MCT82-FK Installation Manual 2020-07-24

Roger Access Control System

MCT82-FK / MCT82-FK-HR-F Installation Manual

Firmware version: 1.1.25.244 and newer

Document version: Rev. A

This document contains minimum information that is necessary for initial setup and installation of the device. The detailed description of configuration parameters and functionalities is specified in respective Operating Manual available at www.roger.pl

.

I

NTRODUCTION

Both versions of the panel with four touch function keys i.e. MCT82-FK (wall mounting) and MCT82-FK-HR-F (flush mounting) are designed to operate in

RACS 5 system as peripheral devices connected to RS485 bus of MC16 access controller. Factory new panel is configured with default settings including ID=100 address. Before connecting to controller, the device should be assigned with unoccupied address in range of 100-115. Programming of other parameters depends on the individual requirements and is not obligatory. Addressing of the panel can be done from computer by means of RogerVDM program.

Configuration of the panel with RogerVDM requires RUD-1 interface.

C

ONFIGURATION WITH

R

OGER

VDM

PROGRAM

Fig. 2 Connection of panel to RUD-1 interface for firmware update

A

PPENDIX

Fig. 1 Connection of panel to RUD-1 interface for configuration

Programming procedure:

1. Connect the device to RUD-1 interface (fig. 1) and connect the RUD-1 to computer’s USB port.

2. Restart the device (switch power supply off and on or short RST contacts for a moment)

3. Within 2-3 seconds place jumper on MEM contacts (fig. 3) and all LED indicators will pulsate quickly.

4. Start RogerVDM program, select MCT device, firmware version, RS485 communication channel and serial port with RUD-1 interface.

5. Click Connect, the program will establish connection and will automatically display Configuration tab.

6. Enter unoccupied RS485 address in range of 100-115 and other settings according to requirements of specific installation.

7. Click Send to Device to update the configuration.

8. Optionally make a backup by clicking Send to File… and saving settings to file on disk.

9. Remove jumper from MEM contacts and disconnect device from RUD-1 interface.

F

IRMWARE UPDATE

The update requires connection of device to computer with RUD-1 interface

(fig. 2) and starting RogerVDM software. The latest firmware file is available at www.roger.pl

.

Firmware update procedure:

1. Connect the device to RUD-1 interface (fig. 2) and connect the RUD-1 to computer’s USB port.

2. Place jumper on FDM contacts (fig. 3).

3. Restart the device (switch power supply off and on or short RST contacts for a moment).

4. Start RogerVDM program and in the top menu select Tools and then Update firmware .

5. In the opened window select device type, serial port with RUD-1 interface and path to firmware file (*.hex).

6. Click Update to start firmware upload with progress bar in the bottom.

7. When the update is finished, remove FDM jumper and restart the device.

Fig. 3 MCT82-FK enclosure opening and location of service contacts

Fig. 4 Wall mounting for surface and flush versions

Table 1. Screw terminals

Screw terminal

12V

Description

Supply plus

GND

A

B

Ground

RS485 bus, line A

RS485 bus, line B

1/2

MCT82-FK Installation Manual 2020-07-24

Fig. 5 Connection of peripheral devices to MC16 access controller

Table 2. Specification

Supply voltage

Current

(average) consumption

Tamper protection

Distance

IP Code

Environmental

Dimensions H x W x D

Weight

Certificates class

(according to EN 50133-1)

Nominal 12VDC, min./max. range 10-15VDC

~60 mA

Enclosure opening reported to access controller

1200m maximal cable length for RS485 bus between controller and panel

IP41

Class II, indoor general conditions, temperature: -

10°C to +50°C, relative humidity: 10 to 95% (no condensation)

MCT82-FK:

MCT82-FK-HR-F:

85 x 85 x 22 mm

105 x 105 x 31 mm

~100g

CE

This symbol placed on a product or packaging indicates that the product should not be disposed of with other wastes as this may have a negative impact on the environment and health. The user is obliged to deliver equipment to the designated collection points of electric and electronic waste. For detailed information on recycling, contact your local authorities, waste disposal company or point of purchase. Separate collection and recycling of this type of waste contributes to the protection of the natural resources and is safe to health and the environment. Weight of the equipment is specified in the document.