Lynxspring Wireless Thermostat Driver Guide

Wireless Thermostat Driver Guide

Used With VWG-APP-1020 Wireless Card

For Lynxspring® JENE PC-1000

& 6000

Series Product

(Issue Date: August 5, 2009 / ITG-VWG-AP-1020-LNX-E03)

Product Overview

The VWG-APP-1020 wireless communication card and related “WirelessStat” driver jar file have been specifically designed to be used by Niagara AX ® powered JENE controllers.

When utilized in conjunction with the VT7xxxXxxxxW series wireless thermostats they offer the integrator simple integration to the Niagara AX ® environment.

The application is targeted at retrofit applications where the addition of communicating field bus wiring within the building space is prohibitive. The JENE communication card and associated Wireless Communicating

Thermostats encourage the use of existing wiring utilized by existing electronic thermostat type controls.

Additional documentation is available on www.lynxspring.com

1

Trademarks

Niagara, Niagara AX is a registered trademark of Tridium, Inc.

LON, LonWorks and LonTalk are registered trademarks of Echelon Corporation

BACnet is a registered trademark of ASHRAE

Disclaimers

NO WARRANTY. Lynxspring, Inc. (herein after referred to as “Lynxspring”) makes no warranty as to the accuracy of or use of this technical documentation. Any use of the technical documentation or the information contained therein is solely at the risk of the user.

Documentation may include technical or other inaccuracies or typographical errors. Lynxspring reserves the right to make changes to this document without prior notice, and the reader should in all cases consult Lynxspring to determine whether any such changes have been made. The information in this publication does not represent a commitment on the part of Lynxspring.

Lynxspring shall not be liable for incidental or consequential damages resulting from the furnishing, performance, or use of this material.

This guide contains links and references to third-party websites that are not under the control of Lynxspring, and

Lynxspring is not responsible for the content of any reference material or linked websites. If you access a third party website mentioned in this guide, then you do so at your own risk. Lynxspring provides these links only as a convenience, and the inclusion of the link does not imply that Lynxspring endorses or accepts any responsibility for the content on those third-party sites.

Electronic controls are static sensitive devices. Discharge yourself properly before manipulation and installing the Lynxspring wireless gateway.

All Lynxspring wireless gateways and related wireless thermostats are to be used only as operating controls.

Whenever a control failure could lead to personal injury and/or loss of property, it becomes the responsibility of the user to add safety devices and/or alarm system to protect against such catastrophic failures.

All VT7000 series wireless thermostats and associated components have been rigorously tested to ensure reliable operation in most building applications using the latest 2.4 ZigBee technologies. Lynxspring cannot guarantee against potential network interference should additional wireless systems be deployed sharing close proximity.

Best practices covered in this manual and all related Lynxspring documents should be considered as a guide to apply Lynxspring Wireless Network devices only. The instructions included in this manual are based upon

Lynxspring in house testing and should be referred to as a guide only.

Lynxspring Inc. may not be held liable for continued reliable, or robust operation of any and all wireless based devices. Although Lynxspring has taken many precautions in assuring the robustness of the VT7000 series wireless thermostat product line and associated network access point (JENE’s with wireless option card) Please note; future application of additional wireless devices utilizing the same or similar channels and / or frequencies may degrade performance of overall system and / or reliability.

Non-approved modifications or changes made to the communication card, the wireless thermostat driver or wireless thermostats may void the FCC compliance of the wireless card and wireless thermostats.

Ferrites supplied with the power supply and VWG MUST be installed according to instructions. Failure to do so may void the FCC compliance of the wireless card and wireless thermostats.

THIS DEVICE COMPLIES WITH PART 15 OF THE FCC RULES. OPERATION IS SUBJECT TO THE

FOLLOWING TWO CONDITIONS: (1) THIS DEVICE MAY NOT CAUSE HARMFUL INTERFERENCE, AND (2)

THIS DEVICE MUST ACCEPT ANY INTERFERENCE RECEIVED, INCLUDING INTERFERENCE THAT MAY

CAUSE UNDESIRED OPERATION.

2

About Lynxspring Wireless Mesh Networks

The Lynxspring wireless card (VWG-APP-1020 ) and related wireless thermostat family (VT7xxxXxxxxW) networkable devices operate using ZigBee/IEEE 802.15.4 physical layer for communication.

General characteristics of the wireless physical communication layer are:

Uses a wireless physical layer of 2.4GHz with a data rates of 250 kbps

Yields high throughput and low latency

Automatic multiple topologies configuration: star, peer-to-peer, mesh

Fully handshake protocol for transfer reliability

Range: 30 feet / 10M typical (up to 100 feet / 30 M based on environment)

IEEE 802.15.4 along with ZigBee Networks and Application Support Layer provide:

Low cost installation deployment

Ease of implementation

Reliable data transfer

Short range operation

Very low power consumption

Appropriate levels of security

The JENE with the wireless communication card acts as network coordinator device for the IEEE

802.15.4/ZigBee network used with the Lynxspring wireless thermostats.

Many network specific features of the IEEE 802.15.4 standard are not covered in detail in this paper. However, these are necessary for the efficient operation of a ZigBee network. These features of the network physical layer include receiver energy detection, link quality indication and clear channel assessment. Both contention-based and contention-free channel access methods are supported with a maximum packet size of 128 bytes, which includes a variable payload up to 104 bytes. Also employed are 64-bit IEEE and 16-bit short addressing, supporting over 65,000 nodes per network. All those properties of the physical layer are used and employed by the Lynxspring mesh network but are hidden to the installed / user for ease of configuration and commissioning of the network database.

A “recommended” typical maximum of 30 networkable thermostats can be supported by a single JENE2.

Database creation and configuration is easily made using the Niagara AX ® environment.

The theoretical maximum of number of thermostats supported by a single JENE is dependent on the resources available for the WirelessStatNetwork driver Jar file and the extent of integration added to the station itself. When additional functions and services are added to the station, the available resources for the driver will be less. Once you have configured the station for the wireless network and all other features (graphics, services, histories, alarms, etc.), you should monitor the resources so that they do not exceed the recommended limits for each specific platform.

Wireless Card Installation

Please refer to the “ Wireless Communication Card Installation ” manual supplied with the VWG-APP-1020 communication card for detailed information on the wireless communication card installation inside a JENE controller.

Only use Com1 option slot card position for the card

3

Basic Initial Design And Deployment Consideration

Proper design considerations need to be addressed prior to any installation of a JENE with a Lynxspring wireless communication card and related wireless thermostats.

1. To properly avoid network interference with 802.11 Wi-Fi devices in the 2.4GHz spectrum range,

Lynxspring recommends the use of 802.15.4 channels 25 and 26 only. 802.11 Wi-Fi transmissions overlap and may interfere with other channel selection allowed by 802.15.4 ( Channels 11 to 24 )

2. Maximum distance between each node ( thermostat ) should be:

Clear line of sight between 2 nodes should be under 100 feet ( 30 M )

Open clear line of sight distance between

2 nodes should be a maximum of

100 feet ( 30 M )

Maximum 100 feet ( 30 M ) between 2 thermostat nodes

4

Non line of sight, typical gypsum wall partitions made with metal stud frame should be under 30 feet (10M )

Non line of sight maximum distance for typical gypsum wall partitions should be maximum of 30 feet ( 10 M ) between 2-thermostat nodes

Maximum 30 feet ( 10 M ) between 2-thermostat nodes

3. Ensure that the minimum distance between any Lynxspring node and any Wi-Fi devices ( wireless routers, wireless adapters, lap-tops using wireless networks, etc….) to be at least 3 foot ( 1 M ) and preferably 10 feet ( 3 M ) or more.

Minimum 3 feet ( 1 M ) between Wi-Fi equipment and

Lynxspring wireless d i

Preferably 10 feet ( 3 M ) or more between Wi-Fi equipment and Lynxspring wireless devices

5

4. Ensure that at least one thermostat is within 30 feet of the VWG for every cluster of 10 thermostats installed.

5. Always try to locate if possible the VWG near the center of all associated wireless thermostats.

6. Always try to locate the VWG near on in line of sigh to as many wireless thermostats as possible.

7. Try to avoid metal, brick walls or concrete obstructions between wireless devices as much as possible.

8. Make sure the antenna on the VWG is always perpendicular to the floor.

9. Avoid placing VWG and thermostats near metal or enclosed in metal boxes. If the VWG needs to be installed inside a metal cabinet, use the remote antenna accessory.

Ex. For a recommended maximum of 30 wireless thermostats total per JENE, a minimum of 3 of them should be within 30 feet ( 9 M ) of the VWG range.

30 feet ( 9 M )

At least 1 Viconics thermostat node to be within 30 feet ( 9 M ) of the

VWG for every other 10 thermostat installed v

6

JENE and Wireless Communication Card Configuration

Initial Configuration Note: The following instructions assume you are familiar with the Niagara AX ® environment and its related functions

• Install the wireless communication card as stipulated by the instructions provided with the wireless card

Copy the “WirelessStatNetwork” jar file to your local module folder

Using the Software Manager, add the “WirelessStat” jar file to the target JENE with the wireless communication card already installed

Re-boot both the local Niagara AX® interface and the JENE itself to properly load the

“WirelessStatNetwork” jar module

Using the “WirelessStat” palette tool, simply drag & drop the “WirelessStatNetwork” driver under the local driver folder of the JENE

Rename the “WirelessStatNetwork” driver extension name if required

7

• Right hand click the “WirelessStatNetwork” driver and load the property sheet

• Under the Serial Port Configuration, set Port Name to “COM1”. Only COM1 can be used with the wireless communication card. All other properties are locked and set as read only

8

• Set the ZigBee wireless communication card options.

VWG ZigBee Settings

Those settings are where you set the ZigBee PAN ID. (Personal Area Network Identification) address and the channel for the wireless communication card.

Gateway ZigBee PAN ID . (Personal Area Network Identification). This is where the PAN ID of the gateway is set. Range is from address 1 to 500. The default of “0” is not a valid PAN ID.

Channel Select. This is where the current Channel frequency used by the gateway is set. Range is from

11 to 26. (2405 MHz to 2480 MHz, 5 MHz channel spacing) Please note that channel 26 is attenuated by 4 db compared to the other channels. The default of “10” is not a valid Channel.

The communication module information and the assigned wireless address information is given for reference only

It is important to click on the “SAVE” button for the new wireless parameters to take effect and the wireless network to properly start.

IMPORTANT NOTES (Please Read Carefully ) :

For every thermostat reporting to a JENE (a maximum of 30 thermostats per JENE is recommended), be sure you set the SAME PAN ID and Channel value at both the gateway and the thermostat(s).

When properly configured, the issue of RF interference and lost data between the gateway and the thermostats can be avoided. Without proper care or proper software configuration serious interference issues can happen.

Lynxspring recommends using only the 2 last channels (25-2575MHz and 26-2580MHz) Lynxspring recommends this purely as a practical tip for deployment in the field based on our experience. These 2 upper channels are not affected and are out of the range of IEEE802.11x Wi-Fi Channels spectrum .

9

Thermostat Discovery & Database Tools

IMPORTANT NOTE (Please Read Carefully) :

The Lynxspring wireless card (VWG-APP-1020 ) and related wireless thermostat family (VT7xxxXxxxxW) networkable devices operate using ZigBee/IEEE 802.15.4 physical layer for communication.

As such this communication layer operates differently than “most” low level traditional wired communication bus.

The “heart” of the network resides on the wireless communication card found on the JENE. It is commonly referred to as the “coordinator” to the network.

As such, as soon as a valid PAN ID and Channel are given to the JENE wireless communication card, any thermostat having the same configuration of PAN ID and Channel can be detected and registered to the wireless coordinator.

A traditional “discovery” process is not necessary and a discovery button is not provided.

The “Discovered Device” folder lists the current thermostats detected by the JENE that have the same PAN ID and Channel settings as the JENE. A Yellow highlight indicates a previously discovered thermostat that has not updated is mandatory wireless heartbeat to the JENE and is now offline to the VWG.

It may take up to 2 minutes for a new thermostat device to be automatically discovered and appear under the

“Discovered Device” folder. If a properly configured thermostat (typically the ones furthest from the JENE) has issues joining the network and cannot be discovered by the JENE; bring it and power it closer to the JENE coordinator. This will get enable it to have a Zigbee address assigned by the wireless communication card of the

JENE or another thermostat device. It will then enable the JENE to discover it; once discovered, re-install it at the proper location.

Name . The thermostat’s given name in the database. The name is constructed of the thermostat model number and its current local MAC address. Ex. A VT7300C5020W with a local MAC address of 21 will carry a name in the database of VT7300C5020_21

Model Type.

The thermostat model number given name in the database. The name is constructed of the thermostat model number and its current local MAC address. Ex. A VT7300C5020W with a local MAC address of 21 will carry a name in the

Type . Identified for the moment which type of Lynxspring wireless device has been detected

Comm Address . The current physical MAC address set at each individual thermostat in its local configuration.

10

Status . Indicates if the current thermostat is online to the JENE or not. o If online, the status will be {OK} and the thermostat line will be all white o If offline, the status will be {down} and the thermostat line will be all yellow

Health . The current status of each thermostat wireless node. “OK” is for an online thermostat and the date and time represent the last time a communication event was received by the JENE from a thermostat. A

“Fail” represents a thermostat that stopped responding to its mandatory heartbeat.

Database Tools. Add / Remove Selected Thermostat

At the bottom of the “Discovered Device” folder, 3 buttons are found to manage the thermostat devices database.

New . The “New” thermostat button is a utility that allows the integrator to create offline devices prior to the installation. This allows the integrator to pre-build a database and all related utilities before the actual installation takes place. When the assigned thermostat would be automatically discovered in the field during commissioning, all required functions and bindings would already be assigned.

Select the number of device to add of the same type and the starting local MAC address each thermostat will be assigned in the field.

Then select the required thermostat model number that will be installed on the job site. Remember to select ALL thermostats if more than one is required. The thermostat can be enabled now or at a later date if the installation is done in segments.

11

Edit Type.

Allow you to edit the characteristics assigned to any specific wireless thermostat. The thermostat name, Com Address and enabled flag can be modified. The thermostat Model Type should not be changed. If another model is required under the same address, simply delete it and either create a new one offline or re-discover the proper one.

Add device to network.

Transfer any selected device from a “temporary” status under the “Discovered

Device” folder and loads them directly under the under “WirelessStatNetwork” folder. This will enable the thermostat to display all its point extensions and its property sheet when you right hand click.

Status: Will give the sanity of the wireless thermostat to the network o (ok) Device heartbeat reporting properly with no fault encountered o (down) Device heartbeat failed. No communication to the device o (fault) Transaction time out on specific object write(s). Device heartbeat is still valid o (disabled,fault) Device has been disabled

Enabled: Enables or disables the communication to the wireless thermostat. Can be used if a complete database is created for all the devices, but it is done in segments.

Health: Health status of the device. The “Last Ok Time” represents the last time the JENE received the mandatory heartbeat from the thermostat

Device Info, Address Info & Communication Module Info : Are all read only properties related to the local thermostat and are given as general information.

Signal Strength: Represents the signal strength of a particular thermostat from the last hop routing a message

(to or from the device) to the JENE. It is NOT representative of the signal quality from end to end (JENE to thermostat )

12

Thermostat Objects Supported

Please note that the wireless all objects related to any specific thermostat exchange present value to and from the JENE on a fixed COV subscription base.

Back and forth from the JENE to the wireless thermostats, the COV values are fixed to:

2.5% for PI demand Numeric objects

0.5 for all temperature ( C & F ) and humidity Numeric objects

On change for all Enum’s & Boolean’s

A single JENE can support a “recommended” maximum of 30 thermostats. The total number of thermostat supported is dependent on the resources available for the WirelessStatNetwork” driver Jar file and the extent of integration added to the JENE station itself. It is safe to assume that if more advanced functions and services added to the station, the available resources for the driver will be less. It is important that once the station is all done and installed with all GUI, services, trends, logs, etc…that resources are monitored and not above what is recommended by Lynxspring for each specific type of JENE controller.

The list of points available for each thermostat model is different and has been optimized to best suit typical applications used by every single typical thermostat model available.

It is important to mention that versus the wired BACnet MS-TP or LON models, which offer ALL possible objects supported by the thermostats (user, status and configuration objects ), the wireless versions only support the points, which are of relevance for typical BAS interaction. As such most configuration properties of the thermostats are not available through the JENE and need to be changed locally at the thermostat.

Versus other wired drivers offered with the Niagara AX® environment, the object list supported by each model of wireless thermostat is not editable and cannot be changed.

13

Objects Supported By Model

Object Name Type Object Property

RoomTemp **

OutdoorTemp **

RoomHumidity **

SupplyTemp

SupplyRH

Local Temperature and Humidity Status

Numeric Present_Value

√ √ √ √ √ √ √ √ √ √ √ √ √ √ √ √ √ √ √ √ √ √

Numeric Present_Value (R,W)

√ √ √ √ √ √ √ √ √ √ √ √ √ √ √ √ √ √ √ √ √ √

Numeric Present_Value

√ √ √ √ √ √

Numeric Present_Value (R,W)

√ √ √ √ √ √ √ √ √ √ √ √ √ √ √ √ √ √ √ √

Numeric Present_Value

√ √

OccCoolSetpoint

Setpoints

Numeric Present_Value (R,W)

√ √ √ √ √ √ √ √ √ √ √ √ √ √ √ √ √ √ √ √ √ √

OccHeatSetpoint

StandByCoolSetpoint

StandByHeatSetpoint

Numeric Present_Value (R,W)

√ √ √ √ √ √ √ √ √ √ √ √ √ √ √ √ √ √ √ √ √ √

Numeric Present_Value (R,W)

√ √ √ √ √ √ √ √ √ √ √ √

Numeric Present_Value (R,W)

√ √ √ √ √ √ √ √ √ √ √ √

UnoccCoolSetpoint

UnoccHeatSetpoint

Numeric Present_Value (R,W)

√ √ √ √ √ √ √ √ √ √ √ √ √ √ √ √ √ √ √ √ √ √

Numeric Present_Value (R,W)

√ √ √ √ √ √ √ √ √ √ √ √ √ √ √ √ √ √ √ √ √ √

DehumidRHSetpoint

HumidificationHighLimitSetpoint

Numeric Present_Value

√ √ √ √ √ √

HumidificationRHSetpoint Numeric Present_Value

√ √

EffectiveHumidificationRHSetpoint Numeric Present_Value

√ √

Numeric Present_Value

√ √

SequenceOfOperation

SystemMode

SystemModeRTU

SystemModeHPU

FanMode

KeypadLockout

DehumidLockout

Main Commands

Present_Value

√ √ √ √ √ √ √ √ √ √ √ √ √ √ √ √ √ √ √ √

Enum Present_Value (R,W)

√ √ √ √ √ √ √ √ √ √ √ √

Enum Present_Value (R,W)

√ √ √ √ √ √ √ √ √ √ √ √

Enum Present_Value

√ √ √ √ √ √ √ √

Enum Present_Value (R,W)

√ √

Enum Present_Value (R,W)

√ √ √ √ √ √ √ √ √ √ √ √ √ √ √ √ √ √ √ √

Enum Present_Value (R,W)

√ √ √ √ √ √ √ √ √ √ √ √ √ √ √ √ √ √ √ √ √ √

Boolean Present_Value

√ √ √ √

Present_Value

√ √ √ √ √ √ √ √ √

** Please note that Room Temperature, Outdoor Temperature and Room Humidity need to be set Out Of Service if you want to write to the object present value. When

Out Of Service is set to "True", the thermostat local present value will be derived from the wireless network instead of the present value at the thermostat.

14

Object Name

Type and

Instance

Object Property

PIHeatingDemand

PICoolingDemand

HumidifierOutput

DehumidStatus

EconomizerOutput

GFanStatus

W2Stratus

W1Status

Y1Status

Y2Status

ReversingValveStatus

AuxStatus

DI1Status

DI2Status

BI1Status

BI2Status

UI3Status

PIRmotionStatus

Main Status

Numeric

Numeric

Present_Value (R)

Present_Value (R)

√ √ √ √ √ √ √ √ √ √ √ √ √ √ √ √ √ √ √ √ √ √

√ √ √ √ √ √ √ √ √ √ √ √ √ √ √ √ √ √ √ √ √ √

√ √ √ √ √ √ √ √ √ √ √ √ √ √ √ √ √ √ √ √ √ √

√ √

Boolean Present_Value

√ √ √ √ √ √

(R)

√ √

√ √ √ √ √ √ √ √ √ √ √ √ √ √ √ √ √ √ √ √ √ √

Output Status

Boolean

Boolean

Boolean

Boolean

Boolean

Boolean

Boolean

Boolean

Boolean

Boolean

Boolean

Boolean

Boolean

Present_Value

√ √ √ √ √ √ √

(R)

√ √ √ √ √ √ √ √ √ √

(R)

√ √ √ √ √ √ √ √

(R)

√ √ √ √ √ √ √ √ √ √

(R)

√ √ √ √ √ √ √ √ √ √

(R)

√ √ √ √ √ √ √ √

Present_Value (R)

√ √

Present_Value (R)

√ √ √ √ √ √ √ √ √ √ √ √ √ √ √ √ √ √ √ √ √ √

(R)

√ √ √ √ √ √ √ √ √ √

(R)

√ √ √ √ √ √ √ √ √ √

Present_Value (R)

Present_Value (R)

Present_Value (R)

Present_Value (R)

√ √ √ √ √ √ √ √ √ √ √ √

√ √ √ √ √ √ √ √ √ √ √ √

√ √ √ √ √ √ √ √ √ √ √ √

√ √ √ √ √ √ √ √ √ √ √ √

** The present value of an object can only be written if identified so in the object table above.

Present_Value (R), object is read only

Present_Value (R,W), object is read / write

15

List of Property Numeric Value Range Restrictions

Minimum range

Object name Object Type

RoomTemp ** Numeric

Maximum value range value

-40.0°F (-40°C) 122.0°F (50°C)

OutdoorTemp ** Numeric -39.0°F (-40°C) 122.0°F (50°C)

RoomHumidity ** Numeric

Default value

N/A

N/A

10% 90% N/A

SupplyTemp Numeric -40.0°F (-40°C) 122.0°F (50°C) N/A

SupplyRH

OccCoolSetpoint

OccHeatSetpoint

StandByCoolSetpoint

Numeric

Numeric

Numeric

Numeric

54°F (13°C)

40°F (4.5°C)

54°F (13°C)

100°F (37°C)

90°F (32°C)

100°F (37°C)

As per Stat

As per Stat

As per Stat

StandByHeatSetpoint

UnoccCoolSetpoint

UnoccHeatSetpoint

DehumidRHSetpoint

Numeric

Numeric

Numeric

Numeric

40°F (4.5°C)

54°F (13°C)

40°F (4.5°C)

15%

90°F (32°C)

100°F (37°C)

90°F (32°C)

95%

As per Stat

As per Stat

As per Stat

As per Stat

HumidificationRHSetpoint

EffectiveHumidificationRHSetpoint

HumidificationHighLimitSetpoint

PIHeatingDemand

PICoolingDemand

HumidifierOutput Numeric

EconomizerOutput Numeric

** Room Temperature, Outdoor Temperature and Room Humidity need to be set Out Of Service if you want to write to the object present value. When Out Of Service is set to "True", the thermostat local present value will be derived from the wireless network instead of the present value at the thermostat.

List of Property Enumeration Sets for BV Objects

Object Name

Object

Type

Inactive_Text Active_Text Default value

AuxCommand Boolean

DehumidStatus Boolean

GFanStatus

W2Stratus

W1Status

Boolean

Boolean

Boolean

Numeric

Numeric

Numeric

Numeric

Numeric

10%

10%

50%

90%

90%

90%

As per Stat

As per Stat

As per Stat

Off On Off

Off On Off

Off On Off

Off On Off

Off On Off

Y1Status

Y2Status

ReversingValveStatus

AuxStatus

DI1Status

Boolean

Boolean

Boolean

Boolean

Boolean

Off On Off

Off On Off

Off On Off

Off On Off

Not Activated Activated Not Activated

DI2Status Boolean Not Activated Activated Not Activated

BI1Status Boolean

BI2Status Boolean

UI3Status * Boolean Not Activated Activated Not Activated

PIRmotionStatus Boolean Not Activated Activated Not Activated

* This object is linked to UI3 input on all VT7200 and VT7300 series thermostat when used in binary mode. The Not

Activated / Activated flag status is changed upon a local contact closing on the input and will also result in the

SupplyTemp Numeric to respond from one end of its range to the other.

16

List of Property Enumeration Sets for MV Objects

Object

Name

Object

Type

Index State Text Default value Notes

Occupancy

Command

Effective

Occupancy

Enum 2 Occupied

3 Unoccupied

1 Occupied

2 Unoccupied network command

Index 1 releases the thermostat to local occupancy schemes: PIR sensor, local schedule, etc…

4 Stand-by

Sequence of

Operation

Enum

2

3

4

Heating Only

Cooling & Reheat

Heating & Reheat

Heating Only

5 Cool/Heat4P

6 Cool/Heat4P&Reht

Index 5 & 6 are only available in 4 pipe ( VT7300 ) & 4.0 Out1Cfg (

VT7200 ) configuration.

The Sequence of Operation will also set the current system mode and restrict the usable range

Note 1

System

Mode

Enum

1 Off

2 Auto

3 Cool

4 Heat

Depends on

Sequence Of

Operation

For VT72xx & VT73xx devices, the currently selected Sequence of Operation will set the default system mode and also restrict the usable range that a local thermostat can accept Note 2

Note 1 For VT72xx & VT73xx devices, usable enumerations for the System Mode depends on Sequence of Operation selected. The Auto mode can be used only if the AutoMode configuration parameter is set to On .

Note 2 Default value of System Mode depends on the Local Sequence of Operation selected and the value of the

AutoMode configuration parameter

Sequence Of

Operation

Function Auto Mode parameter Enabled

Auto Mode parameter Disabled

5

6

Cooling/Heating 4 Pipes

Cooling/Heating 4 Pipes with Reheat

Cool

Auto

Heat

Heat

Auto

Auto

Cool

Heat

Heat

Heat

Heat

Heat

Object

Name

Object

Type

Index State Text Default value Notes

System

Mode RTU

System

Mode HPU

Fan Mode

Enum

Enum

Enum

Enum

1 Off

2 Auto

3 Cool

4 Heat

1 Off

2 Auto

3 Cool

4 Heat

5 Emergency

1 Auto

2 On

3 Low

4 Med

5 High

Depends on

Last valid thermostat value

Last valid thermostat value

Last valid thermostat value

Index 4, Stand-By is not supported by VT7600 series thermostats

Thermostats will not accept all possible indexes values.

Fan actual value is read at

FanStatus for all VT7300 & at

Gfan for all VT7600. Note 3

17

Note 3:

VT7200 do not have fan outputs and fan mode commands

VT7300 fan mode input is dependent on local Fan Configuration

• VT7600 fan mode input accepted are: Auto and On. All other modes are rejected.

Available Fan modes for the VT73xx thermostat is dependent on the local configuration of the Fan Menu parameter

Fan Menu

Configuration

Fan Modes Index Accepted Default Value

1

2

3

1 Low - 2 Med - 3 High

1 Low - 2 High

1 Low - 2 Med - 3 High - 4 Auto

High

High

High

4

5

1 Low - 2 High - 3 Auto

1 Auto -2 On

High

Auto

Object

Name

Object

Type

Index State Text Default value Notes

Fan Status Enum

1 Off

2 Low

3 Med

4 High

Last valid thermostat value

Fan Status is only used with the

VT7300 series thermostats

Keypad

Lockout

Enum

Level 0Last valid thermostat value

Index accepted for all VT7200 are: 1, 2, 5 & 6

Index accepted for all VT7300 are: 1, 2, 3, 4, 5 & 6

Index accepted for all VT7600 are: 1, 2 & 3

Index exposed for all VT7200 and

VT7300 are dependent on local thermostat configuration

Alarms

For VT7200

& VT7300

Enum

5

6

7

5=Window & Filter Alarms

6=Window & Service Alarms

7=Filter & Service Alarms

4

6

7

8

4=Clock & Frost Alarms

Index exposed for all VT7600 are dependent on local thermostat configuration

Clock alarms are only exposed on programmable VT7600 thermostats

Alarms

For VT7600

Enum

6=Filter & Frost Alarms

7=Filter & Clock Alarms

8=Filter, Frost & Alarms

10

11

12

13

14

15

16

10=Service & Frost Alarms

11=Service & Clock Alarms

12=Service, Frost & Clock Alarms

13=Filter & Service Alarms

14=Service, Filter & Frost Alarms

15=Service, Filter & Clock Alarms

16=Clock, Filter, Frost & Service Alarms

18

Integration – Global Commands

The following figure shows which typical objects from each thermostat attached to a VWG can be monitored and commanded from the front-end.

Global Command Control Level Device Level

Figure 1: Global commands from a BAS front-end to a JENE and associated thermostat

19

VT7200X Integration – Graphic User Interface (GUI) objects

The following objects should be typically used in a GUI:

Room Temperature (Numeric);

Occupied and Unoccupied Heat Setpoints (Numeric);

Occupied and Unoccupied Cool Setpoints (Numeric);

Outdoor Temperature (Numeric);

Supply Temperature (Numeric) (If available);

Occupancy Command (Enum);

System Mode (Enum);

Heating Valve Status (Enum);

Cooling Valve Status (Enum);

PI Heating Demand (Numeric)

PI Cooling Demand (Numeric)

Window Alarm (Boolean);

Filter Alarm (Boolean);

Service Alarm (Boolean);

20

VT73xxX Integration – Graphical User Interface (GUI) Objects

The following objects should be typically used in a GUI:

Room Temperature (Numeric);

Occupied and Unoccupied Heat Setpoints (Numeric);

Occupied and Unoccupied Cool Setpoints (Numeric);

Room Humidity (Numeric) (If available);

Room Humidity Setpoint (Numeric) (If available);

Outdoor Temperature (Numeric);

Supply Temperature (Numeric) (If available);

Occupancy Command (Enum);

System Mode (Enum);

Fan Mode (Enum);

Fan Status (Enum);

Heating Valve Status (Enum);

Cooling Valve Status (Enum);

PI Heating Demand (Numeric)

PI Cooling Demand (Numeric)

Window Alarm (Boolean);

Filter Alarm (Boolean);

Service Alarm (Boolean);

21

VT76xxX Integration – Graphical User Interface (GUI) Objects

The following objects should be typically used in a GUI:

Room Temperature (Numeric);

Occupied and Unoccupied Heat Setpoints (Numeric);

Occupied and Unoccupied Cool Setpoints (Numeric);

Outdoor Temperature (Numeric);

Supply Temperature (Numeric) (If available);

Occupancy Command (Enum);

Effective Occupancy (Enum);

System Mode RTU (Enum) or System Mode HPU (Enum);

G Fan (Boolean);

Y1 Cool (Boolean);

Y2 Cool (Boolean);

W1 Heat (Boolean);

W2 Heat (Boolean) or Reversing Valve (Boolean);

Economizer Output (Numeric) (if available);

Aux (Boolean);

DI 1 Status (Boolean);

DI 2 Status (Boolean);

Frost Alarm (Boolean) (if available);

Filter Alarm (Boolean) (if available);

Service Alarm (Boolean) (if available);

Fan Lock Alarm (Boolean) (if available);

(BI 38)

(AV22)

(BI 25)

(BI 26)

(BI 27)

(BI 28)

(BI 29)

(BI 24)

(MV 12)

(MV 14)

(BI 31)

(BI 32)

(BI 36)

(BI 39)

Typical GUI for a VT7605B5020B with Economizer control

(AV 45)

(AV 42)

(AV 43)

(AV 44)

(AV 45)

22

Tips and Things You Need To Know

Be sure all thermostats connected to a JENE are using the same PAN ID and Channel as the JENE wireless communication card.

Room Temperature, Outdoor Temperature and Room Humidity need to be set Out Of Service if you want to write to the objects. When Out Of Service is set to True, the local value will be derived from the BACnet network instead of the value at the thermostat.

For VT7200 and VT7300, the currently selected Sequence of Operation Enum limits the System Mode

Enum usable index. A change in the Sequence Of Operation Enum will set the active system mode and also restrict the usable range that a local thermostat can accept.

For VT7300, Fan Mode Enum. Thermostats will not accept all possible index values. VT7300 fan mode input is dependent on local Fan Configuration parameter. Fan actual current value is read at FanStatus.

Each thermostat connected to a wireless network reports to the JENE with an automatic heartbeat for the local online-offline sanity. Please refer to the health status “Last Ok Time” value for the total amount of time a single thermostat has not updated its mandatory 3 minutes heartbeat update to the JENE.

Gateway Wireless Adapter LED Status Indicators

1 x 200ms short blink

2 x 200ms short blinks

3 x 200ms short blinks

4 x 200ms short blinks

Power on

Power on and card memory initialized properly

Power on, card memory initialized properly and serial communication with VWG main board active

Power on, card memory initialized properly, serial communication with VWG main board active and wireless networks started successfully

4 x 200ms short blinks and 1 x 1500ms long blink

Power on, card memory initialized properly, serial communication with VWG main board active, wireless networks started successfully and wireless communication with thermostats active

Thermostat Wireless Adapter LED Status Indicators

1 x 200ms short blink Power on

2 x 200ms short blinks

3 x 200ms short blinks

4 x 200ms short blinks

4 x 200ms short blinks and 1 x 1500ms long blink

Power on and communicating with thermostat

Power on, communicating with thermostat and there is connectivity to wireless network

Power on, communicating with thermostat, connectivity to wireless network and VWG is communicating with Wireless thermostat

Power on, communicating with thermostat, connectivity to wireless network and VWG is communicating with Wireless thermostat. Thermostat is also added to the exposed BACnet database

System Troubleshooting Recommendations

1. If a thermostat is not detected by the JENE, verify that the LED is blinking at least 4 times. If it is only blinking twice, ensure that the PAN and Channel of the thermostat is the same as the VWG it must communicate with.

2. If there are no points associated to a specific thermostat, verify the LED pattern. If the LED is blinking 4 times then the thermostat is communicating with the gateway, but it has not been added to the network yet. Add that thermostat to the network / database using the Add to Network button.

3. When commissioning a network, it is recommended to use channels 25 and 26. Alternate these channels between floors.

4. If a particular thermostat refuses to join the network and cannot be seen by the VWG. Please move momentarily closer to the JENE until it has joined the network and it is added to the database. It can then be re-located to its original position.

23

Notes about Released Versions

Please be aware of the following potential issues regarding the Beta versions of the products during installation and commissioning.

Installing VT7000 Series Wireless ZigBee Thermostats

Description / Symptom

Receiving same refreshed messages at 2 separate devices

Problem

Duplicated wireless

ZigBee addresses

Possible Cause

Duplicated ZigBee addresses created during commissioning.

Work Around

1) Assure that PAN ID and

Channel settings are secured prior to network discovery.

2) Change PAN ID of all thermostat and associated gateway

3) Redo a wireless network discovery

Document Control

Document Name: Lynxspring Wireless Thermostat Driver Guide

Document Filename: ITG-VWG-AP-1020-LNX-E03.doc

Revision Date

00

E02

November 03, 2008

May 13, 2009

Changes

Initial release

Changed all BACnet references of object type(s) to Niagara ones

E03 August 5, 2009 Reviewed and revised for Lynxspring

24

advertisement

Key Features

  • Supports multiple communication protocols, including BACnet, LonWorks, and Modbus
  • Provides a user-friendly graphical programming interface for easy configuration and customization
  • Offers a wide range of I/O modules for flexible system expansion
  • Features built-in web server for remote access and monitoring
  • Supports multiple network topologies for enhanced system reliability
  • Compact and modular design for easy installation and maintenance
  • High-performance processor for fast and efficient operation

Related manuals

Frequently Answers and Questions

What is the purpose of the JENE PC-1000 Series?
The JENE PC-1000 Series is designed to provide a comprehensive building automation solution for controlling HVAC, lighting, security, and access control systems.
What are the key benefits of using the JENE PC-1000 Series?
The JENE PC-1000 Series offers several key benefits, including ease of use, flexibility, reliability, and cost-effectiveness.
What types of communication protocols does the JENE PC-1000 Series support?
The JENE PC-1000 Series supports a range of communication protocols, including BACnet, LonWorks, and Modbus, allowing for seamless integration with various building systems.

advertisement