Nordyne M3RL 080A AW Installation Instructions Manual

Add to My manuals
36 Pages

advertisement

Nordyne M3RL 080A AW Installation Instructions Manual | Manualzz

Direct Vent (Sealed Combustion) Forced Air Gas Furnaces

M3RL Series 90+ Downflow Condensing Furnace

For installation in:

1. Manufactured Homes

2. Park Models and Manufactured Buildings

3. Modular Homes/Buildings

WARNING:

FIRE OR EXPLOSION HAZARD

Failure to follow safety warnings exactly could

result in serious injury, death or property damage.

- Do not store or use gasoline or other flammable vapors and liquids in the vicinity of this or any other appliance.

-WHAT TO DO IF YOU SMELL GAS

• Do not try to light any appliance.

• Do not touch any electrical switch; do not use any phone in your building.

• Leave the building immediately.

• Immediately call yourgas supplierfrom a neighbor's phone. Follow the gas supplier's instructions.

• If you cannot reach your gas supplier, call the fire department.

-Installation and service must be performed by a qualified installer, service agency, or the gas supplier

J

BW Models

BWT Models

J

ADVERTISSEMENT:

RISQUE D'INCENDIE OU D'EXPLOSION

Le non=respect des avertissements de securite pourrait entrainer des blessures graves, la mort ou des dommages materiels.

- Ne pas entreposer ni utiliser de I'essence ni d'autres vapeurs ou liquides inflammables dans le voisinage de cet appareil, ni de tout autre appareil.

-QUE FAIRE S'ILYA UNE ODEUR DE GAZ

• Ne pas tenter d'allumer aucun appareil.

• Ne toucher a aucun interrupteur electrique; n'utiliser aucun t61ephone dans le b_timent.

€:vacuer I'immeuble immediatement.

• Appeler immediatement le fournisseur de gaz en employant le tel6phone d'un voisin. Respecter la lettre les instructions du fournisseur de gaz.

• Si personne ne repond, appeler le service des incendies.

-L'installation et I'entretien doivent Ctre effectues par un installateur qualifie, un organisme de service ou le fournisseur de gaz.

WARNING:

Should overheating occur, or the gas supply fail to shut off, shut off the manual gas valve to the appliance before shutting off the electrical supply.

Improper installation, adjustment, alteration, service or maintenance can cause injury or property damage.

Refer to this manual.

For assistance or additional information consult a qualified installer, service agency or the gas supplier.

LEAVE THESE INSTRUCTIONS WITH THE HOMEOWNER.

2

TABLE OF CONTENTS

General ......................................................

4

Unit Dimensions ..................................

4

Shipping Weights ................................

4

Furnace Specification ........................

4

Air Flow Data .....................................

4

Owner's information ................................

5 installation Requirements ......................

6

Location ..............................................

8

Clearance ...........................................

8

Circulating Air Supply ..........................

10

Return Air Provisions ............................

10

Air Distribution Systems ......................

11

Duct Connector Selection ....................

11

Duct installation ....................................

12

Venting and Combustion

Air Requirements ..........................

14

Venting Requirements ..........................

14

Vent Table ........................................

15

Vent Pipe Material ............................

16

Vent Pipe Length and Diameter ....... 16

Vent Pipe installation ........................

16

Pipe Routing & Support ....................

16

Location of Outdoor Termination ..... 18

Horizontal Venting ............................

18

Vertical Venting ................................

19

Vent Freezing Protection .................

19

Concentric Vent Termination ........... 20

Drainage of Condensate

From Furnace ................................

20

Gas Supply and Piping .........................

21

Leak Check ......................................

22

High Altitude Derate .........................

22

Pressure Switch ...............................

22

Conversion .............................................

22

Lighting and Adjustment

of the Appliance ............................

24

Electrical Wiring .....................................

24

Line Voltage Wiring ..........................

25

Low Voltage Wiring ..........................

26

Ventilation ...............................................

26

Start-up and Adjustment .....................

26

Start-Up Procedure .........................

26

Shut Down Procedure .....................

27

Verifying and Adjusting Firing Rate.

27

Temperature Rise ............................

27

Verifying and Adjusting

Verifying Burner Operation .............. 28

Verifying Operation of the

Supply Air Limit Switch .................

28

Description of Components ................ 29

Furnace Accessories .............................

29

Maintenance ...........................................

29

Combustion Air and Vent System .... 29

Air Filter(s) .......................................

29

Lubrication ........................................

30

Condensate Drain Assembly ........... 30

Blower Compartment .......................

30

Heat Exchanger and Burner

Maintenance ..................................

30

System Operation Information ............. 30

Sequence of Operation ....................

30

Furnace Fails to Operate .................

31

Component Location ............................

32

Wiring Diagram .......................................

33

Installation/Performance

Checklist .........................................

35

Application

M-Manufactured Home

Furnace Series

Comfort Model

RL - Condensing Downflow

M3RL-060A-A

Heating Capacity input, BTUH (000')

Table 1. Model Identification

W

L

LReturn Air

BlankFront

Configuration

T - Top

Door Color

W - White

G - Gray

Cabinet Dimensions

A - 56"x 19-3/4" x 23-3/4"

B - w/Coil Cavity,

76" x 19-3/4" x 23-3/4"

Electrical Code

A - 1PH, 60 Hz, 120 VAC

3

GENERAL

-19-7/8 --

--3-17/32

COMBUSTION

--1-11/16

EXHAUST

VENT

AIR INTAKE

16

--3-17/32

COMBUSTION

--1-11/16

EXHAUST

VENT

AIR INTAKE

"\

/

SIDE RETURN

/\

KNOCKOUTS

L--- ......_

m

7/3243.

I12

27-25/32

"B" Cabinet

Figure 1.

Furnace Dimensions

"A" Cabinet

_

Top Return Knockouts

Y

Top View

(AW and BW Models)

_

1,000

:

I

_ 12.000

21.000

Top Returrl

(BWT

(

Opening

Models)

21-15/16--

Furnace Model

M3RL 060A AW

M3RL 060A BW*

M3RL 080A AW

M3RL 080A BW*

Shipping

Weight

(Ibs)

150

170

155

175

* May include suffix - T

Table 2.

Shipping Weight

Furnace Specifications / Airflow Data

Furnace rVlodel No.

M3 RL-060

M3 RL-080

Furnace

Input

Btuh

60,000

80,000

Furnace

Output

Btuh

54,000

72,000

Temp.

Rise @ Motor Motor

.3"WC °F HP

35 - 65 1/2

Speed

High*

Med-High

Med-Low

Low**

High*

35 - 65 1/2 Med-High

Med-Low**

Low**

External Static Pressure ( Inches Water Column)

0.1

0.2

0.3

0.4

0.5

CFM

CFM

1660

CFM

1599

CFM

1544

CFM

1474 1410

1512

1340

1467

1304

1416

1261

1363

1217

1304

1158

1176

1660

1142

1599

1108

1544

1025

1474

966

1410

1512

1340

1176

1467

1304

1142

1416

1261

1108

1363

1217

1025

1304

1158

966

Note: Data is for Operation with Filter.

* Factory Wired Cooling Tap

• * Factory Wired Heating Tap

Table 3.

Furnace Specifications/Airflow Data

4

Recommended

A/C

Ton

4

3

2.-1/2

2

4

3

2.-1/2

2

/ WARNING:

Do not use this appliance if any part has been submerged underwater, immediately call a qualified service technician to inspect the appliance and to replace any part of the control system and any gas control that has been submerged underwater,

NOTICE TO INSTALLER

Installer is advised to follow carefully all instruc- tions and warnings in this manual to insure maximum performance, safety, and operating efficiency of these appliances.

Improper installation may create hazardous conditions, and will void the appliance warranty.

GENERAL

General Description

The M3 series gas furnaces are listed direct vent (sealed combustion) forced air furnaces for use with both natural and propane gases.

The M3 series is a Category IV and type FSP furnace.

The M3 furnace series has been certified to the ANSI Z21.47/CSA2.3-2001 for use in the United States and Canada and to the

UL307B --1995 for use in the United States.

These furnaces may be installed in:

1. Manufactured Homes.

2. Park Models and Manufactured buildings

3. Modular Homes/Buildings

The following are safety guidelines with references to their specific sections or pages in the manual.

1.

Use only type of gas approved for this furnace.

Refer to the furnace rating plate.

2.

Install this furnace only in location and position as specified in pages 8 - 14 of these instructions.

3.

Provide adequate combustion and ventilation air to the furnace space as specified in pages 13 - 20 of these instructions.

4.

Combustion products must be discharged outdoors, connect this furnace to an approved vent system only, as specified in pages 14-20 of these instructions.

5.

Never test for gas leaks with an open flame. Use a commercially available soap solution made specifically for the detection of leak to check all connections.

6.

Always install furnace to operate within the furnace's intended temperature rise range with a duct system that has an external static pressure within the allowable range, as specified in page 4 of these instructions. See Table 3 and the furnace rating plate.

7.

When a furnace is installed so that supply ducts carry air circulated by the furnace to areas outside the space containing the furnace, the return air shall also be handled by duct(s) sealed to the furnace casing and terminating outside the space containing the furnace.

Note: This section only applies to furnaces installed with side or top return air.

8.

A gas4ired furnace for installation in a residential garage must be installed as specified in page 9 of these instructions.

9.

The furnace is not to be used for temporary heat of buildings or structures under construction.

M3 series furnaces are air conditioning ready as shipped. The furnace cooling capacities of the blower motor speed taps are shown in

Table 3. Table 2 lists the shipping weights for the M3 series furnaces.

OWNER INFORMATION

NORDYNE has been involved in the design of products for the manufactured home industry since the first manufactured home or trailer was built.

NORDYNE originated the sealed combustion system, which separates the furnace com= bustion system from the living area of the home, now a standard for the manufactured home industry.

NORDYNE engineers developed the first central heating system and the first central air conditioner for manufactured homes.

NORDYNE is dedicated to bringing to its cus= tomers the finest heating and cooling comfort possible.

NORDYNE constantly seeks to fur= ther refine its products to continuously provide exceptional comfort.

Followthe instructionsinthis bookletcarefully andthis appliancewill providemanyyearsof superiorperformance.

If you wish to coolyour homeautomatically with a centralair conditioningsysteminvestiavailablefromyour heatingand coolingcontractor.Thesesystemsare designedto work bestwith your NORDYNEfurnaceand have beencarefullyengineeredto deliveroptimum performancewhen mated with NORDYNE manufacturedhomefurnaces.

6.

Providing instructional training on how to light and operate the furnace.

7.

Furnace problems caused by installation of an air conditioner, heat pump or other air comfort devices.

8.

Revising installation of the furnace flue assembly.

9.

Adjusting or calibrating of thermostat.

10. Any construction debris which falls into the flue system.

Carefully review these responsibilities with your manufactured housing dealer, service company or gas supplier so there will be no misunderstanding at a later time.

and ventilatingsystemsspecificallydesigned

CAUTION: with your manufacturedhomeretailer,your heating and cooling contractor or your factory8000PhoenixParkway,O'Fallon,MO

63368ifyouarenotabletolocateasourcefor yourarea.

MANUFACTURER WARRANTY,

RESPONSIBILITIES

OWNER'S

It is the sole responsibility of the homeowner to make certain the gas furnace has been correctly set up and converted to the proper fuel (L.P. gas or Natural gas) and adjusted to operate properly. All gas furnaces are manufactured for

Natural gas and must be field converted when using LP. gas.

• Never attempt to alter or modify this furnace or any of its components.

• Never attempt to repair damaged or

inoperable components.

Such action could cause unsafe operation, ex-

plosion, fire and/or asphyxiation.

• If a malfunction has occurred, or if you feel that the furnace is not operating as it should, contact a qualified service agency or gas utility for assistance.

INSTALLATION STANDARDS

A warranty certificate with full details is included with these instructions.

However, NORDYNE will not be responsible for any costs found necessary to correct problems due to improper setup, improper installation, furnace adjustments, improper operating procedure on the part of the user, etc.

Some specific examples of service calls which cannot be included in warranty payments are:

1.

Converting the furnace to use another type of gas.

2.

Repairing ductwork in the home found to be faulty.

3.

Correcting wiring problems in the electrical circuit supplying the furnace.

4.

Resetting circuit breakers, blown fuses or other switches.

5.

Correcting problems due to improper gas supply pressure to the furnace.

Installer shall be familiarwith and complywith all codes and regulations applicable to the installation of these heating appliances and related equipment.

In lieu of local codes, the installation shall be in accordance with the current provisions of one or more of the following standards.

a. Federal Manufactured Home Constructions

& Safety Standard (H.U.D.

Title 24, Part

3280.707[a][2]) b. The Standard for Manufactured Home Installations (Manufactured Home Sites, Communities, and Set-Ups) ANSI A225.1

and/or

CAN/CSA-2240 MH Series).

c. American National Standard (ANS1=119.2/

NFPA=501C) for all recreational vehicle installations.

d. American National Standard (ANSI=Z223.1/

NFPA-54) and/or CAN/CGA B149 for all gasfired furnace models.

e. American National Standard (ANSI=C1/NFPA-

70) and/or CSA 22.1 Canadian Electric Code

Part 1 for all electrical field wiring.

6

CE g6nerateurd'air chauddoit Ctre installe conformement auxcodesIocaux.EnI'absencedecodelocal, respecterla normeANSIZ223.,1,instituleNationalFuelGasCodeoulescodesd'installation the side wall horizontal vented gas fueled equipment.

It shall be the responsibility of the property owner to secure the services qualified installation detectors.

licensed of hard professionals wired carbon for of the monoxide

The National Fuel Gas Code is available by writing:

American National Standards Institute, Inc.

1430 Broadway

New York, NY 10018

NFPA publications are available by writing:

National Fire Protection Association

Batterymarch Park

Quincy, ME 02269

IMPORTANT NOTE

INSTALLATION

COMMONWEALTH

MASSACHUSETTS

The

REQUIREMENTS

OF

Commonwealth of

=

Massachusetts requires compliance with regulation 248 CMR

5.00

for installation of the side wall horizontal venting.

The following requirements shall be satisfied.

INSTALLATION OF CARBON

MONOXIDE DETECTORS

At the time of installation of the side wall horizontal vented gas fuel equipment, the installing plumber or gasfitter shall observe that a hard wired carbon monoxide detector with an alarm and battery back-up is installed on the floor level where the gas equipment is to be installed.

In addition, the installing plumber or gasfitter shall observe that a battery operated or hard wired carbon monoxide detector with an alarm is installed on each additional level of the dwelling, building or structure served by

ALL MODELS

Front

Back

Sides

Vent

Top

Duct (Plenum) w/Coil Box w/o Coil Box

(within 3 feet)

CLOSET

Inches

1"

0

0

0

6

0

1/4

ALC OVE

Inches

1"

0

0

0

6

0

1/4

*Note: For 1" clearance, use a fully Iouvered door with at least

400 square inches of free airflow area.

Table 4. Minimum Clearances

In the event that the side wall horizontally vented gas fueled equipment is installed in a crawl space or an attic, the hard wired carbon monoxide detector with alarm and battery back-up may be installed on the next adjacent floor level.

In the event that the requirements of this subdivision can not met at the time of completion of installation, the owner shall have a period of thirty (30) days to comply with the above requirements; provided, however, that during said thirty (30) day period, a battery operated carbon monoxide detector with an alarm shall be installed.

APPROVED CARBON MONOXIDE

DETECTORS

Each carbon monoxide detector as required in accordance with the above provisions shall comply with NFPA 720 and be ANSI/UL 2034 listed and IAS certified.

SIGNAGE

A metal or plastic identification plate shall be permanently mounted to the exterior of the building at minimum height of eight feet above grade directly in line with the exhaust vent terminal for the horizontally vented gas fueled heating appliance or equipment.

The sign shall read, in print size no less than one-half (1/2) inch in size, "GAS VENT DIRECTLY BELOW.

KEEP CLEAR OF ALL OBSTRUCTIONS."

INSPECTION

The state or local gas inspector of the side wall horizontally vented gas fueled equipment shall not approve the installation inspection, inspector unless, observes upon carbon monoxide detectors and signage installed in accordance with the provisions of 248 CNR

5.08(2)(a) 1 through 4.

Exemptions: The following equipment is exempt frolTl 248 CMR 5.08(2)(a) 1 through 4:

Product approved side wall horizontally vented f_eled equipment installed in room or structure separated from the dwelling, building structure used in whole or in part for residential or purposes.

MANUFACTURERREQUIREMENTS-

GASEQUIPMENTVENTINGSYSTEM

NOT PROVIDED.

When the manufacturer of a Product Approved side wall horizontally equipment does not vented provide the gas fueled parts for venting the flue gases, but identifies" special venting systems", the following requirements shall be satisfied by the manufacturer:

1.

The reference system"

"special instructions included venting shall with the appliance be or

2.

equipment instructions; and

The "special venting systems" shall be Product Approved by the board, and the instructions for that system shall include a part list and detailed installation instructions.

A copy of all installation instructions for all

Product Approved side wall horizontally vented gas fueled equipment, all venting instructions, all parts lists for venting instructions, and/or all venting design instructions shall remain with the appliance or equipment at the completion of the installation.

LOCATION

The furnace must be installed on a level surface, and as close to the center of the air distribution system as possible.

See Figure 1 for overall dimensions to determine the required clearances in hallways, doorways, stairs, etc.

to allow the furnace to be moved to the instal= lation point. The furnace must be installed so that all electrical components are protected from water.

Minimum clearances to combustible materials are listed in Table 4. Access for positioning and servicing must be considered when locating the unit.

This furnace is certified for use on wood floor= ing. The furnace must be installed on a solid surface and must be level front-to-back and

, A Single trunk duct

I

_" Dual trunk duct

B w/crossover connector

Transition duct

C [p w/branches

II

7

[']____[1_

D

II

Figure 2. Non-Platinum

Supply Duct System

II

Top View of Duct

Connector

I I

Figure 4. Connector Dimensions

Use Duct Connector

If "X" (Floor Cavity) is: Model Part Number:

English Metric (mm) Finger Tab Screw Dowr

7/8" 22 901987 904008

2"

4 1/4"

6 1/4"

51

108

150

901988

901989

901990

904009

904010

904011

8 1/4"

10 1/4"

12 1/4"

210

260

311

901991

901992

901993

904012

904013

904014

Table 5. Duct Connector Sizes

FLOOR CAVITY

(depth equal to "X" in Table 5)

Figure 3. Floor Cavity

8

FELT-SEAL

REDUCER _\

SPACERS

(1) FINGER TAB DUCT CONNECTOR ONLY

(2) SCREW DOWN DUCT CONNECTOR ONLY

Figure 5. Duct Connector

,&

X SEE

TABLE 5 side=to=side. This furnace must not be installed directly on carpeting, tile, or any combustible material other than wood flooring.

The furnace may be installed on combustible flooring when installed on a Nordyne duct connector (see

Table 5).

( )OPENING TO DUCT

(1) WITH PLATE (C) REMOVED

OPENING BECOMES

13-1/4" x 13-1/4"

(2) WITH PLATE (C) REMOVED

OPENING BECOMES

13"X 13". WITH REDUCER

IT IS 13"X 10-1/8",

The ductwork within 3 feet of the furnaces without the A/C coil box must be installed such that surfaces are at least 1/4" from combustible materials.

When installed in a residential garage, the fur= nace must be positioned so the burners and the source of the ignition are located no less than

18 inches above the floor and protected from physical damage by vehicles.

HOLE \\\\\ lO"

FLo2

23-1/4"

Figure 6. Closet or Alcove

24

3-1/4

2-1/4

_/////_.REAR

F I 142-_/2 _ 2-3/4'_

WALL OF CLOSET bR_,_co_E_

I

I

i

g

-3/4

14-1/2

17-29/32 u_

--

--

3-19/32

1-3/4

J

_VENT

COMBUSTION AIR INTAKE

_-FUEL LINE ENTRY

2 fl ....

' 1-1/4

ALT FUEL LINE

/ I _

/ !. _

ENTRY /'

_,, _

/

_-

12-7/8

!__q,_

.....

15-1/2 _

FLOOR CUT-OUT

FOR OPTIONAL

COOLING COIL

FOR NON-PLATINUM

SERIES UNITS

I

_ 1-3/4

FURNACE

OUTER DOOR

Figure 7. Floor Cut-Out Dimensions

21-7/16

9

CIRCULATING AiR SUPPLY

z WARNING:

Products of combustion must not be allowed to enter the return air openings of the furnace or the circulating air supply, Failure to prevent products of combustion from being circulated into the living space can create potentially hazardous conditions including carbon monoxide poisoning that could result in personal injury or death,

The floor or platform on which the furnace

is mounted must provide sound physical support of the furnace with no gaps, cracks, or sagging between the furnace and the floor or platform,

The circulating air ductwork must not be connected to any other heat producing device such as a fireplace insert, stove, etc,

GENERAL

Plenums and air ducts must be installed in accordance with the Standard for the Installation of Air Conditioning and Ventilating Systems

(NFPA No. 90A) or the Standard for the Installation of Warm Air Heating and Air Conditioning

Systems (NFPA No. 90B).

RETURN AIR PROVISIONS

U.S.A. home manufacturers shall comply with all of the following conditions to have acceptable return air systems for closet installed forced air heating appliances: a. Regardless of the location, the return air opening into the closet shall not be less than specified in the appliance's listing.

b. Means shall be provided to prevent inadvertent closure by a flat object placed over the return air opening when it is located in the floor of the closet (versus the vertical front or side wall).

c. Closet installations must use a Iouvered door having a minimum free area of 235 sq. in.

when located 6" from furnace. For clearance between 1" and 6" from furnace, requirements are a Iouvered door with minimum of

235 sq. in. free area, with the openings in closet door directly inline with the Iouvered openings in the furnace door. For 1" clearance from furnace, use a fully Iouvered door with at least 400 sq. in. of free airflow area.

d. The cross-sectional area of the return duct system leading into the closet, when located in the floor or ceiling shall notbe less than 235 square inches.

e. The total free area of openings in the floor or ceiling registers serving the return air duct system must be at least 352 sq. in. At least one register should be located where it is not likely to be covered by carpeting, boxes and other objects.

f. Materials located in the return duct system must have a flame spread classification of

200 or less. This includes a closet door if the furnace is in a closet.

g. Noncombustible pans having 1" upturned flanges are located beneath openings in a floor duct system.

h. Wiring materials located in the return duct system shall conform to Articles 300-22 of the National Electrical Code (ANSI Cl/

NFPA-70).

i. Gas piping is not run in or through the return duct system.

j.

Test the negative pressure in the closet with the air-circulating fan operating at high speed and the closet closed.

The negative pressure is to be no more negative than minus 0.05 inch water column.

k. For floor return systems, the manufactured home manufacturer shall affix a prominent marking on or near the appliance where it can be easily read when the closet door is open.

The marking shall read:

CAUTION:

HAZARD OF ASPHYXIATION: Do not cover or restrict return air opening,

I. Air conditioning systems may require more duct register and open louver area to obtain necessary airflow.

Use NORDYNE's certiduct program to determine proper duct size for A/C.

10

DUCTEDRETURNAIR

M3furnaceswithmodelnumbersendinginAW or BWarefactoryconfiguredfor the returnair to flow throughthe front Iouvereddoor.The

returnairmayalsobeattachedto eithersideor the top of the furnacecabinetusing a field installedkit.RefertoTable10fortheNORDYNE

ductedreturnkitP/Nnumber.Thelocationand

sizeof the sideandtop returnair connections areshownin Figure1.Thefiltersizefortheside

returnairis20"x20"x 1".Fortopreturnthefilter

size is 24" x 16"x 1".

Three typical distribution systems are illus- trated in Figure 2. Location, size, and number of registers should be selected on the basis of best air distribution and floor plan of the home.

DUCT CONNECTOR SELECTION

PLATINUM SERIES a. For Platinum ready construction use the 14" round plenum, p/n: 903896.

NON=PLATINUM SERIES

M3 furnaceswith modelnumbersendingin

BWTarefactoryconfiguredforthe returnairto enterthe top of the furnace.

AIR DISTRIBUTION SYSTEMS

For proper air distribution, the supply duct system must be designed so that the static pressure measured external to the furnace does not exceed the listed static pressure rating shown on the furnace rating plate.

a.

b.

Determine depth of floor cavity from surface of floor to top of supply air duct

(See Figure 3).

Select appropriate model from Table 5 which matches X-dimension of the floor cavity.

To maximize air delivery, remove reducer "C" (see Figure 5) to obtain the largest open area that will fit the duct/floor construction.

MOUNTING

PLATE

FLOOR

OPENING

REAR WALL

FUEL

LINE

HOLES

SUPPLY AIR DUCT

Figure 8. Mounting Plate

SCREWS

BEND

UNDER

CONNECTOR

DUCT

TABS

OPENING

MOUNTING

PLATE

Finger Tabbed

Duct Connectors

Screw Down

Duct Connectors

Figure 9. Duct Connector Types

Platinum Series

CONNECTION

11

DUCT INSTALLATION

Required floor, ceiling, and roof cut-out openings must be carefully located to avoid misalignment of the furnace (see Figures 6 & 7).

Installation procedures are suggested for typical furnace installations and need not be followed in the exact listed sequence.

CUT OUT FLOOR OPENING & FUEL LINE

HOLE a. Determine center of closet or alcove (Figures 7 & 8).

b. Locate center of the floor opening, measured 10" from the rear wall, and mark cutout measuring approximately 14-1/2" by 14-

1/2" (+ 1") for model duct connector used

(refer to Figures 4 & 5).

c. Locate center of gas line hole, measured 23-

1/4" from the rear wall and 6-5/8" to the left of center of the floor cut=out (See Figure 6) or

5-1/4" to the left of center of the floor cut-out, or for entry through right-side of furnace measured 9" to the right of center of the floor cut-out.

d. Cut out floor opening and one gas line hole.

CUT DUCT OPENING (FINGERTABBED ONLY) a. Place duct connector through the floor opening with bottom tabs resting on top of the supply air duct.

b. Center duct connector and push back against rear edge of floor opening.

c. Mark cut-out location (tab area) and remove duct connector.

d. Cut out duct opening 1/16" larger than area marked.

INSTALL FURNACE MOUNTING PLATE a. Place mounting plate (supplied within duct connector) at rear of the floor opening (See

Figure 9).

TABS

111--.....

TABS

I/--.....

1.

INSERT DUCT PLENUM

INTO DUCT CUT-OUT.

CONNECTOR 2.

BEND BOTTOM TABS OVER

AND ONTO THE UNDERNEATH

DUCT SERVICE.

Figure 10. Installation of Duct Connector

Duct Connector t-_

12

Duct _ Narrow Duct t)

STEP 1.

Figure 11. Narrow Duct Installation

Fold Back Flap "B"

STEP2.

Cut

Fold Back Flap"B"

"--_

Cut- Out

Area "A"

Cut- Out

Area"A"

Lines "__lt "B"'B" _ Duct

Fold Back Flap"B"

Top of Duct

Fold Back Flap "B"

Bend Duct Connector Tabs Up and Over- (along length of duct)

/ \

STEP 4.

Staple Folded Duct

Flap (typ) to side of Duct

Connector

-k

Duct7

Figure 12. Alternate Installation

/

SLIDE FURNACE

ALL

ONTO

THE WAY

MTG.

BACK

PLATE

Figure 13. "A", "B", & Platinum

Cabinet Furnaces

/

SLIDE

ALL THE

FURNACE

WAY BACK

ONTO MTG PLATE iNSTALLiNG FINGER TABBED DUCT

CONNECTORS a. Place duct connector through the floor opening with bottom tabs extending through the duct opening.

(See Figure 9) b. Secure duct connector to floor.

c. Bend bottom tabs under and up tightly against the supply air duct. See Figure 10, page 12.

NOTE: The duct connector is designed for use on ducts 12" in width. When using the connector on 12" wide ducts, there may be insufficient clearance to bend the tabs on two sides of the duct connector.

In such cases the tabs may be attached to the sides of the duct by using sheet metal screws or other suitable fasteners.

(See

Figure 11).

If sealant, mastic, or tape is used to provide a better seal, it should be approved by applicable national or local codes.

ALTERNATE ATTACHMENT METHODS

Figure 14. "A" Cabinet Furnace on 911969

Coil Cabinet (Non=Platinum Series) iNSTALLiNG PLATINUM

ROUND DUCT CONNECTOR

SERIES 14" a. Place duct connector through the floor opening. (See Figure 9).

b. Secure duct connector to floor.

iNSTALLiNG SCREW DOWN DUCT CON=

NECTOR a. Apply a bead of caulking, mastic, or other approved sealant around bottom side of 1/2" flange and restrictor plate, when applicable.

b. Locate the duct connector over duct and carefully lower screw down duct connector into place.

c. Once duct connector is located on duct, temporarily hold in place while fastening duct connector to the floor using flat head screws or nails. Be sure flanges of duct connector stay in contact with the duct.

d. Screw plenum to duct making sure a seal is made between the duct and the duct connector. Additional screws may be added if required.

e. Cut away along edge of flange allowing the center to drop into the duct. Remove section of duct with caution, as edges will be sharp.

This procedure may also be used to install a furnace duct connector to narrow metal ductwork where insufficient clearance prevents bending of the duct connector tabs at the side(s) of the duct. See Figure 12, page 12.

1. Score and cut the top of the metal duct as indicated in Step 1 or Step 2. With Step 1 choice, also cut out the metal from the shaded area "A".

2. Fold the duct flap "B" up (Step 3, Figure 12).

3. At the front=to-back of duct run (Area "A"), bend the duct tabs and secure them directly to the duct.

4. At Area "B", bend the duct tabs up and back over, around the duct connector, (See

Step 3).

5. Fold/form the duct flap against the side of the duct connector and attach as shown, (See

Step 4). Use three (3) staples (minimum) on each duct flap OR, if a 2X block/joist is not provided, use two (2) sheet metal screws

(minimum) on each duct flap. An alternate attachment method is acceptable, as long as the plenum is securely attached.

6. Tape the duct flap edges with an approved tape for a leak-free joint.

iNSTALL FURNACE a. Remove furnace outer door(s) and bottom fuel line knockout.

b. Place furnace onto duct connector and center with floor opening.

13

c. Slideontomountingplate.(Bottomrearslots on furnaceshouldengagewith mounting platetabs.) d. Securefrontwith one(1) fastenerat each corner(SeeFigure13 or 14).

NOTE:Additionalfastenersmay be usedat rear,sidesor throughdoorframe,as desired, to securefurnaceto closetor alcoveframing.

/ WARNING:

Furnace installation using methods other than those described in the following sections must comply with the National

Fuel Gas Code and all applicable local

codes to provide sufficient combustion air for the furnace.

VENTING AND COMBUSTION AIR

REQUIREMENTS

/!X CAUTION:

Snow must not be allowed to restrict or block the combustion air intake or vent pipes.

CAUTION:

Do not allow debris to fall into the fur= nace.

This could cause unsafe operation and voids the furnace warranty.

VENTING REQUIREMENTS

General

NORDYNE condensing furnaces must be

installed with outdoor combustion air piped directly to the furnace.

Codes refer to this type of installation as direct vent, or two pipe installation.

/ WARNING:

FURNACE MUST NOT BE COMMON

VENTED WITH OTHER APPLIANCES.

Provisions must be made for adequate supply of air for combustion and ventilation.

For

United States installations, the adequacy of air provisions can be determined by consulting the current version of the National Fuel Gas

Code (ANSI Z223.1/NPFA=54).

For Canadian

installations, requirements are specified in the

National Standard of Canada (CAN/CGA

B149.1 & .2). Consult local codes for special requirements.

NOTE: If the furnace is operated without adequate air for combustion and ventilation, it may not perform components may be properly.

strained

Furnace by temperature and could fail prematurely.

high

/ WARNING:

The combustion air piping must not be blocked or restricted in any manner.

General

This section specifies installation requirements for 2-pipe combustion air piping.

The capacity table provided in this section applies to the maximum equivalent lengths of vent and combustion air intake pipe.

These condensing furnaces are classified as

"Category IV" appliances, which require special venting materials and installation procedures.

Category IV appliances operate with positive vent pressure and therefore require vent systems which are thoroughly sealed.

They also produce combustion condensate, which is slightly acidic and can cause severe corrosion of ordinary venting materials.

Furnace operation can be adversely affected by restrictive vent and combustion air piping.

Therefore, vent and combustion air piping lengths must conform completely requirements of Table 6, page 15. to the

The furnace must be vented to the outdoors.

14

APPLICATION

PVC,CPVC or ABS

SCH. 40 Pipe Size

Model M3RL 060

Model M3RL 080

MAXIMUM

DIRECT VENT, DUAL

PIPE LENGTH (ft.)*

Inlet/Outlet

3"

50

50

3"

50

50

*NOTES

1.

2.

3.

Subtract

Two45

3.5 ft. for each additional 3" 90 degree degree elbows are equivalent elbow.

to one 90 degree elbow

4.

5.

One short radius elbow is equivalent elbows.

to two long radius

Do not include termination elbows in calculation of vent length

This table is applicable for elevations from sea level to 400C ft. For higher elevations, decrease vent pipe lengths by 8% pel

1000ft.

of altitude.

6.

Onlythe above pipe materialsare approved for usewith these condensing furnaces.

Table 6. Vent Table

[] VENT TERMINAL (_ AiR SUPPLY INLET [] AREA WHERE TERMINAL IS NOT PERMITTED

A = Clearance above grade, veranda, porch, deck, balcony, or snow accumaulation level

B -- Clearance opened to window or door that may be

Canadian Installations 1

12 inches (30 cm)

6 inches (15 cm) for appliances < 10,000

Btuh (3 kW), 12 inches (30 cm)for appliances > 10,000 Btuh (3 kW) and <

100,00 Btuh (30 kW), 36 inches (91 cm)for appliances >100,00 Btuh (30 kW)

C = Clearance to permanently closed window

D = Vertical clearance to ventilated soffit located above the terminal within a horizontal distance of 2 feet (61 cm) from the center line of the terminal

E = Clearance to unventilated soffit

F = Clearance to outside corner

G = Clearance to inside corner

H = Clearance to each side of center line

extended above meter/regulator assembly

I = Clearance to service regulator vent outlet

J = Clearance to nonmechanical air supply inlet to building or the combustion air inlet to any other appliance

3 feet (91 cm) within a height 15 feet above the meter/regulator assembly

3 feet (1.83 m)

6 inches (15 cm) for appliances < 10,000

Btuh (3 kW), 12 inches (30 cm)for appliances > 10,000 Btuh (3 kW) and <

100,00 Btuh (30 kW), 36 inches (91 cm)for appliances >100,00 Btuh (30 kW)

K = Clearance to a mechanical air supply inlet 6 feet (1.83 m)

7 feet (2.13 m) 1"

US Installations 2

12 inches (30 cm)

6 inches (15 cm) for appliances < 10,000

Btuh (3 kW), 9 inches (23 cm) for appliances > 10,000 Btuh (3 kW) and <

50,000 Btuh (15 kW), 12 inches (30 cm) foi appliances > 50,000 Btuh (15 kW)

6 inches (15 cm)for appliances horizontally appliances

,

< 10,000

Btuh (3 kW), 9 inches (23 cm) for appliances > 10,000 Btuh (3 kW) and <

50,000 Btuh (15 kW), 12 inches (30 cm) foi

> 50,000 Btuh (15 kW)

3 feet (91 cm) above if within 10 feet (3 m)

L -- Clearance above paved sidewalk or paved driveway located on public property

M -- Clearance under veranda, porch deck, or balcony

12 inches (30 cm) $ ,

In accordance

2 In accordance with the current with the current

CSA B149.1

ANSI Z223.1

Natural Gas and Propane

/ NFPA 54 National Fuel

Installation

Gas Code

Code

1" A vent shall not terminate directly above a sidewalk local installation manufacturer's or paved driveway that is located codes, installation and the requirements instructions." between two single family

$ dwellings

Permitted

For and serves only if veranda, clearances not both dwellings.

specified porch, deck, or balcony in ANSI Z223.1

/ NFPA is fully

54 open or CSA on a minimum

B149.1, the of two following sides beneath statement shall the floor.

be included:

"Clearance in accordance with of the gas supplier and the

Figure 15. Vent Termination Clearances for Direct Vent Furnaces

15

/ WARNING:

CARBON MONOXIDE POISONING

HAZARD

1.

Seal any unused openings in the venting system

2.

inspect the venting system for proper size and horizontal pitch, as required in the National Fuel

Gas Code, ANSi Z223.1

or the

CAN/CGA B 149 Installation Codes and these instructions. Determine that there is no blockage or restriction, leakage, corrosion and other deficiencies which could cause an unsafe condition.

3.

So far as is practical, close all building doors and windows and all doors between the space in which the appliance(s) connected to the venting system are located and other spaces of the building.

4.

Follow the lighting instructions.

Place the appliance being inspected in operation.

thermostat so appliance

Adjust shall operate continuously.

5.

Turn on clothes dryers and any other appliance not connected to the venting system.

Turn on any

exhaust fans, such as range hoods and bathroom exhausts, so they shall operate at maximum speed.

Do not operate a summer exhaust fan.

6.

Close fireplace dampers.

7.

Test for spillage from draft hood equipped appliance at the draft hood relief opening after 5 minutes of main burner operation.

Use the flame of a match or candle.

8.

If improper venting is observed during any of the above tests, the venting system must be corrected

in accordance with the National

Fuel Gas Code, ANSI Z223.1/NFPA

54and/or CSA B149.1, Natural Gas and Propane Installation Codes.

16

.

After it has been determined that

each appliance connected to the venting system properly vents when tested as outlined above, return doors, windows, exhaust fans, other their fireplace gas dampers burning previous and any appliance conditions

Material .......................................

Standard

Schedule 40PVC ............................ D1785

PVC-DWV .......................................

D2665

SDR-21 & SDR-26 .......................... D2241

ABS-DWV .......................................

D2661

Schedule 40 ABS ............................

F628

Foam/Cellular Core PVC ................ F891 to of use.

It must not be vented in common with any other appliance, even if that appliance is of the condensing type.

Common venting can result in severe corrosion of other appliances or their venting and can allow combustion gases to escape through such appliances or vents.

Do not vent the furnace to a fireplace chimney or building chase.

If removing an existing furnace in a venting system, the venting system may not be properly sized. To test the vent system with the remaining appliances, follow the test outlined below.

The following steps shall be followed with each appliance connected to the venting system placed in operation, while any other appliances connected to the venting system are not in operation:

Vent Pipe Material

Vent and combustion air pipe and fittings must be one of the following materials and must conform to the indicated ANSI/ASTM standards:

Note: In Canada, vent materials must be certified to the Standard for Type BH Gas Venting

System, ULC $636.

Any certified ULC $636 material must not be interchanged with unlisted or non certified pipes and/or fittings. The plastic components, specified primers and glues of the certified vent system must not be intermixed with any other manufacturer's vent systems or parts.

Cement and primer must conform to ATSM

Standard D2564 for PVC and Standard D2235 forABS.

When joining PVC piping toABS, use an appropriate solvent cement and procedure

Downflow Furnace

Seal/Caulk

Around Pipe -at Building

90 ° E bow \

\

\\

\\

!_

I

',

\"\

\

'<,

_

_

_ _

Coupling // i' r-i

Vent

_!3

9/t 6",_

1 7/8"

See Vent Table 4

Combust on

Air intake Pipe _...

Straps or Other Suitable

Supports at Minimum of

I

I

/

_

"1_

_ _

""

_ p

.i

I

,

_,-_ ._.

i (1_

I

5 ft" Inltervals

/ _\\ i-i ii

\, r-i

I_ _

Top View

MIn

[_J,l_ i

Normal Snow Level

_

_

4,

........

Wal Upward Pitch = 1/4" Per F°°t

Wail Outlet Exhaust Vent

First Support

Furnace

Should

Connection be as Close to as Possible

Combustion Air intake Pipe Furnace

A j

Offset with

Vent for Adequate

Dimensional Clearance

Exhaust

Vent

PVC or

ABS pipe

3"x 2"

Reducer

Figure 16. Horizontal Venting

Support System on Vertical Rise

Below Joints

First support should be as

close to furnace as possible

Intake Pipe

Combustion Air !_

...Vent

Upward Pitch

1/4" per foot

" Combustion Air intake Pipe

®

J-..

per the piping manufacturer's and ASTM Standard D3138.

Figure 17. Vertical Venting recommendation any condensate flows back to the furnace where it can be disposed of through the condensate disposal system.

Vent Pipe Installation

Pipe Routing and Support

Route piping as directly as possible between the furnace and the outdoors and remember that routing affects pipe length limitations per

Table 6. Locate the combustion air intake and the vent exhaust in the same atmospheric pressure zone - i.e. both must exit the building though the same portion of exterior wall or roof.

Vent piping must be sloped upwards not less than 1/4" per foot in the direction from the furnace to the terminal.

This is to ensure that

The quality considered.

CAUTION:

Combustion air must not be drawn from occupied atmosphere, spaces and a corrosive of outdoor intake is not located air must also

Be sure that the combustion be air near a source of solvent

17

fumes or other chemicalswhich can cause corrosionof the furnacecombustionsystem.

.

similar recessed areas, and do not terminate above any public walkways.

Select the point of wall penetration where the minimum 1/4 inch per foot of slope up can be maintained.

itsweightdoesnotbeardownonthefurnace.

Supportsmustbe at intervalsno greaterthan five feet,andat smallerintervalsif necessary to ensurethatthereare no saggingsections to trapwater(SeeFigures16 & 17).

CAUTION:

These condensing furnaces have been certifiedfor installationwith zero clearance

For optimal performance vent furnace through wall which experiences the least exposure to winter winds.

However,it is goodpracticetoallowspacefor conveniencein installationand service.

Horizontal Venting

Vent and combustion air intake terminations must be as shown in Figure 19 unless the concentric vent termination kit is used.

Location of Outdoor Terminations

Vent and combustion air intake terminations must be located to ensure proper furnace operation and to conform to applicable codes.

Figure 15 illustrates necessary distances from the vent termination to windows and building air intakes.

In Canada, the Canadian Fuel

Gas Code takes precedence over these instructions.

Specifically, distance requirements with all minimum respect to termination of the vent piping listed below.

The following list is a summary of vent terminal location requirements:

1.

The termination must be 12 inches above snow level or grade level whichever is higher. See Figure 18 for alternate method to achieve 12" above snow level.

2.

The minimum distance for a direct vent (2= pipe) installation from any door, openable window, or air gravity inlet is 1 ft. below, 1 ft. horizontally, or 1 ft. above.

3.

The vent termination shall be a minimum of

3 ft. above any forced air inlet within 10 ft.

4.

The vent termination shall be located at least 4 ft. horizontally from any electric meter, gas meter, regulator and any relief equipment.

These distances apply only to U.S. installations. In Canada, the Canadian Fuel Gas Code takes precedence.

5.

Avoid areas where condensate drainage may cause problems by dropping on plant-

ers or patios, etc.

Also ensure that exhaust gases will not impinge on windows or building surfaces, which may be compromised or damaged by condensation.

Do not install the vent terminal such that exhaust is directed into window wells, stairwells, under decks or into alcoves or z WARNING:

Ensure that the combustion air vent and the exhaust vent are configured as shown in Fig.

19.

improper vent termination can cause recirculation of the flue gases. This may result in furnace vibration, in severe cases, the furnace will cycle, due to the intermittent contact between the flame and the flame sensor.

If you note these oscillations occurring, check the vent configuration.

Make sure that the exhaust vent does not have a 90 degree termination.

For horizontal venting, either the Horizontal

Exterior Vent Mounting Kit or the Concentric

Vent Termination Kit may be used (See Table

12).

For Canadian installations please refer to the

Canadian Installation Code (CAN/CGA-B 149.1

or 2) and/or local codes.

The Horizontal Exterior Vent Mounting Kit consists of two face plates and an insulating gasket to seal the exterior surface. A hole sized closely to the pipe diameter must first be cut through the wall. A short length of pipe is then cut such that it can penetrate the wall and be held in place by closely fitting standard couplings.

The face plates are retained on both sides of the wall by

18

VentConfiguration

12"

Minimum

Snow Level.

height above _

Wail ' '_

12" Min.

19" Max.

Support

Outside _

__ _

1,,2"

" __

:__ insulation ol

Equivalent

12"Above

Normally

Expected

Snow

Level

Exhaust Vent

Option B

Mounting

FacepIate Secured

Combustion

Air Inlet

Exhaust Vent

Option C

Exhaust Vent

ion A

_fJ jJ 12" Min, to

Normal Snow Level

,o,o,

Grade

Level red),

Figure 18.

Vent

Alternate

Installation

Horizontal the couplings, and the gasket is retained against the wall by the outer face plate.

Face plates must be fastened to the wall and the outside one must be flashed as appropriate to prevent entry of water.

When the above kits are not used the following steps are required:

1.

Check the hole size cut through the exterior wall. Insure that the hole diameter is less than the diameter of the couplings to be used.

2.

Extend the vent pipe through the wall approximately 1" and seal the area between the wall and pipe.

3.

Apply couplings to the vent pipe on the interior and exterior sides of the wall to insure the pipe can not be pushed or pulled through the wall.

A= 12" Above Roof or

Snow Accumulation Level

Elbow

5-Min.

36" Max.

Figure 19.

Exhaust and Combustion Air

Pipe Clearances

4.

Insure the combustion air inlet pipe has a 90 degree termination elbow, and is pointing downward as shown in Figures 19 & 20.

Note that a combustion air intake must be provided with an elbow opening downward.

When the vent pipe must exit an exterior wall close to the grade or expected snow level, a riser should be provided as shown in Figure 18.

Insulation is required to prevent freezing of this section of pipe.

Vertical Venting

For vertical venting, either the configuration shown in Figure 20 or the Concentric Vent

Termination Kit may be used. Vertical venting is one of the shortest routing methods when

.... Exhaust

Plumbing Vent

Roof Boot

(Typ. Both Pipes)

Note: If terminations meet= ing these vertical requirements exceed the maximum height for safe transit, the vent and combustion air intakes may be shipped with the home for assembly on site. The furnace must be labeled to notify the installer/ user not to use the furnace until the vent and combustion air intake terminations are installed.

Figure 20.

Vertical Vent Termination

19

.._.__.__...__-_ Collector Box

Step 1 :

Step 2:

Clamp _iiill

Step 3:

I Burner Box j _ Keep

Floor _ _-'Y"

AIt. Drain

AIt. Drain

Concentric

Figure 21. Furnace with Condensate Drain Trap Assembly piping vents for furnaces.

The M3 furnace operates trouble=free when the furnace is installed with a shorter vent.

• The inlet for the combustion intake pipe must be extended at least one foot above the roofline or snow accumulation level.

• The outlet of the vent must be extended at least

10 inches above the inlet of the combustion air intake pipe.

• The vent as well as the combustion air intake pipe should be located on the same side of the roof. Both pipes must not be closer than 5 inches apart. They should not be separated more than 36 inches.

The roof penetration must be properly flashed and waterproofed with a plumbing roof boot or equivalent flashing.

Termination spacing requirements from the roof and from each other must be per Figure 20.

Vent Termination

A concentric vent termination is approved for use with these furnaces (See Table 12).

For proper installation of the concentric vent termination, follow the installation instructions provided with the kit.

NOTE: The condensate drain should tected from freezing when in unheated spaces.

The furnace densate

Do not condensate

The condensate kinked.

is supplied drain trap.

install with an internal

CAUTION: additional drain, traps be proconin the drain may exit through the left side panel, the right side panel, or through the left or right hole on the bottom panel. (See Figure

21). Ensure that the flexible drain hose is not

The condensate should drain from the plastic collector box (location "A", Figure 21) as drop= lets or a small stream. If you notice the furnace has operated for more than 5 minutes without draining or the red status light on the control board is pulsing a 2-blink code follow the steps below.

DRAINAGE OF CONDENSATE

FROM FURNACE

/t WARNING:

The condensate produced by the furnace must be drained, Do not connect a water supply to the drainage hose of the furnace,

1.

Remove the collector box soft tube at location "A", Figure 21 and verify the exit from the collector box is clear of any debris or obstructions.

2.

Replace this tube and verify the fit to the header spout is air tight. Air will be drawn into the header if this connection is not tight.

3.

Check other tube connections along the drain system.

Verify that all are air tight.

NOTE: Industry research studies indicate that when condensate is routed to an active drain,

2O

householddetergents,etc.,bufferitsacidity.If

thedrainis notactivelyusedorifcodesrequire, obtaina neutralizerkit(SeeTable10,page28).

satetubingarerequiredas NORDYNEcannot beheldresponsiblefor water leakagewhich occursdueto loosehoseconnectionsor

NOTE: When pressure testing gas supply lines at pressures greater than 1/2 psig (14 in.

water column), the furnace must be disconnected from the gas supply piping system to prevent damage to the gas control valve.

If the test pressure is less than or equal to 1/2 psig (14 in. water column), the furnace must be isolated from the gas supply line by closing the manual shut-off valve.

GAS SUPPLY AND PIPING

General

This furnace is equipped for bottom, left, or right side gas entry. Typical gas service hookups are shown in Figure 22. When making the gas connection provide clearance between the gas supply line and the entry hole in the furnace casing to avoid unwanted noise and/or damage to the furnace.

Main

All gas piping must be installed in compliance with local codes and utility regulations.

Some local regulations require the installation of a manual main shut=offvalve and ground joint union external to the furnace. The shut-off valve should be readily accessible for service and/or emergency use. Consult the local utility or gas supplier for additional requirements regarding placement of the manual main gas shut-off.

In the absence of local codes, the gas line installation must comply with the provisions stated in the Federal Manufactured Home Standard

(H.U.D Title 24, part 280) and the National Fuel

Gas Code (ANSI Z223.1/NFPA-54) or (CAN/

CGA B149) installation codes.

A drip leg should be installed in the vertical pipe run to the unit. Table 11 (page 34) lists gas flow capacities for standard pipe sizes as a function of length in typical applications based on nominal pressure drop in the line.

NOTE: Gas piping must not be run in or through air ducts, gas vents, etc.

Compounds used on threaded joints of gas piping must be resistant to the actions of liquefied petroleum gases.

CAUTION:

Do not use matches, lighters, candies, or other sources of open flame to check for gas leaks.

Control

Board

Burner

Box

Gas

Floor

To Gas

Supply

"J

AIt. Gas

Line Entry

Figure 22.

Typical Gas Piping

Leak Check

After the gas piping to the furnace is complete, all connections must be tested for gas leaks. To check for leaks use only a soap and water solution or other approved method.

High Altitude Derate

The nameplate input rating for the furnaces apply for elevations up to 4,000 feet above sea level for US and Canada. If the elevation for the furnace location is higher than 4,000 feet above sea level, the furnace input must be derated by using the appropriate orifice size listed in

Table 12, page 34.

21

NOTE:The densityof air decreaseswith increasingelevationabovesea level.This retheunitbederatedbyusingsmallergasorifices or lowermanifoldpressure.

CONVERSION

This furnace can be converted from the factory-equipped gas to either natural gas (for LP gas ready models), or LP gas (for natural gas ready models).

Conversions must be made by qualified service personnel, using only factory authorized or approved parts.

The required conversion orifices are supplied with the furnace.

WARNING:

This conversion kit shall be installed by a qualified service agency in accordance

with the manufacturer's instructions and all applicable codes and requirements of the authority having jurisdiction.

If the information in these instructions is not followed or production exactly, of

a fire, carbon explosion monoxide may result causing property damage, personal injury or loss of life.

The qualified service agency is responsible for the proper installation of this kit.The installation is not proper and complete until the operation of the converted appliance is checked as specified in the manufacturer's

with the kit. instructions supplied

/!XWARNING:

DO NOT REMOVE OR DEFACE THE

ORIGINAL RATING PLATE.

CAUTION:

Turning Off The Fuel Supply:

1.

Set the room thermostat to "OFF" or its lowest temperature setting.

2.

Turn OFF the main gas supplyto the appliance at the manual valve, outside of the appliance casing.

3.

Remove the control access panel / Iouvered door.

4.

Move the appliance gasvalve lever/knob to the "OFF" position.

5.

Turn OFF the electrical power to the appliance.

Removing The Burner Assembly:

1.

Follow the instructions "To Turn Off the

Fuel Supply to the Appliance."

2.

Disconnect the flame sensor wire from the burner box.

3.

Disconnect the ignitor wires at the 2 pin plug. This is a locking quick connect and both sides of the lower section must be depressed in order to be separated.

4.

Remove the wires from the terminals of the gas valve.

5.

Disconnect the rubber pressure tubes from the gas valve and the burner box.

6.

Remove the burner access cover plate from the burner box.

7.

Remove supply gas piping from the gas valve.

8.

Carefully remove the burner assembly fasteners and remove the burner assembly from the appliance.

Keep the fasteners that were removed. Note that the burner box may have hooks near the top and on the right and left hand sides. To remove this type of burner box, lift the burner box upwards and then remove the box from the unit.

Removing The Burner Orifices:

1.

Remove the four (4) fasteners that secure the gas manifold to the burner box, as shown in Figure 25. Carefully remove the gas manifold assembly from the burner box. Note that the gas manifold assembly consists of the gas valve, the gas manifold, and the orifices.

The gas supply shall be shut off prior to disconnecting the electrical power, before proceeding with the conversion.

CAUTION:

Caution: orifices.

Do not re-drill

If the orifice the burner size must be changed, use only new orifices.

2.

Carefully remove the burner orifices from the gas manifold, as shown in Figure 25.

22

Note: The size of the new orifices that will be installed into the unit will depend upon the type of conversion (sea level or high alti=

tude; natural gas or LP gas).

Honeywell

Valve

Figure

PRESSURE

REGULATOR

Regulator

II_1__

23. Convertible

Cap

OTHER

OF CAP

SIDE

Pressure

Converting the Unit to Alternate Gas

1.

Remove the orifice bag from the manifold of the unit.

2.

Install the appropriate gas burner orifices into the gas manifold.

Remember if in= stalling at altitudes above 4,000 feet to install the proper orifices, shown in Table

12. When installing the new orifices, DO

NOT use pipe joint compound on the orifice threads.

Screw the orifices into the manifold by hand until snug to eliminate cross threading, then tighten with a wrench.

Before installing an orifice, check the face or side of the orifice for the drill number to ensure that it is the appropriate size.

3.

For the conversion to the alternate fuel, the gas valve regulator cap must be turned over, as shown in Figure 23.

You will unscrew the cap and reinstall for your installation. After reinstalling the cap, you will be able to read "NAT" for the conversion to natural gas or "LP for the conversion to LP gas.

Figure 24. Burner Inspection

Burner

Orifices

\

Gas

Manifold

Flame

Observation

Burner

Box Inlet

Pressure

Tap

Access

Cover

Plate Inlet Gas

Valve

Figure 25.

Typical Installation For Sealed

Burner Box With Access Cover Plate

Reinstalling the Burner Assembly:

1.

Reinstall the gas manifold assembly to the burner box with the four (4) fasteners, which were removed earlier.

2.

Carefully reinstall the burner box into the unit.

After installing the burner, inspect the alignment of the burners with the heat exchanger tubes.

The center of the burners should be aligned with the center of the tubes.

3.

Reconnect the gas piping to the gas valve.

4.

Reconnect the wires to the gas valve terminals.

5.

Reconnect the rubber pressure tubes to the gas valve and the burner box.

Reinstall the burner access cover plate.

6.

Reconnect the ignitor at the 2 position plug.

7.

Reconnect the flame sensor wire to the burner box.

23

Pressure Gauge Installation

NOTE: For natural gas installations, the incom- ing gas line pressure at the gas valve inlet must be between 4.5" WC and 10.0" WC. For LP gas installations, the incoming gas line pressure at the gas valve inlet must be between 11.0" WC and 14.0" WC.

This pressure can be checked at the inlet end of the gas valve using a pressure gauge or U-tube manometer, which must be installed according to the manufacturer's supplied instructions.

LIGHTING AND ADJUSTMENT OF

THEAPPLIANCE

1.

Turn ON the gas at the manual valve, outside of the unit.

2.

Check all gas connections for leaks with a soap and water solution.

If the solution bubbles there is a gas leak which must be corrected.

Do NOT use an open flame to check for gas leaks.

3.

Turn ON the electrical power to the appliance.

4.

Move the gas valve lever/knob to the "ON" position.

The lever/knob must be moved to the end of its range of motion to insure the valve is completely open.

Use only your hand to push in or turn the gas control valve.

Never use tools.

5.

Set the room thermostat to a point above room temperature to begin the heating cycle of the unit.

6.

Check that the unit ignites and operates properly.

Refer to the installation instruc- tions provided with your unit for the normal operating sequence.

7.

After the flame ignites, visually inspect the burner assembly to ensure that the flame is drawn directly into the center of the heat exchanger tube, as shown in Figure 23.

The end of the flame will be out of sight around the bend of the heat exchanger tube. In a properly adjusted burner assembly, the flame color should be blue with some light yellow streaks near the outer portions of the flame.

Type of Fuel Manifold Pressure in. WC

Natural Gas:

Propane (LP) Gas:

3.5

10.0

Table 7. Manifold Pressure

NOTE: Until all of the air is bled out of the gas line, the hot surface ignitor may not ignite the gas.

If the ignition control locks out, turn the thermostat to its lowest setting and wait one minute then turn the thermostat to a point above room temperature and the ignitor will try again to ignite the main burners.

This process may have to be repeated several times before the burners will ignite.

Once the burners are lit, check all gas connections for leaks again with the soap and water solution.

If the solution bubbles there is a gas leak which must be corrected.

Do not use an open flame to check for gas leaks.

Manifold Pressure

The gas valve for the M3 furnace series is equipped with a special conversion pressure regulator cap. The pressure regulator cap is factory set. if the gas valve is converted from natural gas to propane gas or vise versa, the manifold pressure of the gas valve will be set to pressure listed in Table 7.

COMPLETING THE CONVERSION

1.

Affix the gas valve conversion label found in the package with the orifices to the unit rating plate.

2.

Run the appliance through a complete cycle to assure proper operation.

CAUTION:

To avoid electric shock, personal

injury, or death, turn off the power at the disconnect or the main service panel before making any electrical connections,

ELECTRICAL WIRING

General

Electrical connections must be made in accordance with all applicable local codes and ordinances, and with the current revision of the

National Electric Code (ANSI/NFPA 70).

For Canadian installations electrical connections and grounding must be done in accordance with the current Canadian Electrical

Code (CSA C22.1 Part 1) and/or local codes.

If

24

any of the originalwire as suppliedwith the furnacemustbereplaced,it mustbe replaced /!X CAUTION: of 105°C.Referto thefurnacenameplateand

Table8 for electricalrequirements.

Line Voltage Wiring

The linevoltage(115volt)tothe furnacemust be suppliedfrom a dedicatedbranchcircuit containingthe correctfuse or circuitbreaker for the furnace.See Table8. An electrical switchshouldbe readilyaccessiblefromand within sight of the furnace. See the Wiring

Diagramlabelin the furnacefor moredetails.

The furnacecabinetmust have an uninterrupted,unbrokengroundto minimizeinjury shouldan electricalfaultconditionoccur.The

controlsusedin this furnacerequirean earth groundto operateproperly.Acceptablemethodsforgroundingareelectricalwireor conduit approvedforelectricalgroundservice.Do not usegas pipingas an electricalground.

NOTE:Properline voltagepolaritymust be maintainedin orderfor the controlsystemto operatecorrectly.Verifythattheincomingneutral lineis connectedto thewhitewireandthe incoming"hot"line is connectedto the black wireinthefurnacejunctionbox.Thefurnacewill

not operateunless polarityand ground are properlyconnected.See Figure26.

Label all wires prior to disconnection when servicing controls.

Wiring errors can cause improper and dangerous operation,

Verify proper operation after servicing,

Common

Leads

Connect

Neutral _

.....

and/or Humidifier

H....

::ul_l

24 V

_OM _

Timing

Flame Signal TWIN

BIowerOff O

Status

Light (Red) O

Neutrals o

_

> Z/]

_

Humidifier

_

_ _ 3: © x

Ir_nq _ _ _ _ _ o° _- _

IIIIII

tl

II

If

I

11

Tap |

/ I LElectronic Air Tap

(.5A@ 120 VAC)

(.5A@ 120 VAC) _ I These motor speed taps are

L not used for two-stage models

Figure 27.

Blower Speed Tap Location

Furnace

Input

(Btuh)

45,000

80,000

Cabinet

Width

(in.)

19 3/4

19 3/4

Nominal

Electrical

Supply

115-60-1

115-60-1

Maximum

Operating

Voltage

127

127

Minimum

Operating

Voltage

103

103

Maximum

Furnace

Amperes

9.7

9.7

Time-delay fuses or HACR-type circuit breakers are required.

Recommended Thermostat

Thermostat Wire Gauge

24

22

2O

2 - wire

(Heating)

55 ft.

90 ft.

140 ft.

18 225 ft.

Minimum

Wire

Gauge

14

14

Wire Length

4 or 5 wire

(Cooling)

25 ft.

45 ft.

70 ft.

110 ft.

Maximum

Fuse or Circuit

Breaker Amps _

15

15

Table 8.

Electrical Data

Field Supplied

Fused Service

Panel

\

Field Supplied

Disconnect w/in

Sight of Furnace

\

Junction Box (may be int. or ext.

to the furnace).

These connections can be made disconnect in the field at the furnace.

supplied

Wh e (Neu ra) |

...."1

White /, "_

.... I.......... L-_L-_.-_L-:

....._---

[ Ground

Panel Connector

......

__

Field Line Voltage Wiring

Factory Line Voltage Wiring

Figure 26.

Line Voltage Field Wiring

White

Ground

25

/!X ATTENTION:

Lots des operations d'entretien des commandes, _tiqueter tous les flies avant des les d_connecter.

Toute erreur de c,iblage peut _tre une source de danger et de panne.

S'assurer du bon fonctionnement

I'appareil apr_s tout entretien. de

[-I

,, [m__

_ I_

F_[_j

_ Condensing

I C°ndensingunit

Unit control Box oo oo(--1_

Connect m _;-m

R & W __LN. ....

ForI _1

Heating I _m- .....

'-I-

;0 CO=M [_

3 Amp

Fuse i

O_

-i-_1

24==V

:_t®l

_ Flame Only _

Room

Thermostat

.....

TWIN

Signal Light O

Status Light _

(Red)

Low Voltage Wiring

Install the thermostat per the manufacturer's instructions.

The low voltage (24 volt) connec= tions from the thermostat are made at the terminal strip on the control board in the furnace.

See Figure 28 for the proper connections for heating only (two=wire) and heating/cooling

(four=wire) applications.

The recommended minimum wire gauge for thermostat wiring is shown in Table 8 (page 25).

The thermostat must not be installed on an outside wall or any other location where its operation may be adversely affected. Adverse affects include radiant loading from fireplaces, sunlight, or lighting fixtures, and convective loading from warm air registers or electrical appliances.

To check the heat anticipator setting either:

1.

Add the current draw of the system components; or

2.

Measure the current flow on the thermostat

R-W circuit after the circulating blower motor has started.

Set the heat anticipator according to the thermostat manufacturer's instructions for heat anticipator settings.

VENTILATION

Ventilation must be provided for homes built to

HUD Manufactured Homes Safety and Construction Standards. This ventilation can be supplied by the VentilAire III or VentilAire IV accessories. See Table 10 on page 34.

Alternate means to pro-vide the ventilation air must meet the requirements of all applicable local and federal codes.

For installation of the VentilAire Ill or IV, follow the instructions provided with the VentilAire kit.

NOTE: The "Y" terminal on the

UTEC control board must be connected to the thermostat for proper cooling mode operation.

FIELD WIRING

Low Voltage

Connections

-i-

C = I

Neutrals

Unused Motor Leads

I_,_1 c'_ _ _'o > _ _ _-

I III I II II

Figure 28.

Low Voltage Field,

Four=wire Heating/Cooling Applications

START=U P AND ADJUSTMENTS

General

Prior to start-up, verify that:

.

The line voltage power leads are securely connected, that the polarity of the connections is correct, and that the furnace is properly grounded.

2.

The thermostat wires (R, W, Y, and G) are securely connected to the correct leads on the terminal strip of the circuit board.

.

The natural gas line service pressure must not exceed 10.0 in. water column (0.36

psig), and must not be less than 4.5 in.

water column (0.16 psig). For LP gas the line service pressure must not exceed 14 in. water column (0.51 psig), and must not be less than 11.0 in. W.C. (0.40 psig).

.

The roll-out and vent safety manual reset switches are closed.

If necessary, press the red button to reset a switch.

See

Figure 26 for location.

DO NOT install a jumper wire across a switch to defeat its function.

If a switch reopens on start=up,

DO NOT reset the switch without identifying and correcting the fault condition which caused the switch to trip.

26

5.

6.

1.

2.

3.

The blower door switch in the line voltage

The gas connections

Start=Up

Close line has been are leak tight.

Procedure

Set the thermostat voltage to the furnace.

Follow the procedures circuit.

purged given on the operating instructions label attached to the furnace.

door is in place, closing the and all to the lowest setting.

the disconnect(s) to provide line

4.

Set the thermostat above room temperature and verify the sequence of operation.

(See the SEQUENCE OF OPERATION.)

.

After the furnace has run for approximately five minutes, set the thermostat below room temperature and verify steps 9 - 11 of the

SEQUENCE OF OPERATION (page 31).

Shut Down Procedure

In the event that the furnace must be shut down, follow this procedure:

1.

Set the room thermostat to "OFF" or its lowest temperature setting.

2.

Turn OFF the main gas supply to the appliance at the manual valve outside of the appliance casing.

3.

Remove the control access panel / Iouvered door.

.

.

Move the appliance gas valve lever/knob to the "OFF" position.

Turn OFF the electrical power to the appliance.

Verifying Firing Rate

The firing rate must be verified for each installation to prevent over-firing the furnace.

NOTE: The firing rate must not exceed the rate shown on the furnace rating plate. At altitudes above 4000 ft. it must not exceed that on the rating plate less 4% for each

1000 ft.

Use the following procedure to determine the firing rate:

1.

Shut off all other gas fired appliances.

2.

Start the furnace and allow it to run for at least three minutes.

.

.

.

Measure the time (in seconds) required for the gas meter to complete one revolution.

Convert the time per revolution to cubic feet of gas per hour using Table 9. See page 28.

Multiply the gas flow rate in cubic feet per hour bythe heating value of the gas in Btu per cubic foot to obtain the firing rate in

Btuh. Example:

* Time for 1 revolution of a gas meter with a 1 cubic foot dial = 60 seconds.

* From Table 9 read 60 cubic feet per hour of gas.

* Heating value of the gas (obtained from gas supplier) = 1000 Btu per cubic foot.

* Firing rate = 1000 x 60 = 60,000 Btuh.

6.

See the "High Altitude Derate" section for additional information on firing rate at elevations above 4,000 ft.

The gas valve regulator is set at a nominal value of 3.5 in. water column for use with natural gas.

The manifold pressure must be set at 10.0 in.

water column for use with LP gas.

Verifying and Adjusting Temperature Rise

Verify that the temperature rise through the furnace is within the range specified on the furnace rating plate. Temperature rises outside the specified range could result in premature heat exchanger failure.

Place thermometers in the return and supply air stream as close to the furnace as possible.

The thermometer on the supply air side must be shielded from direct radiation from the heat exchanger to avoid false readings.

Adjust all registers and duct dampers to the desired position and run the furnace for fifteen minutes before taking any temperature readings.

The temperature rise is the difference between the supply and return air temperatures.

For typical duct systems, the temperature rise will fall within the range specified on the rating plate with the blower speed at the factory recommended setting, if the temperature rise measured is outside the range specified, it may be necessary to change the blower speed.

Lower blower speeds will increase the temperature rise and higher blower speeds will decrease the temperature rise.

27

TIME FOR

ONE REVOLUTION

(SECONDS)

24

26

28

30

32

44

46

48

50

34

36

38

40

42

58

60

62

52

54

56

64

GAS FLOW RATE (CUBIC FEET PER HOUR)

62

60

58

69

67

64

56

82

78

75

72

106

100

95

90

86

1

150

138

129

120

113

CUBIC FEET PER REVOLUTION

METER

5

750

692

643

600

563

OF

10

1500

1385

1286

1200

1125

529

500

474

450

429

409

391

375

360

1059

1000

947

900

857

818

783

750

720

346

333

321

310

300

290

281

692

667

643

621

600

581

563

TIME FOR

ON E R EVOLUTION

(SECOoNDS)

9O

92

94

96

82

84

86

88

19080

102

104

106

108

110

112

114

116

118

120

Table 9. Gas Flow Rate

32

31

31

33

33

32

30

36

35

35

34

4O

39

38

38

37

CUBIC FEET PER REVOLUTION

1

METER

5

45

44

43

42

41

225

220

214

209

205

OF

10

450

439

429

419

409

200

196

191

188

184

180

176

173

170

400

391

383

375

367

360

353

346

340

167

164

161

158

155

153

150

333

327

321

316

310

305

300

The furnace is equipped with a multispeed motor. Heating and cooling speed selection is made by moving the leads on the integrated control board located in the furnace. The wiring diagram on the furnace and Figure 30 show the speed taps for adjusting motor speed.

If it is desired that the blower operate at the same speed for heating and cooling, tape off the terminal of the unused blower wire. Install the jumper wire, found in the plastic instruction bag, across the HEAT and COOL taps on the control board. Reconnect the desired blower tap to the piggyback quick connect.

The blower control is designed to start the circulating air blower 30 seconds after the gas valve is opened.

The blower control is factory wired to turn the blower motor off 120 seconds after the gas valve is closed. This timing can be changed using the BLOWER OFF timing switch opposite the terminal block on the control board

(See Figure 27).

Verifying Burner Operation

To verify operation of the burners, remove front door and ensure that the door switch is in the "on" position (see Figure 29). Set the thermostat above room temperature and observe the ignition sequence.

The flame can be observed through the small clear window on the burner box. The burner flame should carry over be= tween all burners. The flames should be blue, without yellow tips. Flames should extend from each burner without lifting, curling, or floating.

28

After verifying ignition, set the thermostat below room temperature and verify that the burner flame extinguishes completely.

Replace the front door.

Verifying Operation of the Supply Air

Limit Switch

To verify operation of the supply air limit switch, make sure that the blower door is in place and that there is power to the furnace.

Completely block the return airflow to the furnace by installing a close-off plate in place of or upstream of the filter(s).

Set the thermostat above room temperature and verify that the Sequence of

Operation is as described in these instructions.

The supply air limit switch should function to turn off the gas valve within approximately five minutes.

The circulating air and combustion blowers should continue to run when the supply

FURNACE ACCESSORY

A/C Coil Box

Kit

Side Return Air Kit

Top Return Air Kit

Sloped Roof VentilAire III Kit

Sloped Roof VentilAire IV Kit

Soffit VentilAire Kit

Concentric Vent Termination Kit

(for horizontal and vertical venting)

Order Number

911969A

904003

904015

914098

914229

917201

904176 (3")

904177 (2")

Horizontal Exterior Vent

Mounting Kit (3" PVC)

Neutralizer Kit - All Models

902375

902377

Table 10.

Accessory Kits

KITS

air limit switchopens.Removethe close-off

MAINTENANCE

opens.Ifthefurnaceoperatesformorethanfive

minuteswith no returnair, setthe thermostat

It is recommended that the furnace be checked yearly. At a minimum, this check should include the following items: the furnace,and replacethe supplyair limit switch.

z: WARNING:

DESCRIPTION OF COMPONENTS

Figure 29 shows the location of each of the functional components described below. If any component of the furnace must be replaced, use only factory authorized replacement parts.

Contact your distributor for the approved replacement parts.

To avoid electricshock, personal injury, or death, turn off the power at the disconnect or the main service panel before performing any maintenance.

z WARNING:

Flame Sensor The flame sensor acts to prove that flame has carried over from the ignitor to the opposite end burner. If no flame is sensed, the furnace will be shut down automatically.

Gas Valve = The gas valve controls the flow of gas to the burners.

When the gas valve is energized it automatically opens and regulates the gas pressure in the manifold.

Pressure Switch = The pressure switch verifies that the inducer is drawing the combustion gases through the heat exchanger.

It also senses a blocked condensate drain condition.

Holes in the vent pipe or heat exchanger can cause products of combustion to enter the occupied space.

Replace the vent pipe or heat exchanger if leaks are found.

Failure to prevent products of combustion from being circulated into the occupied space can crate potentially hazardous conditions, including carbon monoxide poisoning, that could result in personal injury or death.

Deck Limit Switch (Auxiliary Limit) - The deck limit protects the furnace filter temperature from overheating when the motor has malfunctioned.

If the deck switch opens, the power for the furnace will shut down (see Figure

29).

Combustion Air and Vent System

Check the combustion air and vent pipe to ensure that it is not damaged, corroded or blocked by debris.

Any damaged section of vent pipe must be replaced, and any obstruction or blockage must be removed prior to operating the furnace.

Air Filter

Supply Air Limit Switch = The supply air limit switch prevents the air temperature leaving the furnace from exceeding the maximum outlet air temperature.

An air filter is supplied with the furnace as shipped from the factory.

Filters should be changed or cleaned monthly during the heating season.

New or newly renovated homes may require more frequent changing until the construction dust has been removed.

Vent Safety Switch - The vent safety switch shuts the furnace down if the outlet flue gas temperature increases above 145°F.

This switch protects the plastic flue system and the inducer from over-temperature conditions.

/ WARNING'.

Flame Roll-Out Switch - This switch provides flame roll=out protection to the furnace and combustion air inlet pipe.

Never operate the furnace without a filter in place, Dust and lint in the return air can build up on internal components, resulting in loss of efficiency, equipment damage, and possible fire,

29

Lubrication furtheroilingofthe bearingsis requiredforthe lifeofthe motor.

CondensateDrain Assembly

(i.e.avoidkinkinghoses).Alsomakesureall

hoseclampsaretightto avoiddrawingair into the system.

Blower Compartment

The blower compartment should be cleaned monthly during the heating and cooling seasons to remove any dirt and lint that may have accumulated in the compartment or on the blower and motor.

Dirt and lint can create excessive loads on the motor resulting in higher than normal operating temperatures and shortened service life.

Heat Exchanger and Burner Maintenance

The furnace should operate for many years without excessive soot buildup in the flue passageways, however, the flue passageways, the vent system, and the burners should be inspected and cleaned (if required) by a qualified service technician annually to ensure continued safe operation.

Particular attention must be given to identify deterioration from corrosion or other sources.

SYSTEM OPERATION

INFORMATION

GENERAL

Proper maintenance is most important to achieve the best performance from a furnace.

Follow these instructions for years of safe, trouble free operation.

Do not place combustible materials on or against the furnace cabinet or the vent pipe.

Do not store gasoline or any other flammable vapors and liquids in the vicinity of the furnace.

Change or replace the air filters monthly during any period when the circulating blower is operating regularly.

Always replace the doors on the furnace after servicing.

Do not operate the furnace without all doors and covers in place.

Avoid operating the furnace when windows and doors are open.

Be sure that the thermostat is properly installed and is not being affected by drafts or heat from lamps or other appliances.

Sequence of Operation

Operating sequences for the heating, cooling, and fan modes are described below. Refer to the wiring diagrams (Figures 30) and the low voltage field wiring diagram (Figure 26) for more details.

Heating Mode:

1.

On a call for heat the thermostat closes, applying 24 VAC to the W terminal on the control board.

2.

The control board checks for continuity on the 24 VAC limit control circuit (overtemperature limit switch, flame rollout switches and blocked vent switch in series). If an open limit is detected the control board will energize the inducer and the conditioned air blower. All other system functions will be inoperable until the limit circuit closes. While the limit is open, the red LED will pulse at a rate of 1 blink per unit time.

3.

The furnace control checks for continuity across the pressure switch (24 VAC).

If the pressure switch is closed the heat mode sequence will not continue.

If it remains closed for 10 seconds the red

LED will blink 3 times repetitively until the fault condition clears.

4. The inducer is energized.

5. The pressure switch will close.

If the pressure switch does not close after 10 seconds the fault LED will blink 2 times repetitively and the inducer will continue to run until the switch is closed.

6. The inducer will pre=purge for 30 seconds and then the igniter will start its warm-up as follows:

Initial Power up: After 30 seconds of igniter warm-up the gas valve (24 VAC) will then open.

The igniter circuit will stay energized for 3 seconds after the gas valve opens.

After Initial Power up: The control has a programmed adaptive ignition feature which varies the warm-up period as follows: If ignition is successful the warm=up is reduced by 3-seconds on each subsequent

30

call for heat until ignitionfailure occurs.

Uponignitionfailure,the warm-upis increasedby 3-secondson the nexttry. If successful,the timing remainsfixed at this level. In general,wheneverignition failure occurs the warm-up interval is increasedby 3-secondson the next try.

And if successful,it remainsthere.Minimumand maximumwarm-uptime limits are set at 6 and 54-seconds,respectively.

7. Thefurnacecontrolmustproveflamevia theflamesensor5 secondsafterthe gas valveopens.If flameis sensed,all burners are on andthe ignitorcoolsoff. If no flame is sensed,the gas valve closes immediatelyandthe inducercontinuesto run. A secondtrial for ignition(step 6) beginsif no flameis sensed.On the fifth tryforignition,thefurnacecontrolislocked out and the red LED will blink 4 times repetitively. The thermostat must be openedfor at leastten secondsto reset the furnacecontrolaftera lockout.Otherwise,the furnacewill attemptanother ignitionsequencein 1 hour.

8. The furnace control energizesthe circulatingair bloweron the heatingspeed

30 secondsafterthe gasvalvecircuitis energized

.

9.

When the thermostat has been satisfied, gas valve is de-energized.

10. The inducer is de-energized after a 30second postpurge.

11. The furnace control keeps the circulating air blower energized for 120 seconds

(factory set) or 60, 90, or 180 seconds

(field adjustable).

(See Figure 27.)

12. Abnormal conditions: If a limit opens during operation, the inducer and circulating air blower continue to operate. The gas valve is de-energized immediately.

The blowers continue to operate until the limit closes.

When the limit closes the inducer blower is de-energized immediately.

The circulating air blower continues to operate for the specified delay (factory set at 120 seconds).

2.

The furnace control energizes the circulating blower (115 VAC) on the cooling speed.

3.

When the thermostat is satisfied, the G and Y terminals on the control board are de-energized contactor.

opening the compressor

4.

The circulating air blower is de-energized after a 90-second delay.

Fan Mode:

1.

On a call for fan operation, the thermostat applies 24 VAC to the G terminal on the furnace control board.

2.

The circulating air blower is energized immediately on the heating speed.

3.

If the furnace is operated in the continuous ON position at the thermostat and is then switched to AUTO, the circulating blower will operate for a specified delay

(factory set at 120 seconds).

Furnace Fails to Operate

If the furnace does not operate check the following:

1.

Is the thermostat operating properly?

2.

Is the front door in place?

3.

Is the furnace disconnect closed?

4.

Has the circuit breaker tripped or the control board fuse burned open?

5.

Is the gas turned on?

6.

Are any manual reset switches open?

7.

Is the filter dirty or plugged?

8.

Is the flame sensor coated?

(Remove and clean with emery cloth.)

9.

Is the deck switch open?

If the furnace locks out after 5 attempts for ignition, it will try again every hour if a call for heat remains.

If the inducer and circulating air blowers are operating, and items 1 through 8 have been checked, press the red reset button on the vent safety switch. (See Figure 29.)

If the furnace operates after depressing the reset button, contact a qualified service technician to identify and repair the problem.

Cooling Mode:

1.

On a call for cooling the thermostat closes, applying 24 VAC to the G and Y terminals on the furnace control.

This closes the compressor contactor.

If furnace still fails to operate, depress the red reset buttons on the flame roll-out switch.

If the furnace operates after depressing the reset button, contact a qualified service technician to identify and repair the problem.

31

Component Location

1 Door Assembly - Louvered

2 Filter Inside Door

3 Blower Assembly

4 Control Board

5 Pressure Switch

6 Flame Rollout Switch

7 "J" Trap Hard Tube

8 LowVoltageTransformer

9 In Line Drain Assembly

10 Junction Box

11 Vent Safety Switch

Figure 29. M3 DownflowFurnace

12 Ignitor Assembly

13 Burner View Port

14 Main Limit Switch

15 Coil Cabinet Assembly (Optional)

16 Flame Sensor (On Burner Box)

17 Gas Valve

18 Switch, On/Off

19 Blower, Inducer

20 Orifice (In Burner Box)

21 Aux. Limit

22 Burner Box

32

SUPPLY AIR

_s)LIMIT SWITCH

BLUE

FLAME ROLL-OUT

SW_TC H

BLUE

VENT

SAFETY

SWITCH

WHITE (NEUTRAL) .....

BLACK 120V .....

GROUND ....

ROOM THERMOSTAT

'I_ GREEN

WHITE W/BLK

E] TRANSFORMER

STRIPES

STRIPES

,vl[ WHIT ....

BLACK BLK W/WHITE

BLOWER DECK SWtTCH

IITIONER

I

I

I

I m

I

I

I

I

I

I I

I= r

FLAMESENSOR

RED

YELLOW

BROWN

= = i

_]mCWl_A&$

IGNITOR

|l-" i, ,4" :_r_-

Legend

Field Wiring

Factory Wiring:

Low Voltage

High VoJtage

==_._L====

BLACK

BLACK

ORANGE

BLUE

BLACK

2 _

3

4

5

MOTOR

PLUG

FAULT CONDITION

Power On

Limit Circuit Open or External

(Does not apply to Deck Switch,

Load On "W" see below)

Pressure

Pressure

Switch Open with inducer

Switch Closed with inducer

On

On ignition Failure (Check Ground)

115 VAC & Neutral Reversed or no Ground

False Flame or Gas Valve Relay Shorted

Power Off or Deck Limit Open

FAULT CONDiTiON

Low Flame Sensor Signal

Flame Present

STATUS

RED

LIGHT

ON

1 FLASH

2FLASHES

3FLASHES

4 FLASHES

5 FLASHES

Continuous

OFF

FLAME

YELLOW

LIGHT

Continuous

Flash

ON

if any of the original

wire as supplied with the furnace must be replaced, it must be replaced with wiring material having a temperature rating of at least 105 ° C.

Use copper conductors only.

Factory Wired

Heating Speeds

Furnace

input, Btuh

Wire

Color

60,000

80,000

Red

Blue

Figure 30.

Downflow Furnace Wiring Diagram

WD#710240B

33

1

NOMINALBLACK

IRON

PIPE

DIAMETER_

1/2

3/4

1

1/4

10

280

130

520

1,050'

90

190

350

730'

LENGTH OF PIPE BUN (FT)

75

150

285

590

65 i30'

245

500'

760

55

115

215

440

670

50 i05

195

400

610 i

45

95

180

370 i

40

90

170

350

1 1/2 1,600 1,100 890

NOTES

The cubic feet per hour listed in the table above must be greater than the cubic feet per hour of gas flow required by the furnace. To determine the cubic feet per hour of gas flow required by the furnace, divide the input rate of the furnace by the heating value (from gas supplier) of the gas.

input To Furnace (Btu/hr)

Cubic Feet Per Hour Required =

Heating Value of Gas (Btu/Cu. Ft.)

Table 11. Black Iron Gas Pipe Capacities

IVlodel

Number

IVl3RL-

060A-A!BW

080A-A!BW

Heating

Input

(Btuh)

Number of

Burners

60,000

80,000

4

5

0 - 2,000 ft

Nat. Gas LP

50

49

57

1.15mm

2,000 ft - 4,000 ft

Nat. Gas LP

50

49

57

1.15mm

Altitude Above Sea Level

4,000 - 6,000 ft

Nat. Gas LP

51

50

58

57

6,000 - 8,000 ft

Nat. Gas LP

51

50

58

57

Table 12. Approximate Orifice Size for Natural and LP Gases

8,000 - 10,000 ft

Nat. Gas LP

52

51

59

58

34

35

iNSTALLER NAME:

CiTY

STATE iNSTALLATiON ADDRESS:

CiTY STATE

UNiT MODEL #

UNiT SERIAL #

Electrical connections tight?

Line voltage polarity correct?

Supply Voltage:

Has the thermostat been calibrated?

is the thermostat level?

is the heat anticipator setting correct_

YES

YES

YES

YES

YES

NO

NO

VOLTS

NO

NO

NO

Minimum clearances

Has the owner's information been reviewed with the homeowner?

YES

I Has the literature package been left near

NO

NORD E

O'Falton, MO

EFFICIENCY

RA_ING

Gas Type: (circle one)

Gas pipe connections leak tested?

Gas Line Pressure: is there adequate fresh air supply for combustion and ventilation?

Installation Altitude:

Deration Percentage:

Furnace Input:

Supply Air Temperature:

Return Air Temperature:

YES

YES

Temperature Rise:

Propane

NO

(in - W.C.)

NO

(FT.)

(%)

(Btuh)

(o F)

(o F)

(o F_

Vent free restrictions?

from

Filter(s) secured in place?

Filter(s) clean?

Flue connections tight?

is there proper draft?

YES

YES

YES

YES

YES

708768C (Replaces 708768B)

IllIIIIIlilllillllllll

without notice or incurring obligations

Printed in U .S.A (03/09)

708768C

NO

NO

NO

NO

NO

advertisement

Key Features

  • 90%+ AFUE rating for high efficiency
  • Variable-speed blower motor for consistent airflow
  • Sealed combustion for safety and efficiency
  • Direct vent design for ease of installation
  • Compact size for easy fit in tight spaces

Related manuals

Frequently Answers and Questions

What is the AFUE rating of the Nordyne M3RL 080A AW?
The AFUE rating of the Nordyne M3RL 080A AW is 90+.
What type of blower motor does the Nordyne M3RL 080A AW have?
The Nordyne M3RL 080A AW has a variable-speed blower motor.
Is the Nordyne M3RL 080A AW a direct vent furnace?
Yes, the Nordyne M3RL 080A AW is a direct vent furnace.
What are the dimensions of the Nordyne M3RL 080A AW?
The dimensions of the Nordyne M3RL 080A AW are 35-1/2" H x 19-3/4" W x 23-3/4" D.

advertisement