English Installation manual

Presence detector

compact passage 24V

Table of contents

1. Safety . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 43

2. Function and performance characteristics. . . . . . . . . . . . . . . . . . . . . . . 44

3. Fitting and connection . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 45

4. Start-up . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 48

5. Parallel circuit operation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 52

6. Test Operation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 53

7. Technical specifications . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 54

8. Warranty declaration . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 56

9. Troubleshooting . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 57

42

Thank you for purchasing an Theben HTS presence detector and putting your trust in us.

1. Safety

Familiarise yourself with the compact passage 24V before assembly and start-up by reading this operating instructions.

IMPORTANT!

The unit requires no maintenance. Opening the unit or inserting foreign bodies into it will invalidate the warranty.

Proper use

The presence detector serves exclusively for the purpose contractually agreed between the manufacturer and the user. Any other use is regarded as improper. The manufacturer is not responsible for any resulting damage.

43

GB

2. Function and performance characteristics

The presence detector compact passage 24V detects persons within a corridor. Simultaneously, its light sensor measures the brightness in the room and compares it to the pre-set brightness threshold.

The switching contact A «Light» switches on the lighting in case of presence and insufficient brightness, and off in case of absence or sufficient brightness.

● Switching contact „Light”: potential-free relay

● Adjustable brightness threshold and switch-off delay

● Suitable for fluorescent and compact energy saving lamps as wells as for halogen and incandescent lamps

● Pulse function for staircase lighting timer

● SendoPro 868-A management remote control (optionally)

The switching contact B «Presence» controls heating, ventilation and air-conditioning systems. The contact closes in case of presence, a switchon delay allows a delayed switching on. The contact can also be used for room surveillance purposes. Using reduced sensitivity, it only responds on very distinct movements.

● Switching contact „Presence“: potential-free relay

44

● Adjustable switch-on delay and switch-off delay

● Surveillance function

3. Fitting and connection

3.1 Presence detection

The ideal mounting height is 2 m - 3,5m.

The sensitivity of the detector decreases with increasing mounting height.

The detection ranges of multiple detectors should overlap in their fringe zone. Ensure the horizontal installation of the detector.

GB

M-height radial (r)

2,0m 56m² | 16,0m ± 1,5m x 3,5m tangential (t)

56m² | 16,0m ± 1,5m x 3,5m

2,5m 72m² | 18,0m ± 1,5m x 4,0m 88m² | 22,0m ± 1,5m x 4,0m

3,0m

3,5m

4,0m

90m² | 20,0m ± 1,5m x 4,5m 135m² | 30,0m ± 1,5m x 4,5m

100m² | 20,0m ± 1,5m x 5,0m 150m² | 30,0m ± 1,5m x 5,0m

100m² | 20,0m ± 2,0m x 5,0m 150m² | 30,0m ± 2,0m x 5,0m

4,5m

5,0m

6,0m

100m² | 20,0m ± 2,0m x 5,0m 150m² | 30,0m ± 2,0m x 5,0m

100m² | 20,0m ± 2,5m x 5,0m 150m² | 30,0m ± 2,5m x 5,0m

100m² | 20,0m ± 2,5m x 5,0m 150m² | 30,0m ± 2,5m x 5,0m

45

Detection range (mounting height 3,0m)

1

0

3

2

Lux

15m 12 10 8 6 4 2 0 2 4 6 8 10 12 15

0

1

2

1

2 r t

15 14 13 12 11 10 9 8 7 6 5 4 3 2 1 0 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15

Please note: because of the virtually horizontal detection of compact passage to both directions, the detection range of tangential (t) movements of persons is different to the range of radial (r) movements towards the detector.

3.2 Light measurement

The detector measures artificial light and daylight reflected directly beneath the detector (beam width approx. ± 30°). The mounting location is used as the reference for the lighting levels.

46

With indirect lighting, the artificial light at the detector’s mounting location should not exceed 2000 Lux (Brightness value > 2000 Lux).

GB

3.3 Connection

A concealed housing should be used for flush-mounted fitting of the com pact passage 24V. A surface frame is available for surface mounting.

24V =

+ compact power 24V

A1 A2 B1 B2

See the technical data

47

4. Start-up

The detectors are supplied ready for operation with a factory setting of recommended standard values. The SendoPro 868-A management remote control for starting-up the system is optionally available. With the remote control all potentiometer values can be set from a distance.

4.1 Settings for switching contact A «Light»

Potentiometer

 Brightness threshold “LUX” Scale

● Transfer zones (no working area) approx. 2

● Bright transfer zones approx. 3

● Deactivation of brightness measurement “on”

Depending on the installation location, natural light intensity, furniture, reflection characteristics of the room and the furniture it may be necessary to correct the settings by 1-2 steps on the scale.

For ease of setting up, we recommend the management remote control Sendo-

Pro 868-A.

 

48

Switch-off delay time

● Transfer zones approx. 5min.

● In the range between 2 - 15min the switch-off delay varies according to its self-learning behavior. The set values <2min or >15min remain fixed.

● «Pulse»: staircase lighting timer control (0.5sec. “on” / 10sec. “off”)

GB

DIP switch

 Light measurement: adaptive or fixed hysteresis

● auto adaptive mode.

● fix overridden by a superordinate logic, the adaptive mode can be deactivated.

auto

0-10V lin

 fix

0-10V log

49

4.2 Settings for switching output B «Presence»

 Switch-off delay time for presence

● The pre-set values remain unchanged (no self-learning effect).

 Switch-on delay time for presence

● In case of presence, the contact does not close before the set switch-on delay has elapsed.

● 0 = Contact closes immediately in case of presence.

● Room surveillance function; the contact closes only in case of distinct movements (effective protection against false alarms).

50

 

4.3 Behaviour on switching on

Whenever the sensor module is plugged onto the power module or the unit is energised, the detector goes through tree phases which are indicated by an LED.

GB

1. Start-up phase (30sec)

● LED flashes every second, both contacts are closed

(light and presence on)

● In case of absence, both contacts open after 30sec.

2. Service phase (10min)

● The “Light” contact reacts instantaneously on brightness in order to check the brightness threshold.

● If the brightness is insufficient the lighting is switched on (LED on),and if the brightness is sufficient the lighting is switched off (LED off).

3. Operation

● The detector is ready for operation (LED off).

51

5. Parallel circuit operation

● The outputs of a number of detectors can be connected in parallel circuit operation. This enables coverage of large and irregularly shaped rooms such as corridors, underground parkings e.g.

● The total permissible load does not increase.

● Presence detection and brightness measurement by all detectors together.

● The brightness threshold value and switch-off delay time must be adjusted individually for each detector.

24V =

+ compact power 24V

A1 A2 B1 B2

+ compact power 24V

A1 A2 B1 B2

See the technical data

52

6. Test Operation

The test mode serves to check the presence detection and the wiring.

6.1 Setting the test mode with DIP-Switch

● Set DIP switch to «Test».

1. Start-up phase (30sec)

● Both contacts are closed for 30sec. (LED 20s «on», 10s «off» )

2. Test mode

● In case of movement (LED on), both contacts close.

● In case of absence (LED off), both contacts open after 10sec.

● NOTE: no brightness measurement.

● The detector remains permanently in the test mode.

6.2 Setting the test mode with SendoPro 868-A

● While setting the test mode with the management remote control SendoPro 868-A, the detector jumps the start-up phase and changes directly into the test mode.

● Test mode ceases automatically after 10 minutes. The detector performs a reset (see section 4.3).

GB

53

7. Technical specifications

Sensor module

Detection range:

Recommended mounting height (Mh)

Maximum range

Mixed light control

Light measurement deactivated

Switch off delay for light

Short pulse

Switch off delay for presence

Switch on delay for presence

Room surveillance

Power module

Nominal voltage compact passage 24V horizontal 360°

Relay output A1, A2 for „light“

Type of contact potential-free micro-contact

Switching capacity: minimal

maximal

2,0 - 3,5m / max. 6m

30 x 5 m tangential,

20 x 5 m radial ca. 10 - 1500Lux

„on“

10sec. - 20min.

0.5sec. „on“/ 10sec. „off“

10sec. - 120min.

0sec. - 10min.

compact power 24V

24V AC/DC ± 20%

Relais, potential free

24V @ AC/DC ±20%

1V / 1mA *)

50W / 460VA

54

Relay output B1, B2 for „presence“

Type of contact potential-free micro-contact

Switching capacity:

Depth

Diameter

Mounting plate

Screw terminals

Size of concealed housing

(for flush-mounting)

Ambient temperature

Degree of protection

Article numbers compact passage 24V

Surface frame for compact

Management remote control SendoPro 868-A

Relay potential-free

24V @ 2Aµ, 230V~2Aµ

50 W (24 V AC/DC), 460 VA

(230 V AC), µ, min. 1 V/1 mA

40mm

48mm

70 x 70mm max. 2x 2.5mm2

Dim. 1, (NIS,PMI)

0° - 50°C

IP 20 (IP 40 installed)

201 4 090

907 0 514

907 0 675

GB

*) A load of more than 60V or 100mA on the switching contact (max. 1.5W) changes its characteristics permanently; the minimum load specification of 1V/1mA can no longer be guaranteed.

55

8. Warranty declaration

Theben HTS presence detectors are manufactured and quality-tested with the utmost care using state-of-the-art technologies. Theben HTS therefore guarantees perfect function, provided the detectors are used as intended. However, should a defect occur, Theben HTS offers the following warranty within the scope of its General Terms and Conditions of Business:

Please bear in mind the following points:

● The warranty period is 24 months, commencing from the manufacturing date.

● The warranty becomes null and void if you or third parties undertake alterations to the units.

● If the presence detector is connected to a software-controlled system, the warranty for this connection is only valid provided the stated interface specification is adhered to.

We undertake to repair or replace as quickly as possible all supplied components which have become defective or unusable as a result of demonstrably bad material, faulty design or defective workmanship up to the expiry of the warranty period.

Returns

In the event of a warranty claim please send the unit together with the delivery note and a brief description of the fault to the dealer concerned.

Industrial property rights

The concept including hardware and software of these units is protected by copyright.

56

9. Troubleshooting

Fault

Lighting does not switch on or switches off in case of presence and darkness

With persons present, the lighting is on although the brightness is sufficient

Lighting does not switch off or switches on spontaneously in case of absence

Cause

Lux value setting is too low; Lighting was switched off manually with clic; Person is outside the detection range; Detection is disturbed by obstacles;

Set switch-off delay setting is too short

Lux value setting is too high; The lighting has been switched on manually with clic recently (wait for 30 min); Detector is in test mode

Wait until the switch-off delay time has elapsed

(self-learning effect); Disturbing heat sources within the detection range (heaters, incandescent lamp/ halogen lamp, moving objects (e.g. curtains due to open windows)

Lighting keeps switching on and off during the service phase

Too much artificial light is falling on the detector, increase lux value. Set DIP switch to „fix“ or reposi tion the detector.

Error blinking (4x per second) Failure during self test;

Device not working!

-

GB

CE Declaration of Conformity

This device complies with the protection regulations of the EMC directives

2004/108/EC and of the Low Voltage directive 2006/95/EC.

57

Dimensions compact passage 24V

26,5 44

48

76

∅ 66

63

Subject to change without prior notice. Errors and omissions excepted.

58

Theben AG

Hohenbergstrasse 32, DE-72401 Haigerloch

Tel. +49 (0) 74 74 692 - 0

Fax +49 (0) 74 74 692 - 150

Hotline

Tel. +49 (0) 74 74 692 - 369

Fax +49 (0) 74 74 692 - 207 [email protected]

Switzerland

Theben HTS AG

Im Langhag 7b, CH - 8307 Effretikon

Tel. +41 (0)52 355 17 00

Fax +41 (0)52 355 17 01 www.theben-hts.ch

Die Kontaktadressen für weitere Länder finden Sie auf www.theben.de

Veuillez compulser les adresses pour des pays supplémentaires sur www.theben.de

Please find the contact addresses for additional countries on www.theben.de

Las direcciones de contacto de otros países las encontrará en www.theben.de

Gli indirizzi per ulteriori paesi sono disponibili su www.theben.de

De contactadressen voor andere landen vindt u op www.theben.de

59

GB

advertisement

Related manuals

advertisement