Product Catalog - Odyssey Split Systems Air Conditioners

Product Catalog
Split System Air Conditioners
Odyssey™
™
Heat Pump Condenser — 5 to 16.7 Tons — 50 Hz
Air Handler — 4.6 to 16.7 Tons — 50 Hz
March 2018
SSP-PRC024J-EN
Introduction
Trane’s reputation for providing quality comfort solutions continues with the development of the
next generation Light Commercial Odyssey Split Systems.
With wide network availability, flexible applications, installation ease, built-in reliability and easy
servicing, Odyssey will meet any number of customer applications. Add to that Trane’s
outstanding customer service and you have the formula to make Odyssey the clear choice for
continued customer satisfaction.
Wide network availability
A broad distribution network provides owners, maintenance personnel, contractors, etc., the
means to get their hands on equipment when they need it. Whether it’s an emergency
replacement or a new construction project in its infancy stages, Odyssey products meet an array
of needs at the right time and right price.
Flexible applications
No matter what the application, Odyssey provides the solution. A broad array of models and
tonnages are available with single or dual compressors, single or dual circuits and numerous
accessories. Condensing units can be installed on the ground or on a rooftop along with
extended piping runs, while air handlers can be free discharge on the ground or horizontally
suspended with long duct runs from a ceiling. Should application challenges arise, Odyssey
delivers.
Easy to install
Small footprints and low weights combined with factory installed components like TXVs, filter
driers, etc., reduce installation time and cost. Colored and numbered wiring and factory tested
units make Odyssey the right choice.
Built-in reliability
Keeping in mind that productivity only occurs when equipment is operational,Trane has taken
the steps to ensure that Odyssey is up and running. Early indicators such as phase/reversal
monitors and loss of charge protection provide diagnostics which prevent failure and provide
years of worry-free service and operation.
©2018 Ingersoll Rand
SSP-PRC024J-EN
Introduction
Easy to service
When preventive maintenance or service is required, technicians will find efficient access to both
air handlers and condensers. Panels provide complete, easy access coupled with standardized
cabinets in which all components are located in proximity. Odyssey’s improved design results in
minimum service times and costs.
With these capabilities, Odyssey provides customers high efficiency and superior performance
for the best all-around value in the market today.
Copyright
This document and the information in it are the property of Trane, and may not be used or
reproduced in whole or in part without written permission. Trane reserves the right to revise this
publication at any time, and to make changes to its content without obligation to notify any
person of such revision or change.
Trademarks
All trademarks referenced in this document are the trademarks of their respective owners.
Revision History
SSP-PRC024J-EN
•
Configure to Order model number structure has been released and is now reflected in the
model structure. All referenced model numbers have been updated to reflect this.
•
Please note that data values have been updated in the following chapters: General Data,
Electrical Data, Weights, and Performance Data.
•
Running edits included.
3
Table of Contents
Features . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6
Split System Overview . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6
Standard and Optional Features. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7
Standard and Optional Controls. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9
Accessories. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 12
Heat Pump Condenser . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 12
Air Handler . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 13
Electric Heaters . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 14
Application Considerations . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 15
Clearance Requirements . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 15
180° Blower Rotation. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 15
Low Ambient Cooling . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 15
Selection Procedure . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 17
Cooling Capacity. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 17
Heating Capacity. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 17
Air Delivery . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 18
Model Number Description . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 19
Heat Pump Condenser . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 19
Air Handler . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 20
General Data. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 21
Performance Data . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 25
Gross Cooling Capacities . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 25
Gross Heating Capacities . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 49
Fan Performance . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 57
Controls . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 75
ReliaTel . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 75
Electromechanical . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 76
Electrical Data . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 77
Heat Pump Condenser . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 77
Air Handler (Standard) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 77
Jobsite Connections . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 80
ReliaTel Controls . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 80
4
SSP-PRC024J-EN
Table of Contents
Dimensional Data. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 81
Heat Pump Condenser . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 81
Air Handler . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 86
Accessories . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 93
Weights. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 100
Heat Pump Condenser . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 100
Air Handler . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 101
Accessories . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 103
Mechanical Specifications . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 104
Condensing Units. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 104
Air Handlers . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 106
SSP-PRC024J-EN
5
Features
Split System Overview
Unlike typical split systems on the market, Odyssey offers easy servicing, built-in reliability, ease
of installation and outstanding customer service. And because today’s owners are very costconscious when it comes to service and maintenance, the Odyssey Split System was designed
with direct input from service contractors. This valuable information helped to design a product
that would get the service person off the job quicker and save the owner money.
Flexible Applications
Odyssey offers outstanding standard features enhanced by a variety of factory and field installed
options, multiple control options, rigorously tested proven designs and superior product and
technical support. Because of this, Odyssey offers ultimate flexibility. Units are built to order in
our standard “shortest in the industry” ship cycle time. Odyssey is available with single, dual and
manifolded compressor options. Single compressor outdoor units feature a single refrigeration
circuitry, lowering job installation costs by requiring only one set of refrigerant lines.
Equally important, Odyssey offers single refrigerant circuit/capacity unloading models. The
unloading units feature dual manifolded scroll compressors with two stages of capacity
modulation and a single refrigeration circuit. Dual compressor/dual circuit models give true
stand-by protection - if one compressor fails, the second will automatically start-up. Also, the first
compressor can be serviced without shutting down the unit since the refrigerant circuits are
independent. Dual compressor models also save on energy costs. During light load conditions,
only one compressor will operate to save energy.
Unmatched Product Support
One of our finest assets, Trane Sales Representatives are a support group that can assist you
with:
•
Product
•
Application
•
Service
•
Training
•
Special Applications
•
Specifications
•
Computer Programs and much more
Rigorous Testing
Our units are rigorously rain tested to ensure water integrity. Actual shipping tests are performed
to determine packaging requirements. Units are test shipped around the country to determine
the best packaging. Factory shake and drop tests are used as part of the package design process
to help assure that the unit arrives at the job site in top condition. Rigging tests include lifting a
unit into the air and letting it drop one foot, assuring that the lifting lugs and rails hold up under
stress. A 100% coil leak test is performed at the factory. The condenser coils are leak tested at 660
psig and evaporators to 450 psig. All parts are inspected at the point of final assembly. Substandard parts are identified and rejected immediately. Every unit receives a 100% unit run test
before leaving the production line to ensure it lives up to rigorous Trane requirements.
6
SSP-PRC024J-EN
Features
Standard and Optional Features
Figure 1.
Compressors
Figure 2. Belt drive motor
Figure 3.
Easy access to terminal board
A i r f l o w D i s t r i b u t i o n — Odyssey can replace an older machine with old ductwork and, in many
cases, improve the comfort through better air distribution.
A n t i - S h o r t C y c l e T i m e r — Provides a 3 minute minimum “ON” time and 3 minute “OFF” time
for compressors to enhance compressor reliability by assuring proper oil return.
B e l t D r i v e M o t o r s — For additional static requirements, Odyssey Split Systems offer standard
belt drive motors to meet and exceed a wide range of airflow needs.
B l a c k E p o x y P r e - C o a t e d C o n d e n s e r C o i l s — The pre-coated coils are an economical option for
protection in mildly corrosive environments.
C o l o r e d A n d N u m b e r e d W i r i n g — Save time and money tracing wires and diagnosing the unit.
C o m p r e s s o r s — Odyssey Split Systems contain the best compressor technology available to
achieve the highest possible performance. Dual compressors perform very well under part load
cooling conditions and system back- up applications. Dual compressors are available on 4.6-20.9
ton models and allow for efficient cooling utilizing 2-stages of compressor operation.
C o n v e r t i b l e U n i t s — The air handlers ship in a horizontal configuration. They can be easily
converted to vertical by simply repositioning the drain pan. Units come complete with duct
flanges so the contractor doesn’t have to field fabricate them. These duct flanges are a time and
cost saver.
C r a n k c a s e H e a t e r s — These band heaters provide improved compressor reliability by warming
the oil to prevent migration during off-cycles or low ambient conditions.
D u a l S l o p e d D r a i n P a n s — Every Odyssey unit has a non-corrosive, removable, double sloped
drain pan that’s easy to clean and reversible to allow installation of drain trap in two positions on
either side of the unit.
E a s y A c c e s s L o w V o l t a g e T e r m i n a l B o a r d — Odyssey’s Low Voltage Terminal Board is
external to the line voltage electrical cabinet. It is extremely easy to locate and attach the
thermostat wire and test operation of all unit functions. This is another cost and time saving
installation feature.
E l e c t r i c H e a t e r s — Electric heat modules are available in a variety of voltages and capacities.
F o i l F a c e d I n s u l a t i o n — All internal air handler surfaces have cleanable foil-faced insulation. All
edges are either captured or sealed to ensure insulation fibers do not get into the airstream.
H a i l / V a n d a l G u a r d s — These coil guards shall be either factory or field installed for condenser
coil protection. This feature protects the condenser coil from vandalism and/or hail damage.
When ordered factory installed, it also adds additional shipping protection.
H i g h / L o w S t a t i c M o t o r — Available on many models, this high static motor accessory extends
the capability of the standard unit.
H i g h P r e s s u r e C o n t r o l — All units include High Pressure Control as standard.
L o w A m b i e n t — Provides ability to cool space when outdoor ambient is below 50°F. Choice of
fan on/off or modulating control.
SSP-PRC024J-EN
7
Features
L o w A m b i e n t C o o l i n g — All Odyssey microprocessor units have cooling capabilities down to 0°
F as standard.
L o w V o l t a g e C o n n e c t i o n s — The wiring of the low voltage connections to the unit and the zone
sensors is as simple as 1-1, 2-2, and 3-3. This simplified system makes it easy for the installer to
wire.
P h a s e M o n i t o r / R e v e r s a l P r o t e c t i o n — Phase monitor shall provide 100% protection for motors
and compressors against problems caused by phase loss, phase imbalance, and phase reversal.
Phase monitors are equipped with an LED that provides an ON or FAULT indicator.
Q u i c k - A c c e s s P a n e l s — Remove a few screws for access to the standardized internal
components and wiring.
S i n g l e P o i n t P o w e r — A single electrical connection powers the unit.
S i n g l e S i d e S e r v i c e — Single side service is standard on all units.
S t a n d a r d i z e d C o m p o n e n t s — Components are placed in the same location on all Odyssey
units. Because of these standardized components throughout the Odyssey line, contractors/
owners can stock fewer parts.
T h e r m a l E x p a n s i o n V a l v e w i t h B y p a s s C h e c k V a l v e s — This feature is standard on all indoor
units.
U n i t C a b i n e t — The compact cabinet takes up less room and is less costly to ship. It’s cabinet
design also ensures water integrity.
Table 1.
Odyssey features – standard and optional
Options(a)
Standard Factory
Field
Features Installed Installed
1-year Limited Parts Warranty
X
5-year Limited Compressor Warranty
X
Anti-Short Cycle Timer
X
Belt Drive Motors
X
Black Epoxy Pre-Coated Coils
X
Colored and Numbered Wiring
X
Compressor Discharge Temperature Limit (DTL)
X
Convertible Airflow
X
Crankcase Heaters
X
Easy Access Low Voltage Terminal Board (LTB)
X
Electric Heaters
X
Filters
X
Foil-Faced and Edge Captured Insulation
X
Hail/Vandal Guards
High Pressure Control
X
High Static Motor Kit(b)
X
IAQ Dual Sloped and Removable Drain Pans
X
Liquid Line Refrigerant Drier
X
Low Ambient Cooling
X
Low Ambient Cooling to 50°F on Electromechanical Models
X
Low Pressure Control
X
Low Static Motor Kit(b)
8
X
X
X
Low Voltage Circuit Protection
X
Phase Loss/Reversal Monitor
X
Quick Access Panels
X
Scroll Compressors
X
Single Point Power
X
SSP-PRC024J-EN
Features
Table 1.
Odyssey features – standard and optional (continued)
Options(a)
Standard Factory
Field
Features Installed Installed
Single Side Service
X
Standardized Components
X
Thermal Expansion Valve
X
Vibration Isolators
(a)
(b)
X
Refer to model number description for option availability or contact Product Support.
Available on standard units only. See Accessories chapter for more information.
Standard and Optional Controls
ReliaTel™
™ Controls
Figure 4. ReliaTel board
ReliaTel controls provide unit control for heating, cooling, and ventilating, utilizing input from
sensors that measure outdoor and indoor temperature. ReliaTel also provides outputs for
building automation systems and expanded diagnostics. Quality and reliability are enhanced
through ReliaTel control and logic:
•
Prevents the unit from short cycling, considerably improving compressor life.
•
Ensures the compressor will run for a specific amount of time which allows oil to return for
better lubrication, enhancing the reliability of the compressor.
•
Reduces the number of components required to operate the unit, reducing possibilities for
component failure.
ReliaTel Makes Installing and Servicing Easy
ReliaTel eliminates the need for field-installed, anti-short cycle timer and time delay relays. The
wiring of the low voltage connections to the unit and the zone sensors is as easy as 1-1, 2-2, and
3-3. This simplified system makes wiring easier for the installer.
ReliaTel Makes Testing Easy
ReliaTel requires no special tools to run the unit through its paces. Simply place a jumper
between Test 1 and Test 2 terminals on the Low Voltage Terminal Board and the unit will walk
through its operational steps automatically. The unit automatically returns control to the zone
sensor after stepping through the test mode a single time, even if the jumper is left on the unit.
As long as the unit has power and the “system on” LED is lit, ReliaTel is operational. The light
indicates that the controls are functioning properly. ReliaTel features expanded diagnostic
capabilities when utilized with Trane Integrated Comfort™ Systems. Some zone sensor options
have central control panel lights which indicate the mode the unit is in and possible diagnostic
information (dirty filters for example).
ReliaTel Has Other Benefits
SSP-PRC024J-EN
•
The ReliaTel built-in anti-shortcycle timer, time delay relay and minimum “on” time control
functions are factory tested to assure proper operation.
•
ReliaTel softens electrical “spikes” by staging on fans, compressors and heaters.
9
Features
•
Intelligent Fallback is a benefit to the building occupant. If a component goes astray, the unit
will continue to operate at predetermined temperature setpoint.
•
Intelligent Anticipation is a standard feature. It functions continuously as ReliaTel and zone
sensor(s) work together in harmony to provide much tighter comfort control than
conventional electromechanical thermostats.
•
The ReliaTel design is standardized across the board, ensuring a lower cost to owners.
Additional Controls
V a r i T r a c ® B u i l d i n g A u t o m a t i o n S y s t e m — When Trane’s changeover VAV System for light
commercial applications is coupled with the unit, it provides the latest in technological advances
for comfort management systems and can allow thermostat control in every zone served by
VariTrac.
T r a n e C o m m u n i c a t i o n I n t e r f a c e ( T C I ) — This module, when applied with ReliaTel, easily
interfaces with the Trane Integrated Comfort System™.
F r o s t a t ™ — This control utilizes a capillary bulb embedded in the face of the evaporator coil
which monitors coil temperature to inhibit evaporator icing and protect the compressor.
Recommended for applications with low leaving air temperatures, low airflow and/or high latent
load applications.
L o n T a l k ® C o m m u n i c a t i o n s I n t e r f a c e — The LonTalk communications interface allows the unit
to communicate as a Tracer™ LCI-V device or directly with generic LonTalk Network Building
Automation System Controls.
B A C n e t ® C o m m u n i c a t i o n I n t e r f a c e ( B C I ) — The BACnet Communication Interface allows the
unit to communicate directly with a generic open protocol BACnet MS/TP Network Building
Automation Control System.
Z o n e S e n s o r s / T h e r m o s t a t s — Available in wireless, programmable, automatic and manual
styles.
10
SSP-PRC024J-EN
Features
Table 2.
Odyssey control options – standard and optional
Options(a)
Standard Factory
Field
Features Installed Installed
BACnet Communication Interface (BCI)
Froststat - Evaporator Defrost Control (EDC)
X
X
LonTalk Communications Interface (LCI)
ReliaTel Microprocessor Controls
X
X
X
Thermostat
X
Trane Communications Interface (TCI)
X
Wireless Zone Sensor
X
Zone Sensor
X
(a)
SSP-PRC024J-EN
X
Refer to model number description for option availability or contact Product Support.
11
Accessories
Heat Pump Condenser
Table 3.
TWA Accessories
Model
Used With
Coil (Hail/Vandal) Guard
BAYGARD058*
TWA0604*A, TWA0764*A
BAYGARD059*
TWA060**D, TWA076**D
BAYGARD060*
TWA101
BAYGARD061*
TWA156, TWA201
Rubber Isolators
BAYISLT005* (black)
TWA060, TWA076, TWA101
BAYISLT009* (red)
TWA156
BAYISLT010* (green)
TWA201
Steel Spring Isolators
BAYISLT023* (red)
TWA060, TWA076, TWA101
BAYISLT024* (black)
TWA156
BAYISLT025* (yellow)
TWA201
Low Ambient — On/Off Fan Control (External mount, small cabinets)(a) (b) (c)
BAYLOAMU01* (External Mount, small cabinets)(d)
TWA060**A, TWA076**A
BAYLOAMU02* (Internal mount, large cabinets)
TWA101, TWA156, TWA201
Head Pressure Control(b)
BAYLOAM435*, 50Hz
TWA060*DA/D, TWA076*DA/D
BAYLOAM436*, 50Hz
TWA101*DA/D, TWA156*DD, TWA201*DD
Transducer Kit for Head Pressure Control (BAYLOAM435, 436, 437)
TWA060**D, TWA076**D, TWA101**D
BAYLOTR001*(e)
Trane Communication (3/4 Communications
BAYICSI003*
Interface)(f)
All Models
LonTalk Communications Interface(f)
BAYLTCI002*
(a)
(b)
(c)
(d)
(e)
(f)
12
All Models
Cycles fan on/off (no modulating).
Quantity of 1 required for each fan (2 total for 13 ton and larger).
ReliaTel™ requires onboard EDC function to be disabled when BAYLOAM is used, remove OA sensor from terminal J8-1&2
Kit mounts external to the outdoor unit and operates by sensing ambient and liquid line temperatures.
BAYLOTR001 required when modulating BAYLOAM kits used with units that have 2 compressors (dual circuit) and 1 condenser fan.
BAYWRKT003 must also be installed when using BAYICSI003 or the BAYLTCI002 on the 13–16.7T Split System Heat Pump units
SSP-PRC024J-EN
Accessories
Air Handler
Table 4.
TWE Accessories
Model
Used With
Base (Subbase)
BAYBASE009*
BAYBASE0010*
TWE051
TWE072, TWE076
BAYBASE0011*
TWE101
BAYBASE0012*
TWE126, TWE156
BAYBASE0013*
TWE201, TWE251
Drip Kit
BAYDRKT006*
TWE051
BAYDRKT007*
TWE072, TWE076
BAYDRKT008*
TWE101
BAYDRKT009*
TWE126, TWE156
BAYDRKT010*
TWE201, TWE251
High Static Motor Kits(a)
BAYHSMT105* — 1.0HP (50Hz) with Motor Sheave, Fan Sheave and Belt
TWE051*DA
BAYHSMT108* — 1.5HP (50Hz) with Motor Sheave, Fan Sheave and Belt
TWE072*DB, TWE076*DA/B
BAYHSMT110* — 2.0HP (50Hz) with Motor Sheave, Fan Sheave and Belt
TWE072*DB, TWE076*DA/B
BAYHSMT112* — 2.0HP (50Hz) with Motor Sheave, Fan Sheave and Belt
TWE101*DA/B
BAYHSMT114* — 2.0HP (50Hz) with Motor Sheave, Fan Sheave and Belt
TWE126*DB
BAYHSMT117* — 3.0HP (50Hz) with Motor Sheave, Fan Sheave and Belt
TWE126*DB
BAYHSMT120* — 3.0HP (50Hz) with Motor Sheave and Fan Sheave (Stock
Belt used)
TWE156*DB
BAYHSMT122* — 5.0 HP (50Hz) with Motor Sheave, Fan Sheave and Belt
TWE201*DB
Rubber Isolators(b) (c) (d)
BAYISLT004* (Floor — Blue)
TWE051, TWE072, TWE076, TWE101
BAYISLT009* (Floor — Red)(e)
TWE126, TWE156
BAYISLT010* (Floor — Green)(e)(b)
TWE201, TWE251
BAYISLT012* (Suspended —Red/Green)
TWE126, TWE156
BAYISLT013* (Suspended —Red/Green)(d)
BAYISLT014* (Suspended — Green)(d)
TWE051
TWE072, TWE076
BAYISLT015* (Suspended — Green/Black)(d)
TWE101
BAYISLT016* (Suspended —Red/Green)
TWE201
Steel Spring Isolators(c)
BAYISLT019* (Floor — Red)(e)(b)
TWE051, TWE072, TWE076, TWE101
BAYISLT021* (Floor — Black)(e)(b)
TWE126, TWE156
BAYISLT032* (Floor — Black/Yellow)(e)(b)
TWE201, TWE251
BAYISLT028* (Suspended — Tan)
TWE051
BAYISLT029* (Suspended — Red)
TWE072, TWE076, TWE101
BAYISLT030* (Suspended — Black)
TWE126, TWE156
BAYISLT031* (Suspended — Black/Yellow)
TWE201, TWE251
Low Static Drive Kit(a)
BAYLSMT001*
TWE201
Plenum(f)
BAYPLNM015* (Discharge Plenum & Grille)(f)
TWE051
BAYPLNM016* (Discharge Plenum & Grille)(f)
TWE072, TWE076
BAYPLNM017* (Discharge Plenum & Grille)(f)
TWE101
BAYPLNM018* (Discharge Plenum/Hydronic Coil Plenum & Grille)(f)
TWE126, TWE156
BAYPLNM019* (Discharge Plenum/Hydronic Coil Plenum & Grille)(f)
TWE201, TWE251
BAYPLNM020* (Hydronic Coil Discharge Plenum & Grille)(f)
SSP-PRC024J-EN
TWE051
13
Accessories
Table 4.
TWE Accessories (continued)
Model
Used With
BAYPLNM021* (Hydronic Coil Discharge Plenum & Grille)(f)
TWE072, TWE076
BAYPLNM022* (Hydronic Coil Discharge Plenum & Grille)(f)
TWE101
BAYPLNM030* (Electric Heat Discharge Plenum & Grille)(f)
TWE051
BAYPLNM031* (Electric Heat Discharge Plenum & Grille)(f)
TWE072, TWE076
BAYPLNM032* (Electric Heat Discharge Plenum & Grille)(f)
TWE101
BAYPLNM033* (Electric Heat Discharge Plenum & Grille)(f)
TWE126, TWE156
BAYPLNM034* (Electric Heat Discharge Plenum & Grille)(f)
TWE201, TWE251
Return Air Grille
BAYGRLE001*
TWE051
BAYGRLE002*
TWE072, TWE076
BAYGRLE003*
TWE101
BAYGRLE004*
TWE126, TWE156
BAYGRLE005*
TWE201, TWE251
Transformer
BAYTFMR013* -75VA transformer (380*415V/50hz)
TWE076, TWE101, TWE072
Water Kits
BAYWATR022* (Steam Coil Enclosure)(f)
TWE051
BAYWATR023* (Steam Coil Enclosure)(f)
TWE072, TWE076
BAYWATR024* (Steam Coil Enclosure)(f)
TWE101
BAYWATR025* (Steam Coil Enclosure)(f)
TWE126, TWE156
BAYWATR026* (Steam Coil Enclosure)(f)
TWE201, TWE251
BAYWATR027* (Hot Water Coil Enclosure)(f)
TWE051
BAYWATR028* (Hot Water Coil Enclosure)(f)
TWE072, TWE076
BAYWATR029* (Hot Water Coil Enclosure)(f)
TWE101
BAYWATR030* (Hot Water Coil Enclosure)(f)
TWE126, TWE156
BAYWATR031* (Hot Water Coil Enclosure)(f)
TWE201, TWE251
Wire Kit — 180° Blower Discharge Reversal Kit(g)
BAYWRKT002*
(a)
(b)
(c)
(d)
(e)
(f)
(g)
TWE051, TWE072, TWE076, TWE101
Used on standard air handlers only.
Requires use of subbase accessory.
In units with steam or hot water coils applied vertically or horizontally, check IOM for proper Isolator Kit selection.
Do not use if blower will operate less than 600 RPM.
When the air handler is in the vertical position and close proximity trapping of condensate is required, use of subbase is required.
When installed horizontally, plenum/water coil must be self-supported.
Cannot be used on TWE126–201, due to motor mount location.
Electric Heaters
Table 5.
Electric heaters
Model
Used With
4.6–8.33 Ton Electric Heater Selection
BAYHTRL405* — 3.13/3.74 kW Heater 380/415 / 3 Phase
TWE051, TWE072*D, TWE076, TWE101
BAYHTRL410* — 6.25/7.46 kW Heater 380/415 / 3 Phase
TWE051, TWE072*D, TWE076, TWE101
BAYHTRL415* — 9.37/11.17 kW Heater 380/415 / 3 Phase
TWE051, TWE072*D, TWE076, TWE101
BAYHTRL425* — 15.63/18.64 kW Heater 380/415 / 3 Phase
TWE051, TWE072*D, TWE076, TWE101
BAYHTRL435* — 21.86/26.08 kW Heater 380/415 / 3 Phase
TWE072*D, TWE076, TWE101
10.4–16.7 Ton Electric Heater Selection
BAYHTRM410* — 6.25/7.46 kW Heater 380/415 / 3 Phase
TWE126, TWE156, TWE201
BAYHTRM420* — 12.50/14.92 kW Heater 380/415 / 3 Phase
TWE126, TWE156, TWE201
BAYHTRM430* — 18.76/22.38 kW Heater 380/415 / 3 Phase
TWE126, TWE156, TWE201
BAYHTRM450* — 31.26/37.29 kW Heater 380/415 / 3 Phase
TWE126, TWE156, TWE201
14
SSP-PRC024J-EN
Application Considerations
Application of this product should be within the cataloged airflow and performance
considerations.
Clearance Requirements
The recommended clearances identified with unit dimensions should be maintained to assure
adequate serviceability, maximum capacity and peak operating efficiency. Actual clearances
which appear inadequate should be reviewed with the local representative.
180° Blower Rotation
The 4.6, 6.25, and 8.33 ton standard air handler blower section can be rotated 180° to change the
discharge pattern. This modification must be done in the field and requires an additional kit. See
unit installation guide.
Low Ambient Cooling
As manufactured, electromechanical units can operate to 50°F in the cooling mode of operation.
An accessory head pressure control will allow operation to 0°F outdoor ambient. When using
these units with control systems such as bypass changeover Variable Air Volume, make sure to
consider the requirement for a head pressure control to allow low ambient cooling.
Figure 5.
Typical split system application
Air Handling
Unit
Split
Condensing
Unit
SSP-PRC024J-EN
15
Application Considerations
Figure 6.
Typical horizontal air handler application
Isolator (4X)
(Spring or Rubber)
Support Rods and Attaching
Hardware (by others)
Electric Heater
Assembly
Air Handler
Heating Coil &
Enclosure Assembly
(Steam or Hot Water)
Figure 7.
Typical vertical air handler application
Discharge Plenum &
Grille Assembly
Heating Coil &
Enclosure Assembly
Air Handler
Horizontal
Drain
Return-Air Grille
Vertical
Drain
Subbase
Isolators
(Spring or Rubber)
16
SSP-PRC024J-EN
Selection Procedure
Cooling Capacity
1. Calculate the building’s total and sensible cooling loads at design conditions, using
standardized calculation methods.
2. Size the equipment using the gross cooling capacity tables. Match the cooling loads at design
conditions. For example, if the following specifies the building cooling requirements:
Electrical Characteristics: 415/50/3
Summer Design Conditions: Entering Evap Coil—80°F DB/67°F WB (27°C DB/19°C WB),
Outdoor Ambient—95°F (35°C)
Total Cooling Load: 75 MBh (22 kW)
Sensible Cooling Load: 56 MBh (16.4 kW)
Airflow: 2500 cfm (4248 m3/h)
External Static Pressure: .74 inches of water gauge
3. Use Table 14, p. 29 to determine that TWA076**A with TWE076**A has a gross cooling
capacity of 77.2 MBh (22.6 kW) and 62.8 MBh (18.4 kW) sensible capacity at 95°F DB (35°C)
ambient and 2500 cfm (4248 m3/h) with 80°F DB/67° F WB (27°C DB/19°C WB) air entering the
evaporator.
4. To find the net cooling capacities, fan motor heat must be subtracted. Determine the total unit
static pressure:
External Static Duct System: 0.74 (191.8 Pa)
Standard Filter: 0.10 in. (25 Pa)
Supplementary Electric Heat: .16 in. (40.6 Pa)
Total Static Pressure: 1 in. (249.09 Pa)
Notes:
•
The Evaporator Fan Performance Table has included the effect of a 1 in. (249 Pa)
filter already. Therefore, the actual Total Static Pressure is 1 - 0.1 = .9 in. (233.2 Pa).
With 2500 cfm (4248 m3/h) and .93 in. (231.6 Pa) , Table 62, p. 60 shows 1.51 Bhp
(ultra high static drive kit required).
•
This formula can be used to calculate Fan Motor Heat:
3.15 X Bhp = MBh
3.15 X 1.51 = 4.75 MBh
Net Total Cooling Capacity = 77.2 MBh - 4.75 MBh = 72.45 MBh (21.2 kW)
Net Sensible Cooling Capacity = 62.8 MBh - 4.75 MBh = 58.05 MBh (17.0 kW)
Heating Capacity
1. Calculate the building heating load using the Trane calculation form or any other standard
accepted method.
2. Size the equipment using Table 77, p. 74 to match the heating loads at design conditions. For
example, if the following specifies the building heating requirements:
Total Heating Load: 90.0 MBh (26.34 kW)
Outdoor Ambient (Winter): 17°F DB (-8.3°C)
Indoor Return Temperature: 70°F DB (21.1°C)
Airflow: 2500 cfm (4248 m3/h)
3. Table 46, p. 51 indicates the mechanical heating portion of the heat pump will provide 40.4
MBh for the winter design conditions. Full heat load must be carried by the supplementary
heater in the unlikely event the heat pump malfunctions. From Table 78, p. 74, the 34.88 kW
heater at 460V has a capacity of 119,045. From Table 82, p. 78, the 34.88 kW heater at 460V
indicates the heater model is BAYHTRL435.
SSP-PRC024J-EN
17
Selection Procedure
Air Delivery
1. The external static pressure drop through the air distribution system is .74 inches of water
gauge, use Table 77, p. 74 to determine that the static pressure drop through the electric
heater is 0.16 inches of water (.74 + .16 = .9 in.).
2. Enter Table 62, p. 60 for TWE0764DA at 2500 cfm (4248 m3/h) and 1.00 (249 Pa) static
pressure. The high static motor at 987 RPM gives the desired airflow.
18
SSP-PRC024J-EN
Model Number Description
Heat Pump Condenser
Digit 1–3 — Unit Function
Digit 8 — Voltage
Digit 15 — Controls
TWA = Split System Heat Pump
D = 380–415VAC - 3 PH (50Hz)
R = ReliaTel™
Digit 4–6 — Tonnage
Digit 9 — Refrigeration Circuit/Stage
Digit 16 — None
060 = 5 Tons (50Hz)
076 = 6.25 Tons (50Hz)
101 = 8.33 Tons (50Hz)
156 = 13.0 Tons (50Hz)
201 = 16.7 Tons (50Hz)
A = 1 Compressor/1 Line/1 Stage (Single)
D = 2 Compressors/2 Line/2 Stage (Duals)
0 = None
Digit 10 — Major Design Sequence
A = Rev A
Digit 7 — Refrigerant
Digit 11 — Minor Design Sequence
4 = R-410A
A = Rev A
Digit 12–13 — Service Digits
00 = 00
Digit 14 — Efficiency Generation
A = Generation A
Digit 17 — Coil Protection
0 = Standard Coil
1 = Standard Coil w/ Hail Guard
2 = Black Epoxy Pre-Coated Condenser Coil
(FIN/TUBE)
3 = Black Epoxy Pre-Coated Condenser Coil
with Hail Guard (FIN/TUBE)
Digit 18-20 — None
0 = None
Digit 21 — Communications Options
0 = No Option
2 = LonTalk® Communications Interface
(LCI)
Digit 22-40 — None
0 = None
SSP-PRC024J-EN
19
Model Number Description
Air Handler
Digit 1–3 — Unit Function
Digit 8 — Voltage
Digit 14 — Efficiency Generation
TWE = Air Handler
D = 380–415VAC - 3 PH (50Hz)
A = Generation A (2018 DOE)
Digit 4–6 — Tonnage
Digit 9 — Refrigeration Circuit/Stage
Digit 15 — Controls
051 = 4.6 Tons (50Hz)
072 = 6 Tons (50Hz)
076 = 6.25 Tons (50Hz)
101 = 8.33 Tons (50Hz)
126 = 10.4 Tons (50Hz)
156 = 13.0 Tons (50Hz)
201 = 16.7 Tons (50Hz)
251 = 20.9 Tons (50Hz)
A = Single Circuit
B = Dual Circuit
Digit 10 — Major Design Sequence
0 = Constant Volume
A = 2 Stage Airflow (Electromechanical Cond
Only)
B = Single Zone VAV (ReliaTel Cond Only)
A = Rev A
Digit 16 — Indoor Fan Sizes
Digit 11 — Minor Design Sequence
Digit 7 — Refrigerant
A = Rev A
0 = Standard Motor
4 = High Static – (Oversized Motor for VFD
Units)
4 = R-410A
Digit 12–13 — Service Digits
Digit 17–40 — None
0 = None
00 = 00
20
SSP-PRC024J-EN
General Data
Table 6.
General data for 5 - 6.25 ton (TWA0604DA* - TWA0764DD*) heat pump, 50 Hz
5 Tons
Single Compressor
TWA0604DA*
5 Tons
Dual Compressor
TWA0604DD*
6.25 Tons
Single Compressor
TWA0764DA*
6.25 Tons
Dual Compressor
TWA0764DD*
Matched Air Handler
TWE0764DA*
TWE0724DB*
TWE0764DA*
TWE0764DB*
AHRI Rated Airflow - (m³/hr)
2,000 (3398)
2,000 (3398)
2,500 (4248)
2,500 (4248)
Matched Air Handler - Btu (kW)
69,000 (20.2)
65,000 (19.0)
75,000 (22)
80,000 (23.4)
Condensing Unit Only - Btu (kW)
63,500 (18.6)
57,500 (16.9)
70,000 (20.5)
72,000 (21.1)
AHRI Net Cooling Capacity - Btu (kW)
68,000 (19.9)
64,500 (18.9)
74,000 (21.7)
79,000 (23.2)
11.8 / 13.2
11.8 / 12.9
11.8 / 12.7
11.8 / 13.1
5.3 / 4.8
4.9 / 4.5
6.2 / 5.5
6.1 / 5.5
62,000 (18.2)
52,000 (15.2)
66,000 (19.3)
65,000 (19)
4.7 / 3.4
4 / 3.4
4.9 / 3.4
4.9 / 3.4
38,500 (11.3)
29,800 (8.7)
41,000 (12)
38,000 (11.1)
4.2 / 2.3
3.7 / 2.3
4.5 / 2.3
4.5 / 2.3
Scroll
Scroll
Scroll
Scroll
1
2
1
2
Cooling Performance - Gross Cooling
Capacity
Efficiency
Matched Air Handler/Condensing Unit Only
System Power/Condensing Unit Power (kW)
Heating Performance - AHRI Htg/Matched
AH
High Temperature Capacity
System kW/COP
Low Temperature Capacity
System kW/COP
Compressor
Type
No.
System Data
No. Refrigerant Circuits(a)
Suction Line - in. (mm) OD(a)
Liquid Line - in. (mm) OD(a)
1
2
1
2
1-3/8 (34.90)
7/8 (22.23)
1-3/8 (34.90)
1-1/8 (28.60)
1/2 (12.70)
1/2 (12.70)
1/2 (12.70)
1/2 (12.70)
Outdoor Coil
Type
Tube Size - in. (mm) OD
Face Area, sq ft (m2)
Rows/FPI (Fins per inch)
Lanced
Lanced
Lanced
Lanced
3/8 (9.50)
3/8 (9.50)
3/8 (9.50)
3/8 (9.50)
19.24 (1.79)
19.24 (1.79)
19.24 (1.79)
23.96 (2.23)
2/18
2/18
2/18
2/18
Outdoor Fan
Type
No. Used/Diameter - in. (mm)
Drive Type/No. Speeds
Propeller
Propeller
Propeller
Propeller
1/26 (660.40)
1/26 (660.40)
1/26 (660.40)
1/26 (660.40)
Direct/1
Direct/1
Direct/1
Direct/1
CFM (m3/h)
5,525 (9,387)
5,525 (9,387)
5,525 (9,387)
5,525 (9,387)
No. Motor/HP (kW)
1/0.33 (0.25)
1/0.33 (0.25)
1/0.33 (0.25)
1/0.33 (0.25)
925
925
925
925
16.6 (7.5)
11.4/12.4 (5.2 / 5.6)
22.2 (10.1)
11.7/11.7 (5.3 / 5.3)
45” x 45” x 38”
(1143 x 1143 x 965)
45” x 55” x 42”
(1143 x 1397 x 1067)
45” x 45” x 38”
(1143 x 1143 x 965)
45” x 55” x 42”
(1143 x 1397 x 1067)
Motor RPM
Refrigerant Charge (Field Supplied)
lbs (kg) of R-410A
Shipping Dimensions
HxWxD - in. (mm)
Note: Units are tested in accordance with AHRI Standard 340-360 (I-P)-2007. Rating conditions are 95°F outdoor air temperature, 80°F entering dry bulb, 67°F
entering wet bulb with 25ft of interconnecting refrigerant piping with minimum external static pressure as determined by rating standard.
(a)
Refer to refrigerant piping applications manual for line sizing and line length.
SSP-PRC024J-EN
21
General Data
Table 7.
General data for 8.33 - 16.7 ton (TWA1014DA* - TWA2014DD*) heat pump, 50 Hz
8.33 Tons
Single Compressor
TWA1014DA*
8.33 Tons
Dual Compressor
TWA1014DD*
13 Tons
Dual Compressor
TWA1564DD*
Matched Air Handler
TWE1014DA*
TWE1014DB*
TWE1564DB*
TWE2014DB*
AHRI Rated Airflow - (m³/hr)
3,333 (5663)
3,333 (5663)
5,000 (8495)
6,667 (11327)
106,000 (31.0)
102,000 (29.9)
158,000 (46.3)
220,000 (64.5)
96,000 (28.1)
93,000 (27.3)
154,000 (45.1)
230,000 (67.4)
103,000 (30.2)
99,000 (29.0)
156,000 (45.7)
214,000 (62.7)
11.8 / 12.9
11.8 / 13.0
11.6 / 12.8
10.7 / 13.2
8.3 / 7.4
7.9 / 7.1
13.5 / 12.2
19.2 / 17.4
90,000 (26.4)
88,000 (25.8)
158,000 (46.3)
194,000 (56.9)
7 / 3.4
6.6 / 3.4
12.4 / 3.3
16.3 / 3.3
59,000 (17.3)
54,500 (16)
91,000 (26.7)
118,000 (34.6)
6.6 / 2.3
6.1 / 2.3
10.8 / 2.2
14.6 / 2.2
Scroll
Scroll
Scroll
Scroll
1
2
2
2
Cooling Performance - Gross Cooling
Capacity
Matched Air Handler - Btu (kW)
Condensing Unit Only - Btu (kW)
AHRI Net Cooling Capacity - Btu (kW)
16.7 Tons
Dual Compressor
TWA2014DD*
Efficiency
Matched Air Handler/Condensing Unit Only
System Power/Condensing Unit Power (kW)
Heating Performance - AHRI Htg/Matched
AH
High Temperature Capacity
System kW/COP
Low Temperature Capacity
System kW/COP
Compressor
Type
No.
System Data
No. Refrigerant Circuits(a)
Suction Line - in. (mm) OD(a)
Liquid Line - in. (mm) OD(a)
1
2
2
2
1-3/8 (34.90)
1-1/8 (28.60)
1-1/8 (28.60)
1-3/8 (34.90)
1/2 (12.70)
1/2 (12.70)
1/2 (12.70)
5/8 (15.88)
Outdoor Coil
Type
Tube Size - in. (mm) OD
Face Area, sq ft (m2)
Rows/FPI (Fins per inch)
Lanced
Lanced
Lanced
Lanced
3/8 (9.50)
3/8 (9.50)
3/8 (9.50)
3/8 (9.50)
29.02 (2.70)
29.02 (2.70)
52.6 (4.89)
52.6 (4.89)
2/18
2/18
2/18
2/18
Outdoor Fan
Type
No. Used/Diameter - in. (mm)
Drive Type/No. Speeds
CFM (m3/h)
No. Motor/HP (kW)
Motor RPM
Propeller
Propeller
Propeller
Propeller
1/28 (711.20)
1/28 (711.20)
2/28 (711.20)
2/28 (711.20)
Direct/1
Direct/1
Direct/1
Direct/1
8,250 (14,017)
8,250 (14,017)
16,354 (27,786)
16,354 (27,786)
1/.75 (0.56)
1/.75 (0.56)
1/.75 (0.56)
1/.75 (0.56)
925
925
925
925
34.7 (15.7)
14/14 (6.4 / 6.4)
19.2/19.9 (8.7 / 9.0)
18.6/18.4 (8.4 / 8.3)
52.1” x 55” x 42”
(1323 x 1397 x 1067)
52.1” x 55” x 42”
(1323 x 1397 x 1067)
51.1” x 96” x 48"
(1298 x 2438 x 1219)
51.1” x 96” x 48"
(1298 x 2438 x 1219)
Refrigerant Charge (Field Supplied)
lbs (kg) of R-410A
Shipping Dimensions
HxWxD - in. (mm)
Note: Units are tested in accordance with AHRI Standard 340-360 (I-P)-2007. Rating conditions are 95°F outdoor air temperature, 80°F entering dry bulb, 67°F
entering wet bulb with 25ft of interconnecting refrigerant piping with minimum external static pressure as determined by rating standard.
(a)
22
Refer to refrigerant piping applications manual for line sizing and line length.
SSP-PRC024J-EN
General Data
Table 8.
General data for 4.6 - 6.25 ton (TWE0514DA* - TWE0764DB*) air handler, 50 Hz
4.6 Tons
Single Circuit
TWE0514DA*
6 Tons
Dual Circuit
TWE0724DB*
6.25 Tons
Single Circuit
TWE0764DA*
6.25 Tons
Dual Circuit
TWE0764DB*
System Data
No. Refrigerant Circuits
Suction Line Connection, in. (mm) OD
Liquid Line Connection, in. (mm) OD
1
2
1
2
1 1/8 (28.58)
1 1/8 (25.60)
1 3/8 (34.90)
1 1/8 (25.60)
1/2 (12.70)
1/2 (12.70)
1/2 (12.70)
1/2 (12.70)
Indoor Coil
Type
Lanced/Intertwined
Lanced/Intertwined
Lanced/Intertwined
Lanced/Intertwined
Tube Size, in. (mm)
3/8 (9.50)
3/8 (9.50)
3/8 (9.50)
3/8 (9.50)
Face Area, sq. ft. (m2)
5.0 (0.46)
8.1 (0.75)
8.1 (0.75)
8.1 (0.75)
4/14
4/14
4/14
4/14
Refrigerant Control
Expansion Valve
Expansion Valve
Expansion Valve
Expansion Valve
Drain Connection Size, in. (mm)
1.0 (25.40) PVC
1.0 (25.40) PVC
1.0 (25.40) PVC
1.0 (25.40) PVC
Drive Type/No. Speeds
Centrifugal
1/12 x 12
(304.8 x 304.8)
Belt/Adjustable
Centrifugal
1/15 x 15
(381.0 x 381.0)
Belt/Adjustable
Centrifugal
1/15 x 15
(381.0 x 381.0)
Belt/Adjustable
Centrifugal
1/15 x 15
(381.0 x 381.0)
Belt/Adjustable
CFM (m3/h) (Nominal)
2,000 (3,398)
2,000 (3,398)
2,500 (4,248)
2,500 (4,248)
1
0.75/1.0
(0.56/0.75)
1450
1
1.5/2.0/3.0
(1.10/1.50/2.2)
1450
1
1.5/2.0/3.0
(1.10/1.50/2.2)
1450
1
1.5/2.0/3.0
(1.10/1.50/2.2)
1450
56
56H
56H
56H
Throwaway/Yes
(1) 16 x 20 x 1;
(1) 20 x 20 x 1
Throwaway/Yes
Throwaway/Yes
Throwaway/Yes
(3) 16 X 25 X 1
(3) 16 X 25 X 1
(3) 16 X 25 X 1
55.1” x 27.5” x 43.5”
(1399.5 x 698.5 x
1104.9)
61.2” x 30.5” x 53”
(1554.5 x 774.7 x
1346.2)
61.2” x 30.5” x 53”
(1554.5 x 774.7 x
1346.2)
61.2” x 30.5” x 53”
(1554.5 x 774.7 x
1346.2)
Rows/FPI
Indoor Fan
Type
No. Used/Diameter x Width, in. (mm)
No. Motors
Motor HP - Standard/Oversized (kw)
Motor RPM
Motor Frame Size
Filters
Type/Furnished
(No.)/Size Recommended
Shipping Dimensions
HxWxD - in. (mm)
SSP-PRC024J-EN
23
24
1.0 (25.40) PVC
Drain Connection Size, in. (mm)
3,350 (5,692)
No. Used/Diameter x Width, in. (mm)
CFM (m3/h) (Nominal)
56HZ
Motor HP - Standard/Oversized (kw)
Motor Frame Size
HxWxD - in. (mm)
61.2” x 30.5” x 69”
(1554.5 x 774.7 x
1752.6)
(4) 16 X 25 X 1
(No.)/Size Recommended
Shipping Dimensions
Throwaway/Yes
Type/Furnished
Filters
Motor RPM
1
2.0
(1.50)
1500
No. Motors
Drive Type/No. Speeds
Centrifugal
1/15 x 15
(381.0 x 381.0)
Belt/Adjustable
Type
Indoor Fan
Expansion Valve
Refrigerant Control
4/14
11.2 (1.04)
Face Area, sq. ft. (m2)
Rows/FPI
3/8 (9.50)
Tube Size, in. (mm)
Type
Lanced/Intertwined
1/2 (12.70)
Indoor Coil
Liquid Line Connection, in. (mm) OD
1
1 3/8 (34.90)
Suction Line Connection, in. (mm) OD
No. Refrigerant Circuits
8.33 Tons
Single Circuit
TWE1014DA*
61.2” x 30.5” x 69”
(1554.5 x 774.7 x
1752.6)
(4) 16 X 25 X 1
Throwaway/Yes
56HZ
1
2.0/3.0
(1.50/2.20)
1500
3,350 (5,692)
Centrifugal
1/15 x 15
(381.0 x 381.0)
Belt/Adjustable
1.0 (25.40) PVC
Expansion Valve
4/14
11.2 (1.04)
3/8 (9.50)
Lanced/Intertwined
1/2 (12.70)
1 1/8 (25.60)
2
8.33 Tons
Dual Circuit
TWE1014DB*
(8) 15 X 20 X 2
Throwaway/Yes
56HZ
1
3.0/5.0
(2.20/3.70)
1,450/1,500
5,000 (8,495)
Centrifugal
2/15 x 15
(381.0 x 381.0)
Belt/Adjustable
1.0 (25.40) PVC
Expansion Valve
4/14
16.3 (1.51)
3/8 (9.50)
Lanced/Intertwined
1/2 (12.70)
1 3/8 (34.90)
2
13 Tons
Dual Circuit
TWE1564DB*
76.3” x 33.8” x 85”
76.3” x 33.8” x 85”
(1938 x 850.9 x 2159) (1938 x 850.9 x 2159)
(8) 15 X 20 X 2
Throwaway/Yes
145T
1
2.0/3.0/5.0
(1.50/2.20/3.70)
1500
4,200 (7,136)
Centrifugal
2/15 x 15
(381.0 x 381.0)
Belt/Adjustable
1.0 (25.40) PVC
Expansion Valve
4/14
16.3 (1.51)
3/8 (9.50)
Lanced/Intertwined
1/2 (12.70)
1 3/8 (34.90)
2
10.4 Tons
Dual Circuit
TWE1264DB*
General data for 8.33 - 16.7 ton (TWE1014DA* - TWE2014DB*) air handler, 50 Hz
System Data
Table 9.
79.1” x 35.8” x 95”
(2009.1 x 909.3 x
2413)
Throwaway/Yes
(4) 16 X 25 X 2;
(4) 16 X 20 X 2
184T
1
3.0/5.0/7.5 (2.20/
3.70/5.60)
1,500/2,930
6,675 (11,341)
Centrifugal
2/15 x 15
(381.0 x 381.0)
Belt/Adjustable
1.0 (25.40) PVC
Expansion Valve
3/14
21.7 (2.01)
3/8 (9.50)
Lanced/Intertwined
5/8 (15.88)
1 3/8 (34.90)
2
16.7 Tons
Dual Circuit
TWE2014DB*
General Data
SSP-PRC024J-EN
Performance Data
Gross Cooling Capacities
Table 10.
Gross cooling capacities (MBH) TWA0604*A condensing unit with TWE0764*A air handler (IP)
Ambient Temperature (°F)
Ambient Temperature (°F)
85
95
Ambient Temperature (°F)
105
Entering Wet Bulb (°F)
Entering Wet Bulb (°F)
Entering Wet Bulb (°F)
Ent
61
67
73
61
67
73
61
67
73
DB
MBH
SHC
MBH
SHC
MBH
SHC
MBH
SHC
MBH
SHC
MBH
SHC
MBH
SHC
MBH
SHC
MBH
SHC
(°F)
CFM
1800
2000
2200
2400
75
64.6
53.9
72.1
42.1
80.2
29.7
61.5
52.4
68.7
40.7
76.5
28.3
58.2
50.9
65.1
39.2
72.5
26.9
80
64.7
63.6
71.9
51.9
80.3
39.7
61.6
61.6
68.5
50.5
76.6
38.3
58.3
58.3
65.2
49.1
72.6
36.9
85
64.7
64.7
72.3
61.7
80.4
49.7
61.7
61.7
68.9
60.3
76.7
48.3
58.4
58.4
65.3
58.8
72.7
46.9
90
64.8
64.8
72.4
71.4
80.2
59.6
61.7
61.7
69.0
69.0
76.7
58.3
58.4
58.4
65.4
65.4
72.8
56.8
75
65.8
57.1
73.4
44.0
81.5
30.2
62.7
55.6
69.9
42.6
77.6
28.8
59.2
54.0
66.2
41.1
73.5
27.4
80
65.9
65.9
73.5
55.0
81.7
41.4
62.7
62.7
70.0
53.5
77.8
40.0
59.3
59.3
66.3
52.0
73.7
38.6
85
66.0
66.0
73.6
65.7
81.8
52.5
62.8
62.8
70.1
64.3
77.9
51.1
59.4
59.4
66.4
62.8
73.4
49.6
90
66.0
66.0
73.7
73.7
81.8
63.4
62.8
62.8
70.2
70.2
78.0
62.0
59.4
59.4
66.5
66.5
73.9
60.5
75
66.9
60.2
74.5
45.9
82.6
30.7
63.6
58.7
70.9
44.5
78.6
29.3
60.1
57.1
67.0
43.0
74.4
27.9
80
66.9
66.9
74.6
57.8
82.7
43.0
63.7
63.7
71.0
56.4
78.8
41.6
60.2
60.2
67.2
54.8
74.6
40.2
85
67.0
67.0
74.7
69.7
82.5
55.1
63.7
63.7
71.1
68.2
78.5
53.8
60.2
60.2
67.3
66.7
74.3
52.3
90
67.0
67.0
74.8
74.8
82.9
67.1
63.7
63.7
71.2
71.2
79.0
65.7
60.2
60.2
67.3
67.3
74.8
64.2
75
67.7
63.3
75.4
47.7
83.5
31.2
64.4
61.7
71.7
46.3
79.4
29.8
60.8
60.1
67.8
44.8
75.1
28.4
80
67.8
67.8
75.5
60.7
83.7
44.6
64.5
64.5
71.8
59.2
79.6
43.2
60.9
60.9
67.9
57.6
75.3
41.8
85
67.9
67.9
75.6
73.6
83.4
57.9
64.5
64.5
71.9
71.9
79.7
56.4
60.9
60.9
68.0
68.0
75.4
54.9
90
67.9
67.9
75.7
75.7
83.9
70.8
64.5
64.5
72.0
72.0
79.8
69.4
60.9
60.9
68.1
68.1
75.6
67.9
Ambient Temperature (°F)
Ambient Temperature (°F)
115
125
Entering Wet Bulb (°F)
Entering Wet Bulb (°F)
Ent
61
67
73
61
67
73
DB
CFM (°F) MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC
1800
2000
2200
2400
75
54.7
49.2
61.2
37.7
68.2
25.4
50.8
47.5
57.1
36.0
63.6
23.8
80
54.8
54.8
61.3
47.5
68.4
35.4
50.9
50.9
57.2
45.8
63.8
33.8
85
54.8
54.8
61.4
57.2
68.1
45.4
51.0
51.0
57.3
55.5
63.6
43.8
90
54.8
54.8
61.5
61.5
68.6
55.2
51.0
51.0
57.4
57.4
64.0
53.6
75
55.6
52.3
62.2
39.5
69.1
25.9
51.6
50.6
57.9
37.9
64.4
24.3
80
55.7
55.7
62.3
50.4
69.3
37.1
51.7
51.7
58.0
48.6
64.7
35.5
85
55.7
55.7
62.4
61.1
69.1
48.1
51.8
51.8
58.2
58.2
64.8
46.5
90
55.7
55.7
62.5
62.5
69.6
58.9
51.8
51.8
58.2
58.2
64.9
57.3
75
56.3
55.4
63.0
41.4
69.9
26.4
52.3
52.3
58.6
39.7
65.1
24.8
80
56.4
56.4
63.1
53.2
70.1
38.7
52.4
52.4
58.7
51.5
65.4
37.1
85
56.5
56.5
63.2
63.2
70.3
50.7
52.4
52.4
58.9
58.9
65.5
49.1
90
56.5
56.5
63.3
63.3
70.4
62.6
52.5
52.5
58.9
58.9
65.7
61.0
75
57.0
57.0
63.6
43.2
70.5
26.9
52.9
52.9
59.2
41.6
65.6
25.3
80
57.1
57.1
63.8
56.0
70.8
40.3
53.0
53.0
59.3
54.2
66.0
38.7
85
57.1
57.1
63.9
63.9
71.0
53.3
53.0
53.0
59.4
59.4
66.1
51.6
90
57.1
57.1
63.9
63.9
71.1
66.3
53.0
53.0
59.5
59.5
66.3
64.6
Notes:
1. All capacities shown are gross and have not considered indoor fan heat. To obtain net cooling,
subtract indoor fan heat.
2. MBH = Total Gross Capacity, SHC = Sensible Heat Capacity
SSP-PRC024J-EN
25
Performance Data
Table 11.
Gross cooling capacities (kW) TWA0604*A condensing unit with TWE0764*A air handler (SI)
Ambient Temperature (°C)
Ambient Temperature (°C)
30
35
40
Entering Wet Bulb (°C)
Entering Wet Bulb (°C)
Entering Wet Bulb (°C)
Ent
16
Airflow DB
m3/hr (°C) kW SHC
3058
3398
3738
4078
19
22
16
3738
4078
16
19
22
SHC
kW
SHC
kW
SHC
kW
SHC
kW
SHC
kW
SHC
kW
SHC
kW
SHC
24
18.5
15.5
20.7
12.1
22.9
8.5
17.6
15.1
19.7
11.7
21.9
8.1
16.7
14.6
18.6
11.2
20.7
7.7
27
18.5
18.3
20.6
14.9
23.0
11.4
17.7
17.7
19.6
14.5
21.9
11.0
16.7
16.7
18.7
14.1
20.7
10.6
30
18.6
18.6
20.7
17.7
22.9
14.2
17.7
17.7
19.7
17.3
21.9
13.9
16.7
16.7
18.7
16.9
20.8
13.5
33
18.6
18.6
20.7
20.5
22.9
17.1
17.7
17.7
19.8
19.8
21.9
16.7
16.7
16.7
18.7
18.7
20.8
16.3
24
18.9
16.4
21.0
12.6
23.3
8.6
18.0
16.0
20.0
12.2
22.2
8.2
17.0
15.5
18.9
11.8
21.0
7.8
27
18.9
18.9
21.0
15.8
23.3
11.8
18.0
18.0
20.0
15.4
22.2
11.5
17.0
17.0
19.0
14.9
21.0
11.0
30
18.9
18.9
21.1
18.9
23.4
15.0
18.0
18.0
20.1
18.5
22.2
14.6
17.0
17.0
19.0
18.0
21.1
14.2
33
18.9
18.9
21.1
21.1
23.4
18.2
18.0
18.0
20.1
20.1
22.3
17.8
17.0
17.0
19.0
19.0
21.1
17.4
24
19.2
17.3
21.3
13.2
23.6
8.8
18.2
16.9
20.3
12.7
22.4
8.4
17.2
16.4
19.2
12.3
21.2
8.0
27
19.2
19.2
21.3
16.6
23.6
12.3
18.2
18.2
20.3
16.2
22.5
11.9
17.2
17.2
19.2
15.7
21.3
11.5
30
19.2
19.2
21.4
20.0
23.7
15.8
18.3
18.3
20.3
19.6
22.5
15.4
17.2
17.2
19.2
19.1
21.3
15.0
33
19.2
19.2
21.4
21.4
23.7
19.3
18.3
18.3
20.4
20.4
22.5
18.8
17.2
17.2
19.3
19.3
21.4
18.4
24
19.4
18.2
21.6
13.7
23.8
8.9
18.4
17.7
20.5
13.3
22.7
8.5
17.4
17.3
19.4
12.8
21.4
8.1
27
19.4
19.4
21.6
17.4
23.9
12.8
18.5
18.5
20.5
17.0
22.7
12.4
17.4
17.4
19.4
16.5
21.5
12.0
30
19.4
19.4
21.6
21.1
23.9
16.6
18.5
18.5
20.6
20.6
22.8
16.2
17.4
17.4
19.5
19.5
21.5
15.8
33
19.4
19.4
21.6
21.6
23.9
20.3
18.5
18.5
20.6
20.6
22.8
19.9
17.4
17.4
19.5
19.5
21.6
19.5
Ambient Temperature (°C)
45
52
Entering Wet Bulb (°C)
Entering Wet Bulb (°C)
Ent
16
Airflow DB
3
kW
SHC
m /hr (°C)
3398
22
kW
Ambient Temperature (°C)
3058
19
Ambient Temperature (°C)
19
22
16
19
22
kW
SHC
kW
SHC
kW
SHC
kW
SHC
kW
SHC
6.8
24
15.7
14.1
17.5
10.8
19.5
7.2
14.5
13.6
16.3
10.3
18.2
27
15.7
15.7
17.5
13.6
19.5
10.1
14.6
14.6
16.3
13.1
18.2
9.7
30
15.7
15.7
17.6
16.4
19.6
13.0
14.6
14.6
16.4
15.9
18.3
12.6
33
15.7
15.7
17.6
17.6
19.6
15.8
14.6
14.6
16.4
16.4
18.3
15.4
24
15.9
15.0
17.8
11.3
19.7
7.4
14.8
14.5
16.6
10.9
18.4
6.9
27
15.9
15.9
17.8
14.5
19.8
10.6
14.8
14.8
16.6
14.0
18.5
10.2
30
16.0
16.0
17.9
17.6
19.8
13.8
14.8
14.8
16.6
16.6
18.5
13.4
33
16.0
16.0
17.9
17.9
19.9
16.9
14.8
14.8
16.6
16.6
18.5
16.4
24
16.1
15.9
18.0
11.9
20.0
7.5
15.0
15.0
16.7
11.4
18.6
7.1
27
16.2
16.2
18.0
15.3
20.0
11.1
15.0
15.0
16.8
14.8
18.7
10.6
30
16.2
16.2
18.1
18.1
20.1
14.6
15.0
15.0
16.8
16.8
18.7
14.1
33
16.2
16.2
18.1
18.1
20.1
18.0
15.0
15.0
16.8
16.8
18.7
17.5
24
16.3
16.3
18.2
12.4
20.1
7.7
15.1
15.1
16.9
11.9
18.7
7.2
27
16.3
16.3
18.2
16.1
20.2
11.5
15.1
15.1
17.0
15.6
18.8
11.1
30
16.3
16.3
18.3
18.3
20.2
15.3
15.2
15.2
17.0
17.0
18.9
14.8
33
16.3
16.3
18.3
18.3
20.3
19.0
15.2
15.2
17.0
17.0
18.9
18.5
Notes:
1. All capacities shown are gross and have not considered indoor fan heat. To obtain net cooling,
subtract indoor fan heat.
2. kW = Total Gross Capacity, SHC = Sensible Heat Capacity
26
SSP-PRC024J-EN
Performance Data
Table 12.
Gross cooling capacities (MBH) TWA0604*D condensing unit with TWE0724*B air handler (IP)
Ambient Temperature (°F)
Ambient Temperature (°F)
Ambient Temperature (°F)
85
95
105
Entering Wet Bulb (°F)
Entering Wet Bulb (°F)
Entering Wet Bulb (°F)
Ent
61
67
73
61
67
73
61
67
73
DB
MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC
CFM (°F)
1800
2000
2200
2400
75
61.0
49.5
68.3
38.4
72.9
26.9
55.6
48.2
62.2
37.2
69.5
25.7
52.8
46.9
59.0
35.9
66.0
24.5
80
58.6
58.6
64.9
47.5
72.6
36.2
56.4
56.4
61.9
46.3
69.2
35.0
54.1
54.1
58.7
45.0
65.6
33.7
85
64.9
64.9
64.9
56.6
72.3
45.4
59.7
59.7
61.9
55.4
68.8
44.1
57.2
57.2
58.8
54.1
65.3
42.9
90
65.4
65.4
65.5
65.5
72.0
54.6
62.9
62.9
63.0
63.0
71.9
55.9
60.4
60.4
60.5
60.5
65.1
52.1
75
59.5
52.4
66.4
40.1
74.1
27.5
56.7
51.1
63.3
38.9
70.6
26.2
53.8
49.8
60.0
37.6
66.9
24.9
80
60.8
60.8
66.1
50.2
73.8
37.7
58.4
58.4
63.0
49.0
70.3
36.4
55.9
55.9
59.7
47.7
66.6
35.2
85
64.3
64.3
66.2
60.3
73.5
47.9
61.8
61.8
63.2
59.0
69.9
46.6
59.0
59.0
60.0
57.7
66.3
45.4
90
67.8
67.8
68.0
68.0
73.2
58.0
65.2
65.2
65.4
65.4
69.7
56.7
62.6
62.6
62.7
62.7
66.2
55.4
75
60.5
55.2
67.4
41.8
75.1
27.9
57.7
53.9
64.1
40.6
71.5
26.7
54.7
52.5
63.7
41.1
67.7
25.4
80
62.6
62.6
67.1
52.9
74.8
39.1
63.0
63.0
63.9
51.7
71.2
37.9
57.5
57.5
60.6
50.2
67.4
36.6
85
66.3
66.3
67.4
63.9
74.5
50.3
63.7
63.7
64.4
62.6
70.8
49.0
61.0
61.0
61.3
60.3
67.1
47.8
90
70.0
70.0
70.1
70.1
74.4
61.3
67.3
67.3
70.6
70.6
70.8
60.0
64.5
64.5
64.6
64.6
67.1
58.7
75
61.2
58.6
68.2
43.5
76.0
28.4
58.6
56.7
64.9
42.2
72.3
27.2
55.5
55.5
61.5
40.9
68.4
25.9
80
64.3
64.3
68.0
55.4
75.7
40.6
61.7
61.7
64.8
54.1
71.8
39.3
58.9
58.9
64.3
55.2
68.1
38.0
85
68.1
68.1
68.6
67.5
75.4
52.7
65.4
65.4
65.7
65.0
71.6
51.4
62.5
62.5
62.6
62.6
67.8
50.1
90
71.9
71.9
72.1
72.1
75.3
64.6
69.1
69.1
69.2
69.2
71.7
63.3
66.1
66.1
66.2
66.2
68.0
62.0
Ambient Temperature (°F)
Ambient Temperature (°F)
115
125
Entering Wet Bulb (°F)
Entering Wet Bulb (°F)
Ent
61
67
73
61
67
73
DB
MBH
SHC
MBH
SHC
MBH
SHC
MBH
SHC
MBH
SHC
MBH
SHC
CFM (°F)
1800
2000
2200
2400
75
49.9
45.6
55.7
34.6
62.3
23.2
46.9
44.2
52.3
33.3
58.5
21.9
80
51.6
51.6
55.5
43.8
61.9
32.4
49.0
49.0
52.1
42.4
58.1
31.1
85
54.7
54.7
55.6
52.8
61.6
41.6
52.0
52.0
52.5
50.7
57.7
40.3
90
57.7
57.7
57.8
57.8
61.4
50.7
54.9
54.9
55.0
55.0
57.7
49.4
75
53.2
50.7
56.6
36.3
63.1
23.7
47.9
46.3
53.1
34.9
59.2
22.3
80
53.3
53.3
56.4
46.4
62.8
33.9
50.6
50.6
52.9
44.9
58.9
32.6
85
56.5
56.5
56.9
55.5
62.5
44.1
53.7
53.7
53.8
53.6
58.6
42.7
90
59.7
59.7
59.8
59.8
62.4
54.1
56.7
56.7
56.8
56.8
58.6
52.7
75
51.9
50.5
57.3
37.9
63.9
24.1
48.9
48.9
53.7
36.6
59.8
22.8
80
54.9
54.9
57.2
48.9
66.6
37.0
52.0
52.0
53.7
47.5
59.5
34.0
85
58.1
58.1
58.2
58.2
63.2
46.4
55.2
55.2
55.2
55.2
59.3
45.0
90
61.5
61.5
61.6
61.6
63.3
57.4
58.3
58.3
58.4
58.4
59.3
56.0
75
52.8
52.8
57.9
39.5
64.4
24.5
50.0
50.0
54.2
38.1
60.3
23.2
80
56.2
56.2
57.9
51.4
64.2
36.7
53.2
53.2
54.1
50.4
60.1
35.4
85
59.6
59.6
59.7
59.7
63.9
48.7
56.5
56.5
56.5
56.5
59.8
47.3
90
63.0
63.0
63.1
63.1
64.0
60.7
59.7
59.7
59.8
59.8
59.9
59.9
Notes:
1. All capacities shown are gross and have not considered indoor fan heat. To obtain net cooling,
subtract indoor fan heat.
2. MBH = Total Gross Capacity, SHC = Sensible Heat Capacity
SSP-PRC024J-EN
27
Performance Data
Table 13.
Gross cooling capacities (kW) TWA0604*D condensing unit with TWE0724*B air handler (SI)
Ambient Temperature (°C)
3398
3738
4078
30
35
40
Entering Wet Bulb (°C)
Entering Wet Bulb (°C)
3398
3738
4078
19
22
16
19
22
16
19
22
kW
SHC
kW
SHC
kW
SHC
kW
SHC
kW
SHC
kW
SHC
kW
SHC
kW
SHC
24
17.9
14.5
20.0
11.3
21.4
7.9
16.3
14.1
18.2
10.9
20.4
7.5
15.5
13.7
17.3
10.5
19.3
7.2
27
17.2
17.2
19.0
13.9
21.3
10.6
16.5
16.5
18.1
13.6
20.3
10.2
15.8
15.8
17.2
13.2
19.2
9.9
30
19.0
19.0
19.0
16.6
21.2
13.3
17.5
17.5
18.1
16.2
20.2
12.9
16.8
16.8
17.2
15.9
19.1
12.6
33
19.2
19.2
19.2
19.2
21.1
16.0
18.4
18.4
18.5
18.5
21.1
16.4
17.7
17.7
17.7
17.7
19.1
15.3
24
17.4
15.3
19.5
11.8
21.7
8.0
16.6
15.0
18.5
11.4
20.7
7.7
15.8
14.6
17.6
11.0
19.6
7.3
27
17.8
17.8
19.4
14.7
21.6
11.0
17.1
17.1
18.5
14.4
20.6
10.7
16.4
16.4
17.5
14.0
19.5
10.3
30
18.8
18.8
19.4
17.7
21.5
14.0
18.1
18.1
18.5
17.3
20.5
13.7
17.3
17.3
17.6
16.9
19.4
13.3
33
19.9
19.9
19.9
19.9
21.5
17.0
19.1
19.1
19.2
19.2
20.4
16.6
18.3
18.3
18.4
18.4
19.4
16.2
24
17.7
16.2
19.8
12.3
22.0
8.2
16.9
15.8
18.8
11.9
21.0
7.8
16.0
15.4
18.7
12.1
19.9
7.4
27
18.3
18.3
19.7
15.5
21.9
11.5
18.5
18.5
18.7
15.1
20.9
11.1
16.9
16.9
17.8
14.7
19.8
10.7
30
19.4
19.4
19.8
18.7
21.8
14.7
18.7
18.7
18.9
18.4
20.8
14.4
17.9
17.9
18.0
17.7
19.7
14.0
33
20.5
20.5
20.6
20.6
21.8
18.0
19.7
19.7
20.7
20.7
20.7
17.6
18.9
18.9
18.9
18.9
19.7
17.2
24
17.9
17.2
20.0
12.7
22.3
8.3
17.2
16.6
19.0
12.4
21.2
8.0
16.3
16.3
18.0
12.0
20.0
7.6
27
18.8
18.8
19.9
16.2
22.2
11.9
18.1
18.1
19.0
15.9
21.1
11.5
17.3
17.3
18.8
16.2
20.0
11.1
30
20.0
20.0
20.1
19.8
22.1
15.4
19.2
19.2
19.2
19.1
21.0
15.1
18.3
18.3
18.4
18.4
19.9
14.7
33
21.1
21.1
21.1
21.1
22.1
18.9
20.2
20.2
20.3
20.3
21.0
18.6
19.4
19.4
19.4
19.4
19.9
18.2
Ambient Temperature (°C)
Ambient Temperature (°C)
45
52
Entering Wet Bulb (°C)
Entering Wet Bulb (°C)
Ent
16
Airflow DB
m3/hr (°C) kW SHC
3058
Ambient Temperature (°C)
Entering Wet Bulb (°C)
Ent
16
Airflow DB
m3/hr (°C) kW SHC
3058
Ambient Temperature (°C)
19
kW
SHC
22
16
kW
SHC
19
kW
SHC
kW
22
SHC
kW
SHC
6.4
24
14.6
13.4
16.3
10.1
18.3
6.8
13.7
13.0
15.3
9.7
17.1
27
15.1
15.1
16.3
12.8
18.2
9.5
14.4
14.4
15.3
12.4
17.0
9.1
30
16.0
16.0
16.3
15.5
18.1
12.2
15.2
15.2
15.4
14.9
16.9
11.8
33
16.9
16.9
16.9
16.9
18.0
14.9
16.1
16.1
16.1
16.1
16.9
14.5
24
15.6
14.9
16.6
10.6
18.5
6.9
14.0
13.6
15.6
10.2
17.4
6.5
27
15.6
15.6
16.5
13.6
18.4
9.9
14.8
14.8
15.5
13.2
17.3
9.5
30
16.6
16.6
16.7
16.3
18.3
12.9
15.7
15.7
15.8
15.7
17.2
12.5
33
17.5
17.5
17.5
17.5
18.3
15.9
16.6
16.6
16.7
16.7
17.2
15.5
24
15.2
14.8
16.8
11.1
18.7
7.1
14.3
14.3
15.7
10.7
17.5
6.7
27
16.1
16.1
16.8
14.3
19.5
10.8
15.2
15.2
15.7
13.9
17.4
10.0
30
17.0
17.0
17.1
17.1
18.5
13.6
16.2
16.2
16.2
16.2
17.4
13.2
33
18.0
18.0
18.0
18.0
18.6
16.8
17.1
17.1
17.1
17.1
17.4
16.4
24
15.5
15.5
17.0
11.6
18.9
7.2
14.6
14.6
15.9
11.2
17.7
6.8
27
16.5
16.5
17.0
15.1
18.8
10.8
15.6
15.6
15.9
14.8
17.6
10.4
30
17.5
17.5
17.5
17.5
18.7
14.3
16.5
16.5
16.6
16.6
17.5
13.9
33
18.5
18.5
18.5
18.5
18.8
17.8
17.5
17.5
17.5
17.5
17.6
17.6
Notes:
1. All capacities shown are gross and have not considered indoor fan heat. To obtain net cooling,
subtract indoor fan heat.
2. kW = Total Gross Capacity, SHC = Sensible Heat Capacity
28
SSP-PRC024J-EN
Performance Data
Table 14.
Gross cooling capacities (MBH) TWA0764*A condensing unit with TWE0764*A air handler (IP)
Ambient Temperature (°F)
Ambient Temperature (°F)
85
95
Ambient Temperature (°F)
105
Entering Wet Bulb (°F)
Entering Wet Bulb (°F)
Entering Wet Bulb (°F)
Ent
61
67
73
61
67
73
61
67
73
DB
CFM (°F) MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC
2250
2500
2750
3000
75
72.2
63.5
80.3
48.3
89.0
32.7
68.8
61.9
76.4
46.7
84.7
31.2
65.2
60.4
72.2
45.1
80.1
29.6
80
73.2
73.2
80.0
60.6
88.7
45.2
70.3
70.3
76.0
59.1
84.3
43.6
67.2
67.2
71.9
57.5
79.7
42.0
85
77.2
77.2
80.0
73.0
88.4
57.6
74.2
74.2
76.2
71.5
84.0
56.0
70.9
70.9
72.2
69.9
79.4
54.4
90
81.3
81.3
81.4
81.4
88.1
69.9
78.1
78.1
78.2
78.2
83.8
68.4
74.7
74.7
74.8
74.8
79.2
66.9
75
73.6
67.6
81.5
50.6
90.3
33.3
70.0
66.0
77.5
49.1
85.8
31.8
66.2
64.3
73.2
47.4
81.1
30.2
80
75.6
75.6
81.2
64.3
90.0
47.2
72.5
72.5
77.2
62.8
85.5
45.6
69.2
69.2
73.0
61.2
80.7
44.0
85
79.7
79.7
81.5
78.2
89.7
61.0
76.5
76.5
77.6
76.6
85.2
59.4
73.1
73.1
73.6
73.6
80.4
57.8
90
84.0
84.0
84.1
84.1
89.5
74.8
80.6
80.6
80.7
80.7
85.0
73.3
77.0
77.0
77.1
77.1
80.4
71.7
75
74.7
71.6
82.6
53.0
91.4
33.9
71.1
70.0
78.4
51.4
86.8
32.4
67.4
67.4
74.1
49.7
81.9
30.8
80
77.6
77.6
82.3
68.1
91.1
49.2
74.4
74.4
78.2
66.5
86.4
47.6
71.0
71.0
73.9
64.9
81.6
46.0
85
82.0
82.0
82.9
82.9
90.7
64.4
78.6
78.6
79.0
79.0
86.1
62.8
75.0
75.0
75.0
75.0
81.3
61.2
90
86.4
86.4
86.5
86.5
90.7
79.6
82.8
82.8
82.9
82.9
86.1
78.1
79.0
79.0
79.2
79.2
81.4
76.5
75
75.8
75.6
83.5
55.2
92.3
34.5
72.2
72.2
79.2
53.7
87.6
33.0
68.4
68.4
74.8
52.0
82.6
31.3
80
79.4
79.4
83.3
71.8
92.0
51.2
76.1
76.1
79.1
70.2
87.2
49.6
72.5
72.5
74.7
68.6
82.3
48.0
85
83.9
83.9
84.2
84.2
91.6
67.8
80.4
80.4
80.5
80.5
86.9
66.2
76.6
76.6
76.7
76.7
82.0
64.6
90
88.5
88.5
88.3
88.3
91.7
84.4
84.8
84.8
84.9
84.9
87.1
82.9
80.8
80.8
80.9
80.9
82.3
81.2
Ambient Temperature (°F)
Ambient Temperature (°F)
115
125
Entering Wet Bulb (°F)
Entering Wet Bulb (°F)
Ent
61
67
73
61
67
73
DB
MBH
SHC
MBH
SHC
MBH
SHC
MBH
SHC
MBH
SHC
MBH
SHC
CFM (°F)
2250
2500
2750
3000
75
61.5
58.8
67.9
43.4
75.3
27.9
57.7
57.1
63.6
41.8
70.3
26.3
80
63.9
63.9
67.7
55.8
75.0
40.4
60.5
60.5
63.4
54.2
70.0
38.7
85
67.5
67.5
68.1
68.1
74.6
52.8
63.8
63.8
63.9
63.9
69.7
51.2
90
71.1
71.1
71.2
71.2
74.5
65.3
67.3
67.3
67.4
67.4
69.7
63.6
75
62.6
62.6
68.8
45.8
76.2
28.5
58.8
58.8
64.4
44.1
71.1
26.9
80
65.7
65.7
68.6
59.5
75.9
42.4
62.2
62.2
64.3
57.9
70.8
40.7
85
69.5
69.5
69.6
69.6
75.5
56.2
65.7
65.7
65.7
65.7
70.5
54.5
90
73.2
73.2
73.3
73.3
75.6
70.1
69.2
69.2
69.3
69.3
70.6
68.4
75
63.7
63.7
69.5
48.0
77.0
29.1
60.1
60.1
65.0
46.4
71.8
27.4
80
67.3
67.3
69.5
63.2
76.6
44.4
63.7
63.7
65.0
61.6
71.4
42.7
85
71.2
71.2
71.3
71.3
76.3
59.6
67.2
67.2
67.3
67.3
71.1
57.9
90
75.1
75.1
75.2
75.2
76.5
74.8
70.9
70.9
71.0
71.0
71.6
71.6
75
64.9
64.9
70.2
50.3
77.6
29.7
61.3
61.3
65.6
48.6
72.3
28.0
80
68.8
68.8
70.2
66.9
77.2
46.4
64.9
64.9
65.6
65.1
71.9
44.7
85
72.7
72.7
72.8
72.8
76.9
63.0
68.6
68.6
68.6
68.6
71.7
61.3
90
76.7
76.7
76.8
76.8
77.5
77.5
72.3
72.3
71.6
71.6
72.5
72.5
Notes:
1. All capacities shown are gross and have not considered indoor fan heat. To obtain net cooling,
subtract indoor fan heat.
2. MBH = Total Gross Capacity, SHC = Sensible Heat Capacity
SSP-PRC024J-EN
29
Performance Data
Table 15.
Gross cooling capacities (kW) TWA0764*A condensing unit with TWE0764*A air handler (SI)
Ambient Temperature (°C)
Ambient Temperature (°C)
30
35
40
Entering Wet Bulb (°C)
Entering Wet Bulb (°C)
Entering Wet Bulb (°C)
Ent
16
Airflow DB
m3/hr (°C) kW SHC
3823
4248
4672
5097
19
22
3823
4248
4672
5097
19
22
16
19
22
kW
SHC
kW
SHC
kW
SHC
kW
SHC
kW
SHC
kW
SHC
kW
SHC
kW
SHC
24
21.0
18.5
23.3
14.1
25.7
9.5
20.0
18.1
22.1
13.6
24.4
9.0
18.9
17.6
20.9
13.1
23.1
8.5
27
21.3
21.3
23.2
17.7
25.6
13.1
20.4
20.4
22.0
17.2
24.3
12.7
19.5
19.5
20.8
16.7
23.0
12.2
30
22.4
22.4
23.2
21.3
25.5
16.7
21.5
21.5
22.1
20.9
24.2
16.3
20.6
20.6
20.9
20.4
22.9
15.8
33
23.6
23.6
23.6
23.6
25.5
20.4
22.6
22.6
22.7
22.7
24.2
19.9
21.6
21.6
21.7
21.7
22.9
19.5
24
21.4
19.7
23.6
14.7
26.1
9.6
20.3
19.3
22.4
14.3
24.8
9.2
19.2
18.8
21.2
13.8
23.4
8.7
27
22.0
22.0
23.5
18.8
26.0
13.7
21.0
21.0
22.3
18.3
24.7
13.2
20.1
20.1
21.1
17.8
23.3
12.8
30
23.2
23.2
23.6
22.8
25.9
17.7
22.2
22.2
22.5
22.4
24.6
17.3
21.2
21.2
21.3
21.3
23.2
16.8
33
24.4
24.4
24.4
24.4
25.9
21.8
23.4
23.4
23.3
23.3
24.5
21.3
22.3
22.3
22.3
22.3
23.2
20.9
24
21.7
20.9
23.9
15.4
26.4
9.8
20.6
20.4
22.7
14.9
25.0
9.4
19.5
19.5
21.4
14.5
23.6
8.9
27
22.5
22.5
23.8
19.8
26.3
14.3
21.6
21.6
22.6
19.4
24.9
13.8
20.6
20.6
21.4
18.9
23.5
13.4
30
23.8
23.8
24.0
24.0
26.2
18.7
22.8
22.8
22.9
22.9
24.8
18.3
21.7
21.7
21.7
21.7
23.4
17.8
33
25.0
25.0
25.1
25.1
26.2
23.2
24.0
24.0
24.0
24.0
24.8
22.8
22.9
22.9
22.9
22.9
23.5
22.3
24
22.0
22.0
24.1
16.1
26.6
10.0
20.9
20.9
22.9
15.6
25.3
9.5
19.8
19.8
21.6
15.1
23.8
9.1
27
23.1
23.1
24.1
20.9
26.5
14.9
22.1
22.1
22.9
20.5
25.1
14.4
21.0
21.0
21.6
20.0
23.7
13.9
30
24.3
24.3
24.4
24.4
26.4
19.7
23.3
23.3
23.3
23.3
25.0
19.3
22.2
22.2
22.2
22.2
23.6
18.8
33
25.6
25.6
25.7
25.7
26.5
24.6
24.5
24.5
24.6
24.6
25.1
24.2
23.4
23.4
23.4
23.4
23.7
23.7
Ambient Temperature (°C)
Airflow
m3/hr
16
Ambient Temperature (°C)
Ambient Temperature (°C)
45
52
Entering Wet Bulb (°C)
Entering Wet Bulb (°C)
16
19
22
16
19
22
kW
SHC
kW
SHC
kW
SHC
kW
SHC
kW
SHC
kW
17.8
17.1
19.6
12.6
21.7
8.1
16.7
16.7
18.4
12.2
20.3
SHC
7.6
18.5
18.5
19.6
16.3
21.6
11.7
17.6
17.6
18.3
15.8
20.2
11.2
19.6
19.6
19.7
19.7
21.5
15.4
18.5
18.5
18.5
18.5
20.1
14.9
20.6
20.6
20.6
20.6
21.5
19.0
19.5
19.5
19.5
19.5
20.1
18.5
18.1
18.1
19.9
13.3
22.0
8.2
17.1
17.1
18.6
12.8
20.5
7.8
19.1
19.1
19.8
17.3
21.9
12.3
18.0
18.0
18.5
16.9
20.4
11.8
20.1
20.1
20.1
20.1
21.8
16.4
19.0
19.0
19.0
19.0
20.3
15.9
21.2
21.2
21.1
21.1
21.8
20.4
20.0
20.0
20.0
20.0
20.4
19.9
18.5
18.5
20.1
14.0
22.2
8.4
17.4
17.4
18.8
13.5
20.7
7.9
19.5
19.5
20.1
18.4
22.1
12.9
18.4
18.4
18.8
17.9
20.6
12.4
20.6
20.6
20.6
20.6
22.0
17.3
19.4
19.4
19.5
19.5
20.5
16.9
21.7
21.7
21.7
21.7
22.1
21.8
20.5
20.5
20.5
20.5
20.6
20.6
18.8
18.8
20.3
14.6
22.3
8.6
17.8
17.8
18.9
14.1
20.8
8.1
19.9
19.9
20.3
19.5
22.2
13.5
18.8
18.8
19.0
19.0
20.7
13.0
21.0
21.0
21.1
21.1
22.2
18.3
19.8
19.8
19.8
19.8
20.6
17.8
22.2
22.2
22.2
22.2
22.3
22.3
20.9
20.9
20.9
20.9
20.9
20.9
Notes:
1. All capacities shown are gross and have not considered indoor fan heat. To obtain net cooling,
subtract indoor fan heat.
2. kW = Total Gross Capacity, SHC = Sensible Heat Capacity
30
SSP-PRC024J-EN
Performance Data
Table 16.
Gross cooling capacities (MBH) TWA0764*D condensing unit with TWE0764*B air handler (IP)
Ambient Temperature (°F)
Ambient Temperature (°F)
Ambient Temperature (°F)
85
95
105
Entering Wet Bulb (°F)
Entering Wet Bulb (°F)
Entering Wet Bulb (°F)
Ent
61
67
73
61
67
73
61
67
73
DB
MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC
CFM (°F)
2250
2500
2750
3000
75
74.9
61.3
83.7
47.5
89.5
33.0
69.3
60.0
77.3
46.1
86.0
31.8
66.3
58.7
73.9
44.8
82.0
30.4
80
72.6
72.6
80.0
58.7
89.0
44.5
70.2
70.2
76.7
57.4
85.3
43.1
67.7
67.7
73.3
56.0
81.4
41.7
85
79.5
79.5
79.8
70.0
88.4
55.8
74.0
74.0
76.6
68.7
84.5
54.4
71.3
71.3
73.1
67.3
80.8
53.1
90
80.5
80.5
80.7
80.7
87.9
67.1
77.8
77.8
77.9
77.9
87.3
68.3
75.0
75.0
75.1
75.1
80.3
64.4
75
73.6
64.9
82.0
49.6
90.9
33.6
70.6
63.6
78.5
48.2
87.2
32.3
67.5
62.2
75.0
46.8
83.1
30.9
80
75.1
75.1
81.3
62.0
90.4
46.3
72.6
72.6
78.0
60.7
86.6
44.9
69.9
69.9
74.5
59.3
82.5
43.5
85
79.2
79.2
81.3
74.6
89.8
58.8
76.5
76.5
78.0
73.2
85.8
57.4
73.7
73.7
74.6
71.8
81.9
56.0
90
83.4
83.4
83.5
83.5
89.3
71.3
80.4
80.4
80.6
80.6
85.4
70.0
77.5
77.5
77.6
77.6
81.5
68.6
75
74.8
68.4
83.1
51.6
92.1
34.2
71.5
67.8
79.6
50.2
88.2
32.9
68.5
65.7
78.9
50.7
84.1
31.5
80
77.3
77.3
82.5
65.2
91.5
48.0
77.5
77.5
79.1
63.8
87.6
46.6
71.8
71.8
75.4
62.4
83.4
45.2
85
81.6
81.6
82.8
79.0
90.9
61.7
78.7
78.7
79.4
77.7
86.8
60.3
75.7
75.7
76.1
74.8
82.8
58.9
90
85.8
85.8
85.9
85.9
90.5
75.4
82.7
82.7
86.1
86.1
86.5
74.0
79.6
79.6
79.7
79.7
82.5
72.6
75
75.7
72.4
84.1
53.5
93.0
34.7
72.8
70.3
80.4
52.1
89.1
33.4
69.5
69.5
76.7
50.7
84.8
32.0
80
79.2
79.2
83.5
68.3
92.4
49.7
76.5
76.5
80.0
66.9
88.4
48.3
73.5
73.5
79.2
68.0
84.2
46.9
85
83.6
83.6
84.1
83.3
91.8
64.5
80.7
80.7
80.9
80.3
87.6
63.1
77.5
77.5
77.6
77.6
83.5
61.8
90
88.0
88.0
88.1
88.1
91.6
79.4
84.8
84.8
84.9
84.9
87.5
78.0
81.5
81.5
81.6
81.6
83.0
77.5
Ambient Temperature (°F)
Ambient Temperature (°F)
115
125
Entering Wet Bulb (°F)
Entering Wet Bulb (°F)
Ent
61
67
73
61
67
73
DB
MBH
SHC
MBH
SHC
MBH
SHC
MBH
SHC
MBH
SHC
MBH
SHC
CFM (°F)
2250
2500
2750
3000
75
63.1
57.2
70.3
43.3
77.9
28.9
59.8
55.8
66.5
41.9
73.8
27.5
80
65.0
65.0
69.7
54.6
77.3
40.3
62.1
62.1
66.0
53.1
73.1
38.9
85
68.5
68.5
69.7
66.0
76.7
51.7
65.5
65.5
66.1
64.0
75.0
52.1
90
72.0
72.0
72.1
72.1
76.2
63.0
68.7
68.7
68.8
68.8
71.9
61.5
75
66.6
63.3
71.3
45.4
78.9
29.5
61.0
58.7
67.4
43.9
74.6
28.0
80
67.1
67.1
70.8
57.8
78.3
42.1
64.0
64.0
67.0
56.4
73.8
40.6
85
70.7
70.7
71.2
69.3
77.6
54.6
67.5
67.5
67.6
67.6
73.2
53.1
90
74.3
74.3
74.4
74.4
77.3
67.2
70.8
70.8
70.9
70.9
72.5
66.5
75
65.1
65.1
72.2
47.3
79.7
30.0
62.1
62.1
68.2
45.8
75.1
28.5
80
68.8
68.8
71.7
61.0
82.1
45.5
65.7
65.7
67.8
59.5
74.5
42.2
85
72.5
72.5
72.6
72.6
78.5
57.5
69.2
69.2
69.3
69.3
73.9
56.0
90
76.2
76.2
76.3
76.3
77.9
72.1
75.2
75.2
72.7
72.7
73.7
69.3
75
66.6
66.6
72.9
49.3
80.4
30.5
63.4
63.4
68.8
47.7
75.8
29.0
80
70.4
70.4
72.5
64.1
79.8
45.4
67.1
67.1
68.2
63.3
75.1
43.9
85
74.2
74.2
74.2
74.2
79.1
60.3
70.7
70.7
70.8
70.8
74.5
58.8
90
77.9
77.9
78.0
78.0
79.0
74.8
74.1
74.1
74.2
74.2
74.3
74.3
Notes:
1. All capacities shown are gross and have not considered indoor fan heat. To obtain net cooling,
subtract indoor fan heat.
2. MBH = Total Gross Capacity, SHC = Sensible Heat Capacity
SSP-PRC024J-EN
31
Performance Data
Table 17.
Gross cooling capacities (kW) TWA0764*D condensing unit with TWE0764*B air handler (SI)
Ambient Temperature (°C)
4248
4672
5097
30
35
40
Entering Wet Bulb (°C)
Entering Wet Bulb (°C)
4248
4672
5097
19
22
16
19
22
16
19
22
kW
SHC
kW
SHC
kW
SHC
kW
SHC
kW
SHC
kW
SHC
kW
SHC
kW
24
22.0
18.0
24.5
13.9
26.2
9.7
20.3
17.6
22.6
13.5
25.2
9.3
19.4
17.2
21.7
13.1
24.0
8.9
27
21.3
21.3
23.4
17.2
26.1
13.0
20.6
20.6
22.5
16.8
25.0
12.6
19.8
19.8
21.5
16.4
23.9
12.2
30
23.3
23.3
23.4
20.5
25.9
16.4
21.7
21.7
22.4
20.1
24.8
15.9
20.9
20.9
21.4
19.7
23.7
15.6
33
23.6
23.6
23.6
23.6
25.8
19.7
22.8
22.8
22.8
22.8
25.6
20.0
22.0
22.0
22.0
22.0
23.5
18.9
24
21.6
19.0
24.0
14.5
26.6
9.9
20.7
18.6
23.0
14.1
25.6
9.5
19.8
18.2
22.0
13.7
24.4
9.1
27
22.0
22.0
23.8
18.2
26.5
13.6
21.3
21.3
22.9
17.8
25.4
13.2
20.5
20.5
21.8
17.4
24.2
12.8
30
23.2
23.2
23.8
21.8
26.3
17.2
22.4
22.4
22.9
21.5
25.1
16.8
21.6
21.6
21.9
21.1
24.0
16.4
33
24.4
24.4
24.5
24.5
26.2
20.9
23.6
23.6
23.6
23.6
25.0
20.5
22.7
22.7
22.7
22.7
23.9
20.1
24
21.9
20.1
24.4
15.1
27.0
10.0
21.0
19.9
23.3
14.7
25.9
9.6
20.1
19.2
23.1
14.8
24.6
9.2
27
22.6
22.6
24.2
19.1
26.8
14.1
22.7
22.7
23.2
18.7
25.7
13.7
21.1
21.1
22.1
18.3
24.4
13.3
30
23.9
23.9
24.3
23.1
26.6
18.1
23.1
23.1
23.3
22.8
25.4
17.7
22.2
22.2
22.3
21.9
24.3
17.3
33
25.1
25.1
25.2
25.2
26.5
22.1
24.3
24.3
25.2
25.2
25.4
21.7
23.3
23.3
23.4
23.4
24.2
21.3
24
22.2
21.2
24.6
15.7
27.3
10.2
21.3
20.6
23.6
15.3
26.1
9.8
20.4
20.4
22.5
14.9
24.9
9.4
27
23.2
23.2
24.5
20.0
27.1
14.6
22.4
22.4
23.5
19.6
25.9
14.2
21.5
21.5
23.2
19.9
24.7
13.7
30
24.5
24.5
24.7
24.4
26.9
18.9
23.6
23.6
23.7
23.5
25.7
18.5
22.7
22.7
22.7
22.7
24.5
18.1
33
25.8
25.8
25.8
25.8
26.8
23.3
24.8
24.8
24.9
24.9
25.6
22.9
23.9
23.9
23.9
23.9
24.3
22.7
Ambient Temperature (°C)
Ambient Temperature (°C)
45
52
Entering Wet Bulb (°C)
Entering Wet Bulb (°C)
Ent
16
Airflow DB
m3/hr (°C) kW SHC
3823
Ambient Temperature (°C)
Entering Wet Bulb (°C)
Ent
16
Airflow DB
m3/hr (°C) kW SHC
3823
Ambient Temperature (°C)
19
22
kW
SHC
kW
16
SHC
kW
SHC
19
SHC
22
kW
SHC
kW
SHC
24
18.5
16.8
20.6
12.7
22.8
8.5
17.5
16.3
19.5
12.3
21.6
8.1
27
19.0
19.0
20.4
16.0
22.6
11.8
18.2
18.2
19.3
15.6
21.4
11.4
30
20.1
20.1
20.4
19.3
22.5
15.1
19.2
19.2
19.4
18.8
22.0
15.3
33
21.1
21.1
21.1
21.1
22.3
18.5
20.1
20.1
20.2
20.2
21.1
18.0
24
19.5
18.5
20.9
13.3
23.1
8.6
17.9
17.2
19.8
12.9
21.9
8.2
27
19.7
19.7
20.8
17.0
22.9
12.3
18.8
18.8
19.6
16.5
21.6
11.9
30
20.7
20.7
20.9
20.3
22.8
16.0
19.8
19.8
19.8
19.8
21.5
15.6
33
21.8
21.8
21.8
21.8
22.7
19.7
20.8
20.8
20.8
20.8
21.3
19.5
24
19.1
19.1
21.1
13.9
23.4
8.8
18.2
18.2
20.0
13.4
22.0
8.3
27
20.2
20.2
21.0
17.9
24.1
13.3
19.2
19.2
19.9
17.4
21.8
12.4
30
21.2
21.2
21.3
21.3
23.0
16.8
20.3
20.3
20.3
20.3
21.7
16.4
33
22.3
22.3
22.4
22.4
22.8
21.1
22.1
22.1
21.3
21.3
21.6
20.3
24
19.5
19.5
21.4
14.4
23.6
8.9
18.6
18.6
20.2
14.0
22.2
8.5
27
20.6
20.6
21.3
18.8
23.4
13.3
19.7
19.7
20.0
18.5
22.0
12.9
30
21.7
21.7
21.8
21.8
23.2
17.7
20.7
20.7
20.7
20.7
21.8
17.2
33
22.8
22.8
22.9
22.9
23.2
21.9
21.7
21.7
21.7
21.7
21.8
21.8
Notes:
1. All capacities shown are gross and have not considered indoor fan heat. To obtain net cooling,
subtract indoor fan heat.
2. kW = Total Gross Capacity, SHC = Sensible Heat Capacity
32
SSP-PRC024J-EN
Performance Data
Table 18.
Gross cooling capacities (MBH) TWA1014*A condensing unit with TWE1014*A air handler (IP)
Ambient Temperature (°F)
Ambient Temperature (°F)
85
95
Ambient Temperature (°F)
105
Entering Wet Bulb (°F)
Entering Wet Bulb (°F)
Entering Wet Bulb (°F)
Ent
61
67
73
61
67
73
61
67
73
DB
CFM (°F) MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC
3025
3350
3675
4000
75
98.6
84.4 109.4 64.9 121.1 44.7
94.5
82.5 104.7 63.0 115.7 42.8
90.1
80.4
99.7
61.0 110.0 40.8
80
99.7
99.7 109.1 80.7 120.7 60.7
96.2
96.2 104.4 78.8 115.3 58.8
92.5
92.5
99.4
76.8 109.7 56.8
85
105.1 105.1 109.3 96.5 120.4 76.6 101.5 101.5 104.6 94.6 115.0 74.7
97.5
97.5
99.7
92.5 109.3 72.7
90
110.6 110.6 110.8 110.8 120.1 92.5 106.8 106.8 107.0 107.0 114.8 90.6 102.6 102.6 102.8 102.8 109.2 88.5
75
100.5 89.3 111.1 67.7 122.8 45.5
96.3
87.3 106.3 65.8 117.3 43.6
91.7
85.3 101.1 63.8 111.4 41.6
80
103.0 103.0 110.8 85.2 122.4 63.2
99.3
99.3 106.0 83.3 116.9 61.2
95.3
95.3 100.9 81.2 111.0 59.2
85
108.7 108.7 111.3 102.7 122.1 80.8 104.8 104.8 106.6 100.8 116.5 78.8 100.6 100.6 101.6 98.7 110.7 76.8
90
114.4 114.4 114.6 114.6 122.0 98.3 110.3 110.3 110.5 110.5 116.5 96.3 105.9 105.9 106.0 106.0 110.7 94.3
75
102.1 94.1 112.6 70.5 124.2 46.3
92.2 107.6 68.6 118.5 44.3
93.2
90.1 102.3 66.6 112.6 42.3
80
105.9 105.9 112.4 89.6 123.8 65.6 102.0 102.0 107.4 87.7 118.2 63.6
97.8
97.8 102.2 85.6 112.2 61.6
85
111.8 111.8 113.2 108.8 123.5 84.8 107.7 107.7 108.4 106.9 117.8 82.9 103.2 103.2 103.5 103.5 111.9 80.9
90
117.7 117.7 117.9 117.9 123.6 103.9 113.3 113.3 113.5 113.5 118.0 102.0 108.7 108.7 108.8 108.8 112.1 99.9
75
103.6 98.8 113.8 73.3 125.4 47.0
80
108.4 108.4 113.7 93.9 125.0 68.0 104.4 104.4 108.7 91.9 119.2 66.0 100.0 100.0 103.3 89.9 113.1 64.0
85
114.5 114.5 115.0 114.9 124.7 88.8 110.2 110.2 110.3 110.3 118.9 86.9 105.6 105.6 105.7 105.7 112.9 84.8
90
120.6 120.6 120.7 120.7 125.0 109.5 116.0 116.0 116.2 116.2 119.3 107.5 111.1 111.1 111.2 111.2 113.3 105.4
Ambient Temperature (°F)
97.8
98.6
98.6 108.7 71.3 119.6 45.1
94.5
94.5 103.2 69.3 113.5 43.0
Ambient Temperature (°F)
115
125
Entering Wet Bulb (°F)
Entering Wet Bulb (°F)
Ent
61
67
73
61
67
73
DB
MBH
SHC
MBH
SHC
MBH
SHC
MBH
SHC
MBH
SHC
MBH
SHC
CFM (°F)
3025
3350
75
85.4
78.3
94.3
58.8 104.0 38.7
80.2
76.0
88.4
56.6
97.4
36.5
80
88.3
88.3
94.0
74.6 103.6 54.7
83.7
83.7
88.2
72.3
97.1
52.4
85
93.2
93.2
94.5
90.4 103.3 70.6
88.4
88.4
88.9
88.2
96.7
68.3
90
98.1
98.1
98.2
98.2 103.2 86.4
93.0
93.0
93.2
93.2
96.7
84.1
75
86.9
83.1
95.5
61.7 105.2 39.5
81.4
81.4
89.5
59.4
98.5
37.2
80
91.0
91.0
95.4
79.1 104.8 57.1
86.2
86.2
89.4
76.7
98.1
54.9
85
96.0
96.0
96.4
96.4 104.5 74.7
90.9
90.9
91.1
91.1
97.8
72.5
101.1 101.1 101.2 101.2 104.6 92.1
95.7
95.7
95.8
95.8
98.1
89.8
90
3675
75
88.1
88.1
96.6
64.4 106.2 40.2
83.3
83.3
90.4
62.1
99.4
37.9
80
93.3
93.3
96.6
83.4 105.8 59.5
88.2
88.2
90.5
81.0
99.0
57.2
85
98.5
98.5
98.6
98.6 105.6 78.8
93.1
93.1
93.2
93.2
98.8
76.4
103.6 103.6 103.7 103.7 105.9 97.7
98.0
98.0
98.2
98.2
99.3
95.5
90
75
4000
80
89.9
89.9
97.5
67.1 107.1 40.9
85.0
85.0
91.2
64.8 100.1 38.6
95.2
95.2
97.6
87.6 106.7 61.8
90.0
90.0
91.5
85.3
99.8
59.6
85
100.6 100.6 100.7 100.7 106.5 82.6
95.0
95.0
95.1
95.1
99.6
80.2
90
105.8 105.8 106.0 106.0 107.1 103.3 100.1 100.1 100.2 100.2 100.6 100.6
Notes:
1. All capacities shown are gross and have not considered indoor fan heat. To obtain net cooling,
subtract indoor fan heat.
2. MBH = Total Gross Capacity, SHC = Sensible Heat Capacity
SSP-PRC024J-EN
33
Performance Data
Table 19.
Gross cooling capacities (kW) TWA1014*A condensing unit with TWE1014*A air handler (SI)
Ambient Temperature (°C)
Ambient Temperature (°C)
30
35
40
Entering Wet Bulb (°C)
Entering Wet Bulb (°C)
Entering Wet Bulb (°C)
Ent
16
Airflow DB
m3/hr (°C) kW SHC
5148
5692
6252
6796
19
22
6252
6796
22
16
19
22
SHC
kW
SHC
kW
SHC
kW
SHC
kW
SHC
kW
SHC
kW
SHC
kW
SHC
24
28.9
24.7
32.1
19.0
35.5
13.1
27.7
24.2
30.7
18.5
33.9
12.5
26.4
23.6
29.2
17.9
32.3
12.0
27
29.2
29.2
32.0
23.6
35.4
17.8
28.2
28.2
30.6
23.1
33.8
17.2
27.1
27.1
29.1
22.5
32.1
16.6
30
30.8
30.8
32.0
28.3
35.3
22.4
29.7
29.7
30.7
27.7
33.7
21.9
28.6
28.6
29.2
27.1
32.0
21.3
33
32.4
32.4
32.5
32.5
35.2
27.1
31.3
31.3
31.3
31.3
33.6
26.5
30.1
30.1
30.1
30.1
32.0
25.9
24
29.5
26.2
32.6
19.9
36.0
13.3
28.2
25.6
31.1
19.3
34.4
12.8
26.9
25.0
29.6
18.7
32.7
12.2
27
30.2
30.2
32.5
25.0
35.9
18.5
29.1
29.1
31.1
24.4
34.3
17.9
27.9
27.9
29.6
23.8
32.5
17.4
30
31.8
31.8
32.6
30.1
35.8
23.7
30.7
30.7
31.2
29.5
34.2
23.1
29.5
29.5
29.8
28.9
32.4
22.5
33
33.5
33.5
33.6
33.6
35.7
28.8
32.3
32.3
32.4
32.4
34.1
28.2
31.0
31.0
31.1
31.1
32.5
27.6
24
29.9
27.6
33.0
20.7
36.4
13.6
28.7
27.0
31.5
20.1
34.7
13.0
27.3
26.4
30.0
19.5
33.0
12.4
27
31.0
31.0
32.9
26.3
36.3
19.2
29.9
29.9
31.5
25.7
34.6
18.7
28.7
28.7
29.9
25.1
32.9
18.1
30
32.8
32.8
33.2
31.9
36.2
24.9
31.6
31.6
31.8
31.3
34.5
24.3
30.3
30.3
30.3
30.3
32.8
23.7
33
34.5
34.5
34.5
34.5
36.2
30.5
33.2
33.2
33.3
33.3
34.6
29.9
31.8
31.8
31.9
31.9
32.9
29.3
24
30.4
29.0
33.3
21.5
36.8
13.8
28.9
28.9
31.8
20.9
35.0
13.2
27.7
27.7
30.3
20.3
33.3
12.6
27
31.8
31.8
33.3
27.5
36.6
19.9
30.6
30.6
31.8
26.9
34.9
19.3
29.3
29.3
30.3
26.3
33.2
18.7
30
33.6
33.6
33.7
33.7
36.6
26.0
32.3
32.3
32.3
32.3
34.9
25.5
30.9
30.9
31.0
31.0
33.1
24.9
33
35.3
35.3
35.4
35.4
36.6
32.1
34.0
34.0
34.0
34.0
35.0
31.5
32.6
32.6
32.6
32.6
33.2
30.9
Ambient Temperature (°C)
45
52
Entering Wet Bulb (°C)
Entering Wet Bulb (°C)
Ent
16
Airflow DB
3
kW
SHC
m /hr (°C)
5692
19
kW
Ambient Temperature (°C)
5148
16
Ambient Temperature (°C)
19
22
16
19
22
kW
SHC
kW
SHC
kW
SHC
kW
SHC
kW
SHC
24
25.0
22.9
27.6
17.2
30.5
11.4
23.5
22.3
25.9
16.6
28.6
10.7
27
25.9
25.9
27.6
21.9
30.4
16.0
24.5
24.5
25.8
21.2
28.4
15.4
30
27.3
27.3
27.7
26.5
30.3
20.7
25.9
25.9
26.0
25.8
28.3
20.0
33
28.7
28.7
28.8
28.8
30.2
25.3
27.3
27.3
27.3
27.3
28.3
24.7
24
25.5
24.4
28.0
18.1
30.8
11.6
23.8
23.8
26.2
17.4
28.9
10.9
27
26.7
26.7
28.0
23.2
30.7
16.7
25.2
25.2
26.2
22.5
28.8
16.1
30
28.1
28.1
28.2
28.2
30.6
21.9
26.7
26.7
26.7
26.7
28.7
21.2
33
29.6
29.6
29.7
29.7
30.7
27.0
28.0
28.0
28.1
28.1
28.7
26.3
24
25.8
25.8
28.3
18.9
31.1
11.8
24.4
24.4
26.5
18.2
29.1
11.1
27
27.3
27.3
28.3
24.4
31.0
17.4
25.9
25.9
26.5
23.7
29.0
16.8
30
28.9
28.9
28.9
28.9
30.9
23.1
27.3
27.3
27.3
27.3
28.9
22.4
33
30.4
30.4
30.4
30.4
31.0
28.6
28.7
28.7
28.8
28.8
29.1
28.0
24
26.4
26.4
28.6
19.7
31.4
12.0
24.9
24.9
26.7
19.0
29.3
11.3
27
27.9
27.9
28.6
25.7
31.3
18.1
26.4
26.4
26.8
25.0
29.2
17.5
30
29.5
29.5
29.5
29.5
31.2
24.2
27.8
27.8
27.9
27.9
29.2
23.5
33
31.0
31.0
31.1
31.1
31.4
30.3
29.3
29.3
29.4
29.4
29.5
29.5
Notes:
1. All capacities shown are gross and have not considered indoor fan heat. To obtain net cooling,
subtract indoor fan heat.
2. kW = Total Gross Capacity, SHC = Sensible Heat Capacity
34
SSP-PRC024J-EN
Performance Data
Table 20.
Gross cooling capacities (MBH) TWA1014*D condensing unit with TWE1014*B air handler (IP)
Ambient Temperature (°F)
Ambient Temperature (°F)
Ambient Temperature (°F)
85
95
105
Entering Wet Bulb (°F)
Entering Wet Bulb (°F)
Entering Wet Bulb (°F)
Ent
61
67
73
61
67
73
61
67
73
DB
MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC
CFM (°F)
3025
75
95.8
83.2 106.0 63.5 117.0 43.3
91.1
81.0 100.7 61.4 111.1 41.2
86.2
78.8
95.3
59.2 105.1 39.1
80
97.5
97.5 105.8 79.4 116.8 59.3
93.4
93.4 100.5 77.3 110.8 57.2
89.2
89.2
95.1
75.1 104.9 55.1
85
102.8 102.8 106.2 95.3 116.5 75.3
98.6
98.6 100.9 93.2 110.6 73.2
94.3
94.3
95.7
91.1 104.7 71.1
90
108.2 108.2 108.4 108.4 116.5 91.3 103.8 103.8 104.0 104.0 110.6 89.2
99.3
99.3
99.5
99.5 104.7 87.1
75
3350
88.1 107.6 66.4 118.6 44.0
92.7
85.9 102.1 64.2 112.5 41.9
87.6
83.8
96.5
62.1 106.4 39.8
80
100.6 100.6 107.5 83.9 118.3 61.8
96.3
96.3 102.0 81.8 112.2 59.6
91.9
91.9
96.5
79.6 106.2 57.6
85
106.1 106.1 108.1 101.6 118.1 79.4 101.7 101.7 102.8 99.5 112.0 77.3
97.1
97.1
97.6
96.2 105.9 75.2
90
111.7 111.7 111.9 111.9 118.2 97.0 107.1 107.1 107.2 107.2 112.2 94.9 102.3 102.3 102.5 102.5 106.2 92.8
75
3675
4000
97.6
92.9 108.9 69.2 119.9 44.8
94.1
90.6 103.3 67.0 113.6 42.7
88.9
88.9
97.6
64.8 107.4 40.6
80
103.3 103.3 108.9 88.4 119.6 64.2
99.1
98.8
98.8 103.3 86.2 113.4 62.0
94.2
94.2
97.7
84.0 107.2 60.0
85
109.0 109.0 109.9 107.7 119.4 83.5 104.3 104.3 104.8 103.7 113.1 81.4
99.6
99.6
99.7
99.7 107.0 79.3
90
114.8 114.8 115.0 115.0 119.7 102.7 109.9 109.9 110.1 110.1 113.5 100.6 105.0 105.0 105.1 105.1 107.5 98.5
75
100.5 97.4 110.0 71.9 120.9 45.5
95.4 104.3 69.7 114.6 43.4
90.8
90.8
98.5
67.5 108.3 41.3
80
105.7 105.7 110.1 92.7 120.7 66.5 101.0 101.0 104.4 90.5 114.3 64.4
96.3
96.3
98.8
88.3 108.0 62.3
85
111.6 111.6 111.9 111.5 120.5 87.5 106.7 106.7 106.8 106.8 114.2 85.3 101.8 101.8 101.9 101.9 107.9 83.2
90
117.5 117.5 117.6 117.6 121.0 108.3 112.4 112.4 112.5 112.5 114.8 106.2 107.2 107.2 107.4 107.4 108.5 103.9
95.4
Ambient Temperature (°F)
Ambient Temperature (°F)
115
125
Entering Wet Bulb (°F)
Entering Wet Bulb (°F)
Ent
61
67
73
61
67
73
DB
MBH
SHC
MBH
SHC
MBH
SHC
MBH
SHC
MBH
SHC
MBH
SHC
CFM (°F)
3025
3350
3675
4000
75
80.9
76.4
89.5
57.0
98.9
36.9
75.2
73.0
83.0
54.5
92.0
34.6
80
84.7
84.7
89.4
72.9
98.7
53.0
79.5
79.5
83.0
70.4
91.7
50.6
85
89.6
89.6
90.2
88.6
98.5
69.0
84.3
84.3
84.5
84.5
91.5
66.7
90
94.5
94.5
94.7
94.7
98.6
84.9
89.1
89.1
89.2
89.2
91.8
82.6
75
82.1
82.1
90.6
59.8 100.0 37.7
76.9
76.9
84.1
57.3
92.9
35.3
80
87.2
87.2
90.7
77.3
99.8
55.4
81.8
81.8
84.2
74.8
92.7
53.1
85
92.2
92.2
92.4
92.4
99.6
73.1
86.7
86.7
86.9
86.9
92.6
70.7
90
97.3
97.3
97.5
97.5 100.0 90.7
91.6
91.6
91.7
91.7
93.0
88.3
75
84.1
84.1
91.6
62.5 100.9 38.4
78.7
78.7
84.9
60.1
93.7
36.1
80
89.3
89.3
91.8
81.7 100.7 57.8
83.8
83.8
85.3
79.2
93.5
55.5
85
94.5
94.5
94.7
94.7 100.6 77.1
88.8
88.8
88.9
88.9
93.5
74.7
90
99.7
99.7
99.8
99.8 101.0 96.3
93.8
93.8
93.9
93.9
94.0
94.0
75
85.8
85.8
92.4
65.2 101.7 39.1
80.3
80.3
85.6
62.7
94.4
36.7
80
91.2
91.2
92.8
86.0 101.5 60.1
85.5
85.5
86.2
83.0
94.2
57.8
85
96.5
96.5
96.6
96.6 101.4 81.0
90.6
90.6
90.7
90.7
94.2
78.6
101.8 101.8 101.9 101.9 102.0 102.0 95.7
95.7
95.8
95.8
95.9
95.9
90
Notes:
1. All capacities shown are gross and have not considered indoor fan heat. To obtain net cooling,
subtract indoor fan heat.
2. MBH = Total Gross Capacity, SHC = Sensible Heat Capacity
SSP-PRC024J-EN
35
Performance Data
Table 21.
Gross cooling capacities (kW) TWA1014*D condensing unit with TWE1014*B air handler (SI)
Ambient Temperature (°C)
5692
6252
6796
30
35
40
Entering Wet Bulb (°C)
Entering Wet Bulb (°C)
5692
6252
6796
19
22
16
19
22
16
19
22
kW
SHC
kW
SHC
kW
SHC
kW
SHC
kW
SHC
kW
SHC
kW
SHC
kW
SHC
24
28.1
24.4
31.1
18.6
34.3
12.7
26.7
23.7
29.5
18.0
32.5
12.1
25.3
23.1
27.9
17.4
30.8
11.5
27
28.6
28.6
31.0
23.3
34.2
17.4
27.4
27.4
29.5
22.7
32.5
16.8
26.1
26.1
27.9
22.0
30.7
16.2
30
30.1
30.1
31.1
27.9
34.2
22.1
28.9
28.9
29.6
27.3
32.4
21.4
27.6
27.6
28.0
26.7
30.7
20.8
33
31.7
31.7
31.8
31.8
34.1
26.7
30.4
30.4
30.5
30.5
32.4
26.1
29.1
29.1
29.2
29.2
30.7
25.5
24
28.6
25.8
31.5
19.5
34.8
12.9
27.2
25.2
29.9
18.8
33.0
12.3
25.7
24.6
28.3
18.2
31.2
11.7
27
29.5
29.5
31.5
24.6
34.7
18.1
28.2
28.2
29.9
24.0
32.9
17.5
26.9
26.9
28.3
23.3
31.1
16.9
30
31.1
31.1
31.7
29.8
34.6
23.3
29.8
29.8
30.1
29.1
32.8
22.7
28.5
28.5
28.6
28.2
31.1
22.1
33
32.7
32.7
32.8
32.8
34.6
28.4
31.4
31.4
31.4
31.4
32.9
27.8
30.0
30.0
30.0
30.0
31.1
27.2
24
29.1
27.2
31.9
20.3
35.1
13.1
27.6
26.6
30.3
19.6
33.3
12.5
26.1
26.1
28.6
19.0
31.5
11.9
27
30.3
30.3
31.9
25.9
35.1
18.8
29.0
29.0
30.3
25.3
33.2
18.2
27.6
27.6
28.6
24.6
31.4
17.6
30
32.0
32.0
32.2
31.6
35.0
24.5
30.6
30.6
30.7
30.4
33.2
23.8
29.2
29.2
29.2
29.2
31.4
23.2
33
33.6
33.6
33.7
33.7
35.1
30.1
32.2
32.2
32.3
32.3
33.3
29.5
30.8
30.8
30.8
30.8
31.5
28.9
24
29.4
28.5
32.2
21.1
35.4
13.3
27.9
27.9
30.6
20.4
33.6
12.7
26.6
26.6
28.9
19.8
31.7
12.1
27
31.0
31.0
32.3
27.2
35.4
19.5
29.6
29.6
30.6
26.5
33.5
18.9
28.2
28.2
28.9
25.9
31.7
18.3
30
32.7
32.7
32.8
32.7
35.3
25.6
31.3
31.3
31.3
31.3
33.5
25.0
29.8
29.8
29.9
29.9
31.6
24.4
33
34.4
34.4
34.5
34.5
35.5
31.7
32.9
32.9
33.0
33.0
33.6
31.1
31.4
31.4
31.5
31.5
31.8
30.4
Ambient Temperature (°C)
Ambient Temperature (°C)
45
52
Entering Wet Bulb (°C)
Entering Wet Bulb (°C)
Ent
16
Airflow DB
m3/hr (°C) kW SHC
5148
Ambient Temperature (°C)
Entering Wet Bulb (°C)
Ent
16
Airflow DB
m3/hr (°C) kW SHC
5148
Ambient Temperature (°C)
19
kW
SHC
22
kW
SHC
16
kW
SHC
19
22
kW
SHC
kW
SHC
24
23.7
22.4
26.2
16.7
29.0
10.8
22.0
21.4
24.3
16.0
27.0
10.1
27
24.8
24.8
26.2
21.4
28.9
15.5
23.3
23.3
24.3
20.6
26.9
14.8
30
26.3
26.3
26.4
26.0
28.9
20.2
24.7
24.7
24.8
24.8
26.8
19.5
33
27.7
27.7
27.7
27.7
28.9
24.9
26.1
26.1
26.1
26.1
26.9
24.2
24
24.1
24.1
26.6
17.5
29.3
11.0
22.5
22.5
24.6
16.8
27.2
10.4
27
25.5
25.5
26.6
22.7
29.2
16.2
24.0
24.0
24.7
21.9
27.2
15.6
30
27.0
27.0
27.1
27.1
29.2
21.4
25.4
25.4
25.5
25.5
27.1
20.7
33
28.5
28.5
28.6
28.6
29.3
26.6
26.9
26.9
26.9
26.9
27.2
25.9
24
24.6
24.6
26.8
18.3
29.6
11.3
23.1
23.1
24.9
17.6
27.5
10.6
27
26.2
26.2
26.9
23.9
29.5
16.9
24.6
24.6
25.0
23.2
27.4
16.3
30
27.7
27.7
27.7
27.7
29.5
22.6
26.0
26.0
26.1
26.1
27.4
21.9
33
29.2
29.2
29.3
29.3
29.6
28.2
27.5
27.5
27.5
27.5
27.6
27.6
24
25.2
25.2
27.1
19.1
29.8
11.5
23.5
23.5
25.1
18.4
27.7
10.8
27
26.7
26.7
27.2
25.2
29.7
17.6
25.1
25.1
25.3
24.3
27.6
16.9
30
28.3
28.3
28.3
28.3
29.7
23.7
26.6
26.6
26.6
26.6
27.6
23.0
33
29.8
29.8
29.9
29.9
29.9
29.9
28.0
28.0
28.1
28.1
28.1
28.1
Notes:
1. All capacities shown are gross and have not considered indoor fan heat. To obtain net cooling,
subtract indoor fan heat.
2. kW = Total Gross Capacity, SHC = Sensible Heat Capacity
36
SSP-PRC024J-EN
Performance Data
Table 22.
Gross cooling capacities (MBH) TWA1564*D condensing unit with TWE1564*B air handler (IP)
Ambient Temperature (°F)
Ambient Temperature (°F)
85
95
Ambient Temperature (°F)
105
Entering Wet Bulb (°F)
Entering Wet Bulb (°F)
Entering Wet Bulb (°F)
Ent
61
67
73
61
67
73
61
67
73
DB
CFM (°F) MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC
4500
5000
5500
6000
75
146.8 127.5 163.9 97.9 182.5 67.4 141.1 124.9 157.7 95.4 175.6 65.0 135.0 122.2 150.9 92.7 168.1 62.3
80
146.8 146.8 163.9 122.4 182.5 92.1 141.1 141.1 157.6 119.9 175.6 89.7 135.0 135.0 150.9 117.2 168.0 87.1
85
146.8 146.8 163.9 146.8 182.4 116.8 141.1 141.1 157.7 144.2 175.5 114.3 135.0 135.0 150.9 141.5 168.0 111.7
90
146.8 146.8 164.0 164.0 182.4 141.3 141.1 141.1 157.7 157.7 175.5 138.9 135.0 135.0 150.9 150.9 168.0 136.2
75
149.2 135.2 166.4 102.4 185.1 68.7 143.4 132.6 160.0 99.9 178.0 66.2 137.0 129.8 153.0 97.2 170.3 63.6
80
149.2 149.2 166.4 129.6 185.1 96.1 143.4 143.4 160.0 127.0 178.0 93.6 137.0 137.0 153.0 124.3 170.2 90.9
85
149.2 149.2 166.4 156.5 185.1 123.3 143.3 143.3 160.0 153.9 178.0 120.9 137.0 137.0 153.0 151.2 170.2 118.2
90
149.2 149.2 166.5 166.5 185.0 150.5 143.4 143.4 160.0 160.0 178.0 148.0 137.0 137.0 153.0 153.0 170.2 145.4
75
151.2 142.7 168.5 106.9 187.3 69.9 145.2 140.1 161.9 104.3 180.0 67.4 138.7 137.3 154.8 101.6 172.1 64.7
80
151.2 151.2 168.5 136.6 187.2 99.9 145.2 145.2 161.9 134.0 180.0 97.4 138.7 138.7 154.8 131.2 172.1 94.7
85
151.2 151.2 168.5 166.0 187.2 129.8 145.2 145.2 161.9 161.9 179.9 127.3 138.7 138.7 154.8 154.8 172.1 124.7
90
151.2 151.2 168.5 168.5 187.2 159.5 145.2 145.2 161.9 161.9 180.0 157.0 138.7 138.7 154.8 154.8 172.1 154.4
75
152.9 150.1 170.3 111.2 189.1 71.0 146.7 146.5 163.5 108.6 181.7 68.6 140.1 140.1 156.3 105.9 173.7 65.9
80
152.9 152.9 170.3 143.4 189.0 103.7 146.7 146.7 163.5 140.9 181.6 101.2 140.1 140.1 156.3 138.1 173.6 98.5
85
152.8 152.8 170.3 170.3 189.0 136.2 146.7 146.7 163.5 163.5 181.6 133.7 140.1 140.1 156.3 156.3 173.6 131.0
90
152.8 152.8 170.2 170.2 189.0 168.4 146.7 146.7 163.5 163.5 181.6 165.9 140.1 140.1 156.2 156.2 173.6 163.2
Ambient Temperature (°F)
Ambient Temperature (°F)
115
125
Entering Wet Bulb (°F)
Entering Wet Bulb (°F)
Ent
61
67
73
61
67
73
DB
MBH
SHC
MBH
SHC
MBH
SHC
MBH
SHC
MBH
SHC
MBH
SHC
CFM (°F)
4500
5000
5500
6000
75
128.5 119.3 143.7 89.9 160.1 59.6 121.7 116.3 136.1 87.0 151.6 56.6
80
128.6 128.6 143.7 114.4 160.1 84.3 121.7 121.7 136.1 111.4 151.5 81.4
85
128.5 128.5 143.7 138.7 160.1 108.9 121.7 121.7 136.1 134.8 151.5 106.0
90
128.5 128.5 143.8 143.8 160.1 133.5 121.7 121.7 136.1 136.1 151.5 130.5
75
130.4 126.9 145.6 94.4 162.1 60.8 123.4 122.6 137.8 91.4 153.4 57.8
80
130.4 130.4 145.7 121.5 162.1 88.2 123.4 123.4 137.8 118.4 153.3 85.2
85
130.4 130.4 145.7 145.7 162.1 115.4 123.4 123.4 137.8 137.8 153.3 112.5
90
130.4 130.4 145.7 145.7 162.1 142.6 123.4 123.4 137.8 137.8 153.3 139.6
75
131.9 131.9 147.2 98.7 163.8 61.9 124.7 124.7 139.2 95.7 154.9 59.0
80
131.9 131.9 147.2 128.4 163.7 92.0 124.7 124.7 139.2 125.3 154.8 89.0
85
131.9 131.9 147.3 147.3 163.7 121.9 124.7 124.7 139.2 139.2 154.8 118.9
90
131.9 131.9 147.2 147.2 163.7 151.5 124.7 124.7 139.2 139.2 154.8 148.6
75
133.2 133.2 148.6 103.0 165.2 63.1 125.9 125.9 140.4 100.0 156.1 60.1
80
133.2 133.2 148.6 135.2 165.1 95.7 125.9 125.9 140.4 132.2 156.0 92.7
85
133.2 133.2 148.6 148.6 165.1 128.2 125.9 125.9 140.4 140.4 156.0 125.2
90
133.2 133.2 148.6 148.6 165.1 160.4 125.8 125.8 140.4 140.4 156.0 155.2
Notes:
1. All capacities shown are gross and have not considered indoor fan heat. To obtain net cooling,
subtract indoor fan heat.
2. MBH = Total Gross Capacity, SHC = Sensible Heat Capacity
SSP-PRC024J-EN
37
Performance Data
Table 23.
Gross cooling capacities (kW) TWA1564*D heat pump with TWE1564*B air handler (SI)
Ambient Temperature (°C)
Ambient Temperature (°C)
30
35
40
Entering Wet Bulb (°C)
Entering Wet Bulb (°C)
Entering Wet Bulb (°C)
Ent
16
Airflow DB
m3/hr (°C) kW SHC
7646
8495
9345
10194
19
22
9345
10194
22
16
19
22
SHC
kW
SHC
kW
SHC
kW
SHC
kW
SHC
kW
SHC
kW
SHC
kW
SHC
24
43.1
37.5
48.2
28.8
53.6
19.8
41.5
36.8
46.3
28.1
51.5
19.1
39.6
35.9
44.3
27.3
49.3
18.3
27
43.1
43.1
48.1
36.0
53.6
27.1
41.5
41.5
46.3
35.3
51.5
26.3
39.6
39.6
44.3
34.5
49.3
25.6
30
43.1
43.1
48.2
43.2
53.6
34.3
41.5
41.5
46.3
42.4
51.5
33.6
39.6
39.6
44.3
41.6
49.3
32.8
33
43.1
43.1
48.2
48.2
53.5
41.6
41.5
41.5
46.3
46.3
51.5
40.8
39.6
39.6
44.3
44.3
49.3
40.1
24
43.8
39.8
48.9
30.1
54.3
20.2
42.1
39.0
47.0
29.4
52.2
19.4
40.2
38.2
44.9
28.6
49.9
18.6
27
43.8
43.8
48.9
38.1
54.3
28.2
42.1
42.1
47.0
37.4
52.2
27.5
40.2
40.2
44.9
36.6
49.9
26.7
30
43.8
43.8
48.9
46.1
54.3
36.3
42.1
42.1
47.0
45.3
52.2
35.5
40.2
40.2
44.9
44.4
49.9
34.8
33
43.8
43.8
48.9
48.9
54.3
44.3
42.1
42.1
47.0
47.0
52.2
43.5
40.2
40.2
44.9
44.9
49.9
42.7
24
44.4
42.0
49.5
31.4
55.0
20.5
42.6
41.2
47.5
30.7
52.8
19.8
40.7
40.3
45.4
29.9
50.5
19.0
27
44.4
44.4
49.5
40.2
54.9
29.4
42.6
42.6
47.5
39.4
52.8
28.6
40.7
40.7
45.4
38.6
50.4
27.8
30
44.4
44.4
49.5
48.9
54.9
38.2
42.6
42.6
47.5
47.5
52.8
37.4
40.7
40.7
45.4
45.4
50.4
36.6
33
44.4
44.4
49.5
49.5
54.9
46.9
42.6
42.6
47.5
47.5
52.8
46.2
40.7
40.7
45.4
45.4
50.4
45.4
24
44.9
44.2
50.0
32.7
55.5
20.9
43.1
43.1
48.0
31.9
53.3
20.1
41.1
41.1
45.8
31.1
50.9
19.3
27
44.9
44.9
50.0
42.2
55.5
30.5
43.1
43.1
48.0
41.4
53.3
29.7
41.1
41.1
45.8
40.6
50.9
28.9
30
44.9
44.9
50.0
50.0
55.5
40.0
43.1
43.1
48.0
48.0
53.2
39.3
41.1
41.1
45.8
45.8
50.9
38.5
33
44.9
44.9
50.0
50.0
55.5
49.6
43.1
43.1
48.0
48.0
53.2
48.8
41.1
41.1
45.8
45.8
50.9
48.0
Ambient Temperature (°C)
45
52
Entering Wet Bulb (°C)
Entering Wet Bulb (°C)
Ent
16
Airflow DB
3
kW
SHC
m /hr (°C)
8495
19
kW
Ambient Temperature (°C)
7646
16
Ambient Temperature (°C)
19
22
16
19
22
kW
SHC
kW
SHC
kW
SHC
kW
SHC
kW
SHC
24
37.7
35.1
42.2
26.4
46.9
17.5
35.7
34.2
39.9
25.6
44.4
16.6
27
37.7
37.7
42.2
33.7
46.9
24.8
35.7
35.7
39.9
32.8
44.4
23.9
30
37.7
37.7
42.2
40.8
46.9
32.0
35.7
35.7
39.9
39.6
44.4
31.2
33
37.7
37.7
42.2
42.2
46.9
39.2
35.7
35.7
39.9
39.9
44.4
38.4
24
38.3
37.3
42.7
27.7
47.5
17.8
36.2
36.0
40.4
26.9
44.9
17.0
27
38.3
38.3
42.7
35.7
47.5
25.9
36.2
36.2
40.4
34.8
44.9
25.0
30
38.3
38.3
42.7
42.7
47.5
33.9
36.2
36.2
40.4
40.4
44.9
33.1
33
38.3
38.3
42.7
42.7
47.5
41.9
36.2
36.2
40.4
40.4
44.9
41.1
24
38.7
38.7
43.2
29.0
48.0
18.2
36.6
36.6
40.8
28.1
45.4
17.3
27
38.7
38.7
43.2
37.8
48.0
27.0
36.6
36.6
40.8
36.9
45.3
26.1
30
38.7
38.7
43.2
43.2
48.0
35.8
36.6
36.6
40.8
40.8
45.3
35.0
33
38.7
38.7
43.2
43.2
48.0
44.6
36.6
36.6
40.8
40.8
45.3
43.7
24
39.1
39.1
43.6
30.3
48.4
18.5
36.9
36.9
41.2
29.4
45.7
17.6
27
39.1
39.1
43.6
39.8
48.4
28.1
36.9
36.9
41.2
38.9
45.7
27.2
30
39.1
39.1
43.6
43.6
48.4
37.7
36.9
36.9
41.2
41.2
45.7
36.8
33
39.1
39.1
43.6
43.6
48.4
47.2
36.9
36.9
41.2
41.2
45.7
45.5
Notes:
1. All capacities shown are gross and have not considered indoor fan heat. To obtain net cooling,
subtract indoor fan heat.
2. kW = Total Gross Capacity, SHC = Sensible Heat Capacity
38
SSP-PRC024J-EN
Performance Data
Table 24.
Gross cooling capacities (MBH) TWA2014*D heat pump with TWE2014*B air handler (IP)
Ambient Temperature (°F)
Ambient Temperature (°F)
85
95
Ambient Temperature (°F)
105
Entering Wet Bulb (°F)
Entering Wet Bulb (°F)
Entering Wet Bulb (°F)
Ent
61
67
73
61
67
73
61
67
73
DB
CFM (°F) MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC
6000
6680
7350
8030
75
201.8 168.5 224.9 131.1 250.0 92.3 195.2 165.3 217.5 128.1 241.7 89.3 187.5 161.8 208.9 124.6 232.2 85.8
80
202.0 198.8 224.9 162.2 249.9 123.5 195.3 195.0 217.5 159.1 241.6 120.5 187.7 187.7 209.0 155.5 232.1 117.1
85
202.1 202.1 225.2 192.6 250.0 154.7 195.4 195.4 217.7 189.5 241.7 151.7 187.8 187.8 209.2 185.9 232.2 148.3
90
202.2 202.2 225.3 223.0 250.0 185.7 195.5 195.5 217.9 217.9 241.8 182.6 187.8 187.8 209.3 209.3 232.3 179.1
75
205.4 177.5 228.6 136.6 253.8 93.9 198.4 174.4 220.9 133.5 245.3 90.8 190.6 170.8 212.1 130.0 235.5 87.4
80
205.5 205.5 228.7 170.6 253.7 128.2 198.6 198.6 221.0 167.4 245.2 125.2 190.7 190.7 212.2 163.8 235.4 121.7
85
205.6 205.6 228.9 204.0 253.8 162.5 198.7 198.7 221.2 200.9 245.2 159.4 190.8 190.8 212.4 197.3 235.5 156.0
90
205.7 205.7 229.0 229.0 253.9 196.4 198.7 198.7 221.3 221.3 245.3 193.3 190.9 190.9 212.5 212.5 235.6 189.8
75
208.3 186.3 231.7 141.8 257.0 95.4 201.2 183.1 223.8 138.7 248.2 92.3 193.1 179.5 214.7 135.1 238.2 88.8
80
208.4 208.4 231.8 178.7 256.9 132.8 201.3 201.3 223.9 175.5 248.1 129.7 193.3 193.3 214.9 171.9 238.1 126.2
85
208.5 208.5 232.0 215.1 257.0 170.1 201.4 201.4 224.1 211.9 248.2 167.0 193.3 193.3 215.1 208.3 238.2 163.5
90
208.6 208.6 232.1 232.1 257.1 206.8 201.5 201.5 224.2 224.2 248.3 203.7 193.4 193.4 215.2 215.2 238.3 200.1
75
210.8 194.8 234.3 146.9 259.7 96.8 203.5 191.6 226.2 143.7 250.7 93.7 195.3 187.9 217.0 140.2 240.5 90.2
80
211.0 211.0 234.4 186.5 259.6 137.2 203.7 203.7 226.4 183.3 250.6 134.1 195.4 195.4 217.2 179.7 240.4 130.6
85
211.0 211.0 234.6 225.9 259.7 177.5 203.8 203.8 226.6 222.7 250.7 174.4 195.5 195.5 217.3 217.3 240.5 170.9
90
211.1 211.1 234.7 234.7 259.9 217.0 203.8 203.8 226.6 226.6 250.9 213.8 195.5 195.5 217.4 217.4 240.7 210.2
Ambient Temperature (°F)
Ambient Temperature (°F)
115
125
Entering Wet Bulb (°F)
Entering Wet Bulb (°F)
Ent
61
67
73
61
67
73
DB
MBH
SHC
MBH
SHC
MBH
SHC
MBH
SHC
MBH
SHC
MBH
SHC
CFM (°F)
6000
6680
7350
8030
75
179.2 157.9 199.7 120.9 221.8 82.2 170.0 153.8 189.4 116.8 210.2 78.1
80
179.3 179.3 199.8 151.8 221.8 113.4 170.2 170.2 189.5 147.6 210.2 109.3
85
179.4 179.4 200.0 182.1 221.8 144.6 170.3 170.3 189.7 178.0 210.3 140.5
90
179.5 179.5 200.1 200.1 221.9 175.3 170.3 170.3 189.8 189.8 210.4 171.2
75
181.9 166.9 202.6 126.2 224.8 83.6 172.5 162.6 192.0 122.1 212.9 79.5
80
182.1 182.1 202.7 160.0 224.7 118.0 172.7 172.7 192.2 155.8 212.8 113.9
85
182.2 182.2 202.9 193.4 224.8 152.3 172.7 172.7 192.3 189.2 212.9 148.2
90
182.2 182.2 203.0 203.0 224.9 185.9 172.8 172.8 192.4 192.4 213.1 181.7
75
184.3 175.5 205.0 131.3 227.2 85.1 174.6 171.2 194.2 127.2 215.0 80.9
80
184.4 184.4 205.1 168.0 227.1 122.5 174.7 174.7 194.3 163.7 214.9 118.3
85
184.5 184.5 205.3 204.4 227.3 159.8 174.8 174.8 194.5 194.5 215.1 155.7
90
184.5 184.5 205.4 205.4 227.4 196.3 174.8 174.8 194.6 194.6 215.3 192.0
75
186.2 183.9 207.0 136.3 229.3 86.4 176.4 176.4 196.0 132.2 216.9 82.3
80
186.4 186.4 207.2 175.8 229.2 126.8 176.5 176.5 196.2 171.5 216.8 122.6
85
186.4 186.4 207.4 207.4 229.4 167.1 176.6 176.6 196.3 196.3 217.0 163.0
90
186.5 186.5 207.4 207.4 229.5 206.3 176.6 176.6 196.4 196.4 217.1 202.1
Notes:
1. All capacities shown are gross and have not considered indoor fan heat. To obtain net cooling,
subtract indoor fan heat.
2. MBH = Total Gross Capacity, SHC = Sensible Heat Capacity
SSP-PRC024J-EN
39
Performance Data
Table 25.
Gross cooling capacities (kW) TWA2014*D heat pump with TWE2014*B air handler (SI)
Ambient Temperature (°C)
Ambient Temperature (°C)
30
35
40
Entering Wet Bulb (°C)
Entering Wet Bulb (°C)
Entering Wet Bulb (°C)
Ent
16
Airflow DB
m3/hr (°C) kW SHC
10194
11349
12488
13643
19
22
12488
13643
22
16
19
22
SHC
kW
SHC
kW
SHC
kW
SHC
kW
SHC
kW
SHC
kW
SHC
kW
SHC
24
59.2
49.5
65.9
38.5
73.2
27.0
57.2
48.6
63.6
37.6
70.6
26.1
54.9
47.5
61.1
36.5
67.8
25.1
27
59.3
58.5
65.9
47.6
73.1
36.2
57.2
57.2
63.7
46.7
70.6
35.3
54.9
54.9
61.1
45.6
67.7
34.3
30
59.3
59.3
66.0
56.6
73.2
45.4
57.3
57.3
63.7
55.7
70.6
44.5
54.9
54.9
61.2
54.6
67.8
43.4
33
59.3
59.3
66.0
65.6
73.2
54.5
57.3
57.3
63.8
63.8
70.7
53.6
55.0
55.0
61.2
61.2
67.8
52.5
24
60.2
52.2
67.0
40.1
74.3
27.5
58.1
51.2
64.6
39.1
71.6
26.5
55.7
50.1
62.0
38.1
68.7
25.5
27
60.3
60.3
67.0
50.1
74.2
37.6
58.2
58.2
64.7
49.1
71.6
36.7
55.8
55.8
62.0
48.1
68.7
35.6
30
60.3
60.3
67.0
60.0
74.2
47.7
58.2
58.2
64.7
59.0
71.6
46.8
55.8
55.8
62.1
57.9
68.7
45.7
33
60.3
60.3
67.1
67.1
74.3
57.7
58.2
58.2
64.8
64.8
71.6
56.7
55.8
55.8
62.1
62.1
68.7
55.7
24
61.1
54.8
67.9
41.6
75.2
27.9
58.9
53.8
65.5
40.7
72.5
27.0
56.5
52.7
62.7
39.6
69.4
25.9
27
61.1
61.1
67.9
52.5
75.1
38.9
59.0
59.0
65.5
51.5
72.4
38.0
56.5
56.5
62.8
50.4
69.4
36.9
30
61.1
61.1
67.9
63.2
75.2
49.9
59.0
59.0
65.5
62.2
72.5
49.0
56.5
56.5
62.8
61.2
69.5
47.9
33
61.2
61.2
68.0
68.0
75.2
60.7
59.0
59.0
65.6
65.6
72.5
59.8
56.5
56.5
62.9
62.9
69.5
58.7
24
61.8
57.3
68.6
43.1
75.9
28.3
59.6
56.3
66.2
42.2
73.2
27.4
57.1
55.2
63.4
41.1
70.1
26.3
27
61.8
61.8
68.7
54.8
75.9
40.2
59.6
59.6
66.2
53.8
73.1
39.3
57.1
57.1
63.4
52.7
70.1
38.2
30
61.9
61.9
68.7
66.4
75.9
52.1
59.7
59.7
66.2
65.4
73.2
51.1
57.2
57.2
63.5
63.5
70.1
50.1
33
61.9
61.9
68.7
68.7
76.0
63.7
59.7
59.7
66.3
66.3
73.2
62.8
57.2
57.2
63.5
63.5
70.2
61.7
Ambient Temperature (°C)
45
52
Entering Wet Bulb (°C)
Entering Wet Bulb (°C)
Ent
16
Airflow DB
3
kW
SHC
m /hr (°C)
11349
19
kW
Ambient Temperature (°C)
10194
16
Ambient Temperature (°C)
19
22
16
19
22
kW
SHC
kW
SHC
kW
SHC
kW
SHC
kW
SHC
24
52.4
46.4
58.3
35.4
64.6
24.0
49.7
45.1
55.2
34.2
61.2
22.7
27
52.4
52.4
58.3
44.5
64.6
33.2
49.7
49.7
55.3
43.3
61.2
32.0
30
52.5
52.5
58.4
53.5
64.6
42.3
49.8
49.8
55.3
52.2
61.2
41.1
33
52.5
52.5
58.4
58.4
64.7
51.4
49.8
49.8
55.4
55.4
61.2
50.2
24
53.2
49.0
59.1
37.0
65.5
24.4
50.4
47.7
56.0
35.7
61.9
23.2
27
53.2
53.2
59.2
46.9
65.4
34.5
50.4
50.4
56.0
45.7
61.9
33.3
30
53.3
53.3
59.2
56.8
65.5
44.6
50.5
50.5
56.1
55.5
61.9
43.4
33
53.3
53.3
59.2
59.2
65.5
54.5
50.5
50.5
56.1
56.1
62.0
53.3
24
53.9
51.5
59.8
38.5
66.2
24.8
51.0
50.3
56.6
37.2
62.5
23.6
27
53.9
53.9
59.9
49.3
66.1
35.8
51.0
51.0
56.6
48.0
62.5
34.6
30
53.9
53.9
59.9
59.9
66.2
46.8
51.0
51.0
56.7
56.7
62.5
45.6
33
53.9
53.9
59.9
59.9
66.2
57.6
51.1
51.1
56.7
56.7
62.6
56.3
24
54.4
54.0
60.4
39.9
66.7
25.2
51.5
51.5
57.1
38.7
63.0
23.9
27
54.5
54.5
60.4
51.6
66.7
37.1
51.5
51.5
57.2
50.3
63.0
35.8
30
54.5
54.5
60.5
60.5
66.8
49.0
51.5
51.5
57.2
57.2
63.1
47.7
33
54.5
54.5
60.5
60.5
66.8
60.5
51.5
51.5
57.2
57.2
63.1
59.2
Notes:
1. All capacities shown are gross and have not considered indoor fan heat. To obtain net cooling,
subtract indoor fan heat.
2. kW = Total Gross Capacity, SHC = Sensible Heat Capacity
40
SSP-PRC024J-EN
Performance Data
Table 26.
Gross cooling capacities (MBH) TWA0604*A condensing unit only (IP)
Suction Temperature (°F)
Outdoor
Temp (°F)
65
75
85
95
105
115
125
30
35
40
45
50
55
Head Press (psig)
246.0
251.5
257.4
263.6
270.3
277.2
Capacity (Btuh/1000)
56.9
62.7
68.9
75.5
82.6
90.0
Unit Power (kW)
3.4
3.5
3.5
3.6
3.7
3.8
Head Press (psig)
283.6
289.5
295.7
302.3
309.3
316.5
Capacity (Btuh/1000)
54.0
59.5
65.4
71.7
78.4
85.5
Unit Power (kW)
3.8
3.8
3.9
4.0
4.0
4.1
Head Press (psig)
324.9
331.1
337.7
344.6
351.8
359.4
Capacity (Btuh/1000)
50.8
56.1
61.7
67.7
74.1
80.8
Unit Power (kW)
4.2
4.2
4.3
4.4
4.4
4.5
Head Press (psig)
369.8
376.4
383.3
390.5
398.0
405.9
Capacity (Btuh/1000)
47.4
52.4
57.8
63.5
69.6
75.9
Unit Power (kW)
4.6
4.7
4.7
4.8
4.9
5.0
Head Press (psig)
418.6
425.5
432.7
440.3
448.1
456.2
Capacity (Btuh/1000)
43.7
48.5
53.6
59.1
64.8
70.9
Unit Power (kW)
5.1
5.2
5.2
5.3
5.4
5.5
Head Press (psig)
471.6
478.8
486.3
494.0
502.0
510.2
Capacity (Btuh/1000)
39.8
44.4
49.3
54.5
59.9
65.6
Unit Power (kW)
5.7
5.7
5.8
5.9
6.0
6.1
Head Press (psig)
529.0
536.3
543.8
551.5
559.4
567.4
Capacity (Btuh/1000)
35.7
40.1
44.7
49.6
54.8
60.2
Unit Power (kW)
6.3
6.3
6.4
6.5
6.6
6.7
Note: Performance data calculated at 15°F subcooling and 15°F superheat and does not include capacity loss due to refrigerant lines.
Table 27.
Gross cooling capacities (kW) TWA0604*A condensing unit only (SI)
Suction Temperature (°C)
Outdoor
Temp (°C)
18.3
23.9
29.4
35
40.6
46.1
51.7
-1.1
1.7
4.4
7.2
10
12.8
Head Press (kPa)
1695.8
1734.1
1774.7
1817.8
1863.5
1911.3
26.4
Capacity (kW)
16.7
18.4
20.2
22.1
24.2
Unit Power (kW)
3.4
3.5
3.5
3.6
3.7
3.8
Head Press (kPa)
1955.5
1996.1
2039.1
2084.5
2132.2
2182.3
25.0
Capacity (kW)
15.8
17.4
19.2
21.0
23.0
Unit Power (kW)
3.8
3.8
3.9
4.0
4.0
4.1
Head Press (kPa)
2239.8
2282.8
2328.2
2375.6
2425.5
2478.0
23.7
Capacity (kW)
14.9
16.4
18.1
19.8
21.7
Unit Power (kW)
4.2
4.2
4.3
4.4
4.4
4.5
Head Press (kPa)
2549.8
2595.0
2642.6
2692.3
2744.2
2798.6
22.3
Capacity (kW)
13.9
15.4
16.9
18.6
20.4
Unit Power (kW)
4.6
4.7
4.7
4.8
4.9
5.0
Head Press (kPa)
2886.5
2933.8
2983.6
3035.5
3089.3
3145.4
20.8
Capacity (kW)
12.8
14.2
15.7
17.3
19.0
Unit Power (kW)
5.1
5.2
5.2
5.3
5.4
5.5
Head Press (kPa)
3251.7
3301.3
3352.8
3406.1
3461.3
3517.8
19.2
Capacity (kW)
11.7
13.0
14.4
16.0
17.6
Unit Power (kW)
5.7
5.7
5.8
5.9
6.0
6.1
Head Press (kPa)
3647.1
3697.4
3749.1
3802.6
3857.1
3912.2
Capacity (kW)
10.5
11.8
13.1
14.5
16.0
17.6
Unit Power (kW)
6.3
6.3
6.4
6.5
6.6
6.7
Note: Performance data calculated at 8.3°C subcooling and 8.3°C superheat and does not include capacity loss due to refrigerant lines.
SSP-PRC024J-EN
41
Performance Data
Table 28.
Gross cooling capacities (kW) TWA0604*D condensing unit only (IP)
Suction Temperature (°F)
Outdoor
Temp (°F)
65
75
85
95
105
115
125
30
35
40
45
50
55
Head Press (psig)
243.4
248.8
254.6
260.8
267.4
274.3
Capacity (Btuh/1000)
52.2
57.8
63.8
70.2
77.1
84.4
Unit Power (kW)
3.1
3.2
3.2
3.2
3.2
3.2
Head Press (psig)
280.2
285.9
292.0
298.4
305.2
312.4
Capacity (Btuh/1000)
49.3
54.6
60.3
66.4
72.9
79.8
Unit Power (kW)
3.5
3.5
3.6
3.6
3.6
3.7
Head Press (psig)
320.4
326.4
332.7
339.4
346.5
353.9
Capacity (Btuh/1000)
46.1
51.2
56.6
62.3
68.4
74.8
Unit Power (kW)
3.9
4.0
4.0
4.0
4.1
4.1
Head Press (psig)
364.1
370.4
377.0
383.9
391.1
398.7
Capacity (Btuh/1000)
42.7
47.5
52.6
58.0
63.7
69.8
Unit Power (kW)
4.4
4.5
4.5
4.5
4.6
4.6
Head Press (psig)
411.5
418.1
424.9
432.1
439.5
447.2
Capacity (Btuh/1000)
39.0
43.6
48.4
53.6
59.0
64.6
Unit Power (kW)
5.0
5.0
5.0
5.1
5.1
5.2
Head Press (psig)
463.1
469.9
476.9
484.2
491.7
499.4
Capacity (Btuh/1000)
35.3
39.6
44.2
49.0
54.1
59.4
Unit Power (kW)
5.6
5.6
5.7
5.7
5.7
5.8
Head Press (psig)
518.9
525.7
532.8
540.0
547.4
554.9
Capacity (Btuh/1000)
31.5
35.6
39.9
44.4
49.1
54.0
Unit Power (kW)
6.2
6.3
6.3
6.4
6.4
6.5
Note: Performance data calculated at 15°F subcooling and 15°F superheat and does not include capacity loss due to refrigerant lines.
Table 29.
Gross cooling capacities (kW) TWA0604*D condensing unit only (SI)
Suction Temperature (°C)
Outdoor
Temp (°C)
18.3
23.9
29.4
35
40.6
46.1
51.7
-1.1
1.7
4.4
7.2
10
12.8
Head Press (kPa)
1678.2
1715.5
1755.4
1798.0
1843.4
1891.5
Capacity (kW)
15.3
16.9
18.7
20.6
22.6
24.7
Unit Power (kW)
3.1
3.2
3.2
3.2
3.2
3.2
Head Press (kPa)
1932.0
1971.4
2013.2
2057.5
2104.5
2154.2
23.4
Capacity (kW)
14.5
16.0
17.7
19.5
21.4
Unit Power (kW)
3.5
3.5
3.6
3.6
3.6
3.7
Head Press (kPa)
2208.9
2250.4
2294.1
2340.2
2388.8
2439.8
21.9
Capacity (kW)
13.5
15.0
16.6
18.3
20.0
Unit Power (kW)
3.9
4.0
4.0
4.0
4.1
4.1
Head Press (kPa)
2510.3
2553.8
2599.3
2646.9
2696.9
2749.0
20.5
Capacity (kW)
12.5
13.9
15.4
17.0
18.7
Unit Power (kW)
4.4
4.5
4.5
4.5
4.6
4.6
Head Press (kPa)
2837.5
2882.8
2929.8
2979.0
3030.2
3083.4
18.9
Capacity (kW)
11.4
12.8
14.2
15.7
17.3
Unit Power (kW)
5.0
5.0
5.0
5.1
5.1
5.2
Head Press (kPa)
3193.0
3239.7
3288.1
3338.2
3389.9
3443.2
17.4
Capacity (kW)
10.3
11.6
13.0
14.4
15.9
Unit Power (kW)
5.6
5.6
5.7
5.7
5.7
5.8
Head Press (kPa)
3577.7
3624.8
3673.3
3723.0
3774.0
3825.9
Capacity (kW)
9.2
10.4
11.7
13.0
14.4
15.8
Unit Power (kW)
6.2
6.3
6.3
6.4
6.4
6.5
Note: Performance data calculated at 8.3°C subcooling and 8.3°C superheat and does not include capacity loss due to refrigerant lines.
42
SSP-PRC024J-EN
Performance Data
Table 30.
Gross cooling capacities (MBH) TWA0764*A condensing unit only (IP)
Suction Temperature (°F)
Outdoor
Temp (°F)
65
75
85
95
105
115
125
30
35
40
45
50
55
Head Press (psig)
249.7
255.6
262.0
268.8
276.2
284.0
Capacity (Btuh/1000)
63.0
69.3
76.0
83.2
90.9
99.0
Unit Power (kW)
4.0
4.0
4.1
4.2
4.3
4.4
Head Press (psig)
287.9
294.1
300.8
307.9
315.5
323.6
Capacity (Btuh/1000)
60.3
66.2
72.6
79.4
86.6
94.2
Unit Power (kW)
4.4
4.4
4.5
4.6
4.7
4.8
Head Press (psig)
329.1
335.7
342.6
350.0
357.9
366.3
Capacity (Btuh/1000)
56.9
62.5
68.5
74.9
81.7
88.8
Unit Power (kW)
4.8
4.9
4.9
5.0
5.1
5.2
Head Press (psig)
373.8
380.6
387.8
395.5
403.6
412.3
Capacity (Btuh/1000)
53.0
58.4
64.0
70.0
76.3
83.0
Unit Power (kW)
5.3
5.3
5.4
5.5
5.6
5.7
Head Press (psig)
422.2
429.3
436.8
444.7
453.1
461.9
Capacity (Btuh/1000)
49.0
54.0
59.3
64.9
70.9
77.1
Unit Power (kW)
5.8
5.9
6.0
6.1
6.2
6.3
Head Press (psig)
475.0
482.2
489.9
497.9
506.4
515.3
Capacity (Btuh/1000)
44.9
49.6
54.6
59.8
65.3
71.1
Unit Power (kW)
6.4
6.5
6.6
6.7
6.8
6.9
Head Press (psig)
532.2
539.4
547.1
555.1
563.5
572.3
Capacity (Btuh/1000)
40.9
45.2
49.8
54.6
59.7
65.0
Unit Power (kW)
7.1
7.2
7.3
7.4
7.5
7.6
Note: Performance data calculated at 15°F subcooling and 15°F superheat and does not include capacity loss due to refrigerant lines.
Table 31.
Gross cooling capacities (kW) TWA0764*A condensing unit only (SI)
Suction Temperature (°C)
Outdoor
Temp (°C)
18.3
23.9
29.4
35
40.6
46.1
51.7
-1.1
1.7
4.4
7.2
10
12.8
Head Press (kPa)
1721.6
1762.4
1806.3
1853.5
1904.0
1958.2
29.0
Capacity (kW)
18.5
20.3
22.3
24.4
26.6
Unit Power (kW)
4.0
4.0
4.1
4.2
4.3
4.4
Head Press (kPa)
1984.9
2027.9
2073.9
2123.0
2175.5
2231.5
27.6
Capacity (kW)
17.7
19.4
21.3
23.3
25.4
Unit Power (kW)
4.4
4.4
4.5
4.6
4.7
4.8
Head Press (kPa)
2269.3
2314.4
2362.4
2413.5
2467.9
2525.7
26.0
Capacity (kW)
16.7
18.3
20.1
22.0
23.9
Unit Power (kW)
4.8
4.9
4.9
5.0
5.1
5.2
Head Press (kPa)
2577.3
2624.2
2674.1
2726.9
2783.0
2842.4
24.3
Capacity (kW)
15.5
17.1
18.8
20.5
22.4
Unit Power (kW)
5.3
5.3
5.4
5.5
5.6
5.7
Head Press (kPa)
2911.1
2959.8
3011.5
3066.1
3123.8
3184.7
22.6
Capacity (kW)
14.4
15.8
17.4
19.0
20.8
Unit Power (kW)
5.8
5.9
6.0
6.1
6.2
6.3
Head Press (kPa)
3274.7
3324.7
3377.6
3433.2
3491.6
3553.1
20.8
Capacity (kW)
13.2
14.5
16.0
17.5
19.1
Unit Power (kW)
6.4
6.5
6.6
6.7
6.8
6.9
Head Press (kPa)
3669.1
3719.4
3772.1
3827.4
3885.4
3945.8
Capacity (kW)
12.0
13.2
14.6
16.0
17.5
19.1
Unit Power (kW)
7.1
7.2
7.3
7.4
7.5
7.6
Note: Performance data calculated at 8.3°C subcooling and 8.3°C superheat and does not include capacity loss due to refrigerant lines.
SSP-PRC024J-EN
43
Performance Data
Table 32.
Gross cooling capacities (MBH) TWA0764*D condensing unit only (IP)
Suction Temperature (°F)
Outdoor
Temp (°F)
65
75
85
95
105
115
125
30
35
40
45
50
55
Head Press (psig)
250.9
257.3
264.0
271.0
278.3
286.0
Capacity (Btuh/1000)
64.7
71.9
79.5
87.5
95.9
104.5
Unit Power (kW)
3.8
3.8
3.9
3.9
4.0
4.0
Head Press (psig)
287.9
294.6
301.6
308.8
316.3
324.5
Capacity (Btuh/1000)
61.0
67.8
75.0
82.5
90.4
98.5
Unit Power (kW)
4.2
4.3
4.3
4.4
4.4
4.5
Head Press (psig)
328.2
335.2
342.4
349.9
357.6
366.2
Capacity (Btuh/1000)
57.0
63.4
70.2
77.4
84.7
92.3
Unit Power (kW)
4.8
4.8
4.9
4.9
4.9
5.0
Head Press (psig)
372.0
379.2
386.7
394.4
402.2
411.2
Capacity (Btuh/1000)
52.8
58.9
65.3
72.0
78.9
86.0
Unit Power (kW)
5.4
5.4
5.5
5.5
5.5
5.6
Head Press (psig)
419.4
426.8
434.5
442.3
450.3
459.4
Capacity (Btuh/1000)
48.4
54.1
60.2
66.5
73.0
79.7
Unit Power (kW)
6.1
6.1
6.1
6.2
6.2
6.3
Head Press (psig)
470.7
478.3
486.0
493.9
501.9
510.7
Capacity (Btuh/1000)
43.8
49.3
55.0
60.9
67.0
73.2
Unit Power (kW)
6.9
6.9
6.9
7.0
7.0
7.0
Head Press (psig)
525.8
533.3
540.9
548.6
556.3
564.1
Capacity (Btuh/1000)
39.2
44.3
49.6
55.2
60.8
66.5
Unit Power (kW)
7.8
7.8
7.9
7.9
7.9
7.9
Note: Performance data calculated at 15°F subcooling and 15°F superheat and does not include capacity loss due to refrigerant lines.
Table 33.
Gross cooling capacities (kW) TWA0764*D condensing unit only (SI)
Suction Temperature (°C)
Outdoor
Temp (°C)
18.3
23.9
29.4
35
40.6
46.1
51.7
-1.1
1.7
4.4
7.2
10
12.8
Head Press (kPa)
1729.6
1773.8
1820.3
1868.6
1918.6
1972.0
Capacity (kW)
19.0
21.1
23.3
25.6
28.1
30.6
Unit Power (kW)
3.8
3.8
3.9
3.9
4.0
4.0
Head Press (kPa)
1984.8
2031.0
2079.2
2129.2
2180.8
2237.4
28.9
Capacity (kW)
17.9
19.9
22.0
24.2
26.5
Unit Power (kW)
4.2
4.3
4.3
4.4
4.4
4.5
Head Press (kPa)
2262.7
2310.9
2360.9
2412.6
2465.5
2524.7
27.1
Capacity (kW)
16.7
18.6
20.6
22.7
24.8
Unit Power (kW)
4.8
4.8
4.9
4.9
4.9
5.0
Head Press (kPa)
2564.7
2614.6
2666.1
2719.0
2773.0
2834.8
25.2
Capacity (kW)
15.5
17.3
19.1
21.1
23.1
Unit Power (kW)
5.4
5.4
5.5
5.5
5.5
5.6
Head Press (kPa)
2891.6
2942.8
2995.7
3049.9
3104.8
3167.5
23.3
Capacity (kW)
14.2
15.9
17.6
19.5
21.4
Unit Power (kW)
6.1
6.1
6.1
6.2
6.2
6.3
Head Press (kPa)
3245.2
3297.4
3351.1
3405.5
3460.2
3521.0
21.4
Capacity (kW)
12.8
14.4
16.1
17.9
19.6
Unit Power (kW)
6.9
6.9
6.9
7.0
7.0
7.0
Head Press (kPa)
3625.4
3677.1
3729.7
3782.7
3835.6
3889.1
Capacity (kW)
11.5
13.0
14.5
16.2
17.8
19.5
Unit Power (kW)
7.8
7.8
7.9
7.9
7.9
7.9
Note: Performance data calculated at 8.3°C subcooling and 8.3°C superheat and does not include capacity loss due to refrigerant lines.
44
SSP-PRC024J-EN
Performance Data
Table 34.
Gross cooling capacities (MBH) TWA1014*A condensing unit only (IP)
Suction Temperature (°F)
Outdoor
Temp (°F)
65
75
85
95
105
115
125
30
35
40
45
50
55
Head Press (psig)
260.5
266.2
271.8
277.6
283.3
288.9
Capacity (Btuh/1000)
86.3
95.0
104.4
114.4
124.9
135.9
Unit Power (kW)
5.4
5.5
5.5
5.6
5.7
5.7
Head Press (psig)
298.8
304.6
310.4
316.3
322.0
327.6
Capacity (Btuh/1000)
81.8
90.1
99.0
108.5
118.4
128.7
Unit Power (kW)
5.9
6.0
6.1
6.2
6.2
6.3
Head Press (psig)
340.8
346.8
352.7
358.7
364.4
369.9
Capacity (Btuh/1000)
77.2
85.1
93.5
102.4
111.7
121.4
Unit Power (kW)
6.6
6.6
6.7
6.8
6.8
6.9
Head Press (psig)
386.6
392.7
398.8
404.7
410.4
415.9
Capacity (Btuh/1000)
72.2
79.7
87.6
96.0
104.8
113.9
Unit Power (kW)
7.2
7.3
7.4
7.4
7.5
7.6
Head Press (psig)
436.5
442.7
448.8
454.7
460.3
465.5
Capacity (Btuh/1000)
66.9
74.0
81.5
89.4
97.6
106.1
Unit Power (kW)
8.0
8.0
8.1
8.2
8.3
8.3
Head Press (psig)
490.6
496.8
502.8
508.6
513.9
518.8
Capacity (Btuh/1000)
61.3
68.0
75.0
82.4
90.1
98.0
Unit Power (kW)
8.8
8.9
9.0
9.0
9.1
9.1
Head Press (psig)
549.0
555.0
560.7
566.0
570.9
575.1
Capacity (Btuh/1000)
55.3
61.5
68.1
75.0
82.2
89.5
Unit Power (kW)
9.7
9.8
9.9
9.9
10.0
10.0
Note: Performance data calculated at 15°F subcooling and 15°F superheat and does not include capacity loss due to refrigerant lines.
Table 35.
Gross cooling capacities (kW) TWA1014*A condensing unit only (SI)
Suction Temperature (°C)
Outdoor
Temp (°C)
18.3
23.9
29.4
35
40.6
46.1
51.7
-1.1
1.7
4.4
7.2
10
12.8
Head Press (kPa)
1796.2
1835.1
1874.3
1913.9
1953.2
1991.6
39.8
Capacity (kW)
25.3
27.9
30.6
33.5
36.6
Unit Power (kW)
5.4
5.5
5.5
5.6
5.7
5.7
Head Press (kPa)
2060.3
2100.2
2140.4
2180.6
2220.3
2258.8
37.7
Capacity (kW)
24.0
26.4
29.0
31.8
34.7
Unit Power (kW)
5.9
6.0
6.1
6.2
6.2
6.3
Head Press (kPa)
2349.9
2390.9
2432.0
2472.8
2512.7
2550.7
35.6
Capacity (kW)
22.6
24.9
27.4
30.0
32.7
Unit Power (kW)
6.6
6.6
6.7
6.8
6.8
6.9
Head Press (kPa)
2665.8
2707.7
2749.5
2790.4
2829.9
2867.3
33.4
Capacity (kW)
21.2
23.4
25.7
28.1
30.7
Unit Power (kW)
7.2
7.3
7.4
7.4
7.5
7.6
Head Press (kPa)
3009.4
3052.2
3094.2
3135.0
3173.9
3209.8
31.1
Capacity (kW)
19.6
21.7
23.9
26.2
28.6
Unit Power (kW)
8.0
8.0
8.1
8.2
8.3
8.3
Head Press (kPa)
3382.9
3425.6
3467.0
3506.5
3543.4
3576.9
28.7
Capacity (kW)
18.0
19.9
22.0
24.2
26.4
Unit Power (kW)
8.8
8.9
9.0
9.0
9.1
9.1
Head Press (kPa)
3785.4
3826.7
3866.0
3902.7
3936.0
3965.1
Capacity (kW)
16.2
18.0
20.0
22.0
24.1
26.2
Unit Power (kW)
9.7
9.8
9.9
9.9
10.0
10.0
Note: Performance data calculated at 8.3°C subcooling and 8.3°C superheat and does not include capacity loss due to refrigerant lines.
SSP-PRC024J-EN
45
Performance Data
Table 36.
Gross cooling capacities (MBH) TWA1014*D condensing unit only (IP)
Suction Temperature (°F)
Outdoor
Temp (°F)
65
75
85
95
105
115
125
30
35
40
45
50
55
Head Press (psig)
249.0
254.7
260.7
266.9
273.4
280.2
Capacity (Btuh/1000)
86.6
95.3
104.5
114.2
124.4
135.0
Unit Power (kW)
4.9
5.0
5.0
5.1
5.2
5.2
Head Press (psig)
285.4
291.2
297.3
303.8
310.5
317.4
Capacity (Btuh/1000)
80.7
88.8
97.4
106.5
116.0
126.0
Unit Power (kW)
5.5
5.5
5.6
5.7
5.7
5.8
Head Press (psig)
325.9
331.9
338.3
344.9
351.8
358.9
Capacity (Btuh/1000)
75.3
83.0
91.0
99.6
108.6
118.0
Unit Power (kW)
6.2
6.2
6.3
6.4
6.4
6.5
Head Press (psig)
370.2
376.5
383.2
390.1
397.2
404.6
Capacity (Btuh/1000)
70.0
77.2
84.9
93.0
101.5
110.3
Unit Power (kW)
7.0
7.0
7.1
7.2
7.2
7.3
Head Press (psig)
418.1
424.8
431.8
439.0
446.5
454.1
Capacity (Btuh/1000)
64.2
71.2
78.5
86.3
94.4
102.8
Unit Power (kW)
7.8
7.9
8.0
8.0
8.1
8.1
Head Press (psig)
469.3
476.4
483.8
491.4
499.2
507.0
Capacity (Btuh/1000)
57.7
64.5
71.6
79.1
86.8
94.8
Unit Power (kW)
8.7
8.8
8.9
8.9
9.0
9.0
Head Press (psig)
523.4
530.9
538.7
546.6
554.6
562.6
Capacity (Btuh/1000)
50.3
56.9
63.9
71.1
78.5
86.2
Unit Power (kW)
9.6
9.7
9.8
9.9
9.9
10.0
Note: Performance data calculated at 15°F subcooling and 15°F superheat and does not include capacity loss due to refrigerant lines.
Table 37.
Gross cooling capacities (kW) TWA1014*D condensing unit only (SI)
Suction Temperature (°C)
Outdoor
Temp (°C)
18.3
23.9
29.4
35
40.6
46.1
51.7
-1.1
1.7
4.4
7.2
10
12.8
Head Press (kPa)
1716.9
1756.1
1797.2
1840.2
1885.3
1932.2
Capacity (kW)
25.4
27.9
30.6
33.5
36.5
39.6
Unit Power (kW)
4.9
5.0
5.0
5.1
5.2
5.2
Head Press (kPa)
1967.7
2007.8
2050.1
2094.4
2140.6
2188.6
36.9
Capacity (kW)
23.6
26.0
28.5
31.2
34.0
Unit Power (kW)
5.5
5.5
5.6
5.7
5.7
5.8
Head Press (kPa)
2246.7
2288.4
2332.2
2378.0
2425.6
2474.9
34.6
Capacity (kW)
22.1
24.3
26.7
29.2
31.8
Unit Power (kW)
6.2
6.2
6.3
6.4
6.4
6.5
Head Press (kPa)
2552.4
2596.2
2641.9
2689.4
2738.7
2789.3
32.3
Capacity (kW)
20.5
22.6
24.9
27.3
29.7
Unit Power (kW)
7.0
7.0
7.1
7.2
7.2
7.3
Head Press (kPa)
2882.4
2928.8
2976.9
3027.0
3078.3
3130.8
30.1
Capacity (kW)
18.8
20.9
23.0
25.3
27.7
Unit Power (kW)
7.8
7.9
8.0
8.0
8.1
8.1
Head Press (kPa)
3235.4
3284.8
3335.9
3388.3
3441.8
3495.9
27.8
Capacity (kW)
16.9
18.9
21.0
23.2
25.4
Unit Power (kW)
8.7
8.8
8.9
8.9
9.0
9.0
Head Press (kPa)
3608.4
3660.7
3714.2
3768.7
3823.8
3878.9
Capacity (kW)
14.8
16.7
18.7
20.8
23.0
25.3
Unit Power (kW)
9.6
9.7
9.8
9.9
9.9
10.0
Note: Performance data calculated at 8.3°C subcooling and 8.3°C superheat and does not include capacity loss due to refrigerant lines.
46
SSP-PRC024J-EN
Performance Data
Table 38.
Gross cooling capacities (MBH) TWA1564*D condensing unit only (IP)
Suction Temperature (°F)
Outdoor
Temp (°F)
65
75
85
95
105
115
125
30
35
40
45
50
55
Head Press (psig)
230.1
234.1
238.4
243.1
248.1
253.5
Capacity (Btuh/1000)
137.9
151.4
166.0
181.6
198.4
216.3
Unit Power (kW)
8.7
8.9
9.1
9.3
9.5
9.8
Head Press (psig)
266.3
270.7
275.4
280.5
285.8
291.5
Capacity (Btuh/1000)
130.8
144.0
158.1
173.2
189.5
206.9
Unit Power (kW)
9.5
9.7
9.9
10.1
10.3
10.6
Head Press (psig)
306.2
310.9
315.9
321.2
326.9
333.0
Capacity (Btuh/1000)
123.1
135.8
149.4
164.0
179.6
196.4
Unit Power (kW)
10.5
10.6
10.8
11.0
11.2
11.5
Head Press (psig)
349.8
354.8
360.0
365.6
371.6
378.0
Capacity (Btuh/1000)
114.9
127.0
140.0
154.0
169.0
185.1
Unit Power (kW)
11.5
11.7
11.8
12.0
12.2
12.5
Head Press (psig)
397.4
402.6
408.1
413.9
420.1
426.6
Capacity (Btuh/1000)
106.3
117.8
130.2
143.5
157.8
173.1
Unit Power (kW)
12.7
12.8
13.0
13.2
13.4
13.6
Head Press (psig)
449.3
454.6
460.3
466.2
472.6
479.3
Capacity (Btuh/1000)
97.6
108.4
120.1
132.7
146.2
160.6
Unit Power (kW)
14.0
14.2
14.4
14.5
14.7
15.0
Head Press (psig)
505.8
511.1
516.7
522.7
529.0
535.7
Capacity (Btuh/1000)
88.7
98.9
109.8
121.5
134.2
147.7
Unit Power (kW)
15.6
15.7
15.9
16.1
16.2
16.5
Note: Performance data calculated at 15°F subcooling and 15°F superheat and does not include capacity loss due to refrigerant lines.
Table 39.
Gross cooling capacities (kW) TWA1564*D condensing unit only (SI)
Suction Temperature (°C)
Outdoor
Temp (°C)
18.3
23.9
29.4
35
40.6
46.1
51.7
-1.1
1.7
4.4
7.2
10
12.8
Head Press (kPa)
1586.2
1614.0
1644.1
1676.3
1710.8
1747.8
63.4
Capacity (kW)
40.4
44.4
48.6
53.2
58.1
Unit Power (kW)
8.7
8.9
9.1
9.3
9.5
9.8
Head Press (kPa)
1836.4
1866.7
1899.1
1933.7
1970.7
2010.2
60.6
Capacity (kW)
38.3
42.2
46.3
50.8
55.5
Unit Power (kW)
9.5
9.7
9.9
10.1
10.3
10.6
Head Press (kPa)
2111.2
2143.5
2178.0
2214.8
2254.0
2295.9
57.6
Capacity (kW)
36.1
39.8
43.8
48.1
52.6
Unit Power (kW)
10.5
10.6
10.8
11.0
11.2
11.5
Head Press (kPa)
2411.8
2445.9
2482.3
2521.0
2562.3
2606.0
54.2
Capacity (kW)
33.7
37.2
41.0
45.1
49.5
Unit Power (kW)
11.5
11.7
11.8
12.0
12.2
12.5
Head Press (kPa)
2740.0
2775.6
2813.4
2853.6
2896.4
2941.6
50.7
Capacity (kW)
31.2
34.5
38.2
42.1
46.2
Unit Power (kW)
12.7
12.8
13.0
13.2
13.4
13.6
Head Press (kPa)
3098.0
3134.5
3173.4
3214.6
3258.4
3304.9
47.1
Capacity (kW)
28.6
31.8
35.2
38.9
42.8
Unit Power (kW)
14.0
14.2
14.4
14.5
14.7
15.0
Head Press (kPa)
3487.4
3523.8
3562.5
3603.8
3647.4
3693.5
Capacity (kW)
26.0
29.0
32.2
35.6
39.3
43.3
Unit Power (kW)
15.6
15.7
15.9
16.1
16.2
16.5
Note: Performance data calculated at 8.3°C subcooling and 8.3°C superheat and does not include capacity loss due to refrigerant lines.
SSP-PRC024J-EN
47
Performance Data
Table 40.
Gross cooling capacities (MBH) TWA2014*D condensing unit only (IP)
Suction Temperature (°F)
Outdoor
Temp (°F)
65
75
85
95
105
115
125
30
35
40
45
50
55
Head Press (psig)
252.9
259.0
265.6
272.5
279.9
287.8
Capacity (Btuh/1000)
208.6
228.8
250.3
273.1
297.2
322.7
Unit Power (kW)
12.6
12.8
13.1
13.4
13.7
14.1
Head Press (psig)
289.6
296.0
302.8
310.1
317.8
326.0
Capacity (Btuh/1000)
197.9
217.5
238.3
260.3
283.5
307.9
Unit Power (kW)
13.8
14.0
14.3
14.6
14.9
15.3
Head Press (psig)
329.5
336.2
343.3
350.8
358.8
367.3
Capacity (Btuh/1000)
186.0
204.8
224.8
245.8
268.0
291.3
Unit Power (kW)
15.1
15.4
15.6
15.9
16.2
16.6
Head Press (psig)
372.8
379.8
387.1
394.9
403.0
411.7
Capacity (Btuh/1000)
173.0
190.9
210.0
230.0
251.1
273.1
Unit Power (kW)
16.7
16.9
17.2
17.4
17.7
18.1
Head Press (psig)
419.7
426.8
434.3
442.2
450.6
459.3
Capacity (Btuh/1000)
159.2
176.2
194.1
213.1
233.0
253.8
Unit Power (kW)
18.5
18.7
18.9
19.2
19.4
19.8
Head Press (psig)
470.4
477.6
485.2
493.1
501.4
510.2
Capacity (Btuh/1000)
144.7
160.7
177.6
195.4
214.0
233.4
Unit Power (kW)
20.5
20.7
20.9
21.1
21.4
21.7
Head Press (psig)
524.9
531.9
539.3
547.1
555.1
563.6
Capacity (Btuh/1000)
129.8
144.6
160.3
176.7
193.9
211.8
Unit Power (kW)
22.7
22.9
23.1
23.3
23.6
23.8
Note: Performance data calculated at 15°F subcooling and 15°F superheat and does not include capacity loss due to refrigerant lines.
Table 41.
Gross cooling capacities (kW) TWA2014*D condensing unit only (SI)
Suction Temperature (°C)
Outdoor
Temp (°C)
18.3
23.9
29.4
35
40.6
46.1
51.7
-1.1
1.7
4.4
7.2
10
12.8
Head Press (kPa)
1744.0
1786.0
1830.9
1878.8
1929.9
1984.5
94.6
Capacity (kW)
61.1
67.1
73.4
80.0
87.1
Unit Power (kW)
12.6
12.8
13.1
13.4
13.7
14.1
Head Press (kPa)
1996.5
2040.8
2087.9
2137.9
2191.1
2247.6
90.2
Capacity (kW)
58.0
63.7
69.8
76.3
83.1
Unit Power (kW)
13.8
14.0
14.3
14.6
14.9
15.3
Head Press (kPa)
2271.6
2317.9
2367.0
2419.0
2474.0
2532.2
85.4
Capacity (kW)
54.5
60.0
65.9
72.0
78.5
Unit Power (kW)
15.1
15.4
15.6
15.9
16.2
16.6
Head Press (kPa)
2570.4
2618.3
2668.9
2722.4
2778.8
2838.3
80.0
Capacity (kW)
50.7
56.0
61.5
67.4
73.6
Unit Power (kW)
16.7
16.9
17.2
17.4
17.7
18.1
Head Press (kPa)
2893.7
2942.7
2994.5
3049.1
3106.6
3167.1
74.4
Capacity (kW)
46.6
51.6
56.9
62.5
68.3
Unit Power (kW)
18.5
18.7
18.9
19.2
19.4
19.8
Head Press (kPa)
3243.4
3292.8
3345.0
3399.8
3457.3
3517.4
68.4
Capacity (kW)
42.4
47.1
52.0
57.3
62.7
Unit Power (kW)
20.5
20.7
20.9
21.1
21.4
21.7
Head Press (kPa)
3618.7
3667.3
3718.3
3771.8
3827.6
3885.7
Capacity (kW)
38.0
42.4
47.0
51.8
56.8
62.1
Unit Power (kW)
22.7
22.9
23.1
23.3
23.6
23.8
Note: Performance data calculated at 8.3°C subcooling and 8.3°C superheat and does not include capacity loss due to refrigerant lines.
48
SSP-PRC024J-EN
Performance Data
Gross Heating Capacities
Table 42.
Gross heating capacities (MBH) - TWA0604*A heat pump with TWE0764*A air handler at 2000 CFM (IP)
Outdoor
Temp (°F)
Integrated Heating Capacity (MBH)
at Indicated Indoor Dry Bulb Temp (°F)
60
70
75
80
Total Power (kW)
at Indicated Indoor Dry Bulb Temp (°F)
60
70
75
80
-18
20.1
18.4
17.6
16.7
3.9
4.3
4.5
4.7
-13
22.0
20.5
19.7
18.8
4.0
4.4
4.5
4.7
-8
24.3
22.8
22.0
21.1
4.1
4.4
4.6
4.8
-3
26.8
25.3
24.5
23.6
4.1
4.5
4.7
4.9
2
29.5
28.0
27.2
26.4
4.2
4.6
4.8
5.0
7
32.4
31.0
30.1
29.3
4.3
4.6
4.9
5.1
12
35.6
34.1
33.3
32.4
4.3
4.7
4.9
5.2
17
38.9
37.4
36.5
35.7
4.4
4.8
5.0
5.2
22
42.4
40.8
39.9
39.0
4.5
4.9
5.1
5.3
27
46.2
44.5
43.6
42.6
4.6
5.0
5.2
5.4
32
50.3
48.4
47.4
46.4
4.7
5.1
5.3
5.5
37
54.3
52.3
51.3
50.3
4.7
5.2
5.4
5.6
42
58.6
56.4
55.3
54.3
4.8
5.3
5.5
5.7
47
63.0
60.8
59.6
58.5
4.9
5.4
5.6
5.8
52
67.7
65.3
64.1
62.8
5.0
5.5
5.7
5.9
57
72.6
70.0
68.6
67.3
5.1
5.6
5.8
6.1
62
77.6
74.7
73.3
71.9
5.3
5.7
5.9
6.2
67
82.7
79.6
78.1
76.6
5.4
5.8
6.1
6.3
72
87.8
84.6
83.0
81.4
5.5
6.0
6.2
6.5
Notes:
1. Net heating capacity and power include indoor fan heat at AHRI ESP. To obtain net heating at other conditions, subtract fan heat at this condition
and add fan heat at new condition.
2. Integrated heating capacities and power include the effects of defrost in the frost region. All heating capacities and power are at 70% outdoor
relative humidity and demand defrost cycle.
Table 43.
Gross heating capacities (kW) TWA0604*A heat pump with TWE0764*A air handler at 2000 CFM (SI)
Integrated Heating Capacity (kW)
at Indicated Indoor Dry Bulb Temp (°C)
15
21
24
27
Total Power (kW)
at Indicated Indoor Dry Bulb Temp (°C)
15
21
24
27
-28
5.8
5.4
5.1
4.8
3.7
4.1
4.3
4.5
-25
6.4
5.9
5.7
5.4
3.8
4.2
4.4
4.6
-22
7.0
6.6
6.4
6.1
3.9
4.3
4.5
4.7
-19
7.7
7.3
7.1
6.8
3.9
4.3
4.5
4.8
-17
8.5
8.1
7.8
7.6
4.0
4.4
4.6
4.8
-14
9.3
8.9
8.7
8.4
4.1
4.5
4.7
4.9
-11
10.2
9.8
9.5
9.3
4.2
4.6
4.8
5.0
-8
11.2
10.7
10.5
10.2
4.2
4.7
4.9
5.1
-6
12.2
11.7
11.5
11.2
4.3
4.7
5.0
5.2
-3
13.3
12.8
12.5
12.2
4.4
4.8
5.1
5.3
0
14.5
13.9
13.6
13.4
4.5
4.9
5.2
5.4
3
15.6
15.0
14.8
14.5
4.6
5.0
5.3
5.5
6
16.8
16.2
15.9
15.6
4.7
5.1
5.4
5.6
8
18.1
17.5
17.2
16.8
4.8
5.2
5.5
5.7
11
19.5
18.8
18.5
18.1
4.9
5.4
5.6
5.9
14
20.9
20.2
19.8
19.4
5.0
5.5
5.7
6.0
17
22.4
21.6
21.2
20.8
5.1
5.6
5.9
6.1
19
23.8
23.0
22.6
22.2
5.3
5.8
6.0
6.3
22
25.4
24.5
24.0
23.6
5.4
5.9
6.1
6.4
Outdoor
Temp (°C)
Notes:
1. Net heating capacity and power include indoor fan heat at AHRI ESP. To obtain net heating at other conditions, subtract fan heat at this condition
and add fan heat at new condition.
2. Integrated heating capacities and power include the effects of defrost in the frost region. All heating capacities and power are at 70% outdoor
relative humidity and demand defrost cycle.
SSP-PRC024J-EN
49
Performance Data
Table 44.
Gross heating capacities (MBH) - TWA0604*D heat pump with TWE0724*B standard air handler at 2000
CFM (IP)
Integrated Heating Capacity (MBH)
at Indicated Indoor Dry Bulb Temp (°F)
Total Power (kW)
at Indicated Indoor Dry Bulb Temp (°F)
Outdoor
Temp (°F)
60
70
75
80
60
70
75
80
-18
11.3
9.5
9.8
9.7
3.4
3.6
3.8
4.0
-13
13.7
12.1
11.1
10.1
3.4
3.7
3.9
4.1
-8
16.5
14.9
13.9
12.9
3.5
3.8
4.0
4.2
-3
19.2
17.5
16.5
15.7
3.6
3.9
4.1
4.3
2
21.8
20.2
19.5
18.7
3.7
4.0
4.2
4.4
7
25.2
23.4
22.6
21.9
3.8
4.1
4.3
4.5
12
27.7
26.4
25.7
25.0
3.8
4.2
4.4
4.6
17
31.0
29.7
29.0
28.2
3.9
4.3
4.5
4.7
22
34.5
33.1
32.4
31.6
3.9
4.3
4.5
4.8
27
38.1
36.7
35.9
35.1
4.0
4.4
4.6
4.8
32
41.9
40.3
39.5
38.6
4.0
4.4
4.7
4.9
37
45.7
44.0
43.1
42.2
4.1
4.5
4.7
5.0
42
49.5
47.7
46.8
45.8
4.1
4.5
4.8
5.0
47
53.6
51.7
50.7
49.7
4.2
4.6
4.8
5.1
52
58.0
56.0
54.9
53.8
4.2
4.6
4.9
5.1
57
62.7
60.4
59.3
58.1
4.3
4.7
5.0
5.2
62
67.5
65.0
63.8
62.5
4.3
4.8
5.0
5.3
67
72.5
69.7
68.4
67.1
4.4
4.9
5.1
5.4
72
77.7
74.8
73.3
71.9
4.5
5.0
5.2
5.5
Notes:
1. Net heating capacity and power include indoor fan heat at AHRI ESP. To obtain net heating at other conditions, subtract fan heat at this condition
and add fan heat at new condition.
2. Integrated heating capacities and power include the effects of defrost in the frost region. All heating capacities and power are at 70% outdoor
relative humidity and demand defrost cycle.
Table 45.
Gross heating capacities (kW) TWA0604*D heat pump with TWE0724*B air handler at 2000 CFM (SI)
Integrated Heating Capacity (kW)
at Indicated Indoor Dry Bulb Temp (°C)
Total Power (kW)
at Indicated Indoor Dry Bulb Temp (°C)
Outdoor
Temp (°C)
15
21
24
27
15
21
24
27
-28
3.3
2.8
2.9
2.8
3.4
3.6
3.8
4.0
-25
4.0
3.5
3.3
2.9
3.4
3.7
3.9
4.1
-22
4.8
4.4
4.1
3.8
3.5
3.8
4.0
4.2
-19
5.6
5.1
4.8
4.6
3.6
3.9
4.1
4.3
-17
6.4
5.9
5.7
5.5
3.7
4.0
4.2
4.4
-14
7.4
6.8
6.6
6.4
3.8
4.1
4.3
4.5
-11
8.1
7.7
7.5
7.3
3.8
4.2
4.4
4.6
-8
9.1
8.7
8.5
8.3
3.9
4.3
4.5
4.7
-6
10.1
9.7
9.5
9.3
3.9
4.3
4.5
4.8
-3
11.2
10.7
10.5
10.3
4.0
4.4
4.6
4.8
0
12.3
11.8
11.6
11.3
4.0
4.4
4.7
4.9
3
13.4
12.9
12.6
12.4
4.1
4.5
4.7
5.0
6
14.5
14.0
13.7
13.4
4.1
4.5
4.8
5.0
8
15.7
15.1
14.9
14.6
4.2
4.6
4.8
5.1
11
17.0
16.4
16.1
15.8
4.2
4.6
4.9
5.1
14
18.4
17.7
17.4
17.0
4.3
4.7
5.0
5.2
17
19.8
19.1
18.7
18.3
4.3
4.8
5.0
5.3
19
21.2
20.4
20.0
19.7
4.4
4.9
5.1
5.4
22
22.8
21.9
21.5
21.1
4.5
5.0
5.2
5.5
Notes:
1. Net heating capacity and power include indoor fan heat at AHRI ESP. To obtain net heating at other conditions, subtract fan heat at this condition
and add fan heat at new condition.
2. Integrated heating capacities and power include the effects of defrost in the frost region. All heating capacities and power are at 70% outdoor
relative humidity and demand defrost cycle.
50
SSP-PRC024J-EN
Performance Data
Table 46.
Gross heating capacities (MBH) TWA0764*A heat pump with TWE0764*A air handler at 2500 CFM (IP)
Outdoor
Temp (°F)
Integrated Heating Capacity (MBH)
at Indicated Indoor Dry Bulb Temp (°F)
60
70
75
80
Total Power (kW)
at Indicated Indoor Dry Bulb Temp (°F)
60
70
75
80
-18
17.5
17.2
16.9
16.4
3.7
4.1
4.2
4.4
-13
21.5
20.6
20.1
19.6
3.8
4.2
4.3
4.5
-8
24.0
23.7
23.3
22.9
3.9
4.2
4.4
4.6
-3
27.3
27.0
26.4
26.0
4.0
4.3
4.5
4.7
2
30.8
29.9
29.6
29.1
4.0
4.4
4.6
4.8
7
34.3
33.8
33.4
32.9
4.1
4.5
4.7
4.9
12
37.3
36.7
36.3
35.8
4.2
4.5
4.7
4.9
17
41.0
40.4
39.9
39.3
4.2
4.6
4.8
5.0
22
44.9
44.2
43.6
43.0
4.3
4.7
4.9
5.1
27
49.0
48.1
47.2
46.6
4.3
4.7
4.9
5.2
32
53.2
52.1
51.4
50.7
4.4
4.8
5.0
5.2
37
57.4
56.2
55.4
54.6
4.5
4.9
5.1
5.3
42
61.7
60.3
59.4
58.5
4.5
4.9
5.2
5.4
47
66.3
64.6
63.7
62.7
4.6
5.0
5.2
5.5
52
71.2
69.3
68.3
67.2
4.7
5.1
5.3
5.6
57
76.5
74.3
73.1
71.9
4.8
5.2
5.4
5.7
62
82.1
79.6
78.3
77.0
4.9
5.3
5.5
5.8
67
88.0
85.2
83.7
82.2
5.0
5.5
5.7
5.9
72
94.1
91.0
89.3
87.6
5.2
5.6
5.8
6.0
Notes:
1. Net heating capacity and power include indoor fan heat at AHRI ESP. To obtain net heating at other conditions, subtract fan heat at this condition
and add fan heat at new condition.
2. Integrated heating capacities and power include the effects of defrost in the frost region. All heating capacities and power are at 70% outdoor
relative humidity and demand defrost cycle.
Table 47.
Gross heating capacities (kW) TWA0764*A heat pump with TWE0764*A air handler at 2500 CFM (SI)
Integrated Heating Capacity (kW)
at Indicated Indoor Dry Bulb Temp (°C)
15
21
24
27
Total Power (kW)
at Indicated Indoor Dry Bulb Temp (°C)
15
21
24
27
-28
5.0
5.0
4.9
4.7
4.1
4.5
4.7
4.9
-25
6.3
6.0
5.8
5.7
4.2
4.6
4.8
5.0
-22
6.9
6.8
6.7
6.6
4.3
4.7
4.9
5.1
-19
7.7
7.6
7.7
7.5
4.4
4.8
5.0
5.3
-17
8.8
8.7
8.6
8.5
4.4
4.9
5.1
5.4
-14
9.7
9.6
9.4
9.3
4.5
5.0
5.2
5.5
-11
10.7
10.6
10.5
10.3
4.6
5.1
5.3
5.6
-8
11.8
11.6
11.5
11.3
4.7
5.2
5.4
5.6
-6
12.9
12.7
12.6
12.4
4.8
5.2
5.5
5.7
-3
14.1
13.9
13.7
13.5
4.8
5.3
5.6
5.8
0
15.3
15.0
14.9
14.7
4.9
5.4
5.7
5.9
3
16.6
16.2
16.0
15.8
5.0
5.5
5.7
6.0
6
17.8
17.4
17.2
16.9
5.1
5.6
5.8
6.1
8
19.1
18.7
18.4
18.1
5.2
5.7
5.9
6.2
11
20.5
20.0
19.7
19.4
5.3
5.8
6.0
6.3
14
22.0
21.4
21.1
20.8
5.4
5.9
6.2
6.5
17
23.6
23.0
22.6
22.2
5.5
6.0
6.3
6.6
19
25.4
24.6
24.2
23.8
5.7
6.2
6.5
6.7
22
27.1
26.3
25.8
25.3
5.8
6.4
6.6
6.9
Outdoor
Temp (°C)
Notes:
1. Net heating capacity and power include indoor fan heat at AHRI ESP. To obtain net heating at other conditions, subtract fan heat at this condition
and add fan heat at new condition.
2. Integrated heating capacities and power include the effects of defrost in the frost region. All heating capacities and power are at 70% outdoor
relative humidity and demand defrost cycle.
SSP-PRC024J-EN
51
Performance Data
Table 48.
Gross heating capacities (MBH) TWA0764*D heat pump with TWE0764*B air handler at 2500 CFM (IP)
Integrated Heating Capacity (MBH)
at Indicated Indoor Dry Bulb Temp (°F)
Total Power (kW)
at Indicated Indoor Dry Bulb Temp (°F)
Outdoor
Temp (°F)
60
70
75
80
60
70
75
80
-18
13.5
12.8
12.3
11.8
4.5
5.1
5.5
5.8
-13
16.5
16.0
15.6
15.2
4.6
5.2
5.5
5.8
-8
19.8
19.3
18.9
18.5
4.6
5.2
5.5
5.8
-3
23.3
22.7
22.4
21.9
4.6
5.2
5.5
5.9
2
26.9
26.4
26.0
25.5
4.7
5.2
5.6
5.9
7
30.7
30.0
29.6
29.1
4.7
5.3
5.6
5.9
12
34.6
33.8
33.3
32.8
4.8
5.3
5.6
6.0
17
38.8
37.8
37.2
36.7
4.8
5.4
5.7
6.0
22
43.2
42.0
41.4
40.8
4.9
5.4
5.7
6.1
27
47.7
46.3
45.6
44.9
4.9
5.5
5.8
6.1
32
52.5
50.9
50.0
49.2
5.0
5.6
5.9
6.2
37
57.2
55.4
54.5
53.5
5.1
5.6
5.9
6.2
42
62.0
59.9
58.9
57.9
5.1
5.7
6.0
6.3
47
67.0
64.6
63.5
62.4
5.2
5.8
6.1
6.4
52
72.2
69.7
68.5
67.3
5.3
5.8
6.1
6.5
57
77.7
74.9
73.5
72.2
5.4
5.9
6.2
6.5
62
83.4
80.4
78.9
77.5
5.4
6.0
6.3
6.6
67
89.4
86.1
84.5
82.9
5.5
6.1
6.4
6.7
72
95.4
91.7
89.8
85.5
5.6
6.2
6.5
7.1
Notes:
1. Net heating capacity and power include indoor fan heat at AHRI ESP. To obtain net heating at other conditions, subtract fan heat at this condition
and add fan heat at new condition.
2. Integrated heating capacities and power include the effects of defrost in the frost region. All heating capacities and power are at 70% outdoor
relative humidity and demand defrost cycle.
Table 49.
Gross heating capacities (kW) TWA0764*D heat pump with TWE0764*B air handler at 2500 CFM (SI)
Integrated Heating Capacity (kW)
at Indicated Indoor Dry Bulb Temp (°C)
Total Power (kW)
at Indicated Indoor Dry Bulb Temp (°C)
Outdoor
Temp (°C)
15
21
24
27
15
21
24
27
-28
3.9
3.7
3.6
3.4
4.5
5.1
5.5
5.8
-25
4.8
4.7
4.6
4.4
4.6
5.2
5.5
5.8
-22
5.8
5.7
5.5
5.4
4.6
5.2
5.5
5.8
-19
6.8
6.7
6.6
6.4
4.6
5.2
5.5
5.9
-17
7.9
7.7
7.6
7.5
4.7
5.2
5.6
5.9
-14
9.0
8.8
8.7
8.5
4.7
5.3
5.6
5.9
-11
10.1
9.9
9.8
9.6
4.8
5.3
5.6
6.0
-8
11.4
11.1
10.9
10.8
4.8
5.4
5.7
6.0
-6
12.7
12.3
12.1
11.9
4.9
5.4
5.7
6.1
-3
14.0
13.6
13.4
13.2
4.9
5.5
5.8
6.1
0
15.4
14.9
14.7
14.4
5.0
5.6
5.9
6.2
3
16.8
16.2
16.0
15.7
5.1
5.6
5.9
6.2
6
18.2
17.6
17.3
17.0
5.1
5.7
6.0
6.3
8
19.6
18.9
18.6
18.3
5.2
5.8
6.1
6.4
11
21.1
20.4
20.1
19.7
5.3
5.8
6.1
6.5
14
22.8
22.0
21.6
21.2
5.4
5.9
6.2
6.5
17
24.4
23.6
23.1
22.7
5.4
6.0
6.3
6.6
19
26.2
25.2
24.8
24.3
5.5
6.1
6.4
6.7
22
28.0
26.9
26.3
25.1
5.6
6.2
6.5
7.1
Notes:
1. Net heating capacity and power include indoor fan heat at AHRI ESP. To obtain net heating at other conditions, subtract fan heat at this condition
and add fan heat at new condition.
2. Integrated heating capacities and power include the effects of defrost in the frost region. All heating capacities and power are at 70% outdoor
relative humidity and demand defrost cycle.
52
SSP-PRC024J-EN
Performance Data
Table 50.
Gross heating capacities (MBH) TWA1014*A heat pump with TWE1014*A air handler at 3350 CFM (IP)
Outdoor
Temp (°F)
Integrated Heating Capacity (MBH)
at Indicated Indoor Dry Bulb Temp (°F)
60
70
75
80
Total Power (kW)
at Indicated Indoor Dry Bulb Temp (°F)
60
70
75
80
-18
25.4
25.3
25.3
25.2
6.4
7.0
7.3
7.7
-13
29.8
29.6
29.5
29.3
6.5
7.1
7.5
7.8
-8
34.4
34.1
34.0
33.8
6.6
7.3
7.6
8.0
-3
39.2
38.8
38.6
38.3
6.8
7.4
7.8
8.1
2
44.1
43.6
43.3
43.0
6.9
7.5
7.9
8.3
7
49.2
48.6
48.2
48.0
7.0
7.7
8.0
8.4
12
54.3
53.6
53.2
52.8
7.1
7.8
8.1
8.5
17
59.9
59.1
58.5
58.0
7.2
7.9
8.3
8.6
22
65.8
64.7
64.1
63.5
7.3
8.0
8.4
8.7
27
71.9
70.6
70.0
69.3
7.4
8.1
8.5
8.8
32
78.5
77.0
76.3
75.4
7.5
8.2
8.6
8.9
37
84.9
83.1
82.2
81.3
7.6
8.3
8.6
9.0
42
91.5
89.5
88.5
87.5
7.7
8.4
8.7
9.1
47
98.5
96.1
95.0
93.8
7.8
8.4
8.8
9.2
52
105.6
103.0
101.7
100.3
7.8
8.5
8.9
9.3
57
112.7
109.8
108.3
106.7
7.9
8.6
8.9
9.3
62
119.6
116.2
114.5
112.8
8.0
8.6
9.0
9.4
67
126.9
123.2
121.4
119.5
8.1
8.7
9.1
9.5
72
134.9
130.8
128.8
126.8
8.2
8.9
9.3
9.6
Notes:
1. Net heating capacity and power include indoor fan heat at AHRI ESP. To obtain net heating at other conditions, subtract fan heat at this condition
and add fan heat at new condition.
2. Integrated heating capacities and power include the effects of defrost in the frost region. All heating capacities and power are at 70% outdoor
relative humidity and demand defrost cycle.
Table 51.
Gross heating capacities (kW) TWA1014*A heat pump with TWE1014*A air handler at 3350 CFM (SI)
Integrated Heating Capacity (kW)
at Indicated Indoor Dry Bulb Temp (°C)
15
21
24
27
Total Power (kW)
at Indicated Indoor Dry Bulb Temp (°C)
15
21
24
27
-28
7.4
7.4
7.4
7.4
6.4
7.0
7.3
7.7
-25
8.7
8.7
8.6
8.6
6.5
7.1
7.5
7.8
-22
10.1
10.0
10.0
9.9
6.6
7.3
7.6
8.0
-19
11.5
11.4
11.3
11.2
6.8
7.4
7.8
8.1
-17
12.9
12.8
12.7
12.6
6.9
7.5
7.9
8.3
-14
14.4
14.3
14.1
14.1
7.0
7.7
8.0
8.4
-11
15.9
15.7
15.6
15.5
7.1
7.8
8.1
8.5
-8
17.6
17.3
17.2
17.0
7.2
7.9
8.3
8.6
-6
19.3
19.0
18.8
18.6
7.3
8.0
8.4
8.7
-3
21.1
20.7
20.5
20.3
7.4
8.1
8.5
8.8
0
23.0
22.6
22.4
22.1
7.5
8.2
8.6
8.9
3
24.9
24.4
24.1
23.8
7.6
8.3
8.6
9.0
6
26.8
26.2
25.9
25.6
7.7
8.4
8.7
9.1
8
28.9
28.2
27.8
27.5
7.8
8.4
8.8
9.2
11
31.0
30.2
29.8
29.4
7.8
8.5
8.9
9.3
14
33.0
32.2
31.7
31.3
7.9
8.6
8.9
9.3
17
35.1
34.1
33.6
33.1
8.0
8.6
9.0
9.4
19
37.2
36.1
35.6
35.0
8.1
8.7
9.1
9.5
22
39.5
38.3
37.7
37.1
8.2
8.9
9.3
9.6
Outdoor
Temp (°C)
Notes:
1. Net heating capacity and power include indoor fan heat at AHRI ESP. To obtain net heating at other conditions, subtract fan heat at this condition
and add fan heat at new condition.
2. Integrated heating capacities and power include the effects of defrost in the frost region. All heating capacities and power are at 70% outdoor
relative humidity and demand defrost cycle.
SSP-PRC024J-EN
53
Performance Data
Table 52.
Gross heating capacities (MBH) TWA1014*D heat pump with TWE1014*B air handler at 3350 CFM (IP)
Integrated Heating Capacity (MBH)
at Indicated Indoor Dry Bulb Temp (°F)
Total Power (kW)
at Indicated Indoor Dry Bulb Temp (°F)
Outdoor
Temp (°F)
60
70
75
80
60
70
75
80
-18
23.1
22.5
22.2
21.6
5.9
6.4
6.7
7.1
-13
26.7
26.4
26.1
25.5
5.9
6.6
6.9
7.2
-8
31.0
30.6
30.2
29.6
6.1
6.7
7.0
7.4
-3
35.5
34.9
34.4
33.8
6.2
6.8
7.2
7.5
2
40.3
39.4
38.9
38.3
6.3
6.9
7.3
7.7
7
45.3
44.2
43.6
42.8
6.3
7.0
7.4
7.8
12
50.2
48.9
48.4
47.6
6.4
7.1
7.5
7.9
17
55.6
54.0
53.2
52.4
6.5
7.2
7.6
8.0
22
61.2
59.4
58.5
57.6
6.6
7.3
7.7
8.2
27
67.1
65.1
64.1
63.1
6.7
7.4
7.8
8.3
32
73.3
70.9
69.9
68.8
6.8
7.5
7.9
8.4
37
79.5
77.0
75.8
74.6
6.9
7.6
8.0
8.5
42
85.9
83.1
81.8
80.6
7.0
7.7
8.1
8.6
47
92.6
89.5
88.1
86.7
7.1
7.8
8.2
8.7
52
99.7
96.2
94.7
93.2
7.2
7.9
8.3
8.8
57
106.8
103.0
101.3
99.7
7.3
8.0
8.4
8.9
62
114.0
109.9
108.0
106.2
7.4
8.1
8.5
9.0
67
121.0
116.6
114.5
112.6
7.5
8.2
8.6
9.1
72
127.8
122.9
120.7
118.6
7.6
8.3
8.7
9.1
Notes:
1. Net heating capacity and power include indoor fan heat at AHRI ESP. To obtain net heating at other conditions, subtract fan heat at this condition
and add fan heat at new condition.
2. Integrated heating capacities and power include the effects of defrost in the frost region. All heating capacities and power are at 70% outdoor
relative humidity and demand defrost cycle.
Table 53.
Gross heating capacities (kW) TWA1014*D heat pump with TWE1014*B air handler at 3350 CFM (SI)
Integrated Heating Capacity (kW)
at Indicated Indoor Dry Bulb Temp (°C)
Total Power (kW)
at Indicated Indoor Dry Bulb Temp (°C)
Outdoor
Temp (°C)
15
21
24
27
15
21
24
27
-28
6.8
6.6
6.5
6.3
5.9
6.4
6.7
7.1
-25
7.8
7.7
7.7
7.5
5.9
6.6
6.9
7.2
-22
9.1
9.0
8.8
8.7
6.1
6.7
7.0
7.4
-19
10.4
10.2
10.1
9.9
6.2
6.8
7.2
7.5
-17
11.8
11.6
11.4
11.2
6.3
6.9
7.3
7.7
-14
13.3
12.9
12.8
12.6
6.3
7.0
7.4
7.8
-11
14.7
14.3
14.2
14.0
6.4
7.1
7.5
7.9
-8
16.3
15.8
15.6
15.4
6.5
7.2
7.6
8.0
-6
17.9
17.4
17.2
16.9
6.6
7.3
7.7
8.2
-3
19.7
19.1
18.8
18.5
6.7
7.4
7.8
8.3
0
21.5
20.8
20.5
20.2
6.8
7.5
7.9
8.4
3
23.3
22.6
22.2
21.9
6.9
7.6
8.0
8.5
6
25.2
24.4
24.0
23.6
7.0
7.7
8.1
8.6
8
27.1
26.2
25.8
25.4
7.1
7.8
8.2
8.7
11
29.2
28.2
27.7
27.3
7.2
7.9
8.3
8.8
14
31.3
30.2
29.7
29.2
7.3
8.0
8.4
8.9
17
33.4
32.2
31.7
31.1
7.4
8.1
8.5
9.0
19
35.5
34.2
33.6
33.0
7.5
8.2
8.6
9.1
22
37.5
36.0
35.4
34.8
7.6
8.3
8.7
9.1
Notes:
1. Net heating capacity and power include indoor fan heat at AHRI ESP. To obtain net heating at other conditions, subtract fan heat at this condition
and add fan heat at new condition.
2. Integrated heating capacities and power include the effects of defrost in the frost region. All heating capacities and power are at 70% outdoor
relative humidity and demand defrost cycle.
54
SSP-PRC024J-EN
Performance Data
Table 54.
Gross heating capacities (MBH) TWA1564*D heat pump with TWE1564*B air handler at 5000 CFM (IP)
Outdoor
Temp (°F)
Integrated Heating Capacity (MBH)
at Indicated Indoor Dry Bulb Temp (°F)
60
70
75
80
Total Power (kW)
at Indicated Indoor Dry Bulb Temp (°F)
60
70
75
80
-18
37.6
35.4
34.6
32.2
11.5
12.1
12.5
13.0
-13
44.0
40.8
39.3
38.2
11.2
12.2
12.7
13.3
-8
50.6
47.0
45.9
45.4
11.4
12.4
13.0
13.7
-3
57.2
54.3
53.6
53.0
11.6
12.7
13.4
14.0
2
64.3
62.3
61.5
60.7
11.8
13.0
13.7
14.3
7
73.3
70.8
69.8
69.0
12.2
13.3
14.0
14.7
12
82.1
79.7
78.6
77.6
12.4
13.6
14.3
15.0
17
92.3
89.1
87.8
86.7
12.7
13.9
14.6
15.3
22
101.9
99.1
97.5
96.3
13.0
14.2
14.9
15.6
27
112.6
109.5
107.8
106.3
13.3
14.5
15.2
15.9
32
124.2
120.4
118.6
116.9
13.6
14.8
15.5
16.2
37
135.3
131.4
129.5
127.6
13.9
15.1
15.8
16.5
42
147.5
143.1
141.0
139.0
14.2
15.4
16.1
16.8
47
160.3
155.7
153.5
151.3
14.5
15.8
16.5
17.2
52
174.0
169.0
166.6
164.2
14.9
16.1
16.8
17.6
57
188.1
182.8
180.2
177.6
15.2
16.5
17.2
17.9
62
202.8
197.1
194.3
191.6
15.6
16.9
17.6
18.3
67
217.3
211.9
208.9
206.0
16.1
17.3
18.0
18.8
72
231.9
227.1
223.9
220.9
16.6
17.8
18.5
19.3
Notes:
1. Net heating capacity and power include indoor fan heat at AHRI ESP. To obtain net heating at other conditions, subtract fan heat at this condition
and add fan heat at new condition.
2. Integrated heating capacities and power include the effects of defrost in the frost region. All heating capacities and power are at 70% outdoor
relative humidity and demand defrost cycle.
Table 55.
Gross heating capacities (kW) TWA1564*D heat pump with TWE1564*B air handler at 5000 CFM (SI)
Outdoor
Temp (°C)
Integrated Heating Capacity (kW)
at Indicated Indoor Dry Bulb Temp (°C)
15
21
24
27
Total Power (kW)
at Indicated Indoor Dry Bulb Temp (°C)
15
21
24
27
-28
10.6
10.3
9.7
9.3
9.7
10.2
10.7
11.3
-25
12.8
11.9
11.4
11.1
9.5
10.4
11.0
11.6
-22
14.6
13.6
13.2
13.0
9.7
10.7
11.2
11.9
-19
16.5
15.6
15.4
15.2
9.9
11.0
11.6
12.2
-17
18.5
17.9
17.7
17.4
10.1
11.3
11.9
12.5
-14
21.0
20.4
20.1
19.8
10.4
11.6
12.2
12.8
-11
23.6
23.0
22.6
22.3
10.7
11.9
12.5
13.1
-8
26.4
25.6
25.2
24.9
11.0
12.2
12.8
13.5
-6
29.3
28.4
28.0
27.7
11.3
12.5
13.1
13.8
-3
32.5
31.5
31.0
30.6
11.6
12.8
13.4
14.1
0
35.7
34.6
34.1
33.6
11.9
13.1
13.7
14.4
3
39.0
37.8
37.3
36.7
12.2
13.3
14.0
14.7
6
42.4
41.2
40.6
40.0
12.5
13.7
14.3
15.0
8
46.2
44.8
44.2
43.6
12.8
14.0
14.7
15.3
11
50.1
48.7
48.0
47.3
13.1
14.4
15.0
15.7
14
54.2
52.7
51.9
51.2
13.5
14.7
15.4
16.1
17
58.5
56.9
56.0
55.3
13.9
15.1
15.8
16.5
19
62.8
61.2
60.3
59.5
14.2
15.5
16.2
16.9
22
67.1
65.6
64.7
63.8
14.6
15.9
16.6
17.4
Notes:
1. Net heating capacity and power include indoor fan heat at AHRI ESP. To obtain net heating at other conditions, subtract fan heat at this condition
and add fan heat at new condition.
2. Integrated heating capacities and power include the effects of defrost in the frost region. All heating capacities and power are at 70% outdoor
relative humidity and demand defrost cycle.
SSP-PRC024J-EN
55
Performance Data
Table 56.
Gross heating capacities (MBH) TWA2014*D heat pump with TWE2014*B air handler at 6675 CFM (IP)
Outdoor
Temp (°F)
Integrated Heating Capacity (MBH)
at Indicated Indoor Dry Bulb Temp (°F)
60
70
75
80
Total Power (kW)
at Indicated Indoor Dry Bulb Temp (°F)
60
70
75
80
-18
52.8
47.6
44.0
40.8
13.2
14.3
14.7
15.5
-13
61.0
55.5
52.9
50.4
13.4
14.6
15.3
15.9
-8
70.1
64.4
61.6
59.0
13.6
15.0
15.6
16.4
-3
79.5
73.9
71.3
69.0
14.0
15.3
16.1
16.8
2
89.7
84.6
82.2
79.6
14.4
15.7
16.5
17.2
7
100.9
95.9
93.4
90.9
14.7
16.1
16.9
17.7
12
113.1
107.8
105.2
102.6
15.1
16.5
17.3
18.1
17
125.9
120.4
117.6
114.8
15.4
16.9
17.6
18.5
22
139.4
133.6
130.8
127.8
15.8
17.2
18.0
18.9
27
153.6
147.5
144.5
141.4
16.1
17.6
18.4
19.2
32
168.4
162.1
158.8
155.6
16.5
18.0
18.8
19.6
37
183.3
176.6
173.2
169.7
16.8
18.3
19.2
20.0
42
198.8
191.7
188.1
184.5
17.2
18.7
19.5
20.4
47
215.2
207.7
203.9
200.0
17.6
19.1
20.0
20.9
52
232.5
224.5
220.5
216.5
18.0
19.6
20.4
21.3
57
250.4
242.0
237.7
233.5
18.4
20.0
20.9
21.8
62
268.8
260.0
255.5
251.1
18.9
20.5
21.4
22.3
67
287.4
278.1
273.5
268.9
19.3
21.0
21.9
22.8
72
306.4
296.7
291.9
287.1
19.8
21.5
22.4
23.3
Notes:
1. Net heating capacity and power include indoor fan heat at AHRI ESP. To obtain net heating at other conditions, subtract fan heat at this condition
and add fan heat at new condition.
2. Integrated heating capacities and power include the effects of defrost in the frost region. All heating capacities and power are at 70% outdoor
relative humidity and demand defrost cycle.
Table 57.
Gross heating capacities (kW) TWA2014*D heat pump with TWE2014*B air handler at 6675 CFM (SI)
Outdoor
Temp (°C)
Integrated Heating Capacity (kW)
at Indicated Indoor Dry Bulb Temp (°C)
15
21
24
27
Total Power (kW)
at Indicated Indoor Dry Bulb Temp (°C)
15
21
24
27
-28
15.3
13.8
13.2
12.3
12.1
13.3
13.8
14.6
-25
17.6
16.0
15.1
14.5
12.4
13.6
14.1
14.9
-22
20.0
18.4
17.6
16.8
12.6
13.8
14.5
15.2
-19
22.6
21.0
20.1
19.5
12.9
14.1
14.8
15.6
-17
25.3
23.7
23.0
22.3
13.1
14.4
15.2
15.9
-14
28.2
26.7
26.0
25.3
13.4
14.8
15.5
16.3
-11
31.3
29.8
29.1
28.3
13.7
15.1
15.8
16.6
-8
34.6
33.1
32.3
31.5
13.9
15.3
16.1
16.9
-6
38.1
36.4
35.6
34.7
14.2
15.6
16.4
17.2
-3
41.7
39.9
39.0
38.1
14.5
15.9
16.7
17.5
0
45.4
43.5
42.6
41.6
14.8
16.2
17.0
17.8
3
49.1
47.1
46.1
45.1
15.1
16.5
17.3
18.1
6
52.9
50.8
49.7
48.6
15.4
16.9
17.6
18.4
8
57.2
55.0
53.8
52.7
15.8
17.2
18.0
18.8
11
61.1
58.7
57.5
56.4
16.1
17.6
18.3
19.2
14
65.5
63.0
61.7
60.5
16.5
18.0
18.7
19.6
17
70.0
67.4
66.0
64.7
16.9
18.4
19.2
20.0
19
74.6
71.8
70.4
69.0
17.4
18.8
19.6
20.4
22
79.2
76.3
74.8
73.4
17.8
19.3
20.1
20.9
Notes:
1. Net heating capacity and power include indoor fan heat at AHRI ESP. To obtain net heating at other conditions, subtract fan heat at this condition
and add fan heat at new condition.
2. Integrated heating capacities and power include the effects of defrost in the frost region. All heating capacities and power are at 70% outdoor
relative humidity and demand defrost cycle.
56
SSP-PRC024J-EN
Performance Data
Fan Performance
Table 58.
Evaporator fan performance — TWE051 — air handler (IP)
External Static Pressure (Inches of Water Gauge)
CFM
0.10"
0.20"
0.30"
0.40"
0.50"
0.60"
0.70"
0.80"
0.90"
1.00"
1.10"
RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP
1 HP High Static Motor
0.5 HP Standard Motor
1400
612 0.20 674 0.24 731 0.29 786 0.34 840 0.39 891 0.45 941 0.51 989 0.58 1034 0.65 1077 0.72 1117 0.78
1500
647 0.24 705 0.29 760 0.34 812 0.39 863 0.44 912 0.50 960 0.56 1006 0.63 1051 0.70 1094 0.77
—
—
1600
683 0.28 738 0.33 790 0.38 840 0.44 888 0.50 936 0.56 980 0.62 1025 0.69 1070 0.76 1111 0.83
—
—
1700
719 0.33 771 0.38 821 0.44 869 0.50 914 0.56 959 0.62 1003 0.68 1047 0.75 1089 0.82
—
—
—
—
1800
756 0.39 804 0.44 853 0.50 898 0.56 942 0.62 985 0.69 1028 0.75 1068 0.82 1109 0.89
—
—
—
—
1900
792 0.45 838 0.51 884 0.57 928 0.63 971 0.69 1012 0.76 1052 0.83 1092 0.90
—
—
—
—
—
—
2000
829 0.52 873 0.58 917 0.64 959 0.71 1000 0.77 1040 0.84 1079 0.91 1117 0.98
—
—
—
—
—
—
2100
866 0.60 908 0.66 950 0.72 991 0.79 1030 0.86 1069 0.93 1106 1.00 1144 1.08
—
—
—
—
—
—
Notes:
1. Data includes pressure drop due to wet coil and 1" filter.
2. Fan motor heat (MBh) = 3.15 x BHP.
3. Factory supplied motors, in commercial equipment, are definite purpose motors, specifically designed and tested to operate reliably and
continuously at all cataloged conditions. Using the full rsepower range of our fan motors as shown in our tabular data will not result in nuisance tripping
or premature motor failure. Our product's warranty will not be affected.
Table 59.
Evaporator fan performance — TWE051 — air handler (SI)
External Static Pressure (Pascals)
25
50
75
100
125
150
174
199
224
249
274
m3/hr RPM kW RPM kW RPM kW RPM kW RPM kW RPM kW RPM kW RPM kW RPM kW RPM kW RPM kW
0.38 kW Standard Motor
.75 kW High Static Motor
2379
612 0.15 674 0.18 731 0.22 786 0.25 840 0.29 891 0.34 941 0.38 989 0.43 1034 0.48 1077 0.53 1117 0.58
2549
647 0.18 705 0.21 760 0.25 812 0.29 863 0.33 912 0.37 960 0.42 1006 0.47 1051 0.52 1094 0.58
—
—
2719
683 0.21 738 0.25 790 0.29 840 0.33 888 0.37 936 0.42 980 0.46 1025 0.51 1070 0.57 1111 0.62
—
—
2889
719 0.25 771 0.29 821 0.33 869 0.37 914 0.41 959 0.46 1003 0.51 1047 0.56 1089 0.61
—
—
—
—
3059
756 0.29 804 0.33 853 0.37 898 0.42 942 0.46 985 0.51 1028 0.56 1068 0.61 1109 0.66
—
—
—
—
3228
792 0.34 838 0.38 884 0.42 928 0.47 971 0.52 1012 0.57 1052 0.62 1092 0.67
—
—
—
—
—
—
3398
829 0.39 873 0.43 917 0.48 959 0.53 1000 0.58 1040 0.63 1079 0.68 1117 0.73
—
—
—
—
—
—
3568
866 0.45 908 0.49 950 0.54 991 0.59 1030 0.64 1069 0.69 1106 0.75 1144 0.80
—
—
—
—
—
—
Notes:
1. Data includes pressure drop due to wet coil and 1" filter.
2. Fan motor heat (kW) = 1.238 x kW.
3. Factory supplied motors, in commercial equipment, are definite purpose motors, specifically designed and tested to operate reliably and
continuously at all cataloged conditions. Using the full horsepower range of our fan motors as shown in our tabular data will not result in nuisance
tripping or premature motor failure. Our product's warranty will not be affected.
SSP-PRC024J-EN
57
Performance Data
Table 60.
Evaporator fan performance — TWE072 — air handler (IP)
External Static Pressure (Inches of Water Gauge)
0.10"
0.20"
0.30"
0.40"
0.50"
0.60"
0.70"
0.80"
0.90"
1.00"
1.10"
CFM RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP
1.5 HP High Static Motor
1 HP Standard Motor
1600
—
—
—
—
550 0.33 629 0.39 695 0.46 747 0.52 807 0.72 854 0.77 887 0.80 906 0.81 912 0.82
1700
—
—
—
—
559 0.35 634 0.43 697 0.48 751 0.61 809 0.75 857 0.81 894 0.84 920 0.87 985 1.07
1800
—
—
—
—
569 0.38 640 0.46 701 0.53 756 0.64 813 0.77 861 0.85 901 0.90 952 1.07 991 1.14
1900
—
—
—
—
578 0.41 647 0.50 707 0.58 761 0.68 817 0.81 866 0.90 912 1.01 957 1.13 996 1.21
2000
—
—
522 0.34 590 0.45 654 0.52 711
2100
—
—
534 0.38 599 0.48 662 0.59 719 0.67 774 0.77 826 0.88 875 1.00 921 1.11 968 1.27 1007 1.35
1
768 0.73 821 0.84 870 0.95 917 1.06 962 1.20 1002 1.27
2200 474 0.30 547 0.43 610 0.52 671 0.64 727 0.72 781 0.82 832 0.93 881 1.06 926 1.17 973 1.33 1013 1.42
2300 489 0.35 560 0.47 621 0.56 680 0.69 736 0.77 788 0.87 838 0.98 886 1.12 932 1.23 979 1.40 1018 1.50
2400 505 0.41 573 0.52 632 0.61 690 0.74 745 0.83 796 0.93 844 1.04 893 1.18 937 1.30 969 1.47 1023 1.57
External Static Pressure (Inches of Water Gauge)
1.20"
1.30"
1.40"
1.50"
1.60"
1.70"
CFM RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP
2 HP Ultra High Static Motor
1600 1018 1.09 1060 1.21 1094 1.29
—
—
—
—
—
—
1700 1024 1.16 1065 1.28 1099 1.37
—
—
—
—
—
—
1800 1029 1.24 1070 1.35 1105 1.45
—
—
—
—
—
—
1900 1035 1.31 1075 1.42 1110 1.53
—
—
—
—
—
—
2000 1040 1.38 1080 1.50 1116 1.61
—
—
—
—
—
—
2100 1046 1.46 1085 1.58 1122 1.69
—
—
—
—
—
—
2200 1052 1.54 1090 1.66
—
—
—
—
—
—
—
—
2300 1057 1.62 1095 1.74
—
—
—
—
—
—
—
—
2400 1063 1.70 1101 1.82
—
—
—
—
—
—
—
—
Notes:
1. Data includes pressure drop due to wet coil and 1" filter.
2. Fan motor heat (MBh) = 3.15 x BHP.
3. Factory supplied motors, in commercial equipment, are definite purpose motors, specifically designed and tested to operate reliably and
continuously at all cataloged conditions. Using the full horsepower range of our fan motors as shown in our tabular data will not result in nuisance
tripping or premature motor failure. Our product's warranty will not be affected.
58
SSP-PRC024J-EN
Performance Data
Table 61.
Evaporator fan performance — TWE072 — air handler (SI)
External Static Pressure (Pascals)
25
50
75
100
125
150
174
199
224
249
274
m3/hr RPM kW RPM kW RPM kW RPM kW RPM kW RPM kW RPM kW RPM kW RPM kW RPM kW RPM kW
.75 kW Standard Motor
1.12 kW High Static Motor
1.5 kW Ultra High Static Motor
2718
—
—
—
—
550 0.25 629 0.29 695 0.34 747 0.39 807 0.54 854 0.58 887 0.60 906 0.61 912 0.61
2888
—
—
—
—
559 0.26 634 0.32 697 0.36 751 0.45 809 0.56 857 0.61 894 0.62 920 0.65 985 0.80
3058
—
—
—
—
569 0.29 640 0.34 701 0.39 756 0.48 813 0.58 861 0.64 901 0.67 952 0.80 991 0.85
3228
—
—
—
—
578 0.31 647 0.37 707 0.43 761 0.51 817 0.60 866 0.67 912 0.75 957 0.84 996 0.90
3398
—
—
522 0.26 590 0.34 654 0.39 711 0.46 768 0.54 821 0.63 870 0.71 917 0.79 962 0.89 1002 0.95
—
—
534 0.29 599 0.36 662 0.44 719 0.50 774 0.57 826 0.66 875 0.75 921 0.83 968 0.94 1007 1.01
3568
3738
474 0.22 547 0.32 610 0.39 671 0.47 727 0.54 781 0.61 832 0.69 881 0.79 926 0.87 973 1.00 1013 1.06
3908
489 0.26 560 0.35 621 0.42 680 0.51 736 0.58 788 0.65 838 0.73 886 0.83 932 0.92 979 1.05 1018 1.12
4078
505 0.30 573 0.39 632 0.46 690 0.55 745 0.62 796 0.69 844 0.78 893 0.88 937 0.97 969 1.10 1023 1.17
External Static Pressure (Pascals)
299
324
349
m3/hr RPM kW RPM kW RPM kW
1.5 kW Ultra High Static Motor
2718
1018 0.81 1060 0.90 1094 0.96
2888
1024 0.87 1065 0.95 1099 1.02
3058
1029 0.92 1070 1.00 1105 1.08
3228
1035 0.98 1075 1.06 1110 1.14
3398
1040 1.03 1080 1.12 1116 1.20
3568
1046 1.09 1085 1.18 1122 1.26
3738
1052 1.15 1090 1.24
—
—
3908
1057 1.21 1095 1.30
—
—
4078
1063 1.27 1101 1.36
—
—
Notes:
1. Data includes pressure drop due to wet coil and 1" filter.
2. Fan motor heat (kW) = 1.238 x kW.
3. Factory supplied motors, in commercial equipment, are definite purpose motors, specifically designed and tested to operate reliably and
continuously at all cataloged conditions. Using the full horsepower range of our fan motors as shown in our tabular data will not result in nuisance
tripping or premature motor failure. Our product's warranty will not be affected.
SSP-PRC024J-EN
59
Performance Data
Table 62.
Evaporator fan performance — TWE076 — air handler (IP)
External Static Pressure (Inches of Water Gauge)
0.10"
0.20"
0.30"
0.40"
0.50"
0.60"
0.70"
0.80"
0.90"
1.00"
1.10"
CFM RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP
1.5 HP High Static Motor
1 HP Standard Motor
2 HP Ultra High Static Motor
2000
—
—
522 0.34 590 0.44 654 0.52 711 0.62 768 0.73 821 0.84 870 0.95 916 1.06 959 1.16 1001 1.27
2125
—
—
537 0.39 604 0.48 664 0.58 721 0.68 775 0.78 828 0.90 877 1.01 923 1.13 966 1.25 1009 1.36
2250 481 0.33 553 0.44 617 0.53 675 0.64 731 0.74 784 0.84 834 0.96 884 1.09 929 1.21 973 1.33 1016 1.46
2375 501 0.39 569 0.49 631 0.59 688 0.70 742 0.81 794 0.91 842 1.03 891 1.16 937 1.29 981 1.42 1022 1.55
2500 521 0.47 585 0.55 646 0.65 701 0.77 754 0.89 804 0.99 852 1.11 898 1.23 944 1.37 987 1.51 1028 1.64
2625 540 0.53 602 0.61 661 0.72 715 0.84 767 0.97 816 1.08 862 1.19 908 1.32 950 1.45 994 1.60 1036 1.74
2750 559 0.60 619 0.66 677 0.80 729 0.91 780 1.05 827 1.17 872 1.29 916 1.41 960 1.55 1001 1.69 1043 1.84
2875 579 0.67 636 0.72 692 0.88 744 1.00 793 1.13 840 1.27 885 1.40 928 1.52 969 1.65 1009 1.79 1049 1.94
3000 599 0.74 654 0.79 709 0.96 760 1.09 807 1.22 852 1.36 896 1.51 939 1.63 980 1.76 1019 1.90 1057 2.05
External Static Pressure (Inches of Water Gauge)
1.20"
1.30"
1.40"
1.50"
1.60"
1.70"
CFM RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP
2 HP Ultra High Static Motor
2000 1040 1.38 1080 1.50 1116 1.61
—
—
—
—
—
2125 1048 1.48 1085 1.59 1123 1.71
—
—
—
—
—
—
—
2250 1054 1.58 1093 1.70
—
—
—
—
—
—
—
—
2375 1062 1.68 1099 1.80
—
—
—
—
—
—
—
—
2500 1068 1.78 1107 1.92
—
—
—
—
—
—
—
—
2625 1075 1.88 1113 2.02
—
—
—
—
—
—
—
—
2750 1083 1.99
—
—
—
—
—
—
—
—
—
—
2875 1090 2.10
—
—
—
—
—
—
—
—
—
—
3000 1097 2.21
—
—
—
—
—
—
—
—
—
—
Notes:
1. Data includes pressure drop due to wet coil and 1" filter.
2. Fan motor heat (MBh) = 3.15 x BHP.
3. Factory supplied motors, in commercial equipment, are definite purpose motors, specifically designed and tested to operate reliably and
continuously at all cataloged conditions. Using the full horsepower range of our fan motors as shown in our tabular data will not result in nuisance
tripping or premature motor failure. Our product's warranty will not be affected.
60
SSP-PRC024J-EN
Performance Data
Table 63.
Evaporator fan performance — TWE076 — air handler (SI)
External Static Pressure (Pascals)
25
50
75
100
125
150
174
199
224
249
274
m3/hr RPM kW RPM kW RPM kW RPM kW RPM kW RPM kW RPM kW RPM kW RPM kW RPM kW RPM kW
.75 kW Standard Motor
3398
3611
1.12 kW High Static Motor
1.5 kW Ultra High Static Motor
—
0.18 522 0.25 590 0.33 654 0.39 711 0.46 768 0.54 821 0.62 870 0.71 916 0.79 959 0.87 1001 0.95
—
0.21 537 0.29 604 0.36 664 0.43 721 0.50 775 0.58 828 0.67 877 0.76 923 0.84 966 0.93 1009 1.02
3823
481 0.24 553 0.32 617 0.40 675 0.48 731 0.55 784 0.63 834 0.72 884 0.81 929 0.90 973 0.99 1016 1.09
4036
501 0.29 569 0.36 631 0.44 688 0.53 742 0.60 794 0.68 842 0.77 891 0.87 937 0.96 981 1.06 1022 1.15
4248
521 0.35 585 0.41 646 0.49 701 0.57 754 0.66 804 0.74 852 0.83 898 0.92 944 1.02 987 1.12 1028 1.22
4460
540 0.40 602 0.46 661 0.54 715 0.62 767 0.72 816 0.81 862 0.89 908 0.99 950 1.08 994 1.19 1036 1.30
4673
559 0.45 619 0.50 677 0.59 729 0.68 780 0.78 827 0.88 872 0.96 916 1.05 960 1.15 1001 1.26 1043 1.37
4885
579 0.50 636 0.54 692 0.65 744 0.74 793 0.84 840 0.95 885 1.04 928 1.13 969 1.23 1009 1.33 1049 1.45
5098
599 0.55 654 0.59 709 0.72 760 0.81 807 0.91 852 1.02 896 1.12 939 1.22 980 1.32 1019 1.42 1057 1.53
External Static Pressure (Pascals)
299
324
349
m3/hr RPM kW RPM kW RPM kW
1.5 kW Ultra High Static Motor
3398
1040 1.03 1080 1.12 1116 1.20
3611
1048 1.10 1085 1.19 1123 1.28
3823
1054 1.18 1093 1.27
—
—
4036
1062 1.25 1099 1.35
—
—
4248
1068 1.33 1107 1.43
—
—
4460
1075 1.40 1113 1.51
—
—
4673
1083 1.49
—
—
—
—
4885
1090 1.57
—
—
—
—
5098
1097 1.65
—
—
—
—
Notes:
1. Data includes pressure drop due to wet coil and 1" filter.
2. Fan motor heat (kW) = 1.238 x kW.
3. Factory supplied motors, in commercial equipment, are definite purpose motors, specifically designed and tested to operate reliably and
continuously at all cataloged conditions. Using the full horsepower range of our fan motors as shown in our tabular data will not result in nuisance
tripping or premature motor failure. Our product's warranty will not be affected.
SSP-PRC024J-EN
61
Performance Data
Table 64.
Evaporator fan performance — TWE101 — air handler (IP)
External Static Pressure (Inches of Water Gauge)
0.10"
0.20"
0.30"
0.40"
0.50"
0.60"
0.70"
0.80"
0.90"
1.00"
1.10"
CFM RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP
2 HP High Static Motor
1.5 HP Standard Motor
2600
—
—
2775
—
—
499 0.55 541 0.62 580 0.69 617 0.78 653 0.86 687 0.93 719 1.01 750 1.09 782 1.18 812 1.27
—
—
523 0.53 563 0.61 601 0.69 638 0.75 673 0.83 707 0.91 739 0.99 772 1.08 802 1.17
2950
—
—
519 0.63 560 0.71 598 0.79 634 0.87 668 0.96 701 1.05 732 1.12 763 1.21 793 1.30 822 1.39
3125 499 0.70 540 0.71 579 0.82 616 0.90 651 0.98 684 1.08 716 1.17 747 1.26 777 1.34 805 1.42 834 1.52
3300 522 0.81 561 0.81 600 0.94 635 1.02 669 1.10 701 1.20 731 1.30 762 1.40 791 1.49 819 1.57 847 1.66
3475 545 0.93 582 0.93 620 1.07 654 1.15 687 1.24 718 1.33 748 1.43 777 1.54 806 1.65 834 1.74 860 1.83
3650 568 1.05 604 1.09 640 1.18 674 1.30 706 1.39 736 1.48 766 1.58 794 1.69 821 1.81 848 1.91 874 2.01
3825 592 1.19 628 1.27 661 1.30 694 1.46 725 1.55 754 1.65 783 1.75 810 1.85 838 1.98 864 2.09 890 2.20
4000 615 1.34 652 1.47 682 1.45 714 1.63 745 1.73 774 1.83 801 1.93 829 2.04 855 2.16 880 2.28
—
—
External Static Pressure (Inches of Water Gauge)
1.20"
1.30"
1.40"
1.50"
1.60"
1.70"
1.80"
1.90"
CFM RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP
2 HP High Static Motor w/ Field Supplied Sheave & Belt
2600 832 1.25 860 1.34 887 1.43 914 1.52 939
1.6
964 1.69 988 1.77 1011 1.86
2775 841 1.37 870 1.46 897 1.56 923 1.65 949 1.74 973 1.83 997 1.93 1020 2.02
2950 851 1.49 879 1.59 906 1.69 932 1.79 958 1.89 983 1.99 1006 2.08 1030 2.18
3125 861 1.61 889 1.72 916 1.82 943 1.93 967 2.04 992 2.14 1016 2.25 1040 2.36
3300 873 1.76 900 1.86 926 1.97 951 2.08 977 2.19 1002 2.31
—
—
—
3475 886 1.92 912 2.02 938 2.13 962 2.24
—
—
—
—
—
—
—
—
—
3650 900 2.10 926 2.20 950 2.31
—
—
—
—
—
—
—
—
—
—
3825
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
4000
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
Notes:
1. Data includes pressure drop due to wet coil and 1" filter.
2. Fan motor heat (MBh) = 3.15 x BHP.
3. Factory supplied motors, in commercial equipment, are definite purpose motors, specifically designed and tested to operate reliably and
continuously at all cataloged conditions. Using the full horsepower range of our fan motors as shown in our tabular data will not result in nuisance
tripping or premature motor failure. Our product's warranty will not be affected.
62
SSP-PRC024J-EN
Performance Data
Table 65.
Evaporator fan performance — TWE101 — air handler (SI)
External Static Pressure (Pascals)
25
50
75
100
125
150
174
199
224
249
274
m3/hr RPM kW RPM kW RPM kW RPM kW RPM kW RPM kW RPM kW RPM kW RPM kW RPM kW RPM kW
1.12 kW High Static Motor
1.12 kW Standard Motor
4418
—
—
4715
—
—
499 0.41 541 0.46 580 0.52 617 0.58 653 0.64 687 0.69 719 0.75 750 0.81 782 0.88 812 0.95
—
—
519 0.47 560 0.53 598 0.59 634 0.65 668 0.72 701 0.78 732 0.84 763 0.90 793 0.97 822 1.03
5013
—
—
523 0.40 563 0.45 601 0.51 638 0.56 673 0.62 707 0.68 739 0.74 772 0.80 802 0.87
5310
499 0.52 540 0.53 579 0.61 616 0.67 651 0.73 684 0.80 716 0.88 747 0.94 777 1.00 805 1.06 834 1.13
5607
522 0.60 561 0.60 600 0.70 635 0.76 669 0.82 701 0.89 731 0.97 762 1.04 791 1.11 819 1.17 847 1.24
5905
545 0.69 582 0.70 620 0.80 654 0.86 687 0.92 718 0.99 748 1.07 777 1.15 806 1.23 834 1.30 860 1.36
6202
568 0.79 604 0.81 640 0.88 674 0.97 706 1.03 736 1.10 766 1.18 794 1.26 821 1.35 848 1.43 874 1.50
6499
592 0.89 628 0.95 661 0.97 694 1.09 725 1.16 754 1.23 783 1.30 810 1.38 838 1.47 864 1.56 890 1.64
6797
615 1.00 652 1.10 682 1.08 714 1.22 745 1.29 774 1.36 801 1.44 829 1.52 855 1.61 880 1.70 905 1.79
External Static Pressure (Pascals)
299
324
349
374
398
423
448
473
m3/hr RPM kW RPM kW RPM kW RPM kW RPM kW RPM kW RPM kW RPM kW
1.12 kW High Static Motor w/ Field Supplied Sheave & Belt
4418
832 0.93 860 1.00 887 1.06 914 1.13 939 1.19 964 1.26 988 1.32 1011 1.39
4715
841 1.02 870 1.09 897 1.16 923 1.23 949 1.30 973 1.37 997 1.44 1020 1.50
5013
851 1.11 879 1.18 906 1.26 932 1.33 958 1.41 983 1.48 1006 1.55 1030 1.63
5310
861 1.20 889 1.28 916 1.36 943 1.44 967 1.52 992 1.60 1016 1.68 1040 1.76
5607
873 1.31 900 1.39 926 1.47 951 1.55 977 1.63 1002 1.72
—
—
—
—
5905
886 1.43 912 1.51 938 1.59 962 1.67 986 1.75
—
—
—
—
—
—
6202
900 1.57 926 1.64 950 1.72 975 1.81 998 1.89
—
—
—
—
—
—
6499
915 1.72 939 1.79 963 1.87 987 1.95 1010 2.04
—
—
—
—
—
—
6797
929 1.88 953 1.96 977 2.03 1000 2.11 1023 2.20
—
—
—
—
—
—
Notes:
1. Data includes pressure drop due to wet coil and 1" filter.
2. Fan motor heat (kW) = 1.238 x kW.
3. Factory supplied motors, in commercial equipment, are definite purpose motors, specifically designed and tested to operate reliably and
continuously at all cataloged conditions. Using the full horsepower range of our fan motors as shown in our tabular data will not result in nuisance
tripping or premature motor failure. Our product's warranty will not be affected.
SSP-PRC024J-EN
63
Performance Data
Table 66.
Evaporator fan performance —TWE126 — air handler (IP)
External Static Pressure (Inches of Water Gauge)
0.10"
0.20"
0.30"
0.40"
0.50"
0.60"
0.70"
0.80"
0.90"
1.00"
1.10"
CFM RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP
1.5 HP Standard Motor w/
2 HP High Static
Field Supplied Sheave & Belt
1.5 HP Standard Motor
Motor
3200
—
—
3400
—
—
472 0.46 528 0.57 578 0.69 617 0.80 650 0.89 686 1.00 724 1.13 762 1.27 800 1.42 834 1.57
—
—
515 0.51 565 0.63 601 0.71 638 0.81 678 0.93 718 1.06 759 1.21 794 1.35 826 1.49
3600
—
—
486 0.51 541 0.63 590 0.76 633 0.89 666 0.98 697 1.08 732 1.20 767 1.34 804 1.49 840 1.65
3800
—
—
500 0.57 554 0.70 601 0.82 646 0.97 682 1.09 712 1.19 742 1.29 776 1.43 810 1.57 843 1.72
4000
—
—
515 0.64 567 0.78 614 0.91 658 1.05 698 1.20 728 1.31 756 1.41 786 1.53 817 1.66 849 1.82
4200 477 0.58 531 0.71 581 0.85 627 1.00 669 1.13 710 1.29 744 1.43 772 1.55 799 1.65 827 1.78 858 1.93
4400 494 0.65 546 0.79 595 0.94 640 1.09 682 1.23 722 1.39 758 1.55 789 1.69 814 1.80 840 1.92 867 2.05
4600 513 0.73 563 0.87 609 1.03 653 1.19 695 1.34 732 1.48 771 1.66 804 1.83 831 1.96 856 2.08 880 2.20
4800 531 0.82 579 0.96 624 1.13 667 1.29 707 1.45 745 1.60 783 1.77 817 1.96 847 2.12 872 2.25 896 2.37
External Static Pressure (Inches of Water Gauge)
1.20"
1.30"
1.40"
1.50"
1.60"
1.70"
CFM RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP
2 HP High Static
3 HP Ultra High Static Motor
Motor
3200 857 1.63 887 1.78 916 1.93 943 2.08 970 2.23 996 2.39
3400 865 1.72 895 1.88 924 2.03 952 2.19 978 2.35 1003 2.50
3600 873 1.81 903 1.97 931 2.13 959 2.29 986 2.46 1012 2.62
3800 877 1.89 912 2.08 940 2.24 967 2.41 994 2.58
—
—
4000 882 1.98 915 2.16 947 2.34 976 2.53 1002 2.70
—
—
4200 888 2.08 919 2.25 950 2.44 980 2.63 1010 2.82
—
—
4400 896 2.20 925 2.37 955 2.55 985 2.73 1013 2.92
—
—
4600 906 2.34 934 2.50 961 2.67 989 2.85
—
—
—
—
4800 918 2.50 944 2.65 970 2.81 996 2.98
—
—
—
—
Notes:
1. Data includes pressure drop due to wet coil and 1" filter.
2. Fan motor heat (MBh) = 3.15 x BHP.
3. Factory supplied motors, in commercial equipment, are definite purpose motors, specifically designed and tested to
operate reliably and continuously at all cataloged conditions. Using the full horsepower range of our fan motors as shown
in our tabular data will not result in nuisance tripping or premature motor failure. Our product's warranty will not be
affected.
64
SSP-PRC024J-EN
Performance Data
Table 67.
Evaporator fan performance — TWE126 — air handler (SI)
External Static Pressure (Pascals)
25
50
75
100
125
150
174
199
224
249
274
m3/hr RPM kW RPM kW RPM kW RPM kW RPM kW RPM kW RPM kW RPM kW RPM kW RPM kW RPM kW
1.12 kW Standard Motor w/ 1.49 kW High Static
1.12 kW Standard Motor
Field Supplied Sheave & Belt
Motor
5437
—
—
5777
—
—
472 0.34 528 0.42 578 0.52 617 0.60 650 0.66 686 0.74 724 0.84 762 0.94 800 1.06 834 1.17
—
—
515 0.38 565 0.47 601 0.53 638 0.60 678 0.69 718 0.79 759 0.90 794 1.01 826 1.11
6117
—
—
486 0.38 541 0.47 590 0.56 633 0.66 666 0.73 697 0.81 732 0.90 767 1.00 804 1.11 840 1.23
6457
—
—
500 0.43 554 0.52 601 0.61 646 0.72 682 0.81 712 0.89 742 0.97 776 1.06 810 1.17 843 1.29
6797
—
—
515 0.48 567 0.58 614 0.68 658 0.78 698 0.89 728 0.98 756 1.05 786 1.14 817 1.24 849 1.35
7137
477 0.43 531 0.53 581 0.64 627 0.74 669 0.84 710 0.96 744 1.07 772 1.15 799 1.23 827 1.33 858 1.44
7476
494 0.48 546 0.59 595 0.70 640 0.81 682 0.92 722 1.03 758 1.16 789 1.26 814 1.34 840 1.43 867 1.53
7816
513 0.54 563 0.65 609 0.77 653 0.88 695 1.00 732 1.10 771 1.24 804 1.36 831 1.46 856 1.55 880 1.64
8156
531 0.61 579 0.72 624 0.84 667 0.96 707 1.08 745 1.19 783 1.32 817 1.46 847 1.58 872 1.68 896 1.77
External Static Pressure (Pascals)
299
324
349
374
398
423
m3/hr RPM kW RPM kW RPM kW RPM kW RPM kW RPM kW
1.49 kW High Static
2.24 kW Ultra High Static Motor
Motor
5437
857 1.22 887 1.33 916 1.44 943 1.55 970 1.66 996 1.78
5777
865 1.29 895 1.40 924 1.51 952 1.63 978 1.75 1003 1.87
6117
873 1.35 903 1.47 931 1.59 959 1.71 986 1.83 1012 1.96
6457
877 1.41 912 1.55 940 1.67 967 1.80 994 1.92
—
—
6797
882 1.48 915 1.61 947 1.75 976 1.88 1002 2.01
—
—
7137
888 1.55 919 1.68 950 1.82 980 1.96 1010 2.11
—
—
7476
896 1.64 925 1.76 955 1.90 985 2.04 1013 2.18
—
—
7816
906 1.74 934 1.86 961 1.99 989 2.12
—
—
—
—
8156
918 1.86 944 1.97 970 2.10 996 2.22
—
—
—
—
Notes:
1. Data includes pressure drop due to wet coil and 1" filter.
2. Fan motor heat (kW) = 1.238 x kW.
3. Factory supplied motors, in commercial equipment, are definite purpose motors, specifically designed and tested to
operate reliably and continuously at all cataloged conditions. Using the full horsepower range of our fan motors as shown in
our tabular data will not result in nuisance tripping or premature motor failure. Our product's warranty will not be affected.
SSP-PRC024J-EN
65
Performance Data
Table 68.
Evaporator fan performance —TWE156 — air handler (IP)
External Static Pressure (Inches of Water Gauge)
0.10"
0.20"
0.30"
0.40"
0.50"
0.60"
0.70"
0.80"
0.90"
1.00"
1.10"
CFM RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP
1.5 HP Standard Motor w/
2 HP Standard Motor w/ Field Supplied
2 HP High Static
Field Supplied Sheave & Belt
Sheave & Belt
Motor
4000 428
0.5
482 0.62 531 0.72 576 0.84 621 0.98 663 1.11 701 1.25 737 1.38 771 1.51 803 1.64 833 1.77
4250 448 0.58 499 0.71 546 0.82 590 0.94 633 1.08 674 1.22 712 1.37 748 1.51 782 1.65 814 1.79 845 1.93
4500 468 0.68 517 0.81 563 0.93 605 1.05 646 1.19 686 1.34 724 1.50 760 1.65 793 1.80 825 1.95 855 2.09
4750 488 0.78 535 0.91 579 1.06 621 1.18 660 1.32 698 1.46 735 1.63 772 1.79 805 1.95 837 2.11 867 2.27
5000 509 0.90 554 1.03 596 1.19 637 1.32 675 1.46 712 1.61 748 1.77 783 1.94 817 2.11 848 2.28 878 2.44
5250 530 1.02 573 1.16 614 1.32 653 1.47 691 1.61 726 1.76 760 1.92 795 2.10 828 2.28 859 2.45 890 2.64
5500 551 1.16 593 1.31 632 1.47 670 1.64 706 1.78 741 1.93 774 2.09 807 2.26 840 2.46 871 2.64 902 2.83
5750 572 1.32 612 1.47 651 1.63 687 1.81 722 1.97 757 2.12 789 2.28 821 2.45 852 2.64 883 2.84 912 3.03
6000 593 1.48 632 1.64 670 1.81 705 1.99 739 2.17 772 2.32 804 2.48 835 2.66 865 2.84 895 3.04 924 3.24
External Static Pressure (Inches of Water Gauge)
1.20"
1.30"
1.40"
1.50"
1.60"
1.70"
CFM RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP
2 HP High Static
3 HP Ultra High Static Motor
Motor
4000 863
1.9
891 2.03 919 2.15 944 2.28 970 2.40 994 2.53
4250 874 2.07 902 2.20 928 2.33 955 2.47 981 2.61 1004 2.74
4500 884 2.24 913 2.38 939 2.53 966 2.68 991 2.82 1015 2.96
4750 895 2.42 924 2.58 951 2.74 977 2.88 1002 3.04
—
—
5000 907 2.61 934 2.77 962 2.94
—
—
—
—
—
—
5250 918 2.81 946 2.98 973 3.16
—
—
—
—
—
—
5500 931 3.02 958 3.20
—
—
—
—
—
—
—
—
5750 941 3.23
—
—
—
—
—
—
—
—
—
—
6000
—
—
—
—
—
—
—
—
—
—
—
—
Notes:
1. Data includes pressure drop due to wet coil and 1" filter.
2. Fan motor heat (MBh) = 3.15 x BHP.
3. Factory supplied motors, in commercial equipment, are definite purpose motors, specifically designed and tested to
operate reliably and continuously at all cataloged conditions. Using the full horsepower range of our fan motors as shown
in our tabular data will not result in nuisance tripping or premature motor failure. Our product's warranty will not be
affected.
66
SSP-PRC024J-EN
Performance Data
Table 69.
Evaporator fan performance — TWE156 — air handler (SI)
External Static Pressure (Pascals)
25
50
75
100
125
150
174
199
224
249
274
m3/hr RPM kW RPM kW RPM kW RPM kW RPM kW RPM kW RPM kW RPM kW RPM kW RPM kW RPM kW
1.49 kW Standard Motor w/
2.24 kW High Static Motor
1.49 kW Standard Motor
Field Supplied Sheave & Belt
6797
428 0.37 482 0.46 531 0.54 576 0.63 621 0.73 663 0.83 701 0.93 737 1.03 771 1.13 803 1.22 833 1.32
7222
448 0.43 499 0.53 546 0.61 590 0.70 633 0.80 674 0.91 712 1.02 748 1.13 782 1.23 814 1.33 845 1.44
7646
468 0.50 517 0.60 563 0.70 605 0.79 646 0.89 686 1.00 724 1.12 760 1.23 793 1.34 825 1.45 855 1.56
8071
488 0.58 535 0.68 579 0.79 621 0.88 660 0.98 698 1.09 735 1.21 772 1.34 805 1.46 837 1.57 867 1.69
8496
509 0.67 554 0.77 596 0.88 637 0.99 675 1.09 712 1.20 748 1.32 783 1.45 817 1.58 848 1.70 878 1.82
8921
530 0.76 573 0.87 614 0.99 653 1.10 691 1.20 726 1.31 760 1.43 795 1.57 828 1.70 859 1.83 890 1.97
9346
551 0.87 593 0.97 632 1.10 670 1.22 706 1.33 741 1.44 774 1.56 807 1.69 840 1.83 871 1.97 902 2.11
9770
572 0.98 612 1.09 651 1.22 687 1.35 722 1.47 757 1.58 789 1.70 821 1.83 852 1.97 883 2.11 912 2.26
10195
593 1.11 632 1.22 670 1.35 705 1.49 739 1.61 772 1.73 804 1.85 835 1.98 865 2.12 895 2.27 924 2.42
External Static Pressure (Pascals)
299
324
349
374
398
423
m3/hr RPM kW RPM kW RPM kW RPM kW RPM kW RPM kW
2.24 kW High Static Motor w/ Field Supplied Sheave & Belt
6797
863 1.42 891 1.51 919 1.61 944 1.70 970 1.79 994 1.88
7222
874 1.54 902 1.64 928 1.74 955 1.84 981 1.95 1004 2.04
7646
884 1.67 913 1.78 939 1.88 966 2.00 991 2.10 1015 2.21
8071
895 1.80 924 1.92 951 2.04 977 2.15 1002 2.26
—
—
8496
907 1.95 934 2.07 962 2.19
—
—
—
—
—
—
8921
918 2.09 946 2.22 973 2.35
—
—
—
—
—
—
9346
931 2.25 958 2.39
—
—
—
—
—
—
9770
941 2.41
10195
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
Notes:
1. Data includes pressure drop due to wet coil and 1" filter.
2. Fan motor heat (kW) = 1.238 x kW.
3. Factory supplied motors, in commercial equipment, are definite purpose motors, specifically designed and tested to operate reliably and
continuously at all cataloged conditions. Using the full horsepower range of our fan motors as shown in our tabular data will not result in nuisance
tripping or premature motor failure. Our product's warranty will not be affected.
SSP-PRC024J-EN
67
Performance Data
Table 70.
Evaporator fan performance —TWE201 — air handler (IP)
External Static Pressure (Inches of Water Gauge)
0.10"
0.20"
0.30"
0.40"
0.50"
0.60"
0.70"
0.80"
0.90"
1.00"
1.10"
CFM RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP
3 HP Standard
Motor w/ Field
Supplied
2 HP Low Static Motor
3 HP Standard Motor
Sheave & Belt
5200
—
—
531 0.83 580 0.96 627 1.09 666 1.21 707 1.37 748 1.54 787 1.71 825 1.88 864 2.06 902 2.24
5525
—
—
551 0.96 599 1.10 644 1.23 684 1.37 722 1.51 760 1.68 799 1.87 834 2.04 872 2.23 909 2.42
5850
—
—
572 1.10 619 1.25 662 1.39 703 1.54 738 1.68 774 1.84 810 2.02 846 2.22 880 2.40 916 2.60
6175 543 1.11 593 1.26 638 1.42 680 1.57 720 1.72 757 1.87 790 2.02 824 2.20 859 2.40 893 2.61 926 2.81
6500 566 1.28 614 1.43 659 1.61 699 1.77 737 1.92 775 2.08 807 2.24 839 2.40 871 2.59 904 2.80 936 3.02
6825 590 1.47 636 1.62 679 1.80 718 1.98 755 2.14 792 2.31 826 2.48 857 2.64 886 2.81 918 3.02 950 3.25
7150 614 1.67 658 1.83 700 2.02 738 2.21 774 2.38 809 2.55 844 2.73 875 2.90 903 3.07 932 3.26 962 3.47
7475 638 1.89 680 2.06 720 2.25 758 2.45 794 2.63 827 2.81 861 2.99 893 3.18 921 3.36 949 3.54 976 3.73
7800 662 2.13 702 2.31 742 2.50 779 2.71 814 2.91 846 3.09 879 3.28 910 3.48 940 3.67 967 3.86 993 4.04
External Static Pressure (Inches of Water Gauge)
1.20"
1.30"
1.40"
1.50"
1.60"
1.70"
1.80"
1.90"
CFM RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP
3 HP Standard
5 HP Ultra High Static Motor
Motor w/ Field
w/ Field Supplied Sheave &
Supplied
5 HP Ultra High Static Motor
Belt
Sheave & Belt
5200 937 2.42 972 2.59 1004 2.77 1036 2.95 1066 3.12 1095 3.29 1125 3.46 1152 3.63
5525 943 2.60 978 2.80 1012 2.99 1042 3.17 1072 3.35 1102 3.54 1132 3.73 1159 3.91
5850 951 2.80 984 3.00 1018 3.21 1050 3.41 1080 3.60 1109 3.80 1138 4.00 1166 4.19
6175 958 3.00 992 3.22 1024 3.43 1056 3.64 1086 3.86 1115 4.06 1143 4.27
—
—
6500 967 3.22 998 3.44 1030 3.65 1063 3.89 1093 4.11 1122 4.33 1151 4.56
—
—
6825 980 3.47 1010 3.69 1039 3.90 1069 4.13 1098 4.36 1129 4.61 1158 4.85
—
—
7150 991 3.70 1021 3.94 1051 4.18 1078 4.41 1107 4.65 1135 4.88 1165 5.14
—
—
7475 1005 3.97 1034 4.21 1062 4.46 1090 4.71 1117 4.94 1144 5.19
—
—
—
—
7800 1019 4.24 1047 4.49 1074 4.74 1102 5.01 1128 5.25 1154 5.51
—
—
—
—
Notes:
1. Data includes pressure drop due to wet coil and 1" filter.
2. Fan motor heat (MBh) = 3.15 x BHP.
3. Factory supplied motors, in commercial equipment, are definite purpose motors, specifically designed and tested to operate reliably and
continuously at all cataloged conditions. Using the full horsepower range of our fan motors as shown in our tabular data will not result in nuisance
tripping or premature motor failure. Our product's warranty will not be affected.
68
SSP-PRC024J-EN
Performance Data
Table 71.
Evaporator fan performance — TWE201 — air handler (SI)
External Static Pressure (Pascals)
25
50
75
100
125
150
174
199
224
249
274
m3/hr RPM kW RPM kW RPM kW RPM kW RPM kW RPM kW RPM kW RPM kW RPM kW RPM kW RPM kW
2.24 kW Standard
Motor w/ Field
1.49 kW Low Static Motor
2.24 kW Standard Motor
Supplied Sheave &
Belt
8836
—
—
531 0.62 580 0.71 627 0.81 666 0.90 707 1.02 748 1.15 787 1.27 825 1.40 864 1.54 902 1.67
9388
—
—
551 0.72 599 0.82 644 0.92 684 1.02 722 1.12 760 1.25 799 1.39 834 1.52 872 1.66 909 1.80
9940
—
—
572 0.82 619 0.94 662 1.04 703 1.15 738 1.25 774 1.37 810 1.51 846 1.65 880 1.79 916 1.94
10493
543 0.83 593 0.94 638 1.06 680 1.17 720 1.29 757 1.40 790 1.51 824 1.64 859 1.79 893 1.94 926 2.09
11045
566 0.95 614 1.07 659 1.20 699 1.32 737 1.43 775 1.55 807 1.67 839 1.79 871 1.93 904 2.09 936 2.25
11597
590 1.09 636 1.21 679 1.34 718 1.48 755 1.59 792 1.72 826 1.85 857 1.97 886 2.09 918 2.25 950 2.42
12149
614 1.25 658 1.37 700 1.50 738 1.65 774 1.77 809 1.90 844 2.03 875 2.16 903 2.29 932 2.43 962 2.59
12702
638 1.41 680 1.54 720 1.68 758 1.83 794 1.96 827 2.09 861 2.23 893 2.37 921 2.51 949 2.64 976 2.79
13254
662 1.59 702 1.72 742 1.86 779 2.02 814 2.17 846 2.31 879 2.45 910 2.59 940 2.74 967 2.88 993 3.02
External Static Pressure (Pascals)
299
324
349
374
398
423
448
m3/hr RPM kW RPM kW RPM kW RPM kW RPM kW RPM kW RPM kW
3.73 kW Ultra High 3.73 kW Ultra High Static Motor w/ Field Supplied
Static Motor
Sheave & Belt
8836
937 1.80 972 1.94 1004 2.07 1036 2.20 1066 2.33 1095 2.45 1125 2.58
9388
943 1.94 978 2.09 1012 2.23 1042 2.36 1072 2.50 1102 2.64 1132 2.78
9940
951 2.09 984 2.24 1018 2.39 1050 2.54 1080 2.69 1109 2.83
—
—
10493
958 2.24 992 2.40 1024 2.56 1056 2.72 1086 2.88 1115 3.03
—
—
11045
967 2.40 998 2.56 1030 2.73 1063 2.90 1093 3.07 1122 3.23
—
—
11597
980 2.59 1010 2.75 1039 2.91 1069 3.08 1098 3.26 1129 3.44
—
—
12149
991 2.76 1021 2.94 1051 3.12 1078 3.29 1107 3.47
—
—
—
—
12702 1005 2.96 1034 3.14 1062 3.32 1090 3.51 1117 3.69
—
—
—
—
13254 1019 3.17 1047 3.35 1074 3.54 1102 3.74 1128 3.92
—
—
—
—
Notes:
1. Data includes pressure drop due to wet coil and 1" filter.
2. Fan motor heat (kW) = 1.238 x kW.
3. Factory supplied motors, in commercial equipment, are definite purpose motors, specifically designed and tested to operate reliably and
continuously at all cataloged conditions. Using the full horsepower range of our fan motors as shown in our tabular data will not result in nuisance
tripping or premature motor failure. Our product's warranty will not be affected.
SSP-PRC024J-EN
69
Performance Data
Table 72.
Low static fan motors - standard air handlers
Model
Motor
TWE156
Standard Motor
with Field Supplied
Components
2 HP (1.5 kW)
TWE201
Low Static Motor
2 HP (1.5 kW)
Table 73.
Model
0
1
2
3
4
5
0
1
2
3
4
5
541
511
464
417
370
391
712
677
641
605
569
533
Required Field Supplied Components
Motor Sheave
Variable Pitch (2.4 - 3.4
Inch Pitch Diameter),
0.875 Inch Bore, Single
Groove, Browning
1VL40
N/A
Blower Sheave
Fixed Pitch (9.5 Inch
Pitch Diameter),
1.4375 Inch Bore,
Single Groove,
Browning BK105
Belt
Browning AX59
N/A
N/A
Standard fan motors - standard air handlers
Motor
TWE051
Standard Motor
.5 HP (.38 kW)
TWE072
Standard Motor
1 HP (.75 kW)
TWE076
Standard Motor
1 HP (.75 kW)
TWE101
Standard Motor
1.5 HP (1.13 kW)
TWE126
Standard Motor
1.5 HP (1.13 kW)
TWE156
Standard Motor
2 HP (1.5 kW)
70
Motor
Sheave Nominal
Turns
RPM
Open
Motor
Sheave Nominal
Turns
RPM
Open
0
1
2
3
4
5
0
1
2
3
4
5
0
1
2
3
4
5
0
1
2
3
4
5
0
1
2
3
4
5
0
1
2
3
4
5
6
892
833
773
714
654
595
706
659
612
565
518
471
706
659
612
565
518
471
682
644
606
568
530
492
640
604
569
533
498
462
704
676
648
620
592
565
537
Required Field Supplied Components
Motor Sheave
Blower Sheave
Belt
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
SSP-PRC024J-EN
Performance Data
Table 73.
Standard fan motors - standard air handlers (continued)
Motor
Model
Standard Motor
3 HP (2.25 kW)
TWE201
Table 74.
Motor
Sheave Nominal
Turns
RPM
Open
0
1
2
3
4
5
6
Required Field Supplied Components
805
777
749
721
693
665
637
Motor Sheave
Blower Sheave
Belt
N/A
N/A
N/A
High static fan motors - standard air handlers
Model
Motor
TWE051
High Static Motor
1 HP (.75kW)
TWE072
High Static Motor
1.5 HP (1.13 kW)
TWE076
High Static Motor
1.5 HP (1.13 kW)
TWE101
High Static Motor
2 HP (1.5 kW)
TWE101
High Static Motor
with Field Supplied
Components
2 HP (1.5 kW)
TWE126
Standard Motor
with Field Supplied
Components
1.5 HP (1.13 kW)
TWE126
High Static Motor
2 HP (1.5 kW)
SSP-PRC024J-EN
Motor
Sheave Nominal
Turns
RPM
Open
0
1
2
3
4
5
0
1
2
3
4
5
0
1
2
3
4
5
0
1
2
3
4
5
0
1
2
3
4
5
0
1
2
3
4
5
0
1
2
3
4
5
1122
1066
1010
954
898
842
912
866
820
775
729
683
912
866
820
775
729
683
810
769
729
688
648
607
941
894
847
800
753
706
761
718
671
624
577
549
912
866
825
785
744
683
Required Field Supplied Components
Motor Sheave
Blower Sheave
Belt
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
Variable Pitch (2.8 - 3.8
Inch Pitch Diameter),
0.875 Inch Bore,
Single Groove,
Browning 1VP44
Fixed Pitch (6.0 Inch
Pitch Diameter),
1.0 Inch Bore,
Single Groove,
Browning AK64
Browning A50
Variable Pitch (2.4 - 3.4
Inch Pitch Diameter),
0.875 Inch Bore,
Single Groove,
Browning 1VL40
Fixed Pitch (6.7 Inch
Pitch Diameter),
1.4375 Inch Bore,
Single Groove,
Browning AK71
Browning A55
N/A
N/A
N/A
71
Performance Data
Table 74.
Model
High static fan motors - standard air handlers (continued)
Motor
TWE156
High Static Motor
3.5 HP (2.6 kW)
TWE156
High Static Motor
with Field Supplied
Components
3.5 HP (2.6 kW)
TWE201
Standard Motor
with Field Supplied
Components
3 HP (2.25 kW)
Table 75.
Model
TWE072
0
1
2
3
4
5
6
0
1
2
3
4
5
6
0
1
2
3
4
5
6
853
824
794
765
735
705
676
1014
979
932
885
838
803
803
909
878
846
815
783
751
720
Required Field Supplied Components
Motor Sheave
Blower Sheave
Belt
N/A
N/A
N/A
Variable Pitch (3.4 - 4.4
Inch Pitch Diameter),
1.125 Inch Bore,
Single Groove,
Browning 1VP50
Fixed Pitch (6.6 Inch
Pitch Diameter),
1.4375 Inch Bore,
Single Groove,
Browning BK72
Browning BX58
Variable Pitch (2.8 - 3.8
Inch Pitch Diameter),
1.125 Inch Bore,
Single Groove,
Browning 1VP50
Fixed Pitch (10.4 Inch
Pitch Diameter),
1.4375 Inch Bore,
Single Groove,
Browning BK80
Browning BX62
Ultra high static fan motors - standard air handlers
Motor
Ultra High Static Motor
2 HP (1.5 kW)
TWE076
Ultra High Static Motor
2 HP (1.5 kW)
TWE126
Ultra High Static Motor
3.5 HP (2.6 kW)
TWE201
Ultra High Static Motor
5 HP (3.75 kW)
72
Motor
Sheave Nominal
Turns
RPM
Open
Motor
Sheave Nominal
Turns
RPM
Open
0
1122
1
1034
2
3
946
859
4
5
771
683
—
0
1
2
3
4
5
—
0
1
2
3
4
5
6
0
1
2
3
4
5
6
—
1122
1034
946
859
771
683
—
1014
979
944
909
874
838
803
1078
1036
993
950
907
864
822
Required Field Supplied Components
Motor Sheave
Blower Sheave
Belt
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
SSP-PRC024J-EN
Performance Data
Table 75.
Ultra high static fan motors - standard air handlers (continued)
Model
Motor
Ultra High Static Motor
with Field Supplied
Components
5 HP (3.75 kW)
TWE201
Table 76.
Motor
Sheave Nominal
Turns
RPM
Open
0
1
2
3
4
5
6
1096
1067
1036
1004
973
941
926
Required Field Supplied Components
Motor Sheave
Blower Sheave
Variable Pitch (2.8 - 3.8
Inch Pitch Diameter),
1.125 Inch Bore, Single
Groove, Browning
1VP44
Belt
Fixed Pitch (10.4 Inch
Pitch Diameter),
1.4375 Inch Bore,
Single Groove,
Browning BK110
Browning BX62
Discharge plenum and grille assembly throw distance — air handler — ft (m)
Unit Model
No.
TWE051
TWE072
TWE076
TWE101
TWE126
TWE156
TWE201
Louver angle Deflection Position (ft)
Louver angle Deflection Position (m)
CFM
m3/h
Straight
20°
40°
55°
Straight
20°
40°
55°
1800
3060
46
37
29
22
14.0
11.3
8.8
6.7
2000
3395
48
43
33
24
14.6
13.1
10.1
7.3
2200
3737
51
50
36
25
15.5
15.2
11.0
7.6
2400
4074
44
58
41
28
13.4
17.7
12.5
8.5
1800
3061
47
34
28
24
14.0
10.3
8.3
8.0
2000
3400
49
37
30
26
14.7
11.2
9.0
8.3
2200
3739
50
40
32
28
15.3
12.2
9.8
8.5
2400
4078
52
43
35
29
15.9
13.1
10.6
8.8
2250
3823
51
41
33
28
15.4
12.4
10.0
8.6
2500
4249
53
45
36
30
16.2
13.6
10.9
9.0
2750
4671
56
49
39
31
16.9
14.9
11.9
9.4
3000
5098
58
53
42
32
17.7
16.2
12.8
9.9
3025
5139
57
44
36
32
17.4
13.4
10.8
9.6
3350
5692
60
48
39
32
18.3
14.7
12.0
9.7
3675
6245
63
52
43
33
19.3
16.0
13.2
10.0
4000
6795
67
57
47
35
20.3
17.3
14.4
10.5
3750
6370
44
27
25
38
13.4
8.1
7.5
11.7
4200
7137
45
31
28
48
13.7
9.5
8.5
14.5
4650
7902
47
36
31
57
14.3
10.9
9.5
17.4
5100
8666
50
40
34
67
15.2
12.3
10.5
20.5
4500
7644
46
34
30
22
14.1
10.5
9.2
6.6
5000
8497
49
39
34
25
14.9
12.0
10.3
7.6
5500
9346
53
45
37
28
16.2
13.6
11.4
8.5
6000
10195
58
50
41
31
17.7
15.1
12.5
9.3
6000
10195
53
43
36
28
16.0
13.1
10.9
8.6
6680
11348
57
48
40
31
17.5
14.5
12.1
9.4
7350
12488
62
52
44
33
18.8
16.0
13.3
10.0
8030
13645
65
57
47
35
19.8
17.4
14.5
10.5
Note: Throw distance values are based on a terminal velocity of 75 fpm (0.38 m/s). Throw distance values at other terminal velocities may be established by
multiplying throw distances in table above by throw factor as follows: for 50 FPM (0.25 m/s) terminal velocity, multiply by 1.50 throw factor; for 100 FPM
(0.51 m/s) terminal velocity, multiply by 0.75 throw factor; for 150 FPM (0.76 m/s) terminal velocity, multiply by 0.50 throw factor.
SSP-PRC024J-EN
73
Performance Data
Table 77.
Unit
Model
No.
Static pressure drop through accessories (inches if water column) — air handler
Discharge
Plenum &
Grille
Return Grille
CFM m3/h
in. wc Pascal in. wc Pascal
Electric Heaters (kW)
5–10
15–20
25–30
35–50
in. wc Pascal in. wc Pascal in. wc Pascal in. wc Pascal
1400
2379
0.09
23.60
0.16
41.10
0.06
16.20
0.05
13.70
0.09
23.60
—
—
TWE051 1700
2889
0.14
34.90
0.24
60.60
0.09
23.90
0.08
20.20
0.14
34.90
—
—
2000
3398
0.18
45.70
0.33
83.80
0.13
33.00
0.13
33.00
0.19
48.30
—
—
1600
2718
0.03
9.51
0.11
28.91
0.03
7.47
0.03
7.47
0.06
14.94
0.06
14.94
TWE072 2000
3398
0.04
14.70
0.18
45.20
0.03
7.47
0.05
12.45
0.08
19.93
0.10
24.91
2400
4078
0.06
21.11
0.26
65.07
0.04
9.96
0.07
17.44
0.11
27.40
0.15
37.36
2000
3398
0.06
14.70
0.18
45.20
0.03
6.80
0.05
13.50
0.08
19.20
0.10
26.00
TWE076 2500
4248
0.09
22.90
0.28
70.60
0.04
10.60
0.08
21.20
0.12
30.00
0.16
40.60
3000
5098
0.13
33.00
0.40
101.60
0.06
15.20
0.12
30.50
0.17
43.20
0.23
58.40
2600
4418
0.05
11.70
0.28
72.10
0.04
10.10
0.09
21.80
0.13
31.90
0.17
43.60
TWE101 3300
5607
0.07
18.90
0.46
116.20
0.06
16.20
0.14
35.10
0.20
51.30
0.28
70.20
4000
6797
0.11
27.80
0.67
170.70
0.09
23.80
0.20
51.60
0.30
75.40
0.41
103.20
3200
5436
0.04
10.20
0.10
25.60
0.01
2.50
0.02
5.00
0.03
7.50
0.04
10.00
TWE126 4000
6797
0.06
15.90
0.16
39.90
0.02
5.00
0.03
7.50
0.04
10.00
0.06
15.00
4800
8156
0.09
22.90
0.23
57.50
0.03
7.50
0.03
7.50
0.06
15.00
0.08
20.00
4000
6797
0.07
16.90
0.15
38.40
0.02
3.80
0.03
6.80
0.05
13.50
0.08
19.20
TWE156 5000
8496
0.10
26.50
0.24
60.00
0.04
10.60
0.04
10.60
0.08
21.20
0.12
30.00
6000 10195
0.15
38.10
0.34
86.40
0.06
15.20
0.06
15.20
0.12
30.50
0.17
43.20
5200
0.07
18.40
0.30
73.80
0.04
10.60
0.04
10.60
0.08
21.10
0.13
31.70
TWE201 6650 11300
0.12
30.20
0.46
114.90
0.07
17.30
0.07
17.30
0.14
34.50
0.21
51.80
7800 13254
0.16
41.50
0.63
156.10
0.10
23.80
0.10
23.80
0.19
47.50
0.29
71.30
8836
Notes:
1. Return air filter ESP included in Fan Performance Table data.
2. On discharge plenum and grille - at louver opening angle of 42 degrees. For ESP at other angle openings, see accessory installation
instruction.
Table 78.
Auxiliary electric heat capacity — air handler
No. of
Stages
Stage 1
Btu
kW Input
Output
Stage 2
Btu
kW Input
Output
Unit Model No.
Total kW
5.00
1
5.00
17,065
—
TWE0514DA, 0724DB,
0764DA/B, 1014DA/B
9.96
1
9.96
33,993
—
14.96
1
14.96
51,058
24.92
2
14.96
TWE0724DB, 0764DA/
B, 1014DA/B
TWE1264DB, 1564DB,
2014DB
Total
kW Input
Btu
Output
—
5.00
17,065
—
9.96
33,993
—
—
14.96
51,058
51,058
9.96
33993
24.92
85,051
34.88
2
19.92
67,987
14.96
51058
34.88
119,045
10.00
1
10.00
34,130
—
—
10.00
34,130
19.92
1
19.92
67,987
—
—
19.92
67,987
29.92
2
19.92
67,987
10.00
34130
29.92
102,117
49.84
2
29.92
102,117
19.92
67987
49.84
170,104
Note: Heaters are rated at 240V, 480V and 600V. For other than rated voltage, capacity = (Voltage/Related Voltage)2 x Rated Capacity
74
SSP-PRC024J-EN
Controls
ReliaTel
Zone Sensors are the building occupant’s comfort control devices. Zone sensors are required for
SZVAV applications. The following zone sensor options are available for units with ReliaTel
control.
Manual Changeover
(BAYSENS106*)
Manual/Automatic
Changeover (BAYSENS108*)
Manual/Automatic
Changeover (BAYSENS110*)
Heat, Cool or Off System Switch.
Fan Auto or Off Switch. One
temperature setpoint lever.
Auto, Heat, Cool or Off System
Switch. Fan Auto or Off Switch.
Two temperature setpoint levers.
Auto, Heat, Cool or Off System
Switch. Fan Auto or Off Switch.
Two temperature setpoint levers.
Status Indication LED lights,
System On, Heat, Cool, or
Service.
Integrated Comfort™ System
(BAYSENS074*)
Remote Sensor
(BAYSENS077*)
Wireless Zone Sensor
(BAYSENS050*)
Programmable Night Setback
(BAYSENS119*)
Sensor(s) available with optional
temperature adjustment and
override buttons to provide
central control through a Trane
Integrated Comfort™ system.
Sensor(s) available for all zone
sensors to provide remote
sensing capabilities.
LCD display that provides heat,
cool, auto or off. Includes two
temperature setpoints and a
lockable setting with °F or °C
indicators.
Auto or manual changeover with
seven-day programming.
Keyboard selection of Heat, Cool,
Fan, Auto, EM Heat or On. All
sensors have System On, Heat,
Cool, Service LED/ indicators as
standard. Night Setback Sensors
have one (1) Occupied, one (1)
Un-occupied, and one (1)
Override program per day.
SSP-PRC024J-EN
75
Controls
Electromechanical
Non-Programmable Thermostats
TCONT200*** (1H/1C)
TCONT401*** (2H/1C)
TCONT402*** (3H/2C)
$
$
$
Fan
Filter/O D
FILTER
FA N
Mode
Fan
Filter/O D
Mode
M O DE
Auto-changeover Backlit Display &
Keys Filter Reminder Keypad Lock
Auto-changeover Backlit Display &
Keys Filter Reminder Keypad Lock
Outdoor Temp Sensor Available
Auto-changeover Backlit Display &
Keys Filter Reminder Keypad Lock
Outdoor Temp Sensor Included
Programmable Thermostats
TCONT600***(1H/1C)
TCONT602***(2H/2C)
5/2 or 5/1/1 Programming Actual
and Setpoint temps displayed
simultaneously
5/2 or 5/1/1 Programming Actual
and Setpoint temps displayed
simultaneously
TCONT800*** (1H/1C)
TCONT802*** (3H/2C)
MON
TUE
WED
THU
FRI
SAT
FAN
ON
AUTO
CIRC
SUN
HEAT
SYSTEM
EM HEAT
HEAT
OFF
COOL
AUTO
RESET
DONE
EDIT
CANCEL
PERIOD
DEHUMIDIFIER
COOL
PM
WAKE
LEAVE
RETURN
SLEEP
CANCEL
Interactive touchscreen Large
display Real time clock
MON
TUE
WED
THU
FRI
SAT
FAN
ON
AUTO
CIRC
TCONT803*** (3H/2C)
SUN
HEAT
SYSTEM
EM HEAT
HEAT
OFF
COOL
AUTO
RESET
DONE
EDIT
CANCEL
PERIOD
DEHUMIDIFIER
COOL
PM
WAKE
LEAVE
RETURN
SLEEP
CANCEL
Interactive touchscreen Large
display Real time clock
MON
TUE
WED
THU
FRI
SAT
FAN
ON
AUTO
CIRC
SUN
HEAT
SYSTEM
EM HEAT
HEAT
OFF
COOL
AUTO
RESET
DONE
EDIT
CANCEL
PERIOD
DEHUMIDIFIER
COOL
PM
WAKE
LEAVE
RETURN
SLEEP
CANCEL
Interactive touchscreen Large
display Real time clock Built-in
humidity sensor
Notes:
76
•
All thermostats may be used with ReliaTel units.
•
Thermostats may be used with ReliaTel-equipped Cooling units, but only when
matched with Standard Air Handlers (SZVAV Air Handlers excluded).
SSP-PRC024J-EN
Electrical Data
Heat Pump Condenser
Table 79.
Electrical Characteristics — Motors — Heat Pumps — 50Hz
Compressor Motors
Tons
5
6.25
8.33
Compressor 1
Unit Model
Number
Volts
Phase
Condenser Fan Motor
Amps
Compressor 2
No.
RLA
LRA
RLA
LRA
(Amps) (Amps) (Amps) (Amps)
Volts
Phase
FLA
(Ea.)
LRA
(Ea.)
TWA0604DA
380/415
3
10.6
74.0
N/A
N/A
1
380/415
1
1.6
3.8
TWA0604DD
380/415
3
5.4
38.0
5.4
38.0
1
380/415
1
1.6
3.8
TWA0764DA
380/415
3
12.2
100.0
N/A
N/A
1
380/415
1
1.6
3.8
TWA0764DD
380/415
3
6.0
43.0
6.0
43.0
1
380/415
1
1.6
3.8
TWA1014DA
380/415
3
17.8
145.0
N/A
N/A
1
380/415
1
1.9
5.8
TWA1014DD
380/415
3
7.8
51.5
7.8
51.5
1
380/415
1
1.9
5.8
13
TWA1564DD
380/415
3
12.2
101.0
12.2
101.0
2
380/415
1
1.9
5.8
16.7
TWA2014DD
380/415
3
18.5
118.0
18.5
118.0
2
380/415
1
1.9
5.8
Table 80.
Tons
Unit wiring — heat pumps — 50 Hz
Unit Model
Number
Unit Operating
Voltage Range
Max
Circuit
Ampacity
Max Fuse Size or
Max Circuit
Breaker
5
TWA0604DA
380/415
14.9
25
5
TWA0604DD
380/415
13.8
15
6.25
TWA0764DA
380/415
17.0
25
6.25
TWA0764DD
380/415
15.1
20
8.33
TWA1014DA
380/415
24.2
40
8.33
TWA1014DD
380/415
19.5
25
13
TWA1564DD
380/415
31.2
40
16.7
TWA2014DD
380/415
45.4
60
Note: HACR type circuit breaker per NEC.
Air Handler (Standard)
Table 81.
Electrical characteristics — standard motor — 50 Hz air handler
Standard Evaporator Fan Motor
Tons
Unit Model
Number
No.
Volts
Phase
HP
Amps
FLA
LRA
MCA
MFS
4.6
TWE0514DA
1
380-415
3
0.75
1.45
8.00
1.81
15.00
6
TWE0724DB
1
380-415
3
1.00
2.50
17.00
3.13
15.00
6.25
TWE0764DA, B
1
380-415
3
1.00
2.50
17.00
3.13
15.00
8.33
TWE1014DA, B
1
380-415
3
1.50
3.30
19.00
4.13
15.00
10.4
TWE1264DB
1
380-415
3
2.00
3.20
35.00
4.00
15.00
13
TWE1564DB
1
380-415
3
2.00
4.60
39.00
5.75
15.00
16.7
TWE2014DB
1
380-415
3
3.50
8.00
43.00
10.00
15.00
SSP-PRC024J-EN
77
Electrical Data
Table 82.
Ton
4.6
6
6.25
8.33
78
Unit wiring with electric heat (single point connection) — air handlers
Used With
Heater
Model No.
Heater
Unit Power
kW Rating
Supply
Control
Stages
Min
Circuit
Ampacity
Max
Fuse
Breaker Size
BAYHTRL405*
5
380/3/50
1
8
15
BAYHTRL410*
9.96
380/3/50
1
14
15
BAYHTRL415*
14.96
380/3/50
1
20
20
BAYHTRL425*
24.92
380/3/50
2
31
35
TWE0514DA
BAYHTRL405*
5
415/3/50
1
8
15
BAYHTRL410*
9.96
415/3/50
1
15
15
BAYHTRL415*
14.96
415/3/50
1
21
25
BAYHTRL425*
24.92
415/3/50
2
34
35
BAYHTRL405*
5
380/3/50
1
9
15
BAYHTRL410*
9.96
380/3/50
1
15
15
BAYHTRL415*
14.96
380/3/50
1
21
25
BAYHTRL425*
24.92
380/3/50
2
33
35
BAYHTRL435*
34.88
380/3/50
2
45
45
BAYHTRL405*
5
415/3/50
1
10
15
BAYHTRL410*
9.96
415/3/50
1
16
20
BAYHTRL415*
14.96
415/3/50
1
23
25
BAYHTRL425*
24.92
415/3/50
2
36
40
BAYHTRL435*
34.88
415/3/50
2
48
50
BAYHTRL405*
5
380/3/50
1
9
15
BAYHTRL410*
9.96
380/3/50
1
15
15
BAYHTRL415*
14.96
380/3/50
1
21
25
BAYHTRL425*
24.92
380/3/50
2
33
35
BAYHTRL435*
34.88
380/3/50
2
45
45
BAYHTRL405*
5
415/3/50
1
10
15
BAYHTRL410*
9.96
415/3/50
1
16
20
BAYHTRL415*
14.96
415/3/50
1
23
25
BAYHTRL425*
24.92
415/3/50
2
36
40
BAYHTRL435*
34.88
415/3/50
2
48
50
BAYHTRL405*
5
380/3/50
1
10
15
BAYHTRL410*
9.96
380/3/50
1
16
20
BAYHTRL415*
14.96
380/3/50
1
22
25
BAYHTRL425*
24.92
380/3/50
2
34
35
BAYHTRL435*
34.88
380/3/50
2
46
50
BAYHTRL405*
5
415/3/50
1
11
15
BAYHTRL410*
9.96
415/3/50
1
17
20
BAYHTRL415*
14.96
415/3/50
1
24
25
BAYHTRL425*
24.92
415/3/50
2
37
40
BAYHTRL435*
34.88
415/3/50
2
49
50
TWE0724DB
TWE0764DA, B
TWE1014DA, B
SSP-PRC024J-EN
Electrical Data
Table 82.
Ton
10.4
13
16.7
Unit wiring with electric heat (single point connection) — air handlers (continued)
Used With
Heater
Model No.
Heater
Unit Power
kW Rating
Supply
Control
Stages
Min
Circuit
Ampacity
Max
Fuse
Breaker Size
BAYHTRM410*
10
380/3/50
1
16
20
BAYHTRM420*
19.92
380/3/50
1
28
30
BAYHTRM430*
29.92
380/3/50
2
40
40
BAYHTRM450*
49.84
380/3/50
2
63
70
BAYHTRM410*
10
415/3/50
1
17
20
BAYHTRM420*
19.92
415/3/50
1
30
30
BAYHTRM430*
29.92
415/3/50
2
43
45
BAYHTRM450*
49.84
415/3/50
2
69
70
BAYHTRM410*
10
380/3/50
1
18
20
BAYHTRM420*
19.92
380/3/50
1
29
30
BAYHTRM430*
29.92
380/3/50
2
41
45
BAYHTRM450*
49.84
380/3/50
2
65
70
BAYHTRM410*
10
415/3/50
1
19
20
BAYHTRM420*
19.92
415/3/50
1
32
35
BAYHTRM430*
29.92
415/3/50
2
45
45
BAYHTRM450*
49.84
415/3/50
2
71
80
BAYHTRM410*
10
380/3/50
1
22
25
BAYHTRM420*
19.92
380/3/50
1
34
35
BAYHTRM430*
29.92
380/3/50
2
46
50
BAYHTRM450*
49.84
380/3/50
2
69
70
BAYHTRM410*
10
415/3/50
1
23
25
BAYHTRM420*
19.92
415/3/50
1
36
40
BAYHTRM430*
29.92
415/3/50
2
49
50
BAYHTRM450*
49.84
415/3/50
2
75
80
TWE1264DB
TWE1564DB
TWE2014DB
SSP-PRC024J-EN
79
Jobsite Connections
ReliaTel Controls
Wiring shown with dashed lines is to be furnished and installed by the customer. All customer
supplied wiring must be copper only and must conform to NEC and local electrical codes. Codes
may require line of sight between disconnect switch and unit.
Notes:
1. When electric heater accessory is used, single point power entry or dual point power
entry is field optional. Single point power entry option is through electric heater only.
2. ***Choose only one of the following; Thermostat, Zone Sensor, or NSB Panel.
I m p o r t a n t : For the EDC switch to be functional and thereby facilitate reliable unit operation,
make the EDC connections from the indoor to the outdoor control boxes.
Figure 8.
ReliaTel jobsite connections
Disconnect Switch
(By Others)
Note 2
B
Air Handler
Electric
Heat Accessory
D
B
Disconnect Switch
(By Others) Note 2
A
E
T’stat
Zone
Sensor
F
NSB Panel
A.
3 power wires, line voltage for 3 phase, (2 power wires for single phase)
B.
3 power wires, line voltage for 3 phase, (2 power wires for single phase)
C.
Heat Pump thermostat: 5 to 8 wires depending on stages of electric heat
D.
3 to 7 wires depending on type of outdoor unit(s)
E.
Zone Sensor: 4 to 10 wires depending on zone sensor model(a)
F.
Night Setback Panel: 7 wires
(a)
80
C
Disconnect Switch
(By Others)
For SZVAV air handlers: 4 additional wires are required (2 of which require twisted pair or shielded wire) in order to make
connections between ReliaTel boards in the condenser and air handler.
SSP-PRC024J-EN
Dimensional Data
Heat Pump Condenser
Figure 9.
5-6.25 ton heat pump, single compressor
SEE NOTE 3
NOTES:
1. ACCESS OPENING IS FOR FIELD INSTALLED BAYLOAM ACCESSORY.
2. MINIMUM CLEARANCE FOR PROPER OPERATION IS 36" ( 914.4) FROM
WALLS, SHRUBBERY, PRIVACY FENCES ETC. MINIMUM CLEARANCE
BETWEEN ADJACENT UNITS IS 72" (1828.8). RECOMMENDED SERVICE
CLEARANCE 48" (1219.2)
3. TOP DISCHARGE AREA SHOULD BE UNRESTRICTED FOR 100" (2540)
MINIMUM. UNIT SHOULD BE PLACED SO ROOF RUN-OFF WATER DOES
NOT POUR DIRECTLY ON UNIT
4. OUTDOOR AIR TEMPERATURE SENSOR OPENING (DO NOT BLOCK OPENING)
SERVICE PANEL
HAIL GUARD
(OPTIONAL)
SEE NOTE 4
SERVICE CLEARANCE
48" (1219.2) (SEE NOTE 2
FOR CLEARANCE)
HAIL GUARD
(OPTIONAL)
35 15/16"
(912.8)
WITH HAIL GUARD
33 15/16"
(862)
LINE VOLTAGE
SEE NOTE 1
REFRIGERANT ACCESS
CONTROL WIRING
36 3/8"
(923.9)
29 13/16"
(757.2)
39 3/16"
(995.4)
26 15/16"
(684.2)
SERVICE PANEL
14 3/8"
(365.1)
8 5/16"
5 5/8"
(211.1)
(143)
1/16"
(1.6)
LIQUID LINE
6"
(152.4)
6"
(152.4)
2" (50.8)
21 11/16"
(550.9)
SUCTION LINE
41 1/16"
(1043)
33 13/16"
(858.8)
42 1/8"
(1070)
WITH HAIL GUARD
SERVICE PANEL SIDE
3" (76.2)
34 3/4"
40 3/4" (882.7)
(1035)
4 3/16"
(106.4)
1 13/16"
(46)
SSP-PRC024J-EN
3 1/16" (77.8)
7/16" (11.1) DIA. ISOLATOR MOUNTING
HOLES (OUTSIDE HOLES - 4 PLACES)
BOTTOM
OF UNIT
27 11/16"
(703.3)
2 5/16"
(58.7)
81
Dimensional Data
Figure 10.
82
5-6.25 ton heat pump, dual compressor
SSP-PRC024J-EN
Dimensional Data
Figure 11.
8.33 ton heat pump, single compressor
SEE NOTE 3
NOTES:
1. ACCESS OPENING IS FOR FIELD INSTALLED BAYLOAM ACCESSORY.
2. MINIMUM CLEARANCE FOR PROPER OPERATION IS 36" (914.4) FROM
WALLS, SHRUBBERY, PRIVACY FENCES ETC. MINIMUM CLEARANCE
BETWEEN ADJACENT UNITS IS 72" (1828.8). RECOMMENDED SERVICE
CLEARANCE 48" (1219.2)
3. TOP DISCHARGE AREA SHOULD BE UNRESTRICTED FOR 100" (2540)
MINIMUM. UNIT SHOULD BE PLACED SO ROOF RUN-OFF WATER DOES
NOT POUR DIRECTLY ON UNIT
4. OUTDOOR AIR TEMPERATURE SENSOR OPENING (DO NOT BLOCK OPENING)
SERVICE PANEL
SEE NOTE 4
HAIL GUARD
(OPTIONAL)
SERVICE CLEARANCE
48" (1219.2) (SEE NOTE 2
FOR CLEARANCE
39 15/16"
(1014.4)
WITH HAIL GUARD
4 1/4" (108)
HAIL GUARD
(OPTIONAL)
1 1/4" (31.7)
LINE VOLTAGE
37 15/16"
(963.6)
CONTROL WIRING
42 5/16"
35 3/4" (1074.7)
(908)
5 9/16"
(141.3)
SEE NOTE 1
REFRIGERANT ACCESS
44 3/4"
(1136.6)
SERVICE PANEL
32 7/8"
(835)
14 5/16"
(363.5)
8 1/4"
(209.5)
1/16" (1.6)
LIQUID LINE
25 11/16"
(652.5)
6" (152.4)
4" (101.6)
6" (152.4)
37 11/16"
(957.3)
SUCTION LINE
4 3/8" (111.1)
1 13/16" (46)
2 7/8" (73)
50 15/16"
(1293.8)
51 15/16"
(1319.2)
WITH HAIL GUARD
SERVICE PANEL SIDE
3" (76.2)
7/16" (11.1) DIA. ISOLATOR MOUNTING
HOLES (OUTSIDE HOLES - 4 PLACES)
44 3/4"
50 3/4" (1136.6)
(1289)
BOTTOM
OF UNIT
3 13/16"
(96.8)
2 3/16"
(55.6)
SSP-PRC024J-EN
31 11/16"
(805)
1 11/16"
(42.9)
83
Dimensional Data
Figure 12.
84
8.33 ton heat pump, dual compressor
SSP-PRC024J-EN
Dimensional Data
Figure 13.
13-16.7 ton heat pump, dual compressor
SEE NOTE 2
NOTES:
1. MINIMUM CLEARANCE FOR PROPER OPERATION IS 36" (914.4) FROM
WALLS, SHRUBBERY, PRIVACY FENCES ETC. MINIMUM CLEARANCE
BETWEEN ADJACENT UNITS IS 72" (1829). RECOMMENDED SERVICE
CLEARANCE 48" (1219.2)
2. TOP DISCHARGE AREA SHOULD BE UNRESTRICTED FOR 100" (2540)
MINIMUM. UNIT SHOULD BE PLACED SO ROOF RUN-OFF WATER DOES
NOT POUR DIRECTLY ON UNIT
3. OUTDOOR AIR TEMPERATURE SENSOR OPENING (DO NOT BLOCK OPENING).
HAIL GUARD
(OPTIONAL)
SEE NOTE 3
SERVICE CLEARANCE
48" (1219.2) (SEE NOTE 1
FOR CLEARANCE)
DETAIL A
46"
(1168.4)
WITH HAIL GUARD
SERVICE PANEL
44 3/16"
(1122.4)
95 7/16"
(2424.112)
WITH HAIL GUARD
HAIL GUARD
(OPTIONAL)
HAIL GUARD
(OPTIONAL)
45 1/8"
(1146.2)
SERVICE
PANEL
1/16"
(1.6)
41 3/8"
(1051)
9"
(228.6)
93 5/16"
(2370.1)
25 11/16"
(652.5)
9"
(228.6)
9 1/4" (235)
6 13/16" (173)
7/16" (11.1) ( DIA. ISOLATOR MOUNTING
HOLES (OUTSIDE HOLES - 4 PLACES)
CONTROL WIRING
1 3/16" (30.2)
LINE VOLTAGE
SERVICE PANEL SIDE
REFRIGERANT ACCESS
41 5/8"
39 7/8" (1057.3)
(1012.8)
BOTTOM OF UNIT
36 7/8"
(936.6)
41 1/2"
(1054.1)
14 1/2" 14 5/8" 12 5/8"
(368.3) (371.5) (320.7)
5 5/8" 4 1/4"
(143) (108)
SUCTION LINES
3" (76.2)
87"
(2210)
93"
(2362.2)
2 3/16" 6 13/16"
(55.6) (173)
LIQUID LINES
15/16" (23.8)
3 11/16" (94)
6 5/16" (160.3)
FRONT DETAIL A
DIMENSIONAL DETAIL
SSP-PRC024J-EN
85
Dimensional Data
Air Handler
Figure 14.
4.6 ton air handler, single circuit
.50" (12.7)
DUCT FLANGE
1" (25.4)
HEIGHT
NOTES:
1. PANEL DEPTH 1/2" (12.7) (TYP. ALL PANELS).
2. REMOVABLE DRAIN PAN AND ATTACHED DRAIN CONNECTION MAY BE INSTALLED ON END
OF UNIT IN EITHER THE VERTICAL OR HORIZONTAL CONFIGURATION, PLASTIC DRAIN PAN
ACCESS PLATE ON THE END OF UNIT OPPOSITE DRAIN CONNECTION MUST BE REMOVED TO
SLIDE DRAIN PAN OUT OF UNIT FOR CLEANING. ACCESS PLATE MUST BE RE-INSTALLED AFTER
SLIDING DRAIN PAN BACK INTO UNIT.
3. IF PERIODIC DRAIN PAN CLEANING IS REQUIRED, ALLOW ROOM FOR PARTIAL REMOVAL OF
DRAIN PAN CONNECTION AT END OF UNIT.
4. 1" (25.4) FEMALE SCHED. 40 (10.2) PVC PIPE DRAIN CONNECTION VERTICAL CONFIGURATION.
5. 1" (25.4) FEMALE SCHED. 40 (10.2) PVC PIPE DRAIN CONNECTION HORIZONTAL CONFIGURATION.
22 5/8"
(574.7)
16 1/4"
(412.8)
.77"
(19.6)
6 15/16" (176.2)
24 1/16"
(611.2)
SUPPLY
OPEN
37 15/16"
(963.6)
12 7/16"
(315.9)
7 9/16"
(192.1)
HEATER CONTROL
AND SINGLE POWER
ENTRY WIRES
6 7/8"
(174.6)
HEATER
VENTILATION
2 5/16"
(58.7)
1 3/4"
(44.45)
3 9/16"
(90.5)
2 3/4"
(69.9)
22 5/8"
(574.7)
CONTROL WIRING
13 5/16"
(338.14)
BOTTOM RETURN
SIDE RETURN
32 1/2"
(825.5)
32 1/2"
(825.5)
2 3/4"
(69.9)
3 7/16" (87.3)
5 15/16"
(150.8)
LINE VOLTAGE
CONTROL BOX
ACCESS PANEL
COPPER LIQUID LINE
FIELD CONNECTION
13 3/16" (335)
COPPER SUCTION LINE
FIELD CONNECTION
1 11/16"
(42.9)
REMOTE BULB TXV
DRAIN CONNECTION
FOR HORIZONTAL
(SEE NOTE 2,3,5)
1 3/8" (34.9) O.D. SUCTION LINE
20 1/16"
(509.6)
13 9/16" 12"
(344.5) (304.8)
12" 13 9/16" (344.5)
(304.8)
.99" (25.15)
.99" (25.15)
FILTER ACCESS PANEL
32" (813) MIN. DISTANCE
BOTH SIDE
SEE NOTES 2,3,4
1 3/8"
(34.9)
1 3/8" (34.9)
LIQUID LINES
3 3/16" (81)
SEE NOTES 2,3,4
1 1/8"
(28.6)
(4) - HOLE FOR HORIZONTAL
SUSPENSION
35 5/8"
(904.9)
SUPPLY OPENING
3" (76.2)
(4) - HOLE FOR HORIZONTAL
SUSPENSION
BOTTOM RETURN
34 9/16"
48 1/16" (877.9)
(1220.8)
SIDE RETURN
FILTER
10 7/16"
(265.1)
BOTTOM RETURN
SUPPLY VERTICAL RETURN HORIZONTAL /
RETURN VERTICAL
86
SIDE RETURN
SUPPLY HORIZONTAL RETURN VERTICAL /
RETURN HORIZONTAL
SSP-PRC024J-EN
Dimensional Data
Figure 15.
6, 6.25 ton air handler, single circuit
NOTES:
1. PANEL DEPTH 1/2" (12.7) (TYP. ALL PANELS).
2. REMOVABLE DRAIN PAN AND ATTACHED DRAIN CONNECTION MAY BE INSTALLED ON END
OF UNIT IN EITHER THE VERTICAL OR HORIZONTAL CONFIGURATION, PLASTIC DRAIN PAN
ACCESS PLATE ON THE END OF UNIT OPPOSITE DRAIN CONNECTION MUST BE REMOVED TO
SLIDE DRAIN PAN OUT OF UNIT FOR CLEANING. ACCESS PL ATE MUST BE RE-INSTALLED AFTER
SLIDING DRAIN PAN BACK INTO UNIT.
3. IF PERIODIC DRAIN PAN CLEANING IS REQUIRED, ALLOW ROOM FOR PARTIAL REMOVAL OF
DRAIN PAN CONNECTION AT END OF UNIT.
4. 1" (25.4) FEMALE SCHED. 40 (10.2) PVC PIPE DRAIN CONNECTION VERTICAL CONFIGURATION.
5. 1" (25.4) FEMALE SCHED. 40 (10.2) PVC PIPE DRAIN CONNECTION HORIZONTAL CONFIGURATION.
25 1/2"
(647.7)
DUCT FLANGE
1" (25.4)
HEIGHT
16 1/4"
(412.8)
.70"
(17.8)
11 11/16"
(296.8)
24 1/16"
(611.2)
47 1/2"
(1206.5)
SUPPLY
OPEN
12 5/16"
8 5/16"
(312.7)
(211.1)
HEATER CONTROL
AND SINGLE POWER
ENTRY WIRES
16 1/16"
(408)
16 7/8"
(428.6)
SIDE RETURN
BOTTOM RETURN
2 1/4" (57.15)
HEATER
VENTILATION
1 9/16"
(39.7)
6 13/16"
(173)
CONTROL WIRING
1 13/16"
(46)
42"
(1066.8)
2 3/4"
(69.85)
25 1/2"
(647.7)
42"
(1066.8)
2 3/4"
(69.85)
3 1/2" (88.9)
LINE VOLTAGE
COPPER LIQUID LINE
FIELD CONNECTION
8 13/16" (223.8)
16"
(406.4)
CONTROL BOX
ACCESS PANEL
1 3/16" (30.2)
DRAIN CONNECTION
FOR HORIZONTAL
(SEE NOTE 2,3,5)
22 7/8"
(581)
FILTER ACCESS PANEL
22" (558.8) MIN. DISTANCE
BOTH SIDE
COPPER SUCTION LINE
FIELD CONNECTION
REMOTE BULB TXV
SUCTION LINE
16 11/16" 17 7/16"
(442.9)
(423.9)
20"
(508)
17 3/8"
(441.3)
16 11/16"
(423.9)
3 5/8" (92.1)
1 9/16" (39.7)
1 11/16" (42.9)
3 1/2" (88.9)
SEE NOTES 2,3,4
LIQUID LINES
SEE NOTES 2,3,4
1 3/16" (30.16)
45 1/8"
(1146.2)
(4) - HOLE FOR
HORIZONTAL SUSPENSION
(4) HOLE FOR
HORIZONTAL
SUSPENSION
SUPPLY OPENING
6 3/4"
(171.45)
BOTTOM RETURN
54 1/16"
(1373.2)
36 7/8"
(936.6)
SIDE RETURN
FILTER
10 7/16"
(265.1)
BOTTOM RETURN
SUPPLY VERTICAL RETURN HORIZONTAL /
RETURN VERTICAL
SSP-PRC024J-EN
SIDE RETURN
SUPPLY HORIZONTAL RETURN VERTICAL /
RETURN HORIZONTAL
87
Dimensional Data
Figure 16.
6–6.25 ton air handler, dual circuit
NOTES:
1. PANEL DEPTH 1/2" (12.7) (TYP. ALL PANELS).
2. REMOVABLE DRAIN PAN AND ATTACHED DRAIN CONNECTION MAY BE INSTALLED ON END
OF UNIT IN EITHER THE VERTICAL OR HORIZONTAL CONFIGURATION, PLASTIC DRAIN PAN
ACCESS PLATE ON THE END OF UNIT OPPOSITE DRAIN CONNECTION MUST BE REMOVED TO
SLIDE DRAIN PAN OUT OF UNIT FOR CLEANING. ACCESS PLATE MUST BE RE-INSTALLED AFTER
SLIDING DRAIN PAN BACK INTO UNIT.
3. IF PERIODIC DRAIN PAN CLEANING IS REQUIRED, ALLOW ROOM FOR PARTIAL REMOVAL OF
DRAIN PAN CONNECTION AT END OF UNIT.
4. 1" (25.4) FEMALE SCHED. 40 (10.2) PVC PIPE DRAIN CONNECTION VERTICAL CONFIGURATION.
5. 1" (25.4) FEMALE SCHED. 40 (10.2) PVC PIPE DRAIN CONNECTION HORIZONTAL CONFIGURATION.
25 1/2"
(647.7)
DUCT FLANGE
1" (25.4)
HEIGHT
16 1/4"
(412.8)
.70"
(17.78)
11 11/16"
(296.9)
47 1/2"
(1206.5)
SUPPLY
OPEN
24 1/16"
(611.2)
12 5/16"
8 5/16"
(312.7)
(211.1)
HEATER CONTROL
AND SINGLE POWER
ENTRY WIRES
16 1/16"
(408)
SIDE RETURN
16 7/8"
(406.4)
BOTTOM RETURN
2 1/4" (57.15)
HEATER
VENTILATION
1 9/16"
(39.7)
2 3/4"
(69.9)
6 13/16" (173)
CONTROL WIRING
25 1/2"
(647.7)
1 13/16"
(46)
42"
(1066.8)
2 3/4"
(69.9)
42"
(1066.8)
3 1/2" (88.9)
LINE VOLTAGE
CONTROL BOX
ACCESS PANEL
COPPER LIQUID LINE
FIELD CONNECTION
8 13/16" (223.8)
16"
(406.4)
1 3/16" (30.2)
DRAIN CONNECTION
FOR HORIZONTAL
(SEE NOTE 2,3,5)
COPPER SUCTION LINE
FIELD CONNECTION
(2) REMOTE BULB TXV
SUCTION LINE
22 7/8"
(581)
16 1/4"
11 1/16" 13 3/4" (412.8)
(349.2)
(281)
16 3/4"
(425.5)
19 1/16"
(484.2)
20 1/16"
(509.6)
1 5/16" (33.3)
FILTER ACCESS PANEL
22" (559) MIN. DISTANCE
BOTH SIDE
20 1/16"
(509.6) 16 3/4" 16 1/4" 13 3/4"
(425.5) (412.8) (349.3)
1 5/16" (33.3)
1 5/8" (41.3)
SEE NOTES 2,3,4
1 5/8" (41.3)
3 5/8" (92.1)
3 5/8" (92.1)
LIQUID LINES
SEE NOTES 2,3,4
1 3/16" (30.2)
45 1/8"
(1146.2)
(4) - HOLE FOR HORIZONTAL
SUSPENSION
SUPPLY OPENING
(4) HOLE FOR
HORIZONTAL
SUSPENSION
6 3/4"
(171.5)
BOTTOM RETURN
54 1/16"
(1373.2)
36 7/8"
(936.6)
SIDE RETURN
FILTER
10 7/16"
(265.1)
BOTTOM RETURN
SUPPLY VERTICAL RETURN HORIZONTAL /
RETURN VERTICAL
88
SIDE RETURN
SUPPLY HORIZONTAL RETURN VERTICAL /
RETURN HORIZONTAL
SSP-PRC024J-EN
Dimensional Data
Figure 17.
8.33 ton air handler, single circuit
NOTES:
1. PANEL DEPTH 1/2" (12.7) (TYP. ALL PANELS).
2. REMOVABLE DRAIN PAN AND ATTACHED DRAIN CONNECTION MAY BE INSTALLED ON END
OF UNIT IN EITHER THE VERTICAL OR HORIZONTAL CONFIGURATION, PLASTIC DRAIN PAN
ACCESS PLATE ON THE END OF UNIT OPPOSITE DRAIN CONNECTION MUST BE REMOVED TO
SLIDE DRAIN PAN OUT OF UNIT FOR CLEANING. ACCESS PLATE MUST BE RE-INSTALLED AFTER
SLIDING DRAIN PAN BACK INTO UNIT.
3. IF PERIODIC DRAIN PAN CLEANING IS REQUIRED, ALLOW ROOM FOR PARTIAL REMOVAL OF
DRAIN PAN CONNECTION AT END OF UNIT.
4. 1" (25.4) FEMALE SCHED. 40 (10.2) PVC PIPE DRAIN CONNECTION VERTICAL CONFIGURATION.
5. 1" (25.4) FEMALE SCHED. 40 (10.2) PVC PIPE DRAIN CONNECTION HORIZONTAL CONFIGURATION.
25 1/2"
(647.7)
16 1/4"
(412.8)
DUCT FLANGE
1" (25.4)
HEIGHT
.70" (17.8)
19 11/16"
(500.1)
24 1/16"
(611.2)
63 1/2"
(1612.9)
SUPPLY
OPEN
HEATER CONTROL
AND SINGLE POWER
ENTRY WIRES
15 15/16"
(404.8)
16 5/16"
(414.3)
20 5/16"
(515.9)
SIDE RETURN
1 11/16"
(42.9)
BOTTOM RETURN
1 13/16"
(46)
58"
(1473.2)
2 3/4"
(69.8)
HEATER
VENTILATION
16 7/8"
(428.6)
58"
(1473.2)
2 3/4"
(69.8)
2 1/4" (57.2)
6 13/16" (173)
25 1/2"
(647.7)
CONTROL WIRING
3 1/2" (89)
LINE VOLTAGE
8 7/8"
(225.4) 16 1/16"
(408)
CONTROL BOX
ACCESS PANEL
DRAIN CONNECTION
FOR HORIZONTAL
(SEE NOTE 2,3,5)
22 7/8"
(581)
1 3/16"
(30.2)
FILTER ACCESS PANEL
22" (559) MIN. DISTANCE
BOTH SIDE
COPPER LIQUID LINE
FIELD CONNECTION
REMOTE BULB TXV
COPPER SUCTION LINE
FIELD CONNECTION
SUCTION LINE
16 11/16"
(423.9)
17 3/8"
(441.4)
20"
(508)
17 3/8"
(441.3)
16 11/16"
(423.9)
1 11/16" (42.9)
3 5/8" (92.1)
3 5/8" (92.1)
1 11/16" (42.9)
SEE NOTES
2,3,4
LIQUID LINES
SEE NOTES 2,3,4
63 1/2"
(1613)
1 3/16" (30.2)
(4) - HOLE FOR
HORIZONTAL
SUSPENSION
61 1/8"
(1552.6)
(4) HOLE FOR
HORIZONTAL
SUSPENSION
SUPPLY OPENING
BOTTOM RETURN
6 3/4"
(171.45)
SIDE RETURN
54 1/16"
(1373.2)
36 7/8"
(936.63)
FILTER
SIDE RETURN
BOTTOM RETURN
10 7/16" (265.1)
SSP-PRC024J-EN
SUPPLY VERTICAL RETURN HORIZONTAL /
RETURN VERTICAL
SUPPLY HORIZONTAL RETURN VERTICAL /
RETURN HORIZONTAL
89
Dimensional Data
Figure 18.
8.33 ton air handler, dual circuit
NOTES:
1. PANEL DEPTH 1/2" (12.7) (TYP. ALL PANELS).
2. REMOVABLE DRAIN PAN AND ATTACHED DRAIN CONNECTION MAY BE INSTALLED ON END
OF UNIT IN EITHER THE VERTICAL OR HORIZONTAL CONFIGURATION, PLASTIC DRAIN PAN
ACCESS PLATE ON THE END OF UNIT OPPOSITE DRAIN CONNECTION MUST BE REMOVED TO
SLIDE DRAIN PAN OUT OF UNIT FOR CLEANING. ACCESS PLATE MUST BE RE-INSTALLED AFTER
SLIDING DRAIN PAN BACK INTO UNIT.
3. IF PERIODIC DRAIN PAN CLEANING IS REQUIRED, ALLOW ROOM FOR PARTIAL REMOVAL OF
DRAIN PAN CONNECTION AT END OF UNIT.
4. 1" (25.4) FEMALE SCHED. 40 (10.2) PVC PIPE DRAIN CONNECTION VERTICAL CONFIGURATION.
5. 1" (25.4) FEMALE SCHED. 40 (10.2) PVC PIPE DRAIN CONNECTION HORIZONTAL CONFIGURATION.
25 1/2"
(647.7)
16 1/4"
(412.7)
DUCT FLANGE
1" (25.4)
HEIGHT
.70" (17.8)
19 11/16"
(500.1)
24 1/16"
(611.2)
63 1/2"
(1613)
SUPPLY
OPEN
15 15/16"
(404.8)
HEATER CONTROL
AND SINGLE POWER
ENTRY WIRES
20 5/16"
16 5/16" (515.9)
(414.3)
HEATER
VENTILATION
1 11/16"
(42.9)
BOTTOM RETURN
1 13/16"
(46)
58"
(1473.2)
2 3/4"
(69.8)
2 1/4" (57.15)
16 7/8"
(428.6)
SIDE RETURN
58"
(1473.2)
2 3/4"
(69.8)
6 13/16" (173)
25 1/2"
(647.7)
CONTROL WIRING
3 1/2" (89)
LINE VOLTAGE
8 7/8"
(225.4) 16 1/16"
(408)
CONTROL BOX
ACCESS PANEL
DRAIN CONNECTION
FOR HORIZONTAL
(SEE NOTE 2,3,5)
22 7/8"
(581)
COPPER LIQUID LINE
FIELD CONNECTION
(2) REMOTE BULB TXV
COPPER SUCTION LINE
FIELD CONNECTION
SUCTION LINE
1 3/16"
(30.2)
FILTER ACCESS PANEL
22" (558.8) MIN. DISTANCE
BOTH SIDE
13 11/16"
11" (279.4) (347.7)
20"
(508)
19"
16 1/4" 16 11/16"
(423.9) (482.6)
(412.8)
20 1/16"
16 3/4" 16 1/4" 13 3/4"
(509.6)
(425.5) (412.8) (349.3)
1 5/16" (33.4)
1 5/16" (33.3)
1 5/8" (41.3)
1 5/8" (41.3)
3 5/8" (92.1)
3 5/8" (92.1)
SEE NOTES
2,3,4
LIQUID LINES
SEE NOTES 2,3,4
(4) - HOLE FOR HORIZONTAL
SUSPENSION
1 3/16"
(30.2)
61 1/8"
(1552.6)
SUPPLY OPENING
6 3/4"
(171.45)
(4) HOLE FOR
HORIZONTAL
SUSPENSION
BOTTOM RETURN
SIDE RETURN
54 1/16"
(1373.2)
36 7/8"
(936.6)
FILTER
BOTTOM RETURN
10 7/16" (265.1)
90
SUPPLY VERTICAL RETURN HORIZONTAL /
RETURN VERTICAL
SIDE RETURN
SUPPLY HORIZONTAL RETURN VERTICAL /
RETURN HORIZONTAL
SSP-PRC024J-EN
Dimensional Data
Figure 19.
10.4, 13 ton air handler, dual circuit
NOTES:
1. PANEL DEPTH 1/2" (12.7) (TYP. ALL PANELS).
2. REMOVABLE DRAIN PAN AND ATTACHED DRAIN CONNECTION MAY BE INSTALLED ON END
OF UNIT IN EITHER THE VERTICAL OR HORIZONTAL CONFIGURATION, PLASTIC DRAIN PAN
ACCESS PLATE ON THE END OF UNIT OPPOSITE DRAIN CONNECTION MUST BE REMOVED TO
SLIDE DRAIN PAN OUT OF UNIT FOR CLEANING. ACCESS PLATE MUST BE RE-INSTALLED AFTER SLIDING
DRAIN PAN BACK INTO UNIT.
3. IF PERIODIC DRAIN PAN CLEANING IS REQUIRED, ALLOW ROOM FOR PARTIAL REMOVAL OF
DRAIN PAN CONNECTION AT END OF UNIT.
4. 1" (25.4) FEMALE SCHED. 40 (10.2) PVC PIPE DRAIN CONNECTION VERTICAL CONFIGURATION.
5. 1" (25.4) FEMALE SCHED. 40 (10.2) PVC PIPE DRAIN CONNECTION HORIZONTAL CONFIGURATION.
29 1/16"
(738.2)
16 5/16"
(414.3)
DUCT FLANGE
1" (25.4)
HEIGHT
2 7/8" (73)
12 3/8" (314.3)
SUPPLY
OPEN
79 9/16"
(2020.9)
54 15/16"
(1395.4)
17 7/8"
(454)
SUPPLY
OPEN
12 1/8"
(308)
HEATER CONTROL
AND SINGLE POWER
ENTRY WIRES
SIDE RETURN
19 1/2"
(495.3)
SIDE RETURN
BOTTOM RETURN
BOTTOM RETURN
3 7/16" (87.3)
3 5/16" (84.1)
2 3/4"
(69.8)
74 1/8"
(1882.8)
2 3/4"
(69.8)
74 1/8"
(1882.8)
4 5/16" (109.5)
29 1/16"
(738.2)
CONTROL WIRING
LINE VOLTAGE
4 1/4" (108)
12 13/16" (325.4)
20"
(508)
CONTROL BOX
ACCESS PANEL
COPPER LIQUID LINE
FIELD CONNECTION
DRAIN CONNECTION
FOR HORIZONTAL
(SEE NOTE 2,3,5)
25 1/8"
(638.2)
(2) REMOTE BULB TXV
COPPER SUCTION LINE
FIELD CONNECTION
SUCTION LINE
1 1/4"
(31.8)
12" (304.8)
FILTER ACCESS PANEL
32" (813) MIN.
DISTANCE
BOTH SIDE
15 13/16" 18 5/16" 18 11/16"
(474.7)
(465.1)
(401.6)
21 1/2"
(546.1)
22"
(558.8)
21 1/2"
(546.1)
18 11/16"
(474.6)
18 3/8"
(466.7)
15 13/16"
(401.64)
2" (50.8)
1 5/16" (33.3)
SEE NOTES
2,3,4
2 5/16" (58.7)
2 1/8" (54)
2 7/16" (62)
4 1/4" (108)
4 1/8" (104.8)
LIQUID LINES
(4) - HOLE FOR HORIZONTAL
SUSPENSION
SEE NOTES 2,3,4
79 5/8"
(2022.5)
1 3/16"
(30.2)
(4) HOLE FOR
HORIZONTAL
SUSPENSION
SUPPLY OPENING
77 3/16"
(1960.6)
BOTTOM RETURN
9 5/8"
(244.5)
SIDE RETURN
69 1/16"
(1754.2)
48"
(1219.2)
FILTER
BOTTOM RETURN
11 7/16" (290.5)
SSP-PRC024J-EN
SUPPLY VERTICAL RETURN HORIZONTAL /
RETURN VERTICAL
SIDE RETURN
SUPPLY HORIZONTAL RETURN VERTICAL /
RETURN HORIZONTAL
91
Dimensional Data
Figure 20.
16.7 ton air handler, dual circuit
31 1/8"
(790.6)
NOTES:
1. PANEL DEPTH 1/2" (12.7) (TYP. ALL PANELS).
2. REMOVABLE DRAIN PAN AND ATTACHED DRAIN CONNECTION MAY BE INSTALLED ON END
OF UNIT IN EITHER THE VERTICAL OR HORIZONTAL CONFIGURATION, PLASTIC DRAIN PAN
ACCESS PLATE ON THE END OF UNIT OPPOSITE DRAIN CONNECTION MUST BE REMOVED TO
SLIDE DRAIN PAN OUT OF UNIT CLEANING. ACCESS PLATE MUST BE RE-INSTALLED AFTER
SLIDING DRAIN PAN BACK INTO UNIT.
3. IF PERIODIC DRAIN PAN CLEANING IS REQUIRED, ALLOW ROOM FOR PARTIAL REMOVAL OF
DRAIN PAN CONNECTION AT END OF UNIT.
4. 1" (25.4) FEMALE SCHED .40 (10.2) PVC PIPE DRAIN CONNECTION VERTICAL CONFIGURATION.
5. 1" (25.4) FEMALE SCHED .40 (10.2) PVC PIPE DRAIN CONNECTION HORIZONTAL CONFIGURATION.
16 5/16"
(414.3)
DUCT FLANGE
1" (25.4)
HEIGHT
4 15/16" (125.4)
18 7/8"
(479.4)
SUPPLY
OPEN
92 9/16"
(2351.1)
54 15/16"
(1395.4)
20 15/16"
(531.8)
HEATER CONTROL
AND SINGLE POWER
ENTRY WIRES
CONTROL WIRING
6 7/16" (163.5)
31 1/8"
(790.6)
SIDE RETURN
20 15/16"
(531.8)
SIDE RETURN
18 5/8"
(473.1)
3"
(76.2)
4 3/4"
(120.6)
BOTTOM RETURN
2 15/16"
(74.6)
4 3/4"
(120.6)
83 1/8"
(2111.4)
BOTTOM RETURN
83 1/8"
(2111.4)
4 1/4" (108)
LINE VOLTAGE
20" (508)
CONTROL BOX
ACCESS PANEL
DRAIN CONNECTION
FOR HORIZONTAL
(SEE NOTE 2,3,5)
COPPER LIQUID LINE
FIELD CONNECTION
12 13/16"
(325.4)
REMOTE BULB TXV
COPPER SUCTION LINE
FIELD CONNECTION
SUCTION LINE
28 1/2"
(724)
1 3/16"
(30.2)
FILTER ACCESS PANEL
32" (813) MIN. DISTANCE
BOTH SIDE
LIQUID LINES
SEE NOTES 2,3,4
1 11/16"
(42.9)
25 1/2"
18 3/8" 19 1/8" 21 3/8" 21 13/16" (647.7) 25 1/2" 21 13/16"
12 7/8" 15 7/8" (466.7) (485.8) (542.9) (554)
(647.7)
19 1/8" 18 3/8" 15 7/8"
(554)
(327) (403.2)
(485.8) (466.7) (403.2)
SEE NOTES
2,3,4
1 11/16" (42.9)
1 15/16" (49.2)
1 9/16" (39.7)
3 3/8" (85.7)
1 7/8" (47.6)
4" (101.6)
3 1/4" (82.5)
(4) - HOLE FOR HORIZONTAL
SUSPENSION
92 9/16"
(2351.1)
89 3/16"
(2265.4)
3 7/8" (98.4)
9 5/8"
(244.5)
71 7/8" 50 13/16"
(1825.6) (1290.6)
SIDE RETURN
SIDE RETURN
FILTER
BOTTOM RETURN
11 7/16"
(290.5)
92
(4) HOLE FOR
HORIZONTAL
SUSPENSION
SUPPLY OPENING
BOTTOM RETURN
SUPPLY VERTICAL RETURN HORIZONTAL /
RETURN VERTICAL
SUPPLY HORIZONTAL RETURN VERTICAL /
RETURN HORIZONTAL
SSP-PRC024J-EN
Dimensional Data
Accessories
Figure 21.
Table 83.
Rubber isolator accessory dimensions
Rubber isolator accessory dimensions
Model No.
L
W
H
A
B
C
D
E
BAYISLT004
3-1/8 (79.375) 1-3/4 (44.45)
1-1/4 (31.75)
1-1/4 (31.75)
3/8 (9.525)
2-3/8 (60.325)
3/8 (9.525)
1/4 (6.35)
BAYISLT005
3-7/8 (98.425) 2-3/8 (60.325) 1-3/4 (44.45)
1-3/4 (44.45)
3/8 (9.525)
3 (76.2)
3/8 (9.525)
1/4 (6.35)
BAYISLT009
3-7/8 (98.425) 2-3/8 (60.325) 1-3/4 (44.45)
1-3/4 (44.45)
3/8 (9.525)
3 (76.2)
3/8 (9.525)
1/4 (6.35)
BAYISLT010
3-7/8 (98.425) 2-3/8 (60.325) 1-3/4 (44.45)
1-3/4 (44.45)
3/8 (9.525)
3 (76.2)
3/8 (9.525)
1/4 (6.35)
BAYISLT013
2-1/4 (57.15)
2 (50.8)
3 (76.2)
1-3/8 (34.925)
3/4 (19.05)
3/8 (9.525)
1/2 (12.7)
—
BAYISLT014
2-1/4 (57.15)
2 (50.8)
3 (76.2)
1-3/8 (34.925)
3/4 (19.05)
3/8 (9.525)
1/2 (12.7)
—
BAYISLT015
2-1/4 (57.15)
2 (50.8)
3 (76.2)
1-3/8 (34.925)
3/4 (19.05)
3/8 (9.525)
1/2 (12.7)
—
BAYISLT012
3 (76.2)
2-1/4 (57.15)
4-1/2 (114.3) 1-7/8 (47.625)
1/4 (6.35)
5/8 (15.875)
3/4 (19.05)
—
BAYISLT015(a)
3 (76.2)
2-1/4 (57.15)
4-1/2 (114.3) 1-7/8 (47.625)
1/4 (6.35)
5/8 (15.875)
3/4 (19.05)
—
BAYISLT016
3 (76.2)
2-1/4 (57.15)
4-1/2 (114.3) 1-7/8 (47.625)
1/4 (6.35)
5/8 (15.875)
3/4 (19.05)
—
Note: BAYISLT015 contains a quantity 2 of the 2-1/4 x 2 x 3 isolators and quantity of 3 of the 3 x 2-1/4 x 4-1/2 isolators.
SSP-PRC024J-EN
93
Dimensional Data
Figure 22.
Spring isolator accessory dimensions – inches (millimeters)
Figure 23.
Electric heater accessory for 4.6-8.3 ton air handlers – inches (millimeters)
94
SSP-PRC024J-EN
Dimensional Data
Figure 24.
Electric heater accessory for 10.4-16.7 ton air handlers – inches (millimeters)
SSP-PRC024J-EN
95
Dimensional Data
Figure 25.
Hot water coil accessory – inches (millimeters)
J
DUCT OPENING
H
DUCT OPENING
1"
(25.4)
N
K
DUCT FLANGE
16" (406.4)
P
M
1"
(25.4)
C
L
"D" # HOLES EQUALLY
SPACED AT "E" APART
A
F
3" (76.2) DIA.
HOLE FOR "Q"
(RETURN)
B
1/4" (6.3) DIA.
"G" HOLES
2 1/8"
(54)
3 7/8"
(98.4)
3" (76.2) DIA. HOLE
FOR "Q" (SUPPLY)
Table 84.
AIR HANDLER
MATING SURFACE
Hot water coil accessory – inches (millimeters)
Model No.
A
B
C
D
E
F
G
H
BAYWATR027
38.14 (969)
22.74 (576)
13.74 (349)
5 (127)
9 (229)
13.65 (347)
16 (406)
26 (660)
BAYWATR028
47.74 (1213)
25.74 (654)
15.95 (405)
5 (127)
10.84 (275)
17.17 (436)
16 (406)
30 (762)
BAYWATR029
63.84 (1621)
25.74 (654)
15.95 (405)
6 (152)
11.84 (301)
17.16 (436)
18 (457)
36 (914)
BAYWATR030
79.74 (2025)
29.18 (741)
14.36 (365)
8 (203)
10.85 (276)
19.67 (500)
22 (559)
51 (1295)
BAYWATR031
92.74 (2356)
31.24 (793)
16.48 (419)
8 (203)
10.85 (276)
19.67 (500)
22 (559)
64 (1626)
Model No.
J
K
L
M
N
P
Q
BAYWATR027
12 (305)
6 (152)
4.94 (125)
7.79 (198)
2.88 (73)
10.24 (260)
2 NPT (51) NPTI
BAYWATR028
18 (457)
8.88 (225)
8.45 (215)
10.27 (261)
2.88 (73)
7.77 (197)
BAYWATR029
18 (457)
13.88 (352)
8.45 (215)
10.03 (255)
2.88 (73)
7.58 (192)
BAYWATR030
18 (457)
14.25 (362)
6.86 (174)
9.91 (252)
1.88 (48)
7.41 (188)
BAYWATR031
18 (457)
14.25 (362)
8.98 (228)
9.88 (251)
3.75 (95)
7.38 (187)
2.5 NPTI (64)
NPTI
2.5 NPTI (64)
NPTI
2.5 NPTI (64)
NPTI
2.5 NPTI (64)
NPTI
Note: Hot Water Coil Dimensions - inches (millimeters)
96
SSP-PRC024J-EN
Dimensional Data
Figure 26.
Table 85.
Steam coil accessory – inches (millimeters)
Steam coil accessory – inches (millimeters)
Model No.
A
B
C
BAYWATR022 38.14 (969) 22.74 (577) 14.32 (364)
BAYWATR023
BAYWATR024
BAYWATR025
BAYWATR026
47.74
(1212)
63.84
(1621)
79.74
(2025)
92.74
(2355)
D
E
F
G
5 (127)
9 (229)
13.67 (347)
16 (406)
10.88 (276) 11.17 (284)
2 (51)
J
K
25.74 (654) 20.14 (511)
5 (127)
10.84 (275) 17.17 (436)
16 (406)
10.88 (276) 11.17 (284)
2 (51)
25.74 (654) 20.14 (511)
6 (152)
11.87 (301) 17.16 (436)
18 (457)
13.70 (348) 10.57 (268)
2.5 (64)
29.18 (741) 18.55 (471)
8 (203)
10.85 (275) 19.67 (500)
22 (559)
12.11 (308) 10.05 (255)
2.5 (64)
31.24 (793) 20.67 (525)
8 (203)
10.85 (275) 19.67 (500)
22 (559)
14.23 (361) 10.01 (254)
2.5 (64)
Model No.
L
M
N
P
Q
R
BAYWATR022
1.5 (38)
26 (660)
12 (305)
6 (152)
2.87 (73)
9.95 (253)
BAYWATR023
2 (51)
30 (762)
18 (457)
8.87 (225)
2.87 (73)
9.95 (253)
BAYWATR024
2 (51)
36 (914)
18 (457)
13.87 (352)
2.87 (73)
9.13 (232)
BAYWATR025
2 (51)
51 (1295)
18 (457)
14.12 (359)
1.87 (48)
8.61 (219)
BAYWATR026
2 (51)
64 (1626)
18 (457)
14.12 (359)
3.75 (95)
8.58 (218)
SSP-PRC024J-EN
H
97
Dimensional Data
Figure 27.
Discharge plenum and grille accessory
C
A
B
Table 86.
Discharge plenum and grille dimensions – no heat – inches (millimeters)
Unit
Model No.(a)
A
B
C
TWE051
BAYPLNM015
37.94 (963.6)
21.94 (557.2)
28 (711.2)
TWE072, TWE076
BAYPLNM016
47.5 (1206.5)
24.99 (634.7)
28 (711.2)
TWE101
BAYPLNM017
63.5 (1612.9)
24.99 (634.7)
28 (711.2)
TWE126, TWE156
BAYPLNM018(b)
79.5 (2019.3)
27.63 (701.8)
22 (558.8)
TWE201
BAYPLNM019(b)
92.5 (2349.5)
30.43 (772.9)
24 (609.6)
(a)
(b)
When installed horizontally, plenum/water coil must be self-supported.
For use with hydronic heat or no heat.
Figure 28.
Discharge plenum and grille accessory
C
A
B
Table 87.
98
Discharge plenum and grille dimensions – inches (millimeters) – (for use with electric heat)
Tons
Model No.
A
B
C
TWE051
TWE072,
TWE076
TWE101
BAYPLNM030
38.07 (967)
22.69 (576.3)
29.05 (738)
BAYPLNM031
47.86 (1216)
25.69 (652.5)
29.05 (738)
BAYPLNM032
63.86 (1622)
25.69 (652.5)
29.05 (738)
SSP-PRC024J-EN
Dimensional Data
Table 87.
Discharge plenum and grille dimensions – inches (millimeters) – (for use with electric heat) (continued)
Tons
TWE126,
TWE156
TWE201
Model No.
A
B
C
BAYPLNM033
80.14 (2036)
29.10 (739.1)
35.11 (892)
BAYPLNM034
92.96 (2361)
31.10 (789.9)
35.05 (890)
Figure 29.
Subbase accessory – inches (millimeters)
Table 88.
Subbase dimensions – inches (millimeters)
Tons
Model No.
A
B
TWE051
BAYBASE009
38 (965.2)
22.63 (574.8)
BAYBASE010
47.5 (1206.5)
25.51 (648.0)
BAYBASE011
63.5 (1612.9)
25.52 (648.2)
TWE072,
TWE076
TWE101
TWE126,
TWE156
TWE201
SSP-PRC024J-EN
BAYBASE012
79.5 (2019.3)
29.04 (737.6)
BAYBASE013
92.5 (2349.5)
31.14 (791.0)
99
Weights
Heat Pump Condenser
Table 89.
TWA unit and corner weights — kg (50 Hz)
Corner Weights
Model No.
Shipping
Max (kg)
Net Max
(kg)
1
2
3
4
TWA0604DA
164
149
51
38
25
34
TWA0604DD
189
163
58
38
41
26
TWA0764DA
174
151
38
53
27
33
TWA0764DD
213
187
67
44
47
30
TWA1014DA
225
212
75
49
53
34
TWA1014DD
219
199
71
46
50
32
13
TWA1564DD
398
347
107
76
89
74
16.7
TWA2014DD
456
385
115
121
67
82
Tons
5
6.25
8.33
Figure 30.
Figure 31.
TWA060, 076, 101
TWA156, 201
#4
#3
#4
#1
#1
#3
#2
SER
ACC VICE
ESS
LIFTING HOLES
(BOTH SIDES)
100
#2
SER
ACC VICE
ESS
SER
ACC VICE
ESS
LIFTING HOLES
(BOTH SIDES)
SSP-PRC024J-EN
Weights
Air Handler
Table 90.
Standard air handler (TWE) — unit and corner weights - (50 Hz)
1
2
3
4
1
2
3
4
4.6
TWE0514DA
285
232
55
71
51
55
54
67
50
61
6
TWE0724DB
385
323
67
99
75
82
56
92
87
88
6.25
TWE0764DA/B
385
323
67
99
75
82
56
92
87
88
8.33
TWE1014DA/B
441
393
77
121
110
85
79
118
77
119
10.4
TWE1264DB
753
676
168
192
181
135
196
164
145
171
13
TWE1564DB
752
675
167
192
181
135
196
163
145
171
16.7
TWE2014DB
912
818
258
168
161
231
256
181
146
235
Figure 32.
Vertical — TWE051, 072, 076, 101
Control Box Access
Top View
Figure 33.
Vertical — TWE126, 156, 201
Control Box Access
Top View
Figure 34.
Horizontal — TWE051, 072, 076, 101
Top View
Control Box
Access
SSP-PRC024J-EN
101
Weights
Figure 35.
Horizontal — TWE126, 156, 201
Top View
Control Box
Access
102
SSP-PRC024J-EN
Weights
Accessories
Table 91.
Accessory weights (net lbs.)
Discharge
Discharge
Plenum Discharge Plenum
and Grille Plenum and Grille
Unit
with
and Grille
with
Electric
Used with Hot Water
Hydronic
without
Electric Return Air Heat Min/
Tons
Coil
Steam Coil
Heat
Heat
Heat
Grille
Max
5
86
94
63
58
115
Subbase
Oversized
Motor
3
32/43
14.4
31
6.25
116
131
78
73
160
5
27/45
19.4
48
8.33
165
148
97
92
195
7
27/45
23.5
50
10.4
211
234
—
230
235
10
79/100
28.4
80
13
211
234
—
230
235
10
79/100
28.4
80
16.7
242
261
—
145
265
12
79/100
31.7
88
Unit
Used with
Tons
RIS
Isolator
Floor
Mount
RIS
Isolator
Suspended Mount
Steel
Spring
Isolator
Floor
Mount
Steel
Spring
Isolator
Suspended Mount
Hail
Guard
Control
Transformer
Sensors
Modulating Low
Ambient
On/Off
Low
Ambient
5
2
9
12
6
21
—
—
—
—
6.25
2
6
12
6
21
—
—
—
—
8.33
2
7
12
6
28
—
—
—
—
10.4
2
7
12
6
33
—
—
—
—
13
2
7
12
6
55
—
—
—
—
16.7
2
9
12
6
55
—
—
—
—
SSP-PRC024J-EN
103
Mechanical Specifications
Condensing Units
Standard Options
General
•
•
•
•
•
•
•
Weatherproofed steel mounting/lifting rails
Hermetic scroll compressors
Plate fin condenser coils
Fans and motors
Standard operating range 50-125°F (min. 0°F with low ambient accessory)
Nitrogen holding charge
Casing
•
•
•
•
•
•
Zinc coated, heavy gauge, galvanized steel
Weather resistant baked enamel finish
Meets ASTM B117, 672 hour salt spray test
Removable single side maintenance access panels
Lifting handles in maintenance access panels
Unit base provisions for forklift and/or crane lifting
Refrigeration System - Single Compressor (TWA060**A, TWA076**A,
TWA101**A)
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
Single refrigeration circuit with integral subcooling circuit
Single direct drive hermetic scroll compressor
Suction gas-cooled motor w/ ± 10% voltage utilization range of unit nameplate voltage
Reversing valve
Crankcase heater
Internal temperature and current sensitive motor overloads
No compressor suction and/or discharge valves (reduced vibration/sound)
Factory installed liquid line filter drier
Phase loss/reverse rotation monitor
Liquid line service valve (with gauge port)
Suction line service valve (with gauge port)
External high pressure cutout device
External low pressure cutout device
Evaporator defrost control
Loss of charge protection (discharge temperature limit)
Refrigeration System - Dual Compressor (TWA060**D, TWA076**D,
TWA101**D, TWA156**D, TWA201**D)
•
•
•
•
•
•
•
•
•
•
•
•
104
Two (2) separate and independent refrigerant circuits
Each refrigeration circuit equipped with integral subcooling circuit
Two (2) direct drive hermetic scroll compressor
Suction gas-cooled motors w/ ± 10% voltage utilization range of unit nameplate voltage
Reversing valves
Crankcase Heaters
Internal temperature and current sensitive motor overloads
Factory installed liquid line filter driers
Phase loss/reverse rotation monitor
Liquid line service valves (with gauge port)
Suction line service valves (with gauge port)
No compressor suction and/or discharge valves (reduced vibration/sound)
SSP-PRC024J-EN
Mechanical Specifications
•
•
•
•
External high pressure cutout devices
External low pressure cutout devices
Evaporator defrost control
Loss of charge protection (discharge temperature limit)
Condenser Coil (Fin and Tube)
•
•
•
•
3/8” internally enhanced copper tube
Mechanically bonded to lanced aluminum plate fins
Factory pressure and leak tested to 660 psig
Perforated steel hail guards available (factory installed option or field installed accessory)
Condenser Fan
•
•
•
26" or 28" propeller fan(s)
Direct drive
Statically and dynamically balanced
Condenser Motor(s)
•
•
•
Permanently lubricated totally enclosed or open construction
Built-in current and thermal overloads
Ball or sleeve bearing type
Controls
•
•
•
•
•
•
•
•
•
Centralized microprocessor
Indoor and outdoor temperature sensors drive algorithms, making decisions for all heating,
cooling, and ventilation
Integrated anti-short cycle timer
Integrated time delay between compressors
Completely internally wired
Numbered and colored wires
Contactor pressure lugs or terminal block
Unit external mounting location for disconnect device
Single point power entry
Factory Installed Options
Hail Guards
•
•
•
Condenser coil protection from hail, vandals, etc.
Perforated, painted galvanized steel
Factory or field installed
Black Epoxy Coated Condenser Coil (Fin and Tube)
•
•
•
Thermoset vinyl coating
Bonded to aluminum fin stock (prior to fin-stamping process)
Economical protectant in mildly corrosive environments
LonTalk Communication Interface
•
•
•
•
Factory or field installed
Communications board
Allows unit communication as a Tracer™ LCI-R device
Allows unit communication with generic LonTalk® Network building automation controls
Controls: Microprocessor
•
•
•
•
SSP-PRC024J-EN
Centralized processor
Indoor and outdoor temperature sensors drive algorithms, making decisions for all heating,
cooling, and ventilation
Integrated anti-short cycle timer
Integrated time delay between compressors
105
Mechanical Specifications
Field Installed Options
Low Ambient (Fan ON/OFF)
•
•
•
•
Provides unit cooling operation to outdoor ambient of 0°F
Low cost solution
Liquid line temperature controls condenser fan operation
1 kit per condenser fan required
Low Ambient (Modulating)
•
•
•
•
Provides unit cooling operation to outdoor ambient of 0°F
“Wave-chopper”
Discharge line pressure controls condenser fan operation
1 kit per condenser fan required
Vibration Isolators
•
•
•
Neoprene-in-shear or spring flex choice
Reduce vibration transmission to building structures, equipment, and adjacent spaces
Reduce noise transmission to building structures, equipment, and adjacent spaces
Zone Sensor
•
•
•
•
•
Interfaces with microprocessor units
Manual or automatic programmable
System malfunction lights
Remote sensor options
Wireless option
Thermostat
•
•
•
•
1H/1C available
2H/1C available
Manual or automatic changeover available
Programmable and non-programmable solutions available
LonTalk Communication Interface
•
•
•
•
Factory or field installed
Communications board
Allows unit communication as a Tracer™ LCI-R device
Allows unit communication with generic LonTalk® Network building automation controls
BACnet Communication Interface
•
Communicates directly with a generic open protocol BACnet MS/TP Network building
automation system control
Air Handlers
Standard Options
General
•
•
•
•
•
•
Completely factory assembled
Convertible for horizontal or vertical configuration
Convertible for cooling only or heat pump application
Convertible for left or right external connections (refrigerant and/or electrical)
Convertible for front or bottom air return
Nitrogen holding charge
Casing
•
•
106
Zinc coated, heavy gauge, galvanized steel
Weather resistant baked enamel finish
SSP-PRC024J-EN
Mechanical Specifications
•
•
•
•
•
•
Access panels with captive screws
Completely insulated with foil faced, cleanable, fire retardant, permanent, odorless glass fiber
material
Captured or sealed insulation edges
Electrical connection bushings or plugs
Refrigerant connection bushings or plugs
Withstand elevated internal static pressure
Refrigeration System
•
•
•
Single or dual circuit
Distributor(s)
Thermal expansion valves (TXVs)
Evaporator Coil
•
•
•
•
•
•
3/8” internally enhanced copper tube mechanically bonded to lanced aluminum plate fins
Factory pressure and leak tested to 449 psig.
Draw-through airflow
Dual circuits are interlaced/intertwined
Double sloped, removable, cleanable, composite drain pan
Four drain pan positions
Indoor Fan
•
•
•
•
Double inlet, double width, forward curved, centrifugal type fan
Dual fans on 10.4 – 16.7 ton air handlers
Adjustable belt drive
Permanently lubricated bearings
Indoor Motor
•
•
•
•
•
Adjustable motor sheaves (standard units)
Thermal overload protection
Permanently lubricated bearings
Meet energy policy of 1992 (EPACT)
Optional oversized motors for high static applications
Controls
•
•
•
•
•
•
Completely internally wired
Numbered and colored wires
Magnetic indoor fan contactor
Low voltage terminal strip
Single point power entry
Evaporator defrost control
Filters
•
•
•
•
•
Access from side coil panels
Filters slide on rack
One inch (1"), throwaway filters on 4.6 - 8.33 ton units
Filter rack convertible to two inch (2") capability on 4.6 - 8.33 ton units
Two inch (2"), throwaway filters on 10.4 - 20.9 ton units
Field Installed Options
Electric Heaters
•
•
•
•
SSP-PRC024J-EN
Heavy duty nickel chromium elements
Installs directly on fan discharge
One or two stage control (dependent upon capacity)
Single point power entry
107
Mechanical Specifications
•
•
•
Terminal strip connections
460V Heaters
– Internally wye connected
– Automatic line break high limit controls
230V Heaters
– Internally delta connected
– Automatic reset of high limit controls through pilot duty with secondary backup fuse links
Hydronic Heat Coils
•
•
•
•
•
One row steam
Two row hot water
Installs directly on fan discharge
Heavy gauge sheet metal casing matches air handler
Convertible for horizontal or vertical configurations
Discharge Plenums and Grilles
•
•
•
Vertical, free discharge applications
Heavy gauge sheet metal casing matches air handler
Satin-finished, 4-way adjustable louver grilles
Return Air Grilles
•
•
•
Vertical, free discharge applications
Satin-finished, non-adjustable louver grilles
Replaces front lower access panel
Mounting Sub-Base
•
•
•
•
Vertical floor mount configuration requirement
Heavy gauge sheet metal casing matches air handler
Provides additional clearance for condensate drain trapping
Required when isolators are used
Vibration Isolators
•
•
•
•
Neoprene-in-shear or spring flex choice
Floor or suspended applications
Reduce vibration transmission to building structures, equipment, and adjacent spaces
Reduce noise transmission to building structures, equipment, and adjacent spaces
Oversize Motors
•
•
108
High static applications
Motor, sheaves, belt included
SSP-PRC024J-EN
Notes
SSP-PRC024J-EN
109
Notes
110
SSP-PRC024J-EN
Notes
SSP-PRC024J-EN
111
Ingersoll Rand (NYSE: IR) advances the quality of life by creating comfortable, sustainable and efficient
environments. Our people and our family of brands — including Club Car®, Ingersoll Rand®, Thermo King® and
Trane® — work together to enhance the quality and comfort of air in homes and buildings; transport and protect
food and perishables; and increase industrial productivity and efficiency. We are a global business committed to a
world of sustainable progress and enduring results.
ingersollrand.com
Ingersoll Rand has a policy of continuous product and product data improvements and reserves the right to change design and specifications
without notice.
We are committed to using environmentally conscious print practices.
SSP-PRC024J-EN
07 Mar 2018
Supersedes SSP-PRC024H-EN
(May 2017)
©2018 Ingersoll Rand