- Home
- Domestic appliances
- Large home appliances
- Water heaters & boilers
- Dunkirk
- Q90-200 Series II
- User manual
advertisement
Q90 125-200 GAS-FIRED DIRECT VENT
CONDENSING HOT WATER BOILER
DUNKIRK BOILERS
85 Middle Rd.
Dunkirk, NY 14048
www.dunkirk.com
An ISO 9001-2000 Certified Company
P/N 240004826D, Rev. 1.3 [01/06]
Q90 125-200 CAST ALUMINUM BOILER
INSTALLATION MANUAL AND OPERATING INSTRUCTIONS
P/N# 240004826D, Rev. 1.3 [01/06] • Printed in USA • Made In USA
TABLE OF CONTENTS
forces the resulting flue gases from the boiler unit and provides a positive removal of the flue gases from the building through inexpensive and readily available PVC and CPVC vent pipes.
I. Introduction ........................................................ 2
II. Safety Symbols ................................................ 2
III. Rules For Safe Installation and Operation .........3
IV. Boiler Ratings and Capacities ......................... 4
V. Before Installing The Boiler .............................. 5
VI. Placing The Boiler ........................................... 9
VII. Near Boiler Piping .......................................... 9
VIII. Combustion Air and Vent Pipe .................... 11
IX. Gas Supply Piping ........................................ 13
X. Electrical Wiring ............................................. 15
XI. Controls and Accessories ............................. 17
XII. Startup ......................................................... 19
XIII. Checkout Procedures and Adjustments ........23
XIV. Maintenance and Cleaning ......................... 26
XV. Detailed Sequence of Operation .................. 28
XVI. Troubleshooting .......................................... 33
XVII. Installation and Checkout Certificate ......... 40
II. SAFETY SYMBOLS
The following defined symbols are used throughout this manual to notify the reader of potential hazards of varying risk levels.
!
!
DANGER
WARNING
!
Indicates an imminently hazardous situation which, if not avoided, WILL result in death or serious injury.
!
KEEP THIS MANUAL NEAR BOILER AND
RETAIN FOR FUTURE REFERENCE.
Indicates a potentially hazardous situation which, if not avoided, COULD result in death or serious injury.
!
CAUTION
!
I. INTRODUCTION
This appliance is a gas-fired direct vent cast aluminum hot water boiler. A revolutionary cast aluminum heat exchanger means better heat transfer and thermal storage than similarly sized cast iron boilers, which results in higher efficiency.
The heating system water absorbs large amounts of heat from the cast aluminum heat exchanger, cooling the flue gases and causing condensation.
Sealed combustion, premix gas burner, and low flame temperature means drastically reduced CO and NOx emissions, which contribute to a cleaner and healthier environment.
Indicates a potential hazardous situation which, if not avoided, MAY result in minor or moderate injury. It may also be used to alert against unsafe practices.
IMPORTANT:
Read the following instructions
COMPLETELY before installing!!
This appliance, unlike normal residential atmospheric and induced draft units, takes its combustion air directly from the outdoors (sealed combustion) and does not compete with building occupants for fresh air. Sealed combustion (also known as “direct vent”) is the safest and best way to obtain plenty of clean combustion air. The forced draft fan draws in the outside combustion air to mix with gas, which flows into the pre-mix burner and combusts. The fan then
2
III. RULES FOR SAFE INSTALLATION AND OPERATION
!
WARNING
!
This appliance has been equipped for residential installations. If used for commercial applications, any and all additional code requirements must be adhered to for installation. This may require additional controls, including but not limited to a manual reset low water cut off, a manual reset high temperature limit, and wiring and/or piping modifications.
The manufacturer is not responsible for any field installation changes made to a boiler installation
WHICH ARE NOT DESCRIBED OR ACKNOWLEDGED IN THIS MANUAL.
IMPORTANT:
Failure to follow these instructions could cause a malfunction of the boiler and result in death, serious bodily injury, and/or property damage.
For assistance or additional information, consult a qualified installer, service agency, or the gas supplier.
1. Check all applicable state and local building codes and utility company requirements before installation. This installation must conform with these requirements in their entirety. In the absence of these codes, use NFPA installation codes and good industry practice.
2. Before servicing the boiler, allow it to cool.
Always shut off any electricity and gas supply connected to the boiler prior to servicing.
3. Inspect gas line for leaks.
4. Be certain gas input rate is correct. Overfiring may result in early failure of the boiler components.
This may cause dangerous operation. Underfiring
3
may result in too much air for the pre-mix burner causing poor or loss of combustion.
5. Never vent the products of combustion from this boiler to an enclosed space. Always vent to the outdoors. Never vent to another room or to inside a building.
6. Be sure there is adequate outdoor air supply to boiler for complete combustion.
7. Follow a regular service and maintenance schedule for efficient and safe operation.
8. Keep boiler area clean of debris and free of combustible and flammable materials.
9. Proper through-the-wall or through-the-roof combustion venting shall be in accordance with the materials and methods described in this manual.
Installation must comply with local codes.
10. This boiler and related hot water heating systems are not do-it-yourself items. They must be installed and serviced by qualified professionals.
IV. BOILER RATINGS & CAPACITIES
Model
125
150
175
200
TABLE 1 - SEA LEVEL RATINGS (NATURAL AND PROPANE GASES)
Input
(MBH)
(1)
Heating Capacity
(MBH)
(1)(2)
Net I=B=R Rating
(MBH)
(1)
Shipping
Weight (lbs.) AFUE
(2)
Flue Diameter
125
150
175
200
112.5
135
157.5
180
(1)
1 MBH = 1,000 Btuh (British Thermal Units Per Hour)
98
117
137
157
284
284
284
284
90
90
90
90
2” CPVC & 3” PVC
2” CPVC & 3” PVC
2” CPVC & 3” PVC
2” CPVC & 3” PVC
(2)
AFUE (Annual Fuel Utilization Efficiency) and Heating Capacity is based on Department of Energy test procedure.
Ratings shown are for sea level applications. The boiler automatically derates input as altitude increases.
No alterations to boiler are required for altitudes above sea level.
Altitude
0
1,000
2,000
3,000
4,000
5,000
6,000
7,000
8,000
9,000
10,000
Nominal Input
200,000
Vent Lengths
Min Max
TABLE 2 - NATURAL GAS
175,000
Vent Lengths
Min Max
150,000
Vent Lengths
Min Max
125,000
Vent Lengths
Min Max
200,000 200,000 175,000 175,000 150,000 150,000 125,000 125,000
197,000 196,500 172,400 172,200 147,800 147,400 123,500 123,000
194,000 193,000 169,800 169,400 145,600 144,800 122,000 121,000
191,000 189,500 167,200 166,600 143,400 142,200 120,500 119,000
188,000 186,000 164,600 163,800 141,200 139,600 119,000 117,000
185,000 182,500 162,000 161,000 139,000 137,000 117,500 115,000
182,000 179,000 159,400 158,200 136,800 134,400 116,000 113,000
179,000 175,500 156,800 155,400 134,600 131,800 114,500 111,000
176,000 172,000 154,200 152,600 132,400 129,200 113,000 109,000
173,000 168,500 151,600 149,800 130,200 126,600 111,500 107,000
170,000 165,000 149,000 147,000 128,000 124,000 110,000 105,000
Altitude
0
1,000
2,000
3,000
4,000
5,000
6,000
7,000
8,000
9,000
10,000
Nominal Input
200,000
Vent Lengths
TABLE 3 - LP GAS
175,000
Vent Lengths
150,000
Vent Lengths
125,000
Vent Lengths
Min Max Min Max Min Max Min Max
200,000 200,000 175,000 175,000 150,000 150,000 125,000 125,000
195,900 195,750 171,900 171,200 146,900 146,700 123,050 122,250
191,800 191,500 168,800 167,400 143,800 143,400 121,100 119,500
187,700 187,250 165,700 163,600 140,700 140,100 119,150 116,750
183,600 183,000 162,600 159,800 137,600 136,800 117,200 114,000
179,500 178,750 159,500 156,000 134,500 133,500 115,250 111,250
175,400 174,500 156,400 152,200 131,400 130,200 113,300 108,500
171,300 170,250 153,300 148,400 128,300 126,900 111,350 105,750
167,200 166,000 150,200 144,600 125,200 123,600 109,400 103,000
163,100 161,750 147,100 140,800 122,100 120,300 107,450 100,250
159,000 157,500 144,000 137,000 119,000 117,000 105,500 97,500
4
These low pressure gas-fired hot water boilers are design certified by CSA International, for use with natural and propane gases. The boilers are constructed and hydrostatically tested for a maximum working pressure of 50 psig (pounds per square inch gauge) in accordance with A.S.M.E. (American Society of Mechanical Engineers) Boiler and Pressure Vessel Code, Section IV Standards for heating boilers.
The Boilers are certified in accordance with ANSI (American National Standards Institute) Z21.13 standards as gas-fired, direct vent, condensing, hot water boilers.
The
Heating Capacity
indicates the amount of heat available after subtracting the losses up the stack.
Most of this heat is available to heat water. A small portion is heat loss from the jacket and surfaces of the boiler, and it is assumed that this heat stays in the structure. The
Net I=B=R Rating
represents the portion of the remaining heat that can be applied to heat the radiation or terminal units (i.e. finned tube baseboard, cast iron radiators, radiant floor, etc.). The difference between the Heating Capacity and the
Net I=B=R Rating, called the piping and pickup allowance, establishes a reserve for heating the volume of water in the system and offsetting heat losses from the piping. The Net I=B=R Ratings shown are based on a piping and pickup factor of 1.15 in accordance with the I=B=R Standard as published by the
Hydronics Institute. The Net I=B=R Rating of the boiler selected should be greater than or equal to the calculated peak heating load (heat loss) for the building or area(s) served by the boiler and associated hot water heating systems. The manufacturer should be consulted before selecting a boiler for installations having unusual piping and pickup requirements.
V. BEFORE INSTALLING THE BOILER
Complete all of the following prior to installing the boiler.
BOILER SIZING
CODES
This boiler product is a gas-fired, direct vent, condensing boiler and must be installed in accordance with all applicable federal, state and local building codes including, but not limited to the following:
United States -
Installation shall conform with National Fuel Gas Code (NFPA-54/ANSI
Z223.1 - latest revision)
• Check to be sure you have selected the boiler with the proper capacity before continuing the installation. The I=B=R Rating of the boiler selected should be greater than or equal to the calculated peak heating load (heat loss) for the building or area(s) served by the boiler and associated hot water heating systems. See Section IV,
“Boiler
Ratings and Capacities,”
for more information.
• Heat loss calculations should be based on approved industry methods.
CONSIDERATIONS FOR BOILER LOCATION
Canada -
Installation shall be in accordance with CSA-B149.1 and .2 installation codes.
Where required by the authority having jurisdiction, the installation must conform to the American Society of Mechanical Engineers Safety Code for Controls and Safety Devices for Automatically Fired
Boilers, No.CSD-1.
Before selecting a location for the boiler, the following should be considered. Each boiler considered for installation must be:
• Supplied with the correct type of gas (natural gas or propane).
The installation must conform to the requirements of the authority having jurisdiction or, in the absence of such requirements, to the National Fuel
Gas Code, ANSI Z223.1 - latest revision.
• Connected to a suitable combustion air intake piping system to supply the correct amounts of fresh
(outdoor) air for combustion (max. length 60’).
Installers -
Follow local regulations with respect to installation of CO (Carbon Monoxide) Detectors. Follow maintenance recommendations in this manual.
• Connected to a suitable venting system to remove the hazardous products of gas combustion (max. length 60’).
5
• Connected to a suitable hot water heating system.
• Supplied with a suitable electrical supply for all boiler motors and controls.
• Connected to a properly located thermostat or operating control. (not included with boiler)
• Placed on level surface (must
NOT
be installed on carpeting)
• Condensate drain line must be pitched down to floor drain or external condensate pump with reservoir at ¼”per foot (wood frame or blocks may be used to raise boiler).
LOCATING THE BOILER
1. Select a location which is level, central to the piping systems served and as close to the vent and air intake terminals as possible.
2. Accessibility clearances, if more stringent (i.e. larger clearances) than required fire protection clearances, must be used for the boiler installation. Accessibility clearances may be achieved with the use of removable walls or partitions.
3. The boiler is approved for installation in closets and on combustible floors. This boiler shall
NOT
be installed on carpeting.
TABLE 4 - BOILER CLEARANCES
Unit
Top
Left Side
Right Side
Base
Front
Back
Combustible
Clearance
1”
8”
1”
1”
0”
1”
Accessibility, Cleaning, and Servicing
8”
24”
-
-
24”
-
Intake/Vent
Piping
0” -
Near Boiler Hot
Water Piping
1” -
All distances measured from the cabinet of the boiler.
4. The clearances shown in Table 4 indicate required clearances per CSA listing. A min. 1” clearance must be maintained between combustible construction and each of the right, top and back surfaces of the boiler. A min. 8” clearance is required on the left side, to allow room for the inlet air pipe. An 18” clearance must be maintained at the front where passage is required for cleaning or servicing, inspection or replacement of any parts that normally may require such attention. Allow at least 24” at the front and left side and 8” at the top for servicing. No combustible clearances are required to venting or combustion air intake piping.
5. Equipment shall be installed in a location which facilitates the operation of venting and combustion air intake piping systems as described in this manual.
6. Advise owner of boiler to keep venting and combustion air intake passages free of obstructions. Both the venting and combustion air intake piping systems connected to the outdoors must permit flow through the piping systems without restrictions for the boiler to operate.
7. The boiler shall be installed such that the automatic gas ignition system components are protected from water (dripping, spraying, rain, etc.) during operation and service (circulator replacement, control replacement, etc.).
8. The boiler must be located where ambient temperatures (minimum possible room temperatures where boiler is installed assuming boiler is not in operation and therefore contributes no heat to the space) are always at or above 32°F to prevent freezing of liquid condensate.
COMBUSTION AIR/VENT PIPE REQUIREMENTS
This boiler requires a dedicated direct vent system.
In a direct vent system, all air for combustion is taken directly from outside atmosphere, and all flue products are discharged to outside atmosphere.
ROOF VENT/INTAKE TERMINATIONS
8" MINIMUM
VERTICAL SEPARATION
BETWEEN COMBUSTION
AIR INTAKE AND VENT
3'' MAXIMUM
SEPARATION
15'' MAXIMUM
12''
MIMIMUM
6
MAINTAIN 12" MINIMUM
CLEARANCE ABOVE HIGHEST
ANTICIPATED SNOW LEVEL
COMBUSTION
AIR
Figure 1
Combustion air and vent pipe connections must terminate together in the same atmospheric pressure zone, either through the roof or sidewall (roof termination preferred). See Figures 1 and 2 for required clearances.
SIDEWALL VENT/INTAKE TERMINATIONS
OVERHANG
12" MINIMUM
12"
MINIMUM
12"
MINIMUM
VENT
90°
3"
MAXIMUM
SEPARATION
15"
MAXIMUM
18"
MAXIMUM
LESS THAN 12" CLEARANCE
12" SEPARATION
BETWEEN BOTTOM OF
COMBUSTION AIR INTAKE
AND BOTTOM OF VENT
MAINTAIN 12" MINIMUM
CLEARANCE ABOVE HIGHEST
ANTICIPATED SNOW LEVEL OR
GRADE
OVERHANG
12"
MINIMUM
12"
MINIMUM
VENT
BRACKET
90°
12" MINIMUM
12" SEPARATION
BETWEEN BOTTOM OF
COMBUSTION AIR INTAKE
AND BOTTOM OF VENT
1" MAXIMUM
3"
MAXIMUM
SEPARATION
18"
MAXIMUM
12" OR MORE CLEARANCE
Figure 2
If the concentric vent termination is being used, refer to Figure 3 for proper setup.
CONCENTRIC VENT TERMINATIONS
ROOF
OVERHANG
MAINTAIN 12" MINIMUM
CLEARANCE ABOVE HIGHEST
ANTICIPATED SNOW LEVEL OR
GRADE
12" MINIMUM
12" MINIMUM
!
WARNING
!
FAILURE TO FOLLOW THESE WARNINGS
COULD RESULT IN FIRE, PROPERTY
DAMAGE, PERSONAL INJURY, OR DEATH.
When vent pipe is exposed to temperatures below freezing, such as when it passes through an unheated space or when a chimney is used as a chaseway, vent pipe must be insulated with 1/2”Armaflex or equivalent. In extremely cold climate areas, use 3/4”Armaflex or equivalent.
Combustion air must be clean outdoor air.
Combustion air must not be taken from inside the structure because that air is frequently contaminated by halogens, which include fluorides, chlorides, phosphates, bromides and iodides. These elements are found in aerosols, detergents, bleaches, cleaning solvents, salts, air fresheners, paints, adhesives, and other household products.
Locate combustion air inlet as far away as possible from swimming pool and swimming pool pump house. All combustion air and vent pipes must be airtight and watertight.
Combustion air and vent piping must also terminate exactly as shown in Figures 1-2. If a concentric vent termination is being used, refer to Figures 3-5 for proper setup.
Vent connections serving appliances vented by natural draft shall not be connected into any portion of mechanical draft systems operating under positive pressure.
Solvent cements are combustible. Keep away from heat, sparks, or open flame. Use only in well ventilated areas. Avoid breathing in vapor or allowing contact with skin or eyes.
CONCENTRIC VENT
VENT
COMBUSTION AIR
MAINTAIN 12" IN. CLEARANCE
ABOVE HIGHEST ANTICIPATED
SNOW LEVEL OR GRADE
Figure 3
!
CAUTION
!
Keep boiler area clean of debris and free of flammable and combustible materials, vapors, and liquids.
7
Figure 4
CONCENTRIC VENT ROOF INSTALLATION
Figure 5
FOUNDATION REQUIREMENTS
Boiler must be placed on level surface. Boiler is
NOT to be installed on carpeting.
NOTES
1. If boiler is not level condensate drain lines will not function properly. Adjustable feet are located on the boiler to make up for minor surface irregularities or tilt.
2. Wood frame or blocks may be used to raise boiler to maintain drain pitch or to be above external condensate pump reservoir.
REMOVAL OF EXISTING BOILER
FROM COMMON VENT SYSTEM
When an existing boiler is removed from a common venting system, the common venting system is likely to be too large for proper venting of the appliances remaining connected to it. At the time of removal of an existing boiler, the following steps shall be followed with each appliance remaining connected to the common venting system placed in operation, while the other appliances remaining connected to the common venting system are not in operation.
1. Seal any unused openings in the common venting system.
2. Visually inspect the venting system for proper size and horizontal pitch and determine there is no blockage or restriction, leakage, corrosion or other deficiencies which could cause an unsafe condition.
3. When it is practical, close all building doors and windows and all doors between the space in which the appliances remaining connected to the common venting system are located and other spaces of the building. Turn on clothes dryer and any appliance not connected to the common venting system. Turn on any exhaust fans, such as range hoods and bathroom exhaust, so they will operate at maximum speed. Do not operate a summer exhaust fan. Close fire dampers.
4. Place in operation the appliance being inspected. Follow the lighting instructions. Adjust thermostat so appliances will operate continuously.
5. Test for spillage at the draft hood relief opening after 5 minutes of main burner operation. Use the flame of a match or candle, or the smoke from a cigarette, cigar or pipe.
6. After it has been determined that each appliance remaining connected to the common venting system properly vents when tested as outlined above, return doors, windows, exhaust fans and any other gas-burning appliance to their previous condition of use.
7. Any improper operation of the common venting system should be corrected so the installation conforms with the National Fuel Code, NFPA-
54/ANSI -Z223.1-latest revision, or section 5 of
CSA-B149 for Canadian standards. When resizing any portion of the common venting system, the common venting system should be resized to approach the minimum size as determined using the appropriate tables in part 11 in the National
Fuel Gas Code, NFPA-54/ANSI- Z223.1-latest revision, or section 5 of CSA-B149 for Canadian standards.
8
VI. PLACING THE BOILER
The boiler should be placed to provide the most direct connections to the combustion air, vent and system piping as possible.
Place crated boiler as close to selected location as possible and uncrate boiler. The uncrated boiler may be moved into position with an appliance dolly or 2-wheel hand truck. The dolly or hand truck should be inserted under the
right hand side
of the boiler. It is possible to slide the boiler for a short distance on a smooth floor or surface.
NOTE:
Refer to
“Locating The Boiler”
in Section V for required clearances for servicing and maintenance.
VII. NEAR BOILER PIPING
!
CAUTION
!
Copper supply and return piping must NOT be installed directly into aluminum boiler section castings due to galvanic corrosion between dissimilar metals. Iron or steel bushings or pipe nipples should be used between copper system piping and boiler to make final connection to boiler. Also, the use of dielectric unions is acceptable. The packaged boiler is furnished with iron piping in the front boiler section for the supply and return connections.
When the installation of the boiler is for a new heating system, first install all of the radiation units (panels, radiators, baseboard, or tubing) and the supply and return mains. After all heating system piping and components have been installed, make final connection of the system piping to the boiler.
Determine required system fill pressure, system design temperature, and system water content. Boiler contains 2.6 gallons (U.S.). Size expansion tank accordingly. Consult expansion tank manufacturer for proper sizing information. Connect properly sized expansion tank (not furnished) as shown in Figure 6 for diaphragm type expansion tank. For diaphragm type expansion tanks, adjust the tank air pressure to match the system fill pressure. Install air vent
(furnished) as shown for diaphragm type expansion tank system only. Install make-up water connections as shown and per local codes. If a pressure reducing valve is used, adjust to match the system fill pressure. In connecting the cold make-up water supply to the boiler, make sure that clean water supply is available. When the water supply is from a well or pump, a sand strainer should be installed at the pump.
A hot water boiler installed above radiation level must be equipped with a low water cut off device (included with boiler). A periodic inspection is necessary, as is flushing of float type devices, per low water cut off manufacturers specific instructions.
EXPANSION TANK AND MAKE-UP WATER
PRESSURE RELIEF VALVE /
TEMPERATURE PRESSURE GAUGE
RELIEF VALVE DISCHARGE PIPING
DIAPHRAGM TYPE EXPANSION TANK PIPING
Figure 6
Figure 7
9
The boiler is furnished with a relief valve and temperature pressure gauge in the boiler parts bag. Install vent relief valve as shown in Figure 7. Provide
¾” piping from the relief valve to a local floor drain,
but leave an air gap between piping and drain.
No shutoff of any description shall be placed between safety relief valve and the boiler, or on the discharge pipes between such safety valve and the atmosphere. Installation of the safety relief valve shall conform to ANSI/ASME Boiler and Pressure
Vessel Code, Section IV. The manufacturer is not responsible for any water damage.
SINGLE ZONE BOILER PIPING
MULTIZONE BOILER PIPING
WITH ZONE VALVES
Figure 8
MULTIZONE BOILER PIPING
WITH CIRCULATORS
Figure 9b
SUPPLY AND RETURN LINES
The packaged boiler unit is set up to receive 1¼”
NPT supply and return piping from top access.
NOTE:
The circulator pump and isolation valves are furnished within a carton inside the boiler cabinet and can be installed at the installer preferred location.
CONDENSATE DRAIN REQUIREMENTS
CONDENSATE DRAIN PIPING
TO EXHAUST VENT
(2" CPVC)
1/2" ADAPTER
MALE NPT x SOCKET WELD
PVC PIPING
1 3/8" LONG
1/2" UNTHREADED
PVC PIPING
1 3/8" LONG
TO CONDENSATE DRAIN
(FIELD SUPPLIED)
1/2" UNTREADED
PVC TEE
TO BOILER FLUE OUTLET
(2" CPVC)
1/2" UNTHREADED
PVC PIPING
3 3/4" LONG
2" UNTHREADED MALE x 2" NPT MALE
PVC BUSHING
2" NPT MALE PVC BUSHING
1/2" UNTHREADED
PVC ELBOW
1/2" UNTHREADED
PVC PIPING
3 3/4" LONG
1/2" UNTHREADED
PVC ELBOW
1/2" UNTHREADED
PVC PIPING
2" LONG
Figure 10
NOTE:
When zoning with circulators, the furnished circulator pump should be used as one of the zone pumps. Each stripped end of the electrical wires for the circulator pump inside the junction box should be taped or wire nutted to prevent short circuits. Unplug the circulator pump wiring at the integrated boiler control.
Figure 9a
10
Condensate drain line to be pitched down to floor drain at a minimum of ¼” per foot. An external condensate pump (not furnished) may be used if floor drain is not available. The condensate pump must be designed for flue gas condensate application.
NOTES
1. Condensate trap is to be built in the field per Figure 10
FILLING CONDENSATE TRAP WITH WATER
ON INITIAL START UP THE CONDENSATE TRAP
MUST BE MANUALLY FILLED WITH WATER.
2. Wood frame or blocks may be used to raise the boiler to maintain drain pitch or to be above external condensate pump reservoir.
3. There is a 115 volt AC receptacle provided on the service switch junction box which is located at the boiler right side, to provide power for an external condensate pump (if needed).
The following are the steps required to initially fill the condensate trap for start up, these steps are only required at the initial start up or if maintenance requires draining of the condensate trap:
1. Pour about 1 cup of cold tap water into the condensate trap vent.
CONDENSATE DRAIN PIPING
The condensate trap is to be field installed as previously shown in Figure 10. Provided are ½” PVC fittings for the condensate drain trap (assembled in the field). The condensate drain is to be pitched down to the floor drain at a minimum of ¼” per foot.
2. Excess water should go through the condensate drain line. Verify proper operation of the drain line (and external condensate pump if used).
CHILLED WATER PIPING
The ½” diameter schedule 40 PVC condensate drain piping and pipe fittings must conform to ANSI standards and ASTM D1785 or D2846. Schedule
40 PVC cement and primer must conform to ASTM
D2564 or F493. In Canada, use CSA or ULC certified schedule 40 PVC drain pipe and cement.
The boiler, when used in connection with a refrigeration system, must be installed so the chiller medium is piped in parallel with the boiler with appropriate valves to prevent the chilled medium from entering the boiler.
A condensate pump with a reservoir (not furnished) may be used to remove condensate to a drain line
(sanitary line) above boiler if a floor drain is not available or is inaccessible.
The boiler piping system of a hot water boiler connected to heating coils located in air handling units where they may be exposed to refrigerated air circulation must be equipped with flow control valves or other automatic means to prevent gravity circulation of the boiler water during the cooling cycle.
VIII. COMBUSTION AIR AND VENT PIPE
CONNECTIONS AND TERMINATION outdoors through the combustion air intake pipe.
All flue products are discharged to the outdoors through the vent pipe.
IMPORTANT:
To prevent damage to the gas burner and ensure proper operation of the unit, installer must clean and remove all shavings from the interior of all PVC pipe used on the air intake.
For boilers connected to gas vents or chimneys, vent installations shall be in accordance with part 7, Venting of Equipment, of the National Fuel Gas Code, ANSI
Z223.1-latest revision, CSA-B149.1 and B149.2, and applicable provisions of the local building codes.
1. See Figures 1-2 in Section V,
“Combustion Air and Vent Pipe Requirements,”
for standard twopipe roof and sidewall terminations and Figures
3-5 (same section) for concentric vent terminations (roof termination is preferred). Combustion air and vent pipes must terminate together in same atmospheric pressure zone as shown.
Construction through which vent and air intake pipes may be installed is a minimum ¼” and maximum 24” thickness.
Provisions for combustion and ventilation air must be in accordance with section 5.3, Air For Combustion and Ventilation, of the National Fuel Gas
Code, ANSI Z223.1-latest revision, CSA-B149.1 and B149.2, or applicable provisions of the local building code.
2. Combustion air and vent pipe fittings must conform to one of the following American National
Standards Institute (ANSI) and American Society for Testing and Materials (ASTM) standards:
These boilers require a dedicated direct vent system. All air for combustion is taken directly from
• D1784 (schedule-40 CPVC)
• D1785 (schedule-40 PVC)
11
• D2665 (PVC-DWV)
• D2241 (SDR-21 and SDR-26 PVC)
• D2661 (ABS-DWV)
• F628 (schedule-40 ABS).
Pipe cement and primer must conform to ASTM standards D2564 (PVC) or D2235 (ABS).
In Canada construct all combustion air and vent pipes for this unit of CSA or ULC certified schedule-40 CPVC, schedule-40 PVC, PVC-DWV or
ABS-DWV pipe and pipe cement. SDR pipe is
NOT approved in Canada.
3. Combustion air and vent piping connections on boiler are 2”, but must increase to 3”. Due to potential for flue gas temperatures over 155°F, the first 5 feet of vent pipe must be CPVC (furnished), the remaining vent pipe can be PVC.
If any elbows are employed within the first 2 ½’ feet of vent, they must be CPVC. Two 30” pieces of 2” CPVC pipe and one 2” CPVC coupling are furnished with the boiler.
(Figure 11)
COMBUSTION AIR AND VENT PIPING
3 INC H INT AK E AND
E XHAUS T T E R MINAT IONS
INS T ALL F IE LD S UP P LIE D
2˝ B Y 3˝ T R ANS IT ION IN
T HE V E R T IC AL P OS IT ION ONLY
E XHAUS T T E E
(F UR NIS HE D)
5'
Figure 11
2˝ (50.8MM) C P V C C OUP LING
(F UR NIS HE D)
2˝ (50.8MM) C P V C V E NT P IP ING
(F UR NIS HE D & R E QUIR E D)
2˝ (50.8MM) C OMB US T ION AIR
INT AK E P IP ING
A04177
NOT IN
HOR IZONAL
S E C T ION
NOTE:
The exhaust transition from 2” pipe to 3” pipe must be made in a vertical run. (Transition pieces not included.)
3 in. Pipe
Minimum Venting
6 ft. in length plus four (4) 90° elbows
3 in. Pipe
Maximum Venting
60 ft. in length and up to four (4) 90° elbows
The length of pipe is counted from the boiler jacket (air intake pipe) or from vent tee (vent pipe).
The first five feet of “Total Equivalent Length” of vent pipe must be CPVC.
12
Reduce the maximum vent length 5 feet per each additional elbow.
4. Combustion air and vent piping to be pitched back to boiler at minimum ¼” per foot from intake and vent terminals so that all moisture in combustion air and vent piping drains to boiler. Pipes must be pitched continuously with no sags or low spots where moisture can accumulate and block the flow of air or flue gas. Combustion air and vent pipes must be airtight and watertight.
5. Consideration for the following should be used when determining an appropriate location for termination of combustion air and vent piping:
• Comply with all clearances required as stated in paragraph 6 (below)
• Termination should be positioned where vent vapors will not damage plants/shrubs, air conditioning equipment, or siding on the house.
• Termination should be positioned so that it will not be effected by wind eddy, air born leaves, snow, or recirculated flue gases.
• Termination should be positioned where it will not be subjected to potential damage by foreign objects, such as stones, balls, etc.
• Termination should be positioned where vent vapors are not objectionable.
• Put vent on a wall away from the prevailing winter wind. Locate or guard the vent to prevent accidental contact with people or pets.
• Terminate the vent above normal snowline. Avoid locations where snow may drift and block the vent. Ice or snow may cause the boiler to shut down if the vent becomes obstructed.
• Under certain conditions, flue gas will condense, forming moisture, and may be corrosive. In such cases, steps should be taken to prevent building materials at the vent from being damaged by exhaust of flue gas.
6. The venting system shall terminate at least 3 feet above any forced air inlet (except the boiler’s combustion air inlet) within 10 feet. The venting system shall terminate at least 12 inches from any air opening into any building. The bottom of the vent shall be located at least 12 inches
above grade. Termination of the vent shall be not less than 7 feet above an adjacent public walkway. The vent terminal shall not be installed closer than 3 feet from the inside corner of an L shaped structure. Termination of the vent should be kept at least 3 feet away from vegetation.
The venting system shall terminate at least 4 feet horizontally from, and in no case above or below electric meters, gas meters, regulators, and relief equipment.
If multiple terminations are used, there must be a minimum of 12 inches between the exhaust of one termination and the air intake of the next termination. See Figures 1-3 in Section E5 for illustrations.
6. Check dry fit of pipe and mark insertion depth on pipe.
NOTE:
It is recommended that all pipes be cut, prepared, and pre-assembled before permanently cementing any joint.
7. After pipes have been cut and pre-assembled, apply cement primer to pipe fitting socket and end of pipe to insertion mark. Quickly apply approved cement to end of pipe and fitting socket (over primer). Apply cement in light, uniform coat on the inside of socket to prevent buildup of excess cement. Apply second coat.
8. While cement is still wet, insert pipe into socket with a ¼ turn twist. Be sure pipe is fully inserted into fitting socket.
NOTE:
All field installed vent pipe must be 3”.
INSTALLATION
1. Attach combustion air intake piping to supplied Fernco 2” coupling on CVI gas valve. Attach vent piping to furnished 2” CPVC vent tee on draft inducer outlet.
9. Wipe excess cement from joint. A continuous bead of cement will be visible around perimeter of a properly made joint.
10. Handle pipe joint carefully until cement sets.
NOTE:
All pipe joints are to be water tight.
11. Support combustion air and vent piping a minimum of every 5 feet using pre-formed metal hanging straps. Do not rigidly support pipes. Allow for movement due to expansion and contraction.
2. Working from the boiler to the outside, cut pipe to required length(s).
NOTE:
Rigid supports will cause excess noise in vent piping.
3. Deburr inside and outside of pipe. Remove all chips and shavings.
12. Slope combustion air and vent pipes toward boiler a minimum of ¼” per linear foot with no sags between hangers.
4. Chamfer outside edge of pipe for better distribution of primer and cement.
5. Clean and dry all surfaces to be joined.
13. Use appropriate methods to seal openings where vent and combustion air pipes pass through roof or side wall.
IX. GAS SUPPLY PIPING
CHECK GAS SUPPLY line complies with local codes and gas company requirements.
TABLE 5 - GAS SUPPLY PRESSURE
Pressure
Minimum
Natural Gas Propane Gas
4” w.c.
10” w.c.
Maximum 10” w.c.
14” w.c.
Please check line pressure while unit is running.
The gas pipe to your boiler must be the correct size for the length of run and for the total BTU per hour input of all gas utilization equipment connected to it. See Table 6 for proper size. Be sure your gas
The boiler and its individual shutoff valve must be disconnected from the gas supply piping system during any pressure testing of that system at test pressures in excess of ½ psig (3.5kPa).
The boiler must be isolated from the gas supply piping system by closing its individual manual shutoff valve during any pressure testing of the gas supply piping system at test pressures equal to or greater than ½ psig (3.5kPa).
13
TABLE 6 - NATURAL GAS PIPING SIZES
Pipe
Length
½”
Pipe Capacity - BTU/Hr. Input
(1)
¾” 1” 1¼”
20’ 92,000 190,000 350,000 625,000
40’
60’
63,000
50,000
130,000
105,000
245,000
195,000
445,000
365,000
TABLE 6 - PROPANE GAS PIPING SIZES
Pipe Capacity - BTU/Hr. Input
(1)
Pipe
Length
Copper Tubing
(2)
Iron Pipe
⅝” ¾” ½” ¾”
20’
40’
131,000
90,000
216,000
145,000
189,000
129,000
393,000
267,000
60’ 72,000 121,000 103,000 217,000
(1)
Includes Fittings
(2)
Outside Diameter
IMPORTANT:
The length of pipe or tubing should be measured from the gas meter or propane second stage regulator.
CONNECTING THE GAS PIPING
Refer to Figure 12 for the general layout at the boiler. The gas line enters the boiler through the left side panel.
GAS PIPING
requirements, by the National Fuel Gas Code,
ANSI Z223.1- latest revision. In Canada, follow the CAN/CGA B149.1 and .2 Installation Codes for Gas Burning Appliances and Equipment.
2. Use pipe joint compound suitable for liquefied petroleum gas on male threads only.
3. Use ground joint unions.
4. Install a sediment trap upstream of gas controls.
5. Use two pipe wrenches when making the connection to the gas valve to keep it from turning.
6. Install a manual shutoff valve in the vertical pipe about 5 feet above floor outside the boiler jacket.
7. Tighten all joints securely.
8. Propane gas connections should only be made by a licensed propane installer.
9. Two stage regulation should be used by the propane installer.
10. Propane gas piping should be checked out by the propane installer.
11. It is recomended to use a ½” union suitable for natural and propane gas after the ball cock to facilitate service on the unit.
CHECKING THE GAS PIPING
Figure 12
The boiler is equipped with a ½” NPT connection on the gas valve for supply piping and ½” NPT ball cock for manual shut off. The following rules apply:
After all connection have been made, check immediately for leaks. Open the manual shutoff valve.
Test for leaks by applying soap suds (or a liquid detergent) to each joint. Bubbles forming indicate leak.
CORRECT EVEN THE SMALLEST LEAK
AT ONCE.
!
WARNING
!
Never use a match or open flame to test for leaks.
1. Use only those piping materials and joining methods listed as acceptable by the authority having jurisdiction, or in the absence of such
14
!
WARNING
!
X. ELECTRICAL WIRING
Turn off electrical power at fuse box before making any line voltage connections. Follow local electrical codes.
All electrical work must conform to local codes as well as the National Electrical Code, ANSI/NFPA-
70, latest revision. In Canada, electrical wiring shall comply with the Canadian Electrical Codes, CSA-
C22.1 and .2.
The boiler, when installed, must be electrically grounded in accordance with the requirements of the authority having jurisdiction or, in the absence of such requirements, with the National Electrical
Code, ANSI/NFPA-70, latest revision. In Canada, electrical wiring shall comply with the Canadian
Electrical Codes, CSA-C22.1 and .2.
Run a 14 gauge or heavier copper wire from the boiler to a grounded connection in the service panel or a properly driven and electrically grounded ground rod.
ELECTRIC POWER SUPPLY
INSTALLING THE THERMOSTAT
Prior to making any line voltage connections, service switch at boiler should be in the off position and the power turned off at the fuse box.
Run a 120 volt circuit from a separate over current protection device in the electrical service entrance panel.
The thermostat location has an important effect on the operation of your boiler system.
BE SURE TO
FOLLOW THE INSTRUCTIONS INCLUDED WITH
YOUR THERMOSTAT.
NOTE:
Use copper conductors only.
Locate the thermostat about five feet above the floor on an inside wall. It may be mounted directly on the wall or on a vertical mounted outlet box. It should be sensing average room temperature.
This should be a 15 ampere circuit. A service switch has been pre-wired and located on the exterior boiler jacket. See Figure 13 for diagram showing location of service switch junction box and power supply connection points. Connect black (hot) lead from the power supply to either of the unused brass screws on the service switch. Connect the white
(neutral) lead from the power supply to the white screw on the service switch. Connect the green
(ground) lead from the power supply to the ground
(green) screw on the service switch. The receptacle on the service switch is always powered regardless of whether the switch is on or off, and could be used as a power supply for an external condensate pump if one is used.
AVOID THE FOLLOWING:
•
•
• Dead Spots -
corners; alcoves; behind doors
Cold Spots -
concealed pipes or ducts; stairwells - drafts; unheated rooms on the other side of the wall
Hot Spots -
concealed pipes; fireplaces; TVs or radios; lamps; direct sunlight; kitchens
Set heat anticipator at 0.7 amps. Connect 24 volt thermostat leads to the two (2) yellow wires located in service switch junction box, located on outer jacket of boiler. See Figure 12 for service switch junction box and thermostat field wiring connections.
Figure 13
CONNECT CIRCULATOR PUMP WIRING
See Figure 14 for service switch junction box and circulator pump field wiring connections. If the two
120 volt circulator wire terminals inside the junction box are not used, please leave the two wire nuts to prevent the short circuit.
!
CAUTION
!
Label all wires prior to disconnection when servicing controls. Wiring errors can cause improper and dangerous operation.
VERIFY PROPER
OPERATION AFTER SERVICING.
15
SCHEMATIC WIRING CONNECTIONS
NOTE:
If any of the original wire as supplied with this appliance must be replaced, it must be replaced with type 150°C Thermoplastic wire or its equivalent.
LADDER WIRING DIAGRAM
Figure 14
16
XI. CONTROLS AND ACCESSORIES
This section provides a brief description of the key controls and accessories found in this boiler.
as a lack of flame signal. The IBC is manually reset from lockout by either removing and reestablishing the thermostat’s call for heat, or by turning the service switch off, then back on.
See Section XVII,
“Troubleshooting,”
in this installation manual for detailed sequences of operation and troubleshooting procedures. See the separately provided
“Repair Parts Manual”
for locations of all control components and accessories described.
INDICATOR LIGHTS
INTEGRATED BOILER CONTROL (IBC)
The Integrated Boiler Control (IBC) is a microprocessor based controller for high efficiency gas boilers that monitors all safety controls and which controls the operation of the combustion air blower, circulator pump, burner, and a combination hot surface igniter/flame sensor. This controller is not intended for use with a vent damper. This controller is mounted on the control panel inside the boiler and contains five diagnostic indicator lights.
GAS CONTROL VALVE
The electronic 24 volt gas control valve contains a
1:1 gas/air pressure regulator to control gas flow to the main burner of the appliance, is suited for both natural and LP gas, and is rated in accordance with
ANSI Z21.21 - latest revision and and CGA-6.5-M95.
GAS VALVE
Figure 16
HIGH LIMIT AQUASTAT CONTROL
The high limit aquastat control determines the maximum boiler water temperature and also provides a means for protecting the boiler and heating system from unsafe operating conditions which could damage the boiler. The aquastat is mounted in the ½” NPT control well and ¾” x ½” bushing on the top of the front boiler section at the hot water outlet. The aquastat is tied in with the IBC and is factory set at 180°F water temperature. The high limit setpoint is field adjustable and may be set anywhere between 100°F and 200°F.
The field setpoint adjustment for each installation depends on heating system requirements. The aquastat automatically resets when the boiler water temperature drops 20°F below the setpoint value. This reset value can be field adjusted within a range of 5-30°F.
Figure 15
NOTE:
The maximum setpoint of the aquastat must not exceed 200°F.
CASTING TEMPERATURE SAFETY SWITCH
HOT SURFACE IGNITER
The 120 volt hot surface igniter heats up to 1800°F to initiate combustion of the gas in the burner. The igniter is mounted next to the burner through the gas/air mixer. The igniter also serves as a means for proving the main burner flame by flame rectification. In the event of a lack of flame signal on three consecutive trials for ignition, the IBC will lock out.
The “Valve” and “Flame” diagnostic indicator lamps
(see Figure 16) will blink indicating the failure mode
17
In the event of lack of or loss of water in the boiler, the casting temperature safety switch (230°F setpoint) installed on the top of the aluminum boiler section behind the supply piping shuts off the boiler by shutting off power to the IBC and causes the power indicator light to go out. This fault requires manual reset of the casting temperature safety switch to restart the boiler. Verify that the boiler is properly filled with water before resetting this switch.
!
WARNING
!
Never run cold water into a hot, empty boiler.
DIFFERENTIAL PRESSURE SWITCHES
The diaphragm type differential pressure switches are connected by vinyl tubing to the gas valve and the air inlet connection on the negative side and the sight glass adapter on the positive side. The pressure switches monitor air flow by sensing the differential pressure measured in inches of water (” w.c.).
The factory settings on these switches are 0.5” w.c. on the normally open switch and 3.5” w.c. for the normally closed switch. See Section XVI,
“Detailed Sequence of Operation,”
for details on the operation of the differential pressure switches.
as it is heated by the burner/boiler sections. If there is no place for the water to expand its volume, (i.e., a properly sized and functioning expansion tank) pressure on the inside of the boiler and heating system will increase. The furnished relief valve will automatically open at 30 psig pressure to relieve the strain on the boiler and heating system from the increasing pressure. The pressure relief valve discharge must be piped with the same size as the valve discharge opening to an open drain, tub or sink, or other suitable drainage point not subject to freezing, in accordance with A.S.M.E. specifications. Failure to provide the pressure relief valve with piping as herein described may cause water damage and/or serious bodily injury. The boiler manufacturer is not responsible for any water damage or personal injury.
BLOCKED VENT SAFETY SHUTOFF
BLOWER
The blower provides a means for pushing combustion air into and through the mixer, the burner, the flue ways of the cast aluminum boiler section before being discharged through the vent piping to the outdoors.
CIRCULATOR PUMP
Every forced hot water system requires at least one circulating pump. The circulating pump imparts the necessary energy to move the water through the closed loop supply and return piping systems, terminal heating equipment (finned tube radiators, etc.) and back through the boiler for reheating. To provide the required hot water flow rates, the circulator pump must be properly sized to overcome frictional losses
(usually measured in feet of water, also referred to as “pump head loss”) of the supply and return piping systems and boiler. The circulator pump is furnished in a carton within the boiler cabinet. The circulator(s) should always be located on the downstream (i.e.,
“pumping away”) side of the expansion tank.
DRAIN VALVE
The boiler is equipped with a blocked vent safety shutoff which shuts off the main burner gas in the event that the airflow of combustion products through the flue-way is reduced. In the event of a blocked flue-way, enough air will not be available to support combustion and the IBC will lock out due to loss of adequate air flow. Pressure switches monitor air flow by sensing differential pressure. The contacts are normally open and close when the draft inducer is running and causing the differential pressure at the switch to exceed its setting. The closed switch proves there is adequate air flow for combustion. The pressure switch shuts off the main burner if the differential pressure is inadequate due to a blocked vent pipe, a blocked air intake, a blocked boiler section, or a blocked air inducer. After 5 minutes of inadequate differential pressure, the IBC will lock out. The “Purge” indicator lamp (see Figure 16) will blink, indicating a failure to prove adequate combustion air flow or flue gas flow. The IBC will automatically reset after
15 minutes or can be manually reset as noted in the section titled
“Hot Surface Igniter.”
If the boiler cannot be restored to normal operating condition by resetting the control, contact a qualified service agency to check the heat exchanger flue-ways for blockage.
The manual drain valve provides a means of draining the water in the heating system, including the boiler and hot water supply and return piping systems installed above the drain valve. This drain valve is installed in the ¾” tapping at the bottom of the boiler.
Any piping installed below the elevation of this drain valve will require additional drain valves to be installed at low points in the piping systems in order to drain the entire system.
LOW WATER CUT OFF
This unit is equipped with a low water cut off control that protects against dry firing. This control provides burner cut off if there is an unsafe water loss, which can result from a broken or leaking radiator, pipe, or boiler. A water/glycol mixture up to 50% concentration may be used with the low water cut off.
EXTERNAL CONDENSATE PUMP (OPTIONAL)
A.S.M.E. RATED PRESSURE RELIEF VALVE
Each boiler must have a properly sized and installed
A.S.M.E. rated pressure relief valve. Water expands
18
For installations where there is no floor drain or other appropriate drainage available to receive conden-
sate from the boiler, an external float activated condensate pump with integral sump (supplied by others) is required. The condensate pump can be piped to a remote tie in point to a sanitary sewer system.
For this application, the boiler must be installed so that proper pitch of piping to the external condensate reservoir (sump) can be accomplished. Use wood frame or blocks (not factory supplied) to raise boiler as required for proper installation.
WATER TREATMENT AND
FREEZE PROTECTION
XII. STARTUP
1. Consult local water treatment specialist for recomendations if your water pH levels are below of 7.0 or hardness is above 7 grains hardness.
a. This boiler is designed for use in a closed hydronic heating system ONLY!
different types of corrosion inhibitors. Some brands have corrosion inhibitors that break down more rapidly or become ineffective at higher temperatures when used with aluminum. This could lead to premature failure of the aluminum boiler. Consult the antifreeze manufacturer on the compatibility of their product with aluminum.
b. Excessive feeding of fresh make-up water to the boiler may lead to premature failure of the boiler sections.
2. Use clean fresh tap water for initial fill and periodic make-up of boiler.
a. A sand filter must be used if fill and makeup water from a well is to be used.
c. Follow the antifreeze manufacturer’s instructions on determining proper ratio of antifreeze to water for the expected low temperature conditions, and for maintaining the quality of the antifreeze solution from year to year. Improperly maintained antifreeze solutions will gradually lose their ability to protect the aluminum boiler from corrosion.
b. Consideration should be given to cleaning the heating system, particularly in retrofit situations where a new boiler is being installed in an older piping system.
d.
The recommended premixed antifreeze solution is INTERCOOL NFP-50.
This product is sold direct to distributors by the manufacturer. Please contact Interstate Chemical
Company at 1-800-422-2436 or your distributor for more information.
c. In older systems, obviously discolored, murky, or dirty water, or a pH reading below
7, are indications that the system should be cleaned.
d. A pH reading between 7 and 8 is preferred when antifreese is not used in the system.
3. Antifreeze, if needed, must be of a type specifically designed for use in closed hydronic heating systems and be compatible with type 356 T6 aluminum at operating temperatures between 20°F and
250°F.
a. Use of antifreeze must be in accordance with local plumbing codes.
b. Pure glycol solutions are very corrosive, therefore hydronic system antifreeze typically contains corrosion inhibitors. Different brands of hydronic system antifreeze contain
19
Use of an alternate manufacturer’s premix antifreeze is acceptable if the product specifications are comparable with those of the recommended premix antifreeze and the antifreeze is compatible with type 356 T6 aluminum. Use of incompatible antifreeze could damage the heat exchanger and will void the product warranty.
The antifreeze must be maintained per the specifications of the manufacturer. Failure to do so will result in the warranty being voided.
Follow the antifreeze manufacturer’s instructions on determining the proper ratio of antifreeze to water for the expected low temperature conditions and for maintaining the antifreeze solution from year to year.
e.
DO NOT USE AUTOMOTIVE ANTI-
FREEZE
, as the type of corrosion inhibitors used will coat the boiler’s heat transfer sur-
faces and greatly reduce capacity and efficiency. f. Use of antifreeze in any boiler will reduce heating capacity by as much as 10-20% due to differing heat transfer and pumping characteristics. This must be taken into consideration when sizing the heating system, pump(s) and expansion tank. Consult antifreeze manufacturer’s literature for specific information on reduced capacity.
g. Water content of the boiler is 2.6 gallons
(10 liters).
h. Antifreeze will raise the pH of the water in a heating system to between 8.0 and 10.0.
This is due to the corrosion inhibitors in the antifreeze.
FILLING BOILER WITH WATER AND
PURGING AIR FOR SYSTEMS WITH
DIAPHRAGM TYPE EXPANSION TANKS
Refer to the appropriate diagrams in Section VII,
“Near Boiler Piping,”
for more information.
1. Close all zone service valves on the supply and return piping. Open the feed valve and fill boiler with water. Make sure air vent is open.
Hold relief valve open until water runs air free for five seconds to rapidly bleed air from boiler, then let the relief valve snap shut.
2. Open the zone service valve on the supply pipe for the first zone. Open the purge valve on the first zone. Feed water will fill the zone, pushing air out the purge valve. Close the purge valve when the water runs air free. Close the zone service valve.
3. Repeat step 2 for all remaining zones.
4. Open all service valves. Any air remaining trapped in the return lines between the service valves and the boiler will be pushed towards the air vent when the boiler is placed in operation.
5. Inspect piping system. Repair any leaks immediately.
FILLING BOILER WITH WATER
AND PURGING AIR
FOR SYSTEMS WITH CONVENTIONAL
CLOSED TYPE EXPANSION TANKS
Refer to the appropriate diagrams in Section VII,
“Near Boiler Piping,”
for more information.
1. Close all zone service valves on the supply and return piping and close the expansion tank service valve. Drain expansion tank. Open the feed valve and fill boiler with water. Hold relief valve open until water runs air free for five seconds to rapidly bleed air from boiler, then let the relief valve snap shut.
2. Open the zone service valve on the supply pipe for the first zone. Open the purge valve on the first zone. Feed water will fill the zone, pushing air out the purge valve. Close the purge valve when the water runs air free. Close the zone service valve.
3. Repeat step 2 for all remaining zones.
4. Open the expansion tank service valve and the tank vent. Fill the tank to the proper level and close the tank vent. Remove the handle from the expansion tank service valve so the homeowner doesn’t accidentally close it.
5. Open all service valves. Any air remaining trapped in the return lines between the service valves and the boiler will be pushed towards the expansion tank when the boiler is placed in operation.
6. Inspect piping system. Repair any leaks immediately.
NOTE:
DO NOT use stop leak compounds. Leaks in threaded connections in the aluminum boiler sections must be repaired immediately. Aluminum threads will not seal themselves.
PLACING BOILER IN OPERATION
READ BEFORE OPERATING APPLIANCE
1. This appliance does not have a pilot. It is equipped with an ignition device which automatically lights the burner. Do NOT try to light this burner by hand.
20
2. Before operating smell all around the appliance area for gas. Be sure to smell next to the floor because some gas is heavier than air and will settle to the floor.
WHAT TO DO IF YOU SMELL GAS
• Do not try to light any appliance.
• Do not touch any electric switch or use any phone in the building.
• Immediately call your gas supplier from a neighbor’s phone. Follow the gas supplier’s instructions.
• If you can not contact your gas supplier, call the fire department.
3. Use only your hand to turn the gas shut off valve. Never use tools. If the valve will not turn by hand, do not try to repair it, call a qualified service technician. Force or attempted repair may cause fire or explosion.
4. Do not use this appliance if any part has been under water. Immediately call a qualified service technician to inspect the appliance and to replace any part of the control system and any gas control which has been under water.
OPERATING INSTRUCTIONS
1.
STOP!
Read the safety information above before operating this appliance.
2. Set the thermostat to the lowest setting.
3. Turn off all electrical power to the appliance.
4. This appliance does not have a pilot. It is equipped with an ignition device which automatically lights the burner. Do NOT try to light this burner by hand.
5. Remove the front jacket panel.
6. Turn off the gas shut off valve. Valve handle should be perpendicular to the gas pipe.
7. Wait five minutes for any gas to clear. Then smell for gas, including near the floor. If you smell gas,
STOP!
Follow instructions at left under
“What To Do If You Smell Gas.”
If you do not smell gas, go to the next step.
8. Turn the gas shut off valve to the “On” position. The handle on the valve should be parallel to the gas pipe.
9. Replace the front jacket panel.
10. Turn on all electrical power to the appliance.
11. Set thermostat to desired setting.
12. If the appliance will not operate, follow the instructions in
“To Turn Off Gas To Appliance”
(below) and call your service technician or gas supplier.
TO TURN OFF GAS TO APPLIANCE
1. Set the thermostat to the lowest setting.
2. Turn off all electric power to the appliance if service is to be performed.
3. Remove the front jacket panel.
4. Turn gas shut off valve off. Handle should be perpendicular to the gas pipe.
5. Replace the front jacket panel.
Safe lighting and other performance criteria were met with the gas manifold and control assembly provided on the boiler when the boiler underwent tests specified in ANSI Z21.13-latest revision.
21
IF BURNER APPEARS TO PULSATE DURING
IGNITION:
1. Turn off boiler power and shut off gas supply to the boiler.
2. Take the burner assembly apart by removing the combustion air blower and gas valve/venturi assembly from the boiler and visually inspect the inside of the burner. Look for any debris (PVC shavings, etc.) and, if anything is present, remove it.
3. Reassemble burner assembly, turn gas supply and boiler power back on, and relight boiler.
IF BURNER STILL PULSATES OR FAILS TO
LIGHT:
1. Check for proper vent and intake pipe sizing and for proper vent lengths and vent configuration by referring to Section V,
“Before Installing The Boiler,”
and Section VIII,
“Combustion
Air and Vent Pipe,”
in this manual.
2. Check for proper gas supply pressure and proper gas line sizing to the boiler by referring to section IX,
“Gas Supply
Piping,”
in this manual.
3. Check for orifice in negative pressure hose at gas valve and 2” air intake pipe upstream of gas valve.
4. Relight boiler.
5. If boiler still does not light, the air inlet pipe may need to be disconnected to allow the boiler to start in order to verify the boiler firing rate and combustion properties. The inlet air pipe can be disconnected by removing the PVC inlet air piping from the Fernco fitting located on the air inlet of the gas valve/venturu assembly. Relight boiler.
6. When the boiler lights, the firing rate and combustion should be checked per the
“Adjustments and Checkout”
procedure in Section XIII of this manual. If the air inlet piping was disconnected in step 4 (above), leave it disconnected and make first adjustment. Then reconnect air inlet piping, recheck combustion CO
2
, and adjust again if necessary.
7. If burner pulsation continues or boiler fails to light after performing the above procedures, please contact Technical
Service at 1-800-325-5479 for further assistance.
22
XIII. CHECKOUT PROCEDURE & ADJUSTMENTS
VERIFY PROPER SEQUENCE OF OPERATION
The sequence can be followed via the diagnostic indicator lamps on the Integrated Boiler Control in
Figure 16 (Section XI). This is the normal sequence of operation. A more detailed sequence of operation containing potential faults can be found in the service hints section.
SEQUENCE OF OPERATION
(1) Lamp A is illuminated, indicating that the integrated control is receiving
24 volts and is in standby waiting for the thermostat to call for heat.
(2) Thermostat calls for heat, energizing the system circulator.
(3) Integrated boiler control performs self check of internal circuitry, lasting approximately two seconds, and energizes the draft inducer.
(4) The draft inducer comes up to speed and establishes combustion airflow, causing the normally open differential pressure air proving switch contacts to close. When combustion airflow is proved, Lamp
B is illuminated indicating that the 15 second pre-purge cycle has begun.
(5) After the pre-purge has completed, Lamp B is extinguished and
Lamp C is illuminated, indicating power is being delivered to the hot surface igniter for the 20 second igniter warm-up period. The bright yellow-orange glow of the hot surface igniter can be observed through the observation port on the boiler.
(6) After the igniter warm-up period the integrated boiler control energizes the gas valve, initiating a 6 second trial for ignition mode which is indicated by the illumination of Lamp D. Two seconds later,
Lamp C will extinguish when the integrated boiler control stops sending power to the hot surface igniter.
(7) A low level illumination of Lamp E indicates the initiation of flame proving. During the last 2 seconds of the trial for ignition mode, main burner flame is proven by flame rectification through the hot surface igniter, providing a flame signal that is relayed to the integrated boiler control, fully illuminating Lamp E.
(8) The thermostat ends its call for heat, causing the integrated boiler control to de-energize the gas valve and system circulator. Lamp
D is extinguished while the unit enters the 30 second post purge mode, indicated by the illumination of Lamp B. Lamp E will remain illuminated as the remainder of the gas in the blower is burned off
(approximately 2 seconds). During post purge the blower remains powered and clears out any residual products of combustion.
(9) After the post purge mode the draft inducer is de-energized and the unit goes into standby mode until the next call for heat from the thermostat.
DIAGNOSTIC
INDICATOR LAMPS
A.
B.
C.
D.
D.
E.
A.
B.
A.
B.
C.
C.
D.
E.
A.
B.
C.
D.
E.
C.
D.
E.
A.
E.
A.
B.
E.
A.
B.
C.
D.
E.
B.
C.
D.
NOTE:
The first one or two cold starts may be rough due to the gas line not being completely purged of air, causing low firing rate and high excess air levels.
23
INSPECT VENTING & AIR INTAKE SYSTEM
Operate the boiler and verify that all vent/air intake connections are gastight and watertight. Repair any leaks immediately.
test for operation as outlined by the control manufacturer. Burner should be operating and should go off when controls are tested. When safety controls are restored, burner should reignite.
INSPECT CONDENSATE DRAIN
SET THERMOSTAT HEAT ANTICIPATOR
(IF USED)
AND VERIFY THERMOSTAT OPERATION
Verify that all connections are watertight, and that condensate flows freely. Repair any leaks immediately.
INSPECT SYSTEM PIPING
Verify that all connections are watertight. Repair any leaks immediately.
TEST IGNITION SYSTEM SAFETY SHUTOFF
1. Turn off manual gas shut off valve.
For a single thermostat connected to the yellow thermostat lead wires in the furnished field wiring junction box, the heat anticipator should be set at
0.7 amps. For other wiring configurations, refer to the instructions provided by the thermostat manufacturer regarding adjustment of heat anticipator.
Cycle boiler with thermostat. Raise the thermostat to the highest setting and verify boiler goes through normal start up cycle. Lower thermostat to lowest setting and verify boiler goes off.
2. Set thermostat to call for heat.
MEASURE NATURAL GAS INPUT RATE
3. Boiler begins normal sequence of operation.
4. After approximately 30 seconds (pre purge and igniter warm-up period), lamp D illuminates, indicating gas valve is powered.
Correct input rate is essential for proper and efficient operation of the burner and boiler.
1. Determine the elevation at the installation site.
5. After 4 seconds, gas valve closes, lamp D goes out as integrated boiler control senses that flame is not present.
2. See Table 2 in Section IV of this manual to determine the correct approximate input rate for the local elevation.
6. To restart system, follow operating instructions in Section XII,
“Start Up.”
3. Obtain the yearly average heating value of the local gas utility. At sea level elevation, it should be approximately 1000 BTU per standard cubic foot.
TEST AND ADJUST HIGH LIMIT CONTROL
Set high limit differential to minimum setting. While burner is operating, adjust setting on high limit control below actual boiler water temperature. Burner should go off while circulator continues to operate.
Raise limit setting above boiler water temperature and burner should reignite after pre purge and igniter warm-up period. Set the high limit control to the design temperature requirements of the system. Maximum high limit setting is 200°F. Minimum high limit setting is 100°F. Return high limit differential to original setting (20°F)
4. Operate boiler for 5 minutes.
5. Turn off all other gas appliances, extinguishing standing pilots where applicable.
6. At the gas meter, measure the time in seconds required to use one cubic foot of gas.
7. Calculate the “input rate” according to the following formula:
Btuh input rate = 3600 x heating value from step 3
Time in seconds from step 6
TEST OTHER SAFETY CONTROLS
If the boiler is equipped with a low water cut off, a manual reset high limit, or additional safety controls,
24
8. The measured input rate should be within +0/-
2% of the input rating found in step 2. If not, see
“Adjustments and Checkout”
on next page.
ADJUSTMENTS AND CHECKOUT
It is important that this appliance operate between 8.5 and 10% CO
2 that the appliance is operating in this range, follow the steps below.
. To verify
1. Check incoming gas pressure to the appliance using a pressure gauge with a resolution of 0.1” w.c. or better and a range from 0” to at least 14” w.c. Close the gas shut-off inside the boiler jacket. Locate the inlet pressure tap on the gas valve (see Figure 15 in Section XI). Open the inlet pressure tap screw ½ turn and connect the positive side of the pressure gauge to the inlet pressure tap. Open the gas shut-off. The gas pressure should read between 4” and 10” w.c. for natural gas and between 10” and 14” w.c. for propane gas.
2. Drill a hole in the plastic CPVC vent pipe or exhaust tee, just large enough to allow access for the sample probe of your combustion analyzer.
3. Turn the thermostat to the closed position so the appliance is activated.
4. Allow the appliance to run for approximately 5 minutes.
5. Insert the sample probe of your combustion analyzer into the hole you drilled in step 2 above, about halfway into the exhaust gas stream. Take a flue gas reading and observe the CO the CO
2
2
value. Adjust the throttle screw until
value is between 8.5 and 10%. Turning the throttle screw counterclockwise increases the rate and the CO clockwise decreases the rate and the CO
2
2
value. Turning the throttle screw
value. Allow the appliance to stabilize for approximately 1 minute after adjusting the throttle screw before you take a reading with your combustion analyzer.
6. After adjustments are made stop the appliance, disconnect the pressure gauge, tighten the inlet pressure tap on the gas valve, remove the CO
2
meter from the CPVC pipe, and seal the hole with an appropriate material.
7. Return the thermostat switch to its original position.
FINAL CHECKOUT OF THE INSTALLATION
After any adjustment to the appliance, observe several complete cycles to ensure that all components function correctly.
SET THERMOSTAT
TO DESIRED TEMPERATURE
FINAL REVIEW AND SIGNOFF
Set thermostat to desired room temperature and observe several complete cycles to verify proper operation.
Review all instructions shipped with this boiler with owner or maintenance person. Instructions must be affixed on or adjacent to the boiler. Then complete and sign the
“Installation and Checkout Certificate”
at the end of this manual.
25
XIV. MAINTENANCE AND CLEANING
Maintenance as outlined below can be performed by the owner unless otherwise noted.
tings. Repair, if found. DO NOT use stop leak compounds.
The acidic nature of flue gasses condensing on the aluminum boiler sections will cause the formation of aluminum oxide. This oxide formation is normal, is generally uniform throughout the boiler sections, and represents a negligible mass of aluminum that is consumed by oxidation during the life of the boiler.
If left unchecked, this buildup may eventually cause blockage of the flue gas passages in the boiler sections, reducing efficiency, and ultimately shutting down the boiler due to lack of combustion air flow.
Regular service and maintenance by a qualified service agency must be performed to assure safe trouble free operation and maximum efficiency. It is recommended to service the appliance at least once every 12 months.
BEGINNING OF EACH HEATING SEASON
1. Schedule an annual service call by a qualified service agency, which includes:
2. Check that boiler area is free from combustible materials, gasoline, and other flammable vapors and liquids.
3. Circulator pump and blower motor furnished with boiler are permanently lubricated from the factory and require no further lubrication. Additional or non-factory supplied pumps and/or motors should be lubricated according to the pump and/or motor manufacturer’s instruction.
DAILY DURING HEATING SEASON
1. Check for and remove any obstruction to the flow of combustion air or venting of flue gases.
2. Check that boiler area is free from combustible materials, gasoline, and other flammable vapors and liquids.
a. Examine flue passages between boiler sections, burner, and condensate lines, and clean if necessary following the annual examination and cleaning instructions in paragraph F (below).
MONTHLY DURING HEATING SEASON
1. Remove jacket front and top panels and check for piping leaks around relief valve and other fittings. If found, contact a qualified service agency to repair.
DO NOT use stop leak compounds.
b. Visually inspect venting and air intake system for proper operation. If the vent or air intake show any signs of deterioration or leakage, repair or replace them immediately. Insure proper reassembly and resealing of the vent and air intake system.
c. Check for and remove any obstruction to the flow of combustion air or venting of flue gases.
2. Test relief valve. Refer to valve manufacturer’s instructions packaged with relief valve.
3. Visually inspect venting and air intake system for proper function. If the vent or air intake show any signs of deterioration or leakage, contact a qualified service agency to repair or replace them immediately and to insure proper reassembly and resealing of the vent and air intake system.
d. Follow instructions for
“Placing Boiler In Operation”
in Section XII of this manual.
e. Follow
ments”
“Checkout Procedures and Adjust-
on previous page.
4. Visually inspect the PVC condensate drain pipe for proper operation. If the drain pipe shows any signs of blockage, leakage, or deterioration contact a qualified service agency to clean, repair, or replace it immediately.
f. Visually inspect condensate drain line for proper operation. Check for deteriorated or plugged condensate drain line.
5. Check air vent(s) for leakage.
PERIODICALLY DURING HEATING SEASON g. Check all gasketed joints for leakage, and tighten bolts or replace gaskets if necessary.
h. Remove jacket front and top panels and check for piping leaks around relief valve and other fit-
Where low water cut offs are used, a periodic inspection of the low water cut off is necessary, including flushing of float type devices. Refer to low water cut off manufacturer’s specific instructions.
26
ANNUAL SHUT DOWN PROCEDURE
(END OF EACH HEATING SEASON)
1. Follow the instructions in
pliance”
in Section XII.
“To Turn Off Gas To Ap-
i. Use a flexible handle nylon brush to loosen sediment and aluminum oxide on all exposed heating surfaces of boiler (see
“Repair Parts
Manual”
for diagram).
Be sure that brush does not get stuck in heat exhanger!
2. If heating system is to remain out of service during freezing weather, and does not contain antifreeze, drain system completely. If boiler will be exposed to freezing temperatures, drain condensate lines. Otherwise, do not drain system or boiler.
j. After brushing and rinsing, remove any remaining loosened sediment using a shop vacuum with a snorkel attachment.
ANNUAL EXAMINATION AND CLEANING
OF BOILER COMPONENTS
The following service procedures must be performed only by a qualified service agency. Boiler owner should not attempt these procedures.
1. Before servicing, turn off electrical power to boiler at service switch. Close manual gas valve to turn off gas supply to boiler.
k. Inspect burner for any foreign matter in the flame ports or inside the burner. Any foreign matter should be removed by blowing with compressed air or vacuuming.
l. Reinstall burner and gaskets and position blower adapter assembly over studs. Install five nuts but do not tighten. Reinstall igniter and igniter gasket and fasten with two screws.
The igniter element is very sensitive. Do not touch the igniter element with your fingers or hands as oils or debris will cause premature failure
Tighten five nuts holding blower adapter assembly.
2. Examine flue passages by removing blower assembly from casting as shown in the separately provided
“Repair Parts Manual.”
The procedure for examining and cleaning the burner is described below.
m. Connect gas line to gas valve; air inlet assembly to gas valve (using 2” x 1½” flexible coupling); pressure switch hose to gas valve and air inlet assembly; 2” flexible coupling to boiler exhaust port; igniter wires; and gas valve wires.
Any buildup of sediment or aluminum oxide (white powdery or flaky substance) in the flue passages must be cleaned as follows: a. Remove jacket front and top panels.
b. Confirm that manual gas valve is closed and disconnect gas line to gas valve at union.
3. Visually inspect the condensate trap. Refer to repair parts diagrams. Any foreign material or debris that is visible in the condensate lines needs to be cleaned out as described below.
a. Inspect for sediment or blockage.
c. Disconnect wires to gas valve and igniter.
b. Flush out with water or vacuum.
d. Remove air inlet assembly from gas valve.
e. Loosen but do not remove five nuts attaching blower adapter assembly to boiler.
f. Remove two igniter screws and very carefully remove the igniter.
The igniter element is very sensitive. Do not touch the igniter element with your fingers or hands as oils or debris will cause premature failure.
g. Remove five nuts and blower adapter assembly. Remove burner and gaskets.
c. Follow the instructions under
“Near Boiler Piping”
in Section XII for filling condensate trap with water.
4. Inspection of the flue connector requires the following steps. Refer to the
“Repair Parts Manual”
for diagram.
a. Loosen clamp on draft inducer end of 2” flexible coupling that connects vent tee to exhaust port.
h. Aluminum oxide deposits are water soluble and may be rinsed away with spraying or running water.
b. Inspect interior of vent tee. Any buildup of sediment on the inside surface must be cleaned.
c. Reconnect the 2” flexible coupling to the draft inducer outlet.
27
XV. DETAILED SEQUENCE OF OPERATION
POWER ON
STAND BY
THERMOSTAT
CALLS FOR HEAT
CIRCULATOR
ENERGIZES THRU
2K1 CONTACTS
IBC SELF CHECK OF
INTERNAL CIRCUITRY
1-2 SEC
IBC
CHECKS
N.O. AIR
PRESSURE
SWITCH
CONTACTS
OPEN
CLOSED
FALSE
POSITIVES
PROOF OF
AIRFLOW. IBC WAITS
FOR 45 SEC
FOR AIR PRESSURE
SWITCH CONTACTS
TO OPEN
IF MAIN BURNER DOES NOT PROVE
FLAME IN 3 TRIALS, CONTROL
LOCKOUT.
VALVE/FLAME LIGHT BLINKS.
MANUAL RESET IS REQUIRED OR CONTROL
WILL AUTOMATICALLY RESET AFTER 1 HOUR.
THIS PROBLEM IS A RESULT OF NOT
ESTABLISHING FLAME SIGNAL.
CONTROL WILL ATTEMPT 2
ADDITTIONAL IGNITION SEQUENCES.
STARTING WITH PREPURGE.
NO
CLOSED
DOES
MAIN
BURNER PROVE
FLAME WITHIN INITIAL
TRIAL FOR
IGNITION
PERIOD?
YES
NORMAL
OPERATION
OPEN
DRAFT INDUCER
ENERGIZES THRU
1K1 CONTACTS
CLOSED
IBC
WAITS FOR
UP TO 5 MINUTES
FOR AIR PRESSURE
SWITCH CONTACTS TO CLOSE
INDICATING FAN
SUCTION
PRESENT
OPEN
CONTROL LOCKOUT.
PURGE LIGHT
BLINKS.
MANUAL RESET IS REQUIRED OR
CONTROL WILL AUTOMATICALLY RESET
AFTER 15 MINUTES. CIRCULATOR
REMAINS ENERGIZED AS LONG AS
THERMOSTAT CONTINURES TO CALL FOR
HEAT
PURGE LIGHT IS ON.
AIRFLOW PROVED.
DRAFT INDUCER RUNS FOR 15 SEC. PREPURGE
DURING THE LAST 2 SEC OF THE 5 SEC IGNITION
TRIAL, MAIN BURNER FLAME IS PROVED BY FLAME
RECTIFICATION. A FLAME SIGNAL TO IBC. GAS VALVE
REMAINS ENERGIZED. BOILER RUNS.
2 SEC INTO THE 6 SEC IGNITION TRIAL POWER
IS TURNED OFF TO THE HOT SURFACE IGNITER.
IGNITER LIGHT IS OFF.
GAS VALVE OPENS FOR 6 SEC. TRIAL FOR
IGNITION. BLUE ORANGE GLOW OF THE BURNER
CAN BE SEEN THRU OBSERVATION PORT.
GAS VALVE ENERGIZED THRU 3K1 AND 4K1
CONTACTS.
VALVE LIGHT IS ON.
PURGE LIGHT GOES OUT. HOT SURFACE IGNITER
POWERED THRU 5K1 5K2 CONTACTS FOR 20
SEC. IGNITER WARMUP. BRIGHT YELLOW
ORANGE GLOW OF THE HOT SURFACE IGNITER
CAN BE OBSERVED THRU THE OBSERVATION
PORT IN FRONT OF BOILER SECTION JUST
ABOVE IGNITER.
IGNITOR LIGHT IS ON
28
DETAILED SEQUENCE OF OPERATION
SAFETY SEQUENCES DURING OPERATION
DRAFT INDUCER TEMPERATURE SAFETY SWITCH
IF DRAFT INDUCER TEMPERATURE REACHES
TEMPERATURE SAFETY SWITCH SETPOINT,
SAFETY SWITCH CONTACTS OPEN IMMEDIATELY,
CLOSING GAS VALVE (LIGHT GOES OUT).
DRAFT INDUCER RUNS THROUGH 30 SECOND
POST PURGE AND SWITCHES OFF.
CIRCULATOR RUNS WITH THERMOSTAT ON CALL
FOR HEAT.
WHEN TEMPERATURE SAFETY SWITCH CONTACTS
REMAKE BEFORE END OF CALL FOR HEAT, CON-
TROL GOES INTO NORMAL LIGHT-OFF SEQUENCE.
CASTING TEMPERATURE SAFETY SWITCH
IF BURNER OPERATES WHEN BOILER HAS NO WA-
TER, ALUMINUM BOILER SECTIONS HEAT UP RAPIDLY.
CASTING TEMPERATURE SAFETY SWITCH CON-
TACTS WILL OPEN, BREAKING 24 VOLT POWER
TO IBC. POWER INDICATOR LIGHT GOES OUT.
REQUIRES MANUAL RESET TO RECLOSE CON-
TACTS.
POWER LIGHT GOES OUT.
LOSS OF FLAME SIGNAL
IF AN ESTABLISHED FLAME SIGNAL IS LOST WHILE
CONTROL EXPECTS THAT THE BURNER IS OPERAT-
ING, CONTROL WILL IMMEDIATELY DE-ENERGIZE
GAS VALVE.
VALVE AND FLAME LIGHTS GO OUT.
DRAFT INDUCER RUNS THROUGH 30 SECOND
POST PURGE.
CONTROL WILL ATTEMPT TO RELIGHT BOILER
3 TIMES. IF FLAME IS NOT PROVEN, CONTROL
LOCKOUT - PROBLEM ESTABLISHING A FLAME
SIGNAL.
VALVE LIGHT IS BLINKING.
CONTROL
WILL AUTOMATICALLY RESET AFTER 1 HOUR.
HIGH LIMIT CONTROL
IF BOILER WATER TEMPERATURE REACHES
HIGH LIMIT (AQUASTAT) SETPOINT, HIGH LIMIT
N.C. CONTACTS OPEN IMMEDIATELY, CLOSING
GAS VALVE.
VALVE AND FLAME LIGHTS GO OUT.
DRAFT INDUCER CONTINUES TO RUN FOR 30
SECOND POST PURGE AND SWITCH OFF.
CIRCULATOR RUNS AS LONG AS THERMOSTAT
CALLS FOR HEAT.
WHEN HIGH LIMIT CONTACTS REMAKE BEFORE
END OF CALL FOR HEAT - CONTROL GOES INTO
A NORMAL LIGHT-OFF SEQUENCE.
LOSS OF COMBUSTION AIRFLOW
IF COMBUSTION AIRFLOW IS LOST WHILE BURNER
IS FIRING (DIFFERENTIAL AIR PRESSURE SWITCH
CONTACTS OPEN) GAS VALVE WILL BE DE-ENER-
GIZED.
VALVE AND FLAME LIGHTS GO OUT.
DRAFT INDUCER RUNS THROUGH 30 SECOND
POST PURGE.
IF CALL FOR HEAT REMAINS, IBC WAITS 5 MIN-
UTES FOR AIRFLOW TO BE RE-ESTABLISHED.
IF AIRFLOW DOES NOT RE-ESTABLISH CON-
TROL LOCKOUT - PROBLEM WITH COMBUSTION
AIRFLOW.
PURGE LIGHT BLINKS.
CONTROL WILL
AUTOMATICALLY RESET AFTER 15 MINUTES.
CIRCULATOR PUMP
CIRCULATOR WILL BE ENERGIZED AS LONG AS
THERMOSTAT CALLS FOR HEAT DURING LOCKOUT.
RECOVERY FROM ANY LOCKOUT REQUIRES
RESET, WHICH CAN BE ACCOMPLISHED BY:
(A) REMOVING AND REESTABLISHING THE
THERMOSTAT’S CALL FOR HEAT OR TURNING
THE SERVICE SWITCH OFF AND BACK ON;
OR (B) WAITING FOR THE CONTROL TO
AUTOMATICALLY RESET AFTER 15 MINUTES
FOR LOSS OF COMBUSTION AIRFLOW OR
ONE HOUR FOR LOSS OF FLAME.
29
DETAILED SEQUENCE OF OPERATION
END OF NORMAL SEQUENCE OF OPERATION
THERMOSTAT ENDS CALL FOR HEAT.
GAS VALVE AND CIRCULATOR PUMP ARE DE-ENER-
GIZED,
VALVE AND FLAME LIGHTS GO OUT.
BLOWER RUNS FOR 30 SECONDS POST PURGE,
PURGE LIGHT IS ON.
BLOWER IS DE-ENERGIZED AFTER 30 SECONDS,
PURGE LIGHT SHUTS OFF.
BOILER STAND BY FOR NEXT CALL FOR HEAT.
30
DETAILED SEQUENCE OF OPERATION
SERVICE HINTS
!
WARNING
!
Fire, explosion, or shock hazard. May cause property damage, severe injury, or death. Do not attempt to modify the physical or electrical characteristics of this boiler in any way.
IMPORTANT
1. In a reset from lockout condition, all electrical meter readings at the gas control valve (24
VAC) must be taken within the trial for ignition period.
2. If any component does not function properly, make sure it is correctly installed and wired before replacing it.
3. Static electricity discharge can damage the Integrated Boiler Control (IBC). Touch metal surface to discharge static electricity before touching IBC.
4. The IBC cannot be repaired. If it malfunctions it must be replaced.
5. Only trained, experienced service technicians should service the IBC systems. See the chart on the previous page titled
“End of Normal Sequence of Operation”
for a normal light-off sequence.
6. All controls are factory tested in the assembly process and a defective control is generally the least likely cause. If you suspect you have a defective control, read through Section XVI,
“Troubleshooting,”
before you replace it.
7. It is extremely unlikely that two consecutive controls are defective. If it seems to be happening, chances are that either there is nothing wrong with the control or it is being damaged by some other problem (for example, an electrical short burning out a transformer.)
INITIAL SERVICE CHECKS
1. Before troubleshooting: a. Make sure that circuit breaker is on or fuse is okay ay electrical panel.
b. Make sure that service switch is on.
c. Make sure that gas is on at the gas meter, at all appropriate manual shutoff valves, and at the gas control valve.
d. Make sure that the thermostat is calling for heat.
e. Check that wire connectors at the Integrated Boiler Control and at the originating control are securely plugged in or connected.
f. Check that hoses are securely connected and are not plugged or damaged.
2. Troubleshooting Tools: a. Voltmeter to check 120 VAC and 24
VAC.
b. Continuity Tester.
c. Inclined Manometer or Pressure Gauge with 0-4.0” range (0.01” scale) for measuring suction pressures at pressure switch.
d. U-Tube Manometer or Differential Pressure
Gauge with 0-14” range (0.1” scale) for measuring inlet and manifold gas pressures.
3. What is System Status?
A. Consult the
“System Status”
chart in Sextion XVI,
“Troubleshooting.”
B. Refer to Figure 16 in Section XI of this manual for the location of the diagnostic indicator lamps on the boiler.
31
DETAILED SEQUENCE OF OPERATION
SERVICE HINTS
The differential air pressure switch is a safety device which will prevent the boiler from firing if there is an air intake, boiler heat exchanger or vent blockage.
1. Turn off service switch, or lower thermostat setting.
2. Remove vinyl caps from Tee.
3. Install testing lines as shown to inclined manometer or differential pressure gauge with the ability to read 0.01” to at least
6.0” w.c.
4. Turn on service switch and set thermostat to call for heat.
5. If manometer readings do not correspond to the chart at right, check for possible causes:
This diagram indicates the locations of the connection points required to check the differential air pressure.
TESTING
LINES
DIFFERENTIAL AIR
PRESSURE SWITCHES
TRANSPARENT WHITE
SILICONE HOSE
ORANGE SILICONE HOSE
• Blockage or moisture in suction lines to switch.
• Blockage or moisture in orifice installed in suction lines to switch.
• Blockage in air intake or vent pipes.
• Undersized air intake or vent pipes.
• Loose blower wheel on motor shaft.
• Incorrect pressure switch or pressure switch setpoint.
• Gas valve out of adjustment.
6. When pressure reading is proper and the pressure switch is operating properly, remove testing lines and reinstall vinyl caps to Tee and 3-way connector.
MANOMETER
Boiler Status Differential Pressure Switch Contacts
Not Running 0” 3.5”
0.5”
Closed
Open
Running Without Blockage
(Approximate min. vent lengths)
1.00” for Model 125
1.50” for Model 150
1.50” for Model 175
2.00” for Model 200
3.5”
0.5”
Closed
Closed
Running With
Blockage
Greater Than or Equal
To Setpoints
3.5”
0.5”
Open
Closed
32
XVI. TROUBLESHOOTING
SYSTEM STATUS
The indicator lights track the operating sequence. If the system locks out, the lights indicate the point in the sequence of operation were lockout occurs. If this table does not readily provide the reason for boiler malfunction or non-operation, refer to the following pages for more detailed troubleshooting procedures.
LIGHT
POWER
PURGE
IGNITER
VALVE
FLAME
STATUS
On
Off
INDICATES
IBC is energized through 24 volt transformer.
IBC is not energized.
Blinking IBC receives more than 40 VAC.
On IBC is energizing the draft inducer and air flow is proven.
Off
Blinking
Off during purge cycle - draft inducer is not powered on or air flow is not proven.
Off during igniter and run cycle - normal operation, purge cycle complete.
IBC is locked out. Problem could indicate false positive proof of air flow. Blocked vent, intake air pipe, flue way, or orifice in negative pressure hose.
On
Off
On
Off
IBC is energizing igniter.
Igniter is not energized.
IBC is energizing gas control valve to open.
Gas control valve is closed.
Blinking
IBC is locked out. Problem is flame has not been proven in three (3) ignition attempts.
May be due to broken igniter or lack of/low flame signal, or no gas.
On Bright Flame proven.
On Dim Checking for flame signal (during trial for ignition)
Off Flame unproven.
!
WARNING
!
ELECTRICAL SHOCK HAZARD MAY CAUSE SERIOUS INJURY OR DEATH.
The following procedures may expose you to dangerous line voltage. Use caution to avoid touching live electrical contacts. Service must be performed by a trained, experienced service technician.
WHAT TO DO IF YOU SMELL GAS:
• Do not try to light any appliance.
• Do not touch any electric switch or use any phone in the building.
• Immediately call your gas supplier from a neighbor’s phone. Follow the gas supplier’s instructions.
• If you can not contact your gas supplier, call the fire department.
Should overheating occur or the gas supply fail to shut off, do not turn off or disconnect the electrical supply to the pump. Instead, shut off the gas at a location external to the applicance.
Do not use the boiler if any part of the gas control system has been under water. A qualified service technician should inspect the boiler and replace any part of the control system and any gas control which has been under water.
Use only your hand to turn the gas control knob. Never use tools. If the knob will not turn by hand, don’t try to repair it. Force or attempted repair may result in a fire or explosion.
33
TROUBLESHOOTING
TROUBLESHOOTING CHART #1
�������������������������������
�����������������������
���
��
�������
���������������������������������
������������������������������
����������������������������
��������������������������������
����������������������������
������������������������������
��������������
������������������
���
��
���������������������������������������
������������������������������
�������������������������������
���������������������������������
������
����������������������������
������������������������
����
�������
34
�������
TROUBLESHOOTING
TROUBLESHOOTING CHART #2
��
�������
������������������������������������
������������������������������������
��
�������������������������������
��
���������������������������������
�������������������������������������
������������������������������������
��������������
������
�������������������������������������
������������������������������������
���������
���
�������������������������������������
���������������������
���
�������������������������������
����������
���
��������������������������������
����������
���
����������������������������������
���
�����������
����
��
��
��
��
��
��
�������
������������������������������������
��������������������������������
���
�������������������������������
���
�������������������������
��
��
�����������������������������������
���������������������������������
������������������������������������
�����������������
�����������������������������������
�������������
�����������
����������������������������
�������������������
����������������������������������
��������������
���������������������������������
���������������������������������
���������������
������ ����
�������������������
��������������
���������������������������
������������������
�����������
���������������������������
�����������������
35
CHART 1
OPEN
TROUBLESHOOTING
TROUBLESHOOTING CHART #3
BLOWER STARTS
YES
PURGE LIGHT ON?
YES
NO CHECK FOR VAC
BETWEEN TERMINALS 1 AND 3
AT CONNECTOR CN4 ON IBC
YES
CHECK FOR 120 VAC AT
BLOWER LEADS ON WIRING
HARNESS
YES
REPAIR/REPLACE
BLOWER
NO
NO
NO
IBC WAITS UP TO 5
MINUTES FOR NORMALLY
OPEN AIR
PRESSURE SWITCH
CONTACTS TO CLOSE,
INDICATING BLOWER
SUCTION IS
PRESENT
REPLACE IBC
REPAIR/REPLACE
WIRING FROM IBC
TO BLOWER
PRESSURE SWITCH
CONTACTS
OPEN
ARE ORIFICE IN
NEGATIVE PRESSURE
HOSE CLEAR?
YES
ARE VENT PIPE AND AIR
INTAKE PIPE CLEAR
(NO BLOCKAGE)
YES
CHECK AIR
PRESSURE SWITCH PER
INSTRUCTIONS ON
FOLLOWING PAGES. ARE
SAMPLING LINES CLEAR
AND CONNECTED
PROPERLY?
YES
NO
NO
NO
CLEAN OUT BLOCKAGE
AT ORIFICE
CLEAN OUT VENT PIPE
AND/OR AIR INTAKE PIPE.
CHECK FOR SAGS OR
LOW SPOTS WHERE
CONDENSATE MAY
PUDDLE AND BLOCK
THE VENT
CLEAN OUT SAMPLING
LINES OR REPLACE
DEFECTIVE SWITCH
CHECK FLUE PASSAGES
IN BOILER PER
"MAINTENACE AND
CLEANING". ARE FLUE
PASSAGES IN BOILER CLEAN?
NO
YES
CHECK DRAFT INDUCER
MOTOR RPM. IS IT
3400-3600?
YES
NO
CHECK FOR BROKEN OR
LOOSE IMPELLER ON DRAFT
INDUCER AND REPLACE
BLOWER IF FOUND TO
BE BROKEN OR LOOSE
CLEAN BOILER FLUE
PASSAGES PER
MAINTENANCE AND
CLEANING INSTRUCTIONS
REPLACE
BLOWER
15 SECOND PRE PURGE COMPLETE.
PURGE LIGHT IS OFF. SIMULTANEOUSLY
IGNITOR LIGHT IS ON AS IGNITOR CIRCUIT
IS ENERGIZED.
YES
CHART 4
NO
REPLACE IBC
36
TROUBLESHOOTING
TROUBLESHOOTING CHART #4
CHART 3
YES
IGNITER/SENSOR WARMS
UP AND GLOWS
YELLOW/ORANGE
DURING 20 SECOND
WARM UP
YES
NO
CHECK FOR 120 VAC
BETWEEN TERMINALS 1
AND 2 AT CONNECTOR
CN1 ON IBC (DURING
IGNITER WARM UP)
YES
CHECK FOR 120 VAC AT
IGNITER/SENSOR LEADS
ON WIRING HARNESS
(DURING IGNITER
WARM UP)
YES
NO
NO
REPLACE IBC
REPAIR/REPLACE WIRING
FROM IBC
TO IGNITER/SENSOR
REPLACE IGNITER/SENSOR
AFTER 20 SECOND
IGNITER WARM UP, GAS
VALVE IS ENERGIZED
VALVE LIGHT IS ON
2 SECONDS LATER POWER
IS REMOVED FROM
IGNITER/SENSOR
IGNITER LIGHT IS OFF
DOES MAIN BURNER
LIGHT?
NO
YES
CHECK FOR 24 VAC
ACROSS TERMINALS MV
ON THE GAS CONTROL.
WHILE VALVE/FLAME
INDICATOR LIGHT IS ON
YES
NO
CHECK FOR 24 VAC
ACROSS TERMINALS
CN6-2 AND CN6-5 ON
IBC, WHILE THE VALVE/
FLAME LED IS LIT
YES
REPAIR/REPLACE WIRING
BETWEEN IBC AND
GAS CONTROL
NO
REPLACE IBC
CHART 5
CHECK IF IGNITER/
SENSOR POSITION IS OK?
TIP SHOULD BE SLANTED
TOWARDS BURNER
YES
CHECK GAS SUPPLY
PRESSURE AT INLET
PRESSURE TAPPING ON
GAS CONTROL IS GAS
PRESSURE GREATER
THAN 4.0" W.C.?
YES
NO
NO
RESTORE IGNITER/SENSOR
TO CORRECT POSITION.
DO NOT RELOCATE
ARE ALL MANUAL
SHUT-OFFS IN THE GAS
SUPPLY LINE AND ON
THE GAS CONTROL IN
THE OPEN OR ON
POSITION?
YES
CONTACT THE GAS UTILITY
TO TURN THE GAS ON
NO
OPEN OR TURN ON ALL
MANUAL SHUTOFFS
CHART 5
37
TROUBLESHOOTING
TROUBLESHOOTING CHART #5
�������
���
�������
���
��������������������������
����������������������������������
�������������������
��������������������
�����������������������������������
�������������������������
���
��
�������������������������
����������������������������������������������
�������������������������
����������������������������������
��������������������������������
������������������������������
���
���������������������������
�����������������������������
�������������������������������
�����������������������������
������
��
��
�������������������������������������������
�������������������������
�������������������������������������������
���������������������
����������������������������������
�����������������������������������
���������������������������������
��
��������������
�����
�����������������
�������������������
����������������
���������������
��������������
��
�����
�����
�����������������������
�����������������������
������������������������������
���������������
��������������������������
�����������������������
����������������������������
���������������������
������������������������
����������������������
���
��������������������������
�������������������������
����������������������
�����������������������
���
�����������
��
��������
��������������
��������������������
����������������
��
�����������������
�������������������
��������������
��������
��������������
������� ������� �������
38
CHART 5
YES
TROUBLESHOOTING
TROUBLESHOOTING CHART #6
CHART 5
NO #3
CHART 5
NO #2
RUNS FOR 25-50 SECONDS,
THEN TURNS OFF.
CHECK FIRING RATE OF UNIT.
IS UNIT FIRING AT THE CORRECT RATE?
BOILER SHUTS OFF BEFORE END OF
CALL FOR HEAT. ARE HI LIMIT
AQUASTAT CONTACTS CLOSED?
NO
YES
SEE TROUBLESHOOTING PATH
#2 ABOVE
NO
REPLACE GAS CONTROL.
YES
CHECK GAS ORFICICE SIZE.
IS GAS ORIFICE SIZE CORRECT.
CHECK REPAIR PARTS LIST
FOR CORRECT SIZE. IS GAS ORIFICE
CLEAR OF BLOCKAGE.
YES
DOES THE UNIT USE LP GAS.
NO
ADJUST RATE AS DESCRIBED IN THE
CHECK OUT PROCEDURE AND
ADJUSTMENT SECTION
OF THE MANUAL.
YES
CHECK BURNER FOR ANY DETERIORATION
IN THE FLAME PORTS. ARE BURNER PORTS
IN GOOD CONDITION.
NO
YES
CHECK FLAME SIGNAL > 0.6uA?
CONSULT BOILER MFGR. FOR
SPECIFIC INSTRUCTIONS. REQUIRES
SPECIFIC TOOLS.
NO
YES
BOILER OFF ON HIGH LIMIT. IS
ACTUAL BOILER WATER TEMP.
GREATER THAN HI LIMIT SET POINT
MINUS 30°F CONTROL DIFFERENTIAL?
REPLACE WITH CORRECT
AIR BAFFLE.
REPLACE BURNER
REPLACE IBC
NO
REPLACE
AQUASTAT
NO
OK
SET THERMOSTAT BELOW ROOM
TEMPERATURE TO END CALL FOR
HEAT
YES
DOES CIRCULATOR PUMP STOP?
YES
NO
VALE LIGHT IS OFF
YES
DOES DRAFT BLOWER
STOP AFTER 30
SECOND POST PURGE?
YES
SYSTEM OK
NO
NO
ARE THERMOSTAT CONTACTS OPEN?
YES
REPLACE IBC
NO
REMOVE WIRING HARNESS
CONNECTION CN9 FROM GAS
CONTROL DOES GAS CONTROL
CLOSE?
YES
REPLACE IBC
NO
REPLACE THERMOSTAT
REPLACE GAS CONTROL
39
XVII. INSTALLATION & CHECKOUT CERTIFICATE
Boiler Model___________________Serial #___________________Date Installed_____________
Measured BTU/HR Input___________________ o Installation instructions have been followed o Checkout procedure and adjustments performed o Maintenance and Service issues reviewed with owner/ maintenance person o Installation booklet affixed on or adjacent to boiler
Installer (Company) __________________________________________________________
Address ___________________________________________________________________
Phone _____________________________________________________________________
Installer’s Name _____________________________________________________________
Signature __________________________________________________________________
40
advertisement
Related manuals
advertisement
Table of contents
- 2 I. Introduction
- 2 II. Safety Symbols
- 3 III. Rules For Safe Installation and Operation
- 4 IV. Boiler Ratings and Capacities
- 5 V. Before Installing The Boiler
- 9 VI. Placing The Boiler
- 9 VII. Near Boiler Piping
- 11 VIII. Combustion Air and Vent Pipe
- 13 IX. Gas Supply Piping
- 15 X. Electrical Wiring
- 17 XI. Controls and Accessories
- 19 XII. Startup
- 23 XIII. Checkout Procedures and Adjustments
- 26 XIV. Maintenance and Cleaning
- 28 XV. Detailed Sequence of Operation
- 33 XVI. Troubleshooting
- 40 XVII. Installation and Checkout Certificate