TOSHIBA-CARRIER VRF - INDOOR EQUIPMENT SCHEDULE
VRF-2
VRF-3
WEIGHT
(LB)
MMU-AP0242H2UL
4-Way Cassette
Zone 8
73.9
62.1
70.0
20.11
13.52
2.91
670
31
208/1/60
0.8
15
48
1, 2, 3, 4, 5, 7, 8
FCU-9
MMU-AP0121MH2UL
Compact 4-Way Cassette
Zone 9
73.9
62.2
70.0
9.91
7.09
1.64
330
32
208/1/60
0.4
15
35
1, 2, 3, 4, 5, 7, 8
FCU-10
MMD-AP0094BH2UL
Medium Static Ducted
Zone 10
73.9
62.2
70.0
7.09
5.40
1.18
312
28
208/1/60
0.8
15
64
1, 2, 3, 4, 5, 7, 8, 10
FCU-11
MMD-AP0184BH2UL
Medium Static Ducted
Zone 11
74.1
62.2
70.6
15.15
12.00
3.08
635
29
208/1/60
0.9
15
93
1, 2, 3, 4, 5, 7, 8, 10
FCU-12
MMD-AP0184BH2UL
Medium Static Ducted
Zone 12
73.9
62.2
70.0
14.78
10.39
2.36
635
29
208/1/60
0.9
15
93
1, 2, 3, 4, 5, 7, 8, 10
FCU-13
MMU-AP0181MH2UL
Compact 4-Way Cassette
Zone 13
73.9
62.2
70.0
15.95
11.24
2.56
450
36
208/1/60
0.5
15
35
1, 2, 3, 4, 5, 7, 8
FCU-14
MMD-AP0724H2UL
High Static Ducted
Zone 14
74.8
62.4
74.7
49.57
45.86
34.73
2470
47
208/1/60
7.1
15
353
1, 2, 3, 4, 5, 7, 8, 10
FCU-15
MMU-AP0212H2UL
FCU-16
MMU-AP0181MH2UL
FCU-17
4-Way Cassette
Zone 15
74.6
62.4
74.5
15.43
15.39
14.63
670
31
208/1/60
0.8
15
48
1, 2, 3, 4, 5, 7, 8
Compact 4-Way Cassette
Zone 16
74.1
62.2
73.5
16.40
11.70
8.38
450
36
208/1/60
0.5
15
35
1, 2, 3, 4, 5, 7, 8
MMU-AP0182H2UL
4-Way Cassette
Zone 17
74.1
62.2
73.6
16.94
12.24
8.91
550
31
208/1/60
0.6
15
46
1, 2, 3, 4, 5, 7, 8
FCU-18
MMD-AP0364BH2UL
Medium Static Ducted
Zone 18
74.3
62.3
74.2
28.40
23.36
21.67
1088
35
208/1/60
1.8
15
119
1, 2, 3, 4, 5, 7, 8, 10
FCU-19
MMU-AP0212H2UL
4-Way Cassette
Zone 19
74.9
62.5
70.5
14.64
14.02
0.58
670
31
208/1/60
0.8
15
48
1, 2, 3, 4, 5, 7, 8
PROVIDE VRF DIRECT-EXPANSION INDOOR UNIT WITH DC INVERTER DRIVEN FAN MOTOR, PIPING CONNECTORS, PULSE MODULATING VALVE (METERING DEVICE), INTEGRAL LEAVING/RETURN TEMPERATURE SENSORS, AND HANGING BRACKETS.
2.
UNIT SHALL BE PROVIDED WITH FACTORY INSTALLED RETURN AIR TEMPERATURE SENSOR.
3.
PROVIDE INTERNAL CONTROL SYSTEM WHICH EMPLOYS AN ALGORITHM FOR TEMPERATURE CONTROL TO AN ACCURACY OF 0.9° F.
4.
PROVIDE METERING DEVICE THAT SHUTS OFF COMPLETELY WHEN THE ZONE IS SATISFIED.
RN-020-3-0-EB09-16A:UADE-U0F-DRF-D0A-DHFAHYF-00-00C0000AB
Tag: OAU-1
5000 CFM with Wheel
Job Information
Job Name:
Job Number:
Site Altitude:
Refrigerant
Unit Information
NRG Call Center
Job #1253
0 ft
R-410A
Approx. Op./Ship Weights:
Supply CFM/ESP:
Final Filter FV / Qty:
Exhaust CFM/ESP/TSP:
Outside CFM:
Ambient Temperature:
3544 / 3544 lbs. (±5%)
5000 / 1 in. wg.
240.00 fpm / 6
5000 / 0.25 / 1.49 in. wg.
5000
98 ºF DB / 80 ºF WB
1.00
0.25
0.09
0.35
0.03
Economizer:
Heating:
Cabinet:
Heatwheel:
Total:
0.11
0.11
0.05
0.95
2.93
Static Pressure
External:
Evaporator:
Filters Clean:
Dirt Allowance
Re-Heat Coil
in.
in.
in.
in.
in.
wg.
wg.
wg.
wg.
wg.
Cooling Section
5.
PROVIDE WIRED ZONE CONTROLLER RBC-AMS51E-ES.
6.
PROVIDE WIRED REMOTE SENSOR TCB-TC21LUL.
7.
PROVIDE CONDENSATE LIFT AND OVERFLOW SAFETY SWITCH.
8.
PROVIDE FACTORY SUPPLIED BRANCHING KITS CONSISTING OF EITHER Y JOINTS AND/OR HEADERS TO ENSURE EVEN REFRIGERANT FLOW.
9.
INSULATE UNITS WITH 1" RUBATEX SHEET USING AN ADHESIVE. KEEP ALL UNITS SCREWS ACCESSIBLE FOR UNIT MAINTENCE.
PROVIDE AUXILLARY DRAIN PAN UNDER UNIT AND FLOAT SWITCH. DRAIN PAN SHOULD BE A MINIMUM OF 3" LARGER THAN UNIT ON ALL SIDES.
in.
in.
in.
in.
in.
wg.
wg.
wg.
wg.
wg.
Heating Section
Equivalent Total Capacity:
Total Capacity:
Sensible Capacity:
Latent Capacity:
HW Total Cooling Capacity:
Mixed Air Temp:
Entering Air Temp:
Lv Air Temp (Coil):
Lv Air Temp (Unit)
Digital Comp. Capacity Ratio:
Supply Air Fan:
SA Fan RPM / Width:
Exhaust Air Fan:
EA Fan RPM / Width:
Gross
Net
468.42 MBH
458.81 MBH
237.51
227.90 MBH
153.77
144.16 MBH
83.74 MBH
230.91 MBH
82.41 ºF DB
69.18 ºF WB
82.41 ºF DB
69.18 ºF WB
53.39 ºF DB
53.19 ºF WB
55.15 ºF DB
53.92 ºF WB
100%
1 x 220 @ 3.38 BHP
1496 / 4.871"
1 x RM220A @ 1.99 BHP
1322 / 4.920"
Evaporator Coil:
Evaporator Face Velocity:
Energy Recovery Wheel:
19.9 ft² / 6 Rows / 12 FPI
251.7 fpm
1 x ERC-5262C
PreHeat Type:
Std (No Preheat)
Heating Type:
Heating CFM:
Total Capacity:
OA Temp:
RA Temp:
Entering Air Temp:
Leaving Air Temp:
Input:
Heater Qty:
Electric Heat FLA:
Electric Heat
5000
204.8 MBH
27.0 ºF DB / 25.0
72.0 ºF DB / 60.0
57.5 ºF DB / 50.3
95.4 ºF DB / 64.7
60.0 kW
6
72.2
TOSHIBA-CARRIER VRF HEAT PUMP - OUTDOOR EQUIPMENT SCHEDULE
QUANTITY
IEER
MIN # OF
COMPRESSORS
NOMINAL COOLING
CAPACITY (BTUH)
NOMINAL HEATING
CAPACITY (BTUH)
POSITION
SYSTEM NAME
MODEL
MANUFACTURER
CAPACITY
RANK
VRF-1
VRF Condensing Unit 1
MMY-AP0724HT6UL
TOSHIBA-CARRIER
6 TON
1
3
11.2
2
72,000
81,000
VRF-2
VRF Condensing Unit 2
MMY-AP0724HT6UL
TOSHIBA-CARRIER
6 TON
1
5
12.2
2
72,000
VRF-3
VRF Condensing Unit 3
MMY-AP1684HT6UL
TOSHIBA-CARRIER
14 TON
2
6
11.2
6
168,000
MARK
NOTES:
1.
2.
OUTDOOR
INDOOR
ELECTRICAL
WEIGHT (LB)
REMARKS
20
621
1, 2, 3, 4, 5, 6, 7, 8, 10
6.7
20
621
1, 2, 3, 4, 5, 6, 7, 8, 10
8.8 / 6.7
25 / 20
817 / 621
1, 2, 3, 4, 5, 6, 7, 8, 10
V / Ø / Hz
RLA
MOCP
CENTER
460/3/60
6.7
81,000
CENTER
460/3/60
189,000
CENTER
460/3/60
OUTDOOR TEMPERATURE COOLING/HEATING 95° F / 43° F.
SCHEDULED EFFICIENCIES ARE MINIMUM REQUIRED.
3.
PROVIDE INVERTER DRIVEN TWIN ROTARY COMPRESSOR CAPABLE OF FULL RANGE OF CONTROL TO A LEVEL OF 0.1 HZ. ALL COMPRESSORS SHALL BE OF THE SAME TYPE.
4.
PROVIDE DIRECT DRIVE INVERTER DRIVEN OUTDOOR FAN MOTOR.
5.
PROVIDE 4 SIDED OUTDOOR COIL WITH FACTORY APPLIED CORROSION RESISTANT FINISH.
6.
7.
PROVIDE FACTORY MOUNTED COMPRESSOR SOUND BLANKETS, CRANKCASE HEATERS, OVER-TEMPERATURE OPERATION PROTECTION, HIGH/LOW PRESSURE SWITCHES, AND INVERTER OVERLOAD PROTECTOR.
PROVIDE FUSES, FUSIBLE PLUG, OVER CURRENT RELAY FOR COMPRESSORS, THERMAL PROTECTORS FOR COMPRESSOR AND FAN MOTOR, COMPRESSOR TIME DELAY, OIL RECOVERY SYSTEM, OIL LEVEL SENSOR, OVER-CURRENT SENSOR, COMPRESSOR SUCTION AND DISCHARGE TEMPERATURE AND PRESSURE SENSOR.
8.
PROVIDE AN OIL MANAGEMENT SYSTEM THAT BALANCES OIL BETWEEN COMPRESSORS WITHIN A MODULE, REPLENISHES OIL FROM THE OIL SEPARATOR, AND ALLOWS MOVING OIL AND REFRIGERANT BETWEEN TWINNED UNITS, EVEN IF ONE OF THE UNITS IS NOT RUNNING.
9.
PROVIDE CENTRAL WEB BROWSER CONTROL SYSTEM BMS-SM1280HTLUL.
10.
FOR COMPLETE ACCURATE WIRING AND PIPING DIAGRAM, ENGINEERING SUPPORT, AND SALES ASSISTANCE CONTACT TOSHIBA-CARRIER, CHRIS SMELLEY, AT 713-939-6001.
Cooling Capacity (MBH):
Cooling EER:
Cooling IEER:
Rated in accordance with AHRI 340/360
238.0
12.3
14.8
Application EER @ Op. Conditions:
19.7
Capacity:
LA DB / WB:
RH:
90 MBH
70.00 ºF / 59.68 ºF
55%
Minimum Circuit Amp:
Maximum Overcurrent:
88
100
Electrical Data
Rating:
Unit FLA:
Compressor 1:
Compressor 2:
Condenser Fans:
Supply Fan:
Exhaust Fan:
Heatwheel:
460/3/60
85
Qty
1
1
2
1
1
1
HP
0.75
5.00
3.00
0.1667
VAC
460
460
460
460
460
460
ºF
ºF
ºF
ºF
Re-Heat Coil:
Rating Information
OUTDOOR UNIT
23
FCU-8
22
1, 2, 3, 4, 5, 7, 8
21
1, 2, 3, 4, 5, 7, 8
48
20
59
15
19
15
0.8
18
1.0
208/1/60
17
208/1/60
34
16
37
730
15
1160
9.80
13
14.10
17.48
12
23.87
24.06
11
31.71
73.2
9
73.4
62.2
10
62.2
74.1
8
74.2
Zone 7
7
Zone 6
4-Way Cassette
6C
4-Way Cassette
MMU-AP0302H2UL
6B
MMU-AP0362H2UL
FCU-7
6A
FCU-6
1.
10.
REMARKS
5C
MOCP
5B
WB
HEATING
5A
WB
SENSIBLE
4
DB
TOTAL
3
HEATING
COOLING
ROOM
2
TYPE
1C
VRF-1
TOSHIBA-CARRIER
MODEL
ELECTRICAL
SOUND
PRESSURE,
V / Ø / HZ
RLA
LOW (dB)
1D
MARK NO.
Max
Airflow
(CFM)
1B
VRF SYSTEM
CAPACITIES (kBTUH)
ENTERING AIR TEMPERATURES (° F)
1A
INDOOR UNIT
Phase
3
3
3
3
3
1
RPM
FLA
1080
1760
1760
1770
1.8
7.6
4.8
0.6
RLA
16.7
16.7
WB
WB
WB
WB
Download PDF