TopMaster Air Handling Unit
TopMaster Air handling unit
CATALOGUE
Contents
Page
Contents . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .2
Unit description . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .3
Design . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .4
Technical Details
Size 030 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .5
Size 050 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .6
Accessories . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .7
Controls . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .9
Control functions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .10
Product Codes . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .12
Fläkt Woods
8180 GB 2012.10
2
Specifications are subject to alteration without notice
TopMaster Air handling unit
CATALOGUE
Unit Description
Top Master
Product data
is a compact unit in two sizesthat requires minimal
space. Compact dimensions and low sound data provide great flexibility in the location of the unit. Its attractive design also adds to the flexibility of location.
– All duct connections are on top of the unit.
– The unit is supplied with direct driven supply and
extract air fans, supply and exhaust air filters as well
as a rotating heat recovery unit.
– The control system, which is integrated in the unit, is
equipped for a large number of external functions.
– Air flow range 100-550 l/s
(size 030, 100-350 l/s)
(size 050, 100-550 l/s)
– Effective heat recovery
– Integrated control system
– Integrated re-heater
– Simple installation with all connections upwards
– Attractive design
– Externally painted
Quality and Environment
Typical installations
All units and components from Fläkt Woods are designed, tested and built to the applicable standards including quality assurance system ISO 9001 and
Environmental management system ISO 14001.
The TopMaster has a wide range of applications and can
be installed in most buildings that require ventilation,
such as schools, offices, conferencepremises, shops etc.
Environmental declaration
Fläkt Woods
8180 GB 2012.10
Substance
Proportion
Recyclable
material
Metals
92%
X
Polymers
2.5%
X
Mineral wool insulation
5%
X
Others
0.5%
To
landfill
X
X
Specifications are subject to alteration without notice
TopMaster Air handling unit
CATALOGUE
Unit Description -– design
Casing
Fan
The unit is made of galvanized sheet steel and the outside is painted white. The casing is insulated with 25 mm
of mineral wool.
Inspection doors for fans, filter and rotor have handles
and locks.
The unit is supplied on a stable base which can be fitted
with feet.
– Corrosion class C3
– Seal CEN class L3 (CEN class A)
We chose the fan for TopMaster to give you top performance and overall economy combined with low noise
levels. The fan is a single inlet radial fan with forward
curved blades. It is driven by a DC motor with integrated electronics, which establishes a constant flow in the
unit within the work area.
The desired flow is controlled by the unit’s control
system.
Components in the casing
Filter
Supply and extract air filters made of fibreglass. Filter
class F5 on the extract air side and F7 on the supply air
side. The filters are pressed against the sealing strip in
the casing.
Integrated heater
Heater battery for hot water or electricity are built-into
the unit. The desired supply air temperature is controllled by the unit’s control system.
Water heater
The air heater for water heating is made of copper pipes
and aluminium fins. Pipe connection Ø15.
Frost protection sensor is included in the control equipment. Max. operating pressure 1.6 MPa.
Rotary heat exchanger
The rotor is made of non-hygroscopic aluminium
equipped with purging sector and rotation monitor.
During normal comfort ventilation there is no need for
defrosting. When relative humidity in the extract air
exceeds 30% and the outdoor temperature is lower than
–15 °C there is a risk of freezing. Check the need for
defrosting with Fläkt Woods AB.
Fläkt Woods
8180 GB 2012.10
Electric heater
Electric heater with integrated control equipment for
power control. Heater element in stainless steel. The
heater is equipped with 2 thermal overload protection
devices, one with automatic and one with manual reset.
Specifications are subject to alteration without notice
TopMaster Air handling unit
CATALOGUE
Technical Details, size 030
System overview
TopMaster 00 supply air
The diagram shows the accessible external pressure
drop for the duct system and external function components.
The weighted noise levels given in dB(A) apply to ducts
on the fan’s outlet side.
The SFPv values for the respective fans are calculated
according to the Svensk Ventilation (SwedishAssociation
of Air Handling Industries) V document 1995:1 (rev.
2000), that is, clean filters, and reference taken of leakage
and cleaning flow and any additional pressure drop for
correct pressure balance. Readings for the respective fans
are totalled to give the SFPv value for the entire unit.
700
600
500
400
1.5
1.25
300
1
∆p external
, Pa
∆p
extern , Pa
200
Dimensions, weights and electrical data
SFPv
0.75
75
100
LwA,dB 70
50
Direct driven radial fan with forward curved blades.
Motor, IP54. Power electric heater 2.4 kW.
Rotor: Temperature efficiency 80% at 0.3 m3/s.
Mains connection:
– 3x400V, 50Hz (Units with a water heater can be
connected to 1x230V)
– External fuse protection: max 10 A, max 4 mm2.
The mains supply cable must be fitted with an external
switch-disconnector, which can interrupt the current to
the whole unit.
Ambient temperature during operation 0...40 °C
Weight: 170 kg
Filter:
Supply air: 670 x 300 x 50 mm, F7
Extract air: 670 x 300 x 50 mm, F5
0.1
0.2
400
500
qv
600
0.4 m 3 /s
0.3
700
800
900
1000
1100
1200
1300
1400
m 3/h
TopMaster 00 extract air
700
600
500
1.5
400
1.25
300
65
1
∆pexexternal
∆p
tern , Pa , Pa
200
Ø 250
x4
0.75 SFPv
60
100
LwA,dB 55
50
0.1
0.2
qv
500
600
700
800
900
1000
1100
1200
1300
1400
m 3/h
45
400
0.4 m 3 /s
0.3
1050
170
327
286
327
246
Fresh
air
Extract
air
Exhaust
air
100
185
p q
Filter
50
12
12
80
5
73
Ø 15
Fläkt Woods
8180 GB 2012.10
35
q p
Fläkt
5
∆ p
Fläkt
Exhaust
air
Supply
air
50
p q
Filter
310
Fresh
air
140
Right-hand version
p q
Rotor
235 735
Supply
air
p q
Filter
p q
Rotor
q p
Fläkt
Extract
air
p q
Filter
∆ p
Fläkt
Specifications are subject to alteration without notice
TopMaster Air handling unit
CATALOGUE
Technical Details, size 050
System overview
TopMaster 050 supply air
The diagram shows the accessible external pressure
drop for the duct system and external function components.
The weighted noise levels given in dB(A) apply to ducts
on the fan’s outlet side.
The SFPv values for the respective fans are calculated
according to the Svensk Ventilation (SwedishAssociation
of Air Handling Industries) V document 1995:1 (rev.
2000), that is, clean filters, and reference taken of leakage
and cleaning flow and any additional pressure drop for
correct pressure balance. Readings for the respective fans
are totalled to give the SFPv value for the entire unit.
3&0V
∆p
$P Eexternal
XTERN 0,APa
Dimensions, weights and electrical data
Direct driven radial fan with forward curved blades.
Motor, IP54. Power electric heater 4.7 kW.
Rotor: Temperature efficiency 70% at 0.5 m3/s.
Mains connection:
– 3x400V, 50Hz (Units with a water heater can be
connected to 1x230V)
– External fuse protection: max 16 A, max 4 mm2.
The mains supply cable must be fitted with an external
switch-disconnector, which can interrupt the current to
the whole unit.
Ambient temperature during operation 0...40 °C
Weight: 175 kg
Filter:
Supply air: 670 x 300 x 100 mm, F7
Extract air: 670 x 300 x 50 mm, F5
, W! D" QV
MS
MH
TopMaster 050 extract air
3&0V
∆p
, Pa
$PEexternal
XTERN 0A
Ø 250
x4
45
, W! D" 1050
QV
170
327
286
MS
MH
327
246
Fresh
air
100
Extract
air
185
p q
Filter
50
12
80
12
5
73
35
8180 GB 2012.10
p q
Filter
∆ p
Fläkt
310
Exhaust
air
Supply
air
Fresh
air
50
p q
Filter
Fläkt Woods
q p
Fläkt
Ø 15
140
Right-hand version
p q
Rotor
235 735
Supply
air
Exhaust
air
p q
Rotor
q p
Fläkt
Extract
air
p q
Filter
∆ p
Fläkt
Specifications are subject to alteration without notice
TopMaster Air handling unit
CATALOGUE
Accessories
Air cooler, water, for duct mounting,
RDNN
Duct silencer, RDLD
The silencer is a straight circular duct silencer with 100
mm rock wool filling. The duct connections are fitted
with rubber ring seals.
The silencer consists of a perforated pipe surrounded by
a mantel and ends made of hot dip galvanized sheet
steel. The area between is filled with rock wool which is
covered by a fibre sheet to prevent the fibres from loosening. Fire class EI30.
Connection straight section 300 mm from fan outlet.
Air cooler for cold water, copper pipes and aluminium
fins.
The air cooler is built into a hot dip galvanized sheet
steel casing with 9 mm insulation. The casing has a
removable hatch for cleaning and duct connections
with rubber ring seals. The air cooler is installed so that
the distance to the fan or bend before the cooler is at least
600 mm. The cooler is only available in a left-hand
version. Bleeding and draining is carried out via the
pipe system. The pipe connection, positioned on the
outlet end, is flat and intended for clamp connection.
The drainage trough is made of stainless steel, connection R 1/2 ”.
Max. operating pressure 1.0 Mpa.
Max. operating temperature 100 °C
Ø15
Ø50
8
Ø250
900
Adjustable feet, RDTZ-0
50
The unit can be positioned
directly on the foundation if it is
flat and horizontal. Adjustable
feet can be used for adjustment.
Adjustable foot 15-85 mm.
Arubber pad is included in
the kit.
0
Water trap RDTZ-08
Compact water seal for connecting the air cooler.
Spare filter, RDTZ-0
Shut off damper for duct mounting RDVA
A kit with a spare filter for one air passage. F5 or F7.
Damper for duct mounting. Seal class 3 (CEN 3) The
damper is made of hot dip galvanized sheet steel and
fitted with an on/off actuator with spring return. The
damper actuator is connected to the electrical cabinet
via a quick connector.
The damper has a duct connection with a rubber ring
seal and can be mounted directly to the unit or in the
duct. The design is suitable for duct insulation of up to
50 mm.
The sound power level while completely open is
below 20 dB at airspeeds below 10 m/s.
Flexible connection, RDTZ-05
Flexible connection made of fibreglass sheet for flexible
connection of ducts.
Pressure gauge, flow measurement
RDTZ-0
Pressure gauge for measuring airflow, can be installed
on the end of the unit and connected to nipples.
Supplied separately.
Ø250
Pressure gauge, U pipe for filter
RDTZ-0
Fläkt Woods
Single pressure gauge for measuring filter
pressure drop, can be installed on the end of
the unit and connected to nipples. Supplied
separately.
8180 GB 2012.10
Specifications are subject to alteration without notice
TopMaster Air handling unit
CATALOGUE
Accessories
Dual-purpose cowl RDTZ-09
TopMaster 050
External wall cover for outdoor air and extract air, for
wall mounting.
This prevents leakage between the two air flows.
The cover is made of black plastic-coated sheet metal
and consists of a wall plate, wall cover, front panel. The
front panel is detachable and can be turned over.
A
E
B
TopMaster 00
øD
øD
C
øD
øD
G
Product code
B
A
B
C
D
E
Weight,kg
80
0
150
15
15
10
F
RDTZ-09-050-1
C
E
A
RDTZ-09-00-1
A
B
C
D
E
F
G Weight,kg
50 0 250 190 15 90
Storlek
Size
100
,5
Tryckfall,
Pressure Pa
drop, Pa
Product code
Pressure drop, TopMaster 050
Pressure drop, TopMaster 00
PressurePa
drop, Pa
Tryckfall,
125
100
Dual-purpose
cowl RDTZ-09
Kombihuv
RDTZ-09-030-1
Duct dimension ø 250
Kanaldimension
250
Dual-purpose
RDTZ-09-050-1
Kombihuv RDTZ-09-050-1
Duct
dimension øø15
Kanaldimension
315
50
20
5
75
0,02
0,05
0,1
0,2
0,5
1
3
Air
flow, mm
/s
Luftflöde,
/s
50
25
0
50
Fläkt Woods
100 150 200 250 300 350 400 450 500
Luftflöde,
l/s
Air flow, l/s
8180 GB 2012.10
8
Specifications are subject to alteration without notice
1,5
TopMaster Air handling unit
CATALOGUE
Control
General
Technical specifications
TopMaster is always supplied complete with integrated
control equipment. All internal components are pre
connected and the unit is factory tested.
The control equipment for TopMaster is developed with
the intention that it should be as easy as possible to use,
install and monitor.
The control equipment communicates using the
Modbus protocol alternative Lon Works .
–
–
–
–
Operation for pumps, max 2 A
Three speed DC motors for fan operation
ON/OFF rotor control
Daily-/Weekly-/Annual clock built into the control
cabinet. Back up power for 72-hour power loss
– The unit is equipped with quick connectors for auxiliary equipment in direct proximity; damper actuator,
sensors, valve actuator, control panel for the control
cabinet.
Operation
TopMaster is supplied with a control cabinet and a
control panel for operation.
All menus are shown clearly in plain text. Settings and
readings are carried out via the control panel.
FF1
GT3
Control functions
– On-Off or Room temp.control
– Maintaining air flow or pressure
– Night cooling
– Cooling recovery
– Summer and winter compensation
– Outdoor temperature controlled fan speed
– Extended/forced operation via timer
– Frost protection sensor
– Time program.
GT1
GT12
TF1
GS1
Designation of component parts:
TF1
Supply air fan
FF1
Exhaust air fan
TS1
Thermal overload protection, automatic reset
TS2
Thermal overload protection, manual reset
SK1
Control equipment for power control
GT1
Supply air temperature sensor
GT3
Extract air temperature sensor
GT5
Frost protection sensor on the return water
GT12 Extract air temperature sensor
GP1
Pressure monitor for the supply air filter
GP2
Pressure monitor for the extract air filter
GP3
Pressure monitor for the supply air fan
GP7
Pressure monitor for rotary heat exchanger
GS1
Rotation monitor HRC
Accessories
– Defrosting
– Filter monitor
– Flow monitor
Fläkt Woods
8180 GB 2012.10
9
Specifications are subject to alteration without notice
TopMaster Air handling unit
CATALOGUE
Control functions
Flow control
Night purging (free cooling)
The fans in TopMaster are constant flow fans. This
means that they give a preset air flow within their
operating area regardless of the pressure of the unit.
Three different set point values, min, normal and
max flow, are set for the supply air fan and the
extract air fan.
Three set points for each fan allow connection of fan
speed to clock, timer, push button and occupancy
detector.
Function: maintaining flow in the duct system.
The Night purging setting is used during the summer
half of the year. Cold outdoor air can be used to cool
down the premises cool the premises at night. Used
outside ordinary operating time.
Function: When the room temperature exceeds the set
limit value and the outdoor temperature exceeds the set
limit value and the difference between the limit values
exceeds the set difference, the unit is started to cool the
premises using fresh outdoor air. The cooler is not activated.
Pressure control
Night heating
The control board for the fans can be reset for constant
pressure control. The fans in TopMaster then give a
constant preset pressure and flow within their operation area.
Night heating is used to prevent the premises from
being cooled during the night outside the normal operating time.
Function: The unit starts for full heat recovery and
opens for full effect from the air heater if the room
temperature falls below the set value.
Extended and forced operation via timer
Timer for external or flush mounting.
Setting 0–2 hours.
Function: Starts the unit at the desired air flow or change of air flow.
Cooling recovery
Function: Starts the rotary heat exchanger at full heat
recovery for cooling the supply air, when the exhaust air
temperature is lower than the outdoor air temperature
and there is a need for cooling.
Temperature control
The following alternatives are available for control
functions:
Outdoor temperature compensation
(summer and winter compensation)
Supply air control
Function: Shifts the set point for the supply air, exhaust
air or room temperature.
Function: Maintaining the temperature in the supply air
duct at the set point.
Extract air control
Function: Maintaining the extract air temperature in the
extract air duct at the set point value via cascade control
of the supply air temperature with min. and max.
restriction.
Room control
Function: Maintaining the temperature in the premises
at the set point value via cascade control of the supply
air temperature with min. and max. restriction.
Fläkt Woods
8180 GB 2012.10
10
Specifications are subject to alteration without notice
TopMaster Air handling unit
CATALOGUE
Control functions
Controlling the air heater
Fire protection system
Control signal 0-10 V for valve actuator or electric air
heater with built-in thyristor. Frost protection: When
the unit is not in operation the water temperature is
maintained at 25 °C. During operation the valve is
controlled so that the return temperature does not fall
below 12 °C. If the temperature falls below 5 °C the unit
stops and an alarm is triggered.
Afire protection system can be connected to the unit.
Function: Stops the unit and buzzer.
Circulation pump for air heater
Max. current approx 2 A, 1-phase 230 V. Maintenance
operation carried out via the control cabinet.
Gives an alarm if the pressure drop over the relevant
filter exceeds the set value. Not to be used in combination with the flow monitor or control of cooling coil.
Valve actuator for air heater
Flow monitor
Valve actuator suitable for valves with 5.5 mm lift height
and thread G 3/4".
Stops the unit and gives an alarm in the event of low
flow. Not to be used in combination with the filter monitor or control of cooling coil.
Communication
Topmaster is supplied with Modbus RTU and Lon
Works.
Filter monitor
Controlling the air cooler
Defrosting
Control signal 0-10 V for air cooler, water.
Control signal to cooler for direct expansion, DX,
closing contact.
The rotor is defrosted in the event of freezing using the
pressure monitor.
Circulation pump for air cooler
Max. current approx 2 A, 1-phase 230 V. Maintenance
operation carried out via the control cabinet.
Valve actuator for air cooler
Valve actuator suitable for valves with 5.5 mm lift height
and thread G 3/4".
Fläkt Woods
8180 GB 2012.10
11
Specifications are subject to alteration without notice
TopMaster Air handling unit
CATALOGUE
Product code
TopMaster
Air Handling Unit
RDTM-aaa-b-1-d-1-2-0-1
Sound attenuator
Mounted in ductwork
RDLD-aaa-1
Size (aaa)
030, 050
Unit size(aaa)
030, 050
Supply air location (b)
1 = supply air right
2 = supply air left
Adjustable feet
(set, supplied unmounted)
Heat Recovery (c)
1 = rotary heat exchanger
Unit size(bbb)
030, 050
Air heater (d)
0 = without
1 = electrical coil
2 = water coil
Spare filter
(for one air path)
RDTZ-04-bbb-c-1
Unit size(bbb)
030, 050
Control Equipment (e)
1 = standard control, direct current motor
Filter class (c)
1 = F5 (exhaust air)
2 = F7 (supply air)
Voltage (f)
2 = 3 x 400 V AC
Units with water coils can be
connected to 1 x 230V
Flexible connection
(supplied unmounted)
Air cooler, water
Mounted in ductwork
RDTZ-03-bbb-1
RDTZ-05-bbb
RDNN-aaa-1-2-1
Unit size(bbb)
030, 050
Unit size (aaa)
030, 050
Manometer, airflow
Connection side(c)
2 = left
RDTZ-06-bbb-1
Unit size(bbb)
030, 050
Accessories
Damper
RDVA-aaa-1-1
Unit size(aaa)
030, 050
U-tube manometer for filter
(supplied unmounted)
RDTZ-07-1
Water trap
(supplied unmounted)
RDTZ-08-1
Location (b)
1= on/off with spring return
Dual-purpose cowl
RDTZ-09-bbb-1
Unit size(bbb)
050
Installation instruction
RDTZ-36-bb-1
Language (bb)
02 = Swedish
03 = English
06 = Finnish
Fläkt Woods
8180 GB 2012.10
12
Specifications are subject to alteration without notice
TopMaster Air handling unit
CATALOGUE
Product code
Control cabinet
STTM-4-4-ccc-ddd-1-f-4-1-86-5
Temperature control
Fan motor supply air, TF (a)
4 = speed control with frequency
inverter, FO
STYZ-01-86-c-d-e-f-g-0-0-2-5
Control unit (bb)
86 = Fläkt Woods standard
Control situation (c)
1 = supply air control, includes
1 in-duct sensor
2 = extract air control, includes
1 in-duct sensorand 1 factory-fitted
extract air sensor inside air
handling unit
3 = room control, includes
1 in-duct sensor and 1 room sensor
Fan motor exhaust air, FF (b)
4 = speed control with frequency
inverter, FO
Fan output (ccc)
004 = 350 W (size 030)
006 = 550 W (size 050)
Air heater (ddd)
000 = without reheat
003 = hotwater, external shunt
004 = electrical heater with
built-in thyristor
Night cooling (d)
0 = without
1 = with, includes necessary room
sensor and façade sensor
Night-time heating (e)
0 = without
1 = with, includes necessary room sensor
Heat exchanger (e)
1 = rotary heat exchanger
Cooling (f)
0 = without cooling
1 = chilled water
Cooling energy recovery (f)
0 = without
1 = with, includes necessary factory-fitted
temperature sensor in unit handling
Voltage (g)
4= 3x400 V AC
Units with water coils can be
connected to 1 x 230V
Set point displacement (g)
0 = without
1 = outdoor air compensated temperature set
point includes necessary in unit handling
Delivery options (h)
1 = built-in
Airflow compensation (h)
0 = none
Control unit (ii)
86 = Fläkt Woods standard
Efficiency measurement (i)
0 = without
Control unit display (j)
5 = character based, 8 lines
Type of sensor (j)
2 = NI –1000 LG
Connection (k)
5 = with quick connector
Fläkt Woods
8180 GB 2012.10
1
Specifications are subject to alteration without notice
TopMaster Air handling unit
CATALOGUE
Product code
Communication
STYZ-03-86-1-3-05-1
Defrosting
STYZ-10-86-1-1-9-2
Control unit (bb)
86 = Siemens, Saphir ACX 36
Control unit (bb)
86 = Siemens, Saphir ACX 36
Type of heat recovery (c)
1 = rotary heat exchanger
Location (c)
1 = Supply air fan
2 = Exhaust air
Type of defrosting (d)
1 = pressure monitor
Function/protocol (d)
3 = Pressure control
Type of sensor (e)
9= pressure monitor
Flow sensor pressure range (ee)
05 = 0-500 Pa
Delivery configuration (f)
2 = unmounted with cable and quick connector
Delivery configuration (f)
1 = Unmounted if supplied at same time as the controls.
Communication
15 = 15 m
Frost protection sensor
Mounted
STYZ-05-86-c-d-e-2
Control unit (bb)
86 = Siemens, Saphir ACX 36
Version (c)
2 = strap-on sensor
Function/protocol (c)
3 = Lon Works
7 = Modbus RTU
Connection (d)
2= with quick connector
Accessories (d)
0 = without
1 = remote control (bb=21,22)
2 = analogous modem
3 = GSM modem incl. antenna
Fire detection
STYZ-20-1
Control unit (b)
1 = alarm from external fire alarm function
(for potential-free contact)
Fl@ktnet (e)
0 = without
1 = web pages only
3 = web pages + SMS
Extension cable, display
STYZ-11-2-2-2
Filter monitor
1)
STYZ-28-b-2
Location (b)
1 = supply air
2 = extract air
3 = supply air and extract air
STYZ-06-86-cc-0
Length (cc)
05 = 5 m
10 = 10 m
Delivery configuration (c)
2 = unmounted, with cable and quick connector
1) Supply air filter monitor should not be combined
with STYZ-29 and extract air filter monitor should
not be combined with STYZ-70
Flow monitor
2)
STYZ-29-1-2
Location (b)
1 = supply air
Delivery configuration (c)
2 = unmounted, with cable and quick connector
2) Not to be combined with STYZ-28-1-2
Fläkt Woods
8180 GB 2012.10
1
Specifications are subject to alteration without notice
TopMaster Air handling unit
CATALOGUE
Product code
Documentation control
equipment
Coil control
STYZ-36-86-8-dd-1-f-g-1
Brand (bb)
20 = Siemens
Unit size(dd)
30, 50
Scope of supply (c)
1 = actuator only
2 = valve with actuator
Language on documentation, wiring diagram (f)
1 = swedish
3 = english
4 = finnish
Type of valve (d)
0 = without
2 = 2-way
3 = 3-way
Language in DUC display (g)
1 = swedish
3 = english
4 = finnish
Power circuit breaker
(Load interrupter)
016= 16 A (size 030, 050)
Prolonged/forced operation
Location (e)
1 = heating
2 = cooling
STYZ-39-016-1-1
Connection (f)
2 = unmounted with cable and
quick connector
Kvs-value (ggg)
002 = 0.25
004 = 0.4
006 = 0.63
010 = 1.0
016 = 1.6
025 = 2.5
STYZ-40-1-c-0-0-0
Forced operation (b)
1 = prolonged operation
Control via external timer (c)
0-5 timers
Fläkt Woods
STYZ-70-20-c-d-e-2-ggg
8180 GB 2012.10
15
Kvs-value
Siemens-actuator
0.25-2.5
SQS5
Specifications are subject to alteration without notice
We Bring Air to Life
Fläkt Woods is a global leader in air management.
We specialize in the design and manufacture of a wide
range of air climate and air movement solutions.
FWG-eQ TopMaster GB 2012.10-8180
© Copyright 2012 Fläkt Woods Group
Condesign Infocom AB +46 36 291 42 10
Our collective experience is unrivalled.
We are constantly aiming to provide systems that
precisely deliver required function and performance as
well as maximum energy efficiency.