Single Package Heat Pump

Installation Instructions

TM

!

WARNING:

These instructions are intended primarily to assist qualifi ed individuals experienced in the proper installation of this appliance. Some local codes require licensed installation/service personnel for this type of equipment. Read all instructions carefully before starting the installation.

Read these instructions thoroughly before starting the installation. Follow all precautions and warnings contained within these instructions and on the unit.

Improper installation, adjustment, alteration, service, or maintenance can cause injury or property damage. Refer to this manual. For assistance or additional information consult a qualifi ed installer or service agency.

Do not store or use gasoline or other fl ammable vapors and liquids in the vicinity of this or any other appliance.

DO NOT DESTROY. PLEASE READ CAREFULLY AND KEEP IN A SAFE PLACE FOR FUTURE REFERENCE.

SECTION 1. OWNER INFORMATION

5

4

3

6

2

1 4

5

6

3

2

1

WINTER HEATING SUMMER COOLING

1. Outdoor air enters the heat pump.

2. The cold, heat-transfer section (outdoor coil) extracts the heat from the air as the refrigerant evaporates from a liquid to a cold gas.

3. The refrigerant, compressed to a hot gas by the heat pump, carries the heat to the heattransfer section (indoor coil).

4. The hot, heat-transfer section (indoor coil) releases the heat as the refrigerant condenses

from a gas to a liquid.

5. The blower circulates the heat throughout the home via the supply duct.

6. The refrigerant returns to the outdoor coil and evaporates once again to absorb more heat.

1. Indoor air enters the return air duct.

2. The cold, heat-transfer section (indoor coil) extracts the heat from the air as the refrigerant evaporates from a liquid to a cold gas.

3. The refrigerant, drawn to the heat pump and compressed to a hot gas, carries the heat outdoors.

4. The hot, heat-transfer section (outdoor coil) releases the heat as the refrigerant condenses from a gas to a liquid.

5. The heat pump (outdoor fan) discharges the heat to the outside air.

6. The refrigerant returns to the indoor coil and evaporates once again to absorb more heat.

2

It is the sole responsibility of the homeowner to make certain that heat pump has been correctly set up and adjusted to operate properly.

2. Resetting circuit breakers or other switches.

3. Adjusting or calibrating of thermostat.

The Manufacturer warrants the heat pump to be free from defects in material or workmanship for a period of one year. We will not be responsible for any costs found necessary to correct problems due to improper setup, improper installation, adjustments, improper operating procedure on the part of the user, etc.

To avoid misunderstandings at a later date, carefully review these responsibilities with your dealer or service company.

The heat pump system will heat and cool your home and save your energy dollars.

Some specifi c examples of service calls which are not included in the limited warranty are:

1. Correcting wiring problems in the electrical circuit supplying the heat pump.

During the summer, a heat pump cools a house by absorbing heat from within the house and exhausting it outdoors. During the winter, a heat pump heats a house by absorbing heat outdoors and exhausting it indoors. This is an effi cient heating means because you pay for “moving” heat from outdoors to indoors, but do not pay to generate the heat.

OPERATING INSTRUCTIONS

To Operate Your Heat Pump For Cooling —

1. Set the thermostat system switch to COOL and the thermostat fan switch to AUTO. See

Figure 1.

2. Set the thermostat temperature selector to the desired cooling temperature. The outdoor unit fan, the indoor blower, and the compressor will all cycle on and off to maintain the indoor temperature at the desired cooling level.

MODE

SELECT

FAN

SWITCH

TEMPERATURE

SELECTOR

NOTE: If the thermostat temperature level is re-adjusted, or if the thermostat system switch is re-positioned, the outdoor unit fan and the compressor may not start immediately. A protective timer circuit holds the compressor and the outdoor fan off for approximately six minutes following a previous operation or the interruption of the main electric power

To Operate Your Heat Pump For Heating —

Figure 1. Typical Thermostat

Defrost — During cold weather heating operation, the outdoor unit will develop a coating of snow and ice on the heat transfer coil. This is normal and the unit will periodically defrost itself. During the defrost cycle, the outdoor fan will stop, while the compressor continues to run and heat the outdoor coil, causing the snow and ice to melt.

During defrost, there may be some steam rise from the outdoor unit as the warm coil causes some melted frost to evaporate.

1. Set the thermostat system switch for HEAT and the thermostat fan switch to AUTO. See

Figure 1.

SPECIFICATIONS

2. Set the thermostat temperature selector to the desired heating temperature. The outdoor unit fan, the indoor blower, and the compressor will all cycle on and off to maintain the indoor temperature at the desired heating level.

Single Package Heat Pumps are designed for outdoor rooftop or ground level slab installations.

The units are shipped ready for horizontal duct connections and are easily converted for down fl ow applications.

NOTE: If the thermostat temperature level is re-adjusted, or if the thermostat system switch is re-positioned, the outdoor unit fan and the compressor may not start immediately. A protective timer circuit holds the compressor and the outdoor fan off for approximately six minutes following a previous operation or the interruption of the main electrical power.

All models are shipped from the factory with the following:

1. Zero clearance to combustibles

2. Multi-tap fi xed -torque blower.

3. Blower Speed Relay.

4. Horizontal or Down fl ow duct connections.

Emergency Heat — Some thermostats will include a system switch position termed EM HT or AUX HT, etc. This is a back-up heating mode available if supplemental electrical resistance heat is installed. With the system switch set to

EM HT, etc., the compressor and outdoor fan will be locked off and supplemental heat (electric resistance heating) will be used as a source of heat. Sustained use of electric resistance heat in place of the heat pump will result in an increase in electric utility costs.

The unit dimensions are shown in Figure 2.

Optional field-installed electric heater kits are available in 5,8,10,15, and 20Kw heating capacities. A separate installation instruction document for the electric heaters and their application accompanies this one. A two stage heat 24VAC thermostat should be used with electric heater kits installed.

3

4

SAFETY CONSIDERATIONS

It is the responsibility of the installer to ensure that the installation is made in accordance with all applicable local and national codes.

data label. All units have been securely packaged at the point of shipment. After unpacking the unit, carefully inspect it for apparent and concealed damage. Claims for damage should be fi led with the carrier by the consignee.

WARNING:

I m p r o p e r i n s t a l l a t i o n , s e r v i c e , adjustment, or maintenance may cause explosion, fi re, electrical shock or other hazardous conditions which may result in personal injury or property damage. Unless otherwise noted in these instructions, only factory authorized kits or accessories may be used with this product. Noncompliance may void the unit’s warranty.

Labels, Tags — When working with this equipment, follow all precautions in the literature, on tags, and on labels provided with the unit and/or approved fi eld installed kits. The type of hazard and severity are described on each label or tag.

Requirements and Codes — The installer must comply with all local codes and regulations which govern this type equipment. Local codes and regulations take precedence over any recommendations contained in these instructions.

All electrical wiring must be made in accordance with local codes and regulations and with the

National Electric Code (ANSI/NFPA 70) or in

Canada the Canadian Electric Code Part 1 CSA

C.22.1. Air Ducts must be installed in accordance with the standards of the National Fire Protection

Association “Standards for Installation of Air

Conditioning and Ventilation Systems” (NFPA

90A), “Standard for Installation of Residence

Type Warm Air Heating and Air Conditioning

Systems” (NFPA 90B), these instructions and all applicable local codes.

NFPA publications are available by writing:

National Fire Protection Association

Quincy, Maine 02269

Pressures Within The System — This equipment contains R-410A refrigerant under high pressure. Installation or servicing should only be performed by qualifi ed trained personnel thoroughly familiar with this type equipment.

CAUTION:

This unit uses refrigerant R-410A. DO

NOT under any circumstances use any other refrigerant besides R-410A in this unit. Use of another refrigerant will damage this unit.

INSTALLATION REQUIREMENTS

Unit Location — This heat pump is designed only for outdoor installations. Choosing the location of the unit should be based on minimizing the length of the supply and return ducts. Consideration should also be given to availability of electric power, service access, noise, and shade. Suffi cient clearance for unobstructed airfl ow through the outdoor coil must be maintained in order to achieve rated performance See Figure 3 for minimum clearances to obstructions.

Air Filters — A suitable air fi lter must be installed in the return air system. Air fi lter pressure drop must not exceed 0.08 inches w.c. at 300 fpm.

Equipment Check — Before beginning the installation, verify that the unit model is correct for the job. The unit model number is printed on the

Condensate Drain — Condensate is removed from the unit through the 3/4” female pipe fi tting located on the front side of the unit. See Figure

4. Install a 2 inch condensate trap in the drain line of the same size and prime with water. When

24 9/10

3/4" NPT Female

Drain Connector

DOWNFLOW

SUPPLY DUCT

OPENING

13 1/2

16

CG

13 1/2

16

47 1/2

B

13 3/10

12

30.0

27.2

23.6

1.8

1.75 Ø Power Entry (Capped)

1.25 Ø Power Entry

0.88 Ø Control Wiring Entry

12

A

23 1/2

Top View

DOWNFLOW

RETURN DUCT

OPENING

C

14.7

5.0

SUPPLY

13.5

8

16.0

13.45

RETURN

16.0

13.5

4.0

CONDENSING

COIL

Model Number

Q6SD

X24

X30

X36

X42

X48

X60

4.00

11.75

22.75

55.8

Side View

Figure 2. Physical Dimensions

Back View

Unit

Weight

440

450

460

560

570

580

28.0

29.5

29.5

29.5

Center of Gravity

A B

28.0

25.5

28.0

26.0

25.5

26.0

26.0

26.0

Height (in inches)

C with base rails without base rails

39.0

35.3

39.0

35.3

39.0

43.0

43.0

43.0

35.3

39.3

39.3

39.3

Table 1. center of Gravity and Unit Shipping Weights

5

72"

36"

36"

36"

6

0"

Figure 3. Minimum Clearances connecting rigid drain line, hold the female fi tting with a wrench to prevent twisting. Do not over

tighten! Refer to local codes and restrictions for proper condensate disposal requirements.

UNIT INSTALLATION

Ground Level — When installing the unit at ground level, provide a concrete mounting pad separate from the building foundation. The pad must be level to insure proper condensate disposal and strong enough to support the unit’s weight. Refer to Figure 5. Make sure the slab is a minimum of 2” above the grade and in an area that drains well. See Figure 5.

Rigging and Hoisting — The unit should be lifted using slings and spreader bars. The spreader bars are necessary to prevent damaging the top of the unit’s cabinet. Make sure that the lifting equipment is adequate for the load. Refer to Figure 2 for unit weights. Keep the unit in an upright position at all times. For rooftop installations, remove and discard the two supports attached beneath the unit.

WARNING:

To avoid the risk of property damage or personal injury; it is the rigger’s responsibility to insure that whatever means are used to hoist the unit are safe and adequate.

Condensate Drain

Figure 4. Condensate Drain

CAUTION:

All panels must be securely in place when rigging and hoisting.

The rigging must be located outside the unit’s center of gravity. Refer to Figure 2 for center of gravity locations.

Rooftop — For rooftop installations use the appropriate accessory roof curb and follow all instructions included with it. Make sure the two supports beneath the unit have been removed.

Locate the unit according to local building codes and ordinances. The curb must be level to insure proper condensate drainage. See Figure 6.

The roof must be capable of handling the weight of the unit. See Figure 2 for unit weights. Reinforce the roof if required.

AIR DUCTS

This unit is designed only for use with a supply and return duct. Air ducts should be installed in accordance with the standards of the National

Fire Protection Association “Standard for

Installation of Air Conditioning Systems” (NFPA

90A), “Standard for Installation of Residence Type

Warm Air Heating and Air Conditioning Systems”

(NFPA 90B), and all applicable local codes.

Design the duct work according to methods described by the National Warm Air Heating and Air Conditioning Association (ACCA). The ducts must be properly sized not to exceed .2” w.c. pressure drop at 400 scfm per nominal ton of cooling capacity.

Duct work should be attached directly to the unit fl anges for horizontal applications. On roof curb installations the ducts must be attached to the curb hangers, not the unit.

the supply duct work. Acoustical insulation must be in accordance with the current revision of the

Sheet Metal and Air Conditioning Contractors

National Association (SMACNA) application standard for duct liners. Duct lining must be UL classifi ed batts or blankets with a fi re hazard classifi cation of FHC-25/50 or less. Fiber duct work may be used in place of internal duct liners if the fi ber duct work is in accordance with the current revision of the SMACNA construction standard on fi brous glass ducts. Fibrous duct work and internal acoustical lining must be NFPA

Class 1 air ducts when tested per UL Standard

181 for Class 1 ducts.

Horizontal to Down fl ow Conversion — The unit is shipped ready for horizontal duct connections.

If down fl ow ducts are required, the unit must be converted following the steps below for both the supply and return ducts.

1) Locate the duct cap inside the duct openings and remove the screw holding it in place.

2) Lift the cap out of the unit. (The cap can be pushed up from the bottom by reaching through the fork slot).

3) Cover the horizontal duct opening with the cap. The insulation will be on the indoor side.

4) Fasten the cover with screws and seal to prevent air leakage.

Unconditioned Spaces — All duct work passing through unconditioned space must be properly insulated to minimize duct losses and prevent condensation. Use insulation with an outer vapor barrier. Refer to local codes for insulation material requirements.

Clearance — These units are approved for 0 inch clearance.

ELECTRICAL WIRING

Acoustical Duct Work — Certain installations may require the use of acoustical lining inside

General — Electrical power wiring must be made in accordance with all applicable local codes and ordinances, and with the current revision of the

2"

Figure 5. Ground Level Installation

Figure 6. Roof Top Installation

7

8

National Electric Code NFPA 70 or in Canada CSA

C.22.1 - Canadian Electrical Code Part 1. If any of the original wire as supplied with the unit must be replaced, it must be replaced with material of the same gage and temperature rating.

WARNING:

To avoid the risk of electrical shock, personal injury, or death, disconnect all electrical power to the unit before performing any maintenance or service.

The unit may have more than one electrical power supply.

Line Voltage — Before proceeding with the electrical connections, make certain that the voltage, frequency, and phase of the supply source are the same as those specifi ed on the unit rating plate. Also verify that the service provided by the utility is suffi cient to handle the additional load imposed by this equipment.

WARNING:

The unit cabinet must have and uninterrupted or unbroken electrical ground to minimize personal injury if an electrical fault should occur. This ground may consist of electrical wire or approved conduit when installed in accordance with existing national or local codes.

Blower Speed — For optimum system performance and comfort, it may be necessary to change the factory set speed. To change the blower speed:

1. Disconnect all electrical power to the unit and remove the blower panel.

2. Locate the orange and red wires terminated to the blower motor. The orange wire controls cooling operation while the red wire controls heating operation.

See the unit wiring label for proper high and low voltage wiring. Make all electrical connections in accordance with all applicable codes and ordinances.

3. Verify the required speed from the airfl ow data found in Table 1. Place appropriate wire on the appropriate motor speed tap for the required airfl ow point.

Use a separate branch electrical circuit for this unit. A means of electrical disconnect must be located within sight of and readily accessibility to the unit. Internally mounted circuit breakers are available as fi eld installed options. These circuit breakers can be used as an electrical disconnect.

CAUTION:

To avoid personal injury or property damage, make certain that the motor leads cannot come into contact with any uninsulated metal components of the unit.

The unit is shipped from the factory wired for 240 volt transformer operation. For 208 volt operation, remove the lead from the transformer terminal marked 240V and connect it to the terminal marked 208V. For maximum ampacity and over current protection, see the unit rating plate.

Check all factory wiring per the unit wiring diagram and inspect the factory wiring connections to be sure none loosened during shipping or installation.

Provide power supply (or supplies) for the unit in accordance with the unit wiring diagram, and the unit rating plate. Connect the line-voltage leads to the corresponding terminals on the contactor

(or the circuit breaker when the fi eld installed circuit breaker kits are used) inside the control compartment. Use only copper wire for the line voltage power supply to this unit. Use proper code agency listed conduit and a conduit connector for connecting the supply wires to the unit and for obtaining proper grounding. Grounding may also be accomplished by using the grounding lug provided in the control box.

Low Voltage Connections

Room Thermostat — Several options are available for a room thermostat depending on the accessories installed with the unit. Select a thermostat which operates in conjunction with the installed accessories. The thermostat should be mounted about fi ve feet above the ground on an inside wall. The thermostat should be kept away from drafts, slamming doors, lamps, direct sunlight, or in line with the supply air fl ow.

To install the thermostat:

1. Position the sub base on an inside wall and mark the mounting holes and thermostat cable openings.

2. Cut out the cable opening and route the thermostat cable from the unit’s low voltage compartment to the thermostat location.

The thermostat cable is supplied by the installer.

3. Connect the cable leads to the sub base or thermostat terminals and to the unit’s low voltage pigtails as shown in Figure 8.

A system wiring diagram is also provided on the inside of the control panel cover.

4. Secure sub base or thermostat to the wall using screws provided with the thermostat.

5. If sub base is used, install the correct thermostat housing to sub base.

6. Refer to thermostat instruction sheet for complete detailed mounting information.

Defrost Cycle Timer — The defrost cycle timer controls the time interval of the hot gas defrost after the defrost sensor closes. It is located in the lower left corner of the defrost control board on the low voltage side of the control box. Three interval settings are available: 30 minutes, 60 minutes, and 90 minutes. Time setting selection is dependent on the climate where the unit is being installed.

Example 1. Dry climate of Southern Arizona.

A 90 minute setting is recommended.

Example 2. Moist climate of Seattle,

Washington. A 30 minute setting is recommended.

DEFROST CONTROL BOARD OPERATION

AND TESTING

1. Terminals “R”-”C” must have 24±V present between them in order for the time delay and defrost sequences to be operational.

2. Jumper the “T2”-”DFT” test pins. This will indicate to the board that the defrost T-stat is closed(if the compressor is running).

Defrost T-stat is closed at 32° or below and is open at 68° or above. But it’s state is unknown if the temperature is between 32°F and 68°F. The defrost thermostat tells the board whether a defrost cycle needs to be started or terminated. With the DFT closed the unit will run for 30/60/90 minutes in heat mode and then defrost the outdoor coil. The defrost will turn off the outdoor fan, turn on the compressor and raise the coil temperature to

68°F. This will open the DFT and terminate the defrost. If the DFT does not open the defrost will end after 10 minutes.

3. Defrost board speed-up. With compressor running in heat mode, next jump the “Test” pin to “C” on terminal strip. This will initiate a defrost test in 5, 10 or 15 seconds (This is determined by the 30, 60 or 90 minute defrost pin settings. The factory setting will be 30 minutes). Note that this will bypass the compressor off delay when the unit goes into defrost test and if left in defrost test, the delay will be bypassed when the test is terminated by the processor. If the jumper is removed before the test is over the processor will perform the remainder of a normal defrost.

See step 2 above.

To set the cycle timer, place the timing pin on the defrost control board to the desired time interval post.

Note: All units are shipped from the factory with the default time setting of 30 minutes.

Field Installed Electric Heat — These Single

Package Heat Pumps are designed to allow optional electric heat to be fi eld installed as required by the building’s particular heating load.

The options available for each unit are shown in the heater kit installation instructions. As noted in the instructions, a fi eld installed circuit breaker kit is available as a means of electrical disconnect for the unit.

Install the heater kits as directed by the installation instructions that come as part of the heater kit.

Follow all cautions and warnings as directed.

4. Remove the jumpers.

Note: The delay/no-delay pin concer ns compressor operation during defrosts. The default setting is delay. Reciprocating compressors should only use this setting in conjunction with an approved hard start kit. Scroll compressors that have noise issues while going into or coming out of defrost should use this 30 second delay to reduce the defrost noise. To switch from no-delay to delay remove the pin from the “no-delay” pin location and shift it to the “delay” pin location.

Speed up changes:

Manually initiating a defrost will cause the compressor to run continually when entering defrost.

Normal defrost operation:

To test normal defrost operation when the temperature is above 35°F, jumper “R” to

9

10

“DFT” on the 624656 board and allow the unit to run for 30 minutes. Defrost will continue until the “R” to “DFT” jumper is removed or for 10 minutes. Remove the jumper.

The 5 minute time delay feature can be shortened

1 time to 1 second by jumping the “Test” to “C” terminal. Remove the jumper and repeat as desired.

• Verify that the outdoor fan turns freely.

• Verify that the power supply branch circuit overcurrent protection is sized properly.

• Verify that the thermostat is wired correctly.

The thermostat function switch should be set to “Off’ and the thermostat fan switch should be set to “Auto.”

Note: If jumper is left on the “Test” to “common” pins permanently, the defrost cycle will become inoperable.

Start-Up Procedure

Close all electrical disconnects to energize the system.

Defrost Test Procedure for 624656

1. Jumper “T2” to “DFT” at the test terminals.

2. With unit running in heat mode, short the

“TEST” terminal to the common terminal near it. This will speed up the board and cause it to enter defrost mode in 5/10/15 seconds depending on the defrost time selection.

Compressor delay will not function during speed-up.

3. This test will end in 5 seconds if the “TEST”common short is not removed.

4. Remove both the short and the “T2” to “DFT” jumper to terminate the defrost cycle. The

30 second compressor delay should operate normally.

5. Test is complete, reset thermostat to home owner preference.

START UP AND SYSTEM CHECK

Pre-Start Check List

WARNING:

If the unit is equipped with a crankcase heater, allow 24 hours prior to continuing the start up procedures to allow for heating of the refrigerant compressor crankcase. Failure to comply may result in damage and could cause premature failure of the system. This warning should be followed at initial start up and any time the power has been removed for 12 hours or longer.

Air Circulation — Leave the thermostat system switch set to “Off” and set the thermostat fan switch to “On.” The blower motor should run continuously. Check for air delivery at the register(s). Ensure that there are no obstructions at the registers or in the duct work. Set thermostat fan switch to “Auto.”

• Verify that the unit is level to allow proper condensate drainage.

Verify that there is free airfl ow to and from the outdoor coil and that all clearance requirements are met.

Verify that the duct work is sealed to prevent air leakage.

Short Cycle Protection — With the system operating in cooling mode, note the temperature setting of the thermostat and gradually raise the set-point temperature until the unit de-energizes.

Immediately lower the set point temperature of the thermostat to its original setting and verify that the indoor blower is energized. Verify that after approximately 5 minutes the compressor and fan energize and that the temperature of the discharge air is cooler than the room temperature.

• Verify that the line voltage power leads are securely connected and the unit is properly grounded.

• Verify that the low voltage wires are securely connected to the correct leads on the low voltage terminal strip.

• Verify that all exterior panels are replaced and securely fastened.

System Cooling

1. Set the thermostat system switch to “Cool” and the thermostat fan switch to “Auto”.

Gradually lower the thermostat temperature switch below room temperature and observe that the blower, compressor, and

fan energize. Check that air cooler than room temperature is being discharged at the register. Listen for any unusual noises.

2. After allowing the unit to run for several minutes, set the temperature selector above room temperature.

- The fan and compressor cycles off with the thermostat.

- The blower should also stop unless fan switch is set to “ON” position.

equipment. Some local codes require licensed installation/service personnel to service this type of equipment. Under no circumstances should the owner attempt to install and/or service this equipment. Failure to comply with this warning could result in property damage, personal injury, or death.

System Heating — If the unit has been equipped with optional electric heater kits, set the system thermostat switch to HEAT and set the thermostat fan switch to AUTO. Verify that the compressor and outdoor fan are not energized but that the blower and heaters are. Check for warm air at the supply registers.

CAUTION:

Use care when removing parts from this unit. Personal injury can result from sharp metal edges present in all equipment of sheet metal construction.

UNIT MAINTENANCE

WARNING:

To avoid risk of electrical shock, personal injury, or death, disconnect all electrical power to the unit before performing any maintenance or service. The unit may have more than one electrical supply.

Routine Maintenance — Proper maintenance is important to achieve optimum performance from the heat pump. The ability to properly perform maintenance on this equipment requires certain mechanical skills and tools. If you do not possess these skills, contact your dealer for maintenance.

Consult your local dealer about the availability of maintenance contracts. At a minimum, routine maintenance should include the following:

Refrigerant Charging — Packaged heat pumps are fully charged with R-410A refrigerant at the factory . The system refrigerant charge can be checked and adjusted through the service ports provided in the front panel. Use only gauge lines which have a “Schrader” depression device present to actuate the valve. Draw a vacuum on gauge lines to remove air before attaching them to the service ports on the unit. Refrigerant charging must be done by qualifi ed personnel familiar with safe and environmentally responsible refrigerant handling procedures.

1. Inspect and clean or replace air fi lters at the beginning of each heating and cooling season, or more frequently if required.

2. Inspect the condensate drain and outdoor coil at the beginning of each cooling season.

Remove any debris. Clean the outdoor coil and louvers as necessary using a mild detergent and water. Rinse thoroughly with water.

3. Inspect the electrical connections for tightness at the beginning of each heating and cooling season. Service as necessary.

WARNING:

These single Packaged Heat Pumps are shipped fully charged with R-410A refrigerant and ready for installation.

When a system is installed according to these instructions, no refrigerant charging is required. If repairs make it necessary for evacuation and charging, it should only be done by qualifi ed, trained personnel thoroughly familiar with this

CAUTION:

The unit should never be operated without a fi lter in the return air system.

Replace disposable fi lters with the same type and size.

4. The motors for the circulating air blower and the outdoor fan are pre-lubricated at the factory. No further oiling is required for the life of this product.

11

FROM

BLOWER

RELAY

Green

C

ECONOMIZER

PLUG

1

2

Blue

6

7

8

9

3

4

5

W2

Y2

Y1

R

G

O

E

INDOOR

THERMOSTAT

SUB-BASE

DEFROST

BOARD

3

4

1

2

5

6

7

8

9

Brown

Orange

Accessory

Heat Plug

Typical Wiring (Field Supplied) for 1-Stage Cool, 1 Stage Electric Heat

12

FROM

BLOWER

RELAY

O

Green

Optional

Outdoor

Thermostat

(Field Supplied)

ECONOMIZER

PLUG

Blue

3

4

1

2

5

6

7

8

9

C

W2

Y2

Y1

R

G

O

E

INDOOR

THERMOSTAT

SUB-BASE

DEFROST

BOARD

7

8

9

5

6

3

4

1

2

Brown

Orange

Accessory

Heat Plug

Typical Wiring (Field Supplied) for 2-Stage Cool, 2-Stage Electric Heat with an Optional Outdoor Thermostat

Figure 7. Typical Heat Pump Thermostat Connections

Model number

Q6SD

Tap

External Static Pressure Drop - inches water column

0.1

0.2

0.3

X24

* Tap T1

** Tap T2

Tap T3

Tap T4

Tap T5

** Tap T1

* Tap T2

X30 Tap T3

Tap T4

Tap T5

** Tap T1

Tap T2

X36 * Tap T3

Tap T4

Tap T5

X42

** Tap T1

Tap T2

Tap T3

* Tap T4

Tap T5

* Tap T1

** Tap T2

Tap T3 X48

Tap T4

Tap T5

Tap T1

** Tap T2

X60 * Tap T3

Tap T4

Tap T5

* Denotes factory set cooling speed

** Denotes factory set electric heating speed

NOTE: Airfl ow performance is with a dry coil

1960

2090

1515

1580

1740

1960

2090

1150

1230

1400

1524

1700

1515

1580

1740

1400

1600

1700

1150

1230

1464

1600

1700

1110

1211

1400

1600

1700

1211

1275

Table 2. Blower Curves

1910

2050

1450

1520

1690

1910

2050

1050

1190

1350

1476

1650

1450

1520

1690

1350

1500

1650

1050

1190

1394

1500

1650

869

996

1350

1500

1650

996

1077

1840

2010

1380

1460

1650

1840

2010

1000

1120

1200

1424

1600

1380

1460

1650

1200

1400

1600

1000

1120

1332

1400

1600

529

700

1200

1400

1600

700

940

0.4

0.5

0.6

1820

1975

1350

1400

1600

1820

1975

950

1080

1150

1379

1565

1350

1400

1600

1150

1300

1565

950

1080

1272

1300

1565

-

609

1150

1300

1565

609

876

1780

1940

1300

1360

1540

1780

1940

850

1000

1080

1329

1530

1300

1360

1540

1080

1200

1530

850

1000

1216

1200

1530

-

-

1080

1200

1530

-

807

1740

1900

1250

1300

1500

1740

1900

780

950

1030

1268

1480

1250

1300

1500

1030

1050

1480

780

950

1143

1050

1480

-

-

1030

1050

1480

-

732

13

Q6SD-X24 Charging Chart - Cooling

600

580

560

540

520

500

480

460

440

420

400

380

360

340

320

300

280

260

240

220

200

75

Remove refrigerant when above curve

80 85 90 95 100 105 110

Liquid Temperature (F)

Add refrigerant when below curve

115 120 125 130 135

Figure 8. Charging Chart for 2 Ton Units

14

Q6SD-X30 Charging Chart - Cooling

600

580

560

540

520

500

480

460

440

420

400

380

360

340

320

300

280

260

240

220

200

75

Remove refrigerant when above curve

80 85 90 95 100 105 110

Liquid Temperature (F)

Add refrigerant when below curve

115 120 125 130 135

Figure 9. Charging Chart for 2.5 Ton Units

Q6SD-X36 Charging Chart- Cooling

460

440

420

400

380

360

340

320

300

280

260

600

580

560

540

520

500

480

240

220

200

75

Remove refrigerant when above curve

80 85 90 95 100 105 110

Liquid Temperature (F)

Add refrigerant when below curve

115 120 125 130 135

Figure 10. Charging Chart for 3 Ton Units

Q6SD-X42 Charging Chart- Cooling

600

580

560

540

520

500

480

460

440

420

400

380

360

340

320

300

280

260

240

220

200

75

Remove refrigerant when above curve

80

Add refrigerant when below curve

85 90 95 100 105 110 115 120 125 130 135

Liquid Temperature (F)

Figure 11. Charging Chart for 3.5 Ton Units

15

Q6SD-X48 Charging Graph - Cooling

600

580

560

540

520

500

480

460

440

420

400

380

360

340

320

300

280

260

240

220

200

75

Remove refrigerant when above curve

80 85 90 95 100 105 110

Liquid Temperature (F)

Add refrigerant when below curve

115 120 125 130 135

Figure 12. Charging Chart for 4 Ton Units

16

Q6SD-X60 Charging Graph - Cooling

600

580

560

540

520

500

480

460

440

420

400

380

360

340

320

300

280

260

240

220

200

75

Remove refrigerant when above curve

80 85 90 95 100 105 110

Liquid Temperature (F)

Add refrigerant when below curve

115 120 125 130 135

Figure 13. Charging Chart for 5 Ton Units

T2

DFT

TEST

C

Y

O

W2

R

E

Low

Voltage

Terminals

W2

R

DFT

T1

T2

C

Y

O

E

DF1 DF2

Figure 10: Wiring Diagram

17

18

19

INSTALLER: PLEASE LEAVE THESE

INSTALLATION INSTRUCTIONS WITH

THE HOMEOWNER.

O’Fallon MO

¢709130q¤

7091300(Replaces 708869A)

Specifi cations and illustrations subject to change without notice or incurring obligations.

Printed in U.S.A. (10/09)

7091300