advertisement
Installation and Service Manual
TF-Series
Modular Design
Two-Stage R410a
Model Sizes 45-80 (3-6 Ton)
Triple Function Geothermal Heat Pumps
Maritime Geothermal Ltd.
P.O. Box 2555
Petitcodiac, N.B. E4Z 6H4
Ph. (506) 756-8135
01 JAN 2014
Email: [email protected]
Web: www.nordicghp.com
Document Number: 001223MAN-04
001223MAN-04
!
WARNING:
Ensure all access panels are in place and properly secured before applying power to the unit.
Failure to do so may cause risk of electrical shock.
WARNING:
Before performing service or maintenance on the heat pump system, ensure all power sources
are DISCONNECTED. Electrical shock can cause serious personal injury or death.
WARNING:
Heat pump systems contain refrigerant under high pressure and as such can be hazardous to
work on. Only qualified service personnel should install, repair, or service the heat pump.
CAUTION:
Safety glasses and work gloves should be worn at all times whenever a heat pump is serviced. A
fire extinguisher and proper ventilation should be present whenever brazing is performed.
CAUTION:
Venting refrigerant to atmosphere is illegal. A proper refrigerant recovery system must be
employed whenever repairs require removal of refrigerant from the heat pump.
MODEL NOMENCLATURE
TF—65—HACW—P—1T—CC—SDERF—xx
Series:
TF = Active Cooling Liquid to Air &
Liquid To Water
Revision:
01, 02 etc.
Fan Outlet Orientation:
D = Down flow
F = Field Configurable
Nominal Size:
45 = 3 Ton
55 = 4 Ton
65 = 5 Ton
75 = 6 Ton
80 = 6 Ton Single Stage
Functions:
H = Heating
AC = Active Cooling
W = Domestic Hot Water
Fan Return Orientation:
L = Left Return
R = Right Return
Fan Motor:
E = ECM (Variable Speed)
Refrigerant:
P = R410a
Fan Type:
D = Direct Drive
Air Coil:
S = Standard
Voltage Code:
1 = 230-1-60 VAC
2 = 208-3-60 VAC
6 = 220-1-50 VAC
7 = 380-3-50 VAC
Indoor Loop Exchanger:
C = Copper
Z = Cupro-Nickel (CuNi)
Compressor Stages*:
S = 1 Stage
T = 2 Stage
* 2 stage unless unavailable due to voltage code, refer to the
Electrical Tables
.
Outdoor Loop Exchanger:
C = Copper
Z = Cupro-Nickel (CuNi)
001223MAN-04 Page 2 01 JAN 2014
APPLICATION TABLE
SIZE FUNCTION REFRIGERANT VOLTAGE STAGES OUTDOOR
COIL
INDOOR
COIL
45
55
65
75
80
HACW
HACW
HACW
HACW
HACW
P
P
P
P
P
1 T
2 T
C
6 S
Z
7 T
1 T
2 T
C
6 S
Z
7 T
1 T
2 T
C
6 S
Z
7 T
1 T
2 T
6 S
C
Z
7 T
1 S
2 S
C
Z
7 S
C
Z
C
Z
C
Z
C
Z
C
Z
FAN/CASE
SDELF
SDERF
SDELF
SDERF
SDELF
SDERF
SDELF
SDERF
SDELF
SDERF
REVISIONS
13
13
13
13
13
13
13
13
13
13
13
13
13
13
13
13
13
13
13
01 JAN 2014 Page 3 001223MAN-04
Table of Contents
Unit description: ………………………………………………………………………………………………………..…... Page 6
Unpacking the unit: …………………………………………………………………………………………….…………... Page 6
Optimum Placement: …………………………………………………………………………………………………...…. Page 6
Electrical Connections: …………………………………………………………………………………………….……… Page 6
Circulator Pump Module Wiring (Ground Loop Only): …………………………………………………...…………. Page 6
Indoor Loop Circulator Wiring: ………………………………………………………………………….……………….. Page 6
Thermostat Requirements: ………………………………………………………………………………...…………….. Page 6
Aquastat Requirements: ………………...………………………………………………………………….…………….. Page 7
Priority Selection: ……………….………...………………………………………………………………...…………….. Page 7
Operational Description: ………………………………………………………………………………………………….. Page 7
Fan Motor: ……………………………………………………………………………………………………….…………… Page 10
Fan Return Orientation: ………………………...…………………………………………………………….…………… Page 10
Fan Outlet Orientation : ………………………...…………………………………………………………….…………… Page 10
Control Transformer : ……..…………………...…………….………………………………………………….…………
Safety Controls: …………………………………………………………………………………………………….……….
Domestic Hot Water Connections (HACW only): …………………...……………………………………...…………
Page 10
Page 10
Page 11
SIZING AND DUCTWORK: ………………...………………………………………………………………………………..………… PAGE 14
Heat Pump Sizing: …………………………………………………………………………………………………….……. Page 14
Duct Systems - General: ……………………………………………………………………………………………….….. Page 14
Duct Systems - Grill Layout: ………………………………………………………………………………………….…… Page 14
Thermostat Location: ………………………………………………………………………………………………….…… Page 15
Condensate Drain: ………………………………………………………………………………………………...……….. Page 15
Duct Sizing Guide: ………………………………………………………………………………………………….………. Page 17
HYDRONIC INFORMATION: …………………………………………………………………………………………………….……. PAGE 18
Hydronic Systems - General: ………………………………………………………………………………………...…… Page 18
GROUND WATER SYSTEM INFORMATION: ……………………………………………………………………………….……… PAGE 22
General Requirements: ………………….……………………………………………………………………….…...…… Page 22
Plumbing the Heat Pump: ……………………………………………………………………………………………...…. Page 22
Pipe Insulation: ……………………………………………………………………………………………………...……… Page 22
Water Discharge Methods: ……………………………………………………………………………………..………… Page 22
GROUND LOOP SYSTEM INFORMATION: ………………………………………………………………………………………... PAGE 25
Circulator Pump Module: ……………………………………………………………………………………………….…. Page 25
Flushing & Purging the Ground Loop: ……………………………………………………………………………….…. Page 25
Adding Antifreeze Solution: ………………………………………………………………………………………….…… Page 26
Initial Pressurization: ……………………………………………………………………………………………….……… Page 26
Pipe Insulation: …………………………………………………………………………………………………….……….. Page 26
STARTUP PROCEDURE: ………………………………………………………………………………………………………..……. Page 28
Pre-start Inspection: ……………………………………………………………………………………………….………. Page 28
Unit Startup (Air): …………..…...…………………………………………………………………………………….……. Page 29
Startup Record (Air): ……………….…..………………………………………………………………………….………. Page 30
Startup Record (Hydronic): ………………...………………………………………………………………….…………. Page 32
GENERAL MAINTENANCE: ……………...…………………….………………………………………………………….………… PAGE 33
TROUBLESHOOTING GUIDE: ………………………………….………………………………………………………....………… PAGE 34
Repair Procedures: ……………………………………………………………………………………………...………… Page 46
Refrigeration Circuit Diagrams: ………………………………………………………………………………...………. Page 47
Refrigerant Charge Chart: ………………………………………………………………………………………….……… Page 50
Shipping Information: …………………………………………………………………………………………...…...…… Page 50
Standard Capacity Ratings: ……………………...…………………………………………………………...…………. Page 50
Capacity Ratings: ……………………...………………………………………………………………………...……..…. Page 52
Hydronic Capacity Ratings: ……………………...…………………………………………………………...…………. Page 57
Electrical Tables: ………………………………………………………………………………………………...………… Page 60
Aquastat Connection Diagram: …………………………………………………………………………………………. Page 61
Electrical Diagrams (208/230-1-60): ………..……………………………………………………………...…………… Page 62
Case Details: ………………………...……………………………………………………………………...……………… Page 64
APPENDIX A: Control Board Specifications: …………………………………………………………………………..………… PAGE 67
APPENDIX B: ECM Fan Airflow Tables: ……………………………………………………………………………………..……. PAGE 68
WARRANTY INFORMATION: ……………………………………………………………………………………………….……….. PAGE 72
001223MAN-04 Page 4 01 JAN 2014
Tables, Diagrams and Drawings
01 JAN 2014
TABLES
Table 1 - Thermostat Signal Description: …….………...………………………………………………..…….... Page 6
Table 2 - Aquastat Signal Description: …….…………………….………………………………………..…….... Page 7
Table 3 - Typical Aquastat Settings: …….………………………..…...…………………………………..…….... Page 7
Table 4 - TF Control System Truth Table (Air Priority): …………………..…………………………………… Page 8
Table 5 - TF Control System Truth Table (Hydronic Priority): ……………..………………………………… Page 8
Table 6 - Airflow Selections: ………………………………………….……………………………………………... Page 10
Table 7 - Control Board Fault Codes: ……..…………………………………………………………….………... Page 11
Table 8 - Heat Pump Size vs. Heated Area for Ground Loop Systems: …..………………………………... Page 14
Table 9 - Heat Pump Size vs. Heated Area for Ground Water Systems: ….………………………………... Page 14
Table 10 - Heat Pump Size vs. Hot Air Grills: …..………………………………….………………..…………... Page 15
Table 11 - Plenum Heater Sizing: …..………………………………………………..……………………………... Page 15
Table 12 - Duct Sizing Guide: ………………………………………..…………...………………………………... Page 17
Table 13 - Required Flow and Air Tank Sizing: …..……………………………………………….……………... Page 22
Table 14 - Antifreeze Percentages by Volume: ………………………………..………………………………... Page 26
Table 15 - Volume of Fluid per 100ft. Of Pipe: …..………………………………….…………………………... Page 26
Table 16 - Refrigerant Charge Chart: ………...…………………..………………….….………………………... Page 50
Table 17 - Shipping Information: ………...………………………..………………….….………………………... Page 50
Table 18 - Standard Capacity Ratings - Ground Loop Heating 60Hz: …………..…………………………... Page 50
Table 19 - Standard Capacity Ratings - Ground Water Heating 60Hz: …………….………………………... Page 50
Table 20 - Standard Capacity Ratings - Ground Loop Cooling 60Hz: …….…….…………………………... Page 51
Table 21 - Standard Capacity Ratings - Ground Water Cooling 60Hz: …..…….…………….……………... Page 51
Table 22 - Standard Capacity Ratings - Ground Loop Hydronic Heating 60Hz: ……………...…………... Page 51
Table 23 - Standard Capacity Ratings - Ground Water Hydronic Heating 60Hz: ……….………………... Page 51
Table 24 - Heat Pump Electrical Information (230-1-60): …..…………………….….………………………... Page 60
Table 25 - Heat Pump Electrical Information (208-3-60): …..…………………….….………………………... Page 60
Table 26 - Heat Pump Electrical Information (220-1-50): …..…………………….….………………………... Page 60
Table 27 - Heat Pump Electrical Information (380-3-50): …..…………………….….………………………... Page 60
Table 28 - Plenum Heater Electrical Information: …..…………………………..……………………………... Page 60
DIAGRAMS
Diagram A - TF Control System Flow Chart (Air Priority): …………………………………….…………… Page 9
Diagram B - TF Control System Flow Chart (Hydronic Priority): …………………………….….………… Page 9
Diagram C - Typical P/T (Pete’s) Plug & Thermometer Stem: …….……………………….…………..…….. Page 25
Diagram D - Typical Purge Cart: …………………………………………………………………………………… Page 25
Case Details Top Views: ………..…………………….………………………………………………………….….. Page 64
Case Details - Left Return: ……..…………….…………...…………………………………………………….….. Page 65
Case Details - Right Return: ……………………...….………………………………………………………….….. Page 66
DRAWINGS
000344CDG - Typical Heating Only Zone Connection Diagram (TF&DXTF-Series): …...…………..…….. Page 12
000970PDG - Single Unit Connection to DHW Pre-Heat Tank (Brass FPT): ……………………………….. Page 13
001201CDG - Typical Duct and Condensate Connections (Modular Case): ….……………………………. Page 16
001046PDG - Typical Buffer Tank Configuration - Four Port Tank (Brass FPT): ………………………….. Page 19
000530PDG - Typical Zone Types for Hydronic Applications: ……………………………………………….. Page 20
001055PDG - Single Unit Connection to On-Demand DHW Pre-Heat Tank (Brass FPT): ……………….. Page 21
000907CDG - Typical Ground Water Installation for Size 25-75 Heat Pumps (Brass FPT): …………….. Page 23
000619INF - Ground Water Disposal Methods: ………………………………………………………………… Page 24
000906CDG - Geo-Flo Circulator Pump Module Installation: ………………………………………………… Page 27
001197RCD - Modular Parallel TF-Series Refrigeration Circuit Diagram—Heating Mode: ……...……… Page 47
001198RCD - Modular Parallel TF-Series Refrigeration Circuit Diagram—Cooling Mode: …….………. Page 48
001199RCD - Modular Parallel TF-Series Refrigeration Circuit Diagram—Hydronic Heating Mode: … Page 49
001244CDG - Modular Parallel TF(H)-Series Two-Stage Compressor Aquastat Connection Diagram: Page 61
001453SCH - TF-**-HAC*-P-1T-**-*DE** (Parallel) Schematic Diagram: ………...………...…………..…… Page 62
001454ELB - TF-**-HAC*-P-1T-**-*DE** (Parallel) Electrical Box Diagram: …….....……..…….…..……… Page 63
Page 5 001223MAN-04
Installation Information
UNIT DESCRIPTION
The TF-Series unit is a high efficiency two-stage geothermal heat pump with environmentally friendly R410a refrigerant.
Two-stage units offer longer runtimes and fewer cycles resulting in higher efficiency and a higher comfort level. It has three modes of operation: air heating, air cooling or hydronic heating.
NOTE: Air heating and hydronic heating cannot be
accomplished simultaneously.
An electrically commutated (ECM) fan with several speed options is standard. The motor has a soft start function for improved efficiency and reduced wear.
The unit has several key features that are described in the specifications document for the particular heat pump. Please request a copy if desired or visit www.nordicghp.com
UNPACKING THE UNIT
When the heat pump reaches its destination it should be unpacked to determine if any damage has occurred during shipment. Any visible damage should be noted on the carrier's freight bill and a suitable claim filed at once. The heat pump is well constructed and every effort has been made to ensure that it will arrive intact, however it is in the customer's best interest to examine the unit thoroughly when it arrives.
OPTIMUM PLACEMENT
For liquid to air units, to achieve the greatest efficiency, the heat pump should be centrally located in the home with respect to the conditioned space. This design provides the utmost in economy and comfort and usually can be accomplished in harmony with the design of the home. A heating system cannot be expected to produce an even warmth throughout the household when it is located at one end of the structure and the warm air is transmitted with uninsulated metal ductwork.
If possible the access panels should remain clear of obstruction for a distance of two feet to facilitate servicing and general maintenance.
Raising the heat pump off the floor a few inches is generally a good practice since this will prevent rusting of the bottom panel of the unit. We recommend that the heat pump be placed on a piece of 2'' thick styrofoam. The styrofoam will smooth out any irregularities in the cement floor and deaden any compressor noise emitted from the bottom of the cabinet.
The heat pumps come equipped with an air-filter rack which can be installed with the removable end (where the filter is inserted) on either side to facilitate changing the filter.
ELECTRICAL CONNECTIONS
The heat pump has a concentric 1.093” / 0.875” knockout for power supply connection to the electrical box. There is also a 0.875” knockout for connection to the circulator pump module for ground loop applications. There are two 1/2” openings with plastic grommets (grommet hole is 3/8”) in the upper section of the electrical box, one for the thermostat connections, and one for the optional plenum heater connections.
A schematic diagram (SCH) and electrical box layout diagram (ELB) can be found inside the electrical box cover of the unit as well as in the Model Specific section of this manual.
The Electrical Tables in the Model Specific section and the ELB diagram contain information about the size of wire for the connections, as well as the recommended breaker size. A
properly qualified electrician should be retained to make the connections to the heat pump and associated controls.
The connections to the heat pump MUST CONFORM TO
LOCAL CODES.
CIRCULATOR PUMP MODULE
WIRING (GROUND LOOP ONLY)
The heat pump has provisions for connecting the circulator pump module so that the pumps will be turned on whenever the compressor operates. Connect the circulator pump module to the appropriate two terminals of the terminal strip marked
OUTDOOR CIRCULATORS in the heat pump, as per the voltage of the circulator pump module. Ensure that the total current draw does not exceed the value indicated on the label in the heat pump electrical box. Refer to the electrical box drawing on the electrical box cover for more information.
INDOOR LOOP CIRCULATOR WIRING
The Indoor Loop circulator provides flow between the heat pump and the buffer tank. The heat pump has provisions for connecting the Indoor Circulator so that it will be turned on whenever the compressor operates. Connect the Indoor Loop circulator to the appropriate two terminals of the terminal strip marked INDOOR CIRCULATORS in the heat pump, as per the voltage of the circulator pump module. Ensure that the total current draw of all pumps connected to the terminal strip does not exceed the value indicated on the label in the heat pump electrical box. Refer to the electrical box drawing on the electrical box cover for more information.
THERMOSTAT REQUIREMENTS
The TF-Series unit requires a three-stage heating and two stage cooling thermostat for proper forced air operation. The stages are S1 = Stage 1 compressor, S2 = Stage 2 compressor and S3 = electric auxiliary (heating only). One can be purchased with the unit, or other thermostats with the same number of stages can be used. The electrical box diagram (ELB) on the electrical box cover pro- vides a description of the signal connections as does
TABLE 1
.
TABLE 1 - Thermostat Signal Description
Signal Description
G
Y
1
R
H
L
Fan low speed (for air circulation)
Heat Pump Stage 1 Air
W
2
Fault (24VAC when fault condition)
Heat Pump Stage 3 Air (auxiliary heat) /
Emergency Heat
Cooling Mode (reversing valve) O
Y
2
AR
1
Heat Pump Stage 2 Air
Airflow Reduction*
AR
2
Reduction*
I Plenum Heater dry contact
1 Plenum Heater dry contact
* Connect AR
1
to AR
2
with a dry contact to reduce the airflow by 15%. Refer to the Fan Motor sub-section for more information.
001223MAN-04 Page 6 01 JAN 2014
NOTE: Some models are not available in two-stage at the present time (see Electrical Tables ). The Y2 signal is not used for these units.
AQUASTAT REQUIREMENTS
The heat pump requires a two-stage aquastat for proper hydronic operation. The stages are S1 = low speed, and S2 = high speed.
A two-stage aquastat can be purchased with the unit, or other system controllers with dry contacts may be used. This manual covers operation of the heat pump with an aquastat.
The aquastat connection diagram (CDG) can be found near the end of this manual and on the electrical box cover of the unit. It provides a description of the signal connections in the heat pump. They are also listed in
TABLE 2
.
TABLE 2 - Aquastat Signal Description
Signal
Y2A
Y1A
Description
Heat Pump Stage 2 Hydronic
Heat Pump Stage 1 Hydronic
The aquastat can be placed anywhere within the range of the probe cable. The probe(s) should be inserted into a dry well in or near the top of the tank for optimal operation
(refer to
drawing 000533PDG) . If a dry well is not available, it may be possible to fix the probe to the tank inside the insulation.
TABLE 3
shows typical settings for the aquastat. With these settings, Stage 1 will activate when the tank temperature reaches the activation point. If the load is too great, the tank temperature will continue to drop until Stage 2 is activated. As the tank temperature stops dropping and begins to increase ,
Stage 2 will turn off before Stage 1, rather than at the same time as Stage 1. There are three main advantages to this:
•
Less aquastat probe lag leading to reduced overshoot as the tank temperature rate of change is reduced when only
•
Stage 1 is active.
Prolonged Stage 1 runtime leads to increased overall efficiency as Stage 1 has a higher COP than Stage 2.
•
Reduced number of compressor starts.
The settings may be changed as desired; however Stage 1 setpoint should not exceed
120°F (49°C)
; Exceeding this setpoint limit will cause the heat pump operating pressures to approach the safety control settings, possibly causing nuisance shut downs.
TABLE 3 - Typical Aquastat Settings
Item °F
Stage 1
°C
°F
Stage 2
°C
Delta 5 3 5 3
Activation * 110 43 100 38
*Activation is indirectly set by the Setpoint and Delta values
If only floor zones are being heated, it is highly rec-
ommended to drop each of the setpoints by 15°F (8°C) for increased efficiency.
01 JAN 2014
It is recommended that a buffer tank with electric elements be selected to provide auxiliary / backup heat. The tank element thermostats can be set to a low value of around 60F (15C) which will prevent the hydronic system from becoming too cold should there be a failure in the heating system.
Drawing 000344CDG
shows how a typical zone system would be setup with the TF unit. The zone controls and heat pump operate independently, there are no connections between the two systems.
PRIORITY SLECTION
Units are shipped setup for air priority. To convert to hydronic priority, simply remove the jumper wire between the two PR terminals on the aquastat terminal strip. See the electrical box & schematic diagrams for more information.
OPERATIONAL DESCRIPTION
The TF unit is designed to deliver heat to the mode that requires it the most. Once the default priority has been selected, the unit will interpret the control signals and deliver heat based on logic described below. This logic can also be seen in
TABLE 4
and
TABLE 5
, in a truth table format or in
DIAGRAM A
and
DIAGRAM B
in flowchart format. Simply put, whenever there is a call on both air and hydronic, the unit steps up to Stage 2 of the priority mode (if it was not already there) in order to satisfy the demand quickly and return to the non-priority mode.
SINGLE MODE OPERATION:
If there is only an air mode call (Y1 and/or Y2 and/or W2) the unit operates in air mode as Stage 1, Stage 2 or Stage 3.
If there is only a hydronic mode call (Y1 and/or Y2) the unit operates in hydronic mode as Stage 1 or Stage 2.
AIR MODE PRIORITY OPERATION:
If there is a call for both Stage 1 air and Stage 1 hydronic, the unit operates in Air Mode as Stage 2.
If there is a call for both Stage 2 air and Stage 1 hydronic, the unit operates in Air Mode as Stage 2.
If there is a call for both Stage 2 air and Stage 2 hydronic, the unit operates in Air Mode as Stage 2.
HYDRONIC MODE PRIORITY OPERATION:
If there is a call for both Stage 1 air and Stage 1 hydronic, the unit operates in Hydronic Mode as Stage 2.
If there is a call for both Stage 2 air and Stage 1 hydronic, the unit operates in Hydronic Mode as Stage 2.
If there is a call for both Stage 2 air and Stage 2 hydronic, the unit operates in Hydronic Mode as Stage 2.
NOTES:
Stage 3 (W2) of Air Mode overrides Hydronic Mode even if
Hydronic Mode has priority. This unit functions this way because either the air temperature has dropped significantly in order to reach Stage 3 or the thermostat has been set to Emergency Mode.
The fan can operate in recirculation mode (G) only if there is not a hydronic Stage 1 (Y1A) signal present, regardless of priority selection.
Page 7 001223MAN-04
TABLE 4 - TF Control System Truth Table (Air Priority)
CONTROLS SYSTEM OPERATION
Thermostat Aquastat
AIR MODE
STAGE 1
AIR MODE
STAGE 2*
AIR MODE
STAGE 3
HYDRONIC
STAGE 1
HYDRONIC
STAGE 2
STAGE 1 STAGE 2 STAGE 3 STAGE 1 STAGE 2
X
X X
X
X
X X X
X
X X
X
X X
X
X X
X X X
X X X X
X
X
X
X X
X X X
X X X X
X X X X X
X X
X X
X**
X**
* An X in both Stage 2 and Stage 3 indicates that the compressor and plenum heat are active.
** This is emergency heat situation. Only the plenum heater is active.
TABLE 5 - TF Control System Truth Table (Hydronic Priority)
CONTROLS SYSTEM OPERATION
Thermostat Aquastat
AIR MODE
STAGE 1
AIR MODE
STAGE 2*
AIR MODE
STAGE 3
HYDRONIC
STAGE 1
HYDRONIC
STAGE 2
STAGE 1 STAGE 2 STAGE 3 STAGE 1 STAGE 2
X
X X
X X X
X
X
X
X X
X
X X X
X X
X X X
X
X
X X X X
X X X
X X X X
X
X X
X X
X X X X X
X**
X X
X**
* An X in both Stage 2 and Stage 3 indicates that the compressor and plenum heat are active.
** This is emergency heat situation. Only the plenum heater is active.
001223MAN-04 Page 8 01 JAN 2014
Thermostat
G
DIAGRAM A - TF CONTROL SYSTEM FLOW CHART (AIR PRIORITY)
Thermostat
STAGE 1
(Y1)
Thermostat
STAGE 2
(Y2)
Thermostat
STAGE 3
(W2/E)
Aquastat
STAGE 1
(Y1A)
Aquastat
STAGE 2
(Y2A)
ON ON ON ON OFF OFF
ON
ON
OFF
AND
AND
AND
OR AND AND
FAN
RECIRCULATE
AIR MODE
STAGE 1
AIR MODE
STAGE 2
PLENUM
HEATER
HYDRONIC MODE
STAGE 1
HYDRONIC MODE
STAGE 2
DIAGRAM B - TF CONTROL SYSTEM FLOW CHART (HYDRONIC PRIORITY)
Thermostat
G
Thermostat
STAGE 1
(Y1)
Thermostat
STAGE 2
(Y2)
Thermostat
STAGE 3
(W2/E)
Aquastat
STAGE 1
(Y1A)
Aquastat
STAGE 2
(Y2A)
ON ON ON ON OFF OFF
ON
ON
AND
AND AND
FAN
RECIRCULATE
01 JAN 2014
AIR MODE
STAGE 1
AIR MODE
STAGE 2
PLENUM
HEATER
Page 9
AND
AND OR
HYDRONIC MODE
STAGE 1
HYDRONIC MODE
STAGE 2
001223MAN-04
FAN MOTOR
The unit is equipped with a direct drive ECM fan motor for maximum efficiency. The motor features a soft start which further improves efficiency by eliminating inrush current and provides a smooth, quiet ramp up to speed . The motor will maintain the programmed air flow up to the maximum external static value. Refer to the
APPENDIX B: ECM Fan Airflow Tables.
The air flow can be set to four different levels by changing the position on the Air Flow board located in the electrical box.
The four levels are indicated in
TABLE 6
. The actual air flow values can be found in
APPENDIX B
.
CONTROL TRANSFORMER
The low voltage controls are powered by a 75VA class II transformer. The transformer has a resettable breaker on the secondary side for circuit protection. Should the breaker trip, locate and correct the problem and then reset the breaker by pressing in on it.
NOTE: For 208/230VAC-1-60 units, if connecting to 208VAC power supply move the red wire connected to the 240 terminal of the transformer to the 208 terminal of the transformer.
TABLE 6 - Airflow Selections
Position Airflow
LOW -6%
MED Nominal
HIGH +6%
MAX +12%
Units are shipped with the MED position selected for nominal air flow. The air flow can be further reduced by 15% by making a dry contact across AR
1
and AR
2
on the terminal strip.
This can be used for applications that have multiple zones, or retrofits with undersized ductwork, to help reduce air flow noise in the ductwork. It is recommended that airflow reduction only be used with the High or Max air flow setting. Care should be taken to ensure that the unit does not trip a safety control in heating or cooling mode if the 15% reduction is used in conjunction with the MED or LOW air flow setting.
FAN RETURN ORIENTATION
The TF-Series heat pump can be ordered as a left or right hand return from the factory. This must be specified at time of order as the physical construction of the two configurations is different. Refer to the specification documents for more details.
FAN OUTLET ORIENTATION
The TF-Series heat pumps have a field configurable fan.
It’s default location from the factory is in the top of the unit, providing a “ninety” in the airflow. It can easily be placed in the side of the unit for straight through airflow.
To switch the location of the fan outlet follow these simple steps:
1. Turn the power of to the unit.
2. Remove the screw that holds the side access panel in place and remove the access panel by pulling up on the handle and then outward from the bottom.
3. Disconnect the two wire harnesses and ground wire from the fan motor.
4. Repeat step 2 for the access panel with the fan mounted in it. Set the assembly on the floor.
5. Disconnect the plenum heater extension from the fan housing and from the access panel.
6. Mount the fan housing directly to the access panel.
7. Install the fan/panel in the new location and secure with the screw.
8. Reconnect both harnesses and ground wire.
9. Install the remaining access panel and secure with the remaining screw.
SAFETY CONTROLS
The heat pump has two built in safety controls which are designed to protect the unit from situations which could damage it should the operation of the refrigeration circuit fall outside the allowable operating range.
A. Low Pressure Control
The low pressure control monitors the compressor suction pressure and will shut the compressor down if the refrigerant evaporating pressure becomes too low, risking the danger of freezing conditions in the evaporator.
There are (3) main reasons why this control would activate in response to the operating conditions of the unit while operating in heating mode:
1. Low or no Outdoor loop flow.
2. Low Outdoor loop entering liquid temperature.
3. Dirty or fouled Outdoor loop heat exchanger.
B. High Pressure Control
The high pressure safety control monitors the compressor discharge pressure and will shut the compressor down if the condensing pressure becomes too high.
There are (3) main reasons why this control would activate in response to the operating conditions of the unit while operating in heating mode:
1. Low or no airflow.
2. High return air temperature.
3. Dirty air coil due to poor filter maintenance.
The unit contains a control board that monitors the safety controls and operates the compressor accordingly. Refer to
APPENDIX A
for control board specifications. The low pressure control is connected to LP1 and LP2. The high pressure control is connected to HP1 and HP2.
The control board also has provisions for a flow switch.
The flow switch is unused from the factory and a jumper wire is placed across the FLOW SWITCH terminals. If a flow switch is desired, the jumper can be removed and the two leads from the flow switch can be connected to the FLOW SWITCH terminals on the safety board. The flow switch is ignored for 30 seconds on compressor startup to allow time for flow to be established.
The high and low pressure controls are monitored at all times.
The compressor will not be able to start if either of them has a fault.
The control board has an on-board LED and a FAULT pin with a 24VAC output. An external indicator or relay can be connected across the FAULT pin and ground if external signaling is desired. Should a fault occur, the LED will flash the code of the fault condition while the safety control in question is open.
The codes are shown in
TABLE 7.
The control board will lock
001223MAN-04 Page 10 01 JAN 2014
out the compressor for five minutes when a fault occurs. Three retries per fault condition are allowed within a 60 minute period.
If the fault condition occurs a fourth time the control board will
If the control board enters permanent lockout mode there is a serious problem with the system and it must be rectified if the unit is to maintain good service.
DOMESTIC HOT WATER
CONNECTIONS (HACW only)
permanently lock out the compressor and energize the FAULT pin. This can only be reset by powering down the unit. The
LED will flash the fault code until the unit is reset.
!
The port connections for the DHW circuit are 1/2” brass FPT fittings.
A typical piping diagram for a pre-heat tank configuration can be found in
drawing 000970PDG
at the end of this section.
Be sure to note the position of the check valve and the direction of water flow. Other configurations are possible, and there may be multiple units tied together in larger buildings.
TABLE 7 - Control Board Fault Codes
Fault
High Pressure
Code
1
!
WARNING: USE ONLY COPPER LINES TO
CONNECT THE DESUPERHEATER. TEMPERA-
TURES COULD REACH 200F SHOULD THE DHW
CUTOUT SWITCH FAIL, POTENTIALLY RUPTURING
PEX PIPING. Low Pressure 2
Flow 3
WARNING: REPEATED RESETS OF A LOW PRES-
SURE LOCKOUT COULD CAUSE THE HEAT EX-
CHANGER TO FREEZE AND RUPTURE, DESTROYING
THE HEAT PUMP AND VOIDING THE WARRANTY.
when it is started.
Ensure the tank is filled with water and under pressure before activating the heat pump. Slightly loosen the boiler drain on the DHW Out pipe to allow air to escape from the system before the unit is started. This step will make certain that the domestic hot water circulator in the unit is flooded with water
!
CAUTION: the domestic hot water pump is water lubricated; damage will occur to the pump if it is run
dry for even a short period of time.
Connect the brown wire with the blue insulated terminal to
L1 of the compressor contactor. Ensure the power is off
when connecting the wire.
The DHW loop may have to be purged of air several times before good circulation is obtained. A temperature difference between the DHW In and DHW Out can be felt by hand when the circulator pump is operating properly.
For the pre-heat tank setup, the final tank should be set to
140°F(60°C),
unless local code requires a higher setting.
The pre-heat tank does not require electric elements. This setup takes full advantage of the desuperheater as it is the sole heat provider to the pre-heat tank. The desuperheater remains active during the compressor runtime until the pre-heat tank has been completely heated by the desuperheater alone. This setup is more energy efficient than a single tank setup.
CAUTION: If two (2) shut-off valves are located on the domestic hot water ines as shown in the diagram, a pressure relief valve must be installed to prevent possible damage to the domestic hot water circulator pump should both valves be closed.
01 JAN 2014 Page 11 001223MAN-04
001223MAN-04 Page 12 01 JAN 2014
01 JAN 2014 Page 13 001223MAN-04
Sizing and Ductwork
HEAT PUMP SIZING
TABLE 8
depicts a rough guideline as to the size of home each heat pump size can handle for ground loop installations. document) in conjunction with the minimum expected entering liquid temperature of the ground loop (well water temperature for ground water system). The heat pump output must be able to match the total heat loss at the selected entering water temperature in order to provide a comfortable environment with minimal auxiliary heat.
TABLE 8 - Heat Pump Size vs. Heated Area
for a Ground Loop System
Model
Size (tons)
Sq.ft.
Sq.m.
DUCT SYSTEMS - GENERAL
45 3 1,400
55 4 2,000
65 5 2,600
trunks required. Air temperature leaving the heat pump is normally
95º -105ºF (35-40ºC),
much cooler than that of a
75 6 3,100
80 6 3,500
TABLE 9
depicts a rough guideline as to the size a home each heat pump size can handle for ground water installations.
TABLE 9 - Heat Pump Size vs. Heated Area
for a Ground Water System
Model
Size (tons)
Sq.ft.
Sq.m.
45 3 1,800
55 4 2,500
consequently duct sizing must be able to accommodate the greater air flow without creating a high static pressure or high velocity at the floor diffusers.
A duct system capable of supplying the required air flow is of utmost importance. Maritime Geothermal Ltd. recommends that the static pressure be kept below 0.2 inches of water total. In some instances the number of floor diffusers will actually double when compared to the number that would be used for a hot air oil-fired furnace. Refer to
TABLE 12
at the end of this section.
65 5 3,200
75 6 3,800
80 6 4,200
surface area of leads being fed at any given point.
4. Return air grills should have a minimum of the same total
square surface area as the total of the supply grills.
THE TABLES ABOVE ARE FOR INFORMATION ONLY,
THEY SHOULD NOT BE USED TO SELECT A UNIT SIZE.
They simply show on average what size unit is required for a
5. The square surface area of the return trunks should equal
the square surface area of the grills being handled at any
given point along the trunk. typical two-level home (main level and below grade basement) with R-20 walls, R-40 ceiling and average size and number of windows. The Heated Area is the area of the main level, The tables account for a basement the same size as the heated area.
It is VERY IMPORTANT that all turns in both the supply trunks and the return trunks be made with
TURNING RADII
. Air act like a fluid and, just like water, pressure drop is increased when air is forced to change direction rapidly around a sharp or
MARITME GEOTHERMAL LTD. HIGHLY RECOMMENDS
THAT A PROPER HEAT LOSS/GAIN ANALYSIS BE PER-
FORMEDE BY A PROFESSIONAL INSTALLER WITH CSA
APPROVED SOFTWARE BEFORE SELECTING THE SIZE OF
irregular corner.
It is recommended that flexible collars be used to connect the main trunks to the heat pump. This helps prevent any vibrations
UNIT REQUIRED FOR THE APPLICATION. For heating dominant areas, we recommend sizing the unit to 100% of the heating design load for maximum long term efficiency with minimal supplementary heat. The unit should be in-
from travelling down the ductwork. If a plenum heater is installed, the collar should be at least 12” away from the heater elements.
The first 5-10 feet of the main supply trunks should be insulat-
stalled as per CSA 448.2-02. For ground loop applications, the ground exchanger should be designed using suitable software with a multi-year analysis.
ed with acoustical duct insulation to further inhibit any noise from the unit from travelling down the ductwork. If a plenum heater is installed, insulation should not be placed within 12” of the heater elements.
Drawing 001201CDG
shows a typical installation.
There are many factors to consider when sizing the heat pump. Some of these factors include the number of levels, the size of the windows, the orientation of the home, attached gar-
DUCT SYSTEMS - GRILL LAYOUT
age, bonus rooms, walk-in basement, coldest outdoor temperature, etc. The heat loss program will take all of these factors into consideration in its calculations. An undersized installation will not be as efficient as it will require excessive relatively expensive supplemental heat to maintain a comfortable temperature in the home, and the cost savings of having a geothermal heat pump are greatly reduced.
Once the total heat loss has been calculated, the unit can be sized using the performance tables (from the specifications
Most forced air heating systems in homes have the floor grills placed around the perimeter of the room to be heated. Supply grills should be placed under a window when possible to help prevent condensation on the window. As mentioned in the previous sub-section, supply grill leads should be 6'' in diameter (28 sq.in. each) to allow 100cfm of air flow.
In a typical new construction, there should be one supply grill for every 100sq.ft. of area in the room. When rooms require more than one grill, they should be placed in a manner that promotes even heat distribution, such as one at each end of the
001223MAN-04 Page 14 01 JAN 2014
room. It is always a good idea to place a damper in each grill supply or place adjustable grills so that any imbalances in the heat distribution can be corrected.
The total number of supply grills available is based on the heat pump nominal airflow.
TABLE 10
shows the number of grills available per heat pump size.
TABLE 10 - Heat Pump Size vs. Hot Air Grills
Model
Size (tons)
# of Grills (@100cfm)
45 3
55 4
65 5
75 6
80 6
12
15
19
21
24
Return grills should be mounted on the floor. At minimum they should be the same size as the supply grill, it is highly
recommended that they be 25% to 50% larger than the total
supply. They should be placed opposite the supply grills when possible to ensure distribution across the room. For rooms requiring more than one supply grill, it may be possible to use one larger return grill if it can be centrally positioned opposite of the supply grills, however it is preferred to have one return for each supply to maximize heat distribution across the room.
THERMOSTAT LOCATION
Most homes are a single zone with one thermostat. The thermostat should be centrally located within the home, typically on the main floor. It should be placed away from any supply grills, and should not be positioned directly above a return grill. Most installations have the thermostat located in a hallway, or in the inner wall of the living room. It should be noted that most homes do not have any supply ducts in the hallway. This can lead to a temperature lag at the thermostat if there is very little air movement in the hallway, causing the home to be warmer than indicated by the thermostat.
PLENUM HEATER (OPTIONAL)
For installations that do not already have a backup heat source such as electric baseboard, wood stove, propane etc, it is recommended that a plenum heater be installed. This provides two functions.
The first function of the plenum heater is to act as an auxiliary heat source. As such it will provide additional heat on extremely cold days if the heat pump is unable to bring the home temperature up quickly enough, eliminating any discomfort to the homeowner.
The second function of the plenum heater is to provide emergency heat should a problem occur that causes the heat pump to be locked out. This can be engaged by setting the thermostat to emergency heat, allowing the plenum heater to function while preventing the heat pump from operating. Should the heat pump fail while the home is vacant, the auxiliary function of the thermostat will maintain the temperature setting of the thermostat.
INSTALLATION—Fan outlet at top of unit: The heat pump comes equipped with an internal mounting location for the plenum heater. Remove the screws from the cover plate, remove the cover plate and place the plenum heater in the hole. Secure it in place with the cover plate screws. Use the indicated knockouts on the heat pump case for electrical connections.
01 JAN 2014 Page 15
When installation is complete, check the appropriate box of the label on the air handler door to indicate which size heater was installed.
INSTALLATION—Fan outlet at side of unit: The plenum heater should be installed in the supply duct in a manner that allows all of the airflow to pass through it to prevent any hot spots in the heater elements. Ensure that the plenum heater is mounted in an approved position as per its instructions.
Only two control wires are needed to connect the plenum heater to the heat pump terminal strip. Refer to the label on the plenum heater or the electrical box diagram on the inside of the electrical box cover of the compressor unit for details on the connections.
The plenum heater requires its own separate power supply. TABLE 11
shows the recommended size plenum heater, as well as the wire size and breaker size needed to provide power to the plenum heater. Refer to the Electrical Tables for electrical connection information.
TABLE 11 - Plenum Heater Sizing
Heat
Pump
Model
Size
Plenum Heater Sizes (kW)
Recommended Available
75 - 80 20 15
CONDENSATE DRAIN
The unit comes equipped with a 3/4” PVC socket fitting
(female) labeled “Condensate Drain”. This drain allows the condensate which forms during the air-conditioning cycle to be removed from the unit. The drain should be connected as per local codes. During high humidity weather, there could be as much as 25 gallons of water formed per day.
Care should be taken in the spring to ensure that this pipe is not plugged with dust that has collected during the winter causing the condensate to overflow into the bottom of the heat pump and onto the floor. The condensate drain is internally
trapped; however, proper venting is required external to the heat pump. Refer to local codes to ensure the installation is done properly. Drawing 001201CDG
shows a typical installation.
001223MAN-04
001223MAN-04 Page 16 01 JAN 2014
380
452
452
531
616
616
707
201
254
254
314
314
380
707
804
804
908
908
6500
7250
7800
8500
9200
9800
10900
1450
1750
2000
2250
2600
2900
3400
3600
4300
5250
6125
TABLE 12 - Duct Sizing Guide (external static of 0.20”H2O)
Airflow
(CFM)
37
Minimum
Duct Area
(sq.in)
Diameter
(in)
20 5
Rectangular Equivalents (in)
2.25 x 10 3 x 8 3.5 x 6 4 x 5.5 5 x 5
63
100
20
28
5
6
2.25 x 10 3 x 8
3.25 x 10 4 x 8
3.5 x 6 4 x 5.5 5 x 5
5 x 6 5.5 x 5.5 6 x 6
152
212
226
277
304
393
38
50
50
64
64
79
113
7
8
8
9
9
10
3.25 x 14 4 x 11
4 x 15 5 x 12
4 x 15
5 x 15
5 x 15
6 x 15
5 x 12
6 x 12
6 x 12
7 x 13
5 x 8.5
6 x 10
6 x 10
7 x 10
7 x 10
8 x 11
6 x 7 6.5 x 6.5
7 x 8 8 x 8
7 x 8 8 x 8
8 x 9 8.5 x 8.5
8 x 9 8.5 x 8.5
9 x 10 9.5 x 9.5
411
655
680
995
1325
113
154
154
201
12
12
14
14
16
7 x 18
7 x 18
8 x 22
8 x 22
8 x 30
8 x 16
8 x 16
9 x 19
`
9 x 14
9 x 14
10 x 12
10 x 12
11 x 11
11 x 11
10 x 17 11 x 15 12 x 14 13 x 13
9 x 19 10 x 17 11 x 15 12 x 14 13 x 13
10 x 22 12 x 18 14 x 16 15 x 15
Return Air
Diameter
(in)
Airflow
(L/s)
5 17
6
7
30
47
10
10
12
12
8
9
72
100
107
131
143
185
194 12
14
14
16
18
309
321
470
625
32
32
34
34
28
30
30
24
26
28
20
22
22
24
16
18
18
20
8 x 30 10 x 22 12 x 18 14 x 16 15 x 15
8 x 40
8 x 40
10 x 30
10 x 30
12 x 24
12 x 24
14 x 20
14 x 20
16 x 17 16.5 x 16.5
16 x 17 16.5 x 16.5
10 x 38 12 x 30 14 x 26 16 x 22 18 x 19 18.5 x 18.5
10 x 38 12 x 30 14 x 26 16 x 22 18 x 19 18.5 x 18.5
12 x 36 14 x 30 16 x 26 18 x 23 20 x 20
12 x 36 14 x 30 16 x 26 18 x 23 20 x 20
14 x 38 16 x 32 18 x 28 20 x 25 22 x 22
14 x 38 16 x 32 18 x 28 20 x 25 22 x 22
16 x 38 18 x 32 20 x 30 22 x 24 24 x 24
18 x 38 20 x 34 22 x 30 24 x 28 26 x 26
18 x 38 20 x 34 22 x 30 24 x 28 26 x 26
20 x 40 22 x 38 24 x 32 26 x 30 28 x 28
20 x 40 22 x 38 24 x 32 26 x 30 28 x 28
22 x 40 24 x 38 26 x 34 28 x 32 30 x 30
22 x 40 24 x 38 26 x 34 28 x 32 30 x 30
24 x 42 25 x 40 26 x 38 28 x 34 30 x 32 31 x 31
24 x 42 25 x 40 26 x 38 28 x 34 30 x 32 31 x 31
28 x 40 30 x 36 32 x 34 33 x 33
30 x 42 32 x 38 34 x 36 35 x 35
30 x 45 34 x 40 36 x 38 37 x 37
20
684
826 20
22
944
22
1062
24 1227
24 1369
26
1605
26
1699
28 2029
30
2478
32
2891
34 3068
34 3422
36
3681
36 4012
38 4342
38
4625
40
5144
01 JAN 2014 Page 17 001223MAN-04
HYDRONIC INFORMATION
HYDRONIC SYSTEMS - GENERAL
The most common applications for the TF-Series hydronic heating are: (see
drawing 000530PDG
for typical zone types)
•
•
• radiant in-floor heating
On-demand domestic hot water
Swimming pool or spa
The radiant in-floor areas of the home may be sectioned into several areas called zones. Each zone has its own thermostat, allowing simple separate temperature control of the individual areas in the home. A typical system consists of the heat pump, the buffer tank and the zones. The sole purpose of the heat pump is to maintain the buffer tank set point. Its operation is independent of the zone operation.
HYDRONIC SYSTEM CONNECTIONS
The port connections for the Indoor Loop are 1” brass FPT fittings They are marked as INDOOR IN and OUT.
Flow through the unit is provided by an external circulator connected to the Indoor Loop Circulator terminal strip in the electrical box of the unit. The circulator is only powered when in hydronic heating mode and the compressor is operating.
Drawing 001046PDG
shows a typical piping configuration for a single unit with a buffer tank. This is a guideline for a simple installation. This is a typical installation where there may be one or several floor zones or even fan coils. There are many other configurations, such as, multiple units connected to one buffer tank, on-demand domestic only, etc… It is recommended that the hydronic system be designed by a qualified system designer to ensure proper functionality.
Drawing 001055PDG
shows two typical on-demand domestic hot water systems, dedicated and zoned. For a dedicated setup, there are no zones and the home is heated solely by air.
The TF unit can very easily be switched between air or hydronic priority during installation simply by placing or removing a jumper between the set of PR pins on the aquastat terminal strip.
Jumper in place sets the unit to air priority.
WARNING: Most indirect tank heat transfer ratings
!
are done at high water temperatures such as 160°F
(71°C). Be sure to select an indirect tank that has a transfer rate of at least the heat pump capacity at open loop conditions (refer to TABLE 20). Failure to do so can lead to nuisance high pressure trips due to inadequate heat transfer from the heat pump to the tank.
001223MAN-04 Page 18 01 JAN 2014
01 JAN 2014 Page 19 001223MAN-04
001223MAN-04 Page 20 01 JAN 2014
01 JAN 2014 Page 21 001223MAN-04
Ground Water System Information
GENERAL REQUIREMENTS
1. The temperature of the well water should be a minimum of 39°F (4°C), and should normally be 45+°F (7°C)
2. The well system must be able to supply the required water flow as listed under the Total Flow column in
TABLE 13
.
TABLE 13 - Required Flow and Air Tank Sizing
Heat
Pump
Model
Size
Heat
Pump
Flow*
IGPM
(USGPM)
Home
Flow
IGPM
(USGPM)
Total
Flow
IGPM
(USGPM)
Minimum Air
Bladder
Tank**
IGal
(USgal)
45
55
8 (9.6) 3 (3.6)
10 (12.0) 3 (3.6)
65 12 (14.4) 3 (3.6)
75 - 80 14 (16.8) 3 (3.6)
11(13.2)
13(15.6)
15(18.0)
17(20.4)
22(26)
26(31)
30(36)
34(41)
* These are minimum water requirements based on an entering water temperature of 46° F.
**Based on two-minute well pump run time. Use next size larger tank if there is not a match for the value indicated.
A larger tank may be used if a longer run time is desired.
PLUMBING THE HEAT PUMP
The port connections for the Outdoor Loop are 1” brass
FPT fittings. They are marked as OUTDOOR IN and OUT.
Plumbing lines, both supply and discharge, must be of adequate size to handle the water flow necessary for the heat pump. A 1” copper or plastic line should be run to the Outdoor
IN (Supply IN) pipe of the heat pump. Similarly, a 1”' line should be run from the Outdoor OUT (Supply Out) pipe to the method of disposal. P/T plugs should be installed at each port. See
Diagram A
in the Ground Loop section for a description of P/T plugs. The water valve should be installed in the discharge line.
Refer to drawing 000907CDG at the end of this section
for the recommended setup. Placing the water valve in the discharge line ensures that the heat exchanger inside the heat pump remains full of water when the unit is not running. Unions or some other form of disconnect should be used so that the coaxial heat exchanger may be accessed should it required cleaning.
The heat pump has an electrical connector for the water valve just inside the case. After the water valve is installed, run the valve harness into the case through the hole provided. Remove the jumper plug from the Valve Connector and connect the harness in its place.
Ideally there will be water flow available in excess of the requirement of the heat pump. In such a situation the proper pump can be selected to maintain a pressure of 30 to 40 psig. on the lines when the heat pump is operating. However in some cases a well can supply a heat pump only if the minimum requirement for water is used.
001223MAN-04
Water flow to the heat pump can be controlled very accurately by the installation of a reverse action refrigeration pressure valve in the discharge line of the unit.
Another more common method of regulating the flow is by the use of a DOLE Valve. This valve will automatically control the amount of water flowing through it by varying the diameter of a flexible rubber orifice through which the water passes. This minimizes the water usage of the unit and also prevents excessively low discharge pressure when in cooling mode. Dole valves can be noisy, it is recommended that they be installed outside if possible.
Optionally a water flow meter can be installed in the discharge line so that the exact amount of water flowing can be determined at a glance. It should be placed between the Outdoor OUT (Supply OUT) pipe of the heat pump and the water valve.
With Proper flow, there should be
5-7°F (3-4°C)
delta T between the IN and OUT water temperatures of the heat pump when operating in the heating mode.
All water line valves on both the supply and discharge lines should be either BALL or GATE valves. GLOBE valves have a higher pressure drop, meaning more pumping power to maintain the required flow to the heat pump.
PIPE INSULATION
All ground water piping to and from the Outdoor Loop ports on the heat pump should be insulated with 3/8” closed cell pipe insulation, to prevent condensation and dripping onto floors or walls.
WATER DISCHARGE METHODS
Water disposal methods vary from area to area. However, some consideration should be made to prevent the cooled discharge water from immediately coming in contact with the supply source. Attempting to return the water to the source well will eventually cool the water so much that the heat pump will shut off on its low pressure safety control.
Acceptable methods for disposing of the waste water are listed below. The waste water is clean, the heat pump has no effect other than reducing the temperature of the water.
Refer to the Ground Water Disposal methods diagram
for typical disposal method diagrams.
•
Second well (return well)
•
Percolation (Drain, ditch, leaching field)
•
Pond, river or stream.
ENSURE SELECTED METHOD CONFORMS TO LOCAL CODES.
Page 22 01 JAN 2014
A return well should be a minimum of 80 ft. from the supply well for residential applications. The water returned to the well will not necessarily be pumped into the same aquifer, depending on underground conditions. The return well must be able to supply at least the same quantity of water as the amount you wish to recharge into it. If the static level (level when not being pumped) of a well is high (10 to 20 ft. from the surface) it may be necessary to place a well cap on the well to keep the return water from flowing out the top of the well. This cap is commonly required since a certain amount of pressure is needed to force the return water back down the well if the static level is high.
Water discharged by percolation will generally soak into the ground within a distance of 50 to 100 ft. If suitable care is taken to ensure that the drain pipe runs downhill and the end of the pipe is protected by a bale of hay or spruce bows etc. the end of the pipe will not freeze as the pipe will empty out when the heat pump shuts off and the water valve closes.
When snow comes it will usually cover the entire process much like a small spring. It is recommended that the pipe be below the frost line when possible for maximum freeze protection.
When discharging into a river or stream, or above the surface of a pond, the same guidelines should be followed as described in the paragraph above for the percolation method.
When discharging the waste water below the surface of a pond, the discharge pipe should be placed below the frost line to prevent the pipe from freezing. As opposed to the percolation method, water will remain in the end of the pipe. It is recommended that the surface of the pond be lower than the installation location of the heat pump where practical. This reduces the back pressure generated by the weight of the water in the pond.
01 JAN 2014 Page 23 001223MAN-04
001223MAN-04 Page 24 01 JAN 2014
Ground Loop System Information
Once the ground loop has been pressure tested and the header pipes have been connected to the circulator pump module, the heat pump can be connected to the circulator pump module.
CIRCULATOR PUMP MODULE
Maritime Geothermal Ltd. has compact pump modules with built in three way valves to facilitate filling and purging the ground loop.
Refer to drawing 000906CDG at the end of this
section. Alternatively, Grundfoss® Model UPS 26-99 or Taco®
Model 0011 pumps or other brands with similar pumping capability may be used. The single pump module will typically handle systems up to 3 tons (model size 45); the two pump module will typically handle 4 to 6 ton systems (model sizes 55,
65, 75). This is based on a typical parallel system with one circuit per ton.
Maritime Geothermal recommends calculating the total pressure drop of the ground loop (including headers, indoor piping and heat pump exchanger drop) based on the antifreeze type and concentration at the desired minimum loop temperature. A pump module that can deliver the flow required for the unit at the calculated total pressure drop should be selected.
Refer to the Model Specific Information section
for unit flow requirements.
Loop pressure drops can be calculated using software such as those mentioned in the Horizontal Ground loops section, or can be calculated in a spreadsheet using the pipe manufacturer’s pressure drop tables for pipe diameter and fittings.
The circulator pump module must be connected to the heat pump Outdoor Loop ports with a lineset suitable for the flow required with minimum pressure drop. 1” rubber or plastic lines should be used. The installation of P/T plugs (pressure / temperature, pronounced “Pete’s plugs” ) is recommended on both the entering and leaving lines at the heat pump
(see
Diagram C).
DIAGRAM C - Typical P/T (Pete’s) Plug
& Thermometer Stems
The P/T plug will allow the installer or homeowner to check water flow through the loop by measuring the pressure difference through the heat exchanger and comparing it to that listed in the
Model Specific Information section
, or the specifications document . Optional fittings with P/T ports are available for the circulator pump modules sold by Maritime
Geothermal Ltd..
FLUSHING & PURGING THE GROUND
LOOP
Once the groundloop has been installed and all connections are completed between the heat pump, circulator pump module and ground loop, the entire ground loop system should be
pressure tested with air to 100 PSIG to make sure there are no leaks on any of the inside fittings. Soap all joints and observe that the pressure remains constant for 1 hour.
When satisfied that all connections are leak free, release the air pressure and connect a purge cart
(see Diagram D )
to the flushing access ports at the pump module
(refer to drawing
000906CDG).
A temporary flushing system can alternately be constructed using a 45 gal. barrel and a pump with sufficient volume and head capability to circulate fluid at a velocity of at
least 2 ft./min. through all parts of the loop.
DIAGRAM D - Typical Purge Cart
01 JAN 2014
Adjust the circulator pump module valves to connect the purge cart to the ground loop. Begin pumping water through the ground loop, ensuring that the intake of the pump stays submerged at all times by continuously adding water. Water flowing back from the return line should be directed below the water level in the barrel or flush tank to prevent air being mixed with the outgoing water.
Page 25 001223MAN-04
Once the lines have been filled and no more air bubbles are appearing in the line, adjust the circulator pump module valves to circulate water through the heat pump using the same technique as described above. When all air is removed reverse the flow of water through the lines by interchanging the flush cart lines and purge again. You will be able to visibly tell when all air is removed.
ADDING ANTIFREEZE SOLUTION
In most mid and northern areas of the US and in all of
Canada it is necessary to condition the loop fluid by the addition of some type of antifreeze solution so that it will not freeze during operation in the winter months. This antifreeze is required because the loop fluid will normally reach a low entering temperature of
28°F to 32°F (-2°C to 0°C)
and refrigerant temperatures inside the heat pump’s heat exchanger may be as low as
20°F (11°C)
cooler. See TABLE 14 for details of freeze protection provided by different concentrations.
TABLE 14 - Antifreeze Percentages
BY VOLUME
Protection to: 10°F 15°F 20°F 25°F
Methanol 25% 21% 16% 10%
Propylene Glycol 38% 30% 22% 15%
Protection to:
BY WEIGHT
10°F 15°F 20°F 25°F
Methanol 16.8% 13.6% 10% 6.3%
NOTE: Add enough antifreeze to allow for a temperature
20°F (11°C) lower than the expected lowest loop fluid temperature entering the heat pump.
Although many different antifreeze solutions have been employed in geothermal systems, the alcohols such as methanol or ethanol have the most desirable characteristics for groundloop applications. The overall heat transfer characteristics of these fluids remain high although care must be taken when handling pure alcohols since they are extremely flammable. Once mixed in a typical 25% by volume ratio with water the solution is not flammable. In situations where alcohols are not allowed as a loop fluid due to local regulations then propylene glycol is a non-toxic alternative which can be substituted . Propylene glycol should only be used in cases where alcohols are not permitted since the heat transfer characteristics are less desirable and it becomes more viscous at low temperatures, increasing pumping power.
The volume of fluid that your loop system holds can be closely estimated by totaling the number of ft. of each size pipe in the system and referencing
TABLE 15
the for approximate volume per 100 ft.
When the volume of the loop has been calculated and the appropriate amount of antifreeze is ready for addition by referencing
TABLE 14
, drain the equivalent amount of water from the flush cart or mixing barrel and replace it with the antifreeze.
When using alcohols, be sure to inject below the water
line to reduce initial volatility of the pure antifreeze. If the loop is large it may be necessary to refill the tank with antifreeze
001223MAN-04 Page 26 several times to get all the antifreeze into the loop. Pump the loop for 5 to 10 minutes longer to ensure the remaining fluid has been well mixed.
TABLE 15 - Volume of fluid per 100 ft. of pipe
Volume /100ft.
Type of Pipe Diameter Igal
USgal L
Rubber Hose
Polyethylene
1” 3.2
3/4” IPS SDR11
1” IPS SDR11
1-1/4” IPS SDR11 6.7
1-1/2” IPS SDR11 9.1
2” IPS SDR11
2.3
3.7
2.8
4.5
8.0
10.9
10.6
17.0
30.3
41.3
15.0 18.0 68.1
Heat Exchanger
Other Item Volumes
Average
Purge Cart Tank See cart manual
1.2
3.9 14.8
1.5
TBD
5.7
INITIAL PRESSURIZATION
At this point open all valves in the flow circuit and slowly close off the supply and return flush cart valves in a manner that leaves about 20-30 psig. on the system. If an air bladder expansion tank is used it should be charged to the above pressure before actual water pressure is put on the system .
Systems without an expansion tank will experience greater fluctuations in pressure between the heating and cooling seasons, causing pressure gauges to have different values as the loop temperature changes. This fluctuation is normal since expansion and contraction of the loop fluid must be handled by the elasticity of the plastic loop.
•
Pressurize the loop to a static pressure of 45 psig. when installing a system in the fall going into the heating season.
•
Pressurize the loop to a static pressure of 25 psig. when installing a system in the spring or summer going into the cooling season.
After operating the heat pump for a period of time, any residual air in the system should be bled off and the static pressure should be verified and adjusted if necessary. Add additional water / antifreeze mix with the purge cart to bring the pressure back to the original setting if required.
PIPE INSULATION
All ground loop piping inside the structure (between the structure entry point and the heat pump) should be insulated with 3/8” thick closed cell pipe insulation to prevent condensation and dripping onto floors or walls.
01 JAN 2014
01 JAN 2014 Page 27 001223MAN-04
Startup Procedure
The following steps describe how to perform the startup procedure of the geothermal heat pump.
The TF-Series Two-Stage R410a Air and Hydronic Startup Records located in this manual are used in conjunction with this startup procedure to provide a detailed record of the installation. A completed copy should be left on site, a copy kept on file by the installer and a copy should be sent to Maritime Geothermal Ltd.
Check the boxes or fill in the data as each step is completed. For data boxes, circle the appropriate units. Fill in the top section of all three copies, or one copy if photocopies can be made after the startup has been completed.
PRE-START INSPECTION
Ductwork:
1. Verify that all ductwork has been completed and is firmly attached to the unit. Verify that any dampers or diverters are
properly set for operation of the heat pump.
2. Verify that all registers are open and clear of any objects that would restrict the airflow.
3. Verify that a new air filter is installed and the cover is secured.
4. Verify the condensate drain is connected, properly vented and free of debris.
5. If a plenum heater has been installed, verify that it is securely fastened to the ductwork.
Indoor Loop (Hydronic Loop):
1. Verify that all shutoff valves are fully open and there are no restrictions in the piping from the heat pump to the indoor loop,
and that full flow is available to the heat pump.
2. Verify that the entire system has been flooded and all the air has been purged as much as possible. Further purging may
be required after the system has been operating for a while.
3. Verify that the loop contains the proper mix of antifreeze (if used) for the intended application. Record the type of antifreeze
and the mixture value on the startup sheet, circle % Vol. or % Weight.
4. Record the static loop pressure on the startup sheet.
Outdoor Loop (Ground Loop):
1. Verify that all shutoff valves are fully open and there are no restrictions in the piping from the heat pump to the ground loop,
and that full flow is available to the heat pump.
2. Verify that the entire system has been flooded and all the air has been purged as much as possible. Further purging may
be required after the system has been operating for a while.
3. Verify that the loop contains the proper mix of antifreeze for the intended application. Record the type of antifreeze and the
mixture value on the startup sheet; circle % Vol. or % Weight.
4. Record the static loop pressure on the startup sheet.
Outdoor Loop (Ground Water):
1. Verify there are no leaks in the connections to the unit. Verify the water valve is installed and properly oriented in the
return line.
2. Verify that there is flow control in the return line.
Domestic Hot Water (if equipped):
1. Verify that all shutoff valves are fully open and there are no restrictions in the piping from the heat pump to the domestic
hot water tank.
2. Verify that the entire system has been flooded and all the air has been purged as much as possible. Further purging may
be required after the system has been operating for a while.
3. Verify that the brown wire with the insulated terminal is disconnected in the electrical box. Refer to the schematic diagram
for more information.
Electrical:
1. Ensure the power to the unit is off. Ensure the power to the plenum heater is off if equipped.
2. Verify all high voltage connections. Ensure that there are no stray wire strands, all connections are tight and the ground
wire is connected tightly to the ground connector for the heat pump and plenum heater.
3. Record the fuse / circuit breaker size and wire gauge for the heat pump. Record the fuse / circuit breaker size, wire gauge
and size of the plenum heater if installed.
4. Verify that the control connections to the thermostat and plenum heater (if installed) are properly connected and all control
signals are off, so that the unit will not start up when the power is turned on.
5. Ensure all access panels except the lower one that provides access to the electrical box are in place.
001223MAN-04 Page 28 01 JAN 2014
UNIT STARTUP (AIR)
The unit is now ready to be started. The steps below outline the procedure for starting the unit and verifying proper operation of the unit. It is recommended that safety glasses be worn during the following procedures.
Preparation:
1. Remove the caps from the service ports and connect a refrigeration manifold set to the unit.
2. Turn the power on to the heat pump and set the thermostat to OFF. Set up the thermostat as per the instructions provided
with it so that it will function properly with the heat pump system (set for heat pump, not for heating and cooling). The O
signal should be set to active in cooling mode.
3. Measure the following voltages on the compressor contactor and record them on the startup sheet: L1-L2, L2-L3, L1-L3.
Air Heating Mode:
1. Set the aquastat so that both Stage 1 and Stage 1 are off.
2. Set the thermostat to heating mode and adjust the setpoint to activate Stage 1 and Stage 2. The fan should slowly ramp up
to speed after the time delay of the thermostat expires (if applicable) and the compressor will start (allow 30-60 seconds for
the water valve to open for ground water systems)
3. Check the refrigeration gauges. The suction and discharge pressures will depend on the loop temperatures, but they should
be about
90-110PSIG
and
260-360PSIG
respectively for a typical start-up.
4. Monitoring the refrigeration gauges while the unit runs. Record the following after 10 minutes of runtime:
1. Suction pressure
2. Discharge pressure
3. Duct Return temperature (poke a small hole in the flex collar and insert probe in airstream)
4. Duct Supply temperature (poke a small hole in the flex collar and insert probe in airstream)
5. Duct Delta T (should be between
22-32°F, 12-18°C
)
6. Outdoor Loop In (Supply In) temperature
7. Outdoor Loop Out (Supply Out) temperature
8. Outdoor Delta T (should be between
5-8°F, 3-4°C
)
9. Outdoor flow (if available)
10. Compressor L1(C) current (black wire, place meter between electrical box and compressor)
5. Adjust the thermostat setpoint to the desired room temperature and let the unit run through a cycle. Record the setpoint,
suction, discharge pressures when the unit shuts off.
6. For units with a desuperheater, turn the power off to the unit. Connect the brown wire with the blue insulated terminal to the
compressor contactor as shown in the electrical box diagram. Turn the DHW Switch in the unit post on. Turn the power to the
unit on.
7. Remove the electrical cover from the plenum heater. Place a current clamp meter around one of the supply wires. Turn on
the power to the plenum heater. Adjust the thermostat setpoint to
85°F (29°C)
. Verify that the current draw increase as
each stage is activated. (10kW has 2 stages, 15kW has 3 stages and 20kW has 4 stages).
8. Verify the DHW IN and DHW OUT temperatures (if applicable) by hand
(caution: pipes get hot).
If the DHW OUT line does
not become hotter than the DHW IN line the circulator is air locked. Bleed the air from the system and check the
temperature differential again to ensure there is flow from the circulator.
Cooling Mode:
1. Set the thermostat to cooling mode and adjust the setpoint to activate Stage 1 and Stage 2.
2. Monitoring the refrigeration gauges while the unit runs. Record the following after 10 minutes of runtime:
1. Suction pressure
2. Discharge pressure
3. Duct Return temperature
4. Duct Supply Out temperature
5. Duct Delta T
6. Outdoor Loop In (Supply In) temperature
7. Outdoor Loop Out (Supply Out) temperature
8. Outdoor Delta T
3. Adjust the thermostat setpoint to the desired room temperature if possible, otherwise set it just low enough to allow the unit
to run (ie 1°F (0.5°C) less than room temperature) and let the unit run through a cycle. Record the thermostat setpoint, suction,
And discharge pressures when the unit shuts off.
Final Inspection: (If the Hydronic Startup is to be performed as well, do the Final Inspection after is has been completed. )
1. Turn the power off to the unit (and plenum heater if installed) and remove all test equipment.
2. Install the electrical box cover and the access panel on the heat pump. Install the service port caps securely to prevent
refrigerant loss. Install the electrical cover on the plenum heater if applicable.
3. Do a final check for leaks in the ground water / ground loop system and ensure the area is clean.
4. Turn the power on to the unit and the plenum heater if installed. Set the thermostat to the final settings.
Startup Record:
1. The installer shall sign and date the Startup Record and have the homeowner sign as well. The installer shall leave the Startup
Record with the homeowner, retain a copy for filing and send a copy to Maritime Geothermal Ltd. for warranty registration.
01 JAN 2014 Page 29 001223MAN-04
Installation Site
Startup Record (Air) —TF-Series Size 25-75 Two-Stage R410a
Startup Date Installer
City
Province
Country
Company
Check boxes unless asked to record data. Circle units.
Model
Serial #
Homeowner Name
Ductwork
Homeowner Phone #
PRE-START INSPECTION
Ductwork is completed, dampers/ diverters are adjusted
Registers are open and clear of objects
Air filter and end cap are installed
Condensate Drain is connected, properly vented and free of debris
Ground Loop
System
Ground Water
System
Domestic Hot
Water
Electrical
Plenum heater is securely fastened (if applicable)
All shut-off valve are open (full flow available)
Loop is full and purged of air
Antifreeze type
Antifreeze concentration
Loop static pressure
Water Valve installed in return line
Flow control installed in return line
All shut-off valves are open
Lines are full and purged
Desuperheater pump wire is disconnected
High voltage connections are correct and securely fastened
Circuit breaker (or fuse) size and wire gauge for Heat Pump
Circuit breaker (or fuse) size, wire gauge, and Plenum Heater size
Low voltage connections are correct and securely fastened
Preparation
STARTUP DATA
Voltage across L1 and L2, L1 and L3, L2 and L3
Heating Mode
(10 minutes)
Cooling Mode
(10 minutes)
Suction Pressure / Discharge Pressure
Duct Return, Duct Supply, and Delta T
Outdoor In (Supply In), Outdoor Out (Supply Out), and Delta T
Outdoor Flow
Compressor L1 (black wire) current
Domestic Hot Water functioning
Thermostat setpoint and discharge pressure at cycle end
Suction Pressure / Discharge Pressure
Duct Return, Indoor Out, and Delta T
Outdoor In (Supply In), Outdoor Out (Supply Out), and Delta T
Thermostat setpoint and suction pressure at cycle end
A
A
Igpm USgpm L/s
A
°F °C
In
In
In
In
% Volume % Weight
PSI kPa
Ga.
Ga. kW
VAC
Out psig kPa
°F °C
Out °F °C
°F °C psig kPa
Out psig kPa
°F °C
Out °F °C psig kPa
Date:
Installer Signature:
Homeowner Signature:
A total of three copies are required, one for the homeowner, one for the installer and on to be sent to Maritime Geothermal Ltd.
001223MAN-04 Page 30 01 JAN 2014
UNIT STARTUP (HYDRONIC)
The unit is now ready to be started. The steps below outline the procedure for starting the unit and verifying proper operation of the unit controlled by an aquastat. It is recommended that safety glasses be worn during the following procedures.
Preparation:
1. Remove the caps from the service ports and connect a refrigeration manifold set to the unit.
2. Turn the power on to the heat pump and set all controls (including all zone thermostats) to OFF.
3. Measure the following voltages on the compressor contactor and record them on the startup sheet: L1-L2, L2-L3, L1-L3.
Heating Mode:
1. Set the heating aquastat setpoints to activate Stage 1 and Stage 2. The compressor will start (allow 30-60 seconds for the
water valve to open for ground water systems) as well as the circulator pumps.
2. Check the refrigeration gauges. The suction and discharge pressures will depend on the loop temperatures, but they should
be about
90-110PSIG
and
260-360PSIG
respectively for a typical start-up.
3. Monitoring the refrigeration gauges while the unit runs. Record the following after 10 minutes of runtime:
1. Suction pressure
2. Discharge pressure
3. Indoor Loop In (Hot In) temperature
4. Indoor Loop Out (Hot Out) temperature
5. Indoor Delta T (should be between
8-12°F, 4-6°C
)
6. Outdoor Loop In (Supply In) temperature
7. Outdoor Loop Out (Supply Out) temperature
8. Outdoor Delta T (should be between
5-8°F, 3-4°C
)
9. Outdoor flow (if available)
10. Compressor L1(C) current (black wire, place meter between electrical box and compressor)
4. Adjust the aquastat setpoint to the desired buffer tank temperature and let the unit run through a cycle. Record the setpoint,
suction, and discharge pressures when the unit shuts off.
5. Proceed to Final Inspection if the desuperheater (if applicable) has already been tested during the Air Startup.
6. Open a zone (or zones) and let the tank cool down until Stage 2. is activated. Close the zone(s) again.
7. Turn the power off to the unit. Connect the brown wire with the blue insulated terminal to the compressor contactor as shown in
the electrical box diagram. Turn the DHW Switch in the unit post on. Turn the power to the unit on.
8. Verify the DHW IN and DHW OUT temperatures (if applicable) by hand
(caution: pipes get hot).
If the DHW OUT line does
not become hotter than the DHW IN line the circulator is air locked. Bleed the air from the system and check the
temperature differential again to ensure there is flow from the circulator.
Final Inspection:
1. Turn the power off to the unit and remove all test equipment.
2. Install the electrical box cover and the access panel on the heat pump. Install the service port caps securely to prevent
refrigerant loss.
3. Do a final check for leaks in the ground water / ground loop system and ensure the area is clean.
4. Turn the power on to the unit. Set the aquastat to the final settings and record the values.
Startup Record:
1. The installer shall sign and date the Startup Record and have the homeowner sign as well. The installer shall leave the Startup
Record with the homeowner, retain a copy for filing and send a copy to Maritime Geothermal Ltd. for warranty registration.
01 JAN 2014 Page 31 001223MAN-04
Startup Record Sheet (Hydronic)—TF-Series Size 25-75 Two-Stage R410a
Installation Site Startup Date Installer
City Company
Province
Country
Model
Serial #
Indoor Loop
(Hydronic)
Check boxes unless asked to record data, circle units
PRE-START INSPECTION
All shut-off valve are open (full flow available)
Loop is full and purged of air
Antifreeze type
Antifreeze concentration % Volume % Weight
Ground Loop
System
Loop static pressure
All shut-off valve are open (full flow available)
Loop is full and purged of air
Antifreeze type
Antifreeze concentration
PSI kPa
% Volume % Weight
Ground Water
System
Domestic Hot
Water
Electrical
Loop static pressure
Water Valve installed in return line
Flow control installed in return line
All shut-off valves are open
Lines are full and purged
Desuperheater pump wire is disconnected
High voltage connections are correct and securely fastened
Circuit breaker (or fuse) size and wire gauge for Heat Pump
Circulator pump voltages (Outdoor 1, Outdoor 2, Indoor 1)
Low voltage connections are correct and securely fastened
PSI kPa
A
V
Ga.
V
V
Preparation
STARTUP DATA
Voltage across L1 and L2, L1 and L3, L2 and L3
Heating Mode
(10 minutes)
Final Settings
Suction Pressure / Discharge Pressure
Indoor In (Hot In), Indoor Out (Hot Out), and Delta T
Outdoor In (Supply In), Outdoor Out (Supply Out), and Delta T
Outdoor Flow
Compressor L1 (black wire) current
Domestic Hot Water functioning
Aquastat setpoint and discharge pressure at cycle end
S1 Setpoint, S1 Delta, S2 Setpoint, S2 Delta
In
In Out
Igpm USgpm L/s
°F °C
A
°F °C psig kPa
°F °C
VAC
Out psig kPa
°F °C
Date:
Installer Signature:
Homeowner Signature:
A total of three copies are required, one for the homeowner, one for the installer and on to be sent to Maritime Geothermal Ltd.
001223MAN-04 Page 32 01 JAN 2014
General Maintenance
Air Filter
Item Interval
6 months
GENERAL MAINTENANCE SCHEDULE
Procedure
Inspect for dirt. Replace if necessary.
Contactor
Condensate Drain
1 year
1 year
Inspect for pitted or burned points. Replace if necessary.
Inspect for clogs. Remove and clean if necessary.
Heat exchanger
As required* Clean as per HEAT EXHCANGER FLUSING PROCEDURE below.
*Generally not required for closed loop systems. Whenever system performance is reduced for open loop.
COAXIAL HEAT EXCHANGER FLUSHING PROCEDURE—GROUNDWATER
STEP 1
Isolate the heat exchanger by closing the valves in the IN and OUT ports to the heat exchanger.
STEP 2
Blow out the heat exchanger into a clean 5 gallon bucket using compressed air.
STEP 3
If a purge cart is not available, use a 5 gallon plastic bucket, a circulator and some plastic piping to create a makeshift pump system. Connect a the inlet and outlet to the heat exchanger ports.*
STEP 4
Place 2 gallons of RYDLYME in the purge cart (or bucket). Circulate the fluid through the heat exchanger for at least 2 hours (3 recommended).
STEP 5
Disconnect the purge system dispose of the solution. RYDLYME is non-toxic and biodegradable and as such can be poured down a drain.
STEP 6
Connect fresh water and a drain to the heat exchanger ports and flush the exchanger for several minutes.
STEP 7
Return the plumbing to its original configuration and open the IN and OUT valves. Operate the system and check for improved performance.
*Depending on the plumbing, there should be either unions or boiler drains for to access the heat exchanger.
COAXIAL HEAT EXCHANGER FLUSHING PROCEDURE—GROUND LOOP
STEP 1
Isolate the heat exchanger by placing the pump module valves in the exchanger flushing position.
STEP 2
Connect a compressed air and a drain pipe to the pump module purge ports and blow the anti-freeze solution into a clean 5 gallon bucket.
STEP 3
Connect a purge cart to the pump module purge ports.
STEP 4
Place 2 gallons of RYDLYME in the purge cart. Circulate the fluid through the heat exchanger for at least 2 hours (3 recommended).
STEP 5
Disconnect the purge cart and dispose of the solution. RYDLYME is non-toxic and biodegradable and as such can be poured down a drain. Clean the purge cart thoroughly.
STEP 6
Connect fresh water and a drain to the pump module purge ports and flush the exchanger for several minutes.
STEP 7
Blow the heat exchanger out with compressed air as per STEP 2 and dump the water down a drain.
STEP 8
Connect the purge cart to the pump module purge ports. Re-fill and purge the heat exchanger with as per standard procedures (the anti-freeze from STEP 2 can be re-used).
STEP 9
Disconnect the purge cart and set the pump module valves back to the original positions.
STEP 10
Operate the system and check for improved performance.
*Depending on the plumbing, there should be either unions or boiler drains for to access the heat exchanger.
01 JAN 2014 Page 33 001223MAN-04
Troubleshooting Guide
The following steps are for troubleshooting the geothermal heat pump. If the problem is with the domestic hot water or the plenum heater, proceed to those sections at the end of the troubleshooting guide. Repair procedures and reference refrigeration circuit diagrams can be found at the end of the troubleshooting guide.
STEP 1: Verify that the display is present on the thermostat. If it is not, proceed to POWER SUPPLY TROUBLESHOOTING,
otherwise proceed to STEP 2.
STEP 2: Remove the door and electrical box cover and check to see if there is a fault code on the control board. If there is, record
the fault code. Turn the power off, wait 10 seconds and turn the power back on. Set the thermostat to call for heating or
cooling depending on the season, or set the aquastat to call for heating.
STEP 3 (Air): If a 24VAC signal does not appear across Y1 and C of the terminal strip within 6 minutes, proceed to the
THERMOSTAT TROUBLESHOOTING section, otherwise proceed to STEP 4.
STEP 3 (Hydronic): If a 24VAC signal does not appear across Y1A and CA of the terminal strip, proceed to the HYDRONIC
TROUBLESHOOTING - AQUASTAT section, otherwise proceed to STEP 4.
STEP 4: If a fault code appears once a signal is present at Y1 and the compressor does not attempt to start, proceed to the
FAULT CODE TROUBLESHOOTING section, otherwise proceed to STEP 5.
STEP 5: If The compressor does not attempt to start, attempts to start but cannot, starts hard, or starts but does not sound normal,
proceed to the COMPRESSOR TROUBLESHOOTING section, otherwise proceed to STEP 6.
STEP 6: If the compressor starts and sounds normal, this means the compressor is OK and the problem lies elsewhere. Proceed to
the AIR OPERATION TROUBLESHOOTING section or the HYDRONIC OPERATION TROUBLESHOOTING section.
NOTE: To speed up the troubleshooting process, the Test Jumper on the safety board can be placed to the YES position to change
the anti-short cycle timer to 5 seconds. Be sure to set it back to NO when servicing is complete.
POWER SUPPLY TROUBLESHOOTING
Fault
No power to the heat pump
Possible Cause
Disconnect switch open
(if installed)
Fuse blown /
Breaker Tripped.
Verification Recommended Action
Verify disconnect switch is in the
ON position.
Determine why the disconnect switch was opened, if all is OK close the switch.
At heat pump disconnect box, voltmeter shows 230VAC on the line side but not on the load side.
Reset breaker or replace fuse with proper size and type. (Timedelay type “D”)
No display on thermostat.
Transformer breaker tripped.
Faulty transformer
Faulty wiring between heat pump and thermostat.
Faulty Thermostat.
Breaker on transformer is sticking out.
Push breaker back in. If it trips again locate cause of short circuit and correct.
Transformer breaker is not tripped, 230VAC is present across L1 and L3 of the compressor contactor but 24VAC is not present across R
H
and C of the terminal strip.
Replace transformer.
24VAC is not present across C and R(R
H
) of the thermostat.
Correct the wiring.
001223MAN-04
24VAC is present across C and R
(R
H
) of the thermostat but thermostat has no display.
Replace thermostat.
Page 34 01 JAN 2014
THERMOSTAT TROUBLESHOOTING
Fault
No Y1 signal to heat pump
(after 6 minutes)
Possible Cause
Incorrect thermostat setup.
Faulty thermostat to heat pump wiring.
Faulty thermostat.
Verification Recommended Action
Thermostat does not indicate a call for heat. No 24VAC signal present across C and Stage 1 of the thermostat
Correct the setup.
24VAC signal present across Stage
1 and C of the thermostat but not present across Y1 and C of the terminal strip.
Correct or replace wiring
No 24VAC between Stage 1 and C of the thermostat when a call is indicated on the thermostat.
Replace thermostat.
Fault
Fault Code 1
(High Pressure
Control)
Fault Code 2
(Low Pressure
Control)
Fault Code 3
(Flow Switch)
FAULT CODE TROUBLESHOOTING
Possible Cause Verification Recommended Action
Faulty High Pressure Control (open).
* Must be a signal present on Y1 for this test.
*HP pressures must be at static levels.
Verify if there is 24VAC across HP1 on the control board and C of the terminal strip, as well as HP2 and C.
Replace high pressure control if voltage is present on HP1 but not on HP2.
Faulty control board.
24VAC is present across HP1 and
C1, and HP2 and C, but no voltage is present across CC on the control board and C.
Replace control board
.
Faulty Low pressure control (open).
* Must be a signal present on Y1 for this test.
*HP pressures must be at static levels.
Verify if there is 24VAC across LP1 on the control board and C of the terminal strip, as well as LP2 and C.
Faulty control board.
Unit out of refrigerant.
Replace high pressure control if voltage is present on LP1 but not on LP1.
24VAC is present across LP1 and C, and LP2 and C, but no voltage is present across CC on the control board
and C.
Replace control board
.
Check static refrigeration pressure of the unit for a very low value.
Locate the leak and repair it.
Spray nine, a sniffer and dye are common methods of locating a leak.
Flow switch jumper removed or faulty.
Flow switch faulty.
(Only if installed)
Verify jumper is in place between pins marked FLOW SWITCH.
Place a jumper if missing.
Faulty control board.
Verify 24VAC is present between each flow switch pin on the control board and the C terminal of the terminal strip while there is flow through the unit.
Replace flow switch if signal is not present at both terminals on the control board
.
24VAC is present across each
FLOW SWITCH terminal and C, but not voltage is present across CC on the control board and C.
Replace control board
.
01 JAN 2014 Page 35 001223MAN-04
COMPRESSOR TROUBLESHOOTING
Fault
Compressor will
not start
Possible Cause
Faulty control board
.
Faulty run capacitor.
(Single phase only)
Loose or faulty wiring.
Faulty compressor contactor.
Thermal overload on compressor tripped.
Burned out motor
(open winding)
Burned out motor
(shorted windings)
Verification Recommended Action
Measuring from C on the terminal strip, verify there is voltage at Y,
HP1, HP2, LP1, LP2, and both flow pins but no voltage present at CC.
Replace control board
Check value with capacitance meter. Replace if faulty.
Should match label on capacitor.
Compressor will hum while trying to start and then trip its overload.
.
Check all compressor wiring, including inside compressor electrical box.
Fix any loose connections. Replace any damaged wires.
Voltage on line side with contactor held closed, but no voltage on one or both terminals on the load side.
Points pitted or burned.
Or, 24VAC across coil but contactor will not engage.
Replace contactor.
Ohmmeter shows reading when placed across R and S terminals
Proceed to Operation Troubleshooting to determine the cause and infinity between C & R or C & S.
A valid resistance reading is present of the thermal overload trip. again after the compressor has cooled down.
Remove wires from compressor.
Ohmmeter shows infinite resistance between any two terminals Note: Be sure compressor overload has had a chance to reset. If compressor is hot this may take several hours.
Replace the compressor.
Remove wires from compressor.
Resistance between any two terminals is below the specified value.
Replace the compressor.
Compressor starts hard
Compressor
Stage 2 will not activate
001223MAN-04
Motor shorted to ground. Remove wires from compressor.
Check for infinite resistance between each terminal and ground.
If any terminal to ground is not infinite replace the compressor.
Seized compressor due to locked or damaged mechanism.
Compressor attempts to start but trips its internal overload after a few seconds. (Run capacitor already verified)
Attempt to “rock” compressor free.
If normal operation cannot be established, replace compressor.
Start capacitor faulty.
(Single phase only)
Check with capacitance meter.
Check for black residue around blowout hole on top of capacitor.
Replace if faulty.
Remove black residue in electrical box if any.
Potential Relay faulty.
(Single phase only)
Replace if faulty.
Compressor is “tight” due to damaged mechanism
Compressor attempts to start but trips its internal overload after a few seconds. Run capacitor has been verified already.
Attempt to “rock” compressor free.
If normal operation cannot be established, replace compressor.
Faulty Stage 2 module
Replace with new one and verify compressor starts properly.
Verify if 24VAC is present across
Y2 and C of the terminal strip.
Replace module if signal is present. Check wiring if signal is not present.
Page 36 01 JAN 2014
Fault
High Discharge
Pressure
AIR OPERATION TROUBLESHOOTING - HEATING MODE
Possible Cause Verification Recommended Action
Air Flow
TXV adjusted too far closed.
TXV stuck almost closed or partially blocked by foreign object.
See Fan Troubleshooting section Correct the problem.
Verify superheat. It should be between 8-12°F (3-6°C). Superheat will be high if TXV is closed too far.
Adjust TXV to obtain 8-12°F
(3-6°C) superheat.
Adjusting the TXV does not affect the superheat or the suction pressure.
Adjust the TXV all the way in and out a few times to loosen it. Replace
TXV if this does not work.
Filter-drier plugged
Unit is overcharged.
(Only possible if unit has been opened in the field and incorrectly charged)
Feel each end of the filter- drier, it should be the same temperature.
If there is a temperature difference then it is plugged. Also causes low suction pressure.
Replace filter-drier.
High sub-cooling, low delta T across air coil.
Remove 1/2lb of refrigerant at a time and verify that the discharge pressure reduces.
Low Suction
Pressure
01 JAN 2014
Low or no Outdoor liquid flow
Delta T across the Outdoor Loop ports should be between 5-7°F
(3-4°C), or compare pressure drop to the tables for the unit.
Determine the cause of the flow restriction and correct it.
Verify pumps are working and sized correctly for ground loop systems.
Verify well pump and water valve is working for ground water systems.
Increase the size of the ground loop. Entering liquid temperature too cold.
Dirty or fouled coaxial heat exchanger.
(typically for ground water, unlikely for ground loop)
Disconnect the water lines and check the inside of the pipes for scale deposits.
Return air too cold
TXV stuck almost closed or partially blocked by foreign object.
Measure the entering liquid temperature. Most likely caused by undersized ground loop.
Measure return air temperature.
Should be above 60°F (15°C).
Have a qualified service technician backflush the coaxial exchanger.
Restrict air flow temporarily until room comes up to temperature.
Adjusting the TXV does not affect the superheat or the suction pressure. TXV may be frosting up.
Adjust the TXV all the way in and out a few times to loosen it. Replace
TXV if this does not work.
Leaking check valve.
(Located in the receiver liquid line out).
Valve will be cold. Remove the cap from the roto-lock fitting on the receiver and close the rotolock valve. Unit should function normally, there may be a sound change as the roto-lock is closed.
Try tapping the valve and switching from air heat to water heat a few times. Replace the check valve if the problem persists.
Low refrigerant charge. Entering liquid temperature, flow and entering air temperature are good but suction is low. Check static refrigeration pressure of the unit for a very low value.
Locate the leak and repair it. Spray nine, a sniffer and dye are common methods of locating a leak.
Faulty compressor, not pumping.
Pressures change only slightly from static values when compressor is started.
Replace compressor.
Page 37 001223MAN-04
Fault
AIR OPERATION TROUBLESHOOTING - HEATING MODE
Possible Cause Verification Recommended Action
High Suction
Pressure
(may appear to not be pumping)
TXV adjusted too far open.
TXV stuck open.
Verify superheat. It should be between 8-12°F (3-6°C). Superheat will be low if TXV is open too far.
Adjust TXV to obtain 8-12°F
(3-6°C) superheat.
Leaking reversing valve#1.
Leaking reversing valve#2.
Adjusting the TXV does not affect the superheat or the suction pressure. Low super heat and discharge pressure.
Adjust the TXV all the way in and out a few times to loosen it. Replace
TXV if this does not work.
Reversing valve has uniform temperature, common suction line is warm, compressor is running hot.
Replace reversing valve.
Reversing valve has uniform temperature, common suction line is warm, compressor is running hot. Does not work in air heat or water heat but does work in air cool.
Replace reversing valve.
Compressor frosting up
TXV frosting up
Random high pressure trip
(does not occur while on site)
See Low Suction
Pressure in this section.
TXV stuck almost closed or partially blocked by foreign object.
Adjusting the TXV does not affect the superheat or the suction pressure.
Attempt to adjust the TXV all the way out and all the way in a few times to loosen it. Replace TXV if this does not work.
Faulty compressor contactor.
Points pitted or burned. Contactor sometimes sticks causing the compressor to run without the fan, tripping the high pressure control.
Intermittent fan.
Replace contactor.
See Fan Troubleshooting section. Correct the problem.
Fault
Heating instead of cooling
AIR OPERATION TROUBLESHOOTING - COOLING MODE
Possible Cause Verification Recommended Action
Thermostat not set up properly.
Faulty reversing valve#1 solenoid coil.
Verify that there is 24VAC across
O/B/W1 and C of the terminal strip when calling for cooling.
Verify solenoid by removing it from the shaft while the unit is running.
There should be a loud “whoosh” sound when it is removed.
Correct thermostat setup.
Change to a different thermostat.
Replace solenoid if faulty.
High Discharge pressure
Faulty reversing valve#1. A click can be heard when the coil is energized but the unit continues to heat instead of cool.
Replace reversing valve.
Low or no Outdoor liquid flow
Entering liquid temperature too warm.
Delta T across the Outdoor Loop ports should be between 8-12F
(4-7C), or compare pressure drop to the tables for the unit.
Most likely caused by undersized ground loop.
Determine the cause of the flow restriction and correct it.
Verify pumps are working for ground loop systems. Verify well pump and water valve is working for ground water systems.
Verify the ground loop sizing. Increase the size of the ground loop if undersized.
001223MAN-04 Page 38 01 JAN 2014
Fault
High Discharge pressure
(continued)
AIR OPERATION TROUBLESHOOTING - COOLING MODE
Possible Cause Verification Recommended Action
Dirty or fouled coaxial heat exchanger.
(typically for ground water, unlikely for ground loop)
Unit is overcharged.
(Only possible if unit has been opened in the field and incorrectly charged)
Disconnect the water lines and check the inside of the pipes for scale deposits.
High sub-cooling, low delta T across water coil.
Have a qualified service technician backflush the coaxial exchanger.
Remove 1/2lb of refrigerant at a time and verify that the discharge pressure reduces.
High Suction
Pressure
(may appear to not be pumping)
TXV adjusted too far open. Verify superheat. It should be between 8-12°F (3-6°C). Superheat will be low if TXV is open too far.
Adjust TXV to obtain 8-12°F
(3-6°C) superheat.
TXV stuck open. Adjusting the TXV does not affect the superheat or the suction pressure. Low super heat and discharge pressure.
Adjust the TXV all the way in and out a few times to loosen it. Replace TXV if this does not work.
Replace reversing valve#1. Leaking reversing valve#1. Reversing valve is the same temperature on both ends of body, common suction line is warm, compressor is running hot.
Low Suction
Pressure
Air Flow
TXV stuck almost closed or partially blocked by foreign object.
Leaking check valve.
(Located in the receiver liquid line out).
Adjusting the TXV does not affect the superheat or the suction pressure. TXV may be frosting up.
Valve will be cold. Remove the cap from the roto-lock fitting on the receiver and close the rotolock valve. Unit should function normally, there may be a sound change as the roto-lock is closed.
Adjust the TXV all the way in and out a few times to loosen it. Replace TXV if this does not work.
Try tapping the valve and switching from air cool to water heat a few times. Replace the check valve if the problem persists.
Low or no refrigerant charge.
See Fan Troubleshooting section.
Note: low airflow will cause the air coil to ice up once the suction drops below
90PSIG
.
Correct the problem.
Faulty compressor, not pumping.
Entering air temperature and airflow are good but suction is low.
Check static refrigeration pressure of unit for very low value.
Locate the leak and repair it.
Spray nine, a sniffer and dye are common methods of locating a leak.
Pressures change only slightly from static values when compressor is started.
Replace compressor.
Compressor frosting up
See Low Suction
Pressure in this section.
TXV frosting up
TXV stuck almost closed or partially blocked by foreign object.
Adjusting the TXV does not affect the superheat or the suction pressure.
Adjust the TXV all the way in and out a few times to loosen it. Replace TXV if this does not work.
Random Low
Pressure trip
(does not occur while there)
01 JAN 2014
Faulty compressor contactor.
Intermittent fan.
Points pitted or burned. Contactor sometimes sticks causing the compressor to run without the fan, tripping the low pressure control.
Replace contactor.
See Fan Troubleshooting section. Correct the problem.
Page 39 001223MAN-04
Fault
Low Airflow
Possible Cause
Dirty air filter
Dirty air coil.
Poor Ductwork
FAN TROUBLESHOOTING
Inspect.
Verification
Inspect.
Measure delta T between supply and return ducts at the unit, it in heating mode, it should not be above 30°F(17°C).
Recommended Action
Replace.
Clean.
The ECM fan will provide proper airflow up to 0.5 inH2o for 1/2HP motors and 0.7 inH2o for 1HP motors. The ductwork is poorly designed or greatly undersized if the fan motor cannot provide the required airflow.
Select a higher setting. Air flow selected on Tap
Board is too low.
Check selection on Air Flow Tap
Board.
Fan operating on wrong Stage speed
Air flow reduction is enabled.
Fan Control Signal Harness is loose.
AR1 and AR2 are connected with a dry contact.
Air flow reduction may not be feasible with poor ductwork, and/or lower Air Flow selections. Increase settings until unit operates properly.
Verify that the connector is properly inserted into the fan motor. Gently tug on each wire to verify it is properly inserted into the connector.
Repair any loose connections.
Faulty Control Signal Harness or faulty motor head.
Ensure signal is present on terminal strip.
Measure 24VAC between White (pin
3) and the following at the fan control signal harness (insert probes in connector where wire is inserted, do not unplug the connector):
Circulation = Grey (pin 15)
Stage 1 = Yellow (pin 6)
Stage 2=Yellow/Black (pin14)
Stage 3 = Violet (pin 2)
If proper signal isn’t present, replace Fan Control Signal Harness. If proper signal is present, replace fan motor head.
Fan not operating or operating intermittently
Fan Control Signal Harness and/or Fan Power
Harness is loose.
Verify that the connector is properly inserted into the fan motor. Gently tug on each wire to verify it is properly inserted into the connector.
Repair any loose connections.
001223MAN-04
Faulty Control Signal Harness or faulty motor head.
Ensure signal is present on terminal strip.
Measure 24VAC between White (pin
3) and the following at the fan control signal harness (insert probes in connector where wire is inserted, do not unplug the connector):
Circulation = Grey (pin 15)
Stage 1 = Yellow (pin 6)
Stage 2=Yellow/Black (pin14)
Stage 3 = Violet (pin 2)
If proper signal isn’t present, replace Fan Control Signal Harness. If proper signal is present, replace fan motor head.
Faulty Fan Power Harness or faulty motor.
Insert the tips of the voltmeter probes into the back of the connector at the fan to measure the voltage across the red and black wires, value should be 230VAC
Replace Power Harness if
230VAC is not present, replace motor if 230VAC is present
Page 40 01 JAN 2014
Fault
No display on aquastat.
HYDRONIC TROUBLE SHOOTING - AQUASTAT
Possible Cause
Transformer breaker tripped.
Verification
Breaker on transformer is sticking out.
Recommended Action
Push breaker back in. If it trips again locate cause of short circuit and correct.
Faulty transformer Transformer breaker is not tripped,
230VAC is present across L1 and L3 of the compressor contactor but
24VAC is not present across R and
C.
Replace transformer.
Faulty wiring between heat pump and aquastats.
24VAC is not present across 24V and COM at the top of the aquastat.
Correct the wiring.
No Y1A signal to heat pump
Faulty aquastat.
Incorrect aquastat setup.
24VAC is present across 24Vand
COM of the aquastat but there is no display.
Replace aquastat.
Aquastat does not indicate S1 on the display.
Correct the setup.
Faulty aquastat to heat pump wiring.
24VAC not present across Stage 1 C Correct or replace wiring. and COM of the aquastat.
Faulty aquastat to heat pump wiring.
24VAC signal present across Stage
1 NO and COM of the aquastat but not present across Y1A and CA of the terminal strip.
Correct or replace wiring.
Faulty aquastat. No 24VAC between Stage 1 NO and COM of the aquastat when S1 is indicated on the aquastat display.
Replace aquastat.
No Y2A signal to heat pump
Incorrect aquastat setup. Aquastat does not indicate S2 on the display.
Faulty aquastat to heat pump wiring.
24VAC not present across Stage 2
C and COM of the aquastat.
Correct the setup.
Correct or replace wiring.
Setting(s) not retained
Faulty aquastat to heat pump wiring.
Faulty aquastat.
Faulty aquastat
24VAC signal present across Stage
2 NO and COM of the aquastat but not present across Y2A and CA of the terminal strip.
Correct or replace wiring.
No 24VAC between Stage 2 NO and COM of the aquastat when S2 is indicated on the aquastat display.
Replace aquastat.
E2 error message. Can cause the unit to trip a safety control if the setting is too high or low.
Replace aquastat.
01 JAN 2014 Page 41 001223MAN-04
Fault
HYDRONIC OPERATION TROUBLESHOOTING - HEATING MODE
Possible Cause
High Discharge
Pressure
Aquastat set too high.
Low or no Indoor loop flow.
TXV adjusted too far closed.
Verification Recommended Action
Verify aquastat setting
Verify superheat. It should be between 8-12°F (3-6°C). Superheat will be high if TXV is closed too far.
Lower aquastat setting to recommended value of
115°F (46°C)
Delta T across the Indoor Loop ports should be between 8-12°F (3-6°C), or compare pressure drop to the tables for the unit.
Verify pump is working and sized correctly. Check for restrictions in the circuit, ie valve partially closed.
Adjust TXV to obtain 8-12°F
(3-6°C) superheat.
TXV stuck almost closed or partially blocked by foreign object.
Adjusting the TXV does not affect the superheat or the suction pressure.
Adjust the TXV all the way in and out a few times to loosen it. Replace TXV if this does not work.
Filter-drier plugged Feel each end of the filter- drier, it should be the same temperature. If there is a temperature difference then it is plugged. Also causes low suction pressure.
Replace filter-drier.
Unit is overcharged.
(Only possible if unit has been opened in the field and incorrectly charged)
High sub-cooling, low delta T across air coil.
Remove 1/2lb of refrigerant at a time and verify that the discharge pressure reduces.
Faulty reversing valve#2 solenoid coil.
Verify solenoid by removing it from the shaft while the unit is running.
There should be a loud “whoosh” sound when it is removed.
Replace solenoid if faulty.
Low Suction
Pressure
Faulty reversing valve#2. A click can be heard when the coil is energized but the unit will not switch to water heating mode.
Replace reversing valve.
Low or no Outdoor liquid flow
Entering liquid temperature too cold.
Delta T across the Outdoor Loop ports should be between 5-7°F
(3-4°C), or compare pressure drop to the tables for the unit.
Measure the entering liquid temperature. Most likely caused by undersized ground loop.
Determine the cause of the flow restriction and correct it.
Verify pumps are working and sized correctly for ground loop systems.
Verify well pump and water valve is working for ground water systems.
Increase the size of the ground loop.
Dirty or fouled coaxial heat exchanger.
(typically for ground water, unlikely for ground loop)
Disconnect the water lines and check the inside of the pipes for scale deposits.
Indoor Loop entering liquid temperature too cold
Measure temperature. Should be above 60°F (15°C).
Have a qualified service technician backflush the coaxial exchanger.
Restrict Indoor liquid flow temporarily until buffer tank comes up to temperature.
001223MAN-04 Page 42 01 JAN 2014
Fault
Low Suction
Pressure
(continued)
HYDRONIC OPERATION TROUBLESHOOTING - HEATING MODE
Possible Cause Verification Recommended Action
TXV stuck almost closed or partially blocked by foreign object.
Adjusting the TXV does not affect the superheat or the suction pressure. TXV may be frosting up.
Adjust the TXV all the way in and out a few times to loosen it. Replace
TXV if this does not work.
Faulty NO solenoid valve coil.
Verify solenoid by removing it from the shaft while the unit is running.
There should be an audible click sound if the solenoid is working.
Faulty NO solenoid valve. A click can be heard when the coil is energized but the valve is cold instead of warm.
Replace solenoid if faulty.
Replace NO valve.
Leaking check valve.
(Located in parallel with the NO valve.
Valve will be cold instead of warm. Try tapping the valve and switching from air heat to water heat a few times. Replace the check valve if the problem persists.
Low refrigerant charge. Entering liquid temperature, flow and entering air temperature are good but suction is low. Check static refrigeration pressure of the unit for a very low value.
Locate the leak and repair it.
Spray nine, a sniffer and dye are common methods of locating a leak.
Faulty compressor, not pumping.
Pressures change only slightly from static values when compressor is started.
Replace compressor.
High Suction
Pressure
(may appear to not be pumping)
Leaking reversing valve#1.
TXV adjusted too far open.
Reversing valve is the same temperature on both ends of body, common suction line is warm, compressor is running hot.
Verify superheat. It should be between 8-12°F (3-6°C). Superheat will be low if TXV is open too far.
Replace reversing valve.
Adjust TXV to obtain 8-12°F
(3-6°C) superheat.
TXV stuck open. Adjusting the TXV does not affect the superheat or the suction pressure. Low super heat and discharge pressure.
Adjust the TXV all the way in and out a few times to loosen it. Replace
TXV if this does not work.
Leaking check valve.
(Located beside reversing valve#2)
3/4” pipe and check valve going into air coil is hot. Unit works properly in air heating mode.
Replace check valve.
Compressor frosting up
See Low Suction
Pressure in this section.
TXV frosting up
TXV stuck almost closed or partially blocked by foreign object.
Adjusting the TXV does not affect the superheat or the suction pressure.
Adjust the TXV all the way in and out a few times to loosen it. Replace
TXV if this does not work.
Random high pressure trip
(does not occur while on site)
Faulty compressor contactor.
Points pitted or burned. Contactor sometimes sticks causing the compressor to run when it shouldn’t, tripping the high pressure control.
Replace contactor.
Intermittent Indoor circulator.
Verify wiring is good Correct the wiring or replace the circulator.
01 JAN 2014 Page 43 001223MAN-04
Fault
PLENUM HEATER TROUBLE SHOOTING
Possible Cause Verification Recommended Action
No 230VAC across plenum heater L1 and L2
Disconnect switch open.
(if installed)
Verify disconnect switch is in the ON position.
Determine why the disconnect switch was opened, if all is OK close the switch.
Fuse blown /
Breaker Tripped.
At plenum heater disconnect box (if installed), voltmeter shows voltage on the line side but not on the load side. Check if breaker is tripped.
Reset breaker or replace fuse at plenum heater disconnect box.
Replace fuse with proper size and type. (Time-delay type “D”)
Same “Line” to L1 and L2 Measuring L1 to ground and L2 to ground both yield 115VAC, but L1 to
L2 yields 0VAC.
Correct wiring.
No W2 signal at
Heat pump terminal strip
No call for auxiliary or emergency heat from thermostat.
Verify that the thermostat is indicating that auxiliary or emergency heat should be on.
Set thermostat to engage auxiliary or emergency heat (note some thermostats require a jumper between auxiliary and emergency.
Check the thermostat manual).
Faulty thermostat.
Faulty thermostat.
Thermostat doesn’t indicate a call for auxiliary or emergency when it should.
Thermostat indicates auxiliary or emergency but no 24VAC signal present across C and the auxiliary and/or emergency pin at the thermostat.
Replace thermostat.
Replace thermostat.
Faulty thermostat wiring. 24VAC signal is present across C and the auxiliary and/or emergency pin at the thermostat but no 24VAC signal is present across W2 and C at the heat pump terminal strip.
Correct wiring.
Replace transformer.
No 24VAC signal from C to ground at the plenum heater control connector
Plenum Heater transformer is burned out.
Plenum heater control board is faulty.
Voltmeter does not show 24VAC across transformer secondary winding.
Transformer tested OK in previous step.
Replace control board.
No 24VAC signal from 1 to ground at the plenum heater control connector
Faulty wiring. 24VAC present across C and ground at the plenum heater, but not across ground of the plenum heater and I of the heat pump terminal strip
Correct wiring.
Faulty wiring.
No 24VAC signal from 1 to ground at the plenum heater control connector
Faulty Plenum Heater
Relay in heat pump
001223MAN-04
If previous step tested OK, 24VAC is present across ground of the plenum heart and 1 of the heat pump terminal strip, but not across ground of the plenum heater and 1 of the plenum heater.
Correct wiring.
24VAC is present across pin 1 and pin 3 of the relay, 24VAC is present from heat pump terminal strip I to plenum heater ground, but not from heat pump terminal strip 1 to plenum heater ground.
Replace relay.
Page 44 01 JAN 2014
Fault
PLENUM HEATER TROUBLE SHOOTING
Possible Cause Verification
Thermal overload is tripped.
Fan not operating See Fan Not Operating section
Recommended Action
Correct problem. Reset thermal overload.
Faulty overload Reset thermal overload Replace if faulty.
Fault
Insufficient hot water
(Tank Problem)
DOMESTIC HOT WATER (DHW) TROUBLE SHOOTING
Possible Cause Verification Recommended Action
Thermostat on hot water tank set too low. Should be set at 120°F. (140°F if required by local code)
Breaker tripped, or fuse blown in electrical supply to hot water tank.
Reset button tripped on hot water tank.
Visually inspect the setting.
Check both line and load sides of fuses. If switch is open determine why.
Check voltage at elements with multimeter.
Readjust the setting to 120°F.
(140°F if required by local code)
Replace blown fuse or reset breaker.
Push reset button.
Insufficient hot water
(Heat Pump
Problem)
Circulator pump not operating.
Visually inspect the pump to see if shaft is turning. Use an amprobe to measure current draw.
Blockage or restriction in the water line or hot water heat exchanger.
Check water flow and power to pump. Check water lines for obstruction
Faulty DHW cutout (failed open).
Check contact operation. Should close at 120°F and open at 140°F.
Heat pump not running enough hours to make sufficient hot water.
Note the amount of time the heat pump runs in any given hour.
Water is too hot. Faulty DHW cutout (failed closed).
Check contact operation. Should close at 120°F and open at 140°F.
Thermostat on hot water tank set too high. Should be set at 120°F. (140°F if required by local code)
Visually inspect the setting.
Replace if faulty.
Remove obstruction in water lines. Acid treat the domestic hot water coil.
Replace DHW cutout if faulty.
Temporarily turn up the tank thermostats until colder weather creates longer run cycles.
Replace DHW cutout if faulty.
Readjust the setting to 120°F.
(140°F if required by local code)
Refrigeration
In-line Flowmeter
01 JAN 2014
Trouble Shooting Tools
Digital
Multimeter -
Voltmeter /
Page 45
Dole flow control Valve
The Dole® flow control is a simple, selfcleaning device designed to deliver a constant volume of water from any outlet whether the pressure is 15 psig or as high as 125 psi. The controlling mechanism consists of a flexible orifice that varies its area inversely with pressure so that a constant flow is maintained.
001223MAN-04
REPAIR PROCEDURES
PUMP DOWN PROCEDURE
STEP 1
Connect the refrigerant recovery unit to the heat pump service ports via a refrigeration charging manifold and to a recovery tank as per the instructions in the recovery unit manual. If there was a compressor
burn out, the refrigerant cannot be reused and must be disposed of according to local codes.
STEP 2
All water coil heat exchangers must either have full flow or be completely drained of fluid before recovery begins. Failure to do so can freeze and rupture the heat exchanger, voiding its warranty. (Note that this does not apply to double wall domestic hot water exchangers (desuperheater coils)
STEP 3
Ensure all hose connections are properly purged of air. Start the refrigerant recovery as per the instructions in the recovery unit manual.
STEP 4
Allow the recovery unit suction pressure to reach a vacuum. Once achieved, close the charging manifold valves. Shut down, purge and disconnect the recovery unit as per the instructions in its manual. Ensure the recovery tank valve is closed before disconnecting the hose to it.
STEP 5
Connect a nitrogen tank to the charging manifold and add nitrogen to the heat pump until a positive pressure of 5-10PSIG is reached. This prevents air from being sucked into the unit by the vacuum when the hoses are disconnected.
STEP 6
The heat pump is now ready for repairs. Always ensure nitrogen is flowing through the system during any soldering procedures to prevent soot buildup inside the pipes. Maritime Geothermal Ltd. recommends replacing the liquid line filter-drier anytime the refrigeration system has been exposed to the atmosphere.
VACUUM AND CHARGING PROCEDURE
STEP 1
After completion of repairs and nitrogen pressure testing, the refrigeration circuit is ready for vacuuming.
STEP 2
Release the refrigerant circuit pressure and connect the vacuum pump to the charging manifold. Start the vacuum pump and open the charging manifold valves. Vacuum until the vacuum gauge remains at less than 500 microns for at least 1 minute with the vacuum pump valve closed.
STEP 3
Close the charging manifold valves then shut off and disconnect the vacuum pump. Place a refrigerant tank with the proper refrigerant on a scale and connect it to the charging manifold. Purge the hose to the tank.
STEP 4
Weigh in the appropriate amount of refrigerant through the low pressure (suction) service port. Refer to the label on the unit or the
Refrigerant Charge Chart
in the
MODEL SPECIFIC INFORMATION
section for the proper charge amount.
STEP 5
If the unit will not accept the entire charge, the remainder can be added through the low pressure service port after the unit has been restarted.
REPLACMENT PROCEDURE FOR A COMPRESSOR BURN-OUT
STEP 1
Pump down the unit as per the Pump Down Procedure above. Discard the refrigerant according to local codes.
STEP 2
Replace the compressor. Replace the liquid line filter-drier.
STEP 3
Vacuum the unit until it remains under 500 microns for several minutes with the vacuum pump valve closed.
STEP 4
Charge the unit with NEW REFRIGERANT and operate it for continuously for 2 hours. Pump down the unit and replace the filter-drier. Vacuum the unit until it remains under 500 microns for several minutes with the vacuum pump valve closed.
STEP 5
Charge the unit (refrigerant can be re-used) and operate it for 2-3 days. Perform an acid test. If it fails, pump down the unit and replace the filter-drier.
STEP 6
Charge the unit (refrigerant can be re-used) and operate it for 2 weeks. Perform and acid test, If it fails pump down the unit and replace the filter-drier.
STEP 7
Charge the unit a final time. Unit should now be clean and repeated future burn-outs can be avoided.
001223MAN-04 Page 46 01 JAN 2014
REFRIGERATION CIRCUIT DIAGRAMS
01 JAN 2014 Page 47 001223MAN-04
REFRIGERATION CIRCUIT DIAGRAMS (continued)
001223MAN-04 Page 48 01 JAN 2014
REFRIGERATION CIRCUIT DIAGRAMS (continued)
01 JAN 2014 Page 49 001223MAN-04
Model Specific Information
This section provides general information particular to each model. For complete specifications please see the specifications document for the desired model.
REFRIGERANT CHARGE CHART SHIPPING INFORMATION
Table 16 - Refrigerant - R410a
SIZE Lbs. kg
45
55
65
75
80
6.0 2.7
8.0 3.6
10.0 4.5
12.0 5.4
12.0 5.4
System contains POE oil.
MODEL
SIZE
45
55
65
75
80
Table 17 - Shipping Information
WEIGHT
Lbs. (kg)
520 (236)
575 (261)
635 (288)
680 (308)
695 (315)
DIMENSIONS in (cm)
L W H
44 (112) 36 (91) 68 (173)
44 (112) 36 (91) 68 (173)
44 (112) 36 (91) 68 (173)
44 (112) 36 (91) 68 (173)
44 (112) 36 (91) 68 (173)
STANDARD CAPACITY RATINGS
The tables below depict the results of standard capacity rating tests according to C13256-1, which is identical to ISO13256-1.
Stage 1 values do not apply to single stage units. Refer to the Electrical Tables to determine which models are single stage.
Table 18 - Standard Capacity Ratings - Ground Loop Heating* 60Hz
EAT 68°F (20°C)
STAGE 2 - ELT 32°F (0°C)
Model
Size Liquid Flow
Pressure
Drop
Mode Airflow
Input
Energy
Capacity COP
H
Tons IGAL USG L/s PSI kPA CFM L/s Watts BTU/Hr kW W/W
45
55
65
75
80
3
4
5
6
6
8
10 12.0 0.76 5.1 35.3
12 14.4 0.91 6.3 43.7
14
14
9.6 0.61 5.5 37.9
16.8
16.8
1.06
1.06
* 15% NaCl by Weight Ground Loop Fluid
5.9
5.9
40.8
40.8
Stage 1
Stage 2
Stage 1
Stage 2
Stage 1
Stage 2
Stage 1
Stage 2
Stage 1
1030
1200
486
566
1240
1500
1540
1900
585
708
727
897
1660
2100
783
991
2400 1133
1,550
2,290
2,250
3,000
2,615
3,510
3,600
4,465
5,155
23,600
31,700
6.9
9.4
33,500 9.8
39,500 11.6
39,000 11.4
47,800 14.0
48,400 14.2
57,200 16.8
61,900 18.1
4.47
4.06
4.37
3.86
4.37
3.99
3.94
3.75
3.52
REV-11
Table 19 - Standard Capacity Ratings - Ground Water Heating 60Hz
EAT 68°F (20°C) ELT 50°F (10°C)
Model
45
55
65
75
80
Size Liquid Flow
Pressure
Drop
Tons IGAL USG L/s PSI kPA
3
4
5
6
6
8
10 12.0 0.76 4.6 32.1
12 14.4 0.91 5.6 38.9
14
14
9.6 0.61 4.9 34.1
16.8
16.8
1.06
1.06
5.0
5.0
34.6
34.6
Mode
Stage 1
Stage 2
Stage 1
Stage 2
Stage 1
Stage 2
Stage 1
Stage 2
Stage 1
Airflow
CFM
1030
1200
L/s
486
566
1240
1500
1540
1900
585
708
727
897
1660
2100
783
991
2400 1133
Input
Energy
Watts
1,500
2,480
2,315
3,305
2,645
3,790
3,610
4,880
5,600
Capacity
BTU/Hr kW
26,900 7.9
40,200 11.8
37,800 11.1
51,500 15.1
44,100 12.9
60,400 17.7
54,200 15.9
71,400 20.9
77,100 22.6
COP
H
W/W
5.26
4.75
4.78
4.57
4.89
4.67
4.40
4.29
4.04
REV-11
001223MAN-04 Page 50 01 JAN 2014
STANDARD CAPACITY RATINGS (continued)
Table 20 - Standard Capacity Ratings -
Ground Loop Cooling*
60Hz
EAT 80.6°F (27°C)
STAGE 2 - ELT 77°F (25°C)
Model
Size Liquid Flow
Pressure
Drop
Mode Airflow
Input
Energy
Capacity COP c
Tons IGAL USG L/s PSI kPA CFM L/s Watts BTU/Hr kW W/W
45
55
65
75
80
3
4
5
6
6
8
14
14
9.6 0.61 5.1 35.1
10 12.0 0.76 4.9 33.6
12 14.4 0.91 5.7 39.2
16.8
16.8
1.06
1.06
5.6
5.6
38.8
38.8
Stage 1
Stage 2
Stage 1
Stage 2
Stage 1
Stage 2
Stage 1
Stage 2
Stage 1
1030
1200
1240
1500
1540
1900
486
566
585
708
727
897
1660
2100
783
991
2400 1133
1,060
1,965
1,750
3,015
2,025
3,500
2,790
4,460
5,235
32,600
44,100
41,600
51,700
49,400
60,500
58,200
69,700
77,200
9.6
12.9
12.2
15.1
14.4
17.7
17.0
20.4
22.6
9.04
6.57
6.97
5.02
7.14
5.06
6.11
4.58
4.32
* 15% NaCl by Weight Ground Loop Fluid
REV-11
Table 21 - Standard Capacity Ratings -
Ground Water Cooling
60Hz
EAT 80.6°F (27°C) ELT 59°F (15°C)
Model
45
55
65
75
80
Size Liquid Flow
Pressure
Drop
Tons IGAL USG L/s PSI kPA
3
4
5
6
6
8 9.6 0.61 5.0 34.8
10 12.0 0.76 4.7 32.2
12 14.4 0.91 5.5 38.0
14
14
16.8
16.8
1.06
1.06
4.9
4.9
33.6
33.6
Mode
Stage 1
Stage 2
Stage 1
Stage 2
Stage 1
Stage 2
Stage 1
Stage 2
Stage 1
Airflow
CFM
1030
1200
1240
1500
1540
1900
1660
2100
2400 1133
L/s
486
566
585
708
727
897
783
991
Input
Energy
Watts
895
1,640
1,525
2,515
1,760
2,950
2,485
3,875
4,350
Capacity
BTU/Hr kW
33,900
45,600
43,300
56,000
51,300
66,700
61,100
76,600
9.9
13.4
12.7
16.4
15.0
19.5
17.9
22.2
84,100 24.6
COP c
W/W
11.11
8.16
8.31
6.52
8.53
6.63
7.21
5.79
5.66
Table 22 - Standard Capacity Ratings - Ground Loop Hydronic Heating*
EWT 104°F (40°C)
STAGE 2 - ELT 32°F (0°C)
Model
Size
Liquid Flow
(Outdoor & Indoor)
Outdoor
Pressure Drop
Mode
Input
Energy
Capacity COP
H
Tons IGAL USG L/s PSI kPA Watts BTU/Hr kW W/W
45
55
65
75
80
3
4
5
6
6
8
10
12
14
14
9.6
12.0 0.76
14.4 0.91
16.8
16.8
* 15% NaCl by Weight Ground Loop Fluid
0.61
1.06
1.06
5.5
5.1
6.3
5.9
5.9
37.9
35.3
43.7
40.8
40.8
Stage 1
Stage 2
Stage 1
Stage 2
Stage 1
Stage 2
Stage 1
Stage 2
Stage 1
1,940
2,665
2,920
3,950
3,340
4,340
4,395
5,425
6,490
21,600
28,100
31,100
38,300
38,200
46,200
44,800
51,400
56,600
6.3
8.2
9.1
11.2
11.2
13.5
13.1
15.0
16.6
3.26
3.09
3.13
2.85
3.35
3.12
2.99
2.77
2.83
REV-11
Table 23 - Standard Capacity Ratings - Ground Water Hydronic Heating 60Hz
EWT 104°F (40°C) ELT 50°F (10°C)
Model
45
55
65
75
80
Size
Tons
3
4
5
6
6
Liquid Flow
(Outdoor & Indoor)
IGAL USG L/s
8
10
12
14
14
9.6 0.61
12.0 0.76
14.4 0.91
16.8
16.8
1.06
1.06
Outdoor
Pressure Drop
PSI kPA
4.9
4.6
5.6
5.0
5.0
34.1
32.1
38.9
34.6
34.6
Mode
Stage 1
Stage 2
Stage 1
Stage 2
Stage 1
Stage 2
Stage 1
Stage 2
Stage 1
Input
Energy
Watts
1,840
2,595
2,860
3,910
3,305
4,365
4,335
5,565
6,245
Capacity
BTU/Hr
25,700
36,600
35,700
48,800
43,900
59,100
51,700
67,700
73,300 kW
7.5
10.7
10.5
14.3
12.9
17.3
15.2
19.8
21.5
COP
H
W/W
4.09
4.13
3.66
3.65
3.89
3.97
3.50
3.57
3.44
01 JAN 2014 Page 51 001223MAN-04
CAPACITY RATINGS
Heating Mode
TF-45-HACW-P-1T
Source Data (Outdoor Loop)
ELT
Evap.
Temp
Flow LLT Delta T HAB
°F
°C
°F USGPM °F
°C L/s °C
°F
°C
Nominal 3 ton
Power Consumption
Compressor Fan* Effective COPh EAT
BTU/Hr Watts Amps Watts Watts
W/W
Watts
°F
°C
R410a 60 Hz
Sink Data (Indoor Loop)
Cond.
Temp.
°F
°C
Air
Flow
CFM
L/s
LAT Delta T
°F
°C
Net
Output
°F
BTU/Hr
°C
Watts
25.0 20 9.6 20.2 4.8 21,781 217 2,236
3.82
68 100 1,200 92.3 24.3 29,128
-3.9 -6.7 0.606 -6.5 2.7 6,382 20.0 37.8 566 33.5 13.5
8,534
31.0 25 9.6 25.8 5.2 23,701 217 2,293
3.99
68 102 1,200 94.0 26.0 31,242
-0.6 -3.9 0.606 -3.4 2.9 6,944 20.0 38.9 566 34.5 14.5
9,154
37.0 30 9.6 31.4 5.6 25,756 217 2,350
4.18
68 104 1,200 95.9 27.9 33,493
2.8 -1.1 0.606 -0.4 3.1 7,546 20.0 40.0 566 35.5 15.5
9,813
43.0 35 9.6 36.9 6.1 27,903 217 2,399
4.37
68 105 1,200 97.8 29.8 35,806
6.1 1.7 0.606 2.7 3.4 8,175 20.0 40.6 566 36.6 16.6 10,491
45.0 40 9.6 38.7 6.3 29,994 217 2,421
4.62
68 107 1,200 99.5 31.5 38,152
7.2 4.4 0.606 3.7 3.5 8,788 20.0 41.7 566 37.5 17.5 11,179
51.0 45 9.6 44.2 6.8 32,454 217 2,483
4.82
68 109 101.7 33.7 40,822
10.6 7.2 0.606 6.8 3.8 9,509 20.0 42.8 566 38.7 18.7 11,961
57.0 50 9.6 49.7 7.3 35,062 217 2,546
5.02
68 111 104.0 36.0 43,647
13.9 10.0 0.606 9.8 4.1 10,273 20.0 43.9 566 40.0 20.0 12,788
63.0 55 9.6 55.1 7.9 37,821 217 2,612
5.23
68 113 106.5 38.5 46,631
17.2 12.8 0.606 12.8 4.4 11,082 20.0 45.0 566 41.4 21.4 13,663
Compressor: ZPS30K4E-PFV * @ 37.3Pa (0.15inH2o) Ext. Static
Cooling Mode
TF-45-HACW-P-1T
EAT
Source Data (Indoor Loop)
Evap.
Temp
Airflow LAT Delta T Latent Sensible
HAB
R410a 60 Hz
Power Consumption
Sink Data (Outdoor Loop)
Compressor Fan* Effective
Efficiency
ELT
Cond.
Temp.
Flow LLT Delta T Rejection
°F
°C
°F
°C
CFM
L/s
°F
°C
°F
°C
BTU/Hr
Watts
BTU/Hr
Watts
BTU/Hr Watts Amps Watts Watts
EER
Watts
COPc
°F
°C
°F USGPM °F
°C L/min °C
°F BTU/Hr
°C Watts
80.6 44.3 1,200 57.3 23.3 15,569
45,431 1,433 5.5
207 1,586
28.6
57 65 9.6 67.6 10.6 51,026
27.0
27.0
6.8
7.2
566 14.0 13.0
566 14.2 12.8
4,562
4,519
8,749 13,311
8,667 13,185
8.39 13.9 18.3 0.606 19.8 5.9 14,951
80.6 45 1,200 57.5 23.1 15,422 45,001 1,563 6.0 207 1,717
26.2
62 70 9.6 72.6 10.6 51,042
7.68 16.7 21.1 0.606 22.6 5.9 14,955
80.6 45.7 1,200 57.7 22.9 15,262 44,535 1,694 6.4 207 1,847
24.1
67 75 9.6 77.6 10.6 51,023
27.0 7.6 566 14.3 12.7 4,472 8,577 13,049 7.06 19.4 23.9 0.606 25.4 5.9 14,950
80.6 46.3 1,200 57.9 22.7 15,148 44,201 1,753 6.9 207 1,906
23.2
72 80 9.6 82.6 10.6 50,889
27.0 7.9 566 14.4 12.6 4,438 8,513
12,951 6.79 22.2 26.7 0.606 28.1
5.9 14,910
80.6 47 1,200 57.4 23.2 14,236
43,898 1,803 7.4
207 1,992
22.0
78 85 9.6 89.1 11.1 50,760
27.0 8.3 566 14.1 12.9 4,171 8,691
12,862 6.46 25.6 29.4 0.606 31.7
6.2 14,872
80.6 48 1,200 57.7 22.9 14,046
43,310 1,932 7.9
207 2,121
20.4
83 90 9.6 94.1 11.1 50,609
27.0 8.7 566 14.3 12.7 4,115 8,575 12,690 5.98 28.3 32.2 0.606 34.5 6.2 14,828
80.6 48 1,200 58.0 22.6 13,841 42,681 2,065 8.5 207 2,254
18.9
88 95 9.6 99.1 11.1 50,434
27.0 9.1 566 14.5 12.5 4,056 8,450 12,505 5.55 31.1 35.0 0.606 37.3 6.1 14,777
80.6 49 1,200 58.4 22.2 13,623 42,009 2,204 9.0 207 2,393
17.6
93 100 9.6 104.0 11.0 50,237
27.0 9.5 566 14.7 12.3
Compressor: ZPS30K4E-PFV
3,992 8,317 12,308 5.14 33.9 37.8 0.606 40.0 6.1 14,719
* @ 37.3Pa (0.15inH2o) Ext. Static
001223MAN-04 Page 52 01 JAN 2014
CAPACITY RATINGS (continued)
Heating Mode
TF-55-HACW-P-1T
Source Data (Outdoor Loop)
ELT
Evap.
Temp
Flow LLT Delta T HAB
°F
°C
°F USGPM °F
°C L/s °C
°F
°C
Nominal 4 ton
Power Consumption
Compressor Fan* Effective COPh EAT
BTU/Hr Watts Amps Watts Watts
W/W
Watts
°F
°C
R410a 60 Hz
Sink Data (Indoor Loop)
Cond.
Temp.
°F
°C
Air
Flow
LAT Delta T
CFM °F
L/s °C
Net
Output
°F
BTU/Hr
°C
Watts
26.0 15 12.0 21.3 4.7 27,057 184 2,839
3.77
68 91 1,500 92.3 24.3 36,516
-3.3 -9.4 0.757 -6.0 2.6 7,928
32.0 20 12.0 26.8 5.2 29,480 184 3,008
3.85
20.0 32.8 708 33.5 13.5 10,699
68 96 1,500 94.3 26.3 39,518
0.0 -6.7 0.757 -2.9 2.9 8,638 20.0 35.6 708 34.6 14.6 11,579
38.0 25 12.0 32.4 5.6 31,996 184 3,184
3.92
68 101 1,500 96.4 28.4 42,634
3.3 -3.9 0.757 0.2 3.1 9,375 20.0 38.3 708 35.8 15.8 12,492
44.0 30 12.0 37.8 6.2 35,339 184 3,312
4.11
68 110 1,500 98.9 30.9 46,412
6.7 -1.1 0.757 3.2 3.4 10,354 20.0 43.3 708 37.2 17.2 13,599
49.0 35 12.0 42.4 6.6 39,564 184 3,314
4.48
68 116 101.8 33.8 50,663
9.4 1.7 0.757 5.8 3.7 11,592 20.0 46.7 708 38.8 18.8 14,844
55.0 40 12.0 47.9 7.1 42,408 184 3,504
4.53
68 121 104.1 36.1 54,154
12.8 4.4 0.757 8.8 3.9 12,425 20.0 49.4 708 40.1 20.1 15,867
61.0 45 12.0 53.4 7.6 45,485 184 3,685
4.60
68 106.6 38.6 57,849
16.1 7.2 0.757 11.9 4.2 13,327 20.0 51.9 708 41.4 21.4 16,950
67.0 50 12.0 58.9 8.1 48,432 184 3,898
4.62
68 109.0 41.0 61,523
19.4 10.0 0.757 15.0 4.5 14,190 20.0 54.7 708 42.8 22.8 18,026
Compressor: ZPS40K4E-PFV * @ 37.3Pa (0.15inH2o) Ext. Static
Cooling Mode
TF-55-HACW-P-1T
EAT
Source Data (Indoor Loop)
Evap.
Temp
Airflow LAT Delta T Latent Sensible
HAB
R410a 60 Hz
Power Consumption
Sink Data (Outdoor Loop)
Compressor Fan* Effective
Efficiency
ELT
Cond.
Temp.
Flow LLT Delta T Rejection
°F
°C
°F
°C
CFM
L/s
°F
°C
°F
°C
BTU/Hr
Watts
BTU/Hr
Watts
BTU/Hr Watts Amps Watts Watts
EER
Watts
COPc
°F
°C
°F USGPM °F
°C L/s °C
°F BTU/Hr
°C Watts
80.6 46 1,500 55.6 25.0 19,259
58,987 2,069 9.2
181 2,197
26.8
48 75 12.0 59.1 11.1 66,666
27.0
27.0
7.8
7.8
708 13.1 13.9
708 13.4 13.6
5,643
5,514
11,640 17,283
11,374 16,888
7.87
8.9 23.9 0.757 15.1 6.2 19,533
80.6 46 1,500 56.2 24.4 18,819 57,637 2,211 9.8 181 2,339
24.6
53 80 12.0 64.0 11.0 65,800
7.22 11.7 26.7 0.757 17.8 6.1 19,279
80.6 46 1,500 56.8 23.8 18,366 56,252 2,355 10.4 181 2,484
22.6
58 85 12.0 68.8 10.8 64,907
27.0 7.8 708 13.8 13.2 5,381 11,100 16,482 6.64 14.4 29.4 0.757 20.5 6.0 19,018
80.6 47 1,500 57.8 22.8 17,583 53,854 2,623 11.0 181 2,751
19.6
63 90 12.0 73.6 10.6 63,423
27.0 8.3 708 14.3 12.7 5,152 10,627
15,779 5.74 17.2 32.2 0.757 23.1
5.9 18,583
80.6 48 1,500 58.3 22.3 16,209
51,407 2,909 11.7 181 3,045
16.9
78 95 12.0 88.9 10.9 61,955
27.0 8.9 708 14.6 12.4 4,749 10,313
15,062 4.95 25.6 35.0 0.757 31.6
6.0 18,153
80.6 48 1,500 58.9 21.7 15,755
49,970 3,083 12.3 181 3,219
15.5
83 100 12.0 93.7 10.7 61,110
27.0 8.9 708 14.9 12.1 4,616 10,025 14,641 4.55 28.3 37.8 0.757 34.3 6.0 17,905
80.6 48 1,500 59.5 21.1 15,290 48,493 3,265 13.0 181 3,401
14.3
88 105 12.0 98.6 10.6 60,253
27.0 8.9 708 15.3 11.7 4,480 9,728 14,208 4.18 31.1 40.6 0.757 37.0 5.9 17,654
80.6 48 1,500 60.2 20.4 14,811 46,975 3,455 13.8 181 3,591
13.1
93 110 12.0 103.4 10.4 59,386
27.0 8.9 708 15.7 11.3
Compressor: ZPS40K4E-PFV
4,340 9,424 13,764 3.83 33.9 43.3 0.757 39.7 5.8 17,400
* @ 37.3Pa (0.15inH2o) Ext. Static
01 JAN 2014 Page 53 001223MAN-04
CAPACITY RATINGS (continued)
Heating Mode
TF-65-HACW-P-1T
Source Data (Outdoor Loop)
ELT
Evap.
Temp
Flow LLT Delta T HAB
°F
°C
°F USGPM °F
°C L/s °C
°F
°C
Nominal 5 ton
Power Consumption
Compressor Fan* Effective COPh EAT
BTU/Hr Watts Amps Watts Watts
W/W
Watts
°F
°C
R410a 60 Hz
Sink Data (Indoor Loop)
Cond.
Temp.
°F
°C
Air
Flow
LAT Delta T
CFM °F
L/s °C
Net
Output
°F
BTU/Hr
°C
Watts
26.0 15 14.4 21.2 4.8 32,776 255 3,417
3.79
68 96 1,900 91.3 23.3 44,189
-3.3 -9.4 0.908 -6.0 2.7 9,603
32.0 20 14.4 26.7 5.3 36,044 255 3,510
3.99
20.0 35.6 897 32.9 12.9 12,947
68 98 1,900 93.1 25.1 47,774
0.0 -6.7 0.908 -2.9 2.9 10,561 20.0 36.7 897 34.0 14.0 13,998
38.0 25 14.4 32.2 5.8 39,557 255 3,603
4.20
68 100 1,900 95.2 27.2 51,605
3.3 -3.9 0.908 0.1 3.2 11,590 20.0 37.8 897 35.1 15.1 15,120
44.0 30 14.4 37.7 6.3 43,192 255 3,674
4.42
68 102 1,900 97.2 29.2 55,483
6.7 -1.1 0.908 3.2 3.5 12,655 20.0 38.9 897 36.2 16.2 16,256
49.0 35 14.4 42.5 6.5 46,773 255 3,793
4.59
68 105 1,900 99.3 31.3 59,474
9.4 1.7 0.908 5.8 3.6 13,704 20.0 40.6 897 37.4 17.4 17,426
55.0 40 14.4 47.9 7.1 51,013 255 3,889
4.82
68 107 101.7 33.7 64,043
12.8 4.4 0.908 8.8 3.9 14,947 20.0 41.7 897 38.7 18.7 18,765
61.0 45 14.4 53.3 7.7 55,525 255 3,988
5.06
68 109 104.3 36.3 68,892
16.1 7.2 0.908 11.8 4.3 16,269 20.0 42.8 897 40.1 20.1 20,185
67.0 50 14.4 58.6 8.4 60,315 255 4,090
5.30
68 111 107.0 39.0 74,031
19.4 10.0 0.908 14.8 4.7 17,672 20.0 43.9 897 41.6 21.6 21,691
Compressor: ZPS51K4E-PFV * @ 49.7Pa (0.20inH2o) Ext. Static
Cooling Mode
TF-65-HACW-P-1T
EAT
Source Data (Indoor Loop)
Evap.
Temp
Airflow LAT Delta T Latent Sensible
HAB
R410a 60 Hz
Power Consumption
Sink Data (Outdoor Loop)
Compressor Fan* Effective
Efficiency
ELT
Cond.
Temp.
Flow LLT
Delta
T
Rejection
°F
°C
°F
°C
CFM
L/s
°F
°C
°F
°C
BTU/Hr
Watts
BTU/Hr
Watts
BTU/Hr Watts Amps Watts Watts
EER
Watts
COPc
°F
°C
°F USGPM °F
°C L/s °C
°F
°C
BTU/Hr
Watts
80.6 43.7 1,900 57.1 23.5 20,947
67,790 2,556 11.6 260 2,748
24.7
53 75 14.4 63.8 10.8 77,402
27.0
27.0
6.5
6.7
897 14.0 13.0
897 14.2 12.8
6,137
6,036
13,725 19,862
13,499 19,536
7.23 11.7 23.9 0.908 17.6 6.0 22,679
80.6 44 1,900 57.5 23.1 20,603 66,675 2,759 12.3 260 2,950
22.6
58 80 14.4 68.7 10.7 76,977
6.62 14.4 26.7 0.908 20.4 5.9 22,554
80.6 44.3 1,900 57.9 22.7 20,241 65,505 2,964 13.1 260 3,156
20.8
63 85 14.4 73.6 10.6 76,510
27.0 6.8 897 14.4 12.6 5,931 13,262 19,193 6.08 17.2 29.4 0.908 23.1 5.9 22,417
80.6 44.6 1,900 58.7 21.9 19,508 63,132 3,100 14.0 260 3,292
19.2
68 90 14.4 78.4 10.4 74,600
27.0
27.0
7.0
7.2
897 14.9 12.1
897 15.3 11.7
5,716
5,618
12,782
18,497
12,216
17,834
5.62 20.0 32.2 0.908 25.8 5.8 21,858
80.6 45 1,900 59.5 21.1 19,173
60,868 3,233 14.8 260 3,391
17.9
76 95 14.4 86.6 10.6 72,788
5.26 24.4 35.0 0.908 30.4 5.9 21,327
80.6 45 1,900 60.0 20.6 18,764
59,568 3,449 15.7 260 3,607
16.5
81 100 14.4 91.6 10.6 72,226
27.0 7.4 897 15.5 11.5 5,498 11,956 17,453 4.84 27.2 37.8 0.908 33.1 5.9 21,162
80.6 46 1,900 60.4 20.2 18,336 58,208 3,675 16.6 260 3,833
15.2
86 105 14.4 96.5 10.5 71,637
27.0 7.6 897 15.8 11.2 5,372 11,683 17,055 4.45 30.0 40.6 0.908 35.8 5.8 20,989
80.6 46 1,900 60.9 19.7 17,887 56,785 3,912 17.6 260 4,070
14.0
91 110 14.4 101.4 10.4 71,023
27.0 7.7 897 16.1 10.9
Compressor: ZPS51K4E-PFV
5,241 11,397 16,638 4.09 32.8 43.3 0.908 38.5 5.8 20,810
* @ 49.7Pa (0.20inH2o) Ext. Static
001223MAN-04 Page 54 01 JAN 2014
CAPACITY RATINGS (continued)
Heating Mode
TF-75-HACW-P-1T
Source Data (Outdoor Loop)
ELT
°F
°C
Nominal 6 ton
Power Consumption
Evap.
Temp
Flow LLT
°F USGPM °F
°C L/s °C
Delta T
°F
°C
HAB
BTU/Hr
Watts
Compressor Fan* Effective COPh
Watts Amps Watts Watts
W/W
EAT
°F
°C
R410a 60 Hz
Sink Data (Indoor Loop)
Cond.
Temp.
°F
°C
Air
Flow
LAT Delta T
CFM °F
L/s °C
°F
°C
Net
Output
BTU/Hr
Watts
27.0 15 16.8 22.1 4.9 39,359 370 4,375
3.60
68 104 2,100 93.6 25.6 53,818
-2.8 -9.4 1.060 -5.5 2.7 11,532 20.0 40.0 991 34.2 14.2 15,768
33.0 20 16.8 27.6 5.4 43,335 370 4,475
3.81
68 106 2,100 95.7 27.7 58,135
0.6 -6.7 1.060 -2.5 3.0 12,697 20.0 41.1 991 35.4 15.4 17,033
39.0 25 16.8 33.0 6.0 47,606 370 4,575
4.02
68 108 2,100 97.9 29.9 62,747
3.9 -3.9 1.060 0.6 3.3 13,949 20.0 42.2 991 36.6 16.6 18,385
45.0 30 16.8 38.5 6.5 51,487 370 4,713
4.17
68 110 100.0 32.0 67,102
7.2 -1.1 1.060 3.6 3.6 15,086 20.0 43.3 991 37.8 17.8 19,661
50.0 35 16.8 43.4 6.6 55,170 370 4,873
4.29
68 113 102.0 34.0 71,398
10.0 1.7 1.060 6.3 3.7 16,165 20.0 45.0 991 38.9 18.9 20,919
56.0 40 16.8 48.9 7.1 59,792 370 5,031
4.46
68 116 104.5 36.5 76,559
13.3 4.4 1.060 9.4 4.0 17,519 20.0 46.7 991 40.3 20.3 22,432
62.0 45 16.8 54.3 7.7 64,657 370 5,194
4.62
68 119 107.0 39.0 81,982
16.7 7.2 1.060 12.4 4.3 18,944 20.0 48.3 991 41.7 21.7 24,021
68.0 50 16.8 59.7 8.3 69,767 370 5,365
4.79
68 122 109.7 41.7 87,674
20.0 10.0 1.060 15.4 4.6 20,442
Compressor: ZPS60K4E-PFV
20.0 50.0 991 43.2 23.2 25,688
* @ 49.7Pa (0.20inH2o) Ext. Static
TF-75-HACW-P-1T
Source Data (Indoor Loop)
ELT
Evap.
Temp
Airflow LLT Delta T Latent Sensible
HAB
Cooling Mode
R410a 60 Hz
Power Consumption
Sink Data (Outdoor Loop)
Compressor Fan* Effective
Efficiency
EAT
Cond.
Temp.
Flow LAT Delta T Rejection
°F
°C
°F
°C
CFM
L/s
°F
°C
°F
°C
BTU/Hr
Watts
BTU/Hr
Watts
BTU/Hr Watts Amps Watts Watts
EER
Watts
COPc
°F
°C
°F USGPM °F
°C L/s °C
°F BTU/Hr
°C Watts
80.6 43.9 2,100 56.8 23.8 27,790 79,856 3,092 13.9 405 3,461
23.1
49 75 16.8 59.9 10.9 91,790
27.0
27.0
6.6
6.7
991 13.8 13.2
991 14.0 13.0
8,142
7,977
15,255 23,398
14,946 22,923
6.76
9.4 23.9 1.060 15.5 6.1 26,894
80.6 44 2,100 57.2 23.4 27,226 78,236 3,294 14.7 405 3,663
21.4
54 80 16.8 64.8 10.8 90,860
6.26 12.2 26.7 1.060 18.2 6.0 26,622
80.6 44.1 2,100 57.7 22.9 26,643 76,562 3,500 15.6 405 3,869
19.8
59 85 16.8 69.7 10.7 89,889
27.0 6.7 991 14.3 12.7 7,806 14,626 22,432 5.80 15.0 29.4 1.060 20.9 5.9 26,337
80.6 44.2 2,100 58.4 22.2 25,896 74,415 3,639 16.5 405 4,008
18.6
64 90 16.8 74.5 10.5 88,217
27.0 6.8 991 14.7 12.3 7,588 14,216 21,803 5.44 17.8 32.2 1.060 23.6 5.8 25,847
80.6 44 2,100 58.6 22.0 24,204 72,250 3,776 17.4 405 4,152
17.4
70 95 16.8 80.8 10.8 86,521
27.0 6.8 991 14.8 12.2 7,092 14,077
21,169 5.10 21.1 35.0 1.060 27.1
6.0 25,351
80.6 44 2,100 59.2 21.4 23,591
70,422 3,995 18.3 405 4,371
16.1
75 100 16.8 85.7 10.7 85,438
27.0 6.9 991 15.1 11.9 6,912 13,721
20,633 4.72 23.9 37.8 1.060 29.8
5.9 25,033
80.6 45 2,100 59.7 20.9 22,958
68,532 4,223 19.3 405 4,599
14.9
80 105 16.8 90.6 10.6 84,327
27.0 6.9 991 15.4 11.6 6,727 13,353 20,080 4.37 26.7 40.6 1.060 32.5 5.9 24,708
80.6 45 2,100 60.3 20.3 22,304
66,578 4,463 20.4 405 4,839
13.8
85 110 16.8 95.4 10.4 83,191
27.0 7.0 991 15.7 11.3 6,535 12,972 19,507 4.03 29.4 43.3 1.060 35.2 5.8 24,375
Compressor: ZPS60K4E-PFV * @ 49.7Pa (0.20inH2o) Ext. Static
01 JAN 2014 Page 55 001223MAN-04
CAPACITY RATINGS (continued)
Heating Mode
TF-80-HACW-P-*S
Source Data (Outdoor Loop)
ELT
Evap.
Temp
Flow LLT Delta T HAB
°F
°C
°F USGPM °F
°C L/s °C
°F
°C
Nominal 6 ton
Power Consumption
Compressor Fan* Effective COPh EAT
BTU/Hr Watts Amps Watts Watts
W/W
Watts ***
°F
°C
R410a 60 Hz
Sink Data (Indoor Loop)
Cond.
Temp.
°F
°C
Air
Flow
CFM
L/s
LAT Delta T
°F
°C
Net
Output
°F
BTU/Hr
°C
Watts
27.0 15 16.8 21.9 5.1 40,836 560 5,060
3.34
68 104 2,400 92.0 24.0 57,634
-2.8 -9.4 1.1 -5.6 2.8 11,965 14.8 20.0 40.0 1,133 33.3 13.3 16,887
33.0 20 16.8 27.2 5.8 45,990 560 5,145
3.59
68 106 2,400 94.3 26.3 63,078
0.6 -6.7 1.1 -2.6 3.2 13,475 15.0 20.0 41.1 1,133 34.6 14.6 18,482
39.0 25 16.8 32.6 6.4 51,427 560 5,230
3.85
68 108 2,400 96.7 28.7 68,805
3.9 -3.9 1.1 0.3 3.6 15,068 15.2 20.0 42.2 1,133 35.9 15.9 20,160
45.0 30 16.8 38.1 6.9 55,197 560 5,395
3.97
68 110 2,400 98.5 30.5 73,139
7.2 -1.1 1.1 3.4 3.8 16,173 15.4 20.0 43.3 1,133 36.9 16.9 21,430
50.0 35 16.8 43.0 7.0 58,405 560 5,598
4.04
68 113 100.1 32.1 77,109
10.0 1.7 1.1 6.1 3.9 17,113 15.7 20.0 45.0 1,133 37.8 17.8 22,593
56.0 40 16.8 48.4 7.6 63,866 560 5,754
4.23
68 116 102.6 34.6 83,100
13.3 4.4 1.1 9.1 4.2 18,712 16.1 20.0 46.7 1,133 39.2 19.2 24,348
62.0 45 16.8 53.7 8.3 69,610 560 5,911
4.43
68 119 105.2 37.2 89,383
16.7 7.2 1.1 12.1 4.6 20,395 16.4 20.0 48.3 1,133 40.7 20.7 26,189
68.0 50 16.8 59.0 9.0 75,652 560 6,072
4.63
68 122 108.0 40.0 95,973
20.0 10.0 1.1 15.0 5.0 22,166 16.8 20.0 50.0 1,133 42.2 22.2 28,120
Compressor: ZP70KWE *** 230-1-60 208-3-60 * @ 49.7Pa (0.02inH2o) Ext. Static
Cooling Mode
TF-80-HACW-P-*S
EAT
Source Data (Indoor Loop)
Evap.
Temp
Airflow LAT Delta T Latent Sensible
HAB
R410a 60 Hz
Power Consumption
Sink Data (Outdoor Loop)
Compressor Fan* Effective
Efficiency
ELT
Cond.
Temp.
Flow LLT Delta T Rejection
°F
°C
°F
°C
CFM
L/s
°F
°C
°F
°C
BTU/Hr
Watts
BTU/Hr
Watts
BTU/Hr Watts Amps Watts Watts
EER
Watts
*** COPc
°F
°C
°F USGPM °F
°C L/min °C
°F BTU/Hr
°C Watts
80.6 44 2,400 57.8 22.8 30,398
87,349 3,293 17.6
625 3,882
22.5
49 75 16.8 61.0 12.0 100,720
27.0
27.0
6.6
6.7
1,133 14.3 12.7
1,133 14.6 12.4
8,906
8,745
16,687 25,593 11.9
16,384 25,129 12.3
6.59
9.4 23.9 1.060 16.1 6.7 29,511
80.6 44 2,400 58.2 22.4 29,846 85,765 3,522 18.5 625 4,112
20.9
54 80 16.8 65.9 11.9 99,920
6.11 12.2 26.7 1.060 18.8 6.6 29,276
80.6 44 2,400 58.6 22.0 29,251 84,055 3,761 19.5 625 4,350
19.3
59 85 16.8 70.8 11.8 99,026
27.0 6.7 1,133 14.8 12.2 8,571 16,057 24,628 12.6 5.66 15.0 29.4 1.060 21.6 6.6 29,014
80.6 44 2,400 59.1 21.5 28,612 82,219 3,992 20.6 625 4,581
17.9
64 90 16.8 75.7 11.7 97,977
27.0 6.8 1,133 15.1 11.9 8,383 15,707
24,090
13.1
5.26 17.8 32.2 1.060 24.3
6.5 28,707
80.6 44 2,400 59.2 21.4 26,892
80,273 4,235 21.7
625 4,831
16.6
70 95 16.8 82.1 12.1 96,861
27.0 6.8 1,133 15.1 11.9 7,879 15,641
23,520
13.5
4.87 21.1 35.0 1.060 27.9
6.7 28,380
80.6 44 2,400 59.8 20.8 26,191
78,181 4,518 22.9
625 5,114
15.3
75 100 16.8 87.0 12.0 95,733
27.0 6.9 1,133 15.4 11.6 7,674 15,233 22,907 14.0 4.48 23.9 37.8 1.060 30.6 6.7 28,050
80.6 45 2,400 60.4 20.2 25,446 75,959 4,822 24.1 625 5,418
14.0
80 105 16.8 91.8 11.8 94,550
27.0 6.9 1,133 15.8 11.2 7,456 14,800 22,256 14.6 4.11 26.7 40.6 1.060 33.2 6.6 27,703
80.6 45 2,400 61.0 19.6 24,658 73,607 5,151 25.5 625 5,747
12.8
85 110 16.8 96.7 11.7 93,322
27.0 7.0 1,133 16.1 10.9 7,225 14,342 21,567 15.2
Compressor: ZP70KWE *** 230-1-60 208-3-60
3.75 29.4 43.3 1.060 35.9 6.5 27,343
* @ 49.7Pa (0.02inH2o) Ext. Static
001223MAN-04 Page 56 01 JAN 2014
HYDRONIC CAPACITY RATINGS
TF-45-HACW-P-1T
Source Data (Outdoor Loop)
Heating Mode
Nominal 3 ton
Power Consumption
R410a 60 Hz
Sink Data (Indoor Loop)
ELT
°F
°C
Evap.
Temp
°F USGPM °F
°C
Flow
L/s
LLT
°C
Delta T
°F
°C
HAB
BTU/Hr Watts Amps
Watts
Total Effective COPh EWT
Watts
W/W
°F
°C
Cond.
Temp.
°C
Flow LWT Delta T
Output
°F USGPM °F
L/s °C
°F
°C
Net
BTU/Hr
Watts
24.0 15 9.6 20.3 3.7 16,877 2,620 2.86 104.0 115 9.6 109.3 5.3
25,547
-4.4 -9.4 0.606 -6.5 2.1 4,945 40.0 46.1 0.606 43.0 3.0
7,485
30.0 20 9.6 25.9 4.1 18,504 2,661
3.01 104.0
116 9.6 109.7 5.7
27,313
-1.1 -6.7 0.606 -3.4 2.3 5,422 40.0 46.7 0.606 43.2 3.2
8,003
36.0 25 9.6 31.5 4.5 20,415 2,668
3.21 104.0
116 9.6 110.1 6.1
29,247
2.2 -3.9 0.606 -0.3 2.5 5,981 40.0 46.7 0.606 43.4 3.4
8,569
42.0 30 9.6 37.0 5.0 22,990 2,656 3.51 104.0 117 9.6 110.6 6.6
31,782
5.6 -1.1 0.606 2.8 2.8 6,736 40.0 47.2 0.606 43.7 3.7
9,312
45.0 35 9.6 39.3 5.7 25,833 2,596 3.90 104.0 118 9.6 111.2 7.2
34,580
7.2 1.7 0.606 4.1 3.1 7,569 40.0 47.8 0.606 44.0 4.0
10,132
51.0 40 9.6 44.8 6.2 28,381 2,599 4.19 104.0 118 9.6 111.7 7.7
37,139
10.6 4.4 0.606 7.1 3.5 8,316 40.0 47.8 0.606 44.3 4.3
10,882
57.0 45 9.6 50.2 6.8 30,910 2,634 4.43 104.0 119 9.6 112.3 8.3
39,789
13.9 7.2 0.606 10.1 3.8 9,057 40.0 48.3 0.606 44.6 4.6
11,658
63.0 50 9.6 55.6 7.4 33,856 2,638
4.75 104.0
119 9.6 112.9 8.9
42,746
17.2 10.0 0.606 13.1 4.1 9,920
Compressor: ZPS30K4E-PFV
40.0 48.3 0.606 45.0 5.0
12,524
TF-55-HACW-P-1T
Source Data (Outdoor Loop)
Heating Mode
Nominal 4 ton
Power Consumption
R410a 60 Hz
Sink Data (Indoor Loop)
ELT
°F
°C
Evap.
Temp
Flow LLT
°F USGPM °F
°C L/s °C
Delta T
°F
°C
HAB
Watts
Total
BTU/Hr Watts Amps
Effective COPh EWT
Watts
W/W
°F
°C
Cond.
Temp.
°F
°C
Net
Flow LWT Delta T
Output
USGPM
L/s
°F
°C
°F
BTU/Hr
°C
Watts
24.0 15 12.0 20.3 3.7 21,143 3,884
2.58 104.0
129 12.0 109.7 5.7
34,152
-4.4 -9.4 0.757 -6.5 2.1 6,195 40.0 53.9 0.757 43.2 3.2
10,006
30.0 20 12.0 25.8 4.2 23,823 3,943 2.75 104.0 130 12.0 110.2 6.2
37,033
-1.1 -6.7 0.757 -3.4 2.3 6,980 40.0 54.4 0.757 43.4 3.4
10,850
36.0 25 12.0 31.3 4.7 27,005 3,955
2.98 104.0
130 12.0 110.7 6.7
40,259
2.2 -3.9 0.757 -0.4 2.6 7,912 40.0 54.4 0.757 43.7 3.7
11,796
42.0 30 12.0 36.7 5.3 30,068 3,938
3.22 104.0
130 12.0 111.2 7.2
43,263
5.6 -1.1 0.757 2.6 2.9 8,810 40.0 54.4 0.757 44.0 4.0
12,676
46.0 35 12.0 40.2 5.8 33,327 3,908
3.48 104.0
130 12.0 111.7 7.7
46,447
7.8 1.7 0.757 4.5 3.2 9,765 40.0 54.4 0.757 44.3 4.3
13,609
52.0 40 12.0 45.5 6.5 37,284 3,914 3.77 104.0 130 12.0 112.4 8.4
50,424
11.1 4.4 0.757 7.5 3.6 10,924 40.0 54.4 0.757 44.7 4.7
14,774
58.0 45 12.0 50.8 7.2 41,193 3,963 4.03 104.0 131 12.0 113.1 9.1
54,499
14.4 7.2 0.757 10.4 4.0 12,070 40.0 55.0 0.757 45.1 5.1
15,968
64.0 50 12.0 56.0 8.0 45,776 3,967 4.36 104.0 131 12.0 113.9 9.9
59,098
17.8 10.0 0.757 13.3 4.5 13,412
Compressor: ZPS40K4E-PFV
40.0 55.0 0.757 45.5 5.5
17,316
01 JAN 2014 Page 57 001223MAN-04
HYDRONIC CAPACITY RATINGS (continued)
TF-65-HACW-P-1T
Source Data (Outdoor Loop)
Heating Mode
Nominal 5 ton
Power Consumption
R410a 60 Hz
Sink Data (Indoor Loop)
ELT
°F
°C
Evap.
Temp
°F USGPM °F
°C
Flow
L/s
LLT
°C
Delta T
°F
°C
HAB
BTU/Hr Watts Amps
Watts
Total Effective COPh EWT
Watts
W/W
°F
°C
Cond.
Temp.
°C
Flow LWT Delta T
Output
°F USGPM °F
L/s °C
°F
°C
Net
BTU/Hr
Watts
26.0 15 14.4 21.9 4.1 28,283 4,321 2.90 104.0 116 14.4 110.0 6.0
42,815
-3.3 -9.4 0.908 -5.6 2.3 8,287 40.0 46.7 0.908 43.3 3.3
12,545
32.0 20 14.4 27.4 4.6 31,592 4,338
3.12 104.0
116 14.4 110.4 6.4
46,179
0.0 -6.7 0.908 -2.6 2.6 9,256 40.0 46.7 0.908 43.6 3.6
13,530
38.0 25 14.4 32.9 5.1 35,196 4,349
3.36 104.0
116 14.4 110.9 6.9
49,823
3.3 -3.9 0.908 0.5 2.9 10,312 40.0 46.7 0.908 43.8 3.8
14,598
44.0 30 14.4 38.3 5.7 38,689 4,373 3.58 104.0 117 14.4 111.4 7.4
53,396
6.7 -1.1 0.908 3.5 3.1 11,336 40.0 47.2 0.908 44.1 4.1
15,645
48.0 35 14.4 41.8 6.2 42,747 4,365 3.85 104.0 117 14.4 112.0 8.0
57,344
8.9 1.7 0.908 5.4 3.5 12,525 40.0 47.2 0.908 44.4 4.4
16,802
54.0 40 14.4 47.1 6.9 46,946 4,423 4.09 105.0 118 14.4 113.6 8.6
61,739
12.2 4.4 0.908 8.4 3.8 13,755 40.6 47.8 0.908 45.3 4.8
18,090
60.0 45 14.4 52.4 7.6 51,814 4,429 4.41 104.0 118 14.4 113.3 9.3
66,627
15.6 7.2 0.908 11.3 4.2 15,181 40.0 47.8 0.908 45.1 5.1
19,521
66.0 50 14.4 57.7 8.3 56,667 4,487
4.68 105.0
119 14.4 115.0 10.0 71,680
18.9 10.0 0.908 14.3 4.6 16,603
Compressor: ZPS51K4E-PFV
40.6 48.3 0.908 46.1 5.5
21,002
TF-75-HACW-P-1T
Source Data (Outdoor Loop)
ELT
Evap.
Temp
Flow LLT Delta T HAB
Heating Mode
Nominal 6 ton
Power Consumption
Total Effective COPh EWT
R410a 60 Hz
Sink Data (Indoor Loop)
Cond.
Temp.
Net
Flow LWT Delta T
Output
°F °F USGPM °F °F BTU/Hr Watts Amps Watts
W/W
°F °F USGPM °F °F
BTU/Hr
°C °C L/s °C °C Watts °C °C L/s °C °C
Watts
26.0 15 16.8 22.2 3.8 29,942 5,349
2.61 104.0
125 16.8 109.7 5.7
47,736
-3.3 -9.4 1.060 -5.4 2.1 8,773 40.0 51.7 1.060 43.2 3.2
13,987
32.0 20 16.8 27.8 4.2 33,301 5,425 2.77 104.0 126 16.8 110.1 6.1
51,356
0.0 -6.7 1.060 -2.3 2.3 9,757 40.0 52.2 1.060 43.4 3.4
15,047
38.0 25 16.8 33.3 4.7 37,271 5,441 2.98 104.0 126 16.8 110.6 6.6
55,381
3.3 -3.9 1.060 0.7 2.6 10,920 40.0 52.2 1.060 43.7 3.7
16,226
44.0 30 16.8 38.7 5.3 42,601 5,480 3.25 104.0 126 16.8 111.2 7.2
60,844
6.7 -1.1 1.060 3.7 3.0 12,482 40.0 52.2 1.060 44.0 4.0
17,827
49.0 35 16.8 43.0 6.0 48,119 5,560
3.51 104.0
127 16.8 111.9 7.9
66,684
9.4 1.7 1.060 6.1 3.3 14,099 40.0 52.8 1.060 44.4 4.4
19,538
55.0 40 16.8 48.3 6.7 53,401 5,568
3.79 104.0
127 16.8 112.6 8.6
71,991
12.8 4.4 1.060 9.1 3.7 15,646 40.0 52.8 1.060 44.8 4.8
21,093
61.0 45 16.8 53.6 7.4 59,105 5,574
4.08 104.0
127 16.8 113.3 9.3
77,717
16.1 7.2 1.060 12.0 4.1 17,318 40.0 52.8 1.060 45.1 5.1
22,771
67.0 50 16.8 58.9 8.1 64,748 5,641 4.34 104.0 128 16.8 114.0 10.0 83,587
19.4 10.0 1.060 14.9 4.5 18,971
Compressor: ZPS60K4E-PFV
40.0 53.3 1.060 45.5 5.5
24,491
001223MAN-04 Page 58 01 JAN 2014
HYDRONIC CAPACITY RATINGS (continued)
TF-80-HACW-P-*S
Source Data (Outdoor Loop)
Heating Mode
Nominal 6 ton
Power Consumption
R410a 60 Hz
Sink Data (Indoor Loop)
ELT
°F
°C
Evap.
Temp
°F USGPM °F
°C
Flow
L/s
LLT
°C
Delta T
°F
°C
HAB
BTU/Hr Watts Amps
Watts
Total
***
Effective COPh EWT
Watts
W/W
°F
°C
Cond.
Temp.
°C
Flow LWT Delta T
Output
°F USGPM °F
L/s °C
°F
°C
Net
BTU/Hr
Watts
26.0 15 16.8 22.3 3.7 29,901 6,451 2.34 104.0 125 16.8 110.1 6.1
51,458
-3.3 -9.4 1.060 -5.4 2.1 8,761 18.1 40.0 51.7 1.060 43.4 3.4
15,077
32.0 20 16.8 27.6 4.4 34,956 6,489
2.56 104.0
126 16.8 110.7 6.7
56,643
0.0 -6.7 1.060 -2.4 2.4 10,242 18.1 40.0 52.2 1.060 43.7 3.7
16,596
38.0 25 16.8 32.9 5.1 40,761 6,437
2.83 104.0
126 16.8 111.4 7.4
62,270
3.3 -3.9 1.060 0.5 2.8 11,943 18.0 40.0 52.2 1.060 44.1 4.1
18,245
44.0 30 16.8 38.2 5.8 46,150 6,313 3.12 104.0 126 16.8 112.0 8.0
67,235
6.7 -1.1 1.060 3.5 3.2 13,522 17.9 40.0 52.2 1.060 44.5 4.5
19,700
49.0 35 16.8 42.6 6.4 51,148 6,256 3.38 104.0 127 16.8 112.6 8.6
72,087
9.4 1.7 1.060 5.9 3.6 14,986 17.9 40.0 52.8 1.060 44.8 4.8
21,121
55.0 40 16.8 47.8 7.2 57,798 6,194 3.71 104.0 127 16.8 113.4 9.4
78,523
12.8 4.4 1.060 8.8 4.0 16,935 17.8 40.0 52.8 1.060 45.2 5.2
23,007
61.0 45 16.8 52.9 8.1 64,897 6,127 4.08 104.0 127 16.8 114.2 10.2 85,394
16.1 7.2 1.060 11.6 4.5 19,015 17.7 40.0 52.8 1.060 45.7 5.7
25,020
67.0 50 16.8 58.0 9.0 71,851 6,139
4.41 104.0
128 16.8 115.0 11.0 92,391
19.4 10.0 1.060 14.4
Compressor: ZP70KWE-PFV
5.0 21,052 17.6
208-3-60
40.0 53.3 1.060 46.1 6.1
27,070
01 JAN 2014 Page 59 001223MAN-04
ELECTRICAL TABLES
Table 24 - Heat Pump Electrical Information (208/230-1-60)
Model
Compressor Fan
RLA LRA RLA
In/Outdoor
Circulators
Max A
FLA MCA
Amps Amps
Max Fuse/
Breaker
Amps
Wire
Size ga
45 18.6 32.6 40 #8-3
55 23.6 41.3 50 #6-3
65 28.6 49.1 60 #6-3
75 30.4 52.3 60 #6-3
80* 35.7 59.4 70 #6-3
* Models are single stage
Table 25 - Heat Pump Electrical Information (208-3-60)
Model
Compressor Fan
RLA LRA RLA
In/Outdoor
Circulators
Max A
FLA MCA
Amps Amps
Max Fuse/
Breaker
Amps
Wire
Size ga
45 12.4 5.0 21.7 24.8 40 #8-4
55 15.0 7.0 26.8 30.6
50 #6-4
65 19.6 7.0 32.9 37.8 60 #6-4
75 21.2 7.0 35.5 40.8 60 #6-4
80* 25.0 7.0 39.8 46.1
60 #6-4
* Models are single stage
Table 26 - Heat Pump Electrical Information (220-1-50)
Model
Compressor Fan
RLA LRA RLA
In/Outdoor
Circulators
Max A
FLA MCA
Amps Amps
Max Fuse/
Breaker
Amps
Wire
Size ga
45* 15.0 67 3.5 5.0 24.3 28.1 40 #12-2
55* 17.7 98 4.0 7.0 29.5 33.9 50 #10-2
65* 27.3 7.0 40.6 47.4
60 #10-2
75* 32.9 7.0 47.2 55.4
80 #8-2
* Models are single stage
Table 27 - Heat Pump Electrical Information (380-3-50)
Model
Compressor Fan
RLA LRA RLA
In/Outdoor
Circulators
Max A
FLA MCA
Amps Amps
Max Fuse/
Breaker
Amps
Wire
Size ga
45 5.0 5.0 14.3 15.6 20 #12-4
55 7.1 7.0 18.9 20.7 25 #10-4
65 10.0 7.0 23.3 25.8 30 #10-4
75 10.9 7.0 25.2 27.9 40 #8-4
80* 11.8 74 7.0 7.0 26.6 29.6
40 #8-4
* Models are single stage
Heater Size
Size
(kW)
TABLE 28 - Plenum Heater Electrical Information
Electrical 230-1-60 Electrical 208-1-60 Electrical 220-1-50
Current
(A)
Breaker
(A)
Wire
Size
Current
(A)
Breaker
(A)
Wire
Size
Current
(A)
Breaker
(A)
Wire
Size
001223MAN-04
15 63 80 #4 54 70 #4 57 80 #4
Page 60 01 JAN 2014
AQUASTAT CONNECTION DIAGRAM
01 JAN 2014 Page 61 001223MAN-04
ELECTRICAL DIAGRAMS (208/230-1-60)
001223MAN-04 Page 62 01 JAN 2014
ELECTRICAL DIAGRAMS (208/230-1-60) - continued
01 JAN 2014 Page 63 001223MAN-04
CASE DETAILS—TOP VIEWS
Top View (Size 45)
Top View (Size 55-80)
001223MAN-04 Page 64 01 JAN 2014
CASE DETAILS—LEFT RETURN
Front View—Left Return Right Side View—Left Return (Size 45)
01 JAN 2014
Left Side View– Left Return
Page 65
Right Side View—Left Return (Size 55-80)
001223MAN-04
CASE DETAILS—RIGHT RETURN
Front View—Right Return Left Side View—Right Return (Size 45)
Right Side View– Right Return
001223MAN-04 Page 66
Left Side View—Right Return (Size 55-80)
01 JAN 2014
APPENDIX A - Control Board Specifications
01 JAN 2014 Page 67 001223MAN-04
Model
45
55
65
75
80
APPENDIX B - ECM Fan Airflow Tables
CFM
1200
1500
1900
2100
2400
Full
NOMINAL AIRFLOW SETTING (MED)
STAGE 2
Reduced* Full
STAGE 1
Reduced*
L/s
566
708
897
991
1133
CFM
1020
1275
1615
1785
2040
L/s
481
602
762
842
963
CFM
1030
1240
1540
1660
N/A
L/s
486
585
727
783
N/A
CFM
876
1054
1309
1411
N/A
L/s
413
497
618
666
N/A
FAN ONLY (Recirculation)
Full Reduced*
CFM
672
840
1064
1176
1344
L/s
317
396
502
555
634
CFM
571
714
904
1000
1142
L/s
270
337
427
472
539
Model
45
55
65
75
80
CFM
1128
1410
1786
1974
2256
Full
-6% AIRFLOW SETTING (LOW)
STAGE 2
Reduced* Full
STAGE 1
Reduced*
L/s
532
665
843
932
1065
CFM
959
1199
1518
1678
1918
L/s
453
566
716
792
905
CFM
968
1166
1448
1560
N/A
L/s
457
550
683
736
N/A
CFM
823
991
1230
1326
N/A
L/s
388
468
581
626
N/A
FAN ONLY (Recirculation)
Full Reduced*
CFM
632
790
1000
1105
1263
L/s
298
373
472
522
596
CFM
537
671
850
940
1074
L/s
253
317
401
443
507
Model
45
55
65
75
80
CFM
1272
1590
2014
2226
2544
Full
+6% AIRFLOW SETTING (HIGH)
STAGE 2
Reduced* Full
STAGE 1
Reduced*
L/s
600
750
951
1051
1201
CFM
1081
1352
1712
1892
2162
L/s
510
638
808
893
1021
CFM
1092
1314
1632
1760
N/A
L/s
515
620
770
830
N/A
CFM
928
1117
1388
1496
N/A
L/s
438
527
655
706
N/A
FAN ONLY (Recirculation)
Full Reduced*
CFM
712
890
1128
1400
1425
L/s
336
420
532
661
672
CFM
605
757
959
1190
1211
L/s
286
357
452
562
572
Model
45
55
65
75
80
CFM
1344
1680
2128
2352
2688
Full
+12% AIRFLOW SETTING (MAX)
STAGE 2
Reduced* Full
STAGE 1
Reduced*
L/s
634
793
1004
1110
1269
CFM
1142
1428
1809
1999
2285
L/s
539
674
854
944
1078
CFM
1154
1389
1725
1859
N/A
L/s
544
655
814
877
N/A
CFM
981
1180
1466
1580
N/A
L/s
463
557
692
746
N/A
FAN ONLY (Recirculation)
Full Reduced*
CFM
753
941
1192
1317
1505
L/s
355
444
562
622
710
CFM
640
800
1013
1120
1279
L/s
302
377
478
528
604
NOTES: Unit sizes 45 and 55 nominal value up to 0.50 inH2o, sizes 65, 75 and 80 up to 0.70inH2o
*To obtain the REDUCED airflow values use a dry contact to connect AR1 to AR2 on the terminal strip
001223MAN-04
INFORMATION TAKEN FROM DOCUMENT 000527INF-04
Page 68 01 JAN 2014
01 JAN 2014
THIS PAGE INTENTIONALLY LEFT BLANK
Page 69 001223MAN-04
001223MAN-04
THIS PAGE INTENTIONALLY LEFT BLANK
Page 70 01 JAN 2014
01 JAN 2014
THIS PAGE INTENTIONALLY LEFT BLANK
Page 71 001223MAN-04
LIMITED EXPRESS WARRANTY
It is expressly understood that unless a statement is specifically identified as a warranty, statements made by Maritime Geothermal Ltd., a corporation registered in New
Brunswick, Canada, (“MG”) or its representatives, relating to MG’s products, whether oral, written or contained in any sales literature, catalogue or agreement, are not express warranties and do not form a part of the basis of the bargain, but are merely MG’s opinion or commendation of MG’s products.
EXCEPT AS SPECIFICALLY SET FORTH HEREIN, THERE IS NO EXPRESS WARRANTY AS TO ANY OF MG’S PRODUCTS. MG MAKES NO WARRANTY AGAINST
LATENT DEFECTS. MG MAKES NO WARRANTY OF MERCHANTABILITY OF THE GOODS OR OF THE FITNESS OF THE GOODS FOR ANY PARTICULAR PURPOSE.
LIMITED EXPRESS RESIDENTIAL WARRANTY - PARTS
MG warrants its Residential Class products, purchased and retained in the United States of America and Canada, to be free from defects in material and workmanship under normal use and maintenance as follows:
(1) Air conditioning, heating and/or heat pump units built or sold by MG (“MG Units”) for five (5) years from the Warranty Inception Date (as defined below).
(2) Thermostats, auxiliary electric heaters and geothermal pumping modules built or sold by MG, when installed with MG Units, for five (5) years from the Warranty Inception
Date (as defined below).
(3) Sealed refrigerant circuit components of MG Units (which components only include the compressor, refrigerant to air/water heat exchangers, reversing valve body and
refrigerant metering device) for ten (10) years from the Warranty Inception Date (as defined below).
(4) Other accessories and parts built or sold by MG, when installed and purchased with MG Units, for five (5) years from the date of shipment from MG.
(5) Other accessories, when purchased separately, for (1) year from the date of shipment from MG.
The “Warranty Inception Date” shall be the date of original unit installation, as per the date on the installation Startup Record or six (6) months from date of unit shipment from MG, whichever comes first.
To make a claim under this warranty, parts must be returned to MG in Petitcodiac, New Brunswick, freight prepaid, no later than ninety (90) days after the date of the failure of the part. If MG determines the part to be defective and within MG’s Limited Express Residential Warranty, MG shall, when such part has been either replaced or repaired, return such to a factory recognized distributor, dealer or service organization, freight prepaid. The warranty on any part repaired or replaced under warranty expires at the end of the original warranty period.
LIMITED EXPRESS RESIDENTIAL WARRANTY - LABOUR
This Limited Express Residential Labour Warranty shall cover the labour incurred by MG authorized service personnel in connection with the installation of a new or repaired warranty part that is covered by this Limited Express Residential Warranty only to the extent specifically set forth in the current labour allowance schedule "A" provided by MG’s
Warranty Department and only as follows:
(1) MG Units for two (2) years from the Warranty Inception Date.
(2) Thermostats, auxiliary electric heaters and geothermal pump modules built or sold by MG, when installed with MG Units, for two (2) years from the Warranty Inception Date.
(3) Sealed refrigerant circuit components of MG Units (which components only include the compressor, refrigerant to air/water heat exchangers, reversing valve body and
refrigerant metering device) for five (5) years from the Warranty Inception Date.
Labour costs are not covered by this Limited Express Residential Warranty to the extent they exceed the amount allowed under said allowance schedule, they are not specifically provided for in said allowance schedule, they are not the result of work performed by MG authorized service personnel, they are incurred in connection with a part not covered by this Limited Express Residential Warranty, or they are incurred more than the time periods set forth in this paragraph after the Warranty Inception Date.
This warranty does not cover and does not apply to:
(1) Air filters, fuses, refrigerant, fluids, oil.
(2) Products relocated after initial installation.
(3) Any portion or component of any system that is not supplied by MG, regardless of the cause of the failure of such portion or component.
(4) Products on which the unit identification tags or labels have been removed or defaced.
(5) Products on which payment to MG, or to the owner’s seller or installing contractor, is in default.
(6) Products subjected to improper or inadequate installation, maintenance, repair, wiring or voltage conditions.
(7) Products subjected to accident, misuse, negligence, abuse, fire, flood, lightning, unauthorized alteration, misapplication, contaminated or corrosive liquid or air supply,
operation at abnormal air or liquid temperatures or flow rates, or opening of the refrigerant circuit by unqualified personnel.
(8) Mold, fungus or bacteria damage
(9) Corrosion or abrasion of the product.
(10) Products supplied by others.
(11) Products which have been operated in a manner contrary to MG’s printed instructions.
(12) Products which have insufficient performance as a result of improper system design or improper application, installation, or use of MG’s products.
(13) Electricity or fuel, or any increases or unrealized savings in same, for any reason whatsoever.
Except for the limited labour allowance coverage set forth above, MG is not responsible for:
(1) The costs of fluids, refrigerant or system components supplied by others, or associated labour to repair or replace the
same, which is incurred as a result of a defective part covered by MG’s Limited Residential Warranty.
(2) The costs of labour, refrigerant, materials or service incurred in diagnosis and removal of the defective part, or in obtaining
and replacing the new or repaired part.
(3) Transportation costs of the defective part from the installation site to MG, or of the return of that part if not covered by
MG’s Limited Express Residential Warranty.
(4) The costs of normal maintenance.
This Limited Express Residential Warranty applies to MG Residential Class products manufactured on or after February 15, 2010. MG’S LIABILITY UNDER THE TERMS OF
THIS LIMITED WARRANTY SHALL APPLY ONLY TO THE MG UNITS REGISTERED WITH MG THAT BEARS THE MODEL AND SERIAL NUMBERS STATED ON THE
INSTALLATION START UP RECORD, AND MG SHALL NOT, IN ANY EVENT, BE LIABLE UNDER THE TERMS OF THIS LIMITED WARRANTY UNLESS THIS
INSTALLATION START UP RECORD HAS BEEN ENDORSED BY OWNER & DEALER/INSTALLER AND RECIEVED BY MG LIMITED WITHIN 90 DAYS OF START UP.
Limitation: This Limited Express Residential Warranty is given in lieu of all other warranties. If, not withstanding the disclaimers contained herein, it is determined that other warranties exist, any such express warranty, including without imitation any express warranties or any implied warranties of fitness for particular purpose and merchantability, shall be limited to the duration of the Limited Express Residential Warranty.
LIMITATION OF REMEDIES In the event of a breach of the Limited Express Residential Warranty, MG will only be obligated at MG’s option to repair the failed part or unit, or to furnish a new or rebuilt part or unit in exchange for the part or unit which has failed. If after written notice to MG’s factory in Petitcodiac, New Brunswick of each defect, malfunction or other failure, and a reasonable number of attempts by MG to correct the defect, malfunction or other failure, and the remedy fails of its essential purpose, MG shall refund the purchase price paid to MG in exchange for the return of the sold good(s). Said refund shall be the maximum liability of MG. THIS REMEDY IS THE SOLE AND
EXCLUSIVE REMEDY OF THE BUYER OR PURCHASER AGAINST MG FOR BREACH OF CONTRACT, FOR THE BREACH OF ANY WARRANTY OR FOR MG’S
NEGLIGENCE OR IN STRICT LIABILITY.
LIMITATION OF LIABILITY MG shall have no liability for any damages if MG’s performance is delayed for any reason or is prevented to any extent by any event such as, but not limited to: any war, civil unrest, government restrictions or restraints, strikes, or work stoppages, fire, flood, accident, shortages of transportation, fuel, material, or labour, acts of God or any other reason beyond the sole control of MG. MG EXPRESSLY DISCLAIMS AND EXCLUDES ANY LIABILITY FOR CONSEQUENTIAL OR INCIDENTAL
DAMAGE IN CONTRACT, FOR BREACH OF ANY EXPRESS OR IMPLIED WARRANTY, OR IN TORT, WHETHER FOR MG’s NEGLIGENCE OR AS STRICT LIABILITY.
OBTAINING WARRANTY PERFORMANCE Normally, the dealer or service organization who installed the products will provide warranty performance for the owner. Should the installer be unavailable, contact any MG recognized distributor, dealer or service organization. If assistance is required in obtaining warranty performance, write or call: Maritime
Geothermal Ltd • Customer Service • PO Box 2555 • Petitcodiac, New Brunswick E4Z 6H4 • (506) 756
‐8135 • or e-mail to [email protected] NOTE: Some states or Canadian provinces do not allow limitations on how long an implied warranty lasts, or the limitation or exclusions of consequential or incidental damages, so the foregoing exclusions and limitations may not apply to you. This warranty gives you specific legal rights, and you may also have other rights which vary from state to state and from Canadian province to
Canadian province. Please refer to the MG Installation, Installation and Service Manual for operating and maintenance instructions.
An extended warranty option is also available. Please contact Maritime Geothermal Ltd. via the contact information in the previous paragraph for more information.
001223MAN-04 Page 72 01 JAN 2014
advertisement
* Your assessment is very important for improving the workof artificial intelligence, which forms the content of this project