Air Conditioning
Technical Data
Wall mounted unit
EEDEN15-100
FTX-GV
• Indoor Unit • FTX-GV
TABLE OF CONTENTS
FTX-GV
1
Features . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2
2
Specifications . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3
Technical Specifications . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Electrical Specifications . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
3
4
3
Options . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5
4
Dimensional drawings . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6
5
Centre of gravity . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7
6
Piping diagrams . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8
7
Wiring diagrams . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9
Wiring Diagrams - Single Phase
8
.................................... 9
Sound data . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 10
Sound Pressure Spectrum
• Split - Sky Air • FTX-GV
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 10
1
• Indoor Unit • FTX-GV
1
Features
ket tSi n uU - o mr tV o G i lo - l dl X pnaT WFWall
IS
1
mounted unit providing high efficiency and comfort
•
Online controller (optional): control your indoor unit from any location
via smartphone, laptop, pc, tablet or touch screen
•
Home leave operation maintains the indoor temperature at your
specified comfort level during absence, thus saving energy
•
3-D air flow combines vertical and horizontal auto swing to circulate
a stream of warm or cool air right to the corners of even large spaces
•
Dry programme allows humidity levels to be reduced without
variations in room temperature
•
Indoor unit silent operation: "silent" button on the remote control
lowers the operation sound of the indoor unit by 3dBA
•
•
Outdoor unit silent operation: "silent" button on the remote control
lowers the operation sound of the outdoor unit by 3dBA to ensure a
quiet environment for the neighbourhood.
Movement sensor saves power consumption in unoccupied rooms:
when the room is empty, the unit switches to economy mode after 20
minutes and restarts when a person enters the room.
•
Night set mode saves energy by preventing overcooling or
overheating during night time
Movement
sensor
Home leave
operation
Night set mode
Vertical auto Horizontal auto Auto fan speed
swing
swing
Fan only
Powerful mode Auto coolingIndoor unit
Outdoor unit
heating
silent operation silent operation
changeover
3-D air flow
Fan speed
steps
Dry programmeTitanium apatite 24 hour timer Infrared remote
photocatalytic
control
air purification
filter
Auto-restart
Self diagnosis
2
• Split - Sky Air • FTX-GV
• Indoor Unit • FTX-GV
2
Specifications
2-1 Technical Specifications
FTX50GV
FTX60GV
FTX71GV
Power input
Cooling
Nom.
kW
0.034
0.040 (1) / 0.040 (2) / 0.040 (3)
0.045 (1) / 0.045 (2) / 0.045 (3)
Heating
Nom.
kW
0.036
0.045 (1) / 0.045 (2) / 0.045 (3)
0.060 (1) / 0.060 (2) / 0.06 (3)
Casing
Colour
Dimensions
Unit
Height/Width/
Depth
mm
Packed unit
Height/Width/
Depth
mm
Weight
Heat exchanger
White
290/1,050/238
337/1,147/366
366/1,147/337
Unit
kg
12
Packed unit
kg
17
mm
863
mm
1.4
Length
Rows
Quantity
Quantity
16
Tube type
Fin
Air filter
Type
Fan
Type
Air flow rate
ø7 Hi-XD
Type
ML fin (Multi louver)
Removable / washable / mildew proof
Cross flow fan
Cooling High
Nom.
16.2
cfm
519
572
614
m³/min
14.7
16.2
14.6
Output
17.4
519
572
516
m³/min
10.3
11.4
11.6
cfm
364
403
410
Silent
operati
on
m³/min
9.5
10.2
10.6
cfm
335
360
374
m³/min
16.1
17.4
19.7
cfm
568
614
696
m³/min
13.9
15.1
16.9
cfm
491
533
597
Low
m³/min
11.5
12.7
14.3
cfm
406
448
505
Silent
operati
on
m³/min
10.2
11.4
12.7
cfm
360
403
448
Model
Speed
Sound pressure level
14.7
cfm
Nom.
Sound power level
m³/min
Low
Heating High
Fan motor
2
2
Fin pitch
Stages
3
ARW30W8P43DK
Steps
D43F-31
5 + silent, + auto
Cooling High/
rpm
Mediu
m/Low/
Silent
operati
on
1,240/1,080/930/860
1,330/1,170/1,010/920
1,410/1,220/1,040/950
Heating High/
rpm
Mediu
m/Low/
Silent
operati
on
1,270/1,110/960/870
1,360/1,200/1,040/950
1,520/1,330/1,150/1,040
High
W
43
Cooling
dBA
59
60
Heating
dBA
58
59
63
62
Cooling
High/Nom./Low/
Silent operation
dBA
43/39/34/31
45/41/36/33
46/42/37/34
Heating
High/Nom./Low/
Silent operation
dBA
42/38/33/30
44/40/35/32
46/42/37/34
Control systems
Infrared remote control
Refrigerant
Type
ARC433B70
R-410A
• Split - Sky Air • FTX-GV
3
• Indoor Unit • FTX-GV
2
Specifications
2-1 Technical Specifications
Piping connections
FTX50GV
Liquid
OD
Gas
OD
FTX60GV
12.7
Drain
15.9
18
Heat insulation
2
FTX71GV
6.35
Both liquid and gas pipes
Temperature control
Microcomputer control
Air direction control
Right, Left, Horizontal, Downward
Standard Accessories : Operation manual; Quantity : 1;
Standard Accessories : Titanium apatite photocatalytic air purification filter; Quantity : 2;
Standard Accessories : Batteries; Quantity : 2;
Standard Accessories : Wireless remote control; Quantity : 1;
Standard Accessories : Installation manual; Quantity : 1;
Standard Accessories : Indoor unit fixing screws; Quantity : 2;
Standard Accessories : Mounting plate; Quantity : 1;
Standard Accessories : Remote control holder; Quantity : 1;
Standard Accessories : Indoor unit fixing screws (M4 x 12L); Quantity : 2;
2-2 Electrical Specifications
Power supply
FTX50GV
FTX60GV
Name
Phase
Current
Wiring connections 50Hz
1~
Frequency
Hz
50
Voltage
V
220-240
Nominal running
Cooling
current (RLA) - 50Hz Heating
A
0.16 (1) / 0.15 (2) / 0.15 (3)
0.19 (1) / 0.18 (2) / 0.17 (3)
0.21 (1) / 0.20 (2) / 0.19 (3)
A
0.17 (1) / 0.16 (2) / 0.16 (3)
0.21 (1) / 0.20 (2) / 0.19 (3)
0.28 (1) / 0.27 (2) / 0.26 (3)
For power supply
Quantity
Remark
Notes
(1) 220V
(2) 230V
(3) 240V
SL: The silent fan level of the air flow rate setting
4
FTX71GV
V1
• Split - Sky Air • FTX-GV
3 for power supply, 4 for interunit wiring (Earth wire included)
3
• Indoor Unit • FTX-GV
3
Options
3-1
Options
3
3
• Split - Sky Air • FTX-GV
5
• Indoor Unit • FTX-GV
4
Dimensional drawings
4-1
Dimensional Drawings
FTX50-60GV
Rear
Rear
Min. 30
Left
Air flow (indoor)
(For performance and maintenance)
shows piping direction
Right
(Space for
maintenance)
Min. 50
4
Min. 50
(Including
installation plate)
Operation lamp
Flaps
Signal
transmitter
Drain hose for VP13
Gas pipe ø12.7 Cut
(connection part
(the lenght of pipe outside
I.D. 14.0, O.D. 18.0)
the unit: about 430)
(The hose length
of outside the unit:
Liquid pipe ø 6.4 Cut
about 530)
(the lenght of pipe outside the
unit: about 480)
BLADE ANGELS
Heating
Fan
Infrared
remote control
Terminal block
with earth
terminal (inside)
Intelligent eye sensor
Timer lamp
Home leave lamp
Horizontal blade
(automatic)
Cooling
(Space for
maintenance)
REQUIRED SPACE
Model name
plate
Signal receiver
Indoor unit on/off
switch
Room temp. thermistor
(inside)
Front grille fixing screws
(inside)
(Space for
performance)
The mark
Dry
Wall hole
ø 80 hole
Vertical blade (automatic)
Wall hole for
embedded piping
ø 80 hole
STANDARD LOCATIONS OF WALL HOLES
3D055875A
FTX71GV
Rear
Rear
Min. 30
Left
Air flow (indoor)
(For performance and maintenance)
shows piping direction
Right
(Space for
maintenance)
Min. 50
Min. 50
(Including
installation plate)
Operation lamp
Signal receiver
Indoor unit on/off
switch
Room temp. thermistor
(inside)
Front grille fixing screws
(inside)
Flaps
Signal
transmitter
Infrared
remote control
REQUIRED SPACE
Terminal block
with earth
terminal (inside)
Intelligent eye sensor
Timer lamp
Home leave lamp
Fan
Heating
(Space for
maintenance)
Model name
plate
Drain hose for VP13
Gas pipe ø15.9 Cut
(connection part
(the lenght of pipe outside
I.D. 14.0, O.D. 18.0)
the unit: about 430)
(The hose length
of outside the unit:
Liquid pipe ø 6.4 Cut
about 530)
(the lenght of pipe outside the
unit: about 480)
BLADE ANGELS
Horizontal blade
(automatic)
Cooling
(Space for
performance)
The mark
Dry
Wall hole
ø 80 hole
Vertical blade (automatic)
Wall hole for
embedded piping
ø 80 hole
STANDARD LOCATIONS OF WALL HOLES
3D055876A
6
• Split - Sky Air • FTX-GV
• Indoor Unit • FTX-GV
5
Centre of gravity
5-1
Centre of Gravity
3
FTX50-71GV
5
4D065971B
B
%
• Split - Sky Air • FTX-GV
7
• Indoor Unit • FTX-GV
6
Piping diagrams
6-1
Piping Diagrams
6
8
• Split - Sky Air • FTX-GV
• Indoor Unit • FTX-GV
7
Wiring diagrams
7-1
Wiring Diagrams - Single Phase
3
FTX50-71GV
Field wiring
RECTIFIER
Outdoor
7
CAUTION
Note that operation will restart
automatically if the main power
supply is turned off and then back
on again.
Transmission
circuit
LED1 LED2 LED3
Intelligent eye
sensor
Indoor
Signal
receiver
infrared
remote
control
FG
FU
H1~H3
H1P~H3P
M1F
M1S, M2S
Frame ground
Fuse
Harness
Pilot lamp
Fan motor
Swing motor
PCB1~PCB5
R1T,R2T
S1~S38
S1W
X1M
Printed circuit board
Thermistor
Connector
Operation switch
Terminal strip
Protective earth
3D038530U
U
• Split - Sky Air • FTX-GV
9
• Indoor Unit • FTX-GV
8
Sound data
8-1
Sound Pressure Spectrum
8
FTX60GV
Heating
Octave band sound pressure level dB (0 dB = 0.0002μ bar)
Approximate
threshold hearing
for continuous
noise
Octave band center frequency - IEC (Hz)
Octave band center frequency - IEC (Hz)
NOTES
H
45
0.8m
2
3
4
Over All (dB):
(B,G,N is already rectified)
A
Measuring place: measure in anechoic room.
Operation noise differs with operation and ambient conditions.
Location of microphone.
1m
JISC9612
The operation noise
measuring method is in
accordance with JISC9612
NOTES
50Hz
220-240V
Scale
1
Approximate
threshold hearing
for continuous
noise
L
36
1
2
3
4
Scale
Over All (dB):
(B,G,N is already rectified)
A
Measuring place: measure in anechoic room.
Operation noise differs with operation and ambient conditions.
Location of microphone.
1m
JISC9612
The operation noise
measuring method is in
accordance with JISC9612
50Hz
220-240V
H
44
L
35
0.8m
Octave band sound pressure level dB (0 dB = 0.0002μ bar)
Cooling
3D051227E
E
10
• Split - Sky Air • FTX-GV
• Indoor Unit • FTX-GV
8
Sound data
8-1
Sound Pressure Spectrum
3
FTX71GV
Heating
Octave band sound pressure level dB (0 dB = 0.0002μ bar)
Approximate
threshold hearing
for continuous
noise
3D051225D
Octave band center frequency - IEC (Hz)
NOTES
2
3
4
Over All (dB):
(B,G,N is already rectified)
A
Measuring place: measure in anechoic room.
Operation noise differs with operation and ambient conditions.
Location of microphone.
1m
JISC9612
The operation noise
measuring method is in
accordance with JISC9612
H
46
0.8m
1
Approximate
threshold hearing
for continuous
noise
3D051225D
Octave band center frequency - IEC (Hz)
NOTES
50Hz
220-240V
Scale
8
50Hz
220-240V
Scale
L
37
1
2
3
4
Over All (dB):
(B,G,N is already rectified)
A
Measuring place: measure in anechoic room.
Operation noise differs with operation and ambient conditions.
Location of microphone.
1m
JISC9612
The operation noise
measuring method is in
accordance with JISC9612
H
46
L
37
0.8m
Octave band sound pressure level dB (0 dB = 0.0002μ bar)
Cooling
3D051225D
• Split - Sky Air • FTX-GV
11
The present leaflet is drawn up by way of information only and does not
constitute an offer binding upon Daikin Europe N.V.. Daikin Europe N.V.
has compiled the content of this leaflet to the best of its knowledge. No
express or implied warranty is given for the completeness, accuracy, reliability or fitness for particular purpose of its content and the products
and services presented therein. Specifications are subject to change
without prior notice. Daikin Europe N.V. explicitly rejects any liability for
any direct or indirect damage, in the broadest sense, arising from or related to the use and/or interpretation of this leaflet. All content is copyrighted by Daikin Europe N.V.
BARCODE
Daikin products are distributed by:
Naamloze Vennootschap - Zandvoordestraat 300, B-8400 Oostende - Belgium - www.daikin.eu - BE 0412 120 336 - RPR Oostende
EEDEN15-100 05/15 Copyright Daikin
The present publication supersedes EEDEN14-100
Daikin Europe N.V. participates in the Eurovent Certification programme for Liquid
Chilling Packages (LCP), Air handling units
(AHU), Fan coil units (FCU) and variable refrigerant flow systems (VRF) Check ongoing
validity
of
certificate
online:
www.eurovent-certification.com or using:
www.certiflash.com
Download PDF
Similar pages