FloAire Modular Packaged Unit Installation Instructions


Add to my manuals
6 Pages

advertisement

FloAire Modular Packaged Unit Installation Instructions | Manualzz

24ABB

Baset Series Air Conditioners

with Puronr Refrigerant

1---1/2 To 5 Nominal Tons (Sizes 18 to 61)

Installation Instructions

SAFETY CONSIDERATIONS

Improper installation, adjustment, alteration, service, maintenance, or use can cause explosion, fire, electrical shock, or other conditions which may cause death, personal injury, or property damage. Consult a qualified installer, service agency, or your distributor or branch for information or assistance. The qualified installer or agency must use factory--authorized kits or accessories when modifying this product. Refer to the individual instructions packaged with the kits or accessories when installing.

Follow all safety codes. Wear safety glasses, protective clothing, and work gloves. Use quenching cloth for brazing operations.

Have fire extinguisher available. Read these instructions thoroughly and follow all warnings or cautions included in literature and attached to the unit. Consult local building codes and current editions of the National Electrical Code ( NEC ) NFPA 70.

In Canada, refer to current editions of the Canadian electrical code

CSA 22.1.

Recognize safety information. This is the safety--alert symbol

When you see this symbol on the unit and in instructions or manuals, be alert to the potential for personal injury. Understand these signal words; DANGER, WARNING, and CAUTION. These words are used with the safety--alert symbol. DANGER identifies the most serious hazards which will result in severe personal injury or death. WARNING signifies hazards which could result in personal injury or death. CAUTION is used to identify unsafe practices which would result in minor personal injury or product and property damage. NOTE is used to highlight suggestions which will result in enhanced installation, reliability, or operation.

!

WARNING

ELECTRICAL SHOCK HAZARD

Failure to follow this warning could result in personal injury or death.

Before installing, modifying, or servicing system, main electrical disconnect switch must be in the OFF position.

There may be more than 1 disconnect switch. Lock out and tag switch with a suitable warning label.

INSTALLATION INSTRUCTIONS

NOTE: In some cases noise in the living area has been traced to gas pulsations from improper installation of equipment.

1. Locate unit away from windows, patios, decks, etc. where unit operation sound may disturb customer.

2. Ensure that vapor and liquid tube diameters are appropriate for unit capacity.

3. Run refrigerant tubes as directly as possible by avoiding unnecessary turns and bends.

4. Leave some slack between structure and unit to absorb vibration.

5. When passing refrigerant tubes through the wall, seal opening with RTV or other pliable silicon--based caulk. (See Fig.

1.)

6. Avoid direct tubing contact with water pipes, duct work, floor joists, wall studs, floors, and walls.

7. Do not suspend refrigerant tubing from joists and studs with a rigid wire or strap which comes in direct contact with tubing.(See Fig. 1.)

8. Ensure that tubing insulation is pliable and completely surrounds vapor tube.

9. When necessary, use hanger straps which are 1 in. (25.4

mm) wide and conform to shape of tubing insulation. (See

Fig. 1.)

10. Isolate hanger straps from insulation by using metal sleeves bent to conform to shape of insulation.

NOTE: Avoid contact between tubing and structure

OUTDOOR WALL INDOOR WALL

CAULK

LIQUID TUBE

INSULATION

THROUGH THE WALL

HANGER STRAP

(AROUND VAPOR

TUBE ONLY)

VAPOR TUBE

JOIST

INSULATION

VAPOR TUBE

1” (25.4 mm) MIN.

LIQUID TUBE

SUSPENSION

A94026

Fig. 1 -- Piping Installation

The outdoor unit contains system refrigerant charge for operation with AHRI rated indoor unit when connected by 15 ft. (4.57 m) of field--supplied or factory accessory tubing. For proper unit operation, check refrigerant charge using charging information located on control box cover and/or in the Check Charge section of this instruction.

IMPORTANT: Maximum liquid--line size is 3/8--in. OD for all residential applications including long line.

IMPORTANT: Always install the factory--supplied liquid--line filter drier. If replacing the filter drier, refer to Product Data Digest for appropriate part number. Obtain replacement filter driers from your distributor or branch.

INSTALLATION

Check Equipment and Job Site

UNPACK UNIT

Move to final location. Remove carton taking care not to damage unit.

Inspect Equipment

File claim with shipping company prior to installation if shipment is damaged or incomplete. Locate unit rating plate on unit corner panel. It contains information needed to properly install unit.

Check rating plate to be sure unit matches job specifications.

Install on a Solid, Level Mounting Pad

If conditions or local codes require the unit be attached to pad, tie down bolts should be used and fastened through knockouts provided in unit base pan. Refer to unit mounting pattern in Fig. 2 to determine base pan size and knockout hole location.

For hurricane tie downs, contact local distributor for details and PE

(Professional Engineer) certification, if required by local authorities.

On rooftop applications, mount on level platform or frame. Place unit above a load--bearing wall and isolate unit and tubing set from structure. Arrange supporting members to adequately support unit and minimize transmission of vibration to building. Consult local codes governing rooftop applications.

Roof mounted units exposed to winds may require wind baffles.

Consult the Application Guideline and Service Manual --

Residential Split System Air Conditioners and Heat Pumps for wind baffle construction.

NOTE: Unit must be level to within ±2_ (±3/8 in./ft ,.±9.5 mm/m) per compressor manufacturer specifications.

Clearance Requirements

When installing, allow sufficient space for airflow clearance, wiring, refrigerant piping, and service. Allow 24 in. (609.6 mm) clearance to service end of unit and 48 in. (1219.2 mm) (above unit. For proper airflow, a 6--in. (152.4 mm) clearance on 1 side of unit and 12--in. (304.8 mm) on all remaining sides must be maintained. Maintain a distance of 24 in. (609.6 mm) between units or 18 in. (457.2 mm) if no overhang within 12 ft. (3.66 m)

Position so water, snow, or ice from roof or eaves cannot fall directly on unit.

NOTE: 18” (457.2 mm) clearance option described above is approved for outdoor units with wire grille coil guard only.

Units with louver panels require 24” (609.6 mm) between units.

On rooftop applications, locate unit at least 6 in. (152.4 mm) above roof surface.

Operating Ambient

The minimum outdoor operating ambient in cooling mode without accessory is 55 _F (12.78 _C), and the maximum outdoor operating ambient in cooling mode is 125_F (51.67 _C).

Make Piping Connections

!

WARNING

PERSONAL INJURY AND ENVIRONMENTAL

HAZARD

Failure to follow this warning could result in personal injury or death.

Relieve pressure and recover all refrigerant before system repair or final unit disposal. Use all service ports and open all flow--control devices, including solenoid valves.

Federal regulations require that you do not vent refrigerant to the atmosphere. Recover during system repair or final unit disposal.

!

CAUTION

UNIT DAMAGE HAZARD

Failure to follow this caution may result in equipment damage or improper operation.

If ANY refrigerant tubing is buried, provide a 6--in. vertical rise at service valve. Refrigerant tubing lengths up to 36--in.

may be buried without further special consideration. Do not bury lines more than 36--in. (914.4 mm).

3/8---in. (9.53 mm) Dia.

Tiedown Knockouts in

Basepan(2) Places

UNIT BASE PAN

Dimension in. (mm)

23---1/2 X 23---1/2

(596.9 X 596.9)

26 X 26

(660.4 X 660.4)

31–1/2 X 31–1/2

(800.1 X 800.1)

35 X 35

(889 X 889)

View From Top

TIEDOWN KNOCKOUT LOCATIONS in. (mm)

A B C

7---13/16 (198.4) 4–7/16 (112.7) 18–1/16 (458.8)

9–1/8 (231.8)

9–1/8 (231.8)

9–1/8 (231.8)

4–7/16 (112.7) 21–1/4 (539.8)

6–9/16 (166.7) 24–11/16 (627.1)

6–9/16 (166.7) 28–7/16 (722.3)

A05177

Fig. 2 -- Tiedown Knockout Locations

Outdoor units may be connected to indoor section using accessory tubing package or field--supplied refrigerant grade tubing of correct size and condition. Rated tubing diameters shown in Table 1 are recommended up to 80 ft. (24.38 m). See Product Data for acceptable alternate vapor diameters and associated capacity losses.

For tubing requirements beyond 80 ft. (24.38 m), substantial capacity and performance losses can occur. Following the recommendations in the Longline Guideline will reduce these losses. Refer to Table 1 for field tubing diameters. Refer to Table 2 for accessory requirements.

There are no buried--line applications greater than 36--in. (914.4

mm) allowed.

If refrigerant tubes or indoor coil are exposed to atmosphere, they must be evacuated to 500 microns to eliminate contamination and moisture in the system.

Outdoor Unit Connected to Factory Approved Indoor

Unit

Outdoor unit contains correct system refrigerant charge for operation with factory approved AHRI rated indoor unit when connected by 15 ft. (4.57 m) of field--supplied or factory--accessory tubing, and factory supplied filter drier. Check refrigerant charge for maximum efficiency.

Refrigerant Tubing Connection Outdoor

Connect vapor and liquid tubes to fittings on vapor and liquid service valves (see Table 1.) Use refrigerant grade tubing

2

Sweat Connection

!

CAUTION

UNIT DAMAGE HAZARD

Failure to follow this caution may result in equipment damage or improper operation.

Service valves must be wrapped in a heat--sinking material such as a wet cloth while brazing.

Use refrigeration grade tubing. Service valves are closed from factory and ready for brazing. After wrapping service valve with a wet cloth, braze sweat connections using industry accepted methods and materials. Consult local code requirements.

Refrigerant tubing and indoor coil are now ready for leak testing.

This check should include all field and factory joints.

Table 1 – Refrigerant Connections and Recommended Liquid and Vapor Tube Diameters (In.)

UNIT SIZE (SERIES)

18, 24 (Series 0)

18, 24 (Series 1)

30

36 (Series 0)

36 (Series 1)

42, 48

60

24ABB3

LIQUID

Connection

& Max. Tube

Diameter

3/8

3/8

3/8

3/8

3/8

3/8

3/8

RATED VAPOR*

Connection

Diameter

5/8

3/4

3/4

3/4

7/8

7/8

7/8

Tube

Diameter

5/8

3/4

3/4

3/4

7/8

7/8

1---1/8

UNIT SIZE (SERIES)

24ABB4

LIQUID

Connection

& Max. Tube

Diameter

RATED VAPOR*

Connection

Diameter

Tube

Diameter

18, 24

30, 36

42, 48, 49

3/8

3/8

3/8

5/8

3/4

7/8

5/8

3/4

7/8

60, 61 3/8 7/8 1---1/8

* Units are rated with 25 ft. (7.6 m) of lineset. See Product Data sheet for performance data when using different size and length linesets.

Notes:

1. Do not apply capillary tube or fixed orifice indoor coils to these units.

2. For Tubing Set lengths between 80 and 200 ft. (24.38 and 60.96 m) horizontal or 35 ft. (10.7 m) vertical differential 250 ft. (76.2 m) Total

Equivalent Length), refer to the Residential Piping and Longline Guide line--- Air Conditioners and Heat Pumps using Puron refrigerant.

3. For alternate liquid line options on 18---42 size units, see Product Data or

Residential Piping and Application Guideline

Install Liquid--Line Filter Drier Indoor

!

CAUTION

UNIT DAMAGE HAZARD

Failure to follow this caution may result in equipment damage or improper operation.

1. Installation of filter drier in liquid line is required.

2. Filter drier must be wrapped in a heat--sinking material such as a wet cloth while brazing.

Refer to Fig. 3 and install filter drier as follows:

1. Braze 5--in. liquid tube to the indoor coil.

2. Wrap filter drier with damp cloth.

3. Braze filter drier to above 5--in. (127 mm) liquid tube.

Flow arrow must point towards indoor coil.

4. Connect and braze liquid refrigerant tube to the filter drier.

A05178

Fig. 3 -- Liquid Line Filter Drier

Evacuate Refrigerant Tubing and Indoor Coil

!

CAUTION

UNIT DAMAGE HAZARD

Failure to follow this caution may result in equipment damage or improper operation.

Never use the system compressor as a vacuum pump.

Refrigerant tubes and indoor coil should be evacuated using the recommended deep vacuum method of 500 microns. The alternate triple evacuation method may be used (see triple evacuation procedure in service manual). Always break a vacuum with dry nitrogen.

Deep Vacuum Method

The deep vacuum method requires a vacuum pump capable of pulling a vacuum of 500 microns and a vacuum gage capable of accurately measuring this vacuum depth. The deep vacuum method is the most positive way of assuring a system is free of air and liquid water. A tight dry system will hold a vacuum of 1000 microns after approximately 7 minutes. See Fig. 4.

5000

4500

4000

3500

3000

CRONS 2500

2000

1500

1000

500

LEAK IN

SYSTEM

VACUUM TIGHT

TOO WET

TIGHT

DRY SYSTEM

0 1 2 3 4 5 6 7

MINUTES

A95424

A95424

Fig. 4 -- Deep Vacuum Graph

Final Tubing Check

IMPORTANT: Check to be certain factory tubing on both indoor and outdoor unit has not shifted during shipment. Ensure tubes are not rubbing against each other or any sheet metal or wires. Pay close attention to feeder tubes, making sure wire ties on feeder tubes are secure and tight.

3

Table 2 – Accessory Usage

ACCESSORY

REQUIRED FOR LOW---AMBIENT

COOLING APPLICATIONS

(Below 55°F/12.8_C)

REQUIRED FOR LONG LINE

APPLICATIONS*

REQUIRED FOR

SEA COAST

APPLICATIONS

(Within 2 miles/3.22 km)

Ball Bearing Fan Motor

Compressor Start Assist Capacitor and Relay

Crankcase Heater

Evaporator Freeze Thermostat

Yes{

Yes

Yes

Yes

No

Yes

Yes

No

No

No

No

No

Hard Shut---Off TXV

Liquid Line Solenoid Valve

Motor Master ® or Low---ambient Pressure Switch

Support Feet

Yes

No

Yes

Recommended

Yes

No

No

No

Yes

No

No

Recommended

Winter Start Control Yes No No

* For tubing line sets between 80 and 200 ft. (24.38 and 60.96 m) and/or 35 ft. (10.7 m) vertical differential, refer to Residential Split---System Longline

Application Guideline.

{

Additional requirement for Low---Ambient Controller (full modulation feature) MotorMasterr Control.

Make Electrical Connections

Be sure field wiring complies with local and national fire, safety, and electrical codes, and voltage to system is within limits shown on unit rating plate. Contact local power company for correction of improper voltage. See unit rating plate for recommended circuit protection device.

NOTE: Operation of unit on improper line voltage constitutes abuse and could affect unit reliability. See unit rating plate. Do not install unit in system where voltage may fluctuate above or below permissible limits.

NOTE: Use copper wire only between disconnect switch and unit.

NOTE: Install branch circuit disconnect of adequate size per NEC to handle unit starting current. Locate disconnect within sight from and readily accessible from unit, per Section 440--14 of NEC.

Route Ground and Power Wires

Remove access panel to gain access to unit wiring. Extend wires from disconnect through power wiring hole provided and into unit control box.

!

WARNING

ELECTRICAL SHOCK HAZARD

Failure to follow this warning could result in personal injury or death.

The unit cabinet must have an uninterrupted or unbroken ground to minimize personal injury if an electrical fault should occur. The ground may consist of electrical wire or metal conduit when installed in accordance with existing electrical codes.

Connect Ground and Power Wires

Connect ground wire to ground connection in control box for safety. Connect power wiring to contactor as shown in Fig. 5.

DISCONNECT

PER N.E.C. AND/OR

LOCAL CODES

CONTACTOR

Use No. 18 AWG color--coded, insulated (35_C minimum) wire. If thermostat is located more than 100 ft. (30.48 m) from unit, as measured along the control voltage wires, use No. 16 AWG color--coded wire to avoid excessive voltage drop.

All wiring must be NEC Class 1 and must be separated from incoming power leads.

Use furnace transformer, fan coil transformer, or accessory transformer for control power, 24v/40va minimum.

NOTE: Use of available 24v accessories may exceed the minimum 40va power requirement. Determine total transformer loading and increase the transformer capacity or split the load with an accessory transformer as required.

Final Wiring Check

IMPORTANT: Check factory wiring and field wire connections to ensure terminations are secured properly. Check wire routing to ensure wires are not in contact with tubing, sheet metal, etc.

Compressor Crankcase Heater

When equipped with a crankcase heater, furnish power to heater a minimum of 24 hr before starting unit. To furnish power to heater only, set thermostat to OFF and close electrical disconnect to outdoor unit.

A crankcase heater is required if refrigerant tubing is longer than

80 ft. (24.38 m). Refer to the Application Guideline and Service

Manual Longline Section--Residential Split--System Air

Conditioners and Heat Pumps.

Install Electrical Accessories

Refer to the individual instructions packaged with kits or accessories when installing.

Start--Up

!

CAUTION

UNIT OPERATION AND SAFETY HAZARD

Failure to follow this caution may result in personal injury, equipment damage or improper operation.

S Do not overcharge system with refrigerant.

S

Do not operate unit in a vacuum or at negative pressure.

S Compressor dome temperatures may be hot.

FIELD POWER

WIRING

3 PHASE ONLY BLUE

FIELD GROUND

WIRING

GROUND

LUG

A94025

Fig. 5 -- Line Connections

Connect Control Wiring

Route 24--v control wires through control wiring grommet and connect leads to control wiring (See Fig. 7). Refer to Installation

Instructions packaged with thermostat.

!

CAUTION

PERSONAL INJURY HAZARD

Failure to follow this caution may result in personal injury.

Wear safety glasses, protective clothing, and gloves when handling refrigerant and observe the following:

S

Front seating service valves are equipped with Schrader valves.

4

Follow these steps to properly start up system:

1. After system is evacuated, fully open liquid and vapor service valves.

2. Unit is shipped with valve stem(s) front seated (closed) and caps installed. Replace stem caps after system is opened to refrigerant flow. Replace caps finger--tight and tighten with wrench an additional 1/12 turn.

3. Close electrical disconnects to energize system.

4. Set room thermostat at desired temperature. Be sure set point is below indoor ambient temperature.

5. Set room thermostat to COOL and fan control to ON or

AUTO mode, as desired. Operate unit for 15 minutes.

Check system refrigerant charge.

3--Phase Monitor

In 3--phase units a small circuit board is factory installed to monitor line voltage. A small led will flash if a phase problem exists. See code descriptions on monitor. If LED is flashing, disconnect power to unit and interchange 2 field--wiring leads on unit contactor.

Fig. 6 -- 3--Phase Monitor Control

A00010

(Applies to 3--Phase Units Only)

Table 3 – Three--Phase Monitor LED Indicators

LED

OFF

FLASHING

ON

STATUS

No call for compressor operation

Reversed phase

Normal

!

CAUTION

UNIT DAMAGE HAZARD

Failure to follow this caution may result in equipment damage or improper operation.

Ensure compressor rotation is correct.

S 3--phase scroll compressors are rotation sensitive.

S

A flash LED on phase monitor indicates reverse rotation.

(See Table 3)

This will not allow contractor to be energized.

S Disconnect power to unit and interchange 2 field--wiring leads on unit contactor.

Sequence of Operation

Turn on power to indoor and outdoor units. Transformer is energized.

On a call for cooling, thermostat makes circuits R--Y and R--G.

Circuit R--Y energizes contactor, starting outdoor fan motor and compressor circuit. R--G energizes indoor unit blower relay, starting indoor blower motor on high speed.

When thermostat is satisfied, its contacts open, de--energizing contactor and blower relay. Compressor and motors stop.

If indoor unit is equipped with a time--delay relay circuit, the indoor blower will run an additional 90 seconds to increase system efficiency.

Check Charge

Factory charge amount and desired subcooling are shown on unit rating plate. Charging method is shown on information plate inside unit. To properly check or adjust charge, conditions must be favorable for subcooling charging. Favorable conditions exist when the outdoor temperature is between 70_F and 100_F

(21.11_C and 37.78_C), and the indoor temperature is between

70_F and 80_F (21.11_C and 26.67_C). Follow the procedure below:

Unit is factory charged for 15ft (4.57 m) of lineset. Adjust charge by adding or removing 0.6 oz/ft of 3/8 liquid line above or below

15ft (4.57 m) respectively.

For standard refrigerant line lengths (80 ft/24.38 m or less), allow system to operate in cooling mode at least 15 minutes. If conditions are favorable, check system charge by subcooling method. If any adjustment is necessary, adjust charge slowly and allow system to operate for 15 minutes to stabilize before declaring a properly charged system.

If the indoor temperature is above 80_F (26.67_C), and the outdoor temperature is in the favorable range, adjust system charge by weight based on line length and allow the indoor temperature to drop to 80_F (26.67_C) before attempting to check system charge by subcooling method as described above.

If the indoor temperature is below 70_F (21.11_C), or the outdoor temperature is not in the favorable range, adjust charge for line set length above or below 15ft (4.57 m) only. Charge level should then be appropriate for the system to achieve rated capacity. The charge level could then be checked at another time when the both indoor and outdoor temperatures are in a more favorable range.

NOTE: If line length is beyond 80 ft (24.38 m) or greater than 20 ft (6.10 m) vertical separation, See Long Line Guideline for special charging requirements.

Final Checks

IMPORTANT: Before leaving job, be sure to do the following:

1. Ensure that all wiring is routed away from tubing and sheet metal edges to prevent rub--through or wire pinching.

2. Ensure that all wiring and tubing is secure in unit before adding panels and covers. Securely fasten all panels and covers.

3. Tighten service valve stem caps to 1/12--turn past finger tight.

4. Leave Owner’s Manual with owner. Explain system operation and periodic maintenance requirements outlined in manual.

5. Fill out Dealer Installation Checklist and place in customer file.

CARE AND MAINTENANCE

For continuing high performance and to minimize possible equipment failure, periodic maintenance must be performed on this equipment.

Frequency of maintenance may vary depending upon geographic areas, such as coastal applications. See Owner’s Manual for information.

5

A/C

THERMOSTAT

Typical

FURNACE

AIR

CONDITIONER

A/C

THERMOSTAT

Typical

FAN COIL

AIR

CONDITIONER

24 VAC HOT R

24 VAC COM

HEAT STAGE 1

C

W/W1

COOL STAGE 1

INDOOR FAN

Y/Y2

G

R

C

W

Y

G

C

24 VAC HOT

24 VAC COM

R

C

R

C

W2

G

C

HEAT STAGE 1

COOL STAGE 1

INDOOR FAN

W/W1

Y/Y2

G

A02326

C

LEGEND

24-V FACTORY WIRING

24-V FIELD WIRING

FIELD SPLICE CONNECTION

CONTACTOR

A97368

Fig. 7 -- Generic Wiring Diagrams

(See Thermostat Installation Instruction for specific unit combinations)

PURONR (R--410A) REFRIGERANT QUICK REFERENCE GUIDE

S Puron refrigerant operates at 50--70 percent higher pressures than R--22. Be sure that servicing equipment and replacement components are designed to operate with Puron refrigerant

S Puron refrigerant cylinders are rose colored.

S Recovery cylinder service pressure rating must be 400 psig, DOT 4BA400 or DOT BW400.

S

Puron refrigerant systems should be charged with liquid refrigerant. Use a commercial type metering device in the manifold hose when charging into suction line with compressor operating

S

Manifold sets should be 700 psig high side and 180 psig low side with 550 psig low--side retard.

S Use hoses with 700 psig service pressure rating.

S Leak detectors should be designed to detect HFC refrigerant.

S Puron refrigerant, as with other HFCs, is only compatible with POE oils.

S Vacuum pumps will not remove moisture from oil.

S

Do not use liquid--line filter driers with rated working pressures less than 600 psig.

S Do not leave Puron suction line filter driers in line longer than 72 hours.

S Do not install a suction--line filter drier in liquid line.

S POE oils absorb moisture rapidly. Do not expose oil to atmosphere.

S

POE oils may cause damage to certain plastics and roofing materials.

S

Wrap all filter driers and service valves with wet cloth when brazing.

S A factory approved liquid--line filter drier is required on every unit.

S Do NOT use an R--22 TXV.

S If indoor unit is equipped with an R--22 TXV or piston metering device, it must be changed to a hard shutoff Puron TXV.

S Never open system to atmosphere while it is under a vacuum.

S

When system must be opened for service, recover refrigerant, evacuate then break vacuum with dry nitrogen and replace filter driers.

Evacuate to 500 microns prior to recharging.

S

Do not vent Puron refrigerant into the atmosphere.

S Do not use capillary tube coils.

S Observe all warnings, cautions, and bold text.

S All indoor coils must be installed with a hard shutoff Puron TXV metering device.

Copyright 2009 Carrier Corp. S 7310 W. Morris St. S Indianapolis, IN 46231 Printed in U.S.A.

Edition Date: 03/09

Manufacturer reserves the right to change, at any time, specifications and designs without notice and without obligations.

6

Catalog No: 24ABB---3SI

Replaces: 24ABB--- 2SI

advertisement

Was this manual useful for you? Yes No
Thank you for your participation!

* Your assessment is very important for improving the workof artificial intelligence, which forms the content of this project

Related manuals

advertisement