- Home
- Domestic appliances
- Climate control
- Split-system air conditioners
- Greenheck
- 484279 Microprocessor Controller DOAS v4.001 February 2020
- Installation and Operation Manual
Greenheck 484279 Microprocessor Controller DOAS v4.001 February 2020 Installation and Operation Manual
Add to my manuals
56 Pages
advertisement
®
Document 484279
Microprocessor Controller for
Dedicated Outdoor Air System
Reference Guide for Microprocessor Controller
Please read and save these instructions for future reference. Read carefully before attempting to assemble, install, operate or maintain the product described. Protect yourself and others by observing all safety information. Failure to comply with these instructions will result in voiding of the product warranty and may result in personal injury and/or property damage.
DOAS v4.001
Technical Support
Call 1-866-478-2574
Program Features
The microprocessor controller offers control through easy monitoring and adjustment of unit parameters by way of a lighted graphical display and an integral pushbutton keypad.
Pre-Programmed Operating Sequences
Introduction
The controller has been pre-programmed to offer multiple control sequences to provide tempered air.
Factory default settings allow for easy setup and commissioning. The sequence parameters are fully adjustable. Refer to the Sequence of Operation for details.
digital output is reserved for remote alarm indication.
Alarms are also communicated via BMS (if equipped).
Occupancy Modes
The microprocessor controller offers three modes of determining occupancy: a digital input, occupancy schedule or the BMS. If in the unoccupied mode, the unit will either be shut down, continue normal operation utilizing adjustable unoccupied set points, recirculate with unoccupied set points or will cycle on to maintain adjustable unoccupied space temperature and humidity set points (space temperature and humidity sensor is optional).
BMS Communication
The user can remotely adjust set points, view unit status points and alarms. The microprocessor controller is capable of communicating over several protocols:
Remote Unit Access (if equipped)
The WebUI and Remote Display are two ways to gain access to the unit controller allowing monitoring of the unit and parameter adjustment without being at the unit.
• BACnet® MSTP
• BACnet® IP
• LonWorks®
• Modbus RTU
• Modbus TCP
Reference Points List for a complete list of BMS points.
The WebUI can be accessed via a building network and is included with every unit controller. The Remote
Display is an LCD to be panel mounted in a remote location and is an option available for purchase.
Built-In Occupancy Schedule
The controller has an internal programmable time clock, allowing the user to set occupancy schedules for each day of the week. The controller option also has morning warm-up and cool down capability for improved comfort at the time of occupancy.
WARNING
Electrical shock hazard. Can cause personal injury or equipment damage. Service must be performed only by personnel that are knowledgeable in the operation of the equipment being controlled.
Alarm Management
The microprocessor controller will monitor the unit’s status for alarm conditions. Upon detecting an alarm, the controller will record the alarm description, time, date, and input/output status points for user review. A
WARNING
Mechanical high static protection cutoffs must be installed by others to protect the system and equipment from over-pressurization when using factory provided control sensors. The manufacturer does not assume responsibility for this.
Microprocessor Controller for DOAS 1
®
Table of Contents
Sequence of Operation . . . . . . . . . . . . . 3-7
Controller Overview . . . . . . . . . . . . . . .8-11
Display Use . . . . . . . . . . . . . . . . . . . . . 12
Parameter Adjustment . . . . . . . . . . . . . . . 12
Web User Interface . . . . . . . . . . . . . . . . . 13
Main Menu . . . . . . . . . . . . . . . . . . . . . 14
Unit Status Overview . . . . . . . . . . . . . . 15-18
Unit Enable . . . . . . . . . . . . . . . . . . . . . 19
Menu
Control Variables
Temp Control . . . . . . . . . . . . . . . . 19-21
Dehumidification . . . . . . . . . . . . . . 22-23
Refrigeration. . . . . . . . . . . . . . . . . . . 24
Damper Control . . . . . . . . . . . . . . . 24-25
Energy Recovery . . . . . . . . . . . . . . . . 26
Fan Control . . . . . . . . . . . . . . . . . 27-28
Occupancy . . . . . . . . . . . . . . . . . . . 29
Advanced . . . . . . . . . . . . . . . . . . 30-36
Alarms . . . . . . . . . . . . . . . . . . . . . . 37
Appendix
A: Remote Display . . . . . . . . . . . . . . . . .38
B: I/O Expansion Board Quick Start. . . . . . . .39
C: Space Thermostat Quick Start . . . . . . . 40-41
D: GreenTrol ® Airflow Monitoring Quick Start . . . 42
E: Points List . . . . . . . . . . . . . . . . . . 43-54
F: Modbus Connections . . . . . . . . . . . . . .55
Our Commitment . . . . . . . . . . . . . Backcover
2 Microprocessor Controller for DOAS
®
The microprocessor controller can be configured for air handler, energy recovery, and dedicated outdoor air systems. Each application utilizes similar technologies for heating and cooling: chilled water, hot water, indirect gas, electric heat, and packaged or split DX cooling. All set points, lockouts and delays are user adjustable via the integral keypad display, remote display, or web user interface.
General Operation
Sequence of Operation
UNIT START COMMAND: The microprocessor controller requires a digital input to enable operation.
The unit can then be commanded on or off by this digital input, keypad, the BMS or schedule. When a start command becomes active the following steps occur:
• Energy recovery wheel starts, if equipped
• Factory mounted and wired dampers are powered
(Outside air, exhaust air, and recirculation air dampers, if equipped)
• Exhaust fan, if equipped, starts after adjustable delay
• Supply fan starts after adjustable delay
• Tempering operation starts after adjustable delay
UNIT/SYSTEM DISABLED COMMAND:
The unit becomes disabled due to the following:
• The unit was disabled from the controller’s Unit
Enable screen.
• The unit enable digital input changes to the disabled state.
• The unit was disabled from the BMS.
• The remote start input is in the off position.
• The shutdown input is in the shutdown position.
• A system shutdown alarm was activated.
When disabled the following actions occur:
• The unit shuts down immediately; and
• Dampers spring-return to their off position.
OCCUPANCY: The microprocessor controller offers five modes of determining occupancy: digital input, occupancy schedule, BMS, always occupied, or always unoccupied. When in the unoccupied mode, the unit can be configured to shut down, or cycle on to maintain the unoccupied space set points. The unit can be temporarily overridden to the occupied mode via a digital input, keypad display, or space thermostat, if equipped.
UNIT STOP COMMAND: A shutdown occurs when there is not an occupied or unoccupied start command.
The following shutdown methods can occur.
Hard shutdown occurs under the following conditions:
• A user or the BMS disables the system, and the supply temperature is less than the soft shutdown enable set point.
• Occupancy is commanded to unoccupied while there is no unoccupied start command, and the supply temperature is less than the soft shutdown enable set point.
• Occupied Mode:
- Exhaust fan on, if equipped
- Supply fan on
- Energy Recovery Wheel Control (refer to
Energy Recovery Wheel section), if equipped
- Damper Control (refer to Outside Air and
Recirculated Air section), if equipped
- Heating (refer to Heating section)
- Cooling (refer to Cooling section)
When a hard shutdown occurs:
• The unit shuts down immediately.
• Dampers spring-return to their off position. Damper power is cut 30 sec. after the fans. This allows the fans to slow down prior to spring closing the dampers.
Soft shutdown occurs under the following conditions:
• A user or the BMS disables the system, and the supply temperature is greater than or equal to the soft shutdown enable set point.
• There is no unoccupied or occupied start command and the supply temperature is greater than or equal to the soft shutdown enable set point.
• Unoccupied Mode:
- Unit Off: Unit remains off when in unoccupied mode.
- Normal operation with unoccupied set points:
Unoccupied mode will operate as if in occupied mode but will utilize adjustable unoccupied set points.
º Exhaust fan on, if equipped
º Supply fan on
º Energy Recovery Wheel Control (refer to Energy Recovery Wheel section), if equipped
º Damper Control (refer to Outside Air and
Recirculated Air section), if equipped
º Heating (refer to Heating section)
º Cooling (refer to Cooling section)
The following occurs during a soft shutdown:
• Tempering outputs immediately revert back to their off value; while
• Dampers remain open and fans continue to run; until
– The supply air temperature falls below the soft shutdown enable set point minus 5.0°F; or
– The soft shutdown delay timer has expired.
- Recirculation with unoccupied set points :
Optional unoccupied mode when there is an unoccupied recirculation damper. The unit will continue to run, but in full recirculation.
º Supply fan on
º Recirculation air damper open
º OA damper closed
º Tempering operations begin
Microprocessor Controller for DOAS 3
®
Sequence of Operation
- Night Setback: Unoccupied mode when there is space temperature and/or humidity sensor(s) connected to the controller. The unit will cycle on to maintain unoccupied space set points if there is a call for unoccupied heating, cooling or dehumidification.
º Exhaust fan off, if equipped
º Supply fan on
º Recirculation air damper open
º OA damper closed
º Tempering operations begin
• Morning Warm-Up/Cool Down: At the request to occupy the space, the unit will run using the warmup or cool down sequence until the occupied set point is achieved. The heating or cooling mode must not be locked out and the space temperature is below or above set point by the unoccupied hysteresis (5°F, adj). This optional sequence requires a space temperature sensor and is field-enabled.
The following steps occur during a morning warmup/cool down:
Set Point Control (Occupied)
- The dampers would be in full recirc if the damper if the damper actuators are not powered (adj) during occupied mode. Otherwise the following is true:
Supply air temperature set point can be configured as constant, or can be reset by either outside air temperature, or space temperature set point. If equipped with BMS communications, the user can also directly command the temperature set point, if equipped.
• Outside Air Temperature Reset Function: The controller will default to supply temperature reset based on OA temperature. The controller will monitor the OA temperature and reset the supply temperature set point based upon the OA reset function.
• Space temperature Reset: With a space temperature sensor, the controller will adjust the supply air temperature set point between the min
(55°F) and max (90°F), to satisfy the desired space temperature. The temperature set point can be adjusted locally at the microprocessor, the BMS or a space thermostat.
Set Point Control (Unoccupied)
• Outside air damper is open to minimum OAD position.
• Recirculation air damper is open at 100% minus
OAD position.
- Supply Fan is ON at 100%.
- Exhaust fan is OFF.
- In heating, controls to maintain the maximum supply set point (90ºF).
- In cooling, controls to the minimum supply set point (50ºF).
- Reheat off.
- Energy recovery wheel off.
Heating
The heating is controlled to maintain the supply temperature set point. The heating will be locked out when the outside air temperature is above the heating lockout (80°F adj).
• Indirect Gas Furnace: Microprocessor controller will modulate the indirect gas furnace to maintain the supply temperature set point.
When equipped with an unoccupied recirculation damper and optional space temperature and/or humidity sensors, the unit will cycle on to maintain the unoccupied space set points.
• Unoccupied Heating: If equipped with heating, the unit is enabled when the space temperature is less than the unoccupied heating set point minus differential (60°F). The supply air temperature set point will be set to the supply max reset limit (90°F).
The unit cycles off when the space temperature reaches the unoccupied heating set point.
• Hot Water Coil: Microprocessor controller will modulate a hot water valve (provided by others) to maintain the supply temperature set point.
Coil freeze protection must be provided by others in the field!
• Electric Heater: Microprocessor controller will modulate an electric heater to maintain the supply temperature set point.
• Unoccupied Cooling: If equipped with cooling, the unit is enabled when the space temperature is greater than the unoccupied cooling set point plus differential (80°F+5°F). The supply air temperature set point will be set to the supply min reset limit (55°F).
The unit cycles off when the space temperature reaches the unoccupied cooling set point.
Cooling
The cooling is controlled to maintain the supply temperature set point. The cooling will be locked out when the outside air temperature is below the cooling lockout (55°F).
• Unoccupied Dehumidification: If equipped with cooling, the unit is enabled when the space relative humidity exceeds the unoccupied space relative humidity set point plus differential (50%+5%). The supply air temperature set point will be set to the equivalent occupied supply set point.
• Chilled Water: Microprocessor controller will modulate a chilled water valve (provided by others) to maintain supply air set point. Coil freeze protection must be provided by others in the field!
4 Microprocessor Controller for DOAS
®
Sequence of Operation
• Mechanical Cooling: Microprocessor controller enables stages of cooling to maintain the supply air setpoint. When a modulating compressor is installed
(Digital or Inverter Scroll), the compressor modulates to maintain the supply air setpoint. Mechanical cooling is available in the following configurations:
Initiation: One of the following must be true for a defrost cycle to initiate:
- The saturated suction temperature is less than
-15ºF; or
- The saturated suction temperature is less than ambient conditions (temp/dewpoint) minus an offset (35ºF/25ºF).
- Packaged DX: Unit with compressors and condensing section located within the same unit.
This unit may have lead standard, lead digital scroll, or lead inverter scroll compressors.
Termination: The defrost cycle is terminated when one of the following occur:
- Split DX: Unit with compressors located in the unit and utilizes a remote condenser section.
This type of unit may have lead standard, or lead digital scroll compressors.
- The saturated discharge temperatures of all refrigerant circuits are greater than the cancel defrost set point (80ºF); or
- The max defrost time (5 min) has been exceeded.
Air Source Heat Pump
When a unit is configured as an ASHP, compressors are used for cooling and heat pump heating. A reversing valve is energized when the unit is in heating mode to reverse the flow of the refrigerant. The ASHP is only available as a packaged unit with an inverter scroll as the lead compressor.
• Outside Coil Fan Control: Refrigerant pressure control with outside coil fans will have lead EC fans and utilize refrigerant transducers to stage fans on and off in cooling and heating. The following sequences are based on the current mode of operation:
• Cooling: Mechanical cooling operates the same as any other unit with compressors by controlling the compressors to maintain the supply air temperature set point in cooling mode and to maintain the cooling coil temperature in dehumidification mode.
- Cooling/Dehumidification: The lead outside fan turns on with the first compressor and holds for a min of 30 seconds based on the OA temperature.
The lead fan modulates to maintain the refrigerant pressure control set point for cooling mode. Each additional outside fan stage turns on based on the saturated temperature reaching set point plus an offset and turns off when the temperature falls below set point after a delay.
• Heat Pump Heating : When heat is required, the reversing valve is switched, and the compressors are staged to maintain the supply air temperature set point.
• Heat Pump Heating Lockout: Heat pump heating may be locked out for any of the following reasons:
- Defrost is initiated 3 times in one hour.
- Supply Air temperature is 5ºF below set point for more than 10 minutes and secondary heat is available as backup only.
- Heating: The lead outside fan turns on with the first compressor. The lead fan modulates to maintain the refrigerant pressure control set point for heating mode. Each additional outside fan stage turns on based on the saturated temperature being below set point minus an offset and turns off when the temperature rises above set point after a delay.
- Outside ambient temperature is below the HP ambient lockout set point(10ºF).
• Resetting HP Heating Lockout : One of the following conditions must occur to return to HP heating:
- The outside temperature increases by 5ºF.
- The outside humidity decreases by 20%RH, if humidity sensor is installed.
- The unit has been locked out for more than 2 hours when a humidity sensor is not installed and not locked out on low ambient condition.
• Defrost: Periodically, the ASHP need to initiate a defrost cycle to remove accumulated frost from the outside coil when operating in heating mode. The saturated suction temperature, the outside ambient temperature and/or the outside humidity determine when a defrost initiates and terminates.
- Defrost: When defrost is initiated, the outside fans turn off allowing the heat to build and defrost the outside coil. When defrost is terminated, the outside fans turn on to bring the pressure down before switching back to heating mode.
• Secondary Heat: A secondary heating device may be installed in the unit. This device may be electric heat, gas furnace, or a hot water coil. The following sequences are available for secondary heat:
- Backup : Secondary heat only operates when heat pump heating is not available.
- Supplemental : Secondary heat will operate simultaneously with heat pump heating when the compressors are not producing enough heat to stay within 2ºF of set point.
Microprocessor Controller for DOAS 5
®
Economizer
Sequence of Operation
If the application requires cooling, and the OA conditions are suitable for free cooling, the controller will enter economizer mode. If the unit is economizing and the discharge temperature set point is not being met, the controller will bring on mechanical cooling.
If equipped with a modulating OA and recirculated air damper, the dampers will modulate between the min OA and max positions to maintain the supply temperature set point. If equipped with an energy wheel, Reference Energy Recovery Wheel Sequence.
and balance of the unit. If equipped with BMS communications, the user can also directly command the supply fan speed. The following sequences are selectable for supply fan control. The fan speed in constrained by its min and max speed set points.
• Supply fan operates at a constant speed based on a constant volume set point based on occupancy.
• The supply fan is enabled by the unit controller. An external fieldsupplied 0-10 VDC signal to the fan’s VFD is responsible for modulating the supply fan’s speed.
The signal is linear and the speed is at min when 0V is present and at max when 10V is present.
• Temperature: The economizer will be locked out when:
- The outside air is greater than the economizer high lockout (65°F).
- The unit is operating in dehumidification mode.
- There is a call for heating.
• CO
2
Control: The supply fan modulates to maintain
CO
2
set point based on a sensor located in the space or return duct. A CO
2
sensor or BMS communicated value is required for this sequence.
• Temperature/Enthalpy: The economizer will be locked out when:
- The outside air is greater than the economizer high lockout (65°F dry-bulb).
- The outside air is greater than the economizer high enthalpy lockout (23 btu/lb).
- The unit is operating in dehumidification mode.
- There is a call for heating.
Dehumidification
• Duct Static Pressure Sensor: The supply fan modulates to maintain an adjustable duct static set point based on a sensor located in the supply duct. A static pressure sensor or BMS communicated value in required for this sequence.
• Space Static Pressure: The supply fan modulates to maintain a space static pressure set point based on a sensor located in the space. A space static pressure sensor or BMS communicated value in required for this sequence.
The cooling is controlled to maintain the cold coil set point. Dehumidification is enabled when the OA temperature is greater than the cold coil set point plus an offset (adj. 10ºF). Dehumidification is disabled when the OA temperature falls below the enable point by a hysteresis (2ºF). If equipped with BMS communications, the user can also directly set the cold coil leaving air set point.
• Optional Room Relative Humidity Sensor or
Thermostat: The controller will adjust the cold coil leaving air temperature set point between the min
(50°F) and max (55°F) set point to satisfy the desired space relative humidity set point.
• Single Zone VAV : The controller will control the supply air temperature and supply fan speed in order to maintain the space temperature.
Heating Mode The supply temperature set point will be increased before increasing the supply fan speed in order to maintain the space temperature set point. If the calculated supply temperature set point is greater than the current space temperature, the supply fan speed will be increased while the supply temperature set point is increased.
Cooling Mode The supply temperature set point will be decreased before increasing the supply fan speed in order to maintain the pace temperature set point.
Reheat
While the unit is dehumidifying, the supply air temperature is maintained by controlling the reheat device to the supply air set point.
• Hot Gas Reheat (valve): The microprocessor controller modulates to maintain set point.
• The microprocessor controller can be configured to use the primary heat source as secondary reheat.
Supply Fan VFD Sequence
The factory installed VFD is wired to the controller.
Supply fan speed needs to be set during test
Exhaust Fan VFD Sequence
The factory installed VFD is wired to the controller.
Exhaust fan speed needs to be set during test and balance of the unit. If equipped with BMS communications, the user can also directly command the exhaust fan speed. The following sequences are selectable for exhaust fan control. The fan speed constrained by its min and max speed set points.
• Exhaust fan operates at a constant speed based on a constant volume set point based on occupancy.
• The exhaust fan is enabled by the unit controller. An external field-
6 Microprocessor Controller for DOAS
®
Sequence of Operation supplied 0-10 VDC signal to the fan’s VFD is responsible for modulating the supply fan’s speed.
The signal is linear and the speed is at min when 0V is present and at max when 10V is present.
• Space Static Pressure: The exhaust fan modulates to maintain a space static pressure set point based on a sensor located in the space. A space static pressure sensor or BMS communicated value in required for this sequence. modulates wheel speed to maintain the supply temperature set point.
• Energy Wheel Bypass Dampers, if equipped:
During normal operation, the dampers shall remain closed to allow full operation of the energy wheel.
During economizer sequences, the dampers will be open to bypass the energy wheel.
• Supply Fan Tracking: The exhaust fan proportionally modulates based on the supply fan speed plus an adjustable offset.
• Outside Air Damper Tracking: The exhaust fan proportionally modulates based on the outdoor air damper modulation. (This sequence requires a modulating outdoor air damper.)
Frost Control: The microprocessor controller will activate the frost control method when the OA temperature is less than the defrost set point (5°F) and the wheel pressure switch is closed due to a high wheel pressure drop. Once the pressure drop decreases below the pressure switch point or the OA temperature increases, the unit will resume normal operation.
• Electric Preheater: When frosting is occurring, the preheater is energized to defrost the wheel.
Outside Air and Recirculated (Recirc) Air
Damper Control
If equipped with a modulating OA and recirculated air damper, the recirculated air damper will operate inverse of the OA damper. The OA damper opens to its min position. If the controller is configured to modulate the supply fan speed, the min and max OA positions can be reset based on supply fan speed. If equipped with
BMS communications, the BMS can directly control the outside damper position. The damper position is constrained by its min and max set point positions.
• CO
2
Control: The controller will proportionally modulate the OA/RA dampers based upon a comparison of the CO
2
set point to the actual CO level reported from the sensor. As the CO
2 the controller will proportionally modulate the OA
2
level rises, damper open, between the min OA damper position and max CO
2
position.
• Space Static Pressure: The OA/RA dampers will modulate based upon the signal from a building static pressure sensor. The controller will modulate the dampers, between the min and max OA positions, based upon a comparison of the building static pressure set point to the actual building static pressure level reported from the sensor.
Energy Recovery Wheel Sequences
Economizer: If the unit is equipped with an energy recovery wheel, the economizer will modulate/stop the energy wheel to achieve free cooling.
• Stop Wheel: When economizer mode is enabled and there is a call for cooling, the wheel will stop rotating to allow free cooling. Jog wheel control is available during stop wheel economizer operation. This sequence allows the wheel to rotate for a short period of time exposing a new section to the air stream.
• Modulate Wheel: When economizer mode is enabled and there is a call for cooling, the controller
• Modulate Wheel: When frosting is occurring, the wheel slows to allow defrosting to occur.
• Cycle Wheel: When frosting is occurring, the energy wheel is cycled off for a defrost cycle time
(5 minutes). After the defrost cycle time, the wheel is re-energized to continue normal operation. The controller will not allow another defrost cycle for a min normal operating cycle time (30 minutes).
• Timed Exhaust: When frosting is occurring, the supply fan is cycled off along with the tempering for a defrost cycle time (5 minutes). The exhaust fan will continue to run allowing the warm exhaust air to defrost the wheel. After the defrost cycle time, the supply fan and tempering are re-energized to continue normal operation. The controller will not allow another defrost cycle for a min normal operating cycle time (30 minutes).
Alarms
The microprocessor controller includes a digital output for remote indication of an alarm condition, which connects via the J15 port. Alarms include:
• Dirty Filter Alarm: If the outside air or return air filter differential pressure rises above the differential pressure switch set point, the microprocessor controller will activate an alarm.
• Supply and Exhaust Air Proving Alarm:
Microprocessor controller monitors proving switch on each blower and displays an alarm in case of blower failure.
• Sensor Alarm: Microprocessor controller will send an alarm if a failed sensor is detected (temperature, pressure, relative humidity).
• Supply Air Low Limit: If the supply air temperature drops below the supply air low limit (35°F), the controller disables the unit and activate the alarm output after a preset time delay (300 sec.).
• Other Alarms: Wheel Rotation, High Wheel Pressure,
High/Low Refrigerant Pressure.
Microprocessor Controller for DOAS 7
®
24VAC to Controller
Room RH
CO2 Sensor
After Cold Coil Temperature Sensor
Sensor U1, U2, U3 Common
Supply Discharge Temperature Sensor
Outdoor Air Temperature Sensor
G
G0
+V term
GND
+5 V
REF
U1
U2
U3
GND
+VDC
U4
GND
U5
GND
24VAC for Analog Outputs
Outdoor Air Damper Analog Output
Heating Analog Output
Cooling/VSC Cond Fan Analog Output
Hot Gas Reheat Analog Output
Supply Fan Proving
Wheel Pressure Limit
Wheel Rotation Alarm
Unit On/Off Input
Exhaust Fan Proving
Occupied/Unoccupied Input
Dirty Filter Input
Outdoor Relative Humidity Sensor
Building Pressure Sensor
Duct Pressure Sensor
Compressor Limit Circuit A
Compressor Limit Circuit B
Compressor Limit Circuit C
Compressor Limit Circuit D
Supply Fan VFD Output
Exhaust Fan VFD Output
Room Temperature Sensor
Discharge Pressure Circuit B (VSC)
2 Speed Fan Input
2 Position Damper Input
ID13H
ID13
IDC13
ID14
ID14H
U6
U7
U8
GND
ID9
ID10
ID11
ID12
IDC9
VG
VG0
Y1
Y2
Y3
Y4
ID4
ID5
ID6
ID1
ID2
ID3
ID7
ID8
IDC1
ID15H
ID15
IDC15
ID16
ID16H
Y5
Y6
U9
GND
U10
GND
ID17
ID18
IDC17
Large Controller Overview
Remote Display
• Six conductor RJ25 cable
• Connects to J10
Optional BACnet IP, Modbus TCP, Web UI, Ethernet Connections
NO14
C14
NC14
NO15
C15
NC15
C16
NO16
NO17
NO18
C16
NO12
C12
NC12
NO13
C13
NC13
C9
NO9
NO10
NO11
C9
C7
NO7
C7
NO8
C8
NC8
C4
NO4
NO5
NO6
C4
C1
NO1
NO2
NO3
C1
24 VAC When Unit On
Wheel Frost Mode
Supply Fan Enable
Exhaust Fan Enable
24 VAC from Supply Fan Proving
Heating Enable
Staged Compressor 1
Staged Compressor 2
24 VAC
Economizer Mode/Output to Dampers
Alarm Dry Contact
Staged Compressor 3
Staged Compressor 4
Compressor Fan 1 Enable (VSC)
Energy Recovery Wheel Enable
Condenser Fan
Inverter Compressor E-Stop (VSC)
Heat Pump Reversing Valve Output
Optional LonWorks cards are located in BMS Card port.
Optional Modbus RTU/BACnet MSTP connections are made to the J25 BMS2 terminal.
8 Microprocessor Controller for DOAS
®
24VAC to Controller
Refrigerant Pressure Circuit A
Refrigerant Pressure Circuit B
Supply Discharge Air Temperature
Sensor B1, B2, B3 Commons
After Cold Coil Temperature Sensor
Outdoor Air Temperature Sensor
G
G0
+V term
GND
+5 V REF
+VDC
U4
GND
U5
GND
U1
U2
U3
GND
24VAC for Analog Outputs
Cooling Analog Output
Condenser Fan Circuit A or Heating Analog Output
Hot Gas Reheat Analog Output
Condenser Fan Circuit B or Heating Analog Output
Supply Fan Proving
High Pressure Switch Circuit A
Low Pressure Switch Circuit A
Occupied/Unoccupied Input
OA/RA Damper End Switch
Unit On/Off Input
High Pressure Switch Circuit B
Low Pressure Switch Circuit B
Outdoor Relative Humidity Sensor
Outdoor Air Damper Output
Supply Fan VFD Output
Exhaust Fan Proving
Dirty Filter Input
Wheel Rotation Alarm
Freeze Stat Input
Condensate Drain Pan Switch
Remote Start Input
U6
U7
U8
GND
ID9
ID10
ID11
ID12
IDC9
ID13H
ID13
IDC13
ID14
ID14H
ID2
ID3
ID4
Y3
Y4
ID1
VG
VG0
Y1
Y2
ID5
ID6
ID7
ID8
IDC1
Medium Controller Overview
Remote Display
• Six conductor RJ25 cable
• Connects to J10
Optional BACnet IP, Modbus TCP, Web UI, Ethernet Connections
C7
NO7
C7
NO8
C8
NC8
C4
NO4
NO5
NO6
C4
C1
NO1
NO2
NO3
C1
24 VAC When Unit On
Staged Compressor 1
Staged Compressor 2
Staged Compressor 3
24 VAC from Supply Fan Proving
Staged Compressor 4
Supply Fan Start
Exhaust Fan Start
24 VAC
Damper Actuator Power
Alarm Dry Contact
NO12
C12
NC12
NO13
C13
NC13
C9
NO9
NO10
NO11
C9
Condenser Fan Ramp 1 - Stage 2 Start
Condenser Fan Ramp 1 - Stage 3 Start
Condenser Fan Ramp 2 - Stage 2 Start
Inverter Compressor E-Stop (VSC)
Condenser Fan Ramp 2 - Stage 3 Start
®
Optional LonWorks cards are located in BMS Card port.
Optional Modbus RTU/BACnet MSTP connections are made to the J25BMS2 terminal.
Microprocessor Controller for DOAS 9
c.pCOe - Expansion Board Overview, Medium Controller Arrangement
24 VAC Power
Heating Output
Exhaust Fan VFD Output
Energy Recovery Output
Space Temperature
Mixed Air Temperature
Exhaust Air Temperature
Space Humidity
Space Static Pressure
Supply Air Duct Static Pressure
Space Set Point Adjustment
Wheel Enable
Furnace Heating Stage 1
Furnace Heating Stage 2
Preheater Enable
The expansion board is an I/O module than can be used to monitor additional statuses or provide commands from medium board controller.
10 Microprocessor Controller for DOAS
®
24 VAC to Controller
Main Gas Valve
Ignition Controller Alarm
Low Speed Pressure Switch
24 VAC for Analog Outputs
Modulating Gas Valve
Modbus Connection pCOe - 4:1 Furnace Overview
High Speed Pressure Switch
Modbus Address Switches
Ignition Controller
24 VAC
High Speed Fan
24 VAC
24 VAC to Controller
Main Gas Valve - Small Manifold
Main Gas Valve - Large Manifold
Ignition Controller Alarm
24 VAC for Analog Outputs
Modulating Gas Valve
Modbus Connection pCOe - High Turndown Furnace
Low Speed Pressure Switch High Speed Pressure Switch
Ignition Controller - Small Manifold
24 VAC
High Speed Fan
24 VAC
Ignition Controller - Large Manifold
24 VAC
Modbus Address Switches
Microprocessor Controller for DOAS 11
®
Display Use
The microprocessor controller is located in the unit control center. The face of the controller has six buttons, allowing the user to view unit conditions and alter parameters. The microprocessor controller is pre-programmed with easy to use menus. A remote display is also available, which connects via the J10 port with six wire patch.
Button Description
Main Menu
Alarm
Escape
Up
Enter
Down
Keypad Description
Functions
Press to go directly to the Main Menu from any screen.
From the Main Menu, navigate to the following screens:
• Unit Enable
• Unit Status
• Ctrl Variables
• Alarm Menu
The Alarm button flashes when there is an active alarm.
Press to view alarms.
Press twice to go to the alarms reset screen.
Press from the Main Menu to view the Unit Status screen.
Press to go back one menu level.
Press to navigate through the menus/screens.
Press after entering a variable to increase a current value.
Press to enter a highlighted menu or screen item.
Press to enter a writable variable and press again to confirm the new variable value.
Press to navigate menus/screens.
Press after entering a variable to decrease the current value.
Unit display on web interface only.
These two buttons on the virtual keypad/display are used to simulate two-button actions on the handheld keypad/display.
To simulate pressing two buttons simultaneously:
1. Click on 2-Button Click.
2. Then, sequentially click on two keypad buttons (Main, Alarm, Escape, Up, Enter, Down).
To simulate pressing and holding two buttons simultaneously:
1. Click on 2-Button Hold.
2. Then, sequentially click on two keypad buttons (Main, Alarm, Escape, Up, Enter, Down).
Parameter Adjustment
The cursor always begins in the upper left corner of the display and will be blinking. Press the button to move the cursor down for parameter adjustment.
Supply air low limit
Alarm when supply is below: 35.0º F
Alarm delay: 300s
Supply air low limit
Alarm when supply is below: 32.0º F
Alarm delay: 300s
Once the cursor has reached the desired parameter, press the adjust the value.
buttons to
Supply air low limit
Alarm when supply is below: 32.0º F
Alarm delay: 300s
When satisfied with the adjustment, press the button to save the parameter.
When finished, make certain the cursor is in the upper left corner. If the cursor is not in the upper left corner, the changes will not be saved. The cursor must be in the upper left corner to enable screen advancement.
12 Microprocessor Controller for DOAS
®
Web User Interface
The Web User Interface allows access to the unit controller through the building network. Reference Ctrl Variables/
Advanced/Network Settings to set the IP network protocol. Once proper communication is established, the user can click on the follow tabs:
Overview – Includes a functioning unit graphic, monitoring points, and active set point adjustment.
Alarms – Shows current and cleared alarms.
Trending – User can view past and present controller points.
Information – Provides manufacturer support information as well as IOM resources.
Service – User must be logged with service access criteria (9998). Once proper login is established, the user can view configured input/output points associated with the unit controller
Pop-Up Tools
Live Trend - User can see current values from the controller. The list of variables available is preselected based on the configuration of the unit.
Unit Display - Mimics the unit controller display. Allows the user full access to the controller without having to physically be at the unit.
Dewpoint Calculator - A calculator with three sliders to determine the dew point, temperature, or humidity. Two of the three values are necessary to get the third.
Upgrade Application - A new application program can be loaded to the controller via the WebUI.
Unit Display
Web User Interface
®
Web User Interface
Logged in with Service, red boxes will appear after logging in.
Microprocessor Controller for DOAS 13
Unit Enable Main Status
Unit Status
Input Output Status
Note:
Additional status screens are displayed depending on unit configuration.
Screens may include, but are not limited to:
Occupancy
Damper positions
Fan status
Airflow
Set Points
Economizer
Energy recovery
Cooling
Circuit pressure
Heating
Dehumidification
Static pressure
Main Menu Navigation
Temp Control
Dehumidification
Ctrl Variables
Refrigeration
Compressor Control
Pressure Control
Heat Pump Control
Damper Control
Energy Recovery
Fan Control
Supply Fan Control
Exhaust Fan Control
Occupancy
Advanced
Note:
The Advanced menu is readonly. The service password is required to change these settings.
Reference the
Advanced menu section for more information.
*Consult factory for more information.
Login
Manual Overrides
Adv. Set Points*
PID Tuning*
Network Settings
Backup/Restore
IO Status/Offset*
IO Config
Unit Config*
Service Config
Factory Config
Unit Settings*
Service Info*
Alarm
Management
Shutdown
Alarms
General
Alarms
Alarm Menu
Alarm History
Active Alarms
Reset History
Clear History
Export History
14 Microprocessor Controller for DOAS
®
Unit Status Overview
The microprocessor controller will revert to a default main menu loop. This loop includes several screens to view the operating conditions of the unit. Scroll through the menu screens by using the buttons.
T he iniTial menu screen displays The job name
, uniT Tag
, uniT sTaTus
, ouTside air condiTions , space condiTions and seT poinTs .
Possible modes include:
• Off/Standby
• Unoccupied Start
• Dampers Open
• Fan Start Delay
• Fans Starting
• Startup Delay
• System On
• Soft Shutdown
• System Disabled
• Remote Off
• Shutdown Alarm
• Fans Only
• Economizing
• Cooling
• Dehumidifying
• Heating
• HGRH Purging
• Defrost Active
• Overrides Active
• Expansion Offline
Symbol
Unit Status Screen Symbols
Indicates
Supply air fan status.
Rotation indicates airflow; static blades indicate no airflow.
Cooling
Heating
Dehumidifying
Economizing
Defrost i npuT o uTpuT s TaTus
Displays real time conditions from sensors located in the unit and building space if equipped with space mounted sensors. Controller output conditions can also be viewed from this screen. To view the desired input/output point, the user must select the desired channel. Reference the Controller Overview section in this manual for individual point locations.
o ccupancy s TaTus
Displays current status of occupancy and the configured occupancy control method and time zone.
d amper
c ommanded
p os
This screen appears if equipped with modulating OA and recirculated air dampers. Displays current position of the OA damper. s upply
F an
s
TaTus
This screen displays the fan enable command, fan proving status, and the supply fan ramp being sent from the controller to the VFD. The min and max speeds are set in the VFD (Reference unit Installation and Operation Manual for VFD programming). The controller can modulate the fan between the min and max speeds via an analog output.
Microprocessor Controller for DOAS 15
®
Unit Status Overview e xhausT
F an
s
TaTus
This screen displays the fan enable command, fan proving status, and the exhaust fan ramp being sent from the controller to the VFD. The min and max speeds are set in the VFD (Reference unit Installation and Operation Manual for
VFD programming). The controller can modulate the fan between the min and max speeds via an analog output.
a irFlow s TaTus
This screen displays the current status of airflow volumes if the unit is provided with airflow monitoring.
a mbienT
l ockouT
s
TaTus
Displays heating and cooling lockout status based on the outside air ambient temperature. Ambient lockouts for heating and cooling can be altered by entering
Main Menu/Ctrl Variables/Temp Control/Cooling or Heating.
o uTside r eseT
This screen will be active if the controller is configured for outside air reset. The heating and cooling devices modulate to maintain the supply air temperature set point as determined by the outside reset calculation.
a cTive
r eseT
This screen will be active if temperature control mode is set for space or return air reset. The supply temperature set point is calculated based on the active set point and the current space or return temperature. The calculated set point is scaled between the supply temperature min and max set points determined by the current mode of operation.
s upply s eT p oinT
This screen is active when supply temp control is selected or the active mode of control. Displays current supply temperature and supply temperature set point to be achieved.
e conomizer
r amp
The economizer ramp screen will be active if the unit is configured for economizer control. This screen displays the economizer set point, supply air discharge temperature, economizer ramp status, and economizer control mode. Economizer control mode options include, outside dry bulb, outside enthalpy, comparative dry bulb, and comparative enthalpy.
CO
2
r amp
o uTpuT
The CO
2
Ramp Output screen will be active if the unit is configured for CO
2 control. This screen displays the CO status of the control ramp.
2
set point, CO
2
level from the space, and the e nergy
r ecovery
w heel
s
TaTus
This screen provides overall status of the energy recovery wheel.
16 Microprocessor Controller for DOAS
®
®
Unit Status Overview d eFrosT r amp o uTpuT
This screen only appears if the unit has an energy recovery wheel and a frost control method was provided on the unit.
Upon sensing a high differential pressure across the energy wheel, the unit will go into defrost if the outside air temperature is below the defrost temperature set point. c ooling
r amp
1
This screen displays the active set point, supply discharge temperature, cooling enable/disable, cooling ramp being sent from the controller, and the overall capacity being demanded. h eaT p ump h eaTing r amp
The Heat Pump Heating Ramp status screen is active when the unit is configured as a heat pump. The screen displays the active set point, supply temperature, status of the heat pump heating control ramp, the current ramp percentage, and the current capacity of the operating compressors.
c ompressor
r equesT
The compressor request screen will be active if the unit is equipped with DX cooling. This screen displays overall status of individual compressor operation being sent from the unit controller. Example: Circuit A compressor enable (On) with modulating value of 26%.
e x v s TaTus
The ExV Status screen is active when the unit is equipped with an inverter scroll compressor and electronic expansion valve (ExV). The screen displays information from the EVD (electronic valve driver) including the number of steps
(stp) of the valve, the open percentage of the valve, the EVD control status, the suction superheat, the suction temperature, the suction pressure, and the saturated suction temperature. The second status screen also displays the capacity of the circuit the valve is installed on and the discharge refrigerant temperature for that circuit.
i nverTer
c ompressor
s
TaTus
The inverter compressor screen is active when an inverter scroll compressor is installed in the unit. This screen displays information about the operation of the inverter scroll starting with the requested capacity of the compressor compared to its actual operating capacity. The requested capacity and the actual could be different at startup and depending on where it is in the operating envelope.
The status of the compressor, current envelope zone and current refrigerant temperatures and pressures are also displayed.
c ondenser F an s TaTus
The pressure control status screen is active when a unit is equipped with active head pressure control, this is currently available only with inverter scroll compressors. This screen provides information regarding the outside fan ramp status, circuits affected by the ramp, the status of the fans, and the set point, offset and current saturated temperature.
Microprocessor Controller for DOAS 17
r eFrigeranT
c ircuiT
s
TaTus
The refrigerant circuit status screen is active when the unit is equipped with active head pressure control. This screen provides temperatures and pressures for suction, discharge, and liquid line sensors when installed. Superheat is also displayed when suction temperature and pressure sensors are installed.
h eaTing
r amp
This screen displays the active set point, supply air temperature, status of the heating control ramp, and heating ramp being sent from the controller.
d ehumidiFicaTion
This screen will display the overall dehumidification status and selected dehumidification control mode.
The following dehumidification modes are available when the space is in occupied mode:
• Cold coil set point plus offset (10ºF)
• Inside RH*
• Inside dew point*
• Outside dew point
• Inside RH or inside dew point*
• Inside RH or inside dew point or outside dew point
• Inside RH and inside dew point*
• Inside RH and inside dew point or outside dew point
*Available during unoccupied mode.
hgrh r amp
This screen will display the status of the hot gas reheat ramp. The screen includes the active set point, supply air discharge temperature, the ramp status, and hot gas reheat valve request being sent from the controller. s upply s pace s TaTic
This screen displays status points if the unit is configured for space static pressure control. Status points include controller output ramp, static pressure in the space, and the space static pressure set point. Similar status screen will appear for the exhaust fan if the unit is configured for exhaust fan space static control.
s upply
/r eTurn
d ucT
s
TaTic
This screen displays status points if the unit is configured for duct static pressure control. Status points include controller output ramp, static pressure in the duct, and the duct static pressure set point. Similar status screen will appear for the exhaust fan if the unit is configured for exhaust fan duct static control.
c ondiTions
The condition screens are active when both temperature and humidity sensors for the location are installed in the unit. The enthalpy and dew point are calculated based on the temperature and humidity readings. The unit altitude is used for the enthalpy calculation.
18 Microprocessor Controller for DOAS
®
Menu
The controller is equipped with several menus to help guide users with altering program parameters. The following menus can be accessed by pressing the button. To enter the desired menu, press the button.
Unit Enable
The Unit Enable menu allows the user to enable and disable the unit through the controller. Reference sequence of operation for additional unit starts/stop details.
The unit ships from the factory in a disabled state. To allow the unit to operate, the controller must receive a run command from digital input ID4. Jumper unit terminals R - G to allow the unit to operate.
Change to (Enabled/Disabled): Enables user to manually turn unit on/off via display. Unit terminal G must have 24 VAC power to enable the unit.
Control Variables
Control Variables
Temp Control
The Control Variables menu allows the user to view and adjust unit control parameters.
The Temperature Control menu allows the user to view and adjust temperature control conditions of the unit.
m eThod For
T emperaTure
c onTrol
Set Point Selections:
Supply Temp Control – The supply discharge set point is a constant value (e.g.
72°F). Reference Temperature Set point screen for set point adjustment.
Space Reset – The controller will reset the supply air temperature set point to maintain the space temperature set point (requires space temp sensor). Reference the Temperature Set point screen for space set point adjustment.
Return Reset – The controller will reset the supply air temperature set point to maintain the return air temperature set point (requires duct mounted return air temp sensor). Reference the Temperature Set point screen for return air set point adjustment.
OA Reset – The controller monitors the OA temperature and adjusts the desired supply temperature set point accordingly. For example, when the OA is below
55°F, the controller will change the supply set point to 70°F. If the OA is above
65°F, the controller will change the supply set point to 55°F. If the OA temperature is between 55°F and 65°F, the supply set point changes according to the OA reset function. A visual representation of the OA reset function is shown below.
Reference Outside Set points for min and max outside air limits.
Outdoor Air Reset Function
75°
70°
65°
60°
55°
50°
45°
50° 55° 60°
Outside Air Temperature (°F)
65° 70°
Microprocessor Controller for DOAS 19
®
Menu
T emperaTure
s eT
p oinT
This screen only appears if supply temp control, space reset, or return reset is selected as the reset control mode.
Set Point Selections:
Local – The space set point will be constant; set from screen (e.g. 72°F).
BMS – The BMS can directly control the space temperature set point (requires
BMS communication option).
T-Stat – The space set point will be adjustable from the space thermostat.
Reference Appendix: Room Thermostat Quick Start for additional information.
h eaT
c ool
d eadband
This screen only appears if space reset or return air reset is selected as the reset control mode. The heat cool deadband allows for separate cooling and heating set points when the reset control mode is set for space reset or return air reset. s upply s eT p oinTs
Cooling and heating supply set points screens only appear if outdoor reset, space reset, or return air reset is selected. These screens allow the user to set the min and max set point limits for cooling or heating operation. The controller will adjust the supply temperature set point between the set limits depending on mode of operation.
o uTside s eT p oinTs
This screen only appears if outside reset is selected as the reset control mode.
m ode s wiTch d isplay
This screen displays the delay time required before switching between heating and cooling mode. s TarTup d isplay
This screen displays the delay time after the fans have started and tempering begins
20 Microprocessor Controller for DOAS
®
®
Menu c ooling
l ockouT
This screen displays the cooling lockout temperature. Cooling will be disabled when outside air is below the cooling lockout temperature (55ºF).
h eaTing
l ockouT
This screen displays the heating lockout temperature. Heating will be disabled when outside air is above the lockout temperature (80ºF) .
s pace
s eT
p oinTs during
u noccupied
m ode
The controller will have separate screens for unoccupied cooling and heating set points.
Unoccupied Cooling Example: If set point = 80ºF, unoccupied cooling is enabled when space equals 80ºF and above. Unoccupied cooling is disabled when space temperature is below 75ºF.
Unoccupied Heating Example: If set point = 60ºF, unoccupied heating is enabled when space temperature equals 60ºF and below. Unoccupied heating is disabled when space temperature is above 65ºF.
w inTer
r amp
The winter ramp function prevents the supply temperature from dropping below set point under the following conditions:
• Outside air temperature is below the winter ramp enable set point; and
• Heating capacity is at 100%
One of the following is used to perform the winter ramp function:
• Supply fan speed; or
• Outside air damper position
Note: If the unit is a heat pump, the supply fan is always used. m odbus
s pace
T-s
TaT
The quantity of thermostats installed in the space that communicate the temperature, humidity, and set point to the controller. The controller averages the temperature and humidity readings when there is more than one installed. See
Appendix C for more information.
Microprocessor Controller for DOAS 21
Control Variables
Dehumidification
Menu
The Dehumidification menu allows the user to view and adjust dehumidification control parameters. d ehumidiFicaTion
m ode
- o ccupied
.
Possible Modes:
• Outside Air Temp is greater than cold coil set point plus offset (10ºF)
• Inside RH*
• Inside dew point*
• Outside dew point
• Inside RH or inside dew point*
• Inside RH or inside dew point or outside dew point
• Inside RH and inside dew point*
• Inside RH and inside dew point or outside dew point
*Available during unoccupied mode.
There must be a constant call for dehumidification for the duration of the enable delay for dehumidification mode to become enabled. The call remains active until conditions are satisfied and dehumidification mode has been active for the min active time. Reference Ctrl Variables/Advanced/Unit Config/Unit Configuration
Occupied Dehum Call for dehumidification method options. d ehumidiFicaTion m ode - u noccupied .
If the unit is unoccupied while there is a dehumidification call, the unit will start and dehumidify until the unoccupied dehumidification set points are satisfied.
The above dehumidification modes marked with an * indicate availability during unoccupied mode. The unoccupied dehumidification mode can be set differently than the occupied dehumidification mode. Reference Ctrl Variables/Advanced/
Unit Config/Unit Configuration Unoccupied Dehum Call for dehumidification method options.
d ehumidiFicaTion
h ysTeresis
This screen displays hysteresis for enabling dehumidification during occupied and unoccupied conditions.
%RH for indoor RH control and ºF for indoor dew point control. Example: If indoor RH set point = 50%, dehumidification is enabled when indoor RH equals 50% and above. Dehumidification is disabled when indoor RH is below 44%.
d ehumidiFicaTion
T imers
This screen allows adjustment for delay and min on time for dehumidification mode.
Times are in place to prevent short cycling between dehumidification and other control modes.
22 c old
c oil
s eT
p oinT
This screen displays the temperature set pints for the cooling coil.
This screen only appears if the unit is equipped with cooling. When in dehumidification mode, the cooling ramp maintains the cold coil set point by increasing or decreasing the amount of cooling provided from the cooling device installed. The calculated coil set point has a min and max set point that is based on the demand from the dehumidification ramp. When the demand is high, the temperature is low. If a constant temperature off the coil is desired during dehumidification, the min and max can be set to the same value. If a BMS is available, the set points can be adjusted over the BMS.
Microprocessor Controller for DOAS
®
® d ehumidiFicaTion
p rioriTy
The following priorities are used to determine what is more important in the unit: temperature over dehumidification or heating over dehumidification. Both priority selections determine when the unit is allowed to dehumidify.
1. Temperature over Dehumidification
Determines when the unit is allowed to dehumidify based on the space/return air temperatures.
a. Temperature - If temperature is set as the priority,box not checked, and the space or return air is over cooled, dehumidification is locked out until the space or return temperature is no longer overcooled.
b. Dehumidification - If the priority is dehumidification, box checked, and the space or return air is overcooled, the coil offset will be added to the coil leaving set point. (Default 0ºF offset).
c. Overcooled - If space or return reset is enabled, the target is considered over cooled when it is 4°F below set point for 5 minutes. It remains overcooled until the target is at set point and the over-cool logic has been active for a min of 5 minutes.
2. Heating over Dehumidification
Determines when the unit is allowed to dehumidify when heating is active.
a. Heating - If priority is set to heating, box in checked, the unit locks out dehumidification while heating is active.
b. Dehumidification - If priority is set to dehumidification, box is not checked, the unit is allowed to switch to dehumidification when heating is active.
c ompressor d ehumidiFicaTion F orce .
In dehumidification mode, the lead compressor will continue to run as long as the dehumidification mode sequence has been enabled in order to prevent compressor cycling and potential reevaporation of moisture. To disable this operation and allow the compressor to cycle in dehumidification mode, uncheck the applicable cooling ramps.
Microprocessor Controller for DOAS 23
Control Variables
Refrigeration
Control Variables
Refrigeration
Compressor Control
Control Variables
Refrigeration
Pressure Control
Control Variables
Refrigeration
Heat Pump Control
Menu
The Refrigeration menu allows the user to view and adjust compressor and condenser settings, if equipped. c ompressor c onTrol
Consult factory prior to adjusting parameters in the compressor control menu.
p ressure c onTrol
Consult factory prior to adjusting parameters in the pressure control menu.
c ompressor c onTrol
Allows the user to adjust heat pump heating control set points. a ir -s ource h eaT p ump a mbienT l ockouT
The screen allows the user to adjust the minimum ambient temperature the compressors can be utilized for heating. When the outside air temperature drops below this temperature, heating with the compressors will not be allowed. h eaT
p ump
d eFrosT
Consult factory prior to adjusting set points related to heat pump defrost operation.
Control Variables
Damper Control
The Damper Control menu’s allows the user to adjust damper control set points. Economizer set point adjust will also be found at this location if the unit is equipped with outside air and recirculation dampers.
F an
d amper
d elay
This screen allows adjustment for delay time between damper opening and fan operation.
This timer allows the damper to open before the fan start sequence begins. This prevents the fans from having to overcome higher static pressure when the damper(s) are opening.
o uTside
d amper
p osiTion
This screen only appears if equipped with a modulating OA and recirculating damper. The screen displays the min and max positions for the outside air damper. These set points reflect the percentage of the outside air damper being opened.
0% = Full recirculation air
100% = Full OA
Minimum Position – When in the occupied mode, the active set point will be equal to a local min OA set point, which may be constant or reset by fan speed if equipped with a modulating supply fan.
The OA damper set point can then be further adjusted between the min and max OA settings with sequences such as DCV CO
2
Economizer.
, Building Pressure and
24 Microprocessor Controller for DOAS
®
®
Menu
Maximum Position – Each sequence that can adjust the OA damper set point contains a max position to prevent excess OA. The active set point will be determined based on the greatest demand of the configured sequences. For example, if a unit is equipped with a DCV CO
2
and an economizer sequence, the OA damper set point will react to an economizer demand even if the CO
2 point is satisfied. Likewise, if economizer is not available but CO
2 point, the OA damper will open to satisfy the CO
2
set point.
set
is above set
Economizer – The active set point will be reset based on Economizer demand, between the min and max positions.
Set Point Selections:
Local – The min OA percentage is constant; set by the controller.
SF Reset – The min and max positions are reset by the supply fan speed.
BMS – The BMS can directly control the OA damper position between the min ad max percentages.
Building Pressure – Damper position is reset by a building pressure control loop.
DCV CO
2
– Damper position is reset by a demand-controlled ventilation control loop based on space CO
2
levels. The CO
2 max is the highest percentage that the
OA damper can modulate when solely based on CO
2
.
2 Position – Damper position is reset to “2-Pos/Max Vent:” set point when a contact closure is made. The 2-position damper operation can be configured to temporarily force the unit into occupied mode until the contact is open
(Max Ventilation Mode - enabled in Advanced menu).
e conomizer c onTrol v ariables .
The economizer screen appears when economizer function is enabled.
The outside air damper will modulate between the min and max position to maintain the supply temperature set point.
The user can select the economizer control method from the following options:
Outside Dry Bulb – Economizing is allowed when the outside dry bulb is less than the economizer temperature enable set point.
Outside Enthalpy - Economizing is allowed when outside enthalpy is less than the economizer enthalpy set point.
Comparative Dry Bulb - Economizing is allowed when outside temperature is less than the space or return temperature.
Comparative Enthalpy - Economizing is allowed when outside enthalpy is less than the space or return enthalpy.
Microprocessor Controller for DOAS 25
Menu e conomizer
s eTTings
There is a built-in hysteresis that disables economizer above the economizer set point.
(Example: If economizer uutside dry bulb = 65°F, economizer operation is disabled above 67°F).
e nergy
r educTion
o nly
c onTrol
.
If enabled, the OA damper and recirculation damper will not modulate during economizer. Instead, only the energy recovery wheel will be stopped to ensure no energy is transferred from the supply airstream and exhaust airstream.
Control Variables
Energy Recovery
The Energy Recovery menu allows the user to adjust energy recovery wheel sequence set points.
d eFrosT r amp
This screen displays the temperature at which the unit will enable frost control mode if necessary (factory default = 5ºF) This screen only appears if the unit has an energy recovery wheel and a frost control method was provided with the unit.
Upon sensing a high differential pressure across the energy wheel, the unit will enter defrost mode if the outside air temperature is below this temperature setting. Max active time and min off time will be available if the frost control method was provided as timed exhaust or cycle wheel.
e nergy
r ecovery
w heel
j og
F uncTion
This screen display the energy recovery wheel jog function. This screen only appears if the unit has an energy recovery wheel and stop wheel economizer method for control.
Momentarily enables the wheel in order to expose a new section to the airstream.
26 Microprocessor Controller for DOAS
®
Control Variables
Fan Control
Supply Fan Control
Menu
The Supply Fan Control menu allows the user to adjust exhaust control set points s upply
F an
d elay
The supply fan delay will begin once the damper sequence is complete. This delay can be used to offset starting times between the supply fan and exhaust fan.
s upply
F an
s peed
This screen displays min and max supply fan speed percentages.
The speed set point is the proportional percentage of the analog output from the controller to the
VFD.
50% Speed = Min speed
100% Speed = Max speed
Set Point Selections:
Constant Volume – The fan speed will be constant; set from screen (e.g. 100%).
BMS – The BMS can directly control the fan speed (requires BMS communication option).
Duct Pressure – Fan speed is determined by duct pressure control loop.
Space Pressure – Fan speed is determined by building pressure control loop.
CO
2
– Fan speed is determined by CO
2
control loop.
Single Zone VAV - The supply fan is modulated in addition to the supply air temperature to satisfy the space temperature set point.
2-Speed (High Speed Set Point) - Supply fan speed is reset to max speed when a contact closure is made. (Max Ventilation Mode).
s oFT s huTdown e nable c ondiTions
During a soft shutdown the following will occur:
• Tempering outputs immediately revert back to their off value; while
• Dampers remain open and fans continue to run; until
- The supply air temperature falls below the soft shutdown enable set point minus 5ºF; or
- The soft shutdown delay timer has expired.
Microprocessor Controller for DOAS 27
®
Control Variables
Fan Control
Exhaust Fan Control
Menu
The Exhaust Fan Control menu allows the user to adjust exhaust control set points.
e xhausT F an d elay and e nable
This screen displays min and max exhaust fan speed percentages.
This screen displays the exhaust fan delay and enable based on OA damper position. The exhaust fan delay will begin once the damper sequence is complete. This delay can be used to offset starting times between the supply fan and exhaust fan. This screen also provides the ability to enable the exhaust fan on a set OA damper position if the unit is equipped with a modulating OA damper. e xhausT
F an
s peed
p ercenTages
The speed set point is the proportional percentage of the analog output from the controller to the VFD.
25% Speed = Min speed
100% Speed = Max speed
Set Point Selections:
Constant Volume – The fan speed will be constant; set from screen (e.g. 100%).
BMS – The BMS can directly control the fan speed (requires BMS communication option).
Space Pressure – Fan speed is determined by building pressure control loop.
Supply Fan Tracking with Offset – The exhaust fan will track the supply fan, between a min and max position. An offset can be added to achieve the proper balance.
Outside Air Damper Tracking – The exhaust fan will proportionally track the OA damper, between a min and max position.
Return Duct Static Pressure – Fan speed is determined by duct pressure control loop.
28 Microprocessor Controller for DOAS
®
Control Variables
Occupancy
Menu
The Occupancy menu allows the user to adjust occupancy control parameters which includes occupancy control mode and schedule.
o ccupancy
c onTrol
This screen displays the current mode of operation for occupancy control. Status of the other mode option can also be found on this screen.
This screen allows the user to select the source of determining occupancy. The factory default is BMS control.
BMS: BMS control (Reference Points List). BMS can be overridden with ID6.
Digital Input: Typically used with a remote time clock, motion sensor or switch.
Always Occ: Controller will always remain in occupancy mode.
Always Unocc: Controller will always remain in unoccupancy mode.
Schedule: Allows the user to set an occupancy schedule for each individual day of the week. o ccupancy
s chedule
This screen allows the user to adjust the schedule.
Requires the user to enter a start time, stop time and the applicable days of the schedule.
u noccupied s TarT e nable m odes .
This screen only appears if unit is provided with unoccupied recirculation.
This screen allows the user to enable/disable modes of operation when in unoccupied recirculation control.
o ccupancy
T imed
o verride
Screen allows the user to override occupancy for a set duration.
Microprocessor Controller for DOAS 29
®
Control Variables
Advanced
Menu
The Advanced menu allows the user to access several submenus regarding controller information, controller overrides, network settings, I/O configuration, and unit configuration. Submenu options are read only and will require the user to input proper login criteria. The service password (9998) is required to change service access menus. Consult factory for factory level access.
Control Variables
Advanced
Manual Overrides
The Manual Overrides menus are for start-up, commissioning, and troubleshooting. ig F urnace
c ommissioning
m enu
This screen only appears if an indirect gas furnace was provided with the unit.
Entering the furnace commissioning menu will step the user through the furnace start-up.
m anual o verride m ode
The Manual Overrides menu is for start-up, commissioning, and troubleshooting.
This menu allows the user to override the control loops and specific inputs and outputs.
To access the Manual Overrides submenus, enter the service password (9998) .
Manual overrides must be enabled at this screen to allow the user to override control loops. Override options must be changed from Auto to Manual for manual control.
o verride The
u niT
o n or
o
FF
When manual override is set to enable, use the arrow buttons to turn the unit on or off. o verride o ccupancy c onTrol
When manual override is set to enable, use the arrow buttons to change occupancy control. o verride The s upply F an vFd s peed
The speed is the proportional percentage of the analog output from the controller to the VFD.
0% Speed = Min speed (determined by VFD)
100% Speed = Max speed (determined by VFD)
(Reference unit Installation and Operation Manual for VFD programming).
30 Microprocessor Controller for DOAS
®
®
Menu o verride e xhausT F an vFd s peed
This screen only appears if the unit is equipped with a exhaust fan VFD controlled by the microprocessor.
The speed is the proportional percentage of the analog output from the controller to the VFD.
0% Speed = Min speed (determined by VFD)
100% Speed = Max speed (determined by VFD)
(Reference unit Installation and Operation Manual for VFD programming).
o verride The p osiTion oF The o uTside a ir d amper
This screen only appears if the unit is equipped with a modulating OA and recirculation damper. The recirculation damper position will be the inverse of the
OA damper position shown.
0% = Outside air damper closed
100% = Outside air damper fully open o verride The
c ompressor
This screen only appears if the unit is equipped with DX cooling. When manual override is set to enable, use the arrow buttons to turn individual compressor requests on or off. o verride The m odulaTing c ompressor c onTrol l oop
When manual override is set to enable, use the arrow buttons to change the compressor modulation value. o verride
c ooling
When the cooling control is in the manual mode, use the arrow buttons to vary the cooling output.
Chilled Water : The cooling percent is directly proportional to the 0 - 10 VDC output signal.
0% Cooling = 0 VDC
100% Cooling = 10 VDC
Packaged Cooling : The cooling percent displays compressor engagement as a percent. The compressors are subject to the min on/off times and heating/cooling lockouts.
o verride The
e lecTric
h eaTer
This screen only appears if the unit is equipped with electric post heat. Electric heater percentage is directly proportional to the 0 – 10 VDC output signal.
Microprocessor Controller for DOAS 31
Menu o verride
h eaTing
When the heating control is in the manual mode, use the arrow buttons to vary the heating output.
o verride
h eaT
p ump
h eaTing
This screen will be available when the unit is configured as a heat pump. When in manual mode, change the demand to control the position of the reversing valve and the amount of compressor request. The compressors are subject to the min on/off times and heating lockouts.
o verride The
e conomizer
c onTrol
When the heating control is in the manual mode, use the arrow buttons to vary the heating output.
o verride The
h oT
g as
r eheaT
This screen only appears if modulating hot gas reheat option was provided with the unit. When the hot gas reheat loop control is in the manual mode, use the arrow buttons to vary the reheat output.
o verride The
e nergy
r ecovery
d eFrosT
This screen only appears if modulating wheel frost control is equipped. When the defrost control ramp is in manual mode, use the arrow buttons to vary the defrost output.
0% = Maximum Wheel Speed
100% = Minimum Wheel Speed o verride
p ressure
c onTrol
F ans
This screen will be available when active head pressure control is installed in the unit. When in manual mode, with the compressors off, the modulating fan speed can be altered by using the arrows to change the output. The fixed stage fan can be enabled by changing the output to On.
Control Variables
Advanced
Advanced Setpoints
The Advanced Setpoints Menus allows the user to view and modify network settings. The service password (9998) is required to make changes. o ccupied d ehumidiFicaTion c all .
Reference control variables for possible Occupied dehumidification call methods.
u noccupied
d ehumidiFicaTion
c all
.
Reference control variables for possible unoccupied dehumidification call methods.
32 Microprocessor Controller for DOAS
®
Menu v iew and
c hange The
u noccupied
u niT
o peraTion
.
Possible unoccupied unit operation methods include:
• Unit Off
• Night Setback Cycle
• Recirculation with Unoccupied Set Points
• Normal Operation with Unoccupied Set Points e nable m orning w arm u p and c ool d own .
The user can enable morning warm up, morning cool down, and set the duration for the sequence.
Control Variables
Advanced
Network Settings
The Network Settings Menus allows the user to view and modify network settings. The service password (9998) is required to make changes. c
.
p co b oard
a ddress
This screen will appear with or without a network protocol provided with the unit.
This screen allows the user to configure the IP setting for BMS and/or when the Web User Interface will be utilized. The controller may have a DHCP serverassigned address or a manually-assigned static IP address. Factory settings are shown in the screen to the left.
c onTroller bac neT ip c onFig
This screen will appear if the unit is set for BACnet IP and allows the user to set the device and port settings.
m odbus
Tcp s lave
.
This screen will appear if the unit is set for Modbus TCP and allows the user to set device ID number. bac neT msTp p arameTers
This screen only appears if the selected BMS protocol is set to BACnet MSTP.
Factory settings are shown in the screen to the left.
To change BACnet MSTP parameters:
1. Go to Network Settings menu and view BACnet MSTP Config screen.
2. Move cursor to desired parameter by pressing the enter button. Press up and down arrows to adjust the parameter. Press enter to accept adjusted value.
3. Once desired parameters have been entered, enable the ‘Save Settings’ option and press the enter button.
4. Reboot the controller by cycling power to the unit. Allow several minutes for the controller to initialize.
Microprocessor Controller for DOAS 33
®
Menu m odbus
rTu p arameTers
This screen only appears if the selected BMS protocol is set to Modbus. Factory settings are shown in the screen to the left.
To change Modbus RTU parameters:
1. Go to Network Settings menu and view Modbus RTU Config screen.
2. Move cursor to desired parameter by pressing the enter button. Press up and down arrows to adjust the parameter. Press enter to accept adjusted value.
3. Once desired parameters have been entered, enable the ‘Save Settings’ option and press the enter button.
4. Reboot the controller by cycling power to the unit. Allow several minutes for the controller to initialize.
bms w aTchdog
The BMS watchdog function verifies BMS connectivity. The watchdog is required for the BMS to take the place of a hardwired sensor. The BMS toggles the watchdog variable from true to false within the timeout delay. If the timer expires, the controller falls back to hardwired sensors until the BMS connection can be established. At this time, a BMS watchdog alarm activates.
The following variables may be used by the BMS in place of hardwired sensors:
• Outside_RH_from_BMS
• Outside_Temp_from_BMS
• Return_RH_from_BMS
• Return_Temp_from_BMS
• Space_1_CO2_from_BMS
• Return_CO2_from_BMS
• Space_RH_from_BMS
• Space_Static_from_BMS
• Space_Temp_from_BMS s ensor
s ource
The sensor source can be changed to source by BMS through the controller or by a dedicated BMS point. Reference Points List above and in the Appendix for more detailed point information. Screen to the left is an example of the sensor source type. Source can be set for local or BMS at this screen.
Control Variables
Advanced
Backup/Restore
The Backup/Restore Menus allows the user to create a backup file of set points and configuration variables on a USB drive or in the controller’s internal memory.
Connecting to USB Drives
The controller has built-in USB ports for connecting to USB drives. The USB drives can be used for backing up all settings and reported conditions such as alarm history and current values. This creates a file named User_Backup.txt.
USB Type A
USB Type B
34 Microprocessor Controller for DOAS
®
®
Menu c reaTing a
b ackup
F ile
Important:
• At first startup or commissioning, or prior to communicating with Technical
Support about performance issues, we recommend creating a backup file for each controller.
• Name each file with the unit sales order–line number found on the silver nameplate attached to the electrical access door.
• Also consider creating a backup file whenever significant program changes are made.
To create a system backup file using the handheld or virtual keypad/display buttons:
1. Go to the Main Menu/Ctrl Variables/Advanced/Login screen. Press the Enter and Up or Down arrow buttons to enter the service password, which is 9998.
2. Go to the Main Menu/Ctrl Variables/Advanced/Backup/Restore screen.
3. Press the Up or Down arrow buttons to navigate to the Backup Settings screen.
4. Press the Enter and Up or Down arrow buttons to select the backup location
(internal memory or USB). If creating a backup to a USB drive, insert a USB drive into the main controller.
5. Press Enter to highlight and then the Up or Down arrow buttons to fill the Save checkbox. This action creates the backup file. r esToring From a b ackup F ile
From USB
1. Place the restore file in the root directory of a USB drive. (Do not place the file within a folder on the USB drive.) The file must be named: User_Backup.txt
2. Insert the USB drive into the controller’s USB port.
3. Go to the Main Menu/Unit Enable screen. Press the Enter and Up or Down arrow buttons to disable the unit.
4. Go to the Main Menu/Ctrl Variables/Advanced/Login screen. Press the Enter and Up or Down arrow buttons to enter the service password (9998).
5. Go to the Main Menu/Ctrl Variables/Advanced/Backup/Restore screen.
6. Press the Up or Down arrow buttons to navigate to the USB Restore screen.
7. Press Enter to highlight and then the Up or Down arrow buttons to fill the
Restore checkbox. This action restores the backup file. If there is an error during the process, the specific error is displayed on this screen.
8. Cycle power to the controller.
From internal memory
1. Go to the Main Menu/Unit Enable screen. Press the Enter and Up or Down arrow buttons to disable the unit.
2. Go to the Main Menu/Ctrl Variables/Advanced/Login screen. Press the Enter and Up or Down arrow buttons to enter the service password, which is 9998.
3. Go to the Main Menu/Ctrl Variables/Advanced/Backup/Restore screen.
4. Press the Up or Down arrow buttons to navigate to the Internal Restore screen. This screen is only available when a backup file exists in internal memory.
5. Press Enter to highlight and then the Up or Down arrow buttons to fill the
Restore checkbox. This action restores the backup file. If there is an error during the process, the specific error is displayed on this screen.
6. Cycle power to the controller.
Microprocessor Controller for DOAS 35
Control Variables
Advanced
I/O Configuration
Control Variables
Advanced
Unit Config
Service Config
Menu
The IO Configuration Menu allows the user to view and modify controller input and output points.
i/o c onFiguraTion
This screen is read only and will require the factory password to make changes.
Screen to the left is an example of an analog input configuration screen. Similar screens appear for remaining I/O when selected.
To monitor individual I/O points:
1. Press the enter button to highlight the I/O type.
2. Press the up and down arrows to change the IO type.
3. Press the enter button to highlight the controller channel.
4. Press the up and down arrows to change the channel.
i/o c onFiguraTion
o pTions
Changes to the IO configuration requires the factory login password. Consult factory for IO configuration changes.
ADJUSTMENT OF I/O CONFIGURATION MUST ONLY BE DONE UNDER
FACTORY GUIDANCE! IMPROPER ADJUSTMENT MAY RESULT IN SYSTEM
DAMAGE!
The Unit Configuration menus allows the user to view unit configuration provided from factory. Configuration menus listed below can be altered with the service password. Consult factory for unit configuration changes! s upply F an c onTrol T ype
Reference control variables for possible supply fan control methods.
e xhausT F an c onTrol T ype
Reference control variables for possible exhaust fan control methods.
36 Microprocessor Controller for DOAS
®
Alarms
Menu
The Alarms menu allows the user to view active alarms, reset active alarm (if possible), and alarm history.
a cTive
a larms
If an alarm occurs, the button will glow red on the controller and the remote display (if installed).
To view alarm, press the Alarm button once. This will display the most recent alarm. If the alarm cannot be cleared, the cause of the alarm has not been fixed.
Press the up and down buttons to view any additional occurring alarms.
r eseT
a cTive
a larms
This screen allows the user to clear active alarms.
a larm
e venT
h isTory
This screen allows the user view recent alarms. To view all saved alarms, press the “down” button to enter the data logger. c lear a larm l og
This screen allows the user to clear all alarms in alarm log history.
IG no flame 3 try AL
IG Furnace Alarm (AL) Descriptions
Indicates a furnace failure to light or properly sense flame after
3 trials.
IG combustion fan high pressure switch failure
Indicates a call for high speed combustion fan but high pressure switch did not close.
IG furnace ignition control Indicates an alarm from the ignition controller.
Pressure switch closed with combustion fan off
Combustion fan not proved
IG furnace max retry
Indicates low pressure switch was closed with no call for combustion fan.
Indicates a call for low speed combustion fan but low pressure switch did not close.
Indicates that the max number of retries was reached.
IG High Temp AL
IG offline
Indicates that power was lost from the High Temp Limit Sensor.
Check for high limit trip.
Indicates communication with furnace control has failed.
IG Lg Man No Flame AL No flame after 3 trials for ignition on the large manifold.
Alarm only
Alarm only
Alarm only
Alarm only
Alarm only
Alarm and Furnace lockout
Alarm only
Alarm only
Alarm only
Microprocessor Controller for DOAS 37
®
Appendix A: Remote Display (pGD1)
The pGD1 is an optional remote display for use with manufacturer’s microprocessor controllers. The remote display allows for remote monitoring and adjustment of parameters of the unit mounted controller. The remote display allows identical access to menus and screens as the unit mounted controller display.
Specifications
Carel Model
Power Supply
Max distance from unit controller
Required Cable
Operating Conditions
Display Type
PGD1000W00
Power supplied from unit controller through RJ25 cable
150 feet
6P6C RJ25/RJ12 Cable (straight)
-4°F to 140°F, 90%RH
(non-condensing)
Backlit LED with lighted buttons
Installation
The remote display connects to the unit mounted controller through a six-wire RJ25 or RJ12 telephone cable (straight).
When ordered from the factory, a 10 ft. cable is provided with the remote display. The display and cable can be used to assist with start-up and maintenance.
Connecting Cable
If mounted remotely, the factory cable can either be extended or replaced with a longer cable to obtain the necessary distance. The resulting cable connections should be a “straight through cable,” where pins on one end correspond identically to the pins on the opposite end. If making your own cable, use the same pin-out for each end.
1 2 3 4 5 6 1 2 3 4 5 6
NTC Temperature Sensor Chart
80
70
60
50
40
120
110
100
90
30
20
10
0
4 6 8 10 12 14 16 18 20 22 24 26 28
Resistance (k Ω )
38 Microprocessor Controller for DOAS
®
Appendix B: I/O Expansion Board (c.pCOe) Quick Start
The expansion board is an I/O module than can be used to monitor additional statuses or provide commands from large board controller. It allows the user to view and control:
• 6 Universal Inputs (Digital Input*,
NTC, 0/1VDC, 0/10VDC, 0/20mA,
4/20mA, 0/5VDC)
*Only dry to ground contacts can be utilized for digital inputs.
Applying voltage will result in damage to the I/O expansion board.
• 4 Analog Outputs (VDC)
• 6 Digital Outputs
The inputs and outputs can be monitored and controlled by the Building
Management System. Reference Points
List for detailed point information.
24 VAC
Power
Universal
Inputs
Analog
Outputs
Digital
Outputs
Setup
In order for the controller to communicate with the c.pCOe, several parameters must be adjusted. If you have a c.pCOe installed from the factory, the controller is already set up for communication with the main controller.
The factory password is required for expansion board and I/O configuration updates. Consult factory for I/O configuration changes.
Enabling the c.pCOe in the Main Controller.
- To enable the c.pCOe expansion
I/O module, go to Ctrl Variables/Advanced/Unit Config. User will have to enter the Factory Password to make any edits at this point. Consult factory for factory password and configuring the expansion board. The expansion board must be enabled to configure spare I/O points. Once enabled, the user must reboot the controller. See screens to the left for expansion board enable points.
Configuring the I/O Type - In order to edit and configure the I/O configuration of the unit, go to Ctrl Variables/Advanced/I/O Configuration. The user must enable the Editable option for configuring I/O points. If configuring a new I/O point, ‘Scroll by All Configured’ must be deselected to view all I/O options.
Change or Update the I/O Point - Once the editable option is selected, the user must scroll to the I/O Configuration Menu. At this menu the desired I/O type can be selected. Once selected the user can configure the desired channel at the expansion board. The channel will have an ‘E’ designation for expansion board. Aux In Customer 1–6, Aux Analog Out 1-4, and Aux Digital Out 1-6 will be allocated for the I/O expansion board. See example to the left.
Viewing c.PCOe Auxiliary Values – Once the expansion board I/O is configured, the user can view and/or change the I/O type by navigating to Ctrl Variables/Aux
I/O Config.
Microprocessor Controller for DOAS 39
®
Appendix C: Space Thermostat Quick Start
The space thermostat gives users the ability to view the space temperature and relative humidity (optional) and control the active space set points from the adjustable display. The space thermostat also has the ability to send the unit into temporary occupied mode. It is also provides the functionality to average up to 4 temperature readings through the microprocessor.
The space thermostat is shipped loose with installation by others and is a
Modbus connected device.
Room thermostat functions:
• Temporary occupancy override control
• Temperature and relative humidity monitoring
• Temperature and relative humidity set point adjustability
• Status icon on LCD display with push buttons
• Optional temperature monitoring up to 4 sensors
Display
If more than one space thermostat is provided for averaging, only one space thermostat will be provided with a display and push buttons for adjustment.
Adjusting SET POINT - The default display will show the current temperature value for the room. Use the scroll button to index through additional sensor parameters. Parameters with the "SET POINT" icon displayed above the temperature display are adjustable. Use the Up/Down buttons to adjust the set point, and use the scroll button to view the next parameter or return to the normal display mode.
Up/Down Button Function - The Up/Down buttons are used to adjust editable parameters including the temperature and humidity set point.
Override Button Function - The display shows a person in the lower left corner of the display at all times. If the person is solid, the unit is operating in occupied mode. If it is an outline of the person, the unit is in unoccupied mode. Pushing the Override button when the unit is in unoccupied mode will allow a temporary override sequence to
Occupied mode for a period of 1 to 3 hours (adjustable at the unit microprocessor).
Initial Setup and Communication Configuration
The space thermostat is a Modbus connected device There can be up to three additional Modbus temperature sensors added for space temperature averaging. The sensors must all be connected in a daisy chain configuration.
The microprocessor controller will be pre-configured for one space thermostat. If space temperature averaging is desired, additional field setup will be required both in the controller and on the Modbus space sensors:
• Each space sensor must have the DIP switches adjusted on the back of the sensor to the corresponding switches. Reference Room Thermostat Modbus Address chart on the following page for DIP switches settings.
• Once the address is set and the wires are connected the “Status” LED should be a steady green and the “Network” LED should be a quick blinking amber/green color.
• In the Controller, enter the Ctrl Variables Menu/Temperature and scroll down in the Temperature Menu to select Space Thermostat. Choose the number of space sensor being used (1-4).
40 Microprocessor Controller for DOAS
®
Appendix C: Space Thermostat Quick Start
Status LED
Green indicates that the unit is operating properly.
Red indicates that there is a problem with the unit.
Terminal
GND
Net B
Net A
Power
Unit
Controller
Description
Power Supply Ground (common to the controller)
RS485 network connection (Data - )
RS485 network connection (Data +)
Power supply hot
TAP-Stat
+Vtermo
GND
POWER
GND
-
Tx/Rx
+
NET B
NET A
Network LED
Flashing Red Slowly indicates that there has been no communications for 60 seconds.
Flashing Green Slowly indicates that there have been normal communications within the last 60 seconds.
Flashing Green Slowly with Quick Red Flashes; the quick red flashes indicate active communications.
Address in Microprocessor
Dip Switch Set on Stat
Space Thermostat Modbus Address
T-Stat 1 (Display) T-Stat 2
10
Sw 2 + Sw 8
11
Sw 1 + Sw 2 + Sw 8
T-Stat 3
12
Sw 4 + Sw 8
T-Stat 4
13
Sw 1 + Sw 4
Baud Rate Setting
In order for the space thermostat to communicate with the microprocessor, the correct baud rate must be set in the space thermostat. To set the baud rate:
• The “PROG” DIP switch on the back of the space thermostat must be flipped to the right side.
• Use the Set Point Down button to display P11 on the space thermostat.
• Push the Scroll button and use the Set Point Up/Down buttons to adjust the baud rate to 192.
• Once 192 is displayed, push the Scroll button again to save the setting. Once the setting is saved, P11 should appear on the display.
• Flip the “PROG” DIP switch on the back of the space thermostat back to the left. The space thermostat should communicate and be set back to normal mode.
Occupancy Override Time Adjustment
If the occupancy override time needs to be adjusted:
• If the occupancy override is enabled from the space thermostat or the unit microprocessor, it will override for the period of time set on this menu screen.
• To adjust the temperature override time, enter the following menu options at the controller, Ctrl Variables/Occupancy. Scroll down at the Occupancy Menu and select
Occ Timed Override. This menu will allow the user to enable occupancy override from the controller and set override duration.
Microprocessor Controller for DOAS 41
®
Appendix D: GreenTrol ® Airflow Monitoring Quick Start
The GreenTrol ® airflow monitoring station measures airflow using advanced thermal dispersion technology.
An integral LCD display provides a local indication of airflow measurement and device configuration. The airflow monitor also features Modbus communication allowing the main unit microprocessor to monitor the airflow as well. The GreenTrol also accepts up to two airflow probes for averaging.
GreenTrol Airflow Monitor functions:
• LCD readout of measured airflow
• Dual airflow probe averaging
• Modbus connectivity
Display and Navigation
The LCD screen will by default show the current airflow that is being measured. To enter the menu to set up the monitoring station the user must remove the front cover of the GreenTrol to uncover the navigation buttons. Press and hold the UP and DOWN buttons at the same time for 3 seconds to enter the menu.
Enter Button Function - The ENTER button allows the user to go into the selected menu or function, as well as save the selected value.
Up/Down Button Function - The Up/Down buttons are used to navigate the menu and to change values in the menu.
Esc Button Function - The ESC button allows the user to exit the current menu or function.
42 Microprocessor Controller for DOAS
®
VARIABLE DESCRIPTION
Circuit_A_Discharge_
Temp_Analog_Input
Circuit_A_Suction_
Temp_Analog_Input
Cold_Coil_1_Temp_
Analog_Input
Circuit A Discharge
Temperature
Circuit A Suction
Temperature
Cold Coil 1 Temperature
CL_Coil_Spt_Temp
CL_Supply_Spt_Temp
Controls Lite Cooling Coil
Set Point Temperature value
Controls Lite Supply Set
Point Temperature value
Outside_Air_Temp_
Analog_Input
Space_Temp_Analog_
Input
Supply_Temp_Analog_
Input
Outside_RH_Analog_
Input
Space_RH_Analog_
Input
Space_Static_
Pressure_Analog_Input
Outside Air Temperature
Space Temperature
Supply Temperature
Outside % Relative
Humidity
Space % Relative Humidity
Space Static Pressure
Supply_Duct_Static_
Pressure_Analog_Input Supply Duct Static Pressure
Space_CO2_1_
Analog_Input
Space 1 CO2 ppm
Circuit_A_Discharge_
Pressure_Analog_Input
Circuit A Discharge
Pressure
Circuit_A_Suction_
Pressure_Analog_Input Circuit A Suction Pressure
Circuit_B_Discharge_
Pressure_Analog_Input
Circuit B Discharge
Pressure
Aux_In_Customer_1
Aux_In_Customer_2
Aux_In_Customer_3
Aux_In_Customer_4
Aux_In_Customer_5
Aux_In_Customer_6
Customer defined auxiliary input
Customer defined auxiliary input
Customer defined auxiliary input
Customer defined auxiliary input
Customer defined auxiliary input
Customer defined auxiliary input
ACTIVE
TEXT
Appendix E: Points List
INACTIVE
TEXT
OBJECT
INSTANCE
Analog Inputs - Read Only
BACNET
OBJECT
TYPE
ACCESS
1
3
25
AI
AI
AI
ReadCOV_
NoWrite
ReadCOV_
NoWrite
ReadCOV_
NoWrite
31 AI
ReadCOV_
NoWrite
32
37
44
45
86
89
94
95
116
119
120
121
640
642
644
646
648
650
AI
AI
AI
AI
AI
AI
AI
AI
AI
AI
AI
AI
AI
AI
AI
AI
AI
AI
ReadCOV_
NoWrite
ReadCOV_
NoWrite
ReadCOV_
NoWrite
ReadCOV_
NoWrite
ReadCOV_
NoWrite
ReadCOV_
NoWrite
ReadCOV_
NoWrite
ReadCOV_
NoWrite
ReadCOV_
NoWrite
ReadCOV_
NoWrite
ReadCOV_
NoWrite
ReadCOV_
NoWrite
ReadCOV_
NoWrite
ReadCOV_
NoWrite
ReadCOV_
NoWrite
ReadCOV_
NoWrite
ReadCOV_
NoWrite
ReadCOV_
NoWrite
HYST INDEX
MODBUS
REGISTER
TYPE
SIZE
Input
Input
Input
Input
Input
Input
Input
Input
Input
Input
Input
Input
Input
Input
Input
Input
Input
Input
Input
Input
Input
Input
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
30195
30199
30243
30255
30639
30641
30643
30645
30647
30649
30349
30355
30365
30367
30401
30407
30409
30411
30257
30267
30281
30283
0.1
0.1
0.1
0.1
0.1
0.1
0.1
0.1
0.1
0.1
0.01
10
0.1
0.1
0.1
0.01
0.1
1
0.1
0.1
0.1
0.1
Microprocessor Controller for DOAS 43
®
VARIABLE DESCRIPTION
Temperature_Set Point
Temperature_Heat_
Cool_Deadband
Cooling_Coil_Set
Point_Min
Dehumidification_Set
Point
Outside_Dewpoint_Set
Point
Indoor_Dewpoint_Set
Point
Unocc_Indoor_
Dewpoint_Set Point
Unoccupied_Cooling_
Set Point
Unoccupied_
Dehumidification_Set
Point
Unoccupied_Heating_
Set Point
Economizer_Temp_
Enable_Set Point
Economizer_Enthalpy_
Enable_Set Point
Outside_RH_from_
BMS
Outside_Temp_from_
BMS
Return_RH_from_BMS
Return_Temp_from_
BMS
Space_1_CO2_from_
BMS
Space_RH_from_BMS
Space_Static_from_
BMS
Space_Temp_from_
BMS
Cooling_Lockout_Set
Point
Heating_Lockout_Set
Point
Space_Static_
Pressure_Set Point
Main Temperature Set point. Supply, Space, or
Return target temperature
Heat/Cool Spt Deadband when Room or Return control is active. Clg Spt =
Deadband /2 + Temp Spt.
Htg Spt = Deadband /2 -
Temp Spt.
Cooling Coil Leaving Air
Set Point
Dehumidification Set Point.
%RH for Space or Return control.
Outside Dewpoint
Dehumidification Trigger
Set Point
Indoor Dewpoint
Dehumidification Trigger
Set Point
Unoccupied Indoor
Dewpoint Dehumidification
Trigger Set Point
Unoccupied Cooling Set
Point
Unoccupied
Dehumidification %RH Set
Point
Unoccupied Heating Set
Point
Economizer Ambient Temp
Enable Set Point. Allow
Econ when OAT<Spt
Economizer Enthalpy
Enable Set Point.
Allow Econ when OA
Enthalpy<Spt
Outside RH from BMS. Used when source selection is set to BMS.
Outside Temp from BMS.
Used when source selection is set to BMS.
Return RH from BMS. Used when source selection is set to BMS.
Return Temp from BMS.
Used when source selection is set to BMS.
Space 1 CO2 from BMS.
Used when source selection is set to BMS.
Space RH from BMS. Used when source selection is set to BMS.
Space Static from BMS.
Used when source selection is set to BMS.
Space Temp from BMS.
Used when source selection is set to BMS.
Cooling Ambient Lockout
Set Point
Heating Ambient Lockout
Set Point
Space Static Pressure Set
Point
Appendix E: Points List
ACTIVE
TEXT
INACTIVE
TEXT
OBJECT
INSTANCE
BACNET
OBJECT
TYPE
Analog Values - Read/Write - Commandable
ACCESS
1 AV
ReadCOV_
Commandable
2
3
5
6
7
9
10
11
12
16
17
21
22
23
24
25
28
29
30
31
32
37
AV
AV
AV
AV
AV
AV
AV
AV
AV
AV
AV
AV
AV
AV
AV
AV
AV
AV
AV
AV
AV
AV
ReadCOV_
Commandable
ReadCOV_
Commandable
ReadCOV_
Commandable
ReadCOV_
Commandable
ReadCOV_
Commandable
ReadCOV_
Commandable
ReadCOV_
Commandable
ReadCOV_
Commandable
ReadCOV_
Commandable
ReadCOV_
Commandable
ReadCOV_
Commandable
ReadCOV_
Commandable
ReadCOV_
Commandable
ReadCOV_
Commandable
ReadCOV_
Commandable
ReadCOV_
Commandable
ReadCOV_
Commandable
ReadCOV_
Commandable
ReadCOV_
Commandable
ReadCOV_
Commandable
ReadCOV_
Commandable
ReadCOV_
Commandable
HYST
0
0
0
0
0
0
0
0
0
0
0
0
0.1
0.1
0.1
0.1
0.1
0.1
0.1
0.1
0.1
0.1
0.1
INDEX
MODBUS
REGISTER
TYPE
SIZE
40001
40003
40005
40009
40011
40013
40017
40019
40021
40023
40031
40033
40041
40043
40045
40047
40049
40055
40057
40059
40061
40063
40073
Holding
Holding
Holding
Holding
Holding
Holding
Holding
Holding
Holding
Holding
Holding
Holding
Holding
Holding
Holding
Holding
Holding
Holding
Holding
Holding
Holding
Holding
Holding
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
44 Microprocessor Controller for DOAS
®
VARIABLE DESCRIPTION
Supply_Duct_Static_
Pressure_Set Point
Space_CO2_Set Point
Supply Duct Static Pressure
Set Point
Space CO2 Set Point
SF_Control_Signal_
BMS
EF_Control_Signal_
BMS
OAD_Control_Signal_
BMS
Outside_Air_Damper_
Minimum_Set Point
Aux_BMS_Analog_
Output_1
Aux_BMS_Analog_
Output_2
Aux_BMS_Analog_
Output_3
Aux_BMS_Analog_
Output_4
Cooling_Coil_Setpoint_
Max
BMS to control signal for supply fan speed
BMS to control signal for exhaust fan speed
Allows the BMS to control
OAD position. True = BMS.
False = Local.
Outside Air Damper
Minimum Set Point
BMS Commanded auxilary analog output
BMS Commanded auxilary analog output
BMS Commanded auxilary analog output
BMS Commanded auxilary analog output
Maximum Coil Leaving
Setpoint
ACTIVE
TEXT
Appendix E: Points List
INACTIVE
TEXT
OBJECT
INSTANCE
38
39
133
134
BACNET
OBJECT
TYPE
ACCESS
AV
AV
AV
AV
ReadCOV_
Commandable
ReadCOV_
Commandable
ReadCOV_
Commandable
ReadCOV_
Commandable
136 AV
ReadCOV_
Commandable
137
138
139
140
141
313
AV
AV
AV
AV
AV
AV
ReadCOV_
Commandable
ReadCOV_
Commandable
ReadCOV_
Commandable
ReadCOV_
Commandable
ReadCOV_
Commandable
ReadCOV_
Commandable
HYST INDEX
MODBUS
REGISTER
TYPE
SIZE
0.1
40075 Holding 2
0.1
0.1
0.1
0.1
1
0.1
0.1
0.1
0.1
0.1
40077
40083
40085
40089
40091
40093
40095
40097
40099
40101
Holding
Holding
Holding
Holding
Holding
Holding
Holding
Holding
Holding
Holding
2
2
2
2
2
2
2
2
2
2
®
Microprocessor Controller for DOAS 45
VARIABLE DESCRIPTION
Unit_Status_Mode
Supply_Temperature_
Calculated_Set Point
Cooling_1_Ramp_
Capacity
0: Off/Standby
1: Unoccupied Start
2: Occupied Start
5: Dampers Open
6: Fan Start Delay
7: Fans Starting
9: Heat/Cool Delay
10: System On
11: Soft Shutdown
12: System Disabled
13: Remote Off
14: Shutdown Alarm
19: Fans Only
20: Economizing
21: Cooling
22: Heating
23: Dehumidifying
25: HGRH Purging
26: Defrost Active
28: Cooling & Heating
29: Dehum w/Heat
30: Overrides Active
31: Expansion Offline
51: IO Test. Sys Disabled
Active Supply Temperature
Set Point
Cooling Ramp 1 Status
Value
Defrost_Ramp Defrost Ramp
Economizer_Ramp
Exhaust_Fan_Space_
Static_Pressure_Ramp
Exhaust_Fan_Supply_
Tracking_Ramp
Head_Pressure_
Control_Ramp_1_
Ramp
Head_Pressure_
Control_Ramp_2_
Ramp
Economizer Ramp
Exhaust Fan Space Static
Pressure Ramp
Exhaust Fan Supply
Tracking Ramp
Head Pressure Control
Ramp 1
Head Pressure Control
Ramp 2
HP_Ramp_Capacity Heat Pump Heating Ramp
Heating_Ramp Heating Ramp
Hot_Gas_Reheat_
Ramp
Space_CO2_Control_
Ramp
Supply_Duct_Static_
Pressure_Ramp
Supply_Fan_Space_
Static_Pressure_Ramp
Hot Gas Reheat Ramp
Space CO2 Control Ramp
Supply Duct Static Pressure
Ramp
Supply Fan Space Static
Pressure Ramp
Winter_Ramp_Output Winter Ramp Output
Outside_Dewpoint
Outside_Enthalpy
Outside Dewpoint
Outside Enthalpy
Return_Dewpoint
Return_Enthalpy
Space_Dewpoint
Space_Enthalpy
Return Dewpoint
Return Enthalpy
Space Dewpoint
Space Enthalpy
ACTIVE
TEXT
Appendix E: Points List
INACTIVE
TEXT
OBJECT
INSTANCE
Analog Values - Read Only
BACNET
OBJECT
TYPE
ACCESS
40
86
87
88
75
82
83
89
59
60
61
71
72
74
41
43
47
48
49
50
51
52
AV
AV
AV
AV
AV
AV
AV
AV
AV
ReadCOV_
NoWrite
ReadCOV_
NoWrite
ReadCOV_
NoWrite
ReadCOV_
NoWrite
ReadCOV_
NoWrite
ReadCOV_
NoWrite
ReadCOV_
NoWrite
ReadCOV_
NoWrite
ReadCOV_
NoWrite
ReadCOV_
NoWrite
ReadCOV_
NoWrite
ReadCOV_
NoWrite
ReadCOV_
NoWrite
ReadCOV_
NoWrite
ReadCOV_
NoWrite
ReadCOV_
NoWrite
ReadCOV_
NoWrite
ReadCOV_
NoWrite
ReadCOV_
NoWrite
ReadCOV_
NoWrite
ReadCOV_
NoWrite
ReadCOV_
NoWrite
AV
AV
AV
AV
AV
AV
AV
AV
AV
AV
AV
AV
AV
46 Microprocessor Controller for DOAS
HYST INDEX
MODBUS
REGISTER
TYPE
SIZE
0
0.1
1
1
1
1
1
1
30001
30003
30007
30015
30017
30019
30021
30023
30025
30071
30085
30087
30093
30095
30097
30099
30039
30041
30043
30063
30065
30069
Input
Input
Input
Input
Input
Input
Input
Input
Input
Input
Input
Input
Input
Input
Input
Input
Input
Input
Input
Input
Input
Input
1
0.1
0.1
0.1
1
0.1
0.1
0.1
1
1
1
1
1
1
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
®
VARIABLE DESCRIPTION
Circuit_A_Superheat
Total_Exhaust_Fan_
CFM_BMS
OAD_CFM_BMS
Circuit A Superheat
Total Exhaust Fan CFM
OAD CFM
OAD_Space_Static_
Pressure_Ramp
Active_Temperature_
Set Point
Chilled_Water_1_
Valve_Analog_Output
Condenser_1_Analog_
Output
Condenser_2_Analog_
Output
Electric_Heater_1_
Analog_Output
Energy_Recovery_
Analog_Output
Exhaust_Fan_Speed_
Analog_Output
Hot_Gas_Reheat_
Analog_Output
Hot_Water_Valve_1_
Analog_Output
Mod_Gas_Furnace_1_
Analog_Output
Outside_Air_Damper_
Analog_Output
Supply_Fan_Speed_
Analog_Output
Modulating_
Compressor_Analog_
Output_BMS
Circuit_A_Sat_
Discharge_
Temperature
Circuit_B_Sat_
Discharge_
Temperature
Circuit_A_Sat_
Suction_Temperature
Coil_Temperature_
Calculated_Setpoint
OAD Static Pressure Ramp
Active Temperature Set point
Chilled Water 1 Valve
Analog Output
Condenser 1 Analog Output
Condenser 2 Analog Output
Electric Heater 1 Analog
Output
Energy Recovery Analog
Output
Exhaust Fan Speed Analog
Output
Hot Gas Reheat Analog
Output
Hot Water Valve 1 Analog
Output
Mod Gas Furnace 1 Analog
Output
Outside Air Damper Analog
Output
Supply Fan Speed Analog
Output
Modulating Compressor
Analog Output - BMS
Circuit A Saturated
Discharge Temperature
Circuit B Saturated
Discharge Temperature
Circuit A Saturated Suciton
Temperature
Calculated Coil Leaving
Setpoint
ACTIVE
TEXT
Appendix E: Points List
INACTIVE
TEXT
OBJECT
INSTANCE
93
107
129
131
132
201
205
206
221
229
231
235
236
242
250
264
BACNET
OBJECT
TYPE
ACCESS
AV
AV
AV
AV
AV
ReadCOV_
NoWrite
ReadCOV_
NoWrite
ReadCOV_
NoWrite
ReadCOV_
NoWrite
ReadCOV_
NoWrite
AV
AV
AV
AV
AV
AV
ReadCOV_
NoWrite
ReadCOV_
NoWrite
ReadCOV_
NoWrite
ReadCOV_
NoWrite
ReadCOV_
NoWrite
ReadCOV_
NoWrite
AV
AV
AV
AV
AV
ReadCOV_
NoWrite
ReadCOV_
NoWrite
ReadCOV_
NoWrite
ReadCOV_
NoWrite
ReadCOV_
NoWrite
285 AV
ReadCOV_
NoWrite
286
287
294
312
AV
AV
AV
AV
ReadCOV_
NoWrite
ReadCOV_
NoWrite
ReadCOV_
NoWrite
ReadCOV_
NoWrite
0.1
0.1
0.1
0.1
0.1
0.1
0.1
0.1
0.1
0.1
0.1
HYST INDEX
MODBUS
REGISTER
TYPE
SIZE
0.1
30107 Input 2
10
10
30135
30173
Input
Input
2
2
1
0.1
30177
30179
Input
Input
2
2
30473
30481
30483
30513
30517
30521
Input
Input
Input
Input
Input
Input
2
2
2
2
2
2
30523
30525
30537
30541
30557
Input
Input
Input
Input
Input
2
2
2
2
2
0.1
30585 Input 2
0.1
0.1
0.1
0.1
30587
30589
30603
30653
Input
Input
Input
Input
2
2
2
2
Microprocessor Controller for DOAS 47
®
Appendix E: Points List
VARIABLE
Exhaust_Fan_1_
Status_Digital_Input
Occupancy_Digital_
Input
Outside_Filter_Alarm_
Digital_Input
Shutdown_Alarm_
Digital_Input
Supply_Fan_1_Status_
Digital_Input
Unit_Enable_Digital_
Input
Wheel_Status_Digital_
Input
BMS_Watchdog
System_Enable
BMS_Occupancy_
Command
DESCRIPTION
Exhaust Fan 1 Status
Occupancy Digital Input
Status
Outside Filter Alarm Digital
Input Status
Shutdown Alarm Digital
Input Status
Supply Fan 1 Status
Remote Unit Enable Digital
Input Status
Heat Wheel Status
ACTIVE
TEXT
Active
Active
Active
Active
Active
Active
Active
INACTIVE
TEXT
OBJECT
INSTANCE
Binary Inputs - Read Only
BACNET
OBJECT
TYPE
ACCESS
Inactive
Inactive
Inactive
Inactive
Inactive
Inactive
Inactive
23
53
54
75
78
82
83
BI
BI
BI
BI
BI
BI
BI
ReadCOV_
NoWrite
ReadCOV_
NoWrite
ReadCOV_
NoWrite
ReadCOV_
NoWrite
ReadCOV_
NoWrite
ReadCOV_
NoWrite
ReadCOV_
NoWrite
Binary Values - Read/Write - Commandable
BMS Watchdog command.
Used to determine comm status. Must heartbeat within the watchdog timeout delay to detect comm status.
Master system enable/ disable point.
Occupancy Command. True
= Unoccupied. False =
Occupied.
Active
Enable
Inactive
Disable
Unoccupy Occupy
1
2
3
BV
BV
BV
Read_
Commandable
Read_
Commandable
Read_
Commandable
Reset_All_Alarms Alarm Reset Command.
Reset Normal 4 BV
Read_
Commandable
Outside_RH_Source_
BMS
Outside_Temp_
Source_BMS
Outside RH Source
Selection. True = BMS.
False = Local.
Outside Temp Source
Selection. True = BMS.
False = Local.
Return_RH_Source_
BMS
Return_Temp_Source_
BMS
Return RH Source
Return Temp Source
Space_1_CO2_
Source_BMS
Space_RH_Source_
BMS
Space_Static_Source_
BMS
Space_Temp_Source_
BMS
SF_Control_Source_
BMS
EF_Control_Source_
BMS
OAD_Control_Source_
BMS
Space 1 CO2 Source
Selection. True = BMS.
False = Local.
Space RH Source Selection.
True = BMS. False = Local.
Space Static Source
Selection. True = BMS.
False = Local.
Space Temp Source
Selection. True = BMS.
False = Local.
Allows the BMS to control supply fan speed. True =
BMS. False = Local.
Allows the BMS to control exhaust fan speed. True =
BMS. False = Local.
Allows the BMS to control
OAD position. True = BMS.
False = Local.
BMS
BMS
BMS
BMS
BMS
BMS
BMS
BMS
BMS
BMS
BMS
Local
Local
Local
Local
Local
Local
Local
Local
Local
Local
Local
5
6
7
8
9
12
13
14
56
57
59
BV
BV
BV
BV
BV
BV
BV
BV
BV
BV
BV
Read_
Commandable
Read_
Commandable
Read_
Commandable
Read_
Commandable
Read_
Commandable
Read_
Commandable
Read_
Commandable
Read_
Commandable
Read_
Commandable
Read_
Commandable
Read_
Commandable
HYST INDEX
MODBUS
REGISTER
TYPE
SIZE
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
55
76
24
54
79
83
84
2
3
4
5
6
7
8
9
10
13
14
15
19
20
22
Discrete
Discrete
Discrete
Discrete
Discrete
Discrete
Discrete
Coil
Coil
Coil
Coil
Coil
Coil
Coil
Coil
Coil
Coil
Coil
Coil
Coil
Coil
Coil
48 Microprocessor Controller for DOAS
®
Appendix E: Points List
VARIABLE
Occupied
Unoccupied
Unoccupied_Cooling_
Call
Unoccupied_
Dehumidification_Call
Unoccupied_Heating_
Call
Occupied_Start
Unoccupied_Start
Enable_Controls
Global_Alarm
System_Shutdown_
Alarm
Damper_Open
Cooling_is_On
Economizer_is_On
Heating_is_On
Dehumidification_
Mode_Enabled
Manual_Override_
Active
Cooling_Not_Locked_
Out
Heating_Not_Locked_
Out
Preheat_Not_Locked_
Out
HGRH_Purging
Allow_Dampers
Allow_Exhaust_Fans
Allow_Supply_Fans
BMS_Watchdog_Active
BMS_Occupancy_
Status
Compressor_1_
Enable_Digital_Output
Compressor_2_
Enable_Digital_Output
Compressor_3_
Enable_Digital_Output
DESCRIPTION
Occupied Status.
Unoccupied Status.
Unoccupied Cooling Call
Status
Unoccupied
Dehumidification Call
Status
Unoccupied Heating Call
Status
Occupied Start Command
Status
Unoccupied Start Command
Status
ACTIVE
TEXT
Occupied
Active
INACTIVE
TEXT
OBJECT
INSTANCE
Binary Values - Read Only
BACNET
OBJECT
TYPE
ACCESS
Unoccupied
Unoccupied Occupied
Inactive
16
17
18
BV
BV
BV
ReadCOV_
NoWrite
ReadCOV_
NoWrite
ReadCOV_
NoWrite
Active
Active
Active
Active
Inactive
Inactive
Inactive
Inactive
19
20
21
22
BV
BV
BV
BV
ReadCOV_
NoWrite
ReadCOV_
NoWrite
ReadCOV_
NoWrite
ReadCOV_
NoWrite
Status to indicate startup is complete and the unit is ready.
General alarm point.
Optionally set to indicate any alarm is active, or a shutdown alarm is active.
Shutdown alarm status.
When true, System Enable will be set to false and the unit will remain off.
Indicates there is a open air path and the supply fan can run.
Indicates that the unit is cooling.
Indicates that the unit is economizing.
Indicates that the unit is heating.
Indicates that the unit is dehumidifying.
Enabled
Alarm
Shutdown
Open
Active
Active
Active
Active
Disabled
Normal
Normal
Closed
Inactive
Inactive
Inactive
Inactive
23
24
25
26
27
28
29
31
BV
BV
BV
BV
BV
BV
BV
BV
ReadCOV_
NoWrite
ReadCOV_
NoWrite
ReadCOV_
NoWrite
ReadCOV_
NoWrite
Indicates that manual overrides are active.
Indicates that cooling is allowed.
Indicates that heating is allowed.
Indicates that preheat is allowed.
Indicates that the hot gas reheat value is purging.
Startup sequence command to open dampers
Startup sequence command to trigger exhaust fans to start
Startup sequence command to trigger supply fans to start
Status of the BMS watchdog ping.
Status of the BMS occupancy command.
Compressor 1 Enable
Digital Output
Compressor 2 Enable
Digital Output
Compressor 3 Enable
Digital Output
Override
Allowed
Allowed
Allowed
Active
Yes
Yes
Yes
Active
Occupied
Active
Active
Active
Normal
Locked_
Out
Locked_
Out
Locked_
Out
Inactive
No
No
No
Inactive
Unoccupied
Inactive
Inactive
Inactive
32
33
34
36
37
43
44
48
49
50
111
112
113
BV
BV
BV
BV
BV
BV
BV
BV
BV
BV
BV
BV
BV
ReadCOV_
NoWrite
ReadCOV_
NoWrite
ReadCOV_
NoWrite
ReadCOV_
NoWrite
ReadCOV_
NoWrite
ReadCOV_
NoWrite
ReadCOV_
NoWrite
ReadCOV_
NoWrite
ReadCOV_
NoWrite
ReadCOV_
NoWrite
ReadCOV_
NoWrite
ReadCOV_
NoWrite
ReadCOV_
NoWrite
ReadCOV_
NoWrite
ReadCOV_
NoWrite
ReadCOV_
NoWrite
ReadCOV_
NoWrite
®
HYST INDEX
MODBUS
REGISTER
TYPE
SIZE
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
10002 Discrete
10003 Discrete
10004 Discrete
10005 Discrete
10006 Discrete
10007 Discrete
10008 Discrete
10009 Discrete
10010 Discrete
10011 Discrete
10012 Discrete
10013 Discrete
10014 Discrete
10015 Discrete
10017 Discrete
10018 Discrete
10019 Discrete
10020 Discrete
10022 Discrete
10023 Discrete
10029 Discrete
10030 Discrete
10034 Discrete
10035 Discrete
10036 Discrete
10164 Discrete
10165 Discrete
10166 Discrete
Microprocessor Controller for DOAS 49
VARIABLE DESCRIPTION
Circuit_A_Suction_
Temp_Analog_Input_
Alarm.Active
Circuit_B_Discharge_
Pressure_Analog_
Input_Alarm.Active
Cold_Coil_1_
Temperature_Sensor_
Alarm.Active
Comp_Maintenance_
Alarm.Active
Exhaust_Fan_1_Alarm.
Active
Expansion_Board_1_
Alarm.Active
Expansion_Board_2_
Alarm.Active
Expansion_Board_3_
Alarm.Active
Internal_Board_Temp_
Alarm.Active
Multi_Channel_Conf_
Alarm.Active
Outside_Air_
Temperature_Sensor_
Alarm.Active
Outside_Filter_Alarm.
Active
Outside_RH_Sensor_
Alarm.Active
Space_CO2_1_
Analog_Input_Alarm.
Active
Space_High_Static_
Alarm.Active
Compressor_4_
Enable_Digital_Output
Condenser_Fan_1_
Digital_Output
Condenser_Fan_2_
Digital_Output
Condenser_Fan_3_
Digital_Output
Exhaust_Fan_1_Start_
Stop_Digital_Output
Furnace_1_Stage_1_
Digital_Output
Furnace_2_Stage_1_
Digital_Output
Heat_Wheel_Enable_
Digital_Output
PreHeat_Enable_
Digital_Output
Supply_Fan_1_Start_
Stop_Digital_Output
BMS_Offline_Alarm.
Active
Circuit_A_Discharge_
Pressure_Analog_
Input_Alarm.Active
Circuit_A_Discharge_
Temp_Analog_Input_
Alarm.Active
Circuit_A_Suction_
Pressure_Analog_
Input_Alarm.Active
Compressor 4 Enable
Digital Output
Condenser Fan 1 Digital
Output
Condenser Fan 2 Digital
Output
Condenser Fan 3 Digital
Output
Exhaust Fan 1 Start Stop
Digital Output
Furnace 1 Stage 1 Digital
Output
Furnace 2 Stage 1 Digital
Output
Heat Wheel Enable Digital
Output
PreHeat Enable Digital
Output
Supply Fan 1 Start Stop
Digital Output
BMS Offline Alarm
(0=Normal 1=Alarm)
Circuit A Discharge
Pressure Analog Input
Alarm
Circuit A Discharge Temp
Analog Input Alarm
Circuit A Suction Pressure
Analog Input Alarm
Circuit A Suction Temp
Analog Input Alarm
Circuit B Discharge
Pressure Analog Input
Alarm
Cold Coil 1 Temperature
Sensor Alarm (0=Normal
1=Alarm)
Comp Maintenance Alarm
(0=Normal 1=Alarm)
Exhaust Fan 1 Alarm
(0=Normal 1=Alarm)
Expansion Board 1 Alarm
(0=Normal 1=Alarm)
Expansion Board 2 Alarm
(0=Normal 1=Alarm)
Expansion Board 3 Alarm
(0=Normal 1=Alarm)
Internal Board Temp Alarm
(0=Normal 1=Alarm)
Multi Channel Conf Alarm
(0=Normal 1=Alarm)
Outside Air Temperature
Sensor Alarm (0=Normal
1=Alarm)
Outside Filter Alarm
(0=Normal 1=Alarm)
Outside RH Sensor Alarm
(0=Normal 1=Alarm)
Space CO2 1 Analog Input
Alarm (0=Normal 1=Alarm)
Space High Static Alarm
(0=Normal 1=Alarm)
50 Microprocessor Controller for DOAS
ACTIVE
TEXT
Active
Active
Active
Active
Active
Active
Active
Active
Active
Active
Alarm
Appendix E: Points List
INACTIVE
TEXT
Inactive
Inactive
Inactive
Inactive
Inactive
Inactive
Inactive
Inactive
Inactive
Inactive
Normal
OBJECT
INSTANCE
114
119
120
121
127
131
133
163
166
186
313
BACNET
OBJECT
TYPE
ACCESS
BV
BV
BV
BV
BV
ReadCOV_
NoWrite
ReadCOV_
NoWrite
ReadCOV_
NoWrite
ReadCOV_
NoWrite
ReadCOV_
NoWrite
BV
BV
BV
BV
BV
BV
ReadCOV_
NoWrite
ReadCOV_
NoWrite
ReadCOV_
NoWrite
ReadCOV_
NoWrite
ReadCOV_
NoWrite
ReadCOV_
NoWrite
Alarm Normal 315 BV
ReadCOV_
NoWrite
Alarm
Alarm
Alarm
Alarm
Alarm
Alarm
Alarm
Alarm
Alarm
Alarm
Alarm
Alarm
Alarm
Alarm
Alarm
Alarm
Alarm
Normal
Normal
Normal
Normal
Normal
Normal
Normal
Normal
Normal
Normal
Normal
Normal
Normal
Normal
Normal
Normal
Normal
316
319
320
324
387
411
423
434
435
436
498
503
507
508
509
535
537
BV
BV
BV
BV
BV
BV
BV
BV
BV
BV
BV
BV
BV
BV
BV
BV
BV
ReadCOV_
NoWrite
ReadCOV_
NoWrite
ReadCOV_
NoWrite
ReadCOV_
NoWrite
ReadCOV_
NoWrite
ReadCOV_
NoWrite
ReadCOV_
NoWrite
ReadCOV_
NoWrite
ReadCOV_
NoWrite
ReadCOV_
NoWrite
ReadCOV_
NoWrite
ReadCOV_
NoWrite
ReadCOV_
NoWrite
ReadCOV_
NoWrite
ReadCOV_
NoWrite
ReadCOV_
NoWrite
ReadCOV_
NoWrite
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
HYST INDEX
MODBUS
REGISTER
TYPE
SIZE
0 10167 Discrete
0
0
10172
10173
Discrete
Discrete
0
0
10174 Discrete
10180 Discrete
10184
10186
10208
Discrete
Discrete
Discrete
10211 Discrete
10231 Discrete
10264 Discrete
10266 Discrete
10267 Discrete
10270 Discrete
10271 Discrete
10275 Discrete
10338 Discrete
10362 Discrete
10373 Discrete
10384 Discrete
10385 Discrete
10386 Discrete
10448 Discrete
10453 Discrete
10457 Discrete
10458 Discrete
10459 Discrete
10485 Discrete
10487 Discrete
®
VARIABLE DESCRIPTION
Space_RH_Sensor_
Alarm.Active
Space_Set Point_
Slider_Alarm.Active
Space_Static_
Pressure_Analog_
Input_Alarm.Active
Space_Temperature_
Sensor_Alarm.Active
Shutdown_Input_
Alarm.Active
Supply_Air_Temp_
Low_Limit.Active
Supply_Air_
Temperature_Sensor_
Alarm.Active
Supply_Duct_Static_
Pressure_Analog_
Input_Alarm.Active
Supply_Fan_1_Alarm.
Active
Supply_High_Duct_
Static_Alarm.Active
Supply_RH_Sensor_
Alarm.Active
Supply_Temp_High_
Limit_Alarm.Active
TMem_Error.Active
Wheel_Rotation_
Alarm.Active
Al_Batt_EVD_1.Active
Al_ConfigErr_EVD_1.
Active
Al_DscgHiP_COMP_1.
Active
Al_DscgHiTemp_
COMP_1.Active
Al_DscgLowP_
COMP_1.Active
Al_EEPROM_EVD_1.
Active
Al_EEV_A_EVD_1.
Active
Al_EmergencyClosing_
EVD_1.Active
Al_EVD_Offline_
EVD_1.Active
Al_FW_CompatibErr_
EVD_1.Active
Al_HiCurr_COMP_1.
Active
Al_HiRatioP_COMP_1.
Active
Al_HiT_Cond_EVD_1.
Active
Al_IncompleteClosing_
EVD_1.Active
Space RH Sensor Alarm
(0=Normal 1=Alarm)
Space Set Point Slider
Alarm (0=Normal 1=Alarm)
Space Static Pressure
Analog Input Alarm
(0=Normal 1=Alarm)
Space Temperature Sensor
Alarm (0=Normal 1=Alarm)
Shutdown Input Alarm
(0=Normal 1=Alarm)
Supply Air Temp Low Limit
Alarm (0=Normal 1=Alarm)
Supply Air Temperature
Sensor Alarm (0=Normal
1=Alarm)
Supply Duct Static Pressure
Analog Input Alarm
(0=Normal 1=Alarm)
Supply Fan 1 Alarm
(0=Normal 1=Alarm)
Supply High Duct Static
Alarm (0=Normal 1=Alarm)
Supply RH Sensor Alarm
(0=Normal 1=Alarm)
Supply Temp High Limit
Alarm (0=Normal 1=Alarm)
TMem Error Alarm
(0=Normal 1=Alarm)
Wheel Rotation Alarm
(0=Normal 1=Alarm)
EVD Battery Alarm
(0=Normal 1=Alarm)
EVD Configuration Alarm
(0=Normal 1=Alarm)
Compressor Envelope -
High Discharge Pressure
Alarm (0=Normal 1=Alarm)
Compressor Envelope
- High Discharge
Temperature Alarm
(0=Normal 1=Alarm)
EVD Low Discharge
Pressure Alarm (0=Normal
1=Alarm)
EVD EEPROM Alarm
(0=Normal 1=Alarm)
ExV Motor Alarm - Valve 1
(0=Normal 1=Alarm)
EVD Emergency Closing
Alarm (0=Normal 1=Alarm)
EVD Offline Communication
Alarm (0=Normal 1=Alarm)
EVD Firmware Compability
Alarm (0=Normal 1=Alarm)
Compressor Envelope
- High Current Alarm
(0=Normal 1=Alarm)
Compressor Envelope -
High Pressure Ratio Alarm
(0=Normal 1=Alarm)
Al_HiT_Cond_EVD_1
(0=Normal 1=Alarm)
EVD Incomplete Closing
Alarm (0=Normal 1=Alarm)
ACTIVE
TEXT
Alarm
Alarm
Appendix E: Points List
INACTIVE
TEXT
Normal
Normal
OBJECT
INSTANCE
538
539
BACNET
OBJECT
TYPE
ACCESS
BV
BV
ReadCOV_
NoWrite
ReadCOV_
NoWrite
Alarm Normal 540 BV
ReadCOV_
NoWrite
Alarm
Alarm
Alarm
Alarm
Normal
Normal
Normal
Normal
541
546
551
552
BV
BV
BV
BV
ReadCOV_
NoWrite
ReadCOV_
NoWrite
ReadCOV_
NoWrite
ReadCOV_
NoWrite
Alarm
Alarm
Alarm
Alarm
Alarm
Alarm
Alarm
Alarm
Alarm
Alarm
Alarm
Alarm
Alarm
Alarm
Alarm
Alarm
Alarm
Alarm
Alarm
Alarm
Alarm
Normal
Normal
Normal
Normal
Normal
Normal
Normal
Normal
Normal
Normal
Normal
Normal
Normal
Normal
Normal
Normal
Normal
Normal
Normal
Normal
Normal
553
554
563
564
565
567
576
589
590
591
592
593
594
595
597
598
599
600
601
602
603
BV
BV
BV
BV
BV
BV
BV
BV
BV
BV
BV
BV
BV
BV
BV
BV
BV
BV
BV
BV
BV
ReadCOV_
NoWrite
ReadCOV_
NoWrite
ReadCOV_
NoWrite
ReadCOV_
NoWrite
ReadCOV_
NoWrite
ReadCOV_
NoWrite
ReadCOV_
NoWrite
ReadCOV_
NoWrite
ReadCOV_
NoWrite
ReadCOV_
NoWrite
ReadCOV_
NoWrite
ReadCOV_
NoWrite
ReadCOV_
NoWrite
ReadCOV_
NoWrite
ReadCOV_
NoWrite
ReadCOV_
NoWrite
ReadCOV_
NoWrite
ReadCOV_
NoWrite
ReadCOV_
NoWrite
ReadCOV_
NoWrite
ReadCOV_
NoWrite
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
HYST INDEX
MODBUS
REGISTER
TYPE
SIZE
0 10488 Discrete
0 10489 Discrete
0 10490 Discrete
10491 Discrete
10496 Discrete
10501
10502
Discrete
Discrete
10503 Discrete
10504 Discrete
10513 Discrete
10514 Discrete
10515 Discrete
10517 Discrete
10526 Discrete
10539 Discrete
10540 Discrete
10541 Discrete
10542 Discrete
10543 Discrete
10544 Discrete
10545 Discrete
10547 Discrete
10548 Discrete
10549 Discrete
10550 Discrete
10551 Discrete
10552 Discrete
10553 Discrete
Microprocessor Controller for DOAS 51
®
VARIABLE DESCRIPTION
Al_LOP_A_EVD_1.
Active
Al_Low_SH_A_EVD_1.
Active
Al_LowDeltaP_
COMP_1.Active
Al_LowRatioP_
COMP_1.Active
Al_LowSuct_A_EVD_1.
Active
Al_MOP_A_EVD_1.
Active
Al_S1_EVD_1.Active
Al_S2_EVD_1.Active
Al_S4_EVD_1.Active
Al_SuctHiP_COMP_1.
Active
Al_SuctLowP_
COMP_1.Active
EVD Low Operating
Pressure Alarm - Valve 1
(0=Normal 1=Alarm)
EVD Low SuperHeat
Alarm - Valve 1 (0=Normal
1=Alarm)
Compressor Envelope -
Low Pressure DeltaAlarm
(0=Normal 1=Alarm)
Compressor Envelope -
Low Pressure Ratio Alarm
(0=Normal 1=Alarm)
Low Suction Refrigerant
Temperature - Valve 1
(0=Normal 1=Alarm)
EVD Max Operating
Pressure Alarm - Valve 1
(0=Normal 1=Alarm)
EVD-S1 Suction Pressure
Sensor Alarm (0=Normal
1=Alarm)
EVD-S2 Suction
Temperature Sensor Alarm
(0=Normal 1=Alarm)
EVD-S4 Discharge
Temperature Sensor Alarm
(0=Normal 1=Alarm)
Compressor Envelope -
SuctHiP_COMP (0=Normal
1=Alarm)
Compressor Envelope
- SuctLowP_COMP
(0=Normal 1=Alarm)
HP_Defrost_Active.
Active
Heat Pump Defrost Alarm
Comp_Staging_Order_
Skipped.Active
Compressor Staging
Order is Skipped Warning
(0=Normal 1=Alarm)
Heat_Pump_Heating_
Lock_Out_Alarm.
Active
EVD_PrePosition_
Alarm_1.Active
ER_Wheel_High_
DP.Active
OAD_Feedback_Error_
Not_Economizing.
Active
OAD_Feedback_Error_
Economizing.Active
OAD_Feedback_Error_
OAD_Not_Modulating.
Active
OAD_Feedback_Error_
Excess_OA.Active
Heat Pump Heating Locked
Out Alarm
Unexpected EEV Position
(0=Normal 1=Alarm)
Energy Recovery Wheel high differential pressure
(0=Normal 1=Alarm)
Feedback indicates OAD is not opening during economizer
Feedback indicates OAD is open
Feedback indicates the OAD is not modulating
Feedback indicates the OAD is not closing
ACTIVE
TEXT
Appendix E: Points List
INACTIVE
TEXT
OBJECT
INSTANCE
BACNET
OBJECT
TYPE
ACCESS
Alarm Normal 604 BV
ReadCOV_
NoWrite
Alarm
Alarm
Alarm
Alarm
Alarm
Alarm
Alarm
Alarm
Alarm
Alarm
Alarm
Alarm
Alarm
Alarm
Alarm
Alarm
Alarm
Alarm
Alarm
Normal
Normal
Normal
Normal
Normal
Normal
Normal
Normal
Normal
Normal
Normal
Normal
Normal
Normal
Normal
Normal
Normal
Normal
Normal
606
608
609
610
612
614
615
617
618
619
631
632
633
634
731
741
742
743
744
BV
BV
BV
BV
BV
BV
BV
BV
BV
BV
BV
BV
BV
BV
BV
BV
BV
BV
BV
ReadCOV_
NoWrite
ReadCOV_
NoWrite
ReadCOV_
NoWrite
ReadCOV_
NoWrite
ReadCOV_
NoWrite
ReadCOV_
NoWrite
ReadCOV_
NoWrite
ReadCOV_
NoWrite
ReadCOV_
NoWrite
ReadCOV_
NoWrite
ReadCOV_
NoWrite
ReadCOV_
NoWrite
ReadCOV_
NoWrite
ReadCOV_
NoWrite
ReadCOV_
NoWrite
ReadCOV_
NoWrite
ReadCOV_
NoWrite
ReadCOV_
NoWrite
ReadCOV_
NoWrite
0
0
HYST INDEX
MODBUS
REGISTER
TYPE
SIZE
0 10554 Discrete
0
0
0
0
0
0
0
0
0
0
0
10556 Discrete
10558 Discrete
10559 Discrete
10560 Discrete
10562 Discrete
10564 Discrete
10565 Discrete
10567 Discrete
10568 Discrete
10569 Discrete
10579 Discrete
10580 Discrete
10581 Discrete
10582 Discrete
10679 Discrete
10690 Discrete
10692 Discrete
10694 Discrete
10696 Discrete
52 Microprocessor Controller for DOAS
®
VARIABLE
Aux_BMS_Digital_
Output_1
Aux_BMS_Digital_
Output_2
Aux_BMS_Digital_
Output_3
Aux_BMS_Digital_
Output_4
Aux_BMS_Digital_
Output_5
Aux_BMS_Digital_
Output_6
DESCRIPTION
BMS Commanded auxilary digital output
BMS Commanded auxilary digital output
BMS Commanded auxilary digital output
BMS Commanded auxilary digital output
BMS Commanded auxilary digital output
BMS Commanded auxilary digital output
Allow_Fan_Delay_
Remaining
Supply_Fan_Delay_
Remaining
Exhaust_Fan_Delay_
Remaining
LatestAlm
Startup Sequence Fan
Damper Delay. Time before enabling Fan startup sequence.
Supply Fan startup sequence. Time before starting supply fan.
Exhaust Fan startup sequence. Time before starting exhaust fan.
Most recent alarm. See alarm table.
ACTIVE
TEXT
Active
Active
Active
Active
Active
Active
Appendix E: Points List
INACTIVE
TEXT
OBJECT
INSTANCE
Binary Values - Commandable
BACNET
OBJECT
TYPE
ACCESS
Inactive
Inactive
207
208
BV
BV
ReadCOV_
Commandable
ReadCOV_
Commandable
Inactive
Inactive
Inactive
Inactive
209
210
211
212
BV
BV
BV
BV
ReadCOV_
Commandable
ReadCOV_
Commandable
ReadCOV_
Commandable
ReadCOV_
Commandable
Integer Values - Read Only
1 IV
ReadCOV_
NoWrite
2
3
IV
IV
ReadCOV_
NoWrite
ReadCOV_
NoWrite
ReadCOV_
NoWrite
High_Low_Press_
Circ_A_Alarm.Active
High_Low_Press_
Circ_B_Alarm.Active
High_Low_Press_
Circ_C_Alarm.Active
High_Low_Press_
Circ_D_Alarm.Active
High_Low_Press_
Circ_C_Alarm.Active
High_Low_Press_
Circ_D_Alarm.Active
Greentrol_1_Alarm.
Active
Greentrol_2_Alarm.
Active
Greentrol_3_Alarm.
Active
High Low Pressure Switch
Alarm Circuit A
High Low Pressure Switch
Alarm Circuit B
High Low Pressure Switch
Alarm Circuit A
High Low Pressure Switch
Alarm Circuit B
High Low Pressure Switch
Alarm Circuit C
High Low Pressure Switch
Alarm Circuit D
Greentrol Device Alarm
Greentrol Device Alarm
Greentrol Device Alarm
Mixed_Temp_Analog_
Input
Exhaust_Fan_Speed_
Analog_Input
Supply_Fan_Speed_
Analog_Input
Mixed Temperature
Exhaust Fan Speed Remote
Command Analog Input value
Supply Fan Speed Remote
Command Analog Input value
Alarm
Alarm
Alarm
Alarm
Alarm
Alarm
Alarm
Alarm
Alarm
Normal
Normal
Normal
Normal
Normal
Normal
7
Large Board Points
Binary Values - Read Only
Normal 733
Normal 734
IV
BV
BV
735
736
735
736
737
738
Normal 739
Medium Board Points
Analog Inputs - Read Only
35
BV
AI
BV
BV
BV
BV
BV
BV
143
155
AI
AI
ReadCOV_
NoWrite
ReadCOV_
NoWrite
ReadCOV_
NoWrite
ReadCOV_
NoWrite
ReadCOV_
NoWrite
ReadCOV_
NoWrite
ReadCOV_
NoWrite
ReadCOV_
NoWrite
ReadCOV_
NoWrite
ReadCOV_
NoWrite
ReadCOV_
NoWrite
ReadCOV_
NoWrite
HYST INDEX
MODBUS
REGISTER
TYPE
SIZE
1
1
1
1
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0.1
1
1
26
27
24
25
28
29
30182
30184
30186
30195
10682 Discrete
10683 Discrete
10684 Discrete
10685 Discrete
10684 Discrete
10685 Discrete
10686 Discrete
10687 Discrete
10688 Discrete
30263
30455
30461
Coil
Coil
Coil
Coil
Coil
Coil
Input
Input
Input
Input
Input
Input
Input
1
1
1
2
2
2
2
Microprocessor Controller for DOAS 53
®
VARIABLE DESCRIPTION
Comp_Circ_A_High_
Pressure_Digital_Input
Comp_Circ_A_Low_
Pressure_Digital_Input
Comp_Circ_B_High_
Pressure_Digital_Input
Comp_Circ_B_Low_
Pressure_Digital_Input
Drain_Pan_Alarm_
Digital_Input
EAD_End_Switch_
Digital_Input
OAD_End_Switch_
Digital_Input
Circuit A High Pressure
Switch
Circuit A Low Pressure
Switch
Circuit B High Pressure
Switch
Circuit B Low Pressure
Switch
Drain Pan Alarm Digital
Input Status
Exhaust Air Damper End
Switch Digital Input Status
OAD End Switch Digital
Input Status
Condenser_Fan_5_
Digital_Output
Condenser_Fan_6_
Digital_Output
Condenser_Fan_7_
Digital_Output
Comp_Circ_A_High_
Pressure_Alarm.Active
Comp_Circ_A_Low_
Pressure_Alarm.Active
Comp_Circ_B_High_
Pressure_Alarm.Active
Comp_Circ_B_Low_
Pressure_Alarm.Active
Damper_End_Switch_
Alarm.Active
Drain_Pan_Alarm.
Active
Exhaust_Fan_1_AMD_ analog_input_Alarm.
Active
Freeze_Stat_Alarm.
Active
Mixed_Temperature_
Sensor_Alarm.Active
OAD_AMD_analog_ input_Alarm.Active
Condenser Fan 5 Digital
Output
Condenser Fan 6 Digital
Output
Condenser Fan 7 Digital
Output
Comp Circ A High Pressure
Alarm (0=Normal 1=Alarm)
Comp Circ A Low Pressure
Alarm (0=Normal 1=Alarm)
Comp Circ B High Pressure
Alarm (0=Normal 1=Alarm)
Comp Circ B Low Pressure
Alarm (0=Normal 1=Alarm)
Damper End Switch Alarm
(0=Normal 1=Alarm)
Drain Pan Alarm (0=Normal
1=Alarm)
Exhaust Fan 1 CFM Analog
Input Alarm (0=Normal
1=Alarm)
Freeze Stat Alarm
(0=Normal 1=Alarm)
Mixed Temperature Sensor
Alarm (0=Normal 1=Alarm)
OAD CFM Analog Input
Alarm (0=Normal 1=Alarm)
ACTIVE
TEXT
Active
Active
Active
Active
Active
Active
Active
Active
Active
Active
Alarm
Alarm
Alarm
Alarm
Alarm
Alarm
Appendix E: Points List
INACTIVE
TEXT
OBJECT
INSTANCE
Binary Inputs - Read Only
BACNET
OBJECT
TYPE
ACCESS
Inactive
Inactive
Inactive
Inactive
Inactive
Inactive
Inactive
3
4
5
6
21
22
52
BI
BI
BI
BI
BI
BI
BI
ReadCOV_
NoWrite
ReadCOV_
NoWrite
ReadCOV_
NoWrite
ReadCOV_
NoWrite
ReadCOV_
NoWrite
ReadCOV_
NoWrite
ReadCOV_
NoWrite
Binary Values - Read Only
Inactive
Inactive
Inactive
Normal
Normal
Normal
Normal
Normal
Normal
123
124
125
395
396
397
398
420
422
BV
BV
BV
BV
BV
BV
BV
BV
BV
ReadCOV_
NoWrite
ReadCOV_
NoWrite
ReadCOV_
NoWrite
ReadCOV_
NoWrite
ReadCOV_
NoWrite
ReadCOV_
NoWrite
ReadCOV_
NoWrite
ReadCOV_
NoWrite
ReadCOV_
NoWrite
Alarm Normal 424 BV
ReadCOV_
NoWrite
Alarm
Alarm
Alarm
Normal
Normal
Normal
441
502
506
BV
BV
BV
ReadCOV_
NoWrite
ReadCOV_
NoWrite
ReadCOV_
NoWrite
HYST INDEX
MODBUS
REGISTER
TYPE
SIZE
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
10052 Discrete
10053 Discrete
10054 Discrete
10055 Discrete
10070 Discrete
10071 Discrete
10101 Discrete
10176 Discrete
10177 Discrete
10178 Discrete
10346 Discrete
10347 Discrete
10348 Discrete
10349 Discrete
10371 Discrete
10372 Discrete
10374 Discrete
10391 Discrete
10452 Discrete
10456 Discrete
54 Microprocessor Controller for DOAS
®
Appendix F: Factory ModBus Connections
E ABL C DED IEL SH
®
Microprocessor Controller for DOAS 55
Our Commitment
As a result of our commitment to continuous improvement, Greenheck reserves the right to change specifications without notice.
Specific Greenheck product warranties are located on greenheck.com within the product area tabs and in the
Library under Warranties.
AMCA Publication 410-96, Safety Practices for Users and Installers of Industrial and Commercial Fans, provides additional safety information. This publication can be obtained from AMCA International, Inc. at www.amca.org.
®
Phone: 715.359.6171 • Fax: 715.355.2399 • Parts: 800.355.5354 • E-mail: [email protected] • Website: www.greenheck.com
56 484279 • Microprocessor Controller, Rev. 1, February 2020 Copyright 2020 © Greenheck Fan Corporation
advertisement
* Your assessment is very important for improving the workof artificial intelligence, which forms the content of this project
Related manuals
advertisement
Table of contents
- 3 Sequence of Operation
- 8 Controller Overview
- 19 Temp Control
- 22 Dehumidification
- 24 Refrigeration
- 24 Damper Control
- 26 Energy Recovery
- 27 Fan Control
- 29 Occupancy
- 30 Advanced
- 37 Alarms
- 38 Remote Display
- 39 I/O Expansion Board Quick Start
- 40 Space Thermostat Quick Start
- 42 Airflow Monitoring Quick Start
- 43 Points List
- 55 Modbus Connections