Instructions

8008H002 Ed.05

GB

2.1.2.- Configuration by temporal IP from MAC

Before setting a fixed IP or a DHCP, you have to set a temporary and available IP in the same range that your computer in order to configure the device. Insert the IP in the address field, check the checkbox set IP from MAC and, enter the MAC address shown on the permanent side label attached to the device, the format of which is 00:26:45:XX:XX:XX. Do the same with the Netmask and the

Gateway if necessary, and press Configuration

2.2.2.-IP by DHCP

Check the DHCP checkbox and leave the other fields in blank.

AKO-80080

Warnings

This document provides the instructions for use and describes the operation of the AKO-80080 device. If misplaced, the manual may be downloaded from the AKO web site: www.ako.com

2.1.3.-Configuration by IP

If you know the IP assigned by the router write it in the address field and press configuration button.

2.2.3.-Choose Protocol and Port

Set always ModbusTCP as protocol and 502 as port.

Disconnect the device from the power supply source before undertaking any maintenance, modification of connections, repairs, etc. If you suspect an operational fault in the unit or in its protection system, remove the unit from service.

The design of the unit makes it easy to replace in the event of a fault.

1.-Description

The AKO-80080 device is a serial physical environment to

Ethernet communications converter that uses TCP/IP communication packages.

Please connect the device to the Ethernet network to setup it properly.

2.-Communication

2.1.-Ethernet addressing

As the unit is connected to the master communication system by means of an IP connection, the addressing parameters must be configured. The configuration modes include the assignment of a fixed IP or configuration of a DHCP name. We recommend the use of a fixed IP.

We recommend using a fixed IP address, as this will be used by AKOnet to retrieve the data

2.1.1.-Ethernet address assignment

To configure the IP address configuration in any of the available formats, run the IPSetup.exe that you must download through this link: http://help.ako.com/assets/uploads/IPSetup.exe

Run IPSetup and select the AKO-80080 converter.

The device comes with DHCP activated as default parameter.

(If you know the IP you can skip the next step and go directly to 2.1.3 Configuration by IP).

2.2.-Configuration

You have to choose between: Fixed IP or IP by DHCP.

2.2.1.-Fixed IP

Insert the fixed IP in the IP address field, do the same with the

Netmask and the Gateway

2.2.4.-Other Fields

When you choose the Modbus Tcp the other fields get automatically the right values: 9600, 8,None & 1, as you can see in the picture.

2.2.5.-Tx Delay Rx Time

Set always TX delay in blank and RX as 250.

Ÿ Tx Delay: additional delay of the RS serial bus

Ÿ Rx Time: maximum bus waiting time

2.2.6.-Save changes

Once any change has been made to the aforementioned sections, the information must be saved using the

“Configure” button.

website.

those described on our slightly to vary available that might information is

Sant Pere de Ribes.

, S.A.L.

supply materials

Spain.

Sheets. Updated right to

Roquetes, 30-38 Avda.

AKO ELECTROMECÁNICA

08812

Technical reserve the in our

We www.ako.com

Tel.: +34 902 333 145

Barcelona

Fax: +34 938 934 054

3.-

Technical features

Power circuit

Single-phase (A1 – A2). . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 196 - 253 V~

Earth connection terminal. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Borne

Frequency . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 47 - 63 Hz

Maximum consumption . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9 VA

Working temperature . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . -10 - 60 ºC

Humidity (no condensation) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5 - 95 %

Mechanical features

Case material . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . UL94 - V0 self-extinguishing plastic

Unit protection degree . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . IP20

Dimensions (mm) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 35,4 x 73 x 84,68 mm (2 modules)

Weight . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 120 g

Maximum operating height . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2000 m

Network interface

Type . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Ethernet 10BaseT / 100BaseTX self-detecting

Connector. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . RJ45

Network Protocols - Accesses . . . . . . . . . . . . . . . . . . . . . . . TCP / UDP / Modbus/TCP - HTTP

Serial interface

Type . . . . . . . . . . . . . . . . . . . . . . . . . . . . RS-485 three-wires (A+ /S GND /B-) (RX/GND/TX)

Transmission speed (configurable) . . . . . . . . 1.2, 2.4, 4.8, 9.6,19.200, 34.8, 57.6, 115.2 bps

Data bits . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7, 8

Parity . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . No parity, odd, even

Stop bit . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1 or 2

LED symbols

Flashing power LED. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Powered unit and CPU activity

Flashing RX/TX. . . . . . . . . . . . . . . . . . . . . . . . . RS-485 frame delivery and reception activity

LINK/ACTIVITY . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Flashing: Activity in the Ethernet bus

. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Green: Speed 10/100 Mb/s

Standards IEC 60664, VDE 0110, UL 94, EN61010-1, EN55011, EN 61000-4-2, EN 61000-

4-3, 61000-4-11, EN 61000-6-4, EN 61000-6-2, EN 61000-6-1, EN 61000-6-3,

EN 61000-4-5, CE

Safety Installation category: Category III / EN61010 double-insulated electric shock protection class II. The unit must be connected to a power circuit protected with type gl fuses, in compliance with IEC 269, or type M, with values from 0.5 to 1A.

It must be fitted with a circuit breaker switch or equivalent device in order to be able to disconnect the unit from the power supply. The power supply cable must have a minimum cross-section of 1 mm .

If the unit is not operated according to the manufacturer's specifications, its guaranteed degree of protection may be compromised.

4.- Connections

CAM

Ctrl

SET

ESC

?

CAM

Regis

SET

ESC

?

AKO

Control

with communication

AKO

Control

with communication

Tr-

Tr+

GND

AKO-80080

Converter

1000 m

Maximum of 25 computers

Tr-

Tr+

GND

Ethernet

TCP/IP

Switch

AKO-80080

Converter

AKO-5012

LAN

AKO

Control

with communication

CAM

Alarm

PRO

Plus

The AKO-5012 web server supports up to 10 AKO-80080 converters and the AKO-5014 web server supports up to 2.

Terminating resistors are not required.

KEEP THIS DATA SHEET SAFE