Single Package Heat Pump
Installation Instructions
TM
!
WARNING:
These instructions are intended primarily to assist qualifi ed individuals experienced in the proper installation of this appliance. Some local codes require licensed installation/service personnel for this type of equipment. Read all instructions carefully before starting the installation.
Read these instructions thoroughly before starting the installation. Follow all precautions and warnings contained within these instructions and on the unit.
Improper installation, adjustment, alteration, service, or maintenance can cause injury or property damage. Refer to this manual. For assistance or additional information consult a qualifi ed installer or service agency.
Do not store or use gasoline or other fl ammable vapors and liquids in the vicinity of this or any other appliance.
DO NOT DESTROY. PLEASE READ CAREFULLY AND KEEP IN A SAFE PLACE FOR FUTURE REFERENCE.
SECTION 1. OWNER INFORMATION
5
4
3
6
2
1 4
5
6
3
2
1
WINTER HEATING SUMMER COOLING
1. Outdoor air enters the heat pump.
2. The cold, heat-transfer section (outdoor coil) extracts the heat from the air as the refrigerant evaporates from a liquid to a cold gas.
3. The refrigerant, compressed to a hot gas by the heat pump, carries the heat to the heattransfer section (indoor coil).
4. The hot, heat-transfer section (indoor coil) releases the heat as the refrigerant condenses
from a gas to a liquid.
5. The blower circulates the heat throughout the home via the supply duct.
6. The refrigerant returns to the outdoor coil and evaporates once again to absorb more heat.
1. Indoor air enters the return air duct.
2. The cold, heat-transfer section (indoor coil) extracts the heat from the air as the refrigerant evaporates from a liquid to a cold gas.
3. The refrigerant, drawn to the heat pump and compressed to a hot gas, carries the heat outdoors.
4. The hot, heat-transfer section (outdoor coil) releases the heat as the refrigerant condenses from a gas to a liquid.
5. The heat pump (outdoor fan) discharges the heat to the outside air.
6. The refrigerant returns to the indoor coil and evaporates once again to absorb more heat.
2
It is the sole responsibility of the homeowner to make certain that heat pump has been correctly set up and adjusted to operate properly.
2. Resetting circuit breakers or other switches.
3. Adjusting or calibrating of thermostat.
The Manufacturer warrants the heat pump to be free from defects in material or workmanship for a period of one year. We will not be responsible for any costs found necessary to correct problems due to improper setup, improper installation, adjustments, improper operating procedure on the part of the user, etc.
To avoid misunderstandings at a later date, carefully review these responsibilities with your dealer or service company.
The heat pump system will heat and cool your home and save your energy dollars.
Some specifi c examples of service calls which are not included in the limited warranty are:
1. Correcting wiring problems in the electrical circuit supplying the heat pump.
During the summer, a heat pump cools a house by absorbing heat from within the house and exhausting it outdoors. During the winter, a heat pump heats a house by absorbing heat outdoors and exhausting it indoors. This is an effi cient heating means because you pay for “moving” heat from outdoors to indoors, but do not pay to generate the heat.
OPERATING INSTRUCTIONS
To Operate Your Heat Pump For Cooling —
1. Set the thermostat system switch to COOL and the thermostat fan switch to AUTO. See
Figure 1.
2. Set the thermostat temperature selector to the desired cooling temperature. The outdoor unit fan, the indoor blower, and the compressor will all cycle on and off to maintain the indoor temperature at the desired cooling level.
MODE
SELECT
FAN
SWITCH
TEMPERATURE
SELECTOR
NOTE: If the thermostat temperature level is re-adjusted, or if the thermostat system switch is re-positioned, the outdoor unit fan and the compressor may not start immediately. A protective timer circuit holds the compressor and the outdoor fan off for approximately six minutes following a previous operation or the interruption of the main electric power
To Operate Your Heat Pump For Heating —
Figure 1. Typical Thermostat
Defrost — During cold weather heating operation, the outdoor unit will develop a coating of snow and ice on the heat transfer coil. This is normal and the unit will periodically defrost itself. During the defrost cycle, the outdoor fan will stop, while the compressor continues to run and heat the outdoor coil, causing the snow and ice to melt.
During defrost, there may be some steam rise from the outdoor unit as the warm coil causes some melted frost to evaporate.
1. Set the thermostat system switch for HEAT and the thermostat fan switch to AUTO. See
Figure 1.
SPECIFICATIONS
2. Set the thermostat temperature selector to the desired heating temperature. The outdoor unit fan, the indoor blower, and the compressor will all cycle on and off to maintain the indoor temperature at the desired heating level.
Single Package Heat Pumps are designed for outdoor rooftop or ground level slab installations.
The units are shipped ready for horizontal duct connections and are easily converted for down fl ow applications.
NOTE: If the thermostat temperature level is re-adjusted, or if the thermostat system switch is re-positioned, the outdoor unit fan and the compressor may not start immediately. A protective timer circuit holds the compressor and the outdoor fan off for approximately six minutes following a previous operation or the interruption of the main electrical power.
All models are shipped from the factory with the following:
1. Zero clearance to combustibles
2. Multi-tap fi xed -torque blower.
3. Blower Speed Relay.
4. Horizontal or Down fl ow duct connections.
Emergency Heat — Some thermostats will include a system switch position termed EM HT or AUX HT, etc. This is a back-up heating mode available if supplemental electrical resistance heat is installed. With the system switch set to
EM HT, etc., the compressor and outdoor fan will be locked off and supplemental heat (electric resistance heating) will be used as a source of heat. Sustained use of electric resistance heat in place of the heat pump will result in an increase in electric utility costs.
The unit dimensions are shown in Figure 2.
Optional field-installed electric heater kits are available in 5,8,10,15, and 20Kw heating capacities. A separate installation instruction document for the electric heaters and their application accompanies this one. A two stage heat 24VAC thermostat should be used with electric heater kits installed.
3
4
SAFETY CONSIDERATIONS
It is the responsibility of the installer to ensure that the installation is made in accordance with all applicable local and national codes.
data label. All units have been securely packaged at the point of shipment. After unpacking the unit, carefully inspect it for apparent and concealed damage. Claims for damage should be fi led with the carrier by the consignee.
WARNING:
I m p r o p e r i n s t a l l a t i o n , s e r v i c e , adjustment, or maintenance may cause explosion, fi re, electrical shock or other hazardous conditions which may result in personal injury or property damage. Unless otherwise noted in these instructions, only factory authorized kits or accessories may be used with this product. Noncompliance may void the unit’s warranty.
Labels, Tags — When working with this equipment, follow all precautions in the literature, on tags, and on labels provided with the unit and/or approved fi eld installed kits. The type of hazard and severity are described on each label or tag.
Requirements and Codes — The installer must comply with all local codes and regulations which govern this type equipment. Local codes and regulations take precedence over any recommendations contained in these instructions.
All electrical wiring must be made in accordance with local codes and regulations and with the
National Electric Code (ANSI/NFPA 70) or in
Canada the Canadian Electric Code Part 1 CSA
C.22.1. Air Ducts must be installed in accordance with the standards of the National Fire Protection
Association “Standards for Installation of Air
Conditioning and Ventilation Systems” (NFPA
90A), “Standard for Installation of Residence
Type Warm Air Heating and Air Conditioning
Systems” (NFPA 90B), these instructions and all applicable local codes.
NFPA publications are available by writing:
National Fire Protection Association
Quincy, Maine 02269
Pressures Within The System — This equipment contains R-410A refrigerant under high pressure. Installation or servicing should only be performed by qualifi ed trained personnel thoroughly familiar with this type equipment.
CAUTION:
This unit uses refrigerant R-410A. DO
NOT under any circumstances use any other refrigerant besides R-410A in this unit. Use of another refrigerant will damage this unit.
INSTALLATION REQUIREMENTS
Unit Location — This heat pump is designed only for outdoor installations. Choosing the location of the unit should be based on minimizing the length of the supply and return ducts. Consideration should also be given to availability of electric power, service access, noise, and shade. Suffi cient clearance for unobstructed airfl ow through the outdoor coil must be maintained in order to achieve rated performance See Figure 3 for minimum clearances to obstructions.
Air Filters — A suitable air fi lter must be installed in the return air system. Air fi lter pressure drop must not exceed 0.08 inches w.c. at 300 fpm.
Equipment Check — Before beginning the installation, verify that the unit model is correct for the job. The unit model number is printed on the
Condensate Drain — Condensate is removed from the unit through the 3/4” female pipe fi tting located on the front side of the unit. See Figure
4. Install a 2 inch condensate trap in the drain line of the same size and prime with water. When
24 9/10
3/4" NPT Female
Drain Connector
DOWNFLOW
SUPPLY DUCT
OPENING
13 1/2
16
CG
13 1/2
16
47 1/2
B
13 3/10
12
30.0
27.2
23.6
1.8
1.75 Ø Power Entry (Capped)
1.25 Ø Power Entry
0.88 Ø Control Wiring Entry
12
A
23 1/2
Top View
DOWNFLOW
RETURN DUCT
OPENING
C
14.7
5.0
SUPPLY
13.5
8
16.0
13.45
RETURN
16.0
13.5
4.0
CONDENSING
COIL
Model Number
Q6SD
X24
X30
X36
X42
X48
X60
4.00
11.75
22.75
55.8
Side View
Figure 2. Physical Dimensions
Back View
Unit
Weight
440
450
460
560
570
580
28.0
29.5
29.5
29.5
Center of Gravity
A B
28.0
25.5
28.0
26.0
25.5
26.0
26.0
26.0
Height (in inches)
C with base rails without base rails
39.0
35.3
39.0
35.3
39.0
43.0
43.0
43.0
35.3
39.3
39.3
39.3
Table 1. center of Gravity and Unit Shipping Weights
5
72"
36"
36"
36"
6
0"
Figure 3. Minimum Clearances connecting rigid drain line, hold the female fi tting with a wrench to prevent twisting. Do not over
tighten! Refer to local codes and restrictions for proper condensate disposal requirements.
UNIT INSTALLATION
Ground Level — When installing the unit at ground level, provide a concrete mounting pad separate from the building foundation. The pad must be level to insure proper condensate disposal and strong enough to support the unit’s weight. Refer to Figure 5. Make sure the slab is a minimum of 2” above the grade and in an area that drains well. See Figure 5.
Rigging and Hoisting — The unit should be lifted using slings and spreader bars. The spreader bars are necessary to prevent damaging the top of the unit’s cabinet. Make sure that the lifting equipment is adequate for the load. Refer to Figure 2 for unit weights. Keep the unit in an upright position at all times. For rooftop installations, remove and discard the two supports attached beneath the unit.
WARNING:
To avoid the risk of property damage or personal injury; it is the rigger’s responsibility to insure that whatever means are used to hoist the unit are safe and adequate.
Condensate Drain
Figure 4. Condensate Drain
CAUTION:
All panels must be securely in place when rigging and hoisting.
The rigging must be located outside the unit’s center of gravity. Refer to Figure 2 for center of gravity locations.
Rooftop — For rooftop installations use the appropriate accessory roof curb and follow all instructions included with it. Make sure the two supports beneath the unit have been removed.
Locate the unit according to local building codes and ordinances. The curb must be level to insure proper condensate drainage. See Figure 6.
The roof must be capable of handling the weight of the unit. See Figure 2 for unit weights. Reinforce the roof if required.
AIR DUCTS
This unit is designed only for use with a supply and return duct. Air ducts should be installed in accordance with the standards of the National
Fire Protection Association “Standard for
Installation of Air Conditioning Systems” (NFPA
90A), “Standard for Installation of Residence Type
Warm Air Heating and Air Conditioning Systems”
(NFPA 90B), and all applicable local codes.
Design the duct work according to methods described by the National Warm Air Heating and Air Conditioning Association (ACCA). The ducts must be properly sized not to exceed .2” w.c. pressure drop at 400 scfm per nominal ton of cooling capacity.
Duct work should be attached directly to the unit fl anges for horizontal applications. On roof curb installations the ducts must be attached to the curb hangers, not the unit.
the supply duct work. Acoustical insulation must be in accordance with the current revision of the
Sheet Metal and Air Conditioning Contractors
National Association (SMACNA) application standard for duct liners. Duct lining must be UL classifi ed batts or blankets with a fi re hazard classifi cation of FHC-25/50 or less. Fiber duct work may be used in place of internal duct liners if the fi ber duct work is in accordance with the current revision of the SMACNA construction standard on fi brous glass ducts. Fibrous duct work and internal acoustical lining must be NFPA
Class 1 air ducts when tested per UL Standard
181 for Class 1 ducts.
Horizontal to Down fl ow Conversion — The unit is shipped ready for horizontal duct connections.
If down fl ow ducts are required, the unit must be converted following the steps below for both the supply and return ducts.
1) Locate the duct cap inside the duct openings and remove the screw holding it in place.
2) Lift the cap out of the unit. (The cap can be pushed up from the bottom by reaching through the fork slot).
3) Cover the horizontal duct opening with the cap. The insulation will be on the indoor side.
4) Fasten the cover with screws and seal to prevent air leakage.
Unconditioned Spaces — All duct work passing through unconditioned space must be properly insulated to minimize duct losses and prevent condensation. Use insulation with an outer vapor barrier. Refer to local codes for insulation material requirements.
Clearance — These units are approved for 0 inch clearance.
ELECTRICAL WIRING
Acoustical Duct Work — Certain installations may require the use of acoustical lining inside
General — Electrical power wiring must be made in accordance with all applicable local codes and ordinances, and with the current revision of the
2"
Figure 5. Ground Level Installation
Figure 6. Roof Top Installation
7
8
National Electric Code NFPA 70 or in Canada CSA
C.22.1 - Canadian Electrical Code Part 1. If any of the original wire as supplied with the unit must be replaced, it must be replaced with material of the same gage and temperature rating.
WARNING:
To avoid the risk of electrical shock, personal injury, or death, disconnect all electrical power to the unit before performing any maintenance or service.
The unit may have more than one electrical power supply.
Line Voltage — Before proceeding with the electrical connections, make certain that the voltage, frequency, and phase of the supply source are the same as those specifi ed on the unit rating plate. Also verify that the service provided by the utility is suffi cient to handle the additional load imposed by this equipment.
WARNING:
The unit cabinet must have and uninterrupted or unbroken electrical ground to minimize personal injury if an electrical fault should occur. This ground may consist of electrical wire or approved conduit when installed in accordance with existing national or local codes.
Blower Speed — For optimum system performance and comfort, it may be necessary to change the factory set speed. To change the blower speed:
1. Disconnect all electrical power to the unit and remove the blower panel.
2. Locate the orange and red wires terminated to the blower motor. The orange wire controls cooling operation while the red wire controls heating operation.
See the unit wiring label for proper high and low voltage wiring. Make all electrical connections in accordance with all applicable codes and ordinances.
3. Verify the required speed from the airfl ow data found in Table 1. Place appropriate wire on the appropriate motor speed tap for the required airfl ow point.
Use a separate branch electrical circuit for this unit. A means of electrical disconnect must be located within sight of and readily accessibility to the unit. Internally mounted circuit breakers are available as fi eld installed options. These circuit breakers can be used as an electrical disconnect.
CAUTION:
To avoid personal injury or property damage, make certain that the motor leads cannot come into contact with any uninsulated metal components of the unit.
The unit is shipped from the factory wired for 240 volt transformer operation. For 208 volt operation, remove the lead from the transformer terminal marked 240V and connect it to the terminal marked 208V. For maximum ampacity and over current protection, see the unit rating plate.
Check all factory wiring per the unit wiring diagram and inspect the factory wiring connections to be sure none loosened during shipping or installation.
Provide power supply (or supplies) for the unit in accordance with the unit wiring diagram, and the unit rating plate. Connect the line-voltage leads to the corresponding terminals on the contactor
(or the circuit breaker when the fi eld installed circuit breaker kits are used) inside the control compartment. Use only copper wire for the line voltage power supply to this unit. Use proper code agency listed conduit and a conduit connector for connecting the supply wires to the unit and for obtaining proper grounding. Grounding may also be accomplished by using the grounding lug provided in the control box.
Low Voltage Connections
Room Thermostat — Several options are available for a room thermostat depending on the accessories installed with the unit. Select a thermostat which operates in conjunction with the installed accessories. The thermostat should be mounted about fi ve feet above the ground on an inside wall. The thermostat should be kept away from drafts, slamming doors, lamps, direct sunlight, or in line with the supply air fl ow.
To install the thermostat:
1. Position the sub base on an inside wall and mark the mounting holes and thermostat cable openings.
2. Cut out the cable opening and route the thermostat cable from the unit’s low voltage compartment to the thermostat location.
The thermostat cable is supplied by the installer.
3. Connect the cable leads to the sub base or thermostat terminals and to the unit’s low voltage pigtails as shown in Figure 8.
A system wiring diagram is also provided on the inside of the control panel cover.
4. Secure sub base or thermostat to the wall using screws provided with the thermostat.
5. If sub base is used, install the correct thermostat housing to sub base.
6. Refer to thermostat instruction sheet for complete detailed mounting information.
Defrost Cycle Timer — The defrost cycle timer controls the time interval of the hot gas defrost after the defrost sensor closes. It is located in the lower left corner of the defrost control board on the low voltage side of the control box. Three interval settings are available: 30 minutes, 60 minutes, and 90 minutes. Time setting selection is dependent on the climate where the unit is being installed.
Example 1. Dry climate of Southern Arizona.
A 90 minute setting is recommended.
Example 2. Moist climate of Seattle,
Washington. A 30 minute setting is recommended.
DEFROST CONTROL BOARD OPERATION
AND TESTING
1. Terminals “R”-”C” must have 24±V present between them in order for the time delay and defrost sequences to be operational.
2. Jumper the “T2”-”DFT” test pins. This will indicate to the board that the defrost T-stat is closed(if the compressor is running).
Defrost T-stat is closed at 32° or below and is open at 68° or above. But it’s state is unknown if the temperature is between 32°F and 68°F. The defrost thermostat tells the board whether a defrost cycle needs to be started or terminated. With the DFT closed the unit will run for 30/60/90 minutes in heat mode and then defrost the outdoor coil. The defrost will turn off the outdoor fan, turn on the compressor and raise the coil temperature to
68°F. This will open the DFT and terminate the defrost. If the DFT does not open the defrost will end after 10 minutes.
3. Defrost board speed-up. With compressor running in heat mode, next jump the “Test” pin to “C” on terminal strip. This will initiate a defrost test in 5, 10 or 15 seconds (This is determined by the 30, 60 or 90 minute defrost pin settings. The factory setting will be 30 minutes). Note that this will bypass the compressor off delay when the unit goes into defrost test and if left in defrost test, the delay will be bypassed when the test is terminated by the processor. If the jumper is removed before the test is over the processor will perform the remainder of a normal defrost.
See step 2 above.
To set the cycle timer, place the timing pin on the defrost control board to the desired time interval post.
Note: All units are shipped from the factory with the default time setting of 30 minutes.
Field Installed Electric Heat — These Single
Package Heat Pumps are designed to allow optional electric heat to be fi eld installed as required by the building’s particular heating load.
The options available for each unit are shown in the heater kit installation instructions. As noted in the instructions, a fi eld installed circuit breaker kit is available as a means of electrical disconnect for the unit.
Install the heater kits as directed by the installation instructions that come as part of the heater kit.
Follow all cautions and warnings as directed.
4. Remove the jumpers.
Note: The delay/no-delay pin concer ns compressor operation during defrosts. The default setting is delay. Reciprocating compressors should only use this setting in conjunction with an approved hard start kit. Scroll compressors that have noise issues while going into or coming out of defrost should use this 30 second delay to reduce the defrost noise. To switch from no-delay to delay remove the pin from the “no-delay” pin location and shift it to the “delay” pin location.
Speed up changes:
Manually initiating a defrost will cause the compressor to run continually when entering defrost.
Normal defrost operation:
To test normal defrost operation when the temperature is above 35°F, jumper “R” to
9
10
“DFT” on the 624656 board and allow the unit to run for 30 minutes. Defrost will continue until the “R” to “DFT” jumper is removed or for 10 minutes. Remove the jumper.
The 5 minute time delay feature can be shortened
1 time to 1 second by jumping the “Test” to “C” terminal. Remove the jumper and repeat as desired.
• Verify that the outdoor fan turns freely.
• Verify that the power supply branch circuit overcurrent protection is sized properly.
• Verify that the thermostat is wired correctly.
The thermostat function switch should be set to “Off’ and the thermostat fan switch should be set to “Auto.”
Note: If jumper is left on the “Test” to “common” pins permanently, the defrost cycle will become inoperable.
Start-Up Procedure
Close all electrical disconnects to energize the system.
Defrost Test Procedure for 624656
1. Jumper “T2” to “DFT” at the test terminals.
2. With unit running in heat mode, short the
“TEST” terminal to the common terminal near it. This will speed up the board and cause it to enter defrost mode in 5/10/15 seconds depending on the defrost time selection.
Compressor delay will not function during speed-up.
3. This test will end in 5 seconds if the “TEST”common short is not removed.
4. Remove both the short and the “T2” to “DFT” jumper to terminate the defrost cycle. The
30 second compressor delay should operate normally.
5. Test is complete, reset thermostat to home owner preference.
START UP AND SYSTEM CHECK
Pre-Start Check List
WARNING:
If the unit is equipped with a crankcase heater, allow 24 hours prior to continuing the start up procedures to allow for heating of the refrigerant compressor crankcase. Failure to comply may result in damage and could cause premature failure of the system. This warning should be followed at initial start up and any time the power has been removed for 12 hours or longer.
Air Circulation — Leave the thermostat system switch set to “Off” and set the thermostat fan switch to “On.” The blower motor should run continuously. Check for air delivery at the register(s). Ensure that there are no obstructions at the registers or in the duct work. Set thermostat fan switch to “Auto.”
• Verify that the unit is level to allow proper condensate drainage.
•
•
Verify that there is free airfl ow to and from the outdoor coil and that all clearance requirements are met.
Verify that the duct work is sealed to prevent air leakage.
Short Cycle Protection — With the system operating in cooling mode, note the temperature setting of the thermostat and gradually raise the set-point temperature until the unit de-energizes.
Immediately lower the set point temperature of the thermostat to its original setting and verify that the indoor blower is energized. Verify that after approximately 5 minutes the compressor and fan energize and that the temperature of the discharge air is cooler than the room temperature.
• Verify that the line voltage power leads are securely connected and the unit is properly grounded.
• Verify that the low voltage wires are securely connected to the correct leads on the low voltage terminal strip.
• Verify that all exterior panels are replaced and securely fastened.
System Cooling
1. Set the thermostat system switch to “Cool” and the thermostat fan switch to “Auto”.
Gradually lower the thermostat temperature switch below room temperature and observe that the blower, compressor, and
fan energize. Check that air cooler than room temperature is being discharged at the register. Listen for any unusual noises.
2. After allowing the unit to run for several minutes, set the temperature selector above room temperature.
- The fan and compressor cycles off with the thermostat.
- The blower should also stop unless fan switch is set to “ON” position.
equipment. Some local codes require licensed installation/service personnel to service this type of equipment. Under no circumstances should the owner attempt to install and/or service this equipment. Failure to comply with this warning could result in property damage, personal injury, or death.
System Heating — If the unit has been equipped with optional electric heater kits, set the system thermostat switch to HEAT and set the thermostat fan switch to AUTO. Verify that the compressor and outdoor fan are not energized but that the blower and heaters are. Check for warm air at the supply registers.
CAUTION:
Use care when removing parts from this unit. Personal injury can result from sharp metal edges present in all equipment of sheet metal construction.
UNIT MAINTENANCE
WARNING:
To avoid risk of electrical shock, personal injury, or death, disconnect all electrical power to the unit before performing any maintenance or service. The unit may have more than one electrical supply.
Routine Maintenance — Proper maintenance is important to achieve optimum performance from the heat pump. The ability to properly perform maintenance on this equipment requires certain mechanical skills and tools. If you do not possess these skills, contact your dealer for maintenance.
Consult your local dealer about the availability of maintenance contracts. At a minimum, routine maintenance should include the following:
Refrigerant Charging — Packaged heat pumps are fully charged with R-410A refrigerant at the factory . The system refrigerant charge can be checked and adjusted through the service ports provided in the front panel. Use only gauge lines which have a “Schrader” depression device present to actuate the valve. Draw a vacuum on gauge lines to remove air before attaching them to the service ports on the unit. Refrigerant charging must be done by qualifi ed personnel familiar with safe and environmentally responsible refrigerant handling procedures.
1. Inspect and clean or replace air fi lters at the beginning of each heating and cooling season, or more frequently if required.
2. Inspect the condensate drain and outdoor coil at the beginning of each cooling season.
Remove any debris. Clean the outdoor coil and louvers as necessary using a mild detergent and water. Rinse thoroughly with water.
3. Inspect the electrical connections for tightness at the beginning of each heating and cooling season. Service as necessary.
WARNING:
These single Packaged Heat Pumps are shipped fully charged with R-410A refrigerant and ready for installation.
When a system is installed according to these instructions, no refrigerant charging is required. If repairs make it necessary for evacuation and charging, it should only be done by qualifi ed, trained personnel thoroughly familiar with this
CAUTION:
The unit should never be operated without a fi lter in the return air system.
Replace disposable fi lters with the same type and size.
4. The motors for the circulating air blower and the outdoor fan are pre-lubricated at the factory. No further oiling is required for the life of this product.
11
FROM
BLOWER
RELAY
Green
C
ECONOMIZER
PLUG
1
2
Blue
6
7
8
9
3
4
5
W2
Y2
Y1
R
G
O
E
INDOOR
THERMOSTAT
SUB-BASE
DEFROST
BOARD
3
4
1
2
5
6
7
8
9
Brown
Orange
Accessory
Heat Plug
Typical Wiring (Field Supplied) for 1-Stage Cool, 1 Stage Electric Heat
12
FROM
BLOWER
RELAY
O
Green
Optional
Outdoor
Thermostat
(Field Supplied)
ECONOMIZER
PLUG
Blue
3
4
1
2
5
6
7
8
9
C
W2
Y2
Y1
R
G
O
E
INDOOR
THERMOSTAT
SUB-BASE
DEFROST
BOARD
7
8
9
5
6
3
4
1
2
Brown
Orange
Accessory
Heat Plug
Typical Wiring (Field Supplied) for 2-Stage Cool, 2-Stage Electric Heat with an Optional Outdoor Thermostat
Figure 7. Typical Heat Pump Thermostat Connections
Model number
Q6SD
Tap
External Static Pressure Drop - inches water column
0.1
0.2
0.3
X24
* Tap T1
** Tap T2
Tap T3
Tap T4
Tap T5
** Tap T1
* Tap T2
X30 Tap T3
Tap T4
Tap T5
** Tap T1
Tap T2
X36 * Tap T3
Tap T4
Tap T5
X42
** Tap T1
Tap T2
Tap T3
* Tap T4
Tap T5
* Tap T1
** Tap T2
Tap T3 X48
Tap T4
Tap T5
Tap T1
** Tap T2
X60 * Tap T3
Tap T4
Tap T5
* Denotes factory set cooling speed
** Denotes factory set electric heating speed
NOTE: Airfl ow performance is with a dry coil
1960
2090
1515
1580
1740
1960
2090
1150
1230
1400
1524
1700
1515
1580
1740
1400
1600
1700
1150
1230
1464
1600
1700
1110
1211
1400
1600
1700
1211
1275
Table 2. Blower Curves
1910
2050
1450
1520
1690
1910
2050
1050
1190
1350
1476
1650
1450
1520
1690
1350
1500
1650
1050
1190
1394
1500
1650
869
996
1350
1500
1650
996
1077
1840
2010
1380
1460
1650
1840
2010
1000
1120
1200
1424
1600
1380
1460
1650
1200
1400
1600
1000
1120
1332
1400
1600
529
700
1200
1400
1600
700
940
0.4
0.5
0.6
1820
1975
1350
1400
1600
1820
1975
950
1080
1150
1379
1565
1350
1400
1600
1150
1300
1565
950
1080
1272
1300
1565
-
609
1150
1300
1565
609
876
1780
1940
1300
1360
1540
1780
1940
850
1000
1080
1329
1530
1300
1360
1540
1080
1200
1530
850
1000
1216
1200
1530
-
-
1080
1200
1530
-
807
1740
1900
1250
1300
1500
1740
1900
780
950
1030
1268
1480
1250
1300
1500
1030
1050
1480
780
950
1143
1050
1480
-
-
1030
1050
1480
-
732
13
Q6SD-X24 Charging Chart - Cooling
600
580
560
540
520
500
480
460
440
420
400
380
360
340
320
300
280
260
240
220
200
75
Remove refrigerant when above curve
80 85 90 95 100 105 110
Liquid Temperature (F)
Add refrigerant when below curve
115 120 125 130 135
Figure 8. Charging Chart for 2 Ton Units
14
Q6SD-X30 Charging Chart - Cooling
600
580
560
540
520
500
480
460
440
420
400
380
360
340
320
300
280
260
240
220
200
75
Remove refrigerant when above curve
80 85 90 95 100 105 110
Liquid Temperature (F)
Add refrigerant when below curve
115 120 125 130 135
Figure 9. Charging Chart for 2.5 Ton Units
Q6SD-X36 Charging Chart- Cooling
460
440
420
400
380
360
340
320
300
280
260
600
580
560
540
520
500
480
240
220
200
75
Remove refrigerant when above curve
80 85 90 95 100 105 110
Liquid Temperature (F)
Add refrigerant when below curve
115 120 125 130 135
Figure 10. Charging Chart for 3 Ton Units
Q6SD-X42 Charging Chart- Cooling
600
580
560
540
520
500
480
460
440
420
400
380
360
340
320
300
280
260
240
220
200
75
Remove refrigerant when above curve
80
Add refrigerant when below curve
85 90 95 100 105 110 115 120 125 130 135
Liquid Temperature (F)
Figure 11. Charging Chart for 3.5 Ton Units
15
Q6SD-X48 Charging Graph - Cooling
600
580
560
540
520
500
480
460
440
420
400
380
360
340
320
300
280
260
240
220
200
75
Remove refrigerant when above curve
80 85 90 95 100 105 110
Liquid Temperature (F)
Add refrigerant when below curve
115 120 125 130 135
Figure 12. Charging Chart for 4 Ton Units
16
Q6SD-X60 Charging Graph - Cooling
600
580
560
540
520
500
480
460
440
420
400
380
360
340
320
300
280
260
240
220
200
75
Remove refrigerant when above curve
80 85 90 95 100 105 110
Liquid Temperature (F)
Add refrigerant when below curve
115 120 125 130 135
Figure 13. Charging Chart for 5 Ton Units
T2
DFT
TEST
C
Y
O
W2
R
E
Low
Voltage
Terminals
W2
R
DFT
T1
T2
C
Y
O
E
DF1 DF2
Figure 10: Wiring Diagram
17
18
19
INSTALLER: PLEASE LEAVE THESE
INSTALLATION INSTRUCTIONS WITH
THE HOMEOWNER.
O’Fallon MO
¢709130q¤
7091300(Replaces 708869A)
Specifi cations and illustrations subject to change without notice or incurring obligations.
Printed in U.S.A. (10/09)
7091300