LOYTEC L-IP EIA-709 Installation Instructions

Add to My manuals
4 Pages

advertisement

LOYTEC L-IP EIA-709 Installation Instructions | Manualzz
L-IP EIA-709/IP Router
Installation instructions
Instructions de montage
Instruzioni di montaggio
Montageanweisung
Instrucciones de montaje
Montagevoorschrift
Monteringsanvisning
max 50º C
RH
min 5º C
10 - 90 %
kg
11
85
0,220 kg
60
105
LOYTEC
DIN TS35
0,5 - 2,5 mm2
8
Euroclamp SH3-5.08
C
B
G
b
H
A
a
D
E
F
40
1 2 3 4 5 6
15 16 17
8
Termination
(L-Term)
EIA-709 EIA-709
Port 2 Port 1
Ethernet
Status LEDs
A GREEN flashing fast
GREEN flashing at 1 Hz
RED permanent
RED flashing fast
B GREEN flashing fast
GREEN flashing at 1 Hz
RED permanent
RED flashing fast
C GREEN
YELLOW
D
E
F
G
H
RED
Flashing at 1Hz
OFF
GREEN
GREEN flashing
GREEN
GREEN
OFF
- + 12-35 VDC
~ ~ 12-24 VAC
Connectors
Traffic on port 1
Port not commissioned
Port 1 damaged
Traffic overload on port 1
Traffic on port 2
Port not commissioned
Port 2 damaged
Traffic overload on port 2
IP port is fully functional
IP port functional but
config. is not up-to-date
IP port is non-functional
IP port not commissioned
IP port not active
Ethernet link
Ethernet traffic
Config. server enabled
Power
Normal operation
1
2
3
4
5
6
8
15
16
17
EIA-709 input EARTH GND port 2
EIA-709 input B port 2
EIA-709 input A port 2
EIA-709 input EARTH GND port 1
EIA-709 input B port 1
EIA-709 input A port 1
Ethernet 10/100 BaseT (RJ45)
Power supply input earth ground
Power supply input MINUS
Power supply input PLUS
Do not connect to GND
40 RS-232 interface (DB9 male)
Buttons
a
b
Reset
Send service pin message
DIP1 DIP2 Function
ON
ON
OFF
OFF
OFF
ON
1 2 3 4 5 6 7
ON
OFF
ON
OFF
Smart switch mode
Repeater mode
Smart switch mode/ subnet learning
Configured EIA-709 router
DIP3 Function (RS-485 version only)
ON
OFF
Bit-rate auto detection on
Bit-rate auto detection off
DIP4
DIP5
DIP6
DIP7
Must be OFF
Must be OFF
Must be OFF
Must be OFF
Node ID of router on EIA-709 Port 1
Node ID of router on EIA-709 Port 2
Virtual (Node) ID of router on EIA-852 port (Ethernet)
LOYTEC electronics GmbH
NID1
NID2
VID1
MAC address of EIA-852 Ethernet port
MAC1
810000F12A07
LIP-33ECTB
Date Code
810000F12A09
810000F12A0A
MADE IN
AUSTRIA
000AB00FFAA1
W44/2004
SER#
006101810000F12A07
Serial number of the device
Document 88069001
11/2004
Printed in Austria
Data is subject to change
LOYTEC
http://www.loytec.com
[email protected]