
2250
1750
2000
2250
1750
73.1
78.7
84.5
63.2
66.9
70.8
53.2
35.3
37.2
38.8
42.0
43.7
45.3
48.7
3.3
3.3
3.3
3.3
3.3
3.3
3.3
67.6
71.2
75.0
59.1
61.2
63.3
50.6
27.9
30.0
31.9
36.3
38.3
40.1
44.8
3.8
3.8
3.8
3.8
3.8
3.8
3.8
62.1
63.8
65.5
55.1
55.4
55.8
48.0
20.5
22.9
24.9
30.7
32.9
34.8
40.9
4.3
4.3
4.3
4.3
4.3
4.3
4.3
56.6
56.3
56.0
51.0
49.6
48.3
45.4
13.1
15.7
18.0
25.0
27.5
29.6
36.9
4.8
4.8
4.8
4.8
4.8
4.8
4.7
51.1
48.8
46.5
46.9
43.9
40.7
42.8
5.8
8.6
11.0
19.4
22.0
24.4
33.0
5.3
5.3
5.3
5.3
5.3
5.3
5.2
5 TONS
80 dry bulb
62 wet bulb
2000
55.1
50.3
3.3
51.1
46.6
3.8
47.0
42.9
4.3
43.0
39.2
4.7
39.0
35.5
5.2
2250
57.1
51.8
3.3
51.5
48.2
3.8
46.0
44.7
4.3
40.5
41.2
4.7
35.0
37.7
5.2
RAS060 (5 TONS) - UNIT WITH HOT GAS REHEAT IN HOT GAS REHEAT MODE
Air Entering Evaporator - CFM
75 dry bulb
75 dry bulb
75 dry bulb
62.5 wet bulb (50% relative)
64 wet bulb (55% relative)
65.3 wet bulb (60% relative)
1750
2000
2250
1750
2000
2250
1750
2000
2250
23.0
24.4
25.6
24.7
26.2
27.4
26.3
27.7
29.0
5.3
6.1
6.8
3.2
4.0
4.7
1.4
2.2
2.9
2.9
2.9
2.9
2.9
2.9
2.9
2.9
2.9
2.9
23.3
24.6
25.7
25.0
26.3
27.5
26.4
27.8
29.0
5.1
5.8
6.5
3.1
3.9
4.5
1.4
2.2
2.8
2.9
2.9
2.9
2.9
2.9
2.9
2.9
2.9
2.9
23.5
24.8
25.9
25.2
26.4
27.5
26.6
27.9
29.0
4.8
5.5
6.2
3.0
3.7
4.3
1.4
2.1
2.8
3.0
3.0
3.0
3.0
3.0
3.0
3.0
3.0
3.0
24.1
25.2
26.1
25.6
26.7
27.7
26.9
28.0
29.0
4.3
5.0
5.5
2.8
3.4
3.9
1.4
2.0
2.6
3.0
3.0
3.0
3.0
3.0
3.0
3.0
3.0
3.0
24.7
25.6
26.4
26.1
27.0
27.8
27.2
28.2
29.0
3.8
4.4
4.8
2.5
3.1
3.5
1.4
2.0
2.4
3.1
3.1
3.1
3.1
3.1
3.1
3.1
3.1
3.1
25.3
26.0
26.7
26.5
27.3
27.9
27.6
28.3
29.0
3.3
3.8
4.2
2.3
2.8
3.1
1.4
1.9
2.3
3.1
3.1
3.1
3.2
3.2
3.2
3.2
3.2
3.2
Entering Dry-Bulb
Entering Wet-Bulb
Compressor Motor Power Input
Leaving Dry-Bulb
Leaving Wet-Bulb
Sensible Heat Capacity (1000 Btuh) Gross
Total Capacity (1000 Btuh) Gross
NOTES:
1. Direct interpolation is permissible. Do not extrapolate.
2. The following formulas may be used:
sensible capacity (Btuh)
1.10 x cfm
tlwb = Wet-bulb temperature corresponding to enthalpy of air
leaving evaporator coil (hlwb)
tldb = tedb –
total capacity (Btuh)
4.5 x cfm
Where: hewb = Enthalpy of air entering evaporator coil
hlwb = hewb –
37
513 31 3209 02
Table 7 − COOLING CAPACITIES (cont.)
EAT (wb)
1800 Cfm
62
67
72
76
58
EAT (wb)
2100 Cfm
62
67
72
76
58
EAT (wb)
2400 Cfm
62
67
72
76
58
EAT (wb)
2700 Cfm
62
67
72
76
58
EAT (wb)
3000 Cfm
62
67
72
76
LEGEND:
Cfm
EAT(db)
EAT(wb)
SHC
TC
-
6 TONS
AMBIENT TEMPERATURE
95
105
EAT (db)
EAT (db)
80
85
75
80
62.1
70.0
58.9
58.9
62.1
70.0
51.4
58.9
64.9
68.5
60.8
60.8
59.2
68.5
47.9
57.2
71.7
71.7
67.4
67.4
50.5
59.8
39.3
48.6
78.5
78.5
73.7
73.7
41.3
50.6
30.0
39.3
83.3
83.3
77.7
33.5
43.4
31.6
TC
SHC
TC
SHC
TC
SHC
TC
SHC
TC
SHC
75
64.9
56.6
68.7
51.7
75.6
42.8
82.6
33.5
-
85
EAT (db)
80
64.9
64.9
68.7
61.0
75.6
52.2
82.6
42.8
87.5
35.0
TC
SHC
TC
SHC
TC
SHC
TC
SHC
TC
SHC
68.9
60.1
70.9
55.6
77.8
45.4
84.5
34.5
-
68.9
68.9
70.9
66.3
77.8
56.1
84.5
45.2
89.2
36.3
77.7
77.7
76.9
76.9
77.8
66.8
84.5
55.9
89.2
47.8
65.9
57.4
67.1
53.8
73.7
43.7
80.3
32.9
-
65.9
65.9
67.1
64.4
73.7
54.4
80.3
43.5
84.7
34.7
74.3
74.3
75.0
75.0
73.7
65.2
80.3
54.2
84.7
46.0
62.5
54.5
63.0
51.6
69.2
41.8
75.1
30.9
-
TC
SHC
TC
SHC
TC
SHC
TC
SHC
TC
SHC
72.0
62.8
72.8
59.1
79.4
47.7
86.0
35.3
-
72.0
72.0
72.8
71.0
79.4
59.8
86.0
47.2
90.3
37.3
81.2
81.2
82.8
82.8
79.4
71.8
86.0
59.2
90.3
49.8
68.7
60.0
68.9
57.2
75.2
46.0
81.6
33.7
-
68.7
68.7
68.9
68.9
75.2
58.1
81.6
45.6
85.7
35.6
77.5
77.5
80.7
80.7
75.2
70.2
81.6
57.5
85.7
48.0
TC
SHC
TC
SHC
TC
SHC
TC
SHC
TC
SHC
60.3
46.4
65.4
41.0
72.7
33.8
79.7
25.8
-
60.3
60.3
65.4
55.1
72.7
48.0
79.7
40.2
85.1
33.5
74.1
74.1
69.3
69.3
72.7
62.2
79.7
54.6
85.1
48.4
71.1
62.0
71.2
59.0
76.3
48.2
82.5
34.5
-
71.1
71.1
71.2
71.2
76.3
61.6
82.5
47.5
86.4
36.5
TC
SHC
TC
SHC
TC
SHC
TC
SHC
TC
SHC
64.9
51.1
68.7
45.5
75.6
36.6
82.6
27.2
-
64.9
64.9
68.7
61.0
75.6
52.2
82.6
42.8
87.5
35.0
78.8
78.8
76.5
76.5
75.6
67.7
82.6
58.5
87.5
51.5
73.1
63.8
73.2
60.7
77.2
50.2
83.3
35.1
-
73.1
73.1
73.2
73.2
77.2
64.8
83.3
49.2
86.9
37.3
RAS072
58
1−STAGE COOLING
85
73.3
73.3
70.3
70.3
75.6
61.5
82.6
52.2
87.5
44.9
75
62.1
54.1
64.9
49.9
71.7
41.2
78.5
31.9
-
85
66.4
66.4
66.4
66.4
67.4
58.0
73.7
48.6
77.7
41.5
75
55.6
48.5
56.4
45.7
62.5
37.2
67.8
27.8
-
115
EAT (db)
80
55.6
55.6
56.4
54.9
62.5
46.5
67.8
36.9
70.9
29.3
62.5
62.5
63.0
62.1
69.2
52.5
75.1
41.4
78.8
32.6
70.5
70.5
72.5
72.5
69.2
63.2
75.1
52.0
78.8
43.7
58.7
51.2
58.7
48.7
64.0
39.6
68.8
28.5
-
58.7
58.7
58.7
58.7
64.0
50.2
68.8
38.7
71.6
30.1
66.2
66.2
68.7
68.7
64.0
60.7
68.8
48.9
71.6
40.9
65.2
56.9
65.2
54.1
70.5
44.0
76.1
31.7
-
65.2
65.2
65.2
65.2
70.5
56.0
76.1
43.3
79.6
33.5
73.5
73.5
76.4
76.4
70.5
68.1
76.1
55.0
79.6
45.6
61.1
53.3
61.2
50.7
65.1
41.6
69.6
29.1
-
61.1
61.1
61.2
61.2
65.1
53.5
69.6
40.3
72.1
30.8
68.9
68.9
71.6
71.6
65.3
65.3
69.6
51.4
72.1
42.5
80.2
80.2
83.3
83.3
76.3
74.9
82.5
60.5
86.4
49.9
67.4
58.8
67.5
55.9
71.5
46.1
76.9
32.3
-
67.4
67.4
67.5
67.5
71.5
59.3
76.9
45.0
80.2
34.3
76.0
76.0
79.0
79.0
72.6
72.6
76.9
57.7
80.2
47.3
63.0
55.0
63.1
52.3
65.8
43.5
70.1
29.7
-
63.0
63.0
63.1
63.1
65.8
56.5
70.1
41.7
72.5
31.5
71.1
71.1
73.8
73.8
69.4
69.4
70.1
53.8
72.5
44.0
82.5
82.5
85.7
85.7
79.4
79.4
83.3
63.3
86.9
51.6
69.2
60.3
69.2
57.4
72.2
48.0
77.5
32.9
-
69.2
69.2
69.2
69.2
72.2
62.4
77.5
46.6
80.6
35.0
78.0
78.0
81.0
81.0
76.8
76.8
77.5
60.3
80.6
48.9
64.5
56.2
64.5
53.5
66.3
45.1
70.5
30.2
-
64.5
64.5
64.5
64.5
66.3
59.1
70.5
43.0
72.8
32.1
72.7
72.7
75.5
75.5
73.0
73.0
70.5
55.9
72.8
45.3
85
62.7
62.7
64.0
64.0
62.5
55.8
67.8
45.9
70.9
39.1
Do not operate in this region
Cubic feet per minute (supply air)
Entering air temperature (dry bulb)
Entering air temperature (wet bulb)
Sensible heat capacity
Total capacity
513 31 3209 02
38
Table 7 − COOLING CAPACITIES (cont.)
Temp (F) Air Ent
Condenser (Edb)
75
85
95
105
115
TC
SHC
kW
TC
SHC
kW
TC
SHC
kW
TC
SHC
kW
TC
SHC
kW
Temp (F) Air Ent
Condenser (Edb)
80
75
70
60
50
40
LEGEND
Edb Ewb kW Idb Iwb SHC TC -
TC
SHC
kW
TC
SHC
kW
TC
SHC
kW
TC
SHC
kW
TC
SHC
kW
TC
SHC
kW
1−STAGE COOLING
RAS072 (6 TONS) - UNIT WITH HOT GAS REHEAT IN SUBCOOLING MODE
Air Entering Evaporator - CFM
80 dry bulb
80 dry bulb
72 wet bulb
67 wet bulb
2100
2400
2700
2100
2400
2700
2100
86.7
89.9
92.8
79.3
82.3
84.9
71.9
40.1
41.8
43.3
46.9
48.5
49.9
53.7
4.3
4.3
4.3
4.2
4.2
4.2
4.2
79.5
82.6
85.4
72.5
75.3
77.9
65.4
32.1
34.0
35.7
40.7
42.5
44.1
49.4
5.0
5.0
5.0
5.0
5.0
5.0
4.9
72.4
75.3
78.1
65.6
68.3
70.8
58.8
24.1
26.3
28.1
34.6
36.6
38.3
45.1
5.8
5.8
5.8
5.7
5.7
5.7
5.6
65.2
68.1
70.7
58.7
61.4
63.8
52.3
16.2
18.5
20.5
28.5
30.6
32.6
40.7
6.5
6.5
6.5
6.4
6.4
6.4
6.3
58.0
60.8
63.3
51.9
54.4
56.7
45.7
8.2
10.7
13.0
22.3
24.7
26.8
36.4
7.2
7.2
7.2
7.1
7.1
7.1
7.0
6 TONS
80 dry bulb
62 wet bulb
2400
74.6
55.2
4.2
68.0
51.0
4.9
61.3
46.9
5.6
54.7
42.8
6.3
48.0
38.6
7.0
2700
77.0
56.5
4.2
70.3
52.5
4.9
63.6
48.5
5.6
56.8
44.6
6.3
50.1
40.6
7.0
RAS072 (6 TONS) - UNIT WITH HOT GAS REHEAT IN HOT GAS REHEAT MODE
Air Entering Evaporator - CFM
75 dry bulb
75 dry bulb
75 dry bulb
62.5 wet bulb (50% relative)
64 wet bulb (55% relative)
65.3 wet bulb (60% relative)
2100
2400
2700
2100
2400
2700
1750
2000
2700
16.7
19.8
22.5
18.8
21.9
24.7
16.2
19.4
26.7
0.6
0.6
0.6
-0.4
-0.4
-0.4
-1.3
-1.3
-1.3
4.0
4.0
4.0
4.0
4.0
4.0
4.0
4.0
4.0
17.7
20.6
23.1
19.6
22.6
25.3
17.3
20.3
27.1
0.6
0.6
0.6
-0.3
-0.3
-0.3
-1.2
-1.2
-1.2
4.0
4.0
4.0
4.0
4.0
4.0
4.0
4.0
4.0
18.6
21.3
23.7
20.5
23.3
25.8
18.3
21.1
27.6
0.7
0.7
0.7
-0.2
-0.2
-0.2
-1.0
-1.0
-1.0
4.0
4.0
4.0
4.1
4.1
4.1
4.1
4.1
4.1
20.5
22.9
25.0
22.2
24.7
26.8
20.4
22.8
28.5
0.7
0.7
0.7
-0.0
-0.0
-0.0
-0.7
-0.7
-0.7
4.1
4.1
4.1
4.1
4.1
4.1
4.1
4.1
4.1
22.4
24.4
26.2
24.0
26.0
27.9
22.4
24.5
29.3
0.8
0.8
0.8
0.1
0.1
0.1
-0.4
-0.4
-0.4
4.1
4.1
4.1
4.1
4.1
4.1
4.2
4.2
4.2
24.3
25.9
27.4
25.7
27.4
28.9
24.5
26.3
30.2
0.8
0.8
0.8
0.3
0.3
0.3
-0.1
-0.1
-0.1
4.1
4.1
4.1
4.2
4.2
4.2
4.2
4.2
4.2
Entering Dry-Bulb
Entering Wet-Bulb
Compressor Motor Power Input
Leaving Dry-Bulb
Leaving Wet-Bulb
Sensible Heat Capacity (1000 Btuh) Gross
Total Capacity (1000 Btuh) Gross
NOTES:
1. Direct interpolation is permissible. Do not extrapolate.
2. The following formulas may be used:
sensible capacity (Btuh)
1.10 x cfm
tlwb = Wet-bulb temperature corresponding to enthalpy of air
leaving evaporator coil (hlwb)
tldb = tedb –
total capacity (Btuh)
4.5 x cfm
Where: hewb = Enthalpy of air entering evaporator coil
hlwb = hewb –
39
513 31 3209 02
Table 7 − COOLING CAPACITIES (cont.)
EAT (wb)
2250 Cfm
62
67
72
76
58
EAT (wb)
2625 Cfm
62
67
72
76
58
EAT (wb)
3000 Cfm
62
67
72
76
58
EAT (wb)
3375 Cfm
62
67
72
76
58
EAT (wb)
3750 Cfm
62
67
72
76
LEGEND:
Cfm
EAT(db)
EAT(wb)
SHC
TC
-
7.5 TONS
AMBIENT TEMPERATURE
95
105
EAT (db)
EAT (db)
80
85
75
80
77.5
87.7
73.6
73.6
77.5
87.7
63.9
73.6
82.3
84.0
77.2
77.2
72.7
84.0
58.9
70.2
90.7
90.7
85.7
85.7
62.2
73.6
48.8
60.1
98.9
98.9
93.8
93.8
51.2
62.7
37.7
49.2
104.8
104.8
99.1
42.0
54.3
40.0
TC
SHC
TC
SHC
TC
SHC
TC
SHC
TC
SHC
85
EAT (db)
75
80
85
81.2
81.2
91.8
70.5
81.2
91.8
86.9
86.9
86.9
63.6
74.9
86.2
95.2
95.2
95.2
52.8
64.2
75.6
103.5
103.5
103.5
41.5
53.1
64.6
109.6
109.6
43.7
56.0
75
77.5
67.3
82.3
61.4
90.7
50.9
98.9
39.7
-
TC
SHC
TC
SHC
TC
SHC
TC
SHC
TC
SHC
85.9
74.6
89.6
68.1
97.9
55.7
106.0
42.7
-
85.9
85.9
89.6
81.1
97.9
68.7
106.0
55.8
111.8
45.3
97.2
97.2
94.1
94.1
97.9
81.7
106.0
68.9
111.8
59.8
82.2
71.4
85.1
65.9
93.2
53.7
101.3
40.9
-
82.2
82.2
85.1
78.8
93.2
66.7
101.3
53.9
106.9
43.6
93.1
93.1
91.7
91.7
93.2
79.8
101.3
67.0
106.9
58.0
78.1
67.9
80.1
63.4
88.1
51.6
95.9
38.8
-
TC
SHC
TC
SHC
TC
SHC
TC
SHC
TC
SHC
89.6
77.9
91.8
72.2
99.9
58.3
107.9
43.7
-
89.6
89.6
91.8
86.7
99.9
72.9
107.9
58.3
113.8
46.7
101.4
101.4
101.1
101.1
99.9
87.5
107.9
72.8
113.8
62.5
85.9
74.6
87.2
69.9
95.2
56.4
103.0
41.9
-
85.9
85.9
87.2
84.3
95.2
71.0
103.0
56.4
108.4
44.8
97.2
97.2
98.6
98.6
95.2
85.5
103.0
70.9
108.4
60.4
TC
SHC
TC
SHC
TC
SHC
TC
SHC
TC
SHC
92.7
80.5
93.7
75.8
101.5
60.8
109.4
44.6
-
92.7
92.7
93.7
91.6
101.5
76.9
109.4
60.5
115.1
47.8
104.9
104.9
107.3
107.3
101.5
93.0
109.4
76.4
115.1
64.9
88.8
77.1
89.1
73.5
96.7
58.8
104.3
42.8
-
88.8
88.8
89.1
89.1
96.7
74.9
104.3
58.6
109.5
45.9
TC
SHC
TC
SHC
TC
SHC
TC
SHC
TC
SHC
95.3
82.7
95.5
78.7
102.8
63.1
110.6
45.5
-
95.3
95.3
95.5
95.5
102.8
80.6
110.6
62.7
116.1
48.9
107.8
107.8
112.2
112.2
102.8
98.2
110.6
79.9
116.1
67.0
91.3
79.3
91.3
75.3
97.9
61.2
105.4
43.5
-
91.3
91.3
91.3
91.3
97.9
78.7
105.4
60.7
110.3
46.8
RAS091
58
1−STAGE COOLING
85
83.3
83.3
81.5
81.5
85.7
71.5
93.8
60.6
99.1
52.4
75
69.5
60.4
71.9
56.3
79.9
46.3
87.3
35.3
-
115
EA (db)
80
69.5
69.5
71.9
67.6
79.9
57.6
87.3
46.6
91.6
37.4
78.1
78.1
80.1
76.3
88.1
64.6
95.9
51.8
100.7
41.4
88.4
88.4
89.1
89.1
88.1
77.6
95.9
64.7
100.7
55.6
73.9
64.1
74.6
60.6
82.0
49.0
89.0
36.2
-
73.9
73.9
74.6
73.3
82.0
62.0
89.0
48.9
92.7
38.7
83.6
83.6
86.0
86.0
82.0
74.9
89.0
61.7
92.7
52.6
81.7
71.0
82.3
67.2
89.9
54.2
97.3
39.7
-
81.7
81.7
82.3
81.3
89.9
68.8
97.3
54.1
102.0
42.6
92.5
92.5
95.5
95.5
89.9
83.4
97.3
68.4
102.0
57.9
77.0
66.9
77.1
63.5
83.6
51.6
90.1
37.0
-
77.0
77.0
77.1
77.1
83.6
66.1
90.1
51.0
93.4
39.6
87.1
87.1
90.6
90.6
83.6
80.5
90.1
65.0
93.4
54.7
100.5
100.5
104.7
104.7
96.7
91.0
104.3
74.4
109.5
62.7
84.6
73.4
84.6
69.8
91.3
56.7
98.4
40.5
-
84.6
84.6
84.6
84.6
91.3
72.8
98.4
56.2
102.8
43.5
95.7
95.7
99.5
99.5
91.3
88.9
98.4
71.8
102.8
60.1
79.6
69.1
79.6
65.6
84.8
53.9
90.9
37.7
-
79.6
79.6
79.6
79.6
84.8
69.8
90.9
52.8
94.0
40.4
90.0
90.0
93.6
93.6
85.7
85.7
90.9
68.0
94.0
56.5
103.3
103.3
107.4
107.4
97.9
96.3
105.4
77.8
110.3
64.8
86.9
75.5
87.0
71.7
92.3
59.0
99.2
41.3
-
86.9
86.9
87.0
87.0
92.3
76.5
99.2
58.1
103.5
44.4
98.3
98.3
102.2
102.2
94.0
94.0
99.2
75.0
103.5
62.0
81.7
70.9
81.7
67.4
85.7
56.0
91.5
38.3
-
81.7
81.7
81.7
81.7
85.7
73.2
91.5
54.5
94.5
41.1
92.4
92.4
96.0
96.0
90.5
90.5
91.5
70.7
94.5
58.1
85
78.7
78.7
78.8
78.8
79.9
68.9
87.3
57.8
91.6
49.8
Do not operate in this region
Cubic feet per minute (supply air)
Entering air temperature (dry bulb)
Entering air temperature (wet bulb)
Sensible heat capacity
Total capacity
513 31 3209 02
40
Table 7 − COOLING CAPACITIES (cont.)
RAS090
58
EAT (wb)
2250 Cfm
62
67
72
76
58
EAT (wb)
2625 Cfm
62
67
72
76
58
EAT (wb)
3000 Cfm
62
67
72
76
58
EAT (wb)
3375 Cfm
62
67
72
76
62
EAT (wb)
3750 Cfm
58
67
72
76
TC
SHC
TC
SHC
TC
SHC
TC
SHC
TC
SHC
TC
SHC
TC
SHC
TC
SHC
TC
SHC
TC
SHC
TC
SHC
TC
SHC
TC
SHC
TC
SHC
TC
SHC
TC
SHC
TC
SHC
TC
SHC
TC
SHC
TC
SHC
TC
SHC
TC
SHC
TC
SHC
TC
SHC
TC
SHC
75
77.4
66.9
82.2
60.8
90.1
50.2
98.0
39.1
82.1
71.0
84.9
65.4
92.5
53.0
100.4
40.2
85.7
74.1
86.9
69.3
94.3
55.6
102.2
41.2
88.5
76.5
88.9
72.3
95.8
58.0
103.6
42.0
90.8
78.5
90.9
74.5
97.0
60.3
104.7
42.9
-
85
EAT (db)
80
77.4
77.4
82.2
72.4
90.1
61.8
98.0
50.7
104.3
41.7
82.1
82.1
84.9
78.6
92.5
66.3
100.4
53.5
106.5
43.3
85.7
85.7
86.9
84.0
94.3
70.5
102.2
56.0
108.1
44.5
88.5
88.5
88.9
88.1
95.8
74.4
103.6
58.3
109.2
45.6
90.8
90.8
90.9
90.9
97.0
78.2
104.7
60.5
110.2
46.7
85
87.8
87.8
83.9
83.9
90.1
73.3
98.0
62.4
104.3
54.0
93.2
93.2
91.8
91.8
92.5
79.5
100.4
66.7
106.5
57.6
97.3
97.3
98.7
98.7
94.3
85.4
102.2
70.7
108.1
60.2
100.4
100.4
103.9
103.9
95.8
90.9
103.6
74.5
109.2
62.6
103.0
103.0
107.2
107.2
97.0
96.2
104.7
78.1
110.2
64.8
2−STAGE COOLING
AMBIENT TEMPERATURE
95
105
EAT (db)
EAT (db)
75
80
85
75
80
85
73.8
73.8
83.8
70.1
70.1
79.5
63.9
73.8
83.8
60.6
70.1
79.5
77.5
77.5
81.7
72.6
72.6
79.2
58.6
70.1
81.7
56.3
67.7
79.2
86.0
86.0
86.0
81.4
81.4
81.4
48.5
60.1
71.6
46.5
58.1
69.7
94.0
94.0
94.0
89.5
89.5
89.5
37.5
49.2
60.9
35.8
47.5
59.2
100.4
100.4
95.9
95.9
40.3
52.7
38.7
51.0
78.4
78.4
89.0
74.4
74.4
84.4
67.8
78.4
89.0
64.3
74.4
84.4
80.4
80.4
89.5
75.4
75.4
86.7
63.2
76.3
89.5
60.6
73.7
86.7
88.3
88.3
88.3
83.6
83.6
83.6
51.3
64.6
78.0
49.4
62.8
76.1
96.4
96.4
96.4
91.7
91.7
91.7
38.7
52.0
65.3
36.9
50.3
63.7
102.6
102.6
98.0
98.0
41.8
55.9
40.2
54.1
82.2
82.2
93.3
78.0
78.0
88.6
71.1
82.2
93.3
67.5
78.0
88.6
82.8
82.8
96.4
78.2
78.2
92.3
67.2
81.8
96.4
64.1
78.2
92.3
90.1
90.1
90.1
85.2
85.2
85.2
54.0
68.9
83.9
52.1
67.1
82.2
98.1
98.1
98.1
93.3
93.3
93.3
39.7
54.6
69.5
38.0
53.0
68.0
104.2
104.2
99.5
99.5
43.2
58.7
41.6
57.0
85.0
85.0
96.4
81.0
81.0
92
73.5
85.0
96.4
70.1
81.0
92
85.1
85.1
100.4
81.1
81.1
95.7
69.7
85.1
100.4
66.5
81.1
95.7
91.5
91.5
91.5
86.6
86.6
87.9
56.4
73.0
89.6
54.6
71.3
87.9
99.4
99.4
99.4
94.6
94.6
94.6
40.6
57.0
73.4
38.9
55.5
72.0
105.4
105.4
100.7
100.7
44.4
61.3
42.8
59.7
87.3
87.3
99.1
83.3
83.3
94.5
75.5
87.3
99.1
72.0
83.3
94.5
87.4
87.4
103.1
83.3
83.3
98.4
71.6
87.4
103.1
68.3
83.3
98.4
92.6
92.6
95.1
87.6
87.6
93.4
58.8
76.9
95.1
56.9
75.2
93.4
100.5
100.5
100.5
95.6
95.6
95.6
41.4
59.3
77.1
39.8
57.8
75.9
106.2
106.2
101.6
101.6
45.4
63.6
44.0
62.3
7.5 TONS
75
66.0
57.1
67.3
53.6
75.9
44.2
84.3
33.8
70.0
60.6
70.2
57.6
78.3
47.2
86.4
35.0
73.5
63.6
73.6
60.3
79.8
49.9
87.9
36.0
76.5
66.1
76.5
62.7
81.1
52.4
89.1
37.0
78.8
68.2
78.9
64.7
82.1
54.8
90.1
37.9
-
115
EA (db)
80
66.0
66.0
67.3
65.0
75.9
55.8
84.3
45.5
90.7
36.8
70.0
70.0
70.2
70.2
78.3
60.6
86.4
48.4
92.7
38.4
73.5
73.5
73.6
73.6
79.8
65.0
87.9
51.1
94.2
39.8
76.5
76.5
76.5
76.5
81.1
69.1
89.1
53.7
95.3
41.0
78.8
78.8
78.9
78.9
82.1
73.0
90.1
56.1
96.1
42.2
85
74.9
74.9
76.4
76.4
75.9
67.4
84.3
57.2
90.7
49.0
79.5
79.5
82.9
82.9
78.3
73.9
86.4
61.8
92.7
52.2
83.4
83.4
86.9
86.9
80.1
80.1
87.9
66.2
94.2
55.2
86.8
86.8
90.3
90.3
85.8
85.8
89.1
70.3
95.3
58.0
89.4
89.4
93.1
93.1
91.2
91.2
90.1
74.3
96.1
60.6
* See Minimum-Maximum Airflow Ratings. Do not operate outside these limits.
LEGEND:
- Do not operate in this region
Cfm
- Cubic feet per minute (supply air)
EAT(db)
- Entering air temperature (dry bulb)
EAT(wb)
- Entering air temperature (wet bulb)
SHC
- Sensible heat capacity
TC
- Total capacity
41
513 31 3209 02
Table 7 − COOLING CAPACITIES (cont.)
2−STAGE COOLING
RAS090 COOLING CAPACITIES, UNIT WITH HOT GAS REHEAT IN SUBCOOLING MODE
AIR ENTERING EVAPORATOR - CFM
2250/0.05
3000/0.07
3750/0.09
TEMP (F) AIR ENT
CONDENSER (Edb)
Air Entering Evaporator - Ewb (F)
72
67
62
72
67
62
72
67
TC
103.05
93.02
83.60
109.77
99.52
90.08
114.01
103.69
SHC
43.66
55.34
67.09
50.99
66.29
81.31
57.49
76.27
75
kW
4.90
4.83
4.77
4.82
4.88
4.96
4.99
4.91
TC
95.39
85.83
76.88
101.59
91.89
82.95
105.53
95.76
SHC
36.42
48.47
60.60
43.24
58.99
74.40
49.44
68.68
85
kW
5.49
5.42
5.36
5.40
5.47
5.54
5.58
5.50
TC
87.48
78.44
69.97
93.21
84.05
75.61
96.84
87.63
SHC
28.98
41.46
53.97
35.32
51.53
67.34
41.21
60.92
95
kW
6.16
6.09
6.03
6.08
6.14
6.21
6.24
6.17
TC
79.35
70.83
62.84
84.57
75.96
68.04
87.88
79.23
SHC
21.34
34.26
47.18
27.17
43.86
60.08
32.73
52.95
105
kW
6.93
6.86
6.81
6.85
6.91
6.97
7.00
6.93
TC
70.87
62.89
55.42
75.58
67.54
60.15
78.56
70.51
115
SHC
13.40
26.79
40.14
18.70
35.89
52.54
23.94
44.68
kW
7.79
7.74
7.69
7.73
7.78
7.83
7.86
7.80
7.5 TONS
62
95.19
92.20
4.85
87.77
84.90
5.44
80.14
77.41
6.11
72.26
69.70
6.88
64.06
61.67
7.76
RAS090 COOLING CAPACITIES, UNIT WITH HOT GAS REHEAT IN HOT GAS REHEAT MODE
AIR ENTERING EVAPORATOR - Ewb (F)
75 Dry Bulb
75 Dry Bulb
75 Dry Bulb
62.5 Wet Bulb
64 Wet Bulb
65.3 Wet Bulb
TEMP (F) AIR ENT
(50% Relative)
(56% Relative)
(60% Relative)
CONDENSER (Edb)
Air Entering Evaporator - Cfm
2250
3000
3750
2250
3000
3750
2250
3000
3750
TC
27.60
32.75
30.19
40.09
39.43
37.73
45.06
45.25
44.25
SHC
-3.12
5.20
6.71
3.75
5.24
6.75
3.77
5.26
6.78
80
kW
4.56
4.51
4.46
4.63
4.60
4.56
4.70
4.67
4.64
TC
35.40
33.78
31.20
41.14
40.51
38.80
46.15
46.37
45.38
SHC
4.67
6.17
7.69
4.71
6.21
7.73
4.74
6.24
7.76
75
kW
4.41
4.36
4.39
4.41
4.36
4.36
4.41
4.39
4.36
TC
36.36
34.71
32.18
42.10
41.47
39.77
47.08
47.31
46.32
SHC
5.63
7.14
8.66
5.67
7.18
8.71
5.70
7.21
8.74
70
kW
4.43
4.49
4.41
4.44
4.40
4.39
4.49
4.47
4.44
TC
38.25
36.64
34.15
43.97
43.37
41.72
48.98
49.22
48.26
SHC
7.56
9.09
10.62
7.60
9.13
10.66
7.62
9.15
10.69
60
kW
4.56
4.55
4.43
4.57
4.53
4.46
4.56
4.55
4.50
TC
40.15
38.60
36.14
45.95
45.37
43.73
50.57
50.97
49.56
SHC
9.48
11.03
12.58
9.52
11.07
12.62
9.54
11.10
12.64
50
kW
4.63
4.52
4.38
4.45
4.41
4.33
5.25
4.91
5.60
TC
42.18
40.62
38.11
47.80
47.25
45.43
52.65
52.75
51.83
SHC
11.41
12.98
14.54
11.45
13.02
14.58
11.47
13.04
14.60
40
kW
4.32
4.37
4.37
4.65
4.60
4.89
4.96
5.20
5.12
LEGEND
NOTES:
1. Direct interpolation is permissible. Do not extrapolate.
Edb - Entering Dry-Bulb
2. The following formulas may be used:
Ewb - Entering Wet-Bulb
kW - Compressor Motor Power Input
sensible capacity (Btuh)
Idb - Leaving Dry-Bulb
tldb = tedb –
1.10 x cfm
Iwb - Leaving Wet-Bulb
tlwb = Wet-bulb temperature corresponding to enthalpy of air
SHC - Sensible Heat Capacity (1000 Btuh) Gross
leaving evaporator coil (hlwb)
TC - Total Capacity (1000 Btuh) Gross
total capacity (Btuh)
hlwb = hewb –
4.5 x cfm
Where: hewb = Enthalpy of air entering evaporator coil
513 31 3209 02
42
Table 7 − COOLING CAPACITIES (cont.)
EAT (wb)
2550 Cfm
62
67
72
76
58
EAT (wb)
2975 Cfm
62
67
72
76
58
EAT (wb)
3400 Cfm
62
67
72
76
58
EAT (wb)
3825 Cfm
62
67
72
76
58
EAT (wb)
4250 Cfm
62
67
72
76
LEGEND:
Cfm
EAT(db)
EAT(wb)
SHC
TC
43
-
8.5 TONS
TC
SHC
TC
SHC
TC
SHC
TC
SHC
TC
SHC
85
EAT (db)
75
80
85
88.1
88.1
99.9
76.4
88.1
99.9
93.9
93.9
95.2
69.4
82.3
95.2
103.8
103.8
103.8
57.8
70.7
83.6
113.1
113.1
113.1
45.2
58.3
71.3
119.9
119.9
47.9
61.9
AMBIENT TEMPERATURE
95
105
EAT (db)
EAT (db)
75
80
85
75
80
85
84.1
84.1
95.3
79.6
79.6
90.3
72.8
84.1
95.3
69.0
79.6
90.3
88.6
88.6
92.6
82.8
82.8
89.7
66.8
79.7
92.6
64.1
76.9
89.7
98.7
98.7
98.7
93.0
93.0
93.0
55.6
68.5
81.4
53.1
66.1
79.0
108.0
108.0
108.0
102.4
102.4
102.4
43.2
56.3
69.3
41.1
54.1
67.1
114.7
114.7
109.0
109.0
46.0
60.1
44.1
58.1
75
74.9
64.9
76.6
61.0
86.7
50.5
96.1
38.7
-
TC
SHC
TC
SHC
TC
SHC
TC
SHC
TC
SHC
93.6
81.1
97.5
74.7
106.7
61.0
115.8
46.5
-
93.6
93.6
97.5
89.5
106.7
75.8
115.8
61.3
122.4
49.8
106.1
106.1
104.3
104.3
106.7
90.6
115.8
76.2
122.4
66.1
89.3
77.4
92.0
72.0
101.5
58.8
110.6
44.5
-
89.3
89.3
92.0
86.7
101.5
73.6
110.6
59.4
117.0
47.8
101.2
101.2
101.4
101.4
101.5
88.5
110.6
74.2
117.0
63.9
84.6
73.3
86.1
69.1
95.7
56.4
104.9
42.3
-
84.6
84.6
86.1
83.7
95.7
71.3
104.9
57.2
111.1
45.7
96.0
96.0
98.3
98.3
95.7
86.1
104.9
72.1
111.1
61.6
79.6
69.0
79.8
65.6
89.2
53.8
98.4
40.0
-
79.6
79.6
79.8
79.8
89.2
68.7
98.4
54.8
104.5
43.4
90.3
90.3
94.1
94.1
89.2
83.6
98.4
69.7
104.5
59.0
TC
SHC
TC
SHC
TC
SHC
TC
SHC
TC
SHC
98.1
85.0
100.0
79.3
109.0
63.9
117.9
47.6
-
98.1
98.1
100.0
95.8
109.0
80.5
117.9
64.1
124.2
51.2
111.3
111.3
112.3
112.3
109.0
97.2
117.9
80.6
124.2
69.0
93.7
81.2
94.9
76.3
103.6
61.8
112.5
45.6
-
93.7
93.7
94.9
92.5
103.6
78.5
112.5
62.1
118.6
49.2
106.2
106.2
108.6
108.6
103.6
95.2
112.5
78.7
118.6
66.7
88.9
77.0
89.1
73.2
97.6
59.4
106.6
43.4
-
88.9
88.9
89.1
89.1
97.6
76.1
106.6
60.0
112.5
47.0
100.8
100.8
104.9
104.9
97.6
92.9
106.6
76.6
112.5
64.4
83.7
72.5
83.8
68.8
91.0
56.8
100.0
41.1
-
83.7
83.7
83.8
83.8
91.0
73.5
100.0
57.6
105.7
44.7
94.9
94.9
98.7
98.7
91.0
90.3
100.0
74.2
105.7
61.9
TC
SHC
TC
SHC
TC
SHC
TC
SHC
TC
SHC
101.6
88.0
101.9
83.7
110.7
66.7
119.4
48.5
-
101.6
101.6
101.9
101.8
110.7
85.0
119.4
66.6
125.5
52.4
115.1
115.1
120.0
120.0
110.7
103.4
119.4
84.6
125.5
71.5
97.2
84.2
97.3
79.9
105.3
64.6
114.0
46.6
-
97.2
97.2
97.3
97.3
105.3
83.0
114.0
64.7
119.8
50.4
110.1
110.1
114.6
114.6
105.3
101.5
114.0
82.7
119.8
69.3
92.3
80.0
92.4
75.9
99.2
62.2
108.0
44.4
-
92.3
92.3
92.4
92.4
99.2
80.8
108.0
62.6
113.6
48.2
104.6
104.6
108.9
108.9
99.3
99.3
108.0
80.7
113.6
67.0
87.0
75.4
87.1
71.6
92.5
59.6
101.3
42.1
-
87.0
87.0
87.1
87.1
92.5
78.2
101.3
60.2
106.7
45.9
98.6
98.6
102.6
102.6
96.7
96.7
101.3
78.4
106.7
64.4
TC
SHC
TC
SHC
TC
SHC
TC
SHC
TC
SHC
104.4
90.4
104.4
85.8
112.1
69.2
120.7
49.4
-
104.4
104.4
104.4
104.4
112.1
89.2
120.7
68.9
126.6
53.5
118.3
118.3
123.0
123.0
112.1
109.2
120.7
88.4
126.6
73.9
99.9
86.6
99.9
82.1
106.6
67.2
115.1
47.4
-
99.9
99.9
99.9
99.9
106.6
87.3
115.1
67.0
120.8
51.5
113.2
113.2
117.8
117.8
107.5
107.5
115.1
86.5
120.8
71.7
95.0
82.3
95.0
78.1
100.4
64.9
109.0
45.3
-
95.0
95.0
95.0
95.0
100.4
85.1
109.0
64.9
114.5
49.3
107.6
107.6
112.0
112.0
105.3
105.3
109.0
84.6
114.5
69.4
89.5
77.6
89.6
73.6
93.6
62.3
102.2
42.9
-
89.5
89.5
89.6
89.6
93.6
82.5
102.2
62.6
107.4
46.9
101.5
101.5
105.6
105.6
102.7
102.7
102.2
82.3
107.4
66.8
RAS101
58
1−STAGE COOLING
115
EAT (db)
80
85
74.9
84.9
74.9
84.9
76.6
86.5
73.8
86.5
86.7
86.7
63.4
76.4
96.1
96.1
51.7
64.7
102.7
102.7
41.9
55.8
Do not operate in this region
Cubic feet per minute (supply air)
Entering air temperature (dry bulb)
Entering air temperature (wet bulb)
Sensible heat capacity
Total capacity
513 31 3209 02
Table 7 − COOLING CAPACITIES (cont.)
TC
SHC
TC
SHC
TC
SHC
TC
SHC
TC
SHC
75
89.7
77.8
94.3
71.0
105.0
59.0
115.9
46.4
-
EAT (wb)
2550 Cfm
62
67
72
76
58
TC
SHC
TC
SHC
TC
SHC
TC
SHC
TC
SHC
95.3
82.6
97.9
76.7
108.5
62.8
119.1
47.9
-
95.3
95.3
97.9
92.2
108.5
78.4
119.1
63.5
126.4
51.1
107.9
107.9
107.8
107.8
108.5
94.1
119.1
79.2
126.4
67.4
90.7
78.6
92.1
73.9
102.6
60.4
113.5
45.8
-
90.7
90.7
92.1
89.3
102.6
76.0
113.5
61.5
120.8
49.2
102.7
102.7
104.7
104.7
102.6
91.7
113.5
77.1
120.8
65.3
84.8
73.5
85.4
69.6
95.4
57.4
107.2
43.5
-
EAT (wb)
2975 Cfm
62
67
72
76
58
TC
SHC
TC
SHC
TC
SHC
TC
SHC
TC
SHC
100.0
86.7
101.1
81.5
111.1
66.2
121.3
49.2
-
100.0
100.0
101.1
98.7
111.1
83.9
121.3
66.7
128.3
52.7
113.3
113.3
115.8
115.8
111.1
101.6
121.3
84.3
128.3
70.7
95.2
82.6
95.7
78.2
105.1
63.9
115.6
47.1
-
95.2
95.2
95.7
94.9
105.1
81.6
115.6
64.7
122.6
50.7
107.9
107.9
111.7
111.7
105.1
99.3
115.6
82.3
122.6
68.6
EAT (wb)
3400 Cfm
62
67
72
76
58
TC
SHC
TC
SHC
TC
SHC
TC
SHC
TC
SHC
104.0
90.2
104.2
85.7
113.1
69.4
123.0
50.3
-
104.0
104.0
104.2
104.2
113.1
89.1
123.0
69.7
129.7
54.0
117.8
117.8
122.7
122.7
113.1
108.8
123.0
89.0
129.7
73.7
99.1
86.0
99.3
81.7
107.1
67.1
117.2
48.3
-
99.1
99.1
99.3
99.3
107.1
86.8
117.2
67.7
124.0
52.1
EAT (wb)
3825 Cfm
62
67
72
76
58
TC
SHC
TC
SHC
TC
SHC
TC
SHC
TC
SHC
107.4
93.1
107.5
88.4
114.7
72.5
124.3
51.3
-
107.4
107.4
107.5
107.5
114.7
94.0
124.3
72.4
130.7
55.3
121.7
121.7
126.6
126.6
115.6
115.6
124.3
93.4
130.7
76.5
102.5
88.9
102.6
84.4
108.7
70.2
118.5
49.3
-
102.5
102.5
102.6
102.6
108.7
91.8
118.5
70.5
125.0
53.5
EAT (wb)
4250 Cfm
62
67
72
76
85
101.6
101.6
97.9
97.9
105.0
86.1
115.9
73.6
123.7
63.3
75
85.2
73.9
88.7
68.2
99.3
56.6
110.4
44.3
-
8.5 TONS
AMBIENT TEMPERATURE
95
105
EA (dB)
EA (dB)
80
85
75
80
85.2
96.5
79.6
79.6
85.2
96.5
69.0
79.6
88.7
95.2
81.3
81.3
81.7
95.2
64.7
78.1
99.3
99.3
92.2
92.2
70.1
83.7
53.6
67.1
110.4 110.4
104.2
104.2
57.9
71.5
41.9
55.5
118.3 118.3
112.4
47.3
61.4
45.3
85
EA (dB)
80
89.7
89.7
94.3
84.4
105.0
72.6
115.9
60.0
123.7
49.3
RAS102
58
2−STAGE COOLING
85
90.1
90.1
91.5
91.5
92.2
80.7
104.2
69.1
112.4
59.3
75
73.8
64.0
74.3
60.6
84.1
50.3
96.0
38.8
-
115
EA (dB)
80
73.8
73.8
74.3
73.6
84.1
63.8
96.0
52.4
105.7
42.9
84.8
84.8
85.4
84.5
95.4
73.1
107.2
59.2
114.8
47.0
96.1
96.1
99.4
99.4
95.4
88.8
107.2
74.9
114.8
63.0
78.7
68.2
78.8
64.8
86.9
54.0
99.2
40.6
-
78.7
78.7
78.8
78.8
86.9
69.7
99.2
56.3
108.2
44.8
89.1
89.1
92.8
92.8
86.9
85.3
99.2
72.0
108.2
60.7
89.3
77.4
89.4
73.5
97.8
61.0
109.4
44.9
-
89.3
89.3
89.4
89.4
97.8
78.7
109.4
62.5
116.3
48.6
101.1
101.1
105.3
105.3
97.8
96.5
109.4
80.2
116.3
66.4
82.9
71.8
83.0
68.2
89.1
57.5
101.5
42.1
-
82.9
82.9
83.0
83.0
89.1
75.3
101.5
59.9
109.7
46.4
93.9
93.9
97.7
97.7
93.0
93.0
101.5
77.7
109.7
64.2
112.3
112.3
116.9
116.9
107.1
106.5
117.2
87.1
124.0
71.7
93.2
80.8
93.3
76.7
99.9
64.3
110.9
46.1
-
93.2
93.2
93.3
93.3
99.9
84.1
110.9
65.6
117.5
50.0
105.5
105.5
109.8
109.8
103.8
103.8
110.9
85.2
117.5
69.5
86.5
75.0
86.6
71.2
91.0
60.9
103.3
43.5
-
86.5
86.5
86.6
86.6
91.0
80.6
103.3
63.3
110.8
47.8
97.9
97.9
101.9
101.9
100.3
100.3
103.3
83.0
110.8
67.4
116.1
116.1
120.8
120.8
113.5
113.5
118.5
91.7
125.0
74.6
96.5
83.7
96.6
79.5
101.7
67.5
112.1
47.2
-
96.5
96.5
96.6
96.6
101.7
89.2
112.1
68.5
118.5
51.3
109.3
109.3
113.7
113.7
110.8
110.8
112.1
89.9
118.5
72.4
89.5
77.6
89.6
73.7
92.6
64.0
104.7
44.7
-
89.5
89.5
89.6
89.6
92.6
85.6
104.7
66.4
111.6
49.2
101.4
101.4
105.5
105.5
107.2
107.2
104.7
88.1
111.6
70.3
85
83.6
83.6
86.5
86.5
84.1
77.3
96.0
65.9
105.7
56.7
* See Minimum-Maximum Airflow Rating. Do not operate outside these limits.
LEGEND:
- Do not operate in this region
Cfm
- Cubic feet per minute (supply air)
EAT(db)
- Entering air temperature (dry bulb)
EAT(wb)
- Entering air temperature (wet bulb)
SHC
- Sensible heat capacity
TC
- Total capacity
513 31 3209 02
44
Table 7 − COOLING CAPACITIES (cont.)
2−STAGE COOLING
8.5 TONS
RAS102 COOLING CAPACITIES, UNIT WITH HOT GAS REHEAT IN SUBCOOLING MODE
AIR ENTERING EVAPORATOR - CFM
2550/0.04
3400/0.05
4250/0.07
TEMP (F) AIR ENT
CONDENSER (Edb)
Air Entering Evaporator - Ewb (F)
72
67
62
72
67
62
72
67
TC
119.20
107.44
96.41
126.95
114.98
103.92
131.87
119.81
SHC
50.63
63.94
77.40
59.17
76.72
94.21
66.80
88.44
75
kW
5.67
5.57
5.47
5.54
5.63
5.74
5.79
5.68
TC
110.40
99.22
88.76
117.63
106.26
95.77
122.21
110.77
SHC
42.39
56.16
70.07
50.42
68.45
86.38
57.71
79.86
85
kW
6.33
6.23
6.14
6.20
6.30
6.40
6.45
6.34
TC
101.37
90.79
80.86
108.07
97.31
87.39
112.29
101.47
SHC
33.97
48.22
62.56
41.46
60.01
78.39
48.40
71.09
95
kW
7.08
6.99
6.90
6.96
7.05
7.16
7.20
7.09
TC
92.04
82.06
72.71
98.19
88.05
78.72
102.07
91.86
SHC
25.31
40.06
54.88
32.24
51.33
70.17
38.85
62.06
105
kW
7.94
7.85
7.77
7.83
7.91
8.01
8.06
7.95
TC
82.37
73.01
64.24
87.95
78.45
69.73
91.46
81.90
115
SHC
16.38
31.65
46.95
22.71
42.37
61.69
28.94
52.74
kW
8.92
8.84
8.77
8.82
8.89
8.98
9.02
8.93
62
109.54
108.22
5.59
101.07
99.95
6.25
92.38
91.47
7.01
83.40
82.67
7.87
74.09
73.52
8.86
RAS102 COOLING CAPACITIES, UNIT WITH HOT GAS REHEAT IN HOT GAS REHEAT MODE
AIR ENTERING EVAPORATOR - Ewb (F)
75 Dry Bulb
75 Dry Bulb
75 Dry Bulb
62.5 Wet Bulb
64 Wet Bulb
65.3 Wet Bulb
TEMP (F) AIR ENT
(50% Relative)
(56% Relative)
(60% Relative)
CONDENSER (Edb)
Air Entering Evaporator - Cfm
2550
3400
4250
2550
3400
4250
2550
3400
4250
TC
37.61
33.13
26.77
44.74
41.60
36.46
50.96
48.99
44.93
SHC
-0.52
-0.63
-0.73
-0.46
-0.57
-0.67
-0.42
-0.53
-0.62
80
kW
5.88
5.68
5.44
6.13
5.97
5.76
6.35
6.24
6.06
TC
38.71
34.24
27.86
45.84
42.73
37.59
52.05
50.11
46.06
SHC
0.45
0.34
0.25
0.50
0.40
0.31
0.54
0.44
0.36
75
kW
5.68
5.47
5.22
5.94
5.78
5.56
6.18
6.07
5.88
TC
39.70
35.25
28.83
46.80
43.70
38.59
52.97
51.04
47.02
SHC
1.41
1.32
1.23
1.47
1.37
1.29
1.50
1.41
1.34
70
kW
5.65
5.42
5.24
5.97
5.79
5.53
6.26
6.13
5.91
TC
41.77
37.33
30.76
48.86
45.80
40.71
55.00
53.10
49.12
SHC
3.34
3.26
3.18
3.40
3.32
3.25
3.43
3.36
3.29
60
kW
5.42
5.15
5.17
5.80
5.59
5.30
6.16
6.01
5.75
TC
43.83
39.27
32.61
50.92
47.89
42.70
57.04
55.16
51.22
SHC
5.27
5.21
5.14
5.32
5.27
5.21
5.36
5.31
5.25
50
kW
5.18
5.15
5.17
5.62
5.39
5.05
6.04
5.87
5.59
TC
45.75
41.13
34.50
53.08
50.00
44.64
59.24
57.40
53.44
SHC
7.20
7.15
6.95
7.26
7.21
7.16
7.29
7.25
7.21
40
kW
4.79
4.98
4.80
5.25
5.01
5.23
5.68
5.51
5.21
LEGEND
Edb Ewb kW Idb Iwb SHC TC -
Entering Dry-Bulb
Entering Wet-Bulb
Compressor Motor Power Input
Leaving Dry-Bulb
Leaving Wet-Bulb
Sensible Heat Capacity (1000 Btuh) Gross
Total Capacity (1000 Btuh) Gross
NOTES:
1. Direct interpolation is permissible. Do not extrapolate.
2. The following formulas may be used:
sensible capacity (Btuh)
1.10 x cfm
tlwb = Wet-bulb temperature corresponding to enthalpy of air
leaving evaporator coil (hlwb)
tldb = tedb –
total capacity (Btuh)
4.5 x cfm
Where: hewb = Enthalpy of air entering evaporator coil
hlwb = hewb –
45
513 31 3209 02
Table 7 − COOLING CAPACITIES (cont.)
EAT (wb)
3000 Cfm
62
67
72
76
58
EAT (wb)
3500 Cfm
62
67
72
76
58
EAT (wb)
4000 Cfm
62
67
72
76
58
EAT (wb)
4500 Cfm
62
67
72
76
58
EAT (wb)
5000 Cfm
62
67
72
76
LEGEND:
Cfm
EAT(db)
EAT(wb)
SHC
TC
-
10 TONS
AMBIENT TEMPERATURE
95
105
EAT (db)
EAT (db)
80
85
75
80
101.7
115.2
96.6
96.6
101.7
115.2
83.8
96.6
106.5
112.3
99.9
99.9
96.6
112.3
77.8
93.4
117.8
117.8
111.3
111.3
82.5
98.3
64.1
79.8
128.5
128.5
122.0
122.0
67.4
83.2
49.1
64.9
136.3
136.3
129.5
54.7
71.2
52.3
TC
SHC
TC
SHC
TC
SHC
TC
SHC
TC
SHC
75
106.3
92.2
112.5
83.8
123.5
69.2
134.3
53.8
-
85
EAT (db)
80
106.3
106.3
112.5
99.5
123.5
85.0
134.3
69.6
142.4
56.8
TC
SHC
TC
SHC
TC
SHC
TC
SHC
TC
SHC
112.9
97.9
116.3
90.2
126.9
73.2
137.5
55.3
-
112.9
112.9
116.3
108.2
126.9
91.3
137.5
73.4
145.1
59.0
127.8
127.8
126.2
126.2
126.9
109.4
137.5
91.5
145.1
78.2
108.0
93.6
110.5
87.4
120.9
70.8
131.4
53.1
-
108.0
108.0
110.5
105.3
120.9
88.9
131.4
71.1
138.8
56.7
122.3
122.3
123.3
123.3
120.9
107.1
131.4
89.2
138.8
75.8
102.7
89.0
103.8
84.0
114.3
68.1
124.7
50.6
-
102.7
102.7
103.8
101.8
114.3
86.2
124.7
68.7
131.7
54.3
116.3
116.3
119.5
119.5
114.3
104.4
124.7
86.7
131.7
73.1
96.8
83.9
97.1
79.8
106.8
65.0
117.2
47.8
-
96.8
96.8
97.1
97.1
106.8
83.2
117.2
65.9
123.6
51.5
109.7
109.7
114.3
114.3
106.8
101.3
117.2
83.9
123.6
70.0
TC
SHC
TC
SHC
TC
SHC
TC
SHC
TC
SHC
117.8
102.2
119.1
95.8
129.4
76.9
139.7
56.7
-
117.8
117.8
119.1
115.9
129.4
97.3
139.7
76.8
147.0
60.6
133.5
133.5
136.0
136.0
129.4
117.7
139.7
97.0
147.0
81.7
113.0
98.0
113.5
92.8
123.3
74.5
133.5
54.4
-
113.0
113.0
113.5
112.6
123.3
95.0
133.5
74.6
140.5
58.4
128.0
128.0
132.5
132.5
123.3
115.4
133.5
94.7
140.5
79.3
107.5
93.3
107.7
88.6
116.5
71.8
126.6
51.9
-
107.5
107.5
107.7
107.7
116.5
92.3
126.6
72.1
133.2
55.8
121.8
121.8
126.7
126.7
116.5
112.8
126.6
92.3
133.2
76.5
101.5
88.0
101.6
83.6
108.9
68.8
118.8
49.1
-
101.5
101.5
101.6
101.6
108.9
89.3
118.8
69.3
124.9
53.0
115.0
115.0
119.6
119.6
109.8
109.8
118.8
89.5
124.9
73.5
TC
SHC
TC
SHC
TC
SHC
TC
SHC
TC
SHC
121.7
105.6
121.8
100.2
131.3
80.3
141.5
57.9
-
121.7
121.7
121.8
121.8
131.3
102.9
141.5
80.0
148.3
62.1
137.9
137.9
143.4
143.4
131.3
125.5
141.5
102.1
148.3
84.9
116.8
101.3
116.9
96.1
125.1
78.0
135.1
55.6
-
116.8
116.8
116.9
116.9
125.1
100.7
135.1
77.7
141.8
59.8
132.3
132.3
137.6
137.6
125.1
123.3
135.1
99.9
141.8
82.5
111.2
96.4
111.3
91.6
118.2
75.3
128.0
53.1
-
111.2
111.2
111.3
111.3
118.2
98.0
128.0
75.2
134.3
57.3
126.0
126.0
131.0
131.0
120.8
120.8
128.0
97.4
134.3
79.7
105.0
91.0
105.1
86.5
110.5
72.3
120.1
50.3
-
105.0
105.0
105.1
105.1
110.5
95.0
120.1
72.4
125.8
54.4
118.9
118.9
123.7
123.7
117.7
117.7
120.1
94.6
125.8
76.6
TC
SHC
TC
SHC
TC
SHC
TC
SHC
TC
SHC
125.0
108.4
125.1
102.9
132.8
83.6
142.8
59.0
-
125.0
125.0
125.1
125.1
132.8
108.3
142.8
82.9
149.4
63.4
141.6
141.6
147.2
147.2
133.0
133.0
142.8
106.9
149.4
87.9
120.0
104.0
120.1
98.8
126.5
81.2
136.3
56.7
-
120.0
120.0
120.1
120.1
126.5
106.0
136.3
80.7
142.8
61.2
135.9
135.9
141.4
141.4
130.8
130.8
136.3
104.7
142.8
85.5
114.3
99.1
114.4
94.1
119.6
78.6
129.1
54.1
-
114.3
114.3
114.4
114.4
119.6
103.4
129.1
78.2
135.1
58.6
129.5
129.5
134.7
134.7
128.2
128.2
129.1
102.2
135.1
82.7
107.9
93.6
108.0
88.9
111.8
75.6
121.1
51.3
-
107.9
107.9
108.0
108.0
111.8
100.3
121.1
75.4
126.5
55.6
122.3
122.3
127.2
127.2
125.1
125.1
121.1
99.4
126.5
79.4
RAS121
58
1−STAGE COOLING
85
120.5
120.5
115.2
115.2
123.5
100.7
134.3
85.5
142.4
73.3
75
101.7
88.2
106.5
81.0
117.8
66.8
128.5
51.6
-
85
109.4
109.4
109.0
109.0
111.3
95.5
122.0
80.7
129.5
68.8
115
EAT (db)
75
80
91.0
91.0
78.9
91.0
92.7
92.7
74.2
89.7
104.0
104.0
61.0
76.8
114.7
114.7
46.3
62.1
121.8
49.7
85
103.1
103.1
105.2
105.2
104.0
92.5
114.7
77.9
121.8
66.2
Do not operate in this region
Cubic feet per minute (supply air)
Entering air temperature (dry bulb)
Entering air temperature (wet bulb)
Sensible heat capacity
Total capacity
513 31 3209 02
46
Table 7 − COOLING CAPACITIES (cont.)
EAT (wb)
3000 Cfm
62
67
72
76
58
EAT (wb)
3500 Cfm
62
67
72
76
58
EAT (wb)
4000 Cfm
62
67
72
76
58
EAT (wb)
4500 Cfm
62
67
72
76
58
EAT (wb)
5000 Cfm
62
67
72
76
10 TONS
AMBIENT TEMPERATURE
95
105
EAT (db)
EAT (db)
80
85
75
80
102.5
116.2
96.8
96.8
102.5
116.2
83.9
96.8
107.1
113.4
99.7
99.7
97.4
113.4
78.0
93.9
118.4
118.4
111.5
111.5
83.2
99.2
64.3
80.3
129.7
129.7
122.8
122.8
68.1
84.2
49.3
65.4
139
139
131.9
55.6
72.1
53.1
TC
SHC
TC
SHC
TC
SHC
TC
SHC
TC
SHC
75
107.6
93.2
113.6
84.6
124.4
69.7
135.8
54.3
-
85
EAT (db)
80
107.6
107.6
113.6
100.6
124.4
85.7
135.8
70.4
145.3
57.8
TC
SHC
TC
SHC
TC
SHC
TC
SHC
TC
SHC
114.2
98.9
117.2
91.1
127.8
73.8
139.4
56.0
-
114.2
114.2
117.2
109.5
127.8
92.3
139.4
74.6
148.8
60.2
129.4
129.4
127.9
127.9
127.8
110.8
139.4
93.1
148.8
79.5
108.9
94.3
111.0
88.1
121.7
71.3
133.0
53.7
-
108.9
108.9
111.0
106.4
121.7
89.8
133.0
72.2
142.2
58.0
123.4
123.4
124.7
124.7
121.7
108.3
133
90.8
142.2
77.1
102.9
89.1
104.0
83.9
114.5
68.4
125.8
51.0
-
102.9
102.9
104.0
101.7
114.5
87.0
125.8
69.6
134.9
55.4
116.6
116.6
119.5
119.5
114.5
105.5
125.8
88.2
134.9
74.5
96.3
83.4
96.5
79.3
106.6
65.2
117.9
48.1
-
96.3
96.3
96.5
96.5
106.6
83.8
117.9
66.7
126.8
52.7
109.1
109.1
113.7
113.7
106.6
102.3
117.9
85.4
126.8
71.6
TC
SHC
TC
SHC
TC
SHC
TC
SHC
TC
SHC
119.0
103.1
120.3
96.5
130.5
77.7
142.1
57.6
-
119.0
119.0
120.3
116.8
130.5
98.6
142.1
78.4
151.4
62.3
134.9
134.9
137.1
137.1
130.5
119.5
142.1
99.3
151.4
83.8
114.0
98.7
114.7
93.0
124.1
75.2
135.5
55.2
-
114.0
114.0
114.7
112.9
124.1
96.2
135.5
76.1
144.7
60.0
129.2
129.2
132.8
132.8
124.1
117.2
135.5
97.1
144.7
81.4
108.0
93.6
108.2
88.9
116.8
72.3
128.2
52.5
-
108.0
108.0
108.2
108.2
116.8
93.3
128.2
73.6
137.1
57.5
122.4
122.4
127.5
127.5
116.8
114.4
128.2
94.6
137.1
78.8
101.1
87.6
101.3
83.2
108.7
69.1
120.0
49.7
-
101.1
101.1
101.3
101.3
108.7
90.1
120.0
70.7
-
114.6
114.6
119.3
119.3
111.1
111.1
120.0
91.8
-
TC
SHC
TC
SHC
TC
SHC
TC
SHC
TC
SHC
123.0
106.6
123.4
100.9
132.6
81.4
144.2
59.0
-
123.0
123.0
123.4
122.7
132.6
104.6
144.2
82.1
153.4
64.1
139.5
139.5
144.4
144.4
132.6
127.9
144.2
105.2
153.4
87.8
117.8
102.1
117.9
96.9
126.0
78.9
137.4
56.6
-
117.8
117.8
117.9
117.9
126
102.3
137.4
79.8
146.6
61.9
133.6
133.6
139.0
139
126.0
125.7
137.4
103.1
146.6
85.6
111.9
97.0
112.0
92.1
118.7
76.1
129.9
54.0
-
111.9
111.9
112.0
112.0
118.7
99.5
129.9
77.3
138.9
59.4
126.9
126.9
132.0
132
122.9
122.9
129.9
100.7
138.9
83
105.3
91.2
105.4
86.6
110.4
72.9
121.6
51.1
-
105.3
105.3
105.4
105.4
110.4
96.2
121.6
74.5
-
119.3
119.3
124.2
124.2
119.6
119.6
121.6
98
-
TC
SHC
TC
SHC
TC
SHC
TC
SHC
TC
SHC
126.5
109.6
126.5
104.0
134.2
84.9
145.8
60.3
-
126.5
126.5
126.5
126.5
134.2
110.4
145.8
85.6
155.1
65.9
143.3
143.3
149.1
149.1
135.9
135.9
145.8
110.8
155.1
91.5
121.2
105.0
121.3
99.7
127.5
82.4
139.0
57.9
-
121.2
121.2
121.3
121.3
127.5
108.1
139.0
83.4
148.2
63.7
137.4
137.4
142.9
142.9
133.8
133.8
139.0
108.9
148.2
89.5
115.1
99.8
115.2
94.7
120.1
79.6
131.3
55.3
-
115.1
115.1
115.2
115.2
120.1
105.3
131.3
81.0
-
130.5
130.5
135.8
135.8
131.0
131
131.3
106.6
-
108.4
93.9
108.5
89.1
111.9
76.4
122.9
52.5
-
108.4
108.4
108.5
108.5
111.9
102.0
122.9
78.2
-
122.8
122.8
127.8
127.8
127.6
127.6
122.9
104
-
RAS120
58
2−STAGE COOLING
85
121.9
121.9
116.5
116.5
124.4
101.7
135.8
86.6
145.3
74.3
75
102.5
88.8
107.1
81.5
118.4
67.1
129.7
52.0
-
85
109.7
109.7
109.8
109.8
111.5
96.3
122.8
81.6
131.9
69.6
115
EAT (db)
75
80
90.5
90.5
78.4
90.5
91.8
91.8
73.7
89.3
103.3
103.3
60.8
76.8
115
115
46.4
62.5
124.1
50.4
85
102.6
102.6
104.9
104.9
103.3
92.8
115
78.6
124.1
66.9
* See Minimum-Maximum Airflow Ratings. Do not operate outside these limits.
LEGEND:
- Do not operate in this region
Cfm
- Cubic feet per minute (supply air)
EAT(db)
- Entering air temperature (dry bulb)
EAT(wb)
- Entering air temperature (wet bulb)
SHC
- Sensible heat capacity
TC
- Total capacity
47
513 31 3209 02
Table 7 − COOLING CAPACITIES (cont.)
2−STAGE COOLING
10 TONS
RAS120 COOLING CAPACITIES, UNIT WITH HOT GAS REHEAT IN SUBCOOLING MODE
AIR ENTERING EVAPORATOR - CFM
3000/0.04
4000/0.06
5000/0.07
TEMP (F) AIR ENT
CONDENSER (Edb)
Air Entering Evaporator - Ewb (F)
72
67
62
72
67
62
72
67
TC
142.85
129.44
116.93
152.09
138.44
125.76
157.99
144.23
SHC
58.38
74.88
91.58
67.96
89.45
111.02
76.63
102.94
75
kW
7.19
6.97
6.79
6.92
7.12
7.35
7.45
7.22
TC
132.33
119.68
107.86
140.92
128.03
116.10
146.41
133.41
SHC
48.44
65.56
82.83
57.37
79.50
101.68
65.65
92.58
85
kW
7.98
7.77
7.58
7.72
7.92
8.14
8.25
8.01
TC
121.41
109.52
98.43
129.35
117.22
106.04
134.43
122.20
SHC
38.19
55.92
73.78
46.47
69.22
92.01
54.34
81.92
95
kW
8.87
8.66
8.48
8.61
8.80
9.03
9.14
8.90
TC
110.04
98.92
88.56
117.27
105.94
95.53
121.88
110.46
SHC
27.59
45.94
64.39
35.16
58.57
81.98
42.56
70.82
105
kW
9.86
9.66
9.48
9.61
9.79
10.02
10.12
9.89
TC
98.09
87.74
78.13
104.62
94.08
84.45
108.76
98.13
115
SHC
16.52
35.47
54.53
23.37
47.44
71.46
30.32
59.25
kW
10.95
10.76
10.60
10.72
10.89
11.10
11.19
10.98
62
132.06
127.93
7.02
121.98
118.12
7.82
111.50
107.96
8.71
100.54
97.40
9.70
89.01
86.31
10.81
RAS120 COOLING CAPACITIES, UNIT WITH HOT GAS REHEAT IN HOT GAS REHEAT MODE
AIR ENTERING EVAPORATOR - Ewb (F)
75 Dry Bulb
75 Dry Bulb
75 Dry Bulb
62.5 Wet Bulb
64 Wet Bulb
65.3 Wet Bulb
TEMP (F) AIR ENT
(50% Relative)
(56% Relative)
(60% Relative)
CONDENSER (Edb)
80
75
70
60
50
40
LEGEND
Edb Ewb kW Idb Iwb SHC TC -
TC
SHC
kW
TC
SHC
kW
TC
SHC
kW
TC
SHC
kW
TC
SHC
kW
TC
SHC
kW
3000
44.78
-0.44
6.96
45.84
0.53
6.77
46.91
1.51
6.54
48.88
3.44
6.45
50.83
5.38
6.46
52.82
7.32
6.29
4000
39.41
-0.57
6.77
40.46
0.40
6.56
41.48
1.38
6.32
43.42
3.34
6.16
45.28
5.29
6.01
47.29
7.24
6.09
Entering Dry-Bulb
Entering Wet-Bulb
Compressor Motor Power Input
Leaving Dry-Bulb
Leaving Wet-Bulb
Sensible Heat Capacity (1000 Btuh) Gross
Total Capacity (1000 Btuh) Gross
5000
31.89
-0.69
6.52
32.86
0.29
6.29
33.50
1.27
6.02
35.76
3.24
6.70
37.67
5.20
6.34
39.50
7.20
6.12
Air Entering Evaporator - Cfm
3000
4000
5000
53.22
49.44
43.38
-0.37
-0.51
-0.61
7.26
7.13
6.91
54.28
50.51
44.45
0.60
0.47
0.37
7.11
6.95
6.72
55.36
51.59
45.50
1.57
1.45
1.35
6.90
6.74
6.49
57.29
53.56
47.48
3.51
3.40
3.31
6.93
6.72
6.39
59.22
55.52
49.43
5.45
5.36
5.28
6.98
6.71
6.29
61.14
57.48
51.39
7.38
7.31
7.24
7.05
6.72
6.29
3000
60.56
-0.33
7.54
61.61
0.64
7.41
62.69
1.61
7.23
64.56
3.55
7.38
66.05
5.48
8.15
68.23
7.43
7.78
4000
58.12
-0.46
7.45
59.19
0.52
7.31
60.28
1.50
7.13
62.16
3.45
7.24
64.03
5.40
7.38
65.88
7.36
7.55
5000
53.32
-0.56
7.27
54.40
0.42
7.12
55.49
1.40
6.92
57.42
3.37
6.96
59.34
5.33
7.02
61.25
7.29
7.10
NOTES:
1. Direct interpolation is permissible. Do not extrapolate.
2. The following formulas may be used:
sensible capacity (Btuh)
1.10 x cfm
tlwb = Wet-bulb temperature corresponding to enthalpy of air
leaving evaporator coil (hlwb)
tldb = tedb –
total capacity (Btuh)
4.5 x cfm
Where: hewb = Enthalpy of air entering evaporator coil
hlwb = hewb –
513 31 3209 02
48
Table 7 − COOLING CAPACITIES (cont.)
EAT (wb)
3600 Cfm
62
67
72
76
58
EAT (wb)
4200 Cfm
62
67
72
76
58
EAT (wb)
4800 Cfm
62
67
72
76
58
EAT (wb)
5400 Cfm
62
67
72
76
58
EAT (wb)
6000 Cfm
62
67
72
76
12.5 TONS
AMBIENT TEMPERATURE
95
105
EAT (db)
EAT (db)
80
85
75
80
121.7
137.6
115.0
115.0
121.7
137.6
99.9
115.0
131.1
131.1
123.8
123.8
111.2
127.7
91.4
108.0
142.0
142.0
136.2
136.2
93.1
109.2
74.7
91.0
152.4
152.4
147.2
147.2
75.2
91.7
56.8
73.3
160.0
160
155.1
61.1
80.9
59.5
TC
SHC
TC
SHC
TC
SHC
TC
SHC
TC
SHC
75
127.6
110.3
136.1
96.6
146.2
78.5
155.9
60.1
-
85
EAT (db)
80
127.6
126.6
136.1
112.8
146.2
94.4
155.9
76.6
163.0
62.0
TC
SHC
TC
SHC
TC
SHC
TC
SHC
TC
SHC
132.2
115.0
139.6
102.5
149.5
81.8
159.0
61.4
-
132.2
132.2
139.6
120.8
149.5
99.6
159.0
79.6
165.7
64.6
149.5
149.5
139.6
139
149.5
117.4
159.0
97.8
165.7
87.7
128.2
111.5
134.7
100.8
145.4
80.6
155.5
60.2
-
128.2
128.2
134.7
119.4
145.4
98.7
155.5
78.5
162.8
63.5
144.9
144.9
138
138
145.4
116.8
155.5
96.8
162.8
86.3
121.9
106.0
128.0
98.1
139.6
78.5
150.3
58.3
-
TC
SHC
TC
SHC
TC
SHC
TC
SHC
TC
SHC
136.7
118.9
142.2
107.7
152.1
84.8
161.3
62.6
-
136.7
136.7
142.2
127.8
152.1
104.3
161.3
82.2
167.7
66.4
154.5
154.5
147.8
147.8
152.1
123.7
161.3
101.9
167.7
91.4
133.0
115.7
137.4
106.2
148.0
83.8
157.8
61.4
-
133.0
133.0
137.4
126.7
148
103.8
157.8
81.4
164.9
65
150.3
150.3
147.1
147.1
148
123.7
157.8
101.3
164.9
89.2
TC
SHC
TC
SHC
TC
SHC
TC
SHC
TC
SHC
140.5
122.2
144.3
112.2
154.2
87.6
163.1
63.6
-
140.5
140.5
144.3
133.9
154.2
108.6
163.1
84.6
169.3
67.6
158.8
158.8
155.7
155.7
154.2
129.6
163.1
105.6
169.3
93.7
136.9
119
139.6
110.9
150.0
86.8
159.7
62.5
-
136.9
136.9
139.6
132.9
150.0
108.5
159.7
83.9
166.5
66.4
TC
SHC
TC
SHC
TC
SHC
TC
SHC
TC
SHC
143.6
124.9
146.1
116.1
155.8
90.1
164.5
64.5
-
143.6
143.6
146.1
139.3
155.8
112.6
164.5
86.7
170.6
68.7
162.3
162.3
162.4
162.4
155.8
135
164.5
108.9
170.6
95.8
140.1
121.8
141.7
114.7
151.6
89.6
161.2
63.5
-
140.1
140.1
141.7
138.1
151.6
112.8
161.2
86.3
167.8
67.5
RAS150
58
2−STAGE COOLING
85
142.9
142.9
136.1
129.0
146.2
110.3
155.9
93.2
163
81.8
75
121.7
105.8
131.1
94.7
142.0
76.9
152.4
58.7
-
85
130
130
124.5
124.5
136.2
107.3
147.2
89.7
155.1
79.3
75
108.3
94.1
114.9
87.3
128.8
71.7
140.1
54.2
-
115
EAT (db)
80
108.3
108.3
114.9
103.8
128.8
88.1
140.1
70.6
148.2
57.0
121.9
121.9
128.0
116.8
139.6
96.9
150.3
76.7
157.8
61.5
137.8
137.8
135.6
135.6
139.6
115.2
150.3
95
157.8
83.3
115.0
99.9
119.1
93.9
132.1
75.7
143.1
55.8
-
115.0
115.0
119.1
112.6
132.1
94.3
143.1
74.2
150.8
58.9
130.1
130.1
131.2
131.2
132.1
112.8
143.1
92.5
150.8
79.9
127.7
111.0
131.0
103.6
142.2
82.0
152.5
59.7
-
127.7
127.7
131.0
124.2
142.2
102.3
152.5
79.7
159.9
63.1
144.3
144.3
144.7
144.7
142.2
122.6
152.5
99.8
159.9
86.4
120.6
104.9
122.8
99.3
134.6
79.4
145.4
57.2
-
120.6
120.6
122.8
119.8
134.6
99.9
145.4
77.3
152.8
60.5
136.4
136.4
140.3
140.3
134.6
120.4
145.4
97.5
152.8
83.1
154.7
154.7
155
155
150.0
130.1
159.7
105.4
166.5
91.7
131.8
114.7
133.5
108.1
144.2
85.2
154.3
60.8
-
131.8
131.8
133.5
130.2
144.2
107.3
154.3
82.5
161.5
64.5
149
149
152.4
152.4
144.2
129.4
154.3
104.2
161.5
89.2
125.2
108.9
125.8
103.9
136.7
82.8
147.1
58.4
-
125.2
125.2
125.8
125.8
136.7
105.1
147.1
80.2
154.2
61.9
141.6
141.6
147.8
147.8
136.7
127.4
147.1
102
154.2
86.1
158.3
158.3
161.5
161.5
151.6
136
161.2
109.1
167.8
94.1
135.1
117.5
135.6
112.1
145.9
88.3
155.8
61.9
-
135.1
135.1
135.6
135.6
145.9
112.0
155.8
85.1
162.8
65.7
152.7
152.7
159.2
159.2
145.9
135.8
155.8
108.2
162.8
91.8
128.7
111.9
128.8
106.4
138.3
85.9
148.5
59.6
-
128.7
128.7
128.8
128.8
138.3
110.0
148.5
82.9
155.5
63.3
145.5
145.5
151.2
151.2
138.3
134.1
148.5
106.3
155.5
88.8
85
122.6
122.6
120.3
120.3
128.8
104.6
140.1
87.0
148.2
76.3
* See Minimum-Maximum Airflow Rating. Do not operate outside these limits.
LEGEND:
- Do not operate in this region
Cfm
- Cubic feet per minute (supply air)
EAT(db)
- Entering air temperature (dry bulb)
EAT(wb)
- Entering air temperature (wet bulb)
SHC
- Sensible heat capacity
TC
- Total capacity
49
513 31 3209 02
Table 7 − COOLING CAPACITIES (cont.)
2−STAGE COOLING
12.5 TONS
RAS150 COOLING CAPACITIES, UNIT WITH HOT GAS REHEAT IN SUBCOOLING MODE
AIR ENTERING EVAPORATOR - CFM
3750/0.02
5000/0.06
6250/0.05
TEMP (F) AIR ENT
CONDENSER (Edb)
Air Entering Evaporator - Ewb (F)
72
67
62
72
67
62
72
67
TC
183.66
166.86
151.43
194.90
177.83
162.05
201.97
184.84
SHC
79.39
100.52
121.91
91.70
119.42
147.05
102.94
137.00
75
kW
9.82
9.63
9.46
9.58
9.76
9.96
10.04
9.84
TC
172.71
156.78
142.09
183.32
167.13
152.17
189.98
173.73
SHC
69.03
90.92
112.95
80.69
109.17
137.51
91.49
126.33
85
kW
10.82
10.63
10.45
10.57
10.76
10.96
11.04
10.84
TC
161.37
146.24
132.38
171.36
156.04
141.86
177.62
162.22
SHC
58.44
81.04
103.77
69.42
98.67
127.71
79.83
115.45
95
kW
11.92
11.73
11.56
11.68
11.86
12.05
12.14
11.93
TC
149.57
135.32
122.21
158.89
144.45
131.10
164.74
150.27
SHC
47.57
70.92
94.32
57.85
87.91
117.61
67.79
104.26
105
kW
13.12
12.94
12.77
12.89
13.06
13.24
13.32
13.13
TC
137.22
123.88
111.55
145.85
132.33
119.84
151.27
137.71
115
SHC
36.31
60.47
84.57
45.87
76.77
107.19
55.34
92.66
kW
14.41
14.25
14.10
14.20
14.35
14.53
14.59
14.42
62
170.53
166.71
9.67
160.25
156.65
10.67
149.50
146.15
11.77
138.35
135.30
12.97
126.67
123.98
14.28
RAS150 COOLING CAPACITIES, UNIT WITH HOT GAS REHEAT IN HOT GAS REHEAT MODE
AIR ENTERING EVAPORATOR - Ewb (F)
75 Dry Bulb
75 Dry Bulb
75 Dry Bulb
62.5 Wet Bulb
64 Wet Bulb
65.3 Wet Bulb
TEMP (F)AIR ENT
(50% Relative)
(56% Relative)
(60% Relative)
CONDENSER(Edb)
80
75
70
60
50
40
LEGEND
Edb Ewb kW Idb Iwb SHC TC -
TC
SHC
kW
TC
SHC
kW
TC
SHC
kW
TC
SHC
kW
TC
SHC
kW
TC
SHC
kW
3750
52.42
-0.39
9.65
53.45
0.59
9.09
54.33
1.56
8.81
55.47
3.50
8.36
58.33
5.47
8.98
60.33
7.42
9.16
5000
45.88
-0.54
9.39
46.63
0.44
8.83
46.91
1.41
8.53
49.48
3.38
8.84
51.72
5.35
9.25
53.69
7.31
9.88
6250
36.99
-0.67
9.07
36.10
0.30
8.49
37.58
1.29
8.62
40.48
3.27
8.98
42.81
5.24
9.43
46.89
7.22
9.06
Air Entering Evaporator - Cfm
3750
5000
6250
62.64
58.07
51.07
-0.31
-0.46
-0.58
9.97
9.77
9.50
63.77
59.11
51.87
0.67
0.52
0.40
9.39
9.20
8.94
64.77
60.01
52.30
1.64
1.50
1.38
9.15
8.94
8.65
66.62
62.07
54.88
3.59
3.47
3.36
9.88
9.56
9.10
68.72
63.93
55.84
5.54
5.43
5.32
9.33
8.97
8.73
70.67
65.93
49.83
7.49
7.39
7.23
9.50
9.05
9.47
3750
71.56
-0.26
10.25
72.76
0.72
9.67
73.80
1.70
9.46
75.68
3.65
9.83
77.74
5.60
9.55
79.46
7.55
10.31
5000
68.64
-0.40
10.11
69.80
0.58
9.53
70.80
1.56
9.31
72.76
3.52
9.64
74.77
5.49
9.33
76.62
7.45
10.00
6250
63.23
-0.52
9.89
64.31
0.47
9.32
65.24
1.45
9.08
67.28
3.42
9.31
69.24
5.39
9.70
71.24
7.37
9.48
Entering Dry-Bulb
Entering Wet-Bulb
Compressor Motor Power Input
Leaving Dry-Bulb
Leaving Wet-Bulb
Sensible Heat Capacity (1000 Btuh) Gross
Total Capacity (1000 Btuh) Gross
513 31 3209 02
50
Table 7 − COOLING CAPACITIES (cont.)
2−STAGE COOLING
15 TONS
Ambient Temperature
95
105
EA (dB)
EA (dB)
80
85
75
80
149.4
169.1
141.6
141.6
149.4
169.1
123.0
141.6
158.0
162.6
147.6
147.6
140.6
162.6
113.5
135.3
175.6
175.6
165.6
165.6
120.2
142.3
94.0
116.1
192.0
192.0
182.9
182.9
97.9
120.2
72.1
94.4
203.1
203.1
­
193.8
79.3
103.8
­
76.0
THC
SHC
THC
SHC
THC
SHC
THC
SHC
THC
SHC
75
156.6
134.7
166.7
122.8
184.1
101.6
200.3
78.7
­
­
85
EA (dB)
80
156.6
154.9
166.7
144.9
184.1
123.7
200.3
101.1
211.4
82.2
85
160.2
160.2
157.2
157.2
165.6
138.2
182.9
116.7
193.8
100.2
75
133.3
115.7
136.8
107.4
154.5
89.4
172.2
68.2
­
­
115
EA (dB)
80
133.3
133.3
136.8
128.8
154.5
111.5
172.2
90.5
183.9
72.6
THC
SHC
THC
SHC
THC
SHC
THC
SHC
THC
SHC
165.2
143.5
172.3
131.6
189.5
107.2
205.0
80.9
­
­
165.2
165.2
172.3
156.6
189.5
132.4
205.0
106.1
215.4
85.0
186.9
186.9
181.7
181.7
189.5
157.5
205.0
131.3
215.4
113.0
158.2
137.4
163.4
127.1
180.9
103.8
196.5
77.7
­
­
158.2
158.2
163.4
152.0
180.9
129.0
196.5
102.9
206.8
82.0
179.0
179.0
176.9
176.9
180.9
154.1
196.5
128.1
206.8
109.8
150.0
130.2
153.1
120.5
170.7
99.9
187.1
74.4
­
­
150.0
150.0
153.1
144.9
170.7
125.1
187.1
99.5
197.1
78.8
169.7
169.7
169.3
169.3
170.7
150.4
187.1
124.7
197.1
106.4
141.3
122.7
143.4
114.1
159.1
95.3
176.4
70.6
­
­
141.3
141.3
143.4
137.8
159.1
120.6
176.4
95.8
186.9
75.4
160.0
160.0
161.4
161.4
159.1
145.8
176.4
121.0
186.9
102.8
THC
SHC
THC
SHC
THC
SHC
THC
SHC
THC
SHC
172.7
150.0
176.6
139.6
193.6
112.3
208.4
82.7
­
­
172.7
172.7
176.6
167.7
193.6
140.3
208.4
110.5
218.2
87.5
195.4
195.4
195.7
195.7
193.6
168.3
208.4
138.3
218.2
118.6
165.5
143.8
168.1
133.2
184.8
108.9
199.6
79.6
­
­
165.5
165.5
168.1
160.4
184.8
137.0
199.6
107.3
209.5
84.5
187.3
187.3
187.6
187.6
184.8
165.2
199.6
135.1
209.5
115.2
157.1
136.4
158.9
127.1
174.7
105.2
190.2
76.2
­
­
157.1
157.1
158.9
153.7
174.7
133.5
190.2
104.0
199.5
81.1
177.8
177.8
180.2
180.2
174.7
161.7
190.2
131.8
199.5
111.3
148.1
128.6
148.9
120.7
162.7
100.7
179.5
72.6
­
­
148.1
148.1
148.9
146.4
162.7
129.0
179.5
100.6
189.0
77.5
167.7
167.7
172.1
172.1
162.7
157.3
179.5
128.5
189.0
107.3
THC
SHC
THC
SHC
THC
SHC
THC
SHC
THC
SHC
178.8
155.3
181.0
144.1
196.8
117.0
211.0
84.3
­
­
178.8
178.8
181.0
173.9
196.8
147.7
211.0
114.5
220.2
89.5
202.4
202.4
203.6
203.6
196.8
178.4
211.0
144.7
220.2
122.8
171.6
149.0
173.0
139.1
187.9
113.7
202.2
81.2
­
­
171.6
171.6
173.0
168.3
187.9
144.5
202.2
111.5
211.5
86.4
194.2
194.2
197.5
197.5
187.9
175.4
202.2
141.7
211.5
119.4
163.1
141.6
163.8
133.3
177.7
110.1
192.5
77.9
­
­
163.1
163.1
163.8
161.7
177.7
141.1
192.5
108.1
201.3
83.0
184.6
184.6
190.1
190.1
177.7
172.2
192.5
138.4
201.3
115.4
153.8
133.5
153.9
126.7
165.5
105.6
181.8
74.4
­
­
153.8
153.8
153.9
153.9
165.5
136.8
181.8
104.9
190.6
79.4
174.1
174.1
181.1
181.1
167.9
167.9
181.8
135.4
190.6
111.5
THC
183.9
183.9
208.2
176.6
176.6
199.8
SHC
159.7
183.9
208.2
153.3
176.6
199.8
THC
185.1
185.1
212.5
177.1
177.1
206.2
62
SHC
149.5
181.0
212.5
144.5
175.4
206.2
THC
199.3
199.3
199.3
190.3
190.3
190.3
67
SHC
121.3
154.6
187.9
118.1
151.6
185.1
THC
213.0
213.0
213.0
204.1
204.1
204.1
72
SHC
85.8
118.2
150.5
82.7
115.2
147.7
THC
­
221.9
221.9
­
213.0
213.0
76
SHC
­
91.2
126.5
­
88.2
123.1
* See Minimum-Maximum Airflow Ratings. Do not operate outside these limits.
LEGEND:
- Do not operate in this region
Cfm
- Cubic feet per minute (supply air)
EAT(db)
- Entering air temperature (dry bulb)
EAT(wb)
- Entering air temperature (wet bulb)
SHC
- Sensible heat capacity
TC
- Total capacity
168.2
146.0
168.3
138.7
180.0
114.4
194.2
79.4
­
­
168.2
168.2
168.3
168.3
180.0
148.1
194.2
111.9
202.7
84.7
190.3
190.3
197.9
197.9
181.7
181.7
194.2
144.4
202.7
119.2
158.6
137.7
158.7
130.8
167.8
110.1
183.5
76.0
­
­
158.6
158.6
158.7
158.7
167.8
144.0
183.5
108.8
191.8
81.2
179.5
179.5
186.7
186.7
177.8
177.8
183.5
141.6
191.8
115.3
RAS180
58
EAT (wb)
4500 Cfm
62
67
72
76
58
EAT (wb)
5250 Cfm
62
67
72
76
58
EAT (wb)
6000 Cfm
62
67
72
76
58
EAT (wb)
6750 Cfm
62
67
72
76
51
EAT (wb)
7500 Cfm
58
85
175.2
175.2
166.9
166.9
184.1
145.7
200.3
123.5
211.4
107.0
75
149.4
129.8
158.0
118.6
175.6
98.1
192.0
75.5
­
­
85
150.9
150.9
150.3
150.3
154.5
133.6
172.2
112.7
183.9
96.5
513 31 3209 02
Table 7 − COOLING CAPACITIES (cont.)
TEMP (F) AIR ENT
CONDENSER (Edb)
75
85
95
105
115
TC
SHC
kW
TC
SHC
kW
TC
SHC
kW
TC
SHC
kW
TC
SHC
kW
72
204.4
98.9
11.57
189.2
79.5
12.59
174.0
60.0
13.68
158.8
40.5
14.67
143.6
21.0
15.77
2−STAGE COOLING
RAS180 Cooling Capacities, Subcooling Mode
AIR ENTERING EVAPORATOR - CFM
4500/0.02
6000/0.06
Air Entering Evaporator - Ewb (F)
67
62
72
67
62
186.3
168.2
218.4
199.6
180.9
118.1
137.2
114.8
133.7
152.6
11.22
10.77
11.78
11.45
11.00
171.7
154.1
203.0
184.8
166.7
103.4
127.3
96.5
120.2
144.0
12.24
11.81
12.81
12.50
12.03
157.0
140.0
187.6
170.1
152.5
88.7
117.5
78.2
106.8
135.3
13.35
12.86
13.91
13.57
13.05
142.3
125.8
172.2
155.3
138.3
74.1
107.7
59.9
93.3
126.7
14.41
13.88
14.90
14.55
14.10
127.6
111.7
156.8
140.5
124.1
59.4
97.8
41.6
79.9
118.1
15.38
14.88
15.88
15.65
15.10
15 TONS
7500/0.05
72
229.6
127.6
12.06
214.1
110.2
13.05
198.6
92.9
14.15
183.1
75.5
15.15
167.6
58.1
16.12
67
210.4
146.2
11.64
195.5
133.7
12.66
180.6
121.3
13.75
165.7
108.8
14.73
150.9
96.3
15.84
62
191.2
164.9
11.35
176.9
157.3
12.47
162.7
149.7
13.47
148.4
142.0
14.53
134.2
134.2
15.54
RAS180 Cooling Capacities, Hot Gas Reheat Mode
AIR ENTERING EVAPORATOR - Ewb (F)
75 Dry Bulb
62.5 Wet Bulb
(50% Relative)
TEMP (F) AIR ENT
CONDENSER Edb)
80
75
70
60
50
40
LEGEND
Edb Ewb kW Idb Iwb SHC TC -
TC
SHC
kW
TC
SHC
kW
TC
SHC
kW
TC
SHC
kW
TC
SHC
kW
TC
SHC
kW
4500
83.75
37.50
10.50
85.00
40.00
10.16
86.15
42.10
9.84
88.90
46.80
9.37
91.70
51.50
9.12
94.45
56.30
9.05
6000
84.85
42.80
11.49
86.00
45.00
11.15
87.35
47.50
10.83
90.10
52.30
10.36
92.80
57.10
10.09
95.60
61.40
10.02
7500
88.95
55.10
11.60
90.50
57.30
11.25
91.50
59.80
10.94
94.25
64.60
10.44
97.00
69.40
10.16
99.80
73.70
10.10
75 Dry Bulb
64 Wet Bulb
(56% Relative)
Air Entering Evaporator - Cfm
4500
6000
7500
86.65
91.90
92.90
30.90
40.40
44.50
10.56
10.65
11.70
88.05
93.60
94.65
33.20
42.30
46.90
10.21
10.31
11.33
89.20
94.30
96.10
35.50
45.30
49.50
10.02
10.13
11.03
92.00
97.10
98.20
40.20
50.10
54.10
9.42
9.52
10.55
94.80
99.90
101.00
44.80
54.80
58.90
9.17
9.28
10.26
97.45
102.55
103.70
49.70
59.20
63.30
9.10
9.21
10.18
75 Dry Bulb
65.3 Wet Bulb
(60% Relative)
4500
87.90
24.80
11.60
89.20
26.90
11.26
90.40
29.50
10.95
93.20
34.10
10.45
96.10
38.70
10.17
98.65
43.60
10.11
6000
91.75
29.30
11.72
93.45
31.50
11.35
94.10
33.90
11.05
96.90
38.60
10.57
99.70
43.20
10.26
102.35
48.10
10.20
7500
96.30
34.10
11.77
97.85
36.30
11.42
98.95
38.70
11.12
101.75
43.40
10.64
104.20
49.00
10.32
107.00
52.90
10.26
Entering Dry-Bulb
Entering Wet-Bulb
Compressor Motor Power Input
Leaving Dry-Bulb
Leaving Wet-Bulb
Sensible Heat Capacity (1000 Btuh) Gross
Total Capacity (1000 Btuh) Gross
513 31 3209 02
52
Table 8 – STATIC PRESSURE ADDERS (IN. WG) (FACTORY OPTIONS AND/OR ACCESSORIES)
ELECTRIC HEATERS
CFM
1 Electric Heater Module
2 Electric Heater Modules
600
0.03
0.13
900
0.05
0.15
3-6 TONS
1400
0.09
0.16
1200
0.07
0.16
1600
0.09
0.16
1800
0.10
0.17
2000
0.11
0.17
2200
0.11
0.17
2400
0.12
0.18
2600
0.13
0.18
7.5 - 12.5 TONS
CFM
2250
2500
2750
3000
3250
3500
3750
4000
4250
4500
4750
5000
5250
5500
5750
6000
1 Electric
Heater Module
0.03
0.04
0.04
0.05
0.06
0.07
0.08
0.09
0.10
0.11
0.12
0.13
0.14
0.15
0.16
0.18
2 Electric
Heater Modules
0.04
0.05
0.05
0.06
0.07
0.08
0.09
0.10
0.11
0.12
0.13
0.15
0.16
0.17
0.19
0.20
CFM
Vertical ­ 1 Electric Heater
Module
Vertical ­ 2 Electric Heater
Modules
Horizontal ­ 1 Electric
Heater Module
Horizontal ­ 2 Electric
Heater Modules
2813
3125
3438
3750
15 TON
4063
4375
4688
5000
5313
5625
5938
6250
0.01
0.01
0.02
0.02
0.02
0.02
0.02
0.03
0.03
0.03
0.03
0.04
0.02
0.03
0.03
0.03
0.04
0.04
0.05
0.05
0.06
0.06
0.07
0.08
0.03
0.03
0.04
0.04
0.05
0.05
0.06
0.06
0.07
0.07
0.08
0.09
0.02
0.03
0.03
0.04
0.04
0.04
0.05
0.05
0.06
0.06
0.07
0.08
HOT GAS REHEAT
CFM
3 Tons
4 Tons
5 Tons
6 Tons
1000
0.04
-
CFM
7.5 Tons
8.5 Tons
10 Tons
12.5 Tons
2250
0.12
-
CFM
15 Tons
4000
0.06
53
1250
0.052
0.106
-
2500
0.14
0.11
-
4250
0.07
2750
0.16
0.12
-
4500
0.07
3-6 TONS
1750
2000
0.172
0.21
0.172
0.21
0.112
0.125
1500
0.07
0.138
0.138
-
3000
0.19
0.13
0.13
-
3250
0.21
0.15
0.15
-
4750
0.08
3500
0.23
0.17
0.17
0.17
5000
0.08
7.5-12.5 TONS
3750
4000
0.26
0.18
0.20
0.18
0.20
0.18
0.20
15 TONS
5250
5500
0.09
0.10
4250
0.22
0.22
0.22
5750
0.10
2250
0.252
0.161
4500
0.24
0.24
6000
0.11
2500
0.30
0.19
4750
0.26
0.26
6250
0.12
5000
0.28
0.28
2750
0.22
5250
0.31
6500
0.12
5500
0.33
6750
0.13
3000
0.25
5750
0.36
7000
0.14
513 31 3209 02
6000
0.39
7250
0.15
ECONOMIZER, BAROMETRIC RELIEF AND PE PERFORMANCE
Vertical Application
VERTICAL ECONOMIZER
2500
2500
RELIEF FLOW (CFM)
RETURN AIRFLOW (CFM)
3000
2000
1500
1000
500
0
Vertical Economizers
2000
1500
3 -6 Ton
7½ - 12½ Ton
1000
500
0
0.0
0.1
0
0.2
0.05
0.1
0.15
0.2
0.25
0.3
RETURN DUCT STATIC PRESSURE (in. wg)
RETURN DUCT STATIC PRESSURE DROP (in. wg)
3-6 TON
C11238
C08073
Fig. 1 − Return Air Pressure Drop
Fig. 4 − Barometric Relief Flow Capacity
2500
5000
2000
RELIEF FLOW (CFM)
RETURN AIRFLOW (CFM)
VERTICAL ECONOMIZER
6000
4000
3000
2000
1000
0
Vertical Economizers
1500
15 -Ton
1000
500
0
0.0
0.1
0.2
0.3
0.4
0
0.5
0.05
0.1
0.15
0.2
0.25
0.3
RETURN DUCT STATIC PRESSURE (in. wg)
RETURN DUCT STATIC PRESSURE DROP (in. wg)
7.5 - 12.5 TON
C11240
C101122
Fig. 2 − Return Air Pressure Drop
Fig. 5 − Barometric Relief Flow−Vertical 15 Ton
Vertical Power Exhaust
6,800
6,300
5,800
5,300
4,800
4,300
3,800
0.01
4000
3 - 6 Ton
3000
7.5 - 15 Ton
2000
1000
0
0
3,300
2,800
5000
(cfm)
EXHAUST AIRFLOW
RETURN AIRLOW (CEM)
VERTICAL ECONOMIZER STATIC PRESSURE ADDER
7,300
0.02
0.03
0.04
0.05
0.06
0.07
0.1
0.2
0.3
0.4
0.5
RETURN DUCT STATIC PRESSURE (in. wg)
0.08
RETURN DUCT STATIC PRESSURE DROP (in. wg)
C11257
Fig. 3 − Return Air Pressure Drop−Vertical 15 Tons
513 31 3209 02
C11248
Fig. 6 − Vertical Power Exhaust Performance
54
ECONOMIZER, BAROMETRIC RELIEF AND PE PERFORMANCE (cont.)
Horizontal Application
HORIZONTAL ECONOMIZER
3000
2500
RELIEF FLOW (CFM)
RETURN AIRFLOW (CFM)
2500
2000
1500
1000
500
0
Horizontal Economizers
2000
1500
3 -6 Ton
7½ - 12½ Ton
1000
500
0
0.0
0.1
0
0.2
0.05
0.1
0.15
0.2
0.25
0.3
RETURN DUCT STATIC PRESSURE (in. wg)
RETURN DUCT STATIC PRESSURE DROP (in. wg)
3 - 6 TON
C11239
C08070
Fig. 7 − Return Air Pressure Drop
Fig. 10 − Barometric Relief Flow Capacity
2500
5000
2000
RELIEF FLOW (CFM)
RETURN AIRFLOW (CFM)
HORIZONTAL ECONOMIZER
6000
4000
3000
2000
1000
0
0.0
0.1
0.2
0.3
0.4
0.5
Horizontal Economizers
1500
15 -Ton
1000
500
0
0.6
0
0.05
0.1
0.15
0.2
0.25
0.3
RETURN DUCT STATIC PRESSURE (in. wg)
RETURN DUCT STATIC PRESSURE DROP (in. wg)
7.5 - 12.5 TON
C11241
Fig. 8 − Return Air Pressure Drop
C101120
Fig. 11 − Barometric Relief Flow−Horizontal 15 Ton
7,300
6,800
EXHAUST AIRFLOW
(cfm)
RETURN AIRLOW (CFM)
HORIZONTAL ECONOMIZER STATIC PRESSURE ADDER
6,300
5,800
5,300
4,800
4,300
3,800
0.05
2000
1500
1000
500
0
0
3,300
2,800
Horizontal Power Exhaust
2500
0.1
0.2
0.3
0.4
0.5
RETURN DUCT STATIC PRESSURE (in. wg)
0.15
0.25
0.35
0.45
3 - 15 TON
RETURN DUCT STATIC PRESSURE DROP (in. wg)
C11258
Fig. 9 − Return Air Pressure Drop−Horizontal 15 Ton
55
C08012
Fig. 12 − Horizontal Power Exhaust Performance
513 31 3209 02
GENERAL FAN PERFORMANCE NOTES
1. Interpolation is permissible. Do not extrapolate.
2. External static pressure is the static pressure difference between the return duct and the supply duct plus the static
pressure caused by any FIOPs or accessories.
3. Tabular data accounts for pressure loss due to clean filters, unit casing, and wet coils. Factory options and accessories may add static pressure losses. Selection software is available, through your salesperson, to help you
select the best motor/drive combination for your application.
4. The Fan Performance tables offer motor/drive recommendations. In cases when two motor/drive combinations
would work, we recommended the lower horsepower option.
5. For information on the electrical properties of the motors, please see the Electrical information section of this book.
6. For more information on the performance limits of motors, see the application data section of this book.
7. The EPACT (Energy Policy Act of 1992) regulates energy requirements for specific types of indoor fan motors.
Motors regulated by EPACT include any general purpose, T−frame (three−digit, 143 and larger), single−speed, foot
mounted, polyphase, squirrel cage induction motors of NEMA (National Electrical Manufacturers Association) design
A and B, manufactured for use in the United States. Ranging from 1 to 200 Hp, these continuous−duty motors
operate on 230 and 460 volt, 60 Hz power. If a motor does not fit into these specifications, the motor does not have
to be replaced by an EPACT compliant energy−efficient motor. Variable−speed motors are exempt from EPACT
compliance requirements. Therefore, the indoor fan motors for RAS036−180 units are exempt from these requirements.
513 31 3209 02
56
FAN PERFORMANCE
Table 9 – RAS036, 1 PHASE, 3 TON HORIZONTAL SUPPLY
CFM
900
975
1050
1125
1200
1275
1350
1425
1500
CFM
900
975
1050
1125
1200
1275
1350
1425
1500
0.2
RPM
BHP
Field Supplied Drive1
554
0.14
575
0.16
597
0.18
620
0.21
643
0.23
666
0.27
690
0.30
714
0.34
738
0.38
1.2
RPM
BHP
1017
1035
1053
1071
1089
1107
1126
1145
1164
0.64
0.68
0.73
0.78
0.84
0.90
0.96
1.03
1.10
RPM
681
701
721
741
762
784
805
827
849
AVAILABLE EXTERNAL STATIC PRESSURE (IN. WG)
0.4
0.6
0.8
1.0
BHP
RPM
BHP
RPM
BHP
RPM
Standard Static Option
Medium Static Option
0.22
783
0.32
870
0.42
947
0.25
801
0.35
888
0.45
965
0.28
821
0.38
906
0.49
983
0.31
840
0.42
925
0.54
1001
0.35
860
0.46
944
0.58
1020
0.38
880
0.50
964
0.63
1039
0.42
900
0.55
983
0.68
1058
0.47
921
0.60
1003
0.74
1077
0.52
942
0.66
1024
0.80
1097
AVAILABLE EXTERNAL STATIC PRESSURE (IN. WG)
1.4
1.6
1.8
2.0
RPM
BHP
RPM
BHP
RPM
BHP
RPM
Medium Static Option
Field Supplied Drive2
1082
0.76
1143
0.88
1200
1.01
1254
1100
0.81
1160
0.93
1217
1.07
1271
1117
0.86
1177
0.99
1234
1.13
1135
0.92
1195
1.05
1251
1.19
1153
0.98
1212
1.12
1171
1.04
1230
1.19
1189
1.11
1208
1.18
-
BHP
0.53
0.57
0.61
0.66
0.71
0.76
0.82
0.88
0.95
BHP
1.14
1.20
-
NOTE: For more information, see General Fan Performance Notes.
Boldface indicates field−supplied drive is required.
1. Recommend using field-supplied fan pulley (part no. 1178488) and belt (part no. 1177401).
2. Recommend using field-supplied motor pulley (part no. 1175832), and belt (part no. 1178128).
Table 10 – RAS036, 1 PHASE, 3 TON VERTICAL SUPPLY
CFM
900
975
1050
1125
1200
1275
1350
1425
1500
CFM
900
975
1050
1125
1200
1275
1350
1425
1500
0.2
RPM
BHP
Field Supplied Drive1
566
0.14
590
0.17
615
0.19
640
0.22
666
0.25
692
0.29
719
0.33
746
0.37
774
0.42
1.2
RPM
BHP
1029
1046
1064
1082
1100
1119
1139
1159
1179
0.63
0.68
0.73
0.79
0.85
0.91
0.98
1.05
1.13
RPM
690
711
733
755
778
802
825
850
875
AVAILABLE EXTERNAL STATIC PRESSURE (IN. WG)
0.4
0.6
0.8
1.0
BHP
RPM
BHP
RPM
BHP
RPM
Standard Static Option
Medium Static Option
0.23
791
0.32
879
0.42
957
0.26
811
0.36
897
0.46
975
0.29
831
0.39
916
0.50
993
0.33
851
0.43
936
0.55
1012
0.36
873
0.48
956
0.60
1031
0.41
894
0.53
976
0.65
1051
0.45
916
0.58
997
0.71
1071
0.50
939
0.63
1019
0.77
1091
0.55
962
0.69
1041
0.83
1112
AVAILABLE EXTERNAL STATIC PRESSURE (IN. WG)
1.4
1.6
1.8
2.0
RPM
BHP
RPM
BHP
RPM
BHP
RPM
Medium Static Option
Field Supplied Drive2
1095
0.75
1157
0.86
1216
0.99
1272
1112
0.80
1174
0.92
1232
1.05
1287
1129
0.86
1190
0.98
1248
1.11
1147
0.92
1208
1.05
1265
1.18
1165
0.98
1225
1.12
1183
1.05
1243
1.19
1202
1.12
1221
1.20
-
BHP
0.52
0.57
0.62
0.67
0.72
0.78
0.84
0.91
0.98
BHP
1.11
1.18
-
NOTE: For more information, see General Fan Performance Notes.
Boldface indicates field−supplied drive is required.
1. Recommend using field-supplied fan pulley (part no. 1178488) and belt (part no. 1177401).
2. Recommend using field-supplied motor pulley (part no. 1175832) and belt (part no. 1178128).
57
513 31 3209 02
FAN PERFORMANCE (cont.)
Table 11 – RAS036, 3 PHASE, 3 TON HORIZONTAL SUPPLY
CFM
900
975
1050
1125
1200
1275
1350
1425
1500
CFM
900
975
1050
1125
1200
1275
1350
1425
1500
0.2
RPM
BHP
Field Supplied Drive1
554
0.14
575
0.16
597
0.18
620
0.21
643
0.23
666
0.27
690
0.30
714
0.34
738
0.38
1.2
RPM
BHP
1017
1035
1053
1071
1089
1107
1126
1145
1164
0.64
0.68
0.73
0.78
0.84
0.90
0.96
1.03
1.10
RPM
681
701
721
741
762
784
805
827
849
AVAILABLE EXTERNAL STATIC PRESSURE (IN. WG)
0.4
0.6
0.8
1.0
BHP
RPM
BHP
RPM
BHP
RPM
Standard Static Option
Medium Static Option
0.22
783
0.32
870
0.42
947
0.25
801
0.35
888
0.45
965
0.28
821
0.38
906
0.49
983
0.31
840
0.42
925
0.54
1001
0.35
860
0.46
944
0.58
1020
0.38
880
0.50
964
0.63
1039
0.42
900
0.55
983
0.68
1058
0.47
921
0.60
1003
0.74
1077
0.52
942
0.66
1024
0.80
1097
AVAILABLE EXTERNAL STATIC PRESSURE (IN. WG)
1.4
1.6
1.8
2.0
RPM
BHP
RPM
BHP
RPM
BHP
RPM
Medium Static Option
High Static Option
1082
0.76
1143
0.88
1200
1.01
1254
1100
0.81
1160
0.93
1217
1.07
1271
1117
0.86
1177
0.99
1234
1.13
1288
1135
0.92
1195
1.05
1251
1.19
1305
1153
0.98
1212
1.12
1269
1.26
1322
1171
1.04
1230
1.19
1286
1.33
1340
1189
1.11
1249
1.26
1304
1.41
1357
1208
1.18
1267
1.33
1323
1.49
1375
1227
1.25
1285
1.41
1341
1.58
1394
BHP
0.53
0.57
0.61
0.66
0.71
0.76
0.82
0.88
0.95
BHP
1.14
1.20
1.27
1.34
1.41
1.49
1.57
1.66
1.75
NOTE: For more information, see General Fan Performance Notes.
Boldface indicates field−supplied drive is required.
1. Recommend using field-supplied fan pulley (part no. 1178448) and belt (part no. 1177401).
Table 12 – RAS036, 3 PHASE, 3 TON VERTICAL SUPPLY
CFM
900
975
1050
1125
1200
1275
1350
1425
1500
CFM
900
975
1050
1125
1200
1275
1350
1425
1500
0.2
RPM
BHP
Field Supplied Drive1
566
0.14
590
0.17
615
0.19
640
0.22
666
0.25
692
0.29
719
0.33
746
0.37
774
0.42
1.2
RPM
BHP
1029
1046
1064
1082
1100
1119
1139
1159
1179
0.63
0.68
0.73
0.79
0.85
0.91
0.98
1.05
1.13
RPM
690
711
733
755
778
802
825
850
875
AVAILABLE EXTERNAL STATIC PRESSURE (IN. WG)
0.4
0.6
0.8
1.0
BHP
RPM
BHP
RPM
BHP
RPM
Standard Static Option
Medium Static Option
0.23
791
0.32
879
0.42
957
0.26
811
0.36
897
0.46
975
0.29
831
0.39
916
0.50
993
0.33
851
0.43
936
0.55
1012
0.36
873
0.48
956
0.60
1031
0.41
894
0.53
976
0.65
1051
0.45
916
0.58
997
0.71
1071
0.50
939
0.63
1019
0.77
1091
0.55
962
0.69
1041
0.83
1112
AVAILABLE EXTERNAL STATIC PRESSURE (IN. WG)
1.4
1.6
1.8
RPM
BHP
RPM
BHP
RPM
Medium Static Option
1095
0.75
1157
0.86
1216
1112
0.80
1174
0.92
1232
1129
0.86
1190
0.98
1248
1147
0.92
1208
1.05
1265
1165
0.98
1225
1.12
1282
1183
1.05
1243
1.19
1300
1202
1.12
1262
1.27
1318
1221
1.20
1280
1.35
1336
1241
1.28
1300
1.44
1355
BHP
0.52
0.57
0.62
0.67
0.72
0.78
0.84
0.91
0.98
2.0
BHP
RPM
High Static Option
0.99
1272
1.05
1287
1.11
1304
1.18
1320
1.26
1337
1.34
1354
1.42
1372
1.51
1390
1.60
1408
BHP
1.11
1.18
1.25
1.32
1.40
1.49
1.57
1.66
1.76
NOTE: For more information, see General Fan Performance Notes.
Boldface indicates field−supplied drive is required.
1. Recommend using field-supplied fan pulley (part no. 1178448) and belt (part no. 1177401).
513 31 3209 02
58
FAN PERFORMANCE (cont.)
Table 13 – RAS048, 1 PHASE, 4 TON HORIZONTAL SUPPLY
CFM
1200
1300
1400
1500
1600
1700
1800
1900
2000
CFM
1200
1300
1400
1500
1600
1700
1800
AVAILABLE EXTERNAL STATIC PRESSURE (IN. WG)
0.4
0.6
0.8
BHP
RPM
BHP
RPM
BHP
RPM
BHP
Standard Static Option
Medium Static Option
0.23
762
0.35
860
0.46
944
0.58
0.28
791
0.40
887
0.52
970
0.65
0.33
820
0.45
914
0.59
997
0.72
0.38
849
0.52
942
0.66
1024
0.80
0.44
0.59
971
0.74
1051
0.89
879
0.51
910
0.66
1000
0.82
1079
0.98
0.59
941
0.75
1029
0.91
1107
1.08
0.67
972
0.84
1059
1.02
1136
1.19
0.76
1004
0.94
1089
1.12
-
0.2
RPM
643
674
706
738
771
804
837
871
906
AVAILABLE EXTERNAL STATIC PRESSURE (IN. WG)
1.4
1.6
1.8
BHP
RPM
BHP
RPM
BHP
RPM
BHP
Medium Static Option
Field Supplied Drive1
0.84
1153
0.98
1212
1.12
0.92
1177
1.06
1.01
1202
1.15
1.10
1.20
-
1.0
RPM
BHP
1020
1045
1071
1097
1124
1151
-
0.71
0.78
0.86
0.95
1.04
1.14
-
1.2
RPM
1089
1114
1139
1164
1190
-
2.0
RPM
BHP
-
-
NOTE: For more information, see General Fan Performance Notes.
Boldface indicates field−supplied drive is required.
1. Recommend using field-supplied motor pulley (part no. 1175832) and belt (part no. 1178128).
Table 14 – RAS048, 1 PHASE, 4 TON VERTICAL SUPPLY
CFM
1200
1300
1400
1500
1600
1700
1800
1900
2000
CFM
1200
1300
1400
1500
1600
1700
1800
1900
2000
AVAILABLE EXTERNAL STATIC PRESSURE (IN. WG)
0.4
0.6
0.8
BHP
RPM
BHP
RPM
BHP
RPM
BHP
Standard Static Option
Medium Static Option
0.25
778
0.36
873
0.48
956
0.60
0.30
809
0.42
902
0.54
983
0.67
0.36
842
0.48
932
0.61
1012
0.75
0.42
875
0.55
962
0.69
1041
0.83
0.49
909
0.63
994
0.78
1071
0.93
0.57
943
0.72
1026
0.87
1101
1.03
0.65
978
0.81
1059
0.98
1133
1.14
0.75
1014
0.92
1092
1.09
0.86
1050
1.03
-
0.2
RPM
666
701
737
774
811
849
887
926
965
AVAILABLE EXTERNAL STATIC PRESSURE (IN. WG)
1.4
1.6
1.8
BHP
RPM
BHP
RPM
BHP
RPM
BHP
Medium Static Option
Field Supplied Drive1
0.85
1165
0.98
1225
1.12
0.94
1189
1.07
1.03
1215
1.17
1.13
1.24
1.36
1.48
1.62
1.77
-
1.0
RPM
BHP
1031
1057
1085
1112
1141
1170
-
0.72
0.80
0.89
0.98
1.08
1.19
-
1.2
RPM
1100
1126
1152
1179
1206
1235
1264
1293
1324
2.0
RPM
BHP
-
-
NOTE: For more information, see General Fan Performance Notes.
Boldface indicates field−supplied drive is required.
59
513 31 3209 02
FAN PERFORMANCE (cont.)
Table 15 – RAS048, 3 PHASE, 4 TON HORIZONTAL SUPPLY
CFM
1200
1300
1400
1500
1600
1700
1800
1900
2000
CFM
1200
1300
1400
1500
1600
1700
1800
1900
2000
AVAILABLE EXTERNAL STATIC PRESSURE (IN. WG)
0.4
0.6
0.8
BHP
RPM
BHP
RPM
BHP
RPM
BHP
Standard Static Option
Medium Static Option
0.23
762
0.35
860
0.46
944
0.58
0.28
791
0.40
887
0.52
970
0.65
0.33
820
0.45
914
0.59
997
0.72
0.38
849
0.52
942
0.66
1024
0.80
0.44
879
0.59
971
0.74
1051
0.89
0.51
910
0.66
1000
0.82
1079
0.98
0.59
941
0.75
1029
0.91
1107
1.08
0.67
972
0.84
1059
1.02
1136
1.19
0.76
1004
0.94
1089
1.12
1165
1.31
0.2
RPM
643
674
706
738
771
804
837
871
906
AVAILABLE EXTERNAL STATIC PRESSURE (IN. WG)
1.4
1.6
1.8
BHP
RPM
BHP
RPM
BHP
RPM
BHP
Medium Static Option
High Static Option
0.84
1153
0.98
1212
1.12
1269
1.26
0.92
1177
1.06
1236
1.21
1292
1.36
1.01
1202
1.15
1261
1.31
1316
1.47
1.10
1227
1.25
1285
1.41
1341
1.58
1.20
1252
1.36
1311
1.53
1366
1.70
1.31
1278
1.48
1336
1.65
1391
1.83
1.42
1305
1.60
1362
1.78
1416
1.97
1.55
1331
1.73
1388
1.92
1442
2.11
1.68
1358
1.87
1415
2.07
1468
2.27
1.0
RPM
BHP
1020
1045
1071
1097
1124
1151
1178
1206
1234
0.71
0.78
0.86
0.95
1.04
1.14
1.25
1.37
1.49
1.2
RPM
1089
1114
1139
1164
1190
1217
1244
1271
1298
2.0
RPM
BHP
1322
1346
1369
1394
1418
1443
1468
1494
-
1.41
1.52
1.63
1.75
1.87
2.01
2.15
2.31
-
NOTE: For more information, see General Fan Performance Notes.
Boldface indicates field−supplied drive is required.
1. Recommend using field-supplied fan pulley (part no. 1175314), motor pulley (part no. 1170551) and belt (part no. 1178451).
Table 16 – RAS048, 3 PHASE, 4 TON VERTICAL SUPPLY
CFM
1200
1300
1400
1500
1600
1700
1800
1900
2000
CFM
1200
1300
1400
1500
1600
1700
1800
1900
2000
AVAILABLE EXTERNAL STATIC PRESSURE (IN. WG)
0.4
0.6
0.8
BHP
RPM
BHP
RPM
BHP
RPM
BHP
Standard Static Option
Medium Static Option
0.25
778
0.36
873
0.48
956
0.60
0.30
809
0.42
902
0.54
983
0.67
0.36
842
0.48
932
0.61
1012
0.75
0.42
875
0.55
962
0.69
1041
0.83
0.49
909
0.63
994
0.78
1071
0.93
0.57
943
0.72
1026
0.87
1101
1.03
0.65
978
0.81
1059
0.98
1133
1.14
0.75
1014
0.92
1092
1.09
1164
1.26
0.86
1050
1.03
1127
1.21
1197
1.39
0.2
RPM
666
701
737
774
811
849
887
926
965
1.2
RPM
BHP
Medium Static Option
1100
0.85
1126
0.94
1152
1.03
1179
1.13
1206
1.24
1235
1.36
1264
1.48
1293
1.62
1324
1.77
RPM
1165
1189
1215
1241
1268
1295
1323
1352
1381
AVAILABLE EXTERNAL STATIC PRESSURE (IN. WG)
1.4
1.6
1.8
BHP
RPM
BHP
RPM
BHP
High Static Option
0.98
1225
1.12
1282
1.26
1.07
1249
1.22
1306
1.36
1.17
1274
1.32
1330
1.48
1.28
1300
1.44
1355
1.60
1.40
1326
1.56
1381
1.73
1.52
1352
1.69
1407
1.87
1.66
1380
1.84
1434
2.02
1.80
1408
1.99
1461
2.17
1.96
1436
2.15
1489
2.34
1.0
RPM
BHP
1031
1057
1085
1112
1141
1170
1200
1231
1262
0.72
0.80
0.89
0.98
1.08
1.19
1.31
1.44
1.58
2.0
RPM
BHP
1337
1360
1384
1408
1433
1459
1485
1512
-
1.40
1.51
1.63
1.76
1.90
2.04
2.20
2.37
-
NOTE: For more information, see General Fan Performance Notes.
Boldface indicates field−supplied drive is required.
1. Recommend using field-supplied fan pulley (part no. 1175314), motor pulley (part no. 1170551) and belt (part no. 1178451).
513 31 3209 02
60
FAN PERFORMANCE (cont.)
Table 17 – RAS060, 1 PHASE, 5 TON HORIZONTAL SUPPLY
CFM
1500
1625
1750
0.2
RPM
BHP
Field Supplied Drive1
724
0.33
765
0.40
AVAILABLE EXTERNAL STATIC PRESSURE (IN. WG)
0.4
0.6
0.8
RPM
BHP
RPM
BHP
RPM
BHP
Standard Static Option
837
0.45
937
0.59
1028
0.74
873
0.53
969
0.67
1056
0.83
1.0
RPM
BHP
1111
1137
0.91
1.00
806
0.48
909
0.61
1002
0.76
1087
0.92
1165
1.10
849
892
935
0.57
0.67
0.79
947
986
1025
0.71
0.82
0.94
1036
1072
1108
0.86
0.98
1.11
1118
1151
1.03
1.15
1195
1226
1.21
1.33
1185
1.29
1258
1.47
2250
980
0.92
1066
1.08
1146
1.25
1220
1.43
-
-
2375
1024
1.06
1107
1.23
1184
1.41
-
-
-
-
2500
1069
1.22
1149
1.39
-
-
-
-
-
-
1875
2000
2125
CFM
1.2
AVAILABLE EXTERNAL STATIC PRESSURE (IN. WG)
1.4
1.6
1.8
RPM
BHP
RPM
BHP
RPM
BHP
Medium Static Option
1261
1.29
1330
1.49
-
2.0
RPM
BHP
RPM
BHP
1500
1188
1.09
1625
1213
1.18
1284
1.38
-
-
-
-
-
-
-
1750
1239
1.28
1309
1.49
-
-
-
-
-
-
1875
1267
1.40
-
-
-
-
-
-
-
-
2000
2125
-
-
-
-
-
-
-
-
-
-
2250
-
-
-
-
-
-
-
-
-
-
NOTE: For more information, see General Fan Performance Notes.
1. Recommend using field-supplied fan pulley (part no. 1178034) and belt (part no. 1178127).
Table 18 – RAS060, 1 PHASE, 5 TON VERTICAL SUPPLY
RPM
BHP
1500
790
0.40
AVAILABLE EXTERNAL STATIC PRESSURE (IN. WG)
0.4
0.6
0.8
RPM
BHP
RPM
BHP
RPM
BHP
Standard Static Option
897
0.53
991
0.68
1075
0.83
1625
1750
1875
837
885
934
0.48
0.58
0.69
940
983
1027
0.62
0.73
0.85
1030
1070
1112
0.77
0.89
1.01
1112
1150
0.94
1.06
1189
2000
983
0.81
1073
0.98
1154
1.16
1229
2125
1033
0.95
1119
1.13
1198
1.31
2250
1084
1.11
1166
1.29
1242
1.49
2375
1134
1.28
1214
1.48
-
2500
1185
1.48
-
-
-
CFM
CFM
0.2
1.0
RPM
BHP
1152
1.00
1187
1223
1.11
1.24
1.19
1260
1.38
1.34
-
-
1270
1.50
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
AVAILABLE EXTERNAL STATIC PRESSURE (IN. WG)
1.4
1.6
1.8
BHP
RPM
BHP
RPM
BHP
RPM
BHP
Medium Static Option
1.18
1291
1.36
1.30
1323
1.49
-
1.2
RPM
2.0
RPM
BHP
-
-
1500
1625
1224
1257
1750
1292
1.43
-
-
-
-
-
-
-
-
1875
-
-
-
-
-
-
-
-
-
-
2000
2125
2250
2375
2500
-
-
-
-
-
-
-
-
-
-
NOTE: For more information, see General Fan Performance Notes.
Boldface indicates field−supplied drive is required.
61
513 31 3209 02
FAN PERFORMANCE (cont.)
Table 19 – RAS060, 3 PHASE, 5 TON HORIZONTAL SUPPLY
CFM
1800
1950
2100
2250
2400
2550
2700
2850
3000
CFM
1800
1950
2100
2250
2400
2550
2700
2850
3000
0.2
RPM
BHP
822
872
923
974
1026
1079
1132
1186
1240
0.51
0.62
0.75
0.90
1.06
1.25
1.46
1.69
1.94
AVAILABLE EXTERNAL STATIC PRESSURE (IN. WG)
0.4
0.6
0.8
1.0
RPM
BHP
RPM
BHP
RPM
BHP
RPM
Field Supplied Drive1
Standard Static Option
927
0.66
1018
0.82
1100
0.98
1174
973
0.79
1061
0.95
1140
1.13
1213
1019
0.92
1.10
1182
1.29
1253
1104
1067
1.08
1149
1.27
1224
1.46
1294
1115
1.26
1195
1.46
1268
1.66
1336
1164
1.46
1241
1.67
1312
1.88
1379
1214
1.67
1289
1.90
1358
2.12
1422
1264
1.92
1336
2.15
1404
2.39
1467
1315
2.18
1385
2.43
1451
2.68
1512
1.2
RPM
BHP
RPM
1244
1281
1320
1359
1400
1441
1483
1527
1571
1.33
1.49
1.67
1.87
2.09
2.33
2.59
2.87
3.18
1308
1345
1382
1420
1460
1500
1541
1583
1626
AVAILABLE EXTERNAL STATIC PRESSURE (IN. WG)
1.4
1.6
1.8
BHP
RPM
BHP
RPM
BHP
Standard Static Option
1.51
1369
1.70
1427
1.90
1.68
1405
1.88
1462
2.09
1.87
1441
2.08
1498
2.29
2.08
1479
2.29
1534
2.51
2.31
1517
2.53
1572
2.76
2.55
1557
2.79
1610
3.03
2.83
1597
3.07
1650
3.32
3.12
1638
3.37
1690
3.63
3.44
1680
3.70
-
BHP
1.15
1.31
1.48
1.66
1.87
2.10
2.35
2.63
2.93
2.0
RPM
BHP
Medium Static Option
1483
2.10
1517
2.30
1552
2.51
1587
2.74
1624
2.99
1662
3.27
1701
3.57
-
NOTE: For more information, see General Fan Performance Notes.
- High Static Option
Boldface indicates field-supplied drive is required.
1. Recommend using field-supplied fan pulley (part no. 1178034) and belt (part no. 1178127).
Table 20 – RAS060, 3 PHASE, 5 TON VERTICAL SUPPLY
CFM
0.2
RPM
BHP
RPM
1500
1625
1750
1875
2000
2125
790
837
885
934
983
1033
0.40
0.48
0.58
0.69
0.81
0.95
897
940
983
1027
1073
1119
2250
2375
2500
1084
1134
1185
1.11
1.28
1.48
1166
1214
1262
CFM
1.2
RPM
BHP
RPM
1500
1625
1750
1875
1224
1257
1292
1327
1.18
1.30
1.43
1.57
1291
1323
1356
1391
2000
2125
2250
2375
2500
1364
1402
1441
1481
1522
1.74
1.92
2.11
2.33
2.56
1427
1463
1501
1539
1579
AVAILABLE EXTERNAL STATIC PRESSURE (IN. WG)
0.4
0.6
0.8
BHP
RPM
BHP
RPM
BHP
Standard Static Option
0.53
991
0.68
1075
0.83
0.62
1030
0.77
1112
0.94
0.73
1070
0.89
1150
1.06
0.85
1112
1.01
1189
1.19
0.98
1154
1.16
1229
1.34
1.13
1198
1.31
1270
1.50
1.29
1.48
1.68
1242
1287
1333
1.49
1.68
1.89
1312
1355
1399
1.69
1.89
2.10
AVAILABLE EXTERNAL STATIC PRESSURE (IN. WG)
1.4
1.6
1.8
BHP
RPM
BHP
RPM
BHP
Medium Static Option
1.36
1354
1.56
1414
1.77
1.49
1385
1.69
1445
1.90
1.63
1418
1.83
1476
2.05
1.78
1451
1.99
1509
2.21
1.95
2.13
2.34
2.56
2.80
1486
1521
1558
1595
-
2.17
2.36
2.57
2.80
-
1542
1577
1612
-
2.39
2.59
2.81
-
1.0
RPM
BHP
1152
1187
1223
1260
1299
1338
1.00
1.11
1.24
1.38
1.53
1.71
1386
1420
1462
1.89
2.10
2.33
2.0
RPM
BHP
High Static Option
1472
1.98
1501
2.12
1532
2.27
1564
2.44
1596
1630
-
2.63
2.83
-
NOTE: For more information, see General Fan Performance Notes.
Boldface indicates field-supplied drive is required.
513 31 3209 02
62
FAN PERFORMANCE (cont.)
Table 21 – RAS072, 3 PHASE, 6 TON HORIZONTAL SUPPLY
CFM
1800
1950
2100
2250
2400
2550
2700
2850
3000
0.2
RPM
BHP
822
872
923
974
1026
1079
1132
1186
1240
0.51
0.62
0.75
0.90
1.06
1.25
1.46
1.69
1.94
AVAILABLE EXTERNAL STATIC PRESSURE (IN. WG)
0.4
0.6
0.8
1.0
RPM
BHP
RPM
BHP
RPM
BHP
RPM
Field Supplied Drive1
Standard Static Option
927
0.66
1018
0.82
1100
0.98
1174
973
0.79
1061
0.95
1140
1.13
1213
1019
0.92
1104
1.10
1182
1.29
1253
1067
1.08
1149
1.27
1224
1.46
1294
1115
1.26
1195
1.46
1268
1.66
1336
1164
1.46
1241
1.67
1312
1.88
1379
1214
1.67
1289
1.90
1358
2.12
1422
1264
1.92
1336
2.15
1404
2.39
1467
1315
2.18
1385
2.43
1451
2.68
1512
RPM
BHP
1800
1950
1244
1281
1.33
1.49
AVAILABLE EXTERNAL STATIC PRESSURE (IN. WG)
1.4
1.6
1.8
RPM
BHP
RPM
BHP
RPM
BHP
Standard Static Option
1308
1.51
1369
1.70
1427
1.90
1345
1.68
1405
1.88
1462
2.09
2100
2250
2400
2550
2700
2850
3000
1320
1359
1400
1441
1483
1527
1571
1.67
1.87
2.09
2.33
2.59
2.87
3.18
1382
1420
1460
1500
1541
1583
1626
CFM
1.2
1.87
2.08
2.31
2.55
2.83
3.12
3.44
1441
1479
1517
1557
1597
1638
1680
2.08
2.29
2.53
2.79
3.07
3.37
3.70
1498
1534
1572
1610
1650
1690
-
2.29
2.51
2.76
3.03
3.32
3.63
-
BHP
1.15
1.31
1.48
1.66
1.87
2.10
2.35
2.63
2.93
2.0
RPM
BHP
Medium Static Option
1483
2.10
1517
2.30
1552
1587
1624
1662
1701
-
2.51
2.74
2.99
3.27
3.57
-
NOTE: For more information, see General Fan Performance Notes.
- Medium Static Option
- High Static Option
Boldface indicates field-supplied drive is required.
1. Recommend using field-supplied fan pulley (part no. 1175830), motor pulley (part no. 1175849) and belt (part no. 1178128).
Table 22 – RAS072, 3 PHASE, 6 TON VERTICAL SUPPLY
CFM
0.2
RPM
1800
1950
2100
907
965
1024
2250
2400
2550
2700
2850
3000
1083
1143
1203
1264
1326
1387
CFM
1800
1950
2100
2250
2400
2550
2700
2850
3000
AVAILABLE EXTERNAL STATIC PRESSURE (IN. WG)
0.4
0.6
0.8
BHP
RPM
BHP
RPM
BHP
RPM
BHP
Field Supplied Drive1
Standard Static Option
0.63
1006
0.80
1092
0.97
1169
1.14
0.77
1060
0.95
1143
1.13
1218
1.32
0.93
1115
1.12
1195
1.32
1268
1.52
1.11
1170
1.32
1248
1.53
1319
1.74
1.32
1227
1.54
1302
1.76
1371
1.99
1.55
1284
1.78
1357
2.02
1424
2.26
1.81
1342
2.06
1412
2.31
1478
2.56
2.09
1400
2.36
1469
2.62
1532
2.89
2.41
1459
2.69
1525
2.97
1587
3.25
1.2
RPM
BHP
1304
1350
1398
1446
1496
1546
1597
1648
-
1.51
1.71
1.93
2.18
2.45
2.75
3.07
3.43
-
AVAILABLE EXTERNAL STATIC PRESSURE (IN. WG)
1.4
1.6
1.8
RPM
BHP
RPM
BHP
RPM
BHP
Standard Static Option
Medium Static Option
1365
1.69
1422
1.88
1477
2.08
1410
1.91
1467
2.11
1520
2.31
1457
2.14
1512
2.35
1565
2.57
1504
2.40
1559
2.62
1611
2.85
1552
2.68
1606
2.92
1658
3.16
1601
2.99
1654
3.24
1705
3.50
1651
3.33
1703
3.59
1702
3.70
-
1.0
RPM
BHP
1239
1287
1335
1385
1435
1487
1539
1592
1646
1.32
1.51
1.72
1.96
2.22
2.50
2.82
3.16
3.53
2.0
RPM
BHP
High Static Option
1528
2.28
1572
2.52
1616
2.79
1661
3.09
1707
3.40
-
NOTE: For more information, see General Fan Performance Notes.
Boldface indicates field-supplied drive is required.
1. Recommend using field-supplied fan pulley (part no. 1175830), motor pulley (part no. 1175849) and belt (part no. 1178128).
63
513 31 3209 02
FAN PERFORMANCE (cont.)
Table 23 – RAS090 / 091, 3 PHASE, 7.5 TON HORIZONTAL SUPPLY
CFM
2250
2438
2625
2813
3000
3188
3375
3563
3750
0.2
RPM
BHP
Field Supplied Drive1
465
0.43
488
0.51
510
0.60
533
0.70
557
0.82
581
0.94
606
1.08
630
1.24
655
1.41
RPM
555
575
595
616
637
659
681
703
726
AVAILABLE EXTERNAL STATIC PRESSURE (IN. WG)
0.4
0.6
0.8
BHP
RPM
BHP
RPM
Standard Static Option
0.64
629
0.86
694
0.73
648
0.97
712
0.84
666
1.09
729
0.95
686
1.22
748
1.08
705
1.36
766
1.23
726
1.51
785
1.38
746
1.68
805
1.55
767
1.87
825
1.74
789
2.07
845
AVAILABLE EXTERNAL STATIC PRESSURE (IN. WG)
1.4
1.6
1.8
CFM
RPM
BHP
RPM
BHP
RPM
BHP
RPM
Medium Static Option
2250
806
1.60
856
1.87
903
2.15
947
2438
822
1.74
872
2.03
918
2.32
961
2625
839
1.90
887
2.19
933
2.49
977
2813
856
2.06
904
2.37
949
2.68
992
3000
873
2.24
921
2.56
966
2.89
1008
3188
891
2.44
938
2.77
982
3.10
1025
3375
909
2.65
955
2.99
1000
3.34
1041
3563
927
2.88
973
3.23
1017
3.59
1059
3750
946
3.12
992
3.48
1035
3.86
1076
NOTE: For more information, see General Fan Performance Notes.
Boldface indicates field−supplied drive is required.
BHP
1.10
1.21
1.34
1.49
1.64
1.81
2.00
2.20
2.41
1.0
RPM
BHP
Medium Static Option
753
1.34
769
1.47
786
1.62
804
1.77
822
1.94
840
2.12
859
2.32
878
2.53
897
2.76
1.2
2.0
RPM
BHP
High Static Option
988
2.75
1003
2.93
1018
3.13
1033
3.34
1049
3.56
1065
3.81
1081
4.06
1098
4.34
1115
4.632
BHP
2.45
2.62
2.81
3.01
3.22
3.45
3.70
3.96
4.24
1. Recommend using field-supplied fan pulley (part no. 1178189), motor pulley (part no. 1175832) and belt (part no. 1178128).
2. Recommend using field-supplied fan pulley (part no. 1175896) and belt (part no. 1178182).
Table 24 – RAS090 / 091, 3 PHASE, 7.5 TON VERTICAL SUPPLY
CFM
0.2
RPM
BHP
RPM
2250
2438
2625
2813
3000
3188
3375
3563
511
540
569
599
630
661
692
723
0.53
0.64
0.76
0.90
1.06
1.23
1.43
1.65
591
616
642
669
696
724
753
782
3750
755
1.89
811
CFM
2250
2438
2625
2813
3000
3188
1.2
RPM
BHP
832
851
870
890
912
934
1.71
1.87
2.04
2.24
2.46
2.69
AVAILABLE EXTERNAL STATIC PRESSURE (IN. WG)
0.4
0.6
0.8
BHP
RPM
BHP
RPM
Standard Static Option
0.73
660
0.95
722
0.85
683
1.08
743
0.99
706
1.23
765
1.14
731
1.39
788
1.31
756
1.58
811
1.50
782
1.78
836
1.71
809
2.00
861
1.94
836
2.25
887
2.20
864
2.52
913
AVAILABLE EXTERNAL STATIC PRESSURE (IN. WG)
1.4
1.6
1.8
RPM
BHP
RPM
BHP
RPM
Medium Static Option
882
1.99
928
2.29
973
899
2.16
945
2.46
989
918
2.34
2.66
1006
963
937
2.55
982
2.87
1024
958
2.78
1001
3.11
1043
979
3.02
1022
3.36
1063
3375
956
2.95
1000
3.29
3563
980
3.23
1023
3.58
3750
1004
3.54
1046
3.90
NOTE: For more information, see General Fan Performance Notes.
Boldface indicates field−supplied drive is required.
1042
1064
1086
3.64
3.94
4.27
1083
1104
1125
BHP
1.19
1.33
1.49
1.66
1.86
2.07
2.31
2.56
2.84
1.0
RPM
BHP
Medium Static Option
779
1.44
799
1.59
819
1.76
841
1.94
863
2.15
886
2.38
910
2.62
934
2.89
959
3.18
2.0
BHP
RPM
High Static Option
2.59
1015
2.78
1031
2.98
1048
3.21
1065
3.45
1083
3.72
1102
BHP
4.00
4.32
4.65
4.38
4.70
-
1122
1142
-
2.92
3.11
3.32
3.55
3.80
4.08
1. Recommend using field-supplied fan pulley (part no. 1175896) and belt (part no. 1178182).
513 31 3209 02
64
FAN PERFORMANCE (cont.)
Table 25 – RAS101 / 102, 3 PHASE, 8.5 TON HORIZONTAL SUPPLY
CFM
2550
2763
2975
3188
3400
3613
3825
4038
4250
CFM
2550
2763
2975
3188
3400
3613
3825
4038
4250
0.2
RPM
BHP
Field Supplied Drive1
438
0.39
459
0.47
481
0.56
504
0.67
526
0.80
550
0.94
573
1.09
597
1.26
621
1.45
1.2
RPM
BHP
769
782
796
811
826
842
858
875
892
1.11
1.22
1.34
1.48
1.63
1.81
2.00
2.20
2.43
RPM
523
541
560
580
600
620
641
663
685
AVAILABLE EXTERNAL STATIC PRESSURE (IN. WG)
0.4
0.6
0.8
BHP
RPM
BHP
RPM
Standard Static Option
0.50
595
0.64
658
0.60
611
0.73
673
0.70
628
0.84
689
0.82
646
0.97
705
0.95
664
1.11
722
1.10
683
1.26
740
1.26
702
1.43
758
1.44
722
1.62
777
1.64
743
1.83
796
AVAILABLE EXTERNAL STATIC PRESSURE (IN. WG)
1.4
1.6
1.8
RPM
BHP
RPM
BHP
RPM
Medium Static Option
819
1.30
865
1.49
909
831
1.41
877
1.60
921
845
1.53
890
1.73
933
858
1.67
903
1.88
946
873
1.83
917
2.04
959
888
2.01
932
2.22
973
903
2.20
946
2.42
988
919
2.41
962
2.63
1002
936
2.65
978
2.87
1018
1.0
BHP
RPM
BHP
0.78
0.88
1.00
1.13
1.27
1.43
1.61
1.81
2.02
716
730
745
760
776
793
810
827
845
0.94
1.05
1.16
1.30
1.45
1.62
1.80
2.00
2.22
2.0
RPM
BHP
High Static Option
951
1.92
963
2.04
974
2.16
987
2.31
1000
2.48
1013
2.67
1027
2.87
1041
3.10
1056
3.34
BHP
1.70
1.81
1.94
2.09
2.25
2.44
2.64
2.86
3.10
NOTE: For more information, see General Fan Performance Notes.
Boldface indicates field−supplied drive is required.
1. Recommend using field-supplied fan pulley (part no. 1178189) and belt (part no. 1179767).
Table 26 – RAS101 / 102, 3 PHASE, 8.5 TON VERTICAL SUPPLY
CFM
2550
2763
2975
3188
3400
3613
3825
4038
4250
CFM
2550
2763
2975
3188
3400
3613
3825
4038
4250
0.2
RPM
BHP
Field Supplied Drive1
477
0.43
503
0.52
529
0.62
556
0.74
583
0.88
611
1.03
639
1.19
668
1.38
696
1.58
RPM
556
578
601
625
650
675
701
727
753
1.2
RPM
BHP
RPM
794
810
827
845
864
883
903
924
945
1.14
1.28
1.44
1.62
1.80
2.01
2.23
2.47
2.73
842
858
874
891
909
928
947
967
987
AVAILABLE EXTERNAL STATIC PRESSURE (IN. WG)
0.4
0.6
0.8
BHP
RPM
BHP
RPM
Standard Static Option
0.57
624
0.71
685
0.67
644
0.82
704
0.79
665
0.95
724
0.92
687
1.09
744
1.06
710
1.24
765
1.22
733
1.42
787
1.40
757
1.61
809
1.60
781
1.81
832
1.81
806
2.04
855
AVAILABLE EXTERNAL STATIC PRESSURE (IN. WG)
1.4
1.6
1.8
BHP
RPM
BHP
RPM
Medium Static Option
1.29
888
1.44
932
1.44
903
1.60
946
1.61
919
1.78
961
1.79
935
1.98
977
1.99
952
2.18
993
2.21
970
2.41
1010
2.44
988
2.65
1028
2.70
1008
2.92
1047
2.97
1027
3.20
1066
BHP
0.85
0.97
1.11
1.26
1.43
1.61
1.81
2.03
2.27
BHP
1.59
1.77
1.95
2.16
2.38
2.61
2.87
3.14
3.43
1.0
RPM
BHP
Medium Static Option
742
0.99
759
1.13
777
1.28
796
1.44
816
1.62
836
1.81
857
2.02
879
2.25
901
2.50
2.0
RPM
BHP
High Static Option
973
1.75
987
1.93
1001
2.13
1017
2.34
1033
2.57
1049
2.82
1066
3.08
1084
3.37
1103
3.672
NOTE: For more information, see General Fan Performance Notes.
Boldface indicates field−supplied drive is required.
1. Recommend using field-supplied fan pulley (part no. 1178189) and belt (part no. 1179767).
2. Recommend using field-supplied fan pulley (part no. 1175896), motor pulley (part no. 1178133) and belt (part no. 1178182).
65
513 31 3209 02
FAN PERFORMANCE (cont.)
Table 27 – RAS120 / 121, 3 PHASE, 10 TON HORIZONTAL SUPPLY
CFM
3000
3250
3500
3750
4000
4250
4500
4750
5000
CFM
3000
3250
3500
3750
4000
4250
4500
4750
0.2
RPM
BHP
Field Supplied Drive1
523
0.58
555
0.71
588
0.86
621
1.03
655
1.23
689
1.45
723
1.69
758
793
1.96
2.26
RPM
592
620
649
679
709
741
773
805
838
1.2
RPM
BHP
Standard Static Opt.
830
1.39
847
1.57
865
1.77
885
1.99
907
2.24
930
2.51
954
2.81
979
3.13
RPM
883
897
914
932
952
973
996
1019
AVAILABLE EXTERNAL STATIC PRESSURE (IN. WG)
0.4
0.6
0.8
BHP
RPM
BHP
RPM
Standard Static Option
0.73
657
0.88
718
0.87
681
1.04
739
1.03
707
1.21
762
1.21
734
1.40
786
1.42
761
1.61
812
1.65
790
1.86
838
1.90
820
2.12
866
2.19
2.50
850
881
2.42
2.74
894
923
AVAILABLE EXTERNAL STATIC PRESSURE (IN. WG)
1.4
1.6
1.8
BHP
RPM
BHP
RPM
Medium Static Option
1.57
934
1.76
982
1.76
946
1.96
993
1.97
961
2.18
1007
2.20
978
2.42
1022
2.46
996
2.68
1038
2.74
1015
2.97
1057
3.05
1037
3.29
1076
3.38
1059
3.63
1097
5000
1005
3.49
1044
3.74
1082
NOTE: For more information, see General Fan Performance Notes.
Boldface indicates field−supplied drive is required.
4.01
1119
1.0
BHP
RPM
BHP
1.05
1.21
1.39
1.59
1.82
2.07
2.35
2.65
2.98
775
794
815
837
860
885
910
937
965
1.22
1.39
1.58
1.79
2.03
2.29
2.57
2.89
3.23
BHP
RPM
BHP
1.95
2.16
2.38
2.64
2.91
3.21
3.54
3.89
4.27
1029
1039
1051
1065
1080
1097
1115
1135
1156
2.14
2.36
2.60
2.86
3.14
3.45
3.79
4.15
4.55
2.0
1. Recommend using field-supplied fan pulley (part no. 1178190) and belt (part no. 1178181).
Table 28 – RAS120 / 121, 3 PHASE, 10 TON VERTICAL SUPPLY
CFM
3000
3250
3500
3750
4000
4250
4500
4750
5000
0.2
RPM
BHP
Field Supplied Drive1
556
0.65
590
0.79
625
0.96
661
1.16
697
1.37
733
1.62
770
1.89
807
2.20
844
2.54
RPM
623
655
687
719
753
787
821
856
891
AVAILABLE EXTERNAL STATIC PRESSURE (IN. WG)
0.4
0.6
0.8
BHP
RPM
BHP
RPM
Standard Static Option
0.80
684
0.95
738
0.96
713
1.13
766
1.14
742
1.32
794
1.35
773
1.54
822
1.58
804
1.79
852
1.84
836
2.06
883
2.13
869
2.36
914
2.45
902
2.69
945
2.80
936
3.06
978
RPM
BHP
3000
3250
3500
3750
4000
4250
4500
836
861
886
912
940
968
996
1.42
1.63
1.86
2.12
2.40
2.71
3.05
AVAILABLE EXTERNAL STATIC PRESSURE (IN. WG)
1.4
1.6
1.8
RPM
BHP
RPM
BHP
RPM
Medium Static Option
881
1.57
923
1.73
963
904
1.79
945
1.96
985
929
2.04
969
2.22
1008
954
2.31
994
2.50
1031
980
2.61
1019
2.81
1056
1007
2.93
1045
3.15
1081
1035
3.28
1072
3.51
1108
4750
5000
1026
1056
3.42
3.82
1063
1093
CFM
1.2
3.66
4.08
1100
1128
3.91
4.34
1135
1162
1.0
BHP
RPM
BHP
1.11
1.29
1.50
1.73
1.99
2.28
2.59
2.94
3.31
789
815
841
869
897
926
956
986
1018
1.26
1.46
1.68
1.93
2.20
2.49
2.82
3.18
3.57
BHP
RPM
BHP
1.89
2.13
2.40
2.70
3.02
3.36
3.74
4.15
4.59
1001
1023
1045
1068
1092
1117
1142
1168
-
2.05
2.30
2.58
2.89
3.22
3.58
3.97
4.39
-
2.0
NOTE: For more information, see General Fan Performance Notes.
Boldface indicates field−supplied drive is required.
1. Recommend using field-supplied fan pulley (part no. 1178190) and belt (part no. 1178181).
513 31 3209 02
66
FAN PERFORMANCE (cont.)
Table 29 – RAS150, 3 PHASE, 12.5 TON HORIZONTAL SUPPLY
CFM
3438
3750
4063
4375
4688
5000
5313
5625
5938
6250
CFM
3438
3750
4063
4375
0.2
RPM
BHP
Field Supplied Drive1
580
0.82
621
1.03
663
1.28
706
1.56
749
1.89
793
2.26
837
2.69
882
3.16
926
3.68
971
4.26
RPM
642
679
717
757
797
838
880
922
964
1007
1.2
RPM
BHP
RPM
860
885
912
941
1.72
1.99
2.31
2.66
910
932
957
984
AVAILABLE EXTERNAL STATIC PRESSURE (IN. WG)
0.4
0.6
0.8
BHP
RPM
BHP
RPM
Standard Static Option
0.99
700
1.16
756
1.21
734
1.40
786
1.47
769
1.67
818
1.77
805
1.98
852
2.11
843
2.34
887
2.50
881
2.74
923
2.93
921
3.19
961
3.42
961
3.68
999
3.96
1001
4.23
1038
4.55
AVAILABLE EXTERNAL STATIC PRESSURE (IN. WG)
1.4
1.6
1.8
BHP
RPM
BHP
RPM
Medium Static Option
1.92
957
2.12
1003
2.20
978
2.42
1022
2.53
1001
2.75
1043
2.89
1026
3.13
1066
4688
972
3.05
1013
3.29
5000
1005
3.49
1044
3.74
5313
1038
3.97
1076
4.24
5625
1073
4.51
5938
6250
NOTE: For more information, see General Fan Performance Notes.
Boldface indicates field−supplied drive is required.
1053
1082
1113
-
3.54
4.01
4.52
-
1092
1119
-
1.0
BHP
RPM
BHP
1.34
1.59
1.88
2.20
2.57
2.98
3.44
3.95
4.52
-
809
837
866
897
930
965
1000
1037
-
1.53
1.79
2.09
2.43
2.81
3.23
3.71
4.23
-
BHP
RPM
BHP
2.32
2.64
2.98
3.37
1048
1065
1084
1106
1130
1156
-
2.54
2.86
3.22
3.62
4.06
4.55
-
2.0
3.80
4.27
-
1. Recommend using field-supplied fan pulley (part no. 1178189) and belt (part no. 1179767).
2. Recommend using field-supplied fan pulley (part no. 1175896), motor pulley (part no. 1178133) and belt (part no. 1178182).
Table 30 – RAS150, 3 PHASE, 12.5 TON VERTICAL SUPPLY
CFM
3438
3750
4063
4375
4688
5000
5313
5625
5938
6250
CFM
0.2
RPM
BHP
Field Supplied Drive1
616
0.92
661
1.16
706
1.43
752
1.75
798
2.12
844
2.54
891
3.01
938
3.53
986
4.12
-
RPM
679
719
761
804
847
891
936
981
1026
-
1.2
RPM
BHP
RPM
3438
3750
4063
880
912
947
1.80
2.12
2.48
922
954
987
4375
4688
5000
5313
5625
5938
6250
982
1018
1056
1094
-
2.88
3.33
3.82
4.38
-
1021
1056
1093
1130
-
AVAILABLE EXTERNAL STATIC PRESSURE (IN. WG)
0.4
0.6
0.8
BHP
RPM
BHP
RPM
Standard Static Option
1.10
735
1.27
786
1.35
773
1.54
822
1.64
812
1.85
860
1.98
852
2.20
898
2.36
894
2.60
937
2.80
936
3.06
978
3.28
978
3.56
1019
3.83
1022
4.12
1060
4.43
AVAILABLE EXTERNAL STATIC PRESSURE (IN. WG)
1.4
1.6
1.8
BHP
RPM
BHP
RPM
Medium Static Option
1.98
963
2.15
1002
2.31
994
2.50
1031
2.68
1025
2.89
1062
3.10
3.57
4.08
4.65
-
1058
1093
1128
-
3.32
3.81
4.34
-
1094
1128
1162
-
1.0
BHP
RPM
BHP
1.45
1.73
2.06
2.43
2.85
3.31
3.83
4.41
-
835
869
904
941
979
1018
1057
1097
-
1.62
1.93
2.27
2.65
3.09
3.57
4.11
4.70
-
BHP
RPM
BHP
2.33
2.70
3.10
1039
1068
1098
1129
1162
-
2.51
2.89
3.31
3.77
4.29
-
2.0
3.55
4.04
4.59
-
NOTE: For more information, see General Fan Performance Notes.
Boldface indicates field−supplied drive is required.
1. Recommend using field-supplied fan pulley (part no. 1178189) and belt (part no. 1179767).
2. Recommend using field-supplied fan pulley (part no. 1175896), motor pulley (part no. 1178133) and belt (part no. 1178182).
67
513 31 3209 02
FAN PERFORMANCE (cont.)
Table 31 – RAS180, 3 PHASE, 15 TON HORIZONTAL SUPPLY
0.2
CFM
RPM
425
448
472
496
520
544
568
593
617
4500
4875
5250
5625
6000
6375
6750
7125
7500
BHP
0.76
0.92
1.10
1.30
1.52
1.77
2.05
2.35
2.69
RPM
490
510
531
552
574
596
618
641
664
1.2
CFM
4500
4875
5250
5625
6000
6375
6750
7125
7500
0.4
RPM
719
725
734
746
759
773
789
806
823
1.4
BHP
2.34
2.54
2.76
3.03
3.32
3.64
4.00
4.39
4.82
RPM
772
776
783
791
802
814
828
844
860
Available External Static Pressure (in. wg)
0.6
BHP
RPM
BHP
RPM
1.02
550
1.30
607
1.20
566
1.49
621
1.40
584
1.70
636
1.62
603
1.94
652
1.86
623
2.20
670
2.13
644
2.49
688
2.43
664
2.81
707
2.75
685
3.16
727
3.11
707
3.53
747
Available External Static Pressure (in. wg)
1.6
BHP
RPM
BHP
RPM
2.76
823
3.20
872
2.95
825
3.40
873
3.18
830
3.63
876
3.44
836
3.89
880
3.74
845
4.18
887
4.07
855
4.52
895
4.43
867
4.89
905
4.84
881
5.29
917
5.27
895
5.74
-
0.8
1.0
BHP
1.61
1.81
2.03
2.28
2.55
2.86
3.19
3.56
3.95
RPM
664
674
686
699
715
731
749
767
786
1.8
BHP
1.96
2.15
2.38
2.64
2.92
3.24
3.59
3.97
4.38
2.0
BHP
3.67
3.87
4.10
4.36
4.66
4.99
5.36
5.78
-
RPM
918
919
920
923
928
935
943
-
BHP
4.16
4.37
4.60
4.86
5.16
5.49
5.87
-
NOTE: For more information, see General Fan Performance Notes.
Table 32 – RAS180, 3 PHASE, 15 TON VERTICAL SUPPLY
CFM
4500
4875
5250
5625
6000
6375
6750
7125
7500
0.2
RPM
423
447
471
496
520
545
571
596
622
0.4
BHP
0.77
0.94
1.13
1.35
1.59
1.86
2.17
2.50
2.87
RPM
487
507
528
550
572
594
617
640
663
Available External Static Pressure (in. wg)
0.6
BHP
RPM
BHP
RPM
0.99
545
1.22
601
1.18
563
1.42
615
1.38
581
1.64
631
1.62
600
1.89
648
1.88
620
2.17
666
2.17
640
2.47
684
2.48
661
2.81
704
2.83
683
3.17
724
3.22
705
3.58
744
Available External Static Pressure (in. wg)
1.6
RPM
BHP
RPM
BHP
RPM
BHP
RPM
4500
707
2.02
758
2.33
806
2.66
853
4875
716
2.24
764
2.55
811
2.89
856
5250
726
2.49
772
2.81
817
3.14
860
5625
738
2.77
782
3.09
825
3.43
867
6000
752
3.08
794
3.41
835
3.76
875
6375
767
3.42
807
3.76
846
4.12
885
6750
784
3.80
822
4.15
859
4.51
896
7125
801
4.22
838
4.58
874
4.95
909
7500
818
4.66
854
5.04
889
5.42
923
NOTE: For more information, see General Fan Performance Notes.
CFM
513 31 3209 02
1.2
1.4
0.8
1.0
BHP
1.47
1.67
1.91
2.17
2.46
2.78
3.13
3.52
3.93
RPM
655
666
679
694
710
726
744
763
782
1.8
BHP
1.73
1.95
2.19
2.46
2.76
3.10
3.46
3.86
4.30
2.0
BHP
3.01
3.24
3.50
3.79
4.12
4.49
4.89
5.33
5.81
RPM
898
900
903
908
914
923
933
944
-
BHP
3.37
3.61
3.87
4.17
4.50
4.87
5.28
5.73
-
68
FAN PERFORMANCE (cont.)
Table 33 – PULLEY ADJUSTMENT
1 phase
UNIT
RAS
1 phase
3 phase
036
1 phase
3 phase
048
120/121
150
180
3 phase
3 phase
3 phase
101/102
3 phase
090/091
3 phase
072
3 phase
3 phase
060
MOTOR/DRIVE
COMBO
0.0
0.5
1.0
MOTOR PULLEY TURNS OPEN
1.5
2.0
2.5
3.0
3.5
4.0
4.5
5.0
Standard Static
854
825
795
766
736
707
678
648
619
589
560
Medium Static
−
−
−
−
−
−
−
−
−
−
−
High Static
−
−
−
−
−
−
−
−
−
−
−
Standard Static
854
825
795
766
736
707
678
648
619
589
560
Medium Static
−
−
−
−
−
−
−
−
−
−
−
High Static
1466
1423
1380
1337
1294
1251
1207
1164
1121
1078
1035
Standard Static
854
825
795
766
736
707
678
648
619
589
560
Medium Static
−
−
−
−
−
−
−
−
−
−
−
High Static
−
−
−
−
−
−
−
−
−
−
−
Standard Static
854
825
795
766
736
707
678
648
619
589
560
Medium Static
−
−
−
−
−
−
−
−
−
−
−
High Static
1466
1423
1380
1337
1294
1251
1207
1164
1121
1078
1035
Standard Static
1175
1135
1094
1054
1013
973
932
892
851
811
770
Medium Static
1466
1423
1380
1337
1294
1251
1207
1164
1121
1078
1035
High Static
−
−
−
−
−
−
−
−
−
−
−
Standard Static
1175
1135
1094
1054
1013
973
932
892
851
811
770
Medium Static
1466
1423
1380
1337
1294
1251
1207
1164
1121
1078
1035
High Static
1687
1649
1610
1572
1533
1495
1457
1418
1380
1341
1303
Standard Static
1457
1419
1380
1342
1303
1265
1227
1188
1150
1111
1073
Medium Static
1518
1484
1449
1415
1380
1346
1311
1277
1242
1208
1173
High Static
1788
1757
1725
1694
1662
1631
1600
1568
1537
1505
1474
Standard Static
747
721
695
670
644
618
592
566
541
515
489
Medium Static
949
927
906
884
863
841
819
798
776
755
733
High Static
1102
1083
1063
1044
1025
1006
986
967
948
928
909
Standard Static
733
712
690
669
647
626
604
583
561
540
518
Medium Static
936
911
887
862
838
813
788
764
739
715
690
High Static
1084
1059
1035
1010
986
961
936
912
887
863
838
Standard Static
838
813
789
764
739
715
690
665
640
616
591
Medium Static
1084
1059
1035
1010
986
961
936
912
887
863
838
High Static
1240
1218
1196
1175
1153
1131
1109
1087
1066
1044
1022
Standard Static
838
813
789
764
739
715
690
665
640
616
591
Medium Static
1084
1059
1035
1010
986
961
936
912
887
863
838
High Static
1240
1218
1196
1175
1153
1131
1109
1087
1066
1044
1022
Standard Static
676
659
642
625
608
592
575
558
541
524
507
Medium Static
851
829
806
784
761
739
717
694
672
649
627
High Static
955
937
919
901
883
866
848
830
812
794
776
NOTE: Do not adjust pulley further than 5 turns open.
- Factory settings
69
513 31 3209 02
ELECTRICAL DATA FOR UNITS
PRODUCED ON OR AFTER JULY 30, 2012
NOTE: Check the serial number of unit to verify production date.
SERIAL NUMBER
1
2
3
4
5
6
7
8
9
10
U
1
2
3
1
1
2
3
4
5
Manufacture Location
Week of Manufacture
(fiscal calendar)
Sequence Number
Year of Manufacture
(12 = 2012)
513 31 3209 02
70
ELECTRICAL INFORMATION
(UNITS PRODUCED ON OR AFTER JULY 30, 2012)
Table 34 – RAS036
1−STAGE COOLING WITH 1−SPEED INDOOR FAN MOTOR
V-Ph-Hz
VOLTAGE
RANGE
MIN
MAX
208-1-60
187
230-1-60
COMP (ea)
OFM (ea)
RLA
LRA
253
16.6
79
187
253
16.6
79
208-3-60
187
253
10.4
73
230-3-60
187
253
10.4
73
460-3-60
414
506
5.8
38
575-3-60
518
633
3.8
37
3 TONS
IFM
WATTS
FLA
TYPE
EFF at
Full Load
325
325
325
325
325
325
325
325
325
325
325
325
325
325
325
325
1.5
1.5
1.5
1.5
1.5
1.5
1.5
1.5
1.5
1.5
0.8
0.8
0.8
0.6
0.6
0.6
STD
MED
STD
MED
STD
MED
HIGH
STD
MED
HIGH
STD
MED
HIGH
STD
MED
HIGH
67%
67%
67%
67%
75%
75%
87%
75%
75%
87%
75%
75%
87%
73%
73%
78%
Table 34 (cont.) − RAS048 1−STAGE COOLING WITH 1−SPEED INDOOR FAN MOTOR
V-Ph-Hz
VOLTAGE
RANGE
MIN
MAX
COMP (ea)
RLA
OFM (ea)
LRA
208-1-60
187
253
21.8
117
230-1-60
187
253
21.8
117
208-3-60
187
253
13.7
83
230-3-60
187
253
13.7
83
460-3-60
414
506
6.2
41
575-3-60
518
633
4.8
33
VOLTAGE
RANGE
MIN
MAX
IFM
WATTS
FLA
TYPE
EFF at
Full Load
325
325
325
325
325
325
325
325
325
325
325
325
325
325
325
325
1.5
1.5
1.5
1.5
1.5
1.5
1.5
1.5
1.5
1.5
0.8
0.8
0.8
0.6
0.6
0.6
STD
MED
STD
MED
STD
MED
HIGH
STD
MED
HIGH
STD
MED
HIGH
STD
MED
HIGH
67%
67%
67%
67%
75%
75%
87%
75%
75%
87%
75%
75%
87%
73%
73%
78%
COMP (ea)
OFM (ea)
RLA
LRA
208-1-60
187
253
26.2
134
230-1-60
187
253
26.2
134
208-3-60
187
253
15.6
110
230-3-60
187
253
15.6
110
460-3-60
414
506
7.7
52
575-3-60
518
633
5.8
39
71
4.9
4.9
4.9
4.9
5.2
5.2
6.9
5.2
5.2
6.7
2.6
2.6
3.4
2.4
2.4
2.0
4 TONS
Table 34 (cont.) − RAS060 1−STAGE COOLING WITH 1−SPEED INDOOR FAN MOTOR
V-Ph-Hz
FLA
FLA
4.9
4.9
4.9
4.9
5.2
5.2
6.9
5.2
5.2
6.7
2.6
2.6
3.4
2.4
2.4
2.0
5 TONS
IFM
WATTS
FLA
TYPE
EFF at
Full Load
325
325
325
325
325
325
325
325
325
325
325
325
325
325
325
325
1.5
1.5
1.5
1.5
1.5
1.5
1.5
1.5
1.5
1.5
0.8
0.8
0.8
0.6
0.6
0.6
STD
MED
STD
MED
STD
MED
HIGH
STD
MED
HIGH
STD
MED
HIGH
STD
MED
HIGH
67%
76%
67%
76%
75%
87%
89%
75%
87%
89%
75%
87%
89%
73%
78%
77%
FLA
4.9
7.0
4.9
7.0
5.2
6.9
8.4
5.2
6.7
8.3
2.6
3.4
4.2
2.4
2.0
2.8
513 31 3209 02
ELECTRICAL INFORMATION
(UNITS PRODUCED ON OR AFTER JULY 30, 2012) cont.
Table 34 (cont.) − RAS072 1−STAGE COOLING WITH 1−SPEED INDOOR FAN MOTOR
VOLTAGE
RANGE
V-Ph-Hz
MIN
COMP (ea)
RLA
MAX
OFM (ea)
LRA
208-3-60
187
253
19.0
123
230-3-60
187
253
19.0
123
460-3-60
414
506
9.7
62
575-3-60
518
633
7.4
50
Table 34 (cont.) −RAS091
IFM
WATTS
FLA
TYPE
EFF at
Full Load
325
325
325
325
325
325
325
325
325
325
325
325
1.5
1.5
1.5
1.5
1.5
1.5
0.8
0.8
0.8
0.6
0.6
0.6
STD
MED
HIGH
STD
MED
HIGH
STD
MED
HIGH
STD
MED
HIGH
87%
89%
87%
87%
89%
87%
87%
89%
87%
78%
77%
77%
1−STAGE COOLING WITH 1−SPEED INDOOR FAN MOTOR
VOLTAGE
RANGE
V-Ph-Hz
6 TONS
COMP (ea)
MAX
RLA
LRA
208-3-60
187
253
25.0
164
230-3-60
187
253
25.0
164
460-3-60
414
506
12.2
100
575-3-60
518
633
9.0
78
IFM
WATTS
FLA
TYPE
EFF at
Full Load
325
325
325
325
325
325
325
325
325
325
325
325
1.5
1.5
1.5
1.5
1.5
1.5
0.8
0.8
0.8
0.6
0.6
0.6
STD
MED
HIGH
STD
MED
HIGH
STD
MED
HIGH
STD
MED
HIGH
87%
89%
83%
87%
89%
83%
87%
89%
83%
72%
77%
81%
Table 34 (cont.) − RAS090 2−STAGE COOLING WITH 1−SPEED INDOOR FAN MOTOR
VOLTAGE
RANGE
V-Ph-Hz
MIN
COMP (Cir 1)
MAX
RLA
LRA
COMP (Cir 2)
RLA
LRA
208-3-60
187
253
13.6
83
13.6
83
230-3-60
187
253
13.6
83
13.6
83
460-3-60
414
506
6.1
41
6.1
41
575-3-60
518
633
4.2
33
4.2
33
513 31 3209 02
6.9
8.4
10.6
6.7
8.3
10.6
3.4
4.2
5.3
2.0
2.8
2.8
7.5 TONS
OFM (ea)
MIN
FLA
FLA
5.2
8.4
13.6
4.9
8.3
12.7
2.5
4.2
6.4
1.6
2.8
5.6
7.5 TONS
OFM (ea)
IFM
WATTS
FLA
TYPE
325
325
325
325
325
325
325
325
325
325
325
325
1.5
1.5
1.5
1.5
1.5
1.5
0.8
0.8
0.8
0.6
0.6
0.6
STD
MED
HIGH
STD
MED
HIGH
STD
MED
HIGH
STD
MED
HIGH
EFF at Full
Load
87%
89%
83%
87%
89%
83%
87%
89%
83%
72%
77%
81%
FLA
5.2
8.4
13.6
4.9
8.3
12.7
2.5
4.2
6.4
1.6
2.8
5.6
72
ELECTRICAL INFORMATION
(UNITS PRODUCED ON OR AFTER JULY 30, 2012) cont.
Table 34 (cont.) − RAS090 2−STAGE COOLING WITH 2 SPEED INDOOR FAN MOTOR
VOLTAGE
RANGE
V-Ph-Hz
COMP 1
COMP 2
7.5 TONS
OFM (ea)
MIN
MAX
RLA
LRA
RLA
LRA
208-3-60
187
253
13.6
83
13.6
83
230-3-60
187
253
13.6
83
13.6
83
460-3-60
414
506
6.1
41
6.1
41
575-3-60
518
633
4.2
33
4.2
33
IFM
WATTS
FLA
TYPE
325
325
325
325
325
325
325
325
325
325
325
325
1.5
1.5
1.5
1.5
1.5
1.5
0.8
0.8
0.8
0.6
0.6
0.6
STD
MED
HIGH
STD
MED
HIGH
STD
MED
HIGH
STD
MED
HIGH
EFF at Full
Load
0.84
0.85
0.84
0.84
0.85
0.84
0.79
0.85
0.84
0.81
0.84
0.83
Table 34 (cont.) − RAS101 1−STAGE COOLING WITH 1−SPEED INDOOR FAN MOTOR
VOLTAGE
RANGE
V-Ph-Hz
MIN
COMP (ea)
RLA
MAX
208-3-60
187
253
29.5
195
230-3-60
187
253
29.5
195
460-3-60
414
506
14.7
95
575-3-60
518
633
12.2
80
IFM
WATTS
FLA
TYPE
EFF at
Full Load
325
325
325
325
325
325
325
325
325
325
325
325
1.5
1.5
1.5
1.5
1.5
1.5
0.8
0.8
0.8
0.6
0.6
0.6
STD
MED
HIGH
STD
MED
HIGH
STD
MED
HIGH
STD
MED
HIGH
87%
87%
87%
87%
87%
87%
87%
87%
87%
72%
78%
77%
Table 34 (cont.) − RAS102 2−STAGE COOLING WITH 1−SPEED INDOOR FAN MOTOR
V-Ph-Hz
VOLTAGE
RANGE
MIN
COMP (Cir 1)
MAX
RLA
LRA
COMP (Cir 2)
RLA
LRA
208-3-60
187
253
14.5
98
13.7
83
230-3-60
187
253
14.5
98
13.7
83
460-3-60
414
506
6.3
55
6.2
41
575-3-60
518
633
6.0
41
4.8
33
73
5.8
8.6
13.6
5.6
7.8
12.7
2.9
3.8
6.4
2.8
4.5
6.2
8.5 TONS
OFM (ea)
LRA
FLA
325
325
325
325
325
325
325
325
325
325
325
325
5.2
6.9
10.6
4.9
6.7
10.6
2.5
3.4
5.3
1.6
2.0
2.8
8.5 TONS
OFM (ea)
WATTS
FLA
IFM
FLA
1.5
1.5
1.5
1.5
1.5
1.5
0.8
0.8
0.8
0.6
0.6
0.6
EFF at Full
Load
TYPE
STD
MED
HIGH
STD
MED
HIGH
STD
MED
HIGH
STD
MED
HIGH
87%
87%
87%
87%
87%
87%
87%
87%
87%
72%
78%
77%
513 31 3209 02
FLA
5.2
6.9
10.6
4.9
6.7
10.6
2.5
3.4
5.3
1.6
2.0
2.8
ELECTRICAL INFORMATION
(UNITS PRODUCED ON OR AFTER JULY 30, 2012) cont.
Table 34 (cont.) − RAS102 2−STAGE COOLING WITH 2 SPEED INDOOR FAN MOTOR
VOLTAGE
RANGE
V-Ph-Hz
MIN
COMP 1
RLA
MAX
COMP 2
LRA
RLA
8.5 TONS
OFM (ea)
LRA
208-3-60
187
253
14.5
98
13.7
83
230-3-60
187
253
14.5
98
13.7
83
460-3-60
414
506
6.3
55
6.2
41
575-3-60
518
633
6.0
41
4.8
33
IFM
WATTS
FLA
TYPE
EFF at Full
Load
325
325
325
325
325
325
325
325
325
325
325
325
1.5
1.5
1.5
1.5
1.5
1.5
0.8
0.8
0.8
0.6
0.6
0.6
STD
MED
HIGH
STD
MED
HIGH
STD
MED
HIGH
STD
MED
HIGH
0.84
0.77
0.82
0.84
0.77
0.82
0.79
0.77
0.82
0.81
0.80
0.84
Table 34 (cont.) − RAS121 1−STAGE COOLING WITH 1−SPEED INDOOR FAN MOTOR
VOLTAGE
RANGE
V-Ph-Hz
COMP (ea)
MAX
RLA
LRA
208-3-60
187
253
30.1
225
230-3-60
187
253
30.1
225
460-3-60
414
506
16.7
114
575-3-60
518
633
12.2
80
IFM
WATTS
FLA
TYPE
EFF at
Full Load
325
325
325
325
325
325
325
325
325
325
325
325
1.5
1.5
1.5
1.5
1.5
1.5
0.8
0.8
0.8
0.6
0.6
0.6
STD
MED
HIGH
STD
MED
HIGH
STD
MED
HIGH
STD
MED
HIGH
87%
87%
83%
87%
87%
83%
87%
87%
83%
78%
77%
81%
Table 34 (cont.) − RAS120 2−STAGE COOLING WITH 1−SPEED INDOOR FAN MOTOR
VOLTAGE
RANGE
V-Ph-Hz
MIN
COMP (Cir 1)
MAX
RLA
LRA
COMP (Cir 2)
RLA
LRA
208-3-60
187
253
15.6
110
15.9
110
230-3-60
187
253
15.6
110
15.9
110
460-3-60
414
506
7.7
52
7.7
52
575-3-60
518
633
5.8
39
5.7
39
513 31 3209 02
5.8
7.1
10.8
5.6
6.8
9.8
2.9
3.8
4.9
2.8
3.5
4.5
10 TONS
OFM (ea)
MIN
FLA
325
325
325
325
325
325
325
325
325
325
325
325
6.9
10.6
13.6
6.7
10.6
12.7
3.4
5.3
6.4
2.0
2.8
5.6
10 TONS
OFM (ea)
WATTS
FLA
IFM
FLA
1.5
1.5
1.5
1.5
1.5
1.5
0.8
0.8
0.8
0.6
0.6
0.6
TYPE
STD
MED
HIGH
STD
MED
HIGH
STD
MED
HIGH
STD
MED
HIGH
EFF at Full
Load
87%
87%
83%
87%
87%
83%
87%
87%
83%
78%
77%
81%
FLA
6.9
10.6
13.6
6.7
10.6
12.7
3.4
5.3
6.4
2.0
2.8
5.6
74
ELECTRICAL INFORMATION
(UNITS PRODUCED ON OR AFTER JULY 30, 2012) cont.
Table 34 (cont.) − RAS120 2−STAGE COOLING WITH 2 SPEED INDOOR FAN MOTOR
VOLTAGE
RANGE
V-Ph-Hz
MIN
COMP 1
MAX
RLA
COMP 2
LRA
RLA
10 TONS
OFM (ea)
LRA
208-3-60
187
253
15.6
110
15.9
110
230-3-60
187
253
15.6
110
15.9
110
460-3-60
414
506
7.7
52
7.7
52
575-3-60
518
633
5.8
39
5.7
39
IFM
WATTS
FLA
TYPE
EFF at Full
Load
325
325
325
325
325
325
325
325
325
325
325
325
1.5
1.5
1.5
1.5
1.5
1.5
0.8
0.8
0.8
0.6
0.6
0.6
STD
MED
HIGH
STD
MED
HIGH
STD
MED
HIGH
STD
MED
HIGH
0.77
0.82
0.84
0.77
0.82
0.84
0.77
0.82
0.84
0.80
0.84
0.83
Table 34 (cont.) − RAS150 2−STAGE COOLING WITH 1−SPEED INDOOR FAN MOTOR
V-Ph-Hz
VOLTAGE
RANGE
MIN
COMP (Cir 1)
MAX
RLA
LRA
COMP (Cir 2)
RLA
LRA
208-3-60
187
253
19.0
123
22.4
149
230-3-60
187
253
19.0
123
22.4
149
460-3-60
414
506
9.7
62
10.6
75
575-3-60
518
633
7.4
50
7.7
54
VOLTAGE
RANGE
COMP 1
COMP 2
OFM (ea)
IFM
WATTS
FLA
1070
1070
1070
1070
1070
1070
1070
1070
1070
1070
1070
1070
6.2
6.2
6.2
6.2
6.2
6.2
3.1
3.1
3.1
2.5
2.5
2.5
MAX
RLA
LRA
RLA
LRA
208-3-60
187
253
19.0
123
22.4
149
230-3-60
187
253
19.0
123
22.4
149
460-3-60
414
506
9.7
62
10.6
75
575-3-60
518
633
7.4
50
7.7
54
75
EFF at Full
Load
TYPE
STD
MED
HIGH
STD
MED
HIGH
STD
MED
HIGH
STD
MED
HIGH
89%
87%
83%
89%
87%
83%
89%
87%
83%
77%
77%
81%
FLA
8.4
10.6
13.6
8.3
10.6
12.7
4.2
5.3
6.4
2.8
2.8
5.6
12.5 TONS
OFM (ea)
MIN
7.1
10.8
13.6
6.8
9.8
12.7
3.8
4.9
6.4
3.5
4.5
6.2
12.5 TONS
Table 34 (cont.) − RAS150 2−STAGE COOLING WITH 2 SPEED INDOOR FAN MOTOR
V-Ph-Hz
FLA
IFM
WATTS
FLA
TYPE
EFF at Full
Load
1070
1070
1070
1070
1070
1070
1070
1070
1070
1070
1070
1070
6.2
6.2
6.2
6.2
6.2
6.2
3.1
3.1
3.1
2.5
2.5
2.5
STD
MED
HIGH
STD
MED
HIGH
STD
MED
HIGH
STD
MED
HIGH
0.85
0.82
0.84
0.85
0.82
0.84
0.85
0.82
0.84
0.84
0.84
0.83
513 31 3209 02
FLA
8.6
10.8
13.6
7.8
9.8
12.7
3.8
4.9
6.4
4.5
4.5
6.2
ELECTRICAL INFORMATION
(UNITS PRODUCED ON OR AFTER JULY 30, 2012) cont.
Table 34 (cont.) − RAS180 2−STAGE COOLING WITH 1−SPEED INDOOR FAN MOTOR
VOLTAGE
RANGE
V-Ph-Hz
MIN
COMP (Cir 1)
RLA
MAX
COMP (Cir 2)
LRA
RLA
LRA
208-3-60
187
253
25.0
164
25.0
164
230-3-60
187
253
25.0
164
25.0
164
460-3-60
414
506
12.2
100
12.8
100
575-3-60
518
633
9.8
78
9.6
78
Table 34 (cont.) −RAS180
COMP 1
COMP 2
MIN
MAX
RLA
LRA
RLA
LRA
208-3-60
187
253
25.0
164
25.0
164
230-3-60
187
253
25.0
164
25.0
164
460-3-60
414
506
12.2
100
12.8
100
575-3-60
518
633
9.8
78
9.6
78
513 31 3209 02
OFM (ea)
WATTS
IFM
FLA
280
280
280
280
280
280
280
280
280
280
280
280
EFF at Full
Load
TYPE
1.5
1.5
1.5
1.5
1.5
1.5
0.8
0.8
0.8
0.6
0.6
0.6
STD
MED
HIGH
STD
MED
HIGH
STD
MED
HIGH
STD
MED
HIGH
89%
87%
90%
89%
87%
90%
89%
87%
90%
77%
77%
94%
2−STAGE COOLING WITH 2 SPEED INDOOR FAN MOTOR
VOLTAGE
RANGE
V-Ph-Hz
15 TONS
OFM (ea)
FLA
8.4
10.6
20.4
8.3
10.6
20.4
4.2
5.3
10.2
2.8
2.8
9.0
15 TONS
IFM
WATTS
FLA
TYPE
EFF at Full
Load
280
280
280
280
280
280
280
280
280
280
280
280
1.5
1.5
1.5
1.5
1.5
1.5
0.8
0.8
0.8
0.6
0.6
0.6
STD
MED
HIGH
STD
MED
HIGH
STD
MED
HIGH
STD
MED
HIGH
0.85
0.82
0.90
0.85
0.82
0.90
0.85
0.82
0.90
0.84
0.84
0.94
FLA
8.6
10.8
20.4
7.8
9.8
20.4
3.8
4.9
10.2
4.5
4.5
9
76
ELECTRIC HEAT − ELECTRICAL INFORMATION
(UNITS PRODUCED ON OR AFTER JULY 30, 2012)
Table 35 – RAS036
1−STAGE COOLING 1−SPEED INDOOR FAN MOTOR
WITHOUT FACTORY INSTALLED NON−FUSED DISCONNECT
SINGLE POINT KIT PART NUMBER
CRSINGLEXXXXXX
NOM.
V-PH-Hz.
208/
230-1-60
IFM
TYPE
STD
STD
208/
230-3-60
HIGH
STD
460-3-60
HIGH
LEGEND
APP PWR
C.O.
FLA
IFM
NOM PWR
P.E.
UNPWRD
77
ELECTRIC HEATER PART
NUMBER
CRHEATERXXXXXX
101A00
102A00
103B00
104B00
102A00,102A00
101A00
102A00
103B00
104B00
105A00
101A00
102A00
103B00
104B00
105A00
106A00
107A00
108A00
109A00
106A00
107A00
108A00
109A00
NOM
PWR
(kW)
4.4
6.5
8.7
10.5
13.0
4.4
6.5
8.7
10.5
16.0
4.4
6.5
8.7
10.5
16.0
6.0
8.8
11.5
14.0
6.0
8.8
11.5
14.0
APP
PWR
(kW)
3.3/4.0
4.9/6.0
6.5/8.0
7.9/9.6
9.8/11.9
3.3/4.0
4.9/6.0
6.5/8.0
7.9/9.6
12.0/14.7
3.3/4.0
4.9/6.0
6.5/8.0
7.9/9.6
12.0/14.7
5.5
8.1
10.6
12.9
5.5
8.1
10.6
12.9
NO C.O. or UNPWRD C.O.
NO P.E.
037
040
040
037
037
-
w/P.E.
(pwrd fr/unit)
037
040
040
037
037
-
- 208 / 230V / 460V / 575V
- Convenience outlet
- Full load amps
- Indoor fan motor
- 240V / 480V / 600V
- Power exhaust
- Unpowered convenience outlet
513 31 3209 02
ELECTRIC HEAT − ELECTRICAL INFORMATION
(UNITS PRODUCED ON OR AFTER JULY 30, 2012)
Table 35 (cont.) − RAS036
1−STAGE COOLING 1−SPEED INDOOR FAN MOTOR
WITH FACTORY INSTALLED NON−FUSED DISCONNECT
SINGLE POINT KIT PART NUMBER
CRSINGLEXXXXXX
NOM.
V-PH-Hz.
IFM
TYPE
208/
230-1-60
STD
STD
208/
230-3-60
HIGH
STD
460-3-60
HIGH
LEGEND
APP PWR
C.O.
FLA
IFM
NOM PWR
P.E.
UNPWRD
ELECTRIC HEATER PART
NUMBER
CRHEATERXXXXXX
101A00
102A00
103B00
104B00
102A00,102A00
101A00
102A00
103B00
104B00
105A00
101A00
102A00
103B00
104B00
105A00
106A00
107A00
108A00
109A00
106A00
107A00
108A00
109A00
NOM
PWR
(kW)
4.4
6.5
8.7
10.5
13.0
4.4
6.5
8.7
10.5
16.0
4.4
6.5
8.7
10.5
16.0
6.0
8.8
11.5
14.0
6.0
8.8
11.5
14.0
APP
PWR
(kW)
3.3/4.0
4.9/6.0
6.5/8.0
7.9/9.6
9.8/11.9
3.3/4.0
4.9/6.0
6.5/8.0
7.9/9.6
12.0/14.7
3.3/4.0
4.9/6.0
6.5/8.0
7.9/9.6
12.0/14.7
5.5
8.1
10.6
12.9
5.5
8.1
10.6
12.9
NO C.O. or UNPWRD C.O.
NO P.E.
037
037
037
040
040
037
037
037
037
037
037
037
037
037
037
-
w/P.E.
(pwrd fr/unit)
037
037
037
040
040
037
037
037
037
037
037
037
037
037
037
-
- 208 / 230V / 460V / 575V
- Convenience outlet
- Full load amps
- Indoor fan motor
- 240V / 480V / 600V
- Power exhaust
- Unpowered convenience outlet
513 31 3209 02
78
ELECTRIC HEAT − ELECTRICAL INFORMATION
(UNITS PRODUCED ON OR AFTER JULY 30, 2012)
Table 35 (cont.) − RAS048
1−STAGE COOLING 1−SPEED INDOOR FAN MOTOR
WITHOUT FACTORY INSTALLED NON−FUSED DISCONNECT
SINGLE POINT KIT PART NUMBER
CRSINGLEXXXXXX
NOM.
V-PH-Hz.
208/
230-1-60
IFM
TYPE
STD
STD
208/
230-3-60
HIGH
STD
460-3-60
HIGH
LEGEND
APP PWR
C.O.
FLA
IFM
NOM PWR
P.E.
UNPWRD
79
ELECTRIC HEATER PART
NUMBER
CRHEATERXXXXXX
101A00
103B00
102A00,102A00
103B00,103B00
104B00,104B00
102A00
103B00
105A00
104B00,104B00
102A00
103B00
105A00
104B00,104B00
106A00
108A00
109A00
108A00,108A00
106A00
108A00
109A00
108A00,108A00
NOM
PWR
(kW)
4.4
8.7
13.0
17.4
21.0
6.5
8.7
16.0
21.0
6.5
8.7
16.0
21.0
6.0
11.5
14.0
23.0
6.0
11.5
14.0
23.0
APP
PWR
(kW)
3.3/4.0
6.5/8.0
9.8/11.9
13.1/16.0
15.8/19.3
4.9/6.0
6.5/8.0
12.0/14.7
15.8/19.3
4.9/6.0
6.5/8.0
12.0/14.7
15.8/19.3
5.5
10.6
12.9
21.1
5.5
10.6
12.9
21.1
NO C.O. or UNPWRD C.O.
NO P.E.
037
040
040
040
037
038
037
038
037
037
w/P.E.
(pwrd fr/unit)
037
040
040
040
037
038
037
038
037
037
- 208 / 230V / 460V / 575V
- Convenience outlet
- Full load amps
- Indoor fan motor
- 240V / 480V / 600V
- Power exhaust
- Unpowered convenience outlet
513 31 3209 02
ELECTRIC HEAT − ELECTRICAL INFORMATION
(UNITS PRODUCED ON OR AFTER JULY 30, 2012)
Table 35 (cont.) − RAS048
1−STAGE COOLING 1−SPEED INDOOR FAN MOTOR
WITH FACTORY INSTALLED NON−FUSED DISCONNECT
SINGLE POINT KIT PART NUMBER
CRSINGLEXXXXXX
NOM.
V-PH-Hz.
IFM
TYPE
208/
230-1-60
STD
STD
208/
230-3-60
HIGH
STD
460-3-60
HIGH
LEGEND
APP PWR
C.O.
FLA
IFM
NOM PWR
P.E.
UNPWRD
ELECTRIC HEATER PART
NUMBER
CRHEATERXXXXXX
101A00
103B00
102A00,102A00
103B00,103B00
104B00,104B00
102A00
103B00
105A00
104B00,104B00
102A00
103B00
105A00
104B00,104B00
106A00
108A00
109A00
108A00,108A00
106A00
108A00
109A00
108A00,108A00
NOM
PWR
(kW)
4.4
8.7
13.0
17.4
21.0
6.5
8.7
16.0
21.0
6.5
8.7
16.0
21.0
6.0
11.5
14.0
23.0
6.0
11.5
14.0
23.0
APP
PWR
(kW)
3.3/4.0
6.5/8.0
9.8/11.9
13.1/16.0
15.8/19.3
4.9/6.0
6.5/8.0
12.0/14.7
15.8/19.3
4.9/6.0
6.5/8.0
12.0/14.7
15.8/19.3
5.5
10.6
12.9
21.1
5.5
10.6
12.9
21.1
NO C.O. or UNPWRD C.O.
NO P.E.
037
037
040
040
040
037
037
037
038
037
037
037
038
037
037
w/P.E.
(pwrd fr/unit)
037
037
040
040
040
037
037
037
038
037
037
037
038
037
037
- 208 / 230V / 460V / 575V
- Convenience outlet
- Full load amps
- Indoor fan motor
- 240V / 480V / 600V
- Power exhaust
- Unpowered convenience outlet
513 31 3209 02
80
ELECTRIC HEAT − ELECTRICAL INFORMATION
(UNITS PRODUCED ON OR AFTER JULY 30, 2012)
Table 35 (cont.) − RAS060
NOM.
V-PH-Hz.
IFM
TYPE
STD
208/
230-1-60
MED
STD
208/
230-3-60
MED
HIGH
STD
460-3-60
MED
HIGH
LEGEND
APP PWR
C.O.
FLA
IFM
NOM PWR
P.E.
PWRD
UNPWRD
81
1−STAGE COOLING 1−SPEED INDOOR FAN MOTOR
WITHOUT FACTORY INSTALLED NON−FUSED DISCONNECT
ELECTRIC HEATER PART
NUMBER
CRHEATERXXXXXX
102A00
103B00
102A00,102A00
103B00,103B00
104B00,104B00
102A00
103B00
102A00,102A00
103B00,103B00
104B00,104B00
102A00
104B00
105A00
104B00,104B00
104B00,105A00
102A00
104B00
105A00
104B00,104B00
104B00,105A00
102A00
104B00
105A00
104B00,104B00
104B00,105A00
106A00
108A00
109A00
108A00,108A00
108A00,109A00
106A00
108A00
109A00
108A00,108A00
108A00,109A00
106A00
108A00
109A00
108A00,108A00
108A00,109A00
NOM
PWR
(kW)
6.5
8.7
13.0
17.4
21.0
6.5
8.7
13.0
17.4
21.0
6.5
10.5
16.0
21.0
26.5
6.5
10.5
16.0
21.0
26.5
6.5
10.5
16.0
21.0
26.5
6.0
11.5
14.0
23.0
25.5
6.0
11.5
14.0
23.0
25.5
6.0
11.5
14.0
23.0
25.5
APP
PWR
(kW)
4.9/6.0
6.5/8.0
9.8/11.9
13.1/16.0
15.8/19.3
4.9/6.0
6.5/8.0
9.8/11.9
13.1/16.0
15.8/19.3
4.9/6.0
7.9/9.6
12.0/14.7
15.8/19.3
19.9/24.3
4.9/6.0
7.9/9.6
12.0/14.7
15.8/19.3
19.9/24.3
4.9/6.0
7.9/9.6
12.0/14.7
15.8/19.3
19.9/24.3
5.5
10.6
12.9
21.1
23.4
5.5
10.6
12.9
21.1
23.4
5.5
10.6
12.9
21.1
23.4
SINGLE POINT KIT PART NUMBER
CRSINGLEXXXXXX
NO C.O. or UNPWRD C.O.
NO P.E.
w/P.E.
(pwrd fr/unit)
037
040
040
040
037
040
040
040
037
038
038
037
038
038
037
038
038
037
037
037
037
037
037
037
040
040
040
037
040
040
040
037
038
038
037
038
038
038
038
038
037
037
037
037
037
037
- 208 / 230V / 460V / 575V
- Convenience outlet
- Full load amps
- Indoor fan motor
- 240V / 480V / 600V
- Power exhaust
- Powered convenience outlet
- Unpowered convenience outlet
513 31 3209 02
ELECTRIC HEAT − ELECTRICAL INFORMATION
(UNITS PRODUCED ON OR AFTER JULY 30, 2012)
Table 35 (cont.) − RAS060
1−STAGE COOLING 1−SPEED INDOOR FAN MOTOR
WITH FACTORY INSTALLED NON−FUSED DISCONNECT
SINGLE POINT KIT PART NUMBER
CRSINGLEXXXXXX
NOM.
V-PH-Hz.
IFM
TYPE
STD
208/
230-1-60
MED
STD
208/
230-3-60
MED
HIGH
STD
460-3-60
MED
HIGH
LEGEND
APP PWR
C.O.
FLA
IFM
NOM PWR
P.E.
PWRD
UNPWRD
ELECTRIC HEATER PART
NUMBER
CRHEATERXXXXXX
102A00
103B00
102A00,102A00
103B00,103B00
104B00,104B00
102A00
103B00
102A00,102A00
103B00,103B00
104B00,104B00
102A00
104B00
105A00
104B00,104B00
104B00,105A00
102A00
104B00
105A00
104B00,104B00
104B00,105A00
102A00
104B00
105A00
104B00,104B00
104B00,105A00
106A00
108A00
109A00
108A00,108A00
108A00,109A00
106A00
108A00
109A00
108A00,108A00
108A00,109A00
106A00
108A00
109A00
108A00,108A00
108A00,109A00
NOM
PWR
(kW)
6.5
8.7
13.0
17.4
21.0
6.5
8.7
13.0
17.4
21.0
6.5
10.5
16.0
21.0
26.5
6.5
10.5
16.0
21.0
26.5
6.5
10.5
16.0
21.0
26.5
6.0
11.5
14.0
23.0
25.5
6.0
11.5
14.0
23.0
25.5
6.0
11.5
14.0
23.0
25.5
APP
PWR
(kW)
4.9/6.0
6.5/8.0
9.8/11.9
13.1/16.0
15.8/19.3
4.9/6.0
6.5/8.0
9.8/11.9
13.1/16.0
15.8/19.3
4.9/6.0
7.9/9.6
12.0/14.7
15.8/19.3
19.9/24.3
4.9/6.0
7.9/9.6
12.0/14.7
15.8/19.3
19.9/24.3
4.9/6.0
7.9/9.6
12.0/14.7
15.8/19.3
19.9/24.3
5.5
10.6
12.9
21.1
23.4
5.5
10.6
12.9
21.1
23.4
5.5
10.6
12.9
21.1
23.4
NO C.O. or UNPWRD C.O.
NO P.E.
037
037
040
040
040
037
037
040
040
040
037
037
037
038
038
037
037
037
038
038
037
037
037
038
038
037
037
037
037
037
037
w/P.E.
(pwrd fr/unit)
037
037
040
040
040
037
037
040
040
040
037
037
037
038
038
037
037
037
038
038
037
037
038
038
038
037
037
037
037
037
037
- 208 / 230V / 460V / 575V
- Convenience outlet
- Full load amps
- Indoor fan motor
- 240V / 480V / 600V
- Power exhaust
- Powered convenience outlet
- Unpowered convenience outlet
513 31 3209 02
82
ELECTRIC HEAT − ELECTRICAL INFORMATION
(UNITS PRODUCED ON OR AFTER JULY 30, 2012)
Table 35 (cont.) − RAS072
1−STAGE COOLING 1−SPEED INDOOR FAN MOTOR
WITHOUT FACTORY INSTALLED NON−FUSED DISCONNECT
SINGLE POINT KIT PART NUMBER
CRSINGLEXXXXXX
NOM.
V-PH-Hz.
IFM
TYPE
STD
208/
230-3-60
MED
HIGH
STD
460-3-60
MED
HIGH
LEGEND
APP PWR
C.O.
FLA
IFM
NOM PWR
P.E.
PWRD
UNPWRD
83
ELECTRIC HEATER PART
NUMBER
CRHEATERXXXXXX
102A00
104B00
105A00
104B00,104B00
104B00,105A00
102A00
104B00
105A00
104B00,104B00
104B00,105A00
102A00
104B00
105A00
104B00,104B00
104B00,105A00
106A00
108A00
109A00
108A00,108A00
108A00,109A00
106A00
108A00
109A00
108A00,108A00
108A00,109A00
106A00
108A00
109A00
108A00,108A00
108A00,109A00
NOM
PWR
(kW)
6.5
10.5
16.0
21.0
26.5
6.5
10.5
16.0
21.0
26.5
6.5
10.5
16.0
21.0
26.5
6.0
11.5
14.0
23.0
25.5
6.0
11.5
14.0
23.0
25.5
6.0
11.5
14.0
23.0
25.5
APP
PWR
(kW)
4.9/6.0
7.9/9.6
12.0/14.7
15.8/19.3
19.9/24.3
4.9/6.0
7.9/9.6
12.0/14.7
15.8/19.3
19.9/24.3
4.9/6.0
7.9/9.6
12.0/14.7
15.8/19.3
19.9/24.3
5.5
10.6
12.9
21.1
23.4
5.5
10.6
12.9
21.1
23.4
5.5
10.6
12.9
21.1
23.4
NO C.O. or UNPWRD C.O.
NO P.E.
037
038
038
037
038
038
038
038
038
037
037
037
037
037
037
w/P.E.
(pwrd fr/unit)
037
038
038
038
038
038
038
038
038
037
037
037
037
037
037
- 208 / 230V / 460V / 575V
- Convenience outlet
- Full load amps
- Indoor fan motor
- 240V / 480V / 600V
- Power exhaust
- Powered convenience outlet
- Unpowered convenience outlet
513 31 3209 02
ELECTRIC HEAT − ELECTRICAL INFORMATION
(UNITS PRODUCED ON OR AFTER JULY 30, 2012)
Table 35 (cont.) − RAS072
1−STAGE COOLING 1−SPEED INDOOR FAN MOTOR
WITH FACTORY INSTALLED NON−FUSED DISCONNECT
SINGLE POINT KIT PART NUMBER
CRSINGLEXXXXXX
NOM.
V-PH-Hz.
IFM
TYPE
STD
208/
230-3-60
MED
HIGH
STD
460-3-60
MED
HIGH
LEGEND
APP PWR
C.O.
FLA
IFM
NOM PWR
P.E.
PWRD
UNPWRD
ELECTRIC HEATER PART
NUMBER
CRHEATERXXXXXX
102A00
104B00
105A00
104B00,104B00
104B00,105A00
102A00
104B00
105A00
104B00,104B00
104B00,105A00
102A00
104B00
105A00
104B00,104B00
104B00,105A00
106A00
108A00
109A00
108A00,108A00
108A00,109A00
106A00
108A00
109A00
108A00,108A00
108A00,109A00
106A00
108A00
109A00
108A00,108A00
108A00,109A00
NOM
PWR
(kW)
6.5
10.5
16.0
21.0
26.5
6.5
10.5
16.0
21.0
26.5
6.5
10.5
16.0
21.0
26.5
6.0
11.5
14.0
23.0
25.5
6.0
11.5
14.0
23.0
25.5
6.0
11.5
14.0
23.0
25.5
APP
PWR
(kW)
4.9/6.0
7.9/9.6
12.0/14.7
15.8/19.3
19.9/24.3
4.9/6.0
7.9/9.6
12.0/14.7
15.8/19.3
19.9/24.3
4.9/6.0
7.9/9.6
12.0/14.7
15.8/19.3
19.9/24.3
5.5
10.6
12.9
21.1
23.4
5.5
10.6
12.9
21.1
23.4
5.5
10.6
12.9
21.1
23.4
NO C.O. or UNPWRD C.O.
NO P.E.
037
037
037
038
038
037
037
037
038
038
037
037
038
038
038
037
037
037
037
037
037
w/P.E.
(pwrd fr/unit)
037
037
037
038
038
037
037
038
038
038
037
037
038
038
038
037
037
037
037
037
037
- 208 / 230V / 460V / 575V
- Convenience outlet
- Full load amps
- Indoor fan motor
- 240V / 480V / 600V
- Power exhaust
- Powered convenience outlet
- Unpowered convenience outlet
513 31 3209 02
84
ELECTRIC HEAT − ELECTRICAL INFORMATION
(UNITS PRODUCED ON OR AFTER JULY 30, 2012)
Table 35 (cont.) − RAS091
1−STAGE COOLING 1−SPEED INDOOR FAN MOTOR
WITHOUT FACTORY INSTALLED NON−FUSED DISCONNECT
SINGLE POINT KIT PART NUMBER
CRSINGLEXXXXXX
NOM.
V-PH-Hz.
IFM
TYPE
STD
208/
230-3-60
MED
HIGH
STD
460-3-60
MED
HIGH
STD
575-3-60
MED
HIGH
LEGEND
APP PWR
C.O.
FLA
IFM
NOM PWR
P.E.
PWRD
UNPWRD
85
ELECTRIC HEATER PART
NUMBER
CRHEATERXXXXXX
117A00
110A00
111A00
112A00
112A00,117A00
117A00
110A00
111A00
112A00
112A00,117A00
117A00
110A00
111A00
112A00
112A00,117A00
116A00
113A00
114A00
115A00
114A00,116A00
116A00
113A00
114A00
115A00
114A00,116A00
116A00
113A00
114A00
115A00
114A00,116A00
118A00
119A00
118A00
119A00
118A00
119A00
NOM
PWR
(kW)
10.4
16.0
24.8
32.0
42.4
10.4
16.0
24.8
32.0
42.4
10.4
16.0
24.8
32.0
42.4
13.9
16.5
27.8
33.0
41.7
13.9
16.5
27.8
33.0
41.7
13.9
16.5
27.8
33.0
41.7
17.0
34.0
17.0
34.0
17.0
34.0
APP
PWR
(kW)
7.8/9.6
12.0/14.7
18.6/22.8
24.0/29.4
31.8/38.9
7.8/9.6
12.0/14.7
18.6/22.8
24.0/29.4
31.8/38.9
7.8/9.6
12.0/14.7
18.6/22.8
24.0/29.4
31.8/38.9
12.8
15.2
25.5
30.3
38.3
12.8
15.2
25.5
30.3
38.3
12.8
15.2
25.5
30.3
38.3
17.0
34.0
17.0
34.0
17.0
34.0
NO C.O. or UNPWRD C.O.
NO P.E.
042
042
043
043
045
042
042
043
043
045
042
043
043
043
045
042
042
042
042
044
042
042
042
042
044
042
042
042
042
044
042
042
042
042
042
042
w/P.E.
(pwrd fr/unit)
042
042
043
043
045
042
043
043
043
045
042
043
043
043
045
042
042
042
042
044
042
042
042
042
044
042
042
042
042
044
042
042
042
042
042
044
- 208 / 230V / 460V / 575V
- Convenience outlet
- Full load amps
- Indoor fan motor
- 240V / 480V / 600V
- Power exhaust
- Powered convenience outlet
- Unpowered convenience outlet
513 31 3209 02
ELECTRIC HEAT − ELECTRICAL INFORMATION
(UNITS PRODUCED ON OR AFTER JULY 30, 2012)
Table 35 (cont.) − RAS091
1−STAGE COOLING 1−SPEED INDOOR FAN MOTOR
WITH FACTORY INSTALLED NON−FUSED DISCONNECT
SINGLE POINT KIT PART NUMBER
CRSINGLEXXXXXX
NOM.
V-PH-Hz.
IFM
TYPE
STD
208/
230-3-60
MED
HIGH
STD
460-3-60
MED
HIGH
STD
575-3-60
MED
HIGH
LEGEND
APP PWR
C.O.
FLA
IFM
NOM PWR
P.E.
PWRD
UNPWRD
ELECTRIC HEATER PART
NUMBER
CRHEATERXXXXXX
117A00
110A00
111A00
112A00
112A00,117A00
117A00
110A00
111A00
112A00
112A00,117A00
117A00
110A00
111A00
112A00
112A00,117A00
116A00
113A00
114A00
115A00
114A00,116A00
116A00
113A00
114A00
115A00
114A00,116A00
116A00
113A00
114A00
115A00
114A00,116A00
118A00
119A00
118A00
119A00
118A00
119A00
NOM
PWR
(kW)
10.4
16.0
24.8
32.0
42.4
10.4
16.0
24.8
32.0
42.4
10.4
16.0
24.8
32.0
42.4
13.9
16.5
27.8
33.0
41.7
13.9
16.5
27.8
33.0
41.7
13.9
16.5
27.8
33.0
41.7
17.0
34.0
17.0
34.0
17.0
34.0
APP
PWR
(kW)
7.8/9.6
12.0/14.7
18.6/22.8
24.0/29.4
31.8/38.9
7.8/9.6
12.0/14.7
18.6/22.8
24.0/29.4
31.8/38.9
7.8/9.6
12.0/14.7
18.6/22.8
24.0/29.4
31.8/38.9
12.8
15.2
25.5
30.3
38.3
12.8
15.2
25.5
30.3
38.3
12.8
15.2
25.5
30.3
38.3
17.0
34.0
17.0
34.0
17.0
34.0
NO C.O. or UNPWRD C.O.
NO P.E.
042
042
043
043
045
042
042
043
043
045
042
043
043
043
045
042
042
042
042
044
042
042
042
042
044
042
042
042
042
044
042
042
042
042
042
042
w/P.E.
(pwrd fr/unit)
042
042
043
043
045
042
043
043
043
045
042
043
043
043
045
042
042
042
042
044
042
042
042
042
044
042
042
042
042
044
042
042
042
042
042
044
- 208 / 230V / 460V / 575V
- Convenience outlet
- Full load amps
- Indoor fan motor
- 240V / 480V / 600V
- Power exhaust
- Powered convenience outlet
- Unpowered convenience outlet
513 31 3209 02
86
ELECTRIC HEAT − ELECTRICAL INFORMATION
(UNITS PRODUCED ON OR AFTER JULY 30, 2012)
Table 35 (cont.) − RAS090
2−STAGE COOLING 1−SPEED INDOOR FAN MOTOR
WITHOUT FACTORY INSTALLED NON−FUSED DISCONNECT
SINGLE POINT KIT PART NUMBER
CRSINGLEXXXXXX
NOM.
V-PH-Hz.
IFM
TYPE
STD
208/
230-3-60
MED
HIGH
STD
460-3-60
MED
HIGH
STD
575-3-60
MED
HIGH
LEGEND
APP PWR
C.O.
FLA
IFM
NOM PWR
P.E.
PWRD
UNPWRD
87
ELECTRIC HEATER PART
NUMBER
CRHEATERXXXXXX
117A00
110A00
111A00
112A00
112A00,117A00
117A00
110A00
111A00
112A00
112A00,117A00
117A00
110A00
111A00
112A00
112A00,117A00
116A00
113A00
114A00
115A00
114A00,116A00
116A00
113A00
114A00
115A00
114A00,116A00
116A00
113A00
114A00
115A00
114A00,116A00
118A00
119A00
118A00
119A00
118A00
119A00
NOM
PWR
(kW)
10.4
16.0
24.8
32.0
42.4
10.4
16.0
24.8
32.0
42.4
10.4
16.0
24.8
32.0
42.4
13.9
16.5
27.8
33.0
41.7
13.9
16.5
27.8
33.0
41.7
13.9
16.5
27.8
33.0
41.7
17.0
34.0
17.0
34.0
17.0
34.0
APP
PWR
(kW)
7.8/9.6
12.0/14.7
18.6/22.8
24.0/29.4
31.8/38.9
7.8/9.6
12.0/14.7
18.6/22.8
24.0/29.4
31.8/38.9
7.8/9.6
12.0/14.7
18.6/22.8
24.0/29.4
31.8/38.9
12.8
15.2
25.5
30.3
38.3
12.8
15.2
25.5
30.3
38.3
12.8
15.2
25.5
30.3
38.3
17.0
34.0
17.0
34.0
17.0
34.0
NO C.O. or UNPWRD C.O.
NO P.E.
042
042
043
043
045
042
042
043
043
045
042
043
043
043
045
042
042
042
042
044
042
042
042
042
044
042
042
042
042
044
042
042
042
042
042
042
w/P.E.
(pwrd fr/unit)
042
042
043
043
045
042
043
043
043
045
042
043
043
043
045
042
042
042
042
044
042
042
042
042
044
042
042
042
042
044
042
042
042
042
042
044
- 208 / 230V / 460V / 575V
- Convenience outlet
- Full load amps
- Indoor fan motor
- 240V / 480V / 600V
- Power exhaust
- Powered convenience outlet
- Unpowered convenience outlet
513 31 3209 02
ELECTRIC HEAT − ELECTRICAL INFORMATION
(UNITS PRODUCED ON OR AFTER JULY 30, 2012)
Table 35 (cont.) − RAS090
2−STAGE COOLING 1−SPEED INDOOR FAN MOTOR
WITH FACTORY INSTALLED NON−FUSED DISCONNECT
SINGLE POINT KIT PART NUMBER
CRSINGLEXXXXXX
NOM.
V-PH-Hz.
IFM
TYPE
STD
208/
230-3-60
MED
HIGH
STD
460-3-60
MED
HIGH
STD
575-3-60
MED
HIGH
LEGEND
APP PWR
C.O.
FLA
IFM
NOM PWR
P.E.
PWRD
UNPWRD
ELECTRIC HEATER PART
NUMBER
CRHEATERXXXXXX
117A00
110A00
111A00
112A00
112A00,117A00
117A00
110A00
111A00
112A00
112A00,117A00
117A00
110A00
111A00
112A00
112A00,117A00
116A00
113A00
114A00
115A00
114A00,116A00
116A00
113A00
114A00
115A00
114A00,116A00
116A00
113A00
114A00
115A00
114A00,116A00
118A00
119A00
118A00
119A00
118A00
119A00
NOM
PWR
(kW)
10.4
16.0
24.8
32.0
42.4
10.4
16.0
24.8
32.0
42.4
10.4
16.0
24.8
32.0
42.4
13.9
16.5
27.8
33.0
41.7
13.9
16.5
27.8
33.0
41.7
13.9
16.5
27.8
33.0
41.7
17.0
34.0
17.0
34.0
17.0
34.0
APP
PWR
(kW)
7.8/9.6
12.0/14.7
18.6/22.8
24.0/29.4
31.8/38.9
7.8/9.6
12.0/14.7
18.6/22.8
24.0/29.4
31.8/38.9
7.8/9.6
12.0/14.7
18.6/22.8
24.0/29.4
31.8/38.9
12.8
15.2
25.5
30.3
38.3
12.8
15.2
25.5
30.3
38.3
12.8
15.2
25.5
30.3
38.3
17.0
34.0
17.0
34.0
17.0
34.0
NO C.O. or UNPWRD C.O.
NO P.E.
042
042
043
043
045
042
042
043
043
045
042
043
043
043
045
042
042
042
042
044
042
042
042
042
044
042
042
042
042
044
042
042
042
042
042
042
w/P.E.
(pwrd fr/unit)
042
042
043
043
045
042
043
043
043
045
042
043
043
043
045
042
042
042
042
044
042
042
042
042
044
042
042
042
042
044
042
042
042
042
042
044
- 208 / 230V / 460V / 575V
- Convenience outlet
- Full load amps
- Indoor fan motor
- 240V / 480V / 600V
- Power exhaust
- Powered convenience outlet
- Unpowered convenience outlet
513 31 3209 02
88
ELECTRIC HEAT − ELECTRICAL INFORMATION
(UNITS PRODUCED ON OR AFTER JULY 30, 2012)
Table 35 (cont.) − RAS090
2−STAGE COOLING 2−SPEED INDOOR FAN MOTOR
WITHOUT FACTORY INSTALLED NON−FUSED DISCONNECT
SINGLE POINT KIT PART NUMBER
CRSINGLEXXXXXX
NOM.
V-PH-Hz.
IFM
TYPE
STD
208/
230-3-60
MED
HIGH
STD
460-3-60
MED
HIGH
STD
575-3-60
MED
HIGH
LEGEND
APP PWR
C.O.
FLA
IFM
NOM PWR
P.E.
PWRD
UNPWRD
89
ELECTRIC HEATER PART
NUMBER
CRHEATERXXXXXX
117A00
110A00
111A00
112A00
112A00,117A00
117A00
110A00
111A00
112A00
112A00,117A00
117A00
110A00
111A00
112A00
112A00,117A00
116A00
113A00
114A00
115A00
114A00,116A00
116A00
113A00
114A00
115A00
114A00,116A00
116A00
113A00
114A00
115A00
114A00,116A00
118A00
119A00
118A00
119A00
118A00
119A00
NOM
PWR
(kW)
10.4
16.0
24.8
32.0
42.4
10.4
16.0
24.8
32.0
42.4
10.4
16.0
24.8
32.0
42.4
13.9
16.5
27.8
33.0
41.7
13.9
16.5
27.8
33.0
41.7
13.9
16.5
27.8
33.0
41.7
17.0
34.0
17.0
34.0
17.0
34.0
APP
PWR
(kW)
7.8/9.6
12.0/14.7
18.6/22.8
24.0/29.4
31.8/38.9
7.8/9.6
12.0/14.7
18.6/22.8
24.0/29.4
31.8/38.9
7.8/9.6
12.0/14.7
18.6/22.8
24.0/29.4
31.8/38.9
12.8
15.2
25.5
30.3
38.3
12.8
15.2
25.5
30.3
38.3
12.8
15.2
25.5
30.3
38.3
17.0
34.0
17.0
34.0
17.0
34.0
NO C.O. or UNPWRD C.O.
NO P.E.
042
042
043
043
045
042
042
043
043
045
042
043
043
043
045
042
042
042
042
044
042
042
042
042
044
042
042
042
042
044
042
042
042
042
042
042
w/P.E.
(pwrd fr/unit)
042
042
043
043
045
042
043
043
043
045
042
043
043
043
045
042
042
042
042
044
042
042
042
042
044
042
042
042
042
044
042
042
042
044
042
044
- 208 / 230V / 460V / 575V
- Convenience outlet
- Full load amps
- Indoor fan motor
- 240V / 480V / 600V
- Power exhaust
- Powered convenience outlet
- Unpowered convenience outlet
513 31 3209 02
ELECTRIC HEAT − ELECTRICAL INFORMATION
(UNITS PRODUCED ON OR AFTER JULY 30, 2012)
Table 35 (cont.) − RAS101
1−STAGE COOLING 1−SPEED INDOOR FAN MOTOR
WITHOUT FACTORY INSTALLED NON−FUSED DISCONNECT
SINGLE POINT KIT PART NUMBER
CRSINGLEXXXXXX
NOM.
V-PH-Hz.
IFM
TYPE
STD
208/
203-3-60
MED
HIGH
STD
460-3-60
MED
HIGH
STD
575-3-60
MED
HIGH
LEGEND
APP PWR
C.O.
FLA
IFM
NOM PWR
P.E.
PWRD
UNPWRD
ELECTRIC HEATER PART
NUMBER
CRHEATERXXXXXX
117A00
110A00
111A00
112A00
112A00,117A00
117A00
110A00
111A00
112A00
112A00,117A00
117A00
110A00
111A00
112A00
112A00,117A00
116A00
113A00
114A00
115A00
114A00,116A00
116A00
113A00
114A00
115A00
114A00,116A00
116A00
113A00
114A00
115A00
114A00,116A00
118A00
119A00
118A00
119A00
118A00
119A00
NOM
PWR
(kW)
10.4
16.0
24.8
32.0
42.4
10.4
16.0
24.8
32.0
42.4
10.4
16.0
24.8
32.0
42.4
13.9
16.5
27.8
33.0
41.7
13.9
16.5
27.8
33.0
41.7
13.9
16.5
27.8
33.0
41.7
17.0
34.0
17.0
34.0
17.0
34.0
APP
PWR
(kW)
7.8/9.6
12.0/14.7
18.6/22.8
24.0/29.4
31.8/38.9
7.8/9.6
12.0/14.7
18.6/22.8
24.0/29.4
31.8/38.9
7.8/9.6
12.0/14.7
18.6/22.8
24.0/29.4
31.8/38.9
12.8
15.2
25.5
30.3
38.3
12.8
15.2
25.5
30.3
38.3
12.8
15.2
25.5
30.3
38.3
17.0
34.0
17.0
34.0
17.0
34.0
NO C.O. or UNPWRD C.O.
NO P.E.
047
047
049
049
051
047
047
049
049
051
047
049
049
049
051
047
047
047
047
050
047
047
047
047
050
047
047
047
047
050
047
047
047
047
047
047
w/P.E.
(pwrd fr/unit)
047
047
049
049
051
047
049
049
049
051
049
049
049
049
051
047
047
047
047
050
047
047
047
047
050
047
047
047
047
050
047
047
047
047
047
047
- 208 / 230V / 460V / 575V
- Convenience outlet
- Full load amps
- Indoor fan motor
- 240V / 480V / 600V
- Power exhaust
- Powered convenience outlet
- Unpowered convenience outlet
513 31 3209 02
90
ELECTRIC HEAT − ELECTRICAL INFORMATION
(UNITS PRODUCED ON OR AFTER JULY 30, 2012)
Table 35 (cont.) − RAS101
1−STAGE COOLING 1−SPEED INDOOR FAN MOTOR
WITH FACTORY INSTALLED NON−FUSED DISCONNECT
SINGLE POINT KIT PART NUMBER
CRSINGLEXXXXXX
NOM.
V-PH-Hz.
IFM
TYPE
STD
208/
203-3-60
MED
HIGH
STD
460-3-60
MED
HIGH
STD
575-3-60
MED
HIGH
LEGEND
APP PWR
C.O.
FLA
IFM
NOM PWR
P.E.
PWRD
UNPWRD
91
ELECTRIC HEATER PART
NUMBER
CRHEATERXXXXXX
117A00
110A00
111A00
112A00
112A00,117A00
117A00
110A00
111A00
112A00
112A00,117A00
117A00
110A00
111A00
112A00
112A00,117A00
116A00
113A00
114A00
115A00
114A00,116A00
116A00
113A00
114A00
115A00
114A00,116A00
116A00
113A00
114A00
115A00
114A00,116A00
118A00
119A00
118A00
119A00
118A00
119A00
NOM
PWR
(kW)
10.4
16.0
24.8
32.0
42.4
10.4
16.0
24.8
32.0
42.4
10.4
16.0
24.8
32.0
42.4
13.9
16.5
27.8
33.0
41.7
13.9
16.5
27.8
33.0
41.7
13.9
16.5
27.8
33.0
41.7
17.0
34.0
17.0
34.0
17.0
34.0
APP
PWR
(kW)
7.8/9.6
12.0/14.7
18.6/22.8
24.0/29.4
31.8/38.9
7.8/9.6
12.0/14.7
18.6/22.8
24.0/29.4
31.8/38.9
7.8/9.6
12.0/14.7
18.6/22.8
24.0/29.4
31.8/38.9
12.8
15.2
25.5
30.3
38.3
12.8
15.2
25.5
30.3
38.3
12.8
15.2
25.5
30.3
38.3
17.0
34.0
17.0
34.0
17.0
34.0
NO C.O. or UNPWRD C.O.
NO P.E.
047
047
049
049
051
047
047
049
049
051
047
049
049
049
051
047
047
047
047
050
047
047
047
047
050
047
047
047
047
050
047
047
047
047
047
047
w/P.E.
(pwrd fr/unit)
047
047
049
049
051
047
049
049
049
051
049
049
049
049
051
047
047
047
047
050
047
047
047
047
050
047
047
047
047
050
047
047
047
047
047
047
- 208 / 230V / 460V / 575V
- Convenience outlet
- Full load amps
- Indoor fan motor
- 240V / 480V / 600V
- Power exhaust
- Powered convenience outlet
- Unpowered convenience outlet
513 31 3209 02
ELECTRIC HEAT − ELECTRICAL INFORMATION
(UNITS PRODUCED ON OR AFTER JULY 30, 2012)
Table 35 (cont.) − RAS102
2−STAGE COOLING 1−SPEED INDOOR FAN MOTOR
WITHOUT FACTORY INSTALLED NON−FUSED DISCONNECT
SINGLE POINT KIT PART NUMBER
CRSINGLEXXXXXX
NOM.
V-PH-Hz.
IFM
TYPE
STD
208/
203-3-60
MED
HIGH
STD
460-3-60
MED
HIGH
STD
575-3-60
MED
HIGH
LEGEND
APP PWR
C.O.
FLA
IFM
NOM PWR
P.E.
PWRD
UNPWRD
ELECTRIC HEATER PART
NUMBER
CRHEATERXXXXXX
117A00
110A00
111A00
112A00
112A00,117A00
117A00
110A00
111A00
112A00
112A00,117A00
117A00
110A00
111A00
112A00
112A00,117A00
116A00
113A00
114A00
115A00
114A00,116A00
116A00
113A00
114A00
115A00
114A00,116A00
116A00
113A00
114A00
115A00
114A00,116A00
118A00
119A00
118A00
119A00
118A00
119A00
NOM
PWR
(kW)
10.4
16.0
24.8
32.0
42.4
10.4
16.0
24.8
32.0
42.4
10.4
16.0
24.8
32.0
42.4
13.9
16.5
27.8
33.0
41.7
13.9
16.5
27.8
33.0
41.7
13.9
16.5
27.8
33.0
41.7
17.0
34.0
17.0
34.0
17.0
34.0
APP
PWR
(kW)
7.8/9.6
12.0/14.7
18.6/22.8
24.0/29.4
31.8/38.9
7.8/9.6
12.0/14.7
18.6/22.8
24.0/29.4
31.8/38.9
7.8/9.6
12.0/14.7
18.6/22.8
24.0/29.4
31.8/38.9
12.8
15.2
25.5
30.3
38.3
12.8
15.2
25.5
30.3
38.3
12.8
15.2
25.5
30.3
38.3
17.0
34.0
17.0
34.0
17.0
34.0
NO C.O. or UNPWRD C.O.
NO P.E.
047
047
049
049
051
047
047
049
049
051
047
049
049
049
051
047
047
047
047
050
047
047
047
047
050
047
047
047
047
050
047
047
047
047
047
047
w/P.E.
(pwrd fr/unit)
047
047
049
049
051
047
049
049
049
051
047
049
049
049
051
047
047
047
047
050
047
047
047
047
050
047
047
047
047
050
047
047
047
047
047
047
- 208 / 230V / 460V / 575V
- Convenience outlet
- Full load amps
- Indoor fan motor
- 240V / 480V / 600V
- Power exhaust
- Powered convenience outlet
- Unpowered convenience outlet
513 31 3209 02
92
ELECTRIC HEAT − ELECTRICAL INFORMATION
(UNITS PRODUCED ON OR AFTER JULY 30, 2012)
Table 35 (cont.) − RAS102
2−STAGE COOLING 1−SPEED INDOOR FAN MOTOR
WITH FACTORY INSTALLED NON−FUSED DISCONNECT
SINGLE POINT KIT PART NUMBER
CRSINGLEXXXXXX
NOM.
V-PH-Hz.
IFM
TYPE
STD
208/
203-3-60
MED
HIGH
STD
460-3-60
MED
HIGH
STD
575-3-60
MED
HIGH
LEGEND
APP PWR
C.O.
FLA
IFM
NOM PWR
P.E.
PWRD
UNPWRD
93
ELECTRIC HEATER PART
NUMBER
CRHEATERXXXXXX
117A00
110A00
111A00
112A00
112A00,117A00
117A00
110A00
111A00
112A00
112A00,117A00
117A00
110A00
111A00
112A00
112A00,117A00
116A00
113A00
114A00
115A00
114A00,116A00
116A00
113A00
114A00
115A00
114A00,116A00
116A00
113A00
114A00
115A00
114A00,116A00
118A00
119A00
118A00
119A00
118A00
119A00
NOM
PWR
(kW)
10.4
16.0
24.8
32.0
42.4
10.4
16.0
24.8
32.0
42.4
10.4
16.0
24.8
32.0
42.4
13.9
16.5
27.8
33.0
41.7
13.9
16.5
27.8
33.0
41.7
13.9
16.5
27.8
33.0
41.7
17.0
34.0
17.0
34.0
17.0
34.0
APP
PWR
(kW)
7.8/9.6
12.0/14.7
18.6/22.8
24.0/29.4
31.8/38.9
7.8/9.6
12.0/14.7
18.6/22.8
24.0/29.4
31.8/38.9
7.8/9.6
12.0/14.7
18.6/22.8
24.0/29.4
31.8/38.9
12.8
15.2
25.5
30.3
38.3
12.8
15.2
25.5
30.3
38.3
12.8
15.2
25.5
30.3
38.3
17.0
34.0
17.0
34.0
17.0
34.0
NO C.O. or UNPWRD C.O.
NO P.E.
047
047
049
049
051
047
047
049
049
051
047
049
049
049
051
047
047
047
047
050
047
047
047
047
050
047
047
047
047
050
047
047
047
047
047
047
w/P.E.
(pwrd fr/unit)
047
047
049
049
051
047
049
049
049
051
047
049
049
049
051
047
047
047
047
050
047
047
047
047
050
047
047
047
047
050
047
047
047
047
047
047
- 208 / 230V / 460V / 575V
- Convenience outlet
- Full load amps
- Indoor fan motor
- 240V / 480V / 600V
- Power exhaust
- Powered convenience outlet
- Unpowered convenience outlet
513 31 3209 02
ELECTRIC HEAT − ELECTRICAL INFORMATION
(UNITS PRODUCED ON OR AFTER JULY 30, 2012)
Table 35 (cont.) − RAS102
2−STAGE COOLING 2−SPEED INDOOR FAN MOTOR
WITHOUT FACTORY INSTALLED NON−FUSED DISCONNECT
SINGLE POINT KIT PART NUMBER
CRSINGLEXXXXXX
NOM.
V-PH-Hz.
IFM
TYPE
STD
208/
203-3-60
MED
HIGH
STD
460-3-60
MED
HIGH
STD
575-3-60
MED
HIGH
LEGEND
APP PWR
C.O.
FLA
IFM
NOM PWR
P.E.
PWRD
UNPWRD
ELECTRIC HEATER PART
NUMBER
CRHEATERXXXXXX
117A00
110A00
111A00
112A00
112A00,117A00
117A00
110A00
111A00
112A00
112A00,117A00
117A00
110A00
111A00
112A00
112A00,117A00
116A00
113A00
114A00
115A00
114A00,116A00
116A00
113A00
114A00
115A00
114A00,116A00
116A00
113A00
114A00
115A00
114A00,116A00
118A00
119A00
118A00
119A00
118A00
119A00
NOM
PWR
(kW)
10.4
16.0
24.8
32.0
42.4
10.4
16.0
24.8
32.0
42.4
10.4
16.0
24.8
32.0
42.4
13.9
16.5
27.8
33.0
41.7
13.9
16.5
27.8
33.0
41.7
13.9
16.5
27.8
33.0
41.7
17.0
34.0
17.0
34.0
17.0
34.0
APP
PWR
(kW)
7.8/9.6
12.0/14.7
18.6/22.8
24.0/29.4
31.8/38.9
7.8/9.6
12.0/14.7
18.6/22.8
24.0/29.4
31.8/38.9
7.8/9.6
12.0/14.7
18.6/22.8
24.0/29.4
31.8/38.9
12.8
15.2
25.5
30.3
38.3
12.8
15.2
25.5
30.3
38.3
12.8
15.2
25.5
30.3
38.3
17.0
34.0
17.0
34.0
17.0
34.0
NO C.O. or UNPWRD C.O.
NO P.E.
047
047
049
049
051
047
047
049
049
051
047
049
049
049
051
047
047
047
047
050
047
047
047
047
050
047
047
047
047
050
047
047
047
047
047
047
w/P.E.
(pwrd fr/unit)
047
047
049
049
051
047
049
049
049
051
047
049
049
049
051
047
047
047
047
050
047
047
047
047
050
047
047
047
047
050
047
047
047
050
047
050
- 208 / 230V / 460V / 575V
- Convenience outlet
- Full load amps
- Indoor fan motor
- 240V / 480V / 600V
- Power exhaust
- Powered convenience outlet
- Unpowered convenience outlet
513 31 3209 02
94
ELECTRIC HEAT − ELECTRICAL INFORMATION
(UNITS PRODUCED ON OR AFTER JULY 30, 2012)
Table 35 (cont.) − RAS121
1−STAGE COOLING 1−SPEED INDOOR FAN MOTOR
WITHOUT FACTORY INSTALLED NON−FUSED DISCONNECT
SINGLE POINT KIT PART NUMBER
CRSINGLEXXXXXX
NOM.
V-PH-Hz.
IFM
TYPE
STD
208/
230-3-60
MED
HIGH
STD
460-3-60
MED
HIGH
STD
575-3-60
MED
HIGH
LEGEND
APP PWR
C.O.
FLA
IFM
NOM PWR
P.E.
PWRD
UNPWRD
95
ELECTRIC HEATER PART
NUMBER
CRHEATERXXXXXX
117A00
110A00
112A00
112A00,117A00
112A00,110A00
117A00
110A00
112A00
112A00,117A00
112A00,110A00
117A00
110A00
112A00
112A00,117A00
112A00,110A00
116A00
113A00
115A00
114A00,116A00
115A00,113A00
116A00
113A00
115A00
114A00,116A00
115A00,113A00
116A00
113A00
115A00
114A00,116A00
115A00,113A00
118A00
119A00
118A00,119A00
118A00
119A00
118A00,119A00
118A00
119A00
118A00,119A00
NOM
PWR
(kW)
10.4
16.0
32.0
42.4
50.0
10.4
16.0
32.0
42.4
50.0
10.4
16.0
32.0
42.4
50.0
13.9
16.5
33.0
41.7
50.0
13.9
16.5
33.0
41.7
50.0
13.9
16.5
33.0
41.7
50.0
17.0
34.0
51.0
17.0
34.0
51.0
17.0
34.0
51.0
APP
PWR
(kW)
7.8/9.6
12.0/14.7
24.0/29.4
31.8/38.9
37.6/45.9
7.8/9.6
12.0/14.7
24.0/29.4
31.8/38.9
37.6/45.9
7.8/9.6
12.0/14.7
24.0/29.4
31.8/38.9
37.6/45.9
12.8
15.2
30.3
38.3
45.9
12.8
15.2
30.3
38.3
45.9
12.8
15.2
30.3
38.3
45.9
17.0
34.0
51.0
17.0
34.0
51.0
17.0
34.0
51.0
NO C.O. or UNPWRD C.O.
NO P.E.
047
047
049
051
051
047
049
049
051
051
049
049
049
051
051
047
047
047
050
050
047
047
047
050
050
047
047
047
050
050
047
047
050
047
047
050
047
047
050
w/P.E.
(pwrd fr/unit)
047
049
049
051
051
049
049
049
051
051
049
049
049
051
051
047
047
047
050
050
047
047
047
050
050
047
047
047
050
050
047
047
050
047
047
050
047
050
050
- 208 / 230V / 460V / 575V
- Convenience outlet
- Full load amps
- Indoor fan motor
- 240V / 480V / 600V
- Power exhaust
- Powered convenience outlet
- Unpowered convenience outlet
513 31 3209 02
ELECTRIC HEAT − ELECTRICAL INFORMATION
(UNITS PRODUCED ON OR AFTER JULY 30, 2012)
Table 35 (cont.) −RAS121
1−STAGE COOLING 1−SPEED INDOOR FAN MOTOR
WITH FACTORY INSTALLED NON−FUSED DISCONNECT
SINGLE POINT KIT PART NUMBER
CRSINGLEXXXXXX
NOM.
V-PH-Hz.
IFM
TYPE
STD
208/
230-3-60
MED
HIGH
STD
460-3-60
MED
HIGH
STD
575-3-60
MED
HIGH
LEGEND
APP PWR
C.O.
FLA
IFM
NOM PWR
P.E.
PWRD
UNPWRD
ELECTRIC HEATER PART
NUMBER
CRHEATERXXXXXX
117A00
110A00
112A00
112A00,117A00
112A00,110A00
117A00
110A00
112A00
112A00,117A00
112A00,110A00
117A00
110A00
112A00
112A00,117A00
112A00,110A00
116A00
113A00
115A00
114A00,116A00
115A00,113A00
116A00
113A00
115A00
114A00,116A00
115A00,113A00
116A00
113A00
115A00
114A00,116A00
115A00,113A00
118A00
119A00
118A00,119A00
118A00
119A00
118A00,119A00
118A00
119A00
118A00,119A00
NOM
PWR
(kW)
10.4
16.0
32.0
42.4
50.0
10.4
16.0
32.0
42.4
50.0
10.4
16.0
32.0
42.4
50.0
13.9
16.5
33.0
41.7
50.0
13.9
16.5
33.0
41.7
50.0
13.9
16.5
33.0
41.7
50.0
17.0
34.0
51.0
17.0
34.0
51.0
17.0
34.0
51.0
APP
PWR
(kW)
7.8/9.6
12.0/14.7
24.0/29.4
31.8/38.9
37.6/45.9
7.8/9.6
12.0/14.7
24.0/29.4
31.8/38.9
37.6/45.9
7.8/9.6
12.0/14.7
24.0/29.4
31.8/38.9
37.6/45.9
12.8
15.2
30.3
38.3
45.9
12.8
15.2
30.3
38.3
45.9
12.8
15.2
30.3
38.3
45.9
17.0
34.0
51.0
17.0
34.0
51.0
17.0
34.0
51.0
NO C.O. or UNPWRD C.O.
NO P.E.
047
047
049
051
051
047
049
049
051
051
049
049
049
051
051
047
047
047
050
050
047
047
047
050
050
047
047
047
050
050
047
047
050
047
047
050
047
047
050
w/P.E.
(pwrd fr/unit)
047
049
049
051
051
049
049
049
051
051
049
049
049
051
051
047
047
047
050
050
047
047
047
050
050
047
047
047
050
050
047
047
050
047
047
050
047
050
050
- 208 / 230V / 460V / 575V
- Convenience outlet
- Full load amps
- Indoor fan motor
- 240V / 480V / 600V
- Power exhaust
- Powered convenience outlet
- Unpowered convenience outlet
513 31 3209 02
96
ELECTRIC HEAT − ELECTRICAL INFORMATION
(UNITS PRODUCED ON OR AFTER JULY 30, 2012)
Table 35 (cont.) − RAS120
2−STAGE COOLING 1−SPEED INDOOR FAN MOTOR
WITHOUT FACTORY INSTALLED NON−FUSED DISCONNECT
SINGLE POINT KIT PART NUMBER
CRSINGLEXXXXXX
NOM.
V-PH-Hz.
IFM
TYPE
STD
208/
230-3-60
MED
HIGH
STD
460-3-60
MED
HIGH
STD
575-3-60
MED
HIGH
LEGEND
APP PWR
C.O.
FLA
IFM
NOM PWR
P.E.
PWRD
UNPWRD
97
ELECTRIC HEATER PART
NUMBER
CRHEATERXXXXXX
117A00
110A00
112A00
112A00,117A00
112A00,110A00
117A00
110A00
112A00
112A00,117A00
112A00,110A00
117A00
110A00
112A00
112A00,117A00
112A00,110A00
116A00
113A00
115A00
114A00,116A00
115A00,113A00
116A00
113A00
115A00
114A00,116A00
115A00,113A00
116A00
113A00
115A00
114A00,116A00
115A00,113A00
118A00
119A00
118A00,119A00
118A00
119A00
118A00,119A00
118A00
119A00
118A00,119A00
NOM
PWR
(kW)
10.4
16.0
32.0
42.4
50.0
10.4
16.0
32.0
42.4
50.0
10.4
16.0
32.0
42.4
50.0
13.9
16.5
33.0
41.7
50.0
13.9
16.5
33.0
41.7
50.0
13.9
16.5
33.0
41.7
50.0
17.0
34.0
51.0
17.0
34.0
51.0
17.0
34.0
51.0
APP
PWR
(kW)
7.8/9.6
12.0/14.7
24.0/29.4
31.8/38.9
37.6/45.9
7.8/9.6
12.0/14.7
24.0/29.4
31.8/38.9
37.6/45.9
7.8/9.6
12.0/14.7
24.0/29.4
31.8/38.9
37.6/45.9
12.8
15.2
30.3
38.3
45.9
12.8
15.2
30.3
38.3
45.9
12.8
15.2
30.3
38.3
45.9
17.0
34.0
51.0
17.0
34.0
51.0
17.0
34.0
51.0
NO C.O. or UNPWRD C.O.
NO P.E.
047
047
049
051
051
047
049
049
051
051
047
049
049
051
051
047
047
047
050
050
047
047
047
050
050
047
047
047
050
050
047
047
050
047
047
050
047
047
050
w/P.E.
(pwrd fr/unit)
047
049
049
051
051
047
049
049
051
051
047
049
049
051
051
047
047
047
050
050
047
047
047
050
050
047
047
047
050
050
047
047
050
047
047
050
047
050
050
- 208 / 230V / 460V / 575V
- Convenience outlet
- Full load amps
- Indoor fan motor
- 240V / 480V / 600V
- Power exhaust
- Powered convenience outlet
- Unpowered convenience outlet
513 31 3209 02
ELECTRIC HEAT − ELECTRICAL INFORMATION
(UNITS PRODUCED ON OR AFTER JULY 30, 2012)
Table 35 (cont.) − RAS120
2−STAGE COOLING 1−SPEED INDOOR FAN MOTOR
WITH FACTORY INSTALLED NON−FUSED DISCONNECT
SINGLE POINT KIT PART NUMBER
CRSINGLEXXXXXX
NOM.
V-PH-Hz.
IFM
TYPE
STD
208/
230-3-60
MED
HIGH
STD
460-3-60
MED
HIGH
STD
575-3-60
MED
HIGH
LEGEND
APP PWR
C.O.
FLA
IFM
NOM PWR
P.E.
PWRD
UNPWRD
ELECTRIC HEATER PART
NUMBER
CRHEATERXXXXXX
117A00
110A00
112A00
112A00,117A00
112A00,110A00
117A00
110A00
112A00
112A00,117A00
112A00,110A00
117A00
110A00
112A00
112A00,117A00
112A00,110A00
116A00
113A00
115A00
114A00,116A00
115A00,113A00
116A00
113A00
115A00
114A00,116A00
115A00,113A00
116A00
113A00
115A00
114A00,116A00
115A00,113A00
118A00
119A00
118A00,119A00
118A00
119A00
118A00,119A00
118A00
119A00
118A00,119A00
NOM
PWR
(kW)
10.4
16.0
32.0
42.4
50.0
10.4
16.0
32.0
42.4
50.0
10.4
16.0
32.0
42.4
50.0
13.9
16.5
33.0
41.7
50.0
13.9
16.5
33.0
41.7
50.0
13.9
16.5
33.0
41.7
50.0
17.0
34.0
51.0
17.0
34.0
51.0
17.0
34.0
51.0
APP
PWR
(kW)
7.8/9.6
12.0/14.7
24.0/29.4
31.8/38.9
37.6/45.9
7.8/9.6
12.0/14.7
24.0/29.4
31.8/38.9
37.6/45.9
7.8/9.6
12.0/14.7
24.0/29.4
31.8/38.9
37.6/45.9
12.8
15.2
30.3
38.3
45.9
12.8
15.2
30.3
38.3
45.9
12.8
15.2
30.3
38.3
45.9
17.0
34.0
51.0
17.0
34.0
51.0
17.0
34.0
51.0
NO C.O. or UNPWRD C.O.
NO P.E.
047
047
049
051
051
047
049
049
051
051
047
049
049
051
051
047
047
047
050
050
047
047
047
050
050
047
047
047
050
050
047
047
050
047
047
050
047
047
050
w/P.E.
(pwrd fr/unit)
047
049
049
051
051
047
049
049
051
051
047
049
049
051
051
047
047
047
050
050
047
047
047
050
050
047
047
047
050
050
047
047
050
047
047
050
047
050
050
- 208 / 230V / 460V / 575V
- Convenience outlet
- Full load amps
- Indoor fan motor
- 240V / 480V / 600V
- Power exhaust
- Powered convenience outlet
- Unpowered convenience outlet
513 31 3209 02
98
ELECTRIC HEAT − ELECTRICAL INFORMATION
(UNITS PRODUCED ON OR AFTER JULY 30, 2012)
Table 35 (cont.) − RAS120
2−STAGE COOLING 2−SPEED INDOOR FAN MOTOR
WITHOUT FACTORY INSTALLED NON−FUSED DISCONNECT
SINGLE POINT KIT PART NUMBER
CRSINGLEXXXXXX
NOM.
V-PH-Hz.
IFM
TYPE
STD
208/
230-3-60
MED
HIGH
STD
460-3-60
MED
HIGH
STD
575-3-60
MED
HIGH
LEGEND
APP PWR
C.O.
FLA
IFM
NOM PWR
P.E.
PWRD
UNPWRD
99
ELECTRIC HEATER PART
NUMBER
CRHEATERXXXXXX
117A00
110A00
112A00
112A00,117A00
112A00,110A00
117A00
110A00
112A00
112A00,117A00
112A00,110A00
117A00
110A00
112A00
112A00,117A00
112A00,110A00
116A00
113A00
115A00
114A00,116A00
115A00,113A00
116A00
113A00
115A00
114A00,116A00
115A00,113A00
116A00
113A00
115A00
114A00,116A00
115A00,113A00
118A00
119A00
118A00,119A00
118A00
119A00
118A00,119A00
118A00
119A00
118A00,119A00
NOM
PWR
(kW)
10.4
16.0
32.0
42.4
50.0
10.4
16.0
32.0
42.4
50.0
10.4
16.0
32.0
42.4
50.0
13.9
16.5
33.0
41.7
50.0
13.9
16.5
33.0
41.7
50.0
13.9
16.5
33.0
41.7
50.0
17.0
34.0
51.0
17.0
34.0
51.0
17.0
34.0
51.0
APP
PWR
(kW)
7.8/9.6
12.0/14.7
24.0/29.4
31.8/38.9
37.6/45.9
7.8/9.6
12.0/14.7
24.0/29.4
31.8/38.9
37.6/45.9
7.8/9.6
12.0/14.7
24.0/29.4
31.8/38.9
37.6/45.9
12.8
15.2
30.3
38.3
45.9
12.8
15.2
30.3
38.3
45.9
12.8
15.2
30.3
38.3
45.9
17.0
34.0
51.0
17.0
34.0
51.0
17.0
34.0
51.0
NO C.O. or UNPWRD C.O.
NO P.E.
047
047
049
051
051
047
049
049
051
051
047
049
049
051
051
047
047
047
050
050
047
047
047
050
050
047
047
047
050
050
047
047
050
047
047
050
047
047
050
w/P.E.
(pwrd fr/unit)
047
049
049
051
051
047
049
049
051
051
047
049
049
051
051
047
047
047
050
050
047
047
047
050
050
047
047
047
050
050
047
050
050
047
050
050
047
050
050
- 208 / 230V / 460V / 575V
- Convenience outlet
- Full load amps
- Indoor fan motor
- 240V / 480V / 600V
- Power exhaust
- Powered convenience outlet
- Unpowered convenience outlet
513 31 3209 02
ELECTRIC HEAT − ELECTRICAL INFORMATION
(UNITS PRODUCED ON OR AFTER JULY 30, 2012)
Table 35 (cont.) − RAS150
2−STAGE COOLING 1−SPEED INDOOR FAN MOTOR
WITHOUT FACTORY INSTALLED NON−FUSED DISCONNECT
SINGLE POINT KIT PART NUMBER
CRSINGLEXXXXXX
NOM.
V-PH-Hz.
IFM
TYPE
STD
208/
230-3-60
MED
HIGH
STD
460-3-60
MED
HIGH
STD
575-3-60
MED
HIGH
LEGEND
APP PWR
C.O.
FLA
IFM
NOM PWR
P.E.
PWRD
UNPWRD
ELECTRIC HEATER PART
NUMBER
CRHEATERXXXXXX
117A00
110A00
112A00
112A00,117A00
112A00,110A00
117A00
110A00
112A00
112A00,117A00
112A00,110A00
117A00
110A00
112A00
112A00,117A00
112A00,110A00
116A00
113A00
115A00
114A00,116A00
115A00,113A00
116A00
113A00
115A00
114A00,116A00
115A00,113A00
116A00
113A00
115A00
114A00,116A00
115A00,113A00
118A00
119A00
118A00,119A00
118A00
119A00
118A00,119A00
118A00
119A00
118A00,119A00
NOM
PWR
(kW)
10.4
16.0
32.0
42.4
50.0
10.4
16.0
32.0
42.4
50.0
10.4
16.0
32.0
42.4
50.0
13.9
16.5
33.0
41.7
50.0
13.9
16.5
33.0
41.7
50.0
13.9
16.5
33.0
41.7
50.0
17.0
34.0
51.0
17.0
34.0
51.0
17.0
34.0
51.0
APP
PWR
(kW)
7.8/9.6
12.0/14.7
24.0/29.4
31.8/38.9
37.6/45.9
7.8/9.6
12.0/14.7
24.0/29.4
31.8/38.9
37.6/45.9
7.8/9.6
12.0/14.7
24.0/29.4
31.8/38.9
37.6/45.9
12.8
15.2
30.3
38.3
45.9
12.8
15.2
30.3
38.3
45.9
12.8
15.2
30.3
38.3
45.9
17.0
34.0
51.0
17.0
34.0
51.0
17.0
34.0
51.0
NO C.O. or UNPWRD C.O.
NO P.E.
049
049
049
051
051
049
049
049
051
051
049
049
049
051
051
047
047
047
050
050
047
047
047
050
050
047
047
047
050
050
047
047
050
047
047
050
047
047
050
w/P.E.
(pwrd fr/unit)
049
049
049
051
051
049
049
049
051
051
049
049
049
051
051
047
047
047
050
050
047
047
047
050
050
047
047
047
050
050
047
047
050
047
047
050
047
050
050
- 208 / 230V / 460V / 575V
- Convenience outlet
- Full load amps
- Indoor fan motor
- 240V / 480V / 600V
- Power exhaust
- Powered convenience outlet
- Unpowered convenience outlet
513 31 3209 02
100
ELECTRIC HEAT − ELECTRICAL INFORMATION
(UNITS PRODUCED ON OR AFTER JULY 30, 2012)
Table 35 (cont.) − RAS150
2−STAGE COOLING 1−SPEED INDOOR FAN MOTOR
WITH FACTORY INSTALLED NON−FUSED DISCONNECT
SINGLE POINT KIT PART NUMBER
CRSINGLEXXXXXX
NOM.
V-PH-Hz.
IFM
TYPE
STD
208/
230-3-60
MED
HIGH
STD
460-3-60
MED
HIGH
STD
575-3-60
MED
HIGH
LEGEND
APP PWR
C.O.
FLA
IFM
NOM PWR
P.E.
PWRD
UNPWRD
101
ELECTRIC HEATER PART
NUMBER
CRHEATERXXXXXX
117A00
110A00
112A00
112A00,117A00
112A00,110A00
117A00
110A00
112A00
112A00,117A00
112A00,110A00
NOM
PWR
(kW)
10.4
16.0
32.0
42.4
50.0
10.4
16.0
32.0
42.4
50.0
APP
PWR
(kW)
7.8/9.6
12.0/14.7
24.0/29.4
31.8/38.9
37.6/45.9
7.8/9.6
12.0/14.7
24.0/29.4
31.8/38.9
37.6/45.9
117A00
110A00
112A00
112A00,117A00
112A00,110A00
116A00
113A00
115A00
114A00,116A00
115A00,113A00
116A00
113A00
115A00
114A00,116A00
115A00,113A00
116A00
113A00
115A00
114A00,116A00
115A00,113A00
118A00
119A00
118A00,119A00
118A00
119A00
118A00,119A00
118A00
119A00
118A00,119A00
10.4
16.0
32.0
42.4
50.0
13.9
16.5
33.0
41.7
50.0
13.9
16.5
33.0
41.7
50.0
13.9
16.5
33.0
41.7
50.0
17.0
34.0
51.0
17.0
34.0
51.0
17.0
34.0
51.0
7.8/9.6
12.0/14.7
24.0/29.4
31.8/38.9
37.6/45.9
12.8
15.2
30.3
38.3
45.9
12.8
15.2
30.3
38.3
45.9
12.8
15.2
30.3
38.3
45.9
17.0
34.0
51.0
17.0
34.0
51.0
17.0
34.0
51.0
NO C.O. or UNPWRD C.O.
NO P.E.
049
049
049
051
051
049
049
049
051
051
049
049
049
051
051
047
047
047
050
050
047
047
047
050
050
047
047
047
050
050
047
047
050
047
047
050
047
047
050
w/P.E.
(pwrd fr/unit)
049
049
049
051
051
049
049
049
051
051
049
049
049
051
051
047
047
047
050
050
047
047
047
050
050
047
047
047
050
050
047
047
050
047
047
050
047
050
050
- 208 / 230V / 460V / 575V
- Convenience outlet
- Full load amps
- Indoor fan motor
- 240V / 480V / 600V
- Power exhaust
- Powered convenience outlet
- Unpowered convenience outlet
513 31 3209 02
ELECTRIC HEAT − ELECTRICAL INFORMATION
(UNITS PRODUCED ON OR AFTER JULY 30, 2012)
Table 35 (cont.) − RAS150
2−STAGE COOLING 2−SPEED INDOOR FAN MOTOR
WITHOUT FACTORY INSTALLED NON−FUSED DISCONNECT
SINGLE POINT KIT PART NUMBER
CRSINGLEXXXXXX
NOM.
V-PH-Hz.
IFM
TYPE
STD
MED
208/
230-3-60
HIGH
STD
460-3-60
MED
HIGH
STD
575-3-60
MED
HIGH
LEGEND
APP PWR
C.O.
FLA
IFM
NOM PWR
P.E.
PWRD
UNPWRD
ELECTRIC HEATER PART
NUMBER
CRHEATERXXXXXX
117A00
110A00
112A00
112A00,117A00
112A00,110A00
117A00
110A00
112A00
112A00,117A00
112A00,110A00
NOM
PWR
(kW)
10.4
16.0
32.0
42.4
50.0
10.4
16.0
32.0
42.4
50.0
APP
PWR
(kW)
7.8/9.6
12.0/14.7
24.0/29.4
31.8/38.9
37.6/45.9
7.8/9.6
12.0/14.7
24.0/29.4
31.8/38.9
37.6/45.9
117A00
110A00
112A00
112A00,117A00
112A00,110A00
116A00
113A00
115A00
114A00,116A00
115A00,113A00
116A00
113A00
115A00
114A00,116A00
115A00,113A00
116A00
113A00
115A00
114A00,116A00
115A00,113A00
118A00
119A00
118A00,119A00
118A00
119A00
118A00,119A00
118A00
119A00
118A00,119A00
10.4
16.0
32.0
42.4
50.0
13.9
16.5
33.0
41.7
50.0
13.9
16.5
33.0
41.7
50.0
13.9
16.5
33.0
41.7
50.0
17.0
34.0
51.0
17.0
34.0
51.0
17.0
34.0
51.0
7.8/9.6
12.0/14.7
24.0/29.4
31.8/38.9
37.6/45.9
12.8
15.2
30.3
38.3
45.9
12.8
15.2
30.3
38.3
45.9
12.8
15.2
30.3
38.3
45.9
17.0
34.0
51.0
17.0
34.0
51.0
17.0
34.0
51.0
NO C.O. or UNPWRD C.O.
NO P.E.
049
049
049
051
051
049
049
049
051
051
049
049
049
051
051
047
047
047
050
050
047
047
047
050
050
047
047
047
050
050
047
047
050
047
047
050
047
047
050
w/P.E.
(pwrd fr/unit)
049
049
049
051
051
049
049
049
051
051
049
049
049
051
051
047
047
047
050
050
047
047
047
050
050
047
047
047
050
050
047
050
050
047
050
050
047
050
050
- 208 / 230V / 460V / 575V
- Convenience outlet
- Full load amps
- Indoor fan motor
- 240V / 480V / 600V
- Power exhaust
- Powered convenience outlet
- Unpowered convenience outlet
513 31 3209 02
102
ELECTRIC HEAT − ELECTRICAL INFORMATION
(UNITS PRODUCED ON OR AFTER JULY 30, 2012)
Table 35 (cont.) − RAS180
2−STAGE COOLING 1−SPEED INDOOR FAN MOTOR
WITHOUT FACTORY INSTALLED NON−FUSED DISCONNECT
SINGLE POINT KIT PART NUMBER
CRSINGLEXXXXXX
NOM.
V-PH-Hz.
IFM
TYPE
STD
208/
230-3-60
MED
HIGH
STD
460-3-60
MED
HIGH
STD
575-3-60
MED
HIGH
LEGEND
APP PWR
C.O.
FLA
IFM
NOM PWR
P.E.
PWRD
UNPWRD
103
ELECTRIC HEATER PART
NUMBER
CRHEATERXXXXXX
291A00
294A00
288A00,294A00
291A00,294A00
294A00,294A00
291A00
294A00
288A00,294A00
291A00,294A00
294A00,294A00
291A00
294A00
288A00,294A00
291A00,294A00
294A00,294A00
292A00
295A00
289A00,295A00
292A00,295A00
295A00,295A00
292A00
295A00
289A00,295A00
292A00,295A00
295A00,295A00
292A00
295A00
289A00,295A00
292A00,295A00
295A00,295A00
293A00
296A00
290A00,296A00
293A00,296A00
296A00,296A00
293A00
296A00
290A00,296A00
293A00,296A00
296A00,296A00
293A00
296A00
290A00,296A00
293A00,296A00
296A00,296A00
NOM
PWR
(kW)
16.5
33.5
43.5
50.0
67.0
16.5
33.5
43.5
50.0
67.0
16.5
33.5
43.5
50.0
67.0
16.5
33.5
43.5
50.0
67.0
16.5
33.5
43.5
50.0
67.0
16.5
33.5
43.5
50.0
67.0
16.5
33.5
43.5
50.0
67.0
16.5
33.5
43.5
50.0
67.0
16.5
33.5
43.5
50.0
67.0
APP
PWR
(kW)
12.4/15.2
25.2/30.8
32.7/40.0
37.6/45.9
50.3/61.5
12.4/15.2
25.2/30.8
32.7/40.0
37.6/45.9
50.3/61.5
12.4/15.2
25.2/30.8
32.7/40.0
37.6/45.9
50.3/61.5
15.2
30.8
40.0
45.9
61.5
15.2
30.8
40.0
45.9
61.5
15.2
30.8
40.0
45.9
61.5
15.2
30.8
40.0
45.9
61.5
15.2
30.8
40.0
45.9
61.5
15.2
30.8
40.0
45.9
61.5
NO C.O. or UNPWRD C.O.
NO P.E.
049
049
051
051
053
049
049
051
051
053
049
049
051
051
053
047
050
050
050
047
050
050
050
050
050
050
050
047
047
047
050
047
047
047
050
047
050
050
050
w/P.E.
(pwrd fr/unit)
049
049
051
051
053
049
049
051
051
053
049
049
051
051
053
047
050
050
050
047
050
050
050
050
050
050
050
047
050
047
050
047
050
047
050
047
050
050
050
- 208 / 230V / 460V / 575V
- Convenience outlet
- Full load amps
- Indoor fan motor
- 240V / 480V / 600V
- Power exhaust
- Powered convenience outlet
- Unpowered convenience outlet
513 31 3209 02
ELECTRIC HEAT − ELECTRICAL INFORMATION
(UNITS PRODUCED ON OR AFTER JULY 30, 2012)
Table 35 (cont.) − RAS180
2−STAGE COOLING 1−SPEED INDOOR FAN MOTOR
WITH FACTORY INSTALLED NON−FUSED DISCONNECT
SINGLE POINT KIT PART NUMBER
CRSINGLEXXXXXX
NOM.
V-PH-Hz.
IFM
TYPE
STD
208/
230-3-60
MED
HIGH
STD
460-3-60
MED
HIGH
STD
575-3-60
MED
HIGH
LEGEND
APP PWR
C.O.
FLA
IFM
NOM PWR
P.E.
PWRD
UNPWRD
ELECTRIC HEATER PART
NUMBER
CRHEATERXXXXXX
291A00
294A00
288A00,294A00
291A00,294A00
294A00,294A00
291A00
294A00
288A00,294A00
291A00,294A00
294A00,294A00
291A00
294A00
288A00,294A00
291A00,294A00
294A00,294A00
292A00
295A00
289A00,295A00
292A00,295A00
295A00,295A00
292A00
295A00
289A00,295A00
292A00,295A00
295A00,295A00
292A00
295A00
289A00,295A00
292A00,295A00
295A00,295A00
293A00
296A00
290A00,296A00
293A00,296A00
296A00,296A00
293A00
296A00
290A00,296A00
293A00,296A00
296A00,296A00
293A00
296A00
290A00,296A00
293A00,296A00
296A00,296A00
NOM
PWR
(kW)
16.5
33.5
43.5
50.0
67.0
16.5
33.5
43.5
50.0
67.0
16.5
33.5
43.5
50.0
67.0
16.5
33.5
43.5
50.0
67.0
16.5
33.5
43.5
50.0
67.0
16.5
33.5
43.5
50.0
67.0
16.5
33.5
43.5
50.0
67.0
16.5
33.5
43.5
50.0
67.0
16.5
33.5
43.5
50.0
67.0
APP
PWR
(kW)
12.4/15.2
25.2/30.8
32.7/40.0
37.6/45.9
50.3/61.5
12.4/15.2
25.2/30.8
32.7/40.0
37.6/45.9
50.3/61.5
12.4/15.2
25.2/30.8
32.7/40.0
37.6/45.9
50.3/61.5
15.2
30.8
40.0
45.9
61.5
15.2
30.8
40.0
45.9
61.5
15.2
30.8
40.0
45.9
61.5
15.2
30.8
40.0
45.9
61.5
15.2
30.8
40.0
45.9
61.5
15.2
30.8
40.0
45.9
61.5
NO C.O. or UNPWRD C.O.
NO P.E.
049
049
051
051
053
049
049
051
051
053
049
049
051
051
053
047
050
050
050
047
050
050
050
050
050
050
050
047
047
047
050
047
047
047
050
047
050
050
050
w/P.E.
(pwrd fr/unit)
049
049
051
051
053
049
049
051
051
053
049
049
051
051
053
047
050
050
050
047
050
050
050
050
050
050
050
047
050
047
050
047
050
047
050
047
050
050
050
- 208 / 230V / 460V / 575V
- Convenience outlet
- Full load amps
- Indoor fan motor
- 240V / 480V / 600V
- Power exhaust
- Powered convenience outlet
- Unpowered convenience outlet
513 31 3209 02
104
ELECTRIC HEAT − ELECTRICAL INFORMATION
(UNITS PRODUCED ON OR AFTER JULY 30, 2012)
Table 35 (cont.) − RAS180
2−STAGE COOLING 2−SPEED INDOOR FAN MOTOR
WITHOUT FACTORY INSTALLED NON−FUSED DISCONNECT
SINGLE POINT KIT PART NUMBER
CRSINGLEXXXXXX
NOM.
V-PH-Hz.
IFM
TYPE
STD
208/
230-3-60
MED
HIGH
STD
460-3-60
MED
HIGH
STD
575-3-60
MED
HIGH
LEGEND
APP PWR
C.O.
FLA
IFM
NOM PWR
P.E.
PWRD
UNPWRD
105
ELECTRIC HEATER PART
NUMBER
CRHEATERXXXXXX
291A00
294A00
288A00,294A00
291A00,294A00
294A00,294A00
291A00
294A00
288A00,294A00
291A00,294A00
294A00,294A00
294A00
288A00,294A00
291A00,294A00
294A00,294A00
292A00
295A00
289A00,295A00
292A00,295A00
295A00,295A00
292A00
295A00
289A00,295A00
292A00,295A00
295A00,295A00
292A00
295A00
289A00,295A00
292A00,295A00
295A00,295A00
293A00
296A00
290A00,296A00
293A00,296A00
296A00,296A00
293A00
296A00
290A00,296A00
293A00,296A00
296A00,296A00
293A00
296A00
290A00,296A00
293A00,296A00
296A00,296A00
NOM
PWR
(kW)
16.5
33.5
43.5
50.0
67.0
16.5
33.5
43.5
50.0
67.0
33.5
43.5
50.0
67.0
16.5
33.5
43.5
50.0
67.0
16.5
33.5
43.5
50.0
67.0
16.5
33.5
43.5
50.0
67.0
16.5
33.5
43.5
50.0
67.0
16.5
33.5
43.5
50.0
67.0
16.5
33.5
43.5
50.0
67.0
APP
PWR
(kW)
12.4/15.2
25.2/30.8
32.7/40.0
37.6/45.9
50.3/61.5
12.4/15.2
25.2/30.8
32.7/40.0
37.6/45.9
50.3/61.5
25.2/30.8
32.7/40.0
37.6/45.9
50.3/61.5
15.2
30.8
40.0
45.9
61.5
15.2
30.8
40.0
45.9
61.5
15.2
30.8
40.0
45.9
61.5
15.2
30.8
40.0
45.9
61.5
15.2
30.8
40.0
45.9
61.5
15.2
30.8
40.0
45.9
61.5
NO C.O. or UNPWRD C.O.
NO P.E.
049
049
051
051
053
049
049
051
051
053
049
051
051
053
047
050
050
050
047
050
050
050
050
050
050
050
047
047
047
050
047
047
047
050
047
050
050
050
w/P.E.
(pwrd fr/unit)
049
049
051
051
053
049
049
051
051
053
049
051
051
053
047
050
050
050
047
050
050
050
050
050
050
050
047
050
047
050
047
050
047
050
047
050
050
050
- 208 / 230V / 460V / 575V
- Convenience outlet
- Full load amps
- Indoor fan motor
- 240V / 480V / 600V
- Power exhaust
- Powered convenience outlet
- Unpowered convenience outlet
513 31 3209 02
ELECTRICAL INFORMATION
(UNITS PRODUCED ON OR AFTER JULY 30, 2012) cont.
Table 36 – UNIT WIRE/FUSE OR HACR BREAKER SIZING DATA
208/230-1-60
Model
NO M. V-Ph-HZ
ELEC. HTR
NO P.E.
IFM
TYPE
w/ P.E. (pwrd fr/unit)
MAX
FUSE or
HACR
BRKR
FLA
LRA
40
26
95
MCA
30
DISC. SIZE
MAX
FUSE or
HACR
BRKR
FLA
45
29
97
DISC. SIZE
CRHEATER***A00
Nom
(kW)
NONE
-
FLA
-
MCA
28
101A
3.3/4.4
15.9/18.3
28/29
40/40
26/27
95/95
30/32
45/45
29/29
97/97
102A
4.9/6.5
23.5/27.1
36/40
40/45
33/37
95/95
38/43
45/45
35/39
97/97
103B
6.5/8.7
31.4/36.3
46/52
50/60
42/47
95/95
48/54
50/60
44/50
97/97
104B
7.9/10.5
37.9/43.8
54/61
60/70
49/56
95/95
56/64
60/70
51/58
97/97
102A+102A
9.8/13.0
46.9/54.2
65/74
70/80
60/68
95/95
68/77
70/80
62/70
97/97
NONE
-
-
20
30
20
96
22
30
22
98
101A
3.3/4.4
9.2/10.6
20/20
30/30
20/20
96/96
22/23
30/30
22/22
98/98
102A
4.9/6.5
13.6/15.6
24/26
30/30
22/24
96/96
26/29
30/30
24/26
98/98
103B
6.5/8.7
18.1/20.9
30/33
30/35
27/30
96/96
32/35
35/40
29/32
98/98
104B
7.9/10.5
21.9/25.3
34/39
35/40
31/35
96/96
37/41
40/45
33/37
98/98
105A
12.0/16.0
33.4/38.5
49/55
50/60
44/50
96/96
51/57
60/60
47/52
98/98
NONE
-
-
22/22
30/30
22/21
134
24/24
30/30
24/24
136
101A
3.3/4.4
9.2/10.6
22/22
30/30
22/21
134/134
24/24
30/30
24/24
136/136
102A
4.9/6.5
13.6/15.6
26/28
30/30
24/26
134/134
28/31
30/35
26/28
136/136
103B
6.5/8.7
18.1/20.9
32/35
35/35
29/32
134/134
34/37
35/40
31/34
136/136
104B
7.9/10.5
21.9/25.3
36/40
40/40
33/37
134/134
39/43
40/45
35/39
136/136
105A
12.0/16.0
33.4/38.5
51/57
60/60
46/52
134/134
53/59
60/60
49/54
136/136
NONE
-
-
11
15
11
49
12
15
12
50
106A
6.0
7.2
13
15
11
49
14
15
12
50
107A
8.8
10.6
17
20
15
49
18
20
16
50
108A
11.5
13.8
21
25
19
49
22
25
20
50
109A
14.0
16.8
25
25
22
49
26
30
23
50
NONE
-
-
12
15
12
68
13
15
13
69
106A
6.0
7.2
14
15
12
68
15
15
13
69
107A
8.8
10.6
18
20
16
68
19
20
17
69
108A
11.5
13.8
22
25
20
68
23
25
21
69
109A
14.0
16.8
26
30
23
68
27
30
24
69
STD
NONE
-
-
8
15
8
46
10
15
10
48
HIGH
NONE
-
-
8
15
7
50
10
15
10
52
STD
208/230-3-60
STD
HIGH
RAS036
460-3-60
STD
HIGH
575-3-60
NO C.O. or UNPWR C.O.
513 31 3209 02
LRA
106
ELECTRICAL INFORMATION
(UNITS PRODUCED ON OR AFTER JULY 30, 2012) cont.
Table 36 − UNIT WIRE/FUSE OR HACR BREAKER SIZING DATA (cont.)
208/230-1-60
Unit
NO M. V-Ph-HZ
ELEC. HTR
IFM
TYPE
STD
208/230-3-60
STD
HIGH
RAS048
460-3-60
STD
575-3-60
w/ P.E. (pwrd fr/unit)
CRHEATER***A00
Nom
(kW)
FLA
MCA
MAX
FUSE or
HACR
BRKR
FLA
LRA
MCA
MAX
FUSE or
HACR
BRKR
NONE
-
-
34
50
32
133
36
50
35
135
101A
3.3/4.4
15.9/18.3
34/34
50/50
32/32
133/133
36/36
50/50
35/35
135/135
DISC. SIZE
DISC. SIZE
FLA
LRA
103B
6.5/8.7
31.4/36.3
46/52
50/60
42/47
133/133
48/54
50/60
44/50
135/135
102A+102A
9.8/13.0
46.9/54.2
65/74
70/80
60/68
133/133
68/77
70/80
62/70
135/135
103B+103B
13.1/17.4
62.8/72.5
85/97
90/100
78/89
133/133
87/100
90/100
80/91
135/135
104B+104B
15.8/21.0
75.8/87.5
101/116
110/125
93/106
133/133
104/118
110/125
95/108
135/135
NONE
-
-
24
30
23
106
26
30
26
108
102A
4.9/6.5
13.6/15.6
24/26
30/30
23/24
106/106
26/29
30/30
26/26
108/108
103B
6.5/8.7
18.1/20.9
30/33
30/35
27/30
106/106
32/35
35/40
29/32
108/108
105A
12.0/16.0
33.4/38.5
49/55
50/60
44/50
106/106
51/57
60/60
47/52
108/108
104B+104B
15.8/21.0
43.8/50.5
62/70
70/70
56/64
106/106
64/72
70/80
59/66
108/108
NONE
-
-
26/26
30/30
25/25
144
28/28
40/40
28/27
146
102A
4.9/6.5
13.6/15.6
26/28
30/30
25/26
144/144
28/31
40/40
28/28
146/146
103B
6.5/8.7
18.1/20.9
32/35
35/35
29/32
144/144
34/37
40/40
31/34
146/146
105A
12.0/16.0
33.4/38.5
51/57
60/60
46/52
144/144
53/59
60/60
49/54
146/146
104B+104B
15.8/21.0
43.8/50.5
64/72
70/80
58/66
144/144
66/74
70/80
60/68
146/146
NONE
-
-
12
15
11
52
13
15
12
53
106A
6.0
7.2
13
15
11
52
14
15
12
53
108A
11.5
13.8
21
25
19
52
22
25
20
53
109A
14.0
16.8
25
25
22
52
26
30
23
53
108A+108A
23.0
27.7
38
40
35
52
40
40
36
53
NONE
-
-
12
15
12
71
13
15
13
72
106A
6.0
7.2
14
15
12
71
15
15
13
72
108A
11.5
13.8
22
25
20
71
23
25
21
72
109A
14.0
16.8
26
30
23
71
27
30
24
72
108A+108A
23.0
27.7
39
40
36
71
41
45
37
72
STD
NONE
-
-
9
15
9
42
11
15
11
44
HIGH
NONE
-
-
9
15
9
46
11
15
11
48
HIGH
107
NO C.O. or UNPWR C.O.
NO P.E.
513 31 3209 02
ELECTRICAL INFORMATION
(UNITS PRODUCED ON OR AFTER JULY 30, 2012) cont.
Table 36 − UNIT WIRE/FUSE OR HACR BREAKER SIZING DATA (cont.)
UNIT
NO M. V-Ph-HZ
ELEC. HTR
NO P.E.
IFM
TYPE
208/230-1-60
STD
208/230-3-60
FLA
LRA
60
37
150
MCA
42
DISC. SIZE
MAX
FUSE or
HACR
BRKR
FLA
60
40
152
DISC. SIZE
NONE
Nom
(kW)
-
FLA
-
MCA
40
102A
4.9/6.5
23.5/27.1
40/40
60/60
37/37
150/150
42/43
60/60
40/40
152/152
CRHEATER***A00
LRA
103B
6.5/8.7
31.4/36.3
46/52
60/60
42/47
150/150
48/54
60/60
44/50
152/152
102A+102A
9.8/13.0
46.9/54.2
65/74
70/80
60/68
150/150
68/77
70/80
62/70
152/152
103B+103B
13.1/17.4
62.8/72.5
85/97
90/100
78/89
150/150
87/100
90/100
80/91
152/152
104B+104B
15.8/21.0
75.8/87.5
101/116
110/125
93/106
150/150
104/118
110/125
95/108
152/152
NONE
-
-
42
60
40
175
44
60
42
177
102A
4.9/6.5
23.5/27.1
42/43
60/60
40/40
175/175
44/45
60/60
42/42
177/177
103B
6.5/8.7
31.4/36.3
48/55
60/60
44/50
175/175
51/57
60/60
46/52
177/177
9.8/13.0
46.9/54.2
68/77
70/80
62/70
175/175
70/79
70/80
64/73
177/177
103B+103B
13.1/17.4
62.8/72.5
88/100
90/100
80/91
175/175
90/102
90/110
82/94
177/177
104B+104B
15.8/21.0
75.8/87.5
104/119
110/125
95/109
175/175
106/121
110/125
97/111
177/177
NONE
-
-
27
40
26
133
29
40
28
135
102A
4.9/6.5
13.6/15.6
27/27
40/40
26/26
133/133
29/29
40/40
28/28
135/135
104B
7.9/10.5
21.9/25.3
34/39
40/40
31/35
133/133
37/41
40/45
33/37
135/135
105A
12.0/16.0
33.4/38.5
49/55
50/60
44/50
133/133
51/57
60/60
47/52
135/135
104B+104B
15.8/21.0
43.8/50.5
62/70
70/70
56/64
133/133
64/72
70/80
59/66
135/135
104B+105A
19.9/26.5
55.2/63.8
76/87
80/90
69/79
133/133
78/89
80/90
72/82
135/135
NONE
-
-
28/28
40/40
28/27
171
30/30
45/45
30/30
173
102A
4.9/6.5
13.6/15.6
28/28
40/40
28/27
171/171
30/31
45/45
30/30
173/173
104B
7.9/10.5
21.9/25.3
36/40
40/40
33/37
171/171
39/43
45/45
35/39
173/173
105A
12.0/16.0
33.4/38.5
51/57
60/60
46/52
171/171
53/59
60/60
49/54
173/173
104B+104B
15.8/21.0
43.8/50.5
64/72
70/80
58/66
171/171
66/74
70/80
60/68
173/173
104B+105A
19.9/26.5
55.2/63.8
78/89
80/90
71/81
171/171
80/91
90/100
74/83
173/173
NONE
-
-
30/30
45/40
29/29
186
32/32
45/45
32/31
188
102A
4.9/6.5
13.6/15.6
30/30
45/40
29/29
186/186
32/33
45/45
32/31
188/188
104B
7.9/10.5
21.9/25.3
38/42
45/45
35/39
186/186
41/45
45/45
37/41
188/188
105A
12.0/16.0
33.4/38.5
53/59
60/60
48/54
186/186
55/61
60/70
50/56
188/188
104B+104B
15.8/21.0
43.8/50.5
66/74
70/80
60/68
186/186
68/76
70/80
62/70
188/188
104B+105A
19.9/26.5
55.2/63.8
80/91
80/100
73/83
186/186
82/93
90/100
75/85
188/188
NONE
-
-
13
20
13
63
14
20
14
64
106A
6.0
7.2
13
20
13
63
14
20
14
64
108A
11.5
13.8
21
25
19
63
22
25
20
64
109A
14.0
16.8
25
25
22
63
26
30
23
64
108A+108A
23.0
27.7
38
40
35
63
40
40
36
64
108A+109A
25.5
30.7
42
45
38
63
43
45
39
64
NONE
-
-
14
20
14
82
15
20
15
83
106A
6.0
7.2
14
20
14
82
15
20
15
83
108A
11.5
13.8
22
25
20
82
23
25
21
83
109A
14.0
16.8
26
30
23
82
27
30
24
83
108A+108A
23.0
27.7
39
40
36
82
41
45
37
83
108A+109A
25.5
30.7
43
45
39
82
44
45
40
83
NONE
-
-
15
20
15
90
16
20
16
91
106A
6.0
7.2
15
20
15
90
16
20
16
91
108A
11.5
13.8
23
25
21
90
24
25
22
91
109A
14.0
16.8
27
30
24
90
28
30
25
91
108A+108A
23.0
27.7
40
40
37
90
42
45
38
91
108A+109A
25.5
30.7
44
45
40
90
45
45
41
91
STD
NONE
-
-
11
15
10
48
13
15
12
50
MED
NONE
-
-
10
15
10
52
12
15
12
54
HIGH
NONE
-
-
11
15
11
63
13
15
13
65
STD
MED
RAS060
HIGH
STD
460-3-60
w/ P.E. (pwrd fr/unit)
MAX
FUSE or
HACR
BRKR
102A+102A
MED
MED
HIGH
575-3-60
NO C.O. or UNPWR C.O.
513 31 3209 02
108
ELECTRICAL INFORMATION
(UNITS PRODUCED ON OR AFTER JULY 30, 2012) cont.
Table 36 − UNIT WIRE/FUSE OR HACR BREAKER SIZING DATA (cont.)
UNIT
NO M. V-Ph-HZ
ELEC. HTR
NO P.E.
IFM
TYPE
208/230-3-60
STD
MED
HIGH
RAS072
460-3-60
STD
MED
575-3-60
HIGH
109
NO C.O. or UNPWR C.O.
w/ P.E. (pwrd fr/unit)
CRHEATER***A00
Nom
(kW)
FLA
MCA
MAX
FUSE or
HACR
BRKR
FLA
LRA
MCA
MAX
FUSE or
HACR
BRKR
FLA
LRA
NONE
102A
4.9/6.5
13.6/15.6
33/32
33/32
50/50
50/50
32/31
32/31
184
184/184
35/34
35/34
50/50
50/50
34/33
34/33
186
186/186
104B
7.9/10.5
21.9/25.3
36/40
50/50
33/37
184/184
39/43
50/50
35/39
186/186
105A
12.0/16.0
33.4/38.5
51/57
60/60
46/52
184/184
53/59
60/60
49/54
186/186
104B+104B
15.8/21.0
43.8/50.5
64/72
70/80
58/66
184/184
66/74
70/80
60/68
186/186
104B+105A
19.9/26.5
55.2/63.8
78/89
80/90
71/81
184/184
80/91
90/100
74/83
186/186
NONE
-
-
34/34
50/50
33/33
199
36/36
50/50
35/35
201
102A
4.9/6.5
13.6/15.6
34/34
50/50
33/33
199/199
36/36
50/50
35/35
201/201
104B
7.9/10.5
21.9/25.3
38/42
50/50
35/39
199/199
41/45
50/50
37/41
201/201
105A
12.0/16.0
33.4/38.5
53/59
60/60
48/54
199/199
55/61
60/70
50/56
201/201
104B+104B
15.8/21.0
43.8/50.5
66/74
70/80
60/68
199/199
68/76
70/80
62/70
201/201
104B+105A
19.9/26.5
55.2/63.8
80/91
80/100
73/83
199/199
82/93
90/100
75/85
201/201
NONE
102A
4.9/6.5
13.6/15.6
36
36/36
50
50/50
36
36/36
213
213/213
38
38/38
50
50/50
38
38/38
215
215/215
104B
7.9/10.5
21.9/25.3
41/45
50/50
37/41
213/213
43/48
50/50
40/43
215/215
105A
12.0/16.0
33.4/38.5
55/62
60/70
51/56
213/213
58/64
60/70
53/59
215/215
104B+104B
15.8/21.0
43.8/50.5
68/77
70/80
63/70
213/213
71/79
80/80
65/72
215/215
104B+105A
19.9/26.5
55.2/63.8
83/93
90/100
76/86
213/213
85/96
90/100
78/88
215/215
NONE
106A
6.0
7.2
17
17
25
25
16
16
92
92
18
18
25
25
17
17
93
93
108A
11.5
13.8
22
25
20
92
23
25
21
93
109A
14.0
16.8
26
30
23
92
27
30
24
93
108A+108A
23.0
27.7
39
40
36
92
41
45
37
93
108A+109A
25.5
30.7
43
45
39
92
44
45
40
93
NONE
106A
6.0
7.2
18
18
25
25
17
17
100
100
19
19
25
25
18
18
101
101
108A
11.5
13.8
23
25
21
100
24
25
22
101
109A
14.0
16.8
27
30
24
100
28
30
25
101
108A+108A
23.0
27.7
40
40
37
100
42
45
38
101
108A+109A
25.5
30.7
44
45
40
100
45
45
41
101
NONE
106A
6.0
7.2
19
19
25
25
18
18
107
107
20
20
25
25
19
19
108
108
108A
11.5
13.8
24
25
22
107
26
30
23
108
109A
14.0
16.8
28
30
25
107
29
30
27
108
108A+108A
23.0
27.7
42
45
38
107
43
45
39
108
108A+109A
25.5
30.7
45
50
41
107
47
50
43
108
DISC. SIZE
DISC. SIZE
STD
NONE
-
-
12
15
12
63
14
20
14
65
MED
NONE
-
-
13
20
12
74
15
20
15
76
HIGH
NONE
-
-
13
20
12
74
15
20
15
76
513 31 3209 02
ELECTRICAL INFORMATION
(UNITS PRODUCED ON OR AFTER JULY 30, 2012) cont.
UNIT
NO M. V-Ph-HZ
Table 36 − UNIT WIRE/FUSE OR HACR BREAKER SIZING DATA (cont.)
ELEC. HTR
IFM
TYPE
208/230-3-60
STD
MED
HIGH
STD
460-3-60
RAS091
MED
HIGH
STD
575-3-60
NO C.O. or UNPWR C.O.
NO P.E.
MED
HIGH
513 31 3209 02
CRHEATER***A00
NONE
117A
110A
111A
112A
112A+117A
NONE
117A
110A
111A
112A
112A+117A
NONE
117A
110A
111A
112A
112A+117A
NONE
116A
113A
114A
115A
114A+116A
NONE
116A
113A
114A
115A
114A+116A
NONE
116A
113A
114A
115A
114A+116A
NONE
118A
119A
NONE
118A
119A
NONE
118A
119A
Nom
(kW)
7.8/10.4
12.0/16.0
18.6/24.8
24.0/32.0
31.8/42.4
7.8/10.4
12.0/16.0
18.6/24.8
24.0/32.0
31.8/42.4
7.8/10.4
12.0/16.0
18.6/24.8
24.0/32.0
31.8/42.4
13.9
16.5
27.8
33.0
41.7
13.9
16.5
27.8
33.0
41.7
13.9
16.5
27.8
33.0
41.7
17.0
34.0
17.0
34.0
17.0
34.0
FLA
21.7/25.0
33.4/38.5
51.7/59.7
66.7/77.0
88.4/102.0
21.7/25.0
33.4/38.5
51.7/59.7
66.7/77.0
88.4/102.0
21.7/25.0
33.4/38.5
51.7/59.7
66.7/77.0
88.4/102.0
16.7
19.8
33.4
39.7
50.2
16.7
19.8
33.4
39.7
50.2
16.7
19.8
33.4
39.7
50.2
20.4
40.9
20.4
40.9
20.4
40.9
MCA
40/40
40/40
49/55
72/81
90/103
117/134
43/43
43/43
53/59
76/85
94/107
121/138
48/47
48/48
59/64
82/91
101/113
128/144
20
24
28
45
53
66
22
27
30
47
55
68
24
29
33
50
58
71
15
28
54
16
29
55
19
33
59
MAX
FUSE or
HACR
BRKR
60/60
60/60
60/60
80/90
90/110
125/150
60/60
60/60
60/60
80/90
100/110
125/150
60/60
60/60
60/70
90/100
110/125
150/150
30
30
30
45
60
70
30
30
30
50
60
70
30
30
35
50
60
80
20
30
60
20
30
60
25
35
60
w/ P.E. (pwrd fr/unit)
DISC. SIZE
FLA
38/38
38/38
44/50
65/74
83/94
108/123
42/42
42/42
48/54
69/78
86/98
111/127
48/47
48/47
54/59
75/83
92/103
117/132
19
22
26
41
49
61
21
24
28
43
50
63
23
27
30
46
53
65
14
25
49
15
27
50
18
30
53
LRA
208
208/208
208/208
208/208
208/208
208/208
244
244/244
244/244
244/244
244/244
244/244
260
260/260
260/260
260/260
260/260
260/260
122
122
122
122
122
122
140
140
140
140
140
140
148
148
148
148
148
148
89
89
89
104
104
104
118
118
118
MCA
44/43
44/43
53/59
76/86
95/108
122/139
47/47
47/47
57/64
80/90
99/112
126/143
52/51
52/52
64/69
87/96
106/117
133/149
22
27
31
48
55
69
23
29
33
50
58
71
26
32
35
52
60
73
18
33
58
20
34
60
22
38
63
MAX
FUSE or
HACR
BRKR
60/60
60/60
60/60
80/90
100/110
125/150
60/60
60/60
60/70
80/90
100/125
150/150
60/60
60/60
70/70
90/100
110/125
150/150
30
30
35
50
60
70
30
30
35
50
60
80
30
35
35
60
60
80
25
35
60
25
35
60
30
40
70
DISC. SIZE
FLA
43/42
43/42
49/54
70/79
87/99
112/127
46/46
46/46
52/58
73/83
91/102
116/131
52/51
52/51
58/63
79/88
97/108
122/136
21
24
28
43
51
63
23
26
30
45
53
65
25
29
32
48
55
67
18
30
53
19
31
55
23
34
58
LRA
212
212/212
212/212
212/212
212/212
212/212
248
248/248
248/248
248/248
248/248
248/248
264
264/264
264/264
264/264
264/264
264/264
124
124
124
124
124
124
142
142
142
142
142
142
150
150
150
150
150
150
93
93
93
108
108
108
122
122
122
110
ELECTRICAL INFORMATION
(UNITS PRODUCED ON OR AFTER JULY 30, 2012) cont.
UNIT
NO M. V-Ph-HZ
Table 36 − UNIT WIRE/FUSE OR HACR BREAKER SIZING DATA (cont.)
ELEC. HTR
IFM
TYPE
208/230-3-60
STD
MED
HIGH
STD
460-3-60
RAS90
MED
HIGH
575-3-60
STD
MED
HIGH
111
NO C.O. or UNPWR C.O.
NO P.E.
CRHEATER***A00
NONE
117A
110A
111A
112A
112A+117A
NONE
117A
110A
111A
112A
112A+117A
NONE
117A
110A
111A
112A
112A+117A
NONE
116A
113A
114A
115A
114A+116A
NONE
116A
113A
114A
115A
114A+116A
NONE
116A
113A
114A
115A
114A+116A
NONE
118A
119A
NONE
118A
119A
NONE
118A
119A
Nom
(kW)
7.8/10.4
12.0/16.0
18.6/24.8
24.0/32.0
31.8/42.4
7.8/10.4
12.0/16.0
18.6/24.8
24.0/32.0
31.8/42.4
7.8/10.4
12.0/16.0
18.6/24.8
24.0/32.0
31.8/42.4
13.9
16.5
27.8
33.0
41.7
13.9
16.5
27.8
33.0
41.7
13.9
16.5
27.8
33.0
41.7
17.0
34.0
17.0
34.0
17.0
34.0
FLA
21.7/25.0
33.4/38.5
51.7/59.7
66.7/77.0
88.4/102.0
21.7/25.0
33.4/38.5
51.7/59.7
66.7/77.0
88.4/102.0
21.7/25.0
33.4/38.5
51.7/59.7
66.7/77.0
88.4/102.0
16.7
19.8
33.4
39.7
50.2
16.7
19.8
33.4
39.7
50.2
16.7
19.8
33.4
39.7
50.2
20.4
40.9
20.4
40.9
20.4
40.9
MCA
39/39
39/39
49/55
72/81
90/103
117/134
42/42
42/42
53/59
76/85
94/107
121/138
48/47
48/48
59/64
82/91
101/113
128/144
18
24
28
45
53
66
20
27
30
47
55
68
22
29
33
50
58
71
13
28
54
14
29
55
17
33
59
MAX
FUSE or
HACR
BRKR
50/50
50/50
50/60
80/90
90/110
125/150
50/50
50/50
60/60
80/90
100/110
125/150
60/50
60/50
60/70
90/100
110/125
150/150
20
25
30
45
60
70
25
30
30
50
60
70
25
30
35
50
60
80
15
30
60
15
30
60
20
35
60
w/ P.E. (pwrd fr/unit)
DISC. SIZE
FLA
41/40
41/40
44/50
65/74
83/94
108/123
44/44
44/44
48/54
69/78
86/98
111/127
50/49
50/49
54/59
75/83
92/103
117/132
19
22
26
41
49
61
21
24
28
43
50
63
23
27
30
46
53
65
13
25
49
14
27
50
17
30
53
LRA
210
210/210
210/210
210/210
210/210
210/210
246
246/246
246/246
246/246
246/246
246/246
262
262/262
262/262
262/262
262/262
262/262
104
104
104
104
104
104
122
122
122
122
122
122
130
130
130
130
130
130
77
77
77
92
92
92
106
106
106
MCA
43/43
43/43
53/59
76/86
95/108
122/139
46/46
46/47
57/64
80/90
99/112
126/143
51/51
51/52
64/69
87/96
106/117
133/149
20
27
31
48
55
69
22
29
33
50
58
71
24
32
35
52
60
73
17
33
58
18
34
60
21
38
63
MAX
FUSE or
HACR
BRKR
50/50
50/50
60/60
80/90
100/110
125/150
50/50
50/50
60/70
80/90
100/125
150/150
60/60
60/60
70/70
90/100
110/125
150/150
25
30
35
50
60
70
25
30
35
50
60
80
30
35
35
60
60
80
20
35
60
20
35
60
25
40
70
DISC. SIZE
FLA
45/45
45/45
49/54
70/79
87/99
112/127
49/49
49/49
52/58
73/83
91/102
116/131
55/54
55/54
58/63
79/88
97/108
122/136
21
24
28
43
51
63
23
26
30
45
53
65
25
29
32
48
55
67
17
30
53
19
31
55
22
34
58
LRA
214
214/214
214/214
214/214
214/214
214/214
250
250/250
250/250
250/250
250/250
250/250
266
266/266
266/266
266/266
266/266
266/266
106
106
106
106
106
106
124
124
124
124
124
124
132
132
132
132
132
132
81
81
81
96
96
96
110
110
110
513 31 3209 02
ELECTRICAL INFORMATION
(UNITS PRODUCED ON OR AFTER JULY 30, 2012) cont.
UNIT
NO M. V-Ph-HZ
Table 36 − UNIT WIRE/FUSE OR HACR BREAKER SIZING DATA (cont.)
ELEC. HTR
IFM
TYPE
208/230-3-60
STD
MED
HIGH
STD
460-3-60
RAS101
MED
HIGH
STD
575-3-60
NO C.O. or UNPWR C.O.
NO P.E.
MED
HIGH
513 31 3209 02
CRHEATER***A00
NONE
117A
110A
111A
112A
112A+117A
NONE
117A
110A
111A
112A
112A+117A
NONE
117A
110A
111A
112A
112A+117A
NONE
116A
113A
114A
115A
114A+116A
NONE
116A
113A
114A
115A
114A+116A
NONE
116A
113A
114A
115A
114A+116A
NONE
118A
119A
NONE
118A
119A
NONE
118A
119A
Nom
(kW)
7.8/10.4
12.0/16.0
18.6/24.8
24.0/32.0
31.8/42.4
7.8/10.4
12.0/16.0
18.6/24.8
24.0/32.0
31.8/42.4
7.8/10.4
12.0/16.0
18.6/24.8
24.0/32.0
31.8/42.4
13.9
16.5
27.8
33.0
41.7
13.9
16.5
27.8
33.0
41.7
13.9
16.5
27.8
33.0
41.7
17.0
34.0
17.0
34.0
17.0
34.0
FLA
21.7/25.0
33.4/38.5
51.7/59.7
66.7/77.0
88.4/102.0
21.7/25.0
33.4/38.5
51.7/59.7
66.7/77.0
88.4/102.0
21.7/25.0
33.4/38.5
51.7/59.7
66.7/77.0
88.4/102.0
16.7
19.8
33.4
39.7
50.2
16.7
19.8
33.4
39.7
50.2
16.7
19.8
33.4
39.7
50.2
20.4
40.9
20.4
40.9
20.4
40.9
MCA
46/45
46/45
49/55
72/81
90/103
117/134
47/47
47/47
51/57
74/83
92/105
120/136
51
51/51
55/62
78/88
97/110
124/141
23
24
28
45
53
66
24
26
29
46
54
67
26
28
32
49
57
70
19
28
54
19
28
54
20
29
55
MAX
FUSE or
HACR
BRKR
60/60
60/60
60/60
80/90
90/110
125/150
60/60
60/60
60/60
80/90
100/110
125/150
60
60/60
60/70
80/90
100/110
125/150
30
30
30
45
60
70
30
30
30
50
60
70
30
30
35
50
60
70
30
30
60
30
30
60
30
30
60
w/ P.E. (pwrd fr/unit)
DISC. SIZE
FLA
43/43
43/43
44/50
65/74
83/94
108/123
45/45
45/45
46/52
67/76
85/96
110/125
50
50/50
51/56
72/81
89/101
114/129
22
22
26
41
49
61
23
23
27
42
50
62
25
25
29
45
52
64
17
25
49
18
26
49
19
27
50
LRA
239
239/239
239/239
239/239
239/239
239/239
260
260/260
260/260
260/260
260/260
260/260
289
289/289
289/289
289/289
289/289
289/289
117
117
117
117
117
117
127
127
127
127
127
127
142
142
142
142
142
142
91
91
91
95
95
95
106
106
106
MCA
49/49
49/49
53/59
76/86
95/108
122/139
51/51
51/51
56/62
78/88
97/110
124/141
55
55/55
60/67
83/93
102/115
129/146
25
27
31
48
55
69
26
28
32
49
57
70
28
30
34
51
59
72
22
33
58
23
33
59
24
34
60
MAX
FUSE or
HACR
BRKR
60/60
60/60
60/60
80/90
100/110
125/150
60/60
60/60
60/70
80/90
100/110
125/150
80
80/80
80/80
90/100
110/125
150/150
30
30
35
50
60
70
30
30
35
50
60
70
40
40
40
60
60
80
30
35
60
30
35
60
30
35
60
DISC. SIZE
FLA
48/47
48/47
49/54
70/79
87/99
112/127
50/49
50/49
51/56
72/81
89/101
114/129
54
54/54
55/61
76/85
93/105
118/134
24
24
28
43
51
63
25
25
29
44
52
64
27
27
31
47
54
66
22
30
53
22
30
54
23
31
55
LRA
243
243/243
243/243
243/243
243/243
243/243
264
264/264
264/264
264/264
264/264
264/264
293
293/293
293/293
293/293
293/293
293/293
119
119
119
119
119
119
129
129
129
129
129
129
144
144
144
144
144
144
95
95
95
99
99
99
110
110
110
112
ELECTRICAL INFORMATION
(UNITS PRODUCED ON OR AFTER JULY 30, 2012) cont.
UNIT
NO M. V-Ph-HZ
Table 36 − UNIT WIRE/FUSE OR HACR BREAKER SIZING DATA (cont.)
ELEC. HTR
NO P.E.
IFM
TYPE
208/230-3-60
STD
MED
HIGH
STD
460-3-60
RAS102
MED
HIGH
575-3-60
STD
MED
HIGH
113
NO C.O. or UNPWR C.O.
CRHEATER***A00
NONE
117A
110A
111A
112A
112A+117A
NONE
117A
110A
111A
112A
112A+117A
NONE
117A
110A
111A
112A
112A+117A
NONE
116A
113A
114A
115A
114A+116A
NONE
116A
113A
114A
115A
114A+116A
NONE
116A
113A
114A
115A
114A+116A
NONE
118A
119A
NONE
118A
119A
NONE
118A
119A
Nom
(kW)
7.8/10.4
12.0/16.0
18.6/24.8
24.0/32.0
31.8/42.4
7.8/10.4
12.0/16.0
18.6/24.8
24.0/32.0
31.8/42.4
7.8/10.4
12.0/16.0
18.6/24.8
24.0/32.0
31.8/42.4
13.9
16.5
27.8
33.0
41.7
13.9
16.5
27.8
33.0
41.7
13.9
16.5
27.8
33.0
41.7
17.0
34.0
17.0
34.0
17.0
34.0
FLA
21.7/25.0
33.4/38.5
51.7/59.7
66.7/77.0
88.4/102.0
21.7/25.0
33.4/38.5
51.7/59.7
66.7/77.0
88.4/102.0
21.7/25.0
33.4/38.5
51.7/59.7
66.7/77.0
88.4/102.0
16.7
19.8
33.4
39.7
50.2
16.7
19.8
33.4
39.7
50.2
16.7
19.8
33.4
39.7
50.2
20.4
40.9
20.4
40.9
20.4
40.9
MCA
40/40
40/40
49/55
72/81
90/103
117/134
42/42
42/42
51/57
74/83
92/105
120/136
46
46/46
55/62
78/88
97/110
124/141
19
24
28
45
53
66
20
26
29
46
54
67
21
28
32
49
57
70
16
28
54
16
28
54
17
29
55
MAX
FUSE or
HACR
BRKR
50/50
50/50
50/60
80/90
90/110
125/150
50/50
50/50
60/60
80/90
100/110
125/150
50
50/50
60/70
80/90
100/110
125/150
20
25
30
45
60
70
25
30
30
50
60
70
25
30
35
50
60
70
20
30
60
20
30
60
20
30
60
w/ P.E. (pwrd fr/unit)
DISC. SIZE
FLA
42/42
42/42
44/50
65/74
83/94
108/123
44/44
44/44
46/52
67/76
85/96
110/125
48
48/48
51/56
72/81
89/101
114/129
19
22
26
41
49
61
20
23
27
42
50
62
22
25
29
45
52
64
16
25
49
16
26
49
17
27
50
LRA
225
225/225
225/225
225/225
225/225
225/225
246
246/246
246/246
246/246
246/246
246/246
275
275/275
275/275
275/275
275/275
275/275
118
118
118
118
118
118
128
128
128
128
128
128
143
143
143
143
143
143
85
85
85
89
89
89
100
100
100
MCA
44/44
44/44
53/59
76/86
95/108
122/139
46/46
46/46
56/62
78/88
97/110
124/141
50
50/50
60/67
83/93
102/115
129/146
20
27
31
48
55
69
21
28
32
49
57
70
23
30
34
51
59
72
19
33
58
20
33
59
21
34
60
MAX
FUSE or
HACR
BRKR
50/50
50/50
60/60
80/90
100/110
125/150
60/50
60/50
60/70
80/90
100/110
125/150
60
60/60
60/70
90/100
110/125
150/150
25
30
35
50
60
70
25
30
35
50
60
70
25
30
35
60
60
80
25
35
60
25
35
60
25
35
60
DISC. SIZE
FLA
46/46
46/46
49/54
70/79
87/99
112/127
48/48
48/48
51/56
72/81
89/101
114/129
52
52/52
55/61
76/85
93/105
118/134
21
24
28
43
51
63
22
25
29
44
52
64
24
27
31
47
54
66
20
30
53
20
30
54
21
31
55
513 31 3209 02
LRA
229
229/229
229/229
229/229
229/229
229/229
250
250/250
250/250
250/250
250/250
250/250
279
279/279
279/279
279/279
279/279
279/279
120
120
120
120
120
120
130
130
130
130
130
130
145
145
145
145
145
145
89
89
89
93
93
93
104
104
104
ELECTRICAL INFORMATION
(UNITS PRODUCED ON OR AFTER JULY 30, 2012) cont.
Table 36 − UNIT WIRE/FUSE OR HACR BREAKER SIZING DATA (cont.)
UNIT
NO M. V-Ph-HZ
ELEC. HTR
IFM
TYPE
208/230-3-60
STD
MED
HIGH
STD
460-3-60
RAS121
MED
HIGH
STD
575-3-60
NO C.O. or UNPWR C.O.
NO P.E.
MED
HIGH
513 31 3209 02
CRHEATER***A00
NONE
117A
110A
112A
112A+117A
112A+110A
NONE
117A
110A
112A
112A+117A
112A+110A
NONE
117A
110A
112A
112A+117A
112A+110A
NONE
116A
113A
115A
114A+116A
115A+113A
NONE
116A
113A
115A
114A+116A
115A+113A
NONE
116A
113A
115A
114A+116A
115A+113A
NONE
118A
119A
118A+119A
NONE
118A
119A
118A+119A
NONE
118A
119A
118A+119A
Nom
(kW)
7.8/10.4
12.0/16.0
24.0/32.0
31.8/42.4
37.6/50.0
7.8/10.4
12.0/16.0
24.0/32.0
31.8/42.4
37.6/50.0
7.8/10.4
12.0/16.0
24.0/32.0
31.8/42.4
37.6/50.0
13.9
16.5
33.0
41.7
50.0
13.9
16.5
33.0
41.7
50.0
13.9
16.5
33.0
41.7
50.0
17.0
34.0
51.0
17.0
34.0
51.0
17.0
34.0
51.0
FLA
21.7/25.0
33.4/38.5
66.7/77.0
88.4/102.0
104.2/120.3
21.7/25.0
33.4/38.5
66.7/77.0
88.4/102.0
104.2/120.3
21.7/25.0
33.4/38.5
66.7/77.0
88.4/102.0
104.2/120.3
16.7
19.8
39.7
50.2
60.1
16.7
19.8
39.7
50.2
60.1
16.7
19.8
39.7
50.2
60.1
20.4
40.9
61.3
20.4
40.9
61.3
20.4
40.9
61.3
MCA
48/48
48/48
51/57
92/105
120/136
139/129
52
52/52
55/62
97/110
124/141
144/134
55/54
55/54
59/64
101/113
128/144
148/137
26
26
29
54
67
65
28
28
32
57
70
67
29
29
33
58
71
69
19
28
54
64
20
29
55
65
23
33
59
69
MAX
FUSE or
HACR
BRKR
60/60
60/60
60/60
100/110
125/150
150/150
60
60/60
60/80
100/110
125/150
150/150
80/80
80/80
80/80
110/125
150/150
150/150
40
40
40
60
70
70
40
40
40
60
70
80
45
45
45
60
80
80
30
30
60
70
30
30
60
70
30
35
60
80
w/ P.E. (pwrd fr/unit)
DISC. SIZE
FLA
46/46
46/46
46/52
85/96
110/125
128/146
50
50/50
51/56
89/101
114/129
132/151
54/53
54/53
54/59
92/103
117/132
135/153
25
25
27
50
62
73
27
27
29
52
64
75
28
28
30
53
65
76
18
26
49
73
19
27
50
74
22
30
53
77
LRA
290
290/290
290/290
290/290
290/290
290/290
319
319/319
319/319
319/319
319/319
319/319
321
321/321
321/321
321/321
321/321
321/321
146
146
146
146
146
146
161
161
161
161
161
161
162
162
162
162
162
162
95
95
95
95
106
106
106
106
120
120
120
120
MCA
52/52
52/52
56/62
97/110
124/141
144/134
55
55/55
60/67
102/115
129/146
149/139
58/58
58/58
64/69
106/117
133/149
152/141
28
28
32
57
70
67
30
30
34
59
72
69
31
32
35
60
73
71
23
33
59
69
24
34
60
70
26
38
63
74
MAX
FUSE or
HACR
BRKR
60/60
60/60
60/80
100/110
125/150
150/150
80
80/80
80/80
110/125
150/150
150/150
80/80
80/80
80/80
110/125
150/150
175/175
40
40
40
60
70
70
45
45
45
60
80
80
45
45
45
60
80
80
30
35
60
80
30
35
60
80
30
40
70
80
DISC. SIZE
FLA
50/50
50/50
51/56
89/101
114/129
132/150
55
55/55
55/61
93/105
118/134
136/155
58/57
58/57
58/63
97/108
122/136
140/157
27
27
29
52
64
75
29
29
31
54
66
77
30
30
32
55
67
79
22
30
54
77
23
31
55
78
26
34
58
81
LRA
294
294/294
294/294
294/294
294/294
294/294
323
323/323
323/323
323/323
323/323
323/323
325
325/325
325/325
325/325
325/325
325/325
148
148
148
148
148
148
163
163
163
163
163
163
164
164
164
164
164
164
99
99
99
99
110
110
110
110
124
124
124
124
114
ELECTRICAL INFORMATION
(UNITS PRODUCED ON OR AFTER JULY 30, 2012) cont.
Table 36 − UNIT WIRE/FUSE OR HACR BREAKER SIZING DATA (cont.)
UNIT
NO M. V-Ph-HZ
ELEC. HTR
IFM
TYPE
208/230-3-60
STD
MED
HIGH
STD
460-3-60
RAS120
MED
HIGH
575-3-60
STD
MED
HIGH
115
NO C.O. or UNPWR C.O.
NO P.E.
CRHEATER***A00
NONE
117A
110A
112A
112A+117A
112A+110A
NONE
117A
110A
112A
112A+117A
112A+110A
NONE
117A
110A
112A
112A+117A
112A+110A
NONE
116A
113A
115A
114A+116A
115A+113A
NONE
116A
113A
115A
114A+116A
115A+113A
NONE
116A
113A
115A
114A+116A
115A+113A
NONE
118A
119A
118A+119A
NONE
118A
119A
118A+119A
NONE
118A
119A
118A+119A
Nom
(kW)
7.8/10.4
12.0/16.0
24.0/32.0
31.8/42.4
37.6/50.0
7.8/10.4
12.0/16.0
24.0/32.0
31.8/42.4
37.6/50.0
7.8/10.4
12.0/16.0
24.0/32.0
31.8/42.4
37.6/50.0
13.9
16.5
33.0
41.7
50.0
13.9
16.5
33.0
41.7
50.0
13.9
16.5
33.0
41.7
50.0
17.0
34.0
51.0
17.0
34.0
51.0
17.0
34.0
51.0
FLA
21.7/25.0
33.4/38.5
66.7/77.0
88.4/102.0
104.2/120.3
21.7/25.0
33.4/38.5
66.7/77.0
88.4/102.0
104.2/120.3
21.7/25.0
33.4/38.5
66.7/77.0
88.4/102.0
104.2/120.3
16.7
19.8
39.7
50.2
60.1
16.7
19.8
39.7
50.2
60.1
16.7
19.8
39.7
50.2
60.1
20.4
40.9
61.3
20.4
40.9
61.3
20.4
40.9
61.3
MCA
46/46
46/46
51/57
92/105
120/136
139/129
50
50/50
55/62
97/110
124/141
144/134
53/52
53/52
59/64
101/113
128/144
148/137
23
26
29
54
67
65
25
28
32
57
70
67
26
29
33
58
71
69
17
28
54
64
17
29
55
65
20
33
59
69
MAX
FUSE or
HACR
BRKR
60/60
60/60
60/60
100/110
125/150
150/150
60
60/60
60/70
100/110
125/150
150/150
60/60
60/60
60/70
110/125
150/150
150/150
30
30
30
60
70
70
30
30
35
60
70
80
30
30
35
60
80
80
20
30
60
70
20
30
60
70
25
35
60
80
w/ P.E. (pwrd fr/unit)
DISC. SIZE
FLA
48/47
48/47
48/52
85/96
110/125
128/146
52
52/52
52/56
89/101
114/129
132/151
55/54
55/54
55/59
92/103
117/132
135/153
23
23
27
50
62
73
26
26
29
52
64
75
27
27
30
53
65
76
17
26
49
73
18
27
50
74
21
30
53
77
LRA
285
285/285
285/285
285/285
285/285
285/285
314
314/314
314/314
314/314
314/314
314/314
316
316/316
316/316
316/316
316/316
316/316
136
136
136
136
136
136
151
151
151
151
151
151
152
152
152
152
152
152
93
93
93
93
104
104
104
104
118
118
118
118
MCA
50/49
50/49
56/62
97/110
124/141
144/134
53
53/53
60/67
102/115
129/146
149/139
56/55
56/55
64/69
106/117
133/149
152/141
25
28
32
57
70
67
26
30
34
59
72
69
28
32
35
60
73
71
20
33
59
69
21
34
60
70
24
38
63
74
MAX
FUSE or
HACR
BRKR
60/60
60/60
60/70
100/110
125/150
150/150
60
60/60
60/70
110/125
150/150
150/150
60/60
60/60
70/70
110/125
150/150
175/175
30
30
35
60
70
70
30
30
35
60
80
80
30
35
35
60
80
80
25
35
60
80
25
35
60
80
30
40
70
80
DISC. SIZE
FLA
52/52
52/52
52/56
89/101
114/129
132/150
56
56/56
56/61
93/105
118/134
136/155
60/59
60/59
60/63
97/108
122/136
140/157
26
26
29
52
64
75
28
28
31
54
66
77
29
29
32
55
67
79
21
30
54
77
22
31
55
78
25
34
58
81
LRA
289
289/289
289/289
289/289
289/289
289/289
318
318/318
318/318
318/318
318/318
318/318
320
320/320
320/320
320/320
320/320
320/320
138
138
138
138
138
138
153
153
153
153
153
153
154
154
154
154
154
154
97
97
97
97
108
108
108
108
122
122
122
122
513 31 3209 02
ELECTRICAL INFORMATION
(UNITS PRODUCED ON OR AFTER JULY 30, 2012) cont.
Table 36 − UNIT WIRE/FUSE OR HACR BREAKER SIZING DATA (cont.)
Unit
NO M. V-Ph-HZ
ELEC. HTR
IFM
TYPE
208/230-3-60
STD
MED
HIGH
STD
460-3-60
RAS150
MED
HIGH
STD
575-3-60
NO C.O. or UNPWR C.O.
NO P.E.
MED
HIGH
513 31 3209 02
CRHEATER***A00
NONE
117A
110A
112A
112A+117A
112A+110A
NONE
117A
110A
112A
112A+117A
112A+110A
NONE
117A
110A
112A
112A+117A
112A+110A
NONE
116A
113A
115A
114A+116A
115A+113A
NONE
116A
113A
115A
114A+116A
115A+113A
NONE
116A
113A
115A
114A+116A
115A+113A
NONE
118A
119A
118A+119A
NONE
118A
119A
118A+119A
NONE
118A
119A
118A+119A
Nom
(kW)
7.8/10.4
12.0/16.0
24.0/32.0
31.8/42.4
37.6/50.0
7.8/10.4
12.0/16.0
24.0/32.0
31.8/42.4
37.6/50.0
7.8/10.4
12.0/16.0
24.0/32.0
31.8/42.4
37.6/50.0
13.9
16.5
33.0
41.7
50.0
13.9
16.5
33.0
41.7
50.0
13.9
16.5
33.0
41.7
50.0
17.0
34.0
51.0
17.0
34.0
51.0
17.0
34.0
51.0
FLA
21.7/25.0
33.4/38.5
66.7/77.0
88.4/102.0
104.2/120.3
21.7/25.0
33.4/38.5
66.7/77.0
88.4/102.0
104.2/120.3
21.7/25.0
33.4/38.5
66.7/77.0
88.4/102.0
104.2/120.3
16.7
19.8
39.7
50.2
60.1
16.7
19.8
39.7
50.2
60.1
16.7
19.8
39.7
50.2
60.1
20.4
40.9
61.3
20.4
40.9
61.3
20.4
40.9
61.3
MCA
62/62
62/62
62/62
94/107
121/138
141/131
64
64/64
64/64
97/110
124/141
144/134
67/66
67/66
67/66
101/113
128/144
148/137
31
31
31
55
68
66
32
32
32
57
70
67
33
33
33
58
71
69
23
29
55
65
23
29
55
65
26
33
59
69
MAX
FUSE or
HACR
BRKR
80/80
80/80
80/80
100/110
125/150
150/150
80
80/80
80/80
100/110
125/150
150/150
80/80
80/80
80/80
110/125
150/150
150/150
40
40
40
60
70
70
40
40
40
60
70
80
40
40
40
60
80
80
30
30
60
70
30
30
60
70
30
35
60
80
w/ P.E. (pwrd fr/unit)
DISC. SIZE
FLA
64/64
64/64
64/64
86/98
111/127
129/148
67
67/67
67/67
89/101
114/129
132/151
70/69
70/69
70/69
92/103
117/132
135/153
32
32
32
50
63
74
33
33
33
52
64
75
34
34
34
53
65
76
23
27
50
74
23
27
50
74
27
30
53
77
LRA
376
376/376
376/376
376/376
376/376
376/376
390
390/390
390/390
390/390
390/390
390/390
392
392/392
392/392
392/392
392/392
392/392
189
189
189
189
189
189
196
196
196
196
196
196
197
197
197
197
197
197
142
142
142
142
142
142
142
142
156
156
156
156
MCA
66/66
66/66
66/66
99/112
126/143
146/136
68
68/68
68/68
102/115
129/146
149/139
71/70
71/70
71/70
106/117
133/149
152/141
33
33
33
58
71
68
34
34
34
59
72
69
35
35
35
60
73
71
27
34
60
70
27
34
60
70
29
38
63
74
MAX
FUSE or
HACR
BRKR
80/80
80/80
80/80
100/125
150/150
150/150
80
80/80
80/80
110/125
150/150
150/150
80/80
80/80
80/80
110/125
150/150
175/175
40
40
40
60
80
80
40
40
40
60
80
80
40
40
40
60
80
80
30
35
60
80
30
35
60
80
35
40
70
80
DISC. SIZE
FLA
69/69
69/69
69/69
91/102
116/131
134/152
71
71/71
71/71
93/105
118/134
136/155
75/74
75/74
75/74
97/108
122/136
140/157
34
34
34
53
65
76
35
35
35
54
66
77
36
36
36
55
67
79
28
31
55
78
28
31
55
78
31
34
58
81
LRA
380
380/380
380/380
380/380
380/380
380/380
394
394/394
394/394
394/394
394/394
394/394
396
396/396
396/396
396/396
396/396
396/396
191
191
191
191
191
191
198
198
198
198
198
198
199
199
199
199
199
199
146
146
146
146
146
146
146
146
160
160
160
160
116
ELECTRICAL INFORMATION
(UNITS PRODUCED ON OR AFTER JULY 30, 2012) cont.
Table 36 − UNIT WIRE/FUSE OR HACR BREAKER SIZING DATA (cont.)
UNIT
NO M. V-Ph-HZ
ELEC. HTR
IFM
TYPE
208/230-3-60
STD
MED
HIGH
460-3-60
STD
RAS180
MED
HIGH
575-3-60
STD
MED
HIGH
117
NO C.O. or UNPWR C.O.
NO P.E.
CRHEATER***A00
NONE
Nom
(kW)
-
FLA
-
MCA
70/70
MAX
FUSE or
HACR
BRKR
80/80
291A
12.4/16.5
34.4/39.7
70/70
80/80
w/ P.E. (pwrd fr/unit)
MCA
73/73
MAX
FUSE or
HACR
BRKR
80/80
77/77
416
412/412
73/73
80/80
77/77
416/416
DISC. SIZE
FLA
LRA
72/72
412
72/72
DISC. SIZE
FLA
LRA
294A
25.2/33.5
69.9/80.6
98/112
100/125
90/102
412/412
103/116
110/125
94/107
416/416
288A+294A
32.7/43.5
90.7/104.7
124/142
125/150
114/130
412/412
129/146
150/150
118/134
416/416
291A+294A
37.6/50.0
104.3/120.3
141/131
150/150
130/148
412/412
146/136
150/150
134/152
416/416
294A+294A
50.3/67.0
139.7/161.2
151/172
175/200
170/195
412/412
155/177
175/200
175/199
416/416
NONE
-
-
72
80
75
426
76
100
79
430
291A
12.4/16.5
34.4/39.7
72/72
80/80
75/75
426/426
76/76
100/100
79/79
430/430
294A
25.2/33.5
69.9/80.6
101/114
110/125
93/105
426/426
106/119
110/125
97/109
430/430
288A+294A
32.7/43.5
90.7/104.7
127/145
150/150
116/133
426/426
132/149
150/150
121/137
430/430
291A+294A
37.6/50.0
104.3/120.3
144/134
150/150
132/151
426/426
149/139
150/150
137/155
430/430
294A+294A
50.3/67.0
139.7/161.2
153/175
175/200
173/198
426/426
158/180
175/200
177/202
430/430
NONE
-
-
82
100
86
432
85
100
91
436
291A
12.4/16.5
34.4/39.7
82/82
100/100
86/86
432/432
85/85
100/100
91/91
436/436
294A
25.2/33.5
69.9/80.6
113/127
125/150
104/116
432/432
118/131
125/150
108/121
436/436
288A+294A
32.7/43.5
90.7/104.7
139/157
150/175
128/144
432/432
144/162
150/175
132/148
436/436
291A+294A
37.6/50.0
104.3/120.3
156/146
175/175
143/162
432/432
161/151
175/175
148/166
436/436
294A+294A
50.3/67.0
139.7/161.2
166/187
175/225
184/209
432/432
170/192
175/225
188/213
436/436
NONE
-
-
35
45
36
242
37
45
38
244
292A
16.5
19.9
35
45
36
242
37
45
38
244
295A
33.5
40.3
56
60
51
242
58
60
53
244
289A+295A
43.5
52.3
71
80
65
242
73
80
67
244
292A+295A
50.0
60.2
66
70
74
242
68
80
76
244
295A+295A
67.0
80.6
86
100
98
242
89
100
100
244
NONE
-
-
36
45
38
249
38
50
40
251
292A
16.5
19.9
36
45
38
249
38
50
40
251
295A
33.5
40.3
57
60
52
249
60
60
55
251
289A+295A
43.5
52.3
72
80
66
249
75
80
68
251
292A+295A
50.0
60.2
67
80
75
249
70
80
77
251
295A+295A
67.0
80.6
88
100
99
249
90
100
101
251
NONE
-
-
41
50
43
252
43
50
45
254
292A
16.5
19.9
41
50
43
252
43
50
45
254
295A
33.5
40.3
64
70
58
252
66
70
60
254
289A+295A
43.5
52.3
79
80
72
252
81
90
74
254
292A+295A
50.0
60.2
73
80
81
252
76
80
83
254
295A+295A
67.0
80.6
94
100
104
252
96
100
106
254
NONE
-
-
27
30
28
184
31
40
32
188
293A
16.5
15.9
27
30
28
184
31
40
32
188
296A
33.5
32.2
44
45
40
184
49
50
45
188
290A+296A
43.5
41.8
56
60
51
184
61
70
56
188
293A+296A
50.0
48.1
52
60
59
184
57
60
63
188
296A+296A
67.0
64.4
68
80
77
184
73
80
82
188
NONE
-
-
27
30
28
184
31
40
32
188
293A
16.5
15.9
27
30
28
184
31
40
32
188
296A
33.5
32.2
44
45
40
184
49
50
45
188
290A+296A
43.5
41.8
56
60
51
184
61
70
56
188
293A+296A
50.0
48.1
52
60
59
184
57
60
63
188
296A+296A
67.0
64.4
68
80
77
184
73
80
82
188
NONE
-
-
33
40
35
196
37
45
39
200
293A
16.5
15.9
33
40
35
196
37
45
39
200
296A
33.5
32.2
52
60
47
196
57
60
52
200
290A+296A
43.5
41.8
64
70
58
196
69
70
63
200
293A+296A
50.0
48.1
60
70
66
196
65
70
70
200
296A+296A
67.0
64.4
76
80
84
196
81
90
89
200
513 31 3209 02
ELECTRICAL INFORMATION
(UNITS PRODUCED ON OR AFTER JULY 30, 2012) cont.
UNIT
NO M. V-Ph-HZ
Table 37 – UNIT WIRE/FUSE OR HACR BREAKER SIZING DATA WITH 2 SPEED INDOOR FAN MOTOR
ELEC. HTR
NO P.E.
IFM
TYPE
208/230-3-60
STD
MED
HIGH
STD
460-3-60
RAS090
MED
HIGH
STD
575-3-60
NO C.O. or UNPWR C.O.
MED
HIGH
513 31 3209 02
CRHEATER***A00
NONE
117A
110A
111A
112A
112A+117A
NONE
117A
110A
111A
112A
112A+117A
NONE
117A
110A
111A
112A
112A+117A
NONE
116A
113A
114A
115A
114A+116A
NONE
116A
113A
114A
115A
114A+116A
NONE
116A
113A
114A
115A
114A+116A
NONE
118A
119A
NONE
118A
119A
NONE
118A
119A
Nom
(kW)
7.8/10.4
12.0/16.0
18.6/24.8
24.0/32.0
31.8/42.4
7.8/10.4
12.0/16.0
18.6/24.8
24.0/32.0
31.8/42.4
7.8/10.4
12.0/16.0
18.6/24.8
24.0/32.0
31.8/42.4
13.9
16.5
27.8
33.0
41.7
13.9
16.5
27.8
33.0
41.7
13.9
16.5
27.8
33.0
41.7
17.0
34.0
17.0
34.0
17.0
34.0
FLA
21.7/25.0
33.4/38.5
51.7/59.7
66.7/77.0
88.4/102.0
21.7/25.0
33.4/38.5
51.7/59.7
66.7/77.0
88.4/102.0
21.7/25.0
33.4/38.5
51.7/59.7
66.7/77.0
88.4/102.0
16.7
19.8
33.4
39.7
50.2
16.7
19.8
33.4
39.7
50.2
16.7
19.8
33.4
39.7
50.2
20.4
40.9
20.4
40.9
20.4
40.9
MCA
40/40
40/40
49/56
72/82
91/104
118/135
43/42
43/42
53/58
76/85
95/106
122/138
48/47
48/48
59/64
82/91
101/113
128/144
19
25
29
46
54
67
20
26
30
47
55
68
22
29
33
50
58
71
14
29
55
16
32
57
18
34
59
MAX
FUSE or
HACR
BRKR
50/50
50/50
50/60
80/90
100/110
125/150
50/50
50/50
60/60
80/90
100/110
125/150
60/50
60/50
60/70
90/100
110/125
150/150
20
25
30
50
60
70
25
30
30
50
60
70
25
30
35
50
60
80
15
30
60
20
35
60
20
35
60
w/ P.E. (pwrd fr/unit)
DISC. SIZE
FLA
41/41
41/41
45/51
66/75
83/95
108/124
45/44
45/44
48/53
69/78
87/98
112/126
50/49
50/49
54/59
75/83
92/103
117/132
19
23
26
42
49
61
20
24
27
43
50
62
23
27
30
46
53
65
14
27
50
16
29
52
18
31
54
LRA
197
197/197
197/197
197/197
197/197
197/197
227
227/227
227/227
227/227
227/227
227/227
262
262/262
262/262
262/262
262/262
262/262
97
97
97
97
97
97
113
113
113
113
113
113
130
130
130
130
130
130
79
79
79
92
92
92
106
106
106
MCA
44/43
44/43
54/60
77/87
96/108
123/140
46/46
46/46
58/63
81/90
99/111
126/142
51/51
51/52
64/69
87/96
106/117
133/149
20
27
31
48
56
69
21
28
32
49
57
70
24
32
35
52
60
73
18
34
60
19
36
62
22
38
64
MAX
FUSE or
HACR
BRKR
50/50
50/50
60/60
80/90
100/110
125/150
50/50
50/50
60/70
90/90
100/125
150/150
60/60
60/60
70/70
90/100
110/125
150/150
25
30
35
50
60
70
25
30
35
50
60
70
30
35
35
60
60
80
20
35
60
25
40
70
25
40
70
DISC. SIZE
FLA
46/46
46/46
49/55
70/79
88/99
113/128
49/48
49/48
53/58
74/82
91/102
116/131
55/54
55/54
58/63
79/88
97/108
122/136
21
25
28
44
51
63
22
26
29
45
52
64
25
29
32
48
55
67
19
31
55
21
33
57
23
35
59
LRA
201
201/201
201/201
201/201
201/201
201/201
231
231/231
231/231
231/231
231/231
231/231
266
266/266
266/266
266/266
266/266
266/266
99
99
99
99
99
99
115
115
115
115
115
115
132
132
132
132
132
132
83
83
83
96
96
96
110
110
110
118
ELECTRICAL INFORMATION
(UNITS PRODUCED ON OR AFTER JULY 30, 2012) cont.
Table 37 − UNIT WIRE/FUSE OR HACR BREAKER SIZING DATA WITH 2 SPEED INDOOR FAN MOTOR (cont.)
UNIT
NO M. V-Ph-HZ
ELEC. HTR
NO P.E.
IFM
TYPE
208/230-3-60
460-3-60
FLA
LRA
50/50
50/50
50/60
80/90
100/110
125/150
43/42
43/42
45/51
66/75
83/95
108/124
212
212/212
212/212
212/212
212/212
212/212
MCA
45/45
45/45
54/60
77/87
96/108
123/140
DISC. SIZE
MAX
FUSE or
HACR
BRKR
FLA
LRA
50/50
50/50
60/60
80/90
100/110
125/150
47/47
47/47
49/55
70/79
88/99
113/128
216
216/216
216/216
216/216
216/216
216/216
DISC. SIZE
7.8/10.4
12.0/16.0
18.6/24.8
24.0/32.0
31.8/42.4
FLA
21.7/25.0
33.4/38.5
51.7/59.7
66.7/77.0
88.4/102.0
MCA
41/41
41/41
49/56
72/82
91/104
118/135
MED
NONE
117A
110A
111A
112A
112A+117A
7.8/10.4
12.0/16.0
18.6/24.8
24.0/32.0
31.8/42.4
21.7/25.0
33.4/38.5
51.7/59.7
66.7/77.0
88.4/102.0
42/42
42/42
51/57
74/84
93/105
120/136
50/50
50/50
60/60
80/90
100/110
125/150
44/44
44/44
47/52
68/76
85/96
110/125
216
216/216
216/216
216/216
216/216
216/216
46/46
46/46
56/62
79/88
97/110
125/141
60/50
60/50
60/70
80/90
100/110
125/150
48/48
48/48
51/56
72/81
89/101
114/129
220
220/220
220/220
220/220
220/220
220/220
HIGH
NONE
117A
110A
111A
112A
112A+117A
7.8/10.4
12.0/16.0
18.6/24.8
24.0/32.0
31.8/42.4
21.7/25.0
33.4/38.5
51.7/59.7
66.7/77.0
88.4/102.0
46/45
46/45
56/61
79/87
97/109
124/140
60/50
60/50
60/70
80/90
100/110
125/150
48/47
48/47
51/56
72/80
89/100
114/129
266
266/266
266/266
266/266
266/266
266/266
50/49
50/49
60/66
83/92
102/114
129/145
60/60
60/60
60/70
90/100
110/125
150/150
53/52
53/52
55/60
76/84
93/104
118/133
270
270/270
270/270
270/270
270/270
270/270
STD
NONE
116A
113A
114A
115A
114A+116A
13.9
16.5
27.8
33.0
41.7
16.7
19.8
33.4
39.7
50.2
19
25
29
46
54
67
25
25
30
50
60
70
20
23
26
42
49
61
111
111
111
111
111
111
21
27
31
48
56
69
25
30
35
50
60
70
22
25
28
44
51
63
113
113
113
113
113
113
MED
NONE
116A
113A
114A
115A
114A+116A
13.9
16.5
27.8
33.0
41.7
16.7
19.8
33.4
39.7
50.2
20
26
30
47
55
68
25
30
30
50
60
70
21
24
27
43
50
62
114
114
114
114
114
114
22
28
32
49
57
70
25
30
35
50
60
70
23
26
29
45
52
64
116
116
116
116
116
116
HIGH
NONE
116A
113A
114A
115A
114A+116A
13.9
16.5
27.8
33.0
41.7
16.7
19.8
33.4
39.7
50.2
21
27
31
48
56
69
25
30
35
50
60
70
22
25
28
44
51
63
139
139
139
139
139
139
23
30
34
51
58
72
25
30
35
60
60
80
24
27
30
46
53
65
141
141
141
141
141
141
STD
NONE
118A
119A
17.0
34.0
20.4
40.9
17
29
55
20
30
60
17
27
50
87
87
87
21
34
60
25
35
60
21
31
55
91
91
91
MED
NONE
118A
119A
17.0
34.0
20.4
40.9
17
30
56
20
30
60
18
27
51
91
91
91
21
35
61
25
35
70
22
32
55
95
95
95
HIGH
NONE
118A
119A
17.0
34.0
20.4
40.9
18
32
57
20
35
60
19
29
52
100
100
100
22
36
62
25
40
70
23
33
57
104
104
104
RAS102
575-3-60
Nom
(kW)
w/ P.E. (pwrd fr/unit)
MAX
FUSE or
HACR
BRKR
CRHEATER***A00
NONE
117A
110A
111A
112A
112A+117A
STD
119
NO C.O. or UNPWR C.O.
513 31 3209 02
ELECTRICAL INFORMATION
(UNITS PRODUCED ON OR AFTER JULY 30, 2012) cont.
Table 37 − UNIT WIRE/FUSE OR HACR BREAKER SIZING DATA WITH 2 SPEED INDOOR FAN MOTOR (cont.)
UNIT
NO M. V-Ph-HZ
ELEC. HTR
IFM
TYPE
208/230-3-60
STD
MED
HIGH
STD
460-3-60
RAS120
MED
HIGH
STD
575-3-60
NO C.O. or UNPWR C.O.
NO P.E.
MED
HIGH
513 31 3209 02
CRHEATER***A00
NONE
117A
110A
112A
112A+117A
112A+110A
NONE
117A
110A
112A
112A+117A
112A+110A
NONE
117A
110A
112A
112A+117A
112A+110A
NONE
116A
113A
115A
114A+116A
115A+113A
NONE
116A
113A
115A
114A+116A
115A+113A
NONE
116A
113A
115A
114A+116A
115A+113A
NONE
118A
119A
118A+119A
NONE
118A
119A
118A+119A
NONE
118A
119A
118A+119A
Nom
(kW)
7.8/10.4
12.0/16.0
24.0/32.0
31.8/42.4
37.6/50.0
7.8/10.4
12.0/16.0
24.0/32.0
31.8/42.4
37.6/50.0
7.8/10.4
12.0/16.0
24.0/32.0
31.8/42.4
37.6/50.0
13.9
16.5
33.0
41.7
50.0
13.9
16.5
33.0
41.7
50.0
13.9
16.5
33.0
41.7
50.0
17.0
34.0
51.0
17.0
34.0
51.0
17.0
34.0
51.0
FLA
21.7/25.0
33.4/38.5
66.7/77.0
88.4/102.0
104.2/120.3
21.7/25.0
33.4/38.5
66.7/77.0
88.4/102.0
104.2/120.3
21.7/25.0
33.4/38.5
66.7/77.0
88.4/102.0
104.2/120.3
16.7
19.8
39.7
50.2
60.1
16.7
19.8
39.7
50.2
60.1
16.7
19.8
39.7
50.2
60.1
20.4
40.9
61.3
20.4
40.9
61.3
20.4
40.9
61.3
MCA
46/46
46/46
51/57
93/105
120/136
140/129
50/49
50/49
56/61
97/109
124/140
144/133
53/52
53/52
59/64
101/113
128/144
148/137
23
26
30
55
68
65
24
27
31
56
69
67
26
29
33
58
71
69
18
30
56
66
19
32
57
67
21
34
59
70
MAX
FUSE or
HACR
BRKR
60/60
60/60
60/60
100/110
125/150
150/150
60/60
60/60
60/70
100/110
125/150
150/150
60/60
60/60
60/70
110/125
150/150
150/150
30
30
30
60
70
70
30
30
35
60
70
80
30
30
35
60
80
80
20
30
60
70
25
35
60
80
25
35
60
80
w/ P.E. (pwrd fr/unit)
DISC. SIZE
FLA
48/47
48/47
48/52
85/96
110/125
128/146
52/51
52/51
52/56
89/100
114/129
132/150
55/54
55/54
55/59
92/103
117/132
135/153
24
24
27
50
62
73
25
25
28
51
63
75
27
27
30
53
65
76
19
27
51
75
20
29
52
76
22
31
54
78
LRA
255
255/255
255/255
255/255
255/255
255/255
305
305/305
305/305
305/305
305/305
305/305
316
316/316
316/316
316/316
316/316
316/316
122
122
122
122
122
122
147
147
147
147
147
147
152
152
152
152
152
152
95
95
95
95
104
104
104
104
118
118
118
118
MCA
50/50
50/50
56/62
97/110
125/141
144/134
54/53
54/53
60/66
102/114
129/145
149/138
56/55
56/55
64/69
106/117
133/149
152/141
25
28
32
57
70
68
26
30
34
58
72
69
28
32
35
60
73
71
22
35
61
71
23
36
62
72
25
38
64
74
MAX
FUSE or
HACR
BRKR
60/60
60/60
60/70
100/110
125/150
150/150
60/60
60/60
60/70
110/125
150/150
150/150
60/60
60/60
70/70
110/125
150/150
175/175
30
30
35
60
70
80
30
30
35
60
80
80
30
35
35
60
80
80
25
35
70
80
25
40
70
80
30
40
70
80
DISC. SIZE
FLA
52/52
52/52
52/56
89/101
114/129
132/151
56/55
56/55
56/60
93/104
118/133
137/154
60/59
60/59
60/63
97/108
122/136
140/157
26
26
29
52
64
76
27
27
30
53
65
77
29
29
32
55
67
79
23
32
55
79
24
33
57
80
26
35
59
82
LRA
259
259/259
259/259
259/259
259/259
259/259
309
309/309
309/309
309/309
309/309
309/309
320
320/320
320/320
320/320
320/320
320/320
124
124
124
124
124
124
149
149
149
149
149
149
154
154
154
154
154
154
99
99
99
99
108
108
108
108
122
122
122
122
120
ELECTRICAL INFORMATION
(UNITS PRODUCED ON OR AFTER JULY 30, 2012) cont.
Table 37 − UNIT WIRE/FUSE OR HACR BREAKER SIZING DATA WITH 2 SPEED INDOOR FAN MOTOR (cont.)
UNIT
NO M. V-Ph-HZ
ELEC. HTR
IFM
TYPE
208/230-3-60
STD
MED
HIGH
STD
460-3-60
RAS150
MED
HIGH
575-3-60
STD
MED
HIGH
121
NO C.O. or UNPWR C.O.
NO P.E.
CRHEATER***A00
NONE
117A
110A
112A
112A+117A
112A+110A
NONE
117A
110A
112A
112A+117A
112A+110A
NONE
117A
110A
112A
112A+117A
112A+110A
NONE
116A
113A
115A
114A+116A
115A+113A
NONE
116A
113A
115A
114A+116A
115A+113A
NONE
116A
113A
115A
114A+116A
115A+113A
NONE
118A
119A
118A+119A
NONE
118A
119A
118A+119A
NONE
118A
119A
118A+119A
Nom
(kW)
7.8/10.4
12.0/16.0
24.0/32.0
31.8/42.4
37.6/50.0
7.8/10.4
12.0/16.0
24.0/32.0
31.8/42.4
37.6/50.0
7.8/10.4
12.0/16.0
24.0/32.0
31.8/42.4
37.6/50.0
13.9
16.5
33.0
41.7
50.0
13.9
16.5
33.0
41.7
50.0
13.9
16.5
33.0
41.7
50.0
17.0
34.0
51.0
17.0
34.0
51.0
17.0
34.0
51.0
FLA
21.7/25.0
33.4/38.5
66.7/77.0
88.4/102.0
104.2/120.3
21.7/25.0
33.4/38.5
66.7/77.0
88.4/102.0
104.2/120.3
21.7/25.0
33.4/38.5
66.7/77.0
88.4/102.0
104.2/120.3
16.7
19.8
39.7
50.2
60.1
16.7
19.8
39.7
50.2
60.1
16.7
19.8
39.7
50.2
60.1
20.4
40.9
61.3
20.4
40.9
61.3
20.4
40.9
61.3
MCA
62/61
62/61
62/61
95/106
122/138
141/131
64/63
64/63
64/63
97/109
124/140
144/133
67/66
67/66
67/66
101/113
128/144
148/137
30
30
30
55
68
65
31
31
31
56
69
67
33
33
33
58
71
69
24
32
57
67
24
32
57
67
26
34
59
70
MAX
FUSE or
HACR
BRKR
80/80
80/80
80/80
100/110
125/150
150/150
80/80
80/80
80/80
100/110
125/150
150/150
80/80
80/80
80/80
110/125
150/150
150/150
40
40
40
60
70
70
40
40
40
60
70
80
40
40
40
60
80
80
30
35
60
80
30
35
60
80
30
35
60
80
w/ P.E. (pwrd fr/unit)
DISC. SIZE
FLA
65/64
65/64
65/64
87/98
112/126
130/147
67/66
67/66
67/66
89/100
114/129
132/150
70/69
70/69
70/69
92/103
117/132
135/153
31
31
31
50
62
73
33
33
33
51
63
75
34
34
34
53
65
76
25
29
52
76
25
29
52
76
27
31
54
78
LRA
357
357/357
357/357
357/357
357/357
357/357
381
381/381
381/381
381/381
381/381
381/381
392
392/392
392/392
392/392
392/392
392/392
180
180
180
180
180
180
192
192
192
192
192
192
197
197
197
197
197
197
142
142
142
142
142
142
142
142
156
156
156
156
MCA
66/65
66/65
66/65
99/111
126/142
146/135
68/67
68/67
68/67
102/114
129/145
149/138
71/70
71/70
71/70
106/117
133/149
152/141
32
32
32
57
70
68
33
33
34
58
72
69
35
35
35
60
73
71
28
36
62
72
28
36
62
72
30
38
64
74
MAX
FUSE or
HACR
BRKR
80/80
80/80
80/80
100/125
150/150
150/150
80/80
80/80
80/80
110/125
150/150
150/150
80/80
80/80
80/80
110/125
150/150
175/175
40
40
40
60
70
80
40
40
40
60
80
80
40
40
40
60
80
80
30
40
70
80
30
40
70
80
35
40
70
80
DISC. SIZE
FLA
69/68
69/68
69/68
91/102
116/131
134/152
72/70
72/70
72/70
93/104
118/133
137/154
75/74
75/74
75/74
97/108
122/136
140/157
33
33
33
52
64
76
35
35
35
53
65
77
36
36
36
55
67
79
30
33
57
80
30
33
57
80
32
35
59
82
LRA
361
361/361
361/361
361/361
361/361
361/361
385
385/385
385/385
385/385
385/385
385/385
396
396/396
396/396
396/396
396/396
396/396
182
182
182
182
182
182
194
194
194
194
194
194
199
199
199
199
199
199
146
146
146
146
146
146
146
146
160
160
160
160
513 31 3209 02
ELECTRICAL INFORMATION
(UNITS PRODUCED ON OR AFTER JULY 30, 2012) cont.
Table 37 − UNIT WIRE/FUSE OR HACR BREAKER SIZING DATA WITH 2 SPEED INDOOR FAN MOTOR (cont.)
UNIT
NO M. V-Ph-HZ
ELEC. HTR
IFM
TYPE
208/230-3-60
STD
MED
HIGH
460-3-60
STD
RAS180
MED
HIGH
STD
575-3-60
NO C.O. or UNPWR C.O.
NO P.E.
MED
HIGH
513 31 3209 02
CRHEATER***A00
NONE
Nom
(kW)
-
FLA
-
MCA
70/69
MAX
FUSE or
HACR
BRKR
80/80
291A
12.4/16.5
34.4/39.7
70/69
80/80
w/ P.E. (pwrd fr/unit)
MCA
74/73
MAX
FUSE or
HACR
BRKR
80/80
77/76
397
393/393
74/73
80/80
77/76
397/397
DISC. SIZE
FLA
LRA
73/72
393
73/72
DISC. SIZE
FLA
LRA
294A
25.2/33.5
69.9/80.6
99/111
100/125
90/102
393/393
103/116
110/125
95/106
397/397
288A+294A
32.7/43.5
90.7/104.7
125/141
125/150
114/129
393/393
129/146
150/150
119/134
397/397
291A+294A
37.6/50.0
104.3/120.3
142/131
150/150
130/147
393/393
146/135
150/150
134/152
397/397
294A+294A
50.3/67.0
139.7/161.2
151/171
175/200
171/194
393/393
156/176
175/200
175/199
397/397
NONE
-
-
72/71
80/80
75/74
417
76/75
100/90
79/78
421
291A
12.4/16.5
34.4/39.7
72/71
80/80
75/74
417/417
76/75
100/90
79/78
421/421
294A
25.2/33.5
69.9/80.6
101/113
110/125
93/104
417/417
106/118
110/125
97/108
421/421
288A+294A
32.7/43.5
90.7/104.7
127/144
150/150
117/132
417/417
132/148
150/150
121/136
421/421
291A+294A
37.6/50.0
104.3/120.3
144/133
150/150
132/150
417/417
149/138
150/150
137/154
421/421
294A+294A
50.3/67.0
139.7/161.2
154/174
175/200
173/197
417/417
158/179
175/200
177/201
421/421
NONE
-
-
82
100
86
432
85
100
91
436
291A
12.4/16.5
34.4/39.7
82/82
100/100
86/86
432/432
85/85
100/100
91/91
436/436
294A
25.2/33.5
69.9/80.6
113/127
125/150
104/116
432/432
118/131
125/150
108/121
436/436
288A+294A
32.7/43.5
90.7/104.7
139/157
150/175
128/144
432/432
144/162
150/175
132/148
436/436
291A+294A
37.6/50.0
104.3/120.3
156/146
175/175
143/162
432/432
161/151
175/175
148/166
436/436
294A+294A
50.3/67.0
139.7/161.2
166/187
175/225
184/209
432/432
170/192
175/225
188/213
436/436
NONE
-
-
35
45
36
233
37
45
38
235
292A
16.5
19.9
35
45
36
233
37
45
38
235
295A
33.5
40.3
56
60
51
233
58
60
53
235
289A+295A
43.5
52.3
71
80
65
233
73
80
67
235
292A+295A
50.0
60.2
65
70
74
233
68
80
76
235
295A+295A
67.0
80.6
86
90
97
233
88
100
99
235
NONE
-
-
36
45
37
245
38
50
39
247
292A
16.5
19.9
36
45
37
245
38
50
39
247
295A
33.5
40.3
57
60
52
245
59
60
54
247
289A+295A
43.5
52.3
72
80
66
245
74
80
68
247
292A+295A
50.0
60.2
67
80
75
245
69
80
77
247
295A+295A
67.0
80.6
87
100
98
245
89
100
100
247
NONE
-
-
41
50
43
252
43
50
45
254
292A
16.5
19.9
41
50
43
252
43
50
45
254
295A
33.5
40.3
64
70
58
252
66
70
60
254
289A+295A
43.5
52.3
79
80
72
252
81
90
74
254
292A+295A
50.0
60.2
73
80
81
252
76
80
83
254
295A+295A
67.0
80.6
94
100
104
252
96
100
106
254
NONE
-
-
29
35
30
184
32
40
34
188
293A
16.5
15.9
29
35
30
184
32
40
34
188
296A
33.5
32.2
46
50
42
184
51
60
47
188
290A+296A
43.5
41.8
58
60
53
184
63
70
58
188
293A+296A
50.0
48.1
54
60
60
184
59
60
65
188
296A+296A
67.0
64.4
70
80
79
184
75
80
84
188
NONE
-
-
29
35
30
184
32
40
34
188
293A
16.5
15.9
29
35
30
184
32
40
34
188
296A
33.5
32.2
46
50
42
184
51
60
47
188
290A+296A
43.5
41.8
58
60
53
184
63
70
58
188
293A+296A
50.0
48.1
54
60
60
184
59
60
65
188
296A+296A
67.0
64.4
70
80
79
184
75
80
84
188
NONE
-
-
33
40
35
196
37
45
39
200
293A
16.5
15.9
33
40
35
196
37
45
39
200
296A
33.5
32.2
52
60
47
196
57
60
52
200
290A+296A
43.5
41.8
64
70
58
196
69
70
63
200
293A+296A
50.0
48.1
60
70
66
196
65
70
70
200
296A+296A
67.0
64.4
76
80
84
196
81
90
89
200
122
ELECTRICAL INFORMATION
(UNITS PRODUCED ON OR AFTER JULY 30, 2012) cont.
LEGEND:
BRKR
- Circuit breaker
CO
- Convenience outlet
DISC
- Disconnect
FLA
- Full load amps
IFM
- Indoor fan motor
LRA
- Locked rotor amps
MCA
- Minimum circuit amps
MOCP
- MAX FUSE or HACR Breaker
PE
- Power exhaust
PWRD CO
- Powered convenient outlet
UNPWR CO
- Unpowered convenient outlet
NOTES:
1. In compliance with NEC requirements for multimotor and com
ment (refer to NEC Articles 430 and 440), the overcurrent protecti
shall be fuse or HACR breaker. Canadian units may be fuse or ci
2. Unbalanced 3‐Phase Supply Voltage
Never operate a motor where a phase imbalance in supply voltag
Use the following formula to determine the percentage of voltage
max voltage deviation from average voltage
% Voltage Imbalance
= 100 x
average voltage
123
Example: Supply voltage is 230‐3‐60
AB = 224 v
BC = 231 v
AC = 226 v
Average Voltage =
=
(224 + 231 + 226)
3
227
681
3
=
Determine maximum deviation from average voltage.
(AB) 227 – 224 = 3 v
(BC) 231 – 227 = 4 v
(AC) 227 – 226 = 1 v
Maximum deviation is 4 v.
Determine percent of voltage imbalance.
% Voltage Imbalance
= 100 x
4
227
= 1.76%
This amount of phase imbalance is satisfactory as it is below the maxim­
um allowable 2%.
IMPORTANT: If the supply voltage phase imbalance is more than 2%,
contact your local electric utility company immediately.
513 31 3209 02
ELECTRICAL DATA FOR UNITS
PRODUCED PRIOR TO JULY 30, 2012
NOTE: Check the serial number of unit to verify production date.
SERIAL NUMBER
1
2
3
4
5
6
7
8
9
10
U
1
2
3
1
1
2
3
4
5
Manufacture Location
Week of Manufacture
(fiscal calendar)
Sequence Number
Year of Manufacture
(12 = 2012)
513 31 3209 02
124
ELECTRICAL INFORMATION
(UNITS PRODUCED PRIOR TO JULY 30, 2012)
Table 38 – RAS036
1−STAGE COOLING WITH 1−SPEED INDOOR FAN MOTOR
V-Ph-Hz
VOLTAGE
RANGE
MIN
MAX
RLA
LRA
WATTS
FLA
208-1-60
187
253
16.6
79
325
1.5
230-1-60
187
253
16.6
79
325
1.5
208-3-60
187
253
10.4
73
325
1.5
230-3-60
187
253
10.4
73
325
1.5
460-3-60
414
506
5.8
38
325
0.8
575-3-60
518
633
3.8
37
325
0.6
COMP (ea)
3 TONS
OFM (ea)
IFM
TYPE
STD
MED
STD
MED
STD
MED
HIGH
STD
MED
HIGH
STD
MED
HIGH
STD
MED
HIGH
EFF at
Full Load
70%
70%
70%
70%
70%
70%
80%
70%
70%
80%
70%
70%
80%
71%
71%
80%
Table 38 (cont.) − RAS048 1−STAGE COOLING WITH 1−SPEED INDOOR FAN MOTOR
V-Ph-Hz
VOLTAGE
RANGE
MIN
MAX
RLA
LRA
WATTS
FLA
208-1-60
187
253
21.8
117
325
1.5
230-1-60
187
253
21.8
117
325
1.5
208-3-60
187
253
13.7
83
325
1.5
230-3-60
187
253
13.7
83
325
1.5
460-3-60
414
506
6.2
41
325
0.8
575-3-60
518
633
4.8
37
325
0.6
COMP (ea)
OFM (ea)
IFM
V-Ph-Hz
VOLTAGE
RANGE
MIN
MAX
RLA
LRA
WATTS
FLA
208-1-60
187
253
26.2
134
325
1.5
230-1-60
187
253
26.2
134
325
1.5
208-3-60
187
253
15.6
110
325
1.5
230-3-60
187
253
15.6
110
325
1.5
460-3-60
414
506
7.7
52
325
0.8
575-3-60
518
633
5.8
39
325
0.6
125
4.9
4.9
4.9
4.9
4.9
4.9
5.2
4.9
4.9
5.2
2.1
2.1
2.6
1.9
1.9
2.0
4 TONS
TYPE
STD
MED
STD
MED
STD
MED
HIGH
STD
MED
HIGH
STD
MED
HIGH
STD
MED
HIGH
EFF at
Full Load
70%
78%
70%
78%
70%
70%
80%
70%
70%
80%
70%
70%
80%
71%
71%
80%
Table 38 (cont.) − RAS060 1−STAGE COOLING WITH 1−SPEED INDOOR FAN MOTOR
COMP (ea)
FLA
OFM (ea)
FLA
4.9
7.0
4.9
7.0
4.9
4.9
5.2
4.9
4.9
5.2
2.1
2.1
2.6
1.9
2.1
2.0
5 TONS
IFM
TYPE
STD
MED
STD
MED
STD
MED
HIGH
STD
MED
HIGH
STD
MED
HIGH
STD
MED
HIGH
EFF at
Full Load
70%
78%
70%
78%
70%
80%
81%
70%
80%
81%
70%
80%
81%
71%
81%
81%
FLA
4.9
7.0
4.9
7.0
4.9
5.2
7.5
4.9
5.2
7.5
2.1
2.6
3.4
1.9
2.0
2.8
513 31 3209 02
ELECTRICAL INFORMATION
(UNITS PRODUCED PRIOR TO JULY 30, 2012) cont.
Table 38 (cont.) − RAS072 1−STAGE COOLING WITH 1−SPEED INDOOR FAN MOTOR
VOLTAGE
RANGE
V-Ph-Hz
MIN
208-3-60
253
187
460-3-60
518
123
19.0
506
1.5
1.5
325
50
IFM
FLA
325
62
7.4
WATTS
325
123
9.7
633
OFM (ea)
LRA
19.0
253
414
575-3-60
RLA
MAX
187
230-3-60
COMP (ea)
6 TONS
0.8
325
0.6
TYPE
EFF at
Full Load
FLA
STD
80%
5.2
MED
81%
7.5
HIGH
81%
7.5
STD
80%
5.2
MED
81%
7.5
HIGH
81%
7.5
STD
80%
2.6
MED
81%
3.4
HIGH
81%
4.4
STD
80%
2.0
MED
81%
2.8
HIGH
81%
2.8
Table 38 (cont.) − RAS091 1−STAGE COOLING WITH 1−SPEED INDOOR FAN MOTOR
VOLTAGE
RANGE
V-Ph-Hz
208-3-60
230-3-60
IFM
MIN
MAX
RLA
LRA
WATTS
FLA
TYPE
STD
80%
187
253
25.0
164
325
1.5
MED
81%
7.5
HIGH
81%
15.0
5.2
253
414
575-3-60
OFM (ea)
EFF at
Full Load
187
460-3-60
COMP (ea)
7.5 TONS
25.0
506
518
164
12.2
633
325
100
9.0
1.5
325
78
0.8
325
0.6
VOLTAGE
RANGE
208-3-60
230-3-60
460-3-60
575-3-60
COMP (Cir 1)
COMP (Cir 2)
5.2
STD
80%
MED
81%
7.5
HIGH
81%
15.0
STD
80%
2.6
MED
81%
3.4
HIGH
81%
7.4
STD
80%
2.4
MED
81%
2.8
HIGH
81%
5.6
Table 38 (cont.) − RAS090 2−STAGE COOLING WITH 1−SPEED INDOOR FAN MOTOR
V-Ph-Hz
FLA
7.5 TONS
OFM (ea)
IFM
MIN
MAX
RLA
LRA
RLA
LRA
WATTS
FLA
TYPE
EFF at Full
Load
STD
80%
187
253
13.6
83
13.6
83
325
1.5
MED
81%
7.5
HIGH
81%
15.0
5.2
187
414
518
513 31 3209 02
253
506
633
13.6
6.1
4.2
83
41
33
13.6
6.1
4.2
83
41
33
325
325
325
1.5
0.8
0.6
FLA
5.2
STD
80%
MED
81%
7.5
HIGH
81%
15.0
STD
80%
2.6
MED
81%
3.4
HIGH
81%
7.4
STD
80%
2.4
MED
81%
2.8
HIGH
81%
5.6
126
ELECTRICAL INFORMATION
(UNITS PRODUCED PRIOR TO JULY 30, 2012) cont.
Table 38 (cont.) − RAS090 2−STAGE COOLING WITH 2−SPEED INDOOR FAN MOTOR
VOLTAGE
RANGE
V-Ph-Hz
MIN
208-3-60
253
187
460-3-60
518
13.6
83
6.1
633
RLA
83
13.6
506
COMP 2
LRA
13.6
253
414
575-3-60
RLA
MAX
187
230-3-60
COMP 1
13.6
41
4.2
6.1
33
4.2
7.5 TONS
OFM (ea)
LRA
83
83
41
33
IFM
WATTS
FLA
TYPE
EFF at Full
Load
325
1.5
STD
84%
325
1.5
MED
85%
8.6
325
1.5
HIGH
84%
13.6
325
1.5
STD
84%
5.6
325
1.5
MED
85%
7.8
325
1.5
HIGH
84%
12.7
325
0.8
STD
79%
2.9
325
0.8
MED
85%
3.8
325
0.8
HIGH
84%
6.4
325
0.6
STD
81%
2.8
325
0.6
MED
84%
4.5
325
0.6
HIGH
83%
6.2
Table 38 (cont.) − RAS101 1−STAGE COOLING WITH 1−SPEED INDOOR FAN MOTOR
VOLTAGE
RANGE
V-Ph-Hz
208-3-60
230-3-60
460-3-60
575-3-60
COMP (ea)
OFM (ea)
IFM
MIN
MAX
RLA
LRA
WATTS
FLA
TYPE
EFF at
Full Load
STD
80%
187
253
29.5
195
325
1.5
MED
80%
5.2
HIGH
80%
10.0
5.2
187
253
414
29.5
506
518
195
14.7
633
VOLTAGE
RANGE
V-Ph-Hz
230-3-60
460-3-60
575-3-60
127
5.8
8.5 TONS
325
95
12.2
1.5
325
80
0.8
325
0.6
COMP (Cir 1)
COMP (Cir 2)
FLA
5.2
STD
80%
MED
80%
5.2
HIGH
80%
10.0
STD
80%
2.6
MED
80%
2.6
HIGH
80%
4.4
STD
80%
2.4
MED
80%
2.0
HIGH
81%
2.8
Table 38 (cont.) − RAS102 2−STAGE COOLING WITH 1−SPEED INDOOR FAN MOTOR
208-3-60
FLA
8.5 TONS
OFM (ea)
IFM
MIN
MAX
RLA
LRA
RLA
LRA
WATTS
FLA
TYPE
EFF at Full
Load
STD
80%
187
253
14.5
98
13.7
83
325
1.5
MED
80%
5.2
HIGH
80%
10.0
5.2
187
414
518
253
506
633
14.5
6.3
6.0
98
55
41
13.7
6.2
4.8
83
41
33
325
325
325
1.5
0.8
0.6
FLA
5.2
STD
80%
MED
80%
5.2
HIGH
80%
10.0
STD
80%
2.6
MED
80%
2.6
HIGH
80%
4.4
STD
80%
2.4
MED
80%
2.0
HIGH
81%
2.8
513 31 3209 02
ELECTRICAL INFORMATION
(UNITS PRODUCED PRIOR TO JULY 30, 2012) cont.
Table 38 (cont.) − RAS102 2−STAGE COOLING WITH 2−SPEED INDOOR FAN MOTOR
VOLTAGE
RANGE
V-Ph-Hz
MIN
208-3-60
253
187
460-3-60
518
13.7
98
6.3
633
RLA
98
14.5
506
COMP 2
LRA
14.5
253
414
575-3-60
RLA
MAX
187
230-3-60
COMP 1
13.7
55
6.0
6.2
41
4.8
8.5 TONS
OFM (ea)
LRA
83
83
41
33
IFM
WATTS
FLA
TYPE
EFF at Full
Load
325
1.5
STD
84%
325
1.5
MED
77%
7.1
325
1.5
HIGH
82%
10.8
325
1.5
STD
84%
5.6
325
1.5
MED
77%
6.8
325
1.5
HIGH
82%
9.8
325
0.8
STD
79%
2.9
325
0.8
MED
77%
3.8
325
0.8
HIGH
82%
4.9
325
0.6
STD
81%
2.8
325
0.6
MED
80%
3.5
325
0.6
HIGH
84%
4.5
Table 38 (cont.) − RAS121 1−STAGE COOLING WITH 1−SPEED INDOOR FAN MOTOR
VOLTAGE
RANGE
V-Ph-Hz
208-3-60
230-3-60
10 TONS
OFM (ea)
IFM
MIN
MAX
RLA
LRA
WATTS
FLA
TYPE
STD
80%
5.2
187
253
30.1
225
325
1.5
MED
81%
10.0
HIGH
81%
15.0
STD
80%
5.2
MED
81%
10.0
HIGH
81%
15.0
STD
80%
2.6
MED
81%
4.4
HIGH
81%
7.4
STD
80%
2.0
MED
81%
2.8
HIGH
81%
5.6
253
414
575-3-60
30.1
506
518
225
16.7
633
325
114
12.2
1.5
325
80
0.8
325
0.6
Table 38 (cont.) − RAS120 2−STAGE COOLING WITH 1−SPEED INDOOR FAN MOTOR
VOLTAGE
RANGE
V-Ph-Hz
208-3-60
230-3-60
460-3-60
575-3-60
5.8
EFF at
Full Load
187
460-3-60
COMP (ea)
FLA
COMP (Cir 1)
COMP (Cir 2)
FLA
10 TONS
OFM (ea)
IFM
MIN
MAX
RLA
LRA
RLA
LRA
WATTS
FLA
TYPE
EFF at Full
Load
STD
80%
5.2
187
253
15.6
110
15.9
110
325
1.5
MED
81%
10.0
HIGH
81%
15.0
STD
80%
5.2
MED
81%
10.0
HIGH
81%
15.0
STD
80%
2.6
MED
81%
4.4
HIGH
81%
7.4
STD
80%
2.0
MED
81%
2.8
HIGH
81%
5.6
187
414
518
513 31 3209 02
253
506
633
15.6
7.7
5.8
110
52
39
15.9
7.7
5.7
110
52
39
325
325
325
1.5
0.8
0.6
FLA
128
ELECTRICAL INFORMATION
(UNITS PRODUCED PRIOR TO JULY 30, 2012) cont.
Table 38 (cont.) − RAS120 2−STAGE COOLING WITH 2−SPEED INDOOR FAN MOTOR
VOLTAGE
RANGE
V-Ph-Hz
MIN
208-3-60
253
187
460-3-60
110
15.6
506
518
LRA
15.6
253
414
575-3-60
RLA
MAX
187
230-3-60
COMP 1
110
7.7
633
52
5.8
39
COMP 2
RLA
15.9
15.9
7.7
5.7
10 TONS
OFM (ea)
LRA
110
110
52
39
IFM
WATTS
FLA
TYPE
EFF at Full
Load
325
1.5
STD
77%
7.1
325
1.5
MED
82%
10.8
325
1.5
HIGH
84%
13.6
325
1.5
STD
77%
6.8
325
1.5
MED
82%
9.8
325
1.5
HIGH
84%
12.7
325
0.8
STD
77%
3.8
325
0.8
MED
82%
4.9
325
0.8
HIGH
84%
6.4
325
0.6
STD
80%
3.5
325
0.6
MED
84%
4.5
325
0.6
HIGH
83%
6.2
Table 38 (cont.) − RAS120 2−STAGE COOLING WITH 1−SPEED INDOOR FAN MOTOR
VOLTAGE
RANGE
V-Ph-Hz
208-3-60
230-3-60
460-3-60
575-3-60
COMP (Cir 1)
COMP (Cir 2)
12.5 TONS
OFM (ea)
IFM
MIN
MAX
RLA
LRA
RLA
LRA
WATTS
FLA
TYPE
EFF at Full
Load
STD
81%
7.5
187
253
19.0
123
22.4
149
1288
6.2
MED
81%
10.0
HIGH
81%
15.0
STD
81%
7.5
MED
81%
10.0
HIGH
81%
15.0
STD
81%
3.4
MED
81%
4.4
HIGH
81%
7.4
STD
81%
2.8
MED
81%
2.8
HIGH
81%
5.6
187
253
414
19.0
506
518
123
9.7
633
22.4
62
7.4
149
10.6
50
75
7.7
54
1288
6.2
1288
3.1
1288
2.5
Table 38 (cont.) − RAS150 2−STAGE COOLING WITH 2−SPEED INDOOR FAN MOTOR
VOLTAGE
RANGE
V-Ph-Hz
208-3-60
230-3-60
460-3-60
575-3-60
129
FLA
COMP 1
COMP 2
MIN
MAX
RLA
LRA
RLA
LRA
187
253
19.0
123
22.4
149
187
414
518
253
506
633
19.0
9.7
7.4
123
62
50
22.4
10.6
7.7
149
75
54
OFM (ea)
FLA
12.5 TONS
IFM
TYPE
EFF at Full
Load
6.2
STD
85%
8.6
6.2
MED
82%
10.8
1070
6.2
HIGH
84%
13.6
1070
6.2
STD
85%
7.8
1070
6.2
MED
82%
9.8
1070
6.2
HIGH
84%
12.7
1070
3.1
STD
85%
3.8
1070
3.1
MED
82%
4.9
1070
3.1
HIGH
84%
6.4
1070
2.5
STD
84%
4.5
1070
2.5
MED
84%
4.5
1070
2.5
HIGH
83%
6.2
WATTS
FLA
1070
1070
FLA
513 31 3209 02
ELECTRICAL INFORMATION
(UNITS PRODUCED PRIOR TO JULY 30, 2012) cont.
Table 38 (cont.) − RAS180 2−STAGE COOLING WITH 1−SPEED INDOOR FAN MOTOR
VOLTAGE
RANGE
V-Ph-Hz
MIN
208­3­60
230­3­60
460­3­60
575­3­60
COMP (Cir 1)
RLA
MAX
187
253
187
414
164
25.0
100
9.8
LRA
25.0
164
12.2
633
RLA
164
25.0
506
518
LRA
25.0
253
COMP (Cir 2)
164
12.8
78
100
9.6
78
15 TONS
OFM (ea)
WATTS
1288
1288
1288
1288
IFM
FLA
1.5
1.5
0.8
0.6
TYPE
EFF at Full
Load
STD
81%
7.5
MED
81%
10.0
HIGH
89.5%
20.4
STD
81%
7.5
MED
81%
10.0
HIGH
89.5%
20.4
STD
81%
3.4
MED
81%
4.4
HIGH
89.5%
10.2
STD
81%
2.8
MED
81%
2.8
HIGH
89.5%
9.0
Table 38 (cont.) − RAS180 2−STAGE COOLING WITH 2−SPEED INDOOR FAN MOTOR
VOLTAGE
RANGE
V-Ph-Hz
208-3-60
230-3-60
460-3-60
575-3-60
513 31 3209 02
COMP 1
COMP 2
MIN
MAX
RLA
LRA
RLA
LRA
187
253
25.0
164
25.0
164
187
414
518
253
506
633
25.0
12.2
9.8
164
100
78
25.0
12.8
9.6
164
100
78
FLA
OFM (ea)
15 TONS
IFM
TYPE
EFF at Full
Load
1.5
STD
85%
8.6
1.5
MED
82%
10.8
280
1.5
HIGH
90%
20.4
280
1.5
STD
85%
7.8
280
1.5
MED
82%
9.8
280
1.5
HIGH
90%
20.4
280
0.8
STD
85%
3.8
280
0.8
MED
82%
4.9
280
0.8
HIGH
90%
10.2
280
0.6
STD
84%
4.5
280
0.6
MED
84%
4.5
280
0.6
HIGH
94%
9.0
WATTS
FLA
280
280
FLA
130
ELECTRICAL INFORMATION
(UNITS PRODUCED PRIOR TO JULY 30, 2012) cont.
Table 39 – RAS036
ELECTRIC HEAT − ELECTRICAL DATA
1−STAGE COOLING 1−SPEED INDOOR FAN MOTOR
SINGLE POINT KIT PART NUMBER
CRSINGLEXXXXXX
NOM.
V-PH-Hz.
208/
230-1-60
IFM TYPE
STD
STD
208/
230-3-60
HIGH
STD
460-3-60
HIGH
LEGEND
APP PWR
C.O.
FLA
IFM
NOM PWR
P.E.
UNPWRD
131
NO C.O. or UNPWRD C.O.
APP
PWR
(kW)
3.3/4.0
NO P.E.
w/P.E.
(pwrd fr/unit)
101A00
NOM
PWR
(kW)
4.4
-
-
102A00
6.5
4.9/6.0
-
-
103B00
8.7
6.5/8.0
037A00
037A00
ELECTRIC HEATER PART NUMBER
CRHEATERXXXXXX
104B00
10.5
7.9/9.6
040A00
040A00
102A00,102A00
13
9.8/11.9
040A00
040A00
101A00
4.4
3.3/4.0
-
-
102A00
6.5
4.9/6.0
-
-
103B00
8.7
6.5/8.0
-
-
104B00
10.5
7.9/9.6
-
-
105A00
16
12.0/14.7
037A00
037A00
101A00
4.4
3.3/4.0
-
-
102A00
6.5
4.9/6.0
-
-
103B00
8.7
6.5/8.0
-
-
104B00
10.5
7.9/9.6
-
-
105A00
16
12.0/14.7
037A00
037A00
106A00
6
5.5
-
-
107A00
8.8
8.1
-
-
108A00
11.5
10.6
-
-
109A00
14
12.9
-
-
106A00
6
5.5
-
-
107A00
8.8
8.1
-
-
108A00
109A00
11.5
14
10.6
12.9
-
-
- 208 / 230V / 460V / 575V
- Convenience outlet
- Full load amps
- Indoor fan motor
- 240V / 480V / 600V
- Power exhaust
- Unpowered convenience outlet
513 31 3209 02
ELECTRICAL INFORMATION
(UNITS PRODUCED PRIOR TO JULY 30, 2012) cont.
Table 39 (cont.) − RAS048
ELECTRIC HEAT − ELECTRICAL DATA
1−STAGE COOLING 1−SPEED INDOOR FAN MOTOR
SINGLE POINT KIT PART NUMBER
CRSINGLEXXXXXX
NOM.
V-PH-Hz.
208/
230-1-60
IFM TYPE
STD
STD
208/
230-3-60
HIGH
STD
460-3-60
HIGH
LEGEND
APP PWR
C.O.
FLA
IFM
NOM PWR
P.E.
UNPWRD
NO C.O. or UNPWRD C.O.
APP
PWR
(kW)
3.3/4.0
NO P.E.
101A00
NOM
PWR
(kW)
4.4
-
-
103B00
8.7
6.5/8.0
037A00
037A00
ELECTRIC HEATER PART NUMBER
CRHEATERXXXXXX
w/P.E.
(pwrd fr/unit)
102A00,102A00
13
9.8/11.9
040A00
040A00
103B00,103B00
17.4
13.1/16.0
040A00
040A00
104B00,104B00
21
15.8/19.3
040A00
040A00
102A00
6.5
4.9/6.0
-
-
103B00
8.7
6.5/8.0
-
-
105A00
16
12.0/14.7
037A00
037A00
104B00,104B00
21
15.8/19.3
038A00
038A00
102A00
6.5
4.9/6.0
-
-
103B00
8.7
6.5/8.0
-
-
105A00
16
12.0/14.7
037A00
037A00
104B00,104B00
21
15.8/19.3
038A00
038A00
106A00
6
5.5
-
-
108A00
11.5
10.6
-
-
109A00
14
12.9
-
-
108A00,108A00
23
21.1
037A00
037A00
106A00
6
5.5
-
-
108A00
11.5
10.6
-
-
109A00
108A00,108A00
14
23
12.9
21.1
037A00
037A00
- 208 / 230V / 460V / 575V
- Convenience outlet
- Full load amps
- Indoor fan motor
- 240V / 480V / 600V
- Power exhaust
- Unpowered convenience outlet
513 31 3209 02
132
ELECTRICAL INFORMATION
(UNITS PRODUCED PRIOR TO JULY 30, 2012) cont.
Table 39 (cont.) − RAS060
ELECTRIC HEAT − ELECTRICAL DATA
1−STAGE COOLING 1−SPEED INDOOR FAN MOTOR
SINGLE POINT KIT PART NUMBER
CRSINGLEXXXXXX
NOM.
V-PH-Hz.
IFM TYPE
STD
208/
230-1-60
MED
STD
208/
230-3-60
MED
HIGH
STD
460-3-60
MED
HIGH
LEGEND
APP PWR
C.O.
FLA
IFM
NOM PWR
P.E.
UNPWRD
133
NO C.O. or UNPWRD C.O.
APP
PWR
(kW)
4.9/6.0
NO P.E.
102A00
NOM
PWR
(kW)
6.5
-
-
103B00
8.7
6.5/8.0
037A00
037A00
ELECTRIC HEATER PART NUMBER
CRHEATERXXXXXX
w/P.E.
(pwrd fr/unit)
102A00,102A00
13
9.8/11.9
040A00
040A00
103B00,103B00
17.4
13.1/16.0
040A00
040A00
104B00,104B00
21
15.8/19.3
040A00
040A00
102A00
6.5
4.9/6.0
-
-
103B00
8.7
6.5/8.0
037A00
037A00
102A00,102A00
13
9.8/11.9
040A00
040A00
103B00,103B00
17.4
13.1/16.0
040A00
040A00
104B00,104B00
21
15.8/19.3
040A00
040A00
102A00
6.5
4.9/6.0
-
-
104B00
10.5
7.9/9.6
-
-
105A00
16
12.0/14.7
037A00
037A00
104B00,104B00
21
15.8/19.3
038A00
038A00
104B00,105A00
26.5
19.9/24.3
038A00
038A00
102A00
6.5
4.9/6.0
-
-
104B00
10.5
7.9/9.6
-
-
105A00
16
12.0/14.7
037A00
037A00
104B00,104B00
21
15.8/19.3
038A00
038A00
104B00,105A00
26.5
19.9/24.3
038A00
038A00
102A00
6.5
4.9/6.0
-
-
104B00
10.5
7.9/9.6
-
-
105A00
16
12.0/14.7
037A00
037A00
104B00,104B00
21
15.8/19.3
038A00
038A00
104B00,105A00
26.5
19.9/24.3
038A00
038A00
106A00
6
5.5
-
-
108A00
11.5
10.6
-
-
109A00
14
12.9
-
-
108A00,108A00
23
21.1
037A00
037A00
108A00,109A00
25.5
23.4
037A00
037A00
106A00
6
5.5
-
-
108A00
11.5
10.6
-
-
109A00
14
12.9
-
-
108A00,108A00
23
21.1
037A00
037A00
108A00,109A00
25.5
23.4
037A00
037A00
106A00
6
5.5
-
-
108A00
11.5
10.6
-
-
109A00
14
12.9
-
-
108A00,108A00
108A00,109A00
23
25.5
21.1
23.4
037A00
037A00
037A00
037A00
- 208 / 230V / 460V / 575V
- Convenience outlet
- Full load amps
- Indoor fan motor
- 240V / 480V / 600V
- Power exhaust
- Unpowered convenience outlet
513 31 3209 02
ELECTRICAL INFORMATION
(UNITS PRODUCED PRIOR TO JULY 30, 2012) cont.
Table 39 (cont.) − RAS072
ELECTRIC HEAT − ELECTRICAL DATA
1−STAGE COOLING 1−SPEED INDOOR FAN MOTOR
SINGLE POINT KIT PART NUMBER
CRSINGLEXXXXXX
NOM.
V-PH-Hz.
IFM TYPE
NO P.E.
w/P.E.
(pwrd fr/unit)
102A00
APP
PWR
(kW)
4.9/6.0
-
-
104B00
10.5
7.9/9.6
-
-
105A00
16.0
12.0/14.7
037A00
037A00
104B00,104B00
21.0
15.8/19.3
038A00
038A00
104B00,105A00
26.5
19.9/24.3
038A00
038A00
102A00
6.5
4.9/6.0
-
-
104B00
10.5
7.9/9.6
-
-
105A00
16.0
12.0/14.7
037A00
037A00
104B00,104B00
21.0
15.8/19.3
038A00
038A00
104B00,105A00
26.5
19.9/24.3
038A00
038A00
102A00
6.5
4.9/6.0
-
-
104B00
10.5
7.9/9.6
-
-
105A00
16.0
12.0/14.7
037A00
037A00
104B00,104B00
21.0
15.8/19.3
038A00
038A00
104B00,105A00
26.5
19.9/24.3
038A00
038A00
106A00
6.0
5.5
-
-
108A00
11.5
10.6
-
-
109A00
14.0
12.9
-
-
108A00,108A00
23.0
21.1
037A00
037A00
108A00,109A00
25.5
23.4
037A00
037A00
106A00
6.0
5.5
-
-
108A00
11.5
10.6
-
-
109A00
14.0
12.9
-
-
108A00,108A00
23.0
21.1
037A00
037A00
108A00,109A00
25.5
23.4
037A00
037A00
106A00
6.0
5.5
-
-
108A00
11.5
10.6
-
-
109A00
14.0
12.9
-
-
108A00,108A00
108A00,109A00
23.0
25.5
21.1
23.4
037A00
037A00
037A00
037A00
STD
208/
230-3-60
MED
HIGH
STD
460-3-60
MED
HIGH
LEGEND
APP PWR
C.O.
FLA
IFM
NOM PWR
P.E.
UNPWRD
NO C.O. or UNPWRD C.O.
NOM
PWR
(kW)
6.5
ELECTRIC HEATER PART
NUMBER CRHEATERXXXXXX
- 208 / 230V / 460V / 575V
- Convenience outlet
- Full load amps
- Indoor fan motor
- 240V / 480V / 600V
- Power exhaust
- Unpowered convenience outlet
513 31 3209 02
134
ELECTRICAL INFORMATION
(UNITS PRODUCED PRIOR TO JULY 30, 2012) cont.
Table 39 (cont.) − RAS091
ELECTRIC HEAT − ELECTRICAL DATA
1−STAGE COOLING 1−SPEED INDOOR FAN MOTOR
SINGLE POINT KIT PART NUMBER
CRSINGLEXXXXXX
NOM.
V-PH-Hz.
IFM TYPE
NO P.E.
w/P.E.
(pwrd fr/unit)
117A00
APP
PWR
(kW)
7.8/9.6
042A00
042A00
110A00
16.0
12.0/14.7
042A00
042A00
111A00
24.8
18.6/22.8
043A00
043A00
112A00
32.0
24.0/29.4
043A00
043A00
112A00,117A00
42.4
31.8/38.9
045A00
045A00
117A00
10.4
7.8/9.6
042A00
042A00
110A00
16.0
12.0/14.7
042A00
043A00
111A00
24.8
18.6/22.8
043A00
043A00
112A00
32.0
24.0/29.4
043A00
043A00
112A00,117A00
42.4
31.8/38.9
045A00
045A00
117A00
10.4
7.8/9.6
042A00
042A00
110A00
16.0
12.0/14.7
043A00
043A00
111A00
24.8
18.6/22.8
043A00
043A00
112A00
32.0
24.0/29.4
043A00
043A00
112A00,117A00
42.4
31.8/38.9
045A00
045A00
116A00
13.9
12.8
042A00
042A00
113A00
16.5
15.2
042A00
042A00
114A00
27.8
25.5
042A00
042A00
115A00
33.0
30.3
042A00
042A00
114A00,116A00
41.7
38.3
044A00
044A00
116A00
13.9
12.8
042A00
042A00
113A00
16.5
15.2
042A00
042A00
114A00
27.8
25.5
042A00
042A00
115A00
33.0
30.3
042A00
042A00
114A00,116A00
41.7
38.3
044A00
044A00
116A00
13.9
12.8
042A00
042A00
113A00
16.5
15.2
042A00
042A00
114A00
27.8
25.5
042A00
042A00
115A00
33.0
30.3
042A00
044A00
114A00,116A00
41.7
38.3
044A00
044A00
118A00
17.0
17.0
042A00
042A00
119A00
34.0
34.0
042A00
042A00
118A00
17.0
17.0
042A00
042A00
119A00
34.0
34.0
042A00
042A00
118A00
119A00
17.0
34.0
17.0
34.0
042A00
042A00
042A00
044A00
STD
208/
230-3-60
MED
HIGH
STD
460-3-60
MED
HIGH
STD
575-3-60
MED
HIGH
LEGEND
APP PWR
C.O.
FLA
IFM
NOM PWR
P.E.
UNPWRD
135
NO C.O. or UNPWRD C.O.
NOM
PWR
(kW)
10.4
ELECTRIC HEATER PART
NUMBER CRHEATERXXXXXX
- 208 / 230V / 460V / 575V
- Convenience outlet
- Full load amps
- Indoor fan motor
- 240V / 480V / 600V
- Power exhaust
- Unpowered convenience outlet
513 31 3209 02
ELECTRICAL INFORMATION
(UNITS PRODUCED PRIOR TO JULY 30, 2012) cont.
Table 39 (cont.) − RAS090
ELECTRIC HEAT − ELECTRICAL DATA
2−STAGE COOLING 1−SPEED INDOOR FAN MOTOR
SINGLE POINT KIT PART NUMBER
CRSINGLEXXXXXX
NOM.
V-PH-Hz.
IFM TYPE
NO P.E.
w/P.E.
(pwrd fr/unit)
117A00
APP
PWR
(kW)
7.8/9.6
042A00
042A00
110A00
16.0
12.0/14.7
042A00
042A00
111A00
24.8
18.6/22.8
043A00
043A00
112A00
32.0
24.0/29.4
043A00
043A00
112A00,117A00
42.4
31.8/38.9
045A00
045A00
117A00
10.4
7.8/9.6
042A00
042A00
110A00
16.0
12.0/14.7
042A00
043A00
111A00
24.8
18.6/22.8
043A00
043A00
112A00
32.0
24.0/29.4
043A00
043A00
112A00,117A00
42.4
31.8/38.9
045A00
045A00
117A00
10.4
7.8/9.6
042A00
042A00
110A00
16.0
12.0/14.7
043A00
043A00
111A00
24.8
18.6/22.8
043A00
043A00
112A00
32.0
24.0/29.4
043A00
043A00
112A00,117A00
42.4
31.8/38.9
045A00
045A00
116A00
13.9
12.8
042A00
042A00
113A00
16.5
15.2
042A00
042A00
114A00
27.8
25.5
042A00
042A00
115A00
33.0
30.3
042A00
042A00
114A00,116A00
41.7
38.3
044A00
044A00
116A00
13.9
12.8
042A00
042A00
113A00
16.5
15.2
042A00
042A00
114A00
27.8
25.5
042A00
042A00
115A00
33.0
30.3
042A00
042A00
114A00,116A00
41.7
38.3
044A00
044A00
116A00
13.9
12.8
042A00
042A00
113A00
16.5
15.2
042A00
042A00
114A00
27.8
25.5
042A00
042A00
115A00
33.0
30.3
042A00
044A00
114A00,116A00
41.7
38.3
044A00
044A00
118A00
17.0
17.0
042A00
042A00
119A00
34.0
34.0
042A00
042A00
118A00
17.0
17.0
042A00
042A00
119A00
34.0
34.0
042A00
042A00
118A00
119A00
17.0
34.0
17.0
34.0
042A00
042A00
042A00
044A00
STD
208/
230-3-60
MED
HIGH
STD
460-3-60
MED
HIGH
STD
575-3-60
MED
HIGH
LEGEND
APP PWR
C.O.
FLA
IFM
NOM PWR
P.E.
UNPWRD
NO C.O. or UNPWRD C.O.
NOM
PWR
(kW)
10.4
ELECTRIC HEATER PART
NUMBER CRHEATERXXXXXX
- 208 / 230V / 460V / 575V
- Convenience outlet
- Full load amps
- Indoor fan motor
- 240V / 480V / 600V
- Power exhaust
- Unpowered convenience outlet
513 31 3209 02
136
ELECTRICAL INFORMATION
(UNITS PRODUCED PRIOR TO JULY 30, 2012) cont.
Table 39 (cont.) − RAS090
ELECTRIC HEAT − ELECTRICAL DATA
2−STAGE COOLING 2−SPEED INDOOR FAN MOTOR
SINGLE POINT KIT PART NUMBER
CRSINGLEXXXXXX
NOM.
V-PH-Hz.
IFM TYPE
STD
208/
230-3-60
MED
HIGH
STD
460-3-60
MED
HIGH
STD
575-3-60
MED
HIGH
LEGEND
APP PWR
C.O.
FLA
IFM
NOM PWR
P.E.
UNPWRD
137
NO C.O. or UNPWRD C.O.
NO P.E.
w/P.E.
(pwrd fr/unit)
117A00
NOM PWR (kW)
10.4
APP
PWR
(kW)
7.8/9.6
042A00
042A00
110A00
16.0
12.0/14.7
042A00
042A00
111A00
24.8
18.6/22.8
043A00
043A00
112A00
32.0
24.0/29.4
043A00
043A00
112A00,117A00
42.4
31.8/38.9
045A00
045A00
117A00
10.4
7.8/9.6
042A00
042A00
110A00
16.0
12.0/14.7
042A00
043A00
111A00
24.8
18.6/22.8
043A00
043A00
112A00
32.0
24.0/29.4
043A00
043A00
112A00,117A00
42.4
31.8/38.9
045A00
045A00
117A00
10.4
7.8/9.6
042A00
042A00
110A00
16.0
12.0/14.7
043A00
043A00
111A00
24.8
18.6/22.8
043A00
043A00
112A00
32.0
24.0/29.4
043A00
043A00
112A00,117A00
42.4
31.8/38.9
045A00
045A00
116A00
13.9
12.8
042A00
042A00
113A00
16.5
15.2
042A00
042A00
114A00
27.8
25.5
042A00
042A00
115A00
33.0
30.3
042A00
042A00
114A00,116A00
41.7
38.3
044A00
044A00
116A00
13.9
12.8
042A00
042A00
113A00
16.5
15.2
042A00
042A00
114A00
27.8
25.5
042A00
042A00
115A00
33.0
30.3
042A00
042A00
114A00,116A00
41.7
38.3
044A00
044A00
116A00
13.9
12.8
042A00
042A00
113A00
16.5
15.2
042A00
042A00
114A00
27.8
25.5
042A00
042A00
115A00
33.0
30.3
042A00
042A00
114A00,116A00
41.7
38.3
044A00
044A00
118A00
17.0
17.0
042A00
042A00
119A00
34.0
34.0
042A00
042A00
118A00
17.0
17.0
042A00
042A00
119A00
34.0
34.0
042A00
044A00
118A00
119A00
17.0
34.0
17.0
34.0
042A00
042A00
042A00
044A00
ELECTRIC HEATER PART
NUMBER CRHEATERXXXXXX
- 208 / 230V / 460V / 575V
- Convenience outlet
- Full load amps
- Indoor fan motor
- 240V / 480V / 600V
- Power exhaust
- Unpowered convenience outlet
513 31 3209 02
ELECTRICAL INFORMATION
(UNITS PRODUCED PRIOR TO JULY 30, 2012) cont.
Table 39 (cont.) − RAS101
ELECTRIC HEAT − ELECTRICAL DATA
1−STAGE COOLING 1−SPEED INDOOR FAN MOTOR
SINGLE POINT KIT PART NUMBER
CRSINGLEXXXXXX
NOM.
V-PH-Hz.
IFM TYPE
NO P.E.
w/P.E.
(pwrd fr/unit)
117A00
APP
PWR
(kW)
7.8/9.6
047A00
047A00
110A00
16.0
12.0/14.7
047A00
047A00
111A00
24.8
18.6/22.8
049A00
049A00
112A00
32.0
24.0/29.4
049A00
049A00
112A00,117A00
42.4
31.8/38.9
051A00
051A00
117A00
10.4
7.8/9.6
047A00
047A00
110A00
16.0
12.0/14.7
047A00
047A00
111A00
24.8
18.6/22.8
049A00
049A00
112A00
32.0
24.0/29.4
049A00
049A00
112A00,117A00
42.4
31.8/38.9
051A00
051A00
117A00
10.4
7.8/9.6
047A00
049A00
110A00
16.0
12.0/14.7
049A00
049A00
111A00
24.8
18.6/22.8
049A00
049A00
112A00
32.0
24.0/29.4
049A00
049A00
112A00,117A00
42.4
31.8/38.9
051A00
051A00
116A00
13.9
12.8
047A00
047A00
113A00
16.5
15.2
047A00
047A00
114A00
27.8
25.5
047A00
047A00
115A00
33.0
30.3
047A00
047A00
114A00,116A00
41.7
38.3
050A00
050A00
116A00
13.9
12.8
047A00
047A00
113A00
16.5
15.2
047A00
047A00
114A00
27.8
25.5
047A00
047A00
115A00
33.0
30.3
047A00
047A00
114A00,116A00
41.7
38.3
050A00
050A00
116A00
13.9
12.8
047A00
047A00
113A00
16.5
15.2
047A00
047A00
114A00
27.8
25.5
047A00
047A00
115A00
33.0
30.3
047A00
047A00
114A00,116A00
41.7
38.3
050A00
050A00
118A00
17.0
17.0
047A00
047A00
119A00
34.0
34.0
047A00
047A00
118A00
17.0
17.0
047A00
047A00
119A00
34.0
34.0
047A00
047A00
118A00
119A00
17.0
34.0
17.0
34.0
047A00
047A00
047A00
047A00
STD
208/
230-3-60
MED
HIGH
STD
460-3-60
MED
HIGH
STD
575-3-60
MED
HIGH
LEGEND
APP PWR
C.O.
FLA
IFM
NOM PWR
P.E.
UNPWRD
NO C.O. or UNPWRD C.O.
NOM
PWR
(kW)
10.4
ELECTRIC HEATER PART
NUMBER CRHEATERXXXXXX
- 208 / 230V / 460V / 575V
- Convenience outlet
- Full load amps
- Indoor fan motor
- 240V / 480V / 600V
- Power exhaust
- Unpowered convenience outlet
513 31 3209 02
138
ELECTRICAL INFORMATION
(UNITS PRODUCED PRIOR TO JULY 30, 2012) cont.
Table 39 (cont.) − RAS102
ELECTRIC HEAT − ELECTRICAL DATA
2−STAGE COOLING 1−SPEED INDOOR FAN MOTOR
SINGLE POINT KIT PART NUMBER
CRSINGLEXXXXXX
NOM.
V-PH-Hz.
IFM TYPE
NO P.E.
w/P.E.
(pwrd fr/unit)
117A00
APP
PWR
(kW)
7.8/9.6
047
047
110A00
16.0
12.0/14.7
047
047
111A00
24.8
18.6/22.8
049
049
112A00
32.0
24.0/29.4
049
049
112A00,117A00
42.4
31.8/38.9
051
051
117A00
10.4
7.8/9.6
047
047
110A00
16.0
12.0/14.7
047
047
111A00
24.8
18.6/22.8
049
049
112A00
32.0
24.0/29.4
049
049
112A00,117A00
42.4
31.8/38.9
051
051
117A00
10.4
7.8/9.6
047
047
110A00
16.0
12.0/14.7
049
049
111A00
24.8
18.6/22.8
049
049
112A00
32.0
24.0/29.4
049
049
112A00,117A00
42.4
31.8/38.9
051
051
116A00
13.9
12.8
047
047
113A00
16.5
15.2
047
047
114A00
27.8
25.5
047
047
115A00
33.0
30.3
047
047
114A00,116A00
41.7
38.3
050
050
116A00
13.9
12.8
047
047
113A00
16.5
15.2
047
047
114A00
27.8
25.5
047
047
115A00
33.0
30.3
047
047
114A00,116A00
41.7
38.3
050
050
116A00
13.9
12.8
047
047
113A00
16.5
15.2
047
047
114A00
27.8
25.5
047
047
115A00
33.0
30.3
047
047
114A00,116A00
41.7
38.3
050
050
118A00
17.0
17.0
047
047
119A00
34.0
34.0
047
047
118A00
17.0
17.0
047
047
119A00
34.0
34.0
047
047
118A00
119A00
17.0
34.0
17.0
34.0
047
047
047
047
STD
208/
230-3-60
MED
HIGH
STD
460-3-60
MED
HIGH
STD
575-3-60
MED
HIGH
LEGEND
APP PWR
C.O.
FLA
IFM
NOM PWR
P.E.
UNPWRD
139
NO C.O. or UNPWRD C.O.
NOM
PWR
(kW)
10.4
ELECTRIC HEATER PART
NUMBER CRHEATERXXXXXX
- 208 / 230V / 460V / 575V
- Convenience outlet
- Full load amps
- Indoor fan motor
- 240V / 480V / 600V
- Power exhaust
- Unpowered convenience outlet
513 31 3209 02
ELECTRICAL INFORMATION
(UNITS PRODUCED PRIOR TO JULY 30, 2012) cont.
Table 39 (cont.) − RAS102
ELECTRIC HEAT − ELECTRICAL DATA
2−STAGE COOLING 2−SPEED INDOOR FAN MOTOR
SINGLE POINT KIT PART NUMBER
CRSINGLEXXXXXX
NOM.
V-PH-Hz.
IFM TYPE
STD
208/
203-3-60
MED
HIGH
STD
460-3-60
MED
HIGH
STD
575-3-60
MED
HIGH
LEGEND
APP PWR
C.O.
FLA
IFM
NOM PWR
P.E.
UNPWRD
NO C.O. or UNPWRD C.O.
NO P.E.
w/P.E.
(pwrd fr/unit)
117A00
NOM PWR (kW)
10.4
APP
PWR
(kW)
7.8/9.6
047A00
047A00
110A00
16.0
12.0/14.7
047A00
047A00
111A00
24.8
18.6/22.8
049A00
049A00
112A00
32.0
24.0/29.4
049A00
049A00
112A00,117A00
42.4
31.8/38.9
051A00
051A00
117A00
10.4
7.8/9.6
047A00
047A00
110A00
16.0
12.0/14.7
047A00
049A00
111A00
24.8
18.6/22.8
049A00
049A00
112A00
32.0
24.0/29.4
049A00
049A00
112A00,117A00
42.4
31.8/38.9
051A00
051A00
117A00
10.4
7.8/9.6
047A00
047A00
110A00
16.0
12.0/14.7
049A00
049A00
111A00
24.8
18.6/22.8
049A00
049A00
112A00
32.0
24.0/29.4
049A00
049A00
112A00,117A00
42.4
31.8/38.9
051A00
051A00
116A00
13.9
12.8
047A00
047A00
113A00
16.5
15.2
047A00
047A00
114A00
27.8
25.5
047A00
047A00
115A00
33.0
30.3
047A00
047A00
114A00,116A00
41.7
38.3
050A00
050A00
116A00
13.9
12.8
047A00
047A00
113A00
16.5
15.2
047A00
047A00
114A00
27.8
25.5
047A00
047A00
115A00
33.0
30.3
047A00
047A00
114A00,116A00
41.7
38.3
050A00
050A00
116A00
13.9
12.8
047A00
047A00
113A00
16.5
15.2
047A00
047A00
114A00
27.8
25.5
047A00
047A00
115A00
33.0
30.3
047A00
047A00
114A00,116A00
41.7
38.3
050A00
050A00
118A00
17.0
17.0
047A00
047A00
119A00
34.0
34.0
047A00
047A00
118A00
17.0
17.0
047A00
047A00
119A00
34.0
34.0
047A00
050A00
118A00
119A00
17.0
34.0
17.0
34.0
047A00
047A00
047A00
050A00
ELECTRIC HEATER PART
NUMBER CRHEATERXXXXXX
- 208 / 230V / 460V / 575V
- Convenience outlet
- Full load amps
- Indoor fan motor
- 240V / 480V / 600V
- Power exhaust
- Unpowered convenience outlet
513 31 3209 02
140
ELECTRICAL INFORMATION
(UNITS PRODUCED PRIOR TO JULY 30, 2012) cont.
Table 39 (cont.) − RAS121
ELECTRIC HEAT − ELECTRICAL DATA
1−STAGE COOLING 1−SPEED INDOOR FAN MOTOR
SINGLE POINT KIT PART NUMBER
CRSINGLEXXXXXX
NOM.
V-PH-Hz.
IFM TYPE
STD
208/
230-3-60
MED
HIGH
STD
460-3-60
MED
HIGH
STD
575-3-60
MED
HIGH
LEGEND
APP PWR
C.O.
FLA
IFM
NOM PWR
P.E.
UNPWRD
141
ELECTRIC HEATER PART
NUMBER
CRHEATERXXXXXX
117A00
NOM
PWR
(kW)
10.4
APP
PWR
(kW)
7.8/9.6
110A00
16.0
12.0/14.7
112A00
32.0
112A00,117A00
NO C.O. or UNPWRD C.O.
NO P.E.
w/P.E.
(pwrd fr/unit)
047A00
047A00
047A00
047A00
24.0/29.4
049A00
049A00
42.4
31.8/38.9
051A00
051A00
112A00,110A00
50.0
37.6/45.9
051A00
051A00
117A00
10.4
7.8/9.6
047A00
049A00
110A00
16.0
12.0/14.7
049A00
049A00
112A00
32.0
24.0/29.4
049A00
049A00
112A00,117A00
42.4
31.8/38.9
051A00
051A00
112A00,110A00
50.0
37.6/45.9
051A00
051A00
117A00
10.4
7.8/9.6
049A00
049A00
110A00
16.0
12.0/14.7
049A00
049A00
112A00
32.0
24.0/29.4
049A00
049A00
112A00,117A00
42.4
31.8/38.9
051A00
051A00
112A00,110A00
50.0
37.6/45.9
051A00
051A00
116A00
13.9
12.8
047A00
047A00
113A00
16.5
15.2
047A00
047A00
115A00
33.0
30.3
047A00
047A00
114A00,116A00
41.7
38.3
050A00
050A00
115A00,113A00
50.0
45.9
050A00
050A00
116A00
13.9
12.8
047A00
047A00
113A00
16.5
15.2
047A00
047A00
115A00
33.0
30.3
047A00
047A00
114A00,116A00
41.7
38.3
050A00
050A00
115A00,113A00
50.0
45.9
050A00
050A00
116A00
13.9
12.8
047A00
047A00
113A00
16.5
15.2
047A00
047A00
115A00
33.0
30.3
047A00
050A00
114A00,116A00
41.7
38.3
050A00
050A00
115A00,113A00
50.0
45.9
050A00
050A00
118A00
17.0
17.0
047A00
047A00
119A00
34.0
34.0
047A00
047A00
118A00,119A00
51.0
51.0
050A00
050A00
118A00
17.0
17.0
047A00
047A00
119A00
34.0
34.0
047A00
047A00
118A00,119A00
51.0
51.0
050A00
050A00
118A00
17.0
17.0
047A00
047A00
119A00
118A00,119A00
34.0
51.0
34.0
51.0
047A00
050A00
050A00
050A00
- 208 / 230V / 460V / 575V
- Convenience outlet
- Full load amps
- Indoor fan motor
- 240V / 480V / 600V
- Power exhaust
- Unpowered convenience outlet
513 31 3209 02
ELECTRICAL INFORMATION
(UNITS PRODUCED PRIOR TO JULY 30, 2012) cont.
Table 39 (cont.) − RAS120
ELECTRIC HEAT − ELECTRICAL DATA
2−STAGE COOLING 1−SPEED INDOOR FAN MOTOR
SINGLE POINT KIT PART NUMBER
CRSINGLEXXXXXX
NOM.
V-PH-Hz.
IFM TYPE
STD
208/
230-3-60
MED
HIGH
STD
460-3-60
MED
HIGH
STD
575-3-60
MED
HIGH
LEGEND
APP PWR
C.O.
FLA
IFM
NOM PWR
P.E.
UNPWRD
ELECTRIC HEATER PART
NUMBER
CRHEATERXXXXXX
117A00
NOM
PWR
(kW)
10.4
APP
PWR
(kW)
7.8/9.6
110A00
16.0
12.0/14.7
112A00
32.0
112A00,117A00
NO C.O. or UNPWRD C.O.
NO P.E.
w/P.E.
(pwrd fr/unit)
047A00
047A00
047A00
047A00
24.0/29.4
049A00
049A00
42.4
31.8/38.9
051A00
051A00
112A00,110A00
50.0
37.6/45.9
051A00
051A00
117A00
10.4
7.8/9.6
047A00
047A00
110A00
16.0
12.0/14.7
049A00
049A00
112A00
32.0
24.0/29.4
049A00
049A00
112A00,117A00
42.4
31.8/38.9
051A00
051A00
112A00,110A00
50.0
37.6/45.9
051A00
051A00
117A00
10.4
7.8/9.6
047A00
049A00
110A00
16.0
12.0/14.7
049A00
049A00
112A00
32.0
24.0/29.4
049A00
049A00
112A00,117A00
42.4
31.8/38.9
051A00
051A00
112A00,110A00
50.0
37.6/45.9
051A00
051A00
116A00
13.9
12.8
047A00
047A00
113A00
16.5
15.2
047A00
047A00
115A00
33.0
30.3
047A00
047A00
114A00,116A00
41.7
38.3
050A00
050A00
115A00,113A00
50.0
45.9
050A00
050A00
116A00
13.9
12.8
047A00
047A00
113A00
16.5
15.2
047A00
047A00
115A00
33.0
30.3
047A00
047A00
114A00,116A00
41.7
38.3
050A00
050A00
115A00,113A00
50.0
45.9
050A00
050A00
116A00
13.9
12.8
047A00
047A00
113A00
16.5
15.2
047A00
047A00
115A00
33.0
30.3
047A00
050A00
114A00,116A00
41.7
38.3
050A00
050A00
115A00,113A00
50.0
45.9
050A00
050A00
118A00
17.0
17.0
047A00
047A00
119A00
34.0
34.0
047A00
047A00
118A00,119A00
51.0
51.0
050A00
050A00
118A00
17.0
17.0
047A00
047A00
119A00
34.0
34.0
047A00
047A00
118A00,119A00
51.0
51.0
050A00
050A00
118A00
17.0
17.0
047A00
047A00
119A00
118A00,119A00
34.0
51.0
34.0
51.0
047A00
050A00
050A00
050A00
- 208 / 230V / 460V / 575V
- Convenience outlet
- Full load amps
- Indoor fan motor
- 240V / 480V / 600V
- Power exhaust
- Unpowered convenience outlet
513 31 3209 02
142
ELECTRICAL INFORMATION
(UNITS PRODUCED PRIOR TO JULY 30, 2012) cont.
Table 39 (cont.) − RAS120
ELECTRIC HEAT − ELECTRICAL DATA
2−STAGE COOLING 2−SPEED INDOOR FAN MOTOR
SINGLE POINT KIT PART NUMBER
CRSINGLEXXXXXX
NOM.
V-PH-Hz.
IFM TYPE
STD
208/
230-3-60
MED
HIGH
STD
460-3-60
MED
HIGH
STD
575-3-60
MED
HIGH
LEGEND
APP PWR
C.O.
FLA
IFM
NOM PWR
P.E.
UNPWRD
143
NO C.O. or UNPWRD C.O.
NO P.E.
w/P.E.
(pwrd fr/unit)
117A00
NOM PWR (kW)
10.4
APP
PWR
(kW)
7.8/9.6
047A00
047A00
110A00
16.0
12.0/14.7
047A00
049A00
112A00
32.0
24.0/29.4
049A00
049A00
112A00,117A00
42.4
31.8/38.9
051A00
051A00
112A00,110A00
50.0
37.6/45.9
051A00
051A00
117A00
10.4
7.8/9.6
047A00
047A00
110A00
16.0
12.0/14.7
049A00
049A00
112A00
32.0
24.0/29.4
049A00
049A00
112A00,117A00
42.4
31.8/38.9
051A00
051A00
112A00,110A00
50.0
37.6/45.9
051A00
051A00
117A00
10.4
7.8/9.6
047A00
047A00
110A00
16.0
12.0/14.7
049A00
049A00
112A00
32.0
24.0/29.4
049A00
049A00
112A00,117A00
42.4
31.8/38.9
051A00
051A00
112A00,110A00
50.0
37.6/45.9
051A00
051A00
116A00
13.9
12.8
047A00
047A00
113A00
16.5
15.2
047A00
047A00
115A00
33.0
30.3
047A00
047A00
114A00,116A00
41.7
38.3
050A00
050A00
115A00,113A00
50.0
45.9
050A00
050A00
116A00
13.9
12.8
047A00
047A00
113A00
16.5
15.2
047A00
047A00
115A00
33.0
30.3
047A00
047A00
114A00,116A00
41.7
38.3
050A00
050A00
115A00,113A00
50.0
45.9
050A00
050A00
116A00
13.9
12.8
047A00
047A00
113A00
16.5
15.2
047A00
047A00
115A00
33.0
30.3
047A00
047A00
114A00,116A00
41.7
38.3
050A00
050A00
115A00,113A00
50.0
45.9
050A00
050A00
118A00
17.0
17.0
047A00
047A00
119A00
34.0
34.0
047A00
050A00
118A00,119A00
51.0
51.0
050A00
050A00
118A00
17.0
17.0
047A00
047A00
119A00
34.0
34.0
047A00
050A00
118A00,119A00
51.0
51.0
050A00
050A00
118A00
17.0
17.0
047A00
047A00
119A00
118A00,119A00
34.0
51.0
34.0
51.0
047A00
050A00
050A00
050A00
ELECTRIC HEATER PART
NUMBER CRHEATERXXXXXX
- 208 / 230V / 460V / 575V
- Convenience outlet
- Full load amps
- Indoor fan motor
- 240V / 480V / 600V
- Power exhaust
- Unpowered convenience outlet
513 31 3209 02
ELECTRICAL INFORMATION
(UNITS PRODUCED PRIOR TO JULY 30, 2012) cont.
Table 39 (cont.) − RAS150
ELECTRIC HEAT − ELECTRICAL DATA
2−STAGE COOLING 1−SPEED INDOOR FAN MOTOR
SINGLE POINT KIT PART NUMBER
CRSINGLEXXXXXX
NOM.
V-PH.HZ.
IFM TYPE
STD
MED
208/
230-3/60
HIGH
STD
460-3-60
MED
HIGH
STD
575-3-60
MED
HIGH
LEGEND
APP PWR
C.O.
FLA
IFM
NOM PWR
P.E.
UNPWRD
ELECTRIC HEATER PART
NUMBER
CRHEATERXXXXXX
117A00
NOM
PWR
(kW)
10.4
APP
PWR
(kW)
7.8/9.6
110A00
16.0
12.0/14.7
112A00
32.0
112A00,117A00
NO C.O. or UNPWRD C.O.
NO P.E.
w/P.E.
(pwrd fr/unit)
049A00
049A00
049A00
049A00
24.0/29.4
049A00
049A00
42.4
31.8/38.9
051A00
051A00
112A00,110A00
50.0
37.6/45.9
051A00
051A00
117A00
10.4
7.8/9.6
049A00
049A00
110A00
16.0
12.0/14.7
049A00
049A00
112A00
32.0
24.0/29.4
049A00
049A00
112A00,117A00
42.4
31.8/38.9
051A00
051A00
112A00,110A00
50.0
37.6/45.9
051A00
051A00
Std Unit Without Heat
-
-
-
-
117A00
10.4
7.8/9.6
049A00
049A00
110A00
16.0
12.0/14.7
049A00
049A00
112A00
32.0
24.0/29.4
049A00
049A00
112A00,117A00
42.4
31.8/38.9
051A00
051A00
112A00,110A00
50.0
37.6/45.9
051A00
051A00
116A00
13.9
12.8
047A00
047A00
113A00
16.5
15.2
047A00
047A00
115A00
33.0
30.3
047A00
047A00
114A00,116A00
41.7
38.3
050A00
050A00
115A00,113A00
50.0
45.9
050A00
050A00
116A00
13.9
12.8
047A00
047A00
113A00
16.5
15.2
047A00
047A00
115A00
33.0
30.3
047A00
047A00
114A00,116A00
41.7
38.3
050A00
050A00
115A00,113A00
50.0
45.9
050A00
050A00
116A00
13.9
12.8
047A00
047A00
113A00
16.5
15.2
047A00
047A00
115A00
33.0
30.3
047A00
050A00
114A00,116A00
41.7
38.3
050A00
050A00
115A00,113A00
50.0
45.9
050A00
050A00
118A00
17.0
17.0
047A00
047A00
119A00
34.0
34.0
047A00
047A00
118A00,119A00
51.0
51.0
050A00
050A00
118A00
17.0
17.0
047A00
047A00
119A00
34.0
34.0
047A00
047A00
118A00,119A00
51.0
51.0
050A00
050A00
118A00
17.0
17.0
047A00
047A00
119A00
118A00,119A00
34.0
51.0
34.0
51.0
047A00
050A00
050A00
050A00
- 208 / 230V / 460V / 575V
- Convenience outlet
- Full load amps
- Indoor fan motor
- 240V / 480V / 600V
- Power exhaust
- Unpowered convenience outlet
513 31 3209 02
144
ELECTRICAL INFORMATION
(UNITS PRODUCED PRIOR TO JULY 30, 2012) cont.
Table 39 (cont.) − RAS150
ELECTRIC HEAT − ELECTRICAL DATA
2−STAGE COOLING 2−SPEED INDOOR FAN MOTOR
SINGLE POINT KIT PART NUMBER
CRSINGLEXXXXXX
NOM.
V-PH-Hz.
IFM TYPE
STD
208/
230-3-60
MED
STD
460-3-60
MED
HIGH
STD
575-3-60
MED
HIGH
LEGEND
APP PWR
C.O.
FLA
IFM
NOM PWR
P.E.
UNPWRD
145
NO C.O. or UNPWRD C.O.
NO P.E.
w/P.E.
(pwrd fr/unit)
117A00
NOM PWR (kW)
10.4
APP
PWR
(kW)
7.8/9.6
049A00
049A00
110A00
16.0
12.0/14.7
049A00
049A00
112A00
32.0
24.0/29.4
049A00
049A00
112A00,117A00
42.4
31.8/38.9
051A00
051A00
112A00,110A00
50.0
37.6/45.9
051A00
051A00
117A00
10.4
7.8/9.6
049A00
049A00
110A00
16.0
12.0/14.7
049A00
049A00
112A00
32.0
24.0/29.4
049A00
049A00
112A00,117A00
42.4
31.8/38.9
051A00
051A00
112A00,110A00
50.0
37.6/45.9
051A00
051A00
117A00
10.4
7.8/9.6
049A00
049A00
110A00
16.0
12.0/14.7
049A00
049A00
112A00
32.0
24.0/29.4
049A00
049A00
112A00,117A00
42.4
31.8/38.9
051A00
051A00
112A00,110A00
50.0
37.6/45.9
051A00
051A00
116A00
13.9
12.8
047A00
047A00
113A00
16.5
15.2
047A00
047A00
115A00
33.0
30.3
047A00
047A00
114A00,116A00
41.7
38.3
050A00
050A00
115A00,113A00
50.0
45.9
050A00
050A00
116A00
13.9
12.8
047A00
047A00
113A00
16.5
15.2
047A00
047A00
115A00
33.0
30.3
047A00
047A00
114A00,116A00
41.7
38.3
050A00
050A00
115A00,113A00
50.0
45.9
050A00
050A00
116A00
13.9
12.8
047A00
047A00
113A00
16.5
15.2
047A00
047A00
115A00
33.0
30.3
047A00
047A00
114A00,116A00
41.7
38.3
050A00
050A00
115A00,113A00
50.0
45.9
050A00
050A00
118A00
17.0
17.0
047A00
047A00
119A00
34.0
34.0
047A00
050A00
118A00,119A00
51.0
51.0
050A00
050A00
118A00
17.0
17.0
047A00
047A00
119A00
34.0
34.0
047A00
050A00
118A00,119A00
51.0
51.0
050A00
050A00
118A00
17.0
17.0
047A00
047A00
119A00
118A00,119A00
34.0
51.0
34.0
51.0
047A00
050A00
050A00
050A00
ELECTRIC HEATER PART
NUMBER CRHEATERXXXXXX
- 208 / 230V / 460V / 575V
- Convenience outlet
- Full load amps
- Indoor fan motor
- 240V / 480V / 600V
- Power exhaust
- Unpowered convenience outlet
513 31 3209 02
ELECTRICAL INFORMATION
(UNITS PRODUCED PRIOR TO JULY 30, 2012) cont.
Table 39 (cont.) − RAS180
NOM.
V-PH-Hz.
208/
230-3-60
ELECTRIC HEAT − ELECTRICAL DATA
2−STAGE COOLING 1−SPEED INDOOR FAN MOTOR
IFM TYPE
ELECTRIC HEATER PART NUMBER
CRHEATERXXXXXX
291A00
NOM
PWR
(kW)
16.5
APP
PWR
(kW)
12.4/15.2
294A00
33.5
25.2/30.8
049A00
049A00
STD
288A00,294A00
43.5
32.7/40.0
051A00
051A00
291A00,294A00
50.0
37.6/45.9
051A00
051A00
294A00,294A00
67.0
50.3/61.5
053A00
053A00
291A00
16.5
12.4/15.2
049A00
049A00
294A00
33.5
25.2/30.8
049A00
049A00
288A00,294A00
43.5
32.7/40.0
051A00
051A00
291A00,294A00
50.0
37.6/45.9
051A00
051A00
294A00,294A00
67.0
50.3/61.5
053A00
053A00
291A00
16.5
12.4/15.2
049A00
049A00
294A00
33.5
25.2/30.8
049A00
049A00
288A00,294A00
43.5
32.7/40.0
051A00
051A00
291A00,294A00
50.0
37.6/45.9
051A00
051A00
294A00,294A00
67.0
50.3/61.5
053A00
053A00
292A00
16.5
15.2
­
­
295A00
33.5
30.8
047A00
047A00
289A00,295A00
43.5
40.0
050A00
050A00
292A00,295A00
50.0
45.9
050A00
050A00
295A00,295A00
67.0
61.5
050A00
050A00
292A00
16.5
15.2
­
­
295A00
33.5
30.8
047A00
047A00
289A00,295A00
43.5
40.0
050A00
050A00
292A00,295A00
50.0
45.9
050A00
050A00
295A00,295A00
67.0
61.5
050A00
050A00
292A00
16.5
15.2
­
­
295A00
33.5
30.8
050A00
050A00
289A00,295A00
43.5
40.0
050A00
050A00
292A00,295A00
50.0
45.9
050A00
050A00
295A00,295A00
67.0
61.5
050A00
050A00
293A00
16.5
15.2
­
­
296A00
33.5
30.8
047A00
047A00
290A00,296A00
43.5
40.0
047A00
050A00
293A00,296A00
50.0
45.9
047A00
047A00
296A00,296A00
67.0
61.5
050A00
050A00
293A00
16.5
15.2
­
­
296A00
33.5
30.8
047A00
047A00
290A00,296A00
43.5
40.0
047A00
050A00
293A00,296A00
50.0
45.9
047A00
047A00
296A00,296A00
67.0
61.5
050A00
050A00
293A00
16.5
15.2
­
­
296A00
33.5
30.8
047A00
047A00
290A00,296A00
43.5
40.0
050A00
050A00
293A00,296A00
50.0
45.9
050A00
050A00
296A00,296A00
67.0
61.5
050A00
050A00
MED
HIGH
STD
460-3-60
MED
HIGH
STD
575-3-60
MED
HIGH
LEGEND
APP PWR
C.O.
FLA
IFM
NOM PWR
P.E.
UNPWRD
SINGLE POINT KIT PART NUMBER
CRSINGLEXXXXXX
NO C.O. or UNPWRD C.O.
w/P.E.
(pwrd fr/unit)
NO P.E.
049A00
049A00
- 208 / 230V / 460V / 575V
- Convenience outlet
- Full load amps
- Indoor fan motor
- 240V / 480V / 600V
- Power exhaust
- Unpowered convenience outlet
513 31 3209 02
146
ELECTRICAL INFORMATION
(UNITS PRODUCED PRIOR TO JULY 30, 2012) cont.
Table 39 (cont.) − RAS180
ELECTRIC HEAT − ELECTRICAL DATA
2−STAGE COOLING 2−SPEED INDOOR FAN MOTOR
SINGLE POINT KIT PART NUMBER
CRSINGLEXXXXXX
NOM.
V-PH-Hz.
IFM TYPE
STD
208/
230-3-60
MED
HIGH
STD
460-3-60
MED
HIGH
STD
575-3-60
MED
HIGH
LEGEND
APP PWR
C.O.
FLA
IFM
NOM PWR
P.E.
UNPWRD
147
NO C.O. or UNPWRD C.O.
NO P.E.
w/P.E.
(pwrd fr/unit)
291A00
NOM PWR (kW)
16.5
APP
PWR
(kW)
12.4/15.2
049A00
049A00
294A00
33.5
25.2/30.8
049A00
049A00
288A00,294A00
43.5
32.7/40.0
051A00
051A00
291A00,294A00
50.0
37.6/45.9
051A00
051A00
294A00,294A00
67.0
50.3/61.5
053A00
053A00
291A00
16.5
12.4/15.2
049A00
049A00
294A00
33.5
25.2/30.8
049A00
049A00
288A00,294A00
43.5
32.7/40.0
051A00
051A00
291A00,294A00
50.0
37.6/45.9
051A00
051A00
294A00,294A00
67.0
50.3/61.5
053A00
053A00
291A00
16.5
12.4/15.2
049A00
049A00
294A00
33.5
25.2/30.8
049A00
049A00
288A00,294A00
43.5
32.7/40.0
051A00
051A00
291A00,294A00
50.0
37.6/45.9
051A00
051A00
294A00,294A00
67.0
50.3/61.5
053A00
053A00
292A00
16.5
15.2
-
-
295A00
33.5
30.8
047A00
047A00
289A00,295A00
43.5
40.0
050A00
050A00
292A00,295A00
50.0
45.9
050A00
050A00
295A00,295A00
67.0
61.5
050A00
050A00
292A00
16.5
15.2
-
-
295A00
33.5
30.8
047A00
047A00
289A00,295A00
43.5
40.0
050A00
050A00
292A00,295A00
50.0
45.9
050A00
050A00
295A00,295A00
67.0
61.5
050A00
050A00
292A00
16.5
15.2
-
-
295A00
33.5
30.8
050A00
050A00
289A00,295A00
43.5
40.0
050A00
050A00
292A00,295A00
50.0
45.9
050A00
050A00
295A00,295A00
67.0
61.5
050A00
050A00
293A00
16.5
15.2
-
-
296A00
33.5
30.8
047A00
047A00
290A00,296A00
43.5
40.0
047A00
050A00
293A00,296A00
50.0
45.9
047A00
047A00
296A00,296A00
67.0
61.5
050A00
050A00
293A00
16.5
15.2
-
-
296A00
33.5
30.8
047A00
047A00
290A00,296A00
43.5
40.0
047A00
050A00
293A00,296A00
50.0
45.9
047A00
047A00
296A00,296A00
67.0
61.5
050A00
050A00
293A00
16.5
15.2
-
-
296A00
33.5
30.8
047A00
047A00
290A00,296A00
43.5
40.0
050A00
050A00
293A00,296A00
50.0
45.9
050A00
050A00
296A00,296A00
67.0
61.5
050A00
050A00
ELECTRIC HEATER PART
NUMBER CRHEATERXXXXXX
- 208 / 230V / 460V / 575V
- Convenience outlet
- Full load amps
- Indoor fan motor
- 240V / 480V / 600V
- Power exhaust
- Unpowered convenience outlet
513 31 3209 02
ELECTRICAL INFORMATION (UNITS PRODUCED PRIOR TO JULY 30, 2012) cont.
Table 40 – RAS036 Unit Wire/Fuse or HACR Breaker Sizing Data 1 Stage Cooling With 1 Speed Indoor Fan Motor
ELECTRIC HEATER
NOM.
V-PH-Hz.
208/
230-1-60
208/
230-3-60
460-3-60
575-3-60
*
IFM TYPE Nom* (kW)
None
3.3/4.4
4.9/6.5
STD
6.5/8.7
7.9/10.5
9.8/13.0
None
3.3/4.4
4.9/6.5
STD
6.5/8.7
7.9/10.5
12.0/16.0
None
3.3/4.4
4.9/6.5
HIGH
6.5/8.7
7.9/10.5
12.0/16.0
None
6.0
STD
8.8
11.5
14.0
None
6.0
HIGH
8.8
11.5
14.0
STD
None
HIGH
None
FLA
None
15.9/18.3
23.5/27.1
31.4/36.3
37.9/43.8
46.9/54.2
None
9.2/10.6
13.6/15.6
18.1/20.9
21.9/25.3
33.4/38.5
None
9.2/10.6
13.6/15.6
18.1/20.9
21.9/25.3
33.4/38.5
None
7.2
10.6
13.8
16.8
None
7.2
10.6
13.8
16.8
None
None
NO C.O. or UNPWR C.O.
MCA
27.2
27.2/29.0
35.5/40.0
45.4/51.5
53.5/60.9
64.8/73.9
19.4
19.4/19.4
23.1/25.6
28.8/32.3
33.5/37.8
47.9/54.3
19.7
19.7/19.8
23.5/26.0
29.1/32.6
33.9/38.1
48.3/54.6
10.2
11.6
15.9
19.9
23.6
10.7
12.3
16.5
20.5
24.3
7.3
7.4
NO P.E.
MAX
FUSE or
HACR
BRKR
40
40/40
40/45
50/60
60/70
70/80
25
25/25
25/30
30/35
35/40
50/60
30
30/30
30/30
30/35
35/40
50/60
15
15
20
20
25
15
15
20
25
25
15
15
DISC. SIZE
FLA
26
26/27
33/37
42/47
49/56
60/68
19
19/19
21/24
26/30
31/35
44/50
20
20/20
22/24
27/30
31/35
44/50
10
11
15
18
22
11
11
15
19
22
7
7
LRA
95
95/95
95/95
95/95
95/95
95/95
89
89/89
89/89
89/89
89/89
89/89
107
107/107
107/107
107/107
107/107
107/107
46
46
46
46
46
55
55
55
55
55
44
50
MCA
29.1
29.1/31.4
37.9/42.4
47.8/53.9
55.9/63.3
67.1/76.3
21.3
21.3/21.8
25.5/28.0
31.1/34.6
35.9/40.1
50.3/56.6
21.6
21.6/22.1
25.9/28.4
31.5/35.0
36.3/40.5
50.6/57.0
11.2
12.9
17.1
21.1
24.9
11.7
13.5
17.8
21.8
25.5
9.2
9.3
w/ P.E. (pwrd fr/unit)
MAX
DISC. SIZE
FUSE or
HACR
BRKR
FLA
LRA
45
29
97
45/45
29/29
97/97
45/45
35/39
97/97
50/60
44/50
97/97
60/70
51/58
97/97
70/80
62/70
97/97
30
22
91
30/30
22/22
91/91
30/30
23/26
91/91
35/35
29/32
91/91
40/45
33/37
91/91
60/60
46/52
91/91
30
22
109
30/30
22/22
109/109
30/30
24/26
109/109
35/40
29/32
109/109
40/45
33/37
109/109
60/60
47/52
109/109
15
11
47
15
12
47
20
16
47
25
19
47
25
23
47
15
12
56
15
12
56
20
16
56
25
20
56
30
23
56
15
9
46
15
10
52
Nominal values, listed as 208/240V, 480V or 600V as appropriate.
513 31 3209 02
148
ELECTRICAL INFORMATION (UNITS PRODUCED PRIOR TO JULY 30, 2012) cont.
Table 41 – RAS048 Unit Wire/Fuse or HACR Breaker Sizing Data 1 Stage Cooling With 1 Speed Indoor Fan Motor
ELECTRIC HEATER
NOM.
V-PH-Hz.
IFM
TYPE
208/
230-1-60
STD
STD
208/
230-3-60
HIGH
STD
460-3-60
HIGH
575-3-60
*
STD
MED
HIGH
Nom*
(kW)
None
3.3/4.4
6.5/8.7
9.8/13.0
13.1/17.4
15.8/21.0
None
4.9/6.5
6.5/8.7
12.0/16.0
15.8/21.0
None
4.9/6.5
6.5/8.7
12.0/16.0
15.8/21.0
None
6.0
11.5
14.0
23.0
None
6.0
11.5
14.0
23.0
None
None
None
FLA
None
15.9/18.3
31.4/36.3
46.9/54.2
62.8/72.5
75.8/87.5
None
13.6/15.6
18.1/20.9
33.4/38.5
43.8/50.5
None
13.6/15.6
18.1/20.9
33.4/38.5
43.8/50.5
None
7.2
13.8
16.8
27.7
None
7.2
13.8
16.8
27.7
None
None
None
MCA
33.7
33.7/33.7
45.4/51.5
64.8/73.9
84.6/96.8
100.9/115.5
23.5
23.5/25.6
28.8/32.3
47.9/54.3
60.9/69.3
23.8
23.8/26.0
29.1/32.6
48.3/54.6
61.3/69.6
10.7
11.6
19.9
23.6
37.3
11.2
12.3
20.5
24.3
37.9
8.5
8.5
8.6
NO C.O. or UNPWR C.O.
NO P.E.
w/ P.E. (pwrd fr/unit)
MAX
MAX
DISC. SIZE
DISC. SIZE
FUSE or
FUSE or
HACR
HACR
BRKR
BRKR
MCA
FLA
LRA
FLA
LRA
50
32
133
35.6
50
35
135
50/50
32/32
133/133
35.6/35.6
50/50
35/35
135/135
50/60
42/47
133/133
47.8/53.9
50/60
44/50
135/135
70/80
60/68
133/133
67.1/76.3
70/80
62/70
135/135
90/100
78/89
133/133
87.0/99.1
90/100
80/91
135/135
110/125
93/106
133/133
103.3/117.9
110/125
95/108
135/135
30
23
99
25.4
30
25
101
30/30
23/24
99/99
25.5/28.0
30/30
25/26
101/101
30/35
26/30
99/99
31.1/34.6
35/35
29/32
101/101
50/60
44/50
99/99
50.3/56.6
60/60
46/52
101/101
70/70
56/64
99/99
63.3/71.6
70/80
58/66
101/101
30
23
117
25.7
30
26
119
30/30
23/24
117/117
25.9/28.4
30/30
26/26
119/119
30/35
27/30
117/117
31.5/35.0
35/40
29/32
119/119
50/60
44/50
117/117
50.6/57.0
60/60
47/52
119/119
70/70
56/64
117/117
63.6/72.0
70/80
59/66
119/119
15
10
49
11.7
15
12
50
15
11
49
12.9
15
12
50
20
18
49
21.1
25
19
50
25
22
49
24.9
25
23
50
40
34
49
38.5
40
35
50
15
11
58
12.2
15
12
59
15
11
58
13.5
15
12
59
25
19
58
21.8
25
20
59
25
22
58
25.5
30
23
59
40
35
58
39.1
40
36
59
15
8
44
10.4
15
11
46
15
8
44
10.4
15
11
46
15
9
50
10.5
15
11
52
Nominal values, listed as 208/240V, 480V or 600V as appropriate.
149
513 31 3209 02
ELECTRICAL INFORMATION (UNITS PRODUCED PRIOR TO JULY 30, 2012) cont.
Table 42 – RAS060 Unit Wire/Fuse or HACR Breaker Sizing Data 1 Stage Cooling With 1 Speed Indoor Fan Motor
ELECTRIC HEATER
NOM.
V-PH-Hz.
IFM TYPE
STD
208/
230-1-60
MED
STD
208/
230-3-60
MED
HIGH
STD
460-3-60
MED
HIGH
575-3-60
*
STD
MED
HIGH
Nom* (kW)
None
4.9/6.5
6.5/8.7
9.8/13.0
13.1/17.4
15.8/21.0
None
4.9/6.5
6.5/8.7
9.8/13.0
13.1/17.4
15.8/21.0
None
4.9/6.5
7.9/10.5
12.0/16.0
15.8/21.0
19.9/26.5
None
4.9/6.5
7.9/10.5
12.0/16.0
15.8/21.0
19.9/26.5
None
4.9/6.5
7.9/10.5
12.0/16.0
15.8/21.0
19.9/26.5
None
6.0
11.5
14.0
23.0
25.5
None
6.0
11.5
14.0
23.0
25.5
None
6.0
11.5
14.0
23.0
25.5
None
None
None
FLA
None
23.5/27.1
31.4/36.3
46.9/54.2
62.8/72.5
75.8/87.5
None
23.5/27.1
31.4/36.3
46.9/54.2
62.8/72.5
75.8/87.5
None
13.6/15.6
21.9/25.3
33.4/38.5
43.8/50.5
55.2/63.8
None
13.6/15.6
21.9/25.3
33.4/38.5
43.8/50.5
55.2/63.8
None
13.6/15.6
21.9/25.3
33.4/38.5
43.8/50.5
55.2/63.8
None
7.2
13.8
16.8
27.7
30.7
None
7.2
13.8
16.8
27.7
30.7
None
7.2
13.8
16.8
27.7
30.7
None
None
None
NO C.O. or UNPWR C.O.
MCA
39.2
39.2/40.0
45.4/51.5
64.8/73.9
84.6/96.8
100.9/115.5
41.3
41.3/42.6
48.0/54.1
67.4/76.5
87.3/99.4
103.5/118.1
25.9
25.9/25.9
33.5/37.8
47.9/54.3
60.9/69.3
75.1/85.9
26.2
26.2/26.2
33.9/38.1
48.3/54.6
61.3/69.6
75.5/86.3
28.5
28.5/28.9
36.8/41.0
51.1/57.5
64.1/72.5
78.4/89.1
12.5
12.5
19.9
23.6
37.3
41.0
13
13.0
20.5
24.3
37.9
41.6
13.8
13.8
21.5
25.3
38.9
42.6
9.8
9.9
10.7
NO P.E.
MAX
FUSE or
HACR
BRKR
60
60/60
60/60
70/80
90/100
110/125
60
60/60
60/60
70/80
90/100
110/125
30
30/30
40/40
50/60
70/70
80/90
40
40/40
40/40
50/60
70/70
80/90
40
40/40
40/45
60/60
70/80
80/90
20
20
20
25
40
45
20
20
25
25
40
45
20
20
25
30
40
45
15
15
15
DISC. SIZE
FLA
37
37/37
42/47
60/68
78/89
93/106
40
40/40
44/50
62/70
80/91
95/109
25
25/25
31/35
44/50
56/64
69/79
26
26/26
31/35
44/50
56/64
69/79
28
28/28
34/38
47/53
59/67
72/82
12
12
18
22
34
38
13
13
19
22
35
38
14
14
20
23
36
39
10
10
11
LRA
150
150/150
150/150
150/150
150/150
150/150
175
175/175
175/175
175/175
175/175
175/175
126
126/126
126/126
126/126
126/126
126/126
144
144/144
144/144
144/144
144/144
144/144
170
170/170
170/170
170/170
170/170
170/170
60
60
60
60
60
60
69
69
69
69
69
69
82
82
82
82
82
82
46
52
63
MCA
41.1
41.1/42.4
47.8/53.9
67.1/76.3
87.0/99.1
103.3/117.9
43.2
43.2/45.0
50.4/56.5
69.8/78.9
89.6/101.8
105.9/120.5
27.8
27.8/28.0
35.9/40.1
50.3/56.6
63.3/71.6
77.5/88.3
28.1
28.1/28.4
36.3/40.5
50.6/57.0
63.6/72.0
77.9/88.6
30.4
30.4/31.3
39.1/43.4
53.5/59.9
66.5/74.9
80.8/91.5
13.5
13.5
21.1
24.9
38.5
42.3
14
14.0
21.8
25.5
39.1
42.9
14.8
14.8
22.8
26.5
40.1
43.9
11.7
11.8
12.6
w/ P.E. (pwrd fr/unit)
MAX
FUSE or
DISC. SIZE
HACR
BRKR
FLA
LRA
60
40
152
60/60
40/40
152/152
60/60
44/50
152/152
70/80
62/70
152/152
90/100
80/91
152/152
110/125
95/108
152/152
60
42
177
60/60
42/42
177/177
60/60
46/52
177/177
70/80
64/73
177/177
90/110
82/94
177/177
110/125
97/111
177/177
40
27
128
40/40
27/27
128/128
40/45
33/37
128/128
60/60
46/52
128/128
70/80
58/66
128/128
80/90
71/81
128/128
40
28
146
40/40
28/28
146/146
40/45
33/37
146/146
60/60
47/52
146/146
70/80
59/66
146/146
80/90
72/82
146/146
45
30
172
45/45
30/30
172/172
45/45
36/40
172/172
60/60
49/55
172/172
70/80
61/69
172/172
90/100
74/84
172/172
20
13
61
20
13
61
25
19
61
25
23
61
40
35
61
45
39
61
20
14
70
20
14
70
25
20
70
30
23
70
40
36
70
45
39
70
20
15
83
20
15
83
25
21
83
30
24
83
45
37
83
45
40
83
15
12
48
15
12
54
15
13
65
Nominal values, listed as 208/240V, 480V or 600V as appropriate.
513 31 3209 02
150
ELECTRICAL INFORMATION (UNITS PRODUCED PRIOR TO JULY 30, 2012) cont.
Table 43 – RAS072 Unit Wire/Fuse or HACR Breaker Sizing Data 1 Stage Cooling With 1 Speed Indoor Fan Motor
ELECTRIC HEATER
NO C.O. or UNPWR C.O.
NO P.E.
NOM.
V-PH-Hz.
IFM
TYPE
STD
208/
230-3-60
MED
HIGH
STD
460-3-60
MED
*
FLA
LRA
45
30
157
MCA
32.4
DISC. SIZE
MAX
FUSE or
HACR
BRKR
FLA
50
32
159
DISC. SIZE
LRA
Nom* (kW)
None
FLA
None
MCA
30.5
4.9/6.5
13.6/15.6
30.5/30.5
45/45
30/30
157/157
32.4/32.4
50/50
32/32
159/159
7.9/10.5
21.9/25.3
33.9/38.1
45/45
31/35
157/157
36.3/40.5
50/50
33/37
159/159
12.0/16.0
33.4/38.5
48.3/54.6
50/60
44/50
157/157
50.6/57.0
60/60
47/52
159/159
15.8/21.0
43.8/50.5
61.3/69.6
70/70
56/64
157/157
63.6/72.0
70/80
59/66
159/159
19.9/26.5
55.2/63.8
75.5/86.3
80/90
69/79
157/157
77.9/88.6
80/90
72/82
159/159
None
None
32.8
50
32
183
34.7
50
34
185
4.9/6.5
13.6/15.6
32.8/32.8
50/50
32/32
183/183
34.7/34.7
50/50
34/34
185/185
7.9/10.5
21.9/25.3
36.8/41.0
50/50
34/38
183/183
39.1/43.4
50/50
36/40
185/185
12.0/16.0
33.4/38.5
51.1/57.5
60/60
47/53
183/183
53.5/59.9
60/60
49/55
185/185
15.8/21.0
43.8/50.5
64.1/72.5
70/80
59/67
183/183
66.5/74.9
70/80
61/69
185/185
19.9/26.5
55.2/63.8
78.4/89.1
80/90
72/82
183/183
80.8/91.5
90/100
74/84
185/185
None
None
32.8
50
32
183
34.7
50
34
185
4.9/6.5
13.6/15.6
32.8/32.8
50/50
32/32
183/183
34.7/34.7
50/50
34/34
185/185
7.9/10.5
21.9/25.3
36.8/41.0
50/50
34/38
183/183
39.1/43.4
50/50
36/40
185/185
12.0/16.0
33.4/38.5
51.1/57.5
60/60
47/53
183/183
53.5/59.9
60/60
49/55
185/185
15.8/21.0
43.8/50.5
64.1/72.5
70/80
59/67
183/183
66.5/74.9
70/80
61/69
185/185
19.9/26.5
55.2/63.8
78.4/89.1
80/90
72/82
183/183
80.8/91.5
90/100
74/84
185/185
None
None
15.5
25
15
79
16.5
25
16
80
6.0
7.2
15.5
25
15
79
16.5
25
16
80
11.5
13.8
20.5
25
19
79
21.8
25
20
80
14.0
16.8
24.3
25
22
79
25.5
30
23
80
23.0
27.7
37.9
40
35
79
39.1
40
36
80
25.5
30.7
41.6
45
38
79
42.9
45
39
80
None
None
16.3
25
16
92
17.3
25
17
93
6.0
7.2
16.3
25
16
92
17.3
25
17
93
11.5
13.8
21.5
25
20
92
22.8
25
21
93
14.0
16.8
25.3
30
23
92
26.5
30
24
93
23.0
27.7
38.9
40
36
92
40.1
45
37
93
25.5
30.7
42.6
45
39
92
43.9
45
40
93
None
None
17.3
25
17
101
18.3
25
18
102
6.0
7.2
17.3
25
17
101
18.3
25
18
102
11.5
13.8
22.8
25
21
101
24.0
25
22
102
14.0
16.8
26.5
30
24
101
27.8
30
26
102
23.0
27.7
40.1
45
37
101
41.4
45
38
102
25.5
30.7
43.9
45
40
101
45.1
50
42
102
STD
None
None
11.9
15
12
63
13.8
20
14
65
MED
None
None
12.7
20
12
74
14.6
20
15
76
HIGH
None
None
12.7
20
12
74
14.6
20
15
76
HIGH
575-3-60
w/ P.E. (pwrd fr/unit)
MAX
FUSE or
HACR
BRKR
Nominal values, listed as 208/240V, 480V or 600V as appropriate.
151
513 31 3209 02
ELECTRICAL INFORMATION (UNITS PRODUCED PRIOR TO JULY 30, 2012) cont.
Table 44 – RAS091 Unit Wire/Fuse or HACR Breaker Sizing Data 1 Stage Cooling With 1 Speed Indoor Fan Motor
ELECTRIC HEATER
NOM.
V-PH-Hz.
IFM
TYPE
STD
208/
230-3-60
MED
HIGH
STD
460-3-60
MED
HIGH
STD
575-3-60
MED
HIGH
*
Nom* (kW)
None
7.8/10.4
12.0/16.0
18.6/24.8
24.0/32.0
31.8/42.4
None
7.8/10.4
12.0/16.0
18.6/24.8
24.0/32.0
31.8/42.4
None
7.8/10.4
12.0/16.0
18.6/24.8
24.0/32.0
31.8/42.4
None
13.9
16.5
27.8
33.0
41.7
None
13.9
16.5
27.8
33.0
41.7
None
13.9
16.5
27.8
33.0
41.7
None
17.0
34.0
None
17.0
34.0
None
17.0
34.0
FLA
None
21.7/25.0
33.4/38.5
51.7/59.7
66.7/77.0
88.4/102.0
None
21.7/25.0
33.4/38.5
51.7/59.7
66.7/77.0
88.4/102.0
None
21.7/25.0
33.4/38.5
51.7/59.7
66.7/77.0
88.4/102.0
None
16.7
19.8
33.4
39.7
50.2
None
16.7
19.8
33.4
39.7
50.2
None
16.7
19.8
33.4
39.7
50.2
None
20.4
40.9
None
20.4
40.9
None
20.4
40.9
MCA
39.5
39.5/39.5
48.3/54.6
71.1/81.1
89.9/102.8
117.0/134.0
41.8
41.8/41.8
51.1/57.5
74.0/84.0
92.8/105.6
119.9/136.9
49.3
49.3/50.0
60.5/66.9
83.4/93.4
102.1/115.0
129.3/146.3
19.5
24.1
28.0
45.0
52.9
66.0
20.3
25.1
29.0
46.0
53.9
67.0
24.3
30.1
34.0
51.0
58.9
72.0
14.9
28.5
54.1
15.3
29.0
54.6
18.1
32.5
58.1
NO C.O. or UNPWR C.O.
NO P.E.
MAX
DISC. SIZE
FUSE or
HACR
BRKR
MCA
FLA
LRA
60
38
191
43.3
60/60
38/38
191/191
43.3/43.3
60/60
44/50
191/191
53.0/59.4
80/90
65/75
191/191
75.9/85.9
90/110
83/95
191/191
94.6/107.5
125/150
108/123
191/191
121.8/138.8
60
41
228
45.6
60/60
41/41
228/228
45.6/45.6
60/60
47/53
228/228
55.9/62.3
80/90
68/77
228/228
78.8/88.8
100/110
85/97
228/228
97.5/110.4
125/150
110/126
228/228
124.6/141.6
60
49
254
53.1
60/60
49/49
254/254
53.1/54.8
70/70
56/62
254/254
65.3/71.6
90/100
77/86
254/254
88.1/98.1
110/125
94/106
254/254
106.9/119.8
150/150
119/135
254/254
134.0/151.0
30
19
113
21.3
30
22
113
26.4
30
26
113
30.3
50
41
113
47.3
60
49
113
55.1
70
61
113
68.3
30
20
132
22.1
30
23
132
27.4
30
27
132
31.3
50
42
132
48.3
60
50
132
56.1
70
62
132
69.3
30
24
145
26.1
35
28
145
32.4
35
31
145
36.3
60
47
145
53.3
60
54
145
61.1
80
66
145
74.3
20
14
89
18.7
30
26
89
33.3
60
50
89
58.9
20
15
104
19.1
30
27
104
33.8
60
50
104
59.4
25
18
118
21.9
35
30
118
37.3
60
53
118
62.9
w/ P.E. (pwrd fr/unit)
MAX
DISC. SIZE
FUSE or
HACR
BRKR
FLA
LRA
60
43
195
60/60
43/43
195/195
60/60
49/55
195/195
80/90
70/79
195/195
100/110
87/99
195/195
125/150
112/128
195/195
60
45
232
60/60
45/45
232/232
60/70
51/57
232/232
80/90
72/82
232/232
100/125
90/102
232/232
125/150
115/130
232/232
60
54
258
60/60
54/54
258/258
70/80
60/66
258/258
90/100
81/90
258/258
110/125
98/110
258/258
150/175
123/139
258/258
30
21
115
30
24
115
35
28
115
50
43
115
60
51
115
70
63
115
30
22
134
30
25
134
35
29
134
50
44
134
60
52
134
70
64
134
30
26
147
35
30
147
40
33
147
60
49
147
70
56
147
80
68
147
25
19
93
35
31
93
60
54
93
25
19
108
35
31
108
60
55
108
30
23
122
40
34
122
70
58
122
Nominal values, listed as 208/240V, 480V or 600V as appropriate.
513 31 3209 02
152
ELECTRICAL INFORMATION (UNITS PRODUCED PRIOR TO JULY 30, 2012) cont.
Table 45 – RAS090 Unit Wire/Fuse or HACR Breaker Sizing Data 2 Stage Cooling With 1 Speed Indoor Fan Motor
ELECTRIC HEATER
NOM.
V-PH-Hz.
IFM
TYPE
STD
208/
230-3-60
MED
HIGH
STD
460-3-60
MED
HIGH
STD
575-3-60
MED
HIGH
*
Nom* (kW)
7.8/10.4
12.0/16.0
18.6/24.8
24.0/32.0
31.8/42.4
7.8/10.4
12.0/16.0
18.6/24.8
24.0/32.0
31.8/42.4
7.8/10.4
12.0/16.0
18.6/24.8
24.0/32.0
31.8/42.4
13.9
16.5
27.8
33.0
41.7
13.9
16.5
27.8
33.0
41.7
13.9
16.5
27.8
33.0
41.7
17.0
34.0
17.0
34.0
17.0
34.0
FLA
21.7/25.0
33.4/38.5
51.7/59.7
66.7/77.0
88.4/102.0
21.7/25.0
33.4/38.5
51.7/59.7
66.7/77.0
88.4/102.0
21.7/25.0
33.4/38.5
51.7/59.7
66.7/77.0
88.4/102.0
16.7
19.8
33.4
39.7
50.2
16.7
19.8
33.4
39.7
50.2
16.7
19.8
33.4
39.7
50.2
20.4
40.9
20.4
40.9
20.4
40.9
NO C.O. or UNPWR C.O.
MCA
38.8
38.8/38.8
48.3/54.6
71.1/81.1
89.9/102.8
117.0/134.0
41.1
41.1/41.1
51.1/57.5
74.0/84.0
92.8/105.6
119.9/136.9
49.0
49.0/50.0
60.5/66.9
83.4/93.4
102.1/115.0
129.3/146.3
17.9
24.1
28.0
45.0
52.9
66.0
18.7
25.1
29.0
46.0
53.9
67.0
23.1
30.1
34.0
51.0
58.9
72.0
13.1
28.5
54.1
13.5
29.0
54.6
16.6
32.5
58.1
NO P.E.
MAX
FUSE or
HACR
BRKR
50
50/50
50/60
80/90
90/110
125/150
50
50/50
60/60
80/90
100/110
125/150
60
60/60
70/70
90/100
110/125
150/150
20
25
30
50
60
70
25
30
30
50
60
70
30
35
35
60
60
80
15
30
60
15
30
60
20
35
60
DISC. SIZE
FLA
41
41/41
44/50
65/75
83/95
108/123
43
43/43
47/53
68/77
85/97
110/126
52
52/52
56/62
77/86
94/106
119/135
19
22
26
41
49
61
20
23
27
42
50
62
24
28
31
47
54
66
14
26
50
14
27
50
17
30
53
LRA
193
193/193
193/193
193/193
193/193
193/193
230
230/230
230/230
230/230
230/230
230/230
256
256/256
256/256
256/256
256/256
256/256
95
95
95
95
95
95
114
114
114
114
114
114
127
127
127
127
127
127
77
77
77
92
92
92
106
106
106
MCA
42.6
42.6/42.6
53.0/59.4
75.9/85.9
94.6/107.5
121.8/138.8
44.9
44.9/45.4
55.9/62.3
78.8/88.8
97.5/110.4
124.6/141.6
52.8
52.8/54.8
65.3/71.6
88.1/98.1
106.9/119.8
134.0/151.0
19.7
26.4
30.3
47.3
55.1
68.3
20.5
27.4
31.3
48.3
56.1
69.3
24.9
32.4
36.3
53.3
61.1
74.3
16.9
33.3
58.9
17.3
33.8
59.4
20.4
37.3
62.9
w/ P.E. (pwrd fr/unit)
MAX
DISC. SIZE
FUSE or
HACR
BRKR
FLA
LRA
50
45
197
50/50
45/45
197/197
60/60
49/55
197/197
80/90
70/79
197/197
100/110
87/99
197/197
125/150
112/128
197/197
50
48
234
50/50
48/48
234/234
60/70
51/57
234/234
80/90
72/82
234/234
100/125
90/102
234/234
125/150
115/130
234/234
60
56
260
60/60
56/56
260/260
70/80
60/66
260/260
90/100
81/90
260/260
110/125
98/110
260/260
150/175
123/139
260/260
25
21
97
30
24
97
35
28
97
50
43
97
60
51
97
70
63
97
25
22
116
30
25
116
35
29
116
50
44
116
60
52
116
70
64
116
30
26
129
35
30
129
40
33
129
60
49
129
70
56
129
80
68
129
20
18
81
35
31
81
60
54
81
20
19
96
35
31
96
60
55
96
25
22
110
40
34
110
70
58
110
Nominal values, listed as 208/240V, 480V or 600V as appropriate.
153
513 31 3209 02
ELECTRICAL INFORMATION (UNITS PRODUCED PRIOR TO JULY 30, 2012) cont.
Table 46 – RAS090 Unit Wire/Fuse or HACR Breaker Sizing Data 2 Stage Cooling With 2 Speed Indoor Fan Motor
ELECTRIC HEATER
NO C.O. or UNPWR C.O.
NO P.E.
NOM.
V-PH-Hz.
IFM
TYPE
STD
208/
230-3-60
MED
HIGH
STD
460-3-60
MED
HIGH
STD
575-3-60
MED
HIGH
*
Nom
(kW)
7.8/10.4
12.0/16.0
18.6/24.8
24.0/32.0
31.8/42.4
7.8/10.4
12.0/16.0
18.6/24.8
24.0/32.0
31.8/42.4
7.8/10.4
12.0/16.0
18.6/24.8
24.0/32.0
31.8/42.4
13.9
16.5
27.8
33.0
41.7
13.9
16.5
27.8
33.0
41.7
13.9
16.5
27.8
33.0
41.7
17.0
34.0
17.0
34.0
17.0
34.0
FLA
21.7/25.0
33.4/38.5
51.7/59.7
66.7/77.0
88.4/102.0
21.7/25.0
33.4/38.5
51.7/59.7
66.7/77.0
88.4/102.0
21.7/25.0
33.4/38.5
51.7/59.7
66.7/77.0
88.4/102.0
16.7
19.8
33.4
39.7
50.2
16.7
19.8
33.4
39.7
50.2
16.7
19.8
33.4
39.7
50.2
20.4
40.9
20.4
40.9
20.4
40.9
MCA
39.4/39.2
39.4/39.2
49.0/55.1
71.9/81.6
90.6/103.3
117.8/134.5
42.2/41.4
42.2/41.4
52.5/57.9
75.4/84.4
94.1/106.0
121.3/137.3
47.2/46.3
47.2/47.1
58.8/64.0
81.6/90.5
100.4/112.1
127.5/143.4
18.2
24.5
28.4
45.4
53.3
66.4
19.1
25.6
29.5
46.5
54.4
67.5
21.8
28.9
32.8
49.8
57.6
70.8
13.5
29.0
54.6
15.2
31.1
56.8
17.4
33.3
58.9
MAX
FUSE or
HACR
BRKR
50/50
50/50
50/60
80/90
100/110
125/150
50/50
50/50
60/60
80/90
100/110
125/150
60/50
60/50
60/70
90/100
110/125
150/150
20
25
30
50
60
70
25
30
30
50
60
70
25
30
35
50
60
80
15
30
60
20
35
60
20
35
60
DISC. SIZE
FLA
41/41
41/41
45/51
66/75
83/95
108/124
45/44
45/44
48/53
69/78
87/98
112/126
50/49
50/49
54/59
75/83
92/103
117/132
19
23
26
42
49
61
20
24
27
43
50
62
23
27
30
46
53
65
14
27
50
16
29
52
18
31
54
LRA
197
197/197
197/197
197/197
197/197
197/197
227
227/227
227/227
227/227
227/227
227/227
262
262/262
262/262
262/262
262/262
262/262
97
97
97
97
97
97
113
113
113
113
113
113
130
130
130
130
130
130
79
79
79
92
92
92
106
106
106
MCA
43.2/43.0
43.2/43.0
53.8/59.9
76.6/86.4
95.4/108.0
122.5/139.3
46.0/45.2
46.0/45.8
57.3/62.6
80.1/89.1
98.9/110.8
126.0/142.0
51.0/50.1
51.0/51.9
63.5/68.8
86.4/95.3
105.1/116.9
132.3/148.1
20.0
26.8
30.6
47.6
55.5
68.6
20.9
27.9
31.8
48.8
56.6
69.8
23.6
31.1
35.0
52.0
59.9
73.0
17.3
33.8
59.4
19.0
35.9
61.5
21.2
38.0
63.6
w/ P.E. (pwrd fr/unit)
MAX
DISC. SIZE
FUSE or
HACR
BRKR
FLA
LRA
50/50
46/46
201
50/50
46/46
201/201
60/60
49/55
201/201
80/90
70/79
201/201
100/110
88/99
201/201
125/150
113/128
201/201
50/50
49/48
231
50/50
49/48
231/231
60/70
53/58
231/231
90/90
74/82
231/231
100/125
91/102
231/231
150/150
116/131
231/231
60/60
55/54
266
60/60
55/54
266/266
70/70
58/63
266/266
90/100
79/88
266/266
110/125
97/108
266/266
150/150
122/136
266/266
25
21
99
30
25
99
35
28
99
50
44
99
60
51
99
70
63
99
25
22
115
30
26
115
35
29
115
50
45
115
60
52
115
70
64
115
30
25
132
35
29
132
35
32
132
60
48
132
60
55
132
80
67
132
20
19
83
35
31
83
60
55
83
25
21
96
40
33
96
70
57
96
25
23
110
40
35
110
70
59
110
Nominal values, listed as 208/240V, 480V or 600V as appropriate.
513 31 3209 02
154
ELECTRICAL INFORMATION (UNITS PRODUCED PRIOR TO JULY 30, 2012) cont.
Table 47 – RAS101 Unit Wire/Fuse or HACR Breaker Sizing Data 1 Stage Cooling With 1 Speed Indoor Fan Motor
ELECTRIC HEATER
NOM.
V-PH-Hz.
IFM
TYPE
STD
208/
230-3-60
MED
HIGH
STD
460-3-60
MED
HIGH
STD
575-3-60
MED
HIGH
*
Nom* (kW)
None
7.8/10.4
12.0/16.0
18.6/24.8
24.0/32.0
31.8/42.4
None
7.8/10.4
12.0/16.0
18.6/24.8
24.0/32.0
31.8/42.4
None
7.8/10.4
12.0/16.0
18.6/24.8
24.0/32.0
31.8/42.4
None
13.9
16.5
27.8
33.0
41.7
None
13.9
16.5
27.8
33.0
41.7
None
13.9
16.5
27.8
33.0
41.7
None
17.0
34.0
None
17.0
34.0
None
17.0
34.0
FLA
None
21.7/25.0
33.4/38.5
51.7/59.7
66.7/77.0
88.4/102.0
None
21.7/25.0
33.4/38.5
51.7/59.7
66.7/77.0
88.4/102.0
None
21.7/25.0
33.4/38.5
51.7/59.7
66.7/77.0
88.4/102.0
None
16.7
19.8
33.4
39.7
50.2
None
16.7
19.8
33.4
39.7
50.2
None
16.7
19.8
33.4
39.7
50.2
None
20.4
40.9
None
20.4
40.9
None
20.4
40.9
NO C.O. or UNPWR C.O.
MCA
45.1
45.1/45.1
48.3/54.6
71.1/81.1
89.9/102.8
117.0/134.0
45.1
45.1/45.1
48.3/54.6
71.1/81.1
89.9/102.8
117.0/134.0
49.9
49.9/49.9
54.3/60.6
77.1/87.1
95.9/108.8
123.0/140.0
22.6
24.1
28.0
45.0
52.9
66.0
22.6
24.1
28.0
45.0
52.9
66.0
24.4
26.4
30.3
47.3
55.1
68.3
18.9
28.5
54.1
18.5
28.0
53.6
19.3
29.0
54.6
NO P.E.
MAX
FUSE or
HACR
BRKR
60
60/60
60/60
80/90
90/110
125/150
60
60/60
60/60
80/90
90/110
125/150
60
60/60
60/70
80/90
100/110
125/150
30
30
30
50
60
70
30
30
30
50
60
70
30
30
35
50
60
70
30
30
60
30
30
60
30
30
60
DISC. SIZE
FLA
43
43/43
44/50
65/75
83/95
108/123
43
43/43
44/50
65/75
83/95
108/123
49
49/49
50/56
71/80
88/100
113/129
22
22
26
41
49
61
22
22
26
41
49
61
24
24
28
43
51
63
18
26
50
18
26
49
19
27
50
LRA
222
222/222
222/222
222/222
222/222
222/222
233
233/233
233/233
233/233
233/233
233/233
276
276/276
276/276
276/276
276/276
276/276
108
108
108
108
108
108
114
114
114
114
114
114
136
136
136
136
136
136
91
91
91
95
95
95
106
106
106
MCA
48.9
48.9/48.9
53.0/59.4
75.9/85.9
94.6/107.5
121.8/138.8
48.9
48.9/48.9
53.0/59.4
75.9/85.9
94.6/107.5
121.8/138.8
53.7
53.7/53.7
59.0/65.4
81.9/91.9
100.6/113.5
127.8/144.8
24.4
26.4
30.3
47.3
55.1
68.3
24.4
26.4
30.3
47.3
55.1
68.3
26.2
28.6
32.5
49.5
57.4
70.5
22.7
33.3
58.9
22.3
32.8
58.4
23.1
33.8
59.4
w/ P.E. (pwrd fr/unit)
MAX
DISC. SIZE
FUSE or
HACR
BRKR
FLA
LRA
60
48
226
60/60
48/48
226/226
60/60
49/55
226/226
80/90
70/79
226/226
100/110
87/99
226/226
125/150
112/128
226/226
60
48
237
60/60
48/48
237/237
60/60
49/55
237/237
80/90
70/79
237/237
100/110
87/99
237/237
125/150
112/128
237/237
80
53
280
80/80
53/53
280/280
80/80
54/60
280/280
90/100
75/85
280/280
110/125
93/104
280/280
150/150
118/133
280/280
30
24
110
30
24
110
35
28
110
50
43
110
60
51
110
70
63
110
30
24
116
30
24
116
35
28
116
50
43
116
60
51
116
70
63
116
30
26
138
30
26
138
40
30
138
50
46
138
60
53
138
80
65
138
30
23
95
35
31
95
60
54
95
30
22
99
35
30
99
60
54
99
30
23
110
35
31
110
60
55
110
Nominal values, listed as 208/240V, 480V or 600V as appropriate.
155
513 31 3209 02
ELECTRICAL INFORMATION (UNITS PRODUCED PRIOR TO JULY 30, 2012) cont.
Table 48 – RAS102 Unit Wire/Fuse or HACR Breaker Sizing Data 2 Stage Cooling With 1 Speed Indoor Fan Motor
ELECTRIC HEATER
NOM.
V-PH-Hz.
IFM
TYPE
STD
208/
230-3-60
MED
HIGH
STD
460-3-60
MED
HIGH
STD
575-3-60
MED
HIGH
*
Nom* (kW)
7.8/10.4
12.0/16.0
18.6/24.8
24.0/32.0
31.8/42.4
7.8/10.4
12.0/16.0
18.6/24.8
24.0/32.0
31.8/42.4
7.8/10.4
12.0/16.0
18.6/24.8
24.0/32.0
31.8/42.4
13.9
16.5
27.8
33.0
41.7
13.9
16.5
27.8
33.0
41.7
13.9
16.5
27.8
33.0
41.7
17.0
34.0
17.0
34.0
17.0
34.0
FLA
21.7/25.0
33.4/38.5
51.7/59.7
66.7/77.0
88.4/102.0
21.7/25.0
33.4/38.5
51.7/59.7
66.7/77.0
88.4/102.0
21.7/25.0
33.4/38.5
51.7/59.7
66.7/77.0
88.4/102.0
16.7
19.8
33.4
39.7
50.2
16.7
19.8
33.4
39.7
50.2
16.7
19.8
33.4
39.7
50.2
20.4
40.9
20.4
40.9
20.4
40.9
MCA
40.0
40.0/40.0
48.3/54.6
71.1/81.1
89.9/102.8
117.0/134.0
40.0
40.0/40.0
48.3/54.6
71.1/81.1
89.9/102.8
117.0/134.0
44.8
44.8/44.8
54.3/60.6
77.1/87.1
95.9/108.8
123.0/140.0
18.3
24.1
28.0
45.0
52.9
66.0
18.3
24.1
28.0
45.0
52.9
66.0
20.1
26.4
30.3
47.3
55.1
68.3
15.9
28.5
54.1
15.5
28.0
53.6
16.3
29.0
54.6
NO C.O. or UNPWR C.O.
NO P.E.
w/ P.E. (pwrd fr/unit)
MAX FUSE
MAX FUSE
DISC. SIZE
DISC. SIZE
or HACR
or HACR
BRKR
BRKR
MCA
FLA
LRA
FLA
LRA
50
42
208
43.8
50
46
212
50/50
42/42
208/208
43.8/43.8
50/50
46/46
212/212
50/60
44/50
208/208
53.0/59.4
60/60
49/55
212/212
80/90
65/75
208/208
75.9/85.9
80/90
70/79
212/212
90/110
83/95
208/208
94.6/107.5
100/110
87/99
212/212
125/150
108/123
208/208
121.8/138.8
125/150
112/128
212/212
50
42
219
43.8
50
46
223
50/50
42/42
219/219
43.8/43.8
50/50
46/46
223/223
50/60
44/50
219/219
53.0/59.4
60/60
49/55
223/223
80/90
65/75
219/219
75.9/85.9
80/90
70/79
223/223
90/110
83/95
219/219
94.6/107.5
100/110
87/99
223/223
125/150
108/123
219/219
121.8/138.8
125/150
112/128
223/223
50
47
262
48.6
60
52
266
50/50
47/47
262/262
48.6/48.6
60/60
52/52
266/266
60/70
50/56
262/262
59.0/65.4
60/70
54/60
266/266
80/90
71/80
262/262
81.9/91.9
90/100
75/85
266/266
100/110
88/100
262/262
100.6/113.5
110/125
93/104
266/266
125/150
113/129
262/262
127.8/144.8
150/150
118/133
266/266
20
19
109
20.1
25
21
111
25
22
109
26.4
30
24
111
30
26
109
30.3
35
28
111
50
41
109
47.3
50
43
111
60
49
109
55.1
60
51
111
70
61
109
68.3
70
63
111
20
19
115
20.1
25
21
117
25
22
115
26.4
30
24
117
30
26
115
30.3
35
28
117
50
41
115
47.3
50
43
117
60
49
115
55.1
60
51
117
70
61
115
68.3
70
63
117
25
21
137
21.9
25
23
139
30
24
137
28.6
30
26
139
35
28
137
32.5
35
30
139
50
43
137
49.5
50
46
139
60
51
137
57.4
60
53
139
70
63
137
70.5
80
65
139
20
17
85
19.7
25
21
89
30
26
85
33.3
35
31
89
60
50
85
58.9
60
54
89
20
16
89
19.3
25
20
93
30
26
89
32.8
35
30
93
60
49
89
58.4
60
54
93
20
17
100
20.1
25
21
104
30
27
100
33.8
35
31
104
60
50
100
59.4
60
55
104
Nominal values, listed as 208/240V, 480V or 600V as appropriate.
513 31 3209 02
156
ELECTRICAL INFORMATION (UNITS PRODUCED PRIOR TO JULY 30, 2012) cont.
Table 49 – RAS102 Unit Wire/Fuse or HACR Breaker Sizing Data 2 Stage Cooling With 2 Speed Indoor Fan Motor
ELECTRIC HEATER
NOM
V-PH-Hz.
IFM
TYPE
STD
208/
230-3-60
MED
HIGH
STD
460-3-60
MED
HIGH
STD
575-3-60
MED
HIGH
*
Nom
(kW)
7.8/10.4
12.0/16.0
18.6/24.8
24.0/32.0
31.8/42.4
7.8/10.4
12.0/16.0
18.6/24.8
24.0/32.0
31.8/42.4
7.8/10.4
12.0/16.0
18.6/24.8
24.0/32.0
31.8/42.4
13.9
16.5
27.8
33.0
41.7
13.9
16.5
27.8
33.0
41.7
13.9
16.5
27.8
33.0
41.7
17.0
34.0
17.0
34.0
17.0
34.0
FLA
21.7/25.0
33.4/38.5
51.7/59.7
66.7/77.0
88.4/102.0
21.7/25.0
33.4/38.5
51.7/59.7
66.7/77.0
88.4/102.0
21.7/25.0
33.4/38.5
51.7/59.7
66.7/77.0
88.4/102.0
16.7
19.8
33.4
39.7
50.2
16.7
19.8
33.4
39.7
50.2
16.7
19.8
33.4
39.7
50.2
20.4
40.9
20.4
40.9
20.4
40.9
NO C.O. or UNPWR C.O.
MCA
40.6/40.4
40.6/40.4
49.0/55.1
71.9/81.6
90.6/103.3
117.8/134.5
41.9/41.6
41.9/41.6
50.6/56.6
73.5/83.1
92.3/104.8
119.4/136.0
45.6/44.6
45.6/44.6
55.3/60.4
78.1/86.9
96.9/108.5
124.0/139.8
18.6
24.5
28.4
45.4
53.3
66.4
19.5
25.6
29.5
46.5
54.4
67.5
20.6
27.0
30.9
47.9
55.8
68.9
16.3
29.0
54.6
17.0
29.9
55.5
18.0
31.1
56.8
NO P.E.
MAX
FUSE or
HACR
BRKR
50/50
50/50
50/60
80/90
100/110
125/150
50/50
50/50
60/60
80/90
100/110
125/150
60/50
60/50
60/70
80/90
100/110
125/150
25
25
30
50
60
70
25
30
30
50
60
70
25
30
35
50
60
70
20
30
60
20
30
60
20
35
60
DISC. SIZE
FLA
43/42
43/42
45/51
66/75
83/95
108/124
44/44
44/44
47/52
68/76
85/96
110/125
48/47
48/47
51/56
72/80
89/100
114/129
20
23
26
42
49
61
21
24
27
43
50
62
22
25
28
44
51
63
17
27
50
18
27
51
19
29
52
LRA
212
212/212
212/212
212/212
212/212
212/212
216
216/216
216/216
216/216
216/216
216/216
266
266/266
266/266
266/266
266/266
266/266
111
111
111
111
111
111
114
114
114
114
114
114
139
139
139
139
139
139
87
87
87
91
91
91
100
100
100
MCA
44.4/44.2
44.4/44.2
53.8/59.9
76.6/86.4
95.4/108.0
122.5/139.3
45.7/45.4
45.7/45.4
55.4/61.4
78.3/87.9
97.0/109.5
124.1/140.8
49.4/48.4
49.4/48.4
60.0/65.1
82.9/91.6
101.6/113.3
128.8/144.5
20.4
26.8
30.6
47.6
55.5
68.6
21.3
27.9
31.8
48.8
56.6
69.8
22.4
29.3
33.1
50.1
58.0
71.1
20.1
33.8
59.4
20.8
34.6
60.3
21.8
35.9
61.5
w/ P.E. (pwrd fr/unit)
MAX
DISC. SIZE
FUSE or
HACR
BRKR
FLA
LRA
50/50
47/47
216
50/50
47/47
216/216
60/60
49/55
216/216
80/90
70/79
216/216
100/110
88/99
216/216
125/150
113/128
216/216
60/50
48/48
220
60/50
48/48
220/220
60/70
51/56
220/220
80/90
72/81
220/220
100/110
89/101
220/220
125/150
114/129
220/220
60/60
53/52
270
60/60
53/52
270/270
60/70
55/60
270/270
90/100
76/84
270/270
110/125
93/104
270/270
150/150
118/133
270/270
25
22
113
30
25
113
35
28
113
50
44
113
60
51
113
70
63
113
25
23
116
30
26
116
35
29
116
50
45
116
60
52
116
70
64
116
25
24
141
30
27
141
35
30
141
60
46
141
60
53
141
80
65
141
25
21
91
35
31
91
60
55
91
25
22
95
35
32
95
70
55
95
25
23
104
40
33
104
70
57
104
Nominal values, listed as 208/240V, 480V or 600V as appropriate.
157
513 31 3209 02
ELECTRICAL INFORMATION (UNITS PRODUCED PRIOR TO JULY 30, 2012) cont.
Table 50 – RAS121 Unit Wire/Fuse or HACR Breaker Sizing Data 1 Stage Cooling With 1 Speed Indoor Fan Motor
ELECTRIC HEATER
NOM.
V-PH-Hz.
IFM
TYPE
STD
208/
230-3-60
MED
HIGH
STD
460-3-60
MED
HIGH
STD
575-3-60
MED
HIGH
*
Nom* (kW)
None
7.8/10.4
12.0/16.0
24.0/32.0
31.8/42.4
37.6/50.0
None
7.8/10.4
12.0/16.0
24.0/32.0
31.8/42.4
37.6/50.0
None
7.8/10.4
12.0/16.0
24.0/32.0
31.8/42.4
37.6/50.0
None
13.9
16.5
33.0
41.7
50.0
None
13.9
16.5
33.0
41.7
50.0
None
13.9
16.5
33.0
41.7
50.0
None
17.0
34.0
51.0
None
17.0
34.0
51.0
None
17.0
34.0
51.0
FLA
None
21.7/25.0
33.4/38.5
66.7/77.0
88.4/102.0
104.2/120.3
None
21.7/25.0
33.4/38.5
66.7/77.0
88.4/102.0
104.2/120.3
None
21.7/25.0
33.4/38.5
66.7/77.0
88.4/102.0
104.2/120.3
None
16.7
19.8
39.7
50.2
60.1
None
16.7
19.8
39.7
50.2
60.1
None
16.7
19.8
39.7
50.2
60.1
None
20.4
40.9
61.3
None
20.4
40.9
61.3
None
20.4
40.9
61.3
NO C.O. or UNPWR C.O.
MCA
45.8
45.8/45.8
48.3/54.6
89.9/102.8
117.0/134.0
136.8/126.8
50.6
50.6/50.6
54.3/60.6
95.9/108.8
123.0/140.0
142.8/132.8
55.6
55.6/55.6
60.5/66.9
102.1/115.0
129.3/146.3
149.0/139.1
25.1
25.1
28.0
52.9
66.0
63.4
26.9
26.9
30.3
55.1
68.3
65.6
29.9
30.1
34.0
58.9
72.0
69.4
18.5
28.0
53.6
63.8
19.3
29.0
54.6
64.8
22.1
32.5
58.1
68.3
NO P.E.
MAX
FUSE or
HACR
BRKR
60
60/60
60/60
90/110
125/150
150/150
60
60/60
60/80
100/110
125/150
150/150
80
80/80
80/80
110/125
150/150
150/175
30
30
30
60
70
70
40
40
40
60
70
80
45
45
45
60
80
80
30
30
60
70
30
30
60
70
30
35
60
80
DISC. SIZE
FLA
44
44/44
44/50
83/95
108/123
126/144
50
50/50
50/56
88/100
113/129
131/150
55
55/55
56/62
94/106
119/135
137/156
24
24
26
49
61
72
26
26
28
51
63
74
30
30
31
54
66
78
18
26
49
73
19
27
50
74
22
30
53
77
LRA
263
263/263
263/263
263/263
263/263
263/263
306
306/306
306/306
306/306
306/306
306/306
315
315/315
315/315
315/315
315/315
315/315
133
133
133
133
133
133
155
155
155
155
155
155
159
159
159
159
159
159
95
95
95
95
106
106
106
106
120
120
120
120
MCA
49.6
49.6/49.6
53.0/59.4
94.6/107.5
121.8/138.8
141.5/131.6
54.4
54.4/54.4
59.0/65.4
100.6/113.5
127.8/144.8
147.5/137.6
59.4
59.4/59.4
65.3/71.6
106.9/119.8
134.0/151.0
153.8/143.8
26.9
26.9
30.3
55.1
68.3
65.6
28.7
28.7
32.5
57.4
70.5
67.9
31.7
32.4
36.3
61.1
74.3
71.6
22.3
32.8
58.4
68.6
23.1
33.8
59.4
69.6
25.9
37.3
62.9
73.1
w/ P.E. (pwrd fr/unit)
MAX
DISC. SIZE
FUSE or
HACR
BRKR
FLA
LRA
60
48
267
60/60
48/48
267/267
60/60
49/55
267/267
100/110
87/99
267/267
125/150
112/128
267/267
150/150
130/149
267/267
80
54
310
80/80
54/54
310/310
80/80
54/60
310/310
110/125
93/104
310/310
150/150
118/133
310/310
150/150
136/154
310/310
80
60
319
80/80
60/60
319/319
80/80
60/66
319/319
110/125
98/110
319/319
150/175
123/139
319/319
175/175
141/160
319/319
40
26
135
40
26
135
40
28
135
60
51
135
70
63
135
70
74
135
45
28
157
45
28
157
45
30
157
60
53
157
80
65
157
80
76
157
45
32
161
45
32
161
45
33
161
70
56
161
80
68
161
80
80
161
30
22
99
35
30
99
60
54
99
80
77
99
30
23
110
35
31
110
60
55
110
80
78
110
30
26
124
40
34
124
70
58
124
80
81
124
Nominal values, listed as 208/240V, 480V or 600V as appropriate.
513 31 3209 02
158
ELECTRICAL INFORMATION (UNITS PRODUCED PRIOR TO JULY 30, 2012) cont.
Table 51 – RAS120 Unit Wire/Fuse or HACR Breaker Sizing Data 2 Stage Cooling With 1 Speed Indoor Fan Motor
ELECTRIC HEATER
NO C.O. or UNPWR C.O.
NO P.E.
NOM.
V-PH-Hz.
IFM
TYPE
STD
208/
230-3-60
MED
HIGH
STD
460-3-60
MED
HIGH
STD
575-3-60
MED
HIGH
*
Nom* (kW)
7.8/10.4
12.0/16.0
24.0/32.0
31.8/42.4
37.6/50.0
7.8/10.4
12.0/16.0
24.0/32.0
31.8/42.4
37.6/50.0
7.8/10.4
12.0/16.0
24.0/32.0
31.8/42.4
37.6/50.0
13.9
16.5
33.0
41.7
50.0
13.9
16.5
33.0
41.7
50.0
13.9
16.5
33.0
41.7
50.0
17.0
34.0
51.0
17.0
34.0
51.0
17.0
34.0
51.0
FLA
21.7/25.0
33.4/38.5
66.7/77.0
88.4/102.0
104.2/120.3
21.7/25.0
33.4/38.5
66.7/77.0
88.4/102.0
104.2/120.3
21.7/25.0
33.4/38.5
66.7/77.0
88.4/102.0
104.2/120.3
16.7
19.8
39.7
50.2
60.1
16.7
19.8
39.7
50.2
60.1
16.7
19.8
39.7
50.2
60.1
20.4
40.9
61.3
20.4
40.9
61.3
20.4
40.9
61.3
MCA
43.7
43.7/43.7
48.3/54.6
89.9/102.8
117.0/134.0
136.8/126.8
48.5
48.5/48.5
54.3/60.6
95.9/108.8
123.0/140.0
142.8/132.8
53.5
53.5/53.5
60.5/66.9
102.1/115.0
129.3/146.3
149.0/139.1
21.5
24.1
28.0
52.9
66.0
63.4
23.3
26.4
30.3
55.1
68.3
65.6
26.3
30.1
34.0
58.9
72.0
69.4
16.2
28.0
53.6
63.8
17.0
29.0
54.6
64.8
19.8
32.5
58.1
68.3
MAX
FUSE or
HACR
BRKR
50
50/50
50/60
90/110
125/150
150/150
60
60/60
60/70
100/110
125/150
150/150
60
60/60
70/70
110/125
150/150
150/175
25
25
30
60
70
70
30
30
35
60
70
80
30
35
35
60
80
80
20
30
60
70
20
30
60
70
25
35
60
80
w/ P.E. (pwrd fr/unit)
DISC. SIZE
FLA
46
46/46
46/50
83/95
108/123
126/144
51
51/51
51/56
88/100
113/129
131/150
57
57/57
57/62
94/106
119/135
137/156
23
23
26
49
61
72
25
25
28
51
63
74
28
28
31
54
66
78
17
26
49
73
18
27
50
74
21
30
53
77
LRA
258
258/258
258/258
258/258
258/258
258/258
301
301/301
301/301
301/301
301/301
301/301
310
310/310
310/310
310/310
310/310
310/310
123
123
123
123
123
123
145
145
145
145
145
145
149
149
149
149
149
149
93
93
93
93
104
104
104
104
118
118
118
118
MCA
47.5
47.5/47.5
53.0/59.4
94.6/107.5
121.8/138.8
141.5/131.6
52.3
52.3/52.3
59.0/65.4
100.6/113.5
127.8/144.8
147.5/137.6
57.3
57.3/57.3
65.3/71.6
106.9/119.8
134.0/151.0
153.8/143.8
23.3
26.4
30.3
55.1
68.3
65.6
25.1
28.6
32.5
57.4
70.5
67.9
28.1
32.4
36.3
61.1
74.3
71.6
20.0
32.8
58.4
68.6
20.8
33.8
59.4
69.6
23.6
37.3
62.9
73.1
MAX
FUSE or
HACR
BRKR
60
60/60
60/60
100/110
125/150
150/150
60
60/60
60/70
110/125
150/150
150/150
70
70/70
70/80
110/125
150/175
175/175
30
30
35
60
70
70
30
30
35
60
80
80
35
35
40
70
80
80
25
35
60
80
25
35
60
80
30
40
70
80
DISC. SIZE
FLA
50
50/50
50/55
87/99
112/128
130/149
56
56/56
56/60
93/104
118/133
136/154
61
61/61
61/66
98/110
123/139
141/160
25
25
28
51
63
74
27
27
30
53
65
76
30
30
33
56
68
80
21
30
54
77
22
31
55
78
25
34
58
81
LRA
262
262/262
262/262
262/262
262/262
262/262
305
305/305
305/305
305/305
305/305
305/305
314
314/314
314/314
314/314
314/314
314/314
125
125
125
125
125
125
147
147
147
147
147
147
151
151
151
151
151
151
97
97
97
97
108
108
108
108
122
122
122
122
Nominal values, listed as 208/240V, 480V or 600V as appropriate.
159
513 31 3209 02
ELECTRICAL INFORMATION (UNITS PRODUCED PRIOR TO JULY 30, 2012) cont.
Table 52 – RAS120 Unit Wire/Fuse or HACR Breaker Sizing Data 2 Stage Cooling With 2 Speed Indoor Fan Motor
ELECTRIC HEATER
NOM.
V-PH-Hz.
IFM
TYPE
STD
208/
230-3-60
MED
HIGH
STD
460-3-60
MED
HIGH
STD
575-3-60
MED
HIGH
*
Nom
(kW)
7.8/10.4
12.0/16.0
24.0/32.0
31.8/42.4
37.6/50.0
7.8/10.4
12.0/16.0
24.0/32.0
31.8/42.4
37.6/50.0
7.8/10.4
12.0/16.0
24.0/32.0
31.8/42.4
37.6/50.0
13.9
16.5
33.0
41.7
50.0
13.9
16.5
33.0
41.7
50.0
13.9
16.5
33.0
41.7
50.0
17.0
34.0
51.0
17.0
34.0
51.0
17.0
34.0
51.0
FLA
21.7/25.0
33.4/38.5
66.7/77.0
88.4/102.0
104.2/120.3
21.7/25.0
33.4/38.5
66.7/77.0
88.4/102.0
104.2/120.3
21.7/25.0
33.4/38.5
66.7/77.0
88.4/102.0
104.2/120.3
16.7
19.8
39.7
50.2
60.1
16.7
19.8
39.7
50.2
60.1
16.7
19.8
39.7
50.2
60.1
20.4
40.9
61.3
20.4
40.9
61.3
20.4
40.9
61.3
NO C.O. or UNPWR C.O.
MCA
45.6/45.3
45.6/45.3
50.6/56.6
92.3/104.8
119.4/136.0
139.1/128.8
49.3/48.3
49.3/48.3
55.3/60.4
96.9/108.5
124.0/139.8
143.8/132.6
52.1/51.2
52.1/51.2
58.8/64.0
100.4/112.1
127.5/143.4
147.3/136.2
22.7
25.6
29.5
54.4
67.5
64.9
23.8
27.0
30.9
55.8
68.9
66.2
25.3
28.9
32.8
57.6
70.8
68.1
17.7
29.9
55.5
65.7
18.7
31.1
56.8
66.9
20.5
33.3
58.9
69.1
NO P.E.
MAX
FUSE or
HACR
BRKR
60/60
60/60
60/60
100/110
125/150
150/150
60/60
60/60
60/70
100/110
125/150
150/150
60/60
60/60
60/70
110/125
150/150
150/150
30
30
30
60
70
70
30
30
35
60
70
80
30
30
35
60
80
80
20
30
60
70
25
35
60
80
25
35
60
80
DISC. SIZE
FLA
48/47
48/47
48/52
85/96
110/125
128/146
52/51
52/51
52/56
89/100
114/129
132/150
55/54
55/54
55/59
92/103
117/132
135/153
24
24
27
50
62
73
25
25
28
51
63
75
27
27
30
53
65
76
19
27
51
75
20
29
52
76
22
31
54
78
LRA
255
255/255
255/255
255/255
255/255
255/255
305
305/305
305/305
305/305
305/305
305/305
316
316/316
316/316
316/316
316/316
316/316
122
122
122
122
122
122
147
147
147
147
147
147
152
152
152
152
152
152
95
95
95
95
104
104
104
104
118
118
118
118
MCA
49.4/49.1
49.4/49.1
55.4/61.4
97.0/109.5
124.1/140.8
143.9/133.6
53.1/52.1
53.1/52.1
60.0/65.1
101.6/113.3
128.8/144.5
148.5/137.3
55.9/55.0
55.9/55.0
63.5/68.8
105.1/116.9
132.3/148.1
152.0/140.9
24.5
27.9
31.8
56.6
69.8
67.1
25.6
29.3
33.1
58.0
71.1
68.5
27.1
31.1
35.0
59.9
73.0
70.4
21.5
34.6
60.3
70.4
22.5
35.9
61.5
71.7
24.3
38.0
63.6
73.8
w/ P.E. (pwrd fr/unit)
MAX
DISC. SIZE
FUSE or
HACR
BRKR
FLA
LRA
60/60
52/52
259
60/60
52/52
259/259
60/70
52/56
259/259
100/110
89/101
259/259
125/150
114/129
259/259
150/150
132/151
259/259
60/60
56/55
309
60/60
56/55
309/309
60/70
56/60
309/309
110/125
93/104
309/309
150/150
118/133
309/309
150/150
137/154
309/309
60/60
60/59
320
60/60
60/59
320/320
70/70
60/63
320/320
110/125
97/108
320/320
150/150
122/136
320/320
175/175
140/157
320/320
30
26
124
30
26
124
35
29
124
60
52
124
70
64
124
80
76
124
30
27
149
30
27
149
35
30
149
60
53
149
80
65
149
80
77
149
30
29
154
35
29
154
35
32
154
60
55
154
80
67
154
80
79
154
25
23
99
35
32
99
70
55
99
80
79
99
25
24
108
40
33
108
70
57
108
80
80
108
30
26
122
40
35
122
70
59
122
80
82
122
Nominal values, listed as 208/240V, 480V or 600V as appropriate.
513 31 3209 02
160
ELECTRICAL INFORMATION (UNITS PRODUCED PRIOR TO JULY 30, 2012) cont.
Table 53 – RAS150 Unit Wire/Fuse or HACR Breaker Sizing Data 2 Stage Cooling With 1 Speed Indoor Fan Motor
ELECTRIC HEATER
NOM.
V-PH-Hz.
IFM
TYPE
STD
208/
230-3-60
MED
HIGH
STD
460-3-60
MED
HIGH
STD
575-3-60
MED
HIGH
*
Nom* (kW)
7.8/10.4
12.0/16.0
24.0/32.0
31.8/42.4
37.6/50.0
7.8/10.4
12.0/16.0
24.0/32.0
31.8/42.4
37.6/50.0
7.8/10.4
12.0/16.0
24.0/32.0
31.8/42.4
37.6/50.0
13.9
16.5
33.0
41.7
50.0
13.9
16.5
33.0
41.7
50.0
13.9
16.5
33.0
41.7
50.0
17.0
34.0
51.0
17.0
34.0
51.0
17.0
34.0
51.0
FLA
21.7/25.0
33.4/38.5
66.7/77.0
88.4/102.0
104.2/120.3
21.7/25.0
33.4/38.5
66.7/77.0
88.4/102.0
104.2/120.3
21.7/25.0
33.4/38.5
66.7/77.0
88.4/102.0
104.2/120.3
16.7
19.8
39.7
50.2
60.1
16.7
19.8
39.7
50.2
60.1
16.7
19.8
39.7
50.2
60.1
20.4
40.9
61.3
20.4
40.9
61.3
20.4
40.9
61.3
NO C.O. or UNPWR C.O.
MCA
60.7
60.7/60.7
60.7/60.7
92.8/105.6
119.9/136.9
139.6/129.7
63.2
63.2/63.2
63.2/63.2
95.9/108.8
123.0/140.0
142.8/132.8
68.2
68.2/68.2
68.2/68.2
102.1/115.0
129.3/146.3
149.0/139.1
29.5
29.5
29.5
53.9
67.0
64.4
30.5
30.5
30.5
55.1
68.3
65.6
33.5
33.5
34.0
58.9
72.0
69.4
22.3
29.0
54.6
64.8
22.3
29.0
54.6
64.8
25.1
32.5
58.1
68.3
NO P.E.
MAX
FUSE or
HACR
BRKR
80
80/80
80/80
100/110
125/150
150/150
80
80/80
80/80
100/110
125/150
150/150
80
80/80
80/80
110/125
150/150
150/175
40
40
40
60
70
70
40
40
40
60
70
80
40
40
40
60
80
80
30
30
60
70
30
30
60
70
30
35
60
80
DISC. SIZE
FLA
63
63/63
63/63
85/97
110/126
128/147
66
66/66
66/66
88/100
113/129
131/150
72
72/72
72/72
94/106
119/135
137/156
31
31
31
50
62
73
32
32
32
51
63
74
35
35
35
54
66
78
23
27
50
74
23
27
50
74
27
30
53
77
LRA
360
360/360
360/360
360/360
360/360
360/360
377
377/377
377/377
377/377
377/377
377/377
386
386/386
386/386
386/386
386/386
386/386
181
181
181
181
181
181
190
190
190
190
190
190
194
194
194
194
194
194
142
142
142
142
142
142
142
142
156
156
156
156
MCA
64.5
64.5/64.5
64.5/64.5
97.5/110.4
124.6/141.6
144.4/134.4
67.0
67.0/67.0
67.0/67.0
100.6/113.5
127.8/144.8
147.5/137.6
72.0
72.0/72.0
72.0/72.0
106.9/119.8
134.0/151.0
153.8/143.8
31.3
31.3
31.3
56.1
69.3
66.6
32.3
32.3
32.5
57.4
70.5
67.9
35.3
35.3
36.3
61.1
74.3
71.6
26.1
33.8
59.4
69.6
26.1
33.8
59.4
69.6
28.9
37.3
62.9
73.1
w/ P.E. (pwrd fr/unit)
MAX
DISC. SIZE
FUSE or
HACR
BRKR
FLA
LRA
80
68
364
80/80
68/68
364/364
80/80
68/68
364/364
100/125
90/102
364/364
125/150
115/130
364/364
150/150
133/151
364/364
80
71
381
80/80
71/71
381/381
80/80
71/71
381/381
110/125
93/104
381/381
150/150
118/133
381/381
150/150
136/154
381/381
80
76
390
80/80
76/76
390/390
80/80
76/76
390/390
110/125
98/110
390/390
150/175
123/139
390/390
175/175
141/160
390/390
40
33
183
40
33
183
40
33
183
60
52
183
70
64
183
70
75
183
40
34
192
40
34
192
40
34
192
60
53
192
80
65
192
80
76
192
45
37
196
45
37
196
45
37
196
70
56
196
80
68
196
80
80
196
30
28
146
35
31
146
60
55
146
80
78
146
30
28
146
35
31
146
60
55
146
80
78
146
35
31
160
40
34
160
70
58
160
80
81
160
Nominal values, listed as 208/240V, 480V or 600V as appropriate.
161
513 31 3209 02
ELECTRICAL INFORMATION (UNITS PRODUCED PRIOR TO JULY 30, 2012) cont.
Table 54 – RAS150 Unit Wire/Fuse or HACR Breaker Sizing Data 2 Stage Cooling With 2 Speed Indoor Fan Motor
ELECTRIC HEATER
NOM.
V-PH-Hz.
IFM
TYPE
STD
208/
230-3-60
MED
HIGH
STD
460-3-60
MED
HIGH
STD
575-3-60
MED
HIGH
*
Nom
(kW)
7.8/10.4
12.0/16.0
24.0/32.0
31.8/42.4
37.6/50.0
7.8/10.4
12.0/16.0
24.0/32.0
31.8/42.4
37.6/50.0
7.8/10.4
12.0/16.0
24.0/32.0
31.8/42.4
37.6/50.0
13.9
16.5
33.0
41.7
50.0
13.9
16.5
33.0
41.7
50.0
13.9
16.5
33.0
41.7
50.0
17.0
34.0
51.0
17.0
34.0
51.0
17.0
34.0
51.0
FLA
21.7/25.0
33.4/38.5
66.7/77.0
88.4/102.0
104.2/120.3
21.7/25.0
33.4/38.5
66.7/77.0
88.4/102.0
104.2/120.3
21.7/25.0
33.4/38.5
66.7/77.0
88.4/102.0
104.2/120.3
16.7
19.8
39.7
50.2
60.1
16.7
19.8
39.7
50.2
60.1
16.7
19.8
39.7
50.2
60.1
20.4
40.9
61.3
20.4
40.9
61.3
20.4
40.9
61.3
NO C.O. or UNPWR C.O.
MCA
61.8/61.0
61.8/61.0
61.8/61.0
94.1/106.0
121.3/137.3
141.0/130.1
64.0/63.0
64.0/63.0
64.0/63.0
96.9/108.5
124.0/139.8
143.8/132.6
66.8/65.9
66.8/65.9
66.8/65.9
100.4/112.1
127.5/143.4
147.3/136.2
29.9
29.9
29.9
54.4
67.5
64.9
31.0
31.0
31.0
55.8
68.9
66.2
32.5
32.5
32.8
57.6
70.8
68.1
24.0
31.1
56.8
66.9
24.0
31.1
56.8
66.9
25.7
33.3
58.9
69.1
NO P.E.
MAX
FUSE or
HACR
BRKR
80/80
80/80
80/80
100/110
125/150
150/150
80/80
80/80
80/80
100/110
125/150
150/150
80/80
80/80
80/80
110/125
150/150
150/150
40
40
40
60
70
70
40
40
40
60
70
80
40
40
40
60
80
80
30
35
60
80
30
35
60
80
30
35
60
80
DISC. SIZE
FLA
65/64
65/64
65/64
87/98
112/126
130/147
67/66
67/66
67/66
89/100
114/129
132/150
70/69
70/69
70/69
92/103
117/132
135/153
31
31
31
50
62
73
33
33
33
51
63
75
34
34
34
53
65
76
25
29
52
76
25
29
52
76
27
31
54
78
LRA
357
357/357
357/357
357/357
357/357
357/357
381
381/381
381/381
381/381
381/381
381/381
392
392/392
392/392
392/392
392/392
392/392
180
180
180
180
180
180
192
192
192
192
192
192
197
197
197
197
197
197
142
142
142
142
142
142
142
142
156
156
156
156
MCA
65.6/64.8
65.6/64.8
65.6/64.8
98.9/110.8
126.0/142.0
145.8/134.8
67.8/66.8
67.8/66.8
67.8/66.8
101.6/113.3
128.8/144.5
148.5/137.3
70.6/69.7
70.6/69.7
70.6/69.7
105.1/116.9
132.3/148.1
152.0/140.9
31.7
31.7
31.8
56.6
69.8
67.1
32.8
32.8
33.1
58.0
71.1
68.5
34.3
34.3
35.0
59.9
73.0
70.4
27.8
35.9
61.5
71.7
27.8
35.9
61.5
71.7
29.5
38.0
63.6
73.8
w/ P.E. (pwrd fr/unit)
MAX
FUSE or
DISC. SIZE
HACR
BRKR
FLA
LRA
80/80
69/68
361
80/80
69/68
361/361
80/80
69/68
361/361
100/125
91/102
361/361
150/150
116/131
361/361
150/150
134/152
361/361
80/80
72/70
385
80/80
72/70
385/385
80/80
72/70
385/385
110/125
93/104
385/385
150/150
118/133
385/385
150/150
137/154
385/385
80/80
75/74
396
80/80
75/74
396/396
80/80
75/74
396/396
110/125
97/108
396/396
150/150
122/136
396/396
175/175
140/157
396/396
40
33
182
40
33
182
40
33
182
60
52
182
70
64
182
80
76
182
40
35
194
40
35
194
40
35
194
60
53
194
80
65
194
80
77
194
40
36
199
40
36
199
40
36
199
60
55
199
80
67
199
80
79
199
30
30
146
40
33
146
70
57
146
80
80
146
30
30
146
40
33
146
70
57
146
80
80
146
35
32
160
40
35
160
70
59
160
80
82
160
Nominal values, listed as 208/240V, 480V or 600V as appropriate.
513 31 3209 02
162
ELECTRICAL INFORMATION (UNITS PRODUCED PRIOR TO JULY 30, 2012) cont.
Table 55 – RAS180 Unit Wire/Fuse or HACR Breaker Sizing Data 2 Stage Cooling With 1 Speed Indoor Fan Motor
ELECTRIC HEATER
NOM.
V-PH-Hz.
IFM
TYPE
STD
208/
230-3-60
MED
HIGH
STD
460-3-60
MED
HIGH
STD
575-3-60
MED
HIGH
*
Nom* (kW)
­
12.4/16.5
25.2/33.5
32.7/43.5
37.6/50.0
50.3/67.0
­
12.4/16.5
25.2/33.5
32.7/43.5
37.6/50.0
50.3/67.0
­
12.4/16.5
25.2/33.5
32.7/43.5
37.6/50.0
50.3/67.0
­
16.5
33.5
43.5
50.0
67.0
­
16.5
33.5
43.5
50.0
67.0
­
16.5
33.5
43.5
50.0
67.0
­
16.5
33.5
43.5
50.0
67.0
­
16.5
33.5
43.5
50.0
67.0
­
16.5
33.5
43.5
50.0
67.0
FLA
­
34.4/39.7
69.9/80.6
90.7/104.7
104.3/120.3
139.7/161.2
­
34.4/39.7
69.9/80.6
90.7/104.7
104.3/120.3
139.7/161.2
­
34.4/39.7
69.9/80.6
90.7/104.7
104.3/120.3
139.7/161.2
­
19.9
40.3
52.3
60.2
80.6
­
19.9
40.3
52.3
60.2
80.6
­
19.9
40.3
52.3
60.2
80.6
­
15.9
32.2
41.8
48.1
64.4
­
15.9
32.2
41.8
48.1
64.4
­
15.9
32.2
41.8
48.1
64.4
NO C.O. or UNPWR C.O.
MCA
68.3
68.3/68.3
96.8/110.1
122.8/140.3
139.8/129.7
149.1/170.6
70.8
70.8/70.8
99.9/113.3
125.9/143.4
142.9/132.8
152.2/173.7
81.2
81.2/81.2
112.9/126.3
138.9/156.4
155.9/145.8
165.2/186.7
34.0
34.0
54.6
69.6
64.5
84.9
35.0
35.0
55.9
70.9
65.7
86.1
40.8
40.8
63.1
78.1
73.0
93.4
26.5
26.5
43.8
55.8
51.6
67.9
26.5
26.5
43.8
55.8
51.6
67.9
32.7
32.7
51.5
63.5
59.4
75.7
NO P.E.
MAX FUSE
or HACR
BRKR
80
80/80
100/125
125/150
150/150
175/200
80
80/80
100/125
150/150
150/150
175/200
100
100/100
125/150
150/175
175/175
175/225
45
45
60
70
70
90
45
45
60
80
80
100
50
50
70
80
80
100
30
30
45
60
60
80
30
30
45
60
60
80
40
40
60
70
70
80
DISC. SIZE
FLA
71
71/71
89/101
113/129
129/147
169/194
74
74/74
92/104
116/132
131/150
172/197
86
86/86
104/116
128/144
143/162
184/209
35
35
50
64
73
97
37
37
51
65
74
98
43
43
58
72
81
104
28
28
40
51
59
77
28
28
40
51
59
77
35
35
47
58
66
84
LRA
396
396/396
396/396
396/396
396/396
396/396
413
413/413
413/413
413/413
413/413
413/413
432
432/432
432/432
432/432
432/432
432/432
234
234
234
234
234
234
243
243
243
243
243
243
252
252
252
252
252
252
184
184
184
184
184
184
184
184
184
184
184
184
196
196
196
196
196
196
MCA
72.1
72.1/72.1
101.5/114.9
127.5/145.0
144.5/134.4
153.8/175.3
74.6
74.6/74.6
104.6/118.0
130.6/148.1
147.6/137.6
157.0/178.5
85.0
85.0/85.0
117.6/131.0
143.6/161.1
160.6/150.6
170.0/191.5
35.8
35.8
56.9
71.9
66.7
87.1
36.8
36.8
58.1
73.1
68.0
88.4
42.6
42.6
65.4
80.4
75.2
95.6
30.3
30.3
48.5
60.5
56.4
72.7
30.3
30.3
48.5
60.5
56.4
72.7
36.5
36.5
56.3
68.3
64.1
80.4
w/ P.E. (pwrd fr/unit)
MAX FUSE
DISC. SIZE
or HACR
BRKR
FLA
LRA
80
76
400
80/80
76/76
400/400
110/125
93/106
400/400
150/150
117/133
400/400
150/150
133/151
400/400
175/200
174/198
400/400
90
79
417
90/90
79/79
417/417
110/125
96/109
417/417
150/150
120/136
417/417
150/150
136/154
417/417
175/200
177/201
417/417
100
91
436
100/100
91/91
436/436
125/150
108/121
436/436
150/175
132/148
436/436
175/175
148/166
436/436
175/225
188/213
436/436
45
37
236
45
37
236
60
52
236
80
66
236
70
75
236
100
99
236
45
39
245
45
39
245
60
53
245
80
67
245
80
76
245
100
100
245
50
45
254
50
45
254
70
60
254
90
74
254
80
83
254
100
106
254
40
32
188
40
32
188
50
45
188
70
56
188
60
63
188
80
82
188
40
32
188
40
32
188
50
45
188
70
56
188
60
63
188
80
82
188
45
39
200
45
39
200
60
52
200
70
63
200
70
70
200
90
89
200
Nominal values, listed as 208/240V, 480V or 600V as appropriate.
163
513 31 3209 02
ELECTRICAL INFORMATION (UNITS PRODUCED PRIOR TO JULY 30, 2012) cont.
Table 56 – RAS180 Unit Wire/Fuse or HACR Breaker Sizing Data 2 Stage Cooling With 2 Speed Indoor Fan Motor
ELECTRIC HEATER
NOM.
V-PH-Hz.
IFM
TYPE
STD
208/
230-3-60
MED
HIGH
STD
460-3-60
MED
HIGH
STD
575-3-60
MED
HIGH
*
Nom
(kW)
12.4/16.5
25.2/33.5
32.7/43.5
37.6/50.0
50.3/67.0
12.4/16.5
25.2/33.5
32.7/43.5
37.6/50.0
50.3/67.0
12.4/16.5
25.2/33.5
32.7/43.5
37.6/50.0
50.3/67.0
16.5
33.5
43.5
50.0
67.0
16.5
33.5
43.5
50.0
67.0
16.5
33.5
43.5
50.0
67.0
16.5
33.5
43.5
50.0
67.0
16.5
33.5
43.5
50.0
67.0
16.5
33.5
43.5
50.0
67.0
FLA
34.4/39.7
69.9/80.6
90.7/104.7
104.3/120.3
139.7/161.2
34.4/39.7
69.9/80.6
90.7/104.7
104.3/120.3
139.7/161.2
34.4/39.7
69.9/80.6
90.7/104.7
104.3/120.3
139.7/161.2
19.9
40.3
52.3
60.2
80.6
19.9
40.3
52.3
60.2
80.6
19.9
40.3
52.3
60.2
80.6
15.9
32.2
41.8
48.1
64.4
15.9
32.2
41.8
48.1
64.4
15.9
32.2
41.8
48.1
64.4
MCA
69.4/68.6
69.4/68.6
98.1/110.5
124.1/140.6
141.1/130.1
150.5/171.0
71.6/70.6
71.6/70.6
100.9/113.0
126.9/143.1
143.9/132.6
153.2/173.5
81.2
81.2/81.2
112.9/126.3
138.9/156.4
155.9/145.8
165.2/186.7
34.4
34.4
55.1
70.1
65.0
85.4
35.5
35.5
56.5
71.5
66.3
86.7
40.8
40.8
63.1
78.1
73.0
93.4
28.2
28.2
45.9
57.9
53.7
70.0
28.2
28.2
45.9
57.9
53.7
70.0
32.7
32.7
51.5
63.5
59.4
75.7
NO C.O. or UNPWR C.O.
NO P.E.
MAX
FUSE or
DISC. SIZE
HACR
BRKR
FLA
LRA
MCA
80/80
73/72
393
73.2/72.4
80/80
73/72
393/393
73.2/72.4
100/125
90/102
393/393
102.9/115.3
125/150
114/129
393/393
128.9/145.4
150/150
130/147
393/393
145.9/134.8
175/200
171/194
393/393
155.2/175.7
80/80
75/74
417
75.4/74.4
80/80
75/74
417/417
75.4/74.4
110/125
93/104
417/417
105.6/117.8
150/150
117/132
417/417
131.6/147.9
150/150
132/150
417/417
148.6/137.3
175/200
173/197
417/417
158.0/178.2
100
86
432
85.0
100/100
86/86
432/432
85.0/85.0
125/150
104/116
432/432
117.6/131.0
150/175
128/144
432/432
143.6/161.1
175/175
143/162
432/432
160.6/150.6
175/225
184/209
432/432
170.0/191.5
45
36
233
36.2
45
36
233
36.2
60
51
233
57.4
80
65
233
72.4
70
74
233
67.2
90
97
233
87.6
45
37
245
37.3
45
37
245
37.3
60
52
245
58.8
80
66
245
73.8
80
75
245
68.6
100
98
245
89.0
50
43
252
42.6
50
43
252
42.6
70
58
252
65.4
80
72
252
80.4
80
81
252
75.2
100
104
252
95.6
35
30
184
32.0
35
30
184
32.0
50
42
184
50.6
60
53
184
62.6
60
60
184
58.5
80
79
184
74.8
35
30
184
32.0
35
30
184
32.0
50
42
184
50.6
60
53
184
62.6
60
60
184
58.5
80
79
184
74.8
40
35
196
36.5
40
35
196
36.5
60
47
196
56.3
70
58
196
68.3
70
66
196
64.1
80
84
196
80.4
w/ P.E. (pwrd fr/unit)
MAX
FUSE or
DISC. SIZE
HACR
BRKR
FLA
LRA
80/80
77/76
397
80/80
77/76
397/397
110/125
95/106
397/397
150/150
119/134
397/397
150/150
134/152
397/397
175/200
175/199
397/397
100/90
79/78
421
100/90
79/78
421/421
110/125
97/108
421/421
150/150
121/136
421/421
150/150
137/154
421/421
175/200
177/201
421/421
100
91
436
100/100
91/91
436/436
125/150
108/121
436/436
150/175
132/148
436/436
175/175
148/166
436/436
175/225
188/213
436/436
45
38
235
45
38
235
60
53
235
80
67
235
80
76
235
100
99
235
50
39
247
50
39
247
60
54
247
80
68
247
80
77
247
100
100
247
50
45
254
50
45
254
70
60
254
90
74
254
80
83
254
100
106
254
40
34
188
40
34
188
60
47
188
70
58
188
60
65
188
80
84
188
40
34
188
40
34
188
60
47
188
70
58
188
60
65
188
80
84
188
45
39
200
45
39
200
60
52
200
70
63
200
70
70
200
90
89
200
Nominal values, listed as 208/240V, 480V or 600V as appropriate.
513 31 3209 02
164
LEGEND:
BRKR
- Circuit breaker
CO
- Convenience outlet
DISC
- Disconnect
FLA
- Full load amps
IFM
- Indoor fan motor
LRA
- Locked rotor amps
MCA
- Minimum circuit amps
MOCP
- MAX FUSE or HACR Breaker
PE
- Power exhaust
PWRD CO
- Powered convenient outlet
UNPWR CO
- Unpowered convenient outlet
NOTES:
1. In compliance with NEC requirements for multimotor and com
ment (refer to NEC Articles 430 and 440), the overcurrent protecti
shall be fuse or HACR breaker. Canadian units may be fuse or ci
2. Unbalanced 3‐Phase Supply Voltage
Never operate a motor where a phase imbalance in supply voltag
Use the following formula to determine the percentage of voltage
% Voltage
Imbalance
165
= 100 x
max voltage deviation from average voltage
average voltage
Example: Supply voltage is 230‐3‐60
AB = 224 v
BC = 231 v
AC = 226 v
Average Voltage =
=
(224 + 231 + 226)
3
227
=
681
3
Determine maximum deviation from average voltage.
(AB) 227 – 224 = 3 v
(BC) 231 – 227 = 4 v
(AC) 227 – 226 = 1 v
Maximum deviation is 4 v.
Determine percent of voltage imbalance.
% Voltage Imbalance
= 100 x
4
227
= 1.76%
This amount of phase imbalance is satisfactory as it is below the maxim­
um allowable 2%.
IMPORTANT: If the supply voltage phase imbalance is more than 2%,
contact your local electric utility company immediately.
513 31 3209 02
SEQUENCE OF OPERATION
General
The sequence below describes the sequence of
operation for an electromechanical unit with and without a
factory installed Economizer IV and X (called
“economizer” in this sequence). For information regarding
a direct digital controller, see the start−up, operations,
and troubleshooting manual for the applicable controller.
Electromechanical units with no economizer
Cooling (Single speed indoor fan motor) —
When the thermostat calls for cooling, terminals G and
Y1 are energized. As a result, the indoor fan contactor
(IFC) and the compressor contactor (C1) are energized,
causing the indoor fan motor (IFM), compressor #1, and
outdoor fan to start. If the unit has 2 stages of cooling,
the thermostat will additionally energize Y2. The Y2
signal will energize compressor contactor #2 (C2),
causing compressor #2 to start. Regardless of the
number of stages, the outdoor fan motor runs
continuously while unit is cooling.
Cooling (2−speed indoor fan motor) —
Per ASHRAE 90.1 2010 standard section 6.4.3.10.b,
during the first stage of cooling operation the VFD will
adjust the fan motor to provide 2/3rd of the total cfm
established for the unit. When a call for the second stage
of cooling is required, the VFD will allow the total cfm for
the unit established (100%).
Heating
NOTE: The RAS is sold as cooling only. If electric
heaters are required, use only factory−approved electric
heaters. They will operate as described below.
Units have either 1 or 2 stages of electric heat. When the
thermostat calls for heating, power is applied to the W1
terminal at the unit. The unit control will energize the
indoor fan contactor and the first stage of electric heat.
On units with 2−stage heating, when additional heating is
required, the second stage of electric heat (if equipped)
will be energized when power is applied at the W2
terminal on the unit.
Electromechanical units with an economizer
Cooling —
When free cooling is not available, the compressors will
be controlled by the zone thermostat. When free cooling
is available, the outdoor air damper is modulated by the
Economizer IV and X control to provide a 50_F (10_C) to
55_F (13_C) mixed air temperature into the zone. As the
mixed air temperature fluctuates above 55_F (13_C) or
below 50_F (10_C) dampers will be modulated (open or
close) to bring the mixed air temperature back within
control. If mechanical cooling is utilized with free cooling,
the outdoor air damper will maintain its current position at
the time the compressor is started. If the increase in
513 31 3209 02
cooling capacity causes the mixed air temperature to
drop below 45_F (9_C), then the outdoor air damper
position will be decreased to the minimum position. If the
mixed air temperature continues to fall, the outdoor air
damper will close. Control returns to normal once the
mixed air temperature rises above 48_F (9_C). The
power exhaust fans will be energized and de−energized,
if installed, as the outdoor air damper opens and closes.
If field−installed accessory CO2 sensors are connected to
the Economizer IV and X control, a demand controlled
ventilation strategy will begin to operate. As the CO2 level
in the zone increases above the CO2 setpoint, the
minimum position of the damper will be increased
proportionally. As the CO2 level decreases because of
the increase in fresh air, the outdoor air damper will be
proportionally closed. For Economizer IV and X
operation, there must be a thermostat call for the fan (G).
If the unit is occupied and the fan is on, the damper will
operate at minimum position. Otherwise, the damper will
be closed.
When the Economizer IV and X control is in the occupied
mode and a call for cooling exists (Y1 on the thermostat),
the control will first check for indoor fan operation. If the
fan is not on, then cooling will not be activated. If the fan
is on, then the control will open the Economizer IV and X
damper to the minimum position.
On the initial power to the Economizer IV and X control, it
will take the damper up to 2 1/2 minutes before it begins
to position itself. After the initial power−up, further
changes in damper position can take up to 30 seconds to
initiate. Damper movement from full closed to full open
(or vice versa) will take between 1 1/2 and 2 1/2 minutes.
If free cooling can be used as determined from the
appropriate changeover command (switch, dry bulb,
enthalpy curve, differential dry bulb, or differential
enthalpy), then the control will modulate the dampers
open to maintain the mixed air temperature setpoint at
50_F (10_C) to 55_F (13_C). If there is a further demand
for cooling (cooling second stage − Y2 is energized), then
the control will bring on compressor stage 1 to maintain
the mixed air temperature setpoint. The Economizer IV
and X damper will be open at maximum position.
Economizer IV and X operation is limited to a single
compressor.
2−Speed Note: When operating in ventilation mode only,
the indoor fan motor will automatically adjust to 2/3rd of
the total cfm established.
Heating
The sequence of operation for the heating is the same as
an electromechanical unit with no economizer. The only
difference is how the economizer acts. The economizer
will stay at the Economizer Minimum Position while the
evaporator fan is operating. The outdoor air damper is
closed when the indoor fan is not operating.
166
SEQUENCE OF OPERATION (cont.)
Optional Hot Gas Reheat System
Units with the factory equipped Hot Gas Reheat option
are capable of providing multiple modes of improved
dehumidification as a variation of the normal cooling
cycle. The Hot Gas Reheat option includes additional
valves in the liquid line and discharge line of each
refrigerant circuit, a small reheat condenser coil
downstream of the evaporator, and Motormaster
variable−speed control of some or all outdoor fans.
Operation of the revised refrigerant circuit for each mode
is described below.
The Hot Gas Reheat system provides three sub−modes
of operation: Cool, Reheat1, and Reheat2.
167
Cool mode − provides a normal ratio of Sensible and
Latent Cooling effect from the evaporator coil.
Reheat1 − provides increased Latent Cooling while
slightly reducing the Sensible Cooling effect.
Reheat2 − provides normal Latent Cooling but with null
or minimum Sensible Cooling effect delivered to the
space.
The Reheat1 and Reheat2 modes are available when the
unit is not in a Heating mode and when the Low Ambient
Lockout switch is closed.
The following diagrams depict piping for Single Stage
cooling units.
513 31 3209 02
Hot Gas Reheat Coil
Metering
Device
Normal Cooling Mode − Hot Gas Reheat with Single Stage Cooling
Hot Gas Reheat Coil
Metering
Device
Subcooling Mode (Reheat 1) − Hot Gas Reheat System with Single Stage Cooling
Hot Gas Reheat Coil
Metering
Device
Hot Gas Reheat Mode (Reheat2) − Hot Gas Reheat with Single Stage Cooling
513 31 3209 02
168
GUIDE SPECIFICATIONS − RAS036−180
Cooling Only/Electric Heat Packaged Rooftop
HVAC Guide Specifications
Size Range:
Tons
3 to 15 Nominal
Section
Description
23 06 80
Schedules for Decentralized HVAC Equipment
23 06 80.13
Decentralized Unitary HVAC Equipment Schedule
23 06 80.13.A. Rooftop unit schedule
1. Schedule is per the project specification requirements.
23 07 16
HVAC Equipment Insulation
23 07 16.13
Decentralized, Rooftop Units:
23 07 16.13.A. Evaporator fan compartment:
1. Interior cabinet surfaces shall be insulated with a minimum 1/2−in. thick, minimum 1 1/2 lb density, flexible
fiberglass insulation bonded with a phenolic binder, neoprene coated on the air side.
2. Insulation and adhesive shall meet NFPA 90A requirements for flame spread and smoke generation.
23 07 16.13.B. Electric heat compartment:
1. Aluminum foil−faced fiberglass insulation shall be used.
2. Insulation and adhesive shall meet NFPA 90A requirements for flame spread and smoke generation.
23 09 13
Instrumentation and Control Devices for HVAC
23 09 13.23
Sensors and Transmitters
23 09 13.23.A. Thermostats
1. Thermostat must
a. energize both “W” and “G” when calling for heat.
b. have capability to energize 2 different stages of cooling, and 2 different stages of heating.
c. include capability for occupancy scheduling.
23 09 23
Direct−digital Control system for HVAC
23 09 23.13
Decentralized, Rooftop Units:
23 09 23.13.A. N/A
23 09 33
Electric and Electronic Control System for HVAC
23 09 33.13
Decentralized, Rooftop Units:
23 09 33.13.A. General:
1. Shall be complete with self−contained low−voltage control circuit protected by a resettable circuit breaker on the
24−v transformer side. Transformer shall have 75VA capability.
2. Shall utilize color−coded wiring.
3. Shall include a central control terminal board to conveniently and safely provide connection points for vital control functions such as: smoke detectors, phase monitor, economizer, thermostat, DDC control options, and low
and high pressure switches.
4. Unit shall include a minimum of one 8−pin screw terminal connection board for connection of control wiring.
23 09 33.23.B. Safeties:
1. Compressor over−temperature, over current.
2. Low pressure switch.
a. Units with 2 compressors shall have different sized connectors for the circuit 1 and circuit 2 low and high
pressure switches. They shall physically prevent the cross−wiring of the safety switches between circuits 1
and 2.
b. Low pressure switch shall use different color wire than the high pressure switch. The purpose is to assist
the installer and service technician to correctly wire and or troubleshoot the rooftop unit.
3. High pressure switch.
169
513 31 3209 02
a. Units with 2 compressors shall have different sized connectors for the circuit 1 and circuit 2 low and high
pressure switches. They shall physically prevent the cross−wiring of the safety switches between circuits 1
and 2.
b. High pressure switch shall use different color wire than the low pressure switch. The purpose is to assist
the installer and service technician to correctly wire and or troubleshoot the rooftop unit.
4. Automatic reset, motor thermal overload protector.
23 09 93
Sequence of Operations for HVAC Controls
23 09 93.13
23 09 93.13
23 40 13
Decentralized, Rooftop Units:
INSERT SEQUENCE OF OPERATION
Panel Air Filters
23 40 13.13
Decentralized, Rooftop Units:
23 40 13.13.A. Standard filter section
1. Shall consist of factory−installed, low velocity, throwaway 2−in. thick fiberglass filters of commercially available
sizes.
2. Unit shall use only one filter size. Multiple sizes are not acceptable.
3. Filters shall be accessible through an access panel with “no−tool” removal as described in the unit cabinet
section of this specification (23 81 19.13.H).
23 81 19
Self−Contained Air Conditioners
23 81 19.13
Small−Capacity Self−Contained Air Conditioners (RAS036−180)
23 81 19.13.A. General
1. Outdoor, rooftop mounted, electrically controlled, heating and cooling unit utilizing a(n) hermetic scroll compressor(s) for cooling duty and gas combustion for heating duty.
2. Factory assembled, single−piece heating and cooling rooftop unit. Contained within the unit enclosure shall be
all factory wiring, piping, controls, and special features required prior to field start−up.
3. Unit shall use environmentally safe, R−410A refrigerant.
4. Unit shall be installed in accordance with the manufacturer’s instructions.
5. Unit must be selected and installed in compliance with local, state, and federal codes.
23 81 19.13.B. Quality Assurance
1. Unit meets ASHRAE 90.1 minimum efficiency requirements.
2. Unit shall be rated in accordance with AHRI Standards 210/240 and 340/360.
3. Unit shall be designed to conform to ASHRAE 15, 2001.
4. Unit shall be UL−tested and certified in accordance with ANSI Z21.47 Standards and UL−listed and certified
under Canadian standards as a total package for safety requirements.
5. Insulation and adhesive shall meet NFPA 90A requirements for flame spread and smoke generation.
6. Unit casing shall be capable of withstanding 500−hour salt spray exposure per ASTM B117 (scribed specimen).
7. Unit casing shall be capable of withstanding Federal Test Method Standard No. 141 (Method 6061) 5000−hour
salt spray.
8. Unit shall be designed in accordance with ISO 9001:2000, and shall be manufactured in a facility registered by
ISO 9001:2000.
9. Roof curb shall be designed to conform to NRCA Standards.
10. Unit shall be subjected to a completely automated run test on the assembly line. The data for each unit will be
stored at the factory, and must be available upon request.
11. Unit shall be designed in accordance with UL Standard 1995, including tested to withstand rain.
12. Unit shall be constructed to prevent intrusion of snow and tested to prevent snow intrusion into the control box
up to 40 mph.
13. Unit shake tested to assurance level 1, ASTM D4169 to ensure shipping reliability.
14. High Efficient Motors listed shall meet section 313 of the Energy Independence and Security Act of 2007 (EISA
2007).
23 81 19.13.C. Delivery, Storage, and Handling
1. Unit shall be stored and handled per manufacturer’s recommendations.
2. Lifted by crane requires either shipping top panel or spreader bars.
3. Unit shall only be stored or positioned in the upright position.
23 81 19.13.D. Project Conditions
1. As specified in the contract.
513 31 3209 02
170
23 81
1.
23 81
1.
2.
3.
4.
5.
6.
23 81
1.
23 81
1.
2.
3.
4.
5.
6.
7.
8.
9.
171
19.13.E. Project Conditions
As specified in the contract.
19.13.F. Operating Characteristics
Unit shall be capable of starting and running at 115_F (46_C) ambient outdoor temperature, meeting maximum
load criteria of AHRI Standard 210/240 or 340/360 at ± 10% voltage.
Compressor with standard controls shall be capable of operation down to 40_F (4_C), ambient outdoor temperatures. Accessory winter start kit is necessary if mechanically cooling at ambient temperatures down to 25_F
(−4_C).
Unit shall discharge supply air vertically or horizontally as shown on contract drawings.
Unit shall be factory configured for vertical supply & return configurations.
Unit shall be field convertible from vertical to horizontal airflow on all models. No special kit required on 04−14
models. Supply duct kit required for 16 size model only.
Unit shall be capable of mixed operation: vertical supply with horizontal return or horizontal supply with vertical
return.
19.13.G. Electrical Requirements
Main power supply voltage, phase, and frequency must match those required by the manufacturer.
19.13.H. Unit Cabinet
Unit cabinet shall be constructed of galvanized steel, and shall be bonderized and coated with a pre−painted
baked enamel finish on all externally exposed surfaces.
Unit cabinet exterior paint shall be: film thickness, (dry) 0.003 inches minimum, gloss (per ASTM D523, 60_F):
60, Hardness: H−2H Pencil hardness.
Evaporator fan compartment interior cabinet insulation shall conform to AHRI Standards 210/240 or 340/360
minimum exterior sweat criteria. Interior surfaces shall be insulated with a minimum 1/2−in. thick, 1 lb density,
flexible fiberglass insulation, neoprene coated on the air side. Aluminum foil−faced fiberglass insulation shall be
used in the heat compartment.
Base of unit shall have a minimum of four locations for thru−the−base gas and electrical connections (factory
installed or field installed), standard.
Base Rail
a. Unit shall have base rails on a minimum of 2 sides.
b. Holes shall be provided in the base rails for rigging shackles to facilitate maneuvering and overhead rigging.
c. Holes shall be provided in the base rail for moving the rooftop by fork truck.
d. Base rail shall be a minimum of 16 gauge thickness.
Condensate pan and connections:
a. Shall be a sloped condensate drain pan made of a non−corrosive material.
b. Shall comply with ASHRAE Standard 62.
c. Shall use a 3/4” −14 NPT drain connection, possible either through the bottom or end of the drain pan.
Connection shall be made per manufacturer’s recommendations.
Top panel:
a. Shall be a single piece top panel on 04 thru 12 sizes, two piece on 14 and 16 size.
Electrical Connections
a. All unit power wiring shall enter unit cabinet at a single, factory−prepared, knockout location.
b. Thru−the−base capability
(1.) Standard unit shall have a thru−the−base electrical location(s) using a raised, embossed portion of the
unit basepan.
(2.) Optional, factory−approved, water−tight connection method must be used for thru−the−base electrical
connections.
(3.) No basepan penetration, other than those authorized by the manufacturer, is permitted.
Component access panels (standard)
a. Cabinet panels shall be easily removable for servicing.
b. Unit shall have one factory installed, tool−less, removable, filter access panel.
c. Panels covering control box, indoor fan, indoor fan motor, gas components (where applicable), and compressors shall have molded composite handles.
d. Handles shall be UV modified, composite. permanently attached, and recessed into the panel.
513 31 3209 02
23 81
23 81
1.
2.
3.
4.
5.
23 81
1.
2.
e. Screws on the vertical portion of all removable access panel shall engage into heat resistant, molded composite collars.
f. Collars shall be removable and easily replaceable using manufacturer recommended parts.
19.13.I. N/A
19.13.J. Coils
Standard Aluminum fin − Copper Tube Coils:
a. Standard evaporator and condenser coils shall have aluminum lanced plate fins mechanically bonded to
seamless internally grooved copper tubes with all joints brazed.
b. Evaporator coils shall be leak tested to 150 psig, pressure tested to 450 psig, and qualified to UL 1995
burst test at 1775 psig.
c. Condenser coils shall be leak tested to 150 psig, pressure tested to 650 psig, and qualified to UL 1995
burst test at 1980 psig.
Optional Pre−coated aluminum−fin condenser coils (3 Phase Models Only):
a. Shall have a durable epoxy−phenolic coating to provide protection in mildly corrosive coastal environments.
b. Coating shall be applied to the aluminum fin stock prior to the fin stamping process to create an inert barrier between the aluminum fin and copper tube.
c. Epoxy−phenolic barrier shall minimize galvanic action between dissimilar metals.
Optional Copper−fin evaporator and condenser coils (3 Phase Models Only):
a. Shall be constructed of copper fins mechanically bonded to copper tubes and copper tube sheets.
b. Galvanized steel tube sheets shall not be acceptable.
c. A polymer strip shall prevent coil assembly from contacting the sheet metal coil pan to minimize potential
for galvanic corrosion between coil and pan.
Optional E−coated aluminum−fin evaporator and condenser coils (3 Phase Models Only):
a. Shall have a flexible epoxy polymer coating uniformly applied to all coil surface areas without material
bridging between fins.
b. Coating process shall ensure complete coil encapsulation of tubes, fins and headers.
c. Color shall be high gloss black with gloss per ASTM D523−89.
d. Uniform dry film thickness from 0.8 to 1.2 mil on all surface areas including fin edges.
e. Superior hardness characteristics of 2H per ASTM D3363−92A and cross−hatch adhesion of 4B−5B per
ASTM D3359−93.
f. Impact resistance shall be up to 160 in.−lb (ASTM D2794−93).
g. Humidity and water immersion resistance shall be up to minimum 1000 and 250 hours respectively (ASTM
D2247−92 and ASTM D870−92).
h. Corrosion durability shall be confirmed through testing to be no less than 1000 hours salt spray per ASTM
B117−90.
Optional E−coated aluminum−fin, aluminum tube condenser coils:
a. Shall have a flexible epoxy polymer coating uniformly applied to all coil external surface areas without material bridging between fins or louvers.
b. Coating process shall ensure complete coil encapsulation, including all exposed fin edges.
c. E−coat thickness of 0.8 to 1.2 mil with top coat having a uniform dry film thickness from 1.0 to 2.0 mil on
all external coil surface areas, including fin edges, shall be provided.
d. Shall have superior hardness characteristics of 2H per ASTM D3363−00 and cross−hatch adhesion of
4B−5B per ASTM D3359−02.
e. Shall have superior impact resistance with no cracking, chipping or peeling per NSF/ANSI 51−2002 Method 10.2.
19.13.K. Refrigerant Components
Refrigerant circuit shall include the following control, safety, and maintenance features:
a. Fixed orifice metering system shall prevent mal−distribution of two−phase refrigerant by including multiple
fixed orifice devices in each refrigeration circuit. Each orifice is to be optimized to the coil circuit it serves.
b. Refrigerant filter drier.
c. Service gauge connections on suction and discharge lines.
d. Pressure gauge access through a specially designed access port in the top panel of the unit.
There shall be gauge line access port in the skin of the rooftop, covered by a black, removable plug.
a. The plug shall be easy to remove and replace.
513 31 3209 02
172
3.
23 81
1.
2.
3.
4.
5.
23 81
1.
2.
23 81
1.
2.
23 81
1.
2.
173
b. When the plug is removed, the gauge access port shall enable maintenance personnel to route their pressure gauge lines.
c. This gauge access port shall facilitate correct and accurate condenser pressure readings by enabling the
reading with the compressor access panel on.
d. The plug shall be made of a leak proof, UV−resistant, composite material.
Compressors
a. Unit shall use one fully hermetic, scroll compressor for each independent refrigeration circuit.
b. Compressor motors shall be cooled by refrigerant gas passing through motor windings.
c. Compressors shall be internally protected from high discharge temperature conditions.
d. Compressors shall be protected from an over−temperature and over−amperage conditions by an internal,
motor overload device.
e. Compressor shall be factory mounted on rubber grommets.
f. Compressor motors shall have internal line break thermal, current overload and high pressure differential
protection.
g. Crankcase heaters shall not be required for normal operating range, unless provided by compressor manufacturer due to refrigerant charge limits.
19.13.L. Filter Section
Filters access is specified in the unit cabinet section of this specification.
Filters shall be held in place by a pivoting filter tray, facilitating easy removal and installation.
Shall consist of factory−installed, low velocity, throw−away 2−in. thick fiberglass filters.
Filters shall be standard, commercially available sizes.
Only one size filter per unit is allowed.
19.13.M. Evaporator Fan and Motor
Evaporator fan motor:
a. Shall have permanently lubricated bearings.
b. Shall have inherent automatic−reset thermal overload protection or circuit breaker.
c. Shall have a maximum continuous bhp rating for continuous duty operation; no safety factors above that
rating shall be required.
Belt−driven Evaporator Fan:
a. Belt drive shall include an adjustable pitch motor pulley.
b. Shall use sealed, permanently lubricated ball−bearing type.
c. Blower fan shall be double−inlet type with forward−curved blades.
d. Shall be constructed from steel with a corrosion resistant finish and dynamically balanced.
19.13.N. Condenser Fans and Motors
Condenser fan motors:
a. Shall be a totally enclosed motor.
b. Shall use permanently lubricated bearings.
c. Shall have inherent thermal overload protection with an automatic reset feature.
d. Shall use a shaft−down design on 036 to 120 and 180 size models and shaft−up design on 150 size with
rain shield.
Condenser Fans:
a. Shall be a direct−driven propeller type fan.
b. Shall have galvalum blades riveted to corrosion−resistant steel spiders and shall be dynamically balanced.
19.13.O. Special Features, Options and Accessories
2−speed indoor fan motor for 2−stage cooling models only.
a. Evaporator fan motor:
(1.) Shall have permanently lubricated bearings.
(2.) Shall have a maximum continuous bhp rating for continuous duty operation; no safety factors above
that rating.
(3.) Shall be Variable Frequency duty and 2−speed control.
(4.) Shall contain motor shaft grounding ring to prevent electrical bearing fluting damage by safely diverting harmful shaft voltages and bearing currents to ground.
Variable Frequency Drive (VFD). Only available on 2−speed indoor fan motor option:
a. Shall be installed inside the unit cabinet, mounted, wired and tested.
513 31 3209 02
b. Shall contain Electromagnetic Interference (EMI) frequency protection.
c. Insulated Gate Bi−Polar Transistors (IGBT) used to produce the output pulse width modulated (PWM)
waveform, allowing for quiet motor operation.
d. Self diagnostics with fault and power code LED indicator. Field accessory Display Kit available for further
diagnostics and special setup applications.
e. RS485 capability standard.
f. Electronic thermal overload protection.
g. 5% swinging chokes for harmonic reduction and improved power factor.
h. All printed circuit boards shall be conformal coated.
3. Standard Integrated Economizers (Factory installed on 3 Phase Models Only. Field installed on all 3 and 1
Phase Models):
a. Integrated, gear−driven opposing modulating blade design type capable of simultaneous economizer and
compressor operation.
b. Independent modules for vertical or horizontal return configurations shall be available. Vertical return modules shall be available as a factory installed option.
c. Damper blades shall be galvanized steel with composite gears. Plastic or composite blades on intake or
return shall not be acceptable.
d. Shall include all hardware and controls to provide free cooling with outdoor air when temperature and/or
humidity are below setpoints.
e. Shall be equipped with gear driven dampers for both the outdoor ventilation air and the return air for positive air stream control.
f. Standard models shall be equipped with low−leakage dampers, not to exceed 2% leakage at 1 in. wg pressure differential. Economizer controller on electromechanical units shall be Honeywell W7212 that
provides:
(1.) Combined minimum and DCV maximum damper position potentiometers with compressor staging relay.
(2.) Functions with solid state analog enthalpy or dry bulb changeover control sensing.
(3.) Contain LED indicates for:
When free cooling is available
When module is in DCV mode
When exhaust fan contact is closed
g. Ultra low leak Economizer X system shall be available on models with 2−speed indoor fan motor 2−speed
Variable Frequency Drive (VFD) systems. Only available on 2−Speed Indoor Fan Motor Systems with electromechanical controls.
(1.) Maximum damper leakage rate to be equal to or less than 4.0 cfm/sq. ft. at 1.0 in. w.g., meeting or
exceeding ASHRAE 90.1 requirements. Economizer controller on electromechanical units shall be
Honeywell W7220 that provides:
(2.) 2−line LCD interface screen for setup, configuration and troubleshooting
(3.) On−board fault detection and diagnostics
(4.) Sensor failure loss of communication identification
(5.) Automatic sensor detection
(6.) Capabilities for use with multiple−speed indoor fan systems
(7.) Utilize digital sensors: Dry bulb and Enthalpy
h. Shall be capable of introducing up to 100% outdoor air.
i. Shall be equipped with a barometric relief damper capable of relieving up to 100% return air.
j. Shall be designed to close damper(s) during loss−of−power situations with spring return built into motor.
k. Dry bulb outdoor air temperature sensor shall be provided as standard. Outdoor air sensor setpoint shall
be adjustable and shall range from 40 to 100_F / 4 to 38_C. Additional sensor options shall be available as
accessories.
l. The economizer controller shall also provide control of an accessory power exhaust unit function. Factory
set at 100%, with a range of 0% to 100%.
m. The economizer shall maintain minimum airflow into the building during occupied period and provide
design ventilation rate for full occupancy. A remote potentiometer may be used to override the damper setpoint.
n. Dampers shall be completely closed when the unit is in the unoccupied mode.
o. Economizer controller shall accept a 2−10 Vdc CO2 sensor input for IAQ/DCV control. In this mode,
dampers shall modulate the outdoor air damper to provide ventilation based on the sensor input.
513 31 3209 02
174
4.
5.
6.
7.
8.
9.
10.
11.
175
p. Compressor lockout sensor shall open at 35_F (2_C) and close closes at 50_F (10_C).
q. Actuator shall be direct coupled to economizer gear. No linkage arms or control rods shall be acceptable.
r. Economizer controller shall provide indications when in free cooling mode, in the DCV mode, or the exhaust fan contact is closed.
Two−Position Damper (Factory installed on 3 Phase Models Only. Field installed on all 3 and 1 Phase Models)
a. Damper shall be a Two−Position Damper. Damper travel shall be from the full closed position to the field
adjustable %−open setpoint.
b. Damper shall include adjustable damper travel from 25% to 100% (full open).
c. Damper shall include single or dual blade, gear driven dampers and actuator motor.
d. Actuator shall be direct coupled to damper gear. No linkage arms or control rods shall be acceptable.
e. Damper will admit up to 100% outdoor air for applicable rooftop units.
f. Damper shall close upon indoor (evaporator) fan shutoff and/or loss of power.
g. The damper actuator shall plug into the rooftop unit’s wiring harness plug. No hard wiring shall be required.
h. Outside air hood shall include aluminum water entrainment filter
Manual damper
a. Manual damper package shall consist of damper, air inlet screen, and rain hood which can be preset to
admit up to 50% outdoor air for year round ventilation.
Hot Gas Reheat System (3 Phase Models Only).
a. The Hot Gas Reheat System shall be factory−installed in single stage RAS036−072 and 2−stage RAS090
to 180 models with RTPF (round tube plate fin) condenser coils, and shall provide greater dehumidification
of the occupied space by two modes of dehumidification operations beside its normal design cooling
mode:
(1.) Subcooling mode further subcools the hot liquid refrigerant leaving the condenser coil when both temperature and humidity in the space are not satisfied.
(2.) Hot gas reheat mode shall mix a portion of the hot gas from the discharge of the compressor with the
hot liquid refrigerant leaving the condenser coil to create a two−phase heat transfer in the system, resulting in a neutral leaving− air temperature when only humidity in the space is not satisfied.
(3.) Includes Head Pressure Controller.
Head Pressure Control Package
a. Controller shall control coil head pressure by condenser−fan speed modulation or condenser−fan cycling
and wind baffles.
b. Shall consist of solid−state control and condenser−coil temperature sensor to maintain condensing temperature between 90_F (32_C) and 110_F (43_C) at outdoor ambient temperatures down to −20_F (−29_C).
Condenser Coil Hail Guard Assembly (Factory installed on 3 Phase Models Only. Field installed on all 3 and 1
Phase Models)
a. Shall protect against damage from hail.
b. Shall be louvered design.
Unit−Mounted, Non−Fused Disconnect Switch (Available on units with MOCP’s of 80 amps or less):
a. Switch shall be factory−installed, internally mounted.
b. National Electric Code (NEC) and UL approved non−fused switch shall provide unit power shutoff.
c. Shall be accessible from outside the unit
d. Shall provide local shutdown and lockout capability.
Convenience Outlet (3 Phase Models Only):
e. Non−Powered convenience outlet.
(1.) Outlet shall be powered from a separate 115/120v power source.
(2.) A transformer shall not be included.
(3.) Outlet shall be factory−installed and internally mounted with easily accessible 115−v female receptacle.
(4.) Outlet shall include 15 amp GFI receptacles with independent fuse protection.
(5.) Outlet shall be accessible from outside the unit.
(6.) Outlet shall include a field−installed “Wet in Use” cover.
Thru−the−Base Connectors:
a. Kits shall provide connectors to permit electrical connections to be brought to the unit through the unit
basepan.
b. Minimum of four connection locations per unit.
513 31 3209 02
12. Supply Duct Cover (16 size only):
a. Required when field converting the factory standard vertical duct supply to horizontal duct supply configuration. One required per unit.
13. Propeller Power Exhaust:
a. Power exhaust shall be used in conjunction with an integrated economizer.
b. Independent modules for vertical or horizontal return configurations shall be available.
c. Horizontal power exhaust is shall be mounted in return ductwork.
d. Power exhaust shall be controlled by economizer controller operation. Exhaust fans shall be energized
when dampers open past the 0−100% adjustable setpoint on the economizer control.
14. Roof Curbs (Vertical):
a. Full perimeter roof curb with exhaust capability providing separate air streams for energy recovery from the
exhaust air without supply air contamination.
b. Formed galvanized steel with wood nailer strip and shall be capable of supporting entire unit weight.
c. Permits installation and securing of ductwork to curb prior to mounting unit on the curb.
15. Thru−the−Bottom Utility Connectors:
a. Kit shall provide connectors to permit gas and electrical connections to be brought to the unit through the
basepan.
16. Outdoor Air Enthalpy Sensor:
a. The outdoor air enthalpy sensor shall be used to provide single enthalpy control. When used in conjunction
with a return air enthalpy sensor, the unit will provide differential enthalpy control. The sensor allows the
unit to determine if outside air is suitable for free cooling.
17. Return Air Enthalpy Sensor:
a. The return air enthalpy sensor shall be used in conjunction with an outdoor air enthalpy sensor to provide
differential enthalpy control.
18. Indoor Air Quality (CO2) Sensor:
a. Shall be able to provide demand ventilation indoor air quality (IAQ) control.
b. The IAQ sensor shall be available in duct mount, wall mount, or wall mount with LED display. The setpoint
shall have adjustment capability.
19. Smoke detectors (factory−installed only):
a. Shall be a Four−Wire Controller and Detector.
b. Shall be environmental compensated with differential sensing for reliable, stable, and drift−free sensitivity.
c. Shall use magnet−activated test/reset sensor switches.
d. Shall have tool−less connection terminal access.
e. Shall have a recessed momentary switch for testing and resetting the detector.
f. Controller shall include:
(1.) One set of normally open alarm initiation contacts for connection to an initiating device circuit on a fire
alarm control panel.
(2.) Two Form−C auxiliary alarm relays for interface with rooftop unit or other equipment.
(3.) One Form−C supervision (trouble) relay to control the operation of the Trouble LED on a remote test/
reset station.
(4.) Capable of direct connection to two individual detector modules.
(5.) Can be wired to up to 14 other duct smoke detectors for multiple fan shutdown applications.
20. Winter start kit
a. Shall contain a bypass device around the low pressure switch.
b. Shall be required when mechanical cooling is required down to 25_F (−4_C).
c. Shall not be required to operate on an economizer when below an outdoor ambient of 40_F (4_C).
21. Time Guard
a. Shall prevent compressor short−cycling by providing a 5−minute delay (±2 minutes) before restarting a
compressor after shutdown for any reason.
b. One device shall be required per compressor.
22. Electric Heat:
a. Heating Section
(1.) Heater element open coil resistance wire, nickel−chrome alloy, 0.29 inches inside diameter, strung
through ceramic insulators mounted on metal frame. Coil ends are staked and welded to terminal
screw slots.
513 31 3209 02
176
(2.) Heater assemblies are provided with integral fusing for protection of internal heater circuits not exceeding 48 amps each. Auto reset thermo limit controls, magnetic heater contactors (24 v coil) and
terminal block all mounted in electric heater control box (minimum 18 ga galvanized steel) attached to
end of heater assembly.
23. Disconnect Switch Bracket (16 size only)
a. Provides a pre−engineered and sized mounting bracket for applications requiring a unit mounted fused and
non−fused disconnect of greater than 100 amps. Bracket assures that no damage will occur to coils when
mounting with screws and other fasteners.
24. Hinged Access Panels
a. Shall provide easy access through integrated quarter turn latches.
b. Shall be on major panels of: filters, control box, fan motor and compressor.
25. Display Kit for Variable Frequency Drive
a. Kit allows the ability to access the VFD controller programs to provide special setup capabilities and diagnostics.
b. Kit contains display module, mounting bracket and communication cable.
c. Display Kit can be permanently installed in the unit or used on any 2−Speed Indoor Fan Motor System
VFD controller as needed.
International Comfort Products
Lewisburg, Tennessee 37091 USA
www.GoArcoaire.com
177
513 31 3209 02
Download PDF