Datasheet
Article No: 136-5383
Digital Multi-Function Meter 3 Line Display, 96x96, 3Ph, V A F Power
& Energy, with RS 485 Communication
Article No: 136-5384
Digital Multi-Function Meter 3 Line Display, 96x96, 3Ph, V A F Power
& Energy, with RS 485 Communication & Limit Relay/Switch Option
RS Pro
RS Pro
•
MODBUS (RS485) Communication (optional)
•
Pulse/Limit Switch output (optional)
•
3 Line 4 Digits ultra bright LED Display (up to 9999)
•
On site Programmable CT/PT Ratios
•
User selectable CT Secondary 1A/5A
•
User selectable PT Secondary from 100 VLL to 500 VLL
•
Programmable Energy format & Energy rollover count
•
Wide auxillary Power Supply which can accept any input between
40V – 300V AC/DC
RS Pro is a compact multifunction instrument which Measures important
electrical parameters in 3 phase 4 Wire and 3 phase 3 Wire Network &
replaces the multiple analog panel meters.
RPM Measurement
The instrument display Rotation per minutes for generator applications.
Number of poles can be set on site depending upon application
requirement.
Energy Count Storage
In case of power failure, the instrument memorizes the last energy count.
Every 1 min, the instrument updates the energy counter in the
non-volatile memory.
User selectable 3 phase 3 Wire or 4Wire or Single phase Network
User can program on site the network connection as either 3 Phase 3
Wire or 4 Wire or single phase network using front panel keys. Optional
self-powered available, only on either 3 Phase 4 wire or single phase
network are available on request.
Onsite selection of Auto scroll / Fixed Screen
User can set the display in auto scrolling mode or fixed screen mode using
front panel keys.
Optional Pulse Output / Limit switch (Relay output)
Application
The instrument can be programmed as Pulse output or Limit switch.
The RS Pro measures important electrical parameters in 3 phase 4 Wire
and 3 phase 3 Wire Network & replaces the multiple analog panel meters.
It measures electrical parameters like AC Voltage, AC Current, Frequency,
Active, Reactive, Apparent Power, Import Export Energy & many more.
Pulse Output
The optional pulse output is a potential free, very fast acting relay contact
which can be used to drive an external mechanical counter for energy
measurement.
Product Features
Limit Switch
The instrument will trip the relay if the programmed parameter exceeds
the programmed Trip Limits.
On site programmablePT / CT ratios
It is possible to program primary of external potential Transformer (PT),
primary of external Current Transformer (CT) on site via front panel keys
by entering into Programming mode.
Optional MODBUS (RS485) Output
The optional Modbus output enables the instrument to transmit all the
measured parameters over standard MODBUS (RS485).
User selectable CT Secondary 5A /1A
The secondary of external Current Transformer (CT) can be programmed
on site to either 5A or 1A using front panel keys.
Configuration of Instrumnet via MODBUS
The instrument setting can be configured locally via front panel keys by
entering into the programming mode or rometely via MODBUS (Rs485).
Note: The MODBUS communication parameters can only be set
locally via front panel keys in programming mode.
User selectablePT Secondary
The secondary of external Potential Transformer (PT) can be programmed
on site from 100VLL to 500VLL using front panel keys. User can set the
display in auto scrolling mode or fixed screen mode using front panel keys.
Low back depth
The instrument has very low back depth (behind the panel) of less than
55 mm (Without output option).
Four function keys
Using the four function key, it is possible to go desired parameter screen
instantly. Measures & Displays Current Demand, kVA Demand, kW
Import Demand, kW Export Demand. Any of the parameters can be
assigned to optional Limit switch.
Demand Measurement
Measures & Displays Current Demand, kVA Demand, kW Import
Demand, kW Export Demand. Any of the parameters can be assigned
to optional Limit switch.
3 line 4 digits LED display
Simultaneous display of 3 Parameters.
Issue 1.0
Storage of parameters possible
The instrument stores minimum and maximum values for System Voltage,
System Current, Run Hour, ON Hour & number of Interrupts. Every
60 sec stored values are updated.
Enclosure Protection for dust and water
Conforms to IP 50 (for front face) & IP 20 (for back) IP 65 (for front with
seal) as per IEC60529.
EMC Compatibility
Compliance to International standard IEC 61326. Interference IEC
61326-1 : 2005, Class A Emission
Interference Immunity
IEC 61326-1 : 2005
Electrostatic discharge contact/air. (ESD)
IEC 61000-4-2 -- 4kV/8kV
EM Field
IEC 61000-4-3 -- 10 V/m (80 MHz to 1 GHz)
– 3 V/m (1.4 Ghz to 2 GHz)
-- 1 V/m (2 GHz to 2.7 GHz)
PAGE 1
Product Features Continued
True RMS
measurement
Energy
Measurement
(Import & Export)
Programmable
Energy format &
Energy rollover
count
The instrument measures distorted wave
form up to 15th Harmonic.
Active Energy (kWh), Reactive Energy (kVArh),
Apparent Energy (kVAh). Any of the parameters
can be assigned to optional Pulse output.
Customer can assign the format for energy
display on MODBUS (RS485) in terms of
W, kW or MW. Additional to this, customer can
also set a rollover count from 7 to 14 digits
depending on the energy format, after which
the energy will roll back to zero.
Technical Specifications
Reference conditions for Accuracy
Reference temperature
23°C +/- 2°C
Input waveform
Sinusoidal (distortion factor 0.005)
Input frequency
50 or 60 Hz ±2%
Auxiliary supply voltage
Rated Value ±1%
Auxiliary supply frequency
Rated Value ±1%
Voltage Range
20... 100% of Nominal Value.
Current Range
10... 100% of Nominal Value.
Power
Cos phi / sin phi = 1 for Active /
Reactive Power & Energy.
10... 100% of Nominal Current &
20... 100% of Nominal Voltage.
Power Factor /
40... 100% of Nominal Current &
Phase Angle
20... 100% of Nominal Voltage.
Accuracy
Voltage
± 1% of Nominal Value.
Current
± 1% of Nominal Value.
Frequency
0.5% of mid frequency
Active Power
± 1% of Nominal Value.
Re-Active Power
± 1% of Nominal Value.
Apparent Power
± 1% of Nominal Value.
Active Energy
± 1%
Reactive Energy
± 1%
Apparent Energy
± 1%
Power Factor
2% of Unity
Phase angle
2% of range
Burst
Surge
Conducted RF
Rated Power
Frequency
magnetic Field
Voltage dip
Short interruptions
cycles.
IEC 61000-4-4 -- 2 kV (5/50 ns, 5 kHz)
IEC 61000-4-5 -- 1 kVLL / 2 kVLN.
IEC 61000-4-5 -- 3 V (150 kHz to 80 MHz)
IEC 61000-4-8 -- 30 A/m
IEC 61000-4-11 -- 0% during 1 cycle.
-- 40% during 10/12 cycles.
-- 70% during 25/30 cycles.
IEC 61000-4-11 -- 0% during 25/30 cycles.
25 cycles for 50 Hz test.
30 cycles for 60 Hz test.
Dimension Details
With optional MODBUS / Limit switch
Measurement error is normally much less than error specified above.
Variation due to influence quantity is less than twice the error allowed for
reference condition.
Issue 1.0
PAGE 2
Dimension Details
Technical Specifications
Input Voltage
Nominal input voltage
(AC RMS)
Max continuous input
voltage 120% of rated value
Nominal input voltage
burden
System PT secondary values
System PT primary values
Input Current
Nominal input current
System CT secondary values
System CT primary values
Max continuous
input current
Nominal input current
burden
Auxiliary Supply
External Aux
Self powered
Frequency range
VA burden
Overload Withstand
Voltage
Current
Phase –Neutral 290V L-N ,
Line-Line 500V L-L
120% of rated value
With optional MODBUS / Limit switch
< 0.3 VA approx. per phase
(For external auxiliary meter)
100VLL to 500VLL programmable
on site.
100VLL to 692kVLL
programmable on site.
5A / 1A AC RMS
1A & 5A programmable on site
From 1A up to 9999A (for 1 or 5 Amp )
120% of rated value
< 0.2 VA approx. per phase
40 V – 300V AC-DC (± 5 % )
input voltage range from 80% to 100%
of Rated value. (Self powered meter is
available only in 3Phase 4 Wire and
Single Phase network.) Auxiliary input
is derived from Phase 1 (R phase)
45 to 65 Hz
< 4 VA Approx.
2 x rated value for 1 second, repeated
10 times at 10 second intervals
20x rated value for 1 second,
repeated 5 times at 5 min intervals
Operating Measuring Ranges
Voltage Range With
10… 120% of rated value
External Aux
Voltage Range With
80… 120% of rated value
Self Power
Current Range
10 … 120% of rated value
Frequency
45…65 Hz.
Power Factor
0.5 Lead ... 1 ... 0.5 Lag.
Issue 1.0
PAGE 3
Installation
Technical Specifications
Limit Switch (Relay)
Switching Voltage &
Current for Relay
Influence of Variations
Temperature coefficient
Display update rate
Response time to step input
Applicable Standards
EMC
Safety
IP for water & dust
Safety
Pollution degree
Installation category
High Voltage Test
Environmental
Operating temperature
Storage temperature
Relative humidity
Warm up time
Shock
Vibration
Enclosure
Front
Front with seal (Option)
Back
Dimensions and Weights
Bezel size
Panel cut-out
Overall depth
Panel Thickness
Weight
Issue 1.0
240 VDC ,5 A (1NO+1NC)
Easy Clip in Installation on Panel.
0.025%/°C for Voltage
0.05%/°C for Current
1 sec approx.
IEC 61326-1: 2005
IEC 61010-1-2001 , Permanently
connected use
IEC60529
2
III
4.7 kV DC, for 1 minute between Aux.
and measuring inputs
-20 to +70°C
-30 to +80°C
0 to 95% non condensing
Minimum 3 minute
15g in 3 planes
10... 55 Hz, 0.15mm amplitude
IP 50
IP 65
IP 20
96 mm x 96 mm DIN 43 718.
92 +0.8 mm x 92 + 0.8 mm.
55 mm.(without output option)
1 - 3 mm for self clicking,
1 – 6 mm for swivel screws.
320 gm. Approx.(with output option)
PAGE 4
Technical Specifications
Pulsed Output Option
Energy (can be programmed for different energy parameters simultaneously)
Relay contact
(1NO+1NC)
Switching Voltage &
240 VDC ,5 A
current for Relay
Default pulse rate divisor
1 per Wh (up to 3600W) 1 per kWh (up to 3600kWh) 1 per MWh (above 3600kW)
Other Pulse rate divisors (applicable only when Energy on RS485 is in W)
10
1 per 10 Wh (up to 3600W)
1 per 10 kWh (up to 3600kWh))
100
1 per 100 Wh (up to 3600W
1 per 100 kWh (up to 3600kWh)
1000
1 per 1000 Wh (up to 3600W)
1 per 1000 kWh (up to 3600kWh)
Pulse Duration : 60 msec, 100 msec, 200 msec.
Above options are also applicable to Apparent and Reactive Energy.
1 per 10 MWh (above 3600kW)
1 per 100 MWh (above 3600kW)
1 per 1000 MWh (above 3600kW)
Electrical Installations
Issue 1.0
PAGE 5
Rear Connection
Parameter measurement and Display
Sr No
1.
2.
3.
4.
5.
6.
7.
8.
9.
10.
11.
12.
13.
14.
15.
16.
17.
18.
19.
20.
21.
22.
23.
24.
25.
26.
27.
Parameter
System Volts
System Current
Volts R–N (Phase Voltage for Single phase)
Volts Y–N
Volts B–N
Volts R-Y
Volts Y–B
Volts B–R
Current R (Phase Current for Single phase)
Current Y
Current B
Frequency
System Active Power (kW)
Active Power R (Phase Power for Single phase) (kW)
Active Power Y (kW)
Active Power B (kW)
System Re-active Power (kVAr)
Re-active Power R (Phase Power for Single phase) (kVAr)
Re-active Power Y (kVAr)
Re-active Power B (kVAr)
System Apparent Power (kVA)
Apparent Power R (Phase Power for Single phase) (kVA)
Apparent Power Y (kVA)
Apparent Power B (kVA)
System Phase Angle
System Power Factor
Power Factor R
3 Phase 4 Wire
✓
✓
✓
✓
✓
✓
✓
✓
✓
✓
✓
✓
✓
✓
✓
✓
✓
✓
✓
✓
✓
✓
✓
✓
✓
✓
✓
3 Phase 3 Wire
✓
✓
✕
✕
✕
✓
✓
✓
✓
✓
✓
✓
✓
✕
✕
✕
✓
✕
✕
✕
✓
✕
✕
✕
✓
✓
✕
1 Phase 2 Wire
✓
✓
✓
✕
✕
✕
✕
✕
✓
✕
✕
✓
✓
✓
✕
✕
✓
✓
✕
✕
✓
✓
✕
✕
✓
✓
✓
✓- Available ✕ - Not available
Issue 1.0
PAGE 6
Parameter measurement and Display
Sr No
28.
29.
30.
31.
32.
33.
34.
35.
36.
37.
38.
39.
40.
41.
42.
43.
44.
45.
46.
47.
48.
49.
50.
51.
Parameter
Power Factor Y
Power Factor B
Phase Angle R
Phase Angle Y
Phase Angle B
Active Energy Import (kWh)
Active Energy Export (kWh)
Reactive Energy Import (kVArh)
Reactive Energy Export (kVArh)
Apparent Energy (kVAh)
RPM
Max (System Voltage / System Current)
Min (System Voltage / System Current)
Hour Run
ON Hour
Number of auxiliary interrupt
Current Demand
kVA Demand
kW Demand Import
kW Demand Export
Max Current Demand
Max kVA Demand
Max kW Demand Import
Max kW Demand Export
3 Phase 4 Wire
✓
✓
✓
✓
✓
✓
✓
✓
✓
✓
✓
✓
✓
✓
✓
✓
✓
✓
✓
✓
✓
✓
✓
✓
3 Phase 3 Wire
✕
✕
✕
✕
✓
✓
✓
✓
✓
✓
✓
✓
✓
✓
✓
✓
✓
✓
✓
✓
✓
✓
✓
✓
1 Phase 2 Wire
✕
✕
✓
✕
✓
✓
✓
✓
✓
✓
✓
✓
✓
✓
✓
✓
✓
✓
✓
✓
✓
✓
✓
✓
✓- Available ✕ - Not available
Ordering Code
Article No: 136-5383
RS Pro 3 Line display Volts, Amp Frequency, Power and Energy, 96x96mm, 3 Phase 3/4W programmable onsite,
AC VAF + Power + Energy meter, 14mm display,
Input. 100-500VLL,
Input. 1 or 5 Amps AC,
Supply Voltage. 40-300V AC/DC auxiliary (Programmable CT/PT primary and secondary values with RS 485 Communication)
Article No : 136-5384
RS Pro 3 Line display Volts, Amp Frequency, Power and Energy, 96x96mm, 3 Phase 3/4W programmable onsite,