Key Features
Self-configuring
battery pack
Dual mains input
Multi-format design
Rotating back-lit LCD
Load segment control
5 to 10 year design life
battery
Industry Leading Design
Central to the Black Box range
of power management products is
the new ServSwitch UPS series.
This is a true on-line, double
conversion topology with power
rating from 1KVA to 6KVA. Its
multi format design enables rack
mounting or free standing
orientation of the same product
straight out of the box. The
ServSwitch UPS range has been
in development for close to two
years and offers greater flexibility
than any other product in this
power range.
Self configuring battery pack
All UPS' utilise batteries and,
depending on the power rating of
the UPS, the internal DC “string”
voltage will be different: the
higher the voltage, the lower the
current needs to be in order to
deliver the same power and
consequently the UPS is less
1
81101
bulky and more efficient. To
optimise efficiency, the higher the
kVA rating of the UPS, the higher
the “string” voltage used.
In the ServSwitch UPS design,
the battery pack is configured in
multiples to achieve the required
string voltages at higher kVA
ratings.
The advantages of this are:
1. The right battery packs are
always available.
2. The blocks are "plug and
play" so installation is very fast.
3. Specialist technical
installation staff are not needed to
install/change the batteries
4. The packs are small
enough that they are considered
a "one man lift" so handling is
much easier and safer.
Dual mains input
Most UPS' have one mains
input, however the ServSwitch
UPS has 2. It is common for
communications rooms to be fed
from 2 supplies (possibly 2 phases
of the same supply) so that if there
is a problem on one supply the
other can take over and prevent
the UPS from needing to
discharge its batteries until there
is no other option. In order to do
this, ordinarily, a static switch is
required which selects "Mains 1"
or "Mains 2" as the input to the
UPS depending upon which is
available. Since ServSwitch UPS
has 2 mains inlets, it is not
necessary to have a static switch.
The advantages of this are:
1. Cost. An additional static
switch may cost an extra £600
depending on the power rating.
2. Less rack space. A typical
static switch would be either 1U
or 2U in height, once installed in
the rack this takes away space
which could be used by more
communications equipment such
as servers, routers etc.
3. The UPS is never running
from battery (which has a finite
life to it) when there is another
mains supply available. Extended
“uptime” for the load and
extended lifetime for the
batteries..
Multi format
All models are multi-format
design and can be rack mount or
standalone straight from the box;
this achieves 3 important
objectives:
1. Cost reduction by
standardisation of packaging.
2. Cost reduction by
minimisation of stock levels (the
right format is always available !)
3. Fits all standard (600x600)
racks, as all models (UPS and
Battery Modules) are only 510mm
deep.
This also gives the flexibility to
remove an UPS from a rack when
space becomes limited and give
the option of free standing it,
without the need to purchase a
different model.
Simple monitoring and
control
The ServSwitch UPS has a
fully rotating back-lit LCD (which
shows load, voltage, temperature
etc) which is simply twisted to be
the right way up. This makes the
UPS much more user friendly,
especially if it’s in a poorly lit room
(i.e. during power failure
conditions).
Naturally, options to provide
SNMP and remote alarms
through relay contacts etc. are
features of the design.
Load Segment Control
To extend runtime it is possible to
select a load segment control
function from the front panel,
which will shut down a noncritical output of the UPS (on
mains fail) to extend the runtime
on the critical output. This feature
is available on 2500VA + 3000VA
models.
Black Box ServSwitch UPS
Shutdown Software
All models within the
ServSwitch range are provided as
standard with shutdown &
monitoring software. This
software is supplied on a CD and
covers all windows based
platforms. The software offers all
of the functionality of standard
shutdown packages with some
additional features for remote
monitoring and control.
supplied or remotely via a
connected network. This can
provide information back to the
user of major input and output
parameters with alarm
information as and when it
appears.
Control is via the console in
the software and allows the user
again, locally via serial
connection or remotely via
network connection, to schedule
remote system shutdown
(password controlled) and
general UPS house keeping.
In combination with its very
flexible shutdown features, the
software also lets the user know
which programs were shutdown
at last mains failure, to ensure no
files are overlooked.
Monitoring is achieved either
locally througth the RS232 cable
Mechanical Format
RMUPS4000, RMUPS5000 & RMUPS6000
2
RMUPS1000 & RMUPS1500
RMUPS2500 & RMUPS3000
Standard unit with internal batteries 2U
Each additional battery adds 2U
Standard unit with battery 4U
Each additional battery adds 2U
81101
Standard unit with battery 8U
Each additional battery comprises
2 x BM (2 x 2U)
Specifications
Input:
Input Voltage: 176-276 VAC full
load, 125-276 VAC 25% load,
without using battery.
Input Frequency: 50/60 Hz
autosensing (45-65 Hz).
Input Power Factor: >0.98 at full
load.
Crest factor: 3:1
Input Protection: Fuse/breaker.
Output:
Output Voltage: 208/220/230/240
VAC selectable via front panel
LCD.
Output Regulation: + 2% of
nominal.
Output Waveform: Sine wave.
Output THD: < 3%.
Output Protection: Electronic
overload sensing.
Efficiency (AC-AC): 87% up to 1.5
kVA, 90% up to 6 kVA.
Overload Capacity: 105% for 120
secs, 150% for 10 secs.
Output Frequency: 50/60 Hz
autosensing to input.
General: Input Receptacles: 2 x
IEC320-10A <1.5 kVA, 2 x IEC32016A 2.5 kVA to 3 kVA, Hardwired
4 kVA to 6 kVA, Dual feed.
Output Receptacles: 2 x IEC32010A <1.5 kVA, 2 x IEC320-16A 2.5
kVA to 3 kVA, Hardwired 4 to 6
kVA, Load segment control via
LCD 2.5 kVA & 3KVA.
display/Alarm: Front panel LCD
menu driven, audible alarms.
Interface: 2 x RS232 (Rear Panel),
option slot for SNMP/USB or
VFC. Software: Supplied
bundled to support Windows 95.
98, Me, 2000, XP & NT, & Novell.
Environmental: Operating
Temperature: 0 C to + 40 C.
Storage Temperature: -15 C to
+50 C.
Relative Humidity: 0-95% RH noncondensing.
Altitude: 3000m without derating.
Acoustic Noise: <45 dBA at 1
metre.
o
o
o
o
Battery: Internal Battery Type: VRLA
5 year design life, 10 year option
add suffix “X” to model number.
Battery Replacement: Hot swap
all models.
Recharge: <4 hours to 90%,
standard battery only.
Battery String Voltage: 48 V up to
1.5 kVA, 96 V 2.5 kVA to 3 kVA,
192 V 4 kVA to 6 kVA.
Temperature: Autonomy,
recharge & battery life based on
25 C ambient.
o
E M C & Safety:
Safety: EN50091-1-1 & EN60950.
EMI: EN50091-2 Class B,
EN55022B.
Immunity: IEC61000-4-2, -3, -4 & 5.
Approvals: CE, TUV/GS.
Ingress Rating: IP20.
UPS Topology
The Black Box ServSwitch series of On line UPS provides
a high integrity AC power source with zero transfer time
on mains fail conditions to battery. This On line double
conversion topology ensures that the load is
protected against noise and transients.
RMUPS1000 & RMUPS1500
They also offer dual input feeds ensuring that even if the
main input fails, and the auxiliary supply is available, the
load will continue to be
protected against power failure.
The ServSwitch UPS series also incorporates (2.5 kVA
and 3kVA) load segment control - allowing the user to
turn off (via the LCD front panel menu) any load that is
surplus to the critical part of the system. This then
ensures that any critical component connected can
achieve the longest run time available.
RMUPS2500 & RMUPS6000
DIMENSIONS & WEIGHTS
Model
Number
RMUPS1000
RMUPS1500
RMUPS2500
RMUPS3000
RMUPS4000
RMUPS5000
RMUPS6000
RMUPS-BM
RMUPS-BP
3
81101
Height
88.9 mm
88.9 mm
177.8 mm
177.8 mm
355.6 mm
355.6 mm
355.6 mm
88.9 mm
-
Dimensions
Depth
510 mm
510 mm
510 mm
510 mm
510 mm
510 mm
510 mm
510 mm
-
Width
426 mm
426 mm
426 mm
426 mm
426 mm
426 mm
426 mm
426 mm
-
Weight
(Total kg)
22 kg (22)
22 kg (22)
20+28 kg (48)
20+28 kg (48)
28+28+28 kg (84)
28+28+28 kg (84)
28+28+28 kg (84)
4+12+12 kg (28)
12 kg (12)
BLACK BOX SERVSWITCH UPS RUN TIME (IN MINUTES)
UPS
Model
RMUPS1000
+1BM
+2BM
+3BM
RMUPS1500
+1BM
+2BM
+3BM
RMUPS2500
+1BM
+2BM
+3BM
RMUPS3000
+1BM
+2BM
+3BM
RMUPS4000
+2BM
+4BM
+6BM
RMUPS5000
+2BM
+4BM
+6BM
RMUPS6000
+2BM
+4BM
+6BM
200 VA
(140 W)
59
260
466
63
274
491
167
371
589
140
313
-
400 VA
(280 W)
32
134
247
358
34
142
260
377
85
212
337
478
66
175
285
391
130
290
467
133
297
477
140
313
503
-
600 VA
(420 W)
18
83
166
250
19
88
175
264
59
152
244
334
51
121
196
280
88
214
339
479
90
219
346
489
95
231
365
515
800 VA
(560 W)
12
58
124
183
13
62
131
193
47
107
179
255
38
83
153
211
63
166
269
374
65
170
275
382
68
179
290
403
Autonomy vs Load
1000 VA
1500 VA
2000 VA
(700 W)
(1050 W)
(1400 W)
8
50
91
146
9
5
53
31
96
60
154
92
34
15
9
78
46
29
144
66
54
198
104
68
26
15
10
63
46
29
118
67
54
169
106
69
54
37
23
137
84
57
221
149
104
305
208
151
56
38
24
140
86
59
226
152
106
311
212
154
59
40
25
148
91
62
238
161
112
328
224
163
BLACK BOX SERVSWITCH UPS EXTENDED RUN TIME CHART (IN MINUTES)
UPS
Model
RMUPS1000 +5 BMc
RMUPS1000 +6 BMc
RMUPS1000 +7 BMc
RMUPS1500 +5 BMc
RMUPS1500 +6 BMc
RMUPS1500 +7 BMc
RMUPS2500 +5 BMc
RMUPS2500 +6 BMc
RMUPS2500 +7 BMc
RMUPS3000 +5 BMc
RMUPS3000 +6 BMc
RMUPS3000 +7 BMc
RMUPS4000 +8 BMc
RMUPS4000+10 BMc
RMUPS4000+12 BMc
RMUPS5000 +8 BMc
RMUPS5000+10 BMc
RMUPS5000+12 BMc
RMUPS6000 +8 BMc
RMUPS6000+10 BMc
RMUPS6000+12 BMc
4
81101
400 VA
(280 W)
540
720
840
550
740
860
600
750
850
570
730
825
960
1200
970
1220
49
980
1230
-
800 VA
(560 W)
270
330
390
280
350
420
270
330
378
250
300
348
450
570
720
460
580
470
590
760
1000 VA
(700 W)
210
252
300
220
270
315
210
240
300
195
230
270
354
432
510
360
440
740
370
450
530
1500 VA
(1050 W)
132
150
198
138
168
198
128
160
190
210
270
330
220
280
520
230
290
350
2500 VA
(1750 W)
3000 VA
(2100 W)
4000 VA
(2800 W)
5000 VA
(3500 W)
6000 VA
(4200 W)
6
20
41
58
6
21
42
59
16
50
76
119
17
51
78
121
18
54
82
128
5
16
31
49
13
40
60
93
13
41
61
96
14
44
65
101
8
26
48
61
8
26
49
62
9
28
52
66
6
19
37
54
6
20
39
57
5
15
28
46
(1)(2)
Autonomy vs Load
2000 VA
2500 VA
(1400 W)
(1750 W)
100
120
150
95
115
140
192
210
270
200
220
340
210
230
290
70
90
110
65
85
105
150
180
210
155
190
280
160
200
230
3000 VA
(2100 W)
4000 VA
(2800 W)
5000 VA
(3500 W)
6000 VA
(4200 W)
55
70
85
110
150
168
115
155
220
120
160
185
60
70
100
65
75
175
70
85
115
70
75
105
72
79
85
80
50
65
85
Front Panel Layout
2
1
3
5
2
4
FRONT PANEL LAYOUT
No.
1
2
3
4
5
Description
Remove panel to access battery compartment (up to 1.5 kVA only) other models have separate battery module
Top/bottom clips for releasing LCD display (to rotate through 90°) for standalone applications
Back lit full function LCD display
st Keys for menu selection, bypass and menu select button
Input breaker
Rear Panel Layout
RMUPS1000 & RMUPS1500
1
Main
Inlet
Auxilary
Inlet
5
Outlet
Main
Inlet
2
1
4
4
2
3
RMUPS2500 & RMUPS3000
Auxilary
Inlet
3
Outlets
RMUPS4000 - RMUPS6000
6
5
1
7
3
2
REAR PANEL LAYOUT
No.
1
2
3
4
5
6
7
5
Item
Option slot
Comms port
Repo
Input Fuses
External battery
Input Breaker
Hardwire terminals
81101
Description
Option slot allows user to fit RMUPS-VFC dry contact card or SNMP internal network adaptor
Standard serial RS232 communications via 9 pin D type connector
Remote emergency power off (remove link to shutdown)
Overload protection
Allows user to connect external battery packs
Input breaker for 4, 5 & 6 kVA models
Screw Terminals for input, output and battery (if required)
5
MODEL NUMBERS AND POWER OUTPUTS
Output
Power
1000 VA
1500 VA
2500 VA
3000 VA
4000 VA
5000 VA
6000 VA
700 W
1050 W
1750 W
2100 W
2800 W
3500 W
4200 W
Output Current
@ 230 VAC
4.3 A
6.5 A
10.8 A
13.0 A
17.3 A
21.7 A
26.0 A
Ordering Information
ITEM
CODE
On-Line UPS - basic 5 year design life battery
Capacity UPS 1 kVA .......................................RMUPS1000
Capacity UPS 1.5 kVA ....................................RMUPS1500
Capacity UPS 2.5 kVA....................................RMUPS2500
Capacity UPS 3 kVA .......................................RMUPS3000
Capacity UPS 4 kVA .......................................RMUPS4000
Capacity UPS 5 kVA .......................................RMUPS5000
Capacity UPS 6 kVA .......................................RMUPS6000
On-Line UPS - extended 10 year design life battery
Capacity UPS 1 kVA...................................RMUPS1000-X
Capacity UPS 1.5 kVA................................RMUPS1500-X
Capacity UPS 2.5 kVA................................RMUPS2500-X
Capacity UPS 3 kVA...................................RMUPS3000-X
Capacity UPS 4 kVA...................................RMUPS4000-X
Capacity UPS 5 kVA...................................RMUPS5000-X
Capacity UPS 6 kVA...................................RMUPS6000-X
Additional battery module for extra capacity
Battery module (=2 x RMUPS-BP) .............RMUPS-BM
Extra long run time batery module.............RMUS-BMC
Battery module (As above but 10 year design battery .
life)...................................................................RMUPS-BMX
Spare/Replacement Battery Packs
Battery Pack 48VDC........................................RMUPS-BP
Battery Pack 48VDC - 10 year design battery life
.......................................................................RMUPS-BPX
Mounting Options
Adds rail guide kit for each module in UPS......................
..........................................................................RMUPS-RG
Other Options
Adds SNMP/Network adaptor ................RMUPS-MAN
Adds USB option card to UPS...................RMUPS-USB
Adds VFC option (relay contact) card to UPS..................
........................................................................RMUPS-VFC
6
81101
Autonomy
(Full Load)
8 Minutes
5 Minutes
6 Minutes
5 Minutes
8 Minutes
6 Minutes
5 Minutes
Half
Load
25 minutes
15 minutes
25 minutes
15 minutes
23 minutes
17 minutes
14 minutes
Model
Number
RMUPS1000
RMUPS1500
RMUPS2500
RMUPS3000
RMUPS4000
RMUPS5000
RMUPS6000