OB207t-1qxp 25/9/97 8:51 PM Page 1

TCL

WALL MOUNTED

SPLIT-TYPE AIR CONDITIONERS

SERVICE MANUAL

No.TE051220

Models

TAC-09CHSA/GI TAC-12CHSA/GI

CONTENTS

1.

IMPORTANT NOTICE

···································2

2.

TECHNICAL SPECIFICATION

·····················3

3.

OPERATION DETAILS

·······························

4

4.

WIRING DIAGRAM

·············

11

5.

EXPLOSION VIEW

····························

12

6.

PARTS LIST

·············

13

TCL Air Conditioner Service Manual

IMPORTANT NOTICE

This service manual is intended for use by individuals possessing adequate backgrounds of electrical, electronic and mechanical experience. Any attempt to repair the appliance may result in personal injury and property damage. The manufacturer or seller cannot be responsible for the interpretation of this information, nor can it assume any liability in connection with its use.

The information, specifications and parameter are subject to change due to technical modification or improvement without any prior notice. The accurate specifications are presented on the nameplate label.

How to order spare parts

To have your order filled promptly and correctly, please furnish the following information:

1. Model No. with Indoor or Outdoor

2. No. in the Explosion View

3. Part Name

4. The quantity you ordered

2

TCL Air Conditioner Service Manual

Model No.

Type

Control type

Rated cooling capacity

Rated heating capacity

Moisture removal

High

Med.

Low

Btu/h

Btu/h

Liters/h dB(A) dB(A) dB(A) dB(A)

Technical Specifications

TAC-09CHSA/GI

heating pump

TAC-12CHSA/GI

heating pump remote remote

9,000(3,800~10,500) 12,000(5,200~13,500)

10,250(4,200~13,000) 13,800(5,500~16,500)

37 38

Indoor noise level at cooling

Outdoor noise level

Electrical Data

Power supply

Voltage Range

52 55

220-240V~/50Hz

Rated current

V

Cooling A

Heating A

Cooling W

Heating W

158-260

3.6

3.8

780

820

158-260

4.9

5.2

1060

1120 Rated input

Refrigerating System

Refrigerant/Charge

Compressor

Evaporator

Condenser

Expansion device

Defrosting system

Fan System

Indoor air circulation/Hi Cooling

Indoor fan type

Type

Model

LRA

MFG

Gram

A

410A/780g

Rotary

DA108X1C-20FZ3

Toshiba

410A/1080g

Rotary

DA108X1C-20FZ3

Toshiba

Louver fin and Grooved tube type (φ7)

Corrugated fin and Grooved tube type (φ9.53)

Capillary tube

Microcomputer controlled reverse system

Indoor fan speed H/M/L

Outdoor fan type

Outdoor fan speed m

3

/h

Cooling rpm

Heating rpm

Dry

Sleep rpm rpm rpm

450

Cross Flow

1300/1280/1100/950

1300/1280/1100/900

950

950/900

Propeller fan

850

480

Cross Flow

1330/1300/1150/1000

1320/1300/1100/900

1150

1000/900

Propeller fan

850

Connections

Refrigerant coupling

Gas Inches 3/8'' 1/2''

Connecting Pipe

Liquid Inches 1/4'' 1/4''

Connecting Wiring

4×1.5 4×1.5

Drainage Pipe

Others

Suitable area

Net dimensions

(W x H x D)

Net weight

Packing dimensions

(W x H x D)

Gross weight low temp. start-up high temp. start-up m

2

Indoor mm

Outdoor mm

Indoor kg

Outdoor kg

Indoor mm

Outdoor mm

Indoor kg

Outdoor kg

9-15

770*240*180

760*560*260

8.5

30

883*325*271

863*598*381

10.5

33

-15

52

12-19

770*240*180

760*560*260

8.5

34

883*325*273

863*598*383

10.5

37

-15

52

O.D.16mm

Note:The technical specifications is only reference.

3

Operation Details

TCL Air Conditioner Service Manual

Remote controller

Remote controller

The remote controller transmits signals to the system.

5

2

8

4

FEEL

COOL

DRY

FAN

HEAT

SLEEP TIMER ON TMIER OFF

AUTO

HIGH

MID

LOW

SWING

SLEEP

TIMER

MODE

FAN

SWING

ON/OFF

1

3

7

6

1

2

ON/OFF button

Used to start and stop operation when pressed.

TIMER button

Used to select TIMER operation.

3

4

5

6

7

8

UP button (TOO COOL button)

Used to increase the set room temperature

and time.

DOWN button (TOO WARM button)

Used to decrease the set room temperature and time.

SLEEP button

Used to set or cancel sleep mode operation.

VANE control button

Used to adjust airflow direction.

FAN SPEED control button

Used to select the indoor fan motor speed:

Auto, High, Mid and Low.

MODE button

Used to select the type of operation mode: Feel,

Cooling, Dry, Fan and Heating(Only for Heat Pump).

Note: Each mode and relevant function will be further specified in following pages.

Remote Control

The remote controller is not preset ted as Cooling Only Air Conditioner or Heat Pump by manufacturer.

Each time after the remote controller replace batteries or is energized, the arrowhead will flashes on the front of

Heat or Cool on LCD of the remote controller.

User can preset the remote controller type depending on the air conditioner type you have purchased as follows:

Press any button when the arrowhead flashes on the front of Cool , Cooling Only is set.

Press any button when the arrowhead flashes on the front of Heat , Heat Pump is set.

If you don t press any button within 10 seconds, the remote controller is preset as Heat Pump automatically.

Note :

If the air conditioner you purchased is a Cooling Only one, but you preset the remote controller as Heat Pump, it doesn t bring any matter. But if the air conditioner you purchased is a Heat Pump one, and you preset the remote controller as Cooling Only, then you CAN NOT preset the Heating operation with the remote controller.

4

TCL Air Conditioner Service Manual

Electronic Controller

(1) Time Delay for Safety protection z 3 minutes delay for compressor ---The compressor is ceased for 3minutes before restarting to balance the pressure in the refrigeration cycle in order to protect the compressor. z 2 minutes delay for 4-way valve---The 4-way valve will be ceased for 2 minutes late after compressor to prevent the refrigerant-gas abnormal noise when the HEATING operation is OFF or switch to the other operation mode.

(2) Discharge temperature protection

There is a temperature sensor on top of compressor, when temperature on top of compressor exceeded the limit, system control will shut down the compressor and the display board will show the error code.

(3) lower voltage protection

When AC voltage ≤158V and keep it for 10 seconds, unit will be shut down for protection.

(4) Over voltage protection

When AC voltage ≥260V, unit will be shut down and recover while AC≤255V.

(5) Over current protection

When the current of outdoor unit is overload, controller shut down the unit immediately and show error code.

(6) Compressor abnormity protection

When compressor start on or in the process of running, if there is no feedback to controller or load of compressor is abnormity, the air conditioner will shut down, and show error code.

(7) IPM module protection

IPM module has high temperature & over current protection itself, if there is signal feedback to IPM, the outdoor unit will shut down, LED on outdoor PCB will show the error code.

2. “I Feel” Mode Operation

(1) When the “I Feel” mode is selected, the operation mode and initial temperature set are determined by the initial room temperature at start-up of the operation except to turn off the air conditioner and operates it again.

(2) If the mode is change to “I Feel” from other mode, the “I Feel” mode doesn’t operate until compressor stop for more than 3 minutes.

Mode

COOLING

Initial Room Temperature Initial Set Temperature

RT≥26℃ 23℃

DRY

26℃>RT≥20℃ RT-2℃

HEATING for Heat Pump

FAN for Cooling Only

RT<20℃ - z In the “I Feel” mode, when the controller receives the up or down sig nal of temperature, the set temperature can adjust by 1℃ upper or lower. The biggest you can adjust by

2℃ upper or lower.

3. “COOLING” Mode Operation

5

TCL Air Conditioner Service Manual

(1) Compressor frequency control

According to difference room temperature and set temperature(δt = RT-ST), running frequency of compressor is controlled by electronic controller. When room temperature is much higher than set temperature, compressor will start at a high frequency, and as room temperature goes down, compressor running frequency will go down. When room temperature is lower than set temperature, compressor will run at very low frequency. In general, unit will change its running frequency according toδt to make room temperature closing to set temperature.

(2) Outdoor temperature affects running frequency of compressor

Outdoor temperature affect compressor’s running frequency. Difference inlet temperature of outdoor unit is adapted by difference compressor running frequency. While outdoor temperature is about 30℃, the compressor will run in high frequency.

If unit run in “cooling” mode and outdoor temperature is less than -1℃,controller will shut down compressor and show error code, while the ambient temperature is over 0℃, the compressor will run automatically.

(3) Auto fan control in cooling mode

In cooling mode (include cooling in “I feel” mode), fan speed is determined by δt, as the following diagram:

RT-ST

δt come down

3.5

high fan

δt come up

3.0

1.5

1.0

midium fan low fan

(1) The system for DRY operation used the same refrigerant circle as the cooling one.

(2)

When the system operates in DRY mode, at first it operates in cooling mode at 16℃ or

18℃ for 3 minutes. After that, the system will operate in cooling mode with lowest fan speed, meanwhile the set temperature (ST) is “RT-2℃” which means that the ST is room temperature at then minus 2. During the course of this mode, the fan speed set operation and room temperature set are restricted, except the vane motor adjusting.

5. “HEATING” Mode Operation (available for Heat Pump only)

The same as the frequency control in cooing mode, running frequency of compressor is controlled by controller. Unit change its running frequency according to δt to make room temperature closing to the set temperature.

(2) Indoor fan motor control

1. Cold Air Prevention Control z The function is intended to prevent cold air from being discharged when the heating operation starts or when defrosting. z The indoor fan speed will be controlled as following.

6

TCL Air Conditioner Service Manual

37℃

33℃

25℃

T e m p e r a t u r e u p s e t t i n g l o w f a n b r e e z e s t o p

34℃

30℃

22℃

T e m p e r a t u r e d o w n z In the heating operation, if the air conditioner is turned off, the indoor fan motor will run most for 30 seconds since the stop of compressor.

2. Auto fan control (heating)

In heating mode(include in “I feel” mode) , fan speed is determined by δt, as the following:

R T - S T

3 . 5

3 . 0

δ t c o m e d o w n h ig h fa n

1 . 5

1 . 0

δ t c o m e u p m id iu m fa n lo w fa n

In heating mode, 4-way valve will power on ahead of compressor for 5 seconds, and cut off for 2 minutes later than compressor’s stop. 4-way valve will not power off unless the machine is switched off, mode changed or on the process of defrosting.

(4) Defrosting

Defrosting is controlled by the microprocessor.

When one of the following conditions is satisfied, unit will come into defrosting: a. Outdoor heat exchanger Temperature (OPT) is continuously less than 3℃ while the unit runs for more than 40 minutes, and OPT is keeping under -6℃ for more than 3 minutes. b. Outdoor heat exchanger Temperature (OPT) is continuously less than 3℃ meanwhile the unit runs for more than 80 minutes, and OPT is keeping under -4℃ for more than 3 minutes. c. Outdoor heat exchanger Temperature (OPT) is continuously less than 3℃ while the unit runs for more than 120 minutes, and OPT is keeping below -2℃ for more than 3 minutes.

Before the air con come into defrosting, compressor running frequency drop down to a lower frequency firstly, then the compressor shuts down.

In defrosting, the max. frequency of compressor is F9 (a little less than the highest frequency ). In this period all protection function are avaliable.

7

TCL Air Conditioner Service Manual c o m p r e s s o r

O N

O F F

4 - w a y v a lv e

O N

O F F o u t d o o r fa n m o t o r

O N

O F F

2 0 s 1 0 s ≤ 1 0 m 2 0 s 1 0 s

In defrosting, LED showing by winking.

Come into or out of defrosting, indoor fan motor speed is the same as Cold Air Prevention

Control.

One of the following conditions is satisfied, unit come out of defrosting and shift to heating mode:

a. Outdoor coil Temperature (OPT) ≥15℃

b. Defrost time keep time for more than 10 minutes.

(

5) Indoor exchanger overheat protection

When Indoor exchanger Temperature(IPT) is higher than 55 ℃ , unit come into indoor exchanger overheat protection. Compressor drop its frequency toward to F1 level until IPT≤52

℃; If IPT≤52℃ and keep for 5 minutes , control system don’t limit running frequency.

If IPT>62℃, control system shut down compressor, and recover when IPT drop less than 50℃.

6. “SLEEP” mode

When the SLEEP button is pressed, the SLEEP mode is selected as following: z The indoor fan speed is set at low speed, the power lamp and the sleep lamp is on, the display of temperature will be close after 5 minutes.

z When selecting COOLING/DRY operation with SLEEP mode, the set temperature will be raised by 1℃ 1 hour later and by 2℃ 2 hour later. z When selecting HEATING operation with SLEEP mode, the set temperature will be dropped by 1℃ 1 hour later and 2℃ 2hour later. z After the System operates in SLEEP mode for 8 hours, it will stop automatically.

7. EMERGENCY Operation

When the EMERGENCY Operation switch is pressed once, COOLING mode is selected and if in 3 seconds the EMERGENCY Operation switch is pressed again, mode is selected. Then pressed once again, the unit is switch off.

When the remote controller is missing, has failed or the batteries run down, press the

EMERGENCY Operation switch on the front of the indoor unit. The unit will start.

The first 30 minutes of operation will be the test run operation. The operation is for servicing.

The indoor fan runs at high speed and the system is in continuous operation. The thermostat is

ON and the timer is reset to normal.

After 30 minutes of test run operation the system shifts to AUTO COOLING/HEATING mode, and the indoor fan runs in automatic speed. The operation continues unit the EMERGENCY operation switch is pressed or a button on the remote controller is pressed, the normal operation will start.

NOTE: Do not press the EMERGEMCY Operation switch during normal operation.

8. AUTO-RESTART Function (Option)

1. When air conditioner is operating in one mode, all of its operation data, such as working mode and temperature of setup would be memorized into IC by main PCB. If power cuts due to

8

TCL Air Conditioner Service Manual some reason, when power supply come back again, the AUTO-RESTART function will set synchronously and automatically to work. So the air conditioner would work at the same mode before.

Auto-restart Pre-setting (optional)

:

If Auto-restart function is needed, follow the steps below to activate this function:

1) Pulling the air-con's plug out of socket.

2) Pressing and holding the Emergency button (ON/OFF) on the indoor, then insert the plug into the socket again.

3) Keep pressing the Emergency button for more than 10 seconds until three short beeps are heard. The Auto-restart function has been started.

9. Protection and Failure Display

z When protection display is available, controller will show error code, digital LED shows error code and setting temperature by turns. z If there is more than one failure, it will show at first that in front of the error list. z Protection display function can be selected in hardware, and the default don’t display; z To insure of in and out communist is credibility, the failures relate to outdoor unit will remain failure state for 2 minutes max after recovered. z In all failures, only sensor failures don’t have to repower to cancel. z Error list

Failure type

In and out communication failure

Outdoor communication failure

Outdoor sensor

Indoor coil temperature sensor

Outdoor coil temperature sensor

System abnormity

LED CODE

RUN、TIMER –both winking

RUN、TIMER –both winking

RUN-1 time/8s

RUN-2 times /8s

RUN-3 times /8s

RUN-4 times /8s

DIGITAL LED CODE

E0

EC

E1

E2

E3

E4

E5

Type mismatch

Indoor fan motor

Outdoor temperature sensor

Discharge temperature sensor

Invert module abnormity

RUN-5 times /8s

RUN-6 times /8s

RUN-7 times /8s

RUN-8 times /8s

RUN-9 times /8s

E6

E7

E8

E9

Current sensor

EEPROM failure

Top of compressor temperature switch

Voltage sensor

9

RUN-11 times /8s

RUN-12 times /8s

RUN-13 times /8s

RUN-14 times /8s

EA

EE

EP

EU

5

6

7

8

9

10

1

2

3

4

11

12

13

TCL Air Conditioner Service Manual

Protection display code list:

Protection type higher or lower voltage

LED CODE

RUN-winking,TIMER-1 time/8s

DIGITAL LED CODE

P1

Over current

Discharge temperature

RUN- winking,TIMER-2 times /8s

RUN- winking,TIMER-4 times /8s

P2

P4

Over cooling in cooling mode

Over heating in cooling mode

RUN-light,TIMER-5 times /8s

RUN- light,TIMER-6 times /8s

P5

P6

P7

Over heating in heating mode

Outdoor temperature too high or low

Drive protection(Overload)

RUN- light,TIMER-7 times /8s

RUN- light,TIMER-8 times /8s

RUN- winking,TIMER-9 times/8s

P8

P9

Module self protection RUN- winking,TIMER-10 times/8s P0 z Outdoor failure display

There is a LED on outdoor power board, when compressor is running; it is normally light; when no feedback of signal to power board from compressor, it will wink by lighting 1s and going out 1s. If failures happened, it will light 0.5s, go out 0.5s, winking several times and go out 3s for a cycle to indicate failures. The failure list is the follow:

Wink time Failure

IPM protection higher or lower voltage

Over current

Discharge temperature too high

Outdoor coil temperature too high

Drive abnormity

Communication abnormity with indoor unit

Compressor over heat(switch on top of compressor)

Outdoor air temperature sensor failure

Outdoor coil temperature sensor failure

Outdoor discharge pipe temperature sensor failure

Voltage sensor failure

Current sensor failure

15 Outdoor communication abnormity

16 DC fan motor no feedback

17 defrosting

10

TCL Air Conditioner Service Manual

Wiring diagram

Model: TAC-09CHSA/GI, TAC-12CHSA/GI

Indoor unit:

Outdoor Unit:

1

1

TCL Air Conditioner Service Manual

EXPLOSION VIEW

Indoor unit

Model: TAC-09CHSA/GI, TAC-12CHSA/GI

1

2

TCL Air Conditioner Service Manual

PART LIST

Indoor unit

Model: TAC-09CHSA/GI

No. Part No.

20 1070250109

Part Name

Terminal fixing board

25 1070320111 Indoor motor cover

30

Temperature assembly

1073030303 Remote controller supporter

Remark Q’ty

1

1

1

1

1

1

2

1

2

1

1

2

1

1

1

1

1

1

1

1

1

1

1

1

1

1

1

1

1 view

1

1

1

3

TCL Air Conditioner Service Manual

PART LIST

Indoor unit

Model: TAC-12CHSA/GI

No. Part No.

20 1070250109

Part Name

Terminal fixing board

25 1070320111 Indoor motor cover

30

Temperature assembly

1073030303 Remote controller supporter

Remark Q’ty

1

1

1

1

1

1

2

1

2

1

1

2

1

1

1

1

1

1

1

1

1

1

1

1

1

1

1

1

1 view

1

1

1

4

TCL Air Conditioner Service Manual

EXPLOSION VIEW

Outdoor unit

Model: TAC-09CHSA/GI, TAC-12CHSA/GI

1

5

TCL Air Conditioner Service Manual

PART LIST

Outdoor unit

Model: TAC-09CHSA/GI

No. Part No.

4

7

14

17

26

1080050004

1080050001

1120250427

1120250428

Part Name

Outdoor motor supporter

Left grille supporter

Three-way valve connecting pipe

Condenser connecting pipe

1170230007 Pipe Temp. sensor and outdoor Temp. sensor

Discharge sensor

Q’ty

1

1

1

1

1

1

2

1

2

1

1

Remark

1

1

1

1

1

1

1 750*350*8

1

1

1

1

1

1

1

1

1

32 1170100010 Fan motor capacitor

1

1

1

1

1

1

1

1

6

PART LIST

Outdoor unit

Model: TAC-09CHSA/GI

No. Part No.

TCL Air Conditioner Service Manual

Part Name

1

7

Q’ty

1

1

Remark

TCL Air Conditioner Service Manual

PART LIST

Outdoor unit

Model: TAC-12CHSA/GI

No. Part No.

1 1080050026

2 1080050011

3 1110050069

4 1080050004

5 1170040058

6 1070030016

7 1080050001

8 1080050007

10 1080320112

11 1100060052

12 1140020004

13 1120500226

14 1120321531

15 1120321529

16 1120321530

17 1120321532

18 1120321525

19 1140020011

Three-way valve connecting pipe

Condenser connecting pipe

21 1080050002

22 1120120021

23 1210250121 Base

24 1120130032

25 1170190003

26 1170200061

Inductor

Pipe Temp. sensor and outdoor Temp. sensor

Discharge sensor 28 1170230006

29 1070320202

30 1070040007

31 1170200061

32 1170100010

33 1070320207

Terminal

Fan motor capacitor

35 1090321113

36 1090320003

37 1170330001

Part Name

Grille

Condenser

Outdoor motor supporter

Left grille supporter

Radiator

18

Q’ty

1

1

1

1

1

1

2

1

Remark

1

1

1

1

1

1

1

1

1

1

1

1

1

1

1

1

1

PART LIST

Outdoor unit

Model: TAC-12CHSA/GI

No. Part No.

TCL Air Conditioner Service Manual

Part Name Q’ty

1

1

Remark

19