Instructions
8008H002 Ed.05
GB
2.1.2.- Configuration by temporal IP from MAC
Before setting a fixed IP or a DHCP, you have to set a temporary and available IP in the same range that your computer in order to configure the device. Insert the IP in the address field, check the checkbox set IP from MAC and, enter the MAC address shown on the permanent side label attached to the device, the format of which is 00:26:45:XX:XX:XX. Do the same with the Netmask and the
Gateway if necessary, and press Configuration
2.2.2.-IP by DHCP
Check the DHCP checkbox and leave the other fields in blank.
AKO-80080
Warnings
This document provides the instructions for use and describes the operation of the AKO-80080 device. If misplaced, the manual may be downloaded from the AKO web site: www.ako.com
2.1.3.-Configuration by IP
If you know the IP assigned by the router write it in the address field and press configuration button.
2.2.3.-Choose Protocol and Port
Set always ModbusTCP as protocol and 502 as port.
Disconnect the device from the power supply source before undertaking any maintenance, modification of connections, repairs, etc. If you suspect an operational fault in the unit or in its protection system, remove the unit from service.
The design of the unit makes it easy to replace in the event of a fault.
1.-Description
The AKO-80080 device is a serial physical environment to
Ethernet communications converter that uses TCP/IP communication packages.
Please connect the device to the Ethernet network to setup it properly.
2.-Communication
2.1.-Ethernet addressing
As the unit is connected to the master communication system by means of an IP connection, the addressing parameters must be configured. The configuration modes include the assignment of a fixed IP or configuration of a DHCP name. We recommend the use of a fixed IP.
We recommend using a fixed IP address, as this will be used by AKOnet to retrieve the data
2.1.1.-Ethernet address assignment
To configure the IP address configuration in any of the available formats, run the IPSetup.exe that you must download through this link: http://help.ako.com/assets/uploads/IPSetup.exe
Run IPSetup and select the AKO-80080 converter.
The device comes with DHCP activated as default parameter.
(If you know the IP you can skip the next step and go directly to 2.1.3 Configuration by IP).
2.2.-Configuration
You have to choose between: Fixed IP or IP by DHCP.
2.2.1.-Fixed IP
Insert the fixed IP in the IP address field, do the same with the
Netmask and the Gateway
2.2.4.-Other Fields
When you choose the Modbus Tcp the other fields get automatically the right values: 9600, 8,None & 1, as you can see in the picture.
2.2.5.-Tx Delay Rx Time
Set always TX delay in blank and RX as 250.
Ÿ Tx Delay: additional delay of the RS serial bus
Ÿ Rx Time: maximum bus waiting time
2.2.6.-Save changes
Once any change has been made to the aforementioned sections, the information must be saved using the
“Configure” button.
website.
those described on our slightly to vary available that might information is
Sant Pere de Ribes.
, S.A.L.
supply materials
Spain.
Sheets. Updated right to
•
•
Roquetes, 30-38 Avda.
AKO ELECTROMECÁNICA
08812
Technical reserve the in our
We www.ako.com
Tel.: +34 902 333 145
Barcelona
Fax: +34 938 934 054
3.-
Technical features
Power circuit
Single-phase (A1 – A2). . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 196 - 253 V~
Earth connection terminal. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Borne
Frequency . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 47 - 63 Hz
Maximum consumption . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9 VA
Working temperature . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . -10 - 60 ºC
Humidity (no condensation) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5 - 95 %
Mechanical features
Case material . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . UL94 - V0 self-extinguishing plastic
Unit protection degree . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . IP20
Dimensions (mm) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 35,4 x 73 x 84,68 mm (2 modules)
Weight . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 120 g
Maximum operating height . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2000 m
Network interface
Type . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Ethernet 10BaseT / 100BaseTX self-detecting
Connector. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . RJ45
Network Protocols - Accesses . . . . . . . . . . . . . . . . . . . . . . . TCP / UDP / Modbus/TCP - HTTP
Serial interface
Type . . . . . . . . . . . . . . . . . . . . . . . . . . . . RS-485 three-wires (A+ /S GND /B-) (RX/GND/TX)
Transmission speed (configurable) . . . . . . . . 1.2, 2.4, 4.8, 9.6,19.200, 34.8, 57.6, 115.2 bps
Data bits . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7, 8
Parity . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . No parity, odd, even
Stop bit . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1 or 2
LED symbols
Flashing power LED. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Powered unit and CPU activity
Flashing RX/TX. . . . . . . . . . . . . . . . . . . . . . . . . RS-485 frame delivery and reception activity
LINK/ACTIVITY . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Flashing: Activity in the Ethernet bus
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Green: Speed 10/100 Mb/s
Standards IEC 60664, VDE 0110, UL 94, EN61010-1, EN55011, EN 61000-4-2, EN 61000-
4-3, 61000-4-11, EN 61000-6-4, EN 61000-6-2, EN 61000-6-1, EN 61000-6-3,
EN 61000-4-5, CE
Safety Installation category: Category III / EN61010 double-insulated electric shock protection class II. The unit must be connected to a power circuit protected with type gl fuses, in compliance with IEC 269, or type M, with values from 0.5 to 1A.
It must be fitted with a circuit breaker switch or equivalent device in order to be able to disconnect the unit from the power supply. The power supply cable must have a minimum cross-section of 1 mm .
If the unit is not operated according to the manufacturer's specifications, its guaranteed degree of protection may be compromised.
4.- Connections
CAM
Ctrl
SET
ESC
?
CAM
Regis
SET
ESC
?
AKO
Control
with communication
AKO
Control
with communication
Tr-
Tr+
GND
AKO-80080
Converter
1000 m
Maximum of 25 computers
Tr-
Tr+
GND
Ethernet
TCP/IP
Switch
AKO-80080
Converter
AKO-5012
LAN
AKO
Control
with communication
CAM
Alarm
PRO
Plus
The AKO-5012 web server supports up to 10 AKO-80080 converters and the AKO-5014 web server supports up to 2.
Terminating resistors are not required.
KEEP THIS DATA SHEET SAFE
FOR FUTURE REFERENCE