Fire Alarm Systems
Product Range Guide
■ EN Products
Fire Alarm Systems
Contents
NF Series Retrofit Control Panels. ................................................ 4
FX Series Retrofit Control Panels. ................................................ 8
NF Series Retrofit Accessories. .................................................. 12
FX Series Retrofit Accessories.................................................... 13
Detectors & Bases....................................................................... 14
Call Points & Notification Appliances etc..................................... 15
Loop Modules.............................................................................. 16
Software & Accessories. ............................................................. 17
■ JP Products
Conventional Control Panels....................................................... 18
Peripherals.................................................................................. 20
Products Index................................................................................. 22
Business Overview
The Nittan Group has been at the very forefront of the international fire protection industry since 1954 and has sales,
R&D and manufacturing bases in Japan, China, and the UK. Throughout the world, Nittan has an enviable reputation
for continuous innovation and exceptional quality. The group currently enjoys over $300million turnover worldwide
and manufactures millions of detectors each year, while pursuing a commitment to total excellence in everything we
do.
Despite its position as a major global fire safety specialist company, Nittan always prides itself in providing a
dedicated and personal service to its clients. When you look to Nittan to provide you with an optimum fire safety
solution, you’ll enjoy all the major benefits of dealing with a world leader – while receiving a personal level of service
and support that few large companies could ever hope to achieve.
In addition and as a completion to the fire detection solutions listed in this catalogue,
NITTAN offers also a complete selection of advanced products.
For further information, please contact NITTAN overseas business division from:
http://www.nittan.com
2
3
■ EN PRODUCTS
NF Series Retrofit Control Panels
Models
Conventional and Addressable Fire Alarm Control Panels
NF2000
NF1004
NF1002
Technical Features
Models
Conventional Zones
NF1002
NF1004
NF2000
2 zones
4 zones
4 zones
Expandable
Double the technology
Fighting fire power with another powerful element: technology. This is the challenge NITTAN issues
with the 3 versions of NF series fire panels: a brand-new family of advanced and performing fire panels,
for prevention and safety of medium to large applications, such as those realized in banks, industrial,
commercial, and residential buildings.
NF series includes: NF1002 panel: fire panel with 2 conventional zones; NF1004 panel: fire panel
with 4 conventional zones; and NF2000 panel that stands out for the possibility of dual configuration:
conventional (4 conventional zones expandable up to 12*) and hybrid of conventional and analogueaddressable (4 conventional zones expandable up to 12 and 32 analogue-addressable zones, thanks to
the optional NFEXP20 loop module.)
* To expand to 44 conventional zones with 5 expansion boards will be available soon.
Multiply the security
NF series panels are available in various versions, can be set up according to the single systems needs,
and adopt the dual working mode – conventional and conventional/analogue-addressable – to ensure
the most detailed monitoring of fire risks. Moreover, the possibility to integrate several models, make NF
panels able to manage up to 1400 detectors.
The most performing panels of the series can control 12 conventional zones and an analogueaddressable loop. The optional EXTING module extends panels functions, covering also the extinguishing
system control.
Big things with little effort
In spite of the excellent performance capability, the panels are very easy to set up and operate: the userfriendly interface, with graphic display and LED indicators, allows to operate the system effectively and in
a fast and intuitive way.
In addition, the USB connection can be used to configure the panel via PC for control and setup
parameters, or it is possible to install GSM for sending alarm messages through the GSM mobile network.
Available soon, Ethernet modules (optional) enable remote supervision and control of the panels.
4
Connectable detectors
Loop expansion board
Supported devices
Call point line
Programmable I/O lines
Alarm outputs(AL.REL)
Relay outputs
DC24V outputs
Display
Extinguishing module
Event logs
Interfaces and network
MINI-DIN
RS-485 Serial lines
Remote keypads
GSM
General
Protection Class
Dimensions
Weight
Recommended batteries
Power supply
Power supply unit
Output voltage at AL.REL
Available current at AL.REL
Certifications
Up to 44 zones
Conventional 12 zones
+ Addressable 32 zones
--32 per zone
---
NFEXP20 (optional)
---
254 over Loop
1 line
2 lines
4 lines
4 lines
1 supervised output for alarm protected by PTC
1 relay output for general fault
1 relay output for pre-alarm
2 auxiliary relay outputs
1 output protected by PTC
1 resettable output protected by PTC
Graphic LCD display – Color backlighting
EXTING (optional)
Up to 2000 entries
1 MINI-DIN for configuration with browser
2 lines
Up to 2 optional
Optional GSM module
IP30
W 320 X H 304 X D 83 mm
W 390 X H 390 X D 99 mm
4 kg
6 kg
12V - 7Ah
12V - 17Ah
AC230V – +10% / -15%
2A Max
DC27.6V
650mA Max
CPR 305/2011, EN54-2, EN54-4, EN54-21, EN12094-1 certification
(CPD 89/106/EEC ex certification)
5
NF2000 System Configuration
Flexibility and Expandability
6
●
NF2000 panels are able to manage the hybrid configuration of conventional and analogaddressable zones.
●
The expansion boards NFEXP20 (optional) allows to add to the panel one AS LOOP for analogaddressable devices. It allows to connect and manage up to 254 addressable devices connected
the LOOP.
●
The optional EXTING module extends panels functions, covering also the extinguishing system
control.
7
■ EN PRODUCTS
Fx Series Retrofit Control Panels
Models
Analogue-Addressable Fire Alarm Control Panels
FX/10
FX/20
FX/50
Technical Features
Security built on solid base.
In the development of FX series analogue addressable control unit multi-protocol and multi-language,
we combined performance power and management simplicity for the installer and the user. The
FX series control units are the effective solution for the industrial, commercial, bank, postal, service
sector, hotels, military, museum activities protection and, thanks to the low EMC impact, also for risk
environments such as operating theaters, hospitals and clinical laboratories. The versatility is the focal
point on which to build these fire detection control units. For this the FX series control units manage up
to 5 analogue addressable loop with AS or Evolution protocols with the ability to coordinate analogueaddressable loop also simultaneously with different protocols. The sensitivity thresholds of the sensors
(only in cases of AS loops) are programmable for alarm, pre-alarm and maintenance, also based on
time slots, in order to adapt the control unit to the different installation requirements. The FX control units
provide many possibilities for functional extension thanks to the ability to connect synoptic repeaters and
repeaters panels for command and remote signaling. The ability to define the logic equations for evolved
management completes the functionalities range. In detail, the control units outputs and the output
connected to the loop after events occurrence (logical or system) or pattern. They are settable up to 80
“Logical”, namely equations that generate outputs activation following the occurrence of certain logical
associated events, and up to 120 Pattern, activation paths of some outputs that is going to give in case of
alarm coming from define areas.
8
Models
Number of detection Loop
Number of Loop address
Zones number
Fault relay output
Alarm relay output
Supervised alarm output
DC24V output
General LEDs indication
Zone LEDs
LCD display
Keypad
Management levels
Peripherals Loop
Extinguishing management
Remote assistance
Management software
Control units and PC network
Events storage
Compatible protocols
Multi language menu
Electrical mechanical features
Power supply units
Allocable batteries
Power supply
Dimensions
Protection class
Certifications
FX/10
FX/20
FX/50
1
Up to 2
Up to 5
254
40
40
120
1 (8A @250V)
1 programmable (8A @250V)
1 programmable
2 programmable
4 programmable
1
Yes
Expandable to 40
Expandable to 120
4x20 character
Built-in for management and programming
3 access levels with 10 associated user password from step 1 at 2 level and
10 installer password associated from step 2 to level 3
1 for repeaters, synoptic and “intelligent”
Loop FX10485 board (optional)
power supplies units management
Through external control unit
With WINFIRE software
With GLOBAL MANAGEMENT, GLOBALFIRE and WINFIRE software
No
Up to 16
4000 events with graphic display of device historical
AS, Evolution
Italian, English, Spanish, German, Slovenian, Croatian
4A @ DC24V: 1.5A buffer battery charge, 0.5A max to the LOAD terminal for auxiliary device powered
2 x 6.5Ah/12V
2 x 15Ah/12V
2 x 24Ah/12V
AC230V
W 325 X H 304 X D 133 mm
W 480 X H 303 X D 180 mm
W 500 X H 570 X D 190 mm
IP3X
CPR 305/2011 EN54-2 and EN54-4 (CPD 89/106/EEC ex certification)
9
FX/50 System Configuration
The union is the safety
The real strength of the FX analogue-addressable fire detection control units multi-protocol and multilanguage is the connectivity. For even more complex and articulated structures it is possible to connect
via RS-485 network up to 16 FX control units, managed by a wide range of software suitable for any
type of need.
For a control units network even more effective and powerful, we developed the supervisor panel and
FXMASTER repeater. The new FXMASTER supervisor panel is able to interface and manage a network
up to 4 FX fire detection control units. In addition, is possible to create a network on RS-485 BUS of
8 FXMASTER able to divide the management up to 8 FX series fire alarm control units. FXMASTER
allows to view simultaneously the status of all control units connected to it or to those connected to
other FXMASTER on the network. It is able also to send EVACUATION, SILENCING and RESTORING
commands individually or simultaneously to all the control units via RS-485.
FXMASTER functional scheme
10
Analogue addressable detectors
Power supply unit
Analogue interface modules
Optical-acoustic devices
Accessories
Supervision and remote assistance software
Range of analogue-addressable smoke temperature
detectors for AS and EVOLUTION protocols with many
features such as the ability to program the temperature
threshold, the low consumption, the OmniView 360°
alarm signal and CPR certification.
Power supply unit range among which intelligent power
supply unit on RS-485 Serial BUS with voltage network
control, voltage supplied, battery voltage, current
consumption by the control unit, charge current of the
battery and internal temperature of the power supply
unit.
Wide range of analogue-addressable interface modules,
designed for the connection with traditional fire detection
devices or sensors. The relay can be used to command
magnetic retainer, optical-acoustic fire detection alarm
devices, light plaques or to perform different type
activation (skylights opening, electrical energy release,
gas...) or to acquire states and signals from external
devices.
Wide range of alarm detectors such as outdoor selfpowered sirens, indoor sirens, optical-acoustic devices,
optical-acoustic repeaters to signal the sensor status.
Wide range of accessories for the development
and expansion of the fire detection system with FX
control units: call-points, expansion board for AS and
EVOLUTION loop, isolator modules, board of RS-485
serial line interface, LAN interface modules, repeater
panels and all is necessary to complete the fire
detection system.
Remote assistance supervision and programming
soft ware range with maps that allow the direct
connection from PC to one or multiples control units,
multi-maps architecture, control protection levels and
system command, remote assistance and programming.
11
■ EN PRODUCTS
NF Series Retrofit Accessories
NFREPEATER
NFEXP10
• Repeating keypad unit for NF Series control units
• All functions and modes of the control unit are easily managed
from the graphical display and displayed by the signalling LED
• It’s connected to the control unit via an RS485 serial line and each
station can be connected up to 2 NFREPEATER
• Ability to change color of the backlight depending on the status of
the control unit: under normal operation, you will have a GREEN
illuminated display, in case of a malfunction or a fault signal the
display will be lit in YELLOW, in case of alarm the color will be
RED
• While programming or setting the control unit, the background
color will be WHITE
• Power supply DC24V from control unit or external power supply unit
• Power consumption 22mA
• CPR 305/2011, EN54-2 certification (CPD 89/106/EEC ex
certification)
• Supervised power supply unit for fire detection systems
• Equipped with connectors for the transformer connection,
electronic outputs for single fault events, for the connection of a
optional CP8/REL board and 5 optional relay boards UNIREL/24
• Equipped with LEDs front board for general indications
• Power supply AC230V 50Hz
• Output voltage DC24V/4A
• 1x 12V/26Ah allocable battery
• Dimensions W 305 x H 385 x D 210mm
• CPR 305/2011, EN54-4 certification (CPD 89/106/EEC ex
certification)
NFREL24
• 4 Relay board to be connected to NF series control units
• This module allows the control unit, if needed, to manage 4
additional relay outputs, reporting on the terminals the relative
contacts
• By connecting the module to the control unit without acting on the
programming (default), all 4 relays on the module will be activated
on FIRE event, while accessing the programming area at level 3,
each outputs can be programmed for different events
• Power supply DC24V from control unit
• Power consumption 40mA
• CPR 305/2011, EN54-2 certification (CPD 89/106/EEC ex
certification)
FX10485
FX/RP20
FX/485
• Display and functional control remote repeater, supplied with
keypad, LCD display for specific messages and 15 LEDs for
general warnings, excludable built-in buzzer
• Dimensions W 250 x H 200 x D 70mm
• Power consumption 50mA quiescent mode, 90mA alarm mode
• Power supply DC24V from control unit or auxiliary power supply box
FX/SIN01
• RS485 interface board, installable inside FX/20 FX/50 series
control units
• Allows the communication over RS485 line between FX series
control units and Winfire supervision application equipped PC
• Dimensions W 52 x H 115 x D 20mm
• Power consumption 82mA
• Power supplied by control unit
ETRLAN
• Mimic unit with one driver board and one 40-zone FX/SIN10 board
with terminal outputs
• 2 additional FX/SIN10 boards installable, according to control unit
capacity
• Control unit communication via RS485 line
• Dimensions W 303 x H 480 x D 180mm
• Power consumption 32mA
• Power supply DC24V from add power supply box
FX/SIN10
• Internal LAN module for FX/10 fire detection control unit for LAN
network connection
• 10 Base T Ethernet LAN interface, RJ45 connector
• Supports CP, UDP, ICMP (ping), ARP and TELNET protocols
• DC24V power supply provided by the control unit
MDGSME
• GSM Module carried out for use with NF series control units and
other devices
• It allows the connection to and from the control unit through GSM
mobile network
• It allows to send voice alarm messages or via text message
• Power supply DC24V from control unit
• Power consumption 60mA max. (phone transmission), 115mA
max. (GPRS transmission)
• It requires antenna remotization kit mod. GSMEXA15 or
GSMEXA2
• CPR 305/2011, EN54-21 certification (CPD 89/106/EEC ex
certification)
• Remote repeater display with LCD display for specific messages
and 15 LEDs for general warnings
• Excludable built-in buzzer
• Dimensions W 250 x H 200 x D 70mm
• Power consumption 50mA quiescent mode, 62mA alarm mode
• Power supply DC24V from control unit or auxiliary power supply
box
• RS485 serial interface board for FX/10 detection control unit, it
allows the connection of power supply units mod. FX/AL01 (max
15), remote keyboards mod. FX/RP10 - FX/RP20, synoptical unit
mod. FX/SIN01 (max 15), for a total of n.30 devices connectable
• 1000 meters max cable length
• Power supply unit input: AC230V-2A; Output DC29V-2A
• JST connector
• Compatible with NF series control units
EXTING
• 1 zone extinguishing module for NF series control units
• 1 balanced input for manual devices for emergency interruption
• 1 balanced input for manual devices to estinguishing request
• 1 balanced input for estiunguishing agent flux indication
• 1 supervised output with PTC protection for estinguishing signal
transmission
• 1 supervised output with PTC protection for alarm devices
activation
• 1 supervised output with PTC protection for estinguishing
progress signal devices
• 1 module address selector
• 1 RS485 and power connector
• LED for module status
• Power supply DC24V
• Quiescent current with all the balancing 10mA
• Active condiotion power consumption 30mA
• Release condition power consumption 75mA
• Dimensions W 64 x H 125 x D 26 mm
• CPR 305/2011 EN12094-1 certification (CPD 89/106/EEC ex
certification)
FX/RP10
• Loop expansion board for FX/10, FX/20 and FX/50 series control
units, installable inside the control units
• Allows to connect up to 254 devices
• Equipped with LED indicator
• CPR 305/2011, certification (CPD 89/106/EEC ex certification)
AL2SW24
NFEXP20
• Loop expansion board for NF2000 control unit installable inside
control unit
• Allows to connect up to 254 analogue/addressable device with
AS loop board protocol
• Power supply DC24V
• Quiescent current 35mA
• Power consumption with 254 connected devices 175mA
• Maximum power consumption 500mA
• Dimensions W 129 x H 80 x D 20mm
• CPR 305/2011, EN54-2 certification (CPD 89/106/EEC ex
certification)with the NF system
FX/EXP01
• Expansion board for conventional NF2000 control units
• 8 power cunsumption balanced line input zones
• 8 open collector zones outputs
• Quiescent voltage DC24V
• Quiescent current with no balancing 11mA
• Quiescent current with balancing 50mA
• Maximum power cunsumption 165mA
• Dimensions W 140 X H 50 mm
• CPR 305/2011, EN54-2 certification (CPD 89/106/EEC ex
certification)
C1124EN
FX Series Retrofit Accessories
FXLAN
• 40-zone unit expansion board with terminal outputs for alarm and
fault zones signalling
• Installable inside FX/SIN01 mimic unit
C1124EN
• External LAN network connection module for FX/20 and FX/50
fire detection control unit
• 10 Base T Ethernet LAN interface, RJ45 connector
• Supports CP, UDP, ICMP (ping), ARP and TELNET protocols
• DC24V power supplied by control unit
• Supervised power supply unit for fire detection systems
• Equipped with connectors for the transformer connection,
electronic outputs for single fault events, for the connection of a
optional CP8/REL board and 5 optional relay boards UNIREL/24
• Equipped with LEDs front board for general indications
• Power supply AC230V 50Hz
• Output voltage DC24V/4A
• 1x 12V/26Ah allocable battery
• Dimensions W 305 x H 385 x D 210mm
• CPR 305/2011, EN54-4 certification (CPD 89/106/EEC ex
certification)
GSMACI
• Internal antenna kit for control units NF series needed to properly
install the MDGSME module inside control units if you have a
good signal cellular radio
FX/EXP10
• 40-LEDs board for fault/zones disabled alarm status indication
• Installable inside FX series control units
• 1 board installable on FX/10 and FX/20 units, up to 3 boards on
FX/50
GSMEXA15
• Optional antenna for MDGSME interfaces supplied with 15m cable
and connectors
• It can be installed 15m far from control unit or GSM interface when
used with the supplied antenna for a better coverage
MTM-E
• Programmer for ST-PY-AS
• Provides address setting and reading
• Battery Powered DC18V
• Needs 1 or 2 9V (PP3 type) alkaline batteries (Not supplied)
• Handheld, provided with shoulder belt
GSMEXA2
• Optional antenna for MDGSME interfaces supplied with 2m cable
and connectors
• It can be installed 2m far from control unit or GSM interface when
used with the supplied antenna
12
13
■ EN PRODUCTS
Detectors & Bases
Call Points & Notification Appliances etc.
Retrofit Call Points
Addressable Retrofit Detectors
ST-PY-AS
AS-MCP
EVC-PY-IS
• Latest Generation Nittan Optical Chamber
• Omniview 360° LED
• Robust Fully Modulated AS Communications Protocol
• EEPROM Addressed (Address stored in on-board EEPROM,
programmed by handheld programmer)
• WILL REPLACE ST-P-AS
• Quiescent Current - 500µA
• Alarm Current (LED on) - 5.2mA
• Approved to EN54-7:2000
ST-H-AS
• Thermistor Heat Sensor
• Robust Fully Modulated AS Communications Protocol
• DIL Switch Addressed
• Quiescent Current - 200µA
• Alarm Current (LED on) - 2mA
• Approved to EN54-5:2000
Conventional Detectors
• Intrinsically Safe Optical Detector
• Nittan Y Type Chamber
• Omniview 360° LED
• Wide Operational Range (12V-32V)
• Limited to 28v
• External Barrier
• Use UB-4-IS Base or EV-SPB-IS Base
• Quiescent Current - 50µA
• Alarm Current - 50mA
• Approved to EN54-7:2000 and ATEX
FIRERAY5000
• Smoke detector with infrared motorized and autocalibrating light
beam
• Linear optical range 50m
• Linear optical range expandable to 100 m with the optional
additional kit FIRERAY5000100KIT
• N°1 reflective prism (10x10cm)
• Includes control unit and reflective prism
• Easifit Fix system
• Integral laser
• Auto-Align fast automatic beam alignment
• Auto-Optimise building movement and contamination compensation
• Control unit able to manage up to 2 detectors
• 2 wire interface from control unit to detector
• Dimensions W 134 x H 135 x D 134mm (detectors)
• IP54 protection class
• Power consumption 1 detector 5mA (idle mode),6mA (alarm
mode).Alignment mode max 37mA
• Power supply DC24V
• Certified CPD CPD 89/106/EEC, EN54:12 and UL268
EVC-DP
• Dual Optical Detector Reduces False Alarms
• Omniview 360° LED
• Internal Alarm Current Limiting Resistor
• Wide Operational Voltage Range (16V-32V)
• Quiescent Current - 50µA
• Alarm Current - 50mA
• Approved to EN54-7:2000 + A1:2002
EVC-P
• Omniview 360° LED
• Internal Alarm Current Limiting Resistor
• Wide Operational Voltage Range (12V-32V)
• Optical Detector
• Quiescent Current - 50µA
• Alarm Current - 50mA
• Approved to EN54-7:2000 + A1:2002
EVC-H-A2S
• 62°C Heat Detector
• Omniview 360° LED
• Internal Alarm Current Limiting Resistor
• Wide Operational Voltage Range (11V-32V)
• Quiescent Current - 50µA
• Alarm Current - 50mA
• Approved to EN54-5:2000 + A1:2002
• Universal Mounting Base
Standardised Across Entire Nittan Group Worldwide
UB-4-IS
• 92°C Heat Detector
• Omniview 360° LED
• Internal Alarm Current Limiting Resistor
• Wide Operational Voltage Range (11V-32V)
• Quiescent Current - 50µA
• Alarm Current - 50mA
• Approved to EN54-5:2000 + A1:2002
• Outdoor optical repeater, can be connected onto analogue
addressable detector bases
• 2 red LED indicators
• ABS housing
• Dimensions W 100 x H 70 x D 35mm
• Power consumption 7.3mA max
• Power supply DC24V
AS-ABS
• Wall or Base Mounted Sounder
• DIL Switch Addressed
• Robust Fully Modulated AS Communications Protocol
• Quiescent Current - 200µA
• Alarm Current (active) 7-10mA (tone dependant)
• 16 Alarm Tones + 1 Alert Tone
• Retrofit model
• Conventional and Savwire Manual Call Point
• STI RESET Housing-IP24
• Internal Alarm Current Limiting Resistor
• Wide Operational Voltage Range (12V-28V)
• Includes back box and mounting plate. (allows both flush and
surface mounting)
• Approved to EN54-11:2001 + A1:2005
Notification Appliances
Xenon Beacon
• DC24V Red
Alarm Bell 150mm (6”)
• 150mm (6")
• DC24V
• Approved to EN54-3
Duct Detector Housing
UG-3
LB2000
• Very low power consumption (34mA) display panel, it allows the
use of cables with a reduced cross section thus reducing the
installation costs
• Optical alarm signaling with high power LED and with adjustable
flashing frequency
• Alarm indication with buzzer, max sound pressure: 90dB average
• Possibility of wiring side, increasing the comfort and ease of
installation
• Dimensions W 283 x H 150 x D 51. 5 mm (37.5 mm socket)
• DC12V / DC24V (range DC10 - 30V)
• CPR 305/2011, EN54-3 certification (CPD 89/106/EEC ex
certification)
• Duct Detector Housing
• Quick and Simple Installation
• Pre-assembled Cable Entries
• Error Free Pipe Mounting
• Test Hole in Cover
Gas Detectors
RGLOOP/CO
EL/7R
• Carbon monoxide (CO) detector with electrochemical cell
• Equipped with 4-20mA interface and output for direct loop
connection of FX series and NF series analogue-addressable
units
• 500ppm measurement range
• 50ppm pre-alarm first threshold, 100ppm alarm second thresholds
• Dimensions W 80 x H 172 x D 68mm
• Power consumption 18mA@DC12V (quiescent mode), 85mA
alarm 1 + 2 threshold, 20mA@DC24V (quiescent mode), 105mA
alarm 1 + 2 threshold
• Power supply DC12-24V
• Indoor piezoelectric fire alarm siren
• Red ABS housing
• Max sound pressure 103dB (1mt)
• Dimensions W 137 x H 95 x D 40mm
• Power consumption 290mA
• Power supply DC24V
SA100/24
• Intrinsically Safe Base for Use with EVC-PY-IS
UB-4R-470
• Detector Mounting Base with Schottky Diode & Resistor
14
RP-RS1-01/NTN
Detector Bases
UB-4
EVC-H-CS
• STI IP24 Housing MCP
• DIL Switch Addressed
• Robust Fully Modulated AS Communications Protocol
• Quiescent Current - 200µA
• Alarm Current (LED on) - 2mA
• Approved to EN54-10:2000 + A1:2005
EVC-IR
• Omniview 360° LED
• Internal Alarm Current Limiting Resistor
• Wide Operational Voltage Range (12V-32V)
• Dual Band IR Flame Detector
• Quiescent Current - 100µA
• Alarm Current - 50mA
• Approved to EN54-10:2000 + A1:2005
RFP/L
• Self-powered and self-protected outdoor siren
• Timed flashing with incandescent light bulb synchronized with
sounder
• Red NOVODUR housing
• Max sound pressure 110dB (1mt)
• Dimensions W 253 x H 290 x D 85mm
• Power consumption 17mA (quiescent mode), 0.55A (alarm mode)
• Power supply DC24V
• It can allocate a 12V/1.2Ah battery (not included)
• CPR 305/2011, EN54-3 certification (89/106/EEC ex certification)
RGRCO
• Carbon monoxide (CO) detector with electrochemical cell
• Equipped with 2 alarm relay outputs and 1 fail relay output
• 100ppm measurement range
• 50ppm pre-alarm threshold
• 100ppm alarm second thresholds
• Dimensions W 80 x H 172 x D 68mm
• Power consumption 22mA @ DC12V quiescent mode, 44mA
alarm threshold 1 + 2, 25mA @ DC24V quiescent mode, 47mA
alarm threshold 1 + 2
• Power supply DC12-24V
15
■ EN PRODUCTS
Retrofit Loop Modules
Isolators
ISOBASE
1I1OASBOX
• Universal line isolator unit, which can be installed on the detector’s
base, for disabling part of the loop in case a shortcircuit occurs
while normal operation is continued on remaining equipment
• We recommend installing an isolator every 32 detectors/
addresses
• Supplied with two LEDs indicating short circuit direction
• Dimensions diameter 106 x H 22mm
• Power consumption 270µA (quiescent mode), 26,5mA (short
circuit loop and LEDs ON)
• Power supply DC24V supplied by loop
• CPR 305/2011, EN54-17 certification (CPD 89/106/EEC ex
certification)
• 1 input-1 output analogue addressable module. Balanced / not
balanced input for alarm and failure alerts (line opened and
shortcircuited line), allows to connect 1 conventional detector (or
other devices) featuring NO relay output to a detection loop
• Unit address is set via rotary switch
• Terminals for NO inputs, LED alerts, relay outputs and serial loop
connection
• 1 bistable C-NO-NC relay output (2A at DC30V) or alternatively a
supervised output
• Dimensions W 91.6 x H 54.7 x D 20mm
• Housed in a small plastic box
• Power consumption 3.3mA (quiescent mode), 4.5mA (alarm mode)
• Power supply DC24V supplied by loop
• CPR 305/2011, EN54-18 certification (CPD 89/106/EEC ex
certification)
ISOBOX
• Universal analogic line isolator unit for disabling part of the loop in
case a short-circuit occurs while normal operation is kept on the
remaining equipment
• We recommend installing an isolator every 32 detectors/
addresses
• Supplied with two LEDs indicating short circuit direction
• Installable in mod. 503 optional case
• Dimensions W 91.6 x H 55 x D 19mm
• Power consumption 270µA (quiescent mode), 26.5mA (short
circuit loop and LEDs ON)
• Power supply DC24V supplied by loop
• CPR 305/2011, EN54-17 certification (CPD 89/106/EEC ex
certification)
• Analogue addressable module for 1 door control. The module
is equipped with 1 balanced input and 1 independent output to
receive signals from devices or detectors for the control of fire
door and to control their closure with its relay output
• The module is also equipped with 1 balanced / not balanced
input for alarm and failure alerts (line opened and shortcircuited
line), allows to connect 1 conventional detector (or other devices)
featuring NO relay output to a detection loop
• Unit address is set via rotary switch
• C-NC-NO bistable relay output (2A at DC30V)
• Dimensions W 91.6 x H 54.7 x D 20mm
• Housed in a small plastic box
• Power consumption 3.3mA (quiescent mode), 4.5mA (alarm mode)
• Power supply DC24V supplied by loop
• CPR 305/2011, EN54-18 certification (CPD 89/106/EEC ex
certification)
ISOSPLITAS
• Analogue addressable module for 2 doors control equipped with
4 balanced inputs and 2 independent outputs to receive signals
from devices or detectors for the control of 2 fire door or 2 fire
shutters and to control their closure with its relay output
• Each control relay output is associated with 2 inputs which
manages the closed and opened door status
• Unit address is set via rotary switch
• C-NC-NO bistable relay outputs (2A at DC30V)
• Equipped with line isolator
• Dimensions W 129 x H 80 x D 20mm
• Housed in a small plastic box
• Power consumption 5mA (quiescent status), 10mA (alarm mode)
• Power supply DC24V supplied by loop
• CPR 305/2011, EN54-17, EN54-18 certification (CPD 89/106/
EEC ex certification)
1IASBOX
• Analogue addressable module with one balanced / not balanced
input for alarm and failure alerts (line opened and shortcircuited
line), allows to connect 1 conventional detector (or other devices)
featuring NO relay output to a detection loop
• Unit address is set via rotary switch
• Terminals for NO input, LED alerts, and serial loop connection
• Dimensions W 91.6 x H 54.7 x D 20mm
• Housed in a small plastic box
• Power consumption 3.3mA (quiescent mode), 4.5mA (alarm mode)
• Power supply DC24V supplied by loop
• CPR 305/2011, EN54-18 certification (CPD 89/106/EEC ex
certification)
SCM-AS5
MTB
• Analogue addressable unit for local alarm, can be connected to
pull-cord switches, “pull-cord alarms” or for room calls
• Unit address is set via 8 dip-switches
• Dimensions W 59 x H 40 x D 15mm
• Power consumption 300µA (quiescent mode), 4mA (alarm mode)
• Power supply DC24V supplied by loop
Software & Accessories
Accessories
GLOBALPRO
FX/CNV
• GLOBALPRO is the supervision software that allows to
monitor simultaneously 24 hrs the Nittan fire detection
connected via LAN, both local and remote: Fire detection
systems based on FX series analogue-addressable
control units (FX/10, FX/20, FX/50, FXPRO and FXUP).
• RS485 to RS232 serial line converter to connect PC to FX-series
fire alarm control units
• Supplied with DB25/DB9 RS232 cable for FX/GRMAP and FX/
CFGMAP software applications use
• Field bus Galvanic insulation
• Power supply unit included
CP8/SER2
• Connecting cable for direct programming software and PRT
printer connection
• MINIDIN/DB9 connectors
• Length 60cm
GLOBALFIRE
• GLOBALFIRE software can supervise up to 15 FX fire
detection units, and, when connected over LAN network, it
can:
»» Download events from control units
»» Control electronic outputs of control units
»» Arm/disarm control units
»» Display sensors status on electronic maps
• Communications between fire detection control units and
a server equipped with GLOBALFIRE software,work
over the Ethernet, both in small geographic areas, LAN
networks, and in wide geographic areas, WAN networks.
• Compatible fire detection units are: FX/10, FX/20 and
FX/50.
4I4OASBOX
• 4 input-4 output balanced / not balanced analogue addressable
module, for alarm and failure alerts (line opened and shortcircuited
line), allows to connect 4 conventional detectors (or other devices)
featuring NO relay outputs to a detection loop
• Unit address is set via rotary switch
• Terminals for NO inputs, LED alerts, relay outputs and serial loop
connection
• 4 bistable C-NO-NC relay outputs (2A at DC30V)
• Equipped with line isolator
• Dimensions W 129 x H 80 x D 20mm
• Housed in a small plastic box
• Power consumption 5mA (quiescent status), 10mA (alarm mode)
• Power supply DC24V supplied by loop
• CPR 305/2011, EN54-17, EN54-18 certification (CPD 89/106/
EEC ex certification)
• Analogue addressable interface to connect a 4-20mA gas
detector to an analogue addressable detection loop
• The detector’s operating parameters can be monitored and the
operating thresholds set
• Connectable detectors are: TS293KG and TS292KG for LPG
detection, TS293KM and TS292KM for methane detection
• Unit address is set via 8 dip-switches
• Allocable in BOX3 (optional)
• Dimensions W 159 x H 119 x D 75mm
• Power consumption 3mA (quiescent mode), 15µA (alarm mode)
• Requires DC24V power supply
• Module to control sounders, can be inserted onto detection loop
• Inputs for local silencing button
•1 supervised output for sounders (2A@30VDC max.)
• Address is set by rotary switches
• Dimensions W 91.6 x H 54.7 x D 19.0 mm
•Power consumption by loop 3.3 mA (quiescent), 4.5 mA (alarm)
•Requires DC24V power supply from external power supply unit
Software
2DASBOX
Addressable I/O Modules
NAM-ASG
• Control and monitoring module, can be inserted onto the detection
loop, used to monitor conventional detectors
• Address is set by rotary switches.
• 1 conventional detector’s line input
• 1 relay output, 2A@30VDC / 0.5A@125VAC
• 1 power supply input, 1 power supply unit monitoring input
• Dimensions W 91.6 x H 54.7 x D 23.0 mm
• Power consumption by loop 18.5 mA (quiescent), 37.5 mA (alarm)
• Power supply DC24V supplied by loop
1D1IASBOX
Loop Splitter
• Module to connect 2 separate AS loop to the same loop board
• IP3X Protection class
• Power supply DC24V supplied by the loop
• Power consumption 4mA (quiescent mode), 55mA (max)
• Sparkover voltage closed-open Vso = 4.8V + 5%
• Sparkover voltage open-closed Vsc = 7.4V + 5%
• Insulator action time <100ms
• Faulty loop LED indication
• Dimensions and weight W 129 x H 80 x D 20mm, 94g
• Operating temperature -10°C / +55°C
• CPR 305/2011, EN54-17 certification (CPD 89/106/EEC ex
certification)
MCM-AS5
FX/STD
• Software for direct configuration ONLY
• Supplied free with FX control units (no enabling key required)
• Management of 1 FX control unit via RS485 or 1 control unit in LAN through serial port
virtualization SW
CP8/SER3
• Modem connecting cable for remote programming and remote
assistance connection
• MINIDIN/DB25 connectors
• Length 60cm
USB485
• USB to RS485 serial line converter
• Without galvanic insulation
• Power supplied by PC
FX/CFGMAP
• Graphic software application for direct configuration, remote assistance and supervision of a single
control unit, supplied with CFGMAP
• Management of 1 FX control unit via RS485
16
17
■ JP PRODUCTS
Conventional Fire Alarm Control Panels
1PM2
2PD1-10L
High reliability, Advanced fire detection
Main features
■ Re-sounding mode of panel alarm sounder
■ Individual alarm delay OFF function
■ CPU trouble back-up function
■ Output for local alarm bell sounding Emergency PA system interlocking
■ Conpact size
■ Alarm delay function
- Heat detector : 20 sec
- Smoke detector : 60 sec
■ Supervision of detector lines and fault conditions
■ Energy saving technology for its running cost
■ Light body (Using flame retardant ACS resin)
■ High reliability minimizes maintenance cost
■ Surge absorber
■ Spring clamp terminals
■ Built-in backup battery
Advanced function for easy installation and easy maintenance
■ Lightning protection
■ Alarm delay ON/OFF switch
■ Auto reset switch
■ Maintenance switch(all alarm silence)
■ Plug-in type terminals
Self-diagnosis function
Specifications
Number of zones
■ Constant monitoring disconnection of detector line
■ Monitoring circuit voltage low
■ Monitoring CPU trouble
■ Monitoring fuse blow
■ Monitoring disconnection of standby battery
■ Constant monitoring disconnection of emergency PA line
Number of detectors
End of line device
Alarm delay time
Local alarm bells
Indication lamp
Common fire alarm transfer
Number of bells (10mA)
Power supply
Standby battery
Dimensions
Weight
2PD1-10L
10
Heat type (2SC series): Required number
Smoke type (2KH series) : 20 / zone
CRE
Nominal alarm delay time : 60 sec (Heat :20sec / Smoke : 60sec)
DC24V 0.1A (B,BC)
AC25V 0.6A (PL,PL’)
Max load : DC24V 1.0A (GA,GB,GC)
10
AC220V+10%/-10%
DC24V 0.45Ah
W200 x H280 x D65mm
2.2kg
Dimension
20 zones cabinet
450
100
40 zones cabinet
60 zones cabinet
450
450
100
100
2PD1-5L
1250
1060
760
Main features
■ Conpact size
■ Alarm delay function
- Heat detector : 20 sec
- Smoke detector : 60 sec
■ Supervision of detector lines and fault conditions
■ Energy saving technology for its running cost
■ Light body (Using flame retardant ACS resin)
■ High reliability minimizes maintenance cost
■ Re-activation system
■ Surge absorber
■ Insert-style wiring terminal
■ Built-in backup battery
Specifications
Number of zones
Number of detectors
Specifications
Number of zones
Number of bells (10mA)
Number of bell blocks
Power supply
Indicator light
Standby battery
Dimensions (W x H x D mm)
Weight
18
1PM2-nLA
5
10
5
10
10
0.45Ah
450 x 760 x 100
18 kg
20
20
30
40
15
AC220V±10%(50-60Hz)
0.4A (AC25V)
450 x 1060 x 100
25 Kg
50
30
20
60
1.2Ah
450 x 1250 x 100
30kg
End of line device
Alarm delay time
Local alarm bells
Indication lamp
Common fire alarm transfer
Number of bells (10mA)
Power supply
Standby battery
Dimensions
Weight
2PD1-5L
5
Heat type (2SC series): Required number
Smoke type (2KH series) : 20 / zone
CRE
Nominal alarm delay time : 60 sec (Heat :20sec / Smoke : 60sec)
DC24V 125mA (B,BC)
AC25V 0.3A (PL,PL’)
Max load : DC24V 1.0A (F,F’ / GA,GB,GC)
12
AC220V+10%/-10%
DC24V 0.225Ah
W240 x H330 x D70mm
2.2kg
19
■ JP PRODUCTS
Peripherals
Manual Alarm Station
Annunciator
2SC-LS
PSH-nL
1CC2-70-LW
• Fixed temperature heat detector, 70℃ , water-proof
• Mechanical operating heat sensor - for reliability
• Response indicator lights up to show which detector has activated
• Ease of installation and wiring connection - reduces installation
costs
• Connections are non-polarised - reduces wiring mistakes
• Wide working voltage available to suit most control panels
• Self-resetting and requires no replacement of internal elements reduces maintenance costs
• Power consumption 0A (idle mode)
2KAH2-P
• Dual optical smoke detector
• Reduces false alarms caused by non-combustion products
• 360°OMNIVIEW LED indicator for visible indication of operation
• Remote testing function
• Automatic sensitivity compensation
• Power consumption 40µA (idle mode), L-C: 65 mA / P-C: 50 mA
(Alarm)
• 1 open-collector output equipped
• Compatible with Nittan B3-J base
1CD-70-LS
LP01/LP02
2KH2-LS
• Fixed temperature heat detector, explosion-proof type
• Operating temperature range: 60℃ , 70℃ , 80℃ , 90℃ , 100℃ ,
120℃ , 150℃
• Contact capacity DC30V, 100mA
• Ex-proof grade : d2G4
• Gas sensor
• Catalytic combusion type
• Detecting gas: LP gas (heavier than air)
• Alarm sensitivity: less than 1/4 the lower explosion limit (LEL)
• Alarm indication: Red LED indicates instantly, Buzzer rings
instantly (automatic reset type)
• Power supply: DC24V
• UV flame detector
• Low supervising current - typical 120µA
• Wide supervising angle 100°- enables wide covering area by one
detector
• High reliability, Long life
• No polarity allows simple wiring connection
• Indication lamp lights when detector is activated
• Indication lamp flickers when detector in trouble
• Compatible with Nittan B4-F base
• Advanced, premium smoke detector, machinery built-in type
• Scattering light detection
• Very small - W 40 x H 45 x D 40mm
• High degree of protection against unwanted false alarms
• Extremely reliable fire detection
• Use with CPC-3 control unit
• Beam type smoke detector
• Wide range of monitoring distances 5m-100m
• Effective for open air space such as atria and exhibition sites etc.
• Reduce false alarms caused by transient or local smoke such as
cigarette
• Sensitive against smoke spread around a wide area compared to
ordinary point type smoke detectors
• Drift compensation function
• Not susceptible to light noise
• Power consumption 760µA (idle mode)
• Compatible with LP04 and LP05 remote station
LP04/LP05
• Remote station for beam type smoke detector
• Allowing functional testing of a high level mounted beam detector
to be carried out
• Operational test
• Signal monitoring
• Maintenance friendly operation
• Fault/Trouble signal (given an 50% of primary level)
• Number of units per control panel LP04: 3 units , LP05: 1 unit
• Conventional manual alarm station
• Stylish, light weight, strongly built
• Easy of installation and maintenance
• Latching action when operated
• Reset button provided for easy rest
• No break rods necessary
• No replacement of protection glass necessary after activation
• Contact capacity: DC30V 250mA
Local Alarm Bell
BD-6-24-11
• Conventional local alarm bell
• 150mm (6")
• Rating: DC24V 10mA
• Sound pressure level: more than 90dB/m
Indication Lamp
PL-R4-LED
CPC-3
• Indication lamp
• Lamp: LED
• Rating: 24V AC/DC 9mA
• Material: Polycarbonate
• Control unit for 0KB3 detector
• Compact unit W 125 x H 55 x D 208mm
2RA1-P
CKLD-KPT
2ME1A
0KB3
NFD-68-P
• Optical type smoke detector
• Low profile designing for visual concealment
• Effective screen for insects and dust particles
• Effective smoke inflow characteristics
• Wind and atmosphere variations have no influence
• No polarity allows simple wiring connection
• Wide working voltage of DC14.5V - 30V is designed to suit most
panels
• Power consumption less than 24µA (idle mode), 65mA (alarm
mode)
• Compatible with Nittan 3T base
20
FFH-2E
• Conventional manual alarm station with telephone jack
• Stylish, light weight, strongly built
• Easy of installation and maintenance
• Latching action when operated
• Reset button provided for easy rest
• No break rods necessary
• No replacement of protection glass necessary after activation
• Integral response indicator
• Contact capacity: DC30V 250mA
KP-35D
• Fixed temperature heat detector, 70℃
• Mechanical operating heat sensor - for reliability
• Response indicator lights up to show which detector has activated
• Ease of installation and wiring connection - reduces installation
costs
• Connections are non-polarized - reduces wiring mistakes
• Wide working voltage available to suit most control panels
• Self-resetting and requires no replacement of internal elements reduces maintenance costs
• Power consumption 0A (idle mode)
• Compatible with Nittan 3T base
•Remote test station for nKAD2-P, nKAH-P, 2SR2, TCR2, 1CR2
• LP01/0: 1 zone, drip-proof model
• LP01/1: 1 zone, standard model
• LP02/0: 4 zones, standard model
• Testing available by MTS2
1MF1A
• IR flame detector, explosion-proof/drip-dust proof (IP67), with
remote test function
• Dual IR sensing method reducing unwanted false alarms
• Low profile, compact size, light weight
• Max 120° wide detection angle
• Max 55m detection distance with 33cm x 33cm fire tray
• The operation indicator flickers to indicate the detector circuit
trouble
• Flexible installation to ceiling or wall with an adjustable mounting
brackets
• Ex-proof class : ExdⅡ CT6
• Rate-of-rise heat detector
• High quality components are fitted for greater reliability
• Indication lamp lights when the detector is activated
• The sensing chamber is electrically insulated
• Self-resetting and requires no replacement of internal elements reduces maintenance costs
• Power consumption 0A (idle mode)
• Compatible with Nittan 3T base
• Conventional annunciator panel
• Upon receiving the alarm signal, corresponding zone indicator will
illuminate with buzzer sound
• Zone number 5L-100L wall mounting type
• Power supply DC24V
• Compatible with the panels of 1PE/PF/PK/PM/PN/PQ/PS series
• Equipped with silence switch and telephone jack
Conventional Detectors
1RB-EW
• IR flame detector
• Dual IR sensing method reducing unwanted false alarms
• Low profile, compact size, light weight
• 17m-30m long detection distance
• Max 100° wide detection angle
• The operation indicator flickers to indicate the detector circuit
trouble
• Flexible installation to ceiling or wall with an adjustable mounting
brackets
• Compatible with Nittan B3-J base
AL-4-24
Detector Bases
B3-J
• Remote indication lamp
• Lamp: LED
• Rating: DC24V 5mA
• Material: Polycarbonate
• Detector mounting base for 2KW-P, 2RA1-P etc.
DRD-W
• IR flame detector, drip-dust proof (IP67), with remote test function
• Triple waveband IR sensing method reducing false alarms
• Max 100° wide detection angle
• Max 60m detection distance with 33cm x 33cm fire tray
• 360°OMNIVIEW LED indicates the conditions by four colors (Alarm,
Trouble, Startup, Testing)
• Selectable Response time and Self-Test cycle
• Current consumption approx. 6 mA (quiescent), 40 mA (max.)
• Equipped with an angle adjustable bracket
Local Combined Box
SU-01M6L-47SDB
3T
• Detector mounting base for 2KH2-LS, 2SC-LS, 1CD-70-LS etc.
• Local combined box, recessed mounting type
• Bell: BD-6-24-11
• Indication lamp: PL-R4-LED
• Manual alarm station: 1MF1A
• Plate: SUT-47S-05
※ The JP products in this catalogue are equivalent to the products approved with the Japanese standards.
21
Products Index
Model
Description
Page
UG-3
NF Series Panels
Gas Detectors
Duct Detector Housing
15
NF1002
Conventional Fire Alarm Control Panel, 2 zones
4
RGLOOP/CO
Addressable Carbon Monoxide (CO) Detector
15
NF1004
Conventional Fire Alarm Control Panel, 4 zones
4
RGRCO
Carbon Monoxide (CO) Detector
15
NF2000
Conventional / Addressable Fire Alarm Control Panel, 12 zones, 1 loop
4
Loop Modules
ISOBASE
Universal Line Isolator Unit
16
NFREPEATER
Remote Repeater with LCD Indication
12
ISOBOX
Universal Analogic Line Isolator Unit
16
C1124EN
Supervised Power Supply Unit
12
ISOSPLITAS
Loop Splitter for AS Loop
16
NFEXP20
Loop Expansion Board for NF2000
12
1IASBOX
1 input Addressable Module
16
EXTING
Extinguishing Module, 1 zone
12
1I1OASBOX
1 input-1output Addressable Module
16
NFEXP10
Zone Expansion Board for NF2000, 8 zones
12
1D1IASBOX
2 input-1output Addressable Module for 1 Door Control
16
NFREL24
Relay Board, 4 outputs
12
2DASBOX
4 input-2output Addressable Module for 2 Doors Control
16
AL2SW24
Power Supply Unit
12
4I4OASBOX
4 input-4output Addressable module
16
MDGSME
GSM Module
12
MCM-AS5
Zone Control / Monitoring Module
17
GSMACI
Internal Antenna Kit for MDGSME module
12
SCM-AS5
Sounder Control Module
17
GSMEXA15
Optional Antenna for MDGSME with 15m cable
12
NAM-ASG
1 input Addressable Module for 4-20mA Gas Detector
17
GSMEXA2
Optional Antenna for MDGSME with 2m cable
12
MTB
2 input Addressable Module for Pull-cord Switches
17
NF Series Accessories
FX Series Panels
Software
FX/10
Addressable Fire Alarm Control Panel, 1 loop
8
GLOBALPRO
Global Supervision System Software
17
FX/20
Addressable Fire Alarm Control Panel, 2 loops
8
GLOBALFIRE
Supervision Software up to 15 FX Control Panels
17
FX/50
Addressable Fire Alarm Control Panel, 5 loops
8
FX/STD
Local Configuration Software for 1 FX Control Panel
17
FX/CFGMAP
Graphic Supervision Software for 1 FX Control Panel
17
FX Series Accessories
FX/EXP01
Loop Expansion Board for FX series
13
Accessories
FX10485
RS-485 Serial Interface Board for FX/10
13
FX/CNV
RS485 to RS232 Serial Line Converter for FX Control Panels
17
FX/485
RS-485 Serial Interface Board for FX/20 and FX/50
13
CP8/SER2
Printer and Software Connecting Cable
17
ETRLAN
External LAN Module for LAN Network Connection for FX/10
13
CP8/SER3
Modem Connecting Cable
17
FXLAN
External LAN Module for LAN Network Connection for FX/20 and FX/50
13
USB485
USB to RS485 Serial Line Converter
17
FX/EXP10
LED Board, 40 zones
13
■ JP Products
FX/RP10
Remote Repeater with LCD Indication, General Signaling LED
13
Conventional Panels
FX/RP20
Remote Repeater with Control Keys, LCD Indication, General Signaling LED
13
1PM2
Conventional Fire Alarm Control Panel, 5-60 zones
18
FX/SIN01
Mimic Panel, 40 zones
13
2PD1-10L
Conventional Fire Alarm Control Panel 10 zones
19
FX/SIN10
Mimic Panel Expansion Board, 40 zones
13
2PD1-5L
Conventional Fire Alarm Control Panel 5 zones
19
C1124EN
Supervised Power Supply Unit
13
Annunciator
MTM-E
Programmer for ST-PY-AS
13
PSH-nL
Conventional Annunciator Panel, 5-100 zones
20
20
NF/FX Series Peripherals
Conventional Detectors
Addressable Detectors
2KAH2-P
Dual Optical Smoke Detector, with Remote Test Function
ST-PY-AS
Addressable Optical Smoke Detector
14
LP01/LP02
Remote Station for 2KAH2-P
ST-H-AS
Addressable Heat Detector
14
2KH2-LS
Optical Smoke Detector
20
CKLD-KPT
Beam Type Smoke Detector, 5m-100m
20
Conventional Detectors
EVC-DP
Conventional Dual Optical Smoke Detector
14
LP04/ LP05
Remote Station for Beam Type Smoke Detector
20
EVC-P
Conventional Optical Smoke Detector
14
2SC-LS
Rate-of-rise Heat Detector
20
EVC-H-A2S
Conventional Heat Detector, 62℃
14
1CC2-70-LW
Fixed Temperature Heat Detector, 70℃ , water-proof
20
EVC-H-CS
Conventional Heat Detector, 92℃
14
1CD-70-LS
Fixed Temperature Heat Detector, 70℃
20
EVC-PY-IS
Conventional Intrinsically Safe Optical Detector
14
NFD-68-P
UV Flame Detector
20
EVC-IR
Conventional IR Flame Detector
14
2RA1-P
IR Flame Detector
20
FIRERAY5000
Motorized Autocalibrate Beam Type Smoke Detector, 50m
14
DRD-W
Triple Waveband IR Flame Detector, Drip-dust Proof, with Remote Test Function
20
1RB-EW
IR Flame Detector, Explosion-proof / Drip-dust proof, with Remote Test Function
21
Detector Bases
UB-4
Universal Mounting Base (for ST-PY-AS, ST-H-AS, EVC-P, EVC-H-A2, EVC-H-C, EVC-DP)
14
FFH-2E
Fixed Temperature Heat Detector, Explosion-proof Type
21
UB-4-IS
Intrinsically Safe Base for Use with EVC-PY-IS
14
KP-35D
LP Gas Detector
21
UB-4R-470
Detector Mounting Base with Schottky Diode & Resistor
14
0KB3
Machinery Built-in Type Smoke Detector
21
CPC-3
Control Unit for 0KB3 Detector
21
Call Points
AS-MCP
Addressable Manual Call Point
15
Detector Bases
RP-RS1-01/NTN
Conventional Manual Call Point
15
B3-J
Detector Mounting Base for 2KW-P, 2RA1-P etc.
21
3T
Detector Mounting Base for 2KH2-LS, 2SC-LS, 1CD-70-LS etc.
21
Notification Appliances
22
Duct Detector Housing
■ EN Products
Alarm Bell 150mm (6”)
Conventional Local Alarm Bell, 150mm (6")
15
Manual Alarm Station
LB2000
Optical-acoustic Alarms
15
1MF1A
Conventional Manual Alarm Station with Telephone Jack
21
EL/7R
Indoor Piezoelectric Fire Alarm Siren
15
2ME1A
Conventional Manual Alarm Station
21
SA100/24
Outdoor Fire Alarm Siren
15
Notification Appliances
RFP/L
Remote Optical Repeater
15
BD-6-24-11
Conventional Local Alarm Bell, 150mm (6")
21
AS-ABS
Addressable Wall or Base Mounted Sounder
15
PL-R4-LED
Indication Lamp, LED Type
21
Xenon Beacon
Beacon DC24V
15
AL-4-24
Remote Indication Lamp
21
SU-01M6L-47SDB
Local Combined Box, Recessed Mounting Type
21
23
NITTAN COMPANY, LIMITED
Nittan implements detailed sales activities and support activities for customers
in response to each individual fire prevention issue, with the establishment of
45 branch offices and service centers as well as more than 120 distributors
throughout Japan.
Overseas, global coverage encompasses Europe to Africa and the Middle East
to Southeast Asia, with a local subsidiary established in the United Kingdom in
1972.
The Nittan brand provides security to sites using state of the art fire prevention
technologies.
Distributor
http://www.nittan.com
July 2016 Edition
Products features as described above do not bind the manufacturer and may be modified without prior notice.
54-5, 1-chome, Sasazuka, Shibuya-ku, Tokyo151-8535, Japan
TEL:81-3-5333-7021 FAX:81-3-5333-8615
Download PDF