Server Technology CSG Series Smart POPS Cabinet Power Distribution Unit Installation & Operations Manual
Add to my manuals
149 Pages
advertisement
Firmware Release 7.0
Smart Rack Power
Distribution Unit
Installation and Operations Manual
Instructions
This symbol is intended to alert the user to the presence of important operating and maintenance (servicing) instructions in the literature accompanying the appliance.
Dangerous Voltage
This symbol is intended to alert the user to the presence of uninsulated dangerous voltage within the product’s enclosure that may be of sufficient magnitude to constitute a risk of electric shock to persons.
Protective Grounding Terminal
This symbol indicates a terminal that must be connected to earth ground prior to making any other connections to the equipment.
Life-Support Policy
As a general policy, Server Technology does not recommend the use of any of its products in the following situations:
• life-support applications where failure or malfunction of the Server Technology product can be reasonably expected to cause failure of the lifesupport device or to significantly affect its safety or effectiveness.
• direct patient care.
Server Technology will not knowingly sell its products for use in such applications unless it receives in writing assurances satisfactory to Server
Technology that:
• the risks of injury or damage have been minimized,
• the customer assumes all such risks, and
• the liability of Server Technology is adequately protected under the circumstances.
The term life-support device includes but is not limited to neonatal oxygen analyzers, nerve stimulators (whether used for anesthesia, pain relief or other purposes), auto-transfusion devices, blood pumps, defibrillators, arrhythmia detectors and alarms, pacemakers, hemodialysis systems, peritoneal dialysis systems, neonatal ventilator incubators, ventilators (for adults or infants), anesthesia ventilators, infusion pumps, and any other devices designated as
“critical” by the U.S. FDA.
Notices
301-0113-1 Rev L (052016)
Copyright © 2005-2016 Server Technology, Inc. All rights reserved.
1040 Sandhill Drive
Reno, Nevada 89521 USA
All Rights Reserved
This publication is protected by copyright and all rights are reserved. No part of it may be reproduced or transmitted by any means or in any form, without prior consent in writing from Server Technology.
The information in this document has been carefully checked and is believed to be accurate. However, changes are made periodically. These changes are incorporated in newer publication editions. Server Technology may improve and/or change products described in this publication at any time. Due to continuing system improvements, Server Technology is not responsible for inaccurate information which may appear in this manual. For the latest product updates, consult the Server Technology web site at www.servertech.com
. In no event will Server Technology be liable for direct, indirect, special, exemplary, incidental, or consequential damages resulting from any defect or omission in this document, even if advised of the possibility of such damages.
In the interest of continued product development, Server Technology reserves the right to make improvements in this document and the products it describes at any time, without notices or obligation.
The Globe logo is a trademark of Server Technology, Inc., registered in the US. Use of the logos for commercial purposes without the prior written consent of Server Technology may constitute trademark infringement and unfair competition in violation of federal and state laws.
Server Technology, the Globe logo, Sentry, Switched CDU, CDU, PRO2, PIPS, POPS, PDU Power Pivot, and StartUp Stick are trademarks of Server
Technology, Inc., registered in the US. EZip is a trademark of Server Technology.
Other trademarks and trade names may be used in this document to refer to either the entities claiming the marks and names or their products. Server
Technology, Inc. disclaims any proprietary interest in trademarks and trade names other than its own.
Please Recycle
Shipping materials are recyclable. Please save them for later use, or dispose of them appropriately.
Table of Contents
C HAPTER 4: A DVANCED O PERATIONS
Chapter 1: Introduction
Quick Installation Checklist
The following steps are recommended to quickly install and configure the Smart POPS
PDU for use in your data center equipment cabinet:
1.
Mount the Smart POPS PDU.
2.
Connect to the power source.
3.
Connect the devices.
4.
Connect the sensors.
5.
Connect to the Smart POPS CDU.
6.
Configure the Smart POPS PDU.
•
Login as the predefined Administrator (admn/admn).
•
Configure the network settings.
•
Create new administrative user account.
•
Configure location and Smart POPS CDU names.
•
Configure sensor names.
•
Configure new user account(s).
•
Remove the predefined Administrator.
7.
Connect the Smart POPS PDU to the network.
Technical Support
Experience Server Technology's FREE Technical Support
Server Technology
understands that there are often questions when installing and/or using a new product. Free
Technical Support is provided from 8 a.m. to 5 p.m. PST, Monday through Friday. After-hours service is provided to ensure your requests are handled quickly no matter what time zone or country you are located in.
Server Technology, Inc.
1040 Sandhill Drive
Reno, Nevada 89521 USA
Tel: 1-800-835-1515
Fax: 775-284-2065
Web: www.servertech.com
Email: [email protected]
4
•
Introduction Smart POPS PDU
Installation and Operations Manual
PDU Power Pivot
Server Technology’s PDU Power Pivot
flexible infeed provides a simplified power cord routing to the PDU with a design that eliminates bend radius issues.
As illustrated below, the PDU Power Pivot capability can deliver a solution for several types of PDU installations and mountings, setting the correct cord angle for overhead power, offset overhead power, concrete floor, raised floor, and intra-rack power.
PDU Power Pivot – Flexible Cord Design
Smart POPS PDU
Installation and Operations Manual Introduction
•
5
Equipment Overview
1.
The power inlet/cord(s) connects the PDU to the electrical power source.
2.
The Input Current LED(s) displays the current load for each infeed or electrical phase per infeed.
3.
Two RJ45 connectors for Serial (RS-232) and Ethernet connection
4.
Two mini RJ11 connectors for Temperature/Humidity sensors.
Smart POPS Rack Power Distribution Unit (PDU) – Product Family Views
6
•
Introduction Smart POPS PDU
Installation and Operations Manual
IPv6 and Server Technology Products
Server Technology is introducing IPv6 “dual stack” support to the PDU product line. IPv6 has been designed to succeed IPv4 as the dominant communications protocol for internet traffic, to avoid depletions of the IPv4 address space, and to allow more IP address growth. Many devices already in use support IPv6.
IPv6 has several new operational methods:
•
Static IPv6 Address: The IPv6 equivalent of Static IPv4.
•
DHCPv6 Address: The IPv6 equivalent of a DHCP IPv4 address, also known as a “stateful” autoconfiguration of DHCPv6.
•
IPv6 Stateless Auto-Configured Address – (RFC 4862): An automatically-generated unique link-local IPv6 address used for client based configurations. This address is always present in the Server Technology dual stack and cannot be disabled.
•
DHCPv6 Stateless Auto-Configured Address – (RFC 3736): A “stateless” Dynamic Host Configuration
Protocol (DHCP) service for IPv6 (DHCPv6). This address is used by nodes to obtain configuration information, such as addresses of DNS recursive name servers that do not require the maintenance of any dynamic state for individual clients.
PDU Firmware – Protocol Support
IPv6 and IPv4 Protocols:
The PDU firmware supports the following network IPv6 and IPv4 protocols:
•
DNS Ping
•
FTP (or SFTP) Server SNMPv1/2/3
•
FTP (or SFTP) Updates SNTP
•
HTTP HTTPS
•
SMTP
•
Static IPv6 DHCPv6 (stateless and stateful)
•
Syslog SNMPv1/2/3 Traps
•
Telnet SSH
IPv4-Only Protocols:
The PDU firmware supports the following network IPv4-only protocols:
•
Cisco EnergyWise
•
LDAP
•
Load Shedding *
•
RADIUS *
•
TACACS+
* = may work with IPv6 addresses, but not tested.
Smart POPS PDU
Installation and Operations Manual Introduction
•
7
Network-Enabled Modes
NOTES :
•
For all network-enabled modes described below, the PDU will set an auto-configured IPv6 address, and if IPv6 router announcements are
active, a stateless DHCP IPv6 address will also be set. Further, in all network-enabled modes, at least one IPv4 or one IPv6 address will
be active.
•
For maximum backward compatibility, the default network mode is “IPv4 only”.
•
•
Network disabled – No IPv4 or IPv6 addresses available.
•
IPv4 only, DHCP disabled (static IPv4) – If the IPv4 Static Address and Net Mask of the PDU are valid, they will be set.
•
IPv4 only, DHCP enabled (DHCP IPv4) – The PDU will try to resolve an IPv4 DHCP address. If a DHCP address cannot be obtained after 90 seconds, the PDU can: (1) optionally fall back to its static IPv4 settings, or (2) indefinitely wait to acquire an address based on DHCP configuration settings. This setting is the default .
Dual IPv6/IPv4, DHCP disabled (static IPv6/IPv4) – If the IPv6 Static Address and prefix of the PDU are valid, they will be set. Otherwise, the PDU will attempt to use DHCPv6 to obtain an IPv6 address.
•
In addition, if the IPv4 Static Address and Net Mask of the PDU are valid, they will be set.
Dual IPv6/IPv4, DHCP enabled (DHCP IPv6/IPv4) – The PDU will try to resolve both its IPv6 and IPv4 addresses by DHCP. If both DHCP requests are answered, the primary DNS server of the PDU will become the primary IPv6 DNS server, and the secondary DNS server of the PDU will become the primary IPv4
DNS server.
If only one of the DHCP requests is answered, the DNS servers of the PDU will map to the primary and secondary DNS server from that request.
If a DHCP address cannot be obtained after 90 seconds, the PDU can: (1) optionally fall back to its static
IPv4 and/or IPv6 settings, or (2) indefinitely wait to acquire an address based on DHCP configuration settings.
8
•
Introduction Smart POPS PDU
Installation and Operations Manual
Viewing Network Status
You can obtain the IPv6 network status through the firmware Web Interface or Command Line Interface (CLI). For the CLI, use the show network command as follows:
Smart CDU: show network
Network Settings
State: DHCP IPv6/IPv4 Network: Dual IPv6/IPv4
Link: Up Negotiation: Auto
Speed: 100 Mbps Duplex: Full
AutoCfg IPv6: FE80::20A:9CFF:FE52:4104/64
IPv6 Address: FD01::1:B51A:E03C/64
IPv4 Address: 10.1.6.230 Subnet Mask: 255.255.0.0
IPv4 Gateway: 10.1.1.1
DNS1: FD01::A01:585
DNS2: 10.1.5.133
Static IPv4/IPv6 Settings
IPv6 Address: FD01::A01:353/64
IPv6 Gateway: ::
IPv4 Address: 10.1.2.253 Subnet Mask: 255.255.0.0
IPv4 Gateway: 10.1.1.1
DNS1: 10.1.5.133
DNS2: 10.1.5.134
DHCP Settings
DHCP: Enabled
FQDN: Enabled [sentry3-524104]
Boot Delay: Enabled
Static Fallback: Enabled
Network Services
Telnet: Enabled Port: 23
SSH: Enabled Port: 22 Auth: Password, Kb-Int
HTTP: Enabled Port: 80
SSL: Enabled Port: 443 Installed Cert: User Encrypted
Access: Optional Stored Files: Cert & Key
User Cert: Enabled User Passphrase: <set>
SNMPv1/2: Enabled Port: 161 TrapPort: 162
SNMPv3: Disabled Port: 161 TrapPort: 162
FTP Server: Enabled Port: 21
SPM Access: Enabled
Command successful
NOTE : The fields IPv4 Address, IPv4 Subnet Mask, IPv4 Gateway, DNS1, and DNS2 are equivalent to existing PDU IPv4 settings except current network settings and static settings are displayed separately. This allows you to view both static configuration settings and active network settings that can be obtained using DHCP. The DNS addresses may be in IPv4 or IPv6 (based on RFC4291) format at this time.
Smart POPS PDU
Installation and Operations Manual Introduction
•
9
Chapter 2: Installation
Before installing your Smart POPS Rack Power Distribution Unit (PDU) refer to the following lists to make sure you have all the items shipped with the unit, as well as other items needed for proper installation.
Standard Accessories
Mounting Hardware
Vertical Models:
Button mounting kit with M4 screws.
Horizontal Models:
Two removable L-brackets with four M4 screws.
Expansion Models:
RJ12 to RJ12 crossover cable.
Additional Items for Models with C20 Inlets
•
Separate power input (typically sold as a separate line item).
•
Optional power input retention bracket hardware (can be installed); two removable T-brackets with two 40 mm screws per input.
Note: This bracket is not compatible with Server Technology Input Power Cords with the self-locking C19 feature. These power cords have the prefix PTCORD-L#.
Optional Accessories
•
Temperature/humidity sensors (Part Number EMTH-1-1).
•
Environmental monitor (Part Number EMCU-1-1B).
•
Vertical mounting brackets; additional mounting options are available in the Accessories section of the
Server Technology website at www.servertech.com
.
Additional Required Items
•
Flathead and Phillips screwdrivers.
•
Screws, washers, and nuts to attach the PDU to your equipment rack.
10
•
Installation Smart POPS PDU
Installation and Operations Manual
Safety Precautions
This section contains important safety and regulatory information that must be reviewed before installing and using the Smart POPS PDU.
Only for installation and use in a
Restricted Access Location in accordance with the following installation and use instructions.
This equipment should only be installed by trained personnel.
This equipment is designed to be installed on a dedicated circuit.
The power supply cord shall be a minimum of 1.5m (4.9ft) and a maximum of 4.5m (15ft). If using an extension power cord, the total length shall also be no more than the maximum allowed. The plug is considered the disconnect device and must be easily accessible.
The dedicated circuit must have circuit breaker or fuse protection.
PDUs have been designed without a master circuit breaker or fuse to avoid becoming a single point of failure. It is the customer’s responsibility to provide adequate protection for the dedicated power circuit. Protection of capacity equal to the current rating of the PDU must be provided and must meet all applicable codes and regulations. In North America, protection must have a 10,000A interrupt capacity.
Models with unterminated power cords: Input connector must be installed by qualified service personnel. Input connector rating must meet all applicable codes and regulations.
Destiné à l'installation et l'utilisation dans le cadre de Restricted Access Location selon les instructions d'installation et d'utilisation.
Cet équipement est uniquement destiné
à être installé par personnel qualifié.
Cet équipement a été conçu pour être installé que un circuit dédié. Le cordon d’alimentation doit être d’au moins 1,5M et un maximum de 4,5m. Si vous utilisez un cordon de rallonge, la longueur totale est
également plus que le maximum autorise.
La prise est considérée comme un dispositif de coupure et doit être facilement accessible.
Le circuit spécialisé doit avoir un disjoncteur ou une protection de fusible. PDUs ont été conçus sans disjoncteur général ni fusible pour éviter que cela devient un seul endroit de panne. C’est la responsabilité du client de fournir une protection adéquate pour le circuit-alimentation spécialisé. Protection de capacité équivalant à la puissance de l'équipement, et respectant tous les codes et normes applicables. Les disjoncteurs ou fusibles destinés à l'installation en Amérique du Nord doivent avoir une capacité d'interruption de 10.000 A.
Modèles avec cordons d'alimentation non terminées: Le connecteur d’entrée doit être installé par un personnel qualifié. Entrée cote de raccordement doit respecter tous les codes et règlements électriques applicables.
Do not block venting holes when installing this product. Allow for maximum airflow at all times.
Installation Orientation: Vertical units are designed to be installed in vertical orientation.
Always disconnect the power supply cord before servicing to avoid electrical shock. For products with two input power cords, both must be disconnected before servicing.
WARNING! High leakage current!
Earth connection is essential before connecting supply!
WARNING! Cx-xxE-x units double pole/neutral fusing
ATTENTION! Observe precautions for handling Electrostatic Sensitive
Devices.
Products rated for 240/415VAC may be fitted with a plug that is rated for a higher voltage. Caution must be taken to assure that the rating of the unit and the supply voltage match.
Ne bloquez pas les orifices d'aération lors de l'installation de ce produit. Permettre une circulation d'air maximale à tout moment.
Installation Orientation: Les unités vertical sont conçues pour être installées dans une orientation verticale.
Toujours débrancher le cordon d'alimentation avant de l'ouverture pour
éviter un choc électrique . Pour les produits avec deux cordons d'alimentation d'entrée, les deux doivent être déconnectés avant l'entretien.
ATTENTION! Haut fuite très possible! Une connection de masse est essentielle avant de connecter l’alimentation !
ATTENTION! Les unités Cx-xxE-x Double
Pôle/Fusible sur le Neutre
Attention ! Respecter les mesures de sécurité en manipulant des dispositifs sensibles aux décharges électrostatiques.
Les produits prévus pour 240/415VAC peut
être équipé d'un bouchon qui est conçu pour une tension plus élevée. Des précautions doivent être prises pour assurer que la cote de l’unité et la tension d’alimentation correspond.
Nur für Installation und Gebrauch in eingeschränkten Betriebszonen gemäß der folgenden Installations-und
Gebrauchsanweisungen.
Dieses Gerät ist nur für den Einbau durch Personal vorgesehen.
Die Geräte sind für eine Installation an einer fest zugeordneten Leitung ausgelegt.
Die Stromzuleitung hat eine Mindestlänge von 1,5m, und hochstens 4,5m. Sollten Sie ein Verlangerrungsnetzkabel, der
Gesamtlange auch nicht mehr als die maximal zulassige sein. Der Stecker dient zur Trennung vom Netz und muss einfach erreichbar sein.
Der feste Stromkreis muss mit einem
Schutzschalter oder einem
Sicherungsschutz versehen sein. PDUs verfügt über keinen Hauptschutzschalter bzw. über keine Sicherung, damit kein einzelner Fehlerpunkt entstehen kann. Der
Kunde ist dafür verantwortlich, den
Stromkreis sachgemäß zu schützen. Der
Kapazitätsschutz entspricht der aktuellen
Stromstärke der Geräte und muss alle relevanten Codes und Bestimmungen erfüllen. Für Installation in Nordamerika müssen Ausschalter bzw. Sicherung über
10.000 A Unterbrechungskapazität verfügen.
Modelle mit nicht abgeschlossenen
Netzkabel : Der Eingangsstecker darf nur von qualifiziertem Wartungspersonal installiert werden. Eingangsanschluss
Bewertung müssen alle geltenden und verbindlichen Normen und Vorschriften entsprechen.
Achten Sie darauf, dass keine
Belüftungslöcher bei der Installation dieses
Produkts. Damit für maximalen Luftstrom zu allen Zeiten.
Installationsausrichtung: Vertical Einheiten sind zur vertikalen Installation vorgesehen.
Trennen Sie das Netzkabel, bevor Sie
Wartungsarbeiten Öffnung einen elektrischen Schlag zu vermeiden . Für
Produkte mit zwei Eingangsstromkabel, sowohl, müssen vor der Wartung abgeschaltet werden.
ACHTUNG! Hoher Ableitstrom! Ein
Erdungsanschluss ist vor dem Einschalten der Stromzufuhr erforderlich!
ACHTUNG!: Cx-xxE-x Zweipolige bzw.
Neutralleiter-Sicherung
Achtung! Vorsichtshinweise zur
Handhabung elektrostatisch empfindlicher
Geräte beachten.
Produkte die für 240/415VAC zugelassen sind können mit einem Stecker der für eine höhere Spannung ausgestattet sein.
Vorsicht ist geboten, um sicherzustellen, dass die erlaubten Betriebswerte des
Gerätes und der Versorgungsspannung zueinander passen.
Smart POPS PDU
Installation and Operations Manual Installation
•
11
Input Power Cord Retention Options for PDUs with IEC C20 Inlets
Determine which Detachable Input Cord was supplied with the PDU:
•
For the following Detachable Input Cords with the self-locking
IEC C19 feature, follow Procedure A below .
PTCORD-L1, PTCORD-L2, PTCORD-L3, PTCORD-L5, PTCORD-L6, or
PTCORD-L7.
•
For the following Detachable Input Cords, follow Procedure B below .
PTCORD-1, PTCORD-2, PTCORD-3, PTCORD-4, PTCORD-5, PTCORD-6, or PTCORD-7.
Procedure A
If the PDU was supplied with a Detachable Input Power Cord with a self-locking IEC C19, install it directly into the
C20 inlet.
1.
Verify the Retention Bracket Assembly (part number KIT-0016) is not installed. a.
If KIT-0016 is installed, remove the two screws attaching the bracket to the IEC 60320 C20 inlet to the enclosure. b.
Remove the Retention Bracket Assembly. c.
Re-attach the two screws to the IEC C20 and securely tighten.
Push the C19 from the Detachable Input Cord firmly into the C20 inlet to ensure it is properly seated
C20 Inlet without Retention Bracket Assembly KIT-0016, Retention Bracket Assembly
Procedure B
If the PDU was supplied with a Detachable Input Power Cord without the self-locking C19 feature, install with the
Retention Bracket Assembly (part number KIT-0016), followed by the power cord.
1.
Remove the two screws attaching the IEC 60320 C20 inlet to the enclosure.
2.
Assemble and attach the Retention Bracket to the enclosure as shown
3.
Connect the power cord. Ensure the C19 is fully seated against the C20 inlet. (It may be necessary to loosen some of the Retention Bracket Assembly screws to allow the C19 plug to be properly installed.)
4.
Tighten the Retention Bracket Assembly to restrain the power cord.
12
•
Installation Smart POPS PDU
Installation and Operations Manual
Attaching Safety Earth Ground Connection
Server Technology PDUs are supplied with an external safety ground connection to provide an alternate ground path for fault currents, and to maintain the same ground reference between it and the equipment rack.
NOTE: The auxiliary external ground location may vary. Most PDUs will have it located near the power cord entry located near the symbol.
User-supplied materials:
•
One 5 mm internal (or external) tooth star washer;
•
One 4.0 mm
2
(10 AWG) wire with 5 mm ring terminal;
•
One metric M5 x 6 mm coarse pitch screw.
Instructions:
1.
Connect one end of the ground wire to the equipment cabinet or local ground.
2.
Locate the PDU external ground near the symbol.
3.
Connect the other end with a ring terminal and a M5 screw to the PDU external ground. To ensure proper grounding to the chassis, use a star washer between the ring terminal and the PDU.
Smart POPS PDU
Installation and Operations Manual Installation
•
13
Mounting the PDU
The following illustration shows how to mount the Smart POPS PDU in vertical or horizontal orientation:
Horizontal/Rack
1.
Select the appropriate bracket mounting points for proper mounting depth within the rack.
2.
Attach the L-brackets to these mounting points with two screws for each bracket.
3.
Install the enclosure into your rack, using the slots in each bracket. The slots allow about 6 mm (0.25 inch) of horizontal adaptability to align with the mounting holes of your rack.
Vertical
The Switched PDU is supplied with button mounting kit(s). Distribute the buttons vertically and attach to the PDU as
appropriate for the cabinet. An additional 19 mm (0.75 inch) of clearance is required at the top of the PDU to allow the
button to mount into the keyholes.
Note: For more information about horizontal/vertical mounting options for the Switched PDU, see the
Server Technology website www.servertech.com
or contact your Power Strategy Expert.
14
•
Installation Smart POPS PDU
Installation and Operations Manual
Attaching the Expansion Module
If supported, connect the linking unit with the provided RJ12 crossover cable at the Link port on the Smart POPS
PDU.
NOTE: The overall length of the RJ12 crossover cable should not exceed 14 feet (4.3 m).
Connecting to the Power Source
On 30A units, the input power cord is attached to the base of the unit. On units with a total maximum output <30A, you must first attach the power cord to the unit before connecting the unit to the power source.
To attach a power cord to the unit:
1.
Plug the female end of the power cord firmly into its connector at the base.
2.
Use a screwdriver to tighten the two screws on the retention bracket.
To connect to the power source:
Plug the male end of the power cord into the AC power source.
Connecting Devices
To avoid the possibility of noise due to arcing:
1.
Keep the device’s on/off switch in the off position until after it is plugged into the outlet.
2.
Connect devices to the PDU outlets.
NOTE: Server Technology recommends even distribution of attached devices across all available outlets to avoid exceeding the outlet, branch or phase limitations. More information is provided in the Power Ratings section.
Always disconnect ALL power supply cords before opening to avoid electrical shock.
Afin d’éviter les chocs électriques, débranchez TOUTES les cables électrique avant d’ouvrir.
Vor dem Offnen immer Netzleitungen abziehen um elektrischen Schlag zu vermeiden.
Connecting the Sensors
The Smart POPS PDU is equipped with two mini RJ11 T/H ports for attachment of the Temperature/Humidity sensors. Attach the mini RJ11 plug of the sensor(s) to the appropriate T/H port.
Connecting to the Unit
Serial (RS232) port
The Smart POPS Cabinet Distribution Unit is equipped with an RJ45 Serial RS-232 port for attachment to a PC or networked terminal server using the supplied RJ45 to RJ45 crossover cable and RJ45 to DB9F serial port adapter as required. For more information about the serial RS-232 port, see the “Data Connections” section in Appendix C:
Technical Specifications.
Ethernet port
The Smart POPS Cabinet Distribution Unit is equipped with an RJ45 10/100Base-T Ethernet port for attachment to an existing network. This connection allows access to the Smart POPS PDU via Telnet or Web.
The following network defaults are integrated with the Smart POPS PDU to allow unit configuration out-of-the-box through either Telnet or Web:
•
IP address:
•
Subnet Mask:
192.168.1.254
255.255.255.0
•
Gateway: 192.168.1.1
The local PC network connection must be configured as noted below:
NOTE: Contact your system administrator for instructions in reconfiguring the network connection. Reconfiguration of your network connection may require a restart to take effect.
•
IP address: 192.168.1.x (where x is 2-253)
•
Subnet Mask: 255.255.255.0
Smart POPS PDU
Installation and Operations Manual Installation
•
15
Chapter 3: Operations
Interfaces
The Smart Cabinet Distribution Unit has two interfaces: the Web interface accessed via the HTTP enabled Ethernet connections, and the command line for serial and Telnet connections.
Usernames and Passwords
The Smart POPS Cabinet Distribution Unit has one predefined administrative user account (username/password: admn/admn), and supports a maximum of 112 defined user accounts.
NOTE: For security, Server Technology recommends removal of the predefined administrative user account after a new account with administrative rights has been created.
Only an administrative-level user may perform operations such as creating/removing user accounts and command privileges, changing passwords and displaying user information. An administrator may also view the status of all sensors and power inputs.
Usernames may contain from 1-16 characters and are not case sensitive; spaces are not allowed. Passwords may contain up to 16 characters, and are case sensitive.
Web Interface
The Web Interface provides web-based access to the firmware. The interface is designed with three major sections, illustrated below.
1.
System Header: Shows PDU description and location, IP address, and user/ access information.
2.
Navigation Bar: Provides access to PDU configuration, control action, or status page.
3.
Details Window: Current control/status information based on the page selected from the navigation bar.
NOTE: The blinking of the PDU location string (IP address) in the System Header section may not work with all web browsers.
This example shows the Power Monitoring > Input Feeds page:
Example of Firmware Web Interface for the Smart POPS PDU
18
•
Operations Smart POPS PDU
Installation and Operations Manual
Logging In
Logging in through the Web requires directing the Web client to the configured IP address of the unit.
To log in the Web interface:
In the login window, enter a valid username and password and press OK .
If you enter an invalid username or password, you will be prompted again.
You are given three attempts to enter a valid username and password combination. If all three fail, the session ends and a protected page will be displayed.
NOTE: The default username/password is admn/admn .
System Summary
The System Summary is typically displayed as the default page at user login to the firmware Web Interface. If you do not have environmental monitor access for a PDU, your default page at login will be the Outlet Control page (shown in the previous screen capture).
Both the System Summary page and the Outlet Control page display automatically at login and do not require enabling.
The System Summary page contains general system, line, humidity, and temperature status information. The colorcoded sensor graphs shown in the example below provide a quick and efficient real-time view for monitoring environmental conditions in your PDU network.
Example of System Summary Page
The System Summary page displays precise current and system power consumption in your PDU network. Dynamic updates (without a full page refresh) allow you to assess critical system statistics with close to instantaneous feedback. This performance is useful for monitoring new installation or power distribution changes in high-density computing environments. Power system administrators can also quickly identify thermal and humidity concerns that might otherwise escalate into costly infrastructure repairs if left unchecked.
As long as the System Summary page is active, the sensor graphs are continually updating system statistics and threshold values. The data with the most impact on the system is displayed to reduce your analysis and troubleshooting time. You can quickly analyze and correct a PDU if a sudden operating condition affects your device network.
NOTE: Because the System Summary page continually requests updated status information from the PDU, the page does not time-out. You will need to navigate to another page or manually log off.
Smart POPS PDU
Installation and Operations Manual Operations
•
19
System Information
Uptime: Displays the cumulative time the PDU has been up and running since the last unit restarted. Uptime shows continuous, real-time system updates with an approximate 5-second automatic refresh. A manual refresh of the
System Summary page is not required.
Firmware Version: Shows the current firmware version.
Ethernet NIC S/N: Displays the PDU serial number derived from the Ethernet NIC.
Active Users: Displays the number of active user sessions accessing the firmware. These sessions include serial,
TELNET, SSH, and Web sessions. Active Users also shows sessions that an unauthorized user may be attempting to access. The number shown in Active Users changes instantly as the number of active user sessions change. A total of
4 concurrent web user sessions are allowed (HTTP or HTTPS).
NOTE: Depending on your web browser, multiple web accesses from the same machine are often treated as one user.
Total Power Consumption: Displays the total system power (in Watts) being distributed by the current Smart POPS
PDU configuration.
Line Status
The Line Status graph displays a blinking warning (yellow), whenever the total input load on an infeed exceeds the present user set threshold. If an overload occurs, a blinking error condition (red) is displayed. The unit continues to display these yellow and red states until the condition changes or the problem has been resolved.
The default input feed high load threshold is 80% of the input feed maximum load capacity.
NOTE: The input feed high threshold is user-defined. You must configure this threshold value on the SNMP/Thresholds page or the
Command Line Interface (CLI).
Temperature Status
The Temperature Status graph displays a blinking error whenever temperature exceeds the low or high threshold. The
PDU will continue to display this state until the condition changes or the problem has been resolved.
For the temperature sensor, the default range of low/high temperature values is 5º-45º C (41º-115º F).
Up to four sets of dual temperature/humidity sensors can be displayed in this graph for a total of eight possible temperature sensor graphs. A thin blue line separates each set based on the tower or environmental monitor.
NOTE: The temperature threshold values are user-defined. You must configure these threshold values on the SNMP/Thresholds page or the
Command Line Interface (CLI).
Humidity Status
The Humidity Status graph displays a blinking error whenever humidity exceeds the low or high threshold. The PDU will continue to display this state until the condition changes or the problem has been resolved.
For the humidity sensor, the default range of low/high humidity percentage is 0-100% (relative humidity).
Up to four sets of dual temperature/humidity sensors can be displayed in this graph for a total of eight possible humidity sensor graphs. A thin blue line separates each set based on the tower or environmental monitor.
NOTE: The humidity threshold values are user-defined. You must configure these threshold values on the SNMP/Thresholds page or the
Command Line Interface (CLI).
Field Descriptions
The following fields and icons are viewed left to right for Line Status, Temperature Status, and Humidity Status:
Icon: Provides quick viewing of current operational state: Information , Warning and Critical .
ID: Device input feed or sensor identifier.
Name: Descriptive, user-defined name for each input infeed or sensor.
Load, Temp, Humidity: Current state of the reported input load (in amps), current temperature, or current percentage of relative humidity.
Low Limit: Displays the user-defined low limit of the load, temperature, or humidity graph. These values depend on the sensor limited and cannot be set by the user. For example, a 0ºC low limit would be displayed as temperature sensor graph in Celsius.
for a
20
•
Operations Smart POPS PDU
Installation and Operations Manual
Sensor Graph and Level Indicator: The horizontal sensor graph shows current operating conditions in color-coded segments. See the section below, “Sensor Graph Color-Coding”, for details. The level indicator
appears across the graph to indicate the relative position of the current data value with respect to the minimum (low limit) and maximum
(high limit) values displayed at the left and right of the graph.
High Limit: Displays the high limit of the load, temperature, or humidity graph. These values depend on the sensor limits are cannot be set by the user. For example, a 100ºC high limit would be displayed as sensor graph in Celsius.
for a temperature
Status: One of several operating conditions:
System Summary – Status Descriptions
Icon Status Description
Reading
Normal
Load High
Over Load
Temp Low
Temp High
Humid Low
Humid High
Unit is reading a new or restored sensor.
Indicates normal operation.
Infeed current load exceeds present High threshold.
Infeed current load exceeds the measurable range for the infeed.
Current temperature falls below present Low threshold.
Current temperature exceeds present High threshold.
Current percentage of relative humidity falls below present Low threshold.
Current percentage of relative humidity exceeds present High threshold.
Lost The connection was lost to a sensor that was previously detected and the sensor is pulled from the original environment monitoring statistics. There is no data to report, the graph is meaningless, and the threshold settings remain displayed but are grayed.
Sensor Graph Color-Coding
The following colors change dynamically on the sensor graphs to communicate operating conditions:
Line (Load) Status:
Green = Normal
Yellow = High load (load configured by user)
Red = Overload (based on device characteristics)
User configures load capacity at Configuration > SNMP/Thresholds > Input Feed Traps and Thresholds
Temperature Status:
Blue = cold; low temperature (threshold configured by user)
Green = acceptable temperature range
Red = hot; high temperature (threshold configured by user)
User configures low/high temperature thresholds at Configuration > SNMP/Thresholds > Sensor Traps and
Thresholds
Humidity Status:
Blue = wet; high humidity (threshold configured by user)
Green = acceptable percentage of relative humidity
Yellow = dry; low humidity (threshold configured by user)
User configures low/high relative humidity thresholds at Configuration > SNMP/Thresholds > Sensor Traps and
Thresholds
Smart POPS PDU
Installation and Operations Manual Operations
•
21
Logical Group Separators
Logical groups are separated by a thin blue line on the System Summary page as shown in the following example between Tower A_InfeedA and Tower B_InfeedA:
This grouping includes master/link units in addition to some branched units. Up to three blue line dividers can be displayed on the System Summary page between all sensor groups.
Power Monitoring
NOTE: The following web interface examples show a Per Inlet Power Sensing (PIPS
) enabled Smart POPS
PDU. PIPS
provides power monitoring per infeed/inlet to the PDU to monitor (as data displayed in the following interface examples) current, voltage, power (W), apparent power, crest factor, reactance, power factor, and accumulated energy (kWh).
Outlets
The Outlets page displays:
•
The absolute and descriptive names of the outlet
•
Outlet status
•
POPS
•
outlet load in amperes.
POPS outlet voltage
•
POPS outlet active power in watts
The POPS (Per Outlet Power Sensing) technology combines all of the features and functions of a Smart PDU with the ability to provide power monitoring per an individual outlet/device.
For operational details about an outlet, click the Details link next to a specific outlet on the far right of the page.
22
•
Operations Smart POPS PDU
Installation and Operations Manual
The following outlet details page displays:
Power information per individual outlet/device includes current load (A), voltage (V), power (kW), apparent power
(VA), crest factor, and power factor shown above on the Details page.
The Outlets page and Outlet Details page will refresh automatically every 10 seconds.
Input Feeds
The Input Feeds page displays:
•
The absolute and descriptive names of the infeed
•
Infeed status
•
Input/branch phase load in amperes
•
Input voltage
•
Calculated power usage in watts
NOTE: For 3-phase systems, if the Out-of-Balance Alerting feature is enabled, and the system goes into a load out-of-balance condition, the Tower Status field will display the alert “3ph Out-of-Balance”, unless there is a higher priority tower error state to report.
Monitor pages (like the Input Feeds page) refresh occasionally to reflect current PDU status.
Smart POPS PDU
Installation and Operations Manual Operations
•
23
System
The System page displays:
•
Calculated power usage for all infeeds in Watts
•
Configured total system area in square feet
•
•
Calculated power usage in Watts/square foot
Tower monitoring – tower ID, tower name, and tower status
NOTE: For 3-phase systems, if the Out-of-Balance Alerting feature is enabled, and the system goes into a load out-of-balance condition, the Tower Status field will display the alert “3ph Out-of-Balance”, unless there is a higher priority tower error state to report.
Monitor pages (like the System page) refresh occasionally to reflect current PDU status.
24
•
Operations Smart POPS PDU
Installation and Operations Manual
UPS
The UPS page displays the following information for each UPS device associated with the Smart POPS PDU unit:
•
Status
•
Voltage
•
Hostname/IP address
NOTE: The UPS page displays both IPv4 and IPv6 formats in the Hostname/IP field.
Monitor pages (like the UPS page) refresh occasionally to reflect current PDU status.
Environmental Monitoring
Sensors
The Sensors page displays:
•
The absolute and descriptive names of the temperature/humidity sensors
•
Temperature/humidity sensor readings and percentage of relative humidity
Monitor pages (like this Sensors page) refresh occasionally to reflect current PDU status.
Temperature/Humidity Sensor Status
Status
Found
Not Found
Lost
Description
The PDU found the sensor and connection is established.
On a fresh reboot, the PDU does not find a sensor.
The connection to a previously found sensor is now lost.
No Comm Communication loss occurred due to a hardware issue (not loss of communication with the probes).
1
1 = The ENV part of the sensor supports two Temperature/Humidity (T/H) probes as part of the master unit, two T/H probes as part of the link unit, and the optional EMCU-1-1 (which can support two T/H probes, four contact-closure monitoring points, and one water sensor). The “No Comm” sensor status is not loss of communication with probes themselves.
Smart POPS PDU
Installation and Operations Manual Operations
•
25
Contacts
The Contacts page displays:
•
The absolute and descriptive names of the contact closure
•
Contact closure status
Monitor pages (like this Contact Closure page) refresh occasionally to reflect current PDU status.
ADCs
The Analog-to-Digital Converters (ADCs) page displays:
•
The absolute and descriptive names of the ADC
•
The ADC count
Monitor pages (like this ADCs page) refresh occasionally to reflect current PDU status.
26
•
Operations Smart POPS PDU
Installation and Operations Manual
Configuration
The Configuration section offers access to all unit configuration options. This section is available to administrative level users only.
System
The System configuration page is used for reference of system information such as Ethernet NIC Serial Number,
Ethernet MAC address and system firmware and hardware revisions as well as assignment and maintenance of other system wide configurations.
For descriptive names, enter up to 24 alphanumeric and other typed characters - (ASCII 33 to 126 decimal) are allowed; spaces are not allowed.
NOTE: Spaces may be used for the location description only.
Creating a pre-login banner:
Click the Login Banner link. On the subsequent Login Banner page, type pre-login banner text and click Apply .
NOTES:
•
The pre-login banner can be up to 2069 characters in length and is displayed prior to the login prompt. If left blank, a system banner will
not be displayed prior to the login prompt.
•
For an SSH connection, the banner length is truncated to 1500 bytes in SSH packets to avoid failure of the SSH connection when
configured with a long login banner.
The Login Banner displays the following Characters Remaining box to show you in real-time as you type how many of the 2069 maximum characters are still available for you to complete your banner. The box adjusts dynamically as you type or delete characters.
If you reach the maximum 2069 characters, the box displays “-1”. To clear your entry and start over, press
Cancel .
Creating a descriptive system location name:
Enter a descriptive name and click Apply .
Smart POPS PDU
Installation and Operations Manual Operations
•
27
Configuring the LED display orientation:
From the Display Orientation drop-down list, select Normal or Inverted, and click Apply .
NOTES:
•
Only specific PDU models are equipped with an accelerometer chip that senses device orientation. If equipped, your PDU automatically
aligns the LED display orientation (depending on its current direction), and the option “Auto” displays in the Display Orientation
drop-down list by default. In addition, the actual mounting of the unit, such as “<Normal> or <Inverted>”, appears to the right of
the "Auto" option. However, even if your PDU model does have the sensor for device orientation, you can still select the Normal or
Inverted option from the list to override the capability of the hardware.
•
If your PDU model does not have the accelerometer chip, you will need to configure the LED display orientation by selecting Normal or
Inverted.
Enabling or disabling strong password requirements:
The Smart POPS PDU supports enforcement of strong passwords for enhanced security. When enabled, all new passwords must be a minimum of 8 characters in length with at least one uppercase letter, one lowercase letter, one number and one special character.
Acceptable strong passwords: n0tOnmyw@tch john2STI?
H3reUgo!
NOTE: Strong password requirements also enforce a minimum change of four character positions when defining new strong passwords.
Select Enabled or Disabled from the Strong Passwords drop-down menu and click Apply .
NOTE: The strong password requirement is applied against all new passwords.
Enabling or disabling the configuration reset button:
Select Enabled or Disabled from the Configuration Reset Button drop-down menu and click Apply .
Setting the system area (footprint):
Enter a system area value in the Area (Footprint) field and click Apply .
Setting the system area unit of measure:
Select Square Feet or Square Meters from the Area (Footprint) drop-down menu and click Apply .
Setting the power factor:
The Power Factor value calculates the power usage displayed in the Power Monitoring pages.
Type a numeric value in the Power Factor field (from 0.50 to 1.00) and click Apply .
Setting the 3-phase load out-of-balance threshold:
The threshold (percentage) specified determines when the current on the lines of a 3-phase system are out-of-balance between the three phases of power. If the alerting feature is enabled, an alert will be sent when an out-of-balance condition occurs.
In the 3-Phase Load Out-of-Balance Threshold field, type a value from 0 to 100%, and click Apply .
Setting the 3-phase load out-of-balance alerting:
This setting enables/disables the sending of an alert when the current on the lines of a 3-phase system are past a pre-set threshold (percentage) and are out-of-balance between the three phases of power.
From the 3-Phase Load Out-of-Balance Alerting drop-down menu, select Enabled or Disabled , and click Apply .
NOTES:
•
When a device with 3-phase input voltage is out-of-balance, efficiency is reduced and the unit is prevented from reaching maximum
capacity. When an alert for the out-of-balance condition is received (if the alerting feature is enabled), it may be necessary to adjust
distribution of the loads.
•
For 3-phase systems, if the Out-of-Balance Alerting feature is enabled, and the system goes into a load out-of-balance condition, the
Tower Status field on the “Power Monitoring – System” web page will display the alert “3ph Out-of-Balance”, unless there is a higher
priority tower error state to report.
28
•
Operations Smart POPS PDU
Installation and Operations Manual
Setting the temperature scale:
Select Celsius or Fahrenheit from the Temperature Scale drop-down menu and click Apply .
Setting the system area:
Enter a system area value in the Area field and click Apply .
Setting the system area unit of measure:
Select the unit of measure from the Unit of Measure drop-down list and click Apply .
Setting the system input power factor:
The Power Factor value is used to provide calculated power usage displayed in the Power Monitoring pages.
Enter a numeric value in the Power Factor field from 0.50 to 1.00, and click Apply .
Setting the 3-phase load out-of-balance threshold:
This setting is used for devices with 3-phase input voltages to notify of a system imbalance between the three phases of power.
In the 3-Phase Load Out-of-Bounds Threshold field, enter a value from 0 to 100% and click Apply .
Configuring the Command Line Interface (CLI) session timeout:
Enter a timeout period (in minutes) in the CLI Session Timeout field, and click Apply . The valid timeout range is 1 to
1440 minutes (24 hours); the default is 5 minutes.
Configuring the web session (Web Interface) timeout:
Enter a timeout period (in minutes) in the Web Session Timeout field. The valid timeout range is 1 minute to 1440 minutes
(24 hours); the default web session timeout is 5 minutes.
Enabling/Disabling StartUp Stick
:
StartUp Stick is a Server Technology tool for mass configuration of PDU operating parameters.
Select Enabled or Disabled from the StartUp Stick drop-down menu and click Apply .
Creating a descriptive unit name:
Click on the Tower Names link.
On the subsequent Tower Names page, enter a descriptive name and click Apply .
Creating a descriptive input feed name:
Click on the Input Feed Names link.
On the subsequent Input Feed Names page, enter a descriptive name and click Apply .
Creating a descriptive serial port name:
Click the Serial Port Names link to open the Serial Ports configuration page. For more information about creating descriptive serial port names, see the “Serial Ports” section.
Creating a descriptive environmental monitor name:
Click on the Environmental Monitor Names link.
On the subsequent Environmental Monitor Names page, enter a descriptive name and click Apply .
Creating descriptive sensor names:
Click on the Sensor Names link.
On the subsequent Sensor Names page, enter a descriptive name and click Apply .
Creating analog-to-digital converter names:
Click on the ADC Names link.
On the subsequent ADC Names page, enter a descriptive name and click Apply .
Smart POPS PDU
Installation and Operations Manual Operations
•
29
Network
The Network configuration page allows the administrator to maintain the network interface by determining IPv6 and
IPv4 status, network state, IP address, gateway, subnet mask, primary/secondary DNS addresses, and the necessary settings and options for DHCP.
NOTE: For maximum backward compatibility, the default network mode is “IPv4 only”.
Network:
The Network drop-down menu determines the acquisition method used for the protocol stack, IPv4 address, and IPv6 address. From the Network drop-down menu, select the acquisition method for your network (Disabled, IPv4 only, or
Dual IPv6/IPv4), and click Apply .
State:
The view-only State field shows the current IPv6/IPv4 network status and can display any of the following values:
Current Network States
•
Acquiring
•
DCHP IPv4
•
IPv4 Failed (Static IPv4 problem)
•
Static IPv6
•
Disabled
•
Disconnected
•
DCHP IPv6
•
DCHP IPv6/IPv4 (both available)
•
IPv6 Failed (Static IPv6 problem)
•
Static IPv4
•
Static IPv6/IPv4 (both available)
•
Unknown
Additional network communication values are displayed for viewing only: Link, Speed, Duplex, and Negotiation. Also displayed for viewing are the IPv6 and IPv4 IP address, subnet mask, gateway, and primary/secondary DNS addresses.
Setting the IPv6 or IPv4 static IP address, gateway, subnet mask, or DSN address:
In the appropriate fields, type the IP address, gateway, subnet mask, or DNS address, and click Apply .
NOTE: IPv6 address formats are accepted in the IPv6 Address field and IPv6 Gateway field. IPv4 formats are accepted in the IPv4-named
Address, Subnet Mask, and Gateway fields.
30
•
Operations Smart POPS PDU
Installation and Operations Manual
Enabling Dynamic Host Configuration Protocol (DHCP):
To enable DHCP, check the Enable checkbox. To disable DCHP, uncheck (clear) the checkbox. Click Apply .
Setting the fully-qualified domain name (FQDN):
To enable FQDN, check the Enable checkbox and accept the default name “sentry3-521384” (or type a different name). To disable the FQDN, uncheck the checkbox.
Click Apply .
Enabling the DHCP boot delay:
To enable the boot delay, check the Enable checkbox. To disable the boot delay, uncheck (clear) the checkbox.
Click Apply .
•
Enabling the Boot Delay option gives the PDU approximately 100-seconds to establish a connection through a
DHCP server. This interval allows various network component activities to occur as the PDU powers up (such as obtaining SNTP time stamps for logging). This is the default state.
•
Disabling the Boot Delay option forces the PDU to boot after approximately 5-seconds regardless of the
DHCP acquisition state. This speeds up a boot when a DHCP server is connected to one of the outlets in the
PDU. In this configuration, SNMP traps, SNTP, and other protocols will not be available until a DHCP address has been resolved.
NOTES:
•
The Boot Delay option executes only when DHCP is enabled.
•
The firmware can detect network link integrity and will wait for network connection. This means that if the network is not currently
connected, the enabled Boot Delay option will be ignored.
Enabling static address fallback:
NOTE: The Static Address Fallback option executes only when DHCP is enabled.
To enable static address fallback, check the Enable checkbox. To disable, uncheck (clear) the checkbox.
Click Apply .
•
Enabling the Static Address Fallback option informs the PDU to automatically fall back to a static address if a DHCP server does not respond after 100-seconds. This is the default state.
•
Disabling the Static Address Fallback option generates DHCP server requests until the PDU obtains a dynamic address.
NOTE: If the DHCP server boot time is excessive, you may need to disable the DHCP Static Address Fallback option.
Network defaults:
The Smart POPS PDU is configured with the following network defaults to allow unit configuration out-of-the-box through either Telnet or Web:
•
IP address:
•
192.168.1.254
Subnet Mask: 255.255.255.0
•
Gateway: 192.168.1.1
The initial local PC network connection must be configured as noted below:
NOTE: Contact your system administrator for instructions in reconfiguring the network connection. Reconfiguration of your network connection may require a restart to take effect.
•
•
IP address:
Subnet Mask:
192.168.1.x (where x is 2-253)
255.255.255.0
NOTE: The unit must be restarted after network configuration changes.
Setting the IP address, subnet mask, gateway or DNS address:
In the appropriate field, enter the IP address, subnet mask, gateway address or DNS address and click Apply .
Smart POPS PDU
Installation and Operations Manual Operations
•
31
Telnet/SSH
The Telnet/SSH configuration page used to enable or disable Telnet and SSH support and configure the port number that the Telnet or SSH server watches.
Enabling or disabling Telnet or SSH support:
Select Enabled or Disabled from the appropriate Server drop-down menu and click Apply .
Changing the Telnet or SSH server port number:
In the appropriate Port field, enter the port number and click Apply .
Enabling or disabling SSH server authentication methods:
The SSH server supports two authentication methods for security and validation: Password and Keyboard-Interactive.
Password is a method where the SSH client gathers username/password credentials and makes the authentication request to the SSH sever with the credentials. The Password method is controlled by the SSH client.
Keyboard-Interactive is an authentication method where the SSH server controls an information field followed by one or more prompts requesting credential information from the SSH client. The client gathers credential information keyed-in by the user and sends it back to the server. The Keyboard-Interactive method is controlled by the SSH server.
Individual enabling and disabling of the Password and Keyboard-Interactive authentication methods are supported to allow an SSH client to be forced to use a specific method. Although both methods are available, by enabling the
Keyboard-Interactive method and disabling the Password method, the SSH client is forced to used Keyboard-Interactive, which is required to display the login banner.
NOTE: At least one authentication method must be enabled.
Select the Password checkbox and/or the Keyboard Interactive checkbox and click Apply .
32
•
Operations Smart POPS PDU
Installation and Operations Manual
HTTP/SSL
The HTTP/SSL configuration page specifies settings that enable or disable HTTP and SSL support (including userdefined certificates), configures the port number that the HTTP server watches and responds to, determines the SSL access level, and sets options for the Sentry Power Manager (SPM) product.
Enabling or disabling HTTP or SSL support:
From the HTTP or SSL Server drop-down menu, select Enabled or Disabled and click Apply .
NOTE: SSL-encrypted (HTTPS) must be used for secure website connections.
Setting SSL secure access:
SSL allows either optional or required connections. The default secure access is optional.
•
•
Optional: Both non-secure (HTTP) and SSL-encrypted connections (HTTPS) are allowed access.
Required: Only SSL-encrypted connections (HTTPS) are allowed access.
From the Secure Access drop-down menu, select Optional or Required , and click Apply .
Changing the HTTP server or SSL port number:
In the HTTP or SSL section of the page, in the Port field, type the port number, and click Apply . The HTTP default port number is 80; the SSL default port number is 443.
Uploading a custom user certificate:
Enabling and disabling user certificates:
In the User Certificate drop-down menu, select Enabled. Provide a passphrase (0-47 characters) for the new certificate. To change the passphrase, type a new passphrase and check the Change checkbox.
Click Apply .
The Stored Files section displays a message to confirm upload status of the user certificate and its related public key.
Smart POPS PDU
Installation and Operations Manual Operations
•
33
Custom User Certificate Messages
Message
Cert & Key
Cert
No Cert
Factory Encrypted
None
Uploading the certificate:
Description and Valid Values/Range
Both the user certificate and its key were uploaded successfully.
User certificate was uploaded without a key.
User certificate was not uploaded.
User certificate was encrypted and uploaded at product assembly.
Neither the user certificate nor its key were uploaded.
NOTE: You can enable user certificates and provide a passphrase using either the firmware Web interface or the Command Line Interface
(CLI). However, the uploading of a custom user certificate can only be done using the Web interface – there are no equivalent commands for uploading user certificates.
To upload a user certificate, click the Upload link. The Upload window displays. Type the certificate filename (or key filename) and click the Upload button. The upload status is displayed in the Stored Files section as described above.
Removing a certificate:
To remove a user certificate, click the Remove link. A message displays to confirm the removal of the certificate.
34
•
Operations Smart POPS PDU
Installation and Operations Manual
Setting the Sentry Power Manager (SPM) options:
The Sentry Power Manager (SPM) is Server Technology’s enterprise management software product for the data center. The configuration options provided allow you to enable/disable SPM and reset the SPM password to its default.
NOTE: The SPM options apply only if you are currently using Server Technology’s SPM software.
SPM Secure Access:
If your operation does not currently use SPM software, you can disable SPM Secure Access. However, if disabled, the PDU will not be able to use the SPM suite of secure network capabilities or the advanced remote configuration.
Select Enabled or Disabled from the SPM Secure Access drop-down menu and click Apply .
NOTE: Both HTTP and SSL must be enabled or the SPM Secure Access option will not be permitted. When SPM Secure Access is permitted, the default is Enabled .
SPM Password:
Each PDU has a default unique SPM password that is used to communicate between SPM and the PDU. When SPM discovers a PDU in the network, SPM changes this password into a different unique password for added security. The
SPM then continues to manage or alter these passwords as required for system security.
If a PDU is relocated or swapped from the system after a password was generated, SPM may not be able to reestablish a connection to the unit. The Set SPM Reset Password command allows you to reset to the internal default password of the PDU so SPM can re-discover the device and add it to the system. Once the unit has been acquired by
SPM, no further action is necessary.
To reset the password, check SPM Password and click Apply .
NOTE: Do not reset the password if SPM communication has already been established.
Serial Ports
The Serial Ports configuration page is used for maintenance of the serial port.
NOTE: Pass-Thru connections may only be initiated from the command line interface via a Telnet/SSH session.
Smart POPS PDU
Installation and Operations Manual Operations
•
35
Setting the data-rate for all serial ports:
Select the serial port data-rate from the drop-down menu and click Apply .
Setting the serial port timeout value:
The Serial Port Timeout Value sets the serial port inactivity timeout period for individual ports. The timeout period defines the maximum period of inactivity before automatically closing the Pass-Thru session.
The valid range for the timeout is 0 to 60 (in minutes). The default timeout is 5 minutes. Setting the timeout value to
“0” disables the timeout.
Click the Edit link in the Action column next to the individual port to be configured.
Type the timeout minutes in the Connection Timeout field and click Apply .
Creating a descriptive serial port name:
Click on the Edit link in the Action column next to the port to be configured.
On the subsequent Serial Port Edit page, enter a descriptive name. Up to 24 alphanumeric and other typed characters (ASCII 33 to 126 decimal) are allowed; spaces are not allowed. Click Apply .
Enabling or disabling serial port active signal checking:
Click on the Edit link in the Action column next to the port to be configured.
On the subsequent Serial Port Edit page, select On or Off from the DSR Check drop-down menu and click Apply .
Enabling or disabling the Command Line Interface (CLI):
This option enables or disables availability of the CLI for issuing action commands to the PDU. If disabled, only the firmware Web user interface will be available.
Click on the Edit link in the Action column next to the port to be configured.
On the following Serial Ports Edit page, select Enabled or Disabled from the CLI drop-down menu and click Apply .
Enabling or disabling the Serial Command Protocol (SCP):
This option allows SCP functions to be enabled or disabled for a specific serial port.
Click on the Edit link in the Action column next to the port to be configured.
On the following Serial Ports Edit page, select Enabled or Disabled from the SCP drop-down menu and click Apply .
NOTES:
•
Upon a coldboot of the system, if the Coldboot Alert feature is enabled, the system will send a ½ second RS-232 break out to any
SCP-enabled serial ports.
•
The SCP option must be enabled to use the Bluetooth Android solution.
Enabling or disabling the Serial Command Protocol (SCP) emulation:
This option notifies SCP of an MRV device on a specific serial port.
Click on the Edit link in the Action column next to the port to be configured.
On the following Serial Ports Edit page, select None or MRV from the SCP Emulation drop-down menu and click
Apply .
Enabling or disabling the RFTAG option:
This option makes RF Code sensor tags available for the Server Technology wireless monitoring solution.
Click on the Edit link in the Action column next to the port to be configured.
On the following Serial Ports Edit page, select Enabled or Disabled from the RFTAG drop-down menu and click
Apply .
36
•
Operations Smart POPS PDU
Installation and Operations Manual
Configuring the Bluetooth™ options:
If the PDU has been equipped for the mobile monitoring solution using Bluetooth ® technology, and several Bluetooth parameters will be available for editing on the Serial Ports configuration page.
Click the Edit link in the Action column to configure the following parameters.
Provide a value as described for each parameter field, and click Apply .
Firmware Bluetooth Parameters
Parameter
Bluetooth Name
Description and Valid Values/Range
Descriptive name of the Bluetooth module that displays in the list of discovered modules on the Android device. The default module name is “ST Eye”. The name cannot be blank;
Valid range is 1-31 characters.
Bluetooth Discoverability Settings that determine the current status of the pushbutton on the Bluetooth module.
•
Always
– The Bluetooth module is discoverable, even without pressing the pushbutton.
•
Limited – (Default). The pushbutton on the Bluetooth module must be pressed to make
the module discoverable for 60-seconds.
•
Never – The Bluetooth module is never in discoverable mode.
Bluetooth Pin Code The pin code is available for legacy Bluetooth modules that require a pin to pair the module.
Although not used in current Bluetooth modules, the pin code is supported if needed.
Default is 9611; must be 4-digits; range is 0000 to 9999.
Bluetooth Transmission Power Designated transmission power (dbm) for the Bluetooth module. Note that lowering the
transmission power reduces the effective range of the module. Default is 0;
range is -6 to 4 dbm.
Towers
The Towers configuration page is used for assignment and/or editing of:
•
Descriptive names
•
Serial and Model numbers
•
Operation voltage types
NOTE: If set at the factory, you will not be able to edit the serial number, model number, and voltage type.
Creating a descriptive tower name:
In the Tower Name field, enter a descriptive name and click Apply .
Setting the tower serial number:
In the Serial Number field, enter the serial number of the unit and click Apply .
Setting the tower model number:
In the Model Number field, enter the model number of the unit and click Apply .
Setting the operational AC or DC voltage type:
From the AC/DC drop-down menu, select AC or DC , and click Apply .
Smart POPS PDU
Installation and Operations Manual Operations
•
37
Setting the operational AC voltage type:
From the 3-Phase drop-down menu, select yes or no , and click Apply .
Input Feeds
The Input Feeds configuration page is used for assignment and/or editing of input feed descriptive names, operational voltage and maximum load capacity.
Creating a descriptive input feed name:
In the Input Feed Name field, enter a descriptive name and click Apply .
Setting the infeed operational voltage:
In the Input Feed Voltage field, enter a value from 1 to 480 and click Apply .
NOTE: If Smart Load-Shedding has been activated and UPS voltage polling configured for an infeed, the polled voltage value will be used for all power calculations.
Setting the infeed maximum load capacity:
In the Input Feed Load Capacity field, enter a value from 1 to 255 and click Apply .
UPS
The UPS Configuration page is used for adding a new UPS device and configuring the UPS devices connected to
Smart POPS PDUs.
NOTE: The UPS page accepts both IPv4 and IPv6 formats in the Hostname/IP field.
38
•
Operations Smart POPS PDU
Installation and Operations Manual
To add a new UPS:
Select the UPS manufacturer type from the Type drop-down list, type an IP address (or hostname) for the UPS, and click
Apply .
To edit the UPS type:
Under the Action heading, click the Edit link for the UPS to be configured. The Configuration UPS page reformats to an edit page where UPS device settings are configured and UPS devices are associated with an infeed.
Selecting the UPS type:
Select the UPS manufacturer type from the UPS Type drop-down list and click Apply .
Editing the UPS Hostname/IP Address:
In the Hostname/IP field, type an IP Address or Hostname and click Apply .
Editing the UPS SNMP GET community string:
In the SNMP GET Community String field, type the community string configured on the UPS device and click
Apply .
Enabling/Disabling UPS voltage polling:
From the Poll UPS Voltage drop-down list, select Enabled or Disabled and click Apply .
Editing the UPS SNMP port number:
In the Port field, type the port number and click Apply .
Associate the UPS with an infeed:
Select the infeed(s) powered by the UPS and click Apply .
To remove a UPS:
On the Configuration UPS page, under the Action heading, click the Remove link for the UPS you want to remove.
Users
The Users configuration page is used for creation and removal of usernames, assignment of privilege levels, and the changing of user passwords.
Creating a new user:
Enter a user name in the Username field. Up to 16 alphanumeric and other typed characters (ASCII 33 to 126 decimal) are allowed; spaces are not allowed.
Enter a password for the new user and verify in the Password and Verify Password fields. For security, password characters are not displayed. Click Apply .
Smart POPS PDU
Installation and Operations Manual Operations
•
39
Removing a user:
Click on the Remove link in the Action column for the user to be removed and click Yes on the subsequent confirmation window.
Changing a user password:
Click on the Edit link in the Action column for the associated user.
On the subsequent User Edit page, enter a password and verify the new password for the new user in the Password and
Verify Password fields. For security, password characters are not displayed. Click Apply .
Changing a user’s access privilege level:
The Smart POPS PDU has the following defined privilege levels:
•
Admin: Full-access for all configuration, status, and serial/pass-thru ports.
•
Power User: Full-access for status, and automatic access rights for serial/pass-thru ports.
•
User: Partial-access for serial/pass-thru ports.
The administrator can also grant administrative privileges to other user accounts, which allows the unit to have more than one administrative-level user.
NOTE: You cannot remove administrative privileges from the admn user unless another user has already been given administrative access level privileges created.
Click on the Edit link in the Action column for the associated user.
On the subsequent User Edit page, select Admin or User from the Access Level drop-down menu and click Apply .
Adding and deleting serial port access:
Click on the Ports link in the Access column for the associated user.
On the subsequent User Ports page, select or deselect ports to be accessed by the user and click Apply .
40
•
Operations Smart POPS PDU
Installation and Operations Manual
FTP
The FTP configuration page is used for setup and maintenance of all settings required to perform an FTP firmware upload, configure automatic FTP updates or system configuration uploads/downloads. For more information about uploading firmware, the “Uploading Firmware” section in Appendix B.
NOTES:
•
The FTP page accepts both IPv4 and IPv6 formats in the Host field.
•
Secure File Transport Protocol (SFTP) is also supported for encrypted SSH transport over the network.
Setting the FTP Host Address:
Enter the IP address or hostname in the Host field and click Apply .
Setting the FTP username:
Enter the FTP server username in the Username field, and click Apply .
Setting the FTP password:
Enter the FTP server password in the Password field, and click Apply .
Setting the Directory (filepath):
Enter the path of the file to be uploaded in the Directory field, and click Apply .
Setting the filename for upload:
Enter the filename of the file to be uploaded in the Filename field, and click Apply .
Testing the FTP upload configuration:
This test validates that the unit is able to contact and log onto the specified FTP server, download the firmware file, and verify that the firmware file is valid for the unit. Click Test .
Smart POPS PDU
Installation and Operations Manual Operations
•
41
Enabling or disabling automatic updates:
The Smart POPS PDU features the ability to schedule automatic firmware updates. When enabled and configured, the unit will regularly check the FTP server for a new firmware image and upload it.
Select Enabled or Disabled from the drop-down menu and click Apply .
Setting the automatic update scheduled day:
Select the desired day for the automatic update from the drop-down menu and click Apply .
Setting the automatic update scheduled hour:
Select the desired hour for the automatic update from the drop-down menu and click Apply .
Enabling or disabling the FTP server:
The Smart POPS PDU features the ability to upload and download system configuration files to ease implementation across multiple devices. For more information about configuration upload and download, see the “Advanced
Operations – Upload/Download" section in Chapter 4.
Select Enabled or Disabled from the drop-down menu and click Apply .
NOTE: The FTP server must be enabled for configuration upload or download.
42
•
Operations Smart POPS PDU
Installation and Operations Manual
SNTP/Syslog
The SNTP/Syslog page sets the options for the SNTP server, time zone, Daylight Saving Time (DST) automatic clock adjustment, and Syslog server.
About Daylight Saving Time(DST)
Support for DST is disabled by default. When enabled, the date and time are automatically adjusted forward one hour between the starting and ending dates and times (which can be configured).
NOTE: If Daylight Saving Time (DST) is enabled, all system time displays show the current DST time start/end date/time settings.
The default time zone is set for the United Stated until at least 2015.
The time zone format is: mo.w.d/h:m:s , as follows: mo = month from January to December (1-12) w = week number (1-4) or the last week (5) d = day of week from Sunday to Saturday (0-6) h = hour (0-23) m = minute (0-59) s = second (0-59)
Setting the local date/time:
The Date/Time (Local) field shows the current DST settings. To increment the settings – based on updates to the start/end day/time options – click Update .
Setting the SNTP primary/secondary server address:
The Primary/Secondary Host fields contact the SNTP server; the fields are populated with the external NTP pool time zones “2.servertech.pool.ntp.org” and “1.servertech.pool.ntp.org” as default for new PDUs that have not yet been time set.
Enter the IP address or hostname in the Primary Host and/or Secondary Host field and click Apply .
Setting the Local GMT offset (hours/minutes):
The GMT offset supports all standard international time zones from -12:59 to +14.59. The GMT offset can be set in minutes to accommodate partial-hour time zones.
Select the local offset from GMT value from the drop-down menu and click Apply .
Smart POPS PDU
Installation and Operations Manual Operations
•
43
Enabling or disabling Daylight Saving Time (DST):
Select Enabled or Disabled from the SNMPv3 Agent drop-down menu and click Apply .
Setting Daylight Saving Time (DST) start/end date/time options:
Select the week/day/month and hour/minute/second for the start date/time and end date/time from the drop-down menus and click Apply .
Setting the Syslog server address:
Enter the IP address or hostname in the Primary and/or Secondary Host field and click Apply .
NOTE: Both IPv4 and IPv6 formats are accepted in the Primary/Secondary Host fields.
Changing the Syslog server port number:
In the Syslog Port field, enter the port number and click Apply .
SNMP/Thresholds
The SNMP/Thresholds configuration page allows setup and maintenance of all SNMP agent settings required to enable SNMP. The page also provides access to the trap configuration pages for towers, input feed, environmental monitor, and sensors.
NOTE: Traps are generated according to a hierarchical architecture; for example, if a tower status enters a trap condition, only the tower status trap is generated. Infeed and outlet status traps are suppressed until the tower status returns to normal.
44
•
Operations Smart POPS PDU
Installation and Operations Manual
About SNMP versions:
The firmware supports SNMP versions 1, 2, and 3.
SNMP version 3 supports authentication and encryption on a per user basis. Authentication types are None and MD5.
Encryption types are None and DES. If you use authentication, you must use encryption.
Two SNMPv3 users are supported: one user with read-write (RW) access, and one user with read-only (RO) access
Both users have the same configuration parameters, and you can configure each user independently.
SNMPv2 and SNMPv3 can be enabled or disabled independently. You can have SNMPv2 and/or SNMPv3, or none.
Enabling or disabling SNMP v3 support:
Select Enabled or Disabled from the SNMPv3 Agent drop-down menu and click Apply .
NOTE: The default for SNMP support is Enabled . When Server Technology products are shipped, the default SNMP configuration for the
GET community string is set to “ public ” and the SET community string is left blank .
Setting the SNMPv3 read-write (RW) user or read-only (RO) user:
Enter the Read-Write User or Read-Only User username and click Apply . A valid username can be set to any value between 1-31 characters.
Configuring the SNMPv3 read-write (RW) user or read-only (RO) user authentication type:
From the Read-Write User or Read-Only User Authentication Type drop-down menu, select None or MD5, and click
Apply . To clear the password, check Change Password .
Setting the SNMPv3 read-write (RW) user or read-only (RO) user authentication password:
Enter the Read-Write (RW) User or Read-Only (RO) User Password and, and click Apply . To clear the password, check Change Password . A valid authentication password can be set to any value between 1-39 characters. A blank password will clear the string.
Configuring the SNMPv3 read-write (RW) user or read-only (RO) user privacy type:
From the Read-Write User or Read-Only User Privacy Type drop-down menu, select None or DES, and click Apply .
To clear the password, check Change Password .
Setting the SNMPv3 read-write (RW) user or read-only (RO) user privacy password:
Enter the Read-Write User or Read-Only User privacy password and, and click Apply . To clear the password, check
Change Password . A valid password can be set to any value between 1-31 characters.
Setting the SNMPv3 trap username:
The optional trap username displays on SNMP activity logs to identify user actions.
Type a name in the Trap Username field and click Apply . The trap username can be 1-31 alphanumeric characters; spaces are allowed; and the name is case sensitive.
Configuring general parameters for any SNMP version:
Setting trap destinations:
Type an IP address or hostname as necessary in the trap destination field(s) and click Apply .
NOTE: Both IPv4 and IPv6 formats are accepted in the “Trap Destination 1” and “Trap Destination 2” fields.
Setting the error trap repeat time:
Type a time value in the Error Trap Repeat Time field and click Apply . The valid range is 1 to 65535 (in seconds).
Setting the trap format version:
The SNMP Trap Format configures the SNMP trap format version. The trap format can be SNMP v1, v2, or v3. The default is v1, regardless of the versions that are enabled for the agent.
From the Trap Format drop-down menu, select the v1, v2, or v3 option and click Apply .
Smart POPS PDU
Installation and Operations Manual Operations
•
45
Setting IP restrictions:
From the IP Restrictions drop-down menu, select the No Restrictions or Trap Destinations Only option and click
Apply .
NOTE: When the Trap Destinations Only option is selected, SNMP Manager Get and Set requests are allowed only from the IP address of the defined trap destinations.
Setting the SNMP SysName, SysLocation or SysContact objects:
In the appropriate field, enter the SysName, SysLocation or SysContact objects and click Apply .
Enabling or disabling tower traps:
Click on the Tower Traps link.
On the subsequent Tower Traps page, select or deselect the desired traps and click Apply .
Configuring input feed traps:
Click on the Input Feed Traps link.
On the subsequent Input Feed Traps page, select or deselect the desired traps and click Apply .
For Load traps, enter a maximum load value for the infeed in the High Load Threshold field and click Apply .
The default input feed high load threshold is 80% of the input feed maximum load capacity.
Configuring outlet traps:
Click on the Outlet Traps and Thresholds link.
On the subsequent page, select or deselect the desired traps and click Apply .
For the Low Load traps, enter a minimum load value (in whole amps) and click Apply . The default Low Load threshold is 0 A.
For the High Load traps, enter a maximum load value and click Apply . The default threshold is 80% of the maximum outlet load capacity.
Enabling or disabling Environmental Monitor traps:
Click on the Environmental Monitor Traps link.
On the subsequent page, select or deselect the desired traps and click Apply .
Configuring the Temperature and Relative Humidity sensor traps:
Click on the Sensor Traps and Thresholds link.
On the subsequent Sensor Traps and Thresholds page, select or deselect the desired trap checkboxes and click Apply .
Configuring the Temperature and Relative Humidity sensor thresholds:
Click the Sensor Traps and Thresholds link.
For temperature thresholds, type a low and high temperature value in the Low Temp and High temp fields and click
Apply .
For relative humidity thresholds, type a low and high humidity percentage in the Low Humid and High Humid fields, and click Apply .
NOTE: For temperature thresholds, the valid range is 0 to 123 degrees Celsius or 32 to 254 degrees Fahrenheit. For relative humidity, the valid range is 0 to 100 (in percent relative humidity).
46
•
Operations Smart POPS PDU
Installation and Operations Manual
Configuring Temperature and Humidity Recovery Delta (Hysteresis):
Click on the Sensor Traps and Thresholds link.
The Recovery Delta field allows configuration of the number of degrees of change needed to recover from a temperature alarm. After exceeding the high-temperature threshold, the temperature value must fall below the hightemperature threshold by the number of degrees specified in the Recovery Delta field before the sensor recovers.
For example, if the High Temp value is 80 degrees Fahrenheit, and the Recovery Delta field is 2 degrees Fahrenheit, the sensor will not recover until a temperature value of 78 degrees Fahrenheit is reported.
To configure a temperature recovery delta (hysteresis), in the Recovery Delta field for “Temp”, type a value
(in degrees) and click Apply . Valid range is 0-30 Celsius or 0-54 Fahrenheit.
To configure a humidity recovery delta (hysteresis), in the Recovery Delta field for “Humid”, type a value
(in percent) and click Apply . Valid range is 0-20%.
NOTE: The default value for the Recovery Delta field is 1 degree Celsius and 2 degrees Fahrenheit.
Smart POPS PDU
Installation and Operations Manual Operations
•
47
LDAP
The LDAP configuration page is used for setup and maintenance of all settings required to enable LDAP support.
Enabling or disabling LDAP support:
Select Enabled or Disabled from the LDAP drop-down menu and click Apply.
Configuring the authentication order:
Select Remote -> Local or Remote Only from the drop-down menu and click Apply.
NOTE: Server Technology recommends not setting the authentication order to Remote Only until LDAP has been configured and tested.
Setting the LDAP server address:
Enter the IP address or hostname in the Primary and/or Secondary Host field and click Apply.
NOTE: Both IPv4 and IPv6 formats are accepted in the Primary/Secondary Host fields.
Changing the LDAP server port:
Enter the port number in the LDAP Port field and click Apply.
48
•
Operations Smart POPS PDU
Installation and Operations Manual
Setting the LDAP bind type:
The PDU supports three standard LDAP bind methods:
Simple: Uses unencrypted delivery of username-password over the network to the LDAP server for authentication, showing user credentials in plain text.
TLS/SSL: (LDAP over TLS/SSL) Uses a trusted authority certificate to provide encryption of LDAP authentication.
MD5: Provides strong protection using 1-way hash encoding that does not transmit the username-password over the network.
From the Bind Type drop-down menu, select Simple, TLS/SSL, or MD5, and click Apply.
NOTE: If LDAP over TLS/SSL is enabled, MD5 binding is disabled.
Setting the search bind Distinguished Name (DN):
Enter the fully-qualified domain name (FQDN) in the Search Bind field and click Apply.
Setting the search bind password for Distinguished Name (DN):
Enter the Search Bind Password in the Search Bind Password field and click Apply.
Setting the user search base Distinguished Name (DN):
Enter the User Search Base DN in the User Search Base DN field and click Apply.
Setting the user search filter:
Enter the User Search Filter in the User Search Filter field and click Apply.
Setting the group membership attribute:
Enter the group membership attribute in the Group Membership Attribute field and click Apply.
Enabling or disabling group search:
Select Enabled or Disabled from the Group Search drop-down menu and click Apply.
Setting the group search base Distinguished Name (DN):
The Group Search Base DN indicates where the LDAP group search will start.
Enter the Base DN in the Group Search Base DN field and click Apply.
Setting the user membership attribute name:
The User Membership Attribute is a comma-delimited string of up to two attribute names whose values in the search results are the users that are members of the group. Maximum numbers of characters is 61.
Enter the user membership attribute name(s) in the User Membership Attribute field and click Apply.
NOTE: The user membership option allows the searching of directory entries of groups for a user membership attribute to find the groups for which the user is a member.
Setting the DNS IP address:
For information about how to set the DNS IP address, see the “Network” section.
Smart POPS PDU
Installation and Operations Manual Operations
•
49
Configuring LDAP groups:
Click on the LDAP Groups link at the bottom of the page.
Creating an LDAP group:
Enter a descriptive group name in the LDAP Group Name field. Up to 24 alphanumeric and other typed characters
(ASCII 33 to 126 decimal) are allowed; spaces are not allowed. Click Apply .
Removing an LDAP group:
Click on the Remove link in the Action column for the group to be removed and click OK on the subsequent confirmation window.
Changing an LDAP group’s access level:
Click on the Edit link in the Action column for the associated LDAP Group.
On the subsequent LDAP Group - Edit page, select Admin , User , On-only or View-only from the Access Level drop-down menu and click Apply .
Granting or removing environmental monitoring viewing privileges :
Click on the Edit link in the Action column for the associated LDAP Group.
On the subsequent LDAP Group - Edit page, select Yes or No from the Environmental Monitoring drop-down menu and click Apply
NOTE: Granting access to environmental monitoring (temperature/humidity/sensors) to a non-admin user also grants that user access to power monitoring (outlets, infeeds, towers – all the environmental data of the PDU).
Adding and Deleting serial port access:
Click on the Ports link in the Access column for the associated LDAP Group.
On the subsequent LDAP Group - Ports page, select or deselect ports to be accessed by the LDAP Group and click Apply .
50
•
Operations Smart POPS PDU
Installation and Operations Manual
TACACS+
The TACACS+ configuration page is used for setup and maintenance of all settings required to enable TACACS+ support.
Enabling or disabling TACACS+ support:
Select Enabled or Disabled from the TACACS+ drop-down menu and click Apply .
Setting the TACACS+ server address:
Enter the IP address or hostname in the Primary and/or Secondary Host field and click Apply .
NOTE: Both IPv4 and IPv6 formats are accepted in the Primary/Secondary Host fields.
Changing the TACACS+ server port:
Enter the port number in the Port field and click Apply .
Configuring the authentication order:
Select Remote > Local or Remote Only from the drop-down menu and click Apply .
NOTE: Server Technology recommends not setting the authentication order to Remote Only until LDAP has been configured and tested.
Setting the TACACS+ encryption key:
Enter a new key and verify it with the Encryption Key and Verify Encryption Key fields. Click Apply .
For security, key characters are not displayed.
Configuring TACACS+ privilege levels:
Click on the TACACS+ Privilege Levels link at the bottom of the page.
Changing a TACACS+ Privilege Level’s access privilege level:
Click on the Edit link in the Action column for the associated TACACS+ Privilege Level.
On the subsequent TACACS+ Privilege Level - Edit page, select Admin , User , On-only or View-only from the
Access Level drop-down menu and click Apply .
Adding and Deleting serial port access:
Click on the Ports link in the Access column for the associated TACACS+ Privilege Level.
Smart POPS PDU
Installation and Operations Manual Operations
•
51
RADIUS
The Remote Authentication Dial-in User Service (RADIUS) configuration page is used for setup and maintenance of all settings required to enable RADIUS support.
Enabling or disabling RADIUS support:
Select Enabled or Disabled from the RADIUS drop-down menu and click Apply .
Configuring the authentication order:
Select Remote->Local or Remote Only from the drop-down menu and click Apply .
NOTE: Server Technology recommends not setting authentication order to Remote Only until RADIUS has been configured and tested.
Changing the RADIUS server address:
Enter the IP address or hostname in the Primary and/or Secondary Server field and click Apply .
NOTE: Both IPv4 and IPv6 formats are accepted in the Primary/Secondary Host fields.
Setting the RADIUS shared secret:
The shared secret is the RADIUS authentication key.
Enter the shared secret in the Primary and Secondary Shared Secret field. Up to 48 upper and lowercase alphanumeric and other typed characters (ASCII 33 to 126 decimal) and spaces are allowed; control characters are not allowed.
Click Apply .
To change the shared secret, check the Change checkbox to clear the Shared Secret field, enter the new shared secret, and click Apply .
Changing the RADIUS server port:
This field specifies the port number used by the RADIUS server for incoming RADIUS authentication requests.
Enter the port number in the Primary and/or Secondary Port field and click Apply .
The valid port number range is 1-65535; default is 1812.
Setting the RADIUS server timeout value:
The Timeout field specifies the time interval (in seconds) to wait for a reply from the RADIUS server before resending an authentication request.
Enter the timeout value (in seconds) in the Primary and/or Secondary Timeout field and click Apply .
The valid timeout range is 1-30 seconds; default is 5 seconds.
52
•
Operations Smart POPS PDU
Installation and Operations Manual
Setting the number of RADIUS server retries:
The Set RADIUS Retries command specifies the number of times an authentication request is sent to the RADIUS server. The Smart POPS PDU will attempt authentication with the primary server until the number of retries is reached, then will attempt authentication with the secondary server. If the PDU does not receive a response from these attempts, the authentication request will be rejected.
Type the number of retries in the Primary and/or Secondary Retries field and click Apply .
The valid retries range is 0-10; default is 2.
SMTP/Email
The SMTP/Email page allows the configuration of Simple Mail Transfer Protocol (SMTP) and Email options.
NOTE: Both IPv4 and IPv6 formats are accepted in the Host field.
Enabling or disabling Email support:
Select Enabled or Disabled from the Email Notifications drop-down menu and click Apply .
Setting the SMTP server address:
Enter the IP address or hostname in the SMTP Host field and click Apply .
Changing the SMTP server port:
Enter the port number in the SMTP Port field and click Apply .
Setting the SMTP authentication type:
NOTES:
•
SMTP authentication allows the mail client in the PDU to login to the mail server during the process of sending a mail. The mail server
may require this login to relay mail to another mail server.
•
Supported SMTP authentication types are: None (default, no SMTP authentication); Digest-MD5; CRAM-MD5; Login; and Plain.
SMTP authentication occurs with a configured username and password, or you can use the address in the ‘From’ Address field in place
of the username.
From the SMTP Authentication drop-down menu, select an authentication method. From the “with” drop-down menu, select “SMTP Username” or “From Address”. Click
Apply .
Smart POPS PDU
Installation and Operations Manual Operations
•
53
Setting the Email SMTP authentication username:
In the Username field, type the desired Email SMTP username and click Apply . Spaces are not allowed.
Setting the Email SMTP authentication password:
The Set Email SMTP Password command sets the password for SMTP authentication with the username.
In the Password field, type a password of 1-16 alphanumeric and other characters (ASCII 33 to 126 decimal) are allowed; passwords are case sensitive. Click Apply .
To change the password, type over it, check the Change checkbox, and click Apply
Setting the ‘From’ email address:
Enter the ‘from’ email address in the ‘From’ Address field and click
Apply .
Setting the ‘Send To’ email address:
Enter the ‘send to’ email address in the Primary or Secondary ‘Send To’ Address field and click
Apply .
If the primary ‘send to’ address fails, the system then attempts to send the email to the secondary ‘send to’ address.
Setting the subject ID:
From the Subject ID drop-down menu, select the default “Sentry3_524640” option or the “Location” option to specify the email subject line. Click Apply .
Enabling or disabling event type notifications:
Select Enabled or Disabled from the Include…Messages drop-down menus and click
Apply .
Sending a test email:
After providing information in the Email/SMTP web page, click the Test button to send a test email to the target email destinations
Features
The Features configuration page displays the product serial number and the active features currently in the system. The
Features page also provides the Feature Key Value field where the administrator enters the license key value provided by
Server Technology to activate a new system feature.
54
•
Operations Smart POPS PDU
Installation and Operations Manual
Tools
For the Administrator, the Tools section contains access to rebooting the unit, uploading new firmware, and resetting the unit to factory defaults.
Ping
Use the Ping feature to test the ability of the Smart PDU to contact another IP address for an Ethernet-enabled device.
For LDAP support, Ping also tests the configuration of the Domain Name System (DNS) server IP address by testing for proper name resolution.
NOTE: Both IPv4 and IPv6 formats are accepted in the Ping Host Name/IP Address field.
Change Password
The Change Password feature allows users to change their own password.
NOTE : An administrator can always assign a new password to a user.
Changing a password:
Enter the current password, enter a new password and verify the new password. Click Apply .
Firmware
The Firmware page allows the uploading of a system firmware (.bin) file. Click Browse to locate the .bin firmware file, and then click Upload. A confirmation message is displayed.
Smart POPS PDU
Installation and Operations Manual Operations
•
55
View Log
The View Log feature enables viewing of the internal system log. This features logs all authentication attempts, power actions, configuration changes and other system events. The system memory stores more than 4000 entries in a continuously aging log. For permanent off-system log storage, the Syslog protocol is supported.
NOTE: The system log is viewable only by users with administrative privileges.
Reviewing the system log:
Click on the Previous 100 entries or Next 100 entries link to navigate through the log.
Restart
Performing a warm boot:
Select the Restart from the Action drop-down menu and click Apply .
NOTE: System user/outlet/group configuration or outlet states are NOT changed or reset with this command.
Resetting to factory defaults:
For more information about resetting a unit to factory defaults from the Web interface, see the “Resetting to Factory
Defaults” section in Appendix A.
Uploading new firmware:
For more information on uploading new firmware from the Web interface, see the “Uploading Firmware” section.
Generating a new SSL X.509 certificate:
Select the Restart and generate a new X.509 certificate from the Action drop-down menu and click Apply .
Computing new SSH security keys:
Select the Restart and compute new SSH keys from the Action drop-down menu and click Apply .
56
•
Operations Smart POPS PDU
Installation and Operations Manual
Command Line Interface
IMPORTANT: The Command Line Interface (CLI) was modified to allow both IPv4 and IPv6 settings.
Logging In
Logging in through Telnet requires directing the Telnet client to the configured IP address of the unit.
Logging in through the Console (RS232) port requires the use of a terminal or terminal emulation software configured to support ANSI or VT100 and a supported data rate (300, 1200, 2400, 4800, 9600, 19200, 38400, 57600, or 115200
BPS) - 8 data bits-no parity-one stop bit and Device Ready output signal (DTR or DSR).
To log in by RS-232 or Telnet:
1.
Press Enter . The following appears, where x.xx
is the firmware version:
Sentry Version x.xx
Username:
NOTE: Logging in by Telnet will automatically open a session. It is not necessary to press Enter.
2.
At the Username: and Password: prompts, enter a valid username and password. And press Enter .
You are given three attempts to enter a valid username and password combination. If all three fail, the session ends.
NOTE : The default username/password is admn/admn .
When you enter a valid username and password, the command prompt (Smart CDU:) appears. If a location identifier was defined, it will be displayed before the Smart CDU: prompt.
You can enter commands in any combination of uppercase and lowercase characters. All command characters must be entered correctly; there are no command abbreviations. A user must have administrative privileges to use the administration commands. The following tables list and briefly describe each command.
Operations Command Summary
Command Description
Connect
Envmon
IStat
List Ports
Login
Logout
Password
Quit
UPSStat
Connects to a serial/Pass-Thru port
Displays the status of the integrated Environmental Monitor
Displays the status of the infeeds
Lists all accessible serial/Pass-Thru ports for the current user
Ends the current session and brings up the Username: prompt
Ends a session
Changes the password for the current user
Ends a session
Displays the status of the associated UPS devices
Smart POPS PDU
Installation and Operations Manual Operations
•
57
Administrative Command Summary
Add Porttouser
Create User
Delete Portfromuser
List User
List Users
Remove User
Restart
Set Banner
Set Bluetooth Discover
Set Bluetooth Name
Grants a user access to one or all serial/Pass-Thru ports
Adds a user account
Removes access to one or all serial/Pass-Thru ports
Displays all accessible ports for a user
Displays privilege levels for all users
Deletes a user account
Performs a warm boot
Set the pre-login banner text
Determines the current status of the pushbutton on the Bluetooth module
Configures the name of the discovered Bluetooth module on the Android device
Set Bluetooth Pincode
Set Bluetooth Transpwr
Set DHCP
Set DHCP Boot Delay
Pin code value for legacy Bluetooth modules that require a pin to pair the module
Designated transmission power (dbm) for the Bluetooth module.
Enables or disables DHCP support
Enables or disables a 100-second boot delay between PDU and DHCP server
Set DHCP Static Address Fallback Enables or disables DHCP fallback to a static IP address
Set DNS Sets the IP address of the Domain Name System (DNS) server
Set EnergyWise
Set EnergyWise Domain
Enables or disables the Cisco EnergyWise network
Sets the Cisco EnergyWise domain name
Set EnergyWise Port
Set EnergyWise Refresh
Set EnergyWise Secret
Set Envmon Name
Set Envmon THS Name
Set FTP Autoupdate
Set FTP Autoupdate Day
Set FTP Autoupdate Hour
Set FTP Directory
Set FTP Filename
Sets the Cisco EnergyWise port number
Rate (in seconds) at which information is pushed to the EnergyWise manager
Sets the Cisco EnergyWise secret
Specifies a descriptive field fro the integrated Environmental Monitor
Specifies a descriptive field for a temperature-humidity sensor
Enables or disables automatic FTP update support
Sets the automatic FTP update day
Sets the automatic FTP update hour
Specifies the directory for the file to be uploaded
Specifies the file to be uploaded via FTP
Set FTP Host
Set FTP Password
Sets the FTP Host IP address or hostname
Sets the password for the FTP Host
Set FTP Test Validates that the PDU can login to the FTP server and verify/download the firmware file
Set FTP Username Sets the username for the FTP Host
Set FTP Server
Set Gateway
Set HTTP
Set HTTP Port
Enables or disables the FTP server
Sets the Gateway of the unit
Enables or disables HTTP access and sets the HTTP target port.
Specifies the target port for HTTP access
Set Infeed Name
Set IPAddress
Set Infeed Loadmax
Set Infeed Voltage
Set LDAP UseTLS
Set Location
Set Net
Set Option Button
Set Option CLI Timeout
Set Option Coldboot Alert
Specifies a descriptive field for the infeed
Sets the IP address of the unit
Specifies the maximum load capacity for the infeed
Specifies the nominal input voltage for the infeed
Enables or disables LDAP over TLS/SSL support
Specifies a descriptive field for the web control screen and login banner
Determines the acquisition method for the protocol stack and IPv4/IPv6 addresses
Enables or disables the external configuration reset button
Sets the Command Line Interface (CLI) session timeout period
Enables or disables the Coldboot Alert feature using a serial protocol
Set Option Display Sets the LED orientation for external Current displays
58
•
Operations Smart POPS PDU
Installation and Operations Manual
Administrative Command Summary (continued…)
Set Option More Enables or disables the ‘more’ prompt
Set Option Outlet Sequence Configures outlet power-on sequence order as normal or reversed
Set Option Prompt Configures a custom CLI prompt.
Set Option Startupstick
Set Option StrongPasswords
Set Option Tempscale
Enables or disables the StartUp Stick tool for PDU mass configuration.
Enables or disables strong password requirements
Sets the Environmental Monitor temperature scale
Set Option Web Timeout
Set Port CLI
Set Port Name
Set Port DSR Check
Set Port Speed
Set Port SCP
Set Port SCP Emulate
Set Port Timeout
Sets the web session (Web Interface) timeout period
Enables or disables availability of the Command Line Interface (CLI)
Specifies a descriptive field for a serial/Pass-Thru port
Sets the DSR active signal checking for a serial/Pass-Thru port
Set the connection speed for all serial/Pass-Thru ports
Enables or disables Serial Command Protocol (SCP) functions
Notifies the Serial Command Protocol (SCP) of an MRV device on a specific serial port
Sets the inactivity timeout period for a serial port before closing the pass-thru session
Set Port RFTag
Set SCP Authentication
Enables or disables RF Code sensor tags for the wireless monitoring solution
Enables or disables Serial Command Protocol (SCP) authentication
Set SCP Authentication User Sets the username and password for Serial Command Protocol (SCP) authentication
Set SNMP IP Restrict Allows SNMP Get and Set requests only from defined trap destinations
Set SNTP
Set SNTP DST
Set SNTP DST End
Set SNTP DST Start
Sets the IP address or hostname of the SNTP servers
Enables or disables Daylight Saving Time (DST)
Specifies the settings for DST day/time end parameters
Specifies the settings for DST day/time start parameters
Set SNTP GMTOffset
Set SPM
Set SPM Reset Password
Set Subnet
Set System Area
Sets the local GMT offset applied to the SNTP date/time
Enables/disables secure access of Sentry Power Manager (SPM)
Resets the SPM password on the PDU to its internal default password
Sets the Subnet Mask of the unit
Specifies to total system area for the system
Set System Area Unit
Set System Balance
Set System Balance Alert
Set System PF
Set Telnet
Set Telnet Port
Set Tower 3Phase
Set Tower Model
Set Tower Name
Set Tower ProdSN
Set Tower
Set User Access
Set User Envmon
Set User Password
Set UPS AddInfeed
Set UPS DelInfeed
Set UPS GETComm
Set UPS Host
Set UPS Port
Set UPS Type
Specifies the system area (footprint) unit of measure
Sets the percent as load out-of-balance threshold for 3-phase systems
Enables/disables alert when load out-of-balance threshold is reached for 3-phase systems
Sets the power factor used in the total system power calculation
Enables or disables Telnet access
Sets the Telnet server port number
Specifies the AC voltage type for the tower
Specifies the model number for the tower
Specifies a descriptive field for the unit
Specifies the serial number for the tower
Specifies the AC or DC voltage type for the tower
Sets the access level for a user
Grants or removes user access to environmental monitoring
Changes the password for a user
Adds an infeed association to a UPS
Deletes an infeed association from a UPS
Sets the UPS ‘get’ community string
Sets the UPS Host IP address or hostname
Specifies the target port for a UPS
Sets the UPS type
Smart POPS PDU
Installation and Operations Manual Operations
•
59
Administrative Command Summary (continued…)
Set UPS VPoll
Show EnergyWise
Show FTP
Show Infeeds
Show Network
Show Options
Enables or disables UPS voltage polling
Displays Cisco EnergyWise network configuration information
Displays FTP configuration information
Displays infeed configuration information
Displays network configuration information for all IPv4 and IPv6 settings
Displays system option information
Show Ports
Show SNTP
Show System
Show Towers
Show UPS
Show System Status
Version
Displays serial/Pass-Thru port configuration information
Displays SNTP configuration information
Displays system configuration information
Displays tower configuration information
Displays UPS configuration information
Displays system power and tower configuration information
Displays the firmware version
To display the names of commands that you can execute:
At the command prompt, press Enter . A list of valid commands for the current user appears.
Operations Commands
Operations commands manage outlet states, provide information about the environment of the unit, and control session operations.
Displaying infeed status:
The IStat command displays the status of one or more infeeds.
This display includes the infeed absolute and descriptive names and the Input Status and current Load reported to the unit by the infeed, branch, or phase.
To display status of one or more infeeds:
Type istat and press Enter , or
Examples
The following command displays the infeed status:
Smart CDU: istat
Input Input Input Input
Feed ID Feed Name Status Load
.AA Master On 10.5 Amps
Connecting to a serial device:
The Connect command allows Pass-Thru serial connection to devices attached to the standard serial port (Console).
To connect to a serial device:
At the Smart CDU: prompt, type connect console and press Enter .
NOTE: The Connect command will not immediately disconnect when issued from an SSH session that was established while another
Telnet or SSH session already existed.
To disconnect from a serial device:
Type !*break and press Enter .
60
•
Operations Smart POPS PDU
Installation and Operations Manual
Displaying the status of the Environmental Monitor:
The Envmon command displays the status of the integrated Environmental Monitor.
By default, only administrative user accounts are allowed access to the Envmon command. An administrator may user the Set User Envmon command to enable and disable access for other user accounts.
To display the status of the Environmental Monitor:
At the Smart CDU: prompt, type envmon and press Enter .
Example
The following command displays the status of the Environmental Monitor.
Smart CDU: envmon<Enter>
Environmental Monitor .A
Name: Florida_HQ_1 Status: Normal
Temperature/Humidity Sensors
ID Name Temperature Humidity
.A1 Temp_Humid_Sensor_A1 Not Found Not Found
.A2 T/H2_Florida_HQ_1 23.5 Deg. C 22 % RH
Changing a password:
The Password command changes the current user’s password. For security, when you type a password, the characters are not displayed on the screen.
To change a password:
At the Smart CDU: prompt, type password and press Enter .
At the Enter Current Password: prompt, type the current password and press Enter .
At the Enter New Password: prompt, type the new password and press Enter . Passwords may contain 1-16 characters.
At the Verify Password: prompt, retype the new password and press Enter .
Starting a new session:
The Login command activates the Username: prompt. The current session ends, allowing a user to log in and start a new session under a different username.
To start a new session:
At the Smart CDU: prompt, type login and press Enter . The Username: prompt appears.
Ending a session:
The Quit or Logout commands ends a session. A session ends automatically when no activity is detected for five minutes, or upon loss of connection.
To end a session:
At the Smart CDU: prompt, type quit and press Enter , or
Type logout and press Enter .
Smart POPS PDU
Installation and Operations Manual Operations
•
61
Displaying UPS status:
The UPSStat command displays the status of one or more UPS devices associated with the unit.
The display includes UPS index number, type, line/battery status, and reported voltage.
NOTE: Access to this command requires enabling user privileges for environmental monitoring using the Set User Envmon command.
To display status of one or more UPS devices:
At the Smart CDU: prompt, type upsstat and press Enter .
Example
The following command displays the UPS status:
Smart CDU: upsstat<Enter>
UPS UPS UPS UPS
Index Type Status Voltage
1 Generic(RFC1628) N/A N/A
2 Liebert On Battery 120.0
3 MGE On Utility 119.9
Administration Commands
Administration commands may only be issued by a user with administrative privileges, such as the predefined admn user or another user who has been granted administrative privileges with the Set User Admnpriv command.
User Administration
Creating a user account:
The Create User command creates a user account with the specified username and password.
To create a user account:
At the Smart CDU: prompt, type create user , optionally followed by a 1-16 character username (Spaces are not allowed, and usernames are not case sensitive). Press Enter .
At the Password: prompt, type a password of 1-16 alphanumeric and other typed characters - (ASCII 33 to 126 decimal) are allowed; passwords are case sensitive. Press Enter .
At the Verify Password: prompt, retype the password. Press Enter .
Example
The following command creates the user account JaneDoe:
Smart CDU: create user JaneDoe<Enter>
Password: <Enter>
Verify New Password: <Enter>
For security, password characters are not displayed.
Removing a user account:
The Remove User command removes a user account.
NOTE: You may remove the predefined user account Admn only if another user account has been granted administrative privileges using the Set User Admnpriv command.
To remove a user account:
At the Smart CDU: prompt, type remove user , optionally followed by a username. Press Enter .
62
•
Operations Smart POPS PDU
Installation and Operations Manual
Changing a password:
The Set User Password command changes a user’s password. For security, when you type a password, the characters are not displayed on the screen.
To change a password:
At the Smart CDU: prompt, type set user password , followed by a username and press Enter .
At the Password: prompt, type the new password and press Enter . Passwords may contain 1-16 characters.
At the Verify Password: prompt, retype the new password and press Enter .
Example
The following command changes the password for the user JohnDoe:
Smart CDU: set user password johndoe<Enter>
Password: <Enter>
Verify Password: <Enter>
For security, password characters are not displayed.
Setting user access level privileges:
The Set User Access command sets the access level for a user. The user access levels are Admin, Power, and User.
The administrator can also grant administrative privileges to other user accounts allowing the PDU to have more than one administrative-level user.
NOTE: You cannot remove administrative access from the default admn user until you give administrative access to another user.
To set the access level privilege for a user:
At the Smart CDU: prompt, type set user access , followed by admin , poweruser , user , rebootonly , ononly or viewonly , optionally followed by a username and press Enter .
Examples
The following command sets the user access level for JohnDoe to Admin:
Smart CDU: set user access admin johndoe<Enter>
The following command sets the user access level for JaneDoe to User:
Smart CDU: set user access user janedoe<Enter>
Displaying the access privilege levels:
The List Users command displays all defined users with their access privilege level.
To display user access privilege levels:
At the Smart CDU: prompt, type list users and press Enter .
Example
The following command displays all users with their access privilege level:
Smart CDU: list users<Enter>
User Privilege Environmental
Name Level Monitoring
JOHNDOE Admin Allowed
JANEDOE User Allowed
Adding serial port access to a user:
The Add PortToUser command grants a user access to the serial port.
To grant serial port access to a user:
At the Smart CDU: prompt, type add porttouser console and a username. Press Enter .
Smart POPS PDU
Installation and Operations Manual Operations
•
63
Deleting serial port access for a user:
The Delete PortFromUser command removes a user’s access to the serial port. You cannot remove access to the serial port for an administrative level user.
To delete serial port access for a user:
At the Smart CDU: prompt, type delete portfromuser console and a username. Press Enter .
Displaying user serial port access:
The List User command displays all accessible outlets, groups and serial ports for a user.
To display serial port access:
At the Smart CDU: prompt, type list user , optionally followed by a username. Press Enter .
Example
The following command displays information about the user JaneDoe:
Smart CDU: list user janedoe<Enter>
Username: JANEDOE
Ports:
Port Port
ID Name
Console Console
Input Feed Administration
Creating a descriptive infeed name:
The Set Infeed Name command assigns a descriptive name to an infeed. This descriptive name is displayed when the
Show Traps command is issued.
To create a infeed name:
At the Smart CDU: prompt, type set infeed name followed by the absolute infeed name, then a descriptive name of up to 24 alphanumeric and other typed characters - (ASCII 33 to 126 decimal) are allowed; spaces are not allowed.
Press Enter .
Example
The following command adds the descriptive name HQ_1_Infeed_A to the infeed on the Smart CDU:
Smart CDU: set infeed name .aa HQ_1_Infeed_A<Enter>
Setting the infeed operational voltage
The Set Infeed Voltage command is use to edit the input operational voltage.
To set the infeed operational voltage:
At the Smart CDU: prompt, type set infeed voltage , followed by the absolute infeed name, and a value from 1 to 480.
Press Enter .
Example
The following commands sets the operational voltage for input .AA to 100V:
Smart CDU: set infeed voltage .aa 100<Enter>
Setting the infeed maximum load capacity
The Set Infeed LoadMax command is use to edit the input maximum load capacity.
To set the infeed maximum load capacity:
At the Smart CDU: prompt, type set infeed loadmax , followed by the absolute infeed name, and a value from 1 to
255 (in amperes). Press Enter .
Example
The following commands sets the maximum load capacity for input .AA to 15 amperes:
Smart CDU: set infeed loadmax .aa 15<Enter>
64
•
Operations Smart POPS PDU
Installation and Operations Manual
Displaying infeed information:
The Show Infeeds command displays information about all infeeds. This information includes the absolute and descriptive infeed names, operational voltages and maximum load capacities.
To display tower information:
At the Smart CDU: prompt, type show infeeds and press Enter .
Example
Smart CDU: show infeeds<Enter>
Input Input Input Input
Feed ID Feed Name Feed Voltage Feed Capacity (Amps)
.AA HQ_1_Infeed_A 100 15
.AB HQ_1_Infeed_B 120 20
.BA HQ_2_Infeed_A 120 30
.BB HQ_2_Infeed_B 120 30
Smart POPS PDU
Installation and Operations Manual Operations
•
65
Tower Administration
Creating a descriptive tower name:
The Set Tower Name command assigns a descriptive name to a tower. This descriptive name is displayed when the
Show Traps command is issued.
To create a tower name:
At the Smart CDU: prompt, type set tower name followed by the absolute tower name, then a descriptive name of up to 24 alphanumeric and other typed characters - (ASCII 33 to 126 decimal) are allowed; spaces are not allowed. Press
Enter .
Example
The following command adds the descriptive name Florida_HQ_1 to tower .a:
Smart CDU: set tower name .a Florida_HQ_1<Enter>
Setting the tower serial number:
The Set Tower ProdSN command is use to set the product serial number.
NOTE : If set at the factory, you cannot edit the serial number.
To set the tower serial number:
At the Smart CDU: prompt, type set tower prodsn , followed by the absolute tower name, and the tower serial number. Press Enter .
Example
The following command sets the serial number for tower .A to ‘AA06F011157’:
Smart CDU: set tower prodsn .a AA06F011157<Enter>
Setting the tower model number:
The Set Tower Model command is use to set the product model number.
NOTE: If set at the factory, you cannot edit the model number.
To set the tower model number:
At the Smart CDU: prompt, type set tower model , followed by the absolute tower name, and the tower model number. Press Enter .
Example
The following command sets the model number for tower .A to ‘CS-24V2-C20’:
Smart CDU: set tower prodsn .a CS-24V2-C20<Enter>
Setting the tower AC or DC voltage type:
The Set Tower command is used to set the product input AC or DC voltage type.
NOTE: If set at the factory, you cannot edit the voltage type.
To set the tower AC/DC voltage type:
At the Smart CDU: prompt, type set tower , followed by ac or dc , and the absolute tower name. Press Enter .
Example
The following command sets the AC/DC voltage type for tower .A to AC:
Smart CDU: set tower ac.a<Enter>
66
•
Operations Smart POPS PDU
Installation and Operations Manual
Setting the tower AC voltage type:
The Set Tower 3phase command is used to set the product input AC voltage type.
NOTE: If set at the factory, you cannot edit the voltage type.
To set the tower AC voltage type:
At the Smart CDU: prompt, type set tower 3phase , followed by the absolute tower name and yes or no . Press Enter .
Example
The following command sets the AC voltage type for tower .A to non-3-phase:
Smart CDU: set tower 3phase.a no<Enter>
Displaying tower information:
The Show Towers command displays information about the unit. This information includes the absolute and descriptive PDU names, serial/model numbers, and voltage types.
To display tower information:
At the Smart CDU: prompt, type show towers and press Enter .
Example
Smart CDU: show towers<Enter>
Tower ID: .A
Name: TowerA
Product S/N: AA06F011157
Model No.: CS-24V2-C20
3-Phase: No
Power Type: AC
More (Y/es N/o):
Environmental Monitor Administration
Creating a descriptive Environmental Monitor name:
The Set Envmon Name command assigns a descriptive name to the integrated Environmental Monitor. This descriptive name is displayed when the Evnmon command is issued.
To create an Environmental Monitor name:
At the Smart CDU: prompt, type set envmon name followed by the absolute environmental monitor name, then a descriptive name of up to 24 alphanumeric and other typed characters - (ASCII 33 to 126 decimal) are allowed; spaces are not allowed. Press Enter .
Example
The following command adds the descriptive name Florida_HQ_1to the Environmental Monitor:
Smart CDU: set envmon name .a Florida_HQ_1<Enter>
Creating a descriptive temperature/humidity sensor name:
The Set Envmon THS Name command assigns a descriptive name to a temperature/humidity sensor. This descriptive name is displayed when the Evnmon command is issued.
To create a temperature/humidity sensor name:
At the Smart CDU: prompt, type set envmon ths name followed by the absolute name of the temperature/humidity sensor, then a descriptive name of up to 24 alphanumeric and other typed characters - (ASCII 33 to 126 decimal) are allowed; spaces are not allowed. Press Enter .
Example
The following command adds the descriptive name T/H2_Florida_HQ_1 to the second temperature/humidity sensor:
Smart CDU: set envmon ths name .a2 T/H2_Florida_HQ_1<Enter>
Smart POPS PDU
Installation and Operations Manual Operations
•
67
Serial Port Administration
Creating a descriptive serial port name:
The Set Port Name command assigns a descriptive name to a serial port. You may use this name in commands that require a port name as an alternative to using the port’s absolute name.
To create a port name:
At the Smart CDU: prompt, type set port name followed by the absolute outlet name, then a descriptive name of up to 24 alphanumeric and other typed characters - (ASCII 33 to 126 decimal) are allowed; spaces are not allowed; port names are not case sensitive. Press Enter .
Example
The following command adds the descriptive name Rack1 to Console port:
Smart CDU: set port name console Rack1<Enter>
Setting the serial ports data-rate:
The Set Port Speed command sets the default data-rate for the serial port.
Valid data-rates are 1200, 2400, 4800, 9600, 19200, 38400, 57600 and 115200.
To set the serial port data-rate:
At the Smart CDU: prompt, type set port speed , follow by the data-rate and press Enter .
Example
The following command sets the serial ports data-rate to 38400 BPS:
Smart CDU: set port speed 38400<Enter>
Enabling or disabling active signal checking for serial connections:
The Set Port DSR Check command enables or disables active signal checking for serial connections to devices attached to any of the available serial ports.
To enable or disable active signal checking for serial connections:
At the Smart CDU: prompt, type set port dsrcheck console , on or off, and press Enter .
Setting the serial port timeout value:
The Set Port Timeout command sets the serial port inactivity timeout period. The timeout period defines the maximum period of inactivity before automatically closing the Pass-Thru session.
The valid range for the timeout is 0 to 60 (in minutes). The default timeout is 5 minutes. The command can be used to set individual ports by ID or name.
NOTES :
•
Setting the timeout value to “0” disables the timer.
•
Only a numeric value is accepted.
To set the serial port timeout value for an individual port:
At the Smart CDU: prompt, type set port timeout , followed by the port ID or name, followed by a timeout value from 0 to 60 (in minutes), and press Enter .
68
•
Operations Smart POPS PDU
Installation and Operations Manual
Configuring the Bluetooth™ options:
If the PDU has been equipped for the mobile monitoring solution using Bluetooth ® technology, several Bluetooth parameters will be available for editing on the Serial Ports configuration page.
To set the Bluetooth™ module name:
The Bluetooth™ module name displays in the list of discovered modules on the Android device. The default is “ST
Eye”, and the module name cannot be blank.
At the Smart CDU: prompt, type set bluetooth name , followed by 1-31 characters of a descriptive name for the module, and press Enter .
To set the Bluetooth™ discoverability:
Three discoverability settings determine the current status of the pushbutton on the Bluetooth module:
•
Always - The Bluetooth module is discoverable, even without pressing the pushbutton.
•
Limited (Default) - The pushbutton on the Bluetooth module must be pressed to make the module discoverable for 60-seconds.
•
Never - The Bluetooth module is never in discoverable mode.
At the Smart CDU: prompt, type set bluetooth discover , followed by always , limited , or never , and press Enter .
To set the Bluetooth™ pin code:
The pin code is available for legacy Bluetooth modules that require a pin to pair the module. Although not used in current Bluetooth modules, the pin code is supported if needed. The default is 9611.
At the Smart CDU: prompt, type set bluetooth pincode , followed by 4-digits from 0000 to 9999, and press Enter .
To set the Bluetooth™ transmission power:
This setting is the designated transmission power (dbm) for the Bluetooth module. Note that lowering the transmission power reduces the effective range of the module. Default is 0
At the Smart CDU: prompt, type set bluetooth transpwr , followed by a value from -6 to 4 (dbm), and press Enter .
Smart POPS PDU
Installation and Operations Manual Operations
•
69
Enabling or disabling the Command Line Interface (CLI):
This option enables or disables availability of the CLI for issuing action commands to the PDU. If disabled, only the firmware Web user interface will be available.
To enable or disable the CLI:
At the Smart CDU: prompt, type set port cli , follow by the serial port name, followed by enabled or disabled , and press Enter .
Enabling or disabling the Serial Command Protocol (SCP):
This option allows SCP functions to be enabled or disabled for a specific serial port.
To enable or disable the SCP:
At the Smart CDU: prompt, type set port scp , follow by the serial port name, followed by enabled or disabled , and press Enter .
Enabling or disabling the Serial Command Protocol (SCP) emulation:
This option notifies SCP of an MRV device on a specific serial port.
To enable or disable the SCP emulation:
At the Smart CDU: prompt, type set port scp , followed by emulate , followed by none or MRV , and press Enter .
Enabling or disabling the RFTAG option:
This option makes RF Code sensor tags available for the Server Technology wireless monitoring solution.
To enable or disable the RF Code sensor options:
At the Smart CDU: prompt, type set port rftag , follow by the serial port name, followed by enabled or disabled , and press Enter .
Displaying serial port information:
The Show Ports command displays information about all serial ports. This information includes:
•
•
Serial port data rate
Descriptive port name, if applicable
•
DSR signal checking settings
• Bluetooth™ parameter settings, if applicable
To display serial port information:
At the Smart CDU: prompt, type show ports and press Enter .
Example
The following command displays all serial port information:
Smart CDU: show ports<Enter>
Serial Port Configuration
Port ID: Console
DSR Check: ON
Port Name: CONSOLE
CLI: Enabled SCP: Disabled RFTAG: Enabled
Data Rate: 9600 Connection Timeout: 5 minutes
Port ID: Aux
DSR Check: ON
Port Name: AUX
CLI: Enabled SCP: Enabled
Data Rate: 115200 Connection Timeout: 5 minute<s>
Bluetooth Settings:
Name: ST Eye – 10.1.2.77
Discoverability: LIMITED
Pin code: 9611
Transmission pwr: 0 <dbm>
Command successful
70
•
Operations Smart POPS PDU
Installation and Operations Manual
System Administration
Creating a pre-login banner:
The Set Banner command specifies text that appears prior to the login authentication. This feature allows administrators to configure a message up to 2069 characters for display of legal, disclaimer or other text as required by application. If left blank, the user will be taken directly to the login prompt.
NOTES:
For SSH sessions only:
•
The “keyboard-interactive” authentication method must be used for the banner to display.
•
Banner length is truncated to 1500 bytes in SSH packets to avoid failure of SSH connection when configured with a long login banner.
To create a pre-login banner:
At the Switched CDU: prompt, type set banner and press Enter . Type the desired pre-login banner text and when finished type Ctrl-z .
Creating a location description:
The Set Location command specifies text that appears in the Location field of the Web screen. The text is also appended to a Welcome to banner that appears when a user successfully logs in serially or through a Telnet session.
If you do not issue this command, or if you issue this command without specifying any text, the control screen’s
Location field will be blank and no Welcome to banner will be displayed.
To create a location description:
At the Switched CDU: prompt, type set location followed by a descriptive name of up to 24 alphanumeric and other typed characters - (ASCII 33 to 126 decimal) are allowed; spaces are allowed. Press Enter .
Omitting any characters after typing ‘set location’ deletes any previously specified text.
Examples
The following command specifies Florida HQ as the descriptive location for the control screen and the login banner:
Switched CDU: set location Florida HQ<Enter>
The following command deletes any previously specified location description:
Switched CDU: set location<Enter>
In this case, the control screen’s Location field will be blank, and no welcome banner will be displayed after a successful login.
Setting the system area:
The Set System Area command is used to set the total area for the system. This value is used for total system power calculations.
To set the system area:
At the Switched CDU: prompt, type set system area , followed by the system area (in square feet) and press Enter .
Example
The following command sets the total system area to 6.3 square feet:
Switched CDU: set system area 6.3<Enter>
Setting the system area unit of measure:
The Set System Area Unit command sets the value for the system area footprint in either square meters or square feet.
The default unit of area is a square meter.
To set the system area unit of measure:
At the Switched CDU: prompt, type set system areaunit , followed by squaremeter or squarefoot, and press Enter .
Smart POPS PDU
Installation and Operations Manual Operations
•
71
Setting the power factor:
The Set System PF command sets the power factor used in the total system power calculation. The valid range is .50 to 1.00.
To set the power factor:
At the Switched CDU: prompt type set system pf, followed by the power factor, and press Enter .
Setting the 3-phase load out-of-balance threshold:
The Set System Balance command determines when the current on the lines of a 3-phase system are out-of-balance between the three phases of power.
To set the 3-phase load out-of-balance threshold:
At the Switched CDU: prompt, type set system balance , followed by the load out-of-balance threshold (in percent), and press Enter .
Example:
The following command sets the 3-phase load out-of-balance threshold to 20%.
Switched CDU: : set system balance 20<Enter>
Setting the 3-phase load out-of-balance alert:
The Set System Balance Alert command enables or disables the sending of an alert when the current on the lines of a
3-phase system are past a pre-set threshold (percentage) and are out-of-balance between the three phases of power.
At the Switched CDU: prompt, type set system balancealert , followed by enabled or disabled , and press Enter .
Example:
The following command enables the load out-of-balance alert:
Switched CDU: : set system balancealert enabled<Enter>
NOTES:
•
When a device with 3-phase input voltage is out-of-balance, efficiency is reduced and the unit is prevented from reaching maximum
capacity. When an alert for the out-of-balance condition is received (if the alerting feature is enabled), it may be necessary to adjust
distribution of the loads.
•
For 3-phase systems, if the Out-of-Balance Alerting feature is enabled, and the system goes into a load out-of-balance condition, the
System Status command will display the alert “3ph Out-of-Balance” in the Tower Status section, unless there is a higher priority tower
error state to report.
72
•
Operations Smart POPS PDU
Installation and Operations Manual
Displaying system configuration information:
The Show System command displays all system configuration information.
•
Firmware version
•
NIC module serial number and MAC address
•
•
•
System location description
•
Hardware revision code and Flash size
Uptime since last system restart
Area (footprint) and power factor
•
3-phase load out-of-balance threshold and alert status
To display system configuration information:
At the Switched CDU: prompt, type show system and press Enter .
Example
System Information
F/W Version: Sentry Version 6.0a
NIC S/N: 1600001
MAC Address: 00-0a-9c-10-00-01
H/W Rev Code: 0
Flash Size: 2 MB
Uptime: 0 days 6 hours 14 minutes 1 second
Location: Florida HQ
Area <Footprint>: 6.3 square feet
Power Factor: 0.80
3-Phase Load Out-of-Balance
Threshold: 20 percent
Alerting: Enabled
Displaying system power status:
The System Status command displays system power and tower information.
To display system power status:
At the Switched CDU: prompt, type sysstat and press Enter .
Example
Switched CDU: sysstat
System Power Status
Total Power Consumption: 170 Watts
Area <Footprint>: 100.0 Square Meters
Watts Per Area Unit: 2 Watts Per Square Meter
Tower Status
Tower Tower Tower
ID Name Status
.A TowerA Normal
.B TowerB Normal
Command successful
NOTE: For 3-phase systems, if the Out-of-Balance Alerting feature is enabled, and the system goes into a load out-of-balance condition, the System Status command will display the alert “3ph Out-of-Balance” in the Tower Status section, unless there is a higher priority tower error state to report.
Smart POPS PDU
Installation and Operations Manual Operations
•
73
Configuring the LED display orientation:
The Set Option Display command configures the LED display orientation.
To configure the LED display orientation:
At the Switched CDU: prompt, type set option display , followed by normal, inverted , or auto , and press Enter .
Example
The following sets the LED display orientation to Inverted:
Switched CDU: set option display inverted<Enter>
NOTES:
•
Only specific PDU models are equipped with an accelerometer chip that senses device orientation. If equipped, your PDU automatically
aligns the LED display orientation depending on its current direction, and “Auto” will display in the Show Options command by default.
In addition, the actual mounting of the unit, such as such as “<Normal> or <Inverted>”, appears to the right of the "Auto" option when
you issue the Show Options command. However, even if your model does have the sensor for device orientation, you can still
issue the Set Option Display command with either the Normal or Inverted option to override the capability of the hardware.
•
If your model does not have the accelerometer chip, you will need to configure the LED display orientation by entering the Normal
or Inverted option.
Enabling or disabling strong passwords:
The Set Option Strong Password command is used to enable or disable the requirements for strong passwords. When enabled, all new passwords must be a minimum of 8 characters in length with at least one uppercase letter, one lowercase letter, one number and one special character.
To enable or disable strong passwords:
At the Switched CDU: prompt, type set option strong password , followed by enabled or disabled and press Enter .
Enabling or disabling the external configuration reset button:
The Set Option Button command enables or disables the external configuration reset button. This feature can enhance system security by protecting the PDU configurations from being reset locally.
NOTE: If this feature has been enabled and the administrative account username/password has been lost, then the PDU must be returned to the factory for non-warranty reset of the configuration.
To enable or disable the configuration reset button:
At the Switched CDU: prompt, type set option button , followed by enabled or disabled and press Enter .
Enabling or disabling the ‘more’ prompt:
The Set Option More command enables or disables the ‘more’ prompt for display of data larger than the terminal window.
To enable or disable ‘more’:
At the Switched CDU: prompt, type set option more , followed by enabled or disabled and press Enter .
Setting the outlet sequence order:
The PDU allows the configuration of power-on sequence for outlets.
The Normal option powers-on outlets in ascending numeric order by outlet number, for example, from outlet 1-8. The
Reversed option powers on outlets in descending order by outlet number; for example, from outlet 8-1.
The Reversed option is useful when the PDU is mounted with inverted orientation and the last outlet (in this example, outlet 8) is in the first position.
At the Switched CDU: prompt, type set option outletsequence , followed by normal or reversed , and press Enter .
Setting the temperature scale:
The Set Option TempScale command sets the temperature scale reported by the PDU.
To set the temperature scale:
At the Switched CDU: prompt, type set option tempscale , followed by celsius or fahrenheit and press Enter .
74
•
Operations Smart POPS PDU
Installation and Operations Manual
Configuring the Command Line Interface (CLI) session timeout:
The Set Option CLI Timeout command configures the CLI session timeout in minutes.
The valid timeout range is 1 to 1440 minutes (24 hours). The default session timeout is 5 minutes.
To configure the CLI Session Timeout:
At the Switched CDU: prompt, type set option clitimeout , followed by the session timeout (in minutes), and press
Enter .
Example:
The following command sets the CLI session timeout to 15 minutes:
Switched CDU: set option clitimeout 15<Enter>
Configuring the web session (Web Interface) timeout:
The Set Option Web Timeout command configures the Web session timeout in minutes.
The valid timeout range is 1 to 1440 minutes (24 hours). The default session timeout is 5 minutes.
To configure the web session timeout:
At the Switched CDU: prompt, type set option webtimeout , followed by the session timeout (in minutes), and press
Enter .
Example:
The following command sets the web session (Web Interface) timeout to 10 minutes:
Switched CDU: set option webtimeout 10<Enter>
Customizing the CLI prompt:
The Set Option Prompt command customizes the CLI prompt.
To customize the CLI prompt:
At the Switched CDU: prompt, type set option prompt and press Enter . Then type the custom prompt and press
Enter .
To reset the custom prompt to the default prompt, type set option prompt and press Enter . When prompted, leave blank and press Enter .
The maximum length of the custom prompt is 31 characters. Spaces and special characters are allowed.
Example:
The following command sets the default CLI prompt to “My Prompt”:
Switched CDU: set option prompt<Enter>
Custom prompt <blank for default>: My Prompt:
Command successful
My Prompt:
Enabling or Disabling StartUp Stick:
The Set Option Startupstick command enables or disables the StartUp Stick tool for PDU mass configuration of operating parameters.
To enable or disable StartUp Stick:
At the Switched CDU: prompt, type set option startupstick , followed by enabled or disabled and press Enter .
Smart POPS PDU
Installation and Operations Manual Operations
•
75
To enable or disable coldboot alert:
Upon a coldboot of the system (if the Coldboot Alert feature is enabled), the system sends a ½ second RS-232 break out on any serial ports that are also enabled.
The Set Option Coldboot Alert command enables or disables the Coldboot Alert feature.
To enable or disable coldboot alert:
At the Switched CDU: prompt, type set option cbalert , followed by enabled or disabled , and press Enter .
To enable or disable the Serial Command Protocol (SCP) authentication:
The Set SCP Authentication command enables or disables SCP Authentication.
To enable or disable SCP:
At the Switched CDU: prompt, type set scpauth , followed by enabled or disabled , and press Enter .
To set the Serial Command Protocol (SCP) authentication user:
The Set SCPAuth User command sets the username and password for SCPAuthentication.
To set SCP username:
At the Switched CDU: prompt, type set scpauth user , followed by user name, and press Enter . You will be prompted to enter and verify a password.
Displaying system options:
The Show Options command displays settings for all system options.
To display system option information:
At the Switched CDU: prompt, type show options and press Enter .
Example
Switched CDU: show options
System Options
Display Orientation: Auto <Normal>
Outlet Sequence Order: Normal
Strong Passwords: Disabled
Configuration Reset Button: Enabled
More Prompt: Enabled
Temperature Scale: Celsius
CLI Custom Prompt: <none>
CLI Session Timeout: 10 minutes
Web Session Timeout: 10 minutes
Coldboot Alert <SCP>: Enabled
StartUp Stick: Enabled
NOTE: The display of “<SCP>” after the Coldboot Alert parameter in the Show Options command (as indicated above) shows a relationship between the Serial Command Protocol (SCP) and the Coldboot Alert feature. Upon a coldboot of the system, if the Coldboot
Alert feature is enabled, the system will send a ½ second RS-232 break out to to any SCP-enabled serial ports.
76
•
Operations Smart POPS PDU
Installation and Operations Manual
Displaying the firmware version:
The Version command displays the firmware version.
To display the firmware version:
At the Switched CDU: prompt, type version and press Enter .
Performing a warm boot:
The Restart command performs a warm boot of the PDU.
NOTE: System user/outlet/group/port configuration or outlet states are not changed or reset with the Restart command.
To perform a warm boot:
At the Switched CDU: prompt, type restart and press Enter .
Enabling or disabling the Cisco EnergyWise network:
NOTE: Only commands through the CLI are supported for the Cisco EnergyWise network. There is no firmware web-based interface for
EnergyWise. Enabling EnergyWise requires a system restart.
The Set EnergyWise command enables or disables the EnergyWise network support:
To enable or disable EnergyWise:
At the Switched CDU: prompt, type set energywise , followed by enabled or disabled , and press Enter .
Example
Switched CDU: set energywise enabled
Command successful – - restart required
Setting up PDUs in the Cisco EnergyWise network:
NOTE: To use EnergyWise, you must first configure domain name, port, and secret.
The Set EnergyWise Domain command configures the EnergyWise domain the PDU belongs to. The limit of the Domain
Name is 64 characters.
To set the EnergyWise domain name:
At the Switched CDU: prompt, type set energywise domain , followed by the domain name, and press Enter .
Example
Switched CDU: set energywise domain 10.1.2.120
Command successful
To set the EnergyWise port:
The default port number is 43440; the valid range for port numbers is 1-65535.
At the Switched CDU: prompt, type set energywise port , followed by the port number, and press Enter .
Example
Switched CDU: set energywise port
Port [666]: 700
Command successful
To set the EnergyWise secret:
The limit of the Secret field is 64 characters. A blank secret is also acceptable.
At the Switched CDU: prompt, type set energywise secret , then verify the secret, and press Enter .
Example
Switched CDU: set energywise secret
Secret: ********
VerifySecret: ********
Command successful
Smart POPS PDU
Installation and Operations Manual Operations
•
77
To set a blank EnergyWise secret:
A blank secret is acceptable.
At the Switched CDU: prompt, type set energywise secret , do not type in the Secret field, and press Enter twice (to bypass the Secret field and then VerifySecret field.)
Example of a blank secret
Switched CDU: show energywise
EnergyWise Configuration
Endpoint: Enabled *
Port: 666
Domain: (undefined)
Refresh Rate: 60
Secret: (Blank)
Command successful
To set the EnergyWise refresh rate:
The EnergyWise refresh rate is the rate (in seconds) at which new information is pushed to the EnergyWise manager.
Valid range is 30-600 seconds; default is new data sent to the EnergyWise manager every 3 minutes.
At the Switched CDU: prompt, type set energywise refresh , followed by a rate (in seconds) from 30-600, and press
Enter .
Viewing Cisco EnergyWise network parameters:
NOTE : A change in any value (shown in the example below) requires a restart of the system.
To view EnergyWise network parameters:
At the Switched CDU: prompt, type show energywise , and press Enter .
Example
Switched CDU: show energywise
EnergyWise Configuration
Endpoint: Enabled*
Port: 666
Domain: <undefined>
Refresh Rate: 55
Secret: ********
Command successful
78
•
Operations Smart POPS PDU
Installation and Operations Manual
TCP/IP Administration
NOTE: A restart of the unit is required after setting or changing ANY TCP/IP configurations.
Enabling or disabling DHCP support:
The Set DHCP command enables or disables DHCP support.
To enable or disable DHCP support:
At the Smart CDU: prompt, type set dhcp , followed by enabled or disabled , and press Enter .
Enabling or disabling DCHP boot delay:
The Set DHCP Boot Delay command enables or disables the DHCP boot delay option.
•
Enabling the Boot Delay option gives the PDU approximately 100-seconds to establish a connection through a DHCP server.
This interval allows various network component activities to occur as the PDU powers up
(such as obtaining SNTP time stamps for logging). This is the default state.
•
Disabling the Boot Delay option forces the PDU to boot after approximately 5-seconds regardless of the
DHCP acquisition state. This speeds up a boot when a DHCP server is connected to one of the outlets on the
PDU. In this configuration, SNMP traps, SNTP and other protocols will not be available until a DHCP address has been resolved.
To enable the boot delay:
At the Smart CDU: prompt, type set dhcp , followed by bootdelay , followed by enabled or disabled , and press
Enter .
NOTES:
•
The Boot Delay option executes only when DHCP is enabled.
•
The firmware can detect network link integrity and will wait for network connection. This means that if the network is not currently
connected, the enabled Boot Delay option will be ignored.
Smart POPS PDU
Installation and Operations Manual Operations
•
79
Enabling or disabling DCHP static address fallback:
NOTE: DHCP must be enabled to activate the DHCP Static Address Fallback option.
The Set DHCP Static Address Fallback command enables or disables the DHCP static address fallback option.
•
Enabling the Static Address Fallback option informs the PDU to automatically fall back to a static address if a DHCP server does not respond after 100-seconds. This is the default state.
•
Disabling the Static Address Fallback option generates periodic DHCP server requests until the PDU obtains a dynamic address.
To enable the static address fallback:
At the Smart CDU: prompt, type set dhcp , followed by staticfallback , followed by enabled or disabled , and press
Enter .
NOTE: If the DHCP server boot time is excessive, you may need to disable the DHCP Static Address Fallback option.
Setting the network acquisition method:
The Set Net command determines the acquisition method used for the protocol stack and IPv4/IPv6 address.
At the Smart CDU prompt: type set net ; followed by disabled, ipv4only, or dualv6v4; and press Enter .
Setting the IP address:
The Set IP Address command sets the TCP/IP address of the network interface controller.
NOTE: Both IPv4 and IPv6 IP address formats are accepted.
To set the IP address:
At the Smart CDU: prompt, type set ipaddress , followed by the IP address and press Enter .
Example
The following command sets the IP address to 12.34.56.78:
Smart CDU: set ipaddress 12.34.56.78<Enter>
Setting the subnet mask:
The Set Subnet command sets the subnet mask for the network the PT40 will be attached to.
To set the subnet mask:
At the Smart CDU: prompt, type set subnet , followed by the subnet mask and press Enter .
Example
The following command sets the subnet mask to 255.0.0.0
Smart CDU: set subnet 255.0.0.0<Enter>
Setting the gateway:
The Set Gateway command sets the IP address of the default gateway the unit uses to access external networks.
To set the gateway IP address:
At the Smart CDU: prompt, type set gateway , followed by the gateway IP address and press Enter .
Example
The following command set the gateway IP address to 12.34.56.1:
Smart CDU: set gateway 12.34.56.1<Enter>
80
•
Operations Smart POPS PDU
Installation and Operations Manual
Setting the DNS IP address:
The Set DNS command sets the TCP/IP address of the Domain Name System (DNS) server.
To set the DNS IP address:
At the Smart CDU: prompt, type set , followed by dns1 or dns2 and the Domain Name System (DNS) server’s IP address. Press Enter .
NOTE: Both IPv4 and IPv6 formats are accepted for DNS IP address.
Example
The following command sets the primary Domain Name System (DNS) server IP address to 98.76.54.254:
Smart CDU: set dns1 98.76.54.254<Enter>
Displaying network configuration information:
The Show Network command displays TCP/IP, Telnet, SSH, Web, SSL, SNMP, and DHCP options (when DHCP is enabled) configuration information. The Show Network command also displays all IPv4 and IPv6 settings
•
Network configuration: IP address, subnet mask, gateway and DNS IP addresses (both IPv4 and IPv6 formats are displayed).
•
Enabled-disabled status and port numbers for Telnet, SSH, HTTP, SSL, SNMP, and FTP Server support.
•
Network status: Link, speed, duplex, and negotiation.
•
DHCP boot delay and DHCP static address fallback options (when DHCP is enabled).
•
Enabled-disabled status of Sentry Power Manager (SPM).
To display network configuration information:
At the Smart CDU: prompt, type show network and press Enter .
Example
The following command displays the network configuration information:
Smart CDU: show network
Network Settings
State: DHCP IPv6/IPv4 Network: Dual IPv6/IPv4
Link: Up Negotiation: Auto
Speed: 100 Mbps Duplex: Full
AutoCfg IPv6: FE80::20A:9CFF:FE52:4104/64
IPv6 Address: FD01::1:B51A:E03C/64
IPv4 Address: 10.1.6.230 Subnet Mask: 255.255.0.0
IPv4 Gateway: 10.1.1.1
DNS1: FD01::A01:585
DNS2: 10.1.5.133
Static IPv4/IPv6 Settings
IPv6 Address: FD01::A01:353/64
IPv6 Gateway: ::
IPv4 Address: 10.1.2.253 Subnet Mask: 255.255.0.0
IPv4 Gateway: 10.1.1.1
DNS1: 10.1.5.133
DNS2: 10.1.5.134
Smart POPS PDU
Installation and Operations Manual Operations
•
81
DHCP Settings
DHCP: Enabled
FQDN: Enabled [sentry3-524104]
Boot Delay: Enabled
Static Fallback: Enabled
Network Services
Telnet: Enabled Port: 23
SSH: Enabled Port: 22 Auth: Password, Kb-Int
HTTP: Enabled Port: 80
SSL: Enabled Port: 443 Installed Cert: User Encrypted
Access: Optional Stored Files: Cert & Key
User Cert: Enabled User Passphrase: <set>
SNMPv1/2: Enabled Port: 161 TrapPort: 162
SNMPv3: Disabled Port: 161 TrapPort: 162
FTP Server: Enabled Port: 21
SPM Access: Enabled
Command successful
NOTE: The fields IPv4 Address, IPv4 Subnet Mask, IPv4 Gateway, DNS1, and DNS2 are equivalent to existing PDU IPv4 settings except that current network settings and static settings are displayed separately. This allows you to view both static configuration settings and active network settings that can be obtained using DHCP. The DNS addresses can be IPv4 or IPv6 format at this time (based on RFC4291).
82
•
Operations Smart POPS PDU
Installation and Operations Manual
HTTP Administration
NOTE: A restart is required after setting or changing ANY Telnet/Web configurations.
Enabling and disabling HTTP support:
The Set HTTP command is used to enable or disable HTTP support.
To enable or disable HTTP support:
At the Smart CDU: prompt, type set http , followed by enabled or disabled and press Enter .
Changing the HTTP server port:
With HTTP support enabled, the HTTP server watches and responds to requests on the default HTTP port number 80. This port number may be changed using the Set HTTP Port command.
To change the HTTP port:
At the Smart CDU: prompt, type set http port , followed by the port number and press Enter .
Example
The following changes the HTTP port number to 2048:
Smart CDU: set HTTP port 2048<Enter>
Sentry Power Manager (SPM) Administration
The Sentry Power Manager (SPM) is Server Technology’s enterprise management software product for the data center. The configuration options provided allow you to enable/disable SPM and reset the SPM password to its default.
NOTE: The SPM options apply only if you are currently using Server Technology’s SPM software product.
Enabling and disabling SPM Secure Access:
The Set SPM command enables or disables support for Sentry Power Manager (SPM). If your operation does not currently use SPM software, you can disable SPM Secure Access. However, if disabled, the PDU will not be able to use the SPM suite of secure network capabilities or the advanced remote configuration.
To enable or disable SPM support:
At the Smart CDU: prompt, type set spm , followed by enabled or disabled and press Enter .
NOTE: Both HTTP and SSL must be enabled or the SPM Secure Access option will not be permitted. When SPM Secure Access is permitted, the default is Enabled.
Resetting the SPM Password:
The Set SPM Reset Password command resets the SPM password on the PDU to its internal default password.
Each PDU has a default unique SPM password that is used to communicate between SPM and the PDU. When SPM discovers a PDU in the network, SPM changes this password into a different unique password for added security. The
SPM then continues to manage or alter these passwords as required for system security.
If a PDU is relocated or swapped from the system after a password was generated, SPM may not be able to reestablish a connection to the unit. The Set SPM Reset Password command allows you to reset to the internal default password of the PDU so SPM can re-discover the device and add it to the system. Once the unit has been acquired by
SPM, no further action is necessary.
To reset the SPM password:
At the Smart CDU: prompt, type set spm , followed by resetpw and press Enter .
NOTE: Do not reset the password if SPM communication has already been established.
Smart POPS PDU
Installation and Operations Manual Operations
•
83
Telnet Administration
NOTE: A restart of the unit is required after setting or changing any Telnet/Web configurations.
Enabling and disabling Telnet support:
The Set Telnet command is used to enable or disable Telnet support.
To enable or disable Telnet support:
At the Smart CDU: prompt, type set telnet , followed by enabled or disabled and press Enter .
Changing the Telnet port:
With Telnet support enabled, the Telnet server watches and responds to requests on the default Telnet port number 23.
This port number may be changed using the Set Telnet Port command.
To change the Telnet socket:
At the Smart CDU: prompt, type set telnet port , followed by the port number and press Enter .
Example
The following changes the Telnet port number to 7001:
Smart CDU: set telnet port 7001<Enter>
FTP Administration
You may upload new versions of firmware into the Smart POPS PDU using File Transfer Protocol (FTP). This allows access to new firmware releases for firmware improvements and new features additions. The following commands are used to configure the unit for an FTP firmware upload.
NOTE: Secure File Transport Protocol (SFTP) is also supported for encrypted SSH transport over the network.
Setting the FTP host address:
The Set FTP Host command sets the FTP host IP address or hostname allowing for firmware file uploads.
To set the FTP Host address:
At the Smart CDU: prompt, type set ftp host , followed by the IP address or hostname and press Enter .
NOTE: Both IPv4 and IPv6 formats are accepted for IP address or hostname.
Examples
The following command sets the FTP host IP address to 12.34.56.99:
Smart CDU: set ftp host 12.34.56.99<Enter>
The following command sets the FTP hostname to ftp.servertech.com:
Smart CDU: set ftp host ftp.servertech.com<Enter>
Setting the FTP username:
The Set FTP Username command sets the username as required by the FTP Host.
To set the FTP username:
At the Smart CDU: prompt, type set ftp username , followed by the FTP username and press Enter .
Example
The following command sets the FTP username to Guest:
Smart CDU: set ftp username guest<Enter>
Setting the FTP Password:
The Set FTP Password command sets the password as required by the FTP Host.
To set the FTP password:
At the Smart CDU: prompt, type set ftp password , followed by the FTP password and press Enter .
Example
The following command sets the FTP password to OpenDoor:
Smart CDU: set ftp password OpenDoor<Enter>
84
•
Operations Smart POPS PDU
Installation and Operations Manual
Setting the filename to be uploaded:
The Set FTP Filename command sets the filename of the firmware file to be uploaded.
To set the FTP filename:
At the Smart CDU: prompt, type set ftp filename , followed by the firmware filename and press Enter .
Example
The following command sets the FTP filename to snb_s50a.bin:
Smart CDU: set ftp filename smcdu-v60g.bin<Enter>
Setting the directory for the file to be uploaded:
The Set FTP Directory command sets the directory for the firmware file to be uploaded.
To set the FTP directory:
At the Smart CDU: prompt, type set ftp directory , followed by the directory and press Enter .
Example
The following command sets the FTP directory to ftp://Sentry:
Sentry: set ftp directory ftp://sentry<Enter>
Enabling or disabling automatic updates:
The Set FTP Autoupdate command is used to enable or disable automatic firmware update support.
To enable or disable automatic updates:
At the Smart CDU: prompt, type set ftp autoupdate , followed by enabled or disabled and press Enter .
Setting the automatic update scheduled day:
The Set FTP Autoupdate Day command is used to set the day when automatic updates occur.
To set the automatic update day:
At the Smart CDU: prompt, type set ftp autoupdate day , followed by a day of the week or everyday and press Enter .
Example
The following command sets the automatic update day to Sunday:
Smart CDU: set ftp autoupdate day sunday<Enter>
Setting the automatic update scheduled hour:
The Set FTP Autoupdate Hour command is used to hour of the day when automatic updates occur.
To set the automatic update hour:
At the Smart CDU: prompt, type set ftp autoupdate hour , followed by an hour of the day and press Enter .
Examples
The following command sets the automatic update hour to 12 AM:
Smart CDU: set ftp autoupdate hour 12am<Enter>
The following command sets the automatic update hour to 3 PM:
Smart CDU: set ftp autoupdate hour 3pm<Enter>
Testing the FTP upload configuration:
The Set FTP Test command validates that the PDU can login to the FTP server and verify/download the firmware file.
To test the FTP upload configuration:
At the Smart CDU: prompt, type set ftp test , and press Enter .
Smart POPS PDU
Installation and Operations Manual Operations
•
85
Displaying FTP configuration information:
The Show FTP command displays all FTP configuration information.
•
FTP Host IP address
•
FTP Host username and password
•
Firmware filepath and filename
•
Configuration of automatic updates
To display FTP configuration information:
At the Smart CDU: prompt, type show ftp and press Enter .
Example
The following command displays the FTP configuration information:
Smart CDU: show ftp<Enter>
FTP Configuration
Host: 10.1.2.100
Username: djones
Password: *******
Directory: /firmware/7.0d
Filename: smcdu-v70d.bin
FTP Automatic Updates Configuration
Automatic Updates: Disabled
Scheduled Day: Everyday
Scheduled Hour: 1 PM
SNTP Administration
The Smart POPS PDU supports the use of a network time service to provide a synchronized time reference.
About Daylight Saving Time(DST)
Support for DST is disabled by default. When enabled, the date and time are automatically adjusted forward one hour between the starting and ending dates and times (which can be configured).
NOTE: If Daylight Saving Time (DST) is enabled, all system time displays will be shown with the current DST start/end date/time settings.
The default time zone is set for the United Stated until at least 2015.
The time zone format is: mo.w.d/h:m:s , as follows: mo = month from January to December (1-12) w = week number (1-4) or the last week (5) d = day of week from Sunday to Saturday (0-6) h = hour (0-23) m = minute (0-59) s = second (0-59)
86
•
Operations Smart POPS PDU
Installation and Operations Manual
Setting the SNTP server address:
The Set SNTP command is used to set the primary and secondary SNTP server addresses.
To set the SNTP server address:
At the Smart CDU: prompt, type set sntp , followed by primary or secondary , and the SNTP server IP address or hostname. Press Enter .
NOTES:
•
The primary/secondary IP addresses contact the SNTP server; these addresses are populated with the external NTP pool time zones
“2.servertech.pool.ntp.org” and “1.servertech.pool.ntp.org” as default for new PDUs that have not yet been time set.
•
Both IPv4 and IPv6 formats are accepted for primary/secondary IP address or hostname.
Examples
The following command sets the primary SNTP server address to 204.152.184.72:
Smart CDU: set sntp primary 204.152.184.72<Enter>
The following command sets the secondary SNTP server address to cuckoo.nevada.edu:
Smart CDU: set sntp secondary cuckoo.nevada.edu<Enter>
Setting the local GMT offset (hours/minutes):
The Set SNTP GMToffset command is used to set the offset from GMT for the date/time returned by SNTP.
The GMT offset supports all standard international time zones from -12:59 to +14.59. The GMT offset can be set in minutes to accommodate partial-hour time zones.
NOTE: The unit does not support automatic adjustment for Daylight Saving Time (DST).
To set the local GMT offset:
At the Smart CDU: prompt, type set sntp gmtoffset , followed by the offset value, and press Enter .
Examples
The following command sets the local GMT offset to -12:
Smart CDU: set sntp gmtoffset -12<Enter>
Displaying SNTP configuration information:
The Show SNTP command displays all SNTP configuration information.
To display SNTP configuration information
At the Smart CDU: prompt, type show sntp and press Enter .
Example
The following command displays the SNTP configuration information:
Smart CDU: show sntp <Enter>
Date/Time (Local GMT Offset -12): 2006-02-21 21:32:48
Primary Host: 204.152.184.72
Secondary Host: cuckoo.nevada.edu
Enabling or disabling Daylight Saving Time (DST):
The Set SNTP DST command enables or disables Daylight Saving Time.
To set daylight saving time:
At the Smart CDU: prompt, type set sntp dst , followed by enabled or disabled , and press Enter .
Smart POPS PDU
Installation and Operations Manual Operations
•
87
Configuring start day/time Daylight Saving Time (DST):
The Set SNTP DST Start command sets the DST start day/time in the format m.w.d/h:m:s, as follows: mo = month from January to December (1-12) w = week number (1-4) or the last week (5) d = day of week from Sunday to Saturday (0-6) h = hour (0-23) m = minute (0-59) s = second (0-59)
To set daylight savings start day/ time:
At the Smart CDU: prompt, type set sntp dst start , followed by [formatted m.w.d/h:m:s as described above], and press Enter .
Examples
The following command sets the DST start day/time parameters:
Smart CDU: set sntp dst start 4.1.3/5:10:6<Enter>
Displaying SNTP configuration information:
The Show SNTP command displays all SNTP configuration information.
To display SNTP configuration information
At the Smart CDU: prompt, type show sntp and press Enter .
Example
The following command displays the SNTP configuration information:
Smart CDU: show sntp <Enter>
Date/Time: 2013-04-13 15:21:18
Primary Host: 204.152.184.72
Secondary Host: 2.pool.ntp.org
Local GMT Offset: -8
Use DST: Enabled
Start Date: 1 st Wednesday in April
Start Time: 04:18:06
End Date: 1 st Sunday in November
End Time: 02:00:00
88
•
Operations Smart POPS PDU
Installation and Operations Manual
UPS Administration
Creating a UPS record:
The Create UPS command adds a new UPS device to the Smart POPS PDU.
To create a UPS record:
At the Smart CDU: prompt, type create UPS and press Enter .
At the prompt, type the corresponding number from the list of the UPS types and press Enter .
At the Host Name: prompt, type the UPS’s IP address or hostname and press
Enter .
NOTE: Both IPv4 and IPv6 formats are accepted for IP address or hostname.
Example
The following command creates a UPS record for a Toshiba UPS with the hostname ‘DC1Toshiba1’:
Smart CDU: create ups<Enter>
UPS types:
1 -- APC
2 -- Liebert
3 -- MGE
4 -- Tripp Lite
5 -- Generic (RFC1628)
6 -- Hewlett Packard
7 -- Minuteman
8 -- Mitsubishi
9 -- Powerware
10 -- Toshiba
11 -- Falcon Electric
Select type(1-11): 10<Enter>
Host/IP: DC1Toshiba1<Enter>
Removing a UPS record:
The Remove UPS command removes a UPS record.
To remove a UPS record:
At the Smart CDU: prompt, type remove ups and press Enter .
At the prompt, type the index number of the UPS to be removed and press Enter .
Example
The following command removes the UPS record at index 3:
Smart CDU: remove ups<Enter>
1 Type: Liebert
Host/IP: DC1Liebert1
2 Type: Powerware
Host/IP: DC1Powerware1
3 Type: Toshiba
Host/IP: DC1Toshiba1
Select UPS(1-8): 3<Enter>
Smart POPS PDU
Installation and Operations Manual Operations
•
89
Changing the UPS type:
The Set UPS Type command is used to change the type of UPS for each UPS record.
To change a UPS record:
At the Smart CDU: prompt, type set ups type and press Enter .
At the prompt, type the index number for the UPS record to be changed and press Enter .
At the prompt, type the corresponding number from the list of the UPS types and press Enter .
Example
The following command changes UPS type for the record at index number 2 to ‘MGE’:
Smart CDU: set ups type<Enter>
1 Type: Liebert
Host/IP: DC1Liebert1
2 Type: Powerware
Host/IP: DC1Powerware1
Select UPS(1-8): 2<Enter>
UPS types:
1 -- APC
2 -- Liebert
3 -- MGE
4 -- Tripp Lite
5 -- Generic (RFC1628)
6 -- Hewlett Packard
7 -- Minuteman
8 -- Mitsubishi
9 -- Powerware
10 -- Toshiba
11 -- Falcon Electric
Select type(1-11): 3<Enter>
Changing the UPS host address:
The Set UPS Host command is used to change the IP address or hostname for each UPS record. Hostnames may be up to 60 characters long.
To change a UPS host address:
At the Smart CDU: prompt, type set ups host and press Enter .
At the prompt, type the index number for the UPS record to be changed and press Enter .
At the prompt, type IP address or hostname for the UPS and press Enter .
Example
The following command changes UPS hostname for the record at index number 2 to ‘DC1MGE1’:
Smart CDU: set ups host<Enter>
1 Type: Liebert
Host/IP: DC1Liebert1
2 Type: MGE
Host/IP: DC1Powerware1
Select UPS(1-8): 2<Enter>
Host/IP: DC1MGE1<Enter>
90
•
Operations Smart POPS PDU
Installation and Operations Manual
Changing the UPS SNMP port:
With a UPS record configured, the unit sends data requests to the default UPS SNMP port number 161. You can change this port number using the Set UPS Port command.
To change the UPS SNMP port:
At the Smart CDU: prompt, type set ups port and press Enter .
Then type the index number for the UPS record to be changed and press Enter .
Finally, type the desired port number and press Enter .
Example
The following command changes port for the UPS record at index number 1 to ‘162’:
Smart CDU: set ups port<Enter>
UPS UPS
Index Type Port
1 Liebert 161
2 MGE 161
Select UPS(1-8): 1<Enter>
Port: 162<Enter>
Changing the UPS SNMP Get community string:
With a UPS record configured, the CDI sends data requests to the UPS using the default Get community string of
‘public’. You can change this string using the Set UPS Commstr command.
NOTE: The Get community string configured on the PDU must match the read-only community string configured on the UPS.
To change a UPS SNMP community string record:
At the Switched -48 VDC: prompt, type set ups commstr and press Enter .
At the prompt, type the index number for the UPS record to be changed and press Enter .
At the prompt, type the Get community string for the UPS and press Enter .
Example
The following command changes Get community string for the record at index number 2 to ‘readonly’:
Smart CDU: set ups commstr<Enter>
UPS UPS Community
Index Type String
1 Liebert public
2 MGE public
Select UPS(1-8): 2<Enter>
Community String: readonly<Enter>
Smart POPS PDU
Installation and Operations Manual Operations
•
91
Enabling/disabling UPS voltage polling:
With a UPS record configured, by default the unit enables voltage polling of the UPS. This feature may be enabled or disabled using the Set UPS VPoll command.
To enable/ disable UPS voltage polling:
At the Smart CDU: prompt, type set ups vpoll and press Enter .
At the prompt, enter the index number for the UPS record to be changed and press Enter .
At the prompt, type on or off , and press Enter .
Example
The following command disables voltage polling for the record at index number 2:
Smart CDU: set ups vpoll<Enter>
UPS UPS Voltage
Index Type Polling
1 Liebert On
2 MGE On
Select UPS(1-8): 2<Enter>
Voltage Polling: Off<Enter>
Adding an infeed to a UPS:
The Set UPS AddInfeed command adds a logical association of an infeed to a UPS.
To add an infeed to a UPS:
At the Smart CDU: prompt, type set ups addinfeed and press Enter .
At the prompt, enter the index number for the UPS record to be changed and press Enter .
At the prompt, type the absolute infeed ID of the desired infeed, and press Enter .
Example
The following command associates infeed .aa to UPS record at index number 1:
Smart CDU: set ups addinfeed<Enter>
UPS UPS Infeed
Index Type IDs
1 Liebert
2 MGE .AA
Select UPS(1-8): 1<Enter>
Infeed ID: .aa<Enter>
Removing an infeed from a UPS:
The Set UPS DelInfeed command removes a logical association of an infeed from a UPS.
To remove an infeed from a UPS:
At the Smart CDU: prompt, type set ups delinfeed and press Enter .
At the prompt, enter the index number for the UPS record to be changed and press Enter .
At the prompt, type the absolute infeed ID of the desired infeed, and press Enter .
Example
The following command removes the association of infeed .aa from UPS record at index number 2:
Smart CDU: set ups addinfeed<Enter>
UPS UPS Infeed
Index Type IDs
1 Liebert .AA
2 MGE .AA
Select UPS(1-8): 2<Enter>
Infeed ID: .aa<Enter>
92
•
Operations Smart POPS PDU
Installation and Operations Manual
Displaying UPS configuration:
The Show UPS command displays information about all UPS devices.
•
UPS Type and Host/IP address
•
UPS SNMP port and community string
•
SNMP Objects OID values and expected return values
To display UPS configuration information:
At the Smart CDU: prompt, type show ups and press Enter .
Example
The following command displays UPS configuration information:
Smart CDU: show ups<Enter>
1 Type: Liebert
Host/IP: DC1Liebert1
Voltage Polling: ON
SNMP Configuration
Community String: public
SNMP Port: 162
SNMP Objects/Expected Values
Voltage: .1.3.6.1.2.1.33.1.4.4.1.2.1
Utility Status: .1.3.6.1.2.1.33.1.4.1.0
On Battery: 0x5
On Utility: 0x3
More (Y/es N/o):
Smart POPS PDU
Installation and Operations Manual Operations
•
93
Chapter 4: Advanced Operations
SSL 96
Enabling and Setting up SSL Support 96
SSL Technical Specifications 97
Enabling and Setting up SSH Support
Enabling and Setting Up SNMP v1/v2 Support
Enabling and Setting up SNMP Support
Enabling and Setting Up LDAP Support
Enabling and Setting up TACACS+ Support
Configuring TACACS+ Privilege Levels
TACACS+ Technical Specifications
Enabling and Setting Up RADIUS Support
Vendor-Specific Attributes (VSA):
SSL
Secure Socket Layers (SSL) enables secure web sessions between a Remote Power Manager and a remote user. SSL provides two chief features designed to make TCP/IP (Internet) transmitted data more secure:
•
Authentication: The connecting client is assured of the identity of the server.
•
Encryption: All data transmitted between the client and the server is encrypted rendering any intercepted data unintelligible to any third party.
SSL uses the public-and-private key encryption system by RSA, which also requires the use of digital certificates. An
SSL Certificate is an electronic file uniquely identifying individuals or websites and enables encrypted communication; SSL Certificates serve as a kind of digital passport or credential. The SSL Certificate of the unit enables the client to verify the authenticity of the unit and to communicate with the unit securely by an encrypted session, protecting confidential information from interception and hacking.
SSL Command Summary
Command
Set SSL
Set SSL Access
Set SSL Port
Description
Enables/disables SSL support
Sets SSL access as optional or required
Configures the SSL port number
Set SSL User Certificate Enables/disables custom user certificates
Set SSL User Passphrase Passphrase to control login access for user certificates
Enabling and Setting up SSL Support
NOTE: A restart of the unit is required after setting or changing any SSL configurations.
Enabling or disabling SSL support:
The Set SSL command is used to enable or disable SSL support.
To enable or disable SSL support:
At the Smart CDU: prompt, type set ssl , followed by enabled or disabled and press Enter .
Setting SSL access level:
The Set SSL Access command is used to assign use of SSL as optional or required. The default access level is set to optional.
To change the access level:
At the Smart CDU: prompt, type set ssl access , followed optional or required , and press Enter .
Example
The following changes the access level to required:
Smart CDU: set ssl access required<Enter>
Setting the SSL port:
The Set SSL Port command configures the SSL port number. The valid range of values for port number is 1-65535; the SSL default port number is 443.
To change the port number:
At the Smart CDU: prompt, type set ssl port , optionally followed by a port number, and press Enter . If you do not provide a port number on the Command Line, you will be prompted for a port number.
Example
The following changes the SSL port number to 443:
Smart CDU: set ssl port 443
96
•
Advanced Operations Smart POPS PDU
Installation and Operations Manual
Enabling or disabling custom user certificates:
The Set SSL User Certificate command enables or disables uploading of custom user certificates.
To enable or disable user certificates:
At the Smart CDU: prompt, type set ssl usercert , followed by enabled or disabled , and press Enter .
Setting the custom user certificate passphrase:
The Set SSL User Passphrase command sets the user-defined passphrase for authentication of uploaded custom user certificates.
To set the user certificate passphrase:
At the Smart CDU: prompt, type set ssl userpass and press Enter . You will be prompted to provide the passphrase. Press
Enter .
NOTE: A restart of the PDU is required after setting the user certificate passphrase.
SSL Technical Specifications
Secure Socket Layer (SSL)
Transport Layer Security (TLS) version 1 (RFC 2246)
SSL/TLS-enabled HTTPS server (RFC 2818)
Self-Signed X.509 Certificate version 3 (RFC 2459)
Asymmetric Cryptography:
1024-bit RSA Key Exchange
Symmetric Cryptography Ciphers:
TLS_RSA_WITH_AES_256_CBC_SHA
TLS_RSA_WITH_AES_128_CBC_SHA
TLS_RSA_WITH_3DES_EDE_CBC_SHA
TLS_RSA_WITH_DES_CBC_SHA
Smart POPS PDU
Installation and Operations Manual Advanced Operations
•
97
SSH
Secure Shell (SSH) version 2 enables secure network terminal sessions between a Remote Power Manager and a remote user over insecure network. SSH provides encrypted terminal sessions with strong authentication of both the server and client, using public-key cryptography and is typically used as a replacement for unencrypted Telnet. In addition to enabling secure network terminal sessions to the PDU for configuration and power management, the SSH session may be used for secure Pass-Thru connections to attached devices.
SSH requires the configuration and use of a client agent on the client PC. There are many freeware, shareware or forpurchase SSH clients available. Two examples are the freeware client PuTTY and the for-purchase client
SecureCRT
by VanDyke
Software. For configuration and use of these clients, please refer to the applicable software documentation.
SSH Command Summary
Command
Set SSH
Set SSH AuthMethod
Set SSH Port
Description
Enables/disables SSH support
Enables/disables the SSH server authentication methods
Sets the SSH server port number
Enabling and Setting up SSH Support
NOTE: A restart of the unit is required after setting or changing any SSH configurations.
Enabling or disabling SSH support:
The Set SSH command is used to enable or disable SSH support.
To enable or disable SSH support:
At the Smart CDU: prompt, type set ssh , followed by enabled or disabled and press Enter .
Changing the SSH server port:
With SSH support enabled, the SSH server watches and responds to requests on the default SSH port number 22.
This port number may be changed using the Set SSH Port command.
To change the SSH port:
At the Smart CDU: prompt, type set ssh port , followed by the port number and press Enter .
Example
The following changes the SSH port number to 65535:
Smart CDU: set ssh port 65535<Enter>
Enabling or disabling SSH server authentication methods:
The Set SSH Authentication Method command is used to set the method of SSH server authentication. The SSH server supports two authentication methods for security and validation: Password and Keyboard-Interactive.
To enable the SSH authentication methods:
At the Smart CDU: prompt, type set ssh authmethod , followed by password or kbint , followed by enabled or disabled , and press Enter .
Example
The following example sets the SSH authentication method to keyboard-interactive:
Smart CDU: set ssh authmethod kbint enabled<Enter>
98
•
Advanced Operations Smart POPS PDU
Installation and Operations Manual
SSH Technical Specifications
Secure Shell (SSH) version 2
Asymmetric Cryptography:
Diffie-Hellman DSA/DSS 512-1024 (random) bits per NIST specification
Symmetric Cryptography:
AES256-CBC
AES192-CBC
AES128-CBC
RIJNDAEL256-CBC
RIJNDAEL192-CBC
RIJNDAEL128-CBC
Message Integrity:
HMAC-SHA1-160
HMAC-MD5-128
Authentication:
Username/Password
Session Channel Break Extension (for RS232 Break)
3DES-192-CBC
Smart POPS PDU
Installation and Operations Manual Advanced Operations
•
99
SNMP/Thresholds
The Smart POPS family of products supports the Simple Network Management Protocol (SNMP). This allows network management systems to use SNMP requests to retrieve information and control power for the individual outlets.
NOTE: The default for SNMP support is Enabled . When Server Technology products are shipped, the default SNMP configuration for the GET community string is set to “ public
” and the SET community string is left blank.
About SNMP Versions
The firmware supports SNMP versions 1, 2, and 3.
SNMP version 3 supports authentication and encryption on a per user basis. Authentication types are None and MD5.
Encryption types are None and DES. If you use authentication, you must use encryption.
Two SNMPv3 users are supported: one user with read-write (RW) access, and one user with read-only (RO) access
Both users have the same configuration parameters, and you can configure each user independently.
SNMPv2 and SNMPv3 can be enabled or disabled independently. You can have SNMPv2 and/or SNMPv3, or none.
SNMP CLI Commands:
•
All SNMP v3 specific configuration settings use the CLI command SET SNMP V3.
•
All SNMP v1/v2 specific configuration settings use the CLI command SET SNMP V2.
•
All SNMP configuration settings common to any SNMP version use the CLI command SET SNMP.
NOTES:
•
If you use SNMP v1 or SNMP v2, all SET SNMP CLI commands (and the SHOW command) require the “V2” keyword.
•
SNMP v1/v2 CLI commands are documented immediately below in this section showing the required “V2” keyword. All CLI commands
that follow the SNMP v1/v2 section in this manual assume SNMP v3.
SNMP v1/v2 Command Summary
Command Description
Set SNMP IP Restrict Allows SNMP Get and Set request only from defined trap destinations
Set SNMP Trap Format
Set SNMP V2
Set SNMP V2 Getcomm
Set SNMP V2 Setcomm
Show SNMP
Configures the SNMP trap format version
Enables or disables SNMP v1/v2 support
Sets the ‘get’ community string
Set s the ‘set’ community string
Displays all SNMP configuration information
Enabling and Setting Up SNMP v1/v2 Support
The SNMP v1/v2 support must be enabled and configured for access to Sentry3 MIB objects and generation of all
Sentry3 traps.
Enabling/disabling SNMP support:
The SNMP Set command is used to enable or disable SNMP v1/v2 support.
To enable SNMP v1/v2 support:
At the Smart CDU: prompt, type set snmp v2 , followed by enabled or disabled and press Enter .
NOTE: A restart of the unit is required after enabling or disabling SNMP support.
100
•
Advanced Operations Smart POPS PDU
Installation and Operations Manual
Setting the Get/Set community strings:
NOTE : The default for SNMP support is Enabled . When Server Technology products are shipped, the default SNMP configuration for the
GET community string is set to “ public ” and the SET community string is left blank.
The Smart POPS CDU supports two SNMP community strings (SET and GET) that provide varying levels of access to objects defined in the Sentry3 MIB. Valid community strings are 1 to 24 characters.
Set Community String:
The Setcomm string provides read-write access to sentry3 MIB objects. The default Setcomm string is blank.
To set the Setcomm community string:
At the Smart CDU: prompt, type set snmp v2 setcomm , followed by the string, and press Enter .
Get Community String:
The Getcomm string provides read-only access to sentry3 MIB objects. The default Getcomm string is public.
To set the Getcomm community string:
At the Smart CDU: prompt, type set snmp v2 getcomm , followed by the string, and press Enter .
Displaying SNMP v1/v2 configuration information:
The Show SNMP V2 command displays all SNMP v1/v2configuration information, including:
•
SNMP support status
•
SNMP community strings
•
•
Trap timer value
Trap destinations (both IPv4 and IPv6 formats can be displayed.)
To display SNMP v1/v2 configuration information:
At the Smart CDU: prompt, type show snmp v2 and press Enter .
Example
The following command displays the SNMP configuration information:
Smart CDU: show snmp v2<Enter>
SNMP Configuration
SNMPv2 Agent: Enabled
GET Community <RO>: public
SET Community <RW>: <undefined>
TRAP Community: trap
SNMPv3 Agent: Disabled
Engine ID 800006B602000000000000000000000FFFF0A010249
RW Username: <undefined>
RW Auth Type: None <password not set>
RW Privacy Type: None <password not set>
RO Username: <undefined>
RO Auth Type: None <password not set>
RW Privacy Type: None <password not set>
Trap Username <undefined>
Trap Destination 1: <undefined>
Trap Destination 2: <undefined>
Trap format: v3
IP Restrictions: No Restrictions
Error Trap Repeat Time: 60 second<s>
SysName: Sentry3_524640
SysLocation: No Location
SysContact: No Contact
Command successful
Smart POPS PDU
Installation and Operations Manual Advanced Operations
•
101
SNMP v3 Command Summary
Command
Set SNMP IP Restrict
Description
Allows SNMP Get and Set requests from defined trap destinations only
Set SNMP Trap Format Configures the SNMP trap format version
Set SNMP V3 Enables or disables SNMP v3 support
Set SNMP V3 RO Username
Set SNMP V3 RO Auth Type
Sets the SNMP V3 read-only username.
Sets the SNMP V3 read-only authentication type
Set SNMP V3 RO Auth Password Sets the SNMP V3 read-only authentication password
Set SNMP V3 RO Priv Type Sets the SNMP V3 read-only privacy type
Set SNMP V3 RO Priv Password Sets the SNMP V3 ready-only privacy password
Set SNMP V3 RW Username Sets the SNMP V3 read-write username
Set SNMP V3 RW Auth Type Sets the SNMP V3 read-write authentication type
Set SNMP V3 RW Auth Password Sets the SNMP V3 read-write authentication password
Set SNMP V3 RW Priv Type Sets the SNMP V3 read-write privacy type
Set SNMP V3 RW Priv Password Sets the SNMP V3 ready-write privacy password
Set SNMP V3 Trap Username
Show SNMP
Sets the SNMP V3 trap username for display on SNMP activity logs
Displays all SNMP configuration information
MIB, OID and Support
The SNMP MIB and OID are available on the Server Technology website: ftp://ftp.servertech.com/pub/SNMP/sentry3
Technical support is available 8:00AM to 5:00 PM Pacific Time, Monday-Friday.
For SNMP Support, email: [email protected]
Enabling and Setting up SNMP Support
The SNMP support must be enabled and configured for access to Sentry3 MIB objects and generation of all Sentry3 traps.
Enabling/disabling SNMP support:
The SNMP command is used to enable or disable SNMP support.
To enable SNMP support:
At the Smart CDU: prompt, type set snmp v3 , followed by enabled or disabled and press Enter .
NOTE: A restart of the unit is required after enabling or disabling SNMP support.
SNMPv3 Engine ID:
The local engine ID is the unique identifier for the SNMPv3 engine and is displayed for viewing.
Setting the SNMP v3 read-only (RO) username :
The Set SNMP RO Username command sets the read-only username for SNMP v3. A valid username can be set to any value between 1-32 characters.
To set the RO username:
At the Smart CDU: prompt, type set snmp v3 rousername , and press Enter .
NOTE: You can set a blank username but doing so will clear the string and disallow any read-only user access.
Setting the SNMP v3 read-only (RO) authentication type :
The Set SNMP RO Auth Type command sets the SNMP v3 RO authentication type.
To set the RO authentication type:
At the Smart CDU: prompt, type set snmp v3 roauthtype , followed by none or md5 , and press Enter .
102
•
Advanced Operations Smart POPS PDU
Installation and Operations Manual
Setting the SNMP v3 read-only (RO) authentication password:
The Set SNMP RO Auth Password command sets the SNMP v3 RO authentication password. A valid authentication password can be set to any value between 1-40 characters. A blank password will clear the string.
To set the RO authentication password:
At the Smart CDU: prompt, type set snmp v3 roauthpass , and press Enter .
Setting the SNMP v3 read-only (RO) privacy type :
The Set SNMP RO Priv Type command sets the SNMP v3 RO privacy type.
To set the RO privacy type:
At the Smart CDU: prompt, type set snmp v3 roprivtype , followed by none or des , and press Enter .
Setting the SNMP v3 read-only (RO) privacy password:
The Set SNMP RO Priv Password command sets the SNMP v3 RO privacy password. A valid privacy password can be set to any value between 1-32 characters. A blank password will clear the string
To set the RO privacy password:
At the Smart CDU: prompt, type set snmp v3 roprivpass , and press Enter
Setting the SNMP v3 read-write (RW) username :
The Set SNMP RW Username command sets the read-write username for SNMP v3. A valid username can be set to any value between 1-32 characters.
To set the RW username:
At the Smart CDU: prompt, type set snmpv3 rwusername , and press Enter .
NOTE: You can set a blank username but doing so will clear the string and disallow any read-write user access.
Setting the SNMP v3 read-write (RW) authentication type :
The Set SNMP RW Auth Type command sets the SNMP v3 RW authentication type.
To set the RW authentication type:
At the Smart CDU: prompt, type set snmp v3 rwauthtype , followed by none or md5 , and press Enter .
Setting the SNMP v3 read-write (RW) authentication password:
The Set SNMP RW Auth Password command sets the SNMP v3 RW authentication password. A valid authentication password can be set to any value between 1-40 characters. A blank password will clear the string
To set the RW authentication password:
At the Smart CDU: prompt, type set snmp v3 rwauthpass , and press Enter .
Setting the SNMP v3 read-write (RW) privacy type :
The Set SNMP RW Priv Type command sets the SNMP v3 RW privacy type. A valid password can be set to any value between 1-40 characters.
To set the RW privacy type:
At the Smart CDU: prompt, type set snmp v3 rwprivtype , followed by none or des , and press Enter .
Setting the SNMP v3 read-write (RW) privacy password:
The Set SNMP RW Priv Password command sets the SNMP v3 RW privacy password. A valid privacy password can be set to any value between 1-32 characters. A blank password will clear the string
To set the RW privacy password:
At the Smart CDU: prompt, type set snmp v3 rwprivpass , and press Enter.
Smart POPS PDU
Installation and Operations Manual Advanced Operations
•
103
Setting the SNMP v3 trap username:
The Set SNMP Trap Username command sets an optional username for display on SNMP activity logs to identify user actions.
At the Smart CDU: prompt, type set snmp v3 trapusername , and press Enter . The trap username can be 1-31 alphanumeric characters; spaces are allowed; and the name is case sensitive.
Setting the error trap repeat timer:
The Set SNMP Traptime command sets the timer period between repeated error condition traps.
The valid range is 1 to 65535 (in seconds). The default is 60 seconds.
To set the error trap repeat timer:
At the Smart CDU: prompt, type set snmp traptime , followed by the timer period, and press Enter .
Example
The following sets the timer period to 180 seconds:
Smart PDU: set snmp traptime 180<Enter>
Setting the SNMP trap format version:
The SNMP Trap Format configures the SNMP trap format version. The trap format can be SNMP v1, v2, or v3.
To set the trap format version:
At the Smart CDU: prompt, type set snmp trapformat , followed by 1 , 2 , or 3 , and press Enter . The default is v1, regardless of the versions that are enabled for the agent.
Example
The following sets the trap format version to SNMP v3:
Smart CDU: set snmp trapformat 3<Enter>
Setting IP Restrictions:
The Set SNMP IP Restrictions command supports SNMP Manager Get and Set requests to only be allowed from the
IP address of the defined trap destinations.
To set SNMP IP restrictions:
At the Smart CDU: prompt, type set snmp iprestrict trapdests and press Enter .
To remove SNMP IP restrictions:
At the Smart CDU: prompt, type set snmp iprestrict none and press Enter
Setting trap destinations:
The Set SNMP Trapdest1 and Trapdest2 commands are used to set the IP addresses or hostname of SNMP management stations receiving all traps. The PDU supports a maximum of two trap destinations; one must be defined to enable trap generation.
To set the trap destination:
At the Smart CDU: prompt, type set snmp, trapdest1 or trapdest2 , the Ipaddress or hostname and press Enter .
Examples
The following sets the trap destination 1 to 64.42.31.208:
Smart CDU: set snmp trapdest1 64.42.31.208<Enter>
The following sets the trap destination 2 to snmp.servertech.com:
Smart CDU: set snmp trapdest2 snmp.servertech.com<Enter>
To reset the trap destination:
At the Smart CDU: prompt, type set snmp, trapdest1 or trapdest2, 0.0.0.0
and press Enter .
104
•
Advanced Operations Smart POPS PDU
Installation and Operations Manual
Setting the Get/Set community strings:
The PDU supports two SNMP community strings that provide varying levels of access to objects defined in the
Sentry3 MIB.
Community strings may be 1 to 24 characters.
Setcomm:
The Setcomm string provides read-write access to sentry3 MIB objects.
The default Setcomm string is “private”
To set the Setcomm community string:
At the Smart CDU: prompt, type set snmp setcomm , followed by the string and press Enter .
Getcomm:
The Getcomm string provides read-only access to sentry3 MIB objects.
The default Getcomm string is “public”.
To set the Getcomm community string:
At the Smart CDU: prompt, type set snmp getcomm , followed by the string and press Enter .
Setting the SNMP SysName:
The Set SNMP SysName command is used to set the SNMP MIB-II SysName object.
To set the SysName object:
At the Smart CDU: prompt, type set snmp sysname , followed by the object name and press Enter .
Setting the SNMP SysLocation:
The Set SNMP SysLocation command is used to set the SNMP MIB-II SysLocation object.
To set the SysLocation object:
At the Smart CDU: prompt, type set snmp syslocation , followed by the object location and press Enter .
Setting the SNMP SysContact:
The Set SNMP SysContact command is used to set the SNMP MIB-II SysContact object.
To set the SysContact object:
At the Smart CDU: prompt, type set snmp syscontact , followed by the object contact and press Enter .
Smart POPS PDU
Installation and Operations Manual Advanced Operations
•
105
Displaying SNMP configuration information:
The Show SNMP command displays all SNMP configuration information.
•
SNMP version (v2/v3) support status (enabled/disabled)
•
SNMP community strings
•
•
•
Read-Only (RO) or Read-Write (RW) username, authentication type, privacy type (if SNMPv3)
Trap username
•
Trap destination(s)
IP restrictions setting
•
Error trap repeat time (in seconds)
•
Sysname, syslocation, and syscontact
To display SNMP configuration information:
At the Smart CDU: prompt, type show snmp and press Enter .
Example
The following command displays the SNMP configuration information:
Smart CDU: show snmp<Enter>
SNMP Configuration
SNMPv2: Enabled
GET Community <RO>: ABC
SET Community <RW>: DEF
SNMPv3: Disabled
V3 RW Username: (undefined)
V3 RW Auth Type: None <password not set>
V3 RW Privacy Type: None <password not set>
V3 RO Username: (undefined)
V3 RO Auth Type: None <password not set>
V3 Trap Username djones
Trap Destination 1 : (undefined)
Trap Destination 2 : (undefined)
Trap format : v3
IP Restrictions: No Restrictions
Error Trap Repeat Time: 60 seconds
SysName: Sentry3_524640
SysLocation: No Location
SysContact: No Contact
Command successful
SNMP Traps
The Smart POPS PDU supports four types of SNMP traps. Traps are enabled at the Tower (T), Infeed (I),
Environmental Monitor (E) or sensor (S) level.
Trap Summary
Name
Status
Load
Temp
Humid
Level(s)
T, I, O, E, S
I
S
S
Description
Operational status change
Input load out of limit
Temperature is out of range
Relative Humidity is out of range
All traps include the Location of the PDU as defined with the Set Location command.
106
•
Advanced Operations Smart POPS PDU
Installation and Operations Manual
Status trap
A Status trap is generated when an error condition occurs on a tower, infeed, Environmental Monitor or individual sensor. Status traps include the reported Status, the location of the PDU and identifier and name of the affected tower, infeed, outlet, environmental monitor, or sensor.
Any error state generates a Status trap and triggers the trap timer. A new trap is generated at the end of every timer period until the Status returns to a non-error status. All status traps are enabled by default.
Tower Status traps
Status
Normal
Error Description
Tower is working correctly
NoComm x
Infeed Status traps
Communication to the tower has been lost
Status
On
OffError
NoComm
Error x x
Description
Infeed is on
Infeed should be on but no current is sensed at the infeed
Communication to the infeed has been lost
Environmental Monitor Status traps
Status
Normal
NoComm
Error x
Description
Environmental Monitor is working correctly
Communication to the Environmental Monitor has been lost
Temperature/Humidity Sensor Status Traps
Status
Found
NotFound
Lost
Error x
Description
The PDU found the sensor and connection is established.
On a fresh reboot, the PDU does not find a sensor.
The connection to a previously found sensor is now lost.
Communication loss occurred due to a hardware issue (not loss of communication with the probes).
1
NoComm x
1
= The ENV part of the sensor supports two Temperature/Humidity (T/H) probes as part of the master unit, two T/H probes as part of the link unit, and the optional EMCU-1-1 (which can support two T/H probes, four contact-closure monitoring points, and one water sensor). The “No Comm” sensor status is not loss of communication with probes themselves.
NOTE: Traps are generated according to a hierarchical architecture. For example, if a Tower Status enters a trap condition, only the Tower
Status trap will be generated. Infeed, Outlet, Environmental Monitor or Sensor Status and Temp and Humid traps will be suppressed until the Tower Status returns to Normal.
Load Trap
The Load trap is generated whenever the total input load on an infeed exceeds a preset threshold. Load traps include the reported input load, load status, location of the PDU, and identifier and name of the affected infeed.
Any error state generates a Load trap and triggers the trap timer. A new trap is generated at the end of every timer period until the Load returns to a non-error status.
Load traps
Status
Normal
NotOn
Reading
LoadHigh
OverLoad
ReadError
NoComm
Error x x x x
Description
Infeed is on and within preset thresholds
Infeed is off
Non-error state – Load status currently being read
Infeed current load exceeds preset threshold
Infeed current load exceeds the measurable range for the infeed
Unable to read Load status
Communication to the infeed has been lost
Smart POPS PDU
Installation and Operations Manual Advanced Operations
•
107
Temp Trap
The Temp trap is generated whenever the temperature on a temperature/humidity sensor is beyond preset thresholds.
Temp traps include the reported temperature, temp status, Location of the PDU, and identifier and name of the affected sensor.
Any error state generates a Temp trap and triggers the trap timer. A new trap is generated at the end of every timer period until the Temp returns to a non-error status.
Temp traps
Status
Normal
NotFound
Reading
TempLow
TempHigh
ReadError
Lost
NoComm
Error x x x x x
Description
The sensor is working correctly and the temperature is within preset thresholds
No sensor has been detected
Temp status currently being read
Temperature at the sensor below preset low threshold
Temperature at the sensor exceeds preset high threshold
Unable to read Temp status
Sensor initially detected but communication to the sensor has been lost
Communication to the sensor has been lost
Humidity Trap
The Humidity trap is generated whenever the humidity on a temperature/humidity sensor is beyond preset thresholds.
Humidity traps include the reported relative humidity, humidity status, location of the PDU, and identifier and name of the affected sensor.
Any error state generates a Humidity trap and triggers the trap timer. A new trap is generated at the end of every timer period until the Humidity returns to a non-error status.
Humidity traps
Status
Normal
NotFound
Reading
HumidLow x
HumidHigh x
ReadError
Lost
NoComm x x x
Error Description
The sensor is working correctly and the relative humidity is within preset thresholds
No sensor has been detected
Humidity status currently being read
Relative humidity at the sensor below preset low threshold
Relative humidity at the sensor exceeds preset high threshold
Unable to read Humidity status
Sensor initially detected but communication to the sensor has been lost
Communication to the sensor has been lost
108
•
Advanced Operations Smart POPS PDU
Installation and Operations Manual
Configuring Traps
SNMP Trap Command Summary
Command
Set Trap Tower Status
Set Trap Infeed Status
Set Trap Infeed Load
Set Trap Infeed HighThresh
Set Trap EM Status
Set Trap THS Status
Set Trap THS Temp
Set Trap THS Tempdelta
Set Trap THS Temphigh
Set Trap THS Templow
Set Trap THS Humid
Set Trap THS Humiddelta
Set Trap THS Humidhigh
Set Trap THS Humidlow
Show Traps
Description
Enables or disables the Tower Status trap
Enables or disables the Infeed Status trap off
Enables or disables the Infeed Load trap
Sets the Infeed Load trap high limit
Enables or disables the Environmental Monitor Status trap
Enables or disables a temperature/humidity sensor Status trap
Enables or disables a temperature/humidity sensor Temp trap
Sets temperature recovery delta
Sets a temperature/humidity sensor Temp trap high limit
Sets a temperature/humidity sensor Temp trap low limit
Enables or disables a temperature/humidity sensor Humid trap
Sets humidity recovery delta
Sets a temperature/humidity sensor Humid trap high limit
Sets a temperature/humidity sensor Humid trap low limit
Displays trap configurations
Enabling or Disabling a Status Trap:
The Set Trap … Status command is used to enable or disable Status traps for a Tower, Infeed, or Outlet.
To Enable or Disable a Status trap:
At the Smart CDU: prompt, type set trap ( tower , infeed, outlet, em, or ths ) status , followed by the tower, infeed, or outlet name, and on or off .
Press Enter , or\
Type set trap ( tower , infeed, outlet, em, or ths ) Status all , followed by on or off and press Enter .
Examples
The following command enables the Status trap for the first tower, using the tower’s absolute name:
Smart CDU: set trap tower status .a on<Enter>
The following command enables the Status trap for the tower named Florida_HQ_1:
Smart CDU: set trap tower status Florida_HQ_1 on<Enter>
NOTE: Enabling lower hierarchical traps automatically enables traps of higher hierarchical value: i.e. enabling an Outlet Status trap automatically enables the Infeed and Tower Status traps for that outlet. Conversely, if a Tower Status trap is disabled, all associated Infeed
Status & Load and Outlet Status traps will be disabled.
Enabling or Disabling a Load trap:
The Set Trap Infeed Load command is used to enable or disable an Infeed Load trap.
To Enable or Disable a Load trap:
At the Smart CDU: prompt, type set trap infeed load , followed by the infeed name, and on or off .
Press Enter , or
Type set trap infeed load all , followed by on or off and press Enter .
Examples
The following command enables the Load trap for second infeed on the first tower, using the absolute name of the infeed:
Smart CDU: set trap infeed load .AB on<Enter>
The following command disables the Load trap for all infeeds:
Smart CDU: set trap infeed load all off<Enter>
NOTE: Enabling lower hierarchical traps automatically enables traps of higher hierarchical value: i.e. enabling an Infeed Load trap automatically enables the Infeed and Tower Status traps for that infeed.
Smart POPS PDU
Installation and Operations Manual Advanced Operations
•
109
Setting the Infeed Load Limit:
The Set Trap Infeed Loadhigh command is used to set the upper load limits for an input feed.
To set the infeed load limit:
At the Smart CDU: prompt, type set trap infeed loadhigh , followed by the infeed name, and a value from 0 to 255 in amperes. Press Enter .
Example
The following command sets the infeed load limit for the second infeed on the first tower to 25 amperes, using the absolute name of the infeed:
Smart CDU: set trap infeed loadhigh .ab 25<Enter>
Enabling or Disabling the Temp Trap:
The Set Trap THS Temp command is used to enable or disable the Temp trap.
To Enable or Disable the Temp trap:
At the Smart CDU: prompt, type set trap ths temp , followed by the sensor name and on or off . Press Enter .
Example
The following command enables the Temp trap for the first temperature-humidity sensor:
Smart CDU: set trap ths temp .a1 on<Enter>
Setting the Temperature Sensor Threshold Limits:
The Set Trap THS Templow and Set Trap THS Temphigh commands are used to set the lower and upper threshold limits for the Temperature sensor.
To set the Temperature threshold limits:
At the Smart CDU: prompt, type set trap ths , templow or temphigh , followed by the sensor name and a value from
0 to 123 degrees Celsius. Press Enter .
Example
The following command sets the second temperature high threshold limit to 95:
Smart CDU: set trap ths temphigh .a2 95<Enter>
Configuring Temperature Recovery Delta:
The Temperature Recovery Delta command allows configuration of the number of degrees of change needed to recover from a temperature alarm.
To configure the temperature recovery delta:
At the Smart CDU: prompt, type set event temp tempdelta , followed by the sensor name, the number of degrees for the recovery delta, and press Enter .
NOTE: The acceptable value range for the Recovery Delta field is 0-10 degrees for Celsius and 0-18 degrees for Fahrenheit. The default value for the Recovery Delta field is 1 degree Celsius and 2 degrees Fahrenheit.
Example
The following command configures the recovery delta at 2 degrees Fahrenheit for temperature/humidity sensor .A1:
Smart CDU: event temp tempdelta temp_humid_sensor_A1 2<Enter>
110
•
Advanced Operations Smart POPS PDU
Installation and Operations Manual
Configuring Temperature Recovery Delta:
The Temperature Recovery Delta command allows configuration of the number of degrees of change needed to recover from a temperature alarm.
To configure the temperature recovery delta:
At the Smart CDU: prompt, type set trap ths tempdelta , followed by the sensor name, the number of degrees for the recovery delta, and press Enter .
Example
The following command configures the recovery delta at 2 degrees Fahrenheit for temperature/humidity sensor .A1:
Smart CDU: set trap ths tempdelta temp_humid_sensor_A1 2<Enter>
Configuring Humidity Recovery Delta (Hysteresis):
The Humidity Recovery Delta command allows configuration of the percentage of change needed to recover from a humidity alarm.
NOTE: After exceeding a low or high humidity threshold (thus entering an error condition), the humidity value must return past the threshold by the configured recovery delta amount to clear the error condition. Default of humidity recovery delta is 2% relative humidity.
To configure the humidity recovery delta:
At the Smart CDU: prompt, type set trap ths humiddelta , followed by the sensor name, the percentage for the recovery delta, and press Enter .
Example
The following command configures the recovery delta at 2 relative humidity for temperature/humidity sensor .A1:
Smart CDU: set trap ths humiddelta temp_humid_sensor_A1 2<Enter>
Enabling or Disabling the Humid trap:
The Set Trap THS Humid command is used to enable or disable the Humid trap.
To Enable or Disable the Humid trap:
At the Smart CDU: prompt, type set trap ths humid , followed by the sensor name and on or off . Press Enter .
Example
The following command enables the Humid trap for the first temperature-humidity sensor:
Smart CDU: set traps ths humid .a1 on<Enter>
Setting the Humidity Sensor Threshold Limits:
The Set Trap THS Humidlow and Set Trap THS Humidhigh commands are used to set the lower and upper threshold limits for the Humidity sensor.
To set the Humidity threshold limits:
At the Smart CDU: prompt, type set trap ths , humidlow or humidhigh , followed by the sensor name and a value from 0 to 100 in percent relative humidity. Press Enter .
Example
The following command sets the first humidity sensor low threshold limit to 5:
Smart CDU: set trap ths humidlow .a1 5<Enter>
Smart POPS PDU
Installation and Operations Manual Advanced Operations
•
111
Displaying Trap Configuration Information:
The Show Traps command displays information about all traps.
To display trap information:
At the Smart CDU: prompt, type show traps and press Enter .
Example
The following command requests trap configuration information:
Smart CDU: show traps <Enter>
Tower trap configuration:
Tower Tower Status
ID Name Trap
.A Florida_HQ_1 ON
.B Florida_HQ_2 ON
More (Y/es N/o): y
Input feed trap configuration:
Input Input Status Load High
Feed ID Feed Name Trap Trap Thresh
.AA HQ_1_Infeed_A ON ON 255 A
.BA HQ_2_Infeed_A ON ON 255 A
More (Y/es N/o): y
Environmental Monitor .A trap configuration:
Name: Florida_HQ_1
Status Trap: ON
Temperature/Humidity Sensor .A1 Temperature/Humidity Sensor .A2
Name: Temp_Humid_Sensor_A1 Name: T/H2_Florida_HQ_1
Status Trap: ON Status Trap: ON
Temp Trap: ON Temp Trap: ON
Low: 0 Deg.C Low: 0 Deg.C
High: 123 Deg.C High: 95 Deg.C
Humid Trap: ON Humid Trap: ON
Low: 5 % RH Low: 0 % RH
High: 100 % RH High: 100 % RH
Delta: 2 % RH Delta: 2 % RH
112
•
Advanced Operations Smart POPS PDU
Installation and Operations Manual
LDAP
The Smart POPS family of products supports Lightweight Directory Access Protocol (LDAP) Version 3. This support enables authentication with LDAP servers; user accounts do not need to be individually created locally on each PDU.
This allows administrators to pre-define and configure (in each PDU product, and in the LDAP server) a set of necessary LDAP Groups, and access rights for each. User’s access rights can then be assigned or revoked simply by making the user a member of one-or-more pre-defined PDU LDAP Groups. User accounts can be added, deleted, or changed in the LDAP server without any changes needed on individual PDU products.
Smart POPS LDAP support has been tested in the following environments:
•
•
Microsoft Active Directory (MSAD)
Novell eDirectory (eDir)
•
OpenLDAP
LDAP Command Summary
Command
Set Authorder
Set LDAP
Set LDAP Host
Set LDAP Port
Set LDAP Bind
Set LDAP BindDN
Description
Specifies the authentication order for each new session attempt
Enables/disables LDAP support
Sets the IP address or hostname of the Directory Services server
Sets the LDAP server port number
Specifies the LDAP bind request
Specifies the user account Fully-Qualified Domain Name (FQDN) for binds
Set LDAP BindPW
Set LDAP GroupAttr
Set LDAP GroupType
Set LDAP UseTLS/SSL
Set LDAP UserBaseDN
Set LDAP UserFilter
Show LDAP
Set DNS
Ping
Show Network
Create LDAPGroup
Remove LDAPGroup
Add PorttoLDAP
Delete PortfromLDAP
Set LDAPGroupAccess
Set LDAPGroupEnvmon
List LDAPGroup
List LDAPGroups
Specifies the user account password for binds
Specifies the user class distinguished name (DN) or names of groups a user is a member of
Specifies the data type for the Set LDAP GroupAttr command
Enables/disables LDAP over TLS/SSL support
Sets the base distinguished name (DN) for the username search at login
Sets the filter used for the username search at login
Displays LDAP configurations
Sets the IP address of the Domain Name System (DNS) server
Verifies proper DNS configuration by name resolution
Displays network configuration information for all IPv4 and IPv6 settings
Adds an LDAP group name
Deletes an LDAP group name
Grants an LDAP group access to one or more serial ports
Removes access to one or more serial ports for an LDAP group
Sets the access level for an LDAP group
Grants or removes access to environmental monitoring
Displays all accessible ports for an LDAP group
Displays privilege levels for all LDAP groups
Smart POPS PDU
Installation and Operations Manual Advanced Operations
•
113
Enabling and Setting Up LDAP Support
There are a few configuration requirements for properly enabling and setting up LDAP support. Below is an overview of the minimum requirements.
Directory Services server configuration requirements:
1.
Define at least one LDAP group.
2.
Assign users to that LDAP group.
PDU configuration requirements:
1.
Enable LDAP support.
2.
Define the IP address and domain component of at least one Directory Services server.
3.
Set the LDAP bind request method being utilized by the Directory Services server.
4.
Define the IP address of at least one DNS server.
5.
Test DNS server configuration using Ping command support.
6.
Define at least one LDAP group and assign access rights for that group.
NOTE: LDAP group names on the Directory Service server and the Smart POPS PDU must match.
Enabling and Disabling LDAP Support:
The Set LDAP command is used to enable or disable LDAP support.
To enable or disable LDAP support:
At the Smart CDU: prompt, type set ldap , followed by enabled or disabled and press Enter .
Setting the LDAP host address:
The Set LDAP Host command sets the TCP/IP address of the Directory Services server.
NOTE: Both IPv4 and IPv6 formats are accepted for hostname.
To set the LDAP host address:
At the Smart CDU: prompt, type set ldap , followed by host1 or host2 and the Directory Services server’s IP address or hostname. Press Enter .
Examples
The following command sets the primary Directory Services server IP address to 98.76.54.32:
Smart CDU: set ldap host1 98.76.54.32<Enter>
The following command sets the secondary Directory Services server hostname to ldap.servertech.com:
Smart CDU: set ldap host2 ldap.servertech.com<Enter>
Changing the LDAP Server Port:
The Set LDAP port command sets the port to which the PDU sends LDAP requests to on the previously defined
LDAP server. The default port is 389.
To change the LDAP server port:
At the Smart CDU: prompt, type set ldap port , followed by the port number and press Enter .
Example
The following command sets the LDAP server port number to 8888:
Smart CDU: set ldap port 8888<Enter>
Enabling and Disabling LDAP Over TLS/SSL Support:
The Set LDAP UseTLS command is used to enable or disable LDAP over TLS/SSL support.
To enable or disable LDAP over TLS/SSL support:
At the Smart CDU: prompt, type set ldap usetls , followed by yes or no and press Enter .
NOTE: If LDAP over TLS/SSL is enabled, MD5 binding is disabled.
114
•
Advanced Operations Smart POPS PDU
Installation and Operations Manual
Setting the LDAP bind type:
The Set LDAP Bind command specifies the LDAP bind request that authenticates a client with the LDAP server.
The PDU supports three standard LDAP bind methods:
Simple: Uses unencrypted delivery of username-password over the network to the LDAP server for authentication, showing user credentials in plain text.
LDAP over TLS/SSL: Uses a trusted authority certificate to provide encryption of LDAP authentication.
MD5: Provides strong protection using 1-way hash encoding that does not transmit the username-password over the network.
To set the bind type:
At the Smart CDU: prompt, type set ldap bind , followed by simple , TLS , or md5 , and press Enter .
NOTE: If MD5 binding is enabled, LDAP over TLS/SSL is disabled.
To set the bind password type:
At the Smart CDU: prompt, type set ldap bind , followed by simple , TLS , or md5 and press Enter .
NOTE: If MD5 binding is enabled, LDAP over TLS/SSL is disabled.
Setting the Search Bind Distinguished Name (DN):
The Set LDAP BindDN command is used to set the fully-qualified domain name (FQDN) for user accounts to bind with. This is required for directory services that do not support anonymous binds. This field is used ONLY with
Simple Binds. Maximum string length is 124 characters.
NOTE: If left blank, then an anonymous bind will be attempted. Use this field only with Simple binds.
To set the search bind DN:
At the Smart CDU: prompt, type set ldap binddn , and press Enter . At the following prompt, type the FQDN and press Enter .
Example
The following sets the FQDN for MSAD to ‘cn=guest,cn=Users,dc=servertech,dc=com’:
Smart CDU: set ldap binddn<Enter>
Enter Search Bind DN (Max characters 124): cn=guest,cn=Users,dc=servertech,dc=com<Enter>
Setting the Search Bind Distinguished Name (DN) Password:
The Set LDAP BindPW command is used to set the password for the user account specified in the Search Bind DN.
Maximum password size is 20 characters.
To set the Bind Password DN:
At the Smart CDU: prompt, type set ldap bindpw and press Enter .
At the following prompt, type the bind password and press Enter .
Setting the Group Membership Attribute:
The Set LDAP GroupAttr command is used to specify the name of user class attributes that lists distinguished names
(DN), or names of groups that a user is a member of. Maximum string length is 30 characters.
To set Group Membership Attribute:
At the Smart CDU: prompt, type set ldap groupattr and press Enter .
At the following prompt, type the group membership attribute and press Enter .
Example
The following sets the group membership attribute for MSAD to ‘memberof’:
Smart CDU: set ldap groupattr<Enter>
Enter Group Member Attr (Max character 30): memberof<Enter>
Smart POPS PDU
Installation and Operations Manual Advanced Operations
•
115
Setting the Group Membership Value Type:
The Set LDAP GroupType command is used to specify whether the values of Group Membership Attribute represent the Distinguished Name (DN) of a group or just the name of the group.
To set group membership value type:
At the Smart CDU: prompt, type set ldap grouptype followed by DN or Name and press Enter .
Example
The following sets group membership value to DN
Smart CDU: set ldap grouptype DN<Enter>
Setting the user membership attribute:
The User Membership Attribute is a comma-delimited string of up to two attribute names whose values in the search results are the users that are members of the LDAP group. Maximum number of characters is 61.
NOTE: The user membership attribute option allows the searching of group directory names by a user membership attribute to find the groups for which the user is a member.
To set user membership attribute:
At the Smart CDU: prompt, type set ldap groupsearch userattr and press Enter .
Then at the following prompt, type the group membership attribute and press Enter .
Example
The following sets the user membership attribute to Test
Smart CDU: set ldap groupsearch userattr<Enter>
Enter Group Member Attribute <61 character max>:
Test<Enter>
Setting the User Search Base Distinguished Name (DN):
The Set LDAP UserBaseDN command is used to set the base (DN) for the login username search. This is where the search will start, and will include all sub-trees. Maximum size is 100 characters.
To set the user search base DN:
At the Smart CDU: prompt, type set ldap userbasedn and press Enter . At the following prompt, type the search base DN and press E nter.
Example
The following sets the DN user search base for MSAD to ‘cn=Users,dc=servertech,dc=com’:
Smart CDU: set ldap userbasedn<Enter>
Enter User Search Base DN (Max characters 100): cn=Users,dc=servertech,dc=com<Enter>
116
•
Advanced Operations Smart POPS PDU
Installation and Operations Manual
Setting the User Search Filter:
The Set LDAP UserFilter command is used to set the search filter for the username entered at the login prompt.
The search filter must be entered within parenthesis and adhere to the following format:
( searchfilter =%s) where ‘searchfilter’ is the name of the attribute in the user class which has a value that represents the user’s login name. In this string, the ‘%s’ will be replaced by the entered username. Maximum string length is 100 characters.
To set the user search filter:
At the Smart CDU: prompt, type set ldap userfilter and press Enter .
At the following prompt, type the User Search
Filter and press Enter .
Example
The following sets the user search filter for MSAD to ‘samaccountname’:
Smart CDU: set ldap userfilter<Enter>
Enter User Search Filter (Max characters 100):
(samaccountname=%s)<Enter>
Setting the Authentication Order:
The Set Authorder command sets the authentication order for remote authentication sessions. The PDU supports two methods for authentication order: Remote > Local and Remote Only.
The Remote > Local method first attempts authentication with the Active Directory server and if unsuccessful with the local user database on the PDU.
The Remote Only method attempts authentication only with the Active Directory server and if unsuccessful, access is denied.
NOTE: With the Remote Only method, if authentication fails due to a communication failure with the Active Directory server automatic authentication fallback will occur to authenticate with the local user data base on the PDU.
To set the authentication order:
At the Smart CDU: prompt, type set authorder , followed by remotelocal or remoteonly and press Enter .
NOTE: Server Technology recommends NOT setting the authentication order to Remote Only until the LDAP has been fully configured and tested.
Smart POPS PDU
Installation and Operations Manual Advanced Operations
•
117
Displaying LDAP Configuration Information:
The Show LDAP command displays LDAP configuration information.
•
Enabled-disabled status of LDAP support
•
Directory Services server IP address and port
•
•
•
User search base distinguished name and filter
•
Bind request password type and remote authentication order
Search bind distinguished name and password
Group membership attribute and type
To display the LDAP configuration information:
At the Smart CDU: prompt, type show ldap and press Enter .
Example
The following command displays the LDAP configuration information:
Smart CDU: show ldap
LDAP Configuration
LDAP: Enabled
Host 1: 98.76.54.32
Host 2: ldap.servertech.com
Port: 8888
TLS/SSL: Yes
Bind Type: MD5
Auth Order: Remote->Local
Search Bind
DN: cd=guest,cn=Users,dc=servertech,dc=com
Password: OpenDoor
User Search
Base DN: cn=Users,dc=servertech,dc=com
Filter: (samaccountname=%s)
Group Membership
Attribute: memberof
Value Type: DN
Setting the DNS IP address:
The Set DNS command sets the TCP/IP address of the Domain Name System (DNS) server.
NOTE: LDAP requires the definition of at least one Domain Name System (DNS) server.
To display the DNS configuration information, use the Show Network command as described on page 81.
To set the DNS IP address:
At the Smart CDU: prompt, type set , followed by dns1 or dns2 and the Domain Name System (DNS) server’s IP address. Press Enter .
NOTE: Both IPv4 and IPv6 formats are accepted for IP address.
Example
The following command sets the primary Domain Name System (DNS) server IP address to 98.76.54.254:
Smart CDU: set dns1 98.76.54.254<Enter>
118
•
Advanced Operations Smart POPS PDU
Installation and Operations Manual
Verifying the DNS configuration:
The Ping command may be used to verify the configuration of the DNS IP address.
To verify the DNS configuration:
At the Smart CDU: prompt, type ping , followed by the domain component of the Directory Services server previously configured and press Enter .
Example
The following command verifies the DNS configuration:
Smart CDU: ping servertech.com
Pinging servertech.com [98.76.54.32] with 64 bytes of data:
Reply from 98.76.54.32: bytes=64 pseq=0 triptime=0
Reply from 98.76.54.32: bytes=64 pseq=1 triptime=0
Reply from 98.76.54.32: bytes=64 pseq=2 triptime=0
Reply from 98.76.54.32: bytes=64 pseq=3 triptime=0
Reply from 98.76.54.32: bytes=64 pseq=4 triptime=0
Configuring LDAP Groups
Creating an LDAP group:
The Create LDAPGroup command creates an LDAP group.
To create an LDAP group:
At the Smart CDU: prompt, type create ldapgroup , optionally followed by a 1-16 character group name (Spaces are not allowed, and LDAP group names are not case sensitive). Press Enter .
Example
The following command creates the LDAP group PowerUser:
Smart CDU: create ldapgroup PowerUser<Enter>
Removing an LDAP group:
The Remove LDAPGroup command removes an LDAP group.
To remove an LDAP group:
At the Smart CDU: prompt, type remove ldapgroup , optionally followed by a group name. Press Enter .
Smart POPS PDU
Installation and Operations Manual Advanced Operations
•
119
Setting LDAP group access level privileges:
The Set LDAPGroup Access command sets the access level privileges for an LDAP group. The PDU has four defined access privilege levels: Admin, User, On-Only, and View-Only.
To set the access level privilege for an LDAP group :
At the Smart CDU: prompt, type set ldapgroup access , followed by admin , user , ononly or viewonly, optionally followed by a LDAP group name and press Enter .
Examples
The following command sets the LDAP group access level for LDAPAdmin to Admin:
Smart CDU: set ldapgroup access admin ldapadmin<Enter>
The following command sets the LDAP group access level for PowerUser to User:
Smart CDU: set ldapgroup access user poweruser<Enter>
Granting and removing input status viewing privileges :
The Set LDAPGroup Envmon command grants or removes input status viewing privileges to/from an LDAP group.
To grant or remove input status viewing privileges for an LDAP group:
At the Smart CDU: prompt, type set ldapgroup envmon followed by on or off , optionally followed by a group name and press Enter .
Example
The following command grants input status viewing privileges to the LDAP group PowerUser:
Smart CDU: set ldapgroup envmon on poweruser<Enter>
Granting and removing access to environmental monitoring :
The Set LDAPGroup Envmon command grants or removes input status viewing privileges to/from an LDAP group.
To grant or remove input status viewing privileges for an LDAP group:
At the Smart CDU: prompt, type set ldapgroup envmon followed by on or off , optionally followed by a group name and press Enter .
Example
The following command grants input status viewing privileges to the LDAP group PowerUser:
Smart CDU: set ldapgroup envmon on poweruser<Enter>
NOTE: Granting access to environmental monitoring (temperature/humidity/sensors) to a non-admin user also grants that user access to power monitoring (outlets, infeeds, towers – all the environmental data of the PDU).
Displaying the LDAP access privilege levels:
The List LDAPGroups command displays all defined LDAP group with their access privilege level.
To display LDAP group access privilege levels:
At the Smart CDU: prompt, type list ldapgroups and press Enter .
Example
The following command displays all LDAP groups with their access privilege level:
Smart CDU: list ldapgroups<Enter>
LDAP Access Environmental
Group Name Level Monitoring
LDAPAdmin Admin Allowed
PowerUser User Allowed
User On-Only Not Allowed
Guest View-Only Not Allowed
120
•
Advanced Operations Smart POPS PDU
Installation and Operations Manual
Adding serial port access to an LDAP group:
The Add PortToLDAP command grants an LDAP group access to the serial port.
To grant serial port access to an LDAP group:
At the Smart CDU: prompt, type add porttoldap console and a group name. Press Enter .
Deleting serial port access for an LDAP group:
The Delete PortFromLDAP command removes an LDAP group’s access to the serial port. You cannot remove access to the serial port for an administrative level group.
To delete serial port access for a user:
At the Smart CDU: prompt, type delete portfromldap console and a group name. Press Enter .
Displaying LDAP Group access:
The List LDAPGroup command displays all access rights for an LDAP group.
To display LDAP Group access:
At the Smart CDU: prompt, type list ldapgroup , optionally followed by a group name. Press Enter .
Example
The following command displays information about the LDAP group PowerUser:
Smart CDU: list ldapgroup poweruser<Enter>
Username: PowerUser
Ports:
Port Port
ID Name
Console Console
Smart POPS PDU
Installation and Operations Manual Advanced Operations
•
121
LDAP Technical Specifications
Simple Bind Authentication Process
Client LDAP Server Sentry
MD5 Bind Authentication Process
Client LDAP Server
Initiate Sentry session
Authentication request with
Usename/
Password
Successful
Bind?
Username found?
Prompt for login credentials
Simple bind using
Search Bind
DN & Password
Subtree search starting from
User Search Base
DN with User
Search Filter
Simple Bind using
User FQDN and login password
Initiate Sentry session
Authentication request with
Usename/
Password
Access Denied
Successful
Bind?
Username found?
Successful
Bind?
Subtree search starting from
User Search Base
DN with User
Search Filter
Attribute match?
Access Denied
Username found?
Attribute match?
Group
match?
Attribute name compared to
Group
Membership
Attribute
Username groups access rights compared against
Sentry LDAP groups
Access Granted
Group
match?
Access Granted
LDAPS (LDAP-over-TLS/SSL) Client Specifications
Secure Sockets Layer (SSL)
Transport Layer Security (TLS) version 1 (RFC 2246) x.509 version 3 Server Certificates (RFC 2459) with RSA key sizes up to 4096 bits
Symmetric Cryptography Ciphers:
TLS_RSA_WITH_3DES_EDE_CBC_SHA (168-bit)
TLS_RSA_WITH_DEX_CBC_SHA (56-bit)
TLS_RSA_WITH_AES_128_CBC_SHA (128-bit)
TLS_RSA_WITH_AES_256_CBC_SHA (256-bit)
Server certificates are accepted and used on –the-fly
A NULL client certificate is sent to the server if a client certificate is requested.
Sentry
Prompt for login credentials
SASL Digest-MD5 bind using uppercase username & entered password
Subtree search starting from
User Search Base
DN with User
Search Filter
Attribute name compared to
Group
Membership
Attribute
Username groups access rights compared against
Sentry LDAP groups
122
•
Advanced Operations Smart POPS PDU
Installation and Operations Manual
TACACS+
The Smart POPS family of products supports the Terminal Access Controller Access Control System (TACACS+) protocol. This enables authentication and authorization with a central TACACS+ server; user accounts do not need to be individually created locally on each PDU.
This allows administrators to pre-define and configure (in each PDU product, and in the TACACS+ server) a set of necessary TACACS+ privilege levels, and users’ access rights for each. User’s access rights can then be assigned or revoked simply by making the user a member of one-or-more pre-defined TACACS+ privilege levels. User account rights can be added, deleted, or changed within TACACS+ without any changes needed on individual PDU products.
The Smart POPS PDU supports 16 different TACACS+ privilege levels; 15 are entirely configurable by the system administrator (1 is reserved for default Admin level access to all PDU resources).
TACACS+ Command Summary
Command
Set Authorder
Set TACACS
Set TACACS Host
Set TACACS Key
Set TACACS Port
Show TACACS
Add PorttoTACACS
Delete PortfromTACACS
Set TacPriv Access
Set TacPriv Envmon
List TacPrivs
List TacPriv
Description
Specifies the authentication order for each new session attempt
Enables/disables TACACS support
Sets the IP address or hostname of the TACACS server
Sets the TACACS encryption key
Sets the TACACS server port number
Displays TACACS configurations
Grants a TACACS account access to one or more serial ports
Removes access to one or more serial ports for a TACACS account
Sets the access level for a TACACS account
Grants or removes user access to environmental monitoring
Displays user access levels for all TACACS accounts
Displays all accessible ports for a TACACS account
Enabling and Setting up TACACS+ Support
There are a few configuration requirements for properly enabling and setting up TACACS+ support. Below is an overview of the minimum requirements:
1.
Enable TACACS+ support.
2.
Define the IP address and domain component of at least one TACACS+server.
3.
Set the TACACS+ key configured on the supporting TACACS+server.
Enabling and disabling TACACS+ support:
The Set TACACS command is used to enable or disable TACACS+ support.
To enable or disable TACACS+ support:
At the Smart CDU: prompt, type set tacacs , followed by enabled or disabled and press Enter .
Setting the TACACS+ server address:
The Set TACACS Host command sets the IP address or hostname of the TACACS+ server.
NOTE: Both IPv4 and IPv6 formats are accepted for IP address or hostname.
To set the TACACS+ server address:
At the Smart CDU: prompt, type set tacacs , followed by host1 or host2 and the TACACS+ server’s IP address or hostname. Press Enter .
Examples
The following command sets the primary TACACS+ server address to 98.76.54.32:
Smart CDU: set tacacs host1 98.76.54.32<Enter>
The following command sets the secondary TACACS+ server hostname to tacacs.servertech.com:
Smart CDU: set tacacs host2 tacacs.servertech.com<Enter>
Smart POPS PDU
Installation and Operations Manual Advanced Operations
•
123
Setting the TACACS+ encryption key:
The Set TACACS Key command sets the encryption key used to encrypt all data packets between the PDU and the
TACACS+ server. This key must match the key configured on the TACACS+ server.
To set the encryption key:
At the Smart CDU: prompt, type set tacacs key and press Enter .
At the TACACS+ Key: prompt, type an encryption key of up to 60 alphanumeric and other typed characters - (ASCII
33 to 126 decimal) are allowed; encryption keys are case sensitive. Press Enter . To specify no password, press Enter .
At the Verify TACACS+ Key: prompt, retype the key. Press Enter . To verify no password, press Enter at the prompt.
Example
Smart CDU: set tacacs key<Enter>
TACACS+ Key: <Enter>
Verify TACACS+ Key: <Enter>
For security, key characters are not displayed.
NOTE: A key size of zero results in no encryption being applied which may not be supported by the TACACS+ server and is not recommended for a production environment.
Changing the TACACS port:
With TACACS support enabled, the PDU sends TACACS requests to the default TACACS port number 49. This port number may be changed using the Set TACACS Port command.
To change the TACACS port:
At the Smart CDU: prompt, type set tacacs port , followed by the port number and press Enter .
Example
The following changes the TACACS port number to 50:
Smart CDU: set tacacs port 50<Enter>
Setting the authentication order:
The Set Authorder command sets the authentication order for remote authentication sessions. The PDU supports two methods for authentication order: Remote > Local and Remote Only.
The Remote > Local method first attempts authentication with the TACACS+ server and if unsuccessful with the local user database on the PDU.
The Remote Only method attempts authentication only with the TACACS+ server and if unsuccessful, access is denied.
NOTE: With the Remote Only method, if authentication fails due to a communication failure with the TACACS+ server automatic authentication fallback will occur to authenticate with the local user database on the PDU.
To set the authentication order:
At the Smart CDU: prompt, type set authorder , followed by remotelocal or remoteonly and press Enter .
NOTE: Server Technology recommends not setting authentication order to Remote Only until TACACS+ has been configured and tested.
124
•
Advanced Operations Smart POPS PDU
Installation and Operations Manual
Displaying TACACS+ configuration information:
The Show TACACS command displays TACACS+ configuration information.
To display the TACACS configuration information:
At the Smart CDU: prompt, type show tacacs and press Enter .
Example
The following command displays the TACACS configuration information:
Smart CDU: show tacacs<Enter>
TACACS+ Configuration
TACACS+: Enabled
Host 1: 98.76.54.32
Host 2: tacacs.servertech.com
Port: 50
TACACS+ Key: (Set)
Auth Order: Remote->Local
Configuring TACACS+ Privilege Levels
Setting TACACS+ account access level privileges:
The Set TacPriv Access command sets the access level privileges for a TACACS+ account. The PDU has four defined access privilege levels: Admin, User, On-Only, and View-Only.
To set the access level privilege for a TACACS+ account :
At the Smart CDU: prompt, type set tacpriv access , followed by admin , user , ononly or viewonly, optionally followed by a TACACS+ account number and press Enter .
Examples
The following command sets the TACACS+ account access level for account 14 to Admin:
Smart CDU: set tacpriv access admin 14<Enter>
The following command sets the TACACS+ account access level for account 5 to User:
Smart CDU: set tacpriv access user 5<Enter>
Granting and removing input status viewing privileges:
The Set TacPriv Envmon command grants or removes input status viewing privileges to/from a TACACS+ account.
To grant or remove input status viewing privileges for a TACACS+ account:
At the Smart CDU: prompt, type set tacpriv envmon , followed by on or off , optionally followed by a TACACS+ account number and press Enter .
Example
The following command grants input status viewing privileges to the TACACS+ account 5:
Smart CDU: set tacpriv envmon on 5<Enter>
Granting and removing access to environmental monitoring:
The Set TacPriv Envmon command grants or removes input status viewing privileges to/from a TACACS+ account.
To grant or remove input status viewing privileges for a TACACS+ account:
At the Smart CDU: prompt, type set tacpriv envmon , followed by on or off , optionally followed by a TACACS+ account number and press Enter .
Example
The following command grants input status viewing privileges to the TACACS+ account 5:
Smart CDU: set tacpriv envmon on 5<Enter>
NOTE: Granting access to environmental monitoring (temperature/humidity/sensors) to a non-admin user also grants that user access to power monitoring (outlets, infeeds, towers – all the environmental data of the PDU).
Smart POPS PDU
Installation and Operations Manual Advanced Operations
•
125
Displaying the TACACS+ access privilege levels:
The List TacPrivs command displays all TACACS+ accounts with their access privilege levels.
To display TACACS+ account access privilege levels:
At the Smart CDU: prompt, type list tacprivs and press Enter .
Example
The following command displays all TACACS+ account with their access privilege level:
Smart CDU: list tacprivs<Enter>
TACACS Access Environmental
Account Name Level Monitoring
TACAdmin Admin Allowed
PowerUser User Allowed
User On-Only Not Allowed
Guest View-Only Not Allowed
Granting and removing access to environmental monitoring:
The Set TacPriv Envmon command grants or removes input status viewing privileges to/from a TACACS+ account.
To grant or remove input status viewing privileges for a TACACS+ account:
At the Smart CDU: prompt, type set tacpriv envmon , followed by on or off , optionally followed by a TACACS+ account number and press Enter .
Example
The following command grants input status viewing privileges to the TACACS+ account 5:
Smart CDU: set tacpriv envmon on 5<Enter>
NOTE: Granting access to environmental monitoring (temperature/humidity/sensors) to a non-admin user also grants that user access to power monitoring (outlets, infeeds, towers – all the environmental data of the PDU).
Adding serial port access to a TACACS+ account:
The Add PortToTACACS command grants a TACACS+ account access to the serial port.
To grant serial port access to a TACACS+ account:
At the Smart CDU: prompt, type add porttotacacs console and a TACACS+ account number. Press Enter .
Deleting serial port access for a TACACS+ account:
The Delete PortFromTACACS command removes a TACACS+ account’s access to the serial port. You cannot remove access to the serial port for an administrative level account.
To delete serial port access for a TACACS+ account:
At the Smart CDU: prompt, type delete portfromtacacs console and a TACACS+ account number. Press Enter .
Displaying TACACS account access:
The List TacPriv command displays all access rights for a TACACS+ account.
To display TACACS account access:
At the Smart CDU: prompt, type list tacpriv , optionally followed by a TACACS+ account. Press Enter .
Example
The following command displays information about the TACACS+ account 1:
Smart CDU: list tacpriv 1<Enter>
TACACS+ Privilege Level: 1
Ports:
Port ID Port Name
Console Console
126
•
Advanced Operations Smart POPS PDU
Installation and Operations Manual
TACACS+ Technical Specifications
Authentication START Packet includes: action = 1 (TAC_PLUS_AUTHEN_LOGIN) priv_lvl = 0 (TAC_PLUS_PRIV_LVL_MIN) authen_type = 1 (TAC_PLUS_AUTHEN_TYPE_ASCII) service = 1 (TAC_PLUS_AUTHEN_SVC_LOGIN) user = (entered username) port = (access path into the PDU) rem_addr = ‘Sentry3_xxxxxx’ (xxxxxx is last six digits of MAC address) data = ‘‘ (null)
NOTE: The password is sent in a “continue” packet.
Authorization REQUEST Packet includes: authen_method = 6 (TAC_PLUS_AUTHEN_METH_TACACSPLUS) priv_lvl = 0 (TAC_PLUS_PRIV_LVL_MIN) authen_type = 1 (TAC_PLUS_AUTHEN_TYPE_ASCII) authen_service = 1 (TAC_PLUS_AUTHEN_SVC_LOGIN) user = (entered username) port = (access path into the PDU) rem_addr = ‘Sentry3_ xxxxxx
’ (xxxxxx is last six digits of Ethernet MAC address) service = ‘shell’ (for exec) cmd = ‘‘ (null)
NOTE: The access paths into the PDU which support TACACS+ are Console, Telnet, SSH, HTTP, and HTTPS. In the case of
Console and Modem, an administrator is allowed to rename these ports in which case the assigned name is used.
Smart POPS PDU
Installation and Operations Manual Advanced Operations
•
127
RADIUS
The Smart POPS family of products supports the Remote Authentication Dial-in User Service (RADIUS) protocol.
RADIUS provides a centralized network protocol to enable remote authentication and authorization, such as user names and passwords. With a central RADIUS server, user accounts do not need to be individually created locally on each PDU. This allows administrators to pre-define and configure (in each PDU product and in the RADIUS server), a set of necessary RADIUS privilege levels and user access rights for each level.
RADIUS is also used in enterprise-wide networks because it provides the administrator with high performance, less memory usage, less CPU cycles on routers and switches, and an open standard that is easily interoperable within the network.
In addition to the protocol-required attributes, the RADIUS authentication process can be extended by using private vendor-specific attributes (VSA). This extension allows Server Technology to create its own proprietary attributes to support features and services using the PDU in the RADIUS authentication process.
RADIUS Command Summary
Command
Set Authorder
Set RADIUS
Set RADIUS … Server
Set
RADIUS … Secret
Set RADIUS … Port
Set RADIUS … Timeout
Set RADIUS … Retries
Show RADIUS
Description
Specifies the authentication order for each new session attempt
Enables or disables RADIUS support
Configures the address of the RADIUS server
Sets the shared secret for the RADIUS server
Sets the port number of the RADIUS server
Configures the timeout interval for the RADIUS server
Sets the number of retries for the RADIUS server
Displays RADIUS configuration settings
Enabling and Setting Up RADIUS Support
The following configuration tasks are required to properly enable and set up RADIUS support on the primary and secondary RADIUS servers.
Enabling and disabling RADIUS support:
The Set RADIUS command enables or disables RADIUS support.
To enable or disable RADIUS support:
At the Smart CDU: prompt, type set radius , followed by enabled or disabled , and press Enter .
Setting the authentication order:
The Set Authorder command sets the authentication order for remote authentication sessions. The PDU supports two methods for authentication order: Remote > Local and Remote Only.
The Remote > Local method first attempts authentication with the RADIUS server, and, if unsuccessful, then attempts authentication with the local user database on the PDU.
The Remote Only method attempts authentication only with the RADIUS server, and, if unsuccessful, access is denied.
NOTE: With the Remote Only method, if authentication fails due to a communication failure with the RADIUS server automatic authentication fallback will occur to authenticate with the local user data base on the PDU.
To set the authentication order:
At the Smart CDU: prompt, type set authorder , followed by remotelocal or remoteonly and press Enter .
NOTE: Server Technology recommends not setting authentication order to Remote Only until RADIUS has been configured and tested.
128
•
Advanced Operations Smart POPS PDU
Installation and Operations Manual
Setting the RADIUS server address:
The Set RADIUS Server command sets the IP address or hostname of the primary or secondary server used for
RADIUS authentication requests.
NOTE: Both IPv4 and IPv6 formats are accepted for primary/secondary IP address or hostname.
To set the RADIUS server address:
At the Smart CDU: prompt, type set radius , followed by primary or secondary , followed by server , and the
RADIUS server’s IP address or hostname (maximum 63 characters). Press
Enter .
Examples
The following command sets the primary RADIUS server address to 98.76.54.32:
Smart CDU: set radius primary server 98.76.54.32<Enter>
The following command sets the secondary RADIUS server address to radius.servertech.com:
Smart CDU: set radius secondary server radius.servertech.com<Enter>
Setting the RADIUS secret:
The Set RADIUS Secret command sets the shared secret for the server used for RADIUS authentication requests.
To set the shared secret:
At the Smart CDU: prompt, type set radius , followed by primary or secondary , and followed by secret . Press
Enter .
Enter the shared secret and press Enter . For security, shared secret characters are not displayed.
The secret that was set for the primary server will not be cleared when setting the secret for the secondary server, and vice versa.
Changing the RADIUS port number:
The Set RADIUS Port command sets the server port number for RADIUS authentication requests.
To change the port number:
At the Smart CDU: prompt, type set radius , followed by primary or secondary , followed by port , and the port number (1-65535). Press Enter .
The default is 1812.
Example
The following command sets the secondary RADIUS server port number to 1855:
Smart CDU: set radius secondary port 1855<Enter>
Setting the RADIUS timeout value:
The Set RADIUS Timeout command sets the time interval to wait for a reply from the RADIUS server before resending the authentication request.
To set the timeout value:
At the Smart CDU: prompt, type set radius , followed by primary or secondary , followed by timeout , and the time interval in seconds (1-30). Press Enter .
Examples
The following command sets the primary RADIUS server timeout value to 15 seconds:
Smart CDU: set radius primary timeout 15<Enter>
The following command sets the secondary RADIUS server timeout value to 5 seconds:
Smart CDU: set radius secondary timeout 5<Enter>
Smart POPS PDU
Installation and Operations Manual Advanced Operations
•
129
Setting the number of RADIUS server retries:
The Set RADIUS Retries command specifies the number of times an authentication request is sent to the RADIUS server. The PDU attempts authentication with the primary server until the number of retries is reached, then will attempt authentication with the secondary server. If the PDU does not receive a response from these attempts, the authentication request will be rejected.
To set the number of retries:
At the Smart CDU: prompt, type set radius , followed by primary or secondary , followed by retries , and followed by the number of retries (0-10). Press Enter .
Examples
The following command sets the retries for the primary RADIUS server to 5:
Smart CDU: set radius primary retries 5<Enter>
The following command sets the retries for the secondary RADIUS server to 2:
Smart CDU: set radius secondary retries 2<Enter>
Displaying RADIUS configuration information:
The Show RADIUS command displays RADIUS configuration information.
To display the RADIUS configuration information:
At the Smart CDU: prompt, type show radius and press Enter .
Example
The following command displays the RADIUS configuration information:
Smart CDU: show radius<Enter>
RADIUS Configuration
RADIUS: Enabled
Auth Order: Remote->Local
Primary Server:
Shared Secret: ****
Port: 1812
Timeout: 15 seconds
Retries: 5
Secondary Server:
Shared Secret:
Port: 1855
Timeout: 5 seconds
Retries: 2
130
•
Advanced Operations Smart POPS PDU
Installation and Operations Manual
Vendor-Specific Attributes (VSA):
Server Technology has defined and formatted RADIUS vendor-specific attributes (VSA) in the dictionary.sti
file, which is available from Server Technology. The PDU is configured to recognize and use the configuration values in the file as specified by the network administrator, indicating to the RADIUS server that the defined attributes are based on Server Technology’s unique enterprise vendor code.
Using the format of the dictionary.sti file (located on the Server Technology FTP site at ftp.servertech.com
), the
RADIUS implementation supports the following vendor-specific attributes:
Vendor-Specific Attribute (VSA) Descriptions
Attribute
STI-Access-Level
Description
Indicates user access level for the Smart POPS PDU; values are 1-6 as follows; a valid access level is required or access to the PDU is denied.
Valid User Access Levels:
1 = Admin
2 = Power User
3 = User
4 = Reboot Only
5 = On Only
6 = View Only
STI-Env-Mon
STI-Ports
Determines user access rights to environmental monitoring; values are Yes or No. For the STI-
Access-Level value other than 1 (Admn), if STI-Env-Mon is not included for a user, default is no.
Specifies user access rights to ports; values are space-delimited strings of absolute IDs, names, or the special keyword “ALL”. String values are case-sensitive and limited to 253 characters. This attribute can be repeated to append strings that declare additional access rights. For STI-Access
Level values other than 1 (Admn) and 2 (Power User), if STI-Ports is not included for a user, the default is no ports.
NOTE: User access levels must be configured using the dictionary.sti
file. If the administrator does not use the dictionary.sti
file to configure a user, the user will not have access rights to the PDU.
Examples:
Administrator with full access and configuration rights: sti-admin Auth-Type := Local, User-Password == "admin"
STI-Access-Level = Admin
Power user with environmental monitoring allowed and full port access rights: sti-power Auth-Type := Local, User-Password == "power"
STI-Access-Level = Power-User,
STI-Env-Mon = Yes
User with environmental monitoring not allowed and specific port access rights: sti-user Auth-Type := Local, User-Password == "user"
STI-Access-Level = User,
STI-Env-Mon = No,
STI-Outlets = ".A1 .A2 Rtr1 Rtr2 Srvr1 Srvr2",
STI-Outlets += ".A3 .A4 Rtr3 Rtr4 Srvr3 Srvr4",
STI-Groups = "Routers Servers",
STI-Ports = "Console"
View-only user with environmental monitoring allowed and access rights: sti-view Auth-Type := Local, User-Password == "view"
STI-Access-Level = View-Only,
STI-Env-Mon = Yes
Smart POPS PDU
Installation and Operations Manual Advanced Operations
•
131
Logging
The Smart POPS PDU supports logging of system events both internally and externally. An internal log of more than
4000 events is automatically maintained and is reviewable by administrative users. For permanent/long-term log storage, Sentry supports the Syslog protocol. For immediate notification, Sentry also supports Email notifications.
Log entries include a sequential entry number, a date/time stamp and an event message. The event message is preceded with a message ‘type’ heading and if the event is tied to a user, the username will be included.
NOTE: For date/time stamp support, SNTP server support must be configured.
The PDU supports the following event message headers:
•
AUTH:
•
POWER:
•
CONFIG:
•
EVENT:
All authentication attempts.
All power state change requests.
All system configuration changes.
All general system events. Example: over/under threshold event.
Internal System Log
The internal system log is stored in the local memory and has support for up to 4097 continuously aging entries.
Viewing the internal system log:
The Show Log command allows users with administrative access to view the internal system log.
To view the internal system log:
At the Smart CDU: prompt, type show log , and press Enter .
Example
Smart CDU: show log
[1] EVENT: System boot complete
[2] EVENT: TCP/IP stack has started
[3] Jul 24 18:45:52 AUTH: User "ADMN" logged in -- connection source 10.1.2.80
using HTTP
[4] Jul 24 18:50:26 AUTH: User "ADMN" logged in -- connection source 10.1.2.80
using TELNET
[5] Jul 24 18:50:51 CONFIG: Silkscreen to UI mapping changed to 2 for tower
"Master"[A] by user "ADMN"
[6] Jul 24 18:54:00 CONFIG: Silkscreen to UI mapping changed to 3 for tower
"Master" [A] by user "ADMN"
More (Y/es N/o):
NOTE : To terminate from the Show Log command, press <Esc>.
132
•
Advanced Operations Smart POPS PDU
Installation and Operations Manual
Syslog
The Syslog support is RFC3164-compliant and enables off-PDU viewing and storage of log messages. The PDU supports external logging to up to two Syslog servers.
Syslog Command Summary
Command
Set Syslog HostIP
Set Syslog Port
Show Syslog
Description
Sets the IP address of the Syslog server
Sets the Syslog server port number
Displays all Syslog configuration information
Setting the Syslog server IP address:
The Set Syslog HostIP command sets the TCP/IP address of the Syslog server.
To set the Syslog server IP address:
At the Smart CDU: prompt, type set syslog , followed by hostip1 or hostip2 and the Syslog server’s IP address. Press
Enter .
Example
The following command sets the primary Syslog server IP address to 56.47.38.29:
Smart CDU: set syslog hostip1 56.47.38.29<Enter>
Changing the Syslog server port:
With Syslog support enabled, the Syslog server watches and responds to requests on the default Syslog port number
514. This port number may be changed using the Set Syslog Port command.
To change the Syslog port:
At the Smart CDU: prompt, type set syslog port , followed by the port number and press Enter .
Example
The following changes the Syslog port number to 411:
Smart CDU: set syslog port 411<Enter>
Displaying Syslog configuration information:
The Show Syslog command displays Syslog configuration information.
To display the Syslog configuration information:
At the Smart CDU: prompt, type show syslog and press Enter .
Example
The following command displays the Syslog configuration information:
Smart CDU: show syslog<Enter>
SYSLOG Configuration
Primary Syslog Server IP Address: 56.47.38.29
Secondary Syslog Server IP Address: 0.0.0.0
Syslog Server Port: 411
Smart POPS PDU
Installation and Operations Manual Advanced Operations
•
133
Email Command Summary
Command
Set Email
Set Email Auth
Set Email Config
Description
Enables or disables Email notification support
Enables or disables notification of all authentication attempts
Enables or disables notification of configuration changes
Enables or disables notification of general system events
Sets the email ‘From’ address
Set Email Event
Set Email From
Set Email Power
Set Email PrimaryTo
Set Email SecondaryTo
Set Email Test
Set Email SMTP Port
Set Email SMTP AuthType
Enables or disables notification of power state change requests
Sets the primary recipient email address
Sets the secondary recipient email address
Sends a test email to the target email destinations
Sets the SMTP server port number
Determines the SMTP authentication type
Set Email SMTP Host Sets the SMTP Host IP address or hostname
Set Email SMTP Password Sets the password for SMTP authentication with username
Set Email SMTP Use ‘From’ Address Uses the SMTP ‘From” address for SMTP authentication
Set Email SMTP Username
Set Email SMTP Useusername
Show Email
Sets the username for SMTP authentication
Uses the SMTP username/password for SMTP authentication
Displays all Email configuration information
Enabling or disabling Email notification Support:
The Set Email command enables or disables Email notification support.
To enable or disable Email notification support:
At the Smart CDU: prompt, type set email , followed by enabled or disabled and press Enter .
Setting the SMTP server address:
The Set Email Host command sets the IP address or hostname of the SMTP server.
NOTE: Both IPv4 and IPv6 formats are accepted for IP address or hostname.
To set the SMTP server address:
At the Smart CDU: prompt, type set email smtp host , followed by the SMTP server’s IP address or hostname and press Enter .
Examples
The following command sets the SMTP server address to 55.55.55.55:
Smart CDU: set email smtp 55.55.55.55<Enter>
The following command sets the SMTP server address to email.servertech.com:
Smart CDU: set email smtp email.servertech.com<Enter>
134
•
Advanced Operations Smart POPS PDU
Installation and Operations Manual
Changing the SMTP server port:
With SMTP support enabled, the PDU sends SMTP requests to the default SMTP port number 25. This port number may be changed using the Set Email SMTP Port command.
To change the TACACS port:
At the Smart CDU: prompt, type set email smtp port , followed by the port number and press Enter .
Example
The following changes the SMTP port number to 5555:
Smart CDU: set email smtp port 5555<Enter>
Setting the SMTP authentication type:
NOTES:
•
SMTP authentication allows the mail client in the PDU to login to the mail server during the process of sending a mail. The mail server
may require this login to relay mail to another mail server.
•
Support SMTP authentication type are: None (default, no SMTP authentication); Digest-MD5; CRAM-MD5; Login; and Plain. SMTP
authentication occurs with a configured username and password, or you can use the ‘From’ address in place of the username.
To determine the SMTP authentication type:
At the Smart CDU: prompt, type set email smtp authtype , followed by the authentication method, and press Enter .
Examples
The following sets the SMTP authentication type to Digest-MD5:
Smart CDU: set email smtp authtype DIGESTMD5<Enter>
The following sets the SMTP authentication type to CRAM-MD5:
Smart CDU: set email smtp authtype CRAMMD5<Enter>
Setting the ‘From’ email address:
The Set Email From command sets the ‘from’ email address. By default, this is set to ‘Sentry3_’ plus the last three octets of the unit’s MAC address. Example: ‘Sentry3_510c90@’
To set the ‘From’ email address:
At the Smart CDU: prompt, type set email from , followed by the originating email address and press Enter .
Example
The following command sets the ‘from’ email address to [email protected]:
Smart CDU: set email from [email protected]<Enter>
Setting the ‘Send To’ email address:
The Set Email PrimaryTo and Set Email SecondaryTo commands set the recipient email addresses.
To set the ‘Send To’ email address:
At the Smart CDU: prompt, type set email , followed by primaryto or secondaryto and the destination email address.
Press Enter .
If the primary ‘send to’ address fails, the system then attempts to send the email to the secondary ‘send to’ address.
Examples
The following command sets the primary ‘to’ email address to [email protected]:
Smart CDU: set email primaryto [email protected]<Enter>
The following command sets the secondary ‘to’ email address to [email protected]:
Smart CDU: set email secondaryto [email protected]<Enter>
Smart POPS PDU
Installation and Operations Manual Advanced Operations
•
135
Setting the Email SMTP authentication username:
The Set Email SMTP Username command sets the username for SMTP authentication.
At the Smart CDU prompt, type set email smtp username , followed by the SMTP username, and press Enter .
Setting the Email SMTP authentication password:
The Set Email SMTP Password command sets the password for SMTP authentication with username.
At the Smart CDU: prompt, type set email smtp password , followed by the SMTP password, and press Enter .
Setting the Email SMTP Use Username :
The Set Email SMTP Useusername command uses the SMTP username for SMTP authentication.
At the Smart CDU: prompt, type set email smtp useusername , followed by the username, and press Enter .
Setting the Email SMTP Use ‘From’ Address:
The Set Email SMTP Usefromaddr command uses the SMPT ‘From’ address for SMTP authentication.
At the Smart CDU: prompt, type set email smtp usefromaddr , and press Enter .
Enabling or disabling event notification types:
The Set Email Event, Set Email Auth, Set Email Power and Set Email Config commands enable or disable email notification of event types.
To enable or disable event notification types:
At the Smart CDU: prompt, type set email , followed by event , auth , power or config and enabled or disabled .
Press Enter .
Examples
The following command sets the enables email notification general system events:
Smart CDU: set email event enabled<Enter>
The following command sets the disables email notification authentications attempts:
Smart CDU: set email auth disable<Enter>
Sending a test email:
The Set Email Test command sends a test email to the target email destinations.
At the Smart CDU: prompt, type set email test , and press Enter .
136
•
Advanced Operations Smart POPS PDU
Installation and Operations Manual
Displaying Email configuration information:
The Show Email command displays Email configuration information.
To display the Email configuration information:
At the Smart CDU: prompt, type show email and press Enter .
Example
The following command displays the Email configuration information:
Smart CDU: show email
Email/SMTP Configuration
Email/SMTP Configuration
Email Notifications: Enabled
SMTP
Host: email.servertech.com
Port: 25
Authentication Type: Any
Authenticate With: 'From' Address
Username: djones
Password: ********
'From' Address: Sentry3_50e021@
Primary 'Send To' Addr: [email protected]
Secondary 'Send To' Addr:
Subject ID: [Sentry3_5246401]
EVENT Messages: Enabled
AUTH Messages: Disabled
POWER Messages: Disabled
CONFIG Messages: Disabled
Smart POPS PDU
Installation and Operations Manual Advanced Operations
•
137
Upload/Download
The Smart POPS PDU supports the ability to upload and download system configurations using a standard FTP client. This feature enables for backup and restoration of system configuration as well as upload of ‘template’ configurations to ease large initial equipment deployments.
Upload/Download Command Summary
Command
Set FTP Server
Show FTP
Description
Enables or disables the FTP server
Displays FTP configuration information
Integrated FTP Server
The PDU supports an integrated FTP Server which must be enabled for Upload/Download support. The FTP Server supports a single user at a time. Once an administrative user has authenticated with the FTP Server, standard FTP client commands may be used to upload or download PDU configurations.
NOTE: The integrated FTP Server does not support web browser FTP file transfers. A non-web-browser is required for all
Upload/Download requests.
Enabling and disabling the FTP server:
The Set FTP Server command is used to enable or disable the integrated FTP server.
To enable or disable the FTP server:
At the Smart CDU: prompt, type set ftp server , followed by enabled or disabled and press Enter .
FTP Configuration Files
The FTP server supports upload/download of two configuration files: CONFIG.BIN and NETWORK.INI. These files may be uploaded or downloaded using FTP PUT and GET operations.
•
CONFIG.BIN This file contains the entire configuration of the PDU excluding TCP/IP settings, serial/factory-only configurations, the x.509 certificate (SSL) and SSH keys. This file in encoded to keep all data (including usernames, passwords etc.) out of plain view. This file is not editable.
•
FTP.INI This file contains only the FTP settings (FTP Host, username, password, filepath, filename and automatic updates support). This file is user readable and editable ‘plain text’ file.
•
NETWORK.INI This file contains only the TCP/IP settings (IP address, subnet mask, gateway, DNS1 and
DNS2). This file is user readable and editable ‘plain text’ file.
•
SNTP.INI This file contains only the SNTP settings (SNTP Hosts and GMT offset). This file is user readable and editable ‘plain text’ file.
NOTE: The CONFIG.BIN file while encoded is not encrypted and susceptible to decoding using simple tools. Server Technology recommends the secure storage of CONFIG.BIN backup images.
138
•
Advanced Operations Smart POPS PDU
Installation and Operations Manual
Upload/Download Process
GETting a configuration file (Download):
1.
Open the FTP client.
In a Windows environment, in the Run window type ftp and press Enter.
2.
At the prompt, type open , followed by the IP address of the PDU, and press Enter .
FTP> open 12.34.56.78<Enter>
3.
Authenticate with the appropriate administrative username and password.
4.
At the prompt, type get , followed by the filename and press Enter .
FTP> get config.bin<Enter>
5.
At the prompt, type close to close the connection to the PDU.
FTP> close
PUTting a configuration file (Upload):
NOTE: Uploading the CONFIG.BIN file takes considerably longer than the NETWORK.INI file. When uploading both, Server
Technology recommends uploading the NETWORK.INI file first.
1.
Open the FTP client. In a Windows environment, in the Run window type ftp and press Enter .
2.
At the prompt, type open , followed by the IP address of the PDU and press Enter .
FTP> open 12.34.56.78<Enter>
3.
Authenticate with the appropriate administrative username and password.
4.
At the prompt, type put , followed by the filename and press Enter .
FTP> put network.ini<Enter>
5.
At the prompt, type close to close the connection to the PDU and force a restart of the device.
FTP> close
Smart POPS PDU
Installation and Operations Manual Advanced Operations
•
139
Chapter 5: Appendices
Appendix A: Resetting to Factory Defaults
You can reset the non-volatile RAM that stores all configurable options. This clears all administrator-editable fields and resets all command line configurable options to their default values, including all user accounts.
You can also reset the unit to factory defaults from the command line or the Web interface, or by pressing the Reset button. You must have administrator-level privileges to issue the command. Using the reset button may be necessary when a forgotten password prevents administrator login. Each of the methods updates the current working configuration to the factory defaults.
NOTE: Resetting the unit resets all TCP/IP and Telnet/Web configurations. Reconfiguring TCP/IP and Telnet/web settings is required.
Reset to factory defaults from the Web interface
On the Restart page in the Tools section of the Web interface, select Restart and reset to factory defaults from the drop-down menu and click Apply .
Reset to factory defaults from the command line
At the Smart CDU: prompt, type restart factory and press Enter .
Reset to factory defaults using the reset button
Locate the recessed reset button directly beside the Serial & Ethernet ports. You will need a non-conductive, nonmetallic tool that fits inside the recess.
NOTE: This method will not work if you disable the Reset button.
Insert the tool in the recess, then depress and hold the reset button for at least ten seconds.
NOTE: If you press and hold the Reset button for more than 15 seconds, the reset will terminate.
140
•
Appendices Smart POPS PDU
Installation and Operations Manual
Appendix B: Uploading Firmware
You may upload new versions of firmware using File Transfer Protocol (FTP). This allows access to new firmware releases for firmware improvements and new features additions.
NOTE: To begin an FTP upload session, you must first configure the FTP Host address, username/password, filename, and filepath.
You may initiate an FTP upload session by issuing a command or from the Web interface. You must have administrator-level privileges to initiate an upload.
Initiate an FTP upload session from the Web interface
On the Restart page in the Tools section of the Web interface, select Restart and upload firmware via FTP from the drop-down menu and click Apply .
Upon issuing this command the unit will restart and upload the firmware file specified with the FTP Filename command from the previously configured FTP Host.
Initiate an FTP upload session from the command line
The Restart FTPLoad command initiates an upload of firmware. Upon issuing this command the unit will restart and upload the firmware file specified with the FTP Filename command from the previously configured FTP Host.
To initiate an FTP firmware upload session:
At the Smart CDU: prompt, type restart ftpload and press Enter .
Smart POPS PDU
Installation and Operations Manual Appendices
•
141
Appendix C: Technical Specifications
Branch Circuit Protection
Server Technology PDUs are equipped with one of several types of Branch Circuit Protection, including internal fuses, retractable fuse holders, and circuit breakers, as illustrated below.
These fuses and circuit breakers meet the strict safety requirements of UL 60950-1 and EN 60950-1 for Branch
Circuit Protection.
Circuit Breaker
If a circuit breaker is tripped, it can be reset by pressing or switching it back ON once the cause of the overload or short circuit has been identified, removed, or resolved. Intelligent PDUs with branch circuit sensing will display a flashing FE on the input current LED(s) to indicate Fuse Error .
Alternatively, the circuit breaker can be turned OFF manually by inserting a slotted or flatblade tool into the OFF switch as shown in the illustration on the left.
It is not necessary to disconnect the AC power source to perform this operation.
NOTE: This circuit breaker contains no user-serviceable parts. Do not open or disassemble this part.
142
•
Appendices Smart POPS PDU
Installation and Operations Manual
Compact Fuse Holder
The Compact Fuse Holder is a UL 98 listed Fused Disconnect Switch that allows the user to turn OFF the branch circuit and safely service the fuse without having to disconnect the PDU AC power source prior to performing this operation.
To help identify which fuse is open, blown, or missing, the Open Fuse
Indicator Light glows orange when the PDU is powered and the Switch
Handle is in the ON position.
Additionally, intelligent PDUs with branch circuit sensing will display a flashing FE on the input current LEDs to indicate Fuse Error .
To service the fuse or turn OFF the branch, rotate the Switch
Handle toward the Fuse Access Door.
Next, rotate the Fuse Access Door counter clock-wise until it opens.
Only replace the fuse with the same size, type, and ratings as the original fuse.
Reverse these steps after the new fuse(s) is installed.
CAUTION:
•
Failure to replace the fuse with the same size, type, and ratings will damage the PDU and the connected and nearby
equipment, and will cause electrical shock, fire, explosion, or injury/death.
•
Do not attempt to open the Fuse Access Door without first setting the Switch Handle in the OFF position. Forcibly
rotating the Fuse Access Door will damage the fused holder.
Smart POPS PDU
Installation and Operations Manual Appendices
•
143
Fuse Retractor, Fuse Access Window, and Fuse Access Cover
The PDU AC power source must be disconnected prior to servicing a unit with the Fuse Retractor,
Fuse Access Window, and Fuse Access Cover .
Intelligent PDUs with branch circuit sensing will display a flashing FE on the input current LEDs to indicate
Fault Error .
For the fuse retractor, rotate the fuse holder exposing the fuse.
For the fuse access window or cover, remove the screws that secure the plastic cover.
Once the fuses are exposed, carefully remove and replace with a new one of the same size, type, and ratings as the original. A fuse puller may be needed for fuse access windows and covers.
Reverse these steps after the new fuse(s) is installed.
CAUTION:
•
Failure to replace the fuse with the same size, type, and ratings will damage the PDU and the connected and nearby
equipment, and will cause electrical shock, fire, explosion, or injury/death.
Time-Delay Fuses – Class G
NOTE: Server Technology PDUs ship with Bussman SC-20 fuses.
Ampere Rating Voltage Interrupting Rating
20 A 600 Vac 100,000 A RMS Sym. AC
* Cooper Bussman Technical Data Sheet 1024
Bussman Part No.
*
SC-20
Server Technology Part No.
FUSE-SC20G
For technical support or service with time-delay fuses, contact Server Technology as follows:
Experience Server Technology's FREE Technical Support
Server Technology understands that there are often questions when installing and/or using a new product. Free
Technical Support is provided from 8 a.m. to 5 p.m. PST, Monday through Friday. After-hours service is provided to ensure your requests are handled quickly no matter what time zone or country you are located in.
Server Technology, Inc.
1040 Sandhill Drive
Reno, Nevada 89521 USA
Tel: 1-800-835-1515 Web: www.servertech.com
Fax: 775-284-2065 Email: [email protected]
144
•
Appendices Smart POPS PDU
Installation and Operations Manual
Data Connections
RS-232 port
Smart POPS PDUs are equipped standard with an RJ45 DTE RS-232c serial port. This connector may be used for direct local access or from other serial devices such as a terminal server. An RJ45 crossover cable is provided for connection to an RJ45 DCE serial port.
4
5
6
7
8
Pin DTE Signal Name
1 Request to Send RTS
2
3
Data Terminal Ready DTR
Transmit Data TD
Signal Ground
Signal Ground
Receive Data
Data Set Ready
Clear to Send
RD
DSR
CTS
Input/Output
Output
Output
Output
Input
Input
Input
8 7 54321
RJ45 to DB9F serial port adapter
An RJ45 to DB9F serial port adapter is provided in conjunction with the RJ45 crossover cable to connect to a PC
DB9M DCE serial port. The adapter pin-outs below reflect use of the adapter with the provided RJ45 crossover cable.
Input/Output
3
4
5
6
7
8
Pin DCE Signal Name
1
2 Receive Data RD
Transmit Data TD
Data Terminal Ready DTR
Signal Ground
Data Set Ready
Request to Send
Clear to Send
DSR
RTS
CTS
Output
Input
Input
Output
Input
Output
5
9
4
8
3
7
2
6
1
Smart POPS PDU
Installation and Operations Manual Appendices
•
145
Regulatory Compliance
Product Safety
Units have been safety tested and certified to the following standards:
•
USA/Canada UL 60950-1:2007 and CAN/CSA 22.2 No. 60950-1-07
•
European Union EN 60950-1:2006 + A11 +A1 + A12
This product is also designed for Norwegian IT power system with phase-to phase voltage 230V.
USA Notification
Note: This equipment has been tested and found to comply with the limits for a Class A digital device, pursuant to part 15 of the FCC Rules. These limits are designed to provide reasonable protection against harmful interference when the equipment is operated in a commercial environment. This equipment generates, uses, and can radiate radio frequency energy and, if not installed and used in accordance with the instruction manual, may cause harmful interference to radio communications. Operation of this equipment in a residential area is likely to cause harmful interference in which case the user will be required to correct the interference at the user’s own expense.
Modifications not expressly approved by the manufacturer could void the user's authority to operated the equipment under FCC rules.
Canadian Notification
This Class A digital apparatus complies meets all requirements of the Canadian Interference-Causing Equipment
Regulations.
Cet appareil numérique de la classe A respecte toutes les exigencies du Règlement sur le matériel brouilleur du
Canada.
European Union Notification
Products with the CE Marking comply with both the EMC Directive (89/336/EEC) and the Low Voltage Directive
(73/23/EEC) issued by the Commission of the European Community.
Compliance with these directives implies conformity to the following European Norms:
•
EN55022 Electromagnetic Interference
•
EN55024 Electromagnetic Immunity
•
•
EN60950-1 Product Safety
EN61000-3 Harmonics and Flicker
Products with the following mark comply with the RoHS Directive (2002/95/EC) issued by the Commission of the European Community.
Japanese Notification
この装置は、情報処理装置等電波障害自主規制協議会(VCCI)の基準に基づくクラス A 情報技術装置
です。この装置を家庭環境で使用すると電波妨害を引き起こすことがあります。この場合には使用者が適
切な対策を講ずるよう要求されることがあります。
本製品に同梱または付属しております電源コードは、本製品専用です。本製品以外の製品ならびに他の用
途に使用しないで下さい。
146
•
Appendices Smart POPS PDU
Installation and Operations Manual
Chinese Notification
关于符合中国《电子信息产品污染控制管理办法》的声明
产品中有毒有害物质的名称及含量
部件名称
(Parts)
机箱子组件
(Chassis Subassembly)
印刷板组件
(PCAs)
O
铅 (Pb) 汞 (Hg) 镉 (Cd) 六价铬 (Cr (VI)) 多溴联苯 (PBB) 多溴二苯醚 (PBDE)
O
X
O
O
有毒有害物质或元素
(Hazardous Substance)
O
O
O
O
O
O
O
O
表示该有毒有害物质在该部件所有均质材料中的含量均在
SJ/T 11363-2006
标准规定的限量要求以下。
Indicates that this hazardous substance contained in all homogeneous materials of this part is below the limit requirement in SJ/T
11363-2006.
X
表示该有毒有害物质至少在该部件的某一均质材料中的含量超出
SJ/T 11363-2006
标准 规定的限量要求。
Indicates that this hazardous substance contained in at least one of the homogeneous materials of this part is above the limit requirement in SJ/T 11363-2006.
Recycling
Waste Electrical and Electronic Equipment (WEEE)
In the European Union, this label indicates that this product should not be disposed of with household waste.
It should be deposited at an appropriate facility to enable recovery and recycling.
Server Technology Inc. encourages the recycling of its products. Disposal facilities, environmental conditions and regulations vary across local, state and country jurisdictions, so Server Technology encourages consultation with qualified professional and applicable regulations and authorities within your region to ensure proper disposal.
Smart POPS PDU
Installation and Operations Manual Appendices
•
147
Appendix D: Product Support Information
Warranty
For Server Technology product warranty information, visit our website: www.servertech.com
Technical Support
Experience Server Technology's FREE Technical Support
Server Technology understands that there are often questions when installing and/or using a new product. Free
Technical Support is provided from 8 a.m. to 5 p.m. PST, Monday through Friday. After-hours service is provided to ensure your requests are handled quickly no matter what time zone or country you are located in.
Server Technology, Inc.
1040 Sandhill Drive
Reno, Nevada 89521 USA
Tel: 1-800-835-1515
Fax: 775-284-2065
Web: www.servertech.com
Email: [email protected]
Return Merchandise Authorization
If you have a product that is not functioning properly and needs technical assistance or repair, see the Server
Technology Return Merchandise Authorization process at: www.servertech.com
148
•
Appendices Smart POPS PDU
Installation and Operations Manual
advertisement
* Your assessment is very important for improving the workof artificial intelligence, which forms the content of this project
Related manuals
advertisement
Table of contents
- 4 Quick Installation Checklist
- 4 Technical Support
- 5 PDU Power Pivot
- 6 Equipment Overview
- 7 IPv6 and Server Technology Products
- 7 PDU Firmware – Protocol Support
- 7 IPv6 and IPv4 Protocols:
- 7 IPv4-Only Protocols:
- 8 Network-Enabled Modes
- 9 Viewing Network Status
- 10 Standard Accessories
- 10 Mounting Hardware
- 10 Additional Items for Models with C20 Inlets
- 10 Optional Accessories
- 10 Additional Required Items
- 11 Safety Precautions
- 12 Input Power Cord Retention Options for PDUs with IEC C20 Inlets
- 12 Procedure A
- 12 Procedure B
- 13 Attaching Safety Earth Ground Connection
- 14 Mounting the PDU
- 14 Horizontal/Rack
- 14 Vertical
- 15 Attaching the Expansion Module
- 15 Connecting to the Power Source
- 15 Connecting Devices
- 15 Connecting the Sensors
- 15 Connecting to the Unit
- 15 Serial (RS232) port
- 15 Ethernet port
- 18 Interfaces
- 18 Usernames and Passwords
- 18 Web Interface
- 19 Logging In
- 19 To log in the Web interface:
- 19 System Summary
- 20 System Information
- 20 Line Status
- 20 Temperature Status
- 20 Humidity Status
- 20 Field Descriptions
- 21 Sensor Graph Color-Coding
- 21 Line (Load) Status:
- 21 Temperature Status:
- 21 Humidity Status:
- 22 Logical Group Separators
- 22 Power Monitoring
- 22 Outlets
- 23 Input Feeds
- 24 System
- 25 UPS
- 25 Environmental Monitoring
- 25 Sensors
- 26 Contacts
- 26 ADCs
- 27 Configuration
- 27 System
- 27 Creating a pre-login banner:
- 27 Creating a descriptive system location name:
- 28 Configuring the LED display orientation:
- 28 Enabling or disabling strong password requirements:
- 28 Acceptable strong passwords:
- 28 Enabling or disabling the configuration reset button:
- 28 Setting the system area (footprint):
- 28 Setting the system area unit of measure:
- 28 Setting the power factor:
- 28 Setting the 3-phase load out-of-balance threshold:
- 28 Setting the 3-phase load out-of-balance alerting:
- 29 Setting the temperature scale:
- 29 Setting the system area:
- 29 Setting the system area unit of measure:
- 29 Setting the system input power factor:
- 29 Setting the 3-phase load out-of-balance threshold:
- 29 Configuring the Command Line Interface (CLI) session timeout:
- 29 Configuring the web session (Web Interface) timeout:
- 29 Enabling/Disabling StartUp Stick(:
- 29 Creating a descriptive unit name:
- 29 Creating a descriptive input feed name:
- 29 Creating a descriptive serial port name:
- 29 Creating a descriptive environmental monitor name:
- 29 Creating descriptive sensor names:
- 29 Creating analog-to-digital converter names:
- 30 Network
- 30 Network:
- 30 State:
- 30 Setting the IPv6 or IPv4 static IP address, gateway, subnet mask, or DSN address:
- 31 Enabling Dynamic Host Configuration Protocol (DHCP):
- 31 Setting the fully-qualified domain name (FQDN):
- 31 Enabling the DHCP boot delay:
- 31 Enabling static address fallback:
- 31 Network defaults:
- 31 Setting the IP address, subnet mask, gateway or DNS address:
- 32 Telnet/SSH
- 32 Enabling or disabling Telnet or SSH support:
- 32 Changing the Telnet or SSH server port number:
- 32 Enabling or disabling SSH server authentication methods:
- 33 HTTP/SSL
- 33 Enabling or disabling HTTP or SSL support:
- 33 Setting SSL secure access:
- 33 Changing the HTTP server or SSL port number:
- 33 Uploading a custom user certificate:
- 33 Enabling and disabling user certificates:
- 34 Uploading the certificate:
- 34 Removing a certificate:
- 35 Setting the Sentry Power Manager (SPM) options:
- 35 SPM Secure Access:
- 35 SPM Password:
- 35 Serial Ports
- 36 Setting the data-rate for all serial ports:
- 36 Setting the serial port timeout value:
- 36 Creating a descriptive serial port name:
- 36 Enabling or disabling serial port active signal checking:
- 36 Enabling or disabling the Command Line Interface (CLI):
- 36 Enabling or disabling the Serial Command Protocol (SCP):
- 36 Enabling or disabling the Serial Command Protocol (SCP) emulation:
- 36 Enabling or disabling the RFTAG option:
- 37 Configuring the Bluetooth™ options:
- 37 Towers
- 37 Creating a descriptive tower name:
- 37 Setting the tower serial number:
- 37 Setting the tower model number:
- 37 Setting the operational AC or DC voltage type:
- 38 Setting the operational AC voltage type:
- 38 Input Feeds
- 38 Creating a descriptive input feed name:
- 38 Setting the infeed operational voltage:
- 38 Setting the infeed maximum load capacity:
- 38 UPS
- 39 To add a new UPS:
- 39 To edit the UPS type:
- 39 Selecting the UPS type:
- 39 Editing the UPS Hostname/IP Address:
- 39 Editing the UPS SNMP GET community string:
- 39 Enabling/Disabling UPS voltage polling:
- 39 Editing the UPS SNMP port number:
- 39 Associate the UPS with an infeed:
- 39 To remove a UPS:
- 39 Users
- 39 Creating a new user:
- 40 Removing a user:
- 40 Changing a user password:
- 40 Changing a user’s access privilege level:
- 40 Adding and deleting serial port access:
- 41 FTP
- 41 Setting the FTP Host Address:
- 41 Setting the FTP username:
- 41 Setting the FTP password:
- 41 Setting the Directory (filepath):
- 41 Setting the filename for upload:
- 41 Testing the FTP upload configuration:
- 42 Enabling or disabling automatic updates:
- 42 Setting the automatic update scheduled day:
- 42 Setting the automatic update scheduled hour:
- 42 Enabling or disabling the FTP server:
- 43 SNTP/Syslog
- 43 About Daylight Saving Time(DST)
- 43 Setting the local date/time:
- 43 Setting the SNTP primary/secondary server address:
- 43 Setting the Local GMT offset (hours/minutes):
- 44 Enabling or disabling Daylight Saving Time (DST):
- 44 Setting Daylight Saving Time (DST) start/end date/time options:
- 44 Setting the Syslog server address:
- 44 Changing the Syslog server port number:
- 44 SNMP/Thresholds
- 45 About SNMP versions:
- 45 Enabling or disabling SNMP v3 support:
- 45 Setting the SNMPv3 read-write (RW) user or read-only (RO) user:
- 45 Configuring the SNMPv3 read-write (RW) user or read-only (RO) user authentication type:
- 45 Setting the SNMPv3 read-write (RW) user or read-only (RO) user authentication password:
- 45 Configuring the SNMPv3 read-write (RW) user or read-only (RO) user privacy type:
- 45 Setting the SNMPv3 read-write (RW) user or read-only (RO) user privacy password:
- 45 Setting the SNMPv3 trap username:
- 45 Configuring general parameters for any SNMP version:
- 45 Setting trap destinations:
- 45 Setting the error trap repeat time:
- 45 Setting the trap format version:
- 46 Setting IP restrictions:
- 46 Setting the SNMP SysName, SysLocation or SysContact objects:
- 46 Enabling or disabling tower traps:
- 46 Configuring input feed traps:
- 46 Configuring outlet traps:
- 46 Enabling or disabling Environmental Monitor traps:
- 46 Configuring the Temperature and Relative Humidity sensor traps:
- 46 Configuring the Temperature and Relative Humidity sensor thresholds:
- 47 Configuring Temperature and Humidity Recovery Delta (Hysteresis):
- 48 LDAP
- 48 Enabling or disabling LDAP support:
- 48 Configuring the authentication order:
- 48 Setting the LDAP server address:
- 48 Changing the LDAP server port:
- 49 Setting the LDAP bind type:
- 49 Setting the search bind Distinguished Name (DN):
- 49 Setting the search bind password for Distinguished Name (DN):
- 49 Setting the user search base Distinguished Name (DN):
- 49 Setting the user search filter:
- 49 Setting the group membership attribute:
- 49 Enabling or disabling group search:
- 49 Setting the group search base Distinguished Name (DN):
- 49 Setting the user membership attribute name:
- 49 Setting the DNS IP address:
- 50 Configuring LDAP groups:
- 50 Creating an LDAP group:
- 50 Removing an LDAP group:
- 50 Changing an LDAP group’s access level:
- 50 Granting or removing environmental monitoring viewing privileges :
- 50 Adding and Deleting serial port access:
- 51 TACACS+
- 51 Enabling or disabling TACACS+ support:
- 51 Setting the TACACS+ server address:
- 51 Changing the TACACS+ server port:
- 51 Configuring the authentication order:
- 51 Setting the TACACS+ encryption key:
- 51 Configuring TACACS+ privilege levels:
- 51 Changing a TACACS+ Privilege Level’s access privilege level:
- 51 Adding and Deleting serial port access:
- 52 RADIUS
- 52 Enabling or disabling RADIUS support:
- 52 Configuring the authentication order:
- 52 Changing the RADIUS server address:
- 52 Setting the RADIUS shared secret:
- 52 Changing the RADIUS server port:
- 52 Setting the RADIUS server timeout value:
- 53 Setting the number of RADIUS server retries:
- 53 SMTP/Email
- 53 Enabling or disabling Email support:
- 53 Setting the SMTP server address:
- 53 Changing the SMTP server port:
- 53 Setting the SMTP authentication type:
- 54 Setting the Email SMTP authentication username:
- 54 Setting the Email SMTP authentication password:
- 54 Setting the ‘From’ email address:
- 54 Setting the ‘Send To’ email address:
- 54 Setting the subject ID:
- 54 Enabling or disabling event type notifications:
- 54 Sending a test email:
- 54 Features
- 55 Tools
- 55 Ping
- 55 Change Password
- 55 Changing a password:
- 55 Firmware
- 56 View Log
- 56 Reviewing the system log:
- 56 Restart
- 56 Performing a warm boot:
- 56 Resetting to factory defaults:
- 56 Uploading new firmware:
- 56 Generating a new SSL X.509 certificate:
- 56 Computing new SSH security keys:
- 57 Command Line Interface
- 57 Logging In
- 57 To log in by RS-232 or Telnet:
- 60 Operations Commands
- 60 Displaying infeed status:
- 60 To display status of one or more infeeds:
- 60 Examples
- 60 Connecting to a serial device:
- 60 To connect to a serial device:
- 60 To disconnect from a serial device:
- 61 Displaying the status of the Environmental Monitor:
- 61 To display the status of the Environmental Monitor:
- 61 Example
- 61 Changing a password:
- 61 To change a password:
- 61 Starting a new session:
- 61 To start a new session:
- 61 Ending a session:
- 61 To end a session:
- 62 Displaying UPS status:
- 62 To display status of one or more UPS devices:
- 62 Example
- 62 Administration Commands
- 62 User Administration
- 62 Creating a user account:
- 62 To create a user account:
- 62 Example
- 62 Removing a user account:
- 62 To remove a user account:
- 63 Changing a password:
- 63 To change a password:
- 63 Example
- 63 Setting user access level privileges:
- 63 To set the access level privilege for a user:
- 63 Examples
- 63 Displaying the access privilege levels:
- 63 To display user access privilege levels:
- 63 Example
- 63 Adding serial port access to a user:
- 63 To grant serial port access to a user:
- 64 Deleting serial port access for a user:
- 64 To delete serial port access for a user:
- 64 Displaying user serial port access:
- 64 To display serial port access:
- 64 Example
- 64 Input Feed Administration
- 64 Creating a descriptive infeed name:
- 64 To create a infeed name:
- 64 Example
- 64 Setting the infeed operational voltage
- 64 To set the infeed operational voltage:
- 64 Example
- 64 Setting the infeed maximum load capacity
- 64 To set the infeed maximum load capacity:
- 64 Example
- 65 Displaying infeed information:
- 65 To display tower information:
- 65 Example
- 66 Tower Administration
- 66 Creating a descriptive tower name:
- 66 To create a tower name:
- 66 Example
- 66 Setting the tower serial number:
- 66 To set the tower serial number:
- 66 Example
- 66 Setting the tower model number:
- 66 To set the tower model number:
- 66 Example
- 66 Setting the tower AC or DC voltage type:
- 66 To set the tower AC/DC voltage type:
- 66 Example
- 67 Setting the tower AC voltage type:
- 67 To set the tower AC voltage type:
- 67 Example
- 67 Displaying tower information:
- 67 To display tower information:
- 67 Example
- 67 Tower ID: .A Name: TowerA Product S/N: AA06F011157 Model No.: CS-24V2-C20 3-Phase: No Power Type: AC
- 67 Environmental Monitor Administration
- 67 Creating a descriptive Environmental Monitor name:
- 67 To create an Environmental Monitor name:
- 67 Example
- 67 Creating a descriptive temperature/humidity sensor name:
- 67 To create a temperature/humidity sensor name:
- 67 Example
- 68 Serial Port Administration
- 68 Creating a descriptive serial port name:
- 68 To create a port name:
- 68 Example
- 68 Setting the serial ports data-rate:
- 68 To set the serial port data-rate:
- 68 Example
- 68 Enabling or disabling active signal checking for serial connections:
- 68 To enable or disable active signal checking for serial connections:
- 68 Setting the serial port timeout value:
- 68 To set the serial port timeout value for an individual port:
- 68 At the Smart CDU: prompt, type set port timeout, followed by the port ID or name, followed by a timeout value from 0 to 60 (in minutes), and press Enter.
- 69 Configuring the Bluetooth™ options:
- 69 To set the Bluetooth™ module name:
- 69 To set the Bluetooth™ discoverability:
- 69 To set the Bluetooth™ pin code:
- 69 To set the Bluetooth™ transmission power:
- 70 Enabling or disabling the Command Line Interface (CLI):
- 70 To enable or disable the CLI:
- 70 Enabling or disabling the Serial Command Protocol (SCP):
- 70 To enable or disable the SCP:
- 70 Enabling or disabling the Serial Command Protocol (SCP) emulation:
- 70 To enable or disable the SCP emulation:
- 70 Enabling or disabling the RFTAG option:
- 70 To enable or disable the RF Code sensor options:
- 70 Displaying serial port information:
- 70 To display serial port information:
- 70 Example
- 71 System Administration
- 71 Creating a pre-login banner:
- 71 To create a pre-login banner:
- 71 Creating a location description:
- 71 To create a location description:
- 71 Examples
- 71 Setting the system area:
- 71 To set the system area:
- 71 Example
- 71 Setting the system area unit of measure:
- 71 To set the system area unit of measure:
- 72 Setting the power factor:
- 72 To set the power factor:
- 72 Setting the 3-phase load out-of-balance threshold:
- 72 To set the 3-phase load out-of-balance threshold:
- 72 Example:
- 72 Setting the 3-phase load out-of-balance alert:
- 72 Example:
- 73 Displaying system configuration information:
- 73 To display system configuration information:
- 73 Example
- 73 Displaying system power status:
- 73 To display system power status:
- 73 Example
- 74 Configuring the LED display orientation:
- 74 To configure the LED display orientation:
- 74 Example
- 74 Enabling or disabling strong passwords:
- 74 To enable or disable strong passwords:
- 74 Enabling or disabling the external configuration reset button:
- 74 To enable or disable the configuration reset button:
- 74 Enabling or disabling the ‘more’ prompt:
- 74 To enable or disable ‘more’:
- 74 Setting the outlet sequence order:
- 74 Setting the temperature scale:
- 74 To set the temperature scale:
- 75 Configuring the Command Line Interface (CLI) session timeout:
- 75 To configure the CLI Session Timeout:
- 75 Example:
- 75 Configuring the web session (Web Interface) timeout:
- 75 To configure the web session timeout:
- 75 Example:
- 75 Customizing the CLI prompt:
- 75 To customize the CLI prompt:
- 75 Example:
- 75 Enabling or Disabling StartUp Stick:
- 75 To enable or disable StartUp Stick:
- 76 To enable or disable coldboot alert:
- 76 To enable or disable coldboot alert:
- 76 To enable or disable the Serial Command Protocol (SCP) authentication:
- 76 To enable or disable SCP:
- 76 To set the Serial Command Protocol (SCP) authentication user:
- 76 To set SCP username:
- 76 Displaying system options:
- 76 To display system option information:
- 76 Example
- 77 Displaying the firmware version:
- 77 To display the firmware version:
- 77 Performing a warm boot:
- 77 To perform a warm boot:
- 77 Enabling or disabling the Cisco EnergyWise network:
- 77 To enable or disable EnergyWise:
- 77 Example
- 77 Setting up PDUs in the Cisco EnergyWise network:
- 77 To set the EnergyWise domain name:
- 77 Example
- 77 To set the EnergyWise port:
- 77 Example
- 77 To set the EnergyWise secret:
- 77 Example
- 78 To set a blank EnergyWise secret:
- 78 Example of a blank secret
- 78 To set the EnergyWise refresh rate:
- 78 Viewing Cisco EnergyWise network parameters:
- 78 To view EnergyWise network parameters:
- 78 Example
- 79 TCP/IP Administration
- 79 Enabling or disabling DHCP support:
- 79 To enable or disable DHCP support:
- 79 Enabling or disabling DCHP boot delay:
- 79 To enable the boot delay:
- 80 Enabling or disabling DCHP static address fallback:
- 80 To enable the static address fallback:
- 80 Setting the network acquisition method:
- 80 Setting the IP address:
- 80 To set the IP address:
- 80 Example
- 80 Setting the subnet mask:
- 80 To set the subnet mask:
- 80 Example
- 80 Setting the gateway:
- 80 To set the gateway IP address:
- 80 Example
- 81 Setting the DNS IP address:
- 81 To set the DNS IP address:
- 81 Example
- 81 Displaying network configuration information:
- 81 To display network configuration information:
- 81 Example
- 83 HTTP Administration
- 83 Enabling and disabling HTTP support:
- 83 To enable or disable HTTP support:
- 83 Changing the HTTP server port:
- 83 To change the HTTP port:
- 83 Example
- 83 Sentry Power Manager (SPM) Administration
- 83 Enabling and disabling SPM Secure Access:
- 83 To enable or disable SPM support:
- 83 Resetting the SPM Password:
- 83 To reset the SPM password:
- 84 Telnet Administration
- 84 Enabling and disabling Telnet support:
- 84 To enable or disable Telnet support:
- 84 Changing the Telnet port:
- 84 To change the Telnet socket:
- 84 Example
- 84 FTP Administration
- 84 Setting the FTP host address:
- 84 To set the FTP Host address:
- 84 Examples
- 84 Setting the FTP username:
- 84 To set the FTP username:
- 84 Example
- 84 Setting the FTP Password:
- 84 To set the FTP password:
- 84 Example
- 85 Setting the filename to be uploaded:
- 85 To set the FTP filename:
- 85 Example
- 85 Setting the directory for the file to be uploaded:
- 85 To set the FTP directory:
- 85 Example
- 85 Enabling or disabling automatic updates:
- 85 To enable or disable automatic updates:
- 85 Setting the automatic update scheduled day:
- 85 To set the automatic update day:
- 85 Example
- 85 Setting the automatic update scheduled hour:
- 85 To set the automatic update hour:
- 85 Examples
- 85 Testing the FTP upload configuration:
- 85 To test the FTP upload configuration:
- 86 Displaying FTP configuration information:
- 86 To display FTP configuration information:
- 86 Example
- 86 SNTP Administration
- 86 About Daylight Saving Time(DST)
- 87 Setting the SNTP server address:
- 87 To set the SNTP server address:
- 87 Examples
- 87 Setting the local GMT offset (hours/minutes):
- 87 To set the local GMT offset:
- 87 Examples
- 87 Displaying SNTP configuration information:
- 87 To display SNTP configuration information
- 87 Example
- 87 Enabling or disabling Daylight Saving Time (DST):
- 87 To set daylight saving time:
- 88 Configuring start day/time Daylight Saving Time (DST):
- 88 To set daylight savings start day/ time:
- 88 Examples
- 88 Displaying SNTP configuration information:
- 88 To display SNTP configuration information
- 88 Example
- 89 UPS Administration
- 89 Creating a UPS record:
- 89 To create a UPS record:
- 89 Example
- 89 Removing a UPS record:
- 89 To remove a UPS record:
- 89 Example
- 90 Changing the UPS type:
- 90 To change a UPS record:
- 90 Example
- 90 Changing the UPS host address:
- 90 To change a UPS host address:
- 90 Example
- 91 Changing the UPS SNMP port:
- 91 To change the UPS SNMP port:
- 91 Example
- 91 Changing the UPS SNMP Get community string:
- 91 To change a UPS SNMP community string record:
- 91 Example
- 92 Enabling/disabling UPS voltage polling:
- 92 To enable/ disable UPS voltage polling:
- 92 Example
- 92 Adding an infeed to a UPS:
- 92 To add an infeed to a UPS:
- 92 Example
- 92 Removing an infeed from a UPS:
- 92 To remove an infeed from a UPS:
- 92 Example
- 93 Displaying UPS configuration:
- 93 To display UPS configuration information:
- 93 Example
- 96 SSL
- 96 Enabling and Setting up SSL Support
- 96 Enabling or disabling SSL support:
- 96 To enable or disable SSL support:
- 96 Setting SSL access level:
- 96 To change the access level:
- 96 Example
- 96 Setting the SSL port:
- 96 To change the port number:
- 96 Example
- 97 Enabling or disabling custom user certificates:
- 97 To enable or disable user certificates:
- 97 Setting the custom user certificate passphrase:
- 97 To set the user certificate passphrase:
- 97 SSL Technical Specifications
- 98 SSH
- 98 Enabling and Setting up SSH Support
- 98 Enabling or disabling SSH support:
- 98 To enable or disable SSH support:
- 98 Changing the SSH server port:
- 98 To change the SSH port:
- 98 Example
- 98 Enabling or disabling SSH server authentication methods:
- 98 To enable the SSH authentication methods:
- 98 Example
- 99 SSH Technical Specifications
- 100 SNMP/Thresholds
- 100 About SNMP Versions
- 100 SNMP CLI Commands:
- 100 Enabling and Setting Up SNMP v1/v2 Support
- 100 Enabling/disabling SNMP support:
- 100 To enable SNMP v1/v2 support:
- 101 Setting the Get/Set community strings:
- 101 Set Community String:
- 101 To set the Setcomm community string:
- 101 Get Community String:
- 101 To set the Getcomm community string:
- 101 Displaying SNMP v1/v2 configuration information:
- 101 To display SNMP v1/v2 configuration information:
- 101 Example
- 102 MIB, OID and Support
- 102 Enabling and Setting up SNMP Support
- 102 Enabling/disabling SNMP support:
- 102 To enable SNMP support:
- 102 SNMPv3 Engine ID:
- 102 The local engine ID is the unique identifier for the SNMPv3 engine and is displayed for viewing.
- 102 Setting the SNMP v3 read-only (RO) username :
- 102 To set the RO username:
- 102 Setting the SNMP v3 read-only (RO) authentication type :
- 102 To set the RO authentication type:
- 103 Setting the SNMP v3 read-only (RO) authentication password:
- 103 To set the RO authentication password:
- 103 Setting the SNMP v3 read-only (RO) privacy type :
- 103 To set the RO privacy type:
- 103 Setting the SNMP v3 read-only (RO) privacy password:
- 103 To set the RO privacy password:
- 103 Setting the SNMP v3 read-write (RW) username :
- 103 Setting the SNMP v3 read-write (RW) authentication type :
- 103 To set the RW authentication type:
- 103 Setting the SNMP v3 read-write (RW) authentication password:
- 103 To set the RW authentication password:
- 103 Setting the SNMP v3 read-write (RW) privacy type :
- 103 To set the RW privacy type:
- 103 Setting the SNMP v3 read-write (RW) privacy password:
- 103 To set the RW privacy password:
- 104 Setting the SNMP v3 trap username:
- 104 Setting the error trap repeat timer:
- 104 To set the error trap repeat timer:
- 104 Example
- 104 Setting the SNMP trap format version:
- 104 To set the trap format version:
- 104 Example
- 104 Smart CDU: set snmp trapformat 3<Enter>
- 104 Setting IP Restrictions:
- 104 To set SNMP IP restrictions:
- 104 To remove SNMP IP restrictions:
- 104 Setting trap destinations:
- 104 To set the trap destination:
- 104 Examples
- 104 To reset the trap destination:
- 105 Setting the Get/Set community strings:
- 105 Setcomm:
- 105 To set the Setcomm community string:
- 105 Getcomm:
- 105 To set the Getcomm community string:
- 105 Setting the SNMP SysName:
- 105 To set the SysName object:
- 105 Setting the SNMP SysLocation:
- 105 To set the SysLocation object:
- 105 Setting the SNMP SysContact:
- 105 To set the SysContact object:
- 106 Displaying SNMP configuration information:
- 106 To display SNMP configuration information:
- 106 Example
- 106 SNMP Traps
- 107 Status trap
- 107 Infeed Status traps
- 107 Load Trap
- 108 Temp Trap
- 108 Humidity Trap
- 109 Configuring Traps
- 109 Enabling or Disabling a Status Trap:
- 109 To Enable or Disable a Status trap:
- 109 Examples
- 109 Enabling or Disabling a Load trap:
- 109 To Enable or Disable a Load trap:
- 109 Examples
- 110 Setting the Infeed Load Limit:
- 110 To set the infeed load limit:
- 110 Example
- 110 Enabling or Disabling the Temp Trap:
- 110 To Enable or Disable the Temp trap:
- 110 Example
- 110 Setting the Temperature Sensor Threshold Limits:
- 110 To set the Temperature threshold limits:
- 110 Example
- 110 Configuring Temperature Recovery Delta:
- 110 To configure the temperature recovery delta:
- 110 Example
- 111 Configuring Temperature Recovery Delta:
- 111 To configure the temperature recovery delta:
- 111 Example
- 111 Configuring Humidity Recovery Delta (Hysteresis):
- 111 To configure the humidity recovery delta:
- 111 Example
- 111 Enabling or Disabling the Humid trap:
- 111 To Enable or Disable the Humid trap:
- 111 Example
- 111 Setting the Humidity Sensor Threshold Limits:
- 111 To set the Humidity threshold limits:
- 111 Example
- 112 Displaying Trap Configuration Information:
- 112 To display trap information:
- 112 Example
- 113 LDAP
- 114 Enabling and Setting Up LDAP Support
- 114 Enabling and Disabling LDAP Support:
- 114 To enable or disable LDAP support:
- 114 Setting the LDAP host address:
- 114 To set the LDAP host address:
- 114 Examples
- 114 Changing the LDAP Server Port:
- 114 To change the LDAP server port:
- 114 Example
- 114 Enabling and Disabling LDAP Over TLS/SSL Support:
- 114 To enable or disable LDAP over TLS/SSL support:
- 115 Setting the LDAP bind type:
- 115 To set the bind type:
- 115 To set the bind password type:
- 115 Setting the Search Bind Distinguished Name (DN):
- 115 To set the search bind DN:
- 115 Example
- 115 Setting the Search Bind Distinguished Name (DN) Password:
- 115 To set the Bind Password DN:
- 115 Setting the Group Membership Attribute:
- 115 To set Group Membership Attribute:
- 115 Example
- 116 Setting the Group Membership Value Type:
- 116 To set group membership value type:
- 116 Example
- 116 Setting the user membership attribute:
- 116 To set user membership attribute:
- 116 Example
- 116 Setting the User Search Base Distinguished Name (DN):
- 116 To set the user search base DN:
- 116 Example
- 117 Setting the User Search Filter:
- 117 To set the user search filter:
- 117 Example
- 117 Setting the Authentication Order:
- 117 To set the authentication order:
- 118 Displaying LDAP Configuration Information:
- 118 To display the LDAP configuration information:
- 118 Example
- 118 Setting the DNS IP address:
- 118 To set the DNS IP address:
- 118 Example
- 119 Verifying the DNS configuration:
- 119 To verify the DNS configuration:
- 119 Example
- 119 Configuring LDAP Groups
- 119 Creating an LDAP group:
- 119 To create an LDAP group:
- 119 Example
- 119 Removing an LDAP group:
- 119 To remove an LDAP group:
- 120 Setting LDAP group access level privileges:
- 120 To set the access level privilege for an LDAP group :
- 120 Examples
- 120 Granting and removing input status viewing privileges :
- 120 To grant or remove input status viewing privileges for an LDAP group:
- 120 Example
- 120 Granting and removing access to environmental monitoring :
- 120 To grant or remove input status viewing privileges for an LDAP group:
- 120 Example
- 120 Displaying the LDAP access privilege levels:
- 120 To display LDAP group access privilege levels:
- 120 Example
- 121 Adding serial port access to an LDAP group:
- 121 To grant serial port access to an LDAP group:
- 121 Deleting serial port access for an LDAP group:
- 121 To delete serial port access for a user:
- 121 Displaying LDAP Group access:
- 121 To display LDAP Group access:
- 121 Example
- 122 LDAP Technical Specifications
- 122 LDAPS (LDAP-over-TLS/SSL) Client Specifications
- 123 TACACS+
- 123 Enabling and Setting up TACACS+ Support
- 123 Enabling and disabling TACACS+ support:
- 123 To enable or disable TACACS+ support:
- 123 Setting the TACACS+ server address:
- 123 To set the TACACS+ server address:
- 123 Examples
- 124 Setting the TACACS+ encryption key:
- 124 To set the encryption key:
- 124 Example
- 124 Changing the TACACS port:
- 124 To change the TACACS port:
- 124 Example
- 124 Setting the authentication order:
- 124 To set the authentication order:
- 125 Displaying TACACS+ configuration information:
- 125 To display the TACACS configuration information:
- 125 Example
- 125 Configuring TACACS+ Privilege Levels
- 125 Setting TACACS+ account access level privileges:
- 125 To set the access level privilege for a TACACS+ account :
- 125 Examples
- 125 Granting and removing input status viewing privileges:
- 125 To grant or remove input status viewing privileges for a TACACS+ account:
- 125 Example
- 125 Granting and removing access to environmental monitoring:
- 125 To grant or remove input status viewing privileges for a TACACS+ account:
- 125 Example
- 126 Displaying the TACACS+ access privilege levels:
- 126 To display TACACS+ account access privilege levels:
- 126 Example
- 126 Granting and removing access to environmental monitoring:
- 126 To grant or remove input status viewing privileges for a TACACS+ account:
- 126 Example
- 126 Adding serial port access to a TACACS+ account:
- 126 To grant serial port access to a TACACS+ account:
- 126 Deleting serial port access for a TACACS+ account:
- 126 To delete serial port access for a TACACS+ account:
- 126 Displaying TACACS account access:
- 126 To display TACACS account access:
- 126 Example
- 127 TACACS+ Technical Specifications
- 128 RADIUS
- 128 Enabling and Setting Up RADIUS Support
- 128 Enabling and disabling RADIUS support:
- 128 To enable or disable RADIUS support:
- 128 Setting the authentication order:
- 128 To set the authentication order:
- 129 Setting the RADIUS server address:
- 129 To set the RADIUS server address:
- 129 Examples
- 129 Setting the RADIUS secret:
- 129 To set the shared secret:
- 129 Changing the RADIUS port number:
- 129 To change the port number:
- 129 Example
- 129 Setting the RADIUS timeout value:
- 129 To set the timeout value:
- 129 Examples
- 130 Setting the number of RADIUS server retries:
- 130 To set the number of retries:
- 130 Examples
- 130 Displaying RADIUS configuration information:
- 130 To display the RADIUS configuration information:
- 130 Example
- 131 Vendor-Specific Attributes (VSA):
- 131 Examples:
- 132 Logging
- 132 Internal System Log
- 132 Viewing the internal system log:
- 132 To view the internal system log:
- 132 Example
- 133 Syslog
- 133 Setting the Syslog server IP address:
- 133 To set the Syslog server IP address:
- 133 Example
- 133 Changing the Syslog server port:
- 133 To change the Syslog port:
- 133 Example
- 133 Displaying Syslog configuration information:
- 133 To display the Syslog configuration information:
- 133 Example
- 134 Email
- 134 Enabling or disabling Email notification Support:
- 134 To enable or disable Email notification support:
- 134 Setting the SMTP server address:
- 134 To set the SMTP server address:
- 134 Examples
- 135 Changing the SMTP server port:
- 135 To change the TACACS port:
- 135 Example
- 135 Setting the SMTP authentication type:
- 135 To determine the SMTP authentication type:
- 135 Examples
- 135 Setting the ‘From’ email address:
- 135 To set the ‘From’ email address:
- 135 Example
- 135 Setting the ‘Send To’ email address:
- 135 To set the ‘Send To’ email address:
- 135 Examples
- 136 Setting the Email SMTP authentication username:
- 136 Setting the Email SMTP authentication password:
- 136 Setting the Email SMTP Use Username :
- 136 Setting the Email SMTP Use ‘From’ Address:
- 136 Enabling or disabling event notification types:
- 136 To enable or disable event notification types:
- 136 Examples
- 136 Sending a test email:
- 137 Displaying Email configuration information:
- 137 To display the Email configuration information:
- 137 Example
- 138 Upload/Download
- 138 Integrated FTP Server
- 138 Enabling and disabling the FTP server:
- 138 To enable or disable the FTP server:
- 138 FTP Configuration Files
- 139 Upload/Download Process
- 139 GETting a configuration file (Download):
- 139 PUTting a configuration file (Upload):
- 140 Reset to factory defaults from the Web interface
- 140 Reset to factory defaults from the command line
- 140 Reset to factory defaults using the reset button
- 141 Initiate an FTP upload session from the Web interface
- 141 Initiate an FTP upload session from the command line
- 142 Branch Circuit Protection
- 142 Circuit Breaker
- 143 Compact Fuse Holder
- 144 Fuse Retractor, Fuse Access Window, and Fuse Access Cover
- 144 Time-Delay Fuses – Class G
- 145 Data Connections
- 145 RS-232 port
- 145 RJ45 to DB9F serial port adapter
- 146 Regulatory Compliance
- 146 Product Safety
- 146 USA Notification
- 146 Canadian Notification
- 146 European Union Notification
- 146 Japanese Notification
- 147 Chinese Notification
- 147 Recycling
- 147 Waste Electrical and Electronic Equipment (WEEE)
- 148 Warranty
- 148 Technical Support
- 148 Return Merchandise Authorization