H20.0.2X.6C1-07 from version V3.2

EASYBus-Sensor module for humidity temperature

with option: selectable humidity display

Operating Manual

EBHT – ... / UNI

Content

1 INTENDED USE

2 GENERAL ADVICE

3 SAFETY INSTRUCTIONS

4 DISPOSAL NOTES

5 ASSIGNMENT OF ELBOW-TYPE PLUG

6 GENERAL INSTALLATION INSTRUCTIONS:

7 DESIGN TYPES, DIMENSION

8 DISPLAY FUNCTIONS

(ONLY AVAILABLE FOR DEVICES WITH OPTION ...-VO)

8.1

M EASURING DISPLAY

8.2

M IN /M AX V ALUE M EMORY

8.3

U SAGE OF U NIT -L ABELS

8.4

M IN /M AX A LARM D ISPLAY

9 ERROR AND SYSTEM MESSAGES

10 CONFIGURATION OF THE DEVICE

10.1

C ONFIGURATION VIA INTERFACE

10.2

C ONFIGURATION AT THE DEVICE ( ONLY AVAILABLE FOR DEVICE WITH OPTION

…-VO)

11 NOTES TO THE CALIBRATION SERVICES

12 SPECIFICATION

5

5

5

5

7

7

3

4

4

4

4

4

3

3

2

2

2

2

WEEE-Reg.-Nr.: DE93889386

GREISINGER

electronic GmbH

D - 93128 Regenstauf, Hans-Sachs-Straße 26

+49 (0) 9402 / 9383-0

+49 (0) 9402 / 9383-33  [email protected]

H20.0.2X.6C1-07 Operating Manual EBHT – 1R, 1K, 2K, Kabel / UNI

_____________________________________________________ page 2 of 8

_____________________________________________________________________________

1 Intended use

The device measures the relative humidity and temperature of air or non corrosive / non ionizing gases.

From this values others can be derived and displayed instead of the rel. humidity.

Field of application

Room climate monitoring

Monitoring of storage rooms etc...

The safety instructions (see chapter 3) have to be observed.

The device must not be used for purposes and under conditions for that the device had not been designed.

The device must carefully dealt with and has to be used according to the specifications (do not throw, knock, etc.). It has to be protected against dirt.

Do not expose the sensor to aggressive gases (like ammonia) for longer time.

Avoid condensation, as after drying there may remain residues, which may affect the precision negatively.

In dusty environment additional protection has to be applied (special protection caps).

2 General advice

Read through this document attentively and make yourself familiar to the operation of the device before you use it. Keep this document in a ready-to-hand way in order to be able to look up in the case of doubt .

3 Safety instructions

This device has been designed and tested in accordance to the safety regulations for electronic devices.

However, its trouble-free operation and reliability cannot be guaranteed unless the standard safety measures and special safety advises given in this manual will be adhered to when using it.

1. Trouble-free operation and reliability of the device can only be guaranteed if it is not subjected to any other climatic conditions than those stated under “Specification”.

Transporting the device from a cold to a warm environment condensation may result in a failure of the function. In such a case make sure the device temperature has adjusted to the ambient temperature before trying a new start-up.

2. General instructions and safety regulations for electric, light and heavy current plants, including domestic safety regulations (e.g. VDE), have to be observed.

3. If device is to be connected to other devices (e.g. via PC) the circuitry has to be designed most carefully.

Internal connection in third party devices (e.g. connection GND and earth) may result in not-permissible voltages impairing or destroying the device or another device connected.

4. Whenever there may be a risk whatsoever involved in running it, the device has to be switched off immediately and to be marked accordingly to avoid re-starting. Operator safety may be a risk if:

- there is visible damage to the device

- the device is not working as specified

- the device has been stored under unsuitable conditions for a longer time

In case of doubt, please return device to manufacturer for repair or maintenance.

5. Warning: Do not use this product as safety or emergency stop device or in any other application where failure of the product could result in personal injury or material damage.

Failure to comply with these instructions could result in death or serious injury and material damage.

4 Disposal notes

This device must not be disposed as “residual waste”.

To dispose this device, please send it directly to us (adequately stamped).

We will dispose it appropriately and environmentally friendly.

H20.0.2X.6C1-07 Operating Manual EBHT – 1R, 1K, 2K, Kabel / UNI

_____________________________________________________ page 3 of 8

_____________________________________________________________________________

5 Assignment of elbow-type plug

2-wire connection for EASYBus, no polarity, at terminals 1 and 2

6 General installation instructions:

To mount the connection cable (2-wire) the elbow-type plug screw has to be loosened and the coupling insert has to be removed by means of a screw driver at the position indicated (arrow).

Pull out connection cable through PG gland and connect to the loose coupling insert as described in the wiring diagram. Replace loose coupling insert onto the pins at the transducer housing and turn cover cap with

PG gland in the direction desired till it snaps on (4 different starting positions at 90° intervals). Re-tighten the screw at the angle plug.

7 Design types, dimension

EBHT-1R short sensor tube aside

EBHT-1K long sensor tube aside

EBHT-2K long sensor tube bottom

EBHT-Kabel separated sensor tube

H20.0.2X.6C1-07 Operating Manual EBHT – 1R, 1K, 2K, Kabel / UNI

_____________________________________________________ page 4 of 8

_____________________________________________________________________________

8 Display Functions

(only available for devices with option ...-VO)

8.1 Measuring display

During normal operation the selectable humidity display value is displayed alternating to the temperature in [°C] or [°F] .

Arrow to “Temp” indicates temperature display display of selectable humidity value display temperature

If the relative humidity in [%] should be shown, although other display is selected (e.g. dew point temperature, mixing ratio...): press ▼ and ▲ simultaneous display changes between „r.H.„ and measurand

8.2 Min/Max Value Memory

watch Min values (Lo): press ▼ shortly once watch Max values (Hi): press ▲ shortly once restore current values: press ▼ or ▲ once again clear Min-values: press ▼ for 2 seconds clear Max-values: press ▲ for 2 seconds display changes between „Lo„ and Min values display changes between „Hi„ and Max values current values are displayed

Min values are cleared. Disp lay shows shortly „CLr„.

Max values are cleared. Display shows shortly „CLr„.

After 10 seconds the currently measured values will be displayed again.

8.3 Usage of Unit-Labels

As the transmitter is a multiple purpose device, many different display units are possible, e.g. g/kg, g/m

3

.

Therefore unit-labels (within scope of supply) can be shoved between the case cover and the front foil behind the transparent unit-window .

To replace a label, unscrew the cover, pull out the old label (if present) and shove in the new one.

The unit depends on the configuration settings “Unit”!

Please refer to table in chapter “10 Configuration of the device”

8.4 Min/Max Alarm Display

Whenever the measured value is exceeding or undershooting the alarm-values that have been set, the alarm-warning and the measuring value will be displayed alternating.

AL.Lo

AL.Hi the lower alarm boundary is reached or is undershot the upper alarm boundary is reached or is exceeded

H20.0.2X.6C1-07 Operating Manual EBHT – 1R, 1K, 2K, Kabel / UNI

_____________________________________________________ page 5 of 8

_____________________________________________________________________________

9 Error and system messages

Display Description Possible fault cause Remedy

Err.1

Err.2

Err.3

Measuring range exceeded

Measuring value below measuring range

Display range has been exceeded

Wrong signal

Wrong signal

Value >9999

Temperature above 120°C not allowed.

Temperature below -40°C not allowed.

Check settings

Err.7

Err.9

Er.11

System fault

Sensor error

Calculation not possible

8.8.8.8 Segment test

Error in device

Sensor or cable defective

Disconnect from supply and reconnect.

If error remains: return to manufacturer

Check sensors, cable and connections, damages visible?

Calculation variable missing or invalid

Check temperature

The transducer performs a display test for 2 seconds after power up. After that it will change to the display of the measuring.

10 Configuration of the device

10.1 Configuration via interface

The configuration of the device is done by means of the PC-software EASYBus-Configurator or EBxKonfig.

The following parameters can be changed:

- Adjusting of humidity and temperature display (offset and scale correction)

- Setting of the alarm function for humidity and temperature

The adjusting by means of offset and scale is intended to be used to compensate errors of the measurings.

It is recommended to keep the scale correction deactivated. The display value is given by following formula: value = measured value - offset

With a scale correction (just for calibration laboratories, etc) the formula changes: value = (measured value - offset) * ( 1 + scale adjustment/100)

10.2 Configuration at the device (only available for device with o ption …-VO)

Note: If EASYBus sensor modules are operated by a data acquisition software, there can be problems if the configuration is changed during a running acquisition. Therefore it is recommended not to change configuration values during a running recording and furthermore to protect it against manipulation by unauthorised persons. (please refer to right picture)

Follow these instructions to configure the functions of the device:

Press SET until the first parameter

UNIT

appears in the display

If a parameter should be changed, press ▼ or ▲ ,

The device changed to the setting – edit with ▼ or ▲

Confirm the value with SET

Jump to the next parameter with SET.

ATTENTION !

If the jumper is removed from the shown contacts, the configuration is inaccessible, values are protected.

Never connect other contacts !

H20.0.2X.6C1-07

Parameter value

SET ▼ and ▲

Operating Manual EBHT – 1R, 1K, 2K, Kabel / UNI

_____________________________________________________ page 6 of 8

_____________________________________________________________________________ information

UNIT

UNIT

+ Temp arrow

Unit and Range of humidity display factory setting: rel.H

reL.H

F.AbS

FEU.t t.d.

Enth

F.G.

0.0 100.0 % relative air humidity

0.0 … 200.0 g/m 3

absolute humidity

27.0 … 60.0°C wet bulb temperature

40.0 … 60.0°C dew point temperature

25.0 … 999.9 kJ/kg Enthalpy

0.0 … 640.0 g/kg Mixing ratio (atmospheric humidity)

Unit of temperature displays factory setting: °C

°C Temperatures in °Celsius

°F Temperatures in °Fahrenheit

Offset correction of humidity measuring *) oFF

-5.

0 … +5.0 deactivated ( factory setting)

Selectable from -5.0 to +5.0 % rel. humidity

Scale correction of humidity measuring *) oFF deactivated ( factory setting)

-15.

00 … +15.00 Selectable from -15.00 to +15.00 % scale correction

+ Temp arrow

+ Temp arrow

Offset correction of temperature measuring *) oFF

-2.

0 … +2.0 deactivated ( factory setting)

Selectable from -2.0 to +2.0 °C

Scale correction of temperature measuring *) oFF

-5.

00 … +5.00 deactivated ( factory setting)

Selectable from -5.00 to +5.00 % scale correction

ALTI

Altitude input (not at all units available) factory setting: 340

500 … 9000 500 … 9000 m selectable

AL.LO

Min. alarm-point for humidity measuring

-0.1 … AL.Hi

Selectable from: -0.1 %RH to AL.Hi

AL.K,

Max. alarm-point for humidity measuring

AL.Lo … 100.1 Selectable from: AL.Lo to 100.1 %RH

AL.DE

Alarm-delay for humidity measuring oFF

1 … 9999 deactivated ( factory setting)

Selectable from 1 to 9999 sec.

AL.LO

+ Temp arrow

AL.K,

+ Temp arrow

AL.DE

+ Temp arrow

Min. alarm-point for temperature measuring

Min.MB … AL.Hi Selectable from: min. measuring range to AL.Hi

Max. alarm-point for temperature measuring

AL.Lo … Max.MB

Selectable from: AL.Lo to max. measuring range

Alarm-delay for temperature measuring oFF

1 … 9999 deactivated ( factory setting)

Selectable from 1 to 9999 sec.

Pressing SET again stores the settings, the instruments restarts (segment test)

Please note: If there is no key pressed within the menu mode within 2 minutes, the configuration will be cancelled, the entered settings are lost!

*) if higher values are needed, please check sensor, if necessary return to manufacturer for inspection.

Calculation: corrected value = (measured value – Offset) * (1+Scale/100)

H20.0.2X.6C1-07 Operating Manual EBHT – 1R, 1K, 2K, Kabel / UNI

_____________________________________________________ page 7 of 8

_____________________________________________________________________________

11 Notes to the calibration services

Calibration certificates - DKD-certificates - other certificates:

If device should be certificated for its accuracy, it is the best solution to return it with the referring sensors to the manufacturer. (please state desired test values, e.g. 70 %RH)

Only the manufacturer is capable to do efficient recalibration if necessary to get results of highest accuracy!

Humidity transmitters are subject to ageing. For optimum measuring precision we recommend a regular adjusting at the manufacturer (e.g. every 2 nd

year). Cleaning and checking of the sensors is part of the service.

12 Specification

Display ranges humidity Relative air humidity:

Wet bulb temperature:

Dew point temperature:

0.0...100.0 %RH

-27.0 ... 60.0 °C

-40.0 ... 60.0 °C

Enthalpy: -25.0 ... 999.9 kJ/kg

Mixing ratio (atmospheric humidity): 0.0 ... 640.0 g/kg absolute humidity: 0.0 ... 200.0 g/m

3

(or -16,6 … 140,0 °F)

(or -40,0 … 140,0 °F)

Recommended humidity measuring range

Meas. range temperature

Accuracy

Display

Standard: 20.0 ... 80.0 %RH

Option “high humidity”: 5.0 ... 95.0 %RH

-40.0 ... 120.0 °C or -40.0 ... 248.0 °F

(at nom. temperature 25°C)

Rel. Air humidity: ±2.5 %RH (within recom- mended measuring range)

Temperature: ±0.4% of meas. value. ±0.2°C

Non corrosive gasses

Working range of humidity sensor:

Media

Sensors capacitive polymer humidity sensor and Pt1000

Temperature compensation automatic

Meas. frequency 1 per second

Adjusting

Min-/Max-value memory

Output signal

Connection

Busload

Display (only with option VO)

Digital offset and scale adjustment for humidity and temperature

Min and max measured values are stored

EASYBus-protocol

2-wire EASYBus, polarity free

1.5 EASYBus-devices

Operating elements

Ambient conditions

Nom. temperature

Operating temperature

Relative humidity

Storage temperature

Housing

Dimensions approx. 10 mm high, 4-digit LCD-display

3 keys

25°C

Electronics: -25 ... 50 °C, sensor head and shaft: -40 ... 100 °C, short time 120 °C for Option “SHUT”: sensor head max. 80 °C

Electronics: 0 ... 95 %RH (not condensing)

-25 ... 70 °C

Mounting

Mounting distance

Electrical connection

EMC

ABS (IP65, except sensor head)

82 x 80 x 55 mm (without elbow-type plug and sensor tube) for Option “Kabel”: Sensor head Ø14mm*68mm, 1m teflon cable, high humidity sensor

Holes for wall mounting (in housing - accessible after cover has been removed).

50 x 70 mm, max. shaft diameter of mounting screws is 4 mm

Elbow-type plug conforming to DIN 43650 (IP65), max. wire cross section: 1.5 mm², wire/cable diameter from 4.5 to 7 mm

The device corresponds to the essential protection ratings established in the Regulations of the Council for the Approximation of Legislation for the member countries regarding electromagnetic compatibility (2004/108/EG).

In accordance with EN 61326-1 : 2006, additional errors: <1 % FS.

When connecting long leads adequate measures against voltage surges have to be taken.

H20.0.2X.6C1-07 Operating Manual EBHT – 1R, 1K, 2K, Kabel / UNI

_____________________________________________________ page 8 of 8