- Industrial & lab equipment
- Electrical equipment & supplies
- Power conditioning
- Uninterruptible power supplies (UPSs)
- Vertiv
- Liebert EXM 208 Volt BDC
- User manual
advertisement
Liebert® EXM BDC
Bypass Distribution Cabinet
Installer/User Manual
10-100kVA, 60Hz
The information contained in this document is subject to change without notice and may not be suitable for all applications. While every precaution has been taken to ensure the accuracy and completeness of this document, Vertiv™ assumes no responsibility and disclaims all liability for damages resulting from use of this information or for any errors or omissions. Refer to other local practices or building codes as applicable for the correct methods, tools, and materials to be used in performing procedures not specifically described in this document.
The products covered by this instruction manual are manufactured and/or sold by Vertiv. This document is the property of Vertiv and contains confidential and proprietary information owned by Vertiv. Any copying, use or disclosure of it without the written permission of Vertiv is strictly prohibited.
Names of companies and products are trademarks or registered trademarks of the respective companies. Any questions regarding usage of trademark names should be directed to the original manufacturer.
Technical Support Site
If you encounter any installation or operational issues with your product, check the pertinent section of this manual to see if the issue can be resolved by following outlined procedures.
Visit https://www.Vertiv.com/en-us/support/ for additional assistance.
Vertiv™ | Vertiv | Liebert® EXM™ BDC User Manual
TABLE OF CONTENTS
1.4.1 Power Cable Installation
1.4.3 Accessory Fuses and Back-Feed Breaker Wiring
3.1 Electrical Characteristics
3
This page intentionally left blank
4
VertVertiv™ | Liebert® EXM BDC User Manual
IMPORTANT SAFETY INSTRUCTIONS
SAVE THESE INSTRUCTIONS
This manual contains important instructions that should be followed during installation of the Vertiv™ Liebert® EXM BDC
User Manual (Bypass Distribution Cabinet).
Read this manual thoroughly, paying special attention to the sections that apply to your installation, before working with the
UPS. Retain this manual for use by installing personnel.
A properly trained and qualified electrical contractor should oversee the installation of the equipment.
The Liebert EXM BDC cannot be put into operation until it is commissioned by the manufacturer or authorized engineer.
Otherwise, human safety may be endangered and damage to the UPS will not be covered by the warranty.
The Liebert EXM BDC is designed for commercial and industrial uses and cannot be used as life support equipment.
WARNING! Risk of moving heavy equipment and electric shock. Can cause damage to the equipment , injury and death. Exercise extreme care when handling UPS cabinets to avoid damage to the equipment or injury to the personnel. The weight of the Liebert EXM BDC ranges from 660lb. to 1752 lb. (300kg to 794kg).
Determine the weight of the unit’s and locate the center of gravity symbols before handling the Liebert
EXM BDC. Test lift and balance the cabinet before transporting it. Never tilt the equipment more than 15 degrees from vertical. In the case of fire involving electrical equipment, use only carbon dioxide fire extinguishers or those approved for use in fighting electrical fires. Extreme caution is required when performing maintenance. Be constantly aware that the UPS system contains high DC as well as AC voltages.
Check for the voltage with both the AC and DC voltmeters prior to making contact.
AVERTISSEMENT! Risque lors du déplacement de l'équipement lourd et de décharge électrique pouvant entraîner des dommages matériels, des blessures et même la mort. Faites preuve d'une extrême prudence lors de la manutention des armoires ASC afin d'éviter de les endommager ou de blesser le personnel. Les armoires Liebert EXM BDC pèsent de 660 lb à 1752 lb (de 300 kg à 794 kg). Déterminez le poids de l'unité et trouvez les symboles de centre de gravité avant de déplacer l'armoire Liebert EXM BDC. Faites des essais de levage et d'équilibre avant de transporter l'armoire. N'inclinez jamais l'équipement à plus de 15 degrés à la verticale. En cas d'incendie associé à du matériel électrique, n'utilisez que des extincteurs à dioxyde de carbone ou homologués pour la lutte contre les incendies d'origine électrique. Les opérations d'entretien requièrent une extrême prudence. Soyez toujours conscient du fait que le système ASC contient des tensions c.c. et c.a. élevées. Vérifiez les tensions avec des voltmètres c.a. et c.c. avant d'établir tout contact.
1
2
WARNING! Risk of electric shock. it can can cause damage to the equipment, injury and death. As with other types of high power equipment, dangerous voltages are present within the UPS and battery enclosure even after the input power has been disconnected. The risk of contact with these voltages is minimized as the live component parts are housed behind a metal panel. Further internal safety screens make the equipment protected to IP20 standards. Never remove the panels or the covers or open the doors that will expose the internal components to the contact. Read and follow all warnings, cautions and safety and operating instructions to avoid serious injury or death from electric shock. No risk exists to any personnel when operating the equipment in the normal manner, following the recommended operating procedures. All equipment maintenance and servicing procedures involve internal access and should be carried out only by a trained personnel.
AVERTISSEMENT! Risque de décharge électrique pouvant entraîner des dommages matériels, des blessures et même la mort. À l'instar des autres types d'équipement haute puissance, des tensions dangereuses sont présentes à l'intérieur de l'armoire ASC et du châssis de batteries même après le débranchement de l'alimentation d'entrée. Le risque de contact avec ces tensions est diminué, car les parties de composants sous tension sont abritées derrière un panneau métallique. D'autres écrans de sécurité internes protègent l'équipement en conformité avec les normes IP20. Ne retirez jamais les panneaux ou les couvercles et n'ouvrez pas les portes donnant accès aux composants internes avec lesquels vous pouvez entrer en contact.
Veuillez lire et suivre l'ensemble des avertissements, des mises en garde et des instructions de sécurité et de fonctionnement afin d'éviter des blessures graves, voire la mort, pouvant être causées par une décharge
électrique. Il n'y a aucun risque pour le personnel lorsque l'équipement est utilisé normalement, en suivant les procédures de fonctionnement recommandées. Toutes les procédures de réparation et d'entretien de l'équipement exigent un accès à l'intérieur de l'armoire et devraient être menées uniquement par du personnel compétent.
Ground Leakage Currents
WARNING! Risk of electric shock from high leakage current. Can cause injury, damage to the property damage and death. EARTH CONNECTION IS ESSENTIAL BEFORE CONNECTING THE INPUT SUPPLY. The earth leakage current exceeds 3.5 mA and is less than 1000 mA. Transient and steady-state earth leakage currents, which may occur when starting the equipment, should be taken into account when selecting the instantaneous Residual Current Circuit Breakers (RCCBs) or Residual Current Devices (RCD). RCCBs must be selected sensitive to DC unidirectional pulses (Class A) and insensitive to the transient current pulses. Note also that the earth leakage currents of the load will be carried by this RCCBs or RCD. This equipment must be earthed in accordance with the local electrical code of practice.
AVERTISSEMENT! Risque de décharge électrique due à un courant de fuite élevé pouvant causer des blessures, des dommages matériels et même la mort. IL EST PRIMORDIAL D'ASSURER UNE CONNEXION DE
TERRE AVANT DE BRANCHER L'ALIMENTATION D'ENTRÉE. La fuite à la terre est supérieure à 3,5 mA et inférieure à 1 000 mA. Vous devez tenir compte des fuites de courant transitoires et permanentes à la terre, susceptibles de se produire au démarrage de l'équipement, lors de la sélection des dispositifs DDFT instantanés. Vous devez sélectionner des disjoncteurs différentiels de fuite à la terre (DDFT) sensibles aux impulsions unidirectionnelles c.c. (classe A) et insensibles aux impulsions de courant transitoires. Notez
également que les courants de fuite à la terre de la charge seront acheminés par ce dispositif DDFT. Cet
équipement doit être mis à la terre conformément au code national de l'électricité.
VertVertiv™ | Liebert® EXM BDC User Manual
WARNING! Risk of the electric shock. it can cause damage to the property, injury and death. Under typical operation and with all UPS doors closed, only normal safety precautions are necessary. The area around the
UPS system should be kept free of puddles of water, excess moisture and debris. Special safety precautions are required for procedures involving handling, installation and maintenance of the UPS system and the internal batteries (internal batteries accommodated by the 10-40kVA frame only). Observe all safety precautions in this manual before handling or installing the UPS system as well as during all the maintenance procedures. Observe all battery safety precautions before working on or near the battery. This equipment contains several circuits that are energized with high voltage. Only test equipment designed for troubleshooting should be used. This is particularly true for the oscilloscopes. Always check with the AC and
DC voltmeters to ensure safety before making contact or using the tools. Even when the power is turned Off, dangerously high electric charges may exist within the UPS. All power and control wiring should be installed by a qualified electrician. All the power and control wiring must comply with the NEC and applicable local codes. ONLY qualified service personnel should perform maintenance on the UPS system. When performing maintenance with any part of the equipment under power, the service personnel and test equipment should be standing on rubber mats. The service personnel should wear insulating shoes for isolation from direct contact with the floor (earth ground). Never work alone, even if all the power is removed from the equipment.
A second person should be standing by to assist and summon help in the case an accident should occurs.
AVERTISSEMENT! Risque de décharge électrique pouvant causer des blessures, des dommages matériels et même la mort. Les précautions de sécurité habituelles suffisent lorsque le système ASC est en mode de fonctionnement normal et que toutes les portes sont fermées. La zone entourant le système ASC doit être exempte de flaques d’eau, d’humidité excessive et de débris. Des précautions de sécurité spéciales sont requises pour les procédures associées à la manutention, à l’installation et à l’entretien du système ASC.
Observez toutes les précautions de sécurité décrites dans le présent manuel avant de manipuler ou d’installer le système ASC, ainsi que pendant toutes les procédures d’entretien. Cet équipement comporte plusieurs circuits à haute tension. Seuls des équipements d’essai conçus pour le dépannage doivent être utilisés. Cette mise en garde couvre notamment les oscilloscopes. Utilisez toujours des voltmètres c.a. et c.c.
pour vérifier les tensions avant d’établir un contact ou d’utiliser des outils. Des tensions dangereusement
élevées peuvent demeurer dans le système ASC même une fois l’alimentation coupée. Tous les câbles d’alimentation et de contrôle doivent être installés par un électricien qualifié. Tous les câbles d’alimentation et de contrôle doivent être conformes au Code national de l’électricité des États-Unis (NEC) et celui du Canada, ainsi qu’aux codes locaux en vigueur. L’entretien du système ASC ne doit être confié qu’à des professionnels qualifiés. Les responsables de l’entretien et l’équipement d’essai doivent reposer sur des tapis de caoutchouc lors de toute intervention sur une pièce d’équipement sous tension. Les responsables de l’entretien doivent porter des chaussures isolantes pour prévenir tout contact direct avec le plancher. Ne travaillez jamais seul, même si toute l’alimentation d’entrée est coupée de l’équipement. Une seconde personne devrait toujours
être présente pour porter assistance ou chercher de l’aide en cas d’accident.
NOTICE
Risk of improper ground connection. It can cause the equipment damage. The ground connection is essential before connecting the input supply. This equipment must be grounded in accordance with the local electrical codes. Maximum load must not exceed that shown on the UPS rating label.
IMPORTANT SAFETY INSTRUCTIONS
3
NOTICE
Risk of improper electromagnetic shielding. It can cause radio communication interference. This unit complies with the limits for a Class A digital device, pursuant to Part 15 Subpart J of the FCC rules. These limits provide reasonable protection against harmful interference in a commercial environment. This unit generates, uses and radiates radio frequency energy and, if not installed and used in accordance with this instruction manual, may cause harmful interference to radio communications. This unit is not designed for use in a residential area. Operation of this unit in a residential area may cause harmful interference that the user is solely responsible for correcting.
4
VertVertiv™ | Liebert® EXM BDC User Manual
GLOSSARY OF SYMBOLS
Risk of Electrical Shock
Indicates caution followed by important instructions
AC Input
DC Output
Requests the user to consult the manual
Indicates the unit contains a valve-regulated lead acid battery
Recycle
DC Voltage
AC Voltage
Equipment grounding conductor
Bonded to ground
5
This page intentionally left blank
6
VertVertiv™ | Liebert® EXM BDC User Manual
1 LIEBERT® EXM BDC
The Liebert EXM BDC is designed to operate in UPS normal mode, static bypass mode and maintenance mode. The
Liebert EXM BDC offers 10-100kVA capacity to match the associated Vertiv™ Liebert® EXM frame offerings. Each of the
Liebert EXM BDC capacities offer optional input 208V, 220V, 480V and 600V internal transformers as well as multiple output distribution selections.
Figure 1.1 Single Input UPS (with External Liebert EXM BDC and Optional Internal Transformer) - Typical
Configuration
ITEM DESCRIPTION ITEM DESCRIPTION
1
2
3
System AC Input 3 Wire + GND
BATTERY
UPS CABINET
4
5
BIB - Bypass Isolation Breaker
BYPASS DISTRIBUTION CABINET
6 MBB - Maintenance Bypass Breaker
*External Overcurrent Protection by Others
7
8
9
10
11
STATIC BYPASS
MIB - Maintenance Isolation Breaker
(Optional) 54 Pole See Note 5
AC Output 208V 4 Wire + GND
Local Grounding Electrode See Note 1
NOTES TO FIGURE:
1.
Install in accordance with the national and the local electrical codes.
2.
Input and bypass must share the same single source.
3.
UPS system input and output cables must be run in separate conduits.
4.
Control wiring must be run in separate conduits.
5.
Optional 54 pole, 225A for 10-40kVA frame only or optional 54 pole 400A for 60-100kVA frame only.
6.
Transformers available are with input voltage of 208V, 220V, 480V, and 600V.
7
8
1.1 Normal (UPS) Mode
While the Liebert® EXM BDC is in Normal Mode (MBB open; BIB/MIB closed), the UPS is supplying the connected load with continuous, high-quality AC power. In this mode of operation, the load is protected by the UPS.
1.2 Maintenance Mode
When the Liebert EXM BDC is in Maintenance Mode (MBB closed; BIB/MIB open), it provides an alternate path for power to the connected equipment should the UPS need to be taken out of service for limited maintenance or repair. In this mode of operation, no power is supplied to the UPS and the load is NOT protected by the UPS.
1.3 Cable Installation
1.3.1 Wiring Preparation
Be sure that the unit is not connected to any AC utility power source or the UPS before installing any wiring to this unit. This
Liebert EXM BDC should be installed by a qualified/certified electrician.
WARNING! Risk of electrical shock and arc flash. Can cause damage to the property, injury and death. Read this section thoroughly before attempting to install wiring to this unit. Read and comply with all the warnings and cautions in this manual.
Removing the Cover Plates
Cover Plates are given to the input and the output terminals on the front of the Liebert EXM BDC (see
on page no. 8). Remove these plates and keep the screws and plates for reinstallation.
Figure 1.2 Liebert EXM BDC-Access Plate Removed
VertVertiv™ | Liebert® EXM BDC User Manual
1.4 Locating the Cabinet
This Liebert® EXM BDC may be mounted to the right of the UPS or installed as a stand-alone unit. Ensure that the unit is placed in a well-ventilated area and that there is clearance for access to the switches and the cable connections as required by the national and the local codes.
1.4.1 Power Cable Installation
NOTE: Transient and steady state earth leakage currents may occur when starting the equipment. This should be taken into account when selecting the ground current detection devices because these will carry the earth leakage currents of both the UPS equipment and the load.
1.4.2 Input/Output Wiring
Follow the steps below to connect the input wiring:
NOTE: Input wiring must be installed using conduit if the cabinet is not mounted to the immediate right of the UPS.
1.
Locate the input wiring access (top or bottom access), remove the conduit landing plate and punch the appropriate size hole for the size conduit being used. Pull the three/four input wires through it, allowing some slack for installation. For the cabinets that are located to the immediate left of the UPS, the access plate is on the lower right of the cabinet. Remove the access plate and verify that the edge guarding is installed and intact.
2.
Secure the conduit to the access plate of the Liebert® EXM BDC.
3.
Input power cables connect to the system input bus; refer to
4.
Connect the ground (earth) wire to the earth busbar and tighten it to 428 lb.-in. (48Nm) for M12 bolt.
5.
Locate the UPS input and output cables and the access panel to the UPS on the lower right side.
NOTE: If the Liebert EXM BDC is not to be bolted to the UPS, use either top or bottom access plate.
6.
Connect the system ground cable between the Liebert EXM BDC and the UPS and tighten the connections to
428 lb.-in. (48Nm) for M12 bolt.
7.
Connect the system input cables between the Liebert EXM BDC "UPS Input" Busbars (A-B-C-N terminals) and the UPS input busbars (A-B-B N terminals) and tighten the connections to 428 lb.-in. (48Nm) for M12 bolt.
8.
Connect the system output cables between the Liebert EXM BDC "UPS Output" Busbars (A-B-B N terminals) and the UPS output busbars (A-B-C N terminals) and tighten the connections to 428 lb.-in. (48Nm) for M12 bolt.
9.
Connect TB1 from the Liebert EXM BDC to J23, J24 and J26 on the Liebert® EXM.
NOTICE
Risk of improper wiring connection. Can cause damage to the equipment. The control wire must be installed to ensure proper operation of the system and fully protect the load when switching between the bypass cabinet and the UPS.
Notes
1.
All interconnection hardware will be supplied by Vertiv™.
2.
AC connections must be made to the UPS module before attaching the Liebert EXM BDC to the UPS module.
3.
All cabling will be field-supplied when a Liebert EXM BDC is configured as a stand-alone cabinet.
4.
Liebert EXM BDC's must attach to only the right side of the Liebert® EXM UPS.
5.
Refer to individual drawing of each piece of the equipment for additional details.
1 Liebert® EXM BDC
9
Table 1.1 Control Wiring for Liebert® EXM to Liebert EXM BDC
FROM TO FROM TO
Liebert EXM UPS Bypass Module
(X9 J23, J24 and J26)
J24-3
FH1-B
J26-17
J26-19
Liebert EXM BDC Terminal Strip
(TB1)
TB1-7
TB1-8
TB1-6
TB1-5
Liebert EXM UPS Bypass Module
(X9 J23, J24 and J26)
J26-21
J23-4
J23-6
FH1-N
Liebert EXM BDC Terminal Strip
(TB1)
TB1-3
TB1-11
TB1-12
J24-1
J26-23 TB1-4
Refer to
on page no. 11 for the location of fuse block FH1 and to
Figure 1.1
on page no. 1 for the location of J23, J24 and J26
10
VertVertiv™ | Liebert® EXM BDC User Manual
1.4.3 Accessory Fuses and Back-Feed Breaker Wiring
Figure 1.3 Liebert® EXM BDCLiebert EXM BDC wiring, Without Transformer Option, Single Input
NOTES TO FIGURE:
1.
Wiring furnished by factory.
2.
Customer-furnished grounding electrode conductor to be installed in accordance with the National Electric
Code Article 250-26.
1 Liebert® EXM BDC
11
Figure 1.4 Liebert® EXM BDC Wiring with Transformer Option, Single Input
12
NOTES TO FIGURE:
1.
Wiring furnished by factory.
2.
Customer-furnished grounding electrode conductor to be installed in accordance with the National Electric
Code Article 250-26.
VertVertiv™ | Liebert® EXM BDC User Manual
Figure 1.5 Wiring For LDMF with Panelboard
NOTES TO FIGURE:
1.
Wiring furnished by factory.
2.
Customer-furnished grounding electrode conductor to be installed in accordance with the National Electric
Code, Article 250-26.
1 Liebert® EXM BDC
13
Figure 1.6 Wiring for LDMF with subfeed breakers
14
NOTES TO FIGURE:
1.
Wiring furnished by factory.
2.
Customer-furnished grounding electrode conductor to be installed in accordance with the National Electric
Code, Article 250-26.
3.
Cut off the connector from the end of the wires and discard it. Then splice Item 97 to the wires on the display board using Item 98 as shown.
VertVertiv™ | Liebert® EXM BDC User Manual
1.5 Bolting Cabinets Together
NOTE: The UPS wiring must be completed before the cabinets are bolted together.
1.
Line up the cabinets so that the mounting holes are aligned.
2.
Using supplied hardware, bolt the cabinets together. The bolts may be inserted from either the UPS side or from the Liebert® EXM BDC side, whichever is more convenient.
Figure 1.7 Bolting Liebert EXM UPS to a Liebert EXM BDC
ITEM DESCRIPTION
2
3
1 Washer Flat, M10
Washer Split, M10
Hex Head Bolt, M10 x 30mm
NOTES TO FIGURE
1.
Place the cabinets so that the mounting holes are aligned.
2.
A bolt from the adjacent cabinet may be screwed into the threaded top hole or a bolt may be inserted through the lower and screwed into the threaded hole in the adjacent cabinet.
1 Liebert® EXM BDC
15
16
WARNING! Risk of heavy units tipping over while being moved. Can cause damage property, injury and death.
The Liebert® EXM BDC and battery cabinets must be properly prepared and secured for lifting. Improper lifting may cause the cabinets to fall, causing the equipment damage, personal injury and death. Vertiv™ recommends lifting the units by placing the suitable straps on the Liebert EXM BDC or the battery cabinet.
The straps must go under the unit to be lifted.
AVERTISSEMENT! Le centre de gravité élevé des appareils présente un risque de renversement lors des déplacements, pouvant entraîner des dommages matériels, des blessures et même la mort. Les armoires
Liebert® EXM BDC et de batterie doivent être correctement préparées et sécurisées avant d’être levées. Un mauvais levage peut faire tomber les armoires, causant des dommages à l'équipement, des blessures, voire la mort. Vertiv™ recommande de soulever les unités en suivant l'une des méthodes suivantes :
• En installant quatre anneaux de levage dans les ouvertures fabriquées en usine, avec un anneau dans chaque coin de l’appareil, pour ensuite fixer les câbles ou sangles aux anneaux afin d'effectuer le levage à l'aide d'un mécanisme approprié.
• En plaçant des sangles convenables sur l'armoire Liebert ou de batterie. Les sangles doivent passer sous l'unité à soulever.
1.5.1 Floor Installation
If the Liebert EXM BDC is to be placed on a raised floor, the Liebert® EXM UPS should be mounted on a pedestal that will support the equipment point loading. Refer to the Liebert® EXM UPS Installer/User Guide, (SL-25648 or SL-25650), to design this pedestal.
1.5.2 Cable Entry
The Cables can enter the Liebert EXM BDC from the top or bottom through the removable metal plates.
Some plates have factory-punched holes and others are designed to allow the personnel to punch the holes for fitting and securing the conduit. Once the conduit holes are punched, these plates should be reattached to the UPS. The conduit size and wiring method must be in accordance with all the local, regional and national codes and regulations, including the NEC
ANSI/NFPA 70.
NOTE: When installing the UPS, the customer must provide a disconnect with overcurrent protection at the output of the UPS.
VertVertiv™ | Liebert® EXM BDC User Manual
1.5.3 Optional Cabinets
The Liebert® EXM BDC must be bolted to the right side of the Liebert EXM (see
The Liebert EXM BDC must be cabled and bolted to the Liebert EXM before the UPS and the bypass distribution cabinet are moved into their final position. Connect input wiring to the Liebert EXM BDC ONLY after the units are internally cabled and positioned.
Figure 1.8 Cabinet Arrangement
ITEM
1
2
3
DESCRIPTION
Liebert EXM BDC
Battery Cabinet
Liebert EXM BDC
NOTES TO FIGURE:
1.
The Liebert EXM UPS connected to the Liebert EXM BDC (The Liebert EXM BDC must be on the right side of the Liebert EXM UPS)
2.
The Liebert EXM UPS connected to the Liebert EXM BDC and the Battery Cabinets (the Liebert EXM BDC must be on the right side of the Liebert EXM UPS) the (Battery Cabinets must be on the left side of the
Liebert EXM UPS)
1 Liebert® EXM BDC
17
This page intentionally left blank
18
VertVertiv™ | Liebert® EXM BDC User Manual
2 INSTALLATION DRAWINGS
Figure 2.1 Liebert® EXM BDC with 225A or 400A Panelboards—Main Components
ITEM DESCRIPTION ITEM DESCRIPTION
2
3
1
4
System Input Bus
BIB - Bypass Isolation Breaker
MBB - Maintenance Bypass Breaker
MIB - Maintenance Isolation Breaker
5
6
7
Neutral Bus
Ground Bus
Panelboard
NOTES TO FIGURE
1.
Dimensions are in inches (mm).
2.
The control wiring and the power wiring must be run in separate conduits.
3.
All wiring must be in accordance with the national and the local electrical codes.
4.
If the bypass distribution cabinet is attached to the right side of the UPS, Vertiv™ will supply the interconnection cables.
19
Figure 2.2 Liebert® EXM BDC with Two Subfeed Breakers - Main Components
20
ITEM
2
3
1
4
DESCRIPTION
System Input Bus
BIB - Bypass Isolation Breaker
MBB - Maintenance Bypass Breaker
MIB - Maintenance Isolation Breaker
ITEM
5
6
7
8
DESCRIPTION
Neutral Bus
Ground Bus
Subfeed Breakers
LDMF inside front door
NOTES TO FIGURE
1.
All dimensions are in inches (mm).
2.
The control wiring and the power wiring must be run in separate conduits.
3.
Copper cables only are recommended.
4.
All the wiring is to be in accordance with the national and the local electrical codes.
5.
When the Liebert EXM BDC is attached to the UPS, Vertiv™ will supply the interconnection cables.
6.
225A panelboard for 10-40kVA only. 400A panelboard for 60-100kVA only
VertVertiv™ | Liebert® EXM BDC User Manual
Figure 2.3 Liebert® EXM BDC with Optional SKRU and Transformer
ITEM
4
5
6
2
3
1
DESCRIPTION
System Input Bus
BIB - Bypass Isolation Breaker
MBB - Maintenance Bypass Breaker
MIB - Maintenance Isolation Breaker
Neutral Bus
Ground Bus
ITEM
7
8
9
10
11
DESCRIPTION
LDB
Transformer Option for 208V, 220V, 480V or 600V Input
Lamp
Key Operator
Kirk Keys
2 Installation Drawings
21
Figure 2.4 Busbars - Liebert® EXM BDC with Panelboard
22
ITEM DESCRIPTION
4
5
6
1
2
3
BIB - Bypass Isolation Breaker
MIB - Maintenance Isolation Breaker
MBB - Maintenance Bypass Breaker
Panelboard
Ground Busbar
Neutral Busbar
NOTES TO FIGURE
1.
All dimensions are in inches (mm).
2.
The control wiring and power wiring must be run in separate conduits.
3.
All wiring is to be in accordance with the national and the local electrical codes.
4.
Vertiv™ will supply the interconnection cables when the Liebert® EXM BDC is attached to the UPS.
5.
225A panelboard for 10-40kVA only. 400A panelboard for 60-100kVA only.
VertVertiv™ | Liebert® EXM BDC User Manual
Figure 2.5 Busbars - Liebert® EXM BDC
ITEM
1
2
3
4
DESCRIPTION
Neutral Input/Output Connections
Input Ground Bus
System Input Connections
System Input Busbar at Rear, Typical
2 Installation Drawings
ITEM
5
6
7
DESCRIPTION
Input Breaker
UPS Bus Ø 0.44" (11mm) Typical
System Input Bus See Detail B
23
Figure 2.6 Lineup Arrangement, Liebert® EXM with Liebert® EXM BDC
24
NOTES TO FIGURE
1.
All dimensions are in inches (mm).
2.
24" (610mm) minimum clearance above the unit. 36" (914mm) front access required for service. For seismic mounting only, 5" (102mm) in rear for mounting brackets.
3.
Keep the cabinet within 15 degrees of vertical.
4.
Top and bottom cable entry available through removable access plates. Remove, the punch to suit the conduit size and replace.
5.
Unit bottom is structurally adequate for forklift handling.
6.
The control wiring and the power wiring must be run in the separate conduits.
7.
All the wiring is to be in accordance with national and local electrical codes.
8.
Bypass distribution cabinet must be positioned on the right side of the UPS.
VertVertiv™ | Liebert® EXM BDC User Manual
Figure 2.7 Outline Drawing, Liebert® EXM BDC For Liebert® EXM, 10-100kVA
ITEM
2
1
DESCRIPTION
Leveling Feet
Cable Entry Area 11.4" x 13.2" (290 x 335mm)
NOTES TO FIGURE
1.
All dimensions are in inches (mm).
2.
24" (610mm) minimum clearance above unit; 36" (914mm) front access required for service.
3.
Keep the cabinet within 15 degrees of vertical.
4.
Top and bottom cable entry available through removable access plates. Remove, punch to suit conduit size and replace.
5.
The control wiring and the power wiring must be run in separate conduits.
6.
All wiring is to be in accordance with national and local electrical codes.
2 Installation Drawings
25
Figure 2.8 Liebert® EXM BDC Transformer Location
26
ITEM
1
DESCRIPTION
Transformer
VertVertiv™ | Liebert® EXM BDC User Manual
Table 2.1 Wiring for Liebert® EXM to Liebert® EXM BDC
RUN FROM TO
F
G
D
E
A
B
C
Utility AC source
Utility AC source
BDC Bypass Isolation Breaker
BDC Bypass Isolation Breaker
UPS Output
UPS Output
BDC Panelboard
BDC System Input Bus
BDC System Input Bus
UPS Main Input
UPS Main Input
Liebert EXM BDC Maintenance Isolation Breaker
Liebert EXM BDC Maintenance Isolation Breaker
Load AC Connection
H
I
BDC Panelboard
Utility AC Source
Load AC Connection
All Ground Connections
J BDC Terminal Block TB1 UPS Static Bypass Module J23, J24 and J26
See
on page no. 10 for additional details.
CONDUCTORS
Phase A, B, C
Neutral
Phase A, B, C
Neutral
Phase A, B, C
Neutral
Phase A, B, C
Neutral
Ground
Wiring for KO on Liebert EXM BDC
NOTE: Interconnection wiring between the UPS and bypass distribution cabinet is supplied by Vertiv™ when the
Liebert EXM BDC and Liebert® EXM UPS are ordered as a system.
Table 2.2 Hardware Torque Values
HARDWARE TWO BELLEVILLE WASHERS
M10 (3/8")
M12 (1/2")
240 lb-in. (27 Nm)
428 lb-in (48 Nm)
2 Installation Drawings
27
Figure 2.9 One-Line Diagram, 208V Single Input 10-100kVA UPS with Three-Breaker Liebert® EXM BDC and
Panelboard
28
ITEM DESCRIPTION ITEM DESCRIPTION
2
3
1 System AC Input 4 Wire + GND
BATTERY
UPS CABINET
4
5
STATIC BYPASS
BIB - Bypass Isolation Breaker
* External overcurrent protection by others.
6
7
8
BYPASS DISTRIBUTION
CABINET
MBB - Maintenance Bypass
Breaker
MIB - Maintenance Isolation
Breaker
9 (Optional) 54 Pole See Note 6
10 AC Output 208V 4 Wire + GND
NOTES TO FIGURE:
1.
Install in accordance with the national and the local electrical codes.
2.
The input and the bypass must share the same single source.
3.
A neutral is required from the system AC input source.
4.
The UPS system input and output cables must be run in separate conduits.
5.
The control wiring must be run in separate conduits.
6.
Optional 54 pole, 225A for 10-40kVA frame only or optional 54 pole 400A for 60-100kVA frame only.
VertVertiv™ | Liebert® EXM BDC User Manual
Figure 2.10 One-Line Diagram, 208V Single Input 10-100kVA UPS with Three-Breaker Liebert® EXM BDC, Input
Isolation Transformer and Panelboard
ITEM DESCRIPTION
2
3
1 System AC Input 3 Wire + GND
BATTERY
UPS CABINET
4
5
STATIC BYPASS
BIB - Bypass Isolation Breaker
6 BYPASS DISTRIBUTION CABINET
* External overcurrent protection by others.
ITEM
7
8
9
10
11
DESCRIPTION
MBB - Maintenance Bypass Breaker
MIB - Maintenance Isolation Breaker
(Optional) 54 Pole See Note 5
AC Output 208V 4 Wire + GND
Local Grounding Electrode See Note 1
NOTES TO FIGURE:
1.
Install in accordance with the national and the local electrical codes.
2.
The input and the bypass must share the same single source.
3.
The UPS system input and output cables must be run in separate conduits.
4.
The control wiring must be run in separate conduits.
5.
Optional 54 pole, 225A for 10-40kVA frame only or optional 54 pole 400A for 60-100kVA frame only.
6.
Optional transformers are available with input voltage 208V/220V/480V/600V.
2 Installation Drawings
29
Figure 2.11 One-Line Diagram, 208V Single Input 10-100kVA UPS with Three-Breaker Liebert® EXM BDC and Two
Subfeed Breakers
30
ITEM DESCRIPTION
2
3
1 System AC Input 4 Wire + GND
BATTERY
UPS CABINET
4
5
STATIC BYPASS
BIB - Bypass Isolation Breaker
6 BYPASS DISTRIBUTION CABINET
* External overcurrent protection by others.
ITEM
7
8
9
10
11
DESCRIPTION
MBB - Maintenance Bypass Breaker
MIB - Maintenance Isolation Breaker
(Optional) (2) 225A See Note 6
LDB-Load Distribution Breaker
AC Output 208V 4 Wire + GND
NOTES TO FIGURE:
1.
Install in accordance with the national and the local electrical codes.
2.
The input and the bypass must share the same single source.
3.
A neutral is required from the system AC input source. Vertiv™ recommends a full capacity neutral conductor and grounding conductors.
4.
The UPS system input and output cables must be run in separate conduits.
5.
The control wiring must be run in separate conduits.
6.
Optional (2) 225A LDB for 60-100kVA frame only. Optional single 225A LDB for 10-40kVA frame.
VertVertiv™ | Liebert® EXM BDC User Manual
Figure 2.12 One-Line Diagram, 208V Single Input 60-100kVA UPS with Three-Breaker Liebert® EXM BDC, Input
Isolation Transformer and Two Subfeed Breakers
ITEM DESCRIPTION
2
3
1 System AC Input 3 Wire + GND
BATTERY
UPS CABINET
4
5
STATIC BYPASS
BIB - Bypass Isolation Breaker
6 BYPASS DISTRIBUTION CABINET
* External overcurrent protection by others.
ITEM
10
11
12
7
8
9
DESCRIPTION
MBB - Maintenance Bypass Breaker
MIB - Maintenance Isolation Breaker
(Optional) (2) 225A See Note 5
LDB - Load Distribution Breaker
AC Output 208V 4 Wire + GND
Local Grounding Electrode See Note 1
NOTES TO FIGURE:
1.
Install in accordance with the national and the local electrical codes.
2.
The Input and the bypass must share the same single source.
3.
The UPS system input and output cables must be run in separate conduits.
4.
The control wiring must be run in separate conduits.
5.
Optional (2) 225A LDB for 60-100kVA frame only. Optional single 225A LDB for 10-40kVA frame.
6.
Optional Transformers are available with input voltage 208V/220V/480V/600V.
2 Installation Drawings
31
Figure 2.13 One-Line Diagram, 208V Dual Input 10-100kVA UPS with Three-Breaker Liebert® EXM BDC and
Panelboard
32
ITEM DESCRIPTION
1
2
3
Bypass AC Input 4 Wire + GND
Rectifier AC Input 4 Wire + GND See Note 7
BATTERY
4
5
UPS CABINET
STATIC BYPASS
6 BIB - Bypass Isolation Breaker
* External overcurrent protection by others.
ITEM DESCRIPTION
7
8
9
BYPASS DISTRIBUTION CABINET
MBB - Maintenance Bypass Breaker
MIB - Maintenance Isolation Breaker
10 (Optional) 54 Pole See Note 6
11 AC Output 208V 4 Wire + GND
NOTES TO FIGURE:
1.
Install in accordance with the national and the local electrical codes.
2.
The Input and the bypass must share the same single source.
3.
A neutral is required from the system AC input source. Vertiv™ recommends a full capacity neutral conductor.
4.
The bypass and the rectifier inputs and output cables must be run in separate conduits.
5.
The Control wiring must be run in separate conduits.
6.
Optional 54 pole, 225A for 10-40kVA frame only or optional 54 pole 400A for 60-100kVA frame only.
7.
The Customer must supply shunt trip breaker with 120V coil.
8.
Remove the bypass jumper busbars inside the UPS to configure a dual input system.
VertVertiv™ | Liebert® EXM BDC User Manual
Figure 2.14 One-Line Diagram, 208V Dual Input 10-100kVA UPS with Three-Breaker Liebert® EXM BDC and Two
Subfeed Breakers
ITEM DESCRIPTION
2
3
1 Bypass AC Input 4 Wire + GND
Rectifier AC Input 4 Wire + GND See Note 7
BATTERY
4
5
UPS CABINET
STATIC BYPASS
6 BIB - Bypass Isolation Breaker
* External overcurrent protection by others.
ITEM
10
11
12
7
8
9
DESCRIPTION
BYPASS DISTRIBUTION CABINET
MBB - Maintenance Bypass Breaker
MIB - Maintenance Isolation Breaker
(Optional) (2) LDB See Note 6
LDB - Load Distribution Breaker
AC Output 208V 4 Wire + GND
NOTES TO FIGURE:
1.
Install in accordance with the national and the local electrical codes.
2.
The Input and the bypass must share the same single source.
3.
A neutral is required from the system AC input source.Vertiv™ recommends a full capacity neutral conductor and grounding conductors.
4.
The bypass and the rectifier inputs and output cables must be run in separate conduits.
5.
Control wiring must be run in separate conduits.
6.
Optional (2) 225A LDB for 60-100kVA frame only.
7.
The Customer must supply shunt trip breaker with 120V coil.
8.
Remove the bypass jumper busbars inside the UPS to configure a dual input system.
2 Installation Drawings
33
This page intentionally left blank
34
VertVertiv™ | Liebert® EXM BDC User Manual
3 SPECIFICATIONS
Table 3.1 Physical Standards and Parameters
BYPASS DISTRIBUTION CABINET PARAMETERS VALUES
Standard Color
Front Door Opening (for serviceability)
Degree of Protection for UPS Enclosure
Minimum Clearance, Top
Minimum Clearance, Back
Minimum Clearance, Sides
Cable Entrance
Standards and Conformities
Black (ZP-7021)
More than 180°
IP 20 (with and without front door open)
24" (610mm)
0" (5" [127mm] when seismic brackets are used)
0"
Top or Bottom
UL 1778 5th Ed. ; CSA 22.2 107.3 -14 FCC Part 15, Class A ; ISTA Procedure 1H; WEEE; IBC
2012/CBC 2010
Environmental
Storage Temperature Range, °F (°C)
Operating Temperature Range, °F (°C)
Relative Humidity
Maximum Altitude Above MSL, ft. (m)
-13°F to 158°F (-25°C to 70°C)
32°F to 104°F (0 to 40°C) 32°F to 86°F (0-30°C) when seismic brackets are used up to 95% Non-Condensing (Operating and Non-Operating)
4920 (1500) (as per IEC 62040/3) - 1% Maximum kW derate / 100m rise between 1500m-
3000m
The following are approved branch breakers for the panel boards used in the Liebert® EXM BDCLiebert EXM BDC.
Listed (DIVQ), Schneider Electric Square D branch circuit breakers:
• Type QOB, rated 22 kA, 150A maximum.
• Type QO, rated 22 kA, rated 100A maximum.
• Type QOB, rated 10 kA, rated 100A maximum.
• Type QO, rated 10 kA, rated 100A maximum.
Table 3.2 Mechanical Characteristics, Liebert® EXM BDC, 10-100kVA
DIMENSIONS, W X D X H, IN (MM) 23.625 X 39.375 X 78.73
Weight, lb. (kg)
Weight lb. (kg)
Rating kVA
600
600
600
10-40
60
80
600 100
Add 27 lb. (12 kg) for monitoring
No Transformer, No
Distribution
525(238)
550(249)
550(249)
550(249)
No Transformer with
Panelboard or Subfeed
Breaker
625(283)
650(295)
650(295)
650(295)
With Transformer, No
Distribution
914(415)
1125(509)
1249(567)
1365(619)
With Transformer and
Panelboard or Subfeed Breaker
1014 (460)
1223 (555)
1349 (612)
1465 (665)
35
36
Table 3.3 Liebert EXM BDC 60-100kVA, Mechanical Characteristics
RATED POWER, KVA
Dimensions, W x D x H, in. (mm)
Weight, lb. (kg)
Color
Protection Degree IEC (60529)
60-100
23.625 x 39.375 x 78.75 (600 x 1000 x 2000)
No Distribution
Two 225A Subfeed Breakers
400A Panelboard
No Distribution and 480V Transformer
No Distribution and 600V Transformer
Two 225A Subfeed Breakers and 480V Transformer
Two 225A Subfeed Breakers and 600V Transformer
400A Panelboard and 480V Transformer
400A Panelboard and 600V Transformer
550 (250)
660 (300)
660 (300)
1549 (704)
1538 (699)
1669 (759)
1648 (749)
1669 (759)
1648 (749)
ZP 7021 (Black)
IP20 (finger-proof with front doors open or closed)
Table 3.4 Liebert® EXM BDC Heat Dissipation
LIEBERT EXM BDC
RATING, KVA
LIEBERT EXM BDC HEAT
DISSIPATION 208:208
TRANSFORMER BTU/HR
(KW)
LIEBERT EXM BDC HEAT
DISSIPATION 208:208
TRANSFORMER BTU/HR
(KW)
30
40
60
80
100
10
15
20
1966 (0.576)
2504 (0.734)
2938 (0.861)
4847 (1.421)
5676 (1.664)
7479 (2.192)
9612 (2.817)
9728 (2.851)
1808 (0.530)
2320 (0.680)
2593 (0.760)
4408 (1.292)
5166 (1.514)
6804 (1.994)
8711 (2.553)
8881 (2.603)
LIEBERT EXM BDC HEAT
DISSIPATION 220:220
TRANSFORMER BTU/HR (KW)
1723 (0.505)
2474 (0.725)
2958 (0.867)
4343 (1.273)
5005 (1.467)
6670 (1.955)
9001 (2.638)
9953 (2.917)
LIEBERT EXM BDC HEAT
DISSIPATION 220:220
TRANSFORMER BTU/HR
(KW)
1750 (0.513)
2453 (0.719)
2986 (0.875)
4896 (1.435)
4988 (1.462)
6445 (1.899)
8892 (2.606)
10042 (2.943)
VertVertiv™ | Liebert® EXM BDC User Manual
3 Specifications
3.1 Electrical Characteristics
NOTE: The breakers and cables used must be in accordance with the NEC ANSI/NFPA 70. A disconnect breaker must be provided for the AC input, the bypass and the AC output. Recommended cable sizes are suitable for operation at a maximum temperature of 104°F (40°C).
Table 3.5 Liebert EXM BDC Input Currents, Single Input, Main, Without Transformer
VOLTAGE 3-PH, 60HZ
BDC RATING
KVA
SYSTEM
INPUT
CURRENT,
A, MAX
PHASE
RECOMMENDED
UPSTREAM
PROTECTION, A
75°C WIRE
CURRENT,
A, TOTAL
COPPER
WIRE
ALUMINUM
WIRE
BOLT
SIZE
208/120
220/127
208/120
220/127
208/120
220/127
208/120
220/127
208/120
220/127
208/120
220/127
208/120
220/127
208/120
220/127
10
15
20
30
40
60
80
100
34
51
68
102
136
205
273
341
3W + N + G
3W + N + G
3W + N + G
3W + N + G
3W + N + G
3W + N + G
3W + N + G
3W + N + G
45
70
90
150
175
300
350
450
65
85
115
175
230
400
460
610
(1) #6
(1) #4
(1) #2
(1) 2/0
(1) 4/0
(2) 3/0
(2) 4/0
(1) #4
(1) #2
(1) 1/0
(1) 4/0
(2) 1/0
(2) 4/0
M12
M12
M12
M12
M12
M12
(2) 300kcmil M12
(2) 350kcmil (2) 400kcmil M12
37
38
Table 3.6 Liebert® EXM BDC Input Currents, Dual Input, Rectifier, Without Transformer
VOLTAGE 3-
PH, 60HZ
BDC
RATING
KVA
RECTIFIER
INPUT
CURRENT
RIB, A,
MAX
RECTIFIER RECOMMENDED
UPSTREAM PROTECTION, A
PHASE
75°C WIRE
CURRENT, A,
TOTAL
COPPER
WIRE
ALUMINUM
WIRE
BOLT
SIZE
208/120
220/127
208/120
220/127
208/120
220/127
10
15
20
34
51
68
45
70
90
3W + N +
G
3W + N +
G
3W + N +
G
65
85
115
(1) #6
(1) #3
(1) #2
208/120
220/127
208/120
220/127
208/120
220/127
208/120
220/127
30
40
60
80
102
136
205
273
150
175
300
350
3W + N +
G
3W + N +
G
3W + N +
G
3W + N +
G
175
230
400
460
(1) 2/0
(1) 4/0
(2) 3/0
(2) 4/0
208/120
220/127
100 341 400
3W + N +
G
610
Refer to
on page no. 33 for additional details about this system configuration.
(2)
350kcmil
(1) #4
(1) #2
(1) 1/0
(1) 4/0
(2) 1/0
(2) 4/0
M12
M12
M12
M12
M12
M12
(2) 300kcmil M12
(2) 400kcmil M12
VertVertiv™ | Liebert® EXM BDC User Manual
3 Specifications
Table 3.7 Liebert® EXM BDC Input Currents, Dual Input, Bypass, Without Transformer
VOLTAGE 3-PH,
60HZ
BDC
RATING
KVA
BYPASS
INPUT
CURRENT
BIB/MBB,
A, MAX
BYPASS RECOMMENDED
UPSTREAM PROTECTION,
A
PHASE
75°C WIRE
CURRENT,
A, TOTAL
COPPER
WIRE
ALUMINUM
WIRE
BOLT
SIZE
208/120
220/127
208/120
220/127
208/120
220/127
208/120
220/127
208/120
220/127
208/120
220/127
208/120
220/127
10
15
20
30
40
60
80
28
42
56
83
111
167
222
40
70
80
125
175
250
350
3W + N +
G
3W + N +
G
3W + N +
G
3W + N +
G
3W + N +
G
3W + N +
G
3W + N +
G
50
85
115
130
175
285
400
(1) #6
(1) #4
(1) #2
(1) 1/0
(1) 3/0
(1) 350kcmil
(2) 3/0
208/120
220/127
100 278 450
3W + N +
G
460 (2) 4/0
Refer to
on page no. 33 for additional details about this system configuration.
(1) #4
(1) #2
(1) #2
(1) 2/0
(1) 4/0
(2) 2/0
(2) 4/0
M12
M12
M12
M12
M12
M12
M12
(2) 300kcmil M12
39
40
Table 3.8 Liebert® EXM BDC Output Currents
VOLTAGE 3-PH, 60HZ
BDC RATING
KVA
SYSTEM
OUTPUT
CURRENT
A, MAX
PHASE
208/120
220/127
208/120
220/127
208/120
220/127
208/120
220/127
208/120
220/127
208/120
220/127
208/120
220/127
208/120
220/127
10
15
20
30
40
60
80
100
28
42
56
83
111
167
222
278
3W + N + G
3W + N + G
3W + N + G
3W + N + G
3W + N + G
3W + N + G
3W + N + G
3W + N + G
RECOMMENDED
UPSTREAM
PROTECTION, A
40
60
70
110
150
225
300
350
75°C WIRE
CURRENT,
A, TOTAL
COPPER
WIRE
ALUMINUM
WIRE
BOLT
SIZE
50
85
115
130
175
285
400
460
(1) #6
(1) #4
(1) #2
(1) 1/0
(1) 3/0
(1)
350kcmil
(2) 3/0
(1) #4
(1) #2
(1) #2
(1) 2/0
(1) 4/0
(2) 2/0
(2) 4/0
M12
M12
M12
M12
M12
M12
M12
(2) 4/0 (2) 300kcmil M12
VertVertiv™ | Liebert® EXM BDC User Manual
3 Specifications
Table 3.9 Recommended Lug Sizes (Compression type) M12, 1/2" Bolt
CABLE SIZE T&B COPPER TWO HOLE
#4/0AWG
250kcmil
300kcmil
350kcmil
400kcmil
500kcmil
600kcmil
700kcmil
750kcmil
#6AWG
#4AWG
#2-3AWG
#1AWG
#1/0AWG
#2/0AWG
#3/0AWG
256-030695-868
256-030695-733
54811BE
54857BE
256-30695-593
54862BE
54864BE
54866BE
54868BE
54870BE
54872BE
54874BE
54876BE
54878BE
54879BE
54880BE
T&B ALUMINUM TWO HOLE
60250
60256
60262
60267
60269
60273
60275
60277
60278
—
—
—
—
—
60238
60244
3.2 Torque Requirements
All electrical connections must be tight.
on page no. 41 provide the torque values for the connections to the Liebert® EXM
BDC. Use these values unless the equipment is labeled otherwise.
Table 3.10 Busbar torque for power wiring
BOLT SHAFT SIZE TORQUE LB. IN. (NM)
3/8" (M10)
1/2" (M12)
192 (22)
428 (48)
Table 3.11 Terminal block torque with compression lugs for control wiring
AWG WIRE SIZE OR RANGE
#22 - #14
TORQUE LB. IN. (NM)
3.5 to 5.3 (0.4 to 0.6)
NOTE: Refer to the manufacturer's data for proper torque for circuit breaker power connections.
41
42
Table 3.12 Breaker Torque
MANUFACTURER
ABB
Siemens
PART NUMBER
Tmax2
Tmax3
Tmax5
XT1
XT3
D Frame
F Frame
J Frame
TORQUE, NM
7.0
8.0
25.0
6
8
5.5
22.0
31.0
Table 3.13 Electrical data-Liebert® EXM BDC, 480VAC Input, 208VAC Output, Single Input, with 480V:208V
Transformer
LIEBERT EXM BDC
RATING, KVA
MAXIMUM SYSTEM INPUT CURRENT,
A
PHASE
RECOMMENDED
UPSTREAM
PROTECTION, A
75°C WIRE
CURRENT,
A, TOTAL
COPPER
WIRE
ALUMINUM
WIRE
10
15
20
30
40
60
80
100
See
46
61
91
122
152
15
23
31
3W + G
3W + G
3W + G
3W + G
3W + G
3W + G
3W + G
3W + G
60
80
125
175
200
20
30
40
65
85
150
200
205
40
40
40
BOLT
SIZE
(1) #8
(1) #8
(1) #8
(1) #8
(1) #8
(1) #8
(1) #6
(1) #4
(1) #2
(1) 1/0
(1) #4
(1) #2
(1) 1/0
(1) 3/0
M12
M12
M12
M12
(1) 4/0 (1) 250 kcmil M12
M12
M12
M12
VertVertiv™ | Liebert® EXM BDC User Manual
3 Specifications
Table 3.14 Electrical Data-Liebert® EXM BDC, 600VAC Input, 208VAC Output, Single Input, with 600V:208V
Transformer
LIEBERT EXM BDC RATING,
KVA
MAXIMUM SYSTEM INPUT
CURRENT, A
PHASE
RECOMMENDED
UPSTREAM
PROTECTION, A
75°C WIRE
CURRENT,
A, TOTAL
COPPER
WIRE
ALUMINUM
WIRE
30
40
60
80
10
15
20
100
See
73
98
37
49
122
12
18
25
3W + G
3W + G
3W + G
3W + G
3W + G
3W + G
3W + G
3W + G
50
70
100
125
175
20
25
35
50
65
90
120
150
40
40
40
(1) #8
(1) #8
(1) #8
(1) #8
(1) #5
(1) #3
(1) #1
(1) 1/0
(1) #8
(1) #8
(1) #8
(1) #6
(1) #4
(1) #2
(1) 1/0
(1) 3/0
BOLT
SIZE
M12
M12
M12
M12
M12
M12
M12
M12
Table 3.15 Electrical Data-Liebert EXM BDC, 208VAC or 220VAC Input, Single Input, with 208V:208V or 220V:220V
Transformer
LIEBERT EXM
BDC RATING,
KVA
MAXIMUM SYSTEM
INPUT CURRENT, A
PHASE
RECOMMENDED
UPSTREAM PROTECTION,
A
75°C WIRE
CURRENT, A,
TOTAL
COPPER
WIRE
ALUMINUM
WIRE
BOLT
SIZE
10
15
20
30
40
60
80
100
36
53
71
107
141
211
281
352
3W + G
3W + G
3W + G
3W + G
3W + G
3W + G
3W + G
3W + G
45
70
90
150
200
300
400
450
65
85
100
175
230
335
460
510
(1) #6
(1) #4
(1) #3
(1) 2/0
(1) 4/0
(1) 400 kcmil
(2) 4/0
(2) 250 kcmil
(1) #4
(1) #2
(1) #1
(1) 4/0
(1) 300 kcmil
(2) 4/0
(2) 300 kcmil
(2) 400 kcmil
M12
M12
M12
M12
M12
M12
M12
M12
See
43
NOTES ON TABLES.
Notes apply to
1.
Nominal input current (considered continuous) is based on full rated output load maximum current includes nominal input current and maximum battery recharge current (considered noncontinuous). Continuous and noncontinuous current are defined in the NEC 100. Recommended overcurrent protection is based on 80% rated devices.
*The recommended overcurrent protection represents 125% of nominal full load current (continuous) per the
NEC 215.
2.
The maximum input current is controlled by the current limit setting.
3.
The recommended AC input external overcurrent protection is based on 80% rated devices and maximum input current limit setting.
4.
The recommended AC output external overcurrent protection is based on 80% rated devices and full rated output current.
5.
The nominal battery voltage is shown at 2 volts per cell.
6.
The input power factor of 0.99 is used for the calculations.
44
VertVertiv™ | Liebert® EXM BDC User Manual
Vertiv™ | Vertiv | Liebert® EXM™ BDC User Manual
Vertiv.com | Vertiv Headquarters, 1050 Dearborn Drive, Columbus, OH, 43085, USA
© 2020 Vertiv Group Corp. All rights reserved. Vertiv™ and the Vertiv logo are trademarks or registered trademarks of Vertiv Group Corp. All other names and logos referred to are trade names, trademarks or registered trademarks of their respective owners. While every precaution has been taken to ensure accuracy and completeness herein, Vertiv Group
Corp. assumes no responsibility, and disclaims all liability, for damages resulting from use of this information or for any errors or omissions. Specifications are subject to change without notice.
SL-25653_REV4_05-20_05-2020
advertisement
* Your assessment is very important for improving the workof artificial intelligence, which forms the content of this project
Related manuals
advertisement
Table of contents
- 5 IMPORTANT SAFETY INSTRUCTIONS
- 9 GLOSSARY OF SYMBOLS
- 11 1 Liebert® EXM BDC
- 12 1.1 Normal (UPS) Mode
- 12 1.2 Maintenance Mode
- 12 1.3 Cable Installation
- 12 1.3.1 Wiring Preparation
- 13 1.4 Locating the Cabinet
- 13 1.4.1 Power Cable Installation
- 13 1.4.2 Input/Output Wiring
- 15 1.4.3 Accessory Fuses and Back-Feed Breaker Wiring
- 19 1.5 Bolting Cabinets Together
- 20 1.5.1 Floor Installation
- 20 1.5.2 Cable Entry
- 21 1.5.3 Optional Cabinets
- 23 2 Installation Drawings
- 39 3 Specifications
- 41 3.1 Electrical Characteristics
- 45 3.2 Torque Requirements