AUTOMATION
INTERFACE ELECTRONIC
Supplementary Catalog to
Full Line Catalogs, Volumes 3/4
Edition 2012/1
3/4
Contents
I/O-SYSTEM
Volume 3
04 – 19
Interface Modules
Volume 4
20 – 97
Tools and Accessories
Item Number Index
98 – 103
104
Contents
AUTOMATION
I/O-Modules, 753 Series
LON FTT Module
- LON Configurator
4
5
DALI Multi-Master Module
- DALI Configurator
- DALI Multi-Master DC/DC Converter
- Power Supply for DALI Multi-Master
6
7
8
9
Modular I/O-SYSTEM IP67, 767 Series
sercos Fieldbus Coupler
10 – 11
Digital Input Module, 24 VDC, High Speed, 8 Inputs (4 x M12, two inputs per connector) 12 – 13
Digital Output Module, 24 VDC, 0.1 A, High Speed,
8 Outputs (4 x M12, two inputs per connector)
14 – 15
Digital Input/Output Module, 24 VDC / 0.2 A, High Speed, 4 Inputs/Outputs (4 x M12) 16 – 17
Wireless Technology, 758 Series
WLAN ETHERNET Gateway
18
WAGO Ribbon Cables
10/20-Pole Female Connector, / 753 Series Pluggable Connector
19
Contents
INTERFACE ELECTRONIC
Relays and Optocouplers, 857 Series
JUMPFLEX® Relays
JUMPFLEX® Optocouplers
20
21 – 22
WAGO Ribbon Cables
20-Pole Female Connector/One Free Cable End
Female Connector / Female Connector or D-Sub Female Connector
24 – 25
26 – 27
Relays, 788 Series
Sockets with Miniature Switching Relay
Sockets with Solid State Relay
28 – 29
30
Relay Sockets with Industrial Relay
32 – 33
Interface Modules in DIN-Rail Mountable Enclosure, 789 Series
Relay with 1 or 2 Changeover Contact, Manual Configuration
34 – 35
Relay with 1 Make Contact (1 a), Manual-0-Automatic Switch with Monitoring Contact
36
Relay with 1 Changeover Contact (1 u), Manual-0-Automatic Switch with Switch Position Monitoring 37
Interface Module RS-232/SMI in DIN-Rail Mountable Enclosure, 230 V AC
38
Interface Module RS-232/SMI LoVo in DIN-Rail Mountable Enclosure, 24 V DC
39
Current Sensor with Bus Connection in DIN-Rail Mountable Enclosure,
Measuring Range 0 ... 80 A
40 – 41
Measuring Range 0 ... 140 A and 0 ... 50 A
42 – 45
3-Channel Rogowski Signal Conditioner
46
WINSTA® ,770 Series
WINSTA® Sunblind Box
48 – 49
Transducers, 857 Series
JUMPFLEX® Universal Isolation Amplifier
JUMPFLEX® Isolation Amplifiers, Fixed Setting for Voltage or Current Signals
JUMPFLEX® Loop-Powered Isolation Amplifier
JUMPFLEX® Frequency Transducer
JUMPFLEX® Current Transducer
JUMPFLEX® Rogowski Transducer
JUMPFLEX® Potentiometer Position Transducer
JUMPFLEX® Ni Transducer for Ni 100, Ni 120, Ni 200, Ni 500, Ni 1000
JUMPFLEX® KTY Transducer
JUMPFLEX® Supply and Through Module
50 – 51
52 – 53
54 – 55
56 – 59
60 – 61
62 – 63
64 – 67
68 – 69
70 – 71
72 – 73
Power Supplies, 787 Series
EPSITRON® COMPACT Power Supply, 230 VAC / 12 V or 24 VDC
EPSITRON® PRO Power Supply, 230 VAC / 12 V, 24 V or 48 VDC
EPSITRON® UPS Charger and Controller
EPSITRON® Lead Gel Battery Modules
EPSITRON® Redundancy Module
EPSITRON® Wall Mounting Adapter, Carrier Rail Adapter
74 – 79
80 – 88
90
91 – 93
94
95 – 97
Accessories
Mobile Printer, Flatbed Plotter
Crimping Tools, Uninsulated Ferrules
Test and Measurement Tools
Products highlighted in RED are new items for Spring 2012
98 – 99
100 – 101
102 – 103
753-648
1
LON FTT Module
4
753-648
753-648
E: LonWorks Status
13 14
A
B
C
D
B: TxD
C: Mailbox
D: Service
E
F
G
H
F: RxD
G: Communication/
Initialization Phase
H: Service
Data contacts
not
assigned
Service
Switch
Service
Switch
Connection
Service
Switch
24 V
RxD
not
assigned
FT500
AUTOMATION
A: User Configuration
0V
BUS BUS
LON Bus A
Logic
LON Bus B
LON Bus
LON A
LON B
The 753-648 LON FTT Module complies with the ISO/IEC 14908 standard.
The 1⁄2 inch (12 mm) wide I/O module connects LON to 750 Series
Controller and Modules (e.g., BACnet, KNX, EnOcean, DALI, MODBUS). It is
a full-fledged and flexible LON device within LonWorks FT or LP networks.
The module's network variable interface defines 249 network variables of any
type and supports both LonMark objects and configuration properties.
LON network interface is defined via LON Configurator, a comprehensive and
easy-to-use WAGO-I/O-PRO software tool. Interface representations are
programmed via IEC-61131-3 and can be easily used for further applications.
Fieldbus nodes are programmed via WAGO-I/O-PRO software. WAGO
provides a comprehensive IEC-61131-3 library of function blocks, simplifying
the creation of complex control applications.
Description
Item No.
LON FTT Module
753-648
Accessories
Item No.
Pack.
Unit
Pack.
Unit
Approvals
1
pending
A
B
C
D
E
F
G
H
A maximum of two modules may be connected to one controller. However, the
number of modules depends on the memory required by the IEC application
and the type of controller. The module is supplied via 24V power jumper
contacts.
Technical Data
Transmission medium
Max. length of fieldbus segment
LON-LIB
Download: www.wago.com
LON Configurator
see page 5
WAGO-I/O-PRO V2.3, RS-232 kit
759-333
1
Miniature WSB Quick marking system
plain
248-501
5
with marking
see Full Line Catalog 2010/2011
Volume 3, Section 1
753 Series Connectors
753-110
25
Coding fingers
753-150
100
753 Series pluggable connectors and coding fingers are included.
Conformity marking
r UL 508
TxD
Topology
Baud rate
Commissioning
Programming
Interface to LON network
Number of network variables
Number of aliases
ISI (Interoparable Self-Installation)
DMF (Direct Memory Files)
Processor
Transceiver
Transmission channel
Current consumption (internal)
Power supply
Isolation
Internal bit width
Wire connection
Cross sections
Stripped lengths
Width
Weight
EMC: 1 - immunity to interference
EMC: 1 - emission of interference
EMC: marine applications
- immunity to interference
EMC: marine applications
- emission of interference
Twisted Pair - FTT
500 m (free topology);
2700 m (bus topology)
acc. to LON specification
78 kbps
via WAGO-I/O-CHECK
via WAGO-I/O-PRO
programmable via WAGO-I/O-PRO
max. 254 (249 for application)
max. 127
no
no
FT5000
FTX2
1
30 mA
via system power
500 V system/supply
24-byte data
CAGE CLAMP®
0.08 mm² ... 2.5 mm² / AWG 28 ... 14
9 ... 10 mm / 0.37 in
12 mm
55 g
acc. to EN 61000-6-2 (2005)
acc. to EN 61000-6-3 (2007)
acc. to Germanischer Lloyd (2003)
acc. to Germanischer Lloyd (2003)
LON®, LonWorks® and LonMark® are registered trademarks of Echelon Corporation.
LON Configurator
1
LON Configurator is an integral part of the WAGO-I/O-PRO IEC-61131-3 programming environment. The configurator
supports both 753-648 LON Module's LonWorks network interface configuration and WAGO-I/O-PRO project integration.
Network variables of any type can be defined. In addition to standard network variable types (SNVTs) and standard
configuration property types (SCPTs), user-defined types (UNVTs/UCPTs) as well as LonMark functional profiles are also
supported. Network variables are defined using the types and objects of the LonMark resources installed on your
computer.
IEC-61131-3 function blocks are automatically created in the IEC application, simplifying operation. The function blocks
represent the LON network interface in this application. When starting the control unit, both network variable interface
and configuration data are automatically downloaded into the module.
An external interface file (XIF) is created for offline configuration in a network management tool.
Features:
- Integral part of WAGO-I/O-PRO programming software
- Defines and implements a LON network interface
- Automatically generates IEC-61131-3 function blocks representing the LON network interface
in the IEC application
- Downloads both network interfaces and configuration data when starting the control unit
- Generates XIF files
- Configuration check
LON Configurator is available as part of WAGO-I/O-PRO (Version 2.3.9.34 and higher)
AUTOMATION
5
753-647
1
DALI Multi-Master Module
6
E: Full Mode
B: TxD
13 14
C: Availability
AUTOMATION
753-647
753-647
A: Easy Mode
A
B
C
D
D: 1- or 2-Button
Operation
F: RxD
E
F
G
H
G: Power On
H: Latching Function
Data contacts
+DALI Bus
+DALI Bus
+DALI
+DALI
RxD
Logic
-DALI
TxD
-DALI Bus
-DALI Bus
A
B
C
D
-DALI
2 x 270pF
+V
+V
E
F
G
H
+V
BUS BUS
-V
2 x 270pF
-V
-V
+V
-V
The 753-647 DALI Multi-Master Module complies with DALI standard according to
IEC 62386. This manufacturer-independent protocol ensures interoperability of DALI
devices in lighting applications.
The 1⁄2 inch (12 mm) wide module is a DALI interface used in combination with WAGO
750 Series Controllers and Modules (e.g., BACnet, KNX, EnOcean, LON, MODBUS).
Each DALI Multi-Master Module supports 64 addresses for electronic control gears
(ECGs) and 64 addresses for DALI sensors. Each DALI ECG can be assigned to 16 groups
and 16 scenes. The 753-647 Module also offers 16 additional virtual groups on the
DALI bus.
Using the WAGO-I/O-SYSTEM, DALI control devices are seamlessly integrated with all
supported BA and fieldbus protocols. Several DALI masters can be connected to a single
fieldbus node. The maximum number of modules that can be connected to a controller
depends on the memory required by the application. Fieldbus nodes are programmed via
WAGO-I/O-PRO software. WAGO provides a comprehensive IEC-61131-3 library of
function blocks, simplifying the creation of complex lighting applications.
Description
Item No.
DALI Multi-Master Module
753-647
Accessories
Item No.
DALI Configurator
Pack.
Unit
Conformity marking
r UL 508
4 EN 60079-0, -15
EN 61241-0, -1
1
pending
pending
Technical Data
DALI specification
Pack.
Unit
see page 7 or download:
www.wago.com
WAGO-I/O-CHECK, RS-232 kit
759-302
1
Miniature WSB Quick marking system
plain
248-501
5
with marking
see Full Line Catalog 2010/2011
Volume 3, Section 1
753 Series Connectors
753-110
25
Coding fingers
753-150
100
753 Series pluggable connectors and coding fingers are included.
Approvals
Alternatively an “Easy Mode” allows lighting functions to be easily controlled without any
complicated PLC programming. The 753-647 Module is future-proof and upgradable to
the latest DALI release. A comprehensive and easy-to-use commissioning and maintenance tool is available as stand-alone application or as integrated WAGO-I/O-CHECK
software component.
The two following power supply options are available for the 753-647 Series:
1. The 753-620 DALI Multi-Master DC/DC Converter is used to supply one single
module.
2. The 787-1007 Power Supply is used to supply several modules.
DIN IEC 62386 only in conjunction with
753-620 or 787-1007 Power Supplies
Number of slaves (DALI)
addressable:
64 control devices + 64 control gears
Module power supply at +V and -V
18 V via 753-620 / 787-1007 Power
Supplies
Transmission channel
1
Technical information acc. to DALI specification
Maximum supply current
250 mA
Guaranteed supply current
200 mA
Current consumption (internal)
30 mA
Power supply
via system voltage (DC/DC)
Isolation
1500 V DC DALI bus/Internal data bus
Internal bit width
24-byte data
Commissioning
via WAGO-I/O-CHECK
Configuration
with WAGO DALI Configurator
Programming
via WAGO-I/O-PRO
Wire connection
CAGE CLAMP®
Cross sections
0.08 mm² ... 2.5 mm² / AWG 28 ... 14
Stripped lengths
9 ... 10 mm / 0.37 in
Width
12 mm
Weight
55 g
EMC: 1 - immunity to interference
acc. to EN 61000-6-2 (2005) *
EMC: 1 - emission of interference
acc. to EN 61000-6-3 (2007) *
* Only in conjunction with 753-620 /
787-1007 DC/DC Converter
EMC: marine applications
- immunity to interference
acc. to Germanischer Lloyd (2003)
EMC: marine applications
- emission of interference
acc. to Germanischer Lloyd (2003)
DALI Configurator
1
The DALI Configurator allows easy commissioning of a DALI network via 753-647 DALI Multi-Master Module. The
configurator is available as stand-alone Windows application or for use with WAGO-I/O-CHECK software.
It provides the following functions: easy commissioning, configuration, service, support and maintenance of a DALI
network. Comprehensive backup & restore features, as well as offline configuration option for the entire DALI network
(including ECGs and sensors) are available.
Features:
- Stand-alone software or for use with WAGO-I/O-CHECK
- Commissioning functions:
- Addressing
- Formation of scenes and groups
- Control gear configuration
- Offline configuration option
- Service, support and maintenance functions:
- Backup & restore
- Status messages from defective ECGs/lamps
- Identification of double addresses
- Operating hours display
- Windows-conform user interface:
- Multiple selection for time-optimized configuration
- Displays network in a clear tree structure
- Supports different commissioning workflows
DALI Configurator is available as part of WAGO-I/O-CHECK (Version 3.4.1.9 and higher) or as a stand-alone
application (www.wago.com).
AUTOMATION
7
753-620
1
DALI Multi-Master DC/DC Converter
8
753-620
753-620
13 14
AUTOMATION
A
C
B
D
Data contacts
24 V
24 V
0V
SY
+V
0V
0V
0V
+V
-V
-V
Power jumper contacts
Part of the WAGO-I/O-SYSTEM, the 753-620 DALI Multi-Master DC/DC
Converter is just ½ inch (12mm) wide. It supplies power to the 753-647
DALI Multi-Master Module and delivers maximum 200mA current to operate a
single DALI line. The maximum number of slaves depends on the total power
consumption of the single DALI devices.
The 753-620 DC/DC Converter is supplied via 24V power jumper contacts.
Cable bridges connect the DC/DC Converter to the DALI Multi-Master
Module.
Description
Item No.
Pack.
Unit
Technical Data
DALI Multi-Master DC/DC Converter
753-620
1
Voltage via power jumper contacts (max.)
Input voltage range
Current via power jumper contacts (max.)
Output voltage
Nominal output current
Short circuit protection
Test voltage input / output
Wire connection
Cross sections
Stripped lengths
Width
Weight
Accessories
Item No.
Pack.
Unit
Miniature WSB Quick marking system
plain
248-501
5
with marking
see Full Line Catalog 2010/2011
Volume 3, Section 1
753 Series Connectors
753-110
25
Coding fingers
753-150
100
753 Series pluggable connectors and coding fingers are included.
24 VDC
18 ... 31.2 VDC
10 ADC
18 VDC (at +V and -V)
200 mA
permanent
1.5 kV eff.
CAGE CLAMP®
0.08 mm² ... 2.5 mm² / AWG 28 ... 14
9 ... 10 mm / 0.37 in
12 mm
55 g
787-1007
1
Power Supply
for 753-647 DALI Multi-Master Module
L
DC+
DC+
DC DC -
N
The 787-1007 Primary Switch Mode Power Supply is specially designed to
supply the 753-647 DALI Multi-Master Module. The 787-1007 features a
54mm-wide DIN-rail mount enclosure with input voltage range of 85 to
264VAC (120 – 373VAC). The power supply provides an output voltage of
18VDC and a maximum output current of 1100mA — enough to supply up to
five parallel modules. The maximum current per DALI line is limited to 200mA
in each DALI Multi-Master Module.
• Supplies up to five 753-647 DALI Multi-Master Modules*
• Prepared for class II equipment
• Natural convection cooling when horizontally mounted
• Stage profile, ideal for distribution boards or distribution boxes
Technical Data
Input:
Nominal input voltage Vi nom
Input voltage range
Frequency
Input current Ii
Inrush current
Mains failure hold-up time
Output:
Nominal output voltage Vo nom
Output current Io
Factory preset
Adjustment accuracy
Residual ripple
Current limitation
Overload behavior
Operational indication
Efficiency / power losses:
Efficiency
Power loss PV
Fuse protection:
Internal fuse
External fuse
AUTOMATION
9
Description
Item No.
Pack.
Unit
Primary Switch Mode Power Supply,
18 VDC / 1.1A
787-1007
1
Technical Data
100 ... 240 VAC
85 ... 264 VAC; 120 ... 373 VDC
44 ... 66 Hz; 0 Hz
0.6 A at 110 VAC / 0.4 A at 230 VAC
< 30 A, NTC
> 10 ms at 110 VAC /
> 80 ms at 230 VAC
Environmental requirements:
Ambient operating temperature
Storage temperature
Rel. humidity
Degree of pollution
Climatic category
Safety and protection:
Enclosure
18 VDC
1.1 A at 18 VDC
max. 0.8 A (18 VDC) in any mounting
position
18 VDC
2 %
< 150 mV (peak-peak)
1.1 x Io typ.
Constant current
LED green (Va)
Test voltage pri. - sec.
Protection class
Degree of protection
No-load proof
Feedback voltage
Short circuit protection
MTBF
Connection and type of mounting:
Wire connection
Cross sections
80 % typ.
3 W (no load) /
6 W (rated load)
Stripped lengths
Type of mounting
Dimensions and weight:
Dimensions (mm) W x H x L
2 AT
Wire breaking 10 A, 16 A,
Characteristic B, C
An external DC fuse is required for the DC
input voltage
* Note: The 787-1007 Power Supply must be operated in a DALI network with
interconnected 753-647 DALI Multi-Master Module. Otherwise the connected DALI
devices will be destroyed.
Weight
Standards and approvals:
Standards/Specifications
-25 °C ... +55 °C
-25 °C ... +80 °C
30 % ... 85 % (no condensation)
2 (acc. to EN 50178)
3K3 (acc. to EN 60721)
Plastic, light gray,
Flammability class V0 acc. to UL94
4.2 kV DC
Prepared for class II equipment
IP20 (acc. to EN 60529)
yes
max. 20 VDC
yes
500000 h
Input/Output: WAGO Series 740
Input/Output:
0.08 mm² ... 2.5 mm² / AWG 28 ... 12
Input/Output: 6 ... 7 mm / 0.24 ... 0.28 in
DIN-rail mount (EN 60715)
54 x 89 x 59
Length: 55 mm, from upper-edge
of DIN 35 rail
170 g
EN 60950 (SELV), EN 61204-3,
GL (Environmental Category A, EMC 2),
UL 60950**, UL 508** (** pending)
767-1311
2
10
sercos Fieldbus Coupler
incl. 8 digital high-speed inputs (8 x M8)
sercos
FC 8DI HS
AUTOMATION
sercos
Input 1 (4)
sercos
Input 2 (4)
1 FB 2
MS
LED indicators
1
CS
S3 2
ACT/LNK
12 I RES
11 I B/E
10I DS
9 I 2⁸
8 I 2⁷
7 I 2⁶
6 I 2⁵
5 I 2⁴
4 I 2³
3 I 2²
2 I 2¹
1 I 2⁰
Operation
panel
X
7
X
5
X
3
X
1
Pack.
Unit
Technical Data
FC sercos 8DI 24V DC HS
767-1311
1
Fieldbus:
Device type
Connection type (4)
Baud rate
Transmission medium
Station address
DTM (Device Type Manager)
SDDML files
3
X
4
1
X
2
4
2
Digital
inputs (2)
Channel
marking
0
767-1311
Protocols
sercos services
sercos profiles
see Full Line Catalog 2012/2013
Volume 3
Download: www.wago.com
Download: www.wago.com
X
6
Supply
output (1)
Supply
input (1)
Included:
• 1 x WMB marker, yellow
• 1 x channel marking strip
• 2 x M8 protective cap
Item No.
ETHERNET cable + accessories
System bus/power supply cable +
accessories
General accessories
5
Module
marking
Characteristics:
• 8 digital high-speed inputs, type 1 (IEC 61131)
• Hardware delay: 10 μs
• Modular and extendable by up to 64 I/O modules (via system port)
• USB interface for service purposes
• Configuration and parameter setting via SDDML device description file
• Parameter setting via FDT/DTM (incl. diagnostics and simulation)
• Sealable operation panel (operating mode and address switches)
Description
Item No.
X
8
24 V
ULS UA
COM
Accessories
7
6
USB
connection (5)
Short description:
This fieldbus coupler links the WAGO SPEEDWAY 767 system to the sercos network. It
determines station structureand generates the required process images of the configured
inputs and outputs. Setting up the station can involve a mixed arrangement of analog, digital or specialty I/O modules. The fieldbus coupler application allows access to the device as a sercos I/O device on the network. The sercos service channel (SVC), real-time
channel (RTC) and IP channel (NRT) are supported for standard TCP/IP communication.
Two integrated ETHERNET ports allow easy creation of a line and ring structure without
requiring additional components. Each port supports Auto MDI/MDI-X and automatically
detects the direction of transmission, allowing both patch and crossover cables to be used.
Assigning the sercos address can be performed via switch 10, either using the operation
panel (switches) or software (retentive memory). In addition, the fieldbus coupler has 8
digital inputs to capture binary signals from switches and sensors.
System bus
connection (3)
SBM
Module supply:
Connection type (1)
Current carrying capacity of supply
connections
Supply voltage
Logic and sensor voltage ULS
Actuator voltage UA
Supply current
Logic and sensor current ILS
Actuator current IA
Protection
sercos I/O device
M12 connectors, D coded, 5 poles
100 Mbit/s, full duplex
Copper cable (Cat. 5e, Class D)
0 – 511 (adjustable via operation panel or
software)
sercos v1.1.2, TCP/IP, FTP, HTTP
SVC, RTC, CC, IP
GDP_Basic, SCP_VarCfg, SCP_Sync,
SCP_Diag, SCP_WD, SCP_NRT, FSP_IO
M12 connectors, A coded, 4 poles
Max. 8 A (ULS: 4 A, UA: 4 A)
24 VDC (-25 % ... +30 %)
24 V DC (-25 % ... +30 %);
Also required for power supply
transmission
typ. 140 mA + sensors (max. 400 mA)
5mA
Reverse voltage protection for ULS + UA;
short circuit protection for sensor supply
2
11
Input 2
M12 D coded
System bus
connection
1: TX+
2: RX+
3: TX–
4: RX–
Housing: Shield
M12 B coded
1: TD+
2: TD-3: RD-4: RD+
5: GND
Housing: Shield
Block diagram of an input
Digital Input
X1 ... X8
Supply
M12
Reset
Boot / Execute
Operation panel
Disable Switch
28 Address
27
26
25
24
23
22
21
20
USB
COM
M8
M8
Digital Inputs
X1 ... X8
1: 24 V
3: 0 V ULS
Logic
M8
Input 0 ... 7
Error F
4: Input
Input
1: +5 V
2: –Data
3: +Data
4: GND
Housing: Shield
Supply
Output
1: 24 V ULS
2: 24 V UA
3: 0 V ULS
4: 0 V UA
M12 A coded
Technical Data
Digital inputs:
Number of inputs
Connection type (2)
Wire connection
Input filter
Hardware delay
up to fieldbus
Input characteristic
Signal voltage (0)
Signal voltage (1)
Input wiring
Input voltage
Input current (typ.)
Cable length, unshielded
Wrong connection of inputs
System bus:
Number of expendable modules
Connection type (3)
Distance between two modules
Total extension per station
Isolation:
Channel - Channel
ULS, UA, system bus, fieldbus
Service:
Type
Connection type (5)
Standards and approvals:
r UL 508
Conformity marking
Configurable functions:
Fieldbus coupler
Digital Inputs
Input filter (per channel)
Inversion (per channel)
Online simulation (per channel)
I/O diagnostics:
I/O diagnostics (per module)
Module
mount
Technical Data
8
M8 connectors, 3 poles
2- or 3-wire
Hardware: ≤ 10 μs, software
parametrizable depending on operating
mode
10 μs (direct mode)
Type 1, acc. to IEC 61131-2
-30 V ... +5 V DC
+15 V ... +30 V DC
high-side switching
24 VDC (-30 VDC < UIN < +30 VDC)
2.8 mA
≤ 30 m
No effect
64
M12 connectors, B coded, 5 poles,
shielded
20 meters
200 meters
Process image:
Input process image
Output process image
LED indicators:
MS: Module status
S3: sercos status
ACT/LNK 1 : ETHERNET data
exchange/network connection
ACT/LNK 2 : ETHERNET data
exchange/network connection
CS : Fieldbus coupler status
SBM : System bus master status
F: Error status
0 ... 7: Input signal status
ULS + UA: Supply status
Indicators
Advanced features:
Operating hours counter
High-speed inputs
2048 bytes
2048 bytes
LED (green/red)
LED (green/red)
LED (green)
LED (green)
LED (green/red)
LED (green/red)
LED (red)
LED (yellow)
LED (green)
Non-latching
Values in [h]
parametrizable, depending on operating
mode (see manual)
No
500 VDC each
USB standard 1.1
M8 connectors, 4 poles
1
see manual
depending on operating mode
0.1/ 0.5/ 3 /15 /20 ms/ filter off
On/off
Lock/unlock, simulation value: 0/1
Short circuit of sensor supply
Undervoltage (ULS + UA)
General Specifications
Dimensions (mm) W x H x L
Weight
75 x 35.7 x 117
400 g
AUTOMATION
sercos
Input 1
767-3806
2
12
Digital Input Module, 24 VDC, High Speed
8 inputs (4 x M12, two inputs per connector)
8DI HS
Module marking
System bus
output (3)
AUTOMATION
System bus
input (3)
6
LED indicators
X
4
4
X
3
7
5
X
2
0
X
1
3
1
24 V
ULS UA
Supply
input (1)
Short description:
This digital input module records binary signals from sensors with short response times.
The 767-3806 Module features high-speed inputs - ideal for use with fast
ETHERNET-based fieldbus systems (e.g., sercos).
Digital
inputs (2)
2
Channel marking
(2 fields per port/
1 field per channel)
Supply
output (1)
767-3806
Included:
• 1 x WMB marker, yellow
• 1 x marking strip
• 2 x M12 protective cap
Features:
• 8 digital inputs, 24 VDC
• Front-end cycle time (hardware) ≤ 10 μs
• Diagnostic-capable (module by module)
• Parametrizable (filter, inversion, online simulation and diagnostics)
Description
Item No.
Pack.
Unit
Technical Data
8DI 24VDC HS (4xM12)
767-3806
1
Module supply:
Connection type (1)
Current carrying capacity of supply
connections
Supply voltage
Logic and sensor voltage ULS
Actuator voltage UA
Accessories
Marking strips, marking pen, spacer
module and protective caps
IP67 cables and connectors
Item No.
see Full Line Catalog 2012/2013
Volume 3
Supply current
Logic and sensor current ILS
Actuator current IA
Protection
Digital inputs:
Number of inputs
Connection type (2)
Wire connection
Front-end cycle time (hardware)
Front-end jitter/skew (input)
Input characteristic
Signal voltage (0)
Signal voltage (1)
Input wiring
Input voltage
Input current (typ.)
Connection of 2-wire BEROs
Cable length, unshielded
Wrong connection of inputs
M12 connectors, A coded, 4 poles;
Derating must be observed
Max. 8 A (ULS: 4 A, UA: 4 A)
24 V DC (-25 % ... +30 %)
24 V DC (-25 % ... +30 %);
Also required for power supply
transmission
typ. 45 mA + sensors (max. 1.0 A)
5 mA
Reverse voltage protection for ULS + UA;
short circuit protection for sensor supply
8
M12 connectors, A coded, 5 poles,
shielded
2- or 3-wire
≤ 10 μs
< 2 μs
Type 3, acc. to IEC 61131-2
-3 V ... +5 V DC
+11 V ... +30 V DC
high-side switching
24 VDC (-3 VDC < UIN < +30 VDC)
2.8 mA
max. 1.5 mA admissible closed current
≤ 30 m
No effect
2
13
M12 B coded
1: RD+/TD+
2: RD--/TD-3: TD--/RD-4: TD+/RD+
5: GND
Housing: Shield
Block diagram of an input
Digital Input
X1 ... X4
Supply
M12
Diagnostics
Digital Inputs X1 ... X4
(two intputs/connector)
5
5
M12 A coded
Supply
Input
Output
1: 24 V
3: 0 V ULS
M12
Logic
5: Shield
Input
0 ... 7
4: Input A
2: Input B
Housing: Shield
1: 24 V ULS
2: 24 V UA
3: 0 V ULS
4: 0 V UA
270 pF
Error
270 pF
5
Module
mount
M12 A coded
Technical Data
Input characteristic:
Input voltage
0V
5V
11 V
24 V
30 V
System bus:
Connection type (3)
Standards and approvals:
r UL 508
Conformity marking
Technical Data
Typical input current
0 mA
1.6 mA
2.7 mA
2.8 mA
2.8 mA
M12 connectors, B coded, 5 poles,
shielded
1
Isolation:
Channel - Channel
ULS, UA, system bus
Configurable functions:
Input filter (per channel)
Inversion (per channel)
Online simulation (per channel)
Online simulation (per module)
I/O diagnostics:
I/O diagnostics (per module)
Process image:
Process data width
LED indicators:
SB: System bus status
F: Error status
0 ... 7: Input signal status
ULS + UA: Supply status
Indicators
No
500 VDC each
10/ 25/ 50/ 100/ 200 μs/ 1/ 3 ms/
filter off
On/off
Lock/unlock, simulation value: 0/1
Diagnostics
Short circuit of sensor supply
Undervoltage (ULS + UA)
1-byte data + status
LED (green/red)
LED (red)
LED (yellow)
LED (green)
Non-latching
General Specifications
Dimensions (mm) W x H x L
Weight
50 x 35.7 x 117
270 g
AUTOMATION
System bus
Input
Output
767-4808
2
14
Digital Output Module, 24 VDC, 0.1 A, High Speed
8 outputs (4 x M12, two outputs per connector)
8DO HS
Module marking
System bus
output (3)
AUTOMATION
System bus
input (3)
6
LED indicators
X
4
4
X
3
7
X
2
0
X
1
3
1
24 V
ULS UA
Supply
input (1)
Short description:
This digital output module outputs signals from actuators with short response
times. The 767-4808 Module features high-speed outputs - ideal for use with
fast ETHERNET-based fieldbus systems (e.g., sercos).
Digital
outputs (2)
2
5
Channel marking
(2 fields per port/
1 field per channel)
Supply
output (1)
767-4808
Features:
• 8 digital outputs, 24 VDC / 0.1 A
• Front-end cycle time (hardware) ≤ 10 μs
• Diagnostic-capable (channel by channel/module by module)
• Parametrizable (inversion, substitute value strategy, substitute value, manual
mode, online simulation and diagnostics)
Included:
• 1 x WMB marker, red
• 1 x marking strip
• 2 x M12 protective cap
Description
Item No.
Pack.
Unit
Technical Data
8DO 24VDC 0,1A HS (4xM12)
767-4808
1
Module supply:
Connection type (1)
Current carrying capacity of supply
connections
Supply voltage
Logic and sensor voltage ULS
Actuator voltage UA
Supply current
Logic and sensor current ILS
Actuator current IA
Accessories
Marking strips, marking pen, spacer
module and protective caps
IP67 cables and connectors
Item No.
see Full Line Catalog 2012/2013
Volume 3
Protection
Digital outputs:
No. of outputs
Connection type (2)
Wire connection
Output voltage
Output current (per channel)
Voltage drop against UA
at nominal load
Output current (module)
Leakage current in OFF state
Output circuit
M12 connectors, A coded, 4 poles;
Derating must be observed
Max. 8 A (ULS: 4 A, UA: 4 A)
24 V DC (-25 % ... +30 %)
24 V DC (-25 % ... +30 %)
typ. 40 mA (logic component only)
typ. 35 mA + actuator supply (≤ 1 A) +
load
Reverse voltage protection for ULS + UA,
short-circuit protection for actuator supply
8
M12 connectors, A coded, 5 poles,
shielded
2- or 3-wire
≤ UA
0.1 A,
short-circuit/overload proof
(thermal disconnection)
Max. 1.7 V DC
max. 0.8A
typ. 50 μA
Push/Pull
2
15
M12 B coded
1: RD+/TD+
2: RD--/TD-3: TD--/RD-4: TD+/RD+
5: GND
Housing: Shield
Block diagram of an output
Digital Output
X1 ... X4
Supply
M12
Digital Outputs X1 ... X4
(two outputs/connector)
5
5
M12
1: 24 V
3: 0 V UA
Output 0 ... 7
5: Shield
Diagnostics 0 ... 7
10 nF
Logic
10 nF
270 pF
M12 A coded
4: Output A
2: Output B
Housing: Shield
Supply
Input
Output
5
Output
0 ... 7
1: 24 V ULS
2: 24 V UA
3: 0 V ULS
4: 0 V UA
Error
F
Module
mount
M12 A coded
Technical Data
Technical Data
Information on actuator selection:
Front-end cycle time 90%
(hardware)
Edge steepness
Front-end jitter/skew (output)
Cable length
Type of load
Switching frequency
Isolation:
Channel - Channel
ULS, UA, system bus
Configurable functions:
Inversion (per channel)
Substitute value strategy (per channel)
Substitute value (per channel)
Manual mode (per channel)
Manual mode value (per channel)
Online simulation (per channel)
Type of protective circuit
Operating state influence on output:
PLC CPU stop
Fieldbus disruption
S-bus (system bus) disruption
Supply voltage under rated voltage
tolerance
Interruption of
supply voltage
Output operation
Overload behavior
System bus:
Connection type (3)
Standards and approvals:
r UL 508
Conformity marking
< 1 μs
TON/OFF: typ. < 1 μs
< 1 μs
≤ 30 m
Inductive, resistive loads and lamps
Inductive load upon request
Resistive load upon request
Lamp load upon request
External protection (e.g., recovery diodes)
Acc. to substitute value strategy
Acc. to substitute value strategy
0 V status
0 V status
0 V status
Non-latching
Automatic restart
I/O diagnostics:
I/O diagnostics (per channel)
I/O diagnostics (per module)
Process image:
Process data width
LED indicators:
SB: System bus status
F: Error status
0 ... 7: Output signal status
ULS + UA: Supply status
Indicators
No
500 VDC each
On/off
Switch substitute value/hold last value
0/1
On/off
0/1
Lock/Unlock; simulation value: 0/1;
diagnostics
Overtemperature, actuators
Undervoltage (ULS + UA)
1-byte data + status
LED (green/red)
LED (red)
LED (yellow/red)
LED (green)
Non-latching
M12 connectors, B coded, 5 poles,
shielded
1
General Specifications
Dimensions (mm) W x H x L
Weight
50 x 35.7 x 117
260 g
AUTOMATION
System bus
Input
Output
767-5401
2
16
Digital Input/Output Module, 24 VDC / 0.2 A, High Speed
4 inputs/outputs (4 x M12)
4DIO HS
Module marking
System bus
output (3)
AUTOMATION
System bus
input (3)
3
LED indicators
X
4
2
X
3
Digital inputs /
outputs (2)
1
X
2
0
X
1
Channel marking
(2 fields per
port/channel)
24 V
ULS UA
Supply
input (1)
Short description:
This digital input/output module records/outputs binary signals from sensors/
actuators with short response times. The 767-5401 Module features highspeed inputs/outputs - ideal for use with fast ETHERNET-based fieldbus systems
(e.g., sercos).
Supply
output (1)
767-5401
Features:
• 4 digital inputs/outputs, 24 VDC / 0.2 A, incl. counter function
• Front-end cycle time (hardware) ≤ 10 μs
• Diagnostic-capable (channel by channel/module by module)
• Parametrizable (operating mode, filter, inversion, substitute value strategy,
substitute value, manual mode, online simulation and diagnostics)
Included:
• 1 x WMB marker, orange
• 1 x marking strip
• 2 x M12 protective cap
Description
Item No.
Pack.
Unit
Technical Data
4DIO 24VDC 0.2A HS (4xM12)
767-5401
1
Digital inputs:
Number of inputs
Connection type (2)
Accessories
Marking strips, marking pen, spacer
module and protective caps
IP67 cables and connectors
Item No.
see Full Line Catalog 2012/2013
Volume 3
Technical Data
Module supply:
Connection type (1)
Current carrying capacity of supply
connections
Supply voltage
Logic and sensor voltage ULS
Actuator voltage UA
Supply current
Logic and sensor current ILS
Actuator current IA
Protection
M12 connectors, A coded, 4 poles;
Derating must be observed
Max. 8 A (ULS: 4 A, UA: 4 A)
24 V DC (-25 % ... +30 %)
24 V DC (-25 % ... +30 %)
typ. 40 mA (logic component only)
typ. 30 mA + sensors/actuators
(max. 1000 mA) + load
Reverse voltage protection for ULS + UA
Short-circuit protection for sensor/actuator
supply
Wire connection
Front-end cycle time (hardware)
Front-end jitter/skew (input)
Input characteristic
Signal voltage (0)
Signal voltage (1)
Input wiring
Input voltage
Input current (typ.)
Connection of 2-wire BEROs
Cable length, shielded
Wrong connection of inputs
Input characteristic:
Input voltage
0V
5V
15 V
24 V
30 V
Counters:
No. of counters
Counter type
Counting/switching frequency
4
M12 connectors, A coded, 5 poles,
shielded
2- or 3-wire
< 3 μs
< 2 μs
Type 1, acc. to IEC 61131-2
-3 V ... +5 V DC
+15 V ... +30 V DC
high-side switching
24 VDC (-3 VDC < UIN < +30 VDC);
Power from UA strongly recommended
2.9 mA
max. 1.5 mA admissible closed current
≤ 30 m
No effect
Typical input current
0 mA
2.0 mA
2.5 mA
2.9 mA
3.2 mA
1
Event, gateway time, pulse duration
0 Hz ... 1 kHz
2
17
M12, B coded
1: RD+/TD+
2: RD--/TD-3: TD--/RD-4: TD+/RD+
5: GND
Housing: Shield
Block diagram of an input/output
Digital Input/Output
X1 ... X4
Supply
M12
M12
2
3
Digital Inputs/Outputs
X1 ... X4
1: 24 V
3: 0 V UA
5
5
4
Diagnostics sensor/actuator supply
1
Input 0 ... 3
10 nF
Logic
10 nF
5: Shield
Output 0 ... 3
4
M12, A coded
4: In-/Output
Housing: Shield
Input/Output
0 ... 3
Supply
Input
Output
1: 24 V ULS
2: 24 V UA
3: 0 V ULS
4: 0 V UA
270 pF
Error
F
270 pF
5
Module
mount
M12, A coded
Technical Data
Digital outputs:
No. of outputs
Connection type (2)
Wire connection
Output voltage
Output current (per channel)
Voltage drop against UA
at 200 mA
Output current (module)
Leakage current in OFF state
Output circuit
Information on actuator selection:
Front-end cycle time 90%
(hardware)
Edge steepness
Front-end jitter/skew (output)
Type of load
Switching frequency
Type of protective circuit
Operating state influence on output:
PLC CPU stop
Fieldbus disruption
S-bus (system bus) disruption
Supply voltage under rated voltage
tolerance
Interruption of
supply voltage
Output operation
Overload behavior
Technical Data
4
M12 connectors, A coded, 5 poles,
shielded
2- or 3-wire
≤ UA
0.2 A,
short-circuit/overload proof
(thermal disconnection)
Max. 2.0 V DC
max. 0.8A
typ. 100 μA
Push/Pull
< 1 μs
TON/OFF: typ. < 1 μs
< 1 μs
Inductive, resistive loads and lamps
Inductive load upon request
Resistive load upon request
Lamp load upon request
External protection (e.g., recovery diodes)
Acc. to substitute value strategy
Acc. to substitute value strategy
0 V status
0 V status
0 V status
Non-latching
Automatic restart
System bus:
Connection type (3)
Standards and approvals:
r UL 508
Conformity marking
Isolation:
Channel - Channel
ULS, UA, system bus
Configurable functions:
Operating mode (per module)
Input filter (per channel)
Inversion (per channel)
Substitute value strategy (per channel)
Substitute value (per channel)
Manual mode (per channel)
Manual mode value (per channel)
Online simulation (per channel)
Online simulation (per channel/
I/O diagnostics:
I/O diagnostics (per channel)
I/O diagnostics (per module)
Process image:
Process data width
LED indicators:
SB: System bus status
F: Error status
0 – 3: Signal status, inputs/outputs
0 – 3: Diagnostics, outputs
ULS + UA: Supply status
M12 connectors, B coded, 5 poles,
shielded
1
No
500 VDC each
DO module/DI module/DIO module/
DIO + 1 counter
10/ 25/ 50/ 100/ 200 μs/ 1/ 3 ms/
filter off
On/off
Switch substitute value/hold last value
0/1
On/off
0/1
Lock/unlock, simulation value: 0/1
Diagnostics
Overtemperature
Short-circuit of sensor/actuator supply
Undervoltage (ULS + UA)
depends on operating mode
LED (green/red)
LED (red)
LED (yellow/red)
LED (red)
LED (green)
General Specifications
Dimensions (mm) W x H x L
Weight
50 x 35.7 x 117
255 g
AUTOMATION
System bus
Input
Output
758-916, 758-917
7
Wireless transmission link for ETHERNET protocols
AUTOMATION
18
WLAN ETHERNET Gateway
Power connector:
M12 plug, A-coded
1: Vin + (DC 9 ... 30 V)
2: External Trigger Ground
3: Vin GND (0 V)
4: External Trigger + (DC 9 ... 30 V)
5: n.c.
ETHERNET connector:
M12 socket, D-coded
1: Transmit +
2: Receive +
3: Transmit 4: Receive -
WAGO WLAN ETHERNET Gateways simplify creation of a wireless
transmission link for ETHERNET protocols (e.g., PROFINET, MODBUS/TCP,
Ethernet/IP).
Note:
Two WLAN ETHERNET Gateways of the same type are required to
establish a point-to-point connection.
The gateway is used as a cable substitute to create a robust, industry-proven
WLAN link between two automation devices.
The IP65 housing and circularly polarized antenna allow the gateway to be
used even in harsh industrial environments. Simple, push-button operation
provides very fast connection between two WLAN ETHERNET Gateways.
Description
Item No.
Pack.
Unit
Technical Data
WLAN ETHERNET Gateway, 2.4 GHz
WLAN ETHERNET Gateway, 5 GHz
758-916
758-917
1
1
Wireless technology
Topology
Security authentification
Security encryption
Frequency band
Transmission range
Antenna
Pack.
Unit
Accessories
Item No.
IP67 cables and connectors
see Full Line Catalog 2010/2011
I/O-SYSTEM, Sections 6 and 9
Voltage supply
Voltage range
Ports
Configuration
Approvals
Conformity marking
R&TTE (Europe)
FCC/CFR 47 part 15
IC (Industry Canada)
1
Number of inputs
Dimensions (mm) W x H x L
Weight
Operating temperature
Storage temperature
Degree of protection
EMC: 1 - immunity to interference
IEEE 802.11 bgn (758-916)
IEEE 802.11 an (758-917)
Point-to-point connection
Open, Shared, WPA/WPA2 PSK, LEAP,
PEAP
None, WEP64, WEP128, TKIP,
AES/CCMP
License-free ISM band, 2.4 GHz (758-916)
License-free ISM band, 5 GHz (758-917)
up to 400 m (758-916)
up to 200 m (758-917)
Internal, circularly polarized, directional
antenna
24 V DC
9 V ... 30 V DC
ETHERNET connector:
M12 socket, D-coded
Power connector:
M12 plug, A-coded
Simple, push-button operation and
Web-based management
1 (trigger input 9 V ... 30 VDC)
66 x 36.2 x 91
120 g
-30 °C ... +65 °C
-40 °C ... +85 °C
IP65
acc. to EN 61000-6-2 (2005)
10
WAGO Ribbon Cables
AUTOMATION
19
753 Series connector
753 Series connector
20-pole female connector
10-pole female
connector
WAGO ribbon cables provide fast and easy connection of WAGO I/O modules
equipped with pluggable connectors (e.g., 753-430, -431, -530) to appropriate
interface or relay modules featuring a 10-pole female connector.
WAGO ribbon cables provide fast and easy connection of WAGO I/O modules
equipped with pluggable connectors (e.g., 753-430, -431, -530) to appropriate
interface or relay modules featuring a 20-pole female connector.
For example, this cable connects two WAGO I/O modules to one relay output module
(16-channel).
Description
Item No.
Pack.
Unit
WAGO ribbon cable, 1 x 753 Series pluggable
connector/10-pole female connector, 1 m long
706-7753/300-100
1
For other cable lengths, please contact factory.
Item No.
Pack.
Unit
WAGO ribbon cable, 2 x 753 Series pluggable
connector/20-pole female connector, 2 m long
706-7753/301-200
1
For other cable lengths, please contact factory.
Technical Data
Wire cross-section
Color coding
Current per channel
Operating temperature *
Degree of protection
Length
Description
Technical Data
2
0.14 mm LiYY
acc. to DIN VDE 47100
max. 1 A
-25 °C ... +70 °C
IP20
1 m
Wire cross-section
Color coding
Current per channel
Operating temperature
Degree of protection
Length
0.14 mm2 LiYY
acc. to DIN VDE 47100
max. 1 A
-25 °C ... +70 °C
IP20
2 m
* Observe maximum operating temperature of the WAGO I/O modules used.
1
JUMPFLEX® Relay
20
<_________ 96 mm/3.76 in _________>
INTERFACE ELECTRONIC
With 2 relays, with 1 make contact (1 a)
for normal switching power
Nominal input voltage
VN 24 V AC/DC
_>
_>
____________
<_________ 94 mm/3.68 in _________>
6 mm/0.23 in
Note: Inductive loads have to be attenuated by an
appropriate protective circuit in order to protect relay coils
and contacts.
A1
13
A2
14
A3
23
A4
24
Description
VN
IN
Item No.
Pack.
Unit
JUMPFLEX® Relais,
for DIN 35 rail
AC/DC 24 V
10 mA
857-1330
1
Technical Data
Contact material
Input voltage range
Max. switching voltage
Max. continuous current (terminal blocks in a row)
Max. Switching power (resistive)
Recommended minimum load
Max. switching rate with / without load
Operating power
Pull-in/drop-out/bounce time typ.
Nominal operating mode
Dielectric strength contact-coil
Surge capacity open contact
Nominal voltage acc. to VDE 0110 Part 1/4.97,
IEC 60664-1
Mechanical life
Mechanical life at max. load (resistance)
Ambient operating temperature (VN)
Storage temperature
Dimensions (mm) W x H x L
Wire connection
Cross sections
Stripped lengths
Approvals
Accessories see Full Line Catalog 2010/2011 Interface Modules
AgSnO2
VN -15 % ... +20 %
250 V AC
4A
AC 1000 VA; DC see load limit curve
t 100 mA / 12 V AC/DC
6 min-1 / 20 s-1
< 300 mW / < 700 mW
5 ms / 6 ms / 5 ms
continuous duty
2.5 kV
1 kV eff
250 V / 4 kV / 3
5 x 106 switching operations
5 x 104 switching operations
-25 °C ... +60 °C
-40 °C ... +85 °C
6 x 96 x 94
Height from upper-edge of DIN 35 rail
CAGE CLAMP®S
solid: 0.08 mm² ... 2.5 mm² / AWG 28 ... 12
fine-stranded: 0.34 mm² ... 2.5 mm² / AWG 22 ... 12
9 ... 10 mm / 0.37 in
VDE 0110 / EN 60664; VDE 0435 / EN 61810-1
S
JUMPFLEX® Optocouplers
1
21
<_________ 96 mm/3.76 in _________>
INTERFACE ELECTRONIC
Optocoupler
Input: 2 x 24 VDC
Output: 2 x 3 – 30 VDC / 3 A
Optocoupler
Input: 2 x 24 VDC
Output: 2 x 9 – 60 VDC / 0.1 A
_>
_>
____________
<_________ 94 mm/3.68 in _________>
6 mm/0.23 in
A1
13
A2
14
A3
23
A1
13
A2
14
A3
23
A4
24
RL
RL
RL
RL
A4
24
Description
Item No.
Pack.
Unit
Item No.
Pack.
Unit
JUMPFLEX® Optocoupler,
for DIN 35 rail
857-1494
1
857-1430
1
Technical Data
Control circuit:
Nominal input voltage (VN)
Input voltage range
Input voltage range (low level)
Input voltage range (high level)
Input current range
Nominal input current (IN)
Load circuit:
Switching voltage
Max. switching current
Peak reverse voltage
Forward voltage at max. switching current
Leakage current at nominal voltage
Switch on/switch off time
Max. switching frequency
Dielectric strength control/switching circuit
Dielectric strength channel/channel
Ambient operating temperature
Storage temperature
Dimensions (mm) W x H x L
Wire connection
Cross sections
Stripped lengths
Accessories see Full Line Catalog 2010/2011 Interface Modules
2 x 24 V DC
VN -30 % … +25 %
0 V ... 5 V
16.8 V ... 30 V
3 mA ... 7.8 mA
5.6 mA
2 x 24 V DC
VN -30 % … +25 %
0 V ... 5 V
16.8 V ... 30 V
4.25 mA ... 11 mA
7.75 mA
2 x DC 9 V ... 60 V
2 x 0.1 A DC
100 V
<2V
25 μA
20 μs / 120 μs
1.5 kHz
2.5 kV
4 kV
-25 °C ... +70 °C
-40 °C ... +85 °C
6 x 96 x 94
Height from upper-edge of DIN 35 rail
CAGE CLAMP®S
solid: 0.08 mm² ... 2.5 mm² / AWG 28 ... 12
fine-stranded: 0.34 mm² ... 2.5 mm² / AWG 22 ... 12
9 ... 10 mm / 0.37 in
2 x DC 3 V ... 30 V
2 x 3 A DC
55 V
< 0.2 V
250 μA
25 μs / 250 μs
300 Hz
2.5 kV
4 kV
-25 °C ... +70 °C
-40 °C ... +85 °C
6 x 96 x 94
Height from upper-edge of DIN 35 rail
CAGE CLAMP®S
solid: 0.08 mm² ... 2.5 mm² / AWG 28 ... 12
fine-stranded: 0.34 mm² ... 2.5 mm² / AWG 22 ... 12
9 ... 10 mm / 0.37 in
8
1
JUMPFLEX® Optocouplers
22
INTERFACE ELECTRONIC
Optocoupler
Input: 2 x 24 VDC
Output: 2 changeover contacts,
2 x 24 VDC / 0.5 A
A1
12
1
11
RL
14
22
1
21
A2
RL
24
Description
Item No.
Pack.
Unit
JUMPFLEX® Optocoupler,
for DIN 35 rail
857-1432
1
Technical Data
Control circuit:
Nominal input voltage (VN)
Input voltage range
Input voltage range (low level)
Input voltage range (high level)
Input current range
Nominal input current (IN)
Load circuit:
Switching voltage
Max. switching current
Min. switching current
Forward voltage at max. switching current
Leakage current at nominal voltage
Switch on/switch off time
Max. switching frequency
Dielectric strength control/switching circuit
Ambient operating temperature
Storage temperature
Dimensions (mm) W x H x L
Wire connection
Cross sections
Stripped lengths
Accessories see Full Line Catalog 2010/2011 Interface Modules
24 V DC
VN -30 % … +25 %
0 V ... 5 V
16.8 V ... 30 V
5.3 mA ... 6.3 mA
5.9 mA
2 x DC 3 V ... 30 V
2 x 500 mA
2 x 0.5 mA
< 1.5 V
20 μA
25 μs / 250 μs
1.5 kHz
3.75 kV
-25 °C ... +70 °C
-40 °C ... +85 °C
6 x 96 x 94
Height from upper-edge of DIN 35 rail
CAGE CLAMP®S
solid: 0.08 mm² ... 2.5 mm² / AWG 28 ... 12
fine-stranded: 0.34 mm² ... 2.5 mm² / AWG 22 ... 12
9 ... 10 mm / 0.37 in
INTERFACE ELECTRONIC
S
1
23
1
WAGO Ribbon Cables
INTERFACE ELECTRONIC
24
Color coding
HE 10
acc. to DIN VDE 47100
20-pole
Color coding
contact number
acc. to DIN VDE 47100
HE 10
16-pole
contact number
white
1
white
1
brown
2
brown
2
green
3
green
3
yellow
4
yellow
4
grey
5
grey
5
pink
6
pink
6
blue
7
blue
7
red
8
red
8
black
9
black
9
violet
10
violet
10
grey/pink
11
grey/pink
11
red/blue
12
red/blue
12
white/green
13
white/green
13
brown/green
14
brown/green
14
white/yellow
15
white/yellow
15
yellow/brown
16
yellow/brown
16
white/grey
17
grey/brown
18
white/pink
19
pink/brown
20
Description
Item No.
Pack.
Unit
Description
Item No.
Pack.
Unit
WAGO ribbon cable, 20-pole/one free
cable end, lenght 2 m
706-100/1300-200
1
WAGO ribbon cable, 16-pole/one free
cable end, lenght 2 m
706-100/1602-200
1
Technical Data
Ports
Wire cross-section
Color coding
Current per channel
Operating temperature
Degree of protection
Length
Technical Data
20-pole female connector/one free
cable end
0.14 mm2 LiYY
acc. to DIN VDE 47100
max. 1 A
-25 °C ... +70 °C
IP20
2 m
Ports
Wire cross-section
Color coding
Current per channel
Operating temperature
Degree of protection
Length
16-pole female connector/one free
cable end
0.14 mm2 LiYY
acc. to DIN VDE 47100
max. 1 A
-25 °C ... +70 °C
IP20
2 m
1
WAGO Ribbon Cables
INTERFACE ELECTRONIC
25
Color coding
HE 10
acc. to DIN VDE 47100
14-pole
Color coding
contact number
acc. to DIN VDE 47100
HE 10
10-pole
contact number
white
1
white
1
brown
2
brown
2
green
3
green
3
yellow
4
yellow
4
grey
5
grey
5
pink
6
pink
6
blue
7
blue
7
red
8
red
8
black
9
black
9
violet
10
violet
10
grey/pink
11
red/blue
12
white/green
13
brown/green
14
Description
Item No.
Pack.
Unit
Description
Item No.
Pack.
Unit
WAGO ribbon cable, 14-pole/one free
cable end, lenght 2 m
706-100/1303-200
1
WAGO ribbon cable, 10-pole/one free
cable end, lenght 2 m
706-100/1301-200
1
Technical Data
Ports
Wire cross-section
Color coding
Current per channel
Operating temperature
Degree of protection
Length
Technical Data
14-pole female connector/one free
cable end
0.14 mm2 LiYY
acc. to DIN VDE 47100
max. 1 A
-25 °C ... +70 °C
IP20
2 m
Ports
Wire cross-section
Color coding
Current per channel
Operating temperature
Degree of protection
Length
10-pole female connector/one free
cable end
0.14 mm2 LiYY
acc. to DIN VDE 47100
max. 1 A
-25 °C ... +70 °C
IP20
2 m
1
WAGO Ribbon Cables
INTERFACE ELECTRONIC
26
14-pole female connector 14-pole female connector
16-pole female connector 16-pole female connector
The 14-pin cables transmit signals one-to-one from the 14-pole female connector and are
available in 1-, 2- and 3-meter lengths.
The 16-pin cables transmit signals one-to-one from the 16-pole female connector and are
available in 1-, 2- and 3-meter lengths. Signal transmission from the 857-980 Interface
Adapter is also possible.
Suitable for system wiring when combined with the JUMPFLEX® Interface
Adapter (Item No. 857-981 and 857-982)
Suitable for system wiring when combined with the JUMPFLEX® Interface
Adapter (Item No. 857-980)
Description
Item No.
Pack.
Unit
Description
Item No.
Pack.
Unit
WAGO ribbon cable 14/14, 1m long
WAGO ribbon cable 14/14, 2m long
WAGO ribbon cable 14/14, 3m long
706-753/300-100
706-753/300-200
706-753/300-300
1
1
1
WAGO ribbon cable 16/16, 1m long
WAGO ribbon cable 16/16, 2m long
WAGO ribbon cable 16/16, 3m long
706-753/301-100
706-753/301-200
706-753/301-300
1
1
1
Technical Data
Connections
Wire cross-section
Color coding
Current per channel
Operating temperature
Degree of protection
Length
Technical Data
2 x 14-pole female connector
acc. to DIN 41651
0.14 mm2 LiYY
acc. to DIN VDE 47100
max. 1 A
-25 °C ... +70 °C
IP20
1 m (706-753/300-100)
2 m (706-753/300-200)
3 m (706-753/300-300)
Connections
Wire cross-section
Color coding
Current per channel
Operating temperature
Degree of protection
Length
2 x 16-pole female connector
acc. to DIN 41651
0.14 mm2 LiYY
acc. to DIN VDE 47100
max. 1 A
-25 °C ... +70 °C
IP20
1 m (706-753/301-100)
2 m (706-753/301-200)
3 m (706-753/301-300)
1
WAGO Ribbon Cables
INTERFACE ELECTRONIC
27
20-pole female connector
20-pole female connector
15-pole D-sub female
connector
14-pole female connector 14-pole female connector
15-pole D-sub female
connector
The cables provide fast and easy connection of WAGO I/O modules featuring ribbon
cable connectors. The following WAGO I/O modules and adapters are compatible:
750-1500 (16 DO) -- > 857-981 (DO)
750-1502 (8 DO / 8 DI) --> 857-981 (DO) and 857-982 (DI)
The cables provide fast and easy connection of WAGO I/O modules featuring ribbon
cable connectors. The following WAGO I/O modules and D-sub adapters are
compatible:
750-1500 (16 DO) --> 857-986 (DO)
The ribbon cables are available in 1-, 2- and 3-meter lengths -- each has one 20-pole or
two 14-pole female connectors on the ends.
The ribbon cables are available in 1-, 2- and 3-meter lengths -- each has one 20-pole or
two 15-pole female connectors on the ends.
Suitable for system wiring when combined with the JUMPFLEX® Interface
Adapter (Item No. 857-981 and 857-982)
Suitable for system wiring when combined with the JUMPFLEX® Interface
Adapter (Item No. 857-986)
Description
Item No.
Pack.
Unit
Description
Item No.
Pack.
Unit
WAGO ribbon cable 20/2x14, 1m long
WAGO ribbon cable 20/2x14, 2m long
WAGO ribbon cable 20/2x14, 3m long
706-7753/304-100
706-7753/304-200
706-7753/304-300
1
1
1
WAGO ribbon cable 20/2x15, 1m long
WAGO ribbon cable 20/2x15, 2m long
WAGO ribbon cable 20/2x15, 3m long
706-7753/306-100
706-7753/306-200
706-7753/306-300
1
1
1
Technical Data
Connections
Wire cross-section
Color coding
Current per channel
Operating temperature
Degree of protection
Length
Technical Data
1 x 20-pole female connector /
2 x 14-pole female connector
to DIN 41651
0.14 mm2 LiYY
acc. to DIN VDE 47100
max. 1 A
-25 °C ... +70 °C
IP20
1 m (706-7753/304-100)
2 m (706-7753/304-200)
3 m (706-7753/304-300)
Connections
Wire cross-section
Color coding
Current per channel
Operating temperature
Degree of protection
Length
1 x 20-pole female connector to
DIN 41651 / 2 x 15-pole D-sub female
connector to DIN 41652
0.14 mm2 LiYY
acc. to DIN VDE 47100
max. 1 A
-25 °C ... +70 °C
IP20
1 m (706-7753/306-100)
2 m (706-7753/306-200)
3 m (706-7753/306-300)
1
Sockets with Miniature Switching Relay
Relay with 1 changeover contact
Electrical and mechanical status indication
Manual operation
(Relay height: 25 mm)
Nominal input voltage VN:
24 V DC, 48 V DC, 110 V DC
Switching current (A)
INTERFACE ELECTRONIC
28
Relay with 2 changeover contact
Electrical and mechanical status indication
Manual operation
(Relay height: 25 mm)
Nominal input voltage VN:
24 V DC, 48 V DC, 110 V DC
1 change over contact
2 change over contacts
Switching voltage (V)
14
A1
+
A1
+
14
11
11
12
12
A2
-
24
A2
-
21
22
Description
VN
IN
Item No.
Pack.
Unit
Relay sockets with pluggable miniature switching
relay, for DIN 35 rail
24 V DC
48 V DC
110 V DC
16.7 mA
8.3 mA
3.6 mA
788-341
788-342
788-344
1
1
1
Technical Data
Contact material
Input voltage range
Max. switching voltage
Max. continuous current
Max. Switching power (resistive)
Operating power
Responce time/Drop-out time max.
Nominal operating mode
Dielectric strength contact-coil
Dielectric strength open contact
Nominal voltage acc. to VDE 0110 Part 1/4.97,
IEC 60664-1
Mechanical life
Degree of protection
Ambient operating temperature
Storage temperature
Dimensions (mm) W x H x L
Wire connection
Cross sections
Stripped lengths
Standards/Specifications
VN
IN
Item No.
Pack.
Unit
24 V DC
48 V DC
110 V DC
16.7 mA
8.3 mA
3.6 mA
788-346
788-347
788-349
1
1
1
Accessories see Full Line Catalog 2010/2011 Volume 4
AgNi
UN ± 10 %
250 V AC
16 A
4 kVA AC
400 mW typ.
15 ms / 8 ms
continuous duty
5 kV
1 kV
AgNi
UN ± 10 %
250 V AC
2x8A
2 x 2 kVA AC
400 mW typ.
15 ms / 8 ms
continuous duty
5 kV
1 kV
250 V / 4 kV / 3
5 x 106 switching operations
IP20
-25 °C ... +50 °C
-40 °C ... +70 °C
15 x 73 x 86
Height from upper-edge of DIN 35 rail
CAGE CLAMP®S
0.34 mm² ... 2.5 mm² / AWG 22 ... 12
9 ... 10 mm / 0.37 in
DIN VDE 0140 part 1, DIN EN 61140; DIN VDE 0160,
EN 50178; degree of protection II
250 V / 4 kV / 3
5 x 106 switching operations
IP20
-25 °C ... +50 °C
-40 °C ... +70 °C
15 x 73 x 86
Height from upper-edge of DIN 35 rail
CAGE CLAMP®S
0.34 mm² ... 2.5 mm² / AWG 22 ... 12
9 ... 10 mm / 0.37 in
DIN VDE 0140 part 1, DIN EN 61140; DIN VDE 0160,
EN 50178; degree of protection II
S
1
Relay with 1 changeover contact
Electrical and mechanical status indication
Manual operation
(Relay height: 25 mm)
Nominal input voltage VN:
24 V AC, 115 V AC, 230 V AC
Relay with 2 changeover contact
Electrical and mechanical status indication
Manual operation
(Relay height: 25 mm)
Nominal input voltage VN:
24 V AC, 115 V AC, 230 V AC
Similar to illustration
Similar to illustration
1 change over contact
2 change over contacts
Switching voltage (V)
14
A1
∼
A1
∼
14
11
12
11
12
24
A2
∼
A2
∼
21
22
Description
VN
IN
Item No.
Pack.
Unit
Relay sockets with pluggable miniature switching
relay, for DIN 35 rail
24 V DC
115 V AC
230 V AC
31.6 mA
6.6 mA
3.2 mA
788-541
788-543
788-544
1
1
1
Technical Data
Contact material
Input voltage range
Max. switching voltage
Max. continuous current
Max. Switching power (resistive)
Operating power
Responce time/Drop-out time max.
Nominal operating mode
Dielectric strength contact-coil
Dielectric strength open contact
Nominal voltage acc. to VDE 0110 Part 1/4.97,
IEC 60664-1
Mechanical life
Degree of protection
Ambient operating temperature
Storage temperature
Dimensions (mm) W x H x L
Wire connection
Cross sections
Stripped lengths
Standards/Specifications
VN
IN
Item No.
Pack.
Unit
24 V DC
115 V AC
230 V AC
31.6 mA
6.6 mA
3.2 mA
788-546
788-548
788-549
1
1
1
Accessories see Full Line Catalog 2010/2011 Volume 4
AgNi
UN ± 10 %
250 V AC
16 A
4 kVA AC
0.75 VA typ.
15 ms / 8 ms
continuous duty
5 kV
1 kV
AgNi
UN ± 10 %
250 V AC
2x8A
2 x 2 kVA AC
0.75 VA typ.
15 ms / 8 ms
continuous duty
5 kV
1 kV
250 V / 4 kV / 3
5 x 106 switching operations
IP20
-25 °C ... +50 °C
-40 °C ... +70 °C
15 x 73 x 86
Height from upper-edge of DIN 35 rail
CAGE CLAMP®S
0.34 mm² ... 2.5 mm² / AWG 22 ... 12
9 ... 10 mm / 0.37 in
DIN VDE 0140 part 1, DIN EN 61140; DIN VDE 0160,
EN 50178; degree of protection II
250 V / 4 kV / 3
5 x 106 switching operations
IP20
-25 °C ... +50 °C
-40 °C ... +70 °C
15 x 73 x 86
Height from upper-edge of DIN 35 rail
CAGE CLAMP®S
0.34 mm² ... 2.5 mm² / AWG 22 ... 12
9 ... 10 mm / 0.37 in
DIN VDE 0140 part 1, DIN EN 61140; DIN VDE 0160,
EN 50178; degree of protection II
INTERFACE ELECTRONIC
Switching current (A)
29
1
Relay Socket with Solid State Relay
30
INTERFACE ELECTRONIC
Solid state relay
Input: 24 V AC/DC
Output: 12 – 275 VAC / 2 A
Zero voltage switch
A1
13 (L)
A2
14 (Last)
Description
VN
IN
Item No.
Pack.
Unit
Relay socket with solid state relay,
for DIN 35 rail
24 V AC/DC
10 mA
788-721
1
For accessories, see Full Line Catalog 10/11,
Interface Modules, or online catalog
Technical Data
Control circuit:
Input voltage range
Release voltage
Control circuit resistance
Load circuit:
Max. switching voltage
Load switching voltage range
Peak reverse voltage
Max. switching current
Forward voltage at max. switching current
Dielectric strength control/switching circuit
Nominal voltage acc. to IEC 60664-1
Degree of protection
Ambient operating temperature (VN)
Storage temperature
Dimensions (mm) W x H x L
Wire connection
Cross sections
Stripped lengths
Standards/Specifications
15 – 30 VAC
2.5 V AC/DC
2.1 kΩ
275 VAC
12 – 275 VAC (50/60 Hz)
600 V
2A AC
< 1.1 VAC
4 kV
250 V / 2.5 kV / 2
IP20
-20 °C ... +60 °C
-40 °C ... +70 °C
15 x 53 x 86
Height from upper-edge of DIN 35 rail
CAGE CLAMP® S
0.34 mm² ... 2.5 mm² / AWG 22 ... 12
9 ... 10 mm / 0.37 in
DIN VDE 0140 part 1, DIN EN 61140; DIN VDE 0160,
EN 50178; degree of protection II
INTERFACE ELECTRONIC
1
31
1
Relay Sockets with Industrial Relay
32
INTERFACE ELECTRONIC
Relay sockets with industrial relay
Coil voltage:
24 VDC, 110 VDC, 220 VDC
4 changeover contacts
14
11
12
24
A1
+
21
22
34
31
32
44
A2
-
41
42
Description
VN
IN
Item No.
Pack.
Unit
Relay socket with industrial relay,
for DIN 35 rail
24 VDC
110 VDC
220 VDC
31.5 mA
7.7 mA
4.3 mA
858-390
858-392
858-391
1
1
1
Technical Data
Coil
Input voltage range
Contacts
Contact material
Max. continuous current
Max. make current (resistive) at a 10 % duty cycle
Max. switching voltage
Max. Switching power (resistive)
Recommended minimum load
Pull-in/drop-out/bounce time typ.
Mechanical life
General specifications:
Nominal voltage acc. to IEC 60664-1
Dielectric strength contact-coil
Surge capacity open contact
Dielectric strength contact-contact (AC, 1 min.)
Ambient operating temperature (VN)
Storage temperature
Dimensions (mm) W x H x L
Wire connection
Cross sections
Stripped lengths
Standards/Specifications
(OT = On-time)
For accessories, see Full Line Catalog 10/11, Interface Modules, or online catalog
UN -10 % ... +30 %
AgNi 90/10
4x6A
12 A / 20 ms
240 VAC
4 AC x 1500 VA, DC see load curve
12 V / 10 mA
15 ms / 18 ms / 8 ms
30 x 106 switching operations
250 V / 2.5 kV / 2
2.5 kV eff
1.2 kV eff
2 kV eff
-40 °C ... +70 °C
-40 °C ... +85 °C
31 x 55 x 97
Height from upper-edge of DIN 35 rail
CAGE CLAMP® S
2 x 0.34 mm² ... 2 x 1.5 mm² /
1 x 2,5 mm²
AWG 22 ... 16
9 ... 10 mm / 0.37 in
EN 61810-1, EN 60664-1
1
Relay Sockets with Industrial Relay
33
14
A1
+
21
22
A2
VN
IN
Item No.
Pack.
Unit
Relay socket with industrial relay,
for DIN 35 rail
24 VDC
48 VDC
110 VDC
220 VDC
37.5 mA
18.5 mA
8.1 mA
4.1 mA
858-324
858-325
858-327
858-328
1
8
8
8
Coil
Input voltage range
Contacts
Contact material
Max. continuous current
Max. make current (resistive) at a 10 % duty cycle
Max. switching voltage
Max. Switching power (resistive)
Recommended minimum load
Pull-in/drop-out/bounce time typ.
Mechanical life
General specifications:
Nominal voltage acc. to IEC 60664-1
Dielectric strength contact-coil
Surge capacity open contact
Dielectric strength contact-contact (AC, 1 min.)
Ambient operating temperature (VN)
Storage temperature
Dimensions (mm) W x H x L
Wire connection
Cross sections
Stripped lengths
Standards/Specifications
(OT = On-time)
11
12
24
21
22
A2
Description
Technical Data
14
A1
11
12
24
INTERFACE ELECTRONIC
Relay socket with industrial relay
Coil voltage:
AC 230 V
2 changeover contacts
Relay sockets with industrial relay
Coil voltage:
24 VDC, 48 VDC, 110 VDC, 220 VDC
2 changeover contacts
VN
IN
Item No.
Pack.
Unit
230 VAC
11 mA
858-528
8
For accessories, see Full Line Catalog 10/11, Interface Modules, or online catalog
UN -20 % ... +10 %
UN -20 % ... +10 %
AgNi
2 x 12 A
24 A / 4 s
250 VAC
2 AC x 3000 VA, DC see load curve
5 V / 5 mA / 0.3 W
13 ms / 3 ms
2 x 107 switching operations
AgNi
2 x 12 A
24 A / 4 s
250 VAC
2 AC x 3000 VA, DC see load curve
5 V / 5 mA / 0.3 W
10 ms / 8 ms
2 x 107 switching operations
250 V / 4 kV / 2
2.5 kV eff
1.5 kV eff
2.5 kV eff
-40 °C ... +70 °C
-40 °C ... +70 °C
31 x 73 x 97
Height from upper-edge of DIN 35 rail
CAGE CLAMP® S
2 x 0.34 mm² ... 2 x 1.5 mm² /
1 x 2.5 mm²/
AWG 22 ... 16
9 ... 10 mm / 0.37 in
EN 61810-1, EN 60664-1
250 V / 4 kV / 2
2.5 kV eff
1.5 kV eff
2.5 kV eff
-40 °C ... +55 °C
-40 °C ... +70 °C
31 x 73 x 97
Height from upper-edge of DIN 35 rail
CAGE CLAMP® S
2 x 0.34 mm² ... 2 x 1.5 mm² /
1 x 2.5 mm²/
AWG 22 ... 16
9 ... 10 mm / 0.37 in
EN 61810-1, EN 60664-1
1
Relay Modules in DIN-Rail Mount Enclosure
Switching current (A)
INTERFACE ELECTRONIC
34
Relay with 1 changeover contact (1 u),
manual configuration,
electrical and mechanical activation indicator
Relay with 2 changeover contacts (2 u),
manual configuration,
electrical and mechanical activation indicator
Similiar to picture
Similiar to picture
1 change over contact
2 change over contacts
Switching voltage (V)
14
12
A1
+
Note: Inductive loads have to be attenuated by an
appropriate protective circuit in order to protect relay coils
and contacts.
A2
–
VN
Relay module in DIN 35-rail mount enclosure
24 VDC
Technical Data
Coil
Input voltage range
Contacts
Contact material
Max. continuous current
Max. make current (resistive) at a 10 % duty cycle
Max. switching voltage
Max. Switching power (resistive)
Pull-in/drop-out/bounce time typ.
Mechanical life
General specifications:
Nominal voltage to EN 60664
Dielectric strength contact-coil
Surge capacity open contact
Dielectric strength contact-contact (AC, 1 min.)
Ambient operating temperature (VN)
Storage temperature
Dimensions (mm) W x H x L
Wire connection
Cross sections
Stripped lengths
Standards/Specifications
(OT = On-time)
A2
–
11
Description
IN
Item No.
789-1341
14
12
24
22
A1
+
Pack.
Unit
VN
24 VDC
IN
21
11
Item No.
789-1346
For accessories, see Full Line Catalog 10/11, Interface Modules, or online catalog
UN -10% ... +10 %
UN -10% ... +10 %
AgNi
12 A
16 A
250 VAC
3000 VA AC
15 ms / 8 ms / 5 x 106 switching operations
AgNi
2x8A
8A
250 VAC
2 x 2000 VA AC
15 ms / 8 ms / 5 x 106 switching operations
250 V / 4 kV / 3
5 kV eff
1 kV eff
-25 °C ... +50 °C
-40 °C ... +70 °C
17.5 x 55 x 90
Height from upper-edge of DIN 35 rail
CAGE CLAMP®
0.08 mm² ... 2.5 mm² / AWG 28 ... 14
5 ... 6 mm / 0.22 in
EN 60664-1
250 V / 4 kV / 3
5 kV eff
1 kV eff
1.5 kV eff
-25 °C ... +50 °C
-40 °C ... +70 °C
17.5 x 55 x 90
Height from upper-edge of DIN 35 rail
CAGE CLAMP®
0.08 mm² ... 2.5 mm² / AWG 28 ... 14
5 ... 6 mm / 0.22 in
EN 60664-1
Pack.
Unit
1
Relay Modules in DIN-Rail Mount Enclosure
Switching current (A)
Relay with 1 changeover contact (1 u),
manual configuration,
electrical and mechanical activation indicator
Relay with 2 changeover contacts (2 u),
manual configuration,
electrical and mechanical activation indicator
1 change over contact
2 change over contacts
Switching voltage (V)
Similiar to picture
14
12
A1
~
Note: Inductive loads have to be attenuated by an
appropriate protective circuit in order to protect relay coils
and contacts.
A2
~
Description
VN
Relay module in DIN 35-rail mount enclosure
230
Technical Data
Coil
Input voltage range
Contacts
Contact material
Max. continuous current
Max. make current (resistive) at a 10 % duty cycle
Max. switching voltage
Max. Switching power (resistive)
Pull-in/drop-out/bounce time typ.
Mechanical life
General specifications:
Nominal voltage to EN 60664
Dielectric strength contact-coil
Surge capacity open contact
Dielectric strength contact-contact (AC, 1 min.)
Ambient operating temperature (VN)
Storage temperature
Dimensions (mm) W x H x L
Wire connection
Cross sections
Stripped lengths
Standards/Specifications
(OT = On-time)
IN
A2
~
11
Item No.
789-1544
14
12
24
22
A1
~
Pack.
Unit
VN
230
IN
21
11
Item No.
789-1549
For accessories, see Full Line Catalog 10/11, Interface Modules, or online catalog
UN -10% ... +10 %
UN -10% ... +10 %
AgNi
12 A
16 A
250 VAC
3000 VA AC
15 ms / 8 ms / 5 x 106 switching operations
AgNi
2x8A
8A
250 VAC
2 x 2000 VA AC
15 ms / 8 ms / 5 x 106 switching operations
250 V / 4 kV / 3
5 kV eff
1 kV eff
-25 °C ... +50 °C
-40 °C ... +70 °C
17.5 x 55 x 90
Height from upper-edge of DIN 35 rail
CAGE CLAMP®
0.08 mm² ... 2.5 mm² / AWG 28 ... 14
5 ... 6 mm / 0.22 in
EN 60664-1
250 V / 4 kV / 3
5 kV eff
1 kV eff
1.5 kV eff
-25 °C ... +50 °C
-40 °C ... +70 °C
17.5 x 55 x 90
Height from upper-edge of DIN 35 rail
CAGE CLAMP®
0.08 mm² ... 2.5 mm² / AWG 28 ... 14
5 ... 6 mm / 0.22 in
EN 60664-1
Pack.
Unit
INTERFACE ELECTRONIC
35
1
Relay Modules in DIN-Rail Mounted Enclosure
Capability of different lamp loads:
(switching operations acc. to EN 60669)
Relay with 1 make contact (1 a),
manual-0-automatic switch
with monitoring contact
Switching current (A)
INTERFACE ELECTRONIC
36
100
AC resistive load
10
DC resistive load
1
10
100
1000
Switching voltage (V)
(+24V)
Note:
Inductive loads have to be attenuated by an appropriate
protective circuit in order to protect relay coils and
contacts!
A1
+
A3
+
B1
A
0
1
A = Automatic (AUTO)
0 = OFF
1 = Manual ON (MAN)
14
n.c.
B2
A2
A2
-
13 13
Description
VN
Item No.
Pack.
Unit
Relay modules in DIN-rail mounted enclosure,
for DIN 35 rail
24 V DC
789-325
1
Technical Data
Contact material
Input voltage range
Current input at rated voltage (coil 20 °C)
Max. switching voltage
Max. make current
Max. continuous current
Max. Switching power (resistive)
Recommended minimum load
Operating power
Pull-in/drop-out/bounce time typ.
Nominal operating mode
Dielectric strength contact-coil
Surge capacity open contact
Nominal voltage acc. to IEC 60664-1
Mechanical life
Mechanical life at max. load (resistance)
Mechanical life at max. lamp load
Signaling
Ambient operating temperature
Storage temperature
Dimensions (mm) W x H x L
Wire connection
Cross sections
Stripped lengths
Standards/Specifications
(OT = On-time)
Ag alloy
VN -15 % ... +20 %
19mA
250 V AC
120 A at 230 V AC (50 ms)
16 A
4000 VA AC, resistance see load limit curve
> 100 mA / 12 V AC/DC
400 mW
15 ms / 5 ms / continuous duty
4 kV eff
1 kV eff
250 V / 4 kV / 3
10 x 106 switching operations
min. 100.000 switching operations
see "Lamp loads" table
Isolated monitoring contact
(B1/B2 closed in automatic mode;
max. 1 A, 250 V AC)
-25 °C ... +40 °C
-40 °C ... +70 °C
17,5 x 55 x 90
Height from upper-edge of DIN 35 rail
CAGE CLAMP®
0.08 mm² ... 2.5 mm² / AWG 28 ... 14
5 ... 6 mm / 0.22 in
DIN VDE 0160 EN 50178, degree of protection II
Type of load
Capability
Electrical life
Incandescent lamp
Halogen lamp 230 V AC
Halogen trafo
Fluorescent lamp not comp., CB, cos ϕ 0,4-0,6
Fluorescent lamp comp., Conv. ballast, C parallel
Fluorescent lamp comp., Conv. ballast, Duo-circuit
Fluorescent lamp with electronic ballast
Energy saving lamp 15 W
Energy saving lamp 13 W
Energy saving lamp 9 W
Gas discharge lamp
Dulux-Lamp not compensated
Dulux-Lamp compensated
Max. capacitance at 230 V AC
2200 W
1400 W
120 VA
20 x 58 W
9 x 58 W
600 W
12 x 58 W
25 pcs
30 pcs
38 pcs
1000 W
800 W
500 W
60 µF
20.000
50.000
20.000
25.000
25.000
20.000
25.000
20.000
20.000
20.000
20.000
20.000
20.000
min. 5.000
1
Relay Modules in DIN-Rail Mounted Enclosure
Capability of different lamp loads:
(switching operations acc. to EN 60669)
Switching current (A)
Relay with 1 changeover contact (1 u),
manual-0-automatic switch
with switch position monitoring
100
AC resistive load
10
DC resistive load
1
10
100
1000
Switching voltage (V)
(+24V)
Note:
Inductive loads have to be attenuated by an appropriate
protective circuit in order to protect relay coils and
contacts!
A1
+
A3
+
A
0
1
A = Automatic (AUTO)
0 = OFF
1 = Manual (MAN)
14
12
B1
11
B3
A2
A2
-
Description
VN
Item No.
Pack.
Unit
Relay modules in DIN-rail mounted enclosure,
for DIN 35 rail
24 V DC
789-329
1
Technical Data
Contact material
Input voltage range
Current input at rated voltage (coil 20 °C)
Max. switching voltage
Max. make current
Max. continuous current
Max. Switching power (resistive)
Recommended minimum load
Operating power
Pull-in/drop-out/bounce time typ.
Nominal operating mode
Dielectric strength contact-coil
Surge capacity open contact
Nominal voltage acc. to IEC 60664-1
Mechanical life
Mechanical life at max. load (resistance)
Mechanical life at max. lamp load
Signaling
Ambient operating temperature
Storage temperature
Dimensions (mm) W x H x L
Wire connection
Cross sections
Stripped lengths
Standards/Specifications
(OT = On-time)
Ag alloy
VN -15 % ... +20 %
19mA
250 V AC
120 A at 230 V AC (50 ms)
12 A
4000 VA AC, resistance see load limit curve
> 100 mA / 12 V AC/DC
400 mW
15 ms / 5 ms / continuous duty
4 kV eff
1 kV eff
250 V / 4 kV / 3
10 x 106 switching operations
min. 100.000 switching operations
see "Lamp loads" table
Switch position monitoring
(B1 = automatic, B3 = manual;
max. 1 A, 24 V DC)
-25 °C ... +40 °C
-40 °C ... +70 °C
17,5 x 55 x 90
Height from upper-edge of DIN 35 rail
CAGE CLAMP®
0.08 mm² ... 2.5 mm² / AWG 28 ... 14
5 ... 6 mm / 0.22 in
DIN VDE 0160 EN 50178, degree of protection II
Type of load
Capability
Electrical life
Incandescent lamp
Halogen lamp 230 V AC
Halogen trafo
Fluorescent lamp not comp., CB, cos ϕ 0,4-0,6
Fluorescent lamp comp., Conv. ballast, C parallel
Fluorescent lamp comp., Conv. ballast, Duo-circuit
Fluorescent lamp with electronic ballast
Energy saving lamp 15 W
Energy saving lamp 13 W
Energy saving lamp 9 W
Gas discharge lamp
Dulux-Lamp not compensated
Dulux-Lamp compensated
Max. capacitance at 230 V AC
2200 W
1400 W
120 VA
20 x 58 W
9 x 58 W
600 W
12 x 58 W
25 pcs
30 pcs
38 pcs
1000 W
800 W
500 W
60 µF
20.000
50.000
20.000
25.000
25.000
20.000
25.000
20.000
20.000
20.000
20.000
20.000
20.000
min. 5.000
INTERFACE ELECTRONIC
37
789-912
1
For SMI drives, 230 V AC
INTERFACE ELECTRONIC
38
Interface Module RS-232/SMI in DIN-Rail Mountable Enclosure
TxD RxD
GND
+24
RS-232
I-
I+
blue
gray
black
yellow/green
PE
L
SMI
N
I- drive
I+ ~230 V
The 789-912 RS-232/SMI Interface Module is a standard interface for
SMI-compliant electrical drives. The interface represents a purely physical level
conversion between the standard RS-232 interface and the SMI signal level.
The interface module operates up to 16 SMI drives, and the complete SMI
range of functions can be used. The special WAGO-I/O-PRO function blocks
communicate between applications and SMI drives. The modules support both
single and group addressing, as well as status monitoring. Both 750 Series
programmable fieldbus controllers' RS-232 onboard interfaces and
750-650/003-000 or 753-650/003-000 serial RS-232 interfaces can
connect to the SMI Interface Module. The module must be supplied with an
external 24VDC power source. RS-232 and 24V power supply are electrically
isolated from the SMI connections. There is no electrical isolation between
brown
Max. cable length 350 m
L
N
II+
PE
PE
L
SMI
N
I- drive
I+ ~230 V
PE
L
SMI
N
drive
II+ ~230 V
power supply and RS-232. The module is DIN-rail mountable.
Notes on SMI:
SMI stands for Standard Motor Interface, a standard interface for electrical
drives. SMI was developed for connecting drives with integrated electronic
circuitry for applications in shutters and sunshade systems.
Description
Item No.
Pack.
Unit
Technical Data
Interface module RS-232/SMI
789-912
1
Voltage supply
Voltage range
Current consumption (internal)
Number of SMI channels
Number of drives per channel
Operational indication
Interface
Type of cable, cable length
Degree of protection
Mounting position
Ambient operating temperature
Storage temperature
Dimensions (mm) W x H x L
Wire connection
Cross sections
Stripped lengths
Standards/Specifications
24 V DC
± 10%
max. 55mA
1
16
LED green
RS-232 (interface input)
max. 350 m (SMI bus)
max. 3 m (data and power supply cable,
RS-232)
IP20
any
0°C ... +55°C
-25 °C ... +85 °C
35 x 55 x 90
Height from upper-edge of DIN 35 rail
CAGE CLAMP® (WAGO 804 Series)
0.5 mm² ... 2.5 mm² / AWG 20 ... 12
10 ... 11 mm / 0.42 in
EN 50090-2-2
789-913
1
Interface Module RS-232/SMI LoVo in DIN-Rail Mountable Enclosure
For SMI drives, 24 V DC
TxD RxD
GND
INTERFACE ELECTRONIC
39
+24V
RS-232
LoV o
I-
I+
Max. cable length 350 m
+24V
0V
II+
+24V
0V SMI
drive
I24 V
I+
The 789-913 RS-232/SMI LoVo Interface Module is a standard interface for
SMI LoVo-compliant electrical drives. The interface represents a purely physical
level conversion between the standard RS-232 interface and the SMI LoVo
signal level. The interface module operates up to 16 SMI LoVo drives, and the
complete SMI range of functions can be used. The special WAGO-I/O-PRO
function blocks communicate between applications and SMI LoVo drives.
The modules support both single and group addressing, as well as status
monitoring. Both 750 Series programmable fieldbus controllers' RS-232
onboard interfaces and 750-650/003-000 or 753-650/003-000 serial
RS-232 interfaces can connect to the SMI LoVo Interface Module. The module
must be supplied with an external 24VDC power source. RS-232 and 24V
power supply are electrically isolated from the SMI LoVo connections.
+24V
0V SMI
drive
I24 V
I+
+24V
0V SMI
drive
I24 V
I+
There is no electrical isolation between power supply and RS-232. The module
is DIN-rail mountable.
Notes on SMI:
SMI stands for Standard Motor Interface, a standard interface for electrical
drives. SMI was developed for connecting drives with integrated electronic
circuitry for applications in shutters and sunshade systems.
Description
Item No.
Pack.
Unit
Technical Data
Interface module RS-232/SMI LoVo
789-913
1
Voltage supply
Voltage range
Current consumption (internal)
Number of SMI LoVo channels
Number of drives per channel
Operational indication
Interface
Type of cable, cable length
Degree of protection
Mounting position
Ambient operating temperature
Storage temperature
Dimensions (mm) W x H x L
Wire connection
Cross sections
Stripped lengths
Standards/Specifications
24 V DC
± 10%
max. 55mA
1
16
LED green
RS-232 (interface input)
max. 350 m (SMI bus)
max. 3 m (data and power supply cable,
RS-232)
IP20
any
0°C ... +55°C
-25 °C ... +85 °C
35 x 55 x 90
Height from upper-edge of DIN 35 rail
CAGE CLAMP® (WAGO 804 Series)
0.5 mm² ... 2.5 mm² / AWG 20 ... 12
10 ... 11 mm / 0.42 in
EN 50090-2-2
789-620
1
Measuring range 0 ... 80 A
INTERFACE ELECTRONIC
40
Current Sensor with Bus Connection in DIN-Rail Mountable Enclosure
Digital
32767
Digital = Ix364,077
29128
- 10
90 100
- 3641
I/A
- 32768
Short description:
Intelligent current sensor for monitoring solar plants or
inverters for DC measurements within a large current measuring range.
Description
Item No.
Pack.
Unit
Technical Data
Current sensor with bus connection
789-620
1
Electrical data:
Measuring range
Voltage supply
Max. current consumption
Transmission error
Accessories
Item No.
Accessories for data and auxiliary power supply
RJ-45 interface module
289-965
RJ-45 interface module with shield
(screen) clamping saddle
289-966
Pack.
Unit
1
1
Approvals
Conformity marking
Standards/Specifications
1
DIN EN 50178; EN 61000-6-2 ;
EN 61000-6-4
General Specifications
Dimensions (mm) W x H x L
Ambient operating temperature
Storage temperature
35 x 55 x 90
Height from upper-edge of DIN 35 rail
-20°C ... +70°C
-40 °C ... +85 °C
Temperature coefficient
Time frame for polling by master
Hot plugging
Terminating resistor
Status indication
Mechanical data:
Power cable feed-through
Degree of protection
Communication:
Interface
Transmission channels
Protocols
Connector
Addressing
Max. length of bus line
Baud rate
Parity
0 ... 80 A DC
12 - 34V
≤ 8 mA at 24 V
≤ 0.5 % of upper range value
(at room temperature)
0.01 % /K
< 30 ms
possible
150 Ω (can be activated via DIP switch 1)
Green: power
Red: measured current < -3 A or > 83 A
15 mm
IP20
RS-485
Half duplex 8-bit data, 1 stop bit
MODBUS over serial line
RJ-45
1 ... 32
≤ 1200m
19,200 baud
Even
1
789-620
RJ-45-Connector Pin Assignment:
Pin
1
2
Function
RS-485
Uart:
Ub
half duplex
Communication settings requiredfor
transducer:
3
n.c.
4
A (Data+)
5
B (Data-)
6
n.c.
Baud rate: 19200 bd
Data bits: 8
Parity: even
Stop bits: 1
7
GND
8
Communication Description:
MODBUS Function
Read Holding Registers (0x03)
Data Type Measurement
Device Type
0x0000
Char
Firmware
0x0001
Char
Error Code
0x0002
Integer
Measurement
0x0004
Integer
Exception Code
0x0006
Integer
Error Numbers:
Description
id
01
Illegal Function
03
Illegal Data
101
Overflow (Current > +83 A)
102
Underflow (Current < -3 A)
▯ = ON
DIP Switch Adjustability
Adress
2
1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
16
17
18
19
20
21
22
23
24
25
26
27
28
29
30
31
32
Terminating resistor
DIP Switch
3
4
5
6
150 Ohm
●
●
●
●
●
●
●
●
●
●
●
●
●
●
●
●
●
●
●
●
●
●
●
●
●
●
●
●
●
●
●
●
●
●
●
●
●
●
●
●
●
●
●
●
●
●
●
●
●
●
●
●
●
●
●
●
●
●
●
●
●
●
●
●
●
●
●
●
●
●
●
●
●
●
●
●
●
●
●
●
DIP Switch 1
NOTICE:
Only set the MODBUS address in the
OFF state.
●
INTERFACE ELECTRONIC
41
789-621
1
Measuring range: 0 – 140 A
INTERFACE ELECTRONIC
42
Current Sensor with Bus Connection in DIN-Rail Mountable Enclosure
Digital
Digital = I x 208,06
29128
- 10
140
- 3641
I/A
- 32768
Short description:
Intelligent current sensor for monitoring solar plants or
inverters for DC measurements within a large current measuring range.
Description
Item No.
Pack.
Unit
Technical Data
Current sensor with bus connection
789-621
1
Electrical data:
Measuring range
Voltage supply
Max. current consumption
Transmission error
Accessories
Item No.
Accessories for data and auxiliary power supply
RJ-45 interface module
289-965
RJ-45 interface module with shield
(screen) clamping saddle
289-966
Pack.
Unit
1
Temperature coefficient
1
Approvals
Conformity marking
Standards/Specifications
1
DIN EN 50178; EN 61000-6-2 ;
EN 61000-6-4
General Specifications
Dimensions (mm) W x H x L
Ambient operating temperature
Storage temperature
35 x 55 x 90
Height from upper-edge of DIN 35 rail
-20°C ... +70°C
-40 °C ... +85 °C
Time frame for polling by master
Hot plugging
Terminating resistor
Status indication
Mechanical data:
Power cable feed-through
Degree of protection
Communication:
Interface
Transmission channels
Protocols
Connector
Addressing
Max. length of bus line
Baud rate
Parity
0 - 140A DC
12 - 34V
≤ 8 mA at 24 V
0 - 80A: ≤ 0.5% of upper range value (at
room temperature);
80 - 140A: ≤ 1% of upper range value (at
room temperature)
≤ 0.05% /K
(at ambient operating temperature:
-20°C ... +60°C);
≤ 0.1% /K
(at ambient operating temperature:
+60°C ... +70°C)
< 30 ms
possible
150Ω (can be activated via DIP switch 1)
Green: power;
Red: measured current < -3A
or > 143A
15 mm
IP20
RS-485
Half duplex, 8-bit data, 1 stop bit
MODBUS RTU Slave over serial line
RJ-45
1 ... 32
≤ 1200m
19200 baud
Even
1
43
789-622
Pin
1
2
Function
RS-485
Uart:
Ub
half duplex
Communication settings requiredfor
transducer:
3
n.c.
4
A (Data+)
5
B (Data-)
6
n.c.
INTERFACE ELECTRONIC
RJ-45-Connector Pin Assignment:
Baud rate: 19200 bd
Data bits: 8
Parity: even
Stop bits: 1
7
GND
8
Communication Description:
MODBUS Function
Read Holding Registers (0x03)
Address of Measured Value
0x0004
Data Type Measurement
Integer
▯ = ON
DIP Switch Adjustability
Adress
Terminating resistor
DIP Switch
2
3
4
5
6
1
150 Ohm
2
●
3
●
4
●
5
●
6
●
7
●
●
●
●
8
●
10
●
11
●
12
●
13
●
●
14
●
●
15
●
●
●
●
●
●
16
●
●
9
●
●
●
●
●
●
17
●
18
●
19
●
20
●
21
●
●
22
●
●
23
●
●
●
24
●
●
●
25
●
●
26
●
●
27
●
●
●
●
●
●
●
●
●
●
●
28
●
●
29
●
●
●
●
30
●
●
●
31
●
●
●
●
32
●
●
●
●
●
●
●
DIP Switch 1
NOTICE:
Only set the MODBUS address in the
OFF state.
●
789-622
1
Measuring range: 0 – 50 A eff.
INTERFACE ELECTRONIC
44
Current Sensor with Bus Connection in DIN-Rail Mountable Enclosure
Process Value
18205
0
50
I/A (AC)
Short description:
Intelligent DIN 35-rail mount current sensor
for monitoring AC currents.
Description
Item No.
Pack.
Unit
Technical Data
Current sensor with bus connection
789-622
1
Electrical data:
Measuring range
Voltage supply
Max. current consumption
Transmission error
Accessories
Description
Item No.
Accessories for data and auxiliary power supply
RJ-45 interface module
289-965
RJ-45 interface module with shield
(screen) clamping saddle
289-966
Pack.
Unit
1
1
Approvals
Conformity marking
Standards/Specifications
1
DIN EN 50178; EN 61000-6-2 ;
EN 61000-6-4
General Specifications
Dimensions (mm) W x H x L
Ambient operating temperature
Storage temperature
35 x 55 x 90
Height from upper-edge of DIN 35 rail
-20 °C ... +70 °C
-40 °C ... +85 °C
Temperature coefficient
Time frame for polling by master
Hot plugging
Terminating resistor
Status indication
Mechanical data:
Power cable feed-through
Degree of protection
Communication:
Interface
Transmission channels
Protocols
Connector
Addressing
Max. length of bus line
Baud rate
Parity
0 – 50 A AC eff.
12 – 34 V
≤ 8 mA at 24 V
typ. 1%, max. 3% of upper range value (at
room temperature)
≤ 0.01% /K
< 30 ms
possible
150 Ω (can be activated via DIP switch 1)
Green: Power
Red: Measured current > 55 A eff.
15 mm
IP20
RS-485
Half duplex, 8-bit data, 1 stop bit
MODBUS RTU slave over serial line
RJ-45
1 – 32
≤ 1200 m
19200 baud
Even
1
789-622
RJ-45-Connector Pin Assignment:
Pin
1
2
Function
RS-485
Uart:
Ub
half duplex
Communication settings requiredfor
transducer:
3
n.c.
4
A (Data+)
5
B (Data-)
6
n.c.
Baud rate: 19200 bd
Data bits: 8
Parity: even
Stop bits: 1
7
GND
8
Communication Description:
MODBUS Function
Read Holding Registers (0x03)
Address of Measured Value
0x0004
Data Type Measurement
Integer
▯ = ON
DIP Switch Adjustability
Adress
Terminating resistor
DIP Switch
2
3
4
5
6
1
150 Ohm
2
●
3
●
4
●
5
●
6
●
7
●
●
●
●
8
●
10
●
11
●
12
●
13
●
●
14
●
●
15
●
●
●
●
●
●
16
●
●
9
●
●
●
●
●
●
17
●
18
●
19
●
20
●
21
●
●
22
●
●
23
●
●
●
24
●
●
●
25
●
●
26
●
●
27
●
●
●
●
●
●
●
●
●
●
●
28
●
●
29
●
●
●
●
30
●
●
●
31
●
●
●
●
32
●
●
●
●
●
●
●
DIP Switch 1
NOTICE:
Only set the MODBUS address in the
OFF state.
●
INTERFACE ELECTRONIC
45
789-652
1
3-Channel Rogowski Signal Conditioner
INTERFACE ELECTRONIC
46
IL3
U3
GND
OUT (I)
U2
GND
IN (U)
U1
POWER
Item No.
Pack.
Unit
Technical Data
3-Channel Rogowski Signal Conditioner
789-652
1
General specifications:
Supply voltage range
max. power consumption
Operational indication
Degree of protection
Phase error
Max. operating frequency
Linearity
Temperature coefficient
Transmission error
Response threshold
Environmental requirements:
Ambient operating temperature
Storage temperature
Safety and protection:
Test voltage (input/output/supply)
Connection and type of mounting:
Wire connection
Cross sections
Stripped lengths
Dimensions and weight:
Dimensions (mm) W x H x L
Item No.
Rogowski Coils RT500
0758-0950/
0000-0500
750-493
3-Phase Power Measurement Module (1 A)
Pack.
Unit
1
1
Technical Data
Input:
Input signal
Sensitivity
Output:
Output signal
Rated output current
Overcurrent
Load impedance
3 x RT500 (500 A)
10.05 mV
50 Hz sinus
3 x 100 mA AC
100 mA AC (for direct connection to
750-493 Phase Power Measurement
Module)
750 A (max. 150 mA per output)
≤5Ω
24 V
0V
The 750-493 3-Phase Power Measurement Module within the WAGO-I/OSYSTEM measures electrical data (e.g., voltages, currents, effective power and
energy consumption) in a three-phase supply network. Thus, the user is always
able to determine the load condition (imbalance, capacitive components), to
optimize consumption and protect machines or systems from damage and
breakdowns. Easy installation of Rogowski coils also allows existing systems to
be retrofitted without process interruption.
Description
Accessories
IL1
IN
GND
Short description:
The 789-652 Rogowski Signal Conditioner acquires 5–500A alternating
currents in a three-phase system.
The magnetic field produced around each conductor is sensed via three
non-contact Rogowski coils and provided as a proportional voltage signal to
the signal conditioner. The 789-652 adjusts the phase of each of the three
voltage signals, converting them into 100mA alternating current signals. These
are then transmitted to the 750-493 3-Phase Power Measurement Module.
IL2
Weight
Standards and approvals:
Conformity marking
r UL 508
16.8 – 32 V
4000 mW
LED, green
IP20
< 1°
300 Hz (phase accuracy at 50 Hz only)
≤ 0.1 %
≤ 0.1 %/K
< 1.1 %
2A
-25 °C ... +70 °C
-40 °C ... +85 °C
2.5 kV AC, 50 Hz, 1 Min.
CAGE CLAMP®
0.08 mm² ... 2.5 mm² / AWG 28 ... 12
5 ... 6 mm / 0.22 in
70 x 55 x 90
Height from upper-edge of DIN 35 rail
105 g
1
(pending)
INTERFACE ELECTRONIC
1
47
770-629/130-000
1
WINSTA® Sunblind Box
INTERFACE ELECTRONIC
48
Bus
ON
DI P
1 2 3 4 5 6
S2
DIP-Modul
S6
4
NC
3
NC
S7
2
A
GND
1
B
NC
N
N
2
ON
DI P
1 2 3 4 5 6
DIP-Modul
S5
S3
1
S4
Central
Jumper
S1
M3
M
2
1
1
2
M
N
M1
N
M4
N
M
2
1
1
2
M
N
N
N
L
L
M2
230 V
N
The WINSTA® Sunblind Box is a decentralized, stand-alone unit that controls
4 sunblind motors operated via standard switches. Output group configuration,
operating time and "slat/sunblind" mode selection are performed via DIP
switch.
Operating the boxes in a network configuration provides extended
functionality:
N
1. The sunblinds for all connected boxes are moved into the upper or end position via a central 24V control line. Either a weather station, a timer or a central
switch enables this functionality.
2. The boxes also connect to a serial bus, allowing a higher-level control system
to access up to 16 boxes connected to one bus segment. This operating mode
addresses both individual channels and groups of boxes.
The "bus failure/voltage monitoring" function also enables the sun blinds to be
moved to their top position on a bus failure or, for example, on a wire break.
Description
Item No.
Pack.
Unit
Technical Data
WINSTA sunblind box
770-629/130-000
1
Supply:
Voltage supply
Voltage range
Fuse protection
®
Connection type (1)
Accessories
Item No.
750 Series WAGO-I/O-Module
RS-485 / configurable
750-653/003-000
Connector set for WINSTA® sunblind box
770-5001/100-000
The set includes:
1 x socket with strain relief housing, 3-pole (item no. 770-103)
4 x plug with strain relief housing, 4-pole (item no. 770-114)
1 x socket without strain relief housing, 4-pole (item no. 770-244)
1 x strain relief housing, 4-pole (item no. 770-514)
4 x female connector, 3-pole (item no. 734-103)
4 x snap-on type strain relief housing (item no. 734-603)
h-distribution connector, bi-directional,
plug - socket / socket
770-633
Configuration:
Configuration
Inputs:
Number of inputs
Signal voltage
Transmission medium
Connection type (2)
230 VAC, 50 Hz ... 60 Hz
± 10 %
Internal, glass cartridge fuse,
accessible from outside
Socket with strain relief housing, 3-pole
(item no. 770-103)
via DIP switch/header
4 switch inputs for on-site switches
12 V
Control line:
J-Y (St) Y 2x2x0.6 mm2,
max. 10 m
Female connector, 3-pole
(item no. 734-103)
Snap-on type strain relief housing
1
145
6.9
6.2
Connection type (2)
Connection type (4)
150
190
200
Connection type (3)
Connection type (3)
Connection type (3)
Connection type (3)
30
Connection type (1)
Technical Data
Motors:
No. of outputs
Switching voltage
Switching current
Switching power
Connection type (3)
Control:
Operating mode
Connection type (4)
Bus control:
Data transmission
Baud rate
Bus interface
Transmission medium
Central control via 24V signal:
Operating voltage
Current consumption (internal)
Transmission medium
Technical Data
4 power outputs
(up, down, locked against each other)
AC 230 V
1 x 6 A at 230 V AC
300 W (AC3)
Plug with strain relief housing, 4-pole
(item no. 770-114)
Bus control or
central control via 24VDC signal
Socket with strain relief housing, 4-pole
(item no. 770-244)
Strain relief housing, 4-pole
(item no. 770-514)
Serial, master-slave procedure
9,600 baud
Serial interface RS-485,
max. 16 slaves
Shielded bus cable:
YCYM 2x2x0.8 mm2,
max. 800 m
24 V DC +10 % / -50 %
max. 5 mA
Shielded bus cable:
YCYM 2x2x0.8 mm2
Standards and approvals:
Conformity marking
General specifications:
Ambient operating temperature
Storage temperature
Dimensions (mm) W x H x L
Weight
Type of mounting
Assembly
Mounting position
Degree of protection
Degree of pollution
Housing material
1
-5 °C ... +55 °C
-25 °C ... +70 °C
200 x 145 x 30
approx. 450 g
Wall screw adapter
Interior area,
e.g., intermediate floors, suspended ceiling
any
IP20
2
Polyamide (PA 6.6),
flammability class UL94 V-0
INTERFACE ELECTRONIC
49
857-402
Universal Isolation Amplifier
Configuration via:
INTERFACE ELECTRONIC
50
JUMPFLEX® Transducers
<_________ 96 mm/3.76 in _________>
DIP Switches
____________
<_________ 94 mm/3.68 in _________>
Short description:
The universal 857-402 Isolation Amplifier converts unipolar and bipolar standard signals
and amplifies, filters and electrically isolates analog standard signals.
Characteristics:
• Overload protection of current input using reversible fuse
• Zero/span adjustment across the entire measuring range (slide switch)
• Calibrated scale switching for all 456 signals
• Standard analog unipolar and bipolar signals, input/output
• Switchable max. operating frequency
• Clipping capability allows analog standard signal limitation to upper range values.
• Safe 3-way isolation with 2.5kV test voltage to EN 61140
Technical Data
Configuration:
Configuration
Input:
Input signal
Input resistance
Output:
Output signal
Load impedance
Push/Slide Switch
U+ 1
I+ 2
I+ 3
_>
_>
3
OUT
U; I
IN
U; I
I-/U- 4
5 OUT+
6 OUT-
7 Us+
POWER
8 GND 3
6 mm/0.23 in
Description
Item No.
Pack.
Unit
JUMPFLEX® Transducer, for DIN 35 rail
Universal isolation amplifier
857-402
1
Technical Data
DIP switches, push/slide switch
Voltage:
± 60 mV, 0 … 60 mV, ± 100 mV,
0 … 100 mV, ± 150 mV, 0 … 150 mV,
± 300 mV, 0 … 300 mV, ± 500 mV,
0 … 500 mV, ± 1 V, 0 … 1 V, ± 5 V,
0 ... 5 V, 1 ... 5 V, ± 10 V, 0 ... 10 V,
2 ... 10 V, ± 100 V, 0 … 100 V, ± 200 V,
0 … 200 V
Current:
± 0,3 mA, 0 ... 0,3 mA, ± 1 mA, 0 ... 1 mA,
± 5 mA, 0 ... 5 mA, ± 10 mA, 0 ... 10 mA,
2 ... 10 mA, ± 20 mA, 0 ... 20 mA,
4 ... 20 mA, ± 50 mA, 0 ... 50 mA,
± 100 mA, 0 ... 100 mA
approx. 1 MΩ (U input)
≤ 5 mA approx. 100 Ω;
> 5 mA approx. 10 Ω (I input)
Voltage:
± 5 V, 0 ... 5 V, 1 ... 5 V,
± 10 V, 0 ... 10 V, 2 ... 10 V
Current:
± 10 mA, 0 ... 10 mA, 2 ... 10 mA,
± 20 mA, 0 ... 20 mA, 4 ... 20 mA
≤ 600 Ω (I output)
≥ 1 kΩ (U output)
General specifications:
Voltage supply VN
Supply voltage range
Current consumption at 24 V DC
Max. operating frequency
Response time (T10-90)
Transmission error
Temperature coefficient
Zero/span adjustment
Environmental requirements:
Ambient operating temperature
Storage temperature
Safety and protection:
Test voltage (input/output/supply)
Connection and type of mounting:
Wire connection
Cross sections
Strip lengths
Dimensions and weight:
Dimensions (mm) W x H x L
Weight
Standards and approvals:
Conformity marking
r UL 508
r ANSI/ISA 12.12.01
Shipbuilding
Accessories
24 V DC
16.8 V ... 31.2 V
< 40 mA
100 Hz / > 5 kHz
(switchable via DIP switch)
< 3.5 ms / < 100 μs
≤ 0.08 % of upper range value
≤ 0.01 % /K
Adjustable via push/slide switch
-25 °C ... +70 °C
-40 °C ... +85 °C
2.5 kV AC, 50 Hz, 1 min.
CAGE CLAMP® S
solid:
0.08 mm² ... 2.5 mm² / AWG 28 ... 14
fine-stranded:
0.34 mm² ... 2.5 mm² / AWG 22 ... 14
9 ... 10 mm / 0.37 in
6 x 96 x 94
Height from upper-edge of DIN 35 rail
54.3 g
1
(pending)
g (pending)
see Full Line Catalog 2010/2011,
Interface Modules
3
51
857--402
▯ = ON
DIP Switch S1
DIP Switch S1
Input Signal Ranges
1
2
3
4
5
Zero/Span Adjustment
6
7
8
●
2
3
●
●
≥ 5 kHz
●
●
± 60 mV
●
●
0 … 100 mV
●
●
± 100 mV
●
●
●
0 … 150 mV
●
●
●
± 150 mV
●
●
●
●
●
●
●
●
0 … 60 mV
●
●
●
●
●
●
●
●
●
●
Input Signal Ranges
< 100 Hz
Default setting*
●
Max. Operating
Frequency
Inactive
●
Active
●
1
0 … 300 mV
●
●
●
●
●
●
●
●
●
●
●
●
●
●
●
●
●
●
●
●
●
●
●
●
●
●
●
●
●
●
●
●
●
0…1V
●
±1V
●
0…5V
●
±5V
●
●
0 … 10 V
●
●
± 10 V
●
●
●
0 ... 50 V
●
●
●
●
± 50 V
0 … 100 V
●
± 100 V
0 … 200 V
●
± 200 V
DIP Switch S2
Output Signal Ranges
2
3
4
Reserve
5
6
Clipping
7
0 … 10 V
●
●
●
●
●
active
(limiting response)
± 10 V
0…5V
●
●
●
●
●
●
●
●
●
●
±5V
1…5V
0 … 20 mA
●
●
± 20 mA
4 … 20 mA
●
0 … 10 mA
●
●
8
2 … 10 V
●
●
●
± 10 mA
2 … 10 mA
*Default setting
Input
± 10 V
Output
± 10 V
Max. operating frequency
> 5 kHz
Rocker Switch Lock
inactive
(analog response)
Default setting*
●
●
± 500 mV
More information on measurement range setting is available in 857-402 instruction leaflet.
1
●
0 … 500 mV
●
●
*The input and output range DIP switches must be readjusted when changing the default setting.
switched off
●
switched on
6
0 … 0.3 mA
●
●
5
●
± 300 mV
●
●
4
± 0.3 mA
0 … 1 mA
●
± 1 mA
0 … 5 mA
●
± 5mA
0 … 10 mA
●
± 10 mA
0 … 20 mA
●
●
●
± 20 mA
0 … 50 mA
●
●
± 50 mA
0 … 100 mA
●
●
± 100 mA
1…5V
●
2 … 10 V
●
4 … 20 mA
2 … 10 mA
INTERFACE ELECTRONIC
DIP Switch Adjustability
857-411, 857-412, 857-413, 857-414, 857-415, 857-416
3
Isolation amplifiers, fixed setting for voltage or current signals
<_________ 96 mm/3.76 in _________>
INTERFACE ELECTRONIC
52
JUMPFLEX® Transducers
<_________ 94 mm/3.68 in _________>
Short description:
The pre-configured isolation amplifiers convert, amplify, filter and electrically
isolate standard analog signals.
Characteristics:
• Input/Output: current/voltage signal
• Safe 3-way isolation with 2.5kV test voltage to EN 61140
Technical Data
Input:
Input signal
Input resistance
Output:
Output signal
Load impedance
General specifications:
Voltage supply VN
Supply voltage range
Current consumption at 24 V DC
Max. operating frequency
Response time (T10-90)
Transmission error
Temperature coefficient
5 OUT+
IN
OUT
GND 1 2
6 GND 2
Us+ 3
7 Us+
POWER
_>
_>
____________
IN+ 1
GND 3 4
8 GND 3
6 mm/0.23 in
Output signal
Item No.
Pack.
Unit
JUMPFLEX® Transducer, for DIN 35 rail
Isolation amplifier 0(4) ... 20 mA
0(4) ... 20 mA
Isolation amplifier 0(2) ... 10 V
0(2) ... 10 V
Isolation amplifier 0 ... 10 V
0 ... 20 mA
Isolation amplifier 0 ... 10 V
4 ... 20 mA
Isolation amplifier 0 ... 20 mA
0 ... 10 V
Isolation amplifier 4 ... 20 mA
0 ... 10 V
857-411
857-412
857-413
857-414
857-415
857-416
1
1
1
1
1
1
Description
Input signal
Technical Data
857-411: 0(4) ... 20 mA
857-412: 0(2) ... 10 V
857-413: 0 ... 10 V
857-414: 0 ... 10 V
857-415: 0 ... 20 mA
857-416: 4 ... 20 mA
≤ 50 Ω (I input)
≥ 100 kΩ (U input)
857-411: 0(4) ... 20 mA
857-412: 0(2) ... 10 V
857-413: 0 ... 20 mA
857-414: 4 ... 20 mA
857-415: 0 ... 10 V
857-416: 0 ... 10 V
≤ 600 Ω (I output)
≥ 2 kΩ (U output)
24 V DC
16.8 V ... 31.2 V
< 25 mA
100 Hz
< 3.5 ms
≤ 0.1 % of upper range value
≤ 0.01 % /K
Environmental requirements:
Ambient operating temperature
Storage temperature
Safety and protection:
Test voltage (input/output/supply)
Connection and type of mounting:
Wire connection
Cross sections
Strip lengths
Dimensions and weight:
Dimensions (mm) W x H x L
Weight
Standards and approvals:
Conformity marking
r UL 508
r ANSI/ISA 12.12.01
Shipbuilding
Accessories
-25 °C ... +70 °C
-40 °C ... +85 °C
2.5 kV AC, 50 Hz, 1 min
CAGE CLAMP® S
solid:
0.08 mm² ... 2.5 mm² / AWG 28 ... 14
fine-stranded:
0.34 mm² ... 2.5 mm² / AWG 22 ... 14
9 ... 10 mm / 0.37 in
6 x 96 x 94
Height from upper-edge of DIN 35 rail
49.2 g
1
Class I, Div. 2, Grp. ABCD, T4
g
see Full Line Catalog 2010/2011,
Interface Modules
INTERFACE ELECTRONIC
3
53
857-450
3
Loop-Powered Isolation Amplifier
Configuration via:
INTERFACE ELECTRONIC
54
JUMPFLEX® Transducers
<_________ 96 mm/3.76 in _________>
DIP Switches
<_________ 94 mm/3.68 in _________>
Short description:
The 857-450 Loop-Powered Isolation Amplifier converts analog, unipolar and bipolar,
standard signals. It is also designed to amplify, filter and electrically isolate standard
analog signals.
Characteristics:
• No additional supply voltage required
• Zero/span adjustment
• Analog, unipolar and bipolar, standard signals at input
• Calibrated scale switching
• Switchable max. operating frequency
• Safe 2-way isolation with 2.5 kV test voltage to EN 61140
Technical Data
Configuration:
Configuration
Input:
Input signal
Input resistance
Output:
Output signal
Load impedance
Overload capacity
General specifications:
Supply voltage
Max. operating frequency
Response time (T10-90)
Transmission error
Temperature coefficient
Zero/span adjustment
U -- 2
I+ 3
IN
U, I
OUT 5 Us+
4-20 mA
6 OUT 1
7 N.C.
N.C.
_>
_>
____________
U+ 1
I -- 4
8 N.C.
6 mm/0.23 in
Description
Item No.
Pack.
Unit
JUMPFLEX® Transducer, for DIN 35 rail
Loop-Powered Isolation Amplifier
857-450
1
Technical Data
DIP switch
Current:
± 5 mA, 0 ... 5 mA,
± 10 mA, 0 ... 10 mA, 2 ... 10 mA,
± 20 mA, 0 ... 20 mA, 4 ... 20 mA
Voltage:
± 1 V, 0 … 1 V,
± 5 V, 0 ... 5 V, 1 ... 5 V,
± 10 V, 0 ... 10 V, 2 ... 10 V,
± 20 V, ± 2 V, 0 … 2 V
approx. 1 MΩ (U input)
approx. 50 Ω (I input)
4 ... 20 mA
≤ 600 Ω
30 V / 50 mA
8 ... 30 V, power is derived from the output
circuit
100 Hz / 30 Hz
(switchable via DIP switch)
3.5 ms
≤ 0.1 % of upper range value
≤ 0.01 % /K
± 5 % of upper range value
Environmental requirements:
Ambient operating temperature
Storage temperature
Safety and protection:
Test voltage (input/output/supply)
Connection and type of mounting:
Wire connection
Cross sections
Strip lengths
Dimensions and weight:
Dimensions (mm) W x H x L
Weight
Standards and approvals:
Conformity marking
r UL 508
r ANSI/ISA 12.12.01
Shipbuilding
Accessories
-25 °C ... +70 °C
-40 °C ... +85 °C
2.5 kV AC, 50 Hz, 1 min.
CAGE CLAMP® S
solid:
0.08 mm² ... 2.5 mm² / AWG 28 ... 12
fine-stranded:
0.34 mm² ... 2.5 mm² / AWG 22 ... 14
9 ... 10 mm / 0.37 in
6 x 96 x 94
Height from upper-edge of DIN 35 rail
5 g
1
(pending)
g (pending)
see Full Line Catalog 2010/2011,
Interface Modules
3
55
DIP Switch Adjustability
857-450
INTERFACE ELECTRONIC
▯ = ON
DIP switch (6 positions)
Input Signal
1
2
3
4
Max. Operating
Frequency
Output Signal
5
6
100 Hz
4 ... 20 mA
●
●
●
●
●
●
●
0 ... 20 mA
●
●
●
●
30 Hz
± 20 mA
2 … 10 mA
●
●
0 ... 10 mA
●
●
Current
●
± 10 mA
0 ... 5 mA
●
●
●
●
●
●
●
●
●
●
± 5 mA
0 ... 20 V
●
± 20 V
4 ... 20 mA
2 ... 10 V
●
●
●
●
0 ... 10 V
●
± 10 V
1 ... 5 V
●
●
●
●
0 ... 5 V
●
●
Voltage
●
±5V
0 ... 2 V
●
●
●
●
±2V
0 ... 1 V
●
±1V
Default setting
Input
4 ... 20 mA
Output
4 ... 20 mA
Max. operating frequency
100 Hz
Wiring Material
Input card, active
e.g. 0 ... 10 V
+
8 ... 30 V
_
4 ... 20 mA
RLoad impedance
PLC
e.g. 787-1002
230 V AC
8 ... 30 V
+
Input card, passive
_
RLoad impedance
e.g. 0 ... 10 mA
4 ... 20 mA
PLC
857-500
3
Frequency transducer 0.1 Hz ... 120 kHz
INTERFACE ELECTRONIC
56
JUMPFLEX® Transducers
Configuration via:
<_________ 96 mm/3.76 in _________>
DIP Switches
Short description:
The 857-500 Frequency Transducer collects 0.1–120kHz signals from
NAMUR, NPN or PNP sensors and converts them into analog standard signals.
Characteristics:
• Signal acquisition from NAMUR, NPN or PNP sensors
• Calibrated scale switching
• Safe 3-way isolation with 2.5kV test voltage to EN 61140
Technical Data
Configuration:
Configuration
Input:
Sensor types
fIN 2
GND 1 3
_>
_>
____________
<_________ 94 mm/3.68 in _________>
+8,2 V(Namur) 1
IN
f
NPN/PNP 4
OUT 5 OUT+
U, I
6 GND 2
7 Us+
POWER
8 GND 3
6 mm/0.23 in
Description
Item No.
Pack.
Unit
JUMPFLEX® Transducer, for DIN 35 rail
Frequency transducer
857-500
1
Technical Data
DIP switch
-Frequency generators
-NAMUR sensors
-NPN/PNP transistor outputs
without pull-up or pull-down resistor
-mech. contact (dry contact)
Input for frequency generators or NPN/PNP transistor outputs with pull-up or
pull-down resistor
Frequency range
0.1 Hz ... 120 kHz
Signal level
1.5 V, 10 V, 20 V (switchable)
Max. input signal
± DC 31.2 V
Pulse length
≥ 1 μs
Signal form
Any
Coupling
AC/DC (AC above 10 Hz)
(adjustable)
Min. measuring span
10 Hz
Input resistance
10 kΩ
Input for NAMUR sensors per DIN EN 50227
Sensor supply
DC 8.2 V
Signal current (0)
≤ 1.2 mA
Signal current (1)
≥ 2.1 mA
Hysteresis
0.45 mA
Input resistance
< 600 Ω
Frequency range
0.1 Hz ... 1 kHz
Pulse length
≥ 500 μs
Min. measuring span
10 Hz
Short-circuit current
≤ 14 mA
Short-circuit monitoring
> 4.7 mA
Wire break monitoring
< 0.2 mA
Input for NPN/PNP transistor outputs without pull-up or pull-down resistor or
mech. contact (dry contact)
Frequency range
0.1 Hz ... 20 kHz
Pulse length
≥ 25 μs
Min. measuring span
10 Hz
Open-circuit voltage
5 VDC
NPN_Residual voltage
< 1.5 V
PNP Switching voltage
> 7.5 V + residual voltage UCE sat
3
INTERFACE ELECTRONIC
57
Technical Data
Output:
Output signal
Load impedance
Conversion time
General specifications:
Voltage supply VN
Supply voltage range
Current consumption at 24 V DC
Transmission error
Temperature coefficient
General Specifications
Voltage:
0 ... 5 V, 1 ... 5 V, 0 ... 10 V, 2 ... 10 V
Current:
0 ... 10 mA, 2 ... 10 mA,
0 ... 20 mA, 4 ... 20 mA
≤ 600 Ω (I output)
≥ 2 kΩ (U output)
Gate time measurement method
(> 400 Hz): < 20 ms
Pulse time measurement method
(< 400 Hz): < 200 μs + TCycle duration
24 V DC
16.8 V ... 31.2 V
< 40 mA
≤ 0.1 % of upper range value
≤ 0.01 % /K
Environmental requirements:
Ambient operating temperature
Storage temperature
Safety and protection:
Test voltage (input/output/supply)
Connection and type of mounting:
Wire connection
Cross sections
Strip lengths
Dimensions and weight:
Dimensions (mm) W x H x L
Weight
Standards and approvals:
Conformity marking
r UL 508
r ANSI/ISA 12.12.01
Shipbuilding
Accessories
-25 °C ... +70 °C
-40 °C ... +85 °C
2.5 kV AC, 50 Hz, 1 min.
CAGE CLAMP® S
solid:
0.08 mm² ... 2.5 mm² / AWG 28 ... 14
fine-stranded:
0.34 mm² ... 2.5 mm² / AWG 22 ... 14
9 ... 10 mm / 0.37 in
6 x 96 x 94
Height from upper-edge of DIN 35 rail
38.7 g
1
(pending)
g (pending)
see Full Line Catalog 2010/2011,
Interface Modules
Refer to following pages for DIP Switch Table and Pin Assignments.
3
58
INTERFACE ELECTRONIC
DIP Switch Adjustability
857-500
▯ = ON
DIP Switch S1
Source Input
1
2
3
Frequency generator or NPN/PNP transistor
outputs with pull-up or pull-down resistor
●
NAMUR
●
Operation with disturbed frequency signals for acceptable signal level
(applies only to fIN input)
Coupling
●
4
AC/DC
High
Low
AC (without DC), see Figure 1
> 1.5 V
< 0.4 V
> 10 V
<8V
NPN/PNP transistor outputs without pull-up or
pull-down resistor input
Dry Contact
●
●
DIP Switch S1
7
8
9 10
●
U
0.1
●
1
100
●
200
●
200
●
300
●
300 ●
●
●
400
●
●
400
●
●
500 ●
●
●
500
●
600
●
●
700 ●
●
700
●
●
800
●
●
800
●
●
900 ●
●
●
900
●
●
1000
●
●
1000
AC/DC
600
●
●
2000 ●
●
●
2000
●
●
●
3000
●
●
●
3000
●
●
●
4000 ●
●
●
●
AC
t
Figure 1: Coupling
4000
●
5000
●
5000
●
6000 ●
●
6000
Default Setting
●
●
7000
●
●
7000
Input:
●
●
8000 ●
●
●
8000
Input source
●
●
9000
●
●
9000
Frequency generator/transistor output
with pull-up or pull-down resistor
●
●
10000 ●
●
●
10000
Coupling
AC/DC
●
●
●
20000
●
●
●
20000
Signal level
> 1.5 V
●
●
●
●
100 Hz
●
30000 ●
●
30000
Start value
●
●
40000
●
●
40000
End value
1000 Hz
●
●
50000 ●
●
●
50000
Measuring technique
Gate time measurement method
●
●
●
60000
●
●
●
60000
Output:
●
●
●
70000 ●
●
●
●
70000
Output signal
Current
●
●
●
80000
●
●
●
80000
Start value
0 mA
●
●
●
●
●
●
90000
End value
20 mA
●
●
●
●
100000
●
●
●
●
100000
Measuring range underflow
0 mA
●
●
●
●
120000 ●
●
●
●
●
120000
Measuring range overflow
20.5 mA
●
●
< 0.4 V
5
●
●
●
4
1
●
●
3
100 ●
●
●
2
●
●
●
1
●
●
<16 V
● > 1.5 V
Frequency/Hz
0.1 ●
●
●
Input
End Value
Frequency/Hz
●
●
● > 20 V
DIP Switch S2
Input
Start Value
6
5
90000 ●
DIP Switch S2
Output Signal
6
7
8
9
Measuring Range
Overflow
Wire Break
Short Circuit
Lower limit of output range*
-5 %
Upper limit of output range*
+2.5 %
Upper limit of output range*
5%
Lower limit of output range *
-12.5 %
Lower limit of output range
Upper limit of output range
+2.5 %
Upper limit of output range
5%
Lower limit of output range
▯
Lower limit of output range
Upper limit of output range
Upper limit of output range
5%
Upper limit of output range
5%
▯
Lower limit of output range
Upper limit of output range
Lower limit of output range
Lower limit of output range
0 … 20 mA
▯
4 … 20 mA
▯ 0 … 10 mA
▯
▯
▯
▯
0 … 10 V
▯
▯
▯
▯ 2 … 10 mA
2 … 10 V
▯ 0…5V
▯
▯ 1…5V
▯
Only for NAMUR Sensors
Measuring Range
Underflow
10
3
857-500, Wiring Material
2-Conductor DC NAMUR Sensor
2-Conductor DC (Mechanical Contact)
BN
BU
OUT
BN
BU
IN
OUT
24 V
24 V
IN
POWER
POWER
0V
0V
NPN Transistor Output
NPN Transistor Output with Pull-Up Resistor
BN
OUT
BN
BK
−
+
BK
IN
BU
−
BU
OUT
+
R
24 V
24 V
POWER
IN
POWER
0V
0V
PNP Transistor Output with Pull-Down Resistor
PNP Transistor Output
BN
OUT
BK
+
BK
R
BU
−
BU
24 V
−
IN
24 V
POWER
POWER
IN
OUT
+
BN
0V
Frequency Generator
OUT
IN
24 V
POWER
0V
0V
INTERFACE ELECTRONIC
59
857-550
3
Current transducer AC/DC 0 ... 1 A, 0 ... 5 A
Configuration via:
INTERFACE ELECTRONIC
60
JUMPFLEX® Transducers
<_________ 96 mm/3.76 in _________>
DIP Switches
<_________ 94 mm/3.68 in _________>
Short description:
The 857-550 Current Transducer measures 0–1A and 0–5A AC/DC currents
and converts the input signal to a standard analog signal at the output.
Characteristics:
• True RMS measurement or arithmetic mean value
• Switchable filter function
• Switching between measuring ranges is calibrated
• Safe 3-way isolation with 2.5kV test voltage to EN 61140
• Extremely fast response times
• Measuring range overflow indication
Technical Data
Configuration:
Configuration
Input:
Input signal
Input resistance
Frequency range
Output:
Output signal
Load impedance
Filter (T10-90)
Output - Digital
Max. switching voltage
Max. continuous current
General specifications:
Measuring procedure
Response time
Max. response time
Voltage supply VN
Supply voltage range
Current consumption at 24 V DC
Min. measuring span
Transmission error
Temperature coefficient
_>
_>
____________
IN 1A
(GND 1)
IN 5A
(GND 1)
DO
(GND 3)
GND 1
5 OUT+
1
IN
OUT
6 GND 2
2
3 DO
4
7 Us+
POWER
8 GND 3
6 mm/0.23 in
Description
Item No.
Pack.
Unit
JUMPFLEX® Transducer, for DIN 35 rail
Current transducer
857-550
1
Technical Data
DIP switch
0 ... 1 A AC/DC; 0 ... 5 A AC/DC
10 mΩ (5 A); 47 mΩ (1 A)
16 Hz ... 150 Hz
Voltage:
0 ... 5 V, 1 ... 5 V, 0 ... 10 V, 2 ... 10 V
Current:
0 ... 10 mA, 2 ... 10 mA,
0 ... 20 mA, 4 ... 20 mA
≤ 600 Ω (I output)*
≥ 2 kΩ (U output)
*Temperature range restrictions
may occur.
260 ms (DC), 600 ms (AC 50 Hz)
Supply voltage applied
500 mA (up to 60 °C)
100 mA (60 °C ... 70 °C)
Arithmetic mean value
True RMS measurement
1.5 ms + signal cycle duration
60 ms
DC 24 V
16.8 V ... 31.2 V
< 40 mA
2 mA ... 1 A; 4 mA ... 5 A
≤ 0.1 % typ. (≤ 0.2 % max.)
≤ 0.01 % /K
Environmental requirements:
Ambient operating temperature
Storage temperature
Safety and protection:
Test voltage (input/output/supply)
Connection and type of mounting:
Wire connection
Cross sections
Strip lengths
Dimensions and weight:
Dimensions (mm) W x H x L
Weight
Standards and approvals:
Conformity marking
r UL 508
r ANSI/ISA 12.12.01
Shipbuilding
Accessories
-25 °C ... +70 °C
-40 °C ... +85 °C
2.5 kV AC, 50 Hz, 1 min.
CAGE CLAMP® S
solid:
0.08 mm² ... 2.5 mm² / AWG 28 ... 14
fine-stranded:
0.34 mm² ... 2.5 mm² / AWG 22 ... 14
9 ... 10 mm / 0.37 in
6 x 96 x 94
Height from upper-edge of DIN 35 rail
50 g
1
(pending)
g (pending)
see Full Line Catalog 2010/2011,
Interface Modules
HW/SW 03/02
3
61
857-550
▯ = ON
DIP Switch S1
Input Signal
Measuring Method
1
2
5A
Filter
3
Mean square value
● 1A
Output Signal
● Arithmetic mean value
4
5
6
off
0 ... 20 mA
● active
●
4 ... 20 mA
●
●
0 ... 10 V
●
2 ... 10 V
●
●
●
●
●
0 ... 10 mA
●
2 ... 10 mA
●
0 ... 5 V
●
1 ... 5 V
DIP Switch S1
7
Measuring Range Underflow
Measuring Range Overflow
Overcurrent
(Input Signal - End Value + 20%)
Lower limit of measuring range - 5 %*
Upper limit of measuring range + 2.5 %*
Upper limit of measuring range + 5 %*
Lower limit of measuring range
Upper limit of measuring range + 2.5 %
Upper limit of measuring range + 5 %
●
Lower limit of measuring range
Upper limit of measuring range
Lower limit of measuring range
●
Lower limit of measuring range
Upper limit of measuring range
Upper limit of measuring range
8
●
●
9 10
Digit Output DO
Signaling
●
DO Us+ switching
●
DO GND switching
DO not active
●
*
acc. to NAMUR NE 43
Digital Output DO/Signaling
The digital output (DO) signals error messages and can be configured as follows: 24 V … 0 V/0 V … 24 V.
In order to increase the switching current of the DO, the latter may be expanded by a relay. Thanks to the contour uniformity of Series 857, for example, a 857-304
Relay can be snapped in next to it. This output can be quickly and easily expanded to a switching current of 6A by simply using an adjacent jumper (859-402).
Default Setting
All DIP switches are in “OFF“ position for delivery.
Input
Input Signal
0 ... 5 A
Measuring Method
Mean square value
Output
Output Signal
0 ... 20 mA
Measuring Range Underflow
0 mA
Measuring Range Overflow
20.5 mA
Overcurrent
21 mA
Digital Output DO
not active
Filter
not active
Application example:
Current
transformer
250 A/ 1 A
PLC/
LED indication
L1
LED indication
24 V/500 mA
e.g. 787-1002
16.8 ... 31.2 V
AC 230 V
INTERFACE ELECTRONIC
DIP Switch Adjustability
857-552
3
Rogowski Transducer
Configuration via:
INTERFACE ELECTRONIC
62
JUMPFLEX® Transducers
<_________ 96 mm/3.76 in _________>
DIP Switches
<_________ 94 mm/3.68 in _________>
Short description:
The Rogowski transducer records RMS values from alternating currents via a Rogowski
coil, converting the input signal into a standard analog signal on the output side.
Characteristics:
• Supports different types of Rogowski coils
• True RMS measurement (TRMS)
• Configurable output signal
• Configuration via DIP switch
• Safe 3-way isolation with 2.5 kV test voltage to EN 61140
• No current bar interruption during installation
• Measuring range overflow indication
Technical Data
Configuration:
Configuration
Input:
Input signal
Frequency range
Output:
Output signal
Overcurrent
Overrange / measuring range
Load impedance
Measuring procedure
Filter (T10-90)
Output - Digital
Max. switching voltage
Max. continuous current
General specifications:
Resolution
Measuring procedure
Response time
Voltage supply VN
Max. operating frequency
Response time (T10-90)
_>
_>
____________
RC1+
(GND 1)
RC2+
(GND 1)
DO
(GND 3)
GND 1
5 OUT+
1
IN
OUT
6 GND 2
2
3 DO
4
7 Us+
POWER
8 GND 3
6 mm/0.23 in
Description
Item No.
Pack.
Unit
Height from upper-edge of DIN 35 rail
Rogowski Transducer
857-552
1
Technical Data
DIP switch
RC1 500 A: Sensitivity 10.05 mV
RC2A 2000 A: Sensitivity 40.2 mV
RC2B: Sensitivity 100 mV
50/60 Hz sinusoidal and distorted
sinusoidal signals (e.g. leading edge and
trailing edge)
16 Hz ... 100 Hz
Voltage:
0 ... 5 V, 1 ... 5 V, 0 ... 10 V, 2 ... 10 V
Current:
0 ... 10 mA, 2 ... 10 mA,
0 ... 20 mA, 4 ... 20 mA
0 % or +5 % (e. g. 10.5 V/21 mA)
0 % or +2.5 %
Current ≤ 600 Ω, Voltage ≥ 1000 Ω
True RMS measurement
600 ms
Supply voltage applied
500 mA
500A measuring range: 250 mA,
2000A measuring range: 1000 mA
True RMS measurement
1.5 ms + signal cycle duration
24 V DC
< 1 kHz
max. 60 ms
General specifications:
Linearity
Temperature coefficient
Measurement error
Cable length
Environmental requirements:
Ambient operating temperature
Storage temperature
Safety and protection:
Test voltage (input/output/supply)
Connection and type of mounting:
Wire connection
Cross sections
Strip lengths
Dimensions and weight:
Dimensions (mm) W x H x L
Weight
Standards and approvals:
Conformity marking
r UL 508
r ANSI/ISA 12.12.01
Shipbuilding
Accessories
≤ 0,1 %
≤ 0.01 %/K
<1%
< 3 m (to the Rogowski coil)
-25 °C ... +70 °C
-40 °C ... +85 °C
2.5 kV AC, 50 Hz, 1 min.
CAGE CLAMP® S
solid:
0.08 mm² ... 2.5 mm² / AWG 28 ... 14
fine-stranded:
0.34 mm² ... 2.5 mm² / AWG 22 ... 14
9 ... 10 mm / 0.37 in
6 x 96 x 94
Height from upper-edge of DIN 35 rail
36.2 g
1
(pending)
(pending)
g (pending)
see Full Line Catalog 2010/2011,
Interface Modules
Rogowski coils:
RT500: 0758-0950/0000-0500
RT2000: 0758-0950/0000-2000
HW/SW 01/01
3
63
857-552
▯ = ON
DIP Switch S1
Input Signal
1
RC Configuration Input
2
RC1 = RT500 from LEM
● RC2
Filter
Output Signal
3
RC2 = RT2000 from LEM
● RC2 = 100 mV eff. => 1 kA
4
5
6
off
●
0 ... 20 mA
active
●
4 ... 20 mA
●
2 ... 10 V
●
0 ... 10 V
●
●
●
●
●
●
0 ... 10 mA
●
2 ... 10 mA
●
0 ... 5 V
●
1 ... 5 V
DIP-Schalter S1
7
8
Measuring Range Underflow
Measuring Range Overflow
Overcurrent
(Input Signal - End Value + 20%)
(+20 %)
Upper limit of measuring range + 2.5 %*
Upper limit of measuring range + 5 %*
Lower limit of measuring range
Upper limit of measuring range + 2.5 %
Upper limit of measuring range + 5 %
●
Lower limit of measuring range
Upper limit of measuring range
Lower limit of measuring range
●
Lower limit of measuring range
Upper limit of measuring range
Upper limit of measuring range
●
●
*
9 10
Digit Output DO
Signaling
●
DO Us+ switching
●
DO GND switching
DO not active
●
acc. to NAMUR NE 43
Digital Output DO/Signaling
The digital output (DO) signals error messages and can be configured as follows: 24 V … 0 V/0 V … 24 V.
In order to increase the switching current of the DO, the latter may be expanded by a relay. Thanks to the contour uniformity of Series 857, for example, a 857-304
Relay can be snapped in next to it. This output can be quickly and easily expanded to a switching current of 6A by simply using an adjacent jumper (859-402).
Default Setting
All DIP switches are in “OFF“ position for delivery.
Input
Input Signal
RC1 500 A
Measuring Method
Mean square value
Output
Output Signal
0 ... 20 mA
Measuring Range Underflow
0 mA
Measuring Range Overflow
20.5 mA
Overcurrent
21 mA
Digital Output DO
not active
Filter
not active
Application example:
PLC/
LED indication
L1
LED indication
24 V/500 mA
e.g. 787-1002
16.8 ... 31.2 V
AC 230 V
INTERFACE ELECTRONIC
DIP Switch Adjustability
857-809
Potentiometer Position Transducer
Configuration via:
INTERFACE ELECTRONIC
64
JUMPFLEX® Transducers
<_________ 96 mm/3.76 in _________>
DIP Switches
____________
<_________ 94 mm/3.68 in _________>
Short description:
The 857-809 Potentiometer Position Transducer records resistance signals (e.g.,
from potentiometers), converting them into an analog standard signal.
The device is supplied with 24VDC (nominal voltage). Configuration is
performed via DIP switches.
Technical Data
Configuration:
Configuration
Input:
Input signal
Input range
Potentiometer
Resistors
Min. measuring range
Output:
Output signal
Load impedance
Step response
Output - Digital
Max. switching voltage
Max. continuous current
General specifications:
Voltage supply VN
Supply voltage range
Current consumption at 24 V DC
Operational indication
Transmission error
Temperature coefficient
Push/Slide Switch
0%
1
5
OUT+
6
GND 1
OUT
2
IN
100%
3
DO (GND 2) 4 DO
_>
7
POWER
8
Us+
GND 2
_>
3
6 mm/0.23 in
Description
Item No.
Pack.
Unit
JUMPFLEX® Transducer, for DIN 35 rail
Potentiometer Position Transducer
857-809
1
Technical Data
DIP switches, push/slide switch
Potentiometers and resistors
100 Ω – 100 kΩ
10 Ω – 100 kΩ
100 Ω
Voltage:
0 – 10 V, 2 – 10 V, 0 – 5 V, 1 – 5 V
Current:
0 – 20 mA, 4 – 20 mA,
0 – 10 mA, 2 – 10 mA
≤ 600 Ω (I output)
≥ 2 kΩ (U output)
< 32 ms
Supply voltage applied
100 mA
24 V DC
16.8 V ... 31.2 V
< 40 mA
LED, output behavior, DO
≤ 0.1 % of upper range value
≤ 0.01 %/K
Environmental requirements:
Ambient operating temperature
Storage temperature
Safety and protection:
Test voltage (input/output/supply)
Connection and type of mounting:
Wire connection
Cross sections
Strip lengths
Dimensions and weight:
Dimensions (mm) W x H x L
Weight
Standards and approvals:
r UL 508
r ANSI/ISA 12.12.01
Shipbuilding
Accessories
-25 °C ... +70 °C
-40 °C ... +85 °C
2.5 kV AC, 50 Hz, 1 min.
CAGE CLAMP® S
solid:
0.08 mm² –2.5 mm² / AWG 28 –14
fine-stranded:
0.34 mm² –2.5 mm² / AWG 22 –14
9 –10 mm / 0.37 in
6 x 96 x 94
Height from upper-edge of DIN 35 rail
49.2 g
(pending)
(pending)
g (pending)
see Full Line Catalog 2010/2011,
Interface Modules
3
65
DIP Switch Adjustability
857-809
INTERFACE ELECTRONIC
▯ = ON
DIP Switch S1
1
Input
Potentiometer
▯
Resistor
DIP Switch S1 and S2
End Value
Start Value
DIP S1
2
3
4
DIP S1
Resistor Ω
5
7
6
8
9
DIP S2
10
Resistor Ω
1
100000*
0*
●
●
0
●
●
●
12
●
13
●
●
15
●
●
●
●
●
●
●
●
18
●
20
●
22
●
24
●
27
●
●
30
●
●
●
33
●
●
●
36
●
39
●
43
●
●
47
●
●
51
●
●
56
●
●
●
●
●
●
62
●
●
●
68
●
●
●
●
●
●
●
●
●
75
●
●
82
●
●
91
●
●
40
●
●
50
●
●
●
60
●
●
●
70
●
●
●
●
80
●
●
●
●
90
10
●
11
●
●
●
16
●
●
●
●
●
11
●
0
●
10
12
●
13
●
●
15
●
●
16
●
●
●
●
●
●
20
●
22
●
24
●
●
27
●
●
30
●
●
●
33
●
●
●
●
●
39
●
43
●
●
47
●
●
51
●
56
●
●
●
●
●
62
●
●
●
68
●
●
●
●
●
●
●
●
75
●
82
●
●
91
●
●
40
50
●
●
●
●
●
60
●
●
●
70
●
●
●
●
80
●
●
●
●
90
●
●
36
●
●
●
18
*
Default setting
DIP Switch S2
Factor of Initial Value
2
Factor of End Value
3
4
x1*
●
●
Output
5
6
x1*
x10
●
●
x100
●
x1000
●
x10
●
x100
●
x1000
Output Signal Range
7
8
0 – 10 V/0 – 20 mA*
Current*
●
Voltage
●
●
2 – 10 V/4 – 20 mA
●
0 – 5 V/0 – 10 mA
●
1 – 5 V/2 – 10 mA
*
Default setting
9
10
Measuring Range Underflow
Measuring Range Overflow
Wire Break
Upper limit of output range*1
+2.5 %
Lower limit of output range*1
-5 %
Upper limit of output range*1
+5 %
Upper limit of output range
+2.5 %
Lower limit of output range
Upper limit of output range
+5 %
●
Upper limit of output range
Lower limit of output range
Upper limit of output range
+5 %
●
Upper limit of output range
Lower limit of output range
Lower limit of output range
●
●
*1
acc. to NAMUR NE 45
3
66
INTERFACE ELECTRONIC
Push/Slide Switch Operation:
Operating push/slide switch:
The following switching thresholds (SP1 and SP2) are set via
push/slide switch. The switch is located under the front-side
transparent cover and can be operated manually.
press
left
- Press PSS down until the yellow LED is flashing
- Set potentiometer to the minimum value
- Briefly push PSS to the left
- Red LED flashes briefly
- Set potentiometer to the maximum value
- Briefly push PSS to the right
- Red LED flashes briefly
- Briefly press PSS downward
- The yellow LED stops flashing
right
PSS = Push/slide switch
Transmission function
Configuration instructions
Press for
1 sec.
Out
Red
LED
flashes
briefly
Yellow
LED
flashes
max.
No flashing
min.
In
Parameterization mode
SP 2
SP 1
Press for
1 sec.
Out
SP2
SP1
Yellow
LED
flashes
Exit
parameterization mode
Red
LED
flashes
briefly
No flashing
max.
min.
In
SP 1
Parameterization mode
SP2
SP1
SP 2
Press for
1 sec.
Yellow
LED
flashes
Exit
parameterization mode
Red
LED
flashes
briefly
Press for
3 sec.
Delete set
switching points
No flashing
Parameterization mode
Press for
1 sec.
SP1
Yellow
LED
flashes
Exit parameterization
mode without
saving value.
SP = Switching points
Exit
parameterization mode
No flashing
Parameterization mode
Exit
parameterization mode
3
67
4...20 mA
4...2
PLC/
LED indication
e.g 787-1002
16.8...31.2 V
LED indication
24 V/500 mA
AC 230 V
INTERFACE ELECTRONIC
Application example:
857-818
3
Ni Transducer for Ni 100, Ni 120, Ni 200, Ni 500, Ni 1000
Configuration via:
INTERFACE ELECTRONIC
68
JUMPFLEX® Transducers
<_________ 96 mm/3.76 in _________>
DIP Switches
<_________ 94 mm/3.68 in _________>
Short description:
The 857-818 Ni Transducer (Ni = nickel) records signals from Ni sensors
featuring all standard characteristics. On the output side, the NI temperature
transducer converts the temperature signal into a standard analog signal.
Characteristics:
• For Ni100, Ni120, Ni200, Ni500 and Ni1000 sensors
• Calibrated scale switching
• Clipping capability allows analog standard signal limitation to upper range
values
• Safe 3-way isolation with 2.5 kV test voltage to EN 61140
Technical Data
Configuration:
Configuration
Input:
Input signal
Max. input signal
Sensor types
Sensor connection
Output:
Output signal
Load impedance
Step response
General specifications:
Voltage supply VN
Supply voltage range
Current consumption at 24 V DC
Transmission error
OUT
6 GND 1
2
IN
3
_>
4
_>
____________
5 OUT+
1
7 Us+
POWER
8 GND 2
6 mm/0.23 in
Description
Item No.
JUMPFLEX® Transducer, for DIN 35 rail
857-818
Ni transducer for Ni100, Ni120, Ni200, Ni500, Ni1000
with temperature coefficients: 6178 ppm/K (DIN 43760)
5000 ppm/K; 6720 ppm/K; 6370 ppm/K
Pack.
Unit
1
Technical Data
DIP switch
Ni sensors
± 31.2 V DC
Ni 100, Ni 120, Ni 200, Ni 500,
Ni 1000
2-wire, 3-wire, 4-wire (switchable)
0 ... 10 mA, 2 ... 10 mA,
0 ... 20 mA, 4 ... 20 mA,
0... 5 V, 1 ... 5 V,
0 ... 10 V, 2 ... 10 V
≤ 600 Ω (I output)
≥ 2 kΩ (U output)
< 60 ms at 2- and 4-conductor
measurement
< 120 ms at 3-conductor measurement
24 V DC
16.8 V ... 31.2 V
< 40 mA
≤ 0.1 % of upper range value
Environmental requirements:
Ambient operating temperature
Storage temperature
Safety and protection:
Test voltage (input/output/supply)
Connection and type of mounting:
Wire connection
Cross sections
Strip lengths
Dimensions and weight:
Dimensions (mm) W x H x L
Weight
Standards and approvals:
Conformity marking
r UL 508
r ANSI/ISA 12.12.01
Shipbuilding
Accessories
-25 °C ... +70 °C
-40 °C ... +85 °C
2.5 kV AC, 50 Hz, 1 min.
CAGE CLAMP® S
solid:
0.08 mm² ... 2.5 mm² / AWG 28 ... 14
fine-stranded:
0.34 mm² ... 2.5 mm² / AWG 22 ... 14
9 ... 10 mm / 0.37 in
6 x 96 x 94
Height from upper-edge of DIN 35 rail
50 g
1
(pending)
g (pending)
see Full Line Catalog 2010/2011,
Interface Modules
3
69
DIP Switch Adjustability
857-818
INTERFACE ELECTRONIC
▯ = ON
DIP Switch S1
Connection Technology
1
Temperature Coefficient
2
3
4
5
2-conductor
●
6
7
6178 ppm/K
3-conductor
●
Sensor Type
●
Ni 100
5000 ppm/K
4-conductor
●
●
6720 ppm/K
●
Reserve
●
Ni 120
●
●
Ni 200
●
Ni 500
●
Ni 1000
DIP Switch S1
Start Temperature
8
9 10
●
●
●
°C
1
-60
●
●
-50
●
-40
●
-30
●
-20
●
●
-10
●
●
0
●
End Temperature
●
2
4
5
T / °C
1
2
0
●
●
●
10
●
20
●
30
●
40
●
●
50
●
●
60
●
●
3
●
●
●
70
●
80
●
90
T / °C
1
●
100
●
●
●
110
●
●
120
●
●
●
130
●
●
●
140
●
●
3
4
●
150
●
160
●
●
170
●
●
180
●
190
●
●
5
●
●
2
5
T / °C
●
3
●
200
●
●
●
210
●
●
●
220
●
●
●
●
230
●
●
240
●
●
●
250
●
●
●
260
●
●
●
270
●
●
●
280
●
●
●
●
290
●
●
●
●
300
●
●
4
DIP Switch S2
Output Signal
6
7
8
0 … 20 mA
E
4 … 20 mA
F
▯
0 … 10 mA
G
▯
2 … 10 mA
H
▯
▯
▯
0 … 10 V
J
▯
2 … 10 V
K
▯
▯
0…5V
L
▯
▯
1…5V
M
▯
▯
Code OUT
9 10
Measuring Range
Underflow
Measuring Range
Overflow
Wire Break
Short Circuit
Lower limit of output range Upper limit of output range Upper limit of output range Lower limit of output range
-5 % **2
+2.5 %*2
5 %*2
-12.5 % **2
▯
▯
Lower limit of output range
Upper limit of output range Upper limit of output range
Lower limit of output range
+2.5 %
5%
▯
Lower limit of output range
Upper limit of output
range
Upper limit of output range Upper limit of output range
5%
5%
▯
Lower limit of output range
Upper limit of output
range
Lower limit of output range Lower limit of output range
* but not when lower limit of output range = 0V or 0mA
*2 acc. to NAMUR NE 43
Default Setting
All DIP switches are in “OFF“ position for delivery.
Sensor connection
2-conductor
Sensor type
NI 100
Temperature coefficient
6178 ppm/K
Start temperature
0 °C
End temperature
100 °C
Output signal
0 … 20 mA
Measuring range underflow
0 mA
Measuring range overflow
20.5 mA
Wire break
21 mA
Short circuit
0 mA
857-820
3
KTY Transducer
Configuration via:
INTERFACE ELECTRONIC
70
JUMPFLEX® Transducers
<_________ 96 mm/3.76 in _________>
DIP Switches
<_________ 94 mm/3.68 in _________>
Short description:
The 857-820 KTY Transducer records signals from KTY sensors featuring all
standard characteristics. On the output side, the KTY temperature transducer
converts the temperature signal into a standard analog signal.
_>
_>
____________
IN+ 1
KTY
IN- 2
OUT 5 OUT+
U; I
6 GND 1
DO 3
DO
GND 2 4
7 Us+
POWER
8 GND 2
6 mm/0.23 in
Description
Item No.
Pack.
Unit
JUMPFLEX® Transducer, for DIN 35 rail
KTY Transducer
857-820
1
Characteristics:
• Supports all standard KTY sensors
• Calibrated scale switching
• Clipping capability allows analog standard signal limitation to upper range
values
• Safe 3-way isolation with 2.5 kV test voltage to EN 61140
Technical Data
Configuration:
Configuration
Input:
Input signal
Max. input signal
Sensor types
Sensor connection
Output:
Output signal
Load impedance
Step response
Output - Digital
Max. switching voltage
Max. continuous current
Technical Data
DIP switch
KTY sensors
± 30 V DC
KTY81-110, KTY81-120, KTY81-150
KTY82-110, KTY82-120, KTY82-150,
KTY81-121, KTY82-121, KTY81-122,
KTY82-122, KTY81-210, KTY81-220,
KTY82-210, KTY82-220, KTY81-221,
KTY82-221, KTY81-222, KTY82-222,
KTY81-250, KTY82-250, KTY83-110,
KTY83-120, KTY83-150, KTY83-121,
KTY83-122, KTY83-151, KTY84-130,
KTY84-150, KTY84-151, KTY16, KTY19,
ST13, ST20
2-conductor
0 ... 10 mA, 2 ... 10 mA,
0 ... 20 mA, 4 ... 20 mA,
0... 5 V, 1 ... 5 V,
0 ... 10 V, 2 ... 10 V
≤ 600 Ω (I output)
≥ 2 kΩ (U output)
< 50 ms
Supply voltage applied
500 mA (up to 60 °C)
100 mA (60 °C ... 70 °C)
General specifications:
Voltage supply VN
Supply voltage range
Current consumption at 24 V DC
Transmission error
Environmental requirements:
Ambient operating temperature
Storage temperature
Safety and protection:
Test voltage (input/output/supply)
Connection and type of mounting:
Wire connection
Cross sections
Strip lengths
Dimensions and weight:
Dimensions (mm) W x H x L
Weight
Standards and approvals:
Conformity marking
r UL 508
r ANSI/ISA 12.12.01
Shipbuilding
Accessories
24 V DC
16.8 V ... 31.2 V
< 40 mA
≤ 0.1 % of upper range value
-25 °C ... +70 °C
-40 °C ... +85 °C
2.5 kV AC, 50 Hz, 1 min.
CAGE CLAMP® S
solid:
0.08 mm² ... 2.5 mm² / AWG 28 ... 14
fine-stranded:
0.34 mm² ... 2.5 mm² / AWG 22 ... 14
9 ... 10 mm / 0.37 in
6 x 96 x 94
Height from upper-edge of DIN 35 rail
50 g
1
(pending)
g (pending)
see Full Line Catalog 2010/2011,
Interface Modules
3
71
DIP Switch Adjustability
857-820
INTERFACE ELECTRONIC
▯ = ON
DIP Switch S1
Sensor Type
1
2
3
4
KTY81-110, KTY81-120, KTY82-110, KTY82-120
●
KTY81-121, KTY82-121
●
●
KTY81-150, KTY82-150
●
KTY81-210, KTY81-220, KTY82-210, KTY82-220
●
KTY81-221, KTY82-221
●
●
KTY81-222, KTY82-222
●
●
●
●
KTY81-122, KTY82-122
●
KTY81-250, KTY82-250
● KTY83-110, KTY83-120,
●
● KTY83-121
●
●
●
● KTY83-150
●
● KTY83-151
●
● KTY84-130, KTY84-150
●
●
● KTY84-151
●
●
● KTY16, KTY19, ST13, ST20
●
●
● KTY83-122
DIP Switch S2
Start Temperature
1
2
3
●
●
●
°C
4
-55
●
●
-50
●
-40
●
End Temperature
●
-30
●
-20
●
●
-10
●
●
0
●
5
7
8
°C
4
5
0
●
●
●
10
●
20
●
●
6
●
30
●
40
●
●
50
●
●
60
●
●
●
70
●
80
●
90
°C
4
●
100
●
●
●
110
●
●
120
●
●
●
130
●
●
●
●
●
6
7
●
●
●
●
●
8
140
●
150
●
160
●
170
●
180
●
190
●
5
8
°C
●
6
●
200
●
●
●
210
●
●
●
220
●
●
230
●
●
●
●
240
●
●
●
250
●
●
●
260
●
●
270
●
●
●
7
●
●
●
280
●
●
●
●
290
●
●
●
●
300
DIP Switch S1
Output Signal
6
7
8
0 … 20 mA
E
4 … 20 mA
F
▯
0 … 10 mA
G
▯
2 … 10 mA
H
▯
▯
▯
0 … 10 V
J
▯
2 … 10 V
K
▯
▯
0…5V
L
▯
▯
1…5V
M
▯
▯
Code OUT
9 10
Measuring Range
Underflow
Measuring Range
Overflow
Wire Break
Short Circuit
Lower limit of output range Upper limit of output range Upper limit of output range Lower limit of output range
-5 % **2
+2.5 %*2
5 %*2
-12.5 % **2
▯
▯
Lower limit of output range
Upper limit of output range Upper limit of output range
Lower limit of output range
+2.5 %
5%
▯
Lower limit of output range
Upper limit of output
range
Upper limit of output range Upper limit of output range
5%
5%
▯
Lower limit of output range
Upper limit of output
range
Lower limit of output range Lower limit of output range
* but not when lower limit of output range = 0V or 0mA
*2 acc. to NAMUR NE 43
Default Setting
DIP Switch S2
All DIP switches are in „OFF“ position for delivery.
Sensor type
KTY81-110, KTY81-120, KTY82-110, KTY82-120
Start temperature
0 °C
End temperature
100 °C
Output signal
0 … 20 mA
Measuring range underflow
0 mA
Measuring range overflow
20.5 mA
Wire break
21 mA
Short circuit
0 mA
Digital output
not active
9 10
Digit Output DO Signaling
DO not active
●
●
DO Us+ switching
●
DO GND switching
857-979
3
Supply and Through Module
<_________ 96 mm/3.76 in _________>
INTERFACE ELECTRONIC
72
JUMPFLEX® Supply and Through Module
<_________ 94 mm/3.68 in _________>
Short description:
The 857-979 Supply and Through Module transmits electrically isolated signals (e.g., in conjunction with the 857-980 JUMPFLEX® Interface Adapter for
analog signals). When used as a supply module, it transmits the power from the
clamping points to the adjacent JUMPFLEX® modules via push-in type jumper
bars.
Technical Data
General specifications:
Max. voltage
Current carrying capacity
Contact resistance
Environmental requirements:
Ambient operating temperature
Storage temperature
Connection and type of mounting:
Wire connection
Cross sections
Strip lengths
Dimensions and weight:
Dimensions (mm) W x H x L
Weight
Standards and approvals:
Conformity marking
r UL 508
r ANSI/ISA 12.12.01
Shipbuilding
Accessories
-25 °C ... +70 °C
-40 °C ... +85 °C
CAGE CLAMP® S
solid:
0.08 mm² ... 2.5 mm² / AWG 28 ... 14
fine-stranded:
0.34 mm² ... 2.5 mm² / AWG 22 ... 14
9 ... 10 mm / 0.37 in
6 x 96 x 94
Height from upper-edge of DIN 35 rail
30 g
1
(pending)
g (pending)
see Full Line Catalog 2010/2011,
Interface Modules, or online catalog
5 Signal+
GND 2
6 GND
Us+ 3
7 Us+
GND 4
8 GND
6 mm/0.23 in
Description
Item No.
Pack.
Unit
JUMPFLEX® Supply and Through Module
857-979
25
Technical Data
33 V AC/DC
8A
< 10 mΩ
_>
_>
____________
Signal+ 1
3
Application example:
Power supply for 8 JUMPFLEX® modules with plugged interface adapter
•WAGO interface adapter, 857-980
•WAGO ribbon cable, 706-100/1602-200, 16-pole socket/open-ended
•Push-in type jumper bar, 9-way, 859-409
1
2
857-979
INTERFACE ELECTRONIC
73
787-1001
4
EPSITRON® COMPACT Power
INTERFACE ELECTRONIC
74
Switched-Mode Power Supply
L
DC+
DC+
DC DC -
N
•
•
•
•
•
Primary switch mode power supply unit
Prepared for class II equipment
Natural convection cooling when horizontally mounted
Stage profile, ideal for distribution boards or distribution boxes
At reduced output current, any type of mounting positions are possible
(e.g., horizontal, overhead mounting)
Technical Data
Input:
Nominal input voltage Vi nom
Input voltage range
Input voltage derating
Frequency
Input current Ii
Discharge current
Inrush current
Mains failure hold-up time
Output:
Nominal output voltage Vo nom
Output voltage range
Output current Io
Factory preset
Adjustment accuracy
Residual ripple
Current limitation
Overload behavior
Operational indication
Efficiency / power losses:
Efficiency
Power loss PV
Max. power loss PV
Fuse protection:
Internal fuse
External fuse
Description
Item No.
Pack.
Unit
Switched-Mode Power Supply,
12 VDC / 2A
787-1001
1
Technical Data
100 ... 240 VAC
85 ... 264 VAC; 120 ... 373 VDC
< 100 VAC: Ia max. 1.5 A
44 ... 66 Hz; 0 Hz
0.6 A at 110 VAC / 0.4 A at 230 VAC
1 mA typ.
< 30 A, NTC
> 10 ms at 110 VAC /
> 80 ms at 230 VAC
12 VDC
10.8 ... 18 VDC adjustable
2 A at 12 VDC
0.75 A at 18 VDC
max. 1.4 A (12 VDC) in any mounting
position
12 VDC
2%
< 150 mVpp at 20 MHz
1.1 x Io typ.
Constant current
LED green (Va)
80 % typ.
2.6 W (230 VAC/no load),
6.0 W (230 VAC/rated load)
6 W typ. (100 VAC / 12 VDC, 2A)
2 AT
Wire breaking 10A, 16A,
Characteristic B, C
An external DC fuse is required for the
DC input voltage
Environmental requirements:
Ambient operating temperature
Storage temperature
Rel. humidity
Derating
Degree of pollution
Climatic category
Safety and protection:
Enclosure
Test voltage pri. - sec.
Protection class
Degree of protection
Overvoltage protection
Short circuit protection
No-load proof
Feedback voltage
Parallel operation
Series connection
MTBF
Connection and type of mounting:
Wire connection
Cross sections
Stripped lengths
Type of mounting
Dimensions and weight:
Dimensions (mm) W x H x L
Weight
Standards and approvals:
Standards/Specifications
-25 °C ... +55 °C
-25 °C ... +80 °C
30 % ... 85 % (no condensation)
-3 % / K (> 45 °C)
2 (acc. to EN 50178)
3K3 (acc. to EN 60721)
Plastic, light gray,
Flammability class V0 acc. to UL94
4.2 kV DC
Prepared for class II equipment
IP20 (acc. to EN 60529)
< 30 VDC (in the event of a fault)
yes
yes
max. 20 VDC
yes
yes
500000 h
Input/Output: WAGO 740 Series
Input/Output:
0.08 ... 2.5 mm² / AWG 28 ... 12
Input/Output:
6 ... 7 mm / 0.24 ... 0.28 in
DIN-rail mount (EN 60715)
54 x 89 x 59
Length: 55 mm, from upper-edge of DIN
35 rail
180 g
EN 60950 (SELV), EN 61204-3,
UL 60950, UL 508, GL
787-1011
4
Switched-Mode Power Supply
EPSITRON® COMPACT Power
L
DC+
DC+
DC DC -
N
•
•
•
•
•
Primary switch mode power supply unit
Prepared for class II equipment
Natural convection cooling when horizontally mounted
Stage profile, ideal for distribution boards or distribution boxes
At reduced output current, any type of mounting positions are possible
(e.g., horizontal, overhead mounting)
Technical Data
Input:
Nominal input voltage Vi nom
Input voltage range
Input voltage derating
Frequency
Input current Ii
Discharge current
Inrush current
Mains failure hold-up time
Output:
Nominal output voltage Vo nom
Output voltage range
Output current Io
Factory preset
Adjustment accuracy
Residual ripple
Current limitation
Overload behavior
Operational indication
Efficiency / power losses:
Efficiency
Power loss PV
Max. power loss PV
Fuse protection:
Internal fuse
External fuse
INTERFACE ELECTRONIC
75
Description
Item No.
Pack.
Unit
Switched-Mode Power Supply,
12 VDC / 4A
787-1011
1
Technical Data
100 ... 240 VAC
85 ... 264 VAC; 120 ... 373 VDC
< 100 VAC: Ia max. 3.5 A
44 ... 66 Hz; 0 Hz
0.9 A at 110 VAC / 0.5 A at 230 VAC
1 mA typ.
< 30 A, NTC
> 10 ms at 110 VAC /
> 80 ms at 230 VAC
12 VDC
10.5 ... 15.5 VDC adjustable
4 A at 12 VDC
max. 2.4 A in any mounting position
12 VDC
2%
< 100 mVpp at 20 MHz
1.1 x Io typ.
Constant current
LED green (Va)
85 % typ.
2.2 W (230 VAC/no load),
8.5 W (230 VAC/rated load)
9 W typ. (100 VAC / 12 VDC, 4 A)
2 AT
Wire breaking 10A, 16A,
Characteristic B, C
An external DC fuse is required for the
DC input voltage
Environmental requirements:
Ambient operating temperature
Storage temperature
Rel. humidity
Derating
Degree of pollution
Climatic category
Safety and protection:
Enclosure
Test voltage pri. - sec.
Protection class
Degree of protection
Overvoltage protection
Short circuit protection
No-load proof
Feedback voltage
Parallel operation
Series connection
MTBF
Connection and type of mounting:
Wire connection
Cross sections
Stripped lengths
Type of mounting
Dimensions and weight:
Dimensions (mm) W x H x L
Weight
Standards and approvals:
Standards/Specifications
-25 °C ... +55 °C
-25 °C ... +80 °C
30 % ... 85 % (no condensation)
-3 % / K (> 45 °C)
2 (acc. to EN 50178)
3K3 (acc. to EN 60721)
Plastic, light gray,
Flammability class V0 acc. to UL94
4.2 kV DC
Prepared for class II equipment
IP20 (acc. to EN 60529)
< 30 VDC (in the event of a fault)
yes
yes
max. 20 VDC
yes
yes
500000 h
Input/Output: WAGO 740 Series
Input/Output:
0.08 ... 2.5 mm² / AWG 28 ... 12
Input/Output:
6 ... 7 mm / 0.24 ... 0.28 in
DIN-rail mount (EN 60715)
72 x 89 x 59
Length: 55 mm, from upper-edge of DIN
35 rail
255 g
EN 60950 (SELV), EN 61204-3,
UL 60950*, UL 508*,
GL (* pending)
787-1021
4
EPSITRON® COMPACT Power
INTERFACE ELECTRONIC
76
Switched-Mode Power Supply
L
DC+
DC+
DC DC -
N
•
•
•
•
•
Primary switch mode power supply unit
Prepared for class II equipment
Natural convection cooling when horizontally mounted
Stage profile, ideal for distribution boards or distribution boxes
At reduced output current, any type of mounting positions are possible
(e.g., horizontal, overhead mounting)
Technical Data
Input:
Nominal input voltage Vi nom
Input voltage range
Input voltage derating
Frequency
Input current Ii
Discharge current
Inrush current
Mains failure hold-up time
Output:
Nominal output voltage Vo nom
Output voltage range
Output current Io
Factory preset
Adjustment accuracy
Residual ripple
Current limitation
Overload behavior
Operational indication
Efficiency / power losses:
Efficiency
Power loss PV
Max. power loss PV
Fuse protection:
Internal fuse
External fuse
Description
Item No.
Pack.
Unit
Switched-Mode Power Supply,
12 VDC / 6.5A
787-1021
1
Technical Data
100 ... 240 VAC
85 ... 264 VAC; 120 ... 373 VDC
max. 6 A (< 100 VAC) /
5.5 A (< 90 VAC)
44 ... 66 Hz; 0 Hz
1.6 A at 110 VAC / 0.9 A at 230 VAC
1 mA typ.
< 30 A , NTC
> 15 ms at 110 VAC /
> 100 ms at 230 VAC
12 VDC
10.5 ... 15.5 VDC adjustable
6.5 A at 12 VDC
0.75 A at 18 VDC
max. 3.9 A (12 VDC) in any mounting
position
12 VDC
2%
< 100 mVpp at 20 MHz
1.1 x Io typ.
Constant current
LED green (Va)
Environmental requirements:
Ambient operating temperature
Storage temperature
Rel. humidity
Derating
Degree of pollution
Climatic category
Safety and protection:
Enclosure
Test voltage pri. - sec.
Protection class
Degree of protection
Overvoltage protection
Short circuit protection
No-load proof
Feedback voltage
Parallel operation
Series connection
MTBF
Connection and type of mounting:
Wire connection
Cross sections
Stripped lengths
87 % typ.
< 1 W (no load) /
15 W (rated load)
15 W typ. (100 VAC / 12 VDC, 6.5 A)
4 AT
Wire breaking 10 A, 16 A,
Characteristic B, C
An external DC fuse is required for the DC
input voltage
Type of mounting
Dimensions and weight:
Dimensions (mm) W x H x L
Weight
Standards and approvals:
Standards/Specifications
-25 °C ... +55 °C
-25 °C ... +85 °C
30 % ... 85 % (no condensation)
-3 % / K (> 45 °C)
2 (acc. to EN 50178)
3K3 (acc. to EN 60721)
Plastic, light gray,
Flammability class V0 acc. to UL94
4.2 kV DC
Prepared for class II equipment
IP20 (acc. to EN 60529)
< 30 VDC (in the event of a fault)
yes
yes
max. 20 VDC
yes
yes
500000 h
Input/Output: WAGO 740 Series
Input/Output:
0.08 ... 2.5 mm² / AWG 28 ... 12
Input/Output:
6 ... 7 mm / 0.24 ... 0.28 in
DIN-rail mount (EN 60715)
90 x 89 x 59
Length: 55 mm, from upper-edge of DIN
35 rail
300 g
EN 60950 (SELV), EN 61204-3, GL,
UL 60950*, UL 508* (* pending)
787-1002
4
Switched-Mode Power Supply
EPSITRON® COMPACT Power
L
DC+
DC+
DC DC -
N
•
•
•
•
•
Primary switch mode power supply unit
Prepared for class II equipment
Natural convection cooling when horizontally mounted
Stage profile, ideal for distribution boards or distribution boxes
At reduced output current, any type of mounting positions are possible
(e.g., horizontal, overhead mounting)
Technical Data
Input:
Nominal input voltage Vi nom
Input voltage range
Input voltage derating
Frequency
Input current Ii
Discharge current
Inrush current
Mains failure hold-up time
Output:
Nominal output voltage Vo nom
Output voltage range
Output current Io
Factory preset
Adjustment accuracy
Residual ripple
Current limitation
Overload behavior
Operational indication
Efficiency / power losses:
Efficiency
Power loss PV
Max. power loss PV
Fuse protection:
Internal fuse
External fuse
INTERFACE ELECTRONIC
77
Description
Item No.
Pack.
Unit
Switched-Mode Power Supply,
24 VDC / 1.3A
787-1002
1
Technical Data
100 ... 240 VAC
85 ... 264 VAC; 120 ... 373 VDC
< 100 VAC: Ia max. 1A
44 ... 66 Hz; 0 Hz
0.7 A at 110 VAC / 0.5 A at 230 VAC
1mA typ.
< 30 A, NTC
> 10ms at 110 VAC /
> 80ms at 230 VAC
24 VDC
22.8 ... 26.4 VDC adjustable
1.3 A at 24 VDC
max. 0.9 A in any mounting position
24 VDC
2%
< 100 mVpp at 20 MHz
1.1 x Io typ.
Constant current
LED green (Va)
82 % typ.
2.6 W (230 VAC/no load),
7.0 W (230 VAC/rated load)
7.3 W typ. (100 VAC / 24 VDC, 1.3 A)
2 AT
Wire breaking 10 A, 16 A,
Characteristic B, C
An external DC fuse is required for the DC
input voltage
Environmental requirements:
Ambient operating temperature
Storage temperature
Rel. humidity
Derating
Degree of pollution
Climatic category
Safety and protection:
Enclosure
Test voltage pri. - sec.
Protection class
Degree of protection
Overvoltage protection
Short circuit protection
No-load proof
Feedback voltage
Parallel operation
Series connection
MTBF
Connection and type of mounting:
Wire connection
Cross sections
Stripped lengths
Type of mounting
Dimensions and weight:
Dimensions (mm) W x H x L
Weight
Standards and approvals:
Standards/Specifications
-25 °C ... +55 °C
-25 °C ... +80 °C
30% ... 85% (no condensation)
-3 % / K (> 45 °C)
2 (acc. to EN 50178)
3K3 (acc. to EN 60721)
Plastic, light gray,
Flammability class V0 acc. to UL94
4.2 kV DC
Prepared for class II equipment
IP20 (acc. to EN 60529)
< 40 VDC (in the event of a fault)
yes
yes
max. 30 VDC
yes
yes
500000h
Input/Output: WAGO 740 Series
Input/Output:
0.08 mm² ... 2.5 mm² / AWG 28 ... 12
Input/Output:
6 ... 7 mm / 0.24 ... 0.28 in
DIN-rail mount (EN 60715)
54 x 89 x 59
Length: 55 mm, from upper-edge of DIN
35 rail35 rail
180 g
EN 60950 (SELV), EN 61204-3,
UL 60950, UL 508, GL
787-1012
4
EPSITRON® COMPACT Power
INTERFACE ELECTRONIC
78
Switched-Mode Power Supply
L
DC+
DC+
DC DC -
N
•
•
•
•
•
Primary switch mode power supply unit
Prepared for class II equipment
Natural convection cooling when horizontally mounted
Stage profile, ideal for distribution boards or distribution boxes
At reduced output current, any type of mounting positions are possible
(e.g., horizontal, overhead mounting)
Technical Data
Input:
Nominal input voltage Vi nom
Input voltage range
Input voltage derating
Frequency
Input current Ii
Discharge current
Inrush current
Mains failure hold-up time
Output:
Nominal output voltage Vo nom
Output voltage range
Output current Io
Factory preset
Adjustment accuracy
Residual ripple
Current limitation
Overload behavior
Operational indication
Efficiency / power losses:
Efficiency
Power loss PV
Max. power loss PV
Fuse protection:
Internal fuse
External fuse
Description
Item No.
Pack.
Unit
Switched-Mode Power Supply,
24 VDC / 2.5A
787-1012
1
Technical Data
100 ... 240 VAC
85 ... 264 VAC; 120 ... 373 VDC
< 100 VAC: Ia max. 2.0 A
< 90 VAC: Ia max. 1.8 A
44 ... 66 Hz; 0 Hz
1.4 A at 110 VAC / 0.6 A at 230 VAC
1 mA typ.
< 30 A, NTC
> 10 ms at 110 VAC /
> 80 ms at 230 VAC
24 VDC
22.8 ... 26.4 VDC adjustable
2.5 A at 24 VDC
max. 1.6 A in any mounting position
24 VDC
2%
< 100 mVpp at 20 MHz
1.1 x Io typ.
Constant current
LED green (Va)
88 % typ.
2.2 W (230 VAC/no load),
8.5 W (230 VAC/rated load)
10.5 W typ. (100 VAC / 24 VDC, 2.5 A)
2 AT
Wire breaking 10 A, 16 A,
Characteristic B, C
An external DC fuse is required for the DC
input voltage
Environmental requirements:
Ambient operating temperature
Storage temperature
Rel. humidity
Derating
Degree of pollution
Climatic category
Safety and protection:
Enclosure
Test voltage pri. - sec.
Protection class
Degree of protection
Overvoltage protection
Short circuit protection
No-load proof
Feedback voltage
Parallel operation
Series connection
MTBF
Connection and type of mounting:
Wire connection
Cross sections
Stripped lengths
Type of mounting
Dimensions and weight:
Dimensions (mm) W x H x L
Weight
Standards and approvals:
Standards/Specifications
-25 °C ... +55 °C
-25 °C ... +80 °C
30 % ... 85 % (no condensation)
-3 % / K (> 45 °C)
2 (acc. to EN 50178)
3K3 (acc. to EN 60721)
Plastic, light gray,
Flammability class V0 acc. to UL94
4.2 kV DC
Prepared for class II equipment
IP20 (acc. to EN 60529)
< 40 VDC (in the event of a fault)
yes
yes
max. 30 VDC
yes
yes
> 500000h
Input/Output: WAGO 740 Series
Input/Output:
0.08 ... 2.5 mm² / AWG 28 ... 12
Input/Output:
6 ... 7 mm / 0.24 ... 0.28 in
DIN-rail mount (EN 60715)
72 x 89 x 59
Length: 55 mm, from upper-edge of
DIN 35 rail
255 g
EN 60950 (SELV), EN 61204-3,
UL 60950, UL 508, GL
787-1022
4
Switched-Mode Power Supply
EPSITRON® COMPACT Power
L
DC+
DC+
DC DC -
N
•
•
•
•
•
Primary switch mode power supply unit
Prepared for class II equipment
Natural convection cooling when horizontally mounted
Stage profile, ideal for distribution boards or distribution boxes
At reduced output current, any type of mounting positions are possible
(e.g., horizontal, overhead mounting)
Technical Data
Input:
Nominal input voltage Vi nom
Input voltage range
Input voltage derating
Frequency
Input current Ii
Discharge current
Inrush current
Mains failure hold-up time
Output:
Nominal output voltage Vo nom
Output voltage range
Output current Io
Factory preset
Adjustment accuracy
Residual ripple
Current limitation
Overload behavior
Operational indication
Efficiency / power losses:
Efficiency
Power loss PV
Max. power loss PV
Fuse protection:
Internal fuse
External fuse
INTERFACE ELECTRONIC
79
Description
Item No.
Pack.
Unit
Switched-Mode Power Supply,
24 VDC / 4A
787-1022
1
Technical Data
100 ... 240 VAC
85 ... 264 VAC; 120 ... 373 VDC
on request
44 ... 66 Hz; 0 Hz
1.6 A at 110 VAC / 0.9 A at 230 VAC
1 mA typ.
< 30 A, NTC
> 15 ms at 110 VAC /
> 100 ms at 230 VAC
24 VDC
22.8 ... 26.4 VDC adjustable
4 A at 24 VDC
max. 2.4 A in any mounting position
24 VDC
2%
< 100 mVpp at 20 MHz
1.1 x Io typ.
Constant current
LED green (Va)
88 % typ.
0.8 W (230 VAC/no load),
13.1 W (230 VAC/rated load)
14.8 W typ. (264 VAC / 24 VDC, 4 A)
4 AT
Wire breaking 10 A, 16 A,
Characteristic B, C
An external DC fuse is required for the DC
input voltage
Environmental requirements:
Ambient operating temperature
Storage temperature
Rel. humidity
Derating
Degree of pollution
Climatic category
Safety and protection:
Enclosure
Test voltage pri. - sec.
Protection class
Degree of protection
Overvoltage protection
Short circuit protection
No-load proof
Feedback voltage
Parallel operation
Series connection
MTBF
Connection and type of mounting:
Wire connection
Cross sections
Stripped lengths
Type of mounting
Dimensions and weight:
Dimensions (mm) W x H x L
Weight
Standards and approvals:
Standards/Specifications
-25 °C ... +55 °C
-25 °C ... +80 °C
30 % ... 85 % (no condensation)
-3 % / K (> 45 °C)
2 (acc. to EN 50178)
3K3 (acc. to EN 60721)
Plastic, light gray,
Flammability class V0 acc. to UL94
4.2 kV DC
Prepared for class II equipment
IP20 (acc. to EN 60529)
< 40 VDC (in the event of a fault)
yes
yes
max. 30 VDC
yes
yes
500000 h
Input/Output: WAGO 740 Series
Input/Output:
0.08 ... 2.5 mm² / AWG 28 ... 12
Input/Output:
6 ... 7 mm / 0.24 ... 0.28 in
DIN-rail mount (EN 60715)
90 x 89 x 59
Length: 55 mm, from upper-edge of
DIN 35 rail
310 g
EN 60950 (SELV), EN 61204-3,
UL 60950*, UL 508*, GL
(* pending)
787-819
4
EPSITRON® - PRO - Power
INTERFACE ELECTRONIC
80
Switched-Mode Power Supply
Stand-by
DC O.K.
L
DC+
DC+
DC DC -
N
• Primary switch mode power supply with PowerBoost and TopBoost
• Stand-by input for switching off the output and minimizing power
consumption
• DC OK contact for output monitoring
• Parallel operation, series connection possible
• Prepared for class I equipment
• Natural convection cooling when horizontally mounted
• Enclosed for use in switchgear cabinets
Technical Data
Input:
Nominal input voltage Vi nom
Input voltage range
Input voltage derating
Frequency
Input current Ii
Discharge current
Inrush current
Mains failure hold-up time
Output:
Nominal output voltage Vo nom
Output voltage range
Output current Io
PowerBoost
TopBoost
Factory preset
Adjustment accuracy
Residual ripple
Current limitation
Overload behavior
Operational indication
Signaling
Efficiency / power losses:
Efficiency
Power loss PV
Fuse protection:
Internal fuse
External fuse
Description
Item No.
Pack.
Unit
Switched-Mode Power Supply,
12 V DC / 6 A
787-819
1
Technical Data
110 ... 240 VAC
85 ... 264 VAC; 120 ... 350 VDC
(use of DC requires external protection)
-5 % / V AC < 95 VAC
50 Hz ... 60 Hz
0.51 A at 230 VAC and 6 ADC
1 mA typ.
< 30 A (peak)
70 ms typ. at 230 VAC
12 VDC, SELV
11 ... 18 VDC adjustable
6 A at 12 V DC
12 ADC (for 4 s); 9 ADC (for 8 s)
21 ADC (for 25 ms)
12 VDC
1%
< 70 mV (peak-peak)
1.1 x Io typ.
TopBoost / PowerBoost /Constant current
LED green (Vo), LED red (error)
Relay contact DC O.K. (changeover
contact)
Environmental requirements:
Ambient operating temperature
Storage temperature
Rel. humidity
Derating
Degree of pollution
Climatic category
Safety and protection:
Test voltage
PRI-SEC / PRI-GND / SEC-GND
Protection class
Degree of protection
Overvoltage protection
Short circuit protection
No-load proof
Feedback voltage
Parallel operation
Series connection
Connection and type of mounting:
Wire connection
Cross sections
Strip lengths
83 % typ.
0.5 W (stand-by) / 3.0 W (no load) /
9.4 W (rated load)
2 AT
6 A, 10 A and 16 A circuit breakers,
B and C characteristics
An external DC fuse is required for DC
input voltage.
Type of mounting
Dimensions and weight:
Dimensions (mm) W x H x L
Weight
Standards and approvals:
Standards/Specifications
-25 °C ... +70 °C
-25 °C ... +85 °C
30 % ... 85 % (no condensation)
-3 % / K (> +50 °C)
2 (acc. to EN 50178)
3K3 (acc. to EN 60721)
4.2 kVDC / 2.2 kVDC / 0.7 kVDC
Prepared for class I equipment
IP20 (acc. to EN 60529)
Varistor at primary circuit
yes
yes
max. 25 V DC
yes
yes
Input/Output: WAGO 231 Series
Signalising: WAGO 733 Series
Input/Output:
0.08 ... 2.5 mm² / AWG 28 ... 12
Signalising: 0.08 ... 0.5 mm² / AWG 28 ... 20
Input/Output: 8 ... 9 mm / 0.33 in
Signalising: 5 ... 6 mm / 0.22 in
DIN-rail mounting (EN 60715) in 2
positions
40 x 163 x 163
(incl. female connector)
Length from upper-edge of DIN 35 rail
800 g
EN 60950, EN 61204-3, UL 60950,
UL 508
787-821
4
Switched-Mode Power Supply
EPSITRON® - PRO - Power
INTERFACE ELECTRONIC
81
Stand-by
DC O.K.
L
DC+
DC+
DC DC -
N
• Primary switch mode power supply with PowerBoost and TopBoost
• Stand-by input for switching off the output and minimizing power
consumption
• DC OK contact for output monitoring
• Parallel operation, series connection possible
• Prepared for class I equipment
• Natural convection cooling when horizontally mounted
• Enclosed for use in switchgear cabinets
Technical Data
Input:
Nominal input voltage Vi nom
Input voltage range
Input voltage derating
Frequency
Input current Ii
Discharge current
Inrush current
Mains failure hold-up time
Output:
Nominal output voltage Vo nom
Output voltage range
Output current Io
PowerBoost
TopBoost
Factory preset
Adjustment accuracy
Residual ripple
Current limitation
Overload behavior
Operational indication
Signaling
Efficiency / power losses:
Efficiency
Power loss PV
Fuse protection:
Internal fuse
External fuse
Description
Item No.
Pack.
Unit
Switched-Mode Power Supply,
12 V DC / 10 A
787-821
1
Technical Data
110 ... 240 VAC
85 ... 264 VAC; 120 ... 350 VDC
(use of DC requires external protection)
-5 % / V AC < 95 VAC
50 Hz ... 60 Hz
0.97 A at 230 VAC and 10 ADC
1 mA typ.
< 30 A (peak)
35 ms typ. at 230 VAC
12 VDC, SELV
11 ... 18 VDC adjustable
10 A at 12 V DC
20 ADC (for 4 s); 15 ADC (for 8 s)
60 ADC (for 25 ms);
40 ADC at VIN < 110 VAC (for 25 ms)
12 VDC
1%
< 70 mV (peak-peak)
1.1 x Io typ.
TopBoost / PowerBoost /Constant current
LED green (Vo), LED red (error)
Relay contact DC O.K. (changeover
contact)
87.8 % typ.
0.5 W (stand-by) / 5.0 W (no load) /
14.6 W (rated load)
4 AT
6 A, 10 A and 16 A circuit breakers,
B and C characteristics
An external DC fuse is required for DC
input voltage.
Environmental requirements:
Ambient operating temperature
Storage temperature
Rel. humidity
Derating
Degree of pollution
Climatic category
Safety and protection:
Test voltage
PRI-SEC / PRI-GND / SEC-GND
Protection class
Degree of protection
Overvoltage protection
Short circuit protection
No-load proof
Feedback voltage
Parallel operation
Series connection
Connection and type of mounting:
Wire connection
Cross sections
Strip lengths
Type of mounting
Dimensions and weight:
Dimensions (mm) W x H x L
Weight
Standards and approvals:
Standards/Specifications
-25 °C ... +70 °C
-25 °C ... +85 °C
30 % ... 85 % (no condensation)
-3 % / K (> +50 °C)
2 (acc. to EN 50178)
3K3 (acc. to EN 60721)
4.2 kVDC / 2.2 kVDC / 0.7 kVDC
Prepared for class I equipment
IP20 (acc. to EN 60529)
Varistor at primary circuit
yes
yes
max. 25 V DC
yes
yes
Input/Output: WAGO 231 Series
Signalising: WAGO 733 Series
Input/Output:
0.08 ... 2.5 mm² / AWG 28 ... 12
Signalising: 0.08 ... 0.5 mm² / AWG 28 ... 20
Input/Output: 8 ... 9 mm / 0.33 in
Signalising: 5 ... 6 mm / 0.22 in
DIN-rail mounting (EN 60715) in 2
positions
57 x 163 x 163
(incl. female connector)
Length from upper-edge of DIN 35 rail
1295 g
EN 60950, EN 61204-3, UL 60950,
UL 508
787-831
4
EPSITRON® - PRO - Power
INTERFACE ELECTRONIC
82
Switched-Mode Power Supply
Stand-by
DC O.K.
L
DC+
DC+
DC DC -
N
• Primary switch mode power supply with PowerBoost and TopBoost
• Stand-by input for switching off the output and minimizing power
consumption
• DC OK contact for output monitoring
• Parallel operation, series connection possible
• Prepared for class I equipment
• Natural convection cooling when horizontally mounted
• Enclosed for use in switchgear cabinets
Technical Data
Input:
Nominal input voltage Vi nom
Input voltage range
Input voltage derating
Frequency
Input current Ii
Discharge current
Inrush current
Mains failure hold-up time
Output:
Nominal output voltage Vo nom
Output voltage range
Output current Io
PowerBoost
TopBoost
Factory preset
Adjustment accuracy
Residual ripple
Current limitation
Overload behavior
Operational indication
Signaling
Efficiency / power losses:
Efficiency
Power loss PV
Fuse protection:
Internal fuse
External fuse
Description
Item No.
Pack.
Unit
Switched-Mode Power Supply,
12 V DC / 15 A
787-831
1
Technical Data
110 ... 240 VAC
85 ... 264 VAC; 120 ... 350 VDC
(use of DC requires external protection)
-1.5 % / V AC < 110 VAC
50 Hz ... 60 Hz
0.9 A at 240 VAC and 15 ADC
1 mA typ.
< 8 A (active inrush current limitation)
30 ms typ. at 230 VAC
12 VDC, SELV
11 ... 18 VDC adjustable
15 A at 12 V DC
30 ADC (for 4 s); 22.5 ADC (for 8 s)
55 ADC (for 25 ms)
12 VDC
1%
< 70 mV (peak-peak)
1.1 x Io typ.
TopBoost / PowerBoost /Constant current
LED green (Vo), LED red (error)
Relay contact DC O.K. (changeover
contact)
Environmental requirements:
Ambient operating temperature
Storage temperature
Rel. humidity
Derating
Degree of pollution
Climatic category
Safety and protection:
Test voltage
PRI-SEC / PRI-GND / SEC-GND
Protection class
Degree of protection
Overvoltage protection
Short circuit protection
No-load proof
Feedback voltage
Parallel operation
Series connection
Connection and type of mounting:
Wire connection
Cross sections
Strip lengths
87 % typ.
0.8 W (stand-by) / 4.6 W (no load) /
23.4 W (rated load)
6.3 AT
6 A, 10 A and 16 A circuit breakers,
B and C characteristics
An external DC fuse is required for DC
input voltage.
Type of mounting
Dimensions and weight:
Dimensions (mm) W x H x L
Weight
Standards and approvals:
Standards/Specifications
-25 °C ... +70 °C
-25 °C ... +85 °C
30 % ... 85 % (no condensation)
-3 % / K (> +50 °C)
2 (acc. to EN 50178)
3K3 (acc. to EN 60721)
4.2 kVDC / 2.2 kVDC / 0.7 kVDC
Prepared for class I equipment
IP20 (acc. to EN 60529)
Varistor at primary circuit
yes
yes
max. 25 V DC
yes
yes
Input/Output: WAGO 231 Series
Signalising: WAGO 733 Series
Input/Output:
0.08 ... 2.5 mm² / AWG 28 ... 12
Signalising: 0.08 ... 0.5 mm² / AWG 28 ... 20
Input/Output: 8 ... 9 mm / 0.33 in
Signalising: 5 ... 6 mm / 0.22 in
DIN-rail mounting (EN 60715) in 2
positions
57 x 163 x 179
(incl. female connector)
Length from upper-edge of DIN 35 rail
1480 g
EN 60950, EN 61204-3, UL 60950,
UL 508
787-818
4
Switched-Mode Power Supply
EPSITRON® - PRO - Power
INTERFACE ELECTRONIC
83
Stand-by
DC O.K.
L
DC+
DC+
DC DC -
N
• Primary switch mode power supply with PowerBoost and TopBoost
• Stand-by input for switching off the output and minimizing power
consumption
• DC OK contact for output monitoring
• Parallel operation, series connection possible
• Prepared for class I equipment
• Natural convection cooling when horizontally mounted
• Enclosed for use in switchgear cabinets
Technical Data
Input:
Nominal input voltage Vi nom
Input voltage range
Input voltage derating
Frequency
Input current Ii
Discharge current
Inrush current
Mains failure hold-up time
Output:
Nominal output voltage Vo nom
Output voltage range
Output current Io
PowerBoost
TopBoost
Factory preset
Adjustment accuracy
Residual ripple
Current limitation
Overload behavior
Operational indication
Signaling
Efficiency / power losses:
Efficiency
Power loss PV
Fuse protection:
Internal fuse
External fuse
Description
Item No.
Pack.
Unit
Switched-Mode Power Supply,
24 V DC / 3 A
787-818
1
Technical Data
100 ... 240 VAC
85 ... 264 VAC; 120 ... 350 VDC
(use of DC requires external protection)
-5 % / V AC < 95 VAC
50 Hz ... 60 Hz
0.51 A at 230 VAC and 3 ADC
1 mA typ.
< 30 A (peak)
70 ms typ. at 230 VAC
24 VDC, SELV
22 ... 29.5 VDC adjustable
3 A at 24 V DC
6 ADC (for 4 s); 4.5A DC (for 8 s)
14 A DC (for 25 ms)
24 VDC
1%
< 70 mVpp
1.1 x Io typ.
TopBoost / PowerBoost /Constant current
LED green (Vo), LED red (error)
Relay contact DC O.K. (changeover
contact)
Environmental requirements:
Ambient operating temperature
Storage temperature
Rel. humidity
Derating
Degree of pollution
Climatic category
Safety and protection:
Test voltage
PRI-SEC / PRI-GND / SEC-GND
Protection class
Degree of protection
Overvoltage protection
Short circuit protection
No-load proof
Feedback voltage
Parallel operation
Series connection
Connection and type of mounting:
Wire connection
Cross sections
Strip lengths
87.8 % typ.
0.5 W (stand-by) / 3.0 W (no load) /
8.8 W (rated load)
2 AT
6 A, 10 A and 16 A circuit breakers,
B and C characteristics
An external DC fuse is required for DC
input voltage.
Type of mounting
Dimensions and weight:
Dimensions (mm) W x H x L
Weight
Standards and approvals:
Standards/Specifications
-25 °C ... +70 °C
-25 °C ... +85 °C
30 % ... 85 % (no condensation)
-3 % / K (> +50 °C)
2 (acc. to EN 50178)
3K3 (acc. to EN 60721)
4.2 kVDC / 2.2 kVDC / 0.7 kVDC
Prepared for class I equipment
IP20 (acc. to EN 60529)
Varistor at primary circuit
yes
yes
max. 35 V DC
yes
yes
Input/Output: WAGO 231 Series
Signalising: WAGO 733 Series
Input/Output:
0.08 ... 2.5 mm² / AWG 28 ... 12
Signalising: 0.08 ... 0.5 mm² / AWG 28 ... 20
Input/Output: 8 ... 9 mm / 0.33 in
Signalising: 5 ... 6 mm / 0.22 in
DIN-rail mounting (EN 60715) in 2
positions
40 x 163 x 163
(incl. female connector)
Length from upper-edge of DIN 35 rail
960 g
EN 60950, EN 61204-3, UL 60950,
UL 508
787-834
4
EPSITRON® - PRO - Power
INTERFACE ELECTRONIC
84
Switched-Mode Power Supply
Stand-by
DC O.K.
L
DC+
DC+
DC DC -
N
• Primary switch mode power supply with PowerBoost and TopBoost
• Stand-by input for switching off the output and minimizing power
consumption
• DC OK contact for output monitoring
• Parallel operation, series connection possible
• Prepared for class I equipment
• Natural convection cooling when horizontally mounted
• Enclosed for use in switchgear cabinets
Technical Data
Input:
Nominal input voltage Vi nom
Input voltage range
Input voltage derating
Frequency
Input current Ii
Discharge current
Inrush current
Mains failure hold-up time
Output:
Nominal output voltage Vo nom
Output voltage range
Output current Io
PowerBoost
TopBoost
Factory preset
Adjustment accuracy
Residual ripple
Current limitation
Overload behavior
Operational indication
Signaling
Efficiency / power losses:
Efficiency
Power loss PV
Fuse protection:
Internal fuse
External fuse
Description
Item No.
Pack.
Unit
Switched-Mode Power Supply,
24 V DC / 20 A
787-834
1
Technical Data
110 ... 240 VAC
85 ... 264 VAC; 120 ... 350 VDC
(use of DC requires external protection)
-1.5 % / V AC < 110 VAC
50 Hz ... 60 Hz
2.3 A at 230 VAC and 20 ADC
1 mA typ.
< 8 A (active inrush current limitation)
25 ms typ. at 230 VAC
24 VDC, SELV
22 ... 29.5 VDC adjustable
20 A at 24 V DC
30 ADC (for 4 s); 25 ADC (for 8 s)
80 ADC (for 25 ms)
24 VDC
1%
< 70 mV (peak-peak)
1.1 x Io typ.
TopBoost / PowerBoost /Constant current
LED green (Vo), LED red (error)
Relay contact DC O.K. (changeover
contact)
91 % typ.
0.8 W (stand-by) / 4.8 W (no load) /
50.2 W (rated load)
10 AT
10 A and 16 A circuit breakers,
B and C characteristics
An external DC fuse is required for DC
input voltage.
Environmental requirements:
Ambient operating temperature
Storage temperature
Rel. humidity
Derating
Degree of pollution
Climatic category
Safety and protection:
Test voltage
PRI-SEC / PRI-GND / SEC-GND
Protection class
Degree of protection
Overvoltage protection
Short circuit protection
No-load proof
Feedback voltage
Parallel operation
Series connection
Connection and type of mounting:
Wire connection
Cross sections
Strip lengths
Type of mounting
Dimensions and weight:
Dimensions (mm) W x H x L
Weight
Standards and approvals:
Standards/Specifications
-25 °C ... +70 °C
-25 °C ... +85 °C
30 % ... 85 % (no condensation)
-3 % / K (> +50 °C)
2 (acc. to EN 50178)
3K3 (acc. to EN 60721)
4.2 kVDC / 2.2 kVDC / 0.7kV DC
Prepared for class I equipment
IP20 (acc. to EN 60529)
Varistor at primary circuit
yes
yes
max. 35 V DC
yes
yes
Input: WAGO 231 Series
Output: WAGO 831 Series
Signalising: WAGO 733 Series
Input: 0.08 ... 2.5 mm² / AWG 28 ... 12
Output: 0.5 ... 10 mm² / AWG 20 ... 8
Signalising: 0.08 ... 0.5 mm² / AWG 28 ... 20
Input: 8 ... 9 mm / 0.33 in
Output: 13 ... 15 mm / 0.55 in
Signalising: 5 ... 6 mm / 0.22 in
DIN-rail mounting (EN 60715) in 2 positions
97 x 171 x 187
(incl. female connector)
Length from upper-edge of DIN 35 rail
2300 g
EN 60950, EN 61204-3, UL 60950*,
UL 508* (* pending)
787-833
4
Switched-Mode Power Supply
EPSITRON® - PRO - Power
INTERFACE ELECTRONIC
85
Stand-by
DC O.K.
L
DC+
DC+
DC DC -
N
• Primary switch mode power supply with PowerBoost and TopBoost
• Stand-by input for switching off the output and minimizing power
consumption
• DC OK contact for output monitoring
• Parallel operation, series connection possible
• Prepared for class I equipment
• Natural convection cooling when horizontally mounted
• Enclosed for use in switchgear cabinets
Technical Data
Input:
Nominal input voltage Vi nom
Input voltage range
Input voltage derating
Frequency
Input current Ii
Discharge current
Inrush current
Mains failure hold-up time
Output:
Nominal output voltage Vo nom
Output voltage range
Output current Io
PowerBoost
TopBoost
Factory preset
Adjustment accuracy
Residual ripple
Current limitation
Overload behavior
Operational indication
Signaling
Efficiency / power losses:
Efficiency
Power loss PV
Fuse protection:
Internal fuse
External fuse
Description
Item No.
Pack.
Unit
Switched-Mode Power Supply,
48 V DC / 5 A
787-833
1
Technical Data
110 ... 240 VAC
85 ... 264 VAC; 120 ... 350 VDC
(use of DC requires external protection)
-1.5 % / V AC < 110 VAC
50 Hz ... 60 Hz
1.2 A at 230 VAC and 5 ADC
1 mA typ.
< 8 A (active inrush current limitation)
20 ms typ. at 230 VAC
48 VDC, SELV
33 ... 52 VDC adjustable
5 A at 48 V DC
10 ADC (for 4 s); 7.5 ADC (for 8 s)
30 ADC (for 25 ms)
48 VDC
1%
< 70 mV (peak-peak)
1.1 x Io typ.
TopBoost / PowerBoost /Constant current
LED green (Vo), LED red (error)
Relay contact DC O.K. (changeover
contact)
Environmental requirements:
Ambient operating temperature
Storage temperature
Rel. humidity
Derating
Degree of pollution
Climatic category
Safety and protection:
Test voltage
PRI-SEC / PRI-GND / SEC-GND
Protection class
Degree of protection
Overvoltage protection
Short circuit protection
No-load proof
Feedback voltage
Parallel operation
Series connection
Connection and type of mounting:
Wire connection
Cross sections
Strip lengths
91 % typ.
0.8 W (stand-by) / 7.4 W (no load) /
21.6 W (rated load)
6.3 AT
6 A, 10 A and 16 A circuit breakers, B and
C characteristics
An external DC fuse is required for DC
input voltage.
Type of mounting
Dimensions and weight:
Dimensions (mm) W x H x L
Weight
Standards and approvals:
Standards/Specifications
-25 °C ... +70 °C
-25 °C ... +85 °C
30 % ... 85 % (no condensation)
-3 % / K (> +50 °C)
2 (acc. to EN 50178)
3K3 (acc. to EN 60721)
4.2 kVDC / 2.2 kVDC / 0.7 kVDC
Prepared for class I equipment
IP20 (acc. to EN 60529)
Varistor at primary circuit
yes
yes
max. 63 V DC
yes
yes
Input/Output: WAGO 231 Series
Signalising: WAGO 733 Series
Input/Output:
0.08 ... 2.5 mm² / AWG 28 ... 12
Signalising: 0.08 ... 0.5 mm² / AWG 28 ... 20
Input/Output: 8 ... 9 mm / 0.33 in
Signalising: 5 ... 6 mm / 0.22 in
DIN-rail mounting (EN 60715) in 2
positions
57 x 163 x 179 (inkl. Federleisten)
(incl. female connector)
Length from upper-edge of DIN 35 rail
1475 g
EN 60950, EN 61204-3,
UL 60950, UL 508
787-835
4
EPSITRON® - PRO - Power
INTERFACE ELECTRONIC
86
Switched-Mode Power Supply
Stand-by
DC O.K.
L
DC+
DC+
DC DC -
N
• Primary switch mode power supply with PowerBoost and TopBoost
• Stand-by input for switching off the output and minimizing power
consumption
• DC OK contact for output monitoring
• Parallel operation, series connection possible
• Prepared for class I equipment
• Natural convection cooling when horizontally mounted
• Enclosed for use in switchgear cabinets
Technical Data
Input:
Nominal input voltage Vi nom
Input voltage range
Input voltage derating
Frequency
Input current Ii
Discharge current
Inrush current
Mains failure hold-up time
Output:
Nominal output voltage Vo nom
Output voltage range
Output current Io
PowerBoost
TopBoost
Factory preset
Adjustment accuracy
Residual ripple
Current limitation
Overload behavior
Operational indication
Signaling
Efficiency / power losses:
Efficiency
Power loss PV
Fuse protection:
Internal fuse
External fuse
Description
Item No.
Pack.
Unit
Switched-Mode Power Supply,
48 V DC / 10 A
787-835
1
Technical Data
110 ... 240 VAC
85 ... 264 VAC; 120 ... 350 VDC
(use of DC requires external protection)
-1.5 % / V AC < 110 VAC
50 Hz ... 60 Hz
2.3 A at 230 VAC and 10 ADC
1 mA typ.
< 8 A (active inrush current limitation)
20 ms typ. at 230 VAC
48 VDC, SELV
33 ... 52 VDC adjustable
10 A at 48 V DC
17.5 ADC (for 4 s); 15 ADC (for 8 s)
60 ADC (for 25 ms)
48 VDC
1%
< 70 mV (peak-peak)
1.1 x Io typ.
TopBoost / PowerBoost /Constant current
LED green (Vo), LED red (error)
Relay contact DC O.K. (changeover
contact)
91 % typ.
0.8 W (stand-by) / 4.8 W (no load) /
43.2 W (rated load)
10 AT
10 A and 16 A circuit breakers,
B and C characteristics
An external DC fuse is required for DC
input voltage.
Environmental requirements:
Ambient operating temperature
Storage temperature
Rel. humidity
Derating
Degree of pollution
Climatic category
Safety and protection:
Test voltage
PRI-SEC / PRI-GND / SEC-GND
Protection class
Degree of protection
Overvoltage protection
Short circuit protection
No-load proof
Feedback voltage
Parallel operation
Series connection
Connection and type of mounting:
Wire connection
Cross sections
Strip lengths
Type of mounting
Dimensions and weight:
Dimensions (mm) W x H x L
Weight
Standards and approvals:
Standards/Specifications
-25 °C ... +70 °C
-25 °C ... +85 °C
30 % ... 85 % (no condensation)
-3 % / K (> +50 °C)
2 (acc. to EN 50178)
3K3 (acc. to EN 60721)
4.2 kVDC / 2.2 kVDC / 0.7 kVDC
Prepared for class I equipment
IP20 (acc. to EN 60529)
Varistor at primary circuit
yes
yes
max. 63 V DC
yes
yes
Input: WAGO 231 Series
Output: WAGO 831 Series
Signalising: WAGO 733 Series
Input: 0.08 ... 2.5 mm² / AWG 28 ... 12
Output: 0.5 ... 10 mm² / AWG 20 ... 8
Signalising: 0.08 ... 0.5 mm² / AWG 28 ... 20
Input: 8 ... 9 mm / 0.33 in
Output: 13 ... 15 mm / 0.55 in
Signalising: 5 ... 6 mm / 0.22 in
DIN-rail mounting (EN 60715) in 2 positions
97 x 171 x 187
(incl. female connector)
Length from upper-edge of DIN 35 rail
2460 g
EN 60950, EN 61204-3, UL 60950*,
UL 508* (* pending)
787-845
4
Switched-Mode Power Supply
EPSITRON® - PRO - Power
L1
Stand-by
DC O.K.
DC+
DC+
DC DC -
L2
L3
• Primary switch mode power supply with PowerBoost and TopBoost
• Stand-by input for switching off the output and minimizing power
consumption
• DC OK contact for output monitoring
• Parallel operation, series connection possible
• Prepared for class I equipment
• Natural convection cooling when horizontally mounted
• Enclosed for use in switchgear cabinets
Technical Data
Input:
Nominal input voltage Vi nom
Input voltage range
Frequency
Input current Ii
Discharge current
Inrush current
Mains failure hold-up time
Output:
Nominal output voltage Vo nom
Output voltage range
Output current Io
PowerBoost
TopBoost
Factory preset
Adjustment accuracy
Residual ripple
Current limitation
Overload behavior
Operational indication
Efficiency / power losses:
Efficiency
Power loss PV
Fuse protection:
Internal fuse
External fuse
INTERFACE ELECTRONIC
87
Description
Item No.
Pack.
Unit
Switched-Mode Power Supply,
48 V DC / 10 A
787-845
1
Technical Data
3x (2x) 400 ... 500 VAC
340 ... 550 VAC; 480 ... 780 VDC
50 Hz ... 60 Hz
3 x 1.1 A at 340 VAC and 10 ADC
1 mA typ.
< 30 A (peak)
12 ms typ. at 3 x 400 VAC
48 VDC, SELV
39 ... 53 VDC adjustable
10 A at 48 VDC
15 ADC (for 4 s); 12.5 ADC (for 16 s)
55 ADC (for 50 ms)
48 VDC
1%
< 70 mV (peak-peak)
1.1 x Io typ.
TopBoost / PowerBoost /Constant current
LED green (Vo), LED red (error)
93 % typ.
0.8 W (stand-by) / 8.2 W (no load) /
38 W (rated load)
3 x 3.2 AT
3 x (6 A, 10 A and 16 A) circuit breakers,
B and C characteristics
An external DC fuse is required for DC
input voltage.
Environmental requirements:
Ambient operating temperature
Storage temperature
Rel. humidity
Derating
Degree of pollution
Climatic category
Safety and protection:
Test voltage
PRI-SEC / PRI-GND / SEC-GND
Protection class
Degree of protection
Overvoltage protection
Short circuit protection
No-load proof
Feedback voltage
Parallel operation
Series connection
Connection and type of mounting:
Wire connection
Cross sections
Strip lengths
Type of mounting
Dimensions and weight:
Dimensions (mm) W x H x L
Weight
Standards and approvals:
Standards/Specifications
-25 °C ... +70 °C
-25 °C ... +85 °C
30 % ... 85 % (no condensation)
-3 % / K (> +50 °C)
2 (acc. to EN 50178)
3K3 (acc. to EN 60721)
4.2 kVDC / 2.2 kVDC / 0.7 kVDC
Prepared for class I equipment
IP20 (acc. to EN 60529)
Varistor at primary circuit
yes
yes
max. 63 V DC
yes
yes
Input: WAGO 231 Series
Output: WAGO 831 Series
Signalising: WAGO 733 Series
Input: 0.08 ... 2.5 mm² / AWG 28 ... 12
Output: 0.5 ... 10 mm² / AWG 20 ... 8
Signalising: 0.08 ... 0.5 mm² / AWG 28 ... 20
Input: 8 ... 9 mm / 0.33 in
Output: 13 ... 15 mm / 0.55 in
Signalising: 5 ... 6 mm / 0.22 in
DIN-rail mounting (EN 60715) in 2 positions
77 x 171 x 179
(incl. female connector)
Length from upper-edge of DIN 35 rail
1900 g
EN 60950, EN 61204-3, UL 60950*,
UL 508* (* pending)
787-847
4
EPSITRON® - PRO - Power
INTERFACE ELECTRONIC
88
Switched-Mode Power Supply
L1
Stand-by
DC O.K.
DC+
DC+
DC DC -
L2
L3
• Primary switch mode power supply with PowerBoost and TopBoost
• Stand-by input for switching off the output and minimizing power
consumption
• DC OK contact for output monitoring
• Parallel operation, series connection possible
• Prepared for class I equipment
• Natural convection cooling when horizontally mounted
• Enclosed for use in switchgear cabinets
Technical Data
Input:
Nominal input voltage Vi nom
Input voltage range
Frequency
Input current Ii
Discharge current
Inrush current
Mains failure hold-up time
Output:
Nominal output voltage Vo nom
Output voltage range
Output current Io
PowerBoost
TopBoost
Factory preset
Adjustment accuracy
Residual ripple
Current limitation
Overload behavior
Operational indication
Efficiency / power losses:
Efficiency
Power loss PV
Fuse protection:
Internal fuse
External fuse
Description
Item No.
Pack.
Unit
Switched-Mode Power Supply,
48 V DC / 20 A
787-847
1
Technical Data
3x (2x) 400 ... 500 VAC
340 ... 550 VAC; 480 ... 780 VDC
50 Hz ... 60 Hz
3 x 2.0 A at 340 VAC and 20 ADC
1 mA typ.
< 30 A (peak)
15 ms typ. at 3 x 400 VAC
48 VDC, SELV
39 ... 53 VDC adjustable
20 A at 48 VDC
30 ADC (for 4 s); 25 ADC (for 16 s)
80 ADC (for 25 ms)
48 VDC
1%
< 70 mV (peak-peak)
1.1 x Io typ.
TopBoost / PowerBoost /Constant current
LED green (Vo), LED red (error)
94.4 % typ.
0.8 W (stand-by) / 5.2 W (no load) /
59.2 W (rated load)
3 x 3.2 AT
3 x (6 A, 10 A and 16 A) circuit breakers,
B and C characteristics
An external DC fuse is required for DC
input voltage.
Environmental requirements:
Ambient operating temperature
Storage temperature
Rel. humidity
Derating
Degree of pollution
Climatic category
Safety and protection:
Test voltage
PRI-SEC / PRI-GND / SEC-GND
Protection class
Degree of protection
Overvoltage protection
Short circuit protection
No-load proof
Feedback voltage
Parallel operation
Series connection
Connection and type of mounting:
Wire connection
Cross sections
Strip lengths
Type of mounting
Dimensions and weight:
Dimensions (mm) W x H x L
Weight
Standards and approvals:
Standards/Specifications
-25 °C ... +70 °C
-25 °C ... +85 °C
30 % ... 85 % (no condensation)
-5 % / K (> +45 °C)
2 (acc. to EN 50178)
3K3 (acc. to EN 60721)
4.2 kVDC / 2.2 kVDC / 0.7 kVDC
Prepared for class I equipment
IP20 (acc. to EN 60529)
Varistor at primary circuit
yes
yes
max. 63 V DC
yes
yes
Input: WAGO 231 Series
Output: WAGO 831 Series
Signalising: WAGO 733 Series
Input: 0.08 ... 2.5 mm² / AWG 28 ... 12
Output: 0.5 ... 10 mm² / AWG 20 ... 8
Signalising: 0.08 ... 0.5 mm² / AWG 28 ... 20
Input: 8 ... 9 mm / 0.33 in
Output: 13 ... 15 mm / 0.55 in
Signalising: 5 ... 6 mm / 0.22 in
DIN-rail mounting (EN 60715) in 2 positions
128 x 171 x 205
(incl. female connector)
Length from upper-edge of DIN 35 rail
3270 g
EN 60950, EN 61204-3,
UL 60950, UL 508
INTERFACE ELECTRONIC
4
89
787-1675
4
INTERFACE ELECTRONIC
90
Switched-Mode Power Supply with Integrated UPS Charger and Controller
EPSITRON®
ACCU
DC+ DC–
TEMP
DC+
DC+
DC–
DC–
L
IN
N
3
• Primary switch mode power supply with integrated charger and controller for
uninterruptible power supply (UPS)
• Battery control technology for smooth charging and predictive maintenance
applications
• Potential-free contacts provide function monitoring
• Buffer time can be set on-site via potentiometer
• Parameter setting and monitoring via RS-232 interface
• Prepared for class I equipment
• Natural convection cooling when horizontally mounted
• Enclosed for use in switchgear cabinets
Technical Data
Input:
Nominal input voltage Vi nom
Input voltage range
Frequency
Input current Ii
Discharge current
Inrush current
Output:
Nominal output voltage Vo nom
Output voltage range
Output current Io
Adjustment accuracy
Residual ripple
Current limitation
Buffer time
Switch-on threshold (adjustable)
Final load voltage
Recommended battery modules
Operational indication
Signaling
Remote input
LineMonitor, parameter setting
Efficiency / power losses:
Efficiency
Power loss PV
Fuse protection:
Internal fuse
REMOTE
OUT
Description
Item No.
Pack.
Unit
Switched-Mode Power Supply
with Integrated UPS Charger and
Controller, 24 VDC / 5 A
787-1675
1
Technical Data
100 ... 240 VAC; 110 ... 370 VDC
85 ... 264 VAC
45 ... 65 Hz; 0 Hz
1.1 A at 230 VAC and 5 ADC
1 mA typ.
< 30 A
24 VDC
23.0 – 28.5 VDC (mains operation)
18.5 – 27.5 VDC (battery operation)
5A
2%
< 100 mV (peak-to-peak)
1.1 x Io; TopBoost 24 A
0.5 – 20 min, IPC mode or constant
(adjustable)
22 VDC (pre-configured),
20 – 25.5 VDC
(configurable via software)
26 – 29.5 VDC temperature-controlled
(fixed or adjustable)
787-876, 787-871, 787-872, 787-873
Green LED (DC OK), yellow LED (battery
mode), red LED (warning/fault)
3 x 24 VDC signal output, 25 mA and
1 x 30 VDC isolated relay contact, 1 A
to switch off buffer operation
via RS-232 serial interface
89 % typ.
4 W (battery operation, 24 VDC, 5 A) /
15 W (mains operation,
240 VAC/24 VDC, 5 A)
4 AT (input side); Recommended backup
fuse: 6 A, 10 A, 16 A power circuit breaker
Tripping characteristic: B, C
Environmental requirements:
Ambient operating temperature
Storage temperature
Derating
Degree of pollution
Climatic category
Safety and protection:
Test voltage
PRI-SEC / PRI-GND / SEC-GND
Protection class
Reverse voltage protection
Degree of protection
Feedback voltage
Parallel operation
Connection and type of mounting:
Wire connection
Cross sections
Strip lengths
Type of mounting
Dimensions and weight:
Dimensions (mm) W x H x L
Weight
Standards and approvals:
Standards/Specifications
-25 °C ... +70 °C
-40 °C ... +85 °C
-3 % / K (> +50 °C)
2 (acc. to EN 50178)
3K3 (acc. to EN 60721)
4.2 kVDC / 2.2 kVDC /0.7 kVDC
I
yes
IP20 (acc. to EN 60529)
max. 35 VDC
yes, max. 3 battery modules for buffer time
extension
Input/Output/Signals:
WAGO 721 Series
Interface:
WAGO 733 Series
Input/Output/Signals:
0.08 ... 2.5 mm² / AWG 28 ... 12
Interface:
0.08 ... 0.5 mm² / AWG 28 ... 20
Input/Output/Signals:
8 ... 9 mm / 0.33 in
Interface:
5 ... 6 mm / 0.22 in
DIN-rail mount (EN 60715)
60 x 127 x 135.5
Length from upper-edge of DIN 35 rail
440 g
EN 60950, UL 60950*, UL 508*,
EN 61000-6-2, EN 61000-6-3
(* pending)
787-876
4
Lead Gel Battery Module
EPSITRON®
INTERFACE ELECTRONIC
91
Temp
NTC
15 AT
DC–
Temp
DC+
• Lead-acid Absorbed Glass Mat (AGM) battery module for uninterruptible
power supply (UPS)
• Can be connected to both 787-870 UPS Controller and power supply with
integrated UPS charger and controller
• Parallel connections to increase the buffer time*
• With built-in NTC K164 (4.7 kOhm) temperature sensor
• DIN 35 mountable rail fastener
• also available with battery control** for battery life monitoring
Description
Item No.
Pack.
Unit
Lead Gel Battery Module
787-876
1
** from manufacturing no. 216570
System Data
Input:
Nominal input voltage Vi nom
Output:
Nominal output voltage Vo nom
Output current Io
Final load voltage
Charging current
Capacity
Fuse protection:
Internal fuse
Technical Data
24 VDC
24 VDC
max. 7.5 A
max. 27 VDC (at 25 °C)
max. 0.3 A
1.2 Ah
15 AT (Type FK 2)
Environmental requirements:
Ambient operating temperature
Storage temperature
Service life
Safety and protection:
Temperature sensor
Protection class
Degree of protection
Connection and type of mounting:
Wire connection
Cross sections
Strip lengths
Type of mounting
Dimensions and weight:
Dimensions (mm) W x H x L
Weight
Standards and approvals:
Standards/Specifications
* for parallel connection, please switch battery capacity setting to “OFF” in the UPS
charger and controller.
-10 °C ... +40 °C
-20 °C ... +40 °C
typ. 5/ 4/ 2 years at
20 °C/ 30 °C/ 40 °C
NTC K164 (4.7 kΩ)
III
IP20 (acc. to EN 60529)
Input/Output: WAGO 721 Series
Temperatur sensor: WAGO 733 Series
Input/Output:
0.08 ... 2.5 mm² / AWG 28 ... 12
Temperature sensor:
0.08 ... 2.5 mm² / AWG 28 ... 12
Input/Output: 8 ... 9 mm / 0.33 in
Temperature sensor: 8 ... 9 mm / 0.33 in
DIN-rail mount (EN 60715)
55 x 153 x 126 (136.5)**
Height, incl. female connector,
Length from upper-edge of DIN 35 rail
** from manufacturing no. 216570
1800 g
Battery is tested to VdS
787-1664
4
INTERFACE ELECTRONIC
92
Electronic Circuit Breaker
EPSITRON®
ON
13
DC 24V (+)
14
2..10A
2..10A
2..10A
2..10A
OUT1 (+)
OUT1 (+)
OUT1 (+)
OUT1 (+)
0V
0V
• Compact 4-channel electronic circuit breaker
• 2–10 A nominal current, adjustable for each channel via sealable selector
switch
• Switch-on capacity > 50000 μF per channel
• One illuminated bi-color button per channel simplifies switching (on/off), resetting and on-site diagnosing
• Time-delayed switching of channels
• 24 VDC output as group message (triggered channel)
• 24 VDC output as channel status message (pulse sequence)
• Remote input resets tripped channels or switching on/off any number of
channels via pulse sequence
Technical Data
Input:
Nominal input voltage Vi nom
Input voltage range
Output:
Nominal output voltage Vo nom
Nominal current
Voltage drop
Trip time
Switch-on capacity
Switch-on behavior
Operational indication
Signaling
Remote input
Efficiency / power losses:
Efficiency
Power loss PV
Fuse protection:
Internal fuse
Description
Item No.
Pack.
Unit
Electronic Circuit Breaker,
24VDC / 4 x 10 A
787-1664
1
Technical Data
24 VDC
18 ... 30 VDC
4 x 24 VDC
max. 4 x 10 ADC
(2, 3, 4, 6, 8, 10 A adjustable for each
channel via selector switch)
200 mV at 10 A
Load-dependent (20 ms – 100 s)
> 50000 μF per channel
Time-delayed channel switching
(50 – 100 ms each)
Green LED (channel OK),
Red LED (channel triggered)
4 x LED (green/red)
1 x 24 VDC group message , 1 x 24 VDC
status message (pulse sequence)
Reactivation of all tripped channels via
15 – 30 VDC pulse for min. 500 ms.
Switching on/off any number of channels
via pulse sequence.
99 % typ.
1.3 W (stand-by) / 20 W (nominal load)
Environmental requirements:
Ambient operating temperature
Storage temperature
Rel. humidity
Derating
Safety and protection:
Test voltage
Protection class
Reverse voltage protection
Degree of protection
Overload protection
Feedback voltage
Series connection of several devices
Parallel operation of single channels
Connection and type of mounting:
Wire connection
Cross sections
Strip lengths
15 AT per channel
Type of mounting
Dimensions and weight:
Dimensions (mm) W x H x L
Weight
Standards and approvals:
Standards/Specifications
-25 °C ... +70 °C
-25 °C ... +85 °C
30 % ... 85 % (no condensation)
-3 % / K (> +50 °C)
500 VDC (terminals to enclosure)
III
no
IP20 (acc. to EN 60529)
via 33 V suppressor diode at input
max. 35 VDC
not permitted
not permitted
Input:
WAGO 831 Series
Input/Output:
WAGO 721 Series
Input:
0.5 ... 10 mm² / AWG 20 ... 8
Input/Output:
0.08 ... 2.5 mm² / AWG 28 ... 12
Input:
13 ... 15 mm / 0.55 in
Input/Output:
8 ... 9 mm / 0.33 in
DIN-rail mount (EN 60715)
45 x 90 x 115,5
Length from upper-edge of DIN 35 rail
170 g
UL 60950*, UL 508*, UL 2367*, GL*,
EN 60950, EN 61000-6-2,
EN 61000-6-3
(* pending)
787-1668
4
Electronic Circuit Breaker
EPSITRON®
INTERFACE ELECTRONIC
93
ON
13
DC 24V (+)
14
2..10A
2..10A
2..10A
2..10A
2..10A
2..10A
2..10A
2..10A
OUT1 (+)
OUT2 (+)
OUT3 (+)
OUT4 (+)
OUT5 (+)
OUT6 (+)
OUT7 (+)
OUT8 (+)
0V
0V
• Compact 8-channel electronic circuit breaker
• 2–10 A nominal current, adjustable for each channel via sealable selector
switch
• Switch-on capacity > 50000 μF per channel
• One illuminated bi-color button per channel simplifies switching (on/off), resetting and on-site diagnosing
• Time-delayed switching of channels
• 24 VDC output as group message (triggered channel)
• 24 VDC output as channel status message (pulse sequence)
• Remote input resets tripped channels or switching on/off any number of
channels via pulse sequence
Technical Data
Input:
Nominal input voltage Vi nom
Input voltage range
Output:
Nominal output voltage Vo nom
Nominal current
Voltage drop
Trip time
Switch-on capacity
Switch-on behavior
Operational indication
Signaling
Remote input
Efficiency / power losses:
Efficiency
Power loss PV
Fuse protection:
Internal fuse
Description
Item No.
Pack.
Unit
Electronic Circuit Breaker,
24VDC / 8 x 10 A
787-1668
1
Technical Data
24 VDC
18 ... 30 VDC
8x 24 VDC
max. 8 x 10 ADC
(2, 3, 4, 6, 8, 10 A adjustable for each
channel via selector switch)
200 mV at 10 A
Load-dependent (20 ms – 100 s)
> 50000 μF per channel
Time-delayed channel switching
(50 – 100 ms each)
Green LED (channel OK),
Red LED (channel triggered)
8 x LED (green/red)
1 x 24 VDC group message , 1 x 24 VDC
status message (pulse sequence)
Reactivation of all tripped channels
via 15 – 30 VDC pulse for min. 500 ms.
Switching on/off any number of channels
via pulse sequence.
99 % typ.
1.3 W (stand-by) / 20 W (nominal load)
Environmental requirements:
Ambient operating temperature
Storage temperature
Rel. humidity
Derating
Safety and protection:
Test voltage
Protection class
Reverse voltage protection
Degree of protection
Overload protection
Feedback voltage
Series connection of several devices
Parallel operation of single channels
Connection and type of mounting:
Wire connection
Cross sections
Strip lengths
15 AT per channel
Type of mounting
Dimensions and weight:
Dimensions (mm) W x H x L
Weight
Standards and approvals:
Standards/Specifications
-25 °C ... +70 °C
-25 °C ... +85 °C
30 % ... 85 % (no condensation)
-3 % / K (> +50 °C)
500 VDC (terminals to enclosure)
III
no
IP20 (acc. to EN 60529)
via 33 V suppressor diode at input
max. 35 VDC
not permitted
not permitted
Input: WAGO
831 Series
Input/Output:
WAGO 721 Series
Input:
0.5 ... 10 mm² / AWG 20 ... 8
Input/Output:
0.08 ... 2.5 mm² / AWG 28 ... 12
Input:
13 ... 15 mm / 0.55 in
Input/Output:
8 ... 9 mm / 0.33 in
DIN-rail mount (EN 60715)
42 x 127 x 142,5
Length from upper-edge of DIN 35 rail
800 g
UL 60950*, UL 508*, UL 2367*, GL*,
EN 60950, EN 61000-6-2,
EN 61000-6-3
(* pending)
787-886
4
EPSITRON - Redundancy Module
INTERFACE ELECTRONIC
94
1
+
−
2
+
−
+
OUT
IN
• Redundancy module with 2 inputs for decoupling 2 power supplies
• For redundant or uninterruptible power supply
• With potential-free contact for input voltage monitoring
System Data
Input:
Nominal input voltage Vi nom
Input voltage range
Input current Ii
Output:
Nominal output voltage Vo nom
Output voltage range
Output current Io
Operational indication
Signaling
Efficiency / power losses:
Efficiency
Power loss PV
−
Description
Item No.
Pack.
Unit
Redundancy Module
48V DC, 2 x 20A / 1 x 40A
787-886
1
Technical Data
2 x 48 V DC
36 V ... 54 V DC
2 x 20 A, max. 1 x 40 A
48 V DC
Ve - 1 V DC
20 A, max. 40 A
LED green (Vo), 2 x LED yellow (Vi)
1 x floating relay contact
30 V DC, 1 A
96 % typ.
1.7 W (48 VDC/no load) /
20 W (48 VDC/rated load) (20 A) /
40 W (48 VDC/rated load) (40 A)
Fuse protection:
Internal fuse
Environmental requirements:
Ambient operating temperature
Storage temperature
Rel. humidity
Safety and protection:
Test voltage
Protection class
Reverse voltage protection
Degree of protection
Feedback voltage
Parallel operation
Connection and type of mounting:
Wire connection
Cross sections
Stripped lengths
Type of mounting
Dimensions and weight:
Dimensions (mm) W x H x L
Weight
Standards and approvals:
Standards/Specifications
no
-10 °C ... +60°C
-25 °C ... +85 °C
30 % ... 85 % (no condensation)
500 V DC (terminals to enclosure)
III
yes
IP20 (acc. to EN 60529)
max. 60 V DC
yes
Input/Output: WAGO 831 Series
Relay: WAGO 231 Series
Input/Output:
0.5 mm² ... 10 mm² / AWG 20 ... 8
Relay:
0.08 mm² ... 2.5 mm² / AWG 28 ... 12
Input/Output: 13 ... 15 mm / 0.55 in
Relay: 8 ... 9 mm / 0.33 in
DIN-rail mounting (EN 60715) in
2 positions
40 x 181 x 163
Height from upper-edge of DIN 35 rail
860 g
EN 60950, UL 60950*, UL 508*,
EN 61000-6-2, EN 61000-6-3
(* pending)
4
EPSITRON® Wall Mounting Adapter
Wall mounting adapter,
for screw fixing of 787-8xx devices on
mounting plate or wall without DIN 35 rail.
Wall mounting adapter, for screw fixing of 787-8xx
devices on mounting plate or wall without DIN 35 rail.
The wall mounting adapter replaces the rail support of the
787-8xx device.
The adapter is screwed to the 787-8xx device using one of
the provided screws.
Description
Item No.
Pack.
Unit
Wall Mounting Adapter
787-895
5
Technical Data
Material
Dimensions (mm) W x H x L
Fixing
Included:
Galvanized sheet steel
35 x 15 x 158.5
Fixing holes: 4 slots, 5.3 mm x 9 mm
Fixing hole spacing: 143 mm x 19.5 mm
Wall mounting adapter
1x screw M4 x 16
1x screw M4 x 20
1x screw M4 x 30
INTERFACE ELECTRONIC
95
4
EPSITRON® Carrier Rail Adapter
96
INTERFACE ELECTRONIC
Carrier rail adapter
for mounting 787-8xx devices to a DIN 35 rail
Carrier rail adapter for mounting 787-8xx devices to a DIN
35 rail.
The 787-896 Carrier Rail Adapter allows both vertical and
horizontal mounting of 787-8xx devices.
Mounting the adapter to the device is performed by sliding
both single parts into the guide slots of the cooling element
and then screwing, allowing the position to be changed
easily.
Description
Item No.
Pack.
Unit
Carrier Rail Adapter
787-896
1
Technical Data
Material
Dimensions (mm) W x H x L
Fixing
Included
Galvanized sheet steel
35 x 136.5 x 15.5
by sliding both single parts into the guide slot and then
screwing
Carrier rail adapter
Assembly instructions
4
EPSITRON® Carrier Rail Adapter
Carrier rail adapter
made of zinc die-cast
for mounting 787-8xx devices to a DIN 35 rail
Carrier rail adapter made of zinc die-cast for mounting
787-8xx devices to a DIN 35 rail.
The 787-897 Carrier Rail Adapter allows horizontal
mounting of 787-8xx devices.
Mounting the adapter to the device is performed by sliding
both single parts into the guide slots of the cooling element
and then screwing, allowing the position to be changed
easily.
Description
Item No.
Pack.
Unit
Carrier Rail Adapter
787-897
1
Technical Data
Material
Dimensions (mm) W x H x L
Fixing
Included
Zinc die-cast
37 x 102.5 x 10.5
by pressing the adapter into the guide slot
Carrier rail adapter
Assembly instructions
INTERFACE ELECTRONIC
97
Mobile Printer
98
DYMO RHINO 6000
Print-out preparation:
First, insert the label cartridge. To do this, open the cover on the device and insert the cartridge as shown. Ensure the cartridge visibly and audibly locks into
place. The two blue catches must latch on to the top edge of the cartridge. Then
close the cover.
Turn the unit on. A query will appear in the display about setting the material
width. Select your current label width and confirm it with "OK." The unit is now
ready for use.
Note: You can also work with the unit while it is charging.
Please use the latest driver.
Download: www.wago.com under SERVICE / Download / ProServe
Description
Item No.
Pack.
Unit
DYMO RHINO 6000 Mobile Printer
Includes: Hard carrying case, AC adapter, battery, RHINO CONNECT software
and two marking cartridges with 9 mm and 24 mm adhesive strips
258-6000
1
WAGO supplementary set for DYMO RHINO 6000
Includes: ProServe CD, ProServe flyer and quick installation guide for adding
on to an existing manual printer
258-6100
1
Item No.
Pack.
Unit
white,
11 mm width x 5.5 m
211-611
5
white,
9 mm width x 7 m
211-612
1
1
white,
19 mm width x 7 m
211-613
1
white,
9 mm width x 1,5 m
211-614
1
white,
19 mm width x 1.5 m
211-615
1
Accessories
Marking strips
Adhesive strips
Adhesive strips
Heat shrink tube
Heat shrink tube
Technical Data
Resolution
Tape sizes
Tape styles
Keyboard style
Tape cutter
Shock protection
Memory
Symbols
Barcodes
Number of font styles
Number of font sizes
Number of printed lines
Print preview
PC connection
Display
Weight
Operating time
Battery charge indicator
180 dpi
9 mm, 11 mm, 19 mm, 24 mm
(other sizes upon request)
Permanent polyester, flexible nylon, vinyl,
heat shrink tube
ABC
yes
yes
1000 labels (1 MB)
yes
yes
(e.g., Code 39, Code 128, EAN 8 + 13)
4
7
5
yes
USB
65 mm x 35 mm
approx. 3500 g
8 hours
yes
Flatbed Plotter
IP200
•
•
•
•
•
•
•
•
•
•
•
99
Rugged, aluminum construction
Plotting area, A4: 220 mm x 305 mm
Easy replacement of marker receptacles
Auto calibration
Up to 10.5 mm wide markers can be plotted
Special solutions for up to 15 mm wide markers are available
Universal power supply, 100-240 VAC
Neat plotting right from the very first marker
PC interfaces: USB ports
Command language: HPGL
IP200 firmware can be updated via PC and Internet
Description
Item No.
Pack.
Unit
Technical Data
Flatbed plotter IP 200
258-200
1
Plotting area
Interfaces
Language
Data buffer
Speed
Drive system
Plotter pen
Addressable resolution
Repeat accuracy
Repeat accuracy after pen change
Power supply
Operating voltage
Current consumption (internal)
Dimensions (mm) W x H x L
Operating temperature
Rel. humidity
Safety approvals
Immunity to interference
Included:
200 mm x 305 mm
USB Level 1.1
Based on HP-GL 7475A
16 MB
max. 40 mm/s
Two-phase step motor
Special plotter pens with HP receptacle
0.01 mm
0.05 mm
0.05 mm with optimun pen
Separate power supply with exchangeable
plug adapters
100 V ... 240 V AC / 50 Hz ... 60 Hz
0.7 A max. at 220 V AC
125 x 440 x 440
10 °C ... 35 °C
35 % ... 75 %
EN 60950-1
EN 55022 B
EN 61000-4-2 bis 6
EN 61000-4-11
IP200 Plotter,
power supply,
USB data cable,
operating manual + ProServe software
Crimping Tools
100
Crimping tool 1025
Crimping tool for insulated and uninsulated ferrules
Crimping range: 10 mm2, 16 mm2 and 25 mm2
Weight: 560 g
Item No.
Pack. Unit
Crimping tool 1025
Crimping range: 10 mm2, 16 mm2 and 25 mm2
206-225
1
Crimping tool 3550
Crimping tool for insulated and uninsulated ferrules
Crimping range: 35 mm2 and 50 mm2
Weight: 560 g
Item No.
Pack. Unit
Crimping tool 3550
Crimping range: 35 mm2 and 50 mm2
206-250
1
What is "gas-tight?"
In a gas-tight connection, the conductor and the ferrule are compressed together, eliminating all spaces. Under normal atmospheric conditions, neither a liquid nor a gaseous medium
can penetrate into the crimped connection.
Oxidation between crimped single conductors is prevented, ruling out nearly any increase in the crimped connection resistance. In some exceptional cases, minute, isolated spaces may
be present.
These instances can be considered as closed off due to twisted wires, however. Inadequate crimping can allow the conductor to be pulled out of the connection. Hollow spaces also
remain in which oxidation can form and lead to an increase in contact resistance. Elevated resistance is detrimental for signal transmission, as the signal flow is damped (weakened),
and for power transmission, as power loss and, hence a temperature increase due to contact (risk of fire) can result.
Crimping tools with built-in ratchets are recommended, such as the WAGO Variocrimp tools. These tools only open after the crimping process has been fully completed.
Space-saving crimping from all four sides is ideal for spring clamp termination. Cross section data for ferruled conductors indicated for WAGO products is based on this crimping
method.
Insert ferruled conductor into crimping station.
Squeeze handles until ratchet mechanism is released.
A perfect gastight crimp - both electrically and
mechanically reliable.
Uninsulated Ferrules
101
<D2>
<___D___>
Ferrule, uninsulated,
electro-tin plated,
electrolytic copper,
gastight crimped
<__________ L __________>
Item No.
Pack. Unit
Ferrule, uninsulated
sleeve for 25 mm² / AWG 4
25 mm strip length
L=25 mm
D=9.5 mm, D2=7.3 mm
216-413
50
Ferrule, uninsulated
sleeve for 35 mm² / AWG 2
25 mm strip length
L=25 mm
D=11 mm, D2=8.3 mm
216-414
50
Ferrule, uninsulated
sleeve for 35 mm² / AWG 2
30 mm strip length
L=30 mm
D=11 mm, D2=8.3 mm
216-424
50
Ferrule, uninsulated
sleeve for 50 mm² / AWG 1
30 mm strip length
L=30 mm
D=13 mm, D2=10.3 mm
216-425
50
Ferrule, uninsulated
sleeve for 50 mm² / AWG 1
35 mm strip length
L=35 mm
D=13 mm, D2=10.3 mm
216-435
50
Test and Measurement Tools
102
WAGO Profi LCD+
2-pole voltage tester with LCD display
WAGO Profi LED+
2-pole voltage tester with LED display
6 - 1000 V AC/DC
6 - 1000 V AC/DC
Item No.
Pack. Unit
Item No.
Pack. Unit
WAGO Profi LCD+
2-pole voltage tester with LCD display
Measuring range:
6 V ... 1000 V AC/DC
Degree of protection:
IP65
Resistance measurement:
up to 2000 Ω ,
removable test probes,
4 mm Ø
206-807
1
WAGO Profi LED+
2-pole voltage tester with LED display
Measuring range:
6 V ... 1000 V AC/DC,
Degree of protection:
IP65
Resistance measurement:
up to 2000 Ω ,
removable test probes,
4 mm Ø
206-806
1
Additional product features for WAGO Profi LCD+:
• Automatic measurement range selection
• Single-pole phase testing AC >100 V
• Two-pole sequence testing (R and L)
• Continuity testing
• FI/RCD testing (30 mA) via buttons
• One-hand operation for SCHUKO and CEE sockets
• LED torch lamp function
• Automatic backlight
• Auto power-off function
• CAT IV 1000 V
• TÜV/GS tested and approved
• IEC/EN 61243-3 (DIN VDE 0682-401)
Additional product features for WAGO Profi LED+:
• Automatic measurement range selection
• Single-pole phase testing AC >100 V
• Two-pole sequence testing (R and L)
• Continuity testing
• FI/RCD testing (30 mA) via buttons
• One-hand operation for SCHUKO and CEE sockets
• LED torch lamp function
• CAT IV 1000 V
• TÜV/GS tested and approved
• IEC/EN 61243-3 (DIN VDE 0682-401)
WAGO Profi LCD+ and WAGO Profi LED+
- Improved socket contact via 4 mm test probes
- Removable test probes for small test ports (suitable for all
WAGO terminal blocks)
103
WAGO Multi Tester
Digital multimeter
WAGO Amp Tester
Digital clamp meter
600 V AC/DC
10 A AC/DC
0.01 - 200 A AC/DC
Item No.
Pack. Unit
WAGO Multi Tester
Digital multimeter with contact-less voltage tester
Measuring range:
600 V AC/DC
10 A AC/DC
Resistance measurement:
up to 20 MΩ
Includes:
carrying case
206-810
1
Additional product features for WAGO Multi Tester:
• Contact-less voltage test AC >100 V (optical and
acoustical)
• Resistance measurement up to 20 MΩ
• Acoustical continuity test
• Diode test
• Data hold function
• Auto power-off function
• LED torch lamp function
• CAT IV 600 V
• TÜV/GS tested and approved
• IEC/EN 61010-1 (DIN VDE 0411)
Item No.
Pack. Unit
WAGO Amp Tester
Digital clamp meter
Measuring range:
0.01 A ... 200 A AC/DC
Degree of protection:
IP44
True RMS measuring method
Includes:
carrying case
206-815
1
Additional product features for WAGO Amp Tester:
• AC and DC current measurement
• True RMS measurement
• Data hold function
• Maximum jaw opening: 21 mm Ø
• Compact design for measuring in tight spaces
• Resolution: 0.01 A at 40 A
• Resolution: 0.1 A at 200 A
• Sampling rate: 3 times per second
• Auto power-off function
• CAT III 300 V
• TÜV/GS tested and approved
• IEC/EN 61010-1 (DIN VDE 0411)
Item Number Index
104
16 Bit)
Item No.
Page
206 Series
Item No.
Page
734 Series
206-225
206-250
100
100
734-103
734-603
206-806
206-807
206-810
206-815
102
102
103
103
753 Series
753-620
753-647
753-648
98
98
98
98
98
40
40
9
6
4
758 Series
758-916
758-917
18
18
759 Series
216 Series
216-413
216-414
216-424
216-425
216-435
759-302
759-333
101
101
101
101
101
248-501
10
12
14
16
4
770 Series
258 Series
258-200
99
258-6000
258-6100
98
98
289 Series
289-965
289-966
6
4
40
40
706 Series
706-100/1300-200
706-100/1301-200
706-100/1303-200
706-100/1602-200
24
25
25
24
706-753/300-100
706-753/300-200
706-753/300-300
706-753/301-100
706-753/301-200
706-753/301-300
26
26
26
26
26
26
706-7753/300-100
706-7753/301-200
706-7753/304-100
706-7753/304-200
706-7753/304-300
706-7753/306-100
706-7753/306-200
706-7753/306-300
19
19
27
27
27
27
27
27
787-818
787-819
787-821
787-831
787-833
787-834
787-835
787-845
787-847
787-876
787-886
787-895
787-896
787-897
83
80
81
82
85
84
86
87
88
91
94
95
96
97
787-1001
787-1007
787-1011
787-1002
787-1012
787-1021
787-1022
74
8
75
77
78
76
79
787-1664
787-1668
787-1675
92
93
90
788 Series
788-341
788-342
788-344
788-346
788-347
788-349
28
28
28
28
28
28
29
29
29
29
29
29
30
770-103
770-114
48
48
770-244
48
770-514
48
788-541
788-543
788-544
788-546
788-548
788-549
770-629/130-000
48
788-721
770-633
48
770-5001/100-000
48
Item No.
Page
857 Series
767 Series
767-1311
767-3806
767-4808
767-5401
248 Series
Page
787 Series
211 Series
211-611
211-612
211-613
211-614
211-615
Item No.
857-402
857-411
857-412
857-413
857-414
857-415
857-416
857-450
50
52
52
52
52
52
52
54
857-500
857-550
857-552
56
60
62
857-809
857-818
857-820
64
68
70
857-979
72
857-1330
20
857-1430
857-1432
857-1494
21
22
21
858 Series
858-324
858-325
858-327
858-328
858-390
858-391
858-392
32
32
32
32
32
32
32
858-528
33
789 Series
789-325
789-329
36
37
789-620
789-621
789-622
789-652
40
42
44
46
789-912
789-913
38
39
789-1341
789-1346
789-1544
789-1549
34
34
35
35
Products highlighted in RED are new items for Spring 2012
105
106
WAGO Worldwide
– Companies and Representatives –
Argentina
Bruno Schillig S.A.
Arenales 4030, B1604CFD
Florida, PBA
Phone +54 11 4730 1100
Fax +54 11 4761 7244
wago@schillig.com.ar
Croatia
GENERA CTR d.o.o.
- just for automation technology Siget 18 b
10020 Zagreb
Phone +385 13647849
Fax +385 13636662
wago@geneza.hr
Australia
Kontact Group
Building Automation & WINSTA Systems
Office: 730 Springvale Rd
Mulgrave Victoria 3170
P.O. Box 3003, Wheelers Hill VIC 3150
Tel. +61 03 95602757
Fax +61 03 95601727
sales@kontactgroup.com.au
NHP ELECTRICAL ENGINEERING
PRODUCTS PTY LTD
43-67 River Street
Richmond, Victoria, 3121, P.O. Box 199
Phone +61 3 9429 2999
Fax +61 3 9429 1075
export@wago.com
Austria
WAGO Kontakttechnik Ges.m.b.H.
Laxenburger Straße 244
1230 Wien
Phone +43 1 6150780
Fax +43 1 6150775
info.at@wago.com
Azerbaijan
AZ Technics LTD
Zulfi V. Alizade
Y.Safarov str.33 , AZ1025,
Baku
Republic of Azerbaijan
Tel. +994 12 4968335
Fax +994 12 4968334
info@AZtechnics.az
Belarus
UP FEK
pr-t Pushkina 29-B
220015 Minsk
Phone +375 17 2102189
Fax +375 17 2102189
wago@fek.by
Belgium
WAGO Kontakttechnik
Excelsiorlaan 11
1930 Zaventem
Phone +32 2 7179090
Fax +32 2 7179099
info-be@wago.com
Bosnia and Herzegovina
please contact WAGO Bulgaria
Brazil
WAGO Eletroeletrônicos Ltda
Rua Américo Simões 1470
São Roque da Chave
Itupeva SP Brasil 13295-000
Phone +55 11 4591 0199
Fax +55 11 4591 0190
info.br@wago.com
Bulgaria
WAGO Kontakttechnik GmbH & Co. KG
Business Center Serdika
2E Akad. Ivan Geshov Blvd.
Building 1, Floor 4, Office 417
1330 Sofia
Phone +359 2 489 46 09
Fax +359 2 928 28 50
info-BG@wago.com
Canada
please contact WAGO USA
Chile
Desimat Chile
Av Puerto Vespucio 9670
Pudahuel Santiago
Phone +56 2 7470152
Fax +56 2 7470153
ventaschile@desimat.cl
China
WAGO ELECTRONIC (TIANJIN) Co. LTD
No.5, Quan Hui Road, Wuqing Development Area
Tianjin 301700
Phone +86 22 59617688
Fax +86 22 59617668
info-cn@wago.com
Czech Republic
WAGO Elektro spol. sr. o.
Rozvodova 1116/36
143 00 Praha 4 - Modřany
Phone +420 261 090 143
Fax +420 261 090 144
info.cz@wago.com
Denmark
WAGO Danmark
Filial of WAGO Kontakttechnik GmbH & Co. KG
Lejrvej 17
3500 Værløse
Phone +45 44 357777
Fax +45 44 357787
salg.dk@wago.com
Ecuador
ECUAINSETEC CIA LTDA
El Zurriago 177 y El Vengador
P.O. Box 17-16-016
Quito
Phone +593 2 2 26 91 48
Fax +593 2 2 46 18 33
g.castro@ecuainsetec.com.ec
Egypt
IBN Engineering Instrumentation & Control
71 a El Shaheed Ahmed Hamdi St.
King Faisal, Giza
Phone +20 2 7214350
Fax +20 2 7221709
sales@ibnengineering.com
Estonia
Eltarko OÜ
Laki 14 - 502
10621 Tallinn
Phone +372 651 7731
Fax +372 651 7786
andres@eltarko.ee
Finland
WAGO Kontakttechnik GmbH & Co. KG
Filial i Finland
Vellamonkatu 30 B
00550 Helsinki
Phone +358 9 7744 060
Fax +358 9 7744 0660
tilaus@wago.fi
Iceland
S. Gudjonsson ehf.
Audbrekku 9-11
202 Kopavogur
Phone +354 520-4500
Fax +354 520-4501
export@wago.com
India
WAGO & CONTROLS (INDIA) LTD.
C-27, Sector-58, Phase-III
Noida-201 301
Gautam Budh Nagar (U.P)
Phone +91 120 2 580409 10
Fax +91 120 2 580081
info@wagoindia.com
Indonesia
please contact WAGO Singapore
Iraq
please contact WAGO Middle East
Iran
Patsa Industry
No. 2 Bahar St.
South Shiraz Ave
P.O. Box.: 15875-1698
14369 Tehran
Phone +98 21 88047626
Fax +98 21 88040886
info.uae@wago.com
Ireland
Drives & Controls
Unit F4, Riverview Business Park
Nangor Road
Dublin 12
Phone +353 1 4604474
Fax +353 1 4604507
wago@drivesandcontrols.ie
Israel
Comtel Israel Electronic Solutions Ltd.
Bet Hapaamon
20 Hataas Street
P.O. Box 66
44425 Kefar-Saba
Phone +972 9 76 77 240
Fax +972 9 76 77 243
sales@comtel.co.il
Italy
WAGO ELETTRONICA SRL
Via Parini 1
40033 Casalecchio di Reno (BO)
Phone +39 051 6132112
Fax +39 051 6272174
info-ita@wago.com
France
WAGO CONTACT SAS
Paris Nord 2
83 Rue des Chardonnerets
B.P. 55065 - Tremblay en France
95947 - ROISSY CDG CEDEX
Phone +33 1 48172590
Fax +33 1 48632520
info-fr@wago.com
Japan
WAGO Co. of JAPAN Ltd.
Nittetsu ND-Tower Building 4F
Kameido 1-5-7
Koto-Ku
Tokyo 136-0071
Phone +81 3 5627 2050
Fax +81 3 5627 2055
info-jp@wago.com
Germany
WAGO Kontakttechnik GmbH & Co. KG
Postfach 28 80, 32385 Minden
Hansastraße 27
32423 Minden
Phone +49 571 887-0
Fax +49 571 887-169
info@wago.com
Kazakhsta
TOO INTANT
ul. Muratbaeva, d. 61
050026 Almaty
Phone +7 727 2371492
Fax +7 727 2980151
info@intant.kz
WAGO Kontakttechnik GmbH & Co. KG
Waldstraße 1
99706 Sondershausen
Phone +49 3632 659-0
Fax +49 3632 659-100
info@wago.com
Great Britian
WAGO Limited
Triton Park, Swift Valley Industrial Estate
RUGBY
Warwickshire, CV21 1SG
Phone +44 1788 568008
Fax +44 1788 568050
uksales@wago.com
Greece
PANAGIOTIS SP. DIMOULAS - BIOMAT
DIMOULAS AUTOMATIONS
Kritis Str. 26
10439 Athen
Tel. +30 210 883 3337
Fax +30 210 883 4436
wago.info@dimoulas.com.gr
Columbia
T.H.L. Ltda.
Cra. 49 B # 91-33
Bogotá
Phone +57 1 621 85 50
Fax +57 1 621 60 28
ventas-thl@thl-ltda.com
Hong Kong
National Concord Eng., Ltd.
Unit A-B, 5/F.
Southeast Industrial Building
611-619 Castle Peak Road
Tsuen Wan, N.T.
Phone +852 24292611
Fax +852 24292164
sales@nce.com.hk
Croatia
M.B.A. d.o.o. za trgovinu i zastupanje
Frana Supila 5
51211 Matulji HR
Phone +385 51 275-736
Fax +385 51 275-066
mba@ri.htnet.hr
Hungary
WAGO Hungá¡ria KFT
Ipari Park, Gyár u. 2
2040 Budapest
Phone +36 23 502-170
Fax +36 23 502-166
info.hu@wago.com
TOO Technik-Trade
ul. i. A. Protosanova, 81
070004 Ust-Kamenogorsk
Phone +7 7232 254064
Fax +7 7232 253251
info@technik.kz
Korea
Mahani Electric Co. Ltd.
792-7 Yeoksam-Dong
Kangnam-Gu, 135-080
Seoul, Korea
Phone +82 2 2194 3300
Fax +82 2 2194 3397
export@wago.com
Kosovo
please contact WAGO Bulgaria
Kuwait
Kuwait Controls Company
Al Sour Street, Above Lufthansa Airline
Safat Kuwait 13062
Phone +965 222 54300
Fax +965 224 33698
info.uae@wago.com
Latvia
INSTABALT LATVIA SIA
Vestienas iela 6
Rīga, LV-1035
Phone +371 790 1188
Fax +371 790 1180
info@instabalt.lv
Lebanon
Gemayel Trading & Contracting
Antonins Project
P.O. BOX 70-1096
Antelias, Lebanon
Phone +961 4 521 029
Fax +961 4 521 029
gtc.libanon@gmail.com
Lithuania
INSTABALT LIT UAB
Savanorių 187
Vilnius, 2053
Phone +370 52 322 295
Fax +370 52 322 247
info@instabalt.lt
Luxembourg
please contact WAGO Belgium
Macedonia
please contact WAGO Bulgaria
Malaysia
WAGO Representative Office Malaysia
No 806, Block A4, Leisure Commerce Square,
No 9, Jalan PJS 8/9, 46150 Petaling Jaya,
Selangor Darul Ehsan, Malaysia
Phone +60 3 7877 1776
Fax +60 3 7877 2776
kian.guan.tan@wago.com
HPH Materials (M) Sdn Bhd
No. 4, Jalan Nilam 1/6
Suban Hi-Tech Industrial Park
40000 Shah Alam
Selangor, D.E. Malaysia
Phone +60 3 5638 2213
Fax +60 3 5638 8213
info@hphmaterials.com
Romania
WAGO Kontakttechnik GmbH & Co. KG
WAGO Representative Office Bucharest
Str. Nicolae G. Caramfil Nr. 26, Bl. 1D, Et. 3, Ap. 7, Sect. 1, OP52
014144-Bucuresti, Romania
Tel. +40-(0)31 421 85 68
Fax +40-(0)21 232 02 31
info-ro@wago.com
VDR & Servicii srl
Str. Valeriu Branişte, nr. 60, ap.1, sector 3
Romania
Phone +40 21 3225074/76
Fax +40 21 3225075
office@componente-automatizari.ro
Russia
ООО WAGO Kontakt Rus
Gostinichny proezd 4B
127106 Moscow
Russia
Phone +7 495 9874790
Fax +7 495 9874791
info.ru@wago.com
WAGO Branch office
Ekaterinburg
Phone +7 343 216 3426
Setia Raya Teknik Sdn. Bhd.
40 & 42 Jalan SS15/4
Subang Jaya, 47500 P.J.
Selangor D.E. Malaysia
Phone +60 3 5633 5511
Fax +60 3 5633 3411
sales@setiaraya.com.my
WAGO Branch office
Novosibirsk
Phone +7 383 217 9244
Mexico
WAGO SA de CV
Av. Del Marques 38 Bodega 3
P. I. Bernardo Quintana
76240 El Marques, Querétaro
Phone +52 442 221 5946
Fax +52 442 221 5063
Toll-Free: 001-800-309-5975
info.mx@wago.com
Saudi Arabia
Ali Zaid Al Quraishi & Partners Electrical Services of S.A.
Al Quraishi Center, King Khalid Street
P.O. Box 7386
Dammam - 31462
Phone +966 3 8351155
Fax +966 3 8352297
info.uae@wago.com
Netherlands
WAGO Nederland
Laan van de Ram 19
7324 BW Apeldoorn
Phone +31 55 36 83 500
Fax +31 55 36 83 599
info-nl@wago.com
Serbia
please contact WAGO Bulgaria
New Zealand
NHP NZ
7 Lockhart Place
Mt Wellington
New Zealand
Phone +64 9 2761967
Fax +64 9 2761992
export@wago.com
Norway
WAGO Norge NUF
Jerikoveien 20
1067 Oslo
Phone +47 22 30 94 50
Fax +47 22 30 94 51
info.no@wago.com
Pakistan
FuziLogiX Automation & Control
Suit No. 14, 5th Floor, Shan Arcade
New Garden Town, Lahore
Pakistan
Phone +92 42 594 1503 - 4
Fax +92 42 585 1431
info@fuzilogix.com
Peru
Desimat Peru
Av. Velasco Astete 2371
Surco Lima
Phone +51 1 2752776
Fax +51 1 2752765
export@wago.com
Philippines
please contact WAGO Singapore
Poland
WAGO ELWAG sp. z o. o.
ul. Piękna 58 a
50-506 Wrocław
Phone +48 71 3602970
Fax +48 71 3602999
wago.elwag@wago.com
Portugal
MORGADO & CA. LDA - SEDE
Estrada Exterior da
Circunvalação 3558/3560
Apartado 1057
4435 Rio Tinto
Phone +351 22 9770600
Fax +351 22 9770699
export@wago.com
Republic of Moldova
Electroservice Slavinschi T.T.
str. Bolgarskaia 9, office 6
2001 Kishinev
Phone +373 22 274427
Fax +373 22 224481
es@es.mldnet.com
WAGO Branch office
St. Petersburg
Phone +7 812 312 1918
Tagor Electronic doo
Tihomira Brankovica 21
18000 Nis
Tel. +381 18 575545
Fax +381 18 217125
ana.aleksic@tagor.rs
Singapore
WAGO Electronic Pte Ltd
10 Upper Aljunied Link
#04-04 Johnson Controls Building
Singapore 367904
Phone +65 62866776
Fax +65 62842425
info-sing@wago.com
Slovakia
WAGO Elektrik spol. s r. o
Odborárska 52
83102 Bratislava
Tel. +421 2 4569 2503
export@wago.com
Proelektro spol. s r.o.
Na barine 22
84103 Bratislava Lamač
Tel. +421 2 4569 2503
info@wago.sk
Slovenia
GENERA d.o.o.
Prevale 10
1236 Trzin
Phone +386 14393050
Fax +386 14393090
genera@genera.si
IC elektronika d.o.o.
Vodovodna cesta 100
1000 Ljubljana
Phone +386 15680110
Fax +386 15689107
info@ic-elect.si
South Africa
Shorrock Automation (Pty) Ltd
Postnet Suite # 219
Private Bag X 8,Elardus Park
0047 Pretoria
Phone +27 12 4500300
Fax +27 12 4500322
sales@shorrock.co.za
Spain
DICOMAT S.L.
Avda. de la Industria, 36
Apartado Correos, 1.178
28108 - Alcobendas (Madrid)
Phone +34 91 6621362
Fax +34 91 6610089
info@dicomat.com
Sweden
WAGO Sverige
WAGO Kontakttechnik GmbH
Tyskland Filial
Box 639, 17527 Järfälla
Datavägen 9 A, 17543 Järfälla
Phone +46 858410680
Fax +46 858410699
info.se@wago.com
Switzerland
WAGO CONTACT SA
Rte. de l’Industrie 19
Case Postale 168
1564 Domdidier
Phone +41/26 676 75 86
Fax +41/26 676 75 01
info.switzerland@wago.com
Syria
Zahabi Co.
8/5 Shouhadaa St., P.O. Box 8262
Aleppo
Phone +963 21 21 22 235 / 6
Fax +963 21 21 24 768
info.uae@wago.com
Taiwan R.O.C.
WAGO Contact, Ltd.
5F., No.168, Jiankang Rd
Zhonghe City
Taipei County 23585, Taiwan
Phone +886 2 22250123
Fax +886 2 22251511
info.taiwan@wago.com
Thailand
WAGO Representative Office Thailand
4th Floor, KS Building
213/6-8 Rachada Phisek Road
Ding Daeng Bangkok 10320
Phone +66 2 6935611
Fax +66 2 6935612
wago@asianet.co.th
US Power Distribution Co., Ltd.
4th Floor K.S. Building
213/6-8 Rachada Phisek Road
Ding Daeng, Bangkok 10400
Phone +66 2 2763040
Fax +66 2 2763049
wago@asianet.co.th
Turkey
WAGO Elektronik Sanayi ve Ticaret Ltd. Şti.
Yukan Dudullu Mahallesi Bayraktar Bulvan
34775 Ümraniye - Istanbul
Türkiye
Tel. +90 216 472 1133
Fax +90 216 472 9910
info.tr@wago.com
Ukraine
NPP Logicon
Predslavinskaya street, 39, office 303
03150 Kiev
Phone +380 44 5228019
Fax +380 44 2611803
info@logicon.ua
OOO Mikropribor
ul. Kotelnikova, 4
03115 Kiev
Phone +380 44 5369386
Fax +380 44 5369387
sales@micropribor.kiev.ua
United Arab Emirates (UAE)
WAGO Middle East (FZC)
SAIF Zone, Q4-282
P.O. Box: 120665
Sharjah, UAE
Phone +971 6 5579920
Fax +971 6 5579921
info.uae@wago.com
USA
WAGO Corporation
N120 W19129 Freistadt Road
Germantown, WI 53022
Phone +1 262 255 6222
Fax +1 262 255 3232
Toll-Free: 1-800 DIN Rail (346-7245)
info.us@wago.com
Venezuela
PETROBORNAS, C.A.
C.C. PLAZA AEROPUERTO - PISO 1 - LOCAL P1 - B - 03
(8015) UNARE - PUERTO ORDAZ - ESTADO BOLÍVAR
REPÚBLICA BOLIVARIANA DE VENEZUELA
Tel. +58 286 994 3406
Fax +58 286 994 5249
info@petrobornas.net
Vietnam
please contact WAGO Germany (Minden)
Version: 10/2011
Current addresses at www.wago.com
107
Notes
108
109
Notes
110
111
51257931 · 0888-1002/0412-3601 · Suppl. Cat. Automation · GB · 2012/1 · Printed in Germany · Subject to design changes
Download PDF