advertisement
▼
Scroll to page 2
of 68
Installation and Operating Instructions Compressors Mink MM 1202, 1252, 1322 AP ATEX-Version, Gas Tight Busch Produktions GmbH Schauinslandstr. 1 79689 Maulburg Germany 0870142930 / 190705 / Original instructions / Modifications reserved Table of Contents Preface Preface . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2 Product Description . . . . . . . . . . . . . . . . . . . . . . . . . 3 Use . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3 Safety Concept . . . . . . . . . . . . . . . . . . . . . . . . . . 5 Operational Options / Use of Optionally Available Equipment . . 5 Principle of Operation . . . . . . . . . . . . . . . . . . . . . . 5 Cooling . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5 Start Controls. . . . . . . . . . . . . . . . . . . . . . . . . . . 5 Safety . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5 Intended Use . . . . . . . . . . . . . . . . . . . . . . . . . . . 5 Safety Notes . . . . . . . . . . . . . . . . . . . . . . . . . . . 5 Noise Emission . . . . . . . . . . . . . . . . . . . . . . . . . . 5 Transport . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6 Transport in Packaging . . . . . . . . . . . . . . . . . . . . . . 6 Transport without Packaging . . . . . . . . . . . . . . . . . . . 6 Storage . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6 Short-term Storage . . . . . . . . . . . . . . . . . . . . . . . . 6 Conservation . . . . . . . . . . . . . . . . . . . . . . . . . . . 6 Installation and Commissioning . . . . . . . . . . . . . . . . . . 6 Installation Prerequisites . . . . . . . . . . . . . . . . . . . . . 6 Mounting Position and Space . . . . . . . . . . . . . . . . . 6 Gas Inlet . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7 Pressure Connection . . . . . . . . . . . . . . . . . . . . . . 7 Electrical Connection / Controls . . . . . . . . . . . . . . . . 7 Installation . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8 Mounting . . . . . . . . . . . . . . . . . . . . . . . . . . . 8 Checking Synchronising Gear Oil . . . . . . . . . . . . . . . 8 Connecting Electrically . . . . . . . . . . . . . . . . . . . . . 8 Connecting Lines/Pipes . . . . . . . . . . . . . . . . . . . . 9 Checking the Function of the Measurement and Safety Instrumentation . . . . . . . . . . . . . . . . . . . . . . . . . . . 9 Recording of Operational Parameters . . . . . . . . . . . . . 9 Operation Notes . . . . . . . . . . . . . . . . . . . . . . . . 10 Use . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 10 Conveying Condensable Vapours. . . . . . . . . . . . . . . 11 Maintenance . . . . . . . . . . . . . . . . . . . . . . . . . . . 12 Maintenance Schedule . . . . . . . . . . . . . . . . . . . . . 12 Monthly: . . . . . . . . . . . . . . . . . . . . . . . . . . 12 Every 3 Months: . . . . . . . . . . . . . . . . . . . . . . 12 Every 6 Months: . . . . . . . . . . . . . . . . . . . . . . 12 Every Year: . . . . . . . . . . . . . . . . . . . . . . . . . 13 Every 5000 Operating Hours, At the Latest after 2 Years: . 13 Every 10000 Operating Hours, At the Latest after 2 Years:. 13 Every 20000 Operating Hours, At the Latest after 6 Years:. 13 Functional Check of the Measurement and Safety Instrumentation . 14 Congratulations on your purchase of the Busch compressor. With watchful observation of the field’s requirements, innovation and steady development Busch delivers modern vacuum and pressure solutions worldwide. These operating instructions contain information for – – – – – – – – – product description, safety, transport, storage, installation and commissioning, maintenance, overhaul, troubleshooting and spare parts of the compressor. The ATEX-drive motor is subject to a separate instruction manual. For the purpose of these instructions, “handling” the compressor means the transport, storage, installation, commissioning, influence on operating conditions, maintenance, troubleshooting and overhaul of the compressor. Prior to handling the compressor these operating instructions shall be read and understood. If anything remains to be clarified please contact your Busch representative! Keep these operating instructions and, if applicable, other pertinent operating instructions available on site. Overhaul . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 14 Removal from Service . . . . . . . . . . . . . . . . . . . . . . . 14 Temporary Removal from Service . . . . . . . . . . . . . . . . 14 Recommissioning . . . . . . . . . . . . . . . . . . . . . . . . 14 Dismantling and Disposal . . . . . . . . . . . . . . . . . . . . 15 Troubleshooting . . . . . . . . . . . . . . . . . . . . . . . . . . 16 Spare Parts . . . . . . . . . . . . . . . . . . . . . . . . . . . . 19 EU Declaration of Conformity . . . . . . . . . . . . . . . . . . . 20 Equipment Documentation Measurement and Safety Instrumentation .21 Overview . . . . . . . . . . . . . . . . . . . . . . . . . . . . 21 Version with Resistance Thermometer, without Transmitter . 21 Version with Resistance Thermometer and Transmitter . . . . 21 Pressure Switch/Indicator . . . . . . . . . . . . . . . . . . . 22 Excerpt from Operating Instructions Resistance Thermometers and Thermocouples TR40 Pt100/B/3 . . . . . . . . . . . . . . . . . 23 Excerpt from Operating Instructions Temperature Transmitter Type TMT181-B . . . . . . . . . . . . . . . . . . . . . . . . . 45 Excerpt from Operating Instructions BA0607 Precont S10 . . . . . 55 Excerpt from operating-/assembly instructions ROTEX coupling . . 62 Excerpt from operating-/assembly instructions BoWex-ELASTIC coupling . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 63 Technical Data. . . . . . . . . . . . . . . . . . . . . . . . . . . 65 Busch – All over the World in Industry . . . . . . . . . . . . . . 68 MM 1202, 1252, 1322 AP ATEX-Version, Gas Tight 0870142930 / 190705 Preface page 2 a b c Pressure relief lines with collecting line Gas inlet Terminal box d e Nameplate, compressor Inspection port, cooling air duct f g Terminal box, temperature measurement system Oil sight glass h i j Cover Eye bolt Equipotential bonding rail k Pressure switch/indicator l Nameplate, drive motor m Connection for equipotential bonding, inlet air filter n o Inlet air filter (depending on version) Cooling air outlet p q Cooling air inlet Position of condensate drain cock (optional for version “Aqua”) r s t u v w x y Directional arrow Safety valve Gas recirculation line Gas discharge Acoustic enclosure Cylinder Rotors Non-return valve Product Description the data given on the nameplate of the compressor and on the data given on the nameplate of the drive motor. Use This requires a separate consideration of the conveyed gas/air or dust/air mixtures on the one side and the environment of the compressor on the other. On the nameplate of the compressor the classification with regard to the conveyed gas/air or dust/air mixtures is marked with an “(i)” (for “inside”), while the classification with regard to the environment is marked with an “(o)” (for “outside”). The classification of the motor always refers to the environment. The compressor is intended for – the compression of – mixtures of dry non-aggressive and non-toxic gases and/or dust according to the identification on the nameplate of the compressor (explanation see below) Conveying media with a lower or higher density than air leads to an increased thermal and/or mechanical load on the compressor and is permissible only after prior consultation with Busch. Max. allowed temperature of the inlet gas: 40 °C According to the directive 2014/34/EU (“ATEX 2014”) the compressor is made for the intended use in potentially explosive areas according to MM 1202, 1252, 1322 AP ATEX-Version, Gas Tight 0870142930 / 190705 In case Busch delivered the compressor without drive motor or a replacement motor is to be mounted or for economic reasons the compressor was equipped with a simpler motor, the following must be observed: In case the classifications of the compressor and of the drive motor are different the inferior classification is relevant. This means also that the compressor is suitable for the placement in a potentially explosive environment only if both the compressor, the coupling a n d the drive motor are approved to the required extent for use in potentially explosive areas. Product Description page 3 Depending on the version the approval is valid only together with certain standard or optional components, or is limited by the use of certain optional components, as described below and in the chapter Operational Options / Use of Optionally Available Equipment (Ú page 5). The classification on the compressor is to be read as follows (interpretations of equipment categories and zones for information only; the relevant laws, directives and standards are literally binding; for temperature classes and explosion groups see E. Brandes, W. Möller “Sicherheitstechnische Kenngrößen, Band 1: Brennbare Flüssigkeiten und Gase”, ISBN 3-89701-745-8 (or equivalent source)): The compressor is equipped with pressure relief lines between the pump stage and the gas inlet (b). The pressure relief lines and shaft seal rings safeguard that no process gases will escape into the environ-ment of the compressor. The proper function of the compressor requires ambient pressure ±200* hPa (=mbar) to be present at the gas inlet (b) at any operating point. *unless specified otherwise on the nameplate of the compressor The pressure switch/indicator (k) (for version with temperature monitoring in standard scope of delivery, for version without temperature monitoring optional) is to be integrated into the system control such that the maintenance of the permitted pressure range will be monitored. If the pressure gets outside this range the system control must automatically shut down the compressor. Standard-version: The gas shall be free from vapours that would condensate under the temperature and pressure conditions inside the compressor. = Execution according to directive 2014/34/EU inside = in this line classification for explosive atmosphere inside the compressor II 2G IIB3 TX = in the process gas explosive atmosphere consisting of a mixture with air of flammable substances in the form of gas likely to occur in normal operation occasionally; if the process gas contains dust, also if the dust is not combustible, the use of a special ATEX-inlet air filter (with equipotential bonding) is required; temperature monitoring is required (resistance thermometer and temperature-transmitter in standard scope of delivery); II 3G IIB3 TX = in the process gas explosive atmosphere consisting of a mixture with air of flammable substances in the form of gas not likely to occur in normal operation but, if it does occur, will persist for a short period only; if the process gas contains dust, also if the dust is not combustible, the use of a special ATEX-inlet air filter (with equipotential bonding) is required; temperature monitoring is required (resistance thermometer and temperature-transmitter in standard scope of delivery); II 3D TX °C = in the process gas explosive atmosphere in the form of a cloud of combustible dust in air not likely to occur in normal operation but, if it does occur, will persist for a short period only; the use of the special ATEX-inlet air filter (with equipotential bonding) is required; outside = in this line classification for explosive atmosphere in the environment of the compressor II 2G IIB3 TX = in the environment explosive atmosphere consisting of a mixture with air of flammable substances in the form of gas, vapour or mist likely to occur in normal operation occasionally; temperature monitoring is required (resistance thermometer and temperature-transmitter in standard scope of delivery); sufficiently qualified ATEX-drive motor is required; II 3G IIB3 TX °C = in the environment explosive atmosphere consisting of a mixture with air of flammable substances in the form of gas, vapour or mist not likely to occur in normal operation but, if it does occur, will persist for a short period only; temperature monitoring is required (resistance thermometer and temperaturetransmitter in standard scope of delivery); sufficiently qualified ATEX-drive motor is required Version “Aqua”: The compressor features the corrosion protection coating CPC and is capable of conveying water vapour (Ú page 11: Conveying Condensable Vapours). Conveyance of other vapours shall be agreed upon with Busch. Conveyance of water or other liquids in liquid phase increases the power consumption and shall therefore be avoided (risk of drive overload). The compressor is thermally suitable for continuous operation (100 percent duty). Max. permissible number of startings per hour: 12 The maximum allowed pressure on the pressure connection (u) is 0.7 ... 2.0 barg (the nameplate of the compressor indicates the valid pressure). By means of process control it must be made sure that the maximum allowed pressure will not be exceeded. The safety valve (s) on the compressor protects the compressor against overload only. It is n o pressure limiting device in terms of EN 1012-1 for the pressure system. It is not designed for frequent use and must therefore not be used as a system pressure regulating valve. Note: The safety valve (s) routes compressed product gas back to the gas inlet (b). This will increase the gas inlet temperature. In case of continuous operation of the safety valve the temperature monitoring will therefore shut down the compressor. The compressor is not absolutely gas tight. In case of conveying air in new conditions of the compressor the leakage rate amounts to 1.5 hPa l/s (=mbar l/s) at 2 barg. Due to illegal pressures at the gas connections, worn shaft seal rings or clogged pressure relief lines this leakage rate can rise considerably. Make sure that the installation space or location is vented such that in case of conveying media which are dangerous to health no impermissible accumulation of conveyed media in the environment of the compressor will occur. The installation space or location must be vented sufficiently. The approval for use in potentially explosive atmospheres is valid for the compressor together with the described measurement and safety equipment. The approval is void if the system is altered or if the scheduled maintenance is not complied with. Maintenance must be performed by specifically instructed personnel only. II 2D TX °C = in the environment explosive atmosphere in the form of a cloud of combustible dust in air likely to occur in normal operation occasionally; temperature monitoring is required (resistance thermometer and temperature-transmitter in standard scope of delivery); sufficiently qualified ATEX-drive motor is required; II 3D TX °C = in the environment explosive atmosphere in the form of a cloud of combustible dust in air not likely to occur in normal operation but, if it does occur, will persist for a short period only; temperature monitoring is required (resistance thermometer and temperature-transmitter in standard scope of delivery); sufficiently qualified ATEX-drive motor is required MM 1202, 1252, 1322 AP ATEX-Version, Gas Tight 0870142930 / 190705 Product Description page 4 Safety Concept Start Controls Version with temperature monitoring: The compressor comes without start controls. The control of the compressor is to be provided in the course of installation. The safety concept is based on the prevention of excessive temperatures by means of a gas temperature sensor in the vicinity of the stage gas outlet (=zone of highest temperature) together with various other measures to prevent sparks. The temperature sensor must be integrated into the system control such that operation of the compressor will safely be inhibited if the shutdown temperature (see nameplate) is exceeded. Version with pressure monitoring (k) at the gas inlet (for version with temperature monitoring in standard scope of delivery, for version without temperature monitoring optional): In order to ensure the gas tightness the pressure at the gas inlet is monitored. The pressure switch/indicator (k) (in standard scope of delivery) must be integrated into the system control such that the compressor will be switched off if the pressure gets outside the range from -200 mbarg* to +200 mbarg. *unless specified otherwise on the nameplate of the compressor Operational Options / Use of Optionally Available Equipment Operation with varying speed, i.e. with a frequency inverter is permitted, provided that the drive motor is approved for frequency inverter operation and the allowed speed range is given on the nameplate of the compressor. Safety Intended Use Definition: For the purpose of these instructions, “handling” the compressor means the transport, storage, installation, commissioning, influence on operating conditions, maintenance, troubleshooting and overhaul of the compressor. The compressor is intended for industrial use. It shall be handled only by qualified personnel. The allowed media and operational limits (Ú page 3: Product Description) and the installation prerequisites (Ú page 6: Installation Prerequisites) of the compressor shall be observed both by the manufacturer of the machinery into which the compressor is to be incorporated and by the operator. In particular the intended use in potentially explosive areas, i.e. either inside the compressor or in its adjacency potentially explosive atmosphere can occur, requires that the compressor is equipped accordingly and carries the Ex-mark and that the associated documentation acc. to the directive 2014/34/EU is available. The maintenance instructions shall be observed. The system control must be designed such that no speed outside the permissible range can be set. Prior to handling the compressor these installation and operating instructions shall be read and understood. If anything remains to be clarified please contact your Busch representative! For the version “Aqua” it can be necessary to dry the compressor after process end by means of conveying ambient air (Ú page 11: Conveying Condensable Vapours). Safety Notes Aspiration of ambient air from a zone 2 (potentially explosive gas atmospheres) is permitted only if the compressor is approved for the conveyance of these gases. An ATEX-air filter (with equipotential bonding) must be installed upstream the ambient air valve. Aspiration of ambient air from areas not classified as potentially explosive is permitted. It is recommended to install an air filter upstream the ambient air valve. Principle of Operation The compressor has been designed and manufactured according to state-of-the-art methods. Nevertheless, residual risks may remain. These operating instructions highlight potential hazards where appropriate. Safety notes are tagged with one of the keywords DANGER, WARNING and CAUTION as follows: DANGER_a Disregard of this safety note will always lead to accidents with fatal or serious injuries. The compressor works on the claw principle. The components are dimensioned such, that on the one hand there is never contact between the two claws or between a claw and the cylinder, on the other hand the gaps are small enough to keep the clearance loss between the chambers low. In order to avoid the suction of dust, the compressor is equipped with an air filter (n) on the gas inlet. In order to avoid the suction of solids, the compressor is equipped with a screen in the gas inlet. In order to avoid reverse rotation after switching off, the compressor is equipped with a non-return valve (y). The compressor compresses the inlet gas absolutely oil-free. A lubrication of the pump chamber is neither necessary nor allowed. Cooling The compressor is cooled by – – – – WARNING_a Disregard of this safety note may lead to accidents with fatal or serious injuries. CAUTION_a Disregard of this safety note may lead to accidents with minor injuries or property damage. Noise Emission For the sound pressure level in free field according to EN ISO 2151 Ú page 65: Technical Data. CAUTION_a4 radiation of heat from the surface of the compressor the air flow from the fan wheel of the drive motor the process gas the air flow from the fan wheel on the shaft of the compressor MM 1202, 1252, 1322 AP ATEX-Version, Gas Tight 0870142930 / 190705 The compressor emits noise of high intensity in a narrow band. Risk of damage to the hearing. Persons staying in the vicinity of a non noise insulated compressor over extended periods shall wear ear protection. Safety page 5 Transport Transport in Packaging Packed on a pallet the compressor is to be transported with a forklift. Transport without Packaging In case the compressor is packed in a cardboard box with inflated cushions: ◆ Remove the inflated cushions from the box In case the compressor is in a cardboard box cushioned with rolled corrugated cardboard: ◆ Remove the corrugated cardboard from the box In case the compressor is laid in foam: ◆ Remove the foam In case the compressor is bolted to a pallet or a base plate: ◆ Remove the bolting between the compressor and the pallet/base plate In case the compressor is fastened to the pallet by means of tightening straps: ◆ Remove the tightening straps CAUTION_af Do not walk, stand or work under suspended loads. Note: VCI stands for “volatile corrosion inhibitor”. VCI-products (film, paper, cardboard, foam) evaporate a substance that condenses in molecular thickness on the packed good and by its electro-chemical properties effectively suppresses corrosion on metallic surfaces. However, VCI-products may attack the surfaces of plastics and elastomers. Seek advice from your local packaging dealer! Busch uses CORTEC VCI 126 R film for the overseas packaging of large equipment. ● Wrap the compressor in VCI film ● Store the compressor – – – – – if possible in original packing, indoors, dry, dust free and vibration free. For commissioning after conservation: ● Make sure that all remains of adhesive tape are removed from the ports ● Commission the compressor as described in the chapter Installation and Commissioning (Ú page 6) Installation and Commissioning Installation Prerequisites ● Make sure that the eyebolts are in faultless condition (replace damaged, e.g. bent eyebolts with a new ones) CAUTION_a ● Make sure that the eyebolts are fully screwed in and tightened by hand In case of non-compliance with the installation prerequisites, particularly in case of insufficient cooling: ● Attach lifting gear securely to the eyebolts on the synchronising gear (i, 615) and on the drive motor Risk of damage or destruction of the compressor and adjoining plant components! In case the drive motor comes without an eyebolt or the eyebolt on the drive motor is located at an unfavourable position: Risk of injury! ◆ Loop a belt/rope with suitable length and strength around the flange of the drive motor ● Attach the lifting gear to a crane hook with safety latch ● Lift the compressor with a crane In case the compressor was bolted to a pallet or a base plate: ◆ Remove the stud bolts from the rubber feet Storage Short-term Storage The installation prerequisites must be complied with. ● Make sure that the integration of the compressor is carried out such that the essential safety requirements of the Machine Directive 2006/42/EC are complied with (in the responsibility of the de-signer of the machinery into which the compressor is to be incorporated; Ú page 20: note in the EU Declaration of Conformity) Mounting Position and Space ● Make sure that the following ambient conditions will be complied with: ● Make sure that the gas inlet and the pressure connection are closed (leave the provided plugs in) – dry and free from corrosion-promoting gases, vapours, mists and dusts ● Store the compressor – – – ambient temperature: 0 ... 40 °C – – – – – if possible in original packaging, indoors, dry, dust free and vibration free Conservation ambient pressure: atmospheric altitude of location: up to 1000 m above sea level ● Make sure that the environmental conditions comply with the protection class of the drive motor (according to the nameplate) ● Make sure that the compressor can neither inadvertently nor intentionally be stepped on and cannot be used as a support for heavy objects ● Make sure that the compressor cannot be hit by falling objects In case of adverse ambient conditions (e.g. aggressive atmosphere, frequent temperature changes) conserve the compressor immediately. In case of favourable ambient conditions conserve the compressor if a storage of more than 3 months is scheduled. ● Make sure that the compressor will be placed or mounted horizontally ● Make sure that all ports are firmly closed; seal all ports that are not sealed with PTFE-tape, gaskets or o-rings with adhesive tape ● Make sure that in order to warrant a sufficient cooling there will be a clearance of minimum 1 m between the compressor and nearby walls MM 1202, 1252, 1322 AP ATEX-Version, Gas Tight 0870142930 / 190705 ● Make sure that the base for placement / mounting base is even Transport page 6 ● Make sure that no heat sensitive parts (plastics, wood, cardboard, paper, electronics) will touch the surface of the compressor ● Make sure that the installation space or location is vented such that a sufficient cooling of the compressor is warranted CAUTION_ad The compressor is not absolutely gas tight. Risk of damage to health! Make sure that the installation space or location is vented such that in case of conveying media which are dangerous to health no impermissible accumulation of conveyed media in the environment of the compressor will occur. ● Make sure that the installation space or location is vented such that even in the case of an impaired gas tightness of the compressor (e.g. due to illegal pressures at the gas inlet, worn shaft seal rings or clogged pressure relief lines) no impermissible accumulation of process gas in the environment of the compressor will occur. Closed cooling air circuits are not permitted. CAUTION_ac During operation the surface of the compressor may reach temperatures of more than 70 °C. Risk of burns! ● Make sure that the compressor will not be touched inadvertently during operation, provide a guard if appropriate ● Make sure that the sight glass (g) of the synchronising gear will remain accessible Gas Inlet CAUTION_a Version “Aqua”, if very humid process gases and/or adverse operating cycles bear the risk, that condensates remain in the compressor: ◆ Provide a shut-off valve, a drip-leg and a drain cock in the suction line, so that condensates can be drained from the suction line ◆ Make sure that the anti-pulsation chamber is equipped with a condensate drain cock (q) (optional; if the condensate drain cock is missing contact the Busch service) ● Make sure that the suction line does not contain foreign objects, e.g. welding scales Pressure Connection ● Make sure that the pressure line fits to the pressure connection (u) of the compressor ● Make sure that the pressure line is designed for 2.0 barg and 250 °C Version for the conveyance of explosive atmospheres consisting of a mixture with air of flammable substances in the form of gas: ◆ Make sure that the pipe is made from electrically conductive material and equipped with an equipotential bonding connection (execution according to EN 60079-14 or equivalent national or local regulations) ● Make sure that the pipe will cause no stress on the compressor’s connection, if necessary use an expansion joint ● Make sure that the line size of the pressure line over the entire length is at least as large as the pressure connection (u) of the compressor In case the length of the pressure line exceeds 2 m it is prudent to use larger line sizes in order to avoid a loss of efficiency and an overload of the compressor. Seek advice from your Busch representative! ● Make sure that the pressure line either slopes away from the compressor or provide a liquid separator or a drip leg with a drain cock, so that no liquids can back up into the compressor Electrical Connection / Controls Version with ATEX-drive motor: Intruding foreign objects or liquids can destroy the compressor. In case the inlet gas can contain dust or other foreign solid particles: ◆ Make sure that a suitable filter (5 micron or less) is installed upstream the compressor (included in scope of delivery) ◆ Make sure that the filter is sufficiently ATEX-qualified (electrically conductive, with equipotential bonding etc.; also for non-combustible dusts!) ● Make sure that the suction line fits to the gas inlet (b) of the compressor Version for the conveyance of explosive atmospheres consisting of a mixture with air of flammable substances in the form of gas: ◆ Make sure that the pipe is made from electrically conductive material and equipped with an equipotential bonding connection (execution according to EN 60079-14 or equivalent national or local regulations) Version for the conveyance of explosive atmospheres in the form of a cloud of combustible dust in air: ◆ Make sure that the pipe is made from electrically conductive material and equipped with an equipotential bonding connection (execution according to EN 61241-14 or equivalent national or local regulations) ● Make sure that the pipe will cause no stress on the compressor’s connection, if necessary use an expansion joint ● Make sure that ambient pressure ±200* hPa (=mbar) will be present at the gas inlet (b) at any operating point *unless specified otherwise on the nameplate of the compressor MM 1202, 1252, 1322 AP ATEX-Version, Gas Tight 0870142930 / 190705 ◆ Make sure that installation instructions for the ATEX-drive motor (separate leaflet) are available ◆ Observe the instructions given in the installation instructions manual for the ATEX-drive motor ● Make sure that the stipulations acc. to the EMC-Directive 2004/108/EC and Low-Voltage-Directive 2006/95/EC as well as the EN-standards, electrical and occupational safety directives and the local or national regulations, respectively, are complied with (this is the responsibility of the designer of the machinery into which the compressor is to be incorporated; Ú page 20: note in the EU Declaration of Conformity). ● Make sure that the power supply for the drive motor is compatible with the data on the nameplate of the drive motor ● Make sure that an overload protection according to EN 60204-1 is provided for the drive motor ● Make sure that the drive of the compressor will not be affected by electric or electromagnetic disturbance from the mains; if necessary seek advice from the Busch service In case of mobile installation: ◆ Provide the electrical connection with grommets that serve as strain-relief Version with temperature monitoring: ◆ Execute the interface for the temperature measurement system in the system control according to the safety concept (Ú page 5: Safety Concept) and according to the instructions of the manufacturer (Ú page 21: Equipment Documentation Measurement and Safety Instrumentation); applicable shutdown temperature Ú nameplate of the compressor) Installation and Commissioning page 7 Version with pressure monitoring (k) at the gas inlet (for version with temperature monitoring in standard scope of delivery, for version without temperature monitoring optional): Delta connection (low voltage): ◆ Execute the interface for the pressure switch/indicator (k) in the system control according to the safety concept (Ú page 5: Safety Concept) and according to the instructions of the manufacturer (Ú page 21: Equipment Documentation Measurement and Safety Instrumentation) ● Make sure that an earth point is available for connection to the equipotential bonding rail or the ATEX-inlet air filter resp. Electrical circuits in zone 1 (outside) shall be executed intrinsically safe in protection class ib acc. to EN 60079-11. All signal lines shall be executed with shielded cables according to EN 60079-14 or EN 61241-14 or the equivalent national or local regulations. Star connection (high voltage): Installation Mounting ● Make sure that the installation prerequisites (Ú page 6) are complied with ● Set down or mount the compressor at its location Checking Synchronising Gear Oil The compressor is delivered with oil filled synchronising gear. Double star connection, multi-voltage motor (low voltage): The level shall be slightly above the middle of the sight glass (g). ● Check on the sight glass (g) that the proper amount of oil is filled Connecting Electrically WARNING_ab Risk of electrical shock, risk of damage to equipment. Electrical installation work must only be executed by qualified personnel that knows and observes the following regulations: - IEC 364 or CENELEC HD 384 or DIN VDE 0100, respectively, - IEC-Report 664 or DIN VDE 0110, - BGV A2 (VBG 4) or corresponding national accident prevention regulation. Star connection, multi-voltage motor (high voltage): Version with ATEX-driver motor: ◆ Connect the drive motor according to the installation instructions for the drive motor (separate leaflet) Version with non-ATEX-drive motor: ◆ Connect the drive motor according to the installation instructions given below CAUTION_ad Operation in the wrong direction of rotation can destroy the compressor in short time. CAUTION_a Risk of explosion! The connection schemes given below are typical. Depending on the specific order or for certain markets deviating connection schemes may apply. Prior to starting-up it must be made sure that the compressor is operated in the proper direction (clockwise rotating field). Risk of damage to the drive motor! ● Determine the intended direction of rotation with the arrow (r) (stuck on or cast) The inside of the terminal box shall be checked for drive motor connection instructions/schemes. ● “Bump” the drive motor ● Electrically connect the drive motor ● Watch the fan wheel of the drive motor and determine the direction of rotation just before the fan wheel stops ● Connect the protective earth conductor If the rotation must be changed: ◆ Switch any two of the drive motor wires MM 1202, 1252, 1322 AP ATEX-Version, Gas Tight 0870142930 / 190705 Installation and Commissioning page 8 WARNING_ad The proper integration of measurement and safety equipment into the system control is decisive for the explosion safety of the compressor. ● Connect the variable ohmic resistance with 3 identical cables to the pins 1, 2 and 3 of the temperature transmitter as shown in the sketch (the cable connected to pin 2 compensates the cable resistance) Risk of explosion! The compressor may be operated in areas with potentially explosive atmosphere only with completely installed and checked measurement and safety equipment. Version with temperature monitoring: ◆ Connect the temperature measurement system (part of standard scope of delivery) to the system control Version with pressure monitoring (k) at the gas inlet (for version with temperature monitoring in standard scope of delivery, for version without temperature monitoring optional): ◆ Connect the pressure switch/indicator to the system control Version with equipotential bonding rail: ◆ Connect the equipotential bonding rail to the earth point with an earth cable Version with ATEX-inlet air filter, without equipotential bonding rail: ◆ Connect the housing of the ATEX-inlet air filter to the earth point with an earth cable Connecting Lines/Pipes ● Switch on the compressor ● Increase the ohmic resistance to the resistance at shutdown temperature according to the Equipment Documentation Measurement and Safety Instrumentation (Ú page 21) ● Make sure that an alarm is released in the system control and the compressor is shut down automatically ● Decrease the ohmic resistance to a value less than the shutdown point ● Make sure that the alarm persists ● Make sure that the compressor does not start self-acting ● Switch on the compressor again ● Interrupt the ohmic resistance ● Connect the suction line ● Make sure that a fault indication is released in the system control and the compressor is shut down automatically ● Connect the pressure line ● Reconnect the variable ohmic resistance Version with equipotential bonding rail: ● Switch on the compressor again ◆ Connect the equipotential bonding connectors of the pipes to the equipotential bonding rail Version with ATEX-inlet air filter, without equipotential bonding rail: ◆ Connect the equipotential bonding connector of the suction line to the earth point ● Make sure that all provided covers, guards, hoods etc. are mounted ● Make sure that cooling air inlets and outlets are not covered or obstructed and that the cooling air flow is not affected adversely in any other way ● Short circuit the variable ohmic resistance ● Make sure that a fault indication is released in the system control and the compressor is shut down automatically ● Remove the short circuit ● Remove the variable ohmic resistance ● Reconnect the resistance thermometer Pt100 to the temperature transmitter (white cable to pin 1, first red cable to pin 2, second red cable to pin 3, Ú sketch) Checking the Function of the Measurement and Safety Instrumentation (version with temperature monitoring only) WARNING_ab Risk of electrical shock, risk of damage to equipment. Electrical installation work must only be executed by qualified personnel that knows and observes the following regulations: - IEC 364 or CENELEC HD 384 or DIN VDE 0100, respectively, - IEC-Report 664 or DIN VDE 0110, - BGV A2 (VBG 4) or corresponding national accident prevention regulation. ● Firmly close the temperature measurement system (f) with the lid Recording of Operational Parameters As soon as the compressor is operated under normal operating conditions: ● Measure the drive motor current and record it as reference for future maintenance and troubleshooting work ● Make sure that the compressor aspirates inert gases and that there are no potentially explosive atmospheres in the environment ● Open the lid of the temperature measurement system (f) ● Disconnect the white cable from pin 1, the first red cable from pin 2 and the second red cable from pin 3 ● In order to simulate the resistance thermometer Pt100 set a variable ohmic resistance to approx. 100 Ω MM 1202, 1252, 1322 AP ATEX-Version, Gas Tight 0870142930 / 190705 Installation and Commissioning page 9 Operation Notes Use WARNING_ad The compressor is designed for operation under the conditions described below. In case of disregard risk of explosion! The compressor must only be operated under the conditions described below. WARNING_ad Operating a faulty compressor puts the explosion safety at risk. Risk of explosion! The compressor must only be operated in faultless condition. A faulty compressor must immediately be removed from service. The compressor is intended for – the compression of – mixtures of dry non-aggressive and non-toxic gases and/or dust according to the identification on the nameplate of the compressor (explanation see below) Conveying media with a lower or higher density than air leads to an increased thermal and/or mechanical load on the compressor and is permissible only after prior consultation with Busch. Max. allowed temperature of the inlet gas: 40 °C According to the directive 2014/34/EU (“ATEX 2014”) the compressor is made for the intended use in potentially explosive areas according to the data given on the nameplate of the compressor and on the data given on the nameplate of the drive motor. This requires a separate consideration of the conveyed gas/air or dust/air mixtures on the one side and the environment of the compressor on the other. On the nameplate of the compressor the classification with regard to the conveyed gas/air or dust/air mixtures is marked with an “(i)” (for “inside”), while the classification with regard to the environment is marked with an “(o)” (for “outside”). The classification of the motor always refers to the environment. In case Busch delivered the compressor without drive motor or a replacement motor is to be mounted or for economic reasons the compressor was equipped with a simpler motor, the following must be observed: In case the classifications of the compressor and of the drive motor are different the inferior classification is relevant. This means also that the compressor is suitable for the placement in a potentially explosive environment only if both the compressor, the coupling a n d the drive motor are approved to the required extent for use in potentially explosive areas. Depending on the version the approval is valid only together with certain standard or optional components, or is limited by the use of certain optional components, as described below and in the chapter Operational Options / Use of Optionally Available Equipment (Ú page 5). The classification on the compressor is to be read as follows (interpretations of equipment categories and zones for information only; the relevant laws, directives and standards are literally binding; for temperature classes and explosion groups see E. Brandes, W. Möller “Sicherheitstechnische Kenngrößen, Band 1: Brennbare Flüssigkeiten und Gase”, ISBN 3-89701-745-8 (or equivalent source)): MM 1202, 1252, 1322 AP ATEX-Version, Gas Tight 0870142930 / 190705 = Execution according to directive 2014/34/EU inside = in this line classification for explosive atmosphere inside the compressor II 2G IIB3 TX = in the process gas explosive atmosphere consisting of a mixture with air of flammable substances in the form of gas likely to occur in normal operation occasionally; if the process gas contains dust, also if the dust is not combustible, the use of a special ATEX-inlet air filter (with equipotential bonding) is required; temperature monitoring is required (resistance thermometer and temperature-transmitter in standard scope of delivery); II 3G IIB3 TX = in the process gas explosive atmosphere consisting of a mixture with air of flammable substances in the form of gas not likely to occur in normal operation but, if it does occur, will persist for a short period only; if the process gas contains dust, also if the dust is not combustible, the use of a special ATEX-inlet air filter (with equipotential bonding) is required; temperature monitoring is required (resistance thermometer and temperature-transmitter in standard scope of delivery); II 3D TX °C = in the process gas explosive atmosphere in the form of a cloud of combustible dust in air not likely to occur in normal operation but, if it does occur, will persist for a short period only; the use of the special ATEX-inlet air filter (with equipotential bonding) is required; outside = in this line classification for explosive atmosphere in the environment of the compressor II 2G IIB3 TX = in the environment explosive atmosphere consisting of a mixture with air of flammable substances in the form of gas, vapour or mist likely to occur in normal operation occasionally; temperature monitoring is required (resistance thermometer and temperature-transmitter in standard scope of delivery); sufficiently qualified ATEX-drive motor is required; II 3G IIB3 TX °C = in the environment explosive atmosphere consisting of a mixture with air of flammable substances in the form of gas, vapour or mist not likely to occur in normal operation but, if it does occur, will persist for a short period only; temperature monitoring is required (resistance thermometer and temperaturetransmitter in standard scope of delivery); sufficiently qualified ATEX-drive motor is required II 2D TX °C = in the environment explosive atmosphere in the form of a cloud of combustible dust in air likely to occur in normal operation occasionally; temperature monitoring is required (resistance thermometer and temperature-transmitter in standard scope of delivery); sufficiently qualified ATEX-drive motor is required; II 3D TX °C = in the environment explosive atmosphere in the form of a cloud of combustible dust in air not likely to occur in normal operation but, if it does occur, will persist for a short period only; temperature monitoring is required (resistance thermometer and temperature-transmitter in standard scope of delivery); sufficiently qualified ATEX-drive motor is required The compressor is equipped with pressure relief lines between the pump stage and the gas inlet (b). The pressure relief lines and shaft seal rings safeguard that no process gases will escape into the environ-ment of the compressor. The proper function of the compressor requires ambient pressure ±200* hPa (=mbar) to be present at the gas inlet (b) at any operating point. *unless specified otherwise on the nameplate of the compressor The pressure switch/indicator (k) (for version with temperature monitoring in standard scope of delivery, for version without temperature monitoring optional) is to be integrated into the system control such that the maintenance of the permitted pressure range will be monitored. If the pressure gets outside this range the system control must automatically shut down the compressor. Installation and Commissioning page 10 Standard-version: The gas shall be free from vapours that would condensate under the temperature and pressure conditions inside the compressor. Version “Aqua”: The compressor features the corrosion protection coating CPC and is capable of conveying water vapour (Ú page 11: Conveying Condensable Vapours). Conveyance of other vapours shall be agreed upon with Busch. Conveyance of water or other liquids in liquid phase increases the power consumption and shall therefore be avoided (risk of drive overload). The compressor is thermally suitable for continuous operation (100 percent duty). ● Make sure that all provided covers, guards, hoods etc. remain mounted ● Make sure that protective devices will not be disabled ● Make sure that cooling air inlets and outlets will not be covered or obstructed and that the cooling air flow will not be affected adversely in any other way ● Make sure that the installation prerequisites (Ú page 6: Installation Prerequisites) are complied with and will remain complied with, particularly that a sufficient cooling will be ensured Conveying Condensable Vapours Version “Aqua”: Max. permissible number of startings per hour: 12 The maximum allowed pressure on the pressure connection (u) is 0.7 ... 2.0 barg (the nameplate of the compressor indicates the valid pressure). By means of process control it must be made sure that the maximum allowed pressure will not be exceeded. The safety valve (s) on the compressor protects the compressor against overload only. It is no pressure limiting device in terms of EN 1012-1 for the pressure system. It is not designed for frequent use and must therefore not be used as a system pressure regulating valve. Note: The safety valve (s) routes compressed product gas back to the gas inlet (b). This will increase the gas inlet temperature. In case of continuous operation of the safety valve the temperature monitoring will therefore shut down the compressor. The compressor is not absolutely gas tight. In case of conveying air in new conditions of the compressor the leakage rate amounts to 1.5 hPa l/s (=mbar l/s) at 2 barg. Due to illegal pressures at the gas connections, worn shaft seal rings or clogged pressure relief lines this leakage rate can rise considerably. Make sure that the installation space or location is vented such that in case of conveying media which are dangerous to health no impermissible accumulation of conveyed media in the environment of the compressor will occur. The installation space or location must be vented sufficiently. The approval for use in potentially explosive atmospheres is valid for the compressor together with the described measurement and safety equipment. The approval is void if the system is altered or if the scheduled maintenance is not complied with. Maintenance must be performed by specifically instructed personnel only. CAUTION_a Due to the corrosion protection coating CPC the compressor is capable of conveying water vapour. Very humid process gases and/or adverse operating cycles can lead to residual condensates, though, which cause corrosion. If this is the case, it is necessary to counteract residual condensates by warming up the compressor, conveyance of ambient air after process end and regular draining of the anti-pulsation chamber (q). ◆ Close the shut-off valve in the suction line ◆ Warm up the compressor for approx. 10 minutes At process start: ◆ Open the shut-off valve in the suction line At the process end: ◆ Close the shut-off valve in the suction line ◆ Open the ambient air valve ◆ Operate the compressor for another approx. 10 minutes ◆ Close the ambient air valve CAUTION_a During operation of the compressor the anti-pulsation chamber is under pressure. CAUTION_ac During operation the surface of the compressor may reach temperatures of more than 70 °C. Risk of burns! The compressor shall be protected against contact during operation, it shall cool down prior to a required contact or heat protection gloves shall be worn. Risk of injury when the condensate drain cock is opened! Drain condensate only when the compressor is shut down and the pressure connection (u) is vented to atmospheric pressure. ◆ Regularly drain condensate from the anti-pulsation chamber (q) CAUTION_a4 The compressor emits noise of high intensity in a narrow band. Risk of damage to the hearing. Persons staying in the vicinity of a non noise insulated compressor over extended periods shall wear ear protection. MM 1202, 1252, 1322 AP ATEX-Version, Gas Tight 0870142930 / 190705 Installation and Commissioning page 11 The level of the synchronising gear should stay constant over the lifetime of the oil. If the level does fall, the gear is leaky and the compressor requires repair (Busch service). Maintenance Every 6 Months: WARNING_ad The approval of the compressor for use in potentially explosive areas remains valid only if the maintenance is conducted regularly according to the maintenance schedule below and genuine spare parts and consumables, approved for use in potentially explosive areas by Busch, are used exclusively. Maintenance work must be executed by qualified personnel, specially instructed in the maintenance of this type of compressor by Busch. ● Make sure that the housing is free from dust and dirt, clean if necessary ● Make sure that the compressor is shut down and locked against inadvertent start up ● Remove the acoustic enclosure Note: Any kind of deposit on the compressor compromises the explosion safety of the compressor. Deposits on a fan wheel deteriorate the balancing quality of the fan wheel, which compromises the explosion safety further. ● Remove the protective grid (e) from the cooling air outlet WARNING_ad Do not open the compressor in potentially explosive atmosphere. ● Open the inspection port (e) on the cooling air duct ● Clean the cooling air duct (compressed air) Risk of explosion! Note: Make sure that the foam mats do n o t get soaked with water DANGER_age32 In case the compressor conveyed gas that was contaminated with foreign materials which are dangerous to health, harmful material can reside in filters. ● Clean the fan cowlings, fan wheels, the ventilation grilles and cooling fins ● Undo the screws of the drive motor ● Remove the drive motor Version with ROTEX coupling: Danger to health during inspection, cleaning or replacement of filters. Danger to the environment. Personal protective equipment must be worn during the handling of contaminated filters. Contaminated filters are special waste and must be disposed of separately in compliance with applicable regulations. CAUTION_ac During operation the surface of the compressor may reach temperatures of more than 70 °C. ◆ Check the wear of the coupling element (Ú page 62: excerpt from operating- / assembly instructions of the ROTEX coupling) Risk of burns! If the measured value X < 8 mm: ● Prior to disconnecting connections make sure that the connected pipes/lines are vented to atmospheric pressure Maintenance Schedule Note: The maintenance intervals depend very much on the individual operating conditions. The intervals given below are upper limits that must not be exceeded. Particularly heavy duty operation, such like high dust loads in the environment or in the process gas, other contaminations or ingress of process material, can make it necessary to shorten the maintenance intervals significantly. ◆ Replace the coupling element (the proper function of the fan wheel requires the precise adjustment of the coupling on the motor shaft and on the pump shaft; therefore the coupling element can be replaced by the Busch service only) Version with BoWex-ELASTIC coupling: ◆ Check the wear of the coupling element (Ú page 63: excerpt from operating- / assembly instructions of the BoWexELASTIC coupling) ● Mount the drive motor on the compressor ● Mount the protective grid (e) on the cooling air outlet Monthly: ● Close the inspection port (e) on the cooling air duct ● Make sure that the compressor is shut down and locked against inadvertent start up ● Mount the acoustic enclosure ● Check the inlet air filter (n), if necessary replace ● Make sure that the electrical connection of the temperature monitoring is undamaged In case of operation in a dusty environment: ◆ Clean as described under Ú page 12: Every 6 Months: Every 3 Months: ● Make sure that the compressor is shut down ● Check the level of the synchronising gear oil The level shall be slightly above the middle of the sight glass (g). ● Check the electrical connection ● Make sure that the electrical connection of the pressure monitoring is undamaged Version with equipotential bonding of the fan cover: ◆ Make sure that the earth cable on the fan cover is undamaged (resistance check) Version with ATEX-inlet air filter (with equipotential bonding): ◆ Make sure that the earthing cable on the inlet air filter housing is undamaged (resistance check) MM 1202, 1252, 1322 AP ATEX-Version, Gas Tight 0870142930 / 190705 Maintenance page 12 Every Year: 615 ● Make sure that the compressor is shut down and locked against inadvertent start up ● Replace the inlet air filter (n) 424 ● Check the inlet screen, clean if necessary Note: As there is an inlet air filter upstream the inlet screen, the inlet screen should not show soiling. A soiled inlet screen indicates that the filter is either broken through or improperly inserted. WARNING_ad A soiled screen indicates the improper function of the filter. The pump chamber contains material that can compromise the explosion safety of the compressor. Risk of explosion! If the inlet screen is soiled, the compressor must be cleaned by Busch service. Version with vacuum relief valve with inlet air filter: ◆ Replace the inlet air filter of the vacuum relief valve ● Check the function of the measurement and safety instrumentation (Ú page 14: Functional Check of the Measurement and Safety Instrumentation) Every 5000 Operating Hours, At the Latest after 2 Years: ● Remove the eyebolt (i, 615) ● Remove the lid (h, 424) CAUTION_a Pressurised air supply systems supply a too high pressure. In case of higher requirements in terms of gas tightness: ◆ Replace the shaft seal rings (Busch service) Every 10000 Operating Hours, At the Latest after 2 Years: DANGER_age32 Risk of damage to the compressor. Adjust the pressurised air to 0.2 barg by means of a pressure regulator. ● Remove the screw plugs of the pressure relief lines and connect the pressurised air lines (Ú illustration) In case the compressor conveyed gas that was contaminated with foreign materials which are dangerous to health, harmful material can reside in the pressure relief lines (a). Danger to health during blowing out the pressure relief lines. Danger to the environment. Wear personal protective equipment while handling contaminated pressure relief lines. Collect deposits from the pressure relief lines and dispose of them in compliance with applicable regulations. In order to check the pressure relief lines (a): ● Undo the fittings between the pressure relief lines and the collecting line (Ú illustration) ● Apply 0.2 barg to the pressure relief lines (a) ● Check that both pressure relief lines (a) pass the pressurised air In case one or both pressure relief line(s) (a) is/are clogged: ◆ Remove the compressor from service and have it repaired (Busch service) ● Reconnect the collecting line to the gas inlet (b) and to the pressure relief lines ● Reinsert the screw plugs, remount the lid (h, 424) and the eyebolt (i, 615) ● Undo the fitting between the the collecting line and the gas inlet (b) and remove the collecting line ● Blow out the collecting line with pressurised air Every 20000 Operating Hours, At the Latest after 6 Years: ● Have a major overhaul on the compressor (Busch service) ● Pierce the connection for the collection line at the gas inlet (b) MM 1202, 1252, 1322 AP ATEX-Version, Gas Tight 0870142930 / 190705 Maintenance page 13 Functional Check of the Measurement and Safety Instrumentation ● Reconnect the resistance thermometer Pt100 to the temperature transmitter (white cable to pin 1, first red cable to pin 2, second red cable to pin 3, Ú sketch) (version with temperature monitoring only) WARNING_ab Risk of electrical shock, risk of damage to equipment. Electrical installation work must only be executed by qualified personnel that knows and observes the following regulations: - IEC 364 or CENELEC HD 384 or DIN VDE 0100, respectively, - IEC-Report 664 or DIN VDE 0110, - BGV A2 (VBG 4) or corresponding national accident prevention regulation. ● Make sure that the compressor aspirates inert gases and that there are no potentially explosive atmospheres in the environment ● Open the lid of the temperature measurement system (f) ● Firmly close the temperature measurement system (f) with the lid Overhaul WARNING_ad ● Disconnect the white cable from pin 1, the first red cable from pin 2 and the second red cable from pin 3 Improper work on the compressor puts the operating safety at risk. ● In order to simulate the resistance thermometer Pt100 set a variable ohmic resistance to approx. 100 Ω Risk of explosion! ● Connect the variable ohmic resistance with 3 identical cables to the pins 1, 2 and 3 of the temperature transmitter as shown in the sketch (the cable connected to pin 2 compensates the cable resistance) Approval for operation will be void! Any dismantling of the compressor that is beyond of what is described in this manual must be done by specially trained Busch service personnel only. DANGER_age32 In case the compressor conveyed gas that was contaminated with foreign materials which are dangerous to health, harmful material can reside in pores, gaps and internal spaces of the compressor. Danger to health during dismantling of the compressor. ● Switch on the compressor ● Increase the ohmic resistance to the resistance at shutdown temperature according to the Equipment Documentation Measurement and Safety Instrumentation (Ú page 21) ● Make sure that an alarm is released in the system control and the compressor is shut down automatically ● Decrease the ohmic resistance to a value less than the shutdown point ● Make sure that the alarm persists ● Make sure that the compressor does not start self-acting Danger to the environment. Prior to shipping the compressor shall be decontaminated as good as possible and the contamination status shall be stated in a “Declaration of Contamination” (form downloadable from www.buschvacuum.com). Busch service will only accept compressors that come with a completely filled in and legally binding signed “Declaration of Contamination” (form downloadable from www.buschvacuum.com). Removal from Service ● Switch on the compressor again Temporary Removal from Service ● Interrupt the ohmic resistance ● Prior to disconnecting pipes/lines make sure that all pipes/lines are vented to atmospheric pressure ● Make sure that a fault indication is released in the system control and the compressor is shut down automatically ● Reconnect the variable ohmic resistance ● Switch on the compressor again Recommissioning ● Observe the chapter Installation and Commissioning (Ú page 6) ● Short circuit the variable ohmic resistance ● Make sure that a fault indication is released in the system control and the compressor is shut down automatically ● Remove the short circuit ● Remove the variable ohmic resistance MM 1202, 1252, 1322 AP ATEX-Version, Gas Tight 0870142930 / 190705 Maintenance page 14 Dismantling and Disposal DANGER_age32 In case the compressor conveyed gas that was contaminated with foreign materials which are dangerous to health, harmful material can reside in pores, gaps and internal spaces of the compressor. Danger to health during dismantling of the compressor. Danger to the environment. During dismantling of the compressor personal protective equipment must be worn. The compressor must be decontaminated prior to disposal. ● Drain the oil ● Make sure that materials and components to be treated as special waste have been separated from the compressor ● Make sure that the compressor is not contaminated with harmful foreign material According to the best knowledge at the time of printing of this manual the materials used for the manufacture of the compressor involve no risk. ● Dispose of the used oil in compliance with applicable regulations ● Dispose of the compressor as scrap metal MM 1202, 1252, 1322 AP ATEX-Version, Gas Tight 0870142930 / 190705 Removal from Service page 15 Troubleshooting WARNING_ad Vacuum pump/ Compressor/ Vacuum and pressure pump/ Blower for use in potentially explosive atmospheres. The compressor must only be operated in faultless condition. Risk of explosion in case of operation of faulty equipment! A faulty compressor must immediately be removed from service. In case of faults the cause of which cannot be determined the Busch service must be contacted. WARNING_ab Risk of electrical shock, risk of damage to equipment. Electrical installation work must only be executed by qualified personnel that knows and observes the following regulations: - IEC 364 or CENELEC HD 384 or DIN VDE 0100, respectively, - IEC-Report 664 or DIN VDE 0110, - BGV A2 (VBG 4) or equivalent national accident prevention regulation. CAUTION_ac During operation the surface of the compressor may reach temperatures of more than 70 °C. Risk of burns! Let the compressor cool down prior to a required contact or wear heat protection gloves. Problem Possible Cause Remedy The compressor does not reach the usual pressure The pressure system or pressure line is not leak-tight Check the hose or pipe connections for possible leak The pressure relief valve/regulating system is misadjusted or defective Adjust, repair or replace, respectively The screen in the gas inlet (b) is partially clogged Clean the screen The filter (n) on the gas inlet (b) is partially clogged Clean or replace the inlet air filter (n), respectively Partial clogging in the suction, discharge or pressure line Remove the clogging Long suction, discharge or pressure line with too small diameter Use larger diameter The valve disk of the inlet non-return valve is stuck in closed or partially open position Disassemble the inlet, clean the screen and the valve (y) as required and reassemble Internal parts are worn or damaged Repair the compressor (Busch service) Partial clogging in the suction line Remove the clogging The upstream process stage delivers to little or too much process gas Make sure that the upstream process stage delivers the right amount of process gas The drive motor is not supplied with the correct voltage or is overloaded Supply the drive motor with the correct voltage The drive motor draws a too high current (compare with initial value after commissioning) Filling the system takes too long Building up pressure in the system takes too long There is an indication on the control panel / in the control room that the pressure switch/indicator (k) measured a pressure outside the range from -200 mbarg to +200 mbarg The compressor does not start MM 1202, 1252, 1322 AP ATEX-Version, Gas Tight 0870142930 / 190705 If cleaning is required too frequently install a filter upstream Troubleshooting page 16 The drive motor starter overload protection is too small or trip level is too low Compare the trip level of the drive motor starter overload protection with the data on the nameplate, correct if necessary One of the fuses has blown Check the fuses The connection cable is too small or too long causing a voltage drop at the compressor Use sufficiently dimensioned cable The compressor or the drive motor is blocked Make sure the drive motor is disconnected from the power supply Remove the fan cover Try to turn the drive motor with the compressor by hand If the compressor is blocked: Repair the compressor (Busch service) The drive motor is defective Replace the drive motor (Busch service) (in order not to compromise the explosion safety of the compressor the coupling must be adjusted and measured according to a precisely defined procedure; therefore the motor must be mounted by the Busch service only) The compressor is blocked Solid foreign matter has entered the compressor Repair the compressor (Busch service) Make sure the suction line is equipped with a screen If necessary additionally provide a filter Corrosion in the compressor from remaining condensate Repair the compressor (Busch service) Check the process Observe the chapter Conveying Condensable Vapours (Ú page 11) The compressor was run in the wrong direction Repair the compressor (Busch service) The drive motor is running, but the compressor stands still The coupling between the drive motor and the compressor is defective Replace the coupling element The compressor starts, but labours or runs noisily or rattles Loose connection(s) in the drive motor terminal box Check the proper connection of the wires against the connection diagram The drive motor draws a too high current (compare with initial value after commissioning) Not all drive motor coils are properly connected (particularly on motors with six coils) When connecting the compressor make sure the compressor will run in the correct direction (Ú page 8: Installation) (in order not to compromise the explosion safety of the compressor the coupling must be adjusted and measured according to a precisely defined procedure; therefore the coupling element must be replaced by the Busch service only) Tighten or replace loose connections The drive motor operates on two phases only The compressor runs in the wrong direction Verification and rectification Ú page 6: Installation and Commissioning Foreign objects in the compressor Repair the compressor (Busch service) Stuck bearings The compressor runs very noisily Defective bearings Repair the compressor (Busch service) Worn coupling element Replace the coupling element (in order not to compromise the explosion safety of the compressor the coupling must be adjusted and measured according to a precisely defined procedure. Therefore the coupling element must be replaced by Busch service only) Low oil level in the synchronising gear The synchronising gear is leaky Repair the compressor (Busch service) MM 1202, 1252, 1322 AP ATEX-Version, Gas Tight 0870142930 / 190705 Troubleshooting page 17 There is an indication on the control panel / in the control room that the temperature monitoring has tripped (permissible temperature at the outlet of the stage has been exceeded) Synchronising gear damaged due to operation with low oil level Repair the compressor (Busch service) Insufficient air ventilation Make sure that the cooling of the compressor is not impeded by dust/dirt Clean the fan cowlings, the fan wheels, the ventilation grilles and the cooling fins The compressor is shut down Install the compressor in a narrow space only if sufficient ventilation is ensured Ambient temperature too high Observe the permitted ambient temperatures Temperature of the inlet gas too high Observe the permitted temperatures for the inlet gas Insufficient gas transfer Check the process conditions Mains frequency or voltage outside tolerance range Provide a more stable power supply In case a pressure relief valve/regulating system is installed: Adjust, repair or replace, respectively The pressure relief valve/regulating system is misadjusted or defective Partial clogging of filters or screens Remove the clogging Partial clogging in the suction, discharge or pressure line Long suction, discharge or pressure line with too small diameter MM 1202, 1252, 1322 AP ATEX-Version, Gas Tight 0870142930 / 190705 Use larger diameter Troubleshooting page 18 Spare Parts Note: When ordering spare parts or accessories acc. to the table below please always quote the type (“Type”) and the serial no. (“No”) of the compressor. This will allow Busch service to check if the compressor is compatible with a modified or improved part. The approval of the compressor for use in potentially explosive areas remains valid only if genuine spare parts and consumables, which are approved for use in potentially explosive areas by Busch, are used exclusively. Your point of contact for service and spare parts in the United Kingdom: Busch (UK) Ltd. Hortonwood 30-35 Telford Shropshire TF1 7YB Tel: 01952 677 432 Fax: 01952 677 423 Your point of contact for service and spare parts in Ireland: Busch Ireland Ltd. A10-11 Howth Junction Business Centre Kilbarrack, Dublin 5 Tel: +353 (0)1 8321466 Fax: +353 (0)1 8321470 Your point of contact for service and spare parts in the USA: Busch lnc. 516-B Viking Drive Virginia Beach, VA 23452 Tel: 1-800-USA-PUMP (872-7867) Your point of contact for service and spare parts in Canada: Busch Vacuum Technics Inc. 1740, Boulevard Lionel Bertrand Boisbriand (Montréal) Québec J7H 1N7 Tel: 450 435 6899 Fax: 450 430 5132 Your point of contact for service and spare parts in Australia: Busch Australia Pty. Ltd. 30 Lakeside Drive Broadmeadows, Vic. 3047 Tel: (03) 93 55 06 00 Fax: (03) 93 55 06 99 Your point of contact for service and spare parts in New Zealand: Busch New Zealand Ltd. Unit D, Arrenway Drive Albany, Auckland 1311 P O Box 302696 North Harbour, Auckland 1330 Tel: 0-9-414 7782 Fax: 0-9-414 7783 Find the list of Busch companies all over the world (by the time of the publication of these installation and operating instructions) on Ú page 68 (rear cover page). Find the up-to-date list of Busch companies and agencies all over the world on the internet at www.buschvacuum.com. Pos. Part Qty Part no. — Filter cartridge, paper, for inlet filter 1 0532 134 779 — Filter cartridge, polyester, for inlet filter 1 0532 137 989 — Safety valve (quote in your order also the ultimate working pressure of the compressor) 1 on request MM 1202, 1252, 1322 AP ATEX-Version, Gas Tight 0870142930 / 190705 Spare Parts page 19 EU Declaration of Conformity Note: This Declaration of Conformity and the CE-mark affixed to the nameplate are valid for the machine within the Busch scope of delivery. This Declaration of Conformity is issued under the sole responsibility of the manufacturer. When this machine is integrated into a superordinate machinery the manufacturer of the superordinate machinery (this can be the operating company, too) must conduct the conformity assessment process for the superordinate machine or plant, issue the Declaration of Conformity for it and affix the CE-mark. We Busch Produktions GmbH Schauinslandstr. 1 79689 Maulburg Germany Declare that the vacuum pumps MM ‘ATEX’ 1324, 1202, 1252, 1322 AP, Gas Tight with a serial number from DEM11917… to DEM12252… Documentation No.: T611141618 has (have) been manufactured in accordance with the European Directives: • ‘Machinery’ 2006/42/EC • ‘ATEX Directive’ 2014/34/EU for use in potentially explosive areas according to classification written on the machine nameplate • ‘Electromagnetic Compatibility’ 2014/30/EU • ‘RoHS’ 2011/65/EU + Commission Delegated Directive (EU) 2015/863, restriction of the use of certain hazardous substances in electrical and electronic equipment and following the standards. Standard Title of the Standard EN ISO 12100: 2010 Safety of machinery – Basic concepts, General principles for design –Risk assessment and risk reduction EN ISO 13857: 2008 Safety of machinery - Safety distances to prevent hazard zones being reached by the upper and lower limbs EN 1012-1: 2010 EN 1012-2: 1996 + A1: 2009 Compressors and vacuum pumps - Safety requirements - Part 1 and Part 2 EN ISO 2151: 2008 Acoustics - Noise test code for compressors and vacuum pumps - Engineering method (grade 2) EN 60204-1: 2006 Safety of machinery - Electrical equipment of machines - Part 1: General requirements EN 61000-6-2: 2005 Electromagnetic compatibility (EMC) - Generic immunity standards. Immunity for industrial environments EN 61000-6-4: 2007 + A1: 2011 Electromagnetic compatibility (EMC) - Generic immunity standards. Emission standard for industrial environments EN ISO 13849-1: 2015 (1) Safety of machinery - Safety-related parts of control systems - Part 1: General principles for design EN ISO 13463-1: 2009 Non-electrical equipment for potentially explosive atmospheres - Part 1: Basic methodology and requirements EN ISO 1127-1: 2011 Explosive atmospheres - Explosion prevention and protection - Part 1: Basic concepts and methodology Manufacturer Dr. Martin Gutmann, General Manager Person authorized to compile the technical file Gerd Rohweder Busch Dienste GmbH Schauinslandstr. 1 DE-79689 Maulburg Maulburg, 23.04.2019 MM 1202, 1252, 1322 AP ATEX-Version, Gas Tight 0870142930 / 190705 EU Declaration of Conformity page 20 Equipment Documentation Measurement and Safety Instrumentation Temperatures - currents (presets) Temperature Resistance Current Under measurement range (= sensor short circuit) - - 3.6 mA Version with Resistance Thermometer, without Transmitter Lower measurement range limit -20 °C 92.160 Ω 4.0 mA In case the transmitter is furnished by the system supplier or operator. Shutdown temperature 125 °C 147.944 Ω 10.270 mA 130 °C 149.824 Ω 10.486 mA 150 °C 157.315 Ω 11.351 mA 160 °C 161.043 Ω 11.784 mA 165 °C 162.903 Ω 12.000 mA 170 °C 164.760 Ω 12.216 mA 180 °C 168.465 Ω 12.649 mA 190 °C 172.158 Ω 13.081 mA 220 °C 183.168 Ω 14.378 mA 225 °C 184.993 Ω 14.595 mA 230 °C 186.815 Ω 14.811 mA 240 °C 190.451 Ω 15.243 mA 250 °C 194.074 Ω 15.676 mA 270 °C 201.287 Ω 16.541 mA 280 °C 204.876 Ω 16.973 mA 290 °C 208.453 Ω 17.405 mA 300 °C 212.019 Ω 17.838 mA 310 °C 215.573 Ω 18.270 mA 340 °C 226.166 Ω 19.568 mA 350 °C 229.673 Ω 20.000 mA Upper measurement range limit 350 °C 229.673 Ω 20.0 mA Connection of supply voltage to pins + (positive pole) and - (negative pole). Sensor breakage - - 21.0 mA Upper limiting values in supply circuit (certified intrinsically safe electric circuit): More installation notes: After connection of the cables to the switchboard/system control make sure that the housing is firmly closed and the cable glands are tightened. Overview Scope of delivery Resistance thermometer with connecting cable Type/Marking TR40 Pt100/B/3 Documentation (applicable shutdown temperature see nameplate of the compressor) Operating instructions resistance thermometers and thermocouples (on the following pages) Version with Resistance Thermometer and Transmitter Standard scope of delivery for version with temperature monitoring Scope of delivery Thermometer system, consisting of: Resistance thermometer with connecting cable, transmitter, junction box Type/Marking Resistance thermometer: TR40 Pt100/B/3 Transmitter: TMT181-B Junction box: 15060603 Brief description: Resistance thermometer with connected temperature transmitter Temperature resistor with 3-wire connection. Temperature transmitter with 3-wire electronics for signal 4 ... 20 mA. Ui = 30 V; Pi = 800 mW; Ii = 120 mA Documentation Operating instructions resistance thermometers and thermocouples (on the following pages) Operating Instructions Temperature Transmitter (on the following pages) MM 1202, 1252, 1322 AP ATEX-Version, Gas Tight 0870142930 / 190705 Equipment Documentation Measurement and Safety Instrumentation page 21 Pressure Switch/Indicator Fast adjustment on (for version with temperature monitoring in standard scope of delivery, for version without temperature monitoring optional) Behaviour of signal output oFF More installation notes: Type/Marking ExS10-0AVA1710R2SB4 Brief description: The device is fed with a voltage between 14.5 and 45 V DC (between 14.5 and 27.3 V DC in intrinsically safe circuits). The positive pole of the supply is connected to pin 1, the negative pole to pin 3. Depending on the pressure signal the current between pin 3 and the negative pole of the supply varies between 4 mA (corresponding to -1 barg in factory setting) and 20 mA (corresponding to +1 barg in factory setting). If required two switching points can be evaluated by means of the pins 4 and 2 and the state of the switches be read on the LEDs S1 and S2. Technical data excerpt from Installation and Oper-ating Instructions BA0607 Interface A mating coupling is in the scope of delivery. Cable connection with screw clamps max. 0.75 mm². The pressure switch/indicator (k) is to be integrated into the system control such that the maintenance of the permitted pressure range* will be monitored. If the pressure gets outside this range the system control must automatically shut down the compressor. *ambient pressure ±200 hPa (=mbar), unless specified otherwise on the nameplate of the compressor Observe the excerpt from Installation and Operating Instructions BA0607; the complete documentation is available from www.acscontrolsystem.de. A matching coupling for the connection of a cable to the pressure switch/indicator (k) is included in the scope of delivery of the compressor. Pin 1 transmits the sum of the currents of the pins 2, 3 and 4. The monitoring circuitry shall be designed such that the current and the voltage allowed for intrinsically safe circuits will not be exceeded on any wire at any time. Switching options (examples): Upon delivery the pressure switch/indicator is set to “factory values”, except for the limit values of the switch points 1 and 2 and the operating mode of switch point 2. Restoration in case of inad-vertent misadjustment. Lower pressure signal with signal applied (liquid adjustment) not to be set Zero signal without applied signal (dry adjustment) -.999 (achieves sufficient accuracy, can be retained) Upper pressure signal with signal applied (liquid adjustment) not to be set Span signal without applied signal (dry adjustment) 1.000 (achieves sufficient accuracy, can be retained) Decimal places dp3 (corresponds to indication 8.888) Zero scaling -.999 Endpoint-scaling 1.000 Damping 1 (corresponds to 0.3 seconds delay) Limit value switch point 1 -.200 (“customer specific adjustment”) Hysteresis switch point 1 0.003 Operating mode switch point 1 n.o. (working principle) Function switch point 1 norF Limit value switch point 2 0.200 (“customer specific adjustment”) Hysteresis switch point 2 0.003 Operating mode switch point 2 n.c. (quiescent principle, “customer specific adjustment”) MM 1202, 1252, 1322 AP ATEX-Version, Gas Tight 0870142930 / 190705 1. Use of isolation switch amplifiers (e.g. Pepperl+Fuchs KF__-SR2-Ex1.W; not in the Busch scope of delivery) switched between the pins 1, 2 and 4 of the pressure switch/indicator (k) on the one side and the switching relays on the other. 2. Evaluation of the 4 ... 20 mA signal of the pressure switch/indicator (k) alone, by means of a suitable transmitter supply (e.g. Pepperl+Fuchs KF__-CRG-Ex1.D; not in the Busch scope of delivery). 3. Evaluation of the 4 ... 20 mA signal of the pressure switch/indicator (k) alone, after isolation by means of a suitable transmitter supply (e.g. ACS ExTVA500, Pepperl+Fuchs KFD2-STC4-Ex1; not in the Busch scope of delivery), by means of a non-Ex-system control or SPS respectively. The pressure switch/indicator (k) is to be integrated into the system control such that the maintenance of the pressure range from -200 mbarg to +200 mbarg (corresponding to a current between 10.4 and 13.6 mA, if the factory set measurement range is retained) will be monitored. If the pressure gets outside this range the system control must automatically shut down the compressor. The restart of the compressor is permitted only by action from the operating personnel after remedy of the cause of the excessive pressure. Equipment Documentation Measurement and Safety Instrumentation page 22 Documentation Resistance Thermometer MM 1202, 1252, 1322 AP ATEX-Version, Gas Tight 0870142930 / 190705 Equipment Documentation Measurement and Safety Instrumentation page 23 MM 1202, 1252, 1322 AP ATEX-Version, Gas Tight 0870142930 / 190705 Equipment Documentation Measurement and Safety Instrumentation page 24 MM 1202, 1252, 1322 AP ATEX-Version, Gas Tight 0870142930 / 190705 Equipment Documentation Measurement and Safety Instrumentation page 25 MM 1202, 1252, 1322 AP ATEX-Version, Gas Tight 0870142930 / 190705 Equipment Documentation Measurement and Safety Instrumentation page 26 MM 1202, 1252, 1322 AP ATEX-Version, Gas Tight 0870142930 / 190705 Equipment Documentation Measurement and Safety Instrumentation page 27 MM 1202, 1252, 1322 AP ATEX-Version, Gas Tight 0870142930 / 190705 Equipment Documentation Measurement and Safety Instrumentation page 28 MM 1202, 1252, 1322 AP ATEX-Version, Gas Tight 0870142930 / 190705 Equipment Documentation Measurement and Safety Instrumentation page 29 MM 1202, 1252, 1322 AP ATEX-Version, Gas Tight 0870142930 / 190705 Equipment Documentation Measurement and Safety Instrumentation page 30 MM 1202, 1252, 1322 AP ATEX-Version, Gas Tight 0870142930 / 190705 Equipment Documentation Measurement and Safety Instrumentation page 31 MM 1202, 1252, 1322 AP ATEX-Version, Gas Tight 0870142930 / 190705 Equipment Documentation Measurement and Safety Instrumentation page 32 MM 1202, 1252, 1322 AP ATEX-Version, Gas Tight 0870142930 / 190705 Equipment Documentation Measurement and Safety Instrumentation page 33 MM 1202, 1252, 1322 AP ATEX-Version, Gas Tight 0870142930 / 190705 Equipment Documentation Measurement and Safety Instrumentation page 34 MM 1202, 1252, 1322 AP ATEX-Version, Gas Tight 0870142930 / 190705 Equipment Documentation Measurement and Safety Instrumentation page 35 MM 1202, 1252, 1322 AP ATEX-Version, Gas Tight 0870142930 / 190705 Equipment Documentation Measurement and Safety Instrumentation page 36 MM 1202, 1252, 1322 AP ATEX-Version, Gas Tight 0870142930 / 190705 Equipment Documentation Measurement and Safety Instrumentation page 37 MM 1202, 1252, 1322 AP ATEX-Version, Gas Tight 0870142930 / 190705 Equipment Documentation Measurement and Safety Instrumentation page 38 MM 1202, 1252, 1322 AP ATEX-Version, Gas Tight 0870142930 / 190705 Equipment Documentation Measurement and Safety Instrumentation page 39 MM 1202, 1252, 1322 AP ATEX-Version, Gas Tight 0870142930 / 190705 Equipment Documentation Measurement and Safety Instrumentation page 40 MM 1202, 1252, 1322 AP ATEX-Version, Gas Tight 0870142930 / 190705 Equipment Documentation Measurement and Safety Instrumentation page 41 MM 1202, 1252, 1322 AP ATEX-Version, Gas Tight 0870142930 / 190705 Equipment Documentation Measurement and Safety Instrumentation page 42 MM 1202, 1252, 1322 AP ATEX-Version, Gas Tight 0870142930 / 190705 Equipment Documentation Measurement and Safety Instrumentation page 43 MM 1202, 1252, 1322 AP ATEX-Version, Gas Tight 0870142930 / 190705 Equipment Documentation Measurement and Safety Instrumentation page 44 Documentation Temperature Transmitter MM 1202, 1252, 1322 AP ATEX-Version, Gas Tight 0870142930 / 190705 Equipment Documentation Measurement and Safety Instrumentation page 45 MM 1202, 1252, 1322 AP ATEX-Version, Gas Tight 0870142930 / 190705 Equipment Documentation Measurement and Safety Instrumentation page 46 MM 1202, 1252, 1322 AP ATEX-Version, Gas Tight 0870142930 / 190705 Equipment Documentation Measurement and Safety Instrumentation page 47 MM 1202, 1252, 1322 AP ATEX-Version, Gas Tight 0870142930 / 190705 Equipment Documentation Measurement and Safety Instrumentation page 48 MM 1202, 1252, 1322 AP ATEX-Version, Gas Tight 0870142930 / 190705 Equipment Documentation Measurement and Safety Instrumentation page 49 MM 1202, 1252, 1322 AP ATEX-Version, Gas Tight 0870142930 / 190705 Equipment Documentation Measurement and Safety Instrumentation page 50 MM 1202, 1252, 1322 AP ATEX-Version, Gas Tight 0870142930 / 190705 Equipment Documentation Measurement and Safety Instrumentation page 51 MM 1202, 1252, 1322 AP ATEX-Version, Gas Tight 0870142930 / 190705 Equipment Documentation Measurement and Safety Instrumentation page 52 MM 1202, 1252, 1322 AP ATEX-Version, Gas Tight 0870142930 / 190705 Equipment Documentation Measurement and Safety Instrumentation page 53 MM 1202, 1252, 1322 AP ATEX-Version, Gas Tight 0870142930 / 190705 Equipment Documentation Measurement and Safety Instrumentation page 54 MM 1202, 1252, 1322 AP ATEX-Version, Gas Tight 0870142930 / 190705 Equipment Documentation Measurement and Safety Instrumentation page 55 BA 0607 Pressure Lauterbachstr. 57 – 84307 Eggenfelden – Germany Tel: +49 8721/9668-0 – Fax: +49 8721/9668-30 [email protected] – www.acs-controlsystem.de Password function for protection of the settings against alternation Programmable evaluation electronic with high brightness LED-display - in 2-wire-technology with current signal 4...20 mA or - in 3-wire-technology with voltage signal 0...10 V - with two PNP switching outputs Excellent accuracy up to ≤ 0,1% ATEX II 1/2 G D EEx ia IIC T4 Certification for the use in explosion hazardous areas Humidity resistant variant for climatic extreme conditions like high air humidity or also at condensed water formation Various usability, especially for hygienic applications Suitable for wide process temperature range from – 40 °C to +370 °C Ceramic or metallic membrane with various process connections Pressure ranges 0...0,1 bar to 0...1000 bar / -0,1...0/+0,1 bar / -1...0/+1 bar for continuous measuring and supervision of pressures in gases, steam, liquids and dusts Pressure transmitter Precont S – Precont D40 Technical manual ........................................................................................................... 7 ........................................................................................................ 7 ...................................................................................................... 7 Installation notes Maintenance notes Electrical connection ...................................................... 10 ................................. 9 .............................................................................. 21 ............................................................................... 22 .............................................................................. 23 ............................................................................... 24 .............................................................................. 25 ............................................................................... 26 .............................................................................. 27 ............................................................................... 28 Dimension drawings Precont S40 Order code overview Precont S40 Dimension drawings Precont D40 Order code overview Precont D40 Dimension drawings Precont S60 Order code overview Precont S60 Dimension drawings Precont S70 Order code overview Precont S70 page 2 of 28 ............................................................................... 20 Order code overview Precont S30 .............................................................................. 19 .............................................................................. 18 Order code overview Precont S20 Dimension drawings Precont S30 .............................................................................. 17 ............................................................................... 16 Dimension drawings Precont S20 Order code overview Precont S10 .............................................................................. 15 ............................................................................................... 12 / 13 / 14 ........................................................................................................ 11 Dimension drawings Precont S10 Technical data Adjustment menu Operation and display elements / Function modes Electrical connection – connection in explosive hazardous areas ......................... 8 ........................................................................................................... 6 Assignment – electrical connection in non-explosive hazardous areas ................................................................................................................... 6 Safety notes ........................ 5 Safety notes Available pressure ranges – permissible overload resp. burst pressure .......................................................................... 4 ...................................................................................................... 3 ................................................................................................... 3 Variant differences – application range Function description Application description Index Precont S – Precont D40 MM 1202, 1252, 1322 AP ATEX-Version, Gas Tight 0870142930 / 190705 Equipment Documentation Measurement and Safety Instrumentation page 56 page 3 of 28 By 3 keys and the four digit LED display all settings for the display, the analogue output as well as the PNP switching outputs can be set resp. adjusted. A transmitter fast adjustment per key combinations is also possible. According to the resp. settings the PNP switching outputs are driven. The switching state of the two PNP switching output are indicated by each an LED. Signal processing The pressure dependent variation of capacity resp. the variation of the strain gauge output voltage is recorded in high resolution by a processor, adjusted acc. to the settings and converted in high resolution into an output signal of 4...20mA or 0...10V. Characteristics of the process diaphragm seal – Precont S60 / S70 The system pressure is applied to the metallic membrane of the process diaphragm seal and is transmitted by a pressure transmitting liquid to the respective ceramic or metallic measuring membrane that is placed behind. This leads among others to a extension of the permissible medium temperature up to +370°C and to an essential increase of the temperature stability of the device. The metallic membrane offers excellent characteristics like high pressure and pressure blow strength up to six times the nominal pressure, vacuum resistance, good reproducibility and hysteresis and also good long term stability and a low temperature influence. Characteristics of the metallic measuring membrane – Precont S20 / S30 / S70 The system pressure is applied to the metallic membrane and causes there a deflection of the strain gauge at the back side of the membrane. A pressure transmitting liquid is only used at pressure ranges lower than 0...25 bar. The ceramic membrane offers excellent characteristics like highest pressure and pressure blow strength up to forty times the nominal pressure, vacuum resistance, very high resistance against chemicals, corrosion and abrasion as well as very good insensitiveness against temperature shocks, highest accuracy and reproducibility, good long term stability and a very low temperature influence. Characteristics of the ceramic measuring membrane – Precont S10 / S40 / D40 / S60 / S70 The system pressure is applied to the ceramic membrane and causes there a variation of the capacity at the back side of the membrane. A pressure transmitting liquid is not used. The pressure transmitter Precont S – Precont D40 is mounted in the wall of the pressure container or of the pipe. Function description The device variant Precont D40 is especially suitable for the use in areas with high air humidity and condensed water formation, where conventional devices can not or can only be operated with a expensive installed pressure compensation capillary. The use of a capacitive measuring sensor with ceramic membrane or of a strain gauge with metallic membrane, by use of various, also front flush process connections resp. process diaphragm seals, allows the use in nearly all fields of industry, especially also in hygienic applications. The devices of the series Precont S – Precont D40 with integrated digital evaluation electronic are compact pressure transmitter for continuous measuring and supervision of pressures from –1 up to 1000 bar in gases, steams, liquids and dusts within closed container or pipes, also in explosive hazardous areas, at process temperatures from – 40°C to +370°C. Application description Precont S – Precont D40 0032 page 6 of 28 The devices are conceived for measuring of pressures in explosive hazardous areas. The measured medium may also be combustible liquids, gases, fogs or steams. The permitted operating temperatures and pressures are type and variant dependent and can be found in this technical manual. For applications, which require devices of category 1/2 or category 1, the process pressure and temperature range of the media has to be between 0,8 bar and 1,1 bar and between -20 °C and 60 °C. The permissible maximum values for Ui, Ii and Pi are equal for all variants. To this there must be paid especially attention in the case of combining more intrinsically safe circuits at the variants with voltage output 0...10V (variants E/F/G/H) and at the variants with PNP switching outputs (variants A/E). The rules for combination of intrinsically safe circuits must be applied. At variants of the devices with chargeable plastic parts (e.g. cable resp. connection housing), a warning marking points out to the safety measures, that must be applied because of the electrostatic charging in operation and especially in the case of maintenance activities. avoid friction no dry cleaning no assembling in pneumatic conveying stream If a device is installed and operated in explosive hazardous areas, the general Ex construction standards (EN60079-14, VDE0165), this safety notes and the enclosed EC conformity certificate must be observed. The installation of explosive hazardous systems must be carried out principally by specialist staff. The device meets the classification: Ta medium Ta housing II 1/2 G D EEx ia IIC T4 IP65 T60°C / T102°C (T57°C) -20... +60 °C -20…+85 °C (+40 °C) II 2 G D EEx ib IIC T4 IP65 T102°C -20…+85 °C -20…+85 °C II 2 G D EEx ib IIC T4 IP65 T125°C -20…+125 °C -20…+50 °C II 1/2 G EEx ia IIC T4 -20... +60 °C -20…+85 °C II 2 G EEx ib IIC T4 -20…+85 °C -20…+85 °C II 2 G EEx ib IIC T4 -20…+125 °C -20…+50 °C Safety notes for electrical operating supplies for explosive hazardous areas The device meets the legal requirements of all relevant EC directives. This measuring device meets article 3 (3) of the EC directive 97/23/EC (pressure equipment device directive) and is designed and produced in good engineer practice. The sensors may not used as sole device for prevention of dangerous conditions in machines and plants. The materials for membrane, process connection and gaskets must be chosen according to the respective application requirements (used medium, process temperature). An unsuitable material can lead to damage, abnormal behavior or destruction of the device and to the resulting dangers. The device may only be used within the permitted operation limits that are listed in this technical manual. Every use besides these limits as agreed can lead to serious dangers. Installation, electrical connection, inauguration and operation of the device must be made by a qualified employee according to the informations in this technical manual and the relevant standards and rules. Each person that is engaged with inauguration and operation of this device, must have read and understood this technical manual and especially the safety notes. Safety notes Precont S – Precont D40 MM 1202, 1252, 1322 AP ATEX-Version, Gas Tight 0870142930 / 190705 Equipment Documentation Measurement and Safety Instrumentation page 57 page 7 of 28 Inductive loads at the pnp switching outputs, e.g. relays or contactors may only be used with a freewheeling diode or a RC protection circuit to avoid high voltage peaks. The voltage applied to the terminal contacts may not exceed 45 V to avoid damage of the electronic. All connections are polarity protected. At the housing variant with terminal box, the terminals for the connection of a cable are placed below the electronic module. This is plugged and can be pushed easily. After the connection of the cable, the module must be correctly inserted again. The cable gland is suitable für cable diameter from 4,5 to 10 mm. After the installation of the cable the cable gland must be firmly screwed to ensure the tightness of the connection housing. The same is valid for the screw cap of the housing. Use only shielded signal and measurement wires and install these wires separated from power leading wires. Connect the cable shield only at one side to earth, ideally at the installation place of the device. The metallic parts of the device with connection housing plug - type S resp. cable - type K are electrically connected with the earthing connection screw. At the variant with connection housing terminal box – type A all metallic parts are connected with terminal 1 - PE/shield. The electrical connection of the device must be carried out according to the respective country specific standards. Incorrect installation or adjustment could cause applicationally conditioned risks. Electrical connection Special substances can lead to solid coatings on the membrane. Such depositions can lead to faulty measurement results of the pressure transmitter. In the case of coat forming liquids the membrane must be regularly cleaned. Don’t use sharp tools or aggressive chemicals for cleaning. The devices of the series Precont S – Precont D40 are free of maintenance. Maintenance notes The correct function of the device within the specific technical data can only be guaranteed, if the permitted temperature in the area of the connection housing from – 40°C to +85°C will not be exceeded. This can be achieved by the using of the temperature decoupler or also by isolation of the medium carrying part of the plant or by other constructive measures to reduce the transferring of an extreme temperature to the connection housing. Avoid the pollution of the pressure compensation vent. The hindrance of the pressure compensation can lead to faulty measuring results. The housing can be rotated every time, also at operation, by 330°. The tightening of the process connection with screw-in thread may only be done at the hexagon by a suitable spanner. The maximum permitted torque strength is 50 Nm. The screw in of the process connection by using the housing tube is not permitted. Drive the system pressure free prior installation resp. deinstallation of the sensor. The installation of the device should be made if possible at temperature calmed places to get a reliable measuring result. Large temperature steps, e.g. at filling of a hot medium into a cold system, can produce a short-time higher measuring signal deviation at the variants with ceramic measuring membrane. At a large amplification of the measuring signal this deviation will be also amplified accordingly. The deviation will be completely neutralized after the adaptation of the measuring membrane of the pressure transmitter to the temperature. At a step from +20°C ...+80°C this neutralization can wile up to 3 minutes. The use of a process diaphragm seal can cause an essential improvement. The installation of the device at locations where high pressure blows can occur should be avoided. Installation notes Precont S – Precont D40 4 1 3(blau) 1(braun) view to plug socket current shunt or current meter -VS +VS white shortest connection PE / PA connection K current shunt or current meter -VS +VS 4 1(brown) -VS S2 connection K 5 4 +VS connection K white grey S1 +VS 0...10V -VS 5 4 -VS S2 connection K shortest connection S1 +VS 0...10V PE / PA 3(blue) 4(black) 5(grey) 2(white) 1(brown) view to plug socket shortest connection 1 PE / PA connection S 3 2 white green brown grey yellow S1 +VS 0...10V -VS S2 1 +VS PE 2 current shunt or current meter connection A +VS PE 1 3 4 -VS connection A 1 PE +VS T. 1 PE/shield T. 3 -VS T. 5 SP1 PE 1 2 4 -VS 3 6 UOUT 0...10V screw terminal 5 T. 2 +VS T. 4 UOUT (0…10V) T. 6 not connected +VS 2 S2 6 -VS S2 E page 8 of 28 S1 screw terminal 5 UOUT 0...10V 4 T. 2 +VS T. 4 UOUT (0…10V) T. 6 SP2 3 A F/G/H S1 transmitter electronic connection A T. 1 PE/shield T. 3 -VS T. 5 not connected 6 screw terminal 5 T. 2 +VS T. 4 not connected T. 6 SP2 4...20mA 2 T. 1 PE/shield T. 3 IOUT (4…20mA) T. 5 SP1 -VS screw terminal 4...20mA 3 transmitter electronic connection A T. 1 PE/shield T. 2 +VS T. 3 IOUT (4…20mA) transmitter electronic -VS S2 +VS 3 – wire – technology / signal 0...10 V / 2x PNP switching output shortest connection -VS 0...10V white green brown yellow brown PE / PA 3(blue) 5(grey) 1(brown) shortest connection 1 view to plug socket PE / PA connection S 3 2 3 – wire – technology / signal 0...10 V shortest connection S1 +VS PE / PA 3(blue) 4(black) 2(white) shortest connection 1 view to plug socket PE / PA connection S 3 2 connection type A terminal box transmitter electronic B / C / D 2 – wire – technology / signal 4...20 mA / 2x PNP switching output shortest connection PE / PA connection S 3 2 brown connection type K cable 2 – wire – technology / signal 4...20 mA connection type S plug M12x1 Assignment – connection in non-explosion hazardous areas NAMUR NAMUR Precont S – Precont D40 MM 1202, 1252, 1322 AP ATEX-Version, Gas Tight 0870142930 / 190705 Equipment Documentation Measurement and Safety Instrumentation page 58 +I -I +Vs -Vs L/+ N/- auxiliary power isolation amplifier intrinsically safe -O +O SP2 SP1 -I +U -Vs Uout -U +I +Vs L/+ N/- N/- -O N/- N/- N/- isolation amplifier intrinsically safe L/+ auxiliary power isolation amplifier intrinsically safe L/+ auxiliary power -O +O -O +O isolation switch amplifier intrinsically safe L/+ auxiliary power Precont S transmitter electronic variant E SP2 SP1 in out in out -U +U -I -Vs Uout +I +Vs N/- N/- N/- -O N/- isolation switch amplifier intrinsically safe L/+ auxiliary power -O +O +O isolation switch amplifier intrinsically safe L/+ auxiliary power isolation amplifier intrinsically safe L/+ auxiliary power isolation amplifier intrinsically safe L/+ auxiliary power si g n a l 4..20mA relay output relay output mA mA si g n a l 4..20mA si g n a l 4..20mA relay output relay output mA si g n a l 4..20mA si g n a l 4..20mA page 9 of 28 transmitter electronic E mA mA transmitter electronic F / G / H +O isolation switch amplifier intrinsically safe L/+ auxiliary power isolation amplifier intrinsically safe 3 – wire – technology / signal 0...10 V / 2x PNP switching output Precont S transmitter electronic variant F/G/H in out in out -I -Vs 3 – wire – technology / signal 0...10 V Precont S transmitter electronic variant A +I +Vs auxiliary power si g n a l 4..20mA transmitter electronic A mA transmitter electronic B / C / D 2 – wire – technology / signal 4...20 mA / 2x PNP switching output Precont S transmitter electronic variant B/C/D 2 – wire – technology / signal 4...20 mA Electrical connection – connection in explosive hazardous areas Precont S – Precont D40 S1 S2 Control key „OK“ Control key „+ / -“ The counter advance sense is at first set to „+“ Î increasing of the displayed value. Press the control key „Change“ to change the counter advance sense to „-“ Î decreasing the displayed value page 10 of 28 By pushing of key combinations in the run mode the transmitter can be operated without using the adjustment menu. Zero value adjustment with applied pressure signal: Short pushing the key’s „Change“ and „OK“ in succession and hold approx. 6 seconds. The output signal 4mA / 0V is generated that can be varied by „+ / -“ resp. „Change“ and „+ / -“. By pushing the key „OK“, the current pressure value is captured as lower pressure reference value, assigned to the previously adjusted output signal and the changed settings are stored loss protected (duration approx. 3 s). A jump back to the run mode is carried out. End value adjustment with applied pressure signal: Short pushing the key’s „+ / -“ and „OK“ in succession and hold approx. 6 seconds. The output signal 20mA / 10V is generated that can be varied by „+ / -“ resp. „Change“ and „+ / -“. By pushing the key „OK“, the current pressure value is captured as upper pressure reference value, assigned to the previously adjusted output signal and the changed settings are stored loss protected (duration approx. 3 s). A jump back to the run mode is carried out. Damping adjustment: Short pushing the key’s „Change“ and „+ / - “ in succession and hold approx. 6 seconds. The damping value can now be varied. This value can be varied arbitrary by „+ / -“ resp. „Change“ and „+ / -“ from 0,3 to 30 seconds in 100 steps of each 0,3 seconds (variants C / G in 10 steps of each 3 seconds). By pushing the key „OK“, the value is captured and stored loss protected (duration approx. 3 s). A jump back to the run mode is carried out. Reset to factory values: At devices of variants C / G, a reset to factory values will be carried out by pushing the key „OK“ for approx. 5 seconds at a restart after removing the supply voltage. All customer specific adjustment values will be lost. Attention: If the lower pressure reference value (zero) is adjusted higher than the upper pressure reference value (span), the output signal falls below 3,8mA resp. to 0V. The display shows EEEE as long as the key „OK“ is pushed. A readjustment has to be done correctly (zero < span). Fast adjustment mode To access to the adjustment menu push the control key „OK“ and enter the password 3009. Programming mode The pressure transmitter records the applied system pressure and proceeds the chosen functions according to the set parameter. The measuring value is displayed in the display window. The analogue output and the switching outputs are driven, whereby an active switched-on switching output is signaled by the come on of the respective red switching condition light-emitting diode. The transgression of the frame specifications, abnormal behavior conditions or also device malfunctions are displayed by the display values EEEE resp. -EEE. By pushing the control key „+ / -“ the software version will be displayed run mode Function modes Control key „Change“ Also used for switchover the function of the control key „+/-“ Switching state indicator S1 and S2 Indication of the active switching output by the respective red LED Display window 4-digit Operation and display elements Precont S – Precont D40 MM 1202, 1252, 1322 AP ATEX-Version, Gas Tight 0870142930 / 190705 Equipment Documentation Measurement and Safety Instrumentation page 59 OK OK OK OK OK SP 1 SP 2 SAbG ErrS FrES SPEi Limit switch 1 Limit switch 2 Fast adjustment Behaviour output signal Reset to factory values Store OK OK OK OK diSP t_F OK OK SPAn 2Ero password 3009 Func n.o.n.c. OK HYS1 OK OK OK OK SP_1 SPAn OK OK FS22 oFF 25.12 OK OK oFF FS3.8 OK OK OK OK OK OK OK OK OK OK OK OK OK OK OK on ErrF n.c. norF n.o. 0.005 0.250 1 1.000 0.000 dP3 3 seconds 1.000 3 seconds 20..00 3 seconds 0.000 3 seconds 4.00 run mode OK 2Ero oSig OK OK dP-_ OK OK oSig NSig OK Password wrong pressed, the faster the value will increase or decrease. Function direction (higher or lower) can be changed by the key „Change“. Pressing this key in the run mode will display the software version Jump from menu to menu / changing the direction of the „+/-„ key / changing between the different possibilities in selection menu Enter the respective submenu and capturing the set values +- Change the indicated values. The longer the key will be OK Î S1 switches on at transgression of the limit value Î S1 switches on at underrun of the limit value Func is not available. Loss protected storage of all parameters (duration approx. 7 s) Store Reset of all parameters to factory values. Customer specific settings will be lost. Factory-Reset page 11 of 28 A signal besides these limits is not possible. The end values are kept at transgression. A error current output at transgression or underrun is not generated. oFF = The output signal operates linear in the range from 3,9...21,0 mA resp. 0...10,5 V. At transgression of this range a constant signal of 22 mA / 11,25 V is generated. FS22 = The output signal operates linear in the range from 4,0...20,0 mA resp. 0...10 V. At transgression of this range a constant signal of 3,8 mA / 0 V is generated. Behaviour of the output signal at signal range transgression FS3.8 = The output signal operates linear in the range from 4,0...20,0 mA resp. 0...10 V. Unlock or lock of fast adjustment for the lower and upper pressure reference value with applied signal as well as setting the damping per key combinations. Fast adjustment per key combinations This menu is identical to the menu switch point 1 with the exception that the submenu Limit switch 2 lower than 4mA/0V. Function limit switch 1 norF = limit value function with hysteresis ErrF = error indication function Î S1 switches, if the output signal become higher than 20mA/10V resp. Operation mode limit switch 1 n.o. = normally open = working current principle n.c. = normally closed = quiescent current principle Switch point hysteresis of switch point S1 referring to the display value Hysteresis limit switch 1 Display value, where the PNP switching output S1 will be activated. Limit value limit switch 1 Setting the system damping for neutralization of short pressure blows or also for calming down cyclic fluctuating pressure signals. The adjustment range is 0,3...30 seconds, in 100 steps of each 0,3 seconds. System damping indication value at 20 mA / 10 V output signal. If the displayed value rises above 9999, EEEE is displayed. Display end value scaling indication value at 4 mA / 0 V output signal. If the displayed value falls below -999, -EEE is displayed. Display zero value scaling Decimal places setting dP0 display 8888. / setting dP1 display 888.8 setting dP2 display 88.88 / setting dP3 display 8.888 adjust upper pressure reference signal, referring to the nominal sensor pressure, with „+“ resp. „-“ to the value that should be assigned to the output signal of 20,00 mA or resp. 10V. Set with „OK“, cancel by pressing „Change“ for 3 seconds. Adjustment upper pressure reference value without applied signal Current pressure signal is assigned as the upper pressure signal to the displayed and by „+“ resp. „-“ adjustable output signal (output mA resp. V). Set with „OK“, cancel by pressing „Change“ for 3 seconds. At the signal 0...10V the value of 4.00 equals a voltage of 0V and a value of 20.00 equals a voltage of 10V Adjustment of upper pressure reference value with applied signal adjust lower pressure reference signal, referring to the nominal sensor pressure, with „+“ resp. „-“ to the value that should be assigned to the output signal of 4,00 mA or resp. 0V. Set with „OK“, cancel by pressing „Change“ for 3 seconds. Adjustment lower pressure reference value without applied signal Current pressure signal is assigned as the lower pressure signal to the displayed and by „+“ resp. „-“ adjustable output signal (output mA resp. V). Set with „OK“, cancel by pressing „Change“ for 3 seconds. At the signal 0...10V the value of 4.00 equals a voltage of 0V and a value of 20.00 equals a voltage of 10V Adjustment of lower pressure reference value with applied signal Input password 3009 Entry to code-inquiry Indication of current measurement value run mode NSig NESS EEEE OK 0000 System damping Display Adjustment upper pressure reference signal Adjustment lower pressure reference signal Passwort right OK OK codE OK 25.12 Adjustment menu Precont S – Precont D40 at set system damping 1 2) Referring to nominal measuring span resp. full scale (FS) page 12 of 28 at set system damping 1 ≥ 100.000.000 ≤ 330 ms (typ. 280 ms) Delay time: Switching cycles: ≤ 700 μs Rise up time: current limited, short circuit protected output load ≤ 3000 Ω resp. ≥ 4,5 mA ≤ 250 mA, min. 200 mA VOUT ≥ +Vs – 2 V at set system damping 1 Output current: PNP switching to +Vs Output voltage: ≤ ±0,02% FS 2) / 10V ≤ 310 ms (typ. 260 ms) ≤ 0,5 mV RL ≥ 2000 Ω, results in 5 mA at signal 10 V, current limited linear characteristic from ≤ 0,07...10,5 V, error ≤ 0,07 V / 11,25 V inverted output characteristic 10...0 V only possible by manufacturer on separate request ≤ ±0,02% FS 2) / 10V Function: PNP switching output Influence of supply voltage: Minimum delay time: Resolution: Permitted load: Signal range: Analogue output 0...10 V Influence of supply voltage: ≤ 1 μA ≤ 310 ms (typ. 260 ms) Minimum delay time: linear characteristic from 3,9 mA resp. 21 mA, error 3,8 mA / 22 mA inverted output characteristic 20...4 mA only possible by manufacturer on separate request RL max = (VS act - VS min) / 20mA VS min = 10,5 / 12,5 / 14,5 / 16,5 V 2-wire 4...20 mA 3-wire 0...10 V Resolution: Permitted load: Signal range: Analogue output 4...20 mA Supply current: ≤ 2 VPP Ripple voltage: condition: within the permitted supply voltage range ≤ 22 mA PNP switching outputs no load ≤ 10 mA PNP switching outputs no load reverse polarity protected Precont S Variant A/B/E/F/G/H 14,5..45 V DC / Ex 14,5..27,3V Variant C/D 10,5..45 V DC / Ex 10,5..27,3V Precont D40 Variant A/B/E/F/G/H 16,5..45 V DC Variant C/D 12,5..45 V DC Permitted supply voltage: Auxiliary supply Technical data Precont S – Precont D40 MM 1202, 1252, 1322 AP ATEX-Version, Gas Tight 0870142930 / 190705 Equipment Documentation Measurement and Safety Instrumentation page 60 7) 6) 5) 4) 3) 2) not cumulative 2) ≤ ±0,2% FS 2) / 10 K Tk4) Span besides 0...+80°C with factor 2 for Tk metallic membrane Tk4) Zero ≤ ±0,2% FS 2) / 10 K (≤ 25 bar) range 0..0,4 bar ≤ ±0,25% FS 2) / 10 K range 0..0,25 bar ≤ ±0,4% FS 2) / 10 K range 0..0,1 bar ≤ ±1,0% FS 2) / 10 K 4) metallic membrane Tk Zero ≤ ±0,2% FS / 10 K (≥ 40 bar) Tk4) Span ≤ ±0,2% FS 2) / 10 K besides -40...+100°C with factor 2 for Tk ≤ ±0,20% FS 2) / 10 K Tk4) Span max. ≤ ±1,0 % FS 2) (-20...+80°C) besides -20...+80°C with factor 2 for Tk ceramic membrane Tk4) Zero ≤ ±0,20% FS 2) / 10 K Precont D40) max. ≤ ±1,5 % FS 2) (-20...+80°C) ≤ ±0,10% FS 2) / 10 K Tk4) Span max. ≤ ±0,5 % FS 2) (-20...+80°C) max. ≤ ±0,8 % FS 2) (-20...+80°C) ≤ 0..0,4 bar besides -20...+80°C with factor 2 for Tk ceramic membrane Tk4) Zero ≤ ±0,10% FS 2) / 10 K (Precont S) max. ≤ ±0,75 % FS 2) (-20...+80°C) not cumulative ceramic membrane ≤ ±0,1% FS 2) / year metallic membrane ≤ ±0,15% FS 2) / year metallic membrane ≤ ±0,1% FS 2) metallic membrane ≤ ±0,6% FS 2) at pressure range 0..0,1 / 0,25 bar ceramic membrane negligible metallic membrane ≤ ±0,3% FS 2) ceramic membrane ≤ ±0,1% / 0,2% FS 2) metallic membrane ≤ ±1,0% FS 2) at pressure range 0..0,1 / 0,25 bar metallic membrane ≤ ±0,5% FS 2) ceramic membrane ≤ ±0,1% / 0,2% FS 2) page 13 of 28 Referring to nominal measuring span resp. full scale (FS) Nonlinearity + Hysteresis + Reproducibility Tk = Temperature coefficient At limit value adjustment Specification valid, if adjusted measuring range = nominal measuring range, i.e. for TD 7) = 1 At TD 7) ≥ 1 (adjusted measuring range ≤ nominal measuring range): Specification at adjusted measuring range = specification at nominal measuring range x TD 7) Turn-Down TD = nominal measuring range (FS 2)) / adjusted measuring range) Temperature deviation 6): Long term drift 6): Hysteresis 6): Nonlinearity : 6) Characteristic deviation 3) 5) 6): Measuring accuracy Technical data Precont S – Precont D40 Reference conditions: page 14 of 28 at process connections with screw-in thread DIN EN 60592 IP65 at Ex variant DIN EN 60721-3 5 - 100 Hz DIN EN 61326 operation device class B DIN EN 61326 appendix A (industrial range) T = 15...35 °C, relative humidity 45...75 %, environmental air pressure 860...1060 kPa ≤ 50 Nm IP67 4K4H 4g emission immunity DIN IEC 60770 Torque strength: Protection classification: Climatic classification: Vibration classification: EM – compatibility: Weight: Vacuum strength: Overload strength: Precont S20 synthetic oil ranges ≤ 0...25 bar Precont S30 synthetic oil FDA listed Precont S60 vegetable oil food applications Precont S70 silicone oil / high temperature oil depends on membrane resp. measuring range, see table overload / burst pressure 0 mbarabs Ceramic membrane –0,1...0 bar resp. 0...0,1 bar Î 700mbarabs Ceramic membrane –0,1...+0,1 bar / 0...0,2 bar Î 500mbarabs depends on variant Pressure transmitting liquid: Î FPM – fluorelastomere (Viton®) EPDM – etylene-propylene-dienmonomere CR – chloroprene-rubber (Neopren®) FFKM – perfluorelastomere (Kalrez®) NBR – nitril-butadien-rubber Î FPM – fluorelastomere (Viton®) Silicone – 40°C...+85°C, limitation at Ex variants depends on variant, maximum – 40°C...+370°C depends on variant, maximum – 1 bar...1000 bar, relative or absolute others medium contact PC – polycarbonate (Makrolon®) socket CrNi-steel, insert PUR, contacts gold-plated PE – polyethylene housing PA – polyamide, gasket CR / NBR housing PA – polyamide, membrane ePTFE PES – polyester ceramic AL2O3 96% resp. 99,9% steel V4A steel 1.4404 (AISI 316L) steel 1.4404 (AISI 316L) / steel 1.4571 (AISI 316Ti) Precont S20 / S30 steel V4A Precont S60 / S70 steel 1.4404 / 1.4435 (AISI 316L) CrNi-steel / PBT polybutyleneterephthalat / PP – polypropylene / POM – polyoxymethylene (Delrin®) Precont S10 / S40 / D40 Precont S20 / S30 Precont S60 / S70 Precont S10 / S40 / D40 Environmental temperature: Process temperatures: Process pressure ranges: Environmental conditions Gaskets: Display window: Device plug M12x1: Connection cable: Cable gland: Pressure compens. element: Membrane keyboard: Connection housing: Process connection: (medium contact) Membrane: (medium contact) Materials Technical data Precont S – Precont D40 MM 1202, 1252, 1322 AP ATEX-Version, Gas Tight 0870142930 / 190705 Equipment Documentation Measurement and Safety Instrumentation page 61 Dimension drawings Precont S10 page 15 of 28 Precont S – Precont D40 signal 4...20 mA signal 4...20 mA signal 4...20 mA signal 4...20 mA signal 0...10 V signal 0...10 V signal 0...10 V signal 0...10 V manometer connection inside drill 11,4 mm manometer connection only with material connection housing type C - steel 2x PNP switching output LED display, 3 key’s LED display, 3 key’s 3 key’s fix adjusted 2x PNP switching output LED display, 3 key’s LED display, 3 key’s 3 key’s fix adjusted DIN EN 837-3 DIN EN 837-3 10 11 12 13 14 15 16 17 18 YY -40°C to +100°C -40°C to +125°C with temperature decoupler Precont _ _ _ V _ _ _ _ _ _ _ Electrical connection: S Plug M12x1 K Cable 2m A Terminal box page 16 of 28 Accuracy measuring system – variant measuring membrane (medium contact): 2 0,2% ceramic AL2O3 96% 1 0,2% ceramic AL2O3 99,9% (highly clean) 0 0,1% Linearization protocol ceramic AL2O3 96% 3 0,1% Linearization protocol ceramic AL2O3 99,9% (highly clean) Pressure type: R Relative pressure A Absolute pressure Process temperature: 0 Standard 1 Extended for gas applications for food applications 0...10 bar 0...16 bar 0...20 bar 0...40 bar 0...60 bar -0,1...0 bar -1...0 bar -1...+1 bar -0,1...+0,1 bar special measuring range separate spec. necessary not for electrical connection type S / K not for electrical connection type S / K not for electrical connection type A Gaskets (medium contact): 1 FPM fluorelastomere (Viton®) 2 CR chloroprene-rubber (Neopren®) 3 EPDM etylene-propylene-dienmonomere 4 FFKM perfluorelastomere (Kalrez®) 6 FFKM perfluorelastomere high density Measuring range: 01 0...0,1 bar 02 0...0,2 bar 03 0...0,4 bar 04 0...0,6 bar 05 0...1 bar 06 0...1,6 bar 07 0...2,5 bar 08 0...4 bar 09 0...6 bar Material connection housing: A PBT – polybutyleneterephthalat C CrNi-steel D PP – polypropylene E POM – polyoxymethylene (Delrin®) Material process connection (medium contact): V Steel 1.4404 (AISI 316L) / 1.4571 (AISI 316Ti) Electronic - output: A 2-wire-technology B 2-wire-technology C 2-wire-technology D 2-wire-technology E 3-wire-technology F 3-wire-technology G 3-wire-technology H 3-wire-technology Process connection: 0 G ½“ A DIN EN ISO288-1 6 G ½“ A DIN EN ISO288-1 1 G ¼“ A DIN EN ISO288-1 Standard ATEX II 1/2 G EEx ia IIC T4 ATEX II 1/2 GD EEx ia IIC T4 IP65 Digital pressure transmitter with inside placed ceramic capacitive membrane from –1 to 60 bar analogue output 4...20mA resp. 0...10V, 4-digit LED display, 2 switching outputs Type: S10 ExS10 XDS10 Precont S10 Order code overview Precont S10 Precont S – Precont D40 MM 1202, 1252, 1322 AP ATEX-Version, Gas Tight 0870142930 / 190705 Equipment Documentation Measurement and Safety Instrumentation page 62 MM 1202, 1252, 1322 AP ATEX-Version, Gas Tight 0870142930 / 190705 Equipment Documentation Measurement and Safety Instrumentation page 63 MM 1202, 1252, 1322 AP ATEX-Version, Gas Tight 0870142930 / 190705 Equipment Documentation Measurement and Safety Instrumentation page 64 Technical Data 60 50 MM 1252 AP 60 50 MM 1322 AP 60 5.5 1.2 7.5 2.0 11 0.7 7.5 1.0 8.6 1.8 12.6 2.0 17.3 0.9 7.5 1.6 11 2.0 15 0.7 8.6 1.4 12.6 2.0 17.3 1.0 11 1.7 15 2.0 18.5 0.8 12.6 1.5 17.3 2.0 21.3 3000 200 80 3600 240 83 3000 250 81 ~270 ... 350 3600 300 84 3000 300 82 3600 360 85 b ra ien ng t t e em [° p Am C] era tu bi re en tp re ss ur e Am atmospheric MM 1202 AP 0.7 0 ... 40 50 Ul tim [b ate ar (g wo )] rk in No g pr m es [k ina su W lm re ] * ot or No ra tin m g [m ina in -1 l sp ee ] d No m [m ina ³/ l fl h] ow So un (E d p N re m ISO ssu ea 2 re s 1 [d ure 51 leve b( d ) w l A) at ] +0 ith s W .7 ile eig ba nc [k ht r g er, g] Type Fr eq [H uen z] cy Ex-classification, permitted ultimate pressures, shut-off temperatures and motor connection parameters see nameplates *valid ultimate working pressure see nameplate **may vary depending on specific order MM 1202, 1252, 1322 AP ATEX-Version, Gas Tight 0870142930 / 190705 Technical Data page 65 MM 1202, 1252, 1322 AP ATEX-Version, Gas Tight 0870142930 / 190705 page 66 MM 1202, 1252, 1322 AP ATEX-Version, Gas Tight 0870142930 / 190705 page 67 Busch – All over the World in Industry Australia Busch Australia Pty. Ltd. 30 Lakeside Drive Broadmeadows, Vic. 3047 Tel: (03) 93 55 06 00 Fax: (03) 93 55 06 99 Austria Busch Austria GmbH Industriepark Nord 2100 Korneuburg Tel: 02262 / 756 65-0 Fax: 02262 / 756 65-20 Belgium Busch N.V./Busch SA Kruinstraat 7 9160 Lokeren Tel: (0)9 / 348 47 22 Fax: (0)9 / 348 65 35 Brazil Busch do Brasil Ltda. Rod. Edgard Máximo Zambotto, Km 64 13240-000 Jarinu-SP Tel: (55) 11-4016 1400/5277 Fax: (55) 11-4016 5399 Canada Busch Vacuum Technics Inc. 1740, Boulevard Lionel Bertrand Boisbriand (Montréal) Québec J7H 1N7 Tel: 450 435 6899 Fax: 450 430 5132 Chile Busch Chile S. A. Calle El Roble N° 375-G Lampa - Santiago Tel: (56-2) 7387092 Fax: (56-2) 7387092 China Busch Vacuum (Shanghai) Co., Ltd No.5, Lane 195 Xipu Road Songjiang Industrial Estate East New Zone Shanghai 201611 PRC Tel: +86 (0)21 67600800 Fax: +86 (0)21 67600700 Czech Republic Busch Vakuum s.r.o. Praákova 10 619 00 Horní Heršpice Brno Tel: +420 543 42 48 55 Fax: +420 543 42 48 56 Denmark Busch Vakuumteknik A/S Parallelvej 11 8680 Ry Tel: +45 87 88 07 77 Fax: +45 87 88 07 88 Finland Busch Vakuumteknik Oy Sinikellontie 4 01300 VANTAA Tel: 09 774 60 60 Fax: 09 774 60 666 France Busch France S.A. Parc Technologique de Bois Chaland CE 2922 91029 Evry Cedex Tel: 01 69 89 89 89 Fax: 01 60 86 16 74 Germany Dr.-Ing. K. Busch GmbH Schauinslandstr. 1 79689 Maulburg Tel: (0 76 22) 6 81-0 Fax: (0 76 22) 6 81-194 e-mail: [email protected] Dr.-Ing. K. Busch GmbH Niederlassung Nord Ernst-Abbe-Str. 1-3 25451 Quickborn Tel: (0 41 06) 7 99 67-0 Fax: (0 41 06) 7 99 67-77 Dr.-Ing. K. Busch GmbH Niederlassung West Nordring 35 64807 Dieburg Tel: (0 60 71) 92 82-0 Fax: (0 60 71) 14 71 Dr.-Ing. K. Busch GmbH Außenstelle Neuenrade Breslauer Str. 36 58809 Neuenrade Tel: (0 23 92) 50 29 92 Fax: (0 23 92) 50 72 11 Dr.-Ing. K. Busch GmbH Niederlassung Süd-Ost Gewerbestraße 3 90579 Langenzenn Tel: (0 91 01) 90 25-0 Fax: (0 91 01) 90 25-25 Dr.-Ing. K. Busch GmbH Außenstelle Zella-Mehlis Am Rain 11 98544 Zella-Mehlis Tel: (0 36 82) 46 92 71 Fax: (0 36 82) 46 92 73 Dr.-Ing. K. Busch GmbH Außenstelle Meitingen-Ostendorf Grüntenweg 8 86405 Meitingen-Ostendorf Tel: (0 82 71) 426-341 Fax: (0 82 71) 426-342 India Busch Vacuum India Pvt Ltd. Plot No. 110, Sector 7 PCNTDA, Bhosari Pune 411026, Maharashtra Tel: (0)206410 2886 Fax: (0)202711 2838 Ireland Busch Ireland Ltd. A10-11 Howth Junction Business Centre Kilbarrack, Dublin 5 Tel: 00353 1 832 1466 Fax: 00353 1 832 1470 Israel Busch Israel Ltd. 1 Mevo Sivan Street Qiryat Gat 82022, Israel Tel: +972 (0)8 6810485 Fax +972 (0)8 6810486 Italy Busch Italia S.r.l. Via Ettore Majorana, 16 20054 Nova Milanese Tel: 0362 370 91 Fax: 0362 370 999 Japan Nippon Busch K.K. 1-23-33, Megumigaoka Hiratsuka City, Kanagawa Japan 259-1220 Tel: 0463-50-4000 Fax: 0463-50-4004 Korea Busch Korea Ltd. 392-1 Yangji-Ri, Yangji-Myun, Yongin-si, Kyunggi-Do Tel: 031) 321-8114 Fax: 031) 321 4330 Malaysia Busch (Malaysia) Sdn Bhd. 6 Jalan Taboh 33/22 Shah Alam Technology Park Section 33 40400 Shah Alam Selangor D. E. Tel: 03 5122 2128 Fax 03 5122 2108 Mexico Busch Vacuum Mexico S de RL de CV Tlaquepaque 4865, Los Altos Monterrey, Nuevo Leon Mexico 64370 Tel: (81) 8311-1385 Fax: (81) 8311-1386 Netherlands Busch B.V. Pompmolenlaan 2 3447 GK Woerden Postbus 2091 3440 DB Woerden Tel: (0)348 - 462300 Fax: (0)348 - 422939 New Zealand Busch New Zealand Ltd. Unit D, 41 Arrenway Drive Albany 0632 Auckland Tel: 09 414 7782 Fax: 09 414 7783 MM 1202, 1252, 1322 AP ATEX-Version, Gas Tight 0870142930 / 190705 www.buschvacuum.com Norway Busch Vakuumteknikk AS Hestehagen 2 1440 Drøbak Tel: 64 98 98 50 Fax: 64 93 66 21 Poland Busch Polska Sp. z o.o. Ul. Chopina 27 87800 W»oc»awek Tel: (054) 2315400 Fax: (054) 2327076 Portugal Busch lbérica S.A., Sucursal em Portugal Zona Industrial Raso de Travassô, Fracção B, Armazém 2 3750-753 Agueda Aveiro, Portugal Tel: +351 234 648 070 Fax: +351 234 648 068 Russia Busch Vacuum Russia OOO Kotlyakovskaya str., 6/9 115201 Moscow Tel: +7 495 6486726 Fax: +7 495 6486724 Singapore Busch Vacuum Singapore Pte Ltd 20 Shaw Road #01-03 Ching Shine Building Singapore 36 79 56 Tel: (65) 6488 0866 Fax: (65) 6288 0877 Spain Busch Ibérica S.A. C/ Jaume Ferran, 6-8 Pol. Ind. Coll de la Manya 08403 Granollers Tel: +34 93 861 61 60 Fax: +34 93 840 91 56 Sweden Busch Vakuumteknik AB Bråta Industriområde 435 33 Mölnlycke Tel: 031 - 338 00 80 Fax: 031 - 338 00 89 Switzerland Busch AG Waldweg 22 4312 Magden Tel: 061 / 845 90 90 Fax: 061 / 845 90 99 Taiwan Busch Taiwan Corporation 1F. No. 69, Sec. 3, Beishen Rd. Shenkeng Township, Taipei Country, Taiwan (222), R.O.C Tel: (02) 2662 0775 Fax: (02) 2662 0796 Thailand Busch Vacuum (Thailand) Co., Ltd. 888/30 Moo19, Soi Yingcharoen, Bangplee-Tamru Rd., Bangpleeyai, Bangplee, Samutprakarn 10540 Thailand Tel: (66) 2-382-5428 Fax: (66) 2-382-5429 Turkey VAKUTEK Emlak Kredi Ishani No: 179 81130 Üsküdar-Istanbul Tel: (216) 310 0573 Fax: (216) 343 5126 United Kingdom Busch (UK) Ltd Hortonwood 30-35 Telford Shropshire TF1 7YB Tel: 01952 677 432 Fax: 01952 677 423 USA Busch, Inc. 516-B Viking Drive Virginia Beach, VA 23452 Tel: (757) 463-7800 Fax: (757) 463 7407 Semiconductor Vacuum Group Inc. Morgan Hill, CA 95037 Tel: (408) 955 1900 Fax: (408) 955 0229 Busch – All over the World in Industry page 68
advertisement
* Your assessment is very important for improving the workof artificial intelligence, which forms the content of this project
Related manuals
advertisement
Table of contents
- 2 Preface
- 3 Product Description
- 5 Safety Concept
- 5 Operational Options / Use of Optionally Available Equipment
- 5 Principle of Operation
- 5 Cooling
- 5 Start Controls
- 5 Safety
- 5 Intended Use
- 5 Safety Notes
- 5 Noise Emission
- 6 Transport
- 6 Transport in Packaging
- 6 Transport without Packaging
- 6 Storage
- 6 Short-term Storage
- 6 Conservation
- 6 Installation and Commissioning
- 6 Installation Prerequisites
- 6 Mounting Position and Space
- 7 Gas Inlet
- 7 Pressure Connection
- 7 Electrical Connection / Controls
- 8 Installation
- 8 Mounting
- 8 Checking Synchronising Gear Oil
- 8 Connecting Electrically
- 9 Connecting Lines/Pipes
- 9 mentation
- 9 Recording of Operational Parameters
- 10 Operation Notes
- 11 Conveying Condensable Vapours
- 12 Maintenance
- 12 Maintenance Schedule
- 12 Monthly
- 12 Every 3 Months
- 12 Every 6 Months
- 13 Every Year
- 14 Overhaul
- 14 Removal from Service
- 14 Temporary Removal from Service
- 14 Recommissioning
- 15 Dismantling and Disposal
- 16 Troubleshooting
- 19 Spare Parts
- 21 Overview
- 21 Version with Resistance Thermometer and Transmitter
- 22 Pressure Switch/Indicator